Petri Torniainen, October 2009
New ABB industrial drive module ACS850-04 overview Š ABB Group October 18, 2012 | Slide 1
New industrial drive modules Industrial drives
Very flexible drives that are easy to be configured to meet the needs of various industries and applications
Designed especially for process industry segments such as:
© ABB Group October 18, 2012 | Slide 2
Pulp & paper
Mining
Cement
Chemical, oil & gas
Examples of applications:
Cranes
Winders
Mixers
New industrial drive modules For System Integrators and OEMs ACS850-04 is designed for fast, cost effective installation and integration into cabinets, therefore targeted for OEMs and System Integrators
Š ABB Group October 18, 2012 | Slide 3
New industrial drive modules Range Š ABB Group April 2009 | Slide 4
New industrial drive modules Range
Š ABB Group October 18, 2012 | Slide 5
New industrial drive modules Frames A & B Dim. in mm
364
3 Kg
93.5
I2N (A)
PN (kW)
Type
3
1.1
ACS850-04-03A0-5
3.6
1.5
ACS850-04-03A6-5
4.8
2.2
ACS850-04-04A8-5
6
2.2
ACS850-04-06A0-5
8
3
ACS850-04-08A0-5
197 (219)*
380
© ABB Group 5 Kg October 18, 2012 | 101 Slide 6
Frame A, IP20
Frame B, IP20
I2N (A)
PN (kW)
Type
10
4
ACS850-04-010A-5
14
5.5
ACS850-04-014A-5
18
7.5
ACS850-04-018A-5
*Depth in brackets = with control panel 274 (297)*
New industrial drive modules Frames C & D Dim. in mm
567
276 (298)*
I2N (A)
PN (kW)
Type
25
11
ACS850-04-025A-5
30
15
ACS850-04-030A-5
35
18.5
ACS850-04-035A-5
44
22
ACS850-04-044A-5
50
22
ACS850-04-050A-5
16 Kg
166
567
© ABB Group Kg October 18,22 2012 | 221 Slide 7
276 (298)*
Frame C, IP20
Frame D, IP20
I2N (A)
PN (kW)
Type
61
30
ACS850-04-061A-5
78
37
ACS850-04-078A-5
94
45
ACS850-04-094A-5
*Depth in brackets = with control panel
New industrial drive modules Frames E & E0 Dim. in mm
602
354 (376)*
276
35 Kg
I2N (A)
PN (kW)
Type
103
55
ACS850-04-103A-5
144
75
ACS850-04-144A-5
*Depth in brackets = with control panel
700
© ABB Group October 18,4432012 (465)* | Slide 8
67 Kg 312
Frame E0, IP20
Frame E, IP20 I2N (A)
PN (kW)
Type
166
90
ACS850-04-166A-5
202
110
ACS850-04-202A-5
225
110
ACS850-04-225A-5
260
132
ACS850-04-260A-5
290
160
ACS850-04-290A-5
New industrial drive modules Frame G Dim. in mm
1564
© ABB Group 568 Kg October 18,2052012 | Slide 9
562
Frame G, IP00 I2N (A)
PN (kW)
Type
430
200
ACS850-04-430A-5
521
250
ACS850-04-521A-5
602
315
ACS850-04-602A-5
693
355
ACS850-04-693A-5
720
400
ACS850-04-720A-5
New industrial drive modules Ratings Š ABB Group April 2009 | Slide 10
New industrial drive modules Ratings
Currents are expressed in Amperes
I2N rated current available continuously without overloading
ILd continuous current in light-duty use
IHd continuous current in heavy-duty use
IMax maximum output current
© ABB Group October 18, 2012 | Slide 11
New industrial drive modules Ratings Supply voltage : 3-phase 380 V to 500 V
Š ABB Group October 18, 2012 | Slide 12
New industrial drive modules Hardware Š ABB Group April 2009 | Slide 13
New industrial drive modules Hardware Optimized for cabinet installation Bus cc
© ABB Group October 18, 2012 | Slide 14
Compact, narrow design
Side-by-side mounting
DIN-rail mounting (frames A and B )
Power terminals on top (up to 45 kW) enabling compact and EMC compliant installation
Motor connections at the bottom of the drive
Plug-in terminals
I/O
Power terminals (frames A and B )
New industrial drive modules Hardware
© ABB Group October 18, 2012 | Slide 15
2 option slots for I/O extensions and encoders
1 dedicated slot for fieldbus modules
Coated boards as standard
Fan supervision (frames A to D)
New industrial drive modules Hardware Removable memory unit
© ABB Group October 18, 2012 | Slide 16
Stores the complete software and parameter settings
Makes the recommissioning of the unit fast and easy
Gives a possibility for software and parameter configuration at e.g. ABB or OEM workshop before sending it to customer
Easy to install (only a screwdriver is needed !)
New industrial drive modules EMC filters C2 and C3 (1st and 2nd environment)
C3 filter, frames A-B
C3 filter, frames C – G
Optional built-in EMC filter
In frames C and D possibility to retrofit afterwards (a separate “lid” in the cover)
C2 filter, frames A – D
© ABB Group October 18, 2012 | Slide 17
External filter connected directly to the power terminals
External filter
C2 filter, frames E0 & E
Optional built-in EMC filter
New industrial drive modules Chokes for harmonic filtering
Frames A and B: optional, external, AC side
Frames C and D: standard, built-in, DC side
Frames E0,E and G: standard, built-in, AC side
© ABB Group October 18, 2012 | Slide 18
New industrial drive modules Common DC bus
R
R
© ABB Group October 18, 2012 | Slide 19
R
R
Standard ACS850 feature
Allows energy savings due to the capability to use regenerated energy from a motor into another
Possibility to regenerate energy from one or several ACS850 to other ACS850 drives in the DC link
Supports the management of one or several braking choppers (integrated in the drive)
R
R
New industrial drive modules Dynamic braking options Braking choppers
In a common DC system several choppers can operate simultaneously
Braking resistors
Available for different kind of pulse duty performance
Equipped with a thermal sensor as standard
Option / Frame
A-D
E0-G
Built-in braking chopper
Standard
Option (+D150)
Braking resistor
External option
External option
© ABB Group October 18, 2012 | Slide 20
New industrial drive modules Hardware configuration Š ABB Group April 2009 | Slide 21
New industrial drive modules Standard configuration Without control panel
Š ABB Group October 18, 2012 | Slide 22
New industrial drive modules Assistant control panel , option +J400 Assistant control panel
© ABB Group October 18, 2012 | Slide 23
Option + J400
With real time clock
Incl. control panel holder in the unit
Can be attached either to the control unit cover or to the cabinet door
New industrial drive modules Control panel holder, option +J414 Control panel holder on the unit
© ABB Group October 18, 2012 | Slide 24
Option +J414
Incl. control panel holder
No control panel
The dummy control panel has 2 LEDs that indicate the status of the drive
New industrial drive modules Control panel and a door mounting kit, option +J410 Control panel holder on the door
© ABB Group October 18, 2012 | Slide 25
Includes control panel
Includes control panel holder
Includes IP54 kit
Includes 3 meter cable
No control panel holder in the unit
New industrial drive modules No control unit cover, option +0C168 No control unit cover
© ABB Group October 18, 2012 | Slide 26
Option + 0C168
No control panel holder in the unit
No control panel
New industrial drive modules Safe Torque-Off Š ABB Group April 2009 | Slide 27
New industrial drive modules Safe Torque-Off Safe
Torque-Off (STO) as standard
SIL 3 (IEC 61508) / Safety category 4 (EN954-1)
ACS850-04
© ABB Group October 18, 2012 | Slide 28
New industrial drive modules Operating conditions Š ABB Group April 2009 | Slide 29
New industrial drive modules Operating conditions
Temperature:
-10°C to 55°C
G frame up to 50°C
Derating above 40°C
Relative humidity:
Altitude:
Up to 4000 m
At 500V up to 2000 m
1%/100 m derating above 1000m
Vibration:
© ABB Group October 18, 2012 | Slide 30
Max. 95%, no condensation allowed
