Lot 14 Display Home

Page 1

Date

Issued By

A

DA Issue

19/11/2012

NS

B

HRD Issue

20/12/2012

MS

C

HRD Issue

08/01/2013

MS

HRD Issue (missing window tag) 21/01/2013

MS

D E

Rvised DA Issue

24/01/2013

MS

F

Rvised DA Issue 2

01/02/2013

MS

G

CC Issue

11/02/2013

MS

H

Construction Issue

12/02/2013

MS

1 0 A V a l e d i c t i o n R o a d K i n g s P a r k N S W 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . a u Client:

Ichijo Technological Homes

Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155 Dwg No.

Contents

001 002 004 100 102 200 201 202 300 301 400 401 500 501 502 503 508 600 601 602 603 604 605 606 607 608

COVER SHEET GENERAL NOTES WINDOW & DOOR SCHEDULE SITE PLAN CONCEPT DRAINAGE PLAN GROUND FLOOR PLAN SLAB LAYOUT PLAN GROUND FLOOR / ELECTRICAL/DATA LAYOUT SOUTH & WEST ELEVATIONS NORTH & EAST ELEVATIONS SECTIONS AA & BB SECTIONS CC & DD KITCHEN DETAILS LAUNDRY DETAILS & SALES OFFICE KITCHENETTE BATHROOM DETAILS ENSUITE DETAILS BUTLER'S KITCHEN CONSTRUCTION DETAILS CONSTRUCTION DETAILS CONSTRUCTION DETAILS CONSTRUCTION DETAILS CONSTRUCTION DETAILS CONSTRUCTION DETAILS CONSTRUCTION DETAILS CONSTRUCTION DETAILS CONSTRUCTION DETAILS

Scale: Design: COPYRIGHT All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia PTY LTD will result in legal proceeding

Note: Ichijo (Aus) Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Note: All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

NTS @A3

OASIS 26

Council:

Council

HRD No:

N010014-2012

Job No:

D000005

Drawn By:

MS

Drawing No:

DISPLAY(L) CON - 001

Date:

11/02/2013

Facade:

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

Current Revision Description

Revision No


BCA COMPLIANCE

ALL WORK TO BE CARRIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PRINCIPAL CERTIFYING AUTHORITY [PCA] AND THE BUILDING CODE OF AUSTRALIA [BCA] - AS AMENDED.

TERMITE PROTECTION NOTE

BUILDING CODE OF AUSTRALIA BUILDING CLASSIFICATION: 1

TERMGARD RETICULATION SYSTEM TO SLAB PERIMETER

SECTION A GENERAL PROVISIONS VOL. 2 PART 1.3, CLAUSE 1.3.2 CLASSIFICATIONS:

REMOVAL OF ASBESTOS CEMENT SHEETING MUST BE CARRIED OUT BY A LICENSED CONTRACTOR IN COMPLIANCE WITH THE REQUIREMENTS OF THE NSW WORKCOVER AUTHORITY IN RELATION TO THE REMOVAL, HANDLING AND DISPOSAL OF ALL MATERIAL CONTAINING ASBESTOS; AND THE WORK SAFE AUSTRALIA ASBESTOS CODE OF PRACTICE AND GUIDANCE NOTES. ALL DEMOLITION WORK TO BE CARRIED OUT IN ACCORDANCE WITH AS2601 - AS CURRENTLY AMENDED. BUILDER SHALL MAKE GOOD ALL DISTURBED AREAS ADJACENT TO THE WORKS ON COUNCIL'S ROADS. FOOTPATHS ARE TO BE RESTORED TO THE SATISFACTION OF THE BCA. ALL CONCRETE FOOTINGS, FLOOR SLABS, COLUMNS AND TIMBER ROOF FRAMING TO STRUCTURAL ENGINEER'S DETAILS. ALL STORMWATER REQUIREMENTS, EXTERNAL AND DRIVEWAY LEVELS TO HYDRAULIC ENGINEER'S DETAILS.

ONE OR MORE BUILDINGS WHICH IN ASSOCIATION CONSTITUTE (A) CLASS 1A - A SINGLE DWELLING, BEING (I) A DETACHED HOUSE, OR (II) ONE OR MORE ATTACHED DWELLINGS, EACH BEING A BUILDING, SEPARATED BY A FIRE-RESISTING WALL, INCLUDING A ROW HOUSE, TERRACE HOUSE, TOWN HOUSE OR VILLA UNIT; CLASS 10: A NON-HABITABLE BUILDING BEING A PRIVATE GARAGE, CARPORT, SHED, OR THE LIKE. SECTION C FIRE SEPARATION PART 3.7.1 FIRE SEPARATION 3.7.1.1 APPLICATION COMPLIANCE WITH THIS PART SATISFIES PERFORMANCE REQUIREMENT P2.3.1 FOR FIRE SEPARATION. 3.7.1.2

ALL LANDSCAPED AREAS, EXISTING TREES, DRIVEWAY, DRYING YARDS AND FENCING TO LANDSCAPE ARCHITECT'S DETAILS. DRAWINGS ARE TO BE READ IN CONJUNCTION WITH SPECIFICATIONS. ALL STAIR TREADS ARE TO BE EQUAL TO 250MM DEEP. ALL MATERIALS AND COMPONENTS SHALL COMPLY WITH THE EARLY HAZARD INDICES REQUIREMENTS OF BCA SPEC. CLAUSE 1.10. ALL ASPECTS OF THE BUILDING WORK SHALL COMPLY WITH THE RELEVANT CURRENT PROVISIONS OF THE LOCAL GOVERNMENT REGULATIONS AND THE BUILDING CODE OF AUSTRALIA. SILT/SEDIMENT CONTROL MEASURES ARE TO BE IN PLACE PRIOR TO ANY EXCAVATION OR CONSTRUCTION WORK. SAFETY GLASS SHALL BE USED IN EVERY GLASS DOOR OR PANEL ENCLOSING OR PARTLY ENCLOSING A SHOWER OR BATH.

3.7.1.3

ALL BATHROOMS AND WC WINDOWS TO BE INSTALLED WITH OBSCURE GLASS. UNLESS THE DOOR IN A SANITARY COMPARTMENT SWINGS OUTWARD OR IS GREATER THAN 1.2M AWAY FROM THE TOILET SUITE, THE DOOR MUST BE INSTALLED WITH REMOVABLE 'LIFT-OFF' HINGES. THE REFLECTIVITY INDEX OF ALL EXTERNAL GLASS MATERIALS IS NOT TO EXCEED 20%.

3.7.1.5

CLASS 1:

3.7.1.4

PROTECTIVE MEASURES ARE REQUIRED FOR EACH TREE BEING RETAINED ON SITE AND SHALL BE ESTABLISHED BEFORE BUILDING WORKS COMMENCE, AND SHALL BE CONSTRUCTED AND MAINTAINED AS PER COUNCIL REQUIREMENTS. PEDESTRIAN TRAFFIC AND USE OF BOUNDING PUBLIC FOOTPATHS, SPACE TO REMAIN UNCONSTRICTED [UNLESS SUBJECT TO SEPARATE COUNCIL APPROVAL], INCLUDING PRAM ACCESS - TO BE MAINTAINED IN ACCORDANCE WITH AS1742.3 "PART 3 - TRAFFIC CONTROL DEVICES FOR WORKS ON ROADS".

GENERAL CONCESSION - NON-COMBUSTIBLE MATERIALS THE FOLLOWING MATERIALS, THOUGH COMBUSTIBLE OR CONTAINING COMBUSTIBLE FIBTRES, MAY BE USED WHEREVER A NON-COMBUSTIBLE IS REQUIRED IN THE HOUSING PROVISIONS: (a) PLASTERBOARD, AND (b) PERFORATED GYPSUM LATH WITH A NORMAL PAPER FINISH, (c) FIBROUS-PLASTER SHEET, AND (d) FIBRE-REINFORCED CEMENT SHEETING, AND (e) PRE-FINISHED METAL SHEETING HAVING A COMBUSTIBLE SURFACE FINISH NOT EXCEEDING 1MM THICK AND WHERE THE SPREAD-OF-FLAME INDEX OF THE PRODUCT IS NOT MORE THAN 0; AND (f) BONDED LAMINATED MATERIALS, WHERE (i) EACH LAMINATE IS NON-COMBUSTIBLE; AND (ii) EACH ADHESIVE LAYER IS NOT MORE THAN 1MM THICK; AND (iii) THE TOTAL THICKNESS OF ADHESIVE LAYERS IS NOT MORE THAN 2MM; AND (iv) THE SPRED-OF-FLAME INDEX AND THE SMOKE-DEVELOPMENT INDEX OF THE LAMINATED MATERIAL AS A WHOLE DOES NOT EXCEED 0 AND 3 RESPECTIVELY. EXTERNAL WALLS OF CLASS 1 BUILDINGS AN EXTERNAL WALL OF A CLASS 1 BUILDING AND ANY OPENINGS IN THAT WALL MUST COMPLY WITH 3.7.1.5, IF THE WALL IS LESS THAN(a) 900MM FROM THE ALLOTMENT BOUNDARY OTHER THAN THE BOUNDARY ADJOINING A ROAD ALIGNMENT OR OTHER PUBLIC SPACE; OR (b) 1.8M FROM ANOTHER BUILDING ON THE SAME ALLOTMENT OTHER THAN APPURTENANT CLASS 10 BUILDING OR A DETACHED PART OF THE SAME CLASS 1 BUILDING. MEASUREMENT OF DISTANCES (a) THE DISTANCE FROM ANY POINT ON AN EXTERNAL WALL OF A BUILDING TO AN ALLOTMENT BOUNDARY OR ANOTHER BUILDING IS THE DISTANCE TO THAT POINT MEASURED ALONG A LINE AT RIGHT ANGLES FROM THE ALLOTMENT BOUNDARY OR EXTERNAL WALL OF THE OTHER BUILDING WHICH INTERSECTS THAT POINT WITHOUT OBSTRUCTION BY A WALL COMPLYING WITH 3.7.1.5. (b) WHERE A WALL WITHIN A SPECIFIED DISTANCE IS REQUIRED TO BE CONSTRUCTED IN A CERTAIN MANNER, ONLY THAT PART OF THE WALL, (INCLUDING ANY OPENINGS) WITHIN THE SPECIFIED DISTANCE, MUST BE CONSTRUCTED INTHAT MANNER.

