2.7 LOW VOLTAGE
Low Voltage
A low voltage condition will typically cause an increase in current in the customer’s system. This higher current fl ow can cause increased heating of connectors and circuit breakers. Electronic devices are very sensitive to low voltage conditions. The more common characteristics are:
• Dim lights • Motors taking longer to start • Motors have less torque • Circuit breakers tripping for no apparent cause • Improper operation of certain electronic equipment
Possible Causes – Utility Side of the Meter
Consider these possible causes when the trouble investigator determines that the source of the low voltage problem is the responsibility of the utility to correct:
Poor Connections
Improper or corroded connections can cause a low voltage problem because the added resistance at the connector will create a voltage drop. This can be quite common on underground runs when the insulation is nicked during installation or by customer excavation activities. Checking voltage across the connector will demonstrate the integrity of the connection. If the voltmeter reads zero, the connector is fi ne. If a voltage is present, the connection needs to be replaced.
OFF
32
V
Poor connection detected with voltmeter CHAPTER TWO | INVESTIGATING CUSTOMER COMPLAINTS