TechnicalHandbook Where and how to implement fixed ultrasonic gas leak detection
UGLD FLANGE
WHY ULTRASONIC GAS LEAK DETECTION (UGLD)? �Field trials have indicated that gas plumes in well ventilated areas may not be detected by fixed point or open path detectors. Analysis of hydrocarbon release incidents shows that conventional gas detectors have 65% detection efficiency. The potential therefore exists for gas from undetected leaks to disperse to adjacent areas, accumulate in ventilation dead spots in the modules, or for the release to continue undetected for some time...� Health and Safety Executive in the UK, April 2010 @ www.hse.gov.uk/foi/internalops/hid/spc/spctosd05.htm
Ultrasonic gas leak detector
Conventional gas detector
Figure 1: Ultrasonic gas leak detectors do not need physical contact with the gas. They are unaffected by wind, gas dilution, and the direction of the gas plume.
W ind
Contents Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Where to Install UGLD . . . . . . . . . . . . . . . . . . . . 37 Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
1 How does UGLD Work? . . . . . . . . . . . . . . . . . . . . . 9
Applications: Gas Processing Plant . . . . . . . . . . . . . 41
Gas Release Event Tree . . . . . . . . . . . . . . . . . . . . . 11
Applications: Separation Area . . . . . . . . . . . . . . . . . 43
Total Speed of Response . . . . . . . . . . . . . . . . . . . . 12
Applications: Wellheads . . . . . . . . . . . . . . . . . . . . . 44
Detection Coverage . . . . . . . . . . . . . . . . . . . . . . . . 15
Applications: Compressor Area . . . . . . . . . . . . . . . . 45
LEL vs Leak Rate . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Gas Pressure, Leak Size and Detection Coverage . . 20
4 How to Implement and Maintain UGLDs . . . . . . . 47
Frequency and Amplitude . . . . . . . . . . . . . . . . . . . . 22
Implementation Practice . . . . . . . . . . . . . . . . . . . . . 48
UGLD Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Phase One: Where in the Project should UGLD be Implemented? . . . . . . . . . . . . . . . . . . . . . 48
2 Which Gases Can UGLD Detect? . . . . . . . . . . . . 27
Which Areas are Suited for UGLD? . . . . . . . . . . . . . 48
Example of Gases
Phase Two: Where should Individual Detectors
Hydrocarbon Gases (CxHx) . . . . . . . . . . . . . . . . . . . 30
be Installed? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Hydrogen (H2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Offshore Installation of UGLD . . . . . . . . . . . . . . . . . 51
Carbon Dioxide (CO2) . . . . . . . . . . . . . . . . . . . . . . . 30
Onshore Installation of UGLD . . . . . . . . . . . . . . . . . 56
Hydrogen Sulphide (H2S) . . . . . . . . . . . . . . . . . . . . 31
Phase Three: Detailed Engineering Considerations . 58
Condensate, 2-phase, and Liquid Leaks . . . . . . . . . 31
Choosing the Correct Height . . . . . . . . . . . . . . . . . . 58
Gases and Coverage . . . . . . . . . . . . . . . . . . . . . . . 32
Shadowing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 How to Obtain Optimal Detection Coverage . . . . . . . 60
Setting the Right Trigger Level . . . . . . . . . . . . . . . . 61
Communication Buses and Protocols . . . . . . . . . . . 71
Ultrasonic Noise Sources
Power Consumption . . . . . . . . . . . . . . . . . . . . . . . . 71
and Plant Noise Levels . . . . . . . . . . . . . . . . . . . . . . 62
Product Comparison Table . . . . . . . . . . . . . . . . . . . 72
How to Avoid Influence from Other Noise Sources and False Alarms . . . . . . . . . . . . . . . 63
6 How to Interface UGLD
Services – Maintenance . . . . . . . . . . . . . . . . . . . . . 64
and Mix with Other Technologies . . . . . . . . . . . . . . 75
Services – Onsite Mapping Survey . . . . . . . . . . . . . 65
How to Interface Detectors with the Control System . . . . . . . . . . . . . . . . . . . . . . . . 76
Phase Four: How are the UGLDs
Configuring Trigger Level
Commissioned and Tested? . . . . . . . . . . . . . . . . . . 67
and Alarm Delay Time . . . . . . . . . . . . . . . . . . . . . . 77
Services – Onsite Commissioning
Executive Action and Voting Configuration . . . . . . . 78
and Leak Simulation . . . . . . . . . . . . . . . . . . . . . . . 67
UGLD as an Independent Protection Layer
5 Which UGLD Products are Available? . . . . . . . . . 69
UGLD – SIL Rating, SIS and Risk . . . . . . . . . . . . . . . 81
in Safety Instrumented Systems . . . . . . . . . . . . . . . 79 Considerations when Specifying UGLDs Explosion Proof and Intrinsically Safe . . . . . . . . . . . 70
A Final Overview . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Sensor Element . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Explanation and Expressions . . . . . . . . . . . . . . . . . 84
Acoustic Self-Test (Self-Diagnostics) . . . . . . . . . . . . 70 Hazardous Area Approvals and Safety Integrity Levels . . . . . . . . . . . . . . . . . . . 71
Introduction Ultrasonic gas leak detection (UGLD) is a comparatively
and limitations are also discussed. Illustrations show
recent detection technique and has emerged as an
how UGLD can be deployed to provide wide area coverage
effective means of establishing the presence of gas leaks.
per device, even in noisy areas. Last, the handbook
It works especially well in open, ventilated areas where
gives guidelines on sensor placement, installation, and
other methods of gas detection may not be independent of
commissioning, as well as procedures for maintenance
ventilation. Because UGLDs respond to the source of the
of the equipment.
leak, rather than the gas itself, they complement sensors that measure gas concentration. Such application of the
All data found in this handbook is based on knowledge
technology as an additional and complementary means
obtained
of detecting gas leaks is supported by the Health and
Gassonic ultrasonic gas leak detectors since 1996.
Safety Executive (HSE) in the UK. In a recent report,
Since recommendations are based on the acoustic
the organization’s Offshore Division recommends the
characteristic of Gassonic UGLDs, Gassonic cannot be
use of a combination of sensors, with ultrasonic gas
held responsible for implementation of other types of
leak detectors providing early warning and IR detectors
UGLDs according to information found in the handbook.
identifying the gas accumulation (HSE 2004).
during
design
and
implementation
of
We hope readers will gain useful insights on ultrasonic gas
This handbook details the operation and use of UGLDs.
leak detectors and greater confidence on the application
The principles of ultrasonic detection and its strengths
of these instruments to plant safety.
Page 6
Introduction
This handbook is divided into six main sections:
The document is meant to be an active document, which will be updated frequently as more knowledge is gained.
Chapter 1
Links to web-based pages are included wherever relevant
How does UGLD Work?
to provide further documentation and better visualization
Chapter 2
of the different topics. Use the link below to subscribe to
Which Gases can UGLD Detect?
updates on material in this handbook as well as ultrasonic gas leak detection in general.
Chapter 3
Where to Install UGLD Note that ultrasonic gas leak detection is sometimes
Chapter 4
How to Implement and Maintain UGLD
referred to as acoustic leak detection (ALD) in certain countries.
Chapter 5
Which UGLD Products are Available? Chapter 6
How to Interface UGLD and Mix with Other Technologies
Updates See also www.gassonic.com/updates
Reference HSE. 2004. Fire and Explosion Strategy, Issue 1. Hazardous Installations Directorate, Offshore Division.
Introduction
Page 7
1 How does UGLD work? Fixed gas detection in open ventilated areas like offshore or onshore oil and gas facilities is generally considered problematic because the gas easily dilutes and drifts away from conventional gas sensors. Ultrasonic gas leak detectors solve this problem by detecting the airborne acoustic ultrasound generated when pressurized gas escapes from a leak. When a gas leak occurs, the ultrasound generated by the leak travels at the speed of sound, through the air, from the source to the detector. Ultrasonic gas leak detectors are non-concentration based detectors. They send a signal to the control system indicating the onset of a leak.
EVENT TREE FOR GAS RELEASE Gas Release
Immediate Ignition
Vapor Cloud Forms and Ignites
Liquid Rainout and Ignition
Explosion Occurs
Toxic Chemical
Yes
Outcome Jet Fire
Yes
Vapor Cloud Explosion
Yes No
Flash Fire
No Yes No
Pool Fire Yes
No
ULTRASONIC GAS DETECTION
CONVENTIONAL GAS DETECTION
No
Toxic Exposure No Consequences But Environmental Impact
Figure 2. The gas release event tree illustrates the sequence of events that can take place in the event of a gas release. The figure shows that UGLD responds at gas leak initiation whereas conventional detectors only respond when the gas has accumulated and formed a vapour cloud.
Page 10
How does UGLD Work?
Gas Release Event Tree The importance of speed of detection can be visualized
go undetected for hours or days before the concentration
using an event tree for gas releases. As illustrated,
becomes sufficiently high to raise an alarm.
an ultrasonic gas leak detector alarms as soon as a pressurized gas leak occurs. After the gas leak begins,
An UGLD provides the fastest response, preventing a
the gas can either be ignited or accumulate. If a gas
dangerous situation from escalating. For this reason
cloud builds up, conventional gas sensors can detect the
UGLD should be considered a first layer of protection
gas and produce an alarm. Similarly, a well placed flame
in pressurized gas installations and used together with
detector can respond to leaking gas in the event it ignites
conventional gas detection methods to secure optimal
and creates flames.
protection in outdoor or well ventilated areas. The total response time for UGLD and conventional gas detectors
The timeframe for the evolution of different scenarios
is further described on the next pages.
varies according to the location of the installation (offshore or onshore), ambient condition (wind direction and speed), gas and leak properties (leak rate and gas type), and other factors. If the gas leak takes place inside a building, the gas can quickly accumulate and prompt a point or open path detector to alarm. However, if the gas leak is outdoors or where the air current is strong, it may
How does UGLD Work?
