DC Inverter VRF Air Conditioning Systems
VRF
C A T A L O G U E
2 0 1 2
YOUR CONDITIONS! Since 1916,
pioneers in the US market, by designing and manufacturing innovative air conditioning and
heat pump units. The company’s primary competitive advantage is the use of its know-how expertise gained in the past, to build air conditioning systems of the future. The key to
units' success is that they are specifically designed to enable the modern individual invent his
own custom made living and working conditions. Regulating effectively the natural environment, units can create silently the perfect indoor conditions; your conditions!
All units carry a 2-year Warranty for the compressor and for all parts of the unit.
units can be found all across Europe in a continuously growing selected network of air conditioning professionals! Their excellent quality and operational efficiency has been awarded by the European Union with the highest standard certificates. Furthermore, the use of the environmental friendly refrigerants (freon) do not contribute to the increase of the global warming environment.
2
index INV Features
Pages
Higher Efficiency Better Comfort Higher Reliability Better Versatility Easy Installation & Maintenance INV Mini
4-5 6-7 8-9 10-11 12-13 14-15
Outdoor Units
Pages
Line up Specifications
16-17 18-21
Indoor Units
Pages
Line up Duct Type Slim Duct Type Four-way Cassette Type One-way Cassette Type Floor Standing Type Wall Mounted Type Floor Ceiling Type Concole Type Treated Fresh Air Duct Type
22-23 24-27 28-29 30-33 34 35 36-37 38-40 41 42-43
Control System
Pages
Control Network Sketch Controllers Comparison Comments of Control Functions Wired Remote Controller Wireless Remote Controller Group Controller Smart Zone Controller Centralized Controller IR Receiver & Key-card Control Board Communication Module Commissioning Program RS-422/485 Repeater RS-232 to RS-422/485 Converter INVENTOR Eudemon 2009 PC SUIT Piping Design Program
44-45 46 47 48-49 50-51 52 53 54 55 56 57 58 59 60-61 62-63
Energy Recovery Ventilation Connection Branches
64-66 67 3
HIGHER EFFICIENCY ) Significantly improved EER/COP Significantly greater efficiency is realized by the use of DC Inverter Hermetic Scroll Compressors with high-pressure chamber design, improved DC inverter driving technology and large heat exchanger.
27%
18%
increase of EER
increase of COP 4.37
4.07 4.0
4.0 3.7
3.5
3.5 3.2
3.0
3.0
2.5
2.5
Former model
INV
Former model
INV
Heat Exchanger
✍
Fan Motor
• EER is the efficiency rate= cooling capacity (kW) ÷ cooling power input (kW) COP is the coefficient of performance = heating capacity (kW) ÷ heating power input.
Compressor
• EER/COP values are based on INVENTOR laboratory testing method The data refers to a 8HP outdoor unit
) High efficiency compressor High pressure chamber design What’s high pressure chamber? The compressed gas that is discharged from the fix scroll, fulfills the whole hermetic chamber of the compressor. Then, when the whole compressor shell has high temperature and there is high pressure inside the compressor, the gas goes out from the exhaust. What’s the Benefit of High Pressure Chamber? Direct suction in high pressure chamber compressor. No loss from overheat suction. Increased compressor efficiency up to 3-5%. Suction High Pressure Fixed Scroll
Orbiting Scroll
Discharge
Intermediate Pressure Low Pressure Intermediate Pressure Chamber Motor in high Pressure
4
HP chamber structure can raise the high and middle frequency performance New DC motor (concentrated winding) raises the low frequency performance
) DC Fan motor
Air flow volume
Compared with the former model, airflow volume is increased 3% with the same single fan and 7% with the new dual fan, but the power consumption is decreased by 5% with the DC inverter motor. › 8HP/10HP Models
INV
Former model
3% Former model
INV
Air flow volume
› 12HP/14HP Models
Former model
INV
7% Former model
INV
) Heat Exchanger › The bigger condenser increases the heat-exchange area, improving the efficiency.
› Compared with the normal fin, the heat exchange efficiency of the louver is increased by 5%.
Former model: 2098x38.1x1156
Former model: Normal flat fin
INV:
INV:
2248x38.1x1190
Louver fin with golden coated
› Comparing with normal compressor, the DC Inverter Scroll compressor can save up to 40% of energy consumption in a year.
› Special thickened inner groove copper tube enhances heat exchanging performance.
› With stepless power regulating technology, the DC inverter compressor achieves stepless output regulation between 20Hz-120Hz
› Improved DC inverter motor Low frequency performance is highly raised thanks to the concentrated winding.
Compressor efficiency
Distributed winding
Concentrated winding
7% 0
20
Rotating speed (/rps)
5
BETTER COMFORT ) Quiet Operation › Quiet operation during night time The Intelligent adjustment of the outdoor fan control can minimize the operation noise during night time. It can be reduced up to 8dB(A). So the operating noise at night is lower, at 50dB(A).
58dB(A)
Capacity Operating sound
50dB(A)
Capacity Operating sound
Heat load
› Low noise design OUTDOOR UNIT • HP chamber compressor has lower exhaust pressure fluctuation, so the noise is lower.
• The optimized design of the condensing fan blade reduces the air flow turbulence among blades. So, the noise is lower.
Quiet compressor
Average 2dB(A) down
Optimized
Original design
INDOOR UNIT
New design with higher performance &lower noise 4dB(A) less!
› Low noise indoor unit
37dB(A) Office Duct Type with High ESP
37dB(A) Hotel Slim Duct Type
6
37dB(A) Reception Four-way Cassette Type
28dB(A) Bedroom Wall Mounted Type
) Comfortable Temperature
fluctuation of
the room
Less Cool
Uncomfortable Comfortable
Cooler
Uncomfortable
INV
Defrosting
Heating
Defrosting
Heat Loss
› Intelligent defrost technology Traditional defrost program • Simply executes defrosting according to a certain time. • The defrost function may still start even if there is no such (defrosting) demand.
Non VRF
Heating Capacity
› Precise temperature control The EXV (Electronic Expansion Valve) of each Indoor unit responds to the loading changes of indoor environment, so it continually adjusts the flow rate of refrigerant. Meanwhile, the outdoor unit with DC inverter compressor provides the capacity with certain amount of refrigerant exactly according to the total demands of the indoor units. With this Variable Refrigerant Flow (VRF) technology, we can quickly get a nearly constant room temperature. The typical temperature fluctuation that occurs with a conventional ON/OFF control system is eliminated.
Time 10mins
50mins
10mins
50mins
10mins
Defrosting
Heating Capacity
Intelligent defrost program •Humanized technology which considers the maximization of energy saving. • Defrosting program that is designed under the consideration of heating efficiency and operation reliability. • Precise defrosting timing, which is intelligent indeed. • It’s an optimized defrosting program, which will be performed only when the system’s pressure is too low. This can obviously lengthen the time gap between two defrost operations and reduce the times of defrosting. • Heating capacity loss has been decreased by 75% with highly comfortable heating operation.
Heating
Time Defrosting starts if the unit detects frost
Defrosting stops after completion
› Individual control The set temperature of each room may vary by the individual thermostat control of each indoor unit.
OFF 260C 220C
200C 240C
270C
7
HIGHER RELIABILITY ) Modular operating › The operating priority sequence of the outdoor unit modules will be changed without restart when the system accumulatively operates for 12 hours. This can maximize the service life of the system.
12hours Rotation
› Emergency operation Each module is an independent sub-system. The whole system won’t fail down even if partial malfunction occurs. If a malfunction occurs at any module, there can be performed an emergency operation. This can simply be achieved by setting up manually the outdoor PCB switches.
12hours Rotation
Operating
Malfunction 12hours Rotation
Emergency Operation
12hours Rotation
) Continuous operation of indoor units Each indoor unit is controlled individually on the system network. This allows all indoor units to continue operating even if an error occurs at any indoor unit on the VRF system.
Failure
) Wide voltage range operation
) Power supply security
The unit can safely operate within 342V-456V
With power supply security, the outdoor unit will start autoprotection if the power voltage or the current is out of the normal range. Protection will be relived automatically if the power condition resumes normal.
342V
456V Safe operation range
8
) PCB protection design
) Anti-corrosion
With unique high efficiency radiating air-dust design, the outdoor electric box is designed as water-proof, dust-proof, damp-proof and well –ventilated. This can ensure the required condition for the electric elements even in tropical conditions. Also, it improves the system’s reliability and service life.
The primary material of Golden Fin is Al-Mn (Aluminum-Manganese) anti-rust alloy, which is coated with the Golden Protection Layer (Components: Epoxy Resin & Modified Acrylic, Silicon free). The anti-corrosive performance in salt-spray testing is 200%-300% higher than normal Blue Fin*. Hydrophilic Layer Golden Protection Layer (Epoxy resin & Modified Acrylic)
Al-Mn-corrosive alloy
*Salt-spary testing result is from INVENTOR materials chemistry testing laboratory
Air outlet
) New generation of oil return control The pressure control achieves an optimized oil return of the system. As a result, the operating life of the compressor is greatly improved.
Negative pressure
Electric Box Baffle Electric Box Cover
Backflow
Guide louver Positive pressure Air inlet Front pane
) High efficiency oil-balanced technology High-pressure chamber Suction pipe compressor with oil-balanced pipe can automatically drain out the excess oil. Discharge pipe This can prevent an oil-unbalance between the compressors. Auto-oil pipe
› New patented oil separator allows the oil separating efficiency up to 99%. › Oil equalizing pipe connection designed at the outside of the module allows high reliability. Before Oil Balanced
After Oil Balanced
Compressors Oil storage tank
Oil equalizing pipe
Oil equalizing pipe
9
BETTER VERSATILITY ) Long piping design › Maximum total piping length --- 500m › Maximum actual piping length --- 150m › Maximum equivalent piping length --- 175m › Maximum height difference between indoor units --- 15m › Maximum height difference between outdoor and indoor units --- 50m* › Maximum piping length from first indoor branch to the farthest indoor unit --- 40m
) Higher Static pressure of outdoor unit The maximum external static pressure (ESP) of the outdoor fan can reach up to 75Pa*. The outdoor unit can be installed in the equipments room of high buildings. * Default ESP of the product is 40Pa. If higher ESP is required, please contact us.
15m
40m
150m
50m
* This value is based on the case that the outdoor unit is located above the indoor unit. If the outdoor unit is located underneath the indoor unit, the value is 40m.
) Wide operation range The unit can operates in wide range, greatly reducing the ambient temperature limitation.
✍ • If the required capacity of indoor units is 50% higher than the outdoor unit, the cooling range may be lower up to –150C • If the required capacity of indoor units is 50% lower than the outdoor unit, the cooling range may be up to –50C.
