NOTES: ALTERATIONS WILL NOT REQUIRE THE RELOCATION OF ANY UTILITY, PIPING OR CONDUIT SERVING ANOTHER APARTMENT. PROBE EXG. WALL TO EXPAND CLOSET DEPTH. COORDINATE WITH ARCHITECT IN FIELD
EXG. GIRL'S BATHROOM.
NEW FLOORING WITH FOAM SHEET SOUNDPROOFING. SEE SPECIFICATION MANUAL
EXG. BATHROOM VENT TO REMAIN NEW GRILLE TO BE INSTALLED. SEE SPECIFICATION MANUAL.
CL NEW GIRLS' BATH
1
20 4
2
A-202
EXG. RISERS TO REMAIN TYP.
GIRLS' ROOM
3
S-CO
1
EXG. ELECTRICAL PANEL TO BE RELOCATED. NEW LOCATION TBD.
8"
8 A-508
16
1
4'-111 4"
REFURBISH EXG. DOOR INCLUDING STRIPPING, SANDING AND NEW FINISHES.
A-208
4'-11 4"
15
NEW CL EXG. GUEST BATHROOM. EXG. BATHROOM VENT TO REMAIN NEW GRILLE TO BE INSTALLED. SEE SPECIFICATION MANUAL. NEW SHOWER TO REPLACE EXG. BATH TUB
3
2
17
4
A-207
2
3 A-502
A/C
1 A-403
OFFICE
S-CO
NEW LAUNDRY RM. 4 1
14
1
OPTON B
NEW CL
2'-10"
NEW FLOORING WITH FOAM SHEET SOUNDPROOFING. SEE SPECIFICATION MANUAL.
1
W/D
8'-2"
2
CL
CL
19
7'-41 2"
FURNISH AND INSTALL ALL NEW FINISHES REQUIRED BY BUILDING SPECIFICATIONS DUE TO REMOVAL OF EXISTING DOOR AND PATCHING OF NEW 2 HRS. PARTITION.
3
1'-6"
6'-10"
2'-9"
SLOPE
1 A-401
NEW FOYER
1
2
A-210
A-204
3
OPTON B
2
1
4
CL
4'-212"
NEW CLOSET WITH POCKET DOOR
5
NEW CL 7
FULL HEIGHT MIRROR CABINET. SEE SPECIFICATION MANUAL. NEW FLOORING WITH FOAM SHEET SOUNDPROOFING. SEE SPECIFICATION MANUAL.
LIVING & DINING RM.
CL
5'-13 4"
3 A-501
MASTER BEDROOM
3'-81 2"
11
4
1
4
S-CO
1'-1012"
A-206
3
8 S-CO
1'-1"
GUEST BEDROOM
2'-111 2" 10
2
CL
2'-13 4"
9'-5"
1
1
NEW MILLWORK TO BE INSTALLED. FINAL DESIGN TBD.
A-200
A-201 4
3
1
3 X
REF.
2'-83 8"
1
2
2'-01 2"
ALL CEDAR CLOSET INCLUDING WALLS (PANELS). FINAL DESIGN TBD.
3'-0"
1
1'-518"
A-203
2
KITCHEN
3'-41 4"
CL
4
3'-618"
6'-8"
4
ALL FLOOR FINISHES AND SUB FLOOR TO BE REMOVED TO EXG. SLAB AND PREPARED FOR NEW FLOOR. ALL REQUIRED PERMITS TO BE PULLED BY CONTRACTOR. NOW EXCEPTIONS.
2 A-502
NEW MILLWORK TO BE INSTALLED. FINAL DESIGN TBD. SEE DETAIL #2 A-502 NEW BATH TUB TO REPLACE EXG. NEW TOILET TO TO REPLACE EXG. NEW FLOORING WITH FOAM SHEET SOUND PROOFING. SEE SPECIFICATION MANUAL. NEW THROUGH-THE-WALL AC UNIT SEE DETAIL #1 A-502 NEW SINK TO BE REPLACED EXG. EXG. BEAM TO REMAIN.
DW OPTON B
A/C NEW MILLWORK TO BE INSTALLED FINAL DESIGN TBD. SEE DETAIL #2 A-502
PANTRY
OPTON B
A/C
1 A-402
55 EAST END AVE, NEW YORK, NY 10028 UNIT 11HJ BY:
NO.
DATE
01
08.14.14
ISSUED TO CLIENT FOR REVIEW
NZ
02
08.21.14
ISSUED FOR PRELIMINARY BOARD REVIEW
NZ
03
09.03.14
ISSUED TO CLIENT FOR REVIEW
NZ
04
09.18.14
ISSUED TO CLIENT FOR REVIEW
NZ
05
09.23.14
ISSUED FOR PRICING
NZ
06
10.06.14
ISSUED TO CLIENT FOR REVIEW
NZ
NEW COOLING DRAWER. SEE SPECIFICATION MANUAL
07
10.15.14
ISSUED FOR PRICING
NZ
NEW SHELVES. SEE SPECIFICATION MANUAL
08
10.31.14
ISSUED FOR NYC DOB FILING
NZ
NEW CABLE BOX NEW THROUGH-THE-WALL AC UNIT SEE DETAIL #1 A-502 WALL OVEN AND MICROWAVE. SEE SPECIFICATION MANUAL NEW SUB-ZERO REFRIGERATOR TO BE INSTALLED (TIGHT OF COLUMN). SEE SPECIFICATION MANUAL. NEW MILLWORK TO BE INSTALLED. FINAL DESIGN TBD. SEE DETAIL #2 A-502 WALL TO FUR OUT OF COLUMN FOR THE KITCHEN TV POCKET NEW KITCHEN ISLAND. DESIGN TBD. NEW THROUGH-THE-WALL AC UNIT SEE DETAIL #1 A-502
S-CO
DESCRIPTION
NEW FLOORING WITH FOAM SHEET SOUND PROOFING. SEE SPECIFICATION MANUAL. NEW MILLWORK. DESIGN TBD. CLIENT:
NAFTALI HOLTZ VICTORIA SHUSTERMANN 55 EAST END AVENUE, NEW YORK, NY 10028, UNIT 11HJ
NEW SINK AND DISHWASHER. SEE SPECIFICATION MANUAL.
PROJECT:
A 203
EXG. GAS ROUGHING TO REMAIN EXG. RISERS TO REMAIN TYP.
1
55 EAST END AVENUE
REVISIONS
3
NEW THROUGH-THE-WALL AC UNIT SEE DETAIL #1 A-502
ISSUED FOR NYC DOB FILING
NEW MILLWORK BANQUETTE SEATING. DESIGN TBD.
1
NEW LOCATION OF ELECTRICAL PANEL TO BE FED FROM THE PREVIOUS PANEL WITH THE SAME GAUGE ELECTRICAL WIRING, AS PER BUILDING REQUIREMENT.
A/C
3 A-502
NEW THROUGH-THE-WALL AC UNIT SEE DETAIL #1 A-502 NEW WASHER AND DRYER SEE DETAIL # 1 A-503 (TBD BY BUILDING MANAGEMENT). NEW SINK WITH CORIAN OR SYNTHETIC STONE TOP TO BE INSTALLED. SEE SPECIFICATION MANUAL.
CONTRACTOR AND ARCHITECT TO VERIFY CONDITION AND SUPPORT OF ALL DEMO WALLS WITH PROBE PRIOR TO FULL DEMO. SUPERVISION BY BUILDING ARCHITECT AND / OR RESIDENT MANAGER WILL BE REQUESTED.
EXG. BEAM TO REMAIN.
2
A-205
A/C
3
3'-1 2"
OPTON B
2
1
OPTON B
NEW CL 1
S-CO
2
2'-43 4"
NEW WATERPROOFING. SEE SPECIFICATION MANUAL.
4
1 4'-43 8"
A-209
6 3
A/C
3
GUEST BATH
MASTER BATH
A/C
5
12
1
NEW TOILET TO REPLACE EXG. EXG. RISERS TO REMAIN TYP. NEW DOUBLE SINK TO BE INSTALLED. SEE SPECIFICATION MANUAL. NEW FLOORING WITH FOAM SHEET SOUNDPROOFING. SEE SPECIFICATION MANUAL.
7'-11"
OPTON B
13
2'-33 4"
NEW CL
ENTRY 7 A-501
1'-11 2"
6'-1"
3 A-502
ALL DOOR FRAMES TO BE ENLARGED TO 7'6" HIGH, EXCEPT ENTRY DOOR TO APARTMENT.
NEW MILLWORK TO BE INSTALLED. FINAL DESIGN TBD. SEE DETAIL #2 A-502 NEW ELECTRIC FIREPLACE. SEE SPECIFICATION MANUAL .
S-CO
8 A-501
307 7TH AVENUE, 2204 NEW YORK, NY 10001 p : 212.488.3060 f : 212.488.3062 frank@fparchitectspc.com
ALL STRUCTURAL COLUMNS, BEAMS, WALLS AND MEP RISERS TO REMAIN. PROBE SURVEY AS REQUIRED PRIOR TO ANY WORK.
NEW THROUGH-THE-WALL AC UNIT SEE DETAIL #1 A-502 NEW MILLWORK FINAL DESIGN TBD SEE DETAIL #8 A-501
18
CONTRACTOR TO PROVIDE ARCHITECT WITH PULL TEST RESULTS FOR CEILING ANCHORS.
THE BOTTOM AND/OR TOP SURFACES OF THE FLOOR AND/OR CEILING SLABS ARE NOT TO BE NOTCHED OR CHANNELED OUT TO ACCOMMODATE ANY OF THE WORK BEING DONE.
NEW WINDOW TO BE INSTALLED USING BASF NP1 CAULKING. COORDINATE WITH BUILDING MANAGEMENT CODES IN REGARDS TO WIND FORCES. WINDOW TO MEET OR EXCEED ENERGY CODE U-VALUE. EXG. DRYER VENT TO REMAIN
A/C
NEW SINK TO REPLACE EXG. NEW FLOORING WITH FOAM SHEET SOUNDPROOFING. SEE SPECIFICATION MANUAL. NEW TOILET TO REPLACE EXG.
ARCHITECTURE, INTERIORS & CONSULTING P.C.
ALL PENETRATIONS TO RECEIVE FIRESTOP, DRAFTSTOP, AND FIRE-RESISTANT CLOSURE AT ALL PENETRATIONS, TYP.
NEW MILLWORK TO BE INSTALLED FINAL DESIGN TBD. SEE DETAIL #2 A-502
NEW BATH TUB TO REPLACE EXG.
FRANK PIZZURRO JR., AIA
ANY WORK PERFORMED ON WALLS, CEILINGS AND/OR FLOORS COMMON TO OTHER HABITABLE PUBLIC SPACES OR TO THE EXTERIOR SHALL NOT LOWER THEIR FIRE RATINGS.
55 EAST END AVENUE, NEW YORK, NY 10028 UNIT 11HJ TITLE:
CONSTRUCTION PLAN - 11FL #11HJ
CONSTRUCTION PLAN
Scale: 1/4"=1'-0"
5 OF 33 ARCHITECT SEAL & SIGNATURE
DATE:
08.04.14
PR# SCALE:
CONSTRUCTION LEGEND
CONSTRUCTION NOTES
TO BE VERIFIED IN FIELD BY CONTRACTOR WITH OWNER AND/OR ARCHITECT. SEE NOTE SHEETS FOR CONSTRUCTION SPECIFICATION REQUIREMENTS
1. GENERAL CONTRACTOR TO COORDINATE ALL DETAILS AND DIMENSIONS ON SITE WITH ARCHITECT. 2. ARCHITECT WILL BE AVAILABLE FOR ALL INSPECTIONS AND COORDINATION ITEMS WITH ALL TRADES. 3. DESIGN DETAILS AND SKETCHES WILL BE PROVIDED ON A AS NEEDED BASIS AS APPROVED BY OWNER. 4. CONTRACTOR TO LAYOUT ALL NEW PARTITIONS WITH CHALK FOR APPROVAL BY OWNER AND ARCHITECT BEFORE CONSTRUCTION COMMENCES. 5. ALL MATERIALS TO BE USED ARE TO BE FIRE RETARDANT AS REQUIRED BY NYC CODES. 6. REPLACEMENT OF BATHROOM FIXTURES ONLY; NO ADDED FIXTURES OR NEW LOCATIONS. 7. ALL KITCHEN PLUMBING FIXTURES ARE NEW; NEW COPPER PIPING TO RISER, TYP. 8. PROVIDE ALL SHOP DRAWINGS TO ARCHITECT FOR REVIEW FOR ALL TRADES PRIOR TO FABRICATION. 9. ALL DOORS AND FRAMES TO BE NEW UNLESS NOTED OTHERWISE. SEE DOOR SCHEDULE. GC TO PROVIDE AND VERIFY ALL FRAMED OPENINGS. 10. DOOR FABRICATOR TO VERIFY ALL EXISTING CONDITIONS AND SUBMIT SHOP DRAWINGS FOR REVIEW BY ARCHITECT, TYP.
