LG HVAC SOLUTION
LG Electronics http://www.lg.com http://partner.lge.com Copyright © 2016 LG Electronics. All rights reserved.
Distributed by
LG
01
SOLUTION
MULTI V IV Development Philosophy LG’s primary goal is to ‘Vitalize every environment’ around the globe–from private residences to commercial buildings and communal spaces. To make this a reality, the company has developed a comprehensive range of innovative Heating, Ventilation and Air Conditioning (HVAC) products, as well as state-of-the-art energy solutions. One such product is the advanced MULTI V IV Variable Refrigerant Flow (VRF), which delivers incredible performance and energy efficiency through a number of proprietary LG technologies. VRF solutions are widely considered to be among the most versatile and powerful system air conditioners available. Providing exceptional comfort, energy efficiency and reliability, they are highly regarded by building managers, business operators and HVAC engineers. VRF solutions boast a number of other tangible benefits including cost effectiveness and easier installation. Thanks to significant advancements in HVAC technology, VRF systems are now able to offer unmatched performance capabilities along with reduced energy consumption. Nevertheless, LG continues to focus on removing all causes of ‘hidden loss,’ thereby further improving operational efficiency and passing on considerable energy savings to the consumer. Through close observation, testing, analysis and extensive R&D, LG has been able to drastically cut energy loss. The results of this endeavor can clearly be seen in the company’s finest achievement to date, MULTI V IV. Going ‘Beyond Your Standard,’ the ground breaking HVAC system possesses all of the strengths and none of the weaknesses in VRF system. One of LG’s firmly held beliefs is that in order to be the very best, one must offer the very best. Equipped with world’s first technologies and offering unrivalled performance, MULTI V IV can rightly be called ‘the very best’ VRF system in the market.
02
Revolution of MULTI V
2006
2008
2010
2013 LG Electronics participates in the Eurovent Certification Programme for Variable Refrigerant Flow (VRF); the certified models are listed in the Eurovent Directory.
Ø7.0 Corrugate Fuzzy Algorithm AC Inverter R410A
Heat Recovery Ø7.0 Wide louver Fuzzy Algorithm LGDC Inverter
High Pressure Oil Return Continuous Heating Vapor Injection
Active Refrigerant Control Variable Heat Exchanger Smart Load Control Smart Oil Control Vapor Injection (Advanced)
Check on-going validity of certificate : www.eurovent-certification.com
EUROPE SALES INFRASTRUCTURE
GLOBAL PRODUCTION SITE
Europe B2B Regional Head Office National Sales Office Air Conditioning Academy
Tianjin, China
European Distribution Center
Gebze, Turkey
Noida, India
Changwon & Jeonju, Korea Qingdao, China
Europe Energy Lab Riyadh, Saudi Arabia
Production Site
Haiphong, Vietnam Pune, India
Rayong, Thailand Manaus, Brazil
LG Electronics products sold in Europe are ‘Made in Korea’ (Except for ceiling suspended unit).
LG Energy Labs in Europe Committed to meet all requirements regarding energy efficiency and environmental demands, LG has been running Energy Lab. LG Energy Lab is an innovative site dedicated to commercial and residential products in heating, ventilation and the latest energy efficient air conditioning solutions. Also as a showcase, LG Energy Lab is equipped with complete monitoring and control systems. The performance of all products will be tracked and analyzed by a team of Research and Development engineers based in France, Finland and Korea, ensuring efficiency and reliability during the whole product lifecycle.
European Air Conditioning Distribution Center LG’s European Air Conditioning Distribution Center is located in Oosterhout, the Netherlands. Supplying and delivering products all over Europe, this distribution hub has contributed to smooth and rapid delivery, direct shipping for smaller orders and delivery tailored to air conditioners. The hub tries to manage inventory efficiency by taking advantage of LG EU’s established inventory pool.
TOTAL HVAC SOLUTION PROVIDER Ever since manufacturing Korea’s first home grown air conditioner in 1968, LG has remained at the forefront of air conditioning innovation. LG has been the world’s top selling manufacturer of residential air conditioning solutions. In 2008, LG achieved to sell the total of more than 100 million air conditioners. Building on its success and technological leadership in the residential air conditioning sector, LG has moved into system air conditioning as well.
The company produces top-notch air conditioning professionals at its academies, of which there are nearly 80 worldwide. These centers of excellence provide workshops and training programs that offer valuable hands-on experience. LG also provides useful tools for HVAC system engineers and installers, including its time saving LG Air Conditioner Technical Solution (LATS) software. Additionally, LG operates several state-of-the-art R&D facilities all across the planet.
The company’s range of high performance system air conditioning products provides effective temperature control to large-scale buildings and facilities. Overtime, LG has evolved into the total HVAC and energy solution provider, investing in new technologies adding chillers, VRF systems and BMS (building management system) into its comprehensive product portfolio. Along with a wide range of innovative solutions, LG delivers unrivalled customer service.
One such facility is the Energy Lab, a purpose-built R&D and testing center in northern France. Helping to keep the company ahead of the competition, the scientists and engineers at the Energy Lab study the effects of different environmental conditions on LG’s products. This in-depth research and analysis enables LG to tailor its solutions to the specific environmental demands of each individual market. Combining the best technologies with the best ideas, LG’s high quality products are now enjoyed by customers in over 100 countries.
INDEX OUTDOOR UNIT
INDOOR UNIT
MULTI V IV Heat Pump
12
Wall Mounted Unit
104
MULTI V IV Heat Recovery
34
Ceiling Mounted Cassette
112
MULTI V S
50
Ceiling Concealed Duct
120
MULTI V WATER IV
64
Fresh Air Intake Unit
128
90
Ceiling & Floor Convertible Unit 130 Ceiling Suspended Unit
(Heat Pump / Heat Recovery)
MULTI V WATER S
ACCESSORIES
HOT WATER SOLUTION
Console
134
Floor Standing Unit
136
MULTI V Indoor Compatibility
138
Hydro Kit
142
VENTILATION SOLUTION Energy Recovery Ventilator
150
Energy Recovery Ventilator with DX Coil
158
Individual Control
162
Centralized Control
170
Mechanical Accessories
208
Piping Accessories
222
Compatibility Table
234
LG
Solution
8
9
OUTDOOR UNIT 12 MULTI V IV Heat Pump 34 MULTI V IV Heat Recovery 50 MULTI V S
64 MULTI V WATER IV (Heat Pump / Heat Recovery) 90 MULTI V WATER S
MULTI V series offers outstanding energy savings, easy installation and connection to many different types of indoor units, making it easy to design.
LG
Solution
10
11
OUTDOOR UNIT
OUTDOOR UNIT LINE-UP Unit : HP
Type
Features
Appearance
4
5
6
8 10 12 14 16 18 20
22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80
• Energy saving product MULTI V IV • Flexible installation Heat Pump • For large space and high rise building - Office, Commercial, School etc.
• Cooling and heating at the same time • Energy saving by heat recovery MULTI V IV technology Heat • Flexible installation with heat recovery Recovery unit • For individual control building - Office, Hotel, Commercial etc.
MULTI V S
• Saves floor space • Flexible design applications - Slim, light and wide line up (4 ~ 12HP) - Combination of indoor unit (Up to 20 Units) • For Small / Medium building with up to 20 rooms
• High efficiency system regardless external conditions MULTI V • Indoor installation product WATER IV Heat Pump • Quiet unit noise level (No fans) • For Water sourced system, High rise building and Aesthetic building
MULTI V WATER IV Heat Recovery
• Cooling and heating at the same time • Minimizing energy cost by water sourced heat recovery system • For individual control building • For Water sourced system, High rise building and Aesthetic building
MULTI V WATER S
• Easy to install additional capacity • Compact size • Light weight • For Residential and Commercial building 380V, 3Ø
220V, 1Ø
12
Solution
LG
13
OUTDOOR UNIT
MULTI V IV
OUTDOOR UNIT
EFFICIENCY
Heat Pump Longest piping length
LG’s 4th Generation Inverter Compressor
1,000m Total piping length
The new High-Side Shell (HSS) scroll inverter compressor and BLDC concentration motor coil optimizes part load efficiency, with 50% reduction in weight and increase in high-frequency operation of 120Hz to 150Hz.
1. Light Weight 280kg Height between ODU ~ IDU
40m
Height between IDU ~ IDU
MULTI V IV
Vapor Injection
Company B
- Maximize heating capacity via two-stage compression - Provide powerful heating in low temperature conditions - Improve energy efficiency and heating performance
* 20HP Continuous heating model comparison
Extended Compressor Speed 150Hz
2. Piping Capabilities Total Piping Length
1,000m
Actual longest piping length (Equivalent)
200m (225m)
Longest piping length after 1st branch (Conditional application)
40m (90m)
Height between ODU ~ IDU
110m
Height between IDU ~ IDU
40m
Height between ODU ~ ODU
5m
3. Operation Range • Heating : -25 ~ 18oC WB • Cooling : -10 ~ 43oC DB
- Rapid operation response - Capable of reaching required temperature quickly - Increase part load efficiency Operation Range (Hz)
110m
398kg
160 150 120 60
20 15
Constant
LG 3rd Generation
LG 4th Generation
* Operation available up to 160Hz depending on operating conditions
Benefit LG VRF MULTI V IV heat pump systems provide heating or cooling to individual zones. The benefits of VRF heat pump zoning are to provide an individual level of control ensuring the tenant’s comfort in their individual space. The owner saves on boiler size reduction.
Application • Office / Factory • Education facility • Commercial building (Shopping mall / Department store / Large scale retail / Super market)
HiPORTM (High Pressure Oil Return) - Resolve compressor efficiency loss caused by oil return - Improve part load efficiency at all operation ranges
Smart Oil Return - Oil level detection in real time - Oil recovery occurs only when required - Enhance user comfort
Heat Pump
225m*
14
Solution
LG
15
Vapor Injection
EER (Cooling)
COP (Heating) COP
Vapor Injection uses a two-stage compression effect, which is designed to provide efficient heating in extremely cold environments. Combined with HiPORTM, this system boosts heating performance and enhances heating temperature range.
19%
17%
4.00
Variable Heat Exchanger Circuit
4.34
Cycle Control Tech
Low-pressure Gas
All Inverter Compressor Active Refrigerant Control HiPOR™ + Vapor Injection
Up to -25oC
MULTI V IV Conventional
27%
Smart Oil Return Heat Exchanger Expansion
MULTI V IV
Previous Model
* Comparison Based on 10HP in cooling mode
Mid-pressure Gas (Vapor Injection Port)
MULTI V IV
* Comparison Based on 10HP in heating mode
-25
Variable Heat Exchanger Circuit Variable Heat Exchanger Circuit is the world first technology which intelligently selects the optimal path for both heating and cooling.
MULTI V IV
Conventional
Variable Heat Exchanger Circuit adjusts the path number to match temperatures and operation modes, thereby contributing to an increase in energy efficiency
The number and direction of path are fixed independent of temperature and operation mode. A fixed path limits efficiency
-20
-15
-10
-5
0
7 11 15 Outdoor Temp. (°C)
HiPOR™ (High Pressure Oil Return) HiPORTM technology enables oil to return directly into the compressor, instead of returning through the refrigerant suction pipe, to minimize energy losses.
MULTI V IV
Conventional
Maximizing reliability and efficiency of the compressor by reducing high pressure refrigerant loss Oil Separator
Efficiency Comparison
Loss of low pressure refrigerant to the extent of the oil volume returned by the refrigerant pipe
Efficiency
8% 2% 3% 1% 2% 1% 1%
Heating Performance
5.16 4.68
Previous Model
- Improved heating performance by 27% - Minimum operating temperature lowered to -25°C
High-pressure Gas
6% 15%
Oil Separator
6% 6%
23%
6%
33% Cooling
Heating
Maximizing Efficiency for All Operations
Compromising Efficiency for Each Operation Efficiency
Heating
Efficiency
Cooling
Heating
No loss in suction gas
Heating
15 Compressor
Cooling
1
2
3
4
Path Number
Cooling
1
2
3
4
Path Number
HiPORTM
Compressor
20
Conventional
30
60
90
MULTI V IV
* Rating condition (Tc=54.4°C, Te=7.2°C)
120 150 (Hz)
Heat Pump
World’s First Class, Rated Efficiency (Eurovent Test Condition) EER
OUTDOOR UNIT
EFFICIENCY
LG
16
Solution
17
PERFORMANCE Always ahead of the competition and on the leading edge of innovation with powerful heating and unsurpassed cooling performance
MULTI V IV extended range of continuous cooling and heating operation through enhanced inverter compressor and control technology.
Benefits : - Energy efficiency increased by 3-step Smart Load Control during start-up phase - Discharge air temperature adjusted according to outdoor and indoor temperature - Comfort level in cooling / heating operations ensured During Start up
Weather Dependent
Outdoor Temperature
Indoor Discharge Air Temperature
Changed by Indoor Temperature
Cooling
Heating Outdoor Temp. (°C WB)
Smart Load Control function allows MULTI V IV to sense outdoor and indoor temperature and changes indoor discharge air temperature accordingly. This optimizes energy efficiency and maximizes indoor comfort level in cooling / heating modes.
Outdoor Temp. (°C DB)
Wide Operation Range
43°C
Previous Model
-5°C
18°C 15°C
MULTI V IV
Previous Model
-20°C MULTI V IV
-10°C Power Input
Smooth (Level1) Quick (Level 2) Power (Level 3)
SLC Contol Basic Operation (Default Setting)
SLC Start up Operation
Time
MULTI V IV
Conventional Regardless of operation mode, fixed amount of refrigerant is provided to the compressor, which limits optimal efficiency of each modes
Maximizing efficiency for all operations
Compromising efficiency for each operation
Heating Efficiency
15°C
20°C
27°C Indoor Air Temp. (°C DB)
Cooling Efficiency Fixed
Refrigerant Quantity (kg)
• Optimal low pressure by using part load surface of the heat exchanger • Cooling operation range expanded to -10°C
Conventional • Only allowed to use entire surface of heat exchanger which result into extremely low pressure • Cooling operation range limited to -5°C and above
43°C
Conventional
-5°C Accumulator
Efficiency Accumulator
Active Refrigerant Refrigerant Control Quantity (kg)
Part load Efficiency
Receiver
Efficiency
Active Refrigerant Control automatically monitors and adjusts the volume of circulating refrigerant during each cycle. This precise, fivestep control leads to an improvement in energy efficiency
Cooling Efficiency
10°C
Cooling Operation Range Down to -10°C MULTI V IV
Active Refrigerant Control automatically controls the level of refrigerant amount to maximize efficiency.
Heating Efficiency 3%
-25°C
LG has expanded the temperature range for continuous cooling from -5°C to -10°C to provide a better solution for zones that require four seasons cooling such as server rooms.
Active Refrigerant Control
Part load Efficiency 10%
27°C Indoor Air Temp. (°C WB)
Outdoor Temp. (°C DB)
Up to 30% Energy Saving
10°C 14°C
Continuous cooling operation range expansion
-10°C 14°C
27°C Indoor Air Temp. (°C WB)
Heat Pump
Smart Load Control
OUTDOOR UNIT
EFFICIENCY
Solution
LG
18
19
OUTDOOR UNIT
PERFORMANCE Always ahead of the competition and on the leading edge of innovation with powerful heating and unsurpassed cooling performance
Fast Heating and Cooling via Advanced Inverter
Compressor reliability is improved with an oil sensor that allows oil balancing and oil return. The value of the capacitance between the electrodes can measure the presence of oil in real-time.
In conventional models, inverter compressor and on/off compressor operate one by one, which takes far longer to reach maximum capacity. Thanks to LG’s all inverter compressor system and high performance cycle design, MULTI V IV delivers fast cooling or heating by operating two compressors simultaneously.
Smart Oil Return
Auto Oil Balancing
MULTI V IV
Conventional Heating Performance
Heating Performance
MULTI V IV Oil recovery operation only if necessary
0
Operation Time
Operation Time
40°C
2nd Stage A : Speed B : Speed
3rd Stage A : Full Speed B : Full Speed
1st Stage A : Start B : Off
4min.
20°C Time
Indoor Unit Discharge Air Temp. (°C DB)
Oil Sensor
Indoor Unit Discharge Air Temp. (°C DB)
Oil Sensor
1st Stage A : Start B : Start
Conventional
2nd Stage A : Speed B : Off
3rd Stage A : Speed B : On
4th Stage A : Speed B : On
40°C 11min.
20°C
* Condition : Standard heating mode (Ambient air temp.7°C, Indoor temp.20°C)
Continuous Heating Operation in Defrost
Comfort Cooling
MULTI V IV uses the split-defrost technology for continuous heating operation, which provides consistent heating for the indoor environment to improve both heating capacity and indoor comfort.
Without operation stop, this function is able to maintain operation at mild cooling mode around the set temperature. You can experience more comfortable indoor environment and energy saving.
MULTI V IV
ON
ON
Part load Defrosting
ON
ON
Heating stops during defrosting operation.
Continuous Heating
ON
ON
Operation Time
Heating
Heating Performance
Heating Performance
Heating
Comfort Cooling
Conventional
Continuous heating during part load defrosting operation.
• Indoor Unit Target superheat increased • Refrigerant flow rate decreased - Thermo-on Time increased (47min. More than 120min.) - No repeat thermo On / Off. - Average electric power 2% saving
Indoor Temp. Paused Heating
Defrosting
Conventional
Setting Temp. ON
* Continuous heating operation can be switched to existing defrost mode depending on environmental conditions.
OFF
ON
OFF
5th Stage A : Full Speed B : On
ON
OFF
Operation Time
Time
Time
Heat Pump
Smart Oil Management
Solution
LG
20
21
OUTDOOR UNIT
CONVENIENCE Self-diagnostic maintenance solution, offering smart and reliable functionality
Upgraded FDD (Fault Detection & Diagnosis)
Mobile LGMV helps users to monitor the MULTI V IV system cycle using Wi-Fi MV Module. Technicians can check LGMV data 10m away from MULTI V IV outdoor with smartphone.
Newly upgraded FDD elements provide the optimal solution for user reliability and easy maintenance.
Heat Pump
Smartphone Monitoring & Control
New Refrigerant Quantity Decision Feature
Wi-Fi MV Module
Wi-Fi
Install / SVC Engineer
FDD MICOM
Mobile LGMV
Connection type : Wi-Fi / To use Mobile LGMV Application, exclusive Wi-Fi MV Module is required
Smart Phone Specification App. Name OS
Recommended Specification
iOS (iPad Only) AppiOS 8.0 / 8.1 Mobile LGMV Android
Resolution
Wireless Communication Effective Distancd
2,048 x 1,536 (Optimization), 1,024 x 768
• Effective distance : 10m (Open Area) • The effective distance may be reduced by the communication environment
Android 4.4 480 x 800, 720 x 1,280, (Android 3.x, Honeycomb not Supported) 768 x 1,280, 768 x 1,024, 1,080 x 1,920
• Start up time reduction (60min 45min) • Available to use LGMV (LG Monitoring View) through a smartphone • Piping & Wiring error check-up • Auto start-up mode / report • Black box function • Simultaneous diagnosis • Auto refrigerant quantity evaluation and charge • Heating and cooling refrigerant quantity decision
Indoor Air Temp. (°C)
LG MULTI V IV is the first VRF that has a Heating and Cooling mode start up function which permits whole year start up as well as refrigerant quantity evaluation
33 ❷
27 ❸ ❶
18
Cooling Mode
10
Heating Mode
-10
0
24
43 Outdoor Temp. (°C)
❶ Refrigerant quantity evaluation during heating operation ❷ Refrigerant quantity evaluation during cooling operation ❸ Refrigerant quantity evaluation during cooling and heating operation
Auto Dust Removal
Auto Refrigerant Collection
MULTI V IV can remove dust (Sand, leaves, and etc.) in heat exchanger of outdoor unit by outdoor unit setting. Auto Dust Removal function improves the heat exchange efficiency to maintain clean state in heat exchanger of outdoor unit.
In case of an indoor or outdoor unit replacement for service, refrigerant from the malfunctioning unit is transferred to the outdoor unit by pumping down or to an indoor unit by pumping out for easy service.
Auto Dust Removal
Conventional
• Dust is removed in heat exchanger of outdoor unit by reverse rotation of fan • 5min. operation in every 2hour
Pump Down
Pump Out Refrigerant Flow
Dust remains in heat exchanger of outdoor unit
Refrigerant Flow
Fail Fail
Stops for a long time
Auto dust removal
Normal operation
Stops for a long time
Normal operation
LG
22
Solution
23
ARUN140LTE4 / ARUN160LTE4 ARUN180LTE4 / ARUN200LTE4
OUTDOOR UNIT
ARUN080LTE4 / ARUN100LTE4 / ARUN120LTE4
Heat Pump
HP Model Capacity
8
10
12
Combination Unit
ARUN080LTE4
ARUN100LTE4
ARUN120LTE4
Independent Unit
ARUN080LTE4
ARUN100LTE4
ARUN120LTE4
Cooling
Nom
kW
22.4
28.0
33.6
Heating
Nom
kW
25.2
31.5
37.8
HP Model Capacity
Cooling
Nom
kW
4.64
5.98
7.58
Heating
Nom
kW
4.74
6.10
8.51
EER 1)
Cooling
Nom
4.83
4.68
4.43
COP 1)
Heating
Nom
5.32
5.16
4.44
Cooling
Nom
kW
4.38
5.38
6.85
Heating
Nom
kW
4.58
5.49
7.80
EER 2)
Cooling
Nom
5.11
5.20
4.91
EER 2)
COP 2)
Heating
Nom
5.50
5.74
4.85
COP 2)
Nom
7.90
7.54
7.48
ESEER 3)
Power Input 1)
Power Input 2)
ESEER 3) Operation Range Compressor
Cooling
Min ~ Max °C DB
-10°C ~ 43°C
-10°C ~ 43°C
-10°C ~ 43°C
Heating
Min ~ Max °C WB
-25°C ~ 18°C
-25°C ~ 18°C
-25°C ~ 18°C
Hermetically Sealed Scroll
Hermetically Sealed Scroll
Hermetically Sealed Scroll
1
1
1
Propeller fan
Propeller fan
Propeller fan
DC Inverter motor
DC Inverter motor
DC Inverter motor
8mmAq (80Pa)
8mmAq (80Pa)
8mmAq (80Pa)
Type Number of Compressor Type
Fan
Motor Type Max Static Pressure
Airflow Rate Sound Pressure Sound Power
Refrigerant Refrigerant Oil
Piping Length
Piping Level Difference Piping Connection
Nom
4.47
4.11
4.61
4.37
Heating
Nom
4.79
4.42
4.54
4.25
Cooling
Nom
kW
8.48
10.42
9.85
11.54
Heating
Nom
kW
9.60
11.40
11.25
13.36
Cooling
Nom
4.62
4.30
5.12
4.85
Heating
Nom
4.59
4.42
5.04
4.72
Nom
7.37
7.27
7.17
6.78
-10°C ~ 43°C
-10°C ~ 43°C
-10°C ~ 43°C
-10°C ~ 43°C
Power Input 2)
Operation Range Compressor
Fan
Nom
dBA
78.0
78.0
79.0
Heating
Nom
dBA
78.0
78.0
79.0
(920 × 1,680 × 760) × 1
(920 × 1,680 × 760) × 1
(920 × 1,680 × 760) × 1
Dimensions
202 × 1
208 x 1
208 × 1
Net Weight
R410A
R410A
R410A
7.5
7.5
7.5
FVC68D (PVE)
FVC68D (PVE)
FVC68D (PVE)
3,200
3,400
3,400
Ø / V / Hz
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
No. x mm²
2C × 1.0~1.5 1,000
Actual Longest Piping Length 4) Max
m
200 (225)
200 (225)
200 (225)
After 1st Y Branch 5)
Max
m
40 (90)
40 (90)
40 (90)
IDU - ODU
Max
m
110
110
110
IDU - IDU
Max
m
40
40
40
Min ~ Max °C DB
Heating
Min ~ Max °C WB
Type Number of Compressor Motor Type Max Static Pressure
Cooling
1,000
Cooling
Type
59.0
2C × 1.0~1.5
63.0
Cooling
59.0
1,000
56.7
COP 1)
58.5
2C × 1.0~1.5
50.0
EER 1)
dBA
m
44.1
12.81
Nom
Max
kW
14.82
Heating
Total
Nom
10.93
59.0
Transmission Cable (VCTF-SB)
56.0
Heating
12.49
59.0
Power Supply
50.4
10.90
58.5
cc
44.8
11.30
dBA
Control
39.2 8.77
Nom
Type
**ARUN180LTE4
kW
9.21
Cooling
kg
ARUN160LTE4
Nom
kW
210
Charge
Airflow Rate Sound Pressure Sound Power
Refrigerant Refrigerant Oil
DC Inverter motor
DC Inverter motor
DC Inverter motor
DC Inverter motor
8mmAq (80Pa)
8mmAq (80Pa)
8mmAq (80Pa)
8mmAq (80Pa) 290
dBA
59.0
59.0
59.5
59.5
Heating
Nom
dBA
59.0
59.0
59.5
59.5
Cooling
Nom
dBA
82.0
82.0
83.0
83.0
Heating
Nom
dBA
82.0
82.0
83.0
83.0
W x H x D mm kg Type Charge
kg
Type Control
cc
(1,240 × 1,680 × 760) × 1 (1,240 × 1,680 × 760) × 1 (1,240 × 1,680 × 760) × 1 (1,240 × 1,680 × 760) × 1 245 x 1
245 x 1
280 × 1
280× 1
R410A
R410A
R410A
R410A
10.5
10.5
10.5
10.5
FVC68D (PVE)
FVC68D (PVE)
FVC68D (PVE)
FVC68D (PVE)
3,400
3,400
4,400
4,400
Ø / V / Hz
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
No. x mm²
2C × 1.0~1.5
2C × 1.0~1.5
2C × 1.0~1.5
2C × 1.0~1.5
Max
m
1,000
1,000
1,000
1,000
Actual Longest Piping Length 4) Max
m
200 (225)
200 (225)
200 (225)
200 (225)
After 1st Y Branch 5)
Max
m
40 (90)
40 (90)
40 (90)
40 (90)
IDU - ODU
Max
m
110
110
110
110
IDU - IDU
Max
m
40
40
40
40
Gas
mm (inch)
19.05 (3/4)
22.2 (7/8)
28.58 (1-1/8)
1
1
1
Number of Outdoor Units
20
25
30
Number of Connectable Indoor Units
Max
50 ~ 200%
50 ~ 200%
50 ~ 200%
Ratio of the Connectable Indoor Units
Min ~ Max
* This product contains Fluorinated Greenhouse Gases. (R410A)
2 Propeller fan
Nom
12.7 (1/2)
Min ~ Max
2 Propeller fan
Cooling
9.52 (3/8)
Ratio of the Connectable Indoor Units
1 Propeller fan
290
9.52 (3/8)
Max
1 Propeller fan
290
mm (inch)
Number of Connectable Indoor Units
-25°C ~ 18°C Hermetically Sealed Scroll
290
Total
Piping Connection
-25°C ~ 18°C Hermetically Sealed Scroll
m3/min
Transmission Cable (VCTF-SB)
Piping Level Difference
-25°C ~ 18°C Hermetically Sealed Scroll
Max
Power Supply
Piping Length
-25°C ~ 18°C Hermetically Sealed Scroll
Cooling
Liquid
Number of Outdoor Units
**ARUN200LTE4
ARUN140LTE4
Cooling
kW
210
kg
20 **ARUN200LTE4
Nom
210
Type
18 **ARUN180LTE4
Nom
m3/min
Net Weight
16 ARUN160LTE4
Cooling
Max
W x H x D mm
Independent Unit
14 ARUN140LTE4
Heating
Power Input 1)
Cooling
Dimensions
Combination Unit
Liquid
mm (inch)
12.7 (1/2)
12.7 (1/2)
15.88 (5/8)
15.88 (5/8)
Gas
mm (inch)
28.58 (1-1/8)
28.58 (1-1/8)
28.58 (1-1/8)
28.58 (1-1/8)
1
1
1
1
35
40
45
50
50 ~ 200%
50 ~ 200%
50 ~ 200%
50 ~ 200%
* This product contains Fluorinated Greenhouse Gases. (R410A) ** ARUN180LTE4 / ARUN200LTE4 units are excluded from Eurovent certified capacity range
24
Solution
LG
25
ARUN260LTE4 / ARUN280LTE4 ARUN300LTE4 / ARUN320LTE4
OUTDOOR UNIT
ARUN220LTE4 / ARUN240LTE4
Heat Pump
HP Combination Unit Model
Capacity
Independent Unit
22
24
ARUN220LTE4
ARUN240LTE4
ARUN120LTE4
ARUN120LTE4
ARUN100LTE4
ARUN120LTE4
Cooling
Nom
kW
61.6
67.2
Heating
Nom
kW
69.3
75.6
HP Combination Unit Model
Capacity
4.45
4.24
4.54
4.39
4.62
4.43
4.43
4.32
Cooling
Nom
kW
15.33
17.27
16.70
18.39
Heating
Nom
kW
17.40
19.20
19.05
21.16
Cooling
Nom
4.75
4.54
5.03
4.87
Heating
Nom
4.71
4.59
4.96
4.76
Nom
7.43
7.38
7.33
7.13
-10°C ~ 43°C
-10°C ~ 43°C
-10°C ~ 43°C
-10°C ~ 43°C
Heating
Nom
kW
13.29
15.60
EER 2)
Cooling
Nom
5.04
4.91
EER 2)
COP 2)
Heating
Nom
5.21
4.85
COP 2)
Nom
7.51
7.48
ESEER 3)
Type Fan
Propeller fan
Propeller fan
DC Inverter motor
DC Inverter motor
8mmAq (80Pa)
8mmAq (80Pa)
3
Motor Type Max Static Pressure
Airflow Rate Sound Pressure Sound Power
Cooling
Max
m /min
210 x 2
210 x 2
Cooling
Nom
dBA
62.0
62.0
Heating
Nom
dBA
62.0
62.0
Cooling
Nom
dBA
81.5
82.0
Heating
Nom
dBA
Dimensions Net Weight Refrigerant Refrigerant Oil
Piping Length
Piping Level Difference Piping Connection
Airflow Rate Sound Pressure Sound Power
208 × 2
Net Weight
R410A
7.5 × 2
7.5 × 2
FVC68D (PVE)
FVC68D (PVE)
6,800
6,800
Ø / V / Hz
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
No. x mm²
2C × 1.0~1.5
2C × 1.0~1.5
m
1,000
1,000
Actual Longest Piping Length 4) Max
m
200 (225)
200 (225)
After 1st Y Branch 5)
Max
m
40 (90)
40 (90)
IDU - ODU
Max
m
110
110
IDU - IDU
Max
m
40
40
Min ~ Max °C DB
Heating
Min ~ Max °C WB
Type Number of Compressor Motor Type Max Static Pressure
R410A
Max
Total
Fan
208 × 2
cc
Cooling
Type
Dimensions
Type
Transmission Cable (VCTF-SB)
Compressor
82.0
kg
Power Supply
Operation Range
(920 × 1,680 × 760) × 2
kg
Control
Power Input 2)
81.5
Type Charge
Power Input 1)
(920 × 1,680 × 760) × 2
W x H x D mm
100.8
Nom
13.70
2
94.5
Nom
12.23
2
87.8
Heating
kW
Number of Compressor
81.9
Cooling
Nom
Compressor
kW
COP 1)
Cooling
Hermetically Sealed Scroll
Nom
EER 1)
4.44
Hermetically Sealed Scroll
89.6
Heating
20.39
4.74
Type
84.0
23.33
Nom
-25°C ~ 18°C
78.4
18.51
Heating
-25°C ~ 18°C
72.8
21.32
COP
Min ~ Max °C WB
kW
18.48
4.43
Heating
Nom
19.81
4.54
Operation Range
Refrigerant Refrigerant Oil
DC Inverter motor
DC Inverter motor
DC Inverter motor
DC Inverter motor
8mmAq (80Pa)
8mmAq (80Pa)
8mmAq (80Pa)
8mmAq (80Pa)
290 + 210
290 + 210
290 + 210
290 + 210
62.3
62.3
Heating
Nom
dBA
62.0
62.0
62.3
62.3
Cooling
Nom
dBA
83.8
83.8
84.5
84.5
Heating
Nom
dBA
kg
83.8 (1,240 × 1,680 × 760) × 1 + (920 × 1,680 × 760) × 1 245 × 1 + 208 × 1
83.8 (1,240 × 1,680 × 760) × 1 + (920 × 1,680 × 760) × 1 245 × 1 + 208 × 1
84.5 (1,240 × 1,680 × 760) × 1 + (920 × 1,680 × 760) × 1 280 × 1 + 208 × 1
84.5 (1,240 × 1,680 × 760) × 1 + (920 × 1,680 × 760) × 1 280 × 1 + 208 × 1
R410A
R410A
R410A
R410A
kg
10.5 + 7.5
10.5 + 7.5
10.5 + 7.5
10.5 + 7.5
FVC68D (PVE)
FVC68D (PVE)
FVC68D (PVE)
FVC68D (PVE)
6,800
6,800
7,800
7,800
Ø / V / Hz
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
No. x mm²
2C × 1.0~1.5
W x H x D mm Type Charge Type Control
cc
2C × 1.0~1.5
2C × 1.0~1.5
2C × 1.0~1.5
Max
m
1,000
1,000
1,000
1,000
Actual Longest Piping Length 4) Max
m
200 (225)
200 (225)
200 (225)
200 (225)
After 1st Y Branch 5)
Max
m
40 (90)
40 (90)
40 (90)
40 (90)
IDU - ODU
Max
m
110
110
110
110
IDU - IDU
Max
m
40
40
40
40
mm (inch)
28.58 (1-1/8)
34.9 (1-3/8)
2
2
Number of Outdoor Units
44
48
50 ~ 160%
50 ~ 160%
Number of Connectable Indoor Units Ratio of the Connectable Indoor Units
Min ~ Max
3 Propeller fan
62.0
Gas
Ratio of the Connectable Indoor Units
3 Propeller fan
62.0
15.88 (5/8)
* This product contains Fluorinated Greenhouse Gases. (R410A)
2 Propeller fan
dBA
15.88 (5/8)
Max
2 Propeller fan
Nom
mm (inch)
Number of Connectable Indoor Units
-25°C ~ 18°C Hermetically Sealed Scroll
Cooling
Total
Piping Connection
-25°C ~ 18°C Hermetically Sealed Scroll
m3/min
Transmission Cable (VCTF-SB)
Piping Level Difference
-25°C ~ 18°C Hermetically Sealed Scroll
Max
Power Supply
Piping Length
-25°C ~ 18°C Hermetically Sealed Scroll
Cooling
Liquid
Number of Outdoor Units
ARUN120LTE4
Cooling
16.35
Nom
-10°C ~ 43°C
ARUN200LTE4
ARUN120LTE4
17.72
Cooling
-10°C ~ 43°C
ARUN180LTE4
ARUN120LTE4
kW
EER 1)
Min ~ Max °C DB
ARUN160LTE4
ARUN120LTE4
kW
15.16 17.02
Cooling
ARUN140LTE4
Nom
13.56 14.61
ESEER 3)
32 ARUN320LTE4
Nom
kW kW
Power Input 2)
30 ARUN300LTE4
Cooling
Nom Nom
1)
28 ARUN280LTE4
Heating
Cooling Heating
Power Input 1)
Independent Unit
26 ARUN260LTE4
Liquid
mm (inch)
19.05 (3/4)
19.05 (3/4)
19.05 (3/4)
19.05 (3/4)
Gas
mm (inch)
34.9 (1-3/8)
34.9 (1-3/8)
34.9 (1-3/8)
34.9 (1-3/8)
2
2
2
2
52 50 ~ 160%
56 50 ~ 160%
60 50 ~ 160%
64 50 ~ 160%
* This product contains Fluorinated Greenhouse Gases. (R410A)
Max Min ~ Max
26
Solution
LG
27
ARUN380LTE4 / ARUN400LTE4
OUTDOOR UNIT
ARUN340LTE4 / ARUN360LTE4
Heat Pump
HP Combination Unit Model
Independent Unit
Capacity
34
36
ARUN340LTE4
ARUN360LTE4
ARUN200LTE4
ARUN200LTE4
ARUN140LTE4
ARUN160LTE4
Cooling
Nom
kW
95.2
100.8
Heating
Nom
kW
107.1
113.0
Cooling
Nom
kW
21.58
23.71
Heating
Nom
kW
24.03
26.12
EER 1)
Cooling
Nom
4.41
4.25
COP
Heating
Nom
4.46
4.33
Cooling
Nom
kW
20.02
21.96
kW
22.96
24.76
Power Input 1)
1)
Power Input
2)
HP Combination Unit Model
Independent Unit
Capacity
38
40
ARUN380LTE4
ARUN400LTE4
ARUN200LTE4
ARUN200LTE4
ARUN180LTE4
ARUN200LTE4
Cooling
Nom
kW
106.4
112.0
Heating
Nom
kW
119.7
126.0
Cooling
Nom
kW
23.74
25.62
Heating
Nom
kW
27.63
29.64
EER 1)
Cooling
Nom
4.48
4.37
COP 1)
Heating
Nom
4.33
4.25
Cooling
Nom
kW
21.39
23.08
kW
Power Input 1)
Power Input
2)
Heating
Nom
Heating
Nom
24.61
26.72
2)
Cooling
Nom
4.76
4.59
EER 2)
Cooling
Nom
4.97
4.85
COP 2)
Heating
Nom
4.66
4.58
COP 2)
Heating
Nom
4.86
4.72
Nom
7.08
7.03
ESEER 3)
Nom
6.98
6.78
-10°C ~ 43°C
-10°C ~ 43°C
EER
ESEER 3) Operation Range Compressor
Cooling
Min ~ Max °C DB
-10°C ~ 43°C
-10°C ~ 43°C
Heating
Min ~ Max °C WB
-25°C ~ 18°C
-25°C ~ 18°C
Hermetically Sealed Scroll
Hermetically Sealed Scroll
3
3
Propeller fan
Propeller fan
DC Inverter motor
DC Inverter motor
8mmAq (80Pa)
8mmAq (80Pa)
290 x 2
290 x 2
Type Number of Compressor Type
Fan
Motor Type Max Static Pressure
Airflow Rate Sound Pressure Sound Power
Cooling
Max
m3/min
Cooling
Nom
dBA
62.3
62.3
Heating
Nom
dBA
62.3
62.3
85.5
85.5
85.5
85.5
(1,240 × 1,680 × 760) × 2
(1,240 × 1,680 × 760) × 2
Dimensions
280 × 1 + 245 × 1
280 × 1 + 245 × 1
Net Weight
R410A
R410A
10.5 × 2
10.5 × 2
FVC68D (PVE)
FVC68D (PVE)
7,800
7,800
Ø / V / Hz
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
No. x mm²
Type Charge
kg
Type Control
cc
2C × 1.0~1.5
2C × 1.0~1.5
Max
m
1,000
1,000
Actual Longest Piping Length 4) Max
m
200 (225)
200 (225)
Total
Piping Connection
Sound Pressure
dBA
Transmission Cable (VCTF-SB)
Piping Level Difference
Airflow Rate
dBA kg
After 1st Y Branch 5)
Max
m
40 (90)
40 (90)
IDU - ODU
Max
m
110
110
IDU - IDU
Max
m
40
40
Heating
Min ~ Max °C WB
Type Number of Compressor Motor Type Max Static Pressure
Nom
Power Supply
Piping Length
Fan
Nom
W x H x D mm
Min ~ Max °C DB
Type
Cooling
Net Weight
Refrigerant Oil
Compressor
Heating
Dimensions
Refrigerant
Operation Range
Cooling
Sound Power
Refrigerant Refrigerant Oil
62.5
Heating
Nom
dBA
62.5
62.5
Cooling
Nom
dBA
86.0
86.0
Heating
Nom
dBA
86.0
86.0
(1,240 × 1,680 × 760) × 2
(1,240 × 1,680 × 760) × 2
280 × 2
280 × 2
W x H x D mm kg Type Charge
kg
Type Control
cc
R410A
10.5 × 2
10.5 × 2
FVC68D (PVE)
FVC68D (PVE)
8,800
8,800
Ø / V / Hz
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
No. x mm²
2C × 1.0~1.5
2C × 1.0~1.5
m
1,000
1,000
Actual Longest Piping Length 4) Max
m
200 (225)
200 (225)
After 1st Y Branch 5)
Max
m
40 (90)
40 (90)
IDU - ODU
Max
m
110
110
IDU - IDU
Max
m
40
40
mm (inch)
34.9 (1-3/8)
41.3 (1-5/8)
2
2
Number of Outdoor Units
64
64
Number of Connectable Indoor Units
Max
50 ~ 160%
50 ~ 160%
Ratio of the Connectable Indoor Units
Min ~ Max
Min ~ Max
R410A
Max
Gas
Ratio of the Connectable Indoor Units
290 x 2
62.5
19.05 (3/4)
* This product contains Fluorinated Greenhouse Gases. (R410A)
8mmAq (80Pa)
290 x 2
dBA
19.05 (3/4)
Max
DC Inverter motor
8mmAq (80Pa) Nom
mm (inch)
Number of Connectable Indoor Units
DC Inverter motor
Cooling
Liquid
Number of Outdoor Units
4 Propeller fan
m3/min
Total
Piping Connection
4 Propeller fan
Max
Transmission Cable (VCTF-SB)
Piping Level Difference
-25°C ~ 18°C Hermetically Sealed Scroll
Cooling
Power Supply
Piping Length
-25°C ~ 18°C Hermetically Sealed Scroll
Liquid
mm (inch)
19.05 (3/4)
19.05 (3/4)
Gas
mm (inch)
41.3 (1-5/8)
41.3 (1-5/8)
* This product contains Fluorinated Greenhouse Gases. (R410A)
2
2
64
64
50 ~ 160%
50 ~ 160%
LG
28
Solution
29
ARUN480LTE4 / ARUN500LTE4 / ARUN520LTE4
OUTDOOR UNIT
ARUN420LTE4 / ARUN440LTE4 / ARUN460LTE4
Heat Pump
HP Combination Unit Model
Capacity Power Input 1) EER 1) COP 1) Power Input 2) EER 2) COP 2) ESEER 3) Operation Range Compressor
Fan Airflow Rate Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Type Number of Compressor Type Motor Type Max Static Pressure Cooling Cooling Heating Cooling Heating
Dimensions
Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Min ~ Max Min ~ Max
Max Nom Nom Nom Nom
Refrigerant Oil
Piping Level Difference Piping Connection
°C DB °C WB
m3/min dBA dBA dBA dBA
kg Type Charge Type Control
kg
Power Supply Transmission Cable (VCTF-SB) Piping Length
kW kW
W x H x D mm
Net Weight Refrigerant
kW kW kW kW
Total Actual Longest Piping Length 4) After 1st Y Branch 5) IDU - ODU IDU - IDU Liquid Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units * This product contains Fluorinated Greenhouse Gases. (R410A)
Max Max Max Max Max
Max Min ~ Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch)
42
44
46
ARUN420LTE4 ARUN180LTE4 ARUN140LTE4 ARUN100LTE4 117.6 132.3 25.68 28.12 4.58 4.70 23.71 26.34 4.96 5.02 7.36 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 4 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 2 + 210 63.9 63.9 86.2 86.2 (1,240 × 1,680 × 760) × 2 + (920 × 1,680 × 760) × 1 280 × 1 + 245 x 1 + 208 × 1 R410A (10.5 × 2) + 7.5 FVC68D (PVE) 11,200 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 41.3 (1-5/8) 3 64 50 ~ 130%
ARUN440LTE4 ARUN200LTE4 ARUN140LTE4 ARUN100LTE4 123.2 138.6 27.56 30.13 4.47 4.60 25.40 28.45 4.85 4.87 7.23 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 4 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 2 + 210 63.9 63.9 86.2 86.2 (1,240 × 1,680 × 760) × 2 + (920 × 1,680 × 760) × 1 280 × 1 + 245 x 1 + 208 × 1 R410A (10.5 × 2) + 7.5 FVC68D (PVE) 11,200 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 41.3 (1-5/8) 3 64 50 ~ 130%
ARUN460LTE4 ARUN200LTE4 ARUN160LTE4 ARUN100LTE4 128.8 144.5 29.69 32.23 4.34 4.48 27.34 30.25 4.71 4.79 7.20 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 4 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 2 + 210 63.9 63.9 86.2 86.2 (1,240 × 1,680 × 760) × 2 + (920 × 1,680 × 760) × 1 280 × 1 + 245 x 1 + 208 × 1 R410A (10.5 × 2) + 7.5 FVC68D (PVE) 11,200 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 41.3 (1-5/8) 3 64 50 ~ 130%
HP Combination Unit Model
Capacity Power Input 1) EER 1) COP 1) Power Input 2) EER 2) COP 2) ESEER 3) Operation Range Compressor
Fan Airflow Rate Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Type Number of Compressor Type Motor Type Max Static Pressure Cooling Cooling Heating Cooling Heating
Dimensions
Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Min ~ Max Min ~ Max
kW kW kW kW
Max Nom Nom Nom Nom
m3/min dBA dBA dBA dBA
Refrigerant Oil
kg Type Charge Type Control
kg
Power Supply Transmission Cable (VCTF-SB) Piping Length
Piping Level Difference Piping Connection
°C DB °C WB
W x H x D mm
Net Weight Refrigerant
kW kW
Total Actual Longest Piping Length 4) After 1st Y Branch 5) IDU - ODU IDU - IDU Liquid Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units * This product contains Fluorinated Greenhouse Gases. (R410A)
Max Max Max Max Max
Max Min ~ Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch)
48
50
52
ARUN480LTE4 ARUN200LTE4 ARUN180LTE4 ARUN100LTE4 134.4 151.2 29.72 33.73 4.52 4.48 26.77 30.10 5.02 5.02 7.16 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 5 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 2 + 210 64.1 64.1 86.6 86.6 (1,240 × 1,680 × 760) × 2 + (920 × 1,680 × 760) × 1 280 x 2 + 208 × 1 R410A (10.5 × 2) + 7.5 FVC68D (PVE) 12,200 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 41.3 (1-5/8) 3 64 50 ~ 130%
ARUN500LTE4 ARUN200LTE4 ARUN200LTE4 ARUN100LTE4 140.0 157.5 31.60 35.74 4.43 4.41 28.46 32.21 4.92 4.89 7.03 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 5 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 2 + 210 64.1 64.1 86.6 86.6 (1,240 × 1,680 × 760) × 2 + (920 × 1,680 × 760) × 1 280 x 2 + 208 × 1 R410A (10.5 × 2) + 7.5 FVC68D (PVE) 12,200 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 41.3 (1-5/8) 3 64 50 ~ 130%
ARUN520LTE4 ARUN200LTE4 ARUN200LTE4 ARUN120LTE4 145.6 163.8 33.20 38.15 4.39 4.29 29.93 34.52 4.86 4.75 7.01 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 5 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 2 + 210 64.1 64.1 86.8 86.8 (1,240 × 1,680 × 760) × 2 + (920 × 1,680 × 760) × 1 280 x 2 + 208 × 1 R410A (10.5 × 2) + 7.5 FVC68D (PVE) 12,200 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 41.3 (1-5/8) 3 64 50 ~ 130%
LG
30
Solution
31
ARUN620LTE4 / ARUN640LTE4 / ARUN660LTE4 ARUN680LTE4 / ARUN700LTE4
OUTDOOR UNIT
ARUN540LTE4 / ARUN560LTE4 ARUN580LTE4 / ARUN600LTE4
Heat Pump
HP Model
54
56
58
60
Combination Unit
ARUN540LTE4 ARUN200LTE4
ARUN560LTE4 ARUN200LTE4
ARUN580LTE4 ARUN200LTE4
ARUN600LTE4 ARUN200LTE4
Independent Unit
ARUN200LTE4
ARUN200LTE4
ARUN200LTE4
ARUN200LTE4
ARUN140LTE4
ARUN160LTE4
ARUN180LTE4
ARUN200LTE4
HP Combination Unit Model
Cooling
Nom
kW
151.2
156.8
162.4
168.0
Heating
Nom
kW
170.1
176.0
182.7
189.0
Cooling
Nom
kW
34.39
36.52
36.55
38.43
Heating
Nom
kW
38.85
40.94
42.45
44.46
Power Input 1)
EER 1)
Cooling
Nom
4.40
4.29
4.44
4.37
COP 1)
Heating
Nom
4.38
4.30
4.30
4.25
EER 1) COP 1)
Cooling
Nom
kW
31.56
33.50
32.93
34.62
Heating
Nom
kW
36.32
38.12
37.97
40.08
EER 2)
Cooling
Nom
4.79
4.68
4.93
4.85
COP 2)
Heating
Nom
4.68
4.63
4.81
4.72
Capacity Power Input 1)
Power Input 2)
ESEER 3) Operation Range Compressor
Nom Cooling
Min ~ Max °C DB
Heating
Min ~ Max °C WB
Type Number of Compressor Type
Fan
Motor Type Max Static Pressure
Airflow Rate Sound Pressure Sound Power
Cooling
Max
6.91
6.78
-10°C ~ 43°C
-10°C ~ 43°C
-25°C ~ 18°C
-25°C ~ 18°C
-25°C ~ 18°C
-25°C ~ 18°C
Hermetically Sealed Scroll
Hermetically Sealed Scroll
Hermetically Sealed Scroll
Hermetically Sealed Scroll
5
5
6
6
Propeller fan
Propeller fan
Propeller fan
Propeller fan
DC Inverter motor
DC Inverter motor
DC Inverter motor
DC Inverter motor
8mmAq (80Pa)
8mmAq (80Pa)
8mmAq (80Pa)
8mmAq (80Pa)
290 x 3
290 x 3
290 x 3
290 x 3
Cooling
Nom
dBA
64.1
64.1
64.3
64.3
Nom
dBA
64.1
64.1
64.3
64.3
Cooling
Nom
dBA
87.5
87.5
87.8
87.8
Heating
Nom
dBA
87.5
87.5
87.8
87.8
W x H x D mm
Net Weight
Refrigerant Oil
6.94 -10°C ~ 43°C
Heating
Dimensions
Refrigerant
m3/min
6.98 -10°C ~ 43°C
kg Type Charge
kg
Type Control
cc
(1,240 × 1,680 × 760) × 3 (1,240 × 1,680 × 760) × 3 (1,240 × 1,680 × 760) × 3 (1,240 × 1,680 × 760) × 3 280 ×2 + 245 x 1
280 × 2 + 245 x 1
280 × 3
280 × 3
R410A
R410A
R410A
R410A
10.5 x 3
10.5 x 3
10.5 x 3
10.5 x 3
FVC68D (PVE)
FVC68D (PVE)
FVC68D (PVE)
FVC68D (PVE)
12,200
12,200
13,200
13,200
Power Supply
Ø / V / Hz
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
Transmission Cable (VCTF-SB)
No. x mm²
2C × 1.0~1.5
2C × 1.0~1.5
2C × 1.0~1.5
2C × 1.0~1.5
Total Piping Length
Piping Level Difference Piping Connection
Max
m
1,000
1,000
1,000
1,000
Max
m
200 (225)
200 (225)
200 (225)
200 (225)
After 1st Y Branch 5)
Max
m
40 (90)
40 (90)
40 (90)
40 (90)
IDU - ODU
Max
m
110
110
110
110
IDU - IDU
Max
m
40
40
40
40
Actual Longest Piping Length
4)
Liquid
mm (inch)
19.05 (3/4)
19.05 (3/4)
19.05 (3/4)
19.05 (3/4)
Gas
mm (inch)
41.3 (1-5/8)
41.3 (1-5/8)
41.3 (1-5/8)
41.3 (1-5/8)
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units * This product contains Fluorinated Greenhouse Gases. (R410A)
Max Min ~ Max
3
3
3
3
64 50 ~ 130%
64 50 ~ 130%
64 50 ~ 130%
64 50 ~ 130%
Capacity
Power Input 2) EER 2) COP 2) ESEER 3) Operation Range Compressor
Fan Airflow Rate Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Min ~ Max Min ~ Max
kW kW kW kW
Max Nom Nom Nom Nom
m3/min dBA dBA dBA dBA
Number of Compressor Type Motor Type Max Static Pressure Cooling Cooling Heating Cooling Heating
W x H x D mm
Net Weight
Refrigerant Oil
kg Type Charge Type Control
kg cc Ø / V / Hz
Power Supply Transmission Cable (VCTF-SB) Piping Length Piping Level Difference Piping Connection
°C DB °C WB
Type
Dimensions
Refrigerant
kW kW
Total Actual Longest Piping Length 4) After 1st Y Branch 5) IDU - ODU IDU - IDU Liquid Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units * This product contains Fluorinated Greenhouse Gases. (R410A)
Max Max Max Max Max
Max Min ~ Max
No. x mm² m m m m m mm (inch) mm (inch)
62
64
66
68
70
ARUN620LTE4 ARUN180LTE4 ARUN160LTE4 ARUN140LTE4 ARUN140LTE4 173.6 194.9 39.37 42.53 4.41 4.58 37.23 41.85 4.66 4.67 7.30 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 5 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.2 65.2 88.3 88.3 (1,240 × 1,680 × 760) × 4
ARUN640LTE4 ARUN180LTE4 ARUN180LTE4 ARUN140LTE4 ARUN140LTE4 179.2 201.6 39.40 44.04 4.55 4.58 36.66 41.70 4.89 4.83 7.27 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 6 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.3 65.3 88.5 88.5 (1,240 × 1,680 × 760) × 4
ARUN660LTE4 ARUN180LTE4 ARUN180LTE4 ARUN160LTE4 ARUN140LTE4 184.8 207.5 41.53 46.13 4.45 4.50 38.60 43.50 4.79 4.78 7.25 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 6 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.3 65.3 88.5 88.5 (1,240 × 1,680 × 760) × 4
ARUN680LTE4 ARUN200LTE4 ARUN200LTE4 ARUN140LTE4 ARUN140LTE4 190.4 214.2 43.16 48.06 4.41 4.46 40.04 45.92 4.76 4.66 7.08 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 6 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.3 65.3 88.5 88.5 (1,240 × 1,680 × 760) × 4
ARUN700LTE4 ARUN200LTE4 ARUN200LTE4 ARUN160LTE4 ARUN140LTE4 196.0 220.1 45.29 50.15 4.33 4.39 41.98 47.72 4.67 4.62 7.05 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 6 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.3 65.3 88.5 88.5 (1,240 × 1,680 × 760) × 4
280 × 1 + 245 x 3
280 × 2 + 245 x 2
280 × 2 + 245 x 2
280 × 2 + 245 x 2
280 × 2 + 245 x 2
R410A 10.5 x 4 FVC68D (PVE) 14,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 44.5 (1-3/4) 4 64 50 ~ 130%
R410A 10.5 x 4 FVC68D (PVE) 15,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 44.5 (1-3/4) 4 64 50 ~ 130%
R410A 10.5 x 4 FVC68D (PVE) 15,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 53.98 (2-1/8) 4 64 50 ~ 130%
R410A 10.5 x 4 FVC68D (PVE) 15,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 53.98 (2-1/8) 4 64 50 ~ 130%
R410A 10.5 x 4 FVC68D (PVE) 15,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 53.98 (2-1/8) 4 64 50 ~ 130%
LG
32
Solution
33
OUTDOOR UNIT
ARUN720LTE4 / ARUN740LTE4 / ARUN760LTE4 ARUN780LTE4 / ARUN800LTE4
Heat Pump
HP Combination Unit Model
Capacity Power Input 1) EER 1) COP 1) Power Input 2) EER 2) COP 2) ESEER 3) Operation Range Compressor
Fan Airflow Rate Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Min ~ Max Min ~ Max
Number of Compressor Type Motor Type Max Static Pressure Cooling Cooling Heating Cooling Heating
Max Nom Nom Nom Nom
°C DB °C WB
m3/min dBA dBA dBA dBA
W x H x D mm
Net Weight
Refrigerant Oil
kW kW
Type
Dimensions
Refrigerant
kW kW kW kW
kg Type Charge Type Control
kg cc
Power Supply
Ø / V / Hz
Transmission Cable (VCTF-SB)
No. x mm² m m m m m mm (inch) mm (inch)
Piping Length Piping Level Difference Piping Connection
Total Actual Longest Piping Length 4) After 1st Y Branch 5) IDU - ODU IDU - IDU Liquid Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units * This product contains Fluorinated Greenhouse Gases. (R410A)
Max Max Max Max Max
Max Min ~ Max
72
74
76
78
80
ARUN720LTE4 ARUN200LTE4 ARUN200LTE4 ARUN180LTE4 ARUN140LTE4 201.6 226.8 45.32 51.66 4.45 4.39 41.41 47.57 4.87 4.77 7.03 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 7 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.4 65.4 88.8 88.8 (1,240 × 1,680 × 760) × 4
ARUN740LTE4 ARUN200LTE4 ARUN200LTE4 ARUN180LTE4 ARUN160LTE4 207.2 232.7 47.45 53.75 4.37 4.33 43.35 49.37 4.78 4.72 7.00 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 7 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.4 65.4 88.8 88.8 (1,240 × 1,680 × 760) × 4
ARUN760LTE4 ARUN200LTE4 ARUN200LTE4 ARUN180LTE4 ARUN180LTE4 212.8 239.4 47.48 55.26 4.48 4.33 42.78 49.22 4.97 4.86 6.98 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 8 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.5 65.5 89.0 89.0 (1,240 × 1,680 × 760) × 4
ARUN780LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN180LTE4 218.4 245.7 49.36 57.27 4.42 4.29 44.47 51.33 4.91 4.79 6.88 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 8 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.5 65.5 89.0 89.0 (1,240 × 1,680 × 760) × 4
ARUN800LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 224.0 252.0 51.24 59.28 4.37 4.25 46.16 53.44 4.85 4.72 6.78 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 8 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.5 65.5 89.0 89.0 (1,240 × 1,680 × 760) × 4
280 × 3 + 245 x 1
280 × 3 + 245 x 1
280 × 4
280 × 4
280 × 4
R410A 10.5 x 4 FVC68D (PVE) 16,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 53.98 (2-1/8) 4 64 50 ~ 130%
R410A 10.5 x 4 FVC68D (PVE) 16,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 53.98 (2-1/8) 4 64 50 ~ 130%
R410A 10.5 x 4 FVC68D (PVE) 17,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 53.98 (2-1/8) 4 64 50 ~ 130%
R410A 10.5 x 4 FVC68D (PVE) 17,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 53.98 (2-1/8) 4 64 50 ~ 130%
R410A 10.5 x 4 FVC68D (PVE) 17,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 53.98 (2-1/8) 4 64 50 ~ 130%
Note : 1) Eurovent Test Condition : - Refer to EUROVENT certification regulation for more detail test conditions. - Performances of Combination units are sum of Independent unit (Outdoor Units). 2) Performances are based on the following conditions. Cooling - Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB Interconnecting piping length 7.5m Level difference of zero
Heating - Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB Interconnecting piping length 7.5m Level difference of zero
3) ESEER calculation corresponds with below conditions and power input of indoor units is not included. - Refer to PDB for more detail. - Indoor temperature : 27°C (80.6°F) DB / 19°C (66.2°F) WB - Outdoor temperature conditions.
