RENOVATIONS TO THE
WELCOME CENTER AND TENNIS CENTER
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
AT
BROOKDALE PARK
usaarchitects.com Paul R. Swartz, AIA Andrew P. Adornato, AIA Armand T. Christopher Jr., AIA Mitch Miller, AIA, FCSI, CCS Mark A. Coan, AIA Susan M. DeHart, AIA Peter C. Campisano, AIA
TOWNSHIPS OF BLOOMFIELD AND MONTCLAIR
DESIGN TEAM
STANDARD WARRANTY
01.03 ALL DIMENSIONS INDICATED ON THE CONSTRUCTION DOCUMENTS, OF EXISTING CONDITIONS, ARE APPROXIMATE AND SHALL BE FIELD VERIFIED BY THE CONTRACTOR(S) PRIOR TO SUBMITTING A BID.
DIVISION 02 DEMOLITION
01.04 THE CONTRACTOR(S) SHALL DISCUSS & VERIFY, WITH ALL GOVERNING AUTHORITIES ALL CODE REQUIREMENTS INDICATED AND/OR REQUIRED FOR THE COMPLETE EXECUTION OF THE WORK AS INTENDED BY THE CONSTRUCTION DOCUMENTS. 01.05 THE CONTRACTOR(S) SHALL COMPLY WITH ALL FEDERAL, STATE, AND LOCAL CODES AND ORDINANCES HAVING JURISDICTION OVER THE PROJECT. THE CONTRACTOR(S) SHALL OBTAIN PERMITS & GIVE NOTICES TO SUCH AGENCIES IN AMPLE TIME FOR OFFICIALS TO CONDUCT INSPECTIONS AND OBTAIN TIMELY APPROVALS. FAILURE TO COMPLY WILL SOLELY BE THE RESPONSIBILITY OF THE CONTRACTOR(S). 01.06 THE CONTRACTOR(S) SHALL PROVIDE PROTECTION FOR THE PUBLIC, OWNER'S STAFF, AND CONSTRUCTION WORKERS IN AND AROUND THE CONSTRUCTION AREA & ADJACENT PROPERTY. ADEQUATE BARRIERS & SIGNAGE SHALL BE PROVIDED TO EXERCISE CONTROL OF SAFE INGRESS & EGRESS OF PREMISES. FIRE EXITS SHALL NOT BE BLOCKED. PROPER SITE SECURITY DURING WORKING & OFF-HOURS SHALL BE MAINTAINED. BARRICADE ALL UNSAFE OR POTENTIALLY DANGEROUS CONDITIONS. THE CONTRACTOR(S) SHALL FOLLOW O.S.H.A. STANDARDS DURING THE COURSE OF THE PROJECT. 01.07 DO NOT SCALE THE DRAWINGS. USE CALCULATED DIMENSIONS ONLY. NOTE THAT NOT ALL DIMENSIONS ARE GIVEN ON THE CONSTRUCTION DOCUMENTS. SOME DIMENSIONS ARE IMPLIED. IF THE CONTRACTOR IS NOT SURE OF A GIVEN DIMENSION, HE/SHE SHALL SUBMIT A REQUEST FOR INFORMATION (R.F.I.) AND/OR SHALL FIELD VERIFY EXISTING DIMENSIONS. 01.08 ALL INFORMATION FOR ALL TRADES CONTAINED WITHIN THE CONSTRUCTION DOCUMENTS SHALL BE USED TOGETHER & IN CONCERT WITH ONE ANOTHER AS A WHOLE BODY OF INFORMATION FOR THE PROJECT. THE DRAWINGS & PROJECT MANUAL ARE COMPLEMENTARY & WHAT IS REQUIRED BY ONE, SHALL BE REQUIRED BY BOTH. NEITHER THE PRIME CONTRACTOR(S) NOR ANY SUBCONTRACTOR(S) SHALL BE RELIEVED OF THE RESPONSIBILITY TO PROVIDE ALL ITEMS REQUIRED BY THE INFORMATION & DESIGN INTENT INDICATED & IMPLIED. IN THE EVENT OF CONFLICTS BETWEEN DOCUMENTS, THE GREATER QUANTITY OR HIGHER QUALITY OF WORK SHALL PREVAIL AND BE PROVIDED. 01.09 ALL ITEMS LABELED "EXISTING" ARE EXISTING "TO REMAIN" UNLESS OTHERWISE INDICATED. ITEMS NOT LABELED "EXISTING" ARE TO BE PROVIDED. THE TERM "PROVIDE" SHALL MEAN FURNISH & INSTALL AS IT IS USED THROUGHOUT THE CONTRACT DOCUMENTS.
SUMMARY WORK
01.10 THE SCOPE OF THIS SINGLE OVERALL PRIME CONTRACT INCLUDES ALL THE WORK AS INDICATED ON THE DRAWINGS AND IN THE PROJECT MANUAL. THE SINGLE OVERALL PRIME CONTRACTOR BEARS SOLE SOURCE RESPONSIBILITY FOR THE DELIVERY OF THE PROJECT TO 100% COMPLETION.
PROJECT COORDINATION
01.11 THE SINGLE OVERALL PRIME CONTRACTOR BEARS SOLE SOURCE RESPONSIBILITY FOR THE COORDINATION OF THE ACTIVITIES OF ALL SUBCONTRACTORS, SUB-SUBCONTRACTORS, MATERIAL SUPPLIERS, AND ALL PARTIES INVOLVED IN THE EXECUTION OF THE PROJECT.
DIVISION 06 WOOD BLOCKING EXTERIOR WOOD DIVISION 07 SEALANTS
ROOFING
06.01 EVERY HOLLOW WALLBOARD PARTITION THAT IS INDICATED TO RECEIVE ANY ACCESSORIES SUCH AS, BUT NOT LIMITED TO, TOILET ACCESSORIES, HANDICAP RAILS, CABINETS, WALL MOUNTED BACK-BOARDS, ETC. SHALL BE PROVIDED WITH SOLID BLOCKING AND REINFORCEMENT WITHIN THE FRAMING TO ADEQUATELY SUPPORT THE INSTALLATION OF SUCH ITEMS. 06.02 ALL WOOD FRAMING LUMBER AND BLOCKING EXPOSED TO THE ELEMENTS OR USED IN CONTACT WITH MASONRY, CONCRETE, AND/OR ROOFING SHALL BE PRESSURE TREATED FOR RESISTANCE TO DETERIORATION FROM MOISTURE. 07.01 ANY AND ALL CONSTRUCTION JOINTS INCLUDING JOINTS BETWEEN DIFFERENT ITEMS AND MATERIALS, JOINTS SURROUNDING PENETRATIONS THROUGH MATERIALS, AND CRACKS WITHIN MATERIALS, ECT., WHETHER ON THE INTERIOR OR EXTERIOR OF THE BUILDING, SHALL BE FILLED WITH AN APPROPRIATE SEALANT AS REQUIRED. ON THE INTERIOR OF THE BUILDING, SAID SEALANT SHALL BE PAINTABLE. ON THE EXTERIOR OF THE BUILDING, SAID SEALANT SHALL BE WEATHERPROOF AND IN A COLOR SELECTED BY THE ARCHITECT. 07.02 PRIOR TO THE START OF ROOF WORK, THE CONTRACTOR IS REQUIRED TO CONDUCT A PRE-INSTALLATION CONFERENCE WITH THE ROOFING MANUFACTURER, THE ROOF INSTALLER, OTHER AFFECTED CONTRACTORS, AND THE ARCHITECT TO DISCUSS IN DETAIL THE INSTALLATION PROCESS. UPON COMPLETION, A WALK-THROUGH MEETING SHALL BE DONE WITH THE CONTRACT DOCUMENTS AND THE MANUFACTURER'S BEST PRACTICE RECOMMENDATIONS FOR THE WARRANTY SPECIFIED.
DIVISION 08 GLASS
08.01 THE PRIME CONTRACTOR SHALL SET A COORDINATION MEETING WITH THE GLASS SUPPLIER & THE ARCHITECT PRIOR TO FABRICATION & INSTALLATION OF GLAZING TO ASSURE THAT PROPER GLASS TYPE (SAFETY, FIRE RATED, WIRED, SPECIALTY, ETC.) IS PROVIDED IN CORRESPONDING LOCATIONS.
DIVISION 09
09.01 UNLESS FACTORY FINISHED, OR OTHERWISE SPECIFICALLY NOTED ON THE CONSTRUCTION DOCUMENTS, ALL EXPOSED SURFACES (BOTH INTERIOR & EXTERIOR OF THE BUILDING) SHALL BE PAINTED/COATED IN COLORS & TEXTURES AS SELECTED BY THE ARCHITECT/OWNER. NO SURFACES ARE TO BE LEFT UNFINISHED UNLESS SPECIFICALLY NOTED ON THE CONTRACT DOCUMENTS.
DIVISION 23 ROOF PENETRATIONS
23.02 ALL ROOF PENETRATIONS FOR MECHANICAL ITEMS (PIPES, DUCTS, CURBS, ETC.) SHALL BE FULLY COORDINATED BY THE GENERAL CONTRACTOR FOR EXACT LOCATION, SIZE, SUPPORT, ETC. FAILURE TO COORDINATE THESE ITEMS MAY RESULT IN CHANGES IN THE FIELD AT THE EXPENSE OF THE GENERAL CONTRACTOR.
DIVISION 26 ELECTRICAL
26.01 CONVENIENCE & DATA OUTLETS, WALL SWITCHES, AND FIXTURES SHALL BE COORDINATED WITH THE LOCATION OF FURNITURE, MILLWORK, CASEWORK, ETC. PRIOR TO INSTALLATION. FAILURE TO COORDINATE THESE ITEMS MAY RESULT IN CHANGES IN THE FIELD AT THE EXPENSE OF THE PRIME CONTRACTOR.
01.13 THE CONTRACTOR SHALL PROVIDE ALL MATERIAL, LABOR, SERVICES, ETC. TO COMPLETE THE ENTIRE WORK IN A MANNER ACCEPTABLE TO THE OWNER AND THE ARCHITECT. IT IS UNDERSTOOD THAT NOT EVERY DETAIL OR DIMENSION IS SHOWN IN THE CONTRACT DOCUMENTS, NOR ARE THEY NECESSARY FOR THE CONTRACTOR(S) TO PROVIDE A QUALITY PRODUCT. THE CONTRACTOR SHALL SUBMIT A REQUEST FOR INFORMATION (R.F.I.) IF NEEDED TO CLARIFY THE INTENT OF ANY DETAIL OR OTHER INFORMATION. HOWEVER, SUCH REQUEST FOR INFORMATION SHALL NOT CONSTITUTE A CHANGE IN THE SCHEDULE, OR IN THE CONTRACT AMOUNT. NO WORK SHOULD BE INSTALLED IF THE CONTRACTOR IS UNSURE OF THE DESIGN INTENT. INSTALLATION OF ANY WORK THAT DOES NOT COMPLY WITH THE DESIGN INTENT, AS DETERMINED BY THE ARCHITECT, SHALL BE SUBJECT TO REPLACEMENT AT THE CONTRACTOR'S EXPENSE.
PLUMBING - WELCOME CENTER
STRUNK-ALBERT ENGINEERING
MECHANICAL - WELCOME CENTER
804 SEVEN BRIDGES ROAD EAST STROUDSBURG, PA 18301 PHONE: 570.421.2025
M-100 M-101
OCCUPANCY TYPE XXX SF / OCC. SF 100 FT
1
ELECTRICAL - WELCOME CENTER
LANSCAPE ARCHITECT E-100 E-101 E-102
21
21 FT
SUBURBAN CONSULTING ENGINEERS, INC. 2430 HIGHWAY 34, BUILDING A WALL, NJ 08736 PHONE: 732-282-1776
ALTERNATE BID #1 ARCHITECTURAL - TENNIS CENTER A-200 A-201 A-202 A-203 A-204
ALTERNATE ALTERNATE ALTERNATE ALTERNATE ALTERNATE
BID #1 BID #1 BID #1 BID #1 BID #1
FD
- TENNIS CENTER FLOOR PLANS - TENNIS CENTER- EXTERIOR BUILDING ENVELOPE - TENNIS CENTER- EXTERIOR ELEVATIONS - TENNIS CENTER- EXTERIOR ELEVATIONS - TENNIS CENTER FINISH PLAN, ENLARGED TOILET PLANS & DOOR SCHEDULE
ALTERNATE BID #1 - TENNIS CENTER LANDSCAPE PLAN, NOTES AND DETAILS
P-200 P-201 P-202
ROOM + OCCUPANCY INFORMATION
ALTERNATE BID #1 - TENNIS CENTER GENERAL NOTES & SYMBOLS LIST ALTERNATE BID #1 - TENNIS CENTER FLOOR PLANS - PLUMBING ALTERNATE BID #1 - TENNIS CENTER DETAILS SCHEDULES
MECHANICAL - TENNIS CENTER M-200 M-201
DISTANCE TRAVELED (FEET) NUMBER OF OCCUPANTS EXITING
ALTERNATE BID #1 - TENNIS CENTER GENERAL NOTES & SYMBOLS LIST ALTERNATE BID #1 - TENNIS CENTER FLOOR PLANS - MECHANICAL
ELECTRICAL - TENNIS CENTER E-200 E-201 E-202
DIRECTION OF EGRESS TRAVEL
ALTERNATE BID #1 - TENNIS CENTER GENERAL NOTES & SYMBOLS LIST ALTERNATE BID #1 - TENNIS CENTER FLOOR PLANS - ELECTRICAL ALTERNATE BID #1 - TENNIS CENTER DETAILS & SCHEDULES
Signature & License No.
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
01.16 CONSTRUCTION ACCESS ROADS, CURB CUTS, SOIL EROSION CONTROL, & THE LOCATION OF ALL TEMPORARY FACILITIES (INCLUDING POWER, TELEPHONE, WATER, WASTE, ETC.) SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR (UNLESS OTHERWISE NOTED), & SHALL BE COORDINATED WITH UTILITY COMPANIES, MUNICIPAL AUTHORITIES, ETC. AS REQUIRED.
RENOVATIONS
01.17 ALL MATERIALS AND PRODUCTS SHALL BE PROTECTED AND PROPERLY STORED AS PER MANUFACTURER'S RECOMMENDATION. ALL MATERIALS AND PRODUCTS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S CURRENT PRINTED RECOMMENDATIONS TO MAINTAIN THE PROPER WARRANTIES.
TO THE
WOMEN'S TOILET
MEN'S TOILET FD
01.20 MISCELLANEOUS WOOD, COLD FORMED, OR ROLLED STEEL SHAPES, WHETHER BLOCKING OR SUB-FRAMING WHICH ARE REQUIRED FOR THE INSTALLATION OF OTHER ITEMS NECESSARY FOR A COMPLETE PACKAGE SHALL BE PROVIDED WHETHER OR NOT SPECIFICALLY INDICATED ON THE DRAWINGS.
1
CUSTODIAN CLOSET 02 STORAGE 46 SF / 300 SF
FD
1 10 FT VENDING MACHINE
45 FT
STORAGE 04 STORAGE 139 SF / 300 SF
35 FT
STORAGE OFFICE 03 BUSINESS 171 SF / 100 SF
VENDING MACHINE
VENDING MACHINE
VENDING MACHINE
16
LOCKER AREA 01 LOCKER ROOM 345 SF / 50 SF JAN. CLOSET 05 STORAGE 8 SF / 300 SF
WOMEN'S TOILET
AT ADA TOILET FD
BROOKDALE PARK 21 FT
WATCHUNG AVE. BLOOMFIELD, NJ 07003
1
ADA TOILET
38 FT
EXIT DOOR
EXIT DOOR
OCCUPANT CAPACITY: 160 DESIGN OCCUPANT LOAD: 20 FARTHEST DISTANCE TRAVELED: 45'
OCCUPANT CAPACITY: 160 DESIGN OCCUPANT LOAD: 1 FARTHEST DISTANCE TRAVELED: 10'
1
LOCATION MAP SCALE: N.T.S.
BUILDING CODE INFORMATION
01.25 DETAILS & SECTIONS ON THE DRAWINGS ARE SHOWN AT SPECIFIC LOCATIONS & ARE INTENDED TO SHOW GENERAL REQUIREMENTS THROUGHOUT. DETAILS NOTED "TYPICAL" IMPLY ALL "LIKE-CONDITIONS" ARE TO BE TREATED SIMILARLY.
2
WELCOME CENTER EGRESS PLAN SCALE: 1/8" = 1'-0"
3
ALTERNATE #1 TENNIS CENTER EGRESS PLAN SCALE: 1/8" = 1'-0"
NEW JERSEY ADMINISTRATIVE CODES APPLICABLE CONSTRUCTION CODES N.J.A.C. 5:23 N.J.A.C. 5:70 N.J.A.C. 5:23-3.14 N.J.A.C. 5:23-3.15 N.J.A.C. 5:23-3.16 N.J.A.C. 5:23-3.17 N.J.A.C. 5:23-3.18 N.J.A.C. 5:23-20 N.J.A.C. 5:23-6 N.J.A.C. 5:23-7
01.27 MINOR DETAILS OR INCIDENTAL ITEMS NOT USUALLY SHOWN OR SPECIFIED, BUT NECESSARY FOR THE PROPER & COMPLETE EXECUTION OF ANY PART OF THE WORK SHALL BE INCLUDED AS IF THEY WERE SPECIFICALLY INDICATED IN THE CONSTRUCTION DOCUMENTS. 01.28 UNLESS OTHERWISE INDICATED: CUTTING AND PATCHING (EXCEPT FOR FINISHES) IS TO BE PERFORMED BY THE PRIME CONTRACTOR REQUIRING CUTTING AND PATCHING, WHETHER AS SELECTIVE DEMOLITION, OR AS A MEANS OF ACCESSING OR CORRECTING UNSATISFACTORY WORK. PATCHING OF THE SUBSTRATE IS ALSO THE WORK OF THAT PRIME CONTRACTOR, HOWEVER THE PATCHING OF ALL FINISHES EXPOSED TO VIEW IS TO BE DONE BY THE GENERAL CONTRACTOR USING SKILLED TRADESMAN TRAINED FOR PATCHING THE PARTICULAR FINISH INVOLVED. 01.29 THE PROJECT HAS BEEN DESIGNED TO MEET A CERTAIN PROFESSIONAL STANDARD AND PRODUCTS HAVE BEEN SELECTED TO MEET SUCH STANDARDS. THE PRODUCTS SPECIFIED ARE THE PRODUCTS INTENDED TO BE USED. IN THE EVENT THAT SUBSTITUTIONS ARE SUBMITTED FOR REVIEW, A PROPER COMPARATIVE INFORMATION SHEET SHALL ALSO BE SUBMITTED. ALL REQUESTS FOR SUBSTITUTION SHALL BE MADE WITHIN THE FIRST 90 DAYS AFTER THE CONTRACTOR HAS BEEN AWARDED THE CONTRACT FOR CONSTRUCTION. NO SUBSTITUTION WILL BE CONSIDERED AFTER THIS PERIOD.
01.31 THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS SUFFICIENTLY IN ADVANCE OF THE WORK TO ALLOW PROPER TIME FOR REVIEW. MATERIALS SHALL NOT BE FABRICATED OR DELIVERED TO THE SITE BEFORE THE SHOP DRAWINGS HAVE BEEN APPROVED.
TOWNSHIPS OF BLOOMFIELD AND MONTCLAIR
WELCOME CENTER
MEN'S TOILET FD
2
BROOKDALE PARK
01.24 ANY/ALL EQUIPMENT PROVIDED SHALL BE INSTALLED TO BE COMPLETELY FUNCTIONAL. EACH PIECE OF EQUIPMENT PROVIDED BY A PRIME CONTRACTOR, REQUIRING SERVICE CONNECTIONS BY ANOTHER PRIME CONTRACTOR SHALL BE COORDINATED BY THE GENERAL CONTRACTOR. STARTUP & TESTING OF EQUIPMENT SHALL BE PERFORMED & DOCUMENTED BY FACTORY AUTHORIZED PERSONNEL.
01.30 THE PRIME CONTRACTOR SHALL PROVIDE ALL REQUIRED SCHEDULES, SUCH AS BUT NO LIMITED TO: SUBMISSION SCHEDULE, CONSTRUCTION SCHEDULE, & SCHEDULE OF VALUES PRIOR TO SUBMISSION OF THE FIRST APPLICATION FOR PAYMENT. NO APPLICATION FOR PAYMENT WILL BE APPROVED BY THE ARCHITECT UNTIL THIS PREREQUISITE IS COMPLIED WITH PROPERLY.
WELCOME CENTER AND TENNIS CENTER
TENNIS CENTER
FD
01.23 EACH PRIME CONTRACTOR SHALL FIRE STOP/SMOKE PROOF ANY/ALL PENETRATIONS AS REQUIRED TO MAINTAIN THE DESIGNATED FIRE RATING/SMOKE PROOFING OF THE CONSTRUCTION WHETHER EXISTING OR NEW. THE GENERAL CONTRACTOR SHALL ALSO EXTEND RATED CONSTRUCTION TO MAINTAIN CONTINUITY OF SAME THROUGH CONCEALED SPACES (VERTICAL & HORIZONTAL) AS REQUIRED.
01.26 WORK NOT INDICATED IN PART OF THE DRAWING, BUT REASONABLY IMPLIED TO BE SIMILAR TO THAT SHOWN AT CORRESPONDING PLACES SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST.
AI16116
NON-SIMULTANEOUS USE
FD
01.22 EACH PRIME CONTRACTOR SHALL PROVIDE ALL NECESSARY SHORING & BRACING TO SUPPORT EXISTING OR NEW CONSTRUCTION NOT FULLY SET UNTIL PERMANENT SUPPORTS ARE ERECTED. TAKE ALL NECESSARY MEASURES TO PREVENT COLLAPSE OF ANY ELEMENT OF NEW OR EXISTING CONSTRUCTION.
2/27/2018 11:13:34 AM
WELCOME CENTER GENERAL NOTES & SYMBOLS LIST WELCOME CENTER FLOOR PLANS - ELECTRICAL WELCOME CENTER DETAILS AND SCHEDULES
PATH OF EGRESS TRAVEL
01.21 DIMENSIONS GIVEN FOR MASONRY OPENINGS ARE NOMINAL. GENERAL CONTRACTOR(S) SHALL COORDINATE THE FABRICATION OF DOOR, WINDOW, AND VISION PANEL FRAMES AND OTHER ITEMS TO BE INSTALLED IN MASONRY TO ACCOMMODATE ACTUAL DIMENSIONS VERIFIED IN THE FIELD WITH AND WITHOUT MORTAR JOINTS AS THEY OCCUR.
SUBMITTALS AND SUBSTITUTIONS
WELCOME CENTER GENERAL NOTES AND SYMBOLS LIST WELCOME CENTER FLOOR PLANS - MECHANICAL
PLUMBING - TENNIS CENTER
NUMBER
MECHANICAL ROOM 07 STORAGE 117 SF / 300 SF
01.19 LONG LEAD ITEMS SHALL BE IDENTIFIED BY THE CONTRACTOR(S) WITH NOTIFICATION TO THE ARCHITECT IN A TIMELY MANNER. FAILURE BY THE CONTRACTOR(S) TO OBTAIN SUBMITTAL APPROVALS, AND TO ORDER LONG LEAD ITEMS, SO AS NOT THE DELAY THE PROGRESS OF THE WORK, WILL NOT JUSTIFY AN EXTENSION OF THE SCHEDULE FOR COMPLETION, NOR WILL IT CAUSE PRODUCT SUBSTITUTIONS IN ORDER TO MEET THE SCHEDULE.
CUTTING AND PATCHING
WELCOME CENTER GENERAL NOTES AND SYMBOLS LIST WELCOME CENTER FLOOR PLANS - PLUMBING WELCOME CENTER DETAILS AND SCHEDULES
P-100 P-101 P-102
LEGEND
3
WELCOME CENTER LANDSCAPE PLAN, NOTES AND DETAILS
LS-200
28 FT
01.18 PRIOR TO THE INSTALLATION OF ALL MAJOR BUILDING COMPONENTS, THE PRIME CONTRACTOR(S) SHALL CONDUCT A PREINSTALLATION AND COORDINATION MEETING WITH THE MANUFACTURER'S REPRESENTATIVE. INCLUDED IN THE MEETING SHALL BE ANY SUBCONTRACTOR AND PRODUCT MANUFACTURER AFFECTED BY THE SPECIFIC WORK. FAILURE OF THE PRIME CONTRACTOR(S) TO CONDUCT SUCH A MEETING, AND PROPERLY COORDINATE THE PROCESS, SHALL PLACE THE BURDEN FOR ANY & ALL PROBLEMS, RESULTING FROM SAID INSTALLATION, UPON THE PRIME CONTRACTOR(S) RESPONSIBLE FOR THAT PORTION OF THE WORK.
EXECUTION REQUIREMENTS
LS-100
ROOM NAME
01.15 ALL UNUSED MATERIAL AND DEBRIS SHALL BE COMPLETELY REMOVED FROM THE SITE AND LEGALLY DISPOSED OF. NO ON-SITE STORAGE, BURNING, OR BURIAL OF DEBRIS SHALL BE PERMITTED. THE CONSTRUCTION SITE SHALL BE KEPT IN A CLEAN AND SAFE MANNER, INCLUDING, BUT NOT LIMITED TO DAILY BROOM CLEANING THROUGHOUT THE DURATION OF THE CONSTRUCTION PROJECT.
PRODUCT REQUIREMENTS
LANDSCAPE - WELCOME CENTER
LANDSCAPE - TENNIS CENTER
ELECT. CLOSET
WELCOME CENTER 05 BUSINESS 232 SF / 100 SF
CENTER FLOOR PLANS CENTER BUILDING ENVELOPE CENTER EXTERIOR ELEVATIONS CENTER EXTERIOR ELEVATIONS CENTER FINISH PLAN, TOILET PLANS & DOOR SCHEDULE CENTER PLAZA PLANS AND DETAILS
MEP
OCCUPANT CAPACITY: 320 DESIGN OCCUPANT LOAD: 4 FARTHEST DISTANCE TRAVELED: 28'
01.14 ALL CONSTRUCTION, EQUIPMENT, CONTENTS, ETC. SHALL BE PROTECTED BY EACH CONTRACTOR DURING THE ENTIRE PERFORMANCE OF THE WORK. AREAS DISTURBED OR DAMAGED BY THE CONTRACTOR SHALL BE COMPLETELY RESTORED, REPAIRED, OR REPLACED BY THE CONTRACTOR. TO THE OWNER'S COMPLETE SATISFACTION AT NO ADDITIONAL COST.
TEMPORARY FACILITIES & ACCESS
20 NORTH DOUGHTY AVE SOMERVILLE, NJ 08876 PHONE: 908-722-2300
EXIT DOOR
01.12 ENGINEERING DRAWINGS (STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION, COMMUNICATIONS, AND SECURITY SYSTEM DRAWINGS, ETC.) ARE SHOWN DIAGRAMMATICALLY AND ARE NOT TO SCALE, NOR DO THEY SHOW THE EXACT LOCATION OF THEIR COMPONENTS. THE EXACT LOCATION AND CLEARANCES FOR EACH SUCH SYSTEM OF COMPONENTS SHALL BE COORDINATED BY THE CONTRACTOR(S). ALL PRIME CONTRACTORS, PRIOR TO PURCHASE, FABRICATION, OR INSTALLATION OF THESE ITEMS SHALL PREPARE COORDINATION DRAWINGS SHOWING THE DIFFERENT TRADES BY COLORS AND SHALL CONDUCT A COORDINATION MEETING WITH ALL OTHER CONTRACTOR(S) AFFECTED FOR A TOTAL UNDERSTANDING OF THE DESIGN INTENT. THE ARCHITECTS AND THE ENGINEERS(S) SHALL BE INVITED TO ATTEND THIS MEETING AND OFFER INPUT PRIOR TO ANY WORK BEING FABRICATED OR INSTALLED. QUALITY REQUIREMENTS
USA ARCHITECTS PLANNERS + INTERIOR DESIGNERS, P.A.
WELCOME WELCOME WELCOME WELCOME WELCOME WELCOME
DATE
01.02 THE INDICATION OF SUBSTRATE & CONFIGURATION OF CONCEALED ITEMS & MATERIALS SHOWN ON THE CONSTRUCTION DOCUMENTS IS FOR GENERAL REFERENCE ONLY. THE CONTRACTOR(S) SHALL NOT BE ENTITLED TO ADDITIONAL COMPENSATION FOR ANY VARIANCE BETWEEN ACTUAL EXISTING CONDITIONS AND THAT REPRESENTED ON THE CONSTRUCTION DOCUMENTS.
01.35 IF SUBSTITUTIONS ARE APPROVED, THE CONTRACTOR SHALL NOTIFY ALL OTHER TRADES AFFECTED BY THE SUBSTITUTION & FULLY COORDINATE THE IMPACT ON THE PROJECT. ANY ADDITIONAL COST RESULTING FROM SUBSTITUTIONS SHALL BE PAID BY THE CONTRACTOR PROPOSING THE SUBSTITUTION. 01.36 EACH PRIME CONTRACTOR SHALL PROVIDE, AS PART OF ITS REQUIRED CLOSE-OUT DOCUMENTS, A STANDARD WARRANTY COVERING ALL MATERIALS, PRODUCTS, AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE ARCHITECT. THIS STANDARD WARRANTY IS A BASIC REQUIREMENT OF EACH PRIME CONTRACT AND SHALL BE EXTENDED BY SPECIFIC WARRANTY REQUIREMENTS OF THE VARIOUS PRODUCTS AND SYSTEMS AS INDICATED THROUGHOUT THE CONTRACT DOCUMENTS. 02.01 THE ACTUAL SCOPE OF DEMOLITION SHALL NOT BE LIMITED TO WHAT IS SPECIFICALLY INDICATED ON THE DRAWINGS OR WITHIN THE PROJECT MANUAL, BUT SHALL INCLUDE ANY AND ALL COMPLETE OR SELECTIVE DEMOLITION AS MAY BE NECESSARY TO ACCOMPLISH THE INTENDED CONSTRUCTION. THIS APPLIES TO THE WORK OF ALL TRADES.
A-100 A-101 A-102 A-103 A-104 A-105
COUNTY ENGINEER J.J.P.E. LICENSE No. 40597
GENERAL REQUIREMENTS
01.01 ANY ADDITIONAL INFORMATION THAT IS NOT PART OF THE CONSTRUCTION DOCUMENTS, SUCH AS, BUT NOT LIMITED TO, SOIL REPORT(S), HAZARDOUS MATERIALS REPORT(S), EXISTING DRAWINGS, ETC., ARE INTENDED FOR REFERENCE ONLY AND ARE TO BE USED BY THE CONTRACTOR(S) AT HIS/HER OWN DISCRETION.
BASE BID ARCHITECTURAL - WELCOME CENTER
SANJEEV VARGHESE, PE
DIVISION 01 AVAILABLE INFORMATION
BROOKDALE PARK TITLE SHEET, EGRESS PLANS & CODE INFORMATION
APPROVED BY:
00.03 THE BIDDER/CONTRACTOR IS REQUIRED TO VISIT THE SITE & EXAMINE THE EXISTING CONDITIONS TO HIS COMPLETE SATISFACTION PRIOR TO BIDDING. THE BIDDER/CONTRACTOR SHALL COMPARE THE EXISTING CONDITIONS TO THE DESIGN INTENT OF THE CONTRACT DOCUMENTS & SHALL IMMEDIATELY NOTIFY THE ARCHITECT IN WRITING OF ANY/ALL DISCREPANCIES BEFORE SUBMITTING A BID. FAILURE TO DO SO WILL PLACE THE BURDEN OF RESPONSIBILITY ON THE CONTRACTOR TO PERFORM THE WORK AS INTENDED BY THE CONTRACT DOCUMENTS, AT NO ADDITIONAL COST TO THE OWNER.
A-001
DATE
00.02 PRODUCT MANUFACTURERS IN CONJUNCTION WITH SUBCONTRACTORS AND PRIME CONTRACTOR(S) ARE RESPONSIBLE FOR ALL COMPONENTS AND CALCULATIONS AND/OR CERTIFICATIONS OF THEIR PRODUCT AND FOR PROVIDING COMPLETE SYSTEMS/ASSEMBLIES TO MEET THE DESIGN INTENT OF THE PROJECT.
ARCHITECT
COUNTY EXECUTIVE
01.32 SHOP DRAWINGS SHALL BE REVIEWED BY THE ARCHITECT/ENGINEER FOR BASIC CONFORMANCE TO THE DESIGN INTENT ONLY AFTER PRIOR APPROVAL BY THE RESPONSIBLE PRIME CONTRACTOR. THIS REVIEW DOES NOT RELIEVE THE CONTRACTOR OR HIS SUB-CONTRACTOR(S) OF RESPONSIBILITY FOR FULL COMPLIANCE WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DIMENSIONS & CLEARANCES TO BE CONFIRMED & CORRELATED AT THE JOB SITE, FOR MATERIALS QUANTITIES & PROPER FABRICATION, FOR PROPER MEANS & METHODS, FOR PROPER SEQUENCES OF CONSTRUCTION, FOR THE PROPER COORDINATION WITH OTHER TRADES, AND FOR PROVIDING SAFE AND SATISFACTORY CONSTRUCTION OPERATIONS. 01.33 EACH CONTRACTOR IS ADVISED THAT CERTAIN COLOR SCHEDULE SELECTIONS MAY HAVE PREVIOUSLY BEEN MADE, REVIEWED, AND APPROVED BY THE OWNER & RETURNED TO THE CONTRACTOR FOR EXECUTION. ALL CONTRACTORS SHALL TAKE NOTE & HEREAFTER STRONGLY BE ADVISED THAT MATERIAL SUBSTITUTIONS SUBMITTED LATER MAY BE REQUIRED TO BE PROVIDED WITH CUSTOM COLORS, TEXTURES, & FINISHES BASED UPON SELECTIONS PREVIOUSLY APPROVED. MATERIAL SUBSTITUTIONS ARE SUBJECT TO REJECTION SOLELY ON APPEARANCE. 01.34 THE ARCHITECT WILL TAKE APPROPRIATE ACTION UP TO THREE (3) TIMES FOR EACH ITEM SUBMITTED. SUBMITTALS REQUIRING MORE THAN THREE (3) REVIEWS DUE TO INCORRECT OR INCOMPLETE INFORMATION SHALL BE SUBJECT TO A REVIEW FEE FOR EACH SUBSEQUENT SUBMITTAL. THIS FEE SHALL BE AT THE HOURLY RATE OF THE ARCHITECT & ENGINEER, AND SHALL BE PRE-PAID TO THE ARCHITECT BY THE CONTRACTOR PRIOR TO ANY ADDITIONAL CONSIDERATION. FEES PAID SHALL IN NO WAY CONSTITUTE AN OBLIGATION BY THE ARCHITECT TO APPROVE ANY SUBMITTAL THAT IN HIS/HER OPINION DOES NOT COMPLY WITH THE DESIGN INTENT OF THE CONTRACT DOCUMENTS. FURTHERMORE, ANY SUCH ADDITIONAL REVIEW TIME SHALL NOT BE A BASIS FOR AN EXTENSION OF TIME.
JOSEPH DIVINCENZO
00.01 ALL BIDDERS, UPON SUBMITTING BIDS, HEREBY CERTIFY THAT THEY HAVE REVIEWED THE ENTIRE SET OF CONTRACT DOCUMENTS, (CONTRACT DOCUMENTS CONSIST OF A COMPLETE SET OF DRAWINGS AND THE ENTIRE PROJECT MANUAL, INCLUDING ALL DIVISIONS & ANY/ALL ADDENDA) AND ARE AWARE OF, AND AGREE TO MEET THE INTENT OF THE CONTRACT DOCUMENTS WHETHER EXPRESSED OR IMPLIED.
APPROVED BY:
DIVISION 00 PROCUREMENT
DRAWING LIST
APPROVAL SIGNATURES
CSI DIVISION
UNIFORM CONSTRUCTION CODE (UCC) UNIFORM FIRE CODE (UFC) AND THE STATE FIRE PREVENTION CODE BUILDING SUBCODE (IBC/2015) PLUMBING SUBCODE (NSPC/2015) ELECTRICAL SUBCODE (NEC/2014) FIRE PROTECTION SUBCODE (SPECIFIC PORTIONS OF THE IBC, NEC, IMC, IFGC) ENERGY SUBCODE (IECC/2015) MECHANICAL SUBCODE (IMC/2015) REHABILITATION SUBCODE BARRIER FREE CODE
NJ UNIFORM CONSTRUCTION CODE 5:23-6.3 DEFINITIONS THIS PROJECT IS A "RENOVATION" AND "REPAIR"
PROGRESS SUBMISSION 02.16.18 NOT FOR CONSTRUCTION
5:23-6.3 RENOVATIONS THE REMOVAL AND REPLACEMENT OR COVERING OF EXISTING INTERIOR OR EXTERIOR FINISH, TRIM, DOORS, WINDOWS, OR OTHER MATERIALS WITH NEW MATERIALS THAT SERVE THE SAME PURPOSE AND DO NOT CHANGE THE CONFIGURATION OF SPACE. RENOVATION SHALL INCLUDE THE REPLACEMENT OF EQUIPMENT OR FIXTURES. 5:23-6.3 REPAIR THE RESTORATION TO A GOOD OR SOUND CONDITION OF MATERIALS, SYSTEMS AND/OR COMPONENTS THAT ARE WORN, DETERIORATED OR BROKEN USING MATERIALS OR COMPONENTS IDENTICAL TO OR CLOSELY SIMILAR TO THE EXISTING.
No.
Date
Issue or Revision
Drawing Title
BROOKDALE PARK TITLE SHEET, EGRESS PLANS & CODE INFORMATION
Scale
USA Project No.
As indicated Drawing Date
2017-100 Drawing No.
02.15.18 Drawn By
Checked By
JS
ApA
A-001
VENDING MACHINE
BENCH
VENDING MACHINE
16
12 1
13
EXISTING ELECT. BREAKERS TO REMAIN
VENDING MACHINE
WOMEN'S TOILET
STORAGE EXISTING ELECT. PANEL TO REMAIN
VENDING MACHINE
2
13 1
7
FD
6
11
FD
6
11
LOCKER AREA 01
5 14 11
11
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
NEW 2-TIER LOCKERS. REFER TO DWG. 4/A-204
STORAGE 04
WOMEN'S TOILET 06
ADA TOILET
usaarchitects.com
4
STORAGE 1
STORAGE 02
11
JAN. CLOSET 05
3
5
JAN. CLOSET OFFICE
LOCKER AREA
11
1
6
11
MEN'S TOILET
1 1
OFFICE 03
1 A-204
7
2
8
8
MEN'S TOILET 07
Andrew P. Adornato, AIA Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA Mark A. Coan, AIA Peter C. Campisano, AIA
ADA TOILET
2 1
7 6
FD
FD
17 9
17
1
15 BENCH
ALTERNATE #1 - TENNIS CENTER DEMOLITION PLAN
3
SCALE: 1/4" = 1'-0"
ALTERNATE #1 - TENNIS CENTER FLOOR PLAN SCALE: 1/4" = 1'-0"
STORAGE
LOCKER AREA 01
4 3
5
STORAGE 04
WOMEN'S TOILET LOCKER AREA
18
WS-1 HEIGHT VARIES
4 3
SLOPE UP
1
WOMEN'S TOILET 06
V.I.F.
5
4 3
5
APC-2 ±8'-3" A.F.F. V.I.F.
10
CEILING RIDGE
STORAGE
STORAGE 02
JAN. CLOSET
MEN'S TOILET
3
5 16
16
APC-1 ±8'-3" A.F.F. V.I.F.
4 3
PT-2 ±8'-3" A.F.F. V.I.F.
5
MEN'S TOILET 07
SLOPE UP
4
PT-2 ±8'-3" A.F.F. V.I.F.
OFFICE 03
OFFICE
JAN. CLOSET 05
APC-2 ±8'-3" A.F.F. V.I.F.
Signature & License No.
2
ALTERNATE #1 - TENNIS CENTER DEMOLITION CEILING PLAN
4
SCALE: 1/4" = 1'-0"
AI16116
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
ALTERNATE #1 - TENNIS CENTER CEILING PLAN SCALE: 1/4" = 1'-0"
RENOVATIONS TO THE
WELCOME CENTER AND TENNIS CENTER AT
BROOKDALE PARK TOWNSHIPS OF BLOOMFIELD AND MONTCLAIR
DEMOLITION KEY:
SELECTIVE ALTERNATE # 1 DEMOLITION LEGEND: EXISTING TO REMAIN
X
DEMOLITION SCOPE OF WORK ITEM TYPICAL THROUGHOUT ENTIRE ROOM / AREA
X
DEMOLITION SCOPE OF WORK ITEM AT A SPECIFIC LOCATION
1
REMOVE EXISTING FLOOR SYSTEM(S) IN THEIR ENTIRETY TO SUBSTRATE. PATCH AND REPAIR ADJACENT SURFACES TO RECEIVE NEW FINISHES.
12
REMOVE AND REPLACE EXISTING LOCKERS IN THEIR ENTIRETY IN SAME LOCATION. REFER TO DETAIL 4/A-204 FOR MORE INFORMATION.
2
REMOVE EXISTING CERAMIC WALL TILE IN ITS ENTIRETY TO SUBSTRATE. PATCH AND REPAIR ADJACENT SURFACES TO RECEIVE NEW FINISHES.
13
REMOVE AND STORE EXISTING VENDING MACHINE FOR REINSTALLATION.
3
REMOVE EXISTING CEILING SYSTEM(S) IN THEIR ENTIRETY. PATCH AND REPAIR ADJACENT SURFACES TO RECEIVE FINISHES.
14
REMOVE AND STORE EXISTING METAL BENCH AND ITS ACCESSORIES DURING DEMOLITION. REMOVE EXISTING BENCH FINISH AND PREPARE TO RECEIVE NEW FINISH.
4
REMOVE ALL LIGHTING FIXTURES AND ITS ACCESSORIES IN THEIR ENTIRETY. REFER TO M.E.P. DRAWINGS FOR MORE INFORMATION.
15
REMOVE EXISTING STOREFRONT SYSTEM, INCLUDING, BUT NOT LIMITED TO, DOOR, FRAME, GLAZING AND THEIR ACCESSORIES IN THEIR ENTIRETY. PATCH AND REPAIR ADJACENT SURFACES TO RECEIVE NEW DOOR SYSTEM.
5
REMOVE EXISTING PACKAGED THRU-WALL AIR CONDITIONER AND ALL ITS COMPONENTS IN THEIR ENTIRETY. PATCH WALL TO MATCH ADJACENT WALL CONSTRUCTION AND FINISHES. REFER TO M.E.P. DRAWINGS FOR MORE INFORMATION.
16
SCRAPE AND PAINT EXISTING WOOD BEAMS. REFER TO FINISH PLAN FOR MORE INFORMATION.
17
6
REMOVE AND DISCONNECT EXISTING PLUMBING FIXTURES AND COMPONENTS IN THEIR ENTIRETY. TEMPORARILY CAP ALL PIPING AS NECCESARY FOR NEW CONSTRUCTION. SAW CUT FLOOR AND/OR WALL TO ACCESS PIPING AS REQUIRED. PATCH AND REPAIR SURFACES TO MATCH ADJACENT FINISHES. REFER TO M.E.P. DRAWINGS FOR MORE INFORMATION.
REMOVE AND STORE EXISTING WOOD WINDOW SHUTTERS FOR REINSTALLATION. REMOVE EXISTING FINISH AND PREPARE TO RECEIVE NEW FINSH. REFER TO FINISH SCHEDULE FOR MORE INFORMATION.
TO BE REMOVED
GENERAL DEMOLITION NOTES: 1. CONTRACTOR MUST INSTALL AND MAINTAIN PLASTIC DUST BARRIERS DURING DEMOLITION AND CONSTRUCTION TO PROTECT THE GENERAL PUBLIC FROM DUST AND FUMES. LOCATE PARTITIONS REQUIRED TO PROTECT ADJACENT AREAS AND EQUIPMENT, AND CONTINUE EGRESS THROUGH THE SPACE. CONTRACTOR SHALL PROVIDE TEMPORARY EXIT WAYS AS REQUIRED BY LOCAL CODE ENFORCEMENT OFFICIAL DURING CONSTRUCTION. 2. DO NOT CONSIDER DEMOLITION AND ALTERATION NOTES TO BE ALL INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND ASSESS EACH SPACE AND TO FULFILL THE INTENT OF THE WORK INDICATED BY THE CONTRACT DOCUMENTS. VERIFY ALL DIMENSIONS WITHIN THE CONTRACT LIMITS. BRING DEVIATIONS FROM THE CONTRACT DOCUMENTS TO THE ATTENTION OF THE ARCHITECT. THE EXTENT OF DEMOLITION AND REMOVAL INCLUDES, BUT IS NOT LIMITED TO WORK SHOWN ON THE DRAWINGS. COORDINATE W/ MECHANICAL, ELECTRICAL, PLUMBING & STRUCTURAL DRAWINGS.
3/1/2018 2:41:34 PM
3. REMOVE ANY MISCELLANEOUS PROJECTIONS, HANGERS, BOLTS, SCREWS AND NAILS FROM EXISTING SURFACES TO REMAIN. PATCH AND PREPARE SURFACES TO RECEIVE NEW FINISH.
CEILING LEGEND
18
REMOVE EXISTING ELECTRIC HEATING AIR HANDLING UNIT, ITS COMPONENTS AND ACCESSORIES IN THEIR ENTIRETY. PATCH AND REPAIR WALL TO MATCH ADJACENT CONSTRUCTION AND FINISHES. REFER TO M.E.P. DRAWINGS FOR MORE INFORMATION.
APC-1/2 2' x 4' APC
PT-3 GYPSUM BOARD CEILING SYSTEM
2' x 4' LIGHT FIXTURE
PENDANT LIGHT FIXTURE
1
03.06.18
No.
Date
BID SET Issue or Revision
Drawing Title
7
REMOVE EXISTING TOILET ACCESSORIES INCLUDING, BUT NOT LIMITED TO, TOILET PARTITIONS, BENCHES, SOAP DISPENSERS, PAPER TOWEL DISPENSERS, GRAB BARS, MIRRORS, ETC. PATCH AND REPAIR ADJACENT SURFACES TO RECEIVE NEW FINISHES.
4. PATCH AND REPAIR ALL ADJACENT SURFACES WHICH ARE AFFECTED BY THE DEMOLITION OR REMOVAL OF ACCESSORIES TO THEIR ORIGINAL FORM AND PREPARE FOR NEW FINISH. COORDINATE WITH FINISH DRAWINGS.
8
REMOVE AND REPLACE ANY AND ALL DAMAGED, CRACKED, ROATTING OR MISSING WOOD MOLDING THROUGHOUT SPACE. PATCH AND REPAIR TO MATCH ADJACENT SURFACES.
5. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR DAILY CLEANUP OF CONSTRUCTION DEBRIS.
9
REMOVE EXISTING WALL HEATER AND COMPONENTS IN THEIR ENTIRETY. PATCH AND REPAIR ADJACENT SURFACES TO RECEIVE NEW FINISHES. REFER TO M.E.P. DRAWINGS FOR MORE INFORMATION.
6. BEFORE DEMOLITION BEGINS, CONTRACTOR SHALL COORDINATE SEQUENCE AND SCHEDULES FOR ALL WORK AND RELOCATION OR DISPOSAL OF ALL MATERIALS WITH OWNER.
10
SAND AND PREPARE EXISTING WOOD CEILING TO RECEIVE WOOD STAIN.
As indicated
11
REMOVE EXISTING DOOR, HARDWARE AND ACCESSORIES IN THEIR ENTIRETY. PREPARE FRAME FOR NEW FINISH AND INSTALLATION OF NEW DOOR. REFER TO DOOR SCHEDULE FOR MORE INFORMATION.
Drawing Date
ALTERNATE BID #1 - TENNIS CENTER FLOOR PLANS
Scale
7. DEMOLITION PLANS ARE DIAGRAMMATIC. PRIOR TO SUBMITTING BID, GENERAL CONTRACTORS SHALL FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND BRING ANY AREAS IN QUESTION TO THE ATTENTION OF THE ARCHITECT.
USA Project No.
2017-100 Drawing No.
03.06.18 Drawn By
Checked By
JS/JLG
ApA
A-200
ALTERNATE BID #1 - TENNIS BUILDING DOOR SCHEDULE
LKR-1 04 PT-1
APC-1
APC-2 FD
6
TD GB 5'-0"
TD
SD
BPT-1
5
NDU
CLEAR
NDU M
CT-1
4
GB
JAN. CLOSET
JAN. CLOSET 3
STORAGE
MEN'S TOILET 07
GB 3' - 0" FD
EP-1
WB-1
PT-1
PT-1
PT-1
PT-1 8
EP-1
WB-1
PT-1
APC-1
PT-2
WS-1 WOOD CEILING PT-1
7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0"
1 E.T.R. E.T.R. E.T.R. E.T.R. E.T.R. E.T.R. E.T.R.
AL E.T.R. E.T.R. E.T.R. E.T.R. E.T.R. E.T.R. E.T.R.
07 08 09 10 11 12 09 12
ADA ACCESSIBLE DUTCH DOOR VERIFY ALL SIZES IN FIELD VERIFY ALL SIZES IN FIELD VERIFY ALL SIZES IN FIELD VERIFY ALL SIZES IN FIELD VERIFY ALL SIZES IN FIELD VERIFY ALL SIZES IN FIELD
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
DOOR WIDTH
EP-1
CTB-1
CT-4
APC-2
FD
1
2" 3'-0"
usaarchitects.com
2" 11"
Andrew P. Adornato, AIA Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA Mark A. Coan, AIA Peter C. Campisano, AIA
DOOR WIDTH
07
WOOD BEAMS
2"
1" TEMPERED INSULATED GLAZING
1" TEMPERED INSULATED GLAZING (TYP.)
6"
BC
DOOR WIDTH
MEN'S TOILET
WB-1
3'-0" 3'-0" 2'-0" 3'-0" 3'-0" 3'-0" 2'-0" 3'-0"
2" 11"
01
EP-1
AL SWC SWC SWC SWC SWC SWC SWC
5'-6"
5' - 0"
ø
B
1"
1' - 6"
2
PT-2
3' - 10"
5'0"
HD
5' - 0"
03
WB-1
C B A A A A A A
2" 2"
5'-0"
TD
CLEAR
GB SD
LOCKER AREA
EP-1
LOCKER AREA OFFICE STORAGE CLOSET STORAGE ROOM STORAGE ROOM WOMEN'S TOILET JANITOR'S CLOSET MEN'S TOILET
DOOR HEIGHT
02
OFFICE
M
7
05
1 2 3 4 5 6 7 8
7'-0"
WB-1
CTB-1
COMMENTS
8"
FD
EP-1
EP-1
HEIGHT
HARDWARE SET
3'-8"
1' - 6"
ROOM NAME
FRAME ELEVATION MATERIAL
2'-8"
5' - 0"
06
STORAGE
DOOR ELEVATION MATERIAL WIDTH
DOOR NUMBER
2"
4' - 0"
WOMEN'S TOILET
8'-0"
1' - 11"
VENDING MACHINE
DOOR HEIGHT
HD
VENDING MACHINE
DOOR HEIGHT
0" ø 5'-
B
WOMEN'S TOILET 06 1" 1" 3'-0" 5' - 0"
5' - 4"
BC
WEATHERPROOF FRONT LOCKING 19" x 38" OUTDOOR CORK BULLETIN BOARD. (BASIS OF DESIGN: OUTDOOR DISPLAY CASES, ITEM #TKM824)
TOILET ACCESSORY KEY GRAB BAR
M
MIRROR
HD
WALL MOUNTED HAND DRYER
SD
SOAP DISPENSER
TD
TOILET PAPER DISPENSER
BC
BABY CHANGING TABLE
3
FLOOR
SCALE: 1/4" = 1'-0"
A
BASE
WALL CEILING
TYPE 1 FRAME ELEVATION
ALTERNATE BID #1 - TENNIS CENTER DOOR AND FRAME ELEVATIONS SCALE: 1/4" = 1'-0"
ALTERNATE BID #1 - TENNIS CENTER FINISH SCHEDULE
ADA ACCESSIBLE BENCH
SCALE: 1/4" = 1'-0"
CEILING WS-1 PT-1 APC-1 APC-1 PT-1 APC-2 APC-2
COMMENTS WOOD BEAMS TO BE PT-1
SLOPED TOP, PROVIDE REQUIRED END PANELS AND MITERED CORNERS CLOTHES HOOK (TYP.)
CT-2 & CT-3 ACCENT; SEE DETAIL 4/A-9 CT-5 & CT-6 ACCENT; SEE DETAIL 4/A-9
DOUBLE-TIER METAL LOCKERS 15"W x 18"D.
FINISH
MANUFACTURER
STYLE
COLOR
SIZE
CONTINUOUS WOOD FURRING STRIPS
COMMENTS
FLOOR FINISHES ACRILYCON
DECOR SYSTEM
LIGHT GREY D1
SHELF
CT-1
CERAMIC WALL TILE
DAL-TILE
SEMI-GLOSS/MATTE GROUP 1 GOLDEN GRANITE 0138
6" x 6"
FIELD TILE - WOMEN'S
CT-2
CERAMIC WALL TILE
DAL-TILE
SEMI-GLOSS/MATTE GROUP 1 CORNSILK 0160
6" x 6"
ACCENT TILE - WOMEN'S
CT-3
CERAMIC WALL TILE
DAL-TILE
SEMI-GLOSS/MATTE GROUP 4 KEY LIME Q098
6" x 6"
ACCENT TILE - WOMEN'S
CT-4
CERAMIC WALL TILE
DAL-TILE
SEMI-GLOSS/MATTE GROUP 1 PEPPER WHITE 0147
6" x 6"
FIELD TILE - MEN'S
CT-5
CERAMIC WALL TILE
DAL-TILE
SEMI-GLOSS/MATTE GROUP 2 GARDEN SPOT 0141
6" x 6"
ACCENT TILE - MEN'S
CT-6
CERAMIC WALL TILE
DAL-TILE
SEMI-GLOSS/MATTE GROUP 2 BLACK K111
6" x 6"
ACCENT TILE - MEN'S
PT-1
PAINT
BENJAMIN MOORE
FLAT
DISTANT GREY OC-68
MAIN FIELD PAINT
PT-2
PAINT
BENJAMIN MOORE
FLAT
GREENMOUNT SILK HC-3
LOCKER AREA AND ACCENT PAINT
PROVIDE STANDARD END PANELS AS REQUIRED 3'-0"
8'-3"
WALL FINISHES
CT-1 /CT-4: FIELD TILE BRICKWORK PATTERN
6'-0"
CT-2 & CT-3 / CT-5 & CT-6: ACCENT TILES CHECKERBOARD PATTERN
EPOXY FLOORING
6'-0"
1'-6"
TAG
EP-1 1'-0"
FLOOR EP-1 EP-1 EP-1 EP-1 EP-1 EP-1 EP-1
WALL LINE
ALTERNATE BID #1 - TENNIS CENTER FINISH MATERIAL LEGEND
APC-2: ACOUSTICAL PANEL CEILING (REFER TO CEILING PLANS)
6'-0"
FINISH BASE WALL WB-1 PT-2 WB-1 PT-1 WB-1 PT-1 WB-1 PT-1 WB-1 PT-1 CTB-1 CT-1 CTB-1 CT-4
3'-0"
ROOM NUMBER NAME 01 LOCKER AREA 02 STORAGE 03 OFFICE 04 STORAGE 05 JAN. CLOSET 06 WOMEN'S TOILET 07 MEN'S TOILET
ALTERNATE BID # 1 - TOILET ACCESSORY PLAN
1
ROOM #
ALTERNATE BID #1 -TENNIS CENTER FINISH FLOOR PLAN
TYPE C
DOOR ELEVATIONS
ROOM NAME
NDU SANITARY NAPKIN DISPOSAL
B
TYPE B
6"
GB
TYPE A
LOCKERS ABLE TO ACCEPT PADLOCKS (TYP.)
BASE FINISHES CTB-1
CERAMIC TILE BASE
DAL-TILE
COVE BASE A-3601
GOLDEN GRANITE 0138
6" x 6"
CTB-2
CERAMIC TILE BASE
DAL-TILE
COVE BASE A-3601
PEPPER WHITE 0147
6" x 6"
WB-1
VINYL BASE
JOHNSONITE
COVE BASE
PEBBLE 32
4" HIGH
INTEGRAL METAL BASE (TYP.) 4"
EP-1: EPOXY FLOORING
1'-6"
CEILING FINISHES
2
CERAMIC WALL TILE PATTERN (TYPICAL ALL WALLS)
1.) LOCKERS SHALL HAVE INTEGRAL METAL BASE. COORDINATE WITH LOCKER MANUFACTURER PRIOR TO INSTALLATION.
APC-1
ACOUSTIC PANEL CEILING
ARMSTRONG
FINE FISSURED; HIGH NRC 1755; 15/16 SQUARE LAY IN
WHITE
2'-0" x 4'-0"
APC-2
ACOUSTIC PANEL CEILING
ARMSTRONG
CERAMAGUARD UNPERFORATED; #605 - 15/16 SQUARE LAY-IN
WHITE
2'-0" x 4'-0"
PLAIN SLICED SELECT WHITE MAPLE
TO MATCH ARCHITECTS SAMPLE
SCALE: 1/2" = 1'-0"
WS-1
WOOD STAIN
SEE SPECIFICATIONS
4
LOCKER ELEVATION AND SECTION SCALE: 1" = 1'-0"
Signature & License No.
AI16116
DOOR & WINDOW FINISHES DWF-1
DOOR/WINDOW FRAME PAINT COLOR
PPG COATINGS PROTECTED
SEE SPECIFICATIONS
MEDIUM BRONZE
WD-1
WOOD
SEE SPECIFICATIONS
PLAIN SLICED SELECT
WHITE MAPLE - CLEAR
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
RENOVATIONS MISCELLANEOUS FINISHES TP-1
TOILET/URINAL PARTITION
SCRANTON PRODUCTS
HINEY HIDERS - ORANGE PEEL DESERT BEIGE
WOMEN'S TOILET ROOM
TP-2
TOILET/URINAL PARTITION
SCRANTON PRODUCTS
HINEY HIDERS - ORANGE PEEL BLACK
MEN'S TOILET ROOM
LKR-1
LOCKER COLOR
LIST INDUSTRIES
2-TIER ATHLETIC LOCKERS
BPT-1
BENCH PAINT
SEE SPECIFICATIONS
TO THE
WELCOME CENTER AND TENNIS CENTER
BASIL #735
AT
COLOR TO MATCH LOCKER COLOR
TO MATCH ARCHITECTS SAMPLE
BROOKDALE PARK TOWNSHIPS OF BLOOMFIELD AND MONTCLAIR
BARRIER FREE LEGEND
1' - 8" 39" - 41" 4' - 6"
8"
GB
FRONT VIEW H.C. WATER CLOSET
SIDE VIEW H.C. WATER CLOSET
MOUNTING HEIGHT TOILET PAPER DISPENSER
SIDE VIEW SINK MOUNTING HEIGHT
SIDE VIEW LEG CLEARANCE
20" - 25"
10"
MAX
17" - 25"
2'-6"
15" MIN.
2'-0"
4'-0"MAX.
OPERABLE HANDLE
4' - 0" MAX. TO
3'-4"MAX.
> 27"
MAX
2' - 10"
MAX
MAX
1
03.06.18
No.
Date
BID SET Issue or Revision
BID #1 - TENNIS CENTER FINISH PLAN, ENLARGED TOILET PLANS & DOOR SCHEDULE Scale USA Project No.
10" - 24"
3' - 10"
MAX
2' - 10"
MAX
4' - 0"
UNOBSTRUCTED SIDE REACH
5' - 0"
MIN
4' - 0"
34" - 48"
2' - 7"
2' - 10"
2' - 1"
FRONT VIEW DOOR ACCESSORY MOUNTING HEIGHT
ALTERNATE Drawing Title < 80"
OBSTRUCTED FORWARD REACH
MIN
1' - 3"
MAX
4' - 0"
MAX
3' - 8"
MAX
4' - 0"
OBSTRUCTED FORWARD REACH
SIDE VIEW BABY CHANGING STATION
MAX
MIN
1' - 3"
MAX
4' - 0"
3/1/2018 10:36:54 AM
UNOBSTRUCTED FORWARD REACH
MAX
SIDE VIEW URINAL MOUNTING HEIGHT
SIDE VIEW TOE CLEARANCE 4" MAX
NOTE: ALL OPERABLE FIXTURES ARE REQUIRED TO BE MOUNTED WITHIN THE REACH RANGES INDICATED ABOVE
1' - 8"
1' - 5"
9"
MIN
11" MIN INTERNATIONAL SYMBOL OF ACCESS
MIN
7" - 9"
2' - 3"
TD
MAX
2' - 10"
2" MIN
MIN
MIN
GB
16" - 18"
MIN
MIN
1' - 6"
MAX
BCT
1' - 3"
MIN
3' - 6"
17" - 19"
33" - 36"
MIN
1' - 0"
39" - 41"
MIN 2' - 0" 1' - 0"
GB
MIN
GB
33" - 36"
3' - 0"
RANGE OF TACTILE CHARACTER MOUNTING HEIGHT
4"
As indicated Drawing Date
OBSTRUCTED SIDE REACH
OBSTRUCTED SIDE REACH
PROTRUDING OBJECTS IN CIRCULATION PATHS
M
MIRROR
SD
SOAP DISPENSER
HD HAND DRYER
TD
TOILET PAPER DISPENSER
NDU
SANITARY NAPKIN DISPOSAL
2017-100 Drawing No.