PARTITION TYPE KEY EXISTING BUILDING WALLS TO REMAIN INDICATES AREA IN SCOPE OF WORK
D1
NEW DOOR SYMBOL SEE SCHEDULE
INDICATES NEW WALL/PARTITION
W
NEW WINDOW SYMBOL SEE SCHEDULE
NEW BUILT-IN MILLWORK
1
AREA TO BE PROBED TO CONFIRM EXISTING CONDITION S-CO
AREAS THAT REQUIRED WATERPROOFING
NEW WALL PARTITION. SEE DETAIL ON SHEET A-500 NEW SMOKE AND CARBON MONOXIDE DETECTOR. (WALL OR CEILING MOUNTED)
11. ALL DIMENSIONS AND OPENINGS FOR ALL DESIGN ELEMENTS TO BE VERIFIED IN FIELD BY GENERAL CONTRACTOR BY UTILIZATION OF THESE DOCUMENTS. NOTIFY ARCHITECT OF CONFLICTS. 12. GC TO COORDINATE ALL MECHANICAL AND PLUMBING DRAWINGS WITH ARCHITECTURAL PRIOR TO ANY PRICING, AND OR CONSTRUCTION. CONTACT ARCHITECT AND ENGINEERS OF ANY DISCREPANCIES PRIOR TO PURCHASING OF ANY CONSTRUCTION ELEMENTS. 13. GC TO READ ALL ARCHITECTURAL AND ENGINEERING NOTES, DETAILS, SPECIFICATIONS, MANUFACTURER'S SPECIFICATION PRIOR TO ANY PRICING AND INSTALLATION. 14. PROVIDE ACCESS DOORS FOR ALL NEW PLUMBING WORK. COORDINATE WITH ARCHITECT FOR LOCATIONS. 15. ALL PLUMBING WORK TO BE PERFORMED BY LICENSED PLUMBER ONLY. 16. ALL ELECTRICAL WORK TO BE PERFORMED BY LICENSED ELECTRICIAN ONLY 17. NO CHOPPING OR CHANNELLING-NAILING OF SLAB, PERIOD.
NOTE TO CONTRACTORS GENERAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING AND DOCUMENTING ALL FINAL MEASUREMENTS FOR BOTH DEMOLITION AND CONSTRUCTION. GENERAL CONTRACTOR TO NOTIFY ARCHITECT AND ALL REQUIRED PARTIES OF ANY DISCREPANCIES ON THE DRAWINGS, OR IN THE FIELD, THAT ARISE AND MAY CAUSE CONFLICT WITH DESIGN INTENT AND/OR PUBLIC SAFETY CONTRACTOR TO PROVIDE ALL NECESSARY CODE AND BUILDING STANDARD PROTECTION AROUND CONSTRUCTION AREAS, BOTH INSIDE AND OUTSIDE BUILDING ALL DIMENSIONS AND OPENINGS FOR ALL DESIGN ELEMENTS TO BE VERIFIED IN FIELD BY GENERAL CONTRACTOR BY UTILIZATION OF THESE DOCUMENTS. NOTIFY ARCHITECT OF CONFLICTS WATERPROOFING TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS UNDERNEATH ALL NEW OR REPLACED FLOOR FINISHES IN KITCHEN AND BATHROOM, TYP. PROVIDE SHUT OFFS AND BACK FLOW PREVENTERS IN ALL PIPE OUT LOCATIONS GREENBOARD TO BE USED IN ALL WET AREAS IN BATHROOM AND KITCHEN, TYP., CEMENT BOARD @ SHOWERS
AS NOTED
DRAWN
NZ
CHECKED
FP
DWG. NO.
A-101.00 CAD FILE NO. D.O.B. EXAMINER APPROVAL STAMP & SIGNATURE
FRANK PIZZURRO JR., AIA ARCHITECTURE, INTERIORS & CONSULTING P.C. 307 7TH AVENUE, 2204 NEW YORK, NY 10001 p : 212.488.3060 f : 212.488.3062 frank@fparchitectspc.com
4"
DRAPERY POCKET AND TRACKING FINISHED CL 8'-3" DROPPED SOFFIT 7'-9"
NEW CROWN MOLDING. SEE SPECIFICATION MANUAL RECESSED PIN LIGHT CHROME WITH WHITE CASING AND TRIM
2'-418"
CONTINUOUS LED LIGHTING TO ILLUMINATE CEILING FROM COVE ELECTRICAL SOLAR SHADES
1 2"
WOOD REVEAL. SEE SPECIFICATION MANUAL FOR DETAILS
1 2"
WOOD REVEAL. SEE SPECIFICATION MANUAL FOR DETAILS 1 2"
WOOD PANELS. SEE SPECIFICATION MANUAL FOR DETAILS
1"
STONE COUNTERTOP. SEE SPECIFICATION MANUAL
FRAME AROUND WINDOW TO BE PAINTED. PAINT TBD
2'-113 8"
NEW 60" TV. WALL MOUNTED GLASS SHELVING.SEE SPECIFICATION MANUAL FOR DETAILS NEW 60" ELECTRIC FIRE PLACE AL CLX 60. SEE SPEC MANUAL
NEW MILLWORK. DESIGN TBD.
ISSUED FOR NYC DOB FILING
81 4"
STONE COUNTERTOP. SEE SPECIFICATION MANUAL
1'-51 4"
NEW THROUGH-THE-WALL AC UNIT SEE DETAIL #1 A-502 EXG. HEAT RADIATOR TO REMAIN
55 EAST END AVENUE
BASEBOARD. SEE SPECIFICATION MANUAL 4"
BASE MODLING. SEE SPECIFICATION MANUAL 1'-1118"
2
1'-103 8"
1'-105 8"
LIVING & DINING ROOM
1'-107 8"
EQ
5'-0"
EQ
EQ
FINISHED FL 0'-00"
55 EAST END AVE,
Scale: 3/4":1'-0"
NEW YORK, NY 10028 UNIT 11HJ REVISIONS BY:
NO.
DATE
DESCRIPTION
01
08.14.14
ISSUED TO CLIENT FOR REVIEW
NZ
02
08.21.14
ISSUED FOR PRELIMINARY BOARD REVIEW
NZ
03
09.03.14
ISSUED TO CLIENT FOR REVIEW
NZ
04
09.18.14
ISSUED TO CLIENT FOR REVIEW
NZ
05
09.23.14
ISSUED FOR PRICING
NZ
06
10.06.14
ISSUED TO CLIENT FOR REVIEW
NZ
07
10.15.14
ISSUED FOR PRICING
NZ
08
10.31.14
ISSUED FOR NYC DOB FILING
NZ
FINISHED CL 8'-3"
EXG. WINDOW TO REMAIN TYP. EXG. WINDOW TO REMAIN TYP. CLIENT:
SOLAR SHADES. SEE SPECIFICATION MANUAL
SOLAR SHADES. SEE SPECIFICATION MANUAL
FRAME AROUND WINDOW TO BE PAINTED. PAINT TBD
FRAME AROUND WINDOW TO BE PAINTED. PAINT TBD
NAFTALI HOLTZ VICTORIA SHUSTERMANN 55 EAST END AVENUE, NEW YORK, NY 10028, UNIT 11HJ PROJECT:
NEW DRAPERY. SEE SPECIFICATION MANUAL
55 EAST END AVENUE, NEW YORK, NY 10028 UNIT 11HJ TITLE:
ELEVATIONS LIVING ROOM
NEW CROWN MOLDING. SEE SPECIFICATION MANUAL
14 OF 33 ACCESS PANEL NEW MILLWORK. DESIGN TBD.
ARCHITECT SEAL & SIGNATURE
DATE:
08.04.14
PR# SCALE:
NEW THROUGH-THE-WALL AC UNIT SEE DETAIL #1 A-502
NEW THROUGH-THE-WALL AC UNIT SEE DETAIL #1 A-502 1'-2"
1'-2"
EXG. HEAT RADIATOR TO REMAIN
EXG. HEAT RADIATOR TO REMAIN
AS NOTED
DRAWN
NZ
CHECKED
FP
DWG. NO.
A-206.00 CAD FILE NO. D.O.B. EXAMINER APPROVAL STAMP & SIGNATURE
FINISHED FL 0'-00"
2
LIVING & DINING ROOM Scale: 3/4":1'-0"
FRANK PIZZURRO JR., AIA ARCHITECTURE, INTERIORS & CONSULTING P.C.
3 A-401
307 7TH AVENUE, 2204 NEW YORK, NY 10001 p : 212.488.3060 f : 212.488.3062 frank@fparchitectspc.com
RECESSED PIN LIGHT CHROME / WHITE CASING AND TRIM PANEL BLOCKING AS REQUIRED 1 2"
REVEAL TO BE STAINED. COLOR TBD.
2 LAYERS OF 58" GYPSUM BOARD FOR SOUND PROOFING. 5 3'- 8" MTL. STUDS 16" O.C.
EXISTING CONCRETE SLAB RECESSED PIN LIGHT CHROME / WHITE CASING AND TRIM 2-1/2" METAL STUD TO BUILD THE SOFFIT.
WOOD PANELING. SEE SPEC MANUAL
4"
LIVING & DINING ROOM - PLAN
1
FINISHED CL 8'-3"
NEW WALL MOUNTED 60' TV
2
Scale: 3/4":1'-0"
DROPPED SOFFIT 7'-11"
A-401
NEW CROWN MOLDING. SEE SPECIFICATION MANUAL EXISTING CMU WALL
4"
DRAPERY POCKET AND TRACKING FINISHED CL 8'-3" DROPPED SOFFIT 7'-9"
NEW CROWN MOLDING. SEE SPECIFICATION MANUAL RECESSED PIN LIGHT CHROME WITH WHITE CASING AND TRIM
ELECTRICAL SOLAR SHADES
1 2"
WOOD REVEAL. SEE SPECIFICATION MANUAL FOR DETAILS
1 2"
2'-113 8"
NEW 60" TV. WALL MOUNTED GLASS SHELVING.SEE SPECIFICATION MANUAL FOR DETAILS NEW 60" ELECTRIC FIRE PLACE AL CLX 60. SEE SPEC MANUAL
WOOD REVEAL. SEE SPECIFICATION MANUAL FOR DETAILS
WOOD PANELING. SEE SPEC MANUAL
1 2"
WOOD PANELS. SEE SPECIFICATION MANUAL FOR DETAILS
PANEL BLOCKING AS REQUIRED 1 2" REVEAL TO BE STAINED. COLOR TBD.
FRAME AROUND WINDOW TO BE PAINTED. PAINT TBD
PANEL MOUNTING CLIP WALL MOUNTING CLIP
55 EAST END AVENUE 55 EAST END AVE, NEW YORK, NY 10028 UNIT 11HJ
1"
STONE COUNTERTOP. SEE SPECIFICATION MANUAL
ISSUED FOR NYC DOB FILING
2'-518"
2'-418"
CONTINUOUS LED LIGHTING TO ILLUMINATE CEILING FROM COVE
REVISIONS
NEW MILLWORK. DESIGN TBD.
1'-51 4"
2'-113 8"
NEW THROUGH-THE-WALL AC UNIT SEE DETAIL #1 A-502 EXG. HEAT RADIATOR TO REMAIN BASEBOARD. SEE SPECIFICATION MANUAL
4"
BASE MODLING. SEE SPECIFICATION MANUAL 1'-1118"
1'-105 8"
LIVING & DINING ROOM
1'-107 8"
5'-0"
EQ
EQ
EQ
NEW WALL MOUNTED 60' TV
Scale: 3/4":1'-0"
STONE SLAB CABINET TOP. SEE SPECIFICATION MANUAL 1 2" REVEILE - FINISHED WOOD. SPEC TBD. CABINET DOOR PULL. SEE SPEC. MANUAL
DATE
4"
DRAPERY POCKET AND TRACKING
01
08.14.14
ISSUED TO CLIENT FOR REVIEW
NZ
02
08.21.14
ISSUED FOR PRELIMINARY BOARD REVIEW
NZ
03
09.03.14
ISSUED TO CLIENT FOR REVIEW
NZ
04
09.18.14
ISSUED TO CLIENT FOR REVIEW
NZ
05
09.23.14
ISSUED FOR PRICING
NZ
06
10.06.14
ISSUED TO CLIENT FOR REVIEW
NZ
07
10.15.14
ISSUED FOR PRICING
NZ
08
10.31.14
ISSUED FOR NYC DOB FILING
NZ
DRAWER TRACKS. SEE SPEC. MANUAL
FINISHED CL 8'-3"
1 2"
DROPPED SOFFIT 7'-9"
REVEILE - FINISHED WOOD. SPEC TBD. CLIENT:
BLOCKING AS REQUIRED
CONTINUOUS LED LIGHTING TO ILLUMINATE CEILING FROM COVE
FINISHED WOOD CABINET SHELF
ELECTRICAL SOLAR SHADES
CABINET DOOR PULL. SEE SPEC. MANUAL
1'-43 4"
2'-418"
NEW CROWN MOLDING. SEE SPECIFICATION MANUAL RECESSED PIN LIGHT CHROME WITH WHITE CASING AND TRIM 1 2"
NAFTALI HOLTZ VICTORIA SHUSTERMANN 55 EAST END AVENUE, NEW YORK, NY 10028, UNIT 11HJ PROJECT:
55 EAST END AVENUE, NEW YORK, NY 10028 UNIT 11HJ
WOOD REVEAL. SEE SPECIFICATION MANUAL FOR DETAILS
4" 2'-113 8"
FRAME AROUND WINDOW TO BE PAINTED. PAINT TBD
1 " 2
DRAWER PANEL. WOOD FINISH TBD NEW 60" TV. WALL MOUNTED GLASS SHELVING.SEE SPECIFICATION MANUAL FOR DETAILS NEW 60" ELECTRIC FIRE PLACE AL CLX 60. SEE SPEC MANUAL
TITLE:
MILLWORK LIVING ROOM
FINISHED FL 0'-00"
FINISHED FLOOR. SEE SPEC. MANUAL SUBFLOOR
21 OF 33 ARCHITECT SEAL & SIGNATURE
BLOCKING AS REQUIRED
1"
STONE COUNTERTOP. SEE SPECIFICATION MANUAL
DESCRIPTION
71 4"
1"
2
1'-103 8"
FINISHED FL 0'-00"
BY:
NO. 81 4"
STONE COUNTERTOP. SEE SPECIFICATION MANUAL
NEW MILLWORK. DESIGN TBD.
