New VRF FSV Systems - Full Version

Page 1

New VRF FSV SyStemS New New VRF VRF FSV FSV SyStemS SyStemS 2012 2012 2012 // 2013 2013 / 2013 VRF FSV SYSTEMS 2013 / 2014

EVERy BUILDING MATTERS EVERy EVERy BUILDING BUILDING MATTERS MATTERS


PANASONIC AIR CONDITIONING DESIGNED TO CARE FOR YOUR PROJECTS.

With more than 30 years of experience, exporting to more than 120 countries around the world, Panasonic is unquestionably one of the leaders in the air conditioning sector. The company is also a world leader in innovation as it has filed more than 91,539 patents to improve its customers’ lives. Moreover, Panasonic is determined to remain at the forefront of its market. In all, the company has produced more than 200 million compressors and its products, particularly residential air conditioners, now hold the No. 1 market share in Japan and other major countries in Asia. You can be assured of the extremely high quality of Panasonic’s air conditioners. This wish to excel has made Panasonic the international leader in air conditioning solutions. The company’s industrial capacity and firm commitment to the environment has enabled it to open new avenues of research and to develop innovative technologies to enrich customers’ way of life. Panasonic offers a range of turnkey air conditioning solutions for homes, medium-sized buildings such as offices and restaurants, and large-scale buildings. These offer maximum effectiveness, comply with the strictest environmental standards and meet the most avant-garde construction requirements of our time. At Panasonic we know what a great responsibility it is to install cooling and heating systems. Because offering you the best solutions in cooling and heating matters.

EVERY BUILDING MATTERS

2


CONTENTS 02

Introduction

04

Panasonic New FSV Systems

06

2-WAY FSV ME1 Series

20

2-WAY mini-FSV LE1 Series

28

3-WAY FSV MF2 Series

40

FSV Indoor Units

42

Product Range

44

U1 Type / 4-Way Cassette / Semi Concealed Cassette

48

Y1 Type / 4-Way Cassette 60 X 60 / Mini Semi Concealed Cassette

50

L1 Type / 2-Way Cassette

52

D1 Type / 1-Way Cassette / Semi Concealed Slim Cassette

54

F2 Type / Low Silhouette Ducted

58

M1 Type / Slim Low Static Ducted / Concealed Duct

60

E1 Type / High Static Pressure Ducted / Concealed Duct High-static Pressure

62

T1 Type / Ceiling / Floor Ceiling Mounted

64

K1 Type / Wall Mounted

68

P1 Type / Floor Standing

70

R1 Type / Concealed Floor Standing

72

FSV Controllers

74

Individual Control Systems

76

Centralised Control Systems

78

Web Interface Systems

80

P-AIMS

82

T10 Terminals for External Control

83

Serial Interface for 3rd Party External Controller

84

Interfaces for External Control

85

Serial Interface for LonWorks Network

86

Controller External Dimensions

88

VRF Renewal

92

Panasonic Design Support Software 3


New FSV Systems FSV systems are designed for energy savings, easy installation, and high efficiency. Ever evolving, Panasonic uses advanced technologies to meet the requirements of diverse situations and contribute to the creation of comfortable living spaces.

NEW

2-WAY FSV ME1 Series Newly designed next generation VRF! Reverse Cycle Heat Pump •Top class EER = 4.04 / COP = 4.56 (in the case of 8 HP) •Wide range of systems up to 60 HP •Longer max piping length (up to 1000 m) •Increased max number of connectable indoor units (up to 64) •External static pressure increased to a high 80Pa •Cooling operation is possible when outdoor temperature as high as 46˚C •Extended operating range to provide heating at outdoor temperature as low as -25˚C •Suitable for renewal projects

Anti-corrosion model is available.

NEW

High COP Setting Series Enables further energy saving Reverse Cycle Heat Pump •Wide range of system up to 48 HP •High COP especially large capacity zone (38 HP=COP:4.08)

HIGH COP SETTING MODEL

Benefits Ease of installation

Simple to commission

Simple to design

Accurate capacity control

R410A has a higher operating pressure with a lower pressure loss than previous refrigerants. This enables smaller pipe sizes to be used and allows reduced refrigerant charges. Panasonic recognises that designing, selecting and preparing a professional VRF quotation can be a time consuming and costly process, especially as it is often as a speculative exercise. We have a proprietary design software which is quick and easy to use and produces a full schematic layout of pipework and controls, detailed material listing and performance data.

Easy to control

A wide variety of control options are available to ensure that FSV systems provide the user with flexible degree of control, from simple room controllers to state of the art Building Management System (BMS) control.

4

Simple set-up procedures including automatic address setting of connected indoor units enables configuration setting to be made from an outdoor unit or via remote controller. To ensure that the compressor capacity is matched to building load as accurately and efficiently as possible, Panasonic has designed its range of 2-WAY / 3-WAY FSV systems to operate with DC inverter and high-efficiency fixed speed compressors. The system selects the most efficient compressor to operate by dynamically monitoring the building load and choosing the best compressor combination to run.


2-WAY mini-FSV LE1 Series For small-scale commercial and residential use Reverse Cycle Heat Pump 1 phase and 3 phase options •Applicable to both single and three phase power supplies •Top-class EER: 3.76 / COP:4.21 (In case of 4 HP) •Cooling operation is possible up to 46°C outdoor temperature •Heating operation is possible when outdoor temperature as low as -20°C •9 units connectable to one outdoor unit (in the case of 6 HP) •Piping length: 120m (Total piping length: 150m)

Industry Top Class EER/COP

3-WAY FSV MF2 Series For simultaneous heating and cooling operation Simultaneous Heating and Cooling •COP of 4.77, one of the top class in the industry •Simultaneous cooling or heating operation for up to 40 indoor units •Realization of the small installation space, top class in the industry •Rotation operation function and back-up operation function provided

Easy to position

Heat Recovery Type

Easy to maintain

The compact design of the FSV outdoor units enables 8 HP to 12 HP to fit into a standard lift and are easy to handle and position when on site. Space-saving and modular in design ensures building appearance can be maintained.

Each system allows the use of prognostic and diagnostic controls routines, from refrigerant charge control to complex fault code diagnostics, all designed to expedite maintenance calls and reduce unit down time.

Discharge air temperature control

Lower running and life cycle costs

Panasonic ducted units offer the unique advantage of being able to control discharge air temperature for accurate room temperature control, and to reduce cold drafts at heating operation. This is achieved without any extra controls or wiring to each unit.

Wide selection and connectability

With a selection of 12 indoor model types, FSV systems are the ideal choice for multiple small capacity indoor unit installations, with the ability to connect up to 64 indoor units for 2-way ME1 series and up to 40 indoor unit for 3-way MF2 series.

Panasonic FSV is amongst the most efficient VRF systems in the market. The systems are also designed to make sure that we reduce the running cost of each system by using our unique road map control routine to ensure that the most efficient combination of compressors are running at any one time. Improved defrost sequencing also reduces running cost by defrosting each outdoor coil in turn when conditions allow.

5


High-efficiency & large-capacity VRF system

2-WAY FSV ME1 Series Next generation VRF

Large capacity VRF systems using advanced R410a technology. • Compact casing (8~12 HP)

• Increased Max no. of connectable I_U up to 64 units

• Bigger capacity in one casing (max 20P)

• Increased high external static pressure up to 80 Pa

• Wider range of system (Max 60 HP)

• Extended operating range to provide heating at

• Longer Max piping length up to 1000 m

outdoor temperature as low as -25˚C

• Increased connectable I_U/O_U cap. ratio up to 200%

• Cooling is possible as high as 46˚C

• Demand response ready (peak cut)

• Suitable for renewal projects (Refer to technical data book) • High COP mode available by setting • Anti-corrosion treatment model is available

6


FSV ME1 Series

Energy-saving concept.

The use of energy saving design for the structure of fans, fan motors, compressors and heat exchangers resulted in high COP value which ranked as one the top class in the industry. In addition, use of highly efficient R410A refrigerant reduces CO2 emission and lowers operating costs.

4 5

1

Panasonic Inverter Large-capacity inverter compressor is now available up to max 10 HP. The inverter compressor is superior compressor in performance with improved partial-load capacity.

2 Constant-speed compressor

6 3

3 Accumulator

8 2 4 Fan guard

1

High-performance

5 fan with a new

shape

7

Heat exchanger

6 copper tubes, heat

exchanger fins

A constant-speed, large-capacity scroll compressor has been newly developed. Two compressors can be configured up to 16HP whilst three compressors can be configured up to 20 HP. The accumulator capacity has been increased to maintain compressor reliability because of the increased refrigerant quantity, which required an extended max piping length. Furthermore, the refrigerant pressure loss was reduced, which contributes to an improved operating efficiency. The fan wire guard has been newly designed. This results in a reduced air resistance and ventilation noise. Fan rotational efficiency has been increased as the fan can operate on constant airflow even at high external static pressure. Heat exchangers have been redesigned with increased surface area to improve heat transfer and efficiency.

7 Sub-cooling

Large capacity outdoor unit utilizes double piping with top grade tubes to improves heat transfer efficiency.

8 Oil separator

Centrifugal separator is used to improves oil separation efficiency and reduce refrigerant pressure loss.

circuit

7


High-efficiency & large-capacity VRF system

2-WAY fSV ME1 Series A large number of indoor units can be connected

Up to 64

The operation efficiency has been improved using highly efficient R410A refrigerant, new DC inverter compressor, new DC motor and new design of heat exchanger.

Indoor Units Connectable!*

*Maximum number of indoor units depends on outdoor unit capacity.

Increased piping length for greater design flexibility Adaptable to various building types and sizes Actual piping length : 180m Max piping length : 1000m

System difference of elevation:

50m*1

Actual length:

15 m

*1: 40 m if the outdoor unit is below the indoor unit.

180 m

Difference in elevation between indoor units:

Max. total length:1,000m

Connectable indoor/outdoor unit capacity ratio up to 200% fSV systems attain maximum indoor unit connection capacity of up to 200 % of the unit’s connection range, depending on the outdoor and indoor models selected. So for a reasonable investment, fSV systems provide an ideal air conditioning solution for locations where full cooling/heating are not always required.

SyStEm / HP 8

10 12 14 16 18 20 22 24 26 28 30 32 34

MNcIU : 130%

13

16

19

23

26

29

33

36

40

43

47

50

53

56

MNcIU : 200%

20

25

30

35

40

45

50

55

60

64

64

64

64

64

SyStEm / HP 36 38 40 42 44 46 48 50 52 54 56 58 60 MNcIU : 130%

59

64

64

64

64

64

64

64

64

64

64

64

64

MNcIU : 200%

64

64

64

64

64

64

64

64

64

64

64

64

64

MNcIU : Maximum Number of Connectable Indoor Unit Note: If more than 100% indoor units are operated with a high load, the units may not perform at the rated capacity. for the details, please consult with an authorized Panasonic dealer.

Excellent energy saving The operation efficiency has been improved using highly efficient R410A refrigerant, new DC inverter compressor, new DC motor and new design of heat exchanger.

8

4.6 4.5 4.4 4.3 4.2 4.1 4.0 3.9 3.8 3.7 3.6 3.5 3.4 3.3 3.2

4.6 4.5 4.4 4.3 4.2

4.56

4.10

4.04

4.10

4.21

3.85 3.60

3.61

3.86

3.82

3.60 3.50 3.36

3.33

8 HP 10 HP 12 HP 14 HP 16 HP 18 HP 20 HP

8 HP 10 HP 12 HP 14 HP 16 HP 18 HP 20 HP

COOLING

HEATING

HIGH COP SETTING MODEL

4.45

4.45

4.52 4.41

4.39

4.50


FSV ME1 Series

Difference between max. and min. length after first branch can be max 50 m. Up to 64 units can be connected to one system. flexible piping layout makes it easier to design systems for locations such as train stations, airports, schools and hospitals.

Max. 180 m

Max. 50 m Conventional model

ME1

Extended operating range Heating operation range: Extended heating operation range enables heating even when outdoor temperature as low as -25˚C. Using a wired remote control, indoor heating temperature range can be set from 16˚C to 30˚C.

Outside air temperature (˚C WB)

2WAY FSV ME1

-25

-20

-15

-10

-5

0

NEW

5

10

16

20

Outside air temperature (˚C DB)

Cooling operation range:

2WAY FSV ME1

-10˚C DB to +46˚C DB

-10

-5

0

5

10

15

20

25

30

35

40

46

Compact design New ME1 series has reduced the installation space required by 1 chassis for sizes up to 20 HP. 8-12 HP are able to fit inside a lift for easy handling at site.

Weight Weight

421kg kg

88-12 -12 HP HP

(Unit: (Unit: mm) mm)

930 930

18-20 18-20 HP HP

H H 1758 1758

1540 1540 1700 1700 Required Required installation installation space space

1530 1530

W W 770 770

D D 930 930

Newly designed fan Optimized air flow

Noise reduction

Newly designed fan and bell-mouth reduces stress to fan by dispersing fast wind speed. Thus, lower air resistance results in lower energy consumption.

The turbulent flow (blue part) can be suppressed and the noise can be reduced. Even though the high speed circulation is utilized, the noise level is at same level as usual. 9


High-efficiency & large-capacity VRF system

2-WAY FSV ME1 Series High external static pressure Customized setting at site allows all models to provide up to 80Pa due to newly designed fan, fan guard, fan motor and casing. The flexible design comes with a air discharge duct to avoid a reduction in performance due to shortcut of air circulation. The new feature allows the outdoor unit to be installed inside verandas on every floor of the building. High static pressure

80 Pa Fan Guard

Fan

Fan Motor and Casing

Extended compressor life by uniform compressor operation times Compressors with histories showing shorter run times are selected first, ensuring equal wear and tear across all units and extended working life for the system.

Total run-time of compressors are monitored by a built-in microcomputer, which ensures that operation times of all compressors within the same refrigerant circuit are balanced.

System example A,C: DC inverter compressor B,D: Constant speed compressor

A B

C D

50h

60h 10h

30h

Load increase

A B

Load increase

C D

A B

C D

Load increase

A B

C D

Example: Time leveling of compressor operating hours

D C 1

A C 2

D A A C C C 3 4 5

Operating hours (h)

10 5 0

In case of the above graph, compressor drives from DC

1

AC

2

DC

3

AC

4

AC

5

Compressor

3

5

2

4

1

Automatic backup operation in the case of compressor and outdoor units malfunction (Except for 8 HP single unit installation)

Even if either Fan motor or Sensors are failed,

Even if a compressor is failed ,

Even if a compressor at single system is failed ,

NEW function

The other outdoor unit can keep running

The other compressor can keep running

*Backup operation is adopted for emergency case. If error message is displayed, please contact to a service office.

Backup operation can be done. 10


FSV ME1 Series

Demand response Featuring inverter control technology, FSV systems are demand response ready. With this control, power consumption at times of peak load can be set in three steps to deliver optimum performance. This helps to reduce annual power consumption with minimal loss in comfort.

DRED

(Demand controller) Relay contact point:No voltage relay Current input is DC 24 V 10 mA DRM1 DRM2 DRM3

NEW

Simple demand response with the CZ-CAPDC4 Demand control terminal is available to control

Terminal block Outdoor unit

Demand Response Signal

Power Input

DRM 1

0%

DRM 2

* CZ-CAPDC4 is required as an option * Complies with AS 4755 of Australia

Flexible Demand Response with the CZ-CAPDC2 *1

C

DRM 3

Power input

Normal operation

Set point

Setting is possible as 0% or in the range from 40 to Time

*1 Para I/O unit for outdoor unit (CZ-CAPDC2) is required to input the signal.

Power input Level 1 Level 3

Anti-corrosion model available

0% (Always in stop condition)

Outer body Electric box

Screws possibility of rust developing. For details concerning unit installation and maintenance, please consult with an authorized dealer.

Possible to change 40-100%

Fan Fan motor

[On Demand Production]

An anti-corrosion model is available for use in coastal areas and other locations where sea air can easily cause salt damage to outdoor units. As well as the heat exchanger, various other parts are specially treated to provide exceptional durability.

100% (Preset)

Level 2

Heat exchanger (fins, tube, tube panel)

Accumulator Refrigerant pipe port

11


2-WAY 2-WAY 2-WAY FSV FSV FSV ME1 ME1 ME1 Series Series Series Appearance Appearance

HP

HP HP

8

8 8

10

10 10

12

12 12

14

14 14

16

16 16

18

18 18

20

20 20

22

22 22

24

24 24

26

26 26

28

28 28

Modelmodel Model namename name

U-14ME1R8 U-14mE1H8 U-14ME1R8 U-14mE1H8 U-14mE1H8 U-16mE1H8 U-14ME1R8 U-14ME1R8 U-14ME1R8 U-14ME1R8 U-16ME1R8 U-16ME1R8 U-8ME1R8 U-8mE1H7 U-8ME1R8 U-10ME1R8 U-10mE1H7 U-10ME1R8 U-12ME1R8 U-12mE1H8 U-12ME1R8 U-14ME1R8 U-14mE1H8 U-14ME1R8 U-16ME1R8 U-16mE1H8 U-16ME1R8 U-18ME1R8 U-18mE1H8 U-18ME1R8 U-20ME1R8 U-20mE1H8 U-20ME1R8 U-8 ME1R8 U-8mE1H7 U-8 ME1R8 U-10ME1R8 U-10mE1H7 U-10ME1R8 U-12ME1R8 U-12mE1H8 U-12ME1R8 U-12ME1R8 U-12mE1H8 U-12ME1R8

PowerPower supply supply

380/400/415V 400/415V 400/415V 3phase/50, 3phase/50, 60Hz 60Hz

Cooling Cooling Capacity Capacity Heating Heating EER /EER COP/ COP

kW

kW 22.4 22.4

28.0 28.0

380/400/415V 380/400/415V 3phase/50Hz 3phase/50Hz 33.5 33.5

40.0 40.0

45.0 45.0

50.0 50.0

56.0 56.0

61.5 61.5

68.0 68.0

73.0 73.0

78.5 78.5

76,500 95,600 95,600 114,300 114,300136,500 136,500153,600 153,600170,600 170,600191,100 191,100209,900 209,900232,100 232,100249,100 249,100267,900 267,900 BTU/h BTU/h 76,500 kW

kW 25.0 25.0

31.5 31.5

37.5 37.5

45.0 45.0

50.0 50.0

56.0 56.0

63.0 63.0

69.0 69.0

76.5 76.5

81.5 81.5

87.5 87.5

BTU/h BTU/h 85,300 85,300 107,500 107,500128,000 128,000153,600 153,600170,600 170,600191,100 191,100215,000 215,000235,500 235,500261,100 261,100278,200 278,200298,600 298,600

Cooling Cooling

W/W W/W 4.04 4.04

3.60 3.60

3.61 3.61

3.60 3.60

3.36 3.36

3.50 3.50

3.33 3.33

3.75 3.75

3.60 3.60

3.60 3.60

3.47 3.47

Heating Heating

W/W W/W 4.56 4.56

4.10 4.10

4.10 4.10

4.21 4.21

3.85 3.85

3.86 3.86

3.82 3.82

4.34 4.34

4.09 4.09

4.12 4.12

3.96 3.96

Dimensions DimensionsH x WHxxDW x D

1,758 x1,758 770 xx 770 1,758 x x1,758 770 xx 770 1,758 x x1,758 770 xx 770 1,758 x x1,758 1,000x 1,000 1,758 x1,758 1,000x 1,000 1,758 x1,758 1,540x 1,540 1,758 x1,758 1,540x 1,540 1,758 x1,758 1,830x 1,830 1,758 x1,758 1,830x 1,830 1,758 x1,758 1,830x 1,830 1,758 x1,758 1,830x 1,830 mm mm 930 930 930 930 930 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930

Net weight Net weight

kg

kg234 234

234 234

281 281

309 309

309 309

421 421

421 421

543 543

543 543

590 590

590 590

Running Running currentcurrent A A 8.5/8.28.9/8.5/8.2 8.5/8.2 12.2/11.8 12.9/12.2/11.8 12.2/11.814.6/14.1 15.4/14.6/14.1 14.6/14.117.1/16.5 18.0/17.1/16.5 17.1/16.520.7/19.9 21.8/20.7/19.9 20.7/19.922.8/22.0 24.0/22.8/22.0 22.8/22.026.8/25.8 28.2/26.8/25.8 26.8/25.825.2/24.3 26.6/25.2/24.3 25.2/24.329.4/28.3 30.9/29.4/28.3 29.4/28.331.6/30.5 33.3/31.6/30.5 31.6/30.535.2/33.9 37.0/35.2/33.9 35.2/33.9 CoolingCooling PowerPower input input kW kW 5.54 5.54 7.78 7.78 9.29 9.29 11.1 11.1 13.4 13.4 14.3 14.3 16.8 16.8 16.4 16.4 18.9 18.9 20.3 20.3 22.6 22.6 Electrical Electrical ratings ratings Running Running currentcurrent A 8.4/8.1 12.1/11.6 12.1/11.614.4/13.9 14.4/13.916.5/15.9 16.5/15.920.1/19.3 20.1/19.323.1/22.3 23.1/22.326.3/25.4 26.3/25.424.5/23.6 24.5/23.629.1/2830.6/29.1/28 29.1/28 30.8/29.7 30.8/29.734.4/33.1 34.4/33.1 A 8.4/8.18.8/8.4/8.1 12.7/12.1/11.6 15.1/14.4/13.9 17.4/16.5/15.9 21.1/20.1/19.3 24.3/23.1/22.3 27.7/26.3/25.4 25.8/24.5/23.6 32.5/30.8/29.7 36.2/34.4/33.1 Heating Heating PowerPower input input kW kW 5.48 5.48 7.68 7.68 9.15 9.15 10.7 10.7 13.0 13.0 14.5 14.5 16.5 16.5 15.9 15.9 18.7 18.7 19.8 19.8 22.1 22.1 1/1/1 1/1

1/1

1/1/1 1/1

100/102/105 78/81/85 74/77/80 78/81/85 98/101/103 96/98/101 81/8581/85 77/8077/80 81/8581/85 93/9691/93/96 93/96 101/103 101/10386/8883/86/88 86/88 94/9692/94/96 94/96 98/101 98/101 102/105102/105

Starting Starting current current

A

A 1/1

Airrate flow rate Air flow flow

L/s

m³/h L/s2,4508,820 2,450 2,2509,180 2,250 3,16611,400 3,166 3,53312,720 3,533 3,53312,720 3,533 4,06614,640 4,066 4,71616,980 4,716 5,98321,480 5,983 6,08321,900 6,083 6,70024,120 6,700 6,70024,120 6,700

Refrigerant amount at shipment Refrigerant amount at shipment

kg

kg6.5

6.5

6.8

6.8

6.8

6.8

8.5

8.5

8.5

8.5

9.0

9.0

9.0

9.0

15.0 15.0

15.3 15.3

15.3 15.3

15.3 15.3

External External static static pressure pressure

Pa

Pa80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

Gas pipe Gas pipe

PipingPiping LiquidLiquid pipe pipe connections connections Balance Balance pipe pipe

80

80

80

mm mm 9.52 9.52

9.52 9.52

12.7012.70 12.7012.70 12.7012.70 15.8815.88 15.8815.88 15.8815.88 15.8815.88 19.0519.05 19.0519.05

mm mm 6.35 6.35

6.35 6.35

6.35 6.35

Ambient Ambient temperature temperature operating operating rangerange

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

+20˚C Cooling: Cooling: -10˚C-10˚C (DB)~(DB)~ +46˚C+46˚C (DB). (DB). Heating: Heating: -25˚C-25˚C (WB)~(WB)~ +15˚C+15˚C (WB) (WB)

Normal modemode Normal SoundSound pressure level level pressure SilentSilent modemode

dB (A)dB56.5 (A) 56.5

59.0 59.0

61.0 61.0

62.0 62.0

62.0 62.0

60.0 60.0

63.0 63.0

63.0 63.0

63.5 63.5

64.5 64.5

64.5 64.5

dB (A)dB53.5 (A) 53.5

56.0 56.0

58.0 58.0

59.0 59.0

59.0 59.0

57.0 57.0

60.0 60.0

60.0 60.0

60.5 60.5

61.5 61.5

61.5 61.5

Sound Sound power power level level Normal Normal modemode

dB

73.5 73.5

75.5 75.5

76.5 76.5

76.5 76.5

74.5 74.5

77.5 77.5

77.5 77.5

78.0 78.0

79.0 79.0

79.0 79.0

dB71.0 71.0

Cooling Heating RatedRated conditions: conditions: Cooling Heating GLOBAL GLOBAL IndoorIndoor air temperature air temperature27˚C 27˚C DB / 19˚C DB / 19˚C WB WB20˚C 20˚C DB DB REMARKS REMARKS Outdoor 7˚C/ 6˚C DB /WB Outdoor air temperature air temperature 35˚C 35˚C DB DB 7˚C DB 6˚C WB

TheseThese specifications specifications subject subject to change to change without without notice. notice. specifications

8-12 8-12 8-12 HPHP HP

Air intake Air intake

A 894A(installation 894 (installation hole pitch). hole pitch). The tubing The tubing is routed out out is routed from the from front the front B 730B(installation 730 (installation hole pitch). hole pitch). The tubing The tubing is routed out out is routed from the from front the front C 730C(installation hole pitch). 730 (installation hole pitch).

(installation hole pitch) (installation hole pitch) Top view Top view

Air discharge Air discharge

1

1

Electrical Electrical component component box box

Front view Front view

12

80

mm mm 19.0519.05 22.2222.22 25.4025.40 25.4025.40 28.5828.58 28.5828.58 28.5828.58 28.5828.58 28.5828.58 31.7531.75 31.7531.75

4

4

3

3

2

2

1 Installation holes holes (8-15x21 1 Installation (8-15x21 elongated holes)holes) anchor bolts bolts elongated anchor M12 or larger. M12 or larger. 2 Pressure outlet outlet port (for 2 Pressure porthigh (for high pressure: Ø7.94Ø7.94 Scrader-type pressure: Scrader-type connection). connection). 3 Pressure outlet outlet port (for 3 Pressure portlow (for low pressure: Ø7.94Ø7.94 Scrader-type pressure: Scrader-type connection). connection). 4 Knock-out hole for connecting 4 Knock-out hole for connecting pressure gaugegauge (optional). pressure (optional). 5 Terminal board.board. 5 Terminal 6 Terminal boardboard (for inter6 Terminal (for interoutdoor-unit control wiring). outdoor-unit control wiring). * Installation fixing fixing fixing bracket, * Installation bracket, installation side. side. installation


FSV FSV FSV ME1 ME1 ME1 Series Series Series

30 30

30

32 32

32

34 34

34

36 36

36

38 38

38

40 40

40

42 42

42

44 44

44

46 46

46

48 48

48

50 50

50

52 52

52

54 54

54

56 56

56

58 58

58

60 60

60

U-16mE1H8 U-16ME1R8 U-16ME1R8 U-16mE1H8 U-16ME1R8 U-16ME1R8 U-16mE1H8 U-16ME1R8 U-16ME1R8 U-16mE1H8 U-16ME1R8 U-16ME1R8 U-18mE1H8 U-18ME1R8 U-18ME1R8 U-20mE1H8 U-20ME1R8 U-20ME1R8 U-20mE1H8 U-20ME1R8 U-20ME1R8 U-20mE1H8 U-20ME1R8 U-20ME1R8 U-20mE1H8 U-20ME1R8 U-20ME1R8 U-20mE1H8 U-20ME1R8 U-20ME1R8 U-16mE1H8 U-16mE1H8 U-18mE1H8 U-20mE1H8 U-20mE1H8 U-20mE1H8 U-16ME1R8 U-16ME1R8 U-16ME1R8 U-16ME1R8 U-18ME1R8 U-18ME1R8 U-20ME1R8 U-20ME1R8 U-20ME1R8 U-20ME1R8 U-20ME1R8 U-20ME1R8 U-14mE1H8 U-14ME1R8 U-14ME1R8 U-16mE1H8 U-16ME1R8 U-16ME1R8 U-16mE1H8 U-16ME1R8 U-16ME1R8 U-16mE1H8 U-16ME1R8 U-16ME1R8 U-16mE1H8 U-16ME1R8 U-16ME1R8 U-16mE1H8 U-16ME1R8 U-16ME1R8 U-18mE1H8 U-18ME1H8 U-18ME1H8 U-18mE1H8 U-18ME1R8 U-18ME1R8 U-20mE1H8 U-20ME1R8 U-20ME1R8 U-20mE1H8 U-20ME1R8 U-20ME1R8 U-14mE1H8 U-14ME1R8 U-14ME1R8 U-16mE1H8 U-16ME1v U-16ME1vU-16mE1H8 U-16ME1R8 U-16ME1R8 U-16mE1H8 U-16ME1R8 U-16ME1R8 U-18mE1H8 U-18ME1R8 U-18ME1R8 U-20mE1H8 U-20ME1R8 U-20ME1R8 U-12mE1H8 U-12ME1R8 U-12ME1R8 U-12mE1H8 U-12ME1R8 U-12ME1R8 U-14mE1H8 U-14ME1R8 U-14ME1R8 U-16mE1H8 U-16ME1R8 U-16ME1R8 U-16mE1H8 U-16ME1R8 U-16ME1R8 U-16mE1H8 U-16ME1R8 U-16ME1R8 U-16mE1H8 U-16ME1R8 U-16ME1R8 U-18mE1H8 U-18ME1R8 U-18ME1R8 U-18mE1H8 U-18ME1R8 U-18ME1R8 U-20mE1H8 U-20ME1R8 U-20ME1R8 380/400/415V 380/400/415V 3phase/50Hz 3phase/50Hz 85.0 85.0

90.0 90.0

96.0 96.0

101.0101.0 107.0107.0 113.0113.0 118.0118.0 124.0124.0 130.0130.0 135.0135.0 140.0140.0 145.0145.0 151.0151.0 156.0156.0 162.0162.0 168.0168.0

290,100 290,100307,200 307,200327,600 327,600344,700 344,700365,200 365,200385,700 385,700402,700 402,700423,200 423,200443,700 443,700460,800 460,800477,800 477,800494,900 494,900515,400 515,400532,400 532,400552,900 552,900573,400 573,400 95.0 95.0

100.0100.0 108.0108.0 113.0113.0 119.0119.0 127.0127.0 132.0132.0 138.0138.0 145.0145.0 150.0150.0 155.0155.0 160.0160.0 169.0169.0 175.0175.0 182.0182.0 189.0189.0

324,200341,300 341,300368,600 368,600385,700 385,700406,100 406,100433,400 433,400450,500 450,500471,000 471,000494,900 494,900511,900 511,900529,000 529,000546,100 546,100576,800 576,800597,300 597,300621,200 621,200645,100 645,100 324,200 3.47 3.47

