3 minute read

Portable Fire Extinguisher Training

One question that gets asked a lot is whether the Federal OSHA standards for portable fire extinguishers requires employees to perform “hands on” training with extinguishers. And the answer is not as simple as “yes” or “no”; a better answer would be, “it depends”.

First of all, the assumption is that unless you told them otherwise, it is reasonable to assume that any employee at your workplace could pick up a portable fire extinguisher hanging in their work area and try to use it to extinguish a fire should one start. Therefore, 1910.157(g) (1) states that “Where the employer has provided portable fire extinguishers for employee use in the workplace, the employer shall also provide an educational program to familiarize employees with the general principles of fire extinguisher use and the hazards involved with incipient stage fire-fighting.” The standard goes on to explain in paragraph (g)(2) that the “education” required in paragraph (g)(1) “must be provided to employees upon initial employment and at least annually thereafter.”

So, does “education” require hands-on training? If you refer to the definitions for Subpart L that appear in 1910.155, you will find that paragraph (c)(14) defines “Education” as “the process of imparting knowledge or skill through systematic instruction. It does not require formal classroom instruction.” In other words, at a minimum you must provide those workers with instructions on the general principles of fire extinguisher use and the hazards of incipient (early) stage fires, but no actual hands-on training is required by OSHA. Many employers handle this educational requirement by utilizing toolbox talks, safety videos, online fire extinguisher courses, and/or informational brochures on the required topics.

On the other hand, there are many employers who do designate some (or all) employees to use portable fire extinguishers. In fact, some OSHA standards, such as 1910.252(a)(2)(iii)(B) in the section for welding, cutting, and brazing (Subpart Q) mandate that a trained fire-watch be stationed nearby when hot work is being conducted. And that is where OSHA standard 1910.157(g)(2) for portable fire extinguishers comes into play. It states that “the employer shall provide employees who have been designated to use fire-fighting equipment as part of an emergency action plan with training in the use of the appropriate equipment.” And if we refer back to the OSHA definitions for Subpart F at 1910.155(c)(41), we see that in the context of this particular standard, “Training” means “the process of making proficient through instruction and hands-on practice in the operation of equipment, including respiratory protection equipment, that is expected to be used and in the performance of assigned duties.” Therefore, in addition to general instruction, hands-on

safety ENGINEERING SERVICES, INC

practice IS required for all employees who have been designated (or assigned) to use portable fire extinguishers.

At a minimum, trainees should get the opportunity to discharge the type(s) of portable extinguisher(s) they are designated to use as part of their training, but a live fire does not have to be part of the practice scenarios. Also, this is a good time to remind you that starting live fires under controlled conditions for practice can be very dangerous (and maybe even illegal in your area), so utilize trained professionals to conduct live fire drills after seeking and gaining approval from local authorities. There are many instances where local fire departments and portable fire extinguisher vendors provide this training to employees for free.

Employers also have one more option when it comes to portable fire extinguishers: If they write into their emergency action plan and fire prevention plan (covered in 1910.38 and 1910.39, respectively) that all (or certain) employees will immediately evacuate the building in case of a fire and that no one is to use an extinguisher (and train those employees about the plans), then neither education or training is required in portable fire extinguisher use for those employees. This assumes, of course, that there is no situation existing that specifically mandates someone trained in portable fire extinguisher use be available, such as in the welding standard previously mentioned.

So, to recap, employers who have portable fire extinguishers in the workplace must provide education on fire extinguishers for all workers, training for all designated workers, and nothing for any/all employees who have been specifically excluded in their emergency action plan from using fire extinguishers. And if you need one more thing to get your head spinning, just remember that the same requirements for hands-on training also apply to all employees who have been designated to use other fire-fighting equipment such as small fire hoses.

FULL SPECTRUM ENGINEERING AND SURVEYING SERVICES. 1155 13TH STREET SE • SALEM OREGON 97302 • 503-363-9227

The hexagonal grid used in honeycomb is the most efficient way to cover an area with minimal circumference or boundary.

Charles Darwin described it as a masterpiece of engineering, “absolutely perfect in economizing labor and wax.” The use of this shape reflects Hagan Hamilton’s ongoing commitment to proficiency and resourcefulness.

Much like a beehive, Hagan Hamilton is a humming, thriving community in which everyone plays a distinct role but is united in shared purpose. We are industrious, but also operate as a family — working toward something greater than ourselves.

Top Area Builders Months

This article is from: