Roofing Membrane System Rhepanol速 fk
速
Rhepanol fk
Technical Manual Edition 2008
Imprint
FDT - Legal Details
Roofing membrane system Rhepanol fk Technical manual
We refer emphatically to the fact, that all details mentioned, especially the application and utilization recommendation for the roofing membranes and their system accessories, have been developed under normal conditions, and based on our knowledge and experience. Appropriate storage and usage of the products are assumed.
Edition September 2008 Editor: FlachdachTechnologie GmbH & Co. KG EisenbahnstraĂ&#x;e 6 - 8 D-68199 Mannheim Germany Tel +49 6 21-85 04-0 Fax +49 6 21-85 04-2 05 www.fdt.de Copyright 2008 by: FlachdachTechnologie GmbH & Co. KG This manual corresponds with the FDT manufacturer application instructions for designers and applicators. It cannot, however, replace professional knowledge. Every user is obliged to keep his knowledge up to date! Technical changes reserved.
A warranty or reliability of a finished project cannot be deduced because of varying materials, substrates and differing work conditions, neither by any indications nor from verbal statements, irrespective of any legal positions. For the possible accusation, FDT acted intentionally or grossly negligent, the applicator has to supply evidence, that he provided FDT with all information and details, necessary for an appropriate and correct evaluation through FDT in written from, immediately available and complete. The applicator himself is responsible to control that the products are suitable for the given application. It is FDT´s right to change product specifications without notice. Property rights of third parties are to be considered. In addition our particular sales- and delivery terms are valid. Obligatory is the latest version of our product data sheet, which can be requested directly through FDT.
Roofing membrane system RhepanolÂŽ fk
3
Contents
Page
Roofing membrane system Rhepanol fk
5
The system – an overview
5
Rhepanol fk, mechanically fastened with Gripfix system
10
Application techniques
11
Roof Design
19
Rhepanol fk, loose-laid with ballast
31
Application techniques
32
Roof Design
37
Rhepanol fk, bonded fixing Application techniques
43 44
Roof Design
49
Data sheets, product information, accessories Data sheet Roofing membrane Rhepanol fk
62 63
Data sheet Rhepanol laminated metal sheet
65
Data sheet FDT vapour control layer fk
67
Data sheet Rhepanol fk fire protection layer
68
Data sheet FDT protection layer
69
Data sheet Rhepanol walkway tile
70
Data sheet Rhepanol adhesive 90
71
Data sheet FDT adhesive U
73
Data sheet Rhepanol fk standing seam profile
75
Data sheet FDT gravel stop profile
76
Accessories
77
Technical Approval
84
4
allrounder winter world, Neuss/Germany
The world of Rhepanol速 fk
Apartments, INT Marcy L'Etoile, France
Eurocontrol, Haren/Belgium Canary Wharf, London/ United Kingdom
John Dewars Ltd., United Destillers, Scotland/ United Kingdom Volkswagen Poznan/Poland
Roofing membrane system Rhepanol® fk
The system – an overview
5
Rhepanol® fk – advantages One, two, three, sealed!
Application is incredibly easy and safe: Roll out Rhepanol fk, clean the seam area, pull off the protective strip and press down the edge – sealed! The same goes for all preformed details, which are also equipped with the unique selfsealing edge system.
The roofing membrane with a strong character Tried and tested long-term reliability, over 50 years of experience with polyisobutylene The oldest synthetic roofing membrane made in Germany With a unique self-sealing edge for reliable and fast sealing of seams Fleece backing with extremely high tensile strength Made of polyisobutylene (PIB), therefore compatible with bitumen One roofing membrane for all application methods The only roofing membrane to be applied with the Gripfix system Resistant to UV-radiation Flexible at temperatures as low as – 60 °C Free of plasticizers and halogen-containing fireproofing agents Application without open flame No need for surface protection Comprehensive warranty on materials Ideal for refurbishment
Factory applied self-sealing edge for reliable and fast sealing of seams.
The self-sealing edge system The pre-fabricated self-sealing edge system is different from conventional adhesive bonding. Sealing of the seams is carried out by firmly joining homogenous materials. Immediately after the self-sealing edge has been pressed to the connecting membrane the seam is already waterproof. Owing to the integrated selfsealing edge, seams can be sealed without open flame, hot air, solvent welding or additional adhesives, making application more efficient and almost independent of weather conditions.
... roll out It only takes three steps: Rhepanol fk with self-sealing edge system.
... clean the seam, pull off the protective strip
... roll on the edge ... sealed!
Roofing membrane system Rhepanol® fk
6
The system – an overview
Rhepanol® fk – advantages
Preformed details with self-sealing edge system: External corner Internal corner Universal roof light corner Collars Cover tape for cross joints and flashings
These in-situ tests are confirmed in forecasts about the life expectancy by approved neutral European Institutes. The British Board of Agrément has confirmed a life expectancy for Rhepanol fk for at least 30 years. The C.A.U. GmbH Gesellschaft für Consulting und Analytik im Umweltbereich (Company for Ecological Consulting and Analytics Ltd.) has also certified a potential life of 30 years.
For further technical information Rhepanol fk roofing membranes please see product data sheets on p. 63 ff. Long-term reliability – signed and sealed Regular quality tests of Rhepanol fk are carried out by in-house material testing as well as by independent test institutes. Additionally, Rhepanol roofs that have been established many years are opened and tested. The result: Even after 21 years of weather exposure the roofing membrane Rhepanol fk surpasses all requirements set up for new roofing membranes according to DIN 16731. This has been proven in a survey carried out by the independent Material Testing Institute Darmstadt on the roof of the workshop hall of DURA GmbH + Co KG in Plettenberg/Germany.
Continental AG, Hanover: Workshop hall with more than 10,000 m2 of roof area, covered with Rhepanol fk grey, bonded fixing.
DURA GmbH + Co KG, Plettenberg: Practical testing after 21 years of weather exposure has proven outstanding waterproofing quality and ageing resistance of Rhepanol fk.
If you want more detailed information on the long-term qualities of Rhepanol, we are able to provide you with the extended test reports.
Roofing membrane system Rhepanol® fk
The system – an overview
7
Quality control
Official seal of approval for Rhepanol fk
Warranty on materials
Rhepanol fk is known as ´the long-term reliable roofing membrane`. There are many reasons for that: FDT does not focus on short-term profit, but on high-quality and durable products. Therefore we have established stringent quality control requirements that eliminate sources of error. This in-house quality assurance system for the whole company has been certified according to DIN EN ISO 9001, the world’s most strict quality standard, and is Oualitätsmanagement constantly monitored by TÜV CERT. We pay the same attention to materials nach DIN EN ISO 9001 control carried out during production as to the quality assurance measures and the highly mechanized production.
Warranty certificates are available for all roofing membranes supplied by FDT. FDT offers comprehensive warranty, securing everybody’s investments in new buildings or refurbishment.
70 100 M 543
Control measures (amongst others): No blisters or cracks Thickness, width Weight per square metre Maximum tensile force, elongation at maximum tensile force Dimensional stability after storage at + 80 °C Bending at low temperatures In addition, Rhepanol fk is permanently monitored by an officially approved testing institute. In 1980 we signed a quality control agreement with the State Material Testing Institute Darmstadt, plastics department. The regular controls carried out by the Material Testing Institute not only include production, but also external stores and building sites. The quality control of an independent testing institute provides additional security when waterproofing flat roofs with Rhepanol fk.
Quality assurance Testing according to DIN EN ISO 9001. We shall be glad to send you a copy of the TÜV certificate on request. Ecology Since 1990, Rhepanol fk has been subjected to a life cycle assessment, carried out by the renowned and independent Batelle-Institute. It confirmed the outstanding ecological profile of Rhepanol fk during its whole life cycle. In 2002 the C.A.U. GmbH (Company for Ecological Consulting and Analytics Ltd.) was commissioned to update this study for Rhepanol fk according to DIN EN ISO 14040 ff. The result was a life cycle assessment, containing an analysis and a valuation of all ecological aspects of the entire life cycle of the product. The conclusions reconfirm the statements made in 1990. Further information is available on application.
Roofing membrane system Rhepanol® fk
8
The system – an overview
Rhepanol® fk – overview Application methods and roof build-ups
Non-traffic roof areas, slope up to 20° Roof type
Supporting deck
Non-ventilated roof (warm roof)
Profiled steel decking
Reinforced concrete
Aerated concrete
Ventilated roof (cold roof)
Suitable timber board cladding
Suitable chipboards/ veneer boards
mechanically fastened with Gripfix system*
Roofing membrane system Rhepanol® fk
The system – an overview
Rhepanol® fk – overview Application methods and roof build-ups
bonded fixing
Slope up to 3°
Used roofs, slope up to 3°
loose-laid with ballast*
loose-laid with ballast*
On stable old roofing independent of the type of supporting deck (refurbishment)
Aerated concrete
Terraces, balconies
Reinforced concrete
Suitable timber board cladding
Suitable chipboards/ veneer boards
* we recommend a max. roof slope of 3°. For waterproofing roofs for vehicular traffic and roof gardens we recommend our roofing system Rhepanol hg.
9
Rhepanol速 fk mechanically fastened with Gripfix system
10
Swimming bath, Breistroff/ France
RABO-bank, Huizen/ Netherland
Volkswagen, Poznan/ Poland
Velodrome Kaarst/Germany
Rhepanol速 fk mechanically fastened with Gripfix system
Application techniques
Safety and functional efficiency, supporting construction
The mechanical fastening of Rhepanol fk with Gripfix system ensures secure, fast and effective laying.
Safety and functional efficiency
Clean, dry and even roof surfaces.
With mechanical fastening the roof sealing is separated from the lower layers and components across the complete area. Movements of these layers and components can therefore not pass on stresses to the sealing, which is significant for the prevention of damage, especially on lightweight roofs. The roofing membrane Rhepanol fk is rolled onto mechanically fastened Gripfix strips, providing optimal wind load distribution and securing the membrane permanently to the roof.
If Rhepanol fk is directly laid on concrete decks/screed allow the concrete/screed to set for at least 28 days. If Rhepanol fk is installed directly on concrete decks/screed, pre-coating of the main area with bitumen is required. Alternatively, a min. 0.2 mm thick PE foil can be installed as a separation layer. At flashings and cappings no pre-coating or PE foil is needed.
The membrane seams run perpendicular to the Gripfix strips and thus are not affected by wind uplift forces. The integrated highly tear-resistant synthetic fleece of Rhepanol fk allows diffusion of any retained moisture. Rhepanol fk is compatible with bitumen and can be applied without additional separation layers directly onto old bituminous sheets. The integrated synthetic fleece protects the membrane against movement originating from the substrate. Application instructions Supporting construction The supporting deck structure has to meet the requirements with regard to loadbearing capacity, deflection, anchorage and drainage. Substrates for application must be free of open cracks, concrete, rough and sharp projections. Joints have to be formed according to constructional requirements, as their width or movement may impede the functional efficiency of the roof seal.
The effect of air escaping from the building at the roof perimeter and at roof penetrations must be prevented. Therefore these areas have to be made airtight. In the case of profiled steel decking, seal around all openings and perimeters. For compatibility reasons, timber board cladding, chipboards and similar may be treated only with salt-based wood preservatives. Oil or solvent based impregnation agents must not be used. Real wood boarding must be thoroughly swept with a broom. In individual cases, a synthetic fleece 300 g/m2 may be useful as an additional protection layer in order to prevent perforation of the membrane by sticking out splinters. National standards and regulations must be observed.