Part Load Ratio
Outdoor Air Temp.(°C(°F)DB)
Weighting Coefficients
100% 75% 50% 25%
35 (95) 30 (86) 25 (77) 20 (68)
0.03 0.33 0.41 0.23
- Formula : 0.03 x EER100% + 0.33 x EER75% + 0.41 x EER50% + 0.23 x EER25% * Test Condition : This figure calculate based on the Eurovent Chiller test condition (=Temperature condition and Rating figure) * Indoor combination & Piping installation condition : Testedby ISO standard (=LG combination) 4) ( ) is Equivalent Piping length 5) ( ) is Conditional Application - To make 40 ~ 90m of pipe length after first branch refer to the part of “Installation of outdoor units” in PDB * Due to our policy of innovation some specifications may be changed without notification.
CAUTION • A combination operation over 100% cause to reduce each indoor unit capacity • Combination ratio (50 ~ 200%)
No. of Outdoor Unit
Connection Capacity
Single Unit Double Unit Triple Unit Over Triple Unit
200% 160% 130% 130%
We can guarantee the operation only within 130% Combination. If you want to connect more than 130% combination, please contact us and discuss the requirement like below. 1) If the operational capacity of indoor units exceed 130%, then all the indoor units operate under low air flow step mode. 2) Over 130%, capacity is same as capacity of 130%, Same remark is valid for power input.
Solution
LG
34
35
OUTDOOR UNIT
MULTI V IV
Heat Recovery
OUTDOOR UNIT
EFFICIENCY Taking energy efficiency to the next level with the latest heat recovery systems
Simultaneous Operation with High Efficiency Total Piping Length
110m
Height difference between ODU ~ IDU
1,000m
Actual longest piping length (Equivalent)
200m (225m)
Longest piping length after 1st branch (Conditional application)
40m (90m)
Height difference between ODU ~ IDU
110m
Height difference between IDU ~ IDU
40m
Height difference between ODU ~ ODU
5m
Height difference between IDU ~ HR unit
15m
Height difference between HR unit
15m
40m
15m
Height difference between IDU ~ IDU
Height difference between HR unit
2. Energy Saving through MULTI V IV Heat Recovery HR Unit
Zoning control (Maximum indoor unit 8EA)
Indoor unit Heat Absorption
MULTI V IV HEAT RECOVERY
Indoor Cooling Heat Emission
Hydro Kit
Hot Water
Cooling
- Energy consumption can be decreased by 30%
• The outdoor unit’s heat exchanger can be operated for cooling and heating simultaneously.
IT Room Cooling
- Minimize to switch mode for continuous operation - Increase efficiency with simultaneous operation COP
1,000m Total piping length
Heat Recovery
• Possible to reach COP up to 8.5 (Under condition to 40% of cooling and 60% of heating)
1. Piping Capabilities
Cooling Based 9 Operation 8 7 6 5
Maximum 8.5
Heating Based Operation
Gym Heating Heating Office Room
0
20
40
* Outdoor Temperature : 7°C DB / 6°C WB * Indoor Temperature : 20°C DB / 15°C WB
60
80 100 Operation Ratio (%)
High Efficiency Heat Recovery Unit (HR Unit) • Adapting high efficient double spiral tube heat exchanger in heat recovery unit • Maximum 8 indoor units connectable per a branch • Up to 16kW per a branch, Maximum 58kW per a HR unit • Easy installation with auto piping detect function • Access allowed to internal parts for service.
Double spiral tube heat exchanger From Outdoor
3. Operation Range • Heating : -25 ~ 18°C WB • Cooling : -10 ~ 43°C DB • Synchronous : -10 ~ 16°C WB
Linear Expansion Valve
To Indoor
2 Branch
3 Branch
4 Branch
2 Phase Fluid
Advanced Mode Change (AMC) Benefit
AMC control provides an optimal cycle operation under any conditions. Through this mode, system cycles can be more stable and maintain comfort for the user.
LG MULTI V IV heat recovery systems permit synchronous cooling and heating in different zones. The benefit of zoning for heating and cooling at the same time provides ultimate VRF technology, moving heat from one zone to another.
- Real time pressure control - Optimal cycle in optimum area - Minimize settling time after switching mode : ~5 minutes
• Hotel / Resort • Hospital • Dormitory
High Pressure
Application
or Compress (Hz )
nge Mode Cha r ) to ra o (Evap
Optimum Area
nge Mode Cha ser) n e d ( Con
or Compress (Hz )
Low Pressure
36
Solution
LG
37
FLEXIBLE DESIGN
Always ahead of the competition and on the leading edge of innovation with powerful heating and unsurpassed cooling performance
Easy design with the most convenient features
OUTDOOR UNIT
PERFORMANCE
Low temperature operation range is expanded through condenser with various control.
LG’s heat recovery unit allows flexible connection both in series and in a row. MULTI V Heat Recovery unit allows flexible connection both in series and in a row.
Indoor Temp. (°C)*
Flexible Connection of Heat Recovery Unit
27
Office
Outdoor Temperature
21
❶
❸
Zone Control
❶ Heating Mode : - 25°C WB ~ 18°C WB ❷ Cooling Mode : - 10°C DB ~ 43°C DB ❸ Synchronous Mode : -10°C WB ~ 16°C WB
❷
15 14
- Up to 8 indoor units can be connected to a branch, Maximum 32 indoor units can be connected to a HR unit - Same operation mode can be operated for zone control function - Save installation cost
Cooling Mode
10
Room
Heating Mode
-25
-10 -5
16 18 27 35 43 Outdoor Temp. (°C)**
Kitchen
* Heating (°C DB), Cooling (°C WB), Synchronous (°C DB) ** Heating (°C WB), Cooling (°C DB), Synchronous (°C WB)
IT Room
Auto Changeover
Zoning Control Temp.
Auto Changeover function operates cooling and heating to maintain optimal room temperature and increase energy savings.
HR Unit
Change Point (Cooling)
Zoning Control (Maximum Indoor Unit 8EA)
°C + T T
Change Point (Heating)
Set temp. °C Cooling Thermal Off (Fan Mode) Heating
Time
MULTI V IV Heat Recovery
Conventional
Continuous Heating Operation • Improved continuous heating operation (In case of series unit, alternative defrost per unit) - Integrated heating capacity : 17% up
• Heating mode oil return
- Continuous heating and oil return during heating mode
Y Branch
MULTI V IV Heat Recovery
Y Branch Only
Impossible
Impossible
In Series Only
In Series
Conventional Heating Off
Part Load Oil Return Part Load Defrost (Heating Mode) Defrost
Heating Off
Heating Off
Heating Supply
Heating Supply
Time
Time * Existing mode can be operated automatically, depending on the condition of application.
Heat Recovery
Wide Operation Range
38
Solution
LG
39
Combination Unit
Model
Independent Unit
Capacity
8
10
12
ARUB080LTE4
ARUB100LTE4
ARUB120LTE4
ARUB080LTE4
ARUB100LTE4
ARUB120LTE4
Cooling
Nom
kW
22.4
28.0
33.6
Heating
Nom
kW
25.2
31.5
37.8
HP
Cooling
Nom
kW
4.64
5.98
7.58
Nom
kW
4.74
6.10
8.51
EER 1)
Cooling
Nom
4.83
4.68
4.43
COP 1)
Heating
Nom
5.32
5.16
4.44
Cooling
Nom
kW
4.38
5.38
6.85
Heating
Nom
kW
4.58
5.49
7.80
EER 2)
Cooling
Nom
5.11
5.20
4.91
EER 2)
COP 2)
Heating
Nom
5.50
5.74
4.85
COP 2)
Nom
7.90
7.54
7.48
ESEER 3)
Power Input
2)
ESEER 3) Operation Range Compressor
Cooling
Min ~ Max °C DB
-10°C ~ 43°C
-10°C ~ 43°C
-10°C ~ 43°C
Heating
Min ~ Max °C WB
-25°C ~ 18°C
-25°C ~ 18°C
-25°C ~ 18°C
Hermetically Sealed Scroll
Hermetically Sealed Scroll
Hermetically Sealed Scroll
1
1
1
Propeller fan
Propeller fan
Propeller fan
DC Inverter motor
DC Inverter motor
DC Inverter motor
8mmAq (80Pa)
8mmAq (80Pa)
8mmAq (80Pa)
Type Number of Compressor Type
Fan
Motor Type Max Static Pressure
Airflow Rate Sound Pressure Sound Power
Refrigerant Refrigerant Oil
Piping Length
Piping Level Difference
Piping Connection
Nom
4.47
4.11
4.61
4.37
Heating
Nom
4.79
4.42
4.54
4.25
Cooling
Nom
kW
8.48
10.42
9.85
11.54
Heating
Nom
kW
9.60
11.40
11.25
13.36
Cooling
Nom
4.62
4.30
5.12
4.85
Heating
Nom
4.59
4.42
5.04
4.72
Nom
7.37
7.27
7.17
6.78
-10°C ~ 43°C
-10°C ~ 43°C
-10°C ~ 43°C
-10°C ~ 43°C
Power Input
Compressor
Fan
dBA
78.0
78.0
79.0
Heating
Nom
dBA
78.0
78.0
79.0
(920 × 1,680 × 760) × 1
(920 × 1,680 × 760) × 1
(920 × 1,680 × 760) × 1
Dimensions
202 × 1
208 × 1
208 × 1
Net Weight
R410A
R410A
R410A
7.7
7.7
7.7
FVC68D (PVE)
FVC68D (PVE)
FVC68D (PVE)
3,200
3,400
3,400
Ø / V / Hz
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
No. x mm²
1,000
Actual Longest Piping Length 4) Max
m
200 (225)
200 (225)
200 (225)
After 1st Y Branch 5)
Max
m
40 (90)
40 (90)
40 (90)
IDU - ODU
Max
m
110
110
110
IDU - IDU
Max
m
40
40
40
9.52 (3/8)
12.7 (1/2)
Min ~ Max °C DB
Heating
Min ~ Max °C WB
Type Number of Compressor Motor Type Max Static Pressure
Nom
2C × 1.0~1.5
Cooling
Type
Cooling
1,000
2)
Operation Range
59.0
2C × 1.0~1.5
63.0
Cooling
59.0
1,000
56.7
COP 1)
58.5
2C × 1.0~1.5
50.0
EER 1)
dBA
m
44.1
12.81
Nom
Max
kW
14.82
Heating
Total
Nom
10.93
59.0
Transmission Cable (VCTF-SB)
56.0
Heating
12.49
59.0
Power Supply
50.4
10.90
58.5
cc
44.8
11.30
dBA
Control
39.2 8.77
Nom
Type
**ARUB180LTE4
kW
9.21
Cooling
kg
ARUB160LTE4
Nom
kW
210
Charge
Airflow Rate Sound Pressure Sound Power
Refrigerant Refrigerant Oil
DC Inverter motor
DC Inverter motor
DC Inverter motor
DC Inverter motor
8mmAq (80Pa)
8mmAq (80Pa)
8mmAq (80Pa)
8mmAq (80Pa) 290
dBA
59.0
59.0
59.5
59.5
Heating
Nom
dBA
59.0
59.0
59.5
59.5
Cooling
Nom
dBA
82.0
82.0
83.0
83.0
Heating
Nom
dBA
82.0
82.0
83.0
83.0
W x H x D mm kg Type Charge
kg
Type Control
cc
(1,240 × 1,680 × 760) × 1 (1,240 × 1,680 × 760) × 1 (1,240 × 1,680 × 760) × 1 (1,240 × 1,680 × 760) × 1 245 x 1
245 x 1
280 × 1
280× 1
R410A
R410A
R410A
R410A
10.7
10.7
10.7
10.7
FVC68D (PVE)
FVC68D (PVE)
FVC68D (PVE)
FVC68D (PVE)
3,400
3,400
4,400
4,400
Ø / V / Hz
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
No. x mm²
2C × 1.0~1.5
2C × 1.0~1.5
2C × 1.0~1.5
2C × 1.0~1.5
Max
m
1,000
1,000
1,000
1,000
Actual Longest Piping Length 4) Max
m
200 (225)
200 (225)
200 (225)
200 (225)
After 1st Y Branch 5)
Max
m
40 (90)
40 (90)
40 (90)
40 (90)
IDU - ODU
Max
m
110
110
110
110
IDU - IDU
Max
m
40
40
40
40
mm (inch)
19.05 (3/4)
22.2 (7/8)
28.58 (1-1/8)
mm (inch)
15.88 (5/8)
19.05 (3/4)
19.05 (3/4)
1
1
1
Number of Outdoor Units
20
25
30
Number of Connectable Indoor Units
Max
50 ~ 200%
50 ~ 200%
50 ~ 200%
Ratio of the Connectable Indoor Units
Min ~ Max
Min ~ Max
2 Propeller fan
Nom
High Pressure Gas
Ratio of the Connectable Indoor Units
2 Propeller fan
Cooling
Low Pressure Gas
* This product contains Fluorinated Greenhouse Gases. (R410A)
1 Propeller fan
290
9.52 (3/8)
Max
1 Propeller fan
290
mm (inch)
Number of Connectable Indoor Units
-25°C ~ 18°C Hermetically Sealed Scroll
290
Total
Piping Connection
-25°C ~ 18°C Hermetically Sealed Scroll
m3/min
Transmission Cable (VCTF-SB)
Piping Level Difference
-25°C ~ 18°C Hermetically Sealed Scroll
Max
Power Supply
Piping Length
-25°C ~ 18°C Hermetically Sealed Scroll
Cooling
Liquid
Number of Outdoor Units
**ARUB200LTE4
ARUB140LTE4
Cooling
kW
210
kg
20 **ARUB200LTE4
Nom
210
Type
18 **ARUB180LTE4
Nom
m3/min
Net Weight
16 ARUB160LTE4
Cooling
Max
W x H x D mm
14 ARUB140LTE4
Heating
Power Input 1)
Cooling
Dimensions
Independent Unit
Capacity
Heating
Power Input 1)
Combination Unit
Model
Liquid
mm (inch)
12.7 (1/2)
12.7 (1/2)
15.88 (5/8)
15.88 (5/8)
Low Pressure Gas
mm (inch)
28.58 (1-1/8)
28.58 (1-1/8)
28.58 (1-1/8)
28.58 (1-1/8)
High Pressure Gas
mm (inch)
22.2 (7/8)
22.2 (7/8)
22.2 (7/8)
22.2 (7/8)
1
1
1
1
35
40
45
50
50 ~ 200%
50 ~ 200%
50 ~ 200%
50 ~ 200%
* This product contains Fluorinated Greenhouse Gases. (R410A) ** ARUB180LTE4 / ARUB200LTE4 units are excluded from Eurovent certified capacity range
Heat Recovery
HP
ARUB140LTE4 / ARUB160LTE4 ARUB180LTE4 / ARUB200LTE4
OUTDOOR UNIT
ARUB080LTE4 / ARUB100LTE4 / ARUB120LTE4
40
Solution
LG
41
Combination Unit Model
Capacity
Independent Unit
22
24
ARUB220LTE4 ARUB120LTE4
ARUB240LTE4 ARUB120LTE4
ARUB100LTE4
ARUB120LTE4
Cooling
Nom
kW
61.6
67.2
Heating
Nom
kW
69.3
75.6
Cooling
Nom
kW
13.56
15.16
Heating
Nom
kW
14.61
17.02
EER 1)
Cooling
Nom
4.54
4.43
COP 1)
Heating
Nom
4.74
4.44
Power Input 1)
Cooling
Nom
kW
12.23
13.70
Heating
Nom
kW
13.29
15.60
EER 2)
Cooling
Nom
5.04
4.91
COP
Heating
Nom
5.21
4.85
Nom
7.51
7.48
-10°C ~ 43°C
-10°C ~ 43°C
Power Input 2)
2)
ESEER 3) Operation Range Compressor
Cooling
Min ~ Max °C DB
Heating
Min ~ Max °C WB
Type Number of Compressor Type
Fan
Motor Type
Airflow Rate
Cooling
Max Static Pressure
Sound Pressure Sound Power
Max
Propeller fan DC Inverter motor
8mmAq (80Pa)
8mmAq (80Pa)
210 x 2
210 x 2
dBA
62.0
62.0
dBA
62.0
62.0
Combination Unit Model
Capacity Power Input 1) EER 1) COP 1) Power Input 2) EER 2) COP 2) ESEER 3) Operation Range Compressor
Fan Airflow Rate Sound Pressure
Cooling
Nom
dBA
81.5
82.0
Heating
Nom
dBA
81.5
82.0
(920 × 1,680 × 760) × 2
(920 × 1,680 × 760) × 2
Dimensions
208 × 2
208 × 2
Net Weight
R410A
R410A
W x H x D mm kg Type Charge
kg
Type Control
Total
Piping Connection
Propeller fan DC Inverter motor
Nom
cc
Transmission Cable (VCTF-SB)
Piping Level Difference
2
Nom
Power Supply
Piping Length
2
Cooling
Net Weight
Refrigerant Oil
-25°C ~ 18°C Hermetically Sealed Scroll
Heating
Dimensions
Refrigerant
m3/min
-25°C ~ 18°C Hermetically Sealed Scroll
HP
7.7 × 2
7.7 × 2
FVC68D (PVE)
FVC68D (PVE)
6,800
6,800
Ø / V / Hz
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
No. x mm²
2C × 1.0~1.5
2C × 1.0~1.5
Max
m
1,000
1,000
Actual Longest Piping Length 4) Max
m
200 (225)
200 (225)
After 1st Y Branch 5)
Max
m
40 (90)
40 (90)
IDU - ODU
Max
m
110
110
IDU - IDU
Max
m
40
40
Liquid
mm (inch)
15.88 (5/8)
15.88 (5/8)
Low Pressure Gas
mm (inch)
34.9 (1-3/8)
34.9 (1-3/8)
High Pressure Gas
mm (inch)
28.58 (1-1/8)
28.58 (1-1/8)
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units * This product contains Fluorinated Greenhouse Gases. (R410A)
Max Min ~ Max
2
2
44 50 ~ 160%
48 50 ~ 160%
Sound Power
Refrigerant Refrigerant Oil
Independent Unit Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Type Number of Compressor Type Motor Type Max Static Pressure Cooling Cooling Heating Cooling Heating
Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Min ~ Max Min ~ Max
Max Nom Nom Nom Nom
Piping Level Difference
Piping Connection
kW kW
°C DB °C WB
m3/min dBA dBA dBA dBA
W x H x D mm kg Type Charge Type Control
kg
Power Supply Transmission Cable (VCTF-SB) Piping Length
kW kW kW kW
Total Actual Longest Piping Length 4) After 1st Y Branch 5) IDU - ODU IDU - IDU Liquid Low Pressure Gas High Pressure Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units * This product contains Fluorinated Greenhouse Gases. (R410A)
Max Max Max Max Max
Max Min ~ Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch) mm (inch)
26
28
30
32
ARUB260LTE4 ARUB140LTE4 ARUB120LTE4 72.8 81.9 16.35 17.72 4.45 4.62 15.33 17.40 4.75 4.71 7.43 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 2 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 + 210 62.0 62.0 83.8 83.8 (1,240 × 1,680 × 760) × 1 + (920 × 1,680 × 760) × 1 245 × 1 + 208 × 1 R410A 10.7 + 7.7 FVC68D (PVE) 6,800 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 34.9 (1-3/8) 28.58 (1-1/8) 2 52 50 ~ 160%
ARUB280LTE4 ARUB160LTE4 ARUB120LTE4 78.4 87.8 18.48 19.81 4.24 4.43 17.27 19.20 4.54 4.59 7.38 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 2 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 + 210 62.0 62.0 83.8 83.8 (1,240 × 1,680 × 760) × 1 + (920 × 1,680 × 760) × 1 245 × 1 + 208 × 1 R410A 10.7 + 7.7 FVC68D (PVE) 6,800 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 34.9 (1-3/8) 28.58 (1-1/8) 2 56 50 ~ 160%
ARUB300LTE4 ARUB180LTE4 ARUB120LTE4 84.0 94.5 18.51 21.32 4.54 4.43 16.70 19.05 5.03 4.96 7.33 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 3 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 + 210 62.3 62.3 84.5 84.5 (1,240 × 1,680 × 760) × 1 + (920 × 1,680 × 760) × 1 280 x 1 + 208 x 1 R410A 10.7 + 7.7 FVC68D (PVE) 7,800 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 34.9 (1-3/8) 28.58 (1-1/8) 2 60 50 ~ 160%
ARUB320LTE4 ARUB200LTE4 ARUB120LTE4 89.6 100.8 20.39 23.33 4.39 4.32 18.39 21.16 4.87 4.76 7.13 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 3 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 + 210 62.3 62.3 84.5 84.5 (1,240 × 1,680 × 760) × 1 + (920 × 1,680 × 760) × 1 280 x 1 + 208 x 1 R410A 10.7 + 7.7 FVC68D (PVE) 7,800 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 34.9 (1-3/8) 28.58 (1-1/8) 2 64 50 ~ 160%
Heat Recovery
HP
ARUB260LTE4 / ARUB280LTE4 ARUB300LTE4 / ARUB320LTE4
OUTDOOR UNIT
ARUB220LTE4 / ARUB240LTE4
42
Solution
LG
43
Combination Unit Model
Capacity
Independent Unit
34
36
ARUB340LTE4 ARUB200LTE4
ARUB360LTE4 ARUB200LTE4
ARUB140LTE4
ARUB160LTE4
Cooling
Nom
kW
95.2
100.8
Heating
Nom
kW
107.1
113.0
Cooling
Nom
kW
21.58
23.71
Heating
Nom
kW
24.03
26.12
EER 1)
Cooling
Nom
4.41
4.25
COP 1)
Heating
Nom
4.46
4.33
Cooling
Nom
kW
20.02
21.96
kW
22.96
24.76
Power Input 1)
Power Input 2)
HP Combination Unit Model
Capacity
Independent Unit
38
40
ARUB380LTE4 ARUB200LTE4
ARUB400LTE4 ARUB200LTE4
ARUB180LTE4
ARUB200LTE4
Cooling
Nom
kW
106.4
112.0
Heating
Nom
kW
119.7
126.0
Cooling
Nom
kW
23.74
25.62
Heating
Nom
kW
27.63
29.64
EER 1)
Cooling
Nom
4.48
4.37
COP 1)
Heating
Nom
4.33
4.25
Cooling
Nom
kW
21.39
23.08
kW
Power Input 1)
Power Input 2)
Heating
Nom
Heating
Nom
24.61
26.72
2)
Cooling
Nom
4.76
4.59
EER 2)
Cooling
Nom
4.97
4.85
COP 2)
Heating
Nom
4.66
4.58
COP 2)
Heating
Nom
4.86
4.72
Nom
7.08
7.03
ESEER 3)
Nom
6.98
6.78
-10°C ~ 43°C
-10°C ~ 43°C
EER
ESEER 3) Operation Range Compressor
Cooling
Min ~ Max °C DB
-10°C ~ 43°C
-10°C ~ 43°C
Heating
Min ~ Max °C WB
-25°C ~ 18°C
-25°C ~ 18°C
Hermetically Sealed Scroll
Hermetically Sealed Scroll
Type Number of Compressor Type
Fan
Motor Type Max Static Pressure
Airflow Rate Sound Pressure Sound Power
290 x 2
290 x 2
Nom
dBA
62.3
62.3
Heating
Nom
dBA
62.3
62.3
Compressor
Fan Airflow Rate Sound Pressure
Nom
dBA
85.5
85.5
Nom
dBA
85.5
85.5
(1,240 × 1,680 × 760) × 2
(1,240 × 1,680 × 760) × 2
Dimensions
280 × 1 + 245 × 1
280 × 1 + 245 × 1
Net Weight
R410A
R410A
10.7 × 2
10.7 × 2
FVC68D (PVE)
FVC68D (PVE)
7,800
7,800
Ø / V / Hz
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
No. x mm²
kg Type Charge
kg
Type Control
cc
2C × 1.0~1.5
2C × 1.0~1.5
Max
m
1,000
1,000
Actual Longest Piping Length 4) Max
m
200 (225)
200 (225)
After 1st Y Branch 5)
Max
m
40 (90)
40 (90)
IDU - ODU
Max
m
110
110
IDU - IDU
Max
m
40
40
19.05 (3/4)
19.05 (3/4)
Liquid
mm (inch)
Low Pressure Gas
mm (inch)
34.9 (1-3/8)
41.3 (1-5/8)
High Pressure Gas
mm (inch)
28.58 (1-1/8)
28.58 (1-1/8)
2
2
64 50 ~ 160%
64 50 ~ 160%
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units * This product contains Fluorinated Greenhouse Gases. (R410A)
Max Min ~ Max
Heating
Min ~ Max °C WB
Type Number of Compressor Motor Type Max Static Pressure
Cooling
W x H x D mm
Min ~ Max °C DB
Type
Heating
Total
Piping Connection
8mmAq (80Pa)
Cooling
Transmission Cable (VCTF-SB)
Piping Level Difference
DC Inverter motor
8mmAq (80Pa) m3/min
Power Supply
Piping Length
DC Inverter motor Max
Net Weight
Refrigerant Oil
3 Propeller fan
Cooling
Dimensions
Refrigerant
3 Propeller fan
Operation Range
Cooling
Sound Power
Refrigerant Refrigerant Oil
4 Propeller fan
DC Inverter motor
DC Inverter motor
8mmAq (80Pa)
8mmAq (80Pa)
290 x 2
290 x 2
m3/min
Cooling
Nom
dBA
62.5
62.5
Heating
Nom
dBA
62.5
62.5
Cooling
Nom
dBA
86.0
86.0
Heating
Nom
dBA
86.0
86.0
(1,240 × 1,680 × 760) × 2
(1,240 × 1,680 × 760) × 2
280 × 2
280 × 2
W x H x D mm kg Type Charge
kg
Type Control
Total
Piping Connection
4 Propeller fan
Max
cc
Transmission Cable (VCTF-SB)
Piping Level Difference
-25°C ~ 18°C Hermetically Sealed Scroll
Cooling
Power Supply
Piping Length
-25°C ~ 18°C Hermetically Sealed Scroll
R410A
R410A
10.7 × 2
10.7 × 2
FVC68D (PVE)
FVC68D (PVE)
8,800
8,800
Ø / V / Hz
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
No. x mm²
2C × 1.0~1.5
2C × 1.0~1.5
Max
m
1,000
1,000
Actual Longest Piping Length 4) Max
m
200 (225)
200 (225)
After 1st Y Branch 5)
Max
m
40 (90)
40 (90)
IDU - ODU
Max
m
110
110
IDU - IDU
Max
m
40
40
Liquid
mm (inch)
19.05 (3/4)
19.05 (3/4)
Low Pressure Gas
mm (inch)
41.3 (1-5/8)
41.3 (1-5/8)
High Pressure Gas
mm (inch)
34.9 (1-3/8)
34.9 (1-3/8)
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units * This product contains Fluorinated Greenhouse Gases. (R410A)
Max Min ~ Max
2
2
64 50 ~ 160%
64 50 ~ 160%
Heat Recovery
HP
ARUB380LTE4 / ARUB400LTE4
OUTDOOR UNIT
ARUB340LTE4 / ARUB360LTE4
LG
44
Solution
45
Combination Unit Model
Capacity Power Input 1) EER 1) COP 1) Power Input 2) EER 2) COP 2) ESEER 3) Operation Range Compressor Fan Airflow Rate Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Type Number of Compressor Type Motor Type Max Static Pressure Cooling Cooling Heating Cooling Heating
Dimensions
Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Min ~ Max Min ~ Max
Max Nom Nom Nom Nom
Refrigerant Oil
Piping Level Difference Piping Connection
°C DB °C WB
m3/min dBA dBA dBA dBA
kg Type Charge Type Control
kg
Power Supply Transmission Cable (VCTF-SB) Piping Length
kW kW
W x H x D mm
Net Weight Refrigerant
kW kW kW kW
Total Actual Longest Piping Length 4) After 1st Y Branch 5) IDU - ODU IDU - IDU Liquid Low Pressure Gas High Pressure Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units * This product contains Fluorinated Greenhouse Gases. (R410A)
Max Max Max Max Max
Max Min ~ Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch) mm (inch)
42
44
46
ARUB420LTE4 ARUB180LTE4 ARUB140LTE4 ARUB100LTE4 117.6 132.3 25.68 28.12 4.58 4.70 23.71 26.34 4.96 5.02 7.36 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 4 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 2 + 210 63.9 63.9 86.2 86.2 (1,240 × 1,680 × 760) × 2 + (920 × 1,680 × 760) × 1 280 × 1 + 245 x 1 + 208 × 1 R410A (10.7 × 2) + 7.7 FVC68D (PVE) 11,200 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
ARUB440LTE4 ARUB200LTE4 ARUB140LTE4 ARUB100LTE4 123.2 138.6 27.56 30.13 4.47 4.60 25.40 28.45 4.85 4.87 7.23 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 4 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 2 + 210 63.9 63.9 86.2 86.2 (1,240 × 1,680 × 760) × 2 + (920 × 1,680 × 760) × 1 280 × 1 + 245 x 1 + 208 × 1 R410A (10.7 × 2) + 7.7 FVC68D (PVE) 11,200 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
ARUB460LTE4 ARUB200LTE4 ARUB160LTE4 ARUB100LTE4 128.8 144.5 29.69 32.22 4.34 4.48 27.34 30.25 4.71 4.79 7.20 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 4 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 2 + 210 63.9 63.9 86.2 86.2 (1,240 × 1,680 × 760) × 2 + (920 × 1,680 × 760) × 1 280 × 1 + 245 x 1 + 208 × 1 R410A (10.7 × 2) + 7.7 FVC68D (PVE) 11,200 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
HP Combination Unit Model
Capacity Power Input 1) EER 1) COP 1) Power Input 2) EER 2) COP 2) ESEER 3) Operation Range Compressor Fan Airflow Rate Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Type Number of Compressor Type Motor Type Max Static Pressure Cooling Cooling Heating Cooling Heating
Dimensions
Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Min ~ Max Min ~ Max
kW kW kW kW
Max Nom Nom Nom Nom
m3/min dBA dBA dBA dBA
Refrigerant Oil
kg Type Charge Type Control
kg
Power Supply Transmission Cable (VCTF-SB) Piping Length Piping Level Difference Piping Connection
°C DB °C WB
W x H x D mm
Net Weight Refrigerant
kW kW
Total Actual Longest Piping Length 4) After 1st Y Branch 5) IDU - ODU IDU - IDU Liquid Low Pressure Gas High Pressure Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units * This product contains Fluorinated Greenhouse Gases. (R410A)
Max Max Max Max Max
Max Min ~ Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch) mm (inch)
48
50
52
ARUB480LTE4 ARUB200LTE4 ARUB180LTE4 ARUB100LTE4 134.4 151.2 29.72 33.73 4.52 4.48 26.77 30.10 5.02 5.02 7.16 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 5 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 2 + 210 64.1 64.1 86.6 86.6 (1,240 × 1,680 × 760) × 2 + (920 × 1,680 × 760) × 1 280 x 2 + 208 × 1 R410A (10.7 × 2) + 7.7 FVC68D (PVE) 12,200 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
ARUB500LTE4 ARUB200LTE4 ARUB200LTE4 ARUB100LTE4 140.0 157.5 31.60 35.74 4.43 4.41 28.46 32.21 4.92 4.89 7.03 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 5 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 2 + 210 64.1 64.1 86.6 86.6 (1,240 × 1,680 × 760) × 2 + (920 × 1,680 × 760) × 1 280 x 2 + 208 × 1 R410A (10.7 × 2) + 7.7 FVC68D (PVE) 12,200 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
ARUB520LTE4 ARUB200LTE4 ARUB200LTE4 ARUB120LTE4 145.6 163.8 33.20 38.15 4.39 4.29 29.93 34.52 4.86 4.75 7.01 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 5 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 2 + 210 64.1 64.1 86.8 86.8 (1,240 × 1,680 × 760) × 2 + (920 × 1,680 × 760) × 1 280 x 2 + 208 × 1 R410A (10.7 × 2) + 7.7 FVC68D (PVE) 12,200 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
Heat Recovery
HP
ARUB480LTE4 / ARUB500LTE4 / ARUB520LTE4
OUTDOOR UNIT
ARUB420LTE4 / ARUB440LTE4 / ARUB460LTE4
46
Solution
LG
47
Combination Unit Model
Capacity Power Input 1) EER COP 1) 1)
Power Input 2) EER 2) COP 2) ESEER 3) Operation Range Compressor
Fan Airflow Rate Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Type Number of Compressor Type Motor Type Max Static Pressure Cooling Cooling Heating Cooling Heating
Dimensions Net Weight Refrigerant Refrigerant Oil
Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Min ~ Max Min ~ Max
Max Nom Nom Nom Nom WxHxD
Type Charge Type Control
Piping Length
Piping Level Difference
Piping Connection
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units * This product contains Fluorinated Greenhouse Gases. (R410A)
kW kW
°C DB °C WB
m3/min dBA dBA dBA dBA mm kg kg
Power Supply Transmission Cable (VCTF-SB) Total Actual Longest Piping Length 4) After 1st Y Branch 5) IDU - ODU IDU - IDU Liquid Low Pressure Gas High Pressure Gas
kW kW kW kW
Max Max Max Max Max
Max Min ~ Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch) mm (inch)
54
56
58
60
ARUB540LTE4 ARUB200LTE4 ARUB200LTE4 ARUB140LTE4 151.2 170.1 34.39 38.85 4.40 4.38 31.56 36.32 4.79 4.68 6.98 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 5 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 3 64.1 64.1 87.5 87.5 (1,240 × 1,680 × 760) × 3 280 × 2 + 245 x 1 R410A 10.7 x 3 FVC68D (PVE) 12,200 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
ARUB560LTE4 ARUB200LTE4 ARUB200LTE4 ARUB160LTE4 156.8 176.0 36.52 40.94 4.29 4.30 33.50 38.12 4.68 4.63 6.94 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 5 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 3 64.1 64.1 87.5 87.5 (1,240 × 1,680 × 760) × 3 280 × 2 + 245 x 1 R410A 10.7 x 3 FVC68D (PVE) 12,200 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
ARUB580LTE4 ARUB200LTE4 ARUB200LTE4 ARUB180LTE4 162.4 182.7 36.55 42.45 4.44 4.30 32.93 37.97 4.93 4.81 6.91 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 6 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 3 64.3 64.3 87.8 87.8 (1,240 × 1,680 × 760) × 3 280 × 3 R410A 10.7 x 3 FVC68D (PVE) 13,200 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
ARUB600LTE4 ARUB200LTE4 ARUB200LTE4 ARUB200LTE4 168.0 189.0 38.43 44.46 4.37 4.25 34.62 40.08 4.85 4.72 6.78 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 6 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 3 64.3 64.3 87.8 87.8 (1,240 × 1,680 × 760) × 3 280 × 3 R410A 10.7 x 3 FVC68D (PVE) 13,200 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
HP Combination Unit Model
Capacity Power Input 1) EER 1) COP 1) Power Input 2) EER 2) COP 2) ESEER 3) Operation Range Compressor
Fan Airflow Rate Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Min ~ Max Min ~ Max
kW kW kW kW
Max Nom Nom Nom Nom
m3/min dBA dBA dBA dBA
Number of Compressor Type Motor Type Max Static Pressure Cooling Cooling Heating Cooling Heating
W x H x D mm
Net Weight
Refrigerant Oil
kg Type Charge Type Control
kg cc
Power Supply
Ø / V / Hz
Transmission Cable (VCTF-SB) Piping Length Piping Level Difference Piping Connection
°C DB °C WB
Type
Dimensions
Refrigerant
kW kW
Total Actual Longest Piping Length 4) After 1st Y Branch 5) IDU - ODU IDU - IDU Liquid Low Pressure Gas High Pressure Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units * This product contains Fluorinated Greenhouse Gases. (R410A)
Max Max Max Max Max
Max Min ~ Max
No. x mm² m m m m m mm (inch) mm (inch) mm (inch)
62
64
66
68
70
ARUB620LTE4 ARUB180LTE4 ARUB160LTE4 ARUB140LTE4 ARUB140LTE4 173.6 194.9 39.37 42.53 4.41 4.58 37.23 41.85 4.66 4.67 7.30 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 5 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.2 65.2 88.3 88.3 (1,240 × 1,680 × 760) × 4 280 × 1 + 245 x 3 R410A 10.7 x 4 FVC68D (PVE) 14,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 44.5 (1-3/4) 41.3 (1-5/8) 4 64 50 ~ 130%
ARUB640LTE4 ARUB180LTE4 ARUB180LTE4 ARUB140LTE4 ARUB140LTE4 179.2 201.6 39.40 44.04 4.55 4.58 36.66 41.70 4.89 4.83 7.27 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 6 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.3 65.3 88.5 88.5 (1,240 × 1,680 × 760) × 4 280 × 2 + 245 x 2 R410A 10.7 x 4 FVC68D (PVE) 15,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 44.5 (1-3/4) 41.3 (1-5/8) 4 64 50 ~ 130%
ARUB660LTE4 ARUB180LTE4 ARUB180LTE4 ARUB160LTE4 ARUB140LTE4 184.8 207.5 41.53 46.13 4.45 4.50 38.60 43.50 4.79 4.78 7.25 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 6 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.3 65.3 88.5 88.5 (1,240 × 1,680 × 760) × 4 280 × 2 + 245 x 2 R410A 10.7 x 4 FVC68D (PVE) 15,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 53.98 (2-1/8) 44.5 (1-3/4) 4 64 50 ~ 130%
ARUB680LTE4 ARUB200LTE4 ARUB200LTE4 ARUB140LTE4 ARUB140LTE4 190.4 214.2 43.16 48.06 4.41 4.46 40.04 45.92 4.76 4.66 7.08 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 6 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.3 65.3 88.5 88.5 (1,240 × 1,680 × 760) × 4 280 × 2 + 245 x 2 R410A 10.7 x 4 FVC68D (PVE) 15,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 53.98 (2-1/8) 44.5 (1-3/4) 4 64 50 ~ 130%
ARUB700LTE4 ARUB200LTE4 ARUB200LTE4 ARUB160LTE4 ARUB140LTE4 196.0 220.1 45.29 50.15 4.33 4.39 41.98 47.72 4.67 4.62 7.05 -10°C ~ 43°C -25°C ~ 18°C Hermetically ealed Scroll 6 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.3 65.3 88.5 88.5 (1,240 × 1,680 × 760) × 4 280 × 2 + 245 x 2 R410A 10.7 x 4 FVC68D (PVE) 15,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 53.98 (2-1/8) 44.5 (1-3/4) 4 64 50 ~ 130%
Heat Recovery
HP
ARUB620LTE4 / ARUB640LTE4 / ARUB660LTE4 ARUB680LTE4 / ARUB700LTE4
OUTDOOR UNIT
ARUB540LTE4 / ARUB560LTE4 ARUB580LTE4 / ARUB600LTE4
LG
48
Solution
49
OUTDOOR UNIT
ARUB720LTE4 / ARUB740LTE4 / ARUB760LTE4 ARUB780LTE4 / ARUB800LTE4
Combination Unit Model
Capacity Power Input 1) EER 1) COP 1) Power Input 2) EER 2) COP 2) ESEER 3) Operation Range Compressor
Fan Airflow Rate Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Nom Min ~ Max Min ~ Max
kW kW kW kW
kW kW
°C DB °C WB
Type Number of Compressor Type Motor Type Max Static Pressure Cooling Cooling Heating Cooling Heating
Dimensions
Max Nom Nom Nom Nom
m3/min dBA dBA dBA dBA
W x H x D mm
Net Weight
kg Type Charge Type Control
cc
Power Supply
Ø / V / Hz
Transmission Cable (VCTF-SB) Total Actual Longest Piping Length 4) After 1st Y Branch 5) IDU - ODU IDU - IDU Liquid Low Pressure Gas High Pressure Gas
No. x mm² m m m m m mm (inch) mm (inch) mm (inch)
Refrigerant Refrigerant Oil
Piping Length Piping Level Difference Piping Connection
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units * This product contains Fluorinated Greenhouse Gases. (R410A)
kg
Max Max Max Max Max
Max Min ~ Max
72
74
76
78
80
ARUB720LTE4 ARUB200LTE4 ARUB200LTE4 ARUB180LTE4 ARUB140LTE4 201.6 226.8 45.32 51.66 4.45 4.39 41.41 47.57 4.87 4.77 7.03 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 7 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.4 65.4 88.8 88.8 (1,240 × 1,680 × 760) × 4 280 × 3 + 245 x 1 R410A 10.7 x 4 FVC68D (PVE) 16,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 53.98 (2-1/8) 44.5 (1-3/4) 4 64 50 ~ 130%
ARUB740LTE4 ARUB200LTE4 ARUB200LTE4 ARUB180LTE4 ARUB160LTE4 207.2 232.7 47.45 53.75 4.37 4.33 43.35 49.37 4.78 4.72 7.00 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 7 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.4 65.4 88.8 88.8 (1,240 × 1,680 × 760) × 4 280 × 3 + 245 x 1 R410A 10.7 x 4 FVC68D (PVE) 16,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 53.98 (2-1/8) 44.5 (1-3/4) 4 64 50 ~ 130%
ARUB760LTE4 ARUB200LTE4 ARUB200LTE4 ARUB180LTE4 ARUB180LTE4 212.8 239.4 47.48 55.26 4.48 4.33 42.78 49.22 4.97 4.86 6.98 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 8 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.5 65.5 89.0 89.0 (1,240 × 1,680 × 760) × 4 280 × 4 R410A 10.7 x 4 FVC68D (PVE) 17,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 53.98 (2-1/8) 44.5 (1-3/4) 4 64 50 ~ 130%
ARUB780LTE4 ARUB200LTE4 ARUB200LTE4 ARUB200LTE4 ARUB180LTE4 218.4 245.7 49.36 57.27 4.42 4.29 44.47 51.33 4.91 4.79 6.88 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 8 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.5 65.5 89.0 89.0 (1,240 × 1,680 × 760) × 4 280 × 4 R410A 10.7 x 4 FVC68D (PVE) 17,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 53.98 (2-1/8) 44.5 (1-3/4) 4 64 50 ~ 130%
ARUB800LTE4 ARUB200LTE4 ARUB200LTE4 ARUB200LTE4 ARUB200LTE4 224.0 252.0 51.24 59.28 4.37 4.25 46.16 53.44 4.85 4.72 6.78 -10°C ~ 43°C -25°C ~ 18°C Hermetically Sealed Scroll 8 Propeller fan DC Inverter motor 8mmAq (80Pa) 290 x 4 65.5 65.5 89.0 89.0 (1,240 × 1,680 × 760) × 4 280 × 4 R410A 10.7 x 4 FVC68D (PVE) 17,600 3 / 380~415 / 50, 60 2C × 1.0~1.5 1,000 200 (225) 40 (90) 110 40 22.2 (7/8) 53.98 (2-1/8) 44.5 (1-3/4) 4 64 50 ~ 130%
Heat Recovery
HP
Note : 1) Eurovent Test Condition : - Refer to EUROVENT certification regulation for more detail test conditions. - Performances of Combination units are sum of Independent unit (Outdoor Units). 2) Performances are based on the following conditions. Cooling - Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB Interconnecting piping length 7.5m Level difference of zero
Heating - Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB Interconnecting piping length 7.5m Level difference of zero
3) ESEER calculation corresponds with below conditions and power input of indoor units is not included. - Refer to PDB for more detail. - Indoor temperature : 27°C (80.6°F) DB / 19°C (66.2°F) WB - Outdoor temperature conditions.
Part Load Ratio
Outdoor Air Temp.(°C(°F)DB)
Weighting Coefficients
100% 75% 50% 25%
35 (95) 30 (86) 25 (77) 20 (68)
0.03 0.33 0.41 0.23
- Formula : 0.03 x EER100% + 0.33 x EER75% + 0.41 x EER50% + 0.23 x EER25% * Test Condition : This figure calculate based on the Eurovent Chiller test condition (=Temperature condition and Rating figure) * Indoor combination & Piping installation condition : Testedby ISO standard (=LG combination) 4) ( ) is Equivalent Piping length 5) ( ) is Conditional Application - To make 40 ~ 90m of pipe length after first branch refer to the part of “Installation of outdoor units” in PDB * Due to our policy of innovation some specifications may be changed without notification.
CAUTION • A combination operation over 100% cause to reduce each indoor unit capacity • Combination ratio (50 ~ 200%)
No. of Outdoor Unit
Connection Capacity
Single Unit Double Unit Triple Unit Over Triple Unit
200% 160% 130% 130%
We can guarantee the operation only within 130% Combination. If you want to connect more than 130% combination, please contact us and discuss the requirement like below. 1) If the operational capacity of indoor units exceed 130%, then all the indoor units operate under low air flow step mode. 2) Over 130%, capacity is same as capacity of 130%, Same remark is valid for power input.
