CURTAIN WALL TYPE LEGEND
NOTES: For General Arrangement Plans refer to drawings:
CW1: Curtain Wall Type 1 (200mm)
- CTM-XX-00-01-0101 (Site Plan) - CTM-XX-00-20-2000 (Level 00) - CTM-XX-01-20-2001 (Level 01) - CTM-XX-03-20-2003 (Level 03) - CTM-XX-04-20-2004 (Level 04) - CTM-XX-05-20-2005 (Level 05) - CTM-XX-06-20-2006 (Level 06) - CTM-XX-07-20-2007 (Level 07)
Capped stick curtain wall system to typical office floors (with no external fixed brise soleil louvres). Combination of feature vertical caps (250mm deep profile) & standard vertical caps (15mm profile). NBS Spec Ref: FMDC SPEC 3.1.3 CW2: Curtain Wall Type 2 (200mm) Flush capless Structural Silicon Glazing (SSG) system to north core NBS Spec Ref: FMDC SPEC 3.1.2
N
For Floor/Roof finishes drawings refer to: - CTM-XX-00-43-4300 (Level 00) - CTM-XX-00-43-4301 (Level 01) - CTM-XX-00-43-4302 (Level 02) - CTM-XX-00-43-4303 (Level 03) - CTM-XX-00-43-4304 (Level 04) - CTM-XX-00-43-4305 (Level 05)
CW3: Curtain Wall Type 3 (300mm) Flush capless Structural Silicon Glazing (SSG) system to ground floor with 250mm steel plate reinforced mullions. NBS Spec Ref: FMDC SPEC 3.1.4
05
05
04
22-2202
22-2201
22-2204
CW4: Curtain Wall Type 4 (200mm)
Drawings to be read in conjunction with:
Capped stick curtain wall system to typical office floors (with external fixed brise soleil louvres) NBS Spec Ref: FMDC SPEC 3.1.1
- Chapman Taylor, Architects NBS Specification - FMDC, Performance specification for facade elements - CT Fire Strategy Drawings (59-5900, 5901, 5910, 5911)
A8
A7
A6
7500
A5
9000
A4
9000
A3
9000
A2
9000
A1
9000
NOTES THIS DRAWING MUST NOT BE SCALED. ALL DIMENSIONS ARE TO BE VERIFIED AND CHECKED ON SITE. ANY DISCREPANCIES THAT ARE, OR BECOME APPARENT SHOULD BE REPORTED TO CHAPMAN TAYLOR. AREAS INDICATED ARE APPROXIMATE GROSS INTERNAL AREA. THEY RELATE TO THE LIKELY AREAS OF THE BUILDING AT THE CURRENT STAGE OF DESIGN. ANY DECISIONS TO BE MADE ON THE BASIS OF THESE PREDICTIONS, WHETHER AS TO PROJECT VIABILITY, PRE-LETTING, LEASE AGREEMENTS, OR THE LIKE, SHOULD INCLUDE DUE ALLOWANCE FOR THE INCREASES AND DECREASES INHERENT IN THE DESIGN DEVELOPMENT AND BUILDING PROCESS. © COPYRIGHT CHAPMAN TAYLOR 2015
Refer to Landscape Architects drawings and specification for details of hard and soft material finishes within the public realm.
7500 Refer to Civil Engineers draiwngs and specification for details of surface water drainage within the public realm.
TOP +56.590
TOP +56.590
ABBREVIATIONS LEGEND
CW2
BOW C/L EGL FFL HEAD LVL MJ RWO RWP SSL SVP TOC TOP TOS TOW
TOP +54.755 MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
Level 07 54615
MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
MP3
D06-PL04
CW1
GT1
TOP +51.790
GT1
GT1
GT1
GT1
GT1
GT1
GT1
GT1
GT1
GT1
GT1
GT1
GT1
GT1
GT1
GT1
MP3
MP3
CW1
GT1
MP3
MP3
TOP +51.790
Level 06 51470
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
GT1
GT2
GT3
GT3
GT4
GT4
GT3
GT3
GT4
GT4
GT3
GT3
GT4
GT4
GT3
GT3
GT2
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
Bottom of Wall Centre Line External Ground Level Finished Floor Level Top of Glazing/ Door General Level Movement Joint Rainwater Outlet Rainwater Pipe Structural Slab Level Soil Vent Pipe Top of Concrete Top of Parapet Top of Steel Top of Wall
GT1
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
Level 05 47050
GT1
GT2
GT3
GT3
GT4
GT4
GT3
GT3
GT4
GT4
GT3
GT3
GT4
GT4
GT3
GT3
GT2
GT1
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
Level 04 42965
GT1
GT2
GT3
GT3
GT4
GT4
GT3
GT3
GT4
GT4
GT3
GT3
GT4
GT4
GT3
GT3
GT2
GT1
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
GT5
GT5
GT5
GT5
GT5
GT5
GT5
MP1
MP1
MP1
MP1
MP1
Level 03 38880
GT1
GT2
GT3
GT3
GT4
GT4
GT3
GT3
GT4
GT4
GT3
GT3
GT4
GT4
GT3
GT3
GT2
GT1
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP2
MP2
MP2
MP2
MP2
MP2
MP2
MP2
Level 02 34795
GT1
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
GT2
GT3
GT3
GT4
GT4
GT3
GT3
GT4
GT4
GT3
GT3
GT4
GT4
GT3
GT3
GT2
MP1
GT1
Level 01 30710
MP2 MP2 GT1
GT2
GT3
GT3
GT4
GT4
GT3
GT3
GT4
GT4
GT3
GT3
GT4
GT4
GT3
GT3
GT2
GT4
MP4
MP2
MP2 MP2
GT1
GT4
GT4
GT4
GT4
GT4
GT4
MP1
MP4
MP1
GT4
GT1
GT2
GT3
GT3
FFL +24.700
GT3
GT4
GT3
GT4
GT4
GT3
GT3
GT4
FFL +24.700
FFL +24.700
GT3
GT3
GT2
GT1
GT4
GT4
FFL +24.700
GT4
FFL +24.700
D00RE01
GT4
Level 00 24700
D00PL07 MP5
CW3
MP5
ML1
D00PL08 MP5
ML1
D00S202
D00PL09 GT3
D00S102 GS1
GS1
D00RE03
MP5
D00RE02
MP5
MP5
MP5
CW3 T01
26.06.15
II
REV
DATE
INT'L
STAGE E - TENDER ISSUE
MD
DESCRIPTION
CHK'D
PROJECT
THE REGENT, SALFORD QUAYS
CLIENT
GT5
GT6
1
2
5
ML1
Clear glazed panels where brise soleil FMDC Spec Ref: 3.1.1
MP4
10M
Granite stall riser panels FMDC Spec Ref: 3.1.2
Metal louvre panels FMDC Spec Ref: 3.1.7 Circular aluminium cladding to columns RAL TBC FMDC Spec Ref: 3.1.5 Stainless steel plinth RAL TBC FMDC Spec Ref: 3.1.4
MP1
1285
NO FRITTING TO THIS SECTION (CLEAR VISION GLASS)
FRITTING TO BE IN 40MM EQUAL BANDING/STRIPS
MIN 1500
MP5
0
PPC metal plant screen to level 6 RAL TBC GT5
GS1
Clear glazed panels with 650mm fritting at base of panel where no external brise soleil FMDC Spec Ref: 3.1.3
1:100 Scale Bar
CEILING BULKHEAD BEYOND
400 600
GT4
MP1
FFL
GT2 FFL
SEMI TRANSLUCENT FRITT ABOVE CEILING BULKHEAD BEYOND
Chapman Taylor LLP Architects Masterplanners Designers Bass Warehouse 4 Castle Street, Castlefield Manchester M3 4LZ Tel +44 (0)161 828 6500 Fax +44 (0)161 828 6505
STRUCTURAL ENGINEER
NO FRITTING TO THIS SECTION (CLEAR VISION GLASS)
1800
Clear vision glazed panels FMDC Spec Ref: 3.1.2 (SSG to North Core) FMDC Spec Ref: 3.1.4 (SSG to Ground Floor)
MP3
CAP 2: 15mm low profile curtain wall caps. RAL 7016 (dark grey) FMDC Spec Ref: 3.1.1 (where brise soleil) FMDC Spec Ref: 3.1.3 (where no brise soleil)
ARCHITECT
FFL
40 40 40 40 40
GT3
Metal cladding panel over canopy entrance RAL TBC FMDC Spec Ref: 3.1.5
FFL
40 40 40 40 40
Opaque glazed panels FMDC Spec Ref: 3.1.2
MP2
Peel Dome The Trafford Centre Manchester M17 8PL
2910
Semi-translucent glazed panels FMDC Spec Ref: 3.1.2
GT2
MP1
CAP 1: 250mm feature profile curtain wall caps. RAL 7016 (dark grey) FMDC Spec Ref: 3.1.3 (where no brise soleil)
525 650
Back painted glazed panels FMDC Spec Ref: 3.1.2
GT1
PPC aluminium spandrel panels RAL TBC FMDC Spec Ref: 3.1.1 (where brise soleil) FMDC Spec Ref: 3.1.3 (where no brise soleil)
FRITTING CONTROL DIAGRAM FOR GLASS TYPE GT2
FRITTING CONTROL DIAGRAM FOR GLASS TYPE GT5
525 650
CURTAIN WALL - MATERIALS KEY
SEMI TRANSLUCENT FRITT BELOW
Shepherd Gilmour Castlefield House 29 Ellesmere Street Manchester M15 4LZ
SERVICES ENGINEER
Zerum Consult Limited 4 Jordan Street Manchester M15 4PY
DRAWING TITLE
GENERAL ARRANGEMENT EXTERNAL ELEVATION NORTH
JOB NO.
433-BUP
PURPOSE OF ISSUE. TENDER
DRAWN DATE. 15.05.15
SCALE. 1 : 100 @A0
DRAWN BY. II
ISSUE DATE. 26.06.15
MD/AC
COMPANY CODE
CTM
BUILDING ZONE
XX
CHECKED BY.
FLOOR CATEGORY/ DRAWING LEVEL ELEMENT NO.
99
21
REVISION.
2100 T01
CURTAIN WALL TYPE LEGEND
NOTES: For General Arrangement Plans refer to drawings:
CW1: Curtain Wall Type 1 (200mm)
- CTM-XX-00-01-0101 (Site Plan) - CTM-XX-00-20-2000 (Level 00) - CTM-XX-01-20-2001 (Level 01) - CTM-XX-03-20-2003 (Level 03) - CTM-XX-04-20-2004 (Level 04) - CTM-XX-05-20-2005 (Level 05) - CTM-XX-06-20-2006 (Level 06) - CTM-XX-07-20-2007 (Level 07)
Capped stick curtain wall system to typical office floors (with no external fixed brise soleil louvres). Combination of feature vertical caps (250mm deep profile) & standard vertical caps (15mm profile). NBS Spec Ref: FMDC SPEC 3.1.3 CW2: Curtain Wall Type 2 (200mm) Flush capless Structural Silicon Glazing (SSG) system to north core NBS Spec Ref: FMDC SPEC 3.1.2
N
For Floor/Roof finishes drawings refer to:
Flush capless Structural Silicon Glazing (SSG) system to ground floor with 250mm steel plate reinforced mullions. NBS Spec Ref: FMDC SPEC 3.1.4
- CTM-XX-00-43-4300 (Level 00) - CTM-XX-00-43-4301 (Level 01) - CTM-XX-00-43-4302 (Level 02) - CTM-XX-00-43-4303 (Level 03) - CTM-XX-00-43-4304 (Level 04) - CTM-XX-00-43-4305 (Level 05)
CW4: Curtain Wall Type 4 (200mm)
Drawings to be read in conjunction with:
Capped stick curtain wall system to typical office floors (with external fixed brise soleil louvres) NBS Spec Ref: FMDC SPEC 3.1.1
- Chapman Taylor, Architects NBS Specification - FMDC, Performance specification for facade elements - CT Fire Strategy Drawings (59-5900, 5901, 5910, 5911)
CW3: Curtain Wall Type 3 (300mm)
A1
A2 7500
A3
A4
9000
9000
A5
FMDC SEC.23
9000
A6
A7
9000
A8
9000
1 ABBREVIATIONS LEGEND
5050
54615
3 25-2504
1420
Level 06 51470
25-2504
FMDC SEC.19
1085
OFFICE SPACE
03
FMDC SEC.20
1085
Level 04
OFFICE SPACE
FMDC SEC.18
Bottom of Wall Centre Line External Ground Level Finished Floor Level Floor Gulley Top of Glazing/ Door General Level Movement Joint Rainwater Outlet Rainwater Pipe Soil Stack Structural Slab Level Soil Vent Pipe Top of Concrete Top of Parapetdv Top of Steel Top of Wall
3000
25-2501
OFFICE SPACE
BOW C/L EGL FFL FG HEAD LVL MJ RWO RWP SS SSL SVP TOC TOP TOS TOW
3000
2
04
47050
© COPYRIGHT CHAPMAN TAYLOR 2015
25-2504
Level 07
Level 05
AREAS INDICATED ARE APPROXIMATE GROSS INTERNAL AREA. THEY RELATE TO THE LIKELY AREAS OF THE BUILDING AT THE CURRENT STAGE OF DESIGN. ANY DECISIONS TO BE MADE ON THE BASIS OF THESE PREDICTIONS, WHETHER AS TO PROJECT VIABILITY, PRE-LETTING, LEASE AGREEMENTS, OR THE LIKE, SHOULD INCLUDE DUE ALLOWANCE FOR THE INCREASES AND DECREASES INHERENT IN THE DESIGN DEVELOPMENT AND BUILDING PROCESS.
Refer to Civil Engineers draiwngs and specification for details of surface water drainage within the public realm.
7500
FMDC SEC.8
25-2501
ALL DIMENSIONS ARE TO BE VERIFIED AND CHECKED ON SITE. ANY DISCREPANCIES THAT ARE, OR BECOME APPARENT SHOULD BE REPORTED TO CHAPMAN TAYLOR.
Refer to Landscape Architects drawings and specification for details of hard and soft material finishes within the public realm.
GLAZED ATRIUM ROOF LIGHT FMDC SPEC REF: 3.1.8
OFFICE SPACE
NOTES THIS DRAWING MUST NOT BE SCALED.
3000
42965
OFFICE SPACE 1100
OFFICE SPACE
1085
Level 03
OFFICE SPACE
ATRIUM GLASS BALUSTRADE AND INTERNAL TIMBER ACOUSTIC CLADDING FMDC SPEC REF: 3.1.6
3000
38880
OFFICE SPACE
1085
Level 02
OFFICE SPACE
3000
34795
OFFICE SPACE
FMDC SEC.24
OFFICE SPACE
RECEPTION
FMDC SEC.3
4925
30710
1085
Level 01
Level 00 24700
T02
17.07.15
II
STAGE E - TENDER ISSUE LEVEL 6 ROOF VALLEYS ADDED
MD
T01
26.06.15
II
STAGE E - TENDER ISSUE
MD
P01
07.05.15
II
STAGE D ISSUE
MD
REV
DATE
INT'L
DESCRIPTION
CHK'D
PROJECT
THE REGENT, SALFORD QUAYS
CLIENT
CURTAIN WALL - MATERIALS KEY
GT1
Back painted glazed panels FMDC Spec Ref: 3.1.2
MP1
PPC aluminium spandrel panels RAL TBC FMDC Spec Ref: 3.1.1 (where brise soleil) FMDC Spec Ref: 3.1.3 (where no brise soleil)
CAP 1: 250mm feature profile curtain wall caps. RAL 7016 (dark grey) FMDC Spec Ref: 3.1.3 (where no brise soleil)
FRITTING CONTROL DIAGRAM FOR GLASS TYPE GT2
FRITTING CONTROL DIAGRAM FOR GLASS TYPE GT5
Peel Dome The Trafford Centre Manchester M17 8PL
GT6
Clear glazed panels where brise soleil FMDC Spec Ref: 3.1.1
ML1
MP4
MP5
1:100 Scale Bar
PPC metal plant screen to level 6 RAL TBC
Metal louvre panels FMDC Spec Ref: 3.1.7 Circular aluminium cladding to columns RAL TBC FMDC Spec Ref: 3.1.5 Stainless steel plinth RAL TBC FMDC Spec Ref: 3.1.4
Chapman Taylor LLP Architects Masterplanners Designers
CEILING BULKHEAD BEYOND
GT5
FRITTING TO BE IN 40MM EQUAL BANDING/STRIPS
MIN 1500
MP1
NO FRITTING TO THIS SECTION (CLEAR VISION GLASS)
400 600
Granite stall riser panels FMDC Spec Ref: 3.1.2
FFL
1285
MP1
FFL
FFL
GT2 FFL
SEMI TRANSLUCENT FRITT ABOVE CEILING BULKHEAD BEYOND
NO FRITTING TO THIS SECTION (CLEAR VISION GLASS)
Bass Warehouse 4 Castle Street, Castlefield Manchester M3 4LZ Tel +44 (0)161 828 6500 Fax +44 (0)161 828 6505
STRUCTURAL ENGINEER
Shepherd Gilmour Castlefield House 29 Ellesmere Street Manchester M15 4LZ
SERVICES ENGINEER
1800
Clear glazed panels with 650mm fritting at base of panel where no external brise soleil FMDC Spec Ref: 3.1.3
GS1
CAP 2: 15mm low profile curtain wall caps. RAL 7016 (dark grey) FMDC Spec Ref: 3.1.1 (where brise soleil) FMDC Spec Ref: 3.1.3 (where no brise soleil)
40 40 40 40 40
GT5
Clear vision glazed panels FMDC Spec Ref: 3.1.2 (SSG to North Core) FMDC Spec Ref: 3.1.4 (SSG to Ground Floor)
MP3
Metal cladding panel over canopy entrance RAL TBC FMDC Spec Ref: 3.1.5
40 40 40 40 40
GT4
Opaque glazed panels FMDC Spec Ref: 3.1.2
MP2
2910
GT3
Semi-translucent glazed panels FMDC Spec Ref: 3.1.2
525 650
GT2
525 650
ARCHITECT
SEMI TRANSLUCENT FRITT BELOW
Zerum Consult Limited 4 Jordan Street Manchester M15 4PY
DRAWING TITLE
GENERAL ARRANGEMENT, INTERNAL SECTIONS, EAST-WEST SECTION THROUGH ATRIUM JOB NO.
433-BUP
PURPOSE OF ISSUE. TENDER
DRAWN DATE. 03.03.15
SCALE. 1 : 100 @A0
DRAWN BY. II
ISSUE DATE. 26.05.2015
MD/AC
COMPANY CODE
0
1
2
5
10M
CTM
BUILDING ZONE
XX
CHECKED BY.
FLOOR CATEGORY/ DRAWING LEVEL ELEMENT NO.
99
21
REVISION.
2110 T01
NOTES:
CURTAIN WALL TYPE LEGEND
For General Arrangement Plans refer to drawings: CW1: Curtain Wall Type 1 (200mm)
- CTM-XX-00-01-0101 (Site Plan) - CTM-XX-00-20-2000 (Level 00) - CTM-XX-01-20-2001 (Level 01) - CTM-XX-03-20-2003 (Level 03) - CTM-XX-04-20-2004 (Level 04) - CTM-XX-05-20-2005 (Level 05) - CTM-XX-06-20-2006 (Level 06) - CTM-XX-07-20-2007 (Level 07)
Capped stick curtain wall system to typical office floors (with no external fixed brise soleil louvres). Combination of feature vertical caps (250mm deep profile) & standard vertical caps (15mm profile). NBS Spec Ref: FMDC SPEC 3.1.3 CW2: Curtain Wall Type 2 (200mm)
N
For Floor/Roof finishes drawings refer to:
Flush capless Structural Silicon Glazing (SSG) system to north core NBS Spec Ref: FMDC SPEC 3.1.2
NOTES THIS DRAWING MUST NOT BE SCALED.
- CTM-XX-00-43-4300 (Level 00) - CTM-XX-00-43-4301 (Level 01) - CTM-XX-00-43-4302 (Level 02) - CTM-XX-00-43-4303 (Level 03) - CTM-XX-00-43-4304 (Level 04) - CTM-XX-00-43-4305 (Level 05)
CW3: Curtain Wall Type 3 (300mm) Flush capless Structural Silicon Glazing (SSG) system to ground floor with 250mm steel plate reinforced mullions. NBS Spec Ref: FMDC SPEC 3.1.4
ALL DIMENSIONS ARE TO BE VERIFIED AND CHECKED ON SITE. ANY DISCREPANCIES THAT ARE, OR BECOME APPARENT SHOULD BE REPORTED TO CHAPMAN TAYLOR. AREAS INDICATED ARE APPROXIMATE GROSS INTERNAL AREA. THEY RELATE TO THE LIKELY AREAS OF THE BUILDING AT THE CURRENT STAGE OF DESIGN. ANY DECISIONS TO BE MADE ON THE BASIS OF THESE PREDICTIONS, WHETHER AS TO PROJECT VIABILITY, PRE-LETTING, LEASE AGREEMENTS, OR THE LIKE, SHOULD INCLUDE DUE ALLOWANCE FOR THE INCREASES AND DECREASES INHERENT IN THE DESIGN DEVELOPMENT AND BUILDING PROCESS.