Class 3M4 acc. to EN60721-3-3
Climatic / environmental conditions:
Class 3K3, 3C2 acc. to EN60721-3-3
New industrial drive modules Cables Š ABB Group April 2009 | Slide 31
New industrial drive modules Cable lengths
Max. length of the STO cable is 25 m
Longer cable can be made by using extra relays
Max. length of the D2D link is 50 m
© ABB Group October 18, 2012 | Slide 32
New industrial drive modules Interfaces Š ABB Group April 2009 | Slide 33
New industrial drive modules Control board JCON-11 Pin XPOW
Name 1 24Vin 2 GND
XRO1
1 RO1NO 2 RO1COM 3 RO1NC
XRO2
4 RO2NO 5 RO2COM 6 RO2NC
XRO3
7 RO3NO 8 RO3COM 9 RO3NC
XD24
1 2 3 4
24VD 24VD DGND DGND
XDI
1 2 3 4 5 6 A
DI1 DI2 DI3 DI4 DI5 DI6 DIIL
XDIO
XAI
XAO
XD2D
1 DIO1 2 DIO2 1 VREF+ 2 VREF3 AGND 4 AI1+ 5 AI16 AI2+ 7 AI2AI SEL JUMPER AI1 AI2 1 AO1+ 2 AO13 AO2+ 4 AO2Term. Jumper 1B 2A 3 BGND
Control interface 1. Control voltage supply
External supply (24VDC) input for the control unit (to be used, if external power supply is required)
2. Digital I/O
6xDI (DI 6 can be used also as a thermistor input), 2xDI/O (can be used also for pulse train inputs or outputs, max 32 kHz; DI/O can be separated as separate group and used either as a npn/pnp input), 3xRO
3. Analog I/O
2xAI (mA or V), 2xAO (1xmA)
4. DIL input
Drive interlock input
5. RS-485 link
Galvanically isolated, can be used for D2D or Modbus
6. Safe Torque Off (STO)
Designed for Safety Integrity Level 3 (SIL 3) acc. to IEC 61508 and Safety Category 3 acc. to EN 954-1
7. User interface (HMI)
PC-tools and control panel connection (RJ45). Can be used also as a Modbus link for monitoring
Š ABB Group Removable October 18,8. 2012 | memory unit (RMU) Slide 35 XSTO
1 2 3 4
OUT1 OUT2 IN1 IN2
Complete drive configuration and settings are stored in the memory unit.
New industrial drive modules Drive to drive link
Fast communication between drives
Baud rate: 8 Mbit/s
Cable length: ~ 50 m
RS-485
Flexible data communication between drives
Master/follower communication
© ABB Group October 18, 2012 | Slide 36
1 Master – several followers
Multicast communication
Master/follower(s)
Follower/follower(s)
New industrial drive modules Optional I/O Š ABB Group April 2009 | Slide 37
New industrial drive modules Option slots 1 and 2 Options
Data
Install in
Analogue & digital extension
1
FIO-01
4xDI/O, 2xRO
FIO-11
3xAI (mA/V), 1xAO (mA), 2xDI/O
FIO-21
1xAI (mA/V), 1xAO (mA), 1XDI, 2xRO
Slot 1 or 2
Feedback interface
2
Š ABB Group October 18, 2012 | Slide 38
FEN-01
2 inputs (TTL incremental encoder), 1 output *
FEN-11
2 inputs (SinCos absolute, TTL incremental encoder), 1 output *
FEN-21
2 inputs (Resolver, TTL incremental encoder), 1 output*
FEN-31
1 input (HTL incremental encoder), 1 output
Slot 1 or 2
* When this module is used, the lower part of the control unit cover cannot be used
New industrial drive modules Option slot 3 Options
Data
Install in
Communication FPBA-01
PROFIBUS-DP, DPV0/DPV1
FCAN-01
CANopen
FDNA-01
DeviceNet
FENA-01
EtherNet/IP Modbus TCP Later on also PROFINET I/O
FSCA-01
Modbus
FLON-01
LONWorks (comes later)
Slot 3
3
Š ABB Group October 18, 2012 | Slide 39
New industrial drive modules Software Š ABB Group April 2009 | Slide 40
New industrial drive modules Software - DTC DTC with enhanced features
© ABB Group October 18, 2012 | Slide 41
Standard sw supports asynchronous motors and permanent magnet motors