Solution
LG
50
51
OUTDOOR UNIT
MULTI V S
OUTDOOR UNIT
EFFICIENCY
150m
Longest piping length
LG’s 4th Generation Inverter Compressor MULTI V S has high efficiency inverter scroll compressor with frequency range 15Hz ~ 150Hz.
1. Compact Size
World Best Compressor Speed 150Hz
Conventional 8 HP
MULTI V S 8 HP
920mm
950mm
40m
Height difference between ODU ~ IDU
300m Total piping length
2. Piping Capabilities Total Piping Length
300m
Longest piping length (Equivalent)
150m (175m)
Longest piping length after 1st branch (Conditional application)
40m (90m)
Height difference between ODU ~ IDU
40m* (50m**)
Height difference between IDU ~ IDU
15m
Operation Range (Hz)
- Rapid response capability - Compact core design (Concentrated motor) - Down to 15Hz : Part load efficiency improvement 330mm
760mm
55% Reduction
150 120
20 15 Conventional
* In case of outdoor unit installed lower than indoor unit ** In case of outdoor unit installed upper than indoor unit
6 By-pass Valve
3. Operation Range
Compressor reliability is maximized with 6 By-pass Valve - Prevent compressor damage due to excessively compressed refrigerant more efficiently than 4 by-pass valve
• Heating : -20 ~ 18°C WB • Cooling : -5 ~ 43°C DB
High Pressure Compressor - Viscosity of oil is secured due to high temperature and pressure. - Do not need oil pump. (Efficiency Increases) High Pressure Zone
Benefit • Saves valuable floor space • Flexible design applications - Slim, light and wide line up (4 ~ 12HP) - Combination of indoor unit
Application • Premium residential apartment / House (With small balcony) • Small sized office / Restaurant / Retail shops • Building with multiple owners
Low Pressure Zone
High Pressure Zone
Low Pressure Compressor
High Pressure Compressor
Inverter Scroll Compressor - Inverter SCROLL compressor of high efficiency - Low vibration / Low noise
MULTI V S
15m
Height difference between IDU ~ IDU
52
Solution
LG
53
OUTDOOR UNIT
EFFICIENCY High Efficiency
Optimal Heat Exchanger Circuit COP (Heating) 6HP
COP
10%
Variable Heat Exchanger Circuit is the world first technology which intelligently selects the optimal path for both heating and cooling (Efficiency increased up to 5%).
12%
6HP Variable Heat Exchanger Circuit adjusts the path number to match temperatures and operation modes, thereby contributing to an increase in energy efficiency
4.18
3.71
Conventional
3.71
The number and direction of path are fixed independent of temperature and operation mode. A fixed path limits efficiency
3.35
* Comparison Based on 6HP in heating mode
Compromising efficiency for each operation
Heating
1
Compressor Efficiency Comparison
Rotary
8HP
Efficiency
2
3
4
Cooling
Path Number
1
2
3
4
Scroll Compressor Rotary Compressor
Heat Exchanger with Wide Louver Plus Fin Improved heat exchanger efficiency of up to 7%.
12HP
Cooling
Scroll 4 * Based on internal test data
7
10
HP
Heat Exchange Rate (%)
6HP
Heating
Cooling
MULTI V S Inverter compressors are highly efficient and reliable for all commercial & residential applications.
4HP
Heating
Maximizing efficiency for all operations
Reliable Inverter Compressor High reliability and efficiency at all capacity - Below 7HP : Rotary compressor - Upper 7HP : Scroll compressor
Cooling
Heating
5% 105% 100%
Conventional
Wide Louver Plus Fin
Heat Exchange Rate (%)
* Comparison Based on 6HP in cooling mode
Heating
Efficiency
B Company
Efficiency
Cooling
B Company
7% 107% 100%
Conventional
Wide Louver Plus Fin
Path Number
MULTI V S
EER
EER (Cooling)
Solution
54
55
PERFORMANCE Always ahead of the competition and on the leading edge of innovation with powerful heating and unsurpassed cooling performance
Pressure Sensor
OUTDOOR UNIT
EFFICIENCY
High Reliability of Refrigerant Cycle
Low Pressure Sensor
Senses and controls pressure directly using pressure sensor for faster and more exact response to load variation
MULTI V S improved reliability through an excellent technique of Oil separator / Accumulator / Sub-cooling.
1. Cyclone Centrifuges Oil Separator
2. Large Volume Accumulator
- Highly reliable and efficient oil separation by centrifugal separation using cyclone methods
- Improved reliability by adopting the large volume accumulator (138% volume up compared to conventional)
Pressure +Temperature Control Temperature Control
14%
12
- High collection efficiency as well as outstanding resistance to high temperature and pressure
Quicker
14%
Time The indoor environment can be made more comfortable, faster and more accurately.
- Prevents the liquid refrigerant entering the compressor suction
Refrigerant Refrigerant+Oil Oil Cyclone entrifuges Centrifuges
* Based on internal test data
Smart Load Control
Oil Separator
Accumulator
MULTI V S changes indoor discharge air temperature continuously according to load, to save energy.
SLC (Smart Load Control) Operation Start-up Operation
Auto-reactive Operation After 20 minutes
Benefits : - Energy efficiency increased by 3-step Smart Load Control during start-up phase - Discharge air temperature adjusted according to outdoor and indoor temperature - Comfort level in cooling / heating operations ensured During Start up
Weather Dependent
Outdoor Temperature
Indoor Discharge Air Temperature
Changed by Indoor Temperature
3. BLDC Fan Motor
4. Double Sub-cool Interchanger
- The BLDC Fan motor is more efficient than a conventional AC motor, offering an additional 40% energy savings at low speeds and 20% at high speeds
- Reliability is enhanced by minimizing pressure drop due to high efficiency spiral structure and 2 times larger size Long pipe is possible (up to 175m) and high elevation (up to 50m) Reduction of indoor refrigerant noise level
50 Power Input
40%
100
20%
BLDC Motor AC Motor 500
Up to 30% Energy Saving
Smooth (Level1) Quick (Level 2) Power (Level 3)
SLC Start up Operation
SLC Contol Basic Operation (Default Setting)
Time
1,000 Motor Speed (RPM)
Double Sub-cool Interchanger
MULTI V S
High Pressure Sensor
Quick Operating Response Pressure control takes up to 14% less time in cooling mode, to reach the desired temperature. Outlet Temp. (°C)
Temperature + Pressure Control
Efficiency (%)
LG
56
Solution
LG
57
OUTDOOR UNIT
PERFORMANCE Always ahead of the competition and on the leading edge of innovation with powerful heating and unsurpassed cooling performance
Fan Technology and E.S.P. Control
Night Silent Operation
For efficient operation, newly developed fan blows higher air volume and has more high static pressure, also operating noise is decreased.
At night mode, noise reduced maximum 14% compared to normal mode.
Fan Technology
Capacity
Mogul Trailing Edge
Super cannon fan increases the air volume in 50 CMM and the noise level is decreased by 4dB (A).
Max. 8dB (A)
Load
Grooved Suction Surface Reverse Hub
58 Sound Level
Night Mode End
Mode Start
50
50dB (A)
Step 1
526mm
Step 2 (1Ø) 4HP
Narrow Hub Blade
(1Ø) 5 / 6HP (3Ø) 4 / 5 / 6 / 8HP
Super Canon Fan (3Ø) 10 / 12HP
Tip Vortex Suppressor
High E.S.P. Technology
Step 3 8:00
12:00
16:00
Day 20:00
0:00
4:00
8:00
12:00
16:00 Time
Night
* Normal mode noise level (10HP) : 58dB(A) * Night 3 step noise level (10HP) : 56dB(A), 53dB(A), 50dB(A) * Sound pressure tested by following conditions : 1m distance / 1.5m height
Expanded Piping Capabilities
Flow of air has straightness due to fan shroud and E.S.P. control even in high-rise building.
MULTI V S inverter technology and sub cooling control circuit technology allows greater piping length and outstanding elevation differences. A cooling system can be implemented more flexibly in a shop, office and even high-rise building, reducing the designer’s work time and providing more efficient design.
Piping Capabilities
+
+
E.S.P. Control
High Static Pressure
(Fan Max. RPM Up)
Shroud
* E.S.P : External Static Pressure
• Straight air flow - New shroud adopted - Performs high static pressure
- Free design and installation by 4 way piping.
Total Piping Length
175m Fan
4 Way Piping 300m
Longest Equivalent Pipe Length
15m
IDU~IDU Height Difference
50m
ODU-IDU Height Difference
MULTI V S
The new axial fan has a mogul trailing edge, narrow hub blade and reverse hub, this provides a high efficiency, low noise, wide fan, as well as improving the air flow rate.
LG
Solution
58
59
OUTDOOR UNIT
CONVENIENCE Self-diagnostic maintenance solution, offering smart and reliable functionality
Upgraded Fault Detection and Diagnosis
Smartphone Monitoring & Control
The inclusion of FDD elements - Auto start-up, auto refrigerant check, black box functionality, simultaneous evaluation, and auto refrigerant collection, provides the optimal solution for user reliability and ease of maintenance.
Mobile LGMV helps users to monitor the MULTI V S system cycle using Wi-Fi MV Module. Technicians can check LGMV data 10m away from MULTI V S outdoor with smartphone. MULTI V S
FDD MICOM
- Auto commissioning Mode - Auto Refrigerant Collection - Auto evaluation of refrigerant amount and charging - Able to access LGMV (LG Monitoring View) by smartphone - Black box function - Piping & Wiring error check-up
Wi-Fi MV Module
Wi-Fi
Install / SVC Engineer
Mobile LGMV
Connection type : Wi-Fi / To use Mobile LGMV Application, exclusive Wi-Fi MV Module is required
Smart Phone Specification App. Name OS
Recommended Specification
iOS (iPad Only) AppiOS 8.0 / 8.1 Mobile LGMV
Self Cooled Control
Android
Resolution
Wireless Communication Effective Distancd
2,048 x 1,536 (Optimization), 1,024 x 768
• Effective distance : 10m (Open Area) • The effective distance may be reduced by the communication environment
Android 4.4 480 x 800, 720 x 1,280, (Android 3.x, Honeycomb not Supported) 768 x 1,280, 768 x 1,024, 1,080 x 1,920
MULTI V S has heat exchanger structure and diagonal shape of control box. (Efficiency increased up to 3%)
Control Box Cooling System
Heat Exchanger Technology
- Feature of control box is diagonal shape, it makes naturally air flowing (Directly pulling air back of the fan) - Reduced Heating / Cooling efficiency loss
- Heat exchanger structure - Optimal air flow by aluminum heat exchanger on control box. Heat Exchanger
With Home Network System Interlocking with home network system enables various application. Depending on building size and usage, various communication method can be given.
Compatibility to Home Network System
Air Flow
- Basic Control (On / Off, Mode, Setting Temp, Fan Speed) - Lock Function, Error Code
3rd Party Home Network System Security Control
Interlocking
Front View
BACnet LonWorks Modbus KNX Gateway Dry Contact RS485 Comm
Rear View
Lighting
Sub-phone Monitoring Sensors
Remote Controller * PI485 is embedded
LG
60
Solution
61
HP
4 Independent Unit
ARUN040GSS0
HP Model
Cooling
Nom
kW
12.1
Heating
Nom
kW
12.5
Cooling
Nom
kW
3.57
Heating
Nom
kW
2.91
EER 1)
Cooling
Nom
3.39
COP 1)
Heating
Nom
4.30
Nom
6.92
ESEER
Capacity Power Input 1)
ESEER Operation Range Compressor
Cooling
Min ~ Max °C DB
-5°C ~ 43°C
Heating
Min ~ Max °C WB
-20°C ~ 18°C
Type
BLDC Inverter Twin Rotary
Number of Compressor
1
Type Fan
DC Inverter motor
Max Static Pressure Airflow Rate Sound Pressure Sound Power
Refrigerant Oil
Piping Connection
Cooling
Nom
3.99
3.71
COP 1)
Heating
Nom
4.44
4.18
Nom
7.88
7.29
-5°C ~ 43°C
-5°C ~ 43°C
Operation Range Compressor
Fan
52
Cooling
Nom
dBA
66
WxHxD
mm
950 × 834 × 330
Dimensions
69
Net Weight
Control
cc
1,300
Ø / V / Hz
1 / 220~240 / 50, 60
No. x mm²
2C × 1.0~1.5
Total
Max
m
300
Actual Longest Piping Length 2)
Max
m
150 (175)
Min ~ Max °C DB
Heating
Min ~ Max °C WB
Type Number of Compressor Motor Type Max Static Pressure
dBA
FVC68D (PVE)
Cooling
Type
Nom
Transmission Cable (VCTF-SB)
Piping Level Difference
EER 1)
Heating
Power Supply
Piping Length
4.18 4.31
50
Type
15.5 18.0
3.51
dBA
1.8
14.0 16.0 3.60
Nom
kg
kW kW kW
Cooling
Charge
Nom Nom
kW
60
R410A
Cooling Heating
Nom
m3/min
kg
6 ARUN060GSS0
Nom
Max
Type
5 ARUN050GSS0
Cooling
3mmAq (30Pa)
Net Weight
Independent Unit
Heating
Power Input 1)
Cooling
Dimensions
Refrigerant
Capacity
Propeller fan
Motor Type
1Ø / 220V
1Ø 5HP, 6HP
Airflow Rate Sound Pressure Sound Power
Refrigerant Refrigerant Oil
-20°C ~ 18°C BLDC Inverter Twin Rotary
1
1
Propeller fan
Propeller fan
DC Inverter motor
DC Inverter motor
3mmAq (30Pa)
3mmAq (30Pa) 110
Cooling
Max
m3/min
110
Cooling
Nom
dBA
51
52
Heating
Nom
dBA
53
54
Nom
dBA
67
69
WxHxD
mm
950 × 1,380 × 330
950 × 1,380 × 330
Cooling
kg Type Charge
kg
Type Control
cc
Power Supply Transmission Cable (VCTF-SB) Piping Length
-20°C ~ 18°C BLDC Inverter Twin Rotary
94
94
R410A
R410A
3.0
3.0
FVC68D (PVE)
FVC68D (PVE)
1,300
1,300
Ø / V / Hz
1 / 220~240 / 50, 60
1 / 220~240 / 50, 60
No. x mm²
2C × 1.0~1.5
2C × 1.0~1.5
Total
Max
m
300
300
Actual Longest Piping Length 2)
Max
m
150 (175)
150 (175)
After 1st Y Branch
Max
m
40
After 1st Y Branch
Max
m
40
40
IDU - ODU 3)
Max
m
50
IDU - ODU 3)
Max
m
50
50
IDU - IDU
Max
m
15
IDU - IDU
Max
m
Liquid
mm (inch)
9.52 (3/8)
Gas
mm (inch)
15.88 (5/8)
Number of Outdoor Units Number of Connectable Indoor Units
Max
Ratio of the Connectable Indoor Units
Min ~ Max
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1) Eurovent Test Condition 2) ( ) is Equivalent Piping length 3) In case of outdoor unit installed upper than indoor unit (More detailed information, please refer to the “Installation of outdoor units” part in PDB) * 4HP Outdoor unit is not connectable with Hydro Kit * Due to our policy of innovation some specifications may be changed without notification.
Piping Level Difference Piping Connection
15
15
Liquid
mm (inch)
9.52 (3/8)
9.52 (3/8)
Gas
mm (inch)
15.88 (5/8)
19.05 (3/4)
1
Number of Outdoor Units
8
Number of Connectable Indoor Units
Max
50 ~ 160%
Ratio of the Connectable Indoor Units
Min ~ Max
1
1
10
13
50 ~ 160%
50 ~ 160%
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1) Eurovent Test Condition 2) ( ) is Equivalent Piping length 3) In case of outdoor unit installed upper than indoor unit (More detailed information, please refer to the “Installation of outdoor units” part in PDB) * 4HP Outdoor unit is not connectable with Hydro Kit * Due to our policy of innovation some specifications may be changed without notification.
MULTI V S
1Ø / 220V
1Ø 4HP
Model
ARUN050GSS0 / ARUN060GSS0
OUTDOOR UNIT
ARUN040GSS0
LG
62
Solution
63
HP Capacity
Independent Unit
4
5
6
ARUN040LSS0
ARUN050LSS0
ARUN060LSS0
Cooling
Nom
kW
12.1
14.0
15.5
Heating
Nom
kW
12.5
16.0
18.0
Cooling
Nom
kW
2.88
3.56
4.18
Heating
Nom
kW
2.76
3.60
4.31
EER 1)
Cooling
Nom
4.20
3.93
3.71
COP 1)
Heating
Nom
4.53
4.44
Nom
8.11
7.20
Power Input 1)
ESEER Operation Range Compressor
Fan Airflow Rate Sound Pressure Sound Power
Refrigerant Refrigerant Oil
Piping Connection
3.57
3.22
3.20
4.18
COP 1)
Heating
Nom
3.90
4.05
3.80
7.29
ESEER
Nom
7.05
6.58
6.38
BLDC Inverter Twin Rotary 1
Propeller fan
Propeller fan
Propeller fan
DC Inverter motor
DC Inverter motor
DC Inverter motor
3mmAq (30Pa)
3mmAq (30Pa)
3mmAq (30Pa)
Cooling
Max
m3/min
110
110
110
Cooling
Nom
dBA
50
51
52
Heating
Nom
dBA
52
53
54
Power Input 1)
Operation Range Compressor
Fan Airflow Rate Sound Pressure
dBA
66
67
69
mm
950 × 1,380 × 330
950 × 1,380 × 330
950 × 1,380 × 330
Dimensions Net Weight
96
96
96
R410A
R410A
3.0
3.0
3.0
FVC68D (PVE)
FVC68D (PVE)
FVC68D (PVE)
Control
1,300
1,300
1,300
Ø / V / Hz
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
No. x mm²
cc
2C × 1.0~1.5
2C × 1.0~1.5
2C × 1.0~1.5
Total
Max
m
300
300
300
Actual Longest Piping Length 2)
Max
m
150 (175)
150 (175)
150 (175)
Min ~ Max °C DB
-5°C ~ 43°C
-5°C ~ 43°C
-5°C ~ 43°C
Min ~ Max °C WB
-20°C ~ 18°C
-20°C ~ 18°C
-20°C ~ 18°C
Hermetically Sealed Scroll
Hermetically Sealed Scroll
Hermetically Sealed Scroll
1
1
1
Propeller fan
Propeller fan
Propeller fan
DC Inverter motor
DC Inverter motor
DC Inverter motor
3mmAq (30Pa)
3mmAq (30Pa)
3mmAq (30Pa) 190
Type Number of Compressor Motor Type Max Static Pressure
Nom
R410A
Cooling Heating
Type
WxHxD
Transmission Cable (VCTF-SB)
Piping Level Difference
Nom
1
Power Supply
Piping Length
9.66
Cooling
BLDC Inverter Twin Rotary
Type
33.6 36.7
EER 1)
1
kg
28.0 30.6
10.50
BLDC Inverter Twin Rotary
Charge
22.4 24.5
8.70
-5°C ~ 43°C
kg
kW kW
7.56
-20°C ~ 18°C
Type
Nom Nom
6.27
-5°C ~ 43°C
Net Weight
Cooling Heating
6.28
-20°C ~ 18°C
Cooling
12 ARUN120LSS0
kW
-5°C ~ 43°C
Dimensions
10 ARUN100LSS0
kW
-20°C ~ 18°C
Motor Type
8 ARUN080LSS0
Nom
Min ~ Max °C DB
Max Static Pressure
Capacity
Independent Unit
Nom
Min ~ Max °C WB
Type
Model
Cooling
Cooling
Number of Compressor
HP
Heating
Heating Type
3Ø / 380V
3Ø 8HP, 10HP, 12HP
Sound Power
Refrigerant Refrigerant Oil
Cooling
Max
m3/min
140
190
Cooling
Nom
dBA
57
58
60
Heating
Nom
dBA
57
58
60
Cooling
Nom
dBA
74
77
78
WxHxD
mm
950 × 1,380 × 330
1,090 x 1,625 x 380
1,090 x 1,625 x 380
kg Type Charge
kg
Type Control
cc
Power Supply Transmission Cable (VCTF-SB) Piping Length
115
144
157
R410A
R410A
R410A
3.5
4.5
6.0
FVC68D (PVE)
FVC68D (PVE)
FVC68D (PVE)
2,400
2,600
3,400
Ø / V / Hz
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
3 / 380~415 / 50, 60
No. x mm²
2C × 1.0~1.5
2C × 1.0~1.5
2C × 1.0~1.5
Total
Max
m
300
300
300
Actual Longest Piping Length 2)
Max
m
150 (175)
150 (175)
150 (175) 40
After 1st Y Branch
Max
m
40
40
40
After 1st Y Branch
Max
m
40
40
IDU - ODU 3)
Max
m
50
50
50
IDU - ODU 3)
Max
m
50
50
50
IDU - IDU
Max
m
15
15
15
IDU - IDU
Max
m
15
15
15
Liquid
mm (inch)
9.52 (3/8)
9.52 (3/8)
9.52 (3/8)
Gas
mm (inch)
15.88 (5/8)
15.88 (5/8)
19.05 (3/4)
Number of Outdoor Units Number of Connectable Indoor Units
Max
Ratio of the Connectable Indoor Units
Min ~ Max
Piping Level Difference Piping Connection
Liquid
mm (inch)
9.52 (3/8)
9.52 (3/8)
12.7 (1/2)
Gas
mm (inch)
19.05 (3/4)
22.2 (7/8)
28.58 (1-1/8)
1
1
1
Number of Outdoor Units
8
10
13
Number of Connectable Indoor Units
Max
50 ~ 160%
50 ~ 160%
50 ~ 160%
Ratio of the Connectable Indoor Units
Min ~ Max
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1) Eurovent Test Condition 2) ( ) is Equivalent Piping length 3) In case of outdoor unit installed upper than indoor unit (More detailed information, please refer to the “Installation of outdoor units” part in PDB) * 4HP Outdoor unit is not connectable with Hydro Kit * Due to our policy of innovation some specifications may be changed without notification.
1
1
1
13
16
20
50 ~ 160%
50 ~ 160%
50 ~ 160%
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1) Eurovent Test Condition 2) ( ) is Equivalent Piping length 3) In case of outdoor unit installed upper than indoor unit (More detailed information, please refer to the “Installation of outdoor units” part in PDB) * 4HP Outdoor unit is not connectable with Hydro Kit * Due to our policy of innovation some specifications may be changed without notification.
MULTI V S
3Ø / 380V
3Ø 4HP, 5HP, 6HP
Model
ARUN080LSS0 / ARUN100LSS0 / ARUN120LSS0
OUTDOOR UNIT
ARUN040LSS0 / ARUN050LSS0 / ARUN060LSS0
Solution
LG
64
65
OUTDOOR UNIT
OUTDOOR UNIT
MULTI V WATER IV
Heat Pump / Heat recovery 300m Total piping length
Superior Efficiency via Integration of Smart Technologies
1. Compact Size
1m3 per each 20HP
1m
Height difference between IDU~IDU
Service Area
Along with outstanding energy efficiency, the new solution comes with a range of truly smart features, including optimized cycle composition and smart control. For ease of installation and better economy of space, MULTI V WATER IV is both lighter in weight and smaller in overall size. LG, a leading innovator in HVAC technologies, will continue to develop and manufacture high performance, energy efficient solutions for the benefit of its growing global customer-base.
1.1m
0.9m
2. Light Weight
150m
127kg
50m
Longest piping length
Height difference between ODU~IDU
* Based on the tested by 10HP model : ARWN100LAS4
154kg
MULTI V WATER IV
Previous Model
15% Reduced
* Based on 10HP
3. Variable Water Flow Control Kit Variable Water Flow Control Valve DC 0 ~10V
Cooling Tower
Geothermal River / Sea
Adopting a water-based cooling method, this unit optimizes performance in comparison to compressor capacity. It also ensures heat exchange performance for high-rise buildings, thus allowing electrical-savings. 2000 1800 1600 1400 1200 1,000 800 600 400 200
Average Saving
12%
Previous Model
Source : LG Energy Estimate Program (LEEP) simulation data-5th floor building in Paris, France
MULTI V WATER IV
High Efficiency System Regardless of External Conditions Regardless of outdoor temperature and other environmental conditions, MULTI V WATER IV is the optimal solution for high-rise buildings.
Benefit • Saves valuable floor space • Low noise level (No fans)
Inverter Pump
Economical, Highly Efficient System Power Input (kWh)
40m
• Flexible design applications • High efficient water source system
Application • Large scale office • Commercial building using geothermal / Water supply • Luxurious residential building
Outside Temp.
Wind
WATER IV Heat Pump / Heat Recovery
Require Installation Space
Today’s businesses demand highly efficient temperature control solutions, capable of providing optimal energy savings without sacrificing performance. When it comes to cooling and heating a multi-storey or high-rise building, water cooled HVAC systems have become the solution of choice. Offering several performance enhancements and greater installation versatility, LG’s MULTI V WATER IV combines intelligent functions with advanced inverter technology; boosting both energy efficiency and operational range. This superior water cooled system significantly improves return on investment (ROI) with a stellar 5.9 coefficient of performance (COP) and an equally impressive independent part load value (IPLV) of *6.73.
66
Solution
LG
67
PERFORMANCE
Designed to maximize energy efficiency for high-rise building
Stable performance and long life are ensured irrespective of environmental changes, in addition to high-speed cooling and heating
Minimizing Energy Input
With a fourth generation inverter compressor, the MULTI V WATER IV boasts top-class energy efficiency.
Through water sourced heat recovery system, minimizing not only outside unit power input but also external energy input such as cooling tower and boiler.
Extended Compressor Speed 20Hz ~ 140Hz
10% 5.5 5.0
5% 1% 1% 1% 1%
- Rapid operation response - Capable of reaching required temperature quickly - Increase part load efficiency
HEX Optimization Cycle Composition Improvement Inverter Control Active Oil Control
WATER IV Heat Pump / Heat Recovery
Efficiency (EER)
LG’s 4th Generation Inverter Compressor
Energy saving by heat recovery unit
HiPORTM (High Pressure Oil Return)
HIPOR™
- Eliminating loss in suction gas by returning oil directly to compressor - Resolve compressor efficiency loss caused by oil return
Heating based Simultaneous operation External energy saving by between heat recovery system
Smart Oil Return - Oil recovery occurs only when required - Enhanced compressor reliability & user comfort
Previous Model MULTI V WATER IV * Comparison between 10HP in cooling mode
Variable Water Flow Control Kit (Option)
Cooling based Simultaneous operation
Variable Water Flow Control Valve DC 0 ~10V
Cooling Tower
Geothermal
River / Sea
Total Water Flow (m3)
The world’s first variable water flow control system for water cooled VRF system. LG applied variable water flow control system to reduce circulation pump energy consumption, by controlling embedded kit. - Adjust water flow by pressure control after connecting PCB in the existing MULTI V Water Outdoor unit
Largest Capacity
71%
Providing 8 ~ 20HP with single unit, and up to the world’s largest capacity 80HP by combination.
15,456
Line up (HP)
4,439 Inverter Pump
Constant Water Flow
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42 ~ 60
62 ~ 80
3 Units
4 Units
LG 1 Unit
2 Units
Variable Water Flow
Note 1. Location : France 2. Total operationn time : 1,344hr 3. Indoor temperature : Normal office environment 4. Outdoor temperature : Average summer temperature 5. Inlet flow temperature : Approximately 30°C
Company B
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1 Unit 2 Unit
Company C
3 Unit
1 Unit 2 Unit
3 Unit
OUTDOOR UNIT
EFFICIENCY
LG
Solution
68
69
OUTDOOR UNIT
FLEXIBLE DESIGN Easy design with the most convenient features
Longest Piping Length
Compact Size
Provide flexible installation up to 300m of total piping length. As water pipes are not connected to indoor units, users are free from leakage problems.
The optimal design of the compact, lightweight outdoor unit enables double stacking, which results in 50% savings in installation space.
MULTI V WATER IV Total Piping Length
300m
Actual longest piping length (Equivalent)
150m (175m)
WATER IV Heat Pump / Heat Recovery
Height difference 50m
Company B
Longest piping length after 1st branch 40m (Conditional application) (90m)
Longest piping length after 1st branch
Height difference between ODU ~ IDU
50m
Height difference between IDU ~ IDU
40m
Height between IDU
20HP × 2EA
10HP × 4EA
755 × 500
1,560 × 550
Per Each
Per Each
* 40HP Capacity Installation scene
* Double stacking floor area ** 40HP Capacity Installation scene
MULTI V WATER IV System for Geothermal Applications
Light Weight
Uses underground heat sources such as soil, ground water, lake, river, etc. as renewable energy for cooling and Heating of a building. Water or antifreeze solution is circulated through the closed loop HDPE (High Density Poly-Ethylene) pipes buried beneath the earth’s surface. It is a highly efficient and eco-friendly MULTI V system.
Easier to transport and install thanks to 13% reduction in unit size and 15% reduction in overall weight.
127kg MULTI V WATER IV
- The Circulating water temperature range is between -5°C ~ 45°C - Antifreeze should be applied depending on the application. * Please contact local LG office for application availability.
15%
Reduced
154kg Previous Model
Machine Room Pump
* Based on 10HP
MULTI V WATER IV Under Ground HEX
LG
Solution
70
71
Model Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Combination Unit Independent Unit Cooling Heating Cooling Heating Cooling Heating Cooling Heating Type Number of Compressor Cooling Heating Cooling Heating
Dimensions Net Weight Refrigerant Refrigerant Oil
Nom Nom Nom Nom
Min ~ Max °C DB Min ~ Max °C WB
Nom Nom Nom Nom WxHxD
Type Charge Type Control
Piping Level Difference Piping Connection
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units
Heat Exchanger
Water Connection Pipe
dBA dBA dBA dBA mm kg kg
Power Supply Transmission Cable (VCTF-SB) Piping Length
kW kW kW kW
Max Max Max Max Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch)
Max Min ~ Max Type Pressure Resistance Rated Water Flow Head Loss Inlet Outlet Drain Outlet
Max
kgf/cm² L/min kPa mm mm mm
8
10
12
ARWN080LAS4 ARWN080LAS4 22.4 25.2 3.86 4.20 5.80 6.00 7.77 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 1 47 51 59 63 (755 × 997 × 500) × 1 127 x 1 R410A 5.8 FVC68D (PVE) 1,800 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 9.52 (3/8) 22.2 (7/8) 1 20 50 ~ 200% Stainless Steel Plate 45 77 11 PT 40 PT 40 20
ARWN100LAS4 ARWN100LAS4 28.0 31.5 5.09 5.34 5.50 5.90 7.71 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 1 50 53 62 65 (755 × 997 × 500) × 1 127 x 1 R410A 5.8 FVC68D (PVE) 1,800 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 9.52 (3/8) 22.2 (7/8) 1 25 50 ~ 200% Stainless Steel Plate 45 96 16 PT 40 PT 40 20
ARWN120LAS4 ARWN120LAS4 33.6 37.8 6.46 6.75 5.20 5.60 7.26 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 1 56 56 68 68 (755 × 997 × 500) × 1 127 x 1 R410A 5.8 FVC68D (PVE) 1,800 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 12.7 (1/2) 25.4 (1) 1 30 50 ~ 200% Stainless Steel Plate 45 116 22 PT 40 PT 40 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
HP Model Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
14 Combination Unit Independent Unit Cooling Heating Cooling Heating Cooling Heating Cooling Heating Type Number of Compressor Cooling Heating Cooling Heating
Dimensions Net Weight Refrigerant Refrigerant Oil
Nom Nom Nom Nom
Min ~ Max °C DB Min ~ Max °C WB
Nom Nom Nom Nom WxHxD
Type Charge Type Control
Piping Level Difference Piping Connection
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units
Heat Exchanger
Water Connection Pipe
dBA dBA dBA dBA mm kg kg
Power Supply Transmission Cable (VCTF-SB) Piping Length
kW kW kW kW
Max Max Max Max Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch)
Max Min ~ Max Type Pressure Resistance Rated Water Flow Head Loss Inlet Outlet Drain Outlet
Max
kgf/cm² L/min kPa mm mm mm
16
18
20
ARWN140LAS4 ARWN160LAS4 ARWN180LAS4 ARWN200LAS4 ARWN140LAS4 ARWN160LAS4 ARWN180LAS4 ARWN200LAS4 39.2 44.8 50.4 56.0 44.1 50.4 56.7 63.0 7.84 8.15 9.69 11.20 8.17 8.54 10.13 11.67 5.00 5.50 5.20 5.00 5.40 5.90 5.60 5.40 6.96 7.18 7.10 7.02 10°C ~ 45°C 10°C ~ 45°C 10°C ~ 45°C 10°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll Hermetically Sealed Scroll Hermetically Sealed Scroll Hermetically Sealed Scroll 1 1 1 1 58 53 55 54 57 57 56 60 70 65 67 66 69 69 68 72 (755 × 997 × 500) × 1 (755 × 997 × 500) × 1 (755 × 997 × 500) × 1 (755 × 997 × 500) × 1 127 x 1 140 x 1 140 x 1 140 x 1 R410A R410A R410A R410A 5.8 3.0 3.0 3.0 FVC68D (PVE) FVC68D (PVE) FVC68D (PVE) FVC68D (PVE) 1,800 1,800 1,800 1,800 3 / 380-415 / 50, 60 3 / 380-415 / 50, 60 3 / 380-415 / 50, 60 3 / 380-415 / 50, 60 2C × 1.0~1.5 2C × 1.0~1.5 2C × 1.0~1.5 2C × 1.0~1.5 300 300 300 300 150 150 150 150 40 40 40 40 50 50 50 50 40 40 40 40 12.7 (1/2) 12.7 (1/2) 12.7 (1/2) 12.7 (1/2) 25.4 (1) 28.58 (1-1/8) 28.58 (1-1/8) 28.58 (1-1/8) 1 1 1 1 35 40 45 50 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200% Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate 45 45 45 45 135 154 173 192 29 20 25 31 PT 40 PT 40 PT 40 PT 40 PT 40 PT 40 PT 40 PT 40 20 20 20 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
WATER IV Heat Pump / Heat Recovery
HP
ARWN140LAS4 / ARWN160LAS4 ARWN180LAS4 / ARWN200LAS4
OUTDOOR UNIT
ARWN080LAS4 / ARWN100LAS4 / ARWN120LAS4
LG
Solution
72
73
Combination Unit Model
Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom
Cooling Heating Type Number of Compressor Cooling Heating Cooling Heating
Min ~ Max °C DB Min ~ Max °C WB
Dimensions Net Weight Refrigerant Refrigerant Oil
Nom Nom Nom Nom WxHxD
Type Charge Type Control
Piping Level Difference Piping Connection
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units
Heat Exchanger
Water Connection Pipe
dBA dBA dBA dBA mm kg kg
Power Supply Transmission Cable (VCTF-SB) Piping Length
kW kW kW kW
Max Max Max Max Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch)
Max Min ~ Max Type Pressure Resistance Rated Water Flow Head Loss Inlet Outlet Drain Outlet
Max
kgf/cm² L/min kPa mm mm mm
22
24
ARWN220LAS4 ARWN120LAS4 ARWN100LAS4 61.6 69.3 11.55 12.09 5.33 5.73 7.34 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 57 57 70 70 (755 × 997 × 500) x 2 127 x 2 R410A 5.8 + 5.8 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 34.9 (1-3/8) 2 44 50 ~ 160% Stainless Steel Plate 45 116 + 96 22 + 16 PT 40 + PT 40 PT 40 + PT 40 20
ARWN240LAS4 ARWN120LAS4 ARWN120LAS4 67.2 75.6 12.92 13.50 5.20 5.60 7.21 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 57 57 70 70 (755 × 997 × 500) x 2 127 x 2 R410A 5.8 + 5.8 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 34.9 (1-3/8) 2 48 50 ~ 160% Stainless Steel Plate 45 116 + 116 22 + 22 PT 40 + PT 40 PT 40 + PT 40 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
HP Combination Unit Model
Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom
Cooling Heating Type Number of Compressor Cooling Heating Cooling Heating
Min ~ Max °C DB Min ~ Max °C WB
Dimensions Net Weight Refrigerant Refrigerant Oil
Nom Nom Nom Nom WxHxD
Type Charge Type Control
Piping Level Difference Piping Connection
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units
Heat Exchanger
Water Connection Pipe
dBA dBA dBA dBA mm kg kg
Power Supply Transmission Cable (VCTF-SB) Piping Length
kW kW kW kW
Max Max Max Max Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch)
Max Min ~ Max Type Pressure Resistance Rated Water Flow Head Loss Inlet Outlet Drain Outlet
Max
kgf/cm² L/min kPa mm mm mm
26
28
ARWN260LAS4 ARWN140LAS4 ARWN120LAS4 72.8 81.9 14.30 14.92 5.09 5.49 7.11 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 59 58 72 71 (755 × 997 × 500) x 2 127 x 2 R410A 5.8 + 5.8 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 34.9 (1-3/8) 2 52 50 ~ 160% Stainless Steel Plate 45 135 + 116 29 + 22 PT 40 + PT 40 PT 40 + PT 40 20
ARWN280LAS4 ARWN140LAS4 ARWN140LAS4 78.4 88.2 15.68 16.34 5.00 5.40 7.02 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 59 58 72 71 (755 × 997 × 500) x 2 127 x 2 R410A 5.8 + 5.8 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 34.9 (1-3/8) 2 56 50 ~ 160% Stainless Steel Plate 45 135 + 135 29 + 29 PT 40 + PT 40 PT 40 + PT 40 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
WATER IV Heat Pump / Heat Recovery
HP
ARWN260LAS4 / ARWN280LAS4
OUTDOOR UNIT
ARWN220LAS4 / ARWN240LAS4
LG
Solution
74
75
Combination Unit Model
Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom
Cooling Heating Type Number of Compressor Cooling Heating Cooling Heating
Min ~ Max °C DB Min ~ Max °C WB
Dimensions Net Weight Refrigerant Refrigerant Oil
Nom Nom Nom Nom WxHxD
Type Charge Type Control
Piping Level Difference Piping Connection
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units
Heat Exchanger
Water Connection Pipe
dBA dBA dBA dBA mm kg kg
Power Supply Transmission Cable (VCTF-SB) Piping Length
kW kW kW kW
Max Max Max Max Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch)
Max Min ~ Max Type Pressure Resistance Rated Water Flow Head Loss Inlet Outlet Drain Outlet
Max
kgf/cm² L/min kPa mm mm mm
30
32
34
ARWN300LAS4 ARWN160LAS4 ARWN140LAS4 84.0 94.5 15.99 16.71 5.25 5.66 7.12 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 59 58 72 71 (755 × 997 × 500) x 2 (127 x 1) + (140 x 1) R410A 3.0 + 5.8 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 34.9 (1-3/8) 2 60 50 ~ 160% Stainless Steel Plate 45 154 + 135 20 + 29 PT 40 + PT 40 PT 40 + PT 40 20
ARWN320LAS4 ARWN180LAS4 ARWN140LAS4 89.6 100.8 17.53 18.30 5.11 5.51 7.07 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 59 58 72 71 (755 × 997 × 500) x 2 (127 x 1) + (140 x 1) R410A 3.0 + 5.8 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 34.9 (1-3/8) 2 64 50 ~ 160% Stainless Steel Plate 45 173 + 135 25 + 29 PT 40 + PT 40 PT 40 + PT 40 20
ARWN340LAS4 ARWN200LAS4 ARWN140LAS4 95.2 107.1 19.04 19.84 5.00 5.40 7.01 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 59 61 72 74 (755 × 997 × 500) x 2 (127 x 1) + (140 x 1) R410A 3.0 + 5.8 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 34.9 (1-3/8) 2 64 50 ~ 160% Stainless Steel Plate 45 192 + 135 31 + 29 PT 40 + PT 40 PT 40 + PT 40 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
HP Combination Unit Model
Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom
Cooling Heating Type Number of Compressor Cooling Heating Cooling Heating
Min ~ Max °C DB Min ~ Max °C WB
Dimensions Net Weight Refrigerant Refrigerant Oil
Nom Nom Nom Nom WxHxD
Type Charge Type Control
Piping Level Difference Piping Connection
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units
Heat Exchanger
Water Connection Pipe
dBA dBA dBA dBA mm kg kg
Power Supply Transmission Cable (VCTF-SB) Piping Length
kW kW kW kW
Max Max Max Max Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch)
Max Min ~ Max Type Pressure Resistance Rated Water Flow Head Loss Inlet Outlet Drain Outlet
Max
kgf/cm² L/min kPa mm mm mm
36
38
40
ARWN360LAS4 ARWN180LAS4 ARWN180LAS4 100.8 113.4 19.38 20.26 5.20 5.60 7.11 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 56 57 69 70 (755 × 997 × 500) x 2 140 x 2 R410A 3.0 + 3.0 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 2 64 50 ~ 160% Stainless Steel Plate 45 173 + 173 25 + 25 PT 40 + PT 40 PT 40 + PT 40 20
ARWN380LAS4 ARWN200LAS4 ARWN180LAS4 106.4 119.7 20.89 21.80 5.09 5.49 7.06 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 56 61 69 74 (755 × 997 × 500) x 2 140 x 2 R410A 3.0 + 3.0 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 2 64 50 ~ 160% Stainless Steel Plate 45 192 + 173 31 + 25 PT 40 + PT 40 PT 40 + PT 40 20
ARWN400LAS4 ARWN200LAS4 ARWN200LAS4 112.0 126.0 22.40 23.34 5.00 5.40 7.01 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 55 61 68 74 (755 × 997 × 500) x 2 140 x 2 R410A 3.0 + 3.0 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 2 64 50 ~ 160% Stainless Steel Plate 45 192 + 192 31 + 31 PT 40 + PT 40 PT 40 + PT 40 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
WATER IV Heat Pump / Heat Recovery
HP
ARWN360LAS4 / ARWN380LAS4 / ARWN400LAS4
OUTDOOR UNIT
ARWN300LAS4 / ARWN320LAS4 / ARWN340LAS4
LG
Solution
76
77
Combination Unit Model
Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom
Cooling Heating
Min ~ Max °C DB Min ~ Max °C WB
Type Number of Compressor Cooling Heating Cooling Heating
Dimensions
Nom Nom Nom Nom
Refrigerant Oil
dBA dBA dBA dBA
W x H x D mm
Net Weight Refrigerant
kW kW kW kW
kg Type Charge Type Control
kg cc
Power Supply
Ø / V / Hz
Transmission Cable (VCTF-SB)
No. x mm² m m m m m mm (inch) mm (inch)
Piping Length Piping Level Difference Piping Connection
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units
Max Max Max Max Max
Max Min ~ Max Type
Heat Exchanger
Water Connection Pipe
Pressure Resistance Rated Water Flow Head Loss Inlet Outlet Drain Outlet
Max
kgf/cm² L/min kPa mm mm mm
42
44
46
48
50
ARWN420LAS4 ARWN200LAS4 ARWN120LAS4 ARWN100LAS4 117.6 132.3 22.75 23.76 5.17 5.57 7.18 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 3 58 62 72 76 (755 × 997 × 500) x 3 (140 x 1) + (127 X 2) R410A 3.0 + 5.8 + 5.8 FVC68D (PVE) 5,400 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 3 64 50 ~ 130% Stainless Steel Plate 45 192 + 116 + 96 31 + 22 + 16 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 20
ARWN440LAS4 ARWN200LAS4 ARWN120LAS4 ARWN120LAS4 123.2 138.6 24.12 25.17 5.11 5.51 7.12 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 3 58 62 72 76 (755 × 997 × 500) x 3 (140 x 1) + (127 X 2) R410A 3.0 + 5.8 + 5.8 FVC68D (PVE) 5,400 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 3 64 50 ~ 130% Stainless Steel Plate 45 192 + 116 + 116 31 + 22 + 22 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 20
ARWN460LAS4 ARWN200LAS4 ARWN140LAS4 ARWN120LAS4 128.8 144.9 25.50 26.59 5.05 5.45 7.06 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 3 60 62 74 76 (755 × 997 × 500) x 3 (140 x 1) + (127 X 2) R410A 3.0 + 5.8 + 5.8 FVC68D (PVE) 5,400 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 3 64 50 ~ 130% Stainless Steel Plate 45 192 + 135 + 116 31 + 29 + 22 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 20
ARWN480LAS4 ARWN200LAS4 ARWN140LAS4 ARWN140LAS4 134.4 151.2 26.88 28.01 5.00 5.40 7.01 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 3 60 62 74 76 (755 × 997 × 500) x 3 (140 x 1) + (127 X 2) R410A 3.0 + 5.8 + 5.8 FVC68D (PVE) 5,400 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 3 64 50 ~ 130% Stainless Steel Plate 45 192 + 135 + 135 31 + 29 + 29 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 20
ARWN500LAS4 ARWN200LAS4 ARWN160LAS4 ARWN140LAS4 140.0 157.5 27.19 28.38 5.15 5.55 7.07 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 3 60 62 74 76 (755 × 997 × 500) x 3 (140 x 2) + (127 X 1) R410A 3.0 + 3.0 + 5.8 FVC68D (PVE) 5,400 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 3 64 50 ~ 130% Stainless Steel Plate 45 192 + 154 + 135 31 + 20 + 29 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
HP Combination Unit Model
Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom
Cooling Heating
Min ~ Max °C DB Min ~ Max °C WB
Type Number of Compressor Cooling Heating Cooling Heating
Dimensions
Nom Nom Nom Nom
Refrigerant Oil
kg Type Charge Type Control
kg cc
Power Supply
Ø / V / Hz
Transmission Cable (VCTF-SB) Piping Length Piping Level Difference Piping Connection
dBA dBA dBA dBA
W x H x D mm
Net Weight Refrigerant
kW kW kW kW
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units
Max Max Max Max Max
No. x mm² m m m m m mm (inch) mm (inch)
Max Min ~ Max Type
Heat Exchanger
Water Connection Pipe
Pressure Resistance Rated Water Flow Head Loss Inlet Outlet Drain Outlet
Max
kgf/cm² L/min kPa mm mm mm
52
54
ARWN520LAS4 ARWN200LAS4 ARWN180LAS4 ARWN140LAS4 145.6 163.8 28.73 29.97 5.07 5.47 7.04 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 3 60 62 74 76 (755 × 997 × 500) x 3 (140 x 2) + (127 X 1) R410A 3.0 + 3.0 + 5.8 FVC68D (PVE) 5,400 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 3 64 50 ~ 130% Stainless Steel Plate 45 192 + 173 + 135 31 + 25 + 29 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 20
ARWN540LAS4 ARWN200LAS4 ARWN200LAS4 ARWN140LAS4 151.2 170.1 30.24 31.51 5.00 5.40 7.01 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 3 60 62 74 76 (755 × 997 × 500) x 3 (140 x 2) + (127 X 1) R410A 3.0 + 3.0 + 5.8 FVC68D (PVE) 5,400 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 3 64 50 ~ 130% Stainless Steel Plate 45 192 + 192 + 135 31 + 31 + 29 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 20
56
58
60
ARWN560LAS4 ARWN580LAS4 ARWN600LAS4 ARWN200LAS4 ARWN200LAS4 ARWN200LAS4 ARWN180LAS4 ARWN200LAS4 ARWN200LAS4 ARWN180LAS4 ARWN180LAS4 ARWN200LAS4 156.8 162.4 168.0 176.4 182.7 189.0 30.58 32.09 33.60 31.93 33.47 35.01 5.13 5.06 5.00 5.52 5.46 5.40 7.07 7.04 7.01 10°C ~ 45°C 10°C ~ 45°C 10°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C Hermetically Hermetically Hermetically Sealed Scroll Sealed Scroll Sealed Scroll 3 3 3 57 57 56 62 62 62 71 71 70 76 76 76 (755 × 997 (755 × 997 (755 × 997 × 500) x 3 × 500) x 3 × 500) x 3 140 x 3 140 x 3 140 x 3 R410A R410A R410A 3.0 + 3.0 + 3.0 3.0 + 3.0 + 3.0 3.0 + 3.0 + 3.0 FVC68D (PVE) FVC68D (PVE) FVC68D (PVE) 5,400 5,400 5,400 3 / 380-415 / 3 / 380-415 / 3 / 380-415 / 50, 60 50, 60 50, 60 2C × 1.0~1.5 2C × 1.0~1.5 2C × 1.0~1.5 300 300 300 150 150 150 40 40 40 50 50 50 40 40 40 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 41.3 (1-5/8) 41.3 (1-5/8) 41.3 (1-5/8) 3 3 3 64 64 64 50 ~ 130% 50 ~ 130% 50 ~ 130% Stainless Stainless Stainless Steel Plate Steel Plate Steel Plate 45 45 45 192 + 173 + 173 192 + 192+ 173 192 + 192+ 192 31 + 25 + 25 31 + 31 + 25 31 + 31 + 31 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 20 20 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
WATER IV Heat Pump / Heat Recovery
HP
ARWN520LAS4 / ARWN540LAS4 / ARWN560LAS4 ARWN580LAS4 / ARWN600LAS4
OUTDOOR UNIT
ARWN420LAS4 / ARWN440LAS4 / ARWN460LAS4 ARWN480LAS4 / ARWN500LAS4
LG
Solution
78
79
Combination Unit Model
Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom
Cooling Heating
Min ~ Max °C DB Min ~ Max °C WB
Type Number of Compressor Cooling Heating Cooling Heating
Dimensions
Nom Nom Nom Nom
Refrigerant Oil
dBA dBA dBA dBA
W x H x D mm
Net Weight Refrigerant
kW kW kW kW
kg Type Charge Type Control
kg cc
Power Supply
Ø / V / Hz
Transmission Cable (VCTF-SB)
No. x mm² m m m m m mm (inch) mm (inch)
Piping Length Piping Level Difference Piping Connection
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units
Max Max Max Max Max
Max Min ~ Max Type
Heat Exchanger
Water Connection Pipe
Pressure Resistance
Max
kgf/cm²
Rated Water Flow
L/min
Head Loss
kPa
Inlet
mm
Outlet
mm
Drain Outlet
mm
62
64
66
