AMPAC TECHNOLOGIES
Ampac Technologies is the largest independent and privately owned manufacturer and supplier of fire detection and alarm systems in Australia. Ampac specialises in the research & development, design, manufacturing, marketing and distribution for a complete range of system solutions. We supply systems for a vast variety of applications including commercial and industrial buildings, mines, prisons, hospitals, hotels and multi-residential complexes. Ampac operates Australia-wide through a network of branch offices. These offices provide sales and technical support for fire installation & EWIS contractors as well as fire discipline and electrical consulting engineers. We also work with building owners and maintenance engineers to make recommendations for future planning or budgeting.
CONTROL PANELS ZoneSense DH4 Conventional ZoneSense PLUS Conventional NEW LoopSense Intelligent FireFinder Conventional/Intelligent EMERGENCY WARNING SYSTEMS
NEW
Since its inception in 1974, Ampac has grown to become a thriving global operation with a focus on quality and exceptional customer service and support. Our passion for growing our business through the relationships we have with our customers is one that energises us. It fuels our desire to make better products, implement more efficient systems, grow our network of operations and develop our people. Ampac Technologies is ISO 9001 accredited locally and also holds overseas approvals with LPCB & UL for other key global markets. Ampac’s comprehensive range of products enables us to deliver complete solutions for fire detection and alarm systems of any size for any customer. Indeed, developing unparalleled customer partnerships drives our desire to be ‘World leaders of Innovatiove Solutions in Fire Detection and Alarm Systems’.
AUS / PAGE 2
CONTACT AMPAC
HOME
3
CONTENTS
3 6 17 28 45
EV3000 Emergency Warning System Speakers
45 53
GRAPHICS SYSTEM
58
SmartGraphicsHD
58
DETECTORS
60
Orbis Conventional XP95 Intelligent Discovery Intelligent
60 65 70
INTERFACES
77
Ampac I/O Devices Apollo I/O Devices
78 82
AUDIO VISUAL SIGNALLING
85
XP95/Discovery Sounders, Beacons & Sounder Beacons inc Bases Ampac Bells, Strobes & Remote Indicators Klaxon Sounder Beacon Electronic Sounders
86 91 98 99
ANCILLARIES
101
Power Supplies Manual Call Points Occupant Warning Systems Amplified Sound Systems Electro-Magnetic Door Holders Document Cabinets Test Equipment Batteries
102 104 109 111 115 116 118
SEARCH
ZOOM
EXIT
CONTROL PANELS
ZoneSense DH4 Conventional Control Panel The ZoneSense DH4 Control Panel is a simple and low cost 4 zone panel. It is a local alarm panel which means that it is not suitable to be directly connected to fire brigade monitoring equipment. It is an ideal fire panel for any small residential applications (not requiring brigade monitoring) or can also be used as a door holder control panel. Each of the 4 zones can be connected up to 40 x high quality commercial grade conventional fire detectors to deliver a high quality detection & alarm system. It is possible to use the ZoneSense panel in ‘Mains only’ option mode which eliminates the need to connect back up batteries. Both ABS and Metal versions are available.
• Dual Door Holder Outputs • Mains Only Mode • Low Quiescent Current • Single PCB architecture • Walk Test Facility • Class Change Input • Alert Input • Up to 40 Conventional detectors per Zone • Available in ABS (BX1) and Metal (BX10) cabinet versions
AUS / PAGE 3
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
CONTROL PANELS ZONESENSE DH4 Conventional
Power Supply Mains Supply voltage Nom. Operating voltage Power Supply Current Quiescent Current Operating Temperature Relative Humidity
ZoneSense DH4 – Metal Cabinet
ZoneSense DH4 – ABS Cabinet
Zone Detection Circuit No of Zones Zone Monitoring Zone Quiescent Current No of Detectors/Circuits End Of Line (EOL) Max Cable Length
Outputs Available Alarm Outputs (monitored)
Auxiliary DC Output Miscellaneous Features Class Change Input Alert Input Battery Monitoring
Non-Latching, switched -ve Non-Latching, switched -ve 4 Way DIP switch array (factory set to “OFF”)
Fire Output Relay (voltage free) Fault Output Relay (voltage free)
CONTACT AMPAC
HOME
Four (4) x 2-wire system Open and Short circuit 4mA, 10uF EOL 40 (max) 10uF EOL 3km (Based on cable resistive and capacitive values of 50Ω and 1uF respectively)
Open Collector, 250mA (2 O/P’s available) 10KΩ EOL Open Collector, 250mA (2 O/P’s available) 10KΩ EOL NO, C, NC Contact rating: 1A @ 30VDC NO, C, NC Contact rating: 1A @ 30VDC 150mA @ 24VDC
Door Holder outputs (monitored)
AUS / PAGE 4
204 – 264 VAC @ 47 – 63Hz 27 VDC 1.6 A (max) 20 mA (without Door Holder) -5° to +55° C (no icing) 25% - 75% (non condensing)
CONTENTS
SEARCH
ZOOM
EXIT
CONTROL PANELS ZONESENSE DH4 Conventional
Mechanical Material ABS Cabinet Metal Cabinet Finish ABS Cabinet Metal Cabinet ABS (BX1) Cabinet Metal Cabinet (BX10) Packed Weight Packed excluding batteries ABS Metal ZoneSense DH4 – Metal Cabinet
ZoneSense DH4 – ABS Cabinet
ABS/Blend High Impact 1.2mm Mild Steel ABS Light Grey Metal Oyster Matt Ripple H 300mm x W 360mm x D 100mm H 300mm x W 360mm x D 100mm H 310mm x W 500mm x D 110mm 3kg 5.2kg
ZoneSense DH4 ABS (BX1) excl Batteries ZoneSense DH4 METAL (BX10) excl Batteries Metal BX10 Surround
2250-4200 2250-4250 ENC3016-A
Note: Gyprock fixing (toggle brackets) are available to flush fit any Ampac ABS enclosure into a wall cavity Item No (4210-0002 & 4210-0003 )
AUS / PAGE 5
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
CONTROL PANELS
ZoneSense PLUS Conventional Control Panel The Ampac ZoneSense PLUS Fire Alarm Control Panel is a versatile four or eight zone conventional panel. The user friendly navigation system provides simple operation during an emergency while also enabling complex cause and effect programming to be undertaken. A range of modular panel add-on kits allows the panel to be professionally tailored to the requirements of each installation. This means small conventional panels can now be used in a wider range of applications. ZoneSense PLUS offers you complete control. The panel can be easily upgraded and programmed on site. ZoneSense PLUS is approved to AS4428 and is available in ABS (BX1) or metal cabinets (BX20) with either four (4) or eight (8) zone conventional detection circuits.
• Available in 4 Zone or 8 Zone Panels • Up to 40 Conventional detectors per zone • RS485 port supports a range of Add-on modules • Available in ABS (BX1) and Metal (BX20) cabinet versions • Complies with AS4428
AUS / PAGE 6
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
CONTROL PANELS ZONESENSE PLUS Conventional
ZoneSense PLUS – ABS and Metal Power Supply Mains Supply voltage Nom. Operating voltage Power Supply Current Quiescent Current
ZoneSense PLUS – ABS Cabinet
AUS / PAGE 7
CONTACT AMPAC
ZoneSense PLUS – Metal Cabinet
HOME
Zone Detection Circuit No of Zones Zone Monitoring Zone Quiescent Current No of Detectors/Circuits Eon Of Line Value (EOL) Max Cable Length
204 – 264 VAC @ 47 – 63Hz 27 VDC 2 A (max) 40.5 mA (min)
Four (4) or Eight (8) x 2-wire system Open and Short circuit 4mA, 10uF EOL 40 (max) 3K3Ω (default), 4K7Ω, 6K8Ω, 10KΩ and 10uF (Optional) 3km (Based on cable resistive and capacitive values of 50Ω and 1uF respectively)
Outputs Comms Output EXT Bell Output (monitored) Warning Sys Output (monitored) ACF Output (monitored) ASE Output (monitored) Reset/Buzzer Fire Alarm Output Relay (voltage free) Fault Output Relay (voltage free) Auxiliary DC Output (monitored)
RS485 (4 and 8 zone only) 1A (max) 10KΩ EOL 1A (max) 10KΩ EOL 1A (max) 10KΩ EOL 1A (max) 10KΩ EOL Output Open Collector, 40mA 15sec pulse NO, C, NC. Contact rating: 1A @ 30VDC NO, C, NC. Contact rating: 1A @ 30VDC 500mA @ 24VDC10KΩ EOL
Miscellaneous MCP input Fault input Door Switch
Non-Latching, switched –ve Non-Latching, switched –ve Non-Latching, switched –ve
Environmental Operating Temperature Relative Humidity
-5° to +55° C (no icing) 25% - 75% (non condensing)
CONTENTS
SEARCH
ZOOM
EXIT
CONTROL PANELS ZONESENSE PLUS Conventional
ZoneSense PLUS – ABS Certain ABS versions also come optionally with the provision of extra window space. These windows are to allow for space to add ZoneSense Plus Add on Modules into the panel fascia. Mechanical Material Finish Dimensions Weight packed excluding Batteries
ZoneSense PLUS – ABS Cabinet
ZoneSense PLUS – ABS Cabinet with Windows
ABS/Blend High Impact ABS Light Grey 300mm (H) x 360mm (W) x 100mm (D) 3kg
ZoneSense PLUS Control Panel 4 Zone ABS (BX1) 8 Zone ABS (BX1) 4 Zone ABS (BX1) with windows 8 Zone ABS (BX1) with windows ABS Joiner Moulding Ancillary Cabinet ABS (BX1)
2550-1100 2550-1200 2550-2100 2550-2200 ENC1851-A 2510-9001
Note: Gyprock fixing (toggle brackets) are available to flush fit any Ampac ABS enclosure into a wall cavity Item No (4210-0002 & 4210-0003 )
ZoneSense PLUS – ABS Ancillary Cabinet
AUS / PAGE 8
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
CONTROL PANELS ZONESENSE PLUS Conventional
ZoneSense PLUS – Metal A diverse range of factory pre assembled ZoneSense Plus products are made available for the installers convenience. These include a range with occupant warning system pre fitted and or Agent Release (Gas) module fitted. It is also possible to fit ZoneSense Plus “add on modules” after purchasing a standard ZoneSense Plus panel as long as there is space provision on the enclosure to fit the module. Mechanical Material Finish Dimensions Weight packed excluding Batteries
1.2mm Mild Steel Metal Oyster Matt Ripple ZoneSense Plus Metal: 500(H) x 405(W) x 145(D) mm Metal Ancillary Cabinet: 250(H) x 405(W) x 145(D) mm ZoneSense Plus Metal: 8.5kg Metal Ancillary Cabinet: 2kg
ZoneSense PLUS Control Panel 4 Zone Metal (BX20) with MCP 8 Zone Metal (BX20) with MCP 4 Zone Metal (BX20) with Agent Release 8 Zone Metal (BX20) with Agent Release 4 Zone EV20 OWS Fitted 8 Zone EV20 OWS Fitted 4 Zone EV40 OWS Fitted 8 Zone EV40 OWS Fitted Ancillary Cabinet Metal (BX20) Surround for Metal Cabinet only Surround for Metal & Ancillary Cabinet
ZoneSense PLUS – Metal Cabinet
2550-0100 2550-0200 2550-0151 2550-0252 2550-0120 2550-0220 2550-0140 2550-0240 8510-9001 ENC1798-A ENC1797-A
ZoneSense PLUS – Rack Mount For added flexibility ZoneSense Plus Rack versions are now available. This allows a ZoneSense Plus Fire indicator panel to be easily integrated in a rack arrangement with other larger models of Ampac warning systems ZoneSense PLUS Control Panel 4 Zone Combo Rack Mount 8 Zone Combo Rack Mount
AUS / PAGE 9
CONTACT AMPAC
HOME
CONTENTS
SEARCH
2553-0400 2553-0800
ZOOM
EXIT
CONTROL PANELS ZONESENSE PLUS Conventional – Add Ons
Input Board • • • • •
Provides inputs for sprinkler pumps, tanks, valves, shutdowns, etc 16 inputs per board Inputs map to relays or indicators Programmed via the ZoneSense PLUS front panel Max 1 per ZoneSense PLUS
Voltage Quiescent current Max current Output rating Operating temperature Relative humidity Weight
24 VDC 2.6 mA 45 mA 0.5 amp at 24 VDC -5°C to +55°C (no icing) 0 to 95% (non condensing) 120 grams
Input Board
4310-0040
Relay Board • • • • • •
Provides volt free change over contacts 8 relay outputs per board Programmed via the ZoneSense PLUS front panel Max 1 per ZoneSense PLUS system Remote version available – DIN Mount chassis Remote version communication via RS485 serial link
Voltage Quiescent current Max current Relay contact rating Operating temperature Relative humidity Weight
24 VDC 2.4 mA 80 mA 1 amp at 24 VDC -5°C to +55°C (no icing) 0 to 95% (non condensing) 130 grams
Relay Board Relay Board (Remote)
AUS / PAGE 10
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
4310-0050 4310-0055
EXIT
CONTROL PANELS ZONESENSE PLUS Conventional – Add Ons
Sounder Board • • •
Provides 8 monitored switched 24 VDC outputs per board Programmed via the ZoneSense PLUS front panel Max 1 per ZoneSense PLUS
Voltage Quiescent current Max current Output rating (ea) Operating temperature Relative humidity Weight
24 VDC 5.6 mA 26 mA 500 mA at 24 VDC -5°C to +55°C (no icing) 0 to 95% (non condensing) 100 grams
Sounder Board
4310-0060
Fire Brigade Board • Provides common outputs for connection to fire brigade signalling equipment • 5 outputs – Alarm, Fault, Isolate, Battery Fail and 2nd Alarm • Programmed via the ZoneSense PLUS front panel • Max 1 per ZoneSense PLUS
Voltage Quiescent current Max current Output rating Operating temperature Relative humidity Weight
24 VDC 9 mA 52 mA 1 amp at 24 VDC -5°C to +55°C (no icing) 0 to 95% (non condensing) 110 grams
Fire Brigade Board
AUS / PAGE 11
CONTACT AMPAC
HOME
CONTENTS
SEARCH
4310-0070
ZOOM
EXIT
CONTROL PANELS ZONESENSE PLUS Conventional – Add Ons
Fire Fan Module • Controls and monitors fire fans, dampers, sprinkler pumps etc. • 4 controls per module • Separate start and stop output per control • 3 status inputs per control • Labels can be modified on site • Programmed via the FACP front panel • Max 1 per ZoneSense PLUS • Location or title descriptor label
Voltage Quiescent current Max current Relay contact rating Operating temperature Relative Humidity Weight
24 VDC 13.5 mA 50 mA 3 amp at 24 VDC -5°C to 55°C (no icing) 0 to 95% (non condensing) 230 grams
Fire Fan Module
4310-0021
Switch/Indicator Card • Controls and monitors solenoid test switches, manual shutdowns etc • Eight (8) push on / push off switches per card • Switches map to relays – requires relay board (Order Code: 4310-0050) • One (1) status indicator per switch – requires input board (Order Code: 4310-0040) • Labels can be modified on site • Programmed via the FACP front panel • Max 1 per ZoneSense PLUS • Location or title descriptor label
Voltage Quiescent current Max current Operating temperature Relative Humidity Weight
24 VDC 3.6 mA 8 mA -5°C to 55°C (no icing) 0 to 95% (non condensing) 100 grams
Switch/Indicator Card
AUS / PAGE 12
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
4310-0030
EXIT
CONTROL PANELS ZONESENSE PLUS Conventional – Add Ons
Agent Release Module • Compliance with AS4214 • Controls & Monitors Agent release system • Outputs for warning signs & activation devices • Inputs for signals from pressure switches & valves • Serial connection to Agent release (LCS) Local control Station • Programmed via the FACP front panel • Maximum is 1 per ZoneSense PLUS • Location or title descriptor label
Voltage Quiescent current Max current Relay contact rating Operating temperature Relative Humidity Weight
24 VDC 28.5 mA 1.5 A 1 amp at 24 VDC -5°C to 55°C (no icing) 0 to 95% (non condensing) 250 grams
Agent Release Module
4310-0011
Agent Release – Local Control Station • Remote Agent release LCS • Complies with AS4214 • For Use only with Agent release Module 4310-0011 • Double Action manual Agent release facility • Toggle between initial & reserve agent • Can install up to 8 x LCSs per panel
Material Finish Dimension Weight Operating Voltage Quiescent Current Monitored Inputs Manual Release Stage 1 & 2 System Inoperative Gas Fired Comms Output
1.2mm steel for Back Box Oyster matt ripple 233H x 186W x 47D mm 860 grams 27VDC 40.5mA Pressure Switch; Low Pressure Switch; Interlock 2A @ 27VDC (Current Limited) Switched 1A @ 27VDC 1A @ 27VDC 1A @ 27VDC RS485
Local Control Station
AUS / PAGE 13
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
4310-0019
EXIT
CONTROL PANELS
ZoneSense PLUS AR Agent Release Panel The ZoneSense PLUS AR (Agent Release) Panel is a dedicated panel for agent release systems. Housed in a metal cabinet, the ZoneSense PLUS AR is available in either four (4) or eight (8) zones. Based on a ZoneSense PLUS Fire Alarm Control Panel (FACP), the AR version is fitted with an Agent Release Panel Add-on (control card and termination board) and a dual action yellow manual call point as standard. The Agent Release panel add-on option is factory set.
• Dedicated Agent Release system - purpose built with a host of ancillary products to suit • Comprehensive system status – the AR panel includes a number of system status indicators that facilitates ease of operation and maintenance • Local Control Station with control and indication – mimics full status of the Agent Release panel. An outdoor version of this product is available • User interface and operation based around Industry Fire Emergency procedures – ensures that the system installed is intuitive and easy to use • Dual action Manual Call Point – the yellow MCP is a break glass type and requires a dual action to be activated i.e. lift the protective transparent cover and break the glass • Agent Release Panel is compliant with AS4214
AUS / PAGE 14
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
CONTROL PANELS ZoneSense PLUS AR
Fire Alarm Control Panel Operating Voltage Quiescent Current Power Supply Ext Bell Output Warning Sys Output ACF Output ASE Output Fire Alarm Output Fault Output Aux DC Output Reset/Buzzer Communications Output End-Of-Line Values Material Finish Dimension Weight (excluding batteries) Agent Release System Pressure Switch Input Low Pressure Switch Input Interlock Input Gas Fired Output
ZoneSense PLUS AR
System Inoperative Output Stage 1 Output Stage 2 Output Release Initial Agent Output Release Reserve Agent Output
23 to 28 VDC 37 mA (minimum) 27VDC (nominal) @ 2Amps 1A (max) – monitored 1A (max) – monitored 1A (max) – monitored 1A (max) – monitored Volt free 1A @ 24 VDC Open Collector Output Volt free 1A @ 24 VDC Open Collector Output 500mA @ 24 VDC – monitored Open Collector Output RS485 3k3 (fitted as standard), 4k7, 6k8, or 10k ohms, 10μ Farad 1.2 mm mild steel Oyster matt ripple Metal Cabinet: 500H x 405W x 145D mm Metal ancillary cabinet: 250H x 405W x 145D mm 8kg
Monitored Input Monitored Input Monitored Input Volt Free Changeover 1A@24VDC Volt Free Changeover 1A@24VDC Monitored Monitored Monitored current limited 2A max Monitored current limited 2A max
ZoneSense PLUS AR 4 Zone ZoneSense PLUS AR 8 Zone
AUS / PAGE 15
CONTACT AMPAC
HOME
CONTENTS
SEARCH
2550-0151 2550-0252
ZOOM
EXIT
CONTROL PANELS ZoneSense PLUS AR – Ancillary Products
Agent Release Warning Signs
IP50 Model
The AR panel supports a 2-wire connection to warning signs. The 2-wire connection supports both single or dual stage signs. The latter is possible because of the voltage reverse technology adopted by the AR panel. Multiple warning signs may be connected to the AR panel. The connection will be in a ‘daisy chain’ configuration with the last warning sign fitted with an End-Of-Line (EOL) resistor. The EOL resistor facilitates the monitoring of the warning sign circuit. A maximum of 6 warning signs may be fitted to an AR panel. An on-board buzzer fitted to every sign provides audible warning. However in the event AS1670.4 audible warning tones are required, external electronic sounders may be connected directly to each warning sign. An external switch may be connected to the sign to mute audible warning.