Page 11
TOTAL Speed of Response Response time for conventional gas detectors is often
speed of response, comprising the time for diffusion to
measured in seconds. Nevertheless, this response is based
the sensor and gas accumulation:
on gas coming directly in contact with the sensor element. This can be difficult in open, well ventilated areas where
Total speed of response for conventional gas detectors
dilution and the direction of the plume can carry the gas
can be calculated as:
away from the sensor.
Ttotal = Tdetector + Tgas
Conventional Gas Detectors When it comes to the response time of a conventional gas detection system, it is important to consider the total
Tdetector is also referred to as T90 (and T50) and it simply tells how long it takes for the gas detector to reach 90%
90% response
Tdetector for UGLD Tgas for conventional detector
50% response
Figure 3
Tdetector for conventional detector
Ttotal for UGLD
T50 T90
Time
Ttotal for conventional detector Page 12
How does UGLD Work?
(or 50%) of the correct reading when 100% of full-scale
The total speed of response for an UGLD can be cal-
gas concentration is injected directly into the sensor-
culated as:
head of the detector. Tdetector is normally 15-30 seconds. Tgas tells how long it takes for a certain gas concentration
Ttotal = Tdetector + Tultrasound
to travel from the leak to the sensor. This parameter
Tdetector for an UGLD is the alarm delay time implemented
is often taken for granted simply because it is difficult
on the instrument, commonly 10-30 seconds.
to predict mainly due to changing wind directions and dilution of the gas cloud. In practice, Tgas can range from minutes to hours!
Tultrasound represents the time it takes ultrasonic noise to travel from the leak source to the detector. This is typically measured in milliseconds.
In a safety system with gas detectors, it is inadequate to use just Tdetector. One must consider the total speed of response, Ttotal, which is the only parameter that provides a true picture of the actual response time of the gas detection system. Ultrasonic gas leak detectors
The response of the UGLD is not dependent on the gas to travel to the detector, which means that it reacts much faster to the dangerous gas leak. Figure 3 on the opposite page illustrates the superior Ttotal for an ultrasonic gas leak detector.
The main advantage of an UGLD compared to a conventional gas detector is that it does not need to wait for a gas concentration to accumulate and form a potentially explosive cloud before it can detect the leak.
How does UGLD Work?
Page 13
UGLD
High noise areas Low noise areas Very low noise areas
1 2
4
8
12
15 Meter
Figure 4. The graphic shows the detection coverage characteristics for UGLD. The distances are based on the detection of methane based gas leaks using a leak rate of 0.1 kg/s as the performance standard. Page 14
How does UGLD Work?
Detection Coverage Since the sound pressure level decreases over distance at
From the illustration it could be implied that the detector
a predictable rate, operators and engineers can establish
detects gas leaks below ground, but this is rarely the
detection coverage before ultrasonic gas leak detectors
case. The only instance in which a detector responds to
are installed. The location and number of detectors can
gas leaks below ground is when the device is installed on
be planned based on plant drawings when the facility is
a grid floor, which allows ultrasound to travel through the
in the design stage. UGLDs are used to cover both large
cells in the grid with minimum impairment. An UGLD may,
outdoor facilities and single installations. UGLD detection
for example, be installed on an upper platform deck while
coverage depends on the ultrasonic background noise
providing coverage to lower decks as well.
level of the area and on the minimum gas leak rate to be detected. For the purposes of sensor allocation, plant
As shown also, the shape of the detection coverage is
environments can be divided into three types: high noise,
the same for the three plant areas, but the maximum
low noise, and very low noise, as represented in the
detection range varies according to ultrasonic background
graphic to the left.
noise. A more detailed description of specific noise levels and sensor implementation follows in Chapter 4.
The image shows a detector installed on a mounting pole 2 meters (6 feet) above ground as seen from the front. Because the sensor points down when installed, the detection coverage is greater below and to the sides of the sensor than above. Notice that when not obstructed by a floor, the detection coverage is “apple shaped�.
How does UGLD Work?
Page 15
Figure 5
Detection coverage for high, low, and very low noise levels is illustrated in the figures below. Coverage is based on detection of methane leaks using a leak rate of 0.1 kg/s as the performance standard. • High noise areas (eg compressor area) Audible noise: 90-100 dBa Ultrasonic background noise < 78 dB Alarm trigger level = 84 dB Detection coverage = 5-8 meter (16-26 ft)
• Low noise areas (eg normal process area) Audible noise: 60-90 dBa Ultrasonic background noise < 68 dB Alarm trigger level = 74 dB Detection coverage = 9-12 meter (30-39 ft)
• Very low noise areas (eg remote onshore wellhead) Audible noise: 40-55 dBa Ultrasonic background noise < 58 dB Alarm trigger level = 64 dB Detection coverage = 13-20 meter (43-66 ft) Note that very low noise areas settings are generally only used in onshore installations. How does UGLD Work?
Page 17
LEL Vs Leak rate Whereas conventional gas detectors measure gas concentrations as a percentage of the lower explosive limit (LEL) or in parts per million (ppm), the performance of ultrasonic gas leak detectors is based on the leak rate, usually measured in kilograms per second. 20% LEL
100% LEL
Figure 6: The conventional gas detector above measures gas concentration in the lower explosive limit (LEL). The LEL level measured by the sensor depends on the leak rate (mass flow rate), leak directionality, and where the sensor is positioned relative to the leak.
Page 18
How does UGLD Work?
LEL For conventional gas detection, gas concentration is
The categories developed by the body HSE are used
measured in either LEL or ppm. The term LEL is used
to define the guidelines for UGLD. For methane based
for combustible gases and is measured as a percentage.
leaks then UGLD must respond to small leaks of minimum
When the concentration of combustible gas in air reaches
0.1 kg/s.
100% LEL, an ignition of the gas causes an explosion. Guidelines for other gases are found in Chapter 2.
Leak rate The term leak rate describes the amount of gas escaping
Notice an UGLD does not measure the leak rate. The leak
from a leak per unit time. A leak can be considered large,
rate is used to set the performance criteria, and in effect
for instance, if a large quantity of gas escapes every
define, which leaks the UGLD must pick up. The UGLD
hour or every second. Conversely, a leak can be said
provides a measure of the ultrasonic sound measured
to be small if a small amount of gas jets out from the
in decibels (dB). When there is a gas leak with a leak
pressurized system over a given period.
rate of 0.1 kg/s inside the detector’s coverage area, the sound level will exceed the trigger level of the UGLD and
The leak rate, which defines how fast a potential
cause an alarm. As a result, in order to prevent injury or
dangerous gas cloud accumulates, can be divided into
loss of life, UGLDs must detect methane leaks of at least
three categories according to hazard severity:
0.1 kg/s.
· Minor gas leak < 0.1 kg/s
* Reference: HSE website, April 2010: http://www.hse.gov.uk/RESEARCH/ otopdf/2001/oto01055.pdf; page 10
· Significant gas leak 0.1 - 1.0 kg/s · Major gas leak > 1.0 kg/s
How does UGLD Work?
Page 19
Gas pressure, leak size and detection coverage Gas pressure and influence on UGLD The detection coverage illustrated in the previous section is based on a gas pressure of at least 10 bar (145 psi). There is no upper limit. Nonetheless, ultrasonic gas leak detectors can detect gas leaks from pressurized systems kept at much lower pressures. For methane, for instance, a minimum pressure of 2 bar (30 psi) is required to generate ultrasound. Use of the technology in such cases, however, results in reduced detection coverage. For allocation of UGLDs in low pressure systems the manufacturer should be consulted. Figure 7
< 2 Bar (30 psi)
Page 20
2-10 Bar (30-145 psi)
>10 Bar (145 psi)
How does UGLD Work?
Leak size and influence on UGLD
for a leak with a small hole size like 0.5 mm (0.02 in),
The leak size influences the performance of the UGLD in
the systemâ&#x20AC;&#x2122;s pressure must be almost 3,000 bar (or
the following way: the greater the leak size, the bigger the
around 43,500 psi). Since tiny pinhole leaks are found in
leak rate and thus the greater the detectorâ&#x20AC;&#x2122;s coverage
fittings especially on offshore facilities, UGLDs are neither
(assuming the gas pressure is kept constant). Some of
designed for pinhole leaks nor for big pipe ruptures.
the most frequently asked questions pertain to the leak
Pinhole leaks increase in size over time and become
size and whether the opening can be too small or too
easier to detect while pipe ruptures can be identified by the
large to create adequate levels of ultrasound.
pressure drop. Instead of considering specific hole sizes or pressures, UGLD should be related to the leak rate.
The most important thing to understand is that the leak rate can derive from an infinite number of combinations of leak size and gas pressure (gas properties also have some influence). As the hole becomes larger, the leak rate increases. However, with extremely large leaks it becomes more and more difficult to sustain the systemâ&#x20AC;&#x2122;s pressure. When the system pressure starts dropping it causes a reduction of the leak rate and thereby decrease the ultrasonic sound level. In theory, there is no limitation to the rule when the leak becomes small. However, to achieve the commonly used leak rate for methane of 0.1 kg/s
Figure 8. When the pressure is kept constant a small leak has a smaller leak rate and makes less ultrasound compared to a bigger leak.
How does UGLD Work?
