Maggie Grady Work Sample

Page 1

LANKERSHIM + otsego

DE Architects AIA 1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 91601 & 5130 KLUMP AVE., NORTH HOLLYWOOD, CA 91601

KLUMP (R4-2) PORTION - 6 STORIES MULTIFAMILY HOUSING, OVER 1 LEVEL GARAGE, OVER TWO LEVELS SUBTERRANEAN GARAGE. THE PROJECT WILL PROVIDE 11% VERY LOW INCOME HOUSING, THEREFORE THE PROJECT IS ENTITLED TO 2 INCENTIVES.

INCENTIVES:

FLOOR AREA RATIO (12.22.A.25.(f)(4) AVERAGING OF FAR, DENSITY, PARKING OR OPEN SPACE, AND PERMITTING VEHICULAR ACCESS. (12.22.A.25.(f)(8)

PLANNING/ZONING INFORMATION LEGAL DESCRIPTION: SEE A.L.T.A. / A.C.S.M. LAND TITLE SURVEY SHEET 1 OF 2. PROJECT SITE INFORMATION: SITE ADDRESS: 5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 91601 5130 KLUMP AVE., NORTH HOLLYWOOD, CA 91601 CASE NUMBER: ZONE: C4-1-CA / R4-2 APN: 2353-004-023, 2353-004-022, 2353-004-027, 2353-004-028 APPLICANT: CONTACT PERSON: CHRISTOPHER MURRAY / ROSENHEIM & ASSOCIATES, INC. 21600 OXNARD STREET, SUITE 630, WOODLAND HILLS, CA 91367 (TEL- 818.716.2782) OWNER: NOHOLOHA LLC, NOHO KA OI LLC, CAMDEN NOHO SPV LLC CONTACT PERSON: DONALD HAYES 21550 OXNARD STREET, SUITE 860, WOODLAND HILLS, CA 91367 (TEL. 818-888-1968) PROPOSED USE: LANKERSHIM (C4-1) PORTION - 6 STORIES MULTIFAMILY HOUSING, OVER 1 LEVEL COMMERCIAL/GARAGE, OVER TWO LEVELS SUBTERRANEAN GARAGE. KLUMP (R4-2) PORTION - 6 STORIES MULTIFAMILY HOUSING, OVER 1 LEVEL GARAGE, OVER TWO LEVELS SUBTERRANEAN GARAGE. THE PROJECT WILL PROVIDE 11% VERY LOW INCOME HOUSING, THEREFORE THE PROJECT IS ENTITLED TO 2 INCENTIVES. INCENTIVE #1 = FLOOR AREA RATIO (12.22.A.25.(f)(4) INCENTIVE #2 = AVERAGING OF FAR, DENSITY, PARKING OR OPEN SPACE, AND PERMITTING VEHICULAR ACCESS. (12.22.A.25.(f)(8) ZONING

- C4-1-CA / R4-2

HEIGHT LIMIT FOR R4-2 & C4-1

- UNLIMITED

PROPOSED HEIGHT

- 87'-0" TAKEN FROM LOWEST ADJACENT GRADE AT EL:617.91’ TOP OF PARAPET EL:704.91’

CONSTRUCTION TYPE

UNIT MIX:

TYPE IIIA CONSTRUCTION - 5 STORIES TYPE III RESIDENTIAL OVER TYIPE IA GROUND FLOOR COMMERCIAL/ PARKING / RESIDENTIAL. PORTION OF LANKERSHIM = 198 UNITS (42 STUDIOS, 106-1 BEDROOMS, 50-2 BEDROOMS) PORTION OF KLUMP = 99 UNITS (0 STUDIO, 77 - 1 BEDROOMS, 22 - 2 BEDROOMS) TOTAL UNIT MIX = 297 UNITS (42 STUDIOS, 183 - 1 BEDROOMS, 72 - 2 BEDROOMS)

SECOND FLOOR: RESIDENTIAL AREA #1 RESIDENTIAL AREA #2 RESIDENTIAL AREA #3 RESIDENTIAL AREA #4 KLUMP BALCONIES LANKERSHIM BALCONIES TOTAL THIRD FLOOR: RESIDENTIAL AREA #1 RESIDENTIAL AREA #2 RESIDENTIAL AREA #3 RESIDENTIAL AREA #4 RESIDENTIAL AREA #5 KLUMP BALCONIES LANKERSHIM BALCONIES TOTAL

= 12,354 SF = 13,151 SF = 6,181 SF = 14,944 SF = 167 SF = 1,806 SF = 48,603 SF = 13,691 SF = 8,759 SF = 10,463 SF = 9,179 SF = 6,088 SF = 144 SF = 834 SF = 49,158 SF

FOURTH FLOOR: RESIDENTIAL AREA #1 RESIDENTIAL AREA #2 RESIDENTIAL AREA #3 RESIDENTIAL AREA #4 AREA #5 KLUMP BALCONIES LANKERSHIM BALCONIES TOTAL

= 13,311 SF = 8,759 SF = 10,463 SF = 9,179 SF = 6,088 SF = 125 SF = 883 SF = 48,808 SF

FIFTH FLOOR: RESIDENTIAL AREA 1 RESIDENTIAL AREA 2 RESIDENTIAL AREA 3 RESIDENTIAL AREA 4 RESIDENTIAL AREA 5 KLUMP BALCONIES LANKERSHIM BALCONIES TOTAL

= 13,340 SF = 8,743 SF = 10,463 SF = 9,179 SF = 6,088 SF = 140 SF = 852 SF = 48,805 SF

SIXTH FLOOR: RESIDENTIAL AREA 1 RESIDENTIAL AREA 2 RESIDENTIAL AREA 3 RESIDENTIAL AREA 4 RESIDENTIAL AREA 5 KLUMP BALCONIES LANKERSHIM BALCONIES TOTAL

= 13,335 SF = 8,759 SF = 10,799 SF = 9,179 SF = 6,088 SF = 146 SF = 878 SF = 49,184 SF

SEVENTH FLOOR: RESIDENTIAL AREA 1 RESIDENTIAL AREA 2 RESIDENTIAL AREA 3 RESIDENTIAL AREA 4 RESIDENTIAL AREA 5 TOTAL

= 1,695 SF = 8,759 SF = 10,780 SF = 9,179 SF = 3,980 SF = 34,393 SF

- 29,845.0 SQ.FT. LOT AREA (DENSITY) - 29,845.0 / 400 = 74.61 UNITS ALLOWABLE DENSITY ALLOWABLE 35% DENSITY BONUS - 74 X 1.35 = 100 UNITS ALLOWED / 99 PROPOSED BUILDABLE AREA (ALLOWABLE)

- SUBTRACT THE FOLLOWING SETBACKS 15' FRONT YARD, 5' SIDE YARDS, 15' REAR YARD -6 X BUILDABLE AREA – 25,135.5 SQ.FT. X 6 = 150,813 SQ.FT. 150,813 X 1.35 (BONUS) = 203,597.5 SF

C4-1 PORTION LOT SIZE DEDICATIONS LOT AREA ZONING DENSITY

- IRREGULAR - 2' ALONG LANKERSHIM & 7' ALONG OTSEGO (AFTER DEDICATION) - 56,534.8 SQ. FT. - C4-1 - 1 UNIT PER 400 SQ.FT. OF LOT AREA

- 59,111.63 SQ.FT. LOT AREA (DENSITY) - 59,111.63 / 400 = 147.77 UNITS ALLOWABLE DENSITY ALLOWABLE 35% DENSITY BONUS - 147 X 1.35 = 199 UNITS ALLOWED / 198 PROPOSED FAR BUILDABLE AREA (ALLOWED)

OCCUPANCY:

R2 / S2 / M

NO. OF STORIES: 7 STORIES: 5 LEVELS OF TYPE III(A) CONSTRUCTION OVER 2 LEVELS OF TYPE I(A) CONSTRUCTION (ABOVE GRADE PARKING, MARKET & RESIDENTIAL) OVER 2 LEVEL SUBTERRANEAN GARAGE; MODIFICATION REQUESTED FOR 2 STORIES TYPE 1(A) THIS BUILDING AND GARAGE MUST BE EQUIPPED WITH AN AUTOMATIC FIRE EXTINGUISHING SYSTEM, COMPLYING WITH NFPA-13. THE SPRINKLER SYSTEM SHALL BE APPROVED BY PLUMBING DIV. PRIOR TO INSTALLATION.

R-2, TYPE IIIA CONSTRUCTION (TABLE 601)

BUILDING ELEMENT

RATING

OPENINGS

STC

STRUCTURAL FRAME

1 HOUR

N.A.

N.A.

PER 704.8, 3/4 HOUR

N.A.

1.5

BEARING WALLS - INT.

1 HOUR

N.A.

N.A.

1.5 X 59,110.8 SQ.FT.= 88,666.2 SQ.FT. 88,666.2 X 1.35 (BONUS) = 119,699.37 SQ. FT.

NONBEARING WALLS - EXT. 1 HOUR < 30 FEET 0 HOUR > 30 FEET (TABLE 602) NC OR AFRTW PER 602.3 NONBEARING WALLS - INT. 0 HOUR

PER 704.8, 3/4 HOUR

N.A.

N.A.

N.A.

FLOOR

1 HOUR

N.A.

N.A.

ROOF

1 HOUR

N.A.

N.A.

NONE

50

PROPOSED DENSITY: 297 UNITS + 25,307 SQ.FT OF FUTURE MARKET (99 UNITS OF KLUMP) + (198 UNITS OF LANKERSHIM)

TENANT SEP. PARTY WALL 1 HOUR

TOTAL BUILDABLE AREA (R4-2+C4-1) ALLOWED: 203,597.5 SQ.FT. + 119,699.37 SQ.FT. = 323,296.87 SQ.FT. (PROJECT UTILIZES FLOOR ARE RATIO BONUS INCREASE OF 35%) (SINCE PROJECT UTILIZES AVERAGING INCENTIVE BUILDABLE AREA CAN BE AVERAGED ON PROPERTY)

TENANT CORRIDOR

1 HOUR

FIRE WALLS

3 HOURS

1-1/2 HOURS

50 *

STAIRS

1 HOUR WOOD FRAMED OR NC

N.A.

N.A.

EXIT STAIR & ELEVATOR ENCLOSURES

2 HOURS (CONNECTING 4 STORIES OR MORE)

1-1/2 HOURS

50 **

SERVICE CHUTE & VENT SHAFT ENCLOSURES

2 HOURS (CONNECTING 4 STORIES OR MORE)

PER 707.7 - 707.12

50 **

TENANT SEP. FLOOR/CLG. 1 HOUR

NONE

50 + IIC 50

1/3 HOUR W/ SMOKE & 50 + STC 26 DRAFT CONTROL GASKETS DOOR

GOVERNING CODES 2014 CITY OF LOS ANGELES BUILDING CODE BASED ON 2013 CALIFORNIA BUILDING CODE CALIFORNIA CODE OF REGULATIONS TITLE 24, PART 2 VOLUME 142. CHAPTER 11A 2013 CALIFORNIA BUILDING CODE. 2013 CALIFORNIA PLUMBING CODE 2013 CALIFORNIA MECHANICAL CODE 2013 CALIFORNIA ELECTRICAL CODE 2013 CALIFORNIA GREEN BUILDING STANDARDS CODE 2013 CALIFORNIA FIRE CODE 1998 FEDERAL FAIR HOUSING ACT (FHA) 2010 AMERICANS WITH DISABILITIES ACT (ADA)

NOTES: 100% PRIVATELY FUNDED, NO TAXCREDIT, NO PUBLIC HOUSING

VICINITY MAP

BUILDING ELEMENT

RATING

OPENINGS

STC

STRUCTURAL FRAME

3 HOURS NC

N.A.

N.A.

BEARING WALLS - EXT.

3 HOURS NC

PER 704.8, 3/4 HOUR

N.A.

BEARING WALLS - INT.

3 HOURS NC (MAY BE REDUCED TO 2 HOURS WHERE SUPPORTING ROOF ONLY) 1 HOUR NC < 30 FEET 0 HOUR NC OR AFRTW > 30 FEET 0 HOUR

N.A.

N.A.

3/4 HOUR < 30 FEET 0 HOUR > 30 FEET

N.A.

0 HOUR

N.A.

FLOOR

2 HOURS

SHAFT

N.A.

ROOF

1-1/2 HOURS

N.A.

N.A.

TENANT SEP. PARTY WALL 1 HOUR (R OCC)

NONE

50

TENANT SEP. FLOOR/CLG. 1 HOUR (R OCC)

NONE

50 + IIC 50

TENANT CORRIDOR

1/3 HOUR W/ SMOKE & DRAFT CONTROL GASKETS 1-1/2 HOURS

50 + STC 26 DOOR

N.A.

NONBEARING WALLS/ PARTITIONS - EXTERIOR (TABLE 602) NONBEARING WALLS/ PARTITIONS - INTERIOR

1 HOUR

FIRE WALLS

3 HOURS

50 *

STAIRS

1 HOUR WOOD FRAMED OR NC

N.A.

EXIT STAIR & ELEVATOR ENCLOSURES

2 HOURS (CONNECTING 4 STORIES OR MORE)

1-1/2 HOURS

50 **

SERVICE CHUTE & VENT SHAFT ENCLOSURES

2 HOURS (CONNECTING 4 STORIES OR MORE)

PER 707.7 - 707.12

50 **

* WHEN ADJACENT TO LIVING AREAS ** WHEN ADJACENT TO LIVING AREAS AND/OR OCCUPIED PUBLIC AREAS NOTES:

3/9/2017 2:27:41 PM

ALL FIRE RATED ASSEMBLIES SHALL BE PER TABLE 720. GENERIC ASSEMBLIES OF GYPSUM HANDBOOK, HAVE LARR APPROVAL OR ICC APPROVAL.

OPEN SPACE: LANDSCAPE REQUIREMENTS: LANDSCAPE REQUIREMENTS - (SECTION 12.21 G (A3) = 18,544 SF X .25 TREE REQUIREMENTS - 1 - 24" BOX TREE FOR EVERY 4 UNITS (297/4 = 74.25) (SEE LANDSCAPE PLANS)

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

= 4,636 SF = 75 TREES

UNIT L - A3 - SIM 6

702 S.F. - 733 S.F.

1

1

0 BEDROOM UNITS = 7 1 BEDROOM UNITS = 19 2 BEDROOM UNITS = 10

0 BEDROOM UNITS = 8 1 BEDROOM UNITS = 19 2 BEDROOM UNITS = 10

0 BEDROOM UNITS = 4 1 BEDROOM UNITS = 10 2 BEDROOM UNITS = 7

ARCHITECT: DE ARCHITECTS, AIA. 1535 6TH STREET SUITE 101 SANTA MONICA, CA 90401 TEL. (310) 451-7917

ELECTRICAL ENGINEER Z. VORGIAS CONSULTING ELECTRICAL ENGINEERING INC. 232 N. LAKE AVE, SUITE 212 PASADENA, CA 91101 TEL. (626) 577-0449

STRUCTURAL ENGINEER JOHN LABIB + ASSOCIATES 319 MAIN STREET EL SEGUNDO, CA 90245 TEL. (213) 239-9600

TOTAL UNIT MIX = 198 0 BEDROOM UNITS = 42 1 BEDROOM UNITS = 106 2 BEDROOM UNITS = 50

1

1

UNIT L - C

741 S.F.

1

1

1 BEDROOM UNITS = 0 2 BEDROOM UNITS = 0

1 BEDROOM UNITS = 14 2 BEDROOM UNITS = 3

1 BEDROOM UNITS = 13 1 BEDROOM UNITS = 13 2 BEDROOM UNITS = 4 2 BEDROOM UNITS = 4

DEFERRED SUBMITTALS

UNIT L - D

636 S.F.

1

1

FIFTH FLOOR: 17 UNITS

SIXTH FLOOR: 17 UNITS

SEVENTH FLOOR: 14 UNITS

UNIT L - E - SIM 5

739 S.F.

1

1

1 BEDROOM UNITS = 13 2 BEDROOM UNITS = 4

1 BEDROOM UNITS = 13 2 BEDROOM UNITS = 4

1 BEDROOM UNITS = 11 2 BEDROOM UNITS = 3

DEFERRED SUBMITTALS: WET STANDPIPE, FIRE SPRINKLERS, FIRE ALARM, LIFE SAFETY, THICKNESS OF FIRE PROOFING MATERIAL ON STRUCTURAL STEEL MEMBERS, METAL SIDING, ELEVATOR, MECHANICAL, PLUMBING, ELECTRICAL, SIGNS, STOREFRONT, DEMOLITION AND GLASS GUARDRAILS ARE NOT A PART OF THIS PERMIT. THEY WILL BE SUBMITTED FOR PLAN CHECK AS REQUIRED DURING CONSTRUCTION BY THE CONTRACTOR. THESE DOCUMENTS SHALL BE SUBMITTED TO THE ARCHITECT OR ENGINEER OF RECORD, WHO SHALL REVIEW THEM AND RETURN BACK TO CONTRACTOR WITH A NOTATION INDICATING THAT THE DOCUMENTS HAVE BEEN REVIEWED AND THAT THEY HAVE BEEN FOUND TO BE IN GENERAL CONFORMANCE WITH THE DESIGN OF THE BUILDING. THESE SEPARATE ITEMS SHALL NOT BE INSTALLED UNTIL THEIR DESIGN AND SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE DEPARTMENT OF BUILDING AND SAFETY.

UNIT L - E1 - SIM 8

718 S.F.

1

1

UNIT L - E2 - SIM 9

718 S.F. - 726 S.F.

1

1

UNIT L - E3 - SIM 11

686 S.F. - 720 S.F.

1

1

UNIT L - E4 - SIM 1

734 S.F. - 736 S.F.

1

1

UNIT L - E5

736 S.F.

1

1

UNIT L - E6 - SIM 3

704 S.F.

1

1

UNIT L - E7

715 S.F.

1

1

UNIT L - F

795 S.F.

1

1

UNIT L - F1

810 S.F.

1

1

UNIT L - G

809 S.F.

1

1

UNIT L - G1

782 S.F.

1

1

UNIT L - H - SIM 3

703 S.F.

1

1

UNIT L - J - SIM 1

829 S.F.

1

1

UNIT L - M - SIM 4

724 S.F.

1

1

UNIT L - N

1127 S.F.

2

2

UNIT L - N1

1084 S.F.

2

2

UNIT L - P

1126 S.F.

2

2

UNIT L - Q

1209 S.F.

2

2

UNIT L - R - SIM 3

1105 S.F. - 1106 S.F.

2

2

UNIT L - R1 - SIM 3

1108 S.F.

2

2

UNIT L - R2

1067 S.F.

2

2

UNIT L - S - SIM 1

1161 S.F.

2

2

UNIT L - T - SIM 3

1040 S.F.

2

2

UNIT L - U - SIM 4

1110 S.F. - 1126 S.F.

2

2

UNIT L - V

1158 S.F.

2

2

UNIT L - W

1041 S.F.

2

2

UNIT L - X - SIM 1

1240 S.F.

2

2

UNIT L - Y - SIM 3

1141 S.F.

2

2

UNIT L - Z

1160 S.F.

2

2

UNIT L - ZA

1284 S.F.

2

2

UNIT L - ZB

634 S.F.

1

1

UNIT L - ZC

492 S.F.

1

1

UNIT L - ZD

541 S.F.

1

1

UNIT L - ZE

577 S.F.

1

1

UNIT L - ZF

577 S.F.

1

1

UNIT L - ZG

568 S.F.

1

1

UNIT L - ZH - SIM 1

562 S.F. - 564 S.F.

1

1

UNIT L - ZJ - SIM 1

579 S.F.

1

1

UNIT L - ZM

581 S.F.

1

1

UNIT L - ZM2 SIM 3

572 S.F.

1

1

UNIT L - ZN

559 S.F.

1

1

UNIT L - ZO

565 S.F.

1

1

UNIT L - ZP

584 S.F.

1

1

UNIT L - ZQ

500 S.F.

1

1

KLUMP UNIT MIX: GROUND FLOOR: 0 UNITS SECOND FLOOR: 17 UNITS THIRD FLOOR: 17 UNITS FOURTH FLOOR: 17 UNITS

LAND USE: ROSENHEIM & ASSOCIATES, INC 21600 OXNARD STREET, SUITE 630 WOODLAND HILLS, CA 91367 TEL. (818) 716-2782

CIVIL PE&C CIVIL ENGINEERING PE&C CIVIL ENGINEERING 909 N AVIATION BLVD, STE 3 TEL. (310) 318-5069

LANDSCAPE ARCHITECT: SQLA LANDSCAPE ARCHITECT 380 N. PALM STREET SUITE B BREA, CA 92821 TEL. (562) 905-0800

STAMP

ED A RCH NS S EMP I A TA

ACOUSTICAL VENEKLASEN & ASSOCIATES, INC. 1711 SIXTEENTH STREET SANTA MONICA, CA 90404 TEL. (310) 450-1733

NO. C-13779

POOL CONSULTANT HOLDENWATER P.O. BOX 7080 FULLERTON, CA 92834 TEL. (714) 626-0333

INTERIOR DESIGNER DESIGNWEST 22942 COLLINS ST. TRAFFIC CONSULTANT: OVERLAND TRAFFIC CONSULTANTS WOODLAND HILLS, CA 91367 TEL. (818) 888-3182 INC. 24325 MAIN STREET #202 GENERAL CONTRACTOR SANTA CLARITA, CA 91321 TBD TEL. 661.799.8423

REN. 6-30-17

E

OF

A

1

830 S.F.

CA L I F

O

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

TOTAL UNIT MIX = 99 1 BEDROOM UNITS = 77 2 BEDROOM UNITS = 22 GRAND TOTAL (LANKERSHIM + KLUMP): TOTAL UNIT MIX = 297 0 BEDROOM UNITS = 42 1 BEDROOM UNITS = 183 2 BEDROOM UNITS = 72

CRA COMMUNITY BENEFIT - 2010 ADA UNITS UNIT TYPES

42 UNITS X 1 SPACE = 42 SPACES 183 UNITS X 1 SPACE = 183 SPACES 72 UNITS X 2 SPACES = 144 SPACES = 369 SPACES

REQUIRED = 25,307 SF (FUTURE MARKET) + 735 SF (LEASING OFFICE) / 500

= 52 SPACES

TOTAL PARKING SPACES REQUIRED

= 52 SPACES

= 421 SPACES

RESIDENTIAL PARKING PROVIDED: STANDARD SPACES STANDARD ADA SPACES STANDARD ADA / EVCS SPACES STANDARD EVCS SPACES COMPACT SPACES TOTAL PARKING PROVIDED

= 263 SPACES = 11 SPACES = 1 SPACES = 22 SPACES = 152 SPACES = 449 SPACES

(DISABLED ACCESS PARKING - 2% OF PARKING PROVIDED - 449X .02 = 9 SPACES) (VAN DISABLED ACCESS PARKING - 1 FOR EVERY 8 DISABLED ACCESS SPACES = 2 SPACES PER 1109A.8.6 CBC)

FUTURE MARKET PARKING PROVIDED: STANDARD SPACES (INCLUDES 5 ADA SPACES) STANDARD ADA SPACES STANDARD EVCS SPACES STANDARD ADA VAN SPACE (1 FOR EVERY 8 ADA SPACES PER 1109A.8.6 CBC) AND EVCS SPACES STANDARD CLEAN AIR/VANPOOL/EV CHARGING STATION SPACES COMPACT SPACES TOTAL PARKING PROVIDED

= 89 SPACES = 4 SPACES = 5 SPACES = 1 SPACE = 11 SPACES = 5 SPACES = 115 SPACES

(FUTURE MARKET DISABLED ACCESS PARKING = 5 SPACES PER TABLE 11B-208.2 (PARKING SPACES PROVIDED BETWEEN 101 TO 150) ) (VAN DISABLED ACCESS PARKING - 1 FOR EVERY 8 DISABLED ACCESS SPACES = 1 SPACE PER 1109A.8.6 CBC) (ELECTRIC VEHICLE CHARGING STATIONS REQUIRED =6 SPACES (115 SPACES X 0.05 = 5.75 SPACES) SEE 202b) (CLEAN AIR/VANPOOL/EV CHARGING STATIONS REQUIRED = 11 SPACES (PER TABLE A5.106.5.1.1) SEE 202b)

REQUIRED RESIDENTIAL BICYCLE PARKING: LONG TERM PARKING: 1 PER DWELLING UNIT (297 UNITS)

= 297 SPACES

SHORT TERM PARKING: 1/10 DWELLING UNITS (297 / 10)

= 30 SPACES

REQUIRED FUTURE MARKET BICYCLE PARKING: LONG TERM PARKING: 1 PER 2,000 SF. (25,307 SF / 2,000)

= 13 SPACES

SHORT TERM PARKING: 1 PER 2,000 SF. (25,307 SF / 2,000)

= 13 SPACES

PROVIDED RESIDENTIAL BICYCLE PARKING: LONG TERM PARKING: SHORT TERM PARKING:

= 298 SPACES = 31 SPACES

PROVIDED FUTURE MARKET BICYCLE PARKING: (PART OF COMMERCIAL T.I.) LONG TERM PARKING: SHORT TERM PARKING:

= 13 SPACES = 13 SPACES

OPEN SPACE: OPEN SPACE REQUIRED: = 225 X 100 = 72 X 125

= 22,500 SF = 9,000 SF = 31,500 SF

OPEN SPACE PROVIDED:

M, S-2, R2 TYPE IA CONSTRUCTION (TABLE 601)

1

SEVENTH FLOOR: 21 UNITS

UNIT L - B

OPEN SPACE REQUIRED PER LAMC: 42 STUDIOS + 183 ONE BEDROOM = 225 < THAN 3 HABITABLE ROOMS 72 TWO BEDROOM = 3 HABITABLE ROOMS TOTAL OPEN SPACE REQUIRED

* WHEN ADJACENT TO LIVING AREAS ** WHEN ADJACENT TO LIVING AREAS AND/OR OCCUPIED PUBLIC AREAS

739 S.F. - 737 S.F.

SIXTH FLOOR: 37 UNITS

1

BICYCLE PARKING:

SUBTERRANEAN PARKING LEVEL AREAS: P2 LEVEL: 77,539 SF P1 LEVEL: 75,273 SF TOTAL SUBTERRANEAN PARKING LEVEL AREA: 152,812 SF

UNIT L - A2 - SIM 1

FIFTH FLOOR: 36 UNITS

1

VOICE EVAC FIRE ALARM SYSTEM SHALL BE PROVIDED (DEFFERED SUBMITTAL) TWO WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEM SHALL BE PROVIDED AS REQUIRED BY THE 2013 CALIFORNIA FIRE CODE, PER LAFC SECTION 510 CITY OF LOS ANGELES REQUIREMENT #105 (DEFFERED SUBMITTAL)

1

718 S.F.

(ELECTRIC VEHICLE CHARGING STATIONS REQUIRED = 23 SPACES (450 SPACES X 0.05 = 22.5 SPACES) SEE A201b, A201d, A202d & A203d)

AVERAGE GRADE (619.82') TO AVERAGE HEIGHT OF THE HIGHEST ROOF SURFACE (703.82') = 84' - 0"

1

UNIT L - A6

TOTAL PARKING REQUIRED: FUTURE MARKET + RESIDENTIAL SPACES

HEIGHT LIMIT PER CBC: 65' - 0" + 20' - 0" (SPRINKLER SYSTEM INCREASE) = 85' - 0"

804 S.F.

1

PARKING PROVIDED:

NO

UNIT L - A1

1

= 323,296.87 SF

METHANE ZONE:

1

737 S.F.

ALLOWABLE SF

2

1

0 BEDROOM UNITS = 7 0 BEDROOM UNITS = 8 1 BEDROOM UNITS = 19 1 BEDROOM UNITS = 20 2 BEDROOM UNITS = 10 2 BEDROOM UNITS = 9

UNIT L - A5

NO GUEST PARKING REQUIRED OR PROVIDED.

FIRE DISTRICT:

773 S.F. - 776 S.F.

0 BEDROOM UNITS = 8 1 BEDROOM UNITS = 19 2 BEDROOM UNITS = 4

1

FUTURE MARKET: ENTERPRISE ZONE = 1 PER 500 SF.

TYPE I (A) & TYPE III (A) - FULLY SPRINKLERED (NFPA 13) (CONCEALLED HEADS THROUGHOUT - EXCEPT IN GARAGE AREAS)

UNIT L - A - SIM 1

1 BEDROOM UNITS = 0 2 BEDROOM UNITS = 0

1

= 308,168 SF

CONSTRUCTION TYPE:

NO. OF BATHROOMS

673 S.F.

TOTAL PARKING SPACES REQUIRED

BUILDING CODE INFORMATION

NO. OF BEDROOMS

UNIT L - A4

RESIDENTIAL (PER SB1818 PARKING OPTION 1): LESS THAN 3 HABITABLE ROOMS (STUDIO UNITS) 3 HABITABLE ROOMS (1 BEDROOM UNITS) MORE THAN 3 HABITABLE ROOMS (2&3 BEDROOM UNITS)

2 HOURS NC OR AFRTW PER 602.3

PRIOR TO THE ISSUANCE OF THE BUILDING PERMIT, THE FRONT SHEET OF THE FINAL SETS OF PLANS, AS WELL AS OTHER SHEETS THAT ARE RELEVANT TO THE GREEN BUILDING REQUIREMENTS, SHALL BE STAMP-APPROVED BY THE DEPARTMENT OF CITY PLANNING.

231,556 SQ. FT. < 273,273.6 SQ. FT.

PARKING REQUIRED:

BEARING WALLS - EXT.

LOT AREA AND BUILDABLE AREA: ALLOWABLE DENSITY - R4-2 ( 100 UNITS) + C4-1 (199 UNITS) = 299 UNITS (W/ 35% BONUS DENSITY) (SEE CALCULATION ABOVE)

TOTAL BUILDING AREA:

GRAND TOTAL

PROPOSED HEIGHT: - IRREGULAR - 7'-0" ALONG KLUMP AVENUE (AFTER DEDICATION) - 29,217.24 SQ.FT. - R4-2 - 1 UNIT PER 400 SQ.FT. OF LOT AREA

57,460 SQ.FT. < 60,916.8 SQ.FT 44,845 SQ.FT. < 48,000 SQ.FT. 22,105 SQ.FT. < 48,000 SQ.FT. 31,248 SQ.FT. < 48,000 SQ.FT. 46,570 SQ.FT. < 48,000 SQ.FT. 29,140 SQ. FT. < 48,000 SQ. FT.

PARKING CALCULATIONS

R4-2 PORTION LOT SIZE DEDICATIONS LOT AREA ZONING DENSITY

AREA 1 - BUILDING AREA: AREA 2 - BUILDING AREA: AREA 3 - BUILDING AREA: AREA 3a - BUILDING AREA: AREA 4 - BUILDING AREA: AREA 5 - BUILDING AREA:

NET ( S.F. )

MECHANICAL/PLUMBING/ ENERGY CONSULTANT JAYCOCAL ENGINEERING, INC. 232 N. LAKE AVENUE, SUITE 217 PASADENA, CA 91101 TEL. (626)-449-2490

NI

= 25,261 SF = 1,320 SF = 656 SF = 1,495 SF = 485 SF = 29,217 SF

UNIT NAME

OWNER: NOHOLOHA LLC, NOHO KA OI LLC, CAMDEN NOHO SPV LLC 21550 OXNARD STREET, SUITE 860 WOODLAND HILLS, CA 91367 TEL. (818) 888-1968

T

LANKERSHIM (C4-1) PORTION - 6 STORIES MULTIFAMILY HOUSING, OVER 1 LEVEL COMMERCIAL/GARAGE, OVER TWO LEVELS SUBTERRANEAN GARAGE.

PROPOSED USE:

MAX ALLOWABLE AREA PER STORY PER EQUATION 5-2: 24,000 SQ. FT.

LANKERSHIM UNIT MIX: GROUND FLOOR: 0 UNITS SECOND FLOOR: 31 UNITS THIRD FLOOR: 36 UNITS FOURTH FLOOR: 37 UNITS

R

GROUND FLOOR FUTURE MARKET LOBBY #1 MEZZANINE LOBBY #2 LOBBY #3 TOTAL

LANKERSHIM UNIT TYPE SUMMARY

ST A

OWNER: CONTACT PERSON:

INCENTIVE #1 INCENTIVE #2

TOTAL BUILDABLE AREA (R4-2 + C4-1) PROPOSED:

C4-1-CA / R4-2 2353-004-023, 2353-004-022, 2353-004-027, 2353-004-028 CHRISTOPHER MURRAY / ROSENHEIM & ASSOCIATES, INC. 21600 OXNARD STREET, SUITE 630, WOODLAND HILLS, CA 91367 (TEL- 818.716.2782) NOHOLOHA LLC, NOHO KA OI LLC, CAMDEN NOHO SPV LLC DONALD HAYES 21550 OXNARD STREET, SUITE 860, WOODLAND HILLS, CA 91367 (TEL. 818-888-1968)

ALLOWABLE BUILDING AREA

PROJECT TEAM

UNIT CALCULATIONS:

CT TE ERIS K

CASE NUMBER: ZONE: APN: APPLICANT: CONTACT PERSON:

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 91601 5130 KLUMP AVE., NORTH HOLLYWOOD, CA 91601

ALLOWABLE BUILDABLE AREA (R4-2 + C4-1) = 323,296.87 SF

UNIT TYPE SUMMARY

OPEN SPACE PROVIDED PER LAMC PRIVATE OPEN SPACE - 272 UNITS X 50 SF SECOND FLOOR LANKERSHIM USABLE COMMON OPEN SPACE: OUTDOOR RECREATION SPACE COURTYARD SPACE TOTAL USABLE COMMON OPEN SPACE PASSIVE RECREATION SPACE: FITNESS CENTER/YOGA ROOM LOUNGE/RESIDENT BUSINESS CENTER TOTAL PASSIVE RECREATION SPACE

= 13,600 SF

= 1,047 SF = 4,598 SF = 5,645 SF

= 2,865 SF = 1,941 SF = 4,806 SF

SECOND FLOOR KLUMP USABLE COMMON OPEN SPACE: PODIUM DECK SPACE TOTAL USABLE COMMON OPEN SPACE

= 591 SF = 591 SF

TOTAL PASSIVE RECREATION SPACE:

= 0 SF

SEVENTH FLOOR LANKERSHIM USABLE COMMON OPEN SPACE: POOL DECK SPACE LOUNGE DECK SPACE TOTAL USABLE COMMON OPEN SPACE

= 10,066 SF = 530 SF = 10,596 SF

PASSIVE RECREATION SPACE: LOUNGE/GAME ROOM TOTAL PASSIVE RECREATION SPACE

= 1,769 SF = 1,769 SF

SEVENTH FLOOR KLUMP USABLE COMMON OPEN SPACE: SPA DECK TOTAL USABLE COMMON OPEN SPACE:

= 1,712 SF = 1,712 SF

PASSIVE RECREATION SPACE: RECREATION ROOM TOTAL PASSIVE RECREATION SPACE

0 BEDROOM TOTAL NO. OF UNIT TYPES

1 BEDROOM

2 BEDROOM

TOTAL NO. OF UNITS

42

183

72

297

1

8

3

12

L626

L314, L320, L405, L503, L510, K313, K412, K508

L411, L524, K415

1

3

1

L307

K309, K403, K507

L636

40

172

68

CRA COMMUNITY BENEFIT 2010 ADA UNITS (FOR PHYSICALLY IMPAIRED) PROVIDED ASSIGNED UNITS #

CRA COMMUNITY BENEFIT 2010 ADA UNITS (FOR THE VISUAL & HEARING IMPAIRED)

PROVIDED ASSIGNED UNITS #

5

NO. OF CBC 2013 11A ADAPTABLE PROVIDED

280

KLUMP UNIT TYPE SUMMARY UNIT NAME

NET ( S.F. )

NO. OF BEDROOMS

NO. OF BATHROOMS

UNIT K - A - SIM 3

706 S.F.

1

1

UNIT K - A1 - SIM 2

698 S.F. - 7.4 S.F.

1

1

UNIT K - A2 - SIM 2

706S.F. - 707 S.F.

1

1

UNIT K - A3

758 S.F.

1

1

UNIT K - A4

902 S.F.

1

1

UNIT K - B

760 S.F.

1

1

UNIT K - C

724 S.F.

1

1

UNIT K - D

681 S.F.

1

1

UNIT K - E - SIM 13

700 S.F.

1

1

UNIT K - E1

710 S.F.

1

1

UNIT K - E2

722 S.F.

1

1

UNIT K - F - SIM1

707 S.F.

1

1

UNIT K - G - SIM 2

705 S.F.

1

1

UNIT K - H

1089 S.F.

2

2

UNIT K - J

1103 S.F.

2

2

UNIT K - M

1079 S.F.

2

2

UNIT K - N - SIM 1

1083 S.F.

2

2

UNIT K - N1 - SIM 1

1082 S.F.

2

2

UNIT K - O - SIM1

1089 S.F.

2

2

UNIT K - P

1099 S.F.

2

2

SHEET TITLE

TITLE SHEET

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

DATE

1501 03-03-2017

TOTAL USABLE COMMON OPEN SPACE TOTAL PASSIVE RECREATION SPACE TOTAL PASSIVE RECREATION SPACE PER LAMC (TOTAL PASSICE RECREATION SPACE CANNOT EXCEED 25% OF REQUIRED USABLE OPEN SPACE PER 12.21 G.2(a)(4)(i) - 18,544 SF X 0.25 = 4,636 SF) TOTAL PRIVATE OPEN SPACE

= 18,544 SF = 7,374 SF = 4,636 SF

SCALE

= 13,600 SF

SHEET NO.

TOTAL OPEN SPACE PROVIDED PER LAMC:

= 36,780 SF

TOTAL OPEN SPACE PROVIDED: = 39,518 SF (INCLUDES ADDITIONAL PASSIVE RECREATION SPACE EXCEEDING 25% OF USABLE OPEN SPACE)

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO. = 799 SF = 799 SF

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

PROJECT SITE INFORMATION: SITE ADDRESS:

BUILDING AREA

L IC E DONA

SEE A.L.T.A. / A.C.S.M. LAND TITLE SURVEY SHEET 1 OF 2.

LEGAL DESCRIPTION:

ZONING BUILDING AREA

LANKERSHIM + otsego

PROJECT INFORMATION

As indicated

A001


EXISTING FOUR STORY PARKING GARAGE

AREA 1 - CALCULATIONS EQUATION 5-2 AREA INCREASE DUE TO FRONTAGE (If) If = [ F/P - 0.25 ] W/30 If = [333.75 / 676.81 - 0.25 ] 30/30 = .2431

ASSUMED PROPERTY LINE

F = PERIMETER FRONTAGE = 333.75' (F1+F2) (171.12+162.63) P = TOTAL PERIMETER = 676.81 (P1+P2+P3+P4+P5+P6+P7+P8+P9) (192.35+162.63+69.73+78.15+16.66+29.12+10.79+52.35+65.03)

DE Architects AIA 1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

Aa= { At + [At x If] + [At x Is] Aa= { 24,000 + [24,000 x .2431] + [24,000 x 0] Aa= { 24,000 + 5834.4 + 0} Aa= 29834.4

STAMP

AREA 1 - BUILDING AREA

AREA 4

ASSUMED PROPERTY LINE

REN. 6-30-17

E

T

AREA 5

NO. C-13779

13,917 SQ.FT. < 29,834.4 SQ.FT. 13,917 SQ.FT. < 29,834.4 SQ.FT. 13,929 SQ.FT. < 29,834.4 SQ.FT. 13,934 SQ.FT. < 29,834.4 SQ.FT. 1,763 SQ.FT. < 29,834.4 SQ.FT. 57,460 SQ.FT. < 59,668.8 SQ.FT. (MAX ALLOWABLE BUILDING AREA)

ST A

3 HR FIRE WALL, TYP. @ AREA SEPARATION

THIRD FLOOR: FOURTH FLOOR: FIFTH FLOOR: SIXTH FLOOR: SEVENTH FLOOR: TOTAL:

L IC E DONA

MAX ALLOWABLE AREA PER STORY PER EQUATION 5-2: 29,834.4 SQ.FT.

CT TE ERIS K

ED A RCH NS S EMP I A TA

OF

A

ALLOWABLE AREA PER STORY = 29834.4 SQ.FT. TOTAL ALLOWABLE BUILDING AREA PER SECTION 506.4.1: 2 x Aa = 59668.8 SQ.FT.

NI

EXISTING FOUR STORY BUILDING

R

KLUMP AVENUE

EQUATION 5-1 ALLOWABLE AREA (Aa)

CA L I F

O

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

AREA 2 - CALCULATIONS E NK LA HIM RS

ASSUMED PROPERTY LINE

EQUATION 5-1 ALLOWABLE AREA (Aa) Aa= { At + [At x If] + [At x Is] Aa= { 24,000 + [24,000 x 0] + [24,000 x 0] Aa= { 24,000 + 0 + 0} Aa= 24,000

EV UL BO

3 HR FIRE WALL, TYP. @ AREA SEPARATION

ALLOWABLE AREA PER STORY = 24,000 SQFT TOTAL ALLOWABLE BUILDING AREA PER SECTION 506.4.1: 2 x Aa = 48,000 SQFT

D AR

EXISTING TWO STORY BUILDING EXISTING FOUR STORY BUILDING

AREA 2 - BUILDING AREA MAX ALLOWABLE AREA PER STORY PER EQUATION 5-2: 24,000 SQ.FT. THIRD FLOOR: FOURTH FLOOR: FIFTH FLOOR: SIXTH FLOOR: SEVENTH FLOOR: TOTAL:

AREA 3

AREA 3a

8,963 SQ.FT. < 24,000 SQ.FT. 8,963 SQ.FT. < 24,000 SQ.FT. 8,965 SQ.FT. < 24,000 SQ.FT. 8,979 SQ.FT. < 24,000 SQ.FT. 8,975 SQ.FT. < 24,000 SQ.FT. 44,845 SQ.FT. < 48,000 SQ.FT. (MAX ALLOWABLE BUILDING AREA)

ASSUMED PROPERTY LINE

AREA 3 - CALCULATIONS EQUATION 5-1 ALLOWABLE AREA (Aa)

AREA 4 3 HR FIRE WALL, TYP. @ AREA SEPARATION

ALLOWABLE AREA PER STORY = 24,000 SQFT TOTAL ALLOWABLE BUILDING AREA PER SECTION 506.4.1: 2 x Aa = 48,000 SQFT

AREA 3 - BUILDING AREA

AD

AREA 3

AD

AREA 3a ASSUMED PROPERTY LINE

55'

AD

3 HR FIRE WALL, TYP. @ AREA SEPARATION

69'

AD AD AD

/4" 53

MAX ALLOWABLE AREA PER STORY PER EQUATION 5-2: 24,000 SQ.FT.

3) " (P 8 / 87

THIRD FLOOR: FOURTH FLOOR: FIFTH FLOOR: SIXTH FLOOR: SEVENTH FLOOR: TOTAL:

AREA 2 '162 ) (P2

20

'-

) (F2

52' - 4 1/4" (P8) AD

Aa= { At + [At x If] + [At x Is] Aa= { 24,000 + [24,000 x 0] + [24,000 x 0] Aa= { 24,000 + 0 + 0} Aa= 24,000

/8"

/8"

AD

75

4)

AREA 1

EQUATION 5-1 ALLOWABLE AREA (Aa)

75

'162

" (P 7/8

FIFTH FLOOR AREA PLAN 1" = 50'-0"

" 1/2 - 9 7) ' 10 (P

4,421 SQ.FT. < 24,000 SQ.FT. 4,421 SQ.FT. < 24,000 SQ.FT. 4,421 SQ.FT. < 24,000 SQ.FT. 4,421 SQ.FT. < 24,000 SQ.FT. 4,421 SQ.FT. < 24,000 SQ.FT. 22,105 SQ.FT. < 48,000 SQ.FT. (MAX ALLOWABLE BUILDING AREA)

AREA 3a - CALCULATIONS

-1 78'

AREA 2

0"

ALLOWABLE AREA PER STORY = 24,000 SQFT TOTAL ALLOWABLE BUILDING AREA PER SECTION 506.4.1: 2 x Aa = 48,000 SQFT

AREA 3a - BUILDING AREA MAX ALLOWABLE AREA PER STORY PER EQUATION 5-2: 24,000 SQ.FT.

'29

3 HR FIRE WALL, TYP. @ AREA SEPARATION

6) (P /2" 11

' 16

THIRD FLOOR: FOURTH FLOOR: FIFTH FLOOR: SIXTH FLOOR: SEVENTH FLOOR: TOTAL:

) P5 "( 8 -

65' - 0 3/8" (P9)

AREA 5

AREA 4

6,115 SQ.FT. < 24,000 SQ.FT. 6,115 SQ.FT. < 24,000 SQ.FT. 6,115 SQ.FT. < 24,000 SQ.FT. 6,458 SQ.FT. < 24,000 SQ.FT. 6,445 SQ.FT. < 24,000 SQ.FT. 31,248 SQ.FT. < 48,000 SQ.FT. (MAX ALLOWABLE BUILDING AREA)

AREA 4 - CALCULATIONS EQUATION 5-1 ALLOWABLE AREA (Aa) Aa= { At + [At x If] + [At x Is] Aa= { 24,000 + [24,000 x 0] + [24,000 x 0] Aa= { 24,000 + 0 + 0} Aa= 24,000 ALLOWABLE AREA PER STORY = 24,000 SQFT TOTAL ALLOWABLE BUILDING AREA PER SECTION 506.4.1: 2 x Aa = 48,000 SQFT

AREA 1 AREA 3

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

Aa= { At + [At x If] + [At x Is] Aa= { 24,000 + [24,000 x 0] + [24,000 x 0] Aa= { 24,000 + 0 + 0} Aa= 24,000

LANKERSHIM + otsego

AREA 5

AREA 3a

AREA 4 - BUILDING AREA

ASSUMED PROPERTY LINE 33' - 5 3/8"

AD AD AD

MAX ALLOWABLE AREA PER STORY PER EQUATION 5-2: 24,000 SQ.FT. THIRD FLOOR: FOURTH FLOOR: FIFTH FLOOR: SIXTH FLOOR: SEVENTH FLOOR: TOTAL:

171' - 1 1/2" (F1)

OTSEGO STREET

> 30'

192' - 4 1/4" (P1)

AREA 2

9,314 SQ.FT. < 24,000 SQ.FT. 9,314 SQ.FT. < 24,000 SQ.FT. 9,314 SQ.FT. < 24,000 SQ.FT. 9,314 SQ.FT. < 24,000 SQ.FT. 9,314 SQ.FT. < 24,000 SQ.FT. 46,570 SQ.FT. < 48,000 SQ.FT. (MAX ALLOWABLE BUILDING AREA)

AREA 5 - CALCULATIONS

SIXTH FLOOR AREA PLAN 1" = 50'-0"

THIRD FLOOR AREA PLAN 1/16" = 1'-0"

AREA 1

EQUATION 5-1 ALLOWABLE AREA (Aa) Aa= { At + [At x If] + [At x Is] Aa= { 24,000 + [24,000 x 0] + [24,000 x 0] Aa= { 24,000 + 0 + 0} Aa= 24,000 ALLOWABLE AREA PER STORY = 24,000 SQFT TOTAL ALLOWABLE BUILDING AREA PER SECTION 506.4.1: 2 x Aa = 48,000 SQFT

SPA DECK

DECK

ELEVATOR #4

STAIR #4

REC ROOM

AREA 5

AREA 4

AREA 5

SHEET TITLE

BUILDING AREA FRONTAGE INCREASE CALCULATIONS

AREA 5 - BUILDING AREA MAX ALLOWABLE AREA PER STORY PER EQUATION 5-2: 24,000 SQ.FT. THIRD FLOOR: FOURTH FLOOR: FIFTH FLOOR: SIXTH FLOOR: SEVENTH FLOOR: TOTAL:

AREA 4

6,279 SQ.FT. < 24,000 SQ.FT. 6,279 SQ.FT. < 24,000 SQ.FT. 6,279 SQ.FT. < 24,000 SQ.FT. 6,279 SQ.FT. < 24,000 SQ.FT. 4,024 SQ.FT. < 24,000 SQ.FT. 29,140 SQ.FT. < 48,000 SQ.FT. (MAX ALLOWABLE BUILDING AREA)

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

AREA 3a

AREA 3

STAIR #2

AD AD AD

AREA 3

ELEVATOR #3

AD FITNESS CENTER

AREA 3a

AD AD

N LA R KE

AD

AD AD

AV

COURTYARD

AREA 1

LOUNGE

AREA 2

DOG WASH

SCALE

SPA

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

DECK

FOURTH FLOOR AREA PLAN 1" = 50'-0"

AREA 1

SECOND FLOOR BUILDABLE AREA 1" = 50'-0"

JOB NO. DATE

ELEVATOR #2

STAIR #1

GAME ROOM

POOL

SEVENTH FLOOR AREA PLAN 1" = 50'-0"

E

3/9/2017 2:28:50 PM

U EN

LOUNGE

AREA 2

IM

AD

SH

AD AD AD

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

1501 03-03-2017 As indicated

SHEET NO.

OTSEGO STREET

A072a


TOTAL BUILDABLE AREA (R4-2 + C4-1) PROPOSED:

REC ROOM

DECK

R-2 10,780 SF

R-2 10,463 SF

OLF = 200

OLF = 200

OCC. LOAD = 54

AREA #3

AREA #3

DECK

R-2 3,266 SF OLF = 200

R-2 9,179 SF

OCC. LOAD = 16 OLF = 200

AREA #5

714 SF

OLF = 15

OCC. LOAD = 48

OCC. LOAD = 46

R-2 6,088 SF

R-2 9,179 SF

OLF = 200

OLF = 200

OCC. LOAD = 31

AREA #5

AREA #4

OCC. LOAD = 46

AREA #4

OPEN BALCONY, TYP.

ASSUMED PROPERTY LINE

REC. ROOM AREA #5

725 SF

OLF = 15

OCC. LOAD = 48

= 1,695 SF = 8,759 SF = 10,780 SF = 9,179 SF = 714 SF = 3,266 SF

BUILDABLE AREA

= 34,393 SF

RESIDENTIAL AREA #1 RESIDENTIAL AREA #2 RESIDENTIAL AREA #3 RESIDENTIAL AREA #4 RESIDENTIAL AREA #5 K - BALCONIES L - BALCONIES

LOUNGE AREA #1 RESIDENTIAL AREA #1 = 1,695 SF OCCUPANT LOAD: LOUNGE AREA: 725 SF NET = 48 OCC. GAME ROOM: 683 SF NET = 46 OCC. BATHROOM/LOCKERS = 0 OCC.

3 HR FIRE WALL, TYP. @ AREA SEPARATION 3 HR FIRE WALL, TYP. @ AREA SEPARATION

BUILDABLE AREA

= 13,311 SF = 8,759 SF = 10,463 SF = 9,179 SF = 6,088 SF = 125 SF = 883 SF

AD

ASSUMED PROPERTY LINE

AD

AD

COVERED BALCONY, TYP. 3 HR FIRE WALL, TYP. @ AREA SEPARATION 3 HR FIRE WALL, TYP. @ AREA SEPARATION

= 48,808 SF

3 HR FIRE WALL, TYP. @ AREA SEPARATION

3 HR FIRE WALL, TYP. @ AREA SEPARATION

POOL SPA

R-2 8,759 SF OLF = 200

OCC. LOAD = 44

R-2 8,759 SF OLF = 200

DECK

ASSUMED PROPERTY LINE

OCC. LOAD = 44 ASSUMED PROPERTY LINE

AREA #2

AREA #2

683 SF

OLF = 15

OCC. LOAD = 46

R-2 13,311 SF OLF = 200

FOURTH FLOOR BUILDABLE AREA 1" = 40'-0"

GAME ROOM AREA #1

ASSUMED PROPERTY LINE

ASSUMED PROPERTY LINE

3 HR FIRE WALL, TYP. @ AREA SEPARATION

3 HR FIRE WALL, TYP. @ AREA SEPARATION

OCC. LOAD = 67

AREA #1

R-2

485 SF

OLF = 15

OCC. LOAD = 33

= 13,691 SF = 8,759 SF = 10,463 SF = 9,179 SF = 6,088 SF = 144 SF = 834 SF = 49,158 SF

FOURTH FLOOR: RESIDENTIAL AREA #1 RESIDENTIAL AREA #2 RESIDENTIAL AREA #3 RESIDENTIAL AREA #4 AREA #5 KLUMP BALCONIES LANKERSHIM BALCONIES TOTAL

= 13,311 SF = 8,759 SF = 10,463 SF = 9,179 SF = 6,088 SF = 125 SF = 883 SF = 48,808 SF

FIFTH FLOOR: RESIDENTIAL AREA 1 RESIDENTIAL AREA 2 RESIDENTIAL AREA 3 RESIDENTIAL AREA 4 RESIDENTIAL AREA 5 KLUMP BALCONIES LANKERSHIM BALCONIES TOTAL

= 13,340 SF = 8,743 SF = 10,463 SF = 9,179 SF = 6,088 SF = 140 SF = 852 SF = 48,805 SF

SIXTH FLOOR: RESIDENTIAL AREA 1 RESIDENTIAL AREA 2 RESIDENTIAL AREA 3 RESIDENTIAL AREA 4 RESIDENTIAL AREA 5 KLUMP BALCONIES LANKERSHIM BALCONIES TOTAL

= 13,335 SF = 8,759 SF = 10,799 SF = 9,179 SF = 6,088 SF = 146 SF = 878 SF = 49,184 SF

SEVENTH FLOOR: RESIDENTIAL AREA 1 RESIDENTIAL AREA 2 RESIDENTIAL AREA 3 RESIDENTIAL AREA 4 RESIDENTIAL AREA 5 TOTAL

= 1,695 SF = 8,759 SF = 10,780 SF = 9,179 SF = 3,980 SF = 34,393 SF

STAMP

ED A RCH NS S EMP I A TA NO. C-13779

R-2 10,463 SF

OLF = 200

OLF = 200

OCC. LOAD = 54

ELEVATOR #4

R-2 10,799 SF

= 308,168 SF

ALLOWABLE SF

= 323,296.87 SF

KLUMP LOBBY

OCC. LOAD = 53 BICYCLE ROOM STAIR #3A

R-2 1,495 SF OLF = 15

OCC. LOAD = 100

LOBBY #2 BICYCLE ROOM

OLF = 200

AREA #4

OPEN BALCONY, TYP.

OCC. LOAD = 31

OLF = 200

AREA #5

MAIL

4 D# AR TY R U CO

OCC. LOAD = 46

AREA #4

R2

241 SF

OLF = 15

OCC. LOAD = 16

ELECTRICAL

GROUND FLOOR

FAN ROOM

FUTURE MARKET LOBBY #1 MEZZANINE LOBBY #2 LOBBY #3

COURTYARD #4

ASSUMED PROPERTY LINE

ASSUMED PROPERTY LINE

THIRD FLOOR

SIXTH FLOOR

UP

= 25,261 SF = 1,320 SF = 656 SF = 1,495 SF = 485 SF

RES. TRASH #2

AREA #5

OCC. LOAD = 46

R-2 9,179 SF

ELEVATOR #3

OLF = 200

R-2 6,088 SF

STAIR #2

OCC. LOAD = 31

N AN LANKERSHIM MAIN LOBBY

OX KN X BO

UP DN

AD

COVERED BALCONY, TYP. 3 HR FIRE WALL, TYP. @ AREA SEPARATION 3 HR FIRE WALL, TYP. @ AREA SEPARATION

ASSUMED PROPERTY LINE

BUILDABLE AREA

OPEN BALCONY, TYP.

AD

= 29,217 SF

AD

AD

COVERED BALCONY, TYP. 3 HR FIRE WALL, TYP. @ AREA SEPARATION 3 HR FIRE WALL, TYP. @ AREA SEPARATION

= 49,158 SF

BUILDABLE AREA

= 49,184 SF

= 13,691 SF = 8,759 SF = 10,463 SF = 9,179 SF = 6,088 SF = 144 SF = 834 SF

3 HR FIRE WALL, TYP. @ AREA SEPARATION

R-2

656 SF

OLF = 100

OCC. LOAD = 14

RESIDENTIAL TRASH #1

MEZZANINE

3 HR FIRE WALL, TYP. @ AREA SEPARATION

345 SF (ALLOWABLE 660 SF) TYPE I MEZZANINE: 50% OPEN SPACE OF LOBBY #1 (1320 SF)

ELEVATOR #1

AD AD

R-2 8,759 SF OLF = 200

R-2 8,759 SF

OCC. LOAD = 44

OLF = 200

OCC. LOAD = 44

ASSUMED PROPERTY LINE

AREA #2

SIXTH FLOOR BUILDABLE AREA 1" = 40'-0"

R-2 1,320 SF

AREA #2

OLF = 15

ASSUMED PROPERTY LINE

R-2 13,691 SF

OLF = 200

OLF = 200

THIRD FLOOR BUILDABLE AREA 1" = 40'-0"

AREA #1

OCC. LOAD = 69

287 SF

OLF = 15

OCC. LOAD = 19

MAIL

LOBBY #2

FAN ROOM

OCC. LOAD = 88

GROUND FLOOR BUILDABLE AREA 1" = 40'-0"

AREA #1

R-2

ELECTRICAL

FUTURE MARKET

LOBBY #1

R-2 13,335 SF OCC. LOAD = 67

ELECTRICAL RM.

AD

ELEVATOR #2

ASSUMED PROPERTY LINE

RESIDENTIAL AREA #1 RESIDENTIAL AREA #2 RESIDENTIAL AREA #3 RESIDENTIAL AREA #4 RESIDENTIAL AREA #5 K - BALCONIES L - BALCONIES

AD

ELEVATOR #2

AD

STAIR #1

BUILDABLE AREA

= 13,335 SF = 8,759 SF = 10,799 SF = 9,179 SF = 6,088 SF = 146 SF = 878 SF

STAIR #1

RESIDENTIAL AREA #1 RESIDENTIAL AREA #2 RESIDENTIAL AREA #3 RESIDENTIAL AREA #4 RESIDENTIAL AREA #5 K - BALCONIES L - BALCONIES

CA L I F

STAIR #3B

ELECTRICAL

OLF = 200

OF

BICYCLE ROOM

AREA #3

AREA #3

R-2 9,179 SF

E

O

LOBBY #3

STAIR #4

R-2 6,088 SF

REN. 6-30-17

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

GRAND TOTAL

RES. TRASH #3

SEVENTH FLOOR BUILDABLE AREA 1" = 40'-0"

R-2

FOR OCCUPANCY CALCS @ POOL DECKS, SEE 1 / A632

THIRD FLOOR: RESIDENTIAL AREA #1 RESIDENTIAL AREA #2 RESIDENTIAL AREA #3 RESIDENTIAL AREA #4 RESIDENTIAL AREA #5 KLUMP BALCONIES LANKERSHIM BALCONIES TOTAL

T

RESIDENTIAL AREA #1 RESIDENTIAL AREA #2 RESIDENTIAL AREA #3 RESIDENTIAL AREA #4 REC. ROOM AREA #5 RESIDENTIAL AREA #5

FOURTH FLOOR

= 12,354 SF = 13,151 SF = 6,181 SF = 14,944 SF = 167 SF = 1,806 SF = 48,603 SF

ST A

R-2 ASSUMED PROPERTY LINE

SEVENTH FLOOR

ASSUMED PROPERTY LINE

SECOND FLOOR: RESIDENTIAL AREA #1 RESIDENTIAL AREA #2 RESIDENTIAL AREA #3 RESIDENTIAL AREA #4 KLUMP BALCONIES LANKERSHIM BALCONIES TOTAL

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

CT TE ERIS K

R-2

OCC. LOAD = 53

DE Architects AIA

A

SPA

= 25,261 SF = 1,320 SF = 656 SF = 1,495 SF = 485 SF = 29,217 SF

NI

GROUND FLOOR FUTURE MARKET LOBBY #1 MEZZANINE LOBBY #2 LOBBY #3 TOTAL

R

3 HR FIRE WALL, TYP. @ AREA SEPARATION

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

3 HR FIRE WALL, TYP. @ AREA SEPARATION

L IC E DONA

FOR OCCUPANCY CALCS @ SPA DECK, SEE 2 / A634

ALLOWABLE BUILDABLE AREA (R4-2 + C4-1) = 323,296.87 SF

ASSUMED PROPERTY LINE

LANKERSHIM + otsego

ASSUMED PROPERTY LINE

M

7,443 SF

OLF = 300

OCC. LOAD = 25

FUTURE MARKET STORAGE/STOCK/SHIPPING

M 17,822 SF OLF = 30

OCC. LOAD = 594

FUTURE MARKET GRADE FLOOR AREA

ASSUMED PROPERTY LINE

COURTYARD #4

3 HR FIRE WALL, TYP. @ AREA SEPARATION

R-2 1,470 SF OLF = 50

OLF = 200

OUTDOOR FITNESS

COURTYARD #3

R-2 10,463 SF

OCC. LOAD = 30

R-2 2,829 SF

OCC. LOAD = 53

OLF = 50

AREA #3

OCC. LOAD = 57

FITNESS CENTER AREA #2

OUTDOOR FITNESS

OPEN BALCONY, TYP.

R-2 6,088 SF OCC. LOAD = 31

OLF = 200

AREA #5

R-2 14,944 SF

COVERED BALCONY, TYP.

OCC. LOAD = 46

OLF = 200

OCC. LOAD = 75

AD

R-2 3,154 SF OLF = 15

AD

FIFTH FLOOR

BUILDABLE AREA

AD

= 13,340 SF = 8,743 SF = 10,463 SF = 9,179 SF = 6,088 SF = 140 SF = 852 SF

AD

ASSUMED PROPERTY LINE

OPEN BALCONY, TYP. AD

SECOND FLOOR

AD

COVERED BALCONY, TYP. 3 HR FIRE WALL, TYP. @ AREA SEPARATION 3 HR FIRE WALL, TYP. @ AREA SEPARATION

= 48,805 SF 3 HR FIRE WALL, TYP. @ AREA SEPARATION

RESIDENTIAL AREA #1 LOUNGE AREA #1 BUSINESS CENTER AREA #1 DOG WASH AREA #1 RESIDENTIAL AREA #2 FITNESS CENTER AREA #2 RESIDENTIAL AREA #3 RESIDENTIAL AREA #4 K - BALCONIES L - BALCONIES

#2 RD YA AD T UR CO AD

AD

= 10,541 SF = 1,305 SF = 233 SF = 275 SF = 11,474 SF = 2,829 SF = 5,029 SF = 14,944 SF = 167 SF = 1,806 SF

LOUNGE

OCC. LOAD = 44

AREA #2

= 48,603 SF

3/9/2017 2:30:02 PM

OLF = 200

R-2 13,340 SF FIFTH FLOOR BUILDABLE AREA 1" = 40'-0"

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

OLF = 200

OCC. LOAD = 67

AREA #1

R-2

290 SF

OLF = 15

OCC. LOAD = 19

OCC. LOAD = 87

LOUNGE AREA #1

R-2

233 SF

OLF = 100

OCC. LOAD = 2

BUSINESS CENTER AREA #1

OCC. LOAD = 57

AREA #2

SECOND FLOOR BUILDABLE AREA 1" = 40'-0"

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

COURTYARD #2

R-2 1,305 SF BUSINESS

R-2 11,474 SF

ASSUMED PROPERTY LINE

COURTYARD #1

OLF = 15

R-2 8,743 SF OLF = 200

OCC. LOAD = 210

COURTYARD #1

DOG WASH

BUILDABLE AREA

OCC. LOAD = 25

AREA #3

ASSUMED PROPERTY LINE

RESIDENTIAL AREA #1 RESIDENTIAL AREA #2 RESIDENTIAL AREA #3 RESIDENTIAL AREA #4 RESIDENTIAL AREA #5 K - BALCONIES L - BALCONIES

ALLOWABLE AREA CALCS

AD

FITNESS CENTER

AREA #4

AREA #4

OLF = 200

AD

AD

OLF = 200

R-2 9,179 SF

SHEET TITLE

R-2 5,029 SF

R-2 10,541 SF OLF = 200

OCC. LOAD = 53

AREA #1

R-2

275 SF

OLF = 100

OCC. LOAD = 3

DOG WASH AREA #1

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO. DATE SCALE

1501 03-03-2017 As indicated

SHEET NO.

A073


LEGEND

F.E.C.

FIRE EXTINGUISHER CABINET SEMI-RECESSED (MAX 75' TRAVEL DISTANCE FROM ANY PORTION OF BUILDING) 2013 CBC SEC. 906 SEE DETAILS A900 SERIES WALL MOUNTED DIRECTIONAL EXIT SIGNAGE NO POINT SHALL BE MORE THAN 100 FEET FROM THE NEARES VISIBLE SIGN (1011)

DE Architects AIA 1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

PER CBC 2013 TABLE 1016.1 EXIT TRAVEL DISTANCE FOR SPRINKLERED BUILDING SHALL NOT EXCEED: 250' FOR R2-OCCUPANCY & M-OCCUPANCY 400' FOR S2-OCCUPANCY

EXIT TRAVEL DISTANCE 82'-6"

236' - 3 7/ 8"

EXIT TRAVEL DISTANCE 166'-10"

STAIR #4 ELEVATOR #4

STAIR #4 ELEVATOR #4

REC ROOM

FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED ON ADDRESS SIDE OF BUILDING (L.A.M.C. 57.138)

STAIR #3B

STAIR #3B

BUILDING ADDRESS SHALL BE PROVIDED AT OR NEAR ENTRANCE OF THE BUILDING IN ACCORDANCE TO L.A.M.C. 57.09.101

FD WET STANDPIPE

ED A RCH NS S EMP I A TA

CT TE ERIS K

FD WET STANDPIPE

STAMP

DECK

ST A

FD WET STANDPIPE

REN. 6-30-17

EXIT TRAVEL DISTANCE 177'-1"

1/ 3 6"

FD WET STANDPIPE

DI AG

O NA L

EXIT TRAVEL DISTANCE 153'-1"

FD WET STANDPIPE

1/ 3

32 6' -

3" DI ST AN CE

FD WET STANDPIPE =

10 8'9"

FD WET STANDPIPE

FD WET STANDPIPE

EXIT TRAVEL DISTANCE 133'-11"

ON AL

32 6' DI -1 ST AN 1" CE = 10

8'10

11 /1 6"

FD WET STANDPIPE

EXIT TRAVEL DISTANCE 133'-11"

STAIR #5

STAIR #5

EXIT TRAVEL DISTANCE 116'-9"

153' - 2

1/8"

2 1/2"

EXIT TRAVEL DISTANCE 116'-9"

EXIT TRAVEL DISTANCE 248'-3"

153' -

FD WET STANDPIPE EXIT TRAVEL DISTANCE 74'-9"

-

EXIT TRAVEL DISTANCE 153'-0"

FD WET STANDPIPE EXIT TRAVEL DISTANCE 217'-2"

?

EXIT TRAVEL DISTANCE 169'-9"

STAIR #1

ELEVATOR #2

FD WET STANDPIPE

ELEVATOR #2

FD WET STANDPIPE

STAIR #1

DI AG

EXIT TRAVEL DISTANCE 230'-3"

DECK

COMMON PATH OF EGRESS 64'-2"

EXIT TRAVEL DISTANCE 148'-4"

COMMON PATH OF EGRESS 64'-2"

EXIT TRAVEL DISTANCE 237'-9"

EXIT TRAVEL DISTANCE - SEVENTH FLOOR 1" = 30'-0"

EXIT TRAVEL DISTANCE - THIRD THRU FIFTH FLOOR 1" = 30'-0"

236' - 3 7/ 8"

EXIT TRAVEL DISTANCE 166'-10"

STAIR #4

ELEVATOR #4

ELEVATOR #4

STAIR #4

STAIR #3B

236' - 1 3/ 8"

EXIT TRAVEL DISTANCE 166'-10"

FD WET STANDPIPE

COURTYARD #4

FD WET STANDPIPE

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

15/1

LANKERSHIM + otsego

78'3

O

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

ELEVATOR #3

1/8" ONA L DI STA NCE =

CA L I F

EXIT TRAVEL DISTANCE 177'-1"

STAIR #2

EXIT TRAVEL DISTANCE 77'-9"

235 '-0

ELEVATOR #3

DIA G

STAIR #2

1/3

272' 1/3 D - 3" IAGO NAL DIST ANC E=9 0'-9"

OF

R

T

E

A

NO. C-13779

FD WET STANDPIPE

NI

DECK

FD WET STANDPIPE

236' - 6 1/ 4"

EXIT TRAVEL DISTANCE 166'-10"

L IC E DONA

FD WET STANDPIPE

FD WET STANDPIPE

STAIR #3B

FD WET STANDPIPE

FD WET STANDPIPE

EXIT TRAVEL DISTANCE 177'-1"

RAMP DN 1/3 D IAGO NAL

0'-9 1/8"

ELEVATOR #3

FD WET STANDPIPE

STAIR #2

1/ 3

DI AG O NA L

-31 /8" DIST ANC E=8 7' - 5

1/16 "

32

9' -9 DI 3/ ST 4" AN CE = 10

9' -1 1

COURTYARD #3

262'

FITNESS CENTER (YOGA STUDIO)

FITNESS CENTER

EXIT TRAVEL DISTANCE 82'-7"

1/ 4"

FD WET STANDPIPE FD WET STANDPIPE

ELEVATOR #3

-33 /8" AL D ISTA NCE =9

STAIR #2

272'

EXIT TRAVEL DISTANCE 177'-1"

STAIR #7

1/3 D IAGO N

FD WET STANDPIPE

FD WET STANDPIPE FD WET STANDPIPE

SHEET TITLE

FD WET STANDPIPE

EXIT TRAVEL DISTANCE 133'-11"

EXIT TRAVEL DISTANCE PLANS

EXIT TRAVEL DISTANCE 136'-8"

STAIR #5

COURTYARD #1

154' -

2 1/2"

4 5/8"

EXIT TRAVEL DISTANCE 116'-9"

EXIT TRAVEL DISTANCE 225'-8"

153' -

#5 AIR ST

EXIT TRAVEL DISTANCE 119'-7"

EXIT TRAVEL DISTANCE 239'-9"

FD WET STANDPIPE EXIT TRAVEL DISTANCE 217'-2"

ELEVATOR #2

STAIR #1

ELEVATOR #2

STAIR #1

FD WET STANDPIPE

FD WET STANDPIPE EXIT TRAVEL DISTANCE 225'-3"

FD WET STANDPIPE

EXIT TRAVEL DISTANCE 231'-0"

DOG WASH

EXIT TRAVEL DISTANCE 222'-8"

COMMON PATH OF EGRESS 53'-11"

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO.

3/9/2017 2:31:33 PM

DATE

EXIT TRAVEL DISTANCE - SIXTH FLOOR 1" = 30'-0"

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

LOUNGE

FD WET STANDPIPE

COMMON PATH OF EGRESS 64'-2"

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

EXIT TRAVEL DISTANCE 236'-3"

EXIT TRAVEL DISTANCE - SECOND FLOOR 1" = 30'-0"

SCALE

1501 03-03-2017 As indicated

SHEET NO.

A079


DOOR SCHEDULE HRD

DOOR TYPES

DWELLING UNITS A

20 MIN.

WOOD S.C.

U2

3' - 0"

7' - 0"

0' - 1 3/8"

B

-

U3

2' - 10"

6' - 8"

0' - 1 3/8"

A

-

H.M./ GLASS WOOD H.C.

U4

2' - 10"

6' - 8"

0' - 1 3/8"

A

-

WOOD H.C.

U5

5' - 0"

6' - 8"

0' - 1 3/8"

C

-

WOOD H.C.

U6

2' - 0"

6' - 8"

0' - 1 3/8"

A

-

WOOD H.C.

U7

2' - 10"

6' - 8"

0' - 1 3/8"

A

-

WOOD H.C.

U8

8' - 0"

6' - 8"

0' - 1 3/8"

D

-

WOOD H.C.

U9

8' - 0"

6' - 8"

0' - 1 3/8"

D

-

WOOD H.C.

U10

4' - 0"

6' - 8"

0' - 1 3/8"

C

-

WOOD H.C.

U11

2' - 10"

6' - 8"

0' - 1 3/8"

A

-

WOOD H.C.

U12

5' - 0"

6' - 8"

0' - 1 3/8"

D

-

WOOD H.C.

U13

6' - 0"

6' - 8"

0' - 1 3/8"

D

-

WOOD H.C.

U14

2' - 6"

6' - 8"

0' - 1 3/8"

A

-

WOOD H.C.

U15

2' - 10"

6' - 8"

0' - 1 3/8"

A

-

WOOD H.C.

U16

3' - 0"

6' - 8"

0' - 1 3/8"

A

-

WOOD H.C.

U17

3' - 0"

6' - 8"

0' - 1 3/8"

M

-

WOOD H.C.

U18

5' - 0"

6' - 8"

0' - 1 3/8"

Q

-

WOOD H.C.

H.M. WOOD WOOD WOOD WOOD WOOD WOOD WOOD WOOD WOOD WOOD WOOD WOOD WOOD WOOD WOOD WOOD

7, 19 /A906

8, 20 /A906

6/A906

9/A906

11,12,13,14 /A906 12,14 /A906

1/A906

2/A906

-

UNIT BEDROOM DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

1/A906

2/A906

-

UNIT BATHROOM DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE. PROVIDE SCHLUTER TRANSITION

1/A906

2/A906

-

UNIT CLOSET DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

1/A906

2/A906

-

UNIT CLOSET DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

1/A906

2/A906

-

UNIT CLOSET DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

3/A906

-

-

UNIT CLOSET SLIDING DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

3/A906

-

-

UNIT CLOSET SLIDING DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

1/A906

2/A906

-

UNIT CLOSET DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

1/A906

2/A906

-

UNIT CLOSET DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

3/A906

-

-

UNIT CLOSET SLIDING DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

3/A906

-

-

UNIT ENTRY DOOR, SINGLE FLUSH, SELF CLOSING HINGES, SMOKE DRAFT GASKET, KEY FOB

TEMPERED TEMPERED

TEMPERED, TYP.

DE Architects AIA

UNIT BALCONY, EXTERIOR GLASS DOOR

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

A

SMOOTH SURFACE

B

C

D

E

SMOOTH SURFACE

F STAMP

UNIT CLOSET SLIDING DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

1/A906

2/A906

-

UNIT CLOSET DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

1/A906

2/A906

-

UNIT LAUNDRY CLOSET DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

3' - 0"

*REF. 27/A902 FOR TYPICAL FENCE

*REF.27/902 FOR TYPICAL FENCE

V.I.F.

1" x 2 1/4" FLAT STEEL BAR

ED A RCH NS S EMP I A TA

6' - 0" V.I.F.

NO. C-13779

1" x 2 1/4" FLAT STEEL BAR

1/2" x 1 1/2" FLAT STEEL BAR, TYP 1/2" x 1 1/2" FLAT STEEL BAR, TYP

1/A906

2/A906

-

UNIT LAUNDRY CLOSET DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

1/A906

2/A906

-

UNIT CLOSET DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

33/A906

34/A906

-

UNIT LAUNDRY CLOSET BI-FOLD LOUVERED DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

SOLID 18 ga MTL BACKING 3" X 3" STEEL TUBE, TYP.

KICK PLATE ANCHOR TO WALL TYP

10"

0' - 1 3/4"

6' - 0" U.N.O.

8' - 0"

10"

3' - 0"

HEIGHT PER SCHEDULE

U1

REN. 6-30-17

E

OF

A

SEMI GLOSS STAND. COLOR SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS

REMARKS

NI

H.M.

THRESHOLD DETAIL

R

SEMI GLOSS STAND. COLOR SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS

HEAD DETAIL JAMB DETAIL

L IC E DONA

FRAME FINISH

CA L I F

O

SOLID 18 ga MTL BACKING 3" X 3" STEEL TUBE, TYP.

12"

FRAME MATERIAL

KICK PLATE 10"

DOOR FINISH

8' - 0" U.N.O.

DOOR MATERIAL

12"

FIRE RATING

CT TE ERIS K

TYPE

T

THICK.

ST A

HEIGHT

10"

WIDTH

TYP.

DOOR NO.

ANCHOR TO WALL TYP.

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

COMMON SPACES

3' - 0"

8' - 0"

0' - 1 3/4"

A

-

WOOD S.C.

CS4

6' - 0"

8' - 0"

0' - 1 3/4"

C

-

WOOD S.C.

CS5

6' - 0"

8' - 0"

0' - 1 3/4"

C

20 MIN.

H.M.

CS6

3' - 0"

8' - 0"

0' - 1 3/4"

A

-

H.M.

CS7

3' - 0"

8' - 0"

0' - 1 3/4"

A

-

WOOD S.C.

CS8

14' - 0"

8' - 0"

0' - 2"

F

-

CS9

3' - 0"

8' - 0"

0' - 1 3/4"

B

-

CS10

3' - 0"

8' - 0"

0' - 1 3/4"

A

20 MIN.

H.M./ GLASS H.M./ GLASS WOOD S.C.

CS11

3' - 0"

6' - 8"

0' - 1 3/4"

A

-

WOOD H.C.

CS12

3' - 0"

6' - 8"

0' - 1 3/4"

A

-

WOOD H.C.

CS13

3' - 0"

8' - 0"

0' - 1 3/4"

A

-

WOOD H.C.

CS14

3' - 0"

7' - 9 1/2"

0' - 2"

B

-

ALUM.

CS15

3' - 0"

8' - 0"

0' - 2"

B

-

GLASS

CS16

3' - 0"

8' - 0"

0' - 2"

B

-

GLASS

CS17

3' - 0"

7' - 9 1/2"

0' - 2"

B

-

ALUM.

CS18

3' - 0"

8' - 0"

0' - 1 3/4"

B

-

GLASS

CS19

3' - 0"

8' - 0"

0' - 1 3/4"

A

20 MIN.

H.M.

CS20

3' - 0"

8' - 0"

0' - 1 3/4"

A

20 MIN.

H.M.

CS21

3' - 0"

8' - 0"

0' - 1 3/4"

A

20 MIN.

H.M.

ALUM. ALUM.

ALUM.

1/A907

2/A907

32 /A906

H.M.

SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS ALUM.

7/A906

8/A906

11,12 /A906

4/A906

5/A904

-

REC. ROOM - BATHROOM DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

4/A906

5/A904

-

REC. ROOM - STORAGE DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

4/A906

5/A904

-

REC. ROOM - INTERIOR DOOR, HOLLOW CORE MOLDED HARDBOARD DOOR, MASONITE

1/A907

2/A907

1/A907

FITNESS ROOM - PROVIDE CLOSER, PANIC HARDWARE

MTL MTL H.M. H.M. MTL

MTL MTL MTL ALUM. H.M.

19/A906

20/A906

13,14 /A906

30/A906

31/A906

13/A906

FITNESS ROOM - RESTROOM DOOR

30/A906

31/A906

13/A906

YOGA - STORAGE DOOR

19/A906

20/A906

13/A906

FITNESS ROOM - ENTRY DOOR - PROVIDE CLOSER, SMOKE DRAFT GASKET, KEY FOB

7, 19 /A906

8, 20 /A906

13, 32 /A906

4/A906

5/A904

-

LOUNGE TO GAME ROOM INTERIOR DOOR

10/A906

10/A906 SIM

29/A906

LOUNGE EXTERIOR GLASS FOLDING DOOR LOUNGE EXTERIOR GLASS DOOR - PROVIDE CLOSER, KEY FOB

FITNESS ROOM - PROVIDE PANIC HARDWARE, CLOSER, SMOKE DRAFT GASKET, KEY FOB

G

COMMON SPACE - RESTROOM DOOR

REC. ROOM - ENTRY DOOR - SOLID CORE DOOR, PROVIDE CLOSER, SMOKE DRAFT GASKET, KEY FOB

6/A906

9/A906

14/A906

LOUNGE - PROVIDE PANIC HARDWARE, CLOSER

ALUM.

SEMI GLOSS ALUM.

1/A907

2/A907

1/A907

MANAGEMENT OFFICE - GLASS DOOR

ALUM.

ALUM.

1/A907

2/A907

-

YOGA ROOM

H.M.

SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS

7/A906

8/A906

32 /A906

GAME ROOM

7/A906

8/A906

13/A906

LOUNGE - PROVIDE PANIC HARDWARE, CLOSER, SMOKE DRAFT GASKET

7/A906

8/A906

7/A906

8/A906

EQ

H.M. H.M. H.M.

H

EQ

EQ

APARTMENT ENTRY DOORS AND FRAMES - PRE-ASSEMBLED SOLID CORE ENTRY DOORS WITH SPLIT-JAMB METAL FRAMES FOR ALL EXTERIOR APARTMENT ENTRIES. DOOR MANUFACTURER - JELD-WEN-CONTINENTAL DOOR OR APPROVED EQUAL. - COMMERCIAL GRADE HOLLOW METAL DOORS AND FRAMES COMPLYING WITH SDI-100 STANDARDS SHALL BE USED FOR INTERIOR AND EXTERIOR COMMON USE DOORS RECEIVING HEAVY USE, SUCH AS STAIRS, MAINTENANCE AND STORAGE AREAS. LEVEL 2 DOORS AND FRAMES FOR EXTERIOR LOCATIONS AND LEVEL 1 DOORS AND FRAMES FOR INTERIOR LOCATIONS. INSULATED DOORS FOR EXTERIOR LOCATIONS. HOLLOW METAL DOOR FACES ARE REQUIRED FOR EXTERIOR DOORS NOT PROTECTED BY AN OVERHANG. - ALL APARTMENT ENTRY DOORS (FRONT, REAR, PATIO AND BALCONY) AND COMMON AREA DOORS SHOULD BE 3'-0" WIDE.

EQ

EQ

M

WOOD DOORS AND FRAMES - PRE-ASSEMBLED HOLOW-CORE MOLDED HARDBOARD DOORS AND SPLIT-JAMB WOOD FRAMES FOR ALL APARTMENT INTERIOR DOORS. 6-PANEL, WOOD GRAIN, WITH COLONIAL CASING. ACCEPTABLE APARTMENT INTERIOR DOOR MANUFACTURERS ARE MASONITE, CRAFTMASTER AND JELD-WEN. - UREA-FORMALDEHYDE-FREE DOOS AND FRAMES, INCLUDING DOOR CORE AND ADHESIVES. DOOR FACING SHOULD NOT BE LUAN OR OTHER ENDANGERED WOOD SPECIES.

-

GLASS

G3

6' - 0"

9' - 9"

0' - 2"

E

-

GLASS

G4

3' - 0"

8' - 0"

0' - 1 3/4"

A

45 MIN.

H.M.

G5

8' - 0"

7' - 0"

0' - 1 3/4"

G

90 MIN.

STEEL

G6

3' - 0"

8' - 0"

0' - 1 3/4"

A

90 MIN.

H.M.

G7

3' - 0"

8' - 0"

0' - 1 3/4"

A

20 MIN.

H.M.

G8

3' - 0"

7' - 0"

0' - 1 3/4"

A

45 MIN.

H.M.

G9

3' - 0"

7' - 0"

0' - 1 3/4"

A

90 MIN.

H.M.

G10

3' - 0"

8' - 0"

0' - 1 3/4"

A

90 MIN.

H.M.

G11

6' - 0"

8' - 0"

0' - 1 3/4"

C

180 MIN.

H.M.

G12

6' - 0"

8' - 0"

0' - 1 3/4"

C

20 MIN.

H.M.

G13

3' - 0"

7' - 0"

0' - 1 3/4"

A

-

H.M.

G14

2' - 10"

7' - 0"

0' - 1 3/4"

A

20 MIN.

H.M.

3' - 0"

8' - 0"

0' - 1 3/4"

A

180 MIN.

H.M.

G16

3' - 0"

8' - 0"

0' - 1 3/4"

A

20 MIN.

H.M.

G17

3' - 0"

7' - 0"

0' - 1 3/4"

A

-

H.M.

G18

3' - 0"

7' - 0"

0' - 1 3/8"

A

-

H.M.

G19

8' - 0"

8' - 0"

0' - 1 3/4"

D

180 MIN.

H.M.

3' - 0"

7' - 0"

0' - 1 3/4"

A

-

H.M.

G21

8' - 0"

8' - 0"

0' - 1 3/4"

D

-

H.M.

G22

3' - 0"

8' - 0"

0' - 1 3/4"

A

-

H.M.

G23

3' - 0"

7' - 0"

0' - 1 3/4"

A

90 MIN.

H.M.

G24

3' - 0"

8' - 0"

0' - 1 3/4"

A

45 MIN.

H.M.

LANKERSHIM LOBBY #2 ENTRY - PROVIDE CLOSER, KEY FOB

ALUM.

ALUM.

1/A907

2/A907

1/A907

KLUMP MAIN LOBBY ENTRY - PROVIDE CLOSER, KEY FOB

ALUM.

ALUM.

1/A907

2/A907

1/A907

LANKERSHIM MAIN LOBBY ENTRY - PROVIDE CLOSER, KEY FOB

H.M.

SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS

17/A906

17/A906 SIM

13/A906

LANKERSHIM MAIN LOBBY ENTRY (GARAGE SIDE) - PROVIDE CLOSER, SMOKE DRAFT GASKET, KEY FOB

21/A906

22/A906

-

STEEL H.M. H.M. H.M. H.M. H.M. H.M. H.M. H.M. H.M. H.M. H.M. H.M. H.M. H.M. H.M. H.M. H.M. H.M. H.M.

V.I.F.

3" X 3" STEEL TUBE

3" X 3" STEEL TUBE, TYP.

- WHERE BI-FOLD OR BI-PASS ARE LOCATED IMMEDIATELY ADJACENT TO SWING DOORS, UNDERCUT BI-FOLD/BI-PASS DOORS SO THAT CASING TRIM CONCEALING TRACK WILL ALIGN WITH ADJACENT SWING DOOR CASING. - PROVIDE MDF JAMBS AT BI-PASS DOORS.

17/A906

17/A906 SIM

13,14 /A906

17/A906

17/A906 SIM

14/A906

BICYCLE ROOMS - PROVIDE CLOSER, SMOKE DRAFT GASKET

17/A906

17/A906 SIM

13/A906

KLUMP MAIN LOBBY ENTRY (GARAGE SIDE) - PROVIDE CLOSER, SMOKE DRAFT GASKET, KEY FOB

17/A906

17/A906 SIM

13/A906

RESIDENTIAL TRASH ROOM #3 - PROVIDE CLOSER, SMOKE DRAFT GASKET

7/A906

8/A906

11,13 /A906

7, 19 /A906

8, 20 /A906

7/A906

8/A906

6/A906

9/A906

-

6/A906

9/A906

13/A906

ANCHOR TO WALL, TYP.

RESIDENTIAL TRASH ROOMS - ROLL UP DOOR RESIDENTIAL TRASH ROOM #2 - PROVIDE CLOSER, SMOKE DRAFT GASKET

- ACCESS DOORS - PROVIDE FLUSH, LOCKABLE ACCESS DOORS FOR PUBLIC AND COMMON AREAS. ALL ACCESS DOORS FOR PROJECT SHOULD BE KEYED TO THE SAME MASTER KEY.

CORRUGATED MTL. INFILL

O

P

- PROVIDE INSULATED GLAZING FOR STOREFRONTS, SIDELIGHTS AND TRANSOMS. PROVIDE SINGLE GLAZING FOR ENTRANCE DOORS.

TRASH CHUTE ROOM - SELF CLOSING HINGES. PROVIDE CLOSER, SMOKE DRAFT GASKET

- ENTRANCE DOOR STILE AND HEAD RAIL DIMENSIONS AND FRAME DIMENSIONS SHALL BE COORDINATED WITH SPECIFIED HARDWARE, SUCH AS EXIT DEVICES, LOCKSETS, ELECTRIC STRIKES AND CLOSERS TO ENSURE ADEQUATE CLEARANCE FOR MOUNTING HARDWARE.

11,12,13 /A906 FIRE DOOR - HOLD OPEN DEVICE DOOR, PROVIDE PANIC HARDWARE, SMOKE DRAFT GASKET - PROVIDE ELECT. POWER 11,13 /A906 L.V. CLOSET

SAFETY GLAZING NOTES: PROVIDE SAFETY GLAZING AS REQUIRED PER 2013 CBC SECTION 2406. a.GLAZING IN INGRESS AND EGRESS DOORS

ELEVATOR EQUIPMENT ROOM AT ROOF ENCLOSED PLANTER SERVICE DOOR, PROVIDE CLOSER

8' - 0"

0' - 2"

E

-

GLASS

M2

3' - 0"

8' - 0"

0' - 2"

B

-

GLASS

M3

3' - 0"

8' - 0"

0' - 2"

B

-

GLASS

M4

6' - 0"

8' - 0"

0' - 1 3/4"

C

45 MIN.

H.M.

M5

3' - 0"

8' - 0"

0' - 1 3/4"

A

-

H.M.

0' - 8"

P

-

GLASS

19' - 1 1/2" 10' - 9 1/2"

M7

10' - 0"

14' - 0"

0' - 1 3/4"

G

M8

4' - 0"

8' - 0"

0' - 2"

A

STEEL 45 MIN.

H.M.

GLASS CLR. GLASS CLR. GLASS CLR. SEMI GLOSS SEMI GLOSS GLASS CLR.

SEMI GLOSS SEMI GLOSS

7, 19 /A906

8, 20 /A906

11,12,13 /A906 FIRE DOOR - HOLD OPEN DEVICE DOOR, PROVIDE SMOKE DRAFT GASKET - PROVIDE ELECT. POWER

6/A906

9/A906

11,12 /A906

17/A906

17/A906 SIM

13/A906

GARAGE ENTRY - BUILDING 1

19/A906

20/A906

13/A906

COLD STORAGE - LANKERSHIM MAIN LOBBY

19/A906

20/A906

13/A906

FIRE DOOR - HOLD OPEN DEVICE DOOR, PROVIDE PANIC HARDWARE, SMOKE DRAFT GASKET - PROVIDE ELECT. POWER STORAGE ROOM AT ROOF

c.GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS, BATHTUBS, SHOWERS, STEAM ROOMS WITHIN 5' OF STANDING SURFACE AND DRAIN INLET

STORAGE ROOM - LANKERSHIM POOL DECK

6/A906

9/A906

-

17/A906

17/A906 SIM

13/A906

P1 FAN ROOM BUILDING 1 - PAIR OF 4' - 0" DOORS FOR FAN INSTALLATION AND ACCESS

17/A906

17/A906 SIM

13/A906

GARAGE ENTRY - BUILDING 1

17/A906

17/A906 SIM

13/A906

ELECTRICAL ROOM, PROVIDE PANIC HARDWARE, CLOSER, SMOKE DRAFT GASKET

17/A906

17/A906 SIM

14/A906

BICYCLE ROOM - PROVIDE CLOSER, SMOKE DRAFT GASKET

d.GLAZING WITHIN 2' OF VERTICAL EDGE OF CLOSED DOOR AND WITHIN 5' OF WALKING SURFACE

ALUM.

ALUM.

1/A907

2/A907

1/A907

ENTRY GLASS DOUBLE DOORS - PROVIDE SIGNAGE ABOVE DOOR WHICH READS: "THIS DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS" GLASS DOOR - PROVIDE CLOSER

ALUM.

ALUM.

1/A907

2/A907

1/A907

ALUM.

ALUM.

1/A907

2/A907

1,5 A/907

ENTRY GLASS DOOR - PROVIDE CLOSER

H.M.

SEMI GLOSS SEMI GLOSS ALUM.

17/A906

17/A906 SIM

13/A906

MARKET TO GARAGE ENTRY - PROVIDE CLOSER, SMOKE DRAFT GASKET, KEY FOB, DOOR BELL

17/A906

17/A906 SIM

13/A906

-

-

-

SEMI GLOSS SEMI GLOSS

21/A906

23/A906

-

ENTRY DOOR; PROVIDE CLOSER; PROVIDE SIGNAGE ABOVE DOOR WHICH READS: "THIS DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS" AUTOMATIC SLIDING ENTRY DOOR - TORMAX: TX9430 FULL BREAKOUT TELESCOPING SLIDER RH-SX-SX-SO COLOR TO BE SELECTED BY ARCHITECT FROM MANUFACTURER'S FULL RANGE OF COLORS; PROVIDE SIGNAGE ABOVE DOOR WHICH READS: "THIS DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS", BLUE COLOR PMS 2188 PER 365 DESIGN GUIDELINES MARKET DELIVERY ROLL UP DOOR

17/A906

17/A906 SIM

13/A906

0' - 1 3/4"

A

90 MIN.

H.M.

6' - 10"

7' - 0"

0' - 1 3/4"

C

60 MIN.

H.M.

S3

3' - 0"

8' - 0"

0' - 1 3/4"

A

90 MIN.

H.M.

S4

3' - 0"

8' - 0"

0' - 2"

B

-

GLASS

S5

3' - 0"

8' - 0"

0' - 1 3/4"

A

-

H.M.

S6

3' - 0"

7' - 0"

0' - 1 3/4"

A

90 MIN.

H.M.

S7

3' - 0"

8' - 0"

0' - 1 3/4"

A

-

H.M.

7' - 0"

0' - 1 3/4"

C

45 MIN.

H.M.

P2

6' - 0"

7' - 0"

0' - 1 3/4"

C

45 MIN.

H.M.

P3

6' - 0"

7' - 0"

0' - 1 3/4"

C

45 MIN.

H.M.

P4

3' - 0"

7' - 0"

0' - 1 3/4"

A

45 MIN.

H.M.

P5

3' - 0"

7' - 0"

0' - 1- 3/4"

A

-

H.M.

P7

20' - 0"

16' - 0"

0' - 2- 1/8"

L

-

H.M.

P8

28' - 9"

17' - 2"

0' - 1- 3/4"

H

-

STEEL

P9

20' - 10"

16' - 8 5/8"

0' - 1- 3/4"

H

-

STEEL

20' - 9 3/4" 9' - 10 7/8"

0' - 1- 3/4"

H

-

STEEL

P10 P11 P12 P13

3/9/2017 2:31:54 PM

7' - 0"

23' - 2 1/2" 10' - 9 1/8" 20' - 10"

8' - 4"

25' - 7 1/2" 9' - 10 5/8"

0' - 1- 3/4"

H

0' - 1- 3/4"

H

-

STEEL STEEL

0' - 1 3/4"

H

-

STEEL

P14

20' - 0"

9' - 0"

0' - 1 3/4"

H

-

STEEL

P15

3' - 0"

7' - 0"

0' - 1 3/4"

A

45 MIN.

H.M.

P16

3' - 0"

7' - 0"

0' - 1 3/4"

A

45 MIN.

H.M.

P17

6' - 0"

6' - 0"

0' - 1 3/4"

C

45 MIN.

STEEL

P18

5' - 0"

7' - 0"

0' - 1 3/4"

C

45 MIN.

H.M.

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS

-ALL FIRE RATED DOORS SHALL HAVE SMOKE AND DRAFT GASKETS. ALL ACCESSIBLE DOORS TO ROOMS SHALL BE A MINIMUM 32" WIDE WHEN FULLY OPEN. THE EXIT DOOR MUST OPEN OVER A LANDING NOT MORE THAN 1/2" BELOW THE THRESHOLD (PER 2013 CBC SECTION 1008.1.5). -EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF A KEY, SPECIAL KNOWLEDGE, OR EFFORT (PER 2013 CBC SECTION 1008.1.9).

2' - 8" MIN. CLEAR CBC 1008.1.1

** LANDING CAN BE REDUCED TO 39" IF DOOR PROVIDES 34" CLEAR OPENING.

DOOR WIDTH

H.M. ALUM.

STEEL H.M.

H.M. H.M. H.M. ALUM. H.M. H.M. H.M.

SEMI GLOSS SEMI GLOSS SEMI GLOSS ALUM.

7,17,19 /A906

8,17 SIM, 20 /A906 17/A906 SIM

11,12,13,14 /A906 13/A906

1/A907

8,17 SIM, 20 /A906 2/A907

11,12,13,14 /A906 1/A907

SEMI GLOSS SEMI GLOSS SEMI GLOSS

17/A906

17/A906 SIM

13/A906

6/A906

9/A906

-

SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS

17/A906

17/A906 7,17,19 /A906

17/A906

17/A906 SIM

13/A906

H.M. H.M. H.M. H.M. H.M. MTL / GLASS STEEL STEEL STEEL STEEL STEEL STEEL STEEL H.M. H.M. STEEL H.M.

17/A906 SIM

13/A906

MARKET SERVICE DOOR - PROVIDE CLOSER, SMOKE DRAFT GASKET, VIEWER, KEY FOB

MARKET STAIRS; PROVIDE CLOSER, SMOKE DRAFT GASKET, PANIC HARDWARE, ADD SMALL VIEW WINDOW IN EACH DOOR

STAIR #5 AT GROUND; PROVIDE CLOSER, SMOKE DRAFT GASKET, PANIC HARDWARE

STAIR ROOF ACCESS; PROVIDE CLOSER, SMOKE DRAFT GASKET PROVIDE CLOSER, SMOKE DRAFT GASKET, KEY FOB

FAN ROOM; PROVIDE CLOSER, SMOKE DRAFT GASKET

17/A906 SIM

13/A906

SPRINKLER ROOM; PROVIDE CLOSER, SMOKE DRAFT GASKET

17/A906

17/A906 SIM

13/A906

ELECTRICAL ROOM, PROVIDE PANIC HARDWARE, CLOSER, SMOKE DRAFT GASKET

17/A906

17/A906 SIM

13/A906

ELECTRICAL ROOM, PROVIDE PANIC HARDWARE, CLOSER, SMOKE DRAFT GASKET

17/A906

17/A906 SIM

13/A906

-

-

-

SECTIONAL GLASS ALUMINUM OVERHEAD GARAGE DOOR - ETCHED GLASS - BUILDING 1

21/A906

22,23 /A906

-

ROLL-UP GARAGE DOOR - BUILDING 1, CONTRACTOR TO FIELD VERIFY DIMENSIONS

21/A906

22,23 /A906

-

ROLL-UP GARAGE DOOR - BUILDING 1, CONTRACTOR TO FIELD VERIFY DIMENSIONS

21/A906

22,23 /A906

-

ROLL-UP GARAGE DOOR - BUILDING 1, CONTRACTOR TO FIELD VERIFY DIMENSIONS

21/A906 21/A906

22,23 /A906 22,23 /A906

-

2' - 0"

PULL SIDE

MIN. CLR.

MIN. CLR.

1132A.5 THE FLOOR OR LANDING ON THE DWELLING UNIT SIDE OF THE PRIMARY ENTRY DOOR AND ANY REQUIRED EXIT DOOR SHALL HAVE A MIN. LENGTH OF NOT LESS THAN 44"

ROLL-UP GARAGE DOOR - BUILDING 1, CONTRACTOR TO FIELD VERIFY DIMENSIONS

21/A906

22,23 /A906

-

ROLL-UP GARAGE DOOR BETWEEN BUILDING 1 & BUILDING 2, CONTRACTOR TO FIELD VERIFY DIMENSIONS

21/A906

22,23 /A906

-

ROLL-UP GARAGE DOOR - BUILDING 2, CONTRACTOR TO FIELD VERIFY DIMENSIONS

17/A906

17/A906 SIM

13/A906

ELEVATOR CONTROL ROOM, PROVIDE PANIC HARDWARE, CLOSER, SMOKE DRAFT GASKET

17/A906

17/A906 SIM

13/A906

ELECTRICAL ROOM, PROVIDE PANIC HARDWARE, CLOSER, SMOKE DRAFT GASKET

17/A906

17/A906 SIM

13/A906

GREASE INTERCEPTOR, SOLID DOOR. NO VISION. PROVIDE GOOD VENTILATION.

17/A906

17/A906 SIM

13/A906

ELECTRICAL ROOM, PROVIDE PANIC HARDWARE, CLOSER, SMOKE DRAFT GASKET

-HAND ACTIVATED DOOR OPENING HARDWARE IS TO BE BETWEEN 34 & 48 INCHES ABOVE THE FINISHED FLOOR. LATCHING AND LOCKING DOORS THAT ARE HAND ACTIVATED AND IN A PATH OF TRAVEL SHALL HAVE LEVER TYPE HARDWARE, PANIC BARS, PUSH-PULL ACTIVATING BARS, OR OTHER HARDWARE THAT PROVIDES PASSAGE WITHOUT GRASPING THE HARDWARE.

2' - 8" MIN. CLEAR

PROVIDE THIS ADDITIONAL SPACE IF DOOR IS EQUIPPED WITH BOTH A LATCH AND A CLOSER

CBC 1008.1.1

1' - 0" MIN. CLEAR

TYPICAL DOOR CLEARANCE TYPE

FIRE RATING

DOOR MATERIAL

DOOR FINISH

FRAME MATERIAL

FRAME FINISH

6' - 0"

I

-

STEEL

STEEL

-

3' - 0"

3' - 6"

O

-

STEEL

STEEL

GT9

3' - 0"

6' - 0"

J

-

STEEL

GT10

3' - 0"

5' - 0"

J

-

STEEL

GT11

3' - 0"

5' - 0"

J

-

STEEL

GT12

3' - 0"

5' - 0"

O

-

STEEL

GT13

6' - 0"

8' - 0"

K

-

STEEL

GT14

3' - 0"

6' - 0"

N

-

STEEL

GT15

3' - 10"

6' - 0"

J

-

STEEL

SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS

SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS

WIDTH

HEIGHT

GT2

6' - 0"

GT6

THICK.

STEEL STEEL STEEL STEEL STEEL STEEL STEEL

REMARKS

-THE BOTTOM 10 INCHES OF ALL DOORS, EXCEPT AUTOMATIC AND SLIDING DOORS, MUST HAVE A SMOOTH, UNINTERRUPTED SURFACE TO ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR FOOTREST WITHOUT CATCHING ON OR TRAPPING THE FOOTREST.

SHEET TITLE -EVERY ENTRANCE OR PASSAGE DOORWAY SHALL BE OF A SIZE AS TO PERMIT THE INSTALLATION OF A DOOR NOT LESS THAN 3 FEET IN WIDTH. DOORS SHALL BE CAPABLE OF OPENING AT LEAST 90 DEGREES AND SHALL BE SO MOUNTED THAT THE CLEAR WIDTH OF THE DOORWAY IS NOT LESS THAN 32 INCHES. (PASSAGE DOORS IN PARTIAL COMPLIANCE UNITS NEED ONLY PROVIDE 32 INCHES WITHOUT MEETING 3 FEET DOOR SIZE REQUIRED). -PROVIDE PANIC HARDWARE FOR ALL DOORS WITH OCCUPANT LOAD 50 OR MORE.

-CONFIRM SINGLE/DUAL GLAZING AND TINT REQUIREMENTS W/ TITLE 24 ENERGY AND ACOUSTICAL REPORTS. SHOP DRAWINGS: 1.SUBMIT SHOP DRAWINGS FOR ALL DOOR AND WINDOW TYPES. SEE DETAILS REFERENCED FROM SCHEDULES FOR TYPICAL DOOR AND WINDOW CONDITIONS.

BUILDING 2 - SIDE YARD EXIT WITH PANIC HARDWARE; PROVIDE SHOP DRAWINGS BUILDING 1 - POOL GATE; PROVIDE SHOP DRAWINGS BUILDING 1 - SPA GATE; PROVIDE SHOP DRAWINGS BUILDING 1 - POOL DECK MAINTAINENCE GATE; PROVIDE SHOP DRAWINGS BUILDING 1 - ENTRY GATE WITH PANIC HARDWARE; PROVIDE SHOP DRAWINGS TANK ROOM BUILDING 1 - COURTYARD #2

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

2.DOOR MANUFACTURER TO SUBMIT QUANTITY LIST AND LOCATION FOR EVERY DOOR TO ARCHITECT FOR REVIEW PRIOR TO ORDERING. ALLOW THREE (3) WEEKS TO REVIEW LIST. 3.WINDOW MANUFACTURER TO SUBMIT QUANTITY LIST AND LOCATION FOR EVERY WINDOW TO ARCHITECT FOR REVIEW PRIOR TO ORDERING. ALLOW THREE (3) WEEKS TO REVIEW LIST. ADDITIONAL NOTES: -MANUFACTURED DOORS AND WINDOWS SHALL BE CERTIFIED AND LABELED IN COMPLIANCE WITH APPROPRIATE INFILTRATION STANDARDS.(NFRC LABEL) FIRE RATED DOOR FRAMES SHALL BE INSTALLED STRICTLY PER MANUFACTURER'S PRINTED INSTRUCTIONS. MANUFACTURER'S PRINTED INSTRUCTIONS SHALL BE MADE AVAILABLE TO THE INSPECTING AUTHORITIES.

HDR

WATER BOOSTER PUMP ROOM BUILDING 1 - POOL EQUIPMENT GATE; PROVIDE SHOP DRAWINGS

DOOR SCHEDULE

PUSH SIDE 2013 CBC SECTION 1008 & FIGURES 11B-404.2.4.1

GATE NO.

-MAXIMUM EFFORT TO OPERATE DOORS MUST NOT EXCEED 5 POUNDS FOR EXTERIOR DOORS AND 5 POUNDS FOR INTERIOR DOORS. THIS MAXIMUM EFFORT IS MEASURED AS THE AMOUNT OF PUSH OR PULL APPLIED AT RIGHT ANGLES TO HINGED DOORS, AND AT THE CENTER PLANE OF SLIDING OR FOLDING DOORS. COMPENSATING DEVICES OR AUTOMATIC DOOR OPENERS MAY BE USED TO MEET THESE STANDARDS.WHEN FIRE DOORS ARE REQUIRED, THE MAXIMUM EFFORT TO OPERATE THE DOORS MAY BE INCREASED UP TO 15 POUNDS.

-ALL HARDWARE SHALL BE LEVER HARDWARE MEETING ADA REQUIREMENTS.

BUILDING 1 TO BUILDING 2 CONNECTION

ROLL-UP GARAGE DOOR - BUILDING 1, CONTRACTOR TO FIELD VERIFY DIMENSIONS

CLEAR AT EXTERIOR DOORS

CLEAR AT INTERIOR DOORS & HANDICAP BATHROOMS

1' - 6"

PROVIDE CLOSER, SMOKE DRAFT GASKET, PANIC HARDWARE, KEY FOB

17/A906

-FLUSH BOLTS OR SURFACE BOLTS ARE PROHIBITED ON EXIT DOORS.

-GLAZED OPENINGS WITHIN 24" OF THE DOOR LOCK WHEN DOOR IS IN THE CLOSED POSITION SHALL BE FULLY TEMPERED GLASS OR APPROVED BURGLARY-RESISTANT MATERIAL.

INTERNAL UNIT DOOR CLEARANCE

PARKING GARAGE P1

MIN. CLR.

0° .0 90

S2

SEMI GLOSS SEMI GLOSS SEMI GLOSS GLASS CLR. SEMI GLOSS SEMI GLOSS SEMI GLOSS

-DOOR MANUFACTURER TO SUBMIT QUANTITY LIST & LOCATION FOR EVERY DOOR TO ARCHITECT FOR REVIEW PRIOR TO ORDERING. ALLOW THREE (3) WEEKS TO REVIEW LIST.

1' - 6"

-EXIT DOOR HARDWARE SHALL BE AN APPROVED TYPE TESTED IN ACCORDANCE WITH THE PROCEDURES ESTABLISHED BY CALIFORNIA STATE FIRE MARSHAL STANDARDS 33.2.

4' - 0" MINIMUM CLEAR WITH

7' - 0"

e.IN WALLS ENCLOSING STAIRWAY LANDINGS

PUSH SIDE

STAIRS 3' - 0"

b.GLAZING IN FIXED AND SLIDING PANELS OF SLIDING DOORS AND PANELS IN SWINGING DOORS

PULL SIDE

5' - 0" MINIMUM CLEAR WITH

5' - 10"

- ALUMINUM ENTRANCES AND STOREFRONTS - PROVIDE THERMALLY-BROKEN FRAMES WITH CONCEALED FLASHING AND GASKETED GLAZING.

Q

MARKET M1

- FINISH FOR PRE-ASSEMBLED DOOR HINGES TO MATCH BALANCE OF DOOR HARDWARE. DOOR MANUFACTURER'S STANDARD HARDWARE FINISH MAY NOT MATCH HARDWARE FINISH SPECIFIED IN DOOR HARDWARE SECTION.

0° .0 90

G20

1/A907

11' - 0"

E

2/A907

MINIMUM CLEAR

0' - 2"

1/A907

MINIMUM CLEAR**

8' - 9 1/2"

ALUM.

LATCH AND CLOSER

6' - 0"

ALUM.

(3' - 8" MIN. CLEAR WITHOUT) (EXCEPTION: 36" CLEAR IN GROUP R-1 AT INTERIOR)

G2

GLASS CLR. GLASS CLR. GLASS CLR. SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS

LATCH AND CLOSER

GLASS

(3' - 8" MIN. CLEAR WITHOUT)

-

3' - 6"

E

3' - 6"

0' - 2"

DOOR HEIGHT

8' - 0"

10' - 1 1/2"

6' - 2"

S1

- DO NOT APPLY KICKPLATES, DOOR PROTECTION PLATES, ADDRESS SIGNS, ETC. TO THE FACE OF RATED DOORS IN A MANNER THAT WILL VIOLATE REQUIRED DOOR FIRE-RATING.

N

3' - 0"

G1

M6

K

L

DOG WASH - PROVIDE CLOSER, SMOKE DRAFT GASKET

GENERAL

G15

J

20' - 0"

13/A906 SIM COMMON SPACE - RESTROOM DOOR - PROVIDE CLOSER, SMOKE DRAFT GASKET 13/A906

I

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

CS3

H.M.

PERFORATED MTL INFILL - 18 ga 3/32" ROUND& 5/32" STAGGERED GALV.

LANKERSHIM + otsego

H.M.

PERFORATED MTL INFILL - 18 ga 3/32" ROUND& 5/32" STAGGERED GALV.

BUSINESS - PROVIDE CLOSER, SMOKE DRAFT GASKET

HDR 201

VISIBLE PLAQUE SIGNAGE DOOR VIEWER AT STANDARD HEIGHT 10" KICKPLATE AT PUSH SIDE OF DOOR TO MATCH DOOR HARDWARE FINISH

FFL

STANDARD ENTRY DOOR

HDR 201

3' - 6"

90 MIN.

13/A906

HEIGHT PER SCHEDULE

A

20/A906

5' - 4"

0' - 1 3/4"

19/A906

HEIGHT PER SCHEDULE

8' - 0"

SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS ALUM.

16' - 0"

3' - 0"

H.M.

EQ

CS2

SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS STAND. COLOR SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS SEMI GLOSS GLASS CLR. GLASS CLR. SEMI GLOSS GLASS CLR. SEMI GLOSS SEMI GLOSS SEMI GLOSS

EQ

H.M.

EQ

20 MIN.

EQ

A

EQ

0' - 1 3/4"

EQ

8' - 0"

EQ

3' - 0"

EQ

CS1

FFL

ACCESSIBLE ENTRY DOOR

VISIBLE PLAQUE SIGNAGE DOOR VIEWER AT STANDARD HEIGHT SECOND DOOR VIEWER IN ACCESSIBLE UNITS 10" KICKPLATE AT PUSH SIDE OF DOOR TO MATCH DOOR HARDWARE FINISH

NOTE: APPLY KICKPLATES, DOOR PROTECTION PLATES, ADDRESS SIGNS, ETC. TO THE FACE OF THE RATED DOORS ACCORDING TO FIRE-RATING REQUIREMENTS. -KICKPLATES SHALL BE GLUED TO FIBERGLASS DOOR.

TYPICAL DOOR NOTES

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO. DATE SCALE

1501 03-03-2017 As indicated

SHEET NO.

A094


EXISTING FOUR STORY PARKING GARAGE 15' - 0"

DE Architects AIA

72' - 2"

190' - 11"

10' - 2"

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

01A29

12A7 01A28

EL: 619.42'

OPEN TO GROUND FLOOR

EL: 633.42'

10' - 0"

PL N 0° 02' 11" W 71.52'

10' - 1"

EL: 621.35'

SETBACK

10' - 0"

PL N 89° 52' 51" E 296.34'

PL N 89° 52' 37" W 303.96'

RESIDENTIAL SETBACK NO SETBACK REQUIRED AT GROUND FLOOR

EL: 619.42'

EL: 619.42'

EL: 636.42'

OPEN TO GROUND FLOOR

OPEN TO SECOND FLOOR COURTYARD

01A34 01A15

AD

03A3

01A29

03A3 10' - 0"

22B1

RESIDENTIAL SETBACK NO SETBACK REQUIRED AT GROUND FLOOR

EXISTING TWO STORY BUILDING EXISTING FOUR STORY BUILDING

MIXED-USE HOUSING COMPLEX

17' - 8"

A

NI

Y WA 0 3' -

/8" 2 3 AL ' 3 PIC TY

DN

0"

IVE DR

5 STORIES OF TYPE IIIA CONSTRUCTION OVER 2 LEVELS ABOVE GRADE (RESIDENTIAL, MARKET, GARAGE) AND 2 LEVELS SUBTERRANEAN GARAGE TYPE 1A CONSTRUCTION.

01A15

O

30'

262' - 0"

CA L I F

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

W NE

16' - 3"

R

76' - 2"

10' - 0"

10' - 0" SETBACK

SETBACK NO SETBACK REQ. AT GROUND FLOOR

N 89° 50' 37" E 187.34'

OF

"

10' - 0"

EL: 621.35'

OPEN TO GROUND FLOOR

RESIDENTIAL

PL

E

0 3' -

PROPERTY LINE

10' - 0"

EL: 633.42'

REN. 6-30-17

AY EW RIV " D SION 0" 1/4 3' - 3 TEN 11' EX

N 0° 04' 01" W 100.00'

EL: 619.42'

01A29

' .04 299 0" 5' 0 6° 4

15' - 1"

N 89° 52' 31" E 10.00'

N2

7' x 11' SWITCH

SETBACK

DEDICATION

8' x 10' TRANSFORMER

0"

N 0° 07' 29" E 0.12' N 89° 50' 37" E 21.11'

N 0° 07' 29" W 11.00'

3' - 0"

SETBACK

139' - 6"

1" -1 15'

8' - 0"

NO. C-13779

T

15' - 0"

EXISTING FOUR STORY BUILDING

47'

OPEN TO GROUND FLOOR

R4-2 C4-1-CA

21A7.1

L IC E DONA

3' - 0"

OPEN TO GROUND FLOOR

CT TE ERIS K

01A29

01A16

ED A RCH NS S EMP I A TA

ST A

NEW DRIVEWAY

SETBACK

"

30' - 0"

10' - 0"

AY EW RIV S TIE GD ER TIN OP XIS PR "E 3/4 G2 -8 VIN 35' ER HS DT WI

KLUMP AVENUE

STAMP

OPEN TO SECOND FLOOR COURTYARD

0 3' -

74' - 11"

01A15

"

01A30

PL

RD VA LE

01A15 01A15

OPEN TO SECOND FLOOR COURTYARD

225' - 0"

2"

U BO

SETBACK NO SETBACK REQUIRED AT GROUND FLOOR

'259

IM SH ER NK LA

RESIDENTIAL

LANKERSHIM + otsego

01A15

10' - 0"

N 0° 16' 36" W 2.15'

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

N 0° 16' 36" W 82.66'

01A16

OPEN TO SECOND FLOOR COURTYARD

01A29

" 3/8 L 2 A 3' PIC TY

01A15

01A30 01A16

01A15

N 0° 16' 36" W 160.30'

0"

O PR INE YL RT PE

N 89° 51' 56" E 286.55' 01A27 3' - 0"

34' - 0"

01A15

01A16

01A15

01A30

01A15

PROPERTY LINE

01A16

3' - 0"

NEW DRIVEWAY 15' - 0"

8' - 0"

3' - 2 1/4" TYPICAL

8' x 10' TRANSFORMER

DEDICATION

PL

OPEN TO GROUND FLOOR

3' - 1"

SWITCH 7' x 11'

15'

0" N 5' - ATIO DIC DE

30' - 8"

52' - 5"

617.91' POINT OF LOWEST ADJACENT GRADE PER SURVEY

OTSEGO STREET 01A15

163' - 11"

15' - 0"

N

1

SITE PLAN 1/16" = 1'-0"

SHEET TITLE

0'

10'

20'

40'

SITE PLAN

80'

GRAPHIC SCALE 1/16 = 1'-0"

SITE PLAN NOTES: 1. DO NOT SCALE DRAWINGS. CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT JOB SITE PRIOR TO BIDDING AND START OF CONSTRUCTION. IF DISCREPANCIES ARE FOUND, THE ARCHITECT SHALL BE NOTIFIED FOR CLARIFICATION. 2. THE CONTRACTOR SHALL FURNISH ALL MATERIALS, LABOR, EQUIPMENT, TRANSPORTATION AND SERVICES NECESSARY FOR THE SATISFACTORY COMPLETION OF WORK. ALL EQUIPMENT, WORK AND MATERIALS SHALL COMPLY WITH ALL CURRENT AND LOCAL APPLICABLE CODES AND GOVERNING REGULATIONS. BUILDING CODE REQUIREMENTS TAKE PRECEDENCE OVER THE DRAWINGS. 3. IF THE CONTRACTOR ASCERTAINS AT ANY TIME THAT REQUIREMENTS OF THIS CONTRACT CONFLICT WITH OR ARE IN VIOLATION OF APPLICABLE LAWS, CODES, REGULATIONS AND ORDINANCES, HE SHALL NOT PROCEED WITH WORK IN QUESTION, EXCEPT AT HIS OWN RISK, UNTIL ARCHITECT HAS BEEN NOTIFIED IN WRITING AND A WRITTEN DETERMINATION HAS BEEN MADE BY THE ARCHITECT. 4. WHEN IT IS NECESSARY TO INTERRUPT ANY EXISTING UTILITY SERVICES TO MAKE CONNECTIONS AND/OR CONNECTION, A MINIMUM OF 48 HOURS ADVANCE NOTICE SHALL BE GIVEN TO THE OWNER. INTERRUPTIONS IN UTILITY SERVICES SHALL BE OF THE SHORTEST POSSIBLE DURATION FOR THE WORK AT HAND AND SHALL BE APPROVED IN ADVANCE BY THE OWNER.

13. WALKS, SIDEWALKS AND PEDESTRIAN WAYS SHALL BE FREE OF GRATING WHENEVER POSSIBLE. IF THERE ARE GRATINGS, GRID OPENINGS ARE TO BE NO MORE THAN 1/2" IN THE DIRECTION OF TRAFFIC FLOW. 14. SEE PLUMBING DRAWINGS FOR UTILITIES.

16. SEE 1/8" AND 1/4" SCALE DRAWINGS FOR MORE DIMENSIONS, NOTES AND INFORMATION. ALL DRAINAGE FROM ROOF, AND SITE DRAINAGE ARE SHOWN ON PLUMBING DRAWINGS. 17. ALL CONSTRUCTION SHOWN ON SITE IS NEW. 18. PROVIDE 1/4"/1 FOOT MIN. SLOPE TO DRAIN TYP. AT YARDS AND BALCONIES.PROVIDE 1/4"/1 FOOT SLOPE AWAY FROM THE BUILDING AT SIDEWALKS TYP. 19. BUILDING ADDRESS SHALL BE PROVIDED AT OR NEAR THE ENTRANCE OF THE BUILDING IN ACCORDANCE WITH CITY AND FIRE DEPARTMENT REQUIREMENTS.

6. AN APPROVED SEISMIC GAS SHUTOFF VALVE SHALL BE INSTALLED ON THE FUEL GAS LINE ON THE DOWN STREAM SIDE OF THE UTILITY METER AND BE RIGIDLY CONNECTED TO THE EXTERIOR OF THE BUILDING OR STRUCTURE CONTAINING THE FUEL GAS PIPING. FOR PERMIT INFORMATION CONTACT THE PLUMBING DIVISION.

21. TEMPORARY PEDESTRIAN PROTECTION SHALL BE PROVIDE AS REQUIRED BY SECTION 3306. OBTAIN PUBLIC WORKS' APPROVAL. (3201.3, 3202.3.4, 3306)

9. PLANTER WALLS AND FENCES IN THE PUBLIC WAY REQUIRE AN ENCROACHMENT PERMIT PRIOR TO INSTALLATION. DRAINAGE SHALL NOT FLOW OVER PUBLIC PROPERTY OR ACROSS ADJACENT PRIVATE PROPERTY. (2013 UBC SECTION 1506.5). ROOF DRAINAGE SHALL NOT BE CARRIED OVER SIDEWALKS. CONDUCT ALL DOWNSPOUT AND ROOF DRAINS TO THE DRAINAGE SYSTEM. CONCENTRATED DRAINAGE SHALL BE DISCHARGED INTO AN APPROVED LOCATION. 10. ALL WALK SURFACES TO BE SLIP-RESISTANT SURFACES. 11. PROVIDE 30" CLEAR ACCESS AROUND BUILDING.

26. CONCRETE STAIR REQUIREMENT: 11" MIN. TREADS - 7" MAX RISER. CONTRACTOR TO VERIFY GRADES AND ADJUST NUMBER OF RISERS REQUIRED, IF NECESSARY. STAIRS SHALL CONFORM WITH CODE REQUIREMENTS, REF STRUCTURAL DRAWINGS AND SHEET A900 SERIES. 27. SEE LANDSCAPE DRAWINGS FOR IRRIGATION CONTROLLER LOCATION AND TYPE. 28. SEE LANDSCAPE DRAWINGS FOR HARDSCAPE, LANDSCAPE AND COMMON SPACE FURNITURE LAYOUT

15. ACCURACY OF DATA FROM SURVEY NOT GUARANTEED BY ARCHITECT.

20. VERIFY LOCATION OF SECURITY GATES WITH OWNER. PROVIDE KEY BOX AT AN ACCESSIBLE LOCATION FOR FIRE DEPARTMENT EMERGENCY ACCESS. THE KEY BOX SHALL BE OF AN APPROVED TYPE & SHALL CONTAIN KEYS TO GAIN NECESSARY ACCESS AS REQUIRED BY FIRE DEPARTMENT.

8. CONTRACTOR TO PROVIDE SECURITY BY MEANS OF A MINIMUM EIGHT FOOT HIGH FENCE MAINTAINED AROUND THE ENTIRE SITE PRIOR TO START OF WORK.

3/9/2017 2:32:30 PM

12. BALCONY PROJECT INTO FRONT YARD IS 30" MAXIMUM.

5. ALL SURFACES DAMAGED DURING THE COURSE OF WORK BY THE CONTRACTOR OR SUBCONTRACTORS SHALL BE REPAIRED AT NO COST TO THE OWNER.

7. LANDSCAPE DESIGN REQUIRES 100% DRIP IRRIGATION WITHIN 5 FT OF BUILDING PERIMETER FOOTING, SPRAY HEADS NOT ALLOWED IN THIS PROJECT.

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

KEYNOTES LEGEND:

22. SCREENS, BARRICADES, OR FENCES MADE OF MATERIAL WHICH PRECLUDE HIMAN CLIMNING SHALL BE PROVIDED AT EVERY PORTION OF EVERY ROOF, BALCONY, OR SIMILAR SURFACE WHICH IS WIHTIN 8 FT. OF THE UTILITY POLE OR SIMILAR STRUCTURES. (6707)

29. AUTOMATIC LANDSCAPE IRRIGATORS SHALL BE INSTALLED SUCH THAT IT DOESN’T SPRAY ON THE BUILDING.

NO. 01A15 01A16 01A27 01A28 01A29 01A30

01A34 03A3 12A7 21A7.1 22B1

DESCRIPTION ROOF OVERHANG/CANOPY BALCONY BELOW, TYP. PLANTER BELOW, TYP. MECHANICAL SHAFT BELOW LINE OF SETBACK ENCROACHMENT INTO THE PUBLIC RIGHT-OF-WAY PER 2013 CBC SECTION 3202.3.2 & 3202.3.3, TYP. RAISED WALKWAY C.I.P.C. STAIRS BICYCLE DOCK (MANUF: SARIS - BIKE DOCK OR APPROVED EQ.) TYP. (E) FIRE HYDRANT UTILITY GAS METER (REF. PLUMBING DWGS.)