IP65 Model
AUS / PAGE 16
CONTACT AMPAC
HOME
CONTENTS
ACP-04 Manual Call Point Yellow ACP-04 Manual Call Point Hinged Cover
213-0061 213-0057
IP50 SIGNS Warning sign back box (IP50) no fascia 207-0050 “Extinguishing System Inoperative” complete IP50 207-0051 Special wording fascia only 207-0052 “Fire Alarm, Do Not Enter” fascia only 207-0053 “Fire Alarm, Evacuate Area” fascia only 207-0054 “Do Not Enter, Gas Discharged” fascia only 207-0055 “Fire Door CLosing” fascia only 207-0056 “Do Not Enter” fascia only 207-0057 IP65 SIGNS Warning sign back box (IP65) no fascia 207-0060 “Extinguishing System Inoperative” complete IP65 207-0061 Special wording fascia only 207-0062 “Fire Alarm, Do Not Enter” fascia only 207-0063 “Fire Alarm, Evacuate Area” fascia only 207-0064 “Do Not Enter, Gas Discharged” fascia only 207-0065 “Fire Door Closing” fascia only 207-0066 “Do Not Enter” fascia only 207-0067 SOUNDERS Vantage Sounder (Red/White) 205-0062/63 Vantage Combi (Red/White) 205-0066/67
SEARCH
ZOOM
EXIT
CONTROL PANELS
NEW
LoopSense Intelligent Control Panel LoopSense is an Intelligent Analogue Addressable Fire Alarm Control Panel. Available in one or two loops, the LoopSense comes packed with options and features that facilitate flexibility, ease of installation and commissioning.
• Clear back-lit 240 x64 graphic LCD • 500mA loop current • Advanced balanced loop design for noise rejection • Auto learn facility • Supports extensive range of Add Ons, including the SmartTerminal Repeater • User friendly Loopmaster programming software tool • Laptop connection using USB2.0 or RS232 serial port • Complies to AS7240-2:2004, AS7240-4:2004, and AS4428-3:2010 -ActivFire ® listed
AUS / PAGE 17
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
CONTROL PANELS LOOPSENSE Intelligent
NEW LoopSense – SP1X Cabinet
NEW LoopSense – SP8X Cabinet
SP1X
SP8X
Power Supply (General) Output Voltage Battery Type (maximum) Battery Discharged Cut Off Voltage
27.5VDC +/- 0.1VDC 26Ah 21VDC
27.5VDC +/- 0.1VDC 40.0Ah 21VDC
Base Panel Quiescent Current 1 Loop Panel 2 Loop Panel
115mA 135mA
115mA 135mA
Loop Loop current Detectors/Devices per Loop Cabling Requirements Fault supervision Protocol
500mA max 126 max 2 core 1.5 to 2.5mm O/C, S/C, overcurrent XP95, Discovery
500mA max 126 max 2 core 1.5 to 2.5mm O/C, S/C, overcurrent XP95, Discovery
4 x supervised/programmable 24VDC @ 500mA max 3 x programmable Voltage free 24VDC @ 1A 2 x programmable – 30mA 2 x protected/programmable 24VDC @ 500mA
4 x supervised/programmable 24VDC @ 500mA max 3 x programmable Voltage free 24VDC @ 1A 2 x programmable – 30mA 2 x protected/programmable 24VDC @ 500mA
Inputs Supervised
4 x O/C, S/C, 10K EOL
4 x O/C, S/C, 10K EOL
Communications Port Internal to LoopSense External to LoopSense Printer port PC Interfacing
RS485 RS485 RS232 or Parallel RS232 or USB 2.0
RS485 RS485 RS232 or Parallel RS232 or USB 2.0
Outputs Alarm Sounder Outputs Relay outputs Open Collector Output Auxiliary VDC
AUS / PAGE 18
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
CONTROL PANELS LOOPSENSE Intelligent
NEW LoopSense – SP1X Cabinet
NEW LoopSense –SP8X Cabinet
SP1X
SP8X
Electrical Power Supply Input Voltage Protection Output Current Charger Current
3A PSU version 204 - 264VAC 3Amp M205 3Amps 600mA
6A PSU version 204 - 264VAC 5Amp M205 4Amps 1000mA
Environmental Operating temperature Relative humidity IP rating
-5°C to +55°C (no icing) 25% to 75% (non condensing) IP30
-5°C to +55°C (no icing) 25% to 75% (non condensing) IP30
Mechanical Material Finish Dimensions Weight
1.2mm steel Surf Mist Ripple 505H x 405W x 150Dmm 9kg
1.2mm steel Surf Mist Ripple 845H x 515W x 175Dmm 15kg
NEW LoopSense Intelligent Control Panel LoopSense, 1 Loop. 3A SP1X Enclose LoopSense, 2 Loop. 3A SP1X Enclosure LoopSense, 1 Loop. 6A SP8X Enclosure LoopSense, 2 Loop. 6A SP8X Enclosure
8251-0110 8251-0210 8251-0113 8251-0213
Flush Mount Surround for SP1X Flush Mount Surround for SP8X 2nd Loop Activation Key
4210-0042 4210-0044 8210-0001
*Approvals: AS7240-2:2004, AS7240-4:2004, AS4428-3:2010
AUS / PAGE 19
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
CONTROL PANELS LOOPSENSE Intelligent
Dot Matrix Panel Printer • The dot matrix printer provides hardcopy activity report • Alarms, faults, isolates and system logs may be printed • 3 colour status LED • Self test mode • Easy maintenance for replaceable ribbon cassette and paper roll
Voltage Quiescent current Character size Operating temperature Relative humidity Weight
5 VDC 1A @ 5 VDC 5 x 7 dots -5°C to +55°C (no icing) 25 to 95% (non condensing) 380 grams
Dot Matrix Panel Printer Paper – 10 rolls Ribbon
159-0110 MIS1981 MIS1982
SmartTerminal Repeater The SmartTerminal Repeater is an LCD annunciator designed to remotely display the status and provide control of the LoopSense Fire Alarm Control Panel. • Connects to a Communication Driver Board inside the LoopSense Control Panel • 4 line by 40 character LCD with backlight and navigation keys UP/ DOWN keys allow the SmartTerminal to be used for FACP operation and interrogation • Buzzer and system Reset • Flush or surface mountable enclosure • Controls have tactile and audible feedback of operation • All terminals cater for 2.5mm cables • Stand alone power supply capabilities • Flush mount kit available (Gyprock toggel fixings) • Max 30 Per LoopSense
AUS / PAGE 20
CONTACT AMPAC
HOME
CONTENTS
Voltage Quiescent current (backlight/buzzer off ) Max current (backlight/buzzer on) Max distance from main panel Auxiliary output (monitored) Operating temperature Relative humidity Size SmartTerminal Repeater SmartTerminal Slimline Repeater Weight SmartTerminal Repeater SmartTerminal Slimline Repeater
24 VDC 12.4 mA 44 mA 1.2 km 27 VDC 500 mA -5°C to +55°C (no icing) 25 to 95% (non condensing) 300H x 360W x 100Dmm 195H x 324W x 52Dmm 2.5 kg 1 kg
NEW LoopSense SmartTerminal Repeaters SmartTerminal wthout PSU SmartTerminal Repeater with 2 Amp PSU SmartTerminal Slim Line Repeater without PSU
4350-0004 4350-0005 4350-0006
Mounting Kit (Flush Mount)
4210-0002
SEARCH
ZOOM
EXIT
CONTROL PANELS LOOPSENSE Intelligent- Add Ons
Relay Board • • • •
Voltage 24 VDC Quiescent current 2.4 mA Max current 80 mA Relay contact rating 1 amp at 24 VDC Operating temperature -5°C to +55°C (no icing) Relative humidity 0 to 95% (non condensing) Weight 130 grams System Capacity: LoopSense 15 Maximum ZoneSense Plus 1 Maximum
Provides volt free change over contacts 8 relay outputs per board Remote version available – DIN Mount chassis Remote version communication via RS485 serial link
Relay Board Relay Board (Remote)
4310-0050 4310-0055
Sounder Board •
Provides 8 monitored switched 24 VDC outputs per board
Voltage 24 VDC Quiescent current 5.6 mA Output rating (ea) 500 mA at 24 VDC Operating temperature -5°C to +55°C (no icing) Relative humidity 0 to 95% (non condensing) Weight 100 grams System Capacity: LoopSense 15 Maximum ZoneSense Plus 1 Maximum Sounder Board
AUS / PAGE 21
CONTACT AMPAC
HOME
CONTENTS
SEARCH
4310-0060
ZOOM
EXIT
CONTROL PANELS LOOPSENSE Intelligent- Add Ons
Fire Brigade Board • Provides common outputs for connection to fire brigade signalling equipment • 5 outputs – Alarm, Fault, Isolate, Battery Fail and 2nd Alarm
Voltage 24 VDC Quiescent current 9 mA Max current 52 mA Output rating 1 amp at 24 VDC Operating temperature -5°C to +55°C (no icing) Relative humidity 0 to 95% (non condensing) Weight 110 grams System Capacity: LoopSense 1 Maximum ZoneSense Plus 1 Maximum Fire Brigade Board
4310-0070
Input Board • • • •
Provides inputs for sprinkler pumps, tanks, valves, shutdowns, etc 16 inputs per board Inputs map to relays or indicators Programmed via the LoopMaster
Voltage 24 VDC Quiescent current 2.6 mA Max current 45 mA Output rating 0.5 amp at 24 VDC Operating temperature -5°C to +55°C (no icing) Relative humidity 0 to 95% (non condensing) Weight 120 grams System Capacity LoopSense 15 Maximum ZoneSense Plus 1 Maximum Input Board
AUS / PAGE 22
CONTACT AMPAC
HOME
CONTENTS
SEARCH
4310-0040
ZOOM
EXIT
CONTROL PANELS LOOPSENSE Intelligent- Add Ons NEW
8 Zone Conventional Board • Supports up to eight conventional zones • Selectable end of line device 3K3, 4K7, 6K8, 10K or 10µF capacitor • Supports head removal requirement on each zone • Supports up to 40 conventional devices per zone circuit (ORBIS) • Programmable latching and non-latching (self-resetting) input on each zone circuit
Voltage Quiescent current
24 VDC 15mA (including capacitive EOL current) plus device current Alarm current 43mA (one circuit in alarm) Operating temperature -5°C to +55°C (no icing) Relative humidity 0 to 95% (non condensing) Size 72.5 x 155mm Weight 120 grams System Capacity: LoopSense 15 Maximum 8 Zone Conventional Board
4310-0082
NEW
32 Zone Indicator Card • • • • •
Provides 32 Zone LED’s capable of indicating zone Fire, Disabled, Fault and Dependency B. Suitable for use with the FireFinder range of FACP’s Suitable for use with LoopSense FACP Customisable zone identification label Fully programmable via LoopMaster
Voltage 27 VDC Quiescent current 3.6 mA Max current 8mA Output rating 0.5 amp at 24 VDC Operating temperature -5°C to +55°C (no icing) Relative humidity 0 to 95% (non condensing) Weight 100 grams System Capacity: LoopSense 15 Maximum 32 Zone Indicator Card Slip In Label
AUS / PAGE 23
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
4310-0086 LAB 3001
EXIT
CONTROL PANELS LOOPSENSE Intelligent- Add Ons
Switch/Indicator Card • 8 x Push Button On / Off switches • 8 x LED display of the On / Off condition • Controls and Monitors solenoid test switches, manual shutdowns and etc • Programmable via the ZoneSense PLUS front panel • Programmable via ConfigManager for the FireFinder range of panels • Programmable via LoopMaster for the LoopSense range of panels
Voltage 24 VDC Quiescent current 3.6 mA Max current 8 mA Operating temperature -5°C to 55°C (no icing) Relative Humidity 0 to 95% (non condensing) Weight 100 grams System Capacity: FireFinder 15 Maximum LoopSense 15 Maximum ZoneSense Plus 1 Maximum Switch/Indicator Card Slip in Label
AUS / PAGE 24
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
4310-0030 LAB 1483
EXIT
CONTROL PANELS LOOPSENSE Intelligent- Add Ons
Fire Fan Module Each Fire Fan Module houses the control and indication of up to four (4) fire fans and a single control/indication for plant trip reset. A hard-wired version of a fire fan module consists of a Fire Fan Control Card and Termination Board. Field wiring is terminated to the termination board at the FACP. A loop-driven version is also available and in this configuration only the Fire Fan Control Card would be required. Field wiring will terminate to address input/output devices that operate on the addressable loop. • Four (4) Controls per Module • Status indication for Run / Fault / Stop • Controls for ON / Auto / Off • Audible and visual feedback of button press • Built in Plant Trip Reset • Supports 3, 4 and 5 Wire Connections • Available in Hardware or loop driven versions • Communicates with FACP via RS485 communication port • Where applicable all terminals cater for 2.5mm² cables
AUS / PAGE 25
CONTACT AMPAC
HOME
CONTENTS
Operating Voltage Dimensions: Controller Card Termination Board Contact Rating Approval System Capacity: FireFinder LoopSense ZoneSense Plus
27VDC Fits standard Panel Cut-Out 155mm x 72mm 1 amp @ 24VDC AS1668 15 Maximum 15 Maximum 1 Maximum
Hard Wired Loop Driven Slip in Label Template
SEARCH
ZOOM
4310-0021 4310-0071 LAB1486
EXIT
CONTROL PANELS LOOPSENSE Intelligent- Add Ons
Agent Release Module • Compliance with AS4214 • Controls & Monitors Agent release system • Outputs for warning signs & activation devices • Inputs for signals from pressure switches & valves • Serial connection to Agent release (LCS) Local control Station • Programmed via the FACP front panel • Maximum is 1 per FACP • Location or title descriptor label
Voltage Quiescent current Max current Relay contact rating Operating temperature Relative Humidity Weight
24 VDC 28.5 mA 1.5 A 1 amp at 24 VDC -5°C to 55°C (no icing) 0 to 95% (non condensing) 250 grams
System Capacity FireFinder 8 Max LoopSense 8 Max ZoneSense PLUS 1 Max Agent Release Module
4310-0011
Agent Release – Local Control Station • Remote Agent release LCS • Complies with AS4214 • For Use only with Agent release Module 4310-0011 • Double Action manual Agent release facility • Toggle between initial & reserve agent • Can install up to 8 x LCSs per panel
Material Finish Dimension Weight Operating Voltage Quiescent Current Monitored Inputs Manual Release Stage 1 & 2 System Inoperative Gas Fired Comms Output
1.2mm steel for Back Box Oyster matt ripple 233H x 186W x 47D mm 860 grams 27VDC 40.5mA Pressure Switch; Low Pressure Switch; Interlock 2A @ 27VDC (Current Limited) Switched 1A @ 27VDC 1A @ 27VDC 1A @ 27VDC RS485
Local Control Station
AUS / PAGE 26
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
4310-0019
EXIT
CONTROL PANELS LoopSense Intelligent – Ancillary Products
Agent Release Warning Signs The AR panel supports a 2-wire connection to warning signs. The 2-wire connection supports both single or dual stage signs. The latter is possible because of the voltage reverse technology adopted by the AR panel. Multiple warning signs may be connected to the AR panel. The connection will be in a ‘daisy chain’ configuration with the last warning sign fitted with an End-Of-Line (EOL) resistor. The EOL resistor facilitates the monitoring of the warning sign circuit. A maximum of 6 warning signs may be fitted to an AR panel. An on-board buzzer fitted to every sign provides audible warning. However in the event AS1670.4 audible warning tones are required, external electronic sounders may be connected directly to each warning sign. An external switch may be connected to the sign to mute audible warning.
