Tropical Paradise, Yes But Not for Overhead Distribution

Page 1

Archive

www.inmr.com


UTILITY PRACTICE & EXPERIENCE

Tropical Paradise, Yes But Not for Overhead Distribution

Lightning flash density around Thailand. Near the coast and out at sea, activity tends to be low. Levels to the north and south are similar to those found in Florida, USA - with ground flash density of 10 to 14 per km2 per year. (Data from NASA OTD Version 2.2 records).

56

INMR速 Q2 2012

INMR Issue 96.indd 56

tropical paradisE, YEs But not

For

ovErhEad distriBution

16/05/12 2:41 PM


This picturesque, palm-filled scene from southern Thailand conveys a sense of nothing but serene, natural beauty. Yet, lurking hidden in this same image are some of the most important stresses that adversely impact overhead distribution – coastal pollution, high humidity, frequent lightning, intense solar radiation, abundant wildlife and, sadly, occasional vandalism as well. All these present serious challenges to operators of overhead distribution networks in terms of unplanned outages and potentially high maintenance costs.

Photo: INMR Š

The photos on the following pages provide evidence of the types of problems that can occur and also remark on some of the solutions applied by the system operator given the demanding service environment.

tropical paradisE, YEs But not

INMR Issue 96.indd 57

For

ovErhEad distriBution

Q2 2012 INMRÂŽ

57

16/05/12 2:41 PM


All photos: INMR Š

Porcelain insulators are brittle and can quickly fracture due to stone throwing or gunshot. The insulators in these images show typical outcomes of vandalism.

58

INMRÂŽ Q2 2012

INMR Issue 96.indd 58

tropical paradisE, YEs But not

For

ovErhEad distriBution

16/05/12 2:41 PM


All photos: INMR Š

High levels of contamination on both upper and lower surfaces can quickly overwhelm porcelain disc insulators leading to pollution flashover, as clearly evident in these photos. Damage to glaze from successive flashovers will leave surfaces increasingly rough leading to increased concentrations of localized pollution deposition and even greater risk of future similar flashovers.

tropical paradisE, YEs But not

INMR Issue 96.indd 59

For

ovErhEad distriBution

Q2 2012 INMRÂŽ

59

16/05/12 2:41 PM


All photos: INMR ©

Biological contamination is a problem often associated only with polymeric insulation yet can occur with equal ease on porcelain surfaces in a hot, damp environment. Mold growth can reduce effectiveness of external insulation due to build up of persistent wetting. Another issue in a tropical setting is onset of corrosion and possible damage to cement work from leakage current collecting here whenever porcelain is wetted by dew or rain.

60

INMR® Q2 2012

INMR Issue 96.indd 60

Deterioration due to high UV is another potential problem. Cutouts above show evidence that fuse tubes are well on the way to failure caused by long-term exposure to strong sun. Initially, the paint starts to disappear followed by the polyester layer itself. If these cutouts had to operate, they could possibly explode the tube and need to be replaced – not a serious problem if there is a backup tube. If not, there could be a long-term outage.

tropical paradisE, YEs But not

For

ovErhEad distriBution

16/05/12 2:41 PM


The limited angle of glaze damage and its presence on all sheds is likely the result of impulse flashover and resulting power arcs. Since there is no bonding to the insulator bases, leakage current flows through the concrete, which typically has low resistivity. However, the framing looks as if it was adapted from a wood construction and there is no impulse strength in the concrete crossarm. Note the loss of glaze on bottom shed of porcelain in photo at bottom, making it even more vulnerable to contamination build up.

All photos: INMR Š

Also, these post insulators seem to be dimensioned much smaller in terms of dry arc leakage distance than the four accompanying standard discs. This should normally be reversed since post leakage should be higher than series discs in contaminated areas such as this.

62

INMRÂŽ Q2 2012

INMR Issue 96.indd 62

tropical paradisE, YEs But not

For

ovErhEad distriBution

16/05/12 2:41 PM


Wildlife, such as monkeys or large birds, are an issue affecting distribution lines in most tropical countries and remedial measures often include specialized protectors over terminals of, e.g. arresters. However, these are not always effectively installed.

Note: On porcelain bushing at left there is evidence on the second shed from the bottom of a so-called ‘glaze worm’ – a signature of long-term damage from minor arcing (as opposed to flashover).

64

INMR® Q2 2012

INMR Issue 96.indd 64

tropical paradisE, YEs But not

For

All photos: INMR ©

For example, the wildlife protector on the arrester in this photo is virtually worthless against larger animals and birds. A monkey or similar animal that comes close to this top lead will not survive if they are also touching a point of ground potential such as an earthed concrete pole. Similarly, animal guard covers have been installed over a nearby transformer to prevent an animal fault across the terminals but the rod gaps (which probably came already equipped on the transformer) are not protected. To be effective, the top terminals of these rod gaps should have insulation as thick as on the high side phase conductors.

ovErhEad distriBution

16/05/12 2:41 PM


ď ´ This photo shows that

All photos: INMR Š

both 30 kV arresters have failed and operated their disconnectors. The top arrester also has its hot lead cut away so that it is completely isolated from the system. The bottom arrester, however, still has the high voltage applied at the top and therefore also at the bottom since the disconnector is open. Note: Sheds on the insulating hanger in this installation seem highly under-dimensioned. Once the disconnector operates, the full system voltage stress across the insulating hanger will likely cause it to flashover sporadically within a short time.

66

INMRÂŽ Q2 2012

INMR Issue 96.indd 66

tropical paradisE, YEs But not

For

ovErhEad distriBution

16/05/12 2:42 PM


Photos: INMR ©

 Three EPR shed

 Silicone sheds on this 30 kV polymeric arrester that protects the transformer shown above still maintain good hydrophobicity, even in a demanding location right beside the sea. There is no evidence of mold and the discoloration may rather have been due to an external flashover. Note creepage distance of insulating hanger, which is the minimum that would pass IEC or IEEE standards.

tropical paradisE, YEs But not

INMR Issue 96.indd 67

For

material arresters from one manufacturer look almost new and obviously in good shape while older design from another supplier (second from left) shows evidence of superficial surface changes. Note: Fuse tubes on cutouts show one with some paint still on and one with most paint already gone.

ovErhEad distriBution

Q2 2012 INMR®

67

16/05/12 2:42 PM


Hydrophobicity of the top shed of these IEC Class 2 or 3 arresters protecting cable connected on the other side of structure is impressive.

68

INMRÂŽ Q2 2012

INMR Issue 96.indd 68

tropical paradisE, YEs But not

All photos: INMR Š

Note: All have insulated bases with ground leads directed down the structure to probably 1 to 3 condition monitors. Since they are protecting underground cable, power system operator has specified a higher quality arrester for this application and one that lends itself to condition monitoring as well.

For

ovErhEad distriBution

16/05/12 2:42 PM