MEH442
Series Concepts Best suited functions for HVAC application Contribution to energy-saving
A broad range of model variations
Easy maintenance
Simple operation
Global products
The HVAC Inverter Series is an inverter exclusively designed for fans and pumps. Developed by Fuji Electric, a leading inverter company, to meet global needs for economy. Features such as the special functions for the HVAC (Heating, Ventilating, and Air-Conditioning) market, space saving, simple operation, a wide variety of models and global compatibility contribute to energy-savings and power-savings for variable torque load equipment. Requirements for total cost reduction in the fan and pump can be easily met with the FRENIC-Eco.
2
Default functions for fans and pumps Line/inverter switching
Switching among remote/panel/independent inverter operation modes
A line frequency starting program for the inverter is installed to support line/inverter switching through an external sequence. As well, two types of line/inverter operation switching sequences are built in: Fuji's standard sequence and automatic line switching sequence at an inverter fault.
Through frequency setting 1 and frequency setting 2, operation/stop command 1 and operation/stop command 2, and local operation (keypad operation), the remote/panel/independent inverter operation modes can be selected for both operation commands and frequency commands.
Full PID control functions
Various frequency setting methods
A "small water flow stopping function" and "deviation alarm/absolute value alarm output" are added to the PID regulator that controls the temperature, pressure, flow rate and so on. Further, an anti-reset wind-up function for the prevention of overshooting in the PID control, PID output limiter and integration hold/reset signals are provided as easy-to-adjust PID control functions.
The best method can be selected for the frequency setting according to the frequency signal to be used. Keypad operation ( and keys), analog input (4 to 20mA, 0 to +5V, 0 to +10V, +1 to +5, normal or inverse operation), 8-step multi-step frequency (step 0 to 7) setting, UP/DOWN operation, communication, etc.
Continued operation upon momentary power failure
Motor pick-up during idling
The inverter automatically restarts upon recovery from momentary power failure. You can choose starting at the frequency at momentary power failure occurrence or starting at 0Hz. Another option can be chosen: Operation continues at a lower frequency while using the kinetic energy obtained from the inertia of the load at momentary power failure.
Energy saving
If the motor runs due to natural convection or other similar situations, you can use the pick-up function to start smoothly.
Sleep function with low limiter A function for stopping the fan or pump at speeds lower than the lower limit is provided to assure the minimum speed. The function can be used also to stop at a low water flow.
Contribution to energy-saving 110
Automatic energy-saving operation function
100
(Energy savings effect varies depending on the motor characteristics.)
90
In addition to the motor loss, the inverter loss is also kept to a minimum with the FRENIC-Eco when applied to fans or pumps. Required power P[%]
80
Capable of electric power monitoring Simplified monitoring of the electric power can be done through the keypad and the communication ports (power consumption, cumulative watt-hour display, watt-hour application display, etc.)
When damper or valve is used
70 60
Energy saved
50 40 30
Cooling fan ON/OFF control function
20
The inverter's cooling fan can be stopped for noise reduction and energy savings whenever the motor is stopped.
Inverter control (V/f control) Inverter control (Automatic energy-saving mode)
10 0
Safety Precautions
Energy savings effect
10
20
30 40 50 60 70 Air or liquid flow rate Q [%]
80
90
100
1. Use the contents of this catalog only for selecting product types and models. When using a product, read the Instruction Manual beforehand to use the product correctly. 2. Products introduced in this catalog have not been designed or manufactured for such applications in a system or equipment that will affect human bodies or lives. Customers, who want to use the products introduced in this catalog for special systems or devices such as for atomic-energy control, aerospace use, medical use, and traffic control, are requested to consult the Fuji's Sales Division. Customers are requested to prepare safety measures when they apply the products introduced in this catalog to such systems or facilities that will affect human lives or cause severe damage to property if the products become faulty.
3
Consideration for surrounding environment Semi-standard series integrated with DC REACTOR (available soon)
Semi-standard series integrated with EMC filter (available soon)
In this series, the Guideline for Suppressing Harmonics can be satisfied by integrating optional DC REACTOR (DCR) for harmonic suppression. (55kW or smaller [planned])
The product can be used to comply with the EMC Directives in EU. (15kW or smaller [planned])
All models are equipped with an inrush current suppression circuit.
Standard installation of input terminals for auxiliary control power of all models
An inrush current suppression circuit is provided as standard in all models, therefore the cost of peripheral devices such as magnetic switches can be reduced.
The terminal is convenient for automatic line/inverter switching operation as the control power of the inverter is standardized.
Easy maintenance and many protective functions The lifetime of the main circuit capacitor can be estimated.
The alarm history for the 4 latest alarms is recorded.
Because the capacitor's life compared with its initial value can be checked, the replacement timing of the main circuit capacitor can be determined.
Detailed information from back as far as the latest 4 alarms can also be checked.
A long-life cooling fan is provided.
Protective function against phase loss in input/output
Use of a long-life cooling fan (design life: 7 years for models smaller than 5.5kW); 4.5 years for models higher than 7.5 and up to 30kW [at ambient temperature: 40ËšC]) reduces replacement work.
Protection against phase loss in input/output circuits is possible upon start-up and operation.
Cumulative running time is recorded and displayed.
Protective function for grounding fault Protection is provided for an overcurrent caused by a grounding fault.
The inverter records and displays the cumulative "motor running time" and "inverter running time" (PC board capacitor running time, cooling fan running time), so that they can be used to defermine machine and inverter maintenance.
It is possible to output lifetime forecast signal to the transistor output.
Protection of motor with PTC thermistor In addition to the protection of the motor with an electronic thermal relay, a PTC thermistor can be used for motor protection.
This signal is output when the main circuit capacitors in the DC bus circuit, the electrolytic capacitors on the PC boards or the cooling fans are nearing the end of their service life.
Simple operation and wiring Standard keypad capable of remote operation
Quick setup function Only the 19 minimum function codes are displayed to set up drives for fan or pump applications.
The optional extension cable allows easy remote operation. Data can be easily copied to the second or more inverters with the code copying function.
Multi-function keypad (option; available soon) A backlit LCD is installed to allow simple set up through interactive data entry. Function codes can be added or deleted to or from the 19 function codes within the quick setup function.
4
Global products All standard models comply with the EC Directive (CE marking), UL standards and Canadian standards (cUL certification). All standard FRENIC-Eco inverters comply with European and North American/Canadian standards, enabling standardization of the specifications for machines and equipment used at home and abroad.
If the model with built-in EMC filter (available soon) is used, the model conforms to the European EMC Directive (15kW or smaller). North America/Canada
Europe / EC Directive (CE marking)
UL standard (cUL certification)
Sink/source switching
Network support (available soon)
The input/output mode (sink/source) of the digital input terminals can be easily switched.
With an optional card, the inverter becomes compatible with various open buses such as DeviceNet, PROFIBUS-DP, LonWorks network, Modbus Plus or CC-Link. A standard RS485 communication port (Modbus RTU) is provided. With an additional RS485 communication card (optional), up to two more ports can be installed.
Space saving Side-by-side mounting is possible. When multiple inverter units are installed inside a panel, the installation space can be minimized. (5.5kW or less, ambient temperature: 40ËšC or less)
260
150
150
150 (Unit : mm) (Ex.: 3-phase 200V 5.5kW)
5
Flexible through optionals Inverter loader software (option; available soon) The inverter loader program (Windows-based, option), which simplifies setting of function codes, and data management, is provided.
RS485 communications (RJ-45 connector) PC
Converter
USB cable
Remote operation is possible. Remote operation can be done easily using the optional extension cable.
Keypad
Extension cable for remote operation
Function code copy function
External cooling attachment
Because the optional multi-function keypad (available soon) is provided with a built-in copy function, similar to that installed in the main body as a standard feature, data can be easily copied to the second inverters without requiring individual setups.
An external cooling attachment (Option for 30kW or smaller ; available soon. Standard for 37kW or larger) cools the inverter outside the panel. It can be easily mounted on the panel.
6
Caution
Variation
Use the contents of this catalog only for selecting product types and models. When using a product, read the Instruction Manual beforehand to use the product correctly.
Standard specifications Applicable motor rating [kW]
Three-phase 200V series
0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 220 280 315 355 400 450 500
FRN0.75F1S-2A FRN1.5F1S-2A FRN2.2F1S-2A FRN3.7F1S-2A FRN5.5F1S-2A FRN7.5F1S-2A FRN11F1S-2A FRN15F1S-2A FRN18.5F1S-2A FRN22F1S-2A FRN30F1S-2A FRN37F1S-2A FRN45F1S-2A FRN55F1S-2A FRN75F1S-2A FRN90F1S-2A FRN110F1S-2A
Three-phase 400V series FRN0.75F1S-4A FRN1.5F1S-4A FRN2.2F1S-4A FRN3.7F1S-4A FRN5.5F1S-4A FRN7.5F1S-4A FRN11F1S-4A FRN15F1S-4A FRN18.5F1S-4A FRN22F1S-4A FRN30F1S-4A FRN37F1S-4A FRN45F1S-4A FRN55F1S-4A FRN75F1S-4A FRN90F1S-4A FRN110F1S-4A FRN132F1S-4A FRN160F1S-4A FRN200F1S-4A FRN220F1S-4A FRN280F1S-4A FRN315F1S-4A FRN355F1S-4A FRN400F1S-4A FRN450F1S-4A FRN500F1S-4A Available soon
How to read the model number
FRN 5.5 F 1 S - 2 A 5 1 1
Code FRN
Series name FRENIC series
Code 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Applicable motor rating [kW] 0.75kW 1.5kW 2.2kW 3.7kW 5.5kW 7.5kW 11.kW 15.kW
450 500
Application range For fans and pumps Multi-function keypad (For variable torque load)
Code 1
Developed inverter series 1
Control terminal block Screw terminal (standard) Rod terminal
Code 1 2
Built-in option None RS485 communication card
Code 1
9
Keypad Keypad (standard) Multi-function keypad (Available soon) No keypad
Code A
Version/Manual Asia/English
Code 2 4
Input power supply 3-phase 200V 3-phase 400V
5
450.kW 500.kW
Code F
Code 1 2
Structure Code Standard type S Type integrated with EMC filter E Type integrated with DC REACTOR H
Note : When the last three digits of the model number is for a keypad (standard), non built-in option, screw terminal (standard), the model number with a standard specification
in the above model number table will apply.
7
Standard specifications Standard specifications Three-phase 200V series Item Type (FRN
Specifications
F1S-2A)
Applicable motor rating *1)
Output ratings
Rated capacity *2)
Input ratings
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
kVA
1.6
2.6
3.8
6.2
8.3
11
16
21
25
30
40
49
59
75
102
121
146
107
130
156
198
270
320
384
Rated voltage *3)
V
Rated current *4)
A
Three-phase, 200V/50Hz, 200, 220, 230, 240V/60Hz (With AVR function) 4.2
7.0
10
16.5
Overload capability
120% of rated current for 1min
Rated frequency
50, 60Hz
Phases, voltage, frequency
22.5
29
42
68
80
Three-phase, 200 to 220V/50Hz Three-phase, 200 to 230V/60Hz
Auxiliary control power input
Single-phase, 200 to 220V/50Hz Single-phase, 200 to 230V/60Hz
Voltage/frequency variations Rated current *5)
Torque *7)
A
Single-phase, 200 to 240V, 50/60Hz Voltage: +10 to -15% (Voltage unbalance: 2% or less (*8)), Frequency: +5 to -5%
(with DCR)
3.2
6.1
8.9
15.0
21.1
28.8
42.2
57.6
71.0
84.4
114
138
167
203
282
334
(without DCR)
5.3
9.5
13.2
22.2
31.5
42.7
60.7
80.1
97.0
112
151
185
225
270
-
-
-
1.2
2.2
3.1
5.3
7.4
10
15
20
25
30
40
48
58
71
116
142
kVA %
DC injection braking
20
98
10 to 15
Starting frequency: 0.0 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 60%
DC REACTOR(DCR)
Option
Applicable safety standards
UL508C, C22.2No.14, EN50178:1997(Applying)
Enclosure(IEC60529)
IP20 UL close type
Cooling method Weight / Mass
55
Main power supply Three-phase, 200 to 240V, 50/60Hz
Required power supply capacity *6)
Braking
0.75 kW
Natural cooling kg
Standard
IP00 UL open type
Fan cooling 3.3
5.6
6.6
*1) Fuji's 4-pole standard motor *2) Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series. *3) Output voltage cannot exceed the power supply voltage. *4) When setting the carrier frequency (F26) to 1 kHz, reduce the load to 80% of its rated value. *5) Calculated under Fuji-specified conditions. *6) Obtained when a DC REACTOR is used. *7) Average braking torque without optional braking resistor (Varies with the efficiency of the motor.) Max. voltage [V] - Min. voltage [V] *8) Voltage unbalance [%] = x 67 (IEC61800-3(5.2.3)) Three-phase average voltage [V] If this value is 2 to 3%, use an AC REACTOR.
8
9.3
9.5
11.7
23
31
34
41
410
Standard specifications Three-phase 400V series (0.75 to 55kW) Item Type (FRN
Specifications
F1S-4A)
Applicable motor rating *1)
Output ratings
Rated capacity *2)
Input ratings
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
kVA
1.9
2.8
4.1
6.8
9.5
12
17
22
28
33
44
54
64
77
44
58
71
84
102
Rated voltage *3)
V
Three-phase, 380, 400V/50Hz, 380, 400, 440, 460V/60Hz (with AVR function)
Rated current *4)
A
2.5
3.7
5.5
9.0
Overload capability
120% of rated current for 1min
Rated frequency
50, 60Hz
Phases, voltage, frequency
12.5
16.5
23
30
37
Main power supply Three-phase, 380 to 480V, 50/60Hz
Three-phase, 380 to 440V/50Hz Three-phase, 380 to 480V/60Hz
Auxiliary control power input
Single-phase, 380 to 440V/50Hz Single-phase, 380 to 480V/60Hz
Voltage/frequency variations Rated current *5)
A
Single-phase, 380 to 480V, 50/60Hz Voltage: +10 to -15% (Voltage unbalance: 2% or less (*8)), Frequency: +5 to -5%
(with DCR)
1.6
3.0
4.5
7.5
10.6
14.4
21.1
28.8
35.5
42.2
57.0
68.5
83.2
102
(without DCR)
3.1
5.9
8.2
13.0
17.3
23.2
33.0
43.8
52.3
60.6
77.9
94.3
114
140
1.2
2.2
3.1
5.3
7.4
10
15
20
25
30
40
48
58
71
Required power supply capacity *6)
Braking
0.75 kW
Torque *7)
kVA %
DC injection braking
20
10 to 15
Starting frequency: 0.0 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 60%
DC REACTOR(DCR)
Option
Applicable safety standards
UL508C, C22.2No.14, EN50178:1997(Applying)
Enclosure (IEC60529)
IP20 UL close type
Cooling method
Natural cooling
Weight / Mass
IP00 UL open type Fan cooling
kg
3.3
5.6
5.7
6.6
9.2
10.3
11.7
23
23
30
Three-phase 400V series (75 to 500kW) Item Type (FRN
Specifications
F1S-4A)
Applicable motor rating *1)
Output ratings
Rated capacity *2)
Input ratings
90
110
132
160
200
220
280
315
355
400
450
500
75
90
110
132
160
200
220
280
315
355
400
450
500
kVA
105
128
154
182
221
274
316
396
445
495
584
640
731
585
650
740
840
960
881
Rated voltage *3)
V
Three-phase, 380, 400V/50Hz, 380, 400, 440, 460V/60Hz (with AVR function)
Rated current *4)
A
139
168
203
Overload capability
120% of rated current for 1min
Rated frequency
50, 60Hz
Phases, voltage, frequency
240
Main power supply
Three-phase, 380 to 440V, 50Hz Three-phase, 380 to 480V, 60Hz
Auxiliary control power input
Single -phase, 380 to 480V, 50/60Hz
Voltage/frequency variations Rated current *5)
A
Torque *7)
290
415
520
Voltage: +10 to -15% (Voltage unbalance: 2% or less (*8)), Frequency: +5 to -5% 138
164
201
238
286
357
390
500
559
628
705
789
(without DCR)
-
-
-
-
-
-
-
-
-
-
-
-
-
114
140
165
199
248
271
347
388
435
489
547
611
kVA
96
%
DC injection braking
10 to 15 Starting frequency: 0.0 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 60%
DC REACTOR(DCR)
Standard
Applicable safety standards
UL508C, C22.2No.14, EN50178:1997(Applying)
Enclosure (IEC60529)
IP00 UL open type
Cooling method Weight / Mass
360
(with DCR)
Required power supply capacity *6)
Braking
75 kW
Fan cooling kg
35
*1) Fuji's 4-pole standard motor *2) Rated capacity is calculated by assuming the output rated voltage as 440V for three-phase 400V series. *3) Output voltage cannot exceed the power supply voltage. *4) When setting the carrier frequency (F26) to 1 kHz, reduce the load to 80% of its rated value. *5) Calculated under Fuji-specified conditions. *6) Obtained when a DC REACTOR is used. *7) Average braking torque without optional braking resistor (Varies with the efficiency of the motor.) Max. voltage [V] - Min. voltage [V] *8) Voltage unbalance [%] = x 67 (IEC61800-3(5.2.3)) Three-phase average voltage [V] If this value is 2 to 3%, use an AC REACTOR.
9
Common specifications Common specifications Maximum frequency
25 to 120Hz
Related function code F03
Base frequency
25 to 120Hz
F04
Starting frequency
0.1 to 60.0Hz • 0.75 to 15kHz (200V/400V:0.75 to 22kW) • 0.75 to 10kHz (200V/400V:30 to 75kW) • 0.75 to 6kHz (200V/400V:90 to 500kW)
Setting range
Output frequency
Item
Carrier frequency
Explanation
Remarks
F23 The carrier frequency may drop automatically according to the F26 ambient temperature or output current to protect the inverter. F27 H98 This protective operation can be canceled by function code H98.
Accuracy (Stability)
• Analog setting: ±0.2% of maximum frequency (at 25±10˚C) • Keypad setting: ±0.01% of maximum frequency (at -10 to +50˚C)
Setting resolution
• Analog setting: 1/1000 of maximum frequency (ex. 0.06Hz at 60Hz, 0.12Hz at 120Hz) • Keypad setting: 0.01Hz (99.99Hz or less), 0.1Hz (100.0Hz or more) • Link setting: Selectable from 2 types• 1/20000 of maximum frequency (ex. 0.003Hz at 60Hz, 0.006Hz at 120Hz) • 0.01Hz (fixed)
Control method
V/f control
Voltage/freq. characteristic
Possible to set output voltage at base frequency and at maximum output frequency (common spec.). AVR control can be turned ON or OFF.
(Non-linear V/f setting) 1 point (Arbitrary voltage and frequency can be set.) Torque boost
Torque boost can be set with the function code F09.
Setting with
,
keys.
Three-phase 200V: 80 to 240V Three-phase 400V: 160 to 500V
F03 to F05
Three-phase 200V: 0 to 240V/0 to 120Hz Three-phase 400V: 0 to 500V/0 to 120Hz
H50, H51
Set when 0, 1, 3, or 4 is selected at F37.
F09, F37
(Load selection) Select application load type with the function code F37. 0: Variable torque load 1: Variable torque load (for high starting torque) 2: Auto-torque boost 3: Auto-energy-saving operation (variable torque load in acceleration/deceleration) 4: Auto-energy-saving operation (variable torque load (for high starting torque) for acceleration/deceleration) 5: Auto-energy-saving operation (auto-torque boost in acceleration/deceleration) Starting torque
50% or over
Start/stop
Keypad Start (FWD/REV) and stop with operation Start and stop with
/
, ,
keys keys
F09, F37
Keypad (standard)
F02
Multi-function keypad (optional)
F02
External signals (7 digital inputs): Forward (reverse) rotation, stop command (capable of 3-wire operation), second operation command, coast-to-stop command, external alarm, alarm reset, etc.
E01 to E05 E98, E99
Link operation: Operation through RS485 communication and Field Bus communication (option)
H30, y98
Operation command switch: Remote/local switch, link switch, second operation command switch Frequency setting
Keypad operation: Can be set with
,
F01, C30
keys.
External potentiometer: Can be set with the external resistor (1 to 5kΩ, 1/2W)
Connected to analog input terminals 13, 12, 11. A separate variable resistor is necessary.
Analog input
0 to +5V DC:change (200%) in analog F18, C50, C32 to input gain setting. +1 to +5V DC:adjustable C34, C37 to C39, with bias/analog input gain C42 to C44
Can be set with external voltage/current input. 0 to +10V DC (0 to +5V DC)/0 to 100% (terminal 12, V2) 4 to 20mA DC/0 to 100% (terminal C1)
C05 to C11 F01, C30
Link operation: Can be set with RS485 communications and field bus communications (option).
H30, y98
Frequency setting change: Two types of frequency settings can be switched with an external signal (digital input). Changeover between remote and local (keypad operation) or frequency setup through communication is also possible.
F01, C30
Auxiliary frequency setting: Inputs at terminal 12, C1 or V2 can be added to the main setting as auxiliary frequency settings.
E61 to E63
Reverse action: The digital input signal and function code setting sets or switches between the forward and reverse actions. • +10 to 0V DC/0 to 100%(Terminal 12, V2) • 20 to 4mA DC/0 to 100%(Terminal C1)
C53
Acceleration / deceleration time
0 to 3600s • Acceleration and deceleration pattern can be selected from 4 types: Linear, S-curve (weak), S-curve (strong), Curve (constant output max. capacity). • Shutoff of the operation command coasts the motor to decelerate and stop.
F07, F08 H07 H11
Frequency limiter
High and low limiters can be set (setting range: 0 to 120Hz)
Bias frequency
Bias of set frequency and PID command can be set in the range between 0 and ±100%.
Gain for frequency setting
The analog input gain can be set in the range from 0 to 200%.
Jump frequency setting
3 operation points and their common jump hysteresis width (0 to 30Hz) can be set.
C01 to C04
Restart after momentary power failure
• The inverter restarts upon recovery from power failure without stopping the motor. • In the "operation continuation mode," recovery of the power supply is waited for while the output frequency slightly drops. • Selection can be made among starting at 0Hz, starting at the frequency immediately before the momentary power failure, and starting at a set frequency for the starting method after power recovery.
F14
Current limit
Keeps the current under the preset value during operation.
F43, F44
Line/inverter switching
• Line/inverter switching (starting at line frequency) can be made with a digital input signal (SW50, SW60). • A built-in line/inverter switching sequence performs sequence control with a digital input signal (ISW50, ISW60) to output a signal (SW88, SW52-1, SW52-2) for controlling an external magnetic contactor (MC). As a built-in sequence, two types can be selected, including the one switching automatically to the line upon an inverter alarm.
J22
PID control
Capable of PID regulator control for process
E61 to E63 J01 to J06 J10 to 0J19
Control
Multistep frequency: Selectable from 8 steps (step 0 to 7) UP/DOWN operation: The frequency rises or lowers while the digital input signal is turned on.
Selection can be made between continuation of operation and stopping at frequencies equal to or smaller than the lower limit.
Process commands • Key operation (UP and DOWN keys):0 to 100% • Analog input (terminal 12, V2):0 to +10V DC/0 to 100% • Analog input (terminal C1):4 to 20mA DC/0 to 100% • UP/DOWN (digital input):0 to 100% • Communication (RS485, bus option):0 to 20,000/0 to 100
10
F15, F16 H63 F18, C50 to C52
Voltage signals (terminal 12, V2) and current signal (terminal C1) can be set independently.
C32, C34, C37 C39, C42, C44
H13 to H16, H92, H93
Common specifications Item PID control
Explanation
Remarks
Related function code
E61 to E6 J01 to J06 J10 to J19
Feedback value • Analog input (terminal 12, V2):0 to +10V DC/0 to 100% • Analog input (terminal C1):4 to 20mA DC/0 to 100%
Indication
Operation begins at a preset pick-up frequency to search for the motor speed to start an idling motor without stopping it.
H09, H17
Automatic deceleration
Upon a DC link voltage exceeding the overvoltage limit level during deceleration, the deceleration time automatically extends to avoid an OV trip.
H69
Deceleration characteristic
The motor loss increases during deceleration to reduce the load energy regenerating at the inverter to avoid an OV trip upon mode selection.
H71
Automatic energy-saving operation
The output voltage is controlled to minimize the total sum of the motor loss and inverter loss at a constant speed.
F37
Active drive
The output frequency is automatically reduced to suppress the overload protection trip of the inverter caused by an increase in the ambient temperature, operation frequency, motor load or the like.
H70
Auto-tuning
The motor parameters are automatically tuned.
Cooling fan ON/OFF control
Detects inverter internal temperature and stops cooling fan when the temperature is low.
Running/stopping
• Speed monitor, output current [A], output voltage [V], torque calculation value, input power [kW], PID reference value, PID feedback value, PID output, load factor, motor output • Select the speed monitor to be displayed from the following. Output frequency [Hz], motor speed [r/min.], load shaft speed [r/min.], % indication
P04
Life early warning
The life early warning of the main circuit capacitors, capacitors on the PC boards and the cooling fan can be displayed.
Cumulative run hours
The cumulative motor running hours, cumulative inverter running hours and cumulative watt-hours can be displayed.
Trip mode
Displays the cause of trip by codes. • (Overcurrent during acceleration) • (Overcurrent during deceleration) • • (Grounding fault) • (Input phase loss) • • (Output phase loss) • (Overvoltage during acceleration) • • (Overvoltage at constant speed) • (Overheating of the heat sink) • • (Inverter overheat) • (Motor protection (PTC thermistor)) • • (Inverter overload) • (Blown fuse) • • (Memory error) • (Keypad communication error) • • (Optional communication error) • (Option error) • • (Tuning error) • (RS485 communication error) • • (RS485 communication error (option))
An external output is issued in a transistor output signal.
H06 E43 E48
An external output is issued in a transistor output signal.
(Overcurrent at constant speed) (Undervoltage) (Overvoltage during deceleration) (External alarm) (Motor overload) (Charging circuit fault) (CPU error) (Incorrect operation error) (Data save error due to undervoltage)
Running or trip mode
Trip history: Saves and displays the last 4 trip codes and their detailed description.
Overcurrent protection
The inverter is stopped upon an overcurrent caused by an overload.
Short circuit protection
The inverter is stopped upon an overcurrent caused by a short circuit in the output circuit.
Grounding fault protection
The inverter is stopped upon an overcurrent caused by a grounding fault in the output circuit.
Overvoltage protection
An excessive DC link circuit voltage is detected to stop the inverter.
Surge protection
The inverter is protected against surge voltages intruding across the main circuit power cable and ground.
Undervoltage
Stops the inverter by detecting voltage drop in DC link circuit.
3-phase 200V / 200VDC 3-phase 400V / 400VDC
F14
Input phase loss
Stops or protects the inverter against input phase loss.
The protective function can be canceled with function code 99.
H98
Output phase loss
Detects breaks in inverter output wiring at the start of running and during running, stopping the inverter output.
The protective function can be canceled with function code 99.
H98
Overheating
The temperature of the heat sink of the inverter or that inside the inverter unit is detected to stop the inverter, upon a failure or overload of the cooling fan.
Overload
The inverter is stopped upon the temperature of the heat sink of the inverter or the temperature of the switching element calculated from the output current. Thermal time constant can be adjusted (0.5 to 75.0min.).
F10 to F12, P99
Motor protection
Protection Environment
Pick-up
3-phase 200V / 400VDC 3-phase400V / 800VDC
Electronic thermal
The inverter is stopped upon an electronic thermal function setting to protect the motor.
PTC thermistor
A PTC thermistor input stops the inverter to protect the motor.
H26, H27
Overload early warning
Warning signal can be output based on the set level before the inverter trips.
F10, F12, E34, E35, P99
Stall prevention
The output frequency decreases upon an output current exceeding the limit during acceleration or constant speed operation, to avoid overcurrent trip.
Momentary power failure protection
• A protective function (inverter stoppage) is activated upon a momentary power failure for 15msec or longer. • If restart upon momentary power failure is selected, the inverter restarts upon recovery of the voltage within the set time.
Retry function
When the motor is tripped and stopped, this function automatically resets the tripping state and restarts operation.
Command loss detection
A loss (broken wire, etc.) of the frequency command is detected to output an alarm and continue operation at the preset frequency (set at a ratio to the frequency before detection).
Installation location
Shall be free from corrosive gases, flammable gases, oil mist, dusts, and direct sunlight. (Pollution degree 2 (IEC60664-1)). Indoor use only.
Ambient temperature
-10 to +50˚C
Ambient humidity
5 to 95% (no condensation)
Altitude
Altitude [m] Lower than 1,000 1,001 to 2,000 2,001 to 3,000
F14 Waiting time before resetting and the number of retry times can be set.
* If the altitude exceeds 2,000m, insulate the interface circuit from the main power supply to conform to the Low Voltage Directives.