AUS / PAGE 27
CONTACT AMPAC
HOME
CONTENTS
ACP-04 Manual Call Point Yellow ACP-04 Manual Call Point Hinged Cover
213-0061 213-0057
IP50 SIGNS Warning sign back box (IP50) no fascia 207-0050 “Extinguishing System Inoperative” complete IP50 207-0051 Special wording fascia only 207-0052 “Fire Alarm, Do Not Enter” fascia only 207-0053 “Fire Alarm, Evacuate Area” fascia only 207-0054 “Do Not Enter, Gas Discharged” fascia only 207-0055 “Fire Door CLosing” fascia only 207-0056 “Do Not Enter” fascia only 207-0057 IP65 SIGNS Warning sign back box (IP65) no fascia 207-0060 “Extinguishing System Inoperative” complete IP65 207-0061 Special wording fascia only 207-0062 “Fire Alarm, Do Not Enter” fascia only 207-0063 “Fire Alarm, Evacuate Area” fascia only 207-0064 “Do Not Enter, Gas Discharged” fascia only 207-0065 “Fire Door Closing” fascia only 207-0066 “Do Not Enter” fascia only 207-0067 SOUNDERS Vantage Sounder (Red/White) 205-0062/63 Vantage Combi (Red/White) 205-0066/67
SEARCH
ZOOM
EXIT
CONTROL PANELS
FireFinder Conventional / Intelligent Fire Alarm Control Panel FireFinder is a state of the art multi microprocessor controlled Intelligent Fire Alarm Control Panel. Modular in design, the FireFinder provides flexibility and versatility that can be configured to operate with both intelligent analogue addressable and conventional devices in the one system. Available in single loop or multiple loop configurations, the FireFinder supports the leading Apollo XP95 and Discovery detector protocols. The Ampac ConfigManager software tools provide a powerful combination with the FireFinder to configure the system operational and functional characteristics of an installation. Enhanced networking capabilities offer the user extended applications with FireFinder incorporating a Master/ Slave Fire control panel arrangement, true Peer to Peer systems, data gathering panels and SmartGraphics a PC based application for the supervision, monitoring and control of larger fire management systems. • • • • • • • • • • • •
Clear back-lit 40 character 8 line LCD display Programming options via the front panel or laptop computer Remote system interrogation and diagnostics Extensive Alarm Management resources Self Auto Learn capabilities Day Night sensitivity settings Versatile multi processor architecture Event log and printer options SPOT – Single Person Operation Test Flexible modular expansion and panel Add Ons Optional 32, 64, 96 & 128 zone indicators SmartTerminal repeater options
AUS / PAGE 28
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
CONTROL PANELS FIREFINDER Conventional / Intelligent AS4428
FireFinder SP1X Conventional / Intelligent Control Panel
FireFinder SP8X Conventional / Intelligent Control Panel
Electrical Power Supply Output Voltage Quiescent Current Battery Capacity
85 to 264 VAC 27 VDC 450mA (min) 12 Ah (min)
Outputs Bell 1 (monitored) Bell 2 (monitored) Auxiliary (monitored) Auxiliary (unmonitored) EWS (monitored) EWS (unmonitored) Fault Isolate Alarm Valve Monitor Battery Fail
Switched Switched Switched Volt free Switched Volt free Volt free Volt free Volt free Volt free Volt free
Mechanical Materials / Finish Construction Dimensions
1.2mm steel / Arch White powder coat Modular SP1X 500H x 405W x 145D mm SP8X 840H x 515W x 170D mm SP16X 1200H x 625W x 240D mm 10U 700H x 625W x 240D mm 16U 1200H x 700W x 350D mm 29U 1800H x 700W x 350D mm SP1X Anc Cab 250H x 405W x 145D mm SP8X Anc Cab 418H x 515W x 170D mm SP1X 10 kg SP8X 20 kg SP16X 35 kg 10U 40 kg 16U 90 kg 29U 130 kg SP1X Anc Cab 3 kg SP8X Anc Cab 5 kg
Weight
AUS / PAGE 29
CONTACT AMPAC
HOME
CONTENTS
24 VDC 2A 24 VDC 2A 24 VDC 2A 1A @ 24 VDC 24 VDC 2A 1A @ 24 VDC 1A @ 24 VDC 1A @ 24 VDC 1A @ 24 VDC 1A @ 24 VDC 1A @ 24 VDC
SEARCH
ZOOM
EXIT
CONTROL PANELS FIREFINDER Conventional AS4428
FireFinder SP1X Conventional Control Panel
FireFinder SP8X Conventional Control Panel
FireFinder Conventional Control Panel SP1X 16 Zone SP1X 16 Zone EV20+Mic 5.6A SP1X 16 Zone EV40+Mic 5.6A SP8X 16 Zone 5.6A SP8X 16 Zone EV40+Mic 5.6A SP8X 16 Zone EV60+Mic 5.6A SP8X 16 Zone EV120+Mic 18A SP16X 16 Zone 5.6A 10U 16 Zone 5.6A 16U 16 Zone 5.6A 29U 16 Zone 5.6A SP1X Ancillary Cabinet SP8X Ancillary Cabinet SP1X Surround SP8X Surround SP16X Surround SP1X+Ancillary Cabinet Surround SP8X+Ancillary Cabinet Surround
8550-1150 8550-1450 8550-1430 8550-4150 8550-4450 8550-4460 8550-4480 8550-5150 8550-6150 8550-6250 8550-6350 8510-9003 8510-9010 ENC1798-F 158-0033 ENC2844-F ENC1797-F 158-0027
Note: All panels have glazed outer doors Additional 16 Zone and Loop Add-On Kits can be fitted
AUS / PAGE 30
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
CONTROL PANELS FIREFINDER Intelligent AS4428
FireFinder SP1X Intelligent Control Panel
FireFinder SP8X Intelligent Control Panel
FireFinder Intelligent Control Panel SP1X 1 Loop SP1X 1 Loop EV20+Mic 5.6A SP1X 1 Loop EV40+Mic 5.6A SP8X 1 Loop 5.6A SP8X 1 Loop EV40+Mic 5.6A SP8X 1 Loop EV60+Mic 5.6A SP8X 1 Loop EV120+Mic 18A SP16X 1 Loop 5.6A 10U 1 Loop 5.6A 16U 1 Loop 5.6A 29U 1 Loop 5.6A SP1X Ancillary Cabinet SP8X Ancillary Cabinet SP1X Surround SP8X Surround SP16X Surround SP1X+Ancillary Cabinet Surround SP8X+Ancillary Cabinet Surround
8550-1100 8550-1400 8550-1440 8550-4100 8550-4400 8550-4470 8550-4490 8550-5100 8550-6100 8550-6200 8550-6300 8510-9003 8510-9010 ENC1798-F 158-0033 ENC2844-F ENC1797-F 158-0027
Note: All panels have glazed outer doors Additional 16 Zone and Loop Add-On Kits can be fitted
AUS / PAGE 31
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
CONTROL PANELS FIREFINDER Conventional / Intelligent
Network Interface Card (NIC) – 2 Wire Network
NE W
• The NIC gives the FireFinder network capabilities via the RS422 communications port • Provides an additional RS232 communications port when connected to Controller Interface Card (CIC) • High level interface for Building Management or ModBus protocol for SmartGraphics and PLCs • The NIC can be isolated from other network devices • Loop In/Loop Out for easy installation
Voltage Quiescent Current Available Ports
24 VDC 65 mA RS422 – network RS232 – serial comms 1.2km RS422 – 2 pair twisted/screened RS232 – 1 pair twisted/screened -5°C to +55°C (no icing) 0 to 95% (non condensing) 225 grams
Max distance (between NICs) Cable requirements Operating temperature Relative humidity Weight
Network Interface Card – NIC (2 wire) NZ4512 SP1X SP8X SP16X/Rack Add-On Kit
159-0258 159-0259 159-0260 4310-0079
High Level Interface Expander or Port Expander Board The High Level Interface Expander provides the ability for the FireFinder Fire Alarm Control Panels (FACP’s) to support a range of high level interface options. The physical interface between the FACP and equipment can be RS232 or RS485. Typical applications where the HLI Expander is used are: • Building Management • Paging system • Nurse Call Systems • EV3000 • SmartGraphics • MODBUS
AUS / PAGE 32
CONTACT AMPAC
Supply Voltage Quiescent current Max No. HLIE per FACP controller Size Ports Max Distance Cabling
27VDC 7.5ma 3 155 L x 72.5 W x 20 D mm RS232 RS485 15m 1.2kms Multi-core 1 twisted pair + cable+shield shield
FireFinder High Level Interface Expander – Factory Fitted Inside Panel 159-0268 FireFinder High Level Interface Expander – Add-On Kit 4310-0080
HOME
CONTENTS
SEARCH
ZOOM
EXIT
CONTROL PANELS FIREFINDER Conventional / Intelligent
Analogue Loop Upgrade Kit • This kit adds an intelligent analogue loop to the FireFinder Control Panel • For an odd numbered loop upgrade the kit consists of an I/O CPU module, cable and termination card • An even numbered loop upgrade consists of an I/O CPU module and cable
Voltage Quiescent current Loop current Operating temperature Relative humidity Weight
24 VDC 40 mA 250 mA max. -5°C to +55°C (no icing) 0 to 95% (non condensing) 200 grams
1 Loop Upgrade Kit – even numbered loop SP1X 1 Loop Upgrade Kit and processor – odd numbered loop SP1X Even No. Loop SP16X/Rack Even No. Loop SP8 Odd No. Loop SP16X/Rack
159-0001 159-0003 159-0002 159-0046 159-0004
Module Expansion Kit for Modules (5–8) • Expands the capacity of the FireFinder to accommodate a further four loops, 64 conventional zones, four I/O modules or any combination of the above • Requires a main controller board Note: Other expansion module kits are available with 16AZF/Loop/or I/O modules pre-fitted to suit. Consult your Customer Service office for more details.
AUS / PAGE 33
CONTACT AMPAC
HOME
CONTENTS
Voltage Quiescent current Operating temperature Relative humidity Weight
24 VDC 5 mA -5°C to +55°C (no icing) 0 to 95% (non condensing) 110 grams
SP8X Loop Module Expansion Kit SP16X/Rack Loop Module Expansion Kit
SEARCH
ZOOM
159-0112 159-0022
EXIT
CONTROL PANELS FIREFINDER Conventional / Intelligent
8 Way Serial Relay Output Board • Each serial relay output board offers 8 voltage free relay outputs, each rated at 5 amps, 24 VDC • Each relay has a single normally open/close volt-free contact extended to a wire-protected screw terminal • The serial 8-way relay is driven directly from the main controller board
Voltage Quiescent current Relay output current Operating temperature Relative humidity Weight
24 VDC 5 mA 5 Amps at 24 VDC -5°C to +55°C (no icing) 0 to 95% (non condensing) 190 grams
Rack 8 Way Serial Relay Output Board SPX 8 Way Serial Relay Output Board
159-0072 159-0079
4 Plus 4 Bell Monitor Board • The 4 Plus 4 Bell Monitor has screw terminals for 4 voltage free contacts and 4 switched 24V DC sounder outputs • The outputs are programmable and monitored for open or short circuit • The board connects directly to the main controller board
Voltage Quiescent current Relay output current Sounder output current Capacity Operating temperature Relative humidity Weight
24 VDC 20 mA 1 Amp at 24 VDC 1 Amp each 8 boards per main controller -5°C to +55°C (no icing) 0 to 95% (non condensing) 250 grams
4 Plus 4 Bell Monitor Board
AUS / PAGE 34
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
159-0069
EXIT
CONTROL PANELS FIREFINDER Conventional / Intelligent- Add Ons
Fire Fan Module Each Fire Fan Module houses the control and indication of up to four (4) fire fans and a single control/indication for plant trip reset. A hard-wired version of a fire fan module consists of a Fire Fan Control Card and Termination Board. Field wiring is terminated to the termination board at the FACP. A loop-driven version is also available and in this configuration only the Fire Fan Control Card would be required. Field wiring will terminate to address input/output devices that operate on the addressable loop. • Four (4) Controls per Module • Status indication for Run / Fault / Stop • Controls for ON / Auto / Off • Audible and visual feedback of button press • Built in Plant Trip Reset • Supports 3, 4 and 5 Wire Connections • Available in Hardware or loop driven versions • Communicates with FACP via RS485 communication port • Where applicable all terminals cater for 2.5mm² cables
AUS / PAGE 35
CONTACT AMPAC
HOME
CONTENTS
Operating Voltage Dimensions: Controller Card Termination Board Contact Rating Approval System Capacity: FireFinder LoopSense ZoneSense Plus
27VDC Fits standard Panel Cut-Out 155mm x 72mm 1 @ 24VDC AS1668 15 Maximum 15 Maximum 1 Maximum
Hard Wired Loop Driven Slip in Label Template
SEARCH
ZOOM
4310-0021 4310-0071 LAB1486
EXIT
CONTROL PANELS FIREFINDER Conventional / Intelligent
8-Way 5A Relay • Each upgrade panel add-on offers 8 voltage free relay outputs. E ach output is rated at 5 amps, 24 VDC • Each relay has a single normally open/close volt-free contact extended to a wire-protected screw terminal • The standard 8-way relay upgrade requires spare capacity available on a 128/128 I/O and 16/16 I/O module
Voltage Quiescent current Operating temperature Relative Humidity Weight
24 VDC 5 mA (Serial Relay Board) -5°C to 55°C (no icing) 0 to 95% (non condensing) 190 grams
SPX 8-Way 5A O/P Relay Rack 8-Way 5A O/P Relay
AUS / PAGE 36
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
159-0013 159-0015
EXIT
CONTROL PANELS FIREFINDER Conventional / Intelligent
8 Way Bell Monitor Board • The 8-Way Bell Monitor has 8 switched 24V DC sounder outputs • The outputs are programmable and monitored for open or short circuit • The board connects directly to the main controller board
Voltage Quiescent current Max sounder output current Max output current Operating temperature Relative humidity Weight
24 VDC 20 mA 1 Amp each 4 Amps per board -5°C to +55°C (no icing) 0 to 95% (non condensing) 250 grams
8 Way Bell Monitor Board
159-0071
16 Way Conventional Zone Card • Adds 16 conventional Alarm Zone Circuits • Kit consists of an I/O CPU module, cable and 16 zone termination card • Supports up to 40 conventional detectors (Series 60, Series 65 or Orbis) per zone • Fixed 3K3 End-Of-Line device • Supports Ampac NZ detector models
Voltage Quiescent current Operating temperature Relative humidity Weight
24 VDC 145 mA -5°C to +55°C (no icing) 0 to 95% (non condensing) 185 grams
SP8X/SP16X 16 Way Conventional Zone Card Rack 16 Way Conventional Zone Card
AUS / PAGE 37
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
159-0005 159-0006
EXIT
CONTROL PANELS FIREFINDER Conventional / Intelligent
16 Opto Inputs • The Opto Input panel add-on provides 16 programmable electrically isolated inputs to the FACP • The input from a third party source should be a volt-free contact • This upgrade requires spare capacity available on a 128/128 I/O and 16/16 I/O Interconnect Module
Voltage Quiescent current Operating temperature Relative Humidity Weight
24 VDC 5 mA -5°C to 55°C (no icing) 0 to 95% (non condensing) 185 grams
SP 16 Opto Input Rack 16 Opto Input
159-0010 159-0011
Modem • The modem allows a remote access to FireFinder • Configuration and application software can be uploaded or downloaded via the modem • Wireless Modem requires available signal from appropriate network • All modems are AUSTEL approved • Great tool to provide remote support
Voltage Data transfer rate Comms to FACP Operating temperature Relative Humidity Weight
27 VDC 9600 baud max RS 232 -5°C to 55°C (no icing) 0 to 95% (non condensing) SP & Rack: 1kg Wireless: 5kg
SPX Modem Rack Modem Wireless Modem
AUS / PAGE 38
CONTACT AMPAC
HOME
CONTENTS
SEARCH
159-0033 159-0065 159-0068
ZOOM
EXIT
CONTROL PANELS FIREFINDER Conventional / Intelligent- Add Ons
8 Way Switch and Indicator Card • 8 x Push Button On / Off switches • 8 x LED display of the On / Off condition • Controls and Monitors solenoid test switches, manual shutdowns and etc • Programmable via the ZoneSense PLUS front panel • Programmable via ConfigManager for the FireFinder range of panels • Programmable via LoopMaster for the LoopSense range of panels
Voltage 24VDC Quiescent Current 3.6mA Max Current 8mA Operating Temperature -5°C - 55°C (no icing) Relative Humidity 0 to 95% (non condensing) Weight 100grams System Capacity FireFinder 15 Maximum LoopSense 15 Maximum ZoneSense Plus 1 Maximum Switch and Indicator Card Slip In Label
AUS / PAGE 39
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
4310-0030 LAB 1483
EXIT
CONTROL PANELS FIREFINDER Conventional / Intelligent- Add Ons
Agent Release System AS4214 The Agent Release System comprises of the Main Control Card, Termination Board and Local Control Stations. In addition a yellow Manual Call Point can be supplied to fit to the main Fire Alarm Control Panel (FACP) (This is a requirement of AS4214 Agent Release Systems) The Agent Release System can be configured to operate in a single group or dual group mode. • Controls and Monitors Agent Release System • Outputs for Warning Signs and activation devices • Inputs for signals from pressure switches & valves • Serial connection to Agent Release Local Control Station (LCS) • Programmable via the ZoneSense PLUS front panel • Programmable via ConfigManager for the FireFinder range of panels • Programmable via LoopMaster for the LoopSense range of panels
Pressure Switch Input Low Pressure Switch Input Interlock Input Gas Fired Output
Monitored Input Monitored Input Monitored Input Volt Free Changeover 1A@24VDC System Inoperative Output Volt Free Changeover 1A@24VDC Stage 1 Output Monitored Stage 2 Output Monitored Release Initial Agent Output Monitored current limited 2A max Release Reserve Agent Output Monitored current limited 2A max System Capacity FireFinder 8 Maximum LoopSense 8 Maximum ZoneSense Plus 1 Maximum
Agent Release Kit
4310-0011
Local Control Station AS4214 A maximum of 8 LCS's can be connected remote to the panel. An operator may manually release or inhibit release from any of these LCS's. • RS485 serial connection from the FireFinder FACP to the Agent Release Local Control Station (LCS) • A 20mm knock out is provided in the top and bottom of the LCS metal enclosure
AUS / PAGE 40
CONTACT AMPAC
HOME
CONTENTS
Inhibit Agent Release Manual release
Push button hinged cover MCP with hinged cover
Local Control Station
SEARCH
ZOOM
4310-0019
EXIT
CONTROL PANELS FIREFINDER Conventional / Intelligent – Ancillary Products
Agent Release Warning Signs The AR panel supports a 2-wire connection to warning signs. The 2-wire connection supports both single or dual stage signs. The latter is possible because of the voltage reverse technology adopted by the AR panel. Multiple warning signs may be connected to the AR panel. The connection will be in a ‘daisy chain’ configuration with the last warning sign fitted with an End-Of-Line (EOL) resistor. The EOL resistor facilitates the monitoring of the warning sign circuit. A maximum of 6 warning signs may be fitted to an AR panel. An on-board buzzer fitted to every sign provides audible warning. However in the event AS1670.4 audible warning tones are required, external electronic sounders may be connected directly to each warning sign. An external switch may be connected to the sign to mute audible warning.
AUS / PAGE 41
CONTACT AMPAC
HOME
CONTENTS
ACP-04 Manual Call Point Yellow ACP-04 Manual Call Point Hinged Cover
213-0061 213-0057
IP50 SIGNS Warning sign back box (IP50) no fascia 207-0050 “Extinguishing System Inoperative” complete IP50 207-0051 Special wording fascia only 207-0052 “Fire Alarm, Do Not Enter” fascia only 207-0053 “Fire Alarm, Evacuate Area” fascia only 207-0054 “Do Not Enter, Gas Discharged” fascia only 207-0055 “Fire Door CLosing” fascia only 207-0056 “Do Not Enter” fascia only 207-0057 IP65 SIGNS Warning sign back box (IP65) no fascia 207-0060 “Extinguishing System Inoperative” complete IP65 207-0061 Special wording fascia only 207-0062 “Fire Alarm, Do Not Enter” fascia only 207-0063 “Fire Alarm, Evacuate Area” fascia only 207-0064 “Do Not Enter, Gas Discharged” fascia only 207-0065 “Fire Door Closing” fascia only 207-0066 “Do Not Enter” fascia only 207-0067 SOUNDERS Vantage Sounder (Red/White) 205-0062/63 Vantage Combi (Red/White) 205-0066/67
SEARCH
ZOOM
EXIT
CONTROL PANELS FIREFINDER Conventional / Intelligent
Panel Mounted LED Indicators • Provide flexibility to include additional LED indicators to the FireFinder SP1X and SP8X • Available in three versions: – 32 zone alarm only indication (red) – 16 zone alarm/fault indication (red/amber) – 32 zone general indication (amber) • Serial connection to the FireFinder panel • Simple clip installation • Indicators remain illuminated until reset by the panel • Indicators are tested by the FireFinder panel’s lamp test control
AUS / PAGE 42
CONTACT AMPAC
HOME
CONTENTS
Voltage Quiescent current Max current Operating temperature Relative humidity Weight
27 VDC 30 mA 40 mA -5°C to +55°C (no icing) 0 to 95% (non condensing) 100 grams
FireFinder SP1X 32 Zone Alarm Only Indication (Red) FireFinder SP8X 32 Zone Alarm Only Indication (Red)
159-0106 159-0089
FireFinder SP1X 16 Zone Alarm/Fault Indication (Red/Amber) FireFinder SP8X 16 Zone Alarm/Fault Indication (Red/Amber)
159-0107 159-0108
FireFinder SP1X 32 Zone General Indication (Amber) FireFinder SP8X 32 Zone General Indication (Amber)
159-0123 159-0124
SEARCH
ZOOM
EXIT
CONTROL PANELS FIREFINDER Conventional / Intelligent
Remote Mounted LED Indicators • The remote LED indicator boards provide facilities to mimic the FireFinder zone LEDs and switches • Connects to the RS485 communications bus via the controller interface card • Allows the custom design of geographic site layout mimics • Each termination board connects up to 32 zone LEDs – 31 boards maximum – total 992 zone indications FireFinder LED Mimic Driver
Voltage Quiescent current Max current Communication mode Baud rate Communication cable No. of boards No. of zones Buzzer external max current On board status indication
27 VDC 8 mA max 100 mA RS485 19200 max 1 x pair twisted and screened 31 max 992 zones max 20 mA Power on – green Normal – green Fault – yellow Reset Lamp test Buzzer mute Bell isolate Manual evacuate -5°C to +55°C (no icing) 0 to 95% (non condensing)
Common inputs
Operating temperature Relative humidity FireFinder LED Mimic Driver 32 Way Mimic Output Termination Board FireFinder 16 Zone LED Display Board
Mimic Output Termination Board
159-0145 159-0152 159-0218
Remote Expansion LED Board
AUS / PAGE 43
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
CONTROL PANELS FIREFINDER Conventional / Intelligent
Fibre Optic Network Interface The fibre optic network interface kit offers the user a method of interconnecting two (2) or more networked FireFinder Fire Alarm Control Panels (FACP) using fibre optic cable as an alternative to copper wire. Each FACP will require a kit. Each kit comprises of 2 modem interfaces plus cables. • 4 versions available to suit your cabling scheme on site • Redundant loop integrity (same as copper) • A network interface card is still required at each FACP node • Maximum distance using ‘Multimode’ (between nodes) up to 5km; using Single Mode 50km
Supply Voltage Quiescent Current Optical Connector Ports Available Size (mm) Weight Operating Temperature Humidity
24 VDC 80 mA @ 24 VDC ST standard RS422/RS485 104D x 104W x 25H 280g -20°C to +75°C 0 to 95% relative, non-condensing
Item FireFinder Fibre Optic Multimode 2 core FireFinder Fibre Optic Multimode 1 core FireFinder Fibre Optic Single mode 2 core FireFinder Fibre Optic Single mode 1 core
AUS / PAGE 44
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
Max Distance between Nodes 5km max 5km max 50km max 50km max
EXIT
Code 159-0251 159-0252 159-0253 159-0254
EMERGENCY WARNING SYSTEMS
Emergency Warning Systems The Ampac EV3000 Occupant Warning and Intercom System is designed for the purpose of enabling the orderly evacuation of occupants, from a building or structure, in the event of an emergency. The system comprises of two (2) sub-systems. The first being the Occupant Warning System (OWS) and the other the Occupant Intercom System (OIS). While the Warning and Intercom System have separate controls, they coexist in a panel that is logically presented and aesthetically pleasing. The Occupant Warning System makes use of speakers strategically placed around the site, to broadcast ALERT, and/or EVACUATION signals or public address announcements. The OWS may be automatically initiated or manually operated. When not used in an emergency situation, the EV3000 can broadcast background music and/or general paging announcements. The Occupant Intercom System (OIS) consists of front panel control at the Emergency Control Panel (ECP) and Warden Intercom Phones (WIP) that are strategically placed throughout the building. Communication is only possible between the WIP and ECP. For larger sites, multiple control panels may be networked.