Page 21
Frequency and AMPLITUDE Ultrasonic gas leak detection differs from conventional gas detection mainly because it responds to the airborne acoustic sound from the gas leak, and not by sensing the gas molecules. Two new parameters are fundamental to understand ultrasonic technology â&#x20AC;&#x201C; amplitude and frequency, where amplitude is measured in decibels [dB] and frequency is measured in Hertz [Hz].
AMPLITUDE (dB)
Frequency (Hz)
The term amplitude is the parameter that describes the
The term frequency is the parameter that describes the
sound level or volume of the acoustic sound. Imagine that
high and low pitches in acoustic sound. To illustrate this,
you sit in front of the radio and turn up the volume, the
low frequencies can be heard from the bass drums in
sound level increases and in the world of acoustics, we
music, whereas high frequencies can be heard from for
say the dB level increases.
example cymbals. This means there are low frequencies and high frequencies.
Amplitude (dB) Figure 9
104 dB
34 dB
Frequency (Hz)
0 Hz
25 kHz
70 kHz
Human hearing range Ultrasonic range detected by UGLD Page 22
Above detection range
The human ear can hear both high and low frequencies,
for example, in spaces with turbines, compressors,
but only within a certain frequency range, typically from
and other high speed rotating machines. In other areas
20 Hz to 20000 Hz (20 kHz). This frequency range is also
there is a simple mix of sound frequencies at low decibel
called the audible frequency range. Frequencies above 20
levels. This is the case in process areas with no rotating
kHz up to 100 kHz are called ultrasonic frequencies. The
equipment or in remote installations in outdoor locations.
human ear cannot hear acoustic sound in this frequency range. The UGLD is designed to ignore audible and
In very noisy plant locations where the audible noise level
lower ultrasonic frequencies and only sense ultrasonic
may be around 95 dB (very loud), the ultrasonic sound
frequencies in the range 25 kHz to 70 kHz.
level will, as a rule of thumb, be 20-30 dB lower (6575 dB) simply because the machine made noise does
An example of the relation between amplitude (dB) and
not generate a lot of ultrasonic frequencies - only a lot
frequency (Hz) is shown in Figure 9. An interactive version
of audible sound frequencies. For actual examples see
can be found on Gassonicâ&#x20AC;&#x2122;s website: www.gassonic.
Table 1 on page 62.
com/simulator/frequency_and_amplitude/ For this reason UGLDs can be installed in very noisy
Frequencies in plant ENVIRONMENTS
locations without interference from the normal audible
In normal industrial plant environments there can be a
background noise.
wide variety of acoustic sound frequencies present or there may be only a limited number. Basically it depends on the process equipment installed in various parts of the plant. In some areas there is a complex mixture of sound frequencies at high amplitude (high dB level);
How does UGLD Work?
Page 23
?
Are there any installations where UGLD cannot be used? Ultrasonic gas leak detection is only applicable when the gas is under pressure because it is the drop to atmospheric pressure that makes the leak generate ultrasound. In addition, UGLDs cannot be used to detect liquid leaks or in locations with extreme levels of ultrasonic background noise (>95 dB).
UGLD BENEFITS
• Instant detection of pressurized gas leaks – improved Total Speed of Response
Ultrasonic gas leak detection is used for pressurized gas
• Immunity to gas dilution, leak direction and windy conditions
leak detection. Its detection principle is different from that of concentration-based detectors, and consequently, shares few of the conventional devices’ vulnerabilities. Making UGLD part of the plant fire and gas detection system adds an alternative or complementary layer of protection, which may increase detection efficiency while reducing the need for a high point sensor count.
• Immunity to audible noise and lower ultrasonic noise frequencies • Wide detection coverage (area coverage up to 20 m or 65 ft radius) • Lower implementation and maintenance costs improve total cost of ownership
As the UGLD technology is based on sound propagation instead of transport of gas molecules, detectors respond to hazards at a significantly faster rate than concentrationbased sensors. The detectors are unaffected by environmental conditions like wind, leak dilution, and the direction of the leak, which indicate that they have high detection reliability. The box to the right lists the most important benefits of applying UGLD.
How does UGLD Work?
• Failsafe operation due to integrated acoustic self-test technology • Robust microphone sensor and no consumable components – ensures long lifetime (MTBF > 11 years Naval Sheltered) • Easy to operate and field test (using traceable portable test and calibration unit) • Hazardous area certification: ATEX, C-UL, IECEx, FM, CSA – and SIL certified
Page 25
2 WHICH gases can UGLD DETECT? Ultrasonic gas leak detectors can be used for any application that contains pressurized gas since UGLDs detect the leak and not the gas plume.
Figure 10: Lighter gas molecules typically create higher levels of ultrasound at the same leak rate.
Page 28
How does UGLD Work?
Which gases can UGLD detect? Ultrasonic gas leak detectors can be used for any application that contains pressurized gas since the UGLDs respond to the leak noise and not the gas itself. Ultrasonic gas leak detectors respond to leaks when gas
However, gas properties vary, which influence UGLD
is pressurized and in a gaseous, not liquid, state when
coverage and performance. For example, gas properties
it leaks.
such as molecular weight of the gas and boiling point are important factors. Tests carried out by General
When gas molecules move from a high pressure pipe or
Monitors/Gassonic indicate that gas with a low
vessel to lower or atmospheric pressure, the pressure
molecular weight and a low boiling point generates the
drop generates ultrasound. The ultrasonic sound
highest sound pressure levels (SPL) when the leak rate
pressure waves are then detected by the ultrasonic gas
(mass flow rate) is kept constant.
leak detectors. In extremely cold environments special attention should For standard applications and standard coverage, the gas
be taken to ensure the boiling point of the gas is lower
should be under a minimum pressure of 10 bar (145 psi).
than the ambient temperature. The gas, which would leak
For any application that contains pressurized gas, UGLDs
as gas under normal temperatures, may escape as liquid
can be used since they respond to the leak noise and not
due to the cold environment. In consequence, the leak
the gas itself.
may not generate adequate levels of ultrasonic sound and the detection range of the instrument may be reduced.
Which Gases can UGLD Detect?
Page 29
Example of Gases Hydrocarbon Gases (CxHx)
sparks, or static discharge. Since hydrogen molecules
UGLDs have been used for hydrocarbon gas detection
have a low molecular weight and a low boiling point, they
since the mid-1990â&#x20AC;&#x2122;s and the technology has proven
produce high ultrasonic sound levels. UGLD is therefore
effective detecting hydrocarbon gases that leak in
ideal for identifying hydrogen leaks.
a gaseous state. As previously mentioned, the specific gas properties influence detection coverage. In general,
CARBON DIOXIDE (CO2)
lighter hydrocarbons (methane, ethane, and ethylene) are
Because CO2 can only be a liquid or a supercritical fluid
detected at greater distances than heavier hydrocarbons
when pressurized, the material escapes as a gas when
(propane and propylene).
released into atmospheric pressure and temperatures above -78°C. This CO2 gas generates high levels of
Hydrogen (H2)
ultrasound that can be detected by UGLDs.
Due to its chemical properties, hydrogen poses unique challenges in the plant environment. Hydrogen gas is
Carbon dioxide detection is becoming increasingly relevant
colorless, odorless, and not detectable by human senses.
due to heavy investments in massive carbon capture and
It is lighter than air and hence difficult to detect where
storage (CCS) projects as well as projects where CO2
accumulations cannot occur. It also cannot be detected by
is used for reinjection to enhance reservoir pressure.
infrared gas sensing technology. Besides being difficult to
The investments in CCS may reduce CO2 emissions to
detect, hydrogen gas itself possesses severe safety risks:
the atmosphere. CO2 detection is essential to limit the
it is easily ignitable on contact with open flames, electrical
environmental impact of a release and production losses.
Page 30
Which Gases can UGLD Detect?
H2S may also be mixed into the CO2, which increases the
Condensate, 2-Phase, and Liquid Leaks
need for detection. UGLD responds well to CO2 leaks.
The detection of mixed or 2-phase (liquid/gas) leaks
Hydrogen Sulfide (H2S)
equilibrium with liquids are common in many process
by UGLDs is a subject of recent interest. Gases in
Because H2S is highly toxic, industry and governmental
streams. Preliminary work has shown UGLDs provide an
organizations often demand the earliest possible
adequate response to certain water/steam leaks. The
detection of H2S gas releases. As for other pressurized
sound pressure level generated by these leaks is low,
gas installations, UGLDs can be used as a first protective
however, restricting the area coverage of the device
layer in H2S with technologies specifically designed to
to a few meters, or areas with low ambient ultrasonic
detect H2S.
background noise. The results are consistent with those
Reservoirs that contain high concentrations of H2S are likely to hold a mixture of gases and liquids. When
published by the Health and Safety Executive (HSE) on the response of UGLDs to pressurized water leaks.*
H2S escapes before it is separated, it is usually mixed
To summarize, pure liquids do not generate adequate
with hydrocarbon gases. An UGLD does not distinguish
levels of ultrasound to make the use of UGLDs viable for
between the different gases but the leaking pressurized
these types of applications. It is assumed, however, that
hydrocarbons with H2S mixed into it will generate high
most 2-phase leaks containing small liquid fractions are
levels of ultrasonic noise, which are picked up by the
detectable by UGLD at a reduced coverage.
UGLDs. UGLDs should not be used to detect H2S after it has been separated from the hydrocarbon gas.
*Reference:
M. Royle et el. â&#x20AC;?Measurement of Acoustic
Spectra from Liquid Leaksâ&#x20AC;?, Research Report RR568. HSE Books, Colegate, England, 2007.
