Data Centre Complete for the MOD – Yeovil
Data Centre Complete for the MOD – Yeovil Electrical Distribution System From the automatic change over panel the power was distributed via a distribution panel incorporating control switching and wrap around loop for the UPS. A Socomec 120Kva UPS provides back up power at this point. The battery was split by isolators into 120volt DC maximum strings.
New Buildings were constructed to accommodate the Tier 2 Data Centre and provided within electrical power supply and UPS, standby power, environmental control, BMS, fire detection, lighting and earthing. Principles of Services Design:Mechanical Services Systems Close control air conditioning is provided in the Data Hall comprising of 3 Denco internal units each provided with two refrigerant circuits connected to externally mounted condenser units. Two of the air conditioning units are intended to run and one act as standby, the BMS will control an operating pattern giving full shared running times. The fresh air unit has run and standby facilities. The UPS Plantroom has two down flow air conditioning units one run and one standby.
uptimeplus.co.uk
Supplies to 24 server racks are fed via 32amp type C MCB’s located in the PDU’s. Each server rack has two electrical supplies, one from each PDU. The feeds from the commando sockets in the PDU’s to the server racks are using HO7 flexible cables with inline commando plugs and sockets. The UPS was designed with maintenance by pass to the distribution board, with a standby 350Kva generator, to complete the topology. This new data centre was built and Constructed by Integral’s uptimeplus team.
welcome to the revolution.
your world...is our world
uptimeplus.co.uk
uptimeplus
1290 Aztec West, Almondsbury, Bristol BS32 4SG Tel: 07802 383 431 Fax: 01454 201169 Help Desk: 01454 278911
uptimeplus@integral.co.uk
A revolution in critical environment maintenance.