AUS / PAGE 45
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
EMERGENCY WARNING SYSTEMS
Emergency Warning Systems • Modular system design – can be easily customised to meet special requirements • Discrete front panel control – ‘natural’ style layout easy to locate zones • Amplifiers available: 40, 120, 240 & 480-watts – choice of amplifiers to suit your need • Visual output for hearing impaired or noisy environments • Common or individual fire alarm inputs – an “all call” or staged evacuation may be configured • 2-wire Warden Intercom Phones (WIP) – monitored for open and short circuit • Common or zoned background music inputs – non-emergency input gives EV3000 the flexibility to fit most applications including shopping centres, hospitals, etc • Monitoring of speaker circuits – monitoring for short or open circuit • Monitoring of Visual Warning indicators – monitoring for short or open circuit • Automatic volume control incorporating ambient noise sensing microphone – ideal for applications where the ambient noise levels are different at various times of day • Fail safe volume override output – used as a control to shutdown all non-emergency facilities offered by the EV3000 and to override attenuated volume controls located in the field • Stand-by signal generators – provides 100% backup of emergency tones for greater reliability • Stand-by microphone amplifiers – provides 100% backup of emergency public address for greater reliability • Automatic changeover to stand-by amplifier – may be configured in the event an active amplifier is faulty • Digital paging console – attractive remote paging console with seven (7) segment digital display and keypad gives operator quick and easy access to paging zones • Networked system – expands EV3000 features to include master / sub panel configuration, and remote paging console • Optic Fibre Interface – the optional Optic Fibre interface allows the EV3000 to be networked over optic fibre cables
AUS / PAGE 46
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
EMERGENCY WARNING SYSTEMS EV3000 Emergency Control Panel
Mechanical Material Finish Dimensions
1.6mm Mild Steel Powder Coated Arch White 10U 700H x 625W x 240D mm (SEC P only) 12U 900H x 650W x 290D mm 16U 1200H x 700W x 375D mm 29U 1800H x 700W x 375D mm SSL – AS2220.89 Compliant with AS1670.4:2004
Approvals Signals
EV3000 12U
EV3000 16U
EV3000 29U
AUS / PAGE 47
Electrical Power Supply 7.5, 13, 19.5 or 26 A mps @ 24 VDC Communication RS485 @ 9600 bps EWS Zones 144 max EIS Zones 288 max Paging Console 8 max (recommended) ECP’s 12 max (recommended) Visual Warning Option 1 EV3000 Visual Outputs Maximum of 8 pairs per visual circuit (for Xenon 208-0011). Not T3 compliant Option 2 EV3000 Visual Outputs Maximum of 40 pairs per visual circuit (for LED 208-0063). T3 compliant Note: The LED visual pairs require the Ampac 4210-0031 Visual Driver Kit fitted
EV3000 29U Double Rack
CONTACT AMPAC
HOME
EV3000 Emergency Control Panel 12U MECP 16U MECP 29U MECP 29U Double Cabinet MECP 10U SECP 12U SECP 16U SECP 29U SECP
CONTENTS
SEARCH
105-0001 105-0002 105-0003 105-0007 105-0004 105-0005 105-0006 105-0009
ZOOM
EXIT
EMERGENCY WARNING SYSTEMS EV3000 Emergency Control Panel – Add Ons
40 Watt Power Amplifier • A modular power amplifier that is rated at 40 watts • Multi-channel audio input supports Alert tone, Evacuation tone, Public Address, and background music • Continuous monitoring of amplifier and 100 volt speaker circuit • Overload protection with Automatic • Easily plugs into an Ampac EV3000 amplifier frame • Can fit up to 8 amplifiers per frame
Voltage Quiescent current Max current Max output power Output voltage Freq. Response Distortion
24 VDC 58mA 3400mA 40 Watts 100 VAC RMS 150Hz to 12kHz (±1dB) Max 1% at full load (typical 0.5%) +5dB <200Kohm balanced) (1.4VRMS) 100 VRMS + 10% 675 grams
Sensitivity Overload Weight 40 Watt Power Amplifier
154-0075
120 Watt Power Amplifier • A modular power amplifier that is rated at 120 watts • Multi-channel audio input supports Alert tone, Evacuation tone, Public Address, and background music • Continuous monitoring of amplifier and 100 volt speaker circuit • Overload protection with Automatic • Easily plugs into an Ampac EV3000 amplifier frame • Can fit up to 4 amplifiers per frame
Voltage Quiescent current Max current Max output power Output voltage Freq. Response Distortion Signal to Noise Overload Weight
24 VDC 175mA 8100mA 120 Watts 100 VAC RMS 210Hz to 14.5kHz (±1dB) < 0.2% at full load 77 dB 100 VRMS + 10% 1160 grams
120 Watt Power Amplifier
AUS / PAGE 48
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
154-0077
EXIT
EMERGENCY WARNING SYSTEMS EV3000 Emergency Control Panel – Add Ons
240 Watt Power Amplifier • 24v DC supply • Mother board address strapping (120 address positions) • Continuous fault monitoring • Volume override output • Test tone input • Data selectable 4 channel input (balanced) • Tone generator synchronisation input • Indication (power on - green, power shutdown - yellow, amp or line fault - red, overload - red) • Minimum cable size 2.5mm²
Voltage Quiescent current Max current Max output power Output voltage Freq. Response Distortion Signal to Noise Overload Weight
24 VDC 350mA 16200mA 240 Watts 100 VAC RMS 210Hz to 14.5kHz (±1dB) < 0.2% at full load 77 dB 100 VRMS + 10% 2320 grams
240 Watt Power Amplifier
154-0001
480 Watt Power Amplifier • 24v DC supply • Mother board address strapping (120 address positions) • Continuous fault monitoring • Volume override output • Test tone input • Data selectable 4 channel input (balanced) • Tone generator • Indication (power on - green, power shutdown - yellow, amp or line fault - red, overload - red) • Minimum cable size 4mm²
Voltage Quiescent current Max current Max output power Output voltage Freq. Response Distortion Signal to Noise Overload Weight
24 VDC 700mA 32400mA 480 Watts 100 VAC RMS 210Hz to 14.5kHz (±1dB) < 0.2% at full load 77 dB 100 VRMS + 10% 4640 grams
480 Watt Power Amplifier
AUS / PAGE 49
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
154-0002
EXIT
EMERGENCY WARNING SYSTEMS EV3000 Emergency Control Panel – Add Ons
Emergency Alarm Initiating Device (EAID) • Connects to S004 WIP • 2 wires for WIP & EAID • Compatible with 219-0015
Emergency Alarm Initiating Device (EAID)
213-0068
Warden Intercom Phone – 2 Wire (S0004) • 2 Wire WIP/EAID wiring • High quality WIP audio • Complies with AS4428.4 • Suitable for models manufactured after July 2010
Operating Voltage Line Voltage
27 VDC (line driven) On hook - 25 VDC max Off hook - 14 VDC max On hook - 5 mA max Off hook - 35 mA max 360 ohm balanced 0 dB (± 3dB) 2 wire - 2.5mm² max. 215H x 85W x 62D mm 380 grams
Current draw Line Impedance Line Level Cabling Dimensions Weight Warden Intercom Phone – 2 Wire (S0004) WIP Enclosure Metal Surface Mounted
AUS / PAGE 50
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
219-0015 291-0054
EXIT
EMERGENCY WARNING SYSTEMS EV3000 Emergency Control Panel – Add Ons
Warden Intercom Phone – 3 Wire • The WIP is installed remote to the ECP • Provides intercommunication between users at the WIP and Emergency Control Panel • This feature is only available when the Emergency Warning Intercom facility has been incorporated in the control panel • Made of high impact red ABS plastic • Compatible with most EV3000 systems manufactured before July 2010
Operating Voltage Line Voltage
27 VDC (line driven) On hook - 25 VDC max Off hook - 14 VDC max On hook - 5 mA max Off hook - 35 mA max 360 ohm balanced 0 dB (± 3dB) 3 wire - 2.5mm² max. 215H x 85W x 62D mm 380 grams
Current draw Line Impedance Line Level Cabling Dimensions Weight Warden Intercom Phone – 3 Wire WIP Enclosure Metal Surface Mounted
219-0007 291-0054
Remote Paging Console • Provides a point to initiate a non-emergency voice announcement via the EV3000 • Provides a pre-announcement tone • Easy keypad operation to broadcast voice announcements to selected zones, or group of zones • Connects to EV3000 via RS485 • Derives power from the EV3000 panel
AUS / PAGE 51
CONTACT AMPAC
HOME
CONTENTS
Size Supply voltage Current Communication Weight
80H x 300W x 220D mm 12 VDC 400 mA RS 485 1160 grams
Remote Paging Console
SEARCH
ZOOM
154-0005
EXIT
EMERGENCY WARNING SYSTEMS EV3000 Emergency Control Panel – Add Ons
Fibre Optic Network Interface for EV3000 The fibre modem network interface kit offers the user a method of interconnecting two (2) or more EV3000 Emergency Warning and Intercom System (EWIS) using fibre optic cable as an alternative to copper. The modems convert hardwired data and audio, to a common fibre optic compatible output. The fibre optic modems are full duplex and have 4-channels to carry both data and two (2) audio signals. Two (2) channels are required – emergency public address and warden intercom audio signals.
Supply Voltage Quiescent Current Input Ports Available
12 VDC 300 mA RS422 Emergency P.A. Warden Intercom Phone Audio 5 km 2-core multimode fibre ST Standard
Max. Distance Cabling Fibre Connector Optical Data Wavelength Mode Emitter type Operating Temperature Relative Humidity
850nm Multimode LED 0°C to +55°C 0 to 95% (no icing) (non condensing) L104 x W144 x D25 mm
Size Fibre Optic Network Interface for EV3000
154-0005
Combined Strobe for EV3000 (Flush) Combined Strobe for EV3000 (IP65 ) Combined Strobe for EV3000 (Surface )
208-0066 208-0065 208-0066
Combined Strobe for EV3000 (Surface Mount) Item pictured is 208-0066 Indoor. The IP65 model uses the deep base to achieve an outdoor solution where required.
AUS / PAGE 52
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
EMERGENCY WARNING SYSTEMS Speakers
Ceiling Speaker – 100mm Recessed • 100 mm recessed ceiling speaker • Operates with 100 volt speaker line • Capacitor fitted for line monitoring • Five (5) power output settings • Safety cover to protect terminals • Facility to secure field cabling to speaker housing • Optional low profile grill available
Rated Power Line Voltage Frequency R esponse SPL Speaker Tap (watt) Cut-out size Dimensions Weight
5 watts 100 Volt 100 Hz to 20 kHz 96 dB (1 watt @ 0.5m) 0.33, 0.66, 1.25, 2.5, 5 85 mm Diameter 100 x 105 Hmm 800 grams
Ceiling Speaker – 100mm Recessed Low Profile Grill
218-0008 218-0003
Ceiling Speaker – 200mm Recessed • 200 mm recessed ceiling speaker • Operates with 100 volt speaker line • Capacitor fitted for line monitoring • Five (5) power output settings • Safety cover to protect terminals • Facility to secure field cabling to speaker housing • Optional low profile grill available
Rated Power Line Voltage Frequency R esponse SPL Speaker Tap (watt) Cut-out size Dimensions Weight
5 watts 100 Volt 100 Hz to 20 kHz 96 dB (1 watt @ 0.5m) 0.33, 0.66, 1.25, 2.5, 5 190 mm Diameter 200 x 75 Hmm 1 kg
Ceiling Speaker – 200mm Recessed Low Profile Grill
AUS / PAGE 53
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
218-0009 218-0021
EXIT
EMERGENCY WARNING SYSTEMS Speakers
Ceiling Speaker – 100mm One-Shot • 100 mm quick-fit recessed ceiling speaker • Operates with 100 volt speaker line • Capacitor fitted for line monitoring • Five (5) power output settings • Safety cover to protect terminals • Facility to secure field cabling to speaker housing • Speaker grill incorporated with speaker
Rated Power Line Voltage Frequency R esponse SPL Speaker Tap (watt) Cut-out size Dimensions Weight
5 watts 100 Volt 100 Hz to 15 kHz 98 dB (1 watt @ 0.5m) 0.33, 0.66, 1.25, 2.5, 5 140 mm Diameter 155 x 110 Hmm 850 grams
Ceiling Speaker – 100mm One-Shot (White) Ceiling Speaker – 100mm One-Shot (Black) Ceiling Speaker – 200mm One-Shot (White)
218-0026 218-0031 218-0032
Surface Speaker – 100mm • Custom designed speaker and transformer assembly engineered to meet Australian Fire Evacuation Standards • High degree of speech intelligibility
Driver Power taps SPL 1W @ 1m Frequency response Connection
100mm (4”) dual cone 0.33, 0.66, 1.25, 2.5, 5W 90dB @ 1kHz (+/- 2dB) 100Hz-15kHz 4 way terminal block + 22uF bipolar capacitor
Surface Speaker – 100mm
AUS / PAGE 54
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
218-0022
EXIT
EMERGENCY WARNING SYSTEMS High Efficiency Speakers
EasyFit Ceiling Speakers • In four useful sizes: 4”, 5”, 6.5”, 8” • Choice of power rating: 5W, 10W, 15W, & 30W • Wide bandwidth for music reproduction • Wide dispersion for speech intelligibility • Simple output-level selection • Easily flush-mounted in ceilings or bulkheads • Dependable rota-clamp fixing system • Blends in with virtually all interiors
Driver Maximum/rated power Power taps Frequency Range Axial sensitivity 1W/1m/1kHz Opening Angle( -6dB) Ceiling cutout diameter Overall dimensions Safety
4 Inch 5 Watt 4” 8W/5W 5, 2.5, 1.25, 0.66, 0.33W 100Hz - 15kHz 94dB SPL 144° / 93° at 1kHz / 4kHz 140mm 170mm x 110mm acc to EN 60065
5 Inch 5 Watt 5” 8W/5W 5, 2.5, 1, 0,5, 0.33W 50Hz - 17kHz 97dB SPL 170° at 1kHz 170mm 202mm x 90mm acc to EN 60065
6 Inch 10 Watt 6.5” 15W/10W 10, 5, 2.5, 1.25W 60Hz - 20kHz 91dB SPL 170° at 1kHz 195mm 220mm x 115mm acc to EN 60065
8 Inch 15 Watt 8” 22W/15W 15, 10, 5, 2.5, 1.25W 50Hz - 17kHz 93dB SPL 165° at 1kHz 238mm 273mm x 103mm acc to EN 60065
8 Inch 30 Watt 8” 45W/30W 30, 15, 7.5, 3.75W 50Hz - 17kHz 93dB SPL 100° at 1kHz 238mm 273mm x 115mm acc to EN 60065
Ceiling Speaker, Easyfit 5w 4” - EVAC Ceiling Speaker, Easyfit 5w 5” - Brilliant White Ceiling Speaker, Easyfit 5w 5” White Ceiling Speaker, Easyfit 10w 6.5” Ceiling Speaker, Easyfit 15w 8” White Ceiling Speaker, Easyfit 30w 8” White
AUS / PAGE 55
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
218-0041 218-0042 218-0043 218-0044 218-0045 218-0046
EXIT
EMERGENCY WARNING SYSTEMS Speakers
Horn Speaker – 10 Watt • 10 watt Flared horn speaker • Operates with 100 volt speaker line • Capacitor fitted for line monitoring • Five (5) power output settings • High SPL performance • Weatherproof construction • Mounting bracket supplied
Rated Power Line Voltage Frequency R esponse SPL Speaker Tap (watt) Dispersion angle Material IP Rating Dimensions Weight
10 watts 100 Volt 250 Hz to 13 kHz 105 dB (1 watt @ 1m) 1.25, 2.5, 5, 7.5, 10 110° UV stabilised plastic IP65 150 Dia x 190 Dmm 1.4 kg
Horn Speaker – 10 Watt
218-0028
Horn Speaker – 20 Watt • 20 watt Flared horn speaker • Operates with 100 volt speaker line • Capacitor fitted for line monitoring • Five (5) power output settings • High SPL performance • Weatherproof construction • Mounting bracket supplied
Rated Power Line Voltage Frequency R esponse SPL Speaker Tap (watt) Dispersion angle Material IP Rating Dimensions Weight
20 watts 100 Volt 270 Hz to13 kHz 108 dB (1 watt @ 1m) 2.5, 5, 7.5, 10, 15, 20 110° UV stabilised plastic IP65 200 Dia x 290 Dmm 1.5 kg
Horn Speaker – 20 Watt
AUS / PAGE 56
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
218-0007
EXIT
EMERGENCY WARNING SYSTEMS High Efficiency Speakers
Horn Speaker – 10 Watt / 20 Watt • 10W & 20W Models available • IP66 Rated • Emergency Evacuation System ready • Wide dispersion for speech intelligibility • Screwdriver adjustable power tapping • Loop in / Loop out wiring
10 Watt 100V 10W 10, 7.5, 5, 2.5, 1.25 119 dB 108 dB 300Hz - 13kHz 140°@1kHz 1.3KG
Rated input Power handling Power taps SPL at Rated Power (10W @ 1m) SPL at Rated Power (1W @ 1m) Frequency Range (-10dB) Dispersion Angle(-6dB) Weight Horn Speaker – 10 Watt Horn Speaker – 20 Watt
20 Watt 100V 20W 20, 15. 10, 7.5, 5W 124 dB 110 dB 9kHz 90°@1kHz 2.1KG 218-0047 218-0048
Speaker Attenuator • Operates in conjunction with an Emergency Warning System (EWS) • Attenuates the sound level of speakers in the circuit during normal operation of the EWS • 7-step attenuator setting including ‘OFF’ position • Switched 24 VDC (fail-safe operation) enables attenuation control • Screw driver terrminals for easy wiring
Rated Power Speaker L ine Voltage Attentuation Override Relay Operating Voltage Material Dimensions
40 or 100 watts 100 Volt 0, 5.7, 9.8, 16, 20, 26.3dB, ∞ 24 VDC White UV stabilised plastic Suits single gang wall box (Australian) 300 g
Weight Speaker Attenuator – 40 Watt 100V Speaker Attenuator – 100 Watt 100V
AUS / PAGE 57
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
225-0002 225-0003
EXIT
GRAPHICS PACKAGE
SmartGraphicsHD A FireFinder FACP compatible product AMPAC’s SmartGraphicsHD System unleashes the full power of FireFinder (fire detection) and the EV3000 (alarm and intercom) by creating a robust and versatile hub for controlling your fire detection, alarm and intercom systems with one fully integrated package. Flexible and intuitive in its design, SmartGraphicsHD puts the command of your systems at your fingertips.
•
Interfaces to the FireFinder fire detection panel and the EV3000 emergency warning and intercom system
•
Clearly shows on the building floor plan the start and spread of the fire and the status of the emergency warning and intercom system
•
Has capabilities of e-mailing maps to emergency service organisations and key stakeholders
•
Supports the latest 1920x1080 HD computer technology
•
Able to operate over existing IT infrastructure
•
Can be expanded to incorporate multi-site facilities into one central monitoring package
•
Historic data log on the activity of the fire detection system and alarm system
•
Three level password protection
•
Detailed Egress Pathways
•
Building Information (like hazardous materials) and mustering point displayed on maps
AUS / PAGE 58
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
GRAPHICS PACKAGE
Graphics Package Computer (Rec Min)
Monitor RS232 Comms
RS485 Comms Ethernet
Intel Core Processor 2Ghz, 2GB RAM, 500 GB Hard Drive, CDROM, 6 USB Ports Serial Comms port for connection to FACP (RS232 or RS485 as required) Windows XP Professional (32bit) , or Windows 7 Professionl (32bit) 20” min (resolution 1920 x 1080) 1 pair twisted & screened 15m maximum from FireFinder Baud rate- 9600 to 38400 1 pair twisted & screened 1200m maximum from FireFinder 8 pin RGRJ45 Connector 10/100 Mbps IEEE 802.3. IEEE 802.38
SmartGraphicsHD Licence Package Only 4100-0002 Licence Package and computer - including a colour laser printer 4100-0003 Licence Package and embedded computer with touch screen 4100-0004 - including a colour laser printer Licence Package and computer with touch screen monitor 4100-0005 - including a colour laser printer Ethernet 159-0613 * Graphical Engineering available- please contact your local CSO Office.
AUS / PAGE 59
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
DETECTORS
Orbis Conventional Detectors Orbis is a range of conventional detectors which has been developed with sophisticated technology previously only found in intelligent detectors. Orbis is a range with modern styling and incorporates a mounting base wihich saves installation time.
