Second Harmonic Method for Discrimination between Inrush and Fault Current in Power Transformer

Page 1

IJSRD - International Journal for Scientific Research & Development| Vol. 4, Issue 02, 2016 | ISSN (online): 2321-0613

Second Harmonic Method for Discrimination between in Rush and Fault Current in Power Transformer Parth Thummar1 Ghetiya Rahul2 Department of Electrical Engineering 1,2 Marwadi Education Foundations Group of Institution, Rajkot India 1,2

Abstract— Transformers transform electric energy. There are varieties of transformer and used for many different purposes. They are nearly inbuilt into every electric/electronic device around us. Power transformers are essential components in power systems. The purpose of this method to identify inrush current and Fault current in power transformer or to avoid the needless by magnetizing inrush current. The performance of this method is demonstrated by simulation of different faults and switching conditions on a power transformer using MATLAB software. Key words: Transformer, harmonics, Inrush I. INTRODUCTION As an essential element of electric power systems, the power transformer plays a key role in the safe operation of the system. Inadequate and inaccurate protection of this element can lead to a major fault. A damaged transformer needs time for repair or replacement. By accurate protection, the damage can be eliminated or minimized. A fault or unwanted outage in the power transformer leads to disconnection of supply to a large portion of the system; as a result, that the operation of transformer protection be dependable, secure and fast [1], [2]. Differential protection is established as the main protection for transformer for many years due to its simple principle of operation and sensitivity. However, a key problem of differential protection is accurate and rapid discrimination of magnetizing inrush current from a fault current. It is evident that relaying protection should be initiated in response to fault but not to inrush current. To avoid the needless trip by magnetizing inrush current, many different restrain methods are proposed in recent years. Protection of transformers becomes a critical issue related to power system. Thus it becomes very essential that the transformer is protected from various possible failures. Magnetizing inrush current of a transformer ranges between 01 to 05 % of the rated current whose first peak may reach as high as the rated current itself. Magnetizing inrush current find its presence in the initial stage when the transformer is energized and may last up to few milliseconds before the steady state is reached. This inrush current can cause the transformer to malfunction and thus leading to faulty operation of a power system. This inrush current tends to have a high magnitude and is rich in harmonics which may seriously reduce the life expectancy of the transformer. As the power system is subjected to varying magnitudes of load it automatically is subjected to varying inrush current every time the transformer is energized. The magnitude of inrush current is usually 10 to 15 times the rated current due to which this inrush results in high level of harmonics which damages the insulation. On account of the insulation failure the temperature increases. The harmonics are reactive in nature and they generate a voltage drop across the network which leads to instability in

the power system. The transformer design and the station installation affect the magnitude of the inrush currents [3]. II. METHODOLOGY TO BE ADOPTED We have seen that the percentage differential scheme tends to maloperate due to magnetizing inrush. One way to combat this problem is to desensitize the relay for a brief period of time, just after switching on. However, this is not desirable, since the probability of insulation failure just after switching on is quite high, and a desensitized relay would be blind to faults taking place at that crucial time. A solution to this problem suggests itself, when we compare the waveforms of fault current with that of the inrush current. The inrush waveform is rich in harmonics whereas the internal fault current consists of only of the fundamental. Thus, we can develop additional restraint based on harmonic content of the inrush current. This additional restraint comes into picture only during the inrush condition and is ineffective during faults. start

Data entry coming from C.Ts

Calculate I1 and I2

Normal condition

yes

NO |I1-I2|>0

Sec_harmonic >Th

yes

Inrush current

NO

Fault current

Reject trip signal

Generate trip signal

Fig. 1: Flow Chart

All rights reserved by www.ijsrd.com

1525


Second Harmonic Method for Discrimination between in Rush and Fault Current in Power Transformer (IJSRD/Vol. 4/Issue 02/2016/428)

III. SIMULATION AND RESULT Second harmonic method is used to identify inrush and fault current for following cases: 1) Inrush case 2) Fault case 3) Fault with inrush case

The conventional differential protection scheme that are based upon second harmonic restrain assume that only inrush current is reach in second harmonic component. The second order harmonic calculated by using FFT. The window for FFT analysis is taken to be 20 m second i.e. one cycle taking the fundamental frequency of power transmission as 50 Hz. A. Normal Operating Condition FFT plots shows that during normal case the percentage of second harmonic current is very less in comparison to fundamental and in this case there is no problem with the conventional relay. Those relays will remain dormant in this case as the ratio of inrush to fundamental is negligible and that matches with their algorithm. The relays can only issue a trip command to the circuit breaker if the ratio exceeds a predefined limit which is formed by taking the inrush current case as the base or reference.