03.06.18 Drawn By
Checked By
JS/JLG
ApA
A-204
+/- 7'-1"
7'-10"
+/- 7'-0"
HOLD EXISTING GAS METER TO REMAIN
11
2'-0"
4 P1 5
EXISTING ELECT. PANELS TO REMAIN
ELECTRICAL CLOSET 06
P1 WH
STORAGE/ MECHANICAL ROOM
4 3
12
10
12
10
BASEMENT HATCH
WELCOME CENTER 05
W1
Andrew P. Adornato, AIA Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA Mark A. Coan, AIA Peter C. Campisano, AIA
PT-2 ±9'-9" A.F.F. V.I.F.
NEW CEILING ACCESS HATCH
5
4'-10"
10
10
FD
2'-4" 2'-4"
W1
FD
5
5
WOMEN'S TOILET
MEN'S TOILET
4
4
3 FD
3
12
W1
WOMEN'S TOILET 03
12 FD
MEN'S TOILET
2
FD
W1
10
FD
PT-2 ±9'-9" A.F.F. V.I.F.
W1
FD
10
1
MECHANICAL ROOM 07
05 W1
NEW FLOOR HATCH
WOMEN'S TOILET
MECHANICAL ROOM 07
usaarchitects.com
1'-3"
9
PT-2 ±9'-9" A.F.F. V.I.F. WELCOME CENTER
P1
ELECTRICAL CLOSET 06
+/- 16'-8"
1
STORAGE/MECHANICAL ROOM
8
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
6
PT-2 ±9'-9" A.F.F. V.I.F.
1 A-104
FD
MEN'S TOILET 04 PT-2 ±9'-9" A.F.F. V.I.F.
2 6
1
7
6 7
12
12
FD
10
CUSTODIAN CLOSET
10
CUSTODIAN CLOSET
1
FD
4
6 5
W1
3
12
12
WOMEN'S TOILET 03
11
W1
CUSTODIAN CLOSET 02 MEN'S TOILET 04
2 VENDING MACHINE
CUSTODIAN CLOSET 02
VENDING MACHINE
VESTIBULE 01
VESTIBULE 13
13
VESTIBULE
11 1
4 11
12
3
12
1
VESTIBULE 01
PT-2 ±10'-0" A.F.F. V.I.F.
3
PT-3 ±9'-9" A.F.F. V.I.F.
7 14
Signature & License No.
AI16116
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
CONTRACTOR TO PROVIDE (14) PORTABLE TOILETS ("PORTA-POTTIES") FOR PUBLIC USE DURING CONSTRUCTION. CONTRACTOR IS TO MAINTAIN PORTABLE TOILETS THROUGHOUT PROJECT
RENOVATIONS TO THE
1
WELCOME CENTER DEMOLITION PLAN
2
SCALE: 1/4" = 1'-0"
WELCOME CENTER DEMOLITION CEILING PLAN
3
SCALE: 1/4" = 1'-0"
WELCOME CENTER PROPOSED FLOOR PLAN
4
SCALE: 1/4" = 1'-0"
WELCOME CENTER AND TENNIS CENTER
WELCOME CENTER PROPOSED CEILING PLAN SCALE: 1/4" = 1'-0"
AT
BROOKDALE PARK TOWNSHIPS OF BLOOMFIELD AND MONTCLAIR
DEMOLITION KEY:
SELECTIVE DEMOLITION LEGEND: EXISTING TO REMAIN
TO BE REMOVED
GENERAL DEMOLITION NOTES: 1. CONTRACTOR MUST INSTALL AND MAINTAIN PLASTIC DUST BARRIERS DURING DEMOLITION AND CONSTRUCTION TO PROTECT THE GENERAL PUBLIC FROM DUST AND FUMES. LOCATE PARTITIONS REQUIRED TO PROTECT ADJACENT AREAS AND EQUIPMENT, AND CONTINUE EGRESS THROUGH THE SPACE. CONTRACTOR SHALL PROVIDE TEMPORARY EXIT WAYS AS REQUIRED BY LOCAL CODE ENFORCEMENT OFFICIAL DURING CONSTRUCTION. 2. DO NOT CONSIDER DEMOLITION AND ALTERATION NOTES TO BE ALL INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND ASSESS EACH SPACE AND TO FULFILL THE INTENT OF THE WORK INDICATED BY THE CONTRACT DOCUMENTS. VERIFY ALL DIMENSIONS WITHIN THE CONTRACT LIMITS. BRING DEVIATIONS FROM THE CONTRACT DOCUMENTS TO THE ATTENTION OF THE ARCHITECT. THE EXTENT OF DEMOLITION AND REMOVAL INCLUDES, BUT IS NOT LIMITED TO WORK SHOWN ON THE DRAWINGS. COORDINATE W/ MECHANICAL, ELECTRICAL, PLUMBING & STRUCTURAL DRAWINGS.
3/1/2018 10:34:23 AM
3. REMOVE ANY MISCELLANEOUS PROJECTIONS, HANGERS, BOLTS, SCREWS AND NAILS FROM EXISTING SURFACES TO REMAIN. PATCH AND PREPARE SURFACES TO RECEIVE NEW FINISH.
X
DEMOLITION SCOPE OF WORK ITEM TYPICAL THROUGHOUT ENTIRE ROOM / AREA
X
DEMOLITION SCOPE OF WORK ITEM AT A SPECIFIC LOCATION
TRUSS STRUCTURE ABOVE GYPSUM BOARD CEILING AS SPECIFIED
1
REMOVE EXISTING FLOOR SYSTEM(S) IN THEIR ENTIRETY TO SUBSTRATE. PATCH AND REPAIR ADJACENT SURFACES TO RECEIVE NEW FINISHES.
2
REMOVE EXISTING CERAMIC WALL TILE IN ITS ENTIRETY TO SUBSTRATE. PATCH AND REPAIR ADJACENT SURFACES TO RECEIVE NEW FINISHES.
13
REMOVE AND STORE EXISTING VENDING MACHINE. REINSTALL AT COMPLETION.
3
REMOVE EXISTING CEILING SYSTEM(S) TO UNDERSIDE OF ROOF TRUSS IN THEIR ENTIRETY. PATCH AND REPAIR ADJACENT SURFACES TO RECEIVE FINISHES.
14
REMOVE AND REPLACE EXISTING GATE AND ACCESSORIES IN THIER ENTIRETY. PATCH AND REPAIR ADJACENT SURFACES TO RECIEVE NEW GATE SYSTEM.
4
REMOVE ALL LIGHTING FIXTURES, CEILING FANS AND ACCESSORIES IN THEIR ENTIRETY. COORDINATE WITH M.E.P. DRAWINGS.
5
REMOVE EXISTING FLOOR DRAIN STRAINER IN ITS ENTIRETY; MAINTAIN EXISTING FLOOR DRAIN. INSTALL NEW FLOOR DRAIN STRAINER. REFER TO M.E.P. DRAWINGS FOR MORE INFORMATION.
WALL BASE AS, BOTH SIDES
6
REMOVE AND DISCONNECT EXISTING PLUMBING FIXTURES AND COMPONENTS IN THEIR ENTIRETY. TEMPORARILY CAP ALL PIPING AS NECCESARY FOR NEW CONSTRUCTION. SAW CUT FLOOR AND/OR WALL TO ACCESS PIPING AS REQUIRED. PATCH AND REPAIR SURFACES TO MATCH ADJACENT FINISHES. REFER TO M.E.P. DRAWINGS FOR MORE INFORMATION.
SUBFLOOR
7
REMOVE EXISTING TOILET ACCESSORIES INCLUDING, BUT NOT LIMITED TO, TOILET PARTITIONS, SOAP DISPENSERS, PAPER TOWEL DISPENSERS, GRAB BARS, MIRRORS, ETC. PATCH AND REPAIR ADJACENT SURFACES TO RECEIVE NEW FINISHES.
4. PATCH AND REPAIR ALL ADJACENT SURFACES WHICH ARE AFFECTED BY THE DEMOLITION OR REMOVAL OF ACCESSORIES TO THEIR ORIGINAL FORM AND PREPARE FOR NEW FINISH. COORDINATE WITH FINISH DRAWINGS.
8
REMOVE AND REPLACE EXISTING WATER HEATER AND ITS COMPONENTS IN ITS ENTIRETY. REFER TO M.E.P. DRAWINGS FOR MORE INFORMATION.
5. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR DAILY CLEANUP OF CONSTRUCTION DEBRIS.
9
REMOVE EXISTING FLOOR HATCH, FRAME AND ACCESSORIES IN THEIR ENTIRETY. PREPARE ADJACENT SURFACES FOR INSTALLATION OF NEW FLOOR HATCH.
6. BEFORE DEMOLITION BEGINS, CONTRACTOR SHALL COORDINATE SEQUENCE AND SCHEDULES FOR ALL WORK AND RELOCATION OR DISPOSAL OF ALL MATERIALS WITH OWNER.
10
REMOVE EXISTING WINDOW SYSTEM AND ALL COMPONENTS IN THEIR ENTIRETY. PATCH AND REPAIR ADJACENT SURFACES TO RECEIVE NEW WINDOW SYSTEM.
11
REMOVE EXISTING DOOR, HARDWARE AND ACCESSORIES IN THEIR ENTIRETY. PREPARE FRAME FOR NEW FINISH AND INSTALLATION OF NEW DOOR. REFER TO DOOR SCHEDULE FOR MORE INFORMATION.
7. DEMOLITION PLANS ARE DIAGRAMMATIC. PRIOR TO SUBMITTING BID, GENERAL CONTRACTORS SHALL FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND BRING ANY AREAS IN QUESTION TO THE ATTENTION OF THE ARCHITECT.
CONTINUOUS METAL STUD TOP RUNNER
12
REMOVE EXISTING CEILING TRIM IN ITS ENTIRETY. PATCH AND REPAIR ADJACENT SURFACES TO RECEIVE NEW FINISHES. REFER TO FINISH SCHEDULE FOR MORE INFORMATION. ONE LAYER GYPSUM BOARD, EACH SIDE
CONTINUOUS METAL STUD BOTTOM RUNNER
CEILING LEGEND PT-2 PAINTED GYPSUM BOARD CEILING SYSTEM
EXTERIOR CEILING MOUNTED LIGHT FIXTURE
PT-3 PAINTED SOFFIT BOARD CEILING SYSTEM
CEILING MOUNTED LIGHT FIXTURE
SEALANT BOTH SIDES
P1
NEW 24" x 24" CEILING ACCESS DOOR (LOCATION IS EXISTING TO REMAIN)
1
03.06.18
No.
Date
WELCOME CENTER FLOOR PLANS
PARTITION TYPES SCALE: 1 1/2" = 1'-0"
Issue or Revision
Drawing Title
3 5/8" 20 GAUGE METAL STUD @ 16" O.C. AND 5/8" GYPSUM BOARD BOTH SIDES TO UNDERSIDE OF STRUCTURE
A
BID SET
Scale
USA Project No.
As indicated Drawing Date
2017-100 Drawing No.
03.06.18 Drawn By
Checked By
JS/JLG
ApA
A-100
+/- 10'-5"CLEAR
(V.I.F.)
(V.I.F.)
GB
NDU
1"
TD
3' - 0"
1"
NDU
TD
ELECTRICAL CLOSET 06
3' - 0"
FD
1"
1" 2'-11" 1"
2' - 10"
TD NDU
FD
WB-1
PT-1
PT-2
05 1"
TAG
MECHANICAL ROOM 07
WB-1
EP-1
WB-1
EP-1
PT-1
PT-2
PT-1
PT-2
WALL FINISHES
TRM-1 FINISH ALL WALLS THIS ROOM
NEW FLOOR HATCH
TRM-1 FINISH ALL WALLS THIS ROOM
M
SD
2' - 6"
2' - 6"
SD
MEN'S TOILET 04
M
SD
ADA TOILET
ADA TOILET
HD
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
CT-2 & CT-3 ACCENT; SEE DETAIL 4/A-104 CT-2 & CT-3 ACCENT; SEE DETAIL 4/A-104
usaarchitects.com Andrew P. Adornato, AIA Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA Mark A. Coan, AIA Peter C. Campisano, AIA
MANUFACTURER
STYLE
COLOR
SIZE
COMMENTS
EPOXY FLOORING
ACRILYCON
DECOR SYSTEM
LIGHT GREY D1
CT-1
CERAMIC WALL TILE
DAL-TILE
SEMI-GLOSS/MATTE GROUP 1
GOLDEN GRANITE 0138
6" x 6"
FIELD TILE - WOMEN'S
CT-2
CERAMIC WALL TILE
DAL-TILE
SEMI-GLOSS/MATTE GROUP 1
CORNSILK 0160
6" x 6"
ACCENT TILE - WOMEN'S
CT-3
CERAMIC WALL TILE
DAL-TILE
SEMI-GLOSS/MATTE GROUP 4
KEY LIME Q098
6" x 6"
ACCENT TILE - WOMEN'S
CT-4
CERAMIC WALL TILE
DAL-TILE
SEMI-GLOSS/MATTE GROUP 1
PEPPER WHITE 0147
CT-5
CERAMIC WALL TILE
DAL-TILE
SEMI-GLOSS/MATTE GROUP 2
GARDEN SPOT 0141
6" x 6"
ACCENT TILE - MEN'S
CT-6
CERAMIC WALL TILE
DAL-TILE
SEMI-GLOSS/MATTE GROUP 2
BLACK K111
6" x 6"
ACCENT TILE - MEN'S
PT-1
PAINT
BENJAMIN MOORE
FLAT
DISTANT GREY OC-68
FIELD TILE - MEN'S
MAIN FIELD PAINT
BASE FINISHES
2' - 9"
M
BC
M
FINISH
EP-1
SD
2' - 6"
SD
2' - 6"
WOMEN'S TOILET 03
2' - 2"
M
BC
COMMENTS
FLOOR FINISHES
M SD
CEILING PT-2 PT-2 PT-2 PT-2 PT-2 PT-2 PT-2
WELCOME CENTER FINISH MATERIAL LEGEND
1"
1"
NDU
EP-1
WELCOME CENTER
2'-7"
3' - 0"
TD
TD
2'-7"
2'-11"
1"
NDU
6
FINISH BASE WALL E.T.R. PT-1 WB-1 PT-1 CTB-1 CT-1 CTB-2 CT-4 WB-1 PT-1 WB-1 PT-1 WB-1 PT-1
FLOOR EP-1 EP-1 EP-1 EP-1 EP-1 EP-1 EP-1
2'-11"
3' - 0" 3' - 0"
TD
2'-11"
TD 2' - 11" 3' - 0"
2'-11"
1"
NDU
2' - 8"
2'-11"
5 TD
ROOM NUMBER NAME 01 VESTIBULE 02 CUSTODIAN CLOSET 03 WOMEN'S TOILET 04 MEN'S TOILET 05 WELCOME CENTER 06 ELECTRICAL CLOSET 07 MECHANICAL ROOM
4
1" 2'-11"
FD
3' - 0"
2'-11"
FD
TD
WELCOME CENTER FINISH SCHEDULE
1" 2'-11"
3' - 0"
3' - 0" 5' - 0"
1" 2'-11"
TD
CLEAR
GB 5' - 0"
CLEAR
TD
NDU
ADA TOILET
GB
TD
1"
5'-0"
GB
4'-11 1/2"
1' - 6"
ADA TOILET
1' - 6"
+/- 10'-5" CLEAR
HD
CTB-1
CERAMIC TILE BASE
DAL-TILE
COVE BASE A-3601
GOLDEN GRANITE 0138
6" x 6"
CTB-2
CERAMIC TILE BASE
DAL-TILE
COVE BASE A-3601
PEPPER WHITE 0147
6" x 6"
WB-1
VINYL BASE
ARMSTRONG
COVE BASE
PEBBLE 32
4" HIGH
FD
HD +/- 5'-3" CLEAR (V.I.F.)
CEILING FINISH
HD
CUSTODIAN CLOSET 02
TOILET ACCESSORY KEY +/- 5'-5" CLEAR (V.I.F.)
GB
GRAB BAR
M
MIRROR
FD
FD
PT-2
PAINT
BENJAMIN MOORE
FLAT
DISTANT GREY
CEILING AND CEILING HATCH
PT-3
PAINT
BENJAMIN MOORE
FLAT
DISTANT GREY
CEILING AND CEILING HATCH
NDU SANITARY NAPKIN DISPOSAL
VESTIBULE 01
HD
WALL MOUNTED HAND DRYER
SD
SOAP DISPENSER
TD
TOILET PAPER DISPENSER
BC
BABY CHANGING TABLE
DOOR FINISHES DF-1
DOOR FRAME PAINT COLOR
PPG COATINGS PROTECTED
SEE SPECIFICATIONS
MEDIUM BRONZE
WD-1
WOOD
SEE SPECIFICATIONS
PLAIN SLICED SELECT
WHITE MAPLE - CLEAR
MISCELLANEOUS FINISHES TP-1
TOILET/URINAL PARTITION
BRADLEY
POWDER COATED STEEL PARTITIONS
ALMOND
WOMEN'S TOILET ROOM
TP-2
TOILET/URINAL PARTITION
BRADLEY
POWDER COATED STEEL PARTITIONS
BLACK
MEN'S TOILET ROOM
TRM-1
CEILING CORNER TRIM
PVC TRIM - SMOOTH
WHITE
MEN'S TOILET
1" x 63"
04 CTB-2
CT-4
PT-2
WELCOME CENTER DOOR SCHEDULE
TRM-1 FINISH ALL WALLS THIS ROOM
WELCOME CENTER TOILET PLAN
FD
SCALE: 1/4" = 1'-0"
DOOR NUMBER 1 2 3 4 5
FD
WOMEN'S TOILET 03 EP-1
CTB-1
CT-1
PT-2
PT-2: GYPSUM BOARD CEILING SYSTEM (REFER TO CEILING PLANS)
TRM-1 FINISH ALL WALLS THIS ROOM
6 7
ELEVATION A A A AA AA A AA
STL STL
3'-0" 5'-8"
HEIGHT 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0"
EP-1
WB-1
PT-1
PT-2
DOOR WIDTH+4" (V.I.F.) 2" 2" 2" EQUAL EQUAL
VENDING MACHINE
DOOR WIDTH
DOOR WIDTH
DOOR WIDTH +4"
DOOR WIDTH +4"
1" TEMPERED INSULATED GLAZING (TYP.)
PT-2
CERAMIC WALL TILE PATTERN (TYPICAL ALL WALLS)
3
SCALE: 1/2" = 1'-0"
TYPE A ROOM #
WELCOME CENTER FINISH FLOOR PLAN
FLOOR
SCALE: 1/4" = 1'-0"
W1
TYPE 1
WALL CEILING
DOOR AND FRAME ELEVATIONS SCALE: 1/4" = 1'-0"
TYPE 2
TO THE
TYPE 3
WELCOME CENTER AND TENNIS CENTER
FRAME ELEVATIONS
4
AT
WINDOW ELEVATION SCALE: 1/4" = 1'-0"
BROOKDALE PARK
FRONT VIEW H.C. WATER CLOSET
SIDE VIEW H.C. WATER CLOSET
MOUNTING HEIGHT TOILET PAPER DISPENSER
SIDE VIEW SINK MOUNTING HEIGHT
SIDE VIEW LEG CLEARANCE
20" - 25"
10"
MAX
MAX
5' - 0"
MIN
4' - 0"
34" - 48"
2' - 1"
2' - 7"
SIDE VIEW BABY CHANGING STATION
FRONT VIEW DOOR ACCESSORY MOUNTING HEIGHT
1
03.06.18
No.
Date
Issue or Revision
CENTER FINISH PLAN, TOILET PLANS & DOOR SCHEDULE 2'-6"
2'-0"
15" MIN.
4'-0"MAX.
OPERABLE HANDLE
4' - 0" MAX. TO
3'-4"MAX.
> 27"
MAX
2' - 10"
MAX
3' - 10"
MAX
2' - 10"
MAX
4' - 0"
UNOBSTRUCTED SIDE REACH
BID SET
Drawing Title WELCOME
10" - 24"
< 80"
OBSTRUCTED FORWARD REACH
MIN
1' - 3"
MAX
4' - 0"
MAX
3' - 8"
MAX
2' - 10"
SIDE VIEW URINAL MOUNTING HEIGHT
SIDE VIEW TOE CLEARANCE
MAX
MIN
OBSTRUCTED FORWARD REACH
MAX
MIN
17" - 25"
4" MAX
NOTE: ALL OPERABLE FIXTURES ARE REQUIRED TO BE MOUNTED WITHIN THE REACH RANGES INDICATED ABOVE
1' - 8"
1' - 5"
MIN
9"
7" - 9"
2' - 3"
TD
MAX
2' - 10"
2" MIN
MIN
MIN
GB
16" - 18"
8"
GB
1' - 3"
MIN
BCT
MIN
MAX
1' - 6"
3' - 6"
39" - 41"
1' - 0"
33" - 36"
MIN
RANGE OF TACTILE CHARACTER MOUNTING HEIGHT
4"
MIN
GB
MIN 2' - 0" 1' - 0"
4' - 0"
A
BASE
39" - 41"
17" - 19"
33" - 36"
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
1' - 8"
11" MIN
MAX
TYPE AA
DOOR ELEVATIONS
ROOM NAME
4' - 6"
UNOBSTRUCTED FORWARD REACH
AI16116
TOWNSHIPS OF BLOOMFIELD AND MONTCLAIR
BARRIER FREE LEGEND
INTERNATIONAL SYMBOL OF ACCESS
Signature & License No.
RENOVATIONS WEATHERPROOF FRONT LOCKING 19" x 38" OUTDOOR CORK BULLETIN BOARD. (BASIS OF DESIGN: OUTDOOR DISPLAY CASES, ITEM #TKM824)
MIN
+/- 8'-0" V.I.F.
DOOR HEIGHT
PT-1
DOOR HEIGHT +2"
E.T.R.
DOOR HEIGHT +2"
EP-1
3 DOOR HEIGHT
6'-0"
CT-1 / CT-4: FIELD TILE BRICKWORK PATTERN
TRM-1 FINISH ALL WALLS THIS ROOM
DOOR HEIGHT
1
2"
VESTIBULE
EP-1: EPOXY FLOORING
1' - 3"
(V.I.F.)
+/- 9'-9" (V.I.F.)
2 VENDING MACHINE
GB
VERIFY ALL SIZES IN FIELD
+/- 2'-0" V.I.F.
TRM-1 FINISH ALL WALLS THIS ROOM
CT-2 & CT-3 / CT-5 & CT-6: ACCENT TILES CHECKERBOARD PATTERN
3' - 0"
05 03
02
7
4' - 0"
HM HM
COMMENTS VERIFY ALL SIZES IN FIELD; COLOR TO MATCH FRAME VERIFY ALL SIZES IN FIELD; COLOR TO MATCH FRAME VERIFY ALL SIZES IN FIELD; COLOR TO MATCH FRAME VERIFY ALL SIZES IN FIELD; COLOR TO MATCH FRAME
FD
01
3/1/2018 10:34:26 AM
1 3
HARDWARE SET 01 02 01 03 04
CUSTODIAN CLOSET
CT-1 / CT-4: FIELD TILE BRICKWORK PATTERN
2
FRAME ELEVATION MATERIAL E.T.R. E.T.R. E.T.R. E.T.R. E.T.R. E.T.R. E.T.R. E.T.R. 2 HM
2" 2'-2"
3'-0"
TRM-1 1" x 3" PVC TRIM
1'-0"
ROOM NAME WOMEN'S TOILET JANITOR'S CLOSET MEN'S TOILET WELCOME CENTER ELECTRICIAL CLOSET MECH ROOM VESTIBULE
DOOR MATERIAL WIDTH STL 3'-0" STL 3'-0" STL 3'-0" STL 6'-0" STL 6'-0"
+/- 9'-6" (V.I.F.)
1
EP-1
Scale
USA Project No.
As indicated Drawing Date
OBSTRUCTED SIDE REACH
OBSTRUCTED SIDE REACH
PROTRUDING OBJECTS IN CIRCULATION PATHS
M
MIRROR
SD
SOAP DISPENSER
HD HAND DRYER
TD
TOILET PAPER DISPENSER
NDU
SANITARY NAPKIN DISPOSAL
2017-100 Drawing No.
03.06.18 Drawn By
Checked By
JS/JLG
APA
A-104
PRINCIPAL'S AREA ALTERATIONS OF
NUVIEW ACADEMY ANNEX
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
FOR THE
E.S.C. OF N.J
usaarchitects.com Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
1690 Stelton Rd, Piscataway, NJ
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
DRAWING LIST PROJECT LOCATION:
SYMBOL LEGEND
1690 STELTON ROAD PISCATAWAY, TWP, NJ 08854
DESIGN TEAM ARCHITECT
NORTH ARROW
Room Name ROOM TAG
101
A
ELEVATION / SECTION MARK SPOT ELEVATION
VIEW NAME SCALE: 1/8" = 1'-0" 1 A-101
1
TITLE SHEET GENERAL NOTES PARTIAL EGRESS PLANS DEMOLITION PLANS DOOR SCHEDULE + DETAILS
OFFICE ADDRESS PHONE # MEP
REVISION TAG
1
1
A-001 A-002 A-011 A-050 A-600
USA ARCHITECTS PLANNERS + INTERIOR DESIGNERS, P.A.
SIM
A-101
ARCHITECTURAL
TITLE MARK
STRUNK-ALBERT ENGINEERING
SIM DETAIL MARK
BL-1
INTERIOR WINDOW TAG
CW2
WINDOW TAG
101
DOOR TAG
P1
WALL TAG
804 SEVEN BRIDGES ROAD, EAST STROUDSBURG, PA 18301
Signature & License No.
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
LOCATION MAP SCALE: N.T.S.
PRINCIPAL'S AREA ALTERATIONS OF
NUVIEW ACADEMY ANNEX FOR THE
E.S.C. OF N.J 1690 Stelton Rd, Piscataway, NJ
No.
Date
Issue or Revision
Drawing Title
8/29/2017 10:50:51 AM
TITLE SHEET Scale
USA Project No.
As indicated Drawing Date
2017-070 Drawing No.
08.25.17 Drawn By
Checked By
JS
PC
A-001
CSI DIVISION DIVISION 00 PROCUREMENT
00.01 ALL BIDDERS, UPON SUBMITTING BIDS, HEREBY CERTIFY THAT THEY HAVE REVIEWED THE ENTIRE SET OF CONTRACT DOCUMENTS, (CONTRACT DOCUMENTS CONSIST OF A COMPLETE SET OF DRAWINGS AND THE ENTIRE PROJECT MANUAL, INCLUDING ALL DIVISIONS & ANY/ALL ADDENDA) AND ARE AWARE OF, AND AGREE TO MEET THE INTENT OF THE CONTRACT DOCUMENTS WHETHER EXPRESSED OR IMPLIED.
01.15 ALL UNUSED MATERIAL AND DEBRIS SHALL BE COMPLETELY REMOVED FROM THE SITE AND LEGALLY DISPOSED OF. NO ON-SITE STORAGE, BURNING, OR BURIAL OF DEBRIS SHALL BE PERMITTED. THE CONSTRUCTION SITE SHALL BE KEPT IN A CLEAN AND SAFE MANNER, INCLUDING, BUT NOT LIMITED TO DAILY BROOM CLEANING THROUGHOUT THE DURATION OF THE CONSTRUCTION PROJECT.
00.02 PRODUCT MANUFACTURERS IN CONJUNCTION WITH SUBCONTRACTORS AND PRIME CONTRACTOR(S) ARE RESPONSIBLE FOR ALL COMPONENTS AND CALCULATIONS AND/OR CERTIFICATIONS OF THEIR PRODUCT AND FOR PROVIDING COMPLETE SYSTEMS/ASSEMBLIES TO MEET THE DESIGN INTENT OF THE PROJECT. 00.03 THE BIDDER/CONTRACTOR IS REQUIRED TO VISIT THE SITE & EXAMINE THE EXISTING CONDITIONS TO HIS COMPLETE SATISFACTION PRIOR TO BIDDING. THE BIDDER/CONTRACTOR SHALL COMPARE THE EXISTING CONDITIONS TO THE DESIGN INTENT OF THE CONTRACT DOCUMENTS & SHALL IMMEDIATELY NOTIFY THE ARCHITECT IN WRITING OF ANY/ALL DISCREPANCIES BEFORE SUBMITTING A BID. FAILURE TO DO SO WILL PLACE THE BURDEN OF RESPONSIBILITY ON THE CONTRACTOR TO PERFORM THE WORK AS INTENDED BY THE CONTRACT DOCUMENTS, AT NO ADDITIONAL COST TO THE OWNER. DIVISION 01 AVAILABLE INFORMATION
TEMPORARY FACILITIES & ACCESS
01.16 CONSTRUCTION ACCESS ROADS, CURB CUTS, SOIL EROSION CONTROL, & THE LOCATION OF ALL TEMPORARY FACILITIES (INCLUDING POWER, TELEPHONE, WATER, WASTE, ETC.) SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR (UNLESS OTHERWISE NOTED), & SHALL BE COORDINATED WITH UTILITY COMPANIES, MUNICIPAL AUTHORITIES, ETC. AS REQUIRED.
PRODUCT REQUIREMENTS
01.17 ALL MATERIALS AND PRODUCTS SHALL BE PROTECTED AND PROPERLY STORED AS PER MANUFACTURER'S RECOMMENDATION. ALL MATERIALS AND PRODUCTS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S CURRENT PRINTED RECOMMENDATIONS TO MAINTAIN THE PROPER WARRANTIES.
01.01 ANY ADDITIONAL INFORMATION THAT IS NOT PART OF THE CONSTRUCTION DOCUMENTS, SUCH AS, BUT NOT LIMITED TO, SOIL REPORT(S), HAZARDOUS MATERIALS REPORT(S), EXISTING DRAWINGS, ETC., ARE INTENDED FOR REFERENCE ONLY AND ARE TO BE USED BY THE CONTRACTOR(S) AT HIS/HER OWN DISCRETION.
01.18 PRIOR TO THE INSTALLATION OF ALL MAJOR BUILDING COMPONENTS, THE PRIME CONTRACTOR(S) SHALL CONDUCT A PREINSTALLATION AND COORDINATION MEETING WITH THE MANUFACTURER'S REPRESENTATIVE. INCLUDED IN THE MEETING SHALL BE ANY SUBCONTRACTOR AND PRODUCT MANUFACTURER AFFECTED BY THE SPECIFIC WORK. FAILURE OF THE PRIME CONTRACTOR(S) TO CONDUCT SUCH A MEETING, AND PROPERLY COORDINATE THE PROCESS, SHALL PLACE THE BURDEN FOR ANY & ALL PROBLEMS, RESULTING FROM SAID INSTALLATION, UPON THE PRIME CONTRACTOR(S) RESPONSIBLE FOR THAT PORTION OF THE WORK.
01.02 THE INDICATION OF SUBSTRATE & CONFIGURATION OF CONCEALED ITEMS & MATERIALS SHOWN ON THE CONSTRUCTION DOCUMENTS IS FOR GENERAL REFERENCE ONLY. THE CONTRACTOR(S) SHALL NOT BE ENTITLED TO ADDITIONAL COMPENSATION FOR ANY VARIANCE BETWEEN ACTUAL EXISTING CONDITIONS AND THAT REPRESENTED ON THE CONSTRUCTION DOCUMENTS.
01.19 LONG LEAD ITEMS SHALL BE IDENTIFIED BY THE CONTRACTOR(S) WITH NOTIFICATION TO THE ARCHITECT IN A TIMELY MANNER. FAILURE BY THE CONTRACTOR(S) TO OBTAIN SUBMITTAL APPROVALS, AND TO ORDER LONG LEAD ITEMS, SO AS NOT THE DELAY THE PROGRESS OF THE WORK, WILL NOT JUSTIFY AN EXTENSION OF THE SCHEDULE FOR COMPLETION, NOR WILL IT CAUSE PRODUCT SUBSTITUTIONS IN ORDER TO MEET THE SCHEDULE.
01.03 ALL DIMENSIONS INDICATED ON THE CONSTRUCTION DOCUMENTS, OF EXISTING CONDITIONS, ARE APPROXIMATE AND SHALL BE FIELD VERIFIED BY THE CONTRACTOR(S) PRIOR TO SUBMITTING A BID. GENERAL REQUIREMENTS
01.04 THE CONTRACTOR(S) SHALL DISCUSS & VERIFY, WITH ALL GOVERNING AUTHORITIES ALL CODE REQUIREMENTS INDICATED AND/OR REQUIRED FOR THE COMPLETE EXECUTION OF THE WORK AS INTENDED BY THE CONSTRUCTION DOCUMENTS.
EXECUTION REQUIREMENTS
01.05 THE CONTRACTOR(S) SHALL COMPLY WITH ALL FEDERAL, STATE, AND LOCAL CODES AND ORDINANCES HAVING JURISDICTION OVER THE PROJECT. THE CONTRACTOR(S) SHALL OBTAIN PERMITS & GIVE NOTICES TO SUCH AGENCIES IN AMPLE TIME FOR OFFICIALS TO CONDUCT INSPECTIONS AND OBTAIN TIMELY APPROVALS. FAILURE TO COMPLY WILL SOLELY BE THE RESPONSIBILITY OF THE CONTRACTOR(S).
01.22 EACH PRIME CONTRACTOR SHALL PROVIDE ALL NECESSARY SHORING & BRACING TO SUPPORT EXISTING OR NEW CONSTRUCTION NOT FULLY SET UNTIL PERMANENT SUPPORTS ARE ERECTED. TAKE ALL NECESSARY MEASURES TO PREVENT COLLAPSE OF ANY ELEMENT OF NEW OR EXISTING CONSTRUCTION. 01.23 EACH PRIME CONTRACTOR SHALL FIRE STOP/SMOKE PROOF ANY/ALL PENETRATIONS AS REQUIRED TO MAINTAIN THE DESIGNATED FIRE RATING/SMOKE PROOFING OF THE CONSTRUCTION WHETHER EXISTING OR NEW. THE GENERAL CONTRACTOR SHALL ALSO EXTEND RATED CONSTRUCTION TO MAINTAIN CONTINUITY OF SAME THROUGH CONCEALED SPACES (VERTICAL & HORIZONTAL) AS REQUIRED.
01.07 DO NOT SCALE THE DRAWINGS. USE CALCULATED DIMENSIONS ONLY. NOTE THAT NOT ALL DIMENSIONS ARE GIVEN ON THE CONSTRUCTION DOCUMENTS. SOME DIMENSIONS ARE IMPLIED. IF THE CONTRACTOR IS NOT SURE OF A GIVEN DIMENSION, HE/SHE SHALL SUBMIT A REQUEST FOR INFORMATION (R.F.I.) AND/OR SHALL FIELD VERIFY EXISTING DIMENSIONS.
01.24 ANY/ALL EQUIPMENT PROVIDED SHALL BE INSTALLED TO BE COMPLETELY FUNCTIONAL. EACH PIECE OF EQUIPMENT PROVIDED BY A PRIME CONTRACTOR, REQUIRING SERVICE CONNECTIONS BY ANOTHER PRIME CONTRACTOR SHALL BE COORDINATED BY THE GENERAL CONTRACTOR. STARTUP & TESTING OF EQUIPMENT SHALL BE PERFORMED & DOCUMENTED BY FACTORY AUTHORIZED PERSONNEL.
01.08 ALL INFORMATION FOR ALL TRADES CONTAINED WITHIN THE CONSTRUCTION DOCUMENTS SHALL BE USED TOGETHER & IN CONCERT WITH ONE ANOTHER AS A WHOLE BODY OF INFORMATION FOR THE PROJECT. THE DRAWINGS & PROJECT MANUAL ARE COMPLEMENTARY & WHAT IS REQUIRED BY ONE, SHALL BE REQUIRED BY BOTH. NEITHER THE PRIME CONTRACTOR(S) NOR ANY SUBCONTRACTOR(S) SHALL BE RELIEVED OF THE RESPONSIBILITY TO PROVIDE ALL ITEMS REQUIRED BY THE INFORMATION & DESIGN INTENT INDICATED & IMPLIED. IN THE EVENT OF CONFLICTS BETWEEN DOCUMENTS, THE GREATER QUANTITY OR HIGHER QUALITY OF WORK SHALL PREVAIL AND BE PROVIDED.
01.25 DETAILS & SECTIONS ON THE DRAWINGS ARE SHOWN AT SPECIFIC LOCATIONS & ARE INTENDED TO SHOW GENERAL REQUIREMENTS THROUGHOUT. DETAILS NOTED "TYPICAL" IMPLY ALL "LIKE-CONDITIONS" ARE TO BE TREATED SIMILARLY. 01.26 WORK NOT INDICATED IN PART OF THE DRAWING, BUT REASONABLY IMPLIED TO BE SIMILAR TO THAT SHOWN AT CORRESPONDING PLACES SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST.
01.09 ALL ITEMS LABELED "EXISTING" ARE EXISTING "TO REMAIN" UNLESS OTHERWISE INDICATED. ITEMS NOT LABELED "EXISTING" ARE TO BE PROVIDED. THE TERM "PROVIDE" SHALL MEAN FURNISH & INSTALL AS IT IS USED THROUGHOUT THE CONTRACT DOCUMENTS. 01.10 THE SCOPE OF THIS SINGLE OVERALL PRIME CONTRACT INCLUDES ALL THE WORK AS INDICATED ON THE DRAWINGS AND IN THE PROJECT MANUAL. THE SINGLE OVERALL PRIME CONTRACTOR BEARS SOLE SOURCE RESPONSIBILITY FOR THE DELIVERY OF THE PROJECT TO 100% COMPLETION.
01.27 MINOR DETAILS OR INCIDENTAL ITEMS NOT USUALLY SHOWN OR SPECIFIED, BUT NECESSARY FOR THE PROPER & COMPLETE EXECUTION OF ANY PART OF THE WORK SHALL BE INCLUDED AS IF THEY WERE SPECIFICALLY INDICATED IN THE CONSTRUCTION DOCUMENTS. CUTTING AND PATCHING
01.28 UNLESS OTHERWISE INDICATED: CUTTING AND PATCHING (EXCEPT FOR FINISHES) IS TO BE PERFORMED BY THE PRIME CONTRACTOR REQUIRING CUTTING AND PATCHING, WHETHER AS SELECTIVE DEMOLITION, OR AS A MEANS OF ACCESSING OR CORRECTING UNSATISFACTORY WORK. PATCHING OF THE SUBSTRATE IS ALSO THE WORK OF THAT PRIME CONTRACTOR, HOWEVER THE PATCHING OF ALL FINISHES EXPOSED TO VIEW IS TO BE DONE BY THE GENERAL CONTRACTOR USING SKILLED TRADESMAN TRAINED FOR PATCHING THE PARTICULAR FINISH INVOLVED.
SUBMITTALS AND SUBSTITUTIONS
01.29 THE PROJECT HAS BEEN DESIGNED TO MEET A CERTAIN PROFESSIONAL STANDARD AND PRODUCTS HAVE BEEN SELECTED TO MEET SUCH STANDARDS. THE PRODUCTS SPECIFIED ARE THE PRODUCTS INTENDED TO BE USED. IN THE EVENT THAT SUBSTITUTIONS ARE SUBMITTED FOR REVIEW, A PROPER COMPARATIVE INFORMATION SHEET SHALL ALSO BE SUBMITTED. ALL REQUESTS FOR SUBSTITUTION SHALL BE MADE WITHIN THE FIRST 90 DAYS AFTER THE CONTRACTOR HAS BEEN AWARDED THE CONTRACT FOR CONSTRUCTION. NO SUBSTITUTION WILL BE CONSIDERED AFTER THIS PERIOD.
Use only one SUMMARY OF WORK option (above or below) as applicable. Delete the non-applicable option. SUMMARY WORK (MULTIPLE PRIME CONTRACTS) PROJECT COORDINATION (SINGLE OVERALL PRIME CONTRACT)
01.10 THE WORK OF THIS PROJECT IS DIVIDED INTO VARIOUS PRIME CONTRACTS. PRIME CONTRACTS ARE SEPARATE CONTRACTS WITH THE OWNER REPRESENTING SIGNIFICANT PORTIONS OF THE WORK. THE DIVISION OF RESPONSIBILITY FOR EACH PRIME CONTRACT IS NOT INDICATED BY THE ORGANIZATION OF THE DRAWINGS OR THE SPECIFICATIONS, BUT IS GIVEN IN THE PROJECT MANUAL IN THE SECTION TITLED "SUMMARY OF WORK". 01.11 THE SINGLE OVERALL PRIME CONTRACTOR BEARS SOLE SOURCE RESPONSIBILITY FOR THE COORDINATION OF THE ACTIVITIES OF ALL SUBCONTRACTORS, SUB-SUBCONTRACTORS, MATERIAL SUPPLIERS, AND ALL PARTIES INVOLVED IN THE EXECUTION OF THE PROJECT. Use only one PROJECT COORDINATION option (above or below) as applicable. Delete the non-applicable option. 01.11 THE GENERAL CONTRACTOR BEARS SPECIAL RESPONSIBILITIES AS THE PRINCIPAL PROJECT COORDINATOR AS IT PERTAINS TO THE ACTIVITIES OF ALL PRIME CONTRACTORS, AS INDICATED IN THE PROJECTS MANUAL UNDER THE SECTION TITLED "PROJECT COORDINATION".
PROJECT COORDINATION (MULTIPLE PRIME CONTRACTS)
QUALITY REQUIREMENTS
01.12 ENGINEERING DRAWINGS (STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION, COMMUNICATIONS, AND SECURITY SYSTEM DRAWINGS, ETC.) ARE SHOWN DIAGRAMMATICALLY AND ARE NOT TO SCALE, NOR DO THEY SHOW THE EXACT LOCATION OF THEIR COMPONENTS. THE EXACT LOCATION AND CLEARANCES FOR EACH SUCH SYSTEM OF COMPONENTS SHALL BE COORDINATED BY THE CONTRACTOR(S). ALL PRIME CONTRACTORS, PRIOR TO PURCHASE, FABRICATION, OR INSTALLATION OF THESE ITEMS SHALL PREPARE COORDINATION DRAWINGS SHOWING THE DIFFERENT TRADES BY COLORS AND SHALL CONDUCT A COORDINATION MEETING WITH ALL OTHER CONTRACTOR(S) AFFECTED FOR A TOTAL UNDERSTANDING OF THE DESIGN INTENT. THE ARCHITECTS AND THE ENGINEERS(S) SHALL BE INVITED TO ATTEND THIS MEETING AND OFFER INPUT PRIOR TO ANY WORK BEING FABRICATED OR INSTALLED. 01.13 THE CONTRACTOR SHALL PROVIDE ALL MATERIAL, LABOR, SERVICES, ETC. TO COMPLETE THE ENTIRE WORK IN A MANNER ACCEPTABLE TO THE OWNER AND THE ARCHITECT. IT IS UNDERSTOOD THAT NOT EVERY DETAIL OR DIMENSION IS SHOWN IN THE CONTRACT DOCUMENTS, NOR ARE THEY NECESSARY FOR THE CONTRACTOR(S) TO PROVIDE A QUALITY PRODUCT. THE CONTRACTOR SHALL SUBMIT A REQUEST FOR INFORMATION (R.F.I.) IF NEEDED TO CLARIFY THE INTENT OF ANY DETAIL OR OTHER INFORMATION. HOWEVER, SUCH REQUEST FOR INFORMATION SHALL NOT CONSTITUTE A CHANGE IN THE SCHEDULE, OR IN THE CONTRACT AMOUNT. NO WORK SHOULD BE INSTALLED IF THE CONTRACTOR IS UNSURE OF THE DESIGN INTENT. INSTALLATION OF ANY WORK THAT DOES NOT COMPLY WITH THE DESIGN INTENT, AS DETERMINED BY THE ARCHITECT, SHALL BE SUBJECT TO REPLACEMENT AT THE CONTRACTOR'S EXPENSE.
01.20 MISCELLANEOUS WOOD, COLD FORMED, OR ROLLED STEEL SHAPES, WHETHER BLOCKING OR SUB-FRAMING WHICH ARE REQUIRED FOR THE INSTALLATION OF OTHER ITEMS NECESSARY FOR A COMPLETE PACKAGE SHALL BE PROVIDED WHETHER OR NOT SPECIFICALLY INDICATED ON THE DRAWINGS. 01.21 DIMENSIONS GIVEN FOR MASONRY OPENINGS ARE NOMINAL. GENERAL CONTRACTOR(S) SHALL COORDINATE THE FABRICATION OF DOOR, WINDOW, AND VISION PANEL FRAMES AND OTHER ITEMS TO BE INSTALLED IN MASONRY TO ACCOMMODATE ACTUAL DIMENSIONS VERIFIED IN THE FIELD WITH AND WITHOUT MORTAR JOINTS AS THEY OCCUR.
01.06 THE CONTRACTOR(S) SHALL PROVIDE PROTECTION FOR THE PUBLIC, OWNER'S STAFF, AND CONSTRUCTION WORKERS IN AND AROUND THE CONSTRUCTION AREA & ADJACENT PROPERTY. ADEQUATE BARRIERS & SIGNAGE SHALL BE PROVIDED TO EXERCISE CONTROL OF SAFE INGRESS & EGRESS OF PREMISES. FIRE EXITS SHALL NOT BE BLOCKED. PROPER SITE SECURITY DURING WORKING & OFF-HOURS SHALL BE MAINTAINED. BARRICADE ALL UNSAFE OR POTENTIALLY DANGEROUS CONDITIONS. THE CONTRACTOR(S) SHALL FOLLOW O.S.H.A. STANDARDS DURING THE COURSE OF THE PROJECT.
SUMMARY WORK (SINGLE OVERALL PRIME CONTRACT)
01.35 IF SUBSTITUTIONS ARE APPROVED, THE CONTRACTOR SHALL NOTIFY ALL OTHER TRADES AFFECTED BY THE SUBSTITUTION & FULLY COORDINATE THE IMPACT ON THE PROJECT. ANY ADDITIONAL COST RESULTING FROM SUBSTITUTIONS SHALL BE PAID BY THE CONTRACTOR PROPOSING THE SUBSTITUTION.
01.14 ALL CONSTRUCTION, EQUIPMENT, CONTENTS, ETC. SHALL BE PROTECTED BY EACH CONTRACTOR DURING THE ENTIRE PERFORMANCE OF THE WORK. AREAS DISTURBED OR DAMAGED BY THE CONTRACTOR SHALL BE COMPLETELY RESTORED, REPAIRED, OR REPLACED BY THE CONTRACTOR. TO THE OWNER'S COMPLETE SATISFACTION AT NO ADDITIONAL COST.
01.30 THE PRIME CONTRACTOR SHALL PROVIDE ALL REQUIRED SCHEDULES, SUCH AS BUT NO LIMITED TO: SUBMISSION SCHEDULE, CONSTRUCTION SCHEDULE, & SCHEDULE OF VALUES PRIOR TO SUBMISSION OF THE FIRST APPLICATION FOR PAYMENT. NO APPLICATION FOR PAYMENT WILL BE APPROVED BY THE ARCHITECT UNTIL THIS PREREQUISITE IS COMPLIED WITH PROPERLY. 01.31 THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS SUFFICIENTLY IN ADVANCE OF THE WORK TO ALLOW PROPER TIME FOR REVIEW. MATERIALS SHALL NOT BE FABRICATED OR DELIVERED TO THE SITE BEFORE THE SHOP DRAWINGS HAVE BEEN APPROVED. 01.32 SHOP DRAWINGS SHALL BE REVIEWED BY THE ARCHITECT/ENGINEER FOR BASIC CONFORMANCE TO THE DESIGN INTENT ONLY AFTER PRIOR APPROVAL BY THE RESPONSIBLE PRIME CONTRACTOR. THIS REVIEW DOES NOT RELIEVE THE CONTRACTOR OR HIS SUB-CONTRACTOR(S) OF RESPONSIBILITY FOR FULL COMPLIANCE WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DIMENSIONS & CLEARANCES TO BE CONFIRMED & CORRELATED AT THE JOB SITE, FOR MATERIALS QUANTITIES & PROPER FABRICATION, FOR PROPER MEANS & METHODS, FOR PROPER SEQUENCES OF CONSTRUCTION, FOR THE PROPER COORDINATION WITH OTHER TRADES, AND FOR PROVIDING SAFE AND SATISFACTORY CONSTRUCTION OPERATIONS. 01.33 EACH CONTRACTOR IS ADVISED THAT CERTAIN COLOR SCHEDULE SELECTIONS MAY HAVE PREVIOUSLY BEEN MADE, REVIEWED, AND APPROVED BY THE OWNER & RETURNED TO THE CONTRACTOR FOR EXECUTION. ALL CONTRACTORS SHALL TAKE NOTE & HEREAFTER STRONGLY BE ADVISED THAT MATERIAL SUBSTITUTIONS SUBMITTED LATER MAY BE REQUIRED TO BE PROVIDED WITH CUSTOM COLORS, TEXTURES, & FINISHES BASED UPON SELECTIONS PREVIOUSLY APPROVED. MATERIAL SUBSTITUTIONS ARE SUBJECT TO REJECTION SOLELY ON APPEARANCE. 01.34 THE ARCHITECT WILL TAKE APPROPRIATE ACTION UP TO THREE (3) TIMES FOR EACH ITEM SUBMITTED. SUBMITTALS REQUIRING MORE THAN THREE (3) REVIEWS DUE TO INCORRECT OR INCOMPLETE INFORMATION SHALL BE SUBJECT TO A REVIEW FEE FOR EACH SUBSEQUENT SUBMITTAL. THIS FEE SHALL BE AT THE HOURLY RATE OF THE ARCHITECT & ENGINEER, AND SHALL BE PRE-PAID TO THE ARCHITECT BY THE CONTRACTOR PRIOR TO ANY ADDITIONAL CONSIDERATION. FEES PAID SHALL IN NO WAY CONSTITUTE AN OBLIGATION BY THE ARCHITECT TO APPROVE ANY SUBMITTAL THAT IN HIS/HER OPINION DOES NOT COMPLY WITH THE DESIGN INTENT OF THE CONTRACT DOCUMENTS. FURTHERMORE, ANY SUCH ADDITIONAL REVIEW TIME SHALL NOT BE A BASIS FOR AN EXTENSION OF TIME.
STANDARD WARRANTY
01.36 EACH PRIME CONTRACTOR SHALL PROVIDE, AS PART OF ITS REQUIRED CLOSE-OUT DOCUMENTS, A STANDARD WARRANTY COVERING ALL MATERIALS, PRODUCTS, AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE ARCHITECT. THIS STANDARD WARRANTY IS A BASIC REQUIREMENT OF EACH PRIME CONTRACT AND SHALL BE EXTENDED BY SPECIFIC WARRANTY REQUIREMENTS OF THE VARIOUS PRODUCTS AND SYSTEMS AS INDICATED THROUGHOUT THE CONTRACT DOCUMENTS.
DIVISION 02 DEMOLITION
02.01 THE ACTUAL SCOPE OF DEMOLITION SHALL NOT BE LIMITED TO WHAT IS SPECIFICALLY INDICATED ON THE DRAWINGS OR WITHIN THE PROJECT MANUAL, BUT SHALL INCLUDE ANY AND ALL COMPLETE OR SELECTIVE DEMOLITION AS MAY BE NECESSARY TO ACCOMPLISH THE INTENDED CONSTRUCTION. THIS APPLIES TO THE WORK OF ALL TRADES.
DIVISION 05 HANDRAILS & GUARDRAILS
05.01 HANDRAILS & GUARDRAILS ARE SHOWN SCHEMATICALLY TO GIVE LOCATION & GENERAL REQUIREMENTS ONLY. THE CONTRACTOR IS RESPONSIBLE FOR THE TECHNICAL DESIGN OF SUCH, INCLUDING BUT NOT LIMITED TO POSTS AND RAIL WALL THICKNESS & LOCATION, WELDS, MECHANICAL ATTACHMENT, AND ALL CONNECTIONS. THE SYSTEM SHOULD WITHSTAND AN APPLIED LOAD OF 200 LB AT ANY POINT IN ANY DIRECTION AND MEET ALL CODES REGULATION SUCH DESIGN. SHOP DRAWINGS SHALL BE SUBMITTED FOR ARCHITECT'S REVIEW. THIS APPLIES TO BOTH INTERIOR & EXTERIOR CONDITIONS. ALL STAIRS, STEPS, RAMPS, BALCONIES, AND CHANGES IN ELEVATION SHALL BE PROVIDED WITH APPROPRIATE RAIL PROTECTION.
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
EXTERIOR FERROUS METALS
05.02 ALL FERROUS METAL USED ON OR EXPOSED TO THE EXTERIOR OF THE BUILDING INCLUDING BUT NOT LIMITED TO: STRUCTURAL AND MISCELLANEOUS FRAMING, WINDOWS, DOORS AND FRAMES, HANDRAILS, LINTELS, ETC. SHALL BE HOTDIPPED AND GALVANIZED PRIOR TO INSTALLATION AND PAINTING.
usaarchitects.com
DIVISION 06 WOOD BLOCKING
06.01 EVERY HOLLOW WALLBOARD PARTITION THAT IS INDICATED TO RECEIVE ANY ACCESSORIES SUCH AS, BUT NOT LIMITED TO, TOILET ACCESSORIES, HANDICAP RAILS, CABINETS, WALL MOUNTED BACK-BOARDS, ETC. SHALL BE PROVIDED WITH SOLID BLOCKING AND REINFORCEMENT WITHIN THE FRAMING TO ADEQUATELY SUPPORT THE INSTALLATION OF SUCH ITEMS.
EXTERIOR WOOD
06.02 ALL WOOD FRAMING LUMBER AND BLOCKING EXPOSED TO THE ELEMENTS OR USED IN CONTACT WITH MASONRY, CONCRETE, AND/OR ROOFING SHALL BE PRESSURE TREATED FOR RESISTANCE TO DETERIORATION FROM MOISTURE. 07.01 ANY AND ALL CONSTRUCTION JOINTS INCLUDING JOINTS BETWEEN DIFFERENT ITEMS AND MATERIALS, JOINTS SURROUNDING PENETRATIONS THROUGH MATERIALS, AND CRACKS WITHIN MATERIALS, ECT., WHETHER ON THE INTERIOR OR EXTERIOR OF THE BUILDING, SHALL BE FILLED WITH AN APPROPRIATE SEALANT AS REQUIRED. ON THE INTERIOR OF THE BUILDING, SAID SEALANT SHALL BE PAINTABLE. ON THE EXTERIOR OF THE BUILDING, SAID SEALANT SHALL BE WEATHERPROOF AND IN A COLOR SELECTED BY THE ARCHITECT.
DIVISION 07 SEALANTS
ROOFING
07.02 PRIOR TO THE START OF ROOF WORK, THE CONTRACTOR IS REQUIRED TO CONDUCT A PRE-INSTALLATION CONFERENCE WITH THE ROOFING MANUFACTURER, THE ROOF INSTALLER, OTHER AFFECTED CONTRACTORS, AND THE ARCHITECT TO DISCUSS IN DETAIL THE INSTALLATION PROCESS. UPON COMPLETION, A WALK-THROUGH MEETING SHALL BE DONE WITH THE CONTRACT DOCUMENTS AND THE MANUFACTURER'S BEST PRACTICE RECOMMENDATIONS FOR THE WARRANTY SPECIFIED.
DIVISION 08 GLASS
08.01 THE PRIME CONTRACTOR SHALL SET A COORDINATION MEETING WITH THE GLASS SUPPLIER & THE ARCHITECT PRIOR TO FABRICATION & INSTALLATION OF GLAZING TO ASSURE THAT PROPER GLASS TYPE (SAFETY, FIRE RATED, WIRED, SPECIALTY, ETC.) IS PROVIDED IN CORRESPONDING LOCATIONS.
DIVISION 09
09.01 UNLESS FACTORY FINISHED, OR OTHERWISE SPECIFICALLY NOTED ON THE CONSTRUCTION DOCUMENTS, ALL EXPOSED SURFACES (BOTH INTERIOR & EXTERIOR OF THE BUILDING) SHALL BE PAINTED/COATED IN COLORS & TEXTURES AS SELECTED BY THE ARCHITECT/OWNER. NO SURFACES ARE TO BE LEFT UNFINISHED UNLESS SPECIFICALLY NOTED ON THE CONTRACT DOCUMENTS.
DIVISION 10 GYM WALL PADS
10.01 THE CONTRACTOR SHALL PROVIDE & COORDINATE LOCATION, THICKNESS, & COLOR OF WALL PADDING AT GYMNASIUM & MULTI-PURPOSE ROOMS.
FIRE EXTINGUISHERS
10.02 FIRE EXTINGUISHER TYPE, CABINET, QUANTITY, AND LOCATION SHALL BE REVIEWED AND COORDINATED BY THE CONTRACTOR WITH THE BUILDING OFFICIAL AND THE FIRE MARSHAL PRIOR TO THE COMMENCEMENT OF WORK TO INSURE COMPLIANCE WITH LOCAL REGULATIONS.
SPECIALTIES
10.03 THE CONTRACTOR SHALL COORDINATE QUANTITIES, LOCATION & POWER NEEDS FOR ALL FOLDING WALLS, PARTITIONS, PROJECTION SCREENS, WALL CLOCKS, & ANY OTHER SPECIALTY ITEMS.
DIVISION 11 EQUIPMENT
11.01 EQUIPMENT SUPPORT MEMBERS AS WELL AS PLUMBING & ELECTRICAL REQUIREMENTS SHALL BE COORDINATED IN A PRE-INSTALLATION CONFERENCE BY THE GENERAL CONTRACTOR WITH SUPPLIER/INSTALLER, ARCHITECT, & ANY OTHER CONTRACTOR AFFECTED BY THIS WORK.
DIVISION 12 FURNISHINGS
12.01 FURNITURE SHOWN ON THE DRAWINGS IS INDICATED SCHEMATICALLY TO DEMONSTRATE ITS APPROXIMATE LOCATION AND THE INTENDED PURPOSE OF THE SPACE. IT IS NOT AN ACCURATE REPRESENTATION OF ACTUAL SIZE OR OTHER SPECIFICS OF THE OWNER'S NEW OR EXISTING FURNITURE. THE CONTRACTOR(S) SHALL COORDINATE WITH THE OWNER AND/OR FURNITURE SUPPLIER/INSTALLER FOR ACTUAL INFORMATION.
MILLWORK & CASEWORK
12.02 CASEWORK & MILLWORK SHALL BE FULLY COORDINATED BY THE CONTRACTOR FOR SIZE, COLOR, TEXTURE/FINISH, FINAL LOCATION, POWER/DATA, & ALL OTHER REQUIREMENTS. SIGN-OFF BY THE OWNER IS REQUIRED PRIOR TO FABRICATION & INSTALLATION.
DIVISION 14 ELEVATORS & LIFTS
14.01 THE PRIME CONTRACTOR SHALL COORDINATE PRIOR TO FABRICATION ALL SPECIAL REQUIREMENTS SUCH AS KEYING MECHANISM, CAB FINISHES, LIGHTING, ETC. AND GET SIGN-OFF BY THE OWNER.
DIVISION 23 FIRE DAMPERS
23.01 ALL WALLS, FLOORS, CEILINGS, SHAFTS, ETC. THAT ARE DESIGNATED WITH A SMOKE OR FIRE RESISTANCE RATING, OR ARE REQUIRED AS SUCH BY CODE SHALL BE PROVIDED WITH SMOKE OR FIRE DAMPERS WHETHER SHOWN ON THE CONSTRUCTION DOCUMENTS OR NOT. IT SHALL BE THE RESPONSIBILITY FO THE CONTRACTOR(S) AFFECTED TO ASSURE THAT THE SMOKE AND FIRE RESISTANCE INTEGRITY IS MAINTAINED WITH CONTINUITY.
ROOF PENETRATIONS DIVISION 26 ELECTRICAL
23.02 ALL ROOF PENETRATIONS FOR MECHANICAL ITEMS (PIPES, DUCTS, CURBS, ETC.) SHALL BE FULLY COORDINATED BY THE GENERAL CONTRACTOR FOR EXACT LOCATION, SIZE, SUPPORT, ETC. FAILURE TO COORDINATE THESE ITEMS MAY RESULT IN CHANGES IN THE FIELD AT THE EXPENSE OF THE GENERAL CONTRACTOR.
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
Signature & License No.
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
26.01 CONVENIENCE & DATA OUTLETS, WALL SWITCHES, AND FIXTURES SHALL BE COORDINATED WITH THE LOCATION OF FURNITURE, MILLWORK, CASEWORK, ETC. PRIOR TO INSTALLATION. FAILURE TO COORDINATE THESE ITEMS MAY RESULT IN CHANGES IN THE FIELD AT THE EXPENSE OF THE PRIME CONTRACTOR.
PRINCIPAL'S AREA ALTERATIONS OF
NUVIEW ACADEMY ANNEX FOR THE
E.S.C. OF N.J 1690 Stelton Rd, Piscataway, NJ
No.
Date
Issue or Revision
Drawing Title
8/29/2017 10:50:51 AM
GENERAL NOTES Scale
USA Project No.
12" = 1'-0" Drawing Date
2017-070 Drawing No.