Which Gases can UGLD Detect?
Page 31
Gases and coverage As described on the previous pages it is understood that
the industry guideline for detection of methane based
different gases have different characteristics. This will
gas leaks and a useful guideline for carbon dioxide and
have some influence on how high ultrasonic noise the
ethylene leak detection.
gas will make. In effect this will influence on how far away an UGLD can pick up gas leaks.
The graphs represent the ultrasonic sound pressure levels [SPL], which the UGLD picks up (Y-axis). It shows
In the graphs on the following pages, the design engineer
that the SPL becomes lower when the distance between
can find the detection coverage for different gases at
the detector and the leak source increases (X-axis). The
different background noise levels. This makes it relatively
three solid horizontal lines represent the trigger level in
simple to estimate the number of ultrasonic detectors
the three standard plant noise areas. When the line that
required for the specific application. NOTE: The graph
represents the relevant noise area meets the graph the
should not be stretched to its limits as detection range
detection coverage for that gas can be found.
of an UGLD may decrease when the leak is pointed away from the detector. The implementation practice (chapter
As an example, consider an installation in a high-noise
4) provides further guidance. When using the graphs some
area by a compressor module: The ultrasonic background
overlapping coverage can be used to ensure full detection.
noise is typically between 65-75 dB. The trigger level is then set to 84 dB or a corresponding value in mA (see also
DETECTION COVERAGE FOR 0.1 KG/S LEAKS
page 61 for further directives). The individual detectorâ&#x20AC;&#x2122;s
The graphs on the opposite page show UGLD coverage
coverage in radius can now be found in the graph. For
when detecting leaks at a leak rate of 0.1 kg/s. This is
methane the detection radius is 7 meters (23 feet).
Page 32
Which Gases can UGLD Detect?
DETECTION COVERAGE FOR 0.1 KG/S LEAKS
Trigger level [dB (ultrasound)]
Reference test set-up for these curves, see Figure 12
89
84
High noise area
79
74
Low noise area
69 CH4 (methane)
Very low noise area
64 C2H4 (ethylene) C02 (carbon dioxide)
59
2
4
6
8
Example: Detection coverage in high noise area for CH4
10
12 CH4 (0,1 kg/s)
14
16
C2H4 (0,1 kg/s)
18
20
Detection distance [Meter]
C02 (gaseous) (0,1 kg/s)
Figure 11
Page 33
DETECTION COVERAGE FOR 0.01 KG/S LEAKS
should not be used without taking other factors (such
The graphs on the opposite page show UGLD coverage
as blockage) into account. Full verification can always be
when detecting leaks at a leak rate of 0.01 kg/s. This
performed at commissioning (see phase four in chapter 4).
may be used for a lighter and more explosive gas such as hydrogen. It may also be used for detection of propane
The digital version of the Technical Handbook is updated
or propylene, which are typically found in processes with
on a frequent basis as more gases are tested and further
lower pressure. Note that the coverage for propane or
knowledge is obtained. To find the latest graphs and most
propylene is based on 0.018 kg/s leaks or 0.016 kg/s
recent updates and to sign up for automatic updates
respectively.
you can go to www.gassonic.com/handbook. For further input it is recommended to contact a Gassonic or General
Again, as an example on how to read the graph, consider
Monitors representative.
an installation in a high-noise area by the compressor Gassonic UGLD
module: It is found that the detection radius for hydrogen in this area is 7-8 meter (25 feet).
Test gas 3 meter (10 feet)
NOTE: The graphs on these pages are based on comprehensive live tests carried out at Gassonic, Denmark, and
Test nozzle
General Monitors, USA. The results are published with
Detection distance
a safety factor to enhance reliability and repeatability. It should be noted that the detection coverage is based on
1 meter (3 feet)
the assumption that the escaping material is a gas when it is released. It should also be noted that the information on these pages should be seen as guidelines only and
Page 34
Ground Figure 12: Reference test set-up for curves in Figures 11 and 13.
Which Gases can UGLD Detect?
DETECTION COVERAGE FOR 0.01 KG/S LEAKS
Trigger level [dB (ultrasound)]
Reference test set-up for these curves, see Figure 12
89
84
High noise area
79
74
Low noise area H2/He (hydrogen/helium)
69
Very low noise area
64 C3H8 (propane) C3H6 (propylene)
59
2
4
6
8
Example: Detection coverage in high noise area for H2
10
12 H2/He (0,01 kg/s)
14
16
18
C3H8 (0,018 kg/s)
20
Detection distance [Meter]
C3H6 (0,016 kg/s)
Figure 13
Page 35
3 WHERE TO INSTALL UGLD As a rule of thumb, ultrasonic gas leak detectors offer distinct advantages in outdoor or ventilated areas over conventional gas detection methods which are susceptible to changing wind directions and gas dilution.
?
How can UGLD work in noisy plant environments? The detectors can be installed in noisy environments because the technology only responds to high frequency noise. Escaping pressurized gas generates so-called â&#x20AC;?white noiseâ&#x20AC;?, in both audible and ultrasonic frequencies. Normal background noise generated by humans and plant equipment, makes noise primarily in the lower frequencies, which are filtered out by the UGLD.
Applications Ultrasonic gas leak detectors can be used in a wide range
• Chemical Processing Plants
of application areas where there is pressurized gas. As a rule of thumb, UGLDs offer distinct advantages in outdoor or ventilated areas. Conventional gas detection
• Floating Production Storage and Offloading Vessels (FPSOs)
methods have some imminent limitations as gas must accumulate reach a sensor (point gas detection) or pass within a beam (open path detection) to be detected. In such areas, there is a risk that the gas will quickly dilute before accumulation can occur or the wind will blow the gas cloud away before reaching the sensor. Studies carried out on gas leaks in offshore facilities in the UK state that conventional detection methods only detect 65% of the registered gas leaks (see inside front cover). As UGLDs respond to the leak noise, which is
• Gas Compressor and Metering Stations • Gas Turbine Power Plants • LNG/GTL Trains • LNG Re-gasification Plants • Offshore Oil & Gas Platforms • Onshore Oil & Gas Terminals
omni-directional and indifferent to wind directions, they may be used to improve the gas detection efficiency.
• Refineries
A selection of typical installations where UGLDs are being
• Underground Gas Storage Facilities
used can be found in the box to the right. This chapter further details different applications for UGLD. Which Gases can UGLD Detect?
Page 39 Page 39
9 Pig launcher and receiver 8 Gas metering
6 Filter station 3 Power substation
7 Separator
5 Cooler 2 Gathering manifold 1 Wellheads
4 Gas compressor
Figure 14: A generic gas processing plant where the ultrasonic gas leak detectors are installed to protect potential leak spots in all areas with high-pressure gas. These are marked with a number. Page 40
Which Gases can UGLD Detect?
Applications: Gas Processing Plant A typical gas processing plant can be used to illustrate where UGLDs can be applied.
In this facility, gas is being extracted from the wellheads
containment. Other detection means like infrared point
(1) and piped through a central manifold (2) to the rest of
detectors can identify and measure the concentration of
the processing facility. The water knockout drums remove
the gas, giving users a better sense of the scale of the
the water before it reaches the gas compressor (4). The
hazard. Chapter 6 addresses the application of different
cooler (5) ensures optimal temperature before the filter
detection technologies for greater safety.
and separation processes (6 and 7). After separation, the gas is transferred to a gas metering skid (8) on to the gas outlet, where it is distributed through a grid for consumption, storage, or export. Ultrasonic gas leak detectors are applied in all outdoor locations with pressurized gas. Locations in this example include wellheads, compressor area, cooler, filter station, separator, gas metering skid, and receiver area. UGLDs should be installed as a first line of defense to provide the earliest possible warning to a loss of
Where to Install UGLD
Page 41
7 UGLD
Figure 14a
Page 42
Where to Install UGLD
Applications: Separation Area In the separation process, moisture, hydrogen sulfide, and other contaminants are removed from the gas stream.
As shown in the opposite diagram, the separator unit includes the separator itself, a gas exchanger, and gas coolers that ensure the correct temperature for the process. Ultrasonic gas leak detectors are positioned so they cover potential leak sources like the flanges and valves on the separator module and on the coolers. Obstructions are taken into account when determining the number of detectors required for optimal coverage. Detector implementation and placement is discussed further in Chapter 4.
Gassonic Observer UGLD
Where to Install UGLD
Page 43
Applications: Wellheads Wellheads are used to extract and produce oil and gas. The oil and gas pressure is often high in the wellhead area are therefore suitable for ultrasonic gas leak detection.
The top of the wellhead usually consists of a collection
compressor stations, or oil export terminals. As depicted
of valves that makes up a production tree or â&#x20AC;&#x2122;Christmas
on the onshore wellhead below, one ultrasonic gas leak
treeâ&#x20AC;&#x2122;. These valves regulate pressures, control flows, and
detector adequately covers the production tree including
allow access to the wellbore in case further completion
valves and flanges on the topside of the wellhead and
work is needed. In offshore installations the wellheads
potential leak areas inside the wellhead pit if it is exposed.
are normally found on the lower platform decks (in the well bay area) whereas onshore they are found either
1
in close vicinity of a processing plant (Figure 14b) or in remote locations. A wellhead may also be situated on the top of an underground gas storage facility. From the outlet valve of the production tree, the flow can be connected to a distribution network of pipelines to supply the extracted substance to refineries, natural gas UGLD Figure 14b
Page 44
Where to Install UGLD
Applications: Compressor Area Gas compression takes place in the compressor area to increase the gas pressure for transmission
The natural gas compressor area is prone to leaks be-
in the front ensures coverage along the front side of the
cause the operating environment includes a combination
compressors whereas the second detector placed on the
of heat, high operational pressure, and vibration. Leaks
staircase covers the flanges on the top and the back of the
could be caused by the following failures:
compressors. Conventional gas detectors are used inside the housing and on the air intakes.