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO.

23. SEE CIVIL DRAWINGS FOR DRAIN LOCATIONS AND SITE DRAINAGE 24. IT IS THE INTENT OF THE ARCHITECTS TO TIE THE FINISH FLOOR ELEVATIONS WITH THE EXISTING SIDEWALK TO MEET APPLICABLE CODE AND A.D.A. REQUIREMENTS. THE GRADES SHOWN WERE INTERPOLATED FROM THE SURVEY PROVIDED TO THE ARCHITECT AND CAN NOT BE VERIFIED FOR ACCURACY. THEREFORE, CONTRACTOR TO NOTIFY BOTH CIVIL ENGINEER AND ARCHITECT OF ANY DISCREPANCIES PRIOR TO CONSTRUCTION. 25. SITE DEVELOPMENT AND GRADING SHALL BE DESIGNED TO PROVIDE ACCESS TO ALL ENTRANCES AND EXTERIOR GROUND FLOOR EXITS, AND ACCESS TO NORMAL PATHS OF TRAVEL, AND WHERE NECESSARY TO PROVIDE ACCESS, SHALL INCORPORATE PEDESTRIAN RAMPS, CURB RAMPS, ETC. (1110A.1)

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

DATE

1501 03-03-2017

SCALE

1/16" = 1'-0"

SHEET NO.

A101


KC1

KC3

21' - 4"

KC4

18' - 11 5/8"

KC6

KC7

KC9

6' - 10" 6' - 11"

KC11

27' - 10"

KC13

26' - 5"

KC15

18' - 1"

KC17

26' - 6"

KC19

26' - 6"

KC21

26' - 6"

KC24

26' - 6"

KC25

26' - 6"

18' - 0"

KC26

10' - 10"

6"

9 RES.

11 RES.

27 RES.

29 RES.

C

C

C

C

C

C

C

C

C

12 RES.

14 RES.

16 RES.

20 RES.

18 RES.

22 RES.

24 RES.

26 RES.

28 RES.

31 RES.

33 RES.

C

30 RES.

32 RES.

35 RES.

C

37 RES.

39 RES.

41 RES.

43 RES.

45 RES.

47 RES.

C

C

C

C

C

C

C

34 RES.

36 RES.

38 RES.

40 RES.

42 RES.

44 RES.

46 RES.

49 RES.

51 RES.

53 RES.

C

C

C

48 RES.

50 RES.

52 RES.

55 RES.

57 RES.

C

54 RES.

56 RES.

59 RES.

C

C

58 RES.

KCO

60 RES.

KCJ

L IC E DONA

LC24

7' - 8 3/4" 42' - 11 5/8"

7' - 5 1/4"

19' - 5 3/8"

6' - 5 1/2"

1

82 RES.

80 RES.

78 RES.

76 RES.

74 RES.

72 RES.

70 RES.

68 RES.

64 RES.

66 RES.

61 RES.

SWITCH ABOVE @ GROUND FLOOR

N 89° 52' 31" E 10.00'

105 RES.

103 RES.

101 RES.

C

99 RES.

C

C

97 RES.

C

95 RES.

93 RES.

C

C

91 RES.

89 RES.

C

87 RES.

C

C

85 RES.

83 RES.

C

81 RES.

C

C

79 RES.

77 RES.

C

75 RES.

C

C

73 RES.

C

71 RES.

69 RES.

C

67 RES.

C

65 RES.

62 RES.

17' - 4 7/8"

PROPERTY LINE

ED

63 RES.

PL

RAMP UP

26' - 6"

26' - 6"

26' - 6"

26' - 6"

26' - 6"

18' - 10"

8' - 3"

KC8

KC10

KC12

KC14

KC16

KC18

KC20

34 RES.

N 0° 16' 36" W 82.66'

12' - 9 1/4"

6' - 4 3/4"

N 0° 16' 36" W 2.15'

23' - 7 1/4"

89 RES.

37 RES.

44' - 10"

39 RES.

41 RES.

36 RES.

88 RES.

C

91 RES.

45 RES.

43 RES.

50 RES.

C

94 RES.

ED

38 RES.

40 RES.

42 RES.

46 RES.

44 RES.

47 RES.

49 RES.

96 RES.

51 RES.

7' - 2 3/4" 24' - 3 1/4"

99 RES.

98 RES.

C

101 RES.

LC16

C

ED

LC23

58 RES.

59 RES.

60 RES.

61 RES.

62 RES.

63 RES.

106 RES.

C

114 RES.

68 RES. 69 RES.

73 RES.

71 RES.

72 RES.

70 RES.

ELEVATOR PIT

118 RES.

20' - 0 5/8"

ED

01A32

CA

ED

ED

1 RES.

ED

ED

ED

120 RES.

142 RES.

141 RES.

140 RES.

INE YL

N 0° 16' 36" W 160.30'

T ER PO

121 RES. 138 RES.

137 RES.

136 RES.

135 RES.

134 RES.

133 RES.

132 RES.

130 RES.

131 RES.

129 RES.

128 RES.

127 RES.

126 RES.

123 RES.

124 RES.

125 RES.

LCB

122 RES.

PL

139 RES.

PROPERTY LINE

8' - 0"

1' - 0"

LCA

CB

" 5/8

119 RES.

ED

O PR

22' - 6"

8 1' 8"

OPENING ABOVE

3' - 10 1/2"

CC

N 0" 5' - TTIO A C DI DE

117 RES.

C

LCD 2 RES.

CD

26'

3 RES.

74 RES.

116 RES.

ED

CE

8"

115 RES.

ED

4 RES.

113 RES.

26'

5 RES.

C

CF

/8" 25 1' - 7/8" 1

54 RES.

111 RES.

-1 14'

RAMP UP

C

CG

112 RES.

67 RES.

VEHICULAR RAMP #2

109 RES.

110 RES.

66 RES.

ED

C

CH

108 RES.

65 RES. ED

53 RES.

107 RES.

" 1/8

57 RES.

C

CI

" 3/8

56 RES.

105 RES.

0 2' -

64 RES. 55 RES.

C

104 RES.

26' - 8"

52 RES.

CJ

103 RES.

102 RES.

ED

CK

5 8' -

6' - 6 3/4"

C

ED

RESIDENTIAL PARKING 119 STANDARD 23 COMPACT TOTAL = 142 SPACES

74' - 5"

6 RES.

SWITCH ABOVE @ GROUND FLOOR

CM

97 C RES.

ED

7 RES.

LCC

CN

" 3/8 -6 10' /8" 5

8' - 1 1/4"

95 RES.

-1 16'

15' - 6 3/4"

93 RES.

92 RES.

C

48 RES.

C

100 RES.

10 RES.

17' - 10"

CO

ED

ED

LCE

CP

ED

11 RES.

LCF

1' - 6"

C

12 RES.

LCG

3' - 10"

35 RES.

13 RES.

LCH 3' - 5 1/2"

26' - 8"

ED

86 RES.

01A32

90 RES.

14 RES.

8 RES.

LG

46' - 3"

15 RES.

9 RES.

LCI

LC26

LC15

CQ

87 RES.

C

16 RES.

LCK

LCJ

84 RES.

ED

LC6

85 RES.

/8" 03 2' " 5/8

LCM

C

CR

-7 24'

LCN

83 RES.

C

/4" 83 2' - " 1/4

LCQ

81 RES.

-5 24'

LCR

C

LCW

ED

LCS

78 RES.

82 RES.

18 RES. 17 RES.

79 RES.

80 RES.

LCU 1' - 1 3/4"

KC5

C

/8" 97 " 7' 3/4 -4 14'

KC2

KC23

33 RES.

32 RES.

19 RES.

18' - 2"

KC22

KC1

31 RES.

20 RES.

LCV

30 RES.

LCX

STAIR #1

26' - 6"

25' - 6 1/4"

28' - 6"

28 RES. C

CT

" 3/8

28' - 1 1/4"

29 RES.

77 RES.

5 4' 8"

15' - 9 3/4"

26 RES.

ED

27 C RES.

CV

26'

8' - 0"

1' - 7 3/4"

LCY

25 RES.

21 RES.

76 RES.

CW

8"

LCZ

LCXX

75 RES.

EDLCYY

22 RES.

2

24 RES.

KCA

3' - 3 1/8"

AREA RESERVED FOR GAS LINES FROM OTSEGO

O

26'

MATCHLINE

N 89° 52' 37" W 303.96'

23 RES.

VEHICULAR RAMP #1

KCB ED

4 1/4"

N 0° 04' 01" W 100.00'

107 RES.

C

109 RES.

C

"

C

111 RES.

C

" -0 14' N 89° 50' 37" E 187.34'

8 1' -

C

113 RES.

C

KCD

/8"

PL

C

CA L I F

"

07

ED

0 1' -

C3

4 7/8"

84 RES.

21' - 9 3/4"

86 RES.

20' - 9 3/8"

88 RES.

18' - 1"

90 RES.

ELEVATOR #3

92 RES.

GATE

94 RES.

19' - 0"

96 RES.

STAIR #2

98 RES.

20' - 10"

100 RES.

OF

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

C2

ELEVATOR #2

102 RES.

N 0° 07' 29" E 0.12' N 89° 50' 37" E 21.11'

C1

GATE

104 RES.

KCG 15' - 7 1/8"

110 RES.

106 RES.

N 0° 07' 29" W 11.00'

TRANSFORMER ABOVE @ GROUND FLOOR

108 RES.

E

CY

MATCHLINE

112 RES.

REN. 6-30-17

A

NO. C-13779

NI

11' - 9 5/8" 10' - 9 3/4"

LC21

R

ED

LC20

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

ED

LC18

LANKERSHIM + otsego

01A32

ED

LC11

16' - 6"

ED

LC5

8' - 0"1' - 0"

26' - 8 1/8"

ED

LC2

ED A RCH NS S EMP I A TA

' .04 299 0" 5' 0 6° 4

3' - 7"

RESIDENTIAL PARKING 58 STANDARD 55 COMPACT ED TOTAL = 113 SPACES

ED

ED

ED

STAMP

ELEVATOR #1

ELEVATOR #4

11' - 0 1/8"

25 RES.

LC1

17' - 0"

2' - 11 1/8"

23 RES.

N2

KCB

21 RES.

-1 27'

KCC

19 RES.

CT TE ERIS K

KCE

10 RES.

17 RES.

T

KCF

8' - 0" DEDICATION

8 RES.

6 RES.

4 RES.

2 RES.

C

15 RES.

ST A

KCH

6' - 9 7/8"

KCM

12' - 0 7/8"

KCN

8' - 4 5/8"

C

13 RES.

N 89° 51' 56" E 286.55' 4 3/8"

1' - 2 1/8" 8' - 2 7/8" 29' - 1"

15' - 7 7/8"

LC1.1

LC3

LC4

LC8

8' - 0" DEDICATION

STAIR #4

17' - 6"

C

C

14' - 6"

C

31' - 0"

C

WATER BOOSTER PUMP

7 RES.

5 RES.

3 RES.

KCR

N 0° 02' 11" W 71.52'

1 RES.

N 89° 52' 51" E 296.34'

STAIR #3A

KCP

10' - 7 1/4"

6"

KCQ

PL

PL

KCR

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

4"

5"

DE Architects AIA

TRANSFORMERS ABOVE @ GROUND FLOOR

9' - 6 3/8" 6' - 11"

LC10

LC12

LC14

27' - 7 7/8"

14' - 6 1/4"

LC22

12' - 11 3/4"

LC25

LC27

16' - 11"

9' - 9"

LC28

26' - 8"

LC29

26' - 8"

LC30

27' - 6"

LC31

LCA

25' - 9 3/4"

LC32

LC33 0" 1' " '-0 14 '15

SHEET TITLE

8"

P2 GARAGE - KEY PLAN

C3

" '-6 32

C6

C2 ' 5

C1 0"

C4

N

P2 GARAGE - KEY PLAN 1 1/16" = 1'-0"

P2 PARKING

GENERAL NOTES

RESIDENTIAL PARKING TOTAL STANDARD TOTAL COMPACT

-REFER TO SHEET A101 FOR GRADES AND SITE PLAN NOTES NOT CONTAINED IN THIS DRAWING. -LANDSCAPE DESIGN REQUIRES 100% DRIP IRRIGATION WITHIN 5 FT OF BUILDING PERIMETER FOOTING, SPRAY HEADS NOT ALLOWED IN THIS PROJECT. -SEAL EXTERNAL CRACKS, JOINTS ETC. WITH CAULKING AND INSTALL PEST-PROOF SCREENS WHERE REQUIRED.

TOTAL RESIDENTIAL PARKING

177 SPACES 78 SPACES 255 SPACES

METAL LATH: - ATTACH LATH TO SUPPORTS AT 6" O.C. INSTALL LATH USING HOT-DIP GALVANIZED FASTENERS WITH NEOPRENE WASHERS. INSTALL SCREWS TO ENSURE THAT WASHERS HAS MAXIMUM CONTACT WITH BUILDING PAPER/MEMBRANE WATERPROOFING. SCREWS SHALL PENETRATE THROUGH EXTERIOR PLYWOOD SHEATHING INTO FRAMING. - IF STAPLES ARE USED TO ATTACH LATH, ALL PENETRATIONS SHALL BE CAULKED AND SEALED, TYPICAL.

3/9/2017 2:32:37 PM

FIREPROOFING: -APPLY 1HR CEMENTITIOUS FIREPROOFING (LARR #24763 OR APPROVED EQUAL) APPLY IN LOCATIONS NOTED, OTHERWISE PROVIDE INTUMESCENT COATING. -PROVIDE FIRE SPRINKLER SYSTEM SHALL BE APPROVED BY PLUMBING DIV. PRIOR TO INSTALLATION. 12.21A17(d) -INTUMESCENT COATING, TYPICAL AT ALL STEEL LOCATD WITHIN DWELLING UNITS. PROVIDE 1HR RATING THROUGHOUT, EXCEPT FOR COLUMNS ENCLOSED WITHIN EXTERIOR WALL. PROVIDE 2HR RATING FOR COLUMNS ENCLOSED WITHIN EXTERIOR WALL (LARR #25484 OR APPROVED EQUAL) -SEE STRUCTURAL DWGS FOR RESTRAINED CONSTRUCTION OF STEEL MEMBERS. FIRE PROTECTION: -PROVIDE FIRE SPRINKLER SYSTEM SHALL BE APPROVED BY PLUMBING DIV. PRIOR TO INSTALLATION. 12.21A17(d) - CONTRACTOR SHALL PROVIDE SPRINKLER AT ALL CONCEALED SPACES LARGER THAN 6", PER NFPA13, OR SOLIDLY FILL WITH INSULATION. - INSTALL CONCEALED FIRE SPRINKLERS THROUGHOUT, INT. & EXT.

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

INSULATION: -PROVIDE R-25 INSULATION AT 2X8 WALL FRAMING, WHERE IT OCCURS. -WALL INSULATION SHALL FILL & CONTINUOUSLY TOUCH CAVITY ON ALL 6 SIDES - NO AIR GAPS -CEILING/ROOF INSULATION SHALL CONTINUOUSLY TOUCH CAVITY ON 5 SIDES - NO AIR GAPS MATERIALS: - ANNULAR SPACES AROUND PIPES, ELECTRIC CABLES, CONDUITS, OR OTHER OPENINGS IN THE SOLE/BOTTOM PLATES AT EXTERIOR WALLS SHALL BE PROTECTED AGAINST THE PASAGE OF RODENTS BY CLOSING SUCH OPENINGS WITH CEMENT MORTAR, CONCRETE MASONRY, OR METAL PLATES. PIPING PRONE TO CORROSION SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 313.0 OF THE LOS ANGELES PLUMBING CODE. - MATERIALS DELIVERED TO THE CONSTRUCTION SITE SHALL BE PROTECTED FROM RAIN OR OTHER SOURCES OF MOISTURE. MAINTENANCE MANUAL: -AN OPERATION AND MAINTENANCE MANUAL INCLUDING , AT A MINIMUM, THE ITEMS LISTED IN CAL GREEN SECTION 4.410.1, SHALL BE COMPLETED AND PLACED IN THE BUILDING AT THE TIME OF FINAL INSPECTION OUTDOOR LIGHTING SYSTEMS: - OUTDOOR LIGHTING SYSTEMS SHALL BE DESIGNED AND INSTALLED TO COMPLY WITH ALL OF THE FOLLOWING: a) THE MINIMUM REQUIREMENTS IN CALIFORNIA ENERGY CODE FOR LIGHTING ZONES 1-4. b) BACKLIGHT, UPLIGHT AND GLARE (BUG) RATINGS AS DEFINED IN IESNA TM-15-11. (c) ALLOWABLE BUG RATINGS NOT EXCEEDING THOSE SHOWN IN ON TABLE 5.106.8. DISSIMILAR METALS: -PROVIDE RUBBER GASKET AT DISSIMILAR METALS, TYPICAL THROUGHOUT. POOL EQUIPMENT: - POOL EQUIPMENT SHALL BE MOUNTED ON MECHANICAL PADS & ATTACHED WITH SPRING ISOLATORS. REFERENCE SIMILAR DETAIL 4/A909 - PLUMBING LINES SHALL BE RAISED ABOVE ROOF AND ISOLATED WITH RUBBER SUPPORTS, TYPICAL.

ELECTRICAL NOTES: - THE MAIN ELECTRICAL SERVICE PANEL SHALL HAVE A RESERVED SPACE TO ALLOW FOR INSTALLATION OF A DOUBLE POLE CIRCUIT BREAKER FOR A FUTURE SOLAR ELECTRIC INSTALLATION. THE RESERVED SPACE SHALL BE POSITIONED AT THE OPPOSITE (LOAD) END FROM THE INPUT FEEDER LOCATION OR MAIN CIRCUIT LOCATION AND SHALL BE PERMANENTLY MARKED AS ‘FOR FUTURE SOLAR ELECTRIC’. - THE MAIN SERVICE PANEL SHALL HAVE A MINIMUM BUSBAR RATING OF 200 AMPS. - PROVIDE ADEQUATE LIGHTING TO ENSURE SAFE ACCESS TO BICYCLE PARKING FACILITIES IN ACCORDANCE WITH SECTION 12.21A.5(k).

COMMISSIONING: HVAC, INDOOR LIGHTING AND WATER HEATING ARE NOT WITHIN THE SCOPE OF WORK FOR THIS PHASE OF CONSTRUCTION. COMMISSIONING OF THE HVAC, INDOOR LIGHTING AND WATER HEATING SYSTEMS FOR THE NONRESIDENTIAL SPACES WILL BE REQUIRED AND PERFORMED AT THE INITIAL TENANT IMPROVEMENT PHASE.

LEGEND CONCRETE WALL PER STRUCTURAL CMU WALL PER STRUCT. METAL STUD WALL / PARTY-WALL - SOUND WALL STC RATING 50 REQ. / 1HR RATED (REFERENCE WALL TYPE ASSEMBLY)

FIRE RATED WALL - 2HR

METAL STUD FRAMING @ P2 - 2ND FLOORS: - METAL STUD FRAMING, TYP. @ TYPE 1 CONSTRUCTION - WOOD FRAMING NOT PERMITTED WOOD CONSTRUCTION @ 3rd - 7th FLOORS: EXTERIOR WALLS TO BE FIRE TREATED WOOD LARR 24502 (SEE FLOOR PLANS): -FIRE-RETARDANT-TREATED WOOD IS LUMBER OR PLYWOOD IMPREGNATED WITH CHEMICALS AND WHICH, WHEN TESTED IN ACCORDANCE WITH U.B.C. STANDARD NO. 42-1 FOR A PERIOD OF 30 MINUTES, SHALL HAVE A FLAME SPREAD OF NOT OVER 25 AND SHOW NO EVIDENCE OF PROGRESSIVE COMBUSTION. MATERIALS WHICH MAY BE EXPOSED TO THE WEATHER SHALL MAINTAIN THIS FIRE-RETARDANT CLASSIFICATION WHEN TESTED IN ACCORDANCE WITH THE RAIN AND WEATHERING TESTS OF U.B.C. STANDARD NO. 32-7. -ALL MATERIALS SHALL BEAR IDENTIFICATION SHOWING THE FIRE PERFORMANCE RATING THEREOF AND, IF INTENDED FOR EXTERIOR USE, SHALL BE FURTHER IDENTIFIED TO INDICATE SUITABILITY FOR EXPOSURE TO THE WEATHER. SUCH IDENTIFICATIONS SHALL BE ISSUED BY AN APPROVED L.A. CITY AGENCY HAVING A SERVICE FOR INSPECTION OF MATERIALS AT THE FACTORY.

CONCRETE COLUMNS AT GARAGE LEVELS SEE STRUCTURAL DRAWINGS. AD

AREA DRAIN. SLOPE TO DRAIN 2% MAX

PD

PLANTER/AREA DRAIN. EMERGENCY DRAIN.

ED

F.E.C.

FIRE EXTINGUISHER CABINET - RECESSED AT RESIDENTIAL FLOORS & SURFACE MOUNTED GARAGES (MAX. 75' FROM ANY PORTION OF BUILDING). SEE 0/A900. EXIT SIGN

H.B.

HOSE BIB

KEYNOTES LEGEND NO. 01A32 03A5

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

DESCRIPTION LINE OF VEHICLE TURNING RADIUS, TYP. C.I.P.C. WALL / SHOTCRETE WALL (SEE STRUCT DWGS)

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO. DATE

1501 03-03-2017

2% MAX. SLOPE @ CORRIDORS & BALCONIES

SCALE

DISABLED ACCESS VEHICULAR CLEARANCE 8'-2" MIN. CLEARANCE

SHEET NO.

As indicated

A201


KC1

KC3

KC4

21' - 4"

18' - 11 5/8"

KC6

KC7

KC9

6' - 10" 6' - 11"

KC11

27' - 10"

KC13

26' - 5"

KC15

18' - 1"

KC17

26' - 6"

KC19

26' - 6"

KC21

26' - 6"

KC24

26' - 6"

26' - 6"

KC25

18' - 0"

KC26

10' - 10"

DE Architects AIA

C

C

C

C

26 RES. C

28 RES.

30 RES.

C

C

32 RES. C

34 RES.

36 RES.

C

C

38 RES.

40 RES.

C

42 RES.

C

C

44 RES.

46 RES.

C

48 RES.

C

52 RES.

50 RES.

C

C

54 RES.

C

56 RES.

C

C

21A4

KCM

7 RES.

9 RES.

11 RES.

13 RES.

17 RES.

15 RES.

19 RES.

21 RES.

23 RES.

25 RES.

27 RES.

29 RES.

33 RES.

31 RES.

35 RES.

37 RES.

41 RES.

39 RES.

43 RES.

45 RES.

47 RES.

49 RES.

53 RES.

51 RES.

55 RES.

KCO

57 RES.

STAMP

71 RES.

69 RES.

65 RES.

67 RES.

63 RES.

61 RES.

58 RES.

ED

C

C

C

C

C

C

110 RES.

108 RES.

106 RES.

104 RES.

102 RES.

100 RES.

C

C

96 RES.

98 RES.

C

C

94 RES.

C

90 RES.

92 RES.

C

C

88 RES.

86 RES.

C

84 RES.

C

C

82 RES.

80 RES.

C

78 RES.

C

C

76 RES.

74 RES.

C

72 RES.

C

C

70 RES.

C

68 RES.

66 RES.

C

C

64 RES.

62 RES.

59 RES.

32' - 0"

ED

60 RES.

KCD

VEHICULAR RAMP #1 RAMP UP 10% MAX. SLOPE ED

22 COMM.

C

26' - 6"

26' - 6"

18' - 10"

8' - 3"

KC10

KC12

KC14

KC16

KC18

KC20

26 COMM.

76 COMM. 77 COMM. LCW

18 COMM.

N 0° 16' 36" W 82.66'

12' - 9 1/4"

81 COMM.

15 COMM.

31 COMM.

N 0° 16' 36" W 2.15'

37 COMM.

39 COMM.

43 COMM.

41 COMM.

45 COMM.

82 COMM.

47 COMM.

ED

83 COMM.

32 COMM.

34 COMM.

38 COMM.

36 COMM.

42 COMM.

40 COMM.

44 COMM.

46 COMM.

84 COMM.

49 COMM.

48 COMM.

85 COMM.

7' - 2 3/4"

12 COMM.

57 COMM.

58 COMM.

88 COMM.

61 COMM.

59 COMM.

ED

62 COMM.

ED

5 COMM.

RAMP DOWN 20% MAX. SLOPE

RAMP UP 20% MAX. SLOPE

89 COMM.

63 COMM.

RAMP UP 10% MAX. SLOPE

CARTS

64 COMM. ED

STAIR #1

65 COMM.

4 COMM.

71 COMM.

70 COMM.

69 COMM.

67 COMM.

C

01A32

91 COMM.

N 0° 16' 36" W 160.30'

114 COMM.

113 COMM. 112 COMM.

111 COMM.

110 COMM.

109 COMM.

108 COMM.

107 COMM.

106 COMM.

105 COMM.

104 COMM.

103 COMM.

102 COMM.

101 COMM.

LCB

94 COMM. 100 COMM.

99 COMM.

98 COMM.

97 COMM.

96 COMM.

95 COMM.

16' - 6"

115 COMM.

PL

22' - 6"

SWITCH ABOVE @ GROUND FLOOR

21A4

"

LCC

LCA PROPERTY LINE

N 89° 51' 56" E 286.55'

LC1.1

4 3/8"

LC3

TRANSFORMERS ABOVE @ GROUND FLOOR

LC4

LC9 LC10

15' - 7 7/8"1' - 2 1/8"

32' - 0 7/8"

LC12

LC22

5' - 3" 9' - 6 3/8" 6' - 11"

27' - 7 7/8"

LC14

LC25

14' - 6 1/4"

LC27

12' - 11 3/4"

LC28

16' - 11"

LC29

9' - 9"

LC30

26' - 8"

LC31

26' - 8"

LC32

27' - 6"

8' - 0" DEDICATION

1' - 0"

LCA

CA

0 4' -

EXHAUST SHAFT

CB

" 5/8

93 COMM.

ION AT C I ED "D 0 5'

8 1' -

ED

1 COMM.

ED

8"

ED ED ED

26'

21A4

INE YL RT PE

92 COMM.

ED

ED

CC

90 COMM.

66 COMM.

LCD 2 COMM.

CD

O PR

3 COMM.

68 COMM.

ED

CE

" " 5/8 -8 26'

6 COMM.

VEHICULAR RAMP #2

RAMP DOWN 10% MAX. SLOPE

GREASE INTERCEPTOR

S ET RK OR MA EVAT EL

RAMP DOWN TO RESIDENTIAL PARKING

08D2

CF

2 1' -

15' - 6 3/4"

56 COMM.

CG

/8" 0 1 7/8" 2' 1 -1 14'

55 COMM.

" 3/8

54 COMM.

CH

5 8' -

53 COMM.

AIR ST

52 COMM.

" 3/8

87 COMM.

60 COMM.

C

-6 10'

26' - 8"

C

7 COMM.

19' - 4"

" 5/8

LC23

58' - 9 1/8"

8 COMM.

20' - 0 5/8"

CI

" 3/8

6' - 6 3/4" 24' - 3 1/4"

86 COMM.

ED ED

ED

9 COMM.

3' - 10" 8' - 1 1/4"

0 2' -

10 COMM.

LC16

FUTURE MARKET PARKING 110 STANDARD (INCL. 4 STD ADA, 1 STD VAN ADA) 1 VAN ACCESSIBLE SPACE REQUIRED PER EVERY 8 ACCESSIBLE SPACES PER 1109A.8.6 CBC) 5 COMPACT TOTAL = 115 SPACES ED

-1 16'

ED

LCG

3' - 10 1/2"

CK CJ

11 COMM.

LCE

CM

ED

13 COMM.

LCF

CN

/4" " 83 5/8 2' - 4' - 7 2

23' - 7 1/4"

14 COMM.

35 COMM.

33 COMM.

" " 1/4 7/8 -5 24'

6' - 4 3/4"

44' - 10"

51 50 COMM. COMM.

3' - 5 1/2"

80 COMM.

#6 AIR ST

LCH

CO

9 7' -

26' - 8"

LCJ LCI

LC26

ET RK MA

LCK

28' - 5 1/4"

16 COMM.

LC15

ED

E AG OR ST RT CA

LCM

LC6

ED

CP

ET RK MA

LCN

79 COMM.

17 COMM.

LCQ

RETENTION TANK

ED

01A32

LCR

CQ

78 COMM.

ED

LCS

CR

" 3/4

18' - 2"

KC8

75 COMM.

LCX

LCU 1' - 1 3/4"

KC5

FAN ROOM

-4 14'

KC2

KC23

28 COMM.

19 COMM.

C

CT

" 3/8

KC22

27 COMM.

74 COMM. FRESH AIR INTAKE

21A4

29 COMM.

20 COMM.

LCV KC1

ED

19' - 0"

26' - 6"

25 COMM.

30 COMM.

LCYY

ROLL UP GATE

26' - 6"

25' - 6 1/4"

26' - 6"

21 COMM.

24 COMM.

23 COMM.

STAIR #2

2 1' - 7 3/4"

26' - 6"

73 COMM.

CV

5 4' 8"

28' - 6"

72 COMM.

26'

28' - 1 1/4"

08D2

CW

8"

15' - 9 3/4"

RAMP DOWN 10% MAX. SLOPE

RAMP DOWN 20% MAX. SLOPE

ED

LCY

2 3/4"

RAMP UP 20% MAX. SLOPE

LCXX

26'

LCZ

0" 1' " -0 14' N 89° 50' 37" E 187.34'

PL

KCA AREA RESERVED FOR LINES FROM OTSEGO

C3

C4

607.29'

08D2

MATCHLINE

N 89° 52' 37" W 303.96'

N 89° 52' 31" E 10.00'

LANKERSHIM + otsego

73 RES.

C1

LC33

0 1' -

25' - 9 3/4"

2' - 6 1/4" C3

HVAC, INDOOR LIGHTING AND WATER HEATING ARE NOT WITHIN THE SCOPE OF WORK FOR THIS PHASE OF CONSTRUCTION. COMMISSIONING OF THE HVAC, INDOOR LIGHTING AND WATER HEATING SYSTEMS FOR THE NONRESIDENTIAL SPACES WILL BE REQUIRED AND PERFORMED AT THE INITIAL TENANT IMPROVEMENT PHASE.

C4

'32

15

'14

" '-8

"

SHEET TITLE

0"

P1 GARAGE - KEY PLAN

C2

6"

1

N

P1 GARAGE 1/16" = 1'-0"

C6

P1 PARKING

GENERAL NOTES

RESIDENTIAL PARKING STANDARD COMPACT

-REFER TO SHEET A101 FOR GRADES AND SITE PLAN NOTES NOT CONTAINED IN THIS DRAWING. -LANDSCAPE DESIGN REQUIRES 100% DRIP IRRIGATION WITHIN 5 FT OF BUILDING PERIMETER FOOTING, SPRAY HEADS NOT ALLOWED IN THIS PROJECT. -SEAL EXTERNAL CRACKS, JOINTS ETC. WITH CAULKING AND INSTALL PEST-PROOF SCREENS WHERE REQUIRED.

TOTAL RESIDENTIAL PARKING

57 SPACES 54 SPACES 111 SPACES

FUTURE MARKET PARKING STANDARD (INCL. 5 H/C) COMPACT

110 SPACES 5 SPACES

TOTAL FUTURE MARKET PARKING

115 SPACES

METAL LATH: - ATTACH LATH TO SUPPORTS AT 6" O.C. INSTALL LATH USING HOT-DIP GALVANIZED FASTENERS WITH NEOPRENE WASHERS. INSTALL SCREWS TO ENSURE THAT WASHERS HAS MAXIMUM CONTACT WITH BUILDING PAPER/MEMBRANE WATERPROOFING. SCREWS SHALL PENETRATE THROUGH EXTERIOR PLYWOOD SHEATHING INTO FRAMING. - IF STAPLES ARE USED TO ATTACH LATH, ALL PENETRATIONS SHALL BE CAULKED AND SEALED, TYPICAL.

3/9/2017 2:32:44 PM

FIREPROOFING: -APPLY 1HR CEMENTITIOUS FIREPROOFING (LARR #24763 OR APPROVED EQUAL) APPLY IN LOCATIONS NOTED, OTHERWISE PROVIDE INTUMESCENT COATING. -PROVIDE FIRE SPRINKLER SYSTEM SHALL BE APPROVED BY PLUMBING DIV. PRIOR TO INSTALLATION. 12.21A17(d) -INTUMESCENT COATING, TYPICAL AT ALL STEEL LOCATD WITHIN DWELLING UNITS. PROVIDE 1HR RATING THROUGHOUT, EXCEPT FOR COLUMNS ENCLOSED WITHIN EXTERIOR WALL. PROVIDE 2HR RATING FOR COLUMNS ENCLOSED WITHIN EXTERIOR WALL (LARR #25484 OR APPROVED EQUAL) -SEE STRUCTURAL DWGS FOR RESTRAINED CONSTRUCTION OF STEEL MEMBERS. FIRE PROTECTION: -PROVIDE FIRE SPRINKLER SYSTEM SHALL BE APPROVED BY PLUMBING DIV. PRIOR TO INSTALLATION. 12.21A17(d) - CONTRACTOR SHALL PROVIDE SPRINKLER AT ALL CONCEALED SPACES LARGER THAN 6", PER NFPA13, OR SOLIDLY FILL WITH INSULATION. - INSTALL CONCEALED FIRE SPRINKLERS THROUGHOUT, INT. & EXT.

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

O

1' - 0"

75 RES.

4 7/8"

77 RES.

RAMP UP 10% MAX. SLOPE

79 RES.

21' - 9 3/4"

81 RES.

20' - 9 3/8"

83 RES.

18' - 1"

85 RES.

RAMP DOWN TO RESIDENTIAL PARKING

87 RES.

CA L I F

C2

ROLL UP GATE

89 RES.

91 RES.

N 0° 07' 29" E 0.12' N 89° 50' 37" E 21.11'

20' - 10"

93 RES.

OF

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

C1

KCF

20' - 8"

95 RES.

MATCHLINE

97 RES.

E

CY

GATE RESIDENTIAL ENTRY

99 RES.

REN. 6-30-17

42' - 1 3/8"

1

STAIR #3A

101 RES.

7' - 5 1/4"

"

PL

103 RES.

105 RES.

19' - 5 3/8"

8 1' -

PROPOERTY LINE

SWITCH ABOVE @ GROUND FLOOR

107 RES.

42' - 11 5/8"

6' - 5 1/2" 7' - 8 3/4"

#1 OR T A EV EL

26' - 8 1/8"

109 RES.

4' - 9 5/8"

N 0° 07' 29" W 11.00' 14' - 7 1/8"

ELECTRICAL TRANSFORMER ABOVE @ GROUND FLOOR

N 0° 04' 01" W 100.00'

12' - 0 7/8"

6' - 0 1/8" 11' - 9 5/8"

ED

NO. C-13779

LC24

/8"

3' - 3 1/8" 17' - 0"

ED

ED

LC21

07

4"

ED

LC20

' .04 299 0" 5' 0 6° 4

KCA

8' - 0" DEDICATION

ED

LC18

N2

KCB

ED

LC11

-1 27'

KCC

ED

LC5

T

KCE

RESIDENTIAL PARKING 57 STANDARD 54 COMPACT ED TOTAL = 111 SPACES

LC3

LC2

ST A

36' - 5 1/8"

KCH LC1

CT TE ERIS K

ED A RCH NS S EMP I A TA

KCJ

A

C

24 RES.

NI

C

22 RES.

R

C

20 RES.

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

18 RES.

17' - 6"

C

16 RES.

L IC E DONA

3 RES.

C

14 RES.

KCN

5 RES.

TANK ROOM

1 RES.

STAIR #4

12 RES.

N 0° 02' 11" W 71.52'

C

10 RES. KCQ

C

KCR

PL

C

6 RES.

10' - 7 1/4"

4 RES.

N 89° 52' 51" E 296.34'

8 RES.

17' - 10"

2 RES.

8' - 10 5/8"

FAN ROOM

ELEVATOR #4

19' - 4 3/4"

KCP

PL

11' - 1 1/4"

KCR

14' - 6"

5"

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

INSULATION: -PROVIDE R-25 INSULATION AT 2X8 WALL FRAMING, WHERE IT OCCURS. -WALL INSULATION SHALL FILL & CONTINUOUSLY TOUCH CAVITY ON ALL 6 SIDES - NO AIR GAPS -CEILING/ROOF INSULATION SHALL CONTINUOUSLY TOUCH CAVITY ON 5 SIDES - NO AIR GAPS MATERIALS: - ANNULAR SPACES AROUND PIPES, ELECTRIC CABLES, CONDUITS, OR OTHER OPENINGS IN THE SOLE/BOTTOM PLATES AT EXTERIOR WALLS SHALL BE PROTECTED AGAINST THE PASAGE OF RODENTS BY CLOSING SUCH OPENINGS WITH CEMENT MORTAR, CONCRETE MASONRY, OR METAL PLATES. PIPING PRONE TO CORROSION SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 313.0 OF THE LOS ANGELES PLUMBING CODE. - MATERIALS DELIVERED TO THE CONSTRUCTION SITE SHALL BE PROTECTED FROM RAIN OR OTHER SOURCES OF MOISTURE. MAINTENANCE MANUAL: -AN OPERATION AND MAINTENANCE MANUAL INCLUDING , AT A MINIMUM, THE ITEMS LISTED IN CAL GREEN SECTION 4.410.1, SHALL BE COMPLETED AND PLACED IN THE BUILDING AT THE TIME OF FINAL INSPECTION OUTDOOR LIGHTING SYSTEMS: - OUTDOOR LIGHTING SYSTEMS SHALL BE DESIGNED AND INSTALLED TO COMPLY WITH ALL OF THE FOLLOWING: a) THE MINIMUM REQUIREMENTS IN CALIFORNIA ENERGY CODE FOR LIGHTING ZONES 1-4. b) BACKLIGHT, UPLIGHT AND GLARE (BUG) RATINGS AS DEFINED IN IESNA TM-15-11. (c) ALLOWABLE BUG RATINGS NOT EXCEEDING THOSE SHOWN IN ON TABLE 5.106.8. DISSIMILAR METALS: -PROVIDE RUBBER GASKET AT DISSIMILAR METALS, TYPICAL THROUGHOUT. POOL EQUIPMENT: - POOL EQUIPMENT SHALL BE MOUNTED ON MECHANICAL PADS & ATTACHED WITH SPRING ISOLATORS. REFERENCE SIMILAR DETAIL 4/A909 - PLUMBING LINES SHALL BE RAISED ABOVE ROOF AND ISOLATED WITH RUBBER SUPPORTS, TYPICAL.

ELECTRICAL NOTES: - THE MAIN ELECTRICAL SERVICE PANEL SHALL HAVE A RESERVED SPACE TO ALLOW FOR INSTALLATION OF A DOUBLE POLE CIRCUIT BREAKER FOR A FUTURE SOLAR ELECTRIC INSTALLATION. THE RESERVED SPACE SHALL BE POSITIONED AT THE OPPOSITE (LOAD) END FROM THE INPUT FEEDER LOCATION OR MAIN CIRCUIT LOCATION AND SHALL BE PERMANENTLY MARKED AS ‘FOR FUTURE SOLAR ELECTRIC’. - THE MAIN SERVICE PANEL SHALL HAVE A MINIMUM BUSBAR RATING OF 200 AMPS. - PROVIDE ADEQUATE LIGHTING TO ENSURE SAFE ACCESS TO BICYCLE PARKING FACILITIES IN ACCORDANCE WITH SECTION 12.21A.5(k).

COMMISSIONING: HVAC, INDOOR LIGHTING AND WATER HEATING ARE NOT WITHIN THE SCOPE OF WORK FOR THIS PHASE OF CONSTRUCTION. COMMISSIONING OF THE HVAC, INDOOR LIGHTING AND WATER HEATING SYSTEMS FOR THE NONRESIDENTIAL SPACES WILL BE REQUIRED AND PERFORMED AT THE INITIAL TENANT IMPROVEMENT PHASE.

LEGEND CONCRETE WALL PER STRUCTURAL CMU WALL PER STRUCT. METAL STUD WALL / PARTY-WALL - SOUND WALL STC RATING 50 REQ. / 1HR RATED (REFERENCE WALL TYPE ASSEMBLY) FIRE RATED WALL - 2HR

METAL STUD FRAMING @ P2 - 2ND FLOORS: - METAL STUD FRAMING, TYP. @ TYPE 1 CONSTRUCTION - WOOD FRAMING NOT PERMITTED WOOD CONSTRUCTION @ 3rd - 7th FLOORS: EXTERIOR WALLS TO BE FIRE TREATED WOOD LARR 24502 (SEE FLOOR PLANS): -FIRE-RETARDANT-TREATED WOOD IS LUMBER OR PLYWOOD IMPREGNATED WITH CHEMICALS AND WHICH, WHEN TESTED IN ACCORDANCE WITH U.B.C. STANDARD NO. 42-1 FOR A PERIOD OF 30 MINUTES, SHALL HAVE A FLAME SPREAD OF NOT OVER 25 AND SHOW NO EVIDENCE OF PROGRESSIVE COMBUSTION. MATERIALS WHICH MAY BE EXPOSED TO THE WEATHER SHALL MAINTAIN THIS FIRE-RETARDANT CLASSIFICATION WHEN TESTED IN ACCORDANCE WITH THE RAIN AND WEATHERING TESTS OF U.B.C. STANDARD NO. 32-7. -ALL MATERIALS SHALL BEAR IDENTIFICATION SHOWING THE FIRE PERFORMANCE RATING THEREOF AND, IF INTENDED FOR EXTERIOR USE, SHALL BE FURTHER IDENTIFIED TO INDICATE SUITABILITY FOR EXPOSURE TO THE WEATHER. SUCH IDENTIFICATIONS SHALL BE ISSUED BY AN APPROVED L.A. CITY AGENCY HAVING A SERVICE FOR INSPECTION OF MATERIALS AT THE FACTORY.

CONCRETE COLUMNS AT GARAGE LEVELS SEE STRUCTURAL DRAWINGS. AD

AREA DRAIN. SLOPE TO DRAIN 2% MAX

PD

PLANTER/AREA DRAIN. EMERGENCY DRAIN.

ED

F.E.C.

FIRE EXTINGUISHER CABINET - RECESSED AT RESIDENTIAL FLOORS & SURFACE MOUNTED GARAGES (MAX. 75' FROM ANY PORTION OF BUILDING). SEE 0/A900.

KEYNOTES LEGEND NO. 01A32 03A5 08D2 21A4

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

DESCRIPTION LINE OF VEHICLE TURNING RADIUS, TYP. C.I.P.C. WALL / SHOTCRETE WALL (SEE STRUCT DWGS) ROLL UP GATE - RESIDENTIAL PARKING ENTRY WET STANDPIPE. 12" MAX. PROTRUSION FOR POST-MOUNTED OBJECTS, 4" MAX. PROJECTION FOR PROTRUSIONS FROM WALL, OR PROVIDE CANE DETECTION AT THESE LOCATIONS.

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO.

1501

EXIT SIGN H.B.

HOSE BIB

DATE

03-03-2017

2% MAX. SLOPE @ CORRIDORS & BALCONIES

SCALE

DISABLED ACCESS VEHICULAR CLEARANCE 8'-2" MIN. CLEARANCE

SHEET NO.

As indicated

A202


KC1

KC3

KC4

21' - 4"

18' - 11 5/8"

KC6

KC7

KC9

6' - 10" 6' - 11"

KC11

27' - 10"

26' - 5"

KC13

KC15

18' - 1"

KC17

26' - 6"

KC19

26' - 6"

KC21

26' - 6"

KC24

26' - 6"

KC25

26' - 6"

18' - 0"

KC26

10' - 10"

6"

DE Architects AIA 1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

EXISTING FOUR STORY PARKING GARAGE

10 RES.

14 RES.

12 RES.

16 RES.

18 RES.

20 RES.

22 RES.

24 RES.

26 RES.

28 RES.

32 RES.

30 RES.

34 RES.

38 RES.

36 RES.

40 RES.

42 RES.

SEE 2/A635

7 A711

ED

ED

ED

ED

ED

21A4

PD

AD

56 RES.

55 RES.

54 RES.

53 RES.

52 RES.

51 RES.

50 RES.

49 RES.

48 RES.

47 RES.

46 RES.

45 RES.

44 RES.

43 RES.

PD 4' - 2"

57 RES.

3' - 8"

AD

17' - 7"

N 0° 07' 29" E 0.12' N 89° 50' 37" E 21.11' N 89° 52' 31" E 10.00'

AD

" -8 15' PL

PD

PD

PD

PD

PD

PD

PD

PD

PD

AD

21A4

2

26' - 6"

26' - 6"

18' - 10"

8' - 3"

ED

FAN ROOM

15 RES.

LANKERSHIM MAIN LOBBY

18 RES.

AD

PARCELS

2% OX N K X BO

21A8

SEE 3/A631

RES. TRASH #2 AD

KC22

KC23

14 RES.

N 0° 16' 36" W 82.66'

6' - 4 3/4"

12' - 9 1/4"

N 0° 16' 36" W 2.15'

19' - 3"

AD

9 RES.

7' - 2 3/4"

8 RES. 12A8.1

24' - 3 1/4"

7 RES.

AD

AD

LC16

6' - 6 3/4"

5 RES.

8' - 1 1/4"

4 RES.

LC23

58' - 9 1/8"

6 RES.

26' - 8" 1 A711

AD

AD

Sim

BATHROOM SHOWN FOR REFERENCE ONLY CORE & SHELL ONLY)

AD

RAMP DOWN

AD

AD

CORE AND SHELL ONLY HVAC, INDOOR LIGHTING AND WATER HEATING ARE NOT WITHIN THE SCOPE OF WORK FOR THIS PHASE OF CONSTRUCTION. COMMISSIONING OF THE HVAC, INDOOR LIGHTING AND WATER HEATING SYSTEMS FOR THE NONRESIDENTIAL SPACES WILL BE REQUIRED AND PERFORMED AT THE INITIAL TENANT IMPROVEMENT PHASE.

AD

23D6

CC

2%

PE LO .S X MA

55' - 7 1/2"

5' - 2 3/8" 3' - 0"

0"- 2" 3' - 7'

LCB

PD

AD AD

27A2

3' - 0"

5' - 0"

3' - 0"

LCA 8' x 10' TRANSFORMER. PLANTING REQUIRED AROUND TRANSFORMER.

PLANTING REQUIRED AROUND SWITCH.

7' x 11' SWITCH

N 89° 51' 56" E 286.55' RESIDENTIAL/COMMERCIAL ENTRANCE AND EXIT COMMERCIAL TRUCK ENTRANCE ONLY

3' - 0"

34' - 0"

0"

PL

AD

PD 3' - 0"

1' - 0"

AD AD

'15

N 0° 16' 36" W 160.30'

GAS METERS

20' - 0 5/8" 6' - 0"

PL TO RB CU

FAN ROOM

32P4

4' - 0"

" '-0

E OP SL X. MA

16' - 6"

4' - 0"

15

2%

LCA

SEE 1/A631

617.91' POINT OF LOWEST ADJACENT GRADE PER SURVEY

12A7.4

OTSEGO STREET

3' - 0"

NEW DRIVEWAY

PROPERTY LINE 15' - 0"

C1 ° 26.62

0 1' '14

4 3/8" 16' - 10"

LC1.1

32' - 0 7/8"

LC4

° 26.62

LCB

AD

LOBBY #2

" 3/4

LCC

CB

8 5' -

DIRT BELOW

AD

0" 5' -

ION AT C I D DE

8"

INE YL RT PE

LANKERSHIM - LOBBY #2 LEASING OFFICE MEZZANINE 2 1/16" = 1'-0"

ELECT. ROOM

22B1.1

GENERAL CONTRACTOR TO COORD. EXACT LOC. OF DRAINS WITH TENANT

26'

O PR

AD

AD

LEASING OFFICE MEZZANINE ABOVE

CD

23D6

AD

LCD 4' - 4"

CE

" 5/8 ' - 8" 26

19' - 4"

CF

FUTURE MARKET

SHAFT OPENING OVERHEAD

08D2

ENTRY GATE OPEN DURING BUSINESS HOURS

01A12

CG

VEHICULAR RAMP #2

ED

ELECTRICAL RM.

CH

AD

LCE LC14

CI

2 1' -

RESIDENTIAL PARKING 18 STANDARD (INCL. 4 STD ADA AND 1 STD VAN ADA) 1 VAN ADA SPACE REQUIRED PER EVERY 8 ADA SPACES PER 1109A.8.6 CBC) 0 COMPACT TOTAL = 18 SPACES

2 RES.

1 A646

AD

AD

RESIDENTIAL TRASH #1

ED ED

3 RES.

15' - 6 3/4"

3' - 10"

ED

1 RES. 3' - 10 1/2"

CJ

/8" 01 " 2' - 1 7/8 -1 14'

3' - 5 1/2"

AD

CK

AD

LCF

LC12

2%

E OP SL X. A M

" 3/8 " 3/8

ELEVATOR #2

ED

5 8' -

LCG

AD

#1 OR AT EV EL

LCE

CL

-6 10'

LEASING OFFICE MEZZANINE SEE 1/A629

CM

/8" 03 " 2' 5/8 -1 16'

LCH

DN

/4" " 31 1/2 6' -4 18'

4' - 4 1/4"

10 RES.

AD

AD

LOADING DOCK

SCISSOR LIFT WITH PIT BELOW BY LANDLORD AND OPERATIONABLE PER EXHIBIT 'E'

CN

" 3/4

LCI

2%

AD

8 2' " 1/4

11 RES.

PE LO .S X MA

/8" 75

LCF

ED

'53

LCJ

AD

UP

12 RES.

CO

-5 24'

LCK

LINE OF BUILDING ABOVE

4 A711

" 7/8

LCH

LOADING AREA

44' - 10"

ED

LCP

LCM

26' - 8"ED

9 7' -

LCQ

28' - 5 1/4"

LC26

ED

#5 AIR ST

LCR

LC15

"

13 RES.

LCS

LCN

LC6

CP

/8"

LCU

GATE

KC20

19' - 0"

KC18

ELEVATOR #2

KC16

STAIR #1

KC14

RESIDENTIAL & COMMERCIAL ENTRY/EXIT

KC12

1' - 1 3/4" 18' - 2"

KC10

01

KC8

" 1/2

0 3' -

KC5

-8 17'

GATE

-1 18'

LCV

Y WA

COLD STORAGE

CR

0"

KC1

UP

E OP SL X. A 21A6 M

N AN

ELECTRICAL

CT

IVE DR

LCW

17 RES.

16 RES.

7' - 0 1/4" 18' - 1"

26' - 6"

AD

MAIL

5"

26' - 6"

AD

D AR

26' - 6"

23A12

8"

26' - 6"

12A7.3

30'

28' - 6"

RESIDENTIAL & COMMERCIAL ENTRY/EXIT

CV

W NE

43' - 11"

LCX

RAMP DOWN

5' - 3" 9' - 6 3/8"

LC9 LC10

LC12

34' - 6 7/8"

14' - 6 1/4"

LC22

12' - 11 3/4"

LC25

16' - 11"

LC27

9' - 9"

LC28

26' - 8"

LC29

26' - 8"

LC30

1

27' - 6"

2' - 6 1/4" " '-8 15

25' - 9 3/4"

LC31

LC32

LC33 '32

GROUND FLOOR PLAN 1/16" = 1'-0"

"

0"

C2

GENERAL NOTES

RESIDENTIAL PARKING TOTAL STANDARD (INCL. 9 H/C) TOTAL COMPACT

63 SPACES 21 SPACES

TOTAL RESIDENTIAL PARKING

84 SPACES

-REFER TO SHEET A101 FOR GRADES AND SITE PLAN NOTES NOT CONTAINED IN THIS DRAWING. -LANDSCAPE DESIGN REQUIRES 100% DRIP IRRIGATION WITHIN 5 FT OF BUILDING PERIMETER FOOTING, SPRAY HEADS NOT ALLOWED IN THIS PROJECT. -SEAL EXTERNAL CRACKS, JOINTS ETC. WITH CAULKING AND INSTALL PEST-PROOF SCREENS WHERE REQUIRED.

METAL LATH: - ATTACH LATH TO SUPPORTS AT 6" O.C. INSTALL LATH USING HOT-DIP GALVANIZED FASTENERS WITH NEOPRENE WASHERS. INSTALL SCREWS TO ENSURE THAT WASHERS HAS MAXIMUM CONTACT WITH BUILDING PAPER/MEMBRANE WATERPROOFING. SCREWS SHALL PENETRATE THROUGH EXTERIOR PLYWOOD SHEATHING INTO FRAMING. - IF STAPLES ARE USED TO ATTACH LATH, ALL PENETRATIONS SHALL BE CAULKED AND SEALED, TYPICAL.

3/9/2017 2:33:01 PM

FIREPROOFING: -APPLY 1HR CEMENTITIOUS FIREPROOFING (LARR #24763 OR APPROVED EQUAL) APPLY IN LOCATIONS NOTED, OTHERWISE PROVIDE INTUMESCENT COATING. -PROVIDE FIRE SPRINKLER SYSTEM SHALL BE APPROVED BY PLUMBING DIV. PRIOR TO INSTALLATION. 12.21A17(d) -INTUMESCENT COATING, TYPICAL AT ALL STEEL LOCATD WITHIN DWELLING UNITS. PROVIDE 1HR RATING THROUGHOUT, EXCEPT FOR COLUMNS ENCLOSED WITHIN EXTERIOR WALL. PROVIDE 2HR RATING FOR COLUMNS ENCLOSED WITHIN EXTERIOR WALL (LARR #25484 OR APPROVED EQUAL) -SEE STRUCTURAL DWGS FOR RESTRAINED CONSTRUCTION OF STEEL MEMBERS. FIRE PROTECTION: -PROVIDE FIRE SPRINKLER SYSTEM SHALL BE APPROVED BY PLUMBING DIV. PRIOR TO INSTALLATION. 12.21A17(d) - CONTRACTOR SHALL PROVIDE SPRINKLER AT ALL CONCEALED SPACES LARGER THAN 6", PER NFPA13, OR SOLIDLY FILL WITH INSULATION. - INSTALL CONCEALED FIRE SPRINKLERS THROUGHOUT, INT. & EXT.

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

INSULATION: -PROVIDE R-25 INSULATION AT 2X8 WALL FRAMING, WHERE IT OCCURS. -WALL INSULATION SHALL FILL & CONTINUOUSLY TOUCH CAVITY ON ALL 6 SIDES - NO AIR GAPS -CEILING/ROOF INSULATION SHALL CONTINUOUSLY TOUCH CAVITY ON 5 SIDES - NO AIR GAPS MATERIALS: - ANNULAR SPACES AROUND PIPES, ELECTRIC CABLES, CONDUITS, OR OTHER OPENINGS IN THE SOLE/BOTTOM PLATES AT EXTERIOR WALLS SHALL BE PROTECTED AGAINST THE PASAGE OF RODENTS BY CLOSING SUCH OPENINGS WITH CEMENT MORTAR, CONCRETE MASONRY, OR METAL PLATES. PIPING PRONE TO CORROSION SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 313.0 OF THE LOS ANGELES PLUMBING CODE. - MATERIALS DELIVERED TO THE CONSTRUCTION SITE SHALL BE PROTECTED FROM RAIN OR OTHER SOURCES OF MOISTURE. MAINTENANCE MANUAL: -AN OPERATION AND MAINTENANCE MANUAL INCLUDING , AT A MINIMUM, THE ITEMS LISTED IN CAL GREEN SECTION 4.410.1, SHALL BE COMPLETED AND PLACED IN THE BUILDING AT THE TIME OF FINAL INSPECTION OUTDOOR LIGHTING SYSTEMS: - OUTDOOR LIGHTING SYSTEMS SHALL BE DESIGNED AND INSTALLED TO COMPLY WITH ALL OF THE FOLLOWING: a) THE MINIMUM REQUIREMENTS IN CALIFORNIA ENERGY CODE FOR LIGHTING ZONES 1-4. b) BACKLIGHT, UPLIGHT AND GLARE (BUG) RATINGS AS DEFINED IN IESNA TM-15-11. (c) ALLOWABLE BUG RATINGS NOT EXCEEDING THOSE SHOWN IN ON TABLE 5.106.8. DISSIMILAR METALS: -PROVIDE RUBBER GASKET AT DISSIMILAR METALS, TYPICAL THROUGHOUT. POOL EQUIPMENT: - POOL EQUIPMENT SHALL BE MOUNTED ON MECHANICAL PADS & ATTACHED WITH SPRING ISOLATORS. REFERENCE SIMILAR DETAIL 4/A909 - PLUMBING LINES SHALL BE RAISED ABOVE ROOF AND ISOLATED WITH RUBBER SUPPORTS, TYPICAL.

ELECTRICAL NOTES: - THE MAIN ELECTRICAL SERVICE PANEL SHALL HAVE A RESERVED SPACE TO ALLOW FOR INSTALLATION OF A DOUBLE POLE CIRCUIT BREAKER FOR A FUTURE SOLAR ELECTRIC INSTALLATION. THE RESERVED SPACE SHALL BE POSITIONED AT THE OPPOSITE (LOAD) END FROM THE INPUT FEEDER LOCATION OR MAIN CIRCUIT LOCATION AND SHALL BE PERMANENTLY MARKED AS ‘FOR FUTURE SOLAR ELECTRIC’. - THE MAIN SERVICE PANEL SHALL HAVE A MINIMUM BUSBAR RATING OF 200 AMPS. - PROVIDE ADEQUATE LIGHTING TO ENSURE SAFE ACCESS TO BICYCLE PARKING FACILITIES IN ACCORDANCE WITH SECTION 12.21A.5(k).

COMMISSIONING: HVAC, INDOOR LIGHTING AND WATER HEATING ARE NOT WITHIN THE SCOPE OF WORK FOR THIS PHASE OF CONSTRUCTION. COMMISSIONING OF THE HVAC, INDOOR LIGHTING AND WATER HEATING SYSTEMS FOR THE NONRESIDENTIAL SPACES WILL BE REQUIRED AND PERFORMED AT THE INITIAL TENANT IMPROVEMENT PHASE.

LEGEND CONCRETE WALL PER STRUCTURAL CMU WALL PER STRUCT. METAL STUD WALL / PARTY-WALL - SOUND WALL STC RATING 50 REQ. / 1HR RATED (REFERENCE WALL TYPE ASSEMBLY) FIRE RATED WALL - 2HR CONCRETE COLUMNS AT GARAGE LEVELS SEE STRUCTURAL DRAWINGS.

12A7.1

AD

AREA DRAIN. SLOPE TO DRAIN 2% MAX

12A7.2

PD

PLANTER/AREA DRAIN. EMERGENCY DRAIN.

METAL STUD FRAMING @ P2 - 2ND FLOORS: - METAL STUD FRAMING, TYP. @ TYPE 1 CONSTRUCTION - WOOD FRAMING NOT PERMITTED WOOD CONSTRUCTION @ 3rd - 7th FLOORS: EXTERIOR WALLS TO BE FIRE TREATED WOOD LARR 24502 (SEE FLOOR PLANS): -FIRE-RETARDANT-TREATED WOOD IS LUMBER OR PLYWOOD IMPREGNATED WITH CHEMICALS AND WHICH, WHEN TESTED IN ACCORDANCE WITH U.B.C. STANDARD NO. 42-1 FOR A PERIOD OF 30 MINUTES, SHALL HAVE A FLAME SPREAD OF NOT OVER 25 AND SHOW NO EVIDENCE OF PROGRESSIVE COMBUSTION. MATERIALS WHICH MAY BE EXPOSED TO THE WEATHER SHALL MAINTAIN THIS FIRE-RETARDANT CLASSIFICATION WHEN TESTED IN ACCORDANCE WITH THE RAIN AND WEATHERING TESTS OF U.B.C. STANDARD NO. 32-7. -ALL MATERIALS SHALL BEAR IDENTIFICATION SHOWING THE FIRE PERFORMANCE RATING THEREOF AND, IF INTENDED FOR EXTERIOR USE, SHALL BE FURTHER IDENTIFIED TO INDICATE SUITABILITY FOR EXPOSURE TO THE WEATHER. SUCH IDENTIFICATIONS SHALL BE ISSUED BY AN APPROVED L.A. CITY AGENCY HAVING A SERVICE FOR INSPECTION OF MATERIALS AT THE FACTORY.

01A8 01A12 01A33 08D2 11F1

C4

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

ED

F.E.C.

FIRE EXTINGUISHER CABINET - RECESSED AT RESIDENTIAL FLOORS & SURFACE MOUNTED GARAGES (MAX. 75' FROM ANY PORTION OF BUILDING). SEE 0/A900. EXIT SIGN

H.B.

