Camp Lejeune Barracks Daylighting Analysis 19 October 2009 University of North Carolina at Charlotte Charlotte, NC Architects: LS3P 227 W. Trade Street Suite 700 Charlotte, NC 28202
Center for Integrated Building Design Research
School of Architecture - UNC Charlotte
Camp Lejeune Barracks Radiance Simulation
9 a.m. Simulations shown assume the following parameters: South-facing aperture VCT Floors: Warm Gray 7 M Door Frames/Wall Base: Pantone 7531 M Wall Paint: 7534 M Ceilings: White Window Frames: White
21% visual light transmittance
54% visual light transmittance
Camp Lejeune Barracks Radiance Simulation
10 a.m.
21% visual light transmittance
54% visual light transmittance
Camp Lejeune Barracks Radiance Simulation
11 a.m.
21% visual light transmittance
54% visual light transmittance
Camp Lejeune Barracks Radiance Simulation
12 noon
21% visual light transmittance
54% visual light transmittance
Camp Lejeune Barracks Radiance Simulation
1 p.m.
21% visual light transmittance
54% visual light transmittance
Camp Lejeune Barracks Radiance Simulation
2 p.m.
21% visual light transmittance
54% visual light transmittance
Camp Lejeune Barracks Radiance Simulation
3 p.m.
21% visual light transmittance
54% visual light transmittance
Camp Lejeune Barracks Radiance Simulation
4 p.m.
21% visual light transmittance
54% visual light transmittance
Camp Lejeune Barracks
Sq. Ft of Barracks with DF of 2
LEED Analysis
LEED Daylighting Credit Graph 180 160 140 120 100 80 60 40 20 0
9
10
11
12
13
14
15
16
21 VLT Glazing
10
20
25
28
26.5
24
20
10
54 VLT Glazing
96
145
166
170
168
162
123
70
Average Sq. Ft with DF of 12% 79% 2
Exceeds LEED requirement for daylighting performance credit