Output derating None Decreases Decreases*
Amb. temp. Amb. humidity
5 to 95%RH (no condensation)
[90kW or more] 3mm (vibration width) : 2 to less than 9Hz 2m/s2 : 9 to less than 55Hz 1m/s2 :55 to less than 200Hz
11
H04, H05 E65
-10 to 40˚C when inverters are installed side by side without clearance.
[Smaller than 75kW] 3mm (vibration width) : 2 to less than 9Hz, 9.8m/s2 : 9 to less than 20Hz 2m/s2 :20 to less than 55Hz 1m/s2 :55 to less than 200Hz -25 to +65˚C
Vibration
Storage
Control
Accessory functions • Alarm output (absolute value alarm, deviation alarm) • Normal operation/inverse operation • Small water flow stoppage function • Anti-reset wind-up function • PID output limiter • Integration reset/hold
External Dimensions Main body of inverter (5.5kW) 150 7
101.5
7
136
61.5 5
6
260
246
7
2
Unit : mm
163
Power supply voltage
Type
7
Three-phase 200V FRN5.5F1S-2A Three-phase 400V FRN5.5F1S-4A 6 30
30
23.5
45
3
27
81.4
(Height of grounding terminal)
98.9
PULL
Main body of inverter (7.5 to 30kW) W1
12
D1
D2
10
11.2
11
10 A W3
W4
2
B
(Height of separate power terminal block)
PULL
H4
H3
W2
H2
H
H1
11
2
Unit : mm
D
W 12
Power supply voltage
Type
W
FRN7.5F1S-2A FRN11F1S-2A Three-phase FRN15F1S-2A 200V FRN18.5F1S-2A FRN22F1S-2A FRN30F1S-2A FRN7.5F1S-4A FRN11F1S-4A Three-phase FRN15F1S-4A 400V FRN18.5F1S-4A FRN22F1S-4A FRN30F1S-4A
W1
W2
W3
W4
H
Dimensions (mm) H1 H2 H3 H4
220 196 63.5 46.5 46.5 260 238 141.7 16 172.9 136.7 21 250 226
67
58
58
-
-
-
400 378
166.2
2
12
67
58
58
-
-
-
D2
A
B
118.5 96.5
27
34
34
42
85
130
186.2
-
400 378 166.2 -
D1
215
175.2
220 196 63.5 46.5 46.5 260 238 141.7 16 172.9 136.7 21 250 226
D
2
175.2
-
186.2
118.5 96.5 215 85
130
-
-
27
34
34
42
-
-
Main body of inverter (37 to 75kW) 2
W
10
Unit : mm
D
4.5
W1
D2
H
H1
12
D1
10
W3 (8)
W2
Type
FRN37F1S-2A Three-phase FRN45F1S-2A 200V FRN55F1S-2A FRN75F1S-2A FRN37F1S-4A Three-phase FRN45F1S-4A 400V FRN55F1S-4A FRN75F1S-4A
H3
H2
Power supply voltage
Dimensions (mm) W W1 W2 W3 H H1 H2 H3 D 320 240 304 310.2 550 530 192 220.5 255 355 275 339 345.2
615 595
201.5 230.5 270
D1 115
D2 140 155
740 720 320 240 304 310.2 355 275 339 345.2
192 220.5 255
550 530 615 595
140 115
209.5 238 270
155
8
* The above dimensions are planned ones; they are subject to change.
Keypad
(13.775)
9.5 2 M3
8.17
65
Back side view
Inside panel
4.5
23
1
(80) 58
(10.5)
Panel surface
45
(65)
11.4
2
8.1 (16.98)
Panel cutout
4
11.68 (53.8)
15.24 61
13
(9.5)
45
61
(14.615)
18.2
15.08
80
10.5
Unit : mm
Wiring Diagram Basic wiring diagram The following diagram is for reference only. For detailed wiring diagrams, refer to the Instruction Manual.
Keypad operation Run/Stop operation and frequency setting on the keypad
DC REACTOR DCR (Note1)
[Wiring procedure] (1) Wire the inverter main power circuit.
P1
Power supply Three-phase 200 to 240V 50/60Hz or three-phase 380 to 480V 50/60Hz
(Note2) MCCB or ELCB
(Note3) MC
P1
P(+)
Main circuit
N(-)
L1/R
U
Motor
L2/S
V
M
L3/T
W
R0 (Note4)
T0 G
G
Grounding terminal
Analog input
[13] [12] [11]
SINK
[V2]
SOURCE
30C 30B 30 30A
Grounding terminal Control circuit Alarm relay output (for any fault)
Y5C Y5A
Relay output
[C1] [11] [FMA]
[FMP]
(X1) (X2) (X3) (X4) (X5) (CM) (PLC)
<Y1> <Y2> <Y3> <CMY>
Transistor output
Digital input
(FWD) (REV) (CM)
[Operation method] (1) Run/Stop : Press or key on the keypad. (2) Setting frequency : Set the frequency with or key. Note1: When connecting a DC REACTOR (DCR option), remove the jumper bar from across the terminals [P1] and [P (+)]. The DCR is a standard accessory for 75kW or larger capacity inverters. It must be connected when provided. Note2: Install a recommended molded-case circuit-breaker (MCCB) or an earthleakage circuit-breaker (ELCB) (with an overcurrent protection function) in the primary circuit of the inverter to protect wiring. At this time, ensure that the circuit breaker capacity is equivalent to or lower than the recommended capacity. Note3: Install a magnetic contactor (MC) for each inverter to separate the inverter form the power supply, apart from the MCCB or ELCB, when necessary. Connect a surge suppressor in parallel when installing a coil such as the MC or solenoid near the inverter. Note4: Connect the control circuit with the main circuit power supply to bring the inverter in a waiting state. If this terminal is not connected, the inverter can still be operated with the application of main power.
Operation by external signal inputs Run/Stop operation and frequency setting through external signals [Wiring procedure] (1) Wire both the inverter main power circuit and control circuit. (2) Set (external signal) at function code . Next, set (voltage input (terminal 12) (0 to +10VDC)), (current input (terminal C1) (+4 to 20mADC)), or other value at function code .
DC REACTOR DCR (Note1) P1 (Note2) MCCB or ELCB
Power supply Three-phase 200 to 240V 50/60Hz or three-phase 380 to 480V 50/60Hz
(Note3) MC
P1
P(+)
Main circuit
N(-)
L1/R
U
Motor
L2/S
V
M
L3/T
W
R0 (Note4)
T0 G
G
3 2
[13]
1
[12] [11]
SINK
(+) (-)
[V2]
SOURCE
Current input for (+) setting 4 to 20mAdc (-)
[C1] [11]
Voltage input for setting 0 to 10Vdc Voltage input for setting 0 to 10Vdc
30C 30B 30 30A
Grounding terminal Control circuit Alarm relay output (for any fault)
Y5C Y5A
Relay output
[FMA]
Analog meter
[FMP]
Digital frequency meter
Digital input
(FWD) (REV) (CM)
(Note6)
(X1) (X2) (X3) (X4) (X5) (CM) (PLC)
<Y1> <Y2> <Y3> <CMY>
Transistor output
Analog input
(Note5) Power supply for variable resistor
Grounding terminal
[Operation method] (1) Run/Stop : Operate the inverter across terminals FDW and CM shortcircuited, and stop with open terminals. (2) Frequency setting : Voltage input (0 to +10VDC), current input (+4 to 20mADC) Note1: When connecting a DC REACTOR (DCR option), remove the jumper bar from across the terminals [P1] and [P (+)]. The DCR is a standard accessory for 75kW or larger capacity inverters. It must be connected when provided. Note2: Install a recommended molded-case circuit-breaker (MCCB) or an earthleakage circuit-breaker (ELCB) (with an overcurrent protection function) in the primary circuit of the inverter to protect wiring. At this time, ensure that the circuit breaker capacity is equivalent to or lower than the recommended capacity. Note3: Install a magnetic contactor (MC) for each inverter to separate the inverter form the power supply, apart from the MCCB or ELCB, when necessary. Connect a surge suppressor in parallel when installing a coil such as the MC or solenoid near the inverter. Note4: Connect the control circuit with the main circuit power supply to bring the inverter in a waiting state. If this terminal is not connected, the inverter can still be operated with the application of main power. Note5: Frequency can be set by connecting a frequency setting device (external potentiometer) between the terminals 11, 12 and 13 instead of inputting a voltage signal (0 to +10V DC, 0 to +5V DC or +1 to +5V DC) between the terminals 12 and 11. Note6: For the control signal wires, use shielded or twisted wires. Ground shielded wires. To prevent malfunction due to noise, keep the control circuit wiring away from the main circuit wiring as far as possible (recommended: 10cm or more). Never install them in the same wire duct. When crossing the control circuit wiring with the main circuit wiring, set them at right angles.
14
Terminal Functions
Frequency setting
Main circuit
Division
Terminal Functions Symbol
Terminal name
Functions
L1/R,L2/S,L3/T R0,T0 U,V,W P(+),P1 P(+),N(-) G 13 12
Power input Auxiliary control power input Inverter output For DC REACTOR For DC bus connection Grounding Potentiometer power supply Voltage input
C1
(Inverse operation) (PID control) (Frequency aux. setting) (Analog input monitor) Current input
V2
(Inverse operation) (PID control) (Frequency aux. setting) (Analog input monitor) Analog setting voltage input
11
(Inverse operation) (PID control) (For PTC thermistor) (Frequency aux. setting) (Analog input monitor) Analog common
Connect a three-phase power supply. Connect a single-phase power supply. Connect a three-phase motor. Connect the DC reactor (DCR). Used for DC bus connection. Terminal for inverter grounding Used for frequency setting device power supply (variable resistance: 1 to 5kΩ) (10Vdc 10mAdc max.) Used as a frequency setting voltage input. 0 to +10V DC/0 to 100% (0 to +5V DC/0 to 100%) +10 to 0V DC/0 to 100% Used for setting signal (PID process command value) or feedback signal. Used as additional auxiliary setting to various frequency settings. The peripheral analog signal can be displayed on the keypad. (Displaying coefficient: valid) Used as a frequency setting current input. 4 to 20mA DC/0 to 100% 20 to 4mA DC/0 to 100% Used for setting signal (PID process command value) or feedback signal. Used as additional auxiliary setting to various frequency settings. The peripheral analog signal can be displayed on the keypad. (Displaying coefficient: valid) Used as a frequency setting voltage input. 0 to +10V DC/0 to 100% (0 to +5V DC/0 to 100%) +10 to 0V DC/0 to 100% Used for setting signal (PID process command value) or feedback signal. Connects PTC thermistor for motor protection. Used as additional auxiliary setting to various frequency settings. The peripheral analog signal can be displayed on the keypad. (Displaying coefficient: valid) Common terminal for frequency setting signals (12, 13, C1, V2, FMA)
X1 X2 X3 X4 X5 FWD REV (FWD) (REV) (SS1) (SS2) (SS4)
Digital input
Two terminals are provided. Input impedance:22kΩ Maximum input:+15V DC
F18 C32 to C34 E61
Input impedance:250Ω Maximum input:30mA DC
F18 C37 to C39 E62
Input impedance:22kΩ Maximum input:+15V DC
F18 C42 to C44 E63
Isolated from terminals CM and CMY. Two terminals are provided. Digital input 1 The following functions can be set at terminals X1 to X5, FWD and REV for ON state signal input. Source current:2.5 to 5mA Digital input 2 <Common function> Voltage level:2V Digital input 3 • Sink and source are changeable using the built-in sliding switch. OFF state Digital input 4 • ON timing can be changed between short-circuit of terminals X1 and CM and Allowable leakage current: Digital input 5 open circuits of them. The same setting is possible between CM and any of the Smaller than 0.5mA Forward operation command terminals among X2, X3, X4, X5, FWD, and REV. Voltage:22 to 27V Reverse operation command Forward operation command The motor runs in the forward direction upon ON across (FWD) and CM.The motor decelerates and stops upon OFF. This function can be set only for the Reverse operation command The motor runs in the reverse direction upon ON across (REV) and CM.The motor decelerates and stops upon OFF. terminals FWD and REV. 8-step operation can be conducted with ON/OFF signals at (SS1) to (SS4). Multistep freq. Multistep frequency selection 0 1 2 3 4 5 6 7
E01 E02 E03 E04 E05 E98 E99
C05 to C11
Digital input
(HLD) 3-wire operation stop command (BX) (RST) (THR) (Hz2/Hz1) (DCBRK) (SW50) (SW60) (UP) (DOWN) (WE-KP) (Hz/PID)
Related function code
Remarks
Coast-to-stop command Alarm reset Trip command (External fault) Freq. set 2/Freq. set 1 DC braking command Line/inverter switch(50Hz) Line/inverter switch(60Hz) UP command DOWN command Write enable for KEYPAD PID cancel
(IVS) Inverse mode changeover (IL) Interlock (LE) Link enable (RS485, Bus) (U-DI) Universal DI (STM) Starting characteristic selection (STOP) Forcible stop (PID-RST) PID differentiation / integration reset (PID-HLD) PID integral hold (LOC) Local (keypad) command selection (RE) Operation permission (DWP) Dew prevention (ISW50) Line/inverter switching sequence(50Hz) (ISW60) Line/inverter switching sequence(60Hz) (FR2/FR1) Operation command 2/1 (FWD2) Forward rotation/stop command 2 (REV2) Reverse operation/stop command 2 PLC PLC terminal CM Common
Used for 3-wire operation. ON across (HLD) and CM: The inverter self-holds FWD or REV signal. OFF across (HLD) and CM: The inverter releases self-holding. ON across (BX) and CM: The inverter output is shut off immediately and the motor coasts to a stop. ON across (RST) and CM: Faults are reset. OFF across (THR) and CM: The inverter output is shut off immediately and the motor coasts-to-stop. ON across (Hz2/Hz1)and CM: Freq. set 2 is effective. ON across (DCBRK) and CM: Starts DC braking action. OFF across (SW50) and CM: Starts at 50Hz. OFF across (SW60) and CM: Starts at 60Hz The output frequency rises while the circuit across (UP) and CM is connected. The output frequency drops while the circuit across (DOWN) and CM is connected. The function code data can be changed from the keypad only when (WEE-KP) is ON. PID control can be canceled when the circuit across (Hz/PID) and CM is connected. (Operation proceeds according to the selected frequency setting method such as the multi-step frequency, keypad and analog input.) The frequency setting or PID control output signal (frequency setting) action mode switches between normal and inverse actions when the circuit across (IVS) and CM is connected. Connect an auxiliary contact of a switch installed between the inverter and motor. This signal is input upon momentary power failure to detect momentary power failure, and the inverter restarts upon power recovery. Operation proceeds according to commands sent via RS485 communication or field bus (option) when the circuit across (LE) and CM is connected. An arbitrary digital input signal is transmitted to the host controller. ON across (STM) and CM: Starting at the pick-up frequency becomes valid. ON across (STOP) and CM: The inverter is forcibly stopped in the special deceleration time. ON across (PID-RST) and CM: Resets differentiation and integration values of PID. ON across (PID-HLD) and CM: Holds integration values of PID. ON across (LOC) and CM: The operation commands and frequency settings given at the keypad become valid. After an operation command is input, operation starts upon activation of (RE). ON across (DWP) and CM: A current flows through the motor to avoid motor temperature drop during inverter stoppage so that condensation will not occur. OFF across (ISW50) and CM: Line operation starts according to the switching sequence built in the inverter. (For 50Hz commercial line) OFF across (ISW60) and CM: Line operation starts according to the switching sequence built in the inverter. (For 60Hz commercial line) ON across (FR2/FR1) and CM: The operation command switches to (FWD2) (REV2) side. Forward operation upon ON across (FWD) and CM. Deceleration and stop upon OFF. (Second operation command) Reverse operation upon ON across (REV) and CM. Deceleration and stop upon OFF. (Second operation command) Connect to PLC output signal power supply. Common for 24V power. Common terminal for digital input signal
15
(SS1)
-
ON
(SS2)
-
-
(SS4)
-
-
-
ON
-
ON
ON ON
-
-
-
-
-
ON
ON ON
ON ON ON ON
No alarm signal will be output. Alarm reset signal width: 0.1(s) or more Alarm signal will be output. F01, F30 F20 to F22
F01, C30 J02 F00 J01 to J06 J10 to J19 C50, J01 F14 H30, y98
H17, H09 H56 J01 to J06 J10 to J19
J21 F21, F22 J22 J22 F02
+24V 50mA max. Isolated from terminals 11 and CMY.Two terminals are provided.