3.35 3.35

3.43 3.43

3.34 3.34

3.44 3.44

3.36 3.36

3.51 3.51

3.43 3.43

3.43 3.43

3.35 3.35

3.41 3.41

3.35 3.35

3.39 3.39

3.44 3.44

3.38 3.38

3.33 3.33

4.03 4.03

3.86 3.86

3.86 3.86

3.83 3.83

3.84 3.84

3.85 3.85

4.04 4.04

3.92 3.92

3.96 3.96

3.86 3.86

3.86 3.86

3.84 3.84

3.85 3.85

3.85 3.85

3.83 3.83

3.81 3.81

1,758 x1,758 2,060x 2,060 1,758 x1,758 2,060x 2,060 1,758 x1,758 2,600x 2,600 1,758 x1,758 2,600x 2,600 1,758 x1,758 3,140x 3,140 1,758 x1,758 3,140x 3,140 1,758 x1,758 2,890x 2,890 1,758 x1,758 2,890x 2,890 1,758 x1,758 3,120x 3,120 1,758 x1,758 3,120x 3,120 1,758 x1,758 3,660x 3,660 1,758 x1,758 3,660x 3,660 1,758 x1,758 4,200x 4,200 1,758 x1,758 1,758 x1,758 1,758 x1,758 4,740x 4,740 4,740x 4,740 4,740x 4,740 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 x 930 618 618

618 618

730 730

730 730

842 842

842 842

899 899

899 899

927 927

927 927

1039 1039

1039 1039

1151 1151

1263 1263

1263 1263

1263 1263

39.8/37.8/36.5 37.8/36.5 37.8/36.5 43.7/41.5/40.0 41.5/40.0 41.5/40.046.3/44.0/42.4 44.0/42.4 44.0/42.450.0/47.5/45.8 47.5/45.8 47.5/45.852.2/49.6/47.8 49.6/47.8 49.6/47.856.4/53.6/51.7 53.6/51.7 53.6/51.754.9/52.1/50.3 52.1/50.3 52.1/50.359.1/56.2/54.2 56.2/54.2 56.2/54.261.6/58.5/56.4 58.5/56.4 58.5/56.465.5/62.2/60.0 62.2/60.0 62.2/60.067.6/64.2/61.9 64.2/61.9 64.2/61.971.3/67.7/65.3 67.7/65.3 67.7/65.374.0/70.3/67.7 70.3/67.7 70.3/67.776.2/72.4/69.8 72.4/69.8 72.4/69.880.4/76.4/73.6 76.4/73.6 76.4/73.684.6/80.4/77.5 80.4/77.5 80.4/77.5 24.5 24.5

26.9 26.9

28.0 28.0

30.2 30.2

31.1 31.1

33.6 33.6

33.6 33.6

36.2 36.2

37.9 37.9

40.3 40.3

41.1 41.1

43.3 43.3

44.5 44.5

45.4 45.4

47.9 47.9

50.4 50.4

36.4/35.1 36.4/35.1 42.1/40/38.5 40/38.540/38.5 46.3/44.0/42.4 44.0/42.4 44.0/42.448.8/46.4/44.7 46.4/44.7 46.4/44.752.0/49.4/47.7 49.4/47.7 49.4/47.755.4/52.6/50.7 52.6/50.7 52.6/50.753.4/50.8/48.9 50.8/48.9 50.8/48.957.5/54.6/52.7 54.6/52.7 54.6/52.759.5/56.5/54.5 56.5/54.5 56.5/54.563.2/60.1/57.9 60.1/57.9 60.1/57.966.1/62.8/60.5 62.8/60.5 62.8/60.568.6/65.2/62.9 65.2/62.9 65.2/62.973.0/69.3/66.8 69.3/66.8 69.3/66.876.2/72.4/69.8 72.4/69.8 72.4/69.879.7/75.8/73 75.8/7375.8/73 83.3/79.1/76.2 79.1/76.2 79.1/76.2 38.3/36.4/35.1 23.6 23.6

25.9 25.9

28.0 28.0

29.5 29.5

31.0 31.0

33.0 33.0

32.7 32.7

35.2 35.2

36.6 36.6

38.9 38.9

40.2 40.2

41.7 41.7

43.9 43.9

45.4 45.4

47.5 47.5

49.6 49.6

98/101 98/101 100/102/105 102/105 102/105 113/114/116 114/116 114/116 120/122/123 122/123 122/123 121/123/124 123/124 123/124 125/127/128 127/128 127/128 118/119/121 119/121 119/121 122/122/125 122/125 122/125 118/119/121 119/121 119/121 122/122/125 122/125 122/125 135/134/136 134/136 134/136 142/142/143 142/143 142/143 143/144/144 144/144 144/144 145/146/146 146/146 146/146 148/149/149 149/149 149/149 152/153/153 153/153 153/153 96/98/101 25,440 7,0667,066 25,440 7,0667,066 27,360 7,6007,600 29,700 8,2508,250 31,680 8,7838,783 34,020 9,4339,433 36,840 10,233 10,233 36,840 10,233 10,233 38,160 10,600 10,600 38,160 10,600 10,600 40,080 11,133 11,133 42,420 11,783 11,783 44,340 12,316 12,316 46,260 12,850 12,850 48,600 13,500 13,500 50,940 14,150 14,150 17.0 17.0

17.0 17.0

17.5 17.5

17.5 17.5

18.0 18.0

18.0 18.0

23.8 23.8

23.8 23.8

25.5 25.5

25.5 25.5

26.0 26.0

26.0 26.0

26.5 26.5

27.0 27.0

27.0 27.0

27.0 27.0

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

80

31.7531.75 31.7531.75 31.7531.75 38.1038.10 38.1038.10 38.1038.10 38.1038.10 38.1038.10 38.1038.10 38.1038.10 38.1038.10 38.1038.10 38.1038.10 38.1038.10 38.1038.10 38.1038.10 19.0519.05 19.0519.05 19.0519.05 19.0519.05 19.0519.05 19.0519.05 19.0519.05 19.0519.05 19.0519.05 19.0519.05 19.0519.05 19.0519.05 19.0519.05 19.0519.05 19.0519.05 19.0519.05 6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

Cooling: Heating: (WB)~ Cooling: -10˚C-10˚C (DB)~(DB)~ +46˚C+46˚C (DB).(DB). Heating: -25˚C-25˚C (WB)~ +20˚C+20˚C (WB) (WB) 65.0 65.0

65.0 65.0

64.0 64.0

65.5 65.5

65.0 65.0

66.0 66.0

66.5 66.5

66.5 66.5

67.0 67.0

67.0 67.0

66.0 66.0

67.0 67.0

66.5 66.5

66.0 66.0

67.0 67.0

68.0 68.0

62.0 62.0

62.0 62.0

61.0 61.0

62.5 62.5

62.0 62.0

63.0 63.0

63.5 63.5

63.5 63.5

64.0 64.0

64.0 64.0

63.0 63.0

64.0 64.0

63.5 63.5

63.0 63.0

64.0 64.0

65.0 65.0

79.5 79.5

79.5 79.5

78.5 78.5

80.0 80.0

79.5 79.5

80.5 80.5

81.0 81.0

81.0 81.0

81.5 81.5

81.5 81.5

80.5 80.5

81.5 81.5

81.0 81.0

80.5 80.5

81.5 81.5

82.5 82.5

14-16 HPHP 14-16 14-16 HP

18-20 HP 18-20 18-20 HPHP

Air intake Air intake

Air intake Air intake

A 894A(installation hole pitch). 894 (installation hole pitch). The tubing is routed out from The tubing is routed out from the front the front B 730B(installation hole pitch). 730 (installation hole pitch). The tubing is routed out from The tubing is routed out from the front the front C 730C(installation hole pitch). 730 (installation hole pitch).

A 894A(installation 894 (installation hole pitch). hole pitch). The tubing The tubing is routed out from is routed out from the front the front B 730B(installation 730 (installation hole pitch). hole pitch). The tubing The tubing is routed out from is routed out from the front the front C 730C(installation 730 (installation hole pitch). hole pitch). (installation hole pitch) (installation hole pitch)

(installation (installation hole pitch) hole pitch)

Top view Top view Air discharge Air discharge Electrical component box box Electrical component 4 4 4 4 3 3 3 3 2

Front view Front view

2

2

2

1

1

Top view Top view 1

1

1 Installation holesholes (8-15x21 1 Installation (8-15x21 elongated holes)holes) anchor bolts bolts elongated anchor M12 or larger. M12 or larger. 2 Pressure outletoutlet port (for 2 Pressure porthigh (for high pressure: Ø7.94Ø7.94 Scrader-type pressure: Scrader-type connection). connection). portlow (for low 3 Pressure outletoutlet port (for 3 Pressure pressure: Scrader-type pressure: Ø7.94Ø7.94 Scrader-type connection). connection). hole for connecting 4 Knock-out 4 Knock-out hole for connecting pressure pressure (optional). gaugegauge (optional). 5 Terminal 5 Terminal board. board. 6 Terminal 6 Terminal (for interboardboard (for interoutdoor-unit outdoor-unit control wiring). control wiring). * Installation fixing bracket, * Installation fixingfixing bracket, installation side. side. installation

Electrical Electrical component component box box Air discharge Air discharge

4

4

3

3

2

2

1

1

1 Installation 1 Installation (8-15x21 holesholes (8-15x21 elongated elongated anchor holes)holes) anchor bolts bolts M12 or M12 or larger. larger. 2 Pressure 2 Pressure porthigh (for high outletoutlet port (for pressure: pressure: Scrader-type Ø7.94Ø7.94 Scrader-type connection). connection). 3 Pressure 3 Pressure portlow (for low outletoutlet port (for pressure: Scrader-type pressure: Ø7.94Ø7.94 Scrader-type connection). connection). 4 Knock-out hole for connecting 4 Knock-out hole for connecting (optional). pressure pressure gaugegauge (optional). 5 Terminal board. 5 Terminal board. 6 Terminal (for inter6 Terminal boardboard (for interoutdoor-unit control wiring). outdoor-unit control wiring).

Front view Front view

* Installation * Installation fixingfixing bracket, fixing bracket, installation installation side. side.

13


HIGH COPCOP SETTING SETTING MODEL MODEL COP SETTING MODEL 2-WAY FSV ME1 Series 2-WAY 2-WAY FSV FSV ME1 ME1 Series Series HIGHHIGH

Appearance Appearance

HP HP HP

10

model name Model Model namename

U-14ME1R8 U-14ME1R8 U-16ME1R8 U-16ME1R8 U-18ME1R8 U-20ME1R8 U-14mE1H8 U-16mE1H8 U-18ME1R8 U-18mE1H8 U-20ME1R8 U-20mE1H8

PowerPower supply supply Cooling Cooling Capacity Capacity Heating Heating EER /EER COP/ COP

12

12 12

14

14 14

16

16 16

18

18 18

20

22

22 22

24

24 24

U-14ME1R8 U-14ME1R8 U-16ME1R8 U-18ME1R8 U-16ME1R8 U-14mE1H8 U-16ME1R8 U-16mE1H8 U-18ME1R8 U-18mE1H8 U-16ME1R8 U-16mE1H8 U-8ME1R8 U-8ME1R8 U-8ME1R8 U-8ME1R8 U-16ME1R8 U-8mE1H7 U-8ME1R8 U-8mE1H7 U-8ME1R8 U-8mE1H7 U-16ME1R8 U-16mE1H8

380/400/415V 3phase/50Hz 3phase/50Hz 380/400/415V 33.5 33.5

40.0 40.0

45.0 45.0

50.0 50.0

56.0 56.0

61.5 61.5

68.0 68.0

BTU/hBTU/h95,600 95,600

114,300 114,300

136,500 136,500

153,600 153,600

170,600 170,600

191,100 191,100

209,900 209,900

232,100 232,100

kW kW 31.5 31.5

37.5 37.5

45.0 45.0

50.0 50.0

56.0 56.0

63.0 63.0

69.0 69.0

76.5 76.5

BTU/hBTU/h107,500 107,500

128,000 128,000

153,600 153,600

170,600 170,600

191,100 191,100

215,000 215,000

235,500 235,500

261,100 261,100

Cooling Cooling

W/W W/W 4.06 4.06

4.07 4.07

4.01 4.01

3.88 3.88

4.07 4.07

4.06 4.06

3.97 3.97

4.07 4.07

Heating Heating

W/W W/W 4.45 4.45

4.45 4.45

4.41 4.41

4.39 4.39

4.52 4.52

4.50 4.50

4.39 4.39

4.45 4.45

mm mm

Net weight Net weight

kg

kg

1,7581,758 x 1,000 1,7581,758 x 1,000 1,7581,758 x 1,540 1,7581,758 x 1,540 1,7581,758 x 1,830 1,7581,758 x 1,830 1,7581,758 x 2,370 1,7581,758 x 2,060 x 1,000 x 1,000 x 1,540 x 1,540 x 1,830 x 1,830 x 2,370 x 2,060 x 930x 930 x 930x 930 x 930x 930 x 930x 930 x 930x 930 x 930x 930 x 930x 930 x 930x 930 309 309

309 309

421 421

421 421

543 543

543 543

655 655

618 618

Running Running current current A A 11.2/10.7/10.3 11.2/10.7/10.3 13.4/12.7/12.2 13.4/12.7/12.2 16.3/15.4/14.9 16.3/15.4/14.9 18.9/17.9/17.3 18.9/17.9/17.3 19.9/18.9/18.2 19.9/18.9/18.2 22.4/21.2/20.5 22.4/21.2/20.5 25.2/23.9/23.0 25.2/23.9/23.0 27.1/25.8/24.8 27.1/25.8/24.8 Cooling Cooling PowerPower input input kW kW 6.90 6.90 8.23 8.23 9.98 9.98 11.6 11.6 12.3 12.3 13.8 13.8 15.5 15.5 16.7 16.7 Running Running current current A 11.5/10.9/10.5 11.5/10.9/10.5 13.7/13/12.5 13.7/13/12.516.6/15.8/15.2 16.6/15.8/15.2 18.6/17.6/17.0 18.6/17.6/17.0 20.1/19.1/18.4 20.1/19.1/18.4 22.7/21.5/20.8 22.7/21.5/20.8 25.5/24.2/23.3 25.5/24.2/23.3 27.9/26.6/26.5 27.9/26.6/26.5 A Heating Heating PowerPower input input kW kW 7.08 7.08 8.43 8.43 10.2 10.2 11.4 11.4 12.4 12.4 14.0 14.0 15.7 15.7 17.2 17.2

Starting current Starting current

A

A

78/81/85 78/81/85

89/92/95 89/92/95

95/98/101 95/98/101 83/86/88 83/86/88

87/90/93 87/90/93

98/101/103 98/101/103 92/94/98 92/94/98

Air flow flow rate Airrate flow

L/s

L/s 3533 12,720 3533 m³/h

74/77/80 74/77/80

3533 12,720 3533

4066 14,640 4066

4716 16,980 4716

6083 21,540 6083

6700 23,460 6700

pressure External External staticstatic pressure

Pa

Pa

80

80

at shipment Refrigerant Refrigerant amount amount at shipment

kg

kg

8.5 8.5

Gas pipe Gas pipe PipingPiping LiquidLiquid pipe pipe connections connections Balance pipe pipe Balance

80

80

80

80

80

5983 21,540 5983

80

80

80

80

80

80

80

7066 25,440 7066 80

80

8.5 8.5

9.0 9.0

9.0 9.0

15.0 15.0

15.0 15.0

15.5 15.5

17.0 17.0

mm mm 22.2222.22

25.4025.40

25.4025.40

28.5828.58

28.5828.58

28.5828.58

28.5828.58

28.5828.58

mm mm 9.52 9.52

12.7012.70

12.7012.70

12.7012.70

15.8815.88

15.8815.88

15.8815.88

15.8815.88

mm mm 6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

operating rangerange Ambient temperature Ambient temperature operating

Cooling: -10˚C-10˚C (DB)~(DB)~ +43˚C+43˚C (DB). (DB). Heating: -25˚C-25˚C (WB)~ +20˚C+20˚C (WB) (WB) Cooling: Heating: (WB)~

Normal modemode Normal Sound pressure Sound pressure level level SilentSilent modemode

dBA dBA 62.0 62.0

62.0 62.0

60.0 60.0

63.0 63.0

63.0 63.0

63.0 63.0

61.5 61.5

65.0 65.0

dBA dBA 59.0 59.0

59.0 59.0

57.0 57.0

60.0 60.0

60.0 60.0

60.0 60.0

58.5 58.5

62.0 62.0

Normal Sound Sound power power level level Normal modemode

dB

76.5 76.5

74.5 74.5

77.5 77.5

77.5 77.5

77.5 77.5

76.0 76.0

79.5 79.5

dB

76.5 76.5

HigH setting COPCOP SETTING SETTING 10-12 10-12 10-12 HPHP HPHIGHHIGH

flow Air flowAir direction flow direction PCB place PCB place

Installation anchoring hole (4-15x21 elongated hole) hole) Anchor bolt: M12 1 Installation anchoring hole (4-15x21 elongated Anchor bolt: more M12 more Refrigerant pipingpiping port (front / knockout hole) hole) 2 Refrigerant port (front / knockout Electric 3 Electric wiringwiring port (front /Ø60,Ø28 knockout hole hole conduit connection) port (front /Ø60,Ø28 knockout conduit connection) Mounting hole for manifold gaugegauge (high-pressure outletoutlet port / port Ø7.94 dia connector) 4 Mounting hole for manifold (high-pressure / Ø7.94 dia connector) Mounting hole for manifold gaugegauge (low-pressure outletoutlet port / port Ø7.94 dia connector) 5 Mounting hole for manifold (low-pressure / Ø7.94 dia connector) Knockout hole to fix manifold gaugegauge (field (field supply) 6 Knockout fix manifold (field hole to fix supply)

*Installation surface *Installation surface

(Installation hole pitch to fix) fix)

(Installation hole pitch to fix)

Air flow flow direction

Air flow direction

Distribution joint Distribution Distribution joint kit joint kit kit For For indoor For indoor indoor units units units • CZ-P160BK2 (Capacity after distribution: 22.4orkW or lower) • CZ-P160BK2 (Capacity after distribution: 22.4 kW lower) • CZ-P680BK2 (Capacity after distribution: 22.4tokW to kW) 68.0 kW) • CZ-P680BK2 (Capacity after distribution: Over Over 22.4 kW 68.0 • CZ-P1350BK2 (Capacity after distribution: 68.0tokW to 135.0 • CZ-P1350BK2 (Capacity after distribution: Over Over 68.0 kW 135.0 kW) kW) For For outdoor For outdoor outdoor units units units • CZ-P680PJ2 (Capacity after distribution: 68.0orkW or lower) • CZ-P680PJ2 (Capacity after distribution: 68.0 kW lower) • CZ-P1350PJ2 (Capacity after distribution: 68.0tokW to 135.0 • CZ-P1350PJ2 (Capacity after distribution: Over Over 68.0 kW 135.0 kW kW

flow direction Air flowAir direction flow

Air flow flow direction

Air flow direction

1 2 3 4 5 6

(Installation fix) (Installation hole pitch holetopitch fix) to fix) above above

front front

HigH setting COPCOP SETTING SETTING 14-16 14-16 14-16 HPHP HPHIGHHIGH

*Installation surface *Installation surface

(Installation hole pitch to fix) fix)

Air flow flow direction

Air flow direction

Air flow flow direction

Distribution joint Distribution Distribution joint kit joint kit kit For For indoor For indoor indoor units units units • CZ-P160BK2 (Capacity after distribution: 22.4orkW or lower) • CZ-P160BK2 (Capacity after distribution: 22.4 kW lower) • CZ-P680BK2 (Capacity after distribution: 22.4tokW to kW) 68.0 kW) • CZ-P680BK2 (Capacity after distribution: Over Over 22.4 kW 68.0 • CZ-P1350BK2 (Capacity after distribution: 68.0tokW to 135.0 • CZ-P1350BK2 (Capacity after distribution: Over Over 68.0 kW 135.0 kW) kW) For For outdoor For outdoor outdoor units units units • CZ-P680PJ2 (Capacity after distribution: 68.0orkW or lower) • CZ-P680PJ2 (Capacity after distribution: 68.0 kW lower) • CZ-P1350PJ2 (Capacity after distribution: 68.0tokW to 135.0 • CZ-P1350PJ2 (Capacity after distribution: Over Over 68.0 kW 135.0 kW kW

(Installation hole pitch to fix)

flow direction flow direction Air flowAir direction flow Air flowAir direction flow PCB place PCB place

Installation anchoring hole (4-15x21 elongated hole) hole) Anchor bolt: M12 1 Installation anchoring hole (4-15x21 elongated Anchor bolt: more M12 more Refrigerant 2 Refrigerant pipingpiping port (front / knockout hole) hole) port (front / knockout Electric 3 Electric wiringwiring port (front /Ø60,Ø28 knockout hole hole conduit connection) port (front /Ø60,Ø28 knockout conduit connection) Mounting 4 Mounting hole for manifold gaugegauge (high-pressure outletoutlet port / port Ø7.94 dia connector) hole for manifold (high-pressure / Ø7.94 dia connector) Mounting hole for manifold gaugegauge (low-pressure outletoutlet port / port Ø7.94 dia connector) 5 Mounting hole for manifold (low-pressure / Ø7.94 dia connector) Air flowAir direction flow flow direction Knockout 6 Knockout hole to fix manifold fix manifold gaugegauge (field (field (field supply) hole to fix supply) Air flow direction

1 2 3 4 5 6

14

20 20

kW kW 28.0 28.0

Dimensions DimensionsH x WHxxDW x D

Electrical Electrical ratings ratings

10 10

(Installation hole pitch holetopitch fix) to fix) (Installation fix) above above

front front


FSV FSV FSV ME1 ME1 ME1 Series Series Series

26 26

28 28

26

28

30 30

30

32 32

32

34 34

34

36 36

36

38 38

40 40

38

42 42

40

44 44

42

46 46

44

46

48 48

48

U-18ME1R8 U-18ME1R8 U-16ME1R8 U-18mE1H8 U-16ME1R8 U-18ME1R8 U-16mE1H8 U-18ME1R8 U-20ME1R8 U-18mE1H8 U-20ME1R8 U-20mE1H8 U-20mE1H8 U-20ME1R8 U-20mE1H8 U-20ME1R8 U-20ME1R8 U-20mE1H8 U-20ME1R8 U-20ME1R8 U-20mE1H8 U-20ME1R8 U-20ME1R8 U-20ME1R8 U-18ME1R8 U-18ME1R8 U-20ME1R8 U-20ME1R8 U-20ME1R8 U-20ME1R8 U-20ME1R8 U-20ME1R8 U-18mE1H8 U-20mE1H8 U-20mE1H8 U-20mE1H8 U-16ME1R8 U-16ME1R8 U-16ME1R8 U-16mE1H8 U-16ME1R8 U-16ME1R8 U-16mE1H8 U-16ME1R8 U-16ME1R8 U-16mE1H8 U-16ME1R8 U-18mE1H8 U-16mE1H8 U-18ME1R8 U-18mE1H8 U-18ME1R8 U-18ME1R8 U-20mE1H8 U-18ME1R8 U-20ME1R8 U-20mE1H8 U-20ME1R8 U-20ME1R8 U-20ME1R8 U-16ME1R8 U-16ME1R8 U-16ME1R8 U-16ME1R8 U-18ME1R8 U-18ME1R8 U-20ME1R8 U-20ME1R8 U-16mE1H8 U-16mE1H8 U-18mE1H8 U-20mE1H8 U-8MEv U-8MEv U-8mE1H7 U-16ME1R8 U-16ME1R8 U-16ME1R8 U-16mE1H8 U-16ME1R8 U-16mE1H8 U-16mE1H8 U-16ME1R8 U-16mE1H8 U-16ME1R8 U-16ME1R8 U-18mE1H8 U-16ME1R8 U-18ME1R8 U-18mE1H8 U-18ME1R8 U-18ME1R8 U-20mE1H8 U-18ME1R8 U-20MU-20M E1R8 E1R8 380/400/415V 380/400/415V 3phase/50Hz 3phase/50Hz 73.0 73.0

78.5 78.5

85.0 85.0

90.0 90.0

96.0 96.0

101.0101.0

107.0107.0

113.0113.0

118.0118.0

124.0124.0

130.0130.0

135.0135.0

249,100 249,100

267,900 267,900

290,100 290,100

307,200 307,200

327,600 327,600

344,700 344,700

365,200 365,200

385,700 385,700

402,700 402,700

423,200 423,200

443,700 443,700

460,800 460,800

81.5 81.5

87.5 87.5

95.0 95.0

100.0100.0

108.0108.0

113.0113.0

119.0119.0

127.0127.0

132.0132.0

138.0138.0

145.0145.0

150.0150.0

278,200 278,200

298,600 298,600

324,200 324,200

341,300 341,300

368,600 368,600

385,700 385,700

406,100 406,100

433,400 433,400

450,500 450,500

471,000 471,000

494,900 494,900

511,900 511,900

4.01 4.01

3.96 3.96

3.94 3.94

3.88 3.88

4.09 4.09

4.07 4.07

4.08 4.08

4.04 4.04

3.96 3.96

3.97 3.97

3.92 3.92

3.88 3.88

4.38 4.38

4.42 4.42

4.40 4.40

4.41 4.41

4.54 4.54

4.45 4.45

4.44 4.44

4.47 4.47

4.40 4.40

4.42 4.42

4.41 4.41

4.40 4.40

x 3,140 x 3,430 x 3,120 x 3,660 x 3,660 x 4,200 x 4,740 x 4,740 x 4,740 x 2,600 x 2,600 x 1,758 x 3,140 1,7801,780 x 2,600 1,7581,758 x 2,600 x 1,758 x 3,140 1,7581,758 x 3,140 1,7581,758 x 3,430 1,7581,758 x 3,120 1,7581,758 x 3,660 1,7581,758 x 3,660 1,7581,758 x 4,200 1,7581,758 x 4,740 1,7581,758 x 4,740 1,7581,758 x 4,740 x 930x 930 930 930 x 930x 930 x 930x 930 x 930x 930 x 930x 930 x 930x 930 x 930x 930 x 930x 930 x 930x 930 x 930x 930 x 930x 930 730 730

730 730

842 842

842 842

964 964

927 927

1039 1039

1039 1039

1151 1151

1263 1263

1263 1263

1263 1263

29.6/28.1/27.1 32.2/30.6/29.5 35.2/33.4/32.2 37.8/35.9/34.6 38.1/36.2/34.9 40.3/38.3/36.9 42.6/40.5/39.0 45.5/43.3/41.7 48.5/46.1/44.4 50.8/48.3/46.5 54.1/51.4/49.5 56.7/53.8/51.9 29.6/28.1/27.1 32.2/30.6/29.5 35.2/33.4/32.2 37.8/35.9/34.6 38.1/36.2/34.9 40.3/38.3/36.9 42.6/40.5/39.0 45.5/43.3/41.7 48.5/46.1/44.4 50.8/48.3/46.5 54.1/51.4/49.5 56.7/53.8/51.9 18.2 18.2

19.8 19.8

21.6 21.6

23.2 23.2

23.5 23.5

24.8 24.8

26.2 26.2

28.0 28.0

29.8 29.8

31.2 31.2

33.2 33.2

34.8 34.8

30.3/28.7/27.7 32.2/30.6/29.5 35.2/33.4/32.2 37/35.1/33.838.6/36.7/35.4 38.6/36.7/35.4 41.3/39.2/37.8 43.6/41.4/39.9 46.2/43.9/42.3 48.8/46.4/44.7 50.8/48.3/46.5 53.6/50.9/49.1 55.5/52.8/50.8 30.3/28.7/27.7 32.2/30.6/29.5 35.2/33.4/32.2 37/35.1/33.8 41.3/39.2/37.8 43.6/41.4/39.9 46.2/43.9/42.3 48.8/46.4/44.7 50.8/48.3/46.5 53.6/50.9/49.1 55.5/52.8/50.8 18.6 18.6

19.8 19.8

21.6 21.6

22.7 22.7

23.8 23.8

25.4 25.4

26.8 26.8

28.4 28.4

30.0 30.0

31.2 31.2

32.9 32.9

34.1 34.1

103/105/108109/111/114 109/111/114112/114/116 112/114/116114/116/118 114/116/118112/113/116 112/113/116105/107/110 105/107/110116/118/120 116/118/120122/124/126 122/124/126125/127/129 125/127/129128/130/131 128/130/131130/131/133 130/131/133133/134/136 133/134/136 103/105/108 7600 7600 27,360

8250 8250 29,700

8783 8783 31,620

9433 9433 33,960

1023310233 36,180

1060010600 38,160

1113311133 40,080

1178311783 42,420

1231612316 44,340

1285012850 46,260

1350013500 48,600

1415014150 50,940

80

80

80

80

80

80

80

80

80

80

80

80

80

17.5 17.5

80

17.5 17.5

80

18.0 18.0

80

18.0 18.0

80

24.0 24.0

80

25.5 25.5

80

26.0 26.0

80

26.0 26.0

80

26.5 26.5

80

27.0 27.0

80

27.0 27.0

80

27.0 27.0

31.7531.75

31.7531.75

31.7531.75

31.7531.75

31.7531.75

38.1038.10

38.1038.10

38.1038.10

38.1038.10

38.1038.10

38.1038.10

38.1038.10

19.0519.05

19.0519.05

19.0519.05

19.0519.05

19.0519.05

19.0519.05

19.0519.05

19.0519.05

19.0519.05

19.0519.05

19.0519.05

19.0519.05

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

6.35 6.35

Cooling: Heating: Cooling: -10˚C-10˚C (DB)~(DB)~ +43˚C+43˚C (DB). (DB). Heating: -25˚C-25˚C (WB)~(WB)~ +20˚C+20˚C (WB) (WB) 64.0 64.0

65.5 65.5

65.0 65.0

66.0 66.0

64.5 64.5

66.5 66.5

66.0 66.0

67.0 67.0

66.5 66.5

66.0 66.0

67.0 67.0

67.5 67.5

61.0 61.0

62.5 62.5

62.0 62.0

63.0 63.0

61.5 61.5

63.5 63.5

63.0 63.0

64.0 64.0

63.5 63.5

63.0 63.0

64.0 64.0

64.5 64.5

78.5 78.5

80.0 80.0

79.5 79.5

80.5 80.5

79.0 79.0

81.0 81.0

80.5 80.5

81.5 81.5

81.0 81.0

80.5 80.5

81.5 81.5

82.0 82.0

conditions: Cooling Heating RatedRated conditions: Cooling Heating GLOBAL GLOBAL IndoorIndoor air temperature air temperature27˚C 27˚C DB / 19˚C DB / 19˚C WB WB20˚C 20˚C DB DB REMARKS REMARKS Outdoor Outdoor air temperature air temperature 35˚C 35˚C DB DB 7˚C DB 7˚C/ 6˚C DB /WB 6˚C WB

TheseThese specifications specifications specifications subject subject to change to change without without notice. notice.