10
Heating
Cooling
) Compact Design Compact size has been achieved by significantly reducing the width of the outdoor units compared to previous models. Former model (8HP)
INV (8HP)
1670mm
1772mm
17% reduction
880mm
770mm 990mm Floor area: 0,87m
930mm 2
Floor area: 0,72m2
INV (16HP)
41%
1670mm
1772mm
Former model (8HP + 8HP)
reduction
880mm (990+990)mm Floor area: 1,74m2
770mm
1340mm
Floor area: 1,03m2
) Modular outdoor unit design › Various combinations from 8HP to 64HP with 2HP increments. › Max capacity of outdoor unit is 180kW (4 x modules)
) Various combinations › Up to 110 sets of indoor units can be connected* *For the standard model that 4 models connect in parallel, up to 64 indoor units can be connected. If more indoor units are required to be connected please contact us.
› 12 types and 69 models. › Maximum diversity is 135%
11
EASY INSTALATION & MAINTENANCE ) Easier maintainability › Special-designed elecric box. The electric box can be opened by inverting downwards, for easy maintenance.
› Error display & Self-diagnostics system. Any malfunction can be judged by the LED display that is on the main board (different combinations of ON/OFF or BLINK). • Self diagnostics system display
12
• LED display on the connection board
• LED display on the connection board
) Easier transportation & installations › Light weight Former model (8HP+8HP): 240x2=480kg
› Transportation by forklift
INV (16HP): 370kg
› Optimized base frame Optimized base frame. The locating and fixing of the outdoor unit during installation is more convenient and reliable.
› Five-Way piping connection • Piping and wiring are available to the front and back, left and right, bottom. • The five-way piping connection reduces installation difficulty and cost. Improves the installation efficiently.
› Compact design With compact design, the outdoor unit can be carried to the roof of a building through elevator. No crane is needed. Traditional Central Air Conditioner
INV
13
INV MINI 70m
› Long piping design • Maximum total piping length --- 150m • Maximum actual piping length --- 70m • Maximum equivalent piping length --- 80m • Maximum height difference between indoor units --- 10m • Maximum height difference between outdoor and indoor units --- 30m* • Maximum piping length from first indoor branch and the farthest indoor unit --- 25m
30m
) Flexible Design
25m
10m
* This value is based on the outdoor unit to be located above the indoor unit. If the outdoor unit is located underneath the indoor unit, the value is 25m.
› Compact Design Compact size has been achieved by significantly reducing the width of the outdoor units compared to previous models. INV
1100mm
14%
1250mm
1250mm
Former Model
reduction
340mm
340mm mm
Floor area: 0,374m2
) Wide voltage range operation The unit can safely operate within the power supply voltage of 185V to 264V.
14
950mm
Floor area: 0,323m2
185V
264V Safe operation range
) High efficiency
) Comfort
DC inverter rotary compressor
Auto quiet operation The unit is ensured to operate with the lowest noise due to the ultra-low fan speed and auto adjustment according to system parameters. The operation noise of the unit is reduced by 3dB(A) at lower loading.
Operation noise
3dB(A)
) Easy Installation When total piping length is less than 50m [(A+B+C+D+a+b+c+d) ≤ 50m], no additional refrigerant is required.
) Powerful heating in low temperature When outdoor ambient temperature is low, the system can automatically increase the heating effect according to its judgment on parameters. Heating performance is improved by 15%, which brings great comfort.
) Capacity MODEL Capacity Power Supply
HP kW
INV-Pd100W/NaB-K
INV-Pd120W/NaB-K
INV-Pd140W/NaB-K
INV-Pd160W/NaB-K
3.5 10
4.0 12
5.0 14
6.0 16
1Phase, 220-240V, 50Hz
15
OUTDOOR UNITS LINEUP INV-Pdm224W/ NaB-M (8HP)
MODEL INV-Pdm224W/ NaB-M (8HP)
INV-Pdm228W/ NaB-M (10HP)
INV-Pdm335W/ NaB-M (12HP)
INV-Pdm400W/ NaB-M (14HP)
INV-Pdm450W/ NaB-M (16HP)
INV-Pdm504W2/ NaB-M (18HP)
INV-Pdm560W2/ NaB-M (20HP)
INV-Pdm615W2/ NaB-M (22HP)
INV-Pdm670W2/ NaB-M (24HP)
INV-Pdm730W2/ NaB-M (26HP)
INV-Pdm785W2/ NaB-M (28HP)
INV-Pdm850W2/ NaB-M (30HP)
INV-Pdm900W2/ NaB-M (32HP)
16
INV-Pdm280W/ NaB-M (10HP)
INV-Pdm335W/ NaB-M (12HP)
INV-Pdm400W/ NaB-M (14HP)
INV-Pdm450W/ NaB-M (16HP)
INV-Pdm224W/ NaB-M (8HP)
MODEL
INV-Pdm280W/ NaB-M (10HP)
INV-Pdm335W/ NaB-M (12HP)
INV-Pdm400W/ NaB-M (14HP)
INV-Pdm450W/ NaB-M (16HP)
INV-Pdm950W3/ NaB-M (34HP)
INV-Pdm1008W3/ NaB-M (36HP)
INV-Pdm1605W3/ NaB-M (38HP)
INV-Pdm1130W3/ NaB-M (40HP)
INV-Pdm1180W3/ NaB-M (42HP) INV-Pdm11253W3/NaBM (44HP) INV-Pdm1300W3/ NaB-M (46HP) INV-Pdm11350W3/NaBM (48HP) INV-Pdm1405W4/ NaB-M (50HP)
INV-Pdm1456W4/ NaB-M (52HP)
INV-Pdm1512W4/ NaB-M (54HP)
INV-Pdm1570W4/ NaB-M (56HP)
INV-Pdm1650W4/ NaB-M (58HP)
INV-Pdm1700W4/ NaB-M (60HP)
INV-Pdm1750W4/ NaB-M (62HP)
INV-Pdm1800W4/ NaB-M (64HP)
17
SPECIFICATIONS INV Mini RATING CAPACITY
HP
MODEL Combination units Connectable indoor unit Power supply
Maximum Cooling Capacity (kW)
Cooling (kW) Heating (kW) Cooling (kW) Power consumption Heating (kW) Compressor Type m3/h Airflow rate CFM Sound pressure level (dB(A)) Dimensions WxDxH (mm) Net weight Refrigerant charge
4
5
6
INV-Pd 100W/NaB-K
INV-Pd 120W/NaB-K
INV-Pd 140W/NaB-K
INV-Pd 160W/NaB-K
6 5.0-13.5
7 8 6.0-16.2 7.0-18.9 1-Phase, 220-240V, 50Hz 12.0 14.0 14.0 15.4 3.50 4.36 3.40 4.05 DC inverter dual-rotor type compressor x 1 6200 6000 3642 3525 58 58 950x340x1250 950x340x1250 111 111 7.5 7.5 Cooling: 10 to 48, Heating: -20 to 27 Cooling: 18 to 118.4, Heating: -4 to 81 5/8 5/8 3/8 3/8
10.0 11.0 2.86 2.60
Capacity
kg
6200 3642 58 950x340x1250 111 7.5
째C 째F
Operation range Connection pipe diameter
3.5
Gas Liquid
inch
5/8 3/8
9 8.0-21.6 16.0 17.6 4.98 4.85 6400 3759 58 950x340x1250 115 7.5
3/4 3/8
Basic Module RATING CAPACITY
HP
MODEL Combination units Connectable indoor unit Power supply
Maximum Cooling Capacity (kW)
Cooling (kW) Heating (kW) Cooling (kW) Power consumption Heating (kW) Compressor Configration* m3/h Airflow rate CFM Sound pressure level (dB(A)) Dimensions WxDxH Net weight Operating range Refrigerant charge Capacity
Gas Liquid
*DC: DC inverter scroll compressor
18
kg 째C 째F
Operation range Connection pipe diameter
mm
inch
8 INV-Pdm 224W/ NaB-M
10 INV-Pdm 280W/ NaB-M
12 INV-Pdm 335W/ NaB-M
14 16 14.0 - 37.8 16.8 - 45.2 3-Phase, 380-415V, 50Hz 22.4 28.0 33.5 25.0 31.5 37.5 5.52 7.52 9.23 5.82 7.70 9.38 DCx1+Cx1 10000 10000 13000 5874 5874 7636 58 58 60 930x770x1670 255 255 350 275 275 380 12 13 15 Cooling: -5 to 48, Heating: -20 to 27 Cooling: 23 to 118.4, Heating: -4 to 81 7/8 7/8 9/8 3/8 3/8 1/2
14 11.2 - 30.2
C: Constant speed scroll compressor
14 INV-Pdm 400W/ NaB-M
16 INV-Pdm 450W/ NaB-M
16 20.0 - 54.0
16 22.5 - 60.8
40.0 45.0 12.45 11.2 DCx1+Cx2 13000 7636 61 1340x770x1670 350 380 16
45.0 50.0 14.32 13.90
9/8 1/2
13000 7636 61 370 400 17
9/8 1/2
Combination Modules RATING CAPACITY
HP
MODEL
Combination units Connectable indoor unit Power supply
Maximum Cooling Capacity (kW)
Cooling (kW) Heating (kW) Cooling (kW) Power consumption Heating (kW) Compressor Configration* m3/h Airflow rate CFM Sound pressure level (dB(A)) Dimensions WxDxH Net weight Refrigerant charge Capacity
kg 째C 째F
Operation range Connection pipe diameter
mm
Gas Liquid
RATING CAPACITY
Inch HP
MODEL
Combination units
Connectable indoor unit Power supply
Maximum Cooling Capacity (kW)
Cooling (kW) Heating (kW) Cooling (kW) Power consumption Heating (kW) Compressor Configration* m3/h Airflow rate CFM Sound pressure level (dB(A)) Dimensions WxDxH Net weight Refrigerant charge Capacity