Terminal Functions
Pulse output Analog output Division
Terminal Functions Symbol
Terminal name
Functions
Remarks
Related function code
FMA
Analog monitor
The output style can be selected between DC voltage (0 to 10V) and DC current (4 to 20mA). One of the following items can be output in the selected output style. • Output frequency. • Output current. • Output voltage. • Output torque. • Load factor. • Input power. • PID feedback value. • DC link circuit voltage. • Universal AO. • Motor output. • Analog output test. • PID command. • PID output
In the case of voltage output, up to two analog voltmeters F29 to F31 (0 to 10Vdc, input impedance: 10kΩ) can be connected. In the case of current output, analog ammeters (up to 500Ω) can be connected. Gain adjustment range: 0 to 200%
FMP
Pulse monitor
One of the following items can be output in a pulse frequency. • Output frequency. • Output current. • Output voltage. • Output torque. • Load factor. • Power consumption. • PID feedback value. • DC link circuit voltage. • Universal AO. • Motor output. • Analog output test. • PID command. • PID output
Up to two analog voltmeters (0 to 10Vdc, input impedance: 10kΩ) can be connected. (Driven at average voltage) Gain adjustment range: 0 to 200%
(PLC)
Transistor output power
• Power supply for a transistor output load.(24Vdc 50mAdc Max.)(Note: Same terminal as digital input PLC terminal)
Short circuit across terminals CM and CMY to use.
Y1
Transistor output 1
Y2
Transistor output 2
Y3
Transistor output 3
The following functions can be set at terminals Y1 to Y3 for signal output. Max. voltage: 27Vdc, max. current: • The setting of "short circuit upon active signal output" or "open upon active signal output" is possible. 50mA, leak current: 0.1mA max., ON • Sink/source support (switching unnecessary) voltage: within 2V (at 50mA)
F33 to F35
E20 E21 E22
(RUN) Inverter running (speed exists) An active signal is issued when the inverter runs at higher than the starting frequency. (RUN2) Inverter output on
A signal is issued when the inverter runs at smaller than the starting frequency or when DC braking is in action.
(FAR) Speed/freq. arrival
An active signal is issued when the output frequency reaches the set frequency.
(FDT) Speed/freq. detection
An active signal is issued at output frequencies above a preset detection level. Hysteresis width (fixed): 1.0 (Hz) The signal is deactivated if the output frequency falls below the detection level.
Detection width (fixed): 2.5 (Hz) E31
(LV) Undervoltage detection The signal is output when the inverter stops because of undervoltage. (IOL) Inverter output limit (limit on current) The signal is output when the inverter is limiting the current.
F43, F44
(IPF) Auto-restarting
F14
The signal is output during auto restart operation (after momentary power failure and until completion of restart).
Transistor output
(OL) Overload early warning (motor) The signal is output when the electronic thermal relay value is higher than the preset alarm level.
F10 to F12
(RDY) Operation ready output A signal is issued if preparation for inverter operation is completed. (SW88) Line-to-inverter switching
The magnetic contactor on the line side of line-to-inverter switching is controlled.
(SW52-2) Line-to-inverter switching
The magnetic contactor on the inverter output side (secondary side) of line-to-inverter switching is controlled.
(SW52-1) Line-to-inverter switching
The magnetic contactor on the inverter input side (primary side) of line-to-inverter switching is controlled.
(AX) AX terminal function
The electromagnetic contactor on the inverter input side (primary side) is controlled.
(FAN) Cooling fan ON/OFF control
The ON/OFF signal of the cooling fan is issued.
H06
(TRY) Retry in action
The signal is output during an active retry.
H04, H05
(U-DO) Universal DO
The signal transmitted from the host controller is issued.
(OH) Heat sink overheat early warning An early warning signal is issued before the heat sink trips due to an overheat. (LIFE) Lifetime alarm
H42, H43, H98
Outputs alarm signal according to the preset lifetime level.
(REF OFF) Command loss detection A loss of the frequency command is detected. (OLP) Overload preventive control
E65
The signal is output when the overload control is activated.
H70
The signal is output when a current larger than the set value has been detected for the timer-set time.
E34, E35
(PID-ALM) PID alarm output
An absolute value alarm or deviation alarm under PID control is issued as a signal.
J11 to J13
(PID-CTL) Under PID control
The valid state of PID control is issued as a signal.
(PID-STP) PID stop upon small water flow
(ID) Current detection
A signal is issued if operation is stopped due to a small water flow under PID control. (The inverter is stopped even if the operation command is issued.)
J15 to J17
(U-TL) Low torque detection
A signal is issued if the torque falls below the preset low torque detection level for a set time.
E80, E81
(RMT) In remote mode (AX2) Operation command input
A signal is issued in the remote mode. A signal is issued if there is an operation command input and operation ready is completed.
Communication Contact output
(ALM) Alarm relay output (for any fault) An alarm relay output (for any fault) signal is issued as a transistor output signal. CMY
Transistor output common
Common terminal for transistor output
Y5A,Y5C
General-purpose relay output
• Multi-purpose relay output; signals similar to above-mentioned signals Y1 to Y3 can be selected. Contact capacity: 250 V AC, 0.3A, cos =0.3 E24 • An alarm output is issued upon either excitation or no excitation according to selection. +48 V DC, 0.5A
The terminal is isolated from terminals 11 and CM.
E27
30A,30B,30C Alarm relay output (for • A no-voltage contact signal (1c) is issued when the inverter is stopped due to an alarm. • Multi-purpose relay output; signals similar to above-mentioned signals Y1 to Y3 can be selected. any fault) output • An alarm output is issued upon either excitation or no excitation according to selection. RJ45 connector for connection of keypad
One of the following protocols can be selected. • Modbus RTU • Protocol exclusively for keypad (default selection) • Fuji's special inverter protocol • SX protocol for PC loader
16
Power (+5V) is supplied to the keypad.
H30 y01 to y20 y98, y99
Terminal Functions Terminal Arrangement Main circuit terminals Power supply Applicable motor voltage rating (kW) Three-phase 0.75 200V 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 0.75 Three-phase 1.5 400V 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 220 280 315 355 400 450 500
Inverter type FRN0.75F1S-2A FRN1.5F1S-2A FRN2.2F1S-2A FRN3.7F1S-2A FRN5.5F1S-2A FRN7.5F1S-2A FRN11F1S-2A FRN15F1S-2A FRN18.5F1S-2A FRN22F1S-2A FRN30F1S-2A FRN37F1S-2A FRN45F1S-2A FRN55F1S-2A FRN75F1S-2A FRN90F1S-2A FRN110F1S-2A FRN0.75F1S-4A FRN1.5F1S-4A FRN2.2F1S-4A FRN3.7F1S-4A FRN5.5F1S-4A FRN7.5F1S-4A FRN11F1S-4A FRN15F1S-4A FRN18.5F1S-4A FRN22F1S-4A FRN30F1S-4A FRN37F1S-4A FRN45F1S-4A FRN55F1S-4A FRN75F1S-4A FRN90F1S-4A FRN110F1S-4A FRN132F1S-4A FRN160F1S-4A FRN200F1S-4A FRN220F1S-4A FRN280F1S-4A FRN315F1S-4A FRN355F1S-4A FRN400F1S-4A FRN450F1S-4A FRN500F1S-4A
Reference
Fig. D
Fig. A
Available soon
Control circuit terminal block
Control circuit terminal block R0 T0
U
V
W
P(+)
N(-)
Fig. A R0
T0
L1/R L2/S L3/T
Fig. B
P1
P(+)
N(-)
U
V
W G
G
Fig. C
P1
G
G
Terminal sizes R0, T0:M3.5, other:M4
Fig. D Fig. E
L1/R L2/S L3/T
Terminal sizes R0, T0:M3.5, other:M8
Fig. E
Fig. B
Fig. F
Control circuit terminal block
Control circuit terminal block
R0 T0
R0 T0
Available soon L1/R L2/S L3/T L1/R L2/S L3/T
Available soon
P1
P(+)
N(-)
U
V
U P1
G
Fig. A
G
Terminal sizes R0, T0:M3.5, other:M5
Fig. B
V
W
W P(+)
N(-)
G
G
Terminal sizes R0, T0:M3.5, other:M8
Fig. F
Fig. C
Fig. C
Control circuit terminal block
Fig. D
Control circuit terminal block
R0 T0
R0 T0
U
Fig. E
V
W
L1/R L2/S L3/T L1/R L2/S L3/T
P1
P(+)
N(-)
U
V
G
Control circuit terminals (common to all models)
30B 30A
Y1
Y3
V2 Y2
30C CMY
11
C1 11
FMA FMP
12
PLC 13
CM
X5
X1
17
X2
X3
FWD REV
Terminal sizes:M3
G
P(+)
G
Terminal sizes R0, T0:M3.5, G:M8, other:M10
Available soon
Y5C
P1
G
Terminal sizes R0, T0:M3.5, other:M6
Y5A
W
X4 CM
N(-)
Protective Functions Protective Functions Function
LED Alarm output Related indication (30A, B, C) Note) function code
Description
Overcurrent protection Short circuit protection Grounding fault protection
During acceleration The inverter is stopped for protection against overcurrent. The inverter is stopped for protection against overcurrent caused by a short circuit in the output circuit. During deceleration The inverter is stopped upon start-up for protection against overcurrent caused by a During constant grounding fault in the output circuit. If the power supply is turned on with the grounding fault, speed operation the protection may be invalidated. (3-phase 200V 75kW or less, 3-phase 400V 220kW or less) The inverter is stopped upon detection of a zero-phase current on the output current and for protection against overcurrent caused by a grounding fault in the output circuit. (3-phase 200V 90kW or more, 3-phase 400V 280kW or more)
Overvoltage protection
An excessive voltage (3-phase 200V series: 400VDC, 3-phase 400V series: 800VDC) in During acceleration the DC link circuit is detected and the inverter is stopped. If a large voltage is applied by During deceleration mistake, the protection cannot be guaranteed. During constant speed operation (when stopped)
Undervoltage protection
The voltage drop (3-phase 200V series: 200VDC, 3-phase 400V series: 400VDC) in the DC link circuit is detected to stop the inverter.However, when "F14: 4 or 5" is selected, an alarm is not issued even upon a voltage drop in the DC link circuit.
Input phase loss protection
The input phase loss is detected to shut off the inverter output. This function protects the inverter from being damaged by adding extreme stress caused by a power phase loss or imbalance between phases.When the load to be connected is small or DC REACTOR is connected a phase loss is not detected.
H98
Output phase loss protection Detects breaks in inverter output wiring at the start of operation and during running, to shut off the inverter output. The temperature of the heat sink in the event of cooling fan trouble and overload is detected to stop the inverter. Overheating protection The temperature inside the inverter unit in the event of cooling fan trouble and overload is detected to stop the inverter.
H98 H43
The temperature inside the IGBT is calculated from the detection of output current and internal temperature, to shut off the inverter output.
Fuse blown Charging circuit fault Electronic thermal
The wiring breakage of the main circuit fuse in the inverter is detected to stop the inverter. (3-phase 200V 90kW or more, 3-phase 400V 90kW or more)
Motor protection
Overload protection External alarm input
With the digital input signal (THR) opened, the inverter is stopped with an alarm.
F14
E01 to E03 E98, E99
The charging circuit fault in the inverter is detected to stop the inverter. (3-phase 200V 45kW or more, 3-phase 400V 55kW or more) The inverter is stopped with an electronic thermal function set to protect the motor.
F10
• The standard motor is protected at all the frequencies. • The inverter motor is protected at all the frequencies. * The operation level and thermal time constant can be set.
F11,F12
PTC thermistor
A PTC thermistor input stops the inverter to protect the motor. • The PTC thermistor is connected between terminals V2 and 11 to set switches and function codes on the control PC board.
H26,H27
Overload early warning
Warning signal is output at the predetermined level before stopping the inverter with the electronic thermal function to protect the motor.
E34,E35
Stall prevention
This is protected when the instantaneous overcurrent limit works.
H12
Alarm relay output (for any fault)
• Instantaneous overcurrent limit: operates when the inverter output current goes beyond the instantaneous overcurrent limiting level, and avoids tripping (during acceleration and constant speed operation). The relay signal is output when the inverter stops upon an alarm. <Alarm reset> The key or digital input signal (RST) is used to reset the alarm stop state. <Storage of alarm history and detailed data> Up to the last 4 alarms can be stored and displayed.
E20,E27 E01 to E03 E98,E99
Memory error Keypad communication error CPU error Option communication error Option error
Operation error
Data is checked upon power-on and data writing to detect any fault in the memory and to stop the inverter if any. The keypad (standard) or multi-function keypad (optional) is used to detect a communication fault between the keypad and inverter main body during operation and to stop the inverter.