11
12
Rhepanol® fk mechanically fastened with Gripfix system
Application techniques
Vapour control layer, thermal insulation layer
Vapour control layer
Thermal insulation layer
In the case of non-ventilated roofs, we recommend the following vapour control layers:
When designing the thermal insulation layer on steel profile supporting decks, attention must be given to load bearing capacity.
For non air-conditioned rooms (e.g. living rooms and offices or similar rooms without suspended ceiling): FDT vapour control layer fk (polyethylene) with µ x s = 120 m. In the case of aerated concrete supporting decks with correctly calculated thermal insulation, you may leave out a vapour control layer, if the room temperature stays below 20 °C and the relative air humidity inside the room will not exceed 65 %. In case of doubt, we recommend a calculation of the building physics in order to identify the diffusion characteristics of the roof build-up. With lightweight steel deckings, we also recommend in principle the installation of a separate vapour control layer, which should be formed as an air barrier according to the provisions of the Thermal Insulation Regulation. The FDT vapour control layer fk is applied with a seam overlap of 10 cm, with the seams being sealed with connection or seam tape. The vapour control layer must be taken up and flashed at connections and cappings; at roof penetrations it must be flashed. For rooms with high air condition loads: In case of air-conditioned rooms and rooms with high air condition loads, as well as high pressure rooms, there should be no mechanical fastening through the vapour barrier. In these cases please consult our experts to identify the right layer build-up and application method. National standards and regulations must be observed.
As materials for thermal insulation layers we recommend: For roof slopes up to 20°: large-sized insulation boards made of expanded polystyrene with rebated edge according to DIN EN 13163, size 1.20 x 1.20 m or 1.20 x 1.00 m. On top of the insulation boards, for fire protection reasons, the application of a fire protection layer – a specially coated woven glass cloth – will be necessary Flexible insulation boards or expanded polystyrene foam boards with backing according to DIN EN 13163. For fire protection reasons, bituminous sheets with an integrated glass fleece or fabric > 60 g/m2 may be necessary as a lining. Use linings with a PE foil or fleece facing. Large-sized non-flammable mineral fibre boards, according to EN 13162 with a point load of Fp > 650 N in accordance to EN 12430. Small-sized insulation boards can be used, provided they can be properly fastened. National standards and regulations must be observed. The guidelines of the insulation board manufacturer must be observed.
Rhepanol速 fk mechanically fastened with Gripfix system
Application techniques
13
Thermal insulation layer, Rhepanol速 fk, mechanically fastened with Gripfix system
Insulation boards or board sections that are not sufficiently fixed with Gripfix must be secured in a stable position with additional fasteners (at least 2 fasteners/m2) prior to applying the roofing membrane. Insulation materials that are not dimensionally stable and which buckle or bulge must not be installed. Generally insulation boards must be laid brick-bond pattern.
System sketch Rhepanol fk Gripfix system with Rhepanol fk fire protection layer.
Rhepanol速 fk, mechanically fastened with Gripfix system The Gripfix strips are placed according to the wind uplift calculation and mechanically fastened. The Gripfix strip spacing is variable depending on the wind load requirements. The roofing membrane Rhepanol fk is then loose-laid with a seam overlap of 50 mm perpendicular to the Gripfix strips. The grip is achieved by thoroughly rolling the roofing membrane Rhepanol fk to the Gripfix strip. The membrane width is always 1.05 m. With the Gripfix system there is no need for various membrane widths. Depending on the substrate a variety of different fasteners may be used.
Roofing membrane Rhepanol fk Gripfix strip mechanically fastened Rhepanol fk fire protection layer
Thermal insulation
FDT vapour control layer fk
Profiled steel decking, corrosion protected
14
Rhepanol® fk mechanically fastened with Gripfix system
Application techniques
Fasteners/fastener spacing
Rhepanol fk can be mechanically fastened on roofs with any slope. For slopes exceeding 20°, application should be agreed with our experts. On profiled steel deckings and timber board cladding the Gripfix strips must be arranged perpendicularly to the corrugations or boards to achieve the most regular wind load distribution possible into the supporting deck.
On request, computer-based project specific calculations of the necessary amount of fasteners and Gripfix strip spacing are carried out, which may result in lesser amounts of fasteners than indicated in the table, provided the building has a favourable geometry. ■
If Rhepanol fk is directly laid on concrete decks/screed allow the concrete/screed to set for at least 28 days. Pre-coating of the main area with bitumen is then required in two consecutive coats. Alternatively, a min. 0.2 mm thick PE foil can be installed as a separation layer. At flashings and cappings no pre-coating or PE foil is needed.
■
Real wood boarding must be thoroughly swept with a broom. In individual cases, a synthetic fleece 300 g/m2 may be useful as an additional protection layer in order to prevent perforation of the membrane by sticking out splinters.
At all flashings and cappings, roof lights etc. the build-up must be specially secured by circumferential rows of fasteners or Gripfix strips (min. 4 fasteners/m). Note: ■
Max. spacing of Gripfix strips see table above.
■
Fastening spacing on the Gripfix strip min. 150 mm, max. 600 mm.
■
Fastener spacing on the same corrugation at profiled steel deckings must not be less than 200 mm.
■
■
Use only fasteners with washers of max. 50 mm width. The max. wind force (including safety factor 1.5) per m Gripfix strip is 1.5 kN.
The design load is max. 0.5 kN/fastener. Instructions of the fastener manufacturer must be observed. For building heights over 20 m and in special cases (e.g. airplane hangars, buildings near the coast, extreme exposure) each characteristic of the project location and special conditions must be taken into account.
Maximum Gripfix strip spacing Building height
Inner area
Perimeter area
Corner area
up to 12 m
1.20 m
1.00 m
0.80 m
12 – 20 m
1.00 m
1.00 m
0.60 m
Rhepanol速 fk mechanically fastened with Gripfix system
Application techniques
15
Fastening example
Corner area Fastening at component edges at a distance of max. 0.25 m
Corner area
0.20 m 0.20 m
Inner area
0.40 m
Perimeter area = covering width of the roofing membrane
Perimeter area
1.00 m
min. width 1.00 m
Corner area
1.00 m Membrane edge Mechanically fastened Gripfix strip
Perimeter area min. width 1.00 m
Application techniques
Flashings and cappings
All flashings and cappings are carried out with Rhepanol fk flashing strips.
Additional requirements for roof refurbishment:
If the connecting membrane is bonded, then at flashing heights over 200 mm a full-size adhesive bond is necessary. Valley areas are left unbonded at a width of 200 mm to allow movement compensation. If the connecting membrane is mechanically fastened with Gripfix strips the following spacing must be observed (see sketch): – Distance of the first Gripfix strip from the internal corner of the parapet max. 100 mm – Spacing between the Gripfix strips or distance between Gripfix strip and upper capping max. 500 mm.
■
In the case of uneven substrates, protection layers are necessary. Rigid polystyrene foam insulation boards or purlite sheets can be used.
■
The strength of the supporting deck is crucial for the anchoring of the fastening elements. If there is doubt about the strength, e.g. of woodwool slabs or aerated concrete panels, pullout tests will be necessary to define the amount of fasteners depending on the project.
The necessary flashing and capping profiles are cut from laminated metal sheets and bent according to the specification and the local requirements like galvanized sheets. Forming of flashings and cappings is identical for all application methods. You will find details on this topic in the drawings ´Roof Design`.
Gripfix strip max. 500 mm
With wall flashings, the upper edge of the Rhepanol fk roofing membrane is pressed to the substrate with rigid wall connection profiles such as ´Classic` and additionally secured with FDT sealant A or S. The two-part FDT roof edge trims ensure flexible, yet windproof capping of the roof perimeter. When laying roofing membranes Rhepanol fk, in the area of cappings, bracket-mounted gutters and flashings also Rhepanol laminated metal sheets can be used.
Gripfix strip max. 100 mm
16
Rhepanol® fk mechanically fastened with Gripfix system
Sketch Parapet flashing/capping with Gripfix strips.
