Advance grp series interlock socket

Page 1

ADVANCE GRP Series 125A Switched Interlocked socket outlets


ADVANCE GRP Series 125A > SWITCHED INTERLOCKED SOCKET OUTLETS

> REFERENCE STANDARDS

EN 60309-1 Plugs, socket outlets and couples for industrial purposes. Part 1: general requirements.

EN 60309-2 Plugs, socket outlets and couples for industrial purposes. Part 2: dimensional interchangeability requirements for pin and contact-tube accessories of harmonised configurations.

EN 60309-4 Plugs, socket-outlets and couplers for industrial purposes. Part 4: Switched socket-outlets and connectors with or without interlock.

> VERSIONS WITH MECHANICAL INTERLOCK With switch-disconnector

IEC 61241-0 / EN 61241-0 Electrical apparatus for use in the presence of combustible dust. Part 0: General requirements.

With switch-disconnector and fuse

IEC 61241-1 / EN 61241-1 Electrical apparatus for use in the presence of combustible dust. Part 1: Protection by enclosures 'tD'.

With fuse and switch

> PRODUCTS FOR USE IN A POTENTIALY EXPLOSIVE ENVIRONMENT With molded case circuit breaker with thermal magnetic trip unit

With molded case circuit breaker with thermal magnetic and residual current release trip units

> VERSIONS WITH ELECTRICAL INTERLOCK With contactor

2

Scame offers products suitable for installation into environments under potential risk of explosion identified as Zone 22 and that enter into the field of application for the ATEX Directive (European Directive 94/9/CE).


Saline solution

Resistant

Bases

Acids

Solvents

Concentrated

Diluted

Concentrated

Diluted

Hexane

Benzol

Acetone

Alcohol

Limited Resistance

Resistant

Not Resistant

Resistant

Limited Resistance

Limited Resistance

Limited Resistance

Limited Resistance

Mineral oil

UV rays

Resistant

Resistant

ADVANCE GRP Series 125A

> BEHAVIOUR WITH CHEMICAL AND ATMOSPHERIC AGENTS

For specific substances please contact our technical service

> TECHNICAL CHARACTERISTICS Rated current: Rated voltage: Frequency: Insulating voltage: Protection degree: Operating temperature according to the reference standard: Max. operating temperature: Self-extinguishing GW test: Self-extinguishing UL94: Material: IK degree at 20°C: Cable inlets:

125A 100÷690V~ 50÷60Hz 500/690V~ IP66

-25°C+40°C

60°C 850°C/960°C V0 Thermoset IK10 Top side max 3xM63 Bottom side max 2xM63 Switch-disconnectors: ABB OT 160 Fuse: NH00 Thermal magnetic protection: Molded case circuit breaker ABB Tmax T1B (16kA) with thermal magnetic trip unit TMD (adjustable thermal threshold 0,7…1 x In fixed magnetic threshold 10 x In) Thermal-magnetic and Molded case circuit breaker residual current protection: ABB Tmax T1B (16kA) with thermal magnetic trip unit TMD (adjustable thermal threshold 0,7…1 x In fixed magnetic threshold 10 x In) + residual current release trip units RC221/1 (adjustable residual current trip 0,03 - 0,1 - 3A and time limit for non-trip instantaneous) Version with contactor: Contactor CL09 GE POWER CONTROL Colour: Grey RAL7037

> EX CLASSIFICATION Atex Code: II 3D Ex Protection type: Ex tD A22 IP66 T90°C Operating Temperature Range: -25°C +60°C Maximum permissible surface temperature: T90°C Switched socket outlets with interlock degree of Protection: IP66 Plugs - degree of Protection: IP66/IP67 Impact Resistance: 7J Switched socket outlets with interlock material: Thermoset Plugs material: Thermoplastic Interlocked switch sockets outlets CE certificate: SCAME ATEX 02 Plugs CE certificate: SCAME ATEX 03

Via Costa Erta 15 Parre BG ITALY

3P+N+

- 125A - 6h / 346-415V~

Cod. 503.12587-F SCAME ATEX 02 Ex tD A22 IP66 T90°C

II 3D

DO NOT OPEN WHEN ENERGIZED IN PRESENCE OF EXPLOSIVE ATMOSPHERE

> WIRING OPERATIONS Wiring capacity of the terminals (mm2) Socket outlets

Plugs

Rated current (A)

Min

Max

Min

Max

125A

25

70

16

50

3


ADVANCE GRP Series 125A > APPLICATION EXAMPLES

4


ADVANCE GRP Series 125A

> TECHNICAL DATA SWITCH DISCONNECTORS

125A Vac

750

Vdc

750

Rated impulse withstand voltage Uimp

kV

12

Thermal current Ith

A

200

Thermal current Ithe

A

-

400V

A

200

500V

A

-

690V

A

160

400V

A

200

500V

A

-

690V

A

160

400V

A

135

500V

A

125

690V

A

80

400V

A

-

690V

A

-

300V

A

160(*)

250V

A

160(*)

600V

A

-

A

4000

kA

24

kA

30

kA

1200

600V

A

125

120V

Hp

7,5

240V

Hp

20

240V 480V 600V

Hp Hp Hp

40 75 100

Rated insulation voltage Ui

AC21A Resistite loads, inluding moderate overloads

Nominal current rating Ie

Mixed resistite and inductive loads, AC22A including moderate overloads

Switching off motor loads or other AC23A highly inductive loads (3 phase/3 pole)