F02
Detects a CPU error or LS1 error caused by noise. When each option card is used, a fault of communication with the inverter main body is detected to stop the inverter. When each option card is used, the option card detects a fault to stop the inverter. STOP key priority
Pressing the key on the keypad forcibly decelerates and stops the motor even if the operation command is given through a terminal block or communication. ( will be displayed after stopping.)
Start check
If the operation command is entered in the following cases, LED monitor to prohibit operation. • Power-on • Alarm reset ( key ON) • The link operation selection "LE" is used to switch operation.
H96
will be displayed on the
Tuning error RS485 communication error Data save error upon undervoltage RS485 communication error (optional) Retry
When tuning failure, interruption, or any fault as a result of turning is detected while tuning for motor constant.
Surge protection Command loss detection Momentary power failure protection Active drive
The inverter is protected against surge voltage intruding between the main circuit power line and ground.
P04
When the connection port of the keypad connected via RS485 communication port to detects a communication error, the inverter is stopped and displays an error. When the undervoltage protection works, an error is displayed if data cannot be stored. When an optional RS485 communication card is used to configure the network, a fault of communication with the inverter main body is detected to stop the inverter. When the motor is tripped and stopped, this function automatically resets the tripping state and restarts operation.(The number of retries and the length of wait before resetting can be set.)
H04,H05
A loss (broken wire, etc.) of the frequency command is detected to output an alarm and continue operation at the preset frequency (set at a ratio to the frequency before detection).
E65
• A protective function (inverter stoppage) is activated upon a momentary power failure for 15msec or longer. • If restart upon momentary power failure is selected, the inverter restarts upon recovery of the voltage within the set time.
F14 H13 to H16
The inverter output frequency is reduced to avoid tripping before heat sink overheating or tripping due to an overload (alarm indication: or ).
H70
Note : The item indicated with
in the alarm output (30A, B, C) column may not be issued according to some function code settings.
18
Keypad Operations Keypad switches and functions LED monitor
Operation mode display
When the motor is running or stopped: The monitor displays parameters such as output frequency, set frequency, motor speed, load shaft speed, output voltage, output current, and input power. Alarm mode: The monitor shows the alarm description with a fault code.
During keypad operation: When function code is , or (keypad operation), the green KEYPAD CONTROL LED lights up. During operation: The green RUN LED lights up.
Program/Reset key
Unit display
Used to change the mode. Programming mode: Used to shift the digit (cursor movement) to set data. Alarm mode: Resets a trip.
The unit of the data displayed at the LED monitor is indicated. Use the FUNC/DATA key to switch the displayed data.
Run key Used to start the operation.
Function/Data select key
While the motor is stopped:
Used to change the LED monitor and to store the function code and data.
This key is invalid if the function code is set to (operation by external signals).
Stop key
Up/Down keys During operation :Used to increase or decrease the frequency or motor speed. In data setting :Used to indicate the function code number or to change data set value.
Used to stop the operation. During operation: This key is invalid if the function code external signals). The inverter stops when the function code
is set to
(operation by
is set to
or
.
keypad modes are classified Monitor display and key operation The in the following 3 modes.
Operation mode
Programming mode STOP RUN
Monitor, keys Function Display
Monitor
Function PRG.MODE Hz A kW r/min m/min
Running mode STOP
Displays the function code or data.
Displays the output frequency, set frequency, loaded motor speed, required power, output current, and output voltage.
Displays the alarm description and alarm history.
ON The program mode is indicated.
Blinking ON Displays the unit of frequency, output current, required power, speed, and line speed.
Blinking/ON None
PRG.MODE Hz A kW ON r/min m/min
Display
KEYPAD Function CONTROL Display
Frequency indication
PRG.MODE Hz A kW ON r/min m/min
Speed indication
PRG.MODE Hz A kW ON r/min m/min
Current indication
PRG.MODE Hz A kW ON r/min m/min
Capacity or current indication
PRG.MODE Blink Hz A kW or lit r/min m/min
Display
Lit in keypad operation mode
RUN unlit / RUN lit
RUN unlit / RUN lit
RUN unlit / RUN lit
Switches to running mode
Keys
Function
OFF
Operation selection (keypad operation/terminal operation) is displayed.
Function Absence of operation Presence of operation Absence of operation command is displayed. command is displayed. command is displayed. RUN
Alarm mode
RUN
Presence of operation command is displayed.
Presence of operation command is displayed. /Stoppage due to trip is displayed.
RUN unlit / RUN lit
If an alarm occurs during operation, unlit during keypad operation or lit during terminal block operation.
Switches to programming mode
Releases the trip and switches to stop mode or running mode.
Switches the LED monitor display.
Displays the operation information. Displays the alarm history.
Digit shift (cursor movement) in data setting
Determines the function code, stores Function and updates data. Increases/decreases the function code Function and data.
Increases/decreases the frequency, motor speed and other settings.
Function Invalid Function Invalid
Decreases and stops (switches to programming mode (STOP)).
Starts running (switches to running mode (RUN)).
Invalid
Invalid
Invalid
Decreases and stops (switches to running mode (STOP)).
Invalid
This keypad supports a full menu mode which allows you to set or display the following information. Indication and setting change of changed function code, drive monitor, I/O check, maintenance information, and alarm information. For concrete operation methods, refer to the FRENIC-Eco Instruction Manual or User's Manual.
19
Functions Settings Function Settings F codes: Fundamental Functions Func. Code
Name Data Protection Frequency Command 1
Running/Stopping and Rotational Direction
Maximum Frequency Base Frequency Rated Voltage (at base frequency)
Acceleration Time 1 Deceleration Time 1 Torque Boost
Electronic Thermal (Select the motor property) Overload for Motor Protection (Overload detection level)
(Thermal time constant)
Restart Mode after Instantaneous Power Failure
Frequency Limiter (Peak) (Bottom) Bias (for Frequency Command 1) DC Braking (Starting frequency) (Braking level) (Braking time) Starting Frequency Stop Frequency Motor Sound (Carrier frequency)
(Sound tone)
Analog Output Signal Selection for [FMA] (Output gain) Analog Output Signal (Monitor object) Selection for [FMA]
Data Unit copy*2 Default setting
Data setting range
Min.
0: Disable data protection (Function code data can be edited.) 1: Enable data protection (Function code data can not be edited.) 0: Enable the and keys on the built-in keypad 1: Enable the voltage input to terminal [12](0 to +10 V DC) 2: Enable the current input to terminal [C1](+4 to +20 mA DC) 3: Enable the sum of voltage and current inputs to terminals [12] and [C1] 5: Enable the voltage input to the terminal [V2](0 to +10 V DC) 7: Enable the terminal signal command (UP) and (DOWN) control 0: Enable the and keys on the built-in keypad to run and stop motor (The (FWD) or (REV) command should be ON for forward or reverse rotation.) 1: Enable the terminal signal command (FWD) or (REV) command to run motor 2: Enable the and keys on the keypad to run/stop motor forward 3: Enable the and keys on the keypad to run/stop motor reverse 25.0 to 120.0 25.0 to 120.0 0 : Output voltage in line with variance in input voltage 80 to 240 : Output voltage AVR-controlled 160 to 500 : Output voltage AVR-controlled 0.00 to 3600 Note: Acceleration time is ignored at 0.00. (External gradual acceleration pattern) 0.00 to 3600 Note: Deceleration time is ignored at 0.00. (External gradual deceleration pattern) 0.0 to 20.0 (The set voltage at base frequency for F05 is 100%.) Note: This setting is effective for auto torque boost/auto energy saving operations specified by function code F37 (= 0, 1, 3, or 4). 1: For general-purpose motors with built-in self-cooled fans 2: For motors with forced-cooled fans 0.00 (Disabled) 1 to 135% of rated current (allowable continuous drive current) of the inverter 0.5 to 75.0 0: Inactive (Trip immediately without restart) 1: Inactive (Trip without restart after recovery of power) 3: Active (Continuous running for the heavy inertia or general load) 4: Active (Restart at the frequency at which the power failure occurred, for general load) 5: Active (Restart at the starting frequency, for low-inertia load) 0.0 to120.0 0.0 to120.0 -100.00 to 100.00 *1 0.0 to 60.0 0 to 60 (Rated output current of the inverter interpreted as 100%.) 0.00: (Disabled), 0.01 to 30.00 0.1 to 60.0 0.1 to 60.0 _ 22 kW) *3 0.75 to 15 (< 0.75 to 10 (30 to 75 kW) _90 kW) 0.75 to 6 (> 0: Level 0 (Inactive) 1: Level 1 2: Level 2 3: Level 3 0: Output in voltage (0 to +10 V DC) 1: Output in current (+4 to +20 mA DC) 0 to 200 Select the object to be monitored as follows. 0: Output frequency 2: Output current 3: Output voltage 4: Output torque 5: Load rate 6: Input power 7: PID feedback amount 9: DC link circuit voltage 10: Universal AO 13: Motor output 14: Test analog output (+) voltage 15: PID process command (SV) 16: PID process output (MV) 25 to 6000 (Pulse rate at 100% output)
-
-
Y
0
-
-
Y
0
-
-
Y
2
0.1 0.1 1
Hz Hz V
Y Y Y2
60.0 60.0
Digital Output Signal (Pulse rate) Selection for [FMP] (Output gain) 0 : Output pulse rate (Fixed at 50% duty) 1 to 200 : Voltage output adjustment (Pulse rate is fixed at 2000 p/s. Adjust the pulse duty)
20
0.01
s
Y
200 400 20.0
0.01
s
Y
20.0
0.1
%
Y
Depending on the motor applied
-
-
Y
1
0.01
A
0.1
min
Y1 Y2 Y
-
-
Y
100% of the motor rated current _ 22 kW) 5 (< _30 kW) 10 (> 1
0.1 0.1 0.01 0.1 1 0.01 0.1 0.1 1
Hz Hz % Hz % s Hz Hz kHz
Y Y Y Y Y Y Y Y Y
70.0 0.0 0.00 0.0 0 0.00 0.5 0.2 2
-
-
Y
0
1 -
% -
Y Y
100 0
1
p/s
Y
1440
1
%
Y
0
Functions Settings Function Settings F codes: Fundamental Functions Func. Code
Name
Data setting range
Min.
(Monitor object) Select the object to be monitored as follows. 0: Output frequency 9: DC link circuit voltage 2: Output current 10: Universal AO 3: Output voltage 13: Motor output 4: Output torque 14: Test analog output (+) voltage 5: Load rate 15: PID process command (SV) 6: Input power 16: PID process output (MV) 7: PID feedback amount Load Selection/ 0: Variable torque load Auto Torque Boost/ 1: Variable torque load Auto Energy Saving Operation (Higher startup torque required) 2: Auto-torque boost 3: Auto-energy saving operation (Variable torque load increasing in proportion to square of speed) 4: Auto-energy saving operation (Variable torque load increasing in proportion to square of speed (Higher startup torque required)) Note: Apply this setting to a load with short acceleration time. 5: Auto-energy saving operation(Auto-torque boost) Note: Apply this setting to a load with long acceleration time. Current Limiter (Operation condition) 0: Disabled 1: In constant speed (Disabled during acceleration and deceleration) 2: At acceleration and in constant speed (Disabled during deceleration) (Limiting level) 20 to 120 (The data is interpreted as the rated output current of the inverter for 100%.)
Data Unit copy*2 Default setting
-
-
Y
0
-
-
Y
1
-
-
Y
0
1
%
Y
110
E codes: Extension Terminal Functions Func. Code
Name Terminal Command Assignment to:
[X1] [X1] [X3] [X4] [X5]
Data setting range
Min.
Select data to specify the function of terminals [X1] to [X5] as follows. To assign a negative logic input to a terminal, set the value of 1000s shown in ( ) in the table below to the function code. Any negative logic cannot be applied for functions without (1000s) data. 0: (1000) Multi-step frequency selection (0 to 1 steps) (SS1) 1: (1001) Multi-step frequency selection (0 to 3 steps) (SS2) 2: (1002) Multi-step frequency selection (0 to 7 steps) (SS4) 6: (1006) Self-hold the terminal command (HLD) 7: (1007) Coast-to-stop command (BX) 8: (1008) Alarm reset (RST) 9: (1009) Alarm from external equipment (THR) 11: (1011) Frequency command 2 or 1 (Hz2/Hz1) Note: PID process command follows this command. 13: DC braking command (DCBRK) Switch the motor drive source to thecommercial power lines (50 Hz) (SW50) 15: 16: Switch the motor drive source to thecommercial power lines (60 Hz) (SW60) 17: (1017) UP command (UP) 18: (1018) DOWN command (DOWN) 19: (1019) Enable editing of function codes from keypad (WE-KP) 20: (1020) Disable PID control (Hz/PID) 21: (1021) Switch normal/inverted driving (IVS) 22: (1022) Interlock command (IL) 24: (1024) Select link operation (RS485 communication, option) (LE) 25: (1025) Universal DI (U-DI) 26: (1026) Select starting characteristics (STM) 30: (1030) Forced stop (STOP) 33: (1033) Reset PID integral and differential components (PID-RST) 34: (1034) Hold PID integral component (PID-HLD) 35: (1035) Select the local (keypad) (LOC) 38: (1038) Enable to run (RE) 39: Protect the inverter from a dew condensation (DWP) Enable the integrated commercial line switching sequence (50 Hz) (ISW50) 40: 41: Enable the integrated commercial line switching sequence (60 Hz) (ISW60) 87: (1087) Select the run command 1 or 2 (FR2/FR1) 88: Run Forward/Stop command 2 (FWD2) 89: Run Reverse/Stop command 2 (REV2) Note: For (THR) and (STOP), data (1009) and (1030) are assigned for normal logic, and "9" and "30" are for negative logic respectively.
-
*1 When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can display. (Example) If the setting range is from -200.00 to 200.00, the incremental unit is: "1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.
Data Unit copy*2 Default setting -
Y Y Y Y Y
6 7 8 11 35
*2 Symbols in the "Data copy" column Y: Will be copied unconditionally. Y1: Will not be copied if the rated capacity differs from the source inverter. Y2: Will not be copied if the rated input voltage differs from the source inverter. N: Will not be copied. *3 If the carrier frequency is set at 1 kHz or below, estimate the motor output torque at 80% or less of the rated motor torque.
<Changing, validating, and saving function code data when the motor is running> : Impossible, : Possible (Change data with keys and then save/validate it with : Possible (Change and validate data with keys and then save it with key)
21
key),
Functions Settings Function Settings E codes: Extension Terminal Functions Func. Code
Data Unit copy*2 Default setting
Name
Data setting range
Min.