08.25.17 Drawn By
Checked By
JS
PC
A-002
LEGEND ROOM NAME NUMBER
CORRIDOR EXISTING OCCUPANT LOAD: 16 OCCUPANTS
STORAGE CLOSET 35 SF
100 FT
DISTANCE TRAVELED (FEET)
21
PROPOSED OCCUPANT LOAD: 15 OCCUPANTS
BOOKSHELVES
ROOM + OCCUPANCY INFORMATION
OCCUPANCY TYPE XXX SF / OCC. SF
PATH OF EGRESS TRAVEL DIRECTION OF EGRESS TRAVEL
BATH 27 SF
usaarchitects.com
ASST. SUPT OFFICE 242 SF
NON-SIMULTANEOUS USE
HEALTH SUITE 362 SF
72 FT
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
1-HOUR RATED PARTITION
CL
6
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
NUMBER OF OCCUPANTS EXITING
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
2-HOUR RATED PARTITION 3-HOUR RATED PARTITION
SECRETARY 71 SF
PARTITION DESIGNED TO RESIST THE PASSAGE OF SMOKE
OFFICE 4 130 SF
12 120 FT 110 FT
BUILDING DATA + INFORMATION SUMMARY:
BOOKSHELVES
3
HALLWAY
USE GROUP(S):
E - EDUCATIONAL (EXISTING)
CONSTRUCTION TYPE:
BOCA 1993 2C, NON COMBUSTIBLE UNPROTECTED (EXISTING) NJIBC 2015 IIB (PROPOSED)
OFFICE 3 110 SF
OFFICE 2 83 SF
5 67 FT 4 62 FT
SPRINKLERED:
YES (EXISTING)
MAXIMUM TRAVEL DISTANCE:
250'
BUILDING AREA:
54,200 SF (EXISTING)
MAXIMUM HEIGHT:
2 STORIES
30 FEET
1 STORIES
38 FEET (ACTUAL)
OFFICE 1 88 SF BUILDING VOLUME:
1,018,509 CU FT (EXISTING)
EXISTING CORRIDORS:
1 HR RATED
4
CHAPTER 8: INTERIOR FINISHES
52 FT
PRINCIPAL 190 SF
EXISTING OCCUPANT LOAD: 22 OCCUPANTS PROPOSED OCCUPANT LOAD: 15 OCCUPANTS
IBC REFERENCE
CLASSIFICATION
FLAME SPREAD
SMOKE DEVELOPMENT
LOCATION 803.9
CLASS A INTERIOR FINISH:
0-25
0-450
CLASS B INTERIOR FINISH:
26-75
0-450
CLASS C INTERIOR FINISH:
76-200
0-450
Signature & License No.
CORRIDORS TABLE 803.9 - INTERIOR WALL AND CEILING FINISH REQUIREMENTS OCCUPANCY
EXISTING OCCUPANT LOAD: 6 OCCUPANTS PROPOSED OCCUPANT LOAD: 4 OCCUPANTS
EXISTING OCCUPANT LOAD: 44 OCCUPANTS
EXIT ENCLOSURES AND PASSAGEWAYS
E
CLASS B
ROOMS AND ENCLOSED SPACES
E B
CLASS C CLASS C
PROPOSED OCCUPANT LOAD: 34 OCCUPANTS OCCUPANT LOAD REDUCED BY 10 OCCUPANTS THEREFORE CURRENT EXITS ARE SUFFICIENT.
REQUIREMENT
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
PRINCIPAL'S AREA ALTERATIONS OF
NUVIEW ACADEMY ANNEX IBC REFERENCE
INTERIOR FLOOR FINISH CLASSIFICATION
804.2
CLASS I INTERIOR FLOOR FINISH/COVERING: CLASS II INTERIOR FLOOR FINISH/COVERING:
FOR THE
0.45 WATTS/CM2 OR GREATER 0.22 WATTS/CM2 OR GREATER
E.S.C. OF N.J
(CLASSIFICATION AS DETERMINED BY NFPA 253) 1690 Stelton Rd, Piscataway, NJ
No.
Date
Issue or Revision
Drawing Title
8/29/2017 10:50:52 AM
1
PARTIAL EGRESS PLANS
PROPOSED OFFICE EGRESS PLAN SCALE: 1/4" = 1'-0"
HATCH INDICATES AREA OF WORK
Scale
USA Project No.
As indicated Drawing Date
KEY PLAN
2017-070 Drawing No.
08.25.17 Drawn By
Checked By
JS
PC
A-011
35'-0 1/2" 6'-7"
6'-0"
21'-4 1/4"
BATH 27 SF
5
A1
5
OFFICE 320 SF
A1
3
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
17'-0"
5'-10 3/4"
STORAGE 35 SF
usaarchitects.com
4
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
22'-3"
34'-4"
28'-9"
2
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
2
OPEN ROOM 450 SF
6'-5"
4
A1
OFFICE 134 SF 3
26'-3"
10'-5"
3
4
8'-6" 35'-1"
SCALE: 1/4" = 1'-0"
6
EXISTING REFLECTED CEILING DEMOLITION PLAN
STRUCTURE ABOVE
SCALE: 1/4" = 1'-0"
CONTINUOUS METAL TOP RUNNER ONE LAYER GYPSUM BOARD, EACH SIDE
SELECTIVE DEMOLITION LEGEND:
SCHEDULED CEILING EXISTING TO REMAIN
X
DEMOLITION SCOPE OF WORK ITEM TYPICAL THROUGHOUT ENTIRE ROOM / AREA
X
DEMOLITION SCOPE OF WORK ITEM AT A SPECIFIC LOCATION
ACOUSTIC INSULATION 6'-0" MIN. EACH SIDE OF WALL. REFER TO CEILING PLAN FOR LOCATIONS
TO BE REMOVED
1
1. CONTRACTOR MUST INSTALL AND MAINTAIN PLASTIC DUST BARRIERS DURING DEMOLITION AND CONSTRUCTION TO PROTECT THE GENERAL PUBLIC FROM DUST AND FUMES. LOCATE PARTITIONS REQUIRED TO PROTECT ADJACENT AREAS AND EQUIPMENT, AND CONTINUE EGRESS THROUGH THE SPACE. CONTRACTOR SHALL PROVIDE TEMPORARY EXIT WAYS AS REQUIRED BY LOCAL CODE ENFORCEMENT OFFICIAL DURING CONSTRUCTION. 2. DO NOT CONSIDER DEMOLITION AND ALTERATION NOTES TO BE ALL INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND ASSESS EACH SPACE AND TO FULFILL THE INTENT OF THE WORK INDICATED BY THE CONTRACT DOCUMENTS. VERIFY ALL DIMENSIONS WITHIN THE CONTRACT LIMITS. BRING DEVIATIONS FROM THE CONTRACT DOCUMENTS TO THE ATTENTION OF THE ARCHITECT. THE EXTENT OF DEMOLITION AND REMOVAL INCLUDES, BUT IS NOT LIMITED TO WORK SHOWN ON THE DRAWINGS. COORDINATE W/ MECHANICAL, ELECTRICAL, PLUMBING & STRUCTURAL DRAWINGS. 3. REMOVE ANY MISCELLANEOUS PROJECTIONS, HANGERS, BOLTS, SCREWS AND NAILS FROM EXISTING SURFACES TO REMAIN. PATCH AND PREPARE SURFACES TO RECEIVE NEW FINISH. 4. PATCH AND REPAIR ALL ADJACENT SURFACES WHICH ARE AFFECTED BY THE DEMOLITION OR REMOVAL OF ACCESSORIES TO THEIR ORIGINAL FORM AND PREPARE FOR NEW FINISH. COORDINATE WITH FINISH DRAWINGS. 5. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR DAILY CLEANUP OF CONSTRUCTION DEBRIS.
8/29/2017 10:50:53 AM
6. BEFORE DEMOLITION BEGINS, CONTRACTOR SHALL COORDINATE SEQUENCE AND SCHEDULES FOR ALL WORK AND RELOCATION OR DISPOSAL OF ALL MATERIALS WITH OWNER. 7. DEMOLITION PLANS ARE DIAGRAMMATIC. PRIOR TO SUBMITTING BID, GENERAL CONTRACTORS SHALL FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND BRING ANY AREAS IN QUESTION TO THE ATTENTION OF THE ARCHITECT.
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
PRINCIPAL'S AREA ALTERATIONS
ACOUSTIC INSULATION WHERE SCHEDULED
REMOVE EXISTING WALL CONSTRUCTION
OF
METAL STUD
AREAS NOT IN CONTRACT
GENERAL DEMOLITION NOTES:
Signature & License No.
MIN.
EXISTING OFFICE DEMOLITION PLAN
1' - 0"
1
2
REMOVE EXISTING DOOR, FRAME AND HARDWARE AND SALVAGE FOR REINSTALLATION
3
REMOVE EXISTING FLOOR FINISH
4
REMOVE EXISTING CEILING, GRID, AND LIGHT FIXTURES AND PROTECT THE DIFFUSERS DURING DEMOLITION.
5
PROTECT FIRE PANELS DURING DEMOLITION
NUVIEW ACADEMY ANNEX
CONTINUOUS METAL BOTTOM RUNNER
FOR THE
SEALANT BOTH SIDES
E.S.C. OF N.J
SUBFLOOR
2
1690 Stelton Rd, Piscataway, NJ
A-WALL DETAIL SCALE: 1 1/2" = 1'-0"
GENERAL PARTITION CONSTRUCTION NOTES 1. WALL TYPES ARE NUMBERED SEQUENTIALLY. IF WALL TYPES SKIP SEQUENCE, THE OMITTED TYPE IS NOT USED. 2. ALL GYPSUM BOARD & CEMENT BOARD TO BE 5/8" THICK, FIRE RATED MATERIAL UTILIZE TYPE "X". UNLESS OTHERWISE NOTED. 3. THE DISTANCE BETWEEN STEEL STUDS SHALL BE 16" O.C. MAXIMUM UNLESS NOTED OTHERWISE. 4. FOR PARTITIONS HIGHER THAN 13'-10", USE 18 GAUGE METAL STUDS @ 16" O.C. 5. PROVIDE CONTROL JOINTS IN GYPSUM BOARD PARTITIONS @ 24' TO 30' MAX. INTERVALS, TYPICAL.
No.
Date
Issue or Revision
Drawing Title
6. PROVIDE METAL BACKING AT WALL-MOUNTED ACCESSORIES, HANDRAILS AND EQUIPMENT. 7. PARTITION DIMENSIONS FOR DOOR FRAME THROATS SHOULD BE CALCULATED BY THE CONTRACTOR. HATCH INDICATES AREA OF WORK
8. HOLD INTERIOR GYPSUM BOARD OFF OF CAST-IN-PLACE CONCRETE 1/2".
DEMOLITION PLANS Scale
USA Project No.
As indicated Drawing Date
KEY PLAN
2017-070 Drawing No.
08.25.17 Drawn By
Checked By
JS
PC
A-050
35'-0 1/2"
13'-1"
21'-4 1/4"
6'-7"
6'-0"
11'-9 1/2"
9'-6 3/4"
263
BATH 27 SF 4' - 6"
ASST. SUPT OFFICE 242 SF
7" CL
2' - 7"
259
usaarchitects.com 261
260
OFFICE 4 130 SF
7'-6" 3'-0"
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
11'-6"
B
BOOKSHELVES
4'-6"
4'-0"
HALLWAY 258
3" TYP.
257
34'-4"
8'-8"
254
A
5'-6"
15'-0"
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
9' - 5"
SECRETARY 71 SF 28'-9"
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
8'-0"
262
9'-0"
STORAGE CLOSET 35 SF
9'-1"
5'-10 3/4"
BOOKSHELVES
4 A-201
256
OFFICE 2 83 SF
3
A-201
10'-11"
OFFICE 3 110 SF
8'-0"
6'-10"
255
OFFICE 1 88 SF
(2) TACK BOARD PANELS
14'-8"
11'-2"
8'-6"
35'-1"
1
PROPOSED OFFICE LAYOUT PLAN
2
SCALE: 1/4" = 1'-0"
PROPOSED REFLECTED CEILING PLAN
Signature & License No.
SCALE: 1/4" = 1'-0" This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
PRINCIPAL'S AREA ALTERATIONS OF
CEILING LEGEND NUVIEW ACADEMY ANNEX
5' - 0"
NEW METAL STUD WALL
OUTLINE OF WINDOW BEYOND
APC-1
GYP-1
2' x 2' APC
COLD FORMED METAL FRAMING
APC-2
EXP
2' x 4' APC
NO CEILING (UNDERSIDE OF DECK EXPOSED)
FOR THE
E.S.C. OF N.J 1690 Stelton Rd, Piscataway, NJ
METAL CHANNEL
6' - 0"
NOT IN CONTRACT
NEW DOOR
A.D.
ACCESS DOOR (COORDINATE LOCATION WITH OWNER)
TACK BOARD 2' x 4' LIGHT FIXTURE 2' x 2' LIGHT FIXTURE 1' x 4' LIGHT FIXTURE
CORNER ALUMINUM FINISH PIECE
MOUNTING STRIPS
WALL MOUNTED LIGHT FIXTURE
3' - 0"
2' - 6"
PENDANT LIGHT FIXTURE - LINEAR
EXISTING MASONRY WALL
No.
RECESSED DOWNLIGHT
HATCH INDICATES AREA OF WORK
8/29/2017 10:50:54 AM
EXHAUST DIFFUSER
3
SCALE: 1/2" = 1'-0"
4
MASONRY CORNER DETAIL SCALE: 1 1/2" = 1'-0"
Issue or Revision
Drawing Title
PENDANT LIGHT FIXTURE SUPPLY DIFFUSER
TACK BOARD MOUNTING DETAIL
Date
SECURITY CAMERA - FACING DOWN
FIRST FLOOR PROPOSED & REFLECTED CEILING PLAN Scale
USA Project No.
As indicated
SECURITY CAMERA
Drawing Date
KEY PLAN
2017-070 Drawing No.
08.25.17 Drawn By
Checked By
JS
PC
A-201
DOOR SCHEDULE Type Mark Mark
Width Height Door Type
254 255 256 257 258 259 260 261 262 263
3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0"
7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0"
Hardware Set
7'-2" 7'-2" 7'-2" 7'-2" 7'-2" 7'-2" 7'-2" 7'-2" 7'-2" 7'-2"
1 1 1 1 1 1 1 2 1 1
EXISTING WD WD WD WD EXISTING EXISTING EXISTING EXISTING EXISTING
Comments
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
USE EXISTING DOOR,FRAME, & HARDWARE FROM DOOR LOCATION B USE EXISTING DOOR,FRAME, & HARDWARE FROM DOOR LOCATION A usaarchitects.com Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
DOOR HARDWARE (MATCH EXISTING)
SINGLE INTERIOR DOOR (ADMINISTRATION)
SINGLE INTERIOR DOOR (OFFICE)
4"
HARDWARE SET #2
7' - 0"
1 1/2 PAIR BUTTS 1 LOCKSET 1 MOP PLATE 1 KICK PLATE 1 BUMPER 1 SET SILENCERS
1 1/2 PAIR BUTTS 1 LOCKSET 1 CLOSER 1 MOP PLATE 1 KICK PLATE 1 BUMPER 1 SET SILENCERS
2" DOOR WIDTH 2"
3' - 0"
HARDWARE SET #1
TYPE A
1
TYPE B
SCALE: 1/4" = 1'-0"
EXISTING MASONRY PARTITION EXISTING MASONRY PARTITION
STUD PARTITION -SEE PLAN FOR TYPE
7/8" METAL FURRING
SEALANT -BOTH SIDES
1"
5/8" GYPSUM BOARD 1/2" ALUMINUM TRANSITION STRIP TO MATCH EXISTING FRAME FINISH. NO EXPOSED FASTENERS
HOLLOW METAL FRAME 1/2"
2"
4"
1/2"
TYPE A1
DOOR & FRAME ELEVATIONS
SEE WAL TYPES FOR PARTITION WIDTH
SEALANT -BOTH SIDES
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
DOOR HEIGHT
A A A A A A A B A A
Frame Height
GROUT FRAME SOLID
Signature & License No.
EXISTING DOOR FRAME
HOLLOW METAL FRAME
HEAD
HEAD
H1
HEAD
H2
PRINCIPAL'S AREA ALTERATIONS
H3
HOLLOW METAL FRAME
HOLLOW METAL FRAME
OF
EXISTING DOOR FRAME
GROUT FRAME SOLID
1/2" 1/2"
FOR THE
E.S.C. OF N.J 1690 Stelton Rd, Piscataway, NJ
1" DYNABOLT ANCHORS
STUD PARTITION -SEE PLAN FOR TYPE EXISTING MASONRY PARTITION
INTERSECTING PARTITION IN SOME LOCATIONS
NUVIEW ACADEMY ANNEX
1/2" ALUMINUM TRANSITION STRIP TO MATCH EXISTING FRAME FINISH. NO EXPOSED FASTENERS
2"
SEALANT -BOTH SIDES
2"MIN.
2"
ANCHOR
SEALANT -BOTH SIDES
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
5/8" GYPSUM BOARD 7/8" METAL FURRING EXISTING MASONRY PARTITION
SEE WALL TYPE FOR PARTITION WIDTH
JAMB
2
J1
DOOR JAMB DETAILS SCALE: 3" = 1'-0"
JAMB
J2
JAMB
J3
No.
Date
Issue or Revision
Drawing Title
8/29/2017 10:50:54 AM
DOOR SCHEDULE + DETAILS Scale
USA Project No.
As indicated Drawing Date
2017-070 Drawing No.
08.25.17 Drawn By
Checked By
JS
PC
A-600
RENOVATIONS OF THE
MAINTENANCE (MTN) BUILDING
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
FOR
BROOKDALE COMMUNITY COLLEGE
usaarchitects.com Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
765 Newman Springs Road, Lincroft, NJ 07738
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
DRAWING LIST ARCHITECTURAL
BUILDING DATA + INFORMATION SUMMARY: USE GROUP(S):
S-2 LOW HAZARD SRR
CONSTRUCTION TYPE:
VB
SPRINKLERED:
N
BUILDING AREA:
2,132 SF
EXISTING HEIGHT:
1 STORIES
REHABILITATION CATAGORY:
RENOVATION (6.3)
OVERALL OCCUPANT LOAD:
7
TITLE SHEET BUILDING CODE INFO. & EGRESS PLAN DEMOLITION PLANS NEW CONSTRUCTION PLANS
A-001 A-010 A-050 A-100
SYMBOL LEGEND NORTH ARROW (NORTH PLAN)
BUILDING CODE INFORMATION APPLICABLE CONSTRUCTION CODES N.J.A.C. 5:23 N.J.A.C. 5:70 N.J.A.C. 5:23-3.14 N.J.A.C. 5:23-3.15 N.J.A.C. 5:23-3.16 N.J.A.C. 5:23-3.17 N.J.A.C. 5:23-3.18 N.J.A.C. 5:23-20 N.J.A.C. 5:23-6 N.J.A.C. 5:23-7
UNIFORM CONSTRUCTION CODE (UCC) UNIFORM FIRE CODE (UFC) AND THE STATE FIRE PREVENTION CODE BUILDING SUBCODE (IBC/2015) PLUMBING SUBCODE (NSPC/2015) ELECTRICAL SUBCODE (NEC/2014) FIRE PROTECTION SUBCODE (SPECIFIC PORTIONS OF THE IBC, NEC, IMC, IFGC) ENERGY SUBCODE (IECC/2015) MECHANICAL SUBCODE (IMC/2015) REHABILITATION SUBCODE BARRIER FREE CODE
A
VIEW NAME SCALE: 1/8" = 1'-0" 1 A-101
Room Name 101 Area
NEW JERSEY ADMINISTRATIVE CODES
1
TITLE MARK
SIM DETAIL MARK
ROOM TAG
SIM
A-101
ELEVATION / SECTION MARK
BL-1
INTERIOR WINDOW TAG
CW2
WINDOW TAG
101
DOOR TAG
P1
WALL TAG
SPOT ELEVATION 1
REVISION TAG
ROOF LOAD INFORMATION DEAD LOAD: ROOF DECK WOOD FRAMING MECH., ELEC. CEILING
+
LIVE LOAD: DESIGN LOAD GROUND SNOW LOAD (Pg)
+
SLAB ON GRADE LIVE LOAD: DESIGN LOAD
2.0 7.0 4.0 0 13.0
P.S.F. P.S.F. P.S.F. P.S.F. P.S.F.
20.0 25.0 45.0
P.S.F. P.S.F. P.S.F.
DESIGN TEAM
Signature & License No.
ARCHITECT
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
RENOVATIONS OF THE
250.0
P.S.F.
USA ARCHITECTS PLANNERS + INTERIOR DESIGNERS, P.A.
LATERAL LOAD INFORMATION
20 NORTH DOUGHTY AVENUE SOMERVILLE, NJ, 08876 PHONE # (908)-722-2300
WIND LOAD: IBC 2015 - ASCE 7.10 BASIC WIND SPEED = 100 MPH IMPORTANCE FACTOR (I) = 0.87, EXPOSURE B INTERNAL PRESSURE COEFF. GCpi = + 0.18
MAINTENANCE (MTN) BUILDING FOR
BROOKDALE COMMUNITY COLLEGE
PROJECT LOCATION: 765 NEWMAN SPRINGS ROAD LINCROFT, NJ 07738
SEISMIC LOADING: IBC 2015 - ASCE 7.10 SEISMIC OCCUPANY CATEGORY - 1 SITE CLASS - D SEISMIC DESIGN CATEGORY - B
765 Newman Springs Road, Lincroft, NJ 07738
SCOPE OF WORK NOTES: 1. THE WORK INCLUDES THE REPAIRS TO AN EXISTING, SINGLE STORY STORAGE BUILDING FOR BROOKDALE COMMUNITY COLLEGE. 2. THE REPAIRS INCLUDE INSTALLATION OF NEW ROOFING, SIDING, NEW OVERHEAD DOOR, & REPLACE DAMAGED EXISTING TRUSSES, POSTS, POST FOOTINGS, GIRTS & PURLINS. SEE REPAIR COST ESTIMATE REPORT DATED JUNE 9, 2016 BY SCHLEIFER ASSOCIATES INC.
08/30/17 08/25/17
Bulletin #2 Bulletin #1
2
08/11/17
Bid Issue
1
06/19/17
Progress Issue
Date
Issue or Revision
No.
3. STRUCTURAL DESIGN & CALCULATIONS SHOULD BE PROVIDED BY THE GC FOR THE NEW TRUSSES & POSTS.
8/30/2017 10:40:14 AM
4 3
Drawing Title
4. STRUCTURAL CALCULATIONS FOR THE BUILDING, IN ACCORDANCE WITH ICC CHAPTER 16, SHOULD BE SUBMITTED FOR REVIEW & APPROVAL PRIOR TO INSTALLATION OF THE TRUSSES & POSTS. THE CALCUATIONS SHOULD DISPLAY THE RAISED SEAL & SIGNATURE OF AN ENGINEER LICENSED IN THE STATE OF NEW JERSEY.
TITLE SHEET Scale
USA Project No.
As indicated Drawing Date
2017-025 Drawing No.
08.25.17
1
LOCATION MAP
Drawn By
Checked By
SCALE: N.T.S.
JS
JM
A-001
01.23 EACH PRIME CONTRACTOR SHALL FIRE STOP/SMOKE PROOF ANY/ALL PENETRATIONS AS REQUIRED TO MAINTAIN THE DESIGNATED FIRE RATING/SMOKE PROOFING OF THE CONSTRUCTION WHETHER EXISTING OR NEW. THE GENERAL CONTRACTOR SHALL ALSO EXTEND RATED CONSTRUCTION TO MAINTAIN CONTINUITY OF SAME THROUGH CONCEALED SPACES (VERTICAL & HORIZONTAL) AS REQUIRED.
CSI DIVISION 00.01 ALL BIDDERS, UPON SUBMITTING BIDS, HEREBY CERTIFY THAT THEY HAVE REVIEWED THE ENTIRE SET OF CONTRACT DOCUMENTS, (CONTRACT DOCUMENTS CONSIST OF A COMPLETE SET OF DRAWINGS AND THE ENTIRE PROJECT MANUAL, INCLUDING ALL DIVISIONS & ANY/ALL ADDENDA) AND ARE AWARE OF, AND AGREE TO MEET THE INTENT OF THE CONTRACT DOCUMENTS WHETHER EXPRESSED OR IMPLIED.
01.24 ANY/ALL EQUIPMENT PROVIDED SHALL BE INSTALLED TO BE COMPLETELY FUNCTIONAL. EACH PIECE OF EQUIPMENT PROVIDED BY A PRIME CONTRACTOR, REQUIRING SERVICE CONNECTIONS BY ANOTHER PRIME CONTRACTOR SHALL BE COORDINATED BY THE GENERAL CONTRACTOR. STARTUP & TESTING OF EQUIPMENT SHALL BE PERFORMED & DOCUMENTED BY FACTORY AUTHORIZED PERSONNEL. 01.25 DETAILS & SECTIONS ON THE DRAWINGS ARE SHOWN AT SPECIFIC LOCATIONS & ARE INTENDED TO SHOW GENERAL REQUIREMENTS THROUGHOUT. DETAILS NOTED "TYPICAL" IMPLY ALL "LIKE-CONDITIONS" ARE TO BE TREATED SIMILARLY.
00.02 PRODUCT MANUFACTURERS IN CONJUNCTION WITH SUBCONTRACTORS AND PRIME CONTRACTOR(S) ARE RESPONSIBLE FOR ALL COMPONENTS AND CALCULATIONS AND/OR CERTIFICATIONS OF THEIR PRODUCT AND FOR PROVIDING COMPLETE SYSTEMS/ASSEMBLIES TO MEET THE DESIGN INTENT OF THE PROJECT.
01.26 WORK NOT INDICATED IN PART OF THE DRAWING, BUT REASONABLY IMPLIED TO BE SIMILAR TO THAT SHOWN AT CORRESPONDING PLACES SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST.
00.03 THE BIDDER/CONTRACTOR IS REQUIRED TO VISIT THE SITE & EXAMINE THE EXISTING CONDITIONS TO HIS COMPLETE SATISFACTION PRIOR TO BIDDING. THE BIDDER/CONTRACTOR SHALL COMPARE THE EXISTING CONDITIONS TO THE DESIGN INTENT OF THE CONTRACT DOCUMENTS & SHALL IMMEDIATELY NOTIFY THE ARCHITECT IN WRITING OF ANY/ALL DISCREPANCIES BEFORE SUBMITTING A BID. FAILURE TO DO SO WILL PLACE THE BURDEN OF RESPONSIBILITY ON THE CONTRACTOR TO PERFORM THE WORK AS INTENDED BY THE CONTRACT DOCUMENTS, AT NO ADDITIONAL COST TO THE OWNER. 01.01 ANY ADDITIONAL INFORMATION THAT IS NOT PART OF THE CONSTRUCTION DOCUMENTS, SUCH AS, BUT NOT LIMITED TO, SOIL REPORT(S), HAZARDOUS MATERIALS REPORT(S), EXISTING DRAWINGS, ETC., ARE INTENDED FOR REFERENCE ONLY AND ARE TO BE USED BY THE CONTRACTOR(S) AT HIS/HER OWN DISCRETION. 01.02 THE INDICATION OF SUBSTRATE & CONFIGURATION OF CONCEALED ITEMS & MATERIALS SHOWN ON THE CONSTRUCTION DOCUMENTS IS FOR GENERAL REFERENCE ONLY. THE CONTRACTOR(S) SHALL NOT BE ENTITLED TO ADDITIONAL COMPENSATION FOR ANY VARIANCE BETWEEN ACTUAL EXISTING CONDITIONS AND THAT REPRESENTED ON THE CONSTRUCTION DOCUMENTS.
CUTTING AND PATCHING
01.28 UNLESS OTHERWISE INDICATED: CUTTING AND PATCHING (EXCEPT FOR FINISHES) IS TO BE PERFORMED BY THE PRIME CONTRACTOR REQUIRING CUTTING AND PATCHING, WHETHER AS SELECTIVE DEMOLITION, OR AS A MEANS OF ACCESSING OR CORRECTING UNSATISFACTORY WORK. PATCHING OF THE SUBSTRATE IS ALSO THE WORK OF THAT PRIME CONTRACTOR, HOWEVER THE PATCHING OF ALL FINISHES EXPOSED TO VIEW IS TO BE DONE BY THE GENERAL CONTRACTOR USING SKILLED TRADESMAN TRAINED FOR PATCHING THE PARTICULAR FINISH INVOLVED.
SUBMITTALS AND SUBSTITUTIONS
01.29 THE PROJECT HAS BEEN DESIGNED TO MEET A CERTAIN PROFESSIONAL STANDARD AND PRODUCTS HAVE BEEN SELECTED TO MEET SUCH STANDARDS. THE PRODUCTS SPECIFIED ARE THE PRODUCTS INTENDED TO BE USED. IN THE EVENT THAT SUBSTITUTIONS ARE SUBMITTED FOR REVIEW, A PROPER COMPARATIVE INFORMATION SHEET SHALL ALSO BE SUBMITTED. ALL REQUESTS FOR SUBSTITUTION SHALL BE MADE WITHIN THE FIRST 90 DAYS AFTER THE CONTRACTOR HAS BEEN AWARDED THE CONTRACT FOR CONSTRUCTION. NO SUBSTITUTION WILL BE CONSIDERED AFTER THIS PERIOD.
01.03 ALL DIMENSIONS INDICATED ON THE CONSTRUCTION DOCUMENTS, OF EXISTING CONDITIONS, ARE APPROXIMATE AND SHALL BE FIELD VERIFIED BY THE CONTRACTOR(S) PRIOR TO SUBMITTING A BID. GENERAL REQUIREMENTS
01.04 THE CONTRACTOR(S) SHALL DISCUSS & VERIFY, WITH ALL GOVERNING AUTHORITIES ALL CODE REQUIREMENTS INDICATED AND/OR REQUIRED FOR THE COMPLETE EXECUTION OF THE WORK AS INTENDED BY THE CONSTRUCTION DOCUMENTS.
01.07 DO NOT SCALE THE DRAWINGS. USE CALCULATED DIMENSIONS ONLY. NOTE THAT NOT ALL DIMENSIONS ARE GIVEN ON THE CONSTRUCTION DOCUMENTS. SOME DIMENSIONS ARE IMPLIED. IF THE CONTRACTOR IS NOT SURE OF A GIVEN DIMENSION, HE/SHE SHALL SUBMIT A REQUEST FOR INFORMATION (R.F.I.) AND/OR SHALL FIELD VERIFY EXISTING DIMENSIONS. 01.08 ALL INFORMATION FOR ALL TRADES CONTAINED WITHIN THE CONSTRUCTION DOCUMENTS SHALL BE USED TOGETHER & IN CONCERT WITH ONE ANOTHER AS A WHOLE BODY OF INFORMATION FOR THE PROJECT. THE DRAWINGS & PROJECT MANUAL ARE COMPLEMENTARY & WHAT IS REQUIRED BY ONE, SHALL BE REQUIRED BY BOTH. NEITHER THE PRIME CONTRACTOR(S) NOR ANY SUBCONTRACTOR(S) SHALL BE RELIEVED OF THE RESPONSIBILITY TO PROVIDE ALL ITEMS REQUIRED BY THE INFORMATION & DESIGN INTENT INDICATED & IMPLIED. IN THE EVENT OF CONFLICTS BETWEEN DOCUMENTS, THE GREATER QUANTITY OR HIGHER QUALITY OF WORK SHALL PREVAIL AND BE PROVIDED.
01.34 THE ARCHITECT WILL TAKE APPROPRIATE ACTION UP TO THREE (3) TIMES FOR EACH ITEM SUBMITTED. SUBMITTALS REQUIRING MORE THAN THREE (3) REVIEWS DUE TO INCORRECT OR INCOMPLETE INFORMATION SHALL BE SUBJECT TO A REVIEW FEE FOR EACH SUBSEQUENT SUBMITTAL. THIS FEE SHALL BE AT THE HOURLY RATE OF THE ARCHITECT & ENGINEER, AND SHALL BE PRE-PAID TO THE ARCHITECT BY THE CONTRACTOR PRIOR TO ANY ADDITIONAL CONSIDERATION. FEES PAID SHALL IN NO WAY CONSTITUTE AN OBLIGATION BY THE ARCHITECT TO APPROVE ANY SUBMITTAL THAT IN HIS/HER OPINION DOES NOT COMPLY WITH THE DESIGN INTENT OF THE CONTRACT DOCUMENTS. FURTHERMORE, ANY SUCH ADDITIONAL REVIEW TIME SHALL NOT BE A BASIS FOR AN EXTENSION OF TIME.
01.09 ALL ITEMS LABELED "EXISTING" ARE EXISTING "TO REMAIN" UNLESS OTHERWISE INDICATED. ITEMS NOT LABELED "EXISTING" ARE TO BE PROVIDED. THE TERM "PROVIDE" SHALL MEAN FURNISH & INSTALL AS IT IS USED THROUGHOUT THE CONTRACT DOCUMENTS.
01.35 IF SUBSTITUTIONS ARE APPROVED, THE CONTRACTOR SHALL NOTIFY ALL OTHER TRADES AFFECTED BY THE SUBSTITUTION & FULLY COORDINATE THE IMPACT ON THE PROJECT. ANY ADDITIONAL COST RESULTING FROM SUBSTITUTIONS SHALL BE PAID BY THE CONTRACTOR PROPOSING THE SUBSTITUTION.
01.10 THE SCOPE OF THIS SINGLE OVERALL PRIME CONTRACT INCLUDES ALL THE WORK AS INDICATED ON THE DRAWINGS AND IN THE PROJECT MANUAL. THE SINGLE OVERALL PRIME CONTRACTOR BEARS SOLE SOURCE RESPONSIBILITY FOR THE DELIVERY OF THE PROJECT TO 100% COMPLETION.
PROJECT COORDINATION (SINGLE OVERALL PRIME CONTRACT)
01.11 THE SINGLE OVERALL PRIME CONTRACTOR BEARS SOLE SOURCE RESPONSIBILITY FOR THE COORDINATION OF THE ACTIVITIES OF ALL SUBCONTRACTORS, SUB-SUBCONTRACTORS, MATERIAL SUPPLIERS, AND ALL PARTIES INVOLVED IN THE EXECUTION OF THE PROJECT. 01.12 ENGINEERING DRAWINGS (STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION, COMMUNICATIONS, AND SECURITY SYSTEM DRAWINGS, ETC.) ARE SHOWN DIAGRAMMATICALLY AND ARE NOT TO SCALE, NOR DO THEY SHOW THE EXACT LOCATION OF THEIR COMPONENTS. THE EXACT LOCATION AND CLEARANCES FOR EACH SUCH SYSTEM OF COMPONENTS SHALL BE COORDINATED BY THE CONTRACTOR(S). ALL PRIME CONTRACTORS, PRIOR TO PURCHASE, FABRICATION, OR INSTALLATION OF THESE ITEMS SHALL PREPARE COORDINATION DRAWINGS SHOWING THE DIFFERENT TRADES BY COLORS AND SHALL CONDUCT A COORDINATION MEETING WITH ALL OTHER CONTRACTOR(S) AFFECTED FOR A TOTAL UNDERSTANDING OF THE DESIGN INTENT. THE ARCHITECTS AND THE ENGINEERS(S) SHALL BE INVITED TO ATTEND THIS MEETING AND OFFER INPUT PRIOR TO ANY WORK BEING FABRICATED OR INSTALLED. 01.13 THE CONTRACTOR SHALL PROVIDE ALL MATERIAL, LABOR, SERVICES, ETC. TO COMPLETE THE ENTIRE WORK IN A MANNER ACCEPTABLE TO THE OWNER AND THE ARCHITECT. IT IS UNDERSTOOD THAT NOT EVERY DETAIL OR DIMENSION IS SHOWN IN THE CONTRACT DOCUMENTS, NOR ARE THEY NECESSARY FOR THE CONTRACTOR(S) TO PROVIDE A QUALITY PRODUCT. THE CONTRACTOR SHALL SUBMIT A REQUEST FOR INFORMATION (R.F.I.) IF NEEDED TO CLARIFY THE INTENT OF ANY DETAIL OR OTHER INFORMATION. HOWEVER, SUCH REQUEST FOR INFORMATION SHALL NOT CONSTITUTE A CHANGE IN THE SCHEDULE, OR IN THE CONTRACT AMOUNT. NO WORK SHOULD BE INSTALLED IF THE CONTRACTOR IS UNSURE OF THE DESIGN INTENT. INSTALLATION OF ANY WORK THAT DOES NOT COMPLY WITH THE DESIGN INTENT, AS DETERMINED BY THE ARCHITECT, SHALL BE SUBJECT TO REPLACEMENT AT THE CONTRACTOR'S EXPENSE.
STANDARD WARRANTY
01.36 EACH PRIME CONTRACTOR SHALL PROVIDE, AS PART OF ITS REQUIRED CLOSE-OUT DOCUMENTS, A STANDARD WARRANTY COVERING ALL MATERIALS, PRODUCTS, AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE ARCHITECT. THIS STANDARD WARRANTY IS A BASIC REQUIREMENT OF EACH PRIME CONTRACT AND SHALL BE EXTENDED BY SPECIFIC WARRANTY REQUIREMENTS OF THE VARIOUS PRODUCTS AND SYSTEMS AS INDICATED THROUGHOUT THE CONTRACT DOCUMENTS.
DIVISION 02 DEMOLITION
02.01 THE ACTUAL SCOPE OF DEMOLITION SHALL NOT BE LIMITED TO WHAT IS SPECIFICALLY INDICATED ON THE DRAWINGS OR WITHIN THE PROJECT MANUAL, BUT SHALL INCLUDE ANY AND ALL COMPLETE OR SELECTIVE DEMOLITION AS MAY BE NECESSARY TO ACCOMPLISH THE INTENDED CONSTRUCTION. THIS APPLIES TO THE WORK OF ALL TRADES.
EXTERIOR FERROUS METALS
05.02 ALL FERROUS METAL USED ON OR EXPOSED TO THE EXTERIOR OF THE BUILDING INCLUDING BUT NOT LIMITED TO: STRUCTURAL AND MISCELLANEOUS FRAMING, WINDOWS, DOORS AND FRAMES, HANDRAILS, LINTELS, ETC. SHALL BE HOTDIPPED AND GALVANIZED PRIOR TO INSTALLATION AND PAINTING.
EXTERIOR WOOD
06.02 ALL WOOD FRAMING LUMBER AND BLOCKING EXPOSED TO THE ELEMENTS OR USED IN CONTACT WITH MASONRY, CONCRETE, AND/OR ROOFING SHALL BE PRESSURE TREATED FOR RESISTANCE TO DETERIORATION FROM MOISTURE. 07.01 ANY AND ALL CONSTRUCTION JOINTS INCLUDING JOINTS BETWEEN DIFFERENT ITEMS AND MATERIALS, JOINTS SURROUNDING PENETRATIONS THROUGH MATERIALS, AND CRACKS WITHIN MATERIALS, ECT., WHETHER ON THE INTERIOR OR EXTERIOR OF THE BUILDING, SHALL BE FILLED WITH AN APPROPRIATE SEALANT AS REQUIRED. ON THE INTERIOR OF THE BUILDING, SAID SEALANT SHALL BE PAINTABLE. ON THE EXTERIOR OF THE BUILDING, SAID SEALANT SHALL BE WEATHERPROOF AND IN A COLOR SELECTED BY THE ARCHITECT.
DIVISION 07 SEALANTS
ROOFING
01.15 ALL UNUSED MATERIAL AND DEBRIS SHALL BE COMPLETELY REMOVED FROM THE SITE AND LEGALLY DISPOSED OF. NO ON-SITE STORAGE, BURNING, OR BURIAL OF DEBRIS SHALL BE PERMITTED. THE CONSTRUCTION SITE SHALL BE KEPT IN A CLEAN AND SAFE MANNER, INCLUDING, BUT NOT LIMITED TO DAILY BROOM CLEANING THROUGHOUT THE DURATION OF THE CONSTRUCTION PROJECT.
ROOF PENETRATIONS
ENERGY CODE REVIEW ASHRAE 90.1-2013 5.5.2.-BUILDING IS NOT CONDITIONED. UNCONDITIONED BUILDING TO COMPLY WITH REQUIREMENTS OF SEMI-HEATED SPACE. 5.1.3.-ENVELOPE SECTION 5 REQUIREMENTS N/R: EXCEPTION 4 + 5
3 PROVIDE DUAL HEAD EMERGENCY EXIT REMOTE HEAD.
PROVIDE NEW LED EXIT SIGN/EMERGENCY LIGHT COMBO ABOVE EXIT DOOR: 6.28(f)
TD: 57'-10"(>39'-1")
EXIT SINGLE EXIT: 6.28(a)
Signature & License No.
23.02 ALL ROOF PENETRATIONS FOR MECHANICAL ITEMS (PIPES, DUCTS, CURBS, ETC.) SHALL BE FULLY COORDINATED BY THE GENERAL CONTRACTOR FOR EXACT LOCATION, SIZE, SUPPORT, ETC. FAILURE TO COORDINATE THESE ITEMS MAY RESULT IN CHANGES IN THE FIELD AT THE EXPENSE OF THE GENERAL CONTRACTOR.
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
01.16 CONSTRUCTION ACCESS ROADS, CURB CUTS, SOIL EROSION CONTROL, & THE LOCATION OF ALL TEMPORARY FACILITIES (INCLUDING POWER, TELEPHONE, WATER, WASTE, ETC.) SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR (UNLESS OTHERWISE NOTED), & SHALL BE COORDINATED WITH UTILITY COMPANIES, MUNICIPAL AUTHORITIES, ETC. AS REQUIRED. 01.17 ALL MATERIALS AND PRODUCTS SHALL BE PROTECTED AND PROPERLY STORED AS PER MANUFACTURER'S RECOMMENDATION. ALL MATERIALS AND PRODUCTS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S CURRENT PRINTED RECOMMENDATIONS TO MAINTAIN THE PROPER WARRANTIES. 01.18 PRIOR TO THE INSTALLATION OF ALL MAJOR BUILDING COMPONENTS, THE PRIME CONTRACTOR(S) SHALL CONDUCT A PREINSTALLATION AND COORDINATION MEETING WITH THE MANUFACTURER'S REPRESENTATIVE. INCLUDED IN THE MEETING SHALL BE ANY SUBCONTRACTOR AND PRODUCT MANUFACTURER AFFECTED BY THE SPECIFIC WORK. FAILURE OF THE PRIME CONTRACTOR(S) TO CONDUCT SUCH A MEETING, AND PROPERLY COORDINATE THE PROCESS, SHALL PLACE THE BURDEN FOR ANY & ALL PROBLEMS, RESULTING FROM SAID INSTALLATION, UPON THE PRIME CONTRACTOR(S) RESPONSIBLE FOR THAT PORTION OF THE WORK. 01.19 LONG 01.20LEAD MISCELLANEOUS ITEMS SHALL BE WOOD, IDENTIFIED COLD FORMED, BY THE CONTRACTOR(S) OR ROLLED STEEL WITH SHAPES, NOTIFICATION WHETHER TO BLOCKING THE ARCHITECT OR SUB-FRAMING IN A TIMELY WHICH MANNER. ARE REQUIRED FAILURE BY FOR THE THE CONTRACTOR(S) INSTALLATION OF TOOTHER OBTAINITEMS SUBMITTAL NECESSARY APPROVALS, FOR A AND COMPLETE TO ORDER PACKAGE LONG SHALL LEAD ITEMS, BE PROVIDED SO AS NOT WHETHER THE DELAY OR NOT THESPECIFICALLY PROGRESS INDICATED OF THE WORK, ON THE WILL DRAWINGS. NOT JUSTIFY AN EXTENSION OF THE SCHEDULE FOR COMPLETION, NOR WILL IT CAUSE PRODUCT SUBSTITUTIONS IN ORDER TO MEET THE SCHEDULE.
EXECUTION REQUIREMENTS
FE
07.02 PRIOR TO THE START OF ROOF WORK, THE CONTRACTOR IS REQUIRED TO CONDUCT A PRE-INSTALLATION CONFERENCE WITH THE ROOFING MANUFACTURER, THE ROOF INSTALLER, OTHER AFFECTED CONTRACTORS, AND THE ARCHITECT TO DISCUSS IN DETAIL THE INSTALLATION PROCESS. UPON COMPLETION, A WALK-THROUGH MEETING SHALL BE DONE WITH THE CONTRACT DOCUMENTS AND THE MANUFACTURER'S BEST PRACTICE RECOMMENDATIONS FOR THE WARRANTY SPECIFIED.
01.14 ALL CONSTRUCTION, EQUIPMENT, CONTENTS, ETC. SHALL BE PROTECTED BY EACH CONTRACTOR DURING THE ENTIRE PERFORMANCE OF THE WORK. AREAS DISTURBED OR DAMAGED BY THE CONTRACTOR SHALL BE COMPLETELY RESTORED, REPAIRED, OR REPLACED BY THE CONTRACTOR. TO THE OWNER'S COMPLETE SATISFACTION AT NO ADDITIONAL COST.
01.21 DIMENSIONS GIVEN FOR MASONRY OPENINGS ARE NOMINAL. GENERAL CONTRACTOR(S) SHALL COORDINATE THE FABRICATION OF DOOR, WINDOW, AND VISION PANEL FRAMES AND OTHER ITEMS TO BE INSTALLED IN MASONRY TO ACCOMMODATE ACTUAL DIMENSIONS VERIFIED IN THE FIELD WITH AND WITHOUT MORTAR JOINTS AS THEY OCCUR. 01.22 EACH PRIME CONTRACTOR SHALL PROVIDE ALL NECESSARY SHORING & BRACING TO SUPPORT EXISTING OR NEW CONSTRUCTION NOT FULLY SET UNTIL PERMANENT SUPPORTS ARE ERECTED. TAKE ALL NECESSARY MEASURES TO PREVENT COLLAPSE OF ANY ELEMENT OF NEW OR EXISTING CONSTRUCTION.
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
EXISTING FIRE EXTINGUISHER TO REMAIN
01.32 SHOP DRAWINGS SHALL BE REVIEWED BY THE ARCHITECT/ENGINEER FOR BASIC CONFORMANCE TO THE DESIGN INTENT ONLY AFTER PRIOR APPROVAL BY THE RESPONSIBLE PRIME CONTRACTOR. THIS REVIEW DOES NOT RELIEVE THE CONTRACTOR OR HIS SUB-CONTRACTOR(S) OF RESPONSIBILITY FOR FULL COMPLIANCE WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DIMENSIONS & CLEARANCES TO BE CONFIRMED & CORRELATED AT THE JOB SITE, FOR MATERIALS QUANTITIES & PROPER FABRICATION, FOR PROPER MEANS & METHODS, FOR PROPER SEQUENCES OF CONSTRUCTION, FOR THE PROPER COORDINATION WITH OTHER TRADES, AND FOR PROVIDING SAFE AND SATISFACTORY CONSTRUCTION OPERATIONS. 01.33 EACH CONTRACTOR IS ADVISED THAT CERTAIN COLOR SCHEDULE SELECTIONS MAY HAVE PREVIOUSLY BEEN MADE, REVIEWED, AND APPROVED BY THE OWNER & RETURNED TO THE CONTRACTOR FOR EXECUTION. ALL CONTRACTORS SHALL TAKE NOTE & HEREAFTER STRONGLY BE ADVISED THAT MATERIAL SUBSTITUTIONS SUBMITTED LATER MAY BE REQUIRED TO BE PROVIDED WITH CUSTOM COLORS, TEXTURES, & FINISHES BASED UPON SELECTIONS PREVIOUSLY APPROVED. MATERIAL SUBSTITUTIONS ARE SUBJECT TO REJECTION SOLELY ON APPEARANCE.
SUMMARY WORK (SINGLE OVERALL PRIME CONTRACT)
PRODUCT REQUIREMENTS
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
01.31 THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS SUFFICIENTLY IN ADVANCE OF THE WORK TO ALLOW PROPER TIME FOR REVIEW. MATERIALS SHALL NOT BE FABRICATED OR DELIVERED TO THE SITE BEFORE THE SHOP DRAWINGS HAVE BEEN APPROVED.
01.06 THE CONTRACTOR(S) SHALL PROVIDE PROTECTION FOR THE PUBLIC, OWNER'S STAFF, AND CONSTRUCTION WORKERS IN AND AROUND THE CONSTRUCTION AREA & ADJACENT PROPERTY. ADEQUATE BARRIERS & SIGNAGE SHALL BE PROVIDED TO EXERCISE CONTROL OF SAFE INGRESS & EGRESS OF PREMISES. FIRE EXITS SHALL NOT BE BLOCKED. PROPER SITE SECURITY DURING WORKING & OFF-HOURS SHALL BE MAINTAINED. BARRICADE ALL UNSAFE OR POTENTIALLY DANGEROUS CONDITIONS. THE CONTRACTOR(S) SHALL FOLLOW O.S.H.A. STANDARDS DURING THE COURSE OF THE PROJECT.
TEMPORARY FACILITIES & ACCESS
usaarchitects.com
01.30 THE PRIME CONTRACTOR SHALL PROVIDE ALL REQUIRED SCHEDULES, SUCH AS BUT NO LIMITED TO: SUBMISSION SCHEDULE, CONSTRUCTION SCHEDULE, & SCHEDULE OF VALUES PRIOR TO SUBMISSION OF THE FIRST APPLICATION FOR PAYMENT. NO APPLICATION FOR PAYMENT WILL BE APPROVED BY THE ARCHITECT UNTIL THIS PREREQUISITE IS COMPLIED WITH PROPERLY.
01.05 THE CONTRACTOR(S) SHALL COMPLY WITH ALL FEDERAL, STATE, AND LOCAL CODES AND ORDINANCES HAVING JURISDICTION OVER THE PROJECT. THE CONTRACTOR(S) SHALL OBTAIN PERMITS & GIVE NOTICES TO SUCH AGENCIES IN AMPLE TIME FOR OFFICIALS TO CONDUCT INSPECTIONS AND OBTAIN TIMELY APPROVALS. FAILURE TO COMPLY WILL SOLELY BE THE RESPONSIBILITY OF THE CONTRACTOR(S).
QUALITY REQUIREMENTS
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
RENOVATIONS 8'-3 ".
DIVISION 01 AVAILABLE INFORMATION
01.27 MINOR DETAILS OR INCIDENTAL ITEMS NOT USUALLY SHOWN OR SPECIFIED, BUT NECESSARY FOR THE PROPER & COMPLETE EXECUTION OF ANY PART OF THE WORK SHALL BE INCLUDED AS IF THEY WERE SPECIFICALLY INDICATED IN THE CONSTRUCTION DOCUMENTS.
LEGEND ROOM NAME NUMBER OCCUPANCY TYPE XXX SF / OCC. SF 100 FT 21
OF THE
BU (78 ILDING '-3" /2= DIAG 39'1") ONAL :7
DIVISION 00 PROCUREMENT
ROOM + OCCUPANCY INFORMATION
DISTANCE TRAVELED (FEET)
MAINTENANCE (MTN) BUILDING FOR
BROOKDALE COMMUNITY COLLEGE
NUMBER OF OCCUPANTS EXITING
765 Newman Springs Road, Lincroft, NJ 07738
PATH OF EGRESS TRAVEL DIRECTION OF EGRESS TRAVEL
NON-SIMULTANEOUS USE
1-HOUR RATED PARTITION
EXISTING BUILDING 2-HOUR RATED PARTITION 3-HOUR RATED PARTITION PARTITION DESIGNED TO RESIST THE PASSAGE OF SMOKE
1
CODE/EGRESS PLAN SCALE: 3/16" = 1'-0"
3
08.25.17
BULLETIN #1
No.
Date
Issue or Revision
Drawing Title
8/30/2017 10:40:17 AM
BUILDING CODE INFO. & EGRESS PLAN Scale
USA Project No.
As indicated Drawing Date
2017-025 Drawing No.
08.25.17 Drawn By
Checked By
JS
JM
A-010
30'-3" 3 A-050
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
EXISTING TO REMAIN
SELECTIVE DEMOLITION LEGEND: TO BE REMOVED
X
EXISTING STORAGE STRUCTURE ABOVE TO REMAIN & BE PROTECTED
DEMOLITION SCOPE OF WORK ITEM TYPICAL THROUGHOUT ENTIRE ROOM / AREA
usaarchitects.com
5 AREAS NOT IN CONTRACT
X
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
DEMOLITION SCOPE OF WORK ITEM AT A SPECIFIC LOCATION 4
1
REMOVE EXISTING TRUSS -4 TOTAL INCLUDING PURLINS.
2
REMOVE EXISTING POST & FOOTER. REMOVE SECTION OF SLAB FOR FOOTER INSTALL.
3
REMOVE EXISTING OVERHEAD DOOR, GUIDES, & HANGERS.
4
IN THIS AREA OF DAMAGE, REMOVE ALL EXISTING GIRTS BACK TO NEAREST WOOD COLUMN.
GENERAL DEMOLITION NOTES:
2. DO NOT CONSIDER DEMOLITION AND ALTERATION NOTES TO BE ALL INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND ASSESS EACH SPACE AND TO FULFILL THE INTENT OF THE WORK INDICATED BY THE CONTRACT DOCUMENTS. VERIFY ALL DIMENSIONS WITHIN THE CONTRACT LIMITS. BRING DEVIATIONS FROM THE CONTRACT DOCUMENTS TO THE ATTENTION OF THE ARCHITECT. THE EXTENT OF DEMOLITION AND REMOVAL INCLUDES, BUT IS NOT LIMITED TO WORK SHOWN ON THE DRAWINGS. 3. REMOVE ANY MISCELLANEOUS PROJECTIONS, HANGERS, BOLTS, SCREWS AND NAILS FROM EXISTING SURFACES TO REMAIN. PATCH AND PREPARE SURFACES TO RECEIVE NEW FINISH. 4. PATCH AND REPAIR ALL ADJACENT SURFACES WHICH ARE AFFECTED BY THE DEMOLITION OR REMOVAL OF ACCESSORIES TO THEIR ORIGINAL FORM AND PREPARE FOR NEW FINISH. COORDINATE WITH FINISH DRAWINGS.
5 6
SLOPE
3 5 A-050
REMOVE EXISTING WALL PANELS, TRIM , & INSULATION BOARD DOWN TO THE EXISTING STRUCTURE. REMOVE EXISTING BARN DOOR HARDWARE. PROVIDE TEMPORARY STRUCTURE SUPPORT THROUGHOUT, DURING TRANSLUCENT PANEL REMOVAL. EXISTING DOOR TO REMAIN.
SALVAGE VENT FOR RE-INSTALLATION
4
7
5. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR DAILY CLEANUP OF CONSTRUCTION DEBRIS.
6
SLOPE
72'-2"
1. CONTRACTOR MUST INSTALL AND MAINTAIN PLASTIC DUST BARRIERS DURING DEMOLITION AND CONSTRUCTION TO PROTECT THE GENERAL PUBLIC FROM DUST AND FUMES. LOCATE PARTITIONS REQUIRED TO PROTECT ADJACENT AREAS AND EQUIPMENT, AND CONTINUE EGRESS THROUGH THE SPACE. CONTRACTOR SHALL PROVIDE TEMPORARY EXIT WAYS AS REQUIRED BY LOCAL CODE ENFORCEMENT OFFICIAL DURING CONSTRUCTION.
4 A-050
6
EXISTING ELECTRICAL CONDUITS, LIGHT FIXTURES & DEVICES ON TRUSSES TO BE REMOVED.
6. BEFORE DEMOLITION BEGINS, CONTRACTOR SHALL COORDINATE SEQUENCE AND SCHEDULES FOR ALL WORK AND RELOCATION OR DISPOSAL OF ALL MATERIALS WITH OWNER.
3 Roof +16' - 8"
7. DEMOLITION PLANS ARE DIAGRAMMATIC. PRIOR TO SUBMITTING BID, GENERAL CONTRACTORS SHALL FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND BRING ANY AREAS IN QUESTION TO THE ATTENTION OF THE ARCHITECT.
SECOND FLOOR PLAN +11' - 3"
5
4 REMOVE ALL ROOF PANELS & INSULATION BOARD DOWN TO EXISTING STRUCTURE, THIS SLOPE ONLY & RIDGE CAP
4
4
3
2
1 7
FIRST FLOOR PLAN +0' - 0"
REMOVE ROOFING & INSULATION THIS SIDE ONLY
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
3
NORTH ELEVATION-DEMO
Signature & License No.
SCALE: 1/8" = 1'-0" This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
Roof +16' - 8"
RENOVATIONS
EXISTING STORAGE STRUCTURE ABOVE TO REMAIN & BE PROTECTED
SECOND FLOOR PLAN +11' - 3"
OF THE
MAINTENANCE (MTN) BUILDING
5
FOR
(NORTH PLAN) FIRST FLOOR PLAN +0' - 0"
4
EXISTING ROOF TO REMAIN NO WORK
EAST ELEVATION-DEMO
BROOKDALE COMMUNITY COLLEGE
EXISTING BUILDING TO REMAIN NO WORK (PRINT SHOP)
765 Newman Springs Road, Lincroft, NJ 07738
SCALE: 1/8" = 1'-0"
1
ROOF DEMOLITION PLAN SCALE: 3/16" = 1'-0"
2
GROUND FLOOR DEMOLITION PLAN SCALE: 3/16" = 1'-0" 4
Roof +16' - 8" SECOND FLOOR PLAN +11' - 3"
6
5
ELECTRICAL NOTE: EXISTING CONDUIT FEEDS TO 225A PANEL IN PRINT SHOP. GC TO COORDINATE W/ OWNER MIN. SHUTDOWN OF POWER REQUIRED FOR EXISTING DISCONNECT & NEW RECONNECT AT PRINT SHOP.
4 3
08.30.17 08.25.17
BULLETIN #2 BULLETIN #1
No.
Date
Issue or Revision
Drawing Title
3
8/30/2017 10:40:18 AM
FIRST FLOOR PLAN +0' - 0"
5
WEST ELEVATION-DEMO SCALE: 1/8" = 1'-0"
DEMOLITION PLANS
6 Scale
USA Project No.
As indicated Drawing Date
2017-025 Drawing No.
08.25.17 Drawn By
Checked By
JS
JM
A-050
METAL SIDING NEW EAVE TRIM
INSULATION
Roof +16' - 8"
6X6 WOOD POST
2X4 GIRTS
usaarchitects.com
CONSTRUCTION JOINT
3
FIRST FLOOR PLAN +0' - 0"
FIRST FLOOR PLAN +0' - 0"
6"
GRADE
3
TYP.
1'-0" 3"
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
SECOND FLOOR PLAN +11' - 3"
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
NORTH ELEVATION-NC
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
SCALE: 1/8" = 1'-0" 30'-3"
3 A-100
5'-0"
#3 TIES @ 12" O.C.
(6) #5 VERTICALS
8"
B.O. FOOTER -5' - 0"
3'-0"
8
Footing Detail @ New Post SCALE: 1/2" = 1'-0"
Roof +16' - 8" SECOND FLOOR PLAN +11' - 3"
SLOPE
4
SLOPE
NEW SOFFIT TRIM
RUN NEW CONDUIT WIRING FROM EXISTING BOX, ON THIS WALL, TO PRINT SHOP PANEL
FIRST FLOOR PLAN +0' - 0"
4
4
4
EAST ELEVATION-NC
NEW WALL PANELS AT THIS LOCATION ONLY - SEE PLANS
REINSTALL EXISTING SURFACE MOUNTED LIGHTS AT BOTTOM OF TRUSSES IN SAME LOCATIONS
NEW RIDGE TRIM
SCALE: 1/8" = 1'-0" NEW DOOR TRIM, TYP. Roof +16' - 8"
5
4
A-100
A-100
Signature & License No.
72'-2"
SECOND FLOOR PLAN +11' - 3" REINSTALL EXISTING RIDGE VENT
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
NEW OVERHEAD DOOR
RENOVATIONS 4
5
WEST ELEVATION-NC
FIRST FLOOR PLAN +0' - 0"
NEW TRUSS - 4 TOTAL
OF THE
3
DOOR TO MATCH EXISTING STYLE
NEW ROOF PANELS ON NEW INSULATION PANELS ON EXISTING & NEW STRUCTURE
REINSTALL EXISTING TRUSS PLAQUE IN THIS LOCATION
SCALE: 1/8" = 1'-0"
MAINTENANCE (MTN) BUILDING FOR
BROOKDALE COMMUNITY COLLEGE
Roof +16' - 8" NEW 6X6 PRESSURE TREATED POSTS & FOOTINGS.
SECOND FLOOR PLAN +11' - 3"
765 Newman Springs Road, Lincroft, NJ 07738
4 NEW OVERHEAD DOOR
2'-5 1/4" VIF
NEW WOOD TRUSSE & POST BRACING - 3 TOTAL
3
FIRST FLOOR PLAN +0' - 0"
6
CROSS SECTION
PROVIDE NEW 2X4 GIRTS, 2X6 PURLINS IN THIS AREA
NEW 3X10 TRANSLUCENT PANEL ROOF CENTERED ON OVERHEAD DOOR.
SCALE: 1/8" = 1'-0"
VIF
4'-0"
NEW 2-2X12 WOOD HEADER
NEW SLAB INFILL & NEW POST, TYP.
Roof +16' - 8"
8/30/2017 10:40:21 AM
SECOND FLOOR PLAN +11' - 3"
4 3
08.30.17 08.25.17
BULLETIN #2 BULLETIN #1
No.
Date
Issue or Revision
Drawing Title
EXISTING ROOF
FIRST FLOOR PLAN +0' - 0"
7
8--A-100
NEW CONSTRUCTION PLANS
EXISTING BUILDING (PRINT SHOP) Scale
USA Project No.
As indicated
LONGITUDINAL SECTION
Drawing Date
SCALE: 1/8" = 1'-0"
1
ROOF PLAN-NC SCALE: 3/16" = 1'-0"
2
2017-025 Drawing No.
FIRST FLOOR PLAN-NC
08.25.17
SCALE: 3/16" = 1'-0"
Drawn By
Checked By
JS
JM
A-100
ALTERATIONS AT
LOG COLLEGE MIDDLE SCHOOL
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
FOR THE
CENTENNIAL SCHOOL DISTRICT
usaarchitects.com Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
CSI DIVISION
DRAWING LIST
00.01 ALL BIDDERS, UPON SUBMITTING BIDS, HEREBY CERTIFY THAT THEY HAVE REVIEWED THE ENTIRE SET OF CONTRACT DOCUMENTS, (CONTRACT DOCUMENTS CONSIST OF A COMPLETE SET OF DRAWINGS AND THE ENTIRE PROJECT MANUAL, INCLUDING ALL DIVISIONS & ANY/ALL ADDENDA) AND ARE AWARE OF, AND AGREE TO MEET THE INTENT OF THE CONTRACT DOCUMENTS WHETHER EXPRESSED OR IMPLIED.