1'-51 4"
NEW THROUGH-THE-WALL AC UNIT SEE DETAIL #1 A-502 EXG. HEAT RADIATOR TO REMAIN BASEBOARD. SEE SPECIFICATION MANUAL
4"
BASE MODLING. SEE SPECIFICATION MANUAL 1'-1118"
2A
1'-103 8"
1'-105 8"
LIVING & DINING ROOM Scale: 3/4":1'-0"
1'-107 8"
5'-0"
EQ
EQ
EQ
FINISHED FL 0'-00"
3
LIVNG ROOM - MILLWORK AND WALL SECTION Scale: 1 1/2":1'-0"
08.04.14
PR# SCALE:
81 4"
STONE COUNTERTOP. SEE SPECIFICATION MANUAL
DATE:
AS NOTED
DRAWN
NZ
CHECKED
FP
DWG. NO.
A-401.00 CAD FILE NO. D.O.B. EXAMINER APPROVAL STAMP & SIGNATURE
GENERAL NOTE: 1. GENERAL CONTRACTOR RESPONSIBLE FOR ALL DIMENSIONS, MEANS AND METHODS OF CONSTRUCTION. 2. GENERAL CONTRACTOR TO CONFORM TO STANDARD DETAILS PROVIDED AND RESPONSIBLE FOR MATCHING TO EXISTING CONDITIONS WITH APPROVED EQUAL OR VARIANCES OF THE SPECIFICATIONS BY ARCHITECT, TYPICAL.
CODE SOUND TRANSMISSION SCHEDULE TILE =51-F IIC WOOD = 58-F IIC (STC = D.N.A) BOTH
3.
4.
NOTIFY ARCHITECT AND ALL REQUIRED PARTIES OF ANY DISCREPANCIES ON THE DRAWINGS OR IN THE FIELD THAT ARISE AND MAY CAUSE CONFLICT WITH DESIGN INTENT AND/OR PUBLIC SAFETY. ALL CONSTRUCTION TO BE CONSISTENT WITH NYC BUILDING CODES, TYPICAL.
ARCHITECTURE, INTERIORS & CONSULTING P.C.
2. THE PLYWOOD FASTENERS SHOULD NOT PENETRATE THE SOUND INSULATION. NOTES: 1. ALL BLOCKING AND FRAMING TO BE FIRE RETARDENT AS PER CODE., TYPICAL. 2. CONTRACTOR IS TO VERIFY ALL DIMENSIONS AND ELEMENTS WITHIN CEILING TO BE INDEPENDENTLY SUPPORTED AND FIT WITHIN GIVEN DESIGN REQUIREMENTS. 3. CONTRACTOR IS RESPONSIBLE FOR MATERIALS AND METHODS OF CONSTRUCTION WITHIN LOCAL CODES.
3. THE METHOD OF FASTENING THE PLYWOOD TO THE SLAB IS LIQUID NAILS / CONSTRUCTION GLUE.
CODE SOUND TRANSMISSION SCHEDULE TILE =51-F IIC WOOD = 58-F IIC (STC = D.N.A) BOTH
EXTEND HANGER OFF OF STRUCTURE ABOVE
5
8" CEMENT BOARD, TAPE AND SPACKLE, FINISH AS SPECIFIED.
CLEAR, EXISTING PIPE TO REMAIN
PLITEQ PERIMETER ISOLATION STRIP. NEW TILE, TBD.
6" MIN.
1" = 6"
WOOD FLOORING, SELECTION TBD. APPLIED WITH GLUE NAILS, NOT COMPROMISING TO WATERPROOFING, GENIEMAT SOUNDPROOFING, OR SLAB. LATICRETE HYDRO BAN WATERPROOFING MEMBRANE. (2) 3/8" PLYWOOD FASTENED TO SLAB. 1 2" SOUNDPROOFING IMPACTA REGUPOL UNDERLAYMENT OR EQUAL APPROVED. EXISTING SLAB NOT TO BE CHANNELED. TYP.
SLOPE 1 4" PER 1'-0" TO DRAIN
6"
CODE SOUND TRANSMISSION SCHEDULE
SLOPE 1 4" PER 1'-0" TO DRAIN
MEMBRANE TO RUN ON TOP OF THE SLAB UNDERNEATH THE SHOWER PAN AND CURB LINE OF EXISTING SLAB
6" FRAMELESS 12" THICK FIXED TEMPERED GLASS
3" = 1'-0"
55 EAST END AVE, NEW YORK, NY 10028 UNIT 11HJ REVISIONS NO.
DATE
01
08.14.14
ISSUED TO CLIENT FOR REVIEW
NZ
02
08.21.14
ISSUED FOR PRELIMINARY BOARD REVIEW
NZ
03
09.03.14
ISSUED TO CLIENT FOR REVIEW
NZ
04
09.18.14
ISSUED TO CLIENT FOR REVIEW
NZ
05
09.23.14
ISSUED FOR PRICING
NZ
06
10.06.14
ISSUED TO CLIENT FOR REVIEW
NZ
07
10.15.14
ISSUED FOR PRICING
NZ
08
10.31.14
ISSUED FOR NYC DOB FILING
NZ
Scale: 3"=1'-0"
DESCRIPTION
BY:
CLIENT:
FIXED SHOWER SCREEN HARDWARE, SPEC AND FINISH TO BE SPECIFIED
EXG. WALL
NEW TILE DESIGN TDB.
BLOCKING AS REQ'D.
NAFTALI HOLTZ VICTORIA SHUSTERMANN 55 EAST END AVENUE, NEW YORK, NY 10028, UNIT 11HJ PROJECT:
NICHE - SIZE DEPENDENT ON TILE DESIGN (SIMILAR FOR SHOWER) SEE DETAIL #7 ON A-501 SHEET
NEW TILE, TBD.
55 EAST END AVENUE, NEW YORK, NY 10028 UNIT 11HJ TITLE:
WATERPROOFING ON TOP OF THE SLAB AND TO EXTEND OVER CURB MASONRY CURB MEMBRANE TO RUN ON TOP OF THE SLAB UNDERNEATH THE SHOWER PAN AND CURB
4"
WATERPROOFING MEMBRANE TO RAP AROUND THE NICHE AND GO ALL THE WAY TO THE CEILING DIMENSION VARIES COORDINATE WITH TILE DESIGN MITER CONNECTION AT THE NICHE CORNERS
NEW GLASS SHOWER ENCLOSURE
DOTED LINE INDICATES WATERPROOFING TO EXTEND UP TO THE HEIGHT OF THE SHOWER HEAD AT THE TUB ENCLOSURE WALLS (3 SIDES). IN THE REST OF THE BATHROOM WALLS, INCLUDING SADDLES, WATERPROOFING SHOULD GO UP 4" HIGH FROM THE FINISHED FLOOR. TYP.
BLOCKING AS REQ'D. LATICRETE THINSET 5
CEMENT BOARD, TAPE AND SPACKLE, FINISH AS SPECIFIED
7
8"
BATHROOM NICHE DETAIL Scale: 6"=1'-0"
GENERAL ARCHITECTURAL DETAILS 2
25 OF 33
5/8" PLYWOOD FASTENED TO BLOCKING AS REQUIRED
LEAD PAN IS REQUIRED TO BE COATED IN LIQUID WATERPROOFING BEFORE INSTALLATION SO AS TO PROTECT SAME FROM THE PREMATURE CORROSION AS A RESULT OF BEING EXPOSED TO DAMP MORTAR. LEAD PAN MUST BE WATER TESTED BY FILLING THE PAN WITH WATER, MARKING THE WATER LEVEL, ALLOWING THE WATER TO STAND FOR 12 HOURS, AND THEN DETERMINING IF THE WATER LEVEL HAS DECLINED.
6
55 EAST END AVENUE
TILE =51-F IIC WOOD = 58-F IIC (STC = D.N.A) BOTH
IMPORTANT NOTE: ALL BATHROOM SHOWER CONSTRUCTION TO BE DONE AS PER NYC CODE AND TO COOP STANDARDS AS PER OWNER MANUAL. WATERPROOFING IN ALL WET AREAS AND LEAD SHOWER PAN AT SHOWER, TYPICAL. COORDINATE WITH ARCHITECT AS NEEDED.
SHOWER DETAIL
SHOWER COVE CEILING SECTION
NOTE: ALL BATHROOM SHOWER CONSTRUCTION TO BE DONE AS PER NYC CODE AND TO BLDG. BOARD STANDARDS AS PER OWNER MANUAL. WATERPROOFING IN ALL WET AREAS, TYPICAL. COORDINATE WITH ARCHITECT AS NEEDED.
4"
WATERPROOFING TO GO 6" MIN. UP ALL BATHROOM WALLS. IN SHOWER ENCLOSING WALLS WATERPROOFING TO GO FULL HEIGHT TO THE CEILING. TILE LEAD SHOWER PAN TO EXTEND 6" ABOVE SLAB, MIN.
5
1" = 6"
CEMENT BOARD
ISSUED FOR NYC DOB FILING
TILE UP TO INNER COVE
TYPICAL TILE FLOOR / WALL WATERPROOFING DETAIL
107 8"
2"
WET AREA APPROVED LIGHTING FOR COVE IN SHOWER. "WATERPROOF DIMMABLE SUPER FLAT LED ROPE LIGHT WITH 5050 LEDs", SEE SPEC BOOK CROWN MOLDING USED AS LIGHT REFLECTOR FOR COVE LIGHTING
6"
1
2-1/2" STEEL STUD BRACE 5 8" FINISHED GREEN-BOARD CEILING, SEMI-GLOSS PAINT FINISH (TBD) WATER RETARDENT BLOCKING AND/OR SHIMS AS REQUIRED. MEANS AND METHODS BY CONTRACTOR
EXISTING SLAB TO REMAIN AND NOT BE CHANNELED, TYP.
3
1" = 6"
LATICRETE THINSET. (2) 3/8" PLYWOOD FASTENED TO SLAB WITH GLUE NAILS, NOT COMPROMISING TO GENIEMAT SOUNDPROOFING OR SLAB. 10MM(3/8") RUBBER SHEET SOUNDPROOFING. GENIEMAT RST10. LATICRETE HYDRO BAN WATERPROOFING MEMBRANE ON ALL BATHROOM FLOORS. LATICRETE STRATA MAT UNCOUPLING MEMBRANE.
TBD
2
TYPICAL WOOD FLOOR WATERPROOFING DETAIL
2-1/2" STEEL BRACING TO UNDERSIDE OF SLAB ABOVE AS REQUIRED LATERAL BRACING AS REQUIRED BY CODE 2-1/2" STEEL STUDS 16" O.C. TYP. HANGERS & CARRIERS
1'-0" VIF DROPPED CEILING
WATERPROOFING TO GO 6" MIN. UP ALL BATHROOMWALLS. IN SHOWER ENCLOSING WALLS WATERPROOFING TO GO ALL THE WAY UP TO THE CEILING.
TYPICAL WOOD FLOORING DETAIL
307 7TH AVENUE, 2204 NEW YORK, NY 10001 p : 212.488.3060 f : 212.488.3062 frank@fparchitectspc.com
EXISTING BUILDING SLAB
EXISTING WALL TO REMAIN.
1
FRANK PIZZURRO JR., AIA
8
BATHTUB DETAIL 1-1/2" = 1'-0"
CONTINUOUS WATERPROOFING 4" ABOVE ALL BATHROOM WALLS AND 4" UP ABOVE TUB BASIN (3 SIDES). TYP. 1-1/2" PIPE
ARCHITECT SEAL & SIGNATURE
DATE:
08.04.14
PR# SCALE:
AS NOTED
DRAWN
NZ
CHECKED
FP
DWG. NO.
A-501.00 CAD FILE NO. D.O.B. EXAMINER APPROVAL STAMP & SIGNATURE
X A-XXX
TYP LT-1
LT-1
LT-1
LT-1
LT-1
LT-1
LT-1
LT-1
LT-9
LT-1
LT-1
LT-1
LT-1
X
X
A-XXX
A-XXX
LT-1
LT-1
LT-1
LT-1
LT-1
LT-1
LT-1
23-136
LT-1
LT-9
23-85
23-84
23-86
23-85 X
LT-1
A-XXX
LT-1
LT-1
LT-1
LT-1
LT-1
LT-1
LT-1
LT-1
LT-1
LT-1
LT-1
LT-1
LT-1
LT-10D
LT-1
LT-8
LT-8
LT-8
LT-8
23-137
LT-9
LT-9
LT-1
LT-1
LT-26
LT-1 LT-1
23-02 LT-7
23-141 LT-26A LT-1
X
A-XXX
A-XXX
X
LT-5D
LT-1
23-70
LT-13A
X
23-116
A-XXX
A-XXX
A-XXX
LT-13A LT-13B LT-12
23-70
TYP
23-142 23-142
LT-5F
LT-1B
LT-1
LT-8
LT-7
LT-26
LT-1
A-XXX
X
X
LT-8
LT-1
TYP
LT-1
X
LT-13A
LT-1
23-112
LT-13A
LT-5B
LT-13B LT-12
LT-7 23-112
23-01
LT-1
LT-7
LT-13A LT-13B LT-12
LT-1
LT-1
LT-13A
LEGEND OF DIMMING AND RELATED LIGHTING CONTROL EQUIPMENT SYMBOL DESCRIPTION STANDALONE PRESET DIMMING SYSTEM # INDICATES NUMBER OF ZONES
23-62
LT-9 LT-8
LT-9
23-138
LT-8
LT-8
LT-8 LT-1
AV SYSTEM INTERFACE TO OPERATE WITH STANDALONE DIMMING SYSTEM
LT-1
LT-1
OS
23-05
REMOTE CONTROL STATION CAPABLE OF ACTUATING ALL PRESETS.