Status Signal Assignment to: [Y1] [Y2] [Y3] Relay Contact Output [Y5A, Y5C] [30A, B, C] (Mechanical relay contacts)
Select data to specify the terminal function as follows. To assign a negative logic output to a terminal, set the value of 1000s shown in ( ) on the table below to the function code. (OFF if short-circuited) Any negative logic cannot be applied for functions without (1000s) data.
-
-
Y Y Y Y Y
1 2 15 0 99
0.1 0.01
Hz A
Y Y1 Y2
60.0 Nominal rated current (100%) of the motor
0.01 0.01 0.01 -
s -
Y Y Y Y
10.00 100 0.00 0
-
-
Y
0
-
-
Y
0
-
-
Y Y
5 0
0.01 0.001
-
Y Y
30.00 0.010
-
-
Y
0
0: (1000) Inverter running (RUN) 1: (1001) Frequency equivalence signal (FAR) 2: (1002) Frequency level detection (FDT) 3: (1003) Undervoltage detection signal (LU) 5: (1005) Torque limiting (Current limiting) (IOL) 6: (1006) Auto-restarting after recovery of power (IPF) 7: (1007) Motor overload early warning (OL) 10: (1010) Inverter ready to run (RDY) 11: Switch the motor drive source from the commercial power lines to the inverter output (SW88) 12: Switch the motor drive source from the commercial power lines to the inverter output 2 (SW52-2) 13: Switch the motor drive source from the commercial power lines to the inverter output 1 (SW52-1) 15: (1015) Select the AX terminal function (AX) 25: (1025) Turn on/off the cooling fan (FAN) 26: (1026) Retry in operation (TRY) 27: (1027) The universal DO enabled (U-DO) 28: (1028) Overheat early warning (OH) 30: (1030) Lifetime alarm (LIFE) 33: (1033) Command missing detected (REF OFF) 35: (1035) Inverter running (RUN2) 36: (1036) Overload prevention control (OLP) 37: (1037) Current detection (ID) 42: (1042) PID alarm warning (PID-ALM) 43: (1043) PID control in operation (PID-CTL) 44: (1044) PID control out of operation due to the slow flow-rate (PID-STP) 45: (1045) Low output torque detected (L-TL) 54: (1054) Inverter in remote operation (RMT) 55: (1055) Run command activated (AX2) 56: (1056) Motor overheat detected (PTC) (THM) 99: (1099) Alarm relay output (for any alarm) (ALM) Frequency Detection (FDT) (Detection level) 0.0 to 120.0 Overload Early Warning/ (Level) 0 (Disabled) Current Detection Current value of 1 to 200% of the rated inverter current
(Timer) PID Display Coefficient A PID Display Coefficient B LED Monitor Item Selection
LED Monitor Item Selection Display Language Selection
Display Contrast Control LED Monitor (Speed monitor item)
Coefficient for Speed Indication Display Coefficient for Accumulated Power Consumption Keypad(Menu display mode)
0.01 to 600.00*1 -999 to 0.00 to 999 -999 to 0.00 to 999 0: Speed monitor (Select by E48.) 3: Output current 4: Output voltage 8: Calculated torque 9: Input power 10: PID final command value 12: PID feedback amount 14: PID output amount 15: Load rate 16: Motor output 17: Analog input (Monitor) 0: Display the operation guide 1: Display the speed, current or output torque in bar-graph 0: Japanese 1: English 2: German 3: French 4: Spanish 5: Italian 0 (low) to 10 (high) 0: Output frequency 3: Motor speed in rpm 4: Load shaft speed in rpm 7: Display speed in % 0.01 to 200.00*1 0.0 (Cancel/reset)0.001 to 9999 0: Function code data setting mode (Menu #0, #1 and #7) 1: Function code data check mode (Menu #2 and #7) 2: Full-menu mode
22
Functions Settings Function Settings Func. Code
Name
Data setting range
Min.
Data Unit copy*2 Default setting
Analog Input Signal Definition for: [12] Select the data to specify the terminal function as follows. [C1] [V2] 0: None 1: Auxiliary frequency command 1 2: Auxiliary frequency command 2 3: PID process command 1 5: PID feedback amount 20: Analog signal input monitor Specify How to Save the Digital Set 0: Auto-saving Frequency 1: Saving by pressing the key
-
-
Y Y Y
0 0 0
-
-
Y
0
Specify the Inverter Operation when Detecting Command Missing Detect Low Torque (Detection level) (Timer) Terminal Command Assignment to: [FWD] [REV]
1
%
Y
999
1 0.01 -
% s N
Y Y N Y
20 20.00 98 99
0: Coast-to-stop the motor, 1 to 120, 999: Cancel 0 to 150 0.01 to 600.00 Select data to specify the terminal function as follows. To assign a negative logic input to a terminal, set the value of 1000s shown in ( ) in the table below to the function code.Any negative logic cannot be applied for functions without (1000s) data. 00: (1000) Multi-step frequency selection (0 to 1 steps) (SS1) 01: (1001) Multi-step frequency selection (0 to 3 steps) (SS2) 02: (1002) Multi-step frequency selection (0 to 7 steps) (SS4) 06: (1006) Self-hold the terminal command (HLD) 07: (1007) Coast-to-stop command (BX) 8: (1008) Alarm reset (RST) 09: (1009) Alarm from external equipment (THR) 11: (1011) Frequency command 2 or 1 (Hz2/Hz1) Note: PID process command follows this setting. 13: DC brake command (DCBRK) 15: Switch the motor drive source between the commercial line and inverter (50 Hz) (SW50) 16: Switch the motor drive source between the commercial line and inverter (60 Hz) (SW60) 17: (1017) UP command (UP) 18: (1018) DOWN command (DOWN) 19: (1019) Enable editing of function codes from keypad (WE-KP) (WE-KP) 20: (1020) Disable PID control (Hz/PID) 21: (1021) Switch normal/inverted driving (IVS) 22: (1022) Interlock command (IL) 24: (1024) Select link operation (Standard and TB bus-optional RS485 communication) (LE) 25: (1025) Universal DI (U-DI) 26: (1026) Select starting characteristics (STM) 30: (1030) Forced stop (STOP) 33: (1033) Reset PID integral and differential components (PID-RST) 34: (1034) Hold PID integral component (PID-HLD) 35: (1035) Select the local (keypad) (LOC) 38: (1038) Enable to run (RE) 39: Protect the inverter from a dew condensation (DWP) 40: Enable the integrated commercial line switching sequence (50 Hz) (ISW50) 41: Enable the integrated commercial line switching sequence (60 Hz) (ISW60) 87: (1087) Select the run command 1 or 2 (FR2/FR1) 88: Run Forward/Stop command 2 (FWD2) 89: Run Reverse/Stop command 2 (REV2) 98: Run Forward/Stop command (FWD) 99: Run Reverse/Stop command (REV) Note: For (THR) and (STOP), data (1009) and (1030) are assigned for normal logic, and "9" and "30" are for negative logic respectively.
*1 When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can display. (Example) If the setting range is from -200.00 to 200.00, the incremental unit is: "1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99. *2 Symbols in the "Data copy" column Y: Will be copied unconditionally. Y1: Will not be copied if the rated capacity differs from the source inverter. Y2: Will not be copied if the rated input voltage differs from the source inverter. N: Will not be copied. <Changing, validating, and saving function code data when the motor is running> : Impossible, : Possible (Change data with keys and then save/validate it with : Possible (Change and validate data with keys and then save it with key)
23
key),
Functions Settings Function Settings C codes: Control Functions of Frequency Func. Code
Name Jump Frequency 1 2 3 Jump Frequency Band Multi-step Frequency Settings 1 2 3 4 5 6 7 Frequency Command 2
Analog Input Adjustment (Gain for terminal input [12]) (Filter time constant) (Gain reference point) Analog Input Adjustment (Gain for terminal input [C1]) (Filter time constant) (Gain reference point) Analog Input Adjustment (Gain for terminal input [V2]) (Filter time constant) (Gain reference point) Bias(Frequency command 1) (Bias reference point) Bias (PID command 1) (Bias value) (Bias reference point) Select to Run the Motor Forward or Reverse for the Set Frequency 1
Data setting range
Min.
Data Unit copy*2 Default setting
0.0 to 120.0
0.1
Hz
0.0 to 30.0 0.00 to 120.00
0.1 0.01
Hz Hz
-
0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 -
0: Enable the and keys on the keypad 1: Enable the voltage input to terminal [12] (0 to +10 V DC) 2: Enable the current input to terminal [C1] (+4 to +20 mA DC) 3: Enable the sum of voltage and current inputs to terminals [12] and [C1] 5: Enable the voltage input to terminal [V2] (0 to +10 V DC) 7: Enable the (UP)/(DOWN) terminal signal control 0.00 to 200.00*1 0.00 to 5.00 0.00 to 100.00*1 0.00 to 200.00*1 0.00 to 5.00 0.00 to 100.00*1 0.00 to 200.00*1 0.00 to 5.00 0.00 to 100.00*1 0.00 to 100.00*1 -100.00 to 100.00*1 0.00 to 100.00*1 0: Forward 1: Reverse
-
Y Y Y Y Y Y Y Y Y Y Y Y
0.0 0.0 0.0 0.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2
% s % % s % % s % % % % -
Y Y Y Y Y Y Y Y Y Y Y Y Y
100.0 0.05 100.0 100.0 0.05 100.0 100.0 0.05 100.0 0.00 0.00 0.00 0
P codes: Motor Parameters Func. Code
Name
Data setting range
Motor
(No. of the poles) 2 to 22
(Rated capacity) 0.01 to 1,000 kW (where, the data of function code P99 is 0, 3, or 4.) 0.01 to 1,000 HP (where, the data of function code P99 is 1.) (Rated current) 0.00 to 2,000 (Auto-tuning) 0: Disabled 1: Enabled (Tune %R1 and %X while the motor is stopped.) 2: Enabled (Tune %R1 and %X while the motor is stopped, and no load current while running.) (No load current) 0.00 to 2,000 (%R1) 0.00 to 50.00 (%X) 0.00 to 50.00 0: Characteristics of motor 0 (Fuji's standard 8- and 9-series motors) 1: Characteristics of motor 1 (HP motors) 3: Characteristics of motor 3 (Fuji's standard 6- and 9-series motors) 4: Other motors
Motor Selection
Min.
Data Unit copy*2 Default setting
2
Pole
0.01 0.01 0.01 -
kW HP A -
Y1 Y2 Y1 Y2 Y1 N
0.01 0.01 0.01 -
A % % -
Y1 Y1, Y2 Y1, Y2 Y1, Y2
4 Nominal rated capacity of standard motors Nominal rated current of Fuji's standard motor 0
Nominal rated current of Fuji's standard motor Nominal rated current of Fuji's standard motor Nominal rated current of Fuji's standard motor 0
H codes: High Performance Functions Func. Code
Name
Data setting range
Data Initializing
(Data reset) 0: Disable initialization (All function code data manually set remains.) 1: Initialize all function code data to the factory defaults 2: Initialize motor parameters Retry (No. of retries) 0: Inactive 1 to 10 (Latency time) 0.5 to 20.0 Cooling Fan ON/OFF 0: Inactive (Always ON) 1: Active (ON/OFF controllable) Gradual Acceleration/ Deceleration 0: Inactive (Linear) 1: S-curve (Weak) 2: S-curve (Strong) 3: Curvilinear Starting Characteristics of the Motor 0: Inactive (Synchronization mode) 3: Active (As following the RUN command, the inverter synchronizes the motor rotation either forward or reverse.) 4: Active (As following the RUN command, the inverter synchronizes the motor rotation both forward and reverse.) 5: Active (As following the RUN command, the inverter synchronizes the motor rotation reversely either forward or reverse.) 0: Normal deceleration Deceleration Mode 0: Coast-to-stop Instantaneous Overcurrent Limiting 0: Inactive 1: Active
24
Min.
Data Unit copy*2 Default setting
-
-
N
0
1
Times
Y
0
0.1 -
s -
Y Y
5.0 0
-
-
Y
0
-
-
Y
0
-
-
Y
-
-
Y
1
Functions Settings Function Settings H codes: High Performance Functions Func. Code
Name
Data setting range
Min.