• Degraded pipes from exposure to corrosive gases · Broken or unseated seals or bearings within the compressor engines
4
• Rupture in pipe systems or machinery • Degraded flanges or valves Figure 14c exemplifies a typical compressor module with two compressors. The gear box and turbine are situated in the housing to the left. High levels of ultrasound may be generated by the turbine inside the enclosure but the housing attenuates the ultrasound so it does not interfere with the ultrasonic gas leak detectors. The UGLD installed
Where to Install UGLD
UGLD Figure 14c
Page 45
Gassonic service engineer simulating real gas leaks while performing onsite commissioning. Besides testing that the ultrasonic detectors are within accepted tolerances, the commissioning verifies the actual detection coverage and performance of the detectors.
4 How to implement and maintain UGLDâ&#x20AC;&#x2122;s Implementation and installation of ultrasonic gas leak detectors are different than those for conventional gas detectors because UGLD is based on detection of airborne acoustic sound waves. This means there are some particular guidelines that need to be followed when implementing UGLDs.
Phase One: Where in the project should UGLD be implemented? Implementation Practice
wellhead or if it is a large gas plant where hundreds of
The implementation of ultrasonic gas leak detectors can
detectors are needed.
be divided into the following four phases: • Where in the project should ultrasonic gas leak detection be implemented?
WHICH AREAS ARE SUITED FOR UGLD? The first question to be asked is if the project comprises process facilities with compressed gas with a pressure higher than 10 bar (145 psi). If the answer is yes, UGLD is
• Where should each individual detector be installed? • Detailed engineering considerations • After installation: How are the UGLDs commissioned and tested? These four phases are carried out for each new project where UGLD is implemented. This applies whether the project consists of one single detector on a high pressure
Page 48
well suited for the project (see page 20 for installation in systems with lower pressures). Next, is the pressurized gas installation indoors or outdoors? If it is an outdoor or ventilated gas installation, UGLD is the optimal detection technology to use as a first line of defense to ensure fast and reliable detection. UGLDs are well suited for installation both onshore and offshore and several thousand UGLDs are installed both onshore and offshore in areas with high pressure gas.
How to Implement and Maintain UGLD
Examples of process areas adequate for UGLD are listed in the box to the right. For installation near air intakes for machines and in accommodation facilities, conventional gas detectors are more suited than UGLDs due to lack of
Areas suited for UGLD: Fin fan gas coolers
pressure.
Gas compressor and separation areas Gas metering skids and manifold areas Hydrocracking, hydrotreating, catalytic reforming Pig launchers and receivers Wellheads
How to Implement and Maintain UGLD
Page 49 Page 49
PHASE TWO: Where should individual detectors be installed? Figure 15
Once the project team has determined that UGLDs are suitable for a project, the next step is to determine detector placement. Step 1: Obtain the layout design of the plant.
MAC
MAC
Step 1
Step 2
Step 2: Mark the areas where there is pressurized gas and where there are potential leak sources. Step 3: Determine the detection coverage each ultrasonic detector should have based on the ultrasonic plant noise. Next, draw circles on the plant fire and gas layouts to determine how many and where the detectors should be installed. Gassonic (General Monitors), a local representative or a design consultant can provide input at this stage. By following this procedure, users can obtain an estimate of the number of detectors required to cover the entire area. MAC
Step 3 Page 50
How to Implement and Maintain UGLD
Figure 16
Offshore Installation of UGLD A platform used to exemplify an offshore installation is divided into different sections:
Top deck Main deck Lower deck Wellbay deck
How to Implement and Maintain UGLD
Page 51
Top deck
Figure 16a
On the top deck, which is sometimes referred to as the weather deck, the fin-fan coolers help lower the temperature when the gas is compressed and thus heated. The pressurized gas is typically found on the side of the cooler structure and not over the center of the finfans. Ultrasonic gas leak detectors are installed to cover all potential leak sources down the side of the coolers. Since the top deck is exposed to potential high levels of ultrasound the detection coverage is based on high-noise area settings. The detection radius is based on 5-8 meter coverage (16-28 feet). In this example nine detectors protect the area. UGLDs are unaffected by helicopter landings and take offs. The air intakes at the bottom of the drawing are covered with conventional gas detectors because accumulation of gas may occur there.
SM
Page 52
0
5M
10M
15M
20M
How to Implement and Maintain UGLD
Main deck
FP
MaC
PAPA
MaC
The main deck houses the main processing facilities,
Figure 16b
which consist of the compressor skids, inlet gas separation, export gas metering, gas exchanger, and the fuel gas skid. The entire process area is protected with ultrasonic detectors because most of the facilities FP
operate at high pressure. Generally the detection
FP
MaC
area settings, which gives at least 9-12 meters (30-39
MaC
coverage in the process area is based on low-noise feet) coverage in radius. However, near the compressors that produce relatively high levels of ultrasound along with the loud audible noise, the settings should be based on high-noise area settings. This means that the detection radius decreases to 5-8 meters (16-28 feet) in radius. When implementing detectors here it must be considered if there is any blockage from big vessels such as the compressor unit, which could make it necessary FP
to include additional detectors. A total of nine detectors cover the deck in this example. MaC FP
How to Implement and Maintain UGLD
Page 53
LOWER deck The lower deck of the platform contains pipe work, which includes potential leak sources such as flanges and valves. In the bottom of the drawing is the pigging section where the pig is launched or received as part of maintenance and inspection of the pipeline. The whole area is regarded as low-noise because there is no heavy or rotating machinery. The detection radius is therefore FP
FP
set at a minimum of 9 meters (30 feet). Most of the area includes potential high-pressure leak sources. A total of six detectors are implemented to provide optimal coverage of the area.
FP
FP MaC
SM
Page 54
0
5M
10M
15M
20M
Figure 16c
How to Implement and Maintain UGLD
Wellbay deck The wellbay area primarily consists of the wellheads where the gas comes in at high pressure after it is extracted from underground. Often the wellbay could be located on one or more smaller dedicated platforms separated from the main processing platform. On the wellbay deck, manifolds and separation facilities (at the bottom) can also be found. Since the ultrasonic background noise in this area is low, coverage for each detector is set at 9-12 meters (30-39 feet). A total of eight detectors cover this area due to the physical shape of the wellheads. There is some overlapping coverage because the risk of shadowing needs to be taken into account, which could limit coverage in some angles.
MAC
Figure 16d
How to Implement and Maintain UGLD
Page 55
Onshore Installation of UGLD
Most of the facility can be considered a low-noise area
The onshore oil and gas plant is divided into different
providing 9-12 meters (30-39 feet) coverage in radius. In
sections or trains. Unlike the offshore facility, the onshore
the compressor area, which is considered a high-noise
plant covers a large area with long distances between
area, the coverage is 5-8 meters (16-28 feet) in radius.
units. However, the overall implementation practice for
In the plant drawing an average of 10 meters (33 feet)
UGLDs is the same. In the image to the right a typical
is used to provide a rough estimate of the number of
gas plant can be seen. The numbers indicate the areas
detectors required.
where there is pressurized gas: wellheads, manifold, separator, coolers, and compressor (see also Figure 14
In this facility, there is a total number of 23 UGLDs
on page 40). On Figure 17 the gas plant is shown as
identified to provide coverage of the entire facility.
a plant layout drawing. The steps required to allocate UGLDs are as follows: Step 1: Obtain plant drawings and identify where there is
9 8
pressurized gas making it suitable for UGLDs 6
Step 2: Determine the detection coverage for each
3
7
UGLD based on the ultrasonic plant noise in the area of installation.
2 1
4
Step 3: Draw circles on the plant fire and gas layouts to determine how many and where the detectors should be installed.
Page 56
How to Implement and Maintain UGLD
9
6
3
8
1
7
2
4
SM
0
5M
10M
15M
20M
Figure 17: This plant layout shows the gas processing plant from the left hand side in top view. Each circle represents the coverage from an ultrasonic detector. How to Implement and Maintain UGLD
Page 57
PHASE THREE: Detailed engineering considerations Choosing the correct height
With UGLDs, the installation height is always the same. It
For optimal operation an ultrasonic gas leak detector
is not dependent on the gas because the ultrasonic sound
must be installed above or to the side of potential leak
generated by the gas travels in all directions around the
sources and where no solid structures obstruct the path
leak regardless of the weight of the specific gas.
between the detector and the potential leak source. The main rule of thumb is that the UGLD should be installed 1-2 meters (3-6 feet) above the potential leak source. This ensures optimal use of coverage and provides easy access for installation and maintenance, (see also coverage characteristics on Figure 4, Page 14). The installation height of conventional LEL-based gas detectors often depends on the target gas. Some gases
1-2 meter
are heavier and others are lighter than air. As a result, an LEL gas detector needs to be installed in a high position and sometimes in a low position depending on the properties of the gas.
