Project Name: NZ Commercial Subproject Name: NZ Commercial Complex
Project Details
Project Name
NZ Commercial
Number of Distinct Buildings
1
Number of EDGE Subproject(s) associated
1
Total Project Floor Area (m²) 20,082
Project Owner Name abc
Project Owner Email kamatjanhvi14@gmail.com
Project Owner Phone Mobile 91 - 9930254416
Share with Investor(s) or Bank(s)?
NZ Commercial Complex Associated Subproject(s)
Subproject Details
Subproject
Subproject Multiplier for the Project 1 Certification Stage Preliminary
Building Orientation
*** These parameters will be used to estimate building dimensions. If the exact details of the dimensions and orientation are available, then complete the User Entry fields in the Building Lengths section. The orientation of the building will have a direct effect on energy consumption.
Building Systems
Does the building design include an AC system? Yes
Does the building design include a space heating system? No
Key Assumptions for the Base Case
Results
ENERGY SAVINGS
* Virtual energy is the amount of energy that will be required based on the assumption that the retail will eventually install air conditioning or heating.
Project Name: NZ Commercial
Subproject Name: NZ Commercial Complex
Energy Efficiency Measures 34.42%
RTE01 Reduced Window to Wall Ratio - WWR of 58.27%
North 80
South 80 East 0
West 80
RTE02 Reflective Paint/Tiles for Roof - Solar Reflectivity (albedo) of 0.8
SR 0.8
RTE03 Reflective Paint for External Walls - Solar Reflectivity (albedo) of 0.8
SR 0.8
RTE04 External Shading Devices - Annual Average Shading Factor (AASF) of 0.8
AASF 0.8
RTE05 Insulation of Roof : U-value of 0.4
W/m².K 0.4
RTE06 Insulation of External Walls : U-value of 0.3
W/m².K 0.3
RTE07 Low-E Coated Glass : U-value of 1.5 W/m².K and SHGC of 0.5
W/m².K 1.5 SHGC 0.5
RTE08 Natural Ventilation with Operable Windows for Corridors, Atrium, and Common Areas
RTET1
RTE09 Air Economizers During Favorable Outdoor Conditions
RTE10 Variable Refrigerant Flow (VRF) Cooling System - COP of 3.5
RTE11 Air Conditioning with Air Cooled Screw Chiller - COP of 3.63
RTE12 Air Conditioning with Water Cooled Chiller - COP of 4.7 COP 4.7
RTE13 Ground Source Heat Pump - COP of 4.1
RTE14 Absorption Chiller Powered by Waste Heat - COP of 0.7
RTE15 Recovery of Waste Heat from the Generator for Space Heating
RTE16 Variable Speed Drives on the Fans of Cooling Towers
RTE17 Variable Frequency Drives in AHUs
RTE18 Variable Speed Drives Pumps
RTE19 Sensible Heat Recovery from Exhaust Air - Efficiency of 60%
RTE20 CO2 Sensor/Demand-Controlled Ventilation for Fresh Air Intake
Created By: janhvi kamat
Downloaded By: janhvi kamat
EDGE Assessment: v2.1.5
Downloaded date & time: 2020-05-14 05:56 34.42% | 76.39% | 44.95%
RTE21 High-Efficiency Condensing Boiler for Space Heating - Efficiency of 90%
RTET2
RTE22 High-Efficiency Boiler for Water Heating - Efficiency of 90%
RTE23 Energy-Saving Light Bulbs - Sales Area
RTE24 Energy-Saving Light Bulbs - Corridors and Common Areas
RTE25 Energy-Saving Light Bulbs - External Spaces
RTE26 Occupancy Sensors in Bathrooms
RTE27 Higher Efficiency Refrigerated Cases
RTE28 Solar Hot Water Collectors - 50% of Hot Water Demand
RTE29 Solar Photovoltaics - 40% of Total Energy Use
% of Annual Electricity Use 40 Capacity (kWp) 426.0
RTE30 Skylight(s) to Provide Daylight to 50% of Top Floor Area
RTE31 Other Renewable Energy for Electricity Generation
RTE32 Offsite Renewable Energy Procurement - Equal to 100% of total Operational CO2
RTE33 Carbon Offset - 100% of Total CO₂
RTET3
RTET4
File Number: 20043010086394
Project Number: 1000632334
Project Name: NZ Commercial
Subproject Name: NZ Commercial Complex
WATER SAVINGS
EDGE Assessment: v2.1.5
Downloaded date & time: 2020-05-14 05:56 34.42% | 76.39% | 44.95%
Water Efficiency Measures 76.39% Meets EDGE Water Standard
RTW01 Dual Flush for Water Closets in All Bathrooms - 4 L/first flush and 2 L/second flush 1st - L/flush 4 2nd - L/flush 2
RTW02 Water-Efficient Urinals in All Bathrooms - 1 L/flush L/flush 1