Rhepanol速 fk mechanically fastened with Gripfix system
Application techniques
Layer build-ups
Examples of layer build-ups Non-ventilated roof (warm roof)
3
4
1 Profiled steel decking 2 FDT vapour control layer fk 3 Mineral wool boards 4 Gripfix strip, mechanically fastened, laid perpendicularly to the corrugations 5 Roofing membrane Rhepanol fk, laid perpendicularly to the Gripfix strips
5
2 1
5 3
4
2
6
1 Profiled steel decking 2 FDT vapour control layer fk 3 Thermal insulation layer 4 Rhepanol fk fire protection layer 5 Gripfix strip, mechanically fastened, laid perpendicularly to the corrugations 6 Roofing membrane Rhepanol fk, laid perpendicularly to the Gripfix strips
1
3
2 1
1 Aerated concrete 2 Rhepanol Gripfix strip, mechanically fastened 3 Roofing membrane Rhepanol fk, laid perpendicularly to the Gripfix strips
17
18
Rhepanol速 fk mechanically fastened with Gripfix system
Application techniques
Layer build-ups
Examples of layer build-ups Ventilated roof (cold roof)
3
1 Suitable timber board cladding 2 Gripfix strip, mechanically fastened, laid perpendicularly to the boards 3 Roofing membrane Rhepanol fk, laid perpendicularly to the Gripfix strips
2 1
3
2
1
1 Suitable chipboards 2 Gripfix strip, mechanically fastened 3 Roofing membrane Rhepanol fk, laid perpendicularly to the Gripfix strips
Rhepanol速 fk mechanically fastened with Gripfix system
Roof Design
Parapet with insulation fillet Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Corrosion-protected profiled steel decking
AT FDT connection tape for FDT vapour control layer fk
2 Insulation fillet
AK Rhepanol fk flashing strip
3 Metal closure
AL Rhepanol contact adhesive 50
4 FDT vapour control layer fk
AM Metal angle
5 Thermal insulation to specification
AN Aluminium foil
6 Insulation fillet
AO Airtight sealing tape
7 Rhepanol fk fire protection layer (if necessary)
AP Capping
8 Roofing membrane Rhepanol fk mechanically fastened with Gripfix system
AQ Cladding
9 Perimeter fixing
AR Airtight sealing tape AS Gripfix strip
19
20
Rhepanol速 fk mechanically fastened with Gripfix
Roof Design
Parapet/Completed with Rhepanol lamiated metal Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Reinforced concrete
9 Gripfix strips
2 FDT vapour control layer fk
AT Rhepanol fk flashing strip
3 Thermal insulation to specification
AK Treated timber profile
4 Rhepanol fk fire protection layer (if necessary)
AL Rhepanol contact adhesive 50
5 Roofing membrane Rhepanol fk mechanically fastened with Gripfix system
AM FDT adhesive tape
6 Perimeter fixing 7 FDT connection tape for FDT vapour control layer fk 8 Thermal insulation to specification
AN Rhepanol cover tape AO Metal angle AP Rhepanol laminated metal
Rhepanol速 fk mechanically fastened with Gripfix system
Roof Design
Parapet Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Reinforced concrete
8 Thermal insulation to specification
2 FDT vapour control layer fk
9 Gripfix strip
3 Thermal insulation to specification
AT Rhepanol fk flashing strip
4 Rhepanol fk fire protection layer (if necessary)
AK Treated timber profile
5 Roofing membrane Rhepanol fk mechanically fastened with Gripfix system
AL Rhepanol contact adhesive 50
6 Perimeter fixing 7 FDT connection tape for FDT vapour control layer fk
AM FDT edge trim profile 110 mm AN Gripfix strip
21
22
Rhepanol速 fk mechanically fastened with Gripfix system
Roof Design
Wall connection Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Corrosion-protected profiled steel decking
AL Rhepanol laminated metal
2 Insulation fillet
AM Thermal insulation to specification
3 Metal angle
AN Z-profile
4 FDT vapour control layer fk
AO Metal closure
5 Thermal insulation to specification
AP Cladding
6 Rhepanol fk fire protection layer (if necessary)
AQ Thermal insulation
7 Roofing membrane Rhepanol fk
AR Airtight sealing tape
8 Rhepanol cover tape
AS Steel structure
9 FDT adhesive tape
BT Thermal insulation
AT Perimeter fixing
BK External cladding
AK FDT connection tape for FDT vapour control layer fk
Roof Design
Rhepanol速 fk mechanically fastened with Gripfix system
Wall connection with Gripfix profile Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Metal closure 2 Galvanized profiled steel decking
9 Rhepanol fk mechanically fastened with with Gripfix
3 Internal metal closure
AT Perimeter fixing
4 Cold bitumen primer
AK Airtight sealing tape
5 Vapour control layer
AL Brickwork
6 Thermal insulation to specification
AM Rhepanol fk flashing strip
7 Gripfix strip
AN Aluminium wall connection profile Gripfix
8 Rhepanol fk fire protection layer (where necessary)
AO FDT sealant A or S
23
24
Rhepanol速 fk mechanically fastened with Gripfix system
Roof Design
Rooflight connection Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Reinforced concrete
7 Perimeter fixing
2 FDT vapour control layer fk
8 Rhepanol fk upstand flashing
3 Thermal insulation to specification
9 Rhepanol contact adhesive 50
4 Rhepanol fk fire protection layer (if necessary)
AT Insulated rooflight kerb
5 FDT connection tape for FDT vapour control layer fk
AK Render
6 Roofing membrane Rhepanol fk, mechanically fastened with Gripfix system
AL Structural support AM Gripfix strip
Rhepanol速 fk mechanically fastened with Gripfix system
Roof Design
Free standing rooflight kerb Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Metal closure
8 Gripfix strip
2 Corrosion-protected profiled steel decking
9 Rhepanol fk upstand flashing
3 FDT vapour control layer fk
AT Rooflight frame
4 Thermal insulation to specification
AK Rhepanol contact adhesive 50
5 Roofing membrane Rhepanol fk, mechanically fastened with Gripfix system
AL Metal kerb
6 Fixing 7 Thermal insulation to specification
AM FDT connection tape for FDT vapour control layer fk
25
Rhepanol速 fk mechanically fastened with Gripfix system
26
Roof Design
Gutter connected with Rhepanol laminated metal sheet and Rhepanol double sided self sealing edge Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
max. 500 mm max. max. 500 500 mm mm
1 Corrugated steel deck
7 Treated timber profile
2 Thermal insulation to specification
8 Bracket
3 Rhepanol fk, mechanically fastened with Gripfix
9 Rhepanol laminated metal sheet
4 Rhepanol fk double sided self sealing edge 5 Gripfix strip 6 Fastener
AT Gutter
Roof Design
Rhepanol速 fk mechanically fastened with Gripfix system
Gutter connected with Rhepanol laminated metal angle Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Steel structure
7 Treated timber profile
2 Metal closure
8 Bracket
3 Corrosion-protected profiled steel decking
9 Rhepanol laminated metal angle
4 FDT vapour control layer fk
AT Gutter
5 Thermal insulation to specification
AK Perimeter fixing with Gripfix strips
6 Roofing membrane Rhepanol fk, mechanically fastened with Gripfix system
27
Rhepanol速 fk mechanically fastened with Gripfix system
28
Roof Design
Vent pipe Non ventilated roof / ventilated roof Warm roof / Cold roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Internal metal closure 2 Penetration kerb insulation sleeve
8 FDT connection tape for FDT vapour control layer fk
3 Corrosion-protected profiled steel decking
9 Gripfix ring
4 Fixing
AT Rhepanol self sealing collar
5 FDT vapour control layer fk
AK Vent pipe hood-removable
6 Thermal insulation to specification
AL FDT vent pipe
7 Roofing membrane Rhepanol fk, mechanically fastened with Gripfix system
AM Timber deck
Roof Design
Cold roof ventilator Cold roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Timber deck 2 Roofing membrane Rhepanol fk 3 Gripfix ring 4 Rhepanol self sealing collar 5 Fixing 6 FDT vent pipe cowl 7 FDT cold roof ventilator
Rhepanol速 fk mechanically fastened with Gripfix system
29
30
Rhepanol速 fk mechanically fastened with Gripfix system
Lightning conductor collar Non ventilated roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Thermal insulation to specification 2 Roofing membrane Rhepanol fk, mechanically fastened with Gripfix system 3 Fixing with counter sunk screw 4 Rhepanol self sealing collar 5 Cutting edge for 50 mm pipe 6 FDT Rhepanol fk sleeve 7 Jubilee clip 8 Lightning conductor
Roof Design
Rhepanol速 fk loose-laid with ballast
31
School centre, Stadthagen/ Germany
Business and Residential Area, Radevormwald, Germany
Eurocontrol, Haren/ Belgium
32
Rhepanol® fk loose-laid with ballast
Application techniques
Safety and functional efficiency, supporting construction, vapour control layer
Safety and functional efficiency
■
Joints have to be formed according to constructional requirements, as their width or movement may impede the functional efficiency of the roof sealing.
■
The roof slope should not exceed 3° to prevent the ballast slipping off.
■
Rhepanol fk is compatible with bitumen and can be applied without additional separation layers directly on old bituminous sheets.
An intrusion of air underneath the roof covering at the roof perimeter and at roof penetrations must be prevented. Therefore these areas have to be made windtight.
■
The integrated, highly tear-resistant synthetic fleece of Rhepanol fk allows diffusion, ensuring reliable vapour pressure compensation. Furthermore the fleece backing provides protection against stresses originating from the substrate.
For compatibility reasons, timber board cladding, chipboards and similar may be treated only with salt-based wood preservatives. Oil or solvent based impregnation agents must not be used.
■
National standards and regulations must be observed.
Because of loose laying, the roof covering is separated from the other layers of the build-up across the complete area. Movements and cracks in the supporting construction are not transferred into the roof covering. The ballast ensures the membrane remains secure against wind uplift forces.
Application instructions Vapour control layer Supporting construction ■
The supporting deck structure has to meet the requirements with regard to load-bearing capacity, deflection, anchorage and drainage.
■
Clean, dry and even roof surfaces.
■
If Rhepanol fk is directly laid on concrete decks/screed allow the concrete/screed to set for at least 28 days. Pre-coating of the main area with bitumen is then required in two consecutive coats. Alternatively, a min. 0.2 mm thick PE foil can be installed as a separation layer. At flashings and cappings no pre-coating or PE foil is needed.
■
Substrates for application must be free of open cracks, rough concrete, sharp edges and stones.
In the case of non-ventilated roofs, we recommend the following vapour control layers: ■
For non air-conditioned rooms (e.g. living rooms and offices or similar rooms without suspended ceiling): FDT vapour control layer fk (polyethylene) with µ x s = 120 m.
In the case of aerated concrete supporting decks with correctly calculated thermal insulation, you may leave out a vapour control layer, if the room temperature stays below 20 °C und the relative air humidity inside the room will not exceed 65 %. The vapour control layer is applied with a seam overlap of 100 mm, with the seams being sealed with connection or seam tape. The FDT vapour control layer fk must be taken up and flashed at connections and cappings; at roof penetrations it must be flashed.
Rhepanol® fk loose-laid with ballast
Application techniques
Thermal insulation layer, Rhepanol® fk, loose-laid, ballast
■
■
For rooms with high air condition loads (e.g. swimming pools, air-conditioned rooms): – aluminium reinforced bitumen, – vapour control membrane with metal tape reinforcement.
At all flashings and cappings, built-in details etc. you will need linear perimeter fixing with at least 4 fastening elements/m.
National standards and regulations must be observed.
Immediately apply ballast on loose-laid roofing membranes to secure its position against wind uplift.
Ballast
Thermal insulation layer Suitable materials are: You must bear in mind tread-fastness when designing the thermal insulation layer on steel profile supporting decks. Expanded polystyrene foam boards with rebated edge according to DIN EN 13163 and a length of max. 1.25 m are especially suitable materials for thermal insulation layers. With roof areas for walking on, insulation materials with higher compression strength must be used in accordance with the expected loads. Insulation materials that are not dimensionally stable and which buckle or bulge must not be installed. The insulation elements must be laid in a brick-bond pattern.
■
bulk gravel layers, min. 50 mm thick, washed natural uncrushed stones, fraction 16/32 or 20/40.
■ paving
slabs in a fine gravel bed on a protection layer.
If appropriate gravel is not available or the gravel is applied pneumatically, then, as under paving slabs, you will need an additional protection layer (e.g. synthetic fleece or FDT protection layer). Under screed you will have to apply the FDT protection layer (the overlaps have to be welded). PE layers and coarse rubber protective sheets must have an underlying synthetic fleece layer. Examples for ballast
■
■
National standards and regulations must be observed. The guidelines of the insulation board manufacturer must be observed.
Rhepanol fk, loose-laid Roofing membranes Rhepanol fk are loose-laid with a seam overlap of 50 mm. The membrane seams are quickly sealed with the prefabricated self-sealing edge almost independent from weather conditions.
For ballast, the provisions of national wind load standards must be observed. At building heights over 20 m and for roofs with high wind exposure (e.g. tower-style, detached buildings, airplane hangars and buildings near the coast) it is necessary to define appropriate project-related measures for membrane position stability.
33
34
Rhepanol® fk loose-laid with ballast
Application techniques
Flashings and cappings, roof refurbishment
Flashings and cappings All flashings and cappings are carried out with Rhepanol fk flashing strips. With flashing heights of over 200 mm, full-size adhesive bonding of the covering at the upstand is necessary. Valley areas are left unbonded at a width of 200 mm to allow movement compensation. The upper edge of the Rhepanol fk roofing membrane is pressed to the substrate with rigid wall connection profiles such as ´Classic` and additionally secured with FDT sealant A or S. The two-part FDT roof edge trims ensure flexible, yet windproof capping of the roof perimeter. When laying roofing membranes Rhepanol fk, in the area of cappings, bracket-mounted gutters and flashings also Rhepanol laminated metal sheets can be used. The necessary flashing and capping profiles are cut from laminated metal sheets and bent according to the specification and the local requirements like galvanized sheets. The forming of flashings and cappings is identical for all application methods. You will find details on this topic in the drawings ´Roof Design`.
Additional requirements for roof refurbishment: ■
Thoroughly sweep the roof area. Remove any blisters, projections and coarse roughness.
■
On rough substrates (such as embedded gravel), a protection layer is necessary. We recommend suitable polystyrene insulation boards, which provide additional insulation at the same time.
■
Temporary storage of gravel must not exceed the maximum load of the supporting deck.
■
Soiled gravel must be cleaned (e.g. by sieving). Otherwise, appropriate protection layers such as synthetic fleece 300 g/m2 must be applied.