PENNSYLVANIA ADMINISTRATIVE CODES ARCHITECTURAL
00.02 PRODUCT MANUFACTURERS IN CONJUNCTION WITH SUBCONTRACTORS AND PRIME CONTRACTOR(S) ARE RESPONSIBLE FOR ALL COMPONENTS AND CALCULATIONS AND/OR CERTIFICATIONS OF THEIR PRODUCT AND FOR PROVIDING COMPLETE SYSTEMS/ASSEMBLIES TO MEET THE DESIGN INTENT OF THE PROJECT. 00.03 THE BIDDER/CONTRACTOR IS REQUIRED TO VISIT THE SITE & EXAMINE THE EXISTING CONDITIONS TO HIS COMPLETE SATISFACTION PRIOR TO BIDDING. THE BIDDER/CONTRACTOR SHALL COMPARE THE EXISTING CONDITIONS TO THE DESIGN INTENT OF THE CONTRACT DOCUMENTS & SHALL IMMEDIATELY NOTIFY THE ARCHITECT + REYNOLD IN WRITING OF ANY/ALL DISCREPANCIES BEFORE SUBMITTING A BID. FAILURE TO DO SO WILL PLACE THE BURDEN OF RESPONSIBILITY ON THE CONTRACTOR TO PERFORM THE WORK AS INTENDED BY THE CONTRACT DOCUMENTS, AT NO ADDITIONAL COST TO THE OWNER. DIVISION 01 AVAILABLE INFORMATION
01.02 THE INDICATION OF SUBSTRATE & CONFIGURATION OF CONCEALED ITEMS & MATERIALS SHOWN ON THE CONSTRUCTION DOCUMENTS IS FOR GENERAL REFERENCE ONLY. THE CONTRACTOR(S) SHALL NOT BE ENTITLED TO ADDITIONAL COMPENSATION FOR ANY VARIANCE BETWEEN ACTUAL EXISTING CONDITIONS AND THAT REPRESENTED ON THE CONSTRUCTION DOCUMENTS. 01.03 ALL DIMENSIONS INDICATED ON THE CONSTRUCTION DOCUMENTS, OF EXISTING CONDITIONS, ARE APPROXIMATE AND SHALL BE FIELD VERIFIED BY THE CONTRACTOR(S) PRIOR TO SUBMITTING A BID.
GENERAL REQUIREMENTS
01.04 THE SUBCONTRACTOR(S) SHALL DISCUSS & VERIFY, WITH ALL GOVERNING AUTHORITIES ALL CODE REQUIREMENTS INDICATED AND/OR REQUIRED FOR THE COMPLETE EXECUTION OF THE WORK AS INTENDED BY THE CONSTRUCTION DOCUMENTS. 01.05 THE SUBCONTRACTOR(S) SHALL COMPLY WITH ALL FEDERAL, STATE, AND LOCAL CODES AND ORDINANCES HAVING JURISDICTION OVER THE PROJECT. REYNOLDS WILL SECURE THE GENERAL BUILDING PERMIT. SUB-CONTRACTORS TO PROVIDE AND PAY FOR INDIVIDUAL PERMITS REQUIRED BY THE LOCAL AHJ. 01.06 THE SUBCONTRACTOR(S) SHALL PROVIDE PROTECTION FOR THE PUBLIC, OWNER'S STAFF, AND CONSTRUCTION WORKERS IN AND AROUND THE CONSTRUCTION AREA & ADJACENT PROPERTY. ADEQUATE BARRIERS & SIGNAGE SHALL BE PROVIDED TO EXERCISE CONTROL OF SAFE INGRESS & EGRESS OF PREMISES. FIRE EXITS SHALL NOT BE BLOCKED. PROPER SITE SECURITY DURING WORKING & OFF-HOURS SHALL BE MAINTAINED. BARRICADE ALL UNSAFE OR POTENTIALLY DANGEROUS CONDITIONS. THE CONTRACTOR(S) SHALL FOLLOW O.S.H.A. STANDARDS DURING THE COURSE OF THE PROJECT. 01.07 DO NOT SCALE THE DRAWINGS. USE CALCULATED DIMENSIONS ONLY. NOTE THAT NOT ALL DIMENSIONS ARE GIVEN ON THE CONSTRUCTION DOCUMENTS. SOME DIMENSIONS ARE IMPLIED. IF THE CONTRACTOR IS NOT SURE OF A GIVEN DIMENSION, HE/SHE SHALL SUBMIT A REQUEST FOR INFORMATION (R.F.I.) AND/OR SHALL FIELD VERIFY EXISTING DIMENSIONS. 01.08 ALL INFORMATION FOR ALL TRADES CONTAINED WITHIN THE CONSTRUCTION DOCUMENTS SHALL BE USED TOGETHER & IN CONCERT WITH ONE ANOTHER AS A WHOLE BODY OF INFORMATION FOR THE PROJECT. THE DRAWINGS & PROJECT MANUAL ARE COMPLEMENTARY & WHAT IS REQUIRED BY ONE, SHALL BE REQUIRED BY BOTH. NEITHER THE PRIME CONTRACTOR(S) NOR ANY SUBCONTRACTOR(S) SHALL BE RELIEVED OF THE RESPONSIBILITY TO PROVIDE ALL ITEMS REQUIRED BY THE INFORMATION & DESIGN INTENT INDICATED & IMPLIED. IN THE EVENT OF CONFLICTS BETWEEN DOCUMENTS, THE GREATER QUANTITY OR HIGHER QUALITY OF WORK SHALL PREVAIL AND BE PROVIDED. 01.09 ALL ITEMS LABELED "EXISTING" ARE EXISTING "TO REMAIN" UNLESS OTHERWISE INDICATED. ITEMS NOT LABELED "EXISTING" ARE TO BE PROVIDED. THE TERM "PROVIDE" SHALL MEAN FURNISH & INSTALL AS IT IS USED THROUGHOUT THE CONTRACT DOCUMENTS.
PROJECT COORDINATION (SINGLE OVERALL PRIME CONTRACT) QUALITY REQUIREMENTS
01.12 THE SUBCONTRACTOR SHALL PROVIDE ALL MATERIAL, LABOR, SERVICES, ETC. TO COMPLETE THE ENTIRE WORK IN A MANNER ACCEPTABLE TO THE OWNER AND THE ARCHITECT. IT IS UNDERSTOOD THAT NOT EVERY DETAIL OR DIMENSION IS SHOWN IN THE CONTRACT DOCUMENTS, NOR ARE THEY NECESSARY FOR THE CONTRACTOR(S) TO PROVIDE A QUALITY PRODUCT. THE CONTRACTOR SHALL SUBMIT A REQUEST FOR INFORMATION (R.F.I.) IF NEEDED TO CLARIFY THE INTENT OF ANY DETAIL OR OTHER INFORMATION. HOWEVER, SUCH REQUEST FOR INFORMATION SHALL NOT CONSTITUTE A CHANGE IN THE SCHEDULE, OR IN THE CONTRACT AMOUNT. NO WORK SHOULD BE INSTALLED IF THE CONTRACTOR IS UNSURE OF THE DESIGN INTENT. INSTALLATION OF ANY WORK THAT DOES NOT COMPLY WITH THE DESIGN INTENT, AS DETERMINED BY THE ARCHITECT, SHALL BE SUBJECT TO REPLACEMENT AT THE CONTRACTOR'S EXPENSE. 01.14 ALL CONSTRUCTION, EQUIPMENT, CONTENTS, ETC. SHALL BE PROTECTED BY EACH CONTRACTOR DURING THE ENTIRE PERFORMANCE OF THE WORK. AREAS DISTURBED OR DAMAGED BY THE CONTRACTOR SHALL BE COMPLETELY RESTORED, REPAIRED, OR REPLACED BY THE CONTRACTOR AT NO ADDITIONAL COST. 01.15 ALL UNUSED MATERIAL AND DEBRIS SHALL BE COMPLETELY REMOVED FROM THE SITE AND LEGALLY DISPOSED OF. NO ON-SITE STORAGE, BURNING, OR BURIAL OF DEBRIS SHALL BE PERMITTED. THE CONSTRUCTION SITE SHALL BE KEPT IN A CLEAN AND SAFE MANNER, INCLUDING, BUT NOT LIMITED TO DAILY BROOM CLEANING THROUGHOUT THE DURATION OF THE CONSTRUCTION PROJECT.
EXECUTION REQUIREMENTS
01.20 MISCELLANEOUS WOOD, COLD FORMED, OR ROLLED STEEL SHAPES, WHETHER BLOCKING OR SUB-FRAMING WHICH ARE REQUIRED FOR THE INSTALLATION OF OTHER ITEMS NECESSARY FOR A COMPLETE PACKAGE SHALL BE PROVIDED WHETHER OR NOT SPECIFICALLY INDICATED ON THE DRAWINGS. 01.25 DETAILS & SECTIONS ON THE DRAWINGS ARE SHOWN AT SPECIFIC LOCATIONS & ARE INTENDED TO SHOW GENERAL REQUIREMENTS THROUGHOUT. DETAILS NOTED "TYPICAL" IMPLY ALL "LIKE-CONDITIONS" ARE TO BE TREATED SIMILARLY. 01.26 WORK NOT INDICATED IN PART OF THE DRAWING, BUT REASONABLY IMPLIED TO BE SIMILAR TO THAT SHOWN AT CORRESPONDING PLACES SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST.
BUILDING CODE INFORMATION
SHEET NO.
SHEET NAME
2009 INTERNATIONAL BUILDING CODE, WITH MODIFICATIONS 2009 INTERNATIONAL EXISTING BUILDING CODE 2009 INTERNATIONAL FIRE CODE,WITH MODIFICATIONS 2009 INTERNATIONAL ENERGY CONSERVATION CODE (ASHRAE 90), WITH MODIFICATIONS 2009 INTERNATIONAL FUEL GAS CODE ANSI 117.1-2009 BARRIER FREE CODE (WITH CHAPTER 11 AND APPENDIX E OF THE 2015 INTERNATIONAL BUILDING CODE)
ISSUED FOR CONSTRUCTION - 03/14/2018
DIVISION 00 PROCUREMENT
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
IBC CHAPTER 3: USE AND OCCUPANCY CLASSIFICATION IBC REFERENCE 302.1 305.
USE GROUP CLASSIFICATION EXISTING BUILDING E EDUCATION PROPOSED INTERIOR ALTERATION E EDUCATION, NO CHANGE
A-000 A-010 A-054 A-055 A-056 A-057 A-058 A-059 A-060 A-061 A-062 A-104 A-105 A-106 A-107 A-108 A-140 A-141 A-160 A-161 A-162 A-204 A-205 A-206 A-300 A-301 A-600 A-601
TITLE SHEET EGRESS PLANS GROUND FLOOR DEMOLITION PLAN AREA A - LOG COLLEGE MS UPPER FLOOR DEMOLITION PLAN AREA A - LOG COLLEGE MS DEMOLITION FLOOR PLAN AREA B & CORRIDOR- LOG COLLEGE MS TOILET DEMOLITION PLAN - LOG COLLEGE MS DEMO ROOF PLAN AREA A - LOG COLLEGE MS DEMO ROOF PLAN AREA B - LOG COLLEGE MS GROUND FLOOR DEMOLITION RCP AREA A - LOG COLLEGE MS UPPER FLOOR DEMOLITION RCP AREA A - LOG COLLEGE MS DEMOLITION RCP AREA B & CORRIDOR - LOG COLLEGE MS GROUND FLOOR PLAN AREA A - LOG COLLEGE MS UPPER FLOOR PLAN AREA A - LOG COLLEGE MS FLOOR PLAN AREA B & CORRIDOR - LOG COLLEGE MS ROOF PLAN AREA A - LOG COLLEGE MS ROOF PLAN AREA B - LOG COLLEGE MS DETAILS EFCO (B.O.D.) WINDOW DETAILS ENLARGED ART ROOM ENLARGED TOILET PLANS & DETAILS - LOG COLLEGE MS ENLARGED RAMP & LIFT - KLINGER GROUND FLOOR REFLECTED CEILING PLAN AREA A - LOG COLLEGE MS UPPER FLOOR REFLECTED CEILING PLAN AREA A - LOG COLLEGE MS REFLECTED CEILING PLAN AREA B - LOG COLLEGE MS BUILDING A ELEVATIONS - LOG COLLEGE MS BUILDING B ELEVATIONS - LOG COLLEGE MS DOOR SCHEDULE + DETAILS - LOG COLLEGE MS WINDOW TYPES & FINISH SCHEDULES - LOG COLLEGE MS
X X X X X X X X X X X X X X X X X X X X X X X X X X X X
2009 INTERNATION EXISTING BUILDING CODE (IEBC) Chapter 3 Prescriptive Compliance Method (work area method) Section 303.1 Alterations “Alterations shall be such that the existing building or structure is no less conforming with the provisions of the code than the existing building or structure was prior to the alteration.” In other words, if the part of a building is touched, it must be “fixed”, if not, it can remain as-is. Chapter 4 Classification of Work Section 403.1 Alteration Level 1 Alteration 1 “includes the removals and replacement or the covering of existing materials, elements, equipment, or fixtures using new materials, elements, equipment, or fixtures that serve the same purpose.” ICC confirmed that our scope of work falls under this category, since we are not changing the use or occupancy, nor adding onto, the building. Chapter 6 Alterations Level 1 Section 602 specifies that new finishes, trims, etc., shall comply with the related sections of the IBC. Section 602.4 specifies that all new work shall comply with materials and methods requirements of the I codes. Section 604.1 Means of Egress “Repairs shall be done in a manner that maintain the level of protection provided for the means of egress.” The proposed work maintains the current level of protection provided for the current means of egress.
01.27 MINOR DETAILS OR INCIDENTAL ITEMS NOT USUALLY SHOWN OR SPECIFIED, BUT NECESSARY FOR THE PROPER & COMPLETE EXECUTION OF ANY PART OF THE WORK SHALL BE INCLUDED AS IF THEY WERE SPECIFICALLY INDICATED IN THE CONSTRUCTION DOCUMENTS. Signature & License No.
EX8715
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
ALTERATIONS AT
LOG COLLEGE MIDDLE SCHOOL FOR THE
PROJECT LOCATION:
DESIGN TEAM
SYMBOL LEGEND
730 NORRISTOWN ROAD, WARMINSTER, PA 18974
CENTENNIAL SCHOOL DISTRICT 433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
ARCHITECT NORTH ARROW
Room Name 101 Area
USA ARCHITECTS PLANNERS + INTERIOR DESIGNERS, P.A.
A
1 S 3RD STREET, SUITE 700 EASTON, PA, 18042 (610) 599-6000
ROOM TAG
SIM ELEVATION / SECTION MARK
A-101
SPOT ELEVATION
REVISION TAG
1
1
VIEW NAME SCALE: 1/8" = 1'-0"
TITLE MARK
03-14-2018 01-16-2018 No.
2/28/2018 3:04:15 PM
1 A-101
ISSUED FOR CONSTRUCTION ADDENDUM #1
Date
Issue or Revision
SIM
Drawing Title
DETAIL MARK
CW2
WINDOW TAG
101
DOOR TAG
P1
WALL TAG
TITLE SHEET Scale
USA Project No.
As indicated Drawing Date
1
LOCATION MAP SCALE: N.T.S.
2017-002 Drawing No.
01.08.2018 Drawn By
Checked By
ChaW
JMc
A-000
LEGEND
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
PATH OF EGRESS TRAVEL DIRECTION OF EGRESS TRAVEL
FX
NOTES 1. SCOPE OF WORK MEETS REQUIREMENTS FOR LEVEL 1 ALTERATIONS PER 2015 IEBC, THERE IS NO CHANGE IN BUILDING OCCUPANCY OR USE. THERE IS NO CHANGE TO ANY EXISTING MEANS OF EGRESS.
EXISTING EXIT DOOR: OCCUPANT CAPACITY: 320
usaarchitects.com
FIRE EXTINGUISHER
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
EXISTING EXIT DOOR: OCCUPANT CAPACITY: 320
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
FX
FX FX
FX
FX
FX
FX
EXISTING EXIT DOOR: OCCUPANT CAPACITY: 300
EXISTING EXIT DOOR: OCCUPANT CAPACITY: 300
EXISTING EXIT DOOR: OCCUPANT CAPACITY: 320 FX
FX
EXISTING EXIT DOOR: OCCUPANT CAPACITY: 320
EXISTING EXIT DOOR: OCCUPANT CAPACITY: 300 FX FX
FX
FX
FX
EXISTING EXIT DOOR: OCCUPANT CAPACITY: 960
2
UPPER FLOOR PLAN SCALE: 1/32" = 1'-0"
EXISTING EXIT DOOR: OCCUPANT CAPACITY: 300 Signature & License No.
EXISTING EXIT DOOR: OCCUPANT CAPACITY: 300
EX8715
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
FX EXISTING EXIT DOOR: OCCUPANT CAPACITY: 300
FX
ALTERATIONS AT
LOG COLLEGE MIDDLE SCHOOL
FX FX
FOR THE
FX FX
EXISTING EXIT DOOR: OCCUPANT CAPACITY: 300
CENTENNIAL SCHOOL DISTRICT 433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
FX
EXISTING EXIT DOOR: OCCUPANT CAPACITY: 300
FX FX
FX
EXISTING EXIT DOOR: OCCUPANT CAPACITY: 300
EXISTING EXIT DOOR: OCCUPANT CAPACITY: 300
03-14-2018 No.
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
2/28/2018 3:04:19 PM
EGRESS PLANS
1
GROUND FLOOR PLAN SCALE: 1/32" = 1'-0"
Scale
USA Project No.
As indicated Drawing Date
2017-002 Drawing No.
01.08.2018 Drawn By
Checked By
Author
Checker
A-010
10
10 9
10
9
9 14
14
CLASSROOM 15
DEMOLITION LEGEND:
9 14
STAIR 2 ST2.1
14
FACULTY WORKROOM 21-0
FACULTY WORKROOM 19-0
CLASSROOM 19
14
CLASSROOM 20
14 EXISTING TO REMAIN
CLASSROOM 21
CLASSROOM 22
FACULTY WORKROOM 23-0
CLASSROOM 23
CLASSROOM 24
TO BE REMOVED
CLASSROOM 25
STAIR 3 ST3.1
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
GENERAL DEMOLITION NOTES:
ELECTRIC ROOM 137
1
1
FACULTY WORKROOM 25-0
13
CORRIDOR 111B
1
1 1
1
1
1
1
STORAGE 118
E.T.R. CASEWORK
MECH. RM. 119
2 A-057
MECH/ STORAGE 138
HOME MAKING 17
BOY'S TOILET 1.2 BT1.2
GIRL'S TOILET 1.2 GT1.2
2
2 3
13
IT/ STORAGE 120
2 3
DF
HALL 113
WOMEN'S TOILET 115
STORAGE & MECHANICAL ROOM
3
3
STORAGE 117
5. SEE MEP AND STRUCTURAL DRAWINGS FOR FULL SCOPE OF DEMOLITION. COORDINATE BOILER & CHILLER PAD REMOVAL WITH HVAC.
OFFICE 124
11
FREEZER 136
HOME MAKING 16-1
RECEIVING & MAINTENANCE 130
1
6
LOCKER 133
GROUNDS EQUIPMENT TOILET ROOM 132 135
3
7
REFUSE 107
CORRIDOR 111
CORRIDOR 16-3
OFFICE 131
2
13
D.F.
9
KITCHEN HELP 108
JANITOR CLOSET 109
2
SERVING 2 106
3
LIVING ROOM 16-2
E.T.R. CASEWORK
PRINCIPAL OFFICE 122
STORAGE 16-4
MAIN OFFICE 121 OFFICE 105C
CAFETERIA 103
DF 13
CORRIDOR 111A
1
1
1
1 A-057
1
1
KITCHEN 105
9
CORRIDOR 111C
CORRIDOR 111D 6
1
ART 14
22
WOOD SHOP 12-1
CLASSROOM 11
2
STORAGE 13-1 2
WOOD SHOP 12
SERVING 1 104
COMPUTER LAB 10
ART 13
MATERIAL STORAGE 12-3
6 15 16
9
9
FINISH ROOM 12-4
COMPUTER LAB 9
STAIR 1 ST1.1 CLASSROOM 8
ENTRANCE 101
GROUND FLOOR DEMOLITION PLAN
3
REMOVE EXISTING RESILIENT BASE ONLY WHERE FLOORING IS REMOVED.
4
REMOVE EXISTING ACCORDION PARTITION - TRACKS TO REMAIN.
5
REMOVE EXISTING TIERED SEATING RISERS, RAILINGS AND ASSOCIATED CONSTRUCTION.
6
REMOVE EXISTING SINKS AND MILLWORK. CAP EXISTING PLUMBING, COORDINATE WITH PLUMBING DRAWINGS.
7
REMOVE EXISTING PARTITION.
8
REINSTALL DOORS PROVIDED BY OWNER.
9
REMOVE EXISTING WINDOW IN ITS ENTIRETY AND PREP ROUGH OPENING FOR NEW WINDOW INSTALLATION. REMOVE BULKHEAD ABOVE LARGE WINDOWS TO ALLOW FOR FRAMING TO REACH DECK ABOVE.
10
REMOVE EXISTING CONCRETE CURB/ APRON AT BUILDING PERIMETER. PROVIDE NEW TOP SOIL AND GRASS. ENSURE GRADE SLOPES AWAY FROM BUILDING.
11
RELOCATE KILN AND ALL ASSOCIATED POWER/ GAS AND EXHAUSTING REQUIREMENTS BY HVAC CONTRACTOR
12
REMOVE EXISTING ALUMINUM DOORS AND WINDOWS. PREP AREA FOR NEW INSTALL.
13
REMOVE EXISTING DRINKING FOUNTAIN. SEE PLUMBING DRAWINGS FOR MORE INFORMATION.
14
ABATE EXISTING VAT AT WINDOW AS REQIURED FOR INSTALL OF NEW WINDOW.
15
REMOVE EXISTING CERAMIC TILE FLOORING.
16
REMOVE WATER DAMAGED WOOD FLOORING AS REQUIRED. VERIFY EXTENT TO BE REMOVED.
17
PORTION OF EXISTING RAISED HW (HARDWOOD FLOORING) TO REMAIN.
17 18
REMOVE EXISTING ALUMINUM STOREFRONT WINDOWS AND DOORS. PATCH TERRAZZO FLOORING AS REQUIRED.
19
REMOVE EXISTING FLOOR MOUNTED SINKS & CABINET. SEE PLUMBING DRAWINGS FOR MORE INFORMATION.
ENTRANCE VESTIBULE 100
20
REMOVE EXISTING CARPET.
21
SHELVING TO BE REMOVED AND REINSTALLED BY OWNER
22
REMOVE EXISTING TACKBOARD AND MASTIC
23
REMOVE BOILER, CHILLER & BASE IN ROOM 134 (INC. ALL CONCRETE & MASONRY FOUND)
24
REMOVE PLYWOOD FROM WINDOWS
25
REMOVE PANELS AT WINDOW
26
REMOVE RAISED PLATFORM; PATCH VCT.
27
REMOVE, SALVAGE, & REINSTALL EXISTING PANELS AT WINDOW AND OTHER LOCATIONS AS SHOWN IN ROOMS 41 & 42.
Signature & License No.
14
9
14
9
14
18
9
CONNECTING CORRIDOR 102
1
REMOVE EXISTING FINISH FLOORING (VAT) IN ITS ENTIRETY DOWN TO EXISTING SLAB/SUBFLOOR. PATCH, REPAIR, CLEAN AND PREPARE SUBSTRATES AS NECESSARY TO RECEIVE NEW FINISH AS SCHEDULED.
14
18
STORAGE 12-2
21
2
1
9
3
10
4
MATERIAL STORAGE 9-2
REMOVE EXISTING DOOR AND ASSOCIATED HARDWARE AND REPLACE WITH NEW SCHEDULED DOOR AND HARDWARE. DOOR FRAME TO REMAIN.
4
CLOSET 9-1
2
3
BOY'S TOILET 1.1 BT1.1
DISHWASH AREA
FREEZER 105A
STORAGE 141
1
3
GIRL'S CLOSET TOILET 1.1 GT1.1 142
STORE 140
1
REFRIGERATOR 105B
DARK ROOM 143
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
SELECTIVE DEMOLITION NOTES:
2
MT 127
7
FCS 16
D W
GUIDANCE 123
5
WT 126
6. ALL EXISTING CASEWORK, MILLWORK, BUILTINS, CABINETRY, DESKS, & SHELVING ETC. ARE TO REMAIN UNLESS OTHERWISE NOTED.
14
17 1
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
4. PATCH AND REPAIR ALL ADJACENT SURFACES WHICH ARE AFFECTED BY THE DEMOLITION OR REMOVAL OF ACCESSORIES TO THEIR ORIGINAL FORM AND PREPARE FOR NEW FINISH. COORDINATE WITH FINISH DRAWINGS.
CLASSROOM 26
FOOD STORAGE 110
HALL 125
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
3. REMOVE ANY MISCELLANEOUS PROJECTIONS, HANGERS, BOLTS, SCREWS AND NAILS FROM EXISTING SURFACES TO REMAIN. PATCH AND PREPARE SURFACES TO RECEIVE NEW FINISH.
2
112
LOUNGE 116
23 2
ELEV. EL1
MEN'S TOILET 114
usaarchitects.com
2. DO NOT CONSIDER DEMOLITION AND ALTERATION NOTES TO BE ALL INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND ASSESS EACH SPACE AND TO FULFILL THE INTENT OF THE WORK INDICATED BY THE CONTRACT DOCUMENTS. VERIFY ALL DIMENSIONS WITHIN THE CONTRACT LIMITS. BRING DEVIATIONS FROM THE CONTRACT DOCUMENTS TO THE ATTENTION OF THE ARCHITECT. THE EXTENT OF DEMOLITION AND REMOVAL INCLUDES, BUT IS NOT LIMITED TO WORK SHOWN ON THE DRAWINGS.
24
DF
BOILER ROOM 134
1. CONTRACTOR MUST INSTALL AND MAINTAIN PLASTIC DUST BARRIERS DURING DEMOLITION AND CONSTRUCTION TO PROTECT THE GENERAL PUBLIC FROM DUST AND FUMES. LOCATE PARTITIONS REQUIRED TO PROTECT ADJACENT AREAS AND EQUIPMENT, AND CONTINUE EGRESS THROUGH THE SPACE. CONTRACTOR SHALL PROVIDE TEMPORARY EXIT WAYS AS REQUIRED BY LOCAL CODE ENFORCEMENT OFFICIAL DURING CONSTRUCTION.
EX8715
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
ALTERATIONS AT
LOG COLLEGE MIDDLE SCHOOL
SCALE: 3/32" = 1'-0"
FOR THE
CENTENNIAL SCHOOL DISTRICT 433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
03-14-2018
B
A
No.
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
2/28/2018 3:04:24 PM
Drawing Title
GROUND FLOOR DEMOLITION PLAN AREA A - LOG COLLEGE MS Scale
KEY PLAN A - LOG COLLEGE MS SCALE: N.T.S.
USA Project No.
As indicated Drawing Date
2017-002 Drawing No.
01.08.2018 Drawn By
Checked By
ChaW
JMc
A-054
27
9
9
9
9
9
9
9
9
DEMOLITION LEGEND: 14
CLASSROOM 34
14
STAIR 2 ST2.2
CLASSROOM 35
14
CLASSROOM 36
FACULTY WORKROOM 37-0
CLASSROOM 37
14
14
14
EXISTING TO REMAIN
CLASSROOM 39
TO BE REMOVED
CLASSROOM 40
CLASSROOM 41
STAIR 3 ST3.2
CLASSROOM 42
19
PAINT HM FRAMES AT DOOR AND WINDOWS
SCIENCE LAB 43
1
1
4 A-057
1
CORRIDOR 211B
1
14
9
STORAGE 3 230
14 9
1
DF
MECH. 231 CLASSROOM 54
19
CLASSROOM 33
GIRL'S TOILET 2.2 GT2.2
BOY'S TOILET 2.2 BT2.2
3 2
PLANTER
2
2
STORAGE 210
1
13
CONFERENCE 204 SCIENCE LAB 44
WOMEN'S TOILET 1 228
GUIDANCE 224
PLANTER
CORRIDOR 211C
19
COURT UC
26
MEN'S TOILET 1 229
LIBRARY 202
LIBRARY WORKROOM 58
CORRIDOR 211 LIBRARY WORKROOM 58A
14
9
CLASSROOM 52 FACULTY WORKROOM 31-0
1
1
HALL 222
OFFICE 223
9
CORRIDOR 211D
19
9
SCIENCE LAB 45
3 2
STORAGE 31-1
CLASSROOM 61
MAIN OFFICE 220
19
1
CLASSROOM 51
MECHANICAL 241
CLASSROOM 50
14
3
BOY'S TOILET 2.1 BT2.1
2
CLASSROOM 31 14
9
DF
CLASSROOM 60 20
STORAGE 213
1 PLANTER
1
STORAGE 214
CORRIDOR 211A
1
3 A-057
1
1
1
14
14
3 2
CLASSROOM 30
FACULTY WORKROOM 29-0
CLASSROOM 29
CLASSROOM 28
FACULTY WORKROOM 27-0
CLASSROOM 27
MEN'S TOILET 242
8 1
JANITOR CLOSET 245 STAIR 1 ST1.2
CLASSROOM 48
FACULTY WORKROOM 47-0
14
9
1
UPPER FLOOR DEMOLITION PLAN
14
9
14
9
LOUNGE 244
19 3
14
9
SCIENCE LAB 46
MECH. 46-0
CLASSROOM 47
REMOVE EXISTING FINISH FLOORING (VAT) IN ITS ENTIRETY DOWN TO EXISTING SLAB/SUBFLOOR. PATCH, REPAIR, CLEAN AND PREPARE SUBSTRATES AS NECESSARY TO RECEIVE NEW FINISH AS SCHEDULED.
3
REMOVE EXISTING RESILIENT BASE ONLY WHERE FLOORING IS REMOVED.
4
REMOVE EXISTING ACCORDION PARTITION - TRACKS TO REMAIN.
5
REMOVE EXISTING TIERED SEATING RISERS, RAILINGS AND ASSOCIATED CONSTRUCTION.
6
REMOVE EXISTING SINKS AND MILLWORK. CAP EXISTING PLUMBING, COORDINATE WITH PLUMBING DRAWINGS.
7
REMOVE EXISTING PARTITION.
8
REINSTALL DOORS PROVIDED BY OWNER.
9
REMOVE EXISTING WINDOW IN ITS ENTIRETY AND PREP ROUGH OPENING FOR NEW WINDOW INSTALLATION. REMOVE BULKHEAD ABOVE LARGE WINDOWS TO ALLOW FOR FRAMING TO REACH DECK ABOVE.
10
REMOVE EXISTING CONCRETE CURB/ APRON AT BUILDING PERIMETER. PROVIDE NEW TOP SOIL AND GRASS. ENSURE GRADE SLOPES AWAY FROM BUILDING.
11
RELOCATE KILN AND ALL ASSOCIATED POWER/ GAS AND EXHAUSTING REQUIREMENTS BY HVAC CONTRACTOR
12
REMOVE EXISTING ALUMINUM DOORS AND WINDOWS. PREP AREA FOR NEW INSTALL.
13
REMOVE EXISTING DRINKING FOUNTAIN. SEE PLUMBING DRAWINGS FOR MORE INFORMATION.
14
ABATE EXISTING VAT AT WINDOW AS REQIURED FOR INSTALL OF NEW WINDOW.
15
REMOVE EXISTING CERAMIC TILE FLOORING.
16
REMOVE WATER DAMAGED WOOD FLOORING AS REQUIRED. VERIFY EXTENT TO BE REMOVED.
17
PORTION OF EXISTING RAISED HW (HARDWOOD FLOORING) TO REMAIN.
17 18
REMOVE EXISTING ALUMINUM STOREFRONT WINDOWS AND DOORS. PATCH TERRAZZO FLOORING AS REQUIRED.
19
REMOVE EXISTING FLOOR MOUNTED SINKS & CABINET. SEE PLUMBING DRAWINGS FOR MORE INFORMATION.
20
REMOVE EXISTING CARPET.
21
SHELVING TO BE REMOVED AND REINSTALLED BY OWNER
22
REMOVE EXISTING TACKBOARD AND MASTIC
23
REMOVE BOILER, CHILLER & BASE IN ROOM 134 (INC. ALL CONCRETE & MASONRY FOUND)
24
REMOVE PLYWOOD FROM WINDOWS
25
REMOVE PANELS AT WINDOW
26
REMOVE RAISED PLATFORM; PATCH VCT.
27
REMOVE, SALVAGE, & REINSTALL EXISTING PANELS AT WINDOW AND OTHER LOCATIONS AS SHOWN IN ROOMS 41 & 42.
3 2
WOMEN'S TOILET 243
2
9 19
9
REMOVE EXISTING DOOR AND ASSOCIATED HARDWARE AND REPLACE WITH NEW SCHEDULED DOOR AND HARDWARE. DOOR FRAME TO REMAIN.
21
13
1
1
PRINCIPAL OFFICE 221
GIRL'S TOILET 2.1 GT2.1
1
9
19
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
SELECTIVE DEMOLITION NOTES:
1
9
CLASSROOM 53
CLASSROOM 32
1
GUIDANCE 226
PLANTER
9
5. SEE MEP AND STRUCTURAL DRAWINGS FOR FULL SCOPE OF DEMOLITION. COORDINATE BOILER & CHILLER PAD REMOVAL WITH HVAC. 6. ALL EXISTING CASEWORK, MILLWORK, BUILTINS, CABINETRY, DESKS, & SHELVING ETC. ARE TO REMAIN UNLESS OTHERWISE NOTED.
2 1
2. DO NOT CONSIDER DEMOLITION AND ALTERATION NOTES TO BE ALL INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND ASSESS EACH SPACE AND TO FULFILL THE INTENT OF THE WORK INDICATED BY THE CONTRACT DOCUMENTS. VERIFY ALL DIMENSIONS WITHIN THE CONTRACT LIMITS. BRING DEVIATIONS FROM THE CONTRACT DOCUMENTS TO THE ATTENTION OF THE ARCHITECT. THE EXTENT OF DEMOLITION AND REMOVAL INCLUDES, BUT IS NOT LIMITED TO WORK SHOWN ON THE DRAWINGS.
9 14
3
GUIDANCE 225
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
4. PATCH AND REPAIR ALL ADJACENT SURFACES WHICH ARE AFFECTED BY THE DEMOLITION OR REMOVAL OF ACCESSORIES TO THEIR ORIGINAL FORM AND PREPARE FOR NEW FINISH. COORDINATE WITH FINISH DRAWINGS.
DF
CONFERENCE ROOM 227
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
3. REMOVE ANY MISCELLANEOUS PROJECTIONS, HANGERS, BOLTS, SCREWS AND NAILS FROM EXISTING SURFACES TO REMAIN. PATCH AND PREPARE SURFACES TO RECEIVE NEW FINISH.
21
203
ELEV. EL2
2
MECHANICAL 240
STORAGE 212 3 MECHANICAL EQUIPMENT
3
CLASSROOM 55
3
usaarchitects.com 1. CONTRACTOR MUST INSTALL AND MAINTAIN PLASTIC DUST BARRIERS DURING DEMOLITION AND CONSTRUCTION TO PROTECT THE GENERAL PUBLIC FROM DUST AND FUMES. LOCATE PARTITIONS REQUIRED TO PROTECT ADJACENT AREAS AND EQUIPMENT, AND CONTINUE EGRESS THROUGH THE SPACE. CONTRACTOR SHALL PROVIDE TEMPORARY EXIT WAYS AS REQUIRED BY LOCAL CODE ENFORCEMENT OFFICIAL DURING CONSTRUCTION.
2
13
1
GENERAL DEMOLITION NOTES:
3
1
FACULTY WORKROOM 33-0
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
19
14
9
14
FACULTY WORKROOM 40-0
FACULTY WORKROOM 38-0
CLASSROOM 38
14
2
14
9
14
9
19
Signature & License No.
EX8715
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
ALTERATIONS AT
LOG COLLEGE MIDDLE SCHOOL
SCALE: 3/32" = 1'-0"
FOR THE
CENTENNIAL SCHOOL DISTRICT 433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
03-14-2018 No.
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
2/28/2018 3:04:28 PM
B
UPPER FLOOR DEMOLITION PLAN AREA A - LOG COLLEGE MS
A
Scale
USA Project No.
As indicated Drawing Date
2017-002 Drawing No.
KEY PLAN A - LOG COLLEGE MS
01.08.2018
SCALE: N.T.S.
Drawn By
Checked By
ChaW
JMc
A-055
DEMOLITION LEGEND: EXISTING TO REMAIN
TO BE REMOVED
GENERAL DEMOLITION NOTES: 9
9
9
9
9
9
10
9
9
9
1. CONTRACTOR MUST INSTALL AND MAINTAIN PLASTIC DUST BARRIERS DURING DEMOLITION AND CONSTRUCTION TO PROTECT THE GENERAL PUBLIC FROM DUST AND FUMES. LOCATE PARTITIONS REQUIRED TO PROTECT ADJACENT AREAS AND EQUIPMENT, AND CONTINUE EGRESS THROUGH THE SPACE. CONTRACTOR SHALL PROVIDE TEMPORARY EXIT WAYS AS REQUIRED BY LOCAL CODE ENFORCEMENT OFFICIAL DURING CONSTRUCTION.
CONNECTING CORRIDOR 102
9
9
9
9
2. DO NOT CONSIDER DEMOLITION AND ALTERATION NOTES TO BE ALL INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND ASSESS EACH SPACE AND TO FULFILL THE INTENT OF THE WORK INDICATED BY THE CONTRACT DOCUMENTS. VERIFY ALL DIMENSIONS WITHIN THE CONTRACT LIMITS. BRING DEVIATIONS FROM THE CONTRACT DOCUMENTS TO THE ATTENTION OF THE ARCHITECT. THE EXTENT OF DEMOLITION AND REMOVAL INCLUDES, BUT IS NOT LIMITED TO WORK SHOWN ON THE DRAWINGS.
9
10
usaarchitects.com Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
3. REMOVE ANY MISCELLANEOUS PROJECTIONS, HANGERS, BOLTS, SCREWS AND NAILS FROM EXISTING SURFACES TO REMAIN. PATCH AND PREPARE SURFACES TO RECEIVE NEW FINISH. 4. PATCH AND REPAIR ALL ADJACENT SURFACES WHICH ARE AFFECTED BY THE DEMOLITION OR REMOVAL OF ACCESSORIES TO THEIR ORIGINAL FORM AND PREPARE FOR NEW FINISH. COORDINATE WITH FINISH DRAWINGS.
DEMOLITION FLOOR PLAN CORRIDOR
2
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
9
SCALE: 3/32" = 1'-0"
5. SEE MEP AND STRUCTURAL DRAWINGS FOR FULL SCOPE OF DEMOLITION. COORDINATE BOILER & CHILLER PAD REMOVAL WITH HVAC. 6. ALL EXISTING CASEWORK, MILLWORK, BUILTINS, CABINETRY, DESKS, & SHELVING ETC. ARE TO REMAIN UNLESS OTHERWISE NOTED. 10
1
10
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
HEALTH 157
HEALTH 158
10
JANITOR CLOSET 159
1
EXISTING CT FLOORING TO REMAIN. NOTE: NO NEW FLOORING IN THIS SPACE.
1
CORRIDOR 150A HEALTH CL. 158-1
CORRIDOR 153
NURSE 155
MEN 156
1
STAGE 152
BOY'S LOCKER ROOM 160 2
AUDITORIUM 151
3
STORAGE 161
BOY'S TOILET L35
REMOVE EXISTING DOOR AND FRAME. CAREFULLY CUT OUT REMAINING PORTION OF BRICK/BLOCK WALL TO ENLARGE EXISTING OPENING TO BE FULL WIDTH OF EXISTING CORRIDOR.
CORRIDOR 150
CORRIDOR 172
SALVAGE EXISTING FIRE EXTINGUISHER CABINET AND FIRE EXTINGUISHER FOR REINSTALL.
STORAGE 174
1
STORAGE 173
1
2 3
CORRIDOR 154
WOMEN 171 1
SELECTIVE DEMOLITION NOTES: 1
REMOVE EXISTING DOOR AND ASSOCIATED HARDWARE AND REPLACE WITH NEW SCHEDULED DOOR AND HARDWARE. DOOR FRAME TO REMAIN.
2
REMOVE EXISTING FINISH FLOORING (VAT) IN ITS ENTIRETY DOWN TO EXISTING SLAB/SUBFLOOR. PATCH, REPAIR, CLEAN AND PREPARE SUBSTRATES AS NECESSARY TO RECEIVE NEW FINISH AS SCHEDULED.
3
REMOVE EXISTING RESILIENT BASE ONLY WHERE FLOORING IS REMOVED.
4
REMOVE EXISTING ACCORDION PARTITION - TRACKS TO REMAIN.
5
REMOVE EXISTING TIERED SEATING RISERS, RAILINGS AND ASSOCIATED CONSTRUCTION.
6
REMOVE EXISTING SINKS AND MILLWORK. CAP EXISTING PLUMBING, COORDINATE WITH PLUMBING DRAWINGS.
7
REMOVE EXISTING PARTITION.
8
REINSTALL DOORS PROVIDED BY OWNER.
9
REMOVE EXISTING WINDOW IN ITS ENTIRETY AND PREP ROUGH OPENING FOR NEW WINDOW INSTALLATION. REMOVE BULKHEAD ABOVE LARGE WINDOWS TO ALLOW FOR FRAMING TO REACH DECK ABOVE.
10
REMOVE EXISTING CONCRETE CURB/ APRON AT BUILDING PERIMETER. PROVIDE NEW TOP SOIL AND GRASS. ENSURE GRADE SLOPES AWAY FROM BUILDING.
11
RELOCATE KILN AND ALL ASSOCIATED POWER/ GAS AND EXHAUSTING REQUIREMENTS BY HVAC CONTRACTOR
12
REMOVE EXISTING ALUMINUM DOORS AND WINDOWS. PREP AREA FOR NEW INSTALL.
13
REMOVE EXISTING DRINKING FOUNTAIN. SEE PLUMBING DRAWINGS FOR MORE INFORMATION.
14
ABATE EXISTING VAT AT WINDOW AS REQIURED FOR INSTALL OF NEW WINDOW.
15
REMOVE EXISTING CERAMIC TILE FLOORING.
16
REMOVE WATER DAMAGED WOOD FLOORING AS REQUIRED. VERIFY EXTENT TO BE REMOVED.
17
PORTION OF EXISTING RAISED HW (HARDWOOD FLOORING) TO REMAIN.
17 18
REMOVE EXISTING ALUMINUM STOREFRONT WINDOWS AND DOORS. PATCH TERRAZZO FLOORING AS REQUIRED.
19
REMOVE EXISTING FLOOR MOUNTED SINKS & CABINET. SEE PLUMBING DRAWINGS FOR MORE INFORMATION.
20
REMOVE EXISTING CARPET.
1 12
CORRIDOR 150B VOCAL 170
1
PRACTICE ROOM 168
1
JANITOR CLOSET 2 167 3
MUSIC CLASSROOM 169
10
VOCAL 170-1
GIRL'S LOCKER ROOM 163
GIRL'S TOILET L29
B
Signature & License No.
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
ALTERATIONS AT
LOG COLLEGE MIDDLE SCHOOL FOR THE
CENTENNIAL SCHOOL DISTRICT 433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
03-14-2018
21
SHELVING TO BE REMOVED AND REINSTALLED BY OWNER
22
REMOVE EXISTING TACKBOARD AND MASTIC
23
REMOVE BOILER, CHILLER & BASE IN ROOM 134 (INC. ALL CONCRETE & MASONRY FOUND)
24
REMOVE PLYWOOD FROM WINDOWS
25
REMOVE PANELS AT WINDOW
26
REMOVE RAISED PLATFORM; PATCH VCT.
EX8715
No.
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title REMOVE EXISTING WASHING MACHINE AND ASSOCIATED PLUMBING. SEE PLUMBING DRAWINGS FOR MORE INFORMATION.
A
STORAGE 162
2/28/2018 3:04:41 PM
2 3
1
DEMOLITION FLOOR PLAN - AREA B SCALE: 3/32" = 1'-0"
DEMOLITION FLOOR PLAN AREA B & CORRIDOR- LOG COLLEGE MS Scale
USA Project No.
As indicated Drawing Date
KEY PLAN B - LOG COLLEGE MS SCALE: N.T.S.
27
REMOVE, SALVAGE, & REINSTALL EXISTING PANELS AT WINDOW AND OTHER LOCATIONS AS SHOWN IN ROOMS 41 & 42.
2017-002 Drawing No.
01.08.2018 Drawn By
Checked By
ChaW
JMc
A-056
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174 usaarchitects.com BOY'S TOILET BT2.2
GIRL'S TOILET GT1.1
VERIFY EXISTING SINK LOCATIONS TO MINIMIZE EXTENT OF DEMO & PATCHING
VERIFY EXISTING SINK LOCATIONS TO MINIMIZE EXTENT OF DEMO & PATCHING
VERIFY EXISTING SINK LOCATIONS TO MINIMIZE EXTENT OF DEMO & PATCHING BOY'S TOILET BT1.1
BOY'S TOILET BT1.2
GIRL'S TOILET GT2.2
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
GIRL'S TOILET GT1.2 BOY'S TOILET BT2.1
GIRL'S TOILET GT2.1
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
1
TOILET DEMOLITION PLAN - GT1.1 & BT1.1 SCALE: 1/4" = 1'-0"
2
TOILET DEMOLITION PLAN - GT1.2 & BT1.2 SCALE: 1/4" = 1'-0"
3
TOILET DEMOLITION PLAN - GT2.1 & BT2.1 SCALE: 1/4" = 1'-0"
4
TOILET DEMOLITION PLAN - GT2.2 & BT2.2 SCALE: 1/4" = 1'-0"
DEMOLITION LEGEND: EXISTING TO REMAIN
TO BE REMOVED
GENERAL DEMOLITION NOTES: 1. CONTRACTOR MUST INSTALL AND MAINTAIN PLASTIC DUST BARRIERS DURING DEMOLITION AND CONSTRUCTION TO PROTECT THE GENERAL PUBLIC FROM DUST AND FUMES. LOCATE PARTITIONS REQUIRED TO PROTECT ADJACENT AREAS AND EQUIPMENT, AND CONTINUE EGRESS THROUGH THE SPACE. CONTRACTOR SHALL PROVIDE TEMPORARY EXIT WAYS AS REQUIRED BY LOCAL CODE ENFORCEMENT OFFICIAL DURING CONSTRUCTION. 2. DO NOT CONSIDER DEMOLITION AND ALTERATION NOTES TO BE ALL INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND ASSESS EACH SPACE AND TO FULFILL THE INTENT OF THE WORK INDICATED BY THE CONTRACT DOCUMENTS. VERIFY ALL DIMENSIONS WITHIN THE CONTRACT LIMITS. BRING DEVIATIONS FROM THE CONTRACT DOCUMENTS TO THE ATTENTION OF THE ARCHITECT. THE EXTENT OF DEMOLITION AND REMOVAL INCLUDES, BUT IS NOT LIMITED TO WORK SHOWN ON THE DRAWINGS. 3. REMOVE ANY MISCELLANEOUS PROJECTIONS, HANGERS, BOLTS, SCREWS AND NAILS FROM EXISTING SURFACES TO REMAIN. PATCH AND PREPARE SURFACES TO RECEIVE NEW FINISH. 4. PATCH AND REPAIR ALL ADJACENT SURFACES WHICH ARE AFFECTED BY THE DEMOLITION OR REMOVAL OF ACCESSORIES TO THEIR ORIGINAL FORM AND PREPARE FOR NEW FINISH. COORDINATE WITH FINISH DRAWINGS. Signature & License No.
5. SEE MEP AND STRUCTURAL DRAWINGS FOR FULL SCOPE OF DEMOLITION. COORDINATE BOILER & CHILLER PAD REMOVAL WITH HVAC. 6. ALL EXISTING CASEWORK, MILLWORK, BUILTINS, CABINETRY, DESKS, & SHELVING ETC. ARE TO REMAIN UNLESS OTHERWISE NOTED.
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
TOILET ROOM DEMOLITION NOTES:
ALTERATIONS
(NOTES APPLY TO ALL RESTROOMS SHOWN ON THIS SHEET)
AT
1. REMOVE ALL EXISTING FIXTURES & CARRIERS (TOILET, URINALS, AND SINKS) AND ASSCIATED PLUMBING AS INDICATED ON PLUMBING DRAWINGS.
LOG COLLEGE MIDDLE SCHOOL FOR THE
2. SALVAGE ALL HAND DRYERS. SAVE FOR FUTURE REINSTALL. 3. DEMO ENTIRE HARD CEILING INCLUDING LIGHT FIXTURES, GRILLS AND ASSOCIATED HVAC ITEMS ABOVE CEILING. SEE MEP DRAWINGS FOR MORE INFORMATION. 4. DEMO EXISTING TOILET PARTITIONS AND EXISTING GLAZED CMU CHASE WALL.
EX8715
CENTENNIAL SCHOOL DISTRICT 433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
5. EXISTING STEEL TUBE COLUMN LOCATED IN WET WALL OF GIRL'S TOILET - GT1.1 TO REMAIN. 6. PREP EXISTING WALLS AND FLOORS AS REQUIRED FOR NEW RESIN FINISH COATING. SEE A161 FOR MORE INFORMATION.
03-14-2018 No.
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
2/28/2018 3:04:48 PM
TOILET DEMOLITION PLAN - LOG COLLEGE MS Scale
USA Project No.
As indicated Drawing Date
2017-002 Drawing No.
01.08.2018 Drawn By
Checked By
JS
JMc
A-057
DEMOLITION LEGEND: EXISTING TO REMAIN
TO BE REMOVED
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
GENERAL DEMOLITION NOTES: 1. CONTRACTOR MUST INSTALL AND MAINTAIN PLASTIC DUST BARRIERS DURING DEMOLITION AND CONSTRUCTION TO PROTECT THE GENERAL PUBLIC FROM DUST AND FUMES. LOCATE PARTITIONS REQUIRED TO PROTECT ADJACENT AREAS AND EQUIPMENT, AND CONTINUE EGRESS THROUGH THE SPACE. CONTRACTOR SHALL PROVIDE TEMPORARY EXIT WAYS AS REQUIRED BY LOCAL CODE ENFORCEMENT OFFICIAL DURING CONSTRUCTION. 2. DO NOT CONSIDER DEMOLITION AND ALTERATION NOTES TO BE ALL INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND ASSESS EACH SPACE AND TO FULFILL THE INTENT OF THE WORK INDICATED BY THE CONTRACT DOCUMENTS. VERIFY ALL DIMENSIONS WITHIN THE CONTRACT LIMITS. BRING DEVIATIONS FROM THE CONTRACT DOCUMENTS TO THE ATTENTION OF THE ARCHITECT. THE EXTENT OF DEMOLITION AND REMOVAL INCLUDES, BUT IS NOT LIMITED TO WORK SHOWN ON THE DRAWINGS.
SEE MEP PLANS FOR ADDITIONAL DEMO SCOPE AT ROOF.
usaarchitects.com Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
1 3. REMOVE ANY MISCELLANEOUS PROJECTIONS, HANGERS, BOLTS, SCREWS AND NAILS FROM EXISTING SURFACES TO REMAIN. PATCH AND PREPARE SURFACES TO RECEIVE NEW FINISH.
1
4. PATCH AND REPAIR ALL ADJACENT SURFACES WHICH ARE AFFECTED BY THE DEMOLITION OR REMOVAL OF ACCESSORIES TO THEIR ORIGINAL FORM AND PREPARE FOR NEW FINISH. COORDINATE WITH FINISH DRAWINGS. 5. SEE MEP AND STRUCTURAL DRAWINGS FOR FULL SCOPE OF DEMOLITION. COORDINATE BOILER & CHILLER PAD REMOVAL WITH HVAC. 6. ALL EXISTING CASEWORK, MILLWORK, BUILTINS, CABINETRY, DESKS, & SHELVING ETC. ARE TO REMAIN UNLESS OTHERWISE NOTED.
1
1
DEMO EXISTING EQUIPMENT.
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
ROOF DEMOLITION NOTES:
1
1. MEP SUBCONTRACTOR RESPONSIBLE FOR REMOVING ALL EQUIPMENT SHOWN TO BE DEMO'D. SEE MEP DRAWINGS FOR MORE INFORMATION. 2. CUT ROOF, INSTALL BLOCKING, SET AND FLASH. CURBS PROVIDED BY OTHERS.
1 DEMO EXISTING CONDENSING UNIT.
2
1
3. AREAS OF INFILL ROOFING TO MATCH EXISTING ROOFING SYSTEM AND RECEIVE SAME LEVEL OF WARRANTY AS EXISTING ROOF. 4. SKYLIGHTS ARE EXISTING TO REMAIN.
LOWER ROOF
KEY NOTES:
2
3
1 1
4 2
1
CURB IS EXISTING TO REMAIN.
2
PATCH ROOF AT CHILLER OR CONDENSER DUNNAGE OR EXHAUST FAN.
3
SET NEW CURB.
4
PATCH AT VENT PIPE.
DEMO EXISTING COOLING TOWER AND DUNNAGE. PATCH ROOF AS REQUIRED. 1
1
1
1 1
1
Signature & License No.
EX8715
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
ALTERATIONS AT
1
DEMO ROOF PLAN - AREA A
LOG COLLEGE MIDDLE SCHOOL
SCALE: 3/32" = 1'-0" FOR THE
CENTENNIAL SCHOOL DISTRICT 433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
03-14-2018 01-16-2018 No.
B
A
ISSUED FOR CONSTRUCTION ADDENDUM #1
Date
Issue or Revision
Drawing Title
2/28/2018 3:04:50 PM
DEMO ROOF PLAN AREA A - LOG COLLEGE MS Scale
USA Project No.
As indicated Drawing Date
2017-002 Drawing No.
KEY PLAN A - LOG COLLEGE MS
01.08.2018
SCALE: N.T.S.
Drawn By
Checked By
JS
JMc
A-058
ROOF DEMOLITION NOTES: 1. MEP SUBCONTRACTOR RESPONSIBLE FOR REMOVING ALL EQUIPMENT SHOWN TO BE DEMO'D. SEE MEP DRAWINGS FOR MORE INFORMATION. 2. CUT ROOF, INSTALL BLOCKING, SET AND FLASH. CURBS PROVIDED BY OTHERS. 3. AREAS OF INFILL ROOFING TO MATCH EXISTING ROOFING SYSTEM AND RECEIVE SAME LEVEL OF WARRANTY AS EXISTING ROOF. 4. SKYLIGHTS ARE EXISTING TO REMAIN.
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
KEY NOTES: NO WORK AT CONNECTING CORRIDOR ROOF.
1
CURB IS EXISTING TO REMAIN.
2
PATCH ROOF AT CHILLER OR CONDENSER DUNNAGE OR EXHAUST FAN.
3
SET NEW CURB.
4
PATCH AT VENT PIPE.
usaarchitects.com Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
AREA OF ROOFING TO BE REMOVED AND REPLACED. SEE A-108 FOR MORE INFORMATION
2
DEMOLITION ROOF PLAN CORRIDOR SCALE: 3/32" = 1'-0"
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
1
1
1
EXISTING ROOFING & COPING TO REMAIN AT UPPER ROOF LEVELS.
EXG. ROOF HATCH TO REMAIN.
1 1 1 EXISTING DUCT ENCLOSURE TO REMAIN. EXISTING RELIEF VENT TO BE REMOVED. SEE MECHANICAL DRAWINGS. 2 EXISTING ROOFING & COPING TO REMAIN AT UPPER ROOF LEVELS.
1
1
DEMOLITION LEGEND:
EXISTING ROOFING & COPING TO REMAIN AT UPPER ROOF LEVELS.
1
EXISTING TO REMAIN
1 2
TO BE REMOVED Signature & License No.
GENERAL DEMOLITION NOTES: LOCATION OF EXISTING EQUIPMENT TO BE REMOVED AND REPLACED. SEE MECHANICAL DRAWINGS. 1
1
1
1
ETR
AREA OF ROOFING TO BE REMOVED AND REPLACED. SEE A-108 FOR MORE INFORMATION
ETR
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
1. CONTRACTOR MUST INSTALL AND MAINTAIN PLASTIC DUST BARRIERS DURING DEMOLITION AND CONSTRUCTION TO PROTECT THE GENERAL PUBLIC FROM DUST AND FUMES. LOCATE PARTITIONS REQUIRED TO PROTECT ADJACENT AREAS AND EQUIPMENT, AND CONTINUE EGRESS THROUGH THE SPACE. CONTRACTOR SHALL PROVIDE TEMPORARY EXIT WAYS AS REQUIRED BY LOCAL CODE ENFORCEMENT OFFICIAL DURING CONSTRUCTION.
1
EX8715
2. DO NOT CONSIDER DEMOLITION AND ALTERATION NOTES TO BE ALL INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND ASSESS EACH SPACE AND TO FULFILL THE INTENT OF THE WORK INDICATED BY THE CONTRACT DOCUMENTS. VERIFY ALL DIMENSIONS WITHIN THE CONTRACT LIMITS. BRING DEVIATIONS FROM THE CONTRACT DOCUMENTS TO THE ATTENTION OF THE ARCHITECT. THE EXTENT OF DEMOLITION AND REMOVAL INCLUDES, BUT IS NOT LIMITED TO WORK SHOWN ON THE DRAWINGS. 3. REMOVE ANY MISCELLANEOUS PROJECTIONS, HANGERS, BOLTS, SCREWS AND NAILS FROM EXISTING SURFACES TO REMAIN. PATCH AND PREPARE SURFACES TO RECEIVE NEW FINISH.
ALTERATIONS AT
LOG COLLEGE MIDDLE SCHOOL FOR THE
CENTENNIAL SCHOOL DISTRICT 433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
4. PATCH AND REPAIR ALL ADJACENT SURFACES WHICH ARE AFFECTED BY THE DEMOLITION OR REMOVAL OF ACCESSORIES TO THEIR ORIGINAL FORM AND PREPARE FOR NEW FINISH. COORDINATE WITH FINISH DRAWINGS.
1
5. SEE MEP AND STRUCTURAL DRAWINGS FOR FULL SCOPE OF DEMOLITION. COORDINATE BOILER & CHILLER PAD REMOVAL WITH HVAC. ALL SKYLIGHTS TO REMAIN, TYPICAL .
6. ALL EXISTING CASEWORK, MILLWORK, BUILTINS, CABINETRY, DESKS, & SHELVING ETC. ARE TO REMAIN UNLESS OTHERWISE NOTED.
B ETR
1
03-14-2018 No.
A
2/28/2018 3:06:08 PM
1
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
DEMO ROOF PLAN AREA B - LOG COLLEGE MS
DEMO ROOF PLAN - AREA B SCALE: 3/32" = 1'-0"
Scale
USA Project No.
As indicated
KEY PLAN B - LOG COLLEGE MS SCALE: N.T.S.
Drawing Date
2017-002 Drawing No.
01.08.2018 Drawn By
Checked By
JS
JMc
A-059
CEILING LEGEND DEMOLITION
C2
AREA OF CEILING DEMOLITION (ACT AND GYP/PLASTER AS SHOWN)
C2
C1
GYP-1 GYPSUM/PLASTER
C1
C2
CLASSROOM 15
FACULTY WORKROOM 19-0
CLASSROOM 19
C2
CLASSROOM 20
FACULTY WORKROOM 21-0
CLASSROOM 21
NOT IN SCOPE
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
ACT (NEW)
CLASSROOM 22
2' x 4' ACT
FACULTY WORKROOM 23-0
CLASSROOM 23
CLASSROOM 24
STAIR 3 ST3.1
usaarchitects.com
CLASSROOM 25
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
2' x 4' LIGHT FIXTURE
STAIR 2 ST2.1
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
GENERAL NOTES 1. PROVIDE FIRE-RATED CEILING TILE & GRID IN CORRIDORS. 2. PROVIDE WASHABLE CEILING TILE & GRID IN KITCHEN.
ELECTRIC ROOM 137
FACULTY WORKROOM 25-0
CORRIDOR 111B
3. NEW CEILINGS TO BE AT SAME HEIGHT AFF AS DEMOLISHED CEILINGS. VERIFY CEILING HEIGHTS PRIOR TO DEMOLITION. CORRIDORS - 8'-0" TYPICAL CLASSROOMS - 9'-6" TYPICAL 4. SEE MEP AND STRUCTURAL DRAWINGS FOR MORE ADDITIONAL DEMOLITION INFORMATION.
STORAGE 118
BOILER ROOM 134
STORAGE & MECHANICAL ROOM
ELEV. MECH. RM. EL1 GIRL'S 119 TOILET 1.2 GT1.2
BOY'S TOILET 1.2 BT1.2
HOME MAKING 17
MECH/ STORAGE 138
5. PATCH AND PAINT PLASTER/ GWB BULKHEADS AT EXISTING SKYLIGHT LOCATIONS.
MEN'S TOILET 114
112
LOUNGE 116
IT/ STORAGE 120
RECEIVING & MAINTENANCE 130
C1
FREEZER 136
HOME MAKING 16-1
WT 126
MT 127
REFUSE 107
GUIDANCE 123
C4
WOMEN'S TOILET 115 STORAGE 117
CLASSROOM 26
KITCHEN HELP 108
SELECTIVE DEMOLITION NOTES:
JANITOR CLOSET 109
C1
PATCH PLASTER & PAINT AT EXTERIOR SOFFITS AS REQUIRED.
C2
PROVIDE NEW GWB BULKHEAD AT WINDOWS. RECIEVING NEW WINDOWS. REMOVE EXISTING ACT AS REQUIRED, SAVE FOR REPLACEMENT.
C3
EXISTING BULKHEAD TO REMAIN; PATCH & PAINT AS REQUIRED.
C4
REMOVE EXISTING BULKHEAD & LOUVERS.