kg 째C 째F
Operation range Connection pipe diameter
mm
Gas Liquid
*DC: DC inverter scroll compressor
Inch
18 INV-Pdm 504W2/ NaB-M
20 INV-Pdm 560W2/ NaB-M
22 INV-Pdm 615W2/ NaB-M
24 INV-Pdm 670W2/ NaB-M
26 INV-Pdm 730W2/ NaB-M
INV-Pdm 224W/ NaB-M INV-Pdm 280W/ NaB-M
INV-Pdm 280W/ NaB-M INV-Pdm 280W/ NaB-M
INV-Pdm 280W/ NaB-M INV-Pdm 335W/ NaB-M
INV-Pdm 280W/ NaB-M INV-Pdm 400W/ NaB-M
INV-Pdm 280W/ NaB-M INV-Pdm 450W/ NaB-M
30 25.2-68
32 32 32 32 28.0-75.6 30.8-83.0 33.5-90.5 36.5-98.6 3-Phase, 380-415V, 50Hz 50.4 56.0 61.5 68.0 73.0 56.5 63.0 69.0 76.5 81.5 13.04 15.04 16.75 19.97 21.84 13.52 15.40 17.08 18.90 21.60 (DCx1+Cx1)x2 (DCx1+Cx1)+(DCx1+Cx2) 10000x2 10000+13000 5874x2 5874+7636 62 62 62 62 63 (930x770x1670)+(930x770x1670) (930x770x1670)+(1340x770x1670) 255+255 255+255 255+350 255+350 255+370 13+13 13+15 13+15 13+16 13+17 Cooling: -5 to 48, Heating: -20 to 27 Cooling: 23 to 118.4, Heating: -4 to 81 9/8 9/8 9/8 9/8 11/8 5/8 5/8 5/8 3/4 3/4
28 INV-Pdm 785W2/ NaB-M
30 INV-Pdm 850W2/ NaB-M
32 INV-Pdm 900W2/ NaB-M
34 INV-Pdm 950W3/ NaB-M
36 INV-Pdm 1008W3/ NaB-M
INV-Pdm 335W/ NaB-M INV-Pdm 450W/ NaB-M
INV-Pdm 400W/ NaB-M INV-Pdm 450W/ NaB-M
INV-Pdm 450W/ NaB-M INV-Pdm 450W/ NaB-M
INV-Pdm 280W/ NaB-M INV-Pdm 280W/ NaB-M INV-Pdm 400W/ NaB-M
INV-Pdm 280W/ NaB-M INV-Pdm 280W/ NaB-M INV-Pdm 450W/ NaB-M
32 39.3-106.0
32 32 48 48 42.5-114.8 45.0-121.5 47.5-128.3 50.4-136.1 3-Phase, 380-415V, 50Hz 78.5 85.0 90.0 96.0 101.0 87.5 95.0 100.0 108.0 113.0 23.55 26.77 28.64 27.49 29.36 23.28 25.10 27.8 26.60 29.30 (DCx1+Cx2)x2 [(DCx1+Cx1)x2]+(DCx1+Cx2) 13000x2 10000x2+13000 7636x2 5874x2+7636 63 63 63 64 64 (1340X770X1670)+(1340X770X1670) (930x770x1670)+(930x770x1670)+(1340x770x1670) 350+370 350+370 370+370 255+255+350 255+255+370 15+16 18+17 17+17 13+13+16 13+13+17 Cooling: -5 to 48, Heating: -20 to 27 Cooling: 23 to 118.4, Heating: -4 to 81 11/8 11/8 11/8 11/8 11/8 3/4 3/4 3/4 3/4 3/4
C: Constant speed scroll compressor
19
Combination Modules RATING CAPACITY
HP
MODEL
Combination units
Connectable indoor unit Power supply
Maximum Cooling Capacity (kW)
Cooling (kW) Heating (kW) Cooling (kW) Power consumption Heating (kW) Compressor Configration* m3/h Airflow rate CFM Sound pressure level (dB(A)) Dimensions WxDxH Net weight Refrigerant charge Capacity
kg °C °F
Operation range Connection pipe diameter
mm
Gas Liquid
RATING CAPACITY
Inch
HP
MODEL
Combination units
Connectable indoor unit Power supply
Maximum Cooling Capacity (kW)
Cooling (kW) Heating (kW) Cooling (kW) Power consumption Heating (kW) Compressor Configration* m³/h Airflow rate CFM Sound pressure level (dB(A)) Capacity
Dimensions
WxDxH
Net weight Refrigerant charge
kg
Operation range
°C °F
Connection pipe diameter
Gas Liquid
*DC: DC inverter scroll compressor
20
mm
Inch
38
40
42
44
46
48
INV-Pdm 1065W3/NaB-M
INV-Pdm 1130W3/NaB-M
INV-Pdm 1180W3/NaB-M
INV-Pdm 1235W3/NaB-M
INV-Pdm 1300W3/NaB-M
INV-Pdm 1350W3/NaB-M
INV-Pdm280W/ NaB-M
INV-Pdm280W/ NaB-M
INV-Pdm280W/ NaB-M
INV-Pdm335W/ NaB-M
INV-Pdm400W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm335W/ NaB-M
INV-Pdm400W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
48 53.3-143.8
48 48 48 48 48 56.5-152.6 59.0-159.3 61.81-166.7 65.0-175.5 67.5-182.3 3-Phase, 380-415V, 50Hz 106.5 113.0 118.0 123.5 130.0 135.0 119.0 126.5 131.5 137.5 145.0 150.0 31.07 34.29 36.16 37.87 41.09 42.96 30.98 32.80 35.50 37.18 39.00 41.70 (DCx1+Cx1)+[(DCX1+Cx2)x2] (DCx1+Cx2)x3 10000+13000x2 13000X3 5874+7636x2 7636x3 64 64 64 65 65 65 (930x770x1670)+(1340x770x1670)+(1340x770x1670) (1340x770x1670)+(1340x770x1670)+(1340x770x1670) 255+350+370 350+370+370 350+370+370 370+370+370 13+15+17 13+16+17 13+17+17 15+17+17 16+17+17 17+17+17 Cooling: -5 to 48, Heating: -20 to 27 Cooling: 23 to 118.4, Heating: -4 to 81 1” 5/8 1” 5/8 1” 5/8 1” 5/8 1” 5/8 1” 5/8 3/4 3/4 3/4 3/4 3/4 3/4
50 INV-Pdm1405W4/ NaB-M
52 INV-Pdm1456W4/ NaB-M
54 INV-Pdm1512W4/ NaB-M
56 INV-Pdm1570W4/ NaB-M
58 INV-Pdm1650W4/ NaB-M
INV-Pdm280W/ NaB-M
INV-Pdm280W/ NaB-M
INV-Pdm280W/ NaB-M
INV-Pdm280W/ NaB-M
INV-Pdm280W/ NaB-M
INV-Pdm280W/ NaB-M
INV-Pdm280W/ NaB-M
INV-Pdm335W/ NaB-M
INV-Pdm400W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm400W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
64 78.5-212.0
64 82.5-222.8
155.0 176.5 48.61 46.70 (DCx1+Cx1)+[(DCx1+Cx2) x3] 10.000+13.000x3 5.874+7.636x3 65
163.0 181.5 50.48 49.90
64 70.3-189.7
64 64 72.8-196.6 75.6-204.1 3-Phase, 380-415V, 50Hz 141.0 146.0 151.5 158.0 163.0 169.0 41.84 43.68 45.39 40.05 43.20 44.88 [(DCx1+Cx1) x2]+[(DCx1+Cx2)x2] 10.000x2+13.000x2 5.874x2+7.636x2 65 65 65
(930x770x1.670)+(930x770x1.670)+ +(1.340X770X1670)+(1.340X770X1.670) 255+255+350+370 13+13+16+17
1” 3/4 7/8
255+255+350+370 255+350+370+370 255+350+370+370 13+13+17+17 13+15+17+17 13+16+17+17 Cooling: -5 to 48, Heating: -20 to 27 Cooling: 23 to 118.4, Heating: -4 to 81 1” 3/4 7/4 2” 1/8 7/8 7/8 1
C: Constant speed scroll compressor
65
(930x770x1.670)+(1.340x770x1.670)+ +(1.340x770x1670)+(1.340x770x1.670) 255+370+370+370 13+17+17+17
2” 1/8 1
Combination Modules RATING CAPACITY MODEL
HP
Combination units
Connectable indoor unit Power supply
Maximum Cooling Capacity (kW)
Cooling (kW) Heating (kW) Cooling (kW) Power consumption Heating (kW) Compressor Configration* m3/h Airflow rate CFM Sound pressure level (dB(A)) Dimensions WxDxH Net weight Refrigerant charge Capacity
kg °C °F
Operation range Connection pipe diameter
mm
Gas Liquid
*DC: DC inverter scroll compressor
Inch
60 INV-Pdm1700W4/NaB-M
62 INV-Pdm1750W4/NaB-M
64 INV-Pdm1800W4/NaB-M
INV-Pdm335W/ NaB-M
INV-Pdm400W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
INV-Pdm450W/ NaB-M
64 85.0-230.0
64 64 87.5-236.3 80.0-243.0 3-Phase, 380-415V, 50Hz 168.0 175.0 180.0 187.5 195.0 200.0 52.19 55.41 57.21 51.80 52.90 55.60 (DCx1+Cx2) x4 13000x4 7636x4 66 66 66 (1340x770x1670)+(1340x770x1670)+(1340x770x1670)+(1340x770x1670) 350+370+370+370 15+17+17+17 16+17+17+17 17+17+17+17 Cooling: -5 to 48, Heating: -20 to 27 Cooling: 23 to 118.4, Heating: -4 to 81 2” 1/8 2” 1/8 2” 1/8 1 1 1 C: Constant speed scroll compressor
21
INDOOR UNITS LINEUP CAPACITY INDEX (kW)
Duct Type (EXV Integrated)
Slim Duct Type (EXV Integrated) Four-way Cassette Type (EXV Integrated) Compact Four-way Cassette Type (EXV Separated) One-way Cassette Type (EXV Separated)
Floor Standing Type
Concole Type
Floor Ceiling Type (EXV Integrated) Wall Mounted Type (EXV Separated) Wall Mounted Type (EXV Integrated) Treated Fresh Air Duct Type
22
2.2
2.8
3.6
4.5
5.0
5.6
6.3
7.1
8.0
9.0
10.0
11.2
12.5
14.0
22.4
28.0
23
DUCT TYPE ) Highly flexible installation › Highly flexible installation is possible to satisfy various needs eeds Installation examples
Return air inlet Supply air duct
Indoor unit Supply air duct Canvas air duct Indoor unit Long life filter
Maintenance access
› Flexible and easy to install in type-L, type-U and in large rooms
) Fresh air function option for 5.6kW and above units
24
Long life filter
) Drain pump lift reaches 1000mm Only available for INV(L)-R*PS/NaB-K
) Easy maintenance › Long life and washable filter with buckles can be easily disassembled from each direction. › Compact size has been achieved by significantly reducing the width of the outdoor units compared to previous models.
Former structure: push pull type The former structure is not easy to disassembly.
New structure: with buckles The new structure makes the disassembly convenient.