Using Using withwith 18, 20, 18,22, 20,34 22,HP 34module HP module 8 HP HP 8 8 HP

*Installation surface *Installation surface

(Installation hole pitch to fix)

Air flow direction

(Installation hole pitch to fix)

Air flow direction

Distribution joint kit Distribution joint kit kit Distribution joint For indoor For indoor indoor units units For units • CZ-P160BK2 (Capacity after distribution: 22.4 or lower) • CZ-P160BK2 (Capacity after distribution: 22.4 kW orkW lower) • CZ-P680BK2 (Capacity after distribution: Over kW 22.4tokW to kW) • CZ-P680BK2 (Capacity after distribution: Over 22.4 68.0 68.0 kW) (Capacity after distribution: OverkW 68.0 to 135.0 • CZ-P1350BK2 • CZ-P1350BK2 (Capacity after distribution: Over 68.0 tokW 135.0 kW) kW) For outdoor For outdoor units units For outdoor units • CZ-P680PJ2 • CZ-P680PJ2 (Capacity after distribution: 68.0 or lower) (Capacity after distribution: 68.0 kW orkW lower) • CZ-P1350PJ2 • CZ-P1350PJ2 (Capacity (Capacity after distribution: after distribution: Over 68.0 Over kW 68.0tokW 135.0 to 135.0 kW kW

flow direction Air flowAirdirection Air flow direction

Installation 1 Installation anchoring hole (4-15x21 elongated Anchor bolt:more M12 more anchoring hole (4-15x21 elongated hole) hole) Anchor bolt: M12 Refrigerant 2 Refrigerant port (front / knockout pipingpiping port (front / knockout hole) hole) Electric 3 Electric port (front /Ø60,Ø28 knockout hole conduit connection) wiringwiring port (front /Ø60,Ø28 knockout hole conduit connection) Mounting 4 Mounting hole for manifold (high-pressure / Ø7.94 dia connector) hole for manifold gaugegauge (high-pressure outlet outlet port / port Ø7.94 dia connector) Mounting 5 Mounting hole for manifold (low-pressure / Ø7.94 dia connector) hole for manifold gaugegauge (low-pressure outlet outlet port / port Ø7.94 dia connector) Knockout 6 Knockout hole fix manifold to fix manifold (field supply) (field supply) hole to fix gaugegauge (field

Air flow direction

1 2 3 4 5 6

Air flowAirdirection flow direction PCB place PCB place

(Installation pitch to fix) (Installation hole pitchhole to fix)

above above front front

15


Piping design Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below.

1. Main tubing length LM = LA + LB … 2. Main distribution tubes LC – LH are selected according to the capacity after the distribution joint. 3. The outdoor connection main tubing (LO portion) is determined by the total capacity of the outdoor units that are connected to the tube ends. 4. Sizes of indoor unit connection tubing 1 – 64 are determined by the connection tubing sizes on the indoor units. L1 H3

C

L2 LM

Balance tubing (ø 6.35)

B

A LO

LB

LC

LD

H1

R410A distribution joint CZ-P680PJ2 (for outdoor unit) CZ-P1350PJ2 (for outdoor unit) CZ-P160BK2 (for indoor unit) CZ-P680BK2 (for indoor unit) CZ-P1350BK2 (for indoor unit)

L3

LA 4 LF

Max. 40 cm

5

62

63

64

For extension For extension

Explanation of symbols

Max. 40 cm

Distribution joint (CZ-accessory, purchased separately)

LG

Ball valve (field supply) T-joint (field supply)

H2

LH 1

2

3

L4

Solidly welded shut (pinch weld)

Note: Do not use commercially available T-joints for the liquid tubing and parts. * Be sure to use special R410A distribution joints (purchased separately) for outdoor unit connections and tubing branches.

Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights Items

Allowable tubing length

Mark

Allowable length of joint tubing

Length (m) Actual length

≤180

Equivalent length

≤200

L1

Max. tubing length

∆ L (L2 _L4)

Difference between max. length and min. length from the No.1 distribution joint

≤50*5

LM

Max. length of main tubing (at max. diameter)

<180*3

ℓ1, ℓ2... ℓ64

Max. length of each distribution tube

≤30

L1+ ℓ1+ ℓ2... ℓ63+ ℓA+ ℓB+LF+LG+LH

Total max. tubing length including length of each distribution tube (only liquid tubing)

≤1000

Maximum tubing length from outdoor’s 1st distribution joint to each outdoor unit

≤10

When outdoor unit is installed higher than indoor unit

≤50

When outdoor unit is installed lower than indoor unit

≤40

H2

Max. difference between indoor units

≤15*6

H3

Max. difference between outdoor units

≤4

L3

T-joint tubing (field-supply); Max. tubing length between the first T-joint and solidly welded-shut end point

≤2

ℓA, ℓB+LO, ℓC+LO

Allowable elevation difference

Contents

H1

NOTE supply reducer.) (Select the tube size from the table of main tube sizes on the following page reducer.) Determine the length less than the limitation of allowable maximum tubing length. (For the portion that exceeds 50 m, set based on the main tube sizes listed in the table on the following page.) * If the existing tubing is used, and the amount of on-site refrigerant charge exceeds the value listed below, then change the size of the tubing to reduce the amount of refrigerant.

16


FSV ME1 Series

Necessary Amount of Additional Refrigerant Charge Per Outdoor Unit U-8ME1H7

U-10ME1H7

U-12ME1H8

U-14ME1H8

U-16ME1H8

U-18ME1H8

U-20ME1H8

5.9 kg

6.6 kg

6.6 kg

7.8 kg

7.8 kg

8.5 kg

8.5 kg

System Limitations Max. No. allowable connected outdoor units

3*2

Max. capacity allowable connected outdoor units

168 kW (60 hp)

Max. connectable indoor units

64*1

Max. allowable indoor/outdoor capacity ratio umber is limited by the total capacity of the connected indoor units. ded.

Additional refrigerant charge Liquid tubing size

Amount of refrigerant charge/m (g/m)

ø6.35

26

ø9.52

56

ø12.7

128

ø15.88

185

ø19.05

259

ø22.22

366

ø25.4

490

Refrigerant tubing (Existing tubing can be used.) Tubing size (mm) Material O

Material 1/2H • H

ø6.35

t 0.8

ø22.22

t 1.0

ø9.52

t 0.8

ø25.4

t 1.0

ø12.7

t 0.8

ø28.58

t 1.0

ø15.88

t 1.0

ø31.75

t 1.0

ø19.05

t 1.2

ø38.1

over t 1.35

ø41.28

over t 1.45

17


Refrigerant Branch Pipes (optional accessories) for 2-Way ME1 Series Optional Distribution Joint Kits See the installation instructions packaged with the distribution joint kit for the installation procedure.

Model name

Cooling capacity after distribution

Remarks

1. CZ-P680PJ2

68.0 kW or less

for outdoor unit

2. CZ-P1350PJ2

168.0 kW or less

for outdoor unit

3. CZ-P160BK2

22.4 kW or less

for indoor unit

4. CZ-P680BK2

68.0 kW or less

for indoor unit

5. CZ-P1350BK2

168.0 kW or less

for indoor unit

Tubing size (with thermal insulation) 1. CZ-P680PJ2 for outdoor unit (Capacity after distribution joint is 68.0 kW or less.) GAS tUBING

LIqUID tUBING

175

175

B 135

B

D E F

G G

I H

I H

Distribution Joint

Distribution Joint

H I

G

E GF

E F

C

C

F

F D E F

97

F

G

G

H I

H I

F

72

C

110 H I 97

72

C 114

D

C

114

C

D

135

110

Insulation Reducing Joints Reducing Joints

Insulation

Unit: mm

Size of connection point on each part (Shown are inside diameters of tubing) Size

Part A

Part B

Part C

Part D

Part E

Part f

Part G

Part H

Part I

Dimension

Ø38.10

Ø31.75

Ø28.58

Ø25.40

Ø22.22

Ø19.05

Ø15.88

Ø12.70

Ø9.52

2. CZ-P1350PJ2 for outdoor unit (Capacity after distribution joint is greater than 68.0 kW and no more than 168.0 kW.) GAS tUBING

175 135

A

B

A

LIqUID tUBING

175 135 B

A

B

A

B

C

E F

C D

E

H I 97

H I

G

G G

F

G

G

H I

H I

Insulation Reducing Joints

F Reducing Joints

Unit: mm

Insulation Size of connection point on each part (Shown are inside diameters of tubing)

18

Size

Part A

Part B

Part C

Part D

Part E

Part f

Part G

Part H

Part I

Dimension

Ø38.10

Ø31.75

Ø28.58

Ø25.40

Ø22.22

Ø19.05

Ø15.88

Ø12.70

Ø9.52

F

72

I H Distribution Joint

Joint

D

97

E FG

I H

B

110

72

C D

F

E F

114

114

C D BDistribution

F

110


FSV ME1 Series

3. CZ-P160BK2 Use: For indoor unit (Capacity after distribution joint is 22.4 kW or less.) GAS tUBING

D E

C D EUnit: mm

D E

C

C

C D E

C C

D

Distribution Joint C

Insulation

72

A

72

C

D

72

Insulation

72

A

B Distribution B Joint

110 97

110 97

C

C B

B B

AB

A

LIqUID tUBING

110 97

110 97

Size of connection point on each part (Shown are inside diameters of tubing) Size

Part A

Part B

Part C

Part D

Part E

Dimension

Ø19.05

Ø15.88

Ø12.70

Ø9.52

Ø6.35

4. CZ-P680BK2 Use: For indoor unit (Capacity after distribution joint is greater than 22.4 kW and no more than 68.0 kW.) GAS tUBING

LIqUID tUBING

110 97

175 175 135 135 A

Insulation

A

A

B C D

B C D

E F

E F

B

C BD C ED F

E F

G F

G F E

E

E

E

E

E

F G H

F G H

F G HF G H

72

Distribution Joint

A

72

A

114

A

114

D C BD C B

110 97

Distribution Joint

Reducing Joints

Reducing Joints

Insulation Unit: mm

Size of connection point on each part (Shown are inside diameters of tubing) Size

Part A

Part B

Part C

Part D

Part E

Part f

Part G

Part H

Dimension

Ø28.58

Ø25.40

Ø22.22

Ø19.05

Ø15.88

Ø12.70

Ø9.52

Ø6.35

5. CZ-P1350BK2 Use: For indoor unit (Capacity after distribution joint is greater than 68.0 kW and no more than 168.0 kW.) GAS tUBING

B

Distribution Joint

C D E F

Insulation

G H

C D C D

G

G G

G

F

H

H

G

B

Distribution Joint

C D

H I J

E F G H

F G

72

B

F

72

C

B B

110 97

110 97

F

A

B

114

D

D C

A

114

A A

LIqUID tUBING

175 175135 135

H I J

Insulation Reducing Joints

Reducing Joints Unit: mm

Size of connection point on each part (Shown are inside diameters of tubing) Size

Part A

Part B

Part C

Part D

Part E

Part f

Part G

Part H

Part I

Part J

Dimension

Ø38.10

Ø31.75

Ø28.58

Ø25.40

Ø22.22

Ø19.05

Ø15.88

Ø12.70

Ø9.52

Ø6.35

19


For small-scale commercial and residential use

2-WAY mini-FSV LE1 Series REVERSE CYCLE HEAT PUMP 1 PHASE AND 3 PHASE OPTIONS

Panasonic 2-way mini FSV, 2-pipe heat pump is specifically designed for the most demanding applications. mini FSV is available in 3 sizes with cooling capacity ranges from 4 HP to 6 HP and up to 9 connectable indoor units (applicable for 6 HP).

• Top-class EER: 3.76 / COP: 4.21 (In case of 4HP) • Cooling operation is possible when outdoor

• Cooling operation is possible when outdoor • Heating operation is possible when outdoor

• One ampere starting current excellent efficiency • Auto restart from outdoor unit (outdoor UP/DOWN) • Demand response ready (Peak cut) ON 26˚C

OFF OFF

ON 23˚C

ON 25˚C

20


mini-FSV LE1 Series

Energy-saving concept. The use of energy saving design for the structure of fans, fan motors, compressors and heat exchangers resulted in high COP value which ranked as one the top class in the industry. In addition, use of highly efficient R410A refrigerant reduces CO2 emission and lowers operating costs. 2

4

6

Panasonic

1 Inverter

Large-capacity inverter compressor has been adopted. The inverter compressor is superior in performance with improved partial-load capacity.

2 Printed

The number of PCB was reduced from 3 into 2 pieces to improve maintenance work.

3 Accumulator

Bigger accumulator has been adopted to maintain compressor reliability because of the increased refrigerant quantity, which required an extended max piping length. Furthermore, the refrigerant pressure loss was reduced, which contributes to an improved operating efficiency.

4 DC Fan Motor

Checking load and outside temperature, the DC motor is controlled for optimum air volume.

Compressor

Circuit Board

7

3

5

The newly designed fan blades have been realized to inhibit air turbulence and to increase efficiency. As fan diameter has been increased to 490mm, the air volume has been increased by 12% whilst maintaining a low sound level.

5

Newly designed fan

6

Heat Exchanger The heat exchanger size and the copper tube sizes in the & Copper Tubes heat exchanger have been redesigned to increase efficiency.

1

7 Oil Separator

A new centrifugal separator has been adopted to improves oil separation efficiency and reduce refrigerant pressure loss.

21


2-WAY mini-fSV LE1 Series

System example An expansion from Panasonic VRf line up, the mini fSV is compatible with the same indoor units and controls as the rest of the fSV range. 4 - 6 HP

Refrigerant pipe

SYSTEM / HP

4 HP

5 HP

6 HP

Connectable Indoor Unit

6

8

9

Control line

Wide operating range • Cooling operation is possible when outdoor temperature as low as -10°C • Cooling operation is possible when outdoor temperature as high as 46°C • Heating operation is possible when outdoor temperature as low as -20°C The remote controller temperature setting offers a range from 16°C to 30°C. 4 - 6 HP Cooling: -10°C DB ~ 46°C DB Heating: -20°C WB ~ 24°C WB * When you specify and design the products, please refer capacity ratio in the data book.

Improved energy saving The operation efficiency has been improved using highly efficient R410A refrigerant, new DC Inverter compressor, new DC motor and new design of heat exchanger.

Cooling 4.5 4.4 4.3 4.2 4.1 4.0 3.9 3.8 3.7 3.6 3.5 3.4 3.3 3.2 3.1 3.0 2.9

Heating 4.20

3.61 3.45 3.25 3.01

4 HP

22

FS Multi

4.30

5 HP

6 HP

FSV

4.8 4.7 4.6 4.5 4.4 4.3 4.2 4.1 4.0 3.9 3.8 3.7 3.6 3.5 3.4 3.3 3.2

FS Multi

4.62

4.56

4.30 4.11

4.03 3.84

4 HP

5 HP

6 HP

FSV


mini-FSV LE1 Series

Demand response featuring inverter control technology, fSV systems are demand response ready. With this control, power consumption at times of peak load can be set in three steps to deliver optimum performance. This helps to reduce annual power consumption with minimal loss in comfort.

DRED

(Demand controller) Relay contact point:No voltage relay Current input is DC 24 V 10 mA DRM1 DRM2 DRM3

NEW

Simple demand response with the CZ-CAPDC3 Demand control terminal is available to control 0-50-75-100% of capacities.

Outdoor unit

Demand Response Signal

* CZ-CAPDC3 is required as an option * Complies with AS 4755 of Australia

Flexible Demand Response with the CZ-CAPDC2 *1

C

Terminal block

Power input

Power Input

DRM 1

0%

DRM 2

50%

DRM 3

75%

Normal operation

Set point

Setting is possible as 0% or in the range from 40 to 100% (in steps of 5%). At the time of shipping, setting has been done to the three steps of 0%, 70% and 100%. *1 Para I/O unit for outdoor unit (CZ-CAPDC2) is required to input the signal.

Time Power input Level 1

100% (Preset)

Level 2

70% (Preset)

Level 3

0% (Always in stop condition)

Possible to change 40-100%

23


2-WAY mini-FSV LE1 Series

Increased piping length for greater design exibility Adaptable to various building types and sizes (equivalent piping length 140m)

Height difference 50m*1

Actual piping lengh 120m

Level difference between indoor units 15m

*1: 40 m if the outdoor unit is below the indoor unit.

Max. total length:150m

Compact & exible design The slim and lightweight design can be installed in various places.

Single Split

Quiet mode 5dB can be reduced by setting. External input signal is also available.

24

FSV


mini-FSV LE1 Series

HP

4 HP

Model name

U-4LE1R5

Power supply

Capacity Heating

U-5LE1R8

U-6LE1R5

U-6LE1R8

kW

12.10

12.10

14.00

14.00

15.50

15.50

BTU/h

41,300

41,300

47,800

47,800

52,900

52,900

kW

12.50

12.50

16.00

16.00

18.00

18.00

BTU/h

42,700

42,700

54,600

54,600

61,400

61,400

Cooling

W/W

3.76

3.76

3.68

3.68

3.41

3.41

Heating

W/W

4.21

4.21

3.91

3.91

3.59

3.59

mm

1,330 x 940 x 340 (410*)

1,330 x 940 x 340 (410*)

1,330 x 940 x 340 (410*)

1,330 x 940 x 340 (410*)

1,330 x 940 x 340 (410*)

1,330 x 940 x 340 (410*)

Dimensions (H/W/D) Net weight

Electrical ratings

6 HP

U-5LE1R5

(50HZ) 220V/230V/240V/-1phase 380V/400V/415V/-3phase 220V/230V/240V/-1phase 380V/400V/415V/-3phase 220V/230V/240V/-1phase 380V/400V/415V/-3phase Cooling

EER/COP

5 HP U-4LE1R8

Cooling Heating

kg

104

103

104

103

104

103

Running current

A

13.9/13.3/12.7

4.9/4.7/4.5

16.3/15.6/14.9

5.7/5.4/5.2

21.5/20.5/19.7

7.5/7.1/6.9

Power input

kW

3.22

3.22

3.8

3.8

4.54

4.54

Running current

A

13.2/12.7/12.1

4.7/4.5/4.3

18.0/17.2/16.5

6.3/6.0/5.8

21.6/20.7/19.8

7.5/7.2/6.9

Power input

kW

2.97

2.97

4.09

4.09

5.02

5.02

Starting current

A

1/1/1

1/1/1

1/1/1

1/1/1

1/1/1

1/1/1

Air flow rate

L/s

1,583

1,583

1,733

1,733

1,733

1,733

Refrigerant amount at shipment Piping connection

kg

R410A 3.50

R410A 3.50

R410A 3.50

R410A 3.50

R410A 3.50

R410A 3.50

Gas pipe

mm

15.88

15.88

15.88

15.88

19.05

19.05

Liquid pipe

mm

9.52

9.52

9.52

9.52

9.52

9.52

Normal mode

dB(A)

52/54: Cooling/Heating

52/54: Cooling/Heating

53/55: Cooling/Heating

53/55: Cooling/Heating

54/57: Cooling/Heating

54/57: Cooling/Heating

Silent mode

dB(A)

49/51: Cooling/Heating

49/51: Cooling/Heating

50/52: Cooling/Heating

50/52: Cooling/Heating

51/54: Cooling/Heating

51/54: Cooling/Heating

Normal mode

dB(A)

70/72: Cooling/Heating

70/72: Cooling/Heating

71/73: Cooling/Heating

71/73: Cooling/Heating

72/75: Cooling/Heating

72/75: Cooling/Heating

Ambient temperature operating range

* As a foot print.

Heating

Indoor air temperature

27˚C DB / 19˚C WB

20˚C DB

Outdoor air temperature

35˚C DB

7˚C DB / 6˚C WB

Dimensions

660

170 105

219

50 13

26

Air intake

2 x ø32 holes (holes for drain) Of the 4 ø32 holes , use 1 of the 2 holes speci ed for drain use to install the port. Use rubber plugs to seal the remaining 3 holes.

4

110

75 75

(10)

Cooling

20

Air discharge

13

410

2 380

20

290

340

Mounting hole (4-R6.5), anchor bolt : M10 Refrigerant tubing (liquid tube), flared connection (ø9.52) Refrigerant tubing (gas tube), flared connection (ø15.88) Refrigerant tubing port Electrical wiring port (ø16) Electrical wiring port (ø19) Electrical wiring port (ø29) Electrical wiring port (ø38)

1

18

3 4 5 6 7 8

1 940

2 3

Air discharge

Air intake

1330

6 7

5

8 30

592

4

4

60 9

55

60 87

20 64

47

8

49 71

7

10

6

110

5

110

47

30

573

20

49

GLOBAL REMARKS

20

Sound power level

24 71

Sound pressure level

Unit: mm

25


Distribution Joint Kits CZ-P160BK2

(Capacity after distribution joint is 16.00kW or less).

GAS TUBING

B

C

D

Insulation

D E

C D E

D E

C

C

D EC

C C

D

Distribution C Joint

Size of connection point on each part (Shown are inside diameters of tubing) Size

Part A

Part B

Part C

Part D

Part E

Dimension

Wiring System Diagrams 3-3. Wiring System Diagrams

Indoor unit (No. 1)

Power supply

L 220 – 240V ~50/60Hz N

Ground

Remote controller WHT BLK

1 2

B

Power supply 220 – 240 V, Single-phase, ~ 50 Hz C U1

U1 U2

D 1 2

C

L 220 – 240V ~50/60Hz N

1 2

Ground

L N

Ground WHT BLK

Ground

Indoor unit (No. 2)

Power supply

B

In case of 3-phase power supply Outdoor unit : 3-phase model U1 U2

L1 L2 L3 N

A

L1 L2 L3 N

Ground

R1 R2

1 2

C

Ground

Group control: L 220 – 240V ~50/60Hz N

Outdoor unit : 3-phase model

Outdoor unit : single-phase model

Indoor unit (No. 3)

Power supply

Power supply 380 – 415V, 3-phase, ~50Hz

U1 U2

D

L

4P terminal board

2P terminal board

N

Ground

B

Ground

Ground

U2

Ground

R1 R2

Remote controller

Outdoor unit : single-phase model

L N

E

U1 U2 U1

U1

U2

U2

R1 R2

C

L N

Ground

Ground WHT BLK

A

1 2

L N Power supply

L1

U1 U2 Inter-unit control wiring

B D

1 2

Indoor unit 7P terminal board

U1 U2 R1 R2

Mains cable rated for individual requirements

B C

Sheilded 0.75mm twin core

D

Non sheilded 0.75mm twin core

L N Power supply

U1 U2 R1 R2 Unit Remote control controller wiring line T1, F1, E1, D1, L1 Types 6P terminal board

L N U1 U2 Power Unit supply control line

R1 R2 Remote control line

U1, Y1, M1, P1, R1 Types

5P terminal board

L N Power supply

U1 U2 Unit control line K1 Type

Fig. 2-1

26

L2

L3

N

Power supply

Indoor unit (No. n)

L 220 – 240V ~50/60Hz N

Power supply

Remote controller

Ground

U1 U2 Inter-unit control wiring

72

Insulation

A

A

72

BDistribution Joint

72

A

110 97

110 97

C

C B

B

72

B

AB

LIQUID TUBING

110 97

110 97


mini-FSV LE1 Series

Piping design Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below.

LA

LB

LC

L1 L2

LD

n

Less than 400 mm

Main tube of unit

H1

For extension

1st branch

L3

1

3

2

n-1

H2

Unit distribution tube Distribution joint (CZ-P160BK2) Ball valve (field supply)

Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights Items

Marks

Allowable tubing length

Contents

120

Equivalent length

140

L1

Max. tubing length

∆L (L2 – L3)

Difference between max. length and min. length from the No.1 distribution joint

40

1,

2... n

Max. length of each distribution tube

30

1,

2... n-1+L1

Total max. tubing length including length of each distribution tube (only narrow tubing)

150

When outdoor unit is installed higher than indoor unit

50

When outdoor unit is installed lower than indoor unit

40

Max. difference between indoor units

15

H1

Allowable elevation difference

Length (m) Actual length

H2

Tubing Size Main Tubing Size After Distribution (LB, LC...)

Main Tubing Size (LA) 4HP

5HP

6HP

System kilowatts

12.1

14.0

15.5

Gas tubing (mm)

ø15.88

Liquid tubing (mm)

ø9.52

ø19.05

Total Below kW capacity after Over kW distribution Tubing size

Gas tubing (mm)

7.1

12.1

7.1

ø12.7

ø15.88

Liquid tubing (mm) ø9.52

14.0

15.5 ø19.05

ø9.52

the main tube of the unit (LA) should be ø19.05. Convert ø19.05 to ø15.88 using a reducer (field supply) close to the indoor unit and then make the connection.

total capacity of the outdoor units, select the main tubing size for the total capacity of the outdoor units.

System Limitations

Indoor Unit Tubing Connection ( 1, 2... n–1)

Outdoor units

4HP

Number of max. 6 connectable indoor units

5HP

6HP

8

9

Indoor unite type

22

Gas tubing (mm)

ø12.7

28

36

45

56

ø15.88

73

90

Liquid tubing (mm)

ø6.35

ø9.52

106 140 160

Max. allowable indoor/ outdoor capacity ratio

27


Simultaneous heating and cooling VRF system

3-WAY FSV MF2 Series Heat Recovery

New 3-WAY FSV MF2 series enables simultaneous heating and cooling operation • Conforms to COP 4.77 as one of the top class in the industry average • Simultaneous cooling or heating operation for up to 40 indoor units • Space saving installation - one of the top class in the industry

Heating

Cooling 28

* Office building with diverse room temperatures due to the different amount of sunshine received. * The building with computer/business equipment rooms requiring year-round cooling.


FSV MF2 Series

The advanced technology Fan guard DC fan motor

5 types of outdoor units with different capacities have been standardized to one compact casing size. This enables a neat installation finish with superb space saving when rows of units are installed together.

Improved operation efficiency

In addition to the development of a new DC fan motor with high output and high efficiency, the output loss has been reduced by reducing the resistance of the fan guard. This contributes widely to COP increase.

In comparison with the conventional low-pressure The constant-speed scroll, the oil behaviour is stabilized, COP is improved, compressor adopts and the reliability is also improved. a high-performance internal high-pressure scroll

Machine room

Compressor (rear of the machine room)

Standardization of outdoor units to one compact casing size

Heat exchanger

Improvement of the heat exchanger

Hairpin heat exchangers with a diameter of 7 mm increase heat transfer co-efficient.

Relayout of structural parts

Noise level has been reduced by positioning the compressors in a special machine room at the bottom.

Close side-byside installation is possible

The mounting fittings for the outdoor unit have been changed to the front and the rear, so that the units can be installed side by side with just 100 mm between units and reduction of the installation space has been realized.

29


Simultaneous heating and cooling VRF system

3-WAY FSV MF2 Series Fully-automatic simultaneous cooling/heating operation and heat recovery 3-Way MF2 Series enables simultaneous heating and cooling operation via the solenoid valve kit.

CZ-P56HR3 For indoor units under 5.6kW

CZ-P160HR3 For indoor units under 16.0kW

Solenoid valve controller CZ-CAPE2

Individual control of multiple indoor units with solenoid valve kits • Any design and layout can be used in a single system. • Cooling operation is possible up to an outdoor temperature of -10˚C.

System example

Cooling

Heating

Heating

Stop

Up to max. 40 indoor units

Liquid pipe medium-temperature, medium-pressure liquid pipe

Cooling

Stop

Individual operation

Discharge pipe high-temperature, high-pressure gas pipe

Suction pipe low-temperature, low-pressure gas pipe

* When individually controlled with one solenoid valve kit, address setting is required on site.

30


FSV MF2 Series

Increased max. number of connectable indoor units The 3-WAY MF2 series has five DC inverter outdoor units from 8 HP to 16 HP as the basic models, and by combination of up to three units, an air-conditioning capacity of 8 HP to 48 HP can be set according to the user needs. System (HP)

8

10

12

14

16

18

20

22

24

26

28

30

32

34

36

38

40

42

44

46

48

8

10

12

14

16

10

10

12

14

16

16

16

16

10

10

10

10

10

12

14

16

8

10

10

10

10

12

14

16

10

10

12

14

16

16

16

16

14

16

16

16

16

16

16

16

40

40

40

40

40

40

40

40

Outdoor units Connectable indoor units

13

16

19

23

26

29

33

36

40

40

40

40

40

Long piping design Adaptable to various building types and sizes Actual piping length : 180m Max piping length : 500m

System difference of elevation:

50 m*

1

Actual length:

15 m

180 m

Difference in elevation between indoor units: *1: 40 m if the outdoor unit is below the indoor unit.

Max. total length:500 m

Excellent energy saving The operation efficiency has been improved using highly efficient R410A refrigerant, new DC inverter compressor, new DC motor and new fan guard with low-loss wire guard. In addition, the heat exchanger has been redesigned from 4-direction suction to 3-direction suction to improve cosmetic appeal and unify appearance with ME1 models.

4.2

4.09

4.1

3.95

4.0

3.91

3.9 3.8

3.81

3.78

3.79

3.7 3.6

3.45

3.5

3.41

3.45 3.38

3.4 3.3 Cooling Heating

Cooling Heating

Cooling Heating

Cooling Heating

Cooling Heating

8 HP

10 HP

12 HP

14 HP

16 HP

Connectable indoor/outdoor unit capacity ratio up to 130%

31


Simultaneous heating and cooling VRF system

3-WAY FSV MF2 Series Extended operating range Cooling operation range:

Outside air temperature (˚C DB)

The cooling operation range has been extended to -10˚C by changing the outdoor fan to an inverter type.

FSV MF1 -20

-10

0

10

20

30

40

43

50

Heating operation range:

Stable heating operation even with an outside air temperature of -20˚C The heating operation range has been extended to -20˚C by use of a compressor with a high-pressure vessel.

Outside air temperature (˚C WB)

FSV MF1

-20

-10

0

10

16

20

30

40

50

Wide temperature setting range

Wired remote control heating temperature

Compactness for superb space saving and low noise level

930

Operating sound

1000 Installation space: 0093m2 (In case of 16HP)

60 59 58 57 56 55 54 53 52 51 50

dB(A)

8 HP

10 HP

55

54.5

Standard

Silent mode

3-WAY FSV MF2

32

52

51.5 Standard

Silent mode

3-WAY FSV MF2


FSV MF2 Series

Excellent cost saving and realization of smaller piping size By adoption of R410A with low pressure loss, it became possible to reduce the pipe sizes for discharge, suction and liquid pipes. This makes it possible to aim for reduced piping space, improved workability at the site, and reduction of the piping material costs.

Piping

Insulation ø19.05

8 HP ø15.88

ø9.52

ø22.22

10 HP ø19.05

ø9.52

3-WAY FSV MF2 HP

Suction pipe

Discharge pipe

Discharge pipe

8

ø19.05

ø15.88

ø9.52

10

ø22.22

ø19.05

ø9.52

Non-stop operation during maintenance Even when an indoor unit needs maintenance, the other indoor units can be kept operating by setting. (Not applicable for all situations)

Power suppression control for energy saving (Demand control) *1 The 3-WAY FSV MF2 series has a built-in demand function which uses the inverter characteristics. With this demand function, the power consumption can be set in three steps, and operation*2 at optimum performance is performed according to the setting and the power consumption. This function is useful to reduce the annual power consumption and to save electricity fees while maintaining comfort. (*1) An outdoor Seri-Para I/O unit is required for demand input.