Drawings to be read in conjunction with:
CW4: Curtain Wall Type 4 (200mm)
© COPYRIGHT CHAPMAN TAYLOR 2015
GLAZED ATRIUM ROOF LIGHT FMDC SPEC REF: 3.1.8
Capped stick curtain wall system to typical office floors (with external fixed brise soleil louvres) NBS Spec Ref: FMDC SPEC 3.1.1
AA
AB
10500
AC
- Chapman Taylor, Architects NBS Specification - FMDC, Performance specification for facade elements - CT Fire Strategy Drawings (59-5900, 5901, 5910, 5911)
AD
9000
AE
9000
Refer to Landscape Architects drawings and specification for details of hard and soft material finishes within the public realm. Refer to Civil Engineers draiwngs and specification for details of surface water drainage within the public realm.
9000 FMDC SEC.08
FMDC SEC.22
ABBREVIATIONS LEGEND
5050
Level 07 54615
51470
1420
345
Level 06
LIFT LOBBY
3000
FMDC SEC.9
Bottom of Wall Centre Line External Ground Level Finished Floor Level Floor Gulley Top of Glazing/ Door General Level Movement Joint Rainwater Outlet Rainwater Pipe Soil Stack Structural Slab Level Soil Vent Pipe Top of Concrete Top of Parapetdv Top of Steel Top of Wall
BOW C/L EGL FFL FG HEAD LVL MJ RWO RWP SS SSL SVP TOC TOP TOS TOW
OFFICE SPACE
1085
Level 05
LIFT LOBBY
FMDC SEC.19
OFFICE SPACE
FMDC SEC.18
OFFICE SPACE
3000
47050
1085
Level 04 42965
LIFT LOBBY
3000
FMDC SEC.10
1085
Level 03
LIFT LOBBY
OFFICE SPACE
LIFT LOBBY
OFFICE SPACE
FMDC SEC.01
3000
38880
FIXED BRISE SOLEIL LOUVRES FMDC SPEC 3.1.1.2
34795
1085
Level 02 1
3000
25-2502
1085
Level 01 30710
FMDC SEC.03
4925
FMDC SEC.14
LIFT LOBBY
Level 00
T02
17.07.15
II
STAGE E - TENDER ISSUE LEVEL 6 ROOF VALLEYS ADDED
MD
T01
26.06.15
II
STAGE E - TENDER ISSUE
MD
P01
07.05.15
II
STAGE D ISSUE
MD
REV
DATE
INT'L
24700
DESCRIPTION
CHK'D
PROJECT
THE REGENT, SALFORD QUAYS
CLIENT
GT6
PPC metal plant screen to level 6 RAL TBC
Granite stall riser panels FMDC Spec Ref: 3.1.2
ML1
Clear glazed panels where brise soleil FMDC Spec Ref: 3.1.1
MP4
MP5
Metal louvre panels FMDC Spec Ref: 3.1.7 Circular aluminium cladding to columns RAL TBC FMDC Spec Ref: 3.1.5 Stainless steel plinth RAL TBC FMDC Spec Ref: 3.1.4
MP1
1285
NO FRITTING TO THIS SECTION (CLEAR VISION GLASS)
FRITTING TO BE IN 40MM EQUAL BANDING/STRIPS
MIN 1500
Clear glazed panels with 650mm fritting at base of panel where no external brise soleil FMDC Spec Ref: 3.1.3
1:100 Scale Bar
CEILING BULKHEAD BEYOND
GT5 GS1
FFL
400 600
Clear vision glazed panels FMDC Spec Ref: 3.1.2 (SSG to North Core) FMDC Spec Ref: 3.1.4 (SSG to Ground Floor)
MP1
FFL
Chapman Taylor LLP Architects Masterplanners Designers
FFL
SEMI TRANSLUCENT FRITT ABOVE
Bass Warehouse 4 Castle Street, Castlefield Manchester M3 4LZ Tel +44 (0)161 828 6500 Fax +44 (0)161 828 6505
STRUCTURAL ENGINEER
CEILING BULKHEAD BEYOND
NO FRITTING TO THIS SECTION (CLEAR VISION GLASS)
Shepherd Gilmour Castlefield House 29 Ellesmere Street Manchester M15 4LZ
SERVICES ENGINEER
GT2 FFL
1800
GT5
MP3
CAP 2: 15mm low profile curtain wall caps. RAL 7016 (dark grey) FMDC Spec Ref: 3.1.1 (where brise soleil) FMDC Spec Ref: 3.1.3 (where no brise soleil)
40 40 40 40 40
GT4
Opaque glazed panels FMDC Spec Ref: 3.1.2
MP2
Metal cladding panel over canopy entrance RAL TBC FMDC Spec Ref: 3.1.5
Peel Dome The Trafford Centre Manchester M17 8PL ARCHITECT
40 40 40 40 40
GT3
Semi-translucent glazed panels FMDC Spec Ref: 3.1.2
MP1
2910
GT2
Back painted glazed panels FMDC Spec Ref: 3.1.2
CAP 1: 250mm feature profile curtain wall caps. RAL 7016 (dark grey) FMDC Spec Ref: 3.1.3 (where no brise soleil)
525 650
GT1
PPC aluminium spandrel panels RAL TBC FMDC Spec Ref: 3.1.1 (where brise soleil) FMDC Spec Ref: 3.1.3 (where no brise soleil)
FRITTING CONTROL DIAGRAM FOR GLASS TYPE GT2
FRITTING CONTROL DIAGRAM FOR GLASS TYPE GT5
525 650
CURTAIN WALL - MATERIALS KEY
SEMI TRANSLUCENT FRITT BELOW
Zerum Consult Limited 4 Jordan Street Manchester M15 4PY
DRAWING TITLE
GENERAL ARRANGEMENT, INTERNAL SECTIONS, NORTH-SOUTH SECTION THROUGH ATRIUM JOB NO.
433-BUP
PURPOSE OF ISSUE. TENDER
DRAWN DATE. 03.03.2015
SCALE. 1 : 100 @A0
DRAWN BY. II
ISSUE DATE. 26.05.2015
MD/AC
COMPANY CODE
0
1
2
5
10M
CTM
BUILDING ZONE
XX
CHECKED BY.
FLOOR CATEGORY/ DRAWING LEVEL ELEMENT NO.
99
21
REVISION.
2111 T02
CURTAIN WALL TYPE LEGEND
NOTES
ABBREVIATIONS LEGEND
CW1: Curtain Wall Type 1 (200mm)
For General Arrangement Plans refer to drawings:
Capped stick curtain wall system to typical office floors (with no external fixed brise soleil louvres). Combination of feature vertical caps (250mm deep profile) & standard vertical caps (15mm profile). NBS Spec Ref: FMDC SPEC 3.1.3
- CTM-XX-00-01-0101 (Site Plan) - CTM-XX-00-20-2000 (Level 00) - CTM-XX-01-20-2001 (Level 01) - CTM-XX-03-20-2003 (Level 03) - CTM-XX-04-20-2004 (Level 04) - CTM-XX-05-20-2005 (Level 05) - CTM-XX-06-20-2006 (Level 06) - CTM-XX-07-20-2007 (Level 07)
BOW C/L EGL FFL FG HEAD LVL MJ RWO RWP SS SSL SVP TOC TOP TOS TOW
CW2: Curtain Wall Type 2 (200mm) Flush capless Structural Silicon Glazing (SSG) system to north core NBS Spec Ref: FMDC SPEC 3.1.2
Drawings to be read in conjunction with: - Chapman Taylor, Architects NBS Specification - FMDC, Performance specification for facade elements - CT Fire Strategy Drawings (59-5900, 5901, 5910, 5911)
CW3: Curtain Wall Type 3 (300mm) Flush capless Structural Silicon Glazing (SSG) system to ground floor with 250mm steel plate reinforced mullions. NBS Spec Ref: FMDC SPEC 3.1.4
Bottom of Wall Centre Line External Ground Level Finished Floor Level Floor Gulley Top of Glazing/ Door General Level Movement Joint Rainwater Outlet Rainwater Pipe Soil Stack Structural Slab Level Soil Vent Pipe Top of Concrete Top of Parapet Top of Steel Top of Wall
A4
A3
06
AA
22-2201
9000
N
TOP +56.520
TOP +56.520 NOTES THIS DRAWING MUST NOT BE SCALED. ALL DIMENSIONS ARE TO BE VERIFIED AND CHECKED ON SITE. ANY DISCREPANCIES THAT ARE, OR BECOME APPARENT SHOULD BE REPORTED TO CHAPMAN TAYLOR.
Refer to Landscape Architects drawings and specification for details of hard and soft material finishes within the public realm. TOP +54.755
CW4: Curtain Wall Type 4 (200mm)
Refer to Civil Engineers draiwngs and specification for details of surface water drainage within the public realm.
Capped stick curtain wall system to typical office floors (with external fixed brise soleil louvres) NBS Spec Ref: FMDC SPEC 3.1.1
AREAS INDICATED ARE APPROXIMATE GROSS INTERNAL AREA. THEY RELATE TO THE LIKELY AREAS OF THE BUILDING AT THE CURRENT STAGE OF DESIGN. ANY DECISIONS TO BE MADE ON THE BASIS OF THESE PREDICTIONS, WHETHER AS TO PROJECT VIABILITY, PRE-LETTING, LEASE AGREEMENTS, OR THE LIKE, SHOULD INCLUDE DUE ALLOWANCE FOR THE INCREASES AND DECREASES INHERENT IN THE DESIGN DEVELOPMENT AND BUILDING PROCESS.
TOP +54.755
5m PPC Metal plant screening system Level 07
© COPYRIGHT CHAPMAN TAYLOR 2015
06
A3
MP3
A4
22-2201
05
4700
54615
22-2201
MP3
GT1
GT1
GT1
GT1
GT1
GT1
GT1
GT1
GT1
Back painted glazed panels FMDC Spec Ref: 3.1.2
GT2
Semi-translucent glazed panels FMDC Spec Ref: 3.1.2
GT3
Opaque glazed panels FMDC Spec Ref: 3.1.2
GT4
Clear vision glazed panels FMDC Spec Ref: 3.1.2 (SSG to North Core) FMDC Spec Ref: 3.1.4 (SSG to Ground Floor)
GT5
Clear glazed panels with 650mm fritting at base of panel where no external brise soleil FMDC Spec Ref: 3.1.3
GT6
Clear glazed panels where brise soleil FMDC Spec Ref: 3.1.1
MP1
PPC aluminium spandrel panels. RAL TBC FMDC Spec Ref: 3.1.1 (where brise soleil) FMDC Spec Ref: 3.1.3 (where no brise soleil)
MP2
Metal cladding panel over canopy entrance RAL TBC. FMDC Spec Ref: 3.1.5
MP3
PPC metal plant screen to level 6 RAL TBC
GS1
Granite stall riser panels FMDC Spec Ref: 3.1.2
ML1
Metal louvre panels FMDC Spec Ref: 3.1.7
MP4
Circular aluminium cladding to columns RAL TBC. FMDC Spec Ref: 3.1.5
MP5
Stainless steel plinth. RAL TBC FMDC Spec Ref: 3.1.4
3015
9000
CURTAIN WALL - MATERIALS KEY
GT1 TOP +51.790
TOC +51.620
SHEET METAL PARAPET CAP
330
SSL +51.125
Level 06 51470
AA
MP1
MP1
FMDC SEC.16
GT3
GT4
GT4
GT3
GT3
GT2
Low profile curtain wall glazing caps (15x60mm)
GT1 GT5
4390
5M PLANT SCREEN
GT3
4550
GT4
GT5 MIN 300 PPC Aluminium Spandrel Panels
Level 07 (Upper Roof)
1090
STAIR 01 Level 05
1 : 50
47050 FMDC SEC.11
06 22-2201
05
9000 GT4
GT3
GT3
GT4
GT4
GT3
GT3
GT2
Feature curtain wall glazing caps (250x60mm)
GT1 GT5
4085
A4
1089
22-2201
A3
MP1
4085
01
FFL +47.050
GT5
600 1090
FMDC SEC.12
AA
FFL +42.965
FMDC SEC.9
Level 04 42965
MP1
MP1
FFL +51.440 (L6)
CAP 1: 250mm feature profile curtain wall caps. RAL 7016 (dark grey) FMDC Spec Ref: 3.1.3 (where no brise soleil)
SSL +51.125 (L6)
GT4
GT4
GT3
GT3
GT2
GT1 GT5 FMDC SEC.17
FMDC SEC.10
02
GT5
1 : 50
03 25-2500
STAIR 01
Level 06 (Roof)
4085
GT3
CAP 2: 15mm low profile curtain wall caps. RAL 7016 (dark grey) FMDC Spec Ref: 3.1.1 (where brise soleil) FMDC Spec Ref: 3.1.3 (where no brise soleil)
FFL +38.880
1100
GT3
4085
GT4
Stick Curtain Walling Clear glazing on 1500mm planning grid
Level 03 38880
A3
A4
06
MP1
GT5
GT5
FMDC SEC.13
22-2201
1089
22-2201
MP1
CW2
9000 GT3
GT3
GT4
GT4
GT3
GT3
GT2
GT1
FFL +32.834
AA
LIFT 01
600
650mm fritting FFL to glazing panels where no brise soliel located. Refer to 21 series dwgs for control diagram.
Level 02 34795
MP1
FFL +34.795
1100
04 25-2500
1500
600
GT4
4085
CW2
4085
05
MP1
T02
17.07.15
II
STAGE E - TENDER ISSUE PLANT ROOM STRUCTURE ADDED
MD
T01
26.06.15
II
STAGE E - TENDER ISSUE
MD
P01
07.05.15
II
STAGE D ISSUE
MD
REV
DATE
INT'L
LW3
02 25-2500
GT3
GT3
GT4
GT4
GT3
GT3
GT2
GT1 GT5
GT5
4085
GT4
FFL +30.710 UP
CLIENT
Level 01
1 : 50
30710
A3
MP1
A4
06
22-2201
MP1
Peel Dome The Trafford Centre Manchester M17 8PL
1090
03
Level 01-05 (Typical)
THE REGENT, SALFORD QUAYS
1110
STAIR 01
CHK'D
PROJECT
4085
LIFT 02
DESCRIPTION
ARCHITECT
GT4
GT3
GT3
GT4
GT4
GT3
GT3
GT2
GT1
CW2
01
FFL +25.533
GT3
GT2
GT1
GT4
SERVICES ENGINEER
24700 MP5
05
1:50 Scale Bar
GT3
Level 00
CONCRETE STAIRCASE TO STRUCTURAL ENGINEERS DETAILS & SPECIFICATION
1 : 50
GT4
1775
LIFT 02
Level 00 (Ground)
GT3
MIN 1100
40MM S/S HANDRAILS SPEC REF: L30/570A TO STAIRS 1+2
GT3
2500
300 GT4
Bay Elevation 1 : 50
D00S102
FMDC SEC.15
FMDC SEC.14
GS1
STRUCTURAL ENGINEER
Shepherd Gilmour Castlefield House 29 Ellesmere Street Manchester M15 4LZ
STAIR 01
FFL +24.700
04
Bass Warehouse 4 Castle Street, Castlefield Manchester M3 4LZ Tel +44 (0)161 828 6500 Fax +44 (0)161 828 6505
25-2500
LIFT 01
UP
AA
SSG Structural Glazing System
BW5
1500
MIN 1200
LW3
Chapman Taylor LLP Architects Masterplanners Designers
GT4
D00S102
CW2
600
6010
05 40MM S/S HANDRAILS 9000 SPEC REF: L30/540A TO STAIRS 1+2
1090
CW2
3510
22-2201
MP5
FFL +24.700
Zerum Consult Limited 4 Jordan Street Manchester M15 4PY
DRAWING TITLE
PART ELEVATION & SECTION NORTH ELEVATION BETWEEN GRIDLINES A3 & A4
06
Facade Section 1 : 50
JOB NO.
433-BUP
PURPOSE OF ISSUE. TENDER
DRAWN DATE. 03.03.15
SCALE. 1 : 50 @A0
DRAWN BY. II
ISSUE DATE. 27.03.15
MD/AC
COMPANY CODE
0
0.5
1
2
5M
CTM
BUILDING ZONE
XX
CHECKED BY.
FLOOR CATEGORY/ DRAWING LEVEL ELEMENT NO.
99
22
REVISION.
2201 T02
CURTAIN WALL TYPE LEGEND
NOTES
ABBREVIATIONS LEGEND
CW1: Curtain Wall Type 1 (200mm)
For General Arrangement Plans refer to drawings:
Capped stick curtain wall system to typical office floors (with no external fixed brise soleil louvres). Combination of feature vertical caps (250mm deep profile) & standard vertical caps (15mm profile). NBS Spec Ref: FMDC SPEC 3.1.3
- CTM-XX-00-01-0101 (Site Plan) - CTM-XX-00-20-2000 (Level 00) - CTM-XX-01-20-2001 (Level 01) - CTM-XX-03-20-2003 (Level 03) - CTM-XX-04-20-2004 (Level 04) - CTM-XX-05-20-2005 (Level 05) - CTM-XX-06-20-2006 (Level 06) - CTM-XX-07-20-2007 (Level 07)
BOW C/L EGL FFL HEAD LVL MJ RWO RWP SSL SVP TOC TOP TOS TOW
CW2: Curtain Wall Type 2 (200mm) Flush capless Structural Silicon Glazing (SSG) system to north core NBS Spec Ref: FMDC SPEC 3.1.2
Drawings to be read in conjunction with: - Chapman Taylor, Architects NBS Specification - FMDC, Performance specification for facade elements - CT Fire Strategy Drawings (59-5900, 5901, 5910, 5911)
CW3: Curtain Wall Type 3 (300mm) Flush capless Structural Silicon Glazing (SSG) system to ground floor with 250mm steel plate reinforced mullions. NBS Spec Ref: FMDC SPEC 3.1.4
Bottom of Wall Centre Line External Ground Level Finished Floor Level Top of Glazing/ Door General Level Movement Joint Rainwater Outlet Rainwater Pipe Structural Slab Level Soil Vent Pipe Top of Concrete Top of Parapet Top of Steel Top of Wall
AB
AA
7500
10500 TOP +56.590
TOP +56.590 N
NOTES THIS DRAWING MUST NOT BE SCALED. ALL DIMENSIONS ARE TO BE VERIFIED AND CHECKED ON SITE. ANY DISCREPANCIES THAT ARE, OR BECOME APPARENT SHOULD BE REPORTED TO CHAPMAN TAYLOR.
5m PPC Metal plant screening system
TOP +54.755
Refer to Civil Engineers draiwngs and specification for details of surface water drainage within the public realm.
Capped stick curtain wall system to typical office floors (with external fixed brise soleil louvres) NBS Spec Ref: FMDC SPEC 3.1.1
A7
22-2203
Refer to Landscape Architects drawings and specification for details of hard and soft material finishes within the public realm.
CW4: Curtain Wall Type 4 (200mm)
A8
05
AREAS INDICATED ARE APPROXIMATE GROSS INTERNAL AREA. THEY RELATE TO THE LIKELY AREAS OF THE BUILDING AT THE CURRENT STAGE OF DESIGN. ANY DECISIONS TO BE MADE ON THE BASIS OF THESE PREDICTIONS, WHETHER AS TO PROJECT VIABILITY, PRE-LETTING, LEASE AGREEMENTS, OR THE LIKE, SHOULD INCLUDE DUE ALLOWANCE FOR THE INCREASES AND DECREASES INHERENT IN THE DESIGN DEVELOPMENT AND BUILDING PROCESS.