Fig. 2: Simulation of Second Harmonic Method In this simulation is used following parameter [4] Rated capacity 30 kVA Rated voltage ratio 1732.05/380V Rated current ratio 10/45.58A Rated frequency 50Hz No load current 1.45% No load loss 1% Short circuit voltage 9.0 15.0% Short circuit loss 0.35% Load 0.9kW Table 1: For No load No load current 0.66A No load angle 46.32 Magnetizing current 0.477A Core loss component of current 0.455A Magnetizing branch reactance 459.93Ω Resistance represent in core loss 482.17 Ω Magnetizing inductance 1.46H Magnetization resistance Rm (pu) 100.17 Magnetization inductance Lm (pu) 95.55 Table 2: For Short Circuit Equivalent resistance 0.35 Ω Equivalent impedance 12 Ω Equivalent leakage reactance 11.99 Ω Resistance winding 1(pu) 0.0018 Resistance winding 2(pu) 0.0018 Leakage inductance winding 1(pu) 0.059 Leakage inductance winding 2(pu) 0.059 Table 3: Load data Nominal phase-to-phase voltage 1000V Load 0.9KW Table 4:

Fig. 3: FFT for Normal Operating Condition at Phase A Second Third Fifth PHASE harmonic % harmonic % harmonic % Phase A 0.49 0.46 0.41 Phase_B 0.91 0.88 0.81 Phase_C 0.47 0.44 0.40 Table 1: FFT analysis for normal operating condition B. Inrush Case

Fig. 4: Inrush Current at Switching angle 0˚

All rights reserved by www.ijsrd.com

1526


Second Harmonic Method for Discrimination between in Rush and Fault Current in Power Transformer (IJSRD/Vol. 4/Issue 02/2016/428)

PHASE

FFT window: 1 of 150 cycles of selected signal

Phase_A Phase_B Phase_C

20 10 0 0.302

0.304

0.306

0.308

0.31

0.312 Time (s)

0.314

0.316

0.318

0.32

Mag (% of Fundamental)

60 50

Fifth harmonic % 2.80 1.41 4.69

D. Inrush with Fault Case

40 30 20 10 0

0

100

200

300

400 500 Frequency (Hz)

600

700

800

900

1000

Fig. 5: FFT for inrush condition at Phase A During the FFT analysis of inrush case transient currents for one cycle it is seen that the percentage of second harmonic content is different for the three phases. The percentage second harmonic content is of significant amount. The conventional relay will work in this case but the detection and algorithm will fail if the relay operating time will be taken less than a cycle and also if the transient phenomena lasts for less than a cycle. The conventional algorithm starts the FFT window from the starting of the event resulting less percentage of second harmonic content. Phase_A Phase_B Phase_C

Third harmonic % 4.66 2.34 7.81

Table 3: FFT Analysis for Fault Condition For FFT analysis for fault case, second order of harmonic component magnitude small compare to inrush case.

Fundamental (50Hz) = 14.28 , THD= 48.09%

PHASE

Second harmonic % 6.97 3.50 11.68

Second harmonic % 46.79 80.15 89.68

Third harmonic % 3.77 53.59 77.22

Fifth harmonic % 2.23 6.16 45.31

Table 2: FFT analysis for Inrush Condition C. Fault Case

Fig. 8: Fault at transformer terminal(A_B_G) with Inrush current at switching angle 0Ëš Second Third Fifth PHASE harmonic % harmonic % harmonic % Phase_A 19.58 4.08 0.53 Phase_B 20.29 0.54 4 Phase_C 1.09 1.07 1.01 Table 4: FFT analysis for inrush with Fault condition Table 5: gives the harmonic content of a typical inrush waveform. Frequency Magnitude Fundamental 100 DC 40-60 Second harmonic 30-70 Third harmonic 10-30 Fourth harmonic Less than 5% Fifth harmonic Less than 5% Sixth harmonic Less than 5% Seventh harmonic Less than 5% Table 5: Harmonic Content of in Rush Waveform IV. CONCLUSION

Fig. 6: Fault at transformer terminal (A_B_C_G) at Switching angle 0Ëš

In the FFT analysis of inrush and fault, we have observed that the second harmonic content of the inrush current is lying in the high range almost above 30%. The second harmonic content for fault in all the cases is lying below 25%. So, we can easily differentiate the inrush and fault transients on the basis of FFT analysis. REFERENCES [1] P. L. Moa and R. K. Aggarwal, "A novel approach to the classification of the transient phenomena in power transformer using combined wavelet transform and neural network," IEEE Trans. Power Del. vol. 16, no. 4, pp. 654-660, Oct. 2001. [2] S. S. Rao, "Switchgear Protection and Power Systems," theory, practice and solved problems, 11 ed., published by: Romesh Chander Khana, 1999, pp. 645-660.

Fig. 7: FFT for Fault condition at Phase A

All rights reserved by www.ijsrd.com

1527


Second Harmonic Method for Discrimination between in Rush and Fault Current in Power Transformer (IJSRD/Vol. 4/Issue 02/2016/428)

[3] S. R. B. Y.G.Paithankar, "Fundamentals of Power System Protection," PHI, vol. Second Edition, 2014. [4] M. Jing, W. Zengping, Y. Qixun, and L. Yilu, "A Two Terminal Network-Based Method for Discrimination Between Internal Faults and Inrush Currents," Power Delivery, IEEE Transactions on, vol. 25, pp. 15991605, 2010.

All rights reserved by www.ijsrd.com

1528


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.