RTW03 Aerators and Auto Shut-off Faucets in All Bathrooms - 4 L/min L/min 4
RTW04 Water-Efficient Kitchen Faucets - 2 L/min
L/min 2
RTW05 Water-Efficient Dishwashers - 2 L/Rack
RTW06 Pre-Rinse Valve for Rinsing Operation - 6 L/min
RTW07 Water-Efficient Landscaping - 1 L/m²/day
L/m²/day 1
RTW08 Condensate Water Recovery
RTW09 Rainwater Harvesting System - 70% of Roof Area Used for Rainwater Collection
% of Roof Area Used70
RTW10 Grey Water Treatment and Recycling System
RTW11 Black Water Treatment and Recycling System
Created By: janhvi kamat
File Number: 20043010086394
Project Number: 1000632334 Downloaded By: janhvi kamat
Embodied Energy Savings
Project Name: NZ Commercial
Subproject Name: NZ Commercial Complex
EDGE Certification Checklist
Retail Preliminary NZ Commercial Complex
Energy Measures
RTE01 Reduced Window to Wall Ratio
Preliminary Audit Requirements
EDGE Assessment: v2.1.5
Downloaded date & time: 2020-05-14 05:56 34.42% | 76.39% | 44.95%
Calculation of “Glazing Area” and “Gross Exterior Wall Area” for each façade of the building and the average building area weighted WWR using the WWR calculator
All façade eleva o drawi s showi la i dime sio s a d e eral ildi dimensions.
RTE02 Reflective Paint/Tiles for Roof Building design drawings showing the roof material and roof finish.
Roof specification with solar reflectivity of the roof surface indicated.
Bill of quantities with the roof finish clearly marked.
RTE03 Reflective Paint for External Walls Building design drawings showing the wall finish.
Wall specification with solar reflectivity of the wall’s surface indicated.
Bill of quantities with the wall finish clearly marked.
RTE04 External Shading Devices
All façade eleva o drawi s hi hli h the provisio of hori o tal a d ver cal shading devices.
Window details clearly showing the depth of the shading device and the calculation of the proportion.
If vertical and horizontal shading are not provided on all windows, the design team will need to provide the output from the solar shading design software.
RTE05
Insulation of Roof
A roof construction detail drawing showing the type and thickness of insulation material. Ideally the roof detail drawing should be annotated with the U Value of the roof.
Calculations of U value either using the formula or U value calculators.
Manufacturer’s data sheet of specified insulation material for the roof.
RTE06 Insulation of External Walls External walls construction detail drawing showing the type and thickness of the insulation material. Ideally the external walls detail drawing should be annotated with the U Value of the external walls.
Calculations of U value either using the formula or U value calculators.
Manufacturer’s data sheet of specified insulation material for the external walls.
RTE07 Low-E Coated Glass
Manufacturer’s data sheets showing the seasonal average U Value for the glazing (including losses through the glass and frame) and the solar heat gain coefficient (SHGC) of the glass.
A list of different types of window included in the design (window schedule).
RTE08 Natural Ventilation: Corridors, Atrium and Common Areas
Typical floor plans for every floor showing corridors ’ layouts and the location of openings.
20043010086394
Project Number: 1000632334 Downloaded By: janhvi kamat
EDGE Assessment: v2.1.5
Project Name: NZ Commercial
Subproject Name: NZ Commercial Complex
RTE08 Natural Ventilation: Corridors, Atrium and Common Areas
RTE09 Air Economizers During Favorable Outdoor Conditions
RTE12 Air Conditioning with Water Cooled Chiller
RTE15 Recovery of Waste Heat from the Generator for Space Heating
RTE16 Variable Speed Drives on the Fans of Cooling Towers
RTE17
Variable Speed Drives in AHU
RTE18 Variable Speed Drives Pumps
Downloaded date & time: 2020-05-14 05:56 34.42% | 76.39% | 44.95%
Typical sections showing the floor to ceiling height for every floor.
Calculations showing the depth to ceiling height ratio and minimum area of opening for each typical space.
Manufacturer’s data sheet for the air economizer specified.