Figure 18: To the left correct installation of an UGLD in 1-2 meters height above the potential leak source. To the right the detector installed too high. Page 58
How to Implement and Maintain UGLD
Figure 19
ShadowING or blockage Ultrasonic gas leak detectors do not operate optimally if there is a solid, physical blockage between the leak source and the detector element. If there are solid structures such as big vessels, tanks, compressors, or separator units that can block the path from the detector to the potential leak source, they could attenuate or block the ultrasound before reaching the detector. This is
Correct installation of UGLD with regards to blocking and shadows
known as shadowing or blockage. As shown on Figure 19 normal pipework does not block the sound. When implementing UGLDs in the design stage and upon physical installation of the detectors, shadowing/ blockage must be taken into consideration. In the example on the bottom right, the detector must be moved to the other side of the tank or a second detector installed to cover the valve on the right-hand side in order to ensure adequate coverage. The commissioning practice (see page 67) reveals spots at a plant where shadowing or
Incorrect installation of UGLD from the gas leak because the ultrasound is blocked by the vessel.
blockage could affect detection coverage.
How to Implement and Maintain UGLD
Page 59
How to obtain optimal detection coverage
These noise sources represent roughly 95% of worldwide industrial noise in plants. Even though plant noise can be very loud most of it is low frequency noise, which does not
Ultrasonic gas leak detectors detect the acoustic
influence UGLD. The ultrasonic detectors are equipped
ultrasonic noise generated from pressurized gas leaks.
with high pass filters, which effectively eliminate audible
Since the UGLD only “hears” the high frequency sound
and lower ultrasonic background noise.
(the ultrasound), it is immune to most acoustic noise present in plant environments. Normal background
If plant noise didn’t contain any ultrasound, the detector
noise in an industrial plant may come from the following
could always be in its most sensitive alarm level setting,
sources:
and thereby always obtain the same wide detection coverage from the detector. However, in plant areas
• Process fluids or gases running inside pipes and vessels • Rotating machines such as compressors and fin fan coolers • Plant personnel and vehicles
that contain compressors or other high-speed rotating equipment, some ultrasonic noise is generally present, which in turn can interfere with the UGLD. Therefore, it is important to have an overall understanding of the area each UGLD is going to be installed in to ensure the correct alarm trigger level set-point on each detector and that it is always above the base level of ultrasound in the area.
• Airplanes or helicopters
Page 60
How to Implement and Maintain UGLD
Setting the right trigger level Figure 20 shows the three typical noise scenarios in
Figure 20
84 dB
plant environments and the optimal detector trigger level (see also page 17 for a more detailed description of the
74 dB
different areas). The straight black line shows the trigger level set-point in dB and the red trend curve shows
64 dB
the actual ultrasonic noise at the detector. Notice that unlike concentration based detectors, which read out a
Trigger level in high noise area
percentage of LEL, the UGLD reads out the ultrasonic noise in dB, which has a corresponding value on the 4-20
84 dB
mA signal. As an example, 84 dB may correspond to 13 mA. An online demo enables the user to try different noise settings and set-points on Gassonicâ&#x20AC;&#x2122;s website, www.gassonic.com/simulator/coverage_and_background_
74 dB 64 dB
noise/ Trigger level in low noise area 84 dB 74 dB 64 dB
Trigger level in very low noise area How to Implement and Maintain UGLD
Page 61
Ultrasonic Noise Sources AND Plant Noise Levels
important to understand that the ultrasonic detectors are
The table below exemplifies some of the normal noise
away. This means that audible noise measurements made
only affected by ultrasound â&#x20AC;&#x201C; the audible noise is filtered
sources found in plant environments and the normal noise
in plants must not be used in relation to UGLD. Such studies
levels they produce. It also incorporates the recommended
are done to ensure the proper work environment and to
trigger level and resulting detection coverage. The table
know when the audible noise becomes so loud that hearing
shows both audible and ultrasonic noise levels. It is
protection must be used by personnel.
AREA
AUDIBLE NOISE [dBa]
ULTRASONIC NOISE [dB]
RECOMMENDED TRIGGER LEVEL
DETECTION COVERAGE (RADIUS) @ 0.1 kg/sec
Compressors
100
70
84 dB
5-8 m
Helicopter deck
NA
67
84 dB
5-8 m
Choke valves
94
60
74 dB
8-12 m
Generators
94
60
74 dB
8-12 m
Well bays
84
59
74 dB
8-12 m
Manifolds
NA
59
74 dB
8-12 m
Metering skids
NA
58
74 dB
8-12 m
Separators
NA
58
74 dB
8-12 m
Coolers (fin-fans)
95
64
74 dB
8-12 m
Onshore wellheads
NA
<44
64 dB
13-20 m
Table 1: Note: the above readings are based on representative recordings taken during onsite surveys done by Gassonic. The noise levels may fluctuate from plant to plant. Page 62
How to Implement and Maintain UGLD
How to Avoid Influence from Other Noise Sources and False Alarms
High level acoustic noise generated by gas flowing inside
As explained before, UGLDs are immune to most normal
ultrasonic noise that could generate false alarms,
plant noise since it is low frequency noise, which the
but that is not the case. Although the acoustic sound
UGLD filters away. However, other noises can occur in
generated inside the piping, and especially inside a choke
the plant environment which could trigger the UGLD
valve, may contain high frequencies (ultrasound) most
(for example, air driven valves and actuators). This kind
of that ultrasound is blocked by the pipe wall. Compare
of noise is typically of short duration (1-10 seconds),
it with hearing music through a wall. The low frequency
whereas a real gas leak is continuous and lasts for a
bass sounds are heard whereas the high frequencies are
much longer period of time. To avoid false alarms, it is
blocked by the wall.
the pipes is often mentioned as a potential source of
recommended to always implement a short alarm time delay (â&#x2030;Ľ10 sec).
Gas leak
Gas leak Alarm
Short high dB spike Trigger level at 74 dB Background noise at 64 dB
Figure 21
How to Implement and Maintain UGLD
10 sec. Delay
Page 63
Services - maintenance
the detectorâ&#x20AC;&#x2122;s linearity and the loop to the control room
An ultrasonic gas leak detector is a low-maintenance
are verified. For the most advanced models, calibration
product since it does not have any consumable parts.
can be performed onsite.
Conventional gas sensor elements degrade over time due to exposure to gas or other substances. Routine
Some detector models have an integrated self-testing
maintenance service is therefore limited to once every
mechanism (such as Gassonicâ&#x20AC;&#x2122;s Senssonic self-test),
6-12 months for UGLDs.
which tests the detectorâ&#x20AC;&#x2122;s performance at short intervals. This ensures the operation and performance of the
Routine testing is carried out by means of a traceable
ultrasonic detector between inspections.
portable calibration device. During routine maintenance,
Gassonic 1701 test and calibration unit
Page 64
Test carried out with traceable portable test and calibration unit.
How to Implement and Maintain UGLD
Services - onsite mapping survey
onsite mapping survey should always be performed by
An onsite mapping survey can be performed in order
engineers trained and certified by the manufacturer or an
to optimize detector positioning or to verify detector
experienced consultant.
allocation based on plant layouts. When Gassonic trained engineers are carrying out the In existing (brownfield) installations it is possible to
mapping survey, a full documentation report is created.
determine the ultrasonic background noise prior to
The report includes specific suggestions for where to
installation by performing an onsite mapping survey. A
install each detector and how to set the trigger level in
survey may reveal sources of short timescale intermittent
each location for optimal coverage.
ultrasonic noise like pressure relief valves or sources that may produce some continuous ultrasonic noise levels like turbo compressors and turbines. Based on the survey findings, one can determine the exact coverage from each ultrasonic detector and therefore the total number of detectors required to cover the facility. An
Onsite mapping survey performed by Gassonic trained engineer.
How to Implement and Maintain UGLD
Page 65
Gassonic service engineer simulating real gas leaks while performing onsite commissioning. Besides testing that the ultrasonic detectors are within accepted tolerances, the commissioning verifies the actual detection coverage and performance of the detectors.
PHASE FOUR: How are the UGLDs commissioned and tested? Services - onsite commissioning and
the predefined safety standards â&#x20AC;&#x201C; and that it picks up
leak simulation
gas leaks. For optimal verification, onsite commissioning
Start-up commissioning of an ultrasonic gas leak
and leak simulation should always be carried out by
detection system consists of two steps. First, the detector
engineers trained and certified by the manufacturer or
must be tested to ensure detector linearity. This is done
by experienced maintenance engineers using the proper
by means of a customized portable test unit (Gassonic
equipment.
1701). This exercise can be compared to the test that is carried out on a point sensor with a test gas or on a beam detector by means of a filter that absorbs infrared light. Second, simulated leaks are generated at critical leak spots in the perimeter of the coverage area to ensure full detection of the facility and verify that coverage is not influenced by shadowing. The leaks are carried out by means of a non-explosive replacement gas (nitrogen for methane and helium for hydrogen) at the performance standard leak rate of 0.1 kg/sec (methane). This verifies that the ultrasonic gas detection system complies with
How to Implement and Maintain UGLD
Equipment used to perform leak simulation onsite.
Page 67
5 Which UGLD products are available? The UGLD technology has been on the market since 1996. Today a number of different detector models are available. These pages describe the overall principles and features to consider when implementing UGLD.
Considerations when specifying ULTRASONIC GAS LEAK DETECTORS The UGLD technology has been on the market since 1996. Today a number of different detector models are available. These pages describe the overall principles and features to consider when implementing UGLD. You can find a table outlining the available main detector models here as well. Explosion proof AND intrinsically safe
addition, these sensors require little maintenance, about
There are various reasons for choosing explosion proof
1 or 2 times per year, and in rare occasions, calibration.
(Exd) or intrinsically safe (Exi) designs in hazardous
Calibration can be performed onsite with a portable test
location equipment. Choices may be based on a preferred
unit.
engineering practice or the characteristics of the facility (ex. voltage and power requirements).