Level 07 54615 MP3
AB
MP3
MP3
MP3
MP3
MP3
MP3
© COPYRIGHT CHAPMAN TAYLOR 2015
CURTAIN WALL - MATERIALS KEY
AA GT1
10500
GT1
GT1
GT1
GT1
Back painted glazed panels FMDC Spec Ref: 3.1.2
GT2
Semi-translucent glazed panels FMDC Spec Ref: 3.1.2
GT3
Opaque glazed panels FMDC Spec Ref: 3.1.2
GT4
Clear vision glazed panels FMDC Spec Ref: 3.1.2 (SSG to North Core) FMDC Spec Ref: 3.1.4 (SSG to Ground Floor)
GT5
Clear glazed panels with 650mm fritting at base of panel where no external brise soleil FMDC Spec Ref: 3.1.3
GT6
Clear glazed panels where brise soleil FMDC Spec Ref: 3.1.1
MP1
PPC aluminium spandrel panels. RAL TBC FMDC Spec Ref: 3.1.1 (where brise soleil) FMDC Spec Ref: 3.1.3 (where no brise soleil)
MP2
Metal cladding panel over canopy entrance RAL TBC. FMDC Spec Ref: 3.1.5
MP3
PPC metal plant screen to level 6 RAL TBC
GS1
Granite stall riser panels FMDC Spec Ref: 3.1.2
ML1
Metal louvre panels FMDC Spec Ref: 3.1.7
MP4
Circular aluminium cladding to columns RAL TBC. FMDC Spec Ref: 3.1.5
MP5
Stainless steel plinth. RAL TBC FMDC Spec Ref: 3.1.4
TOP +51.790 FFL +51.470
51470
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
1010
Level 06 MP1
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
3560
5M PLANT SCREEN
GT5 650mm fritting FFL to glazing panels where no brise soliel located. Refer to 21 series dwgs for control diagram.
FFL +51.440 (L6)
ROOF SSL +51.125 (L6)
Level 05 MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
525
47050
FFL +47.050
A8 GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
3560
GT1 GT5
05 22-2203
Feature curtain wall glazing caps (250x60mm)
Level 06 (Roof) 1 : 50
Level 04 42965
AB
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
525
01
FFL +42.965
AA 10500
CAP 1: 250mm feature profile curtain wall caps. RAL 7016 (dark grey) FMDC Spec Ref: 3.1.3 (where no brise soleil)
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
CAP 2: 15mm low profile curtain wall caps. RAL 7016 (dark grey) FMDC Spec Ref: 3.1.1 (where brise soleil) FMDC Spec Ref: 3.1.3 (where no brise soleil)
3560
GT5
GT5
FFL +30.710 (L1)
FFL +38.880
PPC Aluminium Spandrel Panels
38880
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
525
Level 03
CW1
OFFICE
Low profile curtain wall glazing caps (15x60mm)
FFL +34.795
Level 02 34795
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
525
A8
3560
GT1
04 Stick Curtain Walling Clear glazing on 1500mm planning grid
05 22-2203
22-2203
CW1
1 : 50
GT5
AB
GT5
GT5
GT5
GT5
GT5
GT5
GT5
GT5
3560
Level 01-05 (Typical)
02
GT5
T01
26.06.15
II
STAGE E - TENDER ISSUE
MD
P01
07.05.15
II
STAGE D ISSUE
MD
REV
DATE
INT'L
DESCRIPTION
CHK'D
PROJECT
THE REGENT, SALFORD QUAYS
AA FFL +30.710
10500
CLIENT
Level 01 MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
MP1
1085
30710 MP1
D00PL07
COMMS ROOM
Peel Dome The Trafford Centre Manchester M17 8PL
HV RMU
HV METER ROOM
ARCHITECT
ML1
GT1
GT1
Aluminium Louvres
Light weight brise soleil with fixed aerofoil (ellipsoid) blades
Chapman Taylor LLP Architects Masterplanners Designers
GT4
Bass Warehouse 4 Castle Street, Castlefield Manchester M3 4LZ Tel +44 (0)161 828 6500 Fax +44 (0)161 828 6505
? D00PL05
D00PL06
MP4
GT1
MP4
MP4
ML1
GT1
STRUCTURAL ENGINEER
HV RMU
Aluminium Louvres
GT1
GT4
Dry Riser
Shepherd Gilmour Castlefield House 29 Ellesmere Street Manchester M15 4LZ
FFL +24.700 SERVICES ENGINEER
Level 00 24700 D00PL04
A8
MP5
D00PL05
D00PL06
ML1
MP5
Zerum Consult Limited 4 Jordan Street Manchester M15 4PY
GS1
05
DRAWING TITLE
22-2203
PART ELEVATION & SECTION EAST ELEVATION BETWEEN GRIDLINES AA & AB
04 22-2203
Level 00 (Ground)
03
04
1 : 50
1:50 Scale Bar
0
0.5
1
2
5M
Bay Elevation 1 : 50
05
Facade Section 1 : 50
JOB NO.
433-BUP
PURPOSE OF ISSUE. TENDER
DRAWN DATE. 03.03.15
SCALE. 1 : 50 @A0
DRAWN BY. II
ISSUE DATE. 27.03.15
MD/AC
COMPANY CODE
CTM
BUILDING ZONE
XX
CHECKED BY.
FLOOR CATEGORY/ DRAWING LEVEL ELEMENT NO.
99
22
REVISION.
2203 T01
40MM S/S HANDRAIL SPEC REF: L30/540A TO STAIRS 1 & 2
SSG CLEAR VISION GLASS CURTAIN WALLING TO NORTH ELEVATION. FOR DETAILS REFER TO FMDC SPEC.
40MM S/S HANDRAILS SPEC REF: L30/540A TO STAIRS 1 & 2
MIN 300
25MM STAINLESS STEEL STEM
50 40
50MM DIA. STAINLESS STEEL BALUTSTRADE POST WITH SATIN POLISHED FINISH SPEC REF: L30/540A
40MM S/S HANDRAIL SPEC REF: L30/540A TO STAIRS 1 & 2
CARPET FINISH TO STAIRS SPEC REF:
STAINLESS STEEL BALUSTRADE BRACKETS
PRECAST CONCRETE STAIR TO STRUCTURAL ENGINEERS DETAIL MAX RISER 170MM MAX GOING 250MM
MIN 900
1100
50MM DIA. STAINLESS STEEL BALUSTRADE POST WITH SATIN POLISHED FINISH SPEC REF: L30/540A
ALUMINIUM SIDE TRIM SPEC REF: L30/592A
01
RECESSED SPOT LIGHTS WITHIN PLASTERBOARD BULKHEAD/CEILING SYSTEM. SIZE & SPEC TBC WITH SERVICES ENGINEER
ALUMINIUM FINISH STAIR NOSING IN CONTRASTING COLOUR, WITH ALUMINIUM SIDE TRIMS TO ALL EXPOSED STAIRCASE STRINGERS SPEC REF: L30/592A
PLASTER SKIM & PAINT FINISH
PAINT FINISH TO STAIR STRINGER
TYPICAL HALF LANDING SECTION DETAIL
02
1 : 10
TYPICAL STRINGER SECTION DETAIL
CLEAR LAMINATED GLASS INFILL PANELS WITH BEVELED EDGES SPEC REF: L30/540A
ALL DIMENSIONS ARE TO BE VERIFIED AND CHECKED ON SITE. ANY DISCREPANCIES THAT ARE, OR BECOME APPARENT SHOULD BE REPORTED TO CHAPMAN TAYLOR. AREAS INDICATED ARE APPROXIMATE GROSS INTERNAL AREA. THEY RELATE TO THE LIKELY AREAS OF THE BUILDING AT THE CURRENT STAGE OF DESIGN. ANY DECISIONS TO BE MADE ON THE BASIS OF THESE PREDICTIONS, WHETHER AS TO PROJECT VIABILITY, PRE-LETTING, LEASE AGREEMENTS, OR THE LIKE, SHOULD INCLUDE DUE ALLOWANCE FOR THE INCREASES AND DECREASES INHERENT IN THE DESIGN DEVELOPMENT AND BUILDING PROCESS. © COPYRIGHT CHAPMAN TAYLOR 2015
STAIR 3 SPECIFICATION GALVANISED BALUSTRADES SPEC REF: L30/560A GALVANISED HANDRAILS SPEC REF: L30/580A STAIR NOSINGS SPEC REF: L30/590A
RECESSED SPOT LIGHTS WITHIN PLASTERBOARD BULKHEAD/CEILING SYSTEM. SIZE & SPEC TBC WITH SERVICES ENGINEER
STAIR TRIMS & EDGINGS SPEC REF: L30/592A
PLASTER SKIM & PAINT FINISH
03
1 : 10
THIS DRAWING MUST NOT BE SCALED.
STEEL SUPPORTS TO STRUCTURAL ENGINEER'S DETAILS & SPECIFICATION
51
VOID
NOTES
GRADUS ELITE ALUMINIUM FINISH STAIR NOSING IN CONTRASTING COLOUR, WITH GRADUS TA5 ALUMINIUM SIDE TRIMS TO ALL EXPOSED STAIRCASE STRINGERS. SPEC REF: L30/590A TO STAIRS 1, 2 & 3
RECESSED SPOT LIGHTS WITHIN PLASTERBOARD SOFFIT. MIN 50MM - MAX 100MM, SO NOT TO FOUL MIN. 2250MM HEADROOM
STEEL SUPPORTS TO STR. ENGINEER'S DETAIL & SPEC.
STAINLESS STEEL BALUSTRADE BRACKETS IN SATIN POLISHED FINISH
CARPET FINISH TO STAIRS & LANDINGS SPEC REF:
PLASTER SKIM & PAINT FINISH
50MM DIA. POST WELDED TO S/S CIRCULAR PLATE -FIXED TO FACE OF LANDING SLAB EDGE
N
S/S POST COVER PLATE IN SATIN POLISHED FINISH. SPEC REF: L30/540A
50MM DIA. POST WELDED TO S/S CIRCULAR PLATE - FIXED TO EDGE OF STAIR STRINGER
CARPET FINISH TO STAIRS SPEC REF:
600
MAX 1100
CLEAR LAMINATED GLASS INFILL PANELS WITH BEVELED EDGES SPEC REF: L30/540A
25MM STAINLESS STEEL STEM
200
50MM DIA. STAINLESS STEEL BALUSTRADE POST WITH SATIN POLISHED FINISH SPEC REF: L30/540A
TYPICAL LANDING SECTION DETAIL 1 : 10
T01
26.06.15
II
REV
DATE
INT'L
STAGE E - TENDER ISSUE
MD
DESCRIPTION
CHK'D
MIN 90
PROJECT
PLASTER SKIM & PAINT FINISH
THE REGENT, SALFORD QUAYS
40MM S/S HANDRAILS SPEC REF: L30/570A TO STAIRS 1+2
CLIENT
Peel Dome The Trafford Centre Manchester M17 8PL
1500
ALUMINIUM FINISH STAIR NOSING IN CONTRASTING COLOUR SPEC REF: L30/590A TO STAIRS 1, 2 & 3
ARCHITECT
Chapman Taylor LLP Architects Masterplanners Designers
SECTION 4 NO. STAINLESS STEEL BALUSTRADES PER STAIRCASE RUN (8 NO. TOTAL PER FLOOR LEVEL)
40MM S/S HANDRAILS SPEC REF: L30/570A TO STAIRS 1 & 2
ELEVATION
Bass Warehouse 4 Castle Street, Castlefield Manchester M3 4LZ Tel +44 (0)161 828 6500 Fax +44 (0)161 828 6505
STRUCTURAL ENGINEER
40
50 40 HANDRAIL TO BE MIN. 900MM FROM PITCH-LINE OF STAIRS
Shepherd Gilmour Castlefield House 29 Ellesmere Street Manchester M15 4LZ
ALUMINIUM SIDE TRIMS TO ALL EXPOSED STAIRCASE STRINGERS TO STAIRS 1, 2 & 3 SPEC REF: L30/592A
MIN 900MM FROM PITCH LINE OF STAIR
250
MIN 90
SERVICES ENGINEER
PLYWOOD PATTRESS BEHIND PLASTERBOARD TO PROVIDE FIXING FOR HANDRAILS
DRAWING TITLE
PLASTER SKIM & PAINT FINISH
NOTE: SEE DRAWING SERIES NO.24 FOR STAIR CORE SETTING OUT DIMENSIONS & DETAILS
04
TYPICAL STAIR SETTING OUT PLAN DETAIL 1 : 10
05
TYPICAL HANDRAIL FIXING SECTION DETAIL 1:5
Zerum Consult Limited 4 Jordan Street Manchester M15 4PY
DETAIL SHEET 1 TYPICAL STAIR, HANDRAIL & BALUSTRADE DETAILS JOB NO.
433-BUP
PURPOSE OF ISSUE. TENDER
DRAWN DATE. 16.06.15
SCALE. As indicated @A1
DRAWN BY. II
ISSUE DATE. 26.06.15
MD/AC
COMPANY CODE
BUILDING ZONE
CTM
XX
CHECKED BY.
FLOOR CATEGORY/ DRAWING LEVEL ELEMENT NO.
99
25
REVISION.
2500 T01
AB INTERNAL TIMBER DOOR WITH STAINLESS STEEL DOOR THRESHOLD STRIP ON HIDDEN FIXINGS
CARPET FINISH TO RAISED FLOOR TILES (OFFICE AREAS)
CARPET FINISH TO RAISED FLOOR TILES
ADJUSTABLE RAISED ACCESS FLOOR
CORRIDOR
LIFT LOBBY
STAIR AND CORE
BRUSHED STAINLESS STEEL SKIRTING ON PLYWOOD BACKING, WITH 10MM SHADOW GAP ALONG INTERNAL WALL
100MM S/W SKIRTING WITH GLOSS PAINT FINISH
NATURAL STONE FLOOR TILING
ADJUSTABLE RAISED ACCESS FLOOR PEDESTALS
REINFORCED POLYETHYLENE SEPERATING LAYER BETWEEN SCREED AND VOID FORMER, TO RETURN VERTICALLY
NATURAL STONE FLOOR TILING POLYETHYLENE SEPERATING LAYER BETWEEN SCREED & VOID FORMER, TO RETURN VERTICALLY
N
NOTES
MOVEMENT JOINT
THIS DRAWING MUST NOT BE SCALED.
600
125
FFL
MAX
FFL
SCREED
SSL
ALL DIMENSIONS ARE TO BE VERIFIED AND CHECKED ON SITE. ANY DISCREPANCIES THAT ARE, OR BECOME APPARENT SHOULD BE REPORTED TO CHAPMAN TAYLOR. AREAS INDICATED ARE APPROXIMATE GROSS INTERNAL AREA. THEY RELATE TO THE LIKELY AREAS OF THE BUILDING AT THE CURRENT STAGE OF DESIGN. ANY DECISIONS TO BE MADE ON THE BASIS OF THESE PREDICTIONS, WHETHER AS TO PROJECT VIABILITY, PRE-LETTING, LEASE AGREEMENTS, OR THE LIKE, SHOULD INCLUDE DUE ALLOWANCE FOR THE INCREASES AND DECREASES INHERENT IN THE DESIGN DEVELOPMENT AND BUILDING PROCESS.
SCREED
600
SSL
VOID FORMER
VOID FORMER
© COPYRIGHT CHAPMAN TAYLOR 2015
CONCRETE SLAB TO STRUCTURAL ENGINEERS DETAILS
CONCRETE SLAB TO STRUCTURAL ENGINEERS DETAILS
20MM COMPRESSION FILLER TO ARCHITECTS SPEC & FIRE REGS INSULATION
CELLULAR BEAMS & STEEL TO STRUCTURAL ENGINEERS DETAILS
165
140MM BLOCKWORK WALL WITH WALL TIES AT 450MM CENTRES
140MM BLOCKWORK WALL 2X12.5MM PLASTERBOARD COLUMN CASING WITH PLASTER SKIM AND PAINT FINISH
2X12.5MM PLASTERBOARD WITH PLASTER SKIM AND PAINT FINISH
01
FLOOR INTERFACE BETWEEN STONE AND RAISED FLOOR
02
1 : 10
JUNCTION AT CORRIDOR & STAIR FLOOR SLABS 1 : 10
T01
26.06.15
II
REV
DATE
INT'L
STAGE E - TENDER ISSUE
MD
DESCRIPTION
CHK'D
PROJECT
A1
A3
OFFICE SPACE 302
INSULATED METAL SPANDREL PANEL - COLOUR/FINISH TBC
STEEL COLUMN TO STR. ENGINEERS DETAILS & SPECIFICATION
CURTAIN WALL MULLION RESTRAINT BRACKET TO CONCRETE SLAB
2X12.5MM PLASTERBOARD COLUMN CASING WITH PLASTER SKIM AND PAINT FINISH
OFFICE SPACE
STEEL COLUMN WITHIN PLASTERBOARD CASING
298
PLASTERBOARD END TRIMS TO ALLOW 10MM SHADOW GAP
100
RECESSED BRUSHED STAINLESSSTEEL SKIRTING 10
CARPET FINISH TO RAISED FLOOR TILES (OFFICE AREAS)
FFL
RECESSED BRUSHED STAINLESSSTEEL SKIRTING FIXED TO PLYWOOD BACKING SHEET
SSL
ADJUSTABLE RAISED ACCESS FLOOR PEDESTALS
525
RAISED ACCESS FLOOR PEDESTALS
CONCRETE SLAB TO STRUCTURAL ENGINEERS DETAILS
300
CELLULAR BEAMS TO STRUCTURAL ENGINEERS DETAILS
CELLULAR BEAMS TO STRUCTURAL ENGINEERS DETAILS
300
PLASTERBOARD CEILING WITH PLASTER SKIM AND PAINT FINISH
1 : 10
DRAWING TITLE
DETAIL SHEET 2 TYPICAL FLOOR FINISHES DETAILS
BLIND BOX (BY BUILDING TENANT)
TYPICAL PERIMETER EDGE DETAIL
Shepherd Gilmour Castlefield House 29 Ellesmere Street Manchester M15 4LZ
Zerum Consult Limited 4 Jordan Street Manchester M15 4PY
RECESSED PLASTERBOARD BULKHEAD TO RECEIVE PLASTER SKIM AND PAINT FINISH SUSPENDED METAL CEILING SYSTEM
03
Bass Warehouse 4 Castle Street, Castlefield Manchester M3 4LZ Tel +44 (0)161 828 6500 Fax +44 (0)161 828 6505
SERVICES ENGINEER
450 FEATURE MULLIONS
Chapman Taylor LLP Architects Masterplanners Designers
STRUCTURAL ENGINEER
1085
1085
100
CONCRETE SLAB TO STRUCTURAL ENGINEERS DETAILS
200
Peel Dome The Trafford Centre Manchester M17 8PL ARCHITECT
RAISED ACCESS FLOOR TILES
SSL
CLIENT
CARPET FINISH TO RAISED FLOOR TILES (OFFICE AREAS)
FFL
RAISED ACCESS FLOOR TILES (PERIMETER TILE CUT TO SUIT)
THE REGENT, SALFORD QUAYS
04
TYPICAL COLUMN TO FLOOR SLAB DETAIL 1 : 10
JOB NO.
433-BUP
PURPOSE OF ISSUE. TENDER
DRAWN DATE. 01.06.15
SCALE. 1 : 10 @A1
DRAWN BY. II
ISSUE DATE. 26.06.15
MD/AC
COMPANY CODE
CTM
BUILDING ZONE
XX
CHECKED BY.
FLOOR CATEGORY/ DRAWING LEVEL ELEMENT NO.
99
25
REVISION.
2501 T01
PPC PRE-FORMED METAL CAPPING
PPC PRE-FORMED METAL CAPPING PERIMETER HALO LIGHTING TO M+E ENGINEER'S DETAILS & SPECIFICATION
PERIMETER HALO LIGHTING TO M+E ENGINEER'S DETAILS & SPECIFICATION
1500x4700 ARCHITECTURAL FLAT WALL PANEL FIXED TO OUTSIDE FACE OF PFC CLADDING RAILS. PANEL JOINTS TO ALIGN WITH PERIMETER CW GLAZING PANELS. SPEC REF: H43/120A
UB TO STRUCTURAL ENGINEER'S DETAILS & SPECIFICATION
MIN 900mm
1500x4700 ARCHITECTURAL FLAT WALL PANEL FIXED TO OUTSIDE FACE OF PFC CLADDING RAILS. PANEL JOINTS TO ALIGN WITH PERIMETER CW GLAZING PANELS. SPEC REF: H43/120A
N
NOTES
PFC CLADDING RAILS TO STRUCTURAL ENGINEER'S DETAILS & SPECIFICATION
THIS DRAWING MUST NOT BE SCALED. ALL DIMENSIONS ARE TO BE VERIFIED AND CHECKED ON SITE. ANY DISCREPANCIES THAT ARE, OR BECOME APPARENT SHOULD BE REPORTED TO CHAPMAN TAYLOR. AREAS INDICATED ARE APPROXIMATE GROSS INTERNAL AREA. THEY RELATE TO THE LIKELY AREAS OF THE BUILDING AT THE CURRENT STAGE OF DESIGN. ANY DECISIONS TO BE MADE ON THE BASIS OF THESE PREDICTIONS, WHETHER AS TO PROJECT VIABILITY, PRE-LETTING, LEASE AGREEMENTS, OR THE LIKE, SHOULD INCLUDE DUE ALLOWANCE FOR THE INCREASES AND DECREASES INHERENT IN THE DESIGN DEVELOPMENT AND BUILDING PROCESS.