3.7.1.8

CONSTRUCTION OF EXTERNAL WALLS (a) EXTERNAL WALLS (INCLUDING GABLES) REQUIRED TO BE FIRERESISTING [REFERRED TO IN 3.7.1.3 OR 3.7.1.6] MUST EXTEND TO THE UNDERSIDE OF A NON-COMBUSTIBLE ROOF COVERING OR NON-COMBUSTIBLE EAVES LINING, AND MUST(i) HAVE AN FRL OF NOT LESS THAN 60/60/60 WHEN TESTED FROM THE OUTSIDE; OR (ii) BE OF MASONRY-VENEER CONSTRUCTION IN WHICH THE EXTERNAL MASONRY VENEER IS NOT LESS THAN 90MM THICK; OR (iii) BE OF MASONRY CONSTRUCTION NOT LESS THAN 90MM THICK. (b) OPENINGS IN EXTERNAL WALLS REQUIRED TO BE FIRE-RESISTING [REFERRED TO IN 3.7.1.3 OR 3.7.1.6] MUST BE PROTECTED BY(i) NON-OPERABLE FIRE-WINDOWS OR OTHER CONSTRUCTION WITH AN FRL OF NOT LESS THAN --/60/-- OR (ii) SELF-CLOSING SOLID-CORE DOORS NOT LESS THAN 35MM THICK. (c) SUB-FLOOR VENTS, ROOF VENTS, WEEP HOLES AND PENETRATIONS FOR PIPES, CONDUITS AND THE LIKE NEED NOT COMPLY WITH (B) ABOVE. (d) CONCESSIONS FOR NON-HABITABLE ROOM WINDOWS, CONDUITS AND THE LIKE-DESPITE THE REQUIREMENTS IN (B), IN A NON-HABITABLE ROOM A WINDOW THAT FACES THE BOUNDARY OF AN ADJOINING ALLOTMENT MAY BE NOT LESS THAN 600MM FROM THAT BOUNDARY, OR, WHERE THE BUILDING FACES ANOTHER BUILDING ON THE SAME ALLOTMENT, NOT LESS THAN 1.2M FROM THAT BUILDING; PROVIDING THAT(i) IN A BATHROOM, LAUNDRY OR TOILET, THE OPENING HAS AN AREA OF NOT MORE THAN 1.2SQM; OR (ii) IN A ROOM OTHER THAN REFERRED TO IN (I), OPENING HAS AN AREA OF NOT MORE THAN 0.54SQM; AND(A) THE WINDOW IS STEEL-FRAMED, THERE ARE NO OPENING SASHES AND IT IS GLAZED IN WIRE GLASS; OR (B) THE OPENING IS ENCLOSED WITH HOLLOW GLASS BLOCKS. SEPARATING WALLS (a) A WALL THAT SEPARATES CLASS 1 DWELLINGS, OR SEPARATES A CLASS 1 BUILDING FROM A CLASS 10A BUILDING WHICH IS NOT APURTENANT TO THAT CLASS 1 BUILDING, MUST HAVE AN FRL OF NOT LESS THAN 60/60/60, AND(i) COMMENCE AT THE FOOTINGS OR GROUND SLAB; AND (ii) EXTEND(A) IF THE BUILDING HAS A NON-COMUSTIBLE ROOF COVERING, TO THE UNDERSIDE OF THE ROOF COVERING; OR (B) IF THE BUILDING HAS A COMBUSTIBLE ROOF COVERING, TO NOT LESS THAN 450MM ABOVE THE ROOF COVERING.

SPECIFICATION C1.10 FIRE HAZARD PROPERTIES MATERIALS USED IN THE BUILDING HAVING FLAMABILITY, SMOKE DEVELOPED AND SPREAD-OF-FLAME INDICES AS SET-OUT IN SPEC. C1.10. SECTION F HEALTH AND AMENITY PART F1: DAMP AND WEATHERPROOFING - STORMWATER DRAINAGE MUST COMPLY WITH AS/NZS 3500.3.2 - ROOF COVERING TO COMPLY WITH F1.5 - SARKING MUST COMPLY WITH AS/NZS 4200, PARTS 1 AND 2 - WATER PROOFING OF WET AREAS IN BUILDINGS TO COMPLY WITH F1.7 - DAMP-PROOFING OF FLOORS ON GROUND TO COMPLY WITH F1.11

PART F3.7: FIRE SAFETY - AUTOMATIC FIRE DETECTION SYSTEM TO BE PROVIDED IN ACCORDANCE WITH PART 3.7.2 GENERAL CONCESSION: PART 3.7.2: SMOKE ALARMS - REQUIREMENTS FOR SMOKE ALARMS: (a) SMOKE ALARMS MUST BE INSTALLED IN: (i) ANY STOREY CONTAINING BEDROOMS. PART 3.8: HEALTH AND AMENITY - WET AREAS WITHIN THE BUILDING MUST COMPLY WITH THE REQUIREMENTS OF PART 3.8.1 WET AREAS. PART 3.8.6: SOUND INSULATION REQUIREMENTS 3.8.6.1 APPLICATION - COMPLIANCE WITH THIS PART SATISFIES PERFORMANCE REQUIREMENT P2.4.6 FOR SOUND INSULATION. 3.8.6.2 SOUND INSULATION REQUIREMENTS (a) TO PROVIDE INSULATION FROM AIR-BORN AND IMPACT SOUND, A SEPARATING WALL BETWEEN TWO OR MORE CLASS 1 BUILDINGS, MUST(i) ACHIEVE THE WEIGHTED SOUND REDUCTION WITH SPECTRUM ADAPTION TERM [RW+CTR] AND DISCONTINUOUS CONSTRUCTION REQUIREMENTS, AS REQUIRED BY TABLE 3.8.6.1; AND (ii) BE INSTALLED IN ACCORDANCE WITH THE APPROPRIATE REQUIREMENTS OF 3.8.6.3 AND 3.8.6.4. (b) FOR THE PURPOSE OF THIS PART, THE RW+CTR MUST BE DETERMINED IN ACCORDANCE WITH AS/NZS 1276.2 OR ISO 717.1, USING RESULTS FROM LABORATORY MEASUREMENTS. PART 3.9: SAFE MOVEMENT AND ACCESS - THE TREADS AND RISERS OF THE PROPOSED STAIRS ARE TO COMPLY WITH PART 3.9.1.2 GENERAL REQUIREMENTS.

SEDIMENT CONTROL NOTES 1. ALL EROSION AND SEDIMENTATION CONTROL MEASURES, INCLUDING REVEGETATION AND STORAGE OF SOIL AND TOPSOIL, SHALL BE IMPLEMENTED TO THE STANDARDS OF THE SOIL CONSERVATION OF NSW AND INSPECTED DAILY BY THE SITE MANAGER.

AUSTRALIAN STANDARDS COMPLIANCE THE BUILDING WORKS SHALL BE CONSTRUCTED IN ACCORDANCE WITH, BUT NOT LIMITED TO THE FOLLOWING AUSTRALIAN STANDARDS: AS/NZS 1664

ALUMINIUM STRUCTURES

AS/NZS 1905

COMPONENTS FOR THE PROTECTION OF OPENINGS IN FIRE RESISTANT WALLS

AS 2050

INSTALLATION OF ROOF TILES

AS 2047

WINDOWS IN BUILDINGS - SELECTION AND INSTALLATION

AS 2327

COMPOSITE STRUCTURES

AS 2870

RESIDENTIAL SLABS AND FOOTING CONSTRUCTION

AS 1684

RESIDENTIAL TIMBER-FRAMED CONSTRUCTION

AS 3700

MASONRY STRUCTURES

AS 3013

ELECTRICAL INSTALLATIONS

2. ALL DRAINAGE WORKS SHALL BE CONSTRUCTED AND STABILIZED AS EARLY AS POSSIBLE DURING DEVELOPMENT.

AS 1668

THE USE OF MECHANICAL VENTILATION AND AIR-CONDITIONING IN BUILDINGS

3. SEDIMENT TRAPS SHALL BE CONSTRUCTED AROUND ALL INLET PITS, CONSISTING OF 300mm WIDE x 300mm DEEP TRENCH.

AS 2441

INSTALLATION OF HOSE REELS

AS 2444

PORTABLE FIRE EXTINGUISHERS AND FIRE BLANKETS - SELECTION AND LOCATION

4. ALL SEDIMENT BASINS AND TRAPS SHALL BE CLEANED WHEN THE STRUCTURES ARE A MAXIMUM OF 60% FULL OF SOIL MATERIALS, INCLUDING THE MAINTENANCE PERIOD.

AS 3786

SMOKE ALARMS

5. ALL DISTURBED AREAS SHALL BE REVEGITATED AS SOON AS THE RELEVANT WORKS ARE COMPLETED.

AS 1288

GLASS IN BUILDINGS - SELECTION AND INSTALLATION

6. SOIL AND TOPSOIL STOCKPILES SHALL BE LOCATED AWAY FROM DRAINAGE LINES AND AREA WHERE WATER MAY CONCENTRATE. ALL ROADS AND FOOTPATHS TO BE SWEPT DAILY.

AS 2107

ACOUSTICS - RECOMMENDED DESIGN SOUND LEVELS AND REVERBERATION TIMES FOR BUILDING

7. FILTER SHALL BE CONSTRUCTED BY STRETCHING A FILTER FABRIC (PROPEX OR APPROVED EQUIVALENT BETWEEN POST AT 3.0m CENTRES. FABRIC SHALL BE BURIED 150mm ALONG ITS LOWER EDGE.

AS 3660.1 -2000

INTERIORS TERMITE MANAGEMENT NEW BUILDING WORK

8. DUST PREVENTION MEASURES TO BE MAINTAINED AT ALL TIMES.

AS/NZS 2890.1 -2004

OFF-STREET PARKING

BASIX CHECKLIST BASIX CERTIFICATE NUMBER : 460457S_04 WATER COMMITMENTS

FIXTURES

ALTERNATIVE WATER

SIMULATION METHOD

INSTALL SHOWERHEADS WITH A MINIMUM RATING OF 3 STARS IN ALL SHOWERS

INSTALL A TOILET FLUSHING SYSTEM WITH A MINIMUM RATING OF 4 STARS IN EACH TOILET

INSTALL TAPS WITH A MINIMUM RATING OF 4 STARS IN THE KITCHEN

INSTALL BASIN TAPS WITH A MINIMUM RATING OF 4 STARS IN EACH BATHROOM

THE APPLICANT MUST INSTALL 9000LT RAINWATER TANK ON THE SITE

CONNECT THE RAINWATER TANK TO THE COLD WATER TAP OF EACH CLOTHES WASHING LINE AND ATLEAST 1 OUTDOOR TAP.

THE APPLICANT MUST MAKE PROVISION TO CONNECT THE DEVELOPMENT TO THE ROUSE HILL RETICULATE ALTERNATIVE WATER SUPPLY SYSTEM.THIS CONNECTION MUST MEET THE REQUIREMENTS OF ALL APPLICATION REGULATORY AUTHORITIES THE APPLICANT MUST MAKE PROVISION TO CONNECT THE RETICULATE ALTERNATIVE WATER SUPPLY SYSTEM TO ALL TOILETS IN THE DEVELOPMENT

VENTILATION

ACTIVE COOLING & HEATING

√ √

NATURAL LIGHTING ALTERNATIVE ENERGY OTHER

FOLLOWING HOT WATER SYSTEM MUST BE INSTALLED: SOLAR (GAS BOOSTED) WITH A PERFORMANCE OF 31 TO 35 RECs OR BETTER.