) HIGHER ESP & lower noise The ESP is obviously upgraded while the noise is almost at the same level as before. Low ESP of new model
Former model
New model (In low ESP)
ESP (Pa)
Sound level (dB(A))
Former model High ESP of new model
Model (kW)
Model (kW)
) Key-card control
25
Duct Type (With drain water pump) MODEL
INV-R22PS/NaB-K
Power supply Cooling (kW) Capacity Heating (kW) Power consumption (W) m3/h Airflow rate CFM Sound pressure level (H/M/L) (dB(A)) Standard Esp (H/L) (Pa) Dimensions (WxDxH) (mm) Net weight (Kg) Inch Gas (Flare) mm Connection pipe Inch Liquid (Flare) mm External dia. mm Drain Pipe Thickness mm
MODEL
2.2 2.5 75 450 265 37/35/33 50/20 28.5 3/8 φ9.52 1/4 φ6.35 φ20 1.5
INV-R56PS/ NaB-K
INV-R28PS/NaB-K
1-Phase, 220-240V, 50Hz 2.8 3.6 3.2 4.0 80 80 570 570 335 336 39/37/35 39/37/35 50/20 50/20 880x665x250 30.5 30.5 3/8 1/2 φ9.52 φ12.7 1/4 1/4 φ6.35 φ6.35 φ20 φ20 1.5 1.5
INV-R71PS/ NaB-K
Power supply Cooling (kW) Capacity Heating (kW) Power consumption (W) m3/h Airflow rate CFM Sound pressure level (H/M/L) (dB(A)) Standard Esp (H/L) (Pa) Dimensions (WxDxH) (mm) Net weight (Kg) Inch Gas (Flare) mm Connection pipe Inch Liquid (Flare) mm External dia. mm Drain Pipe Thickness mm
26
INV-R36PS/NaB-K
5.6 7.1 6.3 8.0 240 240 1.000 1.100 589 647 44/42/40 45/43/41 60/30 60/30 1155x756x300 51 51 5/8 5/8 φ15.9 φ15.9 3/8 3/8 φ9.52 φ9.52 φ30 φ30 1.5 1.5
INV-R90PS/ NaB-K 1-Phase, 220-240V, 50Hz 9.0 10.0 360 1.700 1.000 48/46/44 80/40 64 5/8 φ15.9 3/8 φ9.52 φ30 1.5
INV-R45PS/NaB-K 4.5 5.0 140 700 412 40/38/36 50/20 980x721x266 36 1/2 φ12.7 1/4 φ6.35 φ30 1.5
INV-R112PS/ NaB-K
INV-R140PS/ NaB-K
11.2 12.5 360 1.700 1.000 48/46/44 80/40 1425x736x300 64 5/8 φ15.9 3/8 φ9.52 φ30 1.5
14.0 15.0 500 2.000 1.177 50/48/46 100/50 65.5 5/8 φ15.9 3/8 φ9.52 φ30 1.5
Duct Type (Without drain water pump) MODEL
IN-R22P/ NaB-K
Power supply Cooling (kW) Capacity Heating (kW) Power consumption (W) m3/h Airflow rate CFM Sound pressure level (H/M/L) (dB(A)) Standard Esp (H/L) (Pa) Dimensions (WxDxH) (mm) Net weight (Kg) Inch Gas (Flare) mm Connection pipe Inch Liquid (Flare) mm External dia. mm Drain Pipe Thickness mm
MODEL
2.2 2.5 75 450 265 37/35/33 50/20 27 3/8 φ9.52 1/4 φ6.35 φ20 1.5
INV-R90P/ NaB-K
Power supply Cooling (kW) Capacity Heating (kW) Power consumption (W) m3/h Airflow rate CFM Sound pressure level (H/M/L) (dB(A)) Standard Esp (H/L) (Pa) Dimensions (WxDxH) (mm) Net weight (Kg) Inch Gas (Flare) mm Connection pipe Inch Liquid (Flare) mm External dia. mm Drain Pipe Thickness mm
9.0 10.0 360 1.700 1.000 48/46/44 80/40 62 5/8 φ15.9 3/8 φ9.52 φ30 1.5
INV-R28P/ NaB-K
INV-R36PS/ NaB-K
INV-R45P/ NaB-K
1-Phase, 220-240V, 50Hz 2.8 3.6 3.2 4.0 80 80 570 570 335 336 39/37/35 39/37/35 50/20 50/20 880x665x250 28.5 28.5 3/8 1/2 φ9.52 φ12.7 1/4 1/4 φ6.35 φ6.35 φ20 φ20 1.5 1.5
INV-R112P/ NaB-K 1-Phase, 220-240V, 50Hz 11.2 12.5 360 1.700 1.000 48/46/44 80/40 1425x736x300 62 5/8 φ15.9 3/8 φ9.52 φ30 1.5
INV-R56P/ NaB-K
4.5 5.0 140 700 412 40/38/36 50/20 980x721x266 34 1/2 φ12.7 1/4 φ6.35 φ30 1.5
INV-R140P/ NaB-K 14.0 15.0 500 2.000 1177 50/48/46 100/50 63.5 5/8 φ15.9 3/8 φ9.52 φ30 1.5
INV-R71P/ NaB-K
5.6 7.1 6.3 8.0 240 240 1.000 1.100 589 647 44/42/40 45/43/41 60/30 60/30 1155x756x300 49 49 5/8 5/8 φ15.9 φ15.9 3/8 3/8 φ9.52 φ9.52 φ30 φ30 1.5 1.5
INV-R224P/ NaB-M
INV-R280P/ NaB-M
3-Phase, 380-450V, 50Hz 22.4 28.0 25.0 31.0 1.600 1.600 4.000 4.800 2.381 2.857 56(H) 57(H) 200 220 1463x799x389 1628x869x454 88 113 5/8 5/8 φ15.9 φ15.9 3/8 3/8 φ9.52 φ9.52 φ25.4 φ25.4 1.5 1.5
27
SLIM DUCT TYPE ) Compact Design › 2.2kW, 2.8kW, 3.6Kw Only 700mm in width, 200mm in height and 22kg in weight*, which is perfect to install in limited spaces like drop ceiling in hotel.
✍ • Note: the weight is 23kg for the unit of 3.6kW.
200mm
700mm
› 4.5kW, 5.6kW Only 200mm in height, which can be installed in rooms with little depth as 240mm depth between the drop ceiling and ceiling slab. Suspension bolt
Suction duct*
200mm
AIR 900mm Discharge grille
Air filter
Suction grille
AIR
✍ • Note: to be obtained locally
) Highly flexible installation Highly flexible installation is possible to satisfy various needs. Installation examples Example 1
Example 2 Return air inlet
Supply air duct
Indoor unit
Supply air duct
Canvas air duct Indoor unit Long-life filter
28
Maintenance access
Long-life filter
) Lower noise Plastic propeller housing, fan blade and intelligent-designed air-channel ensure air flow volume with lower operation noise.
For example the normal unit of 2.8kW has noise level up to 40dB(A), but the new unit of 2.8kW reduces the noise up to only 37dB(A).
) Drain pump lift reaches 1000mm
MODEL
INV-R22P/ NaE-K
INV-R28P/ NaE-K
2.2 2.5 64 450 265 37/35/33 20
2.8 3.2 64 450 265 37/35/33 20 700x615x200 21 3/8 φ9.52 1/4 φ6.35 φ20 1.5
Power supply Cooling (kW) Capacity Heating (kW) Power consumption (W) m3/h Airflow rate CFM Sound pressure level (H/M/L) (dB(A)) Standard Esp (Pa) Dimensions (WxDxH) (mm) Net weight (Kg) Inch Gas (Flare) mm Connection pipe Inch Liquid (Flare) mm External dia. mm Drain Pipe Thickness mm
21 3/8 φ9.52 1/4 φ6.35 φ20 1.5
INV-R36P/ NaE-K
INV-R45P/ NaE-K
INV-R56P/ NaE-K
1-Phase, 220-240V, 50HZ 3.6 4.5 5.6 4.0 5.0 6.3 70 91 91 550 700 700 324 412 412 39/37/35 40/38/36 41/39/37 20 20 20 900x615x200 21 26 26 1/2 1/2 5/8 φ12.7 φ12.7 φ15.9 1/4 1/4 3/8 φ6.35 φ6.35 φ9.52 φ20 φ30 φ30 1.5 1.5 1.5
INV-R71P/ NaE-K 7.1 8.0 100 1000 589 42/40/38 20 1100x615x200 30 5/8 φ15.9 3/8 φ9.52 φ30 1.5
29
FOUR WAY CASSETTE TYPE
) Four Four-way way Cassette Type › Compact, light weight and square panel in the same size for easy installation.
Compact act Four-way Four way Cassette Cassette Type › Compact size of 650mm x 650mm for 2.8kW – 5.6kW
650mm
960mm
960mm
30
650mm
› A slim unit below 5.0kW is only 190mm in thickness. It can be installed in a narrow ceiling space of at least 210mm.
› Only 230mm in thickness that can be installed in a ceiling space of at least 250mm.
› Drain pump fitted as standard with increased lift of 1100mm.
› Drain pump fitted as standard with increased lift of 500mm.
Common characteristics › Low noise with 3 – dimensional blade.
Diffuser
3-dimensional blade
› The full-automatic operation, the 4-way air supply, the 3-speed fan setting and the strong circulating air flow volume, make the cooled or heated air to reach directly every corner of the room. This can be succeded even if the ceiling is higher than standard height. • The units below 7.1kW are applicable to height below 3m.
• The units below 8kW are applicable to height below 4.5m.
› Air supply in different directions with 30-60 degree sweep for even better temperature distribution*
✍ Note: the guide louver defaults to min. position of 30° during cooling, dry and fan operation, or maximum position of 60° during heating operation.
› Designed with fresh air baffle for fresh air introduction.
› Long life and washable filter.