ARWN620LAS4 ARWN200LAS4 ARWN200LAS4 ARWN120LAS4 ARWN100LAS4 173.6 195.3 33.95 35.43 5.11 5.51 7.12 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 4 59 63 73 77 (755 × 997 × 500) x 4 (140 x 2) + (127 x 2) R410A 3.0 + 3.0 + 5.8 + 5.8 FVC68D (PVE) 7,200 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 22.2 (7/8) 44.5 (1-3/4) 4 64 50 ~ 130% Stainless Steel Plate 45 192 + 192 + 116 + 96 31 + 31 + 22 + 16 PT 40 + PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 + PT 40 20
ARWN640LAS4 ARWN200LAS4 ARWN200LAS4 ARWN120LAS4 ARWN120LAS4 179.2 201.6 35.32 36.84 5.07 5.47 7.08 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 4 59 63 73 77 (755 × 997 × 500) x 4 (140 x 2) + (127 x 2) R410A 3.0 + 3.0 + 5.8 + 5.8 FVC69D (PVE) 7,200 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 22.2 (7/8) 44.5 (1-3/4) 4 64 50 ~ 130% Stainless Steel Plate 45 192 + 192 + 116 + 116 31 + 31 + 22 + 22 PT 40 + PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 + PT 40 20
ARWN660LAS4 ARWN200LAS4 ARWN200LAS4 ARWN140LAS4 ARWN120LAS4 184.8 207.9 36.70 38.26 5.04 5.43 7.04 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 4 61 63 75 77 (755 × 997 × 500) x 4 (140 x 2) + (127 x 2) R410A 3.0 + 3.0 + 5.8 + 5.8 FVC70D (PVE) 7,200 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 22.2 (7/8) 53.98 (2-1/8) 4 64 50 ~ 130% Stainless Steel Plate 45 192 + 192 + 135 + 116 31 + 31 + 29 + 22 PT 40 + PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 + PT 40 20
68
70
ARWN680LAS4 ARWN700LAS4 ARWN200LAS4 ARWN200LAS4 ARWN200LAS4 ARWN200LAS4 ARWN140LAS4 ARWN160LAS4 ARWN140LAS4 ARWN140LAS4 190.4 196.0 214.2 220.5 38.08 38.39 39.68 40.05 5.00 5.11 5.40 5.51 7.01 7.05 10°C ~ 45°C 10°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C Hermetically Hermetically Sealed Scroll Sealed Scroll 4 4 61 61 63 63 75 75 77 77 (755 × 997 (755 × 997 × 500) x 4 × 500) x 4 (140 x 2) + (127 x 2) (140 x 3) + (127 x 1) R410A R410A 3.0 + 3.0 + 5.8 + 5.8 3.0 + 3.0 + 3.0 + 5.8 FVC71D (PVE) FVC72D (PVE) 7,200 7,200 3 / 380-415 / 3 / 380-415 / 50, 60 50, 60 2C × 1.0~1.5 2C × 1.0~1.5 300 300 150 150 40 40 50 50 40 40 22.2 (7/8) 22.2 (7/8) 53.98 (2-1/8) 53.98 (2-1/8) 4 4 64 64 50 ~ 130% 50 ~ 130% Stainless Stainless Steel Plate Steel Plate 45 45 192 + 192 192 + 192 + 135 + 135 + 154 + 135 31 + 31 + 29 + 29 31 + 31 + 20 + 29 PT 40 + PT 40 PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 20 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
HP Combination Unit Model
Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom
Cooling Heating
Min ~ Max °C DB Min ~ Max °C WB
Type Number of Compressor Cooling Heating Cooling Heating
Dimensions
Nom Nom Nom Nom
Refrigerant Oil
kg Type Charge Type Control
kg cc
Power Supply
Ø / V / Hz
Transmission Cable (VCTF-SB) Piping Length Piping Level Difference Piping Connection
dBA dBA dBA dBA
W x H x D mm
Net Weight Refrigerant
kW kW kW kW
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units
Max Max Max Max Max
No. x mm² m m m m m mm (inch) mm (inch)
Max Min ~ Max Type
Heat Exchanger
Water Connection Pipe
Pressure Resistance
Max
kgf/cm²
Rated Water Flow
L/min
Head Loss
kPa
Inlet
mm
Outlet
mm
Drain Outlet
mm
72
74
ARWN720LAS4 ARWN200LAS4 ARWN200LAS4 ARWN180LAS4 ARWN140LAS4 201.6 226.8 39.93 41.64 5.05 5.45 7.03 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 4 61 63 75 77 (755 × 997 × 500) x 4 (140 x 3) + (127 x 1) R410A 3.0 + 3.0 + 3.0 + 5.8 FVC73D (PVE) 7,200 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 22.2 (7/8) 53.98 (2-1/8) 4 64 50 ~ 130% Stainless Steel Plate 45 192 + 192 + 173 + 135 31 + 31 + 25 + 29 PT 40 + PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 + PT 40 20
ARWN740LAS4 ARWN200LAS4 ARWN200LAS4 ARWN200LAS4 ARWN140LAS4 207.2 233.1 41.44 43.18 5.00 5.40 7.01 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 4 61 63 75 77 (755 × 997 × 500) x 4 (140 x 3) + (127 x 1) R410A 3.0 + 3.0 + 3.0 + 5.8 FVC74D (PVE) 7,200 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 22.2 (7/8) 53.98 (2-1/8) 4 64 50 ~ 130% Stainless Steel Plate 45 192 + 192 + 192 + 135 31 + 31 + 31 + 29 PT 40 + PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 + PT 40 20
76
78
80
ARWN760LAS4 ARWN780LAS4 ARWN800LAS4 ARWN200LAS4 ARWN200LAS4 ARWN200LAS4 ARWN200LAS4 ARWN200LAS4 ARWN200LAS4 ARWN180LAS4 ARWN200LAS4 ARWN200LAS4 ARWN180LAS4 ARWN180LAS4 ARWN200LAS4 212.8 218.4 224.0 239.4 245.7 252.0 41.78 43.29 44.80 43.60 45.14 46.68 5.09 5.05 5.00 5.49 5.44 5.40 7.05 7.03 7.01 10°C ~ 45°C 10°C ~ 45°C 10°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C Hermetically Hermetically Hermetically Sealed Scroll Sealed Scroll Sealed Scroll 4 4 4 58 58 57 63 63 63 72 72 71 77 77 77 (755 × 997 (755 × 997 (755 × 997 × 500) x 4 × 500) x 4 × 500) x 4 140 x 4 140 x 4 140 x 4 R410A R410A R410A 3.0 + 3.0 + 3.0 + 3.0 3.0 + 3.0 + 3.0 + 3.0 3.0 + 3.0 + 3.0 + 3.0 FVC75D (PVE) FVC76D (PVE) FVC77D (PVE) 7,200 7,200 7,200 3 / 380-415 / 3 / 380-415 / 3 / 380-415 / 50, 60 50, 60 50, 60 2C × 1.0~1.5 2C × 1.0~1.5 2C × 1.0~1.5 300 300 300 150 150 150 40 40 40 50 50 50 40 40 40 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) 4 4 4 64 64 64 50 ~ 130% 50 ~ 130% 50 ~ 130% Stainless Stainless Stainless Steel Plate Steel Plate Steel Plate 45 45 45 192 + 192 192 + 192 192 + 192 + 173 + 173 + 192 + 173 + 192 + 192 31 + 31 + 25 + 25 31 + 31 + 31 + 25 31 + 31 + 31 + 31 PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 20 20 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
WATER IV Heat Pump / Heat Recovery
HP
ARWN720LAS4 / ARWN740LAS4 / ARWN760LAS4 ARWN780LAS4 / ARWN800LAS4
OUTDOOR UNIT
ARWN620LAS4 / ARWN640LAS4 / ARWN660LAS4 ARWN680LAS4 / ARWN700LAS4
LG
Solution
80
81
Model Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Combination Unit Independent Unit Cooling Heating Cooling Heating Cooling Heating Cooling Heating Type Number of Compressor Cooling Heating Cooling Heating
Dimensions Net Weight Refrigerant Refrigerant Oil
Nom Nom Nom Nom
Min ~ Max °C DB Min ~ Max °C WB
Nom Nom Nom Nom WxHxD
Type Charge Type Control
Piping Level Difference
Piping Connection
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Low Pressure Gas High Pressure Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units
Heat Exchanger
Water Connection Pipe
dBA dBA dBA dBA mm kg kg
Power Supply Transmission Cable (VCTF-SB) Piping Length
kW kW kW kW
Max Max Max Max Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch) mm (inch)
Max Min ~ Max Type Pressure Resistance Rated Water Flow Head Loss Inlet Outlet Drain Outlet
Max
kgf/cm² L/min kPa mm mm mm
8
10
12
ARWB080LAS4 ARWB080LAS4 22.4 25.2 3.86 4.20 5.80 6.00 7.77 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 1 47 51 59 63 (755 × 997 × 500) × 1 127 x 1 R410A 5.8 FVC68D (PVE) 1,800 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 9.52 (3/8) 22.2 (7/8) 19.05 (3/4) 1 20 50 ~ 200% Stainless Steel Plate 45 77 11 PT 40 PT 40 20
ARWB100LAS4 ARWB100LAS4 28.0 31.5 5.09 5.34 5.50 5.90 7.71 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 1 50 53 62 65 (755 × 997 × 500) × 1 127 x 1 R410A 5.8 FVC68D (PVE) 1,800 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 9.52 (3/8) 22.2 (7/8) 19.05 (3/4) 1 25 50 ~ 200% Stainless Steel Plate 45 96 16 PT 40 PT 40 20
ARWB120LAS4 ARWB120LAS4 33.6 37.8 6.46 6.75 5.20 5.60 7.26 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 1 56 56 68 68 (755 × 997 × 500) × 1 127 x 1 R410A 5.8 FVC68D (PVE) 1,800 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 12.7 (1/2) 25.4 (1) 19.05 (3/4) 1 30 50 ~ 200% Stainless Steel Plate 45 116 22 PT 40 PT 40 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
HP Model Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
14 Combination Unit Independent Unit Cooling Heating Cooling Heating Cooling Heating Cooling Heating Type Number of Compressor Cooling Heating Cooling Heating
Dimensions Net Weight Refrigerant Refrigerant Oil
Nom Nom Nom Nom
Min ~ Max °C DB Min ~ Max °C WB
Nom Nom Nom Nom WxHxD
Type Charge Type Control
Piping Level Difference
Piping Connection
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Low Pressure Gas High Pressure Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units
Heat Exchanger
Water Connection Pipe
dBA dBA dBA dBA mm kg kg
Power Supply Transmission Cable (VCTF-SB) Piping Length
kW kW kW kW
Max Max Max Max Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch) mm (inch)
Max Min ~ Max Type Pressure Resistance Rated Water Flow Head Loss Inlet Outlet Drain Outlet
Max
kgf/cm² L/min kPa mm mm mm
16
18
20
ARWB140LAS4 ARWB160LAS4 ARWB180LAS4 ARWB200LAS4 ARWB140LAS4 ARWB160LAS4 ARWB180LAS4 ARWB200LAS4 39.2 44.8 50.4 56.0 44.1 50.4 56.7 63.0 7.84 8.15 9.69 11.20 8.17 8.54 10.13 11.67 5.00 5.50 5.20 5.00 5.40 5.90 5.60 5.40 6.96 7.18 7.10 7.02 10°C ~ 45°C 10°C ~ 45°C 10°C ~ 45°C 10°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll Hermetically Sealed Scroll Hermetically Sealed Scroll Hermetically Sealed Scroll 1 1 1 1 58 53 55 54 57 57 56 60 70 65 67 66 69 69 68 72 (755 × 997 × 500) × 1 (755 × 997 × 500) × 1 (755 × 997 × 500) × 1 (755 × 997 × 500) × 1 127 x 1 140 x 1 140 x 1 140 x 1 R410A R410A R410A R410A 5.8 3.0 3.0 3.0 FVC68D (PVE) FVC68D (PVE) FVC68D (PVE) FVC68D (PVE) 1,800 1,800 1,800 1,800 3 / 380-415 / 50, 60 3 / 380-415 / 50, 60 3 / 380-415 / 50, 60 3 / 380-415 / 50, 60 2C × 1.0~1.5 2C × 1.0~1.5 2C × 1.0~1.5 2C × 1.0~1.5 300 300 300 300 150 150 150 150 40 40 40 40 50 50 50 50 40 40 40 40 12.7 (1/2) 12.7 (1/2) 12.7 (1/2) 12.7 (1/2) 25.4 (1) 28.58 (1-1/8) 28.58 (1-1/8) 28.58 (1-1/8) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 1 1 1 1 35 40 45 50 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200% Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate 45 45 45 45 135 154 173 192 29 20 25 31 PT 40 PT 40 PT 40 PT 40 PT 40 PT 40 PT 40 PT 40 20 20 20 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
WATER IV Heat Pump / Heat Recovery
HP
ARWB140LAS4 / ARWB160LAS4 ARWB180LAS4 / ARWB200LAS4
OUTDOOR UNIT
ARWB080LAS4 / ARWB100LAS4 / ARWB120LAS4
LG
Solution
82
83
Combination Unit Model Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom
Cooling Heating Type Number of Compressor Cooling Heating Cooling Heating
Min ~ Max °C DB Min ~ Max °C WB
Dimensions Net Weight Refrigerant Refrigerant Oil
Nom Nom Nom Nom WxHxD
Type Charge Type Control
Piping Level Difference Piping Connection
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Low Pressure Gas High Pressure Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units Heat Exchanger
Water Connection Pipe
dBA dBA dBA dBA mm kg kg
Power Supply Transmission Cable (VCTF-SB) Piping Length
kW kW kW kW
Max Max Max Max Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch) mm (inch)
Max Min ~ Max Type Pressure Resistance Rated Water Flow Head Loss Inlet Outlet Drain Outlet
Max
kgf/cm² L/min kPa mm mm mm
22
24
ARWB220LAS4 ARWB120LAS4 ARWB100LAS4 61.6 69.3 11.55 12.09 5.33 5.73 7.34 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 57 57 40 70 (755 × 997 × 500) x 2 127 x 2 R410A 5.8 + 5.8 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 34.9 (1-3/8) 28.58 (1-1/8) 2 44 50 ~ 160% Stainless Steel Plate 45 116 + 96 22 + 16 PT 40 + PT 40 PT 40 + PT 40 20
ARWB240LAS4 ARWB120LAS4 ARWB120LAS4 67.2 75.6 12.92 13.50 5.20 5.60 7.21 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 57 57 70 70 (755 × 997 × 500) x 2 127 x 2 R410A 5.8 + 5.8 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 34.9 (1-3/8) 28.58 (1-1/8) 2 48 50 ~ 160% Stainless Steel Plate 45 116 + 116 22 + 22 PT 40 + PT 40 PT 40 + PT 40 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
HP Combination Unit Model Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom
Cooling Heating Type Number of Compressor Cooling Heating Cooling Heating
Min ~ Max °C DB Min ~ Max °C WB
Dimensions Net Weight Refrigerant Refrigerant Oil
Nom Nom Nom Nom WxHxD
Type Charge Type Control
Piping Level Difference Piping Connection
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Low Pressure Gas High Pressure Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units Heat Exchanger
Water Connection Pipe
dBA dBA dBA dBA mm kg kg
Power Supply Transmission Cable (VCTF-SB) Piping Length
kW kW kW kW
Max Max Max Max Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch) mm (inch)
Max Min ~ Max Type Pressure Resistance Rated Water Flow Head Loss Inlet Outlet Drain Outlet
Max
kgf/cm² L/min kPa mm mm mm
26
28
ARWB260LAS4 ARWB140LAS4 ARWB120LAS4 72.8 81.9 14.30 14.92 5.09 5.49 7.11 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 59 58 72 71 (755 × 997 × 500) x 2 127 x 2 R410A 5.8 + 5.8 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 34.9 (1-3/8) 28.58 (1-1/8) 2 52 50 ~ 160% Stainless Steel Plate 45 135 + 116 29 + 22 PT 40 + PT 40 PT 40 + PT 40 20
ARWB280LAS4 ARWB140LAS4 ARWB140LAS4 78.4 88.2 15.68 16.34 5.00 5.40 7.02 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 59 58 72 71 (755 × 997 × 500) x 2 127 x 2 R410A 5.8 + 5.8 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 34.9 (1-3/8) 28.58 (1-1/8) 2 56 50 ~ 160% Stainless Steel Plate 45 135 + 135 29 + 29 PT 40 + PT 40 PT 40 + PT 40 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
WATER IV Heat Pump / Heat Recovery
HP
ARWB260LAS4 / ARWB280LAS4
OUTDOOR UNIT
ARWB220LAS4 / ARWB240LAS4
LG
Solution
84
85
Combination Unit Model Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom
Cooling Heating Type Number of Compressor Cooling Heating Cooling Heating
Min ~ Max °C DB Min ~ Max °C WB
Dimensions Net Weight Refrigerant Refrigerant Oil
Nom Nom Nom Nom WxHxD
Type Charge Type Control
Piping Level Difference Piping Connection
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Low Pressure Gas High Pressure Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units Heat Exchanger
Water Connection Pipe
dBA dBA dBA dBA mm kg kg
Power Supply Transmission Cable (VCTF-SB) Piping Length
kW kW kW kW
Max Max Max Max Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch) mm (inch)
Max Min ~ Max Type Pressure Resistance Rated Water Flow Head Loss Inlet Outlet Drain Outlet
Max
kgf/cm² L/min kPa mm mm mm
30
32
34
ARWB300LAS4 ARWB160LAS4 ARWB140LAS4 84.0 94.5 15.99 16.71 5.25 5.66 7.12 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 59 58 72 71 (755 × 997 × 500) x 2 (127 x 1) + (140 x 1) R410A 3.0 + 5.8 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 34.9 (1-3/8) 28.58 (1-1/8) 2 60 50 ~ 160% Stainless Steel Plate 45 154 + 135 20 + 29 PT 40 + PT 40 PT 40 + PT 40 20
ARWB320LAS4 ARWB180LAS4 ARWB140LAS4 89.6 100.8 17.53 18.30 5.11 5.51 7.07 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 59 58 72 71 (755 × 997 × 500) x 2 (127 x 1) + (140 x 1) R410A 3.0 + 5.8 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 34.9 (1-3/8) 28.58 (1-1/8) 2 64 50 ~ 160% Stainless Steel Plate 45 173 + 135 25 + 29 PT 40 + PT 40 PT 40 + PT 40 20
ARWB340LAS4 ARWB200LAS4 ARWB140LAS4 95.2 107.1 19.04 19.84 5.00 5.40 7.01 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 59 61 72 74 (755 × 997 × 500) x 2 (127 x 1) + (140 x 1) R410A 3.0 + 5.8 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 34.9 (1-3/8) 28.58 (1-1/8) 2 64 50 ~ 160% Stainless Steel Plate 45 192 + 135 31 + 29 PT 40 + PT 40 PT 40 + PT 40 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
HP Combination Unit Model Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom
Cooling Heating Type Number of Compressor Cooling Heating Cooling Heating
Min ~ Max °C DB Min ~ Max °C WB
Dimensions Net Weight Refrigerant Refrigerant Oil
Nom Nom Nom Nom WxHxD
Type Charge Type Control
Piping Level Difference Piping Connection
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Low Pressure Gas High Pressure Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units Heat Exchanger
Water Connection Pipe
dBA dBA dBA dBA mm kg kg
Power Supply Transmission Cable (VCTF-SB) Piping Length
kW kW kW kW
Max Max Max Max Max
cc Ø / V / Hz No. x mm² m m m m m mm (inch) mm (inch) mm (inch)
Max Min ~ Max Type Pressure Resistance Rated Water Flow Head Loss Inlet Outlet Drain Outlet
Max
kgf/cm² L/min kPa mm mm mm
36
38
40
ARWB360LAS4 ARWB180LAS4 ARWB180LAS4 100.8 113.4 19.38 20.26 5.20 5.60 7.11 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 56 57 69 70 (755 × 997 × 500) x 2 140 x 2 R410A 3.0 + 3.0 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 2 64 50 ~ 160% Stainless Steel Plate 45 173 + 173 25 + 25 PT 40 + PT 40 PT 40 + PT 40 20
ARWB380LAS4 ARWB200LAS4 ARWB180LAS4 106.4 119.7 20.89 21.80 5.09 5.49 7.06 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 56 61 69 74 (755 × 997 × 500) x 2 140 x 2 R410A 3.0 + 3.0 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 2 64 50 ~ 160% Stainless Steel Plate 45 192 + 173 31 + 25 PT 40 + PT 40 PT 40 + PT 40 20
ARWB400LAS4 ARWB200LAS4 ARWB200LAS4 112.0 126.0 22.40 23.34 5.00 5.40 7.01 10°C ~ 45°C -5°C ~ 45°C Hermetically Sealed Scroll 2 55 61 68 74 (755 × 997 × 500) x 2 140 x 2 R410A 3.0 + 3.0 FVC68D (PVE) 3,600 3 / 380-415 / 50, 60 2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 2 64 50 ~ 160% Stainless Steel Plate 45 192 + 192 31 + 31 PT 40 + PT 40 PT 40 + PT 40 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
WATER IV Heat Pump / Heat Recovery
HP
ARWB360LAS4 / ARWB380LAS4 / ARWB400LAS4
OUTDOOR UNIT
ARWB300LAS4 / ARWB320LAS4 / ARWB340LAS4
LG
Solution
86
87
Combination Unit Model
Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom
Cooling Heating
Min ~ Max °C DB Min ~ Max °C WB
Type Number of Compressor Cooling Heating Cooling Heating
Dimensions
Nom Nom Nom Nom
Refrigerant Oil
kg Type Charge Type Control
kg cc
Power Supply Transmission Cable (VCTF-SB) Piping Length Piping Level Difference Piping Connection
dBA dBA dBA dBA
W x H x D mm
Net Weight Refrigerant
kW kW kW kW
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Low Pressure Gas High Pressure Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units
Max Max Max Max Max
Water Connection Pipe
Max
46
48
50
ARWB460LAS4 ARWB200LAS4 ARWB140LAS4 ARWB120LAS4 128.8 144.9 25.50 26.59 5.05 5.45 7.06 10°C ~ 45°C -5°C ~ 45°C
ARWB480LAS4 ARWB200LAS4 ARWB140LAS4 ARWB140LAS4 134.4 151.2 26.88 28.01 5.00 5.40 7.01 10°C ~ 45°C -5°C ~ 45°C
ARWB500LAS4 ARWB200LAS4 ARWB160LAS4 ARWB140LAS4 140.0 157.5 27.19 28.38 5.15 5.55 7.07 10°C ~ 45°C -5°C ~ 45°C
Hermetically Sealed Scroll
Hermetically Sealed Scroll
Hermetically Sealed Scroll
Hermetically Sealed Scroll
Hermetically Sealed Scroll
3 58 62 72 76
3 58 62 72 76
3 60 62 74 76
3 60 62 74 76
3 60 62 74 76
(755 × 997 × 500) x 3
(755 × 997 × 500) x 3
(755 × 997 × 500) x 3
(755 × 997 × 500) x 3
(755 × 997 × 500) x 3
(140 x 1) + (127 X 2) (140 x 1) + (127 X 2) (140 x 1) + (127 X 2) (140 x 1) + (127 X 2) (140 x 2) + (127 X 1) R410A R410A R410A R410A R410A 3.0 + 5.8 + 5.8 3.0 + 5.8 + 5.8 3.0 + 5.8 + 5.8 3.0 + 5.8 + 5.8 3.0 + 3.0 + 5.8 FVC68D (PVE) FVC68D (PVE) FVC68D (PVE) FVC68D (PVE) FVC68D (PVE) 5,400 5,400 5,400 5,400 5,400
HP Combination Unit Model
Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Refrigerant Refrigerant Oil
Ø / V / Hz
3 / 380-415 / 50, 60
3 / 380-415 / 50, 60
Power Supply
No. x mm² m m m m m mm (inch) mm (inch) mm (inch)
2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
Transmission Cable (VCTF-SB)
Stainless Steel Plate
Stainless Steel Plate
Stainless Steel Plate
Stainless Steel Plate
Stainless Steel Plate
45 45 45 45 45 192 + 116 + 96 192 + 116 + 116 192 + 135 + 116 192 + 135 + 135 192 + 154 + 135 31 + 22 + 16 31 + 22 + 22 31 + 29 + 22 31 + 29 + 29 31 + 20 + 29 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 20 20 20 20 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom
Cooling Heating
Min ~ Max °C DB Min ~ Max °C WB
Piping Length Piping Level Difference Piping Connection
kW kW kW kW
Type Number of Compressor Cooling Heating Cooling Heating
Nom Nom Nom Nom
dBA dBA dBA dBA
W x H x D mm
Net Weight
3 / 380-415 / 50, 60
kgf/cm² L/min kPa mm mm mm
Independent Unit
Dimensions
3 / 380-415 / 50, 60
Max Min ~ Max
Pressure Resistance Rated Water Flow Head Loss Inlet Outlet Drain Outlet
44 ARWB440LAS4 ARWB200LAS4 ARWB120LAS4 ARWB120LAS4 123.2 138.6 24.12 25.17 5.11 5.51 7.12 10°C ~ 45°C -5°C ~ 45°C
3 / 380-415 / 50, 60
Type Heat Exchanger
42 ARWB420LAS4 ARWB200LAS4 ARWB120LAS4 ARWB100LAS4 117.6 132.3 22.75 23.76 5.17 5.57 7.18 10°C ~ 45°C -5°C ~ 45°C
kg Type Charge Type Control
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Low Pressure Gas High Pressure Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units
kg cc
Max Max Max Max Max
Water Connection Pipe
Max
56
58
60
ARWB560LAS4 ARWB200LAS4 ARWB180LAS4 ARWB180LAS4 156.8 176.4 30.58 31.93 5.13 5.52 7.07 10°C ~ 45°C -5°C ~ 45°C
ARWB580LAS4 ARWB200LAS4 ARWB200LAS4 ARWB180LAS4 162.4 182.7 32.09 33.47 5.06 5.46 7.04 10°C ~ 45°C -5°C ~ 45°C
ARWB600LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 168.0 189.0 33.60 35.01 5.00 5.40 7.01 10°C ~ 45°C -5°C ~ 45°C
Hermetically Sealed Scroll
Hermetically Sealed Scroll
Hermetically Sealed Scroll
Hermetically Sealed Scroll
Hermetically Sealed Scroll
3 60 62 74 76
3 60 62 74 76
3 57 62 71 76
3 57 62 71 76
3 56 62 70 76
(755 × 997 × 500) x 3
(755 × 997 × 500) x 3
(755 × 997 × 500) x 3
(755 × 997 × 500) x 3
(755 × 997 × 500) x 3
140 x 3 R410A 3.0 + 3.0 + 3.0 FVC68D (PVE) 5,400
140 x 3 R410A 3.0 + 3.0 + 3.0 FVC68D (PVE) 5,400
140 x 3 R410A 3.0 + 3.0 + 3.0 FVC68D (PVE) 5,400
(140 x 2) + (127 X 1) (140 x 2) + (127 X 1) R410A R410A 3.0 + 3.0 + 5.8 3.0 + 3.0 + 5.8 FVC68D (PVE) FVC68D (PVE) 5,400 5,400 3 / 380-415 / 50, 60
3 / 380-415 / 50, 60
3 / 380-415 / 50, 60
3 / 380-415 / 50, 60
3 / 380-415 / 50, 60
No. x mm² m m m m m mm (inch) mm (inch) mm (inch)
2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
2C × 1.0~1.5 300 150 40 50 40 19.05 (3/4) 41.3 (1-5/8) 34.9 (1-3/8) 3 64 50 ~ 130%
Stainless Steel Plate
Stainless Steel Plate
Stainless Steel Plate
Stainless Steel Plate
Stainless Steel Plate
Max Min ~ Max
Pressure Resistance Rated Water Flow Head Loss Inlet Outlet Drain Outlet
54 ARWB540LAS4 ARWB200LAS4 ARWB200LAS4 ARWB140LAS4 151.2 170.1 30.24 31.51 5.00 5.40 7.01 10°C ~ 45°C -5°C ~ 45°C
Ø / V / Hz
Type Heat Exchanger
52 ARWB520LAS4 ARWB200LAS4 ARWB180LAS4 ARWB140LAS4 145.6 163.8 28.73 29.97 5.07 5.47 7.04 10°C ~ 45°C -5°C ~ 45°C
kgf/cm² L/min kPa mm mm mm
45 45 45 45 45 192 + 173 + 135 192 + 192 + 135 192 + 173 + 173 192 + 192+ 173 192 + 192+ 192 31 + 25 + 29 31 + 31 + 29 31 + 25 + 25 31 + 31 + 25 31 + 31 + 31 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 20 20 20 20 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
WATER IV Heat Pump / Heat Recovery
HP
ARWB520LAS4 / ARWB540LAS4 / ARWB560LAS4 ARWB580LAS4 / ARWB600LAS4
OUTDOOR UNIT
ARWB420LAS4 / ARWB440LAS4 / ARWB460LAS4 ARWB480LAS4 / ARWB500LAS4
LG
Solution
88
89
62 Combination Unit
Model
Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom
Cooling Heating
Min ~ Max °C DB Min ~ Max °C WB
Type Number of Compressor Cooling Heating Cooling Heating
Dimensions
Nom Nom Nom Nom
Refrigerant Oil
dBA dBA dBA dBA
W x H x D mm
Net Weight Refrigerant
kW kW kW kW
kg Type Charge Type Control
kg cc
Power Supply
Ø / V / Hz
Transmission Cable (VCTF-SB)
No. x mm² m m m m m mm (inch) mm (inch) mm (inch)
Piping Length Piping Level Difference Piping Connection
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Low Pressure Gas High Pressure Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units
Max Max Max Max Max
Max Min ~ Max Type
Heat Exchanger
Water Connection Pipe
Pressure Resistance
Max
kgf/cm²
Rated Water Flow
L/min
Head Loss
kPa
Inlet
mm
Outlet
mm
Drain Outlet
mm
64
66
68
70
ARWB620LAS4 ARWB640LAS4 ARWB660LAS4 ARWB680LAS4 ARWB700LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB120LAS4 ARWB120LAS4 ARWB140LAS4 ARWB140LAS4 ARWB160LAS4 ARWB100LAS4 ARWB120LAS4 ARWB120LAS4 ARWB140LAS4 ARWB140LAS4 173.6 179.2 184.8 190.4 196.0 195.3 201.6 207.9 214.2 220.5 33.95 35.32 36.70 38.08 38.39 35.43 36.84 38.26 39.68 40.05 5.11 5.07 5.04 5.00 5.11 5.51 5.47 5.43 5.40 5.51 7.12 7.08 7.04 7.01 7.05 10°C ~ 45°C 10°C ~ 45°C 10°C ~ 45°C 10°C ~ 45°C 10°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C Hermetically Hermetically Hermetically Hermetically Hermetically Sealed Scroll Sealed Scroll Sealed Scroll Sealed Scroll Sealed Scroll 4 4 4 4 4 59 59 61 61 61 63 63 63 63 63 73 73 75 75 75 77 77 77 77 77 (755 × 997 (755 × 997 (755 × 997 (755 × 997 (755 × 997 × 500) x 4 × 500) x 4 × 500) x 4 × 500) x 4 × 500) x 4 (140 x 2) + (127 x 2) (140 x 2) + (127 x 2) (140 x 2) + (127 x 2) (140 x 2) + (127 x 2) (140 x 3) + (127 x 1) R410A R410A R410A R410A R410A 3.0 + 3.0 + 5.8 + 5.8 3.0 + 3.0 + 5.8 + 5.8 3.0 + 3.0 + 5.8 + 5.8 3.0 + 3.0 + 5.8 + 5.8 3.0 + 3.0 + 3.0 + 5.8 FVC68D (PVE) FVC69D (PVE) FVC70D (PVE) FVC71D (PVE) FVC72D (PVE) 7,200 7,200 7,200 7,200 7,200 3 / 380-415 / 3 / 380-415 / 3 / 380-415 / 3 / 380-415 / 3 / 380-415 / 50, 60 50, 60 50, 60 50, 60 50, 60 2C × 1.0~1.5 2C × 1.0~1.5 2C × 1.0~1.5 2C × 1.0~1.5 2C × 1.0~1.5 300 300 300 300 300 150 150 150 150 150 40 40 40 40 40 50 50 50 50 50 40 40 40 40 40 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 44.5 (1-3/4) 44.5 (1-3/4) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) 41.3 (1-5/8) 41.3 (1-5/8) 41.3 (1-5/8) 44.5 (1-3/4) 44.5 (1-3/4) 4 4 4 4 4 64 64 64 64 64 50 ~ 130% 50 ~ 130% 50 ~ 130% 50 ~ 130% 50 ~ 130% Stainless Stainless Stainless Stainless Stainless Steel Plate Steel Plate Steel Plate Steel Plate Steel Plate 45 45 45 45 45 192 + 192 192 + 192 192 + 192 192 + 192 192 + 192 + 116 + 96 + 116 + 116 + 135 + 116 + 135 + 135 + 154 + 135 31 + 31 + 22 + 16 31 + 31 + 22 + 22 31 + 31 + 29 + 22 31 + 31 + 29 + 29 31 + 31 + 20 + 29 PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 20 20 20 20 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
HP
72 Combination Unit
Model
Capacity Power Input EER COP ESEER Operation Range Compressor Sound Pressure Sound Power
Independent Unit Cooling Heating Cooling Heating Cooling Heating
Nom Nom Nom Nom
Cooling Heating
Min ~ Max °C DB Min ~ Max °C WB
Type Number of Compressor Cooling Heating Cooling Heating
Dimensions
Nom Nom Nom Nom
Refrigerant Oil
kg Type Charge Type Control
kg cc
Power Supply
Ø / V / Hz
Transmission Cable (VCTF-SB) Piping Length Piping Level Difference Piping Connection
dBA dBA dBA dBA
W x H x D mm
Net Weight Refrigerant
kW kW kW kW
Total Actual Longest Piping Length After 1st Y Branch IDU - ODU IDU - IDU Liquid Low Pressure Gas High Pressure Gas
Number of Outdoor Units Number of Connectable Indoor Units Ratio of the Connectable Indoor Units
Max Max Max Max Max
No. x mm² m m m m m mm (inch) mm (inch) mm (inch)
Max Min ~ Max Type
Heat Exchanger
Water Connection Pipe
Pressure Resistance
Max
kgf/cm²
Rated Water Flow
L/min
Head Loss
kPa
Inlet
mm
Outlet
mm
Drain Outlet
mm
74
76
78
80
ARWB720LAS4 ARWB740LAS4 ARWB760LAS4 ARWB780LAS4 ARWB800LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB180LAS4 ARWB200LAS4 ARWB180LAS4 ARWB200LAS4 ARWB200LAS4 ARWB140LAS4 ARWB140LAS4 ARWB180LAS4 ARWB180LAS4 ARWB200LAS4 201.6 207.2 212.8 218.4 224.0 226.8 233.1 239.4 245.7 252.0 39.93 41.44 41.78 43.29 44.80 41.64 43.18 43.60 45.14 46.68 5.05 5.00 5.09 5.05 5.00 5.45 5.40 5.49 5.44 5.40 7.03 7.01 7.05 7.03 7.01 10°C ~ 45°C 10°C ~ 45°C 10°C ~ 45°C 10°C ~ 45°C 10°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C -5°C ~ 45°C Hermetically Hermetically Hermetically Hermetically Hermetically Sealed Scroll Sealed Scroll Sealed Scroll Sealed Scroll Sealed Scroll 4 4 4 4 4 61 61 58 58 57 63 63 63 63 63 75 75 72 72 71 77 77 77 77 77 (755 × 997 (755 × 997 (755 × 997 (755 × 997 (755 × 997 × 500) x 4 × 500) x 4 × 500) x 4 × 500) x 4 × 500) x 4 (140 x 3) + (127 x 1) (140 x 3) + (127 x 1) 140 x 4 140 x 4 140 x 4 R410A R410A R410A R410A R410A 3.0 + 3.0 + 3.0 + 5.8 3.0 + 3.0 + 3.0 + 5.8 3.0 + 3.0 + 3.0 + 3.0 3.0 + 3.0 + 3.0 + 3.0 3.0 + 3.0 + 3.0 + 3.0 FVC73D (PVE) FVC74D (PVE) FVC75D (PVE) FVC76D (PVE) FVC77D (PVE) 7,200 7,200 7,200 7,200 7,200 3 / 380-415 / 3 / 380-415 / 3 / 380-415 / 3 / 380-415 / 3 / 380-415 / 50, 60 50, 60 50, 60 50, 60 50, 60 2C × 1.0~1.5 2C × 1.0~1.5 2C × 1.0~1.5 2C × 1.0~1.5 2C × 1.0~1.5 300 300 300 300 300 150 150 150 150 150 40 40 40 40 40 50 50 50 50 50 40 40 40 40 40 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) 44.5 (1-3/4) 44.5 (1-3/4) 44.5 (1-3/4) 44.5 (1-3/4) 44.5 (1-3/4) 4 4 4 4 4 64 64 64 64 64 50 ~ 130% 50 ~ 130% 50 ~ 130% 50 ~ 130% 50 ~ 130% Stainless Stainless Stainless Stainless Stainless Steel Plate Steel Plate Steel Plate Steel Plate Steel Plate 45 45 45 45 45 192 + 192 192 + 192 192 + 192 192 + 192 192 + 192 + 173 + 135 + 192 + 135 + 173 + 173 + 192 + 173 + 192 + 192 31 + 31 + 25 + 29 31 + 31 + 31 + 29 31 + 31 + 25 + 25 31 + 31 + 31 + 25 31 + 31 + 31 + 31 PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 + PT 40 20 20 20 20 20
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities and Inputs are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp. 30°C (86°F), Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB, Water inlet temp. 20°C (68°F) 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. Add an anti freeze to circulation water when outside units is operating undet 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)
WATER IV Heat Pump / Heat Recovery
HP
ARWB720LAS4 / ARWB740LAS4 / ARWB760LAS4 ARWB780LAS4 / ARWB800LAS4
OUTDOOR UNIT
ARWB620LAS4 / ARWB640LAS4 / ARWB660LAS4 ARWB680LAS4 / ARWB700LAS4
LG
Solution
90
91
OUTDOOR UNIT
OUTDOOR UNIT
MULTI V
WATER S
Designed for space saving
EER (Rated Efficiency)
COP (Rated Efficiency)
EER
COP
World’s First Class Cooling and Heating Efficiency 46%
48%
5.3
5.7 3.8 WATER S
3.7
1. Piping Length Total Piping Length
300m
Actual longest piping length** (Equivalent)
175m
Longest piping length after 1st branch (Conditional application)
40m
Height difference between ODU ~ IDU
50m
Height difference between IDU ~ IDU
15m
Company B
MULTI V WATER S
Company B
* Comparison between 4HP model, based on internal test data
MULTI V WATER S
* Comparison between 4HP model, based on internal test data
Compact Size Outdoor unit can be placed inside a closet, no need for roof or outside space. It can be applicable for small space application such as shops in city centers and malls.
15m Height between IDU
* Assume equivalent piping length of Y Branch to be 0.5m, that of header to be 1m, calculation purpose. ** To apply Conditional Application
36% Reduced 4, 5, 6 HP 330mm
76%
4, 5, 6 HP
76kg
MULTI V WATER S
Reduction 630mm
MULTI V WATER S
Company B
Convenient Installation Absence of drain pipe makes installation easier.
Benefit • Saves valuable floor space • Low noise level (No fans)
MULTI V WATER S
• Flexible design applications • High efficient water source system
Application • Building remodeling case (Initially Equipped with Chillers) • Residential building with geothermal / Water supply • High-rise commercial building
No Drain Pipe
Cost Saving Space Saving
118kg
Company B
1,120mm
40m (90m : Conditional application)*
Weight
Foot print area
520mm
50m Height difference
150m (200m : Conditional application)*
Conventional
LG
Solution
92
93
ARWN40GA0 / ARWN50GA0 / ARWN60GA0
OUTDOOR UNIT
REFERENCE SITE Bouygues Challenger LG MULTI V Water Solution with Geothermal Application HP Model
Independent Unit
4
5
6
ARWN40GA0
ARWN50GA0
ARWN60GA0
Nom
kW
11.2
14.0
15.5
Heating
Nom
kW
12.5
16.0
18.0
Cooling
Nom
kW
2.10
2.70
3.20
Heating
Nom
kW
2.20
2.90
3.50
EER
5.33
5.19
4.84
COP
5.68
5.52
5.14
10°C ~ 45°C
10°C ~ 45°C
10°C ~ 45°C
Power Input
Operation Range Compressor Sound Pressure Sound Power
Cooling
Min ~ Max °C DB
Heating
Min ~ Max °C WB
Type Number of Compressor
1
1
1
dBA
48
49
50
Heating
Nom
dBA
48
49
50
Cooling
Nom
dBA
59
60
61
Heating
Nom
dBA
59
60
61
520 x 1,080 x 330
520 x 1,080 x 330
520 x 1,080 x 330
W x H x D mm kg Type Charge
kg
Type Control
cc
Power Supply Transmission Cable (VCTF-SB)
Piping Level Difference Piping Connection
76 R410A
1.0
1.0
1.0
FVC68D
FVC68D
FVC68D
1,300
1,300
1,300
Ø / V / Hz
1 / 220-240 / 50, 60
1 / 220-240 / 50, 60
1 / 220-240 / 50, 60
No. x mm²
2C × 1.0~1.5
2C × 1.0~1.5
2C × 1.0~1.5
145
145
145
Actual Longest Piping Length Max
m
90
90
90
After 1st Y Branch
Max
m
40
40
40
IDU - ODU
Max
m
30
30
30
IDU - IDU
Max
m
15
15
15
Liquid
mm (inch)
9.52 (3/8)
9.52 (3/8)
9.52 (3/8)
Gas
mm (inch)
19.05 (3/4)
19.05 (3/4)
19.05 (3/4)
1
1
1
6
8
9
Number of Outdoor Units Max
Ratio of the Connectable Indoor Units
Min ~ Max Type
Water Connection Pipe
76 R410A
m
Number of Connectable Indoor Units
Heat Exchanger
76 R410A
Max
Total Piping Length
-5°C ~ 45°C BLDC Inverter Twin Rotary
Nom
Net Weight
Refrigerant Oil
-5°C ~ 45°C BLDC Inverter Twin Rotary
Cooling
Dimensions
Refrigerant
-5°C ~ 45°C BLDC Inverter Twin Rotary
Pressure Resistance
Max
kgf/cm²
50 ~ 130%
50 ~ 130%
50 ~ 130%
Stainless Steel Plate
Stainless Steel Plate
Stainless Steel Plate
4,413
4,413
4,413
40
50
60
Nom Water Flow
L/min
Head Loss
kPa
14.0
20.7
28.4
Inlet
mm
PT32 (1-1/4)
PT32 (1-1/4)
PT32 (1-1/4)
Outlet
mm
PT32 (1-1/4)
PT32 (1-1/4)
PT32 (1-1/4)
Drain Outlet
mm
-
-
-
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities are based on the following conditions : - Cooling Temperature : Indoor 27°C (80.6°F) DB / 19°C (66.2°F) WB / Water 30°C (86°F) - Heating Temperature : Indoor 20°C (68°F) DB / 15°C (59°F) WB / Water 20°C (68°F) - Piping Length : Interconnected Pipe Length = 7.5m - Difference Limit of Elevation (Outside ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national codes. 3. Due to our policy of innovation some specifications may be changed without notification. 4. Sound Level Values are measured at Anechoic chamber. Therefore, these values can be increased owing to ambient conditions during operation.
WATER S
Cooling
Capacity
Site Information The industrial group Bouygues was established in France in 1952. It now maintains operations in 80 countries and employs more than 131,000 people. In 1988, after two years of construction, the new headquarters for Bouygues Construction was officially opened for business. Named Challenger, the complex became a technological showcase for late 20th century architecture.
LG Solution Bouygues decided to convert their headquarters into an eco-friendly building by significantly reducing its energy footprint. The LG MULTI V Water system was chosen as the ideal HVAC solution for this project. The system not only saves energy but also reduces water usage as it recycles water in order to regulate the temperature of the building. With LG’s advanced technology, the building’s water consumption was reduced by more than 70 percent.
LG
Solution
94
95
INDOOR UNIT 104 112 120 128 130
Wall Mounted Unit Ceiling Mounted Cassette Ceiling Concealed Duct Fresh Air Intake Unit Ceiling & Floor Convertible Unit Ceiling Suspended Unit
134 Console 136 Floor Standing Unit (with Case / without Case) 138 MULTI V Indoor Compatibility
If you need a highly efficient air conditioning system in your building, MULTI V is the best choice for you.
LG
Solution
96
97
INDOOR UNIT LINE-UP
FEATURES OVERVIEW Energy Monitoring
2 Set Point
Occupied / Unoccupied Scheduling Function
Group Control
Test Run (Cooling)
Test Run (Heating)
Model Information Monitoring
Auto Addressing
Refrigerant Leakage Detection
Thermo On / Off Range Setting (Cooling)
Thermo On / Off Range Setting (Heating)
ARTCOOL Gallery
•
•
•
•
•
•
•
•
•
•
ARTCOOL Mirror
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
2 Way Cassette
•
•
•
•
•
1 Way Cassette
•
•
•
•
Mid / High Statics
•
•
•
Low Statics
•
•
Built-in
•
High Sensible
Type
Btu/h
5k
7k
9k 12k 15k 18k 21k 24k 28k 30k 36k 42k 48k 54k 76k 96k
Static Pressure 11 Step Control (Only for Ceiling Concealed Duct Type)
1 Point External Input (On / Off Control)
Filter Sign (Remaining Time)
Auto Rerstart Function Disable / Enable
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
4th Generation
Wall Mounted Unit
NEW
NEW
Standard 4 Way Cassette (570 x 570) 4th Generation
Ceiling Mounted Cassette
4th Generation
Ceiling Concealed Duct
4 Way Cassette (840 x 840)
4th Generation
Fresh Air Intake Units
NEW
NEW
NEW
2nd Generation
Ceiling & Floor Convertible Unit 2nd Generation
Ceiling Suspended Unit
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Floor Standing Unit with Case
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Floor Standing Unit without Case
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Low Temperature
•
•
•
•
High Temperature
•
•
Console Floor Standing Unit
•
•
4th Generation
4th Generation
•
2nd Generation
HYDRO KIT
•
2nd Generation
with Humidifier Energy Recovery Ventilator without Humidifier with DX Coil 1) If 4th generation indoors are connected to MULTIV WATER S outdoor, some of function will not be activated. More detailed information, refer to the "MULTI V INDOOR COMPATIBILITY" (page 138~139)
2) If 4th generation indoors are combined to 2nd generation indoors, some of function will not be activated.
INDOOR UNIT
1.5 2.2 2.8 3.6 4.5 5.6 6.2 7.1 8.2 9.0 10.6 12.3 14.1 15.8 22.4 28.0
kW
LG
Solution
98
99
4th Generation
COMFORT INDOOR UNIT
Quick Control
Filter Sign (Remaining Time)
4th Generation indoor unit offers rapid heating and cooling about 10times faster than conventional through communication mode change and improved communication speed.
The alarm is activated when the filter needs to be cleaned, and the time remaining for cleaning is displayed on the screen, which is convenient for users.
Conventional
New
Communication with user-controlling unit directly
New
Conventional
Remain Time Until Indoor Filter Cleaning + Alarm
Only Alarm
Communication with indoor unit sequentially from 1st to end Standard Wired Remote Controller
Remain Time Until Indoor Filter Cleaning 2400hr.
ON / OFF
ON / OFF
Remain Time Until Indoor Filter Cleaning 1729hr.
Conventional New
Premium Wired Remote Controller
* Ordinary outdoor unit communicates with indoor unit in regular transmission. ** In case of communication between outdoor unit and 64th indoor unit.
1,200bps + Sequential Transmission
10times faster
9,600bps + Direct Transmission
Depending on the installation environment, 4series ceiling concealed duct is controlled the static pressure to 11 step, for providing comfortable environment suitable for any environment.
Thermo On / Off Range Setting (Cooling) User can set cooling thermo On / Off range with wired remote controller for prevention overcooling and making optimized indoor environment.
Prevention Overcooling
Static Pressure 11 Step Control (Only for Ceiling Concealed Duct) Conventional
New
Cooling Thermo On / Off Range OFF
ON
Ts+6oC 1 step
Static Pressure Low Setting Ts+4oC
Ts+2oC Ts+1oC Customer can choose a thermo on, off range of 3options
Setting Temp(Ts) Ts-1oC
11 step
Static Pressure Power Setting
100
Solution
LG
101
4th Generation
CONVENIENCE INDOOR UNIT
Group Control
1 Point External Input (On / Off Control)
In case of group control, user can control much more function than conventional.
Indoor unit can control external devices without dry contact, so customer can save cost of installation.
Conventional
New
Conventional
New Connection between an indoor unit and external devices directly
Connection between an indoor unit and external devices through dry contact
Not Necessary Standard Operation
Cooling / Heating Dehumidification Fan only operating Setting temp.
+ In Case of Group Control
Standard Operation
Cooling / Heating Dehumidification Fan only operating Setting temp.
Motion Detector Sensor
Motion Detector Sensor
Cost Savings
* In case of all indoor unit in 1group is the same unit. ** Fan Auto function is applicable only in the ceiling concealed duct.
Sub function isn’t operating
Key Tag
Key Tag
Energy Monitoring (Accumulated Electric Energy Check) Accumulated electric energy of the indoor unit can be identified with wired remote control, as well as with the central controller. This function is an advantage for energy management.
Install Scene
Apply for Multistory Building 100kWh
Watt Meter
* In case of needing more functions beside On / Off control, a dry contact is required to be installed.
Auto Addressing Addressing time has been reduced up to 1.5min., that needed only power on without any process. Auto addressing takes shorter as 57% as compared to conventional.
Auto Addressing 1.5min Required
Total Power Input
20kWh Premium Wired Remote Controller
Conventional
New
PDI
Power On
Total accumulated electric energy 595kWh
Power On
Time Saving 3.5min 1.5min 50kWh
Total accumulated Standard Wired Remote Controller electric energy 3,248.7kWh
Button On
57%
30kWh
* Outdoor unit's accumulated electric energy / using rate of individual indoor unit + indoor unit's accumulated electric energy is displayed in wired remote controller, only when central controller, digital integrating electricity meter and PDI are installed and PDI, outdoor unit and indoor unit are connected with power wire. Only total accumulated electric energy is displayed in standard wired remote controller. In premium wired remote controller, that are displayed into week / month / year.
* 64ea indoor units installing time
Auto Addressing 3.5min Required Button On
LG
Solution
102
103
4th Generation
CONVENIENCE INDOOR UNIT
Compatibility
Model Information Monitoring
• Outdoor unit
User can check indoor unit and outdoor unit’s information with wired remote controller, so that is convenient for service.
- Any MULTI V series outdoor unit can be installed
Category
• Indoor unit
First Number : Outdoor Unit
- Any MULTI V series can be installed
• Wired remote controller
Category
- Standard II : PREMTB001, PREMTBB01 - Premium : PREMTA000, PREMTA000A, PREMTA000B
• Implementable Functions - Static Pressure 11 Step Control - Cooling thermo On / Off range setting - Filter Sign - Control the external devices - Heating test run mode - Convenient check information
Model
0 1 2
MULTI V MULTI Single
No. Model No.
Second Number : Indoor Unit
Conventional
No.
0 1 2 3 4
Category Installing New indoor unit Additional
CST Duct CVT PAC RAC
6 7 8 9 -
Model
No.
Model
Console Single Package General Ventilation AWHP -
A B -
HYDRO KIT for Medium Temp. HYDRO KIT for High Temp. -
No. Capacity No. Capacity No. Capacity No. Capacity MULTI V
Third Number : Capacity of MULTI the Indoor Unit
Single
0 1 2 3 0 1 2 3 0 1 2 3
5K 7K 9K 12K 5K 7K 8K 9K 9K 12K 18K 21K
4 5 6 7 4 5 6 7 4 5 6 7
15K 18K 24K 28K 12K 14K 15K 18K 24K 30K 36K 42K
8 9 A B 8 9 A B 8 9 -
36K 42K 48K 54K 20K 24K 30K 36K 48K 60K -
C D -
76K 96K -
Test Run (Heating)
Refrigerant Leakage Detection (Option Function)
Test run mode can be operated cooling mode and heating mode for easy service.
To meet the Global refrigerant leakage regulation, LG uses refrigerant leakage detection kit. This detector senses refrigerant leakage and when the refrigerant concentration exceeds 6,000ppm not only stopping the indoor unit operation but also giving an alarm using buzzer and sensor LED (The green and red LED lights blink simultaneously).
New
Conventional
Refrigerant Leakage Detection
In Case of Leak Refrigerant
Oxygen Reduction Stop Operation and Ring Alarm
Heating and cooling test run mode are available
Heating test run mode is unavailable
Sensing Refrigerant Leakage (Refrigerant Leakage Detector) * Refrigerant leakage detector is option accessory.
Global Regulation
ASHRAE Standard 15 / 34 Regulation
Life Span Reduction
Environmental Pollution EN 378 Regulation, EU FGas Regulation 517 / 2014
Solution
LG
104
105
WALL MOUNTED UNIT INDOOR UNIT
Digital Air Flow Control
You no longer need to be told what your air conditioner should look like. With LG’s revolutionary ARTCOOL Gallery, you can change the look of your air conditioner to whatever you want, whenever you want. The ARTCOOL series have outstanding designs and have been awarded the International Forum Design Award, the Reddot Design Award and the G Mark.