Extended compressor life The total operation time of the compressors is monitored by a microcomputer, so that there is no unbalance for the operation times of all compressors in the same refrigerant system, and compressors with a shorter operation time are operated with preference. System example

A,C: DC inverter compressor B,D: Constant speed compressor

Load increase

A B

C D

50h

60h 10h

30h

Load increase

A B

C D

Load increase

A B

C D

A B

C D

33


3-WAY 3-WAYFSV FSVMF2 MF2Series Series Appearance Appearance

HP

HP

8

8

10

10

12

12

14

14

16

16

18

18

20

20

22

22

24

U-8MF2E8U-10MF2E8 U-10MF2E8 U-10MF2E8 U-10MF2E8 U-8MF2E8 U-10MF2E8 U-10MF2E8 U-8MF2E8U-10MF2E8 U-10MF2E8 U-12MF2E8 U-14MF2E8 U-16MF2E8 U-8MF2E8 U-12MF2E8 U-14MF2E8 U-16MF2E8 U-10MF2E8 U-10MF2E8 U-12MF2E8 U-14MF2E8 U-10MF2E8 U-10MF2E8 U-12MF2E8 U-14MF2E8

Model Model namename supply PowerPower supply

380/400/415V-3phase/50Hz 380/400/415V-3phase/50Hz

Cooling Cooling Capacity Capacity Heating Heating Cooling Cooling EER /EER COP/ COP Heating Heating

kW kW22.4 22.4

28.0 28.0

33.5 33.5

40.0 40.0

45.0 45.0

50.4 50.4

56.0 56.0

61.5 61.5

68.0 68.0

BTU/hBTU/h 76,500 76,500

95,600 95,600

114,300 114,300

136,500 136,500

153,600 153,600

172,000 172,000

191,100 191,100

209,900 209,900

232,100 232,100

kW kW25.0 25.0

31.5 31.5

37.5 37.5

45.0 45.0

50.0 50.0

56.5 56.5

63.0 63.0

69.0 69.0

76.5 76.5

BTU/hBTU/h 85,300 85,300

107,500 107,500

128,000 128,000

153,600 153,600

170,600 170,600

192,800 192,800

215,000 215,000

235,500 235,500

261,100 261,100

W/W W/W 4.50 4.50

4.10 4.10

3.41 3.41

3.70 3.70

3.38 3.38

4.27 4.27

3.97 3.97

3.8 3.8

3.65 3.65

W/W W/W 4.77 4.77

4.55 4.55

4.30 4.30

4.41 4.41

4.03 4.03

4.63 4.63

4.47 4.47

4.57 4.57

4.2 4.2

Dimensions Dimensions H x WHxxDW x D

1,887x890x1,887x890x 1,887x890x1,887x890x 1,887x890x1,887x890x 1,887x890x1,887x890x 1,887x890x1,887x1,880x 1,887x1,880x 1,887x1,880x 1,887x1,880x 1,887x1,880x 1,887x890x 1,887x1,880x 1,887x1,880x 1,887x1,880x mm mm 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60)

Net weight Net weight

kg

kg269 269

269 269

314 314

322 322

322 322

583 583

583 583

591 591

591 591

Running Running currentcurrent A Cooling Cooling Electrical Electrical PowerPower input input kW ratings ratings Running Running currentcurrent A Heating Heating PowerPower input input kW

A 8.6/8.17/7.96 8.6/8.17/7.96 11.3/10.8/10.6 11.3/10.8/10.6 15.1/14.5/14.1 15.1/14.5/14.1 19.2/18.4/17.9 19.2/18.4/17.9 22.0/21.1/20.6 22.0/21.1/20.6 19.7/18.9/18.4 19.7/18.9/18.4 23.8/22.9/22.3 23.8/22.9/22.3 27/26/25.3 27/26/25.330.9/29.7/28.9 30.9/29.7/28.9

kW5.24 5.24

6.92 6.92

8.72 8.72

10.2 10.2

12.4 12.4

12.2 12.2

14.1 14.1

15.1 15.1

18.2 18.2

Airrate flow rate Air flow

L/s

L/s2,6332,633

2,9662,966

3,5333,533

3,5333,533

3,5333,533

5,6005,600

6,1666,166

6,1666,166

6,1666,166

Refrigerant amount at shipment Refrigerant amount at shipment

kg

kg8.3 8.3

8.5 8.5

8.8 8.8

9.3 9.3

9.3 9.3

17

Suction Suction pipe pipe Discharge pipe pipe PipingPiping Discharge connections connections LiquidLiquid pipe pipe Balance Balance pipe pipe

kW4.98 4.98

6.83 6.83

9.05 9.05

11.6 11.6

13.3 13.3

11.8 11.8

14.1 14.1

16.2 16.2

18.5 18.5

A 8.95/8.5/8.28 8.95/8.5/8.28 1.6/11.0/10.7 1.6/11.0/10.7 14.7/14.1/13.8 14.7/14.1/13.8 17/16.4/15.9 17/16.4/15.9 20.7/19.9/19.4 20.7/19.9/19.4 20.4/19.6/19.1 20.4/19.6/19.1 23.8/22.9/22.3 23.8/22.9/22.3 25.2/24.2/23.6 25.2/24.2/23.6 30.4/29.2/28.5 30.4/29.2/28.5

17

17

17

18

18

18

mm mm mm mm mm mm Cooling: Cooling: - 10˚C- 10˚C (DB) ~+40˚C (DB) ~+40˚C (DB) (DB) Heating Heating -25˚C-25˚C (WB) (WB) ~ +18˚C ~ +18˚C (WB) (WB) Simultaneous Simultaneous operation operation -10˚C-10˚C ~ +24 ~ (DB) +24 (DB)

dBA dBA 57

57

59

59

60

60

62

62

62

62

61

61

62.5 62.5

63

63

63

dBA dBA 54

54

56

56

58

58

59

59

59

59

58

58

59.5 59.5

60

60

77.5 77.5

TheseThese specifications specifications subject subject to change to change without without notice. notice. Cooling Cooling Heating Heating heating and cooling operation with an outdoor temperature in excess of * For mixed * For mixed heating and cooling operation with an outdoor temperature in excess of GLOBAL GLOBAL Indoor Indoor air temperature air temperature27˚C 27˚C DB / 19˚C DB / 19˚C WB WB20˚C 20˚C DB DB REMARKS REMARKS cooling cooling operation. operation. Outdoor Outdoor air temperature air temperature 35˚C 35˚C DB DB 7˚C DB 7˚C/ 6˚C DB /WB 6˚C WB

System System example example Outdoor Outdoor unit unit

SinceSince all pipings all pipings are concentrated are concentrated into one into one pipe shaft, you can youminimise can minimise pipingpiping spacespace Concentration Concentrationpipe shaft, and construction and construction labour. labour.

Connection Connection

MF2 series MF2 series makemake it possible it possible to linktooutdoor link outdoor units together units together for a large for a large capacity capacity (48 HP) (48 HP)

Solenoid Solenoid valve valve kit kit

If indoor/outdoor If indoor/outdoor units need units need servicing, servicing, a balla ball valve valve (optional) (optional) cuts off cuts non-operational off non-operational units units to let to other let other units stay unitsrunning. stay running. IndoorIndoor unit unit System System limitations limitations Maximum Maximum number number of combined of combined outdoor outdoor units units

3

Maximum Maximum HP ofHP combined of combined outdoor outdoor units units

48 HP48 HP

3

Maximum Maximum number number of connectable of connectable indoorindoor units units

40

Maximum Maximum pipingpiping lengthlength per indoor per indoor unit unit

Addition Addition

40

Indoor/outdoor Indoor/outdoor unit capacity unit capacity ratio ratio 180 m180 m

Maximum Maximum level difference level difference (when(when outdoor outdoor unit isunit lower) is lower) 50 (40) 50m (40) m Maximum Maximum total piping total piping lengthlength

18

mm mm

Ambient Ambient temperature temperature operating operating rangerange Sound Sound Normal Normal modemode pressure pressure SilentSilent modemode level level

34

24

500 m500 m

If yourIf indoor your indoor capacity capacity load changes load changes in theinfuture, the future, it’s easy it’s to easy addtoon add both on indoor both indoor and and outdoor outdoor units using units using the same the same pipings. pipings. If the Ifadditional the additional installment installment of outdoor of outdoor and indoor and indoor units is units expected, is expected, the size theofsize refrigerant of refrigerant pipingpiping should should be decided be decided according according to thetototal thecapacity total capacity after the afteraddition. the addition.

63


FSV FSV MF2 MF2 Series Series

26

26

28

30

28

30

32

34

32

34

36

38

36

40

38

42

40

42

44

44

46

46

48

48

U-10MF2E8 U-10MF2E8 U-10MF2E8 U-10MF2E8 U-10MF2E8 U-10MF2E8 U-10MF2E8 U-10MF2E8 U-10MF2E8 U-10MF2E8 U-12MF2E8 U-12MF2E8 U-14MF2E8 U-14MF2E8 U-16MF2E8 U-16MF2E8 U-10MF2E8 U-12MF2E8 U-14MF2E8 U-16MF2E8 U-10MF2E8 U-12MF2E8 U-14MF2E8 U-16MF2E8 U-10MF2E8 U-10MF2E8 U-10MF2E8 U-10MF2E8 U-12MF2E8 U-12MF2E8 U-14MF2E8 U-14MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-14MF2E8 U-14MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 U-16MF2E8 380/400/415V-3phase/50Hz 380/400/415V-3phase/50Hz 73.0 73.0

78.5 78.5

85.0 85.0

90.0 90.0

96.0 96.0

101.0101.0

107.0107.0

113.0113.0

118.0118.0

124.0124.0

130.0130.0

135.0135.0

249,100 249,100

267,900 267,900

290,100 290,100

307,100 307,100

327,600 327,600

344,700 344,700

363,400 363,400

385,600 385,600

402,700 402,700

421,400 421,400

443,600 443,600

460,700 460,700

81.5 81.5

87.5 87.5

95.0 95.0

100.0100.0

108.0108.0

113.0113.0

119.0119.0

127.0127.0

132.0132.0

138.0138.0

145.0145.0

150.0150.0

278,100 278,100

300,300 300,300

324,200 324,200

343,000 343,000

368,500 368,500

385,600 385,600

407,800 407,800

431,700 431,700

450,400 450,400

470,900 470,900

494,800 494,800

511,900 511,900

3.41 3.41

3.40 3.40

3.41 3.41

3.38 3.38

3.45 3.45

3.41 3.41

3.42 3.42

3.42 3.42

3.40 3.40

3.41 3.41

3.40 3.40

3.38 3.38

3.84 3.84

3.80 3.80

3.85 3.85

3.79 3.79

3.93 3.93

3.88 3.88

3.84 3.84

3.88 3.88

3.84 3.84

3.81 3.81

3.83 3.83

3.79 3.79

1,887x1,880x 1,887x1,880x 1,887x1,880x 1,887x1,880x 1,887x2,870x 1,887x2,870x 1,887x2,870x 1,887x2,870x 1,887x2,870x 1,887x2,870x 1,887x2,870x 1,887x2,870x 1,887x1,880x 1,887x1,880x 1,887x1,880x 1,887x1,880x 1,887x2,870x 1,887x2,870x 1,887x2,870x 1,887x2,870x 1,887x2,870x 1,887x2,870x 1,887x2,870x 1,887x2,870x 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 890(+60) 636 636

644 644

644 644

644 644

905 905

913 913

913 913

913 913

966 966

966 966

966 966

966 966

33.7/32.4/31.5 33.7/32.4/31.5 37.2/35.7/34.8 37.2/35.7/34.8 41.1/39.5/38.5 41.1/39.5/38.5 43.9/42.2/41.1 43.9/42.2/41.1 42.9/41.2/39.7 42.9/41.2/39.7 46.1/44.3/43.1 46.1/44.3/43.1 59.6/47.6/46.4 59.6/47.6/46.4 53.1/51.0/49.7 53.1/51.0/49.7 56/53.8/52.4 56/53.8/52.4 59.6/57.3/55.8 59.6/57.3/55.8 63.8/61.3/59.7 63.8/61.3/59.7 65.9/63.3/61.7 65.9/63.3/61.7 20.4 20.4

22.5 22.5

24.9 24.9

26.6 26.6

25.7 25.7

27.6 27.6

29.7 29.7

31.8 31.8

33.9 33.9

36.1 36.1

38.2 38.2

39.9 39.9

31.1/29.2/28.5 31.1/29.2/28.5 31.1/29.8/29.1 31.1/29.8/29.1 32.6/31.3/30.5 32.6/31.3/30.5 37.7/36.2/35.3 37.7/36.2/35.3 41.7/40.1/39.1 41.7/40.1/39.1 41/39.4/38.4 41/39.4/38.4 41.6/39.9/38.9 41.6/39.9/38.9 52.2/49.6/47.8 52.2/49.6/47.8 49.3/47.3/46.1 49.3/47.3/46.1 53.8/51.6/50.3 53.8/51.6/50.3 58.8/56.5/55.0 58.8/56.5/55.0 62.6/60.1/58.6 62.6/60.1/58.6 18.6 18.6

19.5 19.5

22.6 22.6

24.8 24.8

24.3 24.3

25

27.5 27.5

30.8 30.8

29.6 29.6

32.1 32.1

35

7,0667,066

7,0667,066

7,0667,066

7,0667,066

9,7009,700

9,7009,700

9,7009,700

9,7009,700

10,600 10,600

10,600 10,600

10,600 10,600

10,600 10,600

18

19

19

19

19

26

27

27

27

28

28

28

28

28

28

64.5 64.5

65

65

65

65

65

65

65

65

65.5 65.5

65.5 65.5

65.5 65.5

67

67

67

67

67

67

67

67

61.5 61.5

62

62

62

62

62

62

62

62

62.5 62.5

62.5 62.5

62.5 62.5

64

64

64

64

64

64

64

64

18

19

19

26

25 27

27

27

28

28

35

37

37

Cooling: - 10˚C- 10˚C (DB) ~+40˚C (DB) (DB) Heating -25˚C-25˚C (WB) (WB) ~ +18˚C (WB) (WB) Simultaneous operation -10˚C-10˚C ~ +24 Cooling: (DB) ~+40˚C Heating ~ +18˚C Simultaneous operation ~ (DB) +24 (DB)

Dimensions Dimensions

Air discharge Air discharge Electrical Electrical component component box box

Front view Front view

4

4

3

3

2

2

1

1

1 Installation 1 Installation holes holes (8-15x21 (8-15x21 elongated elongated holes)holes) anchor anchor bolts bolts M12 or M12 larger. or larger. 2 Pressure 2 Pressure outletoutlet port (for porthigh (for high pressure: pressure: Ø7.94Ø7.94 Scrader-type Scrader-type connection). connection). 3 Pressure 3 Pressure outletoutlet port (for portlow (for low pressure: pressure: Ø7.94Ø7.94 Scrader-type Scrader-type connection). connection). hole for hole connecting for connecting 4 Knock-out 4 Knock-out pressure pressure gaugegauge (optional). (optional). 5 Terminal 5 Terminal board.board. 6 Terminal 6 Terminal boardboard (for inter(for intercontrol control wiring). wiring). outdoor-unit outdoor-unit * Installation * Installation fixing fixing bracket, bracket, installation installation side. side.

Air intake Air intake

(installation (installation hole pitch) hole pitch)

4

4

3

3

2

2

Top view Top view 1 1 A 894A(installation 894 (installation hole pitch). hole pitch). The tubing The tubing is routed is routed out from out from the front the front B 730B(installation 730 (installation hole pitch). hole pitch). The tubing The tubing is routed is routed out from out from the front the front C 730C(installation 730 (installation hole pitch). hole pitch).

35


Piping design 1. 2. 3.

Main piping length LM = LA + LB 80 m Main distribution pipes LC-LH are selected according to the capacity after the distribution joint. Size of indoor unit connection piping 1-40 are determined by the connection piping size on the indoor units.

L5

H3

C

L2 LM B

Balance pipe (ø 6.35)

L1

A LO

LB

LC

LD

LE

LA H1 4 LF Within 400 mm

6

5

40

For extension For extension

Within 400 mm

LH

1

LG

Solenoid Valve Kit 2

H2

3

L4

Symbol explanation Distribution joint (CZ-accessory, option) Ball valve (BV, option) Note: Do not use commercial T-pieces for the liquid pipes of and . * Be sure to use R410A distribution joints for outdoor unit connections and piping branches.

Ranges that apply to refrigerant piping lengths and to differences in installation heights Items

Allowable piping length

Allowable elevation difference

Mark

Contents

Length (m) Actual piping length

< =180 < =200

L1

Max. piping length

Δ L (L2 - L4)

Difference between the max. length and the min. length from the No.1 distribution joint

LM

Max. length of main piping (at max. diameter)

1, 2~40

Max. length of each distribution

< =80 < =30

L1+1+2+ ~ 40 +A+B+LF+LG+LH

Total max. piping length including length of each distribution (only narrow tubing)

< =500

L5

Distance between outdoor units

< =10 < =50

H1

Equivalent piping length

When outdoor unit is installed higher than indoor unit When outdoor unit is installed lower than indoor unit

H2

Max. difference between indoor units

H3

Max. difference between outdoor units

< =40

< =40 < =15 < =4

Note 1: The outdoor connection main piping (LO part) depends on the total capacity of the outdoor units connected to the end. Note 2: When the main piping length (L1) (equivalent length) exceeds 90 m, increase the size of both the gas and liquid main piping (LM) by 1 step.

36


FSV MF2 Series

System limitations Max. number of combined outdoor units

3

Max. HP of combined outdoor units

135 kW (48 hp)

Max. number of connectable indoor units

40

Indoor/outdoor unit capacity ratio

50-130%

Additional refrigerant charge Liquid piping size

Amount of refrigerant charge/m (g/m)

ø6.35

26

ø9.52

56

ø12.7

128

ø15.88

185

ø19.05

259

ø22.22

366

ø25.4

490

Distribution joint kits Remarks For outdoor unit

For indoor unit

Model name

Cooling capacity after distribution

1. CZ-P680PH2

68.0 kW or less

2. CZ-P1350PH2

135.0 kW or less

3. CZ-P224BH2

22.4 kW or less

4. CZ-P680BH2

68.0 kW or less

5. CZ-P1350BH2

135.0 kW or less

Refrigerant piping Piping size (mm) Material O

1/2 H, H material

Outer diameter

Wall thickness

Outer diameter

Wall thickness

ø6.35

t 0.8

ø 25.4

t 1.0

ø9.52

t 0.8

ø 28.58

t 1.0

ø12.7

t 0.8

ø 31.75

t 1.1

ø15.88

t 1.0

ø 38.1

t 1.15

ø19.05

t 1.0

ø 41.28

t 1.20

ø22.22

t 1.15

Note: When pipe bending is to be performed, the bending radius shall be at least 4 times the outer diameter. Also, take sufficient care to prevent pipe collapse and damage at the time of bending.

37


Refrigerant Branch Pipes (optional accessories) for 3-Way MF2 Series Optional Distribution Joint Kits

See the installation instructions packaged with the distribution joint kit for the installation procedure. Model name

capacity after distribution JOINT

Remarks

1. CZ-P680PH2

68.0 kW or less

For outdoor unit

2. CZ-P1350PH2

greater than 68.0 kW and no more than 135.0 kW

For outdoor unit

3. CZ-P224BH2

22.4 kW or less

For indoor unit

4. CZ-P680BH2

greater than 22.4 kW and no more than 68.0 kW

For indoor unit

5. CZ-P1350BH2

greater than 68.0 kW and no more than 135.0 kW

For indoor unit

1. CZ-P680PH2

Use: For outdoor unit (Capacity after distribution joint is 68.0 kW or less.) DISCHARGE PIPE

490 490490

490 490490

300 300300

300 300300 C CC C CDC DEDEFE FF

230 230230

D DD D DED EFE FGF GG

838383

126 126 126

112 112112

D DDD DD

E EDE DCD CC C CC

C CC C CC D DD E EE F FF

101 101101

230 230230

G GG GFG FEF EE

I II H HH G GG G GG F FF E EE

H HIH I I 340 340340

D DD D DD E EE F FF G GG

Insulator

E EFE GFF GGG GG

I HI I HH

126 126 126

C CCC CC

C CC

LIQUID PIPE

130 130 130

SUCTION PIPE

Insulator

505050

Insulator Unit: mm

Dimensions for connections of each part Position

A

B

C

D

E

F

G

H

I

J

Dimension

Ø38.10

Ø31.75

Ø28.58

Ø25.40

Ø22.22

Ø19.05

Ø15.88

Ø12.70

Ø9.52

Ø6.35

2. CZ-P1350PH2

Use: For outdoor unit (Capacity after distribution joint is greater than 68.0 kW and no more than 135.0 kW.) DISCHARGE PIPE

LIQUID PIPE

615

I H G

490

375

300

B B C D

315

112

C

C

53

180

10 5

C

D C C

B B A C C D E F

C DEF 112

B A

G GF E 126

B B

B A

I H

G F E

E FG G

130

SUCTION PIPE

H I 50

340

C C D E F

230

66 Insulator

Insulator

Insulator

Unit: mm Dimensions for connections of each part Position

A

B

C

D

E

F

G

H

I

J

Dimension

Ø38.10

Ø31.75

Ø28.58

Ø25.40

Ø22.22

Ø19.05

Ø15.88

Ø12.70

Ø9.52

Ø6.35

Example: (F below indicates inner diameter. F below indicates outer diameter.)

38


FSV MF2 Series

3. CZ-P224BH2.

Use: For indoor unit (Capacity after distribution joint is 22.4 kW or less.) DISCHARGE PIPE 186

55

G H

F F 145

H

H G

H H G

136

55

G H

H

40

92

GH

7

F

F

235

Insulator

I H

77

F

12

210 G F

LIQUID PIPE

I H

HI

69

SUCTION PIPE

Insulator

Insulator

Unit: mm

Dimensions for connections of each part Position

A

B

C

D

E

F

G

H

I

J

Dimension

Ø38.10

Ø31.75

Ø28.58

Ø25.40

Ø22.22

Ø19.05

Ø15.88

Ø12.70

Ø9.52

Ø6.35

4. CZ-P680BH2.

Use: For indoor unit (Capacity after distribution joint is greater than 22.4 kW and no more than 68.0 kW.) DISCHARGE PIPE

300 300300

300 300300 16 16 16

DDD DDD EEE FFF FFF G G G HHH 230 230230

G G G GFGFE FE E

II I HHH GG G GGG FFF EEE

E EFEFGFG GG G G

340 340340

H HI HI I 505050

Insulator

Unit: mm

I IH IH H

55 55 55

74 74 74

55 55 55

FFF GGG 230 230230

112 112112

126 126 126

112 112112 CCC CCC DDD EEE FFF

D D D DEDEF EF F

F FE FED EDCDC C C C

126 126 126

16 16 16

C C CC CDCDE DEF EF F

F FE FED EDCDC CC C C

LIQUID PIPE

130 130 130

SUCTION PIPE

Insulator

Insulator

Dimensions for connections of each part Position

A

B

C

D

E

F

G

H

I

J

Dimension

Ø38.10

Ø31.75

Ø28.58

Ø25.40

Ø22.22

Ø19.05

Ø15.88

Ø12.70

Ø9.52

Ø6.35

5. CZ-P1350BH2.

Use: For indoor unit (Capacity after distribution joint is greater than 68.0 kW and no more than 135.0 kW.) LIQUID PIPE I H G

F E D C C A B B

55

F

F E D C C A B B

90

B

G F E

G G F E

E F G

G HI

I H

10 5

50

340

BA C C D E F 45

H G

130

SUCTION PIPE / DISCHARGE PIPE

112

Insulator

Insulator

Unit: mm

Dimensions for connections of each part Position

A

B

C

D

E

F

G

H

I

J

Dimension

Ø38.10

Ø31.75

Ø28.58

Ø25.40

Ø22.22

Ø19.05

Ø15.88

Ø12.70

Ø9.52

Ø6.35

39


Indoor Units

Wide choice of models depending on the indoor requirements

DUCTED UNITS Available in 3 models

F2 mid static – adjustable static pressure 10 -150pa M1 low static – 200mm high across all models E1 High static – up to 235pa for S-280 model

4 WAY CASSETTES Variable speed DC fan motors with settable output to suit different applications.

U1 – 950 X 950. Fresh air and branch duct options. Install height up to 5m. Y1 – 600 x 600 to fit standard ceiling grid, fresh air option

1WAY & 2 WAY CASSETTES D1 – 1 way cassette. Down blow and front blow installation possible L1 – 2 way cassette. High drain pump lift up to 810mm from ceiling

40


Indoor Unit

K2 WALL MOUNT Noise Reducing External valve Kit Compact design with flat surface enables seamless match with any type of room interior

To reduce noise level of external valve. (Optional accessory) CZ-P56SVK2 (for 22 - 56 type) CZ-P160SVK2 (for 73 - 106 type)

T1 UNDER CEILING • Low sound levels • Standardised height and depth for all models • Long and wide air distribution • Easy to install and maintain • Fresh air knockout

P1 & R1 FLOOR STAND P1 Exposed Floor Standing R1 Concealed Floor Standing

• Pipes can be connected to the unit either from the bottom or rear • Easy to install • Front panel opens fully for easy maintenance • Removable air discharge grille gives flexible air flow • Wired remote can be installed in the top of indoor unit

41


FSV Indoor Units Range Wide choice of models depending on the indoor requirements Class 22 Cooling/Heating Capacity

Type

kW 2.2/2.5 BTU/h 7,500/8,500

28

36

45

56

60

73

Cooling/Heating

Cooling/Heating

Cooling/Heating

Cooling/Heating

Cooling/Heating

Cooling/Heating

2.8/3.2 9,600/11,000

3.6/4.2 12,000/14,000

4.5/5.0 15,000/17,000

5.6/6.3 19,000/21,000

6.0/7.1 20,400/24,200

7.3/8.0 25,000/27,000

U1 type

4-Way Cassette

S-22MU1E51 Panel No. CZ-KPU2

S-28MU1E51 Panel No. CZ-KPU2

S-36MU1E51 Panel No. CZ-KPU2

S-45MU1E51 Panel No. CZ-KPU2

S-56MU1E51 Panel No. CZ-KPU2

S-60MU1E51 Panel No. CZ-KPU2

S-73MU1E51 Panel No. CZ-KPU2

S-22MY1E5 Panel No. CZ-KPY2

S-28MY1E5 Panel No. CZ-KPY2

S-36MY1E5 Panel No. CZ-KPY2

S-45MY1E5 Panel No. CZ-KPY2

S-56MY1E5 Panel No. CZ-KPY2

S-22ML1E5 Panel No. CZ-02KPL2

S-28ML1E5 Panel No. CZ-02KPL2

S-36ML1E5 Panel No. CZ-02KPL2

S-45ML1E5 Panel No. CZ-02KPL2

S-56ML1E5 Panel No. CZ-02KPL2

S-73ML1E5 Panel No. CZ-03KPL2

S-28MD1E5 Panel No. CZ-KPD2

S-36MD1E5 Panel No. CZ-KPD2

S-45MD1E5 Panel No. CZ-KPD2

S-56MD1E5 Panel No. CZ-KPD2

S-73MD1E5 Panel No. CZ-KPD2

S-22MF2E5

S-28MF2E5

S-36MF2E5

S-45MF2E5

S-56MF2E5

S-22MM1E5

S-28MM1E5

S-36MM1E5

S-45MM1E5

S-56MM1E5

Y1 type

4-Way Cassette 600x600

L1 type

2-Way Cassette

D1 type

1-Way Cassette

F2 type

Low Silhouette Ducted

S-60MF2E5

S-73MF2E5

M1 type

Slim Low Static Ducted

E1 type

High Static Pressure Ducted

S-73ME1E5

T1 type

Ceiling

S-36MT1E5

S-45MT1E5

S-56MT1E5

S-73MT1E5

K2 type

Wall Mounted

S-22MK2E5

S-28MK2E5

S-36MK2E5

S-45MK2E5

S-56MK2E5

S-73MK2E5

S-22MP1E5

S-28MP1E5

S-36MP1E5

S-45MP1E5

S-56MP1E5

S-71MP1E5

S-22MR1E5

S-28MR1E5

S-36MR1E5

S-45MR1E5

S-56MR1E5

S-71MR1E5

P1 type

Floor Standing

R1 type

Concealed Floor Standing

42


Indoor Unit

90

106

140

160

224

280

Cooling/Heating

Cooling/Heating

Cooling/Heating

Cooling/Heating

Cooling/Heating

Cooling/Heating

9.0/10.0 30,000/34,000

10.6/11.4 36,000/39,000

14.0/16.0 47,800/54,600

16.0/18.0 54,600/61,500

22.4/25.0 76,400/85,300

28.0/31.5 95,500/107,500

S-90MU1E51 Panel No. CZ-KPU2

S-106MU1E51 Panel No. CZ-KPU2

S-140MU1E51 Panel No. CZ-KPU2

Wireless remote control Type with built-in sensor part

S-160MU1E51 Panel No. CZ-KPU2

• • •

S-90MF2E5

S-106MF2E5

S-140MF2E5

Type with separately installed sensor part

Functions

• • • • •

S-160MF2E5

selfdiagnosing

Auto fan

Mild dry

Auto restart

Air swing

Drain pump

selfdiagnosing

Auto fan

Mild dry

Auto restart

Air swing

Drain pump

selfdiagnosing

Auto fan

Mild dry

Auto restart

Air swing

Drain pump

selfdiagnosing

Auto fan

Mild dry

Auto restart

Air swing

Drain pump

selfdiagnosing

Auto fan

Mild dry

Auto restart

selfdiagnosing

S-106ME1E5

S-106MT1E5

S-140ME1E5

S-224ME1E5

S-280ME1E5

S-106MK2E5

Auto flap

Auto flap

Auto fan

Mild dry

Drain pump

Auto fan

Mild dry

selfdiagnosing

Auto fan

Mild dry

Auto flap

Auto restart

Air swing

selfdiagnosing

Auto fan

Mild dry

Auto flap

Auto restart

Air swing

selfdiagnosing

Auto fan

Mild dry

Auto fan

Mild dry

Auto restart

S-140MT1E5

selfdiagnosing

Auto flap

Drain pump

Auto restart

Auto flap

• • •

Auto restart

selfdiagnosing

Auto restart

Self-diagnosing function

Automatic fan operation

Mild dry

Automatic restart function for power failure

Air swing

Built-in drain pump

Intelligent auto flap control

43


U1TYPE

4-WAY Cassette

Semi concealed cassette

Our best selling U1 Type cassettes are made smaller, slimmer, lighter and comes with a standard 950 x 950mm panel for the entire product range.