• Automatic drift compensation with DirtAlert® warning • Patented FasTest® which reduces the time taken to test detectors • SensAlert® uses a flashing LED to indicate that the sensor is not operating correctly • StartUp™ for fast commissioning • Attractive and compact design • Electrically compatible with Series 60 and Series 65 • Wide voltage and operating temperature ranges • Algorithms for transient rejection • Flashing LED option • 360° visibility of LEDs • Insect resistant
AUS / PAGE 60
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
DETECTORS
ORBIS Conventional
Orbis Optical Smoke Detector (AS) The Orbis Optical Smoke Detector works using the well established light scatter principle, however, the sensing technology is radically different in design from previous optical detectors and significantly reduces false alarms. • • • • • •
Responds well to slow-burning, smouldering fires Performs well in black and white smoke Extra confirmation of smoke before alarm signal is given Reduced incidence of false alarms Sensing chamber keeps out dust and other airborne contaminants Operates over a broad range of voltages at extremes of temperature
Operating voltage Quiescent current Alarm current Remote output Size Operating temperature Relative humidity IP rating Weight
8.5 to 33 VDC 65μA at 24 VDC 40mA at 24 VDC 1.2kΩ to -ve supply 97Dia x 31H mm -40°C to +70°C (no icing) 0 to 98% (non condensing) IP23D (EN60529) 75 grams
Orbis Optical Smoke Detector (AS)
201-0512
Approvals: AS7240.7/CSIRO
Orbis Multisensor Detector (AS) The Orbis Multisensor Detector benefits from the same false alarm reduction technology as the optical detector. It is a thermally enhanced smoke detector and so will not give an alarm from heat alone. • • • • •
Responds well to fast-burning, flaming fires Reduced incidence of false alarms Increased reliability of detection Sensing chamber keeps out dust and other airborne contaminants Operates over a broad range of voltages at extremes of temperature
CONTACT AMPAC
8.5 to 33 VDC 65μA at 24 VDC 40mA at 24 VDC 1.2kΩ to -ve supply 97Dia x 42H mm -40°C to +70°C (no icing) 0 to 98% (non condensing) IP23D (EN60529) 80 grams
Orbis Multisensor Detector (AS)
Approvals: AS7240.7/CSIRO
AUS / PAGE 61
Operating voltage Quiescent current Alarm current Remote output Size Operating temperature Relative humidity IP rating Weight
HOME
CONTENTS
SEARCH
ZOOM
201-0514
EXIT
DETECTORS
ORBIS Conventional
Orbis Heat Detector The Orbis Heat Detector monitors temperature by using a single thermistor network which provides a voltage output proportional to the external air temperature. There are seven classes of heat detectors in the Orbis range designed to suit a wide variety of operating conditions. • • • •
Can be used for applications where smoke detectors are unsuitable Ideal in environments that are dirty or smoky under normal conditions Reduced incidence of false alarms Increased reliability of detection
Operating voltage Quiescent current Alarm current Remote output Size Operating temperature Relative humidity IP rating Weight
8.5 to 33 VDC 65μA at 24 VDC 40mA at 24 VDC 1.2kΩ to -ve supply 97Dia x 36H mm -40°C to +70°C (no icing) 0 to 98% (non condensing) IP23D (EN60529) 70 grams
Orbis Heat Detector Orbis BR (65°C) Heat Detector (Type A) Rate of Rise (AS) Orbis A2S (50°C) Heat Detector (Type B) Static (AS) Orbis CR (80°C) Heat Detector (Type C) Rate of Rise (AS) Orbis CS (80°C) Heat Detector (Type D) Static (AS)
Approvals: AS7240.5/CSIRO
201-0500 201-0504 201-0508 201-0510
Orbis TimeSaver Base The TimeSaver Base is a completely new design that provides installers with an open working area with fixing holes shaped to allow a simple mounting procedure. • • • • • •
Grouped terminals to make wiring easy Two fixing centres LED alignment mark Cable stripping guide Detector locking mechanism Continuity link for voltage testing prior to testing
Size IP rating Weight
100Dia x 8H mm IP23D (EN60529) 60 grams
Orbis TimeSaver Standard Base Orbis Time Saver LX Base Orbis TimeSaver Diode Base
Diode version available, which has a diode fitted for systems that house active EOL monitoring for head removal. Simplified (LX version) available without the continuit link fitted.
AUS / PAGE 62
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
201-0540 201-0541 201-0542
DETECTORS
ORBIS Conventional
Orbis LX Base The Orbis LX Base has two slots for fixing screws at a spacing of 51mm to 69mm. Detectors fit into the base one way only and require clockwise rotation without force to be plugged in. • One way fit • Detector locking mechanism
Size Operating temperature Humidity IP rating Weight
100Dia x 8H mm -40°C to +70°C 0 to 98% IP23D (EN60529) 60 grams
Orbis LX Base
201-0545
Orbis TimeSaver Relay Base The TimeSaver Relay Base incorporates a single pole voltage-free changeover contact for switching external equipment. When the detector changes to the alarm state, the relay is energised, causing the contact to change state. The contact will remain in this condition until the detector is reset. • • • • • • •
Grouped terminals to make wiring easy Two fixing centres LED alignment mark Cable stripping guide Continuity link for voltage testing of zone wiring prior to commissioning Detector locking mechanism Capable of switching up to 30V at 1A
Size Operating temperature Humidity IP rating Weight
100Dia x 8H mm -40°C to +70°C 0 to 98% IP23D (EN60529) 60 grams
Orbis TimeSaver Relay Base
201-0543
Approvals: AS7240/CSIRO
AUS / PAGE 63
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
DETECTORS
ORBIS Conventional
Ampac Duct Sampling Unit The Ampac Duct Sampling Unit is designed to monitor levels of smoke in air ducts operating in air speeds of 0.5 to 20 meters per second. The duct smoke detector can be fitted to any wall of a ventilation duct and has two tubes that extend into the duct through punched holes. The perforated sampling tube is placed in the airflow upstream of the exhaust tube which causes a pressure differential in the duct detector. Air is sucked up the sampling tube, across the detector and exhausted back into the air duct.
• T he cover of the duct smoke detector is monitored to ensure working integrity and if removed, causes a fault to appear at the fire alarm control panel • Easily accessible wire clamping terminals ensure secure and fast termination • Clear cover hence the alarm LED on the detector is visible at all times • Unique self-sealing test port allows the dispensing of test smoke via a needle into the duct smoke detector to be tested without the need to remove the cover • Sampling pipes available in 4 lengths • Weather resistant enclosure Approvals: C-tick, AS1603-13
Using the 360mm sampling pipe supplied, an air duct of up to 560mm can be monitored. For duct widths greater than 560mm, three other lengths of sampling pipe are available: 1. For duct width 300 to 750mm 2. For duct width 750 to 1500mm 3. For duct width 1500 to 3000mm
Housing Cover Dimension Temperature Range Humidity Weight
Grey - ABS Transparent - ABS 115H x 340W x 60D mm 0 to +60°C Up to 85%, no condensation 5.5 kg
Orbis Duct Sampling Unit inc Detector Base Duct Probe 300 to 750mm Sampling Pipe Duct Probe 750 to 1500mm Sampling Pipe Duct Probe 1500 to 3000mm Sampling Pipe Orbis Photo Optical Head
214-0052 214-0060 214-0061 214-0062 201-0512
Note: The detector head is sold separately to the duct sampling unit
z V olt free normally opened or closed non-latching relay contact. Relay energises when detector is in alarm (Available only with Ampac Orbis option) z Both sampling and exhaust pipes are fitted to the back box without the need for tools making installation easier
AUS / PAGE 64
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
DETECTORS
XP95 Intelligent Detectors The XP95 range of intelligent fire detectors is advanced in design, improved in performance and has unique features that benefit the installer and end user. The range features smoke detectors (ionisation and optical), standard and high temperature heat detectors and a multisensor. Beam detectors, flame detectors, manual call points, audio visual signalling devices, interface units and isolators complete the range. XP95 has a ‘central intelligence’ system where all the decisions are made by the control panel.
Features • Alarm Flag for fast alarm reporting • Alarm Address for fast location of alarm • XPERT card addressing • Electronics-free base • Easy installation • Elegant design • Insect Resistant
AUS / PAGE 65
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
DETECTORS
XP95 Intelligent
XP95 Ionisation Smoke Detector The XP95 Ionisation Smoke Detector uses a low activity radioactive foil to detect fires by irradiating the air in the smoke chambers and causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm. • • • •
Responds well to fast-burning, flaming fires Designed to operate in a variety of environments Minimal effects from temperature, humidity, atmospheric pressure Well protected against electromagnetic interference over a wide frequency range
Voltage Quiescent current Alarm current Size inc base Operating temperature Relative humidity IP rating Weight inc base
17-28 VDC 280μA at 24 VDC 2.0mA at 24 VDC 100Dia x 50H mm -20°C to +60°C (no icing) 0 to 95% (non condensing) IP23D 161 grams
XP95 Ionisation Smoke Detector
Approvals: AS1603.2
201-0002
XP95 Optical Smoke Detector The XP95 Optical Smoke Detector works using the light scatter principle and is ideal for applications where slow-burning or smouldering fires are likely. • Responds well to slow-burning, smouldering fires • Well suited for bedrooms and escape routes • Unaffected by wind or atmospheric pressure Approvals: AS1603.2
Voltage Quiescent current Alarm current Size inc base Operating temperature Relative humidity IP rating Weight inc base Sensitivity
17-28 VDC 340μA at 24 VDC 4mA at 24 VDC 100Dia x 50H mm -20°C to +60°C (no icing) 0 to 95% (non condensing) IP23D 157 grams 0.12db/m
XP95 Optical Smoke Detector XP95 Optical Smoke (Black) Detector
AUS / PAGE 66
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
201-0003 201-0092
EXIT
DETECTORS
XP95 Intelligent
XP95 Heat Detector The XP95 Heat Detector monitors temperature by using a single thermistor network which provides a count output proportional to the external air temperature. The XP95 range features two Heat Detectors, standard and high emperature. The standard heat detector is classified as an A2S device and will report an alarm at 55°C. The high temperature detector, classified as a CS device, will report an alarm at 90°C. • Ideal in environments that are dirty or smokey under normal conditions • Well suited for warehouses, loading bays and car parks • Unaffected by wind or atmospheric pressure Approvals: AS1603.1
Voltage Quiescent current Alarm current Size inc base Operating temperature
17-28 VDC 250-270μA at 24 VDC 2mA at 24 VDC 100Dia x 50H mm A2S: -20°C to +70°C (no icing) CS: -20°C to +120°C (no icing) 0 to 95% (non condensing) IP53 157 grams
Relative humidity IP rating Weight inc base
XP95 Heat Detector XP95 Heat Detector (Type A & B) A2S (55°C)
201-0001
XP95 Intelligent Detector Base All detectors in the XP95 range fit the Intelligent Detector Base. It is a low insertion force base with stainless steel contacts for the detector terminals. • XPERT addressing • One way fit of detector • Locking feature to prevent unauthorised removal
CONTACT AMPAC
HOME
100Dia x 8H mm -20°C to +60°C (no icing) 0 to 95% (non condensing) 55 grams
XP95/ Discovery Detector Base with Xpert Card XP95 Detector Base (Black) with Xpert Card
Approvals: AS1603:Pt1&2
AUS / PAGE 67
Size Operating temperature Relative humidity Weight
CONTENTS
SEARCH
ZOOM
201-0004 201-0093
EXIT
DETECTORS
XP95 Intelligent
XP95 Isolating Base The new style Isolating Base senses and detects short-circuit faults on XP95 loops and spurs. • Up to 20 devices may be installed between isolating bases • High brightness LED
Voltage Quiescent current
17-28 VDC 47μA (non isolating) 4mA (isolating) 100Dia x 24H mm -20°C to +60°C (no icing) 0 to 95% (non condensing) 100 grams
Size Operating temperature Relative humidity Weight
XP95/ Discovery Isolating Base with Xpert Card
Blank XPERT Card
Pre-addressed XPERT Card
A universal address card supplied with all bases. Using a coding guide, pips are removed to set the address of the inserted detector.
Pre-addressed XPERT cards are supplied with pips already removed.
• • • •
AUS / PAGE 68
201-0125
Simplifies and speeds up installation and commissioning Uses patented, proven technology Address remains the same, no matter how often detectors are replaced Flexibility to create any address
CONTACT AMPAC
HOME
CONTENTS
z Saves time and increases accuracy during commissioning z Pre-numbered 1-126 Blank XPERT Card Pre-addressed (1-126) Xpert Cards
SEARCH
ZOOM
38531-771 201-0013
EXIT
DETECTORS
XP95 Intelligent
Ampac Duct Sampling Unit The Ampac Duct Sampling Unit is designed to monitor levels of smoke in air ducts operating in air speeds of 0.5 to 20 meters per second. The duct smoke detector can be fitted to any wall of a ventilation duct and has two tubes that extend into the duct through punched holes. The perforated sampling tube is placed in the airflow upstream of the exhaust tube which causes a pressure differential in the duct detector. Air is sucked up the sampling tube, across the detector and exhausted back into the air duct.
• E asily accessible wire clamping terminals ensure secure and fast termination • Clear cover hence the alarm LED on the detector is visible at all times • Unique self-sealing test port allows the dispensing of test smoke via a needle into the duct smoke detector to be tested without the need to remove the cover • Sampling pipes available in 4 lengths • Weather resistant enclosure Approvals: C-tick, AS1603-13 Housing Cover Dimension Temperature Range Humidity Weight
Using the 360mm sampling pipe supplied, an air duct of up to 560mm can be monitored. For duct widths greater than 560mm, three other lengths of sampling pipe are available: 1. For duct width 300mm to 750mm 2. For duct width 750mm to 1500mm 3. For duct width 1500mm to 3000mm
Grey - ABS Transparent - ABS 115H x 340W x 60D mm 0 to +60°C Up to 85%, no condensation 5.5 kg
Duct Sampling Unit inc XP95 Detector Base Duct Probe 300mm to 750mm Sampling Pipe Duct Probe 750mm to 1500mm Sampling Pipe Duct Probe 1500mm to 3000mm Sampling Pipe XP95 Optical Smoke Detector Discovery Multisensor Detector
214-0051 214-0060 214-0061 214-0062 201-0003 201-0094
Note: The detector is sold separately to the duct sampling unit
z B oth sampling and exhaust pipes are fitted to the back box without the need for tools making installation easier z The cover of the duct smoke detector is monitored to ensure working integrity and if removed, causes a fault to appear at the fire alarm control panel
AUS / PAGE 69
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
DETECTORS
Discovery Intelligent Detectors Discovery is a range of high-specification, intelligent fire detectors developed to meet the requirements of sophisticated systems while providing engineers with an additional dimension in fire protection capability. Discovery has a ‘distributed intelligence system’ where decisions are made in the detector head as well as at the control panel. Drift compensation is also incorporated into the detector, allowing it to adapt to dirty or dusty environments reducing false alarms.
• Rejection of transient signals • Flashing LED option • Five response modes for ease of optimisation to changing environments • Drift compensation to ensure constant sensitivity • Four bytes of non-volatile memory for user data • Alarm flag for fast alarm reporting • Conventional alarm facility during control panel processor fault • 360° visibility in alarm • Compatible with XP95 systems • Insect resistant
AUS / PAGE 70
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
DETECTORS
APOLLO DISCOVERY Intelligent
Discovery Heat Detector The Discovery Heat Detector, distinguishable by the low airflow resistant case, uses a single thermistor to sense the air temperature around the detector. • • • •
Ideal in environments that are dirty or smokey under normal conditions Well suited for warehouses, loading bays and car parks Unaffected by wind or atmospheric pressure Remote test feature
CONTACT AMPAC
17-28 VDC 500μA at 24 VDC 3.4mA at 24 VDC 100Dia x 50H mm 0°C to +80°C (no icing) 0 to 95% (non condensing) IP53 160 grams
Discovery Heat Detector Discovery Heat Detector Type D Discovery Heat Detector Type C
Approvals: AS1603.1
AUS / PAGE 71
Voltage Quiescent current Alarm current Size inc base Operating temperature Relative humidity IP rating Weight inc base
HOME
CONTENTS
SEARCH
ZOOM
201-0090 201-0089
EXIT
DETECTORS
APOLLO DISCOVERY Intelligent
Discovery Multisensor Detector The Discovery Multisensor Detector comprises optical smoke and thermistor temperature sensors whose respective outputs can be split to deliver specific smoke or thermal actions respectively. This capability can aid early Alarm warning routines and other advanced detection techniques. • • • • • • •
Ideal for a wide range of applications Highly immune to false alarms Well suited for environments such as hotel bedrooms Unaffected by wind or atmospheric pressure Well suited for sensitive environments Heat only, optical only options Remote test feature
Voltage Quiescent current Alarm current Size inc base Operating temperature Relative humidity IP rating Weight inc base
17-28 VDC 500μA at 24 VDC 3.5mA at 24 VDC 100Dia x 58H mm -20°C to +60°C (no icing) 0 to 95% (non condensing) IP43 160 grams
Discovery Multisensor Detector
201-0094
Approvals: AS1603.1
Multisensor Detector Operating Modes
AUS / PAGE 72
CONTACT AMPAC
Mode
Smoke Sensitivity (grey smoke)
1 2 3 4 5
% per m % per ft 1.1 0.35 2.1 0.7 2.8 0.9 4.2 1.4 No response to smoke
HOME
CONTENTS
Temperature Sensitivity Response Type (relative) High No response to heat Low High See text
SEARCH
Minimum Time to Alarm (seconds)
Multisensor Optical Multisensor Multisensor Heat A1
ZOOM
20 30 20 20 30
EXIT
DETECTORS
APOLLO DISCOVERY Intelligent
Discovery Carbon Monoxide Detector The Discovery Carbon Monoxide (CO) Detector is good at detecting deepseated fires. Please note that CO detectors do not detect smoke particles or heat and are not universal replacements for smoke detectors. • • • • •
Voltage Quiescent current Alarm current Size inc base Operating temperature Relative humidity IP rating Weight inc base Cell life (max)
Enhanced detection capability Early response to hot fires Ideal for smouldering fires Less susceptible to false alarms caused by steam than smoke alarms Five response modes
Discovery Carbon Monoxide Detector
Approvals: AS1603.14
Relative Performance of Detectors in Test Fires
Mode
Alarm Threshold (ppm)
Minimum Time to Alarm (seconds)
1
30
60
CONTACT AMPAC
201-0102
Typical Application
Sleeping with no ambient CO
2 45 30
General use fast response such as supplementary protection in atria
3 45 60
General use and sleeping risk with some low-level CO (such as from light smoking or an unventilated gas fire)
4 60 30
General smoking area and supplementary detection of deep seated fires such as laundry rooms
5
AUS / PAGE 73
17-28 VDC 500μA at 24 VDC 3.5mA at 24 VDC 100Dia x 50H mm 0°C to +50°C (no icing) 15 to 95% (non condensing) IP43 160 grams 7 years
75
HOME
30
CONTENTS
Supplementary use in kitchen or boiler room
SEARCH
ZOOM
EXIT
DETECTORS
APOLLO DISCOVERY Intelligent Discovery Intelligent Detector Base All detectors in the Discovery range fit the Intelligent Detector Base. It is a low insertion force base with stainless steel contacts for the detector terminals. XPERT cards are supplied with all bases. • XPERT addressing • One way fit • Locking feature to prevent unauthorised removal
Size Operating temperature Relative humidity Weight
100Dia x 8H mm -20°C to +60°C (no icing) 0 to 95% (non condensing) 55 grams
XP95/Discovery Detector Base with Xpert Card
201-0004
Approvals: AS1603.1&2
Discovery Isolating Base The new style Isolating Base senses and detects short-circuit faults on loops and spurs.
Voltage Quiescent current
• Up to 20 devices may be installed between isolating bases • High brightness LED
Size Operating temperature Relative humidity Weight
17-28 VDC 47μA (non isolating) 4mA (isolating) 100Dia x 24H mm -20°C to +60°C (no icing) 0 to 95% (non condensing) 100 grams
XP95/Discovery Isolating Base with Xpert Card
Blank XPERT Card
Pre-addressed XPERT Card
A universal address card supplied with all bases. Using a coding guide, pips are removed to set the address of the inserted detector.