C5
SERVING 2 106
FCS 16
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
C2
FOOD STORAGE 110
HALL 125
OFFICE 124
HALL 113
REPLACE ACT ONLY GRID TO REMAIN.
C1
LOCKER 133
GROUNDS EQUIPMENT ROOM
TOILET 132
135
CORRIDOR 16-3
LIVING ROOM 16-2
OFFICE 131
MAIN OFFICE 121
PRINCIPAL OFFICE 122
C3
CORRIDOR 111
APPROXIMATE LOCATIONS OF ACCESS IN CEILING/SOFFIT AS REQ'D FOR ACCESS TO PLUMBING ABOVE, TYP. COORDINATE WITH PLUMBING CONTRACTOR.
CAFETERIA 103
STORAGE 16-4
OFFICE 105C
CORRIDOR 111A
REFRIGERATOR 105B
C2
DARK ROOM 143
C5
KITCHEN 105
FREEZER 105A STORE 140 CORRIDOR 111D
CLASSROOM 11
ART 14
CORRIDOR 111C
CLOSET 142
GIRL'S TOILET 1.1 GT1.1
BOY'S TOILET 1.1 BT1.1
STORAGE 141
MATERIAL STORAGE 9-2
SERVING 1 104 CLOSET 9-1
STORAGE 12-2
STORAGE 13-1 ART 13
C2
WOOD SHOP 12
MATERIAL STORAGE 12-3
C2
FINISH ROOM 12-4
C2
COMPUTER LAB 10
COMPUTER LAB 9
STAIR 1 ST1.1 CLASSROOM 8
Signature & License No.
ENTRANCE VESTIBULE 100
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
APPROXIMATE LOCATIONS OF ACCESS IN CEILING/SOFFIT AS REQ'D FOR ACCESS TO PLUMBING ABOVE, TYP. COORDINATE WITH PLUMBING CONTRACTOR. C2
C2
EX8715
ALTERATIONS
C2 AT
LOG COLLEGE MIDDLE SCHOOL FOR THE
1
GROUND FLOOR REFLECTED CEILING PLAN - AREA A (DEMO)
CENTENNIAL SCHOOL DISTRICT
C1
433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
SCALE: 3/32" = 1'-0"
03-14-2018 No.
2/28/2018 3:06:13 PM
B
A
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
GROUND FLOOR DEMOLITION RCP AREA A - LOG COLLEGE MS Scale
USA Project No.
As indicated Drawing Date
2017-002 Drawing No.
KEY PLAN A - LOG COLLEGE MS
01.08.2018
SCALE: 1" = 100'-0"
Drawn By
Checked By
Author
Checker
A-060
CEILING LEGEND C2
C2
C2
C2
C2
C2
C2
C2 DEMOLITION
CLASSROOM 34
STAIR 2 ST2.2
CLASSROOM 35
CLASSROOM 36
FACULTY WORKROOM 37-0
CLASSROOM 37
FACULTY WORKROOM 40-0
FACULTY WORKROOM 38-0
CLASSROOM 38
CLASSROOM 39
CLASSROOM 40
CLASSROOM 41
CLASSROOM 42
NOT IN SCOPE
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
AREA OF CEILING DEMOLITION (ACT AND GYP/PLASTER AS SHOWN)
STAIR 3 ST3.2
SCIENCE LAB 43
GYP-1 GYPSUM/PLASTER
usaarchitects.com C2
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
ACT (NEW) 2' x 4' ACT
FACULTY WORKROOM 33-0
C2
CORRIDOR 211B
2' x 4' LIGHT FIXTURE
C3
MECH. 231 CLASSROOM 54
CLASSROOM 33
BOY'S TOILET 2.2 BT2.2
GIRL'S TOILET 2.2 GT2.2
CLASSROOM 53
WOMEN'S TOILET 1 228
MECHANICAL EQUIP. OPEN TO ABOVE
MEN'S TOILET 1 229
CORRIDOR 211C
4. SEE MEP AND STRUCTURAL DRAWINGS FOR MORE ADDITIONAL DEMOLITION INFORMATION.
LIBRARY 202
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
5. PATCH AND PAINT PLASTER/ GWB BULKHEADS AT EXISTING SKYLIGHT LOCATIONS.
SCIENCE LAB 44
SELECTIVE DEMOLITION NOTES:
LIBRARY WORKROOM 58
CORRIDOR 211
C1
PATCH PLASTER & PAINT AT EXTERIOR SOFFITS AS REQUIRED.
C2
PROVIDE NEW GWB BULKHEAD AT WINDOWS. RECIEVING NEW WINDOWS. REMOVE EXISTING ACT AS REQUIRED, SAVE FOR REPLACEMENT.
C3
EXISTING BULKHEAD TO REMAIN; PATCH & PAINT AS REQUIRED.
C4
REMOVE EXISTING BULKHEAD & LOUVERS.
C3
LIBRARY WORKROOM 58A
CLASSROOM 52 OFFICE 223
3. NEW CEILINGS TO BE AT SAME HEIGHT AFF AS DEMOLISHED CEILINGS. VERIFY CEILING HEIGHTS PRIOR TO DEMOLITION. CORRIDORS - 8'-0" TYPICAL CLASSROOMS - 9'-6" TYPICAL
CONFERENCE 204
C2
FACULTY WORKROOM 31-0
2. PROVIDE WASHABLE CEILING TILE & GRID IN KITCHEN.
GUIDANCE 226
GUIDANCE 224
C3
1. PROVIDE FIRE-RATED CEILING TILE & GRID IN CORRIDORS.
C2
CONFERENCE ROOM 227
GUIDANCE 225
GENERAL NOTES
STORAGE 210
MECHANICAL EQUIPMENT 203
ELEV. EL2
CLASSROOM 55 MECHANICAL 240
CLASSROOM 32
STORAGE 212
STORAGE 3 230
C2
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
CORRIDOR 211D
C5
HALL 222
REPLACE ACT ONLY GRID TO REMAIN.
SCIENCE LAB 45 CLASSROOM 61
STORAGE 31-1
MAIN OFFICE 220 CLASSROOM 51
C2
MECHANICAL 241
CLASSROOM 50
CLASSROOM 31
PRINCIPAL OFFICE 221
GIRL'S TOILET 2.1 GT2.1
BOY'S TOILET 2.1 BT2.1
CLASSROOM 60
STORAGE 213
STORAGE 214
C2
C3
C2
CORRIDOR 211A
C2
CLASSROOM 30
FACULTY WORKROOM 29-0
CLASSROOM 29
CLASSROOM 28
C2
FACULTY WORKROOM 27-0
C2
CLASSROOM 27
C2
MEN'S TOILET 242
JANITOR CLOSET 245 STAIR 1 ST1.2
WOMEN'S TOILET 243
CLASSROOM 48
FACULTY WORKROOM 47-0
SCIENCE LAB 46
CLASSROOM 47 MECH. 46-0
Signature & License No.
LOUNGE 244
C2
C2
C2
EX8715
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
ALTERATIONS AT
LOG COLLEGE MIDDLE SCHOOL FOR THE
1
CENTENNIAL SCHOOL DISTRICT
UPPER FLOOR DEMOLITION PLAN
433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
SCALE: 3/32" = 1'-0"
03-14-2018 No.
2/28/2018 3:06:18 PM
B
A
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
UPPER FLOOR DEMOLITION RCP AREA A - LOG COLLEGE MS Scale
USA Project No.
As indicated Drawing Date
2017-002 Drawing No.
KEY PLAN A - LOG COLLEGE MS
01.08.2018
SCALE: 1" = 100'-0"
Drawn By
Checked By
Author
Checker
A-061
CEILING LEGEND DEMOLITION
NOT IN SCOPE
AREA OF CEILING DEMOLITION (ACT AND GYP/PLASTER AS SHOWN) GYP-1 GYPSUM/PLASTER EXISTING BULKHEAD TO REMAIN.
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
ACT (NEW) 2' x 4' ACT
CONNECTING CORRIDOR 102
usaarchitects.com
2' x 4' LIGHT FIXTURE
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
GENERAL NOTES
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
1. PROVIDE FIRE-RATED CEILING TILE & GRID IN CORRIDORS. 2. PROVIDE WASHABLE CEILING TILE & GRID IN KITCHEN.
2
3. NEW CEILINGS TO BE AT SAME HEIGHT AFF AS DEMOLISHED CEILINGS. VERIFY CEILING HEIGHTS PRIOR TO DEMOLITION. CORRIDORS - 8'-0" TYPICAL CLASSROOMS - 9'-6" TYPICAL
CORRIDOR REFLECTED CEILING PLAN
4. SEE MEP AND STRUCTURAL DRAWINGS FOR MORE ADDITIONAL DEMOLITION INFORMATION.
SCALE: 3/32" = 1'-0"
5. PATCH AND PAINT PLASTER/ GWB BULKHEADS AT EXISTING SKYLIGHT LOCATIONS. C1
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
HEALTH 157
C1
CORRIDOR 153
NURSE 155
HEALTH 158
JANITOR CLOSET 159
MEN 156
HEALTH CL. 158-1
BOY'S LOCKER ROOM
STAGE 152
CORRIDOR 105A
160
AUDITORIUM 151 STORAGE 161
BOY'S TOILET L35
CORRIDOR 150
CORRIDOR 172 STORAGE 174
C1
STORAGE 173
STORAGE 41C
CORRIDOR 154
Signature & License No.
WOMEN 171
SELECTIVE DEMOLITION NOTES: This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
STORAGE 45 C
C1
PATCH PLASTER & PAINT AT EXTERIOR SOFFITS AS REQUIRED.
C2
PROVIDE NEW GWB BULKHEAD AT WINDOWS. RECIEVING NEW WINDOWS. REMOVE EXISTING ACT AS REQUIRED, SAVE FOR REPLACEMENT.
C3
EXISTING BULKHEAD TO REMAIN; PATCH & PAINT AS REQUIRED.
C4
REMOVE EXISTING BULKHEAD & LOUVERS.
C5
CORRIDOR 105B
PRACTICE ROOM 168
JANITOR CLOSET 167
ALTERATIONS AT
LOG COLLEGE MIDDLE SCHOOL FOR THE
REPLACE ACT ONLY GRID TO REMAIN.
CENTENNIAL SCHOOL DISTRICT
C1
VOCAL 170
EX8715
433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
MUSIC CLASSROOM 169 VOCAL 170-1
GIRL'S LOCKER ROOM
CORRIDOR
163
GIRL'S TOILET L29
B C1 03-14-2018 No.
A
C1
2/28/2018 3:06:21 PM
STORAGE 162
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
DEMOLITION RCP AREA B & CORRIDOR LOG COLLEGE MS Scale
USA Project No.
As indicated
1
REFLECTED CEILING PLAN DEMO - AREA B SCALE: 3/32" = 1'-0"
Drawing Date
KEY PLAN B - LOG COLLEGE MS SCALE: 1" = 100'-0"
2017-002 Drawing No.
01.08.2018 Drawn By
Checked By
Author
Checker
A-062
3 A-300 E
G
F
CLASSROOM 15
E
G
F
CLASSROOM 19
STAIR 2 ST2.1
F2
G19
CLASSROOM 20
CLASSROOM 22
G19-0
F2 G21
G20
F1
G15
CLASSROOM 21
F2
CLASSROOM 23
F2
G22
F1
F1
2. PAINT ALL EXISTING GYPSUM/ PLASTER WALLS ABOVE ALL LOCKERS IN CORRIDORS. PAINT ALL NON-GLAZED BLOCK WALLS IN CORRIDORS.
FACULTY WORKROOM 23-0
F2 G21-0
GENERAL NOTES:
G
F
1. PROVIDE NEW EPOXY PAINT AT FLOOR AND BASE IN ALL MECHANICAL SPACES.
FACULTY WORKROOM 21-0
FACULTY WORKROOM 19-0
F
G
G
G
G23
G23-0
KEY NOTES:
G24 F1
G25
2 A-161
CORRIDOR 111B
134A
138
G17
F3
MECH/ STORAGE 138
HOME MAKING 17
A
A
STORAGE 118
119 BT1.2
BOILER ROOM 134
FACULTY WORKROOM 25-0
G25-0 118
GT1.2
ELEV. EL1
GIRL'S TOILET 1.2 GT1.2
BOY'S TOILET 1.2 BT1.2
MEN'S 114 HALL TOILET 113 114
112 A
MECH. RM. 119
C
STORAGE & MECHANICAL ROOM
A
115
WOMEN'S TOILET 115
F2
B
-NOTE NOT USED-
C
AT DRINKING FOUNTAIN (D.F.) LOCATION, PROVIDE 4'x4' SOLID SURFACE PANEL ON WALL TO COVER OPENING FROM REMOVED D.F.
D
PROVIDE NEW RATED ACCORDIAN DOOR AT STORE WITH LOCK. REUSE EXISTING TRACK. SEE SCHEDULE FOR SPECIFICATIONS.
E
NEW 6 FOOT CASEWORK. UPPER & LOWER CABINETS WITH SINK. COORDINATE WITH PLUMBING. NEW CASEWORK TO HAVE CLEAR MAPLE GINISH WITH BLACK SOLID SURFACE COUNTERTOPS, TYPICAL.
F
-NOTE NOT USED-
G
PATCH AREAS OF ABATED VAT W/ NEW VCT. TYPICAL.
H
INFILL EXISTING AC OPENING TO BE WEATHERTIGHT. MATCH EXISTING BRICK AND CMU
J
PATCH W/ VCT FLOORING.
K
PROVIDE ALUMINUM COVER/ SILL EXTENSION TO COVER AREAS OF PATCHED HARDWOOD FLOORING.
L
PATCH TERRAZZO FLOORING WITH EPOXY TO MATCH EXISTING WHERE ALUMINUM WINDOW HAS BEEN REMOVED.
M
PROVIDE CEMENT BACKER BOARD AND CERAMIC WALL TILE AT BOTH SIDES OF NEW PARTITION.
N
(2) 8" X 16" HOLES IN CMU TO BE INFILLED
usaarchitects.com
G26
112
IT/ STORAGE 120
CLASSROOM 26
STORAGE 117
FOOD STORAGE 110
A
F12
OFFICE 124 130B
FREEZER 136
NEW LOADING DOCK. SEE STRUCTURAL & CIVIL DRAWINGS.
HOME MAKING 16-1
RECEIVING & MAINTENANCE 130
A3
OFFICE 131
CORRIDOR 16-3 STORAGE 16-4
G16-2 130A
135A
C F
MT 127
GUIDANCE 123 CORRIDOR 111
M
JANITOR CLOSET 109
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
SERVING 2 106
106
A1
MAIN OFFICE 121
PRINCIPAL OFFICE 122
G16
KITCHEN HELP 108
REFUSE 107
REPAIR END OF CASEWORK @ REMOVED WALL
A
LIVING ROOM 16-2
A
125
A3
FCS 16
LOCKER 133
WT 126
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
G
120
HALL 125
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
116A
LOUNGE 116
NEW 42" GALV. PIPE GUARDRAIL AND HANDRAIL AT EXISTING STAIR.
135B
PREP. CONC. SLAB FOR NEW FLOOR FINISH.
F3 C
GROUNDS EQUIPMENT TOILET ROOM 132 135
A F2
F
ELECTRIC ROOM 137
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
3. PAINT ALL ELECTRICAL PANELS AND CABINET HEATER COVERS.
CLASSROOM 25
STAIR 3 ST3.1
F2
F1
F1
CLASSROOM 24
OFFICE 105C
CAFETERIA 103
121
122 F7
1 A-300
C
1 A-161
CORRIDOR 111A
REFRIGERATOR 105B KITCHEN 105
F 141
G12
WOOD SHOP 12-1
N
ART 14
DARK ROOM 143
F8
GT1.1
CORRIDOR GIRL'S 111C 1.1 TOILET CLOSET 142 G11A GT1.1 142
CLASSROOM 11
STORE 140
BT1.1
FREEZER 105A
140
BOY'S TOILET 1.1 BT1.1
D
STORAGE 141
A
MATERIAL STORAGE 9-2
G14 F11
M G08
CLOSET 9-1
104
F1
G
L
G13
F10
WOOD SHOP 12
G09
G10
STORAGE 12-2
ART 13
G COMPUTER LAB 10
MATERIAL STORAGE 12-3
K
FINISH ROOM 12-4
STAIR 1 ST1.1
COMPUTER LAB 9
G
ENTRANCE 101
CLASSROOM 8
G
ENTRANCE VESTIBULE 100
L
G
A1
A
A
SERVING 1 104
A1 F9
STORAGE 13-1
2 A-300
Signature & License No.
102A E
E
E
E
1 A-160
1
E
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
M
CONNECTING CORRIDOR 102
4 A-300
H
EX8715
ALTERATIONS
PROPOSED GROUND FLOOR PLAN
AT
SCALE: 3/32" = 1'-0" LOG COLLEGE MIDDLE SCHOOL FOR THE
STRUCTURE ABOVE STRUCTURE ABOVE
SEALANT BOTH SIDES WHERE DRYWALL EXTENDS TO UNDERSIDE OF DECK ABOVE.
CENTENNIAL SCHOOL DISTRICT
SEALANT, TYPICAL
433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
CONTINUOUS METAL TOP RUNNER
CONTINUOUS METAL TOP RUNNER
ONE LAYER GYPSUM BOARD, TYPICAL
EXTEND DRYWALL 6" ABOVE CEILING WHERE SCHEDULED. 6"
METAL STUD, PROVIDE BRACING BACK TO WALL @ 48" O.C. - PROVIDE MINIMUM ONE BRACE AT MIDSPAN
ONE LAYER GYPSUM BOARD, EACH SIDE SCHEDULED CEILING.
METAL STUD ACOUSTIC INSULATION WHERE SCHEDULED CONTINUOUS METAL BOTTOM RUNNER
ACOUSTIC INSULATION WHERE SCHEDULED CONTINUOUS METAL BOTTOM RUNNER
SEALANT SUBFLOOR
SEALANT BOTH SIDES SUBFLOOR VARIES SEE PLAN
2
A-WALL DETAIL SCALE: 1 1/2" = 1'-0"
3
2/28/2018 3:06:27 PM
NOTE: PARTITION TYPE A1 TO HAVE CEMENT BACKER BOARD IN LIEU OF GWB. GYP. BD. GYPSUM BOARD HEIGHT MARK STUD SIZE THICKNESS A1 3-5/8" 5/8" 6" ABOVE FINISHED CEILING A3 3-5/8" 5/8" FULL HEIGHT TO STRUCTURE ABOVE
A
GYPSUM PARTITION WALL TYPE
03-14-2018
C-WALL DETAIL
No.
SCALE: 1 1/2" = 1'-0"
NOTE: WALL TYPES ARE NUMBERED SEQUENTIALLY. IF WALL TYPES SKIP SEQUENCE, THE OMITTED TYPE IS NOT USED.
NOTE: PARTITION TYPE C2 TO HAVE CEMENT BACKER BOARD IN LIEU OF GWB. TOTAL PARTITION THICKNESS 4 7/8"
ACOUSTIC INSULATION NO
STC RATING -
FIRE RATING / UL DESIGN NO. -
4 7/8"
YES
-
-
GYP. BD. GYPSUM BOARD HEIGHT MARK STUD SIZE THICKNESS C2 3-5/8" 5/8" FULL HEIGHT TO STRUCTURE ABOVE
TOTAL PARTITION THICKNESS 4 1/4"
ACOUSTIC INSULATION YES
STC RATING -
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
B
A
FIRE RATING / UL DESIGN NO. -
GROUND FLOOR PLAN AREA A - LOG COLLEGE MS Scale
USA Project No.
As indicated
B
GYPSUM PARTITION WALL TYPE
C
GYPSUM PARTITION WALL TYPE
D
SHAFT PARTITION WALL TYPE
E
MASONRY WALL TYPE
F
Drawing Date
MASONRY WALL TYPE
2017-002 Drawing No.
01.08.2018
KEY PLAN A - LOG COLLEGE MS
Drawn By
Checked By
SCALE: N.T.S.
ChaW
JMc
A-104
3 A-300 A
A
A
A
A
A
A
A
GENERAL NOTES: G
G
STAIR 2 ST2.2
CLASSROOM 34
CLASSROOM 35
FACULTY WORKROOM 37-0
CLASSROOM 36
F2 U36
G
A
U34
FACULTY WORKROOM 33-0
F2
G
G
U35
F1
CLASSROOM 37
CLASSROOM 38
F2
U37
U38
CLASSROOM 39
U39
F3
CORRIDOR 211B
U33-0
U40
F1
CLASSROOM 42
STAIR 3 ST3.2
F1
F1
U42
4 A-161 F2
G
A
U55
F2
231
240
CLASSROOM 54
CLASSROOM 33
CLASSROOM 55
BT2.2
U43
GT2.2
GUIDANCE 225
6 A-300
8 A-300
CORRIDOR 211C U32
FACULTY WORKROOM 31-0
F2
CLASSROOM 52
F2 U31-0 F2
STORAGE 31-1
1 A-300
U31
F2
GUIDANCE 224
228
NEW 6 FOOT CASEWORK. UPPER & LOWER CABINETS WITH SINK. COORDINATE WITH PLUMBING. NEW CASEWORK TO HAVE CLEAR MAPLE GINISH WITH BLACK SOLID SURFACE COUNTERTOPS, TYPICAL.
F
-NOTE NOT USED-
G
PATCH AREAS OF ABATED VAT W/ NEW VCT. TYPICAL.
H
INFILL EXISTING AC OPENING TO BE WEATHERTIGHT. MATCH EXISTING BRICK AND CMU
J
PATCH W/ VCT FLOORING.
K
PROVIDE ALUMINUM COVER/ SILL EXTENSION TO COVER AREAS OF PATCHED HARDWOOD FLOORING.
L
PATCH TERRAZZO FLOORING WITH EPOXY TO MATCH EXISTING WHERE ALUMINUM WINDOW HAS BEEN REMOVED.
M
PROVIDE CEMENT BACKER BOARD AND CERAMIC WALL TILE AT BOTH SIDES OF NEW PARTITION.
N
(2) 8" X 16" HOLES IN CMU TO BE INFILLED
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
U58
LIBRARY WORKROOM 58A
OFFICE 223
U58A F2
SCIENCE LAB 45
U56
F2
F6 220
MAIN OFFICE 220 MECHANICAL 241
BOY'S TOILET 2.1 BT2.1
A
CLASSROOM 31
241
BT2.1
CLASSROOM 61 A F6
2 A-300 E
GIRL'S TOILET 2.1 GT2.1
221A
F2
PRINCIPAL OFFICE 221
GT2.1
CLASSROOM 60
202B
U50
STORAGE 213
STORAGE 214
U60
221C
C
A
U45
A
G
E
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
LIBRARY 202
MEN'S TOILET 1 229
A3
B
C
A
LIBRARY WORKROOM 58
HALL 222
CLASSROOM 50
PROVIDE NEW RATED ACCORDIAN DOOR AT STORE WITH LOCK. REUSE EXISTING TRACK. SEE SCHEDULE FOR SPECIFICATIONS.
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
F2
5 A-300
7 A-300
CLASSROOM 51
D
SCIENCE LAB 44
F4
204A
F6
U51
F2
CONFERENCE 204
CORRIDOR 211
226A WOMEN'S TOILET 1
U52 F2
AT DRINKING FOUNTAIN (D.F.) LOCATION, PROVIDE 4'x4' SOLID SURFACE PANEL ON WALL TO COVER OPENING FROM REMOVED D.F.
A
GUIDANCE 226
A3
B
COURT UC
U44
F2
CONFERENCE ROOM 227
F2
CLASSROOM 32
C
usaarchitects.com
A C
227
CLASSROOM 53
-NOTE NOT USED-
F6
U53
G
ELEV. EL2
U54 F2
A
MECHANICAL EQUIPMENT 203
A
C F2
B
STORAGE 210
202A
A
BOY'S TOILET 2.2 BT2.2
MECHANICAL 240
STORAGE 212
203
MECH. 231
GIRL'S TOILET 2.2 GT2.2
A
STORAGE 3 230
232
PREP. CONC. SLAB FOR NEW FLOOR FINISH.
A
E
C
A
U41
F3 U33
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
KEY NOTES:
SCIENCE LAB 43
F2 U40-0
3. PAINT ALL ELECTRICAL PANELS AND CABINET HEATER COVERS.
A
CLASSROOM 41 F2
F1
F1
2. PAINT ALL EXISTING GYPSUM/ PLASTER WALLS ABOVE ALL LOCKERS IN CORRIDORS. PAINT ALL NON-GLAZED BLOCK WALLS IN CORRIDORS.
CLASSROOM 40
F2 U38-0
1. PROVIDE NEW EPOXY PAINT AT FLOOR AND BASE IN ALL MECHANICAL SPACES.
G
FACULTY WORKROOM 40-0
FACULTY WORKROOM 38-0
F2 U37-0
G
G
U46 F4 F2
CORRIDOR 211A
F1
G
A
F1
U30
F1
U29
U29-0
U27-0
2 A-105 F1
F1
U28
E
3 A-161
U27
A
U27A 242
F3
CLASSROOM 30
F3
FACULTY WORKROOM 29-0
F2
CLASSROOM 29
CLASSROOM 28
F2
FACULTY WORKROOM 27-0
CLASSROOM 27
MEN'S TOILET 242
245
U47-0
F2
JANITOR CLOSET 245
STAIR 1 ST1.2
CLASSROOM 48
U46-0
F1
U48
A
A
U47 F2
FACULTY WORKROOM 47-0
SCIENCE LAB 46
A
CLASSROOM 47
MECH. 46-0
244 G
A
G
A
G
WOMEN'S TOILET 243
LOUNGE 244
G
G
A
A
Signature & License No.
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
A
A
4 A-300
1
EX8715
ALTERATIONS AT
PROPOSED UPPER FLOOR PLAN SCALE: 3/32" = 1'-0"
LOG COLLEGE MIDDLE SCHOOL T.O.STL. UPPER FLOOR +26' - 0"
FOR THE
CENTENNIAL SCHOOL DISTRICT 433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
6'-0" 2X 36" WIDE CABINETS
2'-10"
SOLID SURFACE TOP
2
UPPER FLOOR PLAN +13' - 0"
SCIENCE LAB ELEVATION SCALE: 1/4" = 1'-0" 03-14-2018 No.
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
2/28/2018 3:06:30 PM
B
A
UPPER FLOOR PLAN AREA A - LOG COLLEGE MS Scale
USA Project No.
As indicated Drawing Date
2017-002 Drawing No.
01.08.2018
KEY PLAN A - LOG COLLEGE MS
Drawn By
Checked By
SCALE: N.T.S.
ChaW
JMc
A-105
1 A-301
D
D
D
D
D
CONNECTING CORRIDOR 102
D
D
D
D
D
M 102B
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
M 21'-2 1/4"
21'-4"
21'-4"
21'-4"
21'-4"
R.O. - V.I.F.
R.O. - V.I.F.
R.O. - V.I.F.
R.O. - V.I.F.
R.O. - V.I.F.
13'-10"
13'-10"
13'-10"
13'-10"
13'-10"
D
D
D
8 A-140
102A
usaarchitects.com
102B
D
D
D
D
D
D
A1 4 A-301
2
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
D
7 A-140
REPLACE WOOD SILL WITH NEW SLATE SILL TO MATCH ADJACENT EXISTING SLATE SILLS.
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
6
5
A-140
A-140
NEW INFILL CAVITY WALL: EXTERIOR FACE -SALVAGED FACE BRICK (PROVIDED BY OWNER) -1" MIN. AIR SPACE -WEATHER BARRIER (EP HENRY "BLUE SKIN") -3/4" EXTERIOR SHEATHING (DENSGLASS) -3 5/8" METAL STUD -R-15 BATT INSULATION (3.5") -CEMENT BACKER BOARD -CERAMIC TILE FINISH (TO MATCH SIZE OF EXISTING GLAZED BLOCK) INTERIOR FACE 5 A-301
PROPOSED CORRIDOR FLOOR PLAN SCALE: 3/32" = 1'-0"
DN
HEALTH 157
HEALTH 158
153
155
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
DN
UP
JANITOR CLOSET 159
3 A-301
157 A
156
159 158
HEALTH CL. 158-1 160
CORRIDOR 153
NURSE 155
MEN 156 CORRIDOR 105A
STAGE 152
BOY'S LOCKER ROOM 160
DN
166
AUDITORIUM 151
151A
A
STORAGE 161 7 A-601
NEW HM FRAME TO BE FULL WIDTH OF CORRIDOR, V.I.F.
CORRIDOR 150
REINSTALL SALVAGE FIRE EXT. CABINET AT SAME HEIGHT. CUT AND PATCH BRICK AS REQUIRED.
BOY'S GYM CBG
CORRIDOR 172
145 6 A-601
151B
UP
STORAGE 173
STORAGE 174
CORRIDOR 154
GENERAL NOTES: 1. PROVIDE NEW EPOXY PAINT AT FLOOR AND BASE IN ALL MECHANICAL SPACES.
GIRL'S GYM GG
UP 150A
WOMEN 171
2. PAINT ALL EXISTING GYPSUM/ PLASTER WALLS ABOVE ALL LOCKERS IN CORRIDORS. PAINT ALL NON-GLAZED BLOCK WALLS IN CORRIDORS. 154 3. PAINT ALL ELECTRICAL PANELS AND CABINET HEATER COVERS.
171 150B 150C
KEY NOTES: A
PREP. CONC. SLAB FOR NEW FLOOR FINISH.
B
-NOTE NOT USED-
C
AT DRINKING FOUNTAIN (D.F.) LOCATION, PROVIDE 4'x4' SOLID SURFACE PANEL ON WALL TO COVER OPENING FROM REMOVED D.F.
D
PROVIDE NEW RATED ACCORDIAN DOOR AT STORE WITH LOCK. REUSE EXISTING TRACK. SEE SCHEDULE FOR SPECIFICATIONS.
Signature & License No.
2 A-601
CORRIDOR 105B
170 169
2 A-301
VOCAL 170
E
UP 164
168 PRACTICE ROOM 168
163
JANITOR CLOSET A 167
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
ALTERATIONS
NEW 6 FOOT CASEWORK. UPPER & LOWER CABINETS WITH SINK. COORDINATE WITH PLUMBING. NEW CASEWORK TO HAVE CLEAR MAPLE GINISH WITH BLACK SOLID SURFACE COUNTERTOPS, TYPICAL.
AT
LOG COLLEGE MIDDLE SCHOOL MUSIC CLASSROOM 169
F
-NOTE NOT USED-
G
PATCH AREAS OF ABATED VAT W/ NEW VCT. TYPICAL.
CENTENNIAL SCHOOL DISTRICT
H
INFILL EXISTING AC OPENING TO BE WEATHERTIGHT. MATCH EXISTING BRICK AND CMU
433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
J
PATCH W/ VCT FLOORING.
K
PROVIDE ALUMINUM COVER/ SILL EXTENSION TO COVER AREAS OF PATCHED HARDWOOD FLOORING.
L
PATCH TERRAZZO FLOORING WITH EPOXY TO MATCH EXISTING WHERE ALUMINUM WINDOW HAS BEEN REMOVED.
M
PROVIDE CEMENT BACKER BOARD AND CERAMIC WALL TILE AT BOTH SIDES OF NEW PARTITION.
N
(2) 8" X 16" HOLES IN CMU TO BE INFILLED
FOR THE
A
VOCAL 170-1
167
GIRL'S LOCKER ROOM 163 6 A-301
STORAGE 162
EX8715
B 03-14-2018
A
No.
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
2/28/2018 3:06:32 PM
A 1
PROPOSED FLOOR PLAN AREA B
FLOOR PLAN AREA B & CORRIDOR - LOG COLLEGE MS
SCALE: 3/32" = 1'-0" Scale
USA Project No.
As indicated Drawing Date
2017-002 Drawing No.
KEY PLAN B - LOG COLLEGE MS
01.08.2018
SCALE: N.T.S.
Drawn By
Checked By
ChaW
JMc
A-106
GENERAL NOTES: 1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
1. CONTRACTOR TO SURVEY THE EXISTING ROOF TO LOCATE EXISTING ROOF TOP EQUIPMENT AND COORDINATE THEIR WORK REGARDING FLASHING CURBS ACCORDINGLY. 2. REPLACE ROOF DRAIN BODIES ON LOWER ROOF OF AREA B.
usaarchitects.com
KEY NOTES:
1
ETR
1
PROVIDE ROOF CUT, BLOCKING, SET & FLASH CURB. CURB PROVIDED BY OTHERS.
2
SET NEW CURB. MODIFY ROOF OPENING & BLOCKING AS REQUIRED.
3
FLASH NEW DRYER VENT.
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
1
PROVIDE 2'X2' CURB.
ETR
ETR
ETR
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
NEW EQUIPMENT. SEE MECHANICAL DRAWINGS.
2 ETR
PROVIDE NEW CURB.
3 ETR PATCH
AREA OF ROOF TO BE PATCHED.
ETR
ETR
PROVIDE 2'X2' CURB. 1 PROVIDE 1'X1' CURB.
ETR 1
1
ETR 1
1
1
Signature & License No.
EX8715
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
ALTERATIONS
1
ROOF PLAN - AREA A
AT
SCALE: 3/32" = 1'-0" LOG COLLEGE MIDDLE SCHOOL FOR THE
CENTENNIAL SCHOOL DISTRICT 433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
03-14-2018 No.
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
2/28/2018 3:06:35 PM
B
A ROOF PLAN AREA A LOG COLLEGE MS Scale
USA Project No.
As indicated Drawing Date
2017-002 Drawing No.
KEY PLAN A - LOG COLLEGE MS
01.08.2018
SCALE: N.T.S.
Drawn By
Checked By
JS
JMc
A-107
GENERAL NOTES: 1. CONTRACTOR TO SURVEY THE EXISTING ROOF TO LOCATE EXISTING ROOF TOP EQUIPMENT AND COORDINATE THEIR WORK REGARDING FLASHING CURBS ACCORDINGLY. 2. REPLACE ROOF DRAIN BODIES ON LOWER ROOF OF AREA B.
KEY NOTES: EXISTING ROOF AND COPING AT CONNECTING CORRIDOR - NO NEW WORK.
1
PROVIDE ROOF CUT, BLOCKING, SET & FLASH CURB. CURB PROVIDED BY OTHERS.
2
SET NEW CURB. MODIFY ROOF OPENING & BLOCKING AS REQUIRED.
3
FLASH NEW DRYER VENT.
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174 usaarchitects.com
2
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
PROPOSED ROOF PLAN CORRIDOR SCALE: 3/32" = 1'-0"
HATCH SHOWS AREA OF LOWER ROOF TO RECEIVE NEW ROOFING.
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
2 ETR
A-140
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
2
2
A-140
2
A-140
1 A-140
ETR
ETR NEW ROOF TOP MECH. EQUIP, PROVIDE CURB. SEE MECHANICAL DRAWINGS.
EXISTING ROOFING & COPING TO REMAIN AT UPPER ROOF LEVELS.
EXG. ROOF HATCH TO REMAIN.
ETR 2 NEW ROOF TOP EQUIPMENT. PROVIDE CURB.
EXISTING DUCT ENCLOSURE TO REMAIN. PROVIDE NEW ROOFING.
ETR
2 EXISTING ROOFING & COPING TO REMAIN AT UPPER ROOF LEVELS.
2
ETR
ETR
2
EXISTING ROOFING & COPING TO REMAIN AT UPPER ROOF LEVELS.
NEW ALUMINUM COPING AT LOCATIONS W/ EXISTING EXPOSED PRE-CAST COPING AT LOWER ROOF LEVEL. PROVIDE AT ENTIRE PERIMETER OF LOWER ROOF.
A-140 ETR
ETR NEW ROOF TOP EQUIPMENT. PROVIDE CURB.
2
2 Signature & License No.
ETR
EX8715
2 This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
ETR
ETR
ALTERATIONS
2 A-140
AT
ETR
LOG COLLEGE MIDDLE SCHOOL FOR THE
HATCH SHOWS AREA OF LOWER ROOF TO RECEIVE NEW ROOFING.
CENTENNIAL SCHOOL DISTRICT 433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
ETR
2 A-140
ETR 2 A-140
B 03-14-2018 No.
A
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
2/28/2018 3:08:04 PM
ROOF PLAN AREA B LOG COLLEGE MS 1
ROOF PLAN - AREA B Scale
SCALE: 3/32" = 1'-0"
USA Project No.
As indicated
KEY PLAN B - LOG COLLEGE MS SCALE: N.T.S.
Drawing Date
2017-002 Drawing No.
01.08.2018 Drawn By
Checked By
JS
JMc
A-108
GENERAL NOTES: MECHANICAL EQUIPMENT- SEE SPECS
ROOF MEMBRANE - RUN FLASHING UP AND OVER CURB AND FASTEN ON INSIDE FACE OF CURB.
MEMBRANE FLASHING AND COUNTER FLASHING AT EXISTING PARAPET
VARIES, V.I.F.
EXISTING PRECAST CONCRETE PARAPET TO REMAIN
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
EXISTING FLOOR SLAB AND METAL DECKING
REPLACE CANT STRIP AT EXISTING PARAPET ROOF MEMBRANE TO BE REPAIRED AS NECESSARY EXISTING DECKING & ROOF STRUCTURE TO REMAIN
CEILING TILE SUPPORTS, TYP.
usaarchitects.com Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
SUSPENDED ACOUSTICAL CEILING TILE
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
6 3/8"
ROOF MEMBRANE
COORDINATE WITH DUCTWORK
CEILING TILE SUPPORTS, TYP.
MATCH EXISTING
8" MIN.
FIBROUS CANT STRIP, TYPICAL
2'-5 7/8"
EXISTING FLOOR SLAB AND METAL DECKING
2 X 6 BLOCKING AT T.O. EXISTING PARAPET FOR NEW COPING FASTENERS 12" O.C.
1. GREY HATCH REPRESENTS EXISTING CONSTRUCTION TO REMAIN, TYPICAL.
BRACE AS REQ'D
COPING AT T.O. PARAPET
EXISTING DECKING & STRUCTURE TO REMAIN 2 X 4 FIRE RETARDANT TREATED WOOD BLOCKING TO MATCH EXISTING ROOF DECK HEIGHT
CORNER BEAD AT EDGES, TYP.
SUSPENDED ACOUSTICAL CEILING TILE
ALIGN
5/8" GYPSUM BOARD SOFFIT ON STEEL FRAMING
5/8" GYPSUM BOARD SOFFIT ON STEEL FRAMING
FRAMING FOR DROP CEILING
CORNER BEAD AT EDGES, TYP.
1
EQUIPMENT CURB DETAIL
2
SCALE: 1 1/2" = 1'-0"
ROOF PARAPET DETAIL
3
SCALE: 1 1/2" = 1'-0"
ACT TRANSITION DETAIL
4
SCALE: 1 1/2" = 1'-0"
ACT TRANSITION DETAIL2 SCALE: 1 1/2" = 1'-0"
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
EXISTING PRECAST PARAPET. WINDOW FRAME HEAD WITH RECEPTOR. SHIM AS REQUIRED.
INTERIOR
EXTERIOR
INSULATED METAL PANEL.
PROVIDE CONTINUOUS INSULATION TO DECK ABOVE
BRACE TO MTL. DECK ABOVE
INTERIOR
EXTERIOR
PROVIDE WOOD STUD BLOCKING AT WINDOW HEAD ANCHORED TO EXISTING CMU WALL
CONTINUE INSULATION TO DECK ABOVE EXISTING PRECAST CONCRETE PARAPET
EXISTING PRECAST CONCRETE PARAPET
DRIP EDGE
DRIP EDGE
4" BRICK TO MATCH EXISTING REFER TO ELEVATION SHEETS (BRICK PROVIDED BY OWNER, TYP.)
EXISTING BULKHEAD AT WINDOW.
PROVIDE SPRAY FOAM AIR SEAL BETWEEN TRANSITION STRIP & NEW WINDOW. PROVIDE SEALANT & BACKER ROD, BOTH INTERIOR & EXTERIOR, FULL PERIMETER. 4" BRICK TO MATCH EXISTING REFER TO ELEVATION SHEETS
NEW ACT, SEE CEILING PLANS
NEW ACT, SEE CEILING PLANS
REINSTALL SALVAGED CEILING TILES & ALIGN WITH BULK HEAD AT CEILING INTERMEDIATE MULLION.
EXTERIOR
EXISTING EXTERIOR BRICK
SALVAGED EXTERIOR BRICK TO MATCH EXISTING
UPPER FLOOR CLG
5/8" GYPSUM CEMENTBOARD
4" BRICK TO MATCH EXISTING REFER TO ELEVATION SHEETS FOR TYPE
3 5/8" COLD FORMED METAL FRAMING @ 1'-4" O.C.
1" AIR SPACE AIR/VAPOR BARRIER; EP HENRY BLUE SKIN (BOD AVB PRODCUT)
SPECIFIED PROFILE SCHLUTER QUADEC-K
THRU WALL FLASHING W/ WEEPS
EXISTING EXTERIOR WALL TO REMAIN, CAULK ALL INTERIOR EDGES
5
LINE OF TILED WALL BEYOND BRICK BEYOND
NEW WINDOW WITH INSULATED GLAZING UNIT
SEALANT AND BR, BOTH SIDES; TYPICAL.
SALVAGE & CUT EXISTING SLATE WINDOW SILLS FOR REINSTALLATION.
ALUMINUM SILL
EXISTING EXTERIOR WALL
INTERMEDIATE MULLION. LINE OF WALL ABOVE
PT BLOCKING, AS REQUIRED; TYPICAL AT WINDOW LOCATIONS.
SPECIFIED PROFILE SCHLUTER QUADEC-K INTERIOR
10"
10"
OVERALL EXTERIOR WALL, V.I.F.
OVERALL EXTERIOR WALL, V.I.F.
BRICK INFILL SECTION DETAIL
6
SCALE: 1 1/2" = 1'-0"
BRICK INFILL WINDOW DETAIL
7
SCALE: 1 1/2" = 1'-0"
TYPICAL WINDOW SYSTEM
MORTAR
10"
5/8" EXTERIOR GYPSUM SHEATHING BRICK TIES @ 16" O.C. VERTICAL
SPECIFIED CERAMIC TILE TO MATCH THE SHAPE OF GLAZED BLOCK
OVERALL EXTERIOR WALL, V.I.F.
NEW WINDOW W/ INSULATED GLAZING UNIT
SPECIFIED TILE TO MATCH ADJACENT CMU
BRICK INFILL PLAN DETAIL SCALE: 1 1/2" = 1'-0" ALUMINUM SILL . SELF ADHERED MEMBRANE SILL FLASHING WITH 1" MIN END DAM TURN UP AT JAMBS. TURN DOWN FACE OF EXTERIOR WALL UNDER ALUM SILL FLASHING. APPLY MANUFACTURER'S RECOMMENDED SEALANT TERMINATION AT ALL EDGES AND SEAMS.
EXTERIOR
NEW WINDOW W/ INSULATED GLAZING UNIT
PATCH VCT AS REQ'D.
UPPER FLOOR
Signature & License No.
EX8715
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
ALUMINUM SILL FLASHING.
ALTERATIONS EXISTING PRECAST PANEL. AT
SEALANT AT WINDOW MULLION
LOG COLLEGE MIDDLE SCHOOL EXTERIOR BRICK
FOR THE
EXISTING CMU AIR SPACE RIGID INSULATION
PROVIDE FULL PERIMETER TRANSITION STRIP TO SEAL ACCENT PANEL TO INTERIOR CMU. SIZE TO RECESS FROM OUTER EDGES OF NEW WINDOW 1/4"
CENTENNIAL SCHOOL DISTRICT BREAK METAL CLOSURE
PROVIDE SPRAY FOAM AIR SEAL BETWEEN TRANSITION STRIP & NEW WINDOW. PROVIDE SEALANT & BACKER ROD,BOTH INTERIOR & EXTERIOR, FULL PERIMETER
EXISTING STEEL COMPONENTS TO REMAIN
EXISTING WALL
WINDOW FLANGE ATTACHED TO CMU & COVERED WITH SNAP ON CLOSURE TRIM
433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
LINE OF WALL ABOVE, V.I.F. INTERIOR
WINDOW JAMB EXTRUSION, TYP
PROVIDE WOOD STUD BLOCKING AT WINDOW ANCHORED TO EXISTING CMU.
SPECIFIED PROFILE SCHLUTER QUADEC-K SPECIFIED TILE TO MATCH ADJACENT CMU
INSULATED GLASS GROUND FLOOR CLG
8
TYPICAL JAMB AT BRICK SCALE: 1 1/2" = 1'-0"
9
WALL AT WINDOW PLAN DETAIL SCALE: 1 1/2" = 1'-0"
10
GLAZED TILE PLAN DETAIL SCALE: 3" = 1'-0"
ALUMINUM SILL FLASHING WITH 1" DRIP EDGE SELF ADHERED MEMBRANE SILL FLASHING WITH 1" MIN END DAM TURN UP AT JAMBS. TURN DOWN FACE OF EXTERIOR WALL UNDER ALUM SILL FLASHING. APPLY MANUFACTURER'S RECOMMENDED SEALANT TERMINATION AT ALL EDGES AND SEAMS.
SUBSILL SET IN FULL BED OF SEALANT CONTINUOUS PERIMETER BACKER ROD & SEALANT EXISTING CONCRETE BUILDING SLAB, PATCH VCT AS REQ'D. GROUND FLOOR
03-14-2018 No.
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
2/28/2018 3:08:07 PM
DETAILS Scale
11
USA Project No.
TYPICAL WINDOW OPENING DETAILS
As indicated
SCALE: 1 1/2" = 1'-0"
Drawing Date
2017-002 Drawing No.
01.08.2018 Drawn By
Checked By
Author
Checker
A-140
11 A-160 CEILING LOWER FLR +9' - 6"
8 A-160 13
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
11 A-160
A-160 F 2'-0"
21'-0 3/8"
8'-0"
1X CAB.
7X 36" WIDE CABINETS
4X 24" WIDE CUBBIES
GROUND FLOOR PLAN - AREA A +0' - 0"
2
1X CAB
2'-0"
usaarchitects.com
ENLARGED NORTH ELEVATION ART ROOM 13
3
SCALE: 1/4" = 1'-0"
ENLARGED EAST ELEVATION ART ROOM 13
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
SCALE: 1/4" = 1'-0"
8
10
9
A-160
A-160
A-160
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
CEILING LOWER FLR +9' - 6" KILN HOOD/EXHAUST
CLEAN & PAINT COLUMN
12
8 A-160
7
8X 36" WIDE CABINETS
6
KILN A-160
ART 14
GROUND FLOOR PLAN - AREA A +0' - 0"
F8
4
ENLARGED WEST ELEVATION ART ROOM 13
5
SCALE: 1/4" = 1'-0"
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
ENLARGED SOUTH ELEVATION ART ROOM 13 SCALE: 1/4" = 1'-0"
12
10
A-160
A-160
Sim 13
9
A-160
A-160
Sim CEILING LOWER FLR +9' - 6"
G13
UPPER CABINETS
G14
8'-0"
24'-0"
A-160
13 A-160
F9
GROUND FLOOR PLAN - AREA A +0' - 0"
13-1A
STORAGE 13-1
21'-0"
2 PROVIDE TRANSITION STRIP CERAMIC VCT TILE
KILN
9 A-160
MOUNTED TO WALL WITH CLEATS
FIXED TO WALL
ADJUSTABLE SHELF ON RECESSED STANDARDS
3 11
10
5
EXISTING COLUMN BEYOND
SATIN ALUMINUM WIRE PULLS (TYP.)
A-160
A-160
ADJUSTABLE SHELF ON RECESSED STANDARDS
EXISTING 6" X 6" COLUMN, PAINTED.
A1
1'-6"
4'-7"
CORIAN COUNTER W/INTEGRATED BACK-SPLASH
10'-8"
4" DRAWER
18'-0"
PROPOSED ART ROOM PLAN
2'-0 1/4" TYP.
9X 24" WIDE CABINETS
1
SCALE: 1/4" = 1'-0"
COUNTER/BACK SPLASH RETURNS @ WINDOW MULLION
2'-6" TYP.
3 1/2"
VINYL BASE
PROVIDE INFILL STUD FRAMING AS REQ'D.
GROUND FLOOR PLAN - AREA A +0' - 0"
CASEWORK SECTION 1
9
SCALE: 1" = 1'-0"
EXISTING WINDOW SILL
GROUND FLOOR PLAN - AREA A +0' - 0" 2 X 4 F.R. BASE BLOCKING
CASEWORK SECTION 2 SCALE: 1" = 1'-0"
FOR THE
CENTENNIAL SCHOOL DISTRICT
VINYL BASE
2 X 4 F.R. BASE BLOCKING
433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
GROUND FLOOR PLAN - AREA A +0' - 0" 2 X 4 F.R. BASE BLOCKING
10
CASEWORK SECTION 3 SCALE: 1" = 1'-0"
SPECIFIED FIXTURES (SEE PLUMBING DRAWINGS) SOLID SURFACING W/INTEGRATED BACK-SPLASH
TYP. SPECIFIED FIXTURES 10"
SOLID SURFACING W/INTEGRATED BACK-SPLASH
LOG COLLEGE MIDDLE SCHOOL
ADJUSTABLE SHELF ON RECESSED STANDARDS
VINYL BASE
2'-0 1/4"
AT
SATIN ALUMINUM WIRE PULLS (TYP.)
ADJUSTABLE SHELF ON RECESSED STANDARDS
8
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
FULL HEIGHT WINDOW
NYLON GLIDES, TYP.
NYLON GLIDES, TYP.
SATIN ALUMINUM WIRE PULLS (TYP.)
4" DRAWER
FIXED PANEL FRONT 03-14-2018
FIXED PANEL FRONT
NYLON GLIDES, TYP.
ADJUSTABLE SHELF ON RECESSED STANDARDS
REMOVABLE PANEL TO CONCEAL TRAP
VINYL BASE
VINYL BASE
VINYL BASE
GROUND FLOOR PLAN - AREA A +0' - 0"
11
CASEWORK SECTION 4 SCALE: 1" = 1'-0"
GROUND FLOOR PLAN - AREA A +0' - 0" 2 X 4 F.R. BASE BLOCKING
12
CASEWORK SECTION 5 SCALE: 1" = 1'-0"
13
CASEWORK SECTION 6 SCALE: 1" = 1'-0"
Date
Issue or Revision
ENLARGED ART ROOM GROUND FLOOR PLAN - AREA A +0' - 0"
2 X 4 F.R. BASE BLOCKING
ISSUED FOR CONSTRUCTION
Drawing Title
2'-10"
2'-6"
SATIN ALUMINUM WIRE PULLS (TYP.)
2'-6"
2/28/2018 3:08:18 PM
No.
REMOVABLE PANEL TO CONCEAL TRAP
2 X 4 F.R. BASE BLOCKING
EX8715
ALTERATIONS
E
SCALE: 1/4" = 1'-0"
Signature & License No.
SOLID SURFACING W/INTEGRATED BACK-SPLASH
V.I.F.
A-160
A-160
SCALE: 1/4" = 1'-0"
ENLARGED NORTH ELEVATION ART ROOM 14
1'-2 1/2"
4
8
7
1/2" PIN HOLES FOR SHELF SUPPORTS
3X UPPER CABINETS
ENLARGED WEST ELEVATION ART ROOM 14
2'-6"
4X 2' CABINETS & 1X SINK CABINET
11'-0"
6'-0"
7X 36" WIDE CABINETS
ART 13
3'-9"
2'-6"
4'-0"
6
Scale
USA Project No.
As indicated Drawing Date
2017-002 Drawing No.
01.08.2018 Drawn By
Checked By
Author
Checker
A-160
8'-6 3/8"
8'-6 3/8"
1'-3 3/8"
8'-6 3/8"
8'-6 3/8"
1'-10 3/8"
TOILET FLOOR PLAN - GT1.1 & BT2.1
2
SCALE: 1/4" = 1'-0"
1'-6" 2'-6"
NDU TD
3'-0" 3'-0"
1" 1"
EQ
EQ
NDU TD
3'-0"
1" 1"
EQ EQ EQ
EQ
NDU TD
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
NDU TD
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
8'-6 3/8" 8'-6 3/8"
1
EQ EQ
2'-6" 1"
TD
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
5'-0"
C2
TD
usaarchitects.com
HD . 0" 5'- G R ø IN RN U T
EQ
C2
GIRL'S TOILET 2.1 GT2.1
WS
HD
1'-6"
A1
. 0" 5'- G R ø IN RN U T
3'-0"
2'-2 1/4"
A1
HD
1"
2'-6"
WS
HD 0 " R. ' 5 G HD ø IN N R TU
SD
EQ EQ
3'-0"
1" 3'-0" 1'-6 3/8"
SD
PATCH WALL AT REMOVED SINK
SD
EQ EQ
3'-0"
1" 1"
EQ EQ EQ
SD
TD
EQ
EQ EQ EQ EQ EQ EQ
SD
EQ EQ
2'-6"
2'-1 1/8"1" 2'-5 1/2" 1" 2'-5 1/2" 1" 2'-5 1/2" 1" 2'-5 1/2"
3'-0"
8'-0"
1"
BOY'S TOILET 2.1 BT2.1
NDU
HD
A1 SD
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
GIRL'S TOILET 2.2 GT2.2
5'-0"
NDU TD
ø5 '-0" TU RN ING R.
TD
5'-0"
TD
PATCH WALL AT REMOVED SINK
3'-0"
1"
EQ EQ EQ
NDU TD
SD
1"
EQ
3'-0"
EQ
SD
EQ
TD
EQ EQ
3'-0" 1" 1"
HD
NDU
A1
EQ EQ
TD
EQ
NDU
C2
1'-6"
TD
C2 BOY'S TOILET 2.2 BT2.2 2'-5 1/2" 1" 2'-5 1/2" 1" 2'-5 1/2" 1" 2'-5 1/2" 1"2'-3 1/8"
TD
1"
NDU
HD
1'-6"
1'-6"
TD 1"
3'-5 5/8"
EQ EQ
NDU TD
EQ
1" 3'-0"
1"
1"
TD
. 0" 5'- G R ø N I HD RN TU
5'-0"
NDU
5'-0"
TD
3'-0"
EQ
TD
EQ
NDU
1'-6"
TD
NDU TD
EQ
HD
1"
2'-6"
HD
. 0" G R ' 5 N ø RNI U T
HD
WS
EQ
SD
5'-0"
1'-6"
EQ
1" 3'-0"
EQ
1"
SD
PATCH WALL AT REMOVED SINK
EQ
SD
EQ EQ
2'-6"
SD
. 0" 5'- G R ø N I RN TU
EQ EQ
HD 0" 5'R. ø G N I RN TU
EQ EQ
2'-5 1/2"
SD
SD
EQ EQ
WS
CUT OPENING FOR NEW SINK CARRIER IN EXISTING WALL AS REQ'D. TYP. ALL RESTROOMS.
2'-5 1/2"
A1
HD
2'-5 1/2"
BOY'S TOILET 1.1 BT1.1
1'-6"
1'-6"
A1
HD
HD
C2
2'-5 1/2"
C2
2'-6"
GIRL'S TOILET GT1.1
EQ EQ
2'-3 1/2"
SD
A1
GIRL'S TOILET 1.2 GT1.2
1'-6"
A1
2'-6"
C2
C2
BOY'S TOILET 1.2 BT1.2
5'-0"
1'-8 1/8"
5'-0"
8'-6 3/8"
TOILET FLOOR PLAN - GT 1.2 & BT 1.2
3
SCALE: 1/4" = 1'-0"
TOILET FLOOR PLAN - GT 2.1 & BT 2.1
4
SCALE: 1/4" = 1'-0"
1'-4 1/8"
8'-6 3/8"
TOILET FLOOR PLAN - GT 2.2 & BT 2.2 SCALE: 1/4" = 1'-0"
TOILET ROOM NOTES: 1. PROVIDE FLOOR LEVELING/INFILL AT FLOOR SPACE BETWEEN DEMOLISHED BLOCK CHASE WALL AND NEW GWB CHASE WALLS AS REQUIRED. ALSO PROVIDE NEW CERAMIC FLOOR TILE TO MATCH EXISTING. 2. ALL TOILET ROOMS TO RECEIVE RESINOUS FLOOR AND INTEGRAL BASE COATING. 3. AT GLAZED BLOCK WALLS TO REMAIN, PROVIDE PATCHING WHERE WALL MOUNTED SINKS AND WING WALLS HAVE BEEN REMOVED. GROUT ALL HOLES FROM DEMOLISHED TOILET PARTITIONS AND ACCESSORIES IN EXISTING WALLS. PATCH CERAMIC FLOOR TILE AT REMOVED TOILETS, WING WALLS PARTITIONS, ETC. 4. NEW CERAMIC WALL TILE TO BE 6"x8" TO MATCH EXISTING GLAZED BLOCK DIMENSIONS. ALIGN TILE MORTAR JOINTS WITH EXISTING BLOCK WALL JOINTS. PROVIDE CERAMIC WALL TILE AT NEW CHASE PARTITION & EXISTING PATCHED WALLS ONLY. 5. ALL NEW CERAMIC WALL TILE AND EXISTING GLAZED BLOCK WALLS TO BE EPOXY PAINTED, U.N.O. 6. TOILET ACCESSORIES TO BE PROVIDED AS FOLLOWS: A. EACH MEN AND BOYS ROOM TOILET STALL TO RECEIVE ONE TOILET PAPER DISPENSER. B. EACH WOMEN AND GIRLS ROOM TOILET STALL TO RECEIVE ONE TOILET PAPER DISPENSER & ONE NAPKIN DISPOSAL.
M
5
MIRROR
SD
SOAP DISPENSER
WS
WALL SHELF
HD HAND DRYER
TD
2'-6"
15" MIN.
7. URINAL SCREEN PANELS SHALL BE LOCATED BETWEEN EACH URINAL AND AT THE END OF A ROW OF FIXTURES. 2'-0"
2'-6"
4'-0"MAX.
D. ONE WALL MOUNTED SHELF TO BE INSTALLED IN EACH WOMEN AND GIRLS TOILET ROOMS.
OPERABLE HANDLE
3'-4"MAX.
4' - 0" MAX. TO
C. EACH LAVATORY TO RECIEVE ONE MIRROR AND 1 SOAP DISPENSER.
8. ALL UPPER FLOOR TOILET ROOMS TO RECEIVE NEW FLOOR DRAINS. SEE PLUMBING DRAWINGS. 9. ACCESSIBLE STALLS IN EACH BOY'S & GIRL'S RESTROOM TO RECEIVE GRAB BARS.
TOILET PAPER DISPENSER
NDU
10. CLEAN & PAINT EXISTING COLUMN IN GIRL'S TOILET GT1.1.
SANITARY NAPKIN DISPOSAL
TYPICAL TOILET ACCESSORY MOUNTING HEIGHTS SCALE: 3/8" = 1'-0" Signature & License No.
EX8715
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
ALTERATIONS
BARRIER FREE LEGEND 39" - 41" 54"
LOG COLLEGE MIDDLE SCHOOL
SIDE VIEW H.C. WATER CLOSET
MOUNTING HEIGHT TOILET PAPER DISPENSER
SIDE VIEW SINK MOUNTING HEIGHT
11"
17" - 25"
MIN SIDE VIEW LEG CLEARANCE
SIDE VIEW URINAL MOUNTING HEIGHT
SIDE VIEW TOE CLEARANCE
FRONT VIEW DOOR ACCESSORY MOUNTING HEIGHT
MIN
72"
15" - 48"
MAX
60"
MIN
48"
34" - 48"
MAX
17"
MIN
9"
MIN
27"
MAX
34"
7" - 9"
FRONT VIEW H.C. WATER CLOSET
CENTENNIAL SCHOOL DISTRICT
MIN
33" - 36"
17" - 19"
8"
1 1/2" MIN
MIN
MIN
MAX
FOR THE
15"
12" MIN
42"
MIN
24" MIN
12"
18"
MIN
16" - 18"
INTERNATIONAL SYMBOL OF ACCESS
AT
RANGE OF TACTILE CHARACTER MOUNTING HEIGHT
39" - 41"
33" - 36"
MOUNTING HEIGHTS (BOTH BARRIER FREE AND STANDARD AS PER MANUFACTURERS RECOMENDATIONS AND AS REQUIRED BY A.N.S.I. AND BULDING CODES. REFER TO SPECIFICATIONS FOR SPECIFIC PRODUCT 36" INFORMATION MIN
433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
FRONT VIEW ELEVATOR ACCESSORY MOUNTING HEIGHT
20" - 25"
10"
MAX
10" - 24"
6" MIN.
20"
UNOBSTRUCTED FORWARD REACH
2/28/2018 3:08:26 PM
OBSTRUCTED FORWARD REACH
OBSTRUCTED FORWARD REACH
UNOBSTRUCTED SIDE REACH
OBSTRUCTED SIDE REACH
NOTE: ALL OPERABLE FIXTURES ARE REQUIRED TO BE MOUNTED WITHIN THE REACH RANGES INDICATED ABOVE
OBSTRUCTED SIDE REACH
No.
> 27"
MAX
34"
MAX
46"
MAX
34"
MAX
03-14-2018
MIN
15"
48"
MAX
48"
44"
MAX
MAX
48" 15"
MIN
48"
MAX
< 80"
MAX
6" MIN.
4" MAX
PROTRUDING OBJECTS IN CIRCULATION PATHS
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
TYPICAL MEN'S HANDICAP RESTROOM SIGN
TYPICAL WOMEN'S HANDICAP RESTROOM SIGN
NOTE: SEE DOOR ACCESSORY ELEVATION FOR MOUNTING HEIGHT & PROVIDE RELEVANT SIGN FOR EACH RESTROOM.
ENLARGED TOILET PLANS & DETAILS LOG COLLEGE MS Scale
USA Project No.
As indicated
6
BARRIER FREE LEGEND SCALE: 3/8" = 1'-0"
Drawing Date
2017-002 Drawing No.
01.08.2018 Drawn By
Checked By
JS/SB
JMc
A-161
CEILING LEGEND PATCH & REPAIR PLASTER AS REQ'D.