Selfdiagnosing Function

Automatic Fan Operation

Mild dry

Intelligent Auto Swing

Automatic Restart Function

Auto Swing (Auto Flap Control)

Built-in Drain Pump

Technical focus • Lightweight design • Fresh air knockout • Branch duct connection (plenum is field supply) • Optional air-intake plenum CZ-FDU2

• Compact design • Reduced sound levels (from previous models) • DC fan motor for increased efficiency • Powerful drain pump gives 850 mm lift

Lighter and Slimmer, Easier Installation

Low-Profile

A lightweight unit at 24 kg, the unit is also very slim with a height of only 256 mm, making installation possible even in narrow ceilings. * For 22 - 73 type

33.5 mm Panel Only

256 mm

Drain pump of about 850 mm from the ceiling surface

Up to

The drain height can be increased by approximately 350 mm over the conventional value by using a high-lift drain pump, and long horizontal piping is possible.

Easy fine adjustment of the body suspension height!

Up to

300 mm

850 mm

Even after installation, fine adjustment of the suspension height is possible easily by removing the corner pockets.

The four corners of the ceiling panel have adopted removable corner pockets.

Wireless signal receiver

Easy to clean suction grill & flap A suction grill enables to make 90-degree turns.

It is easy to remove a washable flap by hand.

Air flow directed to avoid ceiling marking The dew condensation and dirt appearing near the discharge ports of the conventional ceiling cassettes have been reduced. 44

Conventional

The discharged air hits the ceiling and causes dirt.

U1 type cassette Upward air flow is suppressed.


Indoor Unit / U1 Type

AIR INTAKE CHAMBER

PANEL

Air intake plenum CZ-FDU2 Air intake box CZ-ATU2 Both Air intake plenum and Air intake box are necessary

CZ-KPU2

Individual flap control Flexible Air flow direction control by individual flap control is possible. 4 Flaps can be controlled individually by setting on wired timer remote controller. It can make more flexible Air-flow control to be matched to several demands in a room.

Temperature distribution by thermograph (cooling operation) 360° Wide

* It needs pre-setting for this function at system test-run procedure.

1m

Simulation conditions: 140M 4-way ceiling-mounted cassette type in cooling mode / Floor area of 225 m2 / Ceiling height of 3 m

Example case for Cooling

High-Ceiling Installation (Up to 5 m for 106M and higher models) The units can be installed in rooms with high ceilings, where they provide ample floor-level heating in the winter. (See ceiling height guidelines below.)

High Ceiling

(Factory settings)

22M-56M

Capacity

3.6m

3.0m

2.7m

New model

60M-90M

106M-160M

Industry’s top-class

4.7m

4.5m

106M160M

4-way discharge

Capacity

high ceiling settings2

3-way discharge with the optional airblocking materials

Ceiling height guidelines *1 settings 4-way discharge

3-way discharge

2-way discharge

Indoor unit

Factory settings 1

High ceiling setting 1

High ceiling setting 2

High ceiling (optional air-blocking materials) setting 2

(optional air-blocking materials) *2

22M-56M

2.7

3.2

3.5

4.2

3.8

4.2

60M-90M

3.0

3.3

3.6

4.2

3.8

4.2

106M-160M

3.6

3.9

4.5

5.0

4.7

5.0

5m

2-way discharge with the optional airblocking materials

*1 When using the unit in a configuration other than the factory settings, it is necessary to make settings on site to increase airflow. *2 Use air-blocking materials (CZ-CFU2) to completely block two discharge outlets for 2-way airflow.

45


U1TYPE

4-WAY Cassette

Model Name

S-22MU1E51

S-28MU1E51

S-36MU1E51

S-45MU1E51

Power source kW

2.2

2.8

3.6

4.5

5.6

BTU/h

7,500

9,600

12,000

15,000

19,000

kW

2.5

3.2

4.2

5.0

6.3

BTU/h

8,500

11,000

14,000

17,000

21,000

Cooling

kW

0.019/0.019/0.018

0.019/0.019/0.018

0.019/0.019/0.018

0.019/0.019/0.019

0.022/0.022/0.021

Heating

kW

0.017/0.017/0.016

0.017/0.017/0.016

0.017/0.017/0.016

0.019/0.019/0.019

0.022/0.022/0.021

Cooling

A

0.020/0.020/0.020

0.020/0.020/0.020

0.020/0.020/0.020

0.020/0.020/0.020

0.025/0.025/0.025

Heating

A

0.18/0.18/0.17

0.18/0.18/0.17

0.18/0.18/0.17

0.21/0.21/0.21

0.28/0.28/0.27

Turbo fan

Turbo fan

Turbo fan

Turbo fan

Turbo fan

Cooling capacity

Heating capacity

Power input Running current

Type Fan

Air flow rate

L/s

233

233

233

250

250

Motor output

kW

0.05

0.05

0.05

0.05

0.05

Sound power level (L/M/H)

dB

47/46/45

47/46/45

47/46/45

48/46/45

50/47/45

Sound pressure level (L/M/H)

dB(A)

30/29/28

30/29/28

30/29/28

31/29/28

3/30/28

Dimensions

HxWxD

mm

Liquid

inches (mm)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

Gas

inches (mm)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

VP-25

VP-25

VP-25

VP-25

VP-25

23 (+4)

23 (+4)

23 (+4)

23 (+4)

23 (+4)

Pipe connections

256+(33.5) x 840 (950) x 840 (950)

Drain piping Net weight (Panel)

GLOBAL REMARKS

kg

Rated conditions:

Cooling

Heating

Indoor air temperature

27˚C DB / 19˚C WB

20˚C DB

Outdoor air temperature

35˚C DB / 24˚C WB

7˚C DB / 6˚C WB

Specifications subject to change without notice.

46

S-56MU1E51

220/230/240 V, 1 phase - 50Hz

1/4 (Ø6.35)


Indoor Unit / U1 Type

S-60MU1E51

S-73MU1E51

S-90MU1E51

S-106MU1E51

S-140MU1E51

S-160MU1E51

220/230/240 V, 1 phase - 50Hz 6.0

7.3

9.0

10.6

14

16

20,400

24,900

30,700

36,000

47,800

54,600

7.10

8.0

10.00

11.4

16.0

18.0

24,200

27,300

34,100

39,000

54,600

61,400

0.032/0.031/0.030

0.036/0.033/0.032

0.039/0.036/0.035

0.073/0.071/0.071

0.077/0.076/0.073

0.090/0.089/0.087

0.030/0.030/0.029

0.035/0.032/0.031

0.037/0.034/0.033

0.066/0.065/0.064

0.075/0.073/0.073

0.083/0.080/0.079

0.035/0.035/0.035

0.040/0.040/0.040

0.040/0.040/0.040

0.095/0.095/0.095

0.100/0.100/0.100

0.115/0.115/0.115

0.30/0.30/0.29

0.35/0.32/0.31

0.37/0.34/0.33

0.85/0.85/0.85

0.86/0.83/0.83

0.105/0.105/0.105

Turbo fan

Turbo fan

Turbo fan

Turbo fan

Turbo fan

Turbo fan

350

367

384

550

583

600

0.06

0.06

0.06

0.09

0.09

0.09

53/49/46

54/49/46

55/52/49

61/55/51

62/55/51

63/56/53

36/32/29

37/32/29

38/35/32

44/38/34

45/39/35

46/40/38

319+(33.5) x 840 (950) x 840 (950) 3/8 (Ø9.52)

3/8 (Ø9.52)

3/8 (Ø9.52)

3/8 (Ø9.52)

3/8 (Ø9.52)

3/8 (Ø9.52)

5/8 (Ø15.88)

5/8 (Ø15.88)

5/8 (Ø15.88)

5/8 (Ø15.88)

5/8 (Ø15.88)

5/8 (Ø15.88)

VP-25

VP-25

VP-25

VP-25

VP-25

VP-25

24 (+4)

24 (+4)

24 (+4)

27 (+4)

27 (+4)

27 (+4)

U1 TYPE 4-WAY CASSETTE Dimensions

421

345

5

3

50

6

42 121 33.5

95

167 130 95 160

160

160 80

Air intake duct connection hole (ø100)

82

9

7

2

18

118

2

950

515

30

2

1

80

le 4 -ø3 Burring ho 13 ø1

X view

A

271

950 514 Less than 670

115

Air discharge duct connection hole (ø150)

7

Less than 300

Less than 850

-ø3 hole 4 Burring 115

62 ø1

480

7

4

50

145

180 B

2

Less than 35 7

106~160 type 319 187

840

167 Less than 35

22~90 type 256 124

B

(411)

8

745 (Suspension bolt pitch) 860~910 (Ceiling opening dimension)

786 (Suspension bolt pitch)

*1: Air inlet kit is necessary. Filter size: 520 x 520 x 16

840 480

A B

130

X 860~910 (Ceiling opening dimension)

1 Air intake grill 2 Air discharge outlet 3 Refrigerant piping (liquid pipes) 22-56 type: ø6.35(flared), 60-160 type: ø9.52(flared) 4 Refrigerant piping (gas pipes) 22-56 type: ø12.7(flared), 60-160 type: ø15.88(flared) 5 Drain outlet VP25(outer ø32) 6 Power supply port 7 Discharge duct (ø150) 8 Suspension bolt hole (4-12x30 slot) 9 Fresh air intake duct connection port (ø100)*1

Drain up 2

Dimensions: mm

* Adjust the suspension bolt length so that the gap from the lower ceiling surface becomes 30 mm or more (18 mm or more from the lower surface of the body) as shown in the figure. When the suspension bolt length is long, it hits the ceiling panel and installation is not possible.

47


4-WAY Cassette 60X60 mini semi concealed cassette Y1 TYPE

Designed to fit exactly into a 600 x 600 mm ceiling grid without the need to alter the bar configuration, the Y1 is ideal for small commercial and retrofit applications. In addition, the improvements to efficiency make this one of the most advanced units in the industry.

Selfdiagnosing Function

Automatic Fan Operation

Mild dry

Intelligent Auto Swing

Automatic Restart Function

Auto Swing (Auto Flap Control)

Built-in Drain Pump

Technical focus • Mini cassette fits into a 600x600 mm ceiling grid • Fresh air knock out • Multidirectional air flow • Anti-mould and anti-bacteria washable filters • Powerful drain pump gives 850 mm lift • Turbo fans and heat exchanger fins with improved design

• DC fan motors with variable speed, new heat exchangers, etc. ensure an efficient power consumption • Optional air-intake plenum CZ-ATU2

Special designed flap The flap can be removed easily for washing with water.

Lighter and slimmer, easier installation A lightweight unit at 19 kg, the unit is also very slim with a height of only 283 mm, making installation possible even in narrow ceilings.

A drain height of approx. 850 mm from the ceiling surface The drain height can be increased by approximately 350 mm over the conventional value by using a high-lift drain pump, and long horizontal piping is possible.

48

Up to 283 mm

Drain Pump of about 850 mm from the ceiling surface

Up to 300 mm

Up to 850 mm


Indoor Unit / Y1 Type

PANEL

CZ-KPY2

Model Name

S-22MY1E5

S-28MY1E5

S-36MY1E5

Power source Cooling capacity Heating capacity Power input Running amperes

S-56MY1E5

kW

2,2

2,8

3,6

4,7

BTU/h

7.500

9.600

12.000

15.000

19.000

kW

2,5

3,2

4,2

5,0

6,3

5,6

11.000

14.000

17.000

21.000

BTU/h

8.500

Cooling

kW

0.016/0.016/0.015

0.016/0.016/0.015

0.018/0.018/0.017

0.021/0.021/0.020

0.029/0.029/0.028

Heating

kW

0.013/0.013/0.012

0.013/0.013/0.012

0.015/0.015/0.014

0.018/0.018/0.017

0.026/0.026/0.025

Cooling

A

0.024/0.025/0.025

0.024/0.025/0.025

0.026/0.027/0.027

0.030/0.031/0.031

0.037/0.038/0.038

Heating

A

0.014/0.015/0.015

0.014/0.015/0.015

0.017/0.017/0.018

0.020/0.021/0.021

Type Fan motor

S-45MY1E5

220/230/240 V, 1 phase - 50, 60 Hz

0.029/0.029/0.029

Centrifugal fan

Centrifugal fan

Centrifugal fan

Centrifugal fan

Centrifugal fan 208

Airflow rate (H)

L/s

133

133

150

177

Output

kW

0,030

0,030

0,030

0,030

0,030

dB(A)

41/38/36

41/38/36

43/40/37

47/43/39

52/48/44

Power sound level (H/M/L) Sound pressure sound (H/M/L)

dB(A)

30/27/25

30/27/25

32/29/26

36/32/28

41/37/33

Dimensions

HxWxD

mm

283 x 575 (625) x 575 (625)

283 x 575 (625) x 575 (625)

283 x 575 (625) x 575 (625)

283 x 575 (625) x 575 (625)

283 x 575 (625) x 575 (625)

Liquid

(mm)

.13/.13/.12

.13/.13/.12

.15/.15/.14

.18/.18/.17

.26/.26/.25

Gas 410 A

(mm)

24/25/25

24/25/25

26/27/27

30/31/31

37/38/38

114/15/15

14/15/15

17/17/18

20/21/21

29/29/29

19 + (2,7)

19 + (2,7)

19 + (2,7)

19 + (2,7)

19 + (2,7)

Net weight

kg

GLOBAL REMARKS

Rated conditions:

Cooling

Heating

Indoor air temperature

27˚C DB / 19˚C WB

20˚C DB

Outdoor air temperature

35˚C DB / 24˚C WB

7˚C DB / 6˚C WB

Y1 TYPE 4-WAY CASSETTE 60X60 Dimensions

(ceiling opening dimension) (suspension bolt pitch)

1 Air intake 2 Discharge outlet 3 Refrigerant piping (liquid pipes) Size 22 to 56: Ø6.35 (flared) 4 Refrigerant piping (gas pipes) Size 22 to 56: Ø12.7 (flared) 5 Drain tube connection port VP20 (outer Ø26) 6 Power supply port 7 Suspension bolt hole (4-12 x 30 hole) 8 Fresh air intake duct connection port (Ø100)

Less than 25

The values in ( ) for external dimensions and Net weight are the values for the optional ceiling panel. Specifications subject to change without notice.

Panel center

(suspension bolt pitch)

Drain piping

(ceiling opening dimension)

Pipe connections

A view

Less than 25

The length of the suspension bolts should be selected so that there is a gap of 30 mm or the ceiling (17 mm or more below the lower surface of the main unit), as shown in the figure at right. If the suspension bolts is too long, it will contact the ceiling panel and the unit cannot be installed. Dimensions: mm

49


L1 TYPE

2-WAY Cassette

Realisation of thin, compact and light units Remarkable size and weight reductions have been achieved by improvement of the design around the fan.

Selfdiagnosing Function

Automatic Fan Operation

Mild dry

Intelligent Auto Swing

Automatic Restart Function

Auto Swing (Auto Flap Control)

Built-in Drain Pump

Technical focus • Airflow and distribution is automatically altered depending on the operational mode of the unit • Drain up is possible up to 500 mm from the drain port • Simple maintenance

auto flap section

20¡ 2.7 m

Airflow and distribution is automatically altered depending on the operational mode of the unit.

40¡

Cooling/(Fan)

Heating/(Hi,M)

Drain up is possible up to 500 mm from the drain port. Maintenance of the drain pump is possible from two sides, from the left side (piping side) and from the inside of the unit.

Simple maintenance The drain pan is equipped with site wiring and can be removed. The fan case has a split construction, and the fan motor can be removed easily when the lower case is removed.

50


Indoor Unit / L1 Type

PANEL

CZ-02KPL2 Big size panel (for S-73ML1E5) CZ-03KPL2

Model Name

S-22ML1E5

S-28ML1E5

S-36ML1E5

Power source Cooling capacity Heating capacity Power input Running current

S-45ML1E5

S-56ML1E5

S-73ML1E5

220/230/240V, 1 phase - 50 / 60Hz kW

2.2

2.8

3.6

4.5

5.6

7.3

BTU/h

7,500

9,600

12,000

15,000

19,000

25,000

kW

2.5

3.2

4.2

5.0

6.3

8.0

BTU/h

8,500

11,000

14,000

17,000

21,000

27,000

Cooling

kW

0.086/0.090/0.095

0.086/0.092/0.097

0.088/0.093/0.099

0.091/0.097/0.103

0.091/0.097/0.103

0.135/0.145/0.154

Heating

kW

0.055/0.058/0.062

0.055/0.060/0.064

0.057/0.061/0.066

0.060/0.065/0.070

0.060/0.065/0.070

0.100/0.109/0.117

Cooling

A

0.45/0.45/0.45

0.44/0.45/0.45

0.44/0.45/0.45

0.45/0.45/0.45

0.45/0.45/0.45

0.64/0.65/0.66

Heating

A

0.29/0.29/0.30

0.28/0.29/0.30

0.28/0.29/0.30

0.29/0.29/0.30

0.29/0.29/0.30

0.46/0.48/0.49

Type

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Air flow rate (H)

L/s

133

150

161

184

184

317

Motor output

kW

0.03

0.03

0.03

0.03

0.03

0.05

Sound power level (L/M/H)

dB

35/38/40

37/40/44

39/42/45

40/44/46

40/44/46

44/46/49

Sound pressure level (L/M/H)

dB(A)

24/27/30

26/29/33

28/31/34

29/33/35

29/33/35

33/35/38

Dimensions

HxWxD

mm

350+(8)x840 (1,060) x600 (680)

350+(8)x840 (1,060) x600 (680)

350+(8)x840 (1,060) x600 (680)

350+(8)x840 (1,060) x600 (680)

350+(8)x840 (1,060) x600 (680)

350+(8)x 1,140 (1,360) x600 (680)

Liquid

inches (mm)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

3/8 (Ø9.52)

Gas

inches (mm)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

5/8 (Ø15.88)

VP-25

VP-25

VP-25

VP-25

VP-25

VP-25

30

30

30

30

30

30

Fan

Pipe connections

Drain piping

Net weight

kg

GLOBAL REMARKS

Rated conditions:

Cooling

Heating

Indoor air temperature

27˚C DB / 19˚C WB

20˚C DB

Outdoor air temperature

35˚C DB / 24˚C WB

7˚C DB / 6˚C WB

The values in ( ) for external dimensions and Net weight are the values for the optional ceiling panel. Specifications subject to change without notice.

L1 TYPE 2-WAY CASSETTE Dimensions 1 Air intake 2 Air outlet 3 Ceiling opening dimensions 4 Suspension fitting (notch: 12 mm) 5 Refrigerant piping (liquid pipes) 6 Refrigerant piping (gas pipes) 7 Drain connection VP25 (outer diameter ø 32) 8 Inlet for option cord between power supply and unit 9 Drain pan, drain pump inspection lid 10 Drain pump inspection lid 11 Round flange (field supply) mounting part (fresh air inlet ø 125) 12 Discharge duct (field supply) mounting part (installation possible only on the right side) 13 Wireless remote controller (option) signal receiver installation part

Inspection lid

300

20

450

40 70 20

(230) 110 30

C

B D E

73 type 1,140 590 630 1,320 1,360

Ceiling opening dimensions

1,020x640

1,320x640

Refrigerant piping (liquid pipes)

ø6.35

ø9.52

Refrigerant piping (gas pipes)

ø12.7

ø15.88

Duct connection port (only on the right side)

x 1 pc.

x 2 pc.

165

290 60

8

195 220 310 350 75 (105)

102

A

22 56 type 840 440 480 1,020 1,060

80 70

70

680

530 600 640 680

Ceiling panel and ceiling opening center

A B C D E

(55)

23

Dimensions: mm

51


D1TYPE

1-WAY Cassette

Semi concealed slim cassette

Designed for installation within the ceiling void, the D1 range of slimline 1 way blow cassettes feature quiet yet powerful fan that can reach the floor up 4.2 m from ceiling height.

Selfdiagnosing Function

Automatic Fan Operation

Mild dry

Intelligent Auto Swing

Automatic Restart Function

Auto Swing (Auto Flap Control)

Built-in Drain Pump

Technical focus • Ultra-Slim • Suitable for standard and high ceilings • Built-in drain pump provides 696 mm lift • Easy to install and maintain • Hanging height can be easily adjusted • Uses a DC fan motor to improve energy-efficiency

Drain height

300 mm or less

696 mm or less

With 3 types of air-blow systems, the units can be used in various ways. (1) One-direction down-blow system Powerful one-direction “downblow” system reaches the floor even from high ceilings (up to 4.2 m).

(2) Two-direction ceiling-mounted system “Down-blow” and “front-blow” systems are combined in a ceilingmounted unit to blow air over a wide area.

(3) One-direction ceiling-mounted system This powerful ceiling-mounted “front-blow” system efficiently airconditions the space in front of the unit. (Additional accessories required) 52


Indoor Unit / D1 Type

PANEL

CZ-KPD2

Model Name

S-28MD1E5

S-36MD1E5

S-45MD1E5

Power source 2.8

3.6

4.5

5.6

7.3

BTU/h

9,600

12,000

15,000

19,000

25,000

kW

3.2

4.2

5.0

6.3

8.0

BTU/h

11,000

14,000

17,000

21,000

27,000

Cooling

kW

0.050/0.051/0.052

0.050/0.051/0.052

0.050/0.051/0.052

0.058/0.060/0.061

0.086/0.087/0.089

Heating

kW

0.039/0.040/0.042

0.039/0.040/0.042

0.039/0.040/0.042

0.046/0.048/0.049

0.075/0.076/0.077

Cooling

A

0.40/0.39/0.39

0.40/0.39/0.39

0.40/0.39/0.39

0.46/0.46/0.46

0.71/0.70/0.69

Heating

A

0.36/0.35/0.35

0.36/0.35/0.35

0.36/0.35/0.35

0.42/0.41/0.41

0.66/0.65/0.63

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Heating capacity

Running current

Type Fan

S-73MD1E5

kW

Cooling capacity

Power input

S-56MD1E5

220/230/240 V, 1 phase - 50 / 60 Hz

Air flow rate (H/M/L)

L/s

200/167/150

200/167/150

200/183/167

210/191/167

300/200/216

Motor output

kW

0.05

0.05

0.05

0.05

0.05

Sound power level (L/M/H)

dB

44/45/47

44/45/47

45/46/47

45/47/49

47/51/56

Sound pressure level (L/M/H)

dB(A)

33/34/36

33/34/36

34/35/36

34/36/38

36/40/45

Dimensions

HxWxD

mm

200+(20) x 1,000 (1,230) x 710 (800)

200+(20) x 1,000 (1,230) x 710 (800)

200+(20) x 1,000 (1,230) x 710 (800)

200+(20) x 1,000 (1,230) x 710 (800)

200+(20) x 1,000 (1,230) x 710 (800)

Liquid

inches (mm)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

3/8 (Ø9.52)

Gas

inches (mm)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

5/8 (Ø15.88)

VP-25

VP-25

VP-25

VP-25

VP-25

26.5

26.5

26.5

26.5

27.5

Pipe connections

Drain piping

Net weight

kg

GLOBAL REMARKS

Rated conditions:

Cooling

Heating

Indoor air temperature

27˚C DB / 19˚C WB

20˚C DB

Outdoor air temperature

35˚C DB / 24˚C WB

7˚C DB / 6˚C WB

The values in ( ) for external dimensions and Net weight are the values for the optional ceiling panel. Specifications subject to change without notice.

D1 TYPE 1-WAY CASSETTE Dimensions

(suspension bolt pitch)

(suspension bolt pitch) (ceiling opening dimension)

1 Air intake grille 2 Air outlet 3 Refrigerant piping (liquid pipes) Size 28 to 56: Ø6.35 (flared) Size 73: Ø9.52 (flared) 4 Refrigerant piping (gas pipes) Size 28 to 56: Ø12.7 (flared) Size 73: Ø15.88 (flared) 5 Drain connection VP25 (outer Ø32) 6 Power supply entry 7 Discharge duct connection port (for descending ceiling) 8 Wireless remote control receiver (option) 9 Suspension mounting (4-12 x 30 slot) 10 Fresh air intake (Ø100)

(ceiling opening dimension)

Dimensions: mm

53


F2 TYPE

Low Silhouette Ducted

The new F2 type is designed specifically for applications requiring fixed square ducting. The internal filter is equipped as standard.

Selfdiagnosing Function

Automatic Fan Operation

Mild dry

Automatic Restart Function

Built-in Drain Pump

Technical focus • Variable external static pressure control • Industry-leading low sound levels from 25 dB(A) • Built-in drain pump provides 702 mm lift • Easy to install and maintain

• Air off sensor avoids cold air dumping • Configurable air temperature control • Anti-mould washable filters included

Variable external static pressure control

Optimal airflow set-up is possible depend on ducting design condition. Optimal Control by DC Motor For short ducting such as hotels

10Pa

150Pa

For long ducting or for usage with high efficient filter

* Please refer technical databook for detail.

System example An inspection port (450 mm x 450 mm or more) is required at the lower side of the indoor unit body.

Canvas duct

Rectangle duct

Intake grille

Inspection port (450 x 450 mm or more)

More powerful drain pump Using a high-lift drain pump, drain piping can be elevated up to 702 mm from the base of the unit.

Up to 300 mm Up to 500 mm 202 mm

54


Indoor Unit / F2 Type

S-60MF2E5 / S-73MF2E5 / S-90MF2E5

S-106MF2E5 / S-140MF2E5 / S-160MF2E5

S-22MF2E5 / S-28MF2E5 / S-36MF2E5 / S-45MF2E5 / S-56MF2E5

External electrical equipment box makes maintenance easy

Built-in Drain pump (DC motor pump)

Standardized height of 290 mm for all models Height standardization enables easy and uniform installation for models with different capacities.

• Built-in filter • Side and bottom access filter Bottom suction possible

Discharge air temperature control • Able to control discharge air temperature for accurate room temperature control. • Possible to reduce cold drafts at heating operation.

Before spec-in, please consult with an authorized Panasonic dealer.

Air intake sensor E3 sensor E1 sensor Air discharge sensor

Circle duct flange (option)* CZ-160DAF2 (4 SA outlet) CZ-90DAF2 (3 SA outlet) CZ-56DAF2 (2 SA outlet) *Duct flange not held locally

55


F2 TYPE

Low Silhouette Ducted

Model Name

S-22MF2E5

S-28MF2E5

S-36MF2E5

Power source 2.2

2.8

3.6

4.5

5.6

BTU/h

7,500

9,600

12,300

15,400

19,100

kW

2.5

3.2

4.2

5.0

6.3

BTU/h

8,500

10,900

14,300

17,100

21,500

Cooling

kW

0.070/0.070/0.070

0.070/0.070/0.070

0.070/0.070/0.070

0.100/0.100/0.100

0.100/0.100/0.100

Heating

kW

0.070/0.070/0.070

0.070/0.070/0.070

0.070/0.070/0.070

0.100/0.100/0.100

0.100/0.100/0.100

Cooling

A

0.60/0.57/0.56

0.60/0.57/0.56

0.60/0.57/0.56

0.77/0.74/0.71

0.070/0.070/0.070

Heating

A

0.60/0.57/0.56

0.60/0.57/0.56

0.60/0.57/0.56

0.77/0.74/0.71

0.070/0.070/0.070

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan 267

Heating capacity

Running amperes

S-56MF2E5

kW

Cooling capacity

Power input

S-45MF2E5

220/230/240V, 1 phase - 50/60Hz

Type Airflow rate (H)

L/s

233

233

233

233

Output

kW

0.119

0.119

0.119

0.119

0.119

External static pressure

Pa

70(10-150)

70(10-150)

70(10-150)

70(10-150)

70(10-150)

Power sound level (H/M/L)

dB(A)

55/51/47

55/51/47

55/51/47

56/54/50

56/54/50

Sound pressure sound (H/M/L)

dB(A)

33/29/25

33/29/25

33/29/25

34/32/28

34/32/28

Dimensions

HxWxD

mm

290x800x700

290x800x700

290x800x700

290x800x700

290x800x700

Liquid

inches (mm)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

Gas 410 A

inches (mm)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

VP-25

VP-25

VP-25

VP-25

VP-25

29

29

29

29

29

Fan motor

Pipe connections

Drain piping

Net weight

GLOBAL REMARKS

kg

Specifications subject to change without notice.

Rated conditions:

Cooling

Heating

Indoor air temperature

27˚C DB / 19˚C WB

20˚C DB

Outdoor air temperature

35˚C DB / 24˚C WB

7˚C DB / 6˚C WB

F2 TYPE LOW SILHOUETTE DUCTED Dimensions Filter

SIZE 22-56 MF2E5

6

35

32

28

172

9

758

3

26 4

700

Inspection access 450 x 450 (Field supply)

636

700

280

1 Refrigerant tubing joint (liquid tube) Ø6.35 Flare 2 Refrigerant tubing joint (gas tube) Ø12.7 Flare 3 Upper drain port VP25 (O.D. Ø32 mm) 200 flexible hose supplied 4 Bottom drain port VP25 (O.D. Ø32 mm) 5 Suspension lug (4-12 × 30 mm) 6 Power supply outlet 7 Fresh air intake port (Ø150 mm) 8 Flange for flexible air outlet duct 9 Electrical component box

7

5

8

71

33

(150)

867(Suspension bolt pitch) 592(Flange O.D.)

154

65

300

113 70

23

140

27

186

23

2

290

(75)

77

186

54

130

32

12-ø3holes 150 x 3 = 450 800

30 20

71

1

23

30

256

89

Dimensions: mm

56


Indoor Unit / F2 Type

S-60MF2E5

S-73MF2E5

S-90MF2E5

S-106MF2E5

S-140MF2E5

S-160MF2E5

220/230/240V, 1 phase - 50/60Hz 6.0

7.3

9.0

10.6

14.0

16.0

20,500

24,900

30,700

36,200

47,800

54,600

7.1

8.0

10.0

11.4

16.0

18.0

24,200

27,300

34,100

38,900

54,600

61,500

0.120/0.120/0.120

0.120/0.120/0.120

0.135/0.135/0.135

0.195/0.195/0.195

0.215/0.215/0.215

0.225/0.225/0.225

0.120/0.120/0.120

0.120/0.120/0.120

0.135/0.135/0.135

0.200/0.200/0.200

0.210/0.210/0.210

0.225/0.225/0.225

0.91/0.89/0.87

0.91/0.89/0.87

0.99/0.97/0.95

1.35/1.30/1.27

1.48/1.44/1.39

1.55/1.50/1.47

0.91/0.89/0.87

0.91/0.89/0.87

0.99/0.97/0.95

1.37/1.34/1.29

1.46/1.42/1.38

1.55/1.50/1.46

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

350

350

417

534

567

600

0.124

0.124

0.124

0.235

0.235

0.235

70(10-150)

70(10-150)

70(10-150)

100(10-150)

100(10-150)

100(10-150)

57/54/48

57/54/48

59/56/50

60/56/53

61/57/54

62/58/55

35/32/26

35/32/26

37/34/28

38/34/31

39/35/32

40/36/33

290x1,000x700

290x1,000x700

290x1,000x700

290x1,400x700

290x1,400x700

290x1,400x700

3/8 (Ø9.52)

3/8 (Ø9.52)

3/8 (Ø9.52)

3/8 (Ø9.52)

3/8 (Ø9.52)

3/8 (Ø9.52)

5/8 (Ø15.88)

5/8 (Ø15.88)

5/8 (Ø15.88)

5/8 (Ø15.88)

5/8 (Ø15.88)

5/8 (Ø15.88)

VP-25

VP-25

VP-25

VP-25

VP-25

VP-25

34

34

34

46

46

46

SIZE 60-90 MF2E5

Filter

9 3

26 4

700

Inspection access 450 x 450 (Field supply)

636

700

758

280 7

6

35

28

172

32

1 Refrigerant tubing joint (liquid tube) Ø9.52 Flare 2 Refrigerant tubing joint (gas tube) Ø15.88 Flare 3 Upper drain port VP25 (O.D. Ø32 mm) 200 flexible hose supplied 4 Bottom drain port VP25 (O.D. Ø32 mm) 5 Suspension lug (4-12 × 30 mm) 6 Power supply outlet 7 Fresh air intake port (Ø150 mm) 8 Flange for flexible air outlet duct 9 Electrical component box

150

1000 1067(Suspension bolt pitch)

5

792(Flange O.D.)