Pre-addressed XPERT cards are supplied with PIPs already removed.
• • • •
AUS / PAGE 74
201-0125
Simplifies and speeds up installation and commissioning Uses patented, proven technology Address remains the same, no matter how often detectors are replaced Flexibility to create any address
CONTACT AMPAC
HOME
CONTENTS
z Saves time and increases accuracy during commissioning z Pre-numbered 1-126
Blank XPERT Card Pre-addressed (1-126) Xpert Cards
SEARCH
ZOOM
38531-771 201-0013
EXIT
DETECTORS
BEAM DETECTORS Conventional
FIRERAY 2000 Optical Beam Smoke Detector The FIRERAY 2000 is a conventional infrared optical beam smoke detector. It is an End to End type beam detector and is thus less susceptible to stray reflections since any reflection goes back towards the transmitter. As a result projected Optical Beams can operate within narrower gaps than reflective types. • • • • • • •
Separate transmitter and receiver Range 10 to 100 metres Low current consumption Automatic drift compemsation 3 x selectable sensitivity threshold levels Low level control unit Optional electronic alignment tool
Operating range 10-100 metres Operating voltage 10.2VDC to 30VDC Fire relay contacts Norm open volt free 2A @ 30VDC Resistive Fault relay contacts Norm closed volt free 2A @ 30VDC Resistive Condition Alarm condition: fire relay closing May be latching or non-latching Operating temperature -20°C to +55°C (no icing) Relative humidity 0-90% (non condensing) IP rating IP50 FIRERAY 2000 Beam Detector
Approvals: AS1603-7, EN54-12 and UL268
AUS / PAGE 75
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
220-0004
DETECTORS
BEAM DETECTORS Conventional
FIRERAY 5000 Motorised Beam System The FIRERAY 5000 Optical Beam Smoke Detectors can be used to provide ‘wide area’ smoke detection. They are usually used in situations where it is impractical, inappropriate or not cost effective (installation, wiring and maintenance) to use traditional point-type detectors. It also enables coverage of a large area, at minimal cost. Optical beam smoke detectors are also ideally suited for situations that might include high ceilings, dusty and dirty environments, or environments that experience temperature extremes. • • • • • • •
Up to 4 optical beam detectors per system controller Easy fit system Ground level control Laser assisted alignment Auto-optimise beam alignment Contamination compensation Building shift compensation
Operating distance (separation) Cable length – system controller to detector (2 core screened fire resistant) Operating voltage (to system controller) Operating temperature Relative humidity IP rating
8-100 metres 100 metres 14VDC to 28VDC -10°C to +55°C (no icing) 93% (non condensing) IP54
FIRERAY 5000 Motorised Beam System System Controller, Detector and Reflector Additional Detector and Reflector
220-0008 220-0009
Approvals: AS7240-12, EN54-12 and UL268
Accessories for FIRERAY 50R/100R AWD 5000 An extensive range of accessories are available to compliment the FIRERAY product. Accessories for FIRERAY 50R/ 100R AWD 5000 Single Reflector <50m 3 x Reflector Long Range 100m Kit Universal Bracket 1 Prism Plate 4 Prism Plate Universal Ceiling Mount
AUS / PAGE 76
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
220-0007 220-0010 220-0011 220-0012 220-0013 220-0014
EXIT
INTERFACES
XP95/Discovery Intelligent Interfaces Apollo manufactures a comprehensive range of interfaces for intelligent systems which enable fire protection systems to be engineered simply and effectively without the need for custom-designed equipment. There are a variety of interfaces available to suit a number of individual applications. Standard Interfaces with Isolators are fitted with bi-directional short-circuit isolators so that they are unaffected by a single short circuit on either loop input or output. However, the Input/Output Unit and Output Unit with isolator are exceptions to this. The removal of loop power to these interfaces will cause a ‘set’ relay to ‘reset’. DIN-Rail Interfaces feature enclosures that clip to standard 35mm DIN-Rails or are screwed to the base of a larger enclosure. They enable fire system designers to determine the functions required and create multi-purpose interfaces for individual sites. Optimum protection can be provided when using the built-in isolator models.
• Easy to install • Well protected • Modular design • A neat solution
AUS / PAGE 77
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
INTERFACES
AMPAC INPUT/OUTPUT DEVICES Intelligent
Single Input Device (SID) The Single Input Device is an addressable loop device for use on the Apollo XP95 or Discovery protocol and provides a single monitored input. • Interfaces a switch input to an Apollo addressable loop • Loop powered • One monitored input • Only one address used • Enclosure or DIN-Rail chassis mount • Status indicators can be switched on and off
Voltage Quiescent current Max current Monitored input Size – enclosure Size – DIN chassis Operating temperature Humidity IP rating – enclosure Weight – enclosure Weight – DIN chassis
17-28 VDC 1.82mA at 24 VDC 2.37mA at 24 VDC 20k normal 500 - 15k closed 132H x 82W x 55D mm 77H x 57W x 40D mm -20°C to +60°C (no icing) 0 to 95% relative humidity IP55 155 grams 75 grams
Single Input Device (SID) – Boxed Single Input Device (SID) – DIN mount
201-0300 201-0350
Single Input/Output Device (SIOD) The Single Input/Output Device is an addressable loop device for use on the Apollo XP95 or Discovery protocol and provides a single monitored input and a voltage free relay output. • Interfaces a switch input and a relay output to addressable loop • Loop powered • One monitored input • Single relay with clean changeover contact • Only one address used • Enclosure or DIN-Rail chassis mount • Status indicators can be switched on and off
Voltage Quiescent current Max current Relay contact rating Monitored input Size – enclosure Size – DIN chassis Operating temperature Humidity IP rating – enclosure Weight – enclosure Weight – DIN chassis
17-28 VDC 1.74mA at 24 VDC 6.84mA at 24 VDC 1A at 24 VDC clean changeover 20k normal 500 - 15k closed 132H x 82W x 55D mm 77H x 57W x 40D mm -20°C to +60°C (no icing) 0 to 95% relative humidity IP55 155 grams 75 grams
Single Input/Output Device (SIOD) – Boxed Single Input/Output Device (SIOD) – DIN mount
AUS / PAGE 78
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
201-0301 201-0351
EXIT
INTERFACES
AMPAC INPUT/OUTPUT DEVICES Intelligent
Three Input Device (3ID) The Three Input Device is a versatile loop-powered three monitored input unit device for use on the Apollo XP95 or Discovery protocol. • Interfaces three switch inputs to addressable loop • Loop powered • Three monitored inputs • Only one address used • Enclosure or DIN-Rail chassis mount • Status indicators can be switched on and off
Voltage Quiescent current Max current Monitored input Size – enclosure Size – DIN chassis Operating temperature Humidity IP rating – enclosure Weight – enclosure Weight – DIN chassis
17-28 VDC 1.45mA at 24 VDC 3.54mA at 24 VDC 20k normal 500 - 15k closed 200H x 150W x 60D mm 98H x 72W x 40D mm -20°C to +60°C (no icing) 0 to 95% relative humidity IP41 500 grams 125 grams
Three Input Device (3ID) – Boxed Three Input Device (3ID) – DIN mount
201-0308 201-0358
Three Input/Output Device (3IOD) The Three Input/Output Device is a versatile loop-powered unit for use on the Apollo XP95 or Discovery protocol. It provides three monitored inputs and three voltage free relay outputs. • Interfaces three switch inputs and three relay outputs to addressable loop • Loop powered • Three fault monitored input • Three relays with clean changeover contact • Only one address used • Enclosure or DIN-Rail chassis mount • Status indicators can be switched on and off
Voltage Quiescent current Max current Relay contact rating Monitored input Size – enclosure Size – DIN chassis Operating temperature Humidity IP rating – enclosure Weight – enclosure Weight – DIN chassis
17-28 VDC 2.06mA at 24 VDC 19.23mA at 24 VDC 1A at 24 VDC clean changeover 20k normal 500 - 15k closed 200H x 150W x 60D mm 98H x 72W x 40D mm -20°C to +60°C (no icing) 0 to 95% relative humidity IP41 500 grams 125 grams
Three Input/Output Device (3IOD) – Boxed Three Input/Output Device (3IOD) – DIN mount
AUS / PAGE 79
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
201-0309 201-0359
EXIT
INTERFACES
AMPAC INPUT/OUTPUT DEVICES Intelligent
Three Input/Output Device (3IOD) EP – Externally Powered The Three Input/Output Device EP is an externally powered unit device for use on the Apollo XP95 or Discovery protocol. Using an external 24VDC power supply, each device draws a minimum amount of loop current and provides three monitored inputs and three voltage free relay outputs. • Interfaces three switch inputs and three relay outputs to addressable loop • Externally powered • Three fault monitored input • Three relays with clean changeover contact • Only one address used • Enclosure or DIN-Rail chassis mount • Status indicators can be switched on or off
Voltage Quiescent current – loop Quiescent current – external Max current – loop Max current – external Relay contact rating Monitored input Size – enclosure Size – DIN chassis Operating temperature Humidity IP rating – enclosure Weight – enclosure Weight – DIN chassis
17-28 VDC 1.51mA at 24 VDC 5.08mA at 24 VDC 7.20mA at 24 VDC 19.55mA at 24 VDC 1A at 24 VDC clean changeover 20k normal 500 - 15k closed 200H x 150W x 60D mm 98H x 72W x 40D mm -20°C to +60°C (no icing) 0 to 95% relative humidity IP41 500 grams 125 grams
Three Input/Output Device (3IOD) EP – Boxed Three Input/Output Device (3IOD) EP – DIN mount
201-0310 201-0360
Alarm Acknowledgement Facility The Alarm Acknowledgment Facility (AAF) is a loop powered addressable device that helps reduce the costly consequence of an unwanted alarm. • • • • • • • • • •
L oop Powered Addressable Device Built in Short Circuit Isolator Easy configuration of Acknowledge and Investigate periods Event logging of AAF sequence Allows a group of detectors to be assigned to a nominated AAF Aesthetically pleasing single gang Clipsal 2000 wall plate Investigate status displayed at FACP and all associated LCDA’s Audible warning is 75dB @ 1m from the built in buzzer On board visual indication for “polling”, Fire and Fault status Remote ‘Hush’ button input terminals available
Operating Voltage Quiescent Current Alarm Current Address Setting Dimension Material Weight
21 to 28 VDC (loop powered) 900μA at 24VDC <8mA at 24VDC 1 to 126 Single gang Clipsal plate High impact ABS (white) 45 grams
Alarm Acknowledgement Facility – Vertical Alarm Acknowledgement Facility – Horizontal
226-0002 226-0004
Approvals: AS7240 and AS4428
AUS / PAGE 80
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
INTERFACES
AMPAC INPUT/OUTPUT DEVICES Intelligent
Loop Powered Zone Interface Device (LZID) AMPAC’s Loop Powered Zone Interface Device (LZID) is designed to connect to the analogue loops in any of AMPAC’s addressable range of fire alarm control panels (FACP’s). • • • • • •
S ingle Conventional Zone Input Apollo XP95 & Discovery protocol Supports up to 40 conventional detectors Remote LED Output Short Circuit Isolation Programmable EOL (3K3Ω, 6K2Ω or 10uF)
Operating Voltage Zone Voltage (Loop Voltage ≥21V) End Of Line Values Quiescent Current (EOL Fitted, Zone oltage = 22V and no detector load Alarm Current (remote LED not fitted) Alarm Current (remote LED fitted) No LZID’s / Loop
16Vdc – 27Vdc 17 – 22Vdc 3K3Ω 6K2Ω
12mA 9mA 6mA 28.5mA 28.5mA 28.5mA 32mA 32mA 32mA 12 x 250mA Loop 24 x 500mA Loop 40 Max 0°C to +70°C
No. Detectors / Zone Operating temperature Dimensions DIN Mount Enclosed / Boxed Weight DIN Mount Enclosed / Boxed
98 (L) x 72.5 (W) x 40mm (D) 200 (L) x 150 (W) x 60mm (D) 140g 460g
Loop Powered ZID (DIN Mount) Loop Powered ZID (Enclosed)
AUS / PAGE 81
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
10uF
4210-0004 4210-0005
EXIT
INTERFACES
XP95/DISCOVERY Intelligent
Input/Output Unit with Isolator The Input/Output unit with Isolator provides a voltage free, single, pole, change-over relay output, a single, monitored switch input and an unmonitored, non-polarised opto-coupled input. • • • • • •
It can report fault, switch open and switch closed levels Three visible LEDs Loop powered Voltage free Capable of switching up to 1A at 30V Built-in short circuit isolator (fitted on 55000-847)
Approvals: AS4428.1
Voltage Quiescent current Max current Relay contact Opto input Monitored input voltage Operating temperature Relative humidity IP Rating Size Weight
17-28vdc 1.2mA at 24vdc 3.5mA at 24vdc 1A at 30vdc 35vdc max 9-11vdc -20°C to +70°C (no icing) 0 to 95% (non condensing) IP54 150W x 90H x 48D mm 240 grams
Input Unit with Isolator Input Unit (no Isolator) Output Unit with Isolator Output Unit (no Isolator)
201-0151 201-0007 201-0152 201-0008
Zone Monitor with Isolator The Zone Monitor with Isolator powers and controls the operation of a zone of up to 20 Apollo Series 65 or Orbis fire detectors from a Discovery or XP95 Loop. • Loop powered • Visible LED • Built-in short circuit isolator (fitted on 55000-845) Approvals: AS4428.1
Voltage Quiescent current Alarm current EOL resistor value Maximum capacitor on zone terminals Zone voltage Operating temperature Relative humidity IP Rating Size Weight
17-28vdc 4mA + detector load 11mA at 24vdc 5.1k ¹⁄₃ watt 50µF 19V ± 1V -20°C to +70°C (no icing) 0 to 95% (non condensing) IP54 150W x 90H x 48D mm 230 grams
Discovery/XP95 Zone Monitor with Isolator Discovery/XP95 Zone Monitor (no Isolator)
AUS / PAGE 82
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
201-0126 201-0012
EXIT
INTERFACES
XP95/DISCOVERY Intelligent
Sounder Control Unit with Isolator The XP95 Sounder Control Unit with Isolator is used to control the operation of a zone of conventional sounders and report their status to the control panel. • Allows sounders to be operated continuously or be pulsed, 1 second on 1 second off • May be synchronized when in pulsed operation Approvals: AS4428.1
Voltage Quiescent current Loop current max External supply External quiescent current External current max Sounder circuit load max Operating temperature Relative humidity IP Rating Size Weight
17-28vdc 1.95mA at 24vdc 4.5mA 9-32vdc 1.25A 3mA at 32vdc 47mA + load 1A at 30vdc -20°C to +70°C (no icing) 0 to 95% (non condensing) IP54 150W x 90H x 48D mm 240 grams
Sounder Control Unit with Isolator Sounder Control Unit (no Isolator)
201-0127 201-0010
Three Channel Input/Output Unit with Isolator The Three Channel Input/Output unit with Isolator provides three voltage free, single pole, change-over relay outputs, and three monitored switch inputs. • Supervises one or more normally-open switches on each of the three inputs • Loop powered • Capable of switching up to 30V at 1A on each of the three outputs • Built-in short circuit isolator Approvals: AS4428.1
AUS / PAGE 83
CONTACT AMPAC
Voltage Quiescent current Max current Relay contact Monitored input voltage Operating temperature Relative humidity IP Rating Size Weight
17-28vdc 3mA at 24vdc 7.5mA at 24vdc 1A at 30vdc 9-11vdc -20°C to +70°C (no icing) 0 to 95% (non condensing) IP54 250W x 175H x 75D mm 621 grams
Three Channel Input/Output Unit with Isolator Three Channel Input/Output Unit (no Isolator)
HOME
CONTENTS
SEARCH
ZOOM
201-0175 201-0115
EXIT
INTERFACES
XP95/DISCOVERY Intelligent
Mains Switching Input/Output Unit The XP95 Loop Powered Mains Switching Input/ Output Unit provides a voltage free, single pole charge- over relay output and a monitored switch input. • • • • •
Voltage free single pole charge-over relay Monitored switch input Fault LED Input active LED Relay on LED
Voltage Quiescent current Max current Relay contact Switching capacity Monitored input voltage Operating temperature Relative humidity IP Rating Size Weight
17-28vdc 1.2mA at 24vdc 2.5mA at 24vdc 1.25kVA 9-11vdc -20°C to +70°C (no icing) 0 to 95% (non condensing) IP54 150W x 90H x 48D mm 240 grams
Mains Switching Input/Output Unit
AUS / PAGE 84
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
201-0180
EXIT
AUDIO VISUAL SIGNALLING
Audio Visual Signalling Ampac offers a wide range of Intelligent Audio Visual (AV) signalling devices for use in conjunction with its range of intelligent and conventional detectors and control panels. A versatile and functional range offering a huge choice for any application. • Sounder Bases combine an alarm sounder and detector base • Beacon Bases combine an alarm beacon and detector base • Sounder Beacon Bases combine an alarm sounder, beacon and detector base • Sounders are used to provide an audible indication of an alarm • Beacons are used to provide an visual flashing indication of an alarm • Sounder/Beacons are used to provide an audible and flashing indication of an alarm
AUS / PAGE 85
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
AUDIO VISUAL SIGNALLING
XP95/DISCOVERY INTELLIGENT SOUNDER BASES
Integrated Sounder Base The Integrated Sounder Base comprises a base sounder with integral mounting base and is for use with Discovery or XP95 ranges. It is designed for indoor use. • • • • • •
Two volume ranges – via DIP switch setting Synchronisation of ‘alert’ and ‘evacuate’ tones Individual and group addressing Unique acoustic self-test Integrated base Built-In short circuit isolator
CONTACT AMPAC
HOME
17-28 VDC 1.2mA 5mA 92dB(A) -20°C to +60°C (no icing) 0 to 95% (non condensing) IP21D 115Dia x 38H mm 140 grams
Integrated Base Sounder White Cap
Approvals: AS1670.4
AUS / PAGE 86
Voltage (polarity sensitive) Quiescent current Max current (sounder operated) Max sounder output Operating temperature Relative humidity IP rating Size Weight
CONTENTS
SEARCH
ZOOM
201-0110 201-0114
EXIT
AUDIO VISUAL SIGNALLING
XP95/DISCOVERY INTELLIGENT SOUNDER BEACON BASES
Sounder Beacon Base The Sounder Beacon Base is a loop-powered sounder and beacon combined with a standard Intelligent Mounting Base. It is used to signal a fire alarm in enclosed areas. The Sounder Beacon Base can be used either with a detector fitted or with a cap for operation as a stand-alone alarm device. • • • • • • • • •
Two volume ranges via DIP switch Beacon flash rate as per AS1670.4 Synchronisation of ‘alert’ and ‘evacuate’ tones Synchronisation of beacon flash Individual and group addressing Unique acoustic and beacon self test Enables DDA compliance Built-In short circuit isolator Beacon only variant available
Voltage (polarity sensitive) Quiescent current + Beacon Max current (sounder operated) Max current (beacon only) Max sounder output Operating temperature Relative humidity IP rating Size Weight
17-28 VDC 300µA 8mA 3.1 mA 91dB(A) -20°C to +60°C (no icing) 0 to 95% (non condensing) IP21D 115Dia x 38H mm 160 grams
Sounder Beacon Base Beacon Base White Cap
Approvals: AS1670.4
AUS / PAGE 87
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
201-0116 201-0120 201-0114
AUDIO VISUAL SIGNALLING
XP95/DISCOVERY INTELLIGENT SOUNDERS
NEW
Intelligent Open-Area Sounder (Sonos) The Intelligent Open-Area Sounder has been designed for use in open areas and can be connected to any Discovery or XP95 system. • • • • • •
Self-test fault monitoring Choice of tones Group addressing and synchronisation of alarm Weatherproof IP65 Comes with Isolating Base as standard Loop powered
CONTACT AMPAC
17-28 VDC 333µA 5mA 88-96dB(A) ±3dB(A) -10°C to +55°C (no icing) 0 to 95% (non condensing) IP65 104Dia x 95.5H mm 225 grams
Intelligent Open Area Sounder (Red) Sonos Intelligent Open Area Sounder (White) Sonos
Approvals: LPCB EN54-3/LPCB
AUS / PAGE 88
Voltage (polarity sensitive) Quiescent current Max current (sounder operated) Max sounder output Operating temperature Relative humidity IP rating Size Weight
HOME
CONTENTS
SEARCH
ZOOM
205-0100 205-0101
EXIT
AUDIO VISUAL SIGNALLING
XP95/DISCOVERY INTELLIGENT BEACONS
Loop-Powered Beacon The Loop-Powered Beacon is a local-area beacon designed for indoor use. The beacon has been developed as a supplement to sounders for use in situations where there is a risk that sounders will not be heard. • • • • • • •
High intensity LED – more reliable than xenon beacons Automatic LED check Lockable Wide angle of visibility Enables DDA compliance Synchronised flash Can be used with Discovery or XP95
Approvals: AS1670.4
Voltage (polarity sensitive) Quiescent current Max current (beacon operated) Flash rate Operating temperature Relative humidity IP rating Size Weight
17-28 VDC 150µA 3mA 1Hz -20°C to +60°C (no icing) 0 to 95% (non condensing) IP23D 115Dia x 38H mm 140 grams
Loop-Powered Beacon (Red) Loop-Powered Beacon (Clear Lens/Red Flash) Standard Flash Loop-Powered Beacon (Amber) Standard Flash
201-0118 55000-878 55000-879
NEW
Intelligent Open-Area Beacon (Sonos) The Intelligent Open-Area Beacon has been developed for use in situations where there is a risk that sounders will not be heard. It is weatherproof and can be used outside. • • • • • •
Self-test fault monitoring Weatherproof IP65 Group addressing Synchronisation of alarm Comes with Isolating Base as standard Loop powered
CONTACT AMPAC
HOME
17-28 VDC 333µA 3.1mA 1Hz -10°C to +55°C (no icing) 0 to 95% (non condensing) IP65 104Dia x 97.5H mm 205 grams
Intelligent Open Area Beacon (Red) Sonos Intelligent Open Area Beacon (Clear) Sonos
Approvals: AS1670.4
AUS / PAGE 89
Voltage (polarity sensitive) Quiescent current Max current (beacon operated) Flash rate Operating temperature Relative humidity IP rating Size Weight
CONTENTS
SEARCH
ZOOM
208-0100 208-0101
EXIT
AUDIO VISUAL SIGNALLING
XP95/DISCOVERY INTELLIGENT SOUNDER/BEACONS
NEW
Intelligent Open-Area Sounder Beacon The Intelligent Open-Area Sounder Beacon has been designed for use in open areas and can be connected to any Discovery or XP95 system. • • • • • •
Gives two functions at one point Self-test fault monitoring Choice of tones Group addressing and synchronisation of alarm Comes with Isolating Base as standard Loop powered
Approvals: AS1670.4
AUS / PAGE 90
CONTACT AMPAC
Voltage (polarity sensitive) Quiescent current Max current (sounder/beacon operated) Max sounder output Flash rate Operating temperature Relative humidity IP rating Size Weight
17-28 VDC 333µA 8mA 100dB(A) 1Hz -10°C to +55°C (no icing) 0 to 95% (non condensing) IP65 104Dia x 97.5H mm 260 grams
Intelligent Open Area Sounder Beacon (Red) Sonos Intelligent Open Area Sounder Beacon (Clear) Sonos
HOME
CONTENTS
SEARCH
ZOOM
EXIT
205-0102 205-0103
AUDIO VISUAL SIGNALLING
AMPAC STROBES
ASL-86 Strobe • Red or Amber Lens • High intensity output • ABS / Polycarbonate / Acrylic construction • Combined Red & Amber surface mount unit available
Voltage Current Rating Size inc base Flash rate Operating temperature IP rating Weight – strobe Weight – combined unit
24 VDC 140mA 10 Watts 100Dia x 88H mm 75 per minute -20°C to + 60°C IP65 182 grams 719 grams
ASL-86 Strobe (Red) ASL-86 Strobe (Amber) ASL-86 Strobe (Red & Amber) Combined Unit
AUS / PAGE 91
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
208-0007 208-0008 208-0011
EXIT
AUDIO VISUAL SIGNALLING
AMPAC STROBES (Conventional)
Sonos Low Current Visual Warning Device The SONOS Low Current Visual Warning strobes are general purpose LED strobes for fire, security and industrial applications. The strobes come with the flexibility of individual Red, Amber and Clear strobes or combined Red/Amber strobe units complete with either a flush or surface mounting plate. The strobes utilises a full faced, translucent case which provides a much larger lens area and a greater spread of light. The strobes are suitable for use with AMPAC’s EV3000 system (both single and combined) and AMPAC’s fire panels (Single only). Simple ‘twist and click’ insertion avoids wiring and connection problems. • Low current consumption • Simple ‘twist and click’ insertion • Red, Amber and Clear options • Quick connect/disconnect • IP65 weather proof options (deep base units) for indoor and outdoor use
Operating voltage Current drain Operating Temperature IP Rating Shallow IP Rating Deep Colour Base Colour Lens Approvals
17 – 60 VDC 5mA -25°C to +70°C IP21 IP65 White Red, Amber, Clear C-tick
Sonos Low Current Visual Warning Device (Red) Sonos Low Current Visual Warning Device (Amber) Sonos Low Current Visual Warning Device (Clear) Sonos Low Current Visual Warning Device (Deep Base Only)
208-0060 208-0061 208-0062 208-0064
Combined Strobe for EV3000 (Flush Mount) Combined Strobe for EV3000 IP65 (Flush Mount) Combined Strobe for EV3000 (Surface Mount)
208-0063 208-0065 208-0066
Combined Strobe for EV3000 Due to its low current draw the Sonos strokes can be connected in larger volumes onto the EV3000 visual output circuits.