ADHERED LINER TRAY TO FORM RW GUTTER WITH TROUGH GRATE SPEC REF: H43/234A
PFC CLADDING RAILS TO STRUCTURAL ENGINEER'S DETAILS & SPECIFICATION
© COPYRIGHT CHAPMAN TAYLOR 2015
UB TO STRUCTURAL ENGINEER'S DETAILS & SPECIFICATION
METAL INSULATED ROOF ON STEEL PURLINS. SPEC REF: H43/130A
STEEL/UB TO STR ENG'S DETAILS & SPECIFICATION
CRANKED STRUT TO STRUCTURAL ENGINEER'S DETAILS & SPECIFICATION
PFC CLADDING RAILS TO STRUCTURAL ENGINEER'S DETAILS & SPECIFICATION
1
PLANT SCREEN SECTION HEAD DETAIL
4
1 : 10 CONCRETE PAVING SLABS (SPEC REF: J21 465A) ON SPACER PADS. RIGID INSULATION LAID ON TO LIQUID APPLIED WATERPROOFING, ON CONCRETE SLAB. SPEC REF: J21/125A
PPC PRE-FORMED METAL CAPPIN CONTINUOUS CONCRETE UPSTAND TO ROOF PERIMETER
DRIP CILL TO PLANT SCREENS SPEC REF: H43/120A
4700
METAL FLASHING DRESSED OVER FIBER CANT & INTO PARAPET HEAD DRIP CILL TO PLANT SCREENS SPEC REF: H43/120
300
50
ROOF SUPPORT BEAMS LAID TO FALLS. APPROX 1 IN 60 TO STRUCTURAL ENGINEER'S DETAILS & SECIFICATION
1 : 10
WATER-PROOF MEMBRANE DRESSED OVER UPDSTAND & BEHIND PLANT SCREEN
A8
CONCRETE UPSTAND TO STRUCTURAL ENGINEER'S DETAILS & SPECIFICATION
LIQUID APPLIED WATERPROOF ROOF COATING. SPEC REF: J31 130A
PLANT ROOM SECTION HEAD DETAIL
INDICATIVE RWO TO STRUCTURAL ENGINEER'S DETAILS & SPEC
ROOF MEMBRANE DRESSED INTO DRAINAGE OUTLETS ON ROOF
FMDC SEC.8
10.07.15
II
REV
DATE
INT'L
STAGE E - TENDER ISSUE
MD
DESCRIPTION
CHK'D
PROJECT
THE REGENT, SALFORD QUAYS
CONCRETE UPSTAND TO STRUCTURAL ENGINEER'S DETAILS & SPECIFICATION
CLIENT
Peel Dome The Trafford Centre Manchester M17 8PL
CONCRETE FLAT SLAB WITHIN PLANT ENCLOSURE, ON RIGID INSULATION LAID ON TO LIQUID APPLIED WATERPROOFING, ON CONCRETE SLAB. SPEC REF: J21/125A ROOF SUPPORT BEAMS LAID TO FALLS. APPROX 1 IN 60 TO STRUCTURAL ENGINEER'S DETAILS & SECIFICATION
T01
ARCHITECT
Chapman Taylor LLP Architects Masterplanners Designers Bass Warehouse 4 Castle Street, Castlefield Manchester M3 4LZ Tel +44 (0)161 828 6500 Fax +44 (0)161 828 6505
50 STRUCTURAL ENGINEER
ROOF BALLAST. SPEC REF: J21 460 Shepherd Gilmour Castlefield House 29 Ellesmere Street Manchester M15 4LZ
SERVICES ENGINEER
Zerum Consult Limited 4 Jordan Street Manchester M15 4PY
DRAWING TITLE
DETAIL SHEET 5 TYPICAL PLANT SCREEN DETAILS & ROOF EDGE/VALLEY DETAIL
2
PLANT SCREEN SECTION BASE DETAIL 1 : 10
3
ROOF PARAPET/VALLEY GUTTER DETAIL 1 : 10
5
PLANT ROOM SECTION BASE DETAIL 1 : 10
JOB NO.
433-BUP
PURPOSE OF ISSUE. TENDER
DRAWN DATE. 06.07.15
SCALE. 1 : 10 @A1
DRAWN BY. II
ISSUE DATE. 10.07.15
MD/AC
COMPANY CODE
BUILDING ZONE
CTM
XX
CHECKED BY.
FLOOR CATEGORY/ DRAWING LEVEL ELEMENT NO.
99
25
REVISION.
2504 T01
THIS DRAWING (OR ANY PART THEREOF) MAY NOT BE COPIED, TRANSMITTED OR DISCLOSED TO ANY THIRD PARTY OR UNAUTHORISED PERSON WITHOUT THE PRIOR WRITTEN PERMISSION OF GILLING DOD ARCHITECTS.
Door Schedule - External Door Number
Mark
Level
Family
Structural Opening Width Height
Type
1.1 2.1
ex21 Level 1 ex01 Level 1
6995B_Door Type E3 6995B_Door Type E3
1010x2110mm Ext Sgl Solid 1010x2110mm Ext Sgl Solid
1010 1010
2110 2110
1.2
ex04 Level 2
6995B_Door Type A CW
Ext Dbl Glass Single Swing
1790
2125
1.2 1.2 1.3
ex05 Level 2 ex22 Level 2 ex07 Level 2
6995B_Door Type B CW Sliding Pockt Sliding Door 6995B_Door Type B 1010x2100mm Ext Sing Glass 6995B_Door Type A CW Ext Dbl Glass Single Swing
3550 1010 1805
2.2 2.2
ex02 Level 2 ex03 Level 2
6995B_Door Type K 6995B_Door Type A
1810x2100mm Ext Dbl Solid 1910x2100mm Ext Dbl Glass
1.2
ex06 Level 3 (Site GF)
6995B_Door Type A CW
Ext Dbl Glass Single Swing
1.3 2.3 2.3
NBS Door Panel Door Panel Door Panel Door Panel Reference Infill 1 Infill 2 Infill 3 Infill 4
Door Ironmongery
Comments
THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL OTHER RELEVANT DRAWINGS PREPARED BY CONSULTANTS AND SUBCONTRACTORS.
Metal Panel Metal Panel Metal Panel Metal Panel L20/280B
Glass
Glass
2353 2100 2105
L20/280C L20/280 L20/280B
Glass Glass Glass
Glass Glass Glass
1810 1910
2100 2100
L20/283 L20/281
Metal Panel Metal Panel Metal Panel Metal Panel Pk EXD-10 L40/370 L40/370 L40/370 L40/370 Pk GDA-02
1800
2350
L20/280B
Glass
Glass
Glass
Glass
Pk GDA-01
ex08 Level 3 (Site GF) ex09 Level 3 (Site GF) ex20 Level 3 (Site GF)
6995B_Door Type B CW Sliding Pockt Sliding Door 3535 6995B_Door Type J 900x2150mm Ext Sgl Glass w Sidelight 900 6995B_Door Type C CW Ext Sgl Glass Single Swing 1045
2353 2049 2400
L20/280C L20/370 L20/280B
Glass Opaque Glass
Glass Opaque Glass
Glass Opaque -
Glass Opaque -
Pk EXD-22 Pk EXD-02
1.5 1.5
ex10 Level 5 ex11 Level 5
6995B_Door Type E3 6995B_Door Type E3
1010x2110mm Ext Sgl Solid Plant 1010x2110mm Ext Sgl Solid Plant
1010 1010
2110 2110
L20/282 L20/282
Metal Panel Metal Panel Metal Panel Metal Panel -
-
Pk EXD-02 Pk EXD-02
1.5
ex12 Level 5
6995B_Door Type B
1010x2100mm Ext Sing Glass
1010
2100
L20/280
Glass
-
Pk EXD-09
2.5
ex13 Level 5
6995B_Door Type E4
1510x2110mm Ext Leaf & Half Solid
1510
2110
L20/281
Metal Panel Metal Panel Metal Panel Metal Panel Pk EXD-07
1.6
ex14 Level 6
6995B_Door Type E3
1010x2110mm Ext Sgl Solid Plant
1010
2110
L20/282
Metal Panel Metal Panel -
-
Pk EXD-02
External Door in Rainscreen wall. Maintenance Access only.
1.7 1.7
ex15 Level 7 main roof ex17 Level 7 main roof
6995B_Door Type E2 6995B_Door Type E4
1910 1390
2110 2100
L20/282 L20/282
Metal Panel Metal Panel Metal Panel Metal Panel -
-
Pk EXD-014 Pk EXD-016
External Door In Plant Room Wall. Maintenance Access only. External Door In Plant Room Wall. Maintenance Access only.
2.7
ex16 Level 7 main roof
6995B_Door Type E4
1390
2100
L20/282
Metal Panel Metal Panel -
-
Pk EXD-016
External Door In Plant Room Wall. Maintenance Access only.
2.7 ex18 Level 7 main roof 2.7 ex19 Level 7 main roof Grand total: 22
6995B_Door Type E3 6995B_Door Type E2
1910x2110mm Ext Dbl Solid Plant 1390x2100mm Ext Leaf & Half Solid Plant 1390x2100mm Ext Leaf & Half Solid Plant 1010x2110mm Ext Sgl Solid Plant 1910x2110mm Ext Dbl Solid Plant
1010 1910
2110 2110
L20/282 L20/282
Metal Panel Metal Panel Metal Panel Metal Panel -
-
Pk GDA-03 Pk EXD-014
External Door In Plant Room Wall. Maintenance Access only. External Door In Plant Room Wall. Maintenance Access only.
Glass
-
Pk EXD-09 Pk EXD-09
External Door for Emergency Escape only. External Door for Emergency Escape only.
Glass
Glass
Pk GDA-01
Glass
Glass
Glass
Glass
Pk EXD-22 Pk EXD-09 Pk GDA-01
Automatic powered swing external door in curtain call. Access & E.E. Automatic powered sliding door in pocket/protection screen External Door In Rendered Wall. Maintenance Access only. Automatic powered swing external door in curtain call. Access & E.E. External Door In Rendered Wall. Escape & Access. External Door in masonary Wall. Escape & Access.
-
DO NOT SCALE FROM THIS DRAWING. WORK ONLY TO PRINTED DIMENSIONS. REPORT ANY DISCREPANCIES TO THE ARCHITECT OR REPRESENTATIVES THEREOF. © ALL RIGHTS RESERVED. NO PART OF THIS DRAWING MAY BE REPRODUCED OR TRANSMITTED IN ANY FORM OR BY ANY MEANS WITHOUT THE WRITTEN PERMISSIONS OF THE COPYRIGHT HOLDER ONCE PRINTED AND DISTRIBUTED THIS DOCUMENT IS ASSUMED UNCONTROLLED
Automatic powered swing external door in curtain call. Access & E.E. Automatic powered sliding door in pocket/protection screen External Door In Rendered Wall. Escape & Access. External Door in existing curtain wall. Size to be checked on site, existing aperture. External Door in rendered wall. Maintenance Access only. External Door In Plant Room Wall (rainscreen). Maintenance Access & E.E. External Door in Rainscreen wall. Maintenance Access only. Site dimenoins to be checked prior to manufacture, to suit opening between phase 1 foor and phase 2 structure. External Door In Rainscreen. Escape & Access. Internally finished. To be on hold open in E.E
11
1748 1045
Varies
Rev
By
Description
Date
2
4
1
3
2
4
925
925
775
1
150
4
3
2100 S/O
2
1
2150
3 150
1
2400
Existing glazing, transom removed. Mullions modified to suit new door. Door to be sized o fit opening.
150
2
TYPE A CW
TYPE B CW Sliding Pocket
TYPE A
TYPE C CW
2102 The Cruck Barn, Duxbury Park, Chorley, Lancashire. PR7 4AT t: 01257 260070 f: 01257 260071 Project
Redevelopment of West Cumberland Hospital - Phase 2
2
1 150
External Door Schedule & Elevations
925
2100 S/
2110 S/O
2110 S/O
150
2110 S/O
1
925
2100 S/O
Title
1
2
1
1
2
1
3
2
2
Project Status
Project Number
For Tender
6995B
Project Issue Date
Drawn By
Checked By
25/02/14
II
SDL
Scale
Sheet Size
Rev.
1 : 20 TYPE B
TYPE E2
TYPE E3
TYPE E4
TYPE K
TYPE J
A1
Drawing Number
WCH-GDA-22-ZZ-DR-A-30-3102
EDPM trapped behind curtain wall frame capping and adhered to existing masonry as per specialist curtain wall manufacturers specification.
EDPM trapped behind curtain wall frame capping and adhered to existing slab edge.
Vertical carrier rails as per specialist cladding manufacturers specification.
Insulated gasket as per specialist curtain wall manufacturers specification. continuous metal channel fixed to existing slab edge to span width of curtain walling, to structural engineers details, to pick up bottom fixing of cladding rails.
Cladding facade.
PPC Aluminium parapet trim clip fixed to SFS - size to suit wall thickness.
External grade curtain wall sealant.
Sika-Trocal 90° metal upstand.
Insulated gasket as per specialist curtain wall manufacturers specification.
Sika-Trocal "S" Membrane lapped over corner, fastened under capping.
REPORT ANY DISCREPANCIES TO THE ARCHITECT OR REPRESENTATIVES THEREOF. Š ALL RIGHTS RESERVED. NO PART OF THIS DRAWING MAY BE REPRODUCED OR TRANSMITTED IN ANY FORM OR BY ANY MEANS WITHOUT THE WRITTEN PERMISSIONS OF THE COPYRIGHT HOLDER Cladding facade.
Sika-Trocal S-Vap 500E. Cladding panel reveal fixed to horizontal support rails. NBS - H92/120H
Refer to elevation
70mm Kingspan TP10 foil backed insulation pre bonded onto glazing, fully silicone sealed with metal backing cassette.
Exact slab / column / beam configuration is to be confirmed prior to finalising any new curtain walling details.
Exact slab / column / beam configuration is to be confirmed prior to finalising any new curtain walling details.
ONCE PRINTED AND DISTRIBUTED THIS DOCUMENT IS ASSUMED UNCONTROLLED
SFS System forming parapet, refer to external wall details for further information.
EDPM trapped behind curtain wall frame as per specialist curtain wall manufacturers specification.
Balck Insect mesh fitted to full length of cladding at window head.
Mullions to extend past transom and be bolted back to slab edge.
External grade curtain wall sealant. Insulated gasket as per specialist curtain wall manufacturers specification.
Opaque glazing to obscure ceiling void and slab edge.
Plasterboard fixed to SW battens / framing within depth of mullions internally.
70mm Kingspan TP10 foil backed insulation pre bonded onto glazing, fully silicone sealed with metal backing cassette.
70mm Kingspan TP10 foil backed insulation pre bonded onto glazing, fully silicone sealed with metal backing cassette.
Exact slab / column / beam configuration is to be confirmed prior to finalising any new curtain walling details.
Refer to ceiling plan / details for further information. Ceiling grid secured to angle fixed in to curtain wall transom.
DO NOT SCALE FROM THIS DRAWING. WORK ONLY TO PRINTED DIMENSIONS.
Sika-Trocal Type S waterproof membrane.
Min 10mm ventilation gap protected with insect mesh.
Opaque glazing to obscure ceiling void and slab edge.
THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL OTHER RELEVANT DRAWINGS PREPARED BY CONSULTANTS AND SUBCONTRACTORS.
New Sika-Trocal Adhered roof laid on existing roof finish. Existing roof finish to be cleaned and suitably prepared prior to installation of new system.
SFS System forming parapet, refer to external wall details for further information.
Cladding facade. External grade curtain wall sealant.
975
THIS DRAWING (OR ANY PART THEREOF) MAY NOT BE COPIED, TRANSMITTED OR DISCLOSED TO ANY THIRD PARTY OR UNAUTHORISED PERSON WITHOUT THE PRIOR WRITTEN PERMISSION OF GILLING DOD ARCHITECTS.
Curtain wall transom.
Opaque glazing to obscure ceiling void and slab edge. Ceiling grid secured to angle fixed in to curtain wall transom.
Refer to ceiling plan / details for further information. Refer to ceiling plan / details for further information.
Curtain wall transom. Curtain wall transom.
2
D1
Curtain Wall Vertical Detail 1
Curtain Wall Vertical Detail 2
D2
1 : 10
1 : 10
D3
Curtain Wall Vertical Detail 3 1 : 10
O/A frame depth varies
Curtain wall as NBS H11/??? Insulated gasket as per specialist curtain wall manufacturers specification. PPC metal downstand cill profile acting as backing rod to accept sealant .
Internal wall line.
O/A box depth varies Internal wall line. Curtain wall as NBS H11/???.
External grade curtain wall sealant. Insulated gasket as per specialist curtain wall manufacturers specification.
3 WCH-GDA-22-ZZ-DR-A-40-4206
Curtain wall spigot fixing as per specialist manufacturers specification, secured to top of concrete retaining wall as per SE specification.
Backing rod to accept sealant DPM & EDPM. Curtain wall EDPM dressed under cill.
Internal cill MR MDF with pencil round profile, factory finished with 1 coat primer 2 coats finish.
External grade curtain wall sealant.
Vinyl floor finish trapped under cill & fully sealed.
Curtain wall external cill.
Curtain wall spigot fixing as per specialist manufacturers specification, secured to curtain wall spigot angle.
Box Size Varies
External grade curtain wall sealant.
Internal cill MR MDF with pencil round profile, factory finished with 1 coat primer 2 coats finish.
Curtain wall EDPM lapped over DPM min 150mm. Wearing course varies Sureset, Tarmac, Concrete Pavers (Woodstone) or Concrete Pavers (1200 x 600mm)
Vinyl floor finish trapped under cill & fully sealed.
Bedding course
15
Sub Base Rev
DPM dressed vertically up face of existing retaining wall & trapped in to curtain wall capping.
D4
20mm Kingspan Styrozone H 350 R or equally approved installed to outside face of tanking membrane.
Curtain Wall Vertical Detail 4 1 : 10
By
Description
Date
Kingspan kooltherm perimeter edge insulation. DPM dressed vertically up face of existing wall & trapped in to curtain wall capping.
Exact slab / column / beam configuration is to be confirmed prior to finalising any new curtain walling details.
MR Protection board.
Tanking Membrane as per Engineers details.
D5
Curtain Wall Vertical Detail 5
D6
1 : 10
Curtain Wall Vertical Detail 6 1 : 10
4 WCH-GDA-22-ZZ-DR-A-40-4206
Curtain wall spigot fixing as per specialist manufacturers specification, secured to halfen channel precast into top of concrete retaining wall as per SE specification. Insulated gasket as per specialist curtain wall manufacturers specification. Internal cill MR MDF with pencil round profile, factory finished with 1 coat primer 2 coats finish.
Curtain wall as NBS - H11/110 Cladding facade.
Curtain wall transom.
Corner fixing angle as per specialist cladding manufacturers specification.
Curtain wall EDPM dressed under cill.
External grade curtain wall sealant. External grade curtain wall sealant.
Insulated gasket as per specialist curtain wall manufacturers specification to accept sealant & EDPM.
Curtain wall external cill.
Vinyl floor finish trapped under cill & fully sealed.
Continuous vertical cladding rails secured to cladding bracket as per specialist cladding manufacturers specification.
Curtain wall spigot fixing as per specialist manufacturers specification fixed at mullion positions into concrete slab.
Vertical carrier rails as per specialist cladding manufacturers specification. continuous metal channel fixed to existing slab edge to span width of curtain walling, to SE details. Carrier rail bracket fixing as per specialist cladding manufacturers specification secured into existing slab edge, to SE details.
Exact slab / column / beam configuration is to be confirmed prior to finalising any new curtain walling details. Boarding to back of window as per NBS K10/156.
Curtain wall EDPM secured behind curtain wall capping & adhered to concrete panels.
DPM dressed vertically up face of existing retaining wall & trapped in to curtain wall capping.
Plasterboard fixed to SW battens / framing within depth of mullions internally.
Double angle fixing to secure side of cladding return as per specialist cladding manufacturers specification.
2 layers of plasterboard.
Cladding bracket to support vertical cladding rails secured back to halfen channels precast into concrete panels.
SFS System, refer to external wall details for further information.
Cladding facade. Exact slab / column / beam configuration is to be confirmed prior to finalising any new curtain walling details.
D7
Refer to elevations for glazing requirements (opaque / clear).
Refer to ceiling plan / details for further information.
