Valves & Tank Equipment

Page 1

VALVES & TANK EQUIPMENT

SAFETY PRODUCTS THAT PROTECT EQUIPMENT, LIVES & THE ENVIRONMENT

TABLE OF CONTENTS

1201B, 1202B, 1203A

1220A, 1221B, 1222B, 1223B

ADDITIONAL GROTH PRODUCTS

VALVES & TANK EQUIPMENT // PAGE 2 www.grothcorp.com
MODEL NUMBER MODEL DESCRIPTION PAGE # PRESSURE/VACUUM RELIEF VALVES
Pressure/Vacuum Relief Valves 3-12 SERIES 1800A Full Lift Type Pressure/Vacuum Relief Valves 13-24
Pressure/Vacuum Relief Valves with Pipe-Away Feature 25-34 1720A,
Pressure/Vacuum Relief Valves with Pipe-Away Feature 35-38 12-TH Thief Hatch 39-42 PRESSURE OR VACUUM RELIEF VALVES 1260A,
Pressure Relief Valves 43-48 2300A,
Pressure Relief Valves 49-54 1300A,
Vacuum Relief Valves, Top Mount 55-60 1360A, 1361A Vacuum Relief Valves, Side Mount 61-66 5000, 5100 Pressure/Vacuum Free Vents, Top Mount 67-76 6000, 6100 Gauge Hatches 77-78 2000A, 2050A Emergency Relief Valves, Weight Loaded 79-82 2100 Emergency Relief Valves, Spring Loaded 83-86 2400A, 2450A Emergency Relief Valves, Weight Loaded; Hinged 87-90 MISC Fiberglass Relief Valves 91-92 Steam Jacketed Relief Valves 93 TECHNICAL SECTION TPD Standard Settings & Max Tank Working Pressure 94 Please see our other Groth Datasheets for additional product lines:
1200A,
1760A
1261A
2301A
1301A

MODEL 1200A

• Sizes // 2" through 12"

• Pressure settings // 0.5 oz/in2 to 15 psig

• Vacuum settings // 0.5 oz/in2 to 12 psig

• Available in aluminum, carbon steel, stainless steel, fiberglass and other materials

• Modular construction

PRESSURE/VACUUM RELIEF VALVE

Model 1200A is designed to protect your tank from damage created by overpressure or excessive vacuum. Costly product evaporation losses due to normal tank “breathing” are greatly reduced. Because the Model 1200A retains toxic vapors, atmospheric contamination is minimized. This helps to provide increased fire protection and safety.

SPECIAL FEATURES

Model 1200A offers Groth’s special “cushioned air” seating. Superior performing fluoropolymer seating diaphragms are standard to minimize sticking caused by resinous vapors and atmospheric moisture. The Model 1200A has a self draining housing body and drip rings to protect seating surfaces from condensate and freezing. This design also avoids dangerous pressure or vacuum buildup due to binding or clogging of the valve. Buna-N, FKM and other seating diaphragms can be provided when required. To insure the proper alignment of seating surfaces, there is peripheral guiding and a center stabilizing system.

VALVES & TANK EQUIPMENT // PAGE 3 www.grothcorp.com
MODEL 1200A MODEL 1201B

SPECIFICATIONS

Specifications subject to change without notice. Certified dimensions available upon request.

2"12oz/in213.63"14"9.50"13.37"19.87"9.50"16 (50mm)(52.7gm/cm2)(346mm)(355mm)(241mm)(340mm)(505mm)(241mm)(7kg)

3"11oz/in218"15"11.50"18.37"22.75"13"21 (80mm)(48.3gm/cm2)(457mm)(381mm)(292mm)(467mm)(578mm)(330mm)(9kg)

4"11oz/in219.75"17.50"13"19.50"27.50"13"31 (100mm)(48.3gm/cm2)(502mm)(444mm)(330mm)(495mm)(699mm)(330mm)(14kg)

6"16oz/in227.75"22.25"19"27.75"37.75"19.50"57 (150mm)(70.3gm/cm2)(704mm)(565mm)(483mm)(705mm)(959mm)(495mm)(26kg) 8"16oz/in233.88"27.50"23.63"33.62"44.50"23.50"75 (200mm)(70.3gm/cm2)(860mm)(699mm)(600mm)(854mm)(1130mm)(597mm)(34kg) 10"16oz/in

(300mm)(70.3gm/cm2)(1168mm)(835mm)(914mm)(1029mm)(1413mm)(648mm)(71kg)

† W.P. = Working Pressure. // ‡ On spring loaded valves, change model number.

◊ 150# ANSI drilling compatibility, F.F. on aluminum and R.F. on carbon steel and stainless steel alloys. Fiberglass dimensions on request. 16 oz/in2 set with spacer. SS set weights-consult factory. *Some sizes require non-ferrous components to achieve 0.5 oz/in2 setting. For easy ordering, select proper model numbers

• Include model number and setting when ordering.

• For special options, consult factory

• When ordering steam jacket, include steam pressure/temperature.

Stainless

VALVES & TANK EQUIPMENT // PAGE 4 www.grothcorp.com
AA BB CC A C A B
Inlet Flg◊ (Metric) Max.Set Pressure Weight Loaded Max.Set Vacuum. Weight Loaded Max. Setting Spring Loaded Min. Setting Weight Loaded Max.W.P.† forMin. Vacuum Setting Min.Vac. Setting for Max.W.P.† A Length (Metric) B Height (Metric) C Width (Metric) AA Length (Metric) BB Height (Metric) CC Width (Metric) Approx. Ship Wt.Lbs. (Aluminum)
240.88"28.88"30.75"38"53"25.50"116
16 oz/in 2 (70.3 gm/cm 2 ) 15 psig SPRING LOADED PRESSURE (1.05 kg/cm 2 ) 12 psig SPRING LOADED VACUUM (0.84 kg/cm 2 ) *0.5 oz/in 2 WEIGHT LOADED (2.20 gm/cm 2 )
(250mm)(70.3gm/cm2)(1038mm)(733mm)(781mm)(965mm)(1346mm)(648mm)(53kg) 12"16oz/in246"32.88"36"40.50"55.62"25.50"157
See TPD for Vacuum Settings and MAWP
MODEL#SIZEMATERIALOPTIONS 1200A Weight Loaded 1201B Pressure Spring 1202B Vacuum Spring 1203A Pressure
Vacuum Springs 1 = Aluminum 3 = Carbon Steel 5 = Stainless Steel 6 = Vinyl Ester Resin 7 = Furan Z
Special O
Z
O
J
S
H
Diaphragm Material
B = Buna-N T = Fluoropolymer V = FKM Z
Pallet Material Seat Material Body Material 02" Thru 12"
&
=
= No Options
= Special Options
= No Jacket
= Steam Jacket
= Spacer
= Steam Jacket & Spacer
(Seat):
= Special
*
steel guides, stems
standard
aluminum
carbon steel bodies. Stainless steel seats standard with carbon steel bodies. NOTES EXAMPLE Indicates a 2" Model 1200A with Aluminum Body and Seat, Stainless Steel Pallet, Fluoropolymer Seat Diaphragm, and no other options. 1200A021T1O5O HOW TO ORDER AC B CC AA BB A
are
with
and

MODEL 1200A/1202B // PRESSURE RELIEF CAPACITY

FLOW CAPACITY CALCULATION

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 5 www.grothcorp.com
AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000StandardCubicFeetperHourat60°F SetPressure(Ps)Size InWCoz/in22" (50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 0.870.507.6516.228.961.9108174217 1.000.588.2217.431.166.5116187233 1.731.0010.822.840.887.2152246305 2.001.1611.624.543.893.7164264328 2.601.5013.227.849.8106186300373
3.462.0015.232.057.3123214345429 4.002.3116.334.461.5131230371460 6.003.4719.841.874.7160279450560 8.004.6222.747.985.7183320516641 10.05.7825.153.195.1203355573712 12.06.9327.357.8103221386623774 15.08.6630.263.9114244427689856 20.011.634.372.5130277485781971 25.014.437.779.61423055328591067 30.017.340.685.71533285739251149
3.001.7314.129.953.4114200322400
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 131,000 SCFH 6" Model 1200A 2. Calculate overpressure % OP = [(7 - 4)/4] x 100 = 75% 4 InWC set pressure [Ps] 3. Read “C” factor from table “C” = 0.87 7 InWC flowing pressure [Pf] 4. Calculate flow capacity Flow = 0.87 x 131,000 = 113,970 SCFH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.87 “C”FactorTable %OP0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00

MODEL 1200A/1202B // PRESSURE RELIEF CAPACITY

MODEL 1220A FLOW CAPACITY CALCULATION

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 6 www.grothcorp.com
AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000NormalCubicMetersperHourat0°C SetPressure(Ps)Size mmWCmb2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 222.160.220.460.821.743.054.916.11 504.900.320.681.222.624.587.389.17 757.350.400.831.493.195.589.0011.2 1009.800.450.961.723.676.4210.412.9 12512.30.511.071.914.097.1511.514.3 15014.70.551.172.094.477.8112.615.6 17517.20.591.262.254.818.413.516.8 20019.60.631.342.395.128.9514.417.9 22522.10.671.412.535.419.4615.318.9 25024.50.701.492.665.689.9316.019.9 27527.00.731.552.785.9410.416.720.8 30029.40.761.622.896.1810.817.421.6 37536.80.851.793.206.8412.019.323.9 50049.00.962.033.637.7613.621.927.2 62561.31.052.233.998.5214.924.029.9 75073.51.142.404.299.1816.125.932.2
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 3,670 NCMH 6" Model 1200A 2. Calculate overpressure % OP = [(175 - 100)/100] x 100 = 75% 100 mmWC Set Pressure [Ps] 3. Read “C” factor from table “C” = 0.87 175 mmWC Flowing Pressure [Pf] 4. Calculate flow capacity Flow = 0.87 x 3,670 = 3,193 NCMH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.87 “C”FactorTable %OP0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00

MODEL 1200A/1201B // VACUUM RELIEF CAPACITY

0.870.504.7010.316.034.760.591.1129 1.000.585.0511.017.237.365.097.9138 1.731.006.6314.522.649.085.3129182 2.001.167.1215.624.252.691.6138195 2.601.508.1017.727.659.8104157222

3.001.738.7019.029.664.2112169238 3.462.009.3320.431.868.9120181256

4.002.3110.021.934.174.0129194274 6.003.4712.226.741.590.1157237334 8.004.6214.030.647.7103180272384 10.05.7815.634.053.0115200302427 12.06.9317.037.157.8125218329465 15.08.6618.841.164.0139242365516 20.011.621.446.872.9158276415587 25.014.423.651.580.3174304457646 30.017.325.455.686.6188327493697

Flow capacity values listed above are based on full open valves at 100% over-vacuum.

Read the flow capacity at 100% over-vacuum directly from the table above. Use linear interpolation if the set vacuum is not listed.

If the allowable over-vacuum is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, consult your Groth Representative.

Calculate the percentage over-vacuum by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OV = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% over-vacuum according to the following example.

VALVES & TANK EQUIPMENT // PAGE 7 www.grothcorp.com
Example—FlowCapacityCalculation 1. Read flow capacity at set vacuum from table Flow = 74,000 SCFH 6" Model 1200A 2. Calculate over-vacuum % OV = [(7 - 4)/4] x 100 = 75% 4 InWC Set Vacuum [Ps] 3. Read “C” factor from table “C” = 0.87 7 InWC Flowing Vacuum [P ] 4. Calculate flow capacity Flow = 0.87 x 74,000 = 64,380 SCFH Example—To find “C” factor from table: Read “C” factor for 75% Over-vacuum at intersection of row 70 and column 5 “C” factor at 75% OV = 0.87 “C”FactorTable %OV0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00 MODEL 1220A FLOW CAPACITY CALCULATION AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000StandardCubicFeetperHourat60°F SetVacuum(Ps)Size InWCoz/in22" (50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)

MODEL 1200A/1201B // VACUUM RELIEF CAPACITY

222.160.130.290.450.981.712.583.65 504.900.200.440.681.482.583.885.48

Flow capacity values listed above are based on full open valves at 100% over-vacuum.

Read the flow capacity at 100% over-vacuum directly from the table above. Use linear interpolation if the set vacuum is not listed.

If the allowable over-vacuum is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, consult your Groth Representative.

Calculate the percentage over-vacuum by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OV = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% over-vacuum according to the following example.

