UPS A3&A5 QUICK GUIDE

UPS A3 & A5 Quick Guide User’s Manual

Copyright AST 2010

www.ast-global.com


UPS A3&A5 QUICK GUIDE 1.

Table 1 Safety Symbols and Means Safety

Symbols

Means Secure alarm

Risk of electric shock

2.

Table 2 UPS Main Performance Index Model

A5

characteristic

Rating voltage

Characteristic

Capacity

Characteristic

Output

Output

Input

Index (V)

In range 120V~290V, 50% load,in range 160V~290V, full load

Rating frequency (Hz)

50/60 ±10%

Input mode

Single-phase three-line

Battery voltage

(V)

192

(VA/W)

5000/3500

3000/2100

Voltage

(V)

230±1%

Frequency

(Hz)

50/60Hz (Battery mode)

Waveform

Sine wave 105%~129% Load, lasting 60 seconds , or 130%~150% Load, lasting 30

Overload capacity

seconds turn to BYPASS

Output mode

Line bar

Panel display

LED

Warning function Other Characteristics

A3

Battery low voltage, abnormal power supply, UPS malfunction, overload Battery low voltage protection, overload protection, short-circuit protection and

Protection function

over temperature protection, over voltage protection

Working temperature

-20 ~ 40℃

Relative humidity Size (mm)

0 ~ 95%,No condensation A3/A5: 440×700×130

(W×D× H)

External Battery Cabinet: : 440×460×176 Weight

A3/A5: 17.5

(kg)

External Battery Cabinet: : 55.5(including BAT. 7Ah,16 PCS)

3.

Panel Indicator Illuminate: BYPASS

①、BYPASS Indicator light ②、Mains supply Indicator light

③、INVERTER Indicator light LINE

LOAD

INV.

100%

100%

④、Capacity indicator of load (contain four lights, each Standing for 25% of total capacity.)

FAULT

Copyright AST

2010BAT.

⑦ ON/TEST

POWER

www.ast-global.com

⑧ OFF


UPS A3&A5 QUICK GUIDE ⑤、Capacity indicator of Battery Indicator light (contain four lights,each standing for 25% of total capacity.) ⑥、FAULT Indicator light ⑦、“ON/TEST” Key START UPS (Please press the “ON” key for 0.5 seconds to run the UPS.) ⑧、“OFF” Key (Please press the “OFF” key for 0.5 second to turn off the UPS.) Press “ON/TEST” for 3 seconds to make the buzzer quiet on battery mode, while power on.

4.

Rear Panel

1

Fuse 250V/15A

AC OUTPUT 10A MAX.

AC OUTPUT 16A MAX. Fuse 250V/10A

Fuse 250V/15A DC INPUT 192V/12.4A

L

N

PE

AC INPUT 230V/20.6A

DIP SWITCH RS232

USB

DRY CONTACT

EPO

L

N

PE

AC INPUT 230V/20.6A

8

9

7

6

5

4

3

2

Fig .1 A5 Rear Panel 1. Output Socket

2. Terminal for DC Input

3. Output fuse

4. Terminal for AC Input

6. Dip switch

7. EPO

8. RS232

9. USB

5. Dry contact

1

Fuse 250V/15A

AC OUTPUT 10A MAX.

AC OUTPUT 16A MAX. Fuse 250V/10A

Fuse 250V/15A DC INPUT 192V/12.4A

DIP SWITCH USB

RS232

DRY CONTACT

EPO

AC INPUT 230V/12A

9

8

7

6

5

4

3

2

Fig.2 A3 Rear Panel 1. Output Socket 6. Dip switch

Copyright AST 2010

2. Terminal for DC Input

3. Output fuse

4. Socket for AC Input

7. EPO

8. RS232

9. USB

www.ast-global.com

5. Dry Contact


UPS A3&A5 QUICK GUIDE

Fig. 3 A5 Connection Schematic

!

Share alike Sockets output to load

Fuse 250V/15A

AC OUTPUT 10A MAX.

AC OUTPUT 16A MAX. Fuse 250V/10A

DC INPUT 192V/12.4A

DIP SWICH USB

RS232

EPO

DRY CONTACT AC INPUT 230V/13.8A

Commercial power input

Fig. 4 A3 Connection Schematic

Copyright AST 2010

www.ast-global.com

DC Input 192V


UPS A3&A5 QUICK GUIDE 5.

Preparations before First Start-up

To ensure normal operation of UPS, please confirm the following before use: A. Correct installation of input and output. B. If supply terminals connect to the rated power.

.

C. Confirm that UPS output does not short circuit and the load capacity does not exceed UPS capacity. D. Confirm if computer or other instrument is turned off. E. Confirm if battery voltage is normal. F. It is not recommended to connect reactive load to the UPS output. Loads are normally powered by electric network directly. 6.

UPS Start-up Sequence

After confirming all the above, please start the machine by following means: A.

Press the "ON/TEST" button on the UPS panel to start UPS, the "INV." indicator light will light up. After retardation time, the "BYPASS" light goes out and the UPS is changed inverter power supply. By this time, the start-up is completed and the equipment starts operation. Wait for about 20 seconds after normal no-load operation to turn on the computer or other instrument. Start the load in the sequence of high-power to low power, first start the high-power equipment then in turns start equipment with lower power.

B.

Start computer or other equipment.

7.

Daily Start-up and Shutdown

During daily operation, operate as per the following for start-up or shut down: A. Press the "ON/TEST" button on the UPS panel to start UPS, after 10 seconds, turn on the computer or other instrument. B. Normally, only when the UPS has been started and is working stably, can the loading equipment power switch be turned on. First turn on high-power equipment, then the equipment with lower power.

Some equipment has large start current (such as monitors of

some brands). When starting such equipment, overload protection (such as bypass operation) may occur.

In this case, it's

recommended to start this type of equipment before other equipment. Before shutdown, turn off the computer and other instrument first and perform no-load operation of UPS for 10 minutes. After the heat in the equipment has been discharged, press the "OFF" button on the panel. 8.

Maintenance Guide

Proper maintenance includes preventive maintenance and remedial maintenance, which is crucial to optimum operation of UPS and can ensure relatively long service life of the equipment. Preventive maintenance includes some procedures that are frequently performed. These procedures are used to prevent system failure as well as to obtain best operating efficiency. Remedial maintenance includes searching for system malfunction to facilitate effective repair. 9.

Safety Precaution

In order to securely and successfully conduct system maintenance, relevant safety precautions must be observed and necessary tools and testing equipment must be used, with the participation of qualified maintenance personnel. Pay attention to the following safety operation rules: A. Bear in mind that the equipment contains lethal voltage even if the system is not in operation. B. Servicing should be performed by qualified service personnel with knowledge of the UPS and required precautions. Keep unauthorized personnel away from the equipment. 10. When operating UPS, do not wear gold or silver jewelry such as ring or watch, etc. 11. Do not take the safety operation procedure for granted. If there is any doubt, consult personnel who are familiar with the equipment. Be cautious that there is dangerous voltage in UPS. Before maintenance and adjustment, use voltmeter to check and ensure that the power is turned off and the equipment is under safe condition. Copyright AST 2010

www.ast-global.com