Output frequency up to 500 Hz
Low motor noise mode
Improved stand still ID run
New industrial drive modules Software LOC
ASSISTANTS
2
Start-up Assistant
Easy start-up
Macros: preprogrammed parameter settings
Start-up Assistant
Motor Set-up Application Speed control EXT1
Speed control EXT2 EXIT
16:31
SEL
© ABB Group October 18, 2012 | Slide 42
Easy use
Intuitive parameter structure
Short/long parameter menus
I/O “mapping”
List of changed parameters
Flexibility
Extensive parameter settings
Limited block programmability as standard
New industrial drive modules Software – Backup and restore LOC
MAIN MENU
PAR BACKUP I/O SETTINGS REF EDIT CANCEL
16:31
EDIT
Panel backup/restore functionality
Creating and uploading the backup file from drive to panel
Showing backup file info
LOC
PAR BACKUP
MAKE BACKUP TO PANEL
(1) Restoring all parameters
EXIT LOC
16:31
SEL
PAR BACKUP
SHOW BACKUP INFO RESTORE PARS ALL RESTORE PARS NO-IDRUN RESTORE PARS IDRUN RESTORE ALL USER SETS
© ABB Group EXIT October 18, 201216:31 | Slide 43
SEL
Versions etc. Incl. ID Run and motor data
(2) Restoring all parameters except ID Run and motor data
(3) Restoring only ID Run and motor data
(4) Restoring all user sets
New industrial drive modules Software – Fault loggers LOC
FAULT LOGGER
36: LOCAL CTRL LOSS 06.11.08 09:59:27 15: SUPPLY PHASE 17: ID-RUN FAULT 31: SAFE TORQUE OFF EXIT 16:31 DETAIL LOC
Fault logger can hold the information of 10 latest faults.
Fault information includes:
LOCAL CTRL LOSS
TIME 9:59:27 FAULT CODE 36 FAULT CODE EXTENSION EXIT LOC
16:31
DIAG
PAR BACKUP
Check parameter ’30.03 Local ctrl loss’ setting. Check PC tool or panel connection.
© ABB Group EXIT October 18, 2012 16:31 | Slide 44
OK
Fault message + fault code
Time stamp
Fieldbus fault code
Status word
Output frequency, speed estimated, torque, current, DC voltage, torque limit status
But no warnings
New industrial drive modules Software – Short/long parameter menus Short/long parameter menus
Only the most important parameters for commissioning are shown as a default parameter set (21 parameter groups)
User can freely activate the long menus in order to see all parameters
P16.15: Load short/Load long
LOC
1601 1602 1603 1615
PARAMETERS
Local lock Parameter lock Pass code Menu set sel No request EXIT 16:31 EDIT
© ABB Group October 18, 2012 | Slide 45
LOC
PAR EDIT
1615 Menu set sel
Load long
[2] CANCEL
16:31
SAVE
New industrial drive modules Software – List of changed parameters LOC
MAIN MENU
CHANGED PAR FAULT LOGGER LOC CHANGED PAR 1616 Menu set active TIME & DATE 2005 Maximum current EXIT
LOC
16:31 ENTER 1.70 A 2202 Acc time1 2203 Dec time1 EXIT 16:31
List of changed parameters (panel view ”CHANGED PAR”)
List of parameters that have been changed from default
Parameter values in changed parameter list can be modified
EDIT
MAIN MENU
PAR CHG LOG PARAMETERS LOC LAST CHANGES 2001 Maximum speed ASSISTANTS 1650 rpm EXIT
16:31
ENTER 28.10.08 13:50:16
EXIT
16:31
© ABB Group October 18, 2012 | Slide 46
List of changed parameters (panel view ”PAR CHG LOG”)
List of 10 latest changes with date and time stamps
Parameter values in parameter changed log can be modified
EDIT
New industrial drive modules Software – I/O mapping
I/O settings info in control panel shows usage of I/O
LOC
The connections between I/O and different software functions are shown.