System schematics showing the location, brand and model of the air economizer.
Mechanical drawings with air conditioning schematics for all floors.
Manufacturer’s data sheets for the Water cooled chiller system specifying COP information.
For systems including more than one chiller unit, the design team must provide the tonweighted average COP calculation.
Mechanical layout drawings/schematic showing the location of the external and internal units.
Manufacturer’s data sheets for electric generator specifying hours of operation and coverage of the demand.
Manufacturer’s data sheets for the recovery technology used.
Mechanical and electrical layout drawings showing the location of the generator, the recovery technology and the output for space heating system.
Calculation to demonstrate that generators capacity to deliver 100% of peak energy and that waste heat covers % of the demand for space heating as calculated in EDGE software.
Mechanical and electrical layout drawings highlighting the use of VSD in the fans of the cooling towers.
Manufacturer’s data sheets for the air conditioning with Water cooled chiller and cooling towers, showing the specification of VSDs in the fans of the cooling towers.
For systems including more than one cooling tower, the design team must ensure that all fans are provided with VSDs.
Mechanical and electrical layout drawings showing the whole HVAC system and highlighting the use of VSD in AHU fans.
Manufacturer’s data sheets VSD for fans.
Mechanical and electrical layout drawings showing the whole HVAC system and highlighting the use of VSD pumps.
Manufacturer’s data sheets VSD pumps.
RTE19 Sensible Heat Recovery from Exhaust Air
Manufacturer’s data sheets for sensible heat recovery device specifying Temperature Transfer Efficiency.
Mechanical and electrical layout drawings showing the location of the heat recovery technology and indicating % of total air passing through the heat recovery system.
In case, manufacture’ data do not specify TTE, calculation to demonstrate efficiency should be undertaken.
Created By: janhvi kamat
Downloaded By: janhvi kamat
File Number: 20043010086394
Project Number: 1000632334
Project Name: NZ Commercial
Subproject Name: NZ Commercial Complex
RTE20 CO2 Sensor / Demand-Controlled Ventilation for Fresh Air Intake
RTE23 Energy Saving Light Bulbs- Sales Area
RTE24 Energy Saving Light Bulbs- Corridors and Common Areas
EDGE Assessment: v2.1.5
Downloaded date & time: 2020-05-14 05:56 34.42% | 76.39% | 44.95%
HVAC layout drawings showing the location of the CO2 sensors including the mounting height.
Specification of the sensors from manufacturer.
Lighting schedule listing type and number of bulbs specified.
Electrical layout drawings showing the location and type of all installed bulbs.
Lighting schedule listing type and number of bulbs specified.
Electrical layout drawings showing the location and type of all installed bulbs.
RTE25 Energy Saving Light Bulbs- External Areas Lighting schedule listing type and number of bulbs specified.
Electrical layout drawings showing the location and type of all installed bulbs.
RTE26 Occupancy Sensors in Bathrooms
Electrical layout drawings showing the location of the occupancy sensors.
Specification of the sensors from manufacturer.
RTE27 Higher Efficiency Refrigerated Cases List of the refrigerated cases, including quantity, energy use, and proof of Certification by Energy Star, EU Energy Efficiency Labelling Scheme, Energy Technology Product List (ETL), or equivalent.
Specifications from the manufactured detailing energy use.
RTE29 Solar Photovoltaics
Manufacturer’s data sheet for the panels specified with information on Wp per square meter.
Calculation showing the proposed solar photovoltaics will deliver sufficient electricity to achieve the claimed proportion of total demand, and at least as much as the area estimated by EDGE. If not clear justification should be provided.
The roof plan and/or other drawings showing the location, orientation, and angle of the panels.
Water Measures
RTW01 Dual Flush for Water Closets in Bathrooms
Preliminary Audit Requirements
Plumbing drawings/specifications including make, model, and flush volumes of water closet(s).
Manufacturer’s data sheet for water closet(s) with information on the flush volume of the main and reduced flushes.
RTW02 Water-Efficient Urinals in all Bathrooms
Plumbing drawings/specifications including make, model, and flush volume of the urinal (s).
Manufacturer’s data sheet for urinal(s) with information on the flush volume.
RTW03 Aerators for Faucets/ Auto Shut-Off Faucet
Plumbing drawings/specifications including make, model, auto shut-off mechanism and flow rate of the washbasin faucet(s)
Manufacturer’s data sheet for faucet(s)/flow aerator(s) confirming the flow rate at 3 bar.