70mm Kingspan TP10 foil backed insulation pre bonded onto glazing, fully silicone sealed with metal backing cassette.
Opaque glazing to obscure ceiling void and slab edge.
Curtain wall transom.
1 : 10
D8
Curtain Wall Vertical Detail 8 1 : 10
Project
Redevelopment of West Cumberland Hospital - Phase 2
100mm insulation.
PD1
Curtain Wall Vertical Detail 7
The Cruck Barn, Duxbury Park, Chorley, Lancashire. PR7 4AT t: 01257 260070 f: 01257 260071
Curtain Wall Typical Jamb Plan Detail 1 : 10
Title
Curtain Wall Details
Project Status
Project Number
For Tender
6995B
Project Issue Date
Drawn By
Checked By
25/02/14
II
Checker
Scale
Sheet Size
Rev.
1 : 10
A1
Drawing Number
WCH-GDA-Z1-ZZ-DR-A-30-3138
Powder coated aluminium once weathered capping fixed to top of parapet. NBS - H72/251
Wall membrane lapped over and sealed to roofing membrane at parapet.
Powder coated aluminium once weathered capping fixed to top of parapet. NBS - H72/251
Insulation fixed to top of parapet. NBS - J31/342A
THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL OTHER RELEVANT DRAWINGS PREPARED BY CONSULTANTS AND SUBCONTRACTORS.
Insulation fixed to top of parapet. NBS - J31/342A
Protective insulation board fixed to face of parapet wall. NBS - J31/342A
Min 10mm ventilation gap protected with insect mesh.
Paving flags on supporting discs NBS - J31/370 & 372
Supporting SHS posts to engineers details.
Existing structural concrete deck.
845
Cladding panel fixed to vertical support rails. NBS - H92/120F
Insulation mechanically fixed to existing masonry wall. All joints taped. NBS - H92/776A Stand off bracket system and supporting cleats to specialists design. NBS - H92/120E
© ALL RIGHTS RESERVED. NO PART OF THIS DRAWING MAY BE REPRODUCED OR TRANSMITTED IN ANY FORM OR BY ANY MEANS WITHOUT THE WRITTEN PERMISSIONS OF THE COPYRIGHT HOLDER
Insulation mechanically fixed to existing masonry wall. All joints taped. NBS - H92/776A
Roofing insulation to achieve U-value of 0.2W/m²k NBS - J31/130
10mm Cement bonded particle board fixed each side of stud frame. NBS - K11/845
REPORT ANY DISCREPANCIES TO THE ARCHITECT OR REPRESENTATIVES THEREOF.
Roofing membrane taken up face of wall insulation, over parapet, lapped and sealed. NBS - J31/130
Thermal protection sheet NBS - J31/353
PFC parpapet beam to engineers details.
DO NOT SCALE FROM THIS DRAWING. WORK ONLY TO PRINTED DIMENSIONS.
Once existing masonry structure is exposed, if required close off cavity with new concrete flat top coping
Existing roof finish and insulation to be retained. Roof finish to be electronically leak tested and repaired where required.
Gravel ballast to perimeter of roof. NBS - J31/365A
Top Of Parapet. - 9670.
SFS studs fixed within base track and PFC to specialists design. NBS - G10/150
THIS DRAWING (OR ANY PART THEREOF) MAY NOT BE COPIED, TRANSMITTED OR DISCLOSED TO ANY THIRD PARTY OR UNAUTHORISED PERSON WITHOUT THE PRIOR WRITTEN PERMISSION OF GILLING DOD ARCHITECTS.
ONCE PRINTED AND DISTRIBUTED THIS DOCUMENT IS ASSUMED UNCONTROLLED
u/s plant room roof 123572
Waterproof roofing membrane applied directly to cement board substrate. NBS - J31/130
Continuous bead of airtight sealant NBS - Z22/310B
15mm Versapanel board fixed to metal deck. NBS - K11/845
Existing wall to have plaster removed and new plasterboard lining applied. NBS - K10/156
Profiled metal floor deck to engineers specification. C section metal floor joists to engineers specifcation at 600mm centres. Edge beam and supporting steel structure to structural engineers details.
Continuous bead of sealant to both sides of mechanical fixing
Low Pitch insulated trapezoidal composite roof panel NBS - H43/120A
Existing structural concrete deck exposed and cleaned. Powder coated Aluminium fascia (dimensions to be confirmed) MBS - H72/251
Breather membrane applied to face of insulation. all joints lapped and taped. NBS - H92/785
Steel purlins to engineers specification.
Compressible compriband filler and continuous bead of airtight sealant NBS - Z22/310B
Continuous bead of airtight sealant NBS - Z22/310B Existing wall to have plaster removed and new plasterboard lining applied. NBS - K10/156
Min 10mm ventilation gap protected with insect mesh.
Structural steel frame to engineers design.
Cladding panel fixed to vertical support rails. NBS - H92/120F
Detail Z1 C-C (E)
Detail Z1 C-C (J) 1 : 10
1 : 10
Metal composite cladding panels fixed to horizontal cladding rails to engineers design. NBS - H43/120 Stand off bracket system and supporting cleats to specialists design. NBS - H92/120E
Horizontal cladding rails to engineers specification and details.
Powder coated aluminium flashing trim . NBS - G10/150
Insulated reveals in accordance with cladding manufactureres details. Covered with powder coated flashing angle. NBS - H92/120F
Louvre system NBS - L10/650A
Detail Z1 C-C (G) 1 : 10 Rev
By
Description
Date
Louvre system NBS - L10/650A Powder coated aluminium sill flashing. NBS - G10/150
Powder coated aluminium flashing trim with butyl seal. NBS - G10/150 Cladding panel fixed to vertical support rails. NBS - H92/120F
10050 Metal composite cladding panels fixed to horizontal cladding rails to engineers design. NBS - H43/120
Insulated reveals in accordance with cladding manufactureres details. Covered with powder coated flashing angle. NBS - H92/120F
Stand off bracket system and supporting cleats to specialists design, fixed to composite panels. NBS - H92/120E
Stand off bracket system and supporting cleats to specialists design. NBS - H92/120E
Cladding panel fixed to vertical support rails. NBS - H92/120F Powder coated aluminium flashing trim . NBS - G10/150
Bottom of clading cavity closed off and protected with insect mesh.
Paving flags on supporting discs NBS - J31/370 & 372 Thermal protection sheet NBS - J31/353
Bottom of clading cavity closed off and protected with insect mesh.
Gravel ballast to perimeter of roof. NBS - J31/365A Paving flags on supporting discs NBS - J31/370 & 372 Thermal protection sheet NBS - J31/353 Roofing insulation to achieve U-value of 0.2W/m²k NBS - J31/130
Waterproof roofing membrane applied directly to concrete substrate. NBS - J31/130
Powder coated aluminium flashing trim . NBS - H72/420 Protective insulation board fixed to face of existing wall. NBS - J31/342A Continuous bead of airtight sealant NBS - Z22/310B
Level 5 6700
Insulation mechanically fixed to existing masonry wall. All joints taped. NBS - H92/776A
Structural steel frame to engineers design. 200
Existing wall to have plaster removed and new plasterboard lining applied. NBS - K10/156
Horizontal claddig rails to engineers specification.
Roofing membrane lapped up face of wall. NBS - J31/130
Roofing insulation to achieve U-value of 0.2W/m²k NBS - J31/130
Roofing membrane taken up face of wall insulation, over parapet, lapped and sealed. NBS - J42/110
Concrete upstand to perimeter of plantroom to engineers details (Height to be confirmed by DSSR)
New structral concrete deck to engineers design.
Gravel ballast to perimeter of roof. NBS - J31/365A Roofing membrane taken up face of wall insulation, lapped under and sealed to wall membrane. NBS - J31/130 & J42/110
Waterproof roofing membrane applied directly to cement board deck. NBS - J31/130
The Cruck Barn, Duxbury Park, Chorley, Lancashire. PR7 4AT t: 01257 260070 f: 01257 260071
Paving flags on supporting discs NBS - J31/370 & 372 Thermal protection sheet NBS - J31/353
Level 7 main roof 120637
380
Insulation mechanically fixed to existing masonry wall. All joints taped. NBS - H92/776A Breather membrane applied to face of insulation. all joints lapped and taped. NBS - H92/785
Level 6
Supporting steel structure to engineers design and details.
15mm Versapanel board fixed to metal deck. NBS - K11/845 Continuation of new floor slab metal deck to engineers specification.
Project
Redevelopment of West Cumberland Hospital - Phase 2 Title
Sectional Details Sheet 3
Gravel ballast to perimeter of roof. NBS - J31/365A Existing structural concrete deck exposed, cleaned. Roofing insulation to achieve U-value of 0.2W/m²k NBS - J31/130
Existing structural concrete deck exposed, cleaned and prepared for new roof finish.
Waterproof roofing membrane applied directly to concrete substrate. NBS - J31/130
Detail Z1 C-C (D)
Detail Z1 C-C (F)
1 : 10
1 : 10
Detail Z1 C-C (H) 1 : 10
Project Status
Project Number
For Tender
6995B
Project Issue Date
Drawn By
Checked By
25/02/14
II
SDL
Scale
Sheet Size
Rev.
1 : 10
A1
Drawing Number
WCH-GDA-Z1-ZZ-DR-A-26-2123
THIS DRAWING (OR ANY PART THEREOF) MAY NOT BE COPIED, TRANSMITTED OR DISCLOSED TO ANY THIRD PARTY OR UNAUTHORISED PERSON WITHOUT THE PRIOR WRITTEN PERMISSION OF GILLING DOD ARCHITECTS. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL OTHER RELEVANT DRAWINGS PREPARED BY CONSULTANTS AND SUBCONTRACTORS. DO NOT SCALE FROM THIS DRAWING. WORK ONLY TO PRINTED DIMENSIONS. REPORT ANY DISCREPANCIES TO THE ARCHITECT OR REPRESENTATIVES THEREOF. Continuous vertical T-box rail spanning between, and fixed back at, floor levels. To specialist design. NBS - H92/120H Window strapped back to existing masonry structure, and sealed with EPDM membrane. NBS - L10/692
260
Aluminium bracket to corner of cladding to suit required fixings. Cladding manufacturer to advise on fixing method.
New window. Refer to window schedule for type. NBS - L10
Continuous bead of airtight sealant NBS - Z22/310B
Wall brackets fixed to structural floor slab / beams, To specialist design. NBS - H92/120H
15mm plasterboard reveal. NBS - K10/156
X34
Existing wall structure retained and reinforced in accordance with structural engineers specifications. Existing wall to have plaster removed and new plasterboard lining applied. NBS - K10/156
260
Z1-DP-02
Pipe boxing formed in metal stud and lined with plasterboard. Insulation packed into void. NBS - K10/177
NBS - K10/156
160
100
Existing wall structure retained and reinforced in accordance with structural engineers specifications.
Continuous vertical box rail spanning between, and fixed back at, floor levels. To specialist design. NBS - H92/120H
Brackets fixed back at structural floor slabs and beams. NBS - H92/120H
Continuous vertical box rail spanning between, and fixed back at, floor levels. To specialist design. NBS - H92/120H
Cladding panel fixed to vertical support rails. NBS - H92/120H
Existing wall to have plaster removed and new plasterboard lining applied. NBS - K10/156
Breather membrane applied to face of insulation. all joints lapped and taped. NBS - H92/785
Cladding panel fixed to vertical support rails. NBS - H92/120H
Continuous metal angle support fixed to vertical box rail. to specialists design. NBS - H92/120H
160
Recessed cladding panel (see elevations for locations)
ONCE PRINTED AND DISTRIBUTED THIS DOCUMENT IS ASSUMED UNCONTROLLED
Continuous vertical box rail spanning between, and fixed back at, floor levels. To specialist design. NBS - H92/120E
Cladding panel fixed to vertical support rails. NBS - H92/120E
Insulation mechanically fixed to existing masonry wall. All joints taped. NBS - H92/776A
Insulation mechanically fixed to existing masonry wall. All joints taped. NBS - H92/776A
Cladding panel fixed to vertical support rails. NBS - H92/120H
Š ALL RIGHTS RESERVED. NO PART OF THIS DRAWING MAY BE REPRODUCED OR TRANSMITTED IN ANY FORM OR BY ANY MEANS WITHOUT THE WRITTEN PERMISSIONS OF THE COPYRIGHT HOLDER
Breather membrane applied to face of insulation. all joints lapped and taped. NBS - H92/785
Cladding panel return fixed to vertical SFS rail system. NBS - H92/120H
Steel windpost to engineers spec and details.
Insulation mechanically fixed to existing masonry wall. All joints taped. NBS - H92/776A
100
External grade sealant. NBS - L10/810
Insulated cavity closer fixed to void within existing wall structure. Breather membrane applied to face of insulation. all joints lapped and taped. NBS - H92/785
Pipe boxing formed in metal stud and lined with plasterboard. Insulation packed into void. NBS - K10/177
Metal profile extrusion (to match window cill) to run length of cladding recess
10
10
Exact slab / column / beam configuration and location is to be confirmed prior to finalising any details.
Existing wall structure retained and reinforced in accordance with structural engineers specifications. Refer to proposed partition drawings for internal wall details
X34
Line of cladding panel below.
Cladding panel fixed to vertical support rails. NBS - H92/120J
X42
Existing wall & column to have plaster removed and new plasterboard lining applied. NBS - K10/156
Exact slab / column / beam configuration and location is to be confirmed prior to finalising any details.
Stand off bracket system and supporting cleats to specialists design. Brackets fixed top and bottom back to structural slab edge between floor levels to engineers design. NBS - H92/120E Stand off bracket system and supporting cleats to specialists design. Brackets fixed top and bottom back to structural slab edge between floor levels to engineers design. NBS - H92/120E
X42
External Corner Detail
Window Jamb Detail
Internal Corner Detail
1 : 10
1 : 10
1 : 10 X45
Rev
Window strapped back to existing masonry structure, and sealed with EPDM membrane. NBS - L10/692
New window. Refer to window schedule for type. NBS - L10
Continuous bead of airtight sealant NBS - Z22/310B Insulated cavity closer fixed to void within existing wall structure.
Description
Date
New plasterboard lining applied to existing wall. NBS - K10/156
Exsting Structure
External grade sealant. NBS - L10/810
By
SFS stud positioned at vertical cladding support locations.
15mm plasterboard reveal. NBS - K10/156 Cladding panel return fixed to vertical SFS rail system. NBS - H92/120H
2No. layers plasterboard. Intermediate fixings to be countersunk with cladding panel plugs in same finish as panel. NBS - H92/120E
Cladding panel fixed to horizontal support rails. NBS - H92/120E Continuous vertical box rail spanning between, and fixed back at, floor levels. Independent supports to allow for building movement. To specialist design. NBS - H92/120E Cladding panel joint as movement joint, structural engineer to advise of requirement.
Existing render & insulation removed to suit service riser. Exposed masonry to be cleaned & made good to comply with compartmentation strategy
X40
Lift shaft blockwork laid side on NBS - F10/255A
Saw cut formed vertically up face of existing masonry and new DPC inserted. DPC lapped over and sealed to SFS.
Insulation mechanically fixed to existing masonry wall. All joints taped. NBS - H92/776A
Insulation fixed to sheathing board layer / existing masonry. All joints taped. NBS - H92/776A Breather membrane applied to face of insulation. all joints lapped and taped. NBS - H92/785
2No. layers of plasterboard fixed to studs. NBS - K10/158 Steel frame to engineers design.
Insulation.
Breather membrane. Vertical support rails & helping hand brackets.
1
Cladding panel fixed to vertical support rails.
Breather membrane applied to face of insulation. all joints lapped and taped. NBS - H92/785
1No. layer of cement bonded particle sheathing board fixed to studs. NBS - K11/845
SFS studs fixed within base track to specialists design. To be fire stopped along abutment. NBS - G10/150
Sheathing board.
SFS stud fixed back to masonry Phase 1
Exact slab / column / beam configuration and location is to be confirmed prior to finalising any details.
Wall brackets fixed to structural floor slab / beams, To specialist design. NBS - H92/120H
Existing wall to have plaster removed and new plasterboard lining applied. NBS - K10/156 Aluminium bracket to corner of cladding to suit required fixings. Cladding manufacturer to advise on fixing method.
Breather membrane applied to face of insulation. all joints lapped and taped. NBS - H92/785
Intermediate fixings to be countersunk with cladding panel plugs in same finish as panel. NBS - H92/120E
Insulation mechanically fixed to existing masonry wall. All joints taped. NBS - H92/776A
Cladding panel fixed to vertical support rails. NBS - H92/120E 160 Continuous vertical T bracket fixed to metal fixing angle. To specialist design. NBS - H92/120E
X42
Cladding panel fixed to vertical support rails. NBS - H92/120H
Phase 2
The Cruck Barn, Duxbury Park, Chorley, Lancashire. PR7 4AT t: 01257 260070 f: 01257 260071 Project
Redevelopment of West Cumberland Hospital - Phase 2 Title
Plan Details Sheet 1
B
Corner Abutment Detail
Blockwork Corner Detail
Typical Phase 1 Junction
1 : 10
1 : 10
1 : 10
Project Status
Project Number
For Tender
6995B
Project Issue Date
Drawn By
Checked By
25/02/14
II
SDL
Scale
Sheet Size
Rev.
1 : 10
A1
Drawing Number
WCH-GDA-22-ZZ-DR-A-20-2102
THIS DRAWING (OR ANY PART THEREOF) MAY NOT BE COPIED, TRANSMITTED OR DISCLOSED TO ANY THIRD PARTY OR UNAUTHORISED PERSON WITHOUT THE PRIOR WRITTEN PERMISSION OF GILLING DOD ARCHITECTS.
Standard Ballustrade handrail
Standard infill panel
Standard side fixing to stringer mounted post
Riser side section
Perforated metal sheet Plan view
Riser side section
String side elevation
THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL OTHER RELEVANT DRAWINGS PREPARED BY CONSULTANTS AND SUBCONTRACTORS.
Standard base fixing to floor mounted post String side elevation
String side section
Standard Wall mounted handrail Riser side section 65
DO NOT SCALE FROM THIS DRAWING. WORK ONLY TO PRINTED DIMENSIONS.
String side elevation
45
85
50 FFL
45
REPORT ANY DISCREPANCIES TO THE ARCHITECT OR REPRESENTATIVES THEREOF. 50
© ALL RIGHTS RESERVED. NO PART OF THIS DRAWING MAY BE REPRODUCED OR TRANSMITTED IN ANY FORM OR BY ANY MEANS WITHOUT THE WRITTEN PERMISSIONS OF THE COPYRIGHT HOLDER
FFL
ONCE PRINTED AND DISTRIBUTED THIS DOCUMENT IS ASSUMED UNCONTROLLED
50
50
35
35
50
35 Fixing bolts
String side elevation
Post to be welded to bracket. Bracket to then be bolted in place. Design must achieve strength rigid structure as described in HBN 00-04: • vertically, they should support 95% of people plus a margin of 50% that is, 88kg + 44kg = 132kg • horizontally, they should support a force from an adult of 155N + 50% = 233N
130
150
FFL
60
FG FG
Calculations required to prove adequacy of fixing bolts
100
FG FG
FG
UP
Handrail Details - NBS L30/552
1:5
1:5 Stair 4 Section A-A
Balustrade Railing Details - NBS L30/552
Stair 4 Section A-A
FG FG
UP FG
Staircase 4 Location Plan 1 : 1000 2791
L30/552
840
640
730
840
730
76
331
Level 6
50
L30/552
GENERAL NOTES:-Existing staircase retained. -Existing handrails and guarding and support posts carefully removed and substrate surfaces made good. -Existing floor finishes and nosings removed and surfaces made good ready to receive new finishes.
980
1100
1100
150
1310
251
1468
L30/552
300
1100
L30/552 PURPOSE MADE BALUSTRADES
1100
730
1100
730
Stair 4 Section B-B
L30/552 PURPOSE MADE BALUSTRADES
Stair 4 Section B-B
150
1100
2730
10050
Level 5
L30/552
Rev
By
Description
Date
Stair 4 Section A-A
1100
1 : 50
1100
1 : 50
1100
Stair 4 - Level 6
Stair 4 Section A-A
Stair 4 - Level 5
Stair 4 Section A-A
1100
6700
Level 4
L30/552
3350
331
1310
1100
331
1100
1100
2730
Project
Redevelopment of West Cumberland Hospital - Phase 2
1100
300
150
300
150
The Cruck Barn, Duxbury Park, Chorley, Lancashire. PR7 4AT t: 01257 260070 f: 01257 260071
Level 3 (Site GF)
L30/552
0
300
300
2880
2730
1100
150
150
1310
L30/552
150
331
1548
1468
L30/552
1468
L30/552 1310
2791
2791
1468
2791
Staircase 4 Plans Sections & Details
1000
L30/552 PURPOSE MADE BALUSTRADES
Stair 4 Section B-B
Stair 4 Section B-B
L30/552 PURPOSE MADE BALUSTRADES
Stair 4 Section B-B
Title L30/552 PURPOSE MADE BALUSTRADES
1100
1100
5 87
300
Level 2 -3350 840
640
840
Stair 4 - Level 2
Stair 4 - Level 3
Stair 4 - Level 4
Stair 4 - Section A-A
Stair 4 - Section B-B
1 : 50
1 : 50
1 : 50
1 : 50
1 : 50
Project Status
Project Number
For Tender
6995B
Project Issue Date
Drawn By
Checked By
25/02/14
II
Checker
Scale
Sheet Size
Rev.