AUS / PAGE 92
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
AUDIO VISUAL SIGNALLING
AMPAC STROBES (Conventional)
Strobe Sign Plate Mounts directly behind the Single Red Sonos Strobe. Used outside the main building entrance which leads fire fighters to the fire indicator panel location. Outdoor strobes should always use the deep base.
Fixing
Directly behind the Sonos Model Strobe / Beacons Painted metal 1mm 120mm W X 160mm H
Material Size Strobe Sign Plate
AUS / PAGE 93
CONTACT AMPAC
HOME
CONTENTS
SEARCH
207-0042
ZOOM
EXIT
AUDIO VISUAL SIGNALLING
AMPAC BELLS
Fire Alarm Bell 150mm • Motorised mechanism • Low current consumption • Red finish with FIRE lettering • Suitable for indoor use • Back box available – 206-0006
Voltage Operating current Size (without back box) Sound Level Operating temperature Weight
24 VDC 25mA 150Dia x 56D mm 92 dB @ 3m -10°C to +55°C (no icing) 764 grams
Bell 150mm
206-0012
Fire Alarm Bell 200mm • Red finish with FIRE lettering • Solenoid actuating mechanism • Suitable for indoor use • Back box available – 206-0006
Voltage Operating current Size (without back box) Sound Level Operating temperature Weight
19-27 VDC 100mA 200Dia x 70D mm 85 dB @ 3m -20°C to +70°C (no icing) 1.25kg
Bell 200mm 24Vdc
206-0001
Bell Back Box • Allows surface mounting of bell • Screw thread conduit entry and protection for wiring terminals • Red finish • Weather seal
Material Finish Depth Weight
Aluminium cast Red 40 mm 270 grams
Bell Back Box for 206-0012 and 206-0001
AUS / PAGE 94
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
206-0006
EXIT
AUDIO VISUAL SIGNALLING
AMPAC KEY HOLDERS
Key Holder – D2 • Provides a visible place to locate a key used for emergency access • Red finish • Instructions on glass • Break glass operation similar to a manual call point • Suitable for indoor use
AUS / PAGE 95
CONTACT AMPAC
HOME
CONTENTS
Size Finish Weight
100Dia x 32D mm Red 130 grams
Key Holder – D2 Spare Glass – D2
SEARCH
215-0003 215-0004
ZOOM
EXIT
AUDIO VISUAL SIGNALLING
AMPAC REMOTE INDICATORS
Fire Alarm Remote Indicator – Round • Detector activation indicator • 5mm Red LED • Compact size • Modern styling • For conventional or analogue detectors • Choice of legend
AUS / PAGE 96
CONTACT AMPAC
HOME
Voltage Current at 24v Size Weight
24 VDC 1.5mA 74Dia x 16H mm 26 grams
Remote Indicator – Blank Remote Indicator – Fire Alarm in Concealed Space Remote Indicator – Fire Alarm in Roof Space Remote Indicator – Fire Alarm in Room Remote Indicator – Fire Alarm in Duct Remote Indicator – Fire Alarm in Cupboard Remote Indicator – Fire Alarm Under Floor Remote Indicator – Fire Alarm in Return Air Remote Indicator – Fire Alarm in Exhaust Duct Remote Indicator – Fire Alarm in Supply Air Duct Remote Indicator – Fire Alarm in Ceiling Remote Indicator – Fire Alarm Above Remote Indicator – Fire Alarm Remote Indicator – Detector Activated
CONTENTS
SEARCH
ZOOM
209-0001 209-0004 209-0005 209-0006 209-0007 209-0008 209-0009 209-0010 209-0011 209-0012 209-0013 209-0014 209-0020 209-0023
EXIT
AUDIO VISUAL SIGNALLING
AMPAC REMOTE INDICATORS
Indicator / Buzzer & Indicator / Buzzer with Mute • Alarm activation indicator and buzzer • 10mm red flashing LED • Buzzer (with mute facility) • Modern styling
Indicator / Buzzer Voltage 24 VDC Current at 24v 27mA LED flash rate 45 per minute Buzzer 3.8kHz @ 114dBA Size 70H x 110W x 10D mm Weight 64g Indicator / Buzzer with Mute Voltage 24 VDC Current at 24v 43mA LED flash rate 45 per minute Buzzer 3.8kHz @ 114dBA Size 70H x 110W x 10D mm Weight 89g Flashing Indicator / Buzzer Flashing Indicator / Buzzer with Mute Switch
AUS / PAGE 97
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
209-0017 209-0016
EXIT
AUDIO VISUAL SIGNALLING
KLAXON SONOS SOUNDER BEACON
Sonos Sounder Beacon A general purpose electronic sounder beacon for fire, security and industrial applications. Deep base units have weatherproof protection to IP65 and can be used in all locations both indoors and outdoors. A full faced, translucent sounder case rather than a separate add-on beacon gives a much larger lens area and a greater spread of light. • • • • • •
Audibility at 1m (tone dependent) Tones Voltage Current
Up to 106dB (A) 32 17-60V DC 4-45mA (sounder) 5mA (beacon) IP65 (deep base) -25°C to +70°C 215 grams (shallow base) 250 grams (deep base)
IP Rating Operating temperature Weight
Simple `First Fix` installation – TimeSaver base Quick connect/disconnect Tone and volume can be preset or adjusted off-base Weatherproof to IP65 (deep base units) Low current LED beacon Sounder and beacon can be controlled separately
Red Lens Sonos LED Beacon, shallow base Deep Base (IP65) Other Colour Combinations Available on Request.
Approvals: EN54-3/LPCB
AUS / PAGE 98
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
205-0105 208-0067
AUDIO VISUAL SIGNALLING
ELECTRONIC SOUNDERS
Vector Sounder • AS1670.4 – signal only • Externally powered - low current consumption • Volume control adjustment • Built-in synchronising circuitry with sounders on the same circuit • Can be installed as a sounder base for Apollo detectors or a surface mount sounder when used in conjunction with the optional lid • Low profile • Available as standard with an XP95 universal base fitted (complete with opto - interface board) so the sounder can be controlled via the remote LED output of the XP95 detector Approvals: AS1670.4
Operating voltage Supply current Evac Supply current Alert Signal output Max. Output level Evac Volume control IP rating Temperature range Construction Dimension (mm)
8 to 35 VDC 15mA @ 24VDC 8 mA @ 24VDC AS1670.4 – signal only 91 dBA @ 1 metre with detector 93 dBA @ 1 metre with lid -30dBA IP42 -20 to + 70°C ABS 106Ø x 35h (Sounder & lid only)
Vector Sounder Vector Sounder Lid
205-0077 205-0017
Vantage Sounder • Selectable signals to AS1670.4 • High output level – up to 100 dB • 3 selectable output levels • Low current consumption for rated output • 2 or 3 wire configuration • Automatic signal changeover facility • Excellent lateral sound dispersion • Built-in synchronising circuitry • Surface mounted • Quick-fit deep base option • Head to base locking
Voltage Volume setting Current (mA @ 27VDC ) Sound Output (dB @ 1m) Signals Size (shallow base) Size (deep base) Temperature range Humidity IP Rating (shallow) IP Rating (deep) Weight
Approvals: AS1670.4
AUS / PAGE 99
CONTACT AMPAC
12 to 35 VDC Low Med High 7 12 19 85 95 100 AS1670.4 94 Dia x 85 H mm 93 Dia x 102 H mm -20°C to +70°C 0 to 95% IP43 IP65 193 grams (deep base +5g)
Vantage Sounder Red with Shallow Base Vantage Sounder White with Shallow Base Deep Base Only Red Deep Base Only White
HOME
CONTENTS
SEARCH
ZOOM
205-0062 205-0063 205-0064 205-0065
EXIT
AUDIO VISUAL SIGNALLING
ELECTRONIC SOUNDER/BEACONS
Vantage Combi • • • • • • • • • • • •
Signals to AS1670.4 High brightness LED strobe High output level – up to 100dB 3-level selectable sound output levels Low current consumption less than 70mA 2 or 3-wire configuration Automatic signal changeover facility ABS plastic – available in red or white Excellent lateral sound dispersion Built-in synchronising circuitry Surface mounted Quick-fit lockable base (both shallow and deep base)
Voltage Volume setting Current (mA @ 27VDC ) Sound Output (dB @ 1m) Signal Flash rate Size (shallow) Size (deep) Temperature range Humidity IP Rating (shallow) Weight
Approvals: AS1670.4
AUS / PAGE 100
CONTACT AMPAC
18 to 35 VDC Low Med High 11 18 30 85 95 100 AS1670.4 1 per sec 93 Dia x 90 H mm 93 Dia x 107 H m -20°C to +70°C 0 to 95% IP43 221 grams (deep base +5g)
Vantage Combi Red with Shallow Base Vantage Combi White with Shallow Base Deep Base Only Red Deep Base Only White
HOME
CONTENTS
SEARCH
ZOOM
205-0066 205-0067 205-0064 205-0065
EXIT
ANCILLARIES
Ancillaries Ampac offers a wide range of Intelligent Ancillary devices for use in conjunction with its range of intelligent and conventional detectors and control panels. A versatile and functional range offering a huge choice for any application. • Power Supplies • Manual Call Points • Fittings • Occupant Warning Systems- Amplified Sound Systems • Electro Magnetic Door Holders • Document Cabinets • Test Equipment • Sealed Rechargeable Lead Acid Batteries
AUS / PAGE 101
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
ANCILLARIES
POWER SUPPLIES
MultiAmp PSU The MultiAmp PSU is a general purpose regulated power supply unit.
MultiAmp PSU ABS
• Available in 2A and 3A versions • Fault Relay Output • Fault indicator and Resettable Buzzer • Earth monitoring • Available in ABS (BX1) • Available in Metal cabinets (BX10) shallow and deep versions • 2.5mm² cable terminals A set of two 7Ahr batteries may be housed in the BX1 and BX10 standard cabinet and a set of two 12Ahr batteries in the BX10 deep cabinet. (Maximum size based on Ampac battery specifications) The unit incorporates temperature sensing and compensation whereby a change in ambient temperature adjusts the battery charging voltage. The power supply will signal a Low Batt fault at 21.3 VDC.
MultiAmp PSU Metal
AUS / PAGE 102
Approvals: C omplies with AS4428/AS7240
CONTACT AMPAC
HOME
CONTENTS
Mains Supply Operating Voltage Supply Current Operating Temperature Relative Humidity Battery Capacity: BX1 and BX10 BX10 Deep Cabinet Maximum Charge Current Fault Relay Dimensions: ABS Cabinet (BX1) Metal Cabinet (BX10) Metal Cabinet (BX10 DEEP)
190 – 264 VAC 27.5 VDC ± 0.2 VDC 2A Current limited (2Amp Version) 3A Current limited (3Amp Version) 0°C to +40°C 25% - 75% 2 x 7Ahr 12V Sealed Lead Acid 2 x 12Ahr 12V Sealed Lead Acid 400mA (2A) 600mA (3A) NO,C,NC Contact rating: 1A @ 30VDC 300mm (H) x 360mm (W) x 100mm (D) 300mm (H) x 360mm (W) x 100mm (D) 300mm (H) x 360mm (W) x 200mm (D)
MultiAmp PSU 2A AS/EN Version (ABS BX1) MultiAmp PSU 3A AS/EN Version (ABS BX1) MultiAmp PSU 2A AS/EN Version (Metal BX10) MultiAmp PSU 3A AS/EN Version (Metal BX10) MultiAmp PSU 2A AS/EN Version (Metal BX10 Deep Cabinet) MultiAmp PSU 3A AS/EN Version (Metal BX10 Deep Cabinet) BX10 Surround
SEARCH
ZOOM
EXIT
4510-2110 4510-2120 4510-2210 4510-2220 4510-2310 4510-2320 ENC3016-A
ANCILLARIES
POWER SUPPLIES
FastSense Power Supply Unit • 2A power supply (incorporating battery charger) • Status indication – “POWER ON”, “BATTERY HIGH”, “BATTERY LOW”, “BATTERY FAIL” • Battery test facility • Termination for power supply output – Clearly labelled and adequate amount of room to terminate • Panel knockouts – top, side and rear of cabinet • Optional 6A power supply / battery charger may be fitted to the FastSense PLUS version
Operating voltage Output voltage Max output current Battery capacity: FastSense 25 & FastSense 100 versions FastSense PLUS version Dimensions: FastSense 25 & FastSense 100 versions FastSense PLUS version Material Finish
240 VAC 27 VDC 2 Amps @ 27.6 VDC 7 Ah 12 Ah 300 H x 350 W x 130 D mm 320 H x 500 W x 160 D mm 1.6 mm Mild steel Powder coated Oyster Grey
FastSense PSU – FastSense 25 & FastSense 100 versions FastSense PSU – FastSense PLUS version
AUS / PAGE 103
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
216-0065 216-0066
ANCILLARIES
Manual Call Points – Conventional
Manual Call Point – ACP-04 • Double terminal, wire protected connectors for independent input and output connections when looping to other devices • Protective film prevents glass from splintering when broken • Open or close circuit operation • 20 mm conduit entries • Testing and resetting the unit with key supplied • High reliability micro-switch operation • Manufactured from high impact plastic and resistant to heat • 470Ω in-line resistor
Current Rating
3A @ 12/24 VDC 1.5A @ 48 VDC H 88 x W 88 mm D 59 mm – surface mounted D 27 mm – flush mounted Single pole micro 6 x 2.5mm2 screw 470Ω (N/O operation only) High impact ABS -5°C to +70°C 0 – 95% non-condensing IP 24D 153 grams
Size Switch Type Cable termination In-Line Resistor Material Operating Temperature Humidity IP rating Weight Manual Call Point – ACP-04 Red Manual Call Point – ACP-04 Yellow Manual Call Point – ACP-04 White Manual Call Point – ACP-04 Green Manual Call Point – ACP-04 Protective Cover Manual Call Point – ACP-04 Glass
AUS / PAGE 104
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
213-0060 213-0061 213-0062 213-0063 213-0057 213-0058
EXIT
ANCILLARIES
Manual Call Points
Manual Call Point – Conventional FP2 • • • • • • •
Re-setable operation No broken glass or frangible element to replace Tested by actual operation Fluorescent band indicates call point has been operated Open or closed circuit operation Surface and Flush mountable Transparent lift up cover available
Contact rating
5A @ 30 VDC 10A @ 250 VAC 87H x 87 W x 54 D mm 87H x 87 W x 16 D mm Single pole High impact ABS -10°C to +70°C IP44 200 grams
Size (surface mount) Size (flush mount) Switch type Material Operating Temperature IP rating Weight FP2 Red FP2 White FP2 Protective Cover
213-0021 213-0022 213-0023
Manual Call Point – Conventional Weatherproof • Suitable for outdoor use • Hermetically sealed switches • Back box supplied
Contact rating Size Switch type Material Temperature range IP rating Weight
5A @ 24 VDC 110H x 110W x 65Dmm Single Pole High Impact ABS -10°C to +70°C IP67 200 g
Manual Call Point – Conventional Weatherproof
AUS / PAGE 105
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
213-0045
EXIT
ANCILLARIES
Manual Call Points
XP95 Manual Call Point The XP95 Manual Call Point is compliant with EN54-11. The address of each call point is set at the commissioning stage by means of a seven segment DIL switch. The device features plug and play terminal connections and a resettable element. • • • • •
Plug-and-play terminal connectors for fast wiring Allows wiring continuity testing before fitting Isolated version available Reports an alarm in under 0.2 seconds Resettable element
Voltage Quiescent current Alarm current Address method Size (surface mount) Operating temperature Relative humidity IP rating Weight
17-28 VDC 100μA at 24VDC 4mA 7 segment DIL switch 93H x 89W x 59.5D mm -20°C to +60°C (no icing) 0-95% (non condensing) IP45 190 grams
XP95 Manual Call Point (Surface) XP95 Manual Call Point with Isolator (Surface) XP95 Manual Call Point Protective Cover
Approvals: AS1670.1 and EN54-11
213-0050 213-0051 213-0064
Intelligent Waterproof Manual Call Point The Intelligent Waterproof Manual Call Point has been designed for use outdoors and in places where moisture can occur. • • • •
Plug and play terminal connections for fast wiring Allow wiring continuity testing before fitting Isolated version available Resettable element
Approvals: AS1670.1 and EN54-11
Voltage Quiescent current Alarm current Address method Size (surface mount) Operating temperature Relative humidity IP rating Weight
17-28 VDC 230μA 2mA 7 segment DIL switch 87H x 87W x 54D mm -20°C to +70°C (no icing) 0-95% (non condensing) IP67 400 grams
Intelligent Waterproof Manual Call Point Intelligent Waterproof Manual Call Point with Isolator
AUS / PAGE 106
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
213-0066 213-0067
EXIT
ANCILLARIES
Manual Call Points
XP95 Intrinsically Safe Manual Call Point The XP95 IS Manual Call Point is based on the standard weatherproof model. It features an ‘interrupt’ facility to provide fast response to an alarm.