21

33 (150)

300

113 65 70

23

140

27

186

23

2

290

(75)

154

186

54

130 30 20

150 x 5 = 750

32

16-ø3holes

8

21

1

27

30

256

89

77

Dimensions: mm

SIZE 106-160 MF2E5

9 3

26

30 20

32

130 70 23 27

33 (150)

154

113 65

256 1192(Flange O.D.)

71

140 186 290

23

2

(75) 27

54

1400 1467(Suspension bolt pitch)

1

186

5

8

150

77

71

20-ø3holes 150 x 7 = 1050

300

4

700

636

700

758

Inspection access 450 x 450 (Field supply)

89

30

7

6

35

32

28

172

280

1 Refrigerant tubing joint (liquid tube) Ø9.52 Flare 2 Refrigerant tubing joint (gas tube) Ø15.88 Flare 3 Upper drain port VP25 (O.D. Ø32 mm) 200 flexible hose supplied 4 Bottom drain port VP25 (O.D. Ø32 mm) 5 Suspension lug (4-12 × 30 mm) 6 Power supply outlet 7 Fresh air intake port (Ø150 mm) 8 Flange for flexible air outlet duct 9 Electrical component box

Filter

Dimensions: mm

57


M1TYPE Slim

concealed duct

Low Static Ducted

The ultra slim M1 type is one of the leading products of its type in the industry. With a height of only 200 mm, it provides greater flexibility and adaptability for various applications. In addition, high efficiency and extreme low noise level make it highly recommended for hotels and small offices.

Selfdiagnosing Function

Automatic Fan Operation

Mild dry

Automatic Restart Function

Built-in Drain Pump

Technical focus • Ultra-slim profile: 200 mm for all models • DC fan motor greatly reduces power consumption • Ideal for hotel application with very narrow false ceilings • Anti-mould washable filters included • Easy maintenance and service by external electrical box • 40 Pa static pressure enables ductwork to be fitted. • Includes drain pump

Ultra-slim profile for all models 200 mm

Drain pump with increased power! By adoption of a high-lift drain pump, the drain piping rise height can be increased to 653 mm from the lower surface of the body.

Up to 300 mm

Up to 500 mm

153 mm

58


Indoor Unit / M1 Type

Model Name

S-22MM1E5

S-28MM1E5

Power source Cooling capacity

Heating capacity

Power input Running current

S-36MM1E5

S-45MM1E5

S-56MM1E5

220/230/240 V, 1 phase - 50 / 60 Hz kW

2.2

2.8

3.6

4.5

BTU/h

7,500

9,600

12,000

15,000

5.6 19,000

kW

2.5

3.2

4.2

5.0

6.3

BTU/h

8,500

11,000

14,000

17,000

21,000

Cooling

kW

0.036/0.036/0.036

0.040/0.040/0.040

0.042/0.042/0.042

0.049/0.049/0.049

0.064/0.064/0.064

Heating

kW

0.026/0.026/0.026

0.030/0.030/0.030

0.032/0.032/0.032

0.039/0.039/0.039

0.054/0.054/0.054

Cooling

A

0.26/0.26/0.26

0.30/0.30/0.30

0.31/0.31/0.31

0.37/0.37/0.37

0.48/0.48/0.48

Heating

A

0.23/0.23/0.23

0.27/0.27/0.27

0.28/0.28/0.28

0.34/0.34/0.34

0.45/0.45/0.45

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan 208/192/167

Type Air flow rate (H/M/L)

L/s

133/116/100

142/133/108

150/133/116

175/158/133

External static pressure

Pa

10 (30)

15 (30)

15 (40)

15 (40)

15 (40)

Sound pressure level (L/M/H)

dB(A)

25/27/28 (27/29/30)*

27/29/30 (29/31/32)*

28/30/32 (30/32/34)*

30/32/34 (32/34/36)*

31/33/35 (32/35/37)*

Dimensions

Fan

Pipe connections

HxWxD

mm

200 x 750 x 640

200 x 750 x 640

200 x 750 x 640

200 x 750 x 640

200 x 750 x 640

Liquid

inches (mm)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

Gas

inches (mm)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

VP-20

VP-20

VP-20

VP-20

VP-20

19

19

19

19

19

Drain piping Net weight

GLOBAL REMARKS

kg

Specifications subject to change without notice.

Rated conditions:

Cooling

Heating

Indoor air temperature

27˚C DB / 19˚C WB

20˚C DB

Outdoor air temperature

35˚C DB / 24˚C WB

7˚C DB / 6˚C WB

* With booster cable.

M1 TYPE SLIM LOW STATIC DUCTED Dimensions

(suspension bolt pitch)

Inspection access

Inspection access (450 x 450) Field supply Hole

Hole

1 Refrigerant tubing joint (narrow tube) 2 Refrigerant tubing joint (wide tube) 3 Upper and bottom drain port (O.D. 26 mm) 4 Suspension lug 5 Power supply outlet (2- Ø30) 6 Flange for air intake duct 7 Pl cover 8 Electrical component box 9 Frame filter 10 Signal output board (ACC-SG-AGB: optional)

(air discharge space)

(suspension bolt pitch)

(air discharge space)

Inspection access panel Ceiling Hole

View A. Frame Filter Uninstalled Dimensions: mm

59


E1 TYPE

High Static Pressure Ducted

Concealed duct high-static pressure

The E1 range of ducted units offers improved design flexibility for extended duct layouts as a result of their increased external static pressures.

Selfdiagnosing Function

Automatic Fan Operation

Mild dry

Automatic Restart Function

Technical focus • Complete flexibility for ductwork design • Can be located into a weatherproof housing for external installation

• Discharge air temperature control • Configurable air temperature control

System example An inspection port (450 x 450 mm or more) is required at the lower side of the indoor unit body (field supply).

Inspection port (450 x 450 mm or more)

Rap valve kit CZ-P160RVK2 (For heating operation only) The types 224 and 280 require two rap valve kits for each unit for heating operation. (not required for cooling only design project) (not required on a 1:1 installation)

Discharge air temperature control • Able to control discharge air temperature for accurate room temperature control. • Possible to reduce cold drafts at heating operation.

E3 sensor

Air intake sensor

E1 sensor

Air discharge sensor

Before spec-in, please consult with an authorized Panasonic dealer.

Increased external static pressure By using booster cable, external static pressure can be increased. 60

Up to 300 mm Up to 500 mm 202 mm


Indoor Unit / E1 Type

S-73ME1E5 / S-106ME1E5 / S-140ME1E5

S-224ME1E5 / S-280ME1E5

Model Name

S-73ME1E5

S-106ME1E5

Power source

S-140ME1E5

S-224ME1E5

S-280ME1E5 220/230/240 V, 1 phase - 50 Hz

220/230/240 V, 1 phase - 50 / 60 Hz kW

7.3

10.6

14.0

22.4

28.0

BTU/h

25,000

36,000

47,800

76,400

95,500

kW

8.0

11.4

16.0

25.0

31.5

BTU/h

27,000

39,000

54,600

85,300

107,500

Cooling

kW

0.480/0.505/0.530

0.520/0.545/0.570

0.600/0.660/0.710

0.870/0.900/0.930

1.270/1.330/1.390

Heating

kW

0.480/0.505/0.530

0.520/0.545/0.570

0.600/0.660/0.710

0.870/0.900/0.930

1.270/1.330/1.390

Cooling

A

2.29/2.30/2.31

2.46/2.46/2.47

2.80/2.90/3.00

4.05/4.06/4.07

6.04/6.06/6.07

Heating

A

2.29/2.30/2.31

2.46/2.46/2.47

2.80/2.90/3.00

4.05/4.06/4.07

6.04/6.06/6.07

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Cooling capacity Heating capacity Power input Running current

Type Fan

Air flow rate (H/M/L)

L/s

384/367/350

500/467/417

600/584/550

934/887/828

1201/1168/1101

External static pressure

Pa

186

176

167

176

216 (235)*

Sound pressure level (L/M/H)

dB(A)

42/43/44

42/44/45

44/46/47

46/47/48

49/50/51 (50/51/52)*

Dimensions

HxWxD

mm

420 x 1,065 x 620

420 x 1,065 x 620

450 x 1,065 x 620

467 x 1,428 x 1,230

467 x 1,428 x 1,230

Liquid

inches (mm)

3/8 (Ø9.52)

3/8 (Ø9.52)

3/8 (Ø9.52)

3/8 (Ø9.52)

3/8 (Ø9.52)

Gas

inches (mm)

5/8 (Ø15.88)

5/8 (Ø15.88)

5/8 (Ø15.88)

3/4 (Ø19.05)

7/8 (Ø22.22)

VP-25

VP-25

VP-25

VP-25

VP-25

47

50

54

110

120

Pipe connections

Drain piping

Net weight

kg

GLOBAL REMARKS

Specifications subject to change without notice.

Rated conditions:

Cooling

Heating

Indoor air temperature

27˚C DB / 19˚C WB

20˚C DB

Outdoor air temperature

35˚C DB / 24˚C WB

7˚C DB / 6˚C WB

* With booster cable.

E1 TYPE HIGH STATIC PRESSURE DUCTED Dimensions SIZE 73-140

SIZE 224-280

1 2 3 4 5 6

1 Refrigerant piping (liquid pipes) Ø9.52 2 Refrigerant piping (gas pipes) 76 type: Ø19.05, 96 type: Ø22.22 3 Power supply outlet (Ø25 grommet, rubber) 4 Power supply outlet (spare) (Ø30 knock-out) 5 Drain port 25 A, male thread 6 Duct connection for suction 7 Duct connection for discharge

Refrigerant liquid line (ø9.52) Refrigerant gas line (ø15.88) Power supply entry Drain connection (25A / VP25) Duct connection for suction Duct connection for discharge 940 793

C

73 / 106

420

395

68

140

450

425

98

(Hole for full circumference) 22 - ø3.2

55 40

20

90 60

130 290 80

(Suspension bolt pitch)

48

4-ø20 (Hole for suspension bolt)

46 16 - ø3.2 (Hole for full circumference) 15

100 100

70 50 55 10

100 100

300

A

310

25 55

620 500

35

500 980 (Suspension bolt pitch)

1010 940

15

35

View in direction of arrow X holes (entire circumference)

holes (for suspension bolts) pitch

Inspection port

100 B

or more (service space)

Electric box

(274)

B

or more (service space)

unit: mm

A

81

holes (entire circumference)

(suspension bolt pitch)

55 C

55 Drain pan

23

Dimensions: mm

61


T1 TYPE

Ceiling

Ceiling mounted

The T1 type ceiling mounted unit features a DC fan motor for increased efficiency and reduced operating sound levels. All unit have the same height and depth for a uniform appearance in mixed installations. It also features a fresh air knockout for improved air quality.

Selfdiagnosing Function

Automatic Fan Operation

Mild dry

Intelligent Auto Swing

Automatic Restart Function

Auto Swing (Auto Flap Control)

Technical focus • Low sound levels • Standardized height of 210 mm for all models • Large and wide air distribution • Easy to install and maintain • Fresh air knockout

Further comfort improvement The wide air discharge opening widens the air flow to the left and the right, so that a comfortable temperature is obtained in the entire room. The unpleasant feeling caused when the air flow directly hits the human body is prevented by the “Draft prevention position”, which changes the swing width, so that the degree of comfort is increased.

4m

Further comfort improvement with airflow distribution

Air distribution is automatically altered depending on the operational mode of the unit

F1 F2

60¡ F3 F4 F5

Heating: F1 to F5 Cooling: F1 to F3

62


Indoor Unit / T1 Type

Model Name

S-36MT1E5

S-45MT1E5

S-56MT1E5

Power source

Fan

3.6

4.5

5.6

7.3

10.6

14.0

12,000

15,000

19,000

25,000

36,000

47,800

kW

4.2

5.0

6.3

8.0

11.4

16.0

BTU/h

14,000

17,000

21,000

27,000

39,000

54,600

Cooling

kW

0.028/0.029/0.029

0.028/0.029/0.029

0.031/0.032/0.032

0.043/0.043/0.044

0.073/0.074/0.075

0.085/0.086/0.088

Heating

kW

0.028/0.028/0.029

0.028/0.028/0.029

0.031/0.031/0.032

0.042/0.042/0.043

0.072/0.073/0.074

0.084/0.085/0.086

Cooling

A

0.26/0.24/0.23

0.26/0.24/0.23

0.28/0.26/0.24

0.38/0.35/0.33

0.62/0.57/0.53

0.69/0.63/0.60

Heating

A

0.26/0.24/0.23

0.26/0.24/0.23

0.28/0.26/0.25

0.38/0.35/0.34

0.62/0.57/0.55

0.69/0.63/0.62

Type

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Air flow rate (H/M/L) L/s

200/167/150

217/183/150

217/183/150

306/250/234

459/383/333

500/434/367

dB(A)

30/32/35

30/33/36

30/33/36

33/36/38

35/38/41

37/40/43

HxWxD

mm

210 x 910 x 680

210 x 910 x 680

210 x 910 x 680

210 x 1,180 x 680

210 x 1,595 x 680

210 x 1,595 x 680

Liquid

inches (mm) 1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

3/8 (Ø9.52)

3/8 (Ø9.52)

3/8 (Ø9.52)

Gas

inches (mm) 1/2 (Ø12.7)

Sound pressure level (L/M/H) Dimensions Pipe connections

S-140MT1E5

BTU/h

Heating capacity

Running current

S-106MT1E5

kW

Cooling capacity

Power input

S-73MT1E5

220/230/240 V, 1 phase - 50 / 60 Hz

Drain piping

1/2 (Ø12.7)

1/2 (Ø12.7)

5/8 (Ø15.88)

5/8 (Ø15.88)

5/8 (Ø15.88)

VP-20

VP-20

VP-20

VP-20

VP-20

VP-20

21

21

21

25

33

33

Net weight

kg

GLOBAL REMARKS

Rated conditions:

Cooling

Heating

Indoor air temperature

27˚C DB / 19˚C WB

20˚C DB

Outdoor air temperature

35˚C DB / 24˚C WB

7˚C DB / 6˚C WB

Specifications subject to change without notice.

1 Drain port VP20 (inner Ø26, hose accessory) 2 Drain for left piping 3 Upper piping outlet port (knock-out hole) 4 Right piping outlet port (knock-out hole) 5 Drain left piping outlet port (knock-out hole) 6 Power supply entry port (knock-out hole Ø40) 7 Remote controller wiring inlet port 8 Wireless remote control receiver mounting part A (body) B (suspension bolt pitch)

28~56 type 910 855

73 type 1,180 1,125

106~140 type 1,595 1,540

(suspension bolt pitch)

T1 TYPE CEILING Dimensions

(suspension bolt pitch)

9 Refrigerant gas piping Size 28-56: Ø12.7 Size 73-140: Ø15.88 10 Refrigerant liquid piping Size 28-56: Ø6.35 Size 73-140: Ø9.52 Air outlet or more Air intake

or more (service space)

Front

or more (service space)

Dimensions: mm

63


K2 TYPE

Wall Mounted

The K2 type wall mounted unit has a stylish smooth design with a washable front panel. Small, lightweight and low noise level makes it ideal for small offices and other commercial applications.

Selfdiagnosing Function

Automatic Fan Operation

Mild dry

Intelligent Auto Swing

Automatic Restart Function

Auto Swing (Auto Flap Control)

Technical focus • Piping outlet in three directions • Washable front panel • Air distribution is automatically altered depending on the operational mode of the unit • Anti-mould washable filters are included

• Closed discharge port • Lighter and smaller units make the installation easy • Quiet operation • Smooth and durable design

External valve

To reduce noise level of refrigerant expansion. (Optional accessory)

CZ-P56SVK2 (for 22 - 56 type) CZ-P160SVK2 (for 73 - 106 type)

Closed discharge port When the unit is turned off, the flap closes completely to prevent entry of dust into the unit and to keep the equipment clean.

Compact indoor units make the installation easy

285 mm

300 mm

825 mm

64

1065 mm


Indoor Unit / K2 Type

S-22MK2E5 / S-28MK2E5 / S-36MK2E5

S-45MK2E5 / S-56MK2E5 / S-73MK2E5 / S-106MK2E5

Quiet operation Low operating noise level makes these units ideal for hotels and hospital.

Smooth and durable design The smooth cover means these units match most modern interiors. Their compact size enables them to blend in, even in small spaces.

Piping outlet in three directions Piping outlet is possible in six directions making the installation work easier. Left side - rear, side and down. Right side - rear, side and down.

Washable front panel

The indoor unit’s front panel can be easily removed and washed for trouble-free cleaning.

Air distribution is automatically altered depending on the operational mode of the unit

F1 F2

90ÂĄ F3

F4

F5

Heating: F1 to F5 Cooling: F1 to F3

65


K2TYPE

Wall Mounted

Model Name

S-22MK2E5

S-28MK2E5

Power source Cooling capacity Heating capacity Power input Running current

S-36MK2E5

S-45MK2E5

220/230/240 V, 1 phase - 50 / 60 Hz

Cooling

kW

2.20

2.80

3.60

BTU/h

7,500

9,600

12,000

4.5 15,000

kW

2.50

3.20

4.20

5.0

BTU/h

8,500

11,000

14,000

17,000

kW

0.018/0.019/0.019

0.018/0.019/0.019

0.021/0.022/0.023

0.020/0.020/0.021

Heating

kW

0.019/0.019/0.020

0.019/0.019/0.020

0.022/0.023/0.023

0.020/0.020/0.021

Cooling

A

0.16/0.16/0.16

0.16/0.16/0.16

0.19/0.19/0.20

0.27/0.26/0.23

Heating

A

Type

0.17/0.17/0.18

0.20/0.20/0.20

0.27/0.26/0.23

Sirocco fan

Sirocco fan

Sirocco fan

L/s

150/125/100

150/125/100

167/142/108

200/175/142

Sound pressure level (L/M/H)

dB(A)

28/32/35

28/32/35

29/33/37

30/34/38

Dimensions

HxWxD

mm

285 x 825 x 217

285 x 825 x 217

285 x 825 x 217

300 x 1,065 x 230

Liquid

inches (mm)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

Gas

inches (mm)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

VP-13

VP-13

VP-13

VP-13

10

10

10

13

Fan

Pipe connections

Air flow rate (H/M/L)

0.17/0.17/0.18 Sirocco fan

Drain piping

Net weight

GLOBAL REMARKS

kg Rated conditions:

Cooling

Heating

Indoor air temperature

27˚C DB / 19˚C WB

20˚C DB

Outdoor air temperature

35˚C DB / 24˚C WB

7˚C DB / 6˚C WB

Specifications subject to change without notice.

K1 TYPE WALL MOUNTED Dimensions S-22MK2E5 / S-28MK2E5 / S-36MK2E5 FILTER SIZE

1 2 3 4 5 6

Refrigerant piping (liquid pipes) Ø6.35 (flared) Refrigerant piping (gas pipes) ø12.7 (flared) Drain hose VP13 (outer Ø18) Rear panel (PL BLACK) Rear panel fixing holes (Ø5 holes or 5 x 13 oval holes) Piping & coiling holes (Ø65)

Gas tube Liquid tube

Front view

66

Drain hose


Indoor Unit / K2 Type

S-56MK2E5

S-73MK2E5

S-106MK2E5

220/230/240 V, 1 phase - 50 / 60 Hz 5.6

7.3

10.6

19,000

25,000

36,000

6.3

8.0

11.4

21,000

27,000

39,000

0.029/0.030/0.030

0.056/0.057/0.057

0.059/0.060/0.060

0.029/0.030/0.030

0.056/0.057/0.057

0.067/0.068/0.068

0.36/0.35/0.32

0.59/0.58/0.52

0.63/0.62/0.55

0.36/0.35/0.32

0.59/0.58/0.52

0.70/0.70/0.62

Sirocco fan

Sirocco fan

Sirocco fan

234/200/175

300/241/192

317/275/217

32/36/40

40/44/47

42/45/49

300 x 1,065 x 230

300 x 1,065 x 230

300 x 1,065 x 230

1/4 (Ø6.35)

3/8 (Ø9.52)

3/8 (Ø9.52)

1/2 (Ø12.7)

5/8 (Ø15.88)

5/8 (Ø15.88)

VP-13

VP-13

VP-13

13

14.5

14.5

A B C D E

Indoor unit:S-45MK1E5 / 56MK1E5 / 73MK1E5 / 106MK1E5

45-56 type 73-106 type 45-56 type Refrigerant tubing (gas tube) 73-106 type Drain hose VP13 (outer dia. 18) Rear panel (PL BACK) Tubing and wiring holes ( 80) Refrigerant tubing (liquid tube)

unit: mm

6.35 (flared) 9.52 (flared) 12.7 (flared) 15.88 (flared)

S-45MK2E5 / 56MK2E5 / 73MK2E5 / 106MK2E5 1 2 3 4 5

Refrigerant tubing (liquid tube) 45-56 / 73-106 type ø6.35 / ø9.52 (flared) 45-56 / 73-106 type ø12.7 / ø15.88 (flared) Refrigerant tubing (gas tube) Drain hose VP13 (outer dia. ø18) Rear panel (PL BACK) Tubing and wiring holes (ø80)

115.9

70 8

60 230

115.9

300

1065

197.4

(2.5)

148.7

2 Gas tube

3 Drain hose

1 Liquid tube

67

200

86 37.3

17.9

67

95

300 48

7.5cm

5cm

132 415 439.8 496.8

Front view

Dimensions: mm

415

(Ø 48

)

158

5cm

(Ø 80

11

230.7

450 95

68

60

384.3 140

80

)

448.2 568.2

4 Rear panel

5 Tubing and wiring holes

67


Floor Standing The compact floor standing P1 units are the ideal solution for providing perimeter air conditioning. The standard wired controller can be incorporated into the body of the unit.

Selfdiagnosing Function

Automatic Fan Operation

Mild dry

Automatic Restart Function

Technical focus • Pipes can be connected to either side of the unit from the bottom or rear • Easy to install • Front panel opens fully for easy maintenance • Removable air discharge grille gives flexible air flow

Effective perimeter handling

A standard wired remote control can be installed in the body

68


Indoor Unit / P1 Type

Model Name

S-22MP1E5

S-28MP1E5

S-36MP1E5

Power source Cooling capacity

Heating capacity

Power input Running current

Fan

S-45MP1E5

S-56MP1E5

S-71MP1E5 7.1

220/230/240 V, 1 phase - 50 / 60 Hz

Cooling

kW

2.2

2.8

3.6

4.5

5.6

BTU/h

7,500

9,600

12,000

15,000

19,000

24,000

kW

2.5

3.2

4.2

5.0

6.3

8.0

BTU/h

8,500

11,000

14,000

17,000

21,000

27,000

kW

0.051/0.056/0.061

0.051/0.056/0.061

0.079/0.085/0.091

0.116/0.126/0.136

0.116/0.126/0.136

0.150/0.160/0.170

Heating

kW

0.036/0.040/0.045

0.036/0.040/0.045

0.064/0.070/0.076

0.079/0.091/0.101

0.079/0.091/0.101

0.110/0.120/0.130

Cooling

A

0.24/0.25/0.26

0.24/0.25/0.26

0.37/0.38/0.39

0.54/0.56/0.58

0.54/0.56/0.58

0.70/0.72/0.73

Heating

A

0.17/0.18/0.19

0.17/0.18/0.19

0.30/0.31/0.32

0.37/0.41/0.43

0.37/0.41/0.43

0.52/0.54/0.56

Type

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Air flow rate (H/M/L) L/s

117/100/83

117/100/83

150/117/100

200/150/133

250/217/184

283/233/200

Sound pressure level (L/M/H)

dB(A)

28/30/33

28/30/33

29/35/39

31/35/38

31/36/39

35/38/41

Dimensions

HxWxD

mm

615 x 1,065 x 230

615 x 1,065 x 230

615 x 1,065 x 230

615 x 1,380 x 230

615 x 1,380 x 230

615 x 1,380 x 230

Liquid

inches (mm) 1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

3/8 (Ø9.52)

Gas

inches (mm) 1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

5/8 (Ø15.88)

VP-20

VP-20

VP-20

VP-20

VP-20

VP-20

29

29

29

39

39

39

Pipe connections

Drain piping Net weight

GLOBAL REMARKS

kg

Rated conditions:

Cooling

Heating

Indoor air temperature

27˚C DB / 19˚C WB

20˚C DB

Outdoor air temperature

35˚C DB / 24˚C WB

7˚C DB / 6˚C WB

Specifications subject to change without notice.

P1 TYPE FLOOR STANDING Dimensions 1 4 x Ø12 holes (for floor fixing) 2 Power supply outlet 3 Air filter 4 Refrigerant piping (liquid pipes) 5 Refrigerant piping (gas pipes) 6 Level adjustment bolt 7 Drain outlet VP20 (with vinyl hose) 8 Refrigerant piping connection port (bottom or rear) 9 Operation switch (remote controller RCS-SH80AG) mounting part 10 Electric equipment box 11 Accessory copper pipe for gas pipe connection

Indoor unit 22 to 36 type 45 type 56 type 71 type

A 1,065

B 665

C 632

1,380

980

947

Liquid pipes

Gas pipes

Ø6.35

Ø12.7

Ø9.52

Ø15.88

Knock-out hole

Dimensions: mm

69


R1 TYPE

Concealed Floor Standing

At just 229 mm deep, the R1 unit can be easily concealed in perimeter areas to provide powerful and effective air conditioning.

Selfdiagnosing Function

Automatic Fan Operation

Mild dry

Automatic Restart Function

Technical focus • Chassis unit for discrete installation • Complete with removable filters • Pipes can be connected to either side of the unit from the bottom or rear • Easy to install

Perimeter air conditioning with high interior quality

70


Indoor Unit / R1 Type

Model Name

S-22MR1E5

S-28MR1E5

S-36MR1E5

Power source Cooling capacity

Heating capacity

Power input Running current Fan

S-45MR1E5

S-56MR1E5

S-71MR1E5 7.1

220/230/240 V. 1 phase - 50. 60 Hz

Cooling

kW

2.2

2.8

3.6

4.5

5.6

BTU/h

7,500

9,600

12,000

15,000

19,000

24,000

kW

2.5

3.2

4.2

5.0

6.3

8.0

BTU/h

8,500

11,000

14,000

17,000

21,000

27,000

kW

0.051/0.056/0.061

0.051/0.056/0.061

0.079/0.085/0.091

0.116/0.126/0.136

0.116/0.126/0.136

0.150/0.160/0.170

Heating

kW

0.036/0.040/0.045

0.036/0.040/0.045

0.064/0.070/0.076

0.079/0.091/0.101

0.079/0.091/0.101

0.110/0.120/0.130

Cooling

A

0.24/0.25/0.26

0.24/0.25/0.26

0.37/0.38/0.39

0.54/0.56/0.58

0.54/0.56/0.58

0.70/0.72/0.73

Heating

A

0.52/0.54/0.56

0.17/0.18/0.19

0.17/0.18/0.19

0.30/0.31/0.32

0.37/0.41/0.43

0.37/0.41/0.43

Type

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Air flow rate (H/M/L) L/s

117/100/83

117/100/83

150/117/100

200/150/133

250/217/184

283/233/200

Sound pressure level (L/M/H)

dB(A)

28/30/33

28/30/33

29/35/39

31/35/38

31/36/39

35/38/41

Dimensions

HxWxD

mm

616 x 904 x 229

616 x 904 x 229

616 x 904 x 229

616 x 1,219 x 229

616 x 1,219 x 229

616 x 1,219 x 229

Liquid

inches (mm) 1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

1/4 (Ø6.35)

3/8 (Ø9.52)

Gas 410 A

inches (mm) 1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

1/2 (Ø12.7)

5/8 (Ø15.88)

VP-20

VP-20

VP-20

VP-20

VP-20

VP-20

21

21

21

28

28

28

Pipe connections

Drain piping Net weight

GLOBAL REMARKS

kg Rated conditions:

Cooling

Heating

Indoor air temperature

27˚C DB / 19˚C WB

20˚C DB

Outdoor air temperature

35˚C DB / 24˚C WB

7˚C DB / 6˚C WB

Specifications subject to change without notice.

R1 TYPE CONCEALED FLOOR STANDING Dimensions 1 4 x Ø12 holes (for floor fixing) 2 Electric equipment box 3 Power supply outlet 4 Air filter 5 Discharge duct connection flange 6 Refrigerant connection outlet (liquid pipes) 7 Refrigerant connection outlet (gas pipes) 8 Drain filter 9 Drain pan 10 Level adjustment bolt 11 Drain outlet VP20 (with vinyl hose)

(inner dimension)

(inner dimension)

(hole pitch=100)

Dimensions: mm

Indoor unit

A

B

C

D

E

F

22 to 36 type

904

692

672

665

500

86

1,219

1,007

1,002

980

900

51

45 type 56 type 71 type

Liquid pipes

Gas pipes

Ø6.35

Ø12.7

Ø9.52

Ø15.88

71


fSV Controllers A wide variety of control options to meet the requirements of different applications.