When selecting channel name (e.g. DI1) information about channel’s source is displayed.
When selecting parameter (e.g. 1002 Ext1 start in1) parameter value can be changed. LOC
MAIN MENU
I/O SETTINGS REF EDIT LOC I/O SETTINGS DRIVE INFO Analog outputs EXIT 16:31 Analog inputs Digital I/Os Digital inputs Relay outputs EXIT 16:31
ENTER
© ABB Group SEL October 18, 2012 | Slide 47
I/O SETTINGS
DI1 1002 Ext1 start in1 DI2 DI3 1010 reset sel LOC FaultI/O SETTINGS EXIT 16:31 EDIT DI1 1002 Ext1 start in1 DI2 DI3 1010 Fault reset sel EXIT 16:31 EDIT
LOC
I/O INFO
NUM OF I/O ITEMS 1 SLOT NUMBER 0 LOC NUMBER PAR EDIT NODE 1002 Ext1 start in1 EXIT 16:31
DI1
[P.02.01.00] CANCEL 16:31
SEL
New industrial drive modules Software – Autotuning
© ABB Group October 18, 2012 | Slide 48
Autotuning updates automatically new tuning values for speed controller
Proportional gain
Integration time
Four possible tuning modes :
Smooth (slow response)
Middle
Tight (fast response)
User (bandwidth, damping)
Speed controller autotuning runs the specific speed curve for finding the tuning values
New industrial drive modules Software – Time levels Extended speed controller functionality
Speed controller at 500 µs time level
Reference handling at 2 ms time level
500 µs
© ABB Group October 18, 2012 | Slide 49
New industrial drive modules Software – Load analyzer Consists of 2 independent loggers: 1) Amplitude logger (AL): 200 ms sampling time interval. 2) Peak value logger (PVL): records peak values of a selected signal.
The data of the two loggers can be restored after a power failure as it is stored to non-volatile memory
© ABB Group October 18, 2012 | Slide 50
Percentage of operating time
When the new peak value is detected, also some other actual signals (speed, current, dc voltage) are saved.
10 %
20 %
30 %
40 %
50 %
60 %
70 %
Amplitude logger range
80 %
90 %
100 %
New industrial drive modules Software – Maintenance assistance
Reminds the user of the need of maintenance
6 individual counters – parameter group 44
Gives alarm for needs such as : cooling fan change, cabinet fan change, DC capacitor change, motor bearings…
© ABB Group October 18, 2012 | Slide 51
New industrial drive modules Software – Energy efficiency counter Energy savings calculation
As an output you can get:
Total energy savings in kWh
Total energy savings in euro or in other currency
Total energy savings in CO2
Energy optimizer
Reduces motor magnetizing current at low mechanical loads
© ABB Group October 18, 2012 | Slide 52
New industrial drive modules Software - Timers
4 timers can be used to control the drive (like drive start/stop command)
Start/Stop daily
Start/Stop weekly
© ABB Group October 18, 2012 | Slide 53
New industrial drive modules PC tools Š ABB Group April 2009 | Slide 54
New industrial drive modules DriveStudio Commissioning, tuning and monitoring tool
© ABB Group October 18, 2012 | Slide 55
Parameters setting and signal monitoring
Data logger and on-line signal monitoring
Backup and restore
Context sensitive helps
Start-up and Diagnostic Assistants
New industrial drive modules Drive SPC Programming tool
© ABB Group October 18, 2012 | Slide 56
Drive Solution Program composer
For function block programming
PLC functions library
Interface to Drive functions and parameters
New industrial drive modules DriveSize
Š ABB Group October 18, 2012 | Slide 57
New industrial drive modules Documentation Š ABB Group April 2009 | Slide 58
New industrial drive modules Documentation
© ABB Group October 18, 2012 | Slide 59
Standard with every drive :
Quick installation and start-up guides
CD with full documentation
Full paper format manuals available as an option
To be ordered as a separate item
Many customers are serial manufacturers or users and do not need / want piles of paper manuals