31
Four-Way Cassette Type MODEL Power supply
INV-R28T/Na-K
Cooling (kW) Heating (kW) Power consumption (W) m3/h Aiflow rate CFM Sound pressure level (H/M/L) (dB(A)) Capacity
Connection pipe Drain Pipe Main body Panel
Gas (Flare) Liquid (Flare)
Inch mm Inch mm
External dia. (mm) Thickness (mm) Dimensons (WxDxH) (mm) Net Weight (kg) Dimensons (WxDxH) (mm) Net Weight (kg)
MODEL Power supply Cooling (kW) Heating (kW) Power consumption (W) m3/h Aiflow rate CFM Sound pressure level (H/M/L) (dB(A))
Drain Pipe Main body Panel
32
25 6.5
INV-R56T/Na-K
Capacity
Connection pipe
2.8 3.2 65 680 400 37/35/33 3/8 φ9.52 1/4 φ6.35 φ30 1.5
Gas (Flare) Liquid (Flare)
Inch mm Inch mm
External dia. (mm) Thickness (mm) Dimensons (WxDxH) (mm) Net Weight (kg) Dimensons (WxDxH) (mm) Net Weight (kg)
5.6 6.3 83 1.180 694 39/37/35 5/8 φ15.9 3/8 φ9.52 φ30 1.5 30 6.5
INV-R36T/Na-K
INV-R45T/Na-K
1-Phase, 220-240V, 50HZ 3.6 4.5 4.0 5.0 65 65 680 680 400 400 37/35/33 37/35/33 1/2 1/2 φ12.7 φ12.7 1/4 1/4 φ6.35 φ6.35 φ30 φ30 1.5 1.5 840x840x190 25 25 950x950x60 6.5 6.5
INV-R63T/Na-K
INV-R80T/Na-K
1-Phase, 220-240V, 50HZ 6.3 8.0 7.1 8.8 83 83 1.180 1.180 694 694 39/37/35 39/37/35 5/8 5/8 φ15.9 φ15.9 3/8 3/8 φ9.52 φ9.52 φ30 φ30 1.5 2.5 840x840x240 30 30 950x950x60 6.5 6.5
INV-R50T/Na-K 5.0 5.8 65 680 400 37/35/33 1/2 φ12.7 1/4 φ6.35 φ30 1.5 25 6.5
INV-R90T/Na-K 9.0 10.0 133 1.860 1.095 40/38/36 5/8 φ15.9 3/8 φ9.52 φ30 3.5 840x840x320 38 6.5
Four-Way Cassette Type MODEL Power supply
INV-R100T/Na-K
Cooling (kW) Heating (kW) Power consumption (W) m3/h Aiflow rate CFM Sound pressure level (H/M/L) (dB(A)) Capacity
Connection pipe Drain Pipe Main body Panel
Gas (Flare) Liquid (Flare)
Inch mm Inch mm
External dia. (mm) Thickness (mm) Dimensons (WxDxH) (mm) Net Weight (kg) Dimensons (WxDxH) (mm) Net Weight (kg)
10.0 11.0 133 1.860 1.095 40/38/36 5/8 φ15.9 3/8 φ9.53 φ30 1.5 38 6.5
INV-R112T/Na-K
INV-R125T/Na-K
1-Phase, 220-240V, 50HZ 11.2 12.5 12.5 13.5 133 133 1.860 1.860 1.095 1.095 40/38/36 40/38/36 5/8 5/8 φ15.9 φ15.9 3/8 3/8 φ9.52 φ9.52 φ30 φ30 1.5 1.5 840x840x320 38 38 950x950x60 6.5 6.5
INV-R140T/Na-K 14.0 14.5 133 1.860 1.095 40/38/36 5/8 φ15.9 3/8 φ9.52 φ30 1.5 38 6.5
Compact Four-Way Cassette Type MODEL Power supply
INV-R22T/NaA-K
Cooling (kW) Heating (kW) Power consumption (W) m3/h Aiflow rate CFM Sound pressure level (H/M/L) (dB(A)) Capacity
Connection pipe Drain Pipe Main body Panel
Gas (Flare) Liquid (Flare)
Inch mm Inch mm
External dia. (mm) Thickness (mm) Dimensons (WxDxH) (mm) Net Weight (kg) Dimensons (WxDxH) (mm) Net Weight (kg)
2.2 2.5 12 600 353 47/44/41 3/8 φ9.52 1/4 φ6.35 φ30 1.5 20 2.5
INV-R28T/NaA-K
INV-R36T/NaA-K
1-Phase, 220-240V, 50HZ 2.8 3.6 3.2 4.0 12 12 600 600 353 353 47/44/41 47/44/41 3/8 1/2 φ9.52 φ12.7 1/4 1/4 φ6.35 φ6.35 φ30 φ30 1.5 1.5 570x570x230 20 20 650x650x50 2.5 2.5
INV-R45T/NaA-K 4.5 5.0 12 600 353 47/44/41 1/2 φ12.7 1/4 φ6.35 φ30 1.5 20 2.5
33
ONE-WAY CASSETTE TYPE ) High flexible
D i pump lift ) Drain
› Highly flexible installations for various needs.
› Drain pump flitted as standard with increased lift of 700mm.
) The unit is applicable to height below 3.5m
) Detachable and washable grille
) Ultra quiet operation
) Comfortable
Low noise cross flow fan reduces vortex flow in the duct thus reducing the noise.
The equal and gentle air supply design and the advanced air flow controlling design make the room temperature equal and balanced. So, the people inside the room feel more comfortable.
) Long life and washable filter MODEL Power supply
INV-R22Td/NaA-K
Cooling (kW) Heating (kW) Power consumption (W) m3/h Aiflow rate CFM Sound pressure level (dB(A)) Capacity
Connection pipe Drain Pipe Main body Panel
34
Gas (Flare) Liquid (Flare)
Inch mm Inch mm
External dia. (mm) Thickness (mm) Dimensons (WxDxH) (mm) Net Weight (kg) Dimensons (WxDxH) (mm) Net Weight (kg)
2.2 2.5 42 450 265 45/43/41 3/8 φ9.52 1/4 φ6.35 φ30 1.5 16 3
INV-R28Td/NaA-K 1-Phase, 220-240V, 50HZ 2.8 3.2 42 500 294 45/43/41 3/8 φ9.52 1/4 φ6.35 φ30 1.5 920x360x185 16 1180χ430χ30 3
INV-R36Td/NaA-K 3.6 4.0 42 500 294 45/43/41 1/2 φ12.7 1/4 φ6.35 φ30 1.5 16 3
FLOOR STANDING TYPE
Wireless FCU Wired remote controller WK-010PA-K
• Auto diagnosis • Fashionable and novel appearance • Quiet operation • Intelligent drainage device • Long life filter • Wider air supply and swing angle • Dynamic color display • Horizontal and vertical swing
Model / Heat pump Capacity
Cooling Heating
Power supply Motor power input Air flow volume Sound pressure level Connecting pipe Drain pipe Dimensions Net Weight
Gas Liquid External dia. Thickness WxDxH Body
kW kW V/Ph/Hz W m3/h CFM dB(A) inch inch mm mm mm kg
INV-R71L/Na-K
INV-R100L/Na-K
INV-R140L/Na-K
7.00 8.00 220-240/1/50 160 1100/1000/920 655/595/548 48/45/42 5/8 3/8 31 4.5 502x316x1756 39.0
10.00 11.00 220-240/1/50 185 1600/1500/1300 952/893/774 51/49/47 5/8 3/8 31 4.5 556x381x1896 53
14.00 15.00 220-240/1/50 200 1700/1600/1400 1012/952/833 52/50/48 5/8 3/8 31 4.5 556x381x1896 57
35
WALL MOUNTED TYPE
) Streamlined design for spaces without ceiling ) Anti cool air design
) Vertical auto swing
When heating in winter, intelligent anti cool air function is started.The unit blows only when the unit is pre-heated inside, to prevent it from blowing out cool air.
When cooling, the cool air is directed across the room and then it sinks. When heating, the warm air is directed across the floor and then it rises. Cooling
Heating
) Auto clean (under COOL & DRY mode)
) Low noise design
After the unit is turned off, the indoor fan will still operate in low speed in order to dry the inner components and parts. This way mould and odor are prevented from growing.
The advanced irregular-distance mixed flow fan, the unique duct design and the multi-grill auxiliary duct, make the operation highly efficient and the noise lower.
) Ternary filters Ternary air filters with anti-mildew, static electric dust capture and anti-bacterial function. Ternary filter
) Washable grille The front grille can be easily removed for washing.
36
MODEL
INV-R22G/ NaG-K
INV-R28G/ NaG-K
Cooling (kW) Heating (kW) Power consumption (W) m3/h CFM Sound pressure level (H/M/L) (dB(A)) Dimensions (WxDxH)(mm) Net weight (kg) Inch Gas (Flare) mm Connection pipe Inch Liquid (Flare) mm External dia. (mm) Drain Pipe Thickness (mm) EXV Position Aiflow rate
MODEL
2.2 2.5 50 500 294 38/36/34
m3/h CFM Sound pressure level (H/M/L) (dB(A)) Dimensions (WxDxH)(mm) Net weight (kg) Inch Gas (Flare) mm Connection pipe Inch Liquid (Flare) mm External dia. (mm) Drain Pipe Thickness (mm) EXV Position Aiflow rate
2.8 3.2 50 500 294 38/36/34
3.6 4.0 60 630 371 44/41/38
10.5 3/8 φ9.52 1/4 φ6.35 φ28 4
13 1/2 φ12.7 1/4 φ6.35 φ28 4
843x180x275 10.5 3/8 φ9.52 1/4 φ6.35 φ28 4
4.5 5.0 60 630 371 44/41/38 940x200x298 13 1/2 φ12.7 1/4 φ6.35 φ28 4
Intergrated
INV-R50G/ NaG-K
Power supply Cooling (kW) Capacity Heating (kW) Power consumption (W)
INV-R45G/ NaG-K
1-Phase, 220-240V, 50HZ
Power supply Capacity
INV-R36G/ NaG-K
5.0 5.8 60 630 371 44/41/38 940x200x298 13 1/2 φ12.7 1/4 φ6.35 φ28 4
INV-R56G/ NaG-K
INV-R71G/ NaG-K
1-Phase, 220-240V, 50HZ 5.6 7.1 6.3 8.0 70 70 800 800 471 471 44/41/38 44/41/38 1008x221x319 15 15 5/8 5/8 φ15.9 φ15.9 3/8 3/8 φ9.52 φ9.52 φ28 φ28 4 4 Integrated
INV-R71G/ NaB-K
INV-R80G/ NaB-K
7.1 8.0 8.0 9.0 63 65 1.200 1.200 706 706 49/45/42 49/45/42 1178x227x326 17.5 17.5 5/8 5/8 φ15.9 φ15.9 3/8 3/8 φ9.52 φ9.52 φ30 φ30 1.5 1.5 External
37
FLOOR CEILING TYPE ) Compact and light weight Only 238mm in height
) Ultra quiet operation
) Long life, detachable and washable grille
) Easy to install and good looking, satisfies more requirements
38
) Easy maintenance Convenient disassembly and maintenance thanks to unique design. › Plastic filter with buckles › Grill buckle
› Dismountable motor
) Wide discharge range With cross-direction sweep. The air supply range is efficiently wider.