HOSE BIB 2% MAX. SLOPE @ CORRIDORS & BALCONIES DISABLED ACCESS VEHICULAR CLEARANCE 8'-2" MIN. CLEARANCE

12A7.3

12A7.4

12A8.1

DESCRIPTION LINE OF FLOOR / STRUCTURE ABOVE LINE OF FLOOR / STRUCTURE BELOW PROPERTY LINE WALL ROLL UP GATE - RESIDENTIAL PARKING ENTRY KNOX BOX KNOX KEY SWITCH 3500 SERIES (SINGLE SWITCH MODEL 3502) BICYCLE DOCK ARRAY OF 3 SHORT TERM RESIDENTIAL BICYCLE PARKING (MANUF: SARIS BIKE DOCK OR APPROVED EQ.) BICYCLE DOCK ARRAY OF 8 SHORT TERM RESIDENTIAL BICYCLE PARKING (MANUF: SARIS BIKE DOCK OR APPROVED EQ.) BICYCLE DOCK ARRAY OF 9 SHORT TERM RESIDENTIAL BICYCLE PARKING (MANUF: SARIS BIKE DOCK OR APPROVED EQ.) BICYCLE DOCK ARRAY OF 11 SHORT TERM RESIDENTIAL BICYCLE PARKING (MANUF: SARIS BIKE DOCK OR APPROVED EQ.) BICYCLE LOCKER ARRAY OF 13 LONG TERM COMMERCIAL BICYCLE PARKING. ACCEPTABLE PARKING FACILITIES INCLUDE: I. COVERED, LOCKABLE ENCLOSURE WITH PERMANENTLY ANCHORED RACKS FOR BICYCLE; II. LOCABLE BICYCLE ROOMS WITH PERMANENTLY ANCHORED RACKS; and III. LOCABLE, PERMANENTLY ANCHORED BICYCLE LOCKERS. (MANUF: PARKABIKE - BIKE LOCKER OR APPROVED EQ.)

GROUND FLOOR PLAN - KEY PLAN

N

6"

KEYNOTES LEGEND NO.

SHEET TITLE

C3

C6

GROUND FLOOR PARKING

O

CW

26'

0.13° FROM PL

VEHICULAR RAMP #1

LCYY

LCY EXISTING FOUR STORY BUILDING

81' - 3 1/4"

CA L I F

EV UL BO

LCZ

EXISTING TWO STORY BUILDING

UP

LCXX

8"

LCZZ

22B1

242 BICYCLES SEE 1/A635

0"

OF

HIM RS

01A8

E

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

26'

N 89° 52' 37" W 303.96'

BICYCLE ROOM

"

N 89° 50' 37" E 187.34'

20' - 8"

AD

MATCHLINE

3' - 8"

PD

14'

C4

ENTRY GATE OPEN DURING BUSINESS HOURS

AD

0 1' -

C3

08D2

AD

47' - 8 1/2"

LCXX

AD PD

7' - 5 1/4"

C1

21' - 9 3/4"

AD

7' - 8 3/4"

C2

PROPOSED DOG RUN

AD

REN. 6-30-17

6' - 5 1/2"

18' - 5"

PD AD

2 3/4"

25' - 4 5/8"

ELECTRICAL AD

PL

4' - 9 5/8"

PD AD

7 x 11 SWITCH

1' - 0 3/8"

7' - 11 1/2"

PD

3' - 0"

PROPERTY LINE

N 0° 04' 01" W 100.00'

58 RES.

STAIR #3A

3' - 0"

3' - 0" 15' - 0"

59 RES.

LC24

1

BIKE MAINT.

4' - 0"

CURB TO PL

4"

60 RES.

LC21

" -0 Y 3' WA IVE DR N 0" 1/4" NSIO -3 E 3' 11' EXT

KCA

61 RES.

LC20

E NK LA

20' - 3 1/8"

CL STREET TO CURB

13' - 0"

62 RES.

63 RES.

LC18

LC13

IF ,V NT 8" 1' -

20' - 0"

64 RES.

LC11

LC7

A DR HY IRE OF "T 3/8

PLANTING REQUIRED AROUND TRANSFORMER/ SWITCH

3' - 10 1/8"

SEE 3/A635

65 RES.

LC5

6' - 0 1/8"

AD

16 BICYCLES

66 RES.

LC3

"

8 x 10 TRANSORMER

NO. C-13779

21A7.1

" -0 47' AY EW RIV IES GD RT TIN PE O XIS R P "E ' 3/4 G2 .04 -8 VIN 299 35' ER 0" HS 5' 0 DT 6° 4 WI N2

KCC

8' - 0" DEDICATION

LC1.2 LC2

EXISTING FOUR STORY BUILDING

PD

ED

ED

LC1

ED A RCH NS S EMP I A TA

-7 78'

RESIDENTIAL PARKING 45 STANDARD (INCL. 3 STD ADA AND 1 STD VAN ADA) 1 VAN ADA SPACE REQUIRED PER EVERY 8 ADA SPACES PER 1109A.8.6 CBC) 21 COMPACT TOTAL = 66 SPACES

PD

3' - 0"

KCJ

STAIR #3B

21A4

KCF

4"

PD

A

8 RES.

AD

08D2 RESIDENTIAL GATE

6 RES.

LANKERSHIM + otsego

AD

4 RES.

STAMP

63 .38 °

AD

2 RES.

40 BICYCLES

16' - 6"

EXHAUST SHAFT

KCO

NI

AD RES. TRASH #3

R

AD

C

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

C

L IC E DONA

C

1' - 0"

C

63 .38 °

AD

CURB TO PL

C

CL STREET TO CURB

C

13' - 0"

AD

C

20' - 0"

C

8' - 0" DEDICATION

C

PD

4 7/8"

C

41 RES.

6' - 5 5/8"

AD

C

37 39 RES. AD RES.

35 RES.

ELEVATOR #3

C

33 RES.

STAIR #2

AD

C

31 RES.

17' - 6"

C

29 RES.

BICYCLE ROOM

PD

NEW DRIVEWAY

C

25 27 RES. AD RES.

CT TE ERIS K

3' - 0"

C

23 RES.

T

30' - 0"

C

21 RES.

+/-

KLUMP AVENUE

C

19 RES.

N 0° 07' 29" W 11.00'

KNOX BOX

STAIR #4

KLUMP LOBBY SEE 1/A634

20' - 0"

AD

17 RES.

0 3' -

26' - 8 1/8"

PARCELS

21A6

C

13 15 RES. AD RES.

9 11 RES. AD RES.

ST A

6' - 9 7/8"

12A7.1

C

7 RES.

PD

AD

AD

5 RES.

UP

ANN

27A1

3 RES.

1' - 7 3/4" 3' - 0 5/8"

11' - 0 1/8"

8' - 4 5/8"

11F1

KCH

AD

C MAIL

KCM

1 RES.

PD

PD

PD

KCN

PD

14' - 6"

AD

AD

PL

12A7.2

KCR N 0° 02' 11" W 71.52'

AD

N 89° 52' 51" E 296.34'

4' - 8"

KCP

23A13

ELEVATOR #4

6"

KCQ

10' - 7 1/4"

PL

KCR

MATCHLINE

5"

21A4

NO. 21A4

21A6 21A7.1 21A8 22B1 22B1.1 23A12

23A13

23D6 27A1 27A2 32P4

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

DESCRIPTION WET STANDPIPE. 12" MAX. PROTRUSION FOR POST-MOUNTED OBJECTS, 4" MAX. PROJECTION FOR PROTRUSIONS FROM WALL, OR PROVIDE CANE DETECTION AT THESE LOCATIONS. FIRE DEPARTMENT CONNECTION (FDC) (E) FIRE HYDRANT FIRE COMMUNICATION PANEL UTILITY GAS METER (REF. PLUMBING DWGS.) UTILITY GAS METER STACKED (REF. PLUMBING DWGS.) MECHANICAL FRESH AIR INTAKE - RUSKIN ELF375DX ALUMINUM OR APPROVED EQ. - 43% FREE OPENING (REF. MECH. DWGS.) MECHANICAL FRESH AIR INTAKE WITHIN PLANTER PROVIDE McNICHOLS BAR GRATING, GALV. OR APPROVED EQ.CONTRATOR TO PROVIDE 1 1/2"x1 1/2"x1/4" GALV.STEEL ANGLES,@ PERIMETER FOR ATTACHMENT. SMOKE DAMPER (REF. MECH. DWGS.) RESIDENT INTERCOM RECESSED IN WALL FREESTANDING RESIDENT INTERCOM BOLLARD

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO. DATE SCALE

1501 03-03-2017 As indicated

SHEET NO.

A203


KC3

KC4

KC6

KC7

KC9

KC11

KC13

KC15

KC17

KC19

KC21

KC24

PROJECT OVERALL UNIT MIX: SECOND FLOOR OVERALL 0 BD 8 UNITS 1 BD 33 UNITS 2BD 7 UNITS TOTAL 48 UNITS

KC25

296' - 2 5/8"

6' - 11" 18' - 11 5/8"

6' - 10"

27' - 10"

26' - 5"

18' - 1"

26' - 6"

26' - 6"

26' - 6"

26' - 6"

26' - 6"

EXISTING BUILDING

18' - 0"

11' - 4"

THIRD FLOOR OVERALL 0BD 7 UNITS 1BD 32 UNITS 2 BD 14 UNITS TOTAL 53 UNITS

EXISTING BUILDING

TOP OF PARAPET 46'-0" (31' - 0" ABOVE PODIUM)

TOP OF PARAPET +/- 65'-0" (50' - 0" ABOVE PODIUM)

EXISTING FOUR STORY PARKING GARAGE

6' - 4 3/4" 6" 11' - 0 1/4"

TOP OF PARAPET 46'-0" (31' - 0" ABOVE PODIUM)

AD

AD

AD

AD

AD

AD

ED A RCH NS S EMP I A TA

KCO

ADPD

PDAD AD

UNIT: TYPE: SHEET:

K206 K-A3 A622

UNIT: TYPE: SHEET:

K208 K-A A622

K210 UNIT: TYPE: K-A SIM1 SHEET: A622

K212 UNIT: TYPE: K-A SIM2 SHEET: A622

K214 UNIT: TYPE: K-A SIM3 SHEET: A622

UNIT: TYPE: SHEET:

K216 K-M A627

L IC E DONA

K204 K-A4 A622

21A10

NO. C-13779

COURTYARD #3

TRASH

KCJ

REN. 6-30-17

E

T

ELEVATOR #4

21A4

UNIT: TYPE: SHEET:

SEE 2/A631 AD AD

AD

(1 - HR CORRIDOR)

PD

26' - 8 1/8"

UNIT: TYPE: SHEET:

K201 K-J A626

AD

LC1

UP STAIR #3B

PD

LC3 LC5

LC1.2 LC2

21A4 AD

(1 - HR CORRIDOR)

AD

AD

AD

AD 633.42'

6' - 0 1/8" 7' - 11 1/2"

3' - 10 1/8"

LC6

LC7

LC11

LC15

LC17

LC18 LC20

LC21

1' - 9" 23' - 7 5/8"

3' - 10 1/8" 7' - 4" 8' - 3 1/4"

17' - 7"

6' - 5 1/2" 7' - 8 3/4"

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

11' - 1 1/8" 7' - 5 1/4"

36' - 7 3/8"

PD

C1

KCF

UNIT: TYPE: SHEET:

K207 K-A2 A623

K209 K-A1 A623

K211 UNIT: TYPE: K-A1 SIM1 SHEET: A623

UNIT: TYPE: SHEET:

K213 UNIT: TYPE: K-A1 SIM2 SHEET: A623

K215 K-H A626

UNIT: TYPE: SHEET:

K217 K-B A623 AD

PD

07D9

PD

PD

KCD AD AD

SWITCH BELOW

633.42'

AD 633.42'

28' - 6"

26' - 6"

26' - 6"

26' - 6"

26' - 6"

26' - 6"

3' - 0 5/8" 9' - 0 3/4"

LCW

26' - 6"

AD AD

636.42'

AD

UNIT: TYPE: SHEET:

RAMP DN

PD

YOGA STUDIO

FITNESS CENTER

KC10

636.42'

PD

SEE 3/A630

DN 21A4

DN

KC12

KC14

KC16

KC18

KC20

DN 638.42'

DN

21A4

AD

AD

AD

PD

PD PD

AD PD

4' - 4 1/4" 19' - 3" 7' - 2 3/4"

(1 - HR CORRIDOR)

AD

AD AD

UNIT: TYPE: SHEET:

AD

L208 L-A1 A601

AD

PD

AD

AD

COURTYARD #1

UNIT: TYPE: SHEET:

PD PD

SEE 1/A631

AD AD

AD

PD

LOUNGE

PD

SEE 2/A632 UNIT: TYPE: SHEET:

SEE 2/A631

L206 L-ZC A619

AD

PD

AD

AD

PD

PD AD

AD

21A4

AD

AD

AD

BUSINESS

PD

AD

AD

SEE 1/A632

L221 UNIT: TYPE: L-A3 sim 3 SHEET: A602

ELEVATOR #2

STAIR #1

DN

L228 L-ZF A620

UNIT: TYPE: SHEET:

AD

L226 L-C A604

UNIT: TYPE: SHEET:

GREASE EXHAUST DUCT (UP TO ROOF)

DOG WASH

UNIT: TYPE: SHEET:

CB

L222 L-A4 A603

CA

(1 - HR CORRIDOR) AD

8 1' -

21A4

6' - 3"

PD

AD

SEE 1/A632

8"

21A4

AD

AD

" 5/8

L202 L-B A604

L230 L-ZE A619

UNIT: TYPE: SHEET:

AD

CC

26'

23' - 11 1/8"

PD

PD

638.42'

LCC

PD

AD

PD

AD

AD

8"

3' - 5 1/2" 19' - 4"

L204 L-ZD A619

L203 UNIT: TYPE: L-A2 sim 1 SHEET: A601

UNIT: TYPE: SHEET:

AD

PD

AD

PD

PD AD

L205 L-A2 A601

PD

AD

CD

26'

AD

AD

L220 UNIT: TYPE: L-A3 sim 4 SHEET: A602

AD

UNIT: TYPE: SHEET:

UNIT: TYPE: SHEET: AD

CF

" 1/2

AD

CH

-2 16'

AD WALKWAY

PD

L219 L-A5 A603

PD

PD

PD

CI

" 1/2

8' - 1 1/4" 6' - 6 3/4" 15' - 6 3/4" 3' - 10"

AD

PD

TRASH

9' - 5 3/8" 14' - 9 7/8"

AD

5 0' "1 3/8

AD

AD

08B3

-6 10'

AD

L207 L-ZB A619

UNIT: TYPE: SHEET:

AD

PD

" 5/8

245' - 1 5/8"

AD

'-1 "16 3/8

PD

PD

PD

LCE

AD

PD

PD

LCF

PD

AD

CJ

PD

AD #2 RD YA T 31 UR /A6 CO AD E4 E S PD

0 2' -

AD PD

1"

LCG

PD

L209 L-N1 A613

UNIT: TYPE: SHEET:

CK

" 5/8

LCH

AD

AD

) OR RID OR RC -H

LCI

AD

AD

AD

'255

AD

AD

AD DN

-7 24'

AD PD

L210 L-A A601

" 3/4

UNIT: TYPE: SHEET:

PD

PD

L217 L-A6 A604

UNIT: TYPE: SHEET: PD

STAIR #5

AD

AD

PD

CM

21A4 PD

CN

(1

LCJ

AD

PD

AD

LCK

L218 UNIT: TYPE: L-A3 sim 5 SHEET: A602

8 2' -

LCM

AD

" 1/4

12' - 9 1/4" 6' - 4 3/4"

PD

PD

LCL

AD

AD

LCN

L215 L-ZH A620

UNIT: TYPE: SHEET:

AD

-5 24'

L212 UNIT: TYPE: L-A sim1 SHEET: A601

CO

" 7/8

L211 L-N A613

UNIT: TYPE: SHEET:

AD

) OR RID OR RC -H

AD

AD

(1

PD PD

LCP

L213 UNIT: TYPE: L-ZH SIM1 SHEET: A620

PD

CP 9 7' -

AD

PD

LCQ

L216 UNIT: TYPE: L-A3 sim 6 SHEET: A602

AD

AD

AD

CR

AD

638.42'

LCS

LCR

L214 L-Q A614 AD

636.42'

CS

/8"

LCT

CT

(1 - HR CORRIDOR)

LCU 5' - 0 1/4" 13' - 1 3/4"

KC8

AD

AD

01

KC5

23A10 23A12

AD

CU

-1 18'

KC2

SEE 3/A630

PD

231' - 7 3/4"

LCV

LINE OF BUILDING ABOVE

AD

OUTDOOR FITNESS

AD

AD

1' - 6 3/4" 1' - 7 3/4" 18' - 1" 7' - 0 1/4"

28' - 1 1/4"

AD

" 7/8

16' - 0 5/8"

PD

PD

-6 17'

EXISTING FOUR STORY BUILDING

PD

" 1/8

LCX

RAMP DN AD

CV

1 9' -

LCY

LCXX

PD

" 5/8

LCZ

PD

-1 13'

EXISTING TWO STORY BUILDING

LCZZ

PD

CW

" 3/8

LCYY

PD

AD PD

636.42'

PD

8"

'-6 "13

21A10

3 A634

PD

PD

CX

0"

8 1"' 3/8

AD

15'

14'

-2 11'

BRIDGE AD

C3

C4

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

UNIT: TYPE: SHEET:

"

AD

K205 UNIT: TYPE: K-A2 SIM1 SHEET: A623

K203 K-C A624

0 1' -

TRASH

UNIT: TYPE: SHEET:

TRANSFORMER BELOW

ELEVATOR #3

K202 K-D A624

STAIR #2

UNIT: TYPE: SHEET:

C2

14' - 7 1/8"

15' - 0"

AD

LANKERSHIM + otsego

AD

20' - 7"

O

(1 - HR CORRIDOR)

KCF

KCC

CA L I F

LC26

LC24

154' - 4 3/8"

4' - 9 5/8"

OF

A

AD

AD

PD

ST A

1' - 11 7/8" 11' - 0 1/8"

AD

AD

PD

PD

AD

633.42' 6' - 9 7/8"

AD

PD

PD

STAMP

CT TE ERIS K

633.42'

PD

PD

PD

PROJECT OVERALL 0 BD 42 UNITS 1 BD 183 UNITS 2 BD 72 UNITS TOTAL 297 UNITS

NI

DN

100' - 0"

SIXTH FLOOR OVERALL 0 BD 8 UNITS 1 BD 32 UNITS 2 BD 14 UNITS TOTAL 54 UNITS

14' - 6"

KCO

PD

PD

PD

PD

PD AD

KCH

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

R

AD

STAIR #4

KCM

DE Architects AIA

SEVENTH FLOOR OVERALL 0 BD 4 UNITS 1 BD 21 UNITS 2 BD 10 UNITS TOTAL 35 UNITS

KCP

KCN

FIFTH FLOOR OVERALL 0 BD 7 UNITS 1 BD 32 UNITS 2BD 14 UNITS TOTAL 53 UNITS

32' - 0"

KCQ

FOURTH FLOOR OVERALL 0 BD 8 UNITS 1 BD 33 UNITS 2 BD 13 UNITS TOTAL 54 UNITS OFFICE PARAPET +/- 60' - 0"

21' - 4"

PENTHOUSE PARAPET +/- 70' - 0"

8' - 0"

UNIT: TYPE: SHEET:

L201 L-P A614

AD

UNIT: TYPE: SHEET:

PD

L223 L-D A604

AD

AD

UNIT: TYPE: SHEET:

AD

L229 L-A3 A602

AD

L227 UNIT: TYPE: L-A3 SIM1 SHEET: A602

AD

AD

UNIT: TYPE: SHEET:

AD

L225 L-A3 A602

AD

UNIT: TYPE: SHEET:

AD

L224 L-ZG A620

16' - 6"

22' - 6"

LCA

1'0"- 0"

LCB L231 UNIT: TYPE: L-A3 sim 2 SHEET: A602

AD

AD

LCA

15' - 7 7/8"

1' - 2 1/8"

37' - 3 7/8"

9' - 6 3/8" 10' - 8 3/4"

23' - 10 1/8"

14' - 6 1/4"

12' - 11 3/4"

16' - 11"

9' - 9"

26' - 8"

26' - 8"

27' - 6"

25' - 9 3/4" 0 1' '14

LC1.1

LC3

LC4

LC10

LC12

LC16

LC22

LC25

LC27

LC28

LC29

LC30

LC31

LC32

LC33 '15 -2 10'

1

-3 22'

SECOND FLOOR PLAN 1/16" = 1'-0"

SHEET TITLE

0"

SECOND FLOOR PLAN

C1

8"

C2

" 1/4

" 3/4

"

C3

N

C4 C5

C6

GENERAL NOTES -REFER TO SHEET A101 FOR GRADES AND SITE PLAN NOTES NOT CONTAINED IN THIS DRAWING. -LANDSCAPE DESIGN REQUIRES 100% DRIP IRRIGATION WITHIN 5 FT OF BUILDING PERIMETER FOOTING, SPRAY HEADS NOT ALLOWED IN THIS PROJECT. -SEAL EXTERNAL CRACKS, JOINTS ETC. WITH CAULKING AND INSTALL PEST-PROOF SCREENS WHERE REQUIRED.

METAL LATH: - ATTACH LATH TO SUPPORTS AT 6" O.C. INSTALL LATH USING HOT-DIP GALVANIZED FASTENERS WITH NEOPRENE WASHERS. INSTALL SCREWS TO ENSURE THAT WASHERS HAS MAXIMUM CONTACT WITH BUILDING PAPER/MEMBRANE WATERPROOFING. SCREWS SHALL PENETRATE THROUGH EXTERIOR PLYWOOD SHEATHING INTO FRAMING. - IF STAPLES ARE USED TO ATTACH LATH, ALL PENETRATIONS SHALL BE CAULKED AND SEALED, TYPICAL.

3/9/2017 2:33:21 PM

FIREPROOFING: -APPLY 1HR CEMENTITIOUS FIREPROOFING (LARR #24763 OR APPROVED EQUAL) APPLY IN LOCATIONS NOTED, OTHERWISE PROVIDE INTUMESCENT COATING. -PROVIDE FIRE SPRINKLER SYSTEM SHALL BE APPROVED BY PLUMBING DIV. PRIOR TO INSTALLATION. 12.21A17(d) -INTUMESCENT COATING, TYPICAL AT ALL STEEL LOCATD WITHIN DWELLING UNITS. PROVIDE 1HR RATING THROUGHOUT, EXCEPT FOR COLUMNS ENCLOSED WITHIN EXTERIOR WALL. PROVIDE 2HR RATING FOR COLUMNS ENCLOSED WITHIN EXTERIOR WALL (LARR #25484 OR APPROVED EQUAL) -SEE STRUCTURAL DWGS FOR RESTRAINED CONSTRUCTION OF STEEL MEMBERS. FIRE PROTECTION: -PROVIDE FIRE SPRINKLER SYSTEM SHALL BE APPROVED BY PLUMBING DIV. PRIOR TO INSTALLATION. 12.21A17(d) - CONTRACTOR SHALL PROVIDE SPRINKLER AT ALL CONCEALED SPACES LARGER THAN 6", PER NFPA13, OR SOLIDLY FILL WITH INSULATION. - INSTALL CONCEALED FIRE SPRINKLERS THROUGHOUT, INT. & EXT.

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

INSULATION: -PROVIDE R-25 INSULATION AT 2X8 WALL FRAMING, WHERE IT OCCURS. -WALL INSULATION SHALL FILL & CONTINUOUSLY TOUCH CAVITY ON ALL 6 SIDES - NO AIR GAPS -CEILING/ROOF INSULATION SHALL CONTINUOUSLY TOUCH CAVITY ON 5 SIDES - NO AIR GAPS MATERIALS: - ANNULAR SPACES AROUND PIPES, ELECTRIC CABLES, CONDUITS, OR OTHER OPENINGS IN THE SOLE/BOTTOM PLATES AT EXTERIOR WALLS SHALL BE PROTECTED AGAINST THE PASAGE OF RODENTS BY CLOSING SUCH OPENINGS WITH CEMENT MORTAR, CONCRETE MASONRY, OR METAL PLATES. PIPING PRONE TO CORROSION SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 313.0 OF THE LOS ANGELES PLUMBING CODE. - MATERIALS DELIVERED TO THE CONSTRUCTION SITE SHALL BE PROTECTED FROM RAIN OR OTHER SOURCES OF MOISTURE. MAINTENANCE MANUAL: -AN OPERATION AND MAINTENANCE MANUAL INCLUDING , AT A MINIMUM, THE ITEMS LISTED IN CAL GREEN SECTION 4.410.1, SHALL BE COMPLETED AND PLACED IN THE BUILDING AT THE TIME OF FINAL INSPECTION OUTDOOR LIGHTING SYSTEMS: - OUTDOOR LIGHTING SYSTEMS SHALL BE DESIGNED AND INSTALLED TO COMPLY WITH ALL OF THE FOLLOWING: a) THE MINIMUM REQUIREMENTS IN CALIFORNIA ENERGY CODE FOR LIGHTING ZONES 1-4. b) BACKLIGHT, UPLIGHT AND GLARE (BUG) RATINGS AS DEFINED IN IESNA TM-15-11. (c) ALLOWABLE BUG RATINGS NOT EXCEEDING THOSE SHOWN IN ON TABLE 5.106.8. DISSIMILAR METALS: -PROVIDE RUBBER GASKET AT DISSIMILAR METALS, TYPICAL THROUGHOUT. POOL EQUIPMENT: - POOL EQUIPMENT SHALL BE MOUNTED ON MECHANICAL PADS & ATTACHED WITH SPRING ISOLATORS. REFERENCE SIMILAR DETAIL 4/A909 - PLUMBING LINES SHALL BE RAISED ABOVE ROOF AND ISOLATED WITH RUBBER SUPPORTS, TYPICAL.

ELECTRICAL NOTES: - THE MAIN ELECTRICAL SERVICE PANEL SHALL HAVE A RESERVED SPACE TO ALLOW FOR INSTALLATION OF A DOUBLE POLE CIRCUIT BREAKER FOR A FUTURE SOLAR ELECTRIC INSTALLATION. THE RESERVED SPACE SHALL BE POSITIONED AT THE OPPOSITE (LOAD) END FROM THE INPUT FEEDER LOCATION OR MAIN CIRCUIT LOCATION AND SHALL BE PERMANENTLY MARKED AS ‘FOR FUTURE SOLAR ELECTRIC’. - THE MAIN SERVICE PANEL SHALL HAVE A MINIMUM BUSBAR RATING OF 200 AMPS. - PROVIDE ADEQUATE LIGHTING TO ENSURE SAFE ACCESS TO BICYCLE PARKING FACILITIES IN ACCORDANCE WITH SECTION 12.21A.5(k).

COMMISSIONING: HVAC, INDOOR LIGHTING AND WATER HEATING ARE NOT WITHIN THE SCOPE OF WORK FOR THIS PHASE OF CONSTRUCTION. COMMISSIONING OF THE HVAC, INDOOR LIGHTING AND WATER HEATING SYSTEMS FOR THE NONRESIDENTIAL SPACES WILL BE REQUIRED AND PERFORMED AT THE INITIAL TENANT IMPROVEMENT PHASE.

LEGEND

NO.

CONCRETE WALL PER STRUCTURAL CMU WALL PER STRUCT. METAL STUD WALL / PARTY-WALL - SOUND WALL STC RATING 50 REQ. / 1HR RATED (REFERENCE WALL TYPE ASSEMBLY)

-ALL MATERIALS SHALL BEAR IDENTIFICATION SHOWING THE FIRE PERFORMANCE RATING THEREOF AND, IF INTENDED FOR EXTERIOR USE, SHALL BE FURTHER IDENTIFIED TO INDICATE SUITABILITY FOR EXPOSURE TO THE WEATHER. SUCH IDENTIFICATIONS SHALL BE ISSUED BY AN APPROVED L.A. CITY AGENCY HAVING A SERVICE FOR INSPECTION OF MATERIALS AT THE FACTORY.

07D9 08B3 21A4

FIRE RATED WALL - 2HR

METAL STUD FRAMING @ P2 - 2ND FLOORS: - METAL STUD FRAMING, TYP. @ TYPE 1 CONSTRUCTION - WOOD FRAMING NOT PERMITTED WOOD CONSTRUCTION @ 3rd - 7th FLOORS: EXTERIOR WALLS TO BE FIRE TREATED WOOD LARR 24502 (SEE FLOOR PLANS): -FIRE-RETARDANT-TREATED WOOD IS LUMBER OR PLYWOOD IMPREGNATED WITH CHEMICALS AND WHICH, WHEN TESTED IN ACCORDANCE WITH U.B.C. STANDARD NO. 42-1 FOR A PERIOD OF 30 MINUTES, SHALL HAVE A FLAME SPREAD OF NOT OVER 25 AND SHOW NO EVIDENCE OF PROGRESSIVE COMBUSTION. MATERIALS WHICH MAY BE EXPOSED TO THE WEATHER SHALL MAINTAIN THIS FIRE-RETARDANT CLASSIFICATION WHEN TESTED IN ACCORDANCE WITH THE RAIN AND WEATHERING TESTS OF U.B.C. STANDARD NO. 32-7.

KEYNOTES LEGEND

CONCRETE COLUMNS AT GARAGE LEVELS SEE STRUCTURAL DRAWINGS. AD

AREA DRAIN. SLOPE TO DRAIN 2% MAX

PD

PLANTER/AREA DRAIN. EMERGENCY DRAIN.

ED

F.E.C.

FIRE EXTINGUISHER CABINET - RECESSED AT RESIDENTIAL FLOORS & SURFACE MOUNTED GARAGES (MAX. 75' FROM ANY PORTION OF BUILDING). SEE 0/A900. EXIT SIGN

H.B.

21A10 23A10 23A12

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

DESCRIPTION 2" SEISMIC SEPERATION 90 MIN. FIRE RATED DOOR ON HOLD OPEN DEVICE WET STANDPIPE. 12" MAX. PROTRUSION FOR POST-MOUNTED OBJECTS, 4" MAX. PROJECTION FOR PROTRUSIONS FROM WALL, OR PROVIDE CANE DETECTION AT THESE LOCATIONS. 36" WIDE METAL FIRE DEPARTMENT ACCESS PARAPET LADDER. SEE 18/A909 MECHANICAL SHAFT - SEE MECH. DWGS. MECHANICAL FRESH AIR INTAKE - RUSKIN ELF375DX ALUMINUM OR APPROVED EQ. - 43% FREE OPENING (REF. MECH. DWGS.)

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO. DATE

HOSE BIB

1501 03-03-2017

2% MAX. SLOPE @ CORRIDORS & BALCONIES

SCALE

DISABLED ACCESS VEHICULAR CLEARANCE 8'-2" MIN. CLEARANCE

SHEET NO.

As indicated

A204


K19

K17

K15

K13

K11

K9

K7

K5

K4

K2

K1

PROJECT OVERALL UNIT MIX: SECOND FLOOR OVERALL 0 BD 8 UNITS 1 BD 33 UNITS 2BD 7 UNITS TOTAL 48 UNITS

288' - 2 5/8"

26' - 8 1/2"

16' - 10 1/8"

27' - 0 5/8"

26' - 9 7/8"

26' - 5 3/8"

26' - 5 3/8"

26' - 5 3/8" EXISTING BUILDING TOP OF PARAPET 46'-0" (31' - 0" ABOVE PODIUM)

EXISTING FOUR STORY PARKING GARAGE

25' - 4 1/4"

15' - 6"

EXISTING BUILDING TOP OF PARAPET +/- 65'-0" (50' - 0" ABOVE PODIUM)

7' - 0"

STAIR #4

DN 08B3

645.42'

(1 - HR CORRIDOR)

L3

L5

L4

L6

L10 L11

L14

L15

L17

E

L17.1 L18

OF

CA L I F

O

2010 ADA MOBILITY COMPLIANT

K311 UNIT: TYPE: K-E SIM6 SHEET: A625

UNIT: TYPE: SHEET:

K315 K-N A627

UNIT: TYPE: SHEET:

K317 K-N1 A627

16' - 5 3/8"

16' - 0 3/4"

5' - 7"

26' - 0 3/4"

ELEVATOR

1 2

KD

O

/8" 91

KA 9 3' -

" 1/4

26' - 5 3/8"

26' - 9 7/8"

26' - 9 7/8"

26' - 5 3/8"

26' - 5 3/8"

36' - 3 1/8"

36' - 5 7/8"

K12

K10

K8

K6

K3 LP LO

(1 - HR CORRIDOR)

AD

21A4

27' - 8"

L311 L-R A614

8' - 8 1/2" 18' - 11 3/8"

AD

(1 - HR CORRIDOR)

L306 UNIT: TYPE: L-E sim 4 A605 SHEET:

" 1/2

2010 ADA VISUAL & HEARING IMPAIRED COMPLIANT

TRASH

L324 L-R2 A615

UNIT: TYPE: SHEET:

25' - 0 1/2"

TOTAL SHALL NOT EXCEED 25% OF LENGTH OF WALL

L304 L-S A616

UNIT: TYPE: SHEET:

C

L327 UNIT: TYPE: L-E3 sim 1 SHEET: A608

21A4 -1 26'

ELEVATOR #2

STAIR #1

L333 L-ZN A621

UNIT: TYPE: SHEET:

AD

UNIT: TYPE: SHEET:

AD

L331 L-W A617 AD

L328 L-E3 A608

PD

OPEN TO ABOVE

08B3

21A4

(1 - HR CORRIDOR)

UNIT: TYPE: SHEET:

B

AD

PD AD

UNIT: TYPE: SHEET: UNIT: TYPE: SHEET:

(1 - HR CORRIDOR)

L301 L-U A617

A

A/V

0" N 5' - ATIO DIC DE

L302 L-T A616

14' - 7 1/2"

UNIT: TYPE: SHEET:

L336 L-F A611

L334 UNIT: TYPE: L-E2 sim 1 SHEET: A607

UNIT: TYPE: SHEET:

L329 L-G A611

L330 L-X A618

UNIT: TYPE: SHEET:

L332 L-E2 A607

1.16° DEG.

10' - 2" 7' - 0 3/8"

6' - 1 3/8" 7' - 10 3/4" 8' - 0 1/4"

6' - 5 1/4" 8' - 9 5/8" 11' - 10 3/4"

29' - 11 1/4"

26' - 11 3/8"

AD

DEDICATION

8' - 0"

11' - 2 1/4"

AD

3' - 6 1/8" 4' - 8 1/4" 23' - 7 3/4"

26' - 11 3/8"

8' - 5 1/4"

" 5/8

UNIT: TYPE: SHEET:

6 2' -

13' - 9 3/4" 5' - 9 1/2" 9' - 10 7/8"

649.92'

L335 L-V A617

0" -1 29'

649.92'

UNIT: TYPE: SHEET:

° 26.62

L303 UNIT: TYPE: L-E1 sim 3 SHEET: A606

/2"

17' - 11 1/4"

01

7' - 1 1/4"

PROPOSED OPENING: 48 SF. LENGTH 6'-0" HEIGHT 8'-0"

L326 L-ZO A621

LC

LB

D

" 1/4

LD

L305 L-E1 A606

L325 UNIT: TYPE: L-E3 sim 2 SHEET: A608

9 8' -

UNIT: TYPE: SHEET:

UNIT: TYPE: SHEET:

E

0" -1 18'

FIRE WALL LENGTH: 58.58' TYPICAL AT 3RD FLOOR THROUGH ROOF

) OR RID OR RC -H

3 A711

(1

LE

F

L323 L-E4 A609

UNIT: TYPE: SHEET:

EACH OPENING SHALL NOT EXCEED 156 SF.

LF

G

-5 20'

37' - 4 5/8"

L322 L-ZP A621

PROPOSED OPENING: 48 SF. LENGTH 6'-0" HEIGHT 8'-0"

" 3/8

" 7/8

UNIT: TYPE: SHEET:

LI

LG

TOTAL SHALL NOT EXCEED 25% OF LENGTH OF WALL

AD

L308 L-E A605

AD

LJ

LH

H

" 1/2

STAIR #5

L309 L-R1 A615

L307 UNIT: L-ZM2 TYPE: SHEET: A621

EACH OPENING SHALL NOT EXCEED 156 SF.

8 5' 0" -1 27'

UNIT: TYPE: SHEET:

FIRE WALL LENGTH: 59.75' TYPICAL AT 3RD FLOOR THROUGH ROOF

I

08B3

2010 ADA MOBILITY COMPLIANT

UNIT: TYPE: SHEET:

252' - 10 1/2"

L321 L-H A612

'-0 270

L320 UNIT: L7 ADA2010 TYPE: SHEET: A621b

LL

LK

UNIT: TYPE: SHEET:

21A4

TOTAL SHALL NOT EXCEED 25% OF LENGTH OF WALL PROPOSED OPENING: 48 SF. LENGTH 6'-0" HEIGHT 8'-0"

L318 L-ZJ A620

6 1' -

EACH OPENING SHALL NOT EXCEED 156 SF.

UNIT: TYPE: SHEET:

L310 UNIT: TYPE: L-E sim 2 SHEET: A605

8" 2' " 3/8

FIRE WALL LENGTH: 80.53' TYPICAL AT 3RD FLOOR THROUGH ROOF

J

-2 21'

LM

" 1/4

LN

L319 L-E6 A610

) OR RID OR RC -H

UNIT: TYPE: SHEET:

08B3

PROPOSED OPENING: 48 SF. LENGTH 6'-0" HEIGHT 8'-0"

UNIT: TYPE: SHEET:

L316 UNIT: TYPE: L-ZJ SIM1 SHEET: A620

(1

TOTAL SHALL NOT EXCEED 25% OF LENGTH OF WALL

K

6 A711

21A4

EACH OPENING SHALL NOT EXCEED 156 SF.

31' - 10 5/8"

TRASH

LP.1

PD

-4 28'

FIRE WALL LENGTH: 73.3' TYPICAL AT 3RD FLOOR THROUGH ROOF

649.92'

649.92'

K1 5' - 9 1/2"

K14

L312 L-M A613

4 D# AR AD Y D 31 UR /A6 5 CO E SE

L

/4"

UNIT: TYPE: SHEET:

L317 L-J A612

UNIT: TYPE: SHEET:

14B1

11

K16

L314 UNIT: L1 ADA2010 TYPE: SHEET: A621a 2010 ADA MOBILITY COMPLIANT

278' - 1 1/2"

K21

L313 L-ZM A621

-1 18'

27' - 6 1/4"

31' - 11 1/2"

EXISTING FOUR STORY BUILDING

UNIT: TYPE: SHEET:

M

" 7/8 '-8 "7 1/8

2

L315 L-Y A618

-9 12'

LQ

UNIT: TYPE: SHEET:

N

46' - 4 1/2"

LR 17' - 0 1/8"

LR

LANKERSHIM + otsego

K309 UNIT: TYPE: K-E SIM12 SHEET: A625

4' - 93'5/8" - 04'7/8" - 7 7/8" 6' - 5 1/2" 7' - 5 1/4"

18' - 6 1/8"

5' - 9 1/2"

K307 UNIT: TYPE: K-E SIM10 SHEET: A625

12' - 0 1/4"6' - 12'3/8" - 3 7/8" 20' - 11 1/2"

30' - 10 1/4"

K305 UNIT: TYPE: K-E SIM4 SHEET: A625

2' - 5 1/4" 19' - 9 7/8"

20' - 11 5/8"

29' - 5 3/8"

LA.1 9 1/4"

K303 K-F A626

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

137' - 9 7/8"

" 1/2

14' - 2 7/8"

L2

1.37° DEG.

2' - 6 5/8"

LA

64 .75 °

UNIT: TYPE: SHEET:

EXISTING TWO STORY BUILDING

K24

REN. 6-30-17

-6 26'

1' - 7 1/2"

L1.1

64 .75 °

2010 ADA VISUAL & HEARING IMPAIRED COMPLIANT

28' - 5 3/8"

NO. C-13779

14' - 5 7/8"

K313 UNIT: K1 ADA2010 TYPE: SHEET: A628a

21A10

16' - 5"

ED A RCH NS S EMP I A TA

KI KH

11 1/4"

K302 K-G A626

STAMP

PROPOSED OPENING: 48 SF. LENGTH 6'-0" HEIGHT 8'-0"

KJ

MATCHLINE 30' - 0 1/4"

8' - 0" UNIT: TYPE: SHEET:

TOTAL SHALL NOT EXCEED 25% OF LENGTH OF WALL

1

(1 - HR CORRIDOR)

DEDICATION

86' - 8 1/8"

21A4

STAIR #3B

(1 - HR CORRIDOR)

KC KB

1' - 11"

TRASH

18' - 10 5/8"

K310 K-E A625

KM

3' - 2 1/2"

1' - 11"

UNIT: TYPE: SHEET:

K316 K-P A628

PROJECT OVERALL 0 BD 42 UNITS 1 BD 183 UNITS 2 BD 72 UNITS TOTAL 297 UNITS

" 1/2

KE

K308 UNIT: TYPE: K-E SIM3 SHEET: A625

UNIT: TYPE: SHEET:

EACH OPENING SHALL NOT EXCEED 156 SF.

-6 13'

KF

1' - 6 3/8"

KG

26' - 7"

1' - 6 1/4" 5' - 4"

100' - 0"

KH

K306 K-E1 A624

KN

SEVENTH FLOOR OVERALL 0 BD 4 UNITS 1 BD 21 UNITS 2 BD 10 UNITS TOTAL 35 UNITS

T

KI

K301 K-O A628

UNIT: TYPE: SHEET:

FIRE WALL LENGTH: 52.38' TYPICAL AT 3RD FLOOR THROUGH ROOF

ST A

UNIT: TYPE: SHEET:

K304 K-E2 A624

21A10

5' - 4"9' - 2 5/8"

645.42'

UNIT: TYPE: SHEET:

K314 UNIT: TYPE: K-E SIM2 SHEET: A625

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

CT TE ERIS K

27' - 3 7/8"

645.42'

K312 UNIT: TYPE: K-E SIM1 SHEET: A625

DE Architects AIA

SIXTH FLOOR OVERALL 0 BD 8 UNITS 1 BD 32 UNITS 2 BD 14 UNITS TOTAL 54 UNITS

KP

MATCHLINE

KL

FIFTH FLOOR OVERALL 0 BD 7 UNITS 1 BD 32 UNITS 2BD 14 UNITS TOTAL 53 UNITS

ELEVATOR #3

5' - 10"

KO

9 A711

ELEVATOR #4

KQ

FOURTH FLOOR OVERALL 0 BD 8 UNITS 1 BD 33 UNITS 2 BD 13 UNITS TOTAL 54 UNITS

10' - 2"

3' - 11" 10' - 2 1/4"

TOP OF PARAPET 46'-0" (31' - 0" ABOVE PODIUM)

21A4

THIRD FLOOR OVERALL 0BD 7 UNITS 1BD 32 UNITS 2 BD 14 UNITS TOTAL 53 UNITS

10' - 4"

L IC E DONA

6' - 11" 6' - 2 1/2"

8' - 2 3/8"

STAIR #2

20' - 2 1/2"

OFFICE PARAPET +/- 60' - 0"

3' - 7"

PENTHOUSE PARAPET +/- 70' - 0"

15' - 1 3/4"

A

K20

NI

K22

R

K23

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

K25

261' - 11 3/8"

L1

L2

L3.1 L3.2

L4

L5

L7

L8

L9

L13

L16

L19

L20

L21

L22

L23

L24

SHEET TITLE

° 25.25

30'

9 5' 33'

THIRD FLOOR PLAN 1 1/16" = 1'-0"

1"

5

GENERAL NOTES -REFER TO SHEET A101 FOR GRADES AND SITE PLAN NOTES NOT CONTAINED IN THIS DRAWING. -LANDSCAPE DESIGN REQUIRES 100% DRIP IRRIGATION WITHIN 5 FT OF BUILDING PERIMETER FOOTING, SPRAY HEADS NOT ALLOWED IN THIS PROJECT. -SEAL EXTERNAL CRACKS, JOINTS ETC. WITH CAULKING AND INSTALL PEST-PROOF SCREENS WHERE REQUIRED. METAL LATH: - ATTACH LATH TO SUPPORTS AT 6" O.C. INSTALL LATH USING HOT-DIP GALVANIZED FASTENERS WITH NEOPRENE WASHERS. INSTALL SCREWS TO ENSURE THAT WASHERS HAS MAXIMUM CONTACT WITH BUILDING PAPER/MEMBRANE WATERPROOFING. SCREWS SHALL PENETRATE THROUGH EXTERIOR PLYWOOD SHEATHING INTO FRAMING. - IF STAPLES ARE USED TO ATTACH LATH, ALL PENETRATIONS SHALL BE CAULKED AND SEALED, TYPICAL.

3/9/2017 2:33:36 PM

FIREPROOFING: -APPLY 1HR CEMENTITIOUS FIREPROOFING (LARR #24763 OR APPROVED EQUAL) APPLY IN LOCATIONS NOTED, OTHERWISE PROVIDE INTUMESCENT COATING. -PROVIDE FIRE SPRINKLER SYSTEM SHALL BE APPROVED BY PLUMBING DIV. PRIOR TO INSTALLATION. 12.21A17(d) -INTUMESCENT COATING, TYPICAL AT ALL STEEL LOCATD WITHIN DWELLING UNITS. PROVIDE 1HR RATING THROUGHOUT, EXCEPT FOR COLUMNS ENCLOSED WITHIN EXTERIOR WALL. PROVIDE 2HR RATING FOR COLUMNS ENCLOSED WITHIN EXTERIOR WALL (LARR #25484 OR APPROVED EQUAL) -SEE STRUCTURAL DWGS FOR RESTRAINED CONSTRUCTION OF STEEL MEMBERS. FIRE PROTECTION: -PROVIDE FIRE SPRINKLER SYSTEM SHALL BE APPROVED BY PLUMBING DIV. PRIOR TO INSTALLATION. 12.21A17(d) - CONTRACTOR SHALL PROVIDE SPRINKLER AT ALL CONCEALED SPACES LARGER THAN 6", PER NFPA13, OR SOLIDLY FILL WITH INSULATION. - INSTALL CONCEALED FIRE SPRINKLERS THROUGHOUT, INT. & EXT.

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

INSULATION: -PROVIDE R-25 INSULATION AT 2X8 WALL FRAMING, WHERE IT OCCURS. -WALL INSULATION SHALL FILL & CONTINUOUSLY TOUCH CAVITY ON ALL 6 SIDES - NO AIR GAPS -CEILING/ROOF INSULATION SHALL CONTINUOUSLY TOUCH CAVITY ON 5 SIDES - NO AIR GAPS MATERIALS: - ANNULAR SPACES AROUND PIPES, ELECTRIC CABLES, CONDUITS, OR OTHER OPENINGS IN THE SOLE/BOTTOM PLATES AT EXTERIOR WALLS SHALL BE PROTECTED AGAINST THE PASAGE OF RODENTS BY CLOSING SUCH OPENINGS WITH CEMENT MORTAR, CONCRETE MASONRY, OR METAL PLATES. PIPING PRONE TO CORROSION SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 313.0 OF THE LOS ANGELES PLUMBING CODE. - MATERIALS DELIVERED TO THE CONSTRUCTION SITE SHALL BE PROTECTED FROM RAIN OR OTHER SOURCES OF MOISTURE. MAINTENANCE MANUAL: -AN OPERATION AND MAINTENANCE MANUAL INCLUDING , AT A MINIMUM, THE ITEMS LISTED IN CAL GREEN SECTION 4.410.1, SHALL BE COMPLETED AND PLACED IN THE BUILDING AT THE TIME OF FINAL INSPECTION OUTDOOR LIGHTING SYSTEMS: - OUTDOOR LIGHTING SYSTEMS SHALL BE DESIGNED AND INSTALLED TO COMPLY WITH ALL OF THE FOLLOWING: a) THE MINIMUM REQUIREMENTS IN CALIFORNIA ENERGY CODE FOR LIGHTING ZONES 1-4. b) BACKLIGHT, UPLIGHT AND GLARE (BUG) RATINGS AS DEFINED IN IESNA TM-15-11. (c) ALLOWABLE BUG RATINGS NOT EXCEEDING THOSE SHOWN IN ON TABLE 5.106.8. DISSIMILAR METALS: -PROVIDE RUBBER GASKET AT DISSIMILAR METALS, TYPICAL THROUGHOUT. POOL EQUIPMENT: - POOL EQUIPMENT SHALL BE MOUNTED ON MECHANICAL PADS & ATTACHED WITH SPRING ISOLATORS. REFERENCE SIMILAR DETAIL 4/A909 - PLUMBING LINES SHALL BE RAISED ABOVE ROOF AND ISOLATED WITH RUBBER SUPPORTS, TYPICAL.

ELECTRICAL NOTES: - THE MAIN ELECTRICAL SERVICE PANEL SHALL HAVE A RESERVED SPACE TO ALLOW FOR INSTALLATION OF A DOUBLE POLE CIRCUIT BREAKER FOR A FUTURE SOLAR ELECTRIC INSTALLATION. THE RESERVED SPACE SHALL BE POSITIONED AT THE OPPOSITE (LOAD) END FROM THE INPUT FEEDER LOCATION OR MAIN CIRCUIT LOCATION AND SHALL BE PERMANENTLY MARKED AS ‘FOR FUTURE SOLAR ELECTRIC’. - THE MAIN SERVICE PANEL SHALL HAVE A MINIMUM BUSBAR RATING OF 200 AMPS. - PROVIDE ADEQUATE LIGHTING TO ENSURE SAFE ACCESS TO BICYCLE PARKING FACILITIES IN ACCORDANCE WITH SECTION 12.21A.5(k).

COMMISSIONING: HVAC, INDOOR LIGHTING AND WATER HEATING ARE NOT WITHIN THE SCOPE OF WORK FOR THIS PHASE OF CONSTRUCTION. COMMISSIONING OF THE HVAC, INDOOR LIGHTING AND WATER HEATING SYSTEMS FOR THE NONRESIDENTIAL SPACES WILL BE REQUIRED AND PERFORMED AT THE INITIAL TENANT IMPROVEMENT PHASE.

LEGEND

PARTY-WALL - SOUND WALL STC RATING 50 REQ. / 1HR RATED 2X PLUMBING WALL WHERE INDICATED

WOOD CONSTRUCTION @ 3rd - 7th FLOORS: EXTERIOR WALLS TO BE FIRE TREATED WOOD LARR 24502 (SEE FLOOR PLANS): -FIRE-RETARDANT-TREATED WOOD IS LUMBER OR PLYWOOD IMPREGNATED WITH CHEMICALS AND WHICH, WHEN TESTED IN ACCORDANCE WITH U.B.C. STANDARD NO. 42-1 FOR A PERIOD OF 30 MINUTES, SHALL HAVE A FLAME SPREAD OF NOT OVER 25 AND SHOW NO EVIDENCE OF PROGRESSIVE COMBUSTION. MATERIALS WHICH MAY BE EXPOSED TO THE WEATHER SHALL MAINTAIN THIS FIRE-RETARDANT CLASSIFICATION WHEN TESTED IN ACCORDANCE WITH THE RAIN AND WEATHERING TESTS OF U.B.C. STANDARD NO. 32-7.

-ALL MATERIALS SHALL BEAR IDENTIFICATION SHOWING THE FIRE PERFORMANCE RATING THEREOF AND, IF INTENDED FOR EXTERIOR USE, SHALL BE FURTHER IDENTIFIED TO INDICATE SUITABILITY FOR EXPOSURE TO THE WEATHER. SUCH IDENTIFICATIONS SHALL BE ISSUED BY AN APPROVED L.A. CITY AGENCY HAVING A SERVICE FOR INSPECTION OF MATERIALS AT THE FACTORY.

AD PD

CONCRETE COLUMNS AT GARAGE LEVELS SEE STRUCTURAL DRAWINGS. AREA DRAIN. PLANTER/AREA DRAIN. ROOF DRAIN BELOW PEDESTAL PAPER

F.E.C.

H.B.

FIRE EXTINGUISHER CABINET - RECESSED AT RESIDENTIAL FLOORS & SURFACE MOUNTED GARAGES (MAX. 75' FROM ANY PORTION OF BUILDING). SEE 7/A906. EXIT SIGN

1.1

N

3 4

KEYNOTES LEGEND 08B3 14B1 21A4

2X STUD WALL U.N.O. FIRE RATED WALL - 2HR

1

5"

" 1/2

NO.

CONCRETE WALL PER STRUCTURAL CMU WALL PER STRUCT.

METAL STUD FRAMING @ P2 - 2ND FLOORS: - METAL STUD FRAMING, TYP. @ TYPE 1 CONSTRUCTION - WOOD FRAMING NOT PERMITTED

THIRD FLOOR PLAN

L25

21A10

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

DESCRIPTION 90 MIN. FIRE RATED DOOR ON HOLD OPEN DEVICE TRASH CHUTE WET STANDPIPE. 12" MAX. PROTRUSION FOR POST-MOUNTED OBJECTS, 4" MAX. PROJECTION FOR PROTRUSIONS FROM WALL, OR PROVIDE CANE DETECTION AT THESE LOCATIONS. 36" WIDE METAL FIRE DEPARTMENT ACCESS PARAPET LADDER. SEE 18/A909

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO. DATE

HOSE BIB 2% MAX. SLOPE @ CORRIDORS & BALCONIES = 3 HOUR FIRE WALL - REFERENCE DETAILS 15, 16, 17 ON SHEET A901

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

SCALE

1501 03-03-2017 As indicated

SHEET NO.

A205


K22

K20

K19

K17

K15

K13

K11

K9

K7

K5

K4

K2

K1

PROJECT OVERALL UNIT MIX: SECOND FLOOR OVERALL 0 BD 8 UNITS 1 BD 33 UNITS 2BD 7 UNITS TOTAL 48 UNITS THIRD FLOOR OVERALL 0BD 7 UNITS 1BD 32 UNITS 2 BD 14 UNITS TOTAL 53 UNITS

6' - 11" 8' - 2 3/8"

6' - 2 1/2"

26' - 8 1/2"

16' - 10 1/8"

27' - 0 5/8"

26' - 9 7/8"

26' - 5 3/8"

26' - 5 3/8"

26' - 5 3/8" EXISTING BUILDING TOP OF PARAPET 46'-0" (31' - 0" ABOVE PODIUM)

EXISTING FOUR STORY PARKING GARAGE

25' - 4 1/4"

FOURTH FLOOR OVERALL 0 BD 8 UNITS 1 BD 33 UNITS 2 BD 13 UNITS TOTAL 54 UNITS

15' - 6"

EXISTING BUILDING

FIFTH FLOOR OVERALL 0 BD 7 UNITS 1 BD 32 UNITS 2BD 14 UNITS TOTAL 53 UNITS

TOP OF PARAPET +/- 65'-0" (50' - 0" ABOVE PODIUM)

18' - 10 5/8" 1' - 11" 7' - 0"

K710 UNIT: TYPE: K-E SIM1 SHEET: A625

K712 UNIT: TYPE: K-E SIM2 SHEET: A625

UNIT: TYPE: SHEET:

K714 K-P A628

TRASH

UP

AD

STAIR #3B

RAMP DN

TELEPHONE PD

(1 - HR CORRIDOR)

DECK AREA #1 608 SF (OLF = 15) OCC. LOAD = 40.5

KJ L1.1

L2

L3

L6

L10

L11

L14

L15

L17

L17.1

K702 UNIT: TYPE: K-E SIM4 SHEET: A625

K705 UNIT: TYPE: K-E SIM12 SHEET: A625

K703 UNIT: TYPE: K-E SIM10 SHEET: A625

K707 UNIT: TYPE: K-E SIM6 SHEET: A625

K709 UNIT: TYPE: K-E SIM8 SHEET: A625

UNIT: TYPE: SHEET:

K711 K-N A627

UNIT: TYPE: SHEET:

KH2' - 5 1/4" 19' - 9 7/8"

20' - 5 1/2"

20' - 11 1/2"

7' - 8 3/4" 6' - 5 1/2" 7' - 5 1/4"

4' - 9 5/8"

16' - 0 3/4"

5' - 7"

O

26' - 0 3/4"

1

K713 K-N1 A627

KD 9 3' -

MATCHLINE

36' - 5 7/8"

K14

K12

K10

K8

K6

K3

K1

L712 L-M A613

31' - 10 5/8"

LP.1

TEL.

21A4 (1 - HR CORRIDOR)

L710 UNIT: TYPE: L-E sim 2 SHEET: A605

27' - 8" 8' - 8 1/2"

21A4

18' - 11 3/8"

UNIT: TYPE: SHEET:

H

L720 L-E5 A610

"

STAIR #5 AD

UNIT: TYPE: SHEET: UNIT: TYPE: SHEET:

L708 L-E A605

AD

UP UP MP RA

PD

03E6

13

17' - 4 1/4"

L709 L-R1 A615

POTENTIAL LOCATION FOR 20 CONDENSERS

-1 53'

ROOF DECK AREA #6 351 SF (OLF = 15) OCC. LOAD = 23.4

PD

L706 UNIT: TYPE: L-E sim 4 SHEET: A605

L707 UNIT: L-ZM2 TYPE: SHEET: A621

PD

TRASH

-

PD

PD

25' - 0 1/2"

E

PD

UNIT: TYPE: SHEET:

DECK AREA #5 630 SF (OLF = 15) OCC. LOAD = 42

L704 L-S A616

D

PD

L705 L-E1 A606

?

PD

Q BB

-7 35'

CHANGING

7' - 1 1/4"

Q BB

PD

36 LOCKERS PROPOSED

" 3/4

TELEPHONE

UNIT: TYPE: SHEET:

0" -1 18'

10' - 1 1/4"9' - 11 1/8"

(1 - HR CORRIDOR)

PD

/4"

SHOWERS

CHANGING

STAIR #1

L703 UNIT: TYPE: L-E1 sim 3 SHEET: A606

RAMP UP

AD AD

GREASE EXHAUST DUCT (UP TO ROOF)

AD

21A4

SPA DECK TOTAL OCC. LOAD = 48.8 [DECK: 701 SF / 15 (OLF) = 46.7] [SPA: 109 SF / 50 (OLF) = 2.1]

PD

PD

PD

PD

DECK AREA #4 665 SF (OLF = 15) OCC. LOAD = 44.3

OPEN TO BELOW PD

" 3/4

POOL (N.I.C. SEPARATE PERMIT REQ.)

DN

PD

PD

AD

(1 - HR CORRIDOR)

B

13A2 PD

-4 32'

LF

PD

PD PD POOL DECK TOTAL OCC. LOAD = 49 [DECK: 582 SF / 15 (OLF) = 38.8] [POOL: 510 SF / 50 (OLF) = 10.2]

° 26.62

ELEVATOR #2

STORAGE

17' - 11 1/4"

LG

I 8 2' -

LH

L718 L-ZJ A620

" 3/8

LI

UNIT: TYPE: SHEET:

L721 L-H A612

UNIT: TYPE: SHEET:

-2 21'

LJ

" 1/4

L711 L-R A614

) OR RID OR RC -H

UNIT: TYPE: SHEET:

LL

LK

J

(1

LM

L719 L-E6 A610

UNIT: TYPE: SHEET:

L716 UNIT: TYPE: L-ZJ SIM1 SHEET: A620

LN

K

-4 28'

LO

UNIT: TYPE: SHEET:

L

/4"

K16

L717 L-ZA A619

UNIT: TYPE: SHEET:

L714 L-E7 A610

11

K18

UNIT: TYPE: SHEET:

M

-1 18'

K21

L713 L-ZM A621

L715 L-Y A618

TRASH

36' - 3 1/8"

UNIT: TYPE: SHEET:

ELEVATOR #3

26' - 5 3/8"

2

31' - 11 1/2"

26' - 5 3/8"

UNIT: TYPE: SHEET:

5' - 9 1/2"

26' - 9 7/8"

AD

" 7/8

26' - 9 7/8"

N

'-8 "7 1/8

26' - 5 3/8"

LR

-9 12'

17' - 7 3/8"

" 1/2

9' - 10 7/8"

LQ

-6 26'

KA

" 1/4

° 26.62

1' - 7 1/2"

O

2

LP

PD PD

L701 UNIT: TYPE: L-U sim 4 SHEET: A617

L702 L-T A616

PD

PD

POOL/ SPA EQUIPMENT

POOL DECK EL: + 5'-0" PD

PD

PD

LC 14' - 7 1/2"

ROOF

PD

PD

03E6

DECK AREA #1 364 SF (OLF = 15) OCC. LOAD = 24.2

PD

DECK AREA #2 364 SF (OLF = 15) OCC. LOAD = 24.2

PD

PD

DECK AREA #3 670 SF (OLF = 15) OCC. LOAD = 44.6

PD

PD

POTENTIAL LOCATION FOR 15 CONDENSERS

DECK EL: + 1'-4 3/4"

SEE 1/A634

LB

LA

L1

L2

4' - 8 1/4" 23' - 7 3/4"

L3.1

3' - 6 1/8" 6' - 1 3/8"

L3.2

L4

L5

7' - 10 3/4" 8' - 0 1/4"

6' - 5 1/4" 1' - 5 5/8" 7' - 4" 11' - 10 3/4"

L7

L9

L8

L12

L13

L16

92' - 3 1/8"

4' -

68' - 11 1/8"

L22

L25

9 5' '33

-REFER TO SHEET A101 FOR GRADES AND SITE PLAN NOTES NOT CONTAINED IN THIS DRAWING. -LANDSCAPE DESIGN REQUIRES 100% DRIP IRRIGATION WITHIN 5 FT OF BUILDING PERIMETER FOOTING, SPRAY HEADS NOT ALLOWED IN THIS PROJECT. -SEAL EXTERNAL CRACKS, JOINTS ETC. WITH CAULKING AND INSTALL PEST-PROOF SCREENS WHERE REQUIRED. METAL LATH: - ATTACH LATH TO SUPPORTS AT 6" O.C. INSTALL LATH USING HOT-DIP GALVANIZED FASTENERS WITH NEOPRENE WASHERS. INSTALL SCREWS TO ENSURE THAT WASHERS HAS MAXIMUM CONTACT WITH BUILDING PAPER/MEMBRANE WATERPROOFING. SCREWS SHALL PENETRATE THROUGH EXTERIOR PLYWOOD SHEATHING INTO FRAMING. - IF STAPLES ARE USED TO ATTACH LATH, ALL PENETRATIONS SHALL BE CAULKED AND SEALED, TYPICAL. FIREPROOFING: -APPLY 1HR CEMENTITIOUS FIREPROOFING (LARR #24763 OR APPROVED EQUAL) APPLY IN LOCATIONS NOTED, OTHERWISE PROVIDE INTUMESCENT COATING. -PROVIDE FIRE SPRINKLER SYSTEM SHALL BE APPROVED BY PLUMBING DIV. PRIOR TO INSTALLATION. 12.21A17(d) -INTUMESCENT COATING, TYPICAL AT ALL STEEL LOCATD WITHIN DWELLING UNITS. PROVIDE 1HR RATING THROUGHOUT, EXCEPT FOR COLUMNS ENCLOSED WITHIN EXTERIOR WALL. PROVIDE 2HR RATING FOR COLUMNS ENCLOSED WITHIN EXTERIOR WALL (LARR #25484 OR APPROVED EQUAL) -SEE STRUCTURAL DWGS FOR RESTRAINED CONSTRUCTION OF STEEL MEMBERS. FIRE PROTECTION: -PROVIDE FIRE SPRINKLER SYSTEM SHALL BE APPROVED BY PLUMBING DIV. PRIOR TO INSTALLATION. 12.21A17(d) - CONTRACTOR SHALL PROVIDE SPRINKLER AT ALL CONCEALED SPACES LARGER THAN 6", PER NFPA13, OR SOLIDLY FILL WITH INSULATION. - INSTALL CONCEALED FIRE SPRINKLERS THROUGHOUT, INT. & EXT.