As indicated
A1
Drawing Number
WCH-GDA-Z2-ZZ-DR-A-70-7105
Ceiling Line
Ceiling Line
740
Ceiling Line
Ceiling Line
THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL OTHER RELEVANT DRAWINGS PREPARED BY CONSULTANTS AND SUBCONTRACTORS.
145
Ceiling Line
1475
145
Ceiling Line
1150
145
Ceiling Line
975
145
Ceiling Line
1985
1635
145
Ceiling Line
680
145
Ceiling Line
950
145
145
145
145
Ceiling Line
1600
145
975
1815
THIS DRAWING (OR ANY PART THEREOF) MAY NOT BE COPIED, TRANSMITTED OR DISCLOSED TO ANY THIRD PARTY OR UNAUTHORISED PERSON WITHOUT THE PRIOR WRITTEN PERMISSION OF GILLING DOD ARCHITECTS.
DO NOT SCALE FROM THIS DRAWING. WORK ONLY TO PRINTED DIMENSIONS.
50
550
50
550
33
890
600
145
225
700
© ALL RIGHTS RESERVED. NO PART OF THIS DRAWING MAY BE REPRODUCED OR TRANSMITTED IN ANY FORM OR BY ANY MEANS WITHOUT THE WRITTEN PERMISSIONS OF THE COPYRIGHT HOLDER
1250
1250
600
1245
1240
145
1250
1250
1250
1250
REPORT ANY DISCREPANCIES TO THE ARCHITECT OR REPRESENTATIVES THEREOF. 1315
550
25
1455
1195 33
925
1240
25
IPS to Vanity Units
150
225
600
45
725
650
45
275
IPS NOTES:
380
•
105
600
225
150
600
10
2500 250
10
2500 5 545
138
545
600
150
700
•
•
Handing of IPS panel swings shown should be checked with position of room & wall elevations before installation. Deregations from HTM regarding fixing heights of certain items such as soap/alchol/gel dispensers and mirrors. All sanitaryware, accessory locations & heights must be obtained from relevant Room C-Sheet drawings. Top of IPS carcases to extend min 100mm beyond suspended ceilings. All IPS panels to stop min 45mm below suspended ceilings unless noted otherwise. Refer to the following plan drawings for all IPS locations:
1. 2. 3. 4. 5.
WCH-GDA-22-02-DR-A-74-0002 WCH-GDA-22-03-DR-A-74-0003 WCH-GDA-22-04-DR-A-74-0004 WCH-GDA-22-05-DR-A-74-0005 WCH-GDA-22-06-DR-A-74-0006
•
IPSX120-Type 2 Elev A
IPSX120-Type 3 Elev A
950
10
10
700
800
•
105
105
IPSX120-Type 5 Elev A
IPSX120-Type 6 Elev A
975
IPSX120-Type 7 Elev A
IPSX120-Type 8 Elev A
740
1475
1150
125
1985
380
800
380
450 105
IPSX120-Type 4 Elev A
1635
680
5
10 105
380
800
105
IPSX120-Type 1 Elev A
1600
380
800
380 105
70
10
5
975
550
800
10
10 380
60
950
105 1815
400
5
250
10
2500
2500 250 150
600
175
10
2500
2500 400 600
600
600
105
600
IPSX110-Type 1 Elev A
IPSX103-Type 1 Elev A
125
10
2500 10
2500 800
1200
50
Sinks centered on IPS panels
IPSX372-Type 1 Elev A
175
138
1000 Belfast sink sat on floor
700
1200 900
1200
800
900
150 200
10
2500
250 10
2500
ONCE PRINTED AND DISTRIBUTED THIS DOCUMENT IS ASSUMED UNCONTROLLED
IPSX372-Type 1
(Level 2) (Level 3) (Level 4) (Level 5) (Level 6)
IPS Panel Legend:
IPSX103-Type 1
IPSX110-Type 1
IPSX120-Type 1
IPSX120-Type 2
IPSX120-Type 3
IPSX120-Type 4
IPSX120-Type 5
IPSX120-Type 6
IPSX120-Type 7
IPSX120-Type 8 Denotes hinged opening panel
Ceiling Line
145
Ceiling Line
Ceiling Line
925
145
Ceiling Line
1265
800
145
Ceiling Line
145
Ceiling Line
145
Ceiling Line
1500
700
145
Ceiling Line
910
925
145
Ceiling Line
850
145
Ceiling Line
925
145
Ceiling Line
145
Ceiling Line
775
700
610
145
Ceiling Line
145
750
145
145
700
Denotes lift off removable panel
Ceiling Line
150
300
600
SITE MEASURE REQUIRED BY SUB-CONTRACTOR PRIOR TO MANUFACTURE & INSTALLATION OF ALL IPS UNITS.
175
DIMENSIONS OF ALL IPS PANEL TYPES TO BE CHECKED AGAINST SCHEDULE ON IPS PLAN LOCATION DRAWINGS LISTED ABOVE.
2500
250 150
600
600
10
10
250
10
250
600
All other panels are fixed in place, unless noted otherwise. For plans and elevations of cubicles, refer to seperate drawing sheet.
1250
1250 365
75
150
600
150
150
250
10
250 150
10
600
600
125
800
150
600
2500
100
2500
50
1250
1250 600
2500
50
2500
10
600
250 150
600
250
10
10
600
1250
1250 300
300
10
600
600
25
200
2500
600
600
10 600
250
250 350
150
10
250 150
1250 50
2500
300
150
600
2500
25
150
250
600
150
25
1250
1250
50
2500 10
250 150
600
250
10 600
150
10 580
120 180
2500
600
2500
50
2500
5
1250
600
1250
5
50
600
600
10
50
600
550
2800
200
1250
1270
1550
Denotes non-removable (fixed) panel
IPSX122-Type 2
IPSX122-Type 3
IPSX123-Type 1
IPSX123-Type 2
IPSX123-Type 3
IPSX124-Type 4 Elev A
1500
IPSX124-Type 2
800
380 105
10
10 380
IPSX124-Type 6 Elev A
1265
925 175
800
IPSX124-Type 3
105
IPSX124-Type 5 Elev A
IPSX124-Type 4
125
IPSX124-Type 3 Elev A
700
IPSX124-Type 1
800
10 105
380
800
800
10 105
910
IPSX123-Type 4
380
800
10 380 105
10 380 105
800
IPSX124-Type 2 Elev A
250
125
125
125
200
125
125
IPSX122-Type 1
IPSX124-Type 1 Elev A
925
850
925
750
IPSX120-Type 9
800
10
IPSX123-Type 4 Elev A
125
775
IPSX123-Type 3 Elev A
175
IPSX123-Type 2 Elev A
105
380
800
10 105
380
800
10 105
380
600
10 380 105
10
IPSX123-Type 1 Elev A
700
610
700
380
IPSX122-Type 3 Elev A
150
IPSX122-Type 2 Elev A
105
800
10 105
380
800
IPSX122-Type 1 Elev A
135
IPSX120-Type 9 Elev A
800
380 105
10
380 105
800
10
Janitorial unit
IPSX124-Type 5
IPSX124-Type 6
145
145
10
465
20
2500 900
100 200 900
600 10 380
800
105
1200 900
10
10 150
150 600
1000
1250
1200
25
T 3 T 2 T 1 Rev
500
125
Ceiling Line
600
10
800
20
140
625
15
635
25
25
1000
10
745
25
25
1000
10
745
IPS to Vanity Units
2790
Ceiling Line
Ceiling Line
775
150
775
145
Ceiling Line
Ceiling Line
IPSX160-Type 4
150
775
245
125
700
200
700
225
700
140
25
IPSX162-Type 1 Elev A
IPSX163-Type 1 Elev A
IPSX163-Type 2 Elev A
10 2920
175
275
175
200
380
470
105
IPSX173-Type 1 Elev A 2790
1805
1320
660
470
IPSX170-Type 1 Elev A
275
1600 1660
Title
10
330 470
600
2500
2500 330 470
10 600 10 105
380
10
IPSX164-Type 1 Elev A
Redevelopment of West Cumberland Hospital - Phase 2 IPS Types - Sheet 1 of 6
1805 2820
Project
600 105
10
900
380
100 200 900
105
380
900
900
800
10
600
10
100 200
2500
2500
400 800 780
105 200 10
1200
105
105
IPSX160-Type 6 Elev A
2500 10
310 140 800
380
900
900
380
10
10
600
10
100 200
2500
2500
1860
The Cruck Barn, Duxbury Park, Chorley, Lancashire. PR7 4AT t: 01257 260070 f: 01257 260071
2500 150 900
15/09/14 28/08/14 27/08/14 Date
1520
2920
1805
145
Ceiling Line
50
1250 10
Dispensers added to IPS panels IPS amended Issued for Tender Description
1250
10
600 10 380 105
IPSX160-Type 5 Elev A
II II II By
IPSX160-Type 4 Elev A
1250
1000
10 380
900
105 1805
1320
145
145
Ceiling Line
25
25
IPSX160-Type 3
1250
1220
Ceiling Line
2920
IPSX160-Type 2
1250
590
1260
IPSX160-Type 3 Elev A
1805
IPSX160-Type 1
1600
1660
1230
10
10
10
100 200 900
900 1900
IPSX154-Type 1
1250
1000
1600
2500
2500
2500 100 200 900
10
600
IPSX160-Type 2 Elev A
50 0
25
25
650
745
10
10
380
1000
1250
25
145
IPSX150-Type 1
145
145
118
380
2900
150
IPSX124-Type 9
Ceiling Line
747
IPSX160-Type 1 Elev A
2360
2820
10
105
IPSX154-Type 1 Elev A
1200
IPSX123-Type 6
1000
10
250 150
580 10 380 105
IPSX150-Type 1 Elev A
125
IPSX123-Type 5
25
105
70
2500
1270 200 900
IPSX124-Type 9 Elev A
900
125
655
145
800
950
10
10 600 10
150 800
380
150 800
IPSX123-Type 6 Elev A
Ceiling Line
200
IPSX123-Type 5 Elev A
1200
2500
150 250
2500
2800
1250
25
105
105
50
1250
600
105
380
800
10
600
250
10
2500 150
250
10 600 10 380
550
Ceiling Line
Ceiling Line
10
800
225
1070
895
600
10
1255
75
150
1550
600
1250
50
550
Ceiling Line
1520
2920
145
Ceiling Line
720
145
Ceiling Line
1805
1900
1100
Ceiling Line
2900
2360
145
1200
145
Ceiling Line
900
145
800
145
145
900
Project Status
Project Number
Preliminary
6995B
Project Issue Date
Drawn By
Checked By
25/02/14
II
AJ
Scale
Sheet Size
Rev.
A0
T3
1 : 20 Drawing Number
IPSX160-Type 5
IPSX160-Type 6
IPSX162-Type 1
IPSX163-Type 1
IPSX163-Type 2
IPSX164-Type 1
IPSX170-Type 1
IPSX173-Type 1
WCH-GDA-22-ZZ-DR-A-74-0008
THIS DRAWING (OR ANY PART THEREOF) MAY NOT BE COPIED, TRANSMITTED OR DISCLOSED TO ANY THIRD PARTY OR UNAUTHORISED PERSON WITHOUT THE PRIOR WRITTEN PERMISSION OF GILLING DOD ARCHITECTS.
X11 ---
---
---
X28
6321 Structural Opening 2505
Mark
1461
1500 Structural Opening
Sim D2 WCH-GDA-Z1-ZZ-DR-A-30-3138
1055
1055
D2 WCH-GDA-Z1-ZZ-DR-A-30-3138
L40/370C
L40/370C
CW.01 CW.02 CW.03 CW.04 CW.05 CW.06 CW.07 CW.08
Level 7 13.720
Sim
L40/370C
L40/370C
L40/370C ---
L40/370
L40/370 Level 6 10.050
Level 6 10.050
1150
L40/370C
L40/370
1150
1150
L40/370C
1150
Stair 4 Section B-B
L40/370 Level 6 10.050
L40/370C
L40/370
WCH-GDA-Z1-ZZ-DR-A-30-3138
L40/370
1050
L40/370C
L40/370C
L40/370
Area
6321 1500 5435 2785 2810 6377 6286 3093
13430 13430 3125 6475 9825 3350 13430 3125
84.9 m² 20.1 m² 17.0 m² 18.0 m² 27.6 m² 21.4 m² 84.4 m² 9.7 m²
205 205 125 145 145 125 205 125
L40/370C
L40/370
A
5
900
L40/370C
L40/370C
250 620
Sim
WCH-GDA-Z1-ZZ-DR-A-30-3138
D8
L40/370C
WCH-GDA-Z1-ZZ-DR-A-30-3138
0C 37 0/ 4 L
480
C 70 0/3 4 L
Level 4 3.350
875
L40/370C
Level 4 3.350
Sim
L40/370C
D3
L40/370
L40/370
Level 3 0.000
Sim
Level 3 0.000
L40/370 Level 3 0.000
Sim D5
D5
E1
-
1--- : 50
-
-
---
---
L40/370
L40/370
E2
1 : 50
Level 3 0.000
S2
L40/370 L40/370
L40/370 L40/370
L40/370
L40/370
L40/370
L40/370
Level 3 0.000
Level 3 0.000
Sim
Sim
CW.02 Section
E3
1 : 50
D5
D6 WCH-GDA-Z1-ZZ-DR-A-30-3138
1 : 50
L40/370
L40/370
Level 4 3.350
L40/370
Mullion and transom sizes TBC
CW.02 Elevation
Level 4 3.350
2130
L40/370
L40/370
L40/370
Level 3 0.000
Mullion and transom sizes TBC
CW.01 Section
S1
L40/370
WCH-GDA-Z1-ZZ-DR-A-30-3138
WCH-GDA-Z1-ZZ-DR-A-30-3138
Mullion and transom sizes TBC
CW.01 Elevation
L40/370C
L40/370
2675
1050
L40/370C
3125 Structural Opening
1275
Level 3 0.000
L40/370C
L40/370
1275
1050
WCH-GDA-Z1-ZZ-DR-A-30-3138
L40/370
L40/370
L40/370
900
L40/370
L40/370
L40/370
535
1220 5435 Structural Opening
L40/370 Level 4 3.350
1905
X31
Level 4 3.350
L40/370
X47
L40/370
1050
1050
L40/370C
L40/370C
L40/370C
Level 5 6.700
D4
WCH-GDA-Z1-ZZ-DR-A-30-3138
Sim D8
Level 5 6.700
465
WCH-GDA-Z1-ZZ-DR-A-30-3138
L40/370
Level 4 3.350
928
D8
L40/370
Level 4 3.350
928
Sim
1220
L40/370C
L40/370C
465
6475 Structural Opening
L40/370C
Level 5 6.700
L40/370C
1150
1150
L40/370C
L40/370
L40/370C
---
Sim
1150
WCH-GDA-Z1-ZZ-DR-A-30-3138
Level 5 6.700
L40/370C
D8
L40/370C
L40/370C
ONCE PRINTED AND DISTRIBUTED THIS DOCUMENT IS ASSUMED UNCONTROLLED
2785 Structural Opening
L40/370
450
1050
Sim L40/370C
© ALL RIGHTS RESERVED. NO PART OF THIS DRAWING MAY BE REPRODUCED OR TRANSMITTED IN ANY FORM OR BY ANY MEANS WITHOUT THE WRITTEN PERMISSIONS OF THE COPYRIGHT HOLDER
D8
L40/370C
Level 5 6.700
1150
Level 5 6.700
REPORT ANY DISCREPANCIES TO THE ARCHITECT OR REPRESENTATIVES THEREOF.
WCH-GDA-Z1-ZZ-DR-A-30-3138
1050
EQ L40/370C
L40/370C
13430 Structural Opening
1150
EQ
L40/370C
1150
13430 Structural Opening
EQ
DO NOT SCALE FROM THIS DRAWING. WORK ONLY TO PRINTED DIMENSIONS.
H11/??? H11/??? H11/??? H11/??? H11/??? H11/??? H11/??? H11/???
---
EQ
Comments
Sim
D8
1150
1050 1150
L40/370
Height
NBS Reference
Level 6 10.050
Sim L40/370C
Length
Frame Depth
2355 Level 7 13.720
L40/370C
THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL OTHER RELEVANT DRAWINGS PREPARED BY CONSULTANTS AND SUBCONTRACTORS.
Curtain Wall Schedule
CW.03 Elevation
S3
1 : 50
CW.03 Section
E4
1 : 50
X44
WCH-GDA-Z1-ZZ-DR-A-30-3138
1855
Mullion and transom sizes TBC
CW.04 Elevation
CW.04 Section
S4
1 : 50
1 : 50
-
-
---
---
X46
Guarding 3 Section
---
6286 Structural Opening 2355
1426
2505 Level 7 13.720
Level 7 13.720
Sim
468
Level 5 6.700
Level 5 6.700
L40/370
L40/370
WCH-GDA-Z1-ZZ-DR-A-30-3138
L40/370
L40/370C
L40/370
L40/370
L40/370
L40/370
1150
L40/370C
L40/370C
L40/370C
L40/370C
L40/370
L40/370
L40/370
L40/370C
L40/370C
D8 Level 5 6.700
Level 5 6.700
WCH-GDA-Z1-ZZ-DR-A-30-3138
X41
GX47
Level 3 0.000
870
1032
1300
510
925
925
241
Level 3 0.000
815
D8
Level 3 0.000
L40/370C
L40/370C
L40/370C
Sim
3093 Structural Opening
WCH-GDA-Z1-ZZ-DR-A-30-3138
Level 4 3.350
Level 4 3.350
1250
1250
Level 4 3.350
593
Level 4 3.350
D1
The Cruck Barn, Duxbury Park, Chorley, Lancashire. PR7 4AT t: 01257 260070 f: 01257 260071
Level 2 -3.350
Mullion and transom sizes TBC
E5
1840
CW.05 Elevation 1 : 50
S5
1 : 50
L40/370
L40/370C
L40/370C
E6
L40/370C L40/370C
L40/370C
CW.06 Elevation E1 1 : 50
Level 2 -3.350
Level 2 -3.350
E6a
CW.06 Elevation E2 1 : 50
Level 3 0.000
L40/370
L40/370C
L40/370 Level 3 0.000
CW.06 Section 1 : 50
E7 ---
0C
Sim
L40/370
L40/370
L40/370C
WCH-GDA-Z1-ZZ-DR-A-30-3138
1 : 50
S7
CW.07 Section
D7 Level 3 0.000
1 : 50
E8
CW.08 Elevation 1 : 50
Redevelopment of West Cumberland Hospital - Phase 2 Title
Sim
Mullion and transom sizes TBC
CW.07 Elevation
Project
D3
Level 3 0.000
Mullion and transom sizes TBC
S6
L40/370C
L4 0/ 37
450 WCH-GDA-Z1-ZZ-DR-A-30-3138
Mullion and transom sizes TBC
1850
L40/370
D5
D6 L40/370C
L40/370C
Sim
L40/370 Level 2 -3.350
L40/370
Sim
L40/370C
L40/370C
G1.1 Sect
1050 L40/370C
1970
L40/370
2375
0/3 70 C
L40/370
L40/370C
L40/370C
L40/370
WCH-GDA-Z1-ZZ-DR-A-30-3138
Level 2 -3.350
L40/370C
2675
L40/370C
3125 Structural Opening
L40/370C
1050
975
0/3 70 C
L40/370C
L4
L40/370
Mullion and transom sizes TBC
CW.05 Section
L40/370C
1275
WCH-GDA-Z1-ZZ-DR-A-30-3138
L40/370C
L4
975
D5
L40/370C
405
L40/370
Sim
1970
L40/370
L40/370
L40/370C
L40/370
405
L40/370
3350 Structural Opening
L40/370
2150
L40/370
L40/370
1225
L40/370
WCH-GDA-Z1-ZZ-DR-A-30-3138
L40/370
Date
Sim
1150
Level 3 0.000
L40/370
Description
Sim 6377 Structural Opening
Level 3 0.000
By
Riser steel roof level 9375
L40/370
1050
X45
X45
Level 6 10.050
Rev L40/370C
L40/370C
L40/370
L40/370
L40/370
L40/370
X31
L40/370
1150
L40/370
L40/370
L40/370
L40/370
Level 4 3.350
X32 2125
9825 Structural Opening
1225
Level 4 3.350
13430 Structural Opening
L40/370
L40/370
2125
L40/370
L40/370
L40/370
D8 WCH-GDA-Z1-ZZ-DR-A-30-3138 Level 6 10.050
1150
L40/370
D4
L40/370
975
L40/370
Sim L40/370
L40/370
1150
920
L40/370C
1050
920
L40/370C
Sim
2810 Structural Opening 503
1055
2
L40/370C
1150
A
D2 WCH-GDA-Z1-ZZ-DR-A-30-3138
Curtain Wall Sections & Elevations
WCH-GDA-Z1-ZZ-DR-A-30-3138
Project Status
Project Number
For Tender
6995B
Project Issue Date CW.08 Section 25/02/14 S8 1 : 50 Scale
1 : 50
Drawn By
Checked By
II
Checker
Sheet Size
Rev.