LT-10D
23-04
NOTE: 1. ALL LOWERCASE LETTERS INDICATE LIGHTING CONTROL ZONE 2. LIGHTNG CONTROLS SHOWN FOR TYPICAL OFFICES ONLY. ASSUME THE SAME LIGHTING CONTROLS STRATEGY FOR ALL OFFICES OF SIMILAR TYPE.
21 A-910
LT-8
LT-15A
27'-0" 23-59
23-58
23-56
23-55
23-52
WIRED OCCUPANCY SENSOR
23-03
23-51
23-52
23-111
23-110 23-110
23-109 23-109
23-108
23-107
LT-25 7'-6"
OS
23-06
4
23-07
23-08 23-08
23-57
X A-XXX OS 4
A-XXX
LT-9
23-140
OS
4
4
OS OS
X
X
4
A-XXX
X 23-50
LT-1
23-139
LT-1
A-XXX
LT-9
LT-1
12P
LT-1
LT-1
8P OS
OS
TYP
OS
TYP
X A-XXX
0
4'
8'
16'
SCALE: NA
TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 | TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AUTOCAD FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF , OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT.
LT-15
REFER TO LIGHT FIXTURE SCHEDULE ON DRAWINGS A-200.00 & PDF OF LIGHT FIXTURE CUTS FOR MORE INFORMATION
LT-15A
ASSURED GUARANTY 23RD & 24TH FLOORS 1633 BROADWAY NEW YORK, NY 23RD FLOOR REFLECTED CEILING PLAN LT-31
7'-6"
27'-0"
12P
8P
0
4'
8'
16'
SCALE: NA
TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 | TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AUTOCAD FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF , OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT.
ASSURED GUARANTY 23RD & 24TH FLOORS 1633 BROADWAY NEW YORK, NY 23RD FLOOR POWER & COMMUNICATION PLAN
TYP.
TYP.
TYP.
TYP.
1/4" THCK STAINLESS STEEL TRIM @ ALL INTERSECTIONS OF GLASS PANELS, TYP. THROUGH OUT. SCHEDULED ELEVATOR INDICATOR LANTERN LT-13A, TYP.
1'-6" VIF
TYP.
ALIGN 121"
LQ2 FRAME
SCHEDULED ELEVATOR CALL LANTERNS, MT1, ALIGN WITH SCHEDULED BASE SCHEDULED FIRE STROBE GLASS PANEL, GL2 FINISH, TYP. SCHEDULED ELEVATOR LANTERN LT-13B, TYP.
EQ
LQ1 CABINETS WITH WHITE MELAMINE ADJUSTABLE SHELVING, TYP.
121"
4'-7" VIF
(2) EQUAL CABINETS
121"
1 COOR. OPENING 12" W/ SPECS.
COOR. OPENING W/ SPECS.
121"
1 COOR. OPENING 12" W/ SPECS.
3 6
8
9
*
0
*
SCHEDULED ELEVATOR CALL BUTTON & EVACUATION PLAN BY OTHERS. SCHEDULED CARD READER ALIGN
EQ
SCHEDULED DOOR RELEASE
EQ
EQ
ELEVATOR DOOR PAINT, P3
SCHEDULED ELEVATOR INDICATOR LANTERN LT-13A, TYP.
7'-3" VIF
LQ2 FRAME
EQ
ELEVATOR DOOR PAINT, P-3
UNDER CABINET LIGHTING,TYP.
SCHEDULED MICROWAVE
SCHEDULED FAUCET, SINK, & WATER FILTER
2'-6"
ALIGN
COFFEE MACHINE BY VENDOR G.C TO PROVIDE FOR THE WATER LINE AT WALL. TYP. U.O.N. GLASS BACK SPLASH, GL3 SOLID SURFACE COUNTER TOP, SS1
ALIGN
BREAK @ GLASS BACK SPLASH TYP.
7'-1"
SCHEDULED FIRE ALARM
4'-7" VIF
MAX CEILING HEIGHT
1 1'-9" 12"
121"
SCHEDULED ELEVATOR CALL LANTERNS, MT1, ALIGN WITH SCHEDULED BASE SCHEDULED FIRE STOBE SCHEDULED ELEVATOR CALL BUTTON & EGRESS SIGN, BY OTHERS. SCHEDULED ELEVATOR LANTERN LT-13B, TYP.
(5) EQUAL CABINETS
OVERHEAD CABINETS, LQ1 WITH ADJUSTABLE SHELVING
1'-6" VIF
1/4" THCK STAINLESS STEEL TRIM @ ALL INTERSECTIONS OF GLASS PANELS, TYP. THROUGH OUT.
221" SCHEDULED METAL BASE, TYP.
121"
(2) EQUAL CABINETS
7'-3" VIF
TYP.
EQ
2 5
7
EQ
EQ
FURNITURE TABLES BY OTHERS
1 4
2'-5" VIF
3'-4"
TYP.
SCHEDULED FLOOR WARDEN PHONE
EQ
7'-1"
EQ
OPEN TO BEYOND
MILLWORK, REFER TO SHEET A-922 BANQUETTE BACK, FA-1 / SEAT, FA-2, / SEATBASE, LQ2 / BANQUETTE BASE, MT2
MAX CEILING HEIGHT
SCHEDULED REFRIGERATORS, TYP.
2'-5" VIF
2'-10"
SCHEDULED RECYCLE & WASTE BASKETS. TYP. GLASS PANEL, GL1 FINISH, TYP. 221" SCHEDULED METAL BASE
SCHEDULED DISH WASHER SCHEDULED ICE MAKER LOWER CABINETS, LQ1 WITH ADJUSTABLE SHELVING 2 EQUAL DOORS
COOR. OPENING W/ SPECS.
1'-5" VIF
1'-10"
3'-0" HOLD
1'-10"
2 EQUAL DOORS
4"
TYP. (7) EQUAL PANELS @ 4' MAX
GLASS FRONT WALL SYSTEM
GLASS FRONT WALL SYSTEM
4'-0" MAX TYP.
(3) EQUAL PANELS
GLASS FRONT WALL SYSTEM
GLASS FRONT WALL SYSTEM
(3) EQUAL PANELS
GLASS FRONT WALL SYSTEM
GLASS FRONT WALL SYSTEM
WOOD PANELS, WD-1, TYP.
WOOD PANELS, WD-1, TYP.
221" METAL BASE, MT2. TYP.
221" METAL BASE, MT2. TYP.
SHADE POCKET, TYP. TYP.
IN-WALL BOX & SWING ARM. SEE AV DRAWINGS, TYP. TV IN RECESSED LQ2 NICHE, TYP. FABRIC WRAPPED PANELS, WC3, TYP.
TYP.
IN-WALL BOX & SWING ARM. SEE AV DRAWINGS, TYP.
FLAT SCREEN REFER TO A/V DRAWINGS
FLAT SCREEN REFER TO A/V DRAWINGS
TV IN RECESSED LQ2 NICHE, TYP.
6'-4" VIF
1/2" X 1/4" POLISHED STAINLESS STEEL, MT2 TRIM TYP.
1'-8"
MILLWORK FLOATING CREDENZA AT WALL. PROVIDE FOR METAL OUTRIGGERS AT WALL. SEE CONSTRUCTION PLANS AND DETAILS FOR MORE INFORMATION. TOP, GL6 / REVEAL, MT2 / CASE, LQ2 / INTERIOR PL1
6'-4" VIF
WC3 FABRIC WRAPPED PANELS, TYP.
FLAT SCREEN REFER TO A/V DRAWINGS
GLASS FRONT WAL SYSTEM, TYP.
SCHEDULED CAM. REFER TO AV DWGS
B3 WOOD BASE, TYP. 10"
B3 BASE, TYP.
(5) EQUAL PANELS
(3) EQUAL PANELS
SHADE POCKET, TYP.
(3) EQUAL PANELS
SHADE POCKET, TYP. TYP.
IN-WALL BOX & SWING ARM. SEE AV DRAWINGS, TYP. TV IN RECESSED LQ2 NICHE, TYP. WC3 FABRIC WRAPPED PANELS, TYP.
WC3 FABRIC WRAPPED PANELS, TYP.
FLAT SCREEN REFER TO A/V DRAWINGS
WC3 FABRIC WRAPPED PANELS. TYP.
SCHEDULED PAINT
FLAT SCREEN REFER TO A/V DRAWINGS
FLAT SCREEN REFER TO A/V DRAWINGS
IN-WALL BOX & SWING ARM. SEE AV DRAWINGS, TYP.
1/2" X 1/4" MT2 POLISHED STAINLESS STEEL TRIM TYP.
SCHEDULED CAM, TYP. REFER TO AV DWGS
AV RACK. REFER TO AV DRAWINGS, TYP.
AV RACK. REFER TO AV DRAWINGS, TYP. (5) EQUAL PANELS
(5) EQUAL CABINETS
6'-7"
MILLWORK FLOATING CREDENZA AT WALL. PROVIDE FOR METAL OUTRIGGERS AT WALL. SEE CONSTRUCTION PLANS AND DETAILS FOR MORE INFORMATION. TOP, GL6 / REVEAL, MT2 / CASE, LQ2 / INTERIOR PL1
TYP.
TPG ARCHITECTURE, LLP SCHEDULED CAM, TYP. REFER TO AV DWGS
1'-8"
MILLWORK FLOATING CREDENZA AT WALL. PROVIDE FOR METAL OUTRIGGERS AT WALL. SEE CONSTRUCTION PLANS AND DETAILS FOR MORE INFORMATION. TOP, GL6 / REVEAL, MT2 / CASE, LQ2 / INTERIOR PL1
(5) EQUAL PANELS
(2) EQUAL PANELS
B3 WOOD BASE, TYP.
B3 WOOD BASE, TYP.
31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 | TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AUTOCAD FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF , OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT.
B3 WD BASE, TYP. 10"
6'-4" TYP.
1/2" X 1/4" MT2 POLISHED STAINLESS STEEL TRIM TYP.
ASSURED GUARANTY 23RD & 24TH FLOORS SHADE POCKET, TYP.
SHADE POCKET, TYP.
1633 BROADWAY NEW YORK, NY
TYP.
ELEVATIONS WC3 FABRIC WRAPPED PANELS, TYP. WC3 FABRIC WRAPPED PANELS, TYP.
SCHEDULED PAINT
1/2" X 1/4" MT2 POLISHED STAINLESS STEEL TRIM TYP.
AV RACK. REFER TO AV DRAWINGS, TYP.
B3 WD BASE, TYP.
(5) EQUAL PANELS
1'-8"
(7) EQUAL CABINETS
10"
MILLWORK FLOATING CREDENZA AT WALL. PROVIDE FOR METAL OUTRIGGERS AT WALL. SEE CONSTRUCTION PLANS AND DETAILS FOR MORE INFORMATION. TOP, GL6 / REVEAL, MT2 / CASE, LQ2 / INTERIOR PL1
(5) EQUAL PANELS
B3 WD BASE, TYP.
SIM
TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 | TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AUTOCAD FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF , OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT.
ASSURED GUARANTY 23RD & 24TH FLOORS 1633 BROADWAY NEW YORK, NY
PARTITION SCHEDULE
TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 | TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AUTOCAD FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF , OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT.
ASSURED GUARANTY 23RD & 24TH FLOORS 1633 BROADWAY NEW YORK, NY
CEILING DETAILS
D08
WOMENS ROOM 33-03
D04 D01
INDICATES AREA NOT IN CONTRACT D01
MENS ROOM 33-04
D03 D05
D04
D03
D08
D05
INDICATES EXISTING DOOR/FRAME TO REMAIN, REFER TO DOOR SCHEDULE DRAWING(S).
D06 D07
D06
INDICATES KEY NOTE REFERENCE, SEE PLAN NOTED FOR FURTHER INFORMATION
X
D07
33-02
D02
INDICATES EXISTING WALLS TO REMAIN
D02
INDICATES EXISTING WALLS TO BE DEMOLISHED
33-05
INDICATES EXISTING MILLWORK TO BE DEMOLISHED
D02
INDICATES EXISTING ITEMS TO BE DEMOLISHED/REMOVED
INDICATES EXISTING VINYL FLOOR AND ADHESIVE TO BE REMOVED.
N N
INDICATES EXISTING PORCELAIN FLOOR AND THINSET TO BE REMOVED DOWN TO EXG. SLAB.
AREA OF WORK
INDICATES EXISTING SADDLE TO BE REMOVED TO EXG. SLAB
N
INDICATES NORTH
INDICATES ROOM/AREA INDICATES SPACE NUMBER D08
D04
INDICATES TRANSITION OF FLOOR FINISH
WALL DUPLEX ELECTRICAL RECEPTACLE
D02 D01
MENS ROOM 33-06
D03
33-07
D05 D06 D07
(E)
EXISTING ITEM TO REMAIN
(D)
EXISTING ITEM TO BE REMOVED
(R)
EXISTING ITEM TO BE RELOCATED
D04
N
D08
D01
G.C. TO REMOVE ALL EXISTING PLUMBING FIXTURES. CAP PLUMBING LINES AT SOURCE IN EXISTING RESTROOMS. EXG. ROUGH INS ARE TO REMAIN AND TO BE USED FOR NEW PLUMBING FIXTURES.