MATERIALS: - ANNULAR SPACES AROUND PIPES, ELECTRIC CABLES, CONDUITS, OR OTHER OPENINGS IN THE SOLE/BOTTOM PLATES AT EXTERIOR WALLS SHALL BE PROTECTED AGAINST THE PASAGE OF RODENTS BY CLOSING SUCH OPENINGS WITH CEMENT MORTAR, CONCRETE MASONRY, OR METAL PLATES. PIPING PRONE TO CORROSION SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 313.0 OF THE LOS ANGELES PLUMBING CODE. - MATERIALS DELIVERED TO THE CONSTRUCTION SITE SHALL BE PROTECTED FROM RAIN OR OTHER SOURCES OF MOISTURE. MAINTENANCE MANUAL: -AN OPERATION AND MAINTENANCE MANUAL INCLUDING , AT A MINIMUM, THE ITEMS LISTED IN CAL GREEN SECTION 4.410.1, SHALL BE COMPLETED AND PLACED IN THE BUILDING AT THE TIME OF FINAL INSPECTION OUTDOOR LIGHTING SYSTEMS: - OUTDOOR LIGHTING SYSTEMS SHALL BE DESIGNED AND INSTALLED TO COMPLY WITH ALL OF THE FOLLOWING: a) THE MINIMUM REQUIREMENTS IN CALIFORNIA ENERGY CODE FOR LIGHTING ZONES 1-4. b) BACKLIGHT, UPLIGHT AND GLARE (BUG) RATINGS AS DEFINED IN IESNA TM-15-11. (c) ALLOWABLE BUG RATINGS NOT EXCEEDING THOSE SHOWN IN ON TABLE 5.106.8. DISSIMILAR METALS: -PROVIDE RUBBER GASKET AT DISSIMILAR METALS, TYPICAL THROUGHOUT. POOL EQUIPMENT: - POOL EQUIPMENT SHALL BE MOUNTED ON MECHANICAL PADS & ATTACHED WITH SPRING ISOLATORS. REFERENCE SIMILAR DETAIL 4/A909 - PLUMBING LINES SHALL BE RAISED ABOVE ROOF AND ISOLATED WITH RUBBER SUPPORTS, TYPICAL.

ELECTRICAL NOTES: - THE MAIN ELECTRICAL SERVICE PANEL SHALL HAVE A RESERVED SPACE TO ALLOW FOR INSTALLATION OF A DOUBLE POLE CIRCUIT BREAKER FOR A FUTURE SOLAR ELECTRIC INSTALLATION. THE RESERVED SPACE SHALL BE POSITIONED AT THE OPPOSITE (LOAD) END FROM THE INPUT FEEDER LOCATION OR MAIN CIRCUIT LOCATION AND SHALL BE PERMANENTLY MARKED AS ‘FOR FUTURE SOLAR ELECTRIC’. - THE MAIN SERVICE PANEL SHALL HAVE A MINIMUM BUSBAR RATING OF 200 AMPS. - PROVIDE ADEQUATE LIGHTING TO ENSURE SAFE ACCESS TO BICYCLE PARKING FACILITIES IN ACCORDANCE WITH SECTION 12.21A.5(k).

-ALL MATERIALS SHALL BEAR IDENTIFICATION SHOWING THE FIRE PERFORMANCE RATING THEREOF AND, IF INTENDED FOR EXTERIOR USE, SHALL BE FURTHER IDENTIFIED TO INDICATE SUITABILITY FOR EXPOSURE TO THE WEATHER. SUCH IDENTIFICATIONS SHALL BE ISSUED BY AN APPROVED L.A. CITY AGENCY HAVING A SERVICE FOR INSPECTION OF MATERIALS AT THE FACTORY.

SHEET TITLE

SEVENTH FLOOR PLAN

1.1 ° 25.25

N

3 4

COMMISSIONING: HVAC, INDOOR LIGHTING AND WATER HEATING ARE NOT WITHIN THE SCOPE OF WORK FOR THIS PHASE OF CONSTRUCTION. COMMISSIONING OF THE HVAC, INDOOR LIGHTING AND WATER HEATING SYSTEMS FOR THE NONRESIDENTIAL SPACES WILL BE REQUIRED AND PERFORMED AT THE INITIAL TENANT IMPROVEMENT PHASE.

LEGEND

5

KEYNOTES LEGEND NO.

CONCRETE WALL PER STRUCTURAL CMU WALL PER STRUCT.

03E6

PARTY-WALL - SOUND WALL STC RATING 50 REQ. / 1HR RATED 2X PLUMBING WALL WHERE INDICATED 2X STUD WALL U.N.O.

METAL STUD FRAMING @ P2 - 2ND FLOORS: - METAL STUD FRAMING, TYP. @ TYPE 1 CONSTRUCTION - WOOD FRAMING NOT PERMITTED WOOD CONSTRUCTION @ 3rd - 7th FLOORS: EXTERIOR WALLS TO BE FIRE TREATED WOOD LARR 24502 (SEE FLOOR PLANS): -FIRE-RETARDANT-TREATED WOOD IS LUMBER OR PLYWOOD IMPREGNATED WITH CHEMICALS AND WHICH, WHEN TESTED IN ACCORDANCE WITH U.B.C. STANDARD NO. 42-1 FOR A PERIOD OF 30 MINUTES, SHALL HAVE A FLAME SPREAD OF NOT OVER 25 AND SHOW NO EVIDENCE OF PROGRESSIVE COMBUSTION. MATERIALS WHICH MAY BE EXPOSED TO THE WEATHER SHALL MAINTAIN THIS FIRE-RETARDANT CLASSIFICATION WHEN TESTED IN ACCORDANCE WITH THE RAIN AND WEATHERING TESTS OF U.B.C. STANDARD NO. 32-7.

" 1/2

/8" 93 ' 17

1"

SEVENTH FLOOR PLAN 1 1/16" = 1'-0" INSULATION: -PROVIDE R-25 INSULATION AT 2X8 WALL FRAMING, WHERE IT OCCURS. -WALL INSULATION SHALL FILL & CONTINUOUSLY TOUCH CAVITY ON ALL 6 SIDES - NO AIR GAPS -CEILING/ROOF INSULATION SHALL CONTINUOUSLY TOUCH CAVITY ON 5 SIDES - NO AIR GAPS

0

" 3/4

64 .75 °

10' - 2" 7' - 0 3/8"

GENERAL NOTES

LD

PD

PD

PD

PD

LE

30' - 10 1/4"

UNIT: TYPE: SHEET:

SPA (N.I.C. SEPARATE PERMIT REQ.)

64 .75 °

29' - 6 1/8"

21A4

PD

3/9/2017 2:33:50 PM

CA L I F

LANKERSHIM + otsego

PD

K701 K-F A626

EXISTING FOUR STORY BUILDING

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

OF

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

KI

5' - 9 1/2"

UNIT: TYPE: SHEET:

EXISTING TWO STORY BUILDING

K24

E

L18

21A10

28' - 5 3/8"

REN. 6-30-17

MATCHLINE 30' - 11 1/2"

PD

KC KB

NO. C-13779

1

DECK +1' - 6" SEE 2/A636

PD

KM

TELEPHONE

03E6

L IC E DONA

ELEVATOR #4

K708 UNIT: TYPE:K-E (UFAS) SHEET: A625

5' - 4"9' - 2 5/8"

5' - 4"

K706 UNIT: TYPE: K-E SIM3 SHEET: A625

STAIR #2

KE

K704 K-E1 A624

ED A RCH NS S EMP I A TA

KN

3' - 2 1/2"

KF

21A10 UNIT: TYPE: SHEET:

REC ROOM

21A4

14A3

1' - 6 1/4"

KG

DECK +5' - 0"

1' - 6 3/8" 1' - 11" 26' - 7"

KH

21A4

SPA (N.I.C. SEPARATE PERMIT REQ.)

STAMP

T

27' - 3 7/8"

13A3

KP

ST A

KI

STAIR #4

PROJECT OVERALL 0 BD 42 UNITS 1 BD 183 UNITS 2 BD 72 UNITS TOTAL 297 UNITS

CT TE ERIS K

KL

SEVENTH FLOOR OVERALL 0 BD 4 UNITS 1 BD 21 UNITS 2 BD 10 UNITS TOTAL 35 UNITS

5' - 0"

KO

SIXTH FLOOR OVERALL 0 BD 8 UNITS 1 BD 32 UNITS 2 BD 14 UNITS TOTAL 54 UNITS

SPA DECK TOTAL OCC. LOAD = 30.5 [DECK: 440 SF / 15 (OLF) = 29.3] [SPA: 60 SF / 50 (OLF) = 1.2]

5' - 10"

KQ

3' - 11"

TOP OF PARAPET 46'-0" (31' - 0" ABOVE PODIUM)

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

A

20' - 2 1/2"

NI

3' - 7"

DE Architects AIA

R

K23

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

K25

FIRE RATED WALL - 2HR

AD PD

CONCRETE COLUMNS AT GARAGE LEVELS SEE STRUCTURAL DRAWINGS. AREA DRAIN.

13A2 13A3 14A3 21A4

PLANTER/AREA DRAIN. ROOF DRAIN BELOW PEDESTAL PAPER

F.E.C.

H.B.

FIRE EXTINGUISHER CABINET - RECESSED AT RESIDENTIAL FLOORS & SURFACE MOUNTED GARAGES (MAX. 75' FROM ANY PORTION OF BUILDING). SEE 7/A906. EXIT SIGN

21A10 23A10

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

DESCRIPTION STAIRS - PRECAST CONCRETE TREADS BY STEPSTONE INC. (SEPSTONEINC.COM) OR APPROVED EQ. STEEL POOL, SEE POOL CONSULTANT DRAWINGS STEEL SPA, SEE POOL CONSULTANT DRAWINGS HANDICPPED LIFT - GARAVENTA GENESIS OPAL MODEL GVL-OP OR APPROVED EQ. WET STANDPIPE. 12" MAX. PROTRUSION FOR POST-MOUNTED OBJECTS, 4" MAX. PROJECTION FOR PROTRUSIONS FROM WALL, OR PROVIDE CANE DETECTION AT THESE LOCATIONS. 36" WIDE METAL FIRE DEPARTMENT ACCESS PARAPET LADDER. SEE 18/A909 MECHANICAL SHAFT - SEE MECH. DWGS.

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO. DATE

HOSE BIB 2% MAX. SLOPE @ CORRIDORS & BALCONIES = 3 HOUR FIRE WALL - REFERENCE DETAILS 15, 16, 17 ON SHEET A901

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

SCALE

1501 03-03-2017 As indicated

SHEET NO.

A209


DE Architects AIA

10H2

10H2

10H2

DUCT FROM BELOW

MECH. PAD TRASH EXHAUST

ED A RCH NS S EMP I A TA

KN

FIRE WALL BELOW

10H2

21A4

STAMP KP

NO. C-13779

21A10

ST A

REN. 6-30-17

66' - 3 3/4"

61' - 6 1/2"

MECH. EQUIP. PAD

21A4

OF

R

T

E

A

10H2

10' - 4"

NI

10H2

15' - 6"

10' - 2"

131' - 6 1/4"

K1 FOS

27' - 0 5/8"

FOS

FOS

FOS

FOS

K2

L IC E DONA

FOS

16' - 10 1/8"

K11

CT TE ERIS K

KM

32' - 5 1/4"

K13

7' - 0"

KO

9' - 10 7/8"

K15

10H2

5' - 0 5/8"

FOS

44' - 7 1/2"

K18

14' - 1 1/4"

8' - 0"

FOS

K21

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

CA L I F

O

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

FOS

FOS 3' - 2 1/2"

3' - 1 7/8"

21A10

10H2

10H2

10H2

10H2

10H2

10H2

10H2

LR

07J9

K21

70' - 10 5/8"

152' - 5 5/8"

K18

FOS

9' - 10 7/8"

FOS

44' - 10 1/4"

FOS

8' - 0"

K12

KA

S FO 10H2

FOS

17' - 0 1/8"

MATCHLINE

22D5

FOS

O

10H2

10H2

MECH. EQUIP. PAD

10H2

10H2

10H2

LQ

2

FOS

K1 ELEVATOR EQUIPMENT ROOM

-4 94'

10H2

TRASH EXHAUST

STORAGE

" 1/8

10H2

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

1' - 11" 14' - 2 7/8"

FOS

10H2 23A2 23A14 07E1

KD

" 1/2

FOS

-6 13'

KB

2

10H2

FOS

KE

1

L10

S FO

FOS

L2

S FO

KF

MATCHLINE

1

10H2

LANKERSHIM + otsego

10H2

10H2

J 10H2 FIRE WALL BELOW

-2 21' " 3/8

10H2

S FO

10H2

10H2

FIRE WALL BELOW

10H2

1 9' -

" 1/2

-7 56' " 3/4

210' - 0 5/8"

I

10H2

10H2

10H2

TRASH EXHAUST

65'

E S FO

0"

10H2 22D5

10H2 10H2

07E1 23A14 MECH. EQUIP. PAD

10H2

07J9 10H2 GREASE DUCT BELOW

10H2

3 5' -

ELEVATOR EQUIPMENT ROOM

-2 18'

" 7/8

" 5/8

21A4 10H2 FIRE WALL BELOW

0 5' -

1 -1 36'

10H2

" 3/4

10H2

FOS 8' - 0"

LB

FOS 17' - 9 3/4"

LC

"

33'

10H2

7' - 0 3/8"

28' - 4"

1"

39' - 3 3/4"

SHEET TITLE S FO

L1

L2

L3.2

L12

ROOF PLAN

S FO

10' - 2"

5

4

N

ROOF PLAN 1/16" = 1'-0" 12. MECHANICAL AND OTHER DUCTS WHICH PENETRATE THE ROOF DECK WILL BE COORDINATED WITH RESPECT TO THEIR LOCATION WITH THE ARCHITECT. DO NOT CUT HOLE IN ROOF DECK PRIOR TO APPROVAL OF LOCATION BY ARCHITECT. 13.PROVIDE SMOKE DETECTORS AT THE TOP OF COMMON STAIRWELLS SERVING TWO OR MORE TENANTS. (HEALTH AND SAFETY CODE 13113.7) 14. ROOFING - CLASS 'A' - SINGLE PLY KEE ROOFING. (45 mil FIBERTITE-SM) SEE CUT SHEETS ON A061.

3/8" / 1'-0" MINIMUM SLOPE U.N.O.

2.GUARDRAIL ADJACENT TO MECHANICAL EQUIPMENT SHALL BE INSTALLED as REQUIRED BY INSPECTOR.

2% MINIMUM SLOPE U.N.O.

3.ALL ROOF WATER TO BE CONDUCTED THROUGH ROOF DRAINS, DOWNSPOUTS AND GUTTERS (NO FREEFALL TO BALCONIES TYPICAL). 4.MECHANICAL SUB-CONTRACTOR TO LOCATE ALL MECHANICAL EQUIPMENT PLATFORMS ON ROOF PRIOR TO CONSTRUCTION OF PLATFORM BY FRAMER. MECHANICAL SUB-CONTRACTOR TO INFORM ARCHITECT OF ANY CLEARANCE PROBLEMS AT THIS TIME. SUPERINTENDENT TO CONFIRM ALL LOCATIONS. NO PLATFORMS ARE PERMITTED OVER BEDROOMS OR LIVING ROOMS.

16. ATTIC ACCESS - PROVIDE A 20"X30" ATTIC ACCESS OPENING AT EACH SEPARATE ATTIC SPACE HAVING A CLEAR HEIGHT OF OVER 30". A 30" MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT OR ABOVE THE ACCESS OPENING.

5.ROOF COVERING SHALL BE CLASS 'A' FIRE RETARDANT. (TITLE 24, CHAPTER 15, 2010 LABC.)

18. ALL PENETRATIONS THROUGH BUILDING PAPER/MEMBRANE WATERPROOFING SHALL BE CAULKED AND SEALED

20. SEAL EXTERNAL CRACKS, JOINTS ETC. WITH CAULKING AND INSTALL PEST-PROOF SCREENS WHERE REQUIRED. 21. INSTALL PLUMBING LINES AS CLOSE TO ROOF AS POSSIBLE.

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

KEYNOTES LEGEND NO.

ROOF DRAIN BELOW PEDESTAL PAPER TWO WAY INSULATION VENT (SEE 14/A909)

07E1

07J9

ROOF TIE-BACK ANCHORS FIRE RATED WALL - 2HR

10H2

= 3 HOUR FIRE WALL - REFERENCE DETAILS 15, 16, 17 ON SHEET A901

21A4

21A10

6.MISCELLANEOUS IRON SUB-CONTRACTOR TO VERIFY ALL LADDERS WITH SUPERINTENDANT IN FIELD PRIOR TO FABRICATION AND INSTALLATION (IF REQUIRED BY OWNER). 7.FRAMER TO PROVIDE BACKING FOR ALL LADDERS AS DIRECTED BY MISCELLANEOUS IRON SUB-CONTRACTOR (IF REQUIRED BY OWNER).

22D5 23A2 23A14

10.DRAIN PIPES INSTALLED IN PARKWAY TO BE IRON OR EQUAL.

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

DESCRIPTION KEE SINGLE PLY MEMBRANE ROOF ICC# ESR-1456 - SRI OF 78 OR BETTER - COOL ROOF (SEE SHEET A060) TWO WAY INSULATION VENT, TYP THROUGHOUT, SEE 14/A909 (1 PER 1,000 SQ. FT.) ROOF ANCHOR, TYP. - SEE EXTERIOR BUILDING MAINTENANCE DRAWINGS WET STANDPIPE. 12" MAX. PROTRUSION FOR POST-MOUNTED OBJECTS, 4" MAX. PROJECTION FOR PROTRUSIONS FROM WALL, OR PROVIDE CANE DETECTION AT THESE LOCATIONS. 36" WIDE METAL FIRE DEPARTMENT ACCESS PARAPET LADDER. SEE 18/A909 ROOF DRAIN (REF. PLUMBING DWGS.) AIR CONDITIONER CONDENSER UNIT MECHANICAL EQUIPMENT PLATFORMS, TYP.

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO. DATE

8.ROOF DRAINAGE SHALL NOT BE CARRIED OVER SIDEWALKS. 9. DISCHARGE OF WATER MUST BE CONDUCTED UNDER SIDEWALK.

19. PROVIDE CONCEALED FIRE SPRINKLER HEADS THROUGHOUT (EXCEPT IN GARAGE)

LEGEND

1. ROOF DECK SLOPE SEE ROOF PLAN. TYPICAL CRICKET SLOPE 1/2" /1'-0".

15. SOLAR PANELS - CONTRACTOR SHALL PROVIDE MINIMUM OF ONE ELECTRICAL CONDUIT (1" MINIMUM) FOR THE FUTURE INSTALLATION OF SOLAR PANELS AT LOCATIONS INDICATED. (PER CALIFORNIA GREEN CODE REQUIREMENT)

17. ATTACH LATH TO SUPPORTS AT 6" O.C. INSTALL LATH USING HOT-DIP GALVANIZED FASTENERS WITH NEOPRENE WASHERS. INSTALL SCREWS TO ENSURE THAT WASHER HAS MAXIMUM CONTACT WITH BUILDING PAPER/MEMBRANE WATERPROOFING. SCREWS SHALL PENETRATE THROUGH EXTERIOR PLYWOOD SHEATING INTO FRAMING.

3/9/2017 2:34:00 PM

ROOF NOTES:

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

SCALE

1501 03-03-2017 As indicated

SHEET NO. 11. PROVIDE FIRE SPRINKLER AT ALL ATTIC SPACES OVER 30".

A210


KEYNOTES NO.

D1.3

W7.3

W3.2a

W7.3

11' - 10 3/4"

D1.3

W3.2a

TYP.

05G10.1

D1.3

05G9 05G10

W7.3a

W3.2a

D1.3

D1.3

W3.2a

W7.3a

D1.3

D2.2

W3.2a

D1.3

W3.2

D1.3

D1.3

W3.2

PROPERTY LINE

05G10

OPEN D1.3

D1.3

W7.3a

D1.3

W3.2a

W7.3a

D1.3

W7.3

W3.2a

D1.3

D1.3

W7.3

05G10.1

D1.2

W7.2a

W3.1a

D1.2

W3.1a

W7.2a

D1.2

D2.1

W3.1a

D1.2

W3.1

D1.2

D1.2

W3.1

03C3 W16 D1.1

W1 L31

L30

D4

L32

D4

L33

D4

L35 W1

L34

L36

D4

L37

W1

L38

D4

L39

W1

L40

D4

W1

L41

W1

L42

D4

L43

05G10

05G10 03C3 L2

03C3

L8

FUTURE TENANT SIGNAGE

L4

1' - 2"

EL: 637.25'

L6

SIGNAGE

FUTURE TENANT SIGNAGE

L11

L15

L13

P7

EL: 629.38' L3

23A12

SIGNAGE

10J4 L1

10B2

L5

M6

L7

L9

L10

L12

M3

M2

FIFTH FLOOR 670.42'

03C3

03C3

03C3

05G10

03C3

05G10

03C3

05G10

07G12

08G3

08B4

03C3

22C5

07G12

03C3

10J3

08G3 03C3

03C3

05G10

08G3

05G10

03C3

03C3

03C3

26A7

07G12

10J7

07G12

05G10

03C3

03C3

10J3

07G12 05G10

08G3

08D3

FOURTH FLOOR 660.17'

08G3

03C3

23A12

03C3

03C3

03C3

23A12

03C3

23A12

10J3

05G10.1

07D7.1

07D7.2

THIRD FLOOR 649.92'

7D10 07G7 07G10

Bath at L-A3 sim3 638.42'

07G11 07G12 07M6 08B4

08D3 AVG. GRADE PLANE 619.82'

05G10

05G10

05G14

MARKET GROUND FLOOR 618.38' 08G3

05G5

05G9

DELIVERY TRUCK EXIT

G22

S4

03C3

SIXTH FLOOR 680.67'

07G12

08G3 09A2.1

09A2.2

23A12

07G12

09A2.3

03C3

EAST ELEVATION LANKERSHIM SIDE (LANKERSHIM BOULEVARD) 3/32" = 1'-0"

3

09A3

07G7

10J6

05G14 10J7

W7.3a

W3

W7

D1

W7.3a

W3.2a

D1.3

W3.2a

W7.3a

D1.3

D1.3

W3.2a

D1.3

W7.3a

W14.1

D1

W7

W3

D1

W3

D1.3

W3

W7

W7.3a

W3.2a

W7.2a

W3.1a

D1.3

D1.2

W3.1a

D1.3

W3.2a

W7.2a

D1.2

D1.3

W7.3a

D1.2

W3.1a

D1.3

W3.2a

PROPERTY LINE

PROPERTY LINE

05G10.1

W7.3a

W7.2a

D1.2

W14 05G10.1

EL: 647.59' W7

D1

W7

D4

W3

L53

L52

W1

D4

L50

L51

W1

D4

L48

D4

L49

L46

L47

W1

L44

D4

L45

W1

W7.1a 05G10

SIGNAGE

03C3 23' - 6 7/8"

L23

L25

08G3

FUTURE TENANT SIGNAGE

L22

L21

L20

L19

FUTURE TENANT L17 SIGNAGE

26A7

SIGN

EL: 629.45' DELIVERY TRUCK AND CUSTOMER ENTRANCE

EL: 629.45'

EL: 629.38'

L16

03C3

L24

03C3 L18

G1

ROOF 702.82'

10J4 10J5

SEVENTH FLOOR 690.92' 10' - 3"

D1.3

W3.2a

10J3

10J6 10J7

22C5 23A9 SIXTH FLOOR 680.67'

10' - 3"

D1.3

10J2.1

AVG HEIGHT OF THE HIGHEST ROOF SURFACE 703.82'

23A9.1

FIFTH FLOOR 670.42' 10' - 3"

W7.3a

RESIDENTIAL SIGNAGE

W7

24" STAINLESS STEEL REVERSE CHANNEL LETTERS - BUILDING ADDRESS METAL CANOPY TYP. COLOR #2 (SEE 28/A904) STEEL FRAME METAL AWNING TYP. W/ MORIN INFILL PANEL (ARIA242) WHOLEFOODS 365 MARQUEE EYEBROW METAL SUNSHADE: 18 GA. 3/32" ROUND & 5/32" STAGGERED GALV. PERFORATED METAL SCREEN WELDED TO STEEL TUBE ROOF OVERHANG STEEL FRAME METAL CANOPY TYP. W/ 18 GA. 3/8" ROUND & 5/8" STAGGERED GALV. 40% PERFORATED METAL SCREEN INFILL GREASE TANK ACCESS STUB METAL GARAGE EXHAUST LOUVERED VENT - RUSKIN ELF375DX ALUMINUM OR APPROVED EQ. - 43% FREE OPENING (REF. MECH. DWGS.) METAL GARAGE EXHAUST LOUVERED VENT - RUSKIN ELF211 ALUMINUM OR APPROVED EQ. - 43% FREE OPENING (REF. MECH. DWGS.) MECHANICAL FRESH AIR INTAKE - RUSKIN ELF375DX ALUMINUM OR APPROVED EQ. 43% FREE OPENING (REF. MECH. DWGS.) J-BOX AND CONDUIT FOR FUTURE SIGNAGE. VERIFY LOCATION W/ TENANT FREESTANDING RESIDENT INTERCOM BOLLARD

23A12

26A7 FOURTH FLOOR 660.17'

27A2 32P4

10' - 3"

D1.3

W3.2a

W3

05G5

W3

10B2

THIRD FLOOR 649.92' 11' - 6"

D1.3

W7.3a

W3.2a

T.O. PARAPET 705.32'

Bath at L-A3 sim3 638.42'

ED A RCH NS S EMP I A TA NO. C-13779

REN. 6-30-17

E

OF

CA L I F

AVG. GRADE PLANE 619.82'

M1

MARKET GROUND FLOOR 618.38' 32P4

23A9

03C3

05G10

32P4

03C3

07G10

03C3

27A2

07G12

05G9 03C3

03C3

07G12

07G12

03A9

10J3 03C3

23A9.1 08G3

05G10

03C3

03C3

07G12

08G3

23A9.1

03C3

03C3

10J3 03C3

03C3

03C3

03C3

03C3

07G12

08G3

03C3

08G3

03C3

10J6

07G7

10J6

10J6

10J5

03C3

SOUTH ELEVATION LANKERSHIM SIDE (OTSEGO STREET) 3/32" = 1'-0" 05G5

10J6

07G7

08G3

10J6

10J5

2' - 6"

10J6

10J6

05G5

10J4

03C3

2 10J5

07G12

O

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

20' - 0 1/2"

D1

84' - 0" FROM AVERAGE GRADE TO AVERAGE HEIGHT OF THE HIGHEST ROOF SURFACE

D1.3

W7

05G10.1

3' - 6" TYP.

W7

05G10

W7

D1

W3

05G9

11' - 10 3/4"

10J7

W3

3/4" CHANNEL SCREED FRY REGLET CONTROL JOINT TYP. CEMENT PLASTER AREA SHALL NOT EXCEED 150 SQFT. WITHOUT A CONTROL JOINT, SEE REFERENCE DETAIL (14/A902)

10J7

2' - 6"

10J7

09A3.2

STAMP

T

3' - 6" TYP.

W14.1

04A6

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

ST A

3' - 6"

W3.2a

TYP.

D1.3

05G9

04A1.1 04A3.1

DE Architects AIA

CT TE ERIS K

PROPERTY LINE

RESIDENTIAL SIGNAGE

SEVENTH FLOOR 690.92'

C.I.P.C. WALL / SHOTCRETE WALL (SEE STRUCT DWGS) C.I.P.C. BENCH ARCHITECTURAL CAST-IN PLACE CONCRETE - 6" BOARD FORM WALL MOCK-UP TO BE APPROVED BY ARCHITECT ARCHITECTURAL CAST-IN PLACE CONCRETE - SMOOTH / SACKED FINISH PAINTED C.M.U. WALL W/ PAINT FINISH C.M.U. PLANTER WALL - BURNISHED C.M.U. BLOCK, STACKED BOND BURNISHED C.M.U. BLOCK, STACKED BOND - JOINTS RAKED AND FINISHED 42" STEEL GUARDRAIL W/ METAL SALES T16E CORRUGATED PERFORATED METAL INFILL. KYNAR FINISH TO BE DETERMINED BY ARCHITECT 42" SIDE MOUNTED ETCHED GLASS GUARDRAIL 42" SURFACE MOUNTED GLASS GUARDRAIL 42" SURFACE MOUNTED ETCHED GLASS GUARDRAIL SIDE MOUNTED METAL SALES T16E CORRUGATED METAL SCREEN METAL SALES CORRUGATED METAL WALL PANEL (T16-E) - HORIZONTAL W/ KYNAR FINISH OR APPROVED EQ METAL SALES CORRUGATED METAL WALL PANEL (T16-E) - VERTICAL W/ KYNAR FINISH OR APPROVED EQ ALUMINUM SIDING TO MATCH ALUMINUM DOOR - FLUSH LOCK SEAM PAINTED 20 GA. GALV. SHEET METAL COPING 20 GA. PAINTED METAL FASCIA LAP SEAMS EQUALLY SPACED DROPPED METAL FRAMED SOFFIT BELOW CONCRETE PODIUM DECK, TYP. 22 GA. ALUMINUM BRAKE METAL DOWNSPOUT NOZZLE, PROVIDE EXTENSION AS NECESSARY, TYP. TORMAX TX9430 FULL BREAKOUT TELESCOPING SLIDER RH, SX-SX-SO. POWDER-COAT TO MATCH PMS 2188. COMMERCIAL OVERHEAD GARAGE DOOR W/ METAL FRAMED GLASS INFILLED SECTIONAL PANELS - COMMERCIAL ENTRY COLORED GLAZING FILM 7/8" (3 COAT SYSTEM) PORTLAND CEMENT PLASTER 20/30 SAND FINISH INTEGRAL COLOR #1 7/8" (3 COAT SYSTEM) PORTLAND CEMENT PLASTER 20/30 SAND FINISH CUSTOM COLOR #1 7/8" (3 COAT SYSTEM) PORTLAND CEMENT PLASTER 20/30 SAND FINISH CUSTOM COLOR #2 1/4" CHANNEL SCREED FRY REGLET CONTROL JOINT, TYP. CEMENT PLASTER AREA SHALL NOT EXCEED 150 SQFT. WITHOUT A CONTROL JOINT, SEE REFERENCE DETAIL (XX/AXXX)

A

W7.3a

03C3

10' - 3"

D1.3

W3.2a

W3.2

10' - 3"

D1.3

3' - 6"

W7.3a

W7.3

W3.2

10' - 3"

D1.3

W3.2a

D1.3

D1.3

ROOF 702.82'

10' - 3"

D1.3

03A9 03C2

10J7

W3.2

W15

AVG HEIGHT OF THE HIGHEST ROOF SURFACE 703.82'

2' - 6"

05G9

03A5

11' - 6"

05G10

T.O. PARAPET 705.32'

20' - 0 1/2"

05G14 10J7

3' - 6" TYP.

05G10

05G10

84' - 0" FROM AVERAGE GRADE TO AVERAGE HEIGHT OF THE HIGHEST ROOF SURFACE

05G10.1

NI

05G10

10J7

DESCRIPTION

= KEYNOTE NO.

R

00A00

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

07G7

L IC E DONA

10J2.1

07G7

LANKERSHIM + otsego

10J2.1

T.O. PARAPET 705.32'

D1

W3

D1

W8

05G5

W7

D1

D1

W7

W3

W3

D1

D1

W8

W3

D1

D1

W7

W3

D1

W3

W7

D1

W3

D1

W7

D1

W8

TYP.

W3

D1

D1

W3

W3

W3

W3

D1

D1

W3

D1

W3

D1

W7

W3

W7

D1

W3

D1

W7

D1

W7

W3

D1

W3

D1

W3

W7

D1

PROPERTY LINE

PROPERTY LINE

3' - 6"

D1

D1

W8

D1

W8

05G5

EL: 647.68' W11

05G5

D9

W11

W11

D7

W11

07M6 D1

W11

W11

D1

D1

W11

D1

LINE OF WALL NOT SHOWN (SEE PLAN)

OTSEGO STREET

PROPERTY WALL

UPPER TERRACE 692.25' SEVENTH FLOOR 690.92'

10' - 3"

W3

D1

SHEET TITLE

ELEVATIONS

SIXTH FLOOR 680.67' 10' - 3"

D1

W7

FIFTH FLOOR 670.42' 10' - 3"

W3

D1

W3

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

FOURTH FLOOR 660.17'

THIRD FLOOR 649.92' THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

Bath at L-A3 sim3 638.42' RECREATION 636.42'

AVG. GRADE PLANE 619.82'

JOB NO.

MARKET GROUND FLOOR 618.38'

DATE

3/9/2017 2:34:38 PM

07M6

07M6

07G11

32P4

SCALE

1

WEST ELEVATION LANKERSHIM SIDE 3/32" = 1'-0"

3

1

1501 03-03-2017 As indicated

SHEET NO.

KEY PLAN 2

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

10' - 3"

W3

W7

3' - 6"

D1

D1

11' - 6"

W3

ROOF 702.82'

20' - 0 1/2"

D1

W7

W3

84' - 0" FROM AVERAGE GRADE TO AVERAGE HEIGHT OF THE HIGHEST ROOF SURFACE

D1

TYP.

W3

TYP.

W3

3' - 6"

D1

11' - 10 3/4"

AVG HEIGHT OF THE HIGHEST ROOF SURFACE 703.82'

A401


KEYNOTES NO.

05G5

09A2.1

05G9

W8a

TYP.

3' - 6"

AVG HEIGHT OF THE HIGHEST ROOF SURFACE 703.82'

06A37

ROOF 702.82'

SEVENTH FLOOR 690.92'

SEVENTH FLOOR 690.92'

07M6

W8a

10' - 3"

09A2.2 FIFTH FLOOR 670.42'

10' - 3"

D1

W8a

FIFTH FLOOR 670.42' 10' - 3"

D1

D1

65' - 4 3/4"

65' - 4 3/4"

05G5

10' - 3"

3' - 6" TYP.

W8a

W8a

10' - 3"

D1

W8a

FOURTH FLOOR 660.17'

10' - 3"

D1

10J2 10J3

THIRD FLOOR 649.92' D1

D1

W11

11' - 6"

D7

THIRD FLOOR 649.92'

11' - 6"

LINE OF WALL NOT SHOWN (SEE PLAN)

09A2.3

09A3.2

FOURTH FLOOR 660.17' D1

09A2.1

S3

10J5

10J6 10J7

Bath at L-A3 sim3 638.42'

Bath at L-A3 sim3 638.42'

10K1

ED A RCH NS S EMP I A TA NO. C-13779

REN. 6-30-17

E

T

D1

W8a

SIXTH FLOOR 680.67'

STAMP

ST A

D1

07G7 07G11

SIXTH FLOOR 680.67' D1

07D7.1

07D7.2

10' - 3"

D1

W8a

05G5

POOL DECK 695.92' UPPER TERRACE 692.25'

10' - 3"

3' - 6" TYP.

11' - 10 3/4"

ROOF 702.82'

05G11

11' - 10 3/4"

AVG HEIGHT OF THE HIGHEST ROOF SURFACE 703.82'

T.O. PARAPET 705.32'

CT TE ERIS K

D1

D1

2' - 6"

2' - 6"

T.O. PARAPET 705.32'

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

OF

A

04A3.1 07G7

DE Architects AIA

NI

03C3

ROOF OVERHANG/CANOPY C.I.P.C. WALL / SHOTCRETE WALL (SEE STRUCT DWGS) ARCHITECTURAL CAST-IN PLACE CONCRETE - SMOOTH / SACKED FINISH PAINTED C.M.U. PLANTER WALL - BURNISHED C.M.U. BLOCK, STACKED BOND 42" STEEL GUARDRAIL W/ METAL SALES T16E CORRUGATED PERFORATED METAL INFILL. KYNAR FINISH TO BE DETERMINED BY ARCHITECT 42" SIDE MOUNTED ETCHED GLASS GUARDRAIL 42" STEEL GUARDRAIL, SEE REFERENCE DETAIL (19/A902) WOOD FRAMED PLANTER W/ POLYETHYLENE PLANTER LINER METAL SALES CORRUGATED METAL WALL PANEL (T16-E) - HORIZONTAL W/ KYNAR FINISH OR APPROVED EQ METAL SALES CORRUGATED METAL WALL PANEL (T16-E) - VERTICAL W/ KYNAR FINISH OR APPROVED EQ PAINTED 20 GA. GALV. SHEET METAL COPING DROPPED METAL FRAMED SOFFIT BELOW CONCRETE PODIUM DECK, TYP. DOWNSPOUT NOZZLE, PROVIDE EXTENSION AS NECESSARY, TYP. 7/8" (3 COAT SYSTEM) PORTLAND CEMENT PLASTER 20/30 SAND FINISH INTEGRAL COLOR #1 7/8" (3 COAT SYSTEM) PORTLAND CEMENT PLASTER 20/30 SAND FINISH CUSTOM COLOR #1 7/8" (3 COAT SYSTEM) PORTLAND CEMENT PLASTER 20/30 SAND FINISH CUSTOM COLOR #2 3/4" CHANNEL SCREED FRY REGLET CONTROL JOINT TYP. CEMENT PLASTER AREA SHALL NOT EXCEED 150 SQFT. WITHOUT A CONTROL JOINT, SEE REFERENCE DETAIL (14/A902)

R

01A15 03A5

05G5

DESCRIPTION

= KEYNOTE NO.

L IC E DONA

00A00

CA L I F

O

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

METAL CANOPY TYP. COLOR #1 (SEE 28/A904) STEEL FRAME METAL AWNING TYP. W/ MORIN INFILL PANEL (ARIA242) METAL SUNSHADE: 18 GA. 3/32" ROUND & 5/32" STAGGERED GALV. PERFORATED METAL SCREEN WELDED TO STEEL TUBE ROOF OVERHANG STEEL FRAME METAL CANOPY TYP. W/ 18 GA. 3/8" ROUND & 5/8" STAGGERED GALV. 40% PERFORATED METAL SCREEN INFILL MANUFACTURED SURROUND FIREPLACE

07M6

COURTYARD LANKERSHIM - NORTH ELEVATION 3/32" = 1'-0"

COURTYARD LANKERSHIM - SOUTH ELEVATION 3/32" = 1'-0"

6

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

7

07G7

CS9 L54

UPPER TERRACE 692.25'

ROOF 702.82'

CS8

UPPER TERRACE 692.25'

FIFTH FLOOR 670.42'

SIXTH FLOOR 680.67'

10J7 3' - 6" TYP.

10' - 3"

05G9

10' - 3"

65' - 4 3/4"

10J7

SEVENTH FLOOR 690.92'

D1

10' - 3"

THIRD FLOOR 649.92'

L29

4

ENTRY COURTYARD LANKERSHIM - NORTH ELEVATION 3/32" = 1'-0"

MEZZANINE LEVEL 628' - 10 9/16"

LINE OF WALL NOT SHOWN (SEE PLAN)

G13

AVG HEIGHT OF THE HIGHEST ROOF SURFACE 703.82'

ENTRY LOBBY OTSEGO - WEST ELEVATION 3/32" = 1'-0"

3

10J6

10J6 07G7

05G5

D1

W8

W8

D1

W8

10' - 3"

D1

W3

W7

W3

D1

W8

W8

D1

W8

10' - 3"

FOURTH FLOOR 660.17'

W7

D1

D1

W3

W7

W3

W7

W3

D1

W8

W8

D1

W8

W8

D1

PROPERTY LINE

10' - 3"

PROPERTY LINE

FIFTH FLOOR 670.42'

W8

D1

W8

THIRD FLOOR 649.92' 11' - 6"

05G5

EL: 647.68' W7 Bath at L-A3 sim3 638.42'

L26

L27

CS14

LINE OF WALL NOT SHOWN (SEE PLAN)

EL: 634.28'

AVG. GRADE PLANE 619.82'

LANKERSHIM BLVD

3/9/2017 2:35:24 PM

ELEVATIONS

SIXTH FLOOR 680.67'

FIFTH FLOOR 670.42'

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

FOURTH FLOOR 660.17'

THIRD FLOOR 649.92'

RECREATION 636.42'

JOB NO.

AVG. GRADE PLANE 619.82' 1

MARKET GROUND FLOOR 618.38' 07M6

03A5

07G11

DATE SCALE

6

05G5

4 5

7

2

ENTRY LOBBY OTSEGO - EAST ELEVATION 3/32" = 1'-0"

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

1

NORTH ELEVATION LANKERSHIM SIDE 3/32" = 1'-0"

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

Bath at L-A3 sim3 638.42'

PROPERTY WALL

MARKET GROUND FLOOR 618.38'

SHEET TITLE

10' - 3"

W7

W3

05G5

SEVENTH FLOOR 690.92'

10' - 3"

D1

W8

3' - 6"

W7

D1

10' - 3"

W8

10' - 3"

D1

W8

3' - 6" TYP.

SEVENTH FLOOR 690.92'

W3

ROOF 702.82'

11' - 6"

UPPER TERRACE 692.25'

W7

TYP.

D1

W3

11' - 10 3/4"

ROOF 702.82'

SIXTH FLOOR 680.67'

S1

T.O. PARAPET 705.32' AVG HEIGHT OF THE HIGHEST ROOF SURFACE 703.82'

84' - 0" FROM AVERAGE GRADE TO AVERAGE HEIGHT OF THE HIGHEST ROOF SURFACE

3' - 6"

05G9

10J2

T.O. PARAPET 705.32'

20' - 0 1/2"

G11

84' - 0" FROM AVERAGE GRADE TO AVERAGE HEIGHT OF THE HIGHEST ROOF SURFACE

TYP.

3' - 6" PROPERTY LINE

05G9

10' - 3"

11' - 10 3/4"

2' - 6"

05G5

G11

Bath at L-A3 sim3 638.42'

AVG. GRADE PLANE 619.82'

07M6

07G7

G11

THIRD FLOOR 649.92'

MARKET GROUND FLOOR 618.38'

05G5

07G7

G11

FOURTH FLOOR 660.17'

2' - 6"

07M6

ENTRY COURTYARD LANKERSHIM - SOUTH ELEVATION 3/32" = 1'-0"

10J7

FIFTH FLOOR 670.42'

Bath at L-A3 sim3 638.42'

LINE OF WALL NOT SHOWN (SEE PLAN)

G11

SIXTH FLOOR 680.67'

M5

Bath at L-A3 sim3 638.42'

5

10J3

11' - 6"

11' - 6"

THIRD FLOOR 649.92'

SEVENTH FLOOR 690.92'

20' - 0 1/2"

10' - 3"

FOURTH FLOOR 660.17' 10J7

10J5

05G9

FIFTH FLOOR 670.42'

FOURTH FLOOR 660.17'

G11

D1

10' - 3"

G11

TYP.

05G9

10' - 3"

65' - 4 3/4"

G11

10' - 3"

SIXTH FLOOR 680.67'

3' - 6"

D1

3' - 6" TYP.

10' - 3"

G11

TYP.

3' - 6"

SEVENTH FLOOR 690.92'

D1

LANKERSHIM + otsego

2' - 6"

ROOF 702.82'

AVG HEIGHT OF THE HIGHEST ROOF SURFACE 703.82'

3' - 6"

G11

07G7

10J7

TYP.

10J7

AVG HEIGHT OF THE HIGHEST ROOF SURFACE 703.82'

8' - 6" T.O. PARAPET TO T.O. STAIR PARAPET

11' - 10 3/4"

EL: 699.90'

T.O. PARAPET 705.32'

11' - 10 3/4"

2' - 6"

T.O. PARAPET 705.32'

10' - 3"

05G5

10' - 3"

05G11

POOL DECK 695.92' UPPER TERRACE 692.25'

10' - 3"

10K1

07G7

84' - 0" FROM AVERAGE GRADE TO AVERAGE HEIGHT OF THE HIGHEST ROOF SURFACE

10J3 10J6

ROOF 702.82'

11' - 6"

10J5

AVG HEIGHT OF THE HIGHEST ROOF SURFACE 703.82'

20' - 0 1/2"

05G5

10' - 3"

11' - 10 3/4"

2' - 6"

T.O. PARAPET 705.32'

KEY PLAN

3

2

1501 03-03-2017 As indicated

SHEET NO.

A402


KEYNOTES LEGEND

05E1

06A33

10J6

T.O. PARAPET 705.32'

2' - 6"

28 A904

Sim

AVG HEIGHT OF THE HIGHEST ROOF SURFACE 703.82'

10J2.1 11' - 10 3/4"

UNIT

UNIT

06A32

UNIT

06A32

07F3

UNIT

UNIT

UNIT

UNIT 06A32

06A32

UNIT

03A10

UNIT

UNIT

UNIT 03A10

03A10

UNIT

UNIT

03A10

UNIT UNIT

16 A903 03A4.1

Sim

08D5

MARKET LINE OF FUTURE MARKET FINISH FLOOR

03A10

20' - 0 1/2"

2 A911

MARKET LINE OF FUTURE MARKET FINISH FLOOR

03A10

15' - 0"

40' - 0"

NEW PL TO CURB

CL STREET TO CURB

9 A904 03A10

10J6 23A9 FIFTH FLOOR 670.42'

23A10 23A14

REN. 6-30-17

E

OF

CA L I F

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

GENERAL NOTES: THIRD FLOOR 649.92'

1. SEE FLOOR PLANS FOR SOFFITS NOT SHOWN IN SECTIONS

Bath at L-A3 sim3 638.42'

10' - 0"

17 A903

P2 594.97'

Sim

07A1

2

LANKERSHIM TRANSVERSE BUILDING SECTION 1 3/32" = 1'-0"

06A33

06A33

23A14

06A33

T.O. PARAPET 705.32'

2' - 6"

06A33

PROPERTY LINE

06A33

23A14

AVG HEIGHT OF THE HIGHEST ROOF SURFACE 703.82'

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

06A32

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

06A32

UNIT

UNIT

10' - 3"

UNIT 07F3

06A32

10' - 3"

06A32

UNIT

06A32

2 A803

UNIT

UNIT

UNIT

UNIT

UNIT

10' - 3"

06A32

UNIT

UNIT

FITNESS CENTER 2 A911

UNIT

UNIT

UNIT

UNIT 03A10

03A10

Sim

11' - 6"

03A10

05G9

23A10

03A10

LINE OF FUTURE MARKET FINISH FLOOR

03A10

ELEVATOR SHAFT

20' - 0 1/2"

RESIDENTIAL TRASH #1

LOBBY #1

03A10

03A10

PARKING 03A10

RAMP PARKING

PARKING 03A2

17 A903

Sim

03A2 17 A903

ELEVATOR PIT

07A1

THIRD FLOOR 649.92'

SHEET TITLE

BUILDING SECTIONS - LANKERSHIM

Bath at L-A3 sim3 638.42' RECREATION 636.42'

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

Sim

P2 594.97'

07A1

JOB NO.

3/9/2017 2:35:32 PM

LEGEND FIRE RATED WALL - 2HR

1 DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

10' - 0"

03A2

FOURTH FLOOR 660.17'

P1 604.97'

03A10

03A4.1

RAMP

FIFTH FLOOR 670.42'

MARKET GROUND FLOOR 618.38'

03A4.1

PARKING

SIXTH FLOOR 680.67'

AVG. GRADE PLANE 619.82'

RAMP

03A10

SEVENTH FLOOR 690.92'

13' - 4 7/8"

CLR.TYP

8' - 2" MIN.

MARKET

CLR. TYP.

RAMP

COMMERCIAL / PARKING

8' - 2" MIN.

11' - 0" MIN. CLR.

9 A904

23A10

11' - 0" MIN. CLR.

ELEC. ROOM

MARKET CLEARANCE

BICYCLE ROOM

MARKET CLEARANCE

23A9 03A10

84' - 0" FROM AVERAGE GRADE TO AVERAGE HEIGHT OF THE HIGHEST ROOF SURFACE

UNIT

ROOF 702.82'

11' - 10 3/4"

UNIT

10' - 3"

10J6

O

FOURTH FLOOR 660.17'

03A2

Sim

PROPERTY LINE

NO. C-13779

P1 604.97'

PARKING

17 A903

10J2.1

AVG. GRADE PLANE 619.82' MARKET GROUND FLOOR 618.38'

03A4.1

PARKING

SIXTH FLOOR 680.67'

ED A RCH NS S EMP I A TA

13' - 4 7/8"

Sim

AT LOADING DOCK

2 A911

MARKET CLEARANCE MARKET CLEARANCE

11' - 0" MIN.

CLR. TYP. CLR. TYP.

11' - 0" MIN.

8' - 2" MIN.

03A10

8' - 2" MIN.

PARKING

14' - 0" MIN. CLR.

03A10

Sim

07J12 08D5

STAMP

LANKERSHIM + otsego

PROPERTY LINE WALL

Sim

11' - 6"

2 A911

50' - 0"

CL STREET TO EXIST. PL

EXIST. PROPERTY LINE

UNIT

NEW PROPERTY LINE

PROPERTY LINE

5' - 0" DEDICATION

10' - 3"

UNIT

10' - 3"

UNIT

CL OF STREET

UNIT

85' - 6" (FROM LOWEST ADJACENT GRADE)

06A32

06A32

06A32

UPI POLYURETHANE PEDESTRIAN COATING (LARR 25261) - W/MONTEREY SAND AGGREGATE AND CLEAR COAT, OR APPROVED EQ. ROOF PARAPET ROLL UP LOADING DOCK DOOR. REFERENCE DOOR SCHEDULE. METAL CANOPY TYP. COLOR #2 (SEE 28/A904) ROOF OVERHANG METAL GARAGE EXHAUST LOUVERED VENT - RUSKIN ELF375DX ALUMINUM OR APPROVED EQ. - 43% FREE OPENING (REF. MECH. DWGS.) MECHANICAL SHAFT - SEE MECH. DWGS. MECHANICAL EQUIPMENT PLATFORMS, TYP.

T

06A32

UNIT

10' - 3"

UNIT

07F3

ST A

1 A803

UNIT

06A32 06A33 06A34 07A1

CT TE ERIS K

UNIT

10' - 3"

06A32

SEVENTH FLOOR 690.92'

84' - 0" FROM AVERAGE GRADE TO AVERAGE HEIGHT OF THE HIGHEST ROOF SURFACE

10J6

UNIT

ROOF 702.82'

05G9

A

06A33

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

23A14

DE Architects AIA

NI

03A10 04A1 04A3.1

C.I.P.C. FOUNDATION (SEE STRUCTURAL) C.I.P.C. COLUMN CAP (SEE STRUCTURAL) C.I.P.C. WALL / SHOTCRETE WALL (SEE STRUCT DWGS) CONCRETE SLAB C.M.U. WALL (REF. STRUC. DWG.) C.M.U. PLANTER WALL - BURNISHED C.M.U. BLOCK, STACKED BOND METAL STUD FRAMED WALL PER STRUCT. & WALL TYPES (SEE A901) 42" SIDE MOUNTED ETCHED GLASS GUARDRAIL WOOD JOIST FLOOR SYSTEM WOOD JOIST ROOF SYSTEM 2X WOOD STUD WALL BELOW GRADE VERTICAL AND HORIZONTAL SURFACE WATERPROOFING W/ TERMINATION BAR AT GRADE TYP. TREMCO SALWATER PARASEAL LG. OR EQ. (LARR# 24709)

R

03A2 03A4.1 03A5

DESCRIPTION

L IC E DONA

NO.

LANKERSHIM LONGITUDINAL BUILDING SECTION 1 3/32" = 1'-0"

= 3 HOUR FIRE WALL - REFERENCE DETAILS 15, 16, 17 ON SHEET A901 = 4 HOUR FIRE ASSEMBLY

DATE SCALE

1501 03-03-2017 As indicated

SHEET NO.

A501


KEYNOTES LEGEND

05E1 05G10 05G10.1

07A1

06A33

07J10 06A33

1 A801

07J10 07J10 06A33

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT 06A32

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

ROOF 702.82'

10' - 3"

06A32

06A32

703.82'

10' - 3"

03E6

UNIT

T.O. PARAPET AVG HEIGHT OF THE HIGHEST ROOF 705.32' SURFACE

BALCONY 05G10.1

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

10' - 3"

06A32

UNIT

06A32

UNIT

03A10

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

10' - 3"

06A32

03A10

BALCONY

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

11' - 6"

03A10 03A10

03A10

03A10 Sim

2 A911

Sim

08E1

FUTURE MARKET FLOOR FINISH

FIFTH FLOOR 670.42'

03A2

FOURTH FLOOR 660.17'

THIRD FLOOR 649.92'

Bath at L-A3 sim3 638.42'

13' - 4 7/8"

MARKET GROUND FLOOR 618.38'

03A2

Sim

Sim

17 A903

P2 594.97'

07A1

6 A804

06A33

06A33

5 A804

05G10

07J10

SPA

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

TYP.

UNIT

06A32

10' - 3"

3' - 3"

06A32

679.51'

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT 06A32

10' - 3"

3' - 3"

06A32

TYP.

UNIT 06A32

669.26'

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

07F3

10' - 3"

3' - 3" TYP.

06A32

UNIT

UNIT

UNIT

UNIT 03A10

03A10

UNIT

UNIT

UNIT

UNIT

UNIT

TYP.

03A10

UNIT

UNIT

UNIT

LOUNGE

UNIT

UNIT

08E1

03A4

03A4.1

03A4

03A2

SEVENTH FLOOR 690.92'

SIXTH FLOOR 680.67'

FIFTH FLOOR 670.42'

FOURTH FLOOR 660.17'

SHEET TITLE

THIRD FLOOR 649.92'

Bath at L-A3 sim3 638.42'

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

03A10

PARKING

5 A903

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

13' - 4 7/8"

CLR. TYP.

03A10

P1 604.97' 03A2

PARKING

03A2

Sim

P2 594.97'

JOB NO.

Sim

LEGEND

07A1

LANKERSHIM LONGITUDINAL BUILDING SECTION 2 1 3/32" = 1'-0"

FIRE RATED WALL - 2HR = 3 HOUR FIRE WALL - REFERENCE DETAILS 15, 16, 17 ON SHEET A901 = 4 HOUR FIRE ASSEMBLY

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

AVG. GRADE PLANE 619.82'

17 A903

3/9/2017 2:35:41 PM

BUILDING SECTIONS - LANKERSHIM

MARKET GROUND FLOOR 618.38'

8' - 2" MIN.

MARKET CLEARANCE

03A10

11' - 0" MIN. CLR.

9 A904

MARKET

CLR. TYP.

23A10

03A4.1

COMMERCIAL / PARKING 8' - 2" MIN.

RAMP

RESIDENTIAL TRASH #2

MARKET CLEARANCE

MAIL ROOM

11' - 0" MIN. CLR.

03A10

POOL DECK 695.92' UPPER TERRACE 692.25'

10' - 0"

03A3

03A10

11' - 6"

03A10

03A10

20' - 0 1/2"

Sim

AVG. GRADE PLANE TO B.O. BALCONY

648.75'

COMMON SPACE

17 A903

3' - 3"

28' - 11"

2 A911

06A32

10' - 3"

659.01'

ROOF 702.82'

84' - 0" FROM AVERAGE GRADE TO AVERAGE HEIGHT OF THE HIGHEST ROOF SURFACE

DECK

GAME ROOM

UNIT 06A32

Sim

AVG HEIGHT OF THE HIGHEST ROOF SURFACE 703.82'

3' - 8"

UNIT

7 A911

6' - 10 3/4"

LOUNGE UNIT

T.O. PARAPET 705.32'

Sim 07J10

UNIT

Sim

7 A911

1' - 4"

PROPERTY LINE

7 A911

23A14

PROPERTY LINE

06A33

LANKERSHIM LONGITUDINAL BUILDING SECTION 3 3/32" = 1'-0"

2' - 6"

2

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

GENERAL NOTES:

P1 604.97'

PARKING

O

1. SEE FLOOR PLANS FOR SOFFITS NOT SHOWN IN SECTIONS

03A10

PARKING

CA L I F

SIXTH FLOOR 680.67'

AVG. GRADE PLANE 619.82'

5 A903

OF

SEVENTH FLOOR 690.92'

10' - 0"

CLR. TYP.

8' - 2" MIN.

03A10

MARKET CLEARANCE

03A10

03A10

17 A903

08E1

03A4.1

MARKET

11' - 0" MIN. CLR.

9 A904

2 A911

MARKET CLEARANCE

CLR.TYP

MAIN LOBBY

8' - 2" MIN.

RESIDENTIAL & COMMERCIAL ENTRY/EXIT

11' - 0" MIN. CLR.

COMMERCIAL / PARKING

03A4.1

20' - 0 1/2"

03A10

UPPER TERRACE 692.25'

07J12 08E1 23A10 23A14

E

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

1 A802

07J10

Sim

REN. 6-30-17

LANKERSHIM + otsego

7 A911

84' - 0" FROM AVERAGE GRADE TO AVERAGE HEIGHT OF THE HIGHEST ROOF SURFACE

06A33

7 A911

Sim

2' - 6"

7 A911

Sim

1' - 4" 10' - 6 3/4"

3 A801

PROPERTY LINE

PROPERTY LINE

01A15

NO. C-13779

T

06A33

UPI POLYURETHANE PEDESTRIAN COATING (LARR 25261) - W/MONTEREY SAND AGGREGATE AND CLEAR COAT, OR APPROVED EQ. ROOF PEDESTAL PAVER SYSTEM, BY TILE TECH PAVERS OR APPROVED EQ, - SINGLE PLY ROOFING SYSTEM BELOW. (REF. LANDSCAPE DWGS.) ROOF PARAPET CLEAR ANODIZED STOREFRONT SYSTEM MECHANICAL SHAFT - SEE MECH. DWGS. MECHANICAL EQUIPMENT PLATFORMS, TYP.

ED A RCH NS S EMP I A TA

ST A

07F3

STAMP

CT TE ERIS K

06A32 06A33 06A34 06A37

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

A

04A1 04A3.1

DE Architects AIA

NI

03A10 03E6

ROOF OVERHANG/CANOPY C.I.P.C. FOUNDATION (SEE STRUCTURAL) C.I.P.C. STAIRS C.I.P.C. COLUMN (SEE STRUCTURAL) C.I.P.C. COLUMN CAP (SEE STRUCTURAL) C.I.P.C. WALL / SHOTCRETE WALL (SEE STRUCT DWGS) CONCRETE SLAB STAIRS - PRECAST CONCRETE TREADS BY STEPSTONE INC. (SEPSTONEINC.COM) OR APPROVED EQ. C.M.U. WALL (REF. STRUC. DWG.) C.M.U. PLANTER WALL - BURNISHED C.M.U. BLOCK, STACKED BOND METAL STUD FRAMED WALL PER STRUCT. & WALL TYPES (SEE A901) 42" SURFACE MOUNTED GLASS GUARDRAIL 42" SURFACE MOUNTED ETCHED GLASS GUARDRAIL WOOD JOIST FLOOR SYSTEM WOOD JOIST ROOF SYSTEM 2X WOOD STUD WALL WOOD FRAMED PLANTER W/ POLYETHYLENE PLANTER LINER BELOW GRADE VERTICAL AND HORIZONTAL SURFACE WATERPROOFING W/ TERMINATION BAR AT GRADE TYP. TREMCO SALWATER PARASEAL LG. OR EQ. (LARR# 24709)

R

01A15 03A2 03A3 03A4 03A4.1 03A5

DESCRIPTION

L IC E DONA

NO.

DATE SCALE

1501 03-03-2017 As indicated

SHEET NO.

A502


4 E

U4

11' - 8 1/4"

W12

U3

S FO

BEDROOM

" 1/2

4'

1 A206a

3

115 0 1' -

U4 0" 0 2' -

"

10' - 0 5/8"

. LR "C

AD

L3.2

SD

1' - 0" CLR.