A0
Drawing Number
WCH-GDA-Z1-01-DR-A-30-3137
6-23 6-E
6-23 6-E
+10.050
+10.050
+10.050
11 N
INTERMEDIATE WALL
PROFILE OF TERRACE DIVIDING WALL WHICH ABUTS GRP BALUSTRADE REFER TO SEPARATE DETAIL ON DRAWING CTM-AR-BKN-C6-L99-47-006
10
1250
1250
TERRACE BALCONY BUILDUP: (WPS-10) LIQUID APPLIED WATERPROOF FINISH (WITH INTEGRAL FINISH), ON SCREED LAID TO FALL, ON SEPARATION LAYER OVER RIGID INSULATION.
175MM WIDE GAP IN RC KERB UPSTAND TO ACCOMMODATE PREFORMED GUTTER OUTLET (PROFILE BEYOND) SHOWN DOTTED
PRE-FORMED GALVANISED STEEL OUTLET, WITH PCC COATING TO MATCH ADJACENT RAINWATER GOODS. OUTLET SECURELY FIXED TO KERBS AND CANTILEVERED OVER HOPPER AND GRC MOULDING BELOW
PRE-FORMED GALVANISED STEEL OUTLET, WITH PCC COATING TO MATCH ADJACENT RAINWATER GOODS. OUTLET SECURELY FIXED TO KERBS AND CANTILEVERED OVER HOPPER AND GRC MOULDING BELOW
LOCALISED ALTERATION TO BALUSTRADE TO ACCOMMODATE OUTLET - REFER TO ELEVATION
+8.800 GRC MOULDING PROFILE. REFER TO SEPARATE DETAIL FOR DETAILED PROFILE AND METHOD OF FIXING
9
200
200
205
LINE OF SLAB BEYOND SHOWN DOTTED
OUTLET TO BE SECURELY FIXED TO RESPECTIVE BLOCK ONLY. NO FIXING TO BRIDGE SEISMIC JOINT IN BUILDING FACE / FACADE
180
200
200
LOCALISED ALTERATION TO BALUSTRADE TO ACCOMMODATE OUTLET - MIN 10MM CLEARANCE TO FULL PERIMETER, VOID MASTIC FILLED TO PREVENT MOMENT OF OUTLET THROUGH WIND UPLIFT & TO PREVENT WATER INGRESS
200
150
Level 05 350
75
Level 05
205
DRAINAGE CHANNEL (LAID FLAT) FORMED WITHIN SCREED. MIN 150 X 50MM DEEP. TO BE CONNECTED TO THE FACADE HOPPERS VIA A SPIT DETAIL. REFER TO SEPARATE DETAIL
150
DOWN PIPE
+8.825
MESH REINFORCEMENT
GRC MOULDING PROFILE - REFER TO SEPARATE DETAIL FOR DETAILED PROFILE AND METHOD OF FIXING - ALTERED LOCALLY TO SUIT OUTLET PENETRATION
401 *
100
+8.895
175
PROFILE OF TERRACE AND GUTTER BEYOND SHOWN DOTTED
250
1:60 FALL TO TERRACE
PRE-FORMED GALVANISED STEEL OUTLET, WITH PCC COATING TO MATCH ADJACENT RAINWATER GOODS. OUTLET SECURELY FIXED TO KERBS AND CANTILEVERED OVER HOPPER AND GRC MOULDING BELOW MIN 2.5MM THK STEEL SHEET WITH WELDED JOINTS, REINFORCED AT EXTERNAL CORNERS.
70
TILT FILLET & REINFORCED COVERING AT CORNERS OF GUTTER
150 OPENING
250MM HIGH RC KERB, TO S.E. DETAIL
Level 05
+8.800
+8.800
OUTLET TO BE SECURELY FIXED TO RESPECTIVE BLOCK ONLY. NO FIXING TO BRIDGE SEISMIC JOINT IN BUILDING / FACADE
180
SURFACE WATER HOPPER REFER TO SPECIFICATION FOR FULL DETAILS OF RAINWATER GOODS, INCLUDING DOWNPIPES
PROFILE OF HOPPER IN FOREGROUND SHOWN DOTTED SURFACE WATER HOPPER REFER TO SPECIFICATION FOR FULL DETAILS OF RAINWATER GOODS, INCLUDING DOWNPIPES
GRC MOULDING PROFILE. REFER TO SEPARATE DETAIL FOR DETAILED PROFILE AND METHOD OF FIXING
8
01
Hopper Single Spout-Section A
Hopper Single Spout-Section B
02
1 : 10
1 : 10
03
7
6-A 6-E
Typical Roof Hopper Elevation 1 : 10
345 2 x 15mm MARINE PLY BOARD
COPING: PPC ALUMINIUM COPING PANEL, MECHANICALLY FIXED.
FFL +12.422 50
PPC FLASHING PIECE FIXED TO UPPER PROFILE EDGE, WP FINISH LAPPED OVER.
GALVANISED STEEL SUPPORT ANGLE TO SUPPORT UPSTAND BUILDUP. FIXED TO TOP SIDE OF ROOF JOISTS. TIMBER BUILDUP FOR STIFFENING AND FIXING. STRUCTURAL ENGINEER TO CONFIRM SUPPORT DETAIL.
DECORATIVE PROFILE TO DORMER. MECHANICALLY FIXED.
395
2 x 15mm MARINE PLY BOARD. FRL +10.050
6
367
150MM INSULATION WITHIN THE 150MM CAVITY
100
85MM INSULATION
2 x 15mm PLASTERBOARD. + 2 OWNER FIT OUT
25
MASTIC SEAL AT ABUTMENTOF DOOR FRAME AND FASCIA. DOOR MANUFACTURER TO PROVIDE EPDM TO FULL EXTEND OF DOOR FRAME, FIXED BACK TO DORMER STRUCTURE
DPM FITTED OVER TREATED SW PACKER AND UP FORMED UPSTAND. EPDM
M20/220A RENDERED FINISH ON EXPANDED GLASS GRANULATE CARRIER BOARD
VAPOUR BARRIER (BLUE) 2 X 15MM PLASTERBOARD
SCREED LAID TO 1:60 FALLS TO PERIMETER BALCONY GUTTER
50 X 85MM TIMBER NOGGINS FITTED TO UNDERSIDE OF PLASTERBOARD THROUGH TO JOISTS ABOVE.
2 x 15MM PLASTERBOARD = BY OWNER.
5
250mm HIGH IN-SITU CONCRETE KERB UPSTAND
SEPARATION LAYER
SSL +8.950
250
Level 05 +8.800
372
WHERE POSSIBLE UPSTAND BOARD TO BE TAKEN 600mm FROM ROOF SLAB TO MINIMISE CUTS AND UTILISE STANDARD BOARD DEPTH. MIN. UPSTAND OF 150mm ABOVE FRL TO BE ACHIEVED
LINE OF MANSARD ROOF BEYOND/ BETWEEN WINDOW PROJECTION
3407
150 POST
5
Intermediate Wall Section C 1 : 10
OPENING WITHIN INTERMEDIATE WALL TO ALLOW FLOW OF WATER TO HOPPER
+8.917
400
SURFACE WATER HOPPER CENTERED ON INTERMEDIATE WALL. REFER TO SPECIFICATION FOR FULL DETAILS OF RAINWATER GOODS, INCLUDING DOWNPIPES.
100
MESH REINFORCEMENT
300 200
1595
200
B
1 1:10 Scale Bar
0
0.1
0.2
04 0.5
06
1 : 10
XX.07.2016
Drn.
Ckd. Appd. Date
Port Baku Towers 153, Neftchilyar Avenue AZ1010 Baku, Azerbaijan T: 00 994 12 404 48 00 F: 00 994 12 498 58 01
Construction Manager:
PASHA INSAAT MMC. Port Baku Towers 153, Neftchilyar Avenue AZ1010 Baku, Azerbaijan
PASHA Insaat
T: 00 994 12 404 48 00 F: 00 994 12 498 58 01
Chapman Taylor Bass Warehouse 4 Castle Street Castlefield Manchester, MLZ T: +44 (0)161 828 6500 F: +44 (0)161 828 6505
URAL Engineering Co. Inc
Structural Engineer:
Akpınar Mahallesi Dikmen Caddesi No:538/14 Çankaya, 06460 Ankara, Turkey T: +90 (312) 475 2848 F: +90 (312) 475 2844 e-mail:info@ural.comtr
Black & White Engineering Limited
Services Engineer:
Unit 2.8 First Floor Generator Studios Trafalgar Street Newcastle upon Tyne NE1 2LA T: +44 (0)191 230 0206 e-mail:enquiries@bw-engineering.com
WSP Group (London)
Traffic Consultant:
WSP House 70 Chancery Lane London WC2A 1AF T: +44 (0)207 314 5000 F: +44 (0)207 314 5111
FALLS
H+H Fire
Fire Engineer:
41-42 London Wall London EC2M 5TB T: +44 (0)207 193 2990 e-mail:glennhorton@hhfire.com
Project Description:
BAKU KNIGHTSBRIDGE Drawing Title:
Typical Roof Hopper Details
Status: CONSTRUCTION
A II
Client Project Code:
Flat Roof Section Detail- Waterproofing
TP
PASHA INSAAT MMC.
Drawn by:
DRAINAGE CHANNEL (LAID FLAT) FORMED WITHIN SCREED. MIN 150 X 50MM DEEP. TO BE CONNECTED TO THE FACADE HOPPERS VIA A SPIT DETAIL. REFER TO SEPARATE DETAIL
RR
PASHA Insaat
375
10
GUTTER
1500 155
1:60 FALL TO TERRACE
WALL PLATE TO ACT AS (PART) BACKING FOR INSULATED KERB AND FIXING POINT FOR INTERNAL FINISHES, SILL BOARD AND DOOR FRAME. ALL TO S.E. DETAIL & SPEC. 300
125
25
+8.800
50 75 70
Level 05
+8.825
OPENING
+8.895
FALL
150
175
6-E
200 x 75mm SW WALLPLATE AT DOOR OPENING ONLY (FIXED BETWEEN 150 X 150mm TIMBER POSTS), STRAPPED TO RC KERB AT SLAB LEVEL AT MAX 1800CTS, USING 30 x 5mm GALV MS STRAPS.
TILT FILLET & REINFORCED COVERING AT CORNERS OF GUTTER
FALLS
FALL
1250
1152 (MIN 1100MM)
LINE OF SPOUT INTO ADJACENT HOPPER & DOWNPIPE BEYOND BALUSTRADE
FFL +8.800
FALLS
TERRACE BALCONY BUILDUP: (WPS-10) LIQUID APPLIED WATERPROOF FINISH (WITH INTEGRAL FINISH), ON SCREED LAID TO FALL, ON SEPARATION LAYER OVER RIGID INSULATION.
251
2
g de 70
25MM RIGID INSULATION SLAB TO UPSTAND, REQUIRED TO REDUCE COLD BRIDGE THROUGH DETAIL
RC KERB
PRE-FORMED GALVANISED STEEL OUTLET, WITH PCC COATING TO MATCH ADJACENT RAINWATER GOODS. OUTLET SECURELY FIXED TO KERBS AND CANTILEVERED OVER HOPPER AND GRC MOULDING BELOW
THRESHOLD FLASHING BY DOOR MANUFACTURER. 60MM THICK SIKA CEM TOP BOARD INSULATION TO UPSTAND. WP LAPPED UP ON TO THRESHOLD
II
Architect:
3 OPENING WITHIN INTERMEDIATE WALL TO ALLOW FLOW OF WATER TO HOPPER
Description
M20/220A RENDERED FINISH ON EXPANDED GLASS GRANULATE CARRIER BOARD
GRC MOULDING
+10.050
DRIP CILL: PPC ALUMINIUM CILL AT BASE OF INTERMEDIATE WALLS, MECHANICALLY FIXED.
RENDER
C
Construction Issue
Owner:
175
72
Rev.
SIKA CEMTOPPED COMPOSITE CEMENT / INSULATION BOARD, 60mm THICK. MECHANICALLY FIXED TO UPSTAND OVER WATERPROOF LAYER
3010
445
GRC CAST BALUSTRADE. GALVANISED AND PAINTED STEEL SUPPORT STRUCTURE WITHIN. ANCHOR-B FIXED TO CONCRETE UPSTAND
2635 S/0
MANSARD 'EAVES' HEIGHT THROUGHOUT TO BE EQUAL AND SET CONSTANTLY ABOVE STRUCTURAL SLAB LEVEL REFER TO CTM-AR-BKN-CY-L06-27-011 FOR RAFTER SET OUT INFORMATION
SSL +8.700
0
200
THERMALLY BROKEN ALUMINIUM FRENCH DOOR.
345
180
DEPTH OF ROOF BUILD-UP SHOWN BEYOND
4
WPS-10 WARM DECK ROOF SYSTEM COMPRISING SCREED FINISH LAID TO FALLS ON SIKA MinFX SEAPARATION LAYER INVERTED ROOF INSULATION BOARD TERRAM 1B1 DECO DRAINAGE COMPOSITE MAT DECOTHANE ROOT RESISTANT WATERPROOFING SYSTEM, REINFORCED WITH SIKA REEMAT PREMIUM GLASS FIBRE MATTING SIKA LIQUID PLASTICS PREPARATORY LAYER BONDED / MECHANICALLY FIXED TO STRUCTURE CONSTRUCTED IN STRICT ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS & SPECIFICATION.
180
1:60 FALL ACROSS TERRACE
WATERPROOF LAYER 192
150MM SQ TIMBER POST BEYOND SHOWN DOTTED
1:60 FALL ACROSS TERRACE
600
150MM TIMBER RAFTER BEYOND SHOWN DOTTED
Roof Hopper Plan View
Checked by:
Original Sheet Size:
1330
1 : 10
RR
A0
Approved by: Scale: 1 : 10
Drawing Number:
TP Sheet: of: Rev:
CTM - AR - BKN - C6 - L99 - 47 - 009
1M
THIS DRAWING MUST NOT BE SCALED.
0
© COPYRIGHT CHAPMAN TAYLOR 2015
ALL DIMENSIONS ARE TO BE VERIFIED AND CHECKED ON SITE. ANY DISCREPANCIES THAT ARE, OR BECOME APPARENT SHOULD BE REPORTED TO CHAPMAN TAYLOR.
A
B
C
D
E
F
G
H
I
J
K
L
M
N
AREAS INDICATED ARE APPROXIMATE GROSS INTERNAL AREA. THEY RELATE TO THE LIKELY AREAS OF THE BUILDING AT THE CURRENT STAGE OF DESIGN. ANY DECISIONS TO BE MADE ON THE BASIS OF THESE PREDICTIONS, WHETHER AS TO PROJECT VIABILITY, PRE-LETTING, LEASE AGREEMENTS, OR THE LIKE, SHOULD INCLUDE DUE ALLOWANCE FOR THE INCREASES AND DECREASES INHERENT IN THE DESIGN DEVELOPMENT AND BUILDING PROCESS.
ONCE PRINTED AND DISRIBUTED THIS DOCUMENT IS ASSUMED UNCONTROLLED © All rights reserved. No part of this drawing may be reproduced or transmitted in any forms and by any means without written permission of the copyright holder.
CONTINUOUS CAST-IN CHANNEL HILTI HAC-70F
ANCON FHR HEAD RESTRAINT FIXED AT APPROX. 1500 CENTRES STAGGERED EACH SIDE OF WALL HEAD. FINISH HOT DIPPED GALVANISED
250
ROCKWOOL INTUMESCENT SEALANT FLUSH WITH WALL LINEAR FIRESTOP 2 BY ROCKWOOL OR SIMILAR APPROVED TO ALLOW MIN. 50MM DEFLECTION HEAD
TO MITIGATE THIS, UNDERTAKE A "FERRO SCAN" TO ESTABLISH THE LOCATION AND AVOID THE REBAR OR POST DRILL AND STOP WHEN REBAR IS HIT, THEN RE-DRILL AND POSTFIX ANCHOR IN LOCATION WITHOUT CLASH.
CUT BLOCK ON ONE-BUTLAST COURSE
CUT BLOCK ON ONE-BUT-LAST COURSE SLIDING HEAD RESTRAINT ANCON IHR-V OR EQUAL FIXED TO SOFFIT OF SLAB WIDTH M10 SINGLE EXPANSION BOLTS, PLACED AT EVERY SECOND PERPEND.
10
200MM THICK GOBUSTONE BLOCKWORK WALL
THIS WILL HOWEVER NECESSITATE LOTS OF DRILLING AND THE INCLUSION OF DETAILING (EG. SLOTTED HOLES IN STEEL PLATES AND ANGLES) TO ACCOMODATE SUCH HILTI HBC-C 8.8F M12 SHIFTS. BOLTS @250MM CENTRES
LINE OF WALL FINISHES INDICATIVE ONLY
120x120x10MM CONTINUOUS STEEL ANGLE. MATERIAL: S275 HOT-DIP GALVANISED
PFC COROFIL C500 FILLER & PFC COROFIL ACOUSTIC INTUMESCENT SEALANT OR SIMILAR APPROVED
200MM THICK GOBUSTONE AERATED BLOCKWORK WALL LINE OF WALL FINISHES INDICATIVE ONLY
150
N
160
40
200
WINDPOST IS ALLOWED TO SLIDE BETWEEN STEEL ANGLE AND POST
9
200
8
30 100
11
JOINING DETAILS TO WALL
120
50
ALTERNATIVE TO CAST-IN CHANNELS IS TO POSTDRILL AND ANCHOR THE STEEL PLATES/ANGLESBUT WILL LIKELY CLASH WITH REBAR.
250
IN-SITU CONCRETE SLAB TO STRUCTURAL ENGINEER'S DESIGN DETAILS & SPEC.
50
IN-SITU CONCRETE SLAB TO STRUCTURAL ENGINEER'S DESIGN DETAILS & SPEC.
200
DETAIL B: Typical Section thru 200mm Single Leaf Aerated Blockwork Wall showing Ancon IHR-V Internal Head Restraint
200 PRIMARY STRUCTURE
Alternative head restraint detail (to Detail B) applicable to all masonry walls higher than 3.5 meters and wider than 4.0 meters for both exterior & Interior walls
Column 600mm Width varies
Vertical section through windpost/beam interface
SECONDARY STRUCTURE
200
A
200
7
REINFORCED CONCRETE VERTICAL TIE/COLUMN
250
REINFORCED CONCRETE VERTICAL TIE/COLUMN
B
6
WALL SHOULD BE CUT. SURFACE SHOULD BE WASHED & CLEANED
WALL SHOULD BE CUT. SURFACE SHOULD BE WASHED & CLEANED
CHEMICAL ANCHORING
CHEMICAL ANCHORING
CONCRETE SLAB
MID TIE-BEAM TO STR. ENG'S DESIGN & SPECIFICATION. UNDERSIDE OF BEAM TO BE SET AT DOOR OPENING LEVEL IN LIEU OF CONCRETE LINTOL WHEREVER POSSIBLE
4Ø 16
250
B
IN-SITU GROUND CONCRETE SLAB TO STR. ENG'S DESIGN DETAILS & SPECIFICATION
250
IN-SITU GROUND CONCRETE SLAB TO STR. ENG'S DESIGN DETAILS & SPECIFICATION
200MM THICK GOBUSTONE BLOCKWORK WALL
CONCRETE SLAB
5
A DETAIL C: Typical Concrete Column elevation above showing steel reinforcement
Cross-section A-A thru typical Concrete Column above showing steel reinforcement
0
Cross-section above thru typical horizontal tie beam showing steel reinforcement
Rev.