THE APPLICANT MUST INSTALL THE FOLLOWING HEATING/ COOLING SYSTEM, OR A SYSTEM WITH A EQUAL OR HIGHER ENERGY RATING OF 3.5 STAR, IN AT LEAST 1 LIVING/ 1 BEDROOM: AIRCONDITIONING

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

INDIVIDUAL FAN, DUCTED TO FACADE OR ROOF WITH MANUAL ON/OFF SWITCH TO BE INSTALLED IN THE LAUNDRY

ARTIFICIAL LIGHTING

ENERGY HOT WATER

INDIVIDUAL FAN, DUCTED TO FACADE OR ROOF WITH MANUAL ON/OFF SWITCH TO BE INSTALLED IN THE KITCHEN

PRIMARY TYPE OF ARTIFICIAL LIGHTING IS TO BE FLUORESCENT OR LIGHT EMITTING DIODE (LED) IN EACH OF THE FOLLOWING ROOMS: • AT LEAST 4 BEDROOMS/ STUDY; DEDICATED • ALL HALLWAYS; DEDICATED

THERMAL COMFORT DWELLING IS TO BE CONSTRUCTED IN ACCORDANCE WITH ALL THERMAL PERFORMANCE SPECIFICATIONS SET OUT IN THE ASSESSOR CERTIFICATE

INDIVIDUAL FAN, DUCTED TO FACADE OR ROOF WITH MANUAL ON/OFF SWITCH TO BE INSTALLED IN AT LEAST 1 BATHROOM

• AT LEAST 2 LIVING/ DINING ROOMS; DEDICATED

• THE KITCHEN; DEDICATED

• ALL BATHROOMS/ TOILETS; DEDICATED

• THE LAUNDRY; DEDICATED

AT LEAST 1 WINDOW AND/ OR SKYLIGHT TO BE IN 2 BATHROOM(S)/ TOILET(S) FOR NATURAL LIGHT

THE APPLICANT MUST INSTALL A PHOTOVOLTAIC SYSTEM WITH THE CAPACITY TO GENERATE AT LEAST 1.44 PEAK KILOWATTS OF ELECTRICITY AS PART OF THE DEVELOPMENT. THE APPLICANT MUST CONNECT THIS SYSTEM TO THE DEVELOPMENT 'S ELECTRICAL SYSTEM.

• GAS COOKTOP & ELECTRICAL OVEN TO BE INSTALLED

COMMENTS

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

NTS @A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(L)

Job No:

D000005

Drawing No: Date:

CON - 002 11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

GENERAL NOTES


W01 W02 W03 W04 W05 W06 W07 W08 W09 W10 W11 W12 W13 W14

J8615T+2009 JK2460+314 JK2030UL(B)+1230 JK2030UR(B)+1230 J5945+774 J5945+774 J5945+774 JK2045R+774 JK2045R+774 J8660T+308 JK2042U(B)+961 JK2042U(B)+961 JK2060+314 J8615T+2009

469 1824 908 908 1364 1364 1364 1364 1364 1830 1177 1177 1824 469

2489 745 602 602 1655 1655 1655 602 602 2489 602 602 602 2489

2478 2138 2138 2138 2138 2138 2138 2138 2138 2138 2138 2138 2138 2478

R2 GLASSWOOL INSULATION BUILDING WRAP

BED 1 BED 1 BATH BATH BED 4 BED 3 BED 2 FAMILY FAMILY LIVING ENS. ENS. BED 1 BED 1

HEBEL POWERPANEL 90mm TIMBER FRAME APPLIED FINISH

140x38 REVEAL FRAME BY HRD

WATERPROOF SEAL UNDER WINDOW

140x38 REVEAL FRAME BY HRD HEBEL POWERPANEL SILL APPROX 12° SLOPE, 20mm OVERHANG AT BOTTOM

Door No.

DOOR SCHEDULE ICHIJO Door Code Height Width

BUILDING WRAP ACRYLIC COATING AS SELECTED

Location

R2 GLASSWOOL INSULATION

D01 D02 D03 D04 D05 D06

Solid flush 1200x 2340 Solid flush 820 x 2040 J11970T J8370 J11970T JK3570AR

2280 2040 2138 2138 2138 2138

1200 820 3399 2235 3399 902

ENTRY TEMPORARY SALES OFFICE FAMILY DINING DINING L'DRY

1

Window Head & Sill_Hebel panel 1 : 10

NOTE : ALLOW ADDITIONAL 45mm TO PERIMETER OF NOTED WINDOW OPENING SIZES.

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:50 @A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(R)

Job No:

D000005

Drawing No:

CON - 004

Date:

11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

WINDOW SCHEDULE Window No. ICHIJO Window Code Height Width Head Height Location


RAINWATER TANK

54.87 E

7 S

SF o

E

L FS

SF

DP

o

.0 55

1

E

SV HY D

o

o

LP

Lot 14 Gormon Avenue, Kellyville, NSW 2155

7

Design: Facade:

S

TEMP. TOILET

RTASS

SET OUT POINT

55.08

55 RN C

- EXTENT OF EXCAVATION TO BE DETERMINED ONSITE. - BACKFILL TO BE AGAINST FOOT OF SLAB. - WATER CONNECTION TO EXISTING PRE LAID WATER SERVICE. - SEWER CONNECTION TO AUTHORITIES REQUIREMENTS. - ALL RETAINING WALLS BY OWNER UNLESS PART OF THE FINAL CONTRACT. - OWNER TO ARRANGE DEMOLITION OF ANY TREES, STUMP, CONCRETE PATHS ETC. THAT ARE WITHIN THE BUILDING PLATFORM UNLESS PART OF THE FINAL CONTRACT.

55.05

4.5 M FRONT SETBACK

7 55 .5 55 .5

Drawn By:

RW

Ichijo Technological Homes

SITE ACCESS .05 55 RN GATE C

RW

Scale:

T

STOCK PILE

TREES TO BE REMOVED

RW

METER BOX & GAS METER LOCATION

5.5 M FRONT SETBACK

3500

RAINWATER TANK CONTROL UNIT LOCATION

S

6.79

.15 55 SF

+ TOW 55.354

RE CT AP

o

1850

G.T

4.98

23 EASEMENT FOR SUPPORT 0.8 WIDE

5.04 296°07'50"

4 55 .5 0

56 .6 FS 5 L

55 .6

SF

RW RW

55 FS .75 L

SF

o

SITE SEDIMENT FENCE

TEMP. TOILET LOCATION CONSTRUCTION FENCE LOCATION STOCK PILE LOCATION

10000L RAINWATER TANK BELOW GROUND .03

RW

SF

RAINWATER CONTROL UNIT LOCATION

S

RW

o

RW

55.97 FSL

RW

2

RW

SF

S

GAS METER LOCATION METER BOX LOCATION

RWC

RW

SETBACK

RW

56 .7

RW

1000

RW

Note:

o

E

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

SF

Client:

Address:

RW

+ TOW 55.74

55 TE .77 MP SL

55 TE .69 MP SL

FS 56. L 63

RW

E

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

o

S

Note:

SF

NGL = 55.520 (+ / - 100mm) FGL = 55.370

1 : 200

Note:

o

TAP (CONNECTED TO RAINWATER TANK)

o

SITE PLAN

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

SF

APPROXIMATE LOCATION OF SEWER MAIN

S

-

30.49 31° 51' 50"

o

S

o

SF

LOT 15

CONSTRUCTION FENCE LOCATION o

o

S

SITE SEDIMENT FENCE LOCATION SF SF SF

SF

7

MB

GAS HOT WATER SYSTEM LOCATION

EXCAVATION & SITE NOTES:

o

SF

o

.00 55 RN C

ALL WEATHER SITE ACCESS

E

o

S

SF

o

GAS

TREES TO BE RETAINED

E

o o

SF

SOLAR GAS BOOSTED WATER HEATER

o

HWS

E

o

S

NGL = 55.895 (+ / - 100mm) FGL = 55.445

o

55

E

o

S

DP o

.9 54

E

o

SF

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

o

(J)

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

DRIVEWAY

55.75

o

COPYRIGHT

S

GARAGE FGL = 55.370

(A)

500mm CUT & FILL YES 500mm CUT & 500mm FILL

o

RL +55.805

o

CONSTRUCTION FENCE

S

o

S

RL +55.880

FGL = 55.445

12 PROPOSED LOW LEVEL RETAINING WALL

PORCH RL +55.805

PROPOSED RESIDENCE

DP o

TEMP. END

o

L FS .73 55

BATTER TO FILL

.98 54 N CR

E

LOT 14 660.8m²

S

3.25 PRIVATE OPEN SPACE REQUIRED : 6.0m x 4.0m OR 24.00 m² YES PROPOSED : 24.00 m²

o

SF

N/A

INV 56.13

o

T

(J) A/C UNIT

YES

.12 55 o L FS

S

N EXISTING RETAINING WALL

N

FILL

S

1.44 KW PV SOLAR SYSTEM

3.24 LANDSCAPE AREA (ENTIRE) MIN. REQ. : 35% OR 231.28 m² YES PROPOSED : 51% OR 338.53 m²

3500

E

DP

o

E

NGL = 55.888 (+ / - 100mm) FGL = 55.445

4530 6SETBACK 5.9

5 L FS

0.00 m 0.00 m N/A 0.00 m

.34 55 FSL

SF SF

3.17 REAR SETBACK MIN. SINGLE STOREY REAR SETBACK REQ. : 4.00 m PROPOSED SIDE SETBACK: 4.53 m

NGL = 55.425 (+ / - 100mm) FGL = 55.445

o

E

YES

3.0 m YES 3.798 m

4500

L FS .69 55

BATTER TO CUT

2

E

13

FGL = 55.370

E

SF

.9 54

W RRW

o

S

LEGEND

EXHIBITION SIGN 800h x 2000w 55.00

.2 55

ADDITIONAL EASEMENT - N/A - N/A

.00 55

9 55 .0

6

55 .0

o

SFSF o SS

SF

4

55.05

6 55 .1

55 .6

.22 55

o S

EP WE

4 55 .5 3

SF

RW

DP

CUT

0.00 m² 0.00 m²

SF S

S

(L)

RL +55.805 YES

3.16 SIDE SETBACK (RHS) MIN. SIDE SETBACK REQ.ALLOWED : PROPOSED SIDE SETBACK :

3.29 EARTHWORK REQUIRED : PROPOSED :

NGL = 55.745 (+ / - 100mm) FGL = 55.370

(E) (K) (L)

o

SF

S

EASEMENT FOR DRAINAGE OF WATER .8 54

EE

ALFRESCO

0.9 m YES 1.00 m

3.24 LANDSCAPE AREA (FRONT ONLY) MIN. REQ. : PROPOSED :

SF

STORMWATER DRAINAGE PIT

S

3.16 SIDE SETBACK (LHS) MIN. SIDE SETBACK REQ.ALLOWED : PROPOSED SIDE SETBACK :

3.21 FRONT ARTICULATION ZONE DWELLING WIDTH : MAX. ALLOWED : PROPOSED :

SF S

E

COMMUNICATION PIT

STREET LIGHT POLE

RW

(E)