W12

7' -

/8" 41

11"

PD

W12

A905

2 A637b

12

W/D FRONTLOADED

7' -

PD

/8" 31 -2 18'

" 3/8

18' - 2 1/2"

12' - 4"

1' - 7 3/4"

BEDROOM

6' - 11 3/4"

LC

FOS

W3

W7

PROVIDE HARD WIRE INTERCONNECTED SMOKE DETECTORS WITH BATTERY BACKUP. SMOKE DETECTORS REQUIRED IN THE FOLLOWING LOCATIONS (310.9.1.4) A) EACH SLEEPING ROOM B) CENTRALLY LOCATED IN CORRIDORS GIVING ACCESS TO EACH SLEEPING ROOM DETECTORS SHALL SOUND AN ALARM AUDIBLE IN ALL SLEEPING AREAS OF THE DWELLING. HARDWIRED DETECTORS ARE REQUIRED IN EXISTING DWELLINGS WHEN AN ADDITION, ALTERNATION, OR REPAIR IS MADE. BATTERY TYPE DETECTORS ARE NOT ALLOWED AND MAY NOT BE USED IN LIEU OF HARD-WIRED DETECTORS (310.9.1.2,SM FIRE DEPARTMENT POLICY), SEE ELECTRICAL DWGS

3

1

4' - 4 3/8"

7' - 9 7/8"

6' - 1 7/8"

4' - 5"

2

W12

14' - 9 5/8" 8 3/4"

10' - 3"

4' - 10 1/4"

SD

BEDROOM D1

5' - 1 1/4"

CO

A CARBON MONOXIDE + SMOKE DETECTOR COMBO ALARM SHALL BE INSTALLED OUTSIDE OF EACH BEDROOM ON EACH LEVEL PER REQUIREMENTS CBC 2013 SOUND WALL -STC RATING 50 REQUIRED / 1HR RATED REFER TO DETAIL W04/A901, WALL TYPE W021 @ PARTY WALLS

3' - 9 5/8" 6' - 2 3/4"

6' - 8"

CLR.

PLUMBING WALL

WALK-IN CLOSET

ROOM 1 HABITABLE AREA: 200 S.F.

14

W8a

A905

8' - 4 3/4"

W12b

BEDROOM

1 A638

ROOM 2 HABITABLE AREA: 393 S.F.

Sim

NATURAL LIGHT (8%) REQUIRED: 393 S.F. X 8% = 31.4 S.F. PROVIDED: 64 S.F.

W12 2' - 6 1/8"

5' - 8 5/8"

E.Q.

W12 3' - 8"

W12a

W12

UNIT L-U SIM2 ( L501 ) 1/4" = 1'-0" 3

1 A636

1 A640

A905

Sim

U1

0"

KITCHEN

W12

11' - 10 1/2"

W12

4' - 9"

CO SD

LIVING / DINING W12

L9

SD 2' - 0"

W12

L3.2

W12a

FRONTLOADED

W3

AD

6"

W04

WALK-IN CLOSET

W12

8' - 4 3/4"

4' - 4 3/8"

W7

1 A638

3' - 9 5/8"

Sim

VENTILATION (4%) REQUIRED: 415 S.F. X 4% = 16.6 S.F. PROVIDED: 32 S.F.

BATHROOM

W08a

ROOM 2 HABITABLE AREA: 160 S.F. NATURAL LIGHT (8%) REQUIRED: 160 S.F. X 8% = 12.8 S.F. PROVIDED: 32 S.F. VENTILATION REQUIRED: 160 S.F. X 4% = 6.4 S.F. PROVIDED: 10.7 S.F.

10' - 0 5/8"

FOS

4' - 5" 11' - 5 1/8"

3' - 7 7/8"

9' - 11 3/4"

2' - 6 3/4"

AD

1.CONTRACTOR TO VERIFY IN FIELD ALL GRIDLINES AND DIMENSIONS PRIOR TO CONSTRUCTION. 2.SEE 1/8" PLANS FOR ADDITIONAL INFO. NOT SHOWN. 3.CONTRACTOR TO VERIFY ALL WINDOW TYPES, LOCATION, AND ORIENTATION WITH UNIT PLANS, WINDOW SCHEDULE, AND ELEVATIONS. WINDOW TYPES ON ELEVATION SUPERCEDES THOSE LISTED ON THE UNIT PLANS WHERE THERE IS A DISCREPANCY. OPENING AND WINDOW SIZES SHOWN ON THE WINDOW SHEDULE TO SUPERCEDE ALL OTHER INFORMATION. 4.ARCHITECT TO APPROVE ALL SOFFIT LOCATIONS 5.CONTRACTOR SHALL PROVIDE CONCEALED HEADS FOR ALL FIRE SPRINKLERS. 6.SEAL EXTERNAL CRACKS, JOINTS ETC. WITH CAULKING AND INSTALL PEST-PROOF SCREENS WHERE REQUIRED. 7.PROVIDE SMITTY PAN @ ALL W/D CLOSETS. 8. CONTRACTOR SHALL PROVIDE 3/4" SUPER W PADS @ EACH W/D CLOSET (TOTAL OF 4 PER CLOSET) MOUNT W/D OVER PADS. 9. PROVIDE 34"X6" METAL LOUVER OVER WASHER /DRYER CLOSET DOOR, TYPICAL AT ALL WASHER / DRYER CLOSETS. 10. REFER TO SHT. A638 - A642 FOR BATHROOM PLANS AND ELEVATIONS 11. REFER TO SHT. A636 - A637 FOR KITCHEN PLANS AND ELEVATIONS 12. REFER TO 1/4" PLANS (SHTS. 601-628) FOR BALCONY DIMENSIONS AND DRAINAGE INFO.COORDINATE DRAIN LOCATIONS AND DRAINAGE WITH FRAMING LAYOUT. 13. SEE ALSO ELEVATION SHEETS A-401-A405 CONTRACTOR V.I.F. ALL WINDOWS TYPES PRIOR OF INSTALLATION 14. CONTRACTOR TO PROVIDE BACKING FOR ALL CLOSET SHELVING & BATHROOM ACCESSORIES. 15. CONTRACTOR TO PROVIDE LIGHT/FAN COMBO IN ALL BEDROOMS, TYP. 16. THE FLOW RATES FOR ALL PLUMBING FIXTURES SHALL COMPLY WITH THE MAXIMUM FLOW RATES SPECIFIED IN CAL GREEN SECTION 4.303.1 17. REFER TO 15&16/A905 FOR LINEN CABINETRY & SHELVES 18. REFER TO 14/A905 FOR CLOSET SHELVES IN BEDROOMS AND CLOSETS THAT ARE MORE THAN 5'-0" IN WIDTH - WALK IN CLOSETS 19. REFER TO 13/A905 FOR CLOSET SHELVES THAT ARE NOT IN BEDROOMS OR SMALLER THAN 5'-0" IN WIDTH 20. REFER TO 12/A905 FOR CLOSETS LARGER THAT 5'-0" IN WIDTH, BUT NOT WALK IN CLOSETS 21. PENETRATION OF THE 1 HOUR CEILING BY DUCTS FOR THE FAU AND THE STOVE HOOD REQUIRE DAMPERS. ATTIC UNITS REQUIRE DAMPERS AT ALL CEILING PENETRATIONS. 22. EXHAUST FANS FROM THE BATHROOM MUST ENTER THROUGH THE WALL. DAMPERS ARE REQUIRED IF THE CEILING IS PENETRATED. 23. REFER TO A063 FOR ALL FRESH INTAKE AND EXHAUST VENT CAPS. 24. REFER TO A063 FOR ALL DRYER VENT CAPS. 25. MEDIA BOX SHALL BE RECESSED IN WALL, TYP. 26. SEE MECHNICAL DWGS FOR SOFFITS NOT ILLUSTRATED ON ARCHITECTURAL DWGS. 27. AT 2ND FLOOR UNITS - AT CONCRETE WALL LOCATIONS - CONTRACTOR SHALL PROVIDE SURFACE MOUNTED RIGID METAL CONDUIT FOR RECEPTACLES AND OUTLETS, REFERENCE ELECTRICAL DRAWINGS FOR LOCATIONS. CONDUIT FROM OUTLES/RECEPTACLE SHALL RUN VERTICALLY AGAINST WALL AND HORIZONTALLY AGAINST CONCRETE CEILING. 28. WHERE SHELVING IS SPECIFIED, CONTRACTOR SHALL PROVID A MINIMUM OF 6 SHELVES, PAINTED POPLAR WOOD.

NATURAL LIGHT (8%) REQUIRED: 415 S.F. X 8% = 33.2 S.F. PROVIDED: 64 S.F.

W08a

5' - 4 3/4"

2

ROOM 1 HABITABLE AREA: 415 S.F.

LB W01

1

5' - 6 3/4"

W08a

LC

3/9/2017 2:36:29 PM

W7

3

CLR.

W12

D1

W12

U15

W/D

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

W12 2' - 0"

W3

W/D FRONTLOADED

U4

W12

UNIT L-U SIM1 ( L401 ) 1/4" = 1'-0"

W12

W12

12' - 6 3/4"

A905

UNIT L-U SIM4 ( L701 ) 5 1/4" = 1'-0"

2

D1

1' - 8 1/2"

14' - 9 5/8"

BEDROOM

U15

14

6' - 2 3/4"

3' - 10 7/8"

FOS

FOS

LC

VENTILATION REQUIRED: 237 S.F. X 4% = 9.5 S.F. PROVIDED: 6.8 S.F.

11' - 4 7/8"

W7

11' - 0"

9' - 11 3/4"

NATURAL LIGHT (8%) REQUIRED: 237 S.F. X 8% = 19 S.F. PROVIDED: 13.5 S.F.

W12a

FRONTLOADED

38' - 9 7/8"

W12

4' - 4 3/8"

6' - 1 7/8"

W12

W/D

5' - 6 3/4" 11' - 8 1/4"

ROOM 3 HABITABLE AREA: 237 S.F.

1' - 4 1/8"

BEDROOM

3' - 9 5/8" 3' - 7 1/2"

U4

2' - 0"

SD U15

LC

A905

NATURAL LIGHT (8%) REQUIRED: 329 S.F. X 8% = 26.3 S.F. PROVIDED: 64 S.F. VENTILATION REQUIRED: 329 S.F. X 4% = 13.1 S.F. PROVIDED: 32 S.F.

BEDROOM

D1

W3

13

ROOM 2 HABITABLE AREA: 329 S.F.

4' - 4 3/8"

LIVING ROOM

W12

W12

BATHROOM

Sim

3' - 0"

SD

U3

BEDROOM

1 A640

W12

UNIT L-V ( L335, L436, L535, L636 ) 1/4" = 1'-0"

W08

WALK-IN CLOSET

U7

U3

CO

VENTILATION (4%) REQUIRED: 198 S.F. X 4% = 7.9 S.F. PROVIDED: 6.8 S.F.

W08

1' - 6"

15' - 5 1/2"

ROOM 1 HABITABLE AREA: 198 S.F. NATURAL LIGHT (8%) REQUIRED: 198 S.F. X 8% = 15.8 S.F. PROVIDED: 13.5 S.F.

5' - 7 7/8"

6' - 9 7/8"

11' - 1 5/8"

5' - 4 1/8"

7' - 11"

14

11"

2' - 0 5/8"

5' - 11 5/8"

1' - 0" 1'-0" MIN. CLR.

Sim

11"

W08a

1' - 2 7/8" 1'-0" MIN.CLR.

2' - 4 3/4"

12' - 10 3/8"

PANTRY

2

1' - 3 5/8" 4' - 5 1/4"

27' - 11 1/2"

2' - 4 5/8"

2' - 2 5/8"

VENTILATION REQUIRED: 199 S.F. X 4% = 15.9 S.F. PROVIDED: 8 S.F.

W12b

BATHROOM

A905

Sim

NOTES

1

U1

3 A636

NATURAL LIGHT (8%) REQUIRED: 199 S.F. X 8% = 15.9 S.F. PROVIDED: 24.5 S.F.

15' - 3 3/4"

49' - 11 3/4"

8' - 4 3/4"

4' - 3 3/8"

2' - 6"

SEE DETAIL 12,13,14/A905 FOR TYPICAL SHELVES IN CLOSETS, U.N.O.

L3.1

W08a

5' - 8 5/8"

KITCHEN

3

U4 U4

13

13' - 4"

W12

U6

10' - 3 5/8"

L3.2

W12

W12

W12

Sim

WALK-IN CLOSET

BALCONY SLOPE AND/OR SLOPE TO DRAIN, MAX 2% TYPICAL

ROOM 3 HABITABLE AREA: 199 S.F.

11' - 0"

W12

FRONTLOADED

4' - 3 3/4"

2' - 0 1/8"

U15

A905

MIN. CLR. 3' - 0"

SD CO

2' - 4 3/4"

U3

W/D

1'0"- 5 1/8"

14

E.Q.

W08a

3' - 8 1/4"

W03

10' - 0 5/8"

4' - 5"

FOS

SD

4' - 7"

7' - 4 3/4"

CO SD

W12

W12

LIVING / DINING

W12

W12

W08a

W03

8' - 4 1/8"

9' - 11 1/4"

W12

3'-8"MIN.CLR.

SD

2 A638

6' - 11"

W12

W12a

U4

3' - 9 1/4"

ELECTRICAL PANEL

VENTILATION REQUIRED: 393 S.F. X 4% = 15.7 S.F. PROVIDED: 32 S.F.

W04 3' - 9 5/8"

BATHROOM

RECESSED MEDICINE CABINET SEE DETAIL 5/A905 FOR TYPICAL INSTALLATION AT RATED WALLS

2' - 0"

BEDROOM

A905

6

URADEK WATERPROOFING W/ CLEAR TOP COAT, 30 MESH SAND (LARR 25261)

D1

3' - 9 1/8"

14

4' - 11 1/2"

2x4 WALL AT INTERIOR, 2X6 WALL AT EXTERIOR UNLESS NOTED OTHERWISE (ALL EXTERIOR WALLS TO HAVE R-19 INSULATION)

NATURAL LIGHT (8%) REQUIRED: 200 S.F. X 8% = 16 S.F. PROVIDED: 24.5 S.F. VENTILATION (4%) REQUIRED: 200 S.F. X 4% = 8 S.F. PROVIDED: 12.3 S.F.

3' - 0" CLR.

10' - 9 3/8"

/4" 03

WALK-IN CLOSET

7'

6' - 6 1/2"

W04

W8a

O

-BATHROOM EXHAUST FANS SHALL BE ENERGY STAR COMPLIANT AND BE DUCTED TO TERMINATE TO THE OUTSIDE OF THE BUILDING -BATHROOM EXHAUST FANS, NOT FUNCTIONING AS A COMPONENT OF A WHOLE HOUSE VENTILATION SYSTEM, MUST BE CONTROLLED BY A HUMIDISTAT WHICH SHALL BE READILY ACCESSIBLE

W12

L22

12' - 7 3/8"

REFERENCE CALL OUT (TOP = DETAIL NO. BOTTOM = SHEET)

VENTILATION REQUIRED: 199 S.F. X 4% = 15.9 S.F. PROVIDED: 12.3 S.F.

11' - 6 5/8"

UNIT L-W ( L331, L432, L531, L632 ) 7 1/4" = 1'-0" 8' - 9 5/8"

XXX AXXX

ROOM 3 HABITABLE AREA: 199 S.F.

W12

FOS

6' - 7 5/8"

CA L I F

EXHAUST FAN, SEE BATHROOM PLANS A638- A642, SEE ELEC. AND MECH. DWGS. REFER TO SHEET A041 FORM GRN 14 NOTES 25 & 26

NATURAL LIGHT (8%) REQUIRED: 199 S.F. X 8% = 15.9 S.F. PROVIDED: 24.5 S.F.

2' - 4 3/4"

OF

DOOR TYPE - SEE SHEET A091 WALL TYPE SEE SHEETS A901

VENTILATION REQUIRED: 393 S.F. X 4% = 15.7 S.F. PROVIDED: 32 S.F.

W08a 4' - 3 1/8"

E

WINDOW TYPE - SEE SHEET A092

WXX

NATURAL LIGHT (8%) REQUIRED: 393 S.F. X 8% = 31.4 S.F. PROVIDED: 64 S.F.

AD

10' - 10 1/4"

REN. 6-30-17

KITCHEN

LIVING / DINING

11"

A905

FRONTLOADED

11"

10' - 10 7/8"

" 1/4

W08

PX2

ROOM 2 HABITABLE AREA: 393 S.F.

12' - 3 7/8"

AD

115

U9 U15

A

VENTILATION (4%) REQUIRED: 214 S.F. X 4% = 8.5 S.F. PROVIDED: 8 S.F.

W/D

DW

6' - 0 1/2"

11' - 3 3/4"

9 4' -

11' - 10 7/8"

BEDROOM

U17 W08

3" R. 1' - N.CL I "M 1'-0

L9

ROOM 1 HABITABLE AREA: 214 S.F.

NO. C-13779

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

LEGEND

NATURAL LIGHT (8%) REQUIRED: 214 S.F. X 8% = 17 S.F. PROVIDED: 24.5 S.F.

Sim

11' - 6 7/8"

UNIT L-U SIM3 ( L601 ) 1/4" = 1'-0"

W04

13

U1

4

"

/4" 43

W08

FOS

U3

Sim

ED A RCH NS S EMP I A TA

T

W12

0 2' -

" 1/4 11 9' -

2' -

1 6' -

LINE OF FURRED WALL BELOW

4

KITCHEN

2

ST A

/8" 67

W08

11"

Sim

1

U4

2 A638

-SHEAR WALLS TO BE LOCATED PER STRUCTURAL PLANS. DO NOT DEVIATE FROM LOCATIONS SHOWN WITHOUT CONSENT OF ARCHITECT. -VERIFY ALL WINDOWS, DOORS, AND BALCONY LOCATIONS WITH 1/8" PLANS AND ELEVATIONS. -PLUMBING TO BE INSTALLED IN A MANNER TO PERMIT REPOSITIONING OF THE SINK AND COUNTERTOP. -DO NOT PROVIDE ACCESS PANELS FOR BATHTUBS. ALL PLUMBING TO BE WITHOUT SLIP JOINTS. -REFER TO ELECTRICAL DRAWING FOR ADDITIONAL ELECTRICAL LAYOUT. -REFER TO MECHANICAL DRAWING FOR ADDITIONAL MECHANICAL REQUIRED. -REFER TO SHEETS A020 FOR GENERAL NOTES. -REFER TO SHEETS A030-A034 FOR HANDICAP NOTES.

D

SD

GENERAL NOTES STAMP

SD

D1

1 A636

2. EVERY SPACE INTENDED FOR HUMAN OCCUPANCY SHALL BE MECHANICALLY VENTILATED PER SECTION 1205.2

13' - 8 7/8"

CT TE ERIS K

0 4' -

W12 CO

W08a

4 3' -

3' - 10 7/8"

Sim

1 A638

W12b

" 1/8

9' - 11 3/4"

L12

BATHROOM

LIVING / DINING

8' - 2 1/4"

W12

8" 3' . LR .C MIN

4'

" 1/4 9 -

4' - 4 5/8"

A

W12

5' - 4 3/8"

NOTE: -ALL KITCHENS HAVE A RANGE W/ OVEN, DUCTED EXHAUST HOOD, REFRIGERATOR, DISHWASHER, DISPOSAL, & STACK OR SIDE BY SIDE WASHER/DRYER. -ALL UNITS HAVE HEATING & AIR CONDITIONING. -REFER TO 1/4" KITCHEN & BATHROOM PLANS FOR MORE INFORMATION. -CONTRACTOR TO VERIFY MIN. CLEARANCES, PER MANUFACTURER, FOR ALL WASHER DRYER UNITS

NI

W12 WALK-IN CLOSET

WALK-IN CLOSET

LC

3' - 7 3/4"

7' - 9 3/8"

3' - 7 7/8" 50' - 5 1/8"

12' - 9"

L3.2

15' - 3 3/4"

L3.2

1

UNIT L-U ( L301 ) 1/4" = 1'-0"

9' - 11 3/4"

4' - 3 3/4"

5' - 6 1/4"

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

"

8' - 4 3/4"

'12

5 8' -

6' - 2 3/4"

BATHROOM /8" 05

LC FOS

1. EVERY SPACE INTENDED FOR HUMAN OCCUPANCY SHALL BE PROVIDED WITH NATURAL LIGHT BY MEANS OF EXTERIOR GLAZED OPENINGS (8% OF FLOOR AREA PER IN ACCORDANCE WITH SECTION 1205.2)OR SHALL BE PROVIDED WITH ARTIFICIAL LIGHT THAT IS ADEQUATE TO PROVIDE AN AVERAGE ILLUMINATION OF 10 FOOT-CANDLES OVER THE AREA OF THE ROOM AT A HEIGHT OF 30 INCHES ABOVE THE FLOOR LEVEL. (1205.1 AND 1205.3)

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

ROOM 3 HABITABLE AREA: 147 S.F.

RCP LEGEND GYP. BD. CEILING AT 9'-0" A.F.F., U.N.O.

NATURAL LIGHT (8%) REQUIRED: 147 S.F. X 8% = 11.8 S.F. PROVIDED: 32 S.F.

LANKERSHIM + otsego

A905

W3

APPLIANCE NOTES

NOTE:

DE Architects AIA

R

W7

14

W12

6' - 1 7/8"

A905

" 3/4

8 3/4"

/4" 51

U15

4' - 4 3/8"

14

0" -1 18'

3' -

0 5' -

1"

ALL DIMENSIONS ARE TO FACE OF STUD UNLESS NOTED OTHERWISE. AREA OF UNITS IS CALCULATED FROM INSIDE FACE OF WALL EXCEPT AT COMMON WALLS WHERE IT IS CALCULATED FROM THE CENTERLINE.

UNIT L-U = 1126 S.F. UNIT L-U SIM1 = 1126 S.F. UNIT L-U SIM2 = 1110 S.F. UNIT L-V = 1158 S.F. UNIT L-W = 1041 S.F.

5' - 4 3/8" "

33'

UNIT AREA:

L IC E DONA

D1

10" 8 7' -

5

DIMENSIONING NOTES

W12

4' - 4 3/8"

9' -

LIGHT & VENTILATION

SHEET TITLE

LANKERSHIM UNIT PLANS

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO. DATE SCALE

CASEWORK SOFFIT VENTILATION REQUIRED: 147 S.F. X 4% = 5.9 S.F. PROVIDED: 10.7 S.F.

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

1501 03-03-2017 As indicated

SHEET NO. EXTERIOR CEMENT PLASTER CEILING AT 8'-0" A.F.F., U.N.O.

A617


K10 K6 K11

1. EVERY SPACE INTENDED FOR HUMAN OCCUPANCY SHALL BE PROVIDED WITH NATURAL LIGHT BY MEANS OF EXTERIOR GLAZED OPENINGS (8% OF FLOOR AREA PER IN ACCORDANCE WITH SECTION 1205.2)OR SHALL BE PROVIDED WITH ARTIFICIAL LIGHT THAT IS ADEQUATE TO PROVIDE AN AVERAGE ILLUMINATION OF 10 FOOT-CANDLES OVER THE AREA OF THE ROOM AT A HEIGHT OF 30 INCHES ABOVE THE FLOOR LEVEL. (1205.1 AND 1205.3)

13' - 7 5/8"

W8

13' - 5 5/8"

BALCONY

GENERAL NOTES

KM

STAMP

D1

16' - 11 3/4" BALCONY

16' - 11 3/4"

2. EVERY SPACE INTENDED FOR HUMAN OCCUPANCY SHALL BE MECHANICALLY VENTILATED PER SECTION 1205.2

KN

W12

3' - 6 1/8"

2

UNIT K-E SIM 13 ( K409, K609 ) 1/4" = 1'-0"

9

UNIT K-E SIM8 ( K513, K709) 1/4" = 1'-0"

4

UNIT K-E SIM3 ( K308, K408, K608, K706 ) 1/4" = 1'-0"

ROOM 1 HABITABLE AREA: 311 S.F.

NATURAL LIGHT (8%) REQUIRED: 311 S.F. X 8% = 25 S.F. PROVIDED: 64 S.F. VENTILATION (4%) REQUIRED: 311 S.F. X 4% = 12.5 S.F. PROVIDED: 32 S.F.

K12

K10 9' - 1 3/4"

K10

K8 7' - 6 1/4"

8' - 8 1/2"

K5

4' - 7 3/4"

W12

XXX AXXX

REFERENCE CALL OUT (TOP = DETAIL NO. BOTTOM = SHEET)

5' - 9 7/8"

-BATHROOM EXHAUST FANS SHALL BE ENERGY STAR COMPLIANT AND BE DUCTED TO TERMINATE TO THE OUTSIDE OF THE BUILDING -BATHROOM EXHAUST FANS, NOT FUNCTIONING AS A COMPONENT OF A WHOLE HOUSE VENTILATION SYSTEM, MUST BE CONTROLLED BY A HUMIDISTAT WHICH SHALL BE READILY ACCESSIBLE

BALCONY

6' - 0"

KN KM

BALCONY

KN

1' - 11"

W8

W8

SD

KM 2

BALCONY

9' - 7"

13' - 5 5/8"

16' - 10 3/8"

1

1 1/4"

3' - 6 1/8"

K12

K10

K10

UNIT K-E SIM12 ( K309, K509, K705 ) 13 1/4" = 1'-0"

K8

ROOM 1 HABITABLE AREA: 199 S.F.

UNIT K-E SIM7 ( K411, K611 ) 8 1/4" = 1'-0"

K14

NATURAL LIGHT (8%) REQUIRED: 199 S.F. X 8% = 16 S.F. PROVIDED: 13.5 S.F.

UNIT K-E SIM2 ( K314, K414, K514, K614, K712 ) 3 1/4" = 1'-0"

K10

K12 6' - 6 1/4"

W12

D1

16' - 11 3/4"

ROOM 2 HABITABLE AREA: 311 S.F.

K5

VENTILATION (4%) REQUIRED: 311 S.F. X 4% = 12.5 S.F. PROVIDED: 32 S.F.

RECESSED MEDICINE CABINET SEE DETAIL 5/A905 FOR TYPICAL INSTALLATION AT RATED WALLS ELECTRICAL PANEL

6' - 0"

BALCONY

13' - 6 3/4"

12' - 11 7/8"

KN

16' - 11 3/4" BALCONY

KM

BALCONY

K14

1

KN W8

KM ROOM 1 HABITABLE AREA: 201 S.F.

K8

NATURAL LIGHT (8%) REQUIRED: 201 S.F. X 8% = 16.1 S.F. PROVIDED: 13.5 S.F.

K12

VENTILATION REQUIRED: 201 S.F. X 4% = 8 S.F. PROVIDED: 6.8 S.F.

UNIT K-E SIM11 ( K407, K607 ) 12 1/4" = 1'-0"

UNIT K-E SIM6 ( K311, K511, K707 ) 7 1/4" = 1'-0"

K14

ROOM 2 HABITABLE AREA: 311 S.F.

UNIT K-E SIM1 ( K312, K412, K512, K612, K710 ) 2 1/4" = 1'-0" K9

K12

NATURAL LIGHT (8%) REQUIRED: 311 S.F. X 8% = 25 S.F. PROVIDED: 64 S.F. VENTILATION (4%) REQUIRED: 311 S.F. X 4% = 12.5 S.F. PROVIDED: 32 S.F.

K7

26' - 5 3/8"

9' - 1"

K16

13' - 1 1/2"

K14 6' - 3 1/4"

13' - 3 7/8"

8' - 8 1/2"

4' - 7 3/4"

11' - 2 3/8"

6' - 6 5/8"

W12 W12

KN 2' - 0"

2' - 0"

SOFFIT AT UNITS K310, K410, K510, K610, K314, K414, K514, K614, K712, K209, K413, K309, K609, K708

16' - 11 3/4" 9' - 7"

BALCONY

16' - 11 3/4" BALCONY

13' - 11 1/2"

W8

D1

2' - 0"

LIVING / DINING

14' - 6 1/8"

KM

BALCONY

6' - 0"

BALCONY

KN

BALCONY

1' - 11"

D1

6' - 0"

BALCONY

W8

KE

13' - 6 3/4"

W8

1' - 11"

D1

6' - 0"

KE

KF

1' - 11"

KF

BEDROOM

3' - 2 1/8" W12

K16

K14 7 1/2"

UNIT K-E SIM5 ( K405, K605 ) 1/4" = 1'-0"

3'-8" MIN. CLR.

4' - 7 3/4"

8' - 8 3/4"

W12

9' - 6 7/8"

12' - 11 7/8"

16' - 11 3/4"

KITCHEN

11"

A905

FRONTLOADED

W12a

W12

W12

W12

W12

W12

U14

WALK-IN CLOSET

U4 2 A638

U4

16' - 11 3/4"

BATHROOM

18" MIN. CLR.

W08

W08

KI

1' - 2 3/4" 12" MIN. CLR. 11' - 4 7/8"

4' - 8"

RCP LEGEND

3/9/2017 2:37:06 PM

K6

K16

GYP. BD. CEILING AT 9'-0" A.F.F., U.N.O.

K14

UNIT K-E SIM9 ( K413, K613) 1/4" = 1'-0"

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

5

UNIT K-E SIM4 ( K305, K505, K702) 1/4" = 1'-0"

KLUMP UNIT PLANS

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

1

UNIT K-E ( K310, K410, K510, K610, K708 ) 1/4" = 1'-0"

K7

CASEWORK SOFFIT

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO. DATE SCALE

K9

10

SHEET TITLE

10' - 4 1/2"

26' - 5 3/8"

K8

Sim

1' - 10 1/2"

U1

BALCONY

BALCONY

A905

8' - 1 3/8"

5' - 8 3/8"

Sim

11"

W8

13

W/D

2' - 8 1/2"

KD

1 A636

BALCONY

KE

D1 6' - 0"

D1

6' - 0"

W8

BALCONY

1' - 11"

KE

KF

U15

14

W12

1' - 11"

W12

KF

2' - 4 3/4"

1' - 6"

9' - 6 1/4"

SD

W12

W12

K6 6' - 3 1/4"

SD U3

7' - 4 3/4"

CO

30' - 0 1/4"

W12

3' - 4 3/4"

K8

6' - 1 1/4"

E.Q.

6

3' - 9 1/4"

3' - 0"

UNIT K-E SIM10 ( K307, K507, K703 ) 1/4" = 1'-0"

28' - 1 1/4"

11

3' - 2 3/4"

2' - 1 1/2"

E.Q.

K12

2' - 0"

1.CONTRACTOR TO VERIFY IN FIELD ALL GRIDLINES AND DIMENSIONS PRIOR TO CONSTRUCTION. 2.SEE 1/8" PLANS FOR ADDITIONAL INFO. NOT SHOWN. 3.CONTRACTOR TO VERIFY ALL WINDOW TYPES, LOCATION, AND ORIENTATION WITH UNIT PLANS, WINDOW SCHEDULE, AND ELEVATIONS. WINDOW TYPES ON ELEVATION SUPERCEDES THOSE LISTED ON THE UNIT PLANS WHERE THERE IS A DISCREPANCY. OPENING AND WINDOW SIZES SHOWN ON THE WINDOW SHEDULE TO SUPERCEDE ALL OTHER INFORMATION. 4.ARCHITECT TO APPROVE ALL SOFFIT LOCATIONS 5.CONTRACTOR SHALL PROVIDE CONCEALED HEADS FOR ALL FIRE SPRINKLERS. 6.SEAL EXTERNAL CRACKS, JOINTS ETC. WITH CAULKING AND INSTALL PEST-PROOF SCREENS WHERE REQUIRED. 7.PROVIDE SMITTY PAN @ ALL W/D CLOSETS. 8. CONTRACTOR SHALL PROVIDE 3/4" SUPER W PADS @ EACH W/D CLOSET (TOTAL OF 4 PER CLOSET) MOUNT W/D OVER PADS. 9. PROVIDE 34"X6" METAL LOUVER OVER WASHER /DRYER CLOSET DOOR, TYPICAL AT ALL WASHER / DRYER CLOSETS. 10. REFER TO SHT. A638 - A642 FOR BATHROOM PLANS AND ELEVATIONS 11. REFER TO SHT. A636 - A637 FOR KITCHEN PLANS AND ELEVATIONS 12. REFER TO 1/4" PLANS (SHTS. 601-628) FOR BALCONY DIMENSIONS AND DRAINAGE INFO.COORDINATE DRAIN LOCATIONS AND DRAINAGE WITH FRAMING LAYOUT. 13. SEE ALSO ELEVATION SHEETS A-401-A405 CONTRACTOR V.I.F. ALL WINDOWS TYPES PRIOR OF INSTALLATION 14. CONTRACTOR TO PROVIDE BACKING FOR ALL CLOSET SHELVING & BATHROOM ACCESSORIES. 15. CONTRACTOR TO PROVIDE LIGHT/FAN COMBO IN ALL BEDROOMS, TYP. 16. THE FLOW RATES FOR ALL PLUMBING FIXTURES SHALL COMPLY WITH THE MAXIMUM FLOW RATES SPECIFIED IN CAL GREEN SECTION 4.303.1 17. REFER TO 15&16/A905 FOR LINEN CABINETRY & SHELVES 18. REFER TO 14/A905 FOR CLOSET SHELVES IN BEDROOMS AND CLOSETS THAT ARE MORE THAN 5'-0" IN WIDTH - WALK IN CLOSETS 19. REFER TO 13/A905 FOR CLOSET SHELVES THAT ARE NOT IN BEDROOMS OR SMALLER THAN 5'-0" IN WIDTH 20. REFER TO 12/A905 FOR CLOSETS LARGER THAT 5'-0" IN WIDTH, BUT NOT WALK IN CLOSETS 21. PENETRATION OF THE 1 HOUR CEILING BY DUCTS FOR THE FAU AND THE STOVE HOOD REQUIRE DAMPERS. ATTIC UNITS REQUIRE DAMPERS AT ALL CEILING PENETRATIONS. 22. EXHAUST FANS FROM THE BATHROOM MUST ENTER THROUGH THE WALL. DAMPERS ARE REQUIRED IF THE CEILING IS PENETRATED. 23. REFER TO A063 FOR ALL FRESH INTAKE AND EXHAUST VENT CAPS. 24. REFER TO A063 FOR ALL DRYER VENT CAPS. 25. MEDIA BOX SHALL BE RECESSED IN WALL, TYP. 26. SEE MECHNICAL DWGS FOR SOFFITS NOT ILLUSTRATED ON ARCHITECTURAL DWGS. 27. AT 2ND FLOOR UNITS - AT CONCRETE WALL LOCATIONS - CONTRACTOR SHALL PROVIDE SURFACE MOUNTED RIGID METAL CONDUIT FOR RECEPTACLES AND OUTLETS, REFERENCE ELECTRICAL DRAWINGS FOR LOCATIONS. CONDUIT FROM OUTLES/RECEPTACLE SHALL RUN VERTICALLY AGAINST WALL AND HORIZONTALLY AGAINST CONCRETE CEILING. 28. WHERE SHELVING IS SPECIFIED, CONTRACTOR SHALL PROVID A MINIMUM OF 6 SHELVES, PAINTED POPLAR WOOD.

W08a

K14

2' - 11 1/4"

SEE DETAIL 12,13,14/A905 FOR TYPICAL SHELVES IN CLOSETS, U.N.O.

NOTES

W12

D1

K10

BALCONY SLOPE AND/OR SLOPE TO DRAIN, MAX 2% TYPICAL

2

1' - 11"

BALCONY

6' - 0"

D1

2 3/4"

URADEK WATERPROOFING W/ CLEAR TOP COAT, 30 MESH SAND (LARR 25261)

9' - 6 1/4"

BALCONY

1' - 11"

W8

16' - 11 3/4" BALCONY

2x4 WALL AT INTERIOR, 2X6 WALL AT EXTERIOR UNLESS NOTED OTHERWISE (ALL EXTERIOR WALLS TO HAVE R-19 INSULATION)

D1 6' - 0"

KE

4' - 7 3/4" 1' - 11"

W12

6' - 6 1/4"

PLUMBING WALL

NATURAL LIGHT (8%) REQUIRED: 311 S.F. X 8% = 25 S.F. PROVIDED: 64 S.F.

KF

W8

SOUND WALL -STC RATING 50 REQUIRED / 1HR RATED REFER TO DETAIL W04/A901, WALL TYPE W021 @ PARTY WALLS

4' - 7 3/4"

W12

KE

A CARBON MONOXIDE + SMOKE DETECTOR COMBO ALARM SHALL BE INSTALLED OUTSIDE OF EACH BEDROOM ON EACH LEVEL PER REQUIREMENTS CBC 2013

VENTILATION REQUIRED: 199 S.F. X 4% = 8 S.F. PROVIDED: 6.8 S.F.

K7

KF

CO

PROVIDE HARD WIRE INTERCONNECTED SMOKE DETECTORS WITH BATTERY BACKUP. SMOKE DETECTORS REQUIRED IN THE FOLLOWING LOCATIONS (310.9.1.4) A) EACH SLEEPING ROOM B) CENTRALLY LOCATED IN CORRIDORS GIVING ACCESS TO EACH SLEEPING ROOM DETECTORS SHALL SOUND AN ALARM AUDIBLE IN ALL SLEEPING AREAS OF THE DWELLING. HARDWIRED DETECTORS ARE REQUIRED IN EXISTING DWELLINGS WHEN AN ADDITION, ALTERNATION, OR REPAIR IS MADE. BATTERY TYPE DETECTORS ARE NOT ALLOWED AND MAY NOT BE USED IN LIEU OF HARD-WIRED DETECTORS (310.9.1.2,SM FIRE DEPARTMENT POLICY), SEE ELECTRICAL DWGS

K8 7' - 6 1/4"

9' - 1"

O

EXHAUST FAN, SEE BATHROOM PLANS A638- A642, SEE ELEC. AND MECH. DWGS. REFER TO SHEET A041 FORM GRN 14 NOTES 25 & 26

13' - 6 3/4" BALCONY

BALCONY

W8

KE

CA L I F

DOOR TYPE - SEE SHEET A091 WALL TYPE SEE SHEETS A901

D1

6' - 0"

D1

OF

WINDOW TYPE - SEE SHEET A092

WXX

VENTILATION REQUIRED: 199 S.F. X 4% = 8 S.F. PROVIDED: 6.8 S.F.

1' - 11"

KF

6' - 0"

KE

NATURAL LIGHT (8%) REQUIRED: 199 S.F. X 8% = 16 S.F. PROVIDED: 13.5 S.F.

W12

1' - 11"

KF

8' - 8 1/2"

E

ROOM 2 HABITABLE AREA: 199 S.F.

K4

1 1/4"

PX2

REN. 6-30-17

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

LEGEND A

NO. C-13779

T

14

K10

ED A RCH NS S EMP I A TA

ST A

K12

K6

-SHEAR WALLS TO BE LOCATED PER STRUCTURAL PLANS. DO NOT DEVIATE FROM LOCATIONS SHOWN WITHOUT CONSENT OF ARCHITECT. -VERIFY ALL WINDOWS, DOORS, AND BALCONY LOCATIONS WITH 1/8" PLANS AND ELEVATIONS. -PLUMBING TO BE INSTALLED IN A MANNER TO PERMIT REPOSITIONING OF THE SINK AND COUNTERTOP. -DO NOT PROVIDE ACCESS PANELS FOR BATHTUBS. ALL PLUMBING TO BE WITHOUT SLIP JOINTS. -REFER TO ELECTRICAL DRAWING FOR ADDITIONAL ELECTRICAL LAYOUT. -REFER TO MECHANICAL DRAWING FOR ADDITIONAL MECHANICAL REQUIRED. -REFER TO SHEETS A020 FOR GENERAL NOTES. -REFER TO SHEETS A030-A034 FOR HANDICAP NOTES.

CT TE ERIS K

1

K8

NOTE: -ALL KITCHENS HAVE A RANGE W/ OVEN, DUCTED EXHAUST HOOD, REFRIGERATOR, DISHWASHER, DISPOSAL, & STACK OR SIDE BY SIDE WASHER/DRYER. -ALL UNITS HAVE HEATING & AIR CONDITIONING. -REFER TO 1/4" KITCHEN & BATHROOM PLANS FOR MORE INFORMATION. -CONTRACTOR TO VERIFY MIN. CLEARANCES, PER MANUFACTURER, FOR ALL WASHER DRYER UNITS

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

A

KN KM

9' - 11 3/8"

BALCONY

6' - 0"

KD 1' - 11"

W8

BALCONY

BALCONY

6' - 0"

W8

KE

D1

6' - 0"

1' - 11"

KE

D1

1' - 11"

BALCONY

APPLIANCE NOTES

NI

W12

DE Architects AIA

NOTE:

9' - 6 1/4"

2 3/8"

W12

KF

ALL DIMENSIONS ARE TO FACE OF STUD UNLESS NOTED OTHERWISE. AREA OF UNITS IS CALCULATED FROM INSIDE FACE OF WALL EXCEPT AT COMMON WALLS WHERE IT IS CALCULATED FROM THE CENTERLINE.

UNIT K-E = 700 S.F. UNIT K-E SIM4 = 700S.F. UNIT K-E SIM11 = 700 S.F.

K9

4' - 11 3/8"

KF

UNIT AREA:

8' - 8 3/4"

R

9' - 6 1/4"

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

K8

8' - 8 1/2"

DIMENSIONING NOTES

L IC E DONA

8' - 6 1/2"

LIGHT & VENTILATION

LANKERSHIM + otsego

K12

1501 03-03-2017 As indicated

SHEET NO. EXTERIOR CEMENT PLASTER CEILING AT 8'-0" A.F.F., U.N.O.

A625


KEYNOTES LEGEND NO. 1..

0 2' -

A502

"

03A10 03C4

4 A648

LC18

LC20

C3

7' - 8 3/4"

36' - 2 3/4"

12'

18' - 0"

2"

05G10 11F1

2' - 1 3/4" 7 1/2"

24' - 5 1/2"

6 1/4" 2' - 1 1/8" 10"

FOF

FOF

5' - 6 3/4"

03C4

2"

23A12

12A7

21A6 21A8 23A12

" 7/8

27A1 27A2

CONCRETE SLAB ARCHITECTURAL CAST-IN PLACE CONCRETE - SMOOTH FORMED - SMOOTH / SACKED FINISH 42" SURFACE MOUNTED GLASS GUARDRAIL KNOX BOX KNOX KEY SWITCH 3500 SERIES (SINGLE SWITCH MODEL 3502) BICYCLE DOCK (MANUF: SARIS - BIKE DOCK OR APPROVED EQ.) TYP. FIRE DEPARTMENT CONNECTION (FDC) FIRE COMMUNICATION PANEL MECHANICAL FRESH AIR INTAKE - RUSKIN ELF375DX ALUMINUM OR APPROVED EQ. 43% FREE OPENING (REF. MECH. DWGS.) RESIDENT INTERCOM RECESSED IN WALL FREESTANDING RESIDENT INTERCOM

DE Architects AIA 1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

03A10

2" N AN

G3

30 A907

REN. 6-30-17

E

T

MAIL

CLR.

NO. C-13779

ST A

25' - 7 1/4"

/8"

2' - 1 1/8"

AD

6' - 5"

ED A RCH NS S EMP I A TA

27A1

8 3/4" 16' - 0 1/8"

A635

2' - 8 1/8"

4' - 1 1/4"

9' - 6 7/8"

LCX

3' -

L14

OX KN X BO

4' - 1" R

T

R

23A12

619.42' 2' - 6 7/8"

21A6

14' - 2"

4 5' - 2 3/4"

3

A635

2' -

LANKERSHIM MAIN LOBBY

O

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

CT

/4" 11 1 1' -

PARCELS

CA L I F

F FO

/8" 01

7' - 1 1/8"

13' - 3"

AD

OF

" 3/8 10 5' -

FOF

11F1

" 3/4

14

/2" 21

0 1' -

9 3/8"

9' - 3 3/8"

10' - 3 1/2"

21A8

4' - 7 7/8"

CT TE ERIS K

6' - 5"

5

A

A635

05

11' - 8 5/8"

7

-1 12'

6' - 5" 5' - 0"

8

A635

NI

10

R

11

L IC E DONA

A635

6

2' - 9 5/8"

13

9

STAMP

5' - 7 3/4"

S5

12

4' - 6"

2' - 1 3/4"

FOF

F FO

"

4 7' -

2' - 4 3/4"1' - 7 1/8"

LCZZ

12A7

" 1/4 10 6' -

0 1' -

CV

/8" 25

10"

DESCRIPTION

1

CLR. 2

0 1' -

"

4' - 0"

COLD STORAGE

14' - 2"

7' - 8 3/4"

LC18

LC20

G5

Sim 3' - 0"

6' - 5 1/2"

4' - 11 3/4"

7' - 5 1/4"

LC21

A648 " -0 15'

17' - 4 1/8"

2' - 8 3/4"

-3 12'

6' - 5 3/4" 16' - 0 1/8"

" 3/8 15'

8"

10' - 2"

C3

LC24 1.. A502

3

LC12

LC14

27' - 10"

7 A708

6' - 6 7/8"

LC12 Sim

LC14 7' - 5 1/8"

25 A915

27' - 3 7/8"

Sim

FOF

FOF

Sim

FOF

7 A708

LANKERSHIM - MAIN LOBBY 1/4" = 1'-0"

34' - 9"

6' - 11"

21' - 3"

13 A701

FOF

LCF

LCF

FOF

LCF

1' - 6"

FOF

1' - 6"

FOF 1' - 6"

LCF

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

3 A709

/8" 45 ' 16

LANKERSHIM + otsego

G6

4

6' - 9 3/8"

10"

AD

RES. TRASH #2

G4

1' - 10"

LCW

1' - 0"

4' - 10"

G18

FOF

CS16

LEASING OFFICE MEZZANINE

3 A642

628.88'

LCE

Sim

DN

49' - 3 1/8"

LEASING OFFICE MEZZANINE ABOVE (656 SF)

6 3/4"

FOF

LCE 1' - 2"

4' - 11" 2' - 9 1/4"

1' - 2"

4' - 11 1/4"

CS6

656 SF (ALLOWABLE 660 SF) TYPE I MEZZANINE: 50% OPEN SPACE OF LOBBY #1 (1320 SF)

2' - 9 5/8"

FOF

05G10 6 3/4"

LC12

05G10

LC14

29' - 5 1/8"

LOBBY #2

SHEET TITLE

24' - 1 1/2"

24' - 6 7/8"

10 3/4"

4' - 5 1/4"

OPEN TO BELOW 1 A707

618.25'

LANKERSHIM - MAIN LOBBY / LOBBY #2

22' - 8 5/8"

LCE

21' - 6"

UP

20' - 0"

17' - 10"

7' - 10 1/2"

17' - 10"

18' - 8 1/8"

LEASING OFFICE

Sim

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

1 A904

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

2

PLENUM ABOVE

A707

5

LCB

2' - 7 5/8"

L24

S1 M5

AD

8' - 5 1/4"

19' - 2 1/2"

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

8' - 4 7/8"

A648 36' - 4 5/8"

6"

FOF

1' - 9 5/8"

5' - 3 5/8"

G1

LCB W07

27A2 5' - 4"

6' - 11"

7 1/2"

19' - 2 3/8"

W22

8' - 5"

JOB NO.

3/9/2017 2:37:13 PM

LC12

FOF

FOF

40' - 5 7/8"

DATE

LC14

LEGEND

1501 03-03-2017

SCALE

1/4" = 1'-0"

SHEET NO.

2 DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

LANKERSHIM - LOBBY #2 1/4" = 1'-0"

1

LANKERSHIM - LOBBY #2 LEASING OFFICE MEZZANINE 1/4" = 1'-0"

GYP. BD. CEILING AT 8' - 0" A.F.F., U.N.O.

A629


J

KEYNOTES LEGEND

9 1' -

4 A705

" 3/8

4

-2 21'

3

Sim

= 300.0

03E7 05F4 05G10 05G13 05G14 05G15 06A37

" 1/2

9 5' -

TOTAL OPEN AREA OCCUPANT LOAD

03E6

3

07E1

A504

" 5/8

I

07F3

H

"

08B5 03E6 UP

UP

692.25' 1 4' -

PD

8 5' -

" 1/2

0"

10K1 12A9 13A2

692.25' 13A3

-1 11'

26'

PD

7"

2 3' -

" 5/8

14A3

8

"

A807

21A4

GT12 J 10K1

PD

1 -1 12'

"

8 4' -

3 4' -

4 4' -

"

" 3/4

E

OF

CA L I F

O

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

" 1/2

GYP. BD. CEILING AT 9'-2" A.F.F., U.N.O.

" 1/8

"

2 8' -

0 3' -

" 3/8

CS8

" 3/8

/8" 17 1 3' 0 5' -

REN. 6-30-17

/4"

0

-1 12'

NO. C-13779

13

692.25' " 1/4

22E6

-0 21'

-2 21'

DECK AREA #6 351 SF (OLF = 15) OCC. LOAD = 23.4

ED A RCH NS S EMP I A TA

LEGEND

ROOF

CS9

-1 53'

/2" 71 ' 5

STAMP

T

" 1/4

MP RA

10G26 10G27 10H3

07E1

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

ST A

1 4' -

5

03E6

DE Architects AIA

CT TE ERIS K

31'

690.92'

AD

/2" 31

07J10

8 2' -

AD

STAIRS - PRECAST CONCRETE TREADS BY STEPSTONE INC. (SEPSTONEINC.COM) OR APPROVED EQ. POOL COPING GALVANIZED METAL LADDER 42" SURFACE MOUNTED GLASS GUARDRAIL 60" GLASS GUARDRAIL - POOL ENCLOSURE SIDE MOUNTED METAL SALES T16E CORRUGATED METAL SCREEN 60" STEEL GUARDRAIL - POOL ENCLOSURE WOOD FRAMED PLANTER W/ POLYETHYLENE PLANTER LINER KEE SINGLE PLY MEMBRANE ROOF ICC# ESR-1456 - SRI OF 78 OR BETTER - COOL ROOF (SEE SHEET A060) UPI POLYURETHANE PEDESTRIAN COATING (LARR 25261) - W/MONTEREY SAND AGGREGATE AND CLEAR COAT, OR APPROVED EQ. ROOF PEDESTAL PAVER SYSTEM, BY TILE TECH PAVERS OR APPROVED EQ, - SINGLE PLY ROOFING SYSTEM BELOW. (REF. LANDSCAPE DWGS.) 3'x 2' EXTERIOR WEATHER-PROOF ACCESS DOOR FOR UNDER DECK ACCESS & MAINTAINENCE. PROVIDE 3" MIN. CURB, LOCKABLE. ADA POOL/SPA LIFT ADA POOL/SPA LIFT ANCHOR SLEEVE FLUSH MOUNTED ROOF TIE-BACK ANCHOR TO COMPLY W/ SECTION 3291 (f) OF THE CCR FOR UNSCHEDULED FACADE MAINTENANCE - SEE EXTERIOR BUILDING MAINTENANCE DRAWINGS MANUFACTURED SURROUND FIREPLACE FIXED BBQ (SEE LANDS. DWGS.) STEEL POOL, SEE POOL CONSULTANT DRAWINGS STEEL SPA, SEE POOL CONSULTANT DRAWINGS HANDICPPED LIFT - GARAVENTA GENESIS OPAL MODEL GVL-OP OR APPROVED EQ. WET STANDPIPE. 12" MAX. PROTRUSION FOR POST-MOUNTED OBJECTS, 4" MAX. PROJECTION FOR PROTRUSIONS FROM WALL, OR PROVIDE CANE DETECTION AT THESE LOCATIONS. DRINKING FOUNTAIN

A

A502

= 24.2 = 24.2 = 44.6 = 44.3 = 42.0 = 23.4 = 49.0 = 48.5

NI

" -5 30'

1.

DECK AREA #1 DECK AREA #2 DECK AREA #3 DECK AREA #4 DECK AREA #5 DECK AREA #6 POOL DECK SPA DECK

DESCRIPTION

R

NO.

7TH FLOOR OPEN AREA OCCUPANT LOAD

L IC E DONA

1

-2 22'

EXTERIOR CEMENT PLASTER CEILING AT 8'-2 1/2" A.F.F., U.N.O.

PD

9 4' -

" 7/8

0" 7' -

" 3/4

PD

"

W8

W17

10H3

"

9 4' -

2 5' -

0"

I

/8" 17 1 3' -

10'

" 7/8

LOUNGE 725 SF (OLF = 15) OCC. LOAD = 48.3

05G10

PD

"

07J10 3 3' -

"

6" 1' -

" 1/8

" 7/8

" 5/8

9 1' -

0 5' -

5 8' -

692.25'

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

6 3' -

3 A504

/2" 11 1 8' -

E PD

3 A637

"

"

DECK AREA #5 630 SF (OLF = 15) OCC. LOAD = 42

20'

W17

GAME ROOM 683 SF (OLF = 15) OCC. LOAD = 46

CONTRACTOR TO DISTRIBUTE VENTS EQUALLY AROUND PERIMETER. ARCHITECT TO APPROVE LOCATIONS.

" 7/8

CHANGING

3' - 10 1/4"

12 5.7 2°

25' - 8 1/2"

OPEN TO BELOW

PD

PD

2' - 6 1/2"

13' - 11 1/2"

692.25'

DN

695.92'

05G15

8' - 10 3/4"

17 -1 ' 1 1

PD

20' - 3"

4' - 9"

5' - 0"

4' - 9"

/8"

" 1/4

PD

SHEET TITLE

LANKERSHIM - POOL DECK

4' - 9"

PD

A

31' - 11 1/2"

DECK AREA #1 364 SF (OLF = 15) OCC. LOAD = 24.2

12' - 0"

7' - 5"

24' - 6 1/2"

14' - 6"

DECK AREA #2 364 SF (OLF = 15) OCC. LOAD = 24.2

PD

27' - 3 1/2"

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

30' - 10 1/4"

21' - 10"

PD

3' - 9 1/8" 31' - 1"

PD

PD

18' - 10 3/4"

4' - 9"

PD

11' - 4 3/4"

16' - 1 3/4"

5' - 0"

12' - 4 3/4"

16' - 9 1/8"

17' - 0 1/2"

4' - 9"

16' - 4 3/4"

26' - 6 5/8"

17' - 11 3/4"

03E6

PD

4' - 9"

PD

4' - 9"

PD

11' - 4 3/4"

PD

4' - 9"

4' - 9"

4' - 9"

11' - 4 7/8"

07J10

05G14

4' - 0"

1' - 0"

4' - 0"

8' - 10 3/8"

1 A805

3' - 8 1/2"

8' - 7 1/8"

692.25'

3' - 10 3/8"

3 1/4"

3' - 6"

GT12

4' - 0"

PD

LA

3 1/4"

LA

05G10 7 8' - 4 3/4"

5' - 1 3/8"

A807

6' - 9 3/8"

10H3

92' - 3 1/8"

JOB NO.

10H3

1

1 A504

1

A502

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

68' - 11 1/8"

1' - 2"

DATE

4 7/8"

L9

L13

L16

L22

L24

L25

" -5 30'

SCALE

1501 03-03-2017 As indicated

SHEET NO.

LANKERSHIM - POOL DECK 1 3/16" = 1'-0" 3

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

DECK AREA #3 670 SF (OLF = 15) OCC. LOAD = 44.6

5' - 0"

PD

ROOF

3/9/2017 2:38:16 PM

LD

11 6.6 2°

30' - 11 1/4"

4' - 0"

5' - 9 1/2"

5' - 9 1/2"

03E6

GT10

POOL/ SPA EQUIPMENT

9 4' -

PD

" 1/4

12' - 1 1/8"

Sim

PD

3 7' -

2' - 4 7/8"

10G27 10G26

4' - 1 1/2"

11' - 0"

14' - 6 3/4" PD

9 A701

4' - 9 1/4"

"

5' - 1 3/8"

10' - 0"

10' - 0"

0" -1 29'

5' - 0"

9 4' -

5' - 9 1/2"

13A3

LE

"

05G14

SPA (N.I.C. SEPARATE PERMIT REQ.)

0 4' -

05G10

GT6

" 1/2

6' - 0 3/4"

B

5' - 9 1/2"

11' - 10 3/8"

4' - 3 7/8" 5' - 0"

RAMP UP

15' - 0"

3 3' -

10' - 2 3/8"

6' - 6 3/4"

32' - 1 3/4"

SPA DECK TOTAL OCC. LOAD = 48.5 [DECK: 693 SF / 15 (OLF) = 46.2] [SPA: 109 SF / 50 (OLF) = 2.1]

"

/8" 13 1 2'

" 1/4

10H3

-5 14'

3' - 5 1/2"8 1/8"

PD

"

" 3/8

0 5' -

A807 PD

" 3/4

9 4' -

07J10

7

-7 35'

695.92'

-3 25'

3' - 5 1/2"

"

1' - 6 1/2"

34' - 0"

05G13

GT11

03E7

DECK AREA #4 665 SF (OLF = 15) OCC. LOAD = 44.3

PD

" 3/8

24' - 6 3/8"

" 0 4' -

11

EL: 695.92' T.O.W.

7' - 0"

PD PD

A701

10G27

POOL (N.I.C. SEPARATE PERMIT REQ.)

692.25' PD

" 1/2

10G26

9"

14A3

/4" 61

" 1/8

LD

13A2

30'

-0 25'

'16

90.00°

7' - 3 3/8"

" 1/8

07J10

03E6

05F4

3' -

-1 14'

A503

2 A503

/8" 81

/8" 73

LE

"

2 6' -

PD

692.25'

0 5' -

Sim

8 A701

5'

2.

22E6

Q

1 7' -

11' - 0 7/8"

PD

PD

DN

"

4' - 4"

POOL DECK TOTAL OCC. LOAD = 49 [DECK: 582 SF / 15 (OLF) = 38.8] [POOL: 510 SF / 50 (OLF) = 10.2]

690.92'

9 4' -

" 1/2 11 9' -

22' - 4"

2° 35.7

AD

" 3/8

GT12

.28° 144

STORAGE

G11

"

" 1/8

G16

BB

PD

SHOWERS

PD

6' - 0 3/4"

21A4

7 5' -

692.25'

PD

AD A703

12A9

CHANGING

11

AD

LOCKER ROOM 36 LOCKERS PROPOSED

STORAGE

691.53'

RAMP UP

690.92'

07E1

2 A646

/2" 11

AD

" 1/2

L56 90.00°

08B5

-7 22'

B

'29

G11

/2" 91

Sim

-3 10'

07F3

Sim

" 3/8

1"

9 A703

'10

.28° 144

2 A641

PD

BQ

6 1' -

-5 31'

1 3' -

A504

692.25'

"

9 4' -

1

9 4' -

" 7/8

CS18

"

6 1' -

" 1/8

D

"

W8

-3 17' 6 6' -

8' - 9 1/8"

PD

0 4' -

25' - 1 5/8"

" 1/4

5' - 1 1/4"

" 7/8

6 8' -

12' - 7 3/8"

-2 10'

" 1/2

Sim

2 A641

2 A645

-9 29'

692.25'

5 5' -

0" -1 18'

NET FREE VENTILATING AREA REQUIRED = 2,227 / 150 = 14.84 SF

8' - 9 5/8"

" 3/4

0 7' -

6"

ATTIC SPACE UNDER POOL DECK = 2,227 SF

7"

1' -

" 1/4

L13

-1 12'

L9

L55

ATTIC SPACE VENTILATION: PER SECTION 1203, "THE NET FREE VENTILATING AREA SHALL NOT BE LESS THAN 1/150TH OF THE AREA OF THE SPACE VENTILATED."

LANKERSHIM + otsego

6 1' -

6 1' -

CS7

A632


2' - 6"

REF. 30" MIN. WORKSPACE

2' - 0" 3B

MAX. TYP.

A637d 3A

11D4

6' - 9 1/4"

1' - 3"

3' - 0"

12D23

1' - 0"

2' - 3"

L IC E DONA

F.O. FINISH

34" HIGH DROP-IN RANGE

3B

1' - 9"

2' - 10 1/4"

30" MIN. WORKSPACE

2' - 0"

PANTRY

REF.

3' - 0"

D.W.

2' - 5"

1' - 6"

1' - 6"

3' - 0"

2' - 0"

1' - 9"

SINK

D.W.

PANTRY

SINK

3' - 0"

R

OF

NI

F.O. FINISH

F.O. FINISH

11D2

22E8

11D6

F.O. FINISH

12D10

12D2

12D15

26B4

26B3

11D2

12D12

12D19

26B3

12D15

12D2

12D10

26B3

11D4

2' - 9"

E

T

2' - 6"

ST A

3/4"

REN. 6-30-17

A

NO. C-13779

CORNER BLIND CABINET

3" 1' - 3"

ED A RCH NS S EMP I A TA

F.O. FINISH

MIN.

1' - 3"

MIN.

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

1" BACKSPLASH TYP.

STAMP

2' - 10"

11 1/4"

2'-0" MIN.

EQ EQ EQ 1' - 3"

T.O. 4TH SHELF

3' - 10" MAX. TO

6' - 9 1/4"

2'-0" MIN.

2' - 4 1/2"

MIN.

1' - 3"

3' - 10" MAX. TO

T.O. FIRST SHELF

26B5

DE Architects AIA

CT TE ERIS K

2' - 10"

11 1/4"

3' - 0"

2' - 6"

2' - 9"

TOTAL LINEAR SHELF = 436.5" ADA LINEAR SHELF = 261"

11D1

34" HIGH DROP-IN RANGE

2' - 10 1/4"

12D10

12D4

TOTAL LINEAR SHELF = 201" ADA LINEAR SHELF = 61.25"

12D5

12D4

12D5

12D4

12D5

12D4

12D10

F.O. FINISH

CA L I F

O

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

3/4"

KITCHEN #12 (2010 ADA COMPLIANT) - INT. ELEV. 3/8" = 1'-0"

3A

KITCHEN #12 (2010 ADA COMPLIANT) - INT. ELEV. 3/8" = 1'-0"

3

KITCHEN #12 (2010 ADA COMPLIANT) - PLAN 3/8" = 1'-0"

F.O. FINISH 3' - 4"

12D23 1' - 0"

F.O. FINISH

D.W.

11D6

2B

A637d

1" BACKSPLASH TYP. 2' - 0"

MAX. TYP.