The air flow can be controlled to ensure maximum comfort and convenience.
Normal
Jet Cool
Sleep Mode
Fast, Wide and Even
Speedy and Powerful
Indirect and Discreet
Wall Mounted Unit
Aesthetic Design Gallery
How to Change the Picture
Filtering (Virus & Allergy Safe Filter) The virus and allergy safe filters are scientifically proven to deactivate viruses that may pose risks to health.
Virus Deactivation
The LG virus & allergy safe filter blocks neuramidase and hemagglutinin, which is activated when the virus breaks up from host cell to proliferate.
Allergy Filter
Allergen
Apatite & Organic / Inorganic Binder
Allergy care filter coated with allergy decomposition substance
ARTCOOL Mirror
Mirror
Standard
Step 1
Silver
White
Step 2
Allergen is captured by filter
The apatite and organic / inorganic binder surrounds the allergen
Virus
Kimchi Extract & Protein Contol Substance
Step 3 Purified air
Certified by British Allergy Foundation (2009.01)
NEW
Virus Filter 5K / 7K / 9K / 12K / 15K / 18K / 24K
30K / 36K
Sterilising filter with anti-virus coating
Step 1 Virus is captured by filter
Step 2 Virus membrane is destroyed by agent composed of kimchi extract
Step 3 Purified air
Certified by Kitasato Institute
Solution
LG
106
107
WALL MOUNTED UNIT INDOOR UNIT
Installation Support Clip
Wider Tubing Space
The triple filter consists of three special filters that can reduce the side effects caused by some organic compounds including formaldehyde. It has the ability to remove unpleasant odours and can create a more comfortable environment.
A support clip creates adequate space between the wall and the unit for easier installation.
The tubing space is up to 45% wider than previous models for easier installation.The tubing space is wider than many products currently on the market.
• Red filter removes smells such as smoke and food smells. • Black filter removes the odour of new buildings such as formaldehyde. • Blue filter removes the chemical smells such as the smell of fresh paint.
45% 25˚ VOC filter removes odour and hazardous VOCs that are discharged from household materials made out of chemical substances (Carpet, Paint, Cleaners, Furniture etc.) (VOC= Volatile Organic Compound) Formaldehyde filter removes formaldehyde, a leading cause of sick building syndrome, and can prevent dermatitis, vomiting, and pneumonia Common odour filter removes ordinary odours that can cause migraines and chronic fatigue syndrome
Conventional
165mm
Eliminating (Plasma Filter)
Auto Cleaning
The plasma air purifying system, first developed by LG, reduces the presence of microscopic contaminants that cause allergies and asthma, such as dust particles, mites and pet fur.
A major cause of air conditioner odours is mould and bacteria that can breed in the heat exchanger. The auto clean function dries the wet heat exchanger to prevent mould and bacteria from breeding which can significantly reduce smells and saves the user from frequent cleaning.
Polluted Air
Ionising
Filtering
Deodorising
LG
Odor Clean Air Dust Particles
Powerful Cooling & Heating Dust Charging (+) Odour Decomposition
Filtering of Dust by Coulomb Force
Deodorisation The opening of the front panel reduces the overload from the air intake.
* Except ARNU30GSVA4, ARNU36GSVA4
Low Noise Level The indoor unit operates quietly in sleep mode for peace and quiet for in bedroom or office. For example, LG model ARNU09GSBL2, ARNU12GSBL2 in sleep mode is only 19dB. In addition, the indoor units have reduced vibration and noise thanks to a super quiet fan and motor.
Skew Fan
Conventional
When the fan rotates, the stabilser and the fan blade are not in parallel (=The contact of points) Instantaneous pressure change is small.
When the fan rotates, the stabilser and the fan blade are in parallel (=the contact of lines) Instantaneous pressure change is great.
Stabilizer
Fan Rotates
Stabilizer
3dB 22dB 19dB
20m
The new and improved skew fan increases the amount of airflow.
20m Windblast
Optimised Airflow
Quick Cooling & Heating
Direction of horizontal vane can be adjusted from step 1 to step 6 with full auto swing. This function can cool and heat specific areas much faster.
Jet cooling and heating disperses air evenly at high speed to secure an optimally cooled or heated room in just 3 minutes.
6 Step Vertical Vane
Fan Rotates Conventional
LG * Only for ARNU30GSVA4 / ARNU36GSVA4
Wall Mounted Unit
Deodorising (Triple Filter)
108
Solution
LG
109
ARTCOOL MIRROR
ARTCOOL MIRROR
Mirror (R)
White (W)
ARNU18GSC*4 / ARNU24GSC*4
Mirror (R)
White (W)
Silver (V)
Model
Independent Unit
Capacity Power Input
ARNU05GSB*4
ARNU07GSB*4
ARNU09GSB*4
ARNU12GSB*4
ARNU15GSB*4
Cooling
Nom
kW
1.6
2.2
2.8
3.6
4.5
Heating
Nom
kW
1.8
2.5
3.2
4.0
5.0
Cooling / Heating
Nom 1)
W
12
13
15
19
21
Cooling / Heating
Rated 2) W
21
21
21
21
21
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
Ø / V / Hz
Power Supply
Model
Independent Unit
Capacity Power Input
H / M / L m3/min
6.5 / 6.0 / 5.5
7.0 / 6.5 / 5.5
8.2 / 7.0 / 5.5
9.5 / 8.2 / 6.5
10.5 / 9.0 / 7.0
Heating
H / M / L m3/min
6.5 / 6.0 / 5.5
7.0 / 6.5 / 5.5
8.2 / 7.0 / 5.5
9.5 / 8.2 / 6.5
10.5 / 9.0 / 7.0
Sound Pressure
H / M / L dBA
30 / 29 / 28
32 / 30 / 28
34 / 32 / 28
37 / 34 / 30
42 / 39 / 32
Sound Pressure
Sound Power
H / M / L dBA
54 / 53 / 52
54 / 53 / 52
55 / 54 / 52
55 / 54 / 53
58 / 56 / 54
Sound Power
W x H x D mm
895 × 285 × 205
895 × 285 × 205
895 × 285 × 205
895 × 285 × 205
895 × 285 × 205
Dimensions Net Weight
Dimensions
Body
Net Weight Piping Connection
kg
10.8
10.8
10.8
10.8
10.8
Liquid
mm
6.35
6.35
6.35
6.35
6.35
Gas
mm
12.7
12.7
12.7
12.7
12.7
mm
16.0
16.0
16.0
16.0
16.0
Drain
I.D
ARNU24GSC*4
Nom
kW
5.6
7.1
Heating
Nom
kW
6.3
8.0
Cooling / Heating
Nom 1)
W
27
39
Cooling / Heating
Rated 2) W
40
40 1 / 220~240 / 50 1 / 220 / 60
Ø / V / Hz
1 / 220~240 / 50 1 / 220 / 60
Cooling
H / M / L m3/min
12.5 / 12.0 / 11.3
14.0 / 12.7 / 11.5
Heating
H / M / L m3/min
12.5 / 12.0 / 11.3
14.0 / 12.7 / 11.5
H / M / L dBA
38 / 35 / 33
43 / 39 / 35
H / M / L dBA
57 / 54 / 52
62 / 58 / 54
W x H x D mm
1,030 × 325 × 245
1,030 × 325 × 245 15.4
Power Supply
Cooling
Airflow Rate
ARNU18GSC*4
Cooling
Airflow Rate
Piping Connection
Body
kg
15.4
Liquid
mm
6.35
9.52
Gas
mm
12.7
15.88
mm
16.0
16.0
Drain
I.D
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’
Accessories
Accessories
Model
ARNU05GSB*4
ARNU07GSB*4
Simple (1 Contact Point with Case) 2 Contact Point Dry Contact For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication EEV Kit for MULTI V Indoor
ARNU09GSB*4
Wired Remote Controller Premium
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTB001 (White)
PREMTBB01 (Black)
ARNU12GSB*4
ARNU15GSB*4
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
Model
ARNU18GSC*4
Simple (1 Contact Point with Case) 2 Contact Point Dry Contact For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication EEV Kit for MULTI V Indoor
PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500 PRGK024A0
Wireless Remote Controller
PQWRHQ0FDB
ARNU24GSC*4 PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500 PRGK024A0
Wired Remote Controller Premium
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTB001 (White)
PREMTBB01 (Black)
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
Wireless Remote Controller
PQWRHQ0FDB
Wall Mounted Unit
Silver (V)
INDOOR UNIT
ARNU05GSB*4 / ARNU07GSB*4 / ARNU09GSB*4 ARNU12GSB*4 / ARNU15GSB*4
110
Solution
LG
111
ARTCOOL GALLERY
STANDARD ARNU05GSBL4 / ARNU07GSBL4 / ARNU09GSBL4 / ARNU12GSBL4 / ARNU15GSBL4 ARNU18GSCL4 / ARNU24GSCL4 / ARNU30GSVA4 / ARNU36GSVA4
INDOOR UNIT
ARNU07GSF14 / ARNU09GSF14 / ARNU12GSF14
NEW
Independent Unit
Capacity Power Input
Nom
kW
2.2
2.8
3.6
Nom
kW
2.5
3.2
4.0
Cooling / Heating
Nom 1)
W
28
28
35
Cooling / Heating
Rated 2) W
35
35
35
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
Ø / V / Hz Cooling
H / M / L m3/min
8.1 / 6.3 / 4.2
8.1 / 6.3 / 4.2
9.3 / 7.7 / 6.0
Heating
H / M / L m3/min
8.1 / 6.3 / 4.2
8.1 / 6.3 / 4.2
9.3 / 7.7 / 6.0
H / M / L dBA
38 / 32 / 27
38 / 32 / 27
44 / 38 / 32
Sound Power Body
H / M / L dBA
48 / 44 / 39
48 / 44 / 39
54 / 48 / 42
W x H x D mm
600 X 600 X 146
600 X 600 X 146
600 X 600 X 146
Net Weight Piping Connection
ARNU12GSF14
Heating
Sound Pressure Dimensions
ARNU09GSF14
Cooling
Power Supply Airflow Rate
ARNU07GSF14
kg
15.0
15.0
15.0
Liquid
mm
6.35
6.35
6.35
Gas
mm
12.7
12.7
12.7
mm
12.2
12.2
12.2
Drain
I.D
Model
Independent Unit
Capacity
Power Input
Cooling Heating Cooling / Heating Cooling / Heating
Power Supply Cooling Heating Sound Pressure Sound Power Dimensions Body Net Weight Liquid Piping Gas Connection Drain Airflow Rate
Nom Nom
kW kW
1.6 1.8
2.2 2.5
2.8 3.2
3.6 4.0
4.5 5.0
5.6 6.3
7.1 8.0
8.8 9.4
10.4 10.8
Nom 1) W
12
13
15
19
21
27
39
67
104
Rated
21
2)
W
/ 50 Ø / V / Hz 1 /1220~240 / 220 / 60 H / M / L m3/min 6.5 / 6.0 / 5.5 H / M / L m3/min 6.5 / 6.0 / 5.5 H / M / L dBA 30 / 29 / 28 H / M / L dBA 54 / 53 / 52 W x H x D mm 895 × 289 × 215 kg 10.0 mm 6.35 mm 12.7 I.D mm 16.0
21
21
21
21
40
40
154
154
1 / 220~240 / 50 1 / 220 / 60 7.0 / 6.5 / 5.5 7.0 / 6.5 / 5.5 32 / 30 / 28 54 / 53 / 52 895 × 289 × 215 10.0 6.35 12.7 16.0
1 / 220~240 / 50 1 / 220 / 60 8.2 / 7.0 / 5.5 8.2 / 7.0 / 5.5 34 / 32 / 28 55 / 54 / 52 895 × 289 × 215 10.0 6.35 12.7 16.0
1 / 220~240 / 50 1 / 220 / 60 9.5 / 8.2 / 6.5 9.5 / 8.2 / 6.5 37 / 34 / 30 55 / 54 / 53 895 × 289 × 215 10.0 6.35 12.7 16.0
1 / 220~240 / 50 1 / 220 / 60 10.5 / 9.0 / 7.0 10.5 / 9.0 / 7.0 40 / 36 /32 58 / 56 / 54 895 × 289 × 215 10.0 6.35 12.7 16.0
1 / 220~240 / 50 1 / 220 / 60 12.5 / 12.0 / 11.3 12.5 / 12.0 / 11.3 38 / 35 / 33 57 / 54 / 52 1,030 × 325 × 255 14.0 6.35 12.7 16.0
1 / 220~240 / 50 1 / 220 / 60 14.0 / 12.7 / 11.5 14.0 / 12.7 / 11.5 43 / 39 / 35 62 / 58 / 54 1,030 × 325 × 255 14.0 9.52 15.88 16.0
1 / 220~240 / 50 1 / 220 / 60 23.0 / 20.0 / 17.0 23.0 / 20.0 / 17.0 49 / 44 / 42 61 / 58 / 55 1,190 x 346 x 265 16.6 9.52 15.88 16.0
1 / 220~240 / 50 1 / 220 / 60 26.0 / 23.0 / 19.0 26.0 / 23.0 / 19.0 52 /47/ 43 63 / 60 / 57 1,190 x 346 x 265 16.6 9.52 15.88 16.0
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’
Accessories
Accessories
Model
ARNU07GSF14
Simple (1 Contact Point with Case) 2 Contact Point Dry Contact For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication EEV Kit for MULTI V Indoor
ARNU09GSF14
Wired Remote Controller Premium
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTB001 (White)
PREMTBB01 (Black)
ARNU12GSF14
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
Model
ARNU05GSBL4 ARNU07GSBL4 ARNU09GSBL4 ARNU12GSBL4 ARNU15GSBL4 ARNU18GSCL4 ARNU24GSCL4 ARNU30GSVA4 ARNU36GSVA4
Simple (1 Contact Point with Case) 2 Contact Point Dry Contact For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication EEV Kit for MULTI V Indoor
PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500 PRGK024A0
Wireless Remote Controller
PQWRHQ0FDB
NEW
ARNU05GSBL4 ARNU07GSBL4 ARNU09GSBL4 ARNU12GSBL4 ARNU15GSBL4 ARNU18GSCL4 ARNU24GSCL4 ARNU30GSVA4 ARNU36GSVA4
PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500 -
PRGK024A0
Wired Remote Controller Premium
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTB001 (White)
PREMTBB01 (Black)
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
Wireless Remote Controller
PQWRHQ0FDB
Wall Mounted Unit
NEW
Model
Solution
LG
112
113
INDOOR UNIT
CEILING MOUNTED CASSETTE (4 WAY) NEW
Compact and Stylish Design
Independent Vane Control
• New 4 Way cassette panel adapted unibody shape and matching with into the ceiling • Panel size is fit into the ceiling tile
The Independent Vane Operation feature uses separate motors, making it possible to control all four vanes independently.
All Vane Operation
Independent Vane Control
Unibody Shape
Indirect Air Flow
620m
m
(No Inlet Line)
620m
m
Compact Size The indoor unit with slim and compact dimensions has reduced the restriction which enables successful installation in various spaces.
Auto Elevation Grille The Independent Vane Operation feature uses separate motors, making it possible to control all four vanes independently. Easy filter cleaning with elevation grill.
4-Point Support Structure
Auto Leveling
Capacity
Height
7.1 ~ 9.0kW
204mm
10.6kW
246mm
12.3 ~ 15.8kW
288mm
Length Width : 840 x 840mm
Memory for User’s Level
Auto Stop Detection STOP
Memory
Prevent Ceiling Pollution Coanda design of air outlet can prevent contamination of ceiling.
Max. 4.5m
* Operating with wired remote controller (Model Name : PREMTB001,PREMTBB01) and wireless remote controller included in PTEGM0. * Except ARNU05GTRC4, ARNU07GTRC4, ARNU09GTRC4, ARNU12GTRC4,Product ARNU15GTQC4, ARNU18GTQC4, ARNU21GTQC4 Louver * Applied to Cassette panel PT-UMC1
Coanda Design Ceiling
Ceiling Pollutions
Product Louver
Conventional Ceiling
Product Louver
Ceiling
Ceiling Pollutions
Ceiling Mounted Cassette
Direct Air Flow
LG
Solution
114
115
CEILING MOUNTED CASSETTE (1 WAY)
INDOOR UNIT
CEILING MOUNTED CASSETTE (4 WAY / 2 WAY)
6-Step Vane Control
Flexible connection of remote controller. - Group control : 1 remote controller up to 16 indoor units. / Second remote control : 2 remote controllers to 1 indoor unit.
There are 6 different steps to control air flow direction. Also 1 Way cassette has vane to move auto swing between left and right as 120 degree.
Easy & Solid Attachment to the Wall
Moving Air Flow_1 Way Cassette
Fixed Air Flow_Duct System
Left and Right (Auto Swing)
Up and Down (6 step)
20˚ wall
wall
120˚
Adjustable Vane 70˚
Convenient Panel Installation The detachable corner design makes it easy to adjust the hanger during installation and to check for leakages in the drain connection pipe.
Detachable Corner Design
Drain leakage Check
Hanger Adjust
Minimized Height LG 1 Way cassette isn’t affected by installation environment. LG 1 Way cassette height is 132mm and duct is 190mm, so it can provide ideal solution for installation in limited space.
Refrigerant piping check and Hanger adjust
Drain leakage check and hanger adjust
Hanger adjust
Hanger adjust
Size Comparison LG It is easy to install the panel to the body, using the button type panel design.
(Unit : mm)
A Company B Company
1 Way Cassette
132
215
230
Duct
190
200
200
132mm 190mm
Flexible Installation 2 Way Air Flow without Temperature Variation
The access for inspection at 1 Way Cassette does not require additional ducted space making the installation environment uncomplicated.
2 Way cassette is suitable for narrow type of space such as office / hotel / dormitory corridor and it provides thermal comfort without temperature variation.
1 Way Cassette
Duct Duct
Inspection hole
Ceiling Mounted Cassette
Flexible Connection
116
Solution
LG
117
4 WAY CASSETTE (570×570)
4 WAY CASSETTE (840×840) ARNU24GTPC4 / ARNU28GTPC4 / ARNU30GTPC4 / ARNU36GTNC4 ARNU42GTMC4 / ARNU48GTMC4 / ARNU54GTMC4
NEW
Model
Independent Unit Nom Nom Nom 1) Rated 2)
kW kW W W
1.6 1.8 13 Power Input 30 / 50 Ø / V / Hz 1 /1220~240 Power Supply / 220 / 60 Cooling H / M / L m3/min 7.5 / 7.0 / 6.6 Airflow Rate Heating H / M / L m3/min 7.5 / 7.0 / 6.6 Sound Pressure H / M / L dBA 29 / 27 / 26 Sound Power H / M / L dBA 46 / 44 / 43 Dimensions Body W x H x D mm 570 x 214 x 570 Net Weight kg 12.6 Liquid mm 6.35 Piping Gas mm 12.7 Connection Drain I.D mm 25.0 Model PT-UQC Morning Fog Color (RAL Code) Decoration (RAL 120-4) Panel 1 W x H x D mm 700 x 22 x 700 Dimensions Weight kg 3.0 Model PT-QCHW0 Morning Fog Color (RAL Code) Decoration (RAL 120-4) Panel 2 W x H x D mm 620 x 35 x 620 Dimensions Weight kg 3.1 Capacity
2.2 2.5 13 30 1 / 220~240 / 50 1 / 220 / 60 7.5 / 7.0 / 6.6 7.5 / 7.0 / 6.6 29 / 27 / 26 46 / 44 / 43 570 x 214 x 570 12.6 6.35 12.7 25.0 PT-UQC Morning Fog (RAL 120-4) 700 x 22 x 700 3.0 PT-QCHW0 Morning Fog (RAL 120-4) 620 x 35 x 620 3.1
2.8 3.2 14 30 1 / 220~240 / 50 1 / 220 / 60 8.0 / 7.5 / 7.1 8.0 / 7.5 / 7.1 30 / 29 / 27 47 / 46 / 44 570 x 214 x 570 13.7 6.35 12.7 25.0 PT-UQC Morning Fog (RAL 120-4) 700 x 22 x 700 3.0 PT-QCHW0 Morning Fog (RAL 120-4) 620 x 35 x 620 3.1
3.6 4.0 17 30 1 / 220~240 / 50 1 / 220 / 60 8.7 / 8.0 / 7.0 8.7 / 8.0 / 7.0 32 / 30 / 27 48 / 47 / 44 570 x 214 x 570 13.7 6.35 12.7 25.0 PT-UQC Morning Fog (RAL 120-4) 700 x 22 x 700 3.0 PT-QCHW0 Morning Fog (RAL 120-4) 620 x 35 x 620 3.1
4.5 5.0 24 30 1 / 220~240 / 50 1 / 220 / 60 11.0 / 10.0 / 9.3 11.0 / 10.0 / 9.3 36 / 34 / 32 51 / 49 / 47 570 x 256 x 570 15.0 6.35 12.7 25.0 PT-UQC Morning Fog (RAL 120-4) 700 x 22 x 700 3.0 PT-QCHW0 Morning Fog (RAL 120-4) 620 x 35 x 620 3.1
5.6 6.3 25 30 1 / 220~240 / 50 1 / 220 / 60 11.2 / 11.0 / 10.0 11.2 / 11.0 / 10.0 37 / 35 / 34 52 / 50 / 49 570 x 256 x 570 15.0 6.35 12.7 25.0 PT-UQC Morning Fog (RAL 120-4) 700 x 22 x 700 3.0 PT-QCHW0 Morning Fog (RAL 120-4) 620 x 35 x 620 3.1
6.0 6.8 28 30 1 / 220~240 / 50 1 / 220 / 60 12.0 / 11.1 / 9.4 12.0 / 11.1 / 9.4 40 / 38 / 34 55 / 53 / 49 570 x 256 x 570 15.0 9.52 15.88 25.0 PT-UQC Morning Fog (RAL 120-4) 700 x 22 x 700 3.0 PT-QCHW0 Morning Fog (RAL 120-4) 620 x 35 x 620 3.1
NEW
Model
Independent Unit
Capacity
Cooling
Nom
kW
7.1
8.2
9.0
10.6
12.3
14.1
15.8
Heating
Nom
kW
8.0
9.2
10.0
11.9
13.8
15.9
18.0
W
31
40
40
70
104
120
135
Cooling / Heating Rated 2) W
40
40
40
144
144
144
144
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
Cooling / Heating Nom 1)
Power Input
Ø / V / Hz
1 / 220~240 / 50 1 / 220 / 60
Cooling
H / M / L m3/min
17.0 / 15.0 / 13.0
19.0 / 16.0 / 14.0
24.3 / 22.8 / 19.5
25.0 / 21.0 / 19.0
30.0 / 27.0 / 24.0
31.0 / 29.0 / 27.0
34.0 / 32.0 / 27.0
Heating
H / M / L m3/min
17.0 / 15.0 / 13.0
19.0 / 16.0 / 14.0
24.3 / 22.8 / 19.5
25.0 / 21.0 / 19.0
30.0 / 27.0 / 24.0
31.0 / 29.0 / 27.0
34.0 / 32.0 / 27.0 50 / 48 / 44
Power Supply Airflow Rate
NEW
ARNU24GTPC4 ARNU28GTPC4 ARNU30GTPC4 ARNU36GTNC4 ARNU42GTMC4 ARNU48GTMC4 ARNU54GTMC4
Sound Pressure
H / M / L dBA
36 / 34 / 31
39 / 35 / 33
40 / 36 / 33
43 / 40 / 37
44 / 41 / 38
46 / 43 / 41
Sound Power
H / M / L dBA
55 / 53 / 50
56 / 54 / 52
57 / 54 / 52
62 / 59 / 56
63 / 59 / 56
65 / 61 / 59
69 / 67 / 63
W x H x D mm
840 x 204 x 840
840 x 204 x 840
840 x 204 x 840
840 x 246 x 840
840 x 288 x 840
840 x 288 x 840
840 x 288 x 840 26.5
Dimensions
Body
Net Weight Piping Connection
kg
20.8
20.8
20.8
23.5
25.6
25.6
Liquid
mm
9.52
9.52
9.52
9.52
9.52
9.52
9.52
Gas
mm
15.88
15.88
15.88
15.88
15.88
15.88
15.88
Drain
I.D
mm
Model Color (RAL Code)
Decoration Panel
W x H x D mm
Dimensions Weight
25.0
25.0
25.0
25.0
25.0
25.0
25.0
PT-UMC1
PT-UMC1
PT-UMC1
PT-UMC1
PT-UMC1
PT-UMC1
PT-UMC1
Morning Fog (RAL 120-4)
Morning Fog (RAL 120-4)
Morning Fog (RAL 120-4)
Morning Fog (RAL 120-4)
Morning Fog (RAL 120-4)
Morning Fog (RAL 120-4)
Morning Fog (RAL 120-4)
950 x 25 x 950
950 x 25 x 950
950 x 25 x 950
950 x 25 x 950
950 x 25 x 950
950 x 25 x 950
950 x 25 x 950
5.6
5.6
5.6
5.6
5.6
5.6
5.6
kg
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’
Accessories
Accessories
Model Dry Contact
ARNU05GTRC4 ARNU07GTRC4 ARNU09GTRC4 ARNU12GTRC4 ARNU15GTQC4 ARNU18GTQC4 ARNU21GTQC4 Simple (1 Contact Point with Case) 2 Contact Point For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication
PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500 PT-QCHW0 / PT-UQC PTVK430
Front Panel Ventilation Kit EEV Kit for MULTI V Indoor
PRGK024A0
Wired Remote Controller Premium
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTB001 (White)
PREMTBB01 (Black)
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
Model Dry Contact
-
Wireless Remote Controller
PQWRHQ0FDB
ARNU24GTPC4 ARNU28GTPC4 ARNU30GTPC4 ARNU36GTNC4 ARNU42GTMC4 ARNU48GTMC4 ARNU54GTMC4 Simple (1 Contact Point with Case) 2 Contact Point For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication
PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500 PT-UMC1 PTEGM0 PTVK410 / PTVK420 / PTVK430
Front Panel Auto Elevation Grille Ventilation Kit
Wired Remote Controller Premium
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTB001 (White)
PREMTBB01 (Black)
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
Wireless Remote Controller
PQWRHQ0FDB
Ceiling Mounted Cassette
Cooling Heating Cooling / Heating Cooling / Heating
ARNU05GTRC4 ARNU07GTRC4 ARNU09GTRC4 ARNU12GTRC4 ARNU15GTQC4 ARNU18GTQC4 ARNU21GTQC4
INDOOR UNIT
ARNU05GTRC4 / ARNU07GTRC4 / ARNU09GTRC4 / ARNU12GTRC4 ARNU15GTQC4 / ARNU18GTQC4 / ARNU21GTQC4
118
Solution
LG
119
2 WAY CASSETTE
1 WAY CASSETTE
Model
Independent Unit
Power Input
ARNU09GTLC4
ARNU12GTLC4
ARNU18GTLC4
ARNU24GTLC4
Cooling
Nom
kW
2.8
3.6
5.6
7.1
Heating
Nom
kW
3.2
4.0
6.3
8.0
Cooling / Heating
Nom 1)
W
28
30
34
40
Cooling / Heating
Rated 2) W
70
70
70
70
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
Power Supply Airflow Rate
Power Supply
Ø / V / Hz Cooling
H / M / L m3/min
9.0 / 8.0 / 7.0
10.0 / 9.0 / 8.0
13.0 / 12.0 / 10.0
17.0 / 15.0 / 13.0
Heating
H / M / L m3/min
9.0 / 8.0 / 7.0
10.0 / 9.0 / 8.0
13.0 / 12.0 / 10.0
17.0 / 15.0 / 13.0
Sound Pressure
H / M / L dBA
36 / 34 / 32
38 / 36 / 32
40 / 36 / 32
42 / 38 / 34
Sound Power
H / M / L dBA
55 / 53 / 51
58 / 55 / 51
59 / 55 / 51
61 / 58 / 53
W x H x D mm
Airflow Rate
Dimensions
Body
Net Weight Liquid Piping Connection
Gas Drain
Decoration Panel
I.D
830 × 225 × 550
830 × 225 × 550
830 × 225 × 550
830 × 225 × 550
kg
20.6
20.6
20.6
20.6
mm
6.35
6.35
6.35
9.52
mm
12.7
12.7
12.7
15.88
mm
25.0
25.0
25.0
25.0
Model
PT-HLC
PT-HLC
PT-HLC
PT-HLC
Color
Morning Fog (RAL 120-4)
Morning Fog (RAL 120-4)
Morning Fog (RAL 120-4)
Morning Fog (RAL 120-4)
1,050 x 28 x 640
1,050 x 28 x 640
1,050 x 28 x 640
1,050 x 28 x 640
4.0
4.0
4.0
4.0
Dimensions
W x H x D mm
Weight
kg
Model
Independent Unit
Capacity Power Input
ARNU07GTUC4
ARNU09GTUC4
ARNU12GTUC4
ARNU18GTTC4
ARNU24GTTC4
Cooling
Nom
kW
2.2
2.8
3.6
5.6
7.1
Heating
Nom
kW
2.5
3.2
4.0
6.3
7.1
Cooling / Heating
Nom 1)
W
20
22
24
38
51
Cooling / Heating
Rated 2) W
40 1 / 220~240 / 50 1 / 220 / 60 9.2 / 8.6 / 8.2
40 1 / 220~240 / 50 1 / 220 / 60 10.0 / 9.2 / 8.2
70 1 / 220~240 / 50 1 / 220 / 60 13.3 / 12.1 / 10.9
70 1 / 220~240 / 50 1 / 220 / 60 14.6 / 13.3 / 11.5
Cooling
H / M / L m3/min
40 1 / 220~240 / 50 1 / 220 / 60 8.2 / 7.3 / 6.4
Heating
Ø / V / Hz H / M / L m3/min
8.2 / 7.3 / 6.4
9.2 / 8.6 / 8.2
10.0 / 9.2 / 8.2
13.3 / 12.1 / 10.9
14.6 / 13.3 / 11.5
Sound Pressure
H / M / L dBA
32 / 29 / 25
35 / 34 / 32
38 / 35 / 32
40 / 37 / 35
43 / 40 / 36
Sound Power
H / M / L dBA
50 / 47 / 43
53 / 52 / 50
57 / 53 / 50
59 / 56 / 54
62 / 59 / 55
W x H x D mm
860 x 132 x 450
860 x 132 x 450
860 x 132 x 450
1,180 x 132 x 450
1,180 x 132 x 450 15.6
Dimensions
Body
Net Weight Piping Connection
kg
13.6
13.6
13.6
15.6
Liquid
mm
6.35
6.35
6.35
6.35
9.52
Gas
mm
12.7
12.7
12.7
12.7
15.88
Drain
I.D
mm
25.0 25.0 25.0 25.0 PT-UUC (Grill) / PT-UUC (Grill) / PT-UUC (Grill) / PT-UTC (Grill) / PT-UUD (Panel) PT-UUD (Panel) PT-UUD (Panel) PT-UTD (Panel) Noble White (RAL 110-1) Noble White (RAL 110-1) Noble White (RAL 110-1) Noble White (RAL 110-1)
Model Decoration Panel
Color (RAL Code) Dimensions
W x H x D mm
Weight
kg
1,100 x 34 x 500
1,100 x 34 x 500
1,100 x 34 x 500
1,420 x 34 x 500
1,420 x 34 x 500
4.6
4.6
4.6
5.5
5.5
ARNU18GTTC4
ARNU24GTTC4
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’
Accessories
Accessories
Model Dry Contact
ARNU09GTLC4
ARNU12GTLC4
Simple (1 Contact Point with Case) 2 Contact Point For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication
Front Panel EEV Kit for MULTI V Indoor
ARNU18GTLC4
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTB001 (White)
PREMTBB01 (Black)
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
Model Dry Contact
-
PRGK024A0
Wired Remote Controller Premium
ARNU24GTLC4
PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500 PT-HLC
Wireless Remote Controller
PQWRHQ0FDB
ARNU07GTUC4
ARNU09GTUC4
ARNU12GTUC4
Simple (1 Contact Point with Case) 2 Contact Point For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication
Front Panel EEV Kit for MULTI V Indoor
PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500 PT-UUC (Grill) / PT-UUD (Panel) PRGK024A0
PT-UTC (Grill) / PT-UTD (Panel) -
Wired Remote Controller Premium
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTB001 (White)
25.0 PT-UTC (Grill) / PT-UTD (Panel) Noble White (RAL 110-1)
PREMTBB01 (Black)
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
Wireless Remote Controller
PQWRHQ0FDB
Ceiling Mounted Cassette
Capacity
ARNU07GTUC4 / ARNU09GTUC4 / ARNU12GTUC4 ARNU18GTTC4 / ARNU24GTTC4
INDOOR UNIT
ARNU09GTLC4 / ARNU12GTLC4 ARNU18GTLC4 / ARNU24GTLC4
LG
Solution
120
121
CEILING CONCEALED DUCT INDOOR UNIT
Operation for Multiple Rooms
Minimized Height
Using a spiral duct (Embedded or flexible type) and stream chamber, it is possible to operate cooling / heating for several rooms simultaneously.
New mid-static ducts provide ideal solution for installation in limited space.
270mm
380 mm
298 mm
270 mm
E.S.P. (External Static Pressure) Control E.S.P. control function can make air volume controlled easily with remote controller. The BLDC motor can control fan speed and air volume regardless of the external static pressure. No additional accessories are necessary to control air flow. E.S.P. Control
Conventional
Ceiling Concealed Duct
12.5kW
8 / 10kW
New
270 mm Conventional
New
E.S.P. Control
Flexible Installation (Low Static Duct Only) The new low static duct allows the air intake at the rear or bottom under installation condition.
Conventional
New Low Static Duct Comfort Cooling / Heating
Comfort Cooling / Heating
Two Thermistors Control The indoor temperature can be checked using the thermistors in the remote controller as well as from the indoor unit. There may be a significant difference between ceiling and floor air temperature. Two thermistors can optimise indoor air temperature for a more comfortable environment.
Indoor Unit Thermistor
Compares temperatures sensed from different positions, and automatically selects the optimum temperature for users.
Remote Controller Thermistor
Air intake at the rear or bottom
Air intake at the only rear
122
Solution
LG
123
MID / HIGH STACTICS
MID / HIGH STACTICS
Independent Unit
Capacity
Power Input
Cooling Heating Cooling / Heating Cooling / Heating
kW kW
2.2 2.5
2.8 3.2
3.6 4.0
4.5 5.0
5.6 6.3
7.1 8.0
Nom 1)
W
39
40
46
67
85
91
Cooling Heating External Static Pressure Sound Pressure Sound Power Dimensions Body Net Weight Liquid Piping Connection Gas Drain
Model
Independent Unit
Capacity
Power Input Rated
2)
Power Supply Airflow Rate
ARNU07GM1A4 ARNU09GM1A4 ARNU12GM1A4 ARNU15GM1A4 ARNU18GM1A4 ARNU24GM1A4
Nom Nom
W Ø / V / Hz
H/M/L H/M/L Min ~ Max H/M/L H/M/L WxHxD
I.D
m3/min m3/min mmAq(Pa) dBA dBA mm kg mm mm mm
190
190
190
190
190
190
1 / 220~240 / 50 1 / 220 / 60 9.0 / 7.5 / 6.0 9.0 / 7.5 / 6.0 2(20) ~ 15(147) 26 / 24 / 23 55 / 54 / 51 900 × 270 × 700 25.5 6.35 12.7 25.0
1 / 220~240 / 50 1 / 220 / 60 9.5 / 7.5 / 6.0 9.5 / 7.5 / 6.0 2(20) ~ 15(147) 27 / 25 / 23 55 / 54 / 52 900 × 270 × 700 25.5 6.35 12.7 25.0
1 / 220~240 / 50 1 / 220 / 60 11.0 / 9.0 / 7.0 11.0 / 9.0 / 7.0 2(20) ~ 15(147) 27 / 25 / 23 55 / 54 / 52 900 × 270 × 700 25.5 6.35 12.7 25.0
1 / 220~240 / 50 1 / 220 / 60 16.0 / 12.0 / 9.0 16.0 / 12.0 / 9.0 2(20) ~ 15(147) 30 / 27 / 23 56 / 54 / 53 900 × 270 × 700 25.5 6.35 12.7 25.0
1 / 220~240 / 50 1 / 220 / 60 17.0 / 14.5 / 12.0 17.0 / 14.5 / 12.0 2(20) ~ 15(147) 31 / 28 / 25 58 / 56 / 54 900 × 270 × 700 25.5 6.35 12.7 25.0
1 / 220~240 / 50 1 / 220 / 60 19.0 / 16.0 / 14.0 19.0 / 16.0 / 14.0 2(20) ~ 15(147) 32 / 29 / 26 59 / 58 / 56 900 × 270 × 700 26.5 9.52 15.88 25.0
Cooling Heating Cooling / Heating Cooling / Heating
Nom Nom
ARNU28GM2A4 ARNU36GM2A4 ARNU42GM2A4 ARNU48GM3A4 ARNU54GM3A4 ARNU76GB8A4 ARNU96GB8A4
kW kW
8.2 9.2
10.6 11.9
12.3 13.8
14.1 15.9
15.8 18.0
22.4 25.2
28.0 31.5
Nom 1)
W
123
184
231
172
260
747
800
Rated
W
350
350
350
400
400
800
800
2)
/ 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 Power Supply Ø / V / Hz 1 /1220~240 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 38.0 / 33.0 / 28.0 40.0 / 34.0 / 28.0 50.0 / 45.0 / 40.0 60.0 / 50.0 / 50.0 72.0 / 64.0 / 64.0 Cooling H / M / L m3/min 28.0 / 24.0 / 21.0 32.0 / 28.0 / 24.0 Airflow Rate Heating H / M / L m3/min 28.0 / 24.0 / 21.0 32.0 / 28.0 / 24.0 38.0 / 33.0 / 28.0 40.0 / 34.0 / 28.0 50.0 / 45.0 / 40.0 60.0 / 50.0 / 50.0 72.0 / 64.0 / 64.0 External Static Pressure Min ~ Max mmAq(Pa) 4(39) ~ 15(147) 4(39) ~ 15(147) 4(39) ~ 15(147) 4(39) ~ 15(147) 4(39) ~ 15(147) 6(59) ~ 25(245) 6(59) ~ 25(245) Sound Pressure H / M / L dBA 36 / 34 / 33 37 / 36 / 34 38 / 37 / 36 39 / 37 / 35 42 / 40 / 39 45 / 41 / 40 47 / 42 / 41 Sound Power H / M / L dBA 59 / 57 / 55 60 / 59 / 57 62 / 61 / 60 65 / 61 / 59 66 / 64 / 63 70 / 68 / 68 72 / 69 / 68 Dimensions Body W x H x D mm 1,250 × 270 × 700 1,250 × 270 × 700 1,250 × 270 × 700 1,250 × 360 × 700 1,250 × 360 × 700 1,562 x 460 x 688 1,562 x 460 x 688 Net Weight kg 38.0 38.0 39.5 44.0 44.0 87.0 87.0 Liquid mm 9.52 9.52 9.52 9.52 9.52 9.52 9.52 Piping Connection Gas mm 15.88 15.88 15.88 15.88 19.05 19.05 22.2 Drain I.D mm 25.0 25.0 25.0 25.0 25.0 25.0 25.0
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’ 4. The Sound Pressure test condition is based on 50 Pa for middle static duct.
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’ 4. B8 : The Sound Pressure test condition is based on 220 Pa (High Static Pressue) as standard. 5. The Sound Pressure test condition is based on 50 Pa for middle static duct.
Accessories
Accessories
Model
ARNU07GM1A4 ARNU09GM1A4 ARNU12GM1A4 ARNU15GM1A4 ARNU18GM1A4 ARNU24GM1A4
Simple (1 Contact Point with Case) 2 Contact Point Dry Contact For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication EEV Kit for MULTI V Indoor IR Receiver
PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500 PRGK024A0 PWLRVN000
Wired Remote Controller Premium
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTB001 (White)
PREMTBB01 (Black)
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
-
Wireless Remote Controller
PQWRHQ0FDB
Model
ARNU28GM2A4 ARNU36GM2A4 ARNU42GM2A4 ARNU48GM3A4 ARNU54GM3A4 ARNU76GB8A4 ARNU96GB8A4
Simple (1 Contact Point with Case) 2 Contact Point Dry Contact For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication EEV Kit for MULTI V Indoor IR Receiver
PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500 PWLRVN000
Wired Remote Controller Premium
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTB001 (White)
PREMTBB01 (Black)
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
Wireless Remote Controller
PQWRHQ0FDB
Ceiling Concealed Duct
Model
ARNU28GM2A4 / ARNU36GM2A4 / ARNU42GM2A4 / ARNU48GM3A4 ARNU54GM3A4 / ARNU76GB8A4 / ARNU96GB8A4
INDOOR UNIT
ARNU07GM1A4 / ARNU09GM1A4 / ARNU12GM1A4 ARNU15GM1A4 / ARNU18GM1A4 / ARNU24GM1A4
124
Solution
LG
125
LOW STACTICS
LOW STACTICS
Independent Unit
Capacity Power Input
ARNU05GL1G4
ARNU07GL1G4
ARNU09GL1G4
Cooling
Nom
kW
1.7
2.2
2.8
Heating
Nom
kW
1.9
2.5
3.2
Cooling / Heating
Nom 1)
W
29
31
39
Cooling / Heating
Rated 2) W
40
40
40
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
Ø / V / Hz
Power Supply Cooling
H / M / L m /min
6.7 / 6.2 / 5.5
7.5 / 6.5 / 5.5
9.0 / 7.0 / 5.5
Heating
H / M / L m3/min
6.7 / 6.2 / 5.5
7.5 / 6.5 / 5.5
9.0 / 7.0 / 5.5
External Static Pressure
Min ~ Max mmAq(Pa)
0(0) ~ 5(49)
0(0) ~ 5(49)
0(0) ~ 5(49)
Sound Pressure
H / M / L dBA
25 / 24 / 22
26 / 24 / 22
Sound Power
H / M / L dBA
47 / 46 / 44
W x H x D mm
Airflow Rate
Dimensions
3
Body
Net Weight Piping Connection
Capacity Power Input
ARNU12GL2G4
ARNU15GL2G4
ARNU18GL2G4
ARNU21GL3G4
ARNU24GL3G4
Cooling
Nom
kW
3.6
4.5
5.6
6.2
7.1
Heating
Nom
kW
4.0
5.0
6.3
7.0
8.0
Cooling / Heating
Nom 1)
W
41
56
71
72
103
Cooling / Heating
Rated 2) W Ø / V / Hz
Power Supply
85
85
85
115
115
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
H / M / L m3/min
10.0 / 8.5 / 7.0
12.5 / 10.0 / 8.5
15.0 / 12.5 / 10.0
17.5 / 14.0 / 12.0
20.0 / 16.0 / 12.0
Heating
H / M / L m3/min
10.0 / 8.5 / 7.0
12.5 / 10.0 / 8.5
15.0 / 12.5 / 10.0
17.5 / 14.0 / 12.0
20.0 / 16.0 / 12.0
External Static Pressure
Min ~ Max mmAq(Pa)
0(0) ~ 5(49)
0(0) ~ 5(49)
0(0) ~ 5(49)
0(0) ~ 5(49)
0(0) ~ 5(49)
28 / 25 / 22
Sound Pressure
H / M / L dBA
30 / 27 / 25
33 / 30 / 28
35 / 32 / 29
35 / 29 / 28
36 / 33 / 28
48 / 46 / 44
49 / 47 / 44
Sound Power
H / M / L dBA
52 / 49 / 46
53 / 52 / 50
54 / 53 / 52
56 / 53 / 51
58 / 54 / 51
700 x 190 x 700
700 x 190 x 700
700 x 190 x 700
Dimensions
W x H x D mm
900 x 190 x 700
900 x 190 x 700
900 x 190 x 700
1,100 × 190 × 700
1,100 × 190 × 700
Net Weight
27.0
kg
17.5
17.5
17.5
mm
6.35
6.35
6.35
Gas
mm
12.7
12.7
12.7
mm
25.4
25.4
25.4
I.D
Independent Unit
Cooling
Liquid Drain
Model
Airflow Rate
Piping Connection
Body
kg
23.0
23.0
23.0
27.0
Liquid
mm
6.35
6.35
6.35
9.52
9.52
Gas
mm
12.7
12.7
12.7
15.88
15.88
mm
25.4
25.4
25.4
25.4
25.4
ARNU21GL3G4
ARNU24GL3G4
Drain
I.D
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’ 4. L1 : The Sound Pressure test condition is based on 20 Pa (Static Pressue) as standard.
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’ 4. L2, L3 : The Sound Pressure test condition is based on 20 Pa (Static Pressue) as standard.
Accessories
Accessories
Model
ARNU05GL1G4
Simple (1 Contact Point with Case) 2 Contact Point Dry Contact For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication EEV Kit for MULTI V Indoor IR Receiver
ARNU07GL1G4
Wired Remote Controller Premium
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTB001 (White)
PREMTBB01 (Black)
ARNU09GL1G4
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
Model
ARNU12GL2G4
Simple (1 Contact Point with Case) 2 Contact Point Dry Contact For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication EEV Kit for MULTI V Indoor IR Receiver
PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500 PRGK024A0 PWLRVN000
Wireless Remote Controller
PQWRHQ0FDB
ARNU15GL2G4
ARNU18GL2G4 PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500
PRGK024A0
Wired Remote Controller Premium
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTB001 (White)
PREMTBB01 (Black)
-
PWLRVN000
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
Wireless Remote Controller
PQWRHQ0FDB
Ceiling Concealed Duct
Model
ARNU12GL2G4 / ARNU15GL2G4 / ARNU18GL2G4 ARNU21GL3G4 / ARNU24GL3G4
INDOOR UNIT
ARNU05GL1G4 / ARNU07GL1G4 / ARNU09GL1G4
126
Solution
LG
127
BUILT-IN
Capacity
Power Input
Cooling Heating Cooling / Heating Cooling / Heating
Cooling Heating External Static Pressure Sound Pressure Sound Power Dimensions Body Net Weight Liquid Piping Connection Gas Drain
ARNU07GB3G4 ARNU09GB3G4 ARNU12GB3G4 ARNU15GB3G4 ARNU18GB4G4 ARNU24GB4G4
Model Independent Unit ARNU07GBGA4 ARNU09GBGA4 ARNU12GBGA4 ARNU15GBGA4 ARNU18GBRA4 ARNU24GBRA4 ARNU28GBRA4 ARNU36GB8A4 ARNU42GB8A4 ARNU48GB8A4
Nom Nom
kW kW
2.2 2.5
2.8 3.2
3.6 4.0
4.5 5.0
5.6 6.3
7.1 8.0
Nom 1)
W
30
38
41
53
60
83
Rated 2) W
85
85
85
85
115
115
1 / 220~240 / 50 1 / 220 / 60 8.0 / 6.5 / 5.5 8.0 / 6.5 / 5.5 0(0) ~ 4(39) 33 / 32 / 29 53 / 52 / 49 820 x 190 x 575 21.0 6.35 12.7 25.4
1 / 220~240 / 50 1 / 220 / 60 9.0 / 7.0 / 6.0 9.0 / 7.0 / 6.0 0(0) ~ 4(39) 34 / 33 / 32 54 / 52 / 51 820 x 190 x 575 21.0 6.35 12.7 25.4
1 / 220~240 / 50 1 / 220 / 60 10.0 / 8.0 / 6.5 10.0 / 8.0 / 6.5 0(0) ~ 4(39) 35 / 34 / 33 55 / 53 / 52 820 x 190 x 575 21.0 6.35 12.7 25.4
1 / 220~240 / 50 1 / 220 / 60 11.0 / 10.0 / 8.0 11.0 / 10.0 / 8.0 0(0) ~ 4(39) 41 / 40 / 37 60 / 55 / 53 820 x 190 x 575 21.0 6.35 12.7 25.4
1 / 220~240 / 50 1 / 220 / 60 14.0 / 12.0 / 10.0 14.0 / 12.0 / 10.0 0(0) ~ 4(39) 43 / 40 / 37 61 / 58 / 55 1,100 x 190 x 575 26.0 6.35 12.7 25.4
1 / 220~240 / 50 1 / 220 / 60 17.0 / 15.0 / 10.0 17.0 / 15.0 / 10.0 0(0) ~ 4(39) 46 / 43 / 37 62 / 61 / 55 1,100 x 190 x 575 26.0 9.52 15.88 25.4
Power Supply Airflow Rate
ARNU07GBGA4 / ARNU09GBGA4 / ARNU12GBGA4 / ARNU15GBGA4 / ARNU18GBRA4 ARNU24GBRA4 / ARNU28GBRA4 / ARNU36GB8A4 / ARNU42GB8A4 / ARNU48GB8A4
Ø / V / Hz H/M/L H/M/L Min ~ Max H/M/L H/M/L WxHxD
I.D
m3/min m3/min mmAq(Pa) dBA dBA mm kg mm mm mm
Capacity Power Input
Cooling Heating Cooling / Heating Cooling / Heating
Nom Nom
kW kW
2.2 2.5
2.8 3.2
3.6 4.0
4.5 5.0
5.6 6.3
7.1 8.0
8.2 9.2
10.6 11.9
12.3 13.8
14.1 15.9
Nom 1)
W
50
50
50
130
130
233
402
420
528
538
Rated 2) W
450
450
450
450
450
450
450
800
800
800
Power Supply Airflow Cooling Rate Heating External Static Pressure Sound Pressure Sound Power
Ø/V / Hz m3/min m3/min mmAq (Pa) dBA dBA
H/M/L H/M/L Min ~ Max H/M/L H/M/L x H mm Dimensions Body W xD Net Weight kg Liquid mm Piping mm Connection Gas mm Drain I.D
1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 12.5 / 11.5 / 9.4 12.8 / 11.5 / 9.4 13.5 / 12.1 / 9.4 13.8 / 11.8 / 8.3 15.2 / 13.8 / 11.8 29.8 / 27.3 / 23.8 36.2 / 32.1 / 28.5 49.0 / 37.3 / 30.2 54.2 / 41.3 / 31.8 57.2 / 43.0 / 34.0 12.5 / 11.5 / 9.4 12.8 / 11.5 / 9.4 13.5 / 12.1 / 9.4 13.8 / 11.8 / 8.3 15.2 / 13.8 / 11.8 29.8 / 27.3 / 23.8 36.2 / 32.1 / 28.5 49.0 / 37.3 / 30.2 54.2 / 41.3 / 31.8 57.2 / 43.0 / 34.0 3(29) ~ 18(177) 3(29) ~ 18(177) 3(29) ~ 18(177) 3(29) ~ 18(177) 5(49) ~ 20(196) 5(49) ~ 20(196) 5(49) ~ 20(196) 6(59) ~ 25(245) 6(59) ~ 25(245) 6(59) ~ 25(245) 31 / 30 / 29 58 / 56 / 55 1,182 x 298 x 450 38.0 9.52 15.88 25.0
32 / 31 / 29 59 / 56 / 55 1,182 x 298 x 450 38.0 9.52 15.88 25.0
32 / 31 / 30 59 / 58 / 56 1,182 x 298 x 450 38.0 9.52 15.88 25.0
33 / 32 / 31 59 / 58 / 56 1,182 x 298 x 450 38.0 9.52 15.88 25.0
33 / 32 / 31 59 / 58 / 56 1,230 x 380 x 590 53.0 9.52 15.88 25.0
44 / 43 / 42 63 / 62 / 60 1,230 x 380 x 590 53.0 9.52 15.88 25.0
45 / 44 / 43 64 / 63 / 62 1,230 x 380 x 590 53.0 9.52 15.88 25.0
46 / 45 / 42 66 / 64 / 60 1,562 x 460 x 688 87.0 9.52 19.05 25.0
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’
Accessories
Accessories
Model
ARNU07GB3G4 ARNU09GB3G4 ARNU12GB3G4 ARNU15GB3G4 ARNU18GB4G4 ARNU24GB4G4
Simple (1 Contact Point with Case) 2 Contact Point Dry Contact For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication Suction Grille Suction Canvas EEV Kit for MULTI V Indoor IR Receiver
PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500 PBSGB30 PBSC30
PBSGB40 PBSC40 PRGK024A0 PWLRVN000
Wired Remote Controller Premium
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTB001 (White)
PREMTBB01 (Black)
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
-
Wireless Remote Controller
PQWRHQ0FDB
Model
47 / 46 / 43 67 / 66 / 62 1,562 x 460 x 688 87.0 9.52 19.05 25.0
47 / 46 / 44 67 / 66 / 63 1,562 x 460 x 688 87.0 9.52 19.05 25.0
ARNU07GBGA4 ARNU09GBGA4 ARNU12GBGA4 ARNU15GBGA4 ARNU18GBRA4 ARNU24GBRA4 ARNU28GBRA4 ARNU36GB8A4 ARNU42GB8A4 ARNU48GB8A4
Simple (1 Contact Point with Case) 2 Contact Point Dry Contact For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication EEV Kit for MULTI V Indoor IR Receiver
PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500 PRGK024A0
Wired Remote Controller Premium
PREMTA000 PREMTA000A PREMTA000B
-
PWLRVN000
Standard II
PREMTB001 (White)
PREMTBB01 (Black)
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
Wireless Remote Controller
PQWRHQ0FDB
Ceiling Concealed Duct
Independent Unit
ARNU07GB3G4 / ARNU09GB3G4 / ARNU12GB3G4 ARNU15GB3G4 / ARNU18GB4G4 / ARNU24GB4G4
INDOOR UNIT
Model
HIGH SENSIBLE
128
Solution
LG
129
FRESH AIR INTAKE UNIT
FRESH AIR INTAKE UNIT
Fresh Outdoor Air Supply
ARNU48GBRZ4
The LG Fresh Air Intake Unit (FAU) is the alternative solution for ventilation, which supplies the fresh outdoor air indoors as well as being able to cool and heat air inside simultaneously. It means the indoor space can have positive air pressure consistently, which can block cold, hot or contaminated air from outside.