PATCH & REPAIR PLASTER AS REQ'D.
DEMOLITION
PATCH & PAINT EXISTING EXTERIOR PLASTER SOFFITS AS REQUIRED.
PATCH & PAINT EXISTING EXTERIOR PLASTER SOFFITS AS REQUIRED.
AREA OF CEILING DEMOLITION (ACT AND GYP/PLASTER AS SHOWN)
NOT IN SCOPE
GYP-1 GYPSUM/PLASTER
CLASSROOM 15
CLASSROOM 19
FACULTY WORKROOM 19-0
CLASSROOM 20
FACULTY WORKROOM 21-0
CLASSROOM 21
CLASSROOM 22
FACULTY WORKROOM 23-0
CLASSROOM 23
CLASSROOM 24
STAIR 3 ST3.1
CLASSROOM 25
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
ACT (NEW) 2' x 4' ACT
usaarchitects.com
STAIR 2 ST2.1
2' x 4' LIGHT FIXTURE
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
GENERAL NOTES ELECTRIC ROOM 137
FACULTY WORKROOM 25-0
CORRIDOR 111B
BOILER ROOM 134
HOME MAKING 17
MECH/ STORAGE 138
STORAGE & MECHANICAL ROOM
ELEV. MECH. RM. EL1 GIRL'S 119 TOILET 1.2 GT1.2
112
MEN'S TOILET 114
PATCH & PAINT EXISTING EXTERIOR PLASTER SOFFITS AS REQUIRED.
RECEIVING & MAINTENANCE 130
FREEZER 136
HOME MAKING 16-1
MT 127
REFUSE 107
GUIDANCE 123
135
CORRIDOR 16-3
LIVING ROOM 16-2
OFFICE 131
MAIN OFFICE 121
PRINCIPAL OFFICE 122
5. PATCH AND PAINT PLASTER/ GWB BULKHEADS AT EXISTING SKYLIGHT LOCATIONS.
STORAGE 117
CLASSROOM 26
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
KITCHEN HELP 108
PATCH & PAINT EXISTING EXTERIOR PLASTER SOFFITS AS REQUIRED.
PATCH & REPAIR PLASTER AS REQ'D. FOR MEP WORK ACCESS TO ITEMS ABOVE
JANITOR CLOSET 109
SERVING 2 106
FCS 16
TOILET 132
WOMEN'S TOILET 115
FOOD STORAGE 110
LOCKER 133
GROUNDS EQUIPMENT ROOM
HALL 113
LOUNGE 116
HALL 125 WT 126
2. PROVIDE WASHABLE CEILING TILE & GRID IN KITCHEN.
4. SEE MEP AND STRUCTURAL DRAWINGS FOR MORE ADDITIONAL DEMOLITION INFORMATION.
IT/ STORAGE 120
OFFICE 124
1. PROVIDE FIRE-RATED CEILING TILE & GRID IN CORRIDORS.
3. NEW CEILINGS TO BE AT SAME HEIGHT AFF AS DEMOLISHED CEILINGS. VERIFY CEILING HEIGHTS PRIOR TO DEMOLITION. CORRIDORS - 8'-0" TYPICAL CLASSROOMS - 9'-6" TYPICAL
STORAGE 118
BOY'S TOILET 1.2 BT1.2
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
SERVING 2 106 CORRIDOR 111 CAFETERIA 103
STORAGE 16-4
OFFICE 105C
CORRIDOR 111A
REFRIGERATOR 105B DARK ROOM 143
KITCHEN 105
FREEZER 105A STORE 140 CLASSROOM 11
CORRIDOR 111D ART 14
CORRIDOR 111C
CLOSET 142
GIRL'S TOILET 1.1 GT1.1
BOY'S TOILET 1.1 BT1.1
STORAGE 141
MATERIAL STORAGE 9-2
SERVING 1 104
2'-6"
CLOSET 9-1
STORAGE 12-2
STORAGE 13-1 ART 13
WOOD SHOP 12
MATERIAL STORAGE 12-3
PATCH & REPAIR PLASTER AS REQ'D. FOR MEP WORK ACCESS TO ITEMS ABOVE
COMPUTER LAB 10
COMPUTER LAB 9
STAIR 1 ST1.1 CLASSROOM 8
ENTRANCE 101
ENTRANCE VESTIBULE 100 Signature & License No.
PATCH & PAINT EXISTING EXTERIOR PLASTER SOFFITS AS REQUIRED.
EX8715
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
FINISH ROOM 12-4
ALTERATIONS AT
PROVIDE NEW GWB BULKHEAD AT WINDOWS IN ROOMS NOT RECEIVING NEW ACT, SALVAGE AND REUSE EXISTING CEILING TILES. TYPICAL AT AREAS SHOWN.
1
LOG COLLEGE MIDDLE SCHOOL FOR THE
GROUND FLOOR PLAN - AREA A
CENTENNIAL SCHOOL DISTRICT
SCALE: 3/32" = 1'-0"
433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
03-14-2018 No.
2/28/2018 3:08:30 PM
B
A
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
GROUND FLOOR REFLECTED CEILING PLAN AREA A - LOG COLLEGE MS Scale
USA Project No.
As indicated Drawing Date
2017-002 Drawing No.
KEY PLAN A - LOG COLLEGE MS
01.08.2018
SCALE: N.T.S.
Drawn By
Checked By
JS
JMc
A-204
CEILING LEGEND DEMOLITION
NOT IN SCOPE
AREA OF CEILING DEMOLITION (ACT AND GYP/PLASTER AS SHOWN) GYP-1 GYPSUM/PLASTER
11 A-140
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
TYP. ACT (NEW) 2' x 4' ACT
usaarchitects.com 2' x 4' LIGHT FIXTURE
STAIR 2 ST2.2
CLASSROOM 35
CLASSROOM 36
FACULTY WORKROOM 37-0
CLASSROOM 37
FACULTY WORKROOM 38-0
CLASSROOM 38
CLASSROOM 39
FACULTY WORKROOM 40-0
CLASSROOM 40
CLASSROOM 41
CLASSROOM 42
SCIENCE LAB 43
STAIR 3 ST3.2
GENERAL NOTES
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
1. PROVIDE FIRE-RATED CEILING TILE & GRID IN CORRIDORS.
2'-6"
CLASSROOM 34
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
2. PROVIDE WASHABLE CEILING TILE & GRID IN KITCHEN. 3. NEW CEILINGS TO BE AT SAME HEIGHT AFF AS DEMOLISHED CEILINGS. VERIFY CEILING HEIGHTS PRIOR TO DEMOLITION. CORRIDORS - 8'-0" TYPICAL CLASSROOMS - 9'-6" TYPICAL
FACULTY WORKROOM 33-0
4. SEE MEP AND STRUCTURAL DRAWINGS FOR MORE ADDITIONAL DEMOLITION INFORMATION. 5. PATCH AND PAINT PLASTER/ GWB BULKHEADS AT EXISTING SKYLIGHT LOCATIONS.
CORRIDOR 211B STORAGE 3 230
STORAGE 212
EXISTING SKYLIGHT
MECH. 231
CLASSROOM 33
CLASSROOM 54
CLASSROOM 55
MECHANICAL EQUIPMENT 203
ELEV. EL2 MECHANICAL 240
BOY'S TOILET 2.2 BT2.2
GIRL'S TOILET 2.2 GT2.2
STORAGE 210
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
CONFERENCE ROOM 227
CONFERENCE 204
GUIDANCE 225
LIBRARY 202
FACULTY WORKROOM 31-0
CORRIDOR 211C
GUIDANCE 224
WOMEN'S TOILET 1 228 MEN'S TOILET 1 229
COURT UC OPEN TO ABOVE. (SEE ROOF PLAN FOR SCOPE OF WORK)
LIBRARY WORKROOM 58 EXISTING SKYLIGHT
EXISTING SKYLIGHT
CLASSROOM 53 CLASSROOM 32
SCIENCE LAB 44
GUIDANCE 226
CORRIDOR 211 LIBRARY WORKROOM 58A
CLASSROOM 52 HALL 222
OFFICE 223
STORAGE 31-1
SCIENCE LAB 45 CLASSROOM 61
MAIN OFFICE 220 CLASSROOM 51
CLASSROOM 50
MECHANICAL 241
BOY'S TOILET 2.1 BT2.1
GIRL'S TOILET 2.1 GT2.1
CUT & PATCH EXISTING PLASTER BULKHEAD AS REQ'D. TO ACCOMODATE NEW MECHANICAL PIPING.
PRINCIPAL OFFICE 221
CLASSROOM 31
CORRIDOR 211D
CLASSROOM 60 STORAGE 213
STORAGE 214
EXISTING SKYLIGHT
CORRIDOR 211A
Signature & License No.
SCIENCE LAB 46
CLASSROOM 30
CLASSROOM 29 FACULTY WORKROOM 29-0
CLASSROOM 28
FACULTY WORKROOM 27-0
CLASSROOM 27
MEN'S TOILET 242
WOMEN'S TOILET 243
JANITOR CLOSET 245
STAIR 1 ST1.2
CLASSROOM 48
CLASSROOM 47
EX8715
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
MECH. 46-0
ALTERATIONS
FACULTY WORKROOM 47-0
AT
LOG COLLEGE MIDDLE SCHOOL
LOUNGE 244
FOR THE
CENTENNIAL SCHOOL DISTRICT
1
PROVIDE NEW GWB BULKHEAD AT WINDOWS IN ROOMS NOT RECEIVING NEW ACT, SALVAGE AND REUSE EXISTING CEILING TILES. TYPICAL AT AREAS SHOWN.
UPPER FLOOR PLAN SCALE: 3/32" = 1'-0"
433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
11 A-140 TYP.
03-14-2018 No.
2/28/2018 3:08:33 PM
B
A
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
UPPER FLOOR REFLECTED CEILING PLAN AREA A - LOG COLLEGE MS Scale
USA Project No.
As indicated
KEY PLAN A - LOG COLLEGE MS SCALE: N.T.S.
Drawing Date
2017-002 Drawing No.
01.08.2018 Drawn By
Checked By
JS
JMc
A-205
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174 CONNECTING CORRIDOR 102
usaarchitects.com Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
2
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
CORRIDOR REFLECTED CEILING PLAN SCALE: 3/32" = 1'-0"
PATCH & PAINT EXISTING EXTERIOR PLASTER SOFFITS AS REQUIRED.
PATCH & PAINT EXISTING EXTERIOR PLASTER SOFFITS AS REQUIRED.
NURSE 155
CORRIDOR 153
HEALTH 158
JANITOR CLOSET 159
PROVIDE GWB SOFFITS AT ACT TRANSITIONS. SEE TYPICAL DETAIL.
MEN 156
CORRIDOR 105A PATCH & PAINT EXISTING EXTERIOR PLASTER SOFFITS AS REQUIRED.
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
HEALTH 157
BOY'S LOCKER ROOM 160
AUDITORIUM 151 STORAGE 161
BOY'S TOILET L35 CORRIDOR 172
CORRIDOR 150
STORAGE 41C
STORAGE 174 STORAGE 173
BOY'S GYM CBG
CEILING LEGEND 3
DEMOLITION
CORRIDOR 154
AREA OF CEILING DEMOLITION (ACT AND GYP/PLASTER AS SHOWN)
A-140
GIRL'S GYM GG
GYP-1 GYPSUM/PLASTER
WOMEN 171
PROVIDE GWB SOFFITS AT ACT TRANSITIONS. SEE TYPICAL DETAIL.
NOT IN SCOPE
Signature & License No.
ACT (NEW)
EX8715
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
2' x 4' ACT
STORAGE 45 C
ALTERATIONS 2' x 4' LIGHT FIXTURE AT
CORRIDOR 105B
PATCH & PAINT EXISTING EXTERIOR PLASTER SOFFITS AS REQUIRED.
VOCAL 170
PRACTICE ROOM 168
FOR THE
1. PROVIDE FIRE-RATED CEILING TILE & GRID IN CORRIDORS. 2. PROVIDE WASHABLE CEILING TILE & GRID IN KITCHEN. 3. NEW CEILINGS TO BE AT SAME HEIGHT AFF AS DEMOLISHED CEILINGS. VERIFY CEILING HEIGHTS PRIOR TO DEMOLITION. CORRIDORS - 8'-0" TYPICAL CLASSROOMS - 9'-6" TYPICAL
MUSIC CLASSROOM 169
JANITOR CLOSET 167
LOG COLLEGE MIDDLE SCHOOL
GENERAL NOTES
VOCAL 170-1
CENTENNIAL SCHOOL DISTRICT 433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
4. SEE MEP AND STRUCTURAL DRAWINGS FOR MORE ADDITIONAL DEMOLITION INFORMATION. 5. PATCH AND PAINT PLASTER/ GWB BULKHEADS AT EXISTING SKYLIGHT LOCATIONS.
GIRL'S LOCKER ROOM 163
GIRL'S TOILET L29
PATCH & PAINT EXISTING EXTERIOR PLASTER SOFFITS AS REQUIRED.
PATCH & PAINT EXISTING EXTERIOR PLASTER SOFFITS AS REQUIRED.
B 03-14-2018 No.
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
A
STORAGE 162
2/28/2018 3:08:36 PM
1
BUILDING B REFLECTED CEILING PLAN SCALE: 3/32" = 1'-0"
REFLECTED CEILING PLAN AREA B - LOG COLLEGE MS Scale
USA Project No.
As indicated Drawing Date
KEY PLAN B - LOG COLLEGE MS SCALE: N.T.S.
2017-002 Drawing No.
01.08.2018 Drawn By
Checked By
JS
JMc
A-206
GENERAL ELEVATION NOTES:
REPAIR KEY/ LEGEND: 100% CUT OUT & REPOINT DETERIORATED, OPEN & ERODED BRICK MASONRYJOINTS. INSTALL HELICAL BRICK TIES 16" O.C.
1. RELIEVING ANGLES AT LOUVERS, WINDOWS AND DOORS TO BE CLEANED & COATED. REMOVE AND TOOTHE IN BRICK AS NECESSARY. ALLOW FOR (12) LOCATIONS TOTAL (CONFIRM LOCATIONS IN FIELD WITH GC.)
R
REMOVE AND REINSTALL BRICK. PROVIDE NEW INSULATION, FLASHING, BRICKTIES AND WEEPS.
2. AT PENTHOUSE LEVEL: LIGHT POWERWASH ALL WHITE BRICK. ALL EXISTING CONTROL JOINTS TO BE CUT OUT AND REPLACED.
C
CLEAN ENTIRE ELEVATION OF PRECAST TRIM OF ATMOSPHEREIC SOILING & BIOGROWTH USING A MILD DETERGENT.
5
C
A
A
A
A
KEY NOTES:
A REMOVE ONE COURSE OF BRICK, RIP, CUT AND REINSTALL WITH COMPRESSIBLE FILLER, BACKER ROD, AND CAULK. TO BUILDING B
C
7
1
2
8
SCALE: 3/32" = 1'-0"
REMOVE AND REPLACE 3 LF OF BRICK AT THE NORTH ELEVATION AND 2 LF OF BRICK AT THE EAST ELEVATION.
ALTERNATE: 100% BRICK REPOINTING. 1
REMOVE EXISTING PLYWOOD SIGN MOUNTED TO FACE OF BUILDING.
2
NEW 4'-0" HIGH SS HEAVY DUTY CORNER GUARDS @ BRICK CORNERS.
3
REMOVE 4 COURSES OF BRICK AT BASE OF PENTHOUSE. REINSTALL METAL FLASHING TWO COURSES OF BRICK HIGHER. INFILL SALVAGED BRICK AS NECESSARY. ALLOW FOR 500SF OF WHITE BRICK REPLACEMENT AND 5% REPOINTING AT THIS AREA.
2
1
usaarchitects.com
CUT BRICK TO ACHEIVE A 1/2" - 5/8" CONTROL JOINT. REINSTALL WITH COMPRESSIBLE FILLER, BACKER ROD AND CAULK. ALLOW FOR 60 LOCATIONS TOTAL.
NORTH ELEVATION A
4
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
LOCATION OF EXPLORATORY OPENING IN BRICK VENEER.
4
LOCATION OF NEW ACCENT LIGHTING MOUNTED TO THE BUILDING - SEE ELECTRICAL PLANS.
5
PATCH AND PAINT PLASTER FASCIA AND SOFFIT AS REQUIRED.
6
NOT USED.
7
PAINT LOUVERS. PROVIDE NEW DAMPERS AS REQUIRED. SEE MECH. DRAWINGS FOR MORE INFORMATION.
8
SEE STRUCTURAL DRAWINGS FOR NEW WORK AT LOADING DOCK.
9
NEW ALUMINUM COPING AT PERIMETER OF LOWER ROOF.
10
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
NOT USED
4 11
LOCATIONS OF EXTERIOR INFILL WALLS. SEE PLANS AND DETAILS.
12
INFILL EXISTING A/C OPENINGS IN EXTERIOR WALL.
13
PROVIDE MISCELLANEOUS AND MINOR REPOINTING AS WELL POWERWASHING/ CLEANING ON ALL SECOND FLOOR AREA NOT NOTED FOR BRICK REMOVAL/ REINSTALLATION.
C
A
A
A
TO BUILDING B
A
C
5
2
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
5
SOUTH ELEVATION A SCALE: 3/32" = 1'-0"
3 C
A
A
A
A
A
A
A
A
C E
E
5
3
3
5
EAST ELEVATION A SCALE: 3/32" = 1'-0"
R
12
Signature & License No.
EX8715
C This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
A
A
A
A
A
A
ALTERATIONS AT
C E
E
E
E
E
LOG COLLEGE MIDDLE SCHOOL
F
CONNECTING CORRIDOR
G
FOR THE
CENTENNIAL SCHOOL DISTRICT 433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
4
WEST ELEVATION A SCALE: 3/32" = 1'-0"
7
B
C
B
C
03-14-2018 No.
2/28/2018 3:10:39 PM
5
SOUTH COURT ELEVATION SCALE: 3/32" = 1'-0"
6
EAST COURT ELEVATION SCALE: 3/32" = 1'-0"
7
WEST COURT ELEVATION SCALE: 3/32" = 1'-0"
8
NORTH COURT ELEVATION SCALE: 3/32" = 1'-0"
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
BUILDING A ELEVATIONS - LOG COLLEGE MS Scale
USA Project No.
As indicated Drawing Date
2017-002 Drawing No.
01.08.2018 Drawn By
Checked By
JS
JMc
A-300
REPAIR KEY/ LEGEND: 100% CUT OUT & REPOINT DETERIORATED, OPEN & ERODED BRICK MASONRYJOINTS. INSTALL HELICAL BRICK TIES 16" O.C.
1. RELIEVING ANGLES AT LOUVERS, WINDOWS AND DOORS TO BE CLEANED & COATED. REMOVE AND TOOTHE IN BRICK AS NECESSARY. ALLOW FOR (12) LOCATIONS TOTAL (CONFIRM LOCATIONS IN FIELD WITH GC.)
R
REMOVE AND REINSTALL BRICK. PROVIDE NEW INSULATION, FLASHING, BRICKTIES AND WEEPS.
2. AT PENTHOUSE LEVEL: LIGHT POWERWASH ALL WHITE BRICK. ALL EXISTING CONTROL JOINTS TO BE CUT OUT AND REPLACED.
C
CLEAN ENTIRE ELEVATION OF PRECAST TRIM OF ATMOSPHEREIC SOILING & BIOGROWTH USING A MILD DETERGENT. REMOVE ONE COURSE OF BRICK, RIP, CUT AND REINSTALL WITH COMPRESSIBLE FILLER, BACKER ROD, AND CAULK.
CUT BRICK TO ACHEIVE A 1/2" - 5/8" CONTROL JOINT. REINSTALL WITH COMPRESSIBLE FILLER, BACKER ROD AND CAULK. ALLOW FOR 60 LOCATIONS TOTAL.
REMOVE 4 COURSES OF BRICK AT BASE OF PENTHOUSE. REINSTALL METAL FLASHING TWO COURSES OF BRICK HIGHER. INFILL SALVAGED BRICK AS NECESSARY. ALLOW FOR 500SF OF WHITE BRICK REPLACEMENT AND 5% REPOINTING AT THIS AREA. REMOVE AND REPLACE 3 LF OF BRICK AT THE NORTH ELEVATION AND 2 LF OF BRICK AT THE EAST ELEVATION.
ALTERNATE: 100% BRICK REPOINTING.
13
D
D
D
D
C
D
D
D
D
D
D
9
5
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174
KEY NOTES: 1
REMOVE EXISTING PLYWOOD SIGN MOUNTED TO FACE OF BUILDING.
2
NEW 4'-0" HIGH SS HEAVY DUTY CORNER GUARDS @ BRICK CORNERS.
3
LOCATION OF EXPLORATORY OPENING IN BRICK VENEER.
4
LOCATION OF NEW ACCENT LIGHTING MOUNTED TO THE BUILDING - SEE ELECTRICAL PLANS.
5
PATCH AND PAINT PLASTER FASCIA AND SOFFIT AS REQUIRED.
6
NOT USED.
7
PAINT LOUVERS. PROVIDE NEW DAMPERS AS REQUIRED. SEE MECH. DRAWINGS FOR MORE INFORMATION.
8
SEE STRUCTURAL DRAWINGS FOR NEW WORK AT LOADING DOCK.
9
NEW ALUMINUM COPING AT PERIMETER OF LOWER ROOF.
10
usaarchitects.com Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
NOT USED
11
LOCATIONS OF EXTERIOR INFILL WALLS. SEE PLANS AND DETAILS.
12
INFILL EXISTING A/C OPENINGS IN EXTERIOR WALL.
13
PROVIDE MISCELLANEOUS AND MINOR REPOINTING AS WELL POWERWASHING/ CLEANING ON ALL SECOND FLOOR AREA NOT NOTED FOR BRICK REMOVAL/ REINSTALLATION.
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
5
TO BUILDING B
TO BUILDING A
C
GENERAL ELEVATION NOTES:
3 7
1
NORTH ELEVATION CORRIDOR
2
SCALE: 3/32" = 1'-0"
3
NORTH ELEVATON B SCALE: 3/32" = 1'-0"
7
13
9
5
C
TO BUILDING B
11
D
11
D
D
D
D
D
11
D
D
D
D
TO BUILDING A
5
C
3
3
SOUTH ELEVATION B
4
SCALE: 3/32" = 1'-0"
SOUTH ELEVATION CORRIDOR SCALE: 3/32" = 1'-0"
Signature & License No.
7
EX8715
13 13
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
7 13
ALTERATIONS 9
C
AT
9
LOG COLLEGE MIDDLE SCHOOL C FOR THE
CONNECTING CORRIDOR
CENTENNIAL SCHOOL DISTRICT 433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
5
5
3
5
EAST ELEVATION B SCALE: 3/32" = 1'-0"
13
1
13 7
13
9 03-14-2018
C
No.
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
2/28/2018 3:10:56 PM
BUILDING B ELEVATIONS - LOG COLLEGE MS 3
6
5
5
5
Scale
USA Project No.
WEST ELEVATION B
As indicated
SCALE: 3/32" = 1'-0"
Drawing Date
2017-002 Drawing No.
01.08.2018 Drawn By
Checked By
Author
Checker
A-301
BUILDING A DOOR SCHEDULE - GROUND FLOOR DOOR
DOOR WIDTH
DOOR WIDTH
DOOR WIDTH
WIDTH
DOOR NUMBER
GENERAL NOTES:
11'-5" EXG M.O. - VIF
1. FIELD VERIFY ALL EXISTING DOOR SIZES LISTED IN SCHEDULE.
8'-0"
EXG M.O. - VIF
DOOR HEIGHT
DOOR HEIGHT
DOOR HEIGHT
DOOR HEIGHT
2. NEW DOOR FINISH TO MATCH EXISTING, UNLESS NOTED OTHERWISE. 3. EXISTING FRAMES TO REMAIN (ETR), UNLESS NOTED OTHERWISE. 4. PATCH SCREW HOLES FROM DEMOLISHED WALL AND FLOOR MOUNTED HOLD OPEN DEVICES AND WALL STOPS, TYPICAL.
DOOR SCHEDULE NOTES: 1. GC TO VERIFY EXISTING OPENING/ FRAME SIZE.
36" TYPE F
TYPE FF
TYPE FF2
TYPE FF3
2. PROVIDE NEW INSULATED OVERHEAD DOOR. COORDINATE POWER REQUIREMENTS AND CONTROL LOCATION.
ACC
3. PROVIDE NEW ACCORDIAN DOOR. PROVIDE LOCK WITH SAME FUNCTION AS EXISTING. REUSE EXISTING FRAME IF POSSIBLE. 4. NEW CLEAR ANODIZED ALUMINUM STOREFRONT WINDOW SYSTEM WITH 1" INSULATED GLAZING UNITS AT WINDOWS.
EXG M.O. - VIF
EXG M.O. - VIF DOOR
2"
WIDTH
DOOR HEIGHT
10'-2"
EXG M.O. - VIF
10'-2"
EXG M.O. - VIF
2"
2"
HM FRAME
2"
5. EXISTING DOORS ARE 2 1/4", FRAMES HAVE ADJUSTABLE STOPS. PROVIDE STANDARD 1 3/4" DOORS, ADJUST STOPS IN FIELD TO ACCOMODATE NEW DOOR THICKNESS.
2"
DOOR WIDTH
2"
17'-6"
6. DOORS TO HAVE MAGNETIC HOLD OPEN DEVICES SET TO RELEASE UPON ACTIVATION OF FIRE-ALARM SYSTEM.
DOOR HEIGHT
10'-0"
7. ACCORDIAN DOOR BASIS OF DESIGN PRODUCT: MANUFACTURER/MODEL: CORFLEX ACCORDIAN DOORS SERIES 3000; OR EQUAL.
HM FRAME
8. HARDWARE BY ALUMINUM DOOR MANUFACTURER. FUNCTION TO MATCH OTHER EXISTING EXTERIOR DOORS PER SCHOOL STANDARDS. 9. FOR OH DOORS PROVIDE CYLINDER & KEY TO MATCH SCHOOL STANDARDS.
OH1
TYPE A
OH2
DOOR TYPES/ ELEVATIONS
1
2
SCALE: 1/4" = 1'-0"
EX = EXISTING ETR = EXISTING TO REMAIN HM = HOLLOW METAL SWC = SOLID WOOD CORE
DOOR FRAME ELEVATIONS SCALE: 1/4" = 1'-0"
EXG GLASS WIDTH VARIES - 3'-0"+/-
EXG GLASS WIDTH VARIES - 3'-6"+/-
EXG GLASS WIDTH - 9'-4"+/- (3 EQ. PANELS)
VIF
VIF
VIF
EXISTING FRAME
ABBREVIATIONS:
TYPE B
EXISTING FRAME
EXG GLASS WIDTH - 12'-6"+/- (4 EQ. PANELS) VIF
EXISTING FRAME
EXISTING FRAME
102A 102B 104 106 112 114 115 116A 118 119 120 121 122 125 130A 130B 134A 135A 135B 138 140 141 142 BT1.1 BT1.2 G08 G09 G10 G11A G12 G13 G14 G15 G16 G16-2 G17 G19 G19-0 G20 G21 G21-0 G22 G23 G23-0 G24 G25 G25-0 G26 GT1.1 GT1.2
ROOM NAME CONNECTOR CORRIDOR CONNECTOR CORRIDOR SERVING 1 SERVING 2 STORAGE & MECHANICAL MEN'S TOILET WOMEN'S TOILET LOUNGE STORAGE MECHANICAL ROOM IT/STORAGE MAIN OFFICE PRINCIPAL OFFICE HALLWAY RECEIVING & MAINTENANCE RECEIVING & MAINTENANCE BOILER ROOM GROUND EQUIPMENT GROUND EQUIPMENT MECHANICAL ROOM STORE STORAGE CLOSET BOY'S TOILET 1.1 BOY'S TOILET 1.2 CLASSROOM COMPUTER LAB COMPUTER LAB CLASSROOM WOOD SHOP ART ART CLASSROOM FAMILY CONSUMER SCIENCE LIVINGROOM HOME MAKING CLASSROOM FACULTY WORKROOM CLASSROOM CLASSROOM FACULTY WORKROOM CLASSROOM CLASSROOM FACULTY WORKROOM CLASSROOM CLASSROOM FACULTY WORKROOM CLASSROOM GIRL'S TOILET 1.1 GIRL'S TOILET 1.22
DOOR ELEVATION DOOR WIDTH
DOOR HEIGHT
FF3 FF3 FF3 FF3 FF F F F F F F F F F FF OH1 F F OH2 FF ACC F F F F F F F F FF2 F F F F F F F F F F F F F F F F F F F F
7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 10'-2" 7'-10" 7'-10" 10'-2" 7'-10" 8'-0" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10"
6'-0" 6'-0" 6'-0" 6'-0" 6'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 6'-0" 10'-0" 3'-0" 3'-0" 17'-6" 6'-0" 11'-5" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 5'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0"
DOOR TYPE FF3 FF3 FF3 FF3 FF F F F F F F F F F FF OH F F OH FF ACC F F F F F F F F FF2 F F F F F F F F F F F F F F F F F F F F
FRAME TYPE B B B B ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR
HARDWARE SET 10 10 10 10 15 8 8 11 12 12 12 11 11 11 15 7 7 15 15 15 8 8 14 14 14 14 1 14 14 14 14 14 14 13 11 13 13 11 13 13 11 13 13 11 13 8 8
FIRE RATING 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. NA 20 MIN. 20 MIN. NA 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN.
COMMENTS 6 6 6 6
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174 usaarchitects.com 1, 2
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
1, 2
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
SIDELIGHT ELEVATION (TYPICAL CLASSROOM AND FACULTY WORKROOM)
F3
F4
WINDOW ELEVATION (2ND FLOOR: LIBRARY, MAIN OFFICE AND GUIDANCE OFFICE)
F6
WINDOW ELEVATION (HOMEMAKING AND FCS)
F7
EXG GLASS WIDTH - 4'-0"+/-
VIF
VIF
VIF
VIF
VIF
VIF
EXG GLASS HEIGHT - 4'-4"
EXG GLASS WIDTH - 2'-10"+/-
EXG GLASS HEIGHT - 4'-4"
EXG GLASS WIDTH - 6'-4"+/- (2 EQ. PANELS)
EXG GLASS HEIGHT - 4'-9"
EXG GLASS WIDTH - 2'-10"
EXISTING WINDOW FRAME
VIF
EXG GLASS HEIGHT - 7'-6"
VIF
EXG GLASS HEIGHT - 7'-6"
VIF
WINDOW ELEVATION
DOOR NUMBER
VIF
F2
VIF
EXG GLASS HEIGHT - 4'-9"
F1
EXG GLASS HEIGHT - 7'-6"
EXISTING DOOR
VIF
EXG GLASS HEIGHT -7'-6"
BUILDING A DOOR SCHEDULE - UPPER FLOOR
GLASS FILM NOTES:
3. USE TRANSLUCENT, DIMENSIONALLY STABLE, CAST PVC FILM, 2-MIL-MINIMUM THICKNESS, WITH PRESSURESENSITIVE, CLEAR ADHESIVE BACK FOR ADHERING TO GLASS AND RELEASABLE PROTECTIVE BACKING.
WINDOW ELEVATION (ART ROOM 14)
F9
SIDELIGHT ELEVATION (ART ROOM 13)
SIDELIGHT ELEVATION (CLASSROOM 11/ COMPUTER LAB)
F10
EXG GLASS WIDTH - 2'-5 1/4"+/-
EXG GLASS WIDTH - 12'-4"+/- (4 EQ. PANELS)
VIF
VIF
VIF
EXG GLASS HEIGHT - 4'-9"+/-
EXG GLASS WIDTH - 9'-11 1/2"+/- (3 EQ. PANELS)
EXISTING WINDOW FRAME
VIF
EXG GLASS HEIGHT - 4'-9"
CORRIDOR
DOOR NUMBER
EXISTING SPANDREL GLASS
2/28/2018 3:10:58 PM
F11
3
F12
WINDOW ELEVATION (FCS/ HOMEMAKING)
GLAZING FILM (EXISTING INTERIOR SIDELIGHTS AND WINDOWS) SCALE: 1/2" = 1'-0"
FF FF F F F F F F F F F FF FF F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F
DOOR WIDTH DOOR HEIGHT 6'-0" 6'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 6'-0" 6'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0"
7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10"
DOOR TYPE FF FF F F F F F F F F F FF FF F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F
FRAME TYPE ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR
HARDWARE SET 2 2 12 11 11 11 11 11 11 12 12 15 15 8 11 4 8 8 8 8 14 11 13 13 13 11 13 13 11 13 13 11 13 13 13 13 11 13 11 13 13 11 13 13 14 14 14 14 12 13 11 13 14 14 14 14 14 14 14 14 14 14
FIRE RATING
COMMENTS
20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN.
Signature & License No.
EX8715
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
ALTERATIONS AT
LOG COLLEGE MIDDLE SCHOOL FOR THE
CENTENNIAL SCHOOL DISTRICT 433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
BUILDING B DOOR SCHEDULE
EXISTING SPANDREL GLASS
WINDOW ELEVATION (CLASSROOM 11/ CORRIDOR)
LIBRARY LIBRARY MECHANICAL ROOM CONFERENCE MAIN OFFICE PRINCIPAL OFFICE PRINCIPAL OFFICE GUIDANCE OFFICE CONFERENCE STORAGE STORAGE STORAGE STORAGE MEN'S TOILET HALLWAY JANITOR CLOSET BOY'S TOILET 2.1 BOY'S TOILET 2.2 GIRL'S TOILET 2.1 GIRL'S TOILET 2.2 CLASSROOM FACULTY WORKROOM CLASSROOM CLASSROOM CLASSROOM FACULTY WORKROOM CLASSROOM CLASSROOM FACULTY WORKROOM CLASSROOM CLASSROOM FACULTY WORKROOM CLASSROOM CLASSROOM CLASSROOM CLASSROOM FACULTY WORKROOM CLASSROOM FACULTY WORKROOM CLASSROOM CLASSROOM FACULTY WORKROOM CLASSROOM CLASSROOM SCIENCE LAB SCIENCE LAB SCIENCE LAB SCIENCE LAB MECHANICAL ROOM CLASSROOM FACULTY WORKROOM CLASSROOM CLASSROOM CLASSROOM CLASSROOM CLASSROOM CLASSROOM CLASSROOM CLASSROOM LIBRARY WORKROOM LIBRARY WORKROOM CLASSROOM
DOOR ELEVATION
VIF
VESTIBULE F8
2. APPLY FILM TO FULL EXTENT (HEIGHTH AND WIDTH) OF EXISTING GLASS PANELS ON CLASSROOM SIDE ONLY.
EXISTING SPANDREL GLASS
2'-11"
2'-11"
1. BASIS OF DESIGN: 3M CRYSTAL GLASS FINISHES, “DUSTED CRYSTAL”. PROVIDE SUBMITTAL & SAMPLE FOR REVIEW BY ARCHITECT. PROVIDE MOCKUP FOR REVIEW BY OWNER.
202A 202B 203 204A 220 221A 221C 226A 227 231 232 240 241 242 244 245 BT2.1 BT2.2 GT2.1 GT2.2 U27 U27-0 U27A U28 U29 U29-0 U30 U31 U31-0 U32 U33 U33-0 U34 U35 U36 U37 U37-0 U38 U38-0 U39 U40 U40-0 U41 U42 U43 U44 U45 U46 U46-0 U47 U47-0 U48 U50 U51 U52 U53 U54 U55 U56 U58 U58A U60
ROOM NAME
145 150A 150B 150C 151A 151B 153 154 155 156 157 158 159 160 163 164 166 167 168 169 170 171
ROOM NAME CORRIDOR STAIR CORRIDOR CORRIDOR AUDITORIUM AUDITORIUM CORRIDOR CORRIDOR NURSE MEN HEALTH HEALTH JANITOR CLOSET BOY'S LOCKER ROOM GIRL'S LOCKER ROOM STAIR STAIR JANITOR CLOSET PRACTICE ROOM (STORAGE) MUSIC CLASSROOM (STORAGE) PRACTICE ROOM (STORAGE) WOMEN
DOOR ELEVATION KK F 2/A-601 2/A-601 FF FF FF FF2 F F FF FF F FF FF F F F F F F F
DOOR WIDTH DOOR HEIGHT 5'-5" 3'-0" 6'-0 1/2" 6'-0 1/2" 6'-0" 6'-0" 6'-0" 5'-0" 3'-0" 3'-0" 6'-0" 6'-0" 3'-0" 6'-0" 6'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0"
7'-10" 7'-10" 7'-0" 7'-0" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10" 7'-10"
DOOR TYPE
F ALUM ALUM FF FF FF FF F F FF FF F FF FF F F F F F F F
FRAME TYPE B ETR ALUM ALUM ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR
HARDWARE SET 3 12 16 16 9 9 3 3 5 8 4 3 3 12 12 4 12 12 12 8
FIRE RATING
COMMENTS
20 MIN. 4, 8 4, 8 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN. 20 MIN.
03-14-2018 No.
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
DOOR SCHEDULE + DETAILS - LOG COLLEGE MS Scale
5 5 5
USA Project No.
As indicated Drawing Date
2017-002 Drawing No.
01.08.2018 Drawn By
Checked By
JS
JMc
A-600
SEE WAL TYPES FOR PARTITION WIDTH
NOTE: ONLY ROOMS/ SPACES RECEIVING NEW FINISHES ARE SHOWN ON SCHEDULES. EXISTING BRICK AT CORRIDOR SIDE.
STUD PARTITION -SEE PLAN FOR TYPE
SEALANT -BOTH SIDES
ROOM FINISH SCHEDULE - GROUND FLOOR PLAN
MASONRY PARTITION PROVIDE NEW PRE-CAST LINTELS. VERIFY EXG. CMU DIMENSION IN FIELD.
NUMBER
EXISTING CEILING HEIGHT AT BOTH SIDES OF DOOR. REMOVE AND REPLACE GRID AND TILE AS REQUIRED FOR NEW DOOR FRAME INSTALLATION.
1/2"
CORRIDOR SIDE
HOLLOW METAL FRAME
2"
2"
1/4"
1/2"
ROOM
SEALANT AND BACKER ROD -BOTH SIDES GROUT FRAME SOLID
HEAD
HOLLOW METAL FRAME H1
HOLLOW METAL FRAME
4
HM MASONRY DTL - HEAD SCALE: 3" = 1'-0"
ANCHOR 5 3/4"
2"
HOLLOW METAL FRAME
1/2" 1/2"
SEALANT AND BACKER ROD -BOTH SIDES EXISTING MASONRY PARTITION.
1/4"
STUD PARTITION -SEE PLAN FOR TYPE
2"
SEALANT -BOTH SIDES
2"MIN.
GROUT FRAME SOLID
INTERSECTING PARTITION IN SOME LOCATIONS SEE WALL TYPE FOR PARTITION WIDTH
JAMB
3
ANCHOR
J1
DOOR DETAILS
5
SCALE: 3" = 1'-0"
HM MASONRY DTL - JAMB SCALE: 3" = 1'-0"
9-2 13 13-1 14 16 17 19-0 21-0 23-0 41C 45 C 101 102 104 105 105C 106 107 108 109 110 111 111A 111B 111C 111D 112 113 114 115 117 118 119 120 121 122 123 124 125 126 127 138 142 143 BT1.1 BT1.2 EL1 GT1.1 GT1.2
ROOM FINISH SCHEDULE - UPPER FLOOR PLAN
FINISH NAME
FLOOR
MATERIAL STORAGE ART STORAGE ART FCS HOME MAKING FACULTY WORKROOM FACULTY WORKROOM FACULTY WORKROOM STORAGE STORAGE ENTRANCE CONNECTING CORRIDOR SERVING 1 KITCHEN OFFICE SERVING 2 REFUSE KITCHEN HELP JANITOR CLOSET FOOD STORAGE CORRIDOR CORRIDOR CORRIDOR CORRIDOR CORRIDOR STORAGE & MECHANICAL ROOM HALL MEN'S TOILET WOMEN'S TOILET STORAGE STORAGE MECH. RM. IT/ STORAGE MAIN OFFICE PRINCIPAL OFFICE GUIDANCE OFFICE HALL WT MT MECH/ STORAGE CLOSET DARK ROOM BOY'S TOILET 1.1 BOY'S TOILET 1.2 ELEV. GIRL'S TOILET 1.1 GIRL'S TOILET 1.2
VCT-1 VCT-1 VCT-1 VCT-1 VCT-1
BASE
ROOM WALL
WB-1 WB-1 WB-1 WB-1 WB-1
ACT-1 ACT-1 ACT-1
PT-1 PT-1 PT-1 PT-1
CTB-1
CWT-1
CTB-1
CWT-1
CEILING
ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-2 ACT-2 ACT-1 ACT-3 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-2 ACT-2 ACT-2 ACT-2 ACT-2
WB-1 PT-1
COMMENTS
NUMBER
2,5 2,5 4
4
1,2,5 1,2,5 1,2,5 1,2,5 1,2,5
EP-1 ACT-1 ACT-1 ACT-1 EP-1 EP-1
CPT-1 CPT-1 CPT-1 CPT-1 CPT-1
WB-1 WB-1 WB-1 WB-1 WB-1
ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1
PT-1 PT-1 PT-1 PT-1 PT-1
EP-1
ERF-1 ERF-1 VCT-1 ERF-1 ERF-1
ERF-1 ERF-1 WB-1 ERF-1 ERF-1
PT-1/CWT-1 PT-1/CWT-1
ACT-1 ACT-1 ACT-1 ACT-1
4 4
PT-1/CWT-1 PT-1/CWT-1
ACT-1 ACT-1
4 4
5
A-601
A-601
ROOM FINISH SCHEDULE NOTES: 1. SCOPE OF PAINTING TO INCLUDE 1) DOOR FRAMES; 2) ELECTRICAL PANEL COVERS; 3) CABINET HEATERS; 4) WINDOW BULKHEADS; 5) STELL COLUMNS IN GLAZED BLOCK WALLS; 6) EXTERIOR LOUVERS AND GRILLES.
CAREFULLY CUT AND REMOVE EXISTING BRICK FOR REINSTALLATION OF SALVAGED FIRE EXTINGUISHER CABINET.
WALL
CEILING
COMMENTS
ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 VCT-1 VCT-1 VCT-1 VCT-1 EP-1
WB-1 WB-1 WB-1 WB-1
VCT-1 VCT-1 EP-1
WB-1 WB-1
PT-1 PT-1 PT-1 PT-1
1 S. 3rd Street Alpha Building, 7th Fl. Easton, PA 18042 t 610.559.6000 f 610.559.2174 1 1 1 1
usaarchitects.com Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
ACT-1
ACT-1 ACT-1 ACT-2 ACT-2 ACT-2 ACT-2 ACT-2 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1 ACT-1
PT-1
CPT-1 CPT-1 CPT-1 CPT-1 CPT-1 CPT-1 CPT-1 CPT-1
WB-1 WB-1 WB-1 WB-1 WB-1 WB-1 WB-1 WB-1
PT-1 PT-1 PT-1 PT-1 PT-1 PT-1 PT-1 PT-1
EP-1 EP-1 EP-1 EP-1 ERF-1 ERF-1 ERF-1 ERF-1
ERF-1 ERF-1 ERF-1 ERF-1
PT-1/CWT-1 PT-1/CWT-1 PT-1/CWT-1 PT-1/CWT-1
ACT-1 ACT-1 ACT-1 ACT-1 ACT-1
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
1,2,5 1,2,5 1,2,5 1,2,5 1,2,5
REYNOLDS SOLUTIONS 3300 NORTH THIRD STREET HARRISBURG, PA 17110 t.717.238.5737
4 4 4 4
2. PROVIDE RATED ACT & GRID IN ALL CORRIDORS. 3. ABATE EXISTING VAT, SHOT-BLAST CONCRETE FLOOR PRIOR TO INSTALL OF EPOXY FLOORING. 4. CERAMIC TILE TO BE AT BOTH SIDES OF NEW PARTITIONS & EXISTING PATCHED AREAS.
FINISH NAME
150 150A 150B 153 154 155 158-1 159 161 162 167 170 170-1 171 172 173 174
3. PAINT DOOR FRAMES IN ROOMS WHERE ANY OF THE FOLLOWING ITEMS ARE BEING PAINTED: ELECTRICAL PANEL COVERS, CABINET HEATERS, WINDOW BULKHEADS, STEEL COLUMNS IN GLAZED BLOCK CORRIDOR WALLS, EXTERIOR LOUVERS/GRILLES. 4
BASE
ROOM
2. PATCH SCREW HOLES AT LOCATIONS OF DEMOLISHED WALL AND FLOOR DOORS STOPS THAT ARE NOT BEING REPLACED.
NEW SCHEDULED HM FRAME TO BE FULL CORRIDOR WIDTH AND GROUTED SOLID. PAINT FRAME.
FACULTY WORKROOM FACULTY WORKROOM FACULTY WORKROOM FACULTY WORKROOM FACULTY WORKROOM FACULTY WORKROOM FACULTY WORKROOM SCIENCE LAB SCIENCE LAB SCIENCE LAB SCIENCE LAB MECH. FACULTY WORKROOM CLASSROOM CLASSROOM MECHANICAL EQUIPMENT CONFERENCE STORAGE CORRIDOR CORRIDOR CORRIDOR CORRIDOR CORRIDOR STORAGE STORAGE STORAGE MAIN OFFICE PRINCIPAL OFFICE HALL OFFICE GUIDANCE GUIDANCE GUIDANCE CONFERENCE ROOM WOMEN'S TOILET 1 MEN'S TOILET 1 MECH. MECHANICAL MECHANICAL JANITOR CLOSET BOY'S TOILET 2.1 BOY'S TOILET 2.2 GIRL'S TOILET 2.1 GIRL'S TOILET 2.2
NUMBER
1. ALL FINISHES ARE PROVIDED AS BASIS OF DESGN (B.O.D.). PROVIDE EQUALS AS REQUIRED. REMOVE CEILING TILE AND GRID (+8'-6", VIF) AS REQUIRED. REINSTALL TO MATCH EXISTING. BOTH SIDES OF WALL.
FLOOR
ROOM FINISH SCHEDULE - AREA B
GENERAL NOTES:
NEW REINFORCED PRE-CAST LINTEL AT WIDTH TO ACCOMMODATE NEW DOOR.
NAME
27-0 29-0 31-0 33-0 37-0 38-0 40-0 43 44 45 46 46-0 47-0 50 55 203 204 210 211 211A 211B 211C 211D 212 213 214 220 221 222 223 224 225 226 227 228 229 231 240 241 245 BT2.1 BT2.2 GT2.1 GT2.2
1 1 1 1
FINISH
FLOOR
CORRIDOR CORRIDOR CORRIDOR CORRIDOR CORRIDOR NURSE HEALTH CL. JANITOR CLOSET STORAGE STORAGE JANITOR CLOSET VOCAL VOCAL WOMEN CORRIDOR STORAGE STORAGE
BASE
WALL
CEILING
COMMENTS
ACT-2 ACT-2 ACT-2 ACT-2 ACT-2 ACT-1 ACT-1 ACT-1
EP-1 EP-1 EP-1 EP-1
1,2,5 1,2,5 1,2,5 1,2,5 1,2,5
ACT-1 ACT-1 ACT-2 ACT-1 ACT-1
2, 5
5. PAINT ALL EXISTING PLASTER/ GWB WALLS ABOVE LOCKERS IN MAIN CORRIDORS. EXISTING MASONRY WALLS TO REMAIN. PATCH EXISTING TERRAZO FLOORING AS REQUIRED.
6
FINISH MATERIAL LEGEND
NEW HM FRAME - ELEVATION
TAG
FINISH
MANUFACTURER
SCALE: 3/4" = 1'-0"
FLOOR FINISHES
STYLE
COLOR
SIZE
COMMENTS
CROSSVILLE (B.O.D.)
-
TBD
MOSAIC
CPT-1 CARPET TILE
TANDUS-CENTIVA (B.O.D.)
ELEMENT 04468; PURE GRAY 76001
-
24X24
ERF
EPOXY RESINOUS FLOORING
KEY RESIN COMPANY (B.O.D.)
-
-
EP
EPOXY PAINT ARMSTRONG (B.O.D.)
-
-
12X12
CWT-1 CERAMIC WALL TILE
CROSSVILLE (B.O.D.)
-
-
MATCH BLOCK
PT-1
PAINT
BENJAMIN MOORE (B.O.D.)
-
-
SEE SPECIFICATIONS
PT-2
PAINT
BENJAMIN MOORE (B.O.D.)
-
-
SEE SPECIFICATIONS
CT-1
CERAMIC TILE
VCT-1 VINYL COMP. TILE
QUARTER TURN
-
PROVIDE AS BASE MTL WHERE INDICATED
-
NEW HM FRAME; GROUTED SOLID. WALL FINISHES
PATCH EXISTING TERRAZO FLOORING AS REQUIRED. PROVIDE 2 UNEQUAL LEAVES PER DOOR SCHEDULE. ADJUST WIDTH OF SMALLER LEAF TO ACCOMMODATE NEW FRAME SIZE.
Signature & License No.
EX8715
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
BASE FINISHES 6"
MIN. CLEARANCE BETWEEN CABINET AND NEW DOOR
CTB-1 CERAMIC TILE BASE
CROSSVILLE (B.O.D.)
-
-
MATCH BLOCK
WB-1
ARMSTRONG (B.O.D.)
-
-
4" AND 6"
WALL BASE
ALTERATIONS AT
CEILING FINISHES
CAREFULLY CUT AND REMOVE EXISTING BRICK FOR REINSTALLATION OF SALVAGED FIRE EXTINGUISHER CABINET.
VERIFY EXG. CORRIDOR WIDTH
LOG COLLEGE MIDDLE SCHOOL
ACT-1 ACOUSTIC PANEL CEILING
CERTAINTEED CEILINGS (B.O.D.) PERFORMA FINE FISSURED HHF-197
WHITE
24X48
STANDARD
ACT-2 ACOUSTIC PANEL CEILING
CERTAINTEED CEILINGS (B.O.D.) PERFORMA FINE FISSURED PFF-197
WHITE
24X48
RATED (PROTECTONE)
ACT-3 ACOUSTIC PANEL CEILING
CERTAINTEED CEILINGS (B.O.D.) PERFORMA ENRIVOGUARD
WHITE
24X48
WASHABLE
FOR THE
CENTENNIAL SCHOOL DISTRICT
7
433 CENTENNIAL ROAD, WARMINSTER, BUCKS COUNTY, PENNSYLVANIA 18974
NEW HM FRAME - PLAN SCALE: 3/4" = 1'-0"
NOTES: 1. WINDOW PROFILES ARE SHOWN AS B.O.D. INTERMEDIATE MULLION QUANTITIES AND SPACING MAY CHANGE BASED ON GC AND OWNER REQUIREMENTS. 2. G.C. TO VERIFY ALL EXISTING MASONRY OPENING SIZES FOR EACH NEW WINDOW AS REQUIRED. 3. PROVIDE SHOP ASSEMBLED WINDOW UNITS FOR FIELD INSTALLATION. 4. PROVIDE SILL AND HEAD FLASHINGS. 5. ALL GLAZING TO BE 1", INSULATED. 6. ALL GLAZING TO BE EITHER CLEAR IGU GL1 OR SPANDREL IGU GL2
5'-0 1/4" 3'-7 5/8" 14'-0"
EXG. M.O. VIF
EXG. M.O. VIF
4'-11 5/8"
EXG. M.O. VIF
GWB BULKHEAD AT CEILING
EXG. M.O. VIF
10'-4" GWB BULKHEAD AT CEILING
10'-5 7/8"
FINISH FLOOR LEVEL A
B
VARIES
C
GL2
GL2
3'-0"
6'-3"
VIF 2'-10"
6'-3"
3'-0"
D
E
GL2
GL1
GL1
GL1
ISSUED FOR CONSTRUCTION
Date
Issue or Revision
Drawing Title
GL2
F
03-14-2018 No.
7'-0"
EXG. M.O. VIF
GL1
10'-1"
1'-0"
GL2
GL1
EXG. M.O. VIF
GL1
10'-1"
EXG. M.O. VIF
GL1
10'-1"
7'-11 5/8"
EXG. M.O. VIF
GL1
3'-0"
GL1
6'-5 5/8"
EXG. M.O. VIF
GL1
FLR SLOPES
2/28/2018 3:11:00 PM
GL1
4'-11 5/8"
GL1
2'-11 5/8"
EXG. M.O. VIF
12'-0"
EXG M.O. VIF
EXG. M.O. VIF
GL2
EXG M.O. - 21'-4"+/-
GWB BULKHEAD AT CEILING
EXG. M.O. VIF
VIF
GL2
GWB BULKHEAD AT CEILING
7'-0"
EXG M.O. - 8'-0"
2'-6"
CEILING AT 2ND FLOOR CLASSROOMS
2'-0"
EXG. M.O. VIF
WINDOW TYPES & FINISH SCHEDULES LOG COLLEGE MS Scale
G
USA Project No.
As indicated Drawing Date
1
WINDOW TYPES SCALE: 1/4" = 1'-0"
2
2017-002 Drawing No.
BUILDING B - SOUTH ENTRANCE
01.08.2018
SCALE: 1/4" = 1'-0"
Drawn By
Checked By
Author
Checker
A-601
NEW CONSTRUCTION AT
40 LT. GLENN ZAMORSKI DRIVE
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
FOR
14-22 HIGH STREET ASSOCIATES, LLC
usaarchitects.com Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
40-42 LT. GLENN ZAMORSKI DRIVE, ELIZABETH, NJ 07201
GENERAL NOTES:
ZONING INFORMATION
CODE COMPLIANCE
WARD #
EXISTING
ZONE: (40 LT. GLENN ZAMORSKI DR.)
'R-3A' - FOUR FAMILY RESIDENTIAL ZONE
ZONE: (42 LT. GLENN ZAMORSKI DR.) PRINCIPLE USE GROUP: (40 LT. GLENN ZAMORSKI DR.)
PROPOSED
YES NO REMARKS
YES NO
REMARKS
TS-1
TITLE SHEET
ARCHITECTURAL
'R-2' - TWO FAMILY RESIDENTIAL
RESIDENTIAL
TWO FAMILY RESIDENTIAL N/A
SITE AREA: (40 LT. GLENN ZAMORSKI DR.)
5,000 SF
SITE AREA: (42 LT. GLENN ZAMORSKI DR.)
N/A
N/A
BLDG. FLOOR AREA: (40 LT. GLENN ZAMORSKI DR.)
N/A
N/A
BLDG. FLOOR AREA: (42 LT. GLENN ZAMORSKI DR.)
N/A
N/A
A-1 A-2 A-3 A-4
TWO FAMILY RESIDENTIAL 2,500 SF 2,500 SF 1,173 SF
CIVIL DETAILS AND FOUNDATION PLAN FLOOR PLANS AND PARTITION TYPES ELEVATIONS DETAILS, RISER DIAGRAM, AND WALL SECTION
1,173 SF
BUILDING CODE + INFORMATION SUMMARY: 100'
100.0'
B) LOT WIDTH:
25'
25'
C) LOT FRONTAGE:
25'
25'
ALL WORK SHALL COMPLY WITH ALL GOVERNING CODES, REGULATIONS AND ORDINANCES, ETC. COMPLIANCE WITH THE FOLLOWING STANDARDS (MOST RECENT VERSION) IS REQUIRED:
100'
B) LOT WIDTH:
25'
25'
C) LOT FRONTAGE:
25'
25'
YARD DIMENSIONS (40 LT. GLENN ZAMORSKI DR.)
N/A
20'
REAR YARD: 60' (PREVAILING)
N/A
75'
LEFT SIDE: 12% WIDTH, NOT LESS THAN 3'-1"
N/A
3'
RIGHT SIDE: 12% WIDTH, NOT LESS THAN 3'-1"
N/A
4'-1"
3. THE CONTRACTOR IS RESPONSIBLE FOR COMPLIANCE WITH ALL APPLICABLE BUILDING CODES & REGULATIONS AND FOR OBTAINING ALL NECESSARY AND REQUIRED INSPECTIONS, APPROVALS AND PERMITS, NECESSARY TO PERFORM ALL WORK AND SERVICES HEREIN NOTED OR INDICATED ON THE DRAWINGS.
23. WATER RESISTANT GYPSUM BACKER BOARD SHALL BE USED IN TOILET ROOMS.
R-5 (DETACHED TWO FAMILY DWELLING)
CONSTRUCTION TYPE:
V-A (COMBUSTIBLE)
SPRINKLERED:
YES
BUILDING AREA:
GROUND FLOOR:
1,173 SF (GARAGE - 403 SF)
FIRST FLOOR:
1,241 SF
VARIANCE (GRANTED 11/2/06) VARIANCE (GRANTED 11/2/06) VARIANCE (GRANTED 11/2/06)
SECOND FLOOR:
1,241 SF
TOTAL:
3,655 SF
(NFPA 13D)
2. PROTECT AT ALL TIMES ADJACENT PROPERTIES AND PUBLIC RIGHT-OF-WAYS FROM DAMAGE, DUST AND DEBRIS. PROVIDE FOR THE SAFETY OF PEDESTRIANS AT ALL TIMES. 3. ALL UNDERGROUND PIPING TO BE REMOVED SHALL BE CAPPED AT THE PROPERTY LINE. 4. THE USE OF EXPLOSIVES IS PROHIBITED WITHOUT THE REQUIRED LOCAL AND STATE PERMITS.
7. ALL CONSTRUCTION DEBRIS AND REFUSE SHALL BE DISPOSED OF OFF-SITE IN AN APPROPRIATE MANNER.
9. IN THE EVENT A DISCREPANCY IS FOUND IN THE CONTRACT DOCUMENTS, THE OWNER SHALL BE NOTIFIED IMMEDIATELY.
8. ACCOMPLISH AND PERFORM THE DEMOLITION IN SUCH A MANNER AS TO PREVENT THE UNAUTHORIZED ENTRY OF PERSONS AT ANY TIME.
10. ALL STUD WALLS ARE DIMENSIONED AT 5" UNLESS NOTED OTHERWISE.
MAXIMUM HEIGHT:
3 STORIES
BUILDING VOLUME:
38,350 CU FT
33'-3" HEIGHT
9. REMOVE FROM THE DESIGNATED SITE, AT THE EARLIEST POSSIBLE TIME, ALL DEBRIS, RUBBISH, SALVAGEABLE ITEMS, HAZARDOUS AND COMBUSTIBLE SERVICES. REMOVAL OF HAZARDOUS AND COMBUSTIBLE MATERIAL SHALL BE ACCOMPLISHED IN ACCORDANCE WITH THE PROCEDURES AS AUTHORIZED BY THE FIRE DEPARTMENT OR OTHER APPROPRIATE REGULATORY AGENCIES AND AUTHORITIES.
11. ASSUME MINIMUM FIBER STRESS 1200 PSI FOR ALL STRUCTURAL BEAMS AND HEADERS UNLESS OTHERWISE NOTED.
13. INDIVIDUAL AIR CONDITIONING UNITS MUST HAVE ADEQUATE RETURN AIR.
FIRE SEPARATION: N/A
20'
REAR YARD: 60' (PREVAILING)
N/A
75'
LEFT SIDE: 12% WIDTH, NOT LESS THAN 3'-1"
N/A
3'
RIGHT SIDE: 12% WIDTH, NOT LESS THAN 3'-1"
N/A
4'-1"
B) BUILDING PROJECTIONS (ALL LOTS) C) ACCESSORY STRUCTURE USE (ALL LOTS)
N/A
N/A
D) OPEN SPACE (40 LT. GLENN ZAMORSKI DR.) 200 SQ FT PER UNIT REQUIRED
N/A
28.5' * 25' = 712 SQ FT
D) OPEN SPACE (42 LT. GLENN ZAMORSKI DR.) 200 SQ FT PER UNIT REQUIRED
N/A
DESIGN LOADS:
EXTERIOR WALLS: (LESS THAN 3FT)
1 HOUR
INTERIOR BEARING PARTITIONS: INTERIOR NONBEARING PARTITIONS: GARAGE SEPARATION: FLOOR CONSTRUCTION:
1 HR O HR 1 HR 1 HR
ROOF CONSTRUCTION:
1 HR
ATTIC: NO STORAGE
ATTIC: W/ STORAGE
LL: 10#/SF
LL: 20#/SF
DL: 10#/SF
DL: 10#/SF
TL: 20#/SF
TL: 30#/SF
ROOF:
BEDROOMS:
LL: 25#/SF
LL: 30#/SF
DL: 10#/SF
DL: 10#/SF
TL: 35#/SF
TL: 40#/SF
OTHER ROOMS:
GARAGE:
LL: 40#/SF
LL: 50#/SF
DL: 10#/SF
DL: 10#/SF
TL: 50#/SF
TL: 60#/SF
14. ALL INTERIOR TOILET ROOMS SHALL BE MECHANICALLY VENTED THROUGH NON-COMBUSTIBLE DUCTS (TO THE EXTERIOR) TO PROVIDE AIR CHANGE EVERY 12 MINUTES (UNDERCUT DOOR 1") - NOTE: NOT REQUIRED WITH OPERABLE WINDOW.
10. USE WATERING, TEMPORARY ENCLOSURES AND OTHER SUITABLE METHODS, AS NECESSARY TO LIMIT THE AMOUNT OF DUST AND DIRT RISING AND SCATTERING IN THE AIR. CLEAN ADJACENT STRUCTURES AND IMPROVEMENTS OF ALL DUST AND DEBRIS CAUSED BY THE DEMOLITION OPERATIONS. RETURN ALL ADJACENT AREAS TO THE CONDITIONS EXISTING PRIOR TO THE START OF WORK. 11. IN ACCORDANCE WITH THE STATE LAW, THE CONTRACTOR SHALL BE REQUIRED TO CALL THE BOARD OF PUBLIC ONE CALL DAMAGE PROTECTION SYSTEM FOR UTILITY MARK OUT IN ADVANCE OF ANY EXCAVATION.