SINK

3' - 0" 2' - 8"

6' - 9 1/4"

2

F.O. FINISH

11D4

F.O. FINISH

1' - 9"

30" MIN. PANTRY WORKSPACE

1 1/4"

KITCHEN #11 (2010 ADA COMPLIANT) - PLAN 3/8" = 1'-0"

F.O. FINISH

TOTAL LINEAR SHELF = 175.5" ADA LINEAR SHELF = 39" A637d

11D2

1A

D.W.

3' - 10" MAX. TO

11 1/4" 2' - 10"

26B3

12D2

26B5

11D4

2' - 9"

34" HIGH DROP-IN RANGE

1' - 6"

KITCHEN #11 (2010 ADA COMPLIANT) - INT. ELEV. 3/8" = 1'-0"

TOTAL LINEAR SHELF = 429" ADA LINEAR SHELF = 265.5"

2' - 6"

SINK

2A

1' - 6"

34" HIGH DROP-IN RANGE

12D4

12D5

12D4

12D5

KITCHEN #11 (2010 ADA COMPLIANT) - INT. ELEV. 3/8" = 1'-0"

12D4

2B

30" MIN. WORKSPACE

MIN.

1' - 3"

PANTRY

2' - 1"

2' - 0"

REF.

F.O. FINISH

3' - 0"

D.W.

T.O. FIRST SHELF

3' - 0"

SINK

2A

22E8

CORNER BLIND CABINET

12D10

2' - 10 1/4"

2' - 6"

12D4

2' - 0"

2' - 9"

12D5

3' - 0"

2'-0" MIN.

2' - 4 1/2"

1' - 9"

26B3

12D15

12D12

MIN.

1' - 3"

T.O. 4TH SHELF

3' - 10" MAX. TO

MIN.

EQ 1' - 3" 11D1

11D2

12D15

12D10

26B3

T.O. 4TH SHELF

EQ

3' - 10" MAX. TO

EQ

2'-0" MIN.

26B4

2' - 10"

11 1/4"

6' - 9 1/4"

3' - 0"

2' - 6"

11D2

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

REF.

11D1

LANKERSHIM + otsego

2' - 9 3/4"

TOTAL LINEAR SHELF = 298.5" ADA LINEAR SHELF = 143.25"

2' - 0"

12D4

12D5

12D4

TOTAL LINEAR SHELF = 304" ADA LINEAR SHELF = 160"

12D5

12D4

12D5

12D4

F.O. FINISH

LINE OF SOFFIT 1B

1B

2' - 6"

2' - 9"

2' - 9 3/4"

1' - 6"

34" HIGH DROP-IN RANGE

30" MIN. WORKSPACE

REF.

PANTRY

KITCHEN #10 (ADA 2010) INT. ELEVATION 3/8" = 1'-0"

1A

2' - 0"

3' - 0" SINK

D.W.

30" CLR. INSIDE

KITCHEN #10

KITCHEN #11

KITCHEN #12

2. IF DISCREPANCIES ARE FOUND, THE ARCHITECT SHALL BE NOTIFIED FOR CLARIFICATION.

ADA SHELF REQUIRED (TOTAL PROVIDED / 2)

ADA SHELF PROVIDED

604.5"

302.25"

304.5"

3. SUBMIT SHOP DWG. FOR APPROVAL PRIOR TO FABRICATION. ALLOW 3 WEEKS FOR 1ST SUBMITTAL FOR SHOP DWGS. REVIEW.

303.25"

4. VERIFY ALL CABINET DESIGNS WITH ARCHITECT PRIOR TO INSTALLATION. SUBMIT FULL SIZE CABINET SAMPLE UNITS FOR APPROVAL BY ARCHITECT.

637.5"

301.25"

318.75"

322.25"

5. STONE, CULTURED STONE, AND TILED COUNTERTOPS MAY BE USED WITHOUT MEETING THE REPOSITIONING REQUIREMENTS. 6. KITCHEN COUNTERTOPS SHALL HAVE GRANITE WITH BACKSPLASH.

ADA NOTES: 1. ALL CABINET SHELVING AT 15"-34" AFF SHALL BE PROVIDED WITH PULL-OUT MECHANISM. 2. ALL SINK & 30" WORKSPACES TO HAVE REMOVABLE BASE CABINETS, TOE KICKS & SHELVES TO PROVIDE 30"x48" FRONT APPROACH W/ KNEE & TOE SPACE (SEE 2/A033). INSULATE PIPES & EXTEND F.F. TO THE WALL.

7. PROVIDE QUARTZ COUNTERTOP EQUIVALENT TO PENTAL QUARTZ INSPIRE COLLECTION. COUNTERTOP SUBSTRATE MUST BE MINIMUM 3/4" THICK. BUILD UP FRONT, BACK AND ENDS TO 1-1/2" THICKNESS, MITER EDGE. FOR SINK TOPS, SPECIFY GRADE M-2 EXTERIOR GLUE PARTICLEBOARD OR EXTERIOR GRADE PLYWOOD. 8. BASE CABINETS DIRECTLY UNDER KITCHEN SINK COUNTER AREA, AND ANY OPEN WORK AREAS, INCLUDING TOEBOARD AND SHELVING, SHALL BE REMOVABLE WITHOUT THE USE OF SPECIAL TOOLS OR KNOWLEDGE TO PROVIDE CLEARANCE FOR A WHEELCHAIR. FINISHED FLOORING SHALL BE INSTALLED BENEATH SUCH COUNTERTOP. WALL FINISHES AND WALL BASE MUST CONTINUE UNDER AND BEHIND ALL REMOVABLE CABINETS. CABINETS MUST BE REMOVABLE WITHOUT MODIFICATION OF COUNTERTOP, ADJACENT CASEWORK OR PLUMBING. INCLUDE FINISHED END PANELS WHERE REQUIRED FOR DISHWASHER. 9. CABINETS TO BE THERMOFOIL. CABINET DESIGN SHOULD BE FULL OVERLAY, 3/4" THK. DOORS AND FLAT PANEL DRAWER FRONTS, EQUAL TO RSI PCS "THERMOFOILTSUKI 2. MANUFACTURERS MUST BE APPROVED BY OWNER PRIOR TO BUILDING. 10. ALL PARTICLE BOARD, MDF AND COMPOSITE WOOD PRODUCTS FOR CABINETS AND COUNTERTOPS MUST BE UREA FORMALDEHYDE-FREE, INCLUDING CERTIFIED COMPLIANCE WITH CALIFORNIA 93120. ALL EXPOSED EDGES AND SIDES OF NONCOMPLIANT COMPOSITE WOOD PRODUCTS TO BE SEALED WITH A LOW-VOC SEALANT. ALL ADHESIVES MUST BE LOW-VOC, INCLUDE REFERENCE TO APPLICABLE STANDARDS, SUCH AS RULE 1168 OF THE SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT. 10a. NEW HARDWOOD PLYWOOD, PARTICLE BOARD, AND MEDIUM DENSITY FIBERBOARD COMPOSITE WOOD PRODUCTS USED IN THE INTERIOR OR EXTERIOR OF THE BUILDING SHALL MEET THE FORMALDEHYDE LIMITS LISTED IN TABLE 4.504.5/TABLE (4.504.5, 9.504.5) THE MANUFACTURER'S SPECIFICATIONS SHOWING FORMALDEHYDE CONTENT FOR ALL APPLICABLE WOOD PRODUCTS SHALL BE READILY AVAILABLE AT THE JOB SITE AND BE PROVIDED TO THE FIELD INSPECTOR FOR VERIFICATION. (4.504.5.1, 9.504.5.1)

5"

1' - 6" 2' - 0"

MAX. TYP.

2' - 0"

1' - 0"

1

F.O. FINISH

11D4

11D1

F.O. FINISH

F.O. FINISH

F.O. FINISH

2' - 9 3/4"

2' - 9"

2' - 6"

PANTRY

REF.

30" MIN. WORKSPACE

34" HIGH DROP-IN RANGE

10"

2' - 0"

CORNER BLIND CABINET

KITCHEN #10 ADA 2010 3/8" = 1'-0"

KEYNOTES LEGEND

KITCHEN CASEWORK AND COUNTERTOP NOTES:

TOTAL SHELF LENGTH PROVIDED

602.5"

11D6

1' - 6"

5"

KITCHEN #10 (ADA 2010) INT. ELEVATION 3/8" = 1'-0"

22E8

F.O. FINISH

1' - 6"

1. CONTRACTOR SHALL FIELD MEASURE & VERIFY ALL CONDITIONS AND DIMENSIONS AT JOB SITE PRIOR TO FABRICATION.

3/9/2017 2:38:45 PM

12D23

3' - 6"

ADA SHELF STORAGE REQUIREMENT TABULATION

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

1" BACKSPLASH, TYP.

6' - 9 1/4"

T.O. FIRST SHELF

3' - 10" MAX. TO

3' - 0"

12D10

12D2

12D15

12D12

11D2

MIN.

1' - 3"

MAX.

26B3

MIN. 2' - 10"

26B4

11 1/4"

2'-0" MIN.

6' - 9 1/4"

2' - 6"

10"

11D1

26B5

26B3

11D4

12D10

12D15

1' - 3"

EQ

3' - 10"

EQ

EQ

2'-0" MIN.

2' - 6"

2' - 4 1/2"

11 1/4"

26B3

2' - 10"

6' - 9 1/4"

3' - 0"

LINE OF SOFFIT

11. MANUFACTURER'S STANDARD CABINET FINISH SHALL BE INSTALLED ADJACENT TO RANGE WITHOUT AFFECTING CABINET FINISH. 12. HINGES TO BE ADJUSTABLE, EUROPEAN-STYLE CONCEALED HINGES, WITH A 110 DEG. MINIMUM OPENING. PROVIDE SELF-CLOSING, EPOXY-COATED, SIDE-MOUNTED DRAWER GUIDES WITH 75 LB. LOAD CAPACITY. 13. DOOR AND DRAWER PULLS TO BE FINISHED TO MATCH STANDARD DOOR HARDWARE THROUGHOUT THE UNIT. STANDARD PULL STYLE IS 4" WIRE PULL. FOR ACCESSIBLE UNITS, VERIFY SPECIFIED PULL COMPLIES WITH GRASPABILITY REQUIREMENTS. 14. SHOP DRAWINGS SHALL NOT SHOW CABINET WIDTHS SMALLER THAN 15". INCLUDE FULL HEIGHT 24" DEEP PANTRY CABINETS WHEN POSSIBLE. INCLUDE BLIND CORNER CABINETS FOR L AND U-SHAPED KITCHENS. CLEARLY INDICATE LOCATION OF FILLERS. 15. COORDINATE CASEWORK LAYOUT WITH APPLIANCES TO ENSURE ADEQUATE CLEARANCE FOR RANGES AND REFRIGERATORS. REVIEW DOOR AND DRAWER OPENING CLEARANCES TO AVOID CONFLICTS WITH APPLIANCE DOORS AND HANDLES.

NO. 11D1 11D2 11D4 11D6 12D2 12D4

12D5 12D10 12D12 12D15

16. CABINET DOORS SHALL OPEN FULLY WITH NO OBSTRUCTIONS. PROVIDE CABINET BOXES THAT ARE FULLY USABLE, WITH NO CENTER STILE. 17. THE SIDES AND BACK OF ADJACENT CABINETS WHICH MAY BECOME EXPOSED TO MOISTURE OR FOOD HANDLING, WHEN A COUNTER TOP IS LOWERED, SHALL BE CONSTRUCTED OF DURABLE NONABSORBENT MATERIALS APPROPRIATE FOR SUCH USES.

12D19 12D23

22E8

18. ALL CABINETS TO BE ANCHORED TO BLOCKING. 19. KITCHEN HALF-WALL CAPS, WHERE SHOWN, SHALL HAVE PLASTIC-LAMINATE TOP WITH SQUARE EDGES. 20. PROVIDE CERAMIC TILE ABOVE KITCHEN COUNTERTOP BACKSPLASH. START WITH FULL TILE AT TOP OF BACKSPLASH AND EXTEND TO UNDERSIDE OF OVERHEAD CABINETS. ALLOW FULL TILE TO EXTEND BEHIND RANGE HOOD. CONTINUE TILE ONE FULL COURSE BELOW TOP OF BACKSPLASH BEHIND RANGE. 21. PROVIDE ADA ACCESSIBLE KITCHEN SINK & FAUCET. 22. KITCHENS SHALL BE DESIGNED AND CONSTRUCTED TO PROVIDE A MINIMUM CLEAR SPACE OF 60" BETWEEN CABINET FRONTS, COUNTERTOPS, OR WALLS FOR ALL U-SHAPED KITCHEN AREAS AND A MINIMUM CLEAR SPACE OF 48" FOR ALL OTHER KITCHEN DESIGNS.

26B3 26B4 26B5

DESCRIPTION REFRIGERATOR (REF. SPECS.) DISHWASHER (REF. SPECS.) RANGE/OVEN UNIT (REF. SPECS.) COUNTERTOP MICROWAVE (REF. SPECS.) BASE CABINETS W/ SHELVES UPPER CABINETS W/ SHELVES - PROVIDE 36" UPPER CABINET AT ALL 2ND FLOOR UNITS, REFERENCE DETAIL 28/A905 (REF. SPECS.) CABINETS (REF. SPECS.) FILLER KITCHEN PANTRY W/ SHELVES KITCHEN BASE CABINET W/ REMOVABLE FRONT AND BASE. REF. DETAIL 2/A033 FOR KNEE & TOE CLEARANCES. CONTINUE FLOOR FINISH UNDER BASE. CORNER BLIND CABINET BUILT-IN SHELVES TO MATCH KITCHEN CABINETS MATERIAL, COLOR & FINISH. PROVIDE BRACING AS NECESSARY. STAINLESS STEEL DOUBLE KITCHEN SINK 33" MIN., GARBAGE DISPOSAL & FAUCET SET. INSULATE PIPES & MEET ADA KNEE CLEARANCES. REF. DETAIL 2/A033 GFCI RECEPTACLE OR SWITCH (REF. ELEC. DWGS.) GARBAGE DISPOSAL SWITCH (REF. ELEC. DWGS.) RANGE HOOD SWITCH (REF. ELEC. DWGS.)

SHEET TITLE

KITCHEN PLANS + INTERIOR ELEVATIONS (ADA 2010)

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO. DATE SCALE

1501 03-03-2017 As indicated

SHEET NO.

A637d


9' - 10" 2' - 8" TUB

7' - 2"

F.O. FINISH

10G28

10C2

10G20

F.O. FINISH

DE Architects AIA 1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

FUTURE GRAB BARS F.O. FINISH 26D1

F.O. FINISH

10G17 10G15

3D

BATH #3 (ADAPTABLE) - INT. ELEV. 3/8" = 1'-0"

COUNTER DEPTH

BATH #3 (ADAPTABLE) - INT. ELEV. 3/8" = 1'-0"

3C

3B

BATH #3 (ADAPTABLE) - INT. ELEV. 3/8" = 1'-0"

BATH #3 (ADAPTABLE) - INT. ELEV. 3/8" = 1'-0"

3A

3

1' - 6"

REN. 6-30-17

E

22E2

2' - 0"

MIN. 3' - 0"

MIN.

MIN.

7' - 0"

R

OF

CA L I F

O

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

2' - 0"

F.O. FINISH

17" - 18"

10G18

10G16

10C2

10G20

10G7

FUTURE GRAB BAR

F.O. FINISH

FUTURE SWING GRAB BAR

NO. C-13779

A

FUTURE SWING GRAB BAR SEE 21/A033 AND 22/A033 FOR FLOOR BACKING

17" MIN.

FUTURE SWING GRAB BAR

ED A RCH NS S EMP I A TA

NI

3' - 4"

5' - 0"

F.O. FINISH

F.O. FINISH

22E9

40" MAX.

CONTROLS

12D7

2' - 10"

38" MIN.

T. O. GRAB BAR

33" - 36"

32" MAX. 22E9

10G16

10G7

12D7

12D10

2' - 10"

38" MIN.

T.O. GRAB BAR

33 - 36" 10G7

MAX.

6" 22E9

10G16

30"

32" MAX.

FUTURE GRAB BAR

STAMP

T

T.O. GRAB BAR

3C

CT TE ERIS K

33" - 36"

22E9

10G15

10G17

3B

L IC E DONA

FUTURE GRAB BARS

MIN.

A638

ST A

38" MIN.

3D

24" MIN.

T.O. GRAB BAR

FUTURE GRAB BAR

CONTROL END WALL

12"

22E2

3A

7' - 0"

24" MIN.

4"

24" MIN.

38" MIN.

MAX.

40" MIN.

6"

MAX.

10G18

33 - 36" MAX.

12"

T.O. MEDICINE CAB

42" MIN.

3' - 8"

6"

EQ

17" MIN. COUNTER DEPTH

EQ

36" MIRROR

5' - 0" TUB

26D1

BATH #3 (ADAPTABLE) PLAN 3/8" = 1'-0" 9' - 6"

22E9

09B5

10C2

10G28

F.O. FINISH

2' - 8" TUB

F.O. FINISH

6' - 10"

FUTURE GRAB BARS F.O. FINISH

F.O. FINISH 26D1

26D1

2D

F.O. FINISH 10G15 22E2 10G17 38" MIN.

17" MIN. COUNTER DEPTH

T. O. GRAB BAR

33" - 36"

F.O. FINISH

10G7

22E9

FUTURE SWING GRAB BAR

32" MAX.

3' - 4"

38" MIN.

T.O. GRAB BAR

CONTROLS

10C2

10G7

33" - 36"

30"

MAX.

6" 22E9

33" - 36"

38" MIN.

T.O. GRAB BAR

10G16

12D10

COUNTER DEPTH

10G7

22E9

10G16

17" MIN.

12D7

2' - 10"

32" MAX.

T. O. GRAB BAR

33" - 36"

38" MIN.

12D7

FUTURE SWING GRAB BAR

2D

BATH #2 (ADAPTABLE) - INT. ELEV. 3/8" = 1'-0"

2C

BATH #2 (ADAPTABLE) - INT. ELEV. 3/8" = 1'-0"

2B

BATH #2 (ADAPTABLE) - INT. ELEV. 3/8" = 1'-0"

BATH #2 (ADAPTABLE) - INT. ELEV. 3/8" = 1'-0"

2A

LANKERSHIM + otsego

EQ

10G7

2

2' - 0"

1' - 8"

1' - 6"

MIN.

FUTURE SWING GRAB BAR SEE 21/A033 AND 22/A033 FOR FLOOR BACKING

17" - 18"

MIN 3' - 0" MIN.

FUTURE GRAB BAR

F.O. FINISH

MAX.

2C

10G20

FUTURE GRAB BAR

EQ 24" MIN.

6"

10G17

MAX.

6"

10G7

FUTURE GRAB BARS

48" MIN.

10G16

6"

2B

A638

10G18

22E2

MIN.

FUTURE GRAB BARS 5' - 0"

2' - 10"

T.O. MEDICINE CAB

40" MAX.

10G15

24" MIN.

F.O. FINISH

4" 12"

CONTROL END WALL

3' - 8"

10G18

40" MIN.

7' - 0"

10G20

6' - 8"

BATH #2 (ADAPTABLE) PLAN 3/8" = 1'-0"

6' - 4" 3' - 0" MIN.

6"

10G17

17" MIN. COUNTER DEPTH

F.O. FINISH

22E2

10G22

10G7

A638

22E9

1B

1C

F.O. FINISH

F.O. FINISH 10C2

F.O. FINISH

12D10

12D8

10G22

10G7

10G16

22E9

10G7

22E9

10G20

1A 1D

COUNTER DEPTH 10C2

10G15

09B5

2' - 10"

32" MAX.

T.O. GRAB BAR

33" - 36"

12D8

38" MIN.

5' - 0"

10G22

10G17

7' - 0"

22E2

F.O. FINISH

FUTURE SWING GRAB BAR

F.O. FINISH

24" MIN.

MIN.

17" MIN.

10G7

22E9

FUTURE SWING GRAB BAR

2' - 10"

B.O. MED. CAB.

40" MAX.

38" MIN.

CONTROLS

MIN.

10G28

10G15

T. O. GRAB BAR

3' - 4"

38" MIN.

T.O. GRAB BAR

30"

33" - 36"

MAX.

10G16

12"

10G16

F.O. FINISH

MIN.

FUTURE GRAB BARS 5' - 0" TUB

EQ 24" MIN.

EQ

6"

T. O. GRAB BAR

33" - 36"

38" MIN.

FUTURE GRAB BARS

FUTURE GRAB BARS

FUTURE GRAB BARS

10G18

40" MIN.

3' - 8"

10G7

33" - 36"

MAX.

24" MIN.

4"

CONTROL END WALL

32" MAX.

MAX.

10G20

6"

2' - 0"

F.O. FINISH

33" MIRROR 48" MIN.

1' - 4"

FUTURE SWING GRAB BAR SEE 21/A033 AND 22/A033 FOR FLOOR BACKING

26D1

26D1

1' - 6"

10G18

17" - 18"

6"

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

10G28

36" MIRROR 24" MIN.

5' - 0" TUB

2A

2' - 8" TUB

6' - 6" 9' - 2"

BATH #1 (ADAPTABLE) - INT. ELEV. 3/8" = 1'-0"

3/9/2017 2:39:06 PM

1D

1C

BATH #1 (ADAPTABLE) - INT. ELEV. 3/8" = 1'-0"

1B

BATH #1 (ADAPTABLE) - INT. ELEV. 3/8" = 1'-0"

1A

BATH #1 (ADAPTABLE) - INT. ELEV. 3/8" = 1'-0"

1

BATH #1 (ADAPTABLE) PLAN 3/8" = 1'-0"

GENERAL CABINET NOTES:

ACCESSIBLE BATHROOM GENERAL NOTES:

1. CONTRACTOR SHALL FIELD MEASURE & VERIFY ALL CONDITIONS AND DIMENSIONS AT JOB SITE PRIOR TO FABRICATION. 2. IF DISCREPANCIES ARE FOUND, THE ARCHITECT SHALL BE NOTIFIED FOR CLARIFICATION. 3. CABINETS TO BE KCMA CERTIFIED. CABINET DESIGN SHOULD BE FULL OVERLAY, 3/4" LENOX-STYLE, STILE AND RAIL DOORS AND FLAT PANEL DRAWER FRONTS, EQUAL TO RSI PCS "THERMOFOIL-TSUKI 2" OR APPROVED EQUAL. 4. ALL PARTICLE BOARD, MDF AND COMPOSITE WOOD PRODUCTS FOR CABINETS AND COUNTERTOPS MUST BE UREA FORMALDEHYDE-FREE, INCLUDING CERTIFIED COMPLIANCE WITH CALIFORNIA 93120. ALL EXPOSED EDGES AND SIDES OF NONCOMPLIANT COMPOSITE WOOD PRODUCTS TO BE SEALED WITH A LOW-VOC SEALANT. ALL ADHESIVES MUST BE LOW-VOC, INCLUDING REFERENCE TO APPLICABLE STANDARDS, SUCH AS RULE 1168 OF THE SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT. 5. SUBMIT FULL-SIZE CABINET SAMPLE UNITS FOR APPROVAL. 6. PROVIDE ADJUSTABLE, EUROPEAN-STYLE CONCEALED HINGES, WITH A 110 DEG. MINIMUM OPENING. 7. PROVIDE SELF-CLOSING, EPOXY-COATED, SIDE-MOUNTED DRAWER GUIDES WITH 75 LB. LOAD CAPACITY. 8. DOOR AND DRAWER PULLS TO BE FINISHED TO MATCH STANDARD DOOR HARDWARE THROUGHOUT THE UNIT. STANDARD PULL STYLE IS 4" WIRE PULL. FOR ACCESSIBLE UNITS, VERIFY PULL COMPLIES WITH GRASPABILITY REQUIREMENTS. 9. NO CABINET WIDTHS SHALL BE SMALLER THAN 15". U.N.O. 10. VERIFY CABINET DOORS WILL OPEN FULLY WITH NO OBSTRUCTIONS. PROVIDE CABINET BOXES THAT ARE FULLY USABLE, WITH NO CENTER STILE. 11. REMOVABLE BASE CABINETS SIZED TO PROVIDE REQUIRED OPEN KNEE SPACE AT SINKS, LAVATORIES AND OPEN WORK AREAS. SPECIFY AND DETAIL REQUIREMENTS FOR CABINETS TO BE REMOVED WITHOUT MODIFICATION OF COUNTERTOP, ADJACENT CASEWORK OR PLUMBING. FLOOR AND WALL FINISHES, INCLUDING WALL BASE, MUST CONTINUE UNDER AND BEHIND ALL REMOVABLE CABINETS. 12. COUNTERTOP SUBSTRATE MUST BE MINIMUM OF 3/4" THICK. BUILD UP FRONT, BACK AND ENDS TO 1-1/2" THICKNESS. MITER EDGE FOR SINK TOPS, SPECIFY GRADE M-2 EXTERIOR GLUE PARTICLEBOARD OR EXTERIOR GRADE PLYWOOD. 13. ALL CABINETS ARE TO BE ANCHORED TO BLOCKING. 14. SUBMIT SHOP DRAWING FOR APPROVAL PRIOR TO FABRICATION. ALLOW 3 WEEKS FROM 1ST SUBMITTAL FOR SHOP DWGS. REVIEW. 15. DO NOT PROVIDE ACCESS PANELS FOR BATHTUBS. ALL PLUMBING TO BE WITHOUT SLIP JOINTS. 16. NEW HARDWOOD PLYWOOD, PARTICLE BOARD, AND MEDIUM DENSITY FIBERBOARD COMPOSITE WOOD PRODUCTS USED IN THE INTERIOR OR EXTERIOR OF THE BUILDING SHALL MEET THE FORMALDEHYDE LIMITS LISTED IN TABLE 4.504.5/TABLE (4.504.5, 9.504.5) SEE SHEET A044 FORM GRN 14 ITEM #20. 17.THE FORMALDEHYDE EMISSIONS VERIFICATION CHECKLIST, FORM GRN 3, SHALL BE COMPLETED PRIOR TO FINAL INSPECTION APPROVAL. THE MANUFACTURER'S SPECIFICATIONS SHOWING FORMALDEHYDE CONTENT FOR ALL APPLICABLE WOOD PRODUCTS SHALL BE READILY AVAILABLE AT THE JOB SITE AND BE PROVIDED TO THE FIELD INSPECTOR FOR VERIFICATION. (4.504.5.1, 9.504.5.1) SEE SHEET A044 FORM GRN 14 ITEMS #21.

1. GRAB BAR BACKING SHALL BE INSTALLED FROM 32" TO 38" ABOVE THE FLOOR. 2. THE GRAB BARS AND THEIR SUPPORTS SHALL BE DESIGNED TO WITHSTAND A 250 POUND POINT LOAD. 3. CONTROLS OF FLUSH VALVES SHALL BE MOUNTED ON THE WIDE SIDE OF THE TOILET NOT MORE THAN 44" ABOVE THE FLOOR. 4. ANY CABINET BENEATH THE LAVATORY IS REMOVABLE WITHOUT THE USE OF SPECIALIZED KNOWLEDGE OR SPECIALIZED TOOLS TO PROVIDE VANITY WITH KNEE AND TOE CLEARANCE . KNEE SPACE SHALL BE AT LEAST 30" WIDE 8" DEEP PER TABLE 1109A.2.2.12. FLOOR AND WALL FINISHES, INCLUDING WALL BASE, MUST CONTINUE UNDER AND BEHIND ALL REMOVABLE CABINETS. 5. PROVIDE HAND-HELD SHOWER HEAD, 60" HOSE AND SLIDE FOR ALL ACCESSIBLE UNITS. 6. PROVIDE COUNTEROP EQUIVALENT TO PENTAL QUARTZ - BQ8220P LATTICE POLISHED COUNTERTOPS WITH BACKSPLASH. PROVIDE KOHLER VERTICYL K-2882 UNDERMOUNT LAVATORY OR APPROVED EQ. LAVATORY BOWL SHOULD HAVE AN INTEGRAL OVERFLOW WHERE ALLOWED BY LOCAL CODES. FOR ADAPTABLE UNITS WHERE THE VANITY CABINET IS REMOVABLE, PROVIDE ADDITIONAL SUPPORT FOR THE COUNTERTOP THAT ALLOWS REMOVAL OF THE CABINET. 7. PROVIDE FOLLOWING BATHROOM ACCESSORIES: TOILET PAPER HOLDER WITH CERAMIC POSTS, TOWEL BAR WITH CERAMIC POSTS AND ADJUSTABLE, CHROME, TENSION-MOUNTED SHOWER ROD. FASTEN ALL TOILET ACCESSORIES TO BLOCKING. CAULK ACCESSORY POST TO WALL.

NO. 09B5 10C2 10G7 10G15

10G16 10G17 10G18 10G20 10G22 10G28 12D7

GENERAL BATHROOM VENTILATION NOTES: 1. ALL FANS MUST BE ENERGY STAR CERTIFIED. FANS SHALL BE DUCTED TO TERMINATE TO THE OUTSIDE OF THE BUILDING. 2. IF VENTING THROUGH THE ROOF OR DIRECTLY THROUGH THE SOFFIT, USE SOLID METAL DUCTING, NOT FLEXIBLE PLASTIC DUCTING, WHICH CAN SAG AND ALLOW MOISTURE TO CONDENSE AND GENERATE MOLD GROWTH. IF THE DUCT TRAVELS THROUGH AN UNCONDITIONED SPACE, INSULATE IT TO DETER CONDENSATION DURING THE WINTER SEASON. 3. FANS, NOT FUNCTIONING AS A COMPONENT OF A WHOLE HOUSE VENTILAITON SYSTEM, MUST BE CONTROLLED BY A HUMIDITY CONTROL. 4. FANS SHALL BE CAPABLE OF PROVIDING A COMPLETE CHANGE OF AIR EVERY 15 MIN. 5. FANS SHALL BE CONNECTED DIRECTLY TO THE OUTSIDE, AND THE POINT OF DISCHARGE SHALL BE AT LEAST 3 FEET FROM ANY OPENING THAT ALLOWS AIR ENTRY INTO OCCUPIED PORTIONS OF THE BUILDING.

12D8

12D10 22E2 22E9 26D1

DESCRIPTION 5/8" DENSARMOR BEHIND TUB/SHOWER ENCLOSURE (OR APPROVED EQUAL) TOWEL BAR GRAB BAR BACKING WALL MOUNTED MEDICINE CABINET (16"x26"). INSTALL SO BOTTOM EDGE OF THE REFLECTIVE SURFACE IS NO HIGHER THAN 40" A.F.F. AND AT LEAST ONE ACCESSIBLE SHELF IS NO HIGHER THAN 44" A.F.F. TOILET SOLID SURFACE COUNTERTOP WALL MOUNTED MIRROR ROBE HOOK CABINET END SUPPORT PANEL SCHLUTER TRANSITION STRIP THRESHOLD, TYP. AT ALL UNIT BATHROOMS BATHROOM BASE CABINET W/ ADAPTABLE FRONT TO MEET ALL KNEE & TOE CLEARANCES PER 2/A033 FRONT APPROACH. EXTEND F.F. TO WALL AND INSULATE PIPES AT SINK WHERE APPLICABLE (REF. SPECS) BATHROOM SLIP-IN BASE CABINET. EXTEND F.F. TO WALL AND INSULATE PIPES AT SINK. REF. DETAIL 2/A033 FOR KNEE CLEARANCE. FILLER LAVATORY: UNDERCOUNTER BATHTUB/SHOWER COMBO (SEE 26/A905) FOR FLASHING DETAIL INTERIOR LIGHTING: WALL SURFACE MOUNTED (REF. ELEC. DWGS)

SHEET TITLE

BATH PLANS + INTERIOR ELEVATIONS

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

DATE

LEGEND

SCALE

EXHAUST FAN, SEE BATHROOM PLANS A638- A646, SEE ELEC. AND MECH. DWGS. REFER TO SHEET A041 FORM GRN 14 NOTES 25 & 26.

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO.

MEDICINE CABINET: 1. MEDICINE CABINET BOTTOM SHELVE SHALL BE MOUNTED AT 44" MAX.

1501 03-03-2017 As indicated

SHEET NO. GRAB BAR BACKING FOR TUB & TOILET, TYP. SEE A033-A034 FOR ADA CLEARANCES. * CONTRACTOR TO INSTALL BACKING FOR ALL CLOSET SHELVING AND BATHROOM ACCESSORIES.

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

KEYNOTES LEGEND

*WHERE PLUMBING IS ROUTED BEHIND BASE CABINETS, REF. PLUMBING DWGS, BASE CABINET DEPTH SHALL BE REDUCED TO ACCOMODATE PLUMBING. PLUMBING SHALL BE ROUTED DIRECTLY AGAINST WALL FINISH.

A638


FOF

17' - 10"

L IC E DONA

A

NI

R

8' - 3" 5' - 5 3/4" CLR.

1' - 0"

9 TREADS @ 11" EA

4' - 5 5/8" CLR.

1' - 11"

1' - 0"

LANDING

3' - 10" CLR.

1' - 11"

4 3/8"

FOC

13

1' - 0"

S7

1' - 6"

DN

LCE

17' - 10"

1' - 5 3/8"

7' - 10 3/8"

4' - 0" CLR.

UP

13 TREADS @ 11" EA

MIN. CLR. 11' - 11"

MIN. CLR.

4' - 5 5/8" CLR.

1' - 11"

3' - 8 1/8" 1' - 0" 1' - 11"

5 TREADS @ 11" EA

4' - 7" 16' - 3 3/8"

3' - 8"

FOC

FOC

LCE

DOOR CLEARANCE

618.25'

1' - 11"

S7

CLASS I WET STANDPIPE

3' - 8" MIN. CLR.

11" TREAD

11

STAIR #8 SECTION 1 1/4" = 1'-0"

7

FOF

5' - 0" CLR.

L7

STAIR #1 - ROOF 1/4" = 1'-0"

STAIR #1 - GROUND LEVEL 1/4" = 1'-0"

3

L5

LC9

L7

LC10

7' - 10 3/4" CLR.

LC12

5' - 3"

7' - 10 3/4" CLR.

1' - 0"

7 5/8"

LCE

FOC DN

S1

17' - 11 1/8" CLR.

5' - 1 3/8" CLR.

UP

1' - 0"

2' - 6"

1' - 11"

DOOR CLEARANCE

8 TREADS @ 11" EA

8' - 3"

MIN. CLR.

4' - 6 3/4" CLR.

1' - 11"

CLR.

3' - 8 1/8" 1' - 0" 8 TREADS @ 11" EA

7' - 4"

3' - 10" CLR.

690.92'

MIN. CLR.

MIN. CLR.

S3

Sim

23 A908

CLASS I WET STANDPIPE

FOC

FOC

DOOR CLEARANCE

3' - 8"

2' - 6"

SEVENTH FLOOR 690.92'

UP

3' - 8"

A.O.R.

A.O.R.

5' - 1 3/8" CLR.

1' - 11"

5' - 1 3/8" CLR.

1' - 4"

Sim

18 A908

UPPER TERRACE 692.25'

16' - 3 3/8" CLR.

MIN. CLR.

17' - 10" CLR.

MIN. CLR.

7' - 4"

3' - 8"

4' - 5 5/8" CLR.

1' - 11"

1' - 0"

3' - 8"

9 TREADS @ 11" EA

POOL DECK 695.92'

PROVIDE TWO - WAY COMMUNICATION PER 2014 LABC 1007.8.1 & 1007.7.8.2

6' - 0 3/8" CLR.

A908

Sim

LG

1' - 0"

24 A908

9 TREADS @ 11" EA

Sim

5

FOF

8' - 3"

HANDRAIL ATTACHMENT AT GLASS PER MANUFACTURER SPECIFICATIONS

A701

FOF 4' - 5 5/8" CLR.

LG

FOF

FOF

13

604.97'

FOC

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

DN

3' - 8"

FOC

LCE

CLASS I WET STANDPIPE

13 A701

STAIR #9 SECTION 1 1/4" = 1'-0"

6

STAIR #1 - 7TH FLOOR 1/4" = 1'-0" L5

2

L7

STAIR #1 - P1 1/4" = 1'-0"

LC9

LC10

LC12

5' - 0" CLR.

1' - 11"

FOC

FOC

FOC FOC

4' - 6 3/4" CLR.

1' - 0" 1' - 11"

17' - 11 1/8" CLR.

7 TREADS @ 11" EA

CLR.

3' - 8 1/8"

3' - 10" CLR. 6' - 5"

17' - 10" CLR.

9 TREADS @ 11" EA

7' - 4"

4' - 5 5/8" CLR.

LCE

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

PROVIDE TWO - WAY COMMUNICATION PER 2014 LABC 1007.8.1 & 1007.7.8.2

A.O.R.

S3 649.92'

1' - 0"

MIN. CLR.

CLASS I WET STANDPIPE

3' - 0"

DOOR CLEARANCE

UP

LR .

DN

A.O.R.

1' - 11"

UP

MIN. CLR. DOOR CLEARANCE

0"

A701

MIN. CLR.

3' - 8"

MIN .C

A701

MIN. CLR.

CANE DETECTION RAIL, SEE 26 / A033

S1

3' -

10

3' - 8"

594.97'

6' - 0 3/8" CLR.

10

DN

3' - 8"

16' - 3 3/8" CLR.

4' - 9" CLR.

695.92'

6' - 1 3/8"

692.25'

CLR.

GT10

5' - 5 1/2"

LD

17' - 10" CLR.

PD

8' - 3"

4' - 11 1/2" CLR.

5' - 9 1/2"

ENLARGED STAIR PLANS

1' - 0"

LG

5' - 1 3/8" CLR.

4' - 5 5/8" CLR.

05G10

1' - 0"

05G2

FOF

FOF

1' - 11"

LG

6 TREADS @ 11" EA 1' - 11"

7' - 10 3/4" CLR.

5' - 11 1/2"

1' - 0"

5' - 6"

1' - 11"

4' - 9" CLR.

9 TREADS @ 11" EA

EQ. SPACED

6' - 6 1/8"

FOF

FOF

7 5/8"

LD

SHEET TITLE

7' - 10 3/4" CLR.

FOC

CLASS I WET STANDPIPE

3' - 2 3/8"

LCE

LC9

LC10

L19

FOC

FOC

FOC

A701

A701

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO. DATE

13

3/9/2017 2:40:02 PM

O

A701

13

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

CA L I F

LC12

1' - 0"

703.69'

CLASS I WET STANDPIPE

EQ. SPACED

35 RISERS @ 7" MAX. EA. = 20' - 0 1/2"

9' - 2 5/8"

7' - 2 5/8"

1' - 0"

1' - 2 3/8"

STAIR #1 SECTION 1/4" = 1'-0"

OF

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

DOOR CLEARANCE

P2 594.97'

13

E

LANKERSHIM + otsego

17 A902

6' - 0 3/8" CLR.

Sim

MIN. CLR.

Sim

6' - 8"

17 A908

TYP.

3' - 0"

A908

16 A908

FOC

1' - 0"

S6

7' - 10 3/4" CLR.

6' - 0"

1' - 4"

UPPER TERRACE 692.25' SEVENTH FLOOR 690.92'

17' - 10" CLR.

POOL DECK 695.92'

10 TREADS @ 11" EA.

MIN. CLR.

9' - 2"

MIN. CLR.

4' - 2 3/8" CLR.

3' - 8"

1' - 0"

3' - 8"

3' - 8"

LG

4' - 5 5/8" CLR.

1' - 11"

12' - 11"

17 A902

4' - 11" CLR.

25 A908

Sim

3' - 10" CLR.

A701

FOF

Sim

PEDESTAL PAVER SYSTEM

EQ. SPACED

5

8 TREADS @ 11" EA

7 5/8"

FOF

WHEELCHAIR LIFT RAMP PER MANUFACTURER

LIFT RISE

15 A909

P1 604.97'

Sim

7' - 4"

L7

1' - 0"

SIDE WALLS, SEE PLAN

CLR.

Sim

16 A908

REN. 6-30-17

STAIR #1 - 2ND FLOOR 1/4" = 1'-0"

4

WHEELCHAIR LIFT SEE A062 CUT SHEET

3 7/8"

6' - 8"

Sim

MIN. CLR.

17 A908

TYP.

3' - 0"

A908

23 RISERS @ 7" MAX. EA. = 13' - 4 7/8"

Sim

CLASS I WET STANDPIPE

FOF

FOF

LG

10

18 RISERS @ 7" MAX. EA. = 10' - 0"

5

638.42'

STAIR #8 ENLARGED PLAN 1/4" = 1'-0"

L19 17 A908

NO. C-13779

FOF

13

MARKET GROUND FLOOR 618.38' Sim

ED A RCH NS S EMP I A TA

LCE FOF

1' - 0"

3' - 0"

Sim

16 A908

TYP.

6' - 8"

A908

MIN. CLR.

Sim

17 A908

MIN. CLR.

6' - 8" 3' - 6"

3' - 0"

Sim

5

STAMP

LCE

DN

Sim

16 A908

S3

1' - 0"

8

TYP.

3' - 0"

A908

" 3/4

DN

DOOR CLEARANCE

7' - 10 3/4"

Bath at L-A3 sim3 638.42'

Sim

17 A908

. EA 11"

UP

CLR.

STAIR #8 SECTION 2 1/4" = 1'-0"

17' - 10" CLR.

5

5' - 5 3/4" CLR.

1' - 4"

6 8' -

7 RISERS @ 7" MAX. EA. = 3' - 8" EQ. SPACED

Sim

17' - 10"

5' - 0"

Sim

EQ. SPACED

20 RISERS @ 7" MAX. EA. = 11' - 6"

Sim

16 A908

MIN. CLR.

6' - 8"

TYP.

3' - 0"

Sim

"

S@ AD E R 6T

L5

EQ. SPACED

18 RISERS @ 7" MAX. EA. = 10' - 3"

MIN. CLR

6' - 8"

20 A908

A908

6 5' -

MIN. CLR.

LC10

EQ. SPACED

18 RISERS @ 7" MAX. EA. = 10' - 3"

MIN. CLR.

6' - 8"

TYP.

Sim

"

MIN. CLR.

4 3/8"

7 RISERS @ 7" MAX. EA. = 3' - 8" EQ. SPACED

8' - 8"

HEAD CLR.

6' - 8" MIN. 2' - 6"

12

EQ. SPACED

18 RISERS @ 7" MAX. EA. = 10' - 3"

MIN. CLR.

6' - 8"

TYP.

0 1' -

THIRD FLOOR 649.92' 5

1"

GT11

EQ. SPACED

18 RISERS @ 7" MAX. EA. = 10' - 3"

6' - 8"

MIN. CLR.

TYP. TYP.

EQ. SPACED

21 RISERS @ 7" MAX. EA. = 12' - 5 5/8"

6' - 8"

MIN. CLR.

TYP.

3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0"

DN 695.92'

3' - 8"

CT TE ERIS K

Sim

9"

3' - 8"

T

Sim

18 A908

Sim

692.25'

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

ST A

22 A908

21 A908

R. CL

A908

1"

1 1' -

FOURTH FLOOR 660.17'

Sim

A701

" 1/2

Sim

Sim

2 6' -

Sim

18 A908

5

24 A908

DE Architects AIA

9"

21 A908

R. CL 30"

22 A908

Sim

A701

S FO

A908

"

695.92'

13

5

FIFTH FLOOR 670.42'

Sim

5

R. CL

Sim

" 1/2

Sim

18 A908

Sim

1 1' /8" 05 ' 9

0 1' -

R. CL

21 A908

A908

22 A908

UPPER TERRACE 692.25' SEVENTH FLOOR 690.92'

SIXTH FLOOR 680.67'

Sim

5

0 4' -

Sim

POOL DECK 695.92'

R. CL " 8 4

" 1/8

Sim

18 A908

Sim

21 A908

A908

22 A908

23 A908

SEVENTH FLOOR 690.92'

Sim

5

R. CL

Sim

-8 11'

18 A908

" 5/8

22 A908

Sim

12

8 4' -

A908

E

A701

0"

Sim

692.25'

12'

ROOF 702.82'

5

18 A908

Sim

R. CL " 1/4

/8" 81

A908

/4" 73

1' - 0"

11

WHEELCHAIR LIFT SEE A062 CUT SHEET

S FO

Sim

11 4' -

7' - 10 3/4" CLR.

" 5/8

5

5

KEEP A CONTINOUS MINIMUM HEADROOM OF 80" THROUGH THE ENTIRE STAIRWAY & LANDING PER LABC 1009.5.

10 6' -

" 7/8

LC12

7 5/8"

/4" 73 8 4' -

WET STANDPIPE LOCATIONS: SPECIFY 12" MAXIMUM PROTRUSION FOR POSTMOUNTED OBJECTS, 4" MAXIMUM PROJECTION FOR PROTRUSIONS FROM A WALL, OR PROVIDE CANE DETECTION AT THESE LOCATIONS.

LC10

E

5' - 4 5/8" CLR.

6' -

/4" 23

" 1/4

FOF

3 4' -

/8" 37

NOTE: PROVIDE AN APPROVED STAIRWAY SIGN INDICATATING THE FLOOR LEVEL, TERMINUS OF THE TOP AND BOTTOM OF THE STAIR AND THE IDENTIFICATION NUMBER OF THE STAIR. IT SHALL BE LOCATED APPROXIMATELY 5 FT ABOVE THE FLOOR LANDING AND BE READILY VISIBLE WHEN THE STAIR DOORS ARE IN AN OPEN OR CLOSED POSITION. SEE DETAIL 34/A033, 9/A033

1501 03-03-2017

SCALE

LC12

1/4" = 1'-0"

SHEET NO.

9

STAIR #9 ENLARGED PLAN 1/4" = 1'-0"

5

STAIR #1 - 3RD-6TH FLOOR 1/4" = 1'-0"

1

STAIR #1 - P2 1/4" = 1'-0"

A701


C3

SEE A710 FOR ELEVATOR NOTES C2

Bath at L-A3 sim3 638.42'

LC14 6' - 11"

L9 0 1' -

6' - 6 1/2"

FOF

1' - 6"

SEVENTH FLOOR 690.92'

90 MIN. FIRE-RATED DOORS AND SMOKE CONTAINMENT

MAX. PIT

0 1' -

10' - 0"

FOF

FOF

5' - 0" 10' - 3"

P2 594.97'

LC12

ELEVATOR #1 SECTION 3/16" = 1'-0"

7

10'

LC14

OF

CA L I F

O

6 2' -

L9

"

C2

6"

R EA CL

CE

6' - 6 1/2"

CLEAR

SIXTH FLOOR 680.67'

10' - 3"

F FO

F FO

6' - 11"

E

F FO

A708

LCE

FOF

FOF

REN. 6-30-17

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

4

FILL PIT WITH STYROFOAM

4

F FO

SEE 16, 17 & 18/A033 FOR ELEVATOR LOBBY CONTROL PANEL AND ELEVATOR CONTROLS DIMENSIONS & ELEVATIONS

P1 604.97'

LCE

NO. C-13779

CE

90 MIN. FIRE-RATED DOORS

MIN. TYP.

42"

13' - 4 7/8"

17' - 10"

19' - 4"

CG CLEAR

7' - 9" 9"

11' - 10 3/4"

ED A RCH NS S EMP I A TA

T

HOIST BEAM

9 A708

STAMP

A708

CT TE ERIS K

9 A708

SEE 16, 17 & 18/A033 FOR ELEVATOR LOBBY CONTROL PANEL AND ELEVATOR CONTROLS DIMENSIONS & ELEVATIONS

SMOKE CONTAINMENT BARRIER: SMOKE GUARD M400 (TYP.)

4

F FO

ST A

15' - 1" MIN. - 17' - 1" MAX

LCF

FOF

MARKET GROUND FLOOR 618.38'

SMOKE CONTAINMENT BARRIER: SMOKE GUARD M400

"

. YP .T MIN 42"

CAB HEIGHT

LINE OF FUTURE FINISHED FLOOR

6 2' -

LCF

F FO

R EA CL

" -0 17' R EA CL

9' - 9"

ROOF 702.82'

CAB HEIGHT

T.O. PARAPET 705.32'

Sim

6"

" -0 17' R EA CL

13' - 1" MIN. - 15' - 1" MAX.

MEZZANINE LEVEL 628' - 10 9/16"

20' - 0 1/2"

10' - 0"

24 A915

10'

C3

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

CG

0"

F FO

HOIST BEAM (SEE STRUCT. DWGS.)

14'

F FO

HOIST BEAM (SEE STRUCT. DWGS.)

PROVIDE ELEVATOR HOISTWAY VENTING AS REQUIRED. THE AREA OF THE VENT SHALL NOT BE LESS THAN 3 1/2% OF AREA OF ELEVATOR SHAFT. PROVIDE A MINIMUM 3 SQ. FT. PER 2013 CBC SEC. 3004. TYPICAL

FOF

CLEAR

DE Architects AIA

"

A

LC12

NI

14 A909

C1

Sim

R

LC14

L IC E DONA

LC12

"

C3

ELEVATOR #2 GROUND FLOOR ENLARGED PLAN 1/4" = 1'-0"

ELEVATOR #1 GROUND FLOOR ENLARGED PLAN 1/4" = 1'-0"

3

C1 LC14

L9

LC12

LC14

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

L7

FIFTH FLOOR 670.42'

6' - 11"

FOF

C3

FOF

10' - 3"

LG

LCF

1' - 6"

1' - 6"

FOF

FOF

"

" -0 17' R EA CL

11"

FOF

LG

F FO

F FO

FOURTH FLOOR 660.17'

6"

R EA CL

6 2' -

LCF

F FO

10'

CG

F FO

CLEAR

FOF

SMOKE CONTAINMENT BARRIER: SMOKE GUARD M400 (TYP.)

4

10' - 3"

F FO

9

9

9

9

A708

A708

A708

A708

A708

CLEAR

17' - 10"

CLEAR

17' - 10"

19' - 4"

CLEAR

NO STOP

F FO

TYP.

F FO

11' - 6"

"

SEE 16, 17, 18/A033 FOR ELEVATOR LOBBY CONTROL PANEL AND ELEVATOR CONTROLS DIMENSIONS & ELEVATIONS

0 4' -

SEE 16, 17 & 18/A033 FOR ELEVATOR LOBBY CONTROL PANEL AND ELEVATOR CONTROLS DIMENSIONS & ELEVATIONS

F FO " -0 17' R EA CL

3' - 6" MIN.

17' - 10"

CLEAR

CLR.

90 MIN. FIRE-RATED DOORS AND SMOKE CONTAINMENT BARRIER: SMOKE GUARD M400

"

THIRD FLOOR 649.92'

5' - 2"

CE

0 4' -

17' - 10"

CG 90 MIN. FIRE-RATED DOORS AND SMOKE CONTAINMENT BARRIER: SMOKE GUARD M400

4

FOF

LCE

FOF

LCE

LCE

FOF

A708

LCE

FOF

C1

FOF

FOF

FOF

FOF

7' - 2 1/2"

CE

6 2' -

6' - 11"

9' - 6 1/2"

MEZZANINE LEVEL 628' - 10 9/16"

C3 LC14

L9

LC12

ELEVATOR #2 3RD-7TH FLOOR ENLARGED PLAN 1/4" = 1'-0"

6

LC14

L9

ELEVATOR #2 P1 ENLARGED PLAN 1/4" = 1'-0"

2

ELEVATOR #1 P1 ENLARGED PLAN 1/4" = 1'-0" OF CE FA LL TO WA 9" MU C

C1 LC14 6' - 11"

LC12

L9

6' - 11"

FOF

FOF

ENLARGED ELEVATOR PLANS AND SECTIONS

FOF 14'

2"

10' - 0"

1' - 0"

LCE

FOF

LCE

A708

CLEAR

17' - 10"

FOF

CG

ELEVATOR PIT

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

F FO

LCE

FOF

FOF

FOF

FOF

5' - 0"

A708

6' - 6 1/2"

CLEAR

CLEAR

TREMCO SALTWATER PARASEAL BENTONITE SHEET MEMBRANE SALINE CONDITION DUAL WATERPROOFING SYSTEM, TYP.

LC12

LC14

LC12

L9

"

JOB NO. F FO

6' - 11"

0 2' -

6' - 11"

" -6 10' R EA CL

C1

DATE

CE

LC14

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

CE

4

BENTONITE WATER STOP CONTINUOUS

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

4

F FO

P2 594.97'

FOF

90 MIN. FIRE-RATED DOORS AND SMOKE CONTAINMENT BARRIER: SMOKE GUARD M400 SEE 16, 17, 18/A033 FOR ELEVATOR LOBBY CONTROL PANEL AND ELEVATOR CONTROLS DIMENSIONS & ELEVATIONS

SEE 16, 17, 18/A033 FOR ELEVATOR LOBBY CONTROL PANEL AND ELEVATOR CONTROLS DIMENSIONS & ELEVATIONS FOF

6"

A708

TYP.

3' - 6" MIN.

90 MIN. FIRE-RATED DOORS AND SMOKE CONTAINMENT BARRIER: SMOKE GUARD M400

LCE

10'

9

CLEAR

17' - 10"

19' - 4"

19' - 4"

A708

17' - 10"

A708

CLEAR

3' - 6" MIN.

9

CLEAR

17' - 10"

9

" -0 17' R EA CL

TYP.

CH

SMOKE CONTAINMENT BARRIER: SMOKE GUARD M400 (TYP.)

3/9/2017 2:40:54 PM

SHEET TITLE

F FO

ELEV. CONTROL ROOM

NO STOP

FOF

P1 604.97'

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

LCF

1' - 6"

LCF

1' - 6"

LCF

1' - 6"

1' - 6"

FOF

A708

ELVATOR #2 SECTION 1/4" = 1'-0"

" 3/8

FOF

9

9

P15

CG

LCF

13' - 4 7/8"

CLEAR

Sim

5 8' -

FOF

LC15

BENTONITE WATER STOP CONTINUOUS

CH

6' - 6 1/2"

CLEAR

MARKET GROUND FLOOR 618.38'

LC14

FOF

10' - 6"

LC12

26 A915

"

CLEAR

6' - 6 1/2"

CLEAR

L7

10

" '-6

R EA CL

F FO

8 1/2"

"

F FO 10

Bath at L-A3 sim3 638.42'

0 2' -

LANKERSHIM + otsego

6' - 6 1/2"

FOF

7' - 11"

SCALE

1501 03-03-2017 As indicated

SHEET NO.

8

ELEVATOR #2 SECOND FLOOR ENLARGED PLAN 1/4" = 1'-0" (MEZZANINE SIMILAR)

5

ELEVATOR #2 P2 ENLARGED PLAN 1/4" = 1'-0"

1

ELEVATOR #1 P2 ENLARGED PLAN 1/4" = 1'-0"

A708


05G10 05G10.1 07F3

07J10

05G10

26 A903

05G10

17 A909

42"

07J10 42"

14 A909

26 A903

Sim

42" SURFACE MOUNTED GLASS GUARDRAIL 42" SURFACE MOUNTED ETCHED GLASS GUARDRAIL UPI POLYURETHANE PEDESTRIAN COATING (LARR 25261) - W/MONTEREY SAND AGGREGATE AND CLEAR COAT, OR APPROVED EQ. ROOF PEDESTAL PAVER SYSTEM, BY TILE TECH PAVERS OR APPROVED EQ, - SINGLE PLY ROOFING SYSTEM BELOW. (REF. LANDSCAPE DWGS.)

07J10

UPPER TERRACE 692.25'

UPPER TERRACE 692.25'

UPPER TERRACE 692.25'

SEVENTH FLOOR 690.92'

SEVENTH FLOOR 690.92'

SEVENTH FLOOR 690.92'

DE Architects AIA 1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

7 A904

Sim

26

26

A901

Sim

29

Sim

26 A901

A901

A901

Sim

STAMP

L IC E DONA

CT TE ERIS K

ED A RCH NS S EMP I A TA

E

MIN. TYP.

42"

OF

R

T

05G10.1

NI

ST A

REN. 6-30-17

A

NO. C-13779

CA L I F

O

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

SIXTH FLOOR 680.67'

SIXTH FLOOR 680.67'

SIXTH FLOOR 680.67' 32 A902

25 TYP.

25

TYP.

27 A906

G.W.B. SOFFIT TO MATCH STEP IN CEILING. CONTINUE FOR EXENT OF ENTIRE ROOM

A901

25

Sim

4 1/8"

17 A904 TYP.

A901

CEMENT PLASTER DROPPED SOFFIT

28

Sim

A901

A901

FIFTH FLOOR 670.42'

32 A902 4 1/8"

17 A904

25 TYP.

25

25

TYP.

28

CEMENT PLASTER DROPPED SOFFIT

A901

Sim

27 A906

TYP.

A901

Sim

Sim

G.W.B. SOFFIT TO MATCH STEP IN CEILING. CONTINUE FOR EXENT OF ENTIRE ROOM

A901

A901

MIN. TYP.

17 A904

25 A901

TYP.

25

TYP.

27

G.W.B. SOFFIT TO MATCH STEP IN CEILING. CONTINUE FOR EXENT OF ENTIRE ROOM

Sim

FOURTH FLOOR 660.17'

FOURTH FLOOR 660.17' 32 A902

Sim

25

TYP.

A901

A906

4 1/8"

42"

05G10.1

FOURTH FLOOR 660.17'

CEMENT PLASTER DROPPED SOFFIT

28

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

FIFTH FLOOR 670.42'

Sim

A901

A901

LANKERSHIM + otsego

FIFTH FLOOR 670.42'

MIN. TYP.

42"

05G10.1

THIRD FLOOR 649.92'

MIN. TYP.

42"

05G10.1

THIRD FLOOR 649.92'

THIRD FLOOR 649.92'

Sim

6

6

A902

4"

13 A903 Sim

A902

8 A904

6

Sim

Sim

A902

CEMENT PLASTER DROPPED SOFFIT

SHEET TITLE

WALL SECTIONS

Sim

42"

4 A911 07F3

MIN. TYP.

2 A911

05G10

Bath at L-A3 sim3 638.42'

6

Bath at L-A3 sim3 638.42'

Sim

6

WALL SECTION 03 1/2" = 1'-0"

6 A902

2

WALL SECTION 02 1/2" = 1'-0"

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

1

WALL SECTION 01 1/2" = 1'-0"

Sim

11 A904 THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO. DATE

9/2017 2:41:02 PM

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

16 A903

A902

A902

3

Sim

Bath at L-A3 sim3 638.42'

1501 03-03-2017

SCALE SHEET NO.

1/2" = 1'-0"


KEYNOTES LEGEND

07E1 T.O. PARAPET 705.32'

14 A909

NO. 05G5

Sim

05G9 ROOF 702.82'

26

Sim

07F3

1' - 7 1/4"

Sim

29

07E1

23A9

A901

A901

DESCRIPTION 42" STEEL GUARDRAIL W/ METAL SALES T16E CORRUGATED PERFORATED METAL INFILL. KYNAR FINISH TO BE DETERMINED BY ARCHITECT 42" SIDE MOUNTED ETCHED GLASS GUARDRAIL KEE SINGLE PLY MEMBRANE ROOF ICC# ESR-1456 - SRI OF 78 OR BETTER - COOL ROOF (SEE SHEET A060) UPI POLYURETHANE PEDESTRIAN COATING (LARR 25261) - W/MONTEREY SAND AGGREGATE AND CLEAR COAT, OR APPROVED EQ. METAL GARAGE EXHAUST LOUVERED VENT - RUSKIN ELF375DX ALUMINUM OR APPROVED EQ. - 43% FREE OPENING (REF. MECH. DWGS.)

DE Architects AIA 1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

STAMP 05G9 07E1

13 A904

Sim

Sim 25

9 A909

TYP. 29

A901

Sim

E

OF

A

REN. 6-30-17

NI

10 A909

NO. C-13779

T

07F3

SEVENTH FLOOR 690.92'

Sim

ST A

7 A911

14 A909

R

33 A902

ED A RCH NS S EMP I A TA

T.O. PARAPET 705.32'

L IC E DONA

Sim

07F3

CT TE ERIS K

2 A911

TYP.

CA L I F

O

ROOF 702.82'

Sim

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

Sim

A901 Sim

26

Bath at L-A3 sim3 638.42'

A901

05G9

SIXTH FLOOR 680.67'

POOL DECK 695.92'

TYP. 29 A901

33 A902

SEVENTH FLOOR 690.92'

Sim

42"

A901

TYP.

05G9

MIN. TYP.

25

07F3

05G5

33 A902

TYP.

FIFTH FLOOR 670.42'

Sim 25

A901

TYP. 29 A901

A901

Sim TYP.

25 05G9 29

Sim

A901

A901 07F3

42"

05G5 FOURTH FLOOR 660.17'

25

MIN. TYP.

20 A903

07F3

SIXTH FLOOR 680.67'

TYP. 29

A901

Sim

A901 SIXTH FLOOR 680.67'

9 A904

10 A906

05G9 29 07F3

MARKET GROUND FLOOR 618.38' 25

28 A906

TYP.

Sim

A901

A901

21 A903

Sim

TYP.

25

05G5

THIRD FLOOR 649.92'

A901

TYP.

15 A903

15 A907

FIFTH FLOOR 670.42'

Sim

TYP.

25 16 A903

29

Sim

Sim

10 A906

LANKERSHIM + otsego

26

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

SEVENTH FLOOR 690.92'

A901

A901

28 A906 05G5

07F3

FIFTH FLOOR 670.42'

05G9

33 A902

TYP.

Bath at L-A3 sim3 638.42'

25

FOURTH FLOOR 660.17'

26 A904

TYP.

A901 TYP.

25 29

SOLID GALV. 22 ga MTL.

Sim

A901

A901

P1 604.97' 25 A904

3' - 6" CLR.

23A9

16 A903

Sim 07F3 15 A906 THIRD FLOOR 649.92'

24 A904

SHEET TITLE

WALL SECTIONS

26 7/8"

FOURTH FLOOR 660.17'

25

05G5

TYP.