D02
G.C. TO REMOVE EXISTING MILLWORK
D03 D04
WOMENS ROOM 33-09
D04 D01 D03 D05
D04
D06 D07
D02
G.C. TO REMOVE EXISTING WALL FINISHES, FLOOR FINISHES, ALL ACCESSORIES (MIRRORS, PAPER TOWEL/TRASH DISPENSARY, ETC.), LAVATORY SINKS, WATER CLOSET & THEIR PARTITIONS, URINALS, FLUSH VALVES, ETC.. NOTE: 1) DEMOLISH WALL & FLOOR FINISH ONLY DOWN TO SUBSTRATE. EXISTING DOORS & FRAMES: PATCH, REPAIR, & PROVIDE SMOOTH FINISH SURFACE. STRIPPED OF EXIST. PAINT. DOORS & FRAMES TO BE BONDOED, SANDED, AND PREPPED TO LIKE NEW CONDITION TO RECEIVE NEW FINISH. NOTE: DOOR FRAMES TO REMAIN IN PLACE, AND NOT REMOVED.
D02
TPG ARCHITECTURE, LLP D05
33-08
D06
N D07
1.
REFER TO DRAWING G-001, G-002, G-003 FOR ADDITIONAL NOTES AND SPECIFICATIONS.
2.
THE DEMOLITION CONTRACTOR IS RESPONSIBLE FOR FAMILIARIZING THEMSELVES WITH THE BUILDING RULES AND REGULATIONS BEFORE AND DURING THE COURSE OF THIS PROJECT. SHOULD A CONFLICT ARISE BETWEEN THE CONTRACT DOCUMENTS AND THE BUILDING RULES, THE CONTRACTOR IS TO NOTIFY THE ARCHITECT IMMEDIATELY. BUILDING RULES AND REGULATIONS SHALL GOVERN EXCEPT WHERE THEY ARE IN CONFLICT WITH APPLICABLE CODES AND ORDINANCES.
(C) THE CONTRACTOR IS RESPONSIBLE TO PROTECT ALL EXISTING ITEMS TO REMAIN THROUGHOUT THE COURSE OF DEMOLITION AND CONSTRUCTION. (D) THE CONTRACTOR MUST PROVIDE ALL REQUIRED PROTECTION TO ALL SURROUNDING AREAS THROUGHOUT THE COURSE OF DEMOLITION AND CONSTRUCTION. THERE IS TO BE NO DUST INFILTRATION BETWEEN EXISTING AND EXISTING ADJACENT AREAS. (E) PROVIDE PROTECTION ALONG PATH FROM FREIGHT ELEVATOR TO WORK AREA. PROVIDE MASONITE AT FLOOR AND PLASTIC COVERING AT WALLS, MINIMUM 4' AFF.
13.
14. 3.
4.
GENERAL CONTRACTOR IS TO COORDINATE ALL PHASES OF DEMOLITION FOR THIS PROJECT AND NOTIFY THE ARCHITECT OF ANY DISCREPANCIES OR CONFLICTING CONDITIONS WHICH WOULD INTERFERE WITH THE SATISFACTORY COMPLETION OF THE WORK, PRIOR TO THE START OF DEMOLITION. A) GENERAL CONTRACTOR IS RESPONSIBLE FOR DEMOLITION AND REMOVAL OF ALL DEBRIS AND DISCARDED MATERIALS AND/OR EQUIPMENT AS INDICATED WITHIN THE SPACE. B) GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL OF MATERIALS FROM BUILDING PREMISES ON A DAILY BASIS. DO NOT MIX CONSTRUCTION DEBRIS WITH THAT OF BUILDING OCCUPANTS. C) IMMEDIATELY CLEAN AND REMOVE ALL DEBRIS FROM PUBLIC CORRIDORS AND LOBBIES AFTER DEMOLITION OPERATION AND BEFORE COMMENCEMENT OF THE NORMAL WORK DAY.
8.
9.
10. 5.
G.C. TO SCRAPE FLOOR SLAB TO ELIMINATE HIGH POINTS. G.C. TO WALK SPACE AND INCLUDE ALL NECESSARY WORK REQUIRED FOR PREP, INCLUDING PATCHING, IN BID.
6.
NOISE: (A) ALL MAJOR DEMOLITION AND NOISE CREATING WORK SHALL BE COORDINATED WITH BUILDING MANAGEMENT FOR ALLOWABLE HOURS OF OPERATION (B) THE FOLLOWING WORK, IN WHICH THE LANDLORD IS TO BE NOTIFIED IN ADVANCE, MUST BE DONE ON OVERTIME AND NOT DURING NORMAL BUSINESS HOURS: 1. DEMOLITION, WHICH PER BUILDING MANAGER'S JUDGEMENT MAY CAUSE DISRUPTION TO OTHER TENANTS. 2. WORK PERFORMED OUTSIDE OF TENANTS PREMISES. 3. OTHER ACTIVITIES THAT, IN BUILDING MANAGER'S JUDGEMENT, MAY DISTURB BLDG. OCCUPANTS.
11.
7.
PROTECTION: (A) THE CONTRACTOR IS TO CONFIRM BEFORE THE START OF DEMOLITION WHICH ITEMS ARE TO BE SAVED FROM DEMOLITION. THE CLIENT TO DIRECT CONTRACTOR TO EITHER PROTECT THESE ITEMS OR REMOVE TO STORAGE. (B) THE CONTRACTOR IS TO CONFIRM WITH THE CLIENT BEFORE THE START OF DEMOLITION WHICH ITEMS INDICATED ON THE DRAWINGS ARE DEEMED TO BE NOT REQUIRED BY THE CLIENT AND ARE TO BE REMOVED FROM THE SITE.
12.
A) ALL UNUSED PLUMBING, SHEET METAL DUCTS, AND EQUIPMENT LINES MUST BE REMOVED AND CAPPED AT THE MAIN RISER OR BRANCH CONNECTION. B) ALL BUILDING SHUTDOWNS - ELECTRICAL, PLUMBING, HVAC EQUIPMENT, FIRE AND LIFE SAFETY (CLASS "E") SYSTEM- MUST BE COORDINATED WITH BUILDING MANAGEMENT IN ADVANCE. POWER: REMOVE EXG. POWER/DATA COVER PLATES, RECEPTACLES, TELEPHONE & DATA OUTLETS, ETC, U.O.N.. EXISTING BACKBOXES, & POWER TO BE CUT AND CAPPED AT SOURCE, U.O.N. GC TO V.I.F. COUNT OF DATA/RECEPTACLES AND PROVIDE IN SCOPE OF WORK. THE CONTRACTOR SHALL HAVE AN ELECTRICIAN ON PREMISES DURING DEMOLITION AFFECTING ELECTRICAL LINES IN AREA OF WORK AND ADJACENT SPACES, WITHOUT EXCEPTION. PLUMBING: (A) VERIFY EXISTING PLUMBING LINES TO REMAIN WITH ARCHITECT PRIOR TO ANY REMOVALS. (B) CONTRACTOR TO PROBE ALL PIPING PRIOR TO ANY REMOVAL TO INSURE THAT NO OPERATIONS ARE INADVERTENTLY INTERRUPTED. USE PINHOLE PROBES. (C) CONTRACTOR IS RESPONSIBLE FOR ANY AND ALL WATER DAMAGE. (D) CAP ALL RELATED PIPING BEHIND WALLS TO REMAIN OR BELOW FLOOR SURFACE. (E) REMOVE AND/OR RELOCATE EXISTING PLUMBING LINES AS REQUIRED FOR NEW WORK. GC TO VERIFY IN FIELD PARTITIONS: (A) REMOVE ALL PARTITIONS IN THEIR ENTIRETY, WHERE INDICATED, INCLUDING GYPSUM WALL BOARD, PLASTER WALLS, METAL PARTITIONS. IT SHOULD BE NOTED THAT CONTRACTOR TO TAKE EXTRA CARE TO PROTECT EXISTING CORE WALLS, DOORS, FRAMES AND HARDWARE. (B) REMOVE ALL ASSOCIATED STUDS, TRACKS, FINISHES, ETC... AT PARTITIONS REMOVED.
DOORS AND FRAMES: A) ALL EXISTING DOORS, FRAMES, AND ASSOCIATED HARDWARE ARE TO REMAIN, U.O.N. B) DEMOLITION CONTRACTOR SHALL NOT REMOVE BUILDING CORE DOORS, INCLUDING BUT NOT LIMITED TO FIRE EXIT DOORS, ELEVATOR DOORS, ELEVATOR HOISTWAY ACCESS DOORS, SHAFT ACCESS DOORS, ETC...UNLESS OTHERWISE NOTED. COORDINATE WITH BUILDING MANAGEMENT AND CLIENT. GENERAL CONTRACTOR IS TO COORDINATE WITH BUILDING MANAGEMENT THE USE OF ELEVATORS AND SERVICES, AND TO CONFORM TO ALL BUILDING REGULATIONS WITH REGARD TO DEMOLITION.
D08
FIRESTROBE BACKBOX TO REMAIN. NEW FRONT FACE FIXTURE ONLY TO BE REPLACED. G.C. TO SUPPLY & INSTALL NEW FRONT FACE.
31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 | TPGARCHITECTURE.COM
GC TO CAREFULLY SURVEY & NOTE THE LOCATIONS AND DIMENSIONS OF ALL EXISTING WALLS PRIOR TO DEMOLITION FOR RE-CREATION IN CONSTRUCTION PHASE. THEN PROCEED WITH REMOVE ALL EXISTING WALL FINISHES, EXISTING SUBSTRATE, AND THEIR ASSOCIATED COMPONENTS, BUT NOT TO DAMAGE EXISTING CORE WALLS (WHEN THEY ARE EXISTED). PROTECT OTHER ENGINEERING DEVICES, ESPECIALLY EXISTING ROUGH-IN PLUMBING AS REQUIRED.
IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT.
CAREFULLY REMOVE EXISTING FLOOR FINISHES. PATCH, REPAIR EXISTING SLAB WHERE IT AFFECT BY DEMOLITION. RE-BUILT/IN-FILL ALL HOLES, DEFORMS ON EXISTING CONCRETE SLAB W/ NEW CONCRETE TO ITS ORIGINAL FIRE RATING, THICKNESS, & STRUCTURAL INTEGRITY. PROVIDE FLOOR LEVELNESS AND WATER PROOFING AS REQUIRED FOR INSTALLATION OF NEW FLOOR FINISHES. COORDINATE WITH BUILDING LAND LORD FOR ACCESS /SCHEDULE TO PERFORM WORK AT THE FLOOR BELOW AND PROVIDE ALL PROTECTIONS AS REQUIRED.
PROJECT
G.C. TO REMOVE EXG. CARPET AND TRANSITION TRIM DOWN TO SUBSTRATE & PREP TO RECIEVE NEW SADDLE AS REQUIRED
DRAWING
MORGAN STANLEY 1633 BROADWAY NEW YORK, NY 11210
PARTIAL RESTROOM DEMOLITION PLANS DATE
06/13/2016
PROJECT NO.
1516589-00
SCALE CAD FILE NO.
PAGE NO. OF 19
DWG NO.
C
INSIDE CABINET DIMENSIONS. B INDICATES AREA NOT IN CONTRACT
33-00 INDICATES KEY NOTE REFERENCE, SEE PLAN NOTED FOR FURTHER INFORMATION
X
CL OF HANDLE
INDICATES EXISTING WALLS TO REMAIN INDICATES NEW WALL
ADA COMPLIANT, FLAT TRIM FIRE EXTINGUISHER CABINET BY LARSEN'S SERIES: ARCHITECTURAL MODEL: SS-2409-R2 DOOR STYLE: VERTICAL SOLID DOOR AND TRIM. REFER TO CONSTRUCTION PLAN FOR COLOR FINISH.
FEC INDICATES NEW MILLWORK
33-01 N
1
A-701.00
NEW FIRE EXTINGUISHER & CABINET, REFER TO CONSTRUCTION PLAN FOR SPECIFICATION. (FOLLOW MANUFACTURER'S INSTRUCTIONS FOR INSTALLATION)
F.E. CABINET DIMENSIONS: ROUGH OPENING SIZE: 241 2"H X 10"W X 61 4"D.
INDICATES EXG. MILLWORK
INDICATES NORTH
INDICATES ROOM/AREA INDICATES SPACE NUMBER
2
N
AREA OF WORK
FRONT OF FACE TO ALIGN
VM1
VM2 SD REF
INSIDE DEPTH DIMENSION.
MW
TD
IH FA
X
INDICATES VIEW NUMBER
X
INDICATES SHEET NUMBER
X
INDICATES EQUIPMENT TAG, REFER TO SHEET A-701 FOR EQUIPMENT LEGEND.
SK REF2
CM
CM
CMER
WF
44" AFF GFI
IM
(R)
PROVIDE METAL STUDS AS REQ'D. 44" AFF GFI 44" AFF GFI 44" AFF GFI (R) (R) (R)
(R)
2 1/2" METAL STUDS, 16" O.C. (MAX.) EXG. SHEETROCK WALL PARTITION.