15. REMOVE RUBBISH FROM PREMISES AS OFTEN AS NECESSARY OR DIRECTED. 16. ALL WORK AND EQUIPMENT SHALL BE CLEANED TO THE SATISFACTION OF THE OWNER BEFORE TURNING SAME OVER TO OWNER. 17. CAULKING, SEALANT AND EXTERIOR JOINTS AROUND WINDOWS AND DOOR FRAMES, BETWEEN WALL AND FOUNDATION, BETWEEN WALL PANELS AT PENETRATIONS, OR UTILITY SERVICES THROUGH WALLS, FLOORS AND ROOFS, AND ALL OTHER OPENINGS IN THE EXTERIOR ENVELOPE SHALL BE SEALED WITH AN APPROVED MANNER.
12. ALL TRENCHES SHALL BE BACKFILLED WITHOUT DELAY, OPEN TRENCHES ARE TO BE KEPT TO A MINIMUM. 13. THE BUILDING(S) SHALL BE RAZED PRIOR TO THE CONSTRUCTION OF THE NEW BUILDING. 14. CONTRACTOR TO COORDINATE WITH RELEVANT UTILITY COMPANIES REGARDING DEMOLITION. 15. ALL STORM OUTFALLS AND PIPES WHICH ARE TO REMAIN ON SITE SHALL BE CLEARED OF ANY DEBRIS, POWER WASHED AND MAINTAINED DURING AND AFTER CONSTRUCTION OF THE PROJECT.
18. FIRE STOP ALL STUD WALLS AT 8'-0" VERTICALLY (OR AT EACH FLOOR).
16. ALL EXCESS SOIL MATERIAL SHALL BE REMOVED FROM THE SITE IN ACCORDANCE WITH LOCAL AND STATE AUTHORITIES.
28.5 * 25' = 712 SQ FT
PRINCIPAL BUILDING REGULATIONS (40 LT. GLENN ZAMORSKI DR.) A) HEIGHT LIMITATIONS C-5 SAME AS R-1 SINGLE FAMILY RESIDENTIAL (3 ST/35 FT)
VARIANCE (GRANTED 11/2/06) VARIANCE (GRANTED 11/2/06)
2'-0"
N/A
5. THE LOCATION OF ALL UNDERGROUND UTILITIES ARE SHOWN FOR REFERENCE PURPOSES ONLY AND ARE TO BE FIELD VERIFIED PRIOR TO ANY CONSTRUCTION ACTIVITIES. ANY DISCREPANCIES BETWEEN PLAN AND FIELD INFORMATION ARE TO REPORTED IMMEDIATELY TO THE OWNER. 6. THE DISRUPTION OF EXISTING UTILITY SERVICES SHALL BE AVOIDED TO THE GREATEST EXTENT POSSIBLE. ANY REQUIRED DISRUPTION OF SERVICE SHALL BE COORDINATED IN ADVANCE WITH THE RESPECTIVE AUTHORITY AND AFFECTED USERS SHALL BE ADEQUATELY NOTIFIED.
8. ANY ERRORS, OMISSIONS OR INCONSISTENCIES ON THESE DRAWINGS OR ANY VARIATIONS OR AMBIGUITIES BETWEEN THESE DRAWINGS AND ACTUAL SITE AND CONSTRUCTION CONDITIONS AND/ OR REQUIREMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER IN WRITING AND RESOLVED AND DOCUMENTED IN WRITING BEFORE CONTINUING WITH THE WORK IN QUESTION.
YARD DIMENSIONS (42 LT. GLENN ZAMORSKI DR.)
FRONT YARD: 20' MINIMUM
24. THERMOSTATS USED FOR HEATING AND COOLING SHALL BE CAPABLE OF BEING SET FROM 55 DEGREES F TO 85 DEGREES F AND SHALL BE CAPABLE OF OPERATING THE SYSTEM'S HEATING AND COOLING SEQUENCE.
1. WORK TO BE IN ACCORDANCE WITH ALL LOCAL AND STATE RULES AND REGULATIONS AND THE OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA).
12. SMOKE DETECTORS TO BE AC POWERED AND UL APPROVED W/ BATTERY BACK UP. SETBACKS
22. CABINET SUPPLIER TO FIELD MEASURE AREA OF WORK AFTER ROUGH FRAMING TO ASSURE AN EXACT FIT.
SITE DEMOLITION NOTES:
7. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES REQUIRED FOR SAFE EXECUTION AND COMPLETION OF WORK AND FOR INITIATING, MAINTAINING AND SUPERVISING ALL SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK.
USE GROUP(S):
SETBACKS FRONT YARD: 20' MINIMUM
21. ALL HVAC EQUIPMENT SHALL COMPLY WITH ALL APPLICABLE STATE, NATIONAL, AND LOCAL CODES.
6. ALL MANUFACTURED MATERIALS, COMPONENTS, FASTENERS, ASSEMBLIES, ETC. SHALL BE HANDLED AND INSTALLED IN ACCORDANCE WITH MANUFACTURES INSTRUCTIONS AND RECOMMENDATIONS. WHERE SPECIFIC MANUFACTURED PRODUCTS ARE CALLED FOR, THE CONTRACTOR MUST NOTIFY THE OWNER OF ANY SUBSTITUTIONS BEFORE THEY ARE MADE.
17.36.100 - LOT DIMENSIONS (42 LT. GLENN ZAMORSKI DR.) 100'
2. ALL WORK/ CONSTRUCTION SHALL BE DONE IN STRICT ACCORDANCE WITH ALL FEDERAL, STATE & LOCAL CODES, ORDINANCES, RULES & REGULATIONS. WHERE SUCH CODES, RULES & REGULATIONS ARE AT VARIANCE WITH THE PLANS & NOTES: SAID CODES, RULES & REGULATIONS, ETC. SHALL TAKE PRECEDENCE OVER THE PLANS & NOTES.
5. UNLESS SHOWN ON THESE DRAWINGS, ALL MECHANICAL WORK, SUCH AS, BUT NOT LIMITED TO ELECTRICAL, PLUMBING, HEATING, AIR CONDITIONING, VENTILATING, SITE WORK ETC., ARE TO BE ESTABLISHED AND DESIGNED BY OTHERS THAN ARCHITECT.
INTERNATIONAL RESIDENTIAL CODE 2015
A) LOT DEPTH:
20. ALL FRAMING TO BE IN CONFORMANCE WITH THE NATIONAL FOREST PRODUCTS 'MANUAL FOR HOUSE FRAMING' AND THE LATEST EDITION OF THE MOST CURRENT BUILDING CODE.
4. THESE DRAWINGS DO NOT CONTAIN COMPLETE SPECIFICATIONS, DETAILS, AND INFORMATION REQUIRED FOR THE INTERIOR FINISHES OF THE PROJECT. ADDITIONAL INFORMATION SHALL BE OBTAINED FROM THE OWNER.
17.36.100 - LOT DIMENSIONS (40 LT. GLENN ZAMORSKI DR.) A) LOT DEPTH:
19. DRYWALL INSTALLATION SHALL BE IN CONFORMANCE WITH THE GYPSUM ASSOCIATION'S RECOMMENDED PRACTICES FOR THICKNESS, NAILING AND TAPING CORRECT STUD SPACING.
1. THE CONTRACTOR SHALL EXAMINE AND BECOME FAMILIAR WITH ALL CONTRACT DOCUMENTS IN THEIR ENTIRETY. SURVEY THE PROJECT AND BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND SCOPE OF WORK.
'R-2' - TWO FAMILY RESIDENTIAL N/A
PRINCIPLE USE GROUP: (42 LT. GLENN ZAMORSKI DR.)
DRAWING LIST
CODE COMPLIANCE
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
N/A
3 ST/33FT
N/A
3 ST/33FT
LT. GLENN ZAMORSKI DR.
PRINCIPAL BUILDING REGULATIONS (42 LT. GLENN ZAMORSKI DR.)
NUMBER OF PARKING SPACES REQUIRED (ALL LOTS) NJRSIS PARKING: 2-BR UNIT @ 2 EACH
N/A
4 PARKING SPACES
PROPOSED WATER SERVICE CONNECTION BY LIBERTY WATER CO. - TYP.
PROPOSED GAS SERVICE CONNECTION BY NUI ELIZABETHTOWN GAS - TYP.
20'-0" 2"
A) HEIGHT LIMITATIONS R-3A SAME AS R-1 SINGLE FAMILY RESIDENTIAL (3 ST/35 FT)
PROPOSED SAN. SEWER CONNECTION
AI16116
Signature & License No.
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
DECIDUOUS SHADE TREE - TYP.
NEW CONSTRUCTION
ELECTRIC FROM NEAREST POLE TO NEW TRANSORM - TO BE COORDINATED WITH UTILITY COMPANY - TYP.
BITUMINOUS DRIVEWAY - TYP.
AT
CONCRETE APRON - TYP.
40 LT. GLENN ZAMORSKI DRIVE FIRST FLOOR ABOVE
BLDG. OVERHAND (6'-0") - TYP. 75'-0" 7"
14-22 HIGH STREET ASSOCIATES, LLC 40-42 LT. GLENN ZAMORSKI DRIVE, ELIZABETH, NJ 07201
5" 55'-0"
TWO PARKING SPACES IN GARAGE - TYP.
FOR
BLDF. OVERHANG (3'-0") - TYP.
PROJECT LOCATION: 40-42 LT. GLENN ZAMORSKI DRIVE ELIZABETH, NJ 07201
9" 100'-0"
PROJECT LOCATION: 40-42 LT. GLENN ZAMORSKI DRIVE ELIZABETH, NJ 07201
0" 3'-0" 0" 4'-1"
FIRST FLOOR ABOVE
0" 4'-1"
3" 25'-0"
0" 3'-0"
RESIDENTIAL UNIT #1 REFER TO A-2
1
03.31.17
ISSUED FOR PERMIT
No.
Date
Issue or Revision
Drawing Title
8/17/2017 10:17:45 AM
TITLE SHEET 25'-0" 2"
1
ZONING MAP SCALE: N.T.S.
2
LOCATION MAP SCALE: N.T.S.
3
PROPOSED SITE PLAN SCALE: N.T.S.
25'-0" 2"
Scale
USA Project No.
As indicated TYPE
BOTANICAL NAME
COMMON NAME
INSTALLED SIZE
MATURE SIZE
Drawing Date
DECIDUOUS
CORNUS FLORIDA
FLOWERING DOGWOOD
6'-8"
15' - 25' HEIGHT 20' - 30' SPREAD
03.31.17
2016-063 Drawing No.
Drawn By
Checked By
JS/DH
APA
TS-1
A
MECH JOINT (TYP.) WATER MAIN CONCRETE THRUST BLOCKS SHALL BE PROVIDED AT ALL BENDS OR OTHER POINTS OF PIPE DIRECTION CHANGE
O.D.
L
D
VALVE BOX COVER MARKED WATER
DEPTH VARIES
TELESCOPIC ADJUSTABLE VALVE A
WATER MAIN MAY BE DUCTILE IRON CEMENT LINED PIPE ALL JOINTS SHALL BE MECHANICAL JOINT OR PUSH-ON AND ALL FITTINGS SHALL BE MECHANICAL JOINT CAST IRON
ANGLE
"D" EQUALS
"R" EQUALS
"L"* EQUALS
45° 22 1/2° 11 1/4 °
Tx1.414 Tx2.613 Tx5.126
Tx1.000 Tx2.414 Tx5.027
D-2A D-2A D-2A
OFFSETS MAY BE SUBTITUTED FOR A OR T UP TO 24" IF APPROVED BY THE ENGINEER.
4.
CONCRETE THRUST BLOCKS SHALL BE PROVIDED AT ALL BENDS OR OTHER POINTS OF PIPE DIRECTION CHANGE.
SIDEWALK ROAD WAY
CONTRACTOR SHALL PROVIDE
2.
TIE RODS SHALL BE UTILIZED TO RESTRAIN PIPE JOINTS. DETAILS OF THE TIE ROD ASSEMBLY SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL. TIE RODS SHALL BE SUFFICIENT TO RESTRAIN THE THRUST DEVELOPED AT 100 P.S.I. WORKING PRESSURE.
3.
LOOPING WATER MAIN
2
SCALE: N.T.S.
PVC SCHEDULE 40 PIPE OR APPROVED EQUAL. SEE PLAN FOR PIPE SIZE.
WATER MAIN PIPE
NOTES:
SIZE AND BEARING FOR THRUST BLOCK SHALL CONFORM TO CURRENT A.W.W.A. STANDARDS, OR SHALL BE DESIGNATED ON THE PLANS.
WHERE PIPE INVERTS ARE IN ROCK, EXCAVATE 6" BELOW INVERT OF PIPE AND FILL WITH 3/4" CRUSHED STONE.
2.
WHERE PIPE INVERTS ARE IN SOFT ORGANIC SOIL AT LEAST 2 FEET OF CRUSHED STONE SHALL BE USED FOR BEDDING, UNDERLAIN BY A LAYER OF FILTER FABRIC SUCH AS MIRAFI OR EQUIVALENT AS DIRECTED BY THE ENGINEER.
3.
WHERE PIPE INVERTS ARE IN FILL CONDITION, SAID FILL IS TO BE CONTROLLED COMPACTED FILL. WHERE PIPES ARE WITHIN CITY ROADS, SEE CITY ROAD PAVEMENT REPAIR DETAIL.
ALL CONNECTIONS TO BE MECHANICAL JOINT, OR LOCK RING TYPE JOINTS, AS SPECIFIED.
GATE VALVE ASSEMBLY
3
SCALE: N.T.S.
NOTES: 1. RISER CONNECTION AND COVER SHALL BE LOCATED WITHIN THE CITY RIGHT-OF-WAY. 2. ALL COUPLINGS, PLUGS, PIPES, AND CAPS TO BE STANDARD FOR THE TYPE OF PIPE USED. INSTALLATION ARE TO BE WATERTIGHT.
4. HOUSE CONNECTIONS ARE TO BE SIZE AS SHOWN (P.V.C. SHALL NOT BE USED WITH LESS THAN 3' OF COVER.
SLEEVE TO JOIN PVC
1/8 BEND 45° WYE
WATER MAIN BEDDING
SANITARY SEWER MAIN
5. SLOPE OF 1/4" PER FOOT MINIMUM REQUIREMENT FOR SEWER LATERAL PIPE.
PLUG OR PIPE CONNECTION
usaarchitects.com
6. REFER TO CITY OF ELIZABETH DEPARTMENT OF PUBLIC WORKS STANDARD SPECIFICATIONS FOR ROAD EXCAVATION AND RESTORATION OVER UTILITY TRENCHES FOR THE BACKFILL, BEDDING, TRENCH AND SURFACE RESTORATION REQUIREMENTS.
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
45°
3/4" CLEAN STONE
4
SCALE: N.T.S.
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
3. CLEANOUTS ARE REQUIRED AS PER PLUMBING CODE.
4' (MIN)
SEWER LATER PIPE
1.
CONCRETE FOR THE THRUST BLOCKS TO BE N.J.D.O.T., CLASS "C".
1/2" GAP
3" LONG PVC SCH 40 UNDISTURBED EARTH
NOTES 1.
SURFA CE
RISER COVER, SCREW TYPE BRASS PLUG FLUSH WITH FINISHED SURFACE
4" PVC SCH 40 RISER CONNECTION
6" CRUSHED STONE BEDDING
POURED CONCRETE THRUST BLOCK SIZE TO BE SPECIFIED (SEE DETAIL FOR SCHEDULE)
CURB
APPROVED BACKFILL
MECH. JOINT (TYP.)
BEARING ON UNDISTURBED GROUND
MINIMUM CLEARANCE BETWEEN OBSTRUCTING PIPE AND WATER MAIN SHALL BE 18" MINIMUM. CLEARANCE BETWEEN WATER MAIN AND OTHER OBSTRUCTIONS SHALL BE 6".
6.
D.I.P.
WATER MAIN AND TEE
* CUT THE PIPE SOMEWHAT SHORTER THAN THEORETICAL TO ALLOW FOR SOME SLIGHT CLEARANCE IN THE JOINTS.
3.
5.
1
GATE VALVE
MECHANICAL JOINTS
WATER MAIN MAY BE LOOPED ABOVE OBSTRUCTION, IF 3' MINIMUM COVER IS MAINTAINED ABOVE WATER MAIN.
2.
R
O.D. + 12"
NOTES: 1.
BOX, MULLER HO360 OR APPROVED EQUAL C.I. VALVE BOX
PROPERTY LINE\ R.O.W.
PAVEMENT 45° MAX.
A
POURED CONCRETE THRUST BLOCK, SIZE TO BE SPECIFIED, SEE TABLE THIS SHEET
4'-0" MIN
SEE NOTE 5
T
D.I.P
CLEANOUT & SEWER CONNECTION SCALE: N.T.S.
FINISHED GRADE PIPE EMBEDMENT ZONE WIDTH
SANITARY SEWER GENERAL NOTES
"A" 1.1 1.9 3.0 4.3 7.7 12.0 17.2
d " "A
"A" 2.0 3.6 5.5 8.0 14.2 22.3 32.0
"A "
"A "
"A"
"A"
1.4 2.7 4.2 5.7 10.0 15.7 22.7
1.4 2.7 4.2 5.7 10.0 15.7 22.7
PIPE EMBEDMENT ZONE
12"
MIN.
1/4 PIPE O.D.
HAUNCHING
3/4" STONE
UNDISTURBED EARTH
2.
THE CONTRACTOR SHALL NOTIFY ALL UTILITIES PRIOR TO THE START OF CONSTRUCTION TO INSURE THAT THEIR FACILITIES WILL NOT DETER THE COURSE OF CONSTRUCTION.
3.
THE OWNER WILL SECURE ALL NECESSARY PERMITS FROM THE MUNICIPAL, COUNTY OR STATE AGENCIES PRIOR TO THE START OF CONSTRUCTION.
4.
ALL WORK SHALL CONFORM TO THE ABOVE MENTIONED PERMITS INCLUDING BACKFILL, PAVEMENT REPAIR AND CONSTRUCTION PROCEDURES.
5.
ALL CONCRETE AS NOTED IN APPURTENANT DESIGNS SHALL BE 3,000 PSI, UNLESS OTHERWISE NOTED.
6.
ALL LATERAL LOCATIONS SHALL BE VERIFIED IN THE FIELD.
7.
ALL SANITARY SEWERS AND APPURTENANCES SHALL BE CONSTRUCTED IN COMPLIANCE WITH THE CONTRACT DOCUMENTS AND CONSTRUCTION DETAILS.
11'-2"
" "A
"A"
d
THE DESIGNS HEREIN RENDERED ARE INTENDED TO COMPLY WITH THE NJDEP. IN CASE OF UNINTENTIONAL DEVIATION AND/OR OMISSIONS, THE NJDEP REGULATIONS WILL CONTROL.
COORDINATE ALL FOOTINGS WITH WALLS ABOVE - TYP.
HAUNCH AND BEDDING COURSE SAND AND GRAVEL (NJDOT I-2) OR 3/4" CLEAN STONE.
8. HYDROHAMMERS ARE NOT TO BE USED 3' OR LESS FROM TOP OF PIPE. USE 3/4" CLEAN STONE TO
TOP OF BELL WHEN SELECT BACKFILL IS NOT USED.
9.
PIPE EMBEDMENT ZONE WIDTH SCHEDULE FOR PVC SEWER PIPE
"A" - CONTACT BEARING AREA OF BLOCK WITH EARTH, IN SQUARE FEET NOTES: 1. BEARING AREAS ARE BASED ON UNDISTURBED SOIL WITH A BEARING CAPACITY OF 4000LBS. PER SQ. FT. FOR A LESSER SOIL BEARING CAPACITY, THESE AREAS SHALL BE INCREASED ACCORDINGLY.
INSIDE DIA. OF PIPE (D) EMBEDMENT ZONE WIDTH (W)
2. ALL CONCRETE THRUST BLOCKS SHALL BE CLASS B. 3. THRUST BLOCKS SHALL BE POURED AGAINST UNDISTURBED EARTH.
10.
4", 6", 8", 10", 12"
16"
18"
21"
24"
27"
30"
3'- 6"
3'- 9"
4'- 0"
4'- 3"
4'- 6"
5'- 0"
5'- 3"
ANY ADJUSTMENTS OR REPAIRS TO EXISTING SANITARY FACILITIES DAMAGED AS A RESULT OF THE CONTRACTORS OPERATIONS SHALL BE MADE AT THE CONTRACTORS EXPENSE AND SHALL BE SUBJECT TO REVIEW, INSPECTION, APPROVAL AND ACCEPTANCE BY THE AUTHORITY ENGINEER.
30" X 30" CONCRETE FOOTING WITH (4) #4 BARS E.W.
WHEN CORING A NEW CONNECTION TO EXISTING AUTHORITY MANHOLE, CORE SHALL BE MADE AT LEAST SIX (6) INCHES FROM MANHOLE BARREL JOINTS. SANITARY SEWER LINES SHALL BE SEPARATED FROM WATER MAINS BY A DISTANCE OF AT LEAST 10 FEET HORIZONTALLY OR THE PIPES SHALL BE IN SEPARATE TRENCHES WITH THE SEWER AT LEAST 18 INCHES BELOW THE WATER MAIN. WHERE APPROPRIATE SEPARATION FROM THE WATER MAIN IS NOT POSSIBLE, THE SEWER SHALL BE ENCASED IN CONCRETE OR CONSTRUCTED OF DUCTILE IRON PIPE USING MECHANICAL OR SLIP-ON JOINTS FOR A DISTANCE OF AT LEAST 10 FEET ON EITHER SIDE OF THE CROSSING. IN ADDITION, ONE FULL LENGTH OF SEWER PIPE SHOULD BE LOCATED SO BOTH JOINTS WILL BE AS FAR AWAY FROM THE WATER LINE AS POSSIBLE.
5'-10"
45°
PLUG d
90° d
d
TEE
BEDDING
TYP.
1.
TOP OF BELL
6" MIN.
22 1/2°
"A" 0.5 1.0 1.5 2.2 4.5 6.1 8.8
6" 8" 10" 12" 16" 20" 24"
90° ELBOW
UNDISTURBED SURFACE
BEDDING
DIAMETER OF PIPE ( d )
45° ELBOW
PIPE EMBEDMENT
SELECT BACKFILL MATERIAL AS APPROVED BY ENGINEER
22 1/2° ELBOW
18'-11"
VARIES
(SEE SCHEDULE)
5'-2"
5
THRUST BLOCKS
6
SCALE: N.T.S.
PIPE BEDDING
7
SCALE: N.T.S.
SANITARY SEWER NOTES SCALE: N.T.S.
TRENCH EXCAVATION AND BACKFILL NOTES
A-1
SURFACE ZONE: ALL ALL TRENCH BACKFILL ZONE: PIPE EMBEDMENT ZONE: THE MINIMUM COMPACTION IN EMBANKMENTS SHALL BE 90%. 2.
6"
STORM SEWER PIPE AND/OR WATER MAIN
95% 90% 95%
3000 PSI CONCRETE
SANITARY SEWER PIPE, STORM SEWER PIPE OR WATER MAIN
6" D
0.5' MINIMUM & VARIES
D
SUITABLE MATERIAL FROM EXCAVATIONS SHALL BE FREE FROM OBJECTIONABLE QUANTITIES
6"
6" NOTE:
4.
BACKFILL TO BE MECHANICALLY COMPACTED IN TWELVE INCH LIFTS TO THE SATISFACTION OF THE ENGINEER.
5.
THE CONTRACTOR MUST COMPLY WITH ALL STATE AND FEDERAL CONFINED SPACE RULES, AND ALL APPLICABLE O.S.H.A. REQUIREMENTS.
FIRE STOP @ 8'-0" AFF
5/8" SHEETROCK BRAND GYPSUM PANELS - 2X4 16" O.C.
NOTE:
SANITARY SEWER
1.
ROCK AND OTHER MATERIALS CONSIDERED DELETERIOUS BY THE AUTHORITY AND SHALL NOT HAVE FINES IN EXCESS OF 10 PERCENT PASSING THE NO. 200 SIEVE NOR STONE OR GRAVEL LARGER THAN 2 INCHES.
FIRE STOP @ 8'-0" AFF
2.
CONCRETE CRADLE TO BE USED WHEN THE STORM SEWER PIPE OR WATER MAIN CROSSES OVER THE SANITARY SEWER PIPE AND THE VERTICAL CLEARANCE IS 18" OR LESS.
8
SCALE: 12" = 1'-0"
9
CONCRETE CRADLE
10
SCALE: N.T.S.
A-4
CONCRETE PIPE ENCASEMENT TO BE USED WHEN VERTICAL CLEARANCE BETWEEN WATER MAIN AND THE SEWER PIPE IS 18" OR LESS OR WHEN HORIZONTAL CLEARANCE AT SAME ELEVATION IS LESS THAN 10'.
DEPRESS SLAB -4" PITCH 1/8" PER FT.
5/8" SHEETROCK BRAND GYPSUM PANELS - 2X6 16" O.C.
AI16116
Signature & License No.
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
NEW CONSTRUCTION
THE SANITARY SEWER SHALL BE ENCASED IN CONCRETE FOR AT LEAST 10 FEET ON EITHER SIDE OF THE CROSSING. IN ADDITION, ONE FULL LENGTH OF SEWER PIPE SHOULD BE LOCATED SO BOTH JOINTS WILL BE AS FAR FROM THE WATER MAIN AS POSSIBLE.
AT
30" X 30" CONCRETE FOOTING WITH (4) #4 BARS E.W.
BASE TRIM FLOOR
EXCAVATION & BACKFILL NOTES
TYP.
3000 PSI CONCRETE
SPECIFIED PIPE SHALL BE REPLACED WITH PIPE OF GREATER CRUSHING STRENGTH OR BOTH, TO ACHIEVE SUITABLE OF ORGANIC MATTER, CLAYS, CONDITIONS. TREES, STUMPS, FROZEN MATERIAL, RUBBLE, REFUSE, CINDERS, 3.
CEILING
6"D
SEE CONCRETE ENCASEMENT DETAIL
SHALL BE INSTALLED IN A HIGHER CLASS BEDDING THAN SHOWN ON THE DRAWINGS OR THE THE PIPE EMBEDMENT ZONE WIDTH AND THE MAXIMUM TRENCH WIDTH SHALL NOT EXCEED THE PERMISSABLE WIDTHS SHOWN. IF THE PERMISSABLE WIDTH IS EXCEEDED, THE PIPE
CEILING
A
65'-0" 65'-11"
THE MAXIMUM DRY DENSITIES SHALL BE DETERMINED IN ACCORDANCE WITH ASTM DESIGNATION D1557. THE MINIMUM PERCENTAGE OF COMPACTION TO BE ACHIEVED BY THE CONTRACTOR IN THE VARIOUS ZONES IS AS FOLLOWS: INITIAL PIPE MATERIAL LOCATION COMPACTION
55'-0" 54'-11"
UNEXCAVATED 1.
TYP.
A
FLOOR
40 LT. GLENN ZAMORSKI DRIVE
6'-2"
FOR
14-22 HIGH STREET ASSOCIATES, LLC
CONCRETE ENCASEMENT SCALE: N.T.S.
INTERIOR WALL - TYPE A
PLUMBING WALL - TYPE B
40-42 LT. GLENN ZAMORSKI DRIVE, ELIZABETH, NJ 07201
COORDINATE ALL FOOTINGS WITH WALLS ABOVE - TYP. FOUNDATIONS:
3.
4.
CEILING
BOTTOMS OF ALL FOOTINGS ARE 3'-6" BELOW EXISTING GRADE UNLESS OTHERWISE NOTED. TOPS OF FOOTINGS ARE AT SAME ELEVATION AT JUNCTIONS OF WALL FOOTING AND COLUMN FOOTING. WALL FOOTING REINFORCEMENT TO RUN CONTINUOUS THROUGH COLUMN FOOTING. BOTTOM OF FOOTING OF HIGHER FOOTING TO SLOPE TO BOTTOM OF LOWER FOOTING AT SLOPE OF 1 VERTICAL TO 2 HORIZONTAL.
FIRE STOP @ 8'-0" AFF
BUILDER SHALL INVESTIGATE SITE DURING CLEARING AND EARTHWORK OPERATION FOR FILLED EXCAVATIONS OR BURIED STRUCTURES SUCH AS CESSPOOLS, CISTERNS, FOUNDATIONS, ETC. IF ANY SUCH ITEMS ARE FOUND, CONTRACTOR SHALL REMOVE SAID ITEMS IN A SAFE AND PROPER MANNER AND PREPARE THE SITE FOR ALL NEW WORK. WHERE REQUIRED FILL BENEATH THE BUILDING SHALL CONSIST OF CLEAN, INERT, WELL-GRADED GRANULAR FILL PLACED IN MAXIMUM 8 INCH LAYERS (LOOSE THICKNESS). FILL BENEATH FOOTINGS TO BE COMPACTED TO 98% OF THE MAXIMUM STANDARD DRY DENSITY (ASTM D-698). FILL UNDER SLAB TO BE COMPACTED TO 95% OF THE SAME STRENGTH. PLACEMENT AND COMP ACTION OF FILL TO BE SUPERVISED AND APPROVED IN WRITING BY A REGISTERED SOILS ENGINEER.
(2) #4 BAR
WHERE FILLING IS NECESSARY TO MEET THE REQUIRED SLAB ELEVATIONS. PROVIDE GRANULAR FILL COMPACTED TO A MIN. COMPACTED DENSITY OF 95%. INSTALL PERIMETER PERFORATED PIPE DRAINS AROUND BUILDING FOUNDATIONS AND COVER PIPE WITH 12 INCHES OF GRAVEL ALL AROUND. COORDINATE IF REQUIRED W/ OWNER.
8.
CONTRACTOR SHALL BE RESPONSIBLE FOR SUPPORT OF ALL TEMPORARY EMBANKMENTS AND EXCAVATIONS.
9.
CUT MISCELLANEOUS OPENINGS IN WALLS AND PARTITIONS FOR MECHANICAL AND ELECTRICAL TRADES. AS REQUIRED BY THE WORK OF SAID TRADES AND AS REQUIRED BY JOB CONDITIONS.
03.31.17
ISSUED FOR PERMIT
No.
Date
Issue or Revision
BASE TRIM
BASE TRIM
FLOOR
FLOOR 12'-3"
CIVIL DETAILS AND FOUNDATION PLAN
6'-8"
8/17/2017 10:17:37 AM
3"
7.
1
Drawing Title 4"
6.
8"
CONTRACTOR SHALL ANALYZE SOILS FOR CONSTRUCTION PURPOSES AND SHALL NOTIFY THE OWNER IMMEDIATELY AS TO ANY UNFORESEEN CONDITIONS.
DEPRESS SLAB -4"
EXTERIOR FINISH OVER TYVEK MOISTURE BARRIER OVER 5/8" TYPE X GYPSUM WALL BOARD OVER 1/2" THICK CDX PLYWOOD OVER 2X4 WOOD STUDS AT 16" O.C. WITH FIBERGLASS BATT INSULATION / VAPOR BARRIER AND 5/8" TYPE X GYPSUM WALL BOARD.
5/8" TYPE X SHEETROCK BRAND PAPER-FACED GYPSUM PANELS BOTH SIDES, FIRE CODE CORE 2X4 16" O.C. - PANELS FASTENED 7" O.C. WITH 17/8" FASTENERS - UL DES U305; STC 50.
P.T. 2" X 4" SILL
1'-8"
FIRE STOP @ 8'-0" AFF
4" CONCRETE SLAB 5.
3'-8"
CEILING
4'-4"
2.
FOOTINGS ARE DESIGNED TO BEAR ON SOIL HAVING A MINIMUM SAFE BEARING VALUE OF 2000 PSF. PRIOR TO CONSTRUCTION, SOIL BEARING VALUE SHALL BE CERTIFIED TO THE OWNER BY LETTER. CLEAN ALL POTHOLES AND FILL WITH 3500 PSI CONCRETE FORM SIDES OF FOOTING WITH WOOD WHERE REQUIRED.
6'-8"
1.
10.
BACK FILL SHALL CONSIST OF NON-EXPANSIVE, FREE-DRAINING, PREDOMINANTLY GRANULAR MATERIAL, FREE OF DEBRIS AND ORGANIC MATERIAL.
INTERIOR WALL - TYPE C 1 HR. UL#U305
1'-0"
EXTERIOR WALL - TYPE D 1 HR. UL#U309 Scale
A
THICKENED SLAB DETAIL SCALE: 1" = 1'-0"
11
PARTITION DETAILS SCALE: 1 1/2" = 1'-0"
USA Project No.
As indicated
13
FOUNDATION PLAN
Drawing Date
SCALE: 1/4" = 1'-0"
03.31.17
2016-063 Drawing No.
Drawn By
Checked By
DAH
APA
A-1
AT 3'-0" CANTILEVER PROVIDE TJI JOIST REINFORCEMENT IN ACCORDANCE WITH MANUFACTURER - TYP.
2 A-3
1 1/4" TIMBERSTRAND LSL CLOSURE - TYP.
18'-11"
6'-0"
8'-10" 5'-10"
5'-10"
4'-4"
9'-8"±
ROOF RIDGE VENT
2'-8"x6'-8"
5'-4"±
BATHROOM
CLOSET A
CLOSET
FIXTURE WITH EXHAUST FAN 2'-8"x6'-8" (100 CFM)
CENTER MIRROR (RECESSED MEDICINE CABINET) AND LIGHT FIXTURE WITH VANITY.
2'-8"x6'-8"
SD
3
BATHROOM #3
B
3
PAINTED WOOD SHELF @ 5'-6" A.F.F. W/ CONTINUOUS ALUMINUM CLOTHES ROD (BRACING AS REQUIRED) TYP.
3 A-3
58'-3" 58'-7"
4'-0"
A
2X12 RIDGE BOARD
REF.
4 A-3
11'-0" 3'-0"
SD
4'-4"
4 A-3
BASE AND OVERHEAD CABINETS TO BE SELECTED BY OWNER. PROVIDE SOFFIT ABOVE OVERHEAD CABINETS. 15'-8"
GFI
58'-7"
3'-3"
15'-8"
GFI
2'-8"x6'-8"
8'-4"
2'-4"
3 A-3
60'-7"
3
60'-7"
A
HOLD
BASE AND OVERHEAD CABINETS TO BE SELECTED BY OWNER. PROVIDE SOFFIT ABOVE OVERHEAD CABINETS.
SD
GFI
GFI
RANGE HOOD WITH FAN
3
3
3
3
DW
GFI
KITCHEN
3
SD
1 HR. F.R. SOLID CORE SELF CLOSING DOOR
3'-0"
3'-0"x6'-8"
4"
3'-0"
(2) 2"X4" POST
SD
CO2
1 HR. F.R. SOLID CORE SELF CLOSING DOOR 3'-0"x6'-8"
(2) 2"X4" POST
2X12 HIP
2X12 HIP
(2) 2"X4" POST. COORDINATE WITH STEEL COLUMN BELOW.
DATA
13'-3"
3
1'-0" OVERHANG 2"X10" RAFTERS 16" O.C.
UP UP 4'-6"
GAURDRAIL/ HANDRAIL SD
5'-1"
CLG HEIGHT=8'-0"
(2) 2"X4" POST
7 RISERS AT 7" 6 TREADS AT 10"
(2) 2"X4" POST. COORDINATE WITH STEEL COLUMN BELOW. 1 HR FIRE RATED WALL (UL #U425)
3
SECOND LEVEL
CO2
UP
DATA
GFI
3
STOVE DATA
22'-3"
22'-3"
8'-4"
(4) 3/4"x11 7/8" M.L. FLUSH
LIVING AREA
DATA
3'-6"
3
LIVING AREA FIRST LEVEL CLG HEIGHT=8'-0"
STOVE
13'-5"
B
INTERCOM B
INTERCOM
9 RISERS AT 7" 8 TREADS AT 10"
2X12 VALLEY
1 3/4 X 11 7/8 ML CONT.
3 WP
4" STEP MIN.
3'-0"
9 RISERS AT 7" 8 TREADS AT 10"
(2) LVL'S
2"X10" RAFTERS 16" O.C.
6'-7"
SLOPE
SLOPE
AI16116
Signature & License No.
° .00 135
1'-7"
1'-8"
2'-8"
11'-11"
2'-0" 3'-0" 7'-0"
ROOF OVER ENTRANCE
2'-0"
1 3/4 X 11 7/8 ML CONT. 11'-3"
SLOPE
3'-0"
PORCH LINE OF OVERHANG
2"X10" RAFTERS 16" O.C.
45. 00°
1'-1"
WP
FILLED VOID SOLID W/ CRUSHED STONE
4'-0"
3'-0"
3
1'-1"
1'-0"
3
3 1/4" X 5 1/2" X 3/8" STEEL ANGLE
(2) LVL'S
4 A-3
DATA
RANGE HOOD WITH FAN
11-7/8" tji/pro 250 @ 16" O.C. FLOOR JOISTS
9'-0"M.O.
A-4
KITCHEN
HIGH EFFICIENCY AND FLUELESS COMBUSTION AIR APPLIANCES EXHAUST VENTS MOUNTED BELOW CEILING.
USE 5/8" TYPE "X" SHEET ROCK UNDER STAIRS
1ST FLOOR ELECTRICAL METER
B
A
(2) 2"X4" POST
3'-0"
ELECTRICAL MAIN PANEL
3
4'-0"
SD
11-7/8" tji/pro 250 @ 16" O.C. FLOOR JOISTS
2"x10" RAFTERS 16" O.C.
2"x10" RAFTERS 16" O.C.
DOUBLE FRAME AT ATTIC ACCESS 2'-0" X 3'-0". PROVIDE FOLD OUT STAIR. PROVIDE 5/8" PLYWOOD FLOORING. SMOKE DETECTOR, PULL LIGHT SWITCH, AND GFI OUTLET.
2ND FL. H.W. H.F.
2'-8"x 6'-8"
SD
EXHAUST VENT (100 CFM)
2'-8"x6'-8"
4'-4"
65'-10" 5'-3"
C
FIXTURE WITH EXHAUST FAN (100 CFM)
8'-4"
2'-4"
8'-4" 7'-7"
GFI HVAC UNIT H.F.
11-7/8" tji/pro 250 @ 16" O.C. FLOOR JOISTS
GFI
A
BEDROOM #3
COORDINATE FLOOR DRAIN WITH FINISH FLOORING - TYP.
CENTER MIRROR (RECESSED MEDICINE CABINET) AND LIGHT FIXTURE WITH VANITY.
BATHROOM CLOSET
ELECTRIC SUB PANEL
CLOSET
9'-0"X7'-0" DOOR
BEDROOM #2
2'-8"x6'-8"
2'-8"x6'-8"
PAINTED WOOD SHELF @ 5'-6" A.F.F. W/ CONTINUOUS ALUMINUM CLOTHES ROD (BRACING AS REQUIRED) TYP.
UP
OVERHEAD GARAGE DOOR
LAUNDRY ROOM
ATTIC ACCESS
B SD
2X12 HIP
TYP.
A
NOTE: ONE OPENING FOR LAUNDRY EXHAUST
DRYER
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
HVAC UNIT
5'-8"±
B
CLOSET
2'-0"x6'-8"
3'-0"x6'-8" 1 HR. F.R. SOLID CORE SELF CLOSING DOOR
2'-6"x6'-8"
2'-6"x6'-8"
3
3 GFI
1ST FL. H.W. H.F.
FD SD CO2
4 NOTE:A-3 ONE OPENING FOR LAUNDRY EXHAUST
WASHER
LAUNDRY ROOM
(4) 3/4"x11 7/8" M.L. FLUSH
24'-4"
FINISHED FLOOR ELEVATION 0'-0"
DRYER
2'-10"
FD
3'-0"x6'-8" 1 HR. F.R. SOLID CORE SELF CLOSING DOOR
C
GFI
3 3
11-7/8" tji/pro 250 @ 16" O.C. FLOOR JOISTS
A
C
CO2
4" STEP MIN.
CLG HEIGHT=9'-6"
2ND FLOOR ELECTRICAL METER
WASHER
A-4
HOLD
A
3 A-3
GFI
SD
3'-0"
55'-3"
GFI
GFI
3'-0"x6'-8"
4" CONC. SLAB. SLOPED TO FRONT @ 1/8" PER FT.
1 HR. F.R. SOLID CORE SELF CLOSING DOOR
9'-1"
C
4" STEP MIN.
TYP.
(2) 2"X4" POST
DATA
NOTE: ALL FRAMING TO BE IN ACCORDANCE WITH TRUSSJOIST GUIDELINES
FINISH FLOOR @ -0'-4" PROVIDE 2 HR FIRE RATED CEILING UL#L511
A UP 3'-3"
CENTER MIRROR (RECESSED MEDICINE CABINET) AND LIGHT FIXTURE WITH VANITY.
1'-0" OVERHANG TYP.
GFI
DATA
GFI
(2) CAR GARAGE
8'-10"
3'-3" 4'-0" A-4
3 1/2" DIAMETER STEEL PIPE FILLED SOLID. COORDINATE WITH FOOTING.
FIXTURE WITH EXHAUST FAN (100 CFM)
BATHROOM
1 3/4"x9 1/2" M.L. FLUSH
BEDROOM #2 10'-0"±
SD
(2) 2"X4" POST
(2) 2"X4" POST
3
1 3/4"x11 7/8" M.L. FLUSH
A
B
ELECTRICAL PANEL
3'-0"
C
CENTER MIRROR (RECESSED MEDICINE CABINET) AND LIGHT FIXTURE WITH VANITY.
TYP.
3'-0"
SD
3
4'-4"
UP
GFI
SD
2X12 HIP
2'-8"x6'-8"
BATHROOM
3'-0"
9'-10"
3
3 1/2" DIAMETER STEEL PIPE FILLED SOLID. COORDINATE WITH FOOTING.
EXHAUST VENT (100 CFM) FIXTURE WITH EXHAUST FAN (100 CFM)
(2) 2"X4" POST
SPIRAL STAIRS 14 RISERS @ 9" 13 TREADS
5'-10"
1 3/4"x11 7/8" M.L. FLUSH
1 3/4"x11 7/8" M.L. FLUSH
11-7/8" tji/pro 250 @ 16" O.C. FLOOR JOISTS
CENTER MIRROR (RECESSED MEDICINE CABINET) AND LIGHT FIXTURE WITH VANITY.
BATHROOM
FINISH FLOOR @ 0'-0"
EXTERIOR LIGHT WITH MOTION DETECTION SYSTEM
B
usaarchitects.com
2"X10" RAFTERS 16" O.C.
B
2'-8"x6'-8"
FIXTURE WITH EXHAUST FAN (100 CFM)
CLG HEIGHT=9'-2"
1 HR FIRE RATED WALL (UL#U305)
1 HR FIRE CEILING (GA FILE NO. FC 5406) TYP.
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
PAINTED WOOD SHELF @ 5'-6" A.F.F. W/ CONTINUOUS ALUMINUM CLOTHES ROD (BRACING AS REQUIRED) TYP.
MASTER BEDROOM
DATA
MASTER BEDROOM
2'-8"x6'-8"
RECREATION ROOM
8'-4"
M.O.
3'-0"
DATA
EXHAUST FAN (100 CFM)
DATA
TYP.
B
UL#U905
B
5'-8"
WIC
3'-0"
B
11-7/8" tji/pro 250 @ 16" O.C. FLOOR JOISTS
WIC
4'-0"
3'-3"
STORAGE
3'-0"
3
4" STEP MIN.
3 A-3
11-7/8" tji/pro 250 @ 16" O.C. FLOOR JOISTS
PAINTED WOOD SHELF @ 5'-6" A.F.F. W/ CONTINUOUS ALUMINUM CLOTHES ROD (BRACING AS REQUIRED) TYP.
3'-0"
4'-0"
A/C
6'-3"
5'-8"
3'-0"
A/C
4'-0"
6'-0"
M.O.
3'-0"
4'-0"
M.O.
8"
3'-0"
SELF CLOSING HOLLOW METAL DOOR
3'-0"x6'-8"
5'-0"
3'-4"
3'-0"
6'-3"
6'-2"
18'-11"
6'-2"
9'-0"
REF.
3'-0"
3'-0"x6'-8" 1 HR. F.R. SOLID CORE SELF CLOSING DOOR
5'-7"
2'-8"x6'-8"
8"
CONCRETE PATIO
A-4
2 A-3
18'-11"
FROST HOSE BIB
A
2 A-3
1'-0" OVERHANG TYP.
2 A-3
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
2X8 RIDGE BOARD
11'-11"
NEW CONSTRUCTION AT
1
CONCRETE STEPS
GROUND FLOOR PLAN
UP
SCALE: 1/4" = 1'-0"
7'-0"
2
7'-0"
FIRST FLOOR PLAN
3
SCALE: 1/4" = 1'-0"
1 A-3
1 A-3
SECOND FLOOR PLAN
4
SCALE: 1/4" = 1'-0"
1 A-3
40 LT. GLENN ZAMORSKI DRIVE
ROOF PLAN SCALE: 1/4" = 1'-0"
FOR
1 A-3
14-22 HIGH STREET ASSOCIATES, LLC 40-42 LT. GLENN ZAMORSKI DRIVE, ELIZABETH, NJ 07201
CONCRETE / MASONRY: CARPENTRY: 13. 1.
ALL CONCRETE SHALL TEST 3,500 PSI AT 28 DAYS. THE SLUMP JUST PRIOR TO PLACING SHALL BE 4 INCHES WITHIN A TOLERANCE OF PLUS OR MINUS 1 INCH (MAX). NOTE: GARAGE SLABS, PORCHES, PATIO SLABS, AND CONCRETE WALKS SHALL TEST 3500 PSI AT 28 DAYS AND SHALL BE AIR ENTRAINED.
2.
ALL CONCRETE SHALL BE PLACED IN THE DRY. NO CONCRETE SHALL BE PLACED LATER THAN 90 MINUTES AFTER MIXING HAS BEGUN. DEPOSIT CONCRETE IN ITS FINAL POSITION WITHOUT SEGREGATION AND REHANDLING.
3.
REINFORCING STEEL SHALL BE NEW BILLET HIGH STRENGTH STEEL OF U.S.A. MANUFACTURE CONFORMING TO LATEST A.S.T.M. A-615 GRADE 60 FABRICATED IN ACCORDANCE WITH MANUAL OF STANDARD PRACTICE OF THEUNLESS C.R.S.I., OTHERWISE NOTED AND PLACING OF REINFORCING SHALL BE IN ACCORDANCE WITH A.C.I. BUILDING CODE. MANUAL OF STANDARD PRACTICE, AND THE MOST CURRENT APPLICABLE BUILDING CODE.
8/17/2017 10:17:39 AM
REINFORCING SHALL HAVE 3" COVER IN FOOTINGS, 2" COVER ON MAIN REINFORCEMENT IN STEM WALLS.
5.
REINFORCING BARS ARE CONTINUOUS UNLESS OTHERWISE NOTED. LAP MESH 12 INCHES AT SPLICES, LAP STEM WALL BARS 32 BAR DIAMETER AT SPLICES (MIN.).
6.
ALL MASONRY AND/OR CONCRETE WALLS BELOW GRADE SHALL BE DAMP-PROOFED (OR WATER PROOFED AS REQUIRED BY REGIONAL CONDITIONS.).
7.
ALL CONCRETE SHALL TEST 3,500 PSI AT 28 DAYS. THE SLUMP JUST PRIOR TO PLACING SHALL BE 4 INCHES WITHIN A TOLERANCE OF PLUS OR MINUS 1 INCH (MAX). NOTE: GARAGE SLABS, PORCHES, PATIO SLABS, AND CONCRETE WALKS SHALL TEST 3500 PSI AT 28 DAYS AND SHALL BE AIR ENTRAINED.
8.
ALL CONCRETE SHALL BE PLACED IN THE DRY. NO CONCRETE SHALL BE PLACED LATER THAN 90 MINUTES AFTER MIXING HAS BEGUN. DEPOSIT CONCRETE IN ITS FINAL POSITION WITHOUT SEGREGATION AND REHANDLING.
9.
REINFORCING STEEL SHALL BE NEW BILLET HIGH STRENGTH STEEL OF U.S.A. MANUFACTURE CONFORMING TO LATEST A.S.T.M. A-615 GRADE 60 FABRICATED IN ACCORDANCE WITH MANUAL OF STANDARD PRACTICE OF THE C.R.S.I., UNLESS OTHERWISE NOTED AND PLACING OF REINFORCING SHALL BE IN ACCORDANCE WITH A.C.I. BUILDING CODE. MANUAL OF STANDARD PRACTICE, AND THE MOST CURRENT APPLICABLE BUILDING CODE.
10.
REINFORCING SHALL HAVE 3" COVER IN FOOTINGS, 2" COVER ON MAIN REINFORCEMENT IN STEM WALLS.
11.
REINFORCING BARS ARE CONTINUOUS UNLESS OTHERWISE NOTED. LAP MESH 12 INCHES AT SPLICES, LAP STEM WALL BARS 32 BAR DIAMETER AT SPLICES (MIN.).
12.
ALL MASONRY AND/OR CONCRETE WALLS BELOW GRADE SHALL BE DAMP-PROOFED (OR WATER PROOFED AS REQUIRED BY REGIONAL CONDITIONS.).
1.
12. ALL LIGHT FRAMING AND STUDS, STRUCTURAL JOISTS AND PLANKS, ETC. SHALL CONFORM TO THE STANDARDS OF WOOD CONSTRUCTION SET FORTH BY THE WESTERN WOOD PRODUCTS ASSOC. (WWPA) AND ALL CONSTRUCTION PLYWOOD SHALL CONFORM TO THE NATIONAL BUREAU OF STANDARDS, PRODUCT STANDARD DIVISION.
FRAMING MEMBERS TO RECEIVE A FINISHED SURFACE-ALIGN THE FINISH SUBSURFACE TO VARY NOT MORE THAN 1/8" FROM THE PLANE OF SURFACES OF ADJACENT FURRING OR FRAMING MEMBERS.
13.
STRUCTURAL LUMBER, HORIZONTAL AND VERTICAL FRAMING, SHALL BE #2 DOUGLAS FIR OR APPROVED EQUAL CONSTRUCTION GRADE. MINIMUM FIBER STRESS OF 1,200 PSI, FREE OR WARP THAT CANNOT BE CORRECTED BY BRIDGING OR NAILING.
ALL EXTERIOR LUMBER SHALL BE EXTERIOR GRADE TYPE. DECAY AND TERMITE RESISTANT WITH PRESERVATIVE TREATMENTS. ALL WOOD IN CONTACT WITH CONCRETE, MASONRY, OR SOIL SHALL BE PRESSURE TREATED PER UBC STANDARD 25-12.
14.
ALL PLYWOOD SHALL BE IDENTIFIED BY GRADE MARK OF AN APPROVED INSPECTION AGENCY AND SHALL BE STANDARD C-D. WITH EXT. GLUE UNLESS OTHERWISE SPECIFIED ON DRAWINGS.
15.
ANCHOR ALL STUDS AT DOOR OPENINGS, ENDS AND CORNERS OF WALLS WHICH ARE SHEATHED WITH PLYWOOD AND/OR GYPSUM BOARD TO BOTTOM PLATE WITH TWO (2) SIMPSON A-35 FRAMING ANCHORS.
16.
BOLT HOLES SHALL BE DRILLED 1/16" LARGER THAN BOLT DIAMETER. PROVIDE WASHERS UNDER ALL BOLT HEADS AND NUT BEARING ON WOOD. HOLES SHALL BE PROPERLY ALIGNED. IN NO CASE SHALL MISALIGNMENT BE ALLOWED WITH PREVENTS PROPER BEARING OR ALIGNMENT OF MEMBERS. OVERSIZED HOLES SHALL NOT BE ALLOWED. BOLTS SHALL BE A307 BOLTS. NUTS SHALL BE TIGHTENED SNUG.
17.
ALL JOISTS SHALL HAVE A MINIMUM OF 1 1/2" BEARING AT SUPPORTS. LAPPING JOISTS SHALL HAVE 3" LAPS CENTERED OVER INTERIOR SUPPORTS.
18.
LEDGERS AND STUD WALL FOUNDATION SILL PLATES SHALL BE BOLTED TO CONCRETE WITH ANCHOR BOLTS OF SIZE AND MINIMUM SPACING AS SHOWN ON DRAWINGS. AT LEAST TWO BOLTS SHALL BE PROVIDED FOR EACH PIECE WITH ONE BOLT WITHIN 12" OF EACH END. PROVIDE TERMITE SHIELD AND SILL SEALER.
14.
TOP OF ALL EXTERIOR FOOTING SHALL BE MINIMUM 3'-0" BELOW EXTERIOR FINISH GRADE.
15.
ALL CMU TO BE LAID IN A FULL BED OF MORTAR.
16.
PROVIDE 1/2" BITUMINOUS FIBER EXPANSION JOINT AT THE INTERSECTION OF WALL AND SLAB.
17.
BASE AND TOP COURSE OF ALL MASONRY FOUNDATION WALLS SHALL BE FILLED SOLID WITH CONCRETE. PROVIDE SOLID BEARING UNDER ALL BEAMS AND GIRDERS.
3.
ALL MASONRY SHALL BE ASTM C-145 WITH A MINIMUM COMPRESSIVE STRENGTH OF 1,800 PSI AS SHOWN ON THE DRAWINGS, WHERE DIMENSIONS OF UNITS ARE NOT SHOWN, PROVIDE UNITS HAVING NOMINAL FACE DIMENSIONS OF 16" LONG BY 8" HIGH BY DEPTH SHOWN OR OTHERWISE REQUIRED, PROVIDE ACCESSORY SHAPES AS INDICATED OR REQUIRED.
4.
ALL TJI AND MICRO-LAM STRUCTURAL MEMBERS SHALL BE MANUFACTURED ERECTED AND BRACED IN ACCORDANCE TO THE LATEST SPECIFICATIONS AND/OR RECOMMENDATIONS OF THE "TRUSS JOIST CORPORATION".
19.
ALL INTERSECTING MASONRY WALLS SHALL BE BONDED TOGETHER WITH METAL ANCHORS AT 3'-4" O.C. VERTICALLY.
5.
20.
ALL FOUNDATION WALLS TO HAVE HORIZONTAL JOINT REINFORCING AT EVERY OTHER COURSE.
ROOFS SHALL BE BUILD TO WITHSTAND A 30 LB. LIVE LOAD AND BE CONSTRUCTED OF 2" X 10" RAFTERS AT 16" O.C. (UNLESS NOTED OTHERWISE) WITH 1/2" THICK APA RATED EXPOSURE 1 GROUP 1. PLYWOOD SHEATHING. PROVIDE COLLAR BEAMS AND HANGERS AS REQUIRED.
21.
ENVIRONMENTAL CONDITIONS - PROTECT MASONRY WORK FROM THE WEATHER AND OTHER PHYSICAL OR CLIMATIC CHANGES THAT INTERFERE WITH THE PROPER SETTING AND CURING. PROTECT WORK FROM THE RAPID EVAPORATION WATER FROM OF THE MORTAR UNTIL IT IS PROPERLY CURED. TAKE ALL NECESSARY PRECAUTIONS TO GUARD MASONRY WORK FROM CONSTRUCTION ABUSE. USE TARPAULINS AND/OR OTHER COVERING FOR THIS PURPOSE.
18. 4.
ALL EXTERIOR SIDES OF CONCRETE BLOCK FOUNDATION WALLS SHALL BE DAMP PROOFED WITH 1/2" CEMENT PLASTER FULL HEIGHT AND TWO (2) COATS OF WATER RESISTANT ASPHALT PITCH BELOW GRADE.
22.
DO NOT PLACE MASONRY UNITS WHEN AIR TEMPERATURE IS BELOW 48 DEGREES F.
23.
PROTECT FROM DIRECT EXPOSURE TO WIND AND SUN WHEN ERECTED IN AMBIENT AIR TEMPERATURE OF 99 DEGREES F. IN THE SHADE AND WITH RELATIVE HUMIDITY LESS THAN 50%.
24.
INSTALLATION - THE FOLLOWING CONDITIONS SHALL BE OBSERVED DURING THE INSTALLATION OF THE MASONRY SECTION OF THE CONSTRUCTION: A. HORIZONTAL AND VERTICAL ALIGNMENT OF THE FOUNDATION IS WITHIN 1" OF PLUMB. B. LAY ONLY DRY MASONRY UNITS. C. USE MASONRY SAWS TO CUT AND FIT MASONRY UNITS. D. SET UNITS PLUMB, TRUE-TO-LINE AND WITH LEVEL COURSES ACCURATELY SPACED. E. CLEAN THE TOP SURFACE OF FOUNDATIONS FREE FROM DIRT, DEBRIS, AND LAITANCE, AND EXPOSE THE AGGREGATE PRIOR TO START OF INSTALLATION OF 1ST COURSE. F. ACCURATELY FIT THE UNITS TO PLUMBING, DUCTS, OPENINGS, AND OTHER INTERFERENCES. NEATLY PATCHING ALL HOLES. G. KEEP THE WALLS CONTINUALLY CLEAN, PREVENTING GROUT AND MORTAR STAINS. NOTE: UNLESS NOTED OTHERWISE, PROVIDE RUNNING BOND WITH VERTICAL JOINTS LOCATED AT THE CENTER OF MASONRY UNITS IN THE ALTERNATE COURSE BELOW.(IF APPLICABLE).
2.
6.
7.
8.
9.
ALL MEMBERS SHALL BE PROPERLY BRACED, PLUMBED AND LEVEL. A SUFFICIENT NUMBER OF NAILS, SCREWS, AND BOLTS SHALL BE USED TO INSURE THE RIGIDITY OF THE CONSTRUCTION. USE GALVANIZED FOR EXTERIOR APPLICATIONS. NOTE: ALL NAILING TO BE IN ACCORDANCE WITH THE MOST CURRENT BUILDING CODES.
ATTIC FLOORS (CEILINGS) SHALL BE CONSTRUCTED OF 10x12 JOISTS AT 16" O.C. (UNLESS NOTED OTHERWISE) WITH 1/2" THICK PLYWOOD SUB FLOOR, (COORD. AMOUNT W/ OWNER) SECURED. PROVIDE APPROPRIATE BRIDGING OF 2" X 3", CROSSED, TWO (2) NAILS EACH AND SPACED MAXIMUM OF 6'-0" O.C. FLOORS SHALL BE BUILD TO WITHSTAND A 40/30 LB. LIVE LOAD AS REQUIRED BY FLOOR LOCATION, AND SHALL BE CONSTRUCTED OF 14 " TJI 560 FLOOR JOISTS (UNLESS NOTED OTHERWISE) WITH 3/4" THICK T&G PLYWOOD(GLUED AND NAILED) APA RATED STURD-I-FLOOR. DOUBLE ALL JOISTS UNDER BATHROOM TUBS . DOUBLE ALL JOISTS UNDER PARALLEL PARTITIONS. PROVIDE METAL JOIST HANGERS FOR ALL JOISTS ABUTTING HEADERS OR GIRDERS, "TECO", "SIMPSON" OR EQUAL. PROVIDE METAL STRAP BRIDGING AS RECOMMENDED BY BY TRUSS JOIST CORP. EXTERIOR WALLS SHALL BE BUILD TO WITHSTAND A 15 LB. WIND LOAD AND BE CONSTRUCTED OF 2" X 4" STUDS AT 16" O.C. (UNLESS NOTED OTHERWISE) WITH A SINGLE BOTTOM PLATE AND DOUBLE TOP PLATE WITH 1/2" THICK PLYWOOD C.D.X. SHEATHING AND ONE (1) LAYER OF 15 LB. ASPHALT SATURATED FELT PAPER. PROVIDE DOUBLE 2" X 4" POSTS AT ALL OPENINGS. INTERIOR BEARING PARTITIONS TO BE 2" X 4" STUDS AT 16" O.C. (UNLESS NOTED OTHERWISE) WITH SINGLE BOTTOM PLATE AND DOUBLE TOP PLATE. PROVIDE DOUBLE 2" X 4" POSTS AT ALL OPENINGS (UNLESS OTHERWISE NOTED).
10.
DOUBLE ALL TRIMMERS AND HEADERS AROUND OPENINGS IN FLOORS, CEILINGS, AND ROOF OPENINGS.
11.
PRODUCE JOINTS WHICH ARE TIGHT. TRUE AND WELL CONNECTED WITH MEMBERS ASSEMBLED IN ACCORDANCE WITH THE DRAWINGS.
19.
20.
21.
22.
ALL PLYWOOD WALL SHEATHING SHALL BE APPLIED AS FOLLOWS, CENTER VERTICAL JOINTS OVER STUDS AND CENTER HORIZONTAL JOINTS OVER 2" BLOCKING OR PLATE. NAIL TOP OF PANELS TO DOUBLE TOP PLATE, AND NAIL BOTTOM OF PANELS TO ANCHORED SILL PLATE. APPLY GYPSUM BOARD SO THAT END JOINTS OF ADJACENT COURSES DO NOT OCCUR OVER THE SAME STUD. PLYWOOD SUBFLOOR AND ROOF SHEATHING: INSTALL WITH FACE GRAIN AT RIGHT ANGLES TO SUPPORTS, CONTINUOUS OVER TWO OR MORE SPANS. ALLOW MINIMUM SPACE 1/16-INCH BETWEEN END JOINTS AND 1/8-INCH AT EDGE JOINTS FOR EXPANSION AND CONTRACTION OF PANELS. UNDERLAYMENT: LAY UNDERLAYMENT 3/8" A.P.A. RATED UNDERLAYMENT ON 36 ROSIN SIZED SHEATHING PAPER. FOR TILE FLOORS UNDERLAYMENT SHALL BE INSTALLED IN ACCORDANCE WITH CODE AS RECOMMENDED BY MANUFACTURER. BUILDING FELT: COVER SURFACES BEHIND SIDING, SHINGLES, AND WHERE INDICATED ON DRAWING WITH ASPHALT-SATURATED. NON PERFORATED, FELT WITHOUT WRINKLES OR BUCKLES. LAP HORIZONTAL JOINTS 3", 6" AT VERTICAL JOINTS, AND CARRY INTO OPENINGS. UP WALL 12" AND DOWN SIDES 6" MINIMUM. LOCATE END LAPS AT LEAST 18" FROM INTERNAL AND EXTERNAL CORNERS. PRIME BACK OF ALL EXTERIOR FASCIA BOARDS BEFORE INSTALLATION. FASCIA BOARD TO BE FREE OF KNOTS.