) Drain pump lift reaches 1100mm
39
Floor ceiling (EXV Integrated) MODEL
INV-R28Zd/NaB-K
Power supply Cooling (kW) Capacity Heating (kW) Power consumption (W) m3/h CFM
Aiflow rate Sound pressure level (dB(A)) Dimensions (WxDxH) (mm) Net weight (kg) Connection pipe Drain Pipe
Inch Gas (Flare) mm Inch Liquid (Flare) mm External dia. (mm) Thickness (mm)
MODEL
2.8 3.2 55 650 383 40 40 3/8 φ9.52 1/4 φ6.35 φ17 1.75
INV-R90Zd/NaB-K
Power supply Cooling (kW) Capacity Heating (kW) Power consumption (W) m3/h CFM
Aiflow rate Sound pressure level (dB(A)) Dimensions (WxDxH) (mm) Net weight (kg) Connection pipe Drain Pipe
40
Inch Gas (Flare) mm Inch Liquid (Flare) mm External dia. (mm) Thickness (mm)
9.0 10.0 180 1.600 942 51 1420x245x700 54 5/8 φ15.9 3/8 φ9.52 φ17 1.75
INV-R36Zd/NaB-K
INV-R50Zd/NaB-K
1-Phase, 220-240V, 50HZ 3.6 5.0 4.0 5.8 55 110 650 950 383 559 40 45 1.220x225x700 40 40 1/2 1/2 φ12.7 φ12.7 1/4 1/4 φ6.35 φ6.35 φ17 φ17 1.75 1.75
INV-R112Zd/NaB-K
INV-R125Zd/NaB-K
1-Phase, 220-240V, 50HZ 11.2 12.5 12.5 13.5 250 250 2.000 2.000 1.777 1.777 55 55 1700x245x700 64 66 5/8 5/8 φ15.9 φ15.9 3/8 3/8 φ9.52 φ9.52 φ17 φ17 1.75 1.75
INV-R71Zd/NaB-K 7.1 8.0 140 1.400 824 49 1420x245x700 52 5/8 φ15.9 3/8 φ9.52 φ17 1.75
INV-R140Zd/NaB-K 14.0 16.0 250 2.000 1.777 55 66 5/8 φ15.9 3/8 φ9.52 φ17 1.75
CONCOLE TYPE
• Vertical swing • Anti-cold function • Quiet operation • Comprehensive protection • Auto restart • Compact design • Easier maintainability
MODEL
INV-R28-C/Na-K
Power Supply Cooling (kW) Capacity Heating (kW) Power consumption (W) m3/h Air flow rate CFM Sound pressure level (H/M/L) (db(A)) Dimenions (WxDxH) (mm) Net weight (kg) inch Gas mm Connection pipe inch Liquid mm
2.8 3.2 60 500-430/370/280 294-253/218/165 38/33/26
3/8 φ9.52 1/4 φ6.35
INV-R36-C/Na-K 1-Phase, 220-240V,50Hz 3.6 4.0 60 600-520/440/360 353-306/259/212 40/37/32 700x215x600 16 3/8 φ9.52 1/4 φ6.35
INV-R28-C/Na-K 5.0 5.5 60 650-620/500/410 383-365/294/241 46/41/35
1/2 φ12.7 1/4 φ6.35
41
TREATED FRESH AIR DUCT TYPE ) Provide fresh air of temperature that is close to the indoor ambient, ensures fresh and comfortable indoor air. ✍ Note: The capacity of fresh air ducted unit should be less than 30% of the capacity of outdoor unit.
) Comfortable › Makes you feel comfortable, like in the nature. It is introducing the outdoor fresh air, after treatment, in to the room.
42
› Treated fresh air supplying temperature is close to the indoor temperature (factory setting at 22 Celsius), reducing the cooling load of other indoor units.
) Easy control › Wired remote control
› Wireless remote control
› Centralized control
› Long-distance monitoring
› Sub-room switch
› Memory function
› Auto restart after power recover
› Weekly timer
) Flexible application › The indoor unit with high static pressure can realize long-distance fresh air supply to all corners of the room. So, it is greatly applicable to places that there is high density of people. › The standard pressure is 200Pa and the optional range is 50-300Pa.
MODEL Power supply Capacity (At rated ESP) Power input1 Aiflow Volume
Cooling (kW) Heating (kW) Cooling (kW) Heating (kW) CFM m3/h
Sound pressure level (H/M/L) (dB(A)) Rated (Pa) External Static Pressure Range (Pa) Dimensions (WxDxH) (mm) Weight (kg) Valve Connection Type Length (m) Connection pipe Gas additional charge (g/m) Liquid Pipe (Inch) Gas pipe (Inch)
INV-R140P/ Na(X1.2)-K
INV-R224P/ Na(X2.0)-M
INV-R280P/ Na(X2.5)-M
INV-R280P/ Na(X3.0)-M
220V, 50Hz, 1 Phase 14 10 0.5 0.5 706 1200 42 150 50~150 1463x756x300 63.5 Flare Connection 7.5 54 3/8 5/8
380V, 50Hz, 3 Phase 22.4 16 1.1 1.1 1177 2000 47 200 50~200 1500x1000x500 130 Brazing Connection 7.5 54 3/8 7/8
380V, 50Hz, 3 Phase 28 20 1.1 1.1 1471 2500 48 200 50~200 1500x1000x500 150 Brazing Connection 7.5 54 3/8 7/8
380V, 50Hz, 3 Phase 28 20 1.1 1.1 1766 3000 51 200 50~200 1500x1000x500 150 Brazing Connection 7.5 54 3/8 7/8
43
CONTROL NETWORK SKETCH Air Conditioning Individual Control
System
Communication module ME30-00/E2
Group Controller ZJA011
Wired Remote Controller Z63351F/Z63151F Z60351F/Z60151F
Communication module ME30-00/E2 Wired Remote Controller ZX60451
Wireless Remote Controller YB1FA Y512 RS-422/485 Repeater
Key-card Control Board MK03
Key-card
IR Receiver Unit JS01 (Field supplied)
✍ Note: • Control network sketch is for reference only, please refer to the equipment manuals for actual cable connection method.
44
Air Conditioning Central Control RS-232 to RS-422/485 Converter
Building Management
INVENTOR AC Eudemon 2009 (Monitoring Software) Module link
FE30-00/A(M)
Transmission line (INV network) Group controller line Remote Controller line
RS-232 to RS-422/485 Converter
Modbus network
Web Monitoring Client
IR receiver line Key-card control board line
Internet
Key-card signal line
Web Monitoring Client
Communication module ME30-00/E2 Centralized Controller CE51-24/E(M)
Smart Zone Controller CE50-24/E
Building Management System
BMS Interface (Modbus) ME30-00/E2
Commissioning Program (Software) Text Parser
45
CONTROLLERS COMPARISON ITEM
Connections
Control functions
Wired Smart Centralized Wired Wireless Wireless INVENTOR BMS Group Remote Controller Zone Remote remote remote AC Eude- Interface Controller Controller Controller CE51-24/ Controller Controller controller mon 2009 (Modbus) ZJA011 Z63351F/ CE50-24/E E(M) XK02 YB1FA Y512 Z60351*
Max Nos. of Outdoor Units
-
-
-
-
-
-
64
Max Nos. of Wired Controller
1
1
1
1
16
16
1024
n*255*16 n*255*16
Max Nos. of Indoor Units
1
1
1
1
16
16
1024
n*255*16 n*255*16
ON/OFF
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
Fan Speed
✓
✓
✓
✓
✓
✓
Vertical Swing
✓
✓
✓
✓
✓
Energy Saving Mode
✓
✓
✓
✓
Turbo Mode ✓
✓
Light
✓
✓
Clock
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
Indoor unit Address
√
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
0.5h
1min
0.5h
0.5h
0.5h
0.5h
1min
1sec
Weekly Timer
✓
✓
✓√
Centralized Week Timer
✓
✓
Group Week Timer Shielding Centralized Shielding
✓ ✓
✓
✓
✓
✓
✓
Group Shielding Centralized Control
✓
✓
✓
✓
✓
✓ ✓
✓
Group Control
✍ Note: • n: Nos. of serial port • Control functions availability is based on the indoor units. Please refer to the user’s manual of indoor unit for details.
46
✓
Lock ON/OFF Timer
Centralized Control
✓ ✓
✓ ✓
Week
Minimum Timer Gap
Shielding
✓ ✓
✓
✓
Room Temp.
✓ ✓
✓
✓
Sleeping Mode Errors
Timer
n*255
Mode Setting
Drying
Display
n*255
✓
✓ ✓
COMMENTS OF CONTROL FUNCTIONS ) ON/OFF Timer Function
) Sleeping Function
Under ON/OFF state, set the unit to be automatically turned on or turned off in 0.5h hours (1≤n<48).
Automatically corrects the set temperature in order to prevent excessive cooling or heating during sleep. In cooling or defrosting mode, the set temperature will automatically increase 2°C in 2 hours (1°C per hour) and then the unit will operate at such temperature. In heating mode, the set temperature will automatically decrease 2°C in 2 hours (1°C per hour) and then the unit will operate at such temperature.
) Error Display When the malfunction occurs during the operation, the room temperature display area will show the error code. The picture here shows the code of compressor high-pressure protection.
Timer setting
Timer setting
60min
60min 1 0C
2 0C
0
1 0C
) Energy Saving Function By setting the minimum value of setting temperature in cooling and defrosting mode as well as the maximum value in heating mode, the unit can operate in smaller temperature range so as to save energy.
) Switch between Fahrenheit and Celsius Scale Under OFF state, press MODE and ▼ buttons simultaneously to switch between °C and between °F.
2C
✍ Note: There is no SLEEP function in FAN mode.
) Memory Function After power failure, if the unit is energized again, it will operate according to previous set, which includes setting temp, fan speed, swing angle, energy-saving mode, blow function etc.
) Blow Function (Only for cooling and heating mode)
) Turbo Function (In COOL or HEAT mode) The unit operates at super-high fan speed so as to cool or heat quickly so that the ambient temperature approaches the set temperature as soon as possible When the difference between the room temperature and the set temperature is not more than 2°C, this function will be turned off automatically.
When the unit is turned off, the indoor fan will keep running at low speed for 10min so as to dry the indoor evaporator, in order to prevent mildew and keep users healthy. This function can be memorized.
) Mute Function (Only for cooling and heating mode)
) Shield Function (Remote monitoring) The indoor unit is operated by remote control. At the same time the functions of the wired controller, such as ON/OFF, temp., mode setting, energy saving function etc, are shield.
Common mute function: the unit automatically operates at low speed and the fan speed can’t be adjusted at that time. Auto mute function: The unit will enter mute operation according to discrepancy between room temperature and setting temperature. At that time, fan speed can be manually turned down.
47
WIRED REMOTE CONTROLLER Z60351F/Z63351F (Heat pump)
51 1F (H Hea at pu pump mp p) Z60351F/Z63351F (Heat pump) 51 1F (C Coo ooli ling li ng go onl nlly) nl y) y) Z60151F/Z63151F (Cooling only)
• ON/OFF • Temperature setting • Fan speed setting • Energy-saving function • Room temperature display • Sleep function • Infrared remote control function is available and the remote controller is optional
• • • • • •
ON/OFF Timer Operation mode setting Vertical swing Self-diagnosis function (Error code display) Memory function Child lock function
Operating Mode Display (COOL, DRY, FAN, HEAT)
Mode Setting Button
Sleep Mode Display Temperature Setting Button Room Temperature Display /Error Displa Fan Speed Display (HIGH, MID, LOW, AUTO) Fan Speed Setting Button Set Temperature Display Sleep Mode Setting Button* Defrosting Display Timer Setting Button Timer Display Signal Receiver (For Remote Controller)
Model Name Power Supply Dimensions (HxWxD) (mm) Weight (g)
ON/OFF button
Z63351F / Z60351F DC12V (Supplied by the indoor unit) 85x85x20 94
* Z60351F is for duct type indoor unit, and swing function is unavailable; Z63351F is for other types of indoor unit, button ‘SLEEP’ changes to ‘SWING’, and sleep function is unavailable.