ARNU76GB8Z4
Model Power Input
Nom Nom Nom 1) Rated 2)
Cooling Heating
Body
H/M/L H/M/L H/M/L H/M/L WxHxD
Liquid Gas Drain
I.D
Ø / V / Hz
Airflow Rate
100% Outdoor Air
Indoor Unit
Diffuser
Indoor Unit
Diffuser
Indoor Unit
Diffuser
Air Conditioning + Outdoor Air Supply
Air Conditioning
m3/min m3/min dBA dBA mm kg mm mm mm
ARNU48GBRZ4
ARNU76GB8Z4
ARNU96GB8Z4
14.1 13.5 169 169 1 / 220~240 / 50 1 / 220 / 60 18.8 / 14.7 / 14.7 18.8 / 14.7 / 14.7 41 / 40 / 38 62 / 63 / 62 1,230 x 380 x 590 45.0 9.52 15.88 25.0
22.4 21.4 253 360 1 / 220~240 / 50 1 / 220 / 60 23.7 / 13.2 / 13.2 23.7 / 13.2 / 13.2 45 / 43 / 43 70 / 67 / 67 1,562 x 460 x 688 73.0 9.52 19.05 25.0
28.0 26.7 360 360 1 / 220~240 / 50 1 / 220 / 60 35.7 / 23.7 / 23.7 35.7 / 23.7 / 23.7 47 / 45 / 45 72 / 68 / 68 1,562 x 460 x 688 73.0 9.52 22.2 25.0
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Capacities are net capacities 3. Noise Level is under standard mode [For actual High Mode (Factory set) condition, Noise Level may exceed the standard level by 1.5db (A)] 4. Due to our policy of innovation some specifications may be changed without prior notification. 5. I.D : ‘ Internal Diameter ’
Economic Operation Using the free cooling and heating can save costs by blowing the natural outdoor air inside when the season change.
1. Operation range (Cooling : 5°C ~ 43°C, Heating : -5°C ~ 43°C) 2. Installation of exhaust fan is recommended for a sealed room.
Fresh Air Intake Unit Diffuser
Indoor Unit
OFF
Diffuser
MULTI V IV Outdoor Unit
Combination
Mixture connection with general indoor unit and fresh intake units
1) The total capacity of indoor units (Standard Indoor Unit + Fresh Air Intake Unit) should be 50 ~ 100% of outdoor unit. 2) The total capacity of fresh air intake unit should be less than 30% of the total capacity of indoor units.
Accessories ARNU48GBRZ4
IR Receiver
dB (A)
It can reduce a noise at low frequencies.
dB (A)
Dry Contact
30.0
ARNU76GB8Z4
Wired Remote Controller Standard II
ARNU96GB8Z4
PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500 PWLRVN000
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
Wireless Remote Controller
30.0 20.0
10.0
10.0 25 40 63 100 160 250 400 630 1k 1.6k 2.5k 4k 6.3k 10k 16k
Simple (1 Contact Point with Case) 2 Contact Point For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication
Premium
40.0
20.0 0.0
❶ Inlet Hood ❷ Intake Air Duct Exhaus Air ❸ Fresh Air Intake Unit ❹ Exhaus Fan ❺ Door
❺
2
BLDC Fan Motor 40.0
❹
1) The total capcity of fresh air intak unit should be 50 ~ 100% of outdoor unit. 2) The max quantity of fresh air intake is 4 units.
Model
BLDC Motor
Outlet Air
Fresh air intake units only are connected with outdoor units
Cool Air + Outdoor Air Supply
AC Tap Motor
1/30 Slope
1
OFF
Warm Air + Outdoor Air Supply
MULTI V IV Outdoor Unit
Installation Scene ❸
3. Indoor Unit Connection
No Connection Condition Indoor Unit
❶
Min. 2m ❷
CAUTION
Autumn Season Fresh Air Intake Unit
Sound Pressure Sound Power Dimensions Net Weight Piping Connection
MULTI V IV Outdoor Unit
Spring Season
kW kW W W
0.0
25 40 63 100 160 250 400 630 1k 1.6k 2.5k 4k 6.3k 10k 16k
PREMTA000 PREMTA000A PREMTA000B
PREMTB001 (White)
PREMTBB01 (Black)
PQWRHQ0FDB
Fresh Air Intake Unit
Cooling Heating Cooling / Heating Cooling / Heating
Power Supply
Fresh Air Intake Unit
ARNU96GB8Z4
Independent Unit
Capacity
INDOOR UNIT
ARNU48GBRZ4 / ARNU76GB8Z4 / ARNU96GB8Z4
Solution
LG
130
131
INDOOR UNIT
CEILING & FLOOR CONVERTIBLE UNIT CEILING SUSPENDED UNIT Flexible Installation
Two Thermistors Control
The ceiling and floor models can be installed either on the ceiling or on the floor. This saves space when installed in the shops or offices.
The indoor temperature can be checked using the thermistors in the remote controller as well as from the indoor unit. There may be a significant difference between ceiling and floor air temperature. Compares temperatures sensed from different positions, and automatically selects the optimum temperature for users. Two thermistors can optimise indoor air temperature for a more comfortable environment.
Ceiling & Floor Convertible Unit Ceiling Suspended Unit
Indoor Unit Thermistor * Ceiling & Floor model name : ARNU09GVEA2, ARNU12GVEA2
Wired Remote Controller Thermistor
Airflow Direction Control Vertical airflow direction can be adjusted using remote controller, and horizontal airflow direction can be adjusted manually. Horizontal
Vertical
Cooling
Heating
100 째
93 째
80 째
63 째
Close
Filter Change Alarm The filter change alarm informs you when the unit has been operating for 2,400hours. It is very easy to clean or change the filter.
Close
One Touch Filter
Filter Change Alarm
132
Solution
LG
133
CEILING & FLOOR CONVERTIBLE UNIT
CEILING SUSPENDED UNIT URNU18GVJA2 / URNU24GVJA2 URNU36GVKA2 / URNU48GVLA2
URNU18GVJA2 / URNU24GVJA2
INDOOR UNIT
ARNU09GVEA2 / ARNU12GVEA2
URNU36GVKA2
URNU48GVLA2
Model
Independent Unit
Capacity
ARNU12GVEA2
Nom
kW
2.8
3.6
Heating
Nom
kW
3.2
4.0
Cooling / Heating
Nom 1)
W
22
30
Cooling / Heating
Rated 2) W
30
30
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
Ø / V / Hz
Power Supply
Model
Independent Unit
Capacity Power Input
URNU18GVJA2
URNU24GVJA2
URNU36GVKA2
URNU48GVLA2
Cooling
Nom
kW
5.6
7.1
10.6
14.1
Heating
Nom
kW
6.3
8.0
11.9
15.0
Cooling / Heating
Nom 1)
W
35
42
68
113
Cooling / Heating
Rated 2) W
63
63
140
190
Ø / V / Hz
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
Cooling
H / M / L m3/min
16.0 / 14.0 / 12.0
18.0 / 16.0 / 14.0
24.6 / 23.0 / 21.4
35.0 / 32.0 / 30.0
Heating
H / M / L m3/min
16.0 / 14.0 / 12.0
18.0 / 16.0 / 14.0
24.6 / 23.0 / 21.4
35.0 / 32.0 / 30.0 49 / 48 / 47
Power Supply
Cooling
H / M / L m3/min
7.6 / 6.9 / 6.2
9.2 / 7.6 / 6.9
Heating
H / M / L m3/min
7.6 / 6.9 / 6.2
9.2 / 7.6 / 6.9
Sound Pressure
H / M / L dBA
36 / 32 / 28
38 / 36 / 30
Sound Pressure
H / M / L dBA
42 / 40 / 37
43 / 41 / 39
48 / 46 / 44
Sound Power
H / M / L dBA
55 / 51 / 45
56 / 55 / 49
Sound Power
H / M / L dBA
61 / 59 / 56
62 / 59 / 56
68 / 66 / 64
68 / 67 / 66
W x H x D mm
900 x 490 x 200
900 x 490 x 200
Dimensions
W x H x D mm
950 x 650 x 220
950 x 650 x 220
1,350 x 650 x 220
1,750 x 650 x 220
Net Weight
45.0
Airflow Rate
Dimensions
Body
Net Weight Piping Connection
kg
13.7
13.7
Liquid
mm
6.35
6.35
Gas
mm
12.7
12.7
mm
16.0
16.0
Drain
I.D
Airflow Rate
Body
Piping Connection
kg
24.6
24.6
35.0
Liquid
mm
6.35
9.52
9.52
9.52
Gas
mm
12.7
15.88
15.88
15.88
mm
16.0
16.0
16.0
16.0
Drain
I.D
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’
Accessories
Accessories
Model
ARNU09GVEA2
Simple (1 Contact Point with Case) 2 Contact Point Dry Contact For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication EEV Kit for MULTI V Indoor
ARNU12GVEA2 PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500 PRGK024A0
Wired Remote Controller Premium
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTB001 (White)
PREMTBB01 (Black)
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
Model Dry Contact
Wireless Remote Controller
PQWRHQ0FDB
URNU18GVJA2
URNU24GVJA2
URNU36GVKA2
Simple (1 Contact Point with Case)
PDRYCB000
2 Contact Point
PDRYCB400
For Thermostat (On-Off / Mode / Fan Speed)
PDRYCB300
Modbus Communication
PDRYCB500
Wired Remote Controller Premium
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTB001 (White)
PREMTBB01 (Black)
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
URNU48GVLA2
Wireless Remote Controller
PQWRHQ0FDB
Ceiling & Floor Convertible Unit Ceiling Suspended Unit
Power Input
ARNU09GVEA2
Cooling
Solution
LG
134
135
CONSOLE
CONSOLE INDOOR UNIT
ARNU07GQAA4 / ARNU09GQAA4 ARNU12GQAA4 / ARNU15GQAA4
Installation Support Clip During the cooling operation, the vane adjusts upwards to direct the air flow towards the ceiling. When heating, the vane directs the warm air downwards to balance the room temperature especially for floor.
Cooling
Heating (Normal)
Heating (Floor Heating Mode) Model
Independent Unit
Capacity Power Input
ARNU07GQAA4
ARNU09GQAA4
ARNU12GQAA4
ARNU15GQAA4
Cooling
Nom
kW
2.2
2.8
3.6
4.5
Heating
Nom
kW
2.5
3.2
4.0
5.0
Cooling / Heating
Nom 1)
W
15
15
18
24
Cooling / Heating
Rated 2) W
30
30
30
30
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
Power Supply
Ø / V / Hz Cooling
H / M / L m3/min
6.7 / 5.9 / 4.8
6.7 / 5.9 / 4.8
7.5 / 5.9 / 4.8
8.7 / 6.7 / 5.9
Heating
H / M / L m3/min
6.7 / 5.9 / 4.8
6.7 / 5.9 / 4.8
7.5 / 5.9 / 4.8
8.7 / 6.7 / 5.9 42 / 37 / 31
5-Step Vane Control
Sound Pressure
H / M / L dBA
37 / 34 / 28
37 / 34 / 28
39 / 34 / 28
Console air conditioners offer a fast and powerful performance. Using the floor heating mode, console air conditioners provide faster floor heating and help to reach the desired temperature quickly.
There are 5 different stages to control air flow direction.
Sound Power
H / M / L dBA
53 / 50 / 44
53 / 50 / 44
56 / 50 / 44
58 / 53 / 50
W x H x D mm
700 x 600 x 210
700 x 600 x 210
700 x 600 x 210
700 x 600 x 210
Company A
Electric Heater
Dimensions
Step2
Step3
Net Weight
Step4 Piping Connection
LG
LG
Floor Heating Mode
15°C
Vertical
Step5
Step1
Horizontal
Lead Time for Heating (13°C ~ 21°C)
12 minutes 30 seconds
50 minutes
9 minutes 30 seconds
kg
14.0
14.0
14.0
14.0
Liquid
mm
6.35
6.35
6.35
6.35
Gas
mm
12.7
12.7
12.7
12.7
mm
12.2
12.2
12.2
12.2
Drain
27°C t
26 25 24 23 22 21 20 19 18
Body
I.D
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’
8 minutes 40 seconds
Accessories
(Test Condition : Target Temp.23°C, Indoor Room : 13°C~ , Outdoor Room : 7°C)
Model
ARNU07GQAA4
ARNU09GQAA4
Simple (1 Contact Point with Case) 2 Contact Point Dry Contact For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication EEV Kit for MULTI V Indoor
Healthier Air (3 Stage Air Filter System)
ARNU12GQAA4
Wired Remote Controller Premium
1st Advanced pre Filter :
2nd Allergy Filter :
3rd Plasma Ion Generator :
The antibacterial pre-filter primarily reduces large dust particles, mould and quilt dust.
Filter consists of enzyme that breaks down allergens, apatite and organic / inorganic binders. When the air passes through the filter, allergens cling to the filter, and the filter deactivates the allergens.
The sterilised ion generator emits around 1.2 million ions, and traps some of the airborne hazardous substances.
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTB001 (White)
PREMTBB01 (Black)
ARNU15GQAA4
PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500 PRGK024A0
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
Wireless Remote Controller
PQWRHQ0FDB
Console
Quick Floor Heating
Airflow Rate
LG
Solution
136
137
FLOOR STANDING UNIT
FLOOR STANDING UNIT INDOOR UNIT
ARNU07GCE*4 / ARNU09GCE*4 / ARNU12GCE*4 ARNU15GCE*4 / ARNU18GCF*4 / ARNU24GCF*4
Block Cold Draft The floor standing unit can block cold drafts from windows to provide a warmer environment for places such as libraries and offices.
Without Floor Standing
With Floor Standing A : Floor standing with case
Block cold drafts to provide a warmer environment
Model
Independent Unit
Capacity
Power Input
Cold Draft
Power Supply Airflow Rate
3 Way Flexible Installation
Sound Pressure Sound Power
It is possible to install and connect the outdoor unit in 3 different ways (Side, Back, Floor).
U : Floor standing without case
Dimensions Net Weight 3)
Nom Nom
ARNU07GCE*4 ARNU09GCE*4 ARNU12GCE*4 ARNU15GCE*4 ARNU18GCF*4
ARNU24GCF*4
kW kW
2.2 2.5
2.8 3.2
3.6 4.0
4.5 5.0
5.6 6.3
7.1 8.0
Nom 1)
W
24
30
36
44
54
84
Rated
W
85
85
85
85
115
115
2)
1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 Ø / V / Hz 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 8.5 / 7.5 / 6.5 9.5 / 8.5 / 7.5 10.5 / 9.5 / 8.5 11.5 / 10.0 / 9.5 16.0 / 14.0 / 12.0 18.0 / 16.0 / 14.0 Cooling H / M / L m3/min Heating H / M / L m3/min 8.5 / 7.5 / 6.5 9.5 / 8.5 / 7.5 10.5 / 9.5 / 8.5 11.5 / 10.0 / 9.5 16.0 / 14.0 / 12.0 18.0 / 16.0 / 14.0 H / M / L dBA 35 / 33 / 31 36 / 34 / 32 37 / 35 / 33 38 / 37 / 35 40 / 37 / 34 43 / 40 / 37 H / M / L dBA 54 / 52 / 50 55 / 54 / 52 57 / 55 / 54 59 / 57 / 55 60 / 57 / 54 61 / 60 / 57 1,067 x 635 x 203 (A) 1,067 x 635 x 203 (A) 1,067 x 635 x 203 (A) 1,067 x 635 x 203 (A) 1,345 x 635 x 203 (A) 1,345 x 635 x 203 (A) W x H x D mm Body 978 x 639 x 190 (U) 978 x 639 x 190 (U) 978 x 639 x 190 (U) 978 x 639 x 190 (U) 1,256 x 639 x 190 (U) 1,256 x 639 x 190 (U) kg 27.0 (A) / 20.0 (U) 27.0 (A) / 20.0 (U) 27.0 (A) / 20.0 (U) 27.0 (A) / 20.0 (U) 34.0 (A) / 27.0 (U) 34.0 (A) / 27.0 (U) Liquid mm 6.35 6.35 6.35 6.35 6.35 9.52 Gas mm 12.7 12.7 12.7 12.7 12.7 15.88 Drain I.D mm 12.0 12.0 12.0 12.0 12.0 12.0
* This product contains Fluorinated Greenhouse Gases. (R410A) 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor 3) Floor standing with case (without case) Note : 1. Capacities are based on the following conditions - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’
Back
Side Floor
Accessories Model
Sliding Type Filter Easy maintenance and extended product life with sliding type filter.
Easy Cleaning
ARNU07GCE*4 ARNU09GCE*4 ARNU12GCE*4 ARNU15GCE*4 ARNU18GCF*4 ARNU24GCF*4
Simple (1 Contact Point with Case) 2 Contact Point Dry Contact For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication EEV Kit for MULTI V Indoor IR Receiver
PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500 PRGK024A0 -
PWLRVN000
Wired Remote Controller Premium
Sliding Type
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTB001 (White)
PREMTBB01 (Black)
Simple
Simple for Hotel
PQRCVCL0Q (Black) PQRCVCL0QW (White)
PQRCHCA0Q (Black) PQRCHCA0QW (White)
Wireless Remote Controller
PQWRHQ0FDB
Floor Standing Unit
Piping Connection
Cooling Heating Cooling / Heating Cooling / Heating
LG
Solution
138
139
INDOOR UNIT
MULTI V INDOOR COMPATIBILITY Note : 1) No.1, 2, 3, 8 : Functions are available to use together with 4th generation Indoor units only. If used together 2nd generation indoor unit and 4th generation indoor unit functions will not be activate. Combined with MULTI V Water S outdoor unit this function is not available 2) No. 4, 5, 6, 7, 9, 10, 11, 12, 13, 14 : If used together 2nd generation indoor unit and 4th generation indoor unit these functions will be activate only in 4th generation indoor 3) 2nd generation indoor unit : Ceiling & Floor Convertible Unit, Ceiling Suspended Unit, HYDRO KIT (Low Temp. / High Temp.), ERV DX (with Humidifier, without Humidifier), AHU Communication Kit
Function Description
1
Energy Monitoring (Accumulated Electric Energy Check)
Monitoring accumulated power consumption by Wired Remote Controller / Central Control Device / PDI
•
or
2
2 Set Point
1) 2 set point control by Indoor and Central controller 2) Synchronization function with remote control (Synchronization Setting and Monitoring)
•
or
No.
Wired Remote Controller
Required Controller
New Function Name (4th Generation Indoor)
Wired Remote Controller
Centralized Controller
X : Not included this function in the Controller
Remarks
Premium (PREMTA000 PREMTA000A PREMTA000B)
Centralized Controller Simple Standard II Simple (PREMTBB01) Simple for Hotel AC EZ AC EZ Touch AC Smart IV ACP IV AC Manager IV (PREMTB001) (PQRCHCA0Q / (PQRCVCL0Q / (PQCSZ250S0) (PACEZA000) (PACS4B000) (PACP4B000) (PACM4B000) QW) QW)
•
* Neccesary to install the PDI (Power Distribution Indicator) * Wired remote controller or central controller must be installed (Function can be activated using just one control device.) * Combined with MULTI V Water S outdoor unit, this function is not available
•
•
X
X
X
•
•
•
•
•
* Wired remote controller or central controller must be installed (Function can be activated using just one control device.) * Combined with MULTI V Water S outdoor unit, this function is not available
•
X
X
X
X
•
•
•
X
•
* Centralized control is able to when you combine only 4th generation indoor units (Use together with 2nd generation and 4th generation indoors, only wired remote controller is able to setting this function as existing way) * Wired remote controller or central controller must be installed (Function can be activeated using just one control device.) * Combined with MULTI V Water S outdoor unit, this function is not available
•
X
X
X
X
•
•
•
X
* Check more details in PDB (Product Data Book) (Additional functions added using together same type of indoor units)
•
•
X
X
Occupied / Unoccupied Scheduling Function (Sub Func. Enable)
1) Synchronization according to occupied / unoccupied by Indoor and Central control 2) Synchronization icon with remote controller (Synchronization Monitoring)
•
4
Group Control
Group Control can use Additional function
•
-
5
Test Run (Heating)
Test run mode can operated in cooling mode and heating mode for easy service
•
-
•
•
X
X
6
Model Information Monitoring
Product Type / Indoor Type / Indoor capacity information can be monitored by remote controller
•
-
•
•
X
X
7
Auto Addressing
Wired remote controller can check indoor unit address information
•
-
•
•
X
X
•
•
X
X
• • (4 Step)
• • (3 Step)
X
X
(3 Step)
•
(3 Step)
•
•
•
•
X
(CN-CC Port Only)
•
X
X
or
8
Refrigerant Leakage Detection
Function error sign display when refrigerant leakage occurred
•
-
* Central controller has been installed, CH230 error code can be recognized (Old / New Same) * Without Central Controller, it is able to recognize with wired remote controller (CH230) * Combined with MULTI V Water S outdoor unit, this function is not available
9
Thermo On / Off Range User can set cooling thermo On / Off range with wired remote Setting (Cooling) controller for prevention overcooling
•
-
* Thermo On / Off temperature setting (3 Step)
10
Thermo On / Off Range User can set heating thermo On / Off range with wired remote Setting (Heating) controller for prevention overheating. (4 Steps)
•
-
* Thermo On / Off temperature setting (4 Step)
11
Static Pressure 11 Step Control (Only for Ceiling Concealed Duct Type)
•
-
* Only applied in Ceiling Concealed Duct
Depends on the installation environment, 4th generation Ceiling Concealed Duct can control the static pressure by 11 steps for providing comfortable environment
•
* Simple On / Off control by Dry Contact at Indoor [Example of Contact port by product type] * 2 Way Cassette : CN-CC Port (Wired remote controller installation function mode 41 is required) * 1 Way / 4 Way Cassette / Ceiling Concealed Duct / Wall Mounted Unit Console / FAU / Floor Standing (with Case / without Case) : CN-EXT Port
12
1 Point External Input (On / Off control)
Indoor unit can control external devices without purchasing Dry contact as an accessory (All 4th generation indoors)
•
-
13
Filter Sign (Remaining Time)
The alarm activates when the filter needs to be cleaned, and the time remaining for cleaning is displayed on the screen.
•
-
•
•
X
X
14
Auto Restart Function Disable / Enable
Enable : Restore the operation for status before power off Disable : Stand by at OFF mode after power failure compensation
•
-
•
•
X
X
MULTI V Indoor Compatibility
3
LG
Solution
140
HOT WATER SOLUTION 142 Hydro Kit
HYDRO KIT, using MULTI V to provide floor heating and hot water supply as a total HVAC solution.
141
LG
142
Solution
143
HYDRO KIT HOT WATER SOLUTION
Easy Installation
Saving Cost through High Efficiency
Easy to install as it uses a compact and modular structure.
Possible to install with equivalent levels of capital cost as a boiler system and minimise energy bills thanks to lower operation costs. 1st Proposal MULTI V IV HYDRO KIT (Air Conditioning + Hot Water Supply + Floor Heating)
MULTI IV + Boiler
MULTI V IV + HYDRO KIT Cooling HR Unit
Floor Heating
Floor Heating
Hot Water Supply
3rd Proposal MULTI V IV Air-Conditioning + Oil Boiler (Hot Water Supply + Floor Heating)
Hot Water Supply
Sanitary Tank
Oil Tank
Boiler
(€) 25,000 20,000 15,000 10,000 5,000
100%
90%
95%
229% 171% 100%
Gas Boiler Oil Boiler
Gas Boiler Oil Boiler
(€) LCC
Analysis Conditions Sanitary Tank
Annual Operating Coast
(€) 25,000 20,000 15,000 10,000 5,000
Hydro Kit
2nd Proposal MULTI V IV Air-Conditioning + Gas Boiler (Hot Water Supply + Floor Heating)
Cooling
Initial Costs
- Building Type : Dormitory, Flats - Cooling / Floor Heating / Sanitary Hot Water for 10 years - Cooling : MULTI V IV Indoor Unit - Floor Heating : Medium Temp. HYDRO KIT (1ea) - Sanitary Hot Water : High Temp. HYDRO KIT (2ea), Sanitary Hot Water Tanks - Electricity Cost : Average Cost in EU - Gas Cost : Average Cost in EU - Oil Cost : Average Cost in EU
50,000
Oil boiler Gas boiler
40,000 30,000 20,000 10,000
1
2
3
4
5
6
7
8
9
10
(Year)
Eco-friendly Green Energy Solution Green energy solution through the reduction of CO2 emmisions.
HYDRO KIT
Energy Saving through MULTI V IV Heat Recovery
CO2 Emissions
Energy costs can be minimized by reusing the wasted heat from indoor units.
(%) 120 100
Conventional System
Refrigerant Cooling HR Unit
Heat Absorption
100% 76%
60 40
30% On Average
20
30%
MULTI V IV HEAT RECOVERY
Indoor Cooling
Heat Emission
Sanitary Tank Oil Boiler
Gas Boiler
Hot Water
Solution
LG
144
145
HYDRO KIT HOT WATER SOLUTION
High Temperature Concept of HYDRO KIT
Various Applications
Provides high temperature up to 80°C with dual inverter cascade cycle, applicable for buildings that require large amount of hot water supply.
Applicable to a variety of facilities including hospitals, residences and resorts that need floor heating and domestic hot water supply.
Dual Inverter Cascade Cycle Technology
Office
University / School
Hospital / Clinic
Shopping Mall / Restaurant
Hotel / Resort
Factory Facilities
• Max 55% improved capacity compared to mid-temp. of HYDRO KIT - Max 20% reduced heating operating cost compared to mid-temp. of HYDRO KIT - Cascade R410A to R134A BLDC compressor technology Hydro Kit
High Volume of Hot Water • Compared to lower temperature, storing high temperature water in a sanitary tank increases the quantity of mixed water available for the user.
High Temperature of HYDRO KIT Cycle Diagram Outdoor Unit
High Temperature HYDRO KIT Refrigerant Refrigerant
Air-Refrigerant
Heating by Hot Water
Refrigerant Water
AIR
50°C
80°C
Pressure
High Temperature Technology Water
R410A R134A Stage 1
Air
Stage 2
Enthalpy
Hotel Application
Office Application
It is possible to operating cooling and heating constantly at the same time during the summer, to provide hot water for bathrooms by using waste heat energy of indoor cooling from an indoor unit.
Hot water can be supplied at all times in the office by cooling the HR unit to warm up the sanitary tank, using waste energy.
LG
Solution
146
147
HYDRO KIT
HYDRO KIT ARNH04GK2A2 / ARNH10GK2A2
ARNH04GK3A2 / ARNH08GK3A2
HOT WATER SOLUTION
Low Temp.
Low Temp.
Type
High Temp.
High Temp.
Model
ARNH04GK2A2
ARNH10GK2A2
Model
ARNH04GK3A2
ARNH08GK3A2
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
1 / 220~240 / 50 1 / 220 / 60
Power Supply Capacity (Rated) Power Input Water Outlet Temperature
Ø / V / Hz Cooling
kW
12.3
28.0
Heating
kW
13.8
31.5
Cooling
Max
kW
0.01
0.01
Heating
Max
kW
0.01
0.01
Cooling
Min
°C
6°C
6°C
Heating
Max
°C
50°C
50°C
Casing Dimensions
Body
WxHxD
Net Weight
Painted Steel Plate
Painted Steel Plate
mm
520 × 631 × 330
520 × 631 × 330
inch
20-15 / 32 x 24-27 / 32 x13
20-15 / 32 x 24-27 / 32 x13
30.4 (67)
35.0 (77.2)
Blazed Plate Hex
Blazed Plate Hex
kg (lbs) Type
Heat Exchanger
Refrigerant to Water Refrigerant to Refrigerant
Compressor Water Side Piping Connections Refrigerant Side
Rated Water Flow
L/min
39.6
92.0
Head Loss
kPa
41.0
69.0
Type
-
-
Type
-
-
Inlet
inch
Male PT 1
Male PT 1
Outlet
inch
Male PT 1
Male PT 1
Liquid Side
mm (inch)
9.52 (3/8)
9.52 (3/8)
Gas Side
mm (inch)
15.88 (5/8)
22.2 (7/8)
mm (inch)
Drain Piping Connection Sound Pressure Level
Male PT 1
Male PT 1
Cooling
dB (A)
26
26
Heating
dB (A)
26
26
Power Supply Cable
No. x mm²
3C × CV2.5
3C × CV2.5
Communication Cable
No. x mm²
2C × CVV-SB 1.0~1.5
2C × CVV-SB 1.0~1.5
Refrigerant Type
-
-
Control
-
-
R410A
R410A
Refrigerant to Refrigerant Refrigerant
Refrigerant Type Refrigerant to Water
Precharged Amount kg (lbs) Control
Combination Ratio
Water Outlet Temperature
kW
-
-
kW
13.8
25.2
Cooling
Max
kW
-
-
Heating
Max
kW
2.3
5.0
Cooling
Min
°C
-
-
Heating
Max
°C
80°C
80°C
Painted Steel Plate
Painted Steel Plate
mm
520 × 1,080 × 330
520 × 1,080 × 330
inch
20-15 / 32 x 42-17 / 32 x13
20-15 / 32 x 42-17 / 32 x13
Casing Dimensions
Body
WxHxD
Net Weight
kg (lbs) Type
Heat Exchanger
Compressor
Refrigerant to Water
Refrigerant to Refrigerant Water Side
Piping Connections Refrigerant Side
94.0 (207.2)
Blazed Plate Hex
Blazed Plate Hex 36.0
Rated Water Flow
L/min
19.8
Head Loss
kPa
5.0
20.0
Blazed Plate Hex
Blazed Plate Hex
Twin Rotary Inverter
Twin Rotary Inverter
Type Type Inlet
inch
Male PT 1
Male PT 1
Outlet
inch
Male PT 1
Male PT 1
Liquid Side
mm (inch)
9.52 (3/8)
9.52 (3/8)
Gas Side
mm (inch)
15.88 (5/8)
19.05 (3/4)
mm (inch)
Male PT 1
Male PT 1
Drain Piping Connection Sound Pressure Level
88.0 (194.0)
Cooling
dB (A)
-
-
Heating
dB (A)
43
43
Power Supply Cable
No. x mm²
3C × CV4.0
3C × CV4.0
Communication Cable
No. x mm²
2C × CVV-SB 1.0~1.5
2C × CVV-SB 1.0~1.5
R410A
R410A
Refrigerant to Refrigerant Refrigerant Refrigerant to Water
Refrigerant Type Control
EEV
EEV
Refrigerant Type
R134A
R134A
Precharged Amount kg (lbs)
2.3(5.1)
3.0(6.6)
EEV
EEV
EEV
Control Cooling
°C (DB)
-
-
Heating
°C (DB)
-20°C ~ 35°C
-20°C ~ 35°C
10°C ~ 43°C
10°C ~ 43°C
Heating
°C (DB)
-20°C ~ 35°C
-20°C ~ 35°C
Cooling
°C (DB)
10°C ~ 43°C
10°C ~ 43°C
Heating
°C (DB)
-20°C ~ 43°C
-20°C ~ 43°C
Only Hydrokit
Min ~ Max
%
50 ~ 100
50 ~ 100
Hydrokit + Standard IDUs
Min ~ Max
%
50 ~ 130
50 ~ 130
Conntected to Heat Recovery
Power Input
Cooling Heating
-
°C (DB)
Operation Range
Capacity (Rated)
Ø / V / Hz
EEV
Cooling
Conntected to Heat Pump
Power Supply
* This product contains Fluorinated Greenhouse Gases. (R410A) Note : 1. Capacities are based on the following conditions : - Cooling : Indoor 27°C (80.6°F) DB / 19° C (66.2°F) WB, Outdoor 35°C (95°F) DB / 24°C (75.2°F) WB, Water Inlet 23°C (73.4°F) / Outlet 18°C (64.4°F) - Heating : Indoor 20°C (68°F) DB / 15°C (59°F) WB, Outdoor 7°C (44.6°F) DB / 6°C (42.8°F) WB, Water Inlet 30°C (86°F) / Outlet 35°C (95°F) 2. Piping Length : Interconnected Pipe Length = 7.5m 3. Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero. 4. MULTI V S 4HP (ARUN040GSS0, ARUNN040LSS0) cannot be connected to Hydro Kit. 5. MULTI V Water S cannot be connected to Hydro Kit. 6. Anti freezing liquid should be added under 10°C (outdoor temp.) during cooling mode.
Conntected to Heat Pump Operation Range
Cooling
°C (DB)
-
-
Heating
°C (DB)
-20°C ~ 43°C
-20°C ~ 43°C
Only Hydrokit
Min ~ Max
%
50 ~ 100
50 ~ 100
Hydrokit + Standard IDUs
Min ~ Max
%
50 ~ 130
50 ~ 130
Conntected to Heat Recovery Combination Ratio
* This product contains Fluorinated Greenhouse Gases. (R410A, R134A) Note : 1. Capacities are based on the following conditions : - Heating : Indoor 20°C (68°F) DB / 15°C (59°F) WB, Outdoor 7°C (44.6°F) DB / 6°C (42.8°F) WB, Water Inlet 55°C (131°F) / Outlet 65°C (149°F) 2. Piping Length : Interconnected Pipe Length = 7.5m 3. Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero. 4. MULTI V S 4HP (ARUN040GSS0, ARUNN040LSS0) cannot be connected to Hydro Kit. 5. MULTI V Water S cannot be connected to Hydro Kit.
Hydro Kit
Type
LG
Solution
148
VENTILATION SOLUTION 150 Energy Recovery Ventilator 158 Energy Recovery Ventilator with DX Coil
Energy Recovery Ventilator
149
LG
Solution
150
151
ERV Energy Recovery Ventilator
Efficiency and comfort is ensured through the high-efficiency energy recovery central core which recovers energy from the indoor air and transfers it to the fresh incoming air without mixing airstream.
VENTILATION SOLUTION
High Efficiency Heat Exchanger
Bypass Ventilation Exhaust Air
Supply Air
LG ERV automatically switches the ventilation mode (Enthalpy Heat Exchange Mode / Bypass Mode) according to the indoor / outdoor temperature.
Enthalpy Heat Exchange Mode (Summer / Winter)
Bypass Mode (Seasonal Change)
Damper
Outdoor Air
Air Filter
Damper
Indoor Air
ERV
Interlocking with Air Conditioning System - LG ERV can be interlocked with air conditioners and controlled individually. - This function can be operated when the system is connected with a remote control.
Cooling / Heating Mode Set Temperature
Flexibility of Installation It’s possible to install upside down when you need only one inspection hole.
Normal Installation of 2 Units
Reverse Installation of 1 Unit (Left Unit)
Compulsory Exhausting System The exhausting system using high static and sirocco fan removes contaminants effectively from indoor air. Supply and exhaust air flows are completely separated in the total heat exchanger, LG ERV can filter out the impurities before supplying outdoor air and make indoor air fresh and healthy.
Outdoors
Indoors
Damper Exhaust Air
Exhaust Air
Return Air
Supply Air
Inspection Chamber Outdoor Air
Return Air
Outdoor Air
Supply Air Total Heat Exchanger
Top
Low
Low
Top
LG
Solution
152
153
ERV Energy Recovery Ventilator
Fast Ventilation Mode
It is easy and convenient to change and clean the filter.
Fast ventilation mode prevents the spread of contaminants under negative indoor pressure, and makes indoor air fresh and comfortable quickly.
Only Exhausting
VENTILATION SOLUTION
Easy Cleaning and Filter Change
Fast Ventilation Mode
Exhausting and Supplying Simultaneously
Exhaust Fan Supply Fan ERV
Remove Side Panel
ERV Unit
Exhausting operation causes negative indoor air pressure, and cannot fully ventilate.
CO2 Concentration Control Using CO2 sensor, LG ERV controls exhaust air flow automatically to keep indoor air fresh under settled CO2 concentration.
Change Filer
Remove Heat Exchanger
External Static Pressure Control
Standard Wired Remote Controller
CO2 Sensor (PES-C0RV0)
CO2 (ppm)
Air Volume
The high static pressure fan can control the air volume depending on the length of the duct. It is also easy to control the pressure level by using the remote controller for a more flexible duct installation and easier testing.
H M L
2,500 L
M
Windows Closed
Windows Open
Windows Closed
Windows Open
H
1,000 External Static Pressure (mmAq)
0 ERV with CO2 Concentration Control Time (min)
Solution
LG
154
155
ERV
ERV
Energy Recovery Ventilator
Energy Recovery Ventilator LZ-H025GBA4 / LZ-H035GBA4 / LZ-H050GBA4
LZ-H080GBA4 / LZ-H100GBA4 LZ-H150GBA4 / LZ-H200GBA4
Model
LZ-H025GBA4
Nominal Capacity Power Supply
ERV Mode
Step Current Power Input
SH / H / L SH / H / L
CMH (CFM) Ø / V / Hz Amps W
Air Flow
SH / H / L
CMH (CFM)
SH / H / L
Pa (inWTR)
Temperature Exchange Efficiency
SH / H / L Heating (SH / H / L) Cooling (SH / H / L) SH / H / L
Noise Level (Sound Level, 1.5m) Step Current Power Input
SH / H / L SH / H / L
% % % dB (A) Amps W
Air Flow
SH / H / L
CMH (CFM)
External Static Pressure
SH / H / L
Pa (inWTR)
Noise Level (Sound Level, 1.5m)
SH / H / L Type
dB (A) kg mm EA mm EA EA EA mm
Enthalpy Exchange Efficiency
Bypass Mode
Heat Exchanger Net Weight Dimension
WxHxD Qty Size (Ø) Qty Type Qty Type Qty Type Size (W x H x D)
Duct work* Supply Air Fan Exhaust Air Fan Filters Dry Contact
LZ-H050GBA4
350 (206) 1 / 220~240 / 50, 60 SUPER-HIGH / HIGH / LOW 0.70 / 0.60 / 0.42 1.10 / 0.95 / 0.60 97 / 78 / 52 180 / 163 / 88 250 / 250 / 150 350 / 350 / 210 (147 / 147 / 88) (206 / 206 / 123) 100 / 70 / 50 150 / 130 / 100 (0.40 / 0.28 / 0.20) (0.60 / 0.52 / 0.40) 80 / 80 / 83 75 / 75 / 77 70 / 70 / 72 68 / 68 / 70 66 / 66 / 68 63 / 63 / 65 29 / 28 / 24 32 / 30 / 27 SUPER-HIGH / HIGH / LOW 0.70 / 0.60 / 0.42 1.10 / 0.95 / 0.60 97 / 78 / 52 180 / 163 / 88 250 / 250 / 150 350 / 350 / 210 (147 / 147 / 88) (206 / 206 / 123) 100 / 70 / 50 150 / 130 / 100 (0.40 / 0.28 / 0.20) (0.60 / 0.52 / 0.40) 29 / 29 / 25 32 / 30 / 27 Air to air cross flow heat exchange 44 44 988 x 273 x 1,014 988 x 273 x 1,014 4 Ø200 1 Direct-Drive (Sirocco Fan) 1 Direct-Drive (Sirocco Fan) 2 Cleanable fibrous fleeces 855 x 10 x 160 PDRYCB000
500 (294)
1.92 / 1.58 / 0.79 240 / 220 / 90 500 / 500 / 320 (294 / 294 / 124) 150 / 100 / 50 (0.60 / 0.40 / 0.20) 78 / 78 / 79 73 / 73 / 75 66 / 66 / 69 34 / 32 / 25 1.92 / 1.58 / 0.79 240 / 220 / 90 500 / 500 / 320 (294 / 294 / 124) 150 / 100 / 50 (0.60 / 0.40 / 0.20) 35 / 33 / 25 44 988 x 273 x 1,014
Standard II
PREMTA000 PREMTA000A PREMTA000B
PREMTBB01
PREMTB001
LZ-H080GBA4
Nominal Capacity Power Supply
ERV Mode
Step Current Power Input
SH / H / L SH / H / L
CMH (CFM) Ø / V / Hz Amps W
Air Flow
SH / H / L
CMH (CFM)
External Static Pressure
SH / H / L
Pa (inWTR)
Temperature Exchange Efficiency
SH / H / L Heating (SH / H / L) Cooling (SH / H / L) SH / H / L
Noise Level (Sound Level, 1.5m) Step Current Power Input
SH / H / L SH / H / L
% % % dB (A) Amps W
Air Flow
SH / H / L
CMH (CFM)
External Static Pressure
SH / H / L
Pa (inWTR)
Noise Level (Sound Level, 1.5m)
SH / H / L Type
dB (A) kg mm EA mm EA EA EA mm
Enthalpy Exchange Efficiency
Bypass Mode
Heat Exchanger Net Weight Dimension
WxHxD Qty Size (Ø) Qty Type Qty Type Qty Type Size (W x H x D)
Duct work* Supply Air Fan Exhaust Air Fan 2 Filters 855 x 6 x 230 Dry Contact
Note : 1. ERV mode : Total Heat Recovery Ventilation mode 2. * : Refer to dimensional drawings. 3. Noise level : - The operating conditions are assumed to be standard - Sound measured at 1.5m below the center the body. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound. 4. Temperature and Enthalpy Exchange Efficiency at cooling Indoor Temperature : 26.5°C DB, 64.5% RH, Outdoor Temperature : 34.5°C DB, 75% RH 5. Temperature and Enthalpy Exchange Efficiency at heating Indoor Temperature : 20.5°C DB, 59.5% RH, Outdoor Temperature : 5°C DB, 65% RH 6. Temperature Exchange efficiency is tested at heating condition.
Premium
Model
LZ-H100GBA4
LZ-H150GBA4
LZ-H200GBA4
800 (471)
1,000 (589) 1,500 (883) 2,000 (1,177) 1 / 220~240 / 50, 60 SUPER-HIGH / HIGH / LOW 2.77 / 2.16 / 1.44 3.41 / 2.90 / 1.76 5.60 / 5.40 / 2.90 6.80 / 5.90 / 3.60 390 / 280 / 187 480 / 385 / 210 780 / 540 / 377 960 / 770 / 420 800 / 800 / 660 1,000 / 1,000 / 800 1,500 / 1,500 / 1,200 2,000 / 2,000 / 1,600 (471 / 471 / 388) (589 / 589 / 471) (883 / 883 / 706) (1,177 / 1,177 / 942) 200 / 110 / 60 160 / 90 / 50 200 / 110 / 60 160 / 90 / 50 (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20) 79 / 79 / 82 77 / 77 / 78 79 / 79 / 82 77 / 77 / 78 72 / 72 / 74 70 / 70 / 72 72 / 72 / 74 70 / 70 / 72 63 / 63 / 66 59 / 59 / 63 63 / 63 / 66 59 / 59 / 63 40 / 37 / 31 41 / 38 / 32 43 / 40 / 34 44 / 41 / 35 SUPER-HIGH / HIGH / LOW 2.77 / 2.16 / 1.44 3.41 / 2.90 / 1.76 5.60 / 5.40 / 2.90 6.80 / 5.90 / 3.60 390 / 280 / 187 480 / 385 / 210 780 / 540 / 377 960 / 770 / 420 800 / 800 / 660 1,000 / 1,000 / 800 1,500 / 1,500 / 1,200 2,000 / 2,000 / 1,600 (471 / 471 / 388) (589 / 589 / 471) (883 / 883 / 706) (1,177 / 1,177 / 942) 200 / 110 / 60 160 / 90 / 50 200 / 110 / 60 160 / 90 / 50 (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20) 41 / 38 / 32 41 / 39 / 33 44 / 41 / 35 44 / 42 / 36 Air to air cross flow heat exchange 62 140 1,062 x 365 x 1,140 1,313 x 738 x 1,140 4 4+2 Ø250 Ø250 + Ø350 1 2 Direct-Drive (Sirocco Fan) 1 2 Direct-Drive (Sirocco Fan) 2 4 Cleanable fibrous fleeces 1,056 x 6 x 212.5 PDRYCB000
Note : 1. ERV mode : Total Heat Recovery Ventilation mode 2. * : Refer to dimensional drawings. 3. Noise level : - The operating conditions are assumed to be standard - Sound measured at 1.5m below the center the body. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound. 4. Temperature and Enthalpy Exchange Efficiency at cooling Indoor Temperature : 26.5°C DB, 64.5% RH, Outdoor Temperature : 34.5°C DB, 75% RH 5. Temperature and Enthalpy Exchange Efficiency at heating Indoor Temperature : 20.5°C DB, 59.5% RH, Outdoor Temperature : 5°C DB, 65% RH 6. Temperature Exchange efficiency is tested at heating condition.
CO2 Sensor
Premium
PES-C0RV0
PREMTA000 PREMTA000A PREMTA000B
Standard II
PREMTBB01
CO2 Sensor
PREMTB001
PES-C0RV0
ERV
External Static Pressure
LZ-H035GBA4
250 (147)
LZ-H150GBA4 / LZ-H200GBA4
VENTILATION SOLUTION
LZ-H080GBA4 / LZ-H100GBA4
LG
Solution
156
157
ERV Energy Recovery Ventilator
140 120 100
70 65
60
55
40
50
Temperature Exchange Efficiency Enthalpy Exchange Efficiency (Heating) Enthalpy Exchange Efficiency (Cooling)
45 100
200
300
40
400 500 Air Volume (m3/h)
0
100
200
300 250 200
90 85 80 75 70 65
100
50
50
45 100
200
300
40
400 500 Air Volume (m3/h)
200
Super-High High Low
300
200
80 75 70 65 60 55
Temperature Exchange Efficiency Enthalpy Exchange Efficiency (Heating) Enthalpy Exchange Efficiency (Cooling)
50 45 100
200
300
400
500
40
600 700 800 Air Volume (m3/h)
Ventilation
0
100
200
300
400
500
600 700 800 Air Volume (m3/h)
Efficiency
500
Super-High High Low
400 300
Exchange Efficiency (%)
0
90 85 80 75 70 65 60
200
55
Temperature Exchange Efficiency Enthalpy Exchange Efficiency (Heating) Enthalpy Exchange Efficiency (Cooling)
50
100
45 0
200
400
600
800
1,000 1,200 Air Volume (m3/h)
40 500
600
700
800
900
1,000
1,100 1,200 Air Volume (m3/h)
70 65
Temperature Exchange Efficiency Enthalpy Exchange Efficiency (Heating) Enthalpy Exchange Efficiency (Cooling)
400
600
800
40 500
1,000 1,200 Air Volume (m3/h)
700
900
1,100 1,300 Air Volume (m3/h)
Efficiency Super-High High Low
400 300
90 85 80 75 70 65 60
200
55
Temperature Exchange Efficiency Enthalpy Exchange Efficiency (Heating) Enthalpy Exchange Efficiency (Cooling)
50 45
0
LZ-H200GBA4
85
200
500
400 500 Air Volume (m3/h)
90
75
50
100
400
800
1,200
40 1,000
1,600 2,000 Air Volume (m3/h)
1,200
1,400
1,600
1,800
2,000 2,200 Air Volume (m3/h)
Efficiency
Ventilation External Static Pressure (Pa)
400
100
External Static Pressure (Pa)
300
Efficiency Exchange Efficiency (%)
Ventilation
100
80
55
Ventilation
Temperature Exchange Efficiency Enthalpy Exchange Efficiency (Heating) Enthalpy Exchange Efficiency (Cooling) 0
85
45
LZ-H150GBA4
55
90
60
200
0
60
150
300
100
External Static Pressure (Pa)
350
Exchange Efficiency (%)
400
400
400 500 Air Volume (m3/h)
Efficiency Super-High High Low
0
LZ-H080GBA4
300
Super-High High Low
ERV
External Static Pressure (Pa)
75
60
Ventilation
External Static Pressure (Pa)
80
80
0
LZ-H050GBA4
85
Efficiency
500
Exchange Efficiency (%)
160
Ventilation
Exchange Efficiency (%)
180
90
500
Super-High High Low
400 300
Exchange Efficiency (%)
Super-High High Low
External Static Pressure (Pa)
200
20
LZ-H035GBA4
LZ-H100GBA4
Efficiency Exchange Efficiency (%)
External Static Pressure (Pa)
Ventilation
VENTILATION SOLUTION
LZ-H025GBA4
90 85 80 75 70 65 60
200
55
Temperature Exchange Efficiency Enthalpy Exchange Efficiency (Heating) Enthalpy Exchange Efficiency (Cooling)
50
100
45 0
500
1,000
1,500
2,000 2,500 Air Volume (m3/h)
40 1,000
1,200
1,400
1,600
1,800
2,000 2,200 Air Volume (m3/h)
LG
Solution
158
159
ERV DX
ERV DX Energy Recovery Ventilator with DX Coil LZ-H050GXH0 / LZ-H080GXH0 / LZ-H100GXH0 LZ-H050GXN0 / LZ-H080GXN0 / LZ-H100GXN0
Energy Recovery Ventilator with DX Coil
During the summer, ERV DX can transform outdoor warm air into cool air for indoors, and it can prevent cold drafts during the winter by supplying warm air.
Cooling
Heating
LG ERV DX can be used as a Total Air Conditioning Solution. It can control condition of incoming air with the DX coil and humidifier for making comfortable indoor air. In the summer, LG ERV DX controls the air indoors by cooling and dehumidifying incoming air. In winter, it can provide warm air by heating and humidifying the incoming air.