Acoustic Self-Test (self-diagnostics) To ensure failsafe operation and avoid unrevealed
Sensor element
failures in between inspections, certain ultrasonic gas
The most common type of sensor for UGLD is stainless
leak detectors are equipped with an acoustic self-test like
steel microphone technology. Stainless steel microphone
Gassonicâ&#x20AC;&#x2122;s Senssonic. This self-test emits an ultrasonic
sensors are reliable, exhibit little drift, and have
signal every 15 minutes. If the signal is not detected by
an excellent record of operation in harsh industrial
the sensor element, the detector produces a fault.
environments in both arctic and desert conditions. In
Page 70
Which UGLD Products are Available?
Hazardous Area Approvals and
Power Consumption
Safety Integrity Levels
UGLDs consume little power, since the technology
Detector models are certified by several regulatory
requires no constant power source for operation. For
agencies and under several directives. Regulatory
installation in isolated locations like a remote solar
approvals include FM, CSA, C-UL, ATEX, IECEx, and GGTN
panel powered application, certain detector models can
K. UGLDs are also certified under FM Approvals to comply
operate on minimal power. Maximum consumption is
with IEC 61508 being as SIL 1 and 2 suitable.
found to be lower than 1 Watt (36 mA at 24 VDC) in these instruments.
Communication buses and protocols Standard 4-20 mA analog output and digital communication are available with UGLD. Information on serial connections and other communication topics are available on the Gassonic website.
Which UGLD Products are Available?
Page 71
Product Comparison Table
Sensor technology Protection method Response time Hazardous area certification
Gassonic Surveyor
Gassonic Observer
Stainless steel electret condenser
Stainless steel electret condenser
microphone
microphone
EEx ia
EEx d
< 1 sec
< 1 sec
ATEX, IECEx
FM, CSA, ATEX, UL/C-UL, IECEx, GGTN K
SIL suitability
SIL 1
SIL 2
Ingress protection
IP66
IP66
Acoustic self test Interface 4 â&#x20AC;&#x201C; 20 mA
X (Integrated Senssonicâ&#x201E;˘ self-test) X
Digital communication
X X
Interface: Alarm relay
X
X
Interface: Fault relay
X
X
5 dB
5 dB
0 to 480 sec in steps
0 to 600 sec in 10 sec steps
Alarm trigger level steps Internal alarm delay setting Page 72
Which UGLD Products are Available?
User interface Cable connection
Gassonic Surveyor
Gassonic Observer
LED indications
Full interactive display
conduit/cable gland
conduit/cable gland
Detector set up
Factory set-up/Field adjustable
Factory set-up/Field adjustable
Coverage radius @ 0.1 kg/sec
≤ 20 meters (background noise
≤ 20 meters (background noise
dependent)
dependent)
Field testing with calibrated device
Yes (with the Gassonic 1701)
Yes (with the Gassonic 1701)
Field calibration option
Yes (with the Gassonic 1701)
Yes (with the Gassonic 1701)
44-104 dB
58-104 dB
Stainless steel
Stainless steel
-40 to +75°C
-40 to +60°C
>10 years
> 10 years
Dynamic range Material Temperature range Sensor life Accuracy Input Power
+/- 3 dB
+/- 3 dB
13 - 28 VDC
15 - 30 VDC
36 mA @ 24 VDC
250 mA @ 24 VDC
Table 2 - In general, all Gassonic detectors can be used for any high-pressure gas installation. However, one feature that makes the Gassonic Observer stand out is the fact that it has integrated self-test capabilities. This means that the risk of unrevealed failures in-between inspections can be eliminated. In certain applications, such as unmanned or remote installations (on NUIs or remote wellheads etc.), where access and frequent routine testing is more problematic, this is particularly important. Although all Gassonic detectors consume relatively little power, in locations with particularly limited power resources, the Gassonic Surveyor can be the optimal choice as its maximum drag is less than 1 Watt (43 mA at 13 VDC).
Which UGLD Products are Available?
Page 73
6 How to interface UGLD and mix with other technologies Ultrasonic gas leak detectors can interface with control systems just like conventional detection methods. The main difference is that the output from UGLDs corresponds to leak noise (measured in dB), rather than gas concentration (measured in % LEL).
How to interface the detectors with the control system Ultrasonic gas leak detectors have various customer selected output methods, which both include analog and digital communication modes. Whether an analog or digital communication method is preferred depends on how the specific safety system is designed. Output methods make it easy to integrate the ultrasonic gas leak detectors into standard control systems like a DCS, PLC, local fire and gas panel as well as customized General Monitors control systems (MC600 and HazardWatch). An ultrasonic gas leak detector can interface with control systems just like traditional detection methods. The main difference is that the output from UGLDs correspond to leak noise (measured in dB), and not gas concentration (measured in %LEL). This difference in unit of measurement must be taken into consideration when the safety system is configured and the alarm levels are incorporated. Alternatively, a dedicated multi-channel controller or input card can be used to transform the signal from the UGLD into a dB value.
Page 76
How to Interface UGLD and Mix with Other Technologies
Configuring Trigger Level and Alarm Delay Time
alarm. When determining the right delay time, the surrounding machinery must be taken into consideration since valves and actuators could be sources of spurious
When installing ultrasonic gas leak detectors two
alarm. Typically, a time delay of 10-15 seconds should be
essential factors must be considered - the alarm trigger
implemented. For general guidelines regarding prevention
level and the time delay.
of spurious alarms (see page 17).
The alarm trigger level refers to a specific dB value. If
The trigger level and time delay must either be
this value is reached, the detector goes into alarm mode.
implemented in the control system or fire and gas panel.
When determining what the right trigger level is for the
Alternatively, it can be configured in the detector itself if
detector, the ultrasonic background noise in the area
relays are being used.
must be taken into consideration. It is recommended to set the trigger level at least 6 dB higher than the measured ultrasonic background noise or use the general guidelines for implementation in ‘high-noise’, ‘low-noise’, ‘very low-noise’ areas (Chapter 4, phase three). The dB range of an ultrasonic detector directly corresponds to a 4-20 mA value so that if the dB range goes from 58-104 dB, 4 mA equals 58 dB and 20 mA equals 104 dB. The introduction of a time delay is used to prevent spurious alarms. Without a time delay, any ultrasonic sound exceeding the trigger level would produce an
How to Interface UGLD and Mix with Other Technologies
Page 77
Executive Action and Voting Configuration Ultrasonic gas leak detectors can be used for alarm or executive action depending on the operatorâ&#x20AC;&#x2122;s needs.
follows examples of how voting configurations between different technologies can work together: Open path detectors and UGLDs
These detectors are commonly used as part of a voting
UGLDs are used for area coverage and gas leak detection in
mechanism, which would either vote the UGLD with
all high-pressure areas. The open path detectors are used
other UGLDs or with conventional detectors (open path
for fence line monitoring to measure the concentration of
or points). The voting configuration may be 2 out of any
the gas.
detector on a deck (2ooN), regardless of the number of sections or enclosed spaces on that deck, or 2 out of 3 detectors in an area (2oo3). In case two detectors identify a gas leak, the fire and gas system automatically issues an alarm and initiates a protective response according to the nature, location, and severity of the detected hazard. This may include starting up the deluge system, initiating beacons and horns, or by performing a full emergency shutdown. It is considered good practice to vote gas detectors to prevent spurious alarms and to ensure at least one detector is available if another one were to fail. Here
Page 78
UGLDs with UGLDs Voting of UGLDs can be done in all high-pressure zones. When using the UGLDs in voting configurations with other UGLDs, overlapping coverage from the detectors must be considered. Alarm delays must also be implemented. Points detectors and UGLDs UGLDs are used as a fist protection layer for early gas leak detection in areas with pressurized gas. The point detectors are implemented in areas where accumulation of gas and vaporization of depressurized liquids are likely to occur. They may also be installed strategically by major flanges and valves where the risk of gas leaks is high.
How to Interface UGLD and Mix with Other Technologies
UGLD as an independent protection layer in
action once the hazard can no longer be prevented. At
the safety instrumented system (SIS)
the heart of the IPL scheme is the assumption that no
The development of international standards like ISA-84
device is 100% reliable. Over the course of their life cycle,
and industry codes of practice that ensure the availability
instruments will fail to perform their functions; and as a
and effectiveness of fire and gas systems has advanced
result, the best defense is multiple independent layers
risk-based concepts in the process industry sector.
of protection.
Among the important assumptions from this regulatory framework is that accidents are rarely the result of a single
Independent
layers
may
represent
a
number
of
failure. Rather, a series of errors combined to expose
common safeguards. Properly defined, however, an IPL
a flank through which the initiating cause propagates.
is â&#x20AC;&#x153;any independent mechanism that reduces risk by
These errors begin with an initiating event and include the
control, prevention or mitigationâ&#x20AC;? (ISA-84 2004). While
enabling conditions which must be present in order for
preventative IPLs serve to stop a scenario from developing
the scenario to proceed. Invariably, as the hazard evolves
further, mitigation IPLs simply reduce the consequences
unchecked, its consequences become more severe and
of an incidence once it occurs. By their nature then, fire
the accident more difficult to control.
and gas detection systems are mitigation layers.
In order to reduce the likelihood and severity of
Just as protection layers need to be independent from
accidents, functional safety professionals recommend
one another, so too do the individual elements within an
the application of independent protection layers [IPLs].