RTW04
Water-Efficient Faucets for Kitchen Sinks
Created By: janhvi kamat
Plumbing drawings/specifications including make, model, and flow rate of kitchen(s) faucet(s) or flow restrictor(s).
File Number: 20043010086394
Project Name: NZ Commercial
Subproject Name: NZ Commercial Complex
RTW04 Water-Efficient Faucets for Kitchen Sinks
EDGE Assessment: v2.1.5
Downloaded date & time: 2020-05-14 05:56
| 44.95%
Manufacturer’s data sheet for faucet(s)/flow restrictor(s) confirming the flow rate at 3 bar.
RTW05 Water-Efficient Dishwashers Summary list of the dishwasher(s) to be installed in the building, including quantity and proof of maximum water use.
Specifications from manufacture detailing water use.
RTW06 Pre-rinse Valve for Rinsing Operation Plumbing drawings/specifications including make, model, and flow rate of the pre-rinse valve(s).
Manufacturer’s data sheet for pre-rinse valve(s) confirming the flow rate at 3 bar.
RTW07 Water Efficient Landscaping
A landscape plan showing the zoning for plants and the type of plants use highlighting native species and the irrigation system selected.
Description of the water requirements use in landscaped areas
Calculation of the landscape water consumption in litres/m²/day.
RTW08 Condensate Water Recovery
Calculations for condensate water recovery specifying cooling load and water collected in litres per day.
Hydraulic layout drawings showing the location of the recovery, collection and reuse technology.
RTW09 Rainwater Harvesting System
A system schematic showing the collection area, feed pipes, and storage tank.
Sizing calculations for the rainwater harvesting system.
RTW10 Grey Water Treatment and Recycling System
A system schematic showing the plumbing layout including the dual plumbing lines.
Manufacturer’s data sheet of the specified grey water treatment plant.
Calculations for: 1.Designed capacity of the grey water treatment system (m3/day) 2.Quantity of grey water available daily to recycle (litres/day) 3.Efficiency of the grey water system to produce treated water (litres/day) 4.Water balance chart.
RTW11 Black Water Treatment and Recycling System
A system schematic showing the plumbing layout including the dual plumbing lines.
Manufacturer’s data sheet of the specified black water treatment plant.
Calculations for: 1. Designed capacity of the black water treatment system (m3/day) 2. Quantity of black water available daily to recycle (litres/day) 3. Efficiency of the black water system to produce treated water (litres/day) 4. Water balance chart
Material Measures
RTM01 Floor Slabs
Preliminary Audit Requirements
Floor sections showing build-up of the floor; or
Manufacturer’s data sheet for specified building material if applicable; or
Bill of quantities with the floor slab specification clearly highlighted.
RTM02 Roof Construction
Created By: janhvi kamat
A section drawing of roof showing the materials and thicknesses; or
Manufacturer’s data sheet for specified building material; or
File Number: 20043010086394
Project Number: 1000632334 Downloaded By: janhvi kamat
Project Name: NZ Commercial
Subproject Name: NZ Commercial Complex
RTM02 Roof Construction
RTM03 External Walls
EDGE Assessment: v2.1.5
Downloaded date & time: 2020-05-14 05:56
| 44.95%
Bill of quantities with the materials used for roof construction clearly highlighted.
Façade drawi s clearly marki the exter al wall speci ca o selected a d
Drawings of the external wall sections; or
Manufacturer’s data sheet for specified building material; or
Bill of quantities with the materials used for the external wall clearly highlighted.
RTM04 Internal Walls
Drawings of the internal wall sections; or
Manufacturer’s data sheet for building materials used for internal wall specifications if available; or
Bill of quantities with the materials used for the internal wall clearly highlighted.
RTM05 Flooring
Drawings clearly marking the flooring specification selected; or
Manufacturer’s data sheet for building materials used for floor specifications; or
Bill of quantities with the materials used for the flooring clearly highlighted.
RTM06 Window Frames
Façade drawi s clearly marki the wi dow frame(s) speci ca o or
Manufacturer’s data sheet for glazing specified; or
Bill of quantities with the windows/window frames clearly highlighted.
RTM07 Wall Insulation
Drawings clearly marking the insulation specification selected; or
Manufacturer’s data sheet for insulation specified; or
Bill of quantities with the insulation materials clearly highlighted.
RTM08 Roof Insulation
Drawings clearly marking the insulation specification selected; or
Manufacturer’s data sheet for insulation specified; or
Bill of quantities with the insulation materials clearly highlighted.