Product Brochure
ABB Power Quality Solutions PCS100 UPS-I, 150 kVA to 2400 kVA UPS Industrial
Ideal where very deep sags or short term power outages are a problem
2 Product Brochure | PCS100 UPS-I Industrial
PCS100 UPS-I, 150 kVA to 2400 kVA Utility voltage sags, surges, and short outages are common and often cause electric and electronic equipment to self protect by switching off. When this occurs in a critical control operation it can cause the complete shutdown of a facility. The results of a shutdown maybe considerable - eg : product loss, damaged equipment, and lost production time. The PCS100 UPS-I is an ideal solution where very deep sags or short term power outages are a problem. Product overview The ABB PCS100 UPS-I is an off line UPS with short time rated energy storage system, coupled to an inverter to allow the downstream load to remain operational through short outages and very deep sags of up to 30 seconds duration.
User benefits - Provides protection against short outages and very deep sags - Protects against utility recloser events - Provides back-up during generator start-up following a utility supply failure - Allows process loads to ride through common power problems increasing yield, reducing product wastage and improving productivity Features - Very high efficiency (typically 99%) - Suited to industrial loads (motors, drives, transformers, tools) - Modular design providing high reliability and short repair times - Very high fault capacity compared with standard UPS solutions - Extensive range of voltages available - Small footprint design - Custom storage solutions available - Not just another data centre UPS but a product designed for the much more demanding requirements of industrial applications PCS100 Industrial UPS ( UPS-I )
The actual ride through time is dependent on the load and the capacity of the storage system, which can be batteries or ultra capacitors. The PCS100 UPS-I operates with an on-line like speed of performance due to the revolutionary fast utility disconnect. The modular inverter construction and fail safe electromechanical bypass (optional) provides exceptional reliability and system availability.
Single line diagram Power supply before PCS100 UPS-I
Power suppied by the PCS100 UPS-I
Power supply after PCS100 UPS-I
Customer supplied Fail-Safe Bypass (optional)
UPS-I
Utility supply Distribution transformer
Circuit breaker
Input
Utility disconnect
Protected load Output
Coupling transformer Inverter
Battery option Ultra cap storage
PCS100 UPS-I Industrial | Product Brochure 3
Technical specifications Environmental
Input Supply voltage
- 220V / 400V / 480V + 10%
Enclosure IP rating
- IP20
Supply frequency
- 50Hz or 60Hz
Standard colour
- RAL 7035
Power system type
- 3 phase TN
Pollution degree rating
- 2
Over voltage category
- III
Minimum operating temp
- 00C, 32oF
Fault capacity
- Model dependent
Maximum operating temp
- 400C, 104oF
Efficiency (208-220V)
- > 98%
Ultra capacitor & battery temp
- 15-250C, 59-77oF
Efficiency (400-480V)
- > 99%
Humidity
- <95% non-condensing
Output
2UCD301083-P_h
Energy storage - 150 kVA to 2400 kVA
DC nominal voltage
- 750Vdc
- - 0.5 to +0.9
Ride through time - ultracap
- 3 sec @ 0.8 PF ( typical )
Fault capacity
- 20 pu for 200 mil sec
Interface
Series protection
- Customer supplied
User interface
- Graphic display module touch panel
Overload capacity
- 150% for 1 min
Digital I/O
- 3 input, 4 outputs
Serial coms
- Ethernet & Modbus TCP (monitoring only)
Rating Displacement power factor Utility disconnect
- 30 sec @ 0.8 PF ( typical )
- battery
Standards
Inverter supply Transition disturbance
- ≤¼ cycle
IEC 62040-1 - General and safety requirements for UPS
Min output voltage
- 90% @ end of discharge
IEC 62040-2 - Electromagnetic compatibility (EMC)
Fault capacity
- 1.5pu
IEC 62040-3 - Method : specifying the performance and test requirements
Physical dimensions The PCS100 UPS-I consists of 4 sub-assemblies : 2. Utility disconnect 3. Inverter 4. Coupling transformer 5. Energy storage Quantity of Cabinets 220V (without storage)
1xA
1xA
1xB
1xA
1xA
1xB
1xA
1xB
600
1xB
1xD
750
1xB
1xD
1xC
1xA
1xB
1xA
1xC
1xD 1xD
Inverter
Inverter
450
Coupling transformer
1xB
1xB
Coupling transformer
1xB
1xB
Coupling transformer
1xB
300
Inverter
150
kVA
Battery
Storage option Ultra caps ( 3s)
Utility disconnect
400V (without Storage) Utility disconnect
Utility disconnect
480V (without Storage)
1xA
1xA
1xA
2xA
1xC
1xA
1xD
1xA
2xA
1xC
1xA
1xD
2xA
3xA
900
1xC
1xA
1xD
1xC
1xA
1xD
1xC
1xA
1xD
2xA
3xA
1200
1xC
2xA
1xD
1xC
2xA
1xD
1xC
2xA
1xD
2xA
4xA
1500
1xC
2xA
1xE
1xC
2xA
1xE
1xC
2xA
1xE
2xA
6xA
1800
1xC
2xA
1xE
1xC
2xA
1xE
3xA
6xA
2400
1xC
3xA
1xE
1xC
3xA
1xE
4xA
8xA
Cabinet dimensions
Contact us ABB Limited LV Power Converter products Discrete Automation and Motion www.abb.com/powerquality
E
804 1209
1609
2154
1209
1204
1609
1209 804
804 1209
2154
Front view
1209
1209
809
D
2154
804
C
2154
B
2154
Plan view
A
804
Type