Data Unit copy*2 Default setting
0.1 Specify the Inverter Operation at (Waiting time) 0.1 to 10.0 s Instantaneous Power Failure Restarting 0.01 (Frequency reduction rate) 0: Set deceleration time Hz/s 0.01 to 100.00 999: Follow the set current limit 1 (DC link voltage allowable to run) 200V series: 200 to 300 V 400V series: 400 to 600 0.1 (Allowable instantaneous 0.0 to 30.0 s power failure time) 999: The longest time automatically determined by the inverter 0.1 Starting Characteristics Hz 0.0 to 120.0 (Synchronous frequency) 999: Synchronize at the highest output frequency PTC Thermistor Input 0: Inactive on the LED and trip, and immediately stop the inverter after detecting (PTC).) 1: Active (Display 2: Active (Output PTC warning status on (THM), and continue to run.) 0.01 V (Level) 0.00 to 5.00 Communication (Function selection) Frequency command Run command Link Operation 0: F01/C30 F02 1: RS485 Link F02 2: F01/C30 RS485 Link 3: RS485 Link RS485 Link 4: RS485 Link (Option) F02 5: RS485 Link (Option) RS485 Link 6: F01/C30 RS485 Link (Option) 7: RS485 Link RS485 Link (Option) 8: RS485 Link (Option) RS485 Link (Option) Capacity of DC Link Bus Capacitor For indication for replacing the DC link bus capacitor (0000 to FFFF: Hexadecimal) 1 Accumulated Run Time of Cooling Fan Show an accumulated run time of the cooling fan for replacing it Initial Capacity of DC Link Bus Capacitor For indication for replacing the DC link bus capacitor (0000 to FFFF: Hexadecimal) 1 Accumulated Run Time of For indication for replacing the capacitors on the PCB Capacitors on the PCB (Printed Circuit Board) (0000 to FFFF: Hexadecimal). Resettable. 0.1 Hz Non-linear V/f Pattern (Frequency) 0.0 (Cancel), 0.1 to 120.0 1 V (Voltage) 0 to 240: Output voltage AVR-controlled for 200 V class motors 0 to 500: Output voltage AVR-controlled for 400 V class motors 0.01 s Deceleration Time for Forced Stop 0.00 to 3,600 Bottom Limiter (Specify operation) Peak Freq./Operation Bottom Freq./Operation 0: Limit by F15 (Peak) and continue to run Limit by F16 (Bottom) and continue to run 1: Limit by F15 (Peak) and continue to run Limit by F16 (Bottom) and coast-to-stop upon lowering the limit. (Min. freq. when limiter is activated) 0.0 (Depends on F16: Freq. limiter (bottom)), 0.1 Hz 0.1 to 60.0 Automatic Deceleration 0: Inactive 1: Active 0.01 Hz/s Overload Prevention Control 0.00 (Equivalent to deceleration time), (Frequency drop rate) 0.01 to 100.00, 999 (Cancel) Deceleration Characteristics 0: Inactive, 1: Active 0.01 Gain for Suppression of Output 0.00 to 0.40 Current Fluctuation for Motor Continue to Run (P Component: Gain) 0.000 to 10.000*1 0.001 Times
(I Component: Time) 0.000 to 10.000
Accumulated Run Time of Motor
*1
Initialize data (Resettable)
0: Slow DC Braking (Braking response mode) 1: Quick STOP Key Priority/Start Check Function
STOP Key Priority Start Check Function
Clear Alarm Data Protection/ (Specify operation) Maintenance Function
0
1
2
OFF ON OFF OFF OFF ON
3
Y
Y2
Depending on the motor capacity 999
Y
235 470 999
Y
999
Y
0
Y Y
1.60 0
N N N N
Set at factory shipping -
Y Y2
0.0 0
Y Y
20.0 0
Y
2.0
Y
0
Y
999
Y Y
0.001
s
Y
-
-
N
0 0.20 for _ <22 kW 0.10 for _ >30 kW _22 kW 0.250 for < _30 kW 0.244 for > _22 kW 0.038 for < _30 kW 0.066 for > -
-
-
Y
1
-
-
Y
0
-
-
Y Y
19 (Bits 4, 1, 0 = 1)
Y
ON ON
Returns to zero after clearing alarm data (if H97 = 1). 0 to 31: (Display data on the LCD of keypad in decimal format. Values of bit are: "0" for disabled, "1" for enabled Bit 0: Auto-lowering the carrier frequency Bit 1: Protecting the inverter operation from input phase loss Bit 2: Protecting the inverter operation from output phase loss Bit 3: Specify a service life criteria for replacing the DC link bus capacitor Bit 4: Indication the service life for the DC link bus capacitor
*1 When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can display. (Example) If the setting range is from -200.00 to 200.00, the incremental unit is: "1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99. *2 Symbols in the "Data copy" column Y: Will be copied unconditionally. Y1: Will not be copied if the rated capacity differs from the source inverter. Y2: Will not be copied if the rated input voltage differs from the source inverter. N: Will not be copied. <Changing, validating, and saving function code data when the motor is running> : Impossible, : Possible (Change data with keys and then save/validate it with key), : Possible (Change and validate data with keys and then save it with key)
25
Y
Functions Settings Function Settings J codes: Application Functions Func. Code
Name PID Control
(Remote process command)
P (Gain) I (Integration time) D (Differentiation time) (Feedback filter) (Anti-rest/windup) (Select alarm output)
(Peak limit alarm(AH)) (Bottom limit alarm(AL)) (Stop frequency for slow flowrate) (Elapsed stop time for slow flowrate) (Starting frequency) (Upper limit of PID process output) (Lower limit of PID process output) Dew Condensation Protection (Duty) Commercial Line Switching Sequence
Data setting range 0: Inactive 1: Process control use (Normal action) 2: Process control use (Inverse action) 0: Keypad 1: PID process command 1 (Data settings of E60, E61 and E62 are also required.) 3: UP/DOWN 4: Communication 0.000 to 30.000*1 0.0 to 3600.0*1 0.00 to 600.00*1 0.0 to 900.0 0 to 200 0: Alarm in absolute value 1: Alarm in absolute value with HOLD 2: Alarm in absolute value with LATCH 3: Alarm in absolute value with HOLD and LATCH 4: Alarm in deviation value 5: Alarm in deviation value with HOLD 6: Alarm in deviation value with LATCH 7: Alarm in deviation value with HOLD and LATCH 0 to 100 0 to 100 0: Disabled, 1 to 120 1 to 60 0: Disabled, 1 to 120 1 to120, 999: Depends on setting of F15 1 to120, 999: Depends on setting of F16 1 to 50 0: Integrated standard switching sequence 1: Auto-switching sequence for inverter alarm
Min.
Data Unit copy*2 Default setting
-
-
Y
0
-
-
Y
0
Y Y Y Y Y Y
0.100 0.0 0.00 0.5 200 0
Y Y Y Y Y Y Y Y Y
100 0 0 0 0 999 999 1 0
0.001 Times 0.1 s 0.01 s 0.1 s 1 % -
1 1 1 1 1 1 1 1 -
% % % s Hz Hz Hz % -
y codes: Link Functions Func. Code
Name
Data setting range
RS485 Communication (Station address) 1 to 255 (Standard) (Mode selection on no response error) 0: Immediate trip and alarm 1: Trip and alarm after running for the period of the timer set by y03 2: Retry during the period of the timer set by y03. If retry fails, trip and alarm If it succeeds, continue to run. 3: Continue to run (Timer) 0.0 to 60.0 (Transmission rate) 0: 2,400 1: 4,800 2: 9,600 3: 19,200 4: 38,400 (Data length) 0: 8 1: 7 (Parity check) 0: None 1: Even parity 2: Odd parity (Stop bits) 0: 2 1: 1 (No response error detection time) 0 (No detection), 1 to 60 (Response interval) 0.00 to 1.00 (Protocol selection) 0: Modbus RTU protocol 1: SX protocol (Loader protocol) 2: Fuji general-purpose inverter protocol
26
Min.
Data Unit copy*2 Default setting
1
-
Y
1
-
-
Y
0
0.1 -
s bps
Y Y
2.0 3
-
bit
Y
0
-
-
Y
0
-
bit
Y
0
1 0.01 -
s s -
Y Y Y
0 0.01 1
Functions Settings Function Settings y codes: Link Functions Func. Code
Name
Data setting range
Min.
RS485 Communication (Station address) 1 to 255 (TB bus option) (Mode selection on no response error) 0: Immediate trip and alarm 1: Trip and alarm after running for the period of the timer set by y03 2: Retry during the period of the timer set by y03. If retry fails, trip and alarm If it succeeds, continue to run. 3: Continue to run (Timer) 0.0 to 60.0 (Transmission rate) 0: 2,400 1: 4,800 2: 9,600 3: 19,200 4: 38,400 (Data length) 0: 8 1: 7 (Parity check) 0: None 1: Even parity 2: Odd parity (Stop bits) 0: 2 1: 1 (No response error detection time) 0 (No detection), 1 to 60 (Response interval) 0.00 to 1.00 (Protocol selection) 0: Modbus RTU protocol 1: SX protocol (Loader protocol) 2: Fuji general-purpose inverter protocol Bus Link Function for Frequency Command source Run command source Supporting Data Input 0: Follow H30 Follow H30 1: Field bus option Follow H30 2: Follow H30 Field bus option 3: Field bus option Field bus option Loader Link Function for Frequency Command source Run command source Supporting Data Input 0: Follow H30 and y98 Follow H30 and y98 1: Loader Follow H30 and y98 2: Follow H30 and y98 Loader 3: Loader Loader
Data Unit copy*2 Default setting
1
-
Y
1
-
-
Y
0
0.1 -
s bps
Y Y
2.0 3
-
bit
Y
0
-
-
Y
0
-
bit
Y
0
1 0.01 -
s s -
Y Y Y
0 0.01 1
-
-
Y
0
-
-
N
0
*1 When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can display. (Example) If the setting range is from -200.00 to 200.00, the incremental unit is: "1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99. *2 Symbols in the "Data copy" column Y: Will be copied unconditionally. Y1: Will not be copied if the rated capacity differs from the source inverter. Y2: Will not be copied if the rated input voltage differs from the source inverter. N: Will not be copied. <Changing, validating, and saving function code data when the motor is running> : Impossible, : Possible (Change data with keys and then save/validate it with : Possible (Change and validate data with keys and then save it with key)
27
key),
Options Options Name (Type)
Name (Type)
Appearance
DC REACTOR
Appearance
Remote operation extension cable
Type
Length(m)
CB-5S CB-3S CB-1S
5 3 1
Cable Connector : RJ45 8 1 L
Wiring equipment Power Applicable motor supply voltage rating [kW] Three- phase 200V
0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 Three- 0.75 phase 1.5 400V 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 220 280 315 355 400 450 500
Inverter type
Molded-case circuit breaker (MCCB), Earth-leakage circuit breaker (ELCB), Rated current [A]
Magnetic contactor(MC) Input circuit
With DCR Without reactor With DCR Without reactor FRN0.75F1S-2A FRN1.5F1S-2A FRN2.2F1S-2A FRN3.7F1S-2A FRN5.5F1S-2A FRN7.5F1S-2A FRN11F1S-2A FRN15F1S-2A FRN18.5F1S-2A FRN22F1S-2A FRN30F1S-2A FRN37F1S-2A FRN45F1S-2A FRN55F1S-2A FRN75F1S-2A FRN90F1S-2A FRN110F1S-2A FRN0.75F1S-4A FRN1.5F1S-4A FRN2.2F1S-4A FRN3.7F1S-4A FRN5.5F1S-4A FRN7.5F1S-4A FRN11F1S-4A FRN15F1S-4A FRN18.5F1S-4A FRN22F1S-4A FRN30F1S-4A FRN37F1S-4A FRN45F1S-4A FRN55F1S-4A FRN75F1S-4A FRN90F1S-4A FRN110F1S-4A FRN132F1S-4A FRN160F1S-4A FRN200F1S-4A FRN220F1S-4A FRN280F1S-4A FRN315F1S-4A FRN355F1S-4A FRN400F1S-4A FRN450F1S-4A FRN500F1S-4A
Output circuit
Recommended cable size [mm2] Input circuit (L1/R, L2/S, L3/T)
Output DB circuit circuit (P1, P(+)) With DCR Without reactor (U, V, W)
30 40 50 75 100 100 150 175 200 250 350
50 75 100 125 150 175 200 250 300 350 -
SC-05 SC-5-1 SC-N1 SC-N2 SC-N2S SC-N2S SC-N4 SC-N5 SC-N7 SC-N8 SC-N11
SC-N1 SC-N2 SC-N2S SC-N3 SC-N4 SC-N5 SC-N7 SC-N8 SC-N8 SC-N11 -
SC-4-0 SC-5-1 SC-N1 SC-N2 SC-N2S SC-N2S SC-N4 SC-N5 SC-N7 SC-N8 SC-N11
2.0 3.5 5.5 14 14 14 38 38 60 100 100
5.5 8.0 14 22 38 38 60 60 100 100 -
2.0 3.5 5.5 8.0 14 14 38 38 60 100 100
2.0 3.5 8.0 14 22 22 38 60 100 100 150
15 20 30 40 40 50 75 100 100 125 175
30 40 50 60 75 100 125 125 150 200 -
SC-05 SC-05 SC-05 SC-5-1 SC-N1 SC-N1 SC-N2 SC-N2S SC-N3 SC-N3 SC-N4
SC-4-0 SC-5-1 SC-N1 SC-N1 SC-N2 SC-N2S SC-N3 SC-N4 SC-N4 SC-N5 -
SC-05 SC-05 SC-4-0 SC-5-1 SC-N1 SC-N1 SC-N2 SC-N2S SC-N3 SC-N4 SC-N5
2.0 2.0 2.0 3.5 5.5 5.5 14 14 22 22 38
2.0 3.5 5.5 8.0 14 14 22 22 38 60 -
2.0 2.0 2.0 3.5 5.5 5.5 14 14 22 38 60
2.0 2.0 2.0 3.5 5.5 8.0 14 22 22 38 60
• For MCCB and ELCB, the required frame type and series depend on the facility transformer capacity and other factors. When selecting optimal breakers, refer to the relevant catalog or technical data. • Also select the rated sensitive current of ELCB utilizing the technical data. The above rated currents of MCCB and ELCB are for Fuji's SA B/ , SA R/ breakers. • The recommended wire sizes are based on the temperature inside the panel not exceeding 50˚C. • The above wires are 600V HIV insulated solid wires (75˚C). • Data in the above table may differ according to environmental conditions (ambient temperature, power supply voltage, and other factors). (Note) Use low-pressure crimp terminal CB150-10 (JEM1399) for the crimp terminal of FRN75F1S-2A. Inverter types indicated with are available soon.
28
Japanese Guidelines for Suppressing Harmonics Guideline for Suppressing Harmonics in Home Electric and General-purpose Appliances Our three-phase, 200V series inverters of 3.7kW or less (FRENIC-Eco series) are the products specified in the "Guideline for Suppressing Harmonics in Home Electric and General-purpose Appliances" (established in September 1994, and revised in October 1999) published by the Ministry of Economy, Trade and Industry. The Japan Electrical Manufacturers' Association has determined a standard of regulation levels based on this guideline. To meet this standard, a reactor (for harmonic suppression) must be connected to an inverter. Use a "DC REACTOR" introduced in this catalog. For a reactor you want to prepare, please contact us about detailed specifications.
Guideline for Suppressing Harmonics by Customers Receiving High Voltage or Special High Voltage Our three-phase, 200V series inverters of 5.5kW or more and three-phase, 400V series inverters (FRENIC-Eco series) are the products specified in the "Guideline for Suppressing Harmonics by Customers Receiving High Voltage or Special High Voltage." When you enter into a new contract with an electric power company or update a contract, you are requested by the electric power company to submit an accounting statement form.
Table 4 "Input fundamental currents" of general-purpose inverters determined by the nominal applied motors
(1) Scope of regulation In principle, the guideline applies to the customers that meet the following two conditions: • The customer receives high voltage or special high voltage. • The "equivalent capacity" of the converter load exceeds the standard value for the receiving voltage (50kVA at a receiving voltage of 6.6kV).
(2) Regulation method The level (calculated value) of the harmonic current that flows from the customer's receiving point out to the system is subjected to the regulation. The regulation value is proportional to the contract demand. The regulation values specified in the guideline are shown in Table 1.
Table 1 Upper limits of harmonic outflow current per kW of contract demand [mA/kW] Receiving voltage
5th
7th
11th
13th
17th
19th
23th
Over 25th
6.6kV 22kV
3.5 1.8
2.5 1.3
1.6 0.82
1.3 0.69
1.0 0.53
0.90 0.47
0.76 0.39
0.70 0.36
1. Calculation of Equivalent Capacity (Pi) Although the equivalent capacity (Pi) is calculated using the equation of (input rated capacity) x (conversion factor), catalog of conventional inverters do not contain input rated capacities. A description of the input rated capacity is shown below:
(1) "Inverter rated capacity" corresponding to "Pi" • Calculate the input fundamental current l1 from the kW rating and efficiency of the load motor, as well as the efficiency of the inverter. Then, calculate the input rated capacity as shown below: Input rated capacity = 3 x (power supply voltage) x l1 x 1.0228/1,000 [kVA] Where 1.0228 is the 6-pulse converter's value of (effective current) / (fundamental current). • When a general-purpose motor or inverter motor is used, the appropriate value shown in Table 2 can be used. Select a value based on the kW rating of the motor used, irrespective of the inverter type.