Rhepanol速 fk loose-laid with ballast
Applications techniques
Layer build-ups
Examples of layer build-ups
3 2 1 1 Timber board cladding/derived timber products 2 Roofing membrane Rhepanol fk 3 Bulk gravel, fraction 16/32 or 20/40
5
4 3 2 1
1 Timber board cladding/derived timber products 2 Roofing membrane Rhepanol fk 3 Protection layer, e.g. FDT protection layer 4 Gravel layer, fraction 8/16, min. 30 mm thick 5 Paving slabs, e.g. 500/500/50 mm
35
36
Rhepanol速 fk loose-laid with ballast
Application techniques
Layer build-ups
Examples of layer build-ups Non-ventilated roof (warm roof) 1 Aerated concrete 2 Roofing membrane Rhepanol fk 3 Bulk gravel
3 2 1
5
1 Reinforced concrete 2 FDT vapour control layer fk 3 Thermal insulation layer EPS 4 Roofing membrane Rhepanol fk 5 Bulk gravel, fraction 16/32 or 20/40
4 3 2 1
7 6 5 4 3 2 1
1 Reinforced concrete 2 FDT vapour control layer fk 3 Thermal insulation 4 Roofing membrane Rhepanol fk 5 Protection layer, e.g. FDT protection layer 6 Gravel layer, fraction 8/16, min. 30 mm thick 7 Paving slabs, e.g. 500/500/50 mm
RhepanolÂŽ fk loose-laid with ballast
Roof Design
Capping Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Reinforced concrete
8 Bonding
2 FDT vapour control layer fk
9 Thermal insulation to specification
3 Thermal insulation to specification
AT Rhepanol fk flashing strip
4 Roofing membrane Rhepanol fk, loosel-laid
AK Rhepanol contact adhesive 50
5 Min. 50 mm round washed gravel (20 – 40 mm diam.)
AL Treated timber profile
6 Perimeter fixings
AN Cladding
7 Sealing tape for FDt vapour control layer fk
AM Rhepanol laminated metal sheet
37
Rhepanol速 fk loose-laid with ballast
38
Roof Design
Parapet completed with Rhepanol laminated metal Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Reinforced concrete
9 Thermal insulation to specification
2 FDT vapour control layer fk
AT Rhepanol fk flashing strip
3 Thermal insulation to specification
AK Rhepanol contact adhesive 50
4 Roofing membrane Rhepanol fk, loose-laid
AL Treated timber profile
5 Min. 50 mm round washed gravel (20 - 40 mm diam.)
AM Metal angle
6 Perimeter fixing
AN Rhepanol laminated metal drip
7 FDT connection tape for FDT vapour control layer fk
AO Cladding
8 Bonding
Rhepanol速 fk loose-laid with ballast
Roof Design
Parapet with FDT edge trim profile Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Reinforced concrete
9 Thermal insulation to specification
2 FDT vapour control layer fk
AT Rhepanol fk upstand flashing
3 Thermal insulation to specification
AK Rhepanol contact adhesive 50
4 Roofing membrane Rhepanol fk, loose-laid
AL Treated timber profile
5 Min. 50 mm round washed gravel (20 - 40 mm diam.)
AM FDT roof edge trim
6 Perimeter fixing with single fasteners
AN Cladding
7 FDT sealing tape for FDT vapour control layer fk 8 Adhesive bond
39
40
Rhepanol® fk loose-laid with ballast
Roof Design
Wall connection Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Reinforced concrete
9 Bonding
2 FDT vapour control layer fk
AT Thermal insulation to specification
3 Thermal insulation to specification
AK Wall connection profile ´Classic`
4 Roofing membrane Rhepanol fk, loose-laid
AL Flashing
5 Min. 50 mm round washed gravel (20 – 40 mm diam.)
AM Treated timber profile
6 Perimeter fixing
AN FDT sealant A or S
7 Rhepanol fk flashing strip
AO Brickwork
8 FDT connection tape for FDT vapour control layer fk
RhepanolÂŽ fk loose-laid with ballast
Roof Design
Rooflight connection Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Reinforced concrete
9 Rhepanol contact adhesive 50
2 FDT vapour control layer fk
AT Rooflight upstand
3 Thermal insulation to specification
AK Render
4 Roofing membrane Rhepanol fk, loose-laid
AL Metal extrusion
5 FDT connection tape for FDT vapour control layer fk 6 Min. 50 mm round washed gravel (20 – 40 mm diam.) 7 Perimeter fixing 8 Rhepanol fk flashing strip
41
42
RhepanolÂŽ fk loose-laid with ballast
Roof Design
Gutter Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Steel structure 2 Internal metal closure
8 Treated timber profiles
3 Corrosion-protected profiled steel decking
9 Rhepanol fk holder with clamp and self sealing collar
4 FDT vapour control layer fk
AT FDT gravel stop profile
5 Thermal insulation to specification
AK Bracket
6 Roofing membrane Rhepanol fk, loose-laid
AL Rhepanol laminated metal angle
7 Min. 50 mm round washed gravel (20 – 40 mm diam.)
AM Gutter
Rhepanol速 fk bonded fixing
43
John Dewars Ltd, United Distillers, Scotland/United Kingdom
Canary Wharf, London/ United Kingdom
Television tower, Hamburg/Germany
Galerie Monnaie, Brussels/Belgium
44
Rhepanol® fk bonded fixing
Application techniques
Safety and functional efficiency, supporting structure, vapour control layer
Safety and functional efficiency
■ The
necessity for pre-coating to provide reliable adhesion and dust bonding depends on the substrate conditions.
Bonding Rhepanol fk in stripes ensures maximum possible mobility of the roofing membrane. The integrated, highly tear-resistant synthetic fleece of Rhepanol fk allows diffusion, thus ensuring reliable vapour pressure compensation and secure bonding to the substrate. Rhepanol fk is compatible with bitumen and can be bonded without additional separation layers, directly to old bituminous sheets. The integrated synthetic fleece protects the membrane against stresses originating from the substrate.
■
– It is not necessary to pre-coat coated profiled steel deckings, except when welding on bituminous sheets (only as bonding agent).
■
National standards and regulations must be observed.
Application instructions
Vapour control layer
Supporting construction
In the case of non-ventilated roofs, we recommend the following vapour control layers:
■
The supporting deck structure has to meet the technical requirements, especially for loadbearing capacity, deflection, anchorage and drainage.
■
Substrates for application must be free of open cracks, rough concrete and sharp projections.
■
Joints have to be formed according to constructional requirements, as their width or movement may impede the functional efficiency of the roof waterproofing.
■
An intrusion of air underneath the roof covering at the roof perimeter and at roof penetrations must be prevented. Therefore these areas have to be made windtight.
■
Clean, dry and even roof surfaces.
■
If Rhepanol fk is directly laid on concrete decks/screed allow the concrete/screed to set for at least 28 days. Pre-coating of the main area with bitumen is then required in two consecutive coats.
– Aerated concrete panels must always be pre-coated.
■
For non air-conditioned rooms (e.g. living rooms and offices or similar rooms without suspended ceiling): vapour control membrane with µ x s over 100 m. In the case of aerated concrete supporting decks with correctly calculated thermal insulation, you may leave out a vapour control layer, if the room temperature stays below 20 °C und the relative air humidity inside the room will not exceed 65 %.
■
For rooms with high air condition loads (e.g. swimming pools, air-conditioned rooms): vapour control layer with aluminium reinforcement, glass fleece or woven glass tissue reinforcement.
In case of doubt, we recommend a calculation of the building physics in order to identify the diffusion characteristics of the roof build-up.
Rhepanol® fk bonded fixing
Application techniques
Vapour control layer, thermal insulation layer
With lightweight steel deckings, we also recommend in principle the installation of a separate vapour control layer, which should be formed as an air barrier according to the provisions of the Thermal Insulation Regulation. ■ The
vapour control layer must be taken up and flashed at connections and cappings, at roof penetrations it must be flashed.
standards and regulations must be observed.
■
Large-sized non-flammable mineral fibre boards, according to EN 13162 with a point load of Fp > 650 N in accordance to EN 12430. With bonded application using mineral wool insulation material, the type of insulation material and the adhesive/amount of adhesive needed is to be defined depending on the project.
■ National
As a lining, use bituminous sheets without PE backing.
Note:
Generally insulation boards must be laid brickbond pattern. Insulation materials that are not dimensionally stable and which buckle or bulge, or insulation elements with insufficient lining stability must not be installed.
For bonding the insulation layer with FDT adhesive U, use vapour control membranes without PE backing or talcum coating. Thermal insulation layer The thermal insulation layer is to be designed in accordance with the thermal protection requirements. As materials for thermal insulation layers we recommend: ■
Flexible insulation boards or expanded polystyrene foam boards according to EN 13163 with backing. For fire protection reasons, bituminous sheets with an integrated glass fleece or fabric > 60 g/m2 may be necessary as a lining.
Bonding of the thermal insulation layer is preferably done with FDT adhesive U, a onecomponent polyurethane adhesive. For roof slopes exceeding 7°, additional supporting measures are necessary to prevent the materials slipping off while the adhesive is curing. For further information on the adhesive and its application see data sheet FDT adhesive U. ■ National
standards and regulations must be observed.
Consumption of FDT adhesive U for thermal insulation1) Building height2)
Inner area
Perimeter and corner area
Min. amount of adhesive stripes/m3)
0–8m
180 g/m2
250 g/m2
10
g/m2
g/m2
10
over 8 – 20 m
200
300
1) For mineral fibre insulation materials, the adhesive consumption is to be defined depending on the project. 2) Not for tower-style, detached buildings. Not for exposed positions and coastal areas. 3) With profiled steel decking, 2 adhesive stripes per corrugation. As the vapour control layer may sag, the adhesive
stripes must be placed on the corrugation shoulders.
45
46
Rhepanol® fk bonded fixing
Application techniques
Rhepanol® fk bonded with Rhepanol adhesive 90
Rhepanol fk bonded with Rhepanol adhesive 90 With the Rhepanol adhesive 90 specially designed for Rhepanol fk, the roofing membrane is securely bonded to the substrate. The adhesive is applied in stripes with at least 8 stripes/m. Consumption of Rhepanol adhesive 90 for the roofing membrane Rhepanol fk1) Building height2)
Inner area
Perimeter and corner areas
0–8m
160 g/m2
240 g/m2
8
g/m2
280 g/m2
8
over 8 m – 20 m
200
Min. amount of adhesive stripes/m1
1) If the base is of mineral wool insulation materials the adhesive/adhesive consumption is to be defined depending on the project. 2) Not for tower-style detached buildings. Not for exposed positions and coastal areas.
Adhesive consumption depends on the location and height of the building and on the bonding substrate. For building heights over 20 m and in the case of roofs with high wind exposure (e.g. towerstyle, detached buildings, airplane hangars and buildings near the coast), it is necessary to calulate the amount of adhesive needed to fix the membrane securely. For roof slopes exceeding 15°, additional mechanical fastening may be necessary to prevent the roofing membrane slipping off while the adhesive is curing. At slopes exceeding 20°, application should be agreed with our experts. For information on the adhesive, its application and processing see data sheet Rhepanol adhesive 90 (page 71).
Rhepanol® fk bonded fixing
Application techniques
Linear perimeter fixing, flashings and cappings, roof refurbishment
Linear perimeter fixing A linear perimeter fixing at flashings and cappings is necessary: ■
With supporting decks made of galvanized profiled steel.
■
In general, with bonded roof build-ups with mineral fibre insulation materials, independent from the supporting deck.