S

E

S

5.50 m 6.145 m

S

E

o

SF

REQUIRED - GARAGE : PROPOSED :

S

HYD

E

o

S

4.50 m 4.50 m

S

o

SF

3.14 FRONT SETBACK REQUIRED : PROPOSED :

E

o

S

7.20 m 2.78 m

S

E

o

COMMPIT

STORMWATER DRAINAGE LINE

ELECTRICAL TURRET

SF

FROM NGL TO UNDERSIDE OF EAVE : PROPOSED :

o

10"

RW

10.00 m 5.92 m

E

o

SUBSTATION

(L) (K)

(L)

N/A

o S

21' 24.27 5 E

.15 55

o S

E

SEWER SUPPLY (ROUTE / CROSSING)

.92 54 54.83

o

S

E

.95 54

HY D

E

3798 SETBACK

S

214°

JU NC TC AP

o

S

E

KERB

S

3.13 BUILDING HEIGHT FROM NGL TO RIDGE : PROPOSED :

OF

SF

0.00 m² 0.00 m²

DISH DRAIN

7 56 .1 4 56 .2 E

60% OR 396.48 m² YES 44% OR 290.57 m²

3.10 MAX. FLOOR AREA ALLOWED : PROPOSED :

GRATE 55.00

RECYCLE WATER SUPPLY (ROUTE/CROSSING)

NOTE : TO BE READ IN CONJUNCTION WITH LANDSCAPE & PLANS PREPARED BY ECO DESIGN LANDSCAPE DESIGNERS

3500

OF

F 55 SL .51

660.80 m² YES 16.81 m

POTABLE WATER SUPPLY (ROUTE/CROSSING)

RW

3.9 SITE COVERAGE ALLOWED : PROPOSED :

E

o

3.8 LOT TYPE SITE AREA : FRONTAGE :

BACK

56.25 CONC. PLYNTH FS L5 TOP OF 56.27 6.1 1

COMPLIANCE TABLE

56

F 56 SL .54

15.00 m²

CL

ELECTRICAL SUPPLY (ROUTE / CROSSING)

1 : 100

15 "

UNCONDITIONED :

DRIVEWAY SECTION

2

NOTE: SALINITY MANAGEMENT TO BE IN ACCORDANCE WITH SALINITY ASSESSMENT REPORT PREPARED BY GEOTECHNIQUE PTY LYD. DATED :26 AUGUST 2011 REFERENCE NO. 11669/2-AC

SE

SITE INFORMATION

7. FILTER SHALL BE CONSTRUCTED BY STRETCHING A FILTER FABRIC (PROPEX OR APPROVED EQUIVALENT BETWEEN POST AT 3.0m CENTRES. FABRIC SHALL BE BURIED 150mm ALONG ITS LOWER EDGE.

.00 55 RN C

NOTES - ALL LEVELS HAVE BEEN PREPARED TO AHD -

1:200 @A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(L)

Job No:

D000005

Drawing No: Date:

CON - 100 11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

6. SOIL AND TOPSOIL STOCKPILES SHALL BE LOCATED AWAY FROM DRAINAGE LINES AND AREA WHERE WATER MAY CONCENTRATE. ALL ROADS AND FOOTPATHS TO BE SWEPT DAILY.

UNCONDITIONED / CONDITIONED AREA 197.00 m²

E

5. ALL DISTURBED AREAS SHALL BE REVEGITATED AS SOON AS THE RELEVANT WORKS ARE COMPLETED.

31.28 m²

:

T.K. RL 55000 mm

EXISTING GRADE (4%)

SW

10%

8. DUST PREVENTION MEASURES TO BE MAINTAINED AT ALL TIMES.

CONDITIONED

NE

STREET

10%

W

NOT TO SCALE

10%

TA P

290.57 m²

SEDIMENT FENCE

T.O.L. RL 55350.0 mm

RE CT T AP AP

TOTAL AREA

GARAGE FLOOR LEVEL FFL 55805.0 mm

55 FS .14 L

207.82 m²

1.5m HIGH TIMBER POSTS @ 3.0m C/C MAX. DRIVEN MIN. 500mm INTO GROUND

55 FSL .13

TOTAL LIVING AREA

4. ALL SEDIMENT BASINS AND TRAPS SHALL BE CLEANED WHEN THE STRUCTURES ARE A MAXIMUM OF 60% FULL OF SOIL MATERIALS, INCLUDING THE MAINTENANCE PERIOD.

D UN RO

+ TOW 55.74

207.82 m² 38.18 m² 35.99 m² 8.58 m²

DG

3.5 M FRONT SETBACK

GROUND FLOOR ALFRESCO GARAGE PORCH

MIN. 150x100mm TRENCH WITH COMPACTED BACKFILL (SET INTO CONCRETE IF ON ROCK)

m

E RB

NW

(MEASURED TO EXTERNAL WALLS)

UN

. 3.0

TU DIS

N

3. SEDIMENT TRAPS SHALL BE CONSTRUCTED AROUND ALL INLET PITS, CONSISTING OF 300mm WIDE x 300mm DEEP TRENCH.

DIR E O CT WA VERL ION O T E AN F RF D LO W

BOUNDARY RL 55193.0 mm ABOVE T.K.

HOUSE AREAS

TOTAL SQUARES

X MA

2. ALL DRAINAGE WORKS SHALL BE CONSTRUCTED AND STABILIZED AS EARLY AS POSSIBLE DURING DEVELOPMENT.

RL 55393.0 mm ABOVE T.K.

660.80 m²

RL 55605.0 mm ABOVE T.K.

DP 1171087

:

2000 TRANSITION (12.5% MAX)

54 .97

:

SITE AREA

(25% MAX)

55.1 4 FSL

DP NUMBER

2000 TRANSITION (12.5% MAX)

75 °

LOT 14

EXISTING CROSSOVER

7.5 14' 25

:

NORTH POINT

6144 SETBACK TO GARAGE 2144

RO LL GU TTE R

LOT NUMBER

ED RB D TU DIS ROUN G

612 mm

SITE DETAILS

GEOTEXTILE FILTER FABRIC ATTACHED TO TIMBER POST

GEOTEXTILE FILTER FABRIC TO BE LAND BELOW TRENCH

MIN. 900mm

1. ALL EROSION AND SEDIMENTATION CONTROL MEASURES, INCLUDING REVEGETATION AND STORAGE OF SOIL AND TOPSOIL, SHALL BE IMPLEMENTED TO THE STANDARDS OF THE SOIL CONSERVATION OF NSW AND INSPECTED DAILY BY THE SITE MANAGER.

GARAGE WALL 612 mm ABOVE T.K.

SEDIMENT CONTROL NOTES

AREA CALCULATIONS


4095

300

4598 KITCHEN 7919 3829

90

300

1730 BTR

902 D06

900465

3190

- DOWNPIPES GENERALLY LOCATED 186mm FROM SLAB CORNER AND/OR TO COVER WALL TILE JOINT WHERE POSSIBLE

B 400

300

NORTH POINT

NOTES - ALL LEVELS HAVE BEEN PREPARED TO AHD

- ALL DOORS TO BE 2040mm IN HEIGHT, UNLESS NOTED

600

DP

7.9 X 4.8 TIMBER DECKING

1

FRAMING DIMENSION LINE

229 229

-

3095 BED 2

3915 FAMILY

180 1048 180 90

3905

3095 BED 3 1655 W06

90 593 90 ROBE 2213

GROUND FLOOR PLAN 1 : 100 COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

JK2030UR(B)+1230 908 X 602 W04

180 3095 BED 4 1655 W05

90

1730 BTR

2128 20843

JK2030UL(B)+1230 908 X 602 RAIN WATER

W03

1265

3323 BATH 602 165 602 W04 W03

D 401

Note:

Note: Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

Note:

GAS METER METER BOX

D02

2 607

CONTROL UNIT

TAP (CONNECTED TO RAINWATER TANK)

5815

90 1048 90 1048 90 WC 6300

3450 MEETING ROOM

455

DOWNPIPE

150

DOWNPIPE & SPREADER DRYER GARDEN TAP

G

GAS POINT

HWS

W01

DISHWASHER PROVISION DOUBLE VANITY

DRY

JD

4918

COOKTOP

DP

G.T

W02

INST. GAS HOT WATER SYSTEM JOIST DIRECTION

TB

LAUNDRY TUB

LOH

LIFT OFF HINGE

MH

MANHOLE LOCATION

MWP

MICROWAVE PROVISION

GD 4800

OBSC.

OBSCURE

OHC

OVERHEAD CUPBOARDS

RWT

RAINWATER TANK

RH

RANGEHOOD

FRP

REFRIGERATOR PROVISION SET OUT POINT

13258

D 1735

270

600

1968 1275 90 HALL WIR 90 1730 90 ENTRY 745 330349 1320 66 722

90 880 229 1670

HRV L'DRY 2185 90 1038 90 229 150 ENS. WC 4460 90 289166 289 BED 1 229 150 166 289 658 2489 76

1383 3095

S

600

SINK

SHR

SHOWER

SD

SLIDING DOORS

S

SMOKE DETECTOR

SS

SQUARE SET OPENING

SP

STEEL POST

T

TOILET

TILE

TILE FINISH

TP

TIMBER POST

UBO

UNDER BENCH OVEN

V

VANITY

HRV

VENTILATION ZONE

WO

WALL OVEN

WMP

WASHING MACHINE PROVISION

371 229

229

229

Panel lift door to be installed before timber framed wall behind. REFER TO CON-607 DETAIL 01

CONCRETE FINISH

DV

DP+SPR

3.3 X 2.4 CARPET

820

5825 GARAGE 5825 OFFICE 4800

90 820

602

150

MEETING ROOM

BTR 90

2868 90 1048 90

1

CAVITY SLIDING DOOR

(CONC.)

L

90 712 90

600 600

90

A 400

2413

WC TILE

90465

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

300

229

B

1795 90

720

SHR

4508 KITCHEN

1951 2401

90

3300

1210

FW

TILE

720

3.3 X 3.2

LO H

3.1 X 3.1 CARPET

FW

90

1255 SS 2449

1275 820 T

BATH

3260 4460

1473 90

2688

2640

OHC

920

1503

JK2460+314 1824 X745

LINEN

620 W'ROBE

150

BREAKFAST BAR

CSD

AREA CALCULATIONS HOUSE AREAS (MEASURED TO EXTERNAL WALLS)

DP 1100 229 1010

1401

239 150 850 60 90 229 1010

1401 1401 1401

NOTE : ALLOW ADDITIONAL 45mm TO PERIMETER OF NOTED WINDOW OPENING SIZES.