Table 2 "Input rated capacities" of general-purpose inverters determined by the nominal applied motors Nominal applied motor[kW]
0.4 0.75 1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
Pi 200V *Inapplicable inverter models 6.77 9.07 13.1 17.6 21.8 25.9 [kVA] 400V 0.57 0.97 1.95 2.81 4.61 6.77 9.07 13.1 17.6 21.8 25.9 Nominal applied motor[kW]
30
37
45
55
75
Pi 200V 34.7 42.8 52.1 63.7 87.2 [kVA] 400V 34.7 42.8 52.1 63.7 87.2 Nominal applied motor[kW]
90
110 132 160 200 220
104 104
127 127
153
183
229
252
250 280 315 355 400 450 500 530 560 630
Pi 200V [kVA] 400V 286
319
359
405
456
512
570
604
638
• Depending on whether an optional ACR (AC REACTOR) or DCR (DC REACTOR) is used, apply the appropriate conversion factor specified in the appendix to the guideline. The values of the converter factor are shown in Table 3.
Table 3 "Conversion factors Ki" for general-purpose inverters determined by reactors
3
0.4 0.75 1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
200V *Inapplicable inverter models 19.1 25.6 36.9 49.8 61.4 73.1 400V 0.81 1.37 2.75 3.96 6.50 9.55 12.8 18.5 24.9 30.7 36.6 6.6kV converted 49 83 167 240 394 579 776 1121 1509 1860 2220 value [mA]
Input fundamental current [A]
Nominal applied motor[kW]
30
37
45
55
75
90
110 132 160 200 220
200V 98.0 121 147 180 245 293 357 400V 49.0 60.4 73.5 89.9 123 147 179 216 258 323 355 6.6kV converted 2970 3660 4450 5450 7450 8910 10850 13090 15640 19580 21500 value [mA]
Input fundamental current [A]
Nominal applied motor[kW]
250 280 315 355 400 450 500 530 560 630
Input fundamental current [A]
200V 400V 403 450 506 571 643 723 804 852 900 1013 6.6kV converted 24400 27300 30700 34600 39000 43800 48700 51600 54500 61400 value [mA]
(2) Calculation of harmonic current Table 5 Generated harmonic current [%], 3-phase bridge (capacitor smoothing) Degree
5th
7th
11th
13th
17th
19th
23th
25th
Without a reactor With a reactor (ACR) With a reactor (DCR) With reactors (ACR and DCR)
65 38 30 28
41 14.5 13 9.1
8.5 7.4 8.4 7.2
7.7 3.4 5.0 4.1
4.3 3.2 4.7 3.2
3.1 1.9 3.2 2.4
2.6 1.7 3.0 1.6
1.8 1.3 2.2 1.4
• ACR: 3% • DCR: Accumulated energy equal to 0.08 to 0.15ms (100% load conversion) • Smoothing capacitor: Accumulated energy equal to 15 to 30ms (100% load conversion) • Load: 100% Calculate the harmonic current of each degree using the following equation: Generated nth harmonic current [%] nth harmonic current [A] = Fundamental current [A] x 100
(3) Maximum availability factor • For a load for elevators, which provides intermittent operation, or a load with a sufficient designed motor rating, reduce the current by multiplying the equation by the "maximum availability factor" of the load. • The "maximum availability factor of an appliance" means the ratio of the capacity of the harmonic generator in operation at which the availability reaches the maximum, to its total capacity, and the capacity of the generator in operation is an average for 30 minutes. • In general, the maximum availability factor is calculated according to this definition, but the standard values shown in Table 6 are recommended for inverters for building equipment.
Table 6 Availability factors of inverters, etc. for building equipment (standard values)
718
(2) Values of "Ki (conversion factor)"
Circuit category
Nominal applied motor[kW]
Circuit type
Conversion factor Ki Main applications Without a reactor K31=3.4 • General-purpose inverters K32=1.8 • Elevators Three-phase bridge With a reactor (ACR) • Refrigerators, (capacitor smoothing) With a reactor (DCR) K33=1.8 air conditioning systems • Other general appliances With reactors (ACR and DCR) K34=1.4
2. Calculation of Harmonic Current (1) Value of "input fundamental current" • Apply the appropriate value shown in Table 4 based on the kW rating of the motor, irrespective of the inverter type or whether a reactor is used. * If the input voltage is different, calculate the input fundamental current in inverse proportion to the voltage.
29
Equipment type
Inverter capacity category
Single inverter availability factor
Air conditioning system
200kW or less Over 200kW
Sanitary pump Elevator Refrigerator, freezer UPS (6-pulse)
50kW or less 200kVA
0.55 0.60 0.30 0.25 0.60 0.60
[Correction coefficient according to contract demand level] • Since the total availability factor decreases if the scale of a building increases, calculating reduced harmonics with the correction coefficient s defined in Table 7 below is permitted.
Contract demand [kW] Correction coefficient 300 500 1000 2000
1.00 0.90 0.85 0.80
Table 7 Correction coefficient according to the building scale *If the contract demand is between two specified values shown in Table 7, calculate the value by interpolation.
(4) Degree of harmonics to be calculated Calculate only the "5th and 7th" harmonic currents.
Lineup Fuji inverter family consisting of wide model variations for various purposes of use Application
Series name (Catalog No.)
Features High-performance, multifunction inverter (Three-phase 200V: 0.2 to 90kW, Three-phase 400V: 0.4 to 400kW)
FRENIC5000G11S (MEH403 for JE) (MEH413 for EN)
• Fuji's dynamic torque vector control has made it possible to achieve 200% starting torque at 0.5Hz. • Loaded with many convenient functions such as automatic tuning. • Compact and full-closed (22kW or smaller), and selectable from wide variations ranging from 0.2 to 400kW.
Inverter best suited for HVAC (Heating, Ventilating, and Air-Conditioning)
[New] FRENIC-Eco (MEH442)
(Three-phase 200V: 0.75 to 110kW, Three-phase 400V: 0.75 to 500kW) • Line/Inverter switching, full PID control functions for optimum fan and pump control • Various functions contributing to energy-saving • Consideration for surrounding environment and global compatibility
Fan/pump drive inverter (Three-phase 200V: 5.5 to 110kW, Three-phase 400V: 5.5 to 500kW)
FRENIC5000P11S (MEH403)
• Developed specifically for variable torque load required to drive funs and pumps. • Energy-saving operation is easy, thanks to automatic energy saving function. • Interactive keypad is standard-equipped for easy operation.
General use for industrial equipment
High-performance compact inverter (Three-phase 200V: 0.1 to 7.5kW, Single-phase 200V: 0.1 to 2.2kW, Three-phase 400V: 0.4 to 7.5kW)
FVR-E11S (MEH404 for JE) (MEH414 for EN)
• Fuji's dynamic torque vector control has made it possible to achieve 200% starting torque at 0.5Hz. • Loaded with many convenient functions such as automatic tuning, slip compensation, torque limit, and 16step speed change. • Various maintenance functions are available; for example, indication of main circuit capacitor life and indication of cumulative operation time. Compact inverter
[New] FRENIC-Mini (MEH441 for Asia) (MEH451 for Europe)
(Three-phase 200V: 0.1 to 3.7kW, Single-phase 200V: 0.1 to 2.2kW, Three-phase 400V: 0.4 to 3.7kW) • Frequency setting dial is standard-equipped for each operation. • Loaded with automatic torque boost, current limit and slip compensation functions, which are best-suited for operating transverse conveyors. • Equipped with automatic energy-saving function and PID control function, which are suitable for driving fans and pumps. High-performance vector control inverter (Three-phase 200V: 0.75 to 90kW, Three-phase 400V: 3.7 to 400kW)
FRENIC5000VG7S (MEH405)
• High-precision inverter that quickly responds to the control signals and has stable torque characteristics. • Abundant functions and various options permit wide application to general industrial systems. • Automatic tuning function allows you to operate general-purpose motors under vector control.
30
31
NOTES In running general-purpose motors • Driving a 400V general-purpose motor When driving a 400V general-purpose motor with an inverter using extremely long cables, damage to the insulation of the motor may occur. Use an output circuit filter (OFL) if necessary after checking with the motor manufacturer. Fuji's motors do not require the use of output circuit filters because of their reinforced insulation.
• Torque characteristics and temperature rise When the inverter is used to run a general-purpose motor, the temperature of the motor becomes higher than when it is operated using a commercial power supply. In the low-speed range, the cooling effect will be weakened, so decrease the output torque of the motor. If constant torque is required in the low-speed range, use a Fuji inverter motor or a motor equipped with an externally powered ventilating fan.
• Vibration Use of an inverter does not increase vibration of a general-purpose motor, but when the motor is mounted to a machine, resonance may be caused by the natural frequencies, including that of the machine system. * The use of a rubber coupling or vibration dampening rubber is recommended. * It is also recommended to use the inverter jump frequency control to avoid resonance points. Note that operation of a 2-pole motor at 60Hz or more may cause abnormal vibration.
• Noise When an inverter is used with a general-purpose motor, the motor noise level is higher than that with a commercial power supply. To reduce noise, raise carrier frequency of the inverter. High-speed operation at 60Hz or more can also result in more noise.
In running special motors • Explosion-proof motors When driving an explosion-proof motor with an inverter, use a combination of a motor and an inverter that has been approved in advance.
• Submersible motors and pumps These motors have a larger rated current than general-purpose motors. Select an inverter whose rated output current is greater than that of the motor. These motors differ from general-purpose motors in thermal characteristics. Set a low value in the thermal time constant of the motor when setting the electronic thermal facility.
• Brake motors For motors equipped with parallel-connected brakes, their braking power must be supplied from the primary circuit (commercial power supply). If the brake power is connected to the inverter power output circuit (secondary circuit) by mistake, problems may occur. Do not use inverters for driving motors equipped with series-connected brakes.
• Geared motors If the power transmission mechanism uses an oillubricated gearbox or speed changer/reducer, then continuous motor operation at low speed may
cause poor lubrication. Avoid such operation.
• Synchronous motors It is necessary to use software suitable for this motor type. Contact Fuji for details.
• Single-phase motors Single-phase motors are not suitable for inverterdriven variable speed operation. Use three-phase motors. * Even if a single-phase power supply is available, use a three-phase motor as the inverter provides three-phase output.
Environmental conditions • Installation location Use the inverter in a location with an ambient temperature range of -10 to 50˚C. The inverter and braking resistor surfaces become hot under certain operating conditions. Install the inverter on nonflammable material such as metal. Ensure that the installation location meets the environmental conditions specified in "Environment" in Common specifications on page 11.
Combination with peripheral devices • Installing a molded case circuit breaker (MCCB) or earth leakage circuit breaker (ELCB) Install a recommended molded case circuit breaker (MCCB) or an earth leakage circuit breaker (ELCB) (with the exception of those exclusively designed for protection from ground faults) in the primary circuit of the inverter to protect the wiring. Ensure that the circuit breaker capacity is equivalent to or lower than the recommended capacity.
• Installing a magnetic contactor (MC) in the secondary circuit If a magnetic contactor (MC) is mounted in the inverter's secondary circuit for switching the motor to commercial power or for any other purpose, ensure that both the inverter and the motor are fully stopped before you turn the MC on or off. Remove the surge sappressor integrated with the MC.
• Installing a magnetic contactor (MC) in the primary circuit Do not turn the magnetic contactor (MC) in the primary circuit on or off more than once an hour as an inverter fault may result. If frequent starts or stops are required during motor operation, use FWD/REV signals.
• Protecting the motor The electronic thermal facility of the inverter can protect the motor. The operation level and the motor type (general-purpose motor, inverter motor) should be set. For high-speed motors or water-cooled motors, set a small value for the thermal time constant to protect the motor, in combination with the "cooling system OFF" signal. If you connect the motor thermal relay to the motor with a long cable, a high-frequency current may flow into the wiring stray capacitance. This may cause the relay to trip at a current lower than the set value for the thermal relay. If this happens, lower the carrier frequency or use the output circuit filter (OFL).
• Discontinuance of power-factor correcting capacitor Do not mount power factor correcting capacitors in the inverter primary circuit. (Use the DC REACTOR
to improve the inverter power factor.) Do not use power factor correcting capacitors in the inverter output circuit. An overcurrent trip will occur, disabling motor operation.
• Discontinuance of surge killer Do not mount surge killers in the inverter secondary circuit.
• Reducing noise Use of a filter and shielded wires are typical measures against noise to ensure that EMC Directives are met. Refer to Appendices, App. A "Advantageous Use of Inverters (Notes on electrical noise)" for details.
• Measures against surge currents If an overvoltage trip occurs while the inverter is stopped or operated under a light load, it is assumed that the surge current is generated by open/close of the phase-advancing capacitor in the power system. * Connect a DC REACTOR to the inverter.
• Megger test When checking the insulation resistance of the inverter, use a 500V megger and follow the instructions contained in the FRENIC-Eco Instruction Manual.
Wiring • Control circuit wiring length When using remote control, limit the wiring length between the inverter and operator box to 20m or less and use twisted shielded cable.
• Wiring length between inverter and motor If long wiring is used between the inverter and the motor, the inverter will overheat or trip as a result of overcurrent (high-frequency current flowing into the stray capacitance) in the wires connected to the phases. Ensure that the wiring is shorter than 50m. If this length must be exceeded, lower the carrier frequency or mount an output circuit filter (OFL).
• Wiring size Select cables with a sufficient capacity by referring to the current value or recommended wire size.
• Wiring type Do not use multicore cables.
• Grounding Securely ground the inverter using the grounding terminal.
Selecting inverter capacity • Driving general-purpose motor Select an inverter according to the applicable motor ratings listed in the standard specifications table for the inverter. When high starting torque is required or quick acceleration or deceleration is required, select an inverter with a capacity one size greater than the standard.
• Driving special motors Select an inverter that meets the following condition: Inverter rated current > Motor rated current
Transportation and storage When transporting or storing inverters, follow the procedures and select locations that meet the environmental conditions listed in the FRENIC-Eco Instruction Manual.
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome Shinagawa-ku, Tokyo 141-0032, Japan Phone: +81-3-5435-7139 Fax: +81-3-5435-7458 Printed on 100% recycled paper
Information in this catalog is subject to change without notice.
Printed in Japan 2003-12 (L03/L03) CM 20 FIS