The perimeter fixing of the roof build-up, including the roofing membrane, is achieved in each instance with at least four fixings per metre.
Flashings and cappings All flashings and cappings are carried out with Rhepanol fk flashing strips. With flashing heights of over 200 mm should be fully
adhered to the upstand. Valley areas should be left un-bonded for an area of 200 mm to allow for movement. The upper edge of the Rhepanol fk roofing membrane is pressed to the substrate with rigid wall connection profiles such as ´Classic` and additionally secured with FDT sealant A or S. The two-part FDT roof edge trims ensure flexible, yet windproof capping of the roof perimeter. When laying Rhepanol fk to parapets, bracket mounted gutters and flashings it may be appropriate to use Rhepanol laminated metal flashings. The necessary flashing and capping profiles are cut from Rhepanol laminated metal sheets and bent according to the specification and the local requirements like galvanized sheets. Forming of flashings and cappings is identical for all application methods. For drawing example see ´Roof Design`.
Additional requirements for roof refurbishment: ■
Before overlaying with Rhepanol fk the adhesion between the old roofing layers, as well as to the supporting deck must be completely secure. Otherwise mechanical fastening will be necessary.
■ With
old roofs bonded with cold bituminous adhesive a mechanical fastening of the old roof is obligatory due to the plastic dimensional dynamics of the cold bituminous adhesive.
■
The substrate must be suitable for bonding, free from chippings and thoroughly cleaned.
Sketch Linear perimeter fixing
47
48
Rhepanol速 fk bonded fixing
Application techniques
Roof build-up
Examples for layer build-up
1 Reinforced concrete 2 FDT vapour control layer fk, bonded with FDT adhesive U 3 Thermal insulation layer EPS, with bitumen facing, bonded with FDT adhesive U 4 Roofing membrane Rhepanol fk, bonded with Rhepanol adhesive 90
4
Non-ventilated roof (warm roof)
3 2 1
1 Aerated concrete, pre-coated as required 2 Adhesive stripes Rhepanol adhesive 90 3 Roofing membrane Rhepanol fk, not bonded over board joints (sliding strips over cross joints as required)
3
2 1 Ventilated roof (cold roof)
4 3 2 1
3
2 1
1 Timber board cladding 2 Bituminous sheet with tear-resistant reinforcement, mechanically fastened, closed seams 3 Adhesive stripes Rhepanol adhesive 90 4 Roofing membrane Rhepanol fk
1 Chipboards/veneer boards 2 Adhesive stripes Rhepanol adhesive 90 3 Roofing membrane Rhepanol fk, not bonded over board joints (sliding strips as required)
Rhepanol速 fk bonded fixing
Roof Design
Wall connection Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Internal metal closure 2 Galvanized profiled steel decking
8 Perimeter fixing (4 pieces per meter)
3 Steel support section
9 Airtight sealing tape
4 Cold bitumen primer
AT Brickwork
5 Bitumen vapour control layer bonded with FDT adhesive U
AK Rhepanol contact adhesive 50
6 Expanded polystyrene with bituminised felt facing bonded with FDT adhesive U
AM FDT wall connection profile
7 Rhepanol fk bonded with Rhepanol adhesive 90
AL Rhepanol fk flashing strip
AN FDT sealant A
49
50
Rhepanol速 fk bonded fixing
Roof Design
Wall connection Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
7 Roofing membrane Rhepanol fk, bonded with Rhepanol adhesive 90
AM Rhepanol laminted metal angle
8 Rhepanol cover tape
AO FDT sealant A or S
3 Metal angle
9 FDT adhesive tape
AP Timber battens vertical
4 Cold bitumen primer
AT Perimeter fixing
AQ Timber battens horizontal
5 Vapour control layer
AK Airtight sealing tape
AR Cladding
6 Thermal insulation to specification bonded with Rhepanol adhesive 90
AL Brickwork
1 Metal plate 2 Corrosion-protected profiled steel decking
AN FDT wall connection profile
Rhepanol速 fk bonded fixing
Roof Design
Parapet/Completed with FDT edge trim profile Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Roof structure 2 Screed laid to falls 3 Existing roofing layers: Vapour control layer, thermal insulation to specification, bitumen felt 4 FDT adhesive U 5 Thermal insulation to specification 6 Roofing membrane Rhepanol fk, bonded with Rhepanol adhesive 90
7 Thermal insulation to specification 8 Rhepanol contact adhesive 50 9 Rhepanol fk flashing strip AT Treated timber profile AK FDT edge trim profile
51
Rhepanol速 fk bonded fixing
52
Roof Design
Roof perimeter/Completed with FDT edge trim profile Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Structure
7 Wall structure
2 Column
8 Thermal insulation to specification
3 Precast concrete
9 Rhepanol fk flashing strip
4 Existing roof layers: Bitumen vapour control layer, thermal insulation, bitumen felt
AT Treated timber profile
5 Expended polystyrene with bituminised felt facing bonded with FDT adhesive U 6 Roofing membrane Rhepanol fk bonded with Rhepanol adhesive 90 (horizontally), Rhepanol contact adhesive 50 (sloped, vertically)
AK FDT edge trim profile
RhepanolÂŽ fk bonded fixing
Roof Design
Rooflight – refurbishment Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Reinforced concrete
8 Rhepanol contact adhesive 50
2 Existing roof layers: Vapour control layer, thermal insulation to specification, bitumen felt
9 FDT sealant S AT Rooflight
3 FDT adhesive U
AK Insulation fillet
4 Thermal insulation to specification
AL Timber profile
5 Roofing membrane Rhepanol fk, bonded with Rhepanol adhesive 90 6 Treated timber profiles 7 Rhepanol fk flashing strip
53
54
Rhepanol速 fk bonded fixing
Roof Design
Gutter Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Steel structure
7 Treated timber profile
2 Metal angle
8 Bracket
3 Corrosion-protected profiled steel decking
9 Rhepanol laminated metal angle
4 Vapour control layer
AT Rhepanol adhesive 90
5 Thermal insulation to specification bonded with FDT adhesive U
AK Gutter
6 Roofing membrane Rhepanol fk bonded with Rhepaol adhesive 90
Rhepanol速 fk bonded fixing
Roof Design
Gutter connected with metal drip Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Steel structure
7 Treated timber profile
2 Metal closure
8 Bracket
3 Corrosion-protected profiled steel decking
9 Metal drip
4 Bitumen vapour control layer bonded with bonded with FDT adhesive U
AT Rhepanol contact adhesive 50
5 Thermal insulation to specification bonded with FDT adhesive U 6 Roofing membrane Rhepanol fk bonded with FDT adhesive 90
AK Bonded with Rhepanol contact adhesive 50 Optional: Precol primer AL Gutter
55
56
Rhepanol速 bonded fixing
Roof Design
Building movement joint with upstand Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Reinforced concrete
8 Thermal insulation to specification
2 Cold bitumen primer
9 Rhepanol fk flashing strip
3 Bitumen vapour control layers with metal sheet bonded with FDT adhesive U
AT Rhepanol contact adhesive 50
4 Thermal insulation to specification
AL Treated timber profile
5 Roofing membrane Rhepanol fk bonded with Rhepanol adhesive 90
AM Compressable thermal insulation
6 Steel angles at 800 mm c/c 7 Treated timber profiles
AK Capping
RhepanolÂŽ fk bonded fixing
Roof Design
FDT VarioGully roof outlet Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Structure
6 Rhepanol fk self sealing collar
2 Precast concrete
7 FDT VarioGully roof outlet ´slim line`
3 Existing roof layers: Bitumen vapour control layer, thermal insulation, bitumen felt 4 Thermal insulation to specification 5 Roofing membrane Rhepanol fk bonded with Rhepanol adhesive 90 (horizontally) and with Rhepanol contact adhesive 50 (sloped)
57
58
Rhepanol速 fk bonded fixing
Roof Design
FDT VarioGully roof outlet Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Roof outlet fixings (4 per outlet) 2 Stiffening metal plate 3 Corrosion-protected profiled steel decking 4 Bitumen vapour control layers with metal sheet bonded with FDT adhesive U 5 Cold bitumen primer 6 Thermal insulation to specification bonded with FDT adhesive U 7 Vapour control layer (collar)
8 FDT leaf guard 9 Gripfix collar AT Rhepanol self sealing collar AK Roofing membrane Rhepanol fk bonded with Rhepanol adhesive 90 AL FDT VarioGully roof outlet AM FDT warm roof attatchment
Roof Design
FDT rainwater outlet Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Thermal insulation to specification 2 Roofing membrane Rhepanol fk bonded 3 Gripfix strip 4 FDT RWE rainwater outlet 125 5 Rhepanol self-sealing collar
Rhepanol速 fk bonded fixing
59
60
Rhepanol速 fk bonded fixing
Roof Design
Re-roof outlet Non ventilatd roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Existing rainwater outlet 2 Existing thermal insualtion
8 Roofing membrane Rhepanol fk bonded with Rhepanol adhesive 90
3 Existing bitumen felts
9 Screw ring
4 Rhepanol Gripfix collar
AT FDT VarioGully re-roof outlet
5 FDT leaf guard 6 Re-roof outlet fixing 7 Rhepanaol fk self-sealing collar
Roof Design
FDT weir overflow Non ventilated roof / Warm roof Scale 1:5 (The layers relevant to the sealing are shown accentuated)
1 Reinforced concrete 2 Rhepanol contact adhesive 50 3 Roofing membrane Rhepanol fk bonded 4 Rhepanol cover tape 5 Rhepanol paste 6 FDT weir overflow Rhepanol
Rhepanol速 fk bonded fixing
61
62
Data sheets Product information Accessories
Roofing membrane Rhepanol® fk
Data sheet
63
Roofing membrane Rhepanol® fk
Rhepanol® fk The roofing membrane for all application methods Rhepanol fk is made of polyisobutylene (PIB), with a prefabricated self sealing edge and an integrated synthetic fleece backing. The sealing edge makes it easier to seal the seams and provides a permanently secure joint. The fleece backing provides additional protection against stresses originating from the substrate. Furthermore, the fleece backing allows diffusion and ensures secure fastening onto the substrate.
Range of application Depending on the supporting deck and the substrate conditions, Rhepanol fk can be applied in different ways: Roll out, clean the seam area,
mechanically fastened with Gripfix system
Material properties
■
loose-laid with ballast
■
■
bonded fixing
■
Rhepanol fk with a doublesided self-sealing edge is used for expansion joints and flashings. Quality assurance Rhepanol fk is subject to constant in-house and external quality control. The in-house quality assurance system for the whole company has been certified according to DIN EN ISO 9001, the world’s most strict quality standard, and is constantly monitored by TÜV CERT.
pull off the protective strip,
roll on the edge, that’s all!