48
WIRED REMOTE CONTROLLER ZX60451
• ON/OFF • Displayed as white characters on black background • Fan speed setting • Self-diagnosis function (Error code display) • Turbo cooling/heating function • Quiet function • Enquire and setting address of wired controller
• ON/OFF Timer • Temperature setting • Vertical swing • Environmental temperature display • Evaporation function • Shield function • Infrared remote control function is available and the remote controller is optional
Operating Mode Display (COOL, DRY, FAN, HEAT)
• Touchable wired controller • Operating mode setting • Energy saving function • Sleep function • Memory function • Child lock function
Defrosting Operation Display
Sleep Mode Display
Key- card Display
Swing Display
Lock Display Timer Display
Fan Speed Display (AUTO, TURBO, LOW, MID, HIGH)
Set / Room Temprature Display Function Display Area
Temperature /Timer / Quiet Mode Setting button
Fan Speed Setting Button Operation Mode Setting Button
Enter / Cancel Button
On/Off Button
Functions Setting Button
Timer Setting Button
Model Name Power Supply Dimensions (HxWxD) (mm) Weight (g)
ZX60451 DC12V (Supplied by the indoor unit) 92x92x24 116
49
WIRELESS REMOTE CONTROLLER Y512
• ON/OFF • Temperature setting • Fan speed setting • Child lock function
• ON/OFF Timer • Operation mode setting • Vertical swing • Sleep function
Fan Speed setting button Swing Button Fan Speed Setting Display (HIGH, MID, LOW, AUTO) Operation Mode Display/ (AUTO, COOL, DRY, FAN, HEAT) Room Temperature/ Malfunction Display
Sleep Mode Display Timer Display Sleep Button Light ON/OFF Button Temperature/Timer Setting Button Timer ON Setting Button Timer OFF Setting Button Mode Setting Button
ON/OFF Button
Model Name Power Supply Dimensions (HxWxD) (mm) Weight (g)
50
Y512 AAA 1.5Vx2 159x56x18 92
WIRELESS REMOTE CONTROLLER YB1FA
• ON/OFF • Temperature setting • Fan speed setting • Energy-saving function • Room temperature display • Turbo cooling/heating function • Mute function • Child lock function
• ON/OFF Timer • Operation mode setting • Vertical swing • Self-diagnosis function (Error code display) • Sleep function • Blow function • Memory function (Turbo, Energy save, Quiet, Evaporation, etc. ) • Clock display
Fan Speed (HIGH, MID, LOW, AUTO) Operating Mode Display (AUTO, COOL, DRY, FAN, HEAT)
Room Temperature/Malfunction Display Timer Display
Sleep Mode Display Temperature Type Display Swing Angle Display ON/OFF Button
Child Lock Display Light Displayer Mode Setting Button
Temperature/ Timer Setting Button Fan Speed Setting Button Clock Setting Button
Swing Mode Setting Button Timer Setting Button
Blow Function ON/OFF Button Temperature Display Button Turbo Mode Setting Button
Light ON/OFF Button Sleep Mode Setting Button
Model Name Power Supply Dimensions (HxWxD) (mm) Weight (g)
YB1FA AAA 1.5Vx2 122x44x21 70
51
GROUP CONTROLLER ZJA011
) Group monitoring control and group wired control t l are the th h two t main control functions for group Controller. Group monitoring controller can monitor or control 16 indoor units of a group for inquiry and single or centralized control. Features: • For a region consisted of 1-16 indoor units both single and central control are available. • The wired controller buttons in a region of 16 indoor units can be shielded or locked. • It can time 16 indoor units in a region. • It has the function of power-off memory.
✍ Note: Wired controller must be reserved with the indoor unit that has been matched. Group wired controller could replace 1-16 selected wired controllers, in order to uniformly set or control the indoor units. Features: • It can uniform the time for the selected indoor units. • It can replace the wired controller, in order to control the selected indoor units in a region. • It has the function of power-off memory.
✍
Note: The wired controller that is matched with the indoor unit must be removed and the indoor unit must be re-energized after debugging.
No. Of indoor Unit Inquiry/Single or Central Control Setting Button
Inquiry/Control Display
Operating Mode Setting Button (COOL, DRY, FAN, HEAT)
Operating Mode Display/ (COOL, DRY, FAN, HEAT) Error display for indoor or outdoor unit
Long-Distance Shield Status Display Value Setting Button for Temperature/ Timer/Indoor Unit Number Selecting (Under INQUIRY Status)
Room temperature display/ Malfunction display Fan Speed Display (AUTO, HIGH, MID, LOW)
Forced Operation Display Fan Speed/ Swing Setting Button
Lock Display
Defrosting Operating Display
Swing Display Set Temperature/Timer Time Display
Timer Button (Under SINGLE / CENTRAL Status) ON/OFF Timer Inquiring of On-line Indoor Uni (Under INQUIRY Status)
ON/OFF Button
Model Name Power Supply Dimensions (HxWxD) (mm) Weight (g)
52
ZJA011 DC12V (Supplied by the indoor unit) 85x85x20 94
SMART ZONE CONTROLLER CE50-24/E • When the indoor units are connected to 3 sets of INV outdoor units, the air duct type indoor unit can be also connected. • Directly controls 16 indoor units in the network without extra communication module. played • If an indoor unit is being operated by its own control group, it can be inquired and displayed on the operation status. • Remote shield function. • Timer function. • Weekly Timer Function.
Operating Mode Display (AUTO, COOL, DRY, FAN, HEAT) Current Day of Week and Time Display
Fan Speed Display (HIGH, MID, LOW, AUTO)
Shield Status Display (From long distance) Setting Temperature / NO. of Indoor Unit Display
Error/Child Lock/Lock Display Environmental Temperature /COM # Display On-line or Selected Indoor Unit No. Display
Timer Display
Operation Mode Setting Button (COOL, DRY, FAN, HEAT) Indoor Unit NO. / Week Selecting
Fan Speed/Swing Setting Set Temperature/Timer Setting Button
Shield Setting Button
On/Off Button Timer/Clock Setting Button
Central Control Setting
Max 16
Serial 1 (multirequency)
Model Name Power Supply Dimensions (HxWxD) (mm) Weight (g)
Serial 2 (multirequency)
Serial 3 (multirequency)
CE50-24/E 220V~240V, 50/60Hz 120x120x62 391
53
CENTRALIZED CONTROLLER CE51-24/E(M)
• Clock setting. • Error alarm and error code display • Single/Group/Center Control (including weekly timer setting, shield setting, etc) • 64 communication modules can be connected and 1024 sets of indoor units can be controlled.
• Inquire and control the ON/OFF, operation mode, set temperature, fan speed, swing state, etc. of indoor unit. • Automatically detect and display the status of online “region” and indoor unit (including operation mode, set temperature, fan speed, swing, weekly timer, shield, etc). • Long distance shield function. • Up to 1km communication wires without repeaters.
Error Display
All Indoor Units ON/OFF Button
Current Region No. and Unit No. Display (for indoor unit)
Operation Mode Display Fan Speed Display (HIGH, MID, LOW, AUTO)
Group No. Display Online Region No. Display*
SWING Operation Display
Online Indoor Unit No. Display
Control Command Sending Display
CENTER/GROUP Operating or Setting Display
Shield Status Display
Day of Week and Time Display
Weekly Timer Display Set Temperature Display
Weekly Timer Display
Room Temperature Display
Direction Key (UP/DOWN/LEFT/RIGHT)
Swing Operation Setting Button Temperature Setting Button
Function Setting Confirmation Button
Operation Mode Setting Button Grouping Information Setting Button
Shield Setting Button
Back to Superior Menu Button
ON/OFF Button
Center Control Setting Button Clock Setting Button
Timer Setting or Inquiring Button
Group Control/Setting Button
Fan Speed Setting Button
Cancel Button
Max 64 Communication Module
Max 16
Model Name Power Supply Dimensions (HxWxD) (mm) Weight (g)
Communication Module
Max 16
CE51-24/E(M) 220V~240V, 50/60Hz 185x131x68 557
* All indoor units connected by one communication module are automatically distributed in one region.
54
Communication Module
Max 16
IR RECEIVER & KEY-CARD CONTROL BOARD JS01 / MK03
) IR receiver JS01 It is applicable to INV duct type indoor unit and equipped with LED lamp for status indication and infrared remote control function. LED Lamp
Signal Receiver: it is used for receiving command sent from remote controller Heating ON/OFF and Cooling ON/OFF
Model Name Power Supply Dimensions (HxWxD) (mm) Weight (g)
JS01 DC5V (Supplied by the indoor unit) 120x70x58.5 172
) Key-card Control Board MK03 • This direction control board is only suitable for INVENTOR multi-variable (INV) indoor unit with gate-control function. • The AC will operate after plugging in the gate-control card and stop operating after pulling out the card. • Upon pulling out the card in order to stop the unit, the running states of the unit will be memorized. • After plugging in the card, the unit will be under standby state or resume running according to settings. • The AC will operate when the customer plugs in the card and automatically stop when he pulls out the card. This ensures that the unit will turn off after people leave the room and that energy will be saved.
Model Name Power Supply Dimensions (HxWxD) (mm) Weight (g)
MK03 220V~240V, 50/60Hz or DC5V~24V (Supplied by the indoor unit) 73x73x36 65
55
COMMUNICATION MODULE ME30-00/E2
) Functions • The communication module (ME30-00/E2) is used for transforming and transmitting signals of the computer and the air conditioning system. It acts as a communication controller. • Modbus protocol and RS485 interface are adopted so that the unit can be connected to user’s BMS system and other networks. • Lots of monitoring nodes make possible to have as many as 255 units in the same network. • Control of setting parameter is available. • Monitoring of operation state is available. • Monitoring of malfunction state is available.
POWER
RS485 Interface
Power Indicator (Red) Communication Indicator (Green)
PC or COM2 of Other Module
Unit 9~12V DC 800mA
Model Name Power Supply Dimensions (HxWxD) (mm) Weight (g)
56
ME30-00/E2 220V~240V, 50/60Hz 185x131x68 557
COMMISSIONING PROGRAM Text Parser
) Brief introduction • This software receives data from the INV system through local COM port or network (both internet and LAN are suitable) and then analyses these data according to communication protocol. • Running parameters of unit, after analysis, will be displayed and saved in real time. There are two kinds of displaying methods, the text displaying and the curve displaying. The analytic data can be saved in database. Technician and service person can use this software to do commissioning.
Real-time parameter display
Operating System
CPU HDD Memory
Curves Analysis
Microsoft® Windows® 2000 Professional (English version / Service pack 4 or later) Microsoft® Windows® XP PROFESSIONAL (English version / Service pack 2 or later) Microsoft® Windows Vista® Home premium / Business / Enterprise / Ultimate Microsoft® Windows® 7 Home premium / Business / Enterprise / Ultimate 64-bit version of Windows® are not supported Intel® Pentium® / Celeron®, AMD® Athlon™ / Duron™ 1Ghz or higher 4 GB or more of free space 512MB or more
57
RS-422/485 R REPEATER (ISOLATED) ) Functions Rs-422/485 repeater (isolated) is used to amplify the communication signal when the quantity of communication modules in the network is more than 30, or communication distance is longer than 800m.
