11.3.6 Auto Re-Arm time (20x

Technical Information

11.3.1 Zone 1 Fence Voltage Alarm Level (01xx#)

Sets the voltage below which the zone alarm will occur. If the fence voltage measured at the return “R” loop terminal falls below this level for more than the Missed pulse count a fence alarm (zone 1) will occur. The value is set directly, not via a table. For example to set a threshold of 25V enter: 0 1 2 5 # Setting this option to 0 effectively turns off fence voltage monitoring. Warning: Setting this level to higher than the normal running voltage of the fence will result in continuous fence alarms.

Value (x) Minimum 0 Default 20 Maximum 40 Alarm Level

0.0 V

20 V

40 V

11.3.2 Missed Pulse Count (06xx#)

This option enables the pulse count to be varied from the default (3). This is the number of bad or missing pulses that are counted before the alarm occurs.

NOTE: The lower this option is set the more likely you are to get false alarms.

The value is set directly. For example to set a threshold of 2 bad or missing pulses enter: 0 6 0 2 #.

Value (x) 0 1 2 3 Missed Pulses 1 1 2 3