Roofing membrane made of polyisobutylene DIN EN 13956, bitumen compatible, with polyester fleece backing, 1.5 mm thick, plus fleece, 1.0 mm thick. ■ Weather-resistant, even without additional surface protection. ■ Resistant to atmospheric influence such as UV-radiation or exhaust gas from industrial and heating plants. ■ Remains flexible, even at temperatures as low as – 60 °C. ■ Outstanding resistance to natural ageing. ■ Free of plasticizers, chlorine, halogens, bitumen and PVC, resistant to rotting, non-porous (factory highfrequency testing). ■ Resistant to flying sparks and radiant heat according to DIN V ENV 1187, confirmed by official test certificates, material class E according to EN 13501-1. ■ In terms of resistance to root penetration Rhepanol fk meets the test requirements of DIN 4062, sections 4.7 and 5.7. ■ Hail-resistant according to SIA 280. Rhepanol fk is highly resistant to most substances commonly used in the construction of roofs. Where exposure to high concentration of organic solvents, lacquers, fats and oils is likely, we recommend further advice from our Technical Support Team. Ecology Rhepanol fk has gone through a life cycle assessment according to ISO EN 14040-49, carried out by the independent institute C.A.U. GmbH (Gesellschaft für Consulting und Analytik im Umweltbereich) (Company for Ecological Consulting and Analytics Ltd). FDT will be glad to send you a summary on the life cycle assessment on request.
64
Roofing membrane Rhepanol® fk
Data sheet
Rhepanol® fk
Properties
EN standard
Tensile strength
EN 12311-2 (A)
Elongation
EN 12311-2 (A)
Value
> 400 > 50
Unit
N/50 mm %
Tear resistance
EN 12310-2
Joint peel resistance
EN 12316-2
> 150 > 80
Joint shear resistance
EN 12317-2
> 150
N/50 mm
Resistance to impact
EN 12691
700
mm
Resistance to static load
EN 12730 (B)
20
kg
Hail resistance; SIA 280
EN 13583
m/s
Dimensional stability
EN 1107-2
%
Water tightness
EN 1928 (B)
> 28 < 0.5 > 400
Foldability at low temperatures
EN 495-5
- 60
°C
UV exposure
EN 1297
h
Water vapour permeability
EN 1931
5000 > 260.000
Reaction to fire
EN 13501-1
class E
External fire performance
ENV 1187
Broof(t1)
Exposure to bitumen
EN 1548
passed
Thermal conductivity
DIN 52612/1
0.26
W/mK
4 x 10-5
K-1
Linear coefficient to thermal expansion
Material
Colour
Thickness Width Length Weight mm m m kg/m2
Rhepanol fk with synthetic fleece backing
grey, black grey, black grey, black grey, black grey, black
1.5 1.5 1.5 1.5 1.5
1.05 1.05 0.65 0.52 0.35
15 10 15 15 15
2.60 2.60 2.60 2.70 2.80
Rhepanol fk with double-sided self-sealing edge
grey, black grey, black grey, black grey, black grey, black
1.5 1.5 1.5 1.5 1.5
1.05 0.65 0.52 0.35 0.25
15 15 15 15 15
2.70 2.80 2.80 2.90 3.00
N N/50 mm
kPa
Rhepanol® laminated metal sheet
Data Sheet
Rhepanol® laminated metal sheet
Product view Rhepanol laminated metal sheet.
Application
Processing
When using Rhepanol fk, in the area of cappings, bracket-mounted gutters and flashings also Rhepanol laminated metal sheets can also be used. The necessary flashing and capping profiles are cut from laminated metal sheets and formed according to the specification and bent to the required dimensions like galvanized sheets.
■ Rhepanol
Range of application Steel drip angle at bracket-mounted gutters Wall capping ■ Wall connection profile ■ Roof edge trim ■
laminated metal sheets should be cut with a sharp tool and with the varnish side up. Thus, trimming of the cut sheets will not be necessary. ■ The clearance should be 0.03 – 0.04 mm. Rhepanol laminated metal sheets can be processed on any standard bending machine. ■ A bending radius of 1.2 – 1.8 mm is to be observed. ■ Processing (cutting, bending) of the Rhepanol laminated metal sheets should be done at room temperature, approx. 18 °C.
■
Properties Rhepanol laminated metal sheets with an overall thickness of 1.4 mm consist of hot galvanized metal sheets with a Rhepanol h facing and a varnish backing.
Substrates Suitable bearing substrates for fastening are concrete, full brickwork, timber, derived timber products, steel etc. Fasteners must be adapted to the substrate according to the following table and with respect to the corresponding manufacturer‘s instructions.
Example Roof edge trim/ Corner detail with the Rhepanol laminated metal sheet.
65
Rhepanol® laminated metal sheet
66
Data sheet
Rhepanol® laminated metal sheet
Suitable fasteners for substrates consisting of lightweight or aerated concrete, or vertically perforated bricks are to be agreed with the manufacturers. In order to prevent premature corrosion, a FDT synthetic fleece layer 300 g/m2 should be installed between the sheets and the substrate (e.g. concrete or aerated concrete). Bearing substrates Concrete or full brickwork
Suitable fastening elements Nylon plugs and corrosionproof impact plugs or screws, hammer impact rivets
■
The integrated self-sealing edge of Rhepanol fk allows for seam connection with the Rhepanol laminated metal sheet without open flame, hot air or solvent welding or additional adhesives!
■
When combining Rhepanol laminated metal sheets and Rhepanol fk, at all flashings and cappings make sure that seam connections are not in the vertical area and that the seams do not have to take any peeling or shearing forces. Rhepanol laminated metal sheets must not be used as linear fastenings for bearing horizontal forces!
Form of supply Timber and Chipboard screws derived timber products Steel
Rivets, bolts or self-tapping screws
Application instructions Rhepanol laminated metal sheets (de-burred cut edges) are butted against each other with a clearance of 4 mm (profile length max. 2.00 m), in order to permit temperatureinduced elongation of the profiles. ■
A 38 mm wide FDT adhesive tape is affixed to the joint area.
■
Afterwards, a 150 mm wide Rhepanol h strip is applied which is homogeneously welded with hot air.
■
In order to avoid capillary action at profile joints, prior to applying the Rhepanol fk trim strips, the membrane edges of the 150 mm wide Rhepanol h strips must be sealed with Rhepanol paste.
Product name
Form of supply
Rhepanol laminated metal sheet 30 units stack 2 x 1 m x 1.4 mm Rhepanol laminated metal sheet 30 units stack 3 x 1 m x 1.4 mm Rhepanol laminated metal sheet 30 x 1 m x 1.4 mm coil Rhepanol h strip
Roll 0.15 m x 15 m
FDT adhesive tape
Roll 0.038 m x 50 m
Storage Rhepanol laminated metal sheets are factorypacked and transported on pallets. They should be stored horizontally in an even and dry place.
Data sheet
67
FDT vapour control layer fk
FDT vapour control layer fk
FDT vapour control layer fk Made of polyethylene sheet (PE). Works as diffusion retarding layer. Range of application ■
For non air-conditioned rooms (e.g. living rooms and offices or similar rooms without suspended ceiling).
■
In loose-laid or mechanically fastened layer build-ups with Rhepanol fk.
Properties Highly vapour-retardant Good stability characteristics ■ Compatible with bitumen ■ Not resistant to UV-radiation ■ ■
Physical data Properties
Testing according to DIN
Unit
Value
Tensile strength
53455
N/mm2
17
Elongation at break
53455
%
450–550
Thermal conductivity
52612
W/m x K
0.35
53122
(air = 1)
300 000
m
≥ 120
Water vapour diffusion resistance coefficient µ Air space width equivalent to water vapour diffusion (sd = µ x s) Forms of supply Material
Colour
FDT vapour control layer fk Connection tape for FDT vapour control layer fk Seam strip
grey
Nominal thickness
Width
Length
0.4 mm
4m
25 m
80 mm
12 m
15 mm
25 m
68
Rhepanol® fk fire protection layer
Data sheet
Rhepanol® fk fire protection layer
Application instructions
Roofing membrane Rhepanol fk, mechanically fastened with Gripfix system Rhepanol fk fire protection layer
Thermal insulation EPS
FDT vapour control layer fk
Profiled steel decking, corrosion protected
Rhepanol fk fire protection layer A special flame-retarding woven glass cloth with a weight of 175 g/m2. Range of application
The Rhepanol fk fire protection layer is loose-laid under the Gripfix strips at a seam overlap of 80 mm. Physical data Properties
As a fire protection layer with mechanical fastening of Rhepanol fk with Gripfix system at roofs up to 20° slope on unbacked polystyrene thermal insulation.
Unit DIN 4102-1 (A2) passed
Max. tensile force
N/50 mm
Elongation at max. tensile force
%
Properties
Weight per square metre
g/m2
Protection against flying sparks and radiant heat ■ Easy and clean application ■ Membrane width of 2.00 m means economical application ■ Resistant to rotting
Form of supply
■
Value
Flame resistance – flame chamber test according to > 1000 >4 175
Material
Colour
Width m
Length m
Weight kg/roll
Rhepanol fk fire protection layer
white
2.00
100
approx. 36
Data sheet
FDT protection layer
69
FDT protection layer
FDT protection layer Protects the roof waterproofing against mechanical damage. The FDT protection layer consists of a 1.8 mm high perforation resistant PIB membrane with polyester fleece backing. Range of application For layer build-ups with synthetic roofing membrane Rhepanol fk: ■ As a separation layer if non-standard gravel is used ■ As a protection layer for used roof terraces with paving slabs or garden roofs or car parks
The FDT protection layer is not designed for weather exposure and must always be covered.
At the edges of building elements, the FDT protection layer is applied in the form of a loosely overlapping skirt projecting approx. 250 mm into the covering area and remaining unwelded.
Paving slabs Fine gravel bed FDT protection layer Roofing membrane Rhepanol fk
Properties Protection of the waterproofing against mechanical damage ■ The fleece backing provides complete reliable separation from the waterproofing layer ■ Membrane width of 2.05 m means economical application ■
Thermal insulation
FDT vapour control layer fk
Concrete floor
Application instructions The FDT protection layer is loose-laid with the fleece-backed side down. Depending on the type of application, the seam connection can be carried out in different ways: With 80 mm seam overlap, without sealing. ■ For easy sealing of the seams the FDT protection layer has no fleece backing along the whole length of one edge. ■ With 50 mm seam overlap and sealing by solvent or hot air welding or with a selfsealing tape. The seams must be closed if used as protection layer under screed or slabs in a bed of mortar. ■
Forms of supply Colour
grey,
Width
Length
m 2.05
lower side : white 1) including fleece backing
m
Overall thickness mm
Weight kg/m2
10
1.81)
1.0
70
Rhepanol® walkway tile
Data sheet
Rhepanol® walkway tile
Analogue to Rhepanol roofing membrane, made of polyisobutylene (PIB), resistant to UV radiation and weathering. The structured surface (9 mm thick) ensures a safe grip, even on sloped and wet areas. Furthermore, the tile provides for good load distribution. Application Rhepanol walkway tiles are used for protecting the waterproofing and for marking the maintenance walkways on roofs covered with Rhepanol fk.
Surface structured for a safe grip. Lower side with self-sealing edge (with protection strip).
Product-testing/requirements Application instructions Reaction to fire: Class E in accordance with DIN EN 13501-1. ■ Dimensional stability after warm storage (6h, 80 °C): < 0,2 % (DIN 16726 Abs. 5.13). ■ slide prevention and load distribution. ■ Meets the requirements of DIN 4426 ´safety requirements for workplaces and accesses` on sloped flat roofs up to 20°. ■ ■
■
■ ■
■ ■
On new, clean and dry Rhepanol roofs the walkway tiles can be installed directly on the roof area. Fixing with the sealing edge: pull off the protective strip from the sealing edge, position the tile and press. At T-joints please seal with Rhepanol paste to prevent capillary action. On older and soiled roofs the seam area must be cleaned with Rhepanol solvent welding agent. Important: Finally press the edges with the FDT universal roller. No further measures are required to keep the tiles in place.
