UPS A3&A5 QUICK GUIDE
UPS A3 & A5 Quick Guide User’s Manual
Copyright AST 2010
www.ast-global.com
UPS A3&A5 QUICK GUIDE 1.
Table 1 Safety Symbols and Means Safety
Symbols
Means Secure alarm
Risk of electric shock
2.
Table 2 UPS Main Performance Index Model
A5
characteristic
Rating voltage
Characteristic
Capacity
Characteristic
Output
Output
Input
Index (V)
In range 120V~290V, 50% load,in range 160V~290V, full load
Rating frequency (Hz)
50/60 ±10%
Input mode
Single-phase three-line
Battery voltage
(V)
192
(VA/W)
5000/3500
3000/2100
Voltage
(V)
230±1%
Frequency
(Hz)
50/60Hz (Battery mode)
Waveform
Sine wave 105%~129% Load, lasting 60 seconds , or 130%~150% Load, lasting 30
Overload capacity
seconds turn to BYPASS
Output mode
Line bar
Panel display
LED
Warning function Other Characteristics
A3
Battery low voltage, abnormal power supply, UPS malfunction, overload Battery low voltage protection, overload protection, short-circuit protection and
Protection function
over temperature protection, over voltage protection
Working temperature
-20 ~ 40℃
Relative humidity Size (mm)
0 ~ 95%,No condensation A3/A5: 440×700×130
(W×D× H)
External Battery Cabinet: : 440×460×176 Weight
A3/A5: 17.5
(kg)
External Battery Cabinet: : 55.5(including BAT. 7Ah,16 PCS)
3.
Panel Indicator Illuminate: BYPASS
①
③
②
①、BYPASS Indicator light ②、Mains supply Indicator light
④
③、INVERTER Indicator light LINE
LOAD
INV.
100%
100%
⑥
⑤
④、Capacity indicator of load (contain four lights, each Standing for 25% of total capacity.)
FAULT
Copyright AST
2010BAT.
⑦ ON/TEST
POWER
www.ast-global.com
⑧ OFF
UPS A3&A5 QUICK GUIDE ⑤、Capacity indicator of Battery Indicator light (contain four lights,each standing for 25% of total capacity.) ⑥、FAULT Indicator light ⑦、“ON/TEST” Key START UPS (Please press the “ON” key for 0.5 seconds to run the UPS.) ⑧、“OFF” Key (Please press the “OFF” key for 0.5 second to turn off the UPS.) Press “ON/TEST” for 3 seconds to make the buzzer quiet on battery mode, while power on.
4.
Rear Panel
1
Fuse 250V/15A
AC OUTPUT 10A MAX.
AC OUTPUT 16A MAX. Fuse 250V/10A
Fuse 250V/15A DC INPUT 192V/12.4A
L
N
PE
AC INPUT 230V/20.6A
DIP SWITCH RS232
USB
DRY CONTACT
EPO
L
N
PE
AC INPUT 230V/20.6A
8
9
7
6
5
4
3
2
Fig .1 A5 Rear Panel 1. Output Socket
2. Terminal for DC Input
3. Output fuse
4. Terminal for AC Input
6. Dip switch
7. EPO
8. RS232
9. USB
5. Dry contact
1
Fuse 250V/15A
AC OUTPUT 10A MAX.
AC OUTPUT 16A MAX. Fuse 250V/10A
Fuse 250V/15A DC INPUT 192V/12.4A
DIP SWITCH USB
RS232
DRY CONTACT
EPO
AC INPUT 230V/12A
9
8
7
6
5
4
3
2
Fig.2 A3 Rear Panel 1. Output Socket 6. Dip switch
Copyright AST 2010
2. Terminal for DC Input
3. Output fuse
4. Socket for AC Input
7. EPO
8. RS232
9. USB
www.ast-global.com
5. Dry Contact
UPS A3&A5 QUICK GUIDE
Fig. 3 A5 Connection Schematic
!
Share alike Sockets output to load
Fuse 250V/15A
AC OUTPUT 10A MAX.
AC OUTPUT 16A MAX. Fuse 250V/10A
DC INPUT 192V/12.4A
DIP SWICH USB
RS232
EPO
DRY CONTACT AC INPUT 230V/13.8A
Commercial power input
Fig. 4 A3 Connection Schematic
Copyright AST 2010
www.ast-global.com
DC Input 192V
UPS A3&A5 QUICK GUIDE 5.
Preparations before First Start-up
To ensure normal operation of UPS, please confirm the following before use: A. Correct installation of input and output. B. If supply terminals connect to the rated power.
.
C. Confirm that UPS output does not short circuit and the load capacity does not exceed UPS capacity. D. Confirm if computer or other instrument is turned off. E. Confirm if battery voltage is normal. F. It is not recommended to connect reactive load to the UPS output. Loads are normally powered by electric network directly. 6.
UPS Start-up Sequence
After confirming all the above, please start the machine by following means: A.
Press the "ON/TEST" button on the UPS panel to start UPS, the "INV." indicator light will light up. After retardation time, the "BYPASS" light goes out and the UPS is changed inverter power supply. By this time, the start-up is completed and the equipment starts operation. Wait for about 20 seconds after normal no-load operation to turn on the computer or other instrument. Start the load in the sequence of high-power to low power, first start the high-power equipment then in turns start equipment with lower power.
B.
Start computer or other equipment.
7.
Daily Start-up and Shutdown
During daily operation, operate as per the following for start-up or shut down: A. Press the "ON/TEST" button on the UPS panel to start UPS, after 10 seconds, turn on the computer or other instrument. B. Normally, only when the UPS has been started and is working stably, can the loading equipment power switch be turned on. First turn on high-power equipment, then the equipment with lower power.
Some equipment has large start current (such as monitors of
some brands). When starting such equipment, overload protection (such as bypass operation) may occur.
In this case, it's
recommended to start this type of equipment before other equipment. Before shutdown, turn off the computer and other instrument first and perform no-load operation of UPS for 10 minutes. After the heat in the equipment has been discharged, press the "OFF" button on the panel. 8.
Maintenance Guide
Proper maintenance includes preventive maintenance and remedial maintenance, which is crucial to optimum operation of UPS and can ensure relatively long service life of the equipment. Preventive maintenance includes some procedures that are frequently performed. These procedures are used to prevent system failure as well as to obtain best operating efficiency. Remedial maintenance includes searching for system malfunction to facilitate effective repair. 9.
Safety Precaution
In order to securely and successfully conduct system maintenance, relevant safety precautions must be observed and necessary tools and testing equipment must be used, with the participation of qualified maintenance personnel. Pay attention to the following safety operation rules: A. Bear in mind that the equipment contains lethal voltage even if the system is not in operation. B. Servicing should be performed by qualified service personnel with knowledge of the UPS and required precautions. Keep unauthorized personnel away from the equipment. 10. When operating UPS, do not wear gold or silver jewelry such as ring or watch, etc. 11. Do not take the safety operation procedure for granted. If there is any doubt, consult personnel who are familiar with the equipment. Be cautious that there is dangerous voltage in UPS. Before maintenance and adjustment, use voltmeter to check and ensure that the power is turned off and the equipment is under safe condition. Copyright AST 2010