FRAMING DIMENSION LINE

3

RL +55.805

STORE

BED 4

J5945+774 W05 1364 X 1655

PORCH

TIMBER DECKING

229

229

229

300

D01

TIMBER

Blocked up from RL +55.805 Garage side & CARPET provide lock 90 1048 90

90

948 1

RL +55.880

TEMPORARY SALES OFFICE

Bar Fridge

BATH

J5945+774 W06 1364 X 1655

INST. GAS HWS

229

301

ENTRY

MH

720

90

3.1 X 3.1 CARPET

S

90 1048 90

1503

3.1 X 3.5 CARPET

620 + 820

180

RL +55.880 820

W'ROBE 90

BED 3

W02

TIMBER

HALL

820

BED 2

1.7 X 2.8

FRP

TIMBER

1820

BTR

180

90 600

OHC

SS 2449

4.6 X 2.9 TIMBER CT/UBO/RH OHC

ALCOVE SS 2449

1055 1210

1210

KITCHEN

S

90

J5945+774 1364 X 1655

DWP

S

1048

820

683

W'ROBE

2.6 X 1.9

LOWERED CEILING

MWP

WIR

820

1200

B/BAR

SS 2449

DP

301

SHR

SS 2449

2965

1383

433 180

TIMBER

WMP

TILE

W01

1540 1101 300

4.0 X 4.4

1.7 X 3.5

1200

TIMBER

L'DRY

BED 1

1 605

90

TIMBER

SS 2240

SS 2449

4.0 X 3.6

3532

3.6 X 3.7

350

JK2045R+774 1364 X 602

HALL

90 1048 90

LIVING

900

SCREEN

FAMILY

A/C UNIT

BATH

BED 3 3095

S/D

J8370 1364 X 1200

180

G.T

90 BTR

2868

KITCHEN

FAMILY 4233 W'ROBE 90 1048 90 BED2 3095

DINING

SS 2449

1383

JK2045R+774 1364 X 602

90

90 4233 683 90

2440

1048

W08

W07 3550

FW

S/D

TIMBER

J8615T+2009 469 X 2489

J8615T+2009 469 X 2489

ENS. FW TILE

J11970T 2138 X 3399

3.9 X 4.2

W14

HALL

D06

D04

W09

C 401

JK2060+314 W13 1824 X 602

BATH

W12

W10

1186

545

W11

2.6 X 3.3

600

L'DRY

3640

DINING 3442

D04 3779

2235 658 726 602

W09

1673 W08

602

J8660T+308 1830 X 2489

JK2042U(B)+961 1177 X 602

S/D

W07

229

B/BAR

CT

341

316 316

229

DP

JK2042U(B)+961 1177 X 602

JK3570AR 902 X 2138

4 606

J11970T 2138 X 3399

D05

D03

2

LEGEND

DWP

A 400 1655

1 604

HRV

300

NOTE : TO BE READ IN CONJUNCTION WITH LANDSCAPE & PLANS PREPARED BY ECO DESIGN LANDSCAPE DESIGNERS

ALFRESCO 4221

4821

FRAMING DIMENSION LINE 316 658 229

316 3779

- REFER TO 500 SERIES DRAWINGS FOR INTERNAL ROOM DETAILS

2 604

1

8874

DP

NW

- ALL BULKHEAD & SS TO BE 2240mm IN HEIGHT, UNLESS NOTED

GROUND FLOOR ALFRESCO GARAGE PORCH

207.82 m² 38.18 m² 35.99 m² 8.58 m²

TOTAL LIVING AREA

207.82 m²

TOTAL AREA

290.57 m²

TOTAL SQUARES

31.28 m²

B 400

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:100 @A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(L)

Job No:

D000005

Drawing No: Date:

CON - 200 11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

180 1048 180

9465

711

S

3915 FAMILY

2489 W10

1251

599 229 564 602 308 602 564 229354 602 346 2489 76 229 150 1251 W11 W12 W13 W14 90 2640 90 4005 229 150 1251 ENS. BED 1 3995 90 2995 229 160 2251 ENTRY

SW

229

696

150

SE

3399 D05

2794

W

229

234 229 531

1302

E

FRAMING DIMENSION LINE

3399 D03 4095

3098

N

229 234

1401

9555

NE

20843 4095


3399

234 760

3399

3761

135 902

599 525

2048

525

1302

NOTE : TO BE READ IN CONJUNCTION WITH LANDSCAPE & PLANS PREPARED BY ECO DESIGN LANDSCAPE DESIGNERS

2944

LEGEND +00.0

-75.0

DEB

STEPS DOWN DROPPED EDGE BEAMS REQUIRED DRAINAGE POINTS

927 1

4821

4671

SET OUT POINT

1 927

1026

1226

4998

ALFRESCO

- ALL LEVELS HAVE BEEN PREPARED TO AHD - DOWNPIPES GENERALLY LOCATED 186mm FROM SLAB CORNER AND/OR TO COVER WALL TILE JOINT WHERE POSSIBLE

150

605

699 150

4

FW

1076

- PVC TERMITE COLLARS TO ALL PENETRATIONS

2944

1246

950

FW HRV

780 214

2235

NOTES

275

+00.0

328

605

RL +55.805

VANITY

3 606

-75.0

887

264 810

999

SHR

- CONCRETE SLAB AND FOOTINGS TO STRUCTURAL ENGINEER'S DETAILS

289

WC

7584

4277

1986

75

1976 1986

519

425

89 245

2019

1820

PORCH RL +55.805

80

2401

2135 VANITY

991

+00.0

-20.0

25 4800

RL +55.805 WC

868

357

4862 CONDUIT

A/C SLAB

RL +55.805

5

GARAGE 2

DETAIL-GARAGE EXTERNAL WALL 1 : 25

FW

1452

229

BATH

684

741

2

600

SHR

75

1275

3305

135 10967

840

673

1220

45

13879

3

6114

DETAIL-ENTRY DOOR SETBACK 1 : 25 139

-

SLAB LAYOUT PLAN 1 : 100

5

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

100

229 20

9013

1

1 : 25 139

2401

2889

DETAIL-GARAGE STEP DOWN

149

RL +55.880

1520

1

137

654

1261

1985 CONDUIT

210

-75.0

219 31

520

-75

+00.0

HOUSE

780

SERVICE CONDUIT FOR ISLAND BENCH

+00.0

2338

3 KITCHEN SINK

DETAIL-GARAGE DOOR STEP DOWN 1 : 25

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

4

DETAIL-TYPICAL REBATE CONSTRUCTION 1 : 25

1:100 @A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(R)

Job No:

D000005

Drawing No:

CON - 201

Date:

11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

463


NOTE : TO BE READ IN CONJUNCTION WITH LANDSCAPE & PLANS PREPARED BY ECO DESIGN LANDSCAPE DESIGNERS

H=2100

H=2100

S

SMOKE ALARM BATON HOLDER LIGHT FITTING LED DOWNLIGHT

P

PENDANT LIGHT

CONDUIT

SPOT LIGHT WALL MOUNT LIGHT (H=FL+..........)

1400

FLUORESCENT LIGHT EX

EXT. DOUBLE POWERPOINT (H=FL+600 UNLESS NOTED) DOUBLE POWERPOINT (H=FL+300 UNLESS NOTED)

S

DOUBLE

SINGLE POWERPOINT (H=FL+300 UNLESS NOTED)

CL

TEL.

300

SWITCH (H=FL+1300 UNLESS NOTED)

DP

S H-1200

C

GL

2

H-1200

TEL

ENS.

RA SA

2 WAY SWITCH (H=FL+1300 UNLESS NOTED)

TEL

TELEPHONE (H=FL+300 UNLESS NOTED)

TV

TV (H=FL+300 UNLESS NOTED)

D

DATA (H=FL+300 UNLESS NOTED)

MS

MOTION SENSOR

RA

L'DRY LIVING

P P P

1 : 20

BED 1

RA

AC

AC

H=2100

AC

WIR

MS

C

2

SECURITY CAMERA

C

202

CEILING FAN

2

FAMILY

MW

DW

S

S

ALARM BOX H=1100

S

ALARM PAD C

202

H-2100 MS

S

LOWERED CEILING

BTR

LED STRIP LIGHTING

MH

KITCHEN LED STRIP LIGHTING UNDER OHC

S

TEL

H=1100

RH H=1800 S

EA GAS CT

H=1100

2

AC RETURN UNIT

H=1100 S

AC UNIT

D TEL

LEGEND (AIR CONDITIONING)

FR H=1600 S

2

W'ROBE

A/C UNIT

S H=600

NOTE: NBN HUB IN ROOF

H=2100

AC

TEMPORARY SALES OFFICE

AC UNIT

AIR CONDITIONING UNIT

AC RETURN UNIT

RETURN AIR GRILL

H=600

W'ROBE

AC

RA

MEETING ROOM

BED 4

EA

BATH

SA HRV

METER BOX GAS METER

INST. GAS HWS

EXHAUST AIR RETURN AIR SUPPLY AIR VENTILATION SYSTEM LOCATION

H=2100

D TEL TV

NOTES C

DP

SUPPLY AIR

RA AC

AC

AIR CONDITIONING OUTLET

H=CEILING

WC

RAIN WATER CONTROL UNIT

BED 3

H-1200

S

AC

W'ROBE

2

DINING

TV WALL ROUGH IN

- PROVIDE MOTION SENSORS

DP

1100

- NBN HUB TO TERMINATE IN ROOF SPACE

301 900 51

301 900

300 900

23

31

300 900

1

GF ELECTRICAL & DATA LAYOUT 1 : 100

42

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:100 @A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(R)

Job No:

D000005

Drawing No:

CON - 202

Date:

11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

LEGEND (ELECTRICAL)

DATA CL

SINGLE TV


ROOF PITCH 23°

SOLAR GAS BOOSTED WATER HEATER

TILE ROOF AS SELECTED FASCIA & GUTTER AS SELECTED

RL+58629 CEILING

P4

P2

P1

P2

S1

P2

ALFRESCO

P2

2749

SELECTED GARAGE DOOR

2478 WINDOW

P1

PAINTED FINISH AS SELECTED

P4

2250

P3

METER BOX

3249

P1

RL+55880 GROUND FLOOR

DP

DP

FRONT DOOR AS SELECTED

SOUTH ELEVATION 1 : 100

BOUNDARY

RL+61419 RIDGE

BOUNDARY

1

SOLAR GAS BOOSTED WATER HEATER

ROOF PITCH 23°

TILE ROOF AS SELECTED 1.44 KW PV SOLAR SYSTEM FASCIA & GUTTER AS SELECTED

RL+58629 CEILING

RL+55880 GROUND FLOOR

P1

P2

2749

METER BOX

P1

3249

INST. GAS HWS

2138 WINDOW 2449

P4

GAS METER

A/C UNIT

DP

DP

PAINTED FINISH AS SELECTED

EXISTING RETAINING WALL

WINDOW COLOUR

PROPOSED RETAINING WALL

2

IN:

WHITE

OUT:

BROWN

WEST ELEVATION

NOTES

1 : 100

- ALL LEVELS HAVE BEEN PREPARED TO AHD - DOWNPIPES GENERALLY LOCATED 186mm FROM SLAB CORNER AND/OR TO COVER WALL TILE JOINT WHERE POSSIBLE

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:100 @A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(L)

Job No:

D000005

Drawing No: Date:

CON - 300 11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

BOUNDARY

RL+61419 RIDGE


ROOF PITCH 23°

1.44 KW PV SOLAR SYSTEM SOLAR GAS BOOSTED WATER HEATER

TILE ROOF AS SELECTED

ALFRESCO

P4

P2

P1

P1

2250

P2

RL+55880 GROUND FLOOR

2749

FASCIA & GUTTER AS SELECTED

2138 WINDOW

RL+58629 CEILING

A/C UNIT

DP

NORTH ELEVATION

3

RL+61419 RIDGE

PAINTED FINISH AS SELECTED

1 : 100

ROOF PITCH 23° TILE ROOF AS SELECTED FASCIA & GUTTER AS SELECTED

1.44 KW PV SOLAR SYSTEM

P4

RL+58629 CEILING

P4 P1

S1

RL+55880 GROUND FLOOR

P1

A/C UNIT

P1

P1

P2

P2

2749

P1

2138 WINDOW

P4 P2

2250

2009

P3

2524

3249

P2

P2

PAINT FINISH AS SELECTED

1

EAST ELEVATION 1 : 100

WINDOW COLOUR IN:

WHITE

OUT:

BROWN

NOTES - ALL LEVELS HAVE BEEN PREPARED TO AHD - DOWNPIPES GENERALLY LOCATED 186mm FROM SLAB CORNER AND/OR TO COVER WALL TILE JOINT WHERE POSSIBLE

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:100 @A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(L)

Job No:

D000005

Drawing No: Date:

CON - 301 11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

BOUNDARY

RL+61419 RIDGE


RL+61419 RIDGE

INSULATION IN CEILING SPACE AS PER BASIX CERTIFICATE

ROOF PITCH 23° 1.44 KW PV SOLAR SYSTEM

1 607

BED 3

BED 2

BED 4

WC

BATH

WC

3249

FC SHEET TO THE U/S OF EAVES

MEETING ROOM

75 STEPDOWN

2524

RL+55880 GROUND FLOOR

2749

RL+58629 CEILING

A/C UNIT

EXISTING RETAINING WALL

REINFORCED CONCRETE SLAB TO ENG'S DETAIL

SECTION AA

A

GORMON AVENUE

BOUNDARY

1 : 100

RL+61419 RIDGE

ROOF PITCH 23° TIMBER ROOF TRUSSES TO MANU. SPECS. INSULATION IN CEILING SPACE AS PER BASIX CERTIFICATE

RL+58629 CEILING

HALL

L'DRY 2250

BATH

2749

FC SHEETING TO U/S OF EAVES

RL+55880 GROUND FLOOR

DP

B

1 : 100

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

REINFORCED CONCRETE SLAB TO ENG'S DETAIL

SECTION BB

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:100 @A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(L)

Job No:

D000005

Drawing No: Date:

CON - 400 11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

BOUNDARY

BOUNDARY

TIMBER ROOF TRUSSES TO MANU. SPECS.


1 603

2 605

KITCHEN

BTR

HALL

ENTRY

2749

FAMILY

3

3249

RL+58629 CEILING

GORMON AVENUE

75 STEPDOWN

605

RL+55880 GROUND FLOOR

3

C

SECTION CC

607

1 : 100

RL+61419 RIDGE

RL+58629 CEILING

2250

ALFRESCO

LIVING

KITCHEN

HALL

BED 4

2 606

3 606

D

2749

1 606

RL+55880 GROUND FLOOR

Section DD 1 : 100

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:100 @A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY (L)

Job No:

D000005

Drawing No:

CON - 401

Date:

11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

RL+61419 RIDGE

ROOF PITCH 23°


2965

LEGEND (ROOM DETAILS)

1200

BATH

350 25

1458

1402

1200

18

2802 18 51

825

413

825

825

413 51

CT

COOKTOP

DR

DRAWERS

3402

18

18

1088

4508 KITCHEN

900

51

SS OPENING

PT1

PT4

PT4

1200

900

1200

966

600

51

180

KITCHEN LAYOUT

KITCHEN-ELEVATION 1

1

1 : 50

KITCHEN-ELEVATION 2

2

1 : 50

DRYER PROVISION DOUBLE VANITY DISHWASHER PROVISION FREE STANDING OVEN REFRIGERATOR PROVISION

FW

FLOOR WASTE

HT

HAND TOWEL

TB

LAUNDRY TUB

LOH

LIFT OFF HINGE

MR

MIRROR

1200 HIGH

MWP

MICROWAVE PROVISION

OHC

OVERHEAD CUPBOARDS

S

RANGEHOOD SINK

SD

SOAP DISH

SHR

SHOWER

SM

SHOWER MIXER

1200 HIGH

SR

SHOWER RAIL (TOP)

1900 HIGH

SC

SHOWER SCREEN

2000 HIGH

T

1 : 50

BY OWNER

FRP

RH

190

PT1

966

PT1

776

PT1

900 UBO

2240

674

674

350 CS1

GAS CT

PT1

FO

600

PT2

20

PT2

600

PT2

PT1

FRP

OHC

PT2

CS1

CS1

1600 GPO

FRP

PT2

RH SPLASHBACK CL

2240

OHC

PT2

PT2

1100 GPO

600

PT2

PT2

CL

544 GPO

GAS CT / UBO / RH

-

PT2 PUSH

CL

SS 2449

KITCHEN

1

180

PT2 PUSH

BREAKFAST BAR

BO

DWP

1210

1210

2

800 HIGH

DV

S

4

800 HIGH

BATH SPOUT

CLGPO

DWP 3

BATH MIXER

BS

DRY

350

DR

BATH TUB

BM

B/BAR

300

CL

965

900

MWP

TOILET

TPH

TOILET PAPER HOLDER

650 HIGH

TR

TOWEL RAIL

1200 HIGH

UBO V

UNDER BENCH OVEN VANITY

HRV

VENTILATION ZONE

WMP

WASHING MACHINE PROVISION

WO

WALL OVEN

NOTES - ALL DIMENSIONS ARE FROM CONCRETE SLAB/FLOOR SHEETING.

600

4

- ALL FLOOR WASTE ARE TO BE RECESSED TO ALLOW FOR TILE INSERT FLOOR WASTE.

501

80

605

350

80 CS1

53 450

CS1

KITCHEN-ELEVATION 3

4

1 : 50

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

PUSH

1 : 50

Note:

Note: Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

Note:

450

450 53

CS1 PUSH

PT1

PT1

PT1

PUSH

PT1

PT1

PUSH

PT1

PT1

350

5

Client:

KITCHEN-ELEVATION 5 1 : 50

Scale:

Ichijo Technological Homes Address:

450

PUSH

776

900

KITCHEN-ELEVATION 4

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

PUSH

190

600

3

200

886

PT1

PT4

450

TB1

766

PT1

190

PT1

966

DWP

PT1 PT1

16

PT1

776

16

460

200

MWP

450

- ALL DIMENSIONS ARE TAKEN FROM TIMBER STUD WALLS.

80

CS1

TB1

80

TB1

CS1

1403

200

1000

40

600

674

600

2240

350 80

1403

966

1250

766

2965

20

350

766

783

1406 GPO 1070

DROPPED CEILING ABOVE

B/BAR

TB1

90

90

350

5

80

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:50 @A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(R)

Job No:

D000005

Drawing No:

CON - 500

Date:

11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

350


BATH MIXER

800 HIGH

BS

BATH SPOUT

800 HIGH

B/BAR

970

HRV

880

229

BO

HRV

18 400

400 18

834

CT

COOKTOP DRAWERS

DV DWP

90

FO

40mm CAESARSTONE KITCHEN BENCH TOP WITH 16mm SHADOWLINE & HANDLES TO DOORS 190mm KICK

WM TAPS 1670

FW 1

305 OUTSIDE OF MDF LB1

1.7 X 3.5

MDF BULKHEAD BY JOINER

90

CL

WMP

90

1

LAUNDRY TUB

LOH

LIFT OFF HINGE

MR

MIRROR

MWP

MICROWAVE PROVISION

OHC

OVERHEAD CUPBOARDS

1200 HIGH

RANGEHOOD SINK

SHOWER

CL CL

SM

SHOWER MIXER

1200 HIGH

SR

SHOWER RAIL (TOP)

1900 HIGH

SC

SHOWER SCREEN

2000 HIGH

ADJUSTABLE SHELF

WM TAPS

600

T

LAUNDRY ELEVATION

450

450

650 HIGH

TOWEL RAIL

1200 HIGH

600

450 50

674 C.O.S

UNDER BENCH OVEN VANITY

HRV

VENTILATION ZONE

WMP

WASHING MACHINE PROVISION

WO

90

50 450

40

2640

600

TOILET PAPER HOLDER

TR

V

NOTE: DIMENSIONS ARE TAKEN FROM SLAB LEVEL

TOILET

TPH

UBO

1 : 50

740

HAND TOWEL

TB

SOAP DISH

350

1 : 50

HT

SHR

593 90 HRV/LINEN

LAUNDRY LAYOUT

REFRIGERATOR PROVISION FLOOR WASTE

PT3

2240

-

1048

FREE STANDING OVEN

SD

340 125 90

DISHWASHER PROVISION

FW

S

966

PT3

350

712 90

LINEN

LINEN

PT3

DRYER PROVISION DOUBLE VANITY

FRP

RH

2050

L'DRY

150

WMP

BREAKFAST BAR BY OWNER

DR DRY

802

BATH TUB

BM

WALL OVEN

NOTES - ALL DIMENSIONS ARE FROM CONCRETE SLAB/FLOOR SHEETING.

16

- ALL FLOOR WASTE ARE TO BE RECESSED TO ALLOW FOR TILE INSERT FLOOR WASTE. DOOR FIXED IN CLOSED POSITION

- ALL DIMENSIONS ARE TAKEN FROM TIMBER STUD WALLS.

3

966

2640

720

ADJUSTABLE SHELF

PT5

PT5

PT5

PT5

190

190 966

Bar Fridge

PT4

90

2

1048

190

90

928

Bar Fridge

776

38 150

LB2

4

90

SALES OFFICE KITCHENETTE

3

1 : 50

1 : 20

KITCHENETTE ELEVATION 1 : 50

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

TYPICAL KITCHEN BENCH SECTION

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:50 @A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(R)

Job No:

D000005

Drawing No:

CON - 501

Date:

11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

LEGEND (ROOM DETAILS) BATH


1048 EQ

90

2185

EQ

920

EQ CL

2185

V2165 CS1

SHR

T

BM

V2165

BATH

TR

705

TPH

1200

TPH

SM 2000

TR

1 608

SR

1900 FIXING BRACKET 1200

FW

SHR

650

910

250

890

3

4

910

1265

502

T CL

EQ

165

1675 BATH 1003

BATH ELEVATION 1

1

1320

1593

EQ

141 341

CL

670

1 : 50

COOKTOP DRAWERS

DRY

DRYER PROVISION

DV

DOUBLE VANITY

BATH LAYOUT

REFRIGERATOR PROVISION FLOOR WASTE

HT

HAND TOWEL

TB

LAUNDRY TUB

LOH

LIFT OFF HINGE

MR

MIRROR

MWP

MICROWAVE PROVISION

OHC

OVERHEAD CUPBOARDS

1200 HIGH

RANGEHOOD

S

SINK

SD

SOAP DISH

SHR

SHOWER

SM

SHOWER MIXER

1200 HIGH

SR

SHOWER RAIL (TOP)

1900 HIGH

SC

SHOWER SCREEN

2000 HIGH

TOILET

TPH

TOILET PAPER HOLDER

650 HIGH

TR

TOWEL RAIL

1200 HIGH

V

3095

FREE STANDING OVEN

FW

UBO

1 : 50

DISHWASHER PROVISION

FRP

T

UNDER BENCH OVEN VANITY

HRV

VENTILATION ZONE

WMP

WASHING MACHINE PROVISION

WO

WALL OVEN

NOTES - ALL DIMENSIONS ARE FROM CONCRETE SLAB/FLOOR SHEETING.