Construction Issue
MP
RR
Description
Drn.
Ckd. Appd. Date
Owner:
Port Baku Towers 153, Neftchilyar Avenue AZ1010 Baku, Azerbaijan T: 00 994 12 404 48 00 F: 00 994 12 498 58 01
Construction Manager:
PASHA INSAAT MMC. Port Baku Towers 153, Neftchilyar Avenue AZ1010 Baku, Azerbaijan
PASHA Insaat Cross-section thru typical Concrete Column showing steel reinforcement to horizontal tie beam
Cross-section B-B thru typical Concrete Column below showing plan view of steel reinforcement
Column Width varies
T: 00 994 12 404 48 00 F: 00 994 12 498 58 01
Chapman Taylor
Architect:
Bass Warehouse 4 Castle Street Castlefield Manchester, MLZ T: +44 (0)161 828 6500 F: +44 (0)161 828 6505
URAL Engineering Co. Inc
Structural Engineer:
REINFORCED CONCRETE VERTICAL TIE/COLUMN 3
REINFORCED CONCRETE HORIZONTAL TIE BEAM
Akpınar Mahallesi Dikmen Caddesi No:538/14 Çankaya, 06460 Ankara, Turkey T: +90 (312) 475 2848 F: +90 (312) 475 2844 e-mail:info@ural.comtr
CHEMICAL ANCHORING CHEMICAL ANCHORING
Black & White Engineering Limited
Services Engineer:
Column 600mm Width varies
Unit 2.8 First Floor Generator Studios Trafalgar Street Newcastle upon Tyne NE1 2LA T: +44 (0)191 230 0206 e-mail:enquiries@bw-engineering.com
WSP Group (London)
200
Traffic Consultant:
250
01.07.16
PASHA INSAAT MMC.
PASHA Insaat
4
TP
WSP House 70 Chancery Lane London WC2A 1AF T: +44 (0)207 314 5000 F: +44 (0)207 314 5111
6Ø 16
H+H Fire
Fire Engineer:
41-42 London Wall London EC2M 5TB T: +44 (0)207 193 2990 e-mail:glennhorton@hhfire.com
2 Project Description:
BAKU KNIGHTSBRIDGE
WALL SHOULD BE CUT. SURFACE SHOULD BE WASHED & CLEANED
CONCRETE COLUMN WIDTH VARIES IN ALL CASES
Drawing Title:
CHEMICAL ANCHORING
Typical Blockwork Junction Details Sheet 4 of 4 Courtyard 6. Block BL01 Status: CONSTRUCTION Drawn by:
• •
1 1:100 Scale Bar
0
1
2
5
10M
• •
GENERAL NOTES: Vertical beams to be anchored to the slab with 12mm steel bar. Exact position of masonry walls are subject to design development and final on-site coordination. All walls to maintain min. 2 hour Fire Resistance, unless stated. Full-fill cavity insulation to all cavity walls within habitable areas, including apartments, bin stores, plant rooms, store rooms.
• •
The level of the horizontal tie beam is tentative and should be arranged on site according to door gross reservation so that the tie beam also works as lintel over the doors. Individual concrete lintels over openings to have a minimum bearing of 250mm either side of the lintel (refer to Gobustone).
II
Client Project Code:
Checked by:
RR
Original Sheet Size:
1330
A0
Approved by: Scale: 1:5
Drawing Number:
TP Sheet: of: Rev:
CTM - AR - BKN - C6 - L99 - 22 - 203 THIS DRAWING MUST NOT BE SCALED.
0
© COPYRIGHT CHAPMAN TAYLOR 2015
ALL DIMENSIONS ARE TO BE VERIFIED AND CHECKED ON SITE. ANY DISCREPANCIES THAT ARE, OR BECOME APPARENT SHOULD BE REPORTED TO CHAPMAN TAYLOR.
A
B
C
D
E
F
G
H
I
J
K
L
M
N
AREAS INDICATED ARE APPROXIMATE GROSS INTERNAL AREA. THEY RELATE TO THE LIKELY AREAS OF THE BUILDING AT THE CURRENT STAGE OF DESIGN. ANY DECISIONS TO BE MADE ON THE BASIS OF THESE PREDICTIONS, WHETHER AS TO PROJECT VIABILITY, PRE-LETTING, LEASE AGREEMENTS, OR THE LIKE, SHOULD INCLUDE DUE ALLOWANCE FOR THE INCREASES AND DECREASES INHERENT IN THE DESIGN DEVELOPMENT AND BUILDING PROCESS.
ONCE PRINTED AND DISRIBUTED THIS DOCUMENT IS ASSUMED UNCONTROLLED © All rights reserved. No part of this drawing may be reproduced or transmitted in any forms and by any means without written permission of the copyright holder.
NBS Ref: F10/370A - Category G2 200/100mm Blockwork to Inner Courtyard Elevations & Internal Non Load bearing Walls.
10
ROCKWOOL INTUMESCENT SEALANT. COLOUR TO MATCH WALL FINISH
TYPICAL SEISMIC WALL WITH 150MM CAVITY 500
20
ANGLE FHR HEAD RESTRAINT S APPLICABLE ONLY TO WALLS HIGHER THAN 3.5M AND WIDER THAN 4.0M FOR BOTH EXTERIOR & INTERIOR WALLS.
100MM THICK GOBUSTONE BLOCKWORK WALL
ROCKWOOL INTUMESCENT SEALANT
SEE WALL FINISHES PLANS & SCHEDULES FOR RENDER/PLASTER AND PAINT FINISH DETAILS
ANCON WALL TIES (REF: CCB-SMJ-200) AT 500MM VERTICAL
N
20
200 375
20
25 FIRE RATED SEALANT TO 20MM JOINT BY ROCKWOOL
ANCON WALL TIES (REF: CCB-JJ) AT MAX 500MM VERTICAL CENTRES FIRE RATED SEALANT TO 20MM JOINT BY ROCKWOOL
150
400
FIRE RATED SEALANT TO 20MM FLEXIBLE JOINT BY ROCKWOOL ROCKWOOL INTUMESCENT SEALANT. COLOUR TO MATCH WALL FINISH
200MM THICK GOBUSTONE CAVITY BLOCK WALL WITH VERTICAL MOVEMENT JOINTS.
ROCKWOOL INTUMESCENT SEALANT COLOUR O MATCH WALL FINISH
DETAIL O Typical plan view of movement joint within Blockwork Wall sections longer than 6m between RC Structural Elements.
DETAIL L TYPICAL SECTIONS BELOW SHOWING ALTERNATIVE HEAD RESTRAINT DETAIL APPLICABLE TO ALL MASONRY WALLS HIGHER THAN 3.5 METERS AND WIDER THAN 4.0 METERS FOR BOTH EXTERIOR & INTERIOR WALLS.
FAIR-FACED BLOCKWORK WALL. NO APPLIED WALL FINISHES
9 FASTLIGHT AIRSEAL COATING APPLIED ABOVE DEFLECTION HEAD
FIRE RATED SEALANT TO 25MM FLEXIBLE JOINT BY ROCKWOOL
200MM THICK GOBUSTONE CAVITY BLOCK WALL WITH VERTICAL MOVEMENT JOINTS.
1050
200MM IN-SITU CONCRETE SLAB TO STR. ENG'S DESIGN DETAILS & SPEC.
ANCON WALL TIES (REF: CCB-SMJ-200) AT 500MM VERTICAL CENTRES FIXED TO CONCRETE COLUMN
8
CUT BLOCK IF REQUIRED ON ONE BUT LAST COURSE
CUT BLOCK ON ONE-BUTLAST COURSE
CUT BLOCK ON ONE-BUTLAST COURSE
WALL TIES AT 2 COURSE CENTRES TO BE STAGGERED VERTICALLY IN ACCORDANCE WITH BS:5268-1:2005
100MM THICK GOBUSTONE BLOCKWORK WALL
20
200MM THICK GOBUSTONE BLOCKWORK WALL
IN-SITU CONCRETE WALL TO STR. ENG'S DESIGN DETAILS & SPECIFICATION. NOTE: WALL SIZE INDICATIVE ONLY.
FAIR-FACED BLOCKWORK WALL. NO APPLIED WALL FINISHES
400
400
ANCON WALL TIES (REF: CCB-L200) 500MM VERTICAL CENTRES FIXED TO IN-SITU CONCRETE COLUMN & WALLS
200MM THICK GOBUSTONE BLOCKWORK WALL
FAIR-FACED BLOCKWORK WALL. NO APPLIED WALL FINISHES
200
FAIR-FACED BLOCKWORK WALL. NO APPLIED WALL FINISHES
7 200MM THICK GOBUSTONE BLOCKWORK WALL
400
CUT BLOCK IF REQUIRED ON ONE BUT LAST COURSE
SEE WALL FINISHES PLANS & SCHEDULES FOR RENDER/PLASTER AND PAINT FINISH DETAILS
20
150
ANCON FHR HEAD RESTRAINT FIXED AT APPROX. 1500 CENTRES STAGGERED EACH SIDE OF WALL HEAD. FINISH HOT DIPPED GALVANISED
200
PFC COROFIL C500 FILLER & PFC COROFIL ACOUSTIC INTUMESCENT SEALANT OR SIMILAR APPROVED
150
WALL FINNISHES INDICATIVE ONLY. INTERNAL FINISHES BY TENANT/ OWNER.
150
PFC COROFIL C500 FILLER & PFC COROFIL ACOUSTIC INTUMESCENT SEALANT OR SIMILAR APPROVED
400
20 ANGLE FHR HEAD RESTRAINT FIXED AT APPROX. 1500 CENTRES STAGGERED EACH SIDE OF WALL HEAD. FINISH HOT DIPPED GALVANISED
20
FIRE RATED FILLER/SEALANT TO 20MM FLEXIBLE JOINT BY ROCKWOOL
WALL FINNISHES INDICATIVE ONLY. INTERNAL FINISHES BY TENANT/ OWNER.
FAIR-FACED BLOCKWORK WALL. NO APPLIED WALL FINISHES
ROCKWOOL INTUMESCENT SEALANT. COLOUR TO MATCH WALL FINISH
100MM THICK GOBUSTONE BLOCKWORK WALL FULL-FILL CAVITY INSULATION TO ALL CAVITY WALLS WITHIN HABITABLE AREAS, INCLUDING BIN STORES, PLANT ROOMS, STORE ROOMS.
200
150
200
550
100
300
375
DETAIL M Typical elevation view of in-situ column within Single Leaf Blockwork wall. Mid concrete tie-bean only applicable to Level B1 (or wall heights of more than 4.0 meters)
75
100
200
475
20
In-situ Concrete Column
IN-SITU CONCRETE COLUMN TO STR. ENG'S DESIGN DETAILS & SPEC. NOTE: COLUMN SIZE INDICATIVE ONLY.
20 ANCON WALL TIES AT EVERY OTHER BLOCK ROW REF: CCB-SMJ-200 & CCB-L200
600
ROCKWOOL INTUMESCENT SEALANT. SEALANT COLOUR TO MATCH WALL FINISH
FIRE RATED SEALANT TO 20MM FLEXIBLE JOINT BY ROCKWOOL
20
200
Width varies
FIRE RATED SEALANT TO 20MM FLEXIBLE JOINT BY ROCKWOOL
0
375
CCB-SMJ-200 75
CCB-SMJ-200
600
5
75
IN-SITU CONCRETE COLUMN TO STR. ENG'S DESIGN DETAILS & SPEC. NOTE: COLUMN SIZE INDICATIVE ONLY.
DETAIL P Typical plan view of Blockwork wall joints within Seismic walls
FULL-FILL CAVITY INSULATION TO ALL CAVITY WALLS WITHIN HABITABLE AREAS, INCLUDING BIN STORES, PLANT ROOMS, STORE ROOMS.
200
800
Rev.
Construction Issue
MP
RR
Description
Drn.
Ckd. Appd. Date
Owner:
T: 00 994 12 404 48 00 F: 00 994 12 498 58 01
Construction Manager: CCB-L200
20
CCB-L200
NOTE: LOCATION OF CONCRETE TIE-BEAM IS TENTATIVE AND SHOULD BE ARRANGED ON SITE ACCORDING TO DOOR GROSS RESERVATION SO THAT THE TIE BEAM ALSO WORKS AS LINTEL SUPPORT OF THE DOOR
MIDDLE TIE-BEAM TO STR. ENG'S DESIGN & SPECIFICATION. UNDERSIDE OF BEAM TO BE SET AT DOOR OPENING LEVEL IN LIEU OF LINTOL WHERE POSSIBLE
ANCON WALL TIES (REF: CCB-JJ) AT MAX 500MM VERTICAL CENTRES
MIDDLE TIE-BEAM TO STR. ENG'S DESIGN & SPECIFICATION. UNDERSIDE OF BEAM TO BE SET AT DOOR OPENING LEVEL IN LIEU OF LINTOL WHERE POSSIBLE
CCB-L200
ANCON WALL TIES (REF: CCB-SMJ-200) 500MM VERTICAL CENTRES FIXED TO CONCRETE COLUMN
ANCON STAIFIX RT2 WALL TIES AT 500MM VERTICAL CENTRES IN ALTERNATIVE COURSES TO ANCON PPS WALL TIES
ANCON WALL TIES (REF: CCB-SMJ-200) 500MM VERTICAL CENTRES
PASHA INSAAT MMC. Port Baku Towers 153, Neftchilyar Avenue AZ1010 Baku, Azerbaijan
PASHA Insaat
FAIR-FACED BLOCKWORK WALL. NO APPLIED WALL FINISHES
T: 00 994 12 404 48 00 F: 00 994 12 498 58 01
Chapman Taylor
Architect:
Bass Warehouse 4 Castle Street Castlefield Manchester, MLZ T: +44 (0)161 828 6500 F: +44 (0)161 828 6505
CCB-L200 FULL-FILL CAVITY INSULATION TO ALL CAVITY WALLS WITHIN HABITABLE AREAS, INCLUDING BIN STORES, PLANT ROOMS, STORE ROOMS. 200MM AERATED GOBUSTONE BLOCKWORK WALL
600
3 CCB-SMJ-200
CCB-SMJ-200
URAL Engineering Co. Inc
Structural Engineer:
DETAIL Q Typical plan view of Internal Corner of Double Leaf Blockwork Wall/Column Junction
Akpınar Mahallesi Dikmen Caddesi No:538/14 Çankaya, 06460 Ankara, Turkey T: +90 (312) 475 2848 F: +90 (312) 475 2844 e-mail:info@ural.comtr
Black & White Engineering Limited
Services Engineer:
Unit 2.8 First Floor Generator Studios Trafalgar Street Newcastle upon Tyne NE1 2LA T: +44 (0)191 230 0206 e-mail:enquiries@bw-engineering.com
100MM AERATED GOBUSTONE BLOCKWORK WALL
ANCON WALL TIES (REF: CCB-JJ) AT MAX 500MM VERTICAL CENTRES IN-SITU CONCRETE COLUMN TO STR. ENG'S DESIGN DETAILS & SPEC. NOTE: COLUMN WIDTH INDICATIVE IN ALL CASES
WSP Group (London)
Traffic Consultant:
FIRE RATED SEALANT TO FLEXIBLE JOINT BY ROCKWOOL
WSP House 70 Chancery Lane London WC2A 1AF T: +44 (0)207 314 5000 F: +44 (0)207 314 5111
WALL FINNISHES INDICATIVE ONLY. INTERNAL FINISHES BY TENANT/ OWNER. SEE WALL FINISHES PLANS & SCHEDULES FOR RENDER/PLASTER AND PAINT FINISH DETAILS
20
ANCON WALL TIES AT EVERY OTHER BLOCK ROW REF: CCB-SMJ-200 & CCB-L200
H+H Fire
Fire Engineer:
41-42 London Wall London EC2M 5TB T: +44 (0)207 193 2990 e-mail:glennhorton@hhfire.com
200
200
2 ANCON WALL TIES (REF: CCB-SMJ-200) AT EVERY OTHER BLOCK ROW
IN-SITU CONCRETE COLUMN TO STR. ENG'S DESIGN DETAILS & SPEC. NOTE: COLUMN WIDTH INDICATIVE ONLY 20
In-situ Concrete Column
FAIR-FACED BLOCKWORK WALL. NO APPLIED WALL FINISHES
FIRE RATED SEALANT TO 20MM JOINT BY ROCKWOOL
Project Description:
INSULATED CAVITY CLOSER
Drawing Title:
IN-SITU CONCRETE CORNER POST TO ALL OPENINGS
Internal Blockwork Head Restraint Details Sheet 2 of 4 Courtyard 6. Block BL01
BAKU KNIGHTSBRIDGE
20
Width varies
Status:
200
200
DETAIL N Typical plan view of in-situ column within Single Leaf Blockwork wall. Note: See GA Plans (series 03) for wall setting-out.
ROCKWOOL INTUMESCENT SEALANT TO EITHER SIDE
CONSTRUCTION INDICATIVE DOOR & JAMB Drawn by:
1:100 Scale Bar
1
2
5
II
Client Project Code:
FIRE RATED FILLER/SEALANT TO 20MM FLEXIBLE JOINT BY ROCKWOOL
1
0
01.07.16
Port Baku Towers 153, Neftchilyar Avenue AZ1010 Baku, Azerbaijan
PASHA Insaat
20
4
TP
PASHA INSAAT MMC.
100
6
FULL-FILL CAVITY INSULATION TO ALL CAVITY WALLS WITHIN HABITABLE AREAS, INCLUDING BIN STORES, PLANT ROOMS, STORE ROOMS.
800
50
50
50
200MM THICK GOBUSTONE BLOCKWORK WALL WITH VERTICAL MOVEMENT JOINTS. 50
WALL FINNISHES INDICATIVE ONLY. INTERNAL FINISHES BY TENANT/ OWNER.
100
GENERAL NOTES: At vertical edges of an opening, unreturned or unbonded edges, additional wall ties should be used at a rate of one per 250mm height, located no more than 250mm from the edge.
ANCON WALL TIES (REF: CCB-SMJ-200) 500MM VERTICAL CENTRES
ANCON WALL TIES (REF: CCB-TMJ-200) AT 500MM VERTICAL CENTRES
SHEAR WALL
FULL-FILL CAVITY INSULATION TO ALL CAVITY WALLS WITHIN HABITABLE AREAS, INCLUDING BIN STORES, PLANT ROOMS, STORE ROOMS.
75
NBS Ref: F10/372A - Category G4 200/100mm Blockwork to All Exterior Elevations & Internal Walls between Seismic Blocks.
ANGLE FHR HEAD RESTRAINT FIXED AT APPROX. 1500 CENTRES STAGGERED EACH SIDE OF WALL HEAD. FINISH HOT DIPPED GALVANISED.
200
11
ANCON WALL TIES (REF: CCB-TMJ-200) AT 500MM VERTICAL CENTRES
SHEAR WALL
DETAIL K Typical plan view of flexible joints at Intersecting Double Leaf Blockwork Wall section.
ROCKWOOL INTUMESCENT SEALANT TO EITHER SIDE
IMAGE ABOVE OF ANCON WALL TIES FOR THIN-JOINTED BLOCKWORK WALLS
Checked by:
RR
Original Sheet Size:
1330
A0
Approved by: Scale: 1 : 10
Drawing Number:
TP Sheet: of: Rev:
CTM - AR - BKN - C6 - L99 - 22 - 201
10M
THIS DRAWING MUST NOT BE SCALED.
0
© COPYRIGHT CHAPMAN TAYLOR 2015
ALL DIMENSIONS ARE TO BE VERIFIED AND CHECKED ON SITE. ANY DISCREPANCIES THAT ARE, OR BECOME APPARENT SHOULD BE REPORTED TO CHAPMAN TAYLOR.
A
B
C
D
E
F
G
H
I
J
K
L
M
N
AREAS INDICATED ARE APPROXIMATE GROSS INTERNAL AREA. THEY RELATE TO THE LIKELY AREAS OF THE BUILDING AT THE CURRENT STAGE OF DESIGN. ANY DECISIONS TO BE MADE ON THE BASIS OF THESE PREDICTIONS, WHETHER AS TO PROJECT VIABILITY, PRE-LETTING, LEASE AGREEMENTS, OR THE LIKE, SHOULD INCLUDE DUE ALLOWANCE FOR THE INCREASES AND DECREASES INHERENT IN THE DESIGN DEVELOPMENT AND BUILDING PROCESS.
ONCE PRINTED AND DISRIBUTED THIS DOCUMENT IS ASSUMED UNCONTROLLED © All rights reserved. No part of this drawing may be reproduced or transmitted in any forms and by any means without written permission of the copyright holder.
iui.org.uk
IFTIKHAR ISMAIL ~ REVIT PORT FOLIO