IPL. This is particularly the case with fire and gas sensors,
Layered protection provides a formidable defense against
which are often the first line of defense against the risk of
accident sequences. IPLs help bring a basic process into a
several types of major incidents. In the IPL scheme, each
safe state or provide early warning and prompt appropriate
sensor serves as a protection layer against a common
How to Interface UGLD and Mix with Other Technologies
Page 79
risk like those of fires and gas releases (Figure 22). Since
and equipment. Their benefit toward hazard mitigation
all detection systems are vulnerable, it stands to reason
lies in their complementary use, so that the limitations
they should be implemented in a way that provides the
of one are offset by the strengths of the others. This
greatest degree of independence between them.
concept of safety in diversity is the premise behind our Total Solution Provider (TSP) philosophy and our belief
As a member of the General Monitors family, we recog-
that diverse safety systems, combined with a design that
nizethere is no absolute security with any one gas
prevents leaks and eliminates possible ignition sources,
detection system. For this reason, we offer a whole host
offers the best approach for reducing the chances of
of detection technologies that safeguard plant personnel
hazard propagation.
Fire Detection
A human sensory model (Table 3 on the next page) applied to gas and flame safety suggests detection
Gas Detection N Gas Detection 2 Gas Detection 1
technologies associated with the classical senses can be combined to provide superior protection. Devices that rely on ultrasound, optics, or mass transport to trace gas are independent, as their methods of operation are based on different physical principles. Sound propagation,
Leak Detection
emission or absorption of light, or an exothermic chemical reaction can inform the presence of a gas under the right conditions but share few common elements; and therefore, few common failures.
Figure 22. Independent Protection Layers Within Automatic Safety Instrumented System IPL. (For Illustration Only â&#x20AC;&#x201C; Number and Types of IPL May Vary.) Page 80
Reference ANSI/ISA-84.00.01-2004 â&#x20AC;&#x201C; Part 1 (IEC 61511-1 Mod), 2 September 2004. Research Triangle Park, NC: ISA.
How to Interface UGLD and Mix with Other Technologies
UGLD â&#x20AC;&#x201C; SIL rating, SIS and Risk
technology is having a known coverage area that is not
There is much industry debate on whether a conventional
influenced by the physical presence of a gas. Unlike
gas detection system can be considered a safety
conventional point and open path detectors, UGLD is
instrumented system. This is due to the fact that a fully
not impacted by wind directionality, wind speed or gas
functioning point or open path detector may never have the
dilution. To maximize a plantâ&#x20AC;&#x2122;s safety and decrease risk
ability to perform as intended simply because a gas leak
as much as possible, it is wise to employ a gas detection
did not reach the detector due to wind conditions or gas
system that includes UGLD and improves the probability of
dilution. Optimal sensor placement and scenario coverage
leak detection.
is absolutely vital when designing a gas detection SIS to ensure that if a leak occurs, a sensor will come in contact
Functional safety is a fascinating topic with many facets of discussion. Please refer to the General Monitors SIL
with the gas and initiate the appropriate response.
Resource Center for further information on SIL and how it Ultrasonic gas leak detection has now become an
relates to gas and flame detection and UGLD. This can be
important part of the functional safety solution for gas
found on: www.gmigasandflame.com/sil_lead.html.
detection systems. A remarkable benefit of ultrasonic
Sense
Detection Technologies
Sight
Gas cloud imaging, UV/IR enabled flame detection
Smell
Fixed point IR gas detection, open path detection, catalytic, metal oxide semiconductor, electrochemical cell
Hearing
Ultrasonic gas leak detection Table 3. Detection Technologies Classified According to Human Sensory Model.
How to Interface UGLD and Mix with Other Technologies
Page 81
A FINAL OVERVIEW Technology
Applications
Uses the hearing sense to pick up the ultrasonic leak
UGLD is primarily installed in outdoor ventilated
noise from pressurized gas leaks.
locations where conventional detector types can be
This enables gas leak detection at the speed of sound
applications include among other offshore platforms,
and a significantly improved total speed of response.
onshore processing plants, compressor and metering
disadvantageous due to wind and leak properties. Typical
UGLD provides area coverage with each unit covering up to 40 meter (130 ft) in diameter. Gases Detects the leak noise generated by all gases under pressure â&#x20AC;&#x201C; from around 10 Bar (145 psi). Suited for detection of lighter hydrocarbons (methane, ethane/ethylene, propane/propylene), light gases such as hydrogen and helium and carbon dioxide. Furthermore, UGLD is excellent for early detection of hydrogen sulphide releases provided it is mixed into methane for example.
Page 82
stations along pipelines, LNG facilities, FPSOs, gas fired power plants and certain parts of chemical facilities. Implementation and operation Implementation of UGLD is relatively simple. Allocation of detectors can be done either based on F&G plant layouts or by performing an onsite mapping survey. UGLD is integrated directly into the F&G system (plant DCS or PLC). During the commissioning, onsite testing and calibration can be carried out as well as live leak simulation to verify the coverage at a distance from the detectors.
The UGLDs do not have any consumables and significant drift. This enables a long life time and minimal maintenance requirements.
Reasons for including UGLD from a loss and prevention point of view:
Integration with other F&G devices UGLD can be used on its own or together with other detector types. To optimize the plant safety level and increase detection reliability, it is always recommended to consider applying different independent layers of protection. It is further advised to incorporate UGLDs in the overall plant F&G voting architecture and thereby increase speed of response.
Speed of response â&#x20AC;&#x201C; the leak noise can be detected at the speed of sound Probability of failure of detection due to wind conditions and leak properties is low Coverage verification can be carried out during commissioning Self-test mechanism limits the risk of unidentified failures
Page 83 Page 83
Explanation and Expressions
Hertz (Hz): Measure for frequencies.
Amplitude: The degree of change in atmospheric pressure
High noise areas: In this handbook, area where ultrasonic
caused by sound waves. It describes the volume of the
background noise is less than 78 dB.
acoustic sound (measured in dB). Background noise: Ambient noise in the area where the UGLD is to be implemented. In this handbook it refers to ultrasonic ambient noise.
Human sensory model: A construct for developing fire and gas sensors based on the classical human senses. Independent Protection Layers (IPLs): An independent mechanism that reduces risk by control, prevention or
Conventional gas detectors: A detector that relies on detection methods that are well established in the
mitigation (ISA-84 2004).
fire and gas industry usually based on identifying and
Leak rate: Amount of gas escaping from a leak per unit
measuring gas concentrations - for example open-path
time, also known as mass flow rate.
and point detectors.
Leak size: the size (diameter) of a leak. Measured in
Decibel (dB): Unit for sound pressure level or volume.
millimeter (or inches).
Detection coverage: The area that a detector covers.
Leak sources: Refers to locations where gas leaks may occur, e.g. flanges or valves.
Frequency: Number of crests of sound wave that pass a given point per unit time. Describes the high and low
Lower Explosive Limit (LEL): Lowest concentration of gas
pitches in acoustic sound (measured in Hz).
in air capable of producing a flash of fire in the presence of an ignition source.
Page 84
Low noise areas: Area where the ultrasonic background
safety instrumented systems.
noise is less than 68 dB. SIL suitability: Capacity of a device to operate in a certain Mapping Survey: A service provided to determine the
SIL environment based on compliance with IEC 61508.
ultrasonic background noise level prior to installation. Sound Pressure Level (SPL): A logarithmic measure Parts per million (ppm): A unit of concentration corre-
of the effective sound pressure of a sound relative to
sponding to one part, either by weight or volume, for every
a reference value, measured in decibels above the
million parts.
standard reference level.
Safety Instrumented System (SIS): An instrumented
Total speed of response: The time elapsed from the onset
system used to implement one or more safety instrumented
of a leak until it is picked up by the detector (includes the
functions. It is composed of any combination of sensors,
time required for the gas to reach the sensor head of a
logic solvers, and final elements.
conventional gas detector).
Senssonicâ&#x201E;˘ self-test: Acoustic self-test that ensures the
UGLD: Abbreviation for ultrasonic gas leak detector or
failsafe operation of certain Gassonic gas leak detectors.
ultrasonic gas leak detection.
Shadowing or blockage: Refers to situations where there
Very low noise areas: Area where the ultrasonic
is a solid, physical obstruction between the leak source
background noise is less than 58 dB.
and the detector. Voting: Alarm configuration procedure in the control Safety Integrity Level (SIL): A discrete level (one out of
room. Voting of detectors prior to executive action is
four) for specifying the safety integrity requirements of
often performed to ensure automatic operations from the
the safety instrumented functions to be allocated to the
fire and gas detection system. Page 85
Gassonic Handbook: BP2009 - 1
Gassonic Denmark Energivej 42 A DK-2750 Ballerup Tel: +45-44-700-910 Fax: +45-44-700-911 mail@gassonic.com
General Monitors - CA 26776 Simpatica Circle Lake Forest, California 92630 Tel: +1-949-581-4464 Fax: +1-949-581-1151 info@generalmonitors.com
General Monitors - Singapore No. 2 Kallang Pudding Road #09-16 Mactech Building Singapore 349307 Tel: +65-6-748-3488 Fax: +65-6-748-1911 genmon@gmpacifica.com.sg
General Monitors - TX 9776 Whithorn Drive Houston, Texas 77095 Tel: +1-281-855-6000 Fax: +1-281-855-3290 gmhou@generalmonitors.com
General Monitors - Ireland Ballybrit Business Park Galway Republic of Ireland Tel: +353-91-751175 Fax: +353-91-751317 info@gmil.ie
General Monitors - UAE PO BOX 61209 Dubai, United Arab Emirates Tel: +971-4-8143814 Fax: +971-4-8857587 gmme@generalmonitors.ae
www.gassonic.com
www.generalmonitors.com
General Monitors - UK Heather Close Lyme Green Business Park Macclesfield, Cheshire United Kingdom, SK11 0LR Tel: +44-1625-619583 Fax: +44-1625-619-098 info@generalmonitors.co.uk