SR

- ALL FLOOR WASTE ARE TO BE RECESSED TO ALLOW FOR TILE INSERT FLOOR WASTE.

MR

- ALL DIMENSIONS ARE TAKEN FROM TIMBER STUD WALLS.

1000

PT3

BATH

V2165 PT3

47 450

450

300 2185

3

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

BATH ELEVATION 3

4

1 : 50

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

PT3

Client:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

900

38 910

BATH ELEVATION 4 1 : 50

Scale:

Ichijo Technological Homes Address:

800

PT3

BM 518

PT3

CL

BS

190

BATH HOB

CL

CS1

890

V2165

800

518 BATH HOB

BS

760

644 16 40

SHR

150

1900 FIXING POINT 2000

1320

890

-

BY OWNER

DR

RH

BATH ELEVATION 2

2

1 : 50

CL

BREAKFAST BAR

CT

FO

11 40

2

1000 SHR 1000

800 HIGH

DWP

SR 1

SM

800 HIGH

BATH SPOUT

BO

910 SHOWER EQ

TR

BATH MIXER

BS B/BAR

720

BATH TUB

BM

Drawn By: Design: Facade:

1:50 @A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(R)

Job No:

D000005

Drawing No:

CON - 502

Date:

11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

LEGEND (ROOM DETAILS) BATH


BATH

BATH MIXER

800 HIGH

BS

BATH SPOUT

800 HIGH

B/BAR

229

2640

90

BO

229

2640

90

COOKTOP DRAWERS

DWP

796

455

FO

4

1255

1730

FW 2 3

EQ

TR

1000

MR SS OPENING

2185

1

EQ CS1

519

PT3

PT3

890

PT3

190

PT3

PT3

SR

30

900

325

1038

90

900

30

2275

650

853

90

1048

1

ENS. ELEVATION 1

ENS. ELEVATION 2

2

1 : 50

1 : 50

REFRIGERATOR PROVISION

HT

HAND TOWEL

TB

LAUNDRY TUB

LOH

LIFT OFF HINGE

MR

MIRROR MICROWAVE PROVISION

OHC

OVERHEAD CUPBOARDS

1 : 50 1083 EQ

RANGEHOOD SINK

SD

SOAP DISH

SHR

SHOWER

SM

SHOWER MIXER

1200 HIGH

SR

SHOWER RAIL (TOP)

1900 HIGH

SC

SHOWER SCREEN

2000 HIGH

TOILET

TPH

TOILET PAPER HOLDER

650 HIGH

TR

TOWEL RAIL

1200 HIGH

UBO

ENSUITE LAYOUT

1200 HIGH

MWP

V

-

FREE STANDING OVEN

FLOOR WASTE

T

UNDER BENCH OVEN VANITY

HRV

VENTILATION ZONE

WMP

WASHING MACHINE PROVISION

WO

WALL OVEN

EQ

NOTES

CL

- ALL DIMENSIONS ARE FROM CONCRETE SLAB/FLOOR SHEETING. - ALL FLOOR WASTE ARE TO BE RECESSED TO ALLOW FOR TILE INSERT FLOOR WASTE.

SR

SR EQ 336

CL

CL

CL

791

650

1200

TPH

2000

SHR

CL

SM

TR

2240

2000

650

- ALL DIMENSIONS ARE TAKEN FROM TIMBER STUD WALLS.

1900 FIXING POINT

EQ

1900 FIXING POINT

90

890

1262

1038

T

PT3

DISHWASHER PROVISION

FW

S

T

SM

DRYER PROVISION DOUBLE VANITY

FRP

RH

16

90

SS 2240

519

90

40

150

CL

BY OWNER

DR

DV

CS1

BREAKFAST BAR

CT

DRY

TR

BATH TUB

BM

T 1048

3

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

90

ENS. ELEVATION 3 1 : 50

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

796

1503

Note:

Client:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1262

ENS. ELEVATION 4

Scale:

Ichijo Technological Homes Address:

4

1255

1 : 50

1:50 @A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(R)

Job No:

D000005

Drawing No:

CON - 503

Date:

11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

LEGEND (ROOM DETAILS)


90

1730

90

1130

BATH

90 600

90

400

2068

400

BATH MIXER

800 HIGH

BS

BATH SPOUT

800 HIGH

500

500

500

500

34 400

BO

PT2

PT2

600

600

PT2

PT1

966

1100 GPO 966

776

PT2 PT2

PT1

PT1

PT1

40 674

674

PT1 CS1

720 16

S

PT1

PT4

90

1050

40

600

600

34 400

400

400

400 34

600

BUTLER'S KITCHEN

1

1 : 50

BTR KITCHEN ELEVATION 1 1 : 50

DRY

DRYER PROVISION

2

BTR KITCHEN ELEVATION 2 1 : 50

REFRIGERATOR PROVISION FLOOR WASTE

HT

HAND TOWEL

TB

LAUNDRY TUB

LOH

LIFT OFF HINGE

MR

MIRROR

MWP

MICROWAVE PROVISION

OHC

OVERHEAD CUPBOARDS

400 350

1210 SS OPENING 2068

965

SINK SOAP DISH

SHR

SHOWER

SM

SHOWER MIXER

1200 HIGH

SR

SHOWER RAIL (TOP)

1900 HIGH

SC

SHOWER SCREEN

2000 HIGH

TOILET

TPH

TOILET PAPER HOLDER

650 HIGH

TR

TOWEL RAIL

1200 HIGH

UNDER BENCH OVEN VANITY

HRV

VENTILATION ZONE

WMP

WASHING MACHINE PROVISION

WO

400

RANGEHOOD

SD

V

693

1200 HIGH

S

UBO

501

FREE STANDING OVEN

FW

T

4

DOUBLE VANITY DISHWASHER PROVISION

FRP

RH

90

WALL OVEN

1380

NOTES

PT1

600 776

776

PT1

674

600 SS OPENING

16 40

CS1

- ALL FLOOR WASTE ARE TO BE RECESSED TO ALLOW FOR TILE INSERT FLOOR WASTE. - ALL DIMENSIONS ARE TAKEN FROM TIMBER STUD WALLS.

2449 SS OPENING

ALL SHELVING PT2

674

2240

600

600

- ALL DIMENSIONS ARE FROM CONCRETE SLAB/FLOOR SHEETING.

966

PT4

600

3

1050

40

BTR KITCHEN ELEVATION 3 1 : 50

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

40

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

190

PT1

190

-

1730

PT4

674

180

190

190

600

90

693

PT2

40

COOKTOP DRAWERS

FO SPLASH BACK CL

BY OWNER

DR

DWP

569 GPO

BREAKFAST BAR

CT

DV

1140 CS1

1.7 X 2.8 TIMBER

PT2

CL

674

2868

3

BTR

ALL SHELVING PT2

2240

2 OHC

SS 2449

1668

4

600

50 674 50 225 225

965

1

1210

400 34

350

50

600

90

90

B/BAR

1380

BATH TUB

BM

4

BTR KITCHEN ELEVATION 4 1 : 50

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:50 @A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(R)

Job No:

D000005

Drawing No:

CON - 508

Date:

11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

LEGEND (ROOM DETAILS)


2464

2824

90x45x8 CLEAT

90x90x4 STEEL POST

DRILL 2x19 Dia

200x90x10 BASE PLATE 90x45x8 CLEAT

PLAN

360

360

CENTRE STEEL POST ALFRESCO

DRILL 6x14 Dia

DRILL 6x14 Dia

2 601

150

3810 300

3510

2 601

3810 300

A

150

3510

A 90x90x4 STEEL POST

1 601

DRILL 2x19 Dia

SECTION A-A

150x132x10 TOP PLATE

42

1 : 50

360x75x75x8 EA

99

360x75x75x8 EA

TOP PLATE PLAN

NOTE : ALL STEEL POST BRACKETS HAVE BEEN DIMENSIONED BASED ON A 360 x 42 LVL. ADJUSTMENTS TO BE MADE IF LVL SIZE IS SPECIFIED DIFFERENTLY. BY FRAMER.

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

150x132x10 TOP PLATE

99

RIGHT HAND SIDE STEEL POST

Alfresco Steel Post Details 1 : 20

Client:

Scale:

Ichijo Technological Homes Address:

200x90x10 BASE PLATE

TOP PLATE PLAN

LEFT HAND SIDE STEEL POST 2

90x90x4 STEEL POST

DRILL 2x19 Dia

200x90x10 BASE PLATE

Alfresco Plan

COPYRIGHT

A

300

SECTION A-A

1

A

42

184

226

600

RIGHT HAND STEEL POST

226

CENTRE STEEL POST

600

600

LEFT HAND STEEL POST

2464

2464

1 601

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:10 @ A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(R)

Job No:

D000005

Drawing No:

CON - 600

Date:

11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

360

DRILL THRU POST 3x14 Dia


589

TIMBECK "VEE JOINT" WF-VJ IN WALNUT - MID BROWN TINT. 15mm X 135mm 574

31X19 TIMBER TRIM

OUTLINE OF BULKHEAD 4.5mm FC SHEET

550

4.5mm FC SHEET 31x19 TIMBER TRIM

6mm FC SHEET

90x90x4 SHS STEEL POST

31x19 TIMBER TRIM

6mm FC SHEET HEBEL POWERPANEL

39

APPLIED FINISH

38x38 DAR WESTERN RED CEDAR BATTENS @ APPROX 80mm CTS (NOMINATED SIZE IS FINISHED SIZE)

370 SQUARE SET EXTERNAL EDGE

SQUARE SET EXTERNAL EDGE

2250

ALFRESCO

1

Alfresco Beam to Steel Post Connection Detail

2

1 : 20

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

Alfresco Bulkhead Detail 1 : 20

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:10 @ A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(R)

Job No:

D000005

Drawing No:

CON - 601

Date:

11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

TIMBER BEAM


360 2964

90x90x4 STEEL POST

A PORCH

BULKHEAD

RIGHT HAND STEEL POST

BULKHEAD

150

TOP HAT BATTEN TO SUIT 4160

150

90x90x4 STEEL POST

DRILL 2x19 Dia

A

90x90x4 STEEL POST

200x90x10 BASE PLATE

300

APPLIED COATING

A

1 603

2 603

HEBEL POWERPANEL

150

300

LEFT HAND STEEL POST

A

DRILL 2x19 Dia

200x90x10 BASE PLATE

SECTION A-A

SECTION A-A

150 150x150x10 TOP PLATE

1

150x150x10 TOP PLATE

600

2 603

Porch Plan

360x75x75x8 EA

1 603

360x75x75x8 EA

76

3260

76

600

76

76

TOP PLATE PLAN

TOP PLATE PLAN

1 : 50

RIGHT HAND SIDE STEEL POST

LEFT HAND SIDE STEEL POST

2

NOTE : ALL STEEL POST BRACKETS HAVE BEEN DIMENSIONED BASED ON A 360 x 42 LVL. ADJUSTMENTS TO BE MADE IF LVL SIZE IS SPECIFIED DIFFERENTLY. BY FRAMER. COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

Porch Steel Post Details 1 : 20

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:10 @ A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(R)

Job No:

D000005

Drawing No:

CON - 602

Date:

11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

360 2964 90x90x4 STEEL POST


TIMBECK "VEE JOINT" WF-VJ IN WALNUT - MID BROWN TINT. 15mm X 135mm

31x19 TIMBER TRIM

4.5mm FC SHEET

6mm FC SHEET

6mm FC SHEET

38x38 DAR WESTERN RED CEDAR BATTENS @ APPROX 80mm CTS (NOMINATED SIZE IS FINISHED SIZE)

6mm FC SHEET

SQUARE SET EXTERNAL EDGES

6

4.5mm FC SHEET

494

TIMBECK "VEE JOINT" WF-VJ IN WALNUT - MID BROWN TINT. 15mm X 135mm

31x19 TIMBER TRIM 6mm FC SHEET

38x38 DAR WESTERN RED CEDAR BATTENS @ APPROX 80mm CTS (NOMINATED SIZE IS FINISHED SIZE)

SQUARE SET EXTERNAL EDGES

100 100

1

2824 2524

2824

2824 2524

2824

3324

194

3324

6

Porch Bulkhead & Raised Roof Detail_Side Bulkheads

2

1 : 20

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

Porch Bulkhead & Raised Roof Details_front bulkhead 1 : 20

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:10 @ A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(R)

Job No:

D000005

Drawing No:

CON - 603

Date:

11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

500

500

589


4.5mm FC SHEET 39mm PACKER

39mm PACKER

CEILING INSULATION 6mm FC SHEET

150

6mm FC SHEET

500

500

CEILING INSULATION

4.5mm FC SHEET

150

38x38 DAR WESTERN RED CEDAR BATTENS @ APPROX 80mm CTS (NOMINATED SIZE IS FINISHED SIZE)

38x38 DAR WESTERN RED CEDAR BATTENS @ APPROX 80mm CTS (NOMINATED SIZE IS FINISHED SIZE) PLASTERBOARD LINING

COLORBOND FLASHING/CAPPING

525

90mm TIMBER FRAMES COLORBOND FLASHING/CAPPING

HEBEL POWERPANEL

PLASTERBOARD LINING

WALL INSULATION

APPLIED COATING

HEBEL POWERPANEL 90mm TIMBER FRAMES

64mm TOP HAT BATTEN

APPLIED COATING

150

WALL INSULATION

BUILDING WRAP

2324

2849

2749

2849

2749

3249

3249

BUILDING WRAP

WEEP HOLE INSERTS @ 1200 CTS

1

WEEP HOLE INSERTS @ 1200 CTS

Ens External Wall Detail of thickened wall_through pier

2

1 : 20

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

Ens External Wall Detail of thickened wall_through recess section 1 : 20

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:10 @ A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(R)

Job No:

D000005

Drawing No: Date:

CON - 604 11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

589

589


SARKING

589 TIMBER ROOF TRUSSES TO MANUFACTURE'S SPECIFICATIONS

COLORBOND FASCIA & GUTTER

589

4.5mm FC SHEET

PLASTERBOARD LINING CEILING INSULATION

FC SHEETING TO U/S OF EAVES

31x19 TIMBER TRIM

31x19 TIMBER TRIM BUILDING WRAP

WATER PROOF SEAL

HEBEL POWERPANEL

SILL TILE TO HAVE FALL TO OUTSIDE

90mm TIMBER FRAME R2 GLASSWOOL INSULATION APPLIED FINISH

150 90mm TIMBER FRAMES

64mm TOP HAT BATTEN

2

BUILDING WRAP WALL INSULATION

Eave drop off_Hebel panel_Tile roof 1 : 10

HEBEL POWERPANEL TILED FINISH

2579 HEAD HEIGHT

R2 GLASSWOOL INSULATION BUILDING WRAP APPLIED FINISH HEBEL POWERPANEL SKIRTING BOARD FLASHING

REINFORCED CONC. SLAB TO ENG. DETAILS

RETICULATION SYSTEM TO BE NO LESS THAN 50mm BELOW REBATE AND NO MORE THAN 100mm FROM OUTER FACE OF SLAB

WEEP HOLE INSERTS @ 1200 CTS

50 100

1

Bedroom 1 External Wall Detail 1 : 20

3

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

Slab edge_Hebel panel 1 : 10

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:10 @ A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(R)

Job No:

D000005

Drawing No:

CON - 605

Date:

11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

TILE ROOF AS SELECTED


WATERPROOF SEAL UNDER WINDOW

BUILDING WRAP HEBEL POWERPANEL 90mm TIMBER FRAME

140x38 REVEAL FRAME BY HRD

APPLIED FINISH

HEBEL POWERPANEL SILL APPROX 12° SLOPE, 20mm OVERHANG AT BOTTOM BUILDING WRAP

140x38 REVEAL FRAME BY HRD ACRYLIC COATING AS SELECTED R2 GLASSWOOL INSULATION

1

Sliding door head_Alfresco-Porch_Hebel panel 1 : 10

2

Window sill_Hebel panel 1 : 10

BUILDING WRAP APPLIED FINISH HEBEL POWERPANEL HEBEL PANEL BEYOND 64mm TOP HAT BATTEN SKIRTING TILE WEEPHOLE INSERT @ 1200 CTS MAX

MORTAR TILE BED

R2 GLASSWOOL INSULATION SKIRTING TILE

ALFRESCO/PORCH TILES

SKIRTING BOARD MORTAR TILE BED ALFRESCO/PORCH TILES

3

Slab edge_Alfresco-Porch_Sliding door sill

4

1 : 10

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

Slab edge_Alfresco-Porch 1 : 10

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:10 @ A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(R)

Job No:

D000005

Drawing No: Date:

CON - 606 11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

R2 GLASSWOOL INSULATION


PLASTERBOARD LINING

APPLIED COATING GARAGE DOOR TRACK INSTALLED AFTER SHUT DOWN OF SALES OFFICE

HEBEL POWERPANEL 4.5mm FC SHEET

PLASTERBOARD LINING

BUILDING WRAP

31x19 TIMBER TRIM 64mm TOP HAT BATTEN

6mm FC SHEET TO INSIDE OF FRONT WALL

64mm TOP HAT BATTEN

HEBEL POWERPANEL

PANEL LIFT GARAGE DOOR

ARCHITRAVE

31x19 STORM MOULD

APPLIED COATING

75 APPROX.

TEMPORARY 90mm STUD WALL CONSTRUCTED AFTER INSTALLATION OF GARAGE DOOR. TO BE REMOVED AFTER SHUT DOWN OF SALES OFFICE

GARAGE DOOR LINTEL DETAIL FOR HIPPED ROOF

1

1 : 20

PIVOT DOOR WATERPROOF MEMBRANE SKIRTING TILE RISER TILE

TIMBER PIVOT DOOR SILL SLAB STEP DOWN ALIGNS WITH REBATE

90mm TIMBER STUD

TILED PORCH

HEBEL POWERPANEL

APPLIED FINISH

64mm TOP HAT BATTEN

FLASHING

MIN. 75MM

3

2

Front Entry Pivot Door in Hebel Wall 1 : 10

Slab edge_Garage Hebel panel 1 : 10

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:10 @ A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(R)

Job No:

D000005

Drawing No:

CON - 607

Date:

11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

589


TILES NOTE: WHERE BATH HOB IS INSTALLED AGAINST AN ICHIJO i-SMART EXTERNAL WALL, RUN PIPE FROM MIXER TO SPOUT WITHIN HOB CAVITY & CHASE OUT STYRENE INSULATION TO INSTALL NOGGING & PIPE WORK ETC.

CHASE OUT INSULATION TO INSTALL PLUMBING

BATH SPOUT FC SHEET WATER PROOF MEMBER - 150mm HIGH MIN.

SEALANT

TILE TRIM AS SELECTED WATER STOP ANGLE TO SUITE (EXTENDS 10mm ABOVE TILING)

HEBEL BLOCKWORK

HEBEL BLOCKWORK

TILES 710

540 HIGH HEBEL BLOCKWORK (FROM SLAB)

INSULATION PIPE FROM MIXER TO BATH SPOUT TO RUN INSIDE BATH HOB CAVITY

100 MIN

WATERPROOF MEMBRANE

MORTAR BED

EQUAL

EQUAL

1

Bath hob_Hebel 1:5

COPYRIGHT

10A Valediction Road Kings Park NSW 2 1 4 8 Tel: (02) 8822 3111 Fax: (02) 9676 1414 w w w . i c h i j o . c o m . au

Note:

Note:

Please be advised that variances may occur in ceiling heights due to provisions for items such as electrical allowances, beams over, mechanical exhaust ducts and other unforeseen issues. Such issues may be resolved through the use of bulkheads, ceiling height adjustments, boxing of beams or any other satisfactory alternative. The builder reserves the right to co-ordinate all services at their discretion in order to ensure proper functionality of all systems throughout the planning and construction stages.

Ichijo Australia Pty Ltd reserves the right to modify features, specifications, plans , and/or prices without obligation. All square metreages are approximate. All Renderings are artist’s concept only, and may differ to displayed house.

All works and materials shall be in accordance with the relevant building code of Australia and the relevant Australian standards as stated in the general housing specification

All plans and drawings are subject of COPYRIGHT. Any attempt or actual infringement by using or reproducing or copying the same, wholly or in part, without prior written permission from ICHIJO Australia Pty Ltd will result in legal proceeding

Note:

Client:

Scale:

Ichijo Technological Homes Address:

Lot 14 Gormon Avenue, Kellyville, NSW 2155

Drawn By: Design: Facade:

1:10 @ A3

Council:

Council

MS

HRD No.:

N010014-2012

OASIS 26 DISPLAY(R)

Job No:

D000005

Drawing No: Date:

CON - 608 11/02/2013

Revision:

H

DO NOT SCALE DRAWINGS - USE FIGURE DIMENSIONS ONLY

NOTE: DETAILS FOR CAROMA 1525mm & 1675mm NEWBURY, VITALITY, ROYALE, VERONA, SHARK & STERLING BATHS ONLY. FOR OTHER BATH STYLES, BATH HOB MAY NEED TO BE MODIFIED TO SUIT.