NEW PARTITION TYPE, REFER TO CORRESPONDING PARTITION TYPE ON SHEET A-902.00
N
GFI
WALL DEDICATED GROUND FAULT INTERRUPTER DUPLEX ELECTRICAL RECEPTACLE NEW WALL DUPLEX ELECTRICAL RECEPTACLE
SK
FA
DESCRIPTION: PANTRY SINK MANUFACTURER: ELKAY MODEL: ECTSRAD25266BG CROSSTOWN STAINLESS STEEL SINGLE BOWL SINK NOTE: PROVIDE DRAIN FITTIN DESCRIPTION: PANTRY FAUCET MANUFACTURER: KOHLER MODEL: PURIST K-7505 CP NOTE: PROVIDE MFR'S DRAIN COVER
REF
REF2
DESCRIPTION: FRIDGE & FREEZER MANUFACTURER: GE MONOGRAM MODEL (FREEZER ON BOTTOM) MODEL: ZICS360NXLH/RH NOTE:
DESCRIPTION: UNDER COUNTER DRAWER FRIDGE MANUFACTURER: SUMMIT MODEL: SP6DS2D7ADA NOTE: STAINLESS STEEL FINISH
REC
REC2
DESCRIPTION: PULL OUT RECYCLE BASKET MANUFACTURER: TBD MODEL: TBD NOTE:
(E)
EXISTING ITEM
(R)
EXISTING ITEM RELOCATED
DESCRIPTION: PULL OUT RECYCLE BASKET MANUFACTURER: TBD MODEL: TBD NOTE:
X
INDICATES EQUIPMENT TAG, REFER THIS SHEET FOR ADDITIONAL INFO
A-701.00
IH
DESCRIPTION: PANTRY INSTANT HOT MANUFACTURER: INSINKERATOR MODEL: F-H3300-SST-FLTR NOTE: G.C. TO PROVIDE (3) ADDITIONAL FILTERS
IM
DESCRIPTION: COUNTERTOP ICE AND WATER DISPENSER MANUFACTURER: FOLLET SYMPHONY PLUS MODEL: 12CI425A-L NOTE: G.C. TO PROVIDE WATER LINE
VM1
44" AFF GFI 44" AFF GFI
(R) 44" AFF GFI
INDICATES TRANSITION OF FLOOR FINISH
6 01
DESCRIPTION: VENDING MACHINE MANUFACTURER: MODEL: NOTE: LOCATED IN PANTRY 33-01, SUPPLIED BY TENANT
33-11
IM
CM
CM
FULLY RECESSED TRIMLESS FIRE EXTINGUISHER AND CABINET:
CMER
02
SD
SK IH
SD
WF
DESCRIPTION: SOAP DISPENSER MANUFACTURER: AMERICAN SPECIALTIES, INC (ASI GROUP) MODEL: EZ FILL TOP-FILL MULTI-FEED SOAP DISPENSING SYSTEM NOTE:
DESCRIPTION: WATER FILTER MANUFACTURER: AQUA-PURE MODEL: AP-117 NOTE:
FA CM
DESCRIPTION: COFFEE MAKER MANUFACTURER: FLAVIA MODEL: C500 NOTE: SUPPLIED BY TENANT; G.C. TO PROVIDE WATER LINE
DESCRIPTION: COFFEE MERCHANDISER CMER MANUFACTURER: FLAVIA MODEL: NOTE: SUPPLIED BY TENANT
VM2
VM3
DESCRIPTION: VENDING MACHINE MANUFACTURER: MODEL: NOTE: LOCATED IN PANTRY 33-01, SUPPLIED BY TENANT
MW
TR
DESCRIPTION: PULL OUT WASTE BASKET MANUFACTURER: TBD MODEL: TBD NOTE:
TD
FIRE EXTINGUISHER: LARSEN'S. MODEL MP10. G.C. TO ENSURE PROPER PARTITION DEPTH TO ACCOMMODATE F.E.C. SEE DETAIL 1 ON THIS SHEET FOR MORE INFORMATION.
44" AFF GFI
R
4
MW
04
5 DESCRIPTION: MICROWAVE MANUFACTURER: GE PROFILE MODEL: PEB7226SF NOTE: INCLUDE 30" DELUXE TRIM KIT
TD
33-10
DESCRIPTION: VENDING MACHINE MANUFACTURER: MODEL: NOTE: LOCATED IN PANTRY 33-10, SUPPLIED BY TENANT
FEC
WF
DESCRIPTION: TOWEL DISPENSER MANUFACTURER: MODEL: NOTE: SUPPLIED BY TENANT
FIRE EXTINGUISHER CABINET: LARSEN'S MODEL: SS-2409-R2, WHITE FINISHED CABINET DOOR, SOLID, ALUMINUM, 3/4" PLASTER STOP TRIMLESS, HORIZONTAL LETTERING STYLE "SILVER" DIE CUT LETTERING STYLE.
01
INDICATES NEW GYP. BD. HEADER ABOVE W/ WOOD BLOCKING
02
NEW DOOR & HARDWARE SUPPLIED BY G.C.. REFER TO ELEVATION FOR ADDITIONAL INFORMATION.
03
NEW HOLLOW METAL FRAMED 3'-0" OPENING IN EXISTING PARTITON, REFER TO DETAILS 3 & 4 ON SHEET A-803
3
A-701.00
(R)
VM3
REF
04 03
N
G.C. TO PATCH EXG. COLUMN TO LIKE NEW CONDITION TO ACCEPT NEW FINISH.
TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 | TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. PROJECT
MORGAN STANLEY 1.
REFER TO DRAWINGS G-001.00, G-002.00. G-003.00, FOR ADDITIONAL NOTES AND SPECIFICATIONS.
2.
CONTRACTOR SHALL REVIEW AND INCLUDE ALL NOTES ON DWGS. IN THIS SET OF CONSTRUCTION DOCUMENTS. THIS INCLUDES BEING FAMILIAR WITH ALL GENERAL NOTES WHICH APPLY DIRECTLY TO ANY AND ALL TRADES. EACH SUBTRADE WILL BE RESPONSIBLE FOR REVIEWING THE ENTIRE SET OF DRAWINGS AND NOTING THEIR WORK AS APPLICABLE. ALL WORK INDICATED OR INFERRED ON THE DRAWINGS WILL BE DEEMED AND INCLUDED IN ALL CONTRACTOR'S COSTS.
3.
4.
5.
6.
11.
12.
GENERAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING DIMENSIONS IN FIELD.
13.
GENERAL CONTRACTOR SHALL LAY OUT PARTITIONS STARTING FROM CONDITIONS WHERE ALIGNMENT WITH EXISTING CONSTRUCTION IS SHOWN.
CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF ALL ITEMS TO REMAIN THROUGH THE ENTIRE COURSE OF DEMOLITION & CONSTRUCTION (INCLUDING, BUT NOT LIMITED TO, PARTITIONS, FINISHES, DOORS, FRAMES, HARDWARE & ELECTRICAL CIRCUITRY). CONTRACTOR SHALL REPAIR &/OR REPLACE ANY DAMAGE WHICH MIGHT OCCUR.
14.
GENERAL CONTRACTOR TO SUBMIT SHOP DRAWINGS TO ARCHITECT'S OFFICE FOR REVIEW & APPROVAL PRIOR TO THE FABRICATION OF ALL ITEMS OF FINISH WORK: LIGHTING FIXTURE, METAL + GLASS PARTITIONS, CEILING MILLWORK, ETC.
FOR ALL EXISTING CONSTRUCTION, GC SHALL MAKE ALL NECESSARY REMOVALS & PATCH, LAMINATE, OR RE-FURR AS NECESSARY ANY DAMAGE PARTITIONS TO REMAIN, IN ORDER TO PROVIDE SMOOTH MONOLITHIC SURFACE FOR NEW FINISHES. CONTRACTOR SHALL PROVIDE PATCHING AS REQUIRED IN ORDER TO INSTALL NEW POWER/COMMUNICATION RECEPTACLES & DEVICES.
15.
FINAL PLACEMENT OF ALL PARTITIONS TO BE APPROVED IN THE FIELD BY ARCHITECTS REPRESENTATIVE PRIOR TO COMMENCEMENT OF ANY WORK.
16.
ALL DOORS (NEW OR EXISTING) TO BE UNDERCUT AS REQUIRED TO ACCOMMODATE NEW FINISHED FLOOR MATERIAL.
17. 18.
7.
GENERAL CONTRACTOR TO PATCH ALL OPENINGS AFTER REMOVAL OF EXISTING ELECTRICAL OUTLETS NOT USED. THIS INCLUDES CONVECTOR/RADIATOR COVERS.
ALL EXISTING DOORS & DOOR FRAMES TO REMAIN SHALL BE CAULKED, PATCHED, REPAIRED UNDERCUT OR ADJUSTED AS REQUIRED FOR A PROPER INSTALLATION.
8.
G.C. TO PATCH & REPAIR FLOOR SURFACES TO A SMOOTH & LEVEL FINISH FOR THE PROPER INSTALLATION OF NEW FLOOR TREATMENT.
9.
ALL EXISTING CONSTRUCTION I.E: CORE WALLS, COLUMNS, ETC...TO REMAIN SHALL BE PATCHED & REPAIRED AS REQUIRED & PREPARED TO A SMOOTH & LEVEL FINISH, TO RECEIVE NEW FINISHES AS PER FINISH PLAN. G.C. TO FIELD SURVEY. PREPARE SAME WALLS TO A SMOOTH SURFACE. SKIM COAT AS REQUIRED OR LAMINATE LAYER OF GYPSUM BOARD IF REQUIRED.
10.
GENERAL CONTRACTOR IS RESPONSIBLE TO PROVIDE & INSTALL ALL BLOCKING & GROUNDS AS REQUIRED FOR THE INSTALLATION OF WINDOW BLINDS, DRAPERIES, CURTAINS, WALL MOUNTED CABINETS, MILLWORK, GLASS PARTITIONS CABINETRY & ANY OTHER WALL MOUNTED ITEMS INDICATED ON THE DRAWINGS.
MILLWORK SUBCONTRACTOR SHALL INSPECT & VERIFY THE ALIGNMENT OF NEW GYPSUM BOARD CONSTRUCTION WITH EXISTING CONDITIONS & NOTIFY THE ARCHITECT OF ANY CONDITION WHICH WOULD PREVENT HIM FROM PRODUCING SATISFACTORY WORK. GENERAL CONTRACTOR SHALL HAVE MILLWORK SUBCONTRACTOR CUT GROMMET HOLES & SUPPLY GROMMETS AS REQUIRED BY ARCHITECT IN ALL PL. LAM. & FINISHED WOOD COUNTERTOPS. LOCATION TO BE DETERMINED & COORDINATED IN THE FIELD U.O.N.
1.
REFER TO DRAWINGS G-001.00, G-002.00. G-003.00 FOR ADDITIONAL NOTES AND SPECIFICATIONS.
2.
ALL WALL OUTLETS ARE TO BE LAID OUT BY CONTRACTOR FOR APPROVAL BY ARCHITECT PRIOR TO INSTALLATION.
3.
G.C. TO INSTALL ADDITIONAL METAL STUDS AS REQUIRED TO INSTALL ALL RECEPTACLE, SWITCH, TELECOMM, ETC BOXES AT LOCATIONS INDICATED ON THE PLANS.
4.
G.C. TO VERIFY CIRCUITING, SWITCHING, AND ADDITIONAL SPECIFICATIONS.
5.
ELECTRICAL CONTRACTOR TO LOCATE ALL OUTLETS AS PER THIS DRAWING.
6.
ALL NEW WORK SHALL BE INSTALLED CONCEALED, UNLESS OTHERWISE INDICATED OR REQUIRED.
7.
ALL OUTLETS INSTALLED ABOVE COUNTERS ARE TO BE INSTALLED HORIZONTALLY AND MOUNTED 6" ABOVE COUNTER SURFACE TO CENTER LINE OF FACEPLATE.
8.
CONTRACTOR SHALL COORDINATE WITH TPG FINAL LOCATIONS OF ALL FIRE SPEAKER/STROBES IN FIELD PRIOR TO INSTALLATION FOR DIMENSIONS AND CENTERING ON WALL
9.
EXG. THERMOSTAT LOCATIONS TO REMAIN, VIF IN FIELD FOR LOCATIONS. IF REQUIRED FOR RELOCATION G.C. MUST VERIFY NEW LOCATION WITH TPG IN THE FIELD PRIOR TO INSTALLATION
AT ALL FIRE RATED PARTITION, CAULK WALL PENETRATION.
10. CONTRACTOR TO PROVIDE PLUMBING FEEDS/WATER LINES & DRAINS AS REQUIRED FOR NEW SINKS, COFFEE MAKERS, OR ANY ICE MAKER AT REFRIGERATOR AT PANTRY.
20.
ALL METAL STUDS SHALL BE 20 GAUGE MINIMUM.
DRAWING
PARTIAL PANTRY CONSTRUCTION PLANS DATE
06/13/2016
PROJECT NO.
1516589-00
SCALE
ALL PANTRIES TO BE PROVIDED WITH PURPLE BOARD (WATER AND MOLD RESISTENT) GYPSUM BOARD. GC TO REFER TO CONSTRUCTION PLANS.
19.
1633 BROADWAY NEW YORK, NY 11210
CATALOGUE CUTS FOR ALL PRE MANUFACTURED ITEMS SHALL BE SUBMITTED TO TPG FOR APPROVAL PRIOR TO ORDERING. SUBSTITUTIONS WILL NO BE ACCEPTED UNLESS PRIOR APPROVAL HAS BEEN GIVEN IN WRITTING
CAD FILE NO.
PAGE NO. OF 19
DWG NO.
04
04
06 04
04
MENS ROOM 33-04
01
06
WOMENS ROOM 33-03
02
01
03
02
06
01 04
04
02
03 05
33-02
INDICATES AREA NOT IN CONTRACT
06
INDICATES EXISTING DOOR/FRAME TO REMAIN, REFER TO DOOR SCHEDULE DRAWING(S).