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

DROPPED MTL. SOFFIT REF. ELEVATION7/8" CEMENT PLASTER FINISH

A901

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

P2 594.97' 17 A903

Sim

2 A911

1' - 0" 4 A911

Sim

CLR. 07F3 13 A904

THIRD FLOOR 649.92'

Sim

Sim

Bath at L-A3 sim3 638.42'

MARKET GROUND FLOOR 618.38' Sim 18 A904

3/9/2017 2:41:11 PM

28 A906

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO. DATE

1501 03-03-2017

SCALE

WALL SECTION @ GARAGE 4 1/2" = 1'-0" DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

WALL SECTION @ EXTERIOR WALL 3 1/2" = 1'-0"

WALL SECTION @ BALCONIES 02 2 1/2" = 1'-0"

WALL SECTION @ BALCONIES 01 1 1/2" = 1'-0"

1/2" = 1'-0"

SHEET NO.

A803


L2

KEYNOTES LEGEND

14 A909

T.O. PARAPET 705.32'

Sim

4

PEDESTAL SYSTEM - OVER 10 MM RUBBER PAD (ECORE QT OR APPROVED EQ) CUT MATTING TO APPROX. SIZE OF PEDESTAL, TYP.

C2

NO. 05G10

KEE ROOFING SYSTEM

06A33 07J10

CONC. PAVER

23A14

ROOF 702.82'

DESCRIPTION 42" SURFACE MOUNTED GLASS GUARDRAIL WOOD JOIST ROOF SYSTEM ROOF PEDESTAL PAVER SYSTEM, BY TILE TECH PAVERS OR APPROVED EQ, - SINGLE PLY ROOFING SYSTEM BELOW. (REF. LANDSCAPE DWGS.) MECHANICAL EQUIPMENT PLATFORMS, TYP.

DE Architects AIA 1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

JOINT SEALANT & BACKER ROD 26

T.O. PARAPET 705.32'

Sim

A901

28 A904

CONC. COPING

Sim

POOL DECK 695.92'

SUPPORT PER POOL DWGS.

ROOF 702.82'

STAMP

5/8" PLYWOOD PER STRUCT. DWGS.

L IC E DONA

STAINLESS STEEL POOL

7 A911

RIP JOIST PER STRUCT. DWGS.

Sim

CLAD MTL. COUNTER FLASHING

RAISED FLOOR JOIST PER STRUCT. DWGS.

10 A909

Sim

Sim

A

NI

R

O

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

SEVENTH FLOOR 690.92'

UPPER TERRACE 692.25'

2" CONC. TOPPING SLAB PER POOL DWGS.

SEVENTH FLOOR 690.92'

SEE STRUCT. DWGS.

1" NEOPRENE PAD

44 1/2"

STAINLESS STEEL CONTAINMENT

4 A807

8 25

1' - 8 1/2" 4 A807

SECTION @ MECHANICAL EQUIPMENT SCREEN 2 1/2" = 1'-0"

Sim

N.T.S.

1' - 8 1/2"

PEDESTAL PAVING SYSTEM

STAINLESS STEEL SPA

TYP.

A901

LD

LA

SEVENTH FLOOR-K 687.42'

2" CONCRETE LEVELING BED, OVER 1" NEOPRENE PAD, OVER STEEL CONTAINMENT- SLOPED TO DRAIN - OVER PLYWOOD SHEATHING (PER STRUCTURAL)

FIFTH FLOOR 670.42'

7 A911

05G10

07J10

TYP.

6' - 6"

A901

23A14

5 A911

44 1/2"

Sim

Sim

Sim

1' - 9 1/2"

V.I.F.

3' - 10"

10 A909

SPA SECTION - BUILDING 2 1/2" = 1'-0"

POOL DECK 695.92'

4 A909 11 A909

3

06A33

7' - 10"

25

Sim

LANKERSHIM + otsego

SIXTH FLOOR 680.67'

Sim

FIRE RATING

POOL/SPA TO DECK TRANSITION DETAIL

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

4

STEEL TUBE FRAME WINDOW CANOPY 18 ga. 3/32" ROUND, 5/32" STAGGERED GLAV. PERFORATED METAL. TYP.

CA L I F

STEEL C-CHANNEL PER POOL DWGS.

2' - 9 5/8"

6' - 5"

2' - 6"

A901

OF

FLOOR JOIST PER STRUCT. DWGS.

10 3/8"

25

11 A909

4 A909

Sim

V.I.F.

10 A907

07J10

TYP.

Sim

4 A909

E

KEE ROOFING SYSTEM

CONDENSER UNITS, TYP.

SEVENTH FLOOR 690.92'

REN. 6-30-17

T

5 A911

NO. C-13779

STRUCT. SUPPORT WATERPROOF PENETRATIONS PER MANUF. RECOMMENDATIONS, TYP. PER STRUCT. DWGS

ST A

86 1/2"

POOL

Sim

CT TE ERIS K

ED A RCH NS S EMP I A TA

4 A807

Sim

1' - 10 1/2"

4 A807

Sim

POOL DECK 695.92'

UPPER TERRACE 692.25'

SEVENTH FLOOR 690.92'

FOURTH FLOOR 660.17' SEVENTH FLOOR 690.92'

25

TYP.

A901

SECTION @ MECHANICAL EQUIPMENT SCREEN 1/2" = 1'-0"

86 1/2"

7

2" CONCRETE LEVELING BED, OVER 1" NEOPRENE PAD, OVER STEEL CONTAINMENT- SLOPED TO DRAIN OVER PLYWOOD SHEATHING (PER STRUCTURAL)

2 7 A911

SPA SECTION - BUILDING 1 1/2" = 1'-0"

SHEET TITLE

POOL SECTIONS & DETAILS

Sim

PEDESTAL PAVING SYSTEM 34 A904

1' - 8 1/2"

1' - 8 1/2"

4 A807

STAINLESS STEEL POOL

4 A807

Sim

17 A902

POOL DECK 695.92'

THIRD FLOOR 649.92'

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

1' - 0"

15 A902 UPPER TERRACE 692.25'

SEVENTH FLOOR 690.92'

2" CONCRETE LEVELING BED, OVER 1" NEOPRENE PAD, OVER STEEL CONTAINMENT- SLOPED TO DRAIN - OVER PLYWOOD SHEATHING (PER STRUCTURAL)

3/9/2017 2:41:31 PM

4 A911 Bath at L-A3 sim3 638.42'

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO. DATE

STAINLESS STEEL POOL

SCALE

00000 Section 125 6 1/2" = 1'-0" DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

POOL SECTION - BUILDING 1 1 1/2" = 1'-0"

1501 03-03-2017 As indicated

SHEET NO.

A807


BOLTS PER STRUCTURAL @ 9" O.C., TYP.

BOLTS PER STRUCTURAL @ 9" O.C., TYP.

FIRE CAULKING, TYP. CMU WALL WITH REINFORCEMENT PER STRUCTURAL

REFERENCE 21/S105

NO

RE HE S R NE TE S FA

1/2"

RS NE E ST FA

1/2" x 1 1/2" FLAT STEEL BAR, TYP. ANCHOR TO WALL TYP.

FIRE CAULKING, TYP. CMU WALL WITH REINFORCEMENT PER STRUCTURAL

NO

VARIES

RE HE

STRUCTURAL PODIUM SLAB

8" MIN.

1/4" x 2 1/4" FLAT STEEL BAR

IMPORTANT: CONSULT MANUFACTURER FOR ADDITIONAL INFORMATION REGARDING PLYWOOD SHEATHING, FRAMING/BLOCKING AND SHEET METAL INSTALLATION REQUIREMENTS

4"

IMPORTANT: CONSULT MANUFACTURER FOR ADDITIONAL INFORMATION REGARDING PLYWOOD SHEATHING, FRAMING/BLOCKING AND SHEET METAL INSTALLATION REQUIREMENTS

NOTE: INTERRELATED EDGE AND PERIMETER FLASHING NOT SHOWN FOR CLARITY

3/4" GYPCRETE

A902

SLOPE

FIRE RATING

WALL / FURRED ROOF TRANSITION DETAIL

26

20" MAX.

FRTW 2X DBL TOP PLATE

FRTW PLYWOOD SHIM

PLYWOOD SHEATHING PER STRUCT.

2 LAYERS OF 5/8" GYP. BD.

FRTW PLYWOOD PER STRUCT.

24 GAUGE BONDERIZED SHEET METAL

6" MIN.

6

5/8" EXTERIOR GYP. BD.

FASTENERS 1/2" MIN. ABOVE DECK ON VERTICAL LEG, TYP.

1/2" FIELD VERIFY

A901

CORRUGATED METAL PANEL BUILDING PAPER OVER 1 LAYER TYVEK

N.T.S.

FIRE RATING

DOOR THRESHOLD FLASHING DETAIL

25

N.T.S.

5/8" EXTERIOR GYPSUM SHEATHING PLYWOOD PER STRUCT. DWGS. METAL FASTENER

19

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF CHANNEL SCREED METAL FASTENER FRY REGLET CHANNEL SCREED (3/4" U.N.O. IN ELEVATIONS) CONTRACTOR TO PROVIDE T-INTERSECTIONS, CROSS INTERSECTIONS & OUTSIDE/INSIDE CORNER SECTIONS AS REQUIRED.

3/4"

7/8" CEMENT PLASTER OVER 3.4 LB METAL LATH OVER 2 LAYERS OF TYPE D PAPER FIRE RATING

GUARDRAIL AT ROOF DETAIL, TYP

N.T.S.

14

FIRE RATING

CEMENT PLASTER CONTROL JOINT, TYP.

N.T.S.

2x WOOD FRAMING PER STRUC.

PLYWOOD SHEAR WHERE OCCURS (SEE STRUCTURAL 1/2" PLY. AT ALL METAL PANELS, TYP.) 5/8" EXTERIOR GYP. BOARD AT ALL METAL PANELS, TYP.

OUTSIDE CORNER FLASHING TO MATCH COLOR AND GAUGE OF CORRUGATED METAL PANELS

1"

LAP SELF-ADHERING

8" MIN.

N.T.S.

18

J-METAL 5/8" STUCCO OVER BUILDING PAPER TO BE FLUSH WITH 7/8" CEMENT PLASTER

EXTERIOR

GYP BOARD 3/8"

METAL FASTENER

J-METAL CAULKING AND BACKER ROD 12" CONCRETE SHEAR WALL PER STRUCTURAL MTL. STUD WALL PER STRUCTURAL INSULATION

8" CMU WALL PER STRUCTURAL

2 COAT CEM. PLASTER OVER 3.4 LB MTL. LATH TYP. CMU WALL

PAINTED 24 GA. GALVANISED SHEET METAL COPING OVER FTR FLASHING PER MANUF. RECOMENDATIONS

MTL. WEEP SCREED

SELF ADHERED SHEET MEMBRANE OVER AND UNDER WEEP SCREED (PRIMER FIRST)

STUCCO OVER 3.4 LB METAL LATH OVER PAPER BACKING

JOINT SEALANT & BACKER ROD

9

7" STUCCO SCREED (WEEP SCREED)

24 GA. GSM L FLASHING SET IN BED OF CAULK

BED OF CAULK FIBER MESH BEAD OF CAULK

FIRE RATING

N.T.S.

20 GA. CONTINUOUS METAL CLEAT NAILED AT 24" O.C.

FIRE RATING

HORIZONTAL SOFFIT VENT/DRIP EDGE

WALL INSULATION PER TITLE 24 AND ACOUSTICAL SPECS

N.T.S.

3" MIN. WEEP

1/2" MIN.

FOOTING PER STRUCTURAL

3

FIRE RATING

FOUNDATION WEEP SCREED AT GRADE

N.T.S.

UPI POLYURETHANE PEDESTRIAN COATING LARR 25261 (INSTALL PER MANUF. SPECS)

PLYWOOD SHEAR PANEL WHERE OCCURS, SEE STRUCTURAL

5/8" EXTERIOR CEMENT PLASTER OVER 3.4 LB. METAL LATH AND BUILDING PAPER

7/8" STUCCO OVER BUILDING PAPER & WOVEN WIRE MESH

23

CONCRETE SUBSTRATE AT CMU WALL

FIRE RATING

N.T.S.

METAL PANEL

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF METAL FASCIA

3"

22ga METAL FASCIA 12" STEEL C-CHANNEL PAINTED TO MATCH COLOR PMS 2188

7/8" EXT. CEM. PLASTER OVER 3.4 LB. METAL LATH AND BUILDING PAPER (PRIME PLYWOOD FIRST) STUD WALL

BED OF APPROVED SEALANT, TYP.

FASTENER WITH SELFADHERED MEMBRANE COVERING HEAD OF FASTENER BEAD OF CAULK, TYP.

24 GA STUCCO SCREED

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF WEEP SCREED PEDESTAL SYSTEM (SEE. LANDS. DWGS.) - OVER 10 MM RUBBER PAD (ECORE QT OR APPROVED EQ) CUT MATTING TO APPROX. SIZE OF PEDESTAL, TYP.

BED OF CAULK

RIP JOIST

13

1/4" MAX. GAP

24 GA. GSM L FLASHING

IMPORTANT: CONSULT MANUFACTURER FOR ADDITIONAL INFORMATION REGARDING CONCRETE/MASONRY SUBSTRATES AND INSULATION INSTALLATION REQUIREMENTS

4" MIN FLASHING

CONCRETE

SEE DIAGRAM A BELOW

N.T.S.

SHEET TITLE

EXTERIOR DETAILS

TOP OF HARDSCAPE

WATERPROOFING MEMBRANE, SEE WATERPROOFING SPEC. FOLLOW MANUFACTURER'S INSTALLATION SPEC. ATTACH SHEET METAL FLASHING TO CONC. SLAB W/ EXPOXY GLUE OR EQUAL

FOOTING PER STRUCTURAL

2

FOUNDATION WEEP SCREED AT HARDSCAPE

FIRE RATING

N.T.S.

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

1/16"

PLYWOOD PER STRUCT. DWGS. 5/8" DENSGLASS

KEE ROOFING ADHERED TO CLAD MTL

1/8" RADIUS • T.C.J. TOOLED CONTROL JOINT

BED OF CAULK FIBER MESH BEAD OF CAULK

FIRE RATING

STUCCO WALL @ ELASTOMERIC DECK

CONC. SLAB, SEE SCHEDULE FOR FINISH

RIP JOIST UPI POLYURETHANE PEDESTRIAN COATING LARR 25261 (INSTALL PER MANUF. SPECS.)

1/2"

CONC. FLOOR

MTL. WEEP SCREED

BED OFOF APPROVED BED CAULK SEALANT, TYP.

20ga L CLIP

7/8" CEMENT PLASTER OVER 3.4 LB METAL LATH OVER BUILDING PAPER

24 ga MTL WEEP SCREED

5/8" EXTERIOR GYPSUM SHEATHING

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF METAL FLASHING 7" STUCCO SCREED (WEEP SCREED)

SELF-ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF Z-METAL FLASHING AND STUCCO STOP

2" MIN. @ CONC. DECK 4" MIN. @ GRADE

CLAD METAL

PLYWOOD SHEAR PANELING AT SHEAR WALLS

DRYWALL INTERIOR FINISH

BUILDING PAPER TO EXTEND OVER SELF-ADHERED MEMBRANE

SELF ADHERED FLASHING OVER AND UNDER LEADING EDGE OF WEEP SCREED

CONDITION THIS SIDE NOT SHOWN

BLKG 1/8"

7/8" CEMENT PLASTER OVER 3.4 LB METAL LATH OVER BUILDING PAPER

BUILDING PAPER ATTACH SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF SHEET METAL FLASHING AND STUCCO SCREED AS SHOWN A MINIMUM OF 6" 26 GA. SHEET METAL FLASHING (L-METAL)

FLASHING

N.T.S.

LINE OF STEEL TUBE BEYOND

METAL FRAMING INFILL, TYP.

WEEP SCREED

CMU PER PLANS

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF WEEP SCREED

4" MIN.

9" STRUCTURAL SEPARATION

WOOD NAILER

JOINT SEALANT & BACKEROD

BEAD OF APPROVED SEALANT AT END OF SELF ADHERED MEMBRANE, TYP.

FRY REGLET OR EQUAL SOFFIT VENT PCS-100-V-100 CONTINUOUS SOFFIT VENT

SELF-ADHERING MEMBRANE

IMPORTANT: CONSULT MANUFACTURER FOR ADDITIONAL INFORMATION REGARDING CONCRETE/MASONRY SUBSTRATES AND INSULATION INSTALLATION REQUIREMENTS

FIRE RATING

2"

1/2" METAL FURRING CHANNEL

MIN. 2" MIN.

FASTENER WITH SELFADHERED MEMBRANE COVERING HEAD OF FASTENER

1/4"

INTERIOR

VERCO 1.5" PLB DECK

METAL PANEL POWDER COATED WITH COLOR TO MATCH PMS 2188

2"

METAL FLASHING

2x_ WOOD FRAMED PARAPET WALL

6" MIN.

CONCRETE

4" MIN FLASHING

RIGID FOAM - SLOPED 2% MIN.

NEOPRENE GASKET

WATERSTOP

SELF-ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF Z-METAL FLASHING AND STUCCO STOP

5/8" EXTERIOR GYPSUM SHEATHING

P.T. SILL PLATE PER STRUCTURAL

3'-6" MIN.

SEALANT, TYP.

24ga. MTL. FLASHING SET IN BED OF CAULKING JOINT SEALANT & BACKEROD

BUILDING PAPER TO EXTEND OVER SELFADHERED MEMBRANE

FRY DRIP SCREED MODEL #DS-875

7/8" CEMENT PLASTER, OVER 3.4 LB. METAL LATH, OVER BUILDING PAPER SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF MTL. FLASHING

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

24ga MTL. FLASHING BED OF APPROVED SEALANT BED OF APPROVED SEALANT, TYP.

1/4"

N.T.S.

29

5/8" EXTERIOR CEMENT PLASTER OVER 3.4 LB. METAL LATH AND BUILDING PAPER

7/8"

7/8" EXTERIOR CEMENT PLASTER OVER 3.4 LB. METAL LATH AND BUILDING PAPER

8

N.T.S.

CONCRETE / CMU PER PLANS

PLYWOOD AT SHEARWALLS ONLY (SEE STRUCT. DWGS) SEE STRUCTURAL DWGS. FOR ROOF/FLOOR FRAMING

10"

FIRE RATING

4

FIRE RATING

WATERPROOF MEMBRANE AT CONCRETE DECK/WALL

WEEP SCREED

2"

1/4"-14 x 7/8" STITCH (1'-0" O.C.)

BED OF APPROVED SEALANT, TYP.

STUD WALL PER STRUCT. DWGS @ 16"O.C. U.N.O.

BED OFAPPROVED CAULK BED OF

18" CONCRETE SHEAR WALL PER STRUCTURAL

4" MIN. FLASHING

STUCCO TO GYP BOARD JOINT

VERIFY LOCATION w/ ARCH.

1/4" PER 12" MIN.

UPI POLYURETHANE PEDESTRIAN COATING LARR 25261 (INSTALL PER MANUF. SPECS.)

6" MIN. FLASHING

SINGLE BEAD TAPE SEALANT, TYP.

SLOPE TO DRAIN

CONC. FLOOR

METAL FASTENER

SLOPE 1/4" PER FT. OR 2%

SELF ADHERING MEMBRANE

5/8" TYPE 'X' GYPSUM BOARD

OUTSIDE CLOSURE

2" MIN. @ CONC. DECK 4" MIN. @ GRADE

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF J-METAL., TYP.

PLYWOOD SHEATHING (WHERE OCCURS, SEE STRUCT. DWGS.)

N.T.S.

2 LAYERS OF TYPE D PAPER

J-METAL BUTYL TAPE

24 GA. BONDERIZED SHEET METAL FLASHING FIBER MESH

CAULKING

#12-14 X 1-1/4" SD (1'-0" O.C.)

BED OF CAULK

2x_ BLOCKING PER STRUCT.

2 LAYERS TYPE 'X' GYPSUM BOARD 5/8" METAL FURRING CHANNEL

1' - 0 1/8"

24

UPI POLYURETHANE PEDESTRIAN COATING LARR 25261 (INSTALL PER MANUF. SPECS)

6"

CORRUGATED METAL PANELS OVER 30# FELT

7/8" CEMENT PLASTER OVER 3.4 LB METAL LATH AND BUILDING PAPER SELF-ADHERING MEMBRANE OVER AND UNDER J- METAL 5/8" EXTERIOR GYPSUM BOARD

N.T.S.

N.T.S.

24 GA STUCCO WEEP SCREED

2" MIN.

NOTE: ALL DETAILS SIM. FOR VERTICAL & HORIZONTAL APPLICATION.

31

FIRE RATING

DUCT FLASHIONG AT BUILT-UP ROOF, TYP

O

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF WEEP SCREED

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF METAL FLASHING

3"MIN.

N.T.S.

FIRE RATING

PLYWOOD DECK EDGE METAL DETAIL

2x RIP STRIP

CA L I F

CONC. OR CONC. BLOCK, SEE STRUCTURAL

5/8" EXTERIOR GYP. SHEATHING

IMPORTANT: CONSULT MANUFACTURER FOR ADDITIONAL INFORMATION REGARDING CONCRETE SUBSTRATES, CONSTRUCTION JOINTS, SHEET METAL INSTALLATION, AND CONCRETE/ MASONRY RELATED REQUIREMENTS

NOTE: DO URETHANE SEALANT LAST - LET CURE 24 HOURS PRIOR TO FOOT TRAFFIC

FIRE RATING

PLYWOODDECK

OF

J-METALS

BED OF APPROVED SEALANT

PARASEAL SYSTEM

WATERPROOFING @ ADJ SLAB ON GRADE

7/8" STUCCO FINISH OVER 3.4LB MTL. LATH & BLDG. PAPER

3'-6" GUARDRAIL MIN.

DECK SLAB

TPO SINGLE PLY ROOFING MEMBRANE PER MANUFACTURERS RECOMMENDATIONS

SEAL GUARD AT ALL PLYWOOD SEAMS

COMPACTED SUBGRADE

FRY REGLET DRIP SCREED SELF-ADHERING MEMBRANE OVER & UNDER FIRE RATING

SLAB ON GRADE

PARASEAL TERMINATION BAR

FRY REGLET DRIP SCREED

CORRUGATED PANEL STUCCO SOFFIT

EPOXY/SAND MIXTURE FEATHERED TO 0"

STUCCO CORNER MESH

1 2_"MIN. 2

24 GA. MTL FASTENERS

FIBER MESH

4" MIN.

PARASEAL MASTIC

APPLY SIMILAR TRANSITION DETAIL AT CEILING, TYP.

2x_ STUDS (SEE STRUCTURAL DWGS.)

LOPE

20 GA. CONTINOUS METAL CLEAT NAILED AT 24" O.C.

BEAD OF CAULK

2"

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF MTL. FLASHING

26 GA. BONDERIZED SHEET METAL FLASHING SET IN APPROVED EPOXY

2" MIN.

1/4" TO 3/8"

CAULKING, TYP.

2 X WOOD CURB

NAILS

UPI POLYURETHANE PEDESTRIAN COATING LARR 25261 (INSTALL PER MANUF. SPECS.) TOP COAT ONLY

8" MIN.FLASHING

PLYWOOD SHEATHING PER STRUCT. BUTYL TAPE

1/2" TO 3/4" MAX.

METAL COUNTERFLASHING SECURED USING EPDM WASHERED FASTENER @ 12 O.C. & BUTLY TAPE

URADEK LARR 25261

2" MIN.

5/8" DENSGLASS

UPI POLYURETHANE PEDESTRIAN COATING LARR 25261 (INSTALL PER MANUF. SPECS.) TOP COAT

2% MIN. S

ELASTOMERIC SEALANT

POURABLE SELF-LEVELING URETHANE SEALANT AT 2:1 WIDTH/DEPTH RATIO W/ BACKER ROD

3"

BUILDING PAPER OVER 1 LAYER OF TYVEK

3/9/2017 2:41:58 PM

2X STUDS 5/8" TYPE X G.W.B.

5/8" EXTERIOR GYPSUM SHEATHING

S.S. CLAMP

E

5/8" (2 COAT) STUCCO OVER CMU EXTERIOR OR CONC.

SHEET METAL DUCT

CORRUGATED METAL PANELS

5

WATERPROOF MEMBRANE WITH REINFORCING MESH OVER SHEET METAL FLASHING SET IN SEALANT

PLY. SHEATHING PER STRUCT.

1"

NOTE: ALL DETAILS SIM. FOR VERTICAL & HORIZONTAL APPLICATION.

33

N.T.S.

REN. 6-30-17

FIRE RATING

WATERPROOF MEMBRANE DECK/WALL

ALIGN

N.T.S.

FIRE RATING

10

SEALANT

6X BLK'G.

2 HR FLOOR TO BALCONY INTERSECTION, TYP

FIRE RATING

PLYWOOD AT SHEARWALLS ONLY (SEE STRUCT. DWGS)

4"

FIRE RATING

J-METAL

STUCCO TO GYP BOARD JOINT

NO. C-13779

2 LAYERS OF 5/8" EXT. GRADE PLYWOOD 24 GA. BONDERIZED SHEET METAL FLASHING BED OF APPROVED SEALANT, TYP.

FLASHING

INSULATION PER T-24

LAG SCREWS

BUTYL TAPE

METAL PANEL FASTNER DETAIL

N.T.S.

4" MIN.

WEEP SCREED DO NOT DAM DRIP EDGE WEEP HOLES

J-METAL

18" U.N.O. ON ROOF PLANS

NO FASTENERS ON HORIZONTAL SURFACE UNLESS COVERED BY W.P., TYP.

4" MIN.

2" 2"

FASTENER AS REC. BY MANUF.

15

NOTES: 1. SEE OTHER DRAWINGS FOR WALL ASSEMBLY 2. INSTALL SCREED OVER CONTINUOUS PAPER BACKING. 3. INTERRUPT LATH AND INSTALL OVER FLANGE OF SCREED. 4. WIRE-TIE CONTROL JOINT TO LATH. 5. SEAL ALL CONTROL JOINT INTERSECTIONS AND CONNECTIONS WITH SILICONE SEALANT.

"PRE MOLDED" FLASHING

VARIES

BLOCKING AS NEEDED

N.T.S.

FIRE RATING

RAMP TO PEDESTAL TRANSITION DETAIL

ED A RCH NS S EMP I A TA

MIN.

5/8" GYP. BOARD

FIRE RATING

FINISHES ON THIS SIDE NOT SHOWN

2x_ STUDS (SEE STRUCT. DWGS)

20" MAX.

5/8" DENSGLASS

METAL FASTENER

RIP JOIST

2" x 2" SQ. TUBE HORIZONTAL RAILS, TYP. SEE STRUCT 2" x 2" OR 3" x 3" SQ. TUBE PER STRUCT DWGS.

42" MIN.

(5) FRTW 2X BLOCKING

HEIGHT VARIES 1/2" MINIMUM

4" MIN.

7/8" STUCCO

METAL FASTENER

JOINT SEALANT & BACKER ROD

WALL END TO DECK EDGE TRANSITIONAL FLASHING, TYP

20

N.T.S.

GYP BOARD

3/8"

1

STUD WALL PER STRUCT. @ 16"O.C. U.N.O.

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF JMETAL, TYP.

SINGLE PLY ROOFING PER MANUF. REC. SELF ADHERED FLASHING MEMBRANE

WALL INSULATION PER TITLE 24

4" MIN.

2X RIPPED JOISTS TO DRAIN. PER STRUCT 2 LAYERS OF PLYWOOD PER STRUCT.

24 ga. METAL FLASHING

BLKG FRTW 2X SILL PLATE

STUCCO OVER 3.4 LB METAL LATH OVER PAPER BACKING

20 ga. EDGE METAL

5/8" GYPSUM EXT. SHEATHING

STAMP

N.T.S.

7/8" STUCCO OVER 3.4 LB. METAL LATH AND BUILDING PAPER. BUILDING PAPER LAPS OVER WEEP SCREED. SELF ADHERED FLASHING MEMBRANE OVER & UNDER LEADING EDGE OF MTL. FLASHING. - EXTEND BEYOND FLASHING (MIN. 2") SELF ADHERED FLASHING MEMBRANE OVER & UNDER LEADING EDGE OF WEEP SCREED BEAD OF CAULK FIBER MESH UPI POLYURETHANE PEDESTRIAN COATING LARR 25261 (INSTALL PER F.F. MANUF. SPECS.)

2 3/16"

URADEK

5/8" EXTERIOR GYPSUM SHEATHING

SHAPED 4 X

A901

WEEP SCREED

1/4" MAX. GAP

RIP JOIST

FRY REGLET DRIP SCREED

6

4" MIN.

EQ EQ

FASTNER AS REC. BY MANUF. BLOCKING AS NEEDED

CORRUGATED METAL PANEL CORNER DETAIL

6

PLYWOOD AT SHEARWALLS ONLY (SEE STRUCT.) PLYWOOD AT SHEARWALLS ONLY (SEE STRUCT. DWGS.)

PLY SHEATHING

METAL FASTENER

N.T.S.

MTL. PLATE LAP, TYP.

30

N.T.S.

55 STC PER CALIF. OFFICE OF NOISE CONTROL 1980 SECTION 2.3.2.1.1.1 MIN. 6" THICK FIRE RATING

STRUCTURAL CONCRETE FLOOR, TYP.

2"

SELF ADHERED FLASHING MEMBRANE WATERPROOFING IS TO BE INTERFACED WITH TRANSITIONAL FLASHING IN A WATERTIGHT SHINGLE FASHION

6"

SEALANT TAPE, TYP.

11

2x_ STUDS

BED OF CAULK UNDER & OVER MTL. FLASHING

24GA. WALL END TRANSITIONAL SHEET METAL FLASHING

SELF ADHERED FLASHING MEMBRANE- OVER AND UNDER DRIP SCREED LEADING EDGE

INTERIOR

BEAD OF CAULK O/ EDGE MTL. FIBER MESH

4"

2X SOLID BLKG.

FRY REGLET SOFFIT VENTS OR APPROVED EQ.

N.T.S.

MEMBRANE 6" MIN. OVER PARAPET WALL ON EITHER SIDE

SCISSOR LIFT DEPRESSION

EXTERIOR BALCONY

8" MIN.

8" MIN.

CONCRETE FLOOR (SEE STRUCT. DWGS.)

FIRE RATING

SCISSOR LIFT PIT EDGE

10"

7/8" CEMENT PLASTER OVER 3.4 LB METAL LATH OVER BUILDING PAPER

STRUCTURAL SLAB

1' - 4" 1' - 0"

STRUCTURAL SLAB

METAL FRAMING

BUTYL TAPE

32

16

PEDESTAL SYSTEM (SEE LANDS. DWGS) - OVER 10 MM RUBBER PAD (ECORE QT OR APPROVED EQ) CUT MATTING TO APPROX. SIZE OF PEDESTAL, TYP. URADEK SYSTEM BED OF CAULK

CURB ANGLE

NOTE: ALL DETAILS SIM. FOR VERTICAL & HORIZONTAL APPLICATION.

34

N.T.S.

STEEL PLATE

9"

1' - 0"

21

N.T.S.

FIRE RATING

SHAFT AT SEVENTH FLOOR KLUMP ROOF DECK

3"

STEP IN STRUCTURAL SLAB TO ACCOMMODATE SCISSOR LIFT

35

TYPICAL FENCE DETAIL

FIRE RATING

STC. AND TEST NO.

N/A 4 HR / 7" THICK 1. 6", 8", 10", 12", 14", 16", OR 18" VARIES SEE 3 HR / 6.2" THICK STRUCTURAL CONCRETE STRUCT. 2 HR / 5" THICK DECK IN TYPE I 1 HR / 3.5" THICK CONSTRUCTION, SEE STRUCTURAL DWGS. PER TABLE 7.21.1(2) SILICEOUS AGGREGATE CONCRETE

WOOD STUD TREMCO 250 GC WALL PER HIGH BUILD SYSTEM STRUCT. WITH DRAIN MAT FIBERGLASS MESH EMBEDDED IN MEMBRANE

TOPPING SLAB W.P DETAIL, TYP

FIRE RATING

T

1' - 4"

27

FIRE RATING

DOOR PAN FLASHING DETAIL,TYP

PLYWOOD SHEATHING

F.O.S. NOMINAL THICK. (INCHES)

ST A

3"

STEEL PLATE 3" x 3" x 1/4" CURB ANGLE, ALL JOINTS WELDED SECURELY. PROVIDE 3" STUDS AT 18" O.C., TYP. AT ALL ANGLES FUTURE MARKET FLOOR FINISH

N.T.S.

FIRE RATING

ACTUAL THICKNESS (INCHES)

COMPONENT DESCRIPTION

CT TE ERIS K

36

FIRE RATING

SECTION

5/8 EXT. GYP. SHEATHING

24 GA. GSM L-FLASHING

EDGE

NON-BEARING CMU - TOP OF WALL AT STRUCTURAL SLAB

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

STUCCO OVER 3.4 LB METAL LATH OVER PAPER BACKING

TREMCO 250 GC MEMBRANE

2 1/4" SQUARE POST

FIELD

DE Architects AIA

2 x BLOCKING

1/2"

5" DEPRESSION

STEEL ANGLE PER STRUCTURAL @ 4' - 0" O.C., TYP.

2' - 6"

STEEL ANGLE PER STRUCTURAL @ 4' - 0" O.C., TYP.

6' - 0"

1" GAP TYP.

FASTENERS 12 " MIN. ABOVE DECK

SELF-ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF J-METAL,TYP.

A

JOINT SEALANT FOAM BOARD

J-METAL

NI

4" MIN.

PROTECT FROM DAMAGE

INTEGRAL COLOR CONCRETE AT PODIUM TOPPING SLAB

R

PROTECT FROM DAMAGE

JOINT SEALANT

MTL. WEEP SCREED

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

6"

6" OR 8" OR 10" OR 12" STRUCTURAL DECK IN TYPE I CONSTRUCTION. SEE STRUCTURAL DWGS.

L IC E DONA

FIELD VERIFY

SLOPED CONCRETE CAP

8" MIN. FLASHING

ANCHOR TO WALL TYP.

SELF ADHERED FLASHING UNDER AND OVER WEEP SCREED LEADING EDGE (PRIMER FIRST)

24GA. SHEET METAL DOORPAN FLASHING

PER PLAN

2 LAYERS OF TYPE D PAPER 7/8" CEM. PLASTER OVER 3.4 LB MTL. LATH

SCREED

4 3/4" TYP.

SHEARWALL PER STRUCT. DWGS.

1" x 2 1/4" FLAT STEEL BAR

1/4" THICK x 12" WIDE PL @ 4' - 0" O.C. PER STRUCTURAL

LANKERSHIM + otsego

7" MIN.

CONCRETE SLAB PER STRUCTURAL

2"

2" TYP.

CONCRETE SLAB PER STRUCTURAL

SET MTL. FLASHING IN BED OF CAULKING

JOB NO. DATE

BEAM PER STRUCT.

• S.C.C.J. SAW CUT CONTROL JOINT

CONC. SLAB, SEE SCHEDULE FOR FINISH

DIAGRAM A NOT TO SCALE (REFERENCE ONLY)

4" MIN. (FLASHING)

BED OF APPROVED SEALANT, TYP.

NOTE: CEMENT PLASTER SHALL BE FLUSH WITH CONCRETE WALL. CONTRACTOR SHALL ADJUST FRAMING ACCORDINGLY.

SCALE

1501 03-03-2017 As indicated

SHEET NO.

28

METAL CANOPY DETAIL, TYP.

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

FIRE RATING

N.T.S.

22

CONCRETE SUBSTRATE AT WOOD STUD WALL DETAIL

FIRE RATING

N.T.S.

17

PEDESTAL / PARAPET WALL, TYP.

FIRE RATING

N.T.S.

12

CONCRETE CONTROL JOINTS

FIRE RATING

N.T.S.

7

WATERPROOF MEMBRANE AT CONCRETE DECK/WALL, TYP.

FIRE RATING

N.T.S.

1

CEMENT PLASTER / CONC. TRANSITION

FIRE RATING

N.T.S.

A902


CMU WALL PER STRUCT. CONCRETE DECK (PER STRCUTURAL DWGS.)

TYP.

UNFACED FIBERGLASS INSULARION PER T-24

30

SEISMIC SEPERATION

N.T.S.

23

BLOCK FRAME WINDOW DETAIL - SILL AT CONCRETE DECK

1 1/2" SQR. TUBE GUARDRAIL POST SLEEVE / 24 GA MTL. FLASHING

SELF ADHERED FLASHING MEMBRANE OVER & UNDER AS ILLUSTRATED

7/8" CEMENT PLASTER OVER 3.4 LB. METAL LATH AND BUILDING PAPER

N.T.S.

FILL VOID WITH INSULATION AS REQ. BY FIRE DEPT.

1/4" JOINT SEALANT & BACKROD 3"x4" STEEL ANGLE AT EDGE OF BALCONY ALIGH W/ EDGE OF DENSGLASS BELOW

MTL. DRIP EDGE FILL VOID WITH INSULATION AS REQ. BY FIRE DEPT. 7/8" CEMENT PLASTER OVER 3.4 LB. MTL. LATH OVER BUILDING PAPER

INSULATION T-24 2 LAYERS OF DENSGLASS

24 GA MTL. CLOSURE

FLUID APPLIED WATERPROOFING

FIRE RATING

BUILDING PAPER UNDER SELF ADHERED FLASHING MEMBRANE

SELF ADHERED MEMBRANE OVER & UNDER, TYP.

SOFFIT VENT

12

FIRE RATING

FURRED FRAMING DETAIL

N.T.S.

RUBBER PAD

6

STAMP

ED A RCH NS S EMP I A TA

FIRE RATING

FURRED FRAMING DETAIL -2

NO. C-13779

N.T.S.

ST A

N.T.S.

COLOR ETCHED TEMPERED GLASSTHICKNESS AS REC, BY MANUF

2 LAYERS OF DENS GLASS

24 GA MTL. FLASHING

1/2" PLYWOOD

METAL J-MOLD

BED OF CAULKING

CONTINUOUS SELF ADHERED FLASHING MEMBRANE OVER AND UNDER, TYP.

4 x 6 WOOD SILL

2 LAYERS 5/8" TYPE "X" GYP. BOARD

DIAGRAM A

STEEL PLATE PER STRUCT. DWGS SET IN BED CAULKING

4 x 4 STUD

BEAM PER STRUCTURAL

3/4" STEEL SHELF ANGLE

2 x 12 JOISTS

#30 FELT OVER 1 LAYER OF TYVEK

24 GA. METAL FLASHING 7/8" CEMENT PLASTER OVER 3.4 LB. METAL LATH AND BUILDING PAPER

18 GA PERFORATED MTL. 3/8" DIAMETER&9/16" SPACING BEYOND

6" METAL FRAMING

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF SOFFIT VENT

WOOD BASE TO FOLLOW EDEGE OF WALL AND FLOOR/STAIRS CONCRETE STAIR PER PLAN

WOOD NAILER

JOINT SEALANT & BACKROD

CONTINUOUS SELF ADHERED FLASHING MEMBRANE BEHIND STEEL PLATE

33

4/A804

N.T.S.

JOINT SEALANT & BACKEROD

20 GA.MTL.CLIP 24 GA.MTL. FLASHIG

CONTINUOUS SELF ADHERED FLASHING MEMBRANE UNDER METAL FLASHING 20 GA. METAL FASCIA 2 x 8 JOISTS

RSIC-1 CLIPS (SEE MANUFACTURER FOR INSTALLATION REQUIREMENTS AND ADDITIONAL INFO. NOT SHOWN)

BEAM PER STRUCTURAL 4 x 6 WOOD HEADER

5/8" TYPE "X" GYP. BOARD 4 x 6 WOOD HEADER 2 x 4 WOOD HEADER

20 GA. METAL CLIP

2 LAYERS 5/8" TYPE "X" GYP. BOARD

7/8" CEMENT PLASTER OVER 3.4 LB. METAL LATH AND BUILDING PAPER

J-MOLD

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER METAL FLASHING.

INTERIOR

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER J METAL AND FLASHING LEADING EDGES

EXTERIOR

SOFFIT VENT

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER J METAL AND FLASHING LEADING EDGES

MILGARD BLOCK FRAME WINDOW

STEEL PLATE PER STRUCT DWGS SET IN BED OF CAULKING FASTENER PRE DRILL&W/ FIRE CAULKING 7/8" CEMENT PLASTER OVER 3.4 LB.MTL.LATH OVER BUILDING PAPER

2 LAYERS OF PLYWOOD REF. STRUCT DWGS

24 GA. MTL. WEEP SCREED

BLOCKING PER STRUCT. DWGS

PAINT

SELF ADHERED FLASHING MEMBRANE OVER & UNDER J METAL LEADING EDGE

SLOPED ROOF FRAMING

24 GA MTL. FLASHING SEE DIAGRAM A 2x2 HOLLOW MTL. STEEL TUBE

JOINT SEALANT & BACKROD

J- METAL

ROOF DECK FRAMING 1/2"

PAINT

SHELF ANGLE BEYOND

JOINT SEALANT

21

FIRE RATING

BLOCK FRAME WINDOW DETAIL - HEADER

16

N.T.S.

FIRE RATING

# 28

N.T.S.

10

GLASS GUARDRAIL CONTINUOUS SELF ADHERED FLASHING MEMBRANE

DIAGRAM A 3"

22ga METAL FASCIA

NEOPRENE GASKET

12" STEEL C-CHANNEL PAINTED TO MATCH COLOR PMS 2188 12" STEEL C-CHANNEL LINE OF STEEL TUBE BEYOND

SET STEEL TUBE IN BED OF CAULKING METAL PANEL POWDER COATED WITH COLOR TO MATCH PMS 2188 1/2" METAL FURRING CHANNEL METAL FRAMING INFILL, TYP. NOTCH/CUT CMU WALL - FILL NOTCH WITH CAULKING CMU WALL

METAL LOUVER 20 GA MTL PANEL SOLID

20ga L CLIP

4" MIN.

FIRE RATING

N.T.S.

26

FIRE RATING

#30 LOUVER HEAD

N.T.S.

20

# 27.1

METAL COPING

FIRE RATING

FIRE RATING

CLAP MTL. FLASHING

#29

N.T.S.

24 GA CONTINUOUS MTL. FLASHING

WATER PROOFING MEMBRANE

9

FIRE RATING

BUILDING FOUNDATION DRAINAGE DETAIL

N.T.S.

#30 FELT OVER 1 LAYER OF TYVEK

8" CMU

7/8" CEMENT PLASTER OVER 3.4 LB MTL. LATH OVER BUILDING PAPER

STEEL PLATE PER STRUCT DWGS SET IN BED OF CAULKING

5/8" 2 COAT CEMENT PLATER OVER 3.4 LB MTL LATH OVER BUILDING PAPER

25

#31 LOUVER TRANSITION

FIRE RATING

N.T.S.

7/8" CEMENT PLASTER OVER 3.4 LB MTL. LATH OVER BUILDING PAPER

19

6" MTL FRAMING

3"

N.T.S.

FRY REGLET DRIP SCREED

7/8" CEMENT PLASTER OVER 3.4 MTL. LATH OVER 2 LAYERS OF TYPE D BUILDING PAPER SMOOTH TROWEL FINISH WEEP SCREED - SELF ADHEARED MEMBRANE OVER AND UNDER LEADING EDGE

DEA: IF THIS SHEET IS NOT 36"x 48". IT IS A REDUCED PRINT

27

BOX SOFFIT DETAIL

8

MTL. PANEL - CONCRETE TRANSITION DETAIL

SELF ADHERED FLASHING MEMBRANE OVER & UNDER LEADING EDGE OF DRIP EDGE

24

#32 LOUVER SILL

N.T.S.

RCP WATER CURTAIN PROTECTION OPENING

N.T.S.

5/8" PLYWOOD PLYWOOD PER STRUCT KEE ROOFING SYSTEM

INSULATION PER T-24

18

30 SIM. A907

SELF ADHERED FLASHING MEMBRANE OVER & UNDER LEADING EDGE OF DRIP SCREED

ROOF JOIST

TERMINATION BAR WITH CAULKING

BELOW GRADE PODIUM WATERPROOFING

PROVIDE BRACE

7/8" CEMENT PLASTER OVER 3.4 LB. MTL. LATH OVER BUILDING PAPER

PLYWOOD PER STRUCT. DWGS

TROWEL GRADE FLUID APPLIED W.P.

8 A902

THE ABOVE DRAWINGS, SPECIFICATIONS AND DESIGNS ARE THE PROPERTY OF DE ARCHITECTS, AIA. NO PART THEREOF SHALL BE COPIED OR USED WITH ANY OTHER WORK OTHER THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN DEVELOPED WITHOUT THE WRITTEN CONSENT OF DE ARCHITECTS, AIA. DE ARCHITECTS AIA, DON EMPAKERIS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.

JOB NO. DATE

FRY REGLET DRIP SCREED

FIRE RATING

N.T.S.

STRUCT. SLAB

13

24 GA. FLASHING

SOFFIT VENT SELF ADHERED FLASHING MEMBRANE OVER & UNDER LEADING EDGE OF SOFFIT VENT, TYP.

TOPPING SLAB EDGE AT PLANTER EDGE

REF. DETAIL 17/A902 FOR WATERPROOFING

FIRE RATING

3" = 1'-0"

7

ISSUE / REVISION PROGRESS SET PLAN CHECK #1 BID SET PERMIT SET

SECOND FLOOR

20 GA CONTINUOUS MTL. CLEAT

FLUID APPLIED WATERPROOFING

DATE 08-27-2016 09-22-2016 01-13-2017 03-03-2017

NOTES: 1. METAL FRAMING, TYP. 2. PROVIDE NEOPRENE GASKET AT DISSIMILAR METALS, TYPICAL THROUGHOUT

1/2"

JOINT SEALANT WITH BACKER ROD

DRAIN MAT

N.T.S.

N.T.S.

2

FIRE RATING

KEE ROOFING SYSTEM

RAW ANCHOR

FIRE RATING

FIRE RATING

20 GA GALVANIZED SHEET MTL. COPING

31"

FIRE RATING

PLAN VIEW

PAINT

5/8" DENSGLASS

FLUID APPLIED WATERPROOFING

N.T.S.

DRIP EDGE

PEDESTAL SYSTEM - OVER 10 MM RUBBER PAD (ECORE QT OR APPROVED EQ) CUT MATTING TO APPROX. SIZE OF PEDESTAL, TYP.

CMU PLANTER WALL

3'-0" MAX.

BETWEEN SPRINKLERS

RIP JOIST

20 GA MTL. CLIP

SELF ADHERED MEMBRANE OVER & UNDER LEADING EDGE OF SOFFIT VENT, TYP

31

N.T.S.

DRAIN MAT

DRIP EDGE

FIRE RATING

MTL. CANOPY DETAIL 2

6'-0" MAX.

EXTERIOR DETAILS

3"

22 GA GLAV. MTL. CANOPY PAINTED

FIRE RATING

3'-0" MAX.

PAINT

FASTENED & SOLDERED LAP SEAMS

20 GA MTL. FASCIA

SOFFIT VENT

CMU PLANTER PARAPET DETAIL

14

4" MTL. JOIST

TERMINATION BAR WITH CAULKING

MTL. LOUVER JOINT SEALANT

24 GA MTL. DRIP EDGE

3/9/2017 2:42:19 PM

4x4 HOLLOW STEEL TUBE PER STRUCT DWGS

SHEET TITLE

FASTENED & SOLDERED LAP SEAMS

22GA GALV. MTL. FASCIA PAINTED & SOLDERED LAP SEAM 20 GA MTL. CLIP SET IN BED OF CAULKING

A904

SPRINKLER HEAD

24 GA. MTL. WEEP FLASHING

Sim

3/4"

TOPPING SLAB

12"

1/2"

J METAL W/ WEEP HOLES

22 GA GLAV. MTL. CANOPY PAINTED

53"

SELF ADHERED MEMBRANE OVER & UNDER LEADING EDGE OF J METAL, TYP.

24 GA CONTINUOUS MTL. FLASHING

FIRE RATING

#27.2

CONCRETE PODIUM DECK PER STRUCT. DWGS.

6" MTL FRAMING

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF J METAL AND METAL DRIP EDGE

FIRE CAULKING FULLY EMBEDING SCREW HEADS SELF ADHERED FLASHING MEMBRANE OVER & UNDER LEADING EDGE OF METAL FLASHING

SEE 7/A911

MTL BRACING BEYOUND, REF,STRUCT DWGS

24 GA MTL. FLASHING SEE DIAGRAM A

MTL. FLASHING SET IN BED OF CAULKING

3

1' - 2"

SEE 2/A911 FOR PLANTER WP INFO

36"

4' - 6"

MTL. LOUVER

METAL PANEL

OPENING

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF DRIP EDGE TYP.

3/4"

FASTENER PER STRUCT DWGS PREDRILL&FILL HOLE W/ FIRE CAULKING

N.T.S.

MTL. PANEL

22 GA GALV. MTL. FASCIA PAINTED

2x2 HOLLOW STEEL TUBE

3

2 LAYERS DENSGLASS

20 GA MTL. PANEL SOLID

BIRD SCREEN

FIRE RATING

SECTION AT WATER CURTAIN

PLYWOOD PER STRUCT

2 LAYERS OF 5/8" GYP. BD.

4x4 HOLLOW STEEL TUBE PER STRUCT DWGS

DIAGRAM A

SPRINKLER HEAD

DRAIN MAT

INSULATION T-24

CLIP / CLOSURE EDGE FOR BIRD SCREEN

6" - 12"

FOLDED FILTER FABRIC OVER LEADING EDGE OF DRAIN MAT

SELF ADHERED FLASHING MEMBRANE OVER & UNDER LEADING EDGE OF LEADING EDGE OF J METALS TYP.

20 GA MTL. CLIP

15

BONDERIZED 24 GA. Z-METAL FLASHING CAULK TERMINATION BAR

SOFFIT VENT

JOINT SEALANT

N.T.S.

THIRD FLOOR

FASTENER

J METAL

METAL CANOPY DETAIL, TYP.

CAULK

7/8" CEMENT PLASTER OVER 3.4 LB.MTL.LATH OVER BUILDING PAPER

STEEL SPACER SET IN BED OF SELF ADHERED CAULKING FLASHING MEMBRANE SELF ADHERED OVER AND UNDER LEADING FLASHING EDGE OF METAL FLASHING MEMBRANE CUT TO SAME SIZE AS SPACER

7/8" CEMENT PLASTER OVER 3.4 LB.MTL.LATH OVER BUILDING PAPER

1 1/2" = 1'-0"

FASTENER

METAL PANEL 18 GA PERFORATED MTL.3/8" 24 GA MTL. FLASHING DIAMETER& SEE DIAGRAM A 9/16" SPACING

FASTENER PER STRUCT DWGS PREDRILL&FILL HOLE W/ FIRE CAULKING

4

MTL. WEEP SCREED

3/4" SHELF ANGLE

CONTINUOUS SELF ADHERED FLASHING MEMBRANE

N.T.S.

FIRE RATING

ROOF CURB FLASHING DETAIL

2 COAT STUCCO OVER 3.4 LB METAL LATH AND 2 LAYERS OF TYPE D BLDG PAPER

2x2 STEEL TUBE FRAME

STEEL PLATE PER STRUCT DWGS SET IN BED OF CAULKING

JOINT SEALANT

UPI POLYURETHANE PEDESTRIAN COATING LARR 25261 (INSTALL PER MANUF. SPECS)

20 GA MTL. FASCIA PAINTED

FIRE CAULKING FULLY EMBEDING SCREW HEADS

FIRE RATING

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF METAL FLASHING TYP.

24 GA MTL. FLASHING

SELF ADHERED FLASHING MEMBRANE, OVER AND UNDER LEADING EDGE OF METAL FASCIA WOOD NAILER

2"

DRIP EDGE

STUCCO PANEL - CONC. TRANSITION DETAIL

METAL PANEL

RIGID FOAM - SLOPED 2% MIN.

KEE ROOFING

24 ga. Z-MTL. FLASHING

N.T.S.

VERCO 1.5" PLB DECK

32

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF WEEP SCREED TYP.

5/8" DENSGLASS

JOINT SEALANT

FIRE RATING

24ga. MTL. FLASHING SET IN BED OF CAULKING

METAL BENT PLATE

3/4" SUPER W WAFFLE PADS (MASON INDUSTRIES INC.) FOLLOW MANUFACTURER'S INSTALLATION SPEC. SPACE 16 - 24" O.C., VERIFY W/ MANUFACTURER'S REC. FOR LOADS UNFACED FIBERGLASS INSULATION PER T-24

4x4 HOLLOW STEEL TUBE PER STRUCT. DWGS 20 GA MTL. CLIP

MTL. CANOPY DETAIL

2 x 6 STUD

Sim

A904

1/2" STEEL PLATE SET IN BED OF CAULKING - TO BE COMPATIBLE WITH SELF ADHERED FLASHING MEMBRANE

28

UPI POLYURETHANE PEDESTRIAN COATING LARR 25261 (INSTALL PER MANUF. SPECS)

DIAGRAM A PLYWOOD SUBFLOOR PER STRUCTURAL

24 GA.MTL. FLASHIG

SELF ADHERED FLASHING MEMBRANE OVER & BELOW, TYP.

FIRE RATING

5/8" PLYWOOD

2 LAYERS OF 5/8" DENSGLASS BEYOND-BETWEEN STEEL TUBE

22 GA GALV. MTL. CANOPY - PAINTED FASTENED & SOLDERED LAP SEAM

7/8" CEMENT PLASTER OVER EXTERIOR GYP. BD.

1/4" DRAINAGE MAT

3/4"

24 GA MTL. FLASHING

20 GA. CONTINUOUS MTL CLEAT

FLUID-APPLIED WATERPROOFING

4" MTL. JOIST 6"

PLYWOOD PER STRUCT

LANKERSHIM + otsego

CONCRETE SLAB

2 LAYERS OF 5/8" GYP. BD. 24 GA. METAL CLOSURE

14

1 1/2" = 1'-0"

6" - 12"

LINE OF WOOD BASE BEYOND

5

18"

FASTENERS PER STRUCT. OREDRILL & CAULK HOLE

3" = 1'-0"

24 GA MTL. FLASHING

3" CONCRETE TOPPING SLAB, SLOPED TO DRAIN

MTL. WEEP SCREED 20 GA MTL. COUNTER FLASHING FIRE CAULKING FULLY EMBEDING SCREW HEADS 22 GA GALV. MTL. CANOPY PAINTED FASTENED & SOLDERED LAP SEAM

11

6" - 12"

METAL STUD WALL

N.T.S.

FIRE RATING

PARAPET DUCTING FLASHING DETAIL

24 GA. MTL COPING

1/2" RUBBER SURFACING TILES

24 GA MTL. FLASHING TO WRAP AROUND STEEL TUBE, TYP.

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF METAL DRIP EDGE AND METAL FLASHING

BALCONY EDGE DETAIL

1/2"

5/8" TYPE 'X' GYP.BD

17

N.T.S.

UPI POLYURETHANE PEDESTRIAN COATING LARR 25261 (INSTALL PER MANUF. SPECS)

7/8" CEMENT PLASTER OVER 3.4 LB. MTL. LATH OVER BUILDING PAPER

2- LAYERS OF 5/8" TYPE 'X' GYP.BD

BLOCK FRAME WINDOW DETAIL - SILL

FIRE RATING

CONC. DECK / MTL. DRIP EDGE

30" MIN.

N.T.S.

22

FIRE RATING

MIN. CLR.

FACADE STEEL FRAMES

FIRE RATING

1' - 6"

N.T.S.

29

J-METAL 7/8" CEMENT PLASTER OVER 3.4LB METAL LATH

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER

3"

EXT. SOFFIT DETAIL

FIRE RATING

3/4"

34

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF METAL FLASHING TYP. JOINT SEALANT AND BACKER ROD

20 GA. METAL CLIP

EXTERIOR

SOFFIT VENT

FIRE RATING

BUILDING PAPER

4"

18 GA PERFORATED MTL. 3/8" DIAMETER&9/16" SPACING CAULK WHERE BUILDING PAPER MEETS MTL. FLASHING

SELF ADHERED FLASHING MEMBRANE OVER & UNDER

SOFFIT VENT

KEE ROOFING

2x2 HOLLOW STEEL TUBE PER STRUCT DWGS

FASTENER PER STRUCT DWGS -PREDRILL & FILL HOLE W/ FIRE CAULKING

DRIP EDGE

UNFACED FIBERGLASS INSULATION PER T-24

20 GA. CONTINUOUS METAL CLEAT NAILED @ 24" O.C.

METAL PANEL SYSTEM

MTL. PANEL BLOCKING PER SCTRUCT

O

NOT FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT

20 GA. METAL CAP

SELF ADHERED MEMBRANE

STEEL PLATE PER STRUCT DWGS 2 LAYERS OF GYP. BD

5/8" DENSGLASS

3/4" GYPCRETE

PLYWOOD SUBFLOOR PER STRUCTURAL

CONTINUOUS SELF ADHERED FLASHING MEMBRANE BEHING STEEL PLATE

CONC. DECK

20 GA. METAL ROOF / FASCIA SOLDERED LAP SEAM

SLOPE 2% MIN.

2 x 4 WOOD SILL

JOINT SEALANT &BACKROD

PEDESTRIAN WATERPROOF

CA L I F

MIN.

JOINT SEALANT

FIRE CAULKING FULLY EMBEDING SCREW HEADS

SELF ADHERED MEMBRANE OVER&UNDER, TYP.

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER, TYP.

1/2"

7/8" CEMENT PLASTER OVER 3.4 LB. MTLLATH OVER BUILDING PAPER

24 GA. Z-METAL FLASHING

EXTERIOR

8"

INTERIOR MILGARD BLOCK FRAME WINDOW

24 GA MTL. FLASHING SEE DIAGRAM A

2% 1.7% MIN.

OF

EPMD WASHERED FASTENER @12" O.C. AND BUTYL TAPE

SELF ADHERED FLASHING MEMBRANE OVER & UNDER AS ILLUSTRATED

4 3/8"

SELF ADHERED FLASHING MEMBRANE OVER AND UNDER LEADING EDGE OF METAL FLASHING

24 GA MTL WEEP SCREED

E

ELASTOMERIC SEALANT

1' - 6"

SELF ADHERED MEMBRANE OVER&UNDER

REN. 6-30-17

T

3"

NON-BEARING CMU WALL

FIRE RATING

3"

SELF ADHERED FLASHING MEMBRANE OVER & UNDER LEADING EDGES OF DRIP EDGE, TYP.

CT TE ERIS K

35

FIRE RATING

7/8" CEMENT PLASTER OVER 3.4 LB. MTL. LATH OVER BUILDING PAPER

1 1/2" SQUARE STEEL TUBE

20 GA. METAL CLIP

EXTERIOR

1/2" PLYWOOD

3"

3"

1535 6th Street Suite 101 Santa Monica, CA 90401 tel: 310.451.7917 fax: 310.451.7916 www.DEArchitects.net

5101 LANKERSHIM BLVD., NORTH HOLLYWOOD, CA 5130 KLUMP AVE, NORTH HOLLYWOOD, CA

2" 3" GAP

CONCRETE SLAB ON GRADE (PER STRCUTURAL DWGS.)

J- METAL

RIP JOIST FURRING SIXTH FLOOR 680.67'

A

CONCRETE FLOOR PER STRUCTURAL BED OF CAULKING

4" 3"

FIFTH FLOOR 670.42'

NI

TOPPING SLAB

ANCHORS PER MANUF. REC.

DE Architects AIA

2 LAYERS OF DENS GLASS

R

TOPPING SLAB

2-1/2" METAL FRAMING 20 GA. METAL ROOF / FASCIA SOLDERED LAP SEAM 5-1/2" METAL FRAMING 1/2" CLARK DIETRICH RC DELUX

2.1%

7/8" CEMENT PLASTER OVER 3.4 LB. MTL. LATH OVER BUILDING PAPER

FILL VOID WITH INSULATION AS REQ. BY FIRE DEPT.

2' - 0"

3-1/2"METAL FRAMING UNFACED FIBERGLASS INSULATION PER T-24

7/8" CEMENT PLASTER OVER 3.4 LB. MTL. LATH OVER BUILDING PAPER

2"

FIRE CAULKING

2 LAYERS 5/8" TYPE "X" GYP. BOARD

TREMCO 250GC HIGH BUILD WATERPROOFING MEMBRANE

1 1/2" x 1/2" STEEL PLATE

6"

TREMCO 250GC HIGH BUILD WATERPROOFING MEMBRANE

SLOPE 2% MIN.

CONTINUOUS SELFADHERING FLASHING MEMBRANE

12"

METAL J-MOLD

16GA L-METAL WITH HEMMED EDGE

CONTINUOUS SELF ADHERED FLASHING MEMBRANE

BED OF CAULKING

JOINT SEALANT

BALCO SYSTEM ES-200 INSTALLED PER MANUFACTURERS INSTRUCTIONS

16GA L-METAL WITH HEMMED EDGE

EXTERIOR

2 7/8"

URADECK W.P.

INTERIOR

1/2"

FLEXIBLE IMPACT RESISTANT POLYMER FLUSH WITH FINISHED SURFACE

BUILDING PAPER OVER SELF ADHERED FLASHING MEMBRANE

GUARDRAIL POST SLEEVE / 24 GA MTL. FLASHING

1' - 6"

CONCRETE SLAB, PER STRUCT.

SELF-ADHERING FLASHING MEMBRANE - OVER AND UNDER, METAL FLASHING

L IC E DONA

24 GA. Z-METAL FLASHING

MILGARD BLOCK FRAME WINDOW

PARAPET @ ROOF DECK DETAIL

FIRE RATING

N.T.S.

INTERIOR

7/8" EXTERIOR CEMENT PLASTER OVER 3.4 LB. METAL LATH AND BUILDING PAPER

1

SCALE

EXTERIOR SOFFIT VENT

CEILING OVER LOBBY #2 ENTRANCE

STUCCO SCREED FIRE RATING

N.T.S.

1501 03-03-2017 As indicated

SHEET NO.

A904