OPERATION SYSTEM

INDIVIDUAL CONTROL SYSTEMS

Requirements

Normal operation

OPERATION SYSTEM

External appearance Requirements

External appearance

TIMER OPERATION

Operation from anywhere in the room

Quick and easy operation

INDIVIDUAL CONTROL SYSTEMS

Normal operation

TIMER OPERATION

Operation from anywhere in the room

quick and easy operation

Timer Remote Controller (Wired)

Simplified Wireless Remote Controller Remote Controller

Backlit remote controller

CZ-RTC2

CZ-RWSU2 CZ-RWSC2 CZ-RE2C2

CZ-RELC2

Type, model name

Built-in Thermostat

l Timer Remote Controller l Wireless Remote Controller l Simplified Remote

Number indoor units Type, of model name which can be controlled

1 group, 8 units

Built-in Thermostat

Daily and weekly program

(Wired)

CZ-RTC2

l

Controller

1 group, 8 units CZ-RWSC2 1 group, 8 units CZ-RWSU2 CZ-RWSY2 CZ-RWSL2

l

CZ-RWST2 CZ-RWSK2

CZ-RE2C2

NEW

Backlit remote controller

Schedule Timer CZ-ESWC2

Schedule Timer

64 groups, max. 64 units CZ-RELC2

l

·U p to 2 ·U p to 2 controllers can ·U p to 2 controllers can controllers can of indoor units which UseNumber limitations group, 8 units group, 8 units group, 8 units be1connected per group. be1connected per group. be1connected can be controlled per group.

Daily and weekly program

CZ-ESWC2

·R equired power supply from — the system controller · When there is no system 64 groups, max. 64 units controller, connection is possible to the T10 terminal of an indoor unit. · Required power supply from the system controller

l · Up to 2 controllers can be l · Up to 2 controllers can be l · Up to 2 controllers can be connected— · When there is no system Use limitations connected per group. connected per group. per group. controller, connection is possible Mode setting l l l — to the T10 terminal of an indoor unit. Fan speed setting l l l — function ON/Off Temperature setting ll ll ll —— Mode setting l l l Air flow direction l l l —— fan speed setting — l l l Permit/Prohibit switching l — — — Temperature setting — l l l Weekly program l l — — Air flow direction — l l l 1. Setting is not possible when a remote control unit is present. (Use the remote controller for setting.) Permit/Prohibit switching — — — — All specifications subject to change without notice. Weekly program — — l l Function ON/OFF

1. Setting is not possible when a remote control unit is present. (Use the remote control for setting.) All specifications subject to change without notice.

72


FSV Controllers

Backlit remote controller [CZ-RELC2]

Backlit remote controller with simple and friendly operation • LCD backlight display • ON/OFF, operation mode switching, temperature setting, airflow velocity switching, airflow direction setting, alarm display and remote controller self diagnosis can be performed • Built-in temp sensor • Batch group control for up to 8 indoor units

Dimensions H 120 x W 70 x D 16 mm

CENTRALISED CONTROL SYSTEMS

Operation with various function Only ON/OFF operation from from centre station centre station

Simplified load distribution ratio (LDR) for each tenant Touch screen panel

CENTRALIZED CONTROL SYSTEMS Operation with various function from center station

BMS System PC Base

Connection with 3rd Party Controller Seri-Para I/O unit for outdoor unit

P-AIMS Basic Software

Only ON/Off operation from center station

Simplified load distribution ratio (LDR) for each tenant Touch screen panel

BMS System PC Base

Connection with 3rd Party Controller

P-AIMS

Seri-Para I /O unit for outdoor unit

Basic CZ-CSWKC2 Software System Controller

ON/OFF Controller

Intelligent Controller

Interface adaptor

Optional software CZ-64ESMC2

CZ-ANC2

CZ-256ESMC2

CZ-CAPDC2 CZ-CSWKC2

System Controller

ON/Off Controller

64 groups, max. 64 units CZ-64ESMC2

Intelligent Controller

16 groups, max. 64 units CZ-ANC2

64 units x 4 systems, max.

256 units CZ-256ESMC2 (CZ-CfUNC2)

·U p to 10 controllers, can be · Up to 8 controllers (4 main — · A communication adaptor connected to one system. — units + 4 sub units) · Main unit/sub unit (1 main can be connected to one (CZ-CFUNC2) must be 64 units x 4 systems, max. 256 unit + 1 sub unit) connection 64 groups, max. 64 units 16 groups, max. 64 units system. installed for three or more units is possible. · U se without remote controller systems. · Use without remote controller is impossible. is possible. · Up to 10 controllers, can be

connected to one system. · Main unit/sub unit (1 main unit + 1 sub unit) connection is possible. · Use without remote controller is possible.

l l l l l¹ l —

l l l l l¹ l —

· Up to 8 controllers (4 main units + 4 sub units) can be connected to one system. · Use without remote controller is impossible.

l — — — — l —

CZ-CAPC2 Local adaptor for ON/OFF control

Optional software

· A communication adaptor (CZ-CfUNC2) must be installed for three or more systems.

l l — l — l — l — l¹ l l l Remote—sensor (CZ-CSRC2)

l l l l l¹ l l

CZ-CSWAC2 for Load distribution CZ-CSWWC2 for Web application CZ-CSWGC2 CZ-CSWAC2 for Object layout display for Load distribution CZ-CSWBC2 CZ-CSWWC2 for BAC net software for Web application interface

CZ-CSWGC2 for Object*PC layout display required CZ-CSWBC2 (field supply) for BAC net software interface Web Interface *PC required (field supply) Systems

CZ-CWEBC2

Web Interface *PC required Systems (field supply)

Seri-Para I/O unit for each indoor unit CZ-CAPC2

MINI CZ-CAPBC2 Seri-Para I/O Unit Communication Adaptor CZ-CAPBC2

CZ-CFUNC2

Communication Adaptor

LonWorks Interface CZ-CfUNC2

LonWorks Interface CZ-CLNC2

CZ-CWEBC2 *PC required (field supply)

CZ-CLNC2

• This is a remote sensor which can be used with indoor units. Please use it to detect the room temperature when no remote controller sensor or body sensor is used. (connection to a system without a remote controller is possible). • For joint use with a remote control switch, use the remote control switch as main remote controller.

73


Individual Control Systems Individual Control Systems Control contents Control contents Standard Control Standard • Control Control of the various operations of the indoor unit by • C ontrolorofwireless the various operations of the indoor unit by wired remote controller. wired or wireless remote • Cooling or heating modecontroller. of the outdoor unit is decided • Cooling or heating the outdoor unit is decided by by the first priority mode of the of remote controller. first priority of theremote remotecontroller controller.sensor and body • the Switching between • Switching between remote controller sensor and body sensor is possible. sensor is possible. (1) Group control • Batch remote control on all indoor units. (1) Group control • Operation of all indoor cells in the same mode. •• B atch control all indoor units. Up to 8remote units can be on connected. •• O peration indoor in theand same mode. ON/OFF The sensorofisallthe bodycells sensor, thermostat • Up to 8in units can to bethe connected. setting regard temperature set by the remote • T he sensor is the in-unit sensor, and thermostat ON/OFF controller is possible for each indoor unit. setting in regard to the temperature set by the remote (2)controller Main/sub is remote possiblecontrol for each indoor unit. • Max 2 remote controllers per indoor unit. (Main remote (2)controller Main/subcan remote control be connected) •• Max 2 remote controllers per indoor The button pressed last has priority.unit. (Main remote can is bepossible connected) • controller Timer setting even with the sub remote • The button pressed last has priority. controller. • Timer setting is possible even with the sub remote controller.

Part name, model No. Part name, model No. Timer remote controller Timer remote controller CZ-RTC2 CZ-RTC2 Simplified remote controller Simplified CZ-RE2C2remote controller CZ-RE2C2 Wireless remote controller Backlit remote controller / CZ-RWSL2 / CZ-RWSC2 / CZ-RWSY2 / CZ-RWSU2 CZ-RELC2 CZ-RWSK2 / CZ-RWST2 Wireless remote controller Timer remote/ CZ-RWSC2 controller CZ-RWSU2 CZ-RTC2 Timer remote controller CZ-RTC2 Simplified remote controller CZ-RE2C2 /CZ-RELC2 Main or sub Timer remote controller Main or sub CZ-RTC2 Timer remote controller Simplified remote controller CZ-RTC2 CZ-RE2C2 Simplified remotecontroller controller Wireless remote CZ-RE2C2 CZ-RWSY2 / CZ-RWSU2 / CZ-RWSL2 / CZ-RWSC2 / Wireless remote controller CZ-RWSK2 / CZ-RWST2 CZ-RWSU2 / CZ-RWSC2

quantity Quantity 1 unit each 1 unit each

1 unit 1 unit

As required As required

SYSTEM EXAMPLEexample FSV System

Remote controller Standard control

Main

Sub

Remote controller (2) Main/sub remote control Standard control

Main Main

Sub

Sub Main (1) Group control

(2) Main/sub remote control

Sub

(1) Group control

Timer remote controller (CZ-RTC2)

Timer remote controller (CZ-RTC2) Weekly Programme Function • A maximum of 6 settings/day and 42 settings/week Weekly Programme Function can be programmed • A maximum of 6 settings/day and 42 settings/ week can be programmed.

Outing Function

Dimensions H 120 x W 120 x D 16 mm Dimensions H 120 x W 120 x D 16 mm

Basic remotecontroller controllerON/OFF ON/OFF Basic remote • Operation Operation mode modechangeover changeover (Cooling, Heating, (Cooling, Dry, Auto,Heating, fan). Dry, Auto, Fan) • Temperature Temperature setting setting (Cooling/Dry: 18-30 deg (Cooling/Dry: 18-30 deg Heating: 16-30 deg). Heating: 16-30 deg). • Fan speed speed setting settingH/ H/M/ M/LLand andAuto Auto. • Air flow flow direction directionadjustment adjustment.

Time Function Function 24 24 hours hoursreal realtime timeclock clock • Day Day of of the the week week indicator indicator. 74

• This function can prevent the room temperature Outing Function from dropping or rising when the occupants are out • This function can prevent the room temperature for a long time from dropping or rising when the occupants are out for a long time.

Sleeping Function

• This function controls the room temperature for Sleeping Function comfortable sleeping • This function controls the room temperature for comfortable sleeping.

Built in Temp Sensor

Max. 88 indoor from Max. indoorunits unitscan canbe becontrolled controlled from one remote controller one remote controller Remote control Remote controlby bymain mainremote remotecontroller controller and sub controller is possible and sub controller is possible Max. 2 remote controllers (main remote controller Max. 2 remote controllers (main remote controller and and sub controller) can be installed for one sub controller) can be installed for one indoor unit indoor unit.


FSV Controllers

Wireless remote controller

Wireless remote controller

Remote control by main remote controller and sub controller is possible Remote control by main remote and sub(main controller • Max.controller 2 remote controllers remoteis controller possible and sub controller) can be installed for one • Max. 2 remote controllers (main remote and sub controller) can be installed indoor controller unit. for one indoor unit

Y1 type CZ-RWSY2

U1 type CZ-RWSU2

L1 type CZ-RWSL2

For all indoor units CZ-RWSC2 T1 / D1 Type CZ-RWST2

U1 type CZ-RWSU2

When CZ-RWSC2 is used, wireless control When CZ-RWSC2 is used, becomes wireless control possible possiblebecomes for all indoor units for all indoor units • When a separate receiver is set up in a different • When a separate receiver is set up in a different room, control room also room, control from that roomfrom alsothat becomes becomes possible possible. • Automatic operation by means •ofAutomatic the emergency operation buttonofisthe possible even operation by means emergency when the remote controller has been lost orbutton the batteries have even been when exhausted operation is possible the remote controller has been lost or the batteries In addition, there are other functions as temperature setting, have beensuch exhausted. K1 type

operation switching, airflow direction/fan speed setting, etc. CZ-RWSK2 In addition, there are other functions such as Ventilation independent operation is possible temperature setting, operation switching, When commercial ventilation fanswind or heat-exchange ventilation fans haveetc been direction/fan speed setting,

installed, they can be operated with this remote control (interlocked operation with the indoor unit or independent ventilation ON/OFF).independent operation is possible Ventilation When commercial ventilation fans or heatexchange ventilation fans have been installed, they for all indoor can be operated with this remote control units CZ-RWSC2 (interlocked operation with the indoor unit or independent ventilation ON/Off).

Simplified remote controller (CZ-RE2C2) Simplified remote controller (CZ-RE2C2) A remote controllerwith withsimple simplefunctions functions and basic operation remote controller and basic operation • Suitable for open rooms or hotels where detailed functions are not required. • Suitable for open rooms or hotels where detailed functions are not required • ON/OFF, operation mode switching, temperature setting, wind velocity switching, • ON/OFF, operation mode switching, temperature setting, airflow velocity switching, wind direction setting, alarm display, and remote controller self-diagnosis can be airflow direction setting, alarm display and remote controller self-diagnosis can be performed. performed • Batch group control for up to 8 indoor units. • Batch group control for up to 8 indoor units • Remote control by main remote controller and sub controller is possible with a • Remote control by main remote controller and sub controller is possible with a simplified remote controller or a wired remote controller (up to two units). simplified remote controller or a wired remote controller (up to two units) Dimensions Dimensions H 120 H 120 xx W W 70 70 xx D D 17 16 mm mm

Backlit remote controller [CZ-RELC2] Backlit remote controller [CZ-RELC2] NEW

Backlit remote and friendly operation Backlit remotecontroller controllerwith withsimple simple and friendly operation backlightdisplay display.(ideal for bedrooms) • LCD backlight operation mode modeswitching, switching,temperature temperaturesetting, setting, wind velocity velocityswitching, switching, • ON/OFF, operation airflow wind direction andremote remotecontroller controllerself selfdiagnosis diagnosis can airflow directionsetting, setting,alarm alarm display, display and can bebe performed. performed temp sensor sensor. • Built-in temp group control controlfor forup uptoto88indoor indoorunits units. • Batch group • Remote control by main remote controller and sub controller is possible with a simplified remote controller or a wired remote controller (up to two units). Dimensions Dimensions H 120 x W 70 x D 16 mm

Outing Function • This function can prevent the room temperature from dropping or rising when the occupants are out for a long time. 75


Centralised Control Systems System controller (CZ-64ESMC2) System controller (CZ-64ESMC2) System controller (CZ-64ESMC2) Dimensions Dimensions 160 x W 160 x D 21 + 69 160 x W 160dimension x D 21 + mm) 69 (embedding Dimensions (embedding dimension mm) 160 x W 160 x D 21 + 69 Power supply: AC 220 to 240 (embedding dimension mm) V Power supply: AC 220 to I/O part: Remote input 240 V (effective voltage: 24toV): Power supply: ACDC 220 I/O part: Remote input All ON/All OFF Remote output 240 V (effective voltage: DC 24 V): (voltage-free contact): I/O part: Remote inputAll ON/ All ON/All Off Remote All OFF (external Power (effective voltage: DC 24 V): output (voltage-free contact): supply within DCRemote 30 V, max 1 All ON/All Off (external A) output (voltage-free contact): Power supply within DC 30 Total wiringOff length : 1 km All ON/All (external V, max 1 A) Power supply within Total wiring length : 1DC km30 V, max 1 A) Total wiring length : 1 km

Individual control is possible for max 64 groups, indoor units. Individual control64 is possible for max 64 groups, 64 indoor units. Individual control is possible for • Control of 64 indoor units divided into 4 max 64 groups, 64 can indoor units. zones. (One zone have up to 16 • Control of 64 indoor units divided into 4 groups, and one group can have up to 8 zones. can have up to into 16 groups, • units.) Control(One of 64zone indoor units divided 4 and one(One group cancan have up to 8tounits.) zones. zone have up 16 groups, • Control is possible for ON/OFF, operation • and Control isgroup possible for ON/OFF, onefan canair have updirection to 8operation units.) mode, speed, flow (only mode, fan speed, air flow direction (only • when Controlused is possible for ON/OFF, operation without a remote controller), when used withoutair a flow remote controller), mode, fan monitoring, speed, direction (only operation alarm monitoring, operation monitoring, alarm monitoring, when used without a remote controller), ventilation, remote controller local ventilation, remote controller local operation operation operation monitoring, prohibition,alarm etc. monitoring, prohibition, remote etc. ventilation, controller local operation prohibition, etc. Individual All operations are possible also from the remote controller. However, the contents will be changed to Individual All operations are possible also from the remote the contents of the controller operated last. controller. However, the contents will be changed to Central 1 The remote controller cannot be used for ON/Off. the contents of the controller operated last. (All other operations are possible from the remote Central 1 The remote controller cannot be used for ON/Off. controller.) (All other operations are possible from the remote The with remoteacontroller cannot be used foran mode • Central Joint3use remote controller, controller.) change or temperature setting change. (All other intelligent controller, schedule Central 3 The remote controlleracannot be usedtimer, for mode operations are possible from the remote controller.) change or temperature setting change. (All other etc. is Central 4 possible The remote controller cannot be used for operation operations are possible from the remote controller.) modenumber change. other operations are possibleis (The maximum of (All connectable controllers Central 4 The remote controller cannotsystem be used for operation from the central remote controllers controller.) on the same circuit.) 10, including other mode change. (All other operations are possible (In case of from joint the use remote with a wireless remote controller, there controller.) are limitations for the control mode. Please use only with • Joint use with a remote controller, an “Individual” and “Central 1”.)

•• AAcontrol to to thethe useuse controlmode modecorresponding corresponding condition can be selected from 10 patterns • condition A control mode corresponding to 10 thepatterns use can be selected from condition can be selected from 10 patterns A : Operation mode: Central control mode or remote control A : Operation mode: Central control mode or remote control mode mode can be selected A : Operation mode: Central control mode or remote control can be selected Central control mode: The system controller is used as mode be selected Centralcan control mode: The system controller is used as centralised centralised control device. (Setting from a remote controller can Central control(Setting mode: The controller is can usedbeasprohibited control device. fromsystem a remote controller be prohibited by prohibiting local operation from the system centralised control device. (Setting a remote controller can by prohibiting local operation from thefrom system controller.) controller.) be prohibited prohibiting local operation from theassystem Remote controlbymode: The system controller is used a remote Remote control mode: The system controller is used as a controller.) controller. (Setting from the system controller can be prohibited by remote controller. (Setting from the system controller can be Remote control mode: The system controller used unit.) as a prohibiting local operation from another central iscontrol prohibited by prohibiting local operation from another central remote controller. (Setting from the system controller can be control unit.) prohibited by unit prohibiting operation another B : Controlled numberlocal mode: All modefrom or zone 1, 2,central 3, 4 control unit.) mode can be selected B : Controlled unit number mode: All mode or zone 1, 2, 3, 4 All mode: All, zone, or group unit can be selected. mode can be selected B : Controlled number mode: All mode 1, 2, 3,units 4 Zone 1, 2, 3, 4unit mode: Setting is possible onlyorforzone the indoor All mode: All, zone, or group unit can be selected. mode be3,selected of zonecan 1, 2, or 4. Zone 1, 2, 3, 4 mode: Setting is possible only for the indoor All mode: All, zone, or group unit can be selected. units of zone 1, 2, 3, or 4. Zone 1, 2, 3, 4 mode: Setting is possible only for the indoor units of zone 1, 2, 3, or 4. Connection example Connection example Connection example All mode All mode B B Controlled Controlled unit B unit number Controlled number mode unit mode number mode

Zone 1 All mode Zone 1 mode mode Zone Zone 1 2 Zone 2 mode mode mode Zone Zone 2 3 Zone 3 mode mode mode Zone Zone 3 4 Zone 4 mode mode mode Zone 4 mode

System controller System controller

controller, a schedule timer, • intelligent Joint use with a remote controller, an etc. is possible schedule timer, etc. • intelligent Control ofcontroller, systemsawithout a remote iscontroller possible and of main/sub systems

(The maximum number of connectable system controllers is 10, including same circuit.) (a totalother of central up tocontrollers 2 units)onisthepossible (The maximum number of connectable system controllers is 10, (In case of joint use with a wireless remote controller, there are including other central controllers on the same circuit.) limitations for the control mode. Please use only with (In case of joint use with a wireless remote controller, there are “Individual” and “Central 1”.) limitations for the control mode. Please use only with “Individual” and “Central 1”.)

• Control of systems without a remote of main/sub • controller Control ofand systems withoutsystems a remote (a total of up to 2 units) is possible controller and of main/sub systems (a total of up to 2 units) is possible

A Operation Mode A Operation mode Central Control Mode Remote Control Mode Central controlAmode Remote Operation modecontrol mode All central control All remote control mode All central control Central mode Remote control Example control 1 All remote control Example 1 All central control Zone 1 central control remote control Zone 1 remote control Zone 1 central control All Example Example 21 Zone 1 remote control Example 2 Zone 1 central control Zone 2 remote control Zone 2 central control Zone 1 2 remote remote control control Example 2 Zone 2 central control Example 3 Example 3 Zone 2 remote control 3 central control Zone control Zone 3 remote control Zone 2 3 central central control Example 3 Example 4 Zone 3 remote control Example 4 Zone 3 central control 43 remote control Zone remote control Zone 4 central control Zone 4 remote control Example 4 Zone 4 central control Example 5 Example 5 Zone 4 remote control Zone 4 central control Example 5

Individual remote controller

Control mode example 2: Central control for zone 1 Individual remote controller Control mode example 2: Central control for zone 1

System controller

Group control

System controller Control mode example 3: Remote control forGroup zone 2control Control mode example 3: Remote control for zone 2

System controller System controller

Individual remote controller

Control mode example 4: Central control for zone 3 Individual remote controller Control mode example 4: Central control for zone 3

System controller

System without a remote controller System without a remote controller Control mode example 5: Remote control for zone 4 System controller

Control mode example 5: Remote control for zone 4 System controller Control mode example 1: All central control System controller Control mode example 1: All central control

76

Control of a group without remote controller Control of a group without remote controller


FSV Controllers

Centralised Control Systems Schedule timer (CZ-ESWC2) Schedule timer (CZ-ESWC2) •• AAfunction functionfor forpausing pausing the timer case the timer in in case of of national holidayshas hasbeen beenadded, added,and andtimer national holidays timer operation also be stopped fortime a operation also can becan stopped for a long long time

Dimensions Dimensions H 120 120 xx W W 120 120 xx D D 16 16 mm mm H

· By setting holidays or operation stop within one ·B week, y setting operation the holidays timer canorbe pausedstop just within for thatone week, week. the timer can be paused just for that week. ·A Allll timer timer settings settingscan canbe bestopped stoppedwith withthe thetimer timer “ON/OFF “ON/Off effective” effective”button. button.(Return (Returntototimer timer operation operation isis made madeby bypressing pressingthe thebutton buttonagain.) again.)

Up to to 64 64 groups groups(max (max64 64indoor indoorunits) units)can can be controlled controlleddivided dividedinto into8 8timer timer groups groups •• Six Six program programoperations operations(Operation/Stop/ (Operation/Stop/ Local permission/ Local prohibition) per Local permission/ Local prohibition) per day day can be set in a program for one can be set in a program for one week week · Only or or stop, remote controller local · Onlyoperation operation stop, remote controller local permission or remote controller local prohibition, permission or remote controller local prohibition, and combinations areare possible. andtheir theirrespective respective combinations possible. (Operation + local permission, stop + local (Operation + local permission, stop + local prohibition, only local permission, etc.) prohibition, only local permission, etc.) · Local prohibition and the combination of the · Local prohibition and the combination of the three items of temperature setting, mode three items of temperature setting, mode change, operation/stop can bebe setset at the change,and and operation/stop can at the time of installation. time of installation.

Connection Connectionexample example11(POWER (powerSUPPLY supplyfROM fromTHE theINDOOR indoor UNIT) unit)

The power supply for the schedule timer is taken from one of the following. The power supply for the schedule timer is taken from one of 1. ontrol circuit board (T10) of a nearby indoor unit (power the Cfollowing. from the indoor unit). 1. supply Controlwiring circuitlength: boardwithin (T10) 200m of a nearby indoor unit (power 2. S ystem wiring controller (power supply wiring withinunit). 100 m supply length: within 200m fromlength: the indoor thecontroller indoor unit). 2. from System (power supply wiring length: within 100 m When fromthe thepower indoorsupply unit). for the schedule timer is taken from the control circuit board of theforindoor unit, that timer indoorisunit cannot When the power supply the schedule taken frombe used with other control using the T10 terminal. the control circuit boarddevices of the indoor unit, that indoor unit As operation mode and temperature settingsusing are not cannot be used with other control devices thepossible T10 with the schedule timer, it must be used together with a remote terminal. controller, a system an intelligent controller, Also, As operation modecontroller, and temperature settings are notetc. possible as not havetimer, an address function, thewith control withit does the schedule it mustsetting be used together a function of a system controller etc. mustanbeintelligent used for address remote controller, a system controller, controller, setting. etc. Also, as it does not have an address setting function, the control function of a system controller etc. must be used for address setting. Individual All operations are possible also from the remote controller. However, the contents will be changed to the contents of the controller operated last. Central 1 The remote controller cannot be used for ON/OFF. (All other operations are possible from the remote controller.) Central 3 The remote controller cannot be used for mode change or temperature setting change. (All other operations are possible from the remote controller.) Central 4 The remote controller cannot be used for operation mode change. (All other operations are possible from the remote controller.)

Remote controller Remote controller

Schedule timer

Connection example 2 (power supply from the central controller)

Connection Indoor/outdoor example 2 (POWER SUPPLY fROM THE CENTRAL CONTROLLER) operation wire

Indoor/outdoor operation wire

Schedule timer

System controller

Schedule timer

System controller

Zone 1 Centralised addresses 1 to 16

Zone 1 Centralised addresses 1 to 16 Zone 2 Centralised addresses 17 to 32 Zone 2 Centralised addresses 17 to 32 Zone 3 Centralised addresses 33 to 48 Zone 3 Centralised addresses 33 to 48 Zone 4 Centralised addresses 49 to 64 Zone 4 Centralised addresses 49 to 64

Timer group 1: Centralised addresses 1 to 8

Timer group 2: Centralised addresses 9 to 16

Timer group 1: Centralised Timer group 3: addresses 1Centralised to 8 addresses 17 to 24

Timer group 2: Centralised Timer group 4: addresses 9Centralised to 16 addresses 25 to 32

Timer group 3: Centralised Timer group 5: addresses Centralised 17 to 24 addresses 33 to 40

Timer group 4: Centralised addresses Timer group 6: 25 to 32 Centralised addresses 41 to 48

Timer group 5: Centralised Timer group 7: addresses Centralised 33 to 40 addresses 49 to 56

Timer group 6: Centralised Timer group 8: addresses Centralised 41 to 48 addresses 57 to 64

Timer group 7: Centralised addresses 49 to 56

Timer group 8: Centralised addresses 57 to 64

77


ON/OFF controller (CZ-ANC2)

ON/OFF controller (CZ-ANC2) • 16 groups of indoor units can be controlled. Collective and individual group (unit) •• 16 groups control of indoor units can be controlled control can also be performed. • Collective control and individual group (unit) control • Up 8 ON/OFF controller (4 main, 4 sub) can can to also be performed be installed in one link system. •U p to 8 ON/OFF controller (4 main, 4 sub) can be • The operation status can be determined installed in one link system immediately. • The operation status can be determined immediately

Power supply: I/O part: Power supply: I/O part:

Dimensions H 121 x W 122 x D 14 + 52 (embedding dimension mm) Dimensions H 121 x W 122 x D 14 + 52 (embedding dimension mm)

Note: As operation mode and temperature settings are not possible with the ON/Off controller, it must be used together with a remote controller, a system Note: As operation mode and temperature settings are not possible with the controller etc. ON/OFF controller, it must be used together with a remote controller, a system controller etc.

AC 220 to 240 V Remote input (effective voltage: within DC 240 V): All ON/OFF Remote output AC 220 to 240 V(allowable voltage: within DC 30 V): All ON, All alarminput (effective voltage: within DC 24 V): All ON/OFF Remote Remote output (allowable voltage: within DC 30 V): All ON, All alarm

Web Interface InterfaceSystems Systems Web Web Interface (CZ-CWEBC2)

Web Interface (CZ-CWEBC2) Functions Functions

(Dimensions: H 248 x W 185 (Dimensions: x D 80 mm) H 248 x W 185 x D 80 mm) AC 100 to 240 V (50/60Hz), AC 100 to 240 Vpower (50/60Hz), 17 W (separate supply) 17 W (separate power supply)

Note: It is recommended to install a remote controller Note: It is recommended install a remote controller or a system controller ontosite to enable local control or if a system controller on site to enable local control if the it network experience a problem. network experiences a problem.

*Power supply *Power supply

to set set to toevery everyroom roomby by Easy to recognisableicon iconand anduser-friendly user-friendly recognizable remote control controlwindow window remote selected, the If any of of the the indoor indoorunits unitsare is selected, remote control window window shown shown will willbe be displayed for displayed fordetailed detailedsetting settingmodifications. modifications.

Easy to to manage manageand andmonitor monitoreach tenant use * use * each tenant’s otherwise each Each floor floor or or tenant, tenant, or otherwise each zone can can be be displayed displayedand andcontrolled. controlled. All unit statuses statuses can canalso alsobe bedisplayed displayedon oneone screen. on screen.

Program Timer set set Programme Timer 50 daily timers with with 50 50 actions actionseach eachday, 50 daily timers day, 50 timers, weeklyholiday timers,timer, holiday timer, 5day weekly 5 special special dayeach timers, for each tenant timers, for tenant. Web interface interface system system not **Web not applicable applicablefor forload distribution. load distribution.