Note: On sloped flat roofs up to 10 ° slope please provide a joint of approx. 2 cm for water drainage, if installing the tiles perpendicular to the slope.
Forms of supply Colour:
anthracite/black; slight deviations in colour ar possible
Surface:
structured, rib height 4 mm
Lower side:
plain, with sealing edge for simple assembly and fixation
length/width/ thickness
800 mm/600 mm/9 mm
tolerances
+ 5 mm
weight:
approx. 7.3 kg/m2 or approx. 4 kg/tile
delivery form: 100 pc/palett or 48 m2/palett
Rhepanol® adhesive 90
Data sheet
71
Rhepanol® adhesive 90, FDT universal application trolley
Application For a consistent application of Rhepanol fk roofing membrane ■ Is applied in stripes with the FDT universal application trolley ■ Is supplied in containers that can be completely drained and thus recycled ■
Range of application For bonding of Rhepanol fk on the following substrates: ■ Reinforced concrete ■ Aerated concrete pre-coated as required ■ Chipboards, ply wood, OSB ■ New bituminous sheets (also as a lining for thermal insulation boards and sheets, without PE backing) ■ Aged bituminous sheets (with solid and clean surface) ■ Suitable insualtion boards Properties Rhepanol adhesive 90 is a liquid, solvent and synthetic-rubber-based adhesive ■ High adhesiveness ■ Elastic, no embrittling ■ Consistent at temperatures from – 40 °C to + 130 °C ■ High thermal stability ■ Application method which needs no power supply ■
Substrate The substrate has to be solid, even, clean, dry and free of grease and oil. Polystyrene rigidfoam boards or sheets must have a bituminous facing.
Application method The adhesive is applied either with the FDT universal application trolley, or manually. Manual application should be limited to roof areas that cannot be worked on with the FDT universal application trolley, such as small areas between roof lights. The FDT universal application trolley Easy to handle application tool which needs no power supply. ■ For the application of stripes of Rhepanol adhesive 90 from 25 kg containers. The amount of adhesive applied is regulated by the speed of application. ■
FDT universal application trolley with attached (completely drainable) 25 kg containers of Rhepanol adhesive 90
Rhepanol® adhesive 90
72
Data sheet
Rhepanol® adhesive 90
Sloping areas
■
At roof slopes over 15°: if necessary, apply additional mechanical fastening to prevent the roofing membrane slipping off while the adhesive is curing. ■ At roof slopes over 20°: application must be agreed with our technical department. ■
Storage Not frost-proof. Best storage in a dry place at + 10 °C.
Curing ■
If bituminous layers are used as a sealing sublayer curing time may be extended. However, even in very unfavourable conditions, the adhesive will be completely hardened within several days.
Under normal conditions a sufficient initial hardness is reached within 4 to 8 hours. The curing time of the adhesive depends on the evaporation of the solvents. Longer evaporation time reduces curing time.
Maximum period of storage: 24 months in tightly closed original containers. For further application instructions, see container and installation instructions Rhepanol fk.
Adhesive consumption Building height 0 – 8 m1) over 8 m – 20 m
Adhesive consumption Inner area
Perimeter and corner area
160 g/m2
240 g/m2
min. 8
g/m2
g/m2
min. 8
200
Number of adhesive stripes/m
280
1) At a consumption of 160 g/m2, the running adhesive stripe should be 8 mm wide.
Technical data Base
Colour
Bulk density
Compulsory notification accord.to Hazardous Material Regulation
Not frost-proof
Installation temperature
Open time
synthetic rubber
white
1.0 g/cm3
yes
no
min. + 5 °C
up to 20 minutes depending on the weather
Hazard identification, safety precautions, transport markings, see EC safety data sheet. Forms of supply Product name Rhepanol adhesive 90
Form of supply 9 kg container
Application for adhesive application with FDT universal application trolley (using adapter) or manual application
Rhepanol adhesive 90
12 kg container1)
for manual adhesive application
Rhepanol adhesive 90
25 kg container1)
for adhesive application with FDT universal application trolley
1) Owing to the clamping ring cover, the containers can be completely drained and thus be recycled.
FDT adhesive U
Data sheet
73
FDT adhesive U
Application
1)
For consistent bonding of thermal insulation materials and bituminous vapour control sheets. ■ To be applied in stripes with the FDT universal application trolley, equipped with a special adapter. ■
Application method With the FDT universal application trolley and adapter for FDT adhesive U (6.5 kg containers) for even substrates. ■ Manual application should be limited to roof areas that cannot be worked on with the application trolley, such as small areas between roof lights. ■
Properties Sloping areas Liquid, one-component solvent and CFC free polyurethane adhesive ■ High adhesiveness ■ Elastic, no embrittling ■ Consistent at temperatures from – 40 to + 100 °C ■ High thermal stability ■ Solvent and CFC free, does not affect rigid polystyrene foam ■ Foams and compensates small level differences of the substrate ■ Simple application method which needs no power supply ■ No risk of burning or fire ■
Substrate The bonding areas have to be solid, even, clean, dry and free of grease and oil. Adhesive consumption For building heights up to 20 m the consumption and the amount of adhesive stripes required are indicated on page 45 in the table “FDT adhesive U consumption for thermal insulation”. For detailed application instructions see the installation instructions Rhepanol fk and the containers.
At roof slopes over 7°: ■ Preferably, the adhesive should be applied in direction of the slope. ■ Supporting measures should be applied to prevent the materials slipping off while the adhesive is curing. Fascia boards, for example, can be used as abutment. At roof slopes over 20°, application must be agreed with our experts. Curing The curing time of the adhesive depends on the temperature as well as on the ambient humidity and the air humidity. Normally a sufficient initial hardness is reached within 1 to 3 hours. A slight moistening reduces the curing time. ■ In case of bonding vapour-proof materials, the curing time may be extended. However, even in very unfavourable conditions, the adhesive will be completely hardened within several days. ■ With high summer temperatures (approx. 25 °C and above) and low air humidity, it is recommended slightly moistening the substrate after applying the adhesive to ensure a sufficient degree of moisture for foaming. ■ Warning: Must not be used to bond Rhepanol roofing membrane. ■
1) Due to its foaming characteristics FDT adhesive U is not approved for bonding of bitumen sheet compensation layers, onto which the roofing membranes are directly bonded.
FDT universal application trolley with adapter and attached 6.5 kg containers of FDT adhesive U
FDT adhesive U
74
Data sheet
FDT adhesive U
Range of application Substrates
Bitumen sheet vapour control layers
Reinforced concrete
• •
Aerated concrete with
Rigid EPS foam boards and sheets
Mineral wool boards
•
cold bitumen primer
•
Chipboards Steel profile sheets – with plastic coating – with aluminium-zinc
• •
• •
•
• •
•
• • • •
•
– galvanized with anticorrosive coating Bituminous vapour control sheets1) Rigid EPS foam boards/sheets New bituminous sheets1)
•
Old bituminous sheets, if the surface is solid and clean
•
1) Without PE backing or talcum coating.
Do not use FDT adhesive U for bonding Rhepanol fk! Technical data Base (VBF) isocyanate prepolymer Flash point
non
Colour
Consistence
Bulk density
brownish
liquid
1.1 g/cm3
Compulsory notification according to Hazardous Material Regulation yes
Non-volatile matter 100 %
Installation temperature (air and substrate)
Open time
Height difference compensation
min. + 5 °C, max. 50 °C
up to 15 minutes depending on the weather
depending on humidity, temperature and amount applied: scheduled 5 mm
Storage Not frost-proof no
Best storage in a dry place at temperatures from + 10 °C to + 20 °C
Form of supply Product name FDT adhesive U
Form of supply 6.5 kg container
Maximum period of storage 12 months in tightly closed original containers.
Application FDT universal application trolley with adapter for FDT adhesive U
Hazard identification, safety precautions, transport markings, see EC safety data sheet.
Rhepanol® standing seam profile fk
Data sheet
Rhepanol® fk standing seam profile
The Rhepanol fk standing seam profile is a solid polyisobutylene profile with a prefabricated self-sealing edge for installation on Rhepanol fk. Length 2 m.
Application instructions ■
The application direction is always from the ridge to the eaves.
■ Do
Range of application
not apply through valley areas as this may impede rainwater drainage.
On sloped areas for a visually attractive imitation of standing seams on Rhepanol fk.
■ The
Properties
■A
special hand roller is used for pressing on the profile.
■ Flexible
for perfect fitting to the geometry of the roof.
■ Simple
application with self-sealing edge system which needs no power supply.
■ Trimming ■
profile is placed on the seam, so there is no need for additional marking.
and cutting with standard tools.
Can be coated with Rhepanol roof paint copper and silver or other colours on request.
Form of supply Product
Form of supply
Rhepanol fk standing seam
100 m/card-
profile grey
boardbox
Hand roller for Rhepanol fk
1 unit
standing seam profile Rhepanol roof paint
5 litres
75
76
Data sheet
FDT gravel stop profile
FDT gravel stop profile
Application
Processing
The FDT gravel stop profiles are high-quality stainless steel elements with an attractive design. The FDT gravel stop profiles consist of 60 mm or 100 mm high and 2 m long sections â&#x20AC;&#x201C; with cut-outs for unhindered rainwater drainage. Compensation of thermal elongation is provided for. The Rhepanol holders are fastened with screws and are equipped with grey or black cover tape collars. Clamps are of stainless steel and serve as a joint connector and profile stiffener over the holder.
Preparing (cutting) of the FDT gravel stop profiles can be done with standard cutting tools such as sheet shears.
Determination of the amount of required Rhenofol holders and clamps Always round up to an even amount of metres. The rounded up sum of metres +1 is the required amount of holders and clamps. In case of discontinued sections every partial section is to be considered separately.
Transportation and storage The gravel stop profiles are factory-packed in cardboard boxes with 10 profiles of 2 m length each, including the necessary holders and clamps. The boxes must be stored horizontally in a dry place.
Range of application As a barrier on gravelled roofs along the eaves or on terraced roofs with paving slabs in a fine gravel bed. Properties
Form of supply Product name
Form of supply
Package of Rhepanol gravel stop profiles, grey or black
10 units at 2 m each, incl. holders and clamps 21 units
Outstanding static properties due to special holders. Additional items as required Application instructions Fasten the holders to a solid substrate, preferably to the gutter board or directly to the concrete.
Rhepanol holders and clamps, grey or black FDT gravel stop profile, 2 m, stainless steel silver Internal corner for FDT gravel stop profile, stainless steel silver External corner for FDT gravel stop profile, stainless steel silver
RhepanolÂŽ fk
Accessories
Contact adhesive 50, Sealants, Primers, Roof paints
Product name
Properties
Range of application
Rhepanol contact adhesive 50
Synthetic-rubber-based contact adhesive.
For bonding Rhepanol to walls, roof lights and parapets.
Rhepanol adhesive 9
Acrylic-based dispersion adhesive.
For bonding Rhepanol fk to chipboards and veneer boards on roof slopes of 15°.
FDT sealant A
Solvent-free plasto-elastic one-component joint sealant (acrylic-based dispersion).
Sealing of joints, cracks with limited movement stress. Good adhesion to e.g. ceramics, render finish, brick work, concrete, lightweight concrete, natural stone.
FDT sealant S
Elastic solvent-containing joint sealant (synthetic rubber based).
For expansion and connection joints e.g. in the facade, in glass, in bathrooms and toilets and on the roof. Good adhesion to Rhepanol fk.