AC3

Squirrel-cage motor: starting, switching off motor during running (3 phase/ 3 pole)

DC21A

Resistite loads, including Moderate overloads

DC22A

Mixed resistite and inductive loads, including moderate overloads

Short-circuit protection

Rated short-time withstand current Icw (s)

Conditional short-circuit current Associate fuse size for conditional short-circuit current - Type gG Rated short-circuit making capacity Icm

Rated current UL

General applications - Single-phase and Three-phase

AC motor, all-pole interruption - Single-phase

AC motor, B, C, D, all-pole interruption - Three-phase Permissible wire range

500V

mm2

10-70

AWG

8-1/10

Wire

(*) 2+2 poles in series

5


ADVANCE GRP Series 125A

Outdoor wall fastening

Ample space for easy wiring

Under-plate cable runway Switchdisconnector with mechanical lock that can be accessorized with auxiliary contacts

Threaded metal inserts

Punched marks for easy closure of the cover Easily extractable bottom plate

Possibility to assemble microswitch

BOTTOM VIEW

TOP VIEW

Module in hightemperature glassfibre filled engineering polymer

Possible entry from bottom side (input-output also)

6

Self-centering punch marks to facilitate drilling


ADVANCE GRP Series 125A

Single-piece waterproof gasket

Rating on metal plate

Captive stainless steel closing screws

Lockable Switch in position 0 and 1

High-strength material with superior UV and chemical resistance

Double mechanical lock and metal levers

Residual current release trip units test push button

Cover entirely separate from the base for easy installation

An electronic device controls the status of the interlocked socket, monitoring the electrical functionality: - operation of the signalling and control card is guaranteed even when the load is not connected; - indicates that the fuses are not open and all the phases are present (indicator light on); - indicates that the socket outlet is powered correctly (indicator light on); - signals the interruption of one or more fuses (indicator light flashing); - signals the absence of a phase (indicator light flashing)*; - indicates that the socket outlet is not powered (indicator light off). * for single-phase products in the event of phase/ neutral loss LED signaling appears off.

7


ADVANCE GRP Series 125A > MECHANICALLY INTERLOCKED SOCKET OUTLETS - IP66

Description

Switchdisconnector

Description

Switchdisconnector and fuse (*)

Description

Fuse (*) and switch

Description

Plug

Volt

2P+E 125A

50/60

200-250V

6

1

503.12583

3P+E 125A

50/60

380-415V

6

1

503.12586

3P+N+E 125A 50/60

346-415V

6

1

503.12587

Hz

Volt

2P+E 125A

50/60

200-205V

6

1

503.12583-F

3P+E 125A

50/60

380-415V

6

1

503.12586-F

3P+N+E 125A 50/60

346-415V

6

1

503.12587-F

Plug

2P+E 125A

50/60

200-205V

6

1

503.12583-FS

3P+E 125A

50/60

380-415V

6

1

503.12586-FS

3P+N+E 125A 50/60

346-415V

6

1

503.12587-FS

Plug

Hz

Plug

Hz

(*) Fuses not included

Volt

Colour

h

Volt

Molded case 2P+E 125A 50/60 circuit breaker with thermal magnetic 3P+E 125A 50/60 and residual current release trip units 3P+N+E 125A 50/60

8

Colour

Hz

Plug

Molded case 2P+E 125A 50/60 circuit breaker 3P+E 125A 50/60 with thermal magnetic trip unit 3P+N+E 125A 50/60

Description

Colour

h

Hz

Colour

h

h

200-205V

6

1

503.12583-M

380-415V

6

1

503.12586-M

346-415V

6

1

503.12587-M

Volt

Colour

h

200-205V

6

1

503.12583-RM

380-415V

6

1

503.12586-RM

346-415V

6

1

503.12587-RM Pack Quantity.


Description

Contactor (*)

Hz

Volt

2P+E 125A

50/60

200-205V

6

1

503.12583-T

3P+E 125A

50/60

380-415V

6

1

503.12586-T

3P+N+E 125A 50/60

346-415V

6

1

503.12587-T

Plug

Colour

ADVANCE GRP Series 125A

> ELECTRICALLY INTERLOCKED SOCKET OUTLETS - IP66

h

(*) Microswitch already provided. Contactor operated by microswitch.

> ACCESSORIES

Description

Terminals

Contacts

Microswitch kit 400V 10A 1NO+1NC (microswitch + terminal block)

4x4 mm2

579.0125

For products with mechanical interlock.

> COMPLEMENTARY PRODUCTS - OPTIMA-EX SERIES - PLUGS IP66/IP67

Description

Plugs

Plug

Hz

Volt

Colour

h

2P+E 125A

50/60

200-250V

6

1

218.EX12533

3P+E 125A

50/60

380-415V

6

1

218.EX12536

3P+N+E 125A 50/60

346-415V

6

1

218.EX12537

9


ADVANCE GRP Series 125A > DIMENSIONS

(Dimensions in mm)

10


Switch-disconnector and fuse

Fuse and switch

Molded case circuit breaker with thermal magnetic trip unit

Molded case circuit breaker with thermal magnetic and residual current release trip units

Contactor

ADVANCE GRP Series 125A

Switch-disconnector

(Dimensions in mm)

11


ZP00738-GB-2

ScameOnLine www.scame.com export@scame.com SCAME PARRE S.p.A. VIA COSTA ERTA, 15 24020 PARRE (BG) ITALY TEL. +39 035 705000 FAX +39 035 703122


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.