78

•• All Units control control All Units •• Alarm Log Alarm Log •• Mail Sent Log Log Mail Sent •• Program Timer set 50 50 daily dailytimers timerswith with Program Timer set 50 actions each day, 50 weekly timers 50 actions each day, 50 weekly timers 50 timers, 11 holiday holidaytimer, timer,55 50 weekly weekly timers, special day timers, for each tenant special day timers, for each tenant •• Prohibit Remote Control set Prohibit Remote Control set •• IP ADDRESS could couldbe bechanged changedvia via IP ADDRESS Internet Internet

•• Access andoperation operationby byWeb Web Access and browser browser •• Icon display Icon display •• Language codesavailable availablein in Language codes English, English, french, German, Italian, French, German, Italian, Portguese, Portguese, Spanish Spanish •• Individual control possible(max. (max. Individual control possible 6464 indoor units) ON/Off operation indoor units) ON/OFF operation mode, set temperature, temperature,fan fanspeed, speed, mode, set flap set, timer on/off alarm code Flap set, timer on/off alarm code monitoring, prohibitRemote RemoteControl Control monitoring, prohibit •• Zone control * Zone control *

Web WebInterface Interface (CZ-CWEBC2) (CZ-CWEBC2) Indoor/outdoor Indoor/outdoor Linksystem system control controlwire wire Link (non-polar) (non-polar)

LAN LAN(10/100BASE-T) (10/100BASE-T)

Intranet Intranet

Maximum Maximumnumber numberofofconnections: connections: Indoor Indoorunits: units:6464 Outdoor Outdoorunits: units:3030 Link Linksystem system(Indoor/outdoor (Indoor/outdoor control controlwire) wire): 1: 1

PCPC (field supply) (field supply)

* Required when more than 129 indoor units are connected


FSV Controllers

Intelligent controller (CZ-256ESMC2)

Intelligent controller (CZ-256ESMC2) • Limitation contents for prohibited operation •Prohibition Limitation contents for prohibited operation means limitation of the operation Prohibition means of the operation contents contents from the limitation remote controller. It is also from the remote controller. It is also possible possible to change the prohibition items. to change the prohibition items. Touch panel Touch panel

Limitation contents Limitation contents (Limitations can be user defined) (Limitations can be user defined) Individual Individual

Dimensions H 240 x W 280 x D 138 mm Dimensions Power 100 mm to 240 V (50 Hz), 20 W (separate power supply) H 240 xsupply W 280 xAC D 138 I/O partsupply Remote in 240 put (voltage-free All ON/OFF Power AC 100 to V (50 Hz), 20 contact): W (separate power supply) Remote output (voltage-freecontact): contact): ON, All alarm I/O part Remote in put (voltage-free AllAll ON/OFF (external power supply within DC 30 V, 0.5 Remote output (voltage-free contact): All ON,A) All alarm Total wiring length: 1 km power for each system (external supply within DC 30 V, 0.5 A) Only for embedding in the Total wiring length: 1 km for panel each system

Prohibition 1 Prohibition 1 Prohibition 2 Prohibition 2

Only for embedding in the panel

Prohibition 3

•• Max Max 256 256 indoor indoorunits units(4(4systems systemsx x6464units) can becan controlled. In caseIn ofcase threeof orthree moreor units) be controlled. systems (more (more than 129 units), a more systems than 128 units), a communication adapter communication adapterCZ-CFUNC2 CZ-CFUNC2must must be installed installedon the outside

Prohibition 3

in in zone units, •• Operation Operationisispossible possibleasasbatch, batch, zone in tenant and in and group units, in tenant in units group units •• ON/OFF, ON/OFF, operation operationmode modesetting, setting, temperature setting, air temperature setting,for forfan fanspeed speedsetting, setting, flowflow direction setting (when usedused without a air direction setting (when remote controller), and remoteand controller without a remote controller), remote local operation controller localprohibition operation (prohibition prohibition 1, 2, 3, 4) can be done (prohibition 1, 2, 3, 4) can be done controller is is •• AAsystem systemwithout withouta aremote remote controller possible. Joint or possible. Jointuse usewith withaaremote remotecontroller controller a system controller is also possible or a system controller is also possible setting •• Use Use of of aa schedule scheduletimer timerand andholiday holiday also canalso be done setting can be done ofof thethe airair conditioning •• Proportional Proportionaldistribution distribution energy is possible. Including csv-file export conditioning energy is possible. Including via CF-card (supplementary accessory) csv-file export via CF-card (supplementary accessory) • NEW function: Pulse signal input from consumption meter • electric/gas NEW function: Pulse signal input from electric/gas consumption meter In case of joint use with a wireless remote control system, there are

Prohibition 4 Prohibition 4

There is no limitation for the operation of the remote controller. However, the contents will be changed to There is no limitation for the operation of the remote the contents of the controller operated last. (Lastcontroller. However, the contents will be changed to pressed priority.) the contents of the controller operated last. (LastThe remote controller cannot be used for ON/Off. pressed priority.) (All other operations are possible from the remote The remote controller cannot be used for ON/OFF. (All controller.) other operations are possible from the remote The remote controller cannot be used for ON/Off, controller.) operation mode change and temperature setting. The remote controller cannot be used for ON/OFF, (All other operations are possible from the remote operation mode change and temperature setting. (All controller.) other operations are possible from the remote The remote controller cannot be used for operation controller.) mode change and temperature setting. (All other The remote controller cannot be used for operation operations are possible from the remote controller.) mode change and temperature setting. (All other The remote controller cannot be used for operation operations are possible from the remote controller.) mode change. (All other operations are possible The remote controller cannot be used for operation from the remote controller.) mode change. (All other operations are possible from the remote controller.) Linked system No. 1

Intelligent controller Intelligent CZ-256ESMC2 controller CZ-256ESMC2

Linked system No. 1

Linked system No. 2 signal x 4 System System signal x 4 RS 485 (Polarity shield wire) RS 485 (Polarity shield wire)

Linked system No. 2

Linked system No. 3 Linked system No. 3

Communication adapter Communication CZ-CfUNC2 adapter CZ-CFUNC2

Linked system No. 4 Linked system No. 4 System signal x 4

System signal x 4 Display sample Max. 4 links can be connected for the indoor/outdoor operation line = Max. 64 indoor units x 4 (256 units) Max.304 outdoor links canunits be connected for the indoor/outdoor Display sample Max. x 4 (120 units) operation line = Max. 64 indoor units x 4 (256 units) Max. 30 outdoor units x 4 (120 units)

Communication adaptor Communication adaptor (CZ-CFUNC2) (CZ-CFUNC2)

limitations for the control mode. Please use only with “Permission” and In case of joint “Prohibition 1”.use with a wireless remote control system, there are limitations for the control mode. Please use only with “Permission” and “Prohibition 1”.

Web Web application application

* Required when more than 129 indoor * Required when more than 128 indoor units units are connected. are connected.

79


Panasonic total air conditioning management system Panasonic total air conditioning management system

P-AIMS P-AIMS

P-AIMS Basic software / CZ-CSWKC2 Up to 1024 indoor units can be controlled by one PC

P-AIMS Basic software / CZ-CSWKC2 functions of basic software

Up to 1024 indoor units can be controlled by one PC • Standard remote control for all indoor units Functions of schedule basic software • Many timer programs can be set on the calender • Detailed information display alarms • Standard remote control for allfor indoor units • CSV file output with alarm history, • Many timer schedule programs canoperating be set on status. the calender Automatic data backup to HDD •• Detailed information display for alarms • CSV file output with alarm history, operating status • Automatic data backup to HDD

With 4 upgrade packages the basic software can be upgraded to suit individual requirements CZ-CfUNC2 With 4 upgrade packages the basic software can be upgraded to suit individual requirements

CZ-CFUNC2

The P-AIMS is ideal for large areas/buildings such as shopping centers, universities and office buildings. Up to eight Communication Adaptors (C/A) can be connected to a P-AIMS to enable P-AIMS is ideal for large areas/buildings such as shopping centres, universities control of 1024 indoor units with one “P-AIMS” PC. and office buildings. Up to eight Communication Adaptors (C/A) can be connected to a P-AIMS to enable control of 1024 indoor units with one “P-AIMS” PC. User PC

Converter

User PC

Building A

(Field supply)

USB line

RS485 (Polarized)

Converter

Building A

(Field supply)

USB line

PC Environment: XP Professional CPU: Pentium 2.8GB or over Memory: 2GB or over PC Environment: HDD: 100GB or over XP Professional CPU: Pentium 2.8GB or over •Memory: Wiring length (PC~C/A) Max. 1 km 2GB or over Max.100GB 8 C/A for 1 system HDD: or over • Wiring length for each link from C/A • Max. 1 km • Wiring length (PC~C/A) Max. 1 km Max. 16 C/A for 1 system • Wiring length for each link from C/A Max. 1 km

RS485 (Polarized)

Communication Adaptor

Communication Adaptor

Building B

Building B

Building D

Building D

80


FSV Controllers

P-AIMS optional software CZ-CSWAC2 for Load distribution

P-AIMS optional software Load distribution calculation for each tenant CZ-CSWAC2 for Load distribution • Air-conditioner load distribution ratio is calculated for each Load distribution calculation each tenant unit (tenant) with used energyfor consumption data (m3, kWh). • Calculated data is stored with CSV type file. • Air-conditioner load distribution ratio is calculated for each Data(tenant) of last with 365 used days energy is stored • unit consumption data (m3, kWh) • Calculated data is stored with CSV type file • Data of last 365 days is stored

P-AIMS optional software CZ-CSWWC2 for Web application Web accessoptional & control from remote station P-AIMS software CZ-CSWWC2 for Web • Accessing P-AIMS software from application remote PC. • You can monitor/operate FSV systems by using Web Web access & control from remote station browser (Inernet Explorer). • Accessing P-AIMS software from remote PC • You can monitor/operate FSV systems by using Web browser (Internet Explorer)

P-AIMS optional software CZ-CSWGC2 for Object layout display Whole system can be controlled visually P-AIMS optional software • Operating status monitor is availablelayout on the layout display. CZ-CSWGC2 for Object display

• Object’s layout and indoor unit’s location can be checked at once. Whole be controlled visually • Each system unit can can be controlled by virtual remote controller on the • display. Operating status monitor is available on the layout display Max 4 layout are shown at once. • Object’s layoutscreens and indoor unit’s location can be checked at once • Each unit can be controlled by virtual remote controller on the display • Max 4 layout screens are shown at once

P-AIMS optional software CZ-CSWBC2 for BACnet software interface

P-AIMS software Connectableoptional to BmS system CZ-CSWBC2 for BACnet software interface • Can communicate with other equipment by BACnet protocol. Connectable BMS • FSV systemsto can be system controlled by both BMS and P-AIMS. • Max 255 indoor units can be connected to 1 PC (that has • P-AIMS Can communicate with other equipment by BACnet protocol. basic & BACnet software). • FSV systems can be controlled by both BMS and P-AIMS. • Max 256 indoor units can be connected to 1 PC (that has P-AIMS basic & BACnet software).

81


T10 Terminal for External Control T10 Terminal for External Control (Digital Connection) (Digital Connection) Connecting an fSV indoor unit to an external device is easy. Connecting an indoor unit to an The T10 device Terminal featured in the external is easy. electronic circuit board of in allthe indoor The T10 Terminal featured units enables digital connection to electronic circuit board of all indoor external devices. units enables digital connection to external devices.

1. T10 Terminal Terminal Specification Specification(T10:CN061 (T10:CN061atatindoor indoorunit unit PCB) PCB) 11 • Control items: 1. Start/stop input COM • ControlCOM items: 22 1. Start/stop input 2. Remote controller prohibit input 33 2. Remote controller prohibit input 3. Start signal output 44 3. Start signal output +12V 4. Alarm signal output COM 55 +12V COM 4. Alarm signal output T10 T10 (yellow) (yellow)

11 COM 22 COM 33

66

300msec. 300msec. or more more or

T10 T10 (yellow) (yellow)

1-2 (pulse (pulse input) input) 1-2

ON ON

OFF OFF

44 +12V +12V COM COM 55

Condition Condition

+12 +12

4-5 (output) (output) 4-5

Unit condition condition Unit

•• Example Exampleof ofwiring wiring

ON ON

NOTE: The within 2.0m The wire wire length lengthfrom fromindoor indoorunit unittotothe theRelay Relaymust mustbebe within 2.0m. Pulse signal (Refer to to JP001) signalchangeable changeabletotostatic staticwith withJPJPcutting. cutting. (Refer JP001)

66

300msec. 300msec.

or more more or 1. 1-2 1-2 (Pulse (Pulse input): with a pulse signal. (1 1. input):Unit UnitON/OFF ON/OFFcondition conditionswitching switching with a pulse signal. 1-2pulse (pulse input) signal: shortage status more thanthan 300msec.or more)more) 1-2 (pulse input) (1 pulse signal: shortage status more 300msec.or 2. 2-3 2-3 (Static (Static input): 2. input):Open/ Open/Operation Operationwith withRemote Remoteisispermitted.(Normal permitted.(Normal condition) Close/ condition) Close/Remote Remotecontroller controllerisisprohibited. prohibited. +12 the unit ON. / No output at OFF 3. 4-5 (Static output): 12V output during +12 4-5 (output) 3. 4-5 (Static output): 12V output during the unit ON. / No output at OFF. 4-5 (output) 4. 5-6 5-6 (Static (Static output): 4. output):12V 12Voutput outputwhen whensome someerrors errorsoccur occur/ No / Nooutput outputatatnormal normal. Unit condition condition Unit

ON ON

OFF OFF

ON ON

Example 2. Usage Example Forced OFF OFF control control Forced

Operation ON/OFF ON/OFF signal signaloutput output Operation

Condition •• Condition

Condition •• Condition

1-2 (Static (Static input): 1-2 input): Close/ Close/ Operation Operationwith withRemote Remoteisispermitted. permitted.(Normal (Normal condition) Open/ controller operation is is condition) Open/ Unit Unitisisforcibly forciblyOFF Offand andRemote Remote controller operation prohibited. prohibited.

4-5 (Static (Static output): 4-5 output): 12V 12V output output during duringthe theunit unitON ON/ /No Nooutput outputatatOFF OFF

Exampleof ofwiring wiring •• Example T10 T10 (YEL) (YEL)

Indoor unit unit Indoor control PCB PCB control

T10 T10 (YEL) (YEL)

Relay (Field (Field supply) supply) Relay

Relay (Field Relay (fieldsupply) supply)

CentralCentral controlcontrol

The contact contact in in the the The figure is is aa state state figure where the the card card is is where pulled out. out. pulled POWER POWER

External contact contact External (Card switch switch box, box, etc.: etc.: (Card field supply) supply) field

NOTE: The The wire 2.0m NOTE: wire length length from fromindoor indoorunit unittotothe theRelay Relaymust mustbebewithin within 2.0m

82

Exampleof ofwiring wiring •• Example

Indoor unit Indoor unit control PCB control PCB

m 22 m

NOTE: The The wire 2.0m NOTE: wire length length from fromindoor indoorunit unittotothe theRelay Relaymust mustbebewithin within 2.0m Pulse signal to to JP001) Pulse signal changeable changeabletotostatic staticwith withJPJPcutting. cutting.(Refer (Refer JP001)


FSV Controllers

Interfaces for External Control Serial Interface for 3rd Party (Digital Connection) External Controller MINI Seri-Para I/O Unit (CZ-CAPBC2)

System example

Example of 3rd party BMS connection with CZ-CFUNC2 (For details please consult an authorised dealer) Remote station

CZ-CAPBC2 Functions via communication adaptor [CZ-CFunC2] Central control panel

Communication adaptor

Unit ON/OFF

Mode-change • Control and status monitoring is possible for individual indoor(CZ-CFUNC2) unit (1 group). Room temperature setting • In addition to operation and stop, there is a digital input function for air speed and operation mode. Fan speed setting •A/C Temperature setting and measuring of the indoor suction temperature can be performed from central unit settings Flap setting monitoring. Central control setting • The analog input for temperature setting is 0 to 10 V, or 0 to 140 Ohm. Filter-sign clear • Power is suppliedAlarm from the T10 terminal of the indoor units. reset • Separate power supply also is possible (in case of suction temperature measuring). Unit ON/OFF status Operation mode Setting temperature

Local adaptor for ON/OFF control (CZ-CAPC2) Fan speed status A/C unit status

Flap status

System Up toexample 128 indoor units can be connected

Central control setting Filter-sign situation

CZ-CAPC2 to

Correct/incorrect status

one Communication Adaptor.

Alarm code

Flexible Options • Control and statusDesign monitoring is possible for

ON/Off controller

individual indoor unit (or any external electrical device up to 250 V AC, 10 A) by contact signal.

For example: fan coil unit etc. Total heat exchanger unit.

Remote temperature sensor (CZ-CSRC2)

Seri-Para I /O unit for outdoor unit (CZ-CAPDC2)

Dimensions H 120 x W 70 x D 16 mm

Dimensions Power supply Input

Output Wiring length

H 80 x W 290 x D 260 mm Single phase 100/200 V (50/60 Hz), 18 W Batch operation/Batch stop (non-voltage contact/DC 24 V, pulse signal). Cooling/Heating (non-voltage contact/static signal). Demand 1/2 (non-voltage contact/static signal) (Local stop by switching) Operation output (non-voltage contact). Alarm output (non-voltage contact) Indoor/Outdoor operation lines: Total length 1 km. Digital signal: 100 m or shorter

Central Control Device

· This is a remote sensor which can be used with indoor example units to detect theSystem room temperature when no remote controller sensor or body sensor is used. (Connection to a Seri-para I/O system without a remote controller is possible). · For joint use with a remote control switch, use the remote control switch as main remote controller.

• This unit can control up to 4 outdoor units. • From the centre control device, mode changing and batch operation/batch stop are possible. • Required for demand control.

83


Serial Interface for 3rd Party Interfaces for External External Controller Control (Digital Connection) Example of 3rd party BMS connection with CZ-CfUNC2

Seri-Para /O unit fortooutdoor (CZ-CAPDC2) (for the detail Ipleace consult authorizedunit dealer) RS485/ RS232C Adaptor (field supply)

BMS Manufacturer adaptor (field supply)

(RS-485) (RS-232C)

Dimensions H 80 x W 290 x D 260 mm Power supply Single phase 110-120/220-240 V AC (50/60 Hz), 18 W Input Batch operation/Batch stop (non-voltage contact/DC 24 V, pulse signal). Cooling/ Communication Heating (non-voltage contact/static signal). Demand 1/2 (non-voltage contact/ adaptor static signal) (Local stop by switching) Output Operation output (non-voltage contact). Alarm output (non-voltage contact) Max. 64 I/D Wiring length Indoor/Outdoor operation lines: Total length 1 km. Digital signal: 100 m or shorter unit •Outdoor This unit can control up to 4 Group outdoor controlunits Remote controller •F rom the centre control device, mode changing and batch operation/batch stop are possible • Required for demand control

System example Outdoor unit

Central Control Device

Remote controller Seri-para I/O

Group control

Max. 64 I/D

Outdoor unit

Remote controller

Group control

Seri-Para I/O unit for each indoor unit (CZ-CAPBC2) Max. 16 system Connectable I/D units: Max. 512

functions via communication adaptor [CZ-CfunC2] Unit ON/Off Mode-change Room temperature setting A/C unit settings

fan speed setting flap setting Central control setting filter-sign clear

Outdoor unit

• Control and status Remote monitoring is possible for individual indoor controller unit (1 group) • In addition to operation and stop, there is a digital input function for air speed and operation mode • Temperature setting and measuring of the indoor suction adaptor temperature can be Communication performed from central monitoring • The analog input for temperature setting is 0 to 10 V, or 0 to (CZ-CFUNC2) 140 Ohm • Power is supplied from the T10 terminal of the indoor units. • Separate power supply also is possible (in case of suction temperature measuring)

Alarm reset Unit ON/Off status Operation mode Setting temperature fan speed status A/C unit status

Remote station

flap status Central control setting filter-sign situation Correct/incorrect status Alarm code

84

System example

Up CZ-CAPBC2 Central control panel

to 128 indoor units can be connected to one Communication Adaptor.


FSV Controllers

Serial Interface for LonWorks Network LonWorks Interface (CZ-CLNC2)

Interface adaptor (CZ-CAPC2) • Control and status monitoring is possible for individual indoor unit (or any external electrical device to 250 V AC, 10 A) by for • This interface is aup communications converter contact signal connecting LonWorks to the control network of fSV. • From System examplethe host connected to LonWorks, basic settings and status monitoring is possible for up to 16 groups of A/C units. CZ-CAPC2

System example

For example: fan coil unit etc. Total heat exchanger unit.

ON/OFF controller

LonWorks Interface (CZ-CLNC2) • This interface is a communications converter for connecting LonWorks to the control network of FSV. • From the host connected to LonWorks, basic settings and status monitoring is possible for up to 16 groups of A/C units LonWorks Interface

Indoor/outdoor unit control line

System example

LON

• System Controller

LON

LonWorks communication line

Center Control Device (field supply)

Functions Start/stop A/C unit settings from the LonWorks communicator

Settings for each group of indoor units

Temp. setting unit Indoor/outdoor control mode line Operation Option 1 settings(*) LON Option 2 settings(*)

Settings for all units

Emergency stop • System Controller Start/stop Temp setting

LonWorks Interface

LON

LonWorks communication line

Center Control Device (field supply)

Operation mode

A/C unit status notifications made to the LonWorks communicator

Configuration properties

Option 1 settings(*) Functions Start/stop Temp. setting Operation mode Option 1 settings(*) Option 2 settings(*) Emergency stop Start/stop Transmission intervals settings Temp setting Operation mode Minimum time secured for transmission Option 1 settings(*) A/C unit status notifications made to Option 2 settings(*) the LonWorks communicator Alarm status Indoor units with active alarms Room temp. A/C unit status Transmission intervals settings Configuration properties Minimum time secured for transmission Option 2 settings(*)

A/C unit Alarm status Settings for each settings from group indoor units Indoor units with of active alarms the LonWorks communicator Room temp. Settings for all units A/C unit status

85


fSV Controller External Dimensions Remote Controller External Dimensions TIMER REMOTE CONTROLLER (CZ-RTC2)

WIRELESS REMOTE CONTROLLER

Timer remote controller (CZ-RTC2)

Wireless remote controller (CZ-RWSU2, CZ-RWSC2)

SEPARATE RECEIVER fOR WIRELESS REMOTE CONTROLLER (CZ-RWSC2)

SIMPLIfIED REMOTE CONTROLLER (CZ-RE2C2) Simplified remote REMOTE SENSOR controller (CZ-CSRC2)

17

70

83.5

16.7

(CZ-RE2C2)

120

4.4 x 9.4 slot

16.6

4.4 x 9.4 slot 4.4 x 9.4 slot

13

3

SYSTEM CONTROLLER (CZ-64ESMC2)

INTELLIGENT CONTROLLER (CZ-256ESMC2)

System controller (CZ-64ESMC2)

Backlit remote controller (CZ-RELC2) Remote sensor (CZ-CSRC2)

116

160 148

(6)

21

69

(6)

115

160 148

121

6

6

121

80

79 79

38 38

256

180 180

256

290 270

ø22.2

ø22.2

(mm)

(mm)

86

Intelligent controller (CZ-256ESMC2)

80

38

Communication adaptOr 290 270 (CZ-CFUNC2)

38

COMMUNICATION ADAPTER (CZ-CfUNC2)

9 33.5

4.4 x 9.4 slot

Separate receiver for wireless remote controller (CZ-RWSC2)

R 2.5 R 2.5

8 8

R5

R5


FSV Controllers

ON/Off CONTROLLER

(6)

LONWORKS INTERfACE (CZ-CLNC2)

(6)

14

69

115

160 148

each indoor unit

(CZ-CAPBC2)

116

121

6

SERI-PARA I/O UNIT fOR EACH INDOOR UNIT Seri-Para (CZ-CAPBC2) I/O unit for

160 148

6

(CZ-ANC2) ON/OFF controller (CZ-ANC2)

122

SERI-PARA I /O UNIT fOR OUTDOOR UNIT (CZ-CAPDC2)

LonWorks interface (CZ-CLNC2)

Seri-Para I /O unit for outdoor unit (CZ-CAPDC2)

4 - Ø 5 hole Potbellied hole (4 locations)

3 - Ø 30 hole 4 - Ø 5 hole

Potbellied hole (4 locations)

3 - Ø 30 hole

Magnified view

Detail of the potbellied hole Magnified view Detail of the potbellied hole

87


VRf Renewal for ME1 Series An important drive to further reduce the potential damage to our ozone R22 is a HCfC and classified as an ozone depleting substance banned under the Montreal Protocol. R22 will be phased out in stages. Effective 1 Jan 2010, the use of Virgin (new) R22 refrigerant will be banned within European Community.

Panasonic takes proactive action to switch to R410A refrigerant Recognizing consumers’ anxiety and financial difficulties to adapt to the new R22 regulations, Panasonic developed a new cost-effective and simple solution to switch to R410A refrigerant.

What is Panasonic VRF Renewal? Panasonic VRf Renewal enables reuse of good quality existing R22 pipe work to be installed with new high efficiency R410A system.

What’s so unique about Panasonic’s solution? By enabling reuse of existing R22 piping, consumers gets to save substantially from reduced installation cost and without limitation to other manufacturers equipments. Ozone Depletion Potential R22

HCfCs

0.055

R410A

HfC

0

R407C

HfC

0

Before renewing piping, be sure to contact an authorized Panasonic dealer for advice.

R22 - The reduction of Chlorine critical for a cleaner future

VRF Renewal Panasonic’s Renewal system allows a completely new VRf system, indoor and outdoor units, to be installed using the existing systems pipe work. Panasonic’s advanced technology enables the system to work with previously installed pipe work by managing the working pressure within the system down to R22 (3.3 bar) levels. This ensures the system works safely and efficiently without loss of capacity. The new equipment has potential to increase COP/EER by using state of the art inverter compressor and heat exchanger technology. Having contacted your Panasonic supplier regarding pipe work restrictions and gained approval to use the Panasonic Renewal System there are three main tests that have to be carried out to ensure that the system can be used effectively. firstly a thorough inspection of the pipe work must be carried out and any damage must be repaired. Secondly an oil test has to be carried out to ensure that the system has not been subject to a compressor burnout during its lifetime. Lastly a VRf Renewal Kit (CZ-SLK2) has to be installed within the pipe work to ensure that the system is cleaned of any oil residue. 88


VRF Renewal

VRF Renewal Kit (CZ-SLK2) and Sight Glass The following shows an overview of the VRf Renewal Kit (CZ-SLK2) that is required when existing tubing is reused. If the exact tube length and tube size of the existing tubing are uncertain, attach a sight glass in accordance with the figure below. It will be used for checking the amount of additional refrigerant charge (calculating the amount in Judgment 4 see page 84).

VRF Renewal Kit: CZ-SLK2 filter Drier

Charge Port

Outdoor unit B

Indoor unit side A

A

B

445 (12, 14, 16 HP) 535 (4,5,6,8, 10 HP) Unit: mm

Attaching the Filter Drier Kit and sight glass • To adjust the limited pressure level into 3.3 MPa, special setting is necessary at site. • A filter Drier shall be attached to the liquid tubing of each outdoor unit. • High-Pressure switches shall be attached to both the liquid and the gas tubings of each outdoor unit. • Do not need to remove Filter Drier Kit after a test run is performed as it can be retained for normal operation. • When attaching Filter Drier Kit, be extra careful with regards to installation location and orientation of the filter drier and ball valve. Any mistakes will complicates maintenance work. • Termal insulation material (field supply: heat resistance of 80ºC or higher and thickness of 10 mm or greater) shall be applied to the Filter Drier Kit. • The filter drier of the Filter Drier Kit may need to be replaced depending on the condition of the existing unit. Use a Danfoss DMB 164 as the replacement filter drier (field supply).

Connecting tube dimensions (Inch mm) A Ø 1/2 (12.7) (12,14,16 HP) B Ø 3/8 (9.52) (8,10 HP)

Sight glass (field supply). If the exact tube length and tube size of the existing tubing are uncertain, attach a sight glass to the liquid tubing, and use it to check whether there is an appropriate amount of additional refrigerant charge.

High-Pressure S/W

Note: If the tube size does not match that of the existing tubing, use a reducer (field supply) to adjust the tube diameter.

Gas tubing

Sight glass (field supply) If the exact tube length and tube size of the existing tubing are uncertain, attach a sight glass to the liquid tubing, and use it to check whether there is an appropriate amount of additional refrigerant charge.

Balance tubing

Liquid tubing

VRf Renewal Kit (CZ-SLK2)

89


Procedure for VRF Renewal Judgment 1

Is the existing pipe work reusable?

Judgment 2

Is the pipe work length and the installation height difference of the existing pipe work within the tolerance ranges of the new system?

Judgment 3

Is the existing pipe work within the ranges of reusable tube size?

Judgment 4

Is the additional refrigerant charge at or below the upper limit?

Judgment 5

Renewal flow

Judgments 1 to 4 all ok

Can the existing pipe work be reused?

No

New pipe work needs to be installed.

Yes Can the existing unit perform cooling operation?

Is there any problem with dirt inside the existing pipe work?

No

Recover the refrigerant using a refrigerant recovery device.

Yes Perform cooling operation for at least 15 minutes, and then perform a pump down to recover refrigerant in the existing unit.

Remove the existing indoor and outdoor units

Judgment 5

Is there a problem with dirt inside the existing pipe work? No

Install the new indoor and outdoor units, and attach the VRf Renewal Kit (CZ-SLK2). If the exact length of the pipe work is uncertain, attach a sight glass to aid charging. If the gas pipe size of the main piping is three sizes larger, add oil. (Judgment 3 item)

Perform a pipe work tightness test and refrigeration charge test If the existing pipe length and pipe size are uncertain, charge with the minimum amount of additional refrigerant based on calculation in Judgment 4. Next, determine if the additional refrigerant charged is sufficiently charged and proportionate to the total refrigerant system by checking the system sight glass and system pressures during a cooling test run.

Recheck

Is there any history of compressor failure in the existing unit?

Yes Perform a heating test run. (1) Operate in heating test run mode for 30 minutes. (2) Replace the filter driers of all outdoor units.

No

Recheck

Could the existing unit perform the cooling operation?

No

*Obtain replacement filter driers separately.

Yes

Perform a cooling test run. If the minimum amount of additional refrigerant was added when the exact existing pipe lengths were uncertain, check the condition of flowing refrigerant through the sight glass attached to the liquid piping - add as required. However, the amount of additional refrigerant charge should not exceed the maximum level.

90


VRF renewal

NOTES

91


Panasonic Design Support Software for FSV Panasonic proprietary Design Support Software for fSV gives architects, consultants or end users the advantages to calculate cooling / heating loads and produce information of actual design conditions. This advanced software is designed to be customizable to make any selections and design processes in a quick and easy way. The design software utilises system wizards and import tools to enable both simple and complex systems to be created. In addition, the system will allow outdoor and indoor units to be dragged and dropped on an interactive desktop. This allows users to create everything from realistic floor plans with detailed piping and wiring schematics to send out with quotations, through to installation guidance drawings.

The Panasonic VRf Designer system software can be used for all Panasonic fSV.

92


Design Support Software

features include • Actual capacity calculation • Auto calculation of refrigerant charged amount • Auto piping (inc. joint kit selection) and wiring features • Detailed wiring and piping diagram • Auto CAD (DXF) export

93


NOTES

94


NOTES

95


‘eco ideas’ Declaration Connecting with the earth The Panasonic Group strives to be a Green Innovation Company with a global perspective.

‘eco ideas’ Declaration ‘eco ideas’ for Lifestyles Connecting with the earth The Panasonic We will promote lifestyles with virtually zero CO2 Group strives to be a Green Innovation emissions all throughout the world Company with a global perspective.

‘eco ideas’ for Business-styles We will ideas’ create and pursue a business-style whichmakes ‘eco for Lifestyles the best use of resources and energy We will promote lifestyles with virtually zero CO2 emissions all throughout the world

‘eco ideas’ for Business-styles We will create and pursue a business-style whichmakes the best use of resources and energy

Do not add or replace refrigerant other than the specified type. Manufacturer is not responsible for the damage and deterioration in safety due to usage of other refrigerant.

Do not add or replace refrigerant other than the specified type. Manufacturer is not responsible for the damage and deterioration in safety due to usage of other refrigerant.

panasonic.co.n z

FSV_50Hz_catalog_2012.indd 96

FSV-ASIA-2012

12.2.22 11:44:50 AM

®

FSV_50Hz_catalog_2012.indd 96

96

J007077 05/13

FSV-ASIA-2012

12.2.22 11:44:50 AM