Heat exchange
DX Coil
Humidification
Exhaust Air
Supply Air
Outdoor Air
Return Air
LZ-H050GXH0 LZ-H080GXH0 LZ-H100GXH0 LZ-H050GXN0 LZ-H080GXN0 LZ-H100GXN0 Cooling 1)
kW
4.93
7.46
9.12
4.93
7.46
9.12
Heating 2)
kW
6.73
9.80
11.72
6.73
9.80
11.72
SH / H / L
%
86 / 86 / 87
80 / 80 / 81
76 / 76 / 78
86 / 86 / 87
80 / 80 / 81
76 / 76 / 78
Enthalpy Exchange Cooling (SH / H / L) Efficiency Heating (SH / H / L) Heat Exchange Mode (SH / H / L) Air Flow Rate Bypass Mode (SH / H / L) Fan External Static Pressure (SH / H / L) System Humidifier Amount 3) Pressure Feed Water Heat Exchange Mode (SH / H / L) Sound Pressure Bypass Mode (SH / H / L) Refrigerant Power Supply Heat Exchange Mode (SH / H / L) Power Input (Nominal) Bypass Mode (SH / H / L) Heat Exchange Mode (SH / H / L) Nominal Running Current (RLA) Bypass Mode (SH / H / L) Dimensions WxHxD Net Weight Liquid Gas Piping Connection Water Drain (Outer Diameter) Connection Duct Diameter Remote Controller Simple (1 Contact Point with Case) 2 Contact Point Dry Contact For Thermostat (On-Off / Mode / Fan Speed) Modbus Communication
% % CMH CMH Pa
61 / 61 / 63 76 / 76 / 77 500 / 500 / 440 500 / 500 / 440 160 / 120 / 100
50 / 50 / 53 45 / 45 / 50 61 / 61 / 63 50 / 50 / 53 67 / 67 / 69 64 / 64 / 66 76 / 76 / 77 67 / 67 / 69 800 / 800 / 640 1,000 / 1,000 / 820 500 / 500 / 440 800 / 800 / 640 800 / 800 / 640 1,000 / 1,000 / 820 500 / 500 / 440 800 / 800 / 640 140 / 90 / 70 110 / 70 / 60 180 / 150 / 110 170 / 120 / 80 Natural Evaporating Type kg/h 2.70 4.00 5.40 Mpa 0.02 ~ 0.49 dB (A) 38 / 36 / 33 39 / 37 / 34 40 / 38 / 35 39 / 37 / 35 41 / 38 / 36 dB (A) 39 / 37 / 34 40 / 38 / 35 40 / 38 / 35 39 / 37 / 35 41 / 38 / 36 R410A Ø / V / Hz 1 / 220~240 / 50, 60 kW 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 kW 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 A 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 A 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 mm 1,667 x 365 x 1,140 1,667 x 365 x 1,140 kg 105 98 mm Ø6.35 Ø6.35 mm Ø12.7 Ø12.7 mm Ø6.35 mm Ø25.4 Ø25.4 mm
LG ERV DX can be interlocked with MULTI V. It can be controlled individually by a wired remote controller connected to MULTI V indoor units.
41 / 39 / 36 41 / 39 / 36
0.48 / 0.42 / 0.27 0.48 / 0.42 / 0.27 3.6 / 3.2 / 2.3 3.6 / 3.2 / 2.3
Ø250 Refer to the below Wired Remote Controller table PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500
ERV DX Standard II
Premium
Outdoor
Ø250
45 / 45 / 50 64 / 64 / 66 1,000 / 1,000 / 820 1,000 / 1,000 / 820 150 / 100 / 70
Note : 1) Cooling Capacity Test condition - Indoor temperature : 27°C DB, 19°C WB / Outdoor temperature : 35°C DB 2) Heating Capacity Test condition - Indoor temperature : 20°C DB / Outdoor temperature : 7°C DB, 6°C WB 3) Humidifying capacity is based on the following conditions - Indoor temperature : 20°C DB, 15°C WB / Outdoor temperature : 7°C DB, 6°C WB * Cooling and heating capacities are based on the following conditions. - Fan is based on High and Super-high. The figures in the parenthesis indicate the heat reclaimed from the heat recovery ventilator. * The operating sound measured at the point 1.5 m below the center of the unit is converted to that measured at an anechoic chamber built in accordance with the KS B 6879 conditions. * The actual operating sound varies depending on the surrounding conditions (near running unit's sound, reflected sound and so on) and is normally higher than this value. * Air flow rate can be changed over to low mode or high mode. * The specifications, designs and information here are subject to change without notice. * This product contains Fluorinated Greenhouse Gases. (R410A)
Interlocking with MULTI V Indoor Units
Fresh Air Conditioning Load Temperature Exchange Efficiency
PREMTA000 PREMTA000A PREMTA000B
PREMTBB01
CO2 Sensor
PREMTB001
PES-C0RV0
ERV DX
Total Air Conditioning Solution
Model
VENTILATION SOLUTION
Providing Cool & Warm Fresh Air
Solution
LG
160
161
LG HVAC CONTROL Individual Control Premium
Wired Remote Controller Standard
PREMTA000 PREMTA000A PREMTA000B
PREMTB001
Simple
PQRCVCL0QW
LINE-UP Centralized Control
Wireless Remote Controller
PQWRHQ0FDB
Wi-Fi Controller *
Centralized Control
Indoor Unit ~ 32
Indoor Unit ~ 128
Indoor Unit ~ 8,192
AC Ez
AC Smart IV
AC Manager IV
PQCSZ250S0
PACS4B000
PACM4B000
Indoor Unit ~ 64
Indoor Unit ~ 256
NEW AC Ez Touch
ACP IV
Facility Integrator
System Integration Device Gateway for Protocol
PDI
ACP BACnet
Premium (8port) PQNUD1S40 Standard (2port) PPWRDB000
PQNFB17C0
ACS IO Module (Input / Output Module)
ACP Lonworks
PEXPMB000
PLNWKB000
(Power Distribution Indicator)
Other Integration Device PI-485
Group Control Wire
For Indoor Unit
(Air-Conditioner, ERV)
PHNFP14A0
PQRCVCL0Q
LG-IR-WF-1
PACEZA000
PACP4B000
DO Kit
KNX Gateway*
PQNFP00T0
LG-AC-KNX4 LG-AC-KNX8 LG-AC-KNX16 LG-AC-KNX64
(Digital Output Kit)
PQRCHCA0QW (Simple for Hotel)
Simple Dry Contact PDRYCB000
For Indoor Unit
2 Points Dry Contact
PSNFP14A0
PDRYCB400
(Air-Conditioner, ERV)
PREMTBB01
Indoor Unit Dry Contact Control Accessory
(For Setback)
Dry Contact for Thermostat PDRYCB300
For Modbus PDRYCB500
PZCWRCG3
Outdoor Unit
AHU Kit
IO Module
Communication Kit
Demand controller for MULTI V IV PVDSMN000
Return / Room Air Control PRCKA1
(Input / Output Module)
Remote Temperature Sensor
Low Ambient Kit
PQRSTA0
For MULTI V IV PRVC2
Supply Air Control by DDC PRDCA0
Zone Controller
Dry Contact for Demand Control
Control kit
4 Zones by thermostat ABZCA
Demand controller for MULTI V III PQDSBCDVM0
PRCKD21E (~ 4 ODUs) PRCKD41E (~ 8 ODUs)
Variable Water Flow Control kit
EEV Kit (Electronic Expansion Valve)
For MULTI V WATER IV PWFCKN000
PRLK048A0 (~ 10HP) PRLK096A0 (~ 20HP)
PQRCHCA0Q (Simple for Hotel)
TXV Kit (Thermal Expansion Valve)
For MULTI V WATER II PRVCO
Cool / Heat Selector
PRDSBM
* This product is provided by INTESIS.
PATX13A0E (8 ~ 16HP) PATX20A0E (18 ~ 26HP) PATX25A0E (28 ~ 36 HP) PATX35A0E (38 ~ 46 HP) PATX50A0E (48~56 HP)
LG
Solution
162
INDIVIDUAL CONTROL
163
INDIVIDUAL CONTROL 168 Wireless Remote Controller
166 Standard Wired Remote Controller
169 Wi-Fi Controller
ACCESSORIES
164 Premium Wired Remote Controller
167 Simple Wired Remote Controller
Control Solution
Remote Controller Line Up Model Name
On / Off Fan Speed Control Temperature Setting Mode Change Additional Mode Setting Auto Swing Vane Control (Louver Direction) E.S.P (External Static Pressure) Reservation Child Lock Electric Failure Compensation Time Display Filter Sign Energy Management** Home Leave
PREMTA000 PREMTA000A PREMTA000B
PREMTB001 PREMTBB01
PQRCVCL0QW PQRCVCL0Q PQRCHCA0QW PQRCHCA0Q
PQWRHQ0FDB
LG-IR-WF-11)
• • • • • • • •
• • • • • • • •
• • • • • • • •
• • • • • • •
• • • •
-
-
Weekly / Yearly
Weekly
-
Sleep, On / Off -
-
-
-
-
-
• • • • •
2 Set Points Control
*
* *
-
• -
-
• • • •
• •
-
-
-
-
-
-
-
-
*
-
* PQRCHCA0QW / PQRCHCA0Q doesn’t offer this function ** Centralized control (PACS4B000 / PACP4B000 / PQNFB17C0 / PLNWKB000) and PDI (PQNUD1S40 / PPWRDB000) should be installed for this function 1) User and product registration are necessary to use functions with internet accessibility. Providing functions can be changed according to the manufacturer.
•
LG
Solution
164
165
PREMIUM WIRED REMOTE CONTROLLER 5 inch full touch screen with a premium design
PREMTA000 1) PREMTA000A 2) PREMTA000B 3)
Energy Management • Self Energy Management
Features 4) - Time limit operation / Power consumption monitoring - Weekly / Monthly / Yearly trend tracking - Target alert alarm - Temperature range setting
User Friendly Design
• Improved scheduling - Timer / Daily / Weekly / Yearly / Holiday
Temperature Setting Mode Change Additional Mode Setting* Auto Swing Vane Control (Louver Direction) E.S.P (External Static Pressure)** Reservation Time Display Electric Failure Compensation Child Lock Filter Sign Energy Management Operation Status LED Indoor Temperature Display Wireless Remote Controller Receiver Display Size (W x H x D, mm) Black Light for Screen Saver Home Leave
• Display Configuration
It is more easy to use and control various functions.
Standard Mode
Users can use of five buttons as shortcuts for frequently used features. Simple Mode
Enhanced Schedule Function PREMTA000 / PREMTA000A / PREMTA000B
Function
Cooling / Heating / Auto / Dehumidification / Fan Plasma Purification / Energy-Saving Cooling / Robot Cleaning / Heater / Humidification
• • •
• Easy Pattern Schedule
• Yearly / Weekly Schedule
• • •
Yearly Schedule
If you set the schedule all at once, you will be able to effectively manage for various lengths of time. It provides 5 kinds of reservation functions. (Timer, Daily, Weekly, Yearly, Holiday)
It is possible to embody various schedules as pattern setting.
Weekly Schedule Pattern
Simple / Sleep / On / Off / Weekly / Yearly / Holiday
• • • • (Remain time + Alarm)
Check Energy Usage*** / Check Operation Time / Target Setting (Energy, Operation Time) / Time Limit Operation / Alarm Popup / Initialization Usage Data
• • •
****
5 Inch TFT color LCD (480 x 272) 137 x 121 x 16.5
•
2 Set Points Control
* It might not be indicated or operated at the partial product ** This function is available for certain indoor unit type *** Centralized control (PACS4B000 / PACP4B000 / PQNFB17C0 / PLNWKB000) and PDI (PQNUD1S40 / PPWRDB000) should be installed for this function **** For ceiling type duct 4) Indoor unit should have functions requested by the controller 5) 2 set points control works normally with MULTI V Heat Recovery and Single Heat Pump. But in case of MULTI V Heat Pump, It is not working in 2 set points control of indoor unit
* Available to save up to a maximum of 20 error histories, 20 holiday reservations and 5 daily event on week
Weekly Schedule
2 Set Points Control • 2 Set Points Control Ambient indoor temperature is guaranteed by setting two-point temperature for cooling and heating. New premium remote automatically changes from heating to cooling (and vice versa) depending on temperature.
• Home Leave Changeable setting for occupied / unoccupied status
Temperature
Cooling Set Point for Home Leave Cooling Set Point for Occupied Heating Set Point for Occupied Heating Set Point for Home Leave
Cooling Occupied
Home leave (Unoccupied)
Heating Cooling
Heating
Indoor Temperature Time
Arrive at a Room Thermo-Off
Leave a Room
Control Solution
Fan Speed Control
• Intuitive UI & GUI Design
• 2 Set Points Control 5)
- Full touch / Intuitive GUI (Graphic User Interface) - Main display simple mode / Touch buzzer
On / Off
Premium remote controller provides convenient trend & target graph for different period.
* Centralized control (PACS4B000 / PACP4B000 / PQNFB17C0 / PLNWKB000) and PDI (PQNUD1S40 / PPWRDB000) should be installed for this function
• Design with user’s convenience
Model Name
Trend & Target Setting Control
ACCESSORIES
1) English / Portuguese / Spanish / French 2) English / Italian / Russian / Chinese 3) English / German / Polish / Czech
• Self-management for energy saving
• Weekly / Monthly / Yearly
After it gathers information about usage time or electricity usage*, offer periodical history data to users as visual information. By using various setting mode (operation hour / electricity usage etc.), you can manage on your own.
LG
Solution
166
167
STANDARD WIRED REMOTE CONTROLLER
SIMPLE WIRED REMOTE CONTROLLER
Standard II
Simple
Providing easy control of one or a group of indoor units with various functions
PREMTB001 (White) PREMTBB01 (Black)
A simple way to control office or hotel systems in a compact design
PQRCVCL0QW (White) PQRCVCL0Q (Black) Simple for Hotel
Simple
Features1) Model Name On / Off Fan Speed Control Temperature Setting Mode Change
Vane Control (Louver Direction) E.S.P (External Static Pressure) Reservation Time Display Electric Failure Compensation Child Lock Filter Sign Operation Status LED Indoor Temperature Display Wireless Remote Controller Receiver Size (W x H x D, mm) Blacklight Power Consumption Monitoring Check Model Information
Features1) PREMTB001 / PREMTBB01
• • •
Cooling / Heating / Auto / Dehumidification / Fan Plasma Purification / Energy-Saving Cooling / Robot Cleaning / Heater / Humidification
• • •
Simple / Sleep / On / Off / Weekly / Holiday
• • • • (Remain time + Alarm) • • • *
120 x 121 x 16
• • •
**
* For Ceiling Concealed Duct type ** Centralized control (PACS4B000 / PACP4B000 / PQNFB17C0 / PLNWKB000) and PDI (PQNUD1S40 / PPWRDB000) should be installed for this function 1) Indoor unit should have functions requested by the controller
Model Name On / Off Fan Speed Control Temperature Setting Mode Change Auto Swing Vane Control (Louver Direction) E.S.P (External Static Pressure) Electric Failure Compensation Child Lock Indoor Temperature Display Wireless Remote Controller Receiver Size (W x H x D, mm) Blacklight * For Ceiling Concealed Duct type 1) Indoor unit should have functions requested by the controller
PQRCVCL0QW / PQRCVCL0Q
PQRCHCA0QW / PQRCHCA0Q
Cooling / Heating / Auto / Dehumidification / Fan
Only Changeable by Central Controller -
• • •
• • • • • • •
*
70 x 121 x 16
•
• • • -
• -
• • •
*
70 x 121 x 16
•
Control Solution
Additional Mode Setting Auto Swing
Simple for Hotel
ACCESSORIES
PQRCHCA0QW (White) PQRCHCA0Q (Black)
LG
Solution
168
169
WIRELESS REMOTE CONTROLLER
WI-FI CONTROLLER
PQWRHQ0FDB
LG-IR-WF-1
Features
Models Applied
On / Off Fan Speed Control Temperature Setting Mode Change Auto Swing Vane Control (Louver Direction) Reservation Indoor Temperature Display Sleep Mode Auto Size (W x H x D, mm)
• • •
Cooling / Heating / Auto / Dehumidification / Fan Plasma Purification / Energy-Saving Cooling / Robot Cleaning / Auto Dry
• •
Sleep / On / Off
•
Max. 7 hours 51.4 x 153 x 26
• Connectable with the indoor unit having IR receiver • Control and monitor • Power supply includes EU-UK-US-AU heads • Easy to install : Wall or desktop mounted • On / Off status and mode indicated by LED light • Automatic firmware Updates* • Additional internet service has to be available and registration user account in Intesis Home cloud to use Wi-fi controller is mandatory • Intesis Home cloud app is available for android phone or iOS phone
Model Name
LG-IR-WF-1
•
Start / Stop Operation Operation Mode
Cool / Heat / Auto / Fan / Dry
• • •
Set Point Ambient Temperature Fan Speed
* Internet access is necessary
Control Solution
Additional Mode Setting
PQWRHQ0FDB
ACCESSORIES
Model Name
1)
Specifications Model Name
LG-IR-WF-1
Enclosure
ABS (V-O, 5VB) 2,1 mm thickness PC (V-2) 1mm thickness
Dimensions (mm)
81 × 78 × 28
Weight (g)
76
Color
White
Power Supply
5VDC 0,2 A NEC Class 2 or Limited Power Source (LPS) and SELV Rated Power supply
Mounting
Wall
LED Indicators
1 × Device Status
Operating Temperature
From 0oC to 40oC
Operating Humidity
<93% HR, no Condensation
Stock Humidity
<93% HR, no Condensation
RoHS Conformity
Compliant with RoHS Directive (2002 / 95 / CE) Compliant with RoHS Directive (2002 / 95 / CE) CE Conformity to EMC Directive (2004 /108 / EC) and Low-voltage Directive (2006 / 95 / EC) EN 60950-1 / EN 301489-1 v1.8.1 / EN 300328
Certifications
Overview Case 1. Connection with Indoor Units with IR Receiver INTESIS Home Cloud
Wi-fi Controller IR
Smart Phone
INTESIS Home Cloud
Wi-fi Controller IR
Smart Phone 220V
220V CAC
1) This product is provided by INTESIS.
Case 2. Connection with Duct Type Indoor Units
CAC
LG
Solution
170
CENTRALIZED CONTROL
171
CENTRALIZED CONTROL 177 ACP IV
174 AC Smart IV
178 AC Manager IV
ACCESSORIES
172 AC Ez Touch
176 AC Ez
Control Solution
Central Controller Line Up Model Name PACEZA000
PQCSZ250S0
PACS4B000
PACP4B000
PACM4B000*
Maximum Number of Units
64
32
128
256
8,192
Individual / Group Control (On & Off, Mode, Set Point, Fan Speed)
• • • • • •
• • • • •
• • • • • • • • •
• • • • • • • • •
• • • • • • • • •
Web
Web
Remote Access by Client S/W
NEW
Ventilation Control Individual Controller Lock Error Check Schedule Operation History Visual Navigation Operation Time Limit Temperature Limit Web Access 1)
-
• Web
Power Consumption Monitoring (with PDI)
• •
Interlock Control
-
Virtual Group Control
-
Auto Changeover / Setback
Emergency Alarm Display ACS IO Module Interlocking
• -
* S/W program 1) Assignment of public IP address is required to access central controller through internet.
-
-
• • • • • •
• • • • • •
• • • • • •
LG
Solution
172
173
AC EZ TOUCH Smart management with 5 inch touch screen for small site NEW
PACEZA000
Features
• Web Access
Features Model Name
Users can control each space efficiently through web access. (Web access : Network configuration is locally necessary)
PACEZA000
Maximum Number of Indoor Units
64
Individual / Group Control (On & Off, Mode, Set Point, Fan Speed)
•
• Energy Statistics
ACCESSORIES
Internet
(with PQNUD1S40 or PPWRDB000) Statistics of operational status (time, power consumption) are provided to help make intelligent system operation decisions.
• (Temperature / Mode / Fan / All)
Individual Controller Lock Error Check
Self diagnosis
Control Solution
Mode Change
Cooling / Heating / Auto / Dehumidification / Fan
•
Slave Mode (Interlocking with Higher Level Controller) Schedule
Daily / Weekly / Monthly / Yearly / Exception day
• • • • • •
Operation History Temperature Limit Web Access 1) Auto Changeover / Setback Power Consumption Monitoring (with PDI) Emergency Alarm Display External IO Port No.
• Energy Mode
DI 1
Compatible Model
When using energy mode function, operation mode changes from cooling to fan or heating to off mode by force. (It is available only air conditioner and ‘on’ mode indoor unit)
MULTI V / ERV / ERV DX / THERMA V / HYDRO KIT
Size (W x H x D, mm)
137 x 25 x 121
1) Assignment of public IP address is required to access central controller through internet please contact regional office to have detailed Internet connection configuration
Installation Scene
• MULTI V IV • MULTI V III • MULTI V II
Internet
• MULTI V WATER IV • MULTI V WATER II
• MULTI V S • MULTI V Mini • MULTI V SPACE II
• MULTI SPLIT • SINGLE SPLIT
• ERV
Appropriate PI 485 should be used according to PDB
• Alarm Indicator It works when there are some errors or it’s time to change the oil or filter. Users can respond immediately according to alarm indicator therefore HVAC system is monitored consistently.
• Schedule Schedule control allows user to set the events in advance to maximize system performance. Also, by blocking unnecessary operation, it prevents a waste of energy.
Solution
LG
174
175
AC SMART IV Large 10.2 inch touch screen with intuitive GUI (Graphic User Interface) allows easy control
PACS4B000
Features
Model Name
Schedule control allows user to set the events in advance to maximize system performance. Also, by blocking unnecessary operation, it prevents a waste of energy.
PACS4B000
Maximum Number of Indoor Units
128
• Visual Navigation Current operation status on floor plan is checked at one view.
•
Individual / Group Control (On & Off, Mode, Set Point, Fan Speed)
• (Temperature / Mode / Fan / All)
Individual Controller Lock Error Check
Self diagnosis Cooling / Heating / Auto / Dehumidification / Fan
Schedule
Daily / Weekly / Monthly / Yearly / Exception day
Control Solution
Mode Change
• • • • • • • • • • •
Operation History Visual Navigation Operation Time Limit Temperature Limit Web Access 1) Auto Changeover / Setback Power Consumption Monitoring (with PDI) Interlock Control Virtual Group Control Emergency Alarm Display ACS IO Module Interlocking External IO Port No.
• Energy Statistics
(with PQNUD1S40 or PPWRDB000) Statistics of operational status (time, power consumption) are provided to help make intelligent system operation decisions.
• Operation Report Report including control status and other information is provided so that operation history can be reviewed easily. Data can be sent by E-mail or stored on USB or external HDD.
DI 2 / DO 2
Interfaceable Products
MULTI V / ERV / ERV DX / THERMA V / HYDRO KIT / AHU (Control Kit)
1) Assignment of public IP address is required to access central controller through internet please contact regional office to have detailed Internet connection configuration
Installation Scene CH1 CH2
• Interlocking Allows interlocked operation of devices or between digital inputs and outputs on the AC Smart IV. • MULTI V IV • MULTI V III • MULTI V II
Internet
ACCESSORIES
• Schedule
Features
• MULTI V WATER IV • MULTI V WATER II
• MULTI V S • MULTI V Mini • MULTI V SPACE II
• MULTI SPLIT • SINGLE SPLIT
• ERV
AHU (Control Kit)
Appropriate PI 485 should be used according to PDB
• Emergency Display Red alert takes up the whole display upon any urgency situation and all other control signals are blocked to prevent any possible accident.
LG
Solution
176
177
ACP IV
Easy to manage up to 32 indoor unit, including ERV with simple interface
ACP IV can be integrated to the web system that allows user can access the control system online anytime, anywhere without access to PC or specific application
PQCSZ250S0
PACP4B000
Features
Features
Model Name
PQCSZ250S0 32
Individual / Group Control (On & Off, Mode, Set Point, Fan Speed)
• • •
Ventilation Control Individual Controller Lock Error Check Mode Change
• • (Temperature / Mode / Fan / All)
Individual Controller Lock Error Check
Self Diagnosis
Mode Change
Cooling / Heating / Auto / Dehumidification / Fan
Schedule
•
Daily / Weekly / Repetition / Exception day
• • • • • • • • • • •
Operation History
Operation Status, Set Temperature, Room Temperature, Schedule
Visual Navigation
190 x 120 x 17
Power
256
Individual / Group Control (On & Off, Mode, Set Point, Fan Speed)
Cooling / Heating / Auto / Dehumidification / Fan
Size (W x H x D, mm)
PACP4B000
Maximum Number of Indoor Units
LED / LCD Display
Master / Slave Setting Display
Model Name
Operation Time Limit
DC 12V
Control Solution
Maximum Number of Indoor Units
ACCESSORIES
AC EZ
Temperature Limit Web Access 1) Auto Changeover / Setback Power Consumption Monitoring (with PDI) Interlock Control Virtual Group Control Emergency Alarm Display ACS IO Module Interlocking External IO Port No.
DI 10 / DO 4
Interfaceable Products
MULTI V / ERV / ERV DX / THERMA V / HYDRO KIT / AHU (Control Kit)
1) Assignment of public IP address is required to access central controller through internet.
Installation Scene
Installation Scene CH5 CH1 ~ 4
• MULTI V IV • MULTI V III • MULTI V II
• MULTI V WATER IV • MULTI V WATER II
• MULTI V S • MULTI V Mini • MULTI V SPACE II
• MULTI SPLIT • SINGLE SPLIT
• ERV
Appropriate PI 485 should be used according to PDB
Internet AC Smart IV
• MULTI V IV • MULTI V III • MULTI V II
• MULTI V WATER IV • MULTI V WATER II
• MULTI V S • MULTI V Mini • MULTI V SPACE II
• MULTI SPLIT • SINGLE SPLIT
• ERV
AHU (Control Kit)
Appropriate PI 485 should be used according to PDB
LG
Solution
178
179
AC MANAGER IV Up to 32 ACP IV can be connected so that 8,192 indoor units can be controlled and monitored
PACM4B000
Solution Overview
PDI
AC Ez
PACM4B000
PACS4B000
Features Model Name Maximum Number of Indoor Units Individual / Group control (On & Off, Mode, Set Point, Fan Speed) Ventilation Control Individual Controller Lock Mode Change Schedule Operation History Visual Navigation Operation Time Limit Temperature Limit Web Access 1) Auto Changeover / Setback Power Consumption Monitoring (with PDI) Interlock Wontrol Virtual Group Control Emergency Alarm Display ACS IO Module Interlocking
PACM4B000 8,192 (supports 32 ACP IV)
ACS IO Module
• •
• (Temperature / Mode / Fan / All) Self diagnosis Cooling / Heating / Auto / Dehumidification / Fan Daily / Weekly / Repetition / Exception day
• • • • • • • • • • •
BMS System
PQNFB17C0 PLNWKB000
Control Solution
Error Check
Dry Contact
ACCESSORIES
PACP4B000
DO Kit
* BACnet / Lonworks G/W can be connected to AC Manager
Comm. Kit
Light
Pump
Fan
Etc
1) Assignment of public IP address is required to access central controller through internet.
External Device
* Combination: we recommend you to connect separated wattmeter for Indoor units and Outdoor units to have correct power distribution value Appropriate PI 485 should be used according to PDB
Control Kit
Solution
180
181
SYSTEM INTEGRATION DEVICE
PDI
POWER DISTRIBUTION INDICATOR
PDI shows power consumption of up to 128 indoor units Premium
Facility Integrator
Gateway for Protocol
PI-485
PQNUD1S40 (8 port) Standard
ACP BACnet (Modbus)
Premium (8 port) PQNUD1S40 Standard (2 port) PPWRDB000
PQNFB17C0
ACS IO Module
PPWRDB000 (2 port)
For Indoor Unit (Air-Conditioner, ERV) PHNFP14A0
ACCESSORIES
PDI (Power Distribution Indicator)
Features • Data is backed up so that correct consumption can be checked when power outage occurred • Connector can be separated for convenient installation • Linkable with pulse type power meter
ACP Lonworks
Control Solution
Installation Scene Power Monitoring PEXPMB000
DO Kit (Digital Output Kit)
PLNWKB000
For Indoor Unit (Air-Conditioner, ERV) PSNFP14A0
Power In Single Phase 50Hz / 60Hz 220V
Watt Meter Pulse Signal
Power Cable of Indoor Unit
LG
KNX Gateway
Power In 3 Phase 4 Wire 50Hz / 60Hz 380V RS485 (LGAP)
PACP4B000 PQNFP00T0
LG-AC-KNX4 LG-AC-KNX8 LG-AC-KNX16 LG-AC-KNX64
PQNFB17C0 Power Cable for 3 Phase 4 Wire Power Cable for Single Phase Communication Cable (2 Wire Shielded Cable) Pulse Signal Wire * This value could be different with measured power consumption by power meter Combination : we recommend you to connect separated watt meter for Indoor units and Outdoor units to have correct power distribution value
or
PACS4B000
PLNWKB000
Solution
LG
182
183
ACS IO MODULE
DO KIT
The module can be connected with PACS4B000 or PACP4B000 if additional control points are needed not only DI / DO but also AI / AO port. These central controller can control 3rd party device as pump, security, lighting and so on through DI / DO and AI / AO
Connected between centralized controllers of LG and external devices, which can switch On / Off devices such as light, pump, motor, etc
PEXPMB000
PQNFP00T0
Features
Features Interface Type
PEXPMB000
NTC 10k PACS4B000 PACP4B000 PACM4B000
Linkable Products
Communication
1 3
Digital Output
3
Universal Input
4
Analog Output
4
Number of Indoor Units Max. I/O Points Maximum Number of Node
PACS4B000
PACP4B000
64 ~ 128
128 ~ 256
8,192
130
224
1,260
9
16
-
Max. 177k Ω
PT 1000
803 Ω
1,573 Ω
Ni 1000
871.7 Ω
1,675.2 Ω
DC (Voltage)
0V
10V
DC (Current)
0mA
20mA
0V
10V
Analog Output
-
Digital Input
Binary Input (Dry Contact)
-
-
Digital Output
Normal open
-
30VAC / 30VDC, 2A
• When the product input is less than equal to 25A
(The device is controlled by turning On / Off the power supply line of the product.)
1. Pull out the power or shut down the breaker. 2. Connect the power line from the breaker to the additional relay cable. 3. Connect the device power line to the additional relay cable. 4. Finish the connected area with the insulating tape.
PACM4B000
• When the product input is greater than equal to 25A
* Maximum number of Indoor units may be reduced by increasing the number of I/O points.
(The device is controlled by turning On / Off the indoor/outdoor communication line.)
1. Pull out the power or shut down the breaker. 2. Cut the communication line. 3. Connect the cut communication line to the additional relay cable. 4. Finish the connected area with the insulating tape.
Installation Scene CH1 ~ 4 CH6 PACS4B000
or
PACP4B000
• When the product input is greater than or equal to
25A (The device is controlled by turning On / Off the power supply line of the product through a fieldsupplied relay)
PUMP
PACM4B000
DDC
• Sensor / Valve / Actuator
Lighting
Fan
1. Pull out the power or shut down the breaker. 2. Connect the power line from the breaker to the additional relay cable. 3. Connect the field-supply relay power line to the additional relay cable. 4. Connect the device power line to the field-supply relay. 5. Finish the connected area with the insulating tape.
Alarm
• Pump / Fan etc.
* D I : Digital Input, DO : Digital Output, UI : Universal Input, AO : Analog Output / Please contact our regional office to have connectable relay specification for analog output
* Please contact our regional office to have connectable relay specification for digital output
Control Solution
I/O
RS-485 Digital Input
Analog Input
Min. 0.68k Ω
ACCESSORIES
Model Name
DIGITAL OUTPUT KIT
LG
Solution
184
185
ACP BACNET GATEWAY
ACP LONWORKS GATEWAY
PQNFB17C0
PLNWKB000
ACCESSORIES
* Please refer PDRYCB500 for Modbus RTU
Features
Features
• Process ability - EHP Type : 256 units (Indoor / ERV / ERV DX / Hydro Kit / THERMA V) - AHU Control kit : Maximum 16 units
Monitoring Items On / Off Status
Operation Mode Setting
Operation Mode Status
Fan Speed Setting
Fan Speed Status
Lock Setting
Lock Status
Air Flow Setting
Air Flow Setting
• Self installation verification function using internet
(Web server included) - Setting gateway - Diagnosis of communication status on LG Air-conditioner network
• Modbus TCP protocol support • BTL Certified (B-ASC) • It offers a variety of functions as ACP which allows the
customer to efficiently control various types of equipment from the customer’s own PC.
* In case of using Modbus, the compatibility is different from BACnet. Refer to manual in detail.
Set Temperature Setting
Set Temperature Status
-
Current Space Temperature Status
-
Error Status
User Mode Setting (for only ERV)
User Mode Status (for only ERV)
-
Accumulator Power Distribution Status
Upper Limit Temp. Setting
Upper Limit Temperature Status
Low Limit Temp. Setting
Low Limit Temperature Status
Mode Lock Setting
Mode Lock Status
AC Operation Mode Setting (ERV DX only) AC On / Off Command (ERV DX only)
Air Conditioner Operation Mode Status (ERV DX only) Air Conditioner On / Off Status (ERV DX only)
Installation Scene
CH1 ~ 4
- EHP Type : 64 units (Indoor / ERV / Hydro Kit / THERMA V) - AHU Control kit : Maximum 16 units
• Connect to use Lonworks® protocol and LG air
conditioner protocol. • Self installation verification function using internet (Web server included) - Setting gateway - Diagnosis of communication status on LG Air-conditioner network
• It offers a variety of functions as ACP which allows the
customer to efficiently control various types of equipment from the customer’s own PC.
Remote Checking
BMS System Indoor Unit : Max. 256 Units (Air Conditioner & Ventilation) / Indoor Address : 00 ~ FF
Utility Control
CH5
BMS System
CH1 ~ 4
Monitoring Items On / Off Status Operation Mode Setting Fan Speed Status Lock Status Air Flow Setting Set Temperature Status Current Space Temperature Status Error Status Accumulator Power Distribution Status Accumulator Power Distribution Status Low Limit Temperature Setting Mode Lock Status Peak Operation Ratio Setting Total Accumulate Power Status
Lighting Control
Remote Checking
Utility Control
Indoor Unit : Max. 64 Units (Air Conditioner & Ventilation) / Indoor Address : 00 ~ FF
1)
1)
Internet
Internet
PACS4B000
ACP function
Controlling On / Off Command Operation Mode Setting Fan Speed Setting Lock Setting Air Flow Setting Set Temperature Setting Upper Limit Temperature Setting Low Limit Temperature Setting Mode Lock Setting Peak Operation Ratio Setting All On / Off Setting -
Installation Scene
Lighting Control
CH5
• Process ability
PACS4B000 • MULTI V IV • MULTI V III • MULTI V II
1) Assignment of public IP address is required to access central controller through internet.
• MULTI V WATER IV • MULTI V WATER II
• MULTI V S • MULTI V Mini • MULTI V SPACE II
• MULTI SPLIT • SINGLE SPLIT
• ERV / ERV DX
AHU (Control Kit)
Appropriate PI 485 should be used according to PDB
ACP function
• MULTI V IV • MULTI V III • MULTI V II
1) Assignment of public IP address is required to access central controller through internet.
• MULTI V WATER IV • MULTI V WATER II
• MULTI V S • MULTI V Mini • MULTI V SPACE II
• MULTI SPLIT • SINGLE SPLIT
• ERV
AHU (Control Kit)
Appropriate PI 485 should be used according to PDB
Control Solution
Controlling On / Off Command
LG
Solution
186
187
KNX GATEWAY
PI 485
Specially designed to allow monitoring and bidirectional control of all the parameters and functionality of LG air conditioners from KNX installations
PI 485 converts the air conditioner’s protocol to the RS485 protocol for the central controller
1)
PHNFP14A0 PSNFP14A0
• Easy installation, direct connection to all outdoor units (Communication interface PMNFP14A1, when needed) and Heat recovering units (Communication interface PHNFP14A0, when needed) throungh the RS485 Bus. • Great integration flexibility. Using the supplied software LinkBoxEIB, a complete set of communication objects can be accessed. Model Name • Direct connection to KNX bus LG-AC-KNX4 • Independent management of communications LG-AC-KNX8 • Power supply : 9 to 24V DC or 24V AC LG-AC-KNX16 • Standard DIN-Rail 6 modules enclosure LG-AC-KNX64 • Maximum connection unit
ACCESSORIES
LG-AC-KNX4 LG-AC-KNX8 LG-AC-KNX16 LG-AC-KNX64
Features
Max. Connection Units 4 8
• Model Name : PHNFP14A0
16
• Power : Connected with the Indoor Units
64
• 1 for Each Indoor Unit - Indoor Unit (Air-Conditioner, ERV) Control Solution
Link BoxEIB Configuration Software for IntesisBox® KNX Serious Easy to use tool for the configuration of intesisBox, in a fast and effective way. It offers the maximum integration possibilities with a minimal knowledge required on the system to be integrated.
LinkBoxEIB Configuration Software
- Only needed during configuration. - One single tool for the configuration of the whole range of IntesisBox KNX series gateways. - Supplied with IntesisBox with no additional cost. - Configuration examples for all systems that can be integrated. - Mapping table editable using excel, allowing a simple and fast association of KNX Group Addresses, exported from ETS, to IntesisBox’s datapoints. - Includes powerful and useful features for configuration, setup and troubleshooting.
• Model Name : PSNFP14A0 • Power : Connected with the Indoor Units • 1 for Each Indoor Unit - Indoor Unit (Air-Conditioner, ERV) * Provided with a case to be installed on the exterior.
Installation Scene Configuration Software LinkBoxEIB (above 1.1.17)
(Only Needed for Configuration)
RS232
* MULTI V PLUS II & MULTI V III & MULTI V IV series do not require any other PI 485 since these series have PI 485 in its outdoor unit PCB.
EIB Bus
RS485
IntesisBox LG-AC-KNX4 LG-AC-KNX8 LG-AC-KNX16 LG-AC-KNX64 • MULTI V IV • MULTI V III • MULTI V II 1) This product is provided by INTESIS.
• MULTI V • MULTI V S • MULTI SPLIT WATER IV • MULTI V Mini • SINGLE SPLIT • MULTI V • MULTI V WATER II SPACE II
• ERV
Appropriate PI 485 should be used according to PDB
LG
Solution
188
OTHER INTEGRATION CONTROL
189
OTHER INTEGRATION DEVICE LINE-UP Indoor Unit Dry Contact
2 Points Dry Contact (For Setback) PDRYCB400
AHU Kit
Group Control Wire
IO Module (Input / Output Module)
Communication Kit
PZCWRCG3
PVDSMN000
PRCKA1
Remote Temperature Sensor
Low Ambient Kit
PQRSTA0
PRVC2
PRDCA0
Zone Controller
Dry Contact for Demand Control
Control Kit
ABZCA
PQDSBCDVM0
PRCKD21E PRCKD41E
Variable Water Flow Control Kit
EEV Kit (Electronic Expansion Valve)
PWFCKN000
PRLK048A0 / PRLK096A0
ACCESSORIES
Simple Dry Contact PDRYCB000
Outdoor Unit
Control Accessory
Control Solution
Dry Contact for Thermostat PDRYCB300
For Modbus PDRYCB500
TXV Kit (Thermal Expansion Valve)
PRVCO
Cool / Heat Selector
PRDSBM
PATX13A0E / PATX20A0E PATX25A0E / PATX35A0E PATX50A0E
LG
Solution
190
191
DRY CONTACT Connection between an indoor unit and external devices to control various functions
PDRYCB300
Features
Features
Model Name
PDRYCB000
PDRYCB400
Model Name
Contact Point
1 Contact Point
2 Contact Point
On / Off Control
AC 220V
From Indoor Unit
Mode Control
Power Input
•
• •
Rotary Switch 1
-
Operating Set Temperature Selection
Rotary Switch 2
-
Operating Logic Selection
120 x 120
120 x 120
-
• •
Error Monitoring Operation Monitoring Size (W x H, mm)
• • (Cool, Heat, Fan) • (Low, Middle, High) • • •
Fan Speed Setting
• •
* Refer to each models PDB for applicable models. * Maximum operation AC : 3A * 4th generation indoor unit has 1 contact point function for On / Off control. But in case of using more function of Dry Contact besides On / Off control, Dry Contact is needed.
• PDRYCB000
PDRYCB300
• PDRYCB400
Thermo Off Error Monitoring Operation Monitoring Rotary Switch 1
Operating Set Temperature Selection
Rotary Switch 2
Operating Logic Selection
Size (W x H, mm)
120 x 120
Control Solution
On / Off Control
Voltage / Non Voltage Input
ACCESSORIES
PDRYCB000 PDRYCB400
• PDRYCB300
AC 220V AC 220V
To Apply Power Source through PCB
To Apply Power Source Directly to External Source
In Case Non Voltage Signal
In Case Voltage Signal
Installation Scene
For no Power Contact Point Signal Input
For Power Contact Point Signal Input
Indoor Unit Monitoring
Installation Scene
CN - CC Control Module Dry Contact (Contact point linked with outer part)
Key Switch
Lighting Sensor
Fire Alarm
Timer
Motion Detect Sensor
Door Check Sensor
CN - CC
System Structure * Please contact our regional office to have full compatible room controller list
Solution
LG
192
193
GROUP CONTROL WIRE
Connection between an indoor unit and external devices to control various functions
Cables used to connect a wired remote controller up to 16 indoor units
PDRYCB500
PZCWRCG3
Features
Features
• Function
Model Name
- MODBUS communicate with MODBUS master controller - MODBUS RTU slave / 2 wire RS485 / 9,600bps - MAX. 8 IDUs can be connected with one MODBUS master controller - Size (W x H x D) : 120mm x 120mm x 36.5mm
ACCESSORIES
DRY CONTACT
PZCWRCG3
Y-type Cable
0.25m Length
Long Cable
9.6m Length
• Memory map Name
Range
Notes
00001
Operation
0 ··· 1
0 : Stop, 1 : Run
30003
Indoor Temperature
100 ··· 390
Degrees C x 100
30100
Error Alarm
0 ··· 1
0 : No Error, 1 : Error 0 : Cooling, 2 : Fan, 4 : Heating
40001
Set Run Mode
0 ··· 4
40002
Set Temperature
180 ··· 300
Degrees C x 100
40015
Set Fan Speed
0 ··· 3
0 : Low, 1 : Middle, 2 : High, 3 : Auto
Installation Scene
Control Solution
Register (hexa)
Installation Scene <Modbus Communication Function>
Indoor 1 MAIN PCB Indoor 1
Room Control Master
Indoor terminal block
CN-CC
RCU*
Indoor Unit
...
Max. 8 IDUs
RED (12V) YL (SIGNAL) BK (GND)
Controller * RCU : Room Control Unit.
One to one connection between dry contact and indoor unit CN-CC Note :
Indoor Unit * Please contact our regional office to have full compatible room controller list
1 2
Y type Cable assembly for connecting indoor unit and low cable. Long Cable assembly for connecting indoor to indoor. - Please connect cable assembly Y type Cable with already connected indoor unit.
Indoor 2 Indoor terminal block
YL (SIGNAL) BK (GND)
Indoor 3 Indoor terminal block
YL (SIGNAL) BK (GND)
LG
Solution
194
195
ZONE CONTROLLER
Sensor for detecting the room temperature
Controls air conditioning in up to 4 zones by external thermostat
PQRSTA0
ABZCA
Features
Features
• It can help to detect the exact room temperature instead of indoor unit’s air temperature sensor • Applied to Ceiling Mounted Cassette, Ceiling Concealed Duct, THERMA V and HYDRO KIT • Extension cable (15m) is included
• Controls different zones (Up to 4 zones) by external thermostat (AC 24V) • Maintain proper air volume of each zone • Auto variation of dampers • Auto control of fan speed and On / Off operation
Indoor Unit (Duct Type)
Installation Scene
Models Applied
1. Wire to the control box in the indoor unit by removing the existing thermistor and connect the extension cable its place. 2. Cut the extension cable to the appropriate length and connect the screw terminal of the remote sensor.
• Ceiling Concealed Duct (refer to PDB for applicable models)
Wiring Diagram Extension Cable CN-ROOM
Ceiling Concealed Duct 1 2 3 4 5 6 7 8
CN - ZONE Indoor Unit
AC 24V
Remote Temperature Sensor
Wired Remote Controller
Zone Controller
ROOM(External) THERMOSTAT #1
Damper Or Relay
ROOM THERMOSTAT #2
Damper Or Relay
ROOM THERMOSTAT #3
Damper Or Relay
ROOM THERMOSTAT #4
Damper Or Relay
ROOM2
Thermostat
Temperature Sensor
Temperature Sensor
Temperature Sensor
ROOM3
ROOM4
Control Solution
Zone Control sub PCB
ROOM1
ACCESSORIES
REMOTE TEMPERATURE SENSOR
LG
Solution
196
IO MODULE
197
INPUT / OUTPUT MODULE
Interface module between system air conditioner and external device
PVDSMN000
Installation Scene • Demand Control Provides variable setting for demand control according to input method to reduce power consumption. This function supports 2 types of input signal : AI (0 ~ 10V, 10 Step) and contact signal (3 Step).
Capacity Control with
or
Features
Contact Signal (3 Points / 3 Steps)
• Function
MULTI V WATER IV
- Demand control - Low noise operation - Output outdoor or indoor unit operation status - Output error status
MULTI V IV
IO Module
Range of Operation Rate AI 0 ~ 10V : 0%, 40% ~ 100% Contact signal (3 steps) : 0%, 40% ~ 80%
Control Solution
• Description - IO Module is communication interface module for connection between MULTI V IV and external IO (Input / Output Module) devices.
• Low Noise Operation To reduce noise level , control outdoor unit’s fan speed by dry contact input.
Note : IO Module is not compatible for MULTI V III
DDC (Direct Digital Controller)
(dB) Max 7 dB*
Models Applied
Timer
or
• MULTI V IV, MULTI V WATER IV, MULTI V S
Wiring
Contact Signal
1) Dry Contact Input Part • Input_1, 2, 3 : Demand control by contact input (3 Step) • Input_LNO : Low Noise Operation • Priority Setting Using priority setting contact signal the priority of command. (Capacity control for external command from DDC vs. peak control by LG Central controller.) - Close : Central controller has priority to external signal - Open : External signal has priority to central controller (Default setting)
Noise Level
MULTI V IV
IO Module
* 8 HP model, Sound power level can be changed by outdoor unit operation status and low noise operation input signal.
Power AC or DC Power AC or DC
AO_4
Error Status
AO_3 Operating Status
AO_2 AO_1
2) Analog Input Part (AI : DC 0 ~ 10V)
• Output Operation and Error Status This function displays outdoor or indoor unit’s operation and error status. Depends on dip switch setting, either outdoor or indoor unit operation status is reflected through output signal. Additionally, either outside or indoor unit has an error, IO Module display error signal by another replay.
• AI_1 : Demand ontrol by analog input (10 Step) • Low ambient operation (AO_1 ~ 3) • IO Module communication error display
4) Digital Output (DO : 250VAC, Max 1A) • Output error status • Output operation status
IO Module
Reserved AI_1
Priority setting Reserved Input_LNO Input_3 Input_2 Input_1
3) Analog Output Part(AO : DC 0 ~ 10V, Max 20 mA)
or
AI : Analog Input (DC0~10V) AO : Analog Output ( DC0~10V, Max 20mA) Input_LNO : Low Noise Operation
OFF
MULTI V WATER IV
MULTI V IV
ACCESSORIES
DDC (Direct Digital Controller)
OFF
ON
Error
Operation Status (Output 250V AC, Max 1A) Error Status (Output 250V AC, Max 1A)
LG
Solution
198
199
LOW AMBIENT KIT External integration module for cooling operation with -25oC low ambient temperature.
OUTDOOR UNIT DRY CONTACT
PRVC2
PQDSBCDVM0
Features
Features
• Function
• Function
Dry contact for demand control
ACCESSORIES
- 25oC Low ambient cooling operation by Low ambient kit and hood with damper (Analog output 0 ~ 10V) - Demand control - Low noise operation - Output outdoor or indoor unit operation status (250VAC, Max 1A) - Output error status (250VAC, Max 1A)
- Demand control (3 Contact signal) - Demand control (Co-work with DDC) - Outdoor unit fan low speed control (Night low noise operation) - All Off - Error output (Display)
Error Display
• Description
Low Noise
The product is especially designed for demand control.
- Low ambient kit supports -25 C cooling operation by making stable condensing pressure with reducing air flow rate from hood and damper control given 0 ~ 10V proportional to condensing pressure. - Low ambient kit provides IO Module function. - External snow hood and air damper are required for this item.* - Transformer and terminal block are included.
Control Solution
• Description o
By DDC 0 ~ 10V
Front
Back
or
By Dry Contact
Demand Control (Input)
: Field Supply Item
* Before apply this accessory, please contact regional sales office.
Models Applied
Models Applied
• MULTI V IV
• MULTI V S, MULTI V III, MULTI V MINI, MULTI V SPACE II, MULTI V WATER II, MULTI V WATER S
Installation Scene
Installation Scene Reference : Air Damper
Main PCB
DDC (Direct Digital Controller) 0 ~ 10V (Analog Input)
Damper Actuator (0 ~ 10V)
Contact Signal (3 Points / 3 Steps)
Transformer 220VAC -> 24VAC
MULTI V IV
MULTI V III
IO Module
Common
DC 0 ~ 10V Control
Note : The IO Module can control maximum three actuators. Please, review damper actuator’s installation manual.
24VAC
Outdoor Unit Dry Contact
Range of Operation Rate AI 0 ~ 10V : 0%, 40% ~ 100% Contact Signal (3 Steps) : 0%, 40% ~ 80%
Solution
LG
200
201
VARIABLE WATER FLOW CONTROL KIT
COOL / HEAT SELECTOR
PWFCKN000 (MULTI V WATER IV)
PRDSBM
Cooling, heating, or fan mode can be selected to prevent cooling and heating mixing errors during seasonal changes
Accessory developed for controlling the water flow
PRVC0 (MULTI V WATER II)
Features
• Function
• Indoor unit mode control without central controller • Select operation mode : Cooling, Heating, Fan mode • Mode lock for cooling & heating mixing error-proof during the change of season
- Water pump or valve control (0 ~ 10V) - Minimum output voltage setting available - Operation, error output (250VAC, Max 1A) - Dry contact input and analog output for demand control - Digital output for operation, error status (250VAC, Max 1A)
Fan Mode Fan Mode
Cooling only
Cooling only
• Advantage
Mode Change Mode Change Heating only Heating only
Control Solution
- Water flow consumption reduction - Pump electricity consumption reduction - Including IO Module (Dry contact input, Analog input / output, Digital output) : Using Dry contact and variable water flow control function simultaneously Cooling Tower
Wiring Diagram
Models Applied Single Line
Cooling Tower
Water Flow Line
0 ~ 10V (Analog output) Flow control valve
• MULTI V IV • MULTI V S • MULTI V WATER IV • MULTI V WATER S
• MULTI V PLUS II, MULTI V PLUS • MULTI V MINI • MULTI V WATER II • MULTI V SPACE II
Pump / Cooling Tower Controller
<Outdoor Main PCB > Wiring Diagram Flow control valve
ACCESSORIES
Features
<Outdoor Main PCB>
Push Button Push Button Insert wire method
• Connect Terminals (1, 2, GND) on the back side of the outdoor dry contact to terminals (1, 2, GND) of outdoor as show below. Push arrow direction
Pressure sensor
Insert wire method
From Water Source
Push arrow direction
Inverter pump • Flow control valve : Regulates the flow or pressure of a fluid, normally responding to signals generated by independent devices. • Flow Meter : Measures mass flow rate of a fluid traveling through a tube. (The mass flow rate is the mass of the fluid traveling past a fixed point per unit time.) • Pressure Sensor : Measures the pressure.