03
04
04 04
INDICATES KEY NOTE REFERENCE, SEE PLAN NOTED FOR FURTHER INFORMATION
05
01
INDICATES EXISTING WALLS TO REMAIN
02
INDICATES NEW WALL
03 J
J
J
J
J
J
J
J
J
33-05
04
INDICATES NEW MILLWORK
INDICATES NEW SADDLE
N
INDICATES NORTH
N N
INDICATES ROOM/AREA INDICATES SPACE NUMBER
AREA OF WORK
INDICATES TRANSITION OF FLOOR FINISH
FRONT OF FACE TO ALIGN
04 J
06 J
J
NEW PARTITION TYPE, REFER TO CORRESPONDING PARTITION TYPE ON SHEET A-902.00
J
J
GFI
WALL GROUND FAULT INTERRUPTER DUPLEX ELECTRICAL RECEPTACLE
05
WALL RECESSED DUPLEX ELECTRICAL RECEPTACLE
33-07
J
04 01
MENS ROOM 33-06
02 04
03
04
POWER (ELECTRICAL) WALL JUNCTION BOX .
(E)
EXISTING ITEM
(R)
EXISTING ITEM RELOCATED
04
06
01 02
N
03
04
01 02 03
WOMENS ROOM 33-09
06
NOTE: 1. RELOCATE & MODIFY EXIST. PLUMBING ROUGH-IN AS REQUIRED TO ACCOMMODATE NEW LAYOUT AND LOCATIONS OF PLUMBING FIXTURES (SINKS, TOILET BOWLS, URINALS, ETC.... GC TO COORD. & VERIFY EXIST. CONDITIONS.
01
GC TO RE-CONSTRUCTION NEW PARTITIONS AT THE EXACT LOCATIONS OF EXISTING WALLS THAT WERE DEMOLISHED DURING DEMOLITION PHASE. REFER TO DEMO DRAWINGS FOR MORE INFO.
02
CAREFULLY REVIEW NEW LAYOUT DIMENSIONS OF TOILET PARTITIONS. MODIFY LOCATIONS OF EXISTING ROUGH-IN AS NEEDED TO ACHIEVE DIMENSIONS INDICATED ON CD DRAWINGS. CONFIRM FINAL LOCATIONS WITH ARCHITECT PRIOR TO FABRICATION & CONSTRUCTION.
03
LAYOUT FLOOR AND WALL TILES: REFER TO NEW DIMENSIONS INDICATED ON ELEVATION DRAWINGS. SURVEY EXISTING CONDITIONS AND CONFIRM FINAL DIMENSIONS WITH ARCHITECT PRIOR TO INSTALLATION.
04
NEW 5 8" PURPLE BOARD OVER EXIST. METAL STUDS ON CMU. PATCH, REPAIR EXIST. METAL STUD & PREP TO RECEIVE NEW 5 8" PURPLE BOARD. REPLACE W/ NEW IF NEEDED TO. GC TO COORD, TYP.
04 06
04
05
33-08 01
TPG ARCHITECTURE, LLP
02 03 J J
J
J
05
NEW FULL HEIGHT PARTITION W/ 5 8" PURPLE BOARD ON BOTH SIDES OF MTL. STUDS. RUN MTL. STUDS TO UNDERSIDE OF EXIST. SLAB ABOVE. EXTEND GYP. BD. TO 6" ABOVE FINISHED CEILING. "FATTEN" PARTITION AS NEEDED TO ACCOMMODATE TOILET ACCESSORIES, TYP.
06
EXIST. DOOR, FRAME, & HARDWARE AT CORE RESTROOMS: PAINT EXIST. DOOR & FRAME REPLACE ALL EXIST. HARDWARE WITH NEW. SPECS TO MATCH EXIST. REFER TO DEMO DRAWINGS FOR MORE INFO.
04
N
31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 | TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. PROJECT
MORGAN STANLEY 1.
REFER TO DRAWINGS G-001.00, G-002.00. G-003.00 FOR ADDITIONAL NOTES AND SPECIFICATIONS.
2.
CONTRACTOR SHALL REVIEW AND INCLUDE ALL NOTES ON DWGS. IN THIS SET OF CONSTRUCTION DOCUMENTS. THIS INCLUDES BEING FAMILIAR WITH ALL GENERAL NOTES WHICH APPLY DIRECTLY TO ANY AND ALL TRADES. EACH SUBTRADE WILL BE RESPONSIBLE FOR REVIEWING THE ENTIRE SET OF DRAWINGS AND NOTING THEIR WORK AS APPLICABLE. ALL WORK INDICATED OR INFERRED ON THE DRAWINGS WILL BE DEEMED AND INCLUDED IN ALL CONTRACTOR'S COSTS.
3.
4.
5.
6.
11.
12.
GENERAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING DIMENSIONS IN FIELD.
13.
GENERAL CONTRACTOR SHALL LAY OUT PARTITIONS STARTING FROM CONDITIONS WHERE ALIGNMENT WITH EXISTING CONSTRUCTION IS SHOWN.
CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF ALL ITEMS TO REMAIN THROUGH THE ENTIRE COURSE OF DEMOLITION & CONSTRUCTION (INCLUDING, BUT NOT LIMITED TO, PARTITIONS, FINISHES, DOORS, FRAMES, HARDWARE & ELECTRICAL CIRCUITRY). CONTRACTOR SHALL REPAIR &/OR REPLACE ANY DAMAGE WHICH MIGHT OCCUR.
14.
GENERAL CONTRACTOR TO SUBMIT SHOP DRAWINGS TO ARCHITECT'S OFFICE FOR REVIEW & APPROVAL PRIOR TO THE FABRICATION OF ALL ITEMS OF FINISH WORK: LIGHTING FIXTURE, METAL + GLASS PARTITIONS, CEILING MILLWORK, ETC.
FOR ALL EXISTING CONSTRUCTION, GC SHALL MAKE ALL NECESSARY REMOVALS & PATCH, LAMINATE, OR RE-FURR AS NECESSARY ANY DAMAGE PARTITIONS TO REMAIN, IN ORDER TO PROVIDE SMOOTH MONOLITHIC SURFACE FOR NEW FINISHES. CONTRACTOR SHALL PROVIDE PATCHING AS REQUIRED IN ORDER TO INSTALL NEW POWER/COMMUNICATION RECEPTACLES & DEVICES.
15.
FINAL PLACEMENT OF ALL PARTITIONS TO BE APPROVED IN THE FIELD BY ARCHITECTS REPRESENTATIVE PRIOR TO COMMENCEMENT OF ANY WORK.
16.
ALL DOORS (NEW OR EXISTING) TO BE UNDERCUT AS REQUIRED TO ACCOMMODATE NEW FINISHED FLOOR MATERIAL.
17. 18.
7.
GENERAL CONTRACTOR TO PATCH ALL OPENINGS AFTER REMOVAL OF EXISTING ELECTRICAL OUTLETS NOT USED. THIS INCLUDES CONVECTOR/RADIATOR COVERS.
ALL EXISTING DOORS & DOOR FRAMES TO REMAIN SHALL BE CAULKED, PATCHED, REPAIRED UNDERCUT OR ADJUSTED AS REQUIRED FOR A PROPER INSTALLATION.
8.
G.C. TO PATCH & REPAIR FLOOR SURFACES TO A SMOOTH & LEVEL FINISH FOR THE PROPER INSTALLATION OF NEW FLOOR TREATMENT.
9.
ALL EXISTING CONSTRUCTION I.E: CORE WALLS, COLUMNS, ETC...TO REMAIN SHALL BE PATCHED & REPAIRED AS REQUIRED & PREPARED TO A SMOOTH & LEVEL FINISH, TO RECEIVE NEW FINISHES AS PER FINISH PLAN. G.C. TO FIELD SURVEY. PREPARE SAME WALLS TO A SMOOTH SURFACE. SKIM COAT AS REQUIRED OR LAMINATE LAYER OF GYPSUM BOARD IF REQUIRED.
10.
GENERAL CONTRACTOR IS RESPONSIBLE TO PROVIDE & INSTALL ALL BLOCKING & GROUNDS AS REQUIRED FOR THE INSTALLATION OF WINDOW BLINDS, DRAPERIES, CURTAINS, WALL MOUNTED CABINETS, MILLWORK, GLASS PARTITIONS CABINETRY & ANY OTHER WALL MOUNTED ITEMS INDICATED ON THE DRAWINGS.
MILLWORK SUBCONTRACTOR SHALL INSPECT & VERIFY THE ALIGNMENT OF NEW GYPSUM BOARD CONSTRUCTION WITH EXISTING CONDITIONS & NOTIFY THE ARCHITECT OF ANY CONDITION WHICH WOULD PREVENT HIM FROM PRODUCING SATISFACTORY WORK. GENERAL CONTRACTOR SHALL HAVE MILLWORK SUBCONTRACTOR CUT GROMMET HOLES & SUPPLY GROMMETS AS REQUIRED BY ARCHITECT IN ALL PL. LAM. & FINISHED WOOD COUNTERTOPS. LOCATION TO BE DETERMINED & COORDINATED IN THE FIELD U.O.N.
1.
REFER TO DRAWINGS G-001.00, G-002.00. G-003.00 FOR ADDITIONAL NOTES AND SPECIFICATIONS.
2.
ALL WALL OUTLETS ARE TO BE LAID OUT BY CONTRACTOR FOR APPROVAL BY ARCHITECT PRIOR TO INSTALLATION.
3.
G.C. TO INSTALL ADDITIONAL METAL STUDS AS REQUIRED TO INSTALL ALL RECEPTACLE, SWITCH, TELECOMM, ETC BOXES AT LOCATIONS INDICATED ON THE PLANS.
4.
G.C. TO VERIFY CIRCUITING, SWITCHING, AND ADDITIONAL SPECIFICATIONS.
5.
ELECTRICAL CONTRACTOR TO LOCATE ALL OUTLETS AS PER THIS DRAWING.
6.
ALL NEW WORK SHALL BE INSTALLED CONCEALED, UNLESS OTHERWISE INDICATED OR REQUIRED.
7.
ALL OUTLETS INSTALLED ABOVE COUNTERS ARE TO BE INSTALLED HORIZONTALLY AND MOUNTED 6" ABOVE COUNTER SURFACE TO CENTER LINE OF FACEPLATE.
8.
CONTRACTOR SHALL COORDINATE WITH TPG FINAL LOCATIONS OF ALL FIRE SPEAKER/STROBES IN FIELD PRIOR TO INSTALLATION FOR DIMENSIONS AND CENTERING ON WALL
9.
EXG. THERMOSTAT LOCATIONS TO REMAIN, VIF IN FIELD FOR LOCATIONS. IF REQUIRED FOR RELOCATION G.C. MUST VERIFY NEW LOCATION WITH TPG IN THE FIELD PRIOR TO INSTALLATION
AT ALL FIRE RATED PARTITION, CAULK WALL PENETRATION REFER DETAIL.
10. CONTRACTOR TO PROVIDE PLUMBING FEEDS/WATER LINES & DRAINS AS REQUIRED FOR NEW SINKS, COFFEE MAKERS, OR ANY ICE MAKER AT REFRIGERATOR AT PANTRY.
20.
ALL METAL STUDS SHALL BE 20 GAUGE MINIMUM.
DRAWING
PARTIAL RESTROOM CONSTRUCTION PLANS DATE
06/13/2016
PROJECT NO.
1516589-00
SCALE
ALL RESTROOMS TO BE PROVIDED WITH PURPLE BOARD (WATER AND MOLD RESISTENT) GYPSUM BOARD. GC TO REFER TO CONSTRUCTION PLANS.
19.
1633 BROADWAY NEW YORK, NY 11210
CATALOGUE CUTS FOR ALL PRE MANUFACTURED ITEMS SHALL BE SUBMITTED TO TPG FOR APPROVAL PRIOR TO ORDERING. SUBSTITUTIONS WILL NO BE ACCEPTED UNLESS PRIOR APPROVAL HAS BEEN GIVEN IN WRITTING
CAD FILE NO.
PAGE NO. OF 19
DWG NO.
B.O. EXG. CEILING V.I.F.
B.O. EXG. CEILING V.I.F.
NEW SCHLUTER STRIP GL1
EXG. COLUMN PATCH AND REPAIR AS REQUIRED TO ACCEPT NEW FINISH
FULL HEIGHT BACKSLASH. SEE FINISH PLAN FOR SPEC.
NEW BASE REFER TO FINISH PLAN (TYP)
PL1
FULL HEIGHT BACKSLASH. SEE FINISH PLAN FOR SPEC.
MW
COUNTERTOP. SEE FINISH PLAN FOR SPEC.
REF
MW
CMER PL1
PL1
BASE CABINETS. SEE FINISH PLAN FOR SPEC.
NEW 5/8" GYP. BD. WALL CAP. G.C. TO TAPE, SPACKLE, AND SAND TO RECIEVE NEW FINISH
IM
BASE CABINETS. SEE FINISH PLAN FOR SPEC.
COUNTERTOP. SEE FINISH PLAN FOR SPEC.
PL1
3" 4
3" 4
4 A802
REC2
VM1
REF2
VM2
PL2
FINISHED FL 0'-0"
FINISHED FL 0'-0"
1 A801
1 A801
5 A801
3 A801
N
AREA OF WORK
REF
COUNTERTOP. SEE FINISH PLAN FOR SPEC.
SD
BASE CABINETS. SEE FINISH PLAN FOR SPEC.