1
03.31.17
ISSUED FOR PERMIT
No.
Date
Issue or Revision
Drawing Title
FLOOR PLANS AND PARTITION TYPES Scale
USA Project No.
1/4" = 1'-0" Drawing Date
2016-063 Drawing No.
03.31.17 Drawn By
Checked By
DAH
APA
A-2
CONTINUOUS ROOF RIDGE VENT ROOF RIDGE VENT
ROOF RIDGE VENT
FIBERGLASS SHINGLES - TYP. SELF SEALING ASPHALT SHINGLE ROOF OVER #15 FELT PAPER
12
VENT
6 VENT
ATTIC +27' - 6"
1'-0"
4'-6"
BRICK VENEER - TYP. FIXED WINDOW
EGRESS 36" x 54"
5'-9"
EGRESS 36" x 54"
DOUBLE HUNG
STUCCO
EGRESS 36" x 54"
DOUBLE HUNG
usaarchitects.com
DOUBLE HUNG STUCCO
SECOND FLOOR +19' - 6"
4'-6"
8'-0"
FIBERGLASS SHINGLES - TYP. DECORATIVE METAL POSTS
2'-6"
EXTERIOR LIGHTS
EGRESS 36" x 54"
EGRESS 36" x 54"
EGRESS 36" x 54"
DOUBLE HUNG
DOUBLE HUNG
DOUBLE HUNG
INTERCOM - TYP.
O.C.
4" O.C. FIRST FLOOR +10' - 6"
2'-6"
3'-0"
4"
EXTERIOR LIGHT W/ MOTION DETECTION SYSTEM
FIRST FLOOR +10' - 6"
42" AFF METAL GUARDRAIL SYSTEM W/ 36" AFF CONTINUOUS METAL HANDRAIL SYSTEM
EXTERIOR LIGHTS CENTER METAL GAURDRAIL SYSTEM ON RAIL
4'-0"
7" RISER
STONE
DOUBLE HUNG APROX. GRADE LINE
DOUBLE HUNG CEMENT STUCCO FINISH
MIN.
3'-0"
4" PVC (SCHEDULE40) STORM SEWER CONNECTED TO STREET
GROUND FLOOR +0' - 0"
CONCRETE FOOTING/FOUNDATION
CONCRETE FOOTING/FOUNDATION
1
2" PRE-CAST CONCRETE TREAD
GROUND FLOOR +0' - 0"
4" PVC (SCHEDULE40) STORM SEWER CONNECTED TO STREET
METAL GATE TO MATCH HANDRAIL SYSTEM - TYP.
36" x 48"
36" x 48"
3'-0"
MIN. RAILING
3'-0"
PRE-CAST CONCRETE TREADS
4'-0"
OVERHEAD GARAGE DOOR - TYP.
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
VINYL SIDING
2'-6"
12
4'-6"
SECOND FLOOR +19' - 6"
AT TOP OF SHED, EXTEND BASE FLASHING 6" UP WALL AND 4" ONTO ROOF. COUNTER FLASHING AT LEAST 4" - TYP.
12
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
ATTIC +27' - 6"
2'-6"
1'-0"
FRONT ELEVATION
3
SCALE: 1/4" = 1'-0"
SIDE ELEVATION SCALE: 1/4" = 1'-0"
ROOF RIDGE VENT
ROOF RIDGE VENT 12 6
4" GUTTER & LEADER (TYP)
VENT
VENT
VENT
SELF SEALING ASPHALT SHINGLE ROOF OVER #15 FELT PAPER
VENT VENT
4" GUTTER & LEADER (TYP) ATTIC +27' - 6"
ATTIC +27' - 6"
4'-6"
1'-0"
EGRESS 36" X 54"
3'-0"
DOUBLE HUNG
STUCCO
SECOND FLOOR +19' - 6"
SECOND FLOOR +19' - 6" VINYL SIDING
VINYL SIDING
VENT
VENT
4'-6"
VENT
EGRESS 36" X 54"
3'-0"
DOUBLE HUNG
FIRST FLOOR +10' - 6" 4" EXTERIOR LIGHT
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
3'-0"
O.C. VENT
VENT
4'-0"
NEW CONSTRUCTION
3'-6"
3'-0"
CEMENT STUCCO FINISH
GROUND FLOOR +0' - 0" 4" PVC (SCHEDULE40) STORM SEWER CONNECTED TO STREET
2
CONCRETE FOOTING/FOUNDATION
40 LT. GLENN ZAMORSKI DRIVE
STONE APROX. GRADE LINE
CEMENT STUCCO FINISH
FOR
GROUND FLOOR +0' - 0"
4" PVC (SCHEDULE40) STORM SEWER CONNECTED TO STREET
4" PVC (SCHEDULE40) STORM SEWER CONNECTED TO STREET
4
SCALE: 1/4" = 1'-0"
40-42 LT. GLENN ZAMORSKI DRIVE, ELIZABETH, NJ 07201
SIDE ELEVATION SCALE: 1/4" = 1'-0"
ROOFING:
SHEET METAL FLASHING & TRIM:
SEALANTS & CAULKING:
DOORS:
1.
FIBERGLASS OR ASPHALT SHINGLES SHALL BE CLASS "C" (MINIMUM) TYPE OF THE UNDERWRITERS LABORATORIES, INC. OVER 15 LB. ASPHALT SATURATED FELT PAPER.
1.
PROVIDE FLASHING AND SHEET METAL AS REQUIRED TO PREVENT PENETRATION OF THE ELEMENTS THROUGH THE EXTERIOR SHELL OF THE BUILDING.
1.
1.
PROVIDE WOOD, METAL, OR SLIDING DOORS, AND FRAMES IN DIMENSIONS AND DESIGN SHOWN ON THE DRAWINGS.
2.
INSTALL SHINGLES TO PROVIDE A DOUBLE THICKNESS AT ALL POINTS.
2.
WHERE SHEET METAL IS REQUIRED AND NO MATERIAL OR GAUGE IS INDICATED IN THE DRAWINGS. PROVIDE THE HIGHEST GAUGE AND QUALITY.
SEAL AND CAULK JOINTS AS REQUIRED TO PROVIDE A POSITIVE BARRIER AGAINST THE PENETRATION OF AIR AND MOISTURE; EXTERIOR WALL JOINTS. JOINTS BETWEEN EQUIPMENT AND OTHER CONSTRUCTION, AND MISCELLANEOUS INTERIOR WALL CONDITIONS.
2.
PROVIDE PRIMERS. BACK-UP MATERIALS. BOND-PREVENTATIVE MATERIALS AND ANY OTHERS REQUIRED FOR A COMPLETE AND PROPER INSTALLATION.
2.
INTERIOR WOOD DOORS TO BE SOLID CORE, 1 3/8"THICK: ALL INTERIOR DOORS TO BE RAISED PANEL PINE BY "MORGAN" OR AS APPROVED BY OWNER. EXTERIOR DOOR TO BE INSULATED OR SOLID WOOD AS SELECTED BY OWNER.
3.
THOROUGHLY AND COMPLETELY MASK JOINTS WHERE THE APPEARANCE OF SEALANT ON ADJACENT SURFACES WOULD BE OBJECTIONABLE.
3.
FLUSH SOLID CORE WOOD DOORS (FOR GARAGE DOORS UNLESS NOTED OTHERWISE) 1-3/4" THICK.
4.
PROVIDE TWO (2) COMPONENT, RUBBER-BASED COMPOUND IN COLOR(S) AS SELECTED BY THE OWNER AND TOOL THE JOINTS TO A NEAT AND SMOOTH PROFILE.
4.
5.
CAULK AND/OR SEAL ALL EXPOSED EXTERIOR AND INTERIOR JOINTS ABOVE AND BELOW GRADE AND ALL THOSE INTERIOR AND EXTERIOR JOINTS AND APPENDAGES CONCEALED BY OTHER BUILDING MATERIALS, FLASHING, ETC. IN COLOR AS NEAR AS POSSIBLE TO MATCH ABUTTING NATURAL OR PAINTED FINISHES.
WOOD AND METAL DOORS SHALL BE ANCHORED FIRMLY INTO POSITION AND PLUMB WITHIN A TOLERANCE OF A IN 1.000. REHANG OR REPLACE AS REQUIRED DOORS WHICH ARE HINGEBOUND OR WHICH DO NOT SWING FREELY.
WINDOWS: 1.
PROVIDE WINDOWS AND FRAMES IN DIMENSIONS AND DESIGN SHOWN ON THE DRAWINGS.
MATERIAL SHALL BE PRODUCED BY SONNEBORN-CONTECK, TREMCO, PECORA. CHEMICAL CORP., DOW CORNING, OR GENERAL ELECTRIC.
2.
ALL WINDOWS SHALL BE CASEMENT OR DOUBLEHUNG SEE PLANS. MANUFACTURER TO BE SELECTED BY OWNER.
3.
FRAMES, PANELS, AND SASH TO BE WOOD CORE TREATED WITH A WATER REPELLENT PRESERVATIVE AND COVERED WITH RIGID VINYL (P.V.C.) COLOR AS SELECTED.
3.
STYLE AND COLOR SHALL BE AS SELECTED BY THE OWNER.
4.
VENTILATE ROOF INSULATION AS REQUIRED BY CODE AND AS SHOWN ON DRAWINGS.
5.
PROVIDE PERIMETER UNDERLAYMENT AT ALL EAVES, VALLEYS, AND ROOF PENETRATIONS BY OWENS CORNING "WEATHER LOCK" OR APPROVED EQUAL.
6.
ALL ROOF PENETRATIONS TO BE PROPERLY FLASHED AND MADE WATER TIGHT IN ACCORDANCE WITH MANUFACTURES STANDARDS.
FORM, FABRICATE, AND INSTALL SHEET METAL SO AS TO ADEQUATELY PROVIDE FOR EXPANSION AND CONTRACTION IN THE FINISHED WORK: A. FINISH WATERTIGHT AND WEATHERTIGHT AS REQUIRED. B. EMBED METALS IN CONNECTION WITH ROOFS IN A SOLID BED OF APPROVED SEALANT. C. WHENEVER POSSIBLE, SECURE METAL BY MEANS OF CLIPS OR CLEATS WITHOUT NAILING THROUGH THE METAL. D. SPACE NAILS, RIVETS, AND SCREWS NOT MORE THAN 8" APART AND USE LEAD WASHERS WHERE EXPOSED. E. FOR NAILING INTO WOOD USE BARBED ROOFING NAILS, 1-1/4" LONG LI GAUGE. F. FOR NAILING INTO CONCRETE USE DRILLED PLUG HOLES AND PLUGS.
INSULATION: 4. 1.
2.
PROVIDE THE FOLLOWING FIBERGLASS BATT INSULATION AS SHOWN ON THE DRAWINGS: A. UNDER ROOFS, IN SOFFITS, AND GARAGE USE 9" THICK FOIL-BACKED R-30 INSULATION. B. WITHIN ALL EXTERIOR STUD WALL CONSTRUCTION USE 3 1/2" THICK, FOIL BACKED. R-13 INSULATION. C. AT CATHEDRAL CEILING PROVIDE 8 1/4" R30C FOIL BACKED INSULATION. D. OVER UNHEATED SPACES PROVIDE 6" THICK FOIL BACKED R-19 INSULATION. FOR SLAB-ON-GRADE CONSTRUCTION USE 1 1/2" (MIN.) THICK RIGID BOARD INSULATION. EXTEND RIGID INSULATION A FULL 2'-0" INTO BUILDING AND 2'-0" BELOW FINISHED AT SLAB PERIMETER OF CONSTRUCTION.
ALL VENTS THROUGH ROOF SHALL HAVE CAP AND BASE FLASHING.
6.
GUTTERS, LEADERS & DRAINS: 1.
2.
14-22 HIGH STREET ASSOCIATES, LLC
CONCRETE FOOTING/FOUNDATION
REAR ELEVATION
3.
8/17/2017 10:17:42 AM
AT
MIN. RAILING
36" X 48"
APROX. GRADE LINE
AI16116
Signature & License No.
FIRST FLOOR +10' - 6"
PROVIDE PREFINISHED GALVANIZED ALUMINUM GUTTERS AND LEADERS AS REQUIRED IN BOOTS CONNECTED TO THE EXISTING DRAINAGE SYSTEM OR PITCHED AWAY FROM HOUSE TO DAY LIGHT. VERIFY IF EXISTING DRAINAGE SYSTEM MEETS LOCAL CODE. IF NOT, MODIFY AS REQUIRED TO MEET CODE. INSURE A WATERPROOF BASEMENT. PROVIDE CONTINUOUS FOUNDATION DRAINAGE AT EXTERIOR FOOTINGS PITCHED TO DRAIN TO SUMP PUMP OR TO DAYLIGHT.
FINISH HARDWARE: 1. 2.
PROVIDE ALL HARDWARE, TEMPLATES, ETC. AS REQUIRED FOR THE COMPLETE EXECUTION OF THE WORK.
1
03.31.17
ISSUED FOR PERMIT
No.
Date
Issue or Revision
Drawing Title
ELEVATIONS Scale
USA Project No.
1/4" = 1'-0"
4.
GLAZING TO BE HIGH PERFORMANCE. DOUBLE-PANE. INSULATING GLASS.
5.
PROVIDE GRILLE PATTERN (WHERE SELECTED). GLAZING BEADS, WEATHER-STRIPPING, FLASHING, INSECT SCREEN, HARDWARE, ETC. AS REQUIRED FOR COMPLETE INSTALLATION.
Drawing Date
EGRESS REQUIREMENTS ARE SATISFIED AS LATEST EDITION OF APPLICABLE BUILDING CODE.
Drawn By
Checked By
DAH
APA
HARDWARE SELECTIONS AS DIRECTED BY OWNER. 6.
2016-063 Drawing No.
03.31.17
A-3
INTERIOR FINISHES: 1.
ALL INTERIOR FINISHES TO BE MINIMUM CLASS III FLAME SPREAD AND SMOKE DEVELOPED RATING NOT TO EXCEED 450.
DRYWALL: 1. 2.
3. 4.
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
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
usaarchitects.com
WOOD FLOORS: 1. 2.
3.
4. 5.
6.
PROVIDE AND INSTALL ALL HARDWOOD FLOORING AS INDICATED ON THE DRAWINGS AND AS DIRECTED BY THE OWNER. USE MAPLE OR OAK WOOD FLOORING THAT IS ISI GRADE. PRACTICALLY FREE OF DEFECTS WITH ONLY MILD COLOR VARIATIONS OR EQUAL WOOD MATCHING BOTH IN APPEARANCE AND PERFORMANCE, COLOR, WIDTH, AND THICKNESS AS SELECTED BY THE OWNER. HARDWOOD FLOORING SHALL BE SET DIRECTLY OVER SUBFLOOR THAT IS DRY AND FREE OF ALL FOREIGN MATERIALS. SUBFLOORS SHALL BE TROWELED AND SANDED TO A SMOOTH EVE SURFACE WHERE THE MAXIMUM TOLERANCE FROM PLANE IS PLUS OR MINUS 1/8" IN ANY 10'-0" RADIUS. CONCRETE SUBFLOORS ON OR BELOW GRADE SHALL BE PROPERLY WATERPROOFED BENEATH THE SLAB AND AT THE PERIMETER. WOOD FLOORING SHALL NOT BE INSTALLED UNTIL ALL MASONRY, PLASTERING, TILE, MARBLE, AND TERRAZZO WORK IS COMPLETED AND ALL MECHANICAL TRADES AND PAINTERS ARE DONE IN AREAS TO RECEIVE FINISH WOOD FLOORING. MACHINE SAND WOOD FLOOR SMOOTH AND LEVEL USING COARSE, MEDIUM, AND FINE GRADES OF SANDPAPER AND FINISH WITH A CLEAR, PENETRATING, WATER-REPELLENT WOOD PRESERVATIVE.
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
1
WOOD FLOOR DETAIL
2
SCALE: 12" = 1'-0"
STAIR DETAIL
3
SCALE: 12" = 1'-0"
HIP ROOF SCALE: 12" = 1'-0"
CERAMIC TILE: 1. 2. 3. 4.
PROVIDE AND INSTALL ALL CERAMIC TILE TO FLOORS AND WALLS AS INDICATED ON THE DRAWINGS AND AS DIRECTED BY THE OWNER. ALL INSTALLATION SHALL BE ON THIN-SET GROUT. CERAMIC TILES SHALL BE 4" X 4" OR 2" X 2" IN COLORS SELECTED FROM MANUFACTURERS STANDARDS BY "AMERICAN OLEAN" OR APPROVED EQUAL. WORK SHALL COMPLY WITH THE RECOMMENDATIONS SET FORTH IN THE "HANDBOOK FOR CERAMIC TILE INSTALLATION" OF THE TILE COUNCIL OF AMERICA, LATEST EDITION.
3'-0" 36" MIN. ICE AND WATER EAVE FLASHING MEMBRANE AT ALL EAVES & VALLEYS
ROOF RAFTERS (PROVIDE 2"X6" COLLAR TIES AT 48" O.C.)
CARPET: 1. 2. 3.
12 6
ASPHALT SHINGLES ON 15# BUILDING FELT OVER 5/8" APA RATED EXPOSURE 1 PLYWOOD ROOF SHEATHING
PROVIDE AND INSTALL CARPETING TO FLOORS AS INDICATED ON THE DRAWINGS AND AS DIRECTED BY OWNER. CARPET TO MEET ASTM STANDARDS SET FORTH IN "FLAME SPREAD" AND "SMOKE DEVELOPED" TESTS. INSTALLATION METHOD SHALL BE JUTE BACK OR DIRECT GLUE DOWN, AS DIRECTED BY OWNER.
INSULATION BAFFLE VTR
VTR
VTR
ATTIC + 27' - 6"
EAVE FLASHING
8" MIN. ABOVE ROOF ROOF
PAINTING: 1.
2.
3. 4. 5. 6.
2"
PROVIDE SURFACE PREPARATION AND FINISH COATS ON ALL DOORS, WINDOWS, FRAMES, TRIMS, RAILINGS, DRYWALL PARTITIONS, SOFFITS, CEILINGS, FASCIAS, EXTERIOR SIDING, INTERIOR AND EXTERIOR BLOCK WORK AS DIRECTED BY THE OWNER. PAINT SCHEDULE: A. EXTERIOR CONCRETE - ONE (1) COAT OF ACRYLIC FILLER AND ONE (1) COAT OF ACRYLIC FINISH. B. EXTERIOR WOOD - ONE (1) COAT OF PRIMER AND TWO (2) COATS OF WEATHER PROTECTIVE FINISH. C. EXTERIOR METAL, GALVANIZED - TWO (2) COATS OF LINSEED ALKYD ENAMEL. D. METAL, FERROUS - ONE (1) COAT OF RUST PREVENTATIVE PRIMER AND TWO (2) COATS OF ALKYD ENAMEL. E. INTERIOR DRYWALL - ONE (1) COAT OF WHITE PRIMER AND TWO (2) COATS OF FLAT LATEX. F. INTERIOR WOOD - TWO (2) COATS OF SEMI-GLOSS LATEX. ALL SURFACES TO RECEIVE PAINT SHOULD BE FREE OF RUST, DIRT, GREASE, OIL, WAX, LOOSE PAINT, AND ALL OTHER FOREIGN MATTER. DO NOT PAINT IN DIRECT SUNLIGHT OR ANY EXTERIOR WORK IN FOGGY, DAMP WEATHER, DURING RAINY WEATHER OR WHEN THE TEMPERATURE IS BELOW 45 DEG. F. ALL COATS SHALL BE THOROUGHLY DRY AND HARD BEFORE APPLYING SUCCEEDING COATS. SUGGESTED MANUFACTURERS INCLUDE "BENJAMIN MOORE", "PITTSBURGH PAINTS", "GLIDDEN" OR "CON-LUX".
2" 4"
4"
4"
BATHROOM
1 1/2"
ALUMINUM GUTTER OVER ALUMINUM CLAD WOOD FASCIA BOARD KITCHEN
BATHROOM 1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1/2" PLYWOOD SUBFLOOR
2"X8" SUB FASCIA
1 1/2"
1 1/2"
1 1/2"
R-30 FIBERGLASS BATT. INSULATION
PERFORATED ALUMINUM OR VINYL SOFFIT 2X10 AT 16" O.C. CEILING JOISTS BLOCKING AS REQUIRED 5/8" GYPSUM CIELING
DW SECOND FLOOR 1 1/2"
1 1/2"
4"
4"
1 1/2" 2"
2"
2"
1 1/2"
BATHROOM
KITCHEN
BATHROOM 1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2" 11 7/8" tji/pro 250 AT 16" O.C. FLOOR JOISTS (TYP.)
FINISH CARPENTRY & MILWORK: 1. 2.
PROVIDE FINISH TRIMS, SOFFITS, AND FASCIAS AS INDICATED ON THE DRAWINGS OR AS DIRECTED BY THE OWNER. ALL INTERIOR DOOR AND WINDOW TRIMS AND ALL FLOOR BASE AS SELECTED BY OWNER.
FIRST FLOOR 1 1/2"
1 1/2"
1 1/2"
4"
4"
2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14.
ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICIAN AND SHALL BE IN ACCORDANCE WITH ALL CODES AND AGENCIES HAVING JURISDICTION. ELECTRICAL LAYOUT SHOWN IS DIAGRAMMATIC ONLY. ALL SWITCHES TO BE 3'-10" ABOVE FINISH FLOOR TO CENTER LINE OF SWITCH UNLESS OTHERWISE NOTED. ALL CONVENIENCE OUTLETS ARE 1'-0" ABOVE FINISH FLOOR TO CENTER LINE OF SWITCH UNLESS OTHERWISE NOTED. ALL INTERIOR WALL BRACKET FIXTURES TO BE AT 6'-6" ABOVE FINISH FLOOR TO CENTER LINE OF FIXTURE. (6'-10" AT BATHROOM MIRRORS). ALL EXTERIOR WALL BRACKET FIXTURES TO BE AT 6'-6" ABOVE FINISHED FLOOR TO CENTER LINE OF FIXTURE. ELECTRIC SERVICE CONDUCTORS AND EQUIPMENT SHALL BE OF A CAPACITY ADEQUATE TO SERVE THE CALCULATED LOAD AND ANY SPARE CIRCUITS PROVIDED FOR FUTURE USE. SMOKE DETECTORS SHALL BE U.L. APPROVED. THEY SHALL BE LOCATED ON CEILING WITH 12" CLEARANCE TO WALLS & WIRE TO SOUND ALARM W/ BATTERY BACK-UP. VERIFY LOCATION OF ALL RECEPTACLES FOR APPLIANCES WITH MANUFACTURER'S SPECIFICATIONS. PROVIDE AT LEAST TWO (2) 15 AMP CIRCUITS FOR LIGHTING AND GENERAL USE FOR FIRST 500 S.F. OF GROSS AREA AND ONE (1) 15 AMP FOR EACH ADDITIONAL 500 S.F. OF AREA. PROVIDE AT LEAST TWO (2) 20 AMP CIRCUITS TO SERVICE RECEPTACLES IN KITCHEN, BATHROOMS, AND LAUNDRY. PROVIDE INDIVIDUAL BRANCH CIRCUIT FOR ANY FIXED APPLIANCES OR EQUIPMENT RATED MORE THAN 1,400 WATTS. NO POINT ALONG FLOOR LINE MEASURED HORIZONTALLY SHALL BE MORE THAN 6'-0" FROM A RECEPTACLE OUTLET. ALL ELECTRICAL INSTALLATION SHALL MEET THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE. ALL MATERIAL AND EQUIPMENT SHALL BEAR THE LABEL OR APPROVAL OF THE UNDERWRITERS LABORATORIES. ELECTRICAL CONTRACTOR SHALL, BEFORE CONSTRUCTION, VERIFY SPACE REQUIRED FOR METER INSTALLATION AND SHALL NOTIFY GENERAL CONTRACTOR AND ARCHITECT OF ANY PROBLEM. GROUND FAULT INTERCEPTORS SHALL BE PROVIDED AT ALL BATHROOM OUTLETS AS PER SECTION 210-0 N.E.C. & KITCHENS. WITHIN 6'-0" OF SINK.
EXTERIOR RATED WALL-UL #U309. 1 HOUR FIRE RATED FLOOR/CIELING SYSTEM (TYP.) (GA FILE NO. FC 5406); BASE LAYER 5/8" TYPE X GYPSUM BOARD, FACE LAYER 5/8" TYPE X GYPSUM BOARD
2"
ELECTRICAL: 1.
SECOND FLOOR + 19' - 6"
DW
LAUNDRY ROOM
BATHROOM
1 1/2"
SOUND TESTED GLASS FIBER INSULATION (50 STC) (TYP.) 1 1/2"
1 1/2" (2) 2"X4"
C.O. WITH P-TRAP
C.O. WITH P-TRAP
2"
W
D GROUND FLOOR
2" 4"
1 1/2" 4"
1 1/2"
1 1/2"
EXTERIOR WALL - NOT FIRE RATED: 4" VINYL SIDING OVER TYVEX HOUSE WRAP BUILDING PAPER OVER 1/2" EXTERIOR SHEATHING NAILED TO 2"X4" STUDS AT 16" O.C. INNER LAYER 5/8" GYPSUM BOARD
CONNECT TO CITY SEWER AT STREET
2. 3. 4. 5.
6.
2. 3.
4.
8/17/2017 10:17:43 AM
5. 6.
AT
PROVIDE 2"X4" SQUASH BLOCKS/WEB STIFFENERS PER TRUSS JOIST SPECIFICATIONS (TYP.)
RISER DIAGRAM
40 LT. GLENN ZAMORSKI DRIVE FOR
SCALE: 1/4" = 1'-0" EIFS CAP
(2) 2X8 PRESSURE TREATED SILL WITH 1/2" 3/8 X 18" LONG ANCHOR BOLTS AT 8'0" O.C. (MIN. OF 2 PER BOARD LENGTH) FILL TOP TWO COURSES SOLID
ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBER AND SHALL BE IN ACCORDANCE WITH ALL CODES AND AGENCIES HAVING JURISDICTION. PLUMBING LAYOUT SHOWN IS DIAGRAMMATIC ONLY. WORK INCLUDES, BUT NOT LIMITED TO SOIL, WASTE, AND VENT PIPING INSTALLATION AND CONNECTION TO EXISTING SUPPLY AND SEWER. HOT AND COLD WATER PIPING, PLUMBING FIXTURES AND APPLIANCES AND GAS PIPING (WHERE APPLICABLE). ALL WATER PIPING BELOW CONCRETE FLOORS SHALL BE SOFT TEMPER, TYPE "K" COPPER TUBING, WATER PIPING ABOVE GROUND SHALL BE SOFT OR HARD COPPER TUBING. ALL PIPING INSIDE EXTERIOR WALLS SHALL BE INSULATED. ALL WASTE, SOIL, AND DRAINAGE PIPING SHALL BE P.V.C. SCHEDULE 40 PLASTIC PIPE. WHENEVER SUBSOIL DRAINAGE, FIXTURES, AND OTHER EQUIPMENT ARE SITUATED BELOW THE LEVEL OF INCOMING PUBLIC SEWER SERVICE USE SEWAGE EJECTORS, PUMPS AND OTHER RELATED EQUIPMENT AS REQUIRED TO EXPEL THE CONTENTS INTO THE PUBLIC SEWERS. (I.E. BACKFLOW PREVENTER) PROVIDE SHUT OFF VALVES TO ALL FIXTURES.
14-22 HIGH STREET ASSOCIATES, LLC
1 HR FIRE RATED R-19 FIBERGLASS BATT INSULATION (TYP.)
40-42 LT. GLENN ZAMORSKI DRIVE, ELIZABETH, NJ 07201
CONTINUOUS TERMITE SHIELD 2X4 STUDS 16" O.C. W/ 5/8" GYPSUM BOARD
EXTERIOR INSULATION AND FINISH SYSTEM
8" CMU WITH VERTICAL REINFORCEMENT EVERY OTHER COURSE
1/2" CEMENT PARGING
1/2" PREFORMED EXPANSION JOINT FILLER - SEAL ALL JOINTS WITH RADON SEALANT
12" CMU WALL - FILL SOLID WITH 3,000 PSI CONCRETE LADDER OR TRUSS TYPE REINFORCEMENT EVERY OTHER COURSE
MECHANICAL: 1.
FIRST FLOOR + 10' - 6"
1 1/4" TIMBERSTRAND LSL RIM BOARD
PLUMBING: 1.
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
WOOD FLOORING OVER 3/4" TOUNGE AND GROOVE PLYWOOD SUBFLOOR (GLUED AND NAILED) (TYP.)
NEW CONSTRUCTION
NOTE: PLUMBING RISER LAYOUT IS DIAGRAMMATIC AND TO BE INSTALLED IN ACCORDANCE WITH THE NATIONAL PLUMBING CODE BY A LICENSED PLUMBER
4
AI16116
Signature & License No.
R-13 FIBERGLASS BATT INSULATION
4" CONCRETE SLAB ON GRADE WITH 6X6 W-1.4X2-1.4 WWF ON 6 MIL VAPOR BARRIER OVER 4" CRUSHED STONE BASE (TYP.)
APPROXIMATE FINISH CONCRETE WALKWAY SLOPE AWAY FROM BUILDING (2%)
ALL WORK SHALL BE PERFORMED BY A LICENSED MECHANICAL CONTRACTOR AND SHALL BE IN ACCORDANCE WITH ALL CODES AND AGENCIES HAVING JURISDICTION. HEATING AND COOLING SYSTEMS SHALL BE DESIGNED AND SIZED BY THE CONTRACTOR TO MEET ALL REQUIREMENTS OF THE AREA OF THIS CONSTRUCTION. HEATING SYSTEM SHALL BE AUTOMATICALLY CONTROLLED WITH HUMIDITY ADJUSTMENTS. WALLS AND FLOORS BETWEEN TWO ZONES SHALL HAVE FIBERGLASS INSULATION. 3-1/2" THICK. EACH ZONE TO HAVE A THERMOSTAT CONTROL. CENTRAL AIR CONDITIONING (WHERE APPLICABLE) SHALL BE INSTALLED WITH COOLING COOLS ABOVE FURNACE AND CONDENSING UNIT OUTSIDE ON CONCRETE PAD ON GRADE - COORDINATE LOCATION WITH THE OWNER. SCREEN WITH FOLIAGE AS DIRECTED. INSTALL ALL DISTRIBUTION DUCTWORK, DIFFUSERS, AND RETURN GRILLES AS REQUIRED FOR A COMPLETE INSTALLATION. REFRIGERANT SECTION PIPING SHALL BE INSULATED TYPE "K" OR "L" HARD COPPER TUBING, SIZED IN ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS AND RECOMMENDATIONS. FITTINGS SHALL BE WROUGHT COPPER SOLDER TYPE. ALL BATHROOMS WITH NO WINDOWS SHALL HAVE AN EXHAUST FAN FOR 100 C.F.M AND ALL KITCHENS SHALL HAVE AN EXHAUST FAN OVER RANGE/OVEN.
FILTER FABRIC - 12" MINIMUM FROM FOOTING - OVER GRANULAR DRAINAGE MATERIAL
GROUND FLOOR + 0' - 0"
2" RIGID INSULATION 24" VERTICAL AND HORIZONTAL AT PERIMETERS (TYP.)
1
03.31.17
ISSUED FOR PERMIT
No.
Date
Issue or Revision
Drawing Title
DETAILS, RISER DIAGRAM, AND WALL SECTION
CONTINUOUS MASONRY CANT
PROVIDE GROUNDING CLAMP AND STRAP FOR ELECTRICAL SYSTEM TO REINFORCEMENT BARS IN FOUNDATION
A
WALL SECTION SCALE: 1/2" = 1'-0"
12" x 24" CONTINUOUS CONCRETE FOOTING WITH (3) #4 BARS CONTINUOUS Scale
USA Project No.
As indicated Drawing Date
2016-063 Drawing No.
03.31.17 Drawn By
Checked By
DAH
APA
A-4
PROJECT LOCATION: 2 CHARLOTTE HILL DRIVE BERNARDSVILLE, SOMERSET COUNTY NEW JERSEY, 07924
PORCH ROOF FOR
DRAWING LIST
MR. & MRS. DAMELIO
ARCHITECTURAL A-1 A-2
AT
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
GENERAL NOTES & SITE PLAN NEW PORCH ELEVATION, FLOOR PLANS, SECTIONS, & DETAILS
DAMELIO RESIDENCE
usaarchitects.com Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
2 CHARLOTTE HILL DRIVE BERNADRDSVILLE, SOMERSET, NJ 07924 GENERAL NOTES
FOUNDATION NOTES
1.
THE CONTRACTOR SHALL EXAMINE AND BECOME FAMILIAR WITH ALL CONTRACT DOCUMENTS IN THEIR ENTIRETY. SURVEY THE PROJECT AND BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND SCOPE OF WORK.
1.
2.
ALL WORK/ CONSTRUCTION SHALL BE DONE IN STRICT ACCORDANCE WITH ALL FEDERAL, STATE & LOCAL CODES, ORDINANCES, RULES & REGULATIONS. WHERE SUCH CODES, RULES & REGULATIONS ARE AT VARIANCE WITH THE PLANS & NOTES: SAID CODES, RULES & REGULATIONS, ETC. SHALL TAKE PRECEDENCE OVER THE PLANS & NOTES.
FOOTINGS ARE DESIGNED TO BEAR ON SOIL HAVING A MINIMUM SAFE BEARING VALUE OF 2000 PSF. PRIOR TO CONSTRUCTION, SOIL BEARING VALUE SHALL BE CERTIFIED TO THE OWNER BY LETTER. CLEAN ALL POTHOLES AND FILL WITH 3500 PSI CONCRETE FORM SIDES OF FOOTING WITH WOOD WHERE REQUIRED.
2.
BOTTOMS OF ALL FOOTINGS ARE 3'-6" BELOW EXISTING GRADE UNLESS OTHERWISE NOTED. TOPS OF FOOTINGS ARE AT SAME ELEVATION AT JUNCTIONS OF WALL FOOTING AND COLUMN FOOTING. WALL FOOTING REINFORCEMENT TO RUN CONTINUOUS THROUGH COLUMN FOOTING. BOTTOM OF FOOTING OF HIGHER FOOTING TO SLOPE TO BOTTOM OF LOWER FOOTING AT SLOPE OF 1 VERTICAL TO 2 HORIZONTAL.
3.
BUILDER SHALL INVESTIGATE SITE DURING CLEARING AND EARTHWORK OPERATION FOR FILLED EXCAVATIONS OR BURIED STRUCTURES SUCH AS CESSPOOLS, CISTERNS, FOUNDATIONS, ETC. IF ANY SUCH ITEMS ARE FOUND, CONTRACTOR SHALL REMOVE SAID ITEMS IN A SAFE AND PROPER MANNER AND PREPARE THE SITE FOR ALL NEW WORK.
4.
WHERE REQUIRED FILL BENEATH THE BUILDING SHALL CONSIST OF CLEAN, INERT, WELL-GRADED GRANULAR FILL PLACED IN MAXIMUM 8 INCH LAYERS (LOOSE THICKNESS). FILL BENEATH FOOTINGS TO BE COMPACTED TO 98% OF THE MAXIMUM STANDARD DRY DENSITY (ASTM D-698). FILL UNDER SLAB TO BE COMPACTED TO 95% OF THE SAME STRENGTH. PLACEMENT AND COMP ACTION OF FILL TO BE SUPERVISED AND APPROVED IN WRITING BY A REGISTERED SOILS ENGINEER.
5.
CONTRACTOR SHALL ANALYZE SOILS FOR CONSTRUCTION PURPOSES AND SHALL NOTIFY THE OWNER IMMEDIATELY AS TO ANY UNFORESEEN CONDITIONS.
USA ARCHITECTS PLANNERS + INTERIOR DESIGNERS, P.A.
6.
WHERE FILLING IS NECESSARY TO MEET THE REQUIRED SLAB ELEVATIONS. PROVIDE GRANULAR FILL COMPACTED TO A MIN. COMPACTED DENSITY OF 95%.
20 North Doughty Avenue Somerville, NJ 08876
7.
CONTRACTOR SHALL BE RESPONSIBLE FOR SUPPORT OF ALL TEMPORARY EMBANKMENTS AND EXCAVATIONS.
8.
CUT MISCELLANEOUS OPENINGS IN WALLS AND PARTITIONS FOR MECHANICAL AND ELECTRICAL TRADES. AS REQUIRED BY THE WORK OF SAID TRADES AND AS REQUIRED BY JOB CONDITIONS.
9.
BACK FILL SHALL CONSIST OF NON-EXPANSIVE, FREE-DRAINING, PREDOMINANTLY GRANULAR MATERIAL, FREE OF DEBRIS AND ORGANIC MATERIAL.
3.
THE CONTRACTOR IS RESPONSIBLE FOR COMPLIANCE WITH ALL APPLICABLE BUILDING CODES & REGULATIONS AND FOR OBTAINING ALL NECESSARY AND REQUIRED INSPECTIONS, APPROVALS AND PERMITS, NECESSARY TO PERFORM ALL WORK AND SERVICES HEREIN NOTED OR INDICATED ON THE DRAWINGS.
4.
THESE DRAWINGS DO NOT CONTAIN COMPLETE SPECIFICATIONS, DETAILS, AND INFORMATION REQUIRED FOR THE INTERIOR FINISHES OF THE PROJECT. ADDITIONAL INFORMATION SHALL BE OBTAINED FROM THE OWNER.
5.
UNLESS SHOWN ON THESE DRAWINGS, ALL MECHANICAL WORK, SUCH AS, BUT NOT LIMITED TO ELECTRICAL, PLUMBING, HEATING, AIR CONDITIONING, VENTILATING, SITE WORK ETC., ARE TO BE ESTABLISHED AND DESIGNED BY OTHER THAN ARCHITECT.
6.
ALL MANUFACTURED MATERIALS, COMPONENTS, FASTENERS, ASSEMBLIES, ETC. SHALL BE HANDLED AND INSTALLED IN ACCORDANCE WITH MANUFACTURES INSTRUCTIONS AND RECOMMENDATIONS. WHERE SPECIFIC MANUFACTURED PRODUCTS ARE CALLED FOR, THE CONTRACTOR MUST NOTIFY THE OWNER OF ANY SUBSTITUTIONS BEFORE THEY ARE MADE.
7.
THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES REQUIRED FOR SAFE EXECUTION AND COMPLETION OF WORK AND FOR INITIATING, MAINTAINING AND SUPERVISING ALL SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK.
8.
ANY ERRORS, OMISSIONS OR INCONSISTENCIES ON THESE DRAWINGS OR ANY VARIATIONS OR AMBIGUITIES BETWEEN THESE DRAWINGS AND ACTUAL SITE AND CONSTRUCTION CONDITIONS AND/ OR REQUIREMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER IN WRITING AND RESOLVED AND DOCUMENTED IN WRITING BEFORE CONTINUING WITH THE WORK IN QUESTION.
9.
IN THE EVENT A DISCREPANCY IS FOUND IN THE CONTRACT DOCUMENTS, THE OWNER SHALL BE NOTIFIED IMMEDIATELY.
10.
ASSUME MINIMUM FIBER STRESS 1200 PSI FOR ALL STRUCTURAL BEAMS AND HEADERS UNLESS OTHERWISE NOTED.
11.
REMOVE RUBBISH FROM PREMISES AS OFTEN AS NECESSARY OR DIRECTED.
CONCRETE & MASONRY NOTES
12.
ALL WORK AND EQUIPMENT SHALL BE CLEANED TO THE SATISFACTION OF THE OWNER BEFORE TURNING SAME OVER TO OWNER.
1.
ALL CONCRETE SHALL TEST 3,500 PSI AT 28 DAYS. THE SLUMP JUST PRIOR TO PLACING SHALL BE 4 INCHES WITHIN A TOLERANCE OF PLUS OR MINUS 1 INCH (MAX). NOTE: GARAGE SLABS, PORCHES, PATIO SLABS, AND CONCRETE WALKS SHALL TEST 3500 PSI AT 28 DAYS AND SHALL BE AIR ENTRAINED.
13.
CAULKING, SEALANT AND EXTERIOR JOINTS AROUND WINDOWS AND DOOR FRAMES, BETWEEN WALL AND FOUNDATION, BETWEEN WALL PANELS AT PENETRATIONS, OR UTILITY SERVICES THROUGH WALLS, FLOORS AND ROOFS, AND ALL OTHER OPENINGS IN THE EXTERIOR ENVELOPE SHALL BE SEALED WITH AN APPROVED MANNER.
2.
ALL CONCRETE SHALL BE PLACED IN THE DRY. NO CONCRETE SHALL BE PLACED LATER THAN 90 MINUTES AFTER MIXING HAS BEGUN. DEPOSIT CONCRETE IN ITS FINAL POSITION WITHOUT SEGREGATION AND REHANDLING.
ALL FRAMING TO BE IN CONFORMANCE WITH THE NATIONAL FOREST PRODUCTS 'MANUAL FOR HOUSE FRAMING' AND THE LATEST EDITION OF THE MOST CURRENT BUILDING CODE.
3.
REINFORCING STEEL SHALL BE NEW BILLET HIGH STRENGTH STEEL OF U.S.A. MANUFACTURE CONFORMING TO LATEST A.S.T.M. A-615 GRADE 60 FABRICATED IN ACCORDANCE WITH MANUAL OF STANDARD PRACTICE OF THE C.R.S.I., UNLESS OTHERWISE NOTED AND PLACING OF REINFORCING SHALL BE IN ACCORDANCE WITH A.C.I. BUILDING CODE. MANUAL OF STANDARD PRACTICE, AND THE MOST CURRENT APPLICABLE BUILDING CODE.
4.
REINFORCING SHALL HAVE 3" COVER IN FOOTINGS, 2" COVER ON MAIN REINFORCEMENT IN STEM WALLS.
5.
REINFORCING BARS ARE CONTINUOUS UNLESS OTHERWISE NOTED. LAP MESH 12 INCHES AT SPLICES, LAP STEM WALL BARS 32 BAR DIAMETER AT SPLICES (MIN.).
14.
GENERAL STRUCTURAL NOTES DESIGN, FABRICATION, AND CONSTRUCTION OF WOOD FRAMING SHALL CONFORM WITH THE FOLLOWING CODES AND STANDARDS. 1.
SPLICE DOUBLE SOLE PLATES DIRECTLY OVER STUD. STAGGER SPLICE OF EACH PLATE.
2.
ALL JOISTS AND RAFTERS SHALL BE RIGIDLY BRIDGED AT INTERVALS NOT EXCEEDING 8'-0”.
6.
ALL MASONRY AND/OR CONCRETE WALLS BELOW GRADE SHALL BE DAMP-PROOFED (OR WATER PROOFED AS REQUIRED BY REGIONAL CONDITIONS.).
3.
GUYS AND OTHER BRACING REQUIRED TO PROVIDE LATERAL STABILITY TO WOOD FRAMES SHALL BE ADEQUATELY SIZED AND ANCHORED. THIS BRACING SHALL REMAIN UNTIL PERMANENT BRACING ELEMENTS AND ATTACHED CONSTRUCTION IS INSTALLED.
7.
ALL EXTERIOR SIDES OF CONCRETE BLOCK FOUNDATION WALLS SHALL BE DAMP PROOFED WITH 1/2" CEMENT PLASTER FULL HEIGHT AND TWO (2) COATS OF WATER RESISTANT ASPHALT PITCH BELOW GRADE.
THE WOOD STRUCTURE IS A NON-SELF-SUPPORTING FRAME AND IS DEPENDENT UPON DIAPHRAGM ACTION OF THE PANELS AND ATTACHMENT TO THE SHEAR WALLS FOR STABILITY AND FOR RESISTANCE TO WIND AND SEISMIC FORCES. PROVIDE ALL TEMPORARY SUPPORTS REQUIRED FOR STABILITY AND FOR RESISTANCE TO WIND AND SEISMIC FORCES UNTIL THESE ELEMENTS ARE COMPLETE AND ARE CAPABLE OF PROVIDING THIS SUPPORT.
8.
TOP OF ALL EXTERIOR FOOTING SHALL BE MINIMUM 3'-0" BELOW EXTERIOR FINISH GRADE.
9.
ALL CMU TO BE LAID IN A FULL BED OF MORTAR.
ALL BOLTS AND LAG BOLTS SHALL BE FITTED WITH GALVANIZED, MALLEABLE IRON OR STEEL PLATE WASHERS.
10.
PROVIDE 1/2" BITUMINOUS FIBER EXPANSION JOINT AT THE INTERSECTION OF WALL AND SLAB.
11.
BASE AND TOP COURSE OF ALL MASONRY FOUNDATION WALLS SHALL BE FILLED SOLID WITH CONCRETE. PROVIDE SOLID BEARING UNDER ALL BEAMS AND GIRDERS.
4.
5. 6.
ALL WOOD MEMBERS EXPOSED TO EXTERIOR TO BE PRESSURE TREATED.
7.
PROVIDE FASTENERS, ANCHORS AND CONNECTORS WITH ADEQUATE CORROSION PROTECTION, WHERE IN CONTACT WITH TREATED WOOD. PROVIDE MINIMUM ZMAX COATING WHERE SIMPSON CONNECTORS ARE USED IN CONTACT WITH TREATED WOOD.
8.
BASE DESIGN VALUES FOR ROOF/FLOOR JOIST FRAMING: DOUG-FIR NO. 1 AND NO.2 (FB = 850 PSI, FV = 180 PSI, E = 1,600,000 PSI) MINIMUM.
9.
BASE DESIGN VALUE FOR WOOD STUDS AND BRACING: DOUG FIR STUD MINIMUM COMPRESSION PARALLEL TO GRAIN FC =850 PSI, MINIMUM TENSION PARALLEL TO GRAIN, FT = 400 PSI, MINIMUM COMPRESSION PERPENDICULAR TO GRAIN, 625 PSI.
10.
ALL PLYWOOD SHEATHING SHALL COMPLY WITH APA. PLYWOOD SHALL MEET C-D INTERIOR APA, STRUCTURAL I AND II C-D INTERIOR APA, OR STRUCTURAL I AND II C-C EXTERIOR APA. ATTACHMENT TO BE IN ACCORDANCE WITH IBC REQUIREMENTS. ALL PLYWOOD TO HAVE EXTERIOR GLUE.
11.
ROOF SHEATHING SHALL BE APA RATED SHEATHING, 19/32” THICK, 42/20.
12.
SCHEDULE WHEN JOINING TWO OR MORE FRAMING MEMBERS.
13.
HANGER CONNECTIONS FOR JOISTS, BEAMS, TRUSSES, AND MANUFACTURED WOOD FRAMING SHALL BE STRONG-TIE CONNECTORS BY SIMPSON (TRUS JOIST MACMILLAN).
14.
SEE INTERNATIONAL BUILDING CODE FOR MINIMUM BRACING AND FASTENING REQUIREMENTS.
15.
PROVIDE ADDITIONAL JOIST UNDER PARALLEL NON-LOADING BEARING PARTITIONS THAT RUN MORE THAN 1/3 THE SPAN OF THE JOIST. ANSI/TPI 1-1995 "DESIGN SPECIFICATIONS FOR METAL PLATE-CONNECTED WOOD TRUSS CONSTRUCTION AND COMMENTARY", TRUSS PLATE INSTITUTE. BUILDING COMPONENT SAFETY INFORMATION BCSI 1-03 “GUIDE TO GOOD PRACTICE FOR HANDLING, INSTALLING & BRACING OF METAL PLATE CONNECTED WOOD TRUSSES,” WOOD TRUSS COUNCIL OF AMERICA AND TRUSS PLATE INSTITUTE.
DEMOLITION NOTES THE CONTRACTOR SHALL NOT CONSIDER THESE DEMOLITION AND ALTERATION NOTES TO BE ALL INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND ASSESS EACH SPACE, AND TO FULFILL THE INTENT OF THE WORK INDICATED BY THE CONTRACT DOCUMENTS. VERIFY ALL DIMENSIONS WITHIN THE CONTRACT LIMITS. BRING DEVIATIONS FROM THE CONTRACT DOCUMENTS NECESSITATED BY FIELD CONDITIONS TO THE ATTENTION OF THE ARCHITECT. THE EXTENT OF DEMOLITION AND REMOVAL WORK IS SHOWN ON THE DRAWINGS AND INCLUDES, BUT IS NOT NECESSARILY LIMITED TO THE FOLLOWING:
1/31/2018 1:52:35 PM
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
1.
CONTRACTOR SHALL INSTALL PLASTIC DUST BARRIERS DURING DEMOLITION AND CONSTRUCTION TO PROTECT THE OWNER FROM DUST AND FUMES.
2.
CONTRACTOR SHALL BE RESPONSIBLE FOR DAILY CLEANUP OF CONSTRUCTION DEBRIS.
3.
FOR REQUIRED REMOVAL AND TERMINATION OF UTILITIES. COORDINATE ALL UTILITY SHUT-OFF W/OWNER PRIOR TO BEGINNING WORK.
4.
PRIOR TO THE START OF DEMOLITION, CONTRACTOR SHALL COORDINATE SEQUENCE OF WORK AND SCHEDULES FOR ALL WORK WITH OWNER.
5.
CONTRACTOR SHALL PROVIDE PROTECTION TO EXISTING FINISHES TO REMAIN.
6.
PROTECT, PATCH AND REPAIR ALL ADJACENT SURFACES WHICH ARE AFFECTED BY THE DEMOLITION OR REMOVAL OF ACCESSORIES TO THEIR ORIGINAL FORM AND FINISH (UNLESS OTHERWISE NOTED).
7.
EXISTING ROOF TO REMAIN WHICH IS AFFECTED BY DEMOLITION, SHALL BE FINISHED TO MATCH NEW ADJACENT ROOF. PATCH AND REPAIR EXISTING ROOF TO MATCH NEW ROOF.
8.
REMOVE PROJECTIONS, HANGERS, BOLTS, SCREWS AND NAILS FROM EXISTING SURFACES. FILL ALL GAPS AND PREPARE SURFACES TO RECEIVE NEW WORK AND FINISH.
9.
REMOVE ALL EXISTING WALL OR MOUNTED ITEMS EITHER AS REQUIRED FOR REPAIR AND PAINTING OF ADJACENT WALL SURFACES, OR AS DESIGNATED BY OWNER TO BE REMOVED AND DISPOSED OF. THESE SHALL INCLUDE, BUT NOT BE LIMITED TO ALL EXISTING ELECTRICAL DEVICES SUCH AS SWITCHES, RECEPTACLES, THERMOSTATS, CONDUITS, ETC., AS WELL AS, INTERCOM/LOUDSPEAKERS AND MISCELLANEOUS SIGNAGE, ETC. PATCH AND REPAIR ALL DAMAGED WALL, FLOOR AND CEILING SURFACES AS REQUIRED.
12.
ALL MASONRY SHALL BE ASTM C-145 WITH A MINIMUM COMPRESSIVE STRENGTH OF 1,800 PSI AS SHOWN ON THE DRAWINGS, WHERE DIMENSIONS OF UNITS ARE NOT SHOWN, PROVIDE UNITS HAVING NOMINAL FACE DIMENSIONS OF 16" LONG BY 8" HIGH BY DEPTH SHOWN OR OTHERWISE REQUIRED, PROVIDE ACCESSORY SHAPES AS INDICATED OR REQUIRED.
13.
ALL INTERSECTING MASONRY WALLS SHALL BE BONDED TOGETHER WITH METAL ANCHORS AT 3'-4" O.C. VERTICALLY.
14.
ALL FOUNDATION WALLS TO HAVE HORIZONTAL JOINT REINFORCING AT EVERY OTHER COURSE.
15.
ENVIRONMENTAL CONDITIONS - PROTECT MASONRY WORK FROM THE WEATHER AND OTHER PHYSICAL OR CLIMATIC CHANGES THAT INTERFERE WITH THE PROPER SETTING AND CURING. PROTECT WORK FROM THE RAPID EVAPORATION OF WATER FROM THE MORTAR UNTIL IT IS PROPERLY CURED. TAKE ALL NECESSARY PRECAUTIONS TO GUARD MASONRY WORK FROM CONSTRUCTION ABUSE. USE TARPAULINS AND/OR OTHER COVERING FOR THIS PURPOSE.
16.
DO NOT PLACE MASONRY UNITS WHEN AIR TEMPERATURE IS BELOW 48 DEGREES F.
17.
PROTECT FROM DIRECT EXPOSURE TO WIND AND SUN WHEN ERECTED IN AMBIENT AIR TEMPERATURE OF 99 DEGREES F. IN THE SHADE AND WITH RELATIVE HUMIDITY LESS THAN 50%.
18.
INSTALLATION - THE FOLLOWING CONDITIONS SHALL BE OBSERVED DURING THE INSTALLATION OF THE MASONRY SECTION OF THE CONSTRUCTION: A. B. C. D. E. F. G.
HORIZONTAL AND VERTICAL ALIGNMENT OF THE FOUNDATION IS WITHIN 1" OF PLUMB. LAY ONLY DRY MASONRY UNITS. USE MASONRY SAWS TO CUT AND FIT MASONRY UNITS. SET UNITS PLUMB, TRUE-TO-LINE AND WITH LEVEL COURSES ACCURATELY SPACED. CLEAN THE TOP SURFACE OF FOUNDATIONS FREE FROM DIRT, DEBRIS, AND LAITANCE, AND EXPOSE THE AGGREGATE PRIOR TO START OF INSTALLATION OF 1ST COURSE. ACCURATELY FIT THE UNITS TO PLUMBING, DUCTS, OPENINGS, AND OTHER INTERFERENCES.NEATLY PATCHING ALL HOLES. KEEP THE WALLS CONTINUALLY CLEAN, PREVENTING GROUT AND MORTAR STAINS. NOTE: UNLESS NOTED OTHERWISE, PROVIDE RUNNING BOND WITH VERTICAL JOINTS LOCATED AT THE CENTER OF
DESIGN TEAM ARCHITECT
PHONE #908-722-2300
AREA OF WORK
AI16116
Signature & License No.
1
EXISTING SITE PLAN SCALE: N.T.S.
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
PORCH ROOF
PROJECT INFORMATION FOR
PROJECT LOCATION:
2 CHARLOTTE HILL DRIVE BERNARDSVILLE, SOMERSET COUNTY NEW JERSEY 07924
MR. & MRS. DAMELIO
BUILDING CODE INFORMATION
AT
ALL WORK SHALL COMPLY WITH ALL GOVERNING CODES, REGULATIONS AND ORDINANCES, ETC. COMPLIANCE WITH THE FOLLOWING STANDARDS (MOST RECENT VERSION) IS REQUIRED.
DAMELIO RESIDENCE 2 CHARLOTTE HILL DRIVE BERNADRDSVILLE, SOMERSET, NJ 07924
INTERNATIONAL RESIDENTIAL CODE NEW JERSEY 2015 USE GROUP:
"R-2" - RESIDENTIAL (ONE AND TWO FAMILY)
CONSTRUCTION TYPE:
V-A (COMBUSTIBLE)
SPRINKLERED:
NO
AREA OF NEW ROOF:
150 SF
DESIGN LOADS:
ROOF: LL: 25# /SF DL: 10# /SF TL: 35# /SF
1 No.
01.19.18
PERMIT DRAWINGS
Date
Issue or Revision
Drawing Title
GENERAL NOTES & SITE PLAN Scale
USA Project No.
As indicated Drawing Date
2017-096 Drawing No.
01.19.18 Drawn By
Checked By
JS
ApA
A-1
EXISTING BRICK COUNTER FLASHING 3/4" PLYWOOD TEMPALTE CUTOUT
ICE & WATER SHIELD EXISTING ROOF STRUCTURE TO REMAIN. PRESSURE TREATED 2X8
20 N. Doughty Avenue Somerville, NJ 08876 t 908.722.2300 f 908.722.7201
EXISTING GUTTER SYSTEM TO REMAIN. 5--A-2
EXISTING STRUCTURE
(2) 1/2" x 6" LAG SCREWS FASTENED TO EXISTING STRUCTURE @ 16" O.C. CURVED PORCH ROOF STRUCTURE WITH ATAS METAL ROOFING ARCH PANEL SYSTEM. COORDINATE WITH MANUFACTURER DETAILS.
SIMPSON CLIP JOIST
EXISTING RAILINGS TO REMAIN.
usaarchitects.com
1X12 ARCHITECTURAL FINISH PIECE
GUTTER SYSTEM (TO MATCH EXISTING STYLE & COLOR)
Paul R. Swartz, AIA Armand T. Christopher Jr., AIA Mark A. Coan, AIA Peter C. Campisano, AIA
Andrew P. Adornato, AIA Daniel J. Fortunato, AIA Mitch Miller, AIA, FCSI, CCS Susan M. DeHart, AIA
EXISTING DOOR, SIDELIGHTS, AND WINDOW ASSEMBLY TO REMAIN.
EXISTING BRICK STAIRS TO REMAIN.
COLUMN TO SUPPORT ROOF STRUCTURE. (TO MATCH EXISTING)
EXISTING GROUND FLOOR PLAN
1
SCALE: 1/4" = 1'-0"
EXISTING WINDOWS TO REMAIN.
6
NEW PORCH ROOF CONNECTION DETAIL SCALE: 3" = 1'-0"
9 A-2 EXISTING MASONRY FRONT STEPS TO REMAIN.
(2) 2x10 WOOD TOP PLATES 8 1/2"x11" GLULAM WOOD BEAM
DRY-BLOCK PIER SYSTEM
2x12
APPROX. GRADE
FASICA BOARD CONCRETE PIER, SEE DETAIL 8/A-2. GUTTER SYSTEM (TO MATCH EXISTING COLOR & STYLE)
CONCRETE FOOTING, SEE DETAIL 8/A-2.
WOOD BLOCKING 8 A-2
7'-0"
4
PROPOSED FRONT ELEVATION SCALE: 1/4" = 1'-0"
--EQ
EQ 12'-10" AI16116
Signature & License No.
8 A-2
7
A-2 -
PORCH ROOF
M AT C
11'-2"
NEW METAL ROOF ARC PANELS SYSTEM, COORDINATE WITH MANUFACTURER DETAILS.
---
H
EX ± IS R TI 5' NG -6 " AR V. I.F C H . W IN D O W
COLUMN CAP, LAP AND NAIL TYP.
PRESSURE TREATED 2X8 JOISTS TO SUPPORT NEW ROOF STRUCTURE SPACED 12" O.C. (TYP.)
1 x 12 FASCIA BOARD (TO MATCH EXISTING STYLE & COLOR)
METAL FLASHING, PER MANUFACTURER
DRY BLOCK CAP W/ 1 1/2" REVEAL
COORDINATE WITH MANUFACTURER DETAILS FOR VAULTED TRIM FOR THE ROOF CONNECTION AT THE CORNERS OF EXISTING BUILDING FOR PROPER INSTALLATION OF METAL ROOF PANELS.
DRY BLOCK PIER SYSTEM, (TO MATCH EXISTING)
COLUMN TOP TRIM (MATCH EXISTING STYLE)
2 CHARLOTTE HILL DRIVE BERNADRDSVILLE, SOMERSET, NJ 07924
12"x12" CONCRETE PIER (APPROX.) GRADE (2) #5 BENT REBAR
DECORATIVE COLUMN COVER
PRESSURE TREATED 8 x 8 COLUMN WITH TIE-IN AT TOP AND BOTTOM.
#4 @ 24 TRANSVERSE (4) #5 BARS E.W. @ 8" O.C. 12" x 30" x 30" CONCRETE FOOTER
14'-10" 1'-0"
1/31/2018 1:52:39 PM
ROOF PLAN SCALE: 1/4" = 1'-0"
COLUMN BASE TRIM (MATCH EXISTING STYLE).
4" LAYER OF CRUSHED STONE COMPACTED TO 95" SPD
5-
3
1
2'-6"
5
NEW PORCH ROOF SECTION SCALE: 1/2" = 1'-0"
8
PIER FOUNDATION DETAIL SCALE: 1/2" = 1'-0"
No.
01.19.18
PERMIT DRAWINGS
Date
Issue or Revision
Drawing Title
NEW PORCH ELEVATION, FLOOR PLANS, SECTIONS, & DETAILS
EARTH BELOW TO BE COMPACTED TO 95" SPD FOR NEW STRUCTURAL FOOTING.
A-2 ---
DAMELIO RESIDENCE
STEEL REBAR FOR SUPPORT OF DRYBLOCK SYSTEM.
GUTTER SYSTEM OVER NEW WOOD FASCIA BOARDS (TO MATCH EXISTING STYLE & COLOR) 7 A-2
AT
WELL-GRADED GRANULAR WALL ROCK FILL
PRESSURE TREATED WOOD STRUCTURAL COLUMN AND BEAM SYSTEM TO SUPPORT ROOF, SEE DETAIL 7/A-2.
RA DI US
FOR
MR. & MRS. DAMELIO
11"
SCALE: 1/4" = 1'-0"
METAL ARC PANELS ROOFING SYSTEM BY ATAS INTERNATIONAL OR APPROVED EQUAL.
9'-3"
GROUND FLOOR PLAN 5--A-2
9'-2"
This Document is the property and copyright of USA Architects for the specified project and shall not be used or reproduced without authorization.
SCALE: 1 1/2" = 1'-0"
10'-2"
2
GLULAM ROOF SUPPORT DETAIL
3'-9" 3'-6"
5-
9
STRUCTURAL COLUMN DETAIL SCALE: 1/2" = 1'-0"
Scale
USA Project No.
As indicated Drawing Date
2017-096 Drawing No.
01.19.18 Drawn By
Checked By
JS
ApA
A-2