Insert wire to connector Shows field wiring Connected wiring Shows field wiring Connected wiring
Insert wire to connector * Communication line length can be maximum 300m, use Communication line as thick as 1.25mm
Solution
LG
202
203
AHU KITS
AIR HANDLING UNIT KITS
Solution to connect LG outdoor unit on the DX coil of an air handing unit, with LG’s high efficient products for maximum cost saving
Features • Communication Kit PRCKA1 List
Description On / Off
Mode Change
Cooling / Heating / Fan
Return Air (or Room) Temperature Setting
Communication Kit PRCKA1
Control Kit
PRDCA0
PRCKD21E PRCKD41E
EEV Kit
(Electronic Expansion Valve) PRLK048A0 PRLK096A0
TXV Kit
(Thermal Expansion Valve) PATX13A0E PATX25A0E PATX20A0E PATX35A0E PATX50A0E
Fan Speed Signal Output
3 Steps fan signal output (220V)
Reservation
On / Off, Weekly
Return Air (or Room) Temperature Display
Cooling 18 ~ 30oC, Heating 16 ~ 30oC
Accessories for PRCKA1
• Communication & Control Kit Type
Model
Communication Kit
PRCKA1
MULTI V
PRDCA0
Outdoor unit
EEV Kit
TXV Kit
MULTI V
• •
PRCKD21E
MULTI V
-
PRCKD41E
MULTI V
-
• • • •
Wired Remote Controller Standard II
Dimensions (mm) Description
Centralized Controller
W
H
D 135
•
Return / Room air control by remote controller or dry contact
280
280
-
Return / Room air or supply air (Capacity) control by DDC
330
430
180
Max capacity 1 ~ 4 master outdoor unit
600
750
285
Max capacity 5 ~ 8 master outdoor unit
600
750
285
• •
PREMTB001 (White)
PREMTBB01 (Black)
List
Outdoor Unit Combination (Capacity Range)
Model
Liquid (ODU)
Gas (AHU)
W
H
D
Controlling
• Expansion valves Dimensions (mm)
PDRYCB000
Dry Contact Thermostat 2 Point PDRYCB400
Description
10V
-
-
217
404
83
PATX13A0E
8 ~ 16HP
15.88
15.88
22.2
491
331
174
Outdoor Unit Operation
On / Off
PATX20A0E TXV Kit (Thermal PATX25A0E Expansion Valve) PATX35A0E
18 ~ 26HP
15.88
22.2
28.58
28.58
491
331
174
Communication Kit Operation
On / Off
28 ~ 36HP
22.2
28.58
34.92
34.92
491
331
174
38 ~ 46HP
28.58
34.92
41.3
41.3
491
331
174
PATX50A0E
48 ~ 56HP
28.58
34.92
41.3
41.3
561
331
192
Liquid (Outdoor Side)
Monitoring
12.7
Liquid (AHU Side)
-
0V
12.7
Mode
Compressor Off, Compressor Off & Fan Off, 40 ~ 100% Capacity Control
Fan / Defrost / Cooling / Heating
Fan mode
High / Mid / Low (3 Steps)
Error Status
No Error / Error Occurred
* Binary input and output (Open and short), DO is normal open, for more detail please refer to installation manual Note : DDC or thermostat (filed supplied item) is required to control PRDCA0
Accessories for PRDCA0 Wired Remote Controller Standard II (Monitoring Only) PREMTB001 (White)
Gas (Outdoor Side)
-
Analog Input
12 ~ 20HP
Supply Air Temperature Control (by Outdoor Capacity Control)
Gas (AHU Side)
-
10V
83
H
-
0V
404
H
-
Analog Input
217
Liquid (Outdoor Side)
Max
-
Cooling 18 ~ 30oC, Heating 16 ~ 30oC
Room Temperature Control
-
W
Min
High / Mid / Low (3 steps)
-
Liquid (AHU Side)
Type
Fan Step Signal Output
12.7
• TXV Kit
PVDSMN000 (MULTI V IV) PWFCKN000 (MULTI V WATER IV)
Fan only / Heating / Cooling
12.7
W
PDRYCB500
Mode Change
4 ~ 10HP
• EEV Kit
IO Module (for Outdoor Capacity Control)
Digital Input* (Non Voltage) Digital Input (Non Voltage) Voltage Output (220V ~ 230V)
On / Off
EEV Kit PRLK048A0 (Electronic Expansion Valve) PRLK096A0
22.2
PDRYCB300
Modbus
PRDCA0 Communication Kit Operation
Pipe Diameter (mm) Gas Liquid (ODU) (AHU)
Simple
PREMTBB01 (Black)
Digital Output* (Non Voltage) Digital Output (Non Voltage) Digital Output (Non Voltage) Digital Output (Non Voltage) Digital Output (Non Voltage)
Max : AC 250V, DC 30V, 1A Max : AC 250V, DC 30V, 1A Max : AC 250V, DC 30V, 1A Max : AC 250V, DC 30V, 1A Max : AC 250V, DC 30V, 1A
Control Solution
Combination
Type
Cooling 18 ~ 30oC, Heating 16 ~ 30oC
Note : PRCKA1 is controlled by LG wired remote controller or LG centralized controller
Specifications
Control Kit
ACCESSORIES
Communication Kit Operation
LG
Solution
204
AHU KITS
205
AIR HANDLING UNIT KITS
Solution to connect LG outdoor unit on the DX coil of an air handing unit, with LG’s high efficient products for maximum cost saving
Features
Installation Scene
• Control Kit
• Simple Control with PRCKA1 – Single AHU
List
Required Item
Heating / Cooling
MULTI V
AHU (Field Supply)
PRCKA1
SA / RA temperature sensor (or SA / RA temperature & humidity sensor)
Wired Remote Controller
EEV Kit or TXV Kit
Wired Remote Controller
Centralized Controller
DDC (Field Supply) + Dry Contact
IO module
SA/RA temperature, CO2 sensor, Damper actuator (OA, EA, Mix)
Energy Waving (Cooling Mode only)
EEV Kit or TXV Kit
ACCESSORIES
Automatic Ventilation
Optional
SA temperature, OA / RA temp&humidity sensor, Damper actuator (OA, EA, Mix)
Humidification
SA temperature, RA temperature & Humidity sensor, Humidifier
Inverter Fan Control
SA / RA temperature, Static pressure sensor, Inverter driver for fan control
Filter Alarm
• Simple Control with PRDCA0 – Single AHU
Difference pressure Sensor
Smoke Detecting
MULTI V
Smoke detection sensor
AHU (Field Supply)
PRDCA0
DDC (Field Supply) + Dry Contact
RA : Return Air, EA : Exhaust Air, OA : Outdoor Air, SA : Supply Air, MA : Mix air (RA + OA)
• Field supplied item List
Required Specification
Apply Location
- Power : AC 24V, Output Signal : DC 0 ~ 10V - Temperature Boundary : -50 ~ 50°C
- Apply to MA, SA, RA
Temperature & Humidity Sensor
- Power : AC 24V, Output Signal : DC 0 ~ 10V - Temperature Boundary : -40 ~ 70°C - Humidity Boundary : 0 ~ 95% RH
- Apply to SA, RA, OA - Can not be applied to MA
Damper Actuator
- Power : AC 24V, In / Output Signal : DC 0 ~ 10V - Torque : 15 Nm, Operation Time : 150sec. - Rotation Angle : 90°
- Apply to OA, EA, MA damper
Difference Pressure Sensor (for Filter)
- Power : AC 24V, Output Signal : DC 0 ~ 10V - Boundary : 0 ~ 1000Pa * Switch Type : Relay Open / Close
- Apply to filter
CO2 sensor Smoke Detection Sensor
• Simple Control with PRCKA1 – Multiple AHUs (DX Coils) AHU (Field Supply)
PRCKA1
EEV Kit Only
Wired Remote Controller
DDC (Field Supply) + Dry Contact Centralized Controller
MULTI V
- Power : AC 24V, Output Signal : DC 0 ~ 10V - Boundary : 0 ~ 1000pa - Power : AC 24V, Output Signal : DC 0 ~ 10V - Boundary : 0 ~ 2000ppm - Power : AC 24V, From : Contact Point type
Static Pressure Sensor
(Monitoring Only)
Control Solution
Temperature sensor
- Apply to SA (for Inverter Control) AHU (Field Supply)
- Apply to RA duct
PRCKA1
EEV Kit Only
Wired Remote Controller
DDC (Field Supply) + Dry Contact
- Apply to RA duct
Note : Boundary of specification can be changed through LGAV software. However, please make a specification referring to the above table
Capacity Selection
Indoor Unit
• For Communication Kit with MULTI V - After checking the need capacity, remove the 36k Option PCB equipped in the main PCB, and set up the Option PCB fitted the need capacity in the main PCB.
Detail
Capacity setting 'Option PCB'
(Main PCB)
Option PCB P/No
Capacity Index (Btu/h)
Recommended Heat Exchanger Volume (10-3 x m3)
Maximum Heat Exchanger Capacity (kW)
Air Flow Rate (CMM)
EBR52358907 EBR52358908 EBR52358909 EBR52358910 EBR52358911 EBR52358912 EBR52358914 EBR52358915 EBR52358916 EBR52358917 EBR52358913
28k 36k 42k 48k 76k 96k 115k 134k 153k 172k 192k
2.7 3.1 3.4 4.0 5.4 6.3 7.3 8.5 9.5 10.5 11.2
8.6 11.0 13.8 15.4 22.2 28.1 33.7 39.3 45.4 50.4 56.2
22 ~ 26 25 ~ 32 31 ~ 35 33 ~ 45 50 ~ 64 64 ~ 72 72 ~ 88 88 ~ 103 103 ~ 116 114 ~ 129 121 ~ 137
* Evaporator Saturated Temperature = 6oC, Air Temperature = 27oC DBT / 19oC WBT * Heat exchanger volume (m3) : Pipe cross-section x Tube length - Pipe cross-section (m2) = ϖ x ID2 / 4
- Tube length (m) = Tube length of 1 pipe x Tube step x Tube row
Wired Remote Controller
• Various Control with Control Kit – Multiple MULTI Vs (Up to 8 ODUs) MULTI V
TXV Kit Only AHU (Field Supply)
MULTI V
Control Kit
Centralized Controller
TXV Kit Only
Sensors and Actuators are Required According to Control Function
LG
Solution
206
207
AHU KITS
AIR HANDLING UNIT KITS
Solution to connect LG outdoor unit on the DX coil of an air handing unit, with LG’s high efficient products for maximum cost saving
Application
Application
• Simple Control with PRCKA1 – EEV Kits + Indoor Units
• Simple Control with PRDCA0 – Single EEV Kit or TXV Kit
Wired Remote Controller
Comm. Kit PRCKA1
Dry Contact (Option)
* DDC : Digital Direct Controller
Refrigerant Piping Communication Wire Sensor Signal *DDC
Comm. Kit PRDCA0
Wired Remote Controller (Monitoring Only)
* DDC : Digital Direct Controller
AI (Analog Input) 0 ~ 10V DI (Digital Input) *DDC DO (Digital Output)
Return Air
Exhaust Air
Outdoor Air
Supply Air
Return Air
Exhaust Air
Outdoor Air
Supply Air
ACCESSORIES
Refrigerant Piping Communication Wire Sensor Signal
EEV Kit EEV Kit TXV Kit or
Control Solution
• Various Control with Control Kit – Multiple MULTI Vs + TXV Kits Refrigerant Piping Communication Wire Thermistor (Pipe Temp.) Signal (On / Off) Signal (DC 0 ~ 10V)
• Simple Control with PRCKA1 – Single TXV Kit (without Indoor Unit) Wired Remote Controller
Refrigerant Piping Communication Wire Sensor Signal
Comm. Kit PRCKA1
* DDC : Digital Direct Controller
Air Handling Unit
Dry Contact (Option)
Temperature Sensor
- Return Air, Supply Air (Essential) - Mixed Air
*DDC
Temp & Humidity Sensor
- Return Air / Supply Air / Outdoor Air
Damper Actuator Return Air
Exhaust Air
Outdoor Air
- Exhaust Air / Outdoor Air / Mixed Air
Supply Air
Differential Pressure Switch Valve for Humidifier Control Kit CO2 Sensor TXV Kit
Smoke Detector Fan
- Supply / Return
Wired Remote Controller Local
Control Kit
Expansion Kit
Solution
LG
208
209
MECHANICAL ACCESSORIES LINE-UP Indoor Ceiling Mounted Cassette Auto Elevation Grille
Ceiling Concealed Duct
Cassette Cover
Suction Grill
AUTO ELEVATION GRILLE Easy filter cleaning with the elevation grille Outdoor MULTI V
PTEGM0
Air Guide
PBSGB30 / PBSGB40
PTEGM0
PTDCM PTDCQ
Cassette Panel
Ventilation Kit
PRAGX3S0 PRAGX2S0
PBSC30 / PBSC40
ETC.
Drain Pan
CO2 Sensor PRODX20 PRODX30
PTVK410 NEW 4 Way Cassette
(Compact Panel) PT-QCHW0
ACCESSORIES
Canvas
PES-C0RV0 PTVK420 PTVK430
Refrigerant Leakage Detector
Features • Easy Filter Cleaning with Elevation Grill - Installation inside main body - Auto horizontal control - 4 points support structure
- Memory for user’s level - Max 4.5m length - Model : PTEGM0 (for chassis TM, TN, TP)
4-Point Support Structure
Auto Horizontal Control
Memory for User’s Level
Auto Bottom Detection
STOP
PRLDNVS0
2 Way Cassette PT-HLC
Independent Power Module
1 Way Cassette (Grill Type) PT-UUC / PT-UUC1 / PT-UTC (Panel Type) PT-UUD / PT-UTD
EEV Kit
PRGK024A0
NEW
IR Receiver
PWLRVN000
Mechanical Accessories Line up and Application Type 1
INDOOR
OUTDOOR
Type 2 Auto Elevation Grille Cassette Panel Cassette Cover Ventilation Kit Suction Grille / Canvas Refrigerant Leakage Detection Kit Independent Power Module CO2 Sensor EEV Kit IR Receiver Air Guide Drain Pan
Operating with wired remote controller* and wireless remote controller included in PTEGM0. * PREMTB001, PREMTBB01
Models Applied
PRIP0 NEW
Mechanical Accessories
4 Way Cassette PT-UQC / PT-UMC1
• 4 Way Cassette : Refer to PDB for applicable models
Parts Included • Inlet Grille (1EA) • Auto Elevation Grille Kit (1EA) • Wireless Remote Controller (1EA)
• Screws (4EA) • Installation Manual (1EA)
Remark 4-Way Cassette 4-Way / 2-Way / 1-Way Cassette 4-Way Cassette 4-Way Cassette Ceiling Concealed Duct (Built-in) MULTI V 4th Generation Indoors Indoor Energy Recovery Ventilator Indoor Ceiling Concealed Duct Outdoor Outdoor
Application
• Auto elevation grille kit
• Install the kit inside indoor unit
• Install the front panel and the Inlet grille
• Operate the auto elevation grille by the wireless remote controller
• Easy maintenance
Solution
LG
210
211
CASSETTE PANEL
CASSETTE COVER
Stylish designed panels make more unique space by various applications
Air purifying filter to prevent dust and allergens
4 Way Cassette
2 Way Cassette
PT-QCHW0
1 Way Cassette (Grill Type)
PT-HLC
PT-UUC / PT-UUC1 / PT-UTC
NEW
PTDCM PTDCQ
(Panel Type)
ACCESSORIES
PT-UUD / PT-UTD PT-UQC / PT-UMC1 Features
• Independent vane operation uses separate motors, making it Possible to control all four vanes independently. • The detachable corner design makes it easy to adjust the hanger during installation and to check for leakages in the drain connection pipe.
• Specially designed for indoor unit • Covers the side area of cassette
Compact and Stylish Design
Models Applied
• New 4 way cassette panel adapted unibody shape and matching with into the ceiling
• Panel size is fit into the ceiling tile
Unibody Shape
• 4 Way Cassette (for chassis TP, TN, TM, TQ, TR)
Parts Included
620m
m
• Cover A (4EA), Cover B (4EA) • Cover C (4EA), Cover D (4EA)
(No Inlet Line)
620m
m
Specifications Suction Type
Color (RAL)
Gloss
Weight (kg)
Dimension (mm) W H D
Applied Model MULTI V
PT-QCHW0
Horizontal Grill
Morning Fog (RAL 120-4)
X
3.0
620
20
620
1.5 ~ 5.0kw
4-Way
PT-UQC
Horizontal Grill
Morning Fog (RAL 120-4)
X
3.0
700
22
700
1.5 ~ 5.0kw
PT-UMC1
Horizontal Grill
Morning Fog (RAL 120-4)
X
5.6
950
25
950
7.1 ~ 14.0kw
2-Way
PT-HLC
Grill
Morning Fog (RAL 120-4)
X
4.0
1,050
28
640
5.0 ~ 7.1kw
PT-UUC
Grill
Noble White (RAL 110-1)
O
4.6
1,100
34
500
2.1 ~ 3.5kw
PT-UUC1
Grill
Morning Fog (RAL 120-4)
X
4.4
1,100
34
500
2.5 ~ 3.5kw
1-Way
• Screws • Installation Manual (1EA)
Accessory Model Name Model
Model name
• Gives elegant looks • Light weight
Mechanical Accessories
Features
PT-UTC
Grill
Noble White (RAL 110-1)
O
5.5
1,420
34
500
5.0 ~ 7.1kw
PT-UUD
Panel
Noble White (RAL 110-1)
O
4.6
1,100
34
500
2.1 ~ 3.5kw
PT-UTD
Panel
Noble White (RAL 110-1)
O
5.5
1,420
34
500
5.0 ~ 7.1kw
Weight (kg)
Front Panel
NET
Gross
W
Dimensions (mm) H
D
5.9
8.8
1,157
1,157
268
PTDCM
PT-UMC / PT-UMC1
TP / TN TM
5.9
8.8
1,157
1,157
310
PTDCQ
-
TR
5.0
7.2
907
907
268
TQ
5.0
7.2
907
907
310
Solution
LG
212
213
VENTILATION KIT
SUCTION GRILLE / CANVAS
Fresh air can be supplied from outside through this ventilation kit
High flexibility for a wide variety of applications
PTVK410 PTVK420 PTVK430
PBSGB30 PBSGB40 PBSC30 PBSC40 PTVK420
PTVK430
ACCESSORIES
PTVK410
SUCTION GRILLE - PBSGB30 / PBSGB40
CANVAS - PBSC30 / PBSC40
Features
Features
• The ventilation kit can be supplied air from outside.
• High external static pressure facilitates unit use with flexible ducts of varying lengths • When using suction grille, unit requires only 270mm of ceiling space • Blends unobtrusively with any interior decoration
Models Applied • There are 2 Solutions for Fresh Air
Models Applied • Ceiling Concealed Duct _ Built-in type
* Users can purchase and use PTVK430 in addition to PTVK410+PTVK420 in need to phase in larger outdoor air volume.
Accessory Model Name
Parts Included • PTVK410 : 1 Ventilation Kit, 8 Bolts, 1 Insulation • PTVK420 : 1 Flange, 7 Screws • PTVK420 : 1 Flange, 4 Screws, 1 Insulation
Category Grille
Dimensions
Canvas
Assembly Diagram 406
4
840
435
443
81
13
Mechanical Accessories
- PTVK410+PTVK420 (for chassis TP, TN, TM) - PTVK430 (for chassis TR, TQ, TP, TN, TM)
PTVK430 419 840 55mm
PTVK410+PTVK420
Model Name
Capacity (Btu/h) ARNU07GB3G2 ARNU09GB3G2 ARNU12GB3G2 ARNU15GB3G2 ARNU18GB4G2 ARNU24GB4G2
PBSGB30
O
O
O
O
-
-
PBSGB40
-
-
-
-
O
O
PBSC30
O
O
O
O
-
-
PBSC40
-
-
-
-
O
O
Solution
LG
214
215
SUCTION GRILLE / CANVAS
CO2 SENSOR
High flexibility for a wide variety of applications
CO2 sensor in ventilation system.
Parts Included
PES-C0RV0
• For the Suction Grille :
• For the Suction Canvas :
- Suction panel with air filter (1EA) - Suction panel fix bolt M5 x 18 (4EA) - Installation manual (1EA)
Features
Dimensions
1) Model name : PES-C0RV0 2) Specification C
C
C
A B
A
B
C
Model Name
359 359
56 56
PBSC30 PBSC40
Off
500 ~ 700ppm
Low Speed
700 ~ 900ppm
High Speed
>900ppm
Super High Speed
A
B
C
821 1,100
274 274
42 ~ 250 42 ~ 250
• The product is especially designed to detect CO2 concentration in ERV system. Mechanical Accessories
A
ERV Fan Operation
<500ppm
3) Description (Unit : mm)
910 1,188
CO2 Sensor Reading
- Supply Vottage : DV 12V ± 5% - Output : 0 ~ 5V (Linear output, 1 ~ 2,000ppm CO2) - Accuracy : 30ppm ± 5% of reading
B
(Unit : mm) PBSGB30 PBSGB40
• Operation Table
• Applied Model : ERV, ERV DX • Function
A B
Model Name
ACCESSORIES
- Air suction canvas (1EA) - Screws for air suction canvas (4EA) - Adjusting chain (4EA) - Screws for adjusting chain (8EA) - Installation manual (1EA)
Installation Scene
Standard Wired Remote Controller
CO2 Sensor (PES-C0RV0)
CO2 (ppm)
over 270mm
over 520mm
Application
2,500
Windows Closed
Windows Open
Windows Closed
Windows Open
1,000 0 ERV with CO2 Concentration Control Time (min)
Solution
LG
216
217 NEW
EEV KIT
R410A refrigerant leakage detector makes more safe our space
MULTI V EEV KIT is specially designed to reduce noise and make comfort environment
PRLDNVS0
PRGK024A0
Features
Features
• This detector senses refrigerant leakage and when the refrigerant concentration exceeds 6,000ppm not only it will stop indoor unit operation but also it will give an alarm using buzzer and sensor LED. (The green and red LED lights blink simultaneously.) • Alarm is “ON” over 6,000ppm has been maintained 5 seconds, and on the contrary to this, Alarm is “OFF” under 6,000ppm has been maintained 5 seconds. • When the alarm of the refrigerant leak detector is switched on the user must ventilate until the alarm is disabled. • The detector has to be installed inside the room and it can be installed 300 ~ 500mm from floor.
• Decreasing noise level of Multi V Indoor units Easy installation
* Fresh Air intake Unit is not able to connect this Kit
Specifications
Application
Specifications Rated Voltage (V)
DC 5.0 ± 5%
Dimensions (W x H x D, mm)
31 x 44 x 20
Weight (g) Detectable Refrigerant
Sensor
Detected Concentration (ppm)
Connecting Cable
• Console (up to 15kBtu) • Floor Standing Unit (with Case / without Case) (up to 15kBtu) • Convertible (up to 12kBtu, Ceiling Suspended Type is not able to connect this Kit)
22 R410A 0 / 6,000 Alarm Off / On
Operating Temperature Range (oC)
-10 ~ 50
Preserved Temperature Range (oC)
- 40 ~ 60
Average Power Consumption (mA)
35
Cable Length (m)
10
Dimensions of Front Plate (W x H x D, mm)
80 x 110 x 44.6
Dimension of Backplate (W x H x D, mm)
80 x 110 x 6.5
Sensor Protective Cover
Application 3 Stop Operation and Ring Alarm 2 Senses Refrigerant Leakage
1 Refrigerant Leakage
Note : If you don’t use EEV of same specification, Cooling (Heating) capacity may decrease.
Mechanical Accessories
• New 4th generation indoor units only More detailed information refer to the “MULTI V INDOOR UNIT LINE UP & FEATURES OVERVIEW”. (Page 96 ~ 97)
Parts
Models Applied • Ceiling Cassette (up to 15kBtu) • Ceiling Concealed Duct (up to 18kBtu) • Wall Mounted (up to 24kBtu)
Models Applied
ACCESSORIES
REFRIGERANT LEAKAGE DETECTOR
LG
Solution
218
219
NEW
IR RECEIVER IR RECEIVER can be connected to CCD where the customer wants to control by wireless remote controller
INDEPENDENT POWER MODULE
PWLRVN000
PRIP0
Features
Features
• Designed for wireless control to operate Ceiling Concealed Duct Operation of Indication lamp (3 colors) Self-diagnosis function
• Independent Power Module is specially designed to close the Indoor EEV at power cut-Off.
EEV full close function in case of power cut
ACCESSORIES
- Supply Voltage : DC 12V ±50%
Models Applied
• MULTI V Indoors (Ceiling Concealed Duct, Floor Standing Units)
• MULTI V Indoors
Application
Mechanical Accessories
Models Applied
3 Phase 400V Outdoor Unit
1 Phase 220V
4th
Independent Power Module (Option)
Switch BOX Main Switch
Power Plug 3rd 2nd
A/C Switch
1st
Each room
Independent Power Module (Option)
Switch BOX Main Switch
Power Plug 3rd 2nd
A/C Switch
1st
Each room
Note : Do not install both the IR Receiver and Wired Remote Controller. This may cause malfunctions.
Solution
LG
220
221
AIR GUIDE
DRAIN PAN
Air discharge in difficult to access areas
Easy drain installation
PRAGX*S0
PRODX20 / PRODX30
512
Features 632
50 45
• Converts vertical discharge into horizontal discharge • Designed for outdoor discharge air
PRODX20
PRODX30
33
Features
00
R6
512
564
PRAGX3S0 (8 / 10 / 12HP)
ACCESSORIES
PRAGX2S0 (14 / 16 / 18 / 20HP)
• Direction of air discharge can be changed by simple installation • Installation flexibility
• This unit can be applied for outdoor unit’s drain.
652
618
0
60
Models Applied 33
50
512
512
00
R6
* In case of UX3, must purchase 2 units of PRAGX3SO. 652
Dimensions 618
900
564 00
Net Weight
22.5kg
12.3kg
17kg
9.4kg
• MULTI V IV (UX2)
760
50
832
564
564 33
652
Drain Pipe 0
33
60
* In case of the installation of drain pan, drain pipe should be located below the SVC valve.
00
00 R6
R6
* Push drain pan in the direction of the arrow. Brackets can be fixed on the side panel.
632
632
618
50
45
904
45
760
45
45
570
0
652
832
900
500
500
500
0
718
0 60 60 R
R
50
760
760
904
45
832
50
762 832
832
500
832
* N : Heat Pump / B : Heat Recovery
832
50
500
50
50
570 - ARU*140LTE4 570 - ARU*160LTE4 - ARU*180LTE4 - ARU*200LTE4 900
45
652
00
• MULTI V IV (UX3)
500
* N : Heat Pump / B : Heat Recovery
900
45
• MULTI V IV (UX2) 45
762
• This unit does not cover water drops of the outside product. • Connect drain hose to drain pipe for drain condensate.
0 0 6
Application 904
652
652
60
718
- ARU*080LTE4 - ARU*100LTE4 - ARU*120LTE4
50
618
832
45
832
50
50
512
512
512
762
00
500
Service Valve
618 718
500
632
• MULTI V IV (UX3)
900
R6
* Tuck drain pan below base pan 00
R6
652
570
512
832
50
PRAGX3S0
45
50
PRAGX2S0
33
512
Gross Weight 500
500
652
Model Name
R6
512
0
60
45
632
570
45
50
Mechanical Accessories
• MULTI V IV (UX2, UX3)
Installation
652
564
R6
760
Accessory Model Name Model Name
Width x Length
Remark
PRODX20
920mm x 466mm
UX2
PRODX30
1,240mm x 466mm
UX3
LG
Solution
222
223
PIPING ACCESSORIES LINE-UP MULTI V Heat Recovery Unit
Y Branch and Header Branch
HEAT RECOVERY UNIT PRHR022 PRHR032 PRHR042 PRHR032 (3 Branch Unit)
PRHR042 (4 Branch Unit)
Features
PRHR022 PRHR032 PRHR042
• Max. 32 indoor units can be connected (Max. 8 indoor units per branch) • It is easy to install due to the automatic search algorithm for piping detection • Subcooling cycle in HR unit makes the system efficiency maximum
ACCESSORIES
PRHR022 (2 Branch Unit)
ETC Stopper Valve
Drain Hose
Models Applied • MULTI V IV Heat Recovery • MULTI V III Heat Recovery • MULTI V SYNC II • MULTI V SYNC PHDHA05T PHDHA07T PHDHA05B PHDHA07B
Specifications Model name
Mechanical Accessories Line up and Application Model name Heat Recovery Unit Y Branch and Header Branch
Remark MULTI V Sync II / MULTI V III Heat Recovery / MULTI V IV Heat Recovery Various Type of MULTI V Series
PRHR022
PRHR032
PRHR042
Number of Branch
EA
2
3
4
Maximum Connectable Capacity of Indoor Units (Per branch / unit)
kW
16 / 32
16 / 48
16 / 58
Maximum Number of Connectable Indoor Units per Branch
EA
8
8
8
kW
0.026
0.040
0.040 0.040
Nominal Input
Cooling
kW
0.026
0.040
Net. Weight
Heating
kg
18
20
22
Dimensions (W x H x D)
mm
801 x 218 x 617
801 x 218 x 617
801 x 218 x 617
Indoor Unit Piping Connections
Outdoor Unit
Power Supply
Liquid
mm (inch)
9.52 (3/8)
9.52 (3/8)
9.52 (3/8)
Gas
mm (inch)
15.88 (5/8)
422 x 202 x 300
422 x 202 x 300
Liquid
mm (inch)
9.52 (3/8)
15.88 (5/8)
15.88 (5/8)
Low pressure
mm (inch)
22.2 (7/8)
28.58 (11/8)
28.58 (11/8)
High Pressure
mm (inch)
19.05 (3/4)
22.2 (7/8)
22.2 (7/8)
Ø / V / Hz
1 / 220~240 / 50
1 / 220~240 / 50
1 / 220~240 / 50
Parts Included • HR unit (1EA) • Hanging bolts M10 or M8 (4EA) • Nut M8 or M10 (8EA)
• Washers M10 (8EA) • Reducers
Piping Accessories
PRVT120 PRVT780 PRVT980
• MULTI V WATER IV Heat Recovery • MULTI V WATER II Heat Recovery
LG
Solution
224
225
HEAT RECOVERY UNIT
Y BRANCH AND HEADER BRANCH For refrigerant distribution of indoor units
Reducers for Indoor Unit and HR Unit (Unit : mm)
Model Name
Liquid
High pressure
Low pressure
Y Branch
Header Branch
Features • Various Y Branch pipe of different capacities make MULTI V installation much easier. • Y Branch and header branch for both gas and liquid are provided. • Insulation material is also provided for covering the branches.
PRHR022
ACCESSORIES
Indoor unit reducer
HR unit reducer
Piping Diagram
PRHR032 / PRHR042
Heat Pump System Y Branch for Indoor Units (2 Pipes)
Y Branch for Heat Pump Outdoor Units (2 Pipes)
MULTI V IV Heat recovery provides flexible control over individual zones for the user’s convenience.
• Individual Control
Office
- Perfect individual control over spaces ventilation needed
Kitchen
Heat Recovery System
• Zone Control
Y Branch for Heat Recovery Units (3 Pipes)
- Max. of 8 indoor units can be connected for one branch - Max. of 32 indoor units can be connected for one HR unit - Same opeational model can be operated by indoor units with zone control function installed
HR Unit Y Branch for Heat Recovery Outdoor Units (3 Pipes)
• Combination of Individual and Zoning Installations - Flexible piping design
Y Branch for Zoning Control (2 Pipes)
• Save Product and Installation Cost
HR Unit
Room
[Zoning Control]
Piping Accessories
Convenient Free Zoning
Header for Indoor Units (2 Pipes)
IT Room HR unit
Zoning Control (Max Indoor unit 8EA)
Models Applied • MULTI V IV • MULTI V S • MULTI V WATER IV • MULTI V WATER S
• MULTI V III, MULTI V PLUS II, MULTI V PLUS • MULTI V MINI • MULTI V WATER II • MULTI V SPACE II
LG
Solution
226
227
PIPING ACCESSORIES Y Branch pipe for connection of outdoor units
Details of Model Name [Header Branch] • R410A
[Heat Pump] • R410A MULTI V IV, MULTI V III ,MULTI V WATER IV, MULTI V WATER II (Unit : mm)
Gas Pipe
Liquid Pipe
2 Outdoor Units Model Name
Low Pressure Gas Pipe
Liquid Pipe
416 408
4 Branch / ARBL054
C ARCNN21
ARCNN21
C ARCNN21
111
I.D.22.2
I.D.31.8 I.D.34.9
416 408 I.D.15.88
130
BARCNN21 C
C
C
I.D.41.3 I.D.31.8 I.D.34.9
B ARCNN31 C ARCNN21
416 408 I.D.15.88
I.D.28.58 I.D.34.9
O.D.34.9
111
111
I.D.22.2
415 70 130375
B
B
C ARCNN31
A
C
B
C C ARCNN21
7 Branch / ARBL107
I.D.41.3
416 408
I.D.41.3 I.D.28.58
I.D.41.3 I.D.31.8 I.D.34.9
111
I.D.28.58 I.D.28.58
O.D.34.9
111
I.D.22.2 I.D.28.58
I.D.41.3 O.D.34.9 I.D.19.05 I.D.31.8 I.D.34.9
I.D.28.58
415 130 375
B
B
C
C
B B C ARCNN31
A
Model Name
B
C
I.D.41.3
A ARCNN41 B ARCNN31
341
298
I.D.41.3
134
I.D.28.58 I.D.34.9
111
A
B
C
A
A ARCNN41 B
I.D.44.48 I.D.53.98
83
I.D.12.7 I.D.9.52
83
I.D.15.88 I.D.12.7
I.D.15.88
I.D.12.7 Liquid Pipe
I.D.22.2 O.D.19.05
I.D.15.88
334
70
281
111 I.D.22.2 I.D.12.7 I.D.9.52 I.D.15.88
83 I.D.12.7
83
I.D.15.88
I.D.12.7
I.D.15.88
334 70
70
341 I.D.19.05 298
I.D.22.2 334 I.D.41.3 I.D.44.48 I.D.53.98 I.D.25.4 O.D.22.2 281
I.D.41.3
I.D.15.88 I.D.12.7 I.D.15.88 83 I.D.19.05
I.D.15.88 I.D.12.7
281
80 4I.D.41.3 Outdoor Units I.D.22.2 I.D.19.05
83
I.D.12.7 I.D.9.52
I.D.19.05
I.D.22.2 O.D.19.05 I.D.28.58 I.D.12.7
I.D.19.05
I.D.19.05
83 I.D.22.2
134
281
334
I.D.19.05
281
I.D.34.9 I.D.28.58
I.D.19.05
83
I.D.25.4 O.D.22.2 111 83
I.D.19.05
I.D.15.88 I.D.12.7 I.D.22.2
I.D.19.05 80
83
I.D.19.05
Liquid Pipe
O.D.34.9 I.D.28.58 I.D.15.88 I.D.12.7
I.D.15.88 I.D.12.7
125 415
415
ARCNN41
I.D.15.88 I.D.19.05
I.D.19.05
281
I.D.28.58 125
375
83
I.D.15.88 I.D.12.7
O.D.34.9 Gas Pipe LowI.D.41.3 Pressure
10 Branch / ARBL1010
331 314 I.D.15.88 83 I.D.22.2 I.D.19.05
334
334
130
I.D.44.48 I.D.53.98
I.D.12.7 I.D.28.58
I.D.41.3 I.D.38.1 125 O.D.34.9 I.D.22.2 O.D.19.05
I.D.41.3 I.D.38.1 O.D.34.9
A ARCNN41
281
I.D.15.88 I.D.28.58 I.D.34.9 111 I.D.19.05 I.D.12.7 I.D.9.52 111 I.D.22.2
I.D.28.58
125 415
334
281 331 314
334 334 I.D.19.05 83 I.D.22.2 I.D.19.05 298 I.D.22.2 I.D.19.05 281 134 I.D.41.3 I.D.44.48 I.D.53.98 281 I.D.25.4 O.D.22.2 I.D.25.4 O.D.22.2 331 416 331 314 408 I.D.15.88 I.D.12.7 314 I.D.15.88 I.D.28.58 111 I.D.28.58 I.D.41.3 I.D.34.9 83 I.D.22.2 I.D.15.88 I.D.19.05 I.D.19.05 I.D.28.58 I.D.15.88 I.D.22.2 I.D.19.0580 80
375
A
10 Branch / ARBL2010
134
I.D.34.9
334
341
298
C
C
A ARCNN41 B ARCNN31 C ARCNN21
341
I.D.44.48 I.D.53.98
I.D.15.88
A ARCNN41 I.D.41.3
C
I.D.28.58
134
334
334
375
281
281
I.D.53.98I.D.19.05 I.D.44.48I.D.22.2
I.D.41.3
I.D.19.05 134
83
I.D.15.88 I.D.12.7 I.D.28.58 80
I.D.22.2
I.D.19.05
I.D.19.05
83
I.D.25.4 O.D.22.2
I.D.25.4 O.D.22.2
I.D.15.88 I.D.12.7 80
Piping Accessories
A
A ARCNN41 B B C ARCNN31
I.D.12.7
83
70
I.D.41.3 I.D.38.1 O.D.34.9 125
415 130 375
4 Branch / ARBL104
I.D.22.2 O.D.19.05
I.D.15.88
3 Outdoor I.D.22.2 UnitsO.D.19.05I.D.28.58 I.D.15.88 I.D.12.7
I.D.28.58
I.D.28.58 125 Low Pressure Gas Pipe
C
I.D.28.58 I.D.41.3 I.D.22.2 I.D.19.05 I.D.19.05 I.D.41.3 O.D.34.9 I.D.31.8 I.D.34.9
I.D.41.3 I.D.38.1 O.D.34.9
Model Name
83
70
298
298
416 408 I.D.28.58 I.D.41.3
I.D.15.88
I.D.12.7 I.D.9.52
I.D.19.05
341
341
B
I.D.12.7 I.D.28.58
I.D.28.58
B ARCNN31 C
331 314 I.D.15.88
I.D.15.88
I.D.12.7 111 I.D.9.52 I.D.22.2
I.D.19.05 I.D.31.8 I.D.34.9
130
7 Branch / ARBL057
331 314 I.D.28.58
I.D.41.3 I.D.38.1 O.D.34.9 I.D.22.2 O.D.19.05
I.D.41.3 I.D.38.1 O.D.34.9
C
C
I.D.28.58
I.D.28.58
I.D.28.58
ACCESSORIES
Model Name
(Unit : mm)
LG
Solution
228
229
PIPING ACCESSORIES Y Branch pipe for connection of outdoor units
[Heat Recovery] • R410A MULTI V IV Heat Recovery, MULTI V III Heat Recovery, MULTI V WATER IV Heat Recovery, MULTI V WATER II Heat Recovery
[Heat Pump, Heat Recovery zone control] • R410A MULTI V IV, MULTI V III, MULTI V PLUS II, MULTI V PLUS, MULTI V S, MULTI V MINI, MULTI V SPACE II, MULTI V WATER IV, MULTI V WATER S, MULTI V WATER II
Model Name
ARCNB21
I.D.22.22
I.D.31.8 I.D.34.9 I.D.41.31
I.D.18.88
I.D.28.58
111
I.D.12.7
I.D.9.52
I.D.22.2
I.D.28.58 130
I.D22.2
I.D.15.88 I.D.15.88
70
I.D6.35
I.D12.7
I.D15.88
I.D12.7
I.D6.35
I.D. 9.52 O.D9.52
83
I.D.19.05
I.D.19.05
I.D9.52
I.D6.35
O.D15.88
O.D.19.05 I.D.12.7
I.D9.52
I.D15.88
I.D19.05
83 I.D.22.2
.D.38.1 O.D.34.9
ARBLN01621
Liquid Pipe I.D15.88
I.D15.88
I.D12.7
334 281
I.D.15.88
I.D.19.05
Gas Pipe
High Pressure Gas Pipe
331 314
416 408 I.D.28.58
Model Name
2 Outdoor Units Liquid Pipe
Low Pressure Gas Pipe
ACCESSORIES
(Unit : mm)
(Unit : mm)
I.D19.05
I.D19.05
I.D15.88
I.D9.52
I.D9.52
I.D6.35
I.D.12.7 I.D12.7
I.D25.4
ARBLN03321
I.D12.7
I.D12.7
O.D19.05
I.D28.58
I.D12.7
I.D15.88 I.D19.05
I.D9.52
Model Name
Low Pressure Gas Pipe
2 Outdoor Units Liquid Pipe
341 298
I.D.34.9
I.D.41.3 I.D.41.3
I.D.28.58
111 I.D.22.2
O.D.34.9
I.D.19.05
I.D.19.05
83
I.D.31.8
(Unit : mm)
I.D.28.58
111
I.D.22.2
I.D.34.9 I.D.41.31 .D.38.1
I.D.28.58
• R410A MULTI V IV, MULTI V III, MULTI V PLUS II, MULTI V PLUS, MULTI V S, MULTI V MINI, MULTI V SPACE II, MULTI V WATER IV, MULTI V WATER S, MULTI V WATER II
416 408
334 281
I.D12.7
I.D 22.2
Model Name
Gas Pipe
Liquid Pipe I.D19.05
O.D.34. 9 I.D.28.58
I.D28.58
I.D22.2
Piping Accessories
ARCNB31
High Pressure Gas Pipe
I.D6.35
O.D19.05
I.D25.4
O.D19.05 I.D 22.2
I.D15.88
I.D19.05 I.D12.7
I.D15.88
I.D15.88
I.D12.7
I.D.15.88 I.D.12.7
125
I.D12.7
130
ARBLN07121
I.D19.05 I.D34.9 O.D31.8
I.D12.7 I.D19.05
I.D31.8 I.D15.88
I.D31.8 O.D22.2 I.D28.58 O.D19.05 I.D28.58 I.D22.2
I.D15.88 O.D12.7 I.D6.35 I.D9.52
I.D19.05
I.D9.52 O.D12.7
I.D34.9 I.D34.9
Model Name
Low Pressure Gas Pipe
4 Outdoor Units Liquid Pipe
ARCNB41
I.D.44.48 I.D.53.98
I.D.41.3
134
I.D.22.2
I.D.19.05 I.D.25.4
I.D.19.05
83
I.D.41.3 O.D.34. 9
80
I.D.28.58 125
I.D28.58 I.D28.58
I.D41.3 O.D34.9 I.D41.3 O.D38.1 I.D38.1
O.D22.2 I.D15.88 I.D19.05
I.D.34.9 I.D.41.3
I.D.15.88 I.D.12.7 I.D.28.58
ARBLN14521
341 298
O.D.22. 2
I.D38.1
I.D38.1
High Pressure Gas Pipe
334 281
415 375
I.D41.3
I.D34.9
I.D22.2
I.D12.7 O.D28.58 I.D19.05 O.D15.88 I.D22.2
111
• R410A MULTI V IV, MULTI V III, MULTI V PLUS II, MULTI V PLUS, MULTI V S, MULTI V MINI, MULTI V SPACE II, MULTI V WATER IV, MULTI V WATER S, MULTI V WATER II (Unit : mm)
Model Name
ARBLN23220
Low Pressure Gas Pipe
Liquid Pipe
LG
Solution
230
231
PIPING ACCESSORIES
STOPPER VALVES
Y Branch pipe for connection of outdoor units Under 1 / 2 (inch)
PRVT120 [Heat Recovery] • R410A MULTI V IV Heat Recovery, MULTI V III Heat Recovery, MULTI V WATER IV Heat Recovery, MULTI V WATER II Heat Recovery
Under 7 / 8 (inch)
PRVT780 Under 9 / 8 (inch)
Model Name
Low Pressure Gas Pipe I.D15.88
I.D12.7
ARBLB01621
Liquid Pipe I.D9.52
High Pressure Gas Pipe
I.D9.52
Features
I.D6.35
I.D6.35
I.D15.88
I.D12.7
I.D19.05
I.D15.88
I.D12.7
O.D15.88
Model Name
I.D6.35
I.D. 9.52
PRVT980
ACCESSORIES
(Unit : mm)
Specification
O.D9.52
PRVT120 I.D22.2
I.D19.05
I.D19.05
I.D15.88
I.D9.52
I.D9.52
I.D6.35
I.D12.7
I.D25.4
ARBLB03321
I.D12.7
I.D12.7
O.D19.05
I.D28.58
I.D12.7
I.D15.88 I.D19.05
I.D9.52
I.D6.35
PRVT780
I.D12.7
O.D19.05
I.D25.4
O.D19.05
I.D 22.2
I.D 22.2
I.D19.05
I.D19.05 I.D28.58
I.D22.2
I.D15.88
I.D15.88
I.D12.7
I.D15.88
I.D12.7
I.D12.7
I.D12.7 I.D19.05
I.D19.05
I.D15.88 I.D6.35 O.D12.7 I.D9.52
O.D22.2
I.D31.8
I.D28.58
I.D34.9
O.D19.05
O.D31.8
PRVT980
I.D15.88
I.D28.58
Piping Accessories
I.D31.8
ARBLB07121
I.D19.05
I.D9.52
I.D22.2
O.D12.7
I.D34.9 I.D41.3
I.D34.9
I.D38.1
I.D28.58
I.D41.3 O.D38.1
Usage
I.D28.58
I.D38.1
ARBLB14521
I.D41.3
I.D22.2
I.D34.9
O.D34.9
I.D38.1
I.D15.88 O.D22.2 I.D19.05
I.D12.7 O.D15.88
O.D28.58
• This unit can be applied for the additional indoor unit’s installation. • This unit can be applied for each indoor unit’s service.
I.D19.05
I.D22.2
• R410A MULTI V IV Heat Recovery, MULTI V III Heat Recovery, MULTI V WATER IV Heat Recovery, MULTI V WATER II Heat Recovery
Installation (Unit : mm)
Model Name
Low Pressure Gas Pipe I.D.53.98
I.D.44.48
O.D.38.1 2 3
I.D.28.58 X2 175
O.D.44.48
I.D.53.98
2 3
X2
I.D.22.2
3 O.D.22. 2
346 379
I.D.15.88
O.D.19.05
I.D.15.88
2 3
I.D28.58 2
471 517
96
I.D19.05 O.D22.2 3
I.D19.52 I.D6.35
O.D12.7
I.D15.88 O.D38.1 I.D41.3
120 3 O.D15.88
O.D34.9
I.D12.7
I.D22.2 I.D19.05
2 70
I.D41.3 130
O.D28.58 120
1. Cut the inlet side of the connector, and weld the pipe
2. If installing additional indoor units, the outlet side connector should be cut according to installation pipe.
I.D38.1
3 90
Pin(Closed)
125
3
2
3 110
I.D28.58 I.D34.9 I.D22.2
I.D38.1
3
I.D.12.7 X2
110 120
I.D38.1
I.D.19.05 2
I.D.22.2
115 I.D.19.05
3 70
I.D22.2
I.D.25.4 I.D.22.2 I.D.19.05
I.D.25.4 O.D.28.58 3
100 I.D12.7
O.D15.88
I.D25.4
3
I.D31.8
I.D34.9 I.D.41.3
I.D.25.4
I.D.44.48 I.D38.1 134
I.D41.3 420 490
I.D.34.9
High Pressure Gas Pipe I.D34.9
2
1
ARBLB23220
Liquid Pipe
I.D.44.48 I.D41.3 I.D38.1
* When welding, service valve shoud be wrapped by wet cloth.
3. When installing a stopper valve, the flare part should be facing towards additional indoor unit.
Pin(Open)
4. When installing anadditional indoor unit, the SVC valve should be in closed state.
LG
Solution
232
233
STOPPER VALVES
DRAIN HOSE Easy drain installation
Details of Model Name • Case1 In case of the installation of additional Cut inlet side of the connector, and weld pipe 1 & 2 : Need to install indoor units) indoor unit, outlet side connector should (Room 3 & 4 : In use /the Room be cut according to installation pipe.
ACCESSORIES
* Stopper Valve is already installed
PHDHA05T PHDHA07T PHDHA05B PHDHA07B
"A" 9.52 : 19.05 Room 1
3.0m 9.52 : 19.05 3.0m
Closed State Pin(Closed)
Pin(Open)
Stopper Valves
In case of installation of stopper valve, 9.52 : 15.88In case of installation of additional flare part should be facing towards indoor unit, SVC valve should be in 10.0m additional indoor unit. closed state
Room 2
-When welding, service valve shoud be wrapped by wet cloth. 9.52 : 15.88
5.0m 6.35 : 12.7 3.0m
Features • It reduces the installation time by over 40% with elbow-less drain hose. • Midget drain pump covers maximum 800mm high, featuring easy piping installation.
Models Applied
Room 3
• Ceiling Mounted Cassette and Ceiling Concealed Duct (refer to PDB for applicable model)
Room 4
Max. 450
250
Ceiling Mounted Cassette (4 Way, 1 Way) Ceiling Concealed Duct (with Drain Pump)
Flexible Hose Make a Loop Form (Unit : mm)
be cut according to installation pipe.
Open / Close Port
Charge Port
Accessory Model Name
9.52 : 19.05 3.0m 9.52 : 19.05 3.0m
Pin(Closed)
Stopper Valves
: 15.88 In case of installation of9.52 stopper valve, flare part should be facing towards additional indoor unit. 10.0m
In case of installation of additional indoor unit, SVC valve should be in closed state
6.35 : 12.7 3.0m -When welding, service valve shoud be wrapped by wet cloth. 9.52 : 15.88 3.0m
Room 3
Room 4
Pin(Open) Open State
Room 2
Room 1
Model Name
Length
Quantity
PHDHA05T
500mm
30EA
PHDHA07T
700mm
30EA
PHDHA05B
500mm
5EA
PHDHA07B
700mm
5EA
Piping Accessories
• In case of installation of additional indoor unit, refrigerant of used indoor unit must be discharged. (Room 3 & Room 4) • If stopper valve is already installed, you can install additional indoor unit without refrigerant loss from the entire system. • After installation of additional indoor unit, you just need refrigerant charging for “A” section. In case of the installation of additional Cut inlet side of the connector, and weld • Then, open the Stopper Valve. the pipe indoor unit, outlet side connector should
Solution
LG
234
235
COMPATIBILITY TABLE : Compatibility is available
: Wired remote controller is required
Controller Product
Premium
PREMTA000 PREMTA000A PREMTA000B
Standard ll
PREMTBB01
PREMTB001
: Compatibility is available but more detailed functions refer to “MULTI V INDOOR UNIT LINE UP & FEATURES OVERVIEW”. (Page 96 ~ 97)
Simple
PQRCVCLOQ
PQRCVC0QW
Simple for Hotel
Dry Contact
Wireless
PQRCHCA0Q PQRCHCA0QW PQWRHQ0FDB
Wi-Fi
Simple Dry Contact PDRYCB000
2 points Dry Contact PDRYCB400
Dry Contact for Thermostat PDRYCB300
For Modbus PDRYCB500
LG-IR-WF-1
ARNU-C4
•
•
•
•
•
•
•
•
ARNU-C4
•
•
•
•
•
•
•
•
ARNU-A4
•
•
•
•
•
•
•
ARNU-A4
•
•
•
•
•
•
•
• •
• •
• •
• •
• •
• •
• •
•
•
•
•
•
•
•
•
• • • •
• • • • • •
• • • • • •
• • • • • •
• • • • • •
• • • • • •
• • • • • •
• • • • • •
x
x
x
x
x
x
x
x
• •
• •
• •
4 Way
2 Way / 1 Way
ACCESSORIES
Ceiling Mounted Cassette
X : Compatibility is unavailable
MEMO
High Sensible
Ceiling Concealed Duct
High Statics Mid Statics Low Statics
ARNU-G4
ARNU-G4
MULTI V
Built-in ARNU-Z4
Convertible & Ceiling Suspended Unit
ARNU-A2
Console
ARNU-A4
Floor Standing Unit
ARNU-A4 ARNU-U4 ARNU-A4 ARNU-*4 1)
Wall Mounted Unit
• • • • •
ARNU-L4 ARNU-A4
• • • • • •
HYDRO KIT 2)
Ventilation
Energy Recovery Ventilator Energy Recovery Ventilator with DX coil
AHU Communication Kit 1) Artcool Mirror : Mirror (R) / Silver (V) / White (W) 2) It has a separate remote controller
• • •
• • •
x
x
x
x
x
x
•
•
• • • •
x x
Compatibility Table
FAU (Fresh Air intake Unit)
MEMO