IH
TD
MW
FA
TR
COORD. W/ SPEC
GL1
EXISTING PARTITION PATCH AND REPAIR AS REQUIRED TO ACCEPT NEW FINISH
FULL HEIGHT BACKSLASH. SEE FINISH PLAN FOR SPEC. COUNTERTOP. SEE FINISH PLAN FOR SPEC.
IM CM
BASE CABINETS. SEE FINISH PLAN FOR SPEC.
REC
NEW HOLLOW METAL FRAMED HEADER, REFER TO DETAIL 3 ON SHEET A-803
GL1
CM
OPEN TO BEYOND
CMER
PL1
REC2 PL2
FINISHED FL 0'-0"
EXG. COLUMN. PATCH & REPAIR AS REQUIRED TO ACCEPT NEW FINISH (2) NEW HAFELE STEVEN DOOR PULL HANDLES W/ BACK-TO-BACK FASTENER MOUNTING
FINISHED FL 0'-0"
ALIGN
121"
FULL HEIGHT BACKSLASH. SEE FINISH PLAN FOR SPEC.
B.O. EXG. CEILING V.I.F.
2'-10"
VIF
B.O. EXG. CEILING V.I.F.
B.O. EXG. CEILING V.I.F.
NEW HOLLOW METAL FRAMED JAMB, REFER TO DETAIL 4 ON SHEET A-803
G.C. TO PROVIDE NEW HAFELE DEADBOLT LOCK 13MM PROFILE CYLINDER FINISHED FL 0'-0"
1 A801
4 A801
NEW BASE REFER TO FINISH PLAN (TYP)
3 A801
G.C. TO PROVIDE NEW HAFELE DUST PROOF STRIKE W/ SPRING LOADED COVER
TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 | TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. PROJECT
MORGAN STANLEY
(2) NEW HAFELE STEVEN DOOR PULL HANDLES W/ BACK-TO-BACK FASTENER MOUNTING HARDWARE FINISHED FL 0'-0"
1633 BROADWAY NEW YORK, NY 11210
1'-6" HOLD 7'-1" VIF & COORDINATE W/ FLATEC V HAFELE SPEC SHEET
B.O. EXG. CEILING V.I.F.
1'-0"
6'-6" VIF & COORDINATE W/ FLATEC V HAFELE SPEC SHEET & REP
DRAWING
NEW FLATEC V WITH HOLLOW STAINLESS STEEL TRACK BY HAFELE, REFER TO SPEC FOR INSTALLATION & PROVIDE WOOD BLOCKING IN HEADER & PARTITION AS REQUIRED NEW PAINTED NEW WALL
1 34"
PANTRY ELEVATIONS
WD DOOR
EXG. COLUMN PATCH & REPAIR AS REQUIRED TO ACCEPT NEW FINISH NEW BASE REFER TO FINISH PLAN (TYP)
DATE
06/13/2016
PROJECT NO.
1516589-00
SCALE 2'-1021" VIF & COORDINATE W/ FLATEC V HAFELE SPEC SHEET
CAD FILE NO.
OF 19
NOTE: 1- G.C TO CONFIRM ALL APPLIANCE SIZE FOR CLEARANCES PRIOR TO ANY CONSTRUCTION 2- ALL OUTLETS TO BE COORDINATED WITH APPLIANCE MANUFACTURER 3- G.C. TO PROVIDE ALL IN-WALL/AND CEILINGS BLOCKING AS REQUIRED FOR THE INSTALLATION OF ALL MILLWORK.
PAGE NO.
DWG NO.
TYP.
ADA SHELF
TYP
TYP TYP TYP.
ADA SHELF
ADA SHELF
SIM
TYP
SIM.
TYP
CRAC
UPS
SIM
ADA SHELF
TYP.
SIM TYP
TYP.
5
TYP.
1
ADA SHELF
3
11 12
DATE
BY
11
12
10
2
TPG ARCHITECTURE, LLP
YP
1T
3 TYP.
31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 | TPGARCHITECTURE.COM
.
1
12
SIM TYP
IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT.
5
4
14
14
5
6
7
8
9
3
SIM TYP.
PROJECT
TYP.
SIM
REVISION
ADA
2
1
NO.
10
SIM
FIN TECH 14TH & 15TH FLOORS 4 TIMES SQUARE NEW YORK, NY
G:\16\1516383-00\ARCH\SHEET\A-115.00.DWG / Plot Date: Sep, 30, 2016 - 5:57 :PM Last Saved By: PREBNICKY / Save Date: 9/30/2016 3:59:19 PM
DRAWING
15TH FLOOR CONSTRUCTION PLAN
SEAL
DATE PROJECT NO.
06/21/16 1516383-00
SCALE CAD FILE NO. DWG NO.
NYC DOB NO.
DOB PAGE
W18X40
W12X57
W2
4X
W12X19
62
W24X62
W18X40
W12X19
W12X19
W12X19
W12X19
W12X19
W12X19
W12X19
W12X19
X35
W18
W4X22
W6X26
W6X26
W16X31
W12X19
W21X14
W12X19
W24X55
W21X50
W24X62
W24X62
W24X62
W24X62
W2X19
W21X14
4X
W18X40
W16X26
W16X26
W18X40
W24X62
W4X22
W21X62
W12X14
W21X62
W24X62
W12X19
W12X14
W18X40
W16X26
W18X40
W16X26
62
W12X14
W16X26
W16X26
W24X68
W21X14
W18X35
W14X22
W16X26
W21X44
W16X26
W18X40
W
W2
2 X6 24
W21X14 W18X40
W12X19
W18X40
W16X26
W14X22
W12X19
W14X22
W16X26
W16X26
W24X62
W24X62
W21X68
W16X26
W16X26
W21X50
W21X62
W21X44
W12X19
W16X26
W12X14
W14X22
W24X62
W14X76
W24X62
W16X26
W16X26 W16X26
W12X14
W12X19
W21X68
W16X26 W16X26
W21X62
W24X68
W24X62
W18X35
W21X68
W12X14
W21X68
W16X26
NO. W18X35
X35
W18
W18X35
W18X35
REVISION
DATE
BY
W12X19
TPG ARCHITECTURE, LLP
W21X44
W21X44
W21X44
W21X50
W21X44
5 X3
W21X44
W21X50
W21X44
18
W
W21X44
W12X14
4X 62
W16X31
W2
W21X50
W12X19
W1 8X3 5
31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 | TPGARCHITECTURE.COM W12X14
W24X62
W24X62
W24
X62
W12X19
W12X14
IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. PROJECT
W18X40
W24X62
W24X62
W24X62
FIN TECH 14TH & 15TH FLOORS 4 TIMES SQUARE NEW YORK, NY
G:\16\1516383-00\ARCH\SHEET\A-214A.00.DWG / Plot Date: Sep, 30, 2016 - 5:42 :PM Last Saved By: PREBNICKY / Save Date: 9/30/2016 3:22:37 PM
DRAWING
14TH FLOOR REFLECTED CEILING PLAN
SEAL
DATE PROJECT NO.
06/21/16 1516383-00
SCALE CAD FILE NO. DWG NO.
NYC DOB NO.
DOB PAGE
TYP.
4 A-921
6 A-921 2 EQ PANELS
SHARED CONF. ROOM 15-09
COAT CLOSET
AV CLOSET
SHARED CONF. ROOM 15-03
4'-0"
2 EQ PANELS
4'-0"
SHARED CONF. ROOM 15-03
SHELF FOR CAM. COORDINATE W/ A/V DRW'S. TYP.
(3) EQ PANELS
TYP.
2 EQ PANELS
SEE AV DRAWINGS
RECESSED NICHE FOR CAM. COORDINATE W/ A/V DRW'S. TYP. SCHEDULED FULL LENGTH FABRIC PANEL, SEE FINISH PLAN. TYP.
ALIGN TYP.
SCHEDULED CREDENZA, SEE FURNITURE PLAN. TYP.
4'-0"
4'-0"
VIF
RECESSED NICHE FOR CAM. COORDINATE W/ A/V DRW'S. TYP. SCHEDULED FULL LENGTH FABRIC PANEL, SEE FINISH PLAN. TYP. SCHEDULED CREDENZA, SEE FURNITURE PLAN. TYP.
SCHEDULED BASE, TYP.
6'-4" VIF 2 EQ PANELS
4'-0"
RECESSED NICHE FOR CAM. COORDINATE W/ A/V DRW'S. TYP. SCHEDULED FULL LENGTH FABRIC PANEL, SEE FINISH PLAN. TYP. SCHEDULED CREDENZA, SEE FURNITURE PLAN. TYP.
SCHEDULED BASE, TYP.
TYP.
SCHEDULED BASE, TYP.
TYP.
TYP.
6A A-921
4 A-921
6 A-921
6A A-921 (5) EQ PANELS 4'-0" MAX
2 EQ PANELS
SCHEDULED ALUM. ANGLE @ PERIMTER OF EACH WALL, SEE FINISH PLAN. TYP.
4'-0"
2 EQ PANELS
4'-0"
SCHEDULED ALUM. ANGLE @ PERIMTER OF EACH WALL, SEE FINISH PLAN. TYP.
SCHEDULED GLASS PANEL, SEE FINISH PLAN. TYP.
SCHEDULED FULL LENGTH FABRIC PANEL, SEE FINISH PLAN. TYP.
SCHEDULED BASE, TYP.
NO.
REVISION
DATE
BY
SCHEDULED CREDENZA, SEE FURNITURE PLAN. TYP.
ALIGN TYP.
SCHEDULED GLASS PANEL, SEE FINISH PLAN. TYP.
RECESSED NICHE FOR CAM. COORDINATE W/ A/V DRW'S. TYP.
SEE AV DRAWINGS
(5) EQ PANELS 4'-0" MAX
4'-0"
VIF
ALIGN TYP.
2 EQ PANELS
4'-0"
4 A-921
6 A-921
ALIGN TYP.
4'-0"
VIF
TYP.
4 A-921
6 A-921
SEE AV DRAWINGS
4 A-921
(3) EQ PANELS
SEE AV DRAWINGS
TYP.
SCHEDULED CREDENZA, SEE FURNITURE PLAN. TYP. SCHEDULED BASE, TYP.
(3) EQ PANELS
6 A-921
SCHEDULED FULL LENGTH FABRIC PANEL, SEE FINISH PLAN. TYP.
ALIGN TYP.
2'-6"
2'-6"
5'-0"
SEE AV DRAWINGS
DISTRACTION STRIP, TYP.
5'-0"
DISTRACTION STRIP, TYP.
SCHEDULED BASE, TYP.
SCHEDULED BASE, TYP.
TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 | TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. PROJECT TYP.
3 A-921 VIF
4'-0"
TYP.
6 A-921 4'-0"
TYP.
6A A-921
6A A-921
(3) EQ PANELS 4'-0" MAX
VIF
(6) EQ PANELS 4'-0" MAX
FIN TECH 14TH & 15TH FLOORS 4 TIMES SQUARE NEW YORK, NY
SCHEDULED ALUM. ANGLE @ PERIMTER OF EACH WALL, SEE FINISH PLAN. TYP.
SCHEDULED ALUM. ANGLE @ PERIMTER OF EACH WALL, SEE FINISH PLAN. TYP.
12TH & 15TH FLOOR RESTROOM ELEVATIONS PARTIAL ENLARGED PLANS, & INTERIOR ELEVATIONS SEAL
SEE AV DRAWINGS
SCHEDULED FULL LENGTH FABRIC PANEL, SEE FINISH PLAN. TYP.
SCHEDULED GLASS PANEL, SEE FINISH PLAN. TYP.
CAD FILE NO. DWG NO. SCHEDULED BASE, TYP.
06/21/16 1516383-00
SCALE
SCHEDULED GLASS PANEL, SEE FINISH PLAN. TYP.
SCHEDULED CREDENZA, SEE FURNITURE PLAN. TYP. SCHEDULED BASE, TYP.
DATE PROJECT NO.
RECESSED NICHE FOR CAM. COORDINATE W/ A/V DRW'S. TYP.
ALIGN TYP.
G:\16\1516383-00\ARCH\SHEET\A-715D.00.DWG / Plot Date: Sep, 30, 2016 - 5:12 :PM Last Saved By: PREBNICKY / Save Date: 9/30/2016 3:37:46 PM
DRAWING
SCHEDULED BASE, TYP.
NYC DOB NO.
DOB PAGE
NO.
REVISION
DATE
BY
TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 | TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. PROJECT
FIN TECH 14TH & 15TH FLOORS 4 TIMES SQUARE NEW YORK, NY
G:\16\1516383-00\ARCH\SHEET\A-911.00.DWG / Plot Date: Sep, 30, 2016 - 5:14 :PM Last Saved By: VTRAN / Save Date: 9/30/2016 4:10:25 PM
DRAWING
CEILING DETAILS
SEAL
DATE PROJECT NO.
06/21/16 1516383-00
SCALE CAD FILE NO. DWG NO.
NYC DOB NO.
DOB PAGE
NO.
REVISION
DATE
BY
TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 | TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. PROJECT
FIN TECH 14TH & 15TH FLOORS 4 TIMES SQUARE NEW YORK, NY
G:\16\1516383-00\ARCH\SHEET\A-921.00.DWG / Plot Date: Sep, 30, 2016 - 5:14 :PM Last Saved By: VTRAN / Save Date: 9/30/2016 4:01:04 PM
DRAWING
MILLWORK SECTIONS AND DETAILS
SEAL
DATE PROJECT NO.
06/21/16 1516383-00
SCALE CAD FILE NO. DWG NO.
NYC DOB NO.
DOB PAGE