Rhepanol primer 1
Blue coloured polymer solution with outstanding adhesion to steel, concrete, render finish, wood and rigid PVC.
Bonding agent for Rhepanol contact adhesive 11.
Rhepanol primer 2
Transparent polymer solution with good adhesion to most nonferrous metals and special steels.
Especially reliable adhesive bond is reached, if coating with primer 2 is followed by coating with primer 1.
Rhepanol primer Precol
Black relatively high-viscous pre-coat with outstanding adhesive qualities.
Adhesive qualities on various substrates. Bonding agent for waterproof connection of Rhepanol to different materials such as concrete, brickwork, rigid PVC, metal.
Rhepanol roof paint
Special PIB-based roof paint.
For a decorative coating of all Rhepanol membranes. Colours: silver, copper, other colours on request.
77
78
Rhepanol® fk
Accessories
Gripfix strips, Sealing and cover tapes, Preformed corners, Collars
Product name
Properties
Range of application
Rhepanol sealing tape
Double-sided self-adhesive, good adhesion.
For waterproof connection of Rhepanol fk to various substrates such as concrete, coated metal sheets, in connection with Rhepanol primer Precol.
Rhepanol Gripfix strips
Highly tear-resistant polyester backing with velcro grips.
For fastening Rhepanol fk with Gripfix system. To be fastened with standard fasteners and washers.
Rhepanol fk cover tape
With self-sealing edge system, as sealing tape on Rhepanol f-backing.
For cross joints and flashings at roofing membranes Rhepanol fk.
Rhepanol fk internal corner 90°
With self-sealing edge system.
Preformed detail for sealing internal corners at roofing membranes Rhepanol fk.
Rhepanol fk internal corner 90° rapid
With self-sealing edge system.
Internal corner with integrated cover tape strips.
Rhepanol fk external corner 90°
With self-sealing edge system.
Preformed detail for sealing external corners at roofing membranes Rhepanol fk.
Rhepanol fk universal roof light corner
With self-sealing edge system.
Preformed detail for sealing roof light corners at roofing membranes Rhepanol fk.
Rhepanol fk roof light corner Universal rapid
With self-sealing edge system.
Preformed detail for sealing roof light corners, if the flashing strip projects more than 150 mm onto the roof area.
Rhepanol fk universal collar
With self-sealing edge system with Gripfix ring.
Preformed detail for built-in details and roof penetrations at roofing membranes Rhepanol fk, collar diameter 340 mm.
Rhepanol fk collar loose/ fixed flange
Up to ø 350 mm with self-sealing edge system and from ø 350 mm on with Rhepanol f.
For all standard rainwater outlets with bolt connection (6 or 8 holes).
Rhepanol fk EPDM framing ring
As set (4 framing rings).
For flashing to loose/fixed flange rainwater outlets at Rhepanol fk.
Rhepanol fk collar
With self-sealing edge system incl. Gripfix ring.
For reliable flashing of Rhepanol fk against the VarioGully. The Gripfix ring replaces contact bonding with Rhepanol contact adhesive 50.
Accessories
Rhepanol® fk
79
FDT VarioGully roof outlet
VarioGully 73
■ A proven flat roof rainwater outlet, which is regularly tested by the external testing institute LGA Bavaria.
ø 184 8 4
3 8 11
2
1
■ In warm and cold roof structures in vertical and angled version. ■ Corresponding warm roof frames are available for insulation material thicknesses from 35 to 160 mm and 160 to 240 mm1). Direct connection to all vapour control membranes or roofing membranes, or with separately preformed collar.
FDT VarioGully vertical, DN 125
FDT VarioGully angled, DN 100
without reducer
extremely flat, overall height 110 mm, with transition piece DN 70/100
Adjustabl eVariabel to any für alle thermal Dämminsulation schichtdicken von thickness 35 mm bis from 240 mm, 35 mm to ohne Zusatzteil 240 mm
without additional parts
8 4 6
5
7
2
1 262
Roof penetration 270 mm Deckenöffnung 190190 x 270x mm
DN 125 ø 125 mm
FDT VarioGully vertical, DN 125
FDT VarioGully angled, DN 125
with warm roof upstand, without reducer
ø 273
250
■ If used as an emergency outlet for draining centennial rainfall, at the VarioGully or the warm roof upstand the emergency outlet socket is installed instead of the screwed ring. 9
10 DN 100 ø 110 mm
1) Other insulation material thicknesses on request.
3
DN 125 ø 125 mm
Range of application
Roof penetration x mm 240 mm Deckenöffnung 190190 x 240
Deckenöffnung 190 mmmm Roof penetrationø Ø 190
189
■ In case of heatable VarioGully versions, the splash-proof installed – not foamed-in – heater unit is doubly protected by the two integrated safety systems (heat monitoring relay and fuse). Connection via safety transformer 220/24 V (10 W per outlet).
DN 125 ø 125 mm
185
■ Made of rigid PVC with increased impact strength, including gravel and leaf catcher. Available for installation with pipe DN 70, DN 100, DN 125 and DN 150.
FDT VarioGully vertical, DN 100 with reducer DN 125/100
1 Rainwater outlet DN 125 2 Insulating sleeve 3 Sealing ring 4 Screw ring 5 Roll ring 6 Warm roof upstand 7 Vapour control layer collar2) 8 Leaf guard 9 Roll ring DN 125 AT Reducer DN 125/100 AK Transition piece DN 70/100 2) Not part of the FDT VarioGully delivery.
DN 100 ø 110 mm
110
Properties
DN 70 ø 75 mm
4
80
Rhepanol® fk
Accessories
FDT VarioGully refurbishment, accessories for FDT VarioGully: FDT emergency outlet socket, FDT terrace grating
FDT VarioGully refurbishment ■ Ensures installation in the existing old roof without backflow. ■ Supplied complete with bolts and sealing cord. ■ To be used with old roof outlets up to DN 150, depending on the diameter of the run-in area.
5
7
8
6
4
3
2
1
Accessories for FDT VarioGully: Emergency outlet socket
10
146 166
1 Existing old roof rainwater outlet 3 FDT VarioGully refurbishment
9 Mechanical fastening
Rhepanol fk 6 Rhepanol contact adhesive 50 (alternatively Gripfix ring)
FDT terrace grating Made of aluminium with lift ring. For application on flat roofs with paving slabs or on inverted roofs. The installation height of 67 to 90 mm can be adapted to the terrace structure in steps of 3 mm. With a slab height of 90 mm or more, additional lift rings will be necessary. Each lift ring provides an additional height of 38 mm. Dimension: 200 x 200 mm
self-sealing edge system 8 FDT leaf guard
5 Roofing membrane
■ The banking height is 40 mm.
7 Rhepanol collar with
2 Existing layer build-up 4 Thermal insulation layer
■ For easy retrofitting of all FDT VarioGully rainwater outlets as emergency outlets
9
(4 per rainwater outlet) AT Sealing cord
Rhepanol® fk
Accessories
FDT RWE rainwater outlets, FDT through-wall outlet and FDT weir overflow
Product name
Dimensions
Properties/application
FDT RWE rainwater outlets
outer diameter 50 56 63 75 95 110 125 140 160
The true advantage of this built-in element is its simple installation. An ideal solution, e.g. when it comes to upgrading a roof during refurbishment. The rainwater outlet can be installed in the existing opening in no time at all.
Rhepanol Rhepanol Rhepanol Rhepanol Rhepanol Rhepanol Rhepanol Rhepanol Rhepanol
RWE RWE RWE RWE RWE RWE RWE RWE RWE
50 56 63 75 95 110 125 140 160
FDT leaf guard
The FDT leaf guard is compatible with all rainwater outlets and water spouts and can be cut to size to fit the corresponding diameter.
pipe diameter DN 100 DN 125 DN 150 DN 200
FDT lip seal Rhepanol Rhepanol Rhepanol Rhepanol
RWE RWE RWE RWE
95 95 125 160
FDT through wall outlets Rhepanol through wall outlet 50 Rhepanol through wall outlet 75 Rhepanol through wall outlet 110
FDT weir overflows Rhepanol Rhepanol Rhepanol Rhepanol
weir weir weir weir
overflow overflow overflow overflow
63 110 600 x 100 “tailor made”
DN d
The FDT lip seals are suitable for installation without backflow with all rainwater outlets as well as for installation directly into the downpipe and old rainwater outlets.
outer diameter 50 75 110
Especially suitable for draining smaller roof areas such as garages, carports, terraces, etc.
outer diameter 63 110
When installed in a sufficient number, FDT emergency overflows provide complete drainage of the rainwater from the whole roof or individual roof areas. Two types are available: a sink-type for larger roof areas (see fig.) or with a pipe for smaller roof areas (no fig.).
81
82
Rhepanol® fk
Accessories
FDT flat roof vent pipe, FDT refurbishment vent pipe, FDT cold roof vent, FDT lightning conductor collar, FDT support covering
Product name
Properties/application
FDT flat roof vent pipe DN 100
Made of rigid PVC with increased impact strength. With removable cap and bearing ring. Ready for installation with integrated collar (version for Rhepanol fk with selfsealing edge system incl. Gripfix collar).
FDT refurbishment vent pipe for DN 100
Made of rigid PVC with increased impact strength. With removable cap and ready-to-install integrated collar (Version for Rhepanol fk with selfsealing edge system incl. Gripfix collar). For connection with vents (pipe diameter DN 100) at roof refurbishment with Rhepanol.
FDT cold roof vent DN 100
Made of rigid PVC with increased impact strength. Vent cross-section of 88 cm2. Weather cap can be removed for maintenance. Ready for installation with integrated collar (version for Rhepanol fk with self-sealing edge system incl. Gripfix collar).
FDT lightning conductor collar Rhepanol
With self-sealing edge system and collar. For flashing against lightning protectors and for penetrations from 08 up to ø 53 mm.
FDT support covering
With Rhepanol collar. For flashing against penetrations from 14 mm to 50 mm. With stainless steel clamp for safety holders with Ø 140 - 160 mm. Height 120 mm.
RhepanolÂŽ fk
Accessories
FDT wall connection profiles/roof edge trims
Properties/application
FDT aluminium wall connection profile Economy
Rigid aluminium profile in punched 3 m sections. For fixing Rhepanol and Rhenofol roofing membranes at vertical surfaces. Fastening with 5 fasteners per metre, hole diameter 8 mm.
FDT aluminium wall connection profile Classic
Highly rigid aluminium profile in punched 4 m sections with slot for hooking up metal sheets. For fixing Rhepanol and Rhenofol roofing membranes at vertical surfaces. Fastening with 5 fasteners per metre, 6.2 â&#x20AC;&#x201C; 8 mm slotted holes.
FDT aluminium wall connection profile Gripfix
Rigid aluminium profile in punched 4 m sections. For fixing Rhepanol fk roofing membranes at vertical surfaces. Flashing of Rhepanol fk in the profile. Fastening with 5 fasteners per metre, hole diameter 6.5 mm.
FDT aluminium roof edge trim 110/175
Consisting of an extruded aluminium mounting rail and roll-formed stove enamel cover (colour: silver metal grey, similar to RAL 9007), as well as plastic clamps for fixing roofing membranes up to 5 mm thickness. Roofing membranes 1.5 mm must be folded back once in the clamping area.
95 95 95
25 25 25
110 110 110 175 175 175
Product name
83
84
Rhepanol速 fk
Technical Approval