RS-422/485
Operation Indication LEDs
RS-422/585
Power
Maximum 30 Nos. of module between two repeaters
Power Supply Dimensions (HxWxD) (mm) Weight (g)
58
Maximum cable length between two repeaters is 800m
Input AC 220V~50/60HZ Output 12~30 DC 800mA 96 x 100.6 x 25 277
RS-232 TO RS-422/485 CONVERTER (ISOLATED) ) Functions RS232-RS485 opt electronic isolated converter is used for converting the signal between computer / BMS System (RS232) and INVENTOR Air Conditioning Systems (RS485).
RS-422/485
Operation Indication LEDs
RS-232 Power
Power Supply Dimensions (HxWxD) (mm) Weight (g)
Input AC 220V~50/60HZ Output 12~30 DC 800mA 96 x 100.6 x 25 263
59
INVENTOR AC EUDEMON 2009 PC SUIT ) Brief introduction of INVENTOR AC Eudemon 2009 009 INVENTOR AC Eudemon 2009 is the latest solution for controlling, monitoring and management of INVENTOR central air conditioning systems with your PC. › Maximum Connectable Systems/ Outdoor Units: 255 › Maximum Connectable Indoor Units (INV System): 4,000 › Maximum Control Distance: 5,600m (Standard distance 800m & extendable to 5.6km) › Compatible Systems: INV System, Centrifugal Chiller, Water-cooled screw chiller, Air-Cooled screw chiller, Air-cooled scroll chiller, etc.
) System schematic plan INVENTOR AC Eudemon 2009 Management System/BMS Network Schematic Plan
Personal Computer
BMS System
INVENTOR AC Eudemon 2009
Serial Port Max 255
More AC Units
Convertor RS485 Network Protocol (Modbus)
Max 255 Communication Module 1 Max 16
Communication Module n Max 16
✍ Note: • In a RS485 Network, different type of systems cannot be connected. • User can only choose either INVENTOR AC Eudemon 2009 or BMS (Modbus) to manage the Air-conditioner system.
60
Communication Module 255 Max 16
) Functions of INVENTOR AC Eudemon 2009 › Air Conditioning System running status / error information checking. › Air Conditioning System Operation Parameter setting. › Multi User Management with different authorized levels. › Intelligent Timer with simplified schedule management. › Multi Serial port and Multithreading Monitoring. › Automatic Detection enables quick monitoring even if the user is not familiar with the concept of equipments, protocol and models, etc. › Vivid network plan helps the easy understanding of the physical structure of the air conditioning system. › Vivid location plan helps easy management of the air conditioning system.
) Functions of INVENTOR AC Eudemon 2009 Model name
INVENTOR AC Eudemon 2009 FE30-00/A(M)
Content
INVENTOR AC Eudemon 2009 CD-ROM x 1 PCS RS232-RS485 Opto electronic Isolated Convertor x 1 PCS
) Requirement of PC for INVENTOR AC Eudemon 2009 Operating System CPU HDD Memory
Microsoft® Windows® XP PROFESSIONAL (English version / Service pack 2 or later) Microsoft® Windows Vista® Home premium / Business / Enterprise / Ultimate Microsoft® Windows® 7 Home premium / Business / Enterprise / Ultimate 64-bit version of Windows® are not supported Intel® Pentium® / Celeron®, AMD® Athlon™ / Duron™ 1Ghz or higher 10 GB or more of free space 1GB or more Internet Explorer® 6.0 SpP1 or later (.NET Framework supported) Microsoft® . NET framework® 2.0
Software Environment
Microsoft® SQL Server® 2005 Express Microsoft® Data Access Components (MDAC) 2.8 SP1 or later. Microsoft Visual C++® 2008 Redistributable SP1
61
PIPING DESIGN PROGRAM INV SELECTOR ) BRIEF Introduction › INVENTOR INV Selector is a program for doing the piping design of INV VRF systems.
› Interface of the main program.
62
) The software provides two ways to output the design › Excel summary files: it consists of the equipment summary, design condition, system details and remote monitor detail.
› AutoCAD drawings: Electrical & Communication wiring design of the system.
› Download “VRF Selection Software” www.inventor.ac/tech_spec
Operating System
CPU HDD Memory
Microsoft® Windows® 2000 Professional (English version / Service pack 4 or later) Microsoft® Windows® XP Professional (English version / Service pack 2 or later) Microsoft® Windows Vista® Home premium / Business / Enterprise / Ultimate Microsoft® Windows® 7 Home premium / Business / Enterprise / Ultimate 64-bit version of Windows® are not supported Intel® Pentium® / Celeron®, AMD® Athlon™ / Duron™ 1Ghz or higher 4 GB or more of free space 512MB or more AutoDesk® AutoCAD® Excel 2004/2005/2008
Software Environment
Microsoft Office® Excel 2000/2003/2007 Professional Microsoft Visual C++® 2008 Redistributable SP1
63
ENERGY RECOVERY VENTILATION ) Introducing outdoor fresh air and discharging arging indoor air. air Makes you feel comfortable as in the nature.
Shell
Indoor air outlet Fresh air outlet
Indoors air inlet
Electrical box Heat exchanger Fresh air outlet Air filter
Lug
) Energy saving › Unique by-pass mode can reduce power consumption of fan motor, in order to prolong lifetime of the heat exchanger core. › By the combination of heat exchange mode and by pass mode, the unit load can be reduced about 26% in a year.
Power reduction ratio
› Internal heat exchanger performs cooling and heating exchange between the discharged air and fresh air. Energy-recovery rate above 70%, high energy saving.
0% Direct fresh air introduction
Air Supply Discharge air
20%
Independent heat exchange process
Temp plate
Heat exchange mode Air exchange fan
Heat exchange element
26%
Heat exchange combined with by-pass proccess
By-pass mode Room temperature sensor
Air exchange fan
Heat exchange element
Indoor air temperature sensor
Exchange air
Return air
Exchange air
Return air
Outdoor air intake
Supply air
Outdoor air intake
Supply air
Outdoor air temperature sensor
64
Air supply fan
Outdoor air temperature sensor
Air supply fan
) High efficiency heat exchange The ERV can exchange the latent heat and sensible heat simultaneously, which can adjust temperature and humidity at the same time. It can be widely applied where there is big humidity difference between indoor and outdoor. › Heat exchange (sensible heat) inside the core Heat is exchanged between discharged air and fresh air, so that the fresh air temperature to come down and be close to the indoor temperature. The feeling of uncomfortable is avoided and meanwhile the load of air conditioning is effectively decreased.
› Exchanege of humidity (latent heat) The vapour on the side with high humidity is absorbed by hygroscopic agent and discharged to the side with low humidity through capillary action of the fibber. › Through heat exchange between the indoor air and fresh air, the internal heat exchanger reduces the fluctuation of indoor temperature. At the same time it prevents from high temperature difference of the supply air, while reducing the operation load of the unit.
Moisture absorption Move through capillary Moisture release
› Air Filtration and purification Function • Internal air filter keeps the fresh air introduced into room pure and dustless. • The efficient isolation between fresh air duct and discharge air duct ensures pure air supply. • With antibacterial and anti-mildew materials, the heat exchange core is suiting for healthy. › Wide range of models 7 models in a range of 350~3000m3/h, which can fit for different spaces and reduce the waste of power. Wide range from 350 to 3000 m3/h, matching with buildings of various structures.
› Flexible control • LED display • Energy saving mode • 24h timer • Centralized controller • Weekly timer • Long-distance Monitoring Control (optional)
› Reliability and easy maintenance • The complete unit with non-moving parts except the fan motor can reliably operate for a long period of time, without frequent maintenance. • Filter and heat exchange core can be easily taken out from the access door for cleaning.
› Low-noise Design Build-in low noise ventilation fan.
› Compact design and easy installation With a minimum height of 360mm, the unit is space saving. It can be installed inside limited ceiling spaces.
) Installation example Fresh air duct
Fresh air inlet Fresh air Supply
Indoor air outlet Discharge air duct Insulation material
Indoor air return
Fresh air outlet
Room air inlet
65
SPECIFICATIONS ) ERV
MODEL Power supply Power Input (W) Airflow rate Sound pressure level (dB(A)) External static pressure Temperature exchange efficiently Enthalpy exchange efficiency
HRVQ-D3.5-K
H/M/L H/M/L H/M/L Heating (H/M/L) Cooling (H/M/L)
m3/h CFM Pa %
Dimension (WxDxH) (mm) Net weight (Kg)
MODEL Power supply Power Input (W) m3/h CFM
Airflow rate Sound pressure level (dB(A)) External static pressure Temperature exchange efficiently Enthalpy exchange efficiency Dimension (WxDxH) (mm) Net weight (Kg)
66
Pa Heating Cooling
%
165 360/260/210 212/153/124 37 100/80/60 71/73/75 65/67/68 61/63/65 800x879x306 45
HRVQ-D5-K
HRVQ-D8-K
220 240V, 1Ph, 50Hz 262 400 500/380/300 800/600/480 294/224/176 471/353/282 39 45 100/80/60 110/85/65 68/70/72 70/72/74 62/64/65 63/65/67 57/59/61 60/62/64 800x879x306 832x1016x380 45 57
HRVQ-D10-K 440 1000/750/600 588/441/353 46 110/85/65 75/77/79 66/68/70 62/64/65 832x1016x380 57
HRVQ-D15-M
HRVQ-D20-M
HRVQ-D30-M
600 1500 882 48 150 73 65 60 1210x1215x452 100
380~415V 3N~50Hz 950 2000 1176 50 150 71 62 58 1210x1215x452 100
2800 3000 1176 54 220 70 62 58 1340x1550x572 240
CONNECTION BRANCHES ) Modular Outdoor Unit Branch Joint
) Indoor Unit Y-Type Branch Joint
Gas Pipe
Gas Pipe
Liquid Pipe
Liquid Pipe
Modular Outdoor Unit Branch Joint Model Name ML01R ML02R
Configuration Configuration
22.4 ≤ X ≤ 96 96 < X
Indoor Unit Y-Type Branch Joint Model Name FQ01A/A FQ01B/A FQ02/A FQ03/A FQ04/A FQ01Na/A FQ02Na/A FQ03Na/A FQ04Na/A FQ05Na/A FQ06Na/A FQ07Na/A
Configuration X ≤ 20.0 20.0 < X ≤ 30.0 30.0 < X ≤ 70.0 70.0 < X ≤ 135.0 135.0 < X X ≤ 5.6 5.6 < X ≤ 22 22 < X ≤ 30 30 < X ≤ 68 68 < X ≤ 96 96 < X ≤ 135 135 < X