• Reports an alarm in under 0.2 seconds • Waterproof • IP67 Approvals: AS1670.1 and EN54-11
Voltage Quiescent current Alarm current Address method Size Operating temperature Humidity IP rating Weight Classification
14 to 22 VDC 230uA 2mA 7 segment DIL switch 124H x 124W x 60D mm -20°C to +60°C (no icing) 0 to 95% IP67 400 grams E Ex ia IIc T5
XP95 Intrinsically Safe Manual Call Point
AUS / PAGE 107
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
55100-940
EXIT
ANCILLARIES
Fittings
Wall Boxes • Used for flush mounting devices such as manual call points and sounders • Suitable for MCP models ACP-01 & FP2 • Suitable for ‘Vara’ sounder
Size
Metal Plastic Weight Metal Plastic
72H x 72W x 47D mm 72H x 72W x 35D mm 153 grams 47 grams
Wall Box Metal Wall Box Plastic
AUS / PAGE 108
CONTACT AMPAC
HOME
CONTENTS
SEARCH
268-0002 268-0009
ZOOM
EXIT
ANCILLARIES
Occupant Warning Systems
Amplified Sound System – EV20 • Single zone amplified sound system for occupant warning • Signals to AS1670.4 • Open and short circuit speaker line monitoring and protection • Manual control / isolation facility • Volt free Fire Alarm Control Panel input (latching) • Adjustable volume control • Automatic changeover between tones • Fault output • P.A. microphone input (optional) • Verbal messaging (optional) Approvals: AS1670.4
Voltage Quiescent current Max current Max output power Output voltage Signals Size - main board Size - controls Tone timeout
27 VDC 41mA 650mA 20 Watts 100 VAC RMS AS1670.4 180L x 82W x 55H mm 90L x 35W x 40H mm 0, 30, 60, 120, 180, 240 or 300 secs 690 grams
Weight Amplified Sound System – EV20 Verbal Message EV20/60/120 Microphone Upgrade Kit
222-0020 222-0026 222-0007
Amplified Sound System – EV40 • Single zone amplified sound system for occupant warning • Signals to AS1670.4 • Open and short circuit speaker line monitoring and protection • Manual control / isolation facility • Volt free Fire Alarm Control Panel input (latching) • Adjustable volume control • Automatic changeover between tones • Fault output • P.A. microphone input (optional) • Verbal messaging (optional)
Voltage Quiescent current Max current Max output power Output voltage Signals Size - main board Size - control card Tone timeout
27 VDC 140mA 2.8A 40 Watts 100 VAC RMS AS1670.4 170L x 90W x 60H mm 90L x 35W x 40H mm 0, 30, 60, 120, 150, 180, 210, 240, 270, 300, 360, 420, 480 or 540 secs 900 grams
Weight
Approvals: AS1670.4
Amplified Sound System – EV40 Verbal Message EV40 Microphone Upgrade
AUS / PAGE 109
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
222-0021 222-0013 294-0001
EXIT
ANCILLARIES
Occupant Warning Systems
Amplified Sound System – EV60 • Single zone amplified sound system for occupant warning • Signals to AS1670.4 • Open and short circuit speaker line monitoring and protection • Manual control / isolation facility • Volt free Fire Alarm Control Panel input (latching) • Adjustable volume control • Automatic changeover between tones • Fault output • P.A. microphone input (optional) • Verbal messaging (optional) Approvals: AS1670.4
Voltage Quiescent current Max current Max output power Output voltage Signals Size - main board Size - controls Tone timeout
27 VDC 140mA 3.9A 60 Watts 100 VAC RMS AS1670.4 180L x 82W x 55H mm 90L x 35W x 40H mm 0, 30, 60, 120, 180, 240 or 300 secs 2.75 kg
Weight Amplified Sound System – EV60 Verbal Message EV20/60/120 Microphone Upgrade Kit
222-0022 222-0013 222-0007
Amplified Sound System – EV120 • Single zone amplified sound system for occupant warning • Signals to AS1670.4 • Open and short circuit speaker line monitoring and protection • Manual control / isolation facility • Volt free Fire Alarm Control Panel input (latching) • Adjustable volume control • Automatic changeover between tones • Fault output • P.A. microphone input (optional) • Verbal messaging (optional) Approvals: AS1670.4
AUS / PAGE 110
CONTACT AMPAC
Voltage Quiescent current Max current Max output power Output voltage Signals Size - main board Size - controls Tone timeout
27 VDC 260mA 8A 120 Watts 100 VAC RMS AS1670.4 170L x 210W x 85H mm 90L x 35W x 40H mm 0, 30, 60, 120, 180, 240 or 300 secs 3.7 kg
Weight Amplified Sound System – EV120 Verbal Message EV20/60/120 Microphone Upgrade Kit
HOME
CONTENTS
SEARCH
ZOOM
222-0023 222-0013 222-0007
EXIT
ANCILLARIES
Electro-Magnetic Door Holders
ADH-01 – Electro-Magnetic Door Holder • • • • • •
Available in 24VDC with 50kg/50N holding force Release switch on housing Designed for surface mounted Adjustable door mounted keeper plate Separate screw terminals to maintain monitoring integrity Rear and side cable access
Operating Voltage Operating Current Holding Force Housing Operating Temperature Dimension (mm) IP rating Weight Approval
15 to 29 VDC 55mA @ 24 VDC 50kg White High Temperature ABS -10° to +55° C 100h x 100w x 50d IP 51 750 g C-Tick
ADH-01 – Electro-Magnetic Door Holder, 50kg/50N holding force
212-0012
H1330 – Magnet • • • •
50kg/50N holding force Retains fire doors in the open position In built residual magnetism release pin Fail safe operation
Voltage Quiescent current Size exc anvil Weight inc anvil
24 VDC 60mA at 24 VDC 65H x 65W x 35D mm 420 grams
H1330 – Magnet, 50kg/50N holding force
AUS / PAGE 111
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
212-0002
EXIT
ANCILLARIES
Electro-Magnetic Door Holders
H1360 – Surface Mount • Retains fire doors in the open position • Cover in black ABS • Container in white aluminium • In built residual magnetism release pin • In built manual release switch • Fail safe operation
Voltage Quiescent current Size exc anvil Weight inc anvil
24 VDC 100mA at 24 VDC 95H x 95W x 40D mm 700 grams
H1360 – Surface Mount, 50kg/50N holding force H1360 – Surface Mount, 100kg/100N holding force
212-0003 212-0004
H1368 – Flush Mount • 50kg/50N holding force • Retains fire doors in the open position • Flush Mount • Cover in aluminium • Housing in galvanised steel • In built residual magnetism release pin • Fail safe operation
Voltage Quiescent current Size exc anvil Weight inc anvil
24 VDC 100mA at 24 VDC 120H x 76W x 41D mm 650 grams
H1368 – Flush Mount, 50kg/50N holding force
212-0006
H1369 – Floor Mount • 50kg/50N holding force • Retains fire doors in the open position • Black steel bracket, die-cast aluminium mounting • In built residual magnetism release pin • In built manual release switch • Fail safe operation
AUS / PAGE 112
CONTACT AMPAC
HOME
Voltage Quiescent current Size exc anvil Weight inc anvil
24 VDC 60mA at 24 VDC 100H x 110W x 80D mm 946 grams
H1369 – Floor Mount, 50kg/50N holding force
CONTENTS
SEARCH
ZOOM
212-0001
EXIT
ANCILLARIES
Electro-Magnetic Door Holders
H1370 – Floor or Wall Mount • 50kg/50N holding force • Retains fire doors in the open position • Black steel bracket, aluminium support • In built residual magnetism release pin • In built manual release switch • Fail safe operation •
Voltage Quiescent current Size exc anvil Base Arm 1370/15 Arm 1370/30 Weight inc anvil
24 VDC 60mA at 24 VDC 125H x 125W x 15D mm 40Dia x 150H mm 40Dia x 300H mm 1.277 kg
H1370/15 – Floor or Wall Mount – 150mm arm H1370/30 – Floor or Wall Mount – 300mm arm
212-0007 212-0008
H1351 – Anvil • Retains fire doors in the open position • Cushioned magnetic support for 50kg electromagnets • Swivel adjustment
Size Weight
65H x 64W x 48D mm 18 grams
H1351 – Anvil
212-0009
Remote Door Release • Remotely releases fire doors held open by electro magnetic door holder
Size Weight
70H x 110W x 10D mm 68 grams
Remote Door Release
AUS / PAGE 113
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
268-0003
EXIT
ANCILLARIES
Electro-Magnetic Door Holders
MultiAmp-DH The MultiAmp-DH 250mA Door Holder Supply (DHS) provides up to 250mA of current at 24 VDC to operate door holders. The unit can operate as an “Automatic Door Release System” (ADRS) or respond to a secondary control. When configured as an ADRS, conventional detectors are installed and connected directly to the DHS. The detection circuit is monitored for alarm, open, or short circuit conditions. The presence of any one of these conditions will deactivate supply to the door holders and cause doors to be released. Alternatively doors may be released by a switched VDC input to the DHS, derived normally from a Fire Alarm Control Panel (FACP) or security system. The switched VDC input must be between 8 to 30VDC to release the doors. • Mains powered 240vAC supply • On board conventional detection zone • Switches off DH power in alarm condition or atlernatively remote switched input can trigger the door to release
Mechanical Material Finish Dimension (mm) Weight
High Impact ABS White 91H X 149W x 40D (Recessed) 91H X 149W x 53D (Surface) 400g packed
Power Supply Mains Supply Voltage Door Holder Output Voltage Operating Temperature Relative Humidity
230 VAC +/- 10% @ 47-63Hz 24 VDC @ 250mA -5° to +45° C 25% to 95%
Zone Detection Circuit No of Zones Zone Monitoring Zone Current Load EOL Value No of detectors/circuit
1 (one), 2-wire system Open and short-circuit 4.8mA max 3k3 ohm 40 (Max)
Input Switched VDC Input
Inactive state: 0 to 2 VDC Active state: 8 to 30 VDC
MultiAmp-DH Flush Mount MultiAmp-DH Surface Mount
AUS / PAGE 114
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
4510-1100 4510-1101
EXIT
ANCILLARIES
DOCUMENT CABINETS
Document Cabinets AMPAC offers ABS and metal document cabinets designed to complement the range of AMPAC’s fire control panels. The cabinets can hold in excess of 100 A4 sheets of fire and security information relevant to the premises. The cabinets are fitted with a lockable front door for security and comes complete with an internal key holder bracket to allow easy storage of security keys. Whilst the ABS cabinet is available only in cool grey, there is a choice of Oyster Grey or Arch White with the metal cabinet option. • Metal and ABS versions available • Metal version available in Oyster Grey or Arch White • Provides the facility to hold documents i.e. Operation and Maintenance Manuals • Lockable front door • Internal key holder bracket • Designed to complement the AMPAC range of enclosures
AUS / PAGE 115
CONTACT AMPAC
HOME
CONTENTS
Colour
ABS – Cool Grey Metal – Oyster Grey Metal – Arch White ABS – 300H x 360W x 100Dmm Metal – 295H x 356W x 92Dmm IP30 ABS – 1kg Metal – 3kg 003 Key
Dimensions IP Rating Weight Key Type Document Cabinet ABS – Cool Grey Document Cabinet Metal – Oyster Grey Document Cabinet Metal – Arch White
SEARCH
ZOOM
4210-0010 4210-0020 4210-0021
EXIT
ANCILLARIES
TEST EQUIPMENT
Test Equipment • Access poles are used with interchangeable heads that fit onto the end of the pole • The equipment is suitable for use on a wide range of detectors • Poles are telescopic, nonconductive, toughened fibreglass • Light weight and simple to use
Telescopic Pole 204-0001
Aerosol Smoke Dispenser 204-0004
AUS / PAGE 116
CO Test Can 204-0020 250ml Smoke Can 204-0014 150ml Smoke Can 204-0015
CONTACT AMPAC
Telescopic pole – 6 metre Extension pole – 1.3 metre Universal detector removal tool Aerosol Smoke Dispenser Heat detector tester – cordless (head only) Smoke detector test set – 8.2 metre Smoke detector test set – 6.7 metre Smoke & cordless heat test set – 4.5 metre 250ml can of smoke (test set use only) 150ml can of smoke (hand held) Can of smoke for CO detectors (test set use only) Battery Baton for Cordless Tester
Cordless Heat Detector 204-0017
HOME
CONTENTS
Head Removal Tool
SEARCH
ZOOM
204-0001 204-0002 204-0003 204-0004 204-0017 204-0009 204-0010 204-0018 204-0014 204-0015 204-0020 204-0021
Smoke & Cordless Heat Test Set
EXIT
ANCILLARIES
TEST EQUIPMENT
XP95 Test Set (Loop Manager Apollo) The XP95 Test Set is a self-contained, portable test unit capable of providing a number of useful functions in relation to individual detectors, ancillary devices or complete circuits of analogue addressable devices in the Apollo intelligent ranges. The main function of the test set is to help the engineer guarantee correct loop configuration before an active control panel is installed.
Apollo XP95 Test Set Ampac XP95 Test Set
55000-870EUR 204-0016
• User friendly LCD information display • Speedy commissioning • Option for hard copy of results • No unnecessary site visits • Significant cost reductions
Discovery Programmer The Discovery Programmer is a portable test and configuration tool for Discovery smoke and heat detectors.
Discovery Programmer
53832-030
• Look up the date of manufacture • Check the drift compensation value • Display and change the operating mode • Select/de-select LED flash mode • Tests detectors • Reads approval codes
AUS / PAGE 117
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
ANCILLARIES
TEST EQUIPMENT
Flame Sensor Test Unit and Case The Flame Sensor Test Kit is a tool which is designed to test flame detectors without the need of real flames.
Flame Sensor Test Unit and Case
29600-226
• Mimics the characteristics of real flames
AUS / PAGE 118
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT
ANCILLARIES
Sealed Rechargeable Lead-Acid Batteries
Sealed Rechargeable Lead-Acid Batteries Ampac sells a comprehensive battery range for all applications requiring a reliable rechargeable power source. The wide range of sizes coupled with good cycling ability make them perfect for critical systems such as fire alarm and emergency warning systems. Designed using VRLA technology, negating the need to add water, these batteries can be applied in many critical systems requiring reliable reserve power. Available as 12V or for very large systems 2 volt cells (x12). Consideration should be given to the battery space available. If in doubt, consult your local customer service office. • VRLA technology (Valve Regulated Lead-Acid) • No topping up • Wide capacity range • Can be operated in any position without leakage • Long operating life • Many capacities available • 2 volt cells – very large systems
AUS / PAGE 119
CONTACT AMPAC
HOME
CONTENTS
Voltage (nominal) Capacity Operating temperature – charging – discharging Life expectancy – standby use Terminal
12 VDC Various -15°C to +50°C (no icing) -20°C to +60°C (no icing) 3 to 5 years Quick disconnect or receptacle M5
12 VOLT 1.2 AH SLA 50BP1.212 12 VOLT 3.0 AH 5LA 50BP312 12 VOLT 7AH SLA 50BP712 12 VOLT 12 AH SLA 50BP1212 12 VOLT 17AH SLA 50BP1712 12 VOLT 26AH SLA 50BP2612 12 VOLT 40AH SLA 50BP4012 12 VOLT 65AH 50BP6512
210-0008 210-0006 210-0016 210-0010 210-0003 210-0012 210-0013 210-0015
12 VOLT 90AH SLA 50BP9012 BATT 12 VOLT 100AH E12V100 12VOLT 120AH 50BP12012
210-0002 210-0009 210-0022
Extra large 12 Volt (consideration of battery cabinet space required) 12V 160AH 50BP16012 12 VOLT 230AH SLA 50BP23012
210-0017 210-0011
Extra large 12 Volt (consideration of battery cabinet space required) 2 Volt Cells (12 x Cells are required) 210-0018 2VOLT 250AH UPZ 2-250 210-0019 2VOLT 300AH UXL-330-2 210-0020 2VOLT 550AH UXL-550-2
210-0018 210-0019 210-0020
SEARCH
ZOOM
EXIT
CONTACT Australia Customer Service Offices
NEW SOUTH WALES & AUSTRALIAN CAPITAL TERRITORY Unit B 28-32 Egerton Street Silverwater New South Wales 2128
WESTERN AUSTRALIA 7 Ledgar Road Balcatta Western Australia 6021 Telephone: +618 9201 6110 Fax: +618 9201 6111 Email: info@ampac.net Mobile: 0421 129 163
Contact: Lester Gaskin Paul Beer
Contact: David Lehn Wes McMillan Mason Truong
VICTORIA & TASMANIA 422 Johnston Street Abbotsford Victoria 3067
QUEENSLAND 1/53 Parramatta Road, Underwood, Queensland 4119
Telephone: +613 8459 3300 Fax: +613 9416 4227 Email: info.vic@ampac.net Mobile: 0417 331 473
Telephone: +617 3462 5700 Fax: +617 3208 9355 Email: info.qld@ampac.net Mobile: 0409 630 633
Contact: Tom Stroumos Nick Vangeli Ian Siemonek
Contact: Michael Schuster Sam Adams
CONTACT AMPAC
Telephone: +618 8246 3800 Fax: +618 8340 4218 Email: info.sa@ampac.net Mobile: 0400 835 969
Telephone: +612 8866 6200 Fax: +612 9648 4932 Email: info.nsw@ampac.net Mobile: 0417 986 847
Contact: Joe Fusari David Thomas Lukasz Swietojanski
AUS / PAGE 120
SOUTH AUSTRALIA 63 Grange Road Welland South Australia 5032
HOME
CONTENTS
NORTHERN TERRITORY 2/10 Cato St, Winnellie Northern Territory, 0820
SEARCH
Telephone: +618 8911 1260 Fax: +618 8911 1261 Email: m.cavenagh@ampac.net Mobile: 0451 632 965 Contact: Matt Cavenagh
ZOOM
EXIT
CONTACT
Head Office & Administration
HEAD OFFICE & ADMINISTRATION Ampac Technologies Pty Ltd 7 Ledgar Road Balcatta Western Australia 6021 Telephone: +618 9201 6100 Fax: +618 9201 6101 Email: info@ampac.net Web: www.ampac.net
CLICK HERE TO VIEW CUSTOMER SERVICE OFFICES
As part of Ampac’s commitment to continuous improvement, specifications may change without notice. Version AUS/15-05-2012 Planned, written, designed and produced by Right Angle • www.rightangle.co.uk
AUS / PAGE 121
CONTACT AMPAC
HOME
CONTENTS
SEARCH
ZOOM
EXIT