VALVES & TANK EQUIPMENT // PAGE 8 www.grothcorp.com
Example—FlowCapacityCalculation 1. Read flow capacity at set vacuum from table Flow = 2,080 NCMH 6" Model 1200A 2. Calculate over-vacuum % OV = [(175 - 100)/100] x 100 = 75% 100 mmWC Set Vacuum [Ps] 3. Read “C” factor from table “C” = 0.87 175 mmWC Flowing Vacuum [P ] 4. Calculate flow capacity Flow = 0.87 x 2,080 = 1,810 NCMH Example—To find “C” factor from table: Read “C” factor for 75% over-vacuum at intersection of row 70 and column 5 “C” factor at 75% OV = 0.87 “C”FactorTable %OV0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00 MODEL 1220A FLOW CAPACITY CALCULATION AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000NormalCubicMetersperHourat0°C SetVacuum(Ps)Size mmWCmb2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)
757.350.240.530.831.813.154.746.70 1009.800.280.620.962.083.625.467.72 12512.30.310.691.072.324.046.098.60 15014.70.340.751.172.534.416.659.40
17517.20.370.811.262.734.757.1610.1 20019.60.390.861.342.915.077.6410.8 22522.10.420.911.423.085.368.0811.4 25024.50.440.961.493.235.648.4912.0 27527.00.461.001.563.385.908.8812.6 30029.40.481.041.623.526.149.2513.1 37536.80.531.161.803.916.8110.314.5 50049.00.601.322.054.457.7511.716.5 62561.30.661.452.264.908.5412.918.2 75073.50.721.572.445.299.2213.919.6

MODEL 1201B/1203A // PRESSURE RELIEF CAPACITY

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 9 www.grothcorp.com
AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000StandardCubicFeetperHourat60°F SetPressure(Ps)Size psig2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 1.0028.053.492.5210345529739 2.0040.377.41343045007671070 3.0050.296.91683816259601340 4.0058.811419844873611301577 5.0066.513022551083812861794 6.0073.714425056893214311997 7.0080.4158274622102215682188 8.0086.7171297674110716992371 9.0092.8184319724118918252546 10.098.6196340772126719452714 11.0104208360818134320622877 12.0110219380863141721763036 13.0115231400907148922863189 14.0120241418949155923933339 15.0125252437991162724983486
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 448,000 SCFH 6" Model 1201B 2. Calculate overpressure % OP = [(7 - 4)/4] x 100 = 75% 4 psig Set Pressure [Ps] 3. Read “C” factor from table “C” = 0.83 7 psig Flowing Pressure [Pf] 4. Calculate flow capacity Flow = 0.83 x 448,000 = 371,840 SCFH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.83 “C”FactorTable %OP0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00
MODEL 1220A FLOW CAPACITY CALCULATION

MODEL 1201B/1203A // PRESSURE RELIEF CAPACITY

MODEL 1220A FLOW CAPACITY CALCULATION

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

= Set pressure

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 10 www.grothcorp.com
AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000NormalCubicMetersperHourat0°C SetPressure(P
barg2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)
0.100.991.893.287.4512.218.826.2 0.151.232.364.099.2815.223.432.6 0.201.432.764.8010.917.927.438.3 0.251.623.145.4412.320.331.143.4
0.351.953.816.6115.024.637.852.7
0.502.394.708.1618.530.446.665.1 0.552.524.988.6419.632.249.468.9 0.602.655.259.1020.633.952.172.6 0.702.895.7610.022.737.257.279.7 0.803.136.2510.824.640.462.186.5 0.903.356.7211.726.543.566.793.1 1.003.567.1812.528.346.471.299.4
s)Size
0.070.821.572.726.1610.115.521.7
0.301.793.486.0413.722.534.548.2
0.402.104.127.1416.226.640.957.0 0.452.254.417.6617.428.543.861.1
P s
% OP = [(Pf - Ps)/Ps] x 100
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 16,200 NCMH 6" Model 1201B 2. Calculate overpressure % OP = [(0.7 - 0.4)/0.4] x 100 = 75% 0.4 barg Set Pressure [Ps] 3. Read “C” factor from table “C” = 0.83 0.7 barg Flowing Pressure [Pf] 4. Calculate flow capacity Flow = 0.83 x 16,200 = 13,446 NCMH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.83 “C”FactorTable %OP0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00

MODEL 1202B/1203A // VACUUM RELIEF

MODEL 1220A FLOW CAPACITY CALCULATION

Flow capacity values listed above are based on full open valves at 100% over-vacuum.

Read the flow capacity at 100% over-vacuum directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable over-vacuum is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, consult your Groth Representative.

Calculate the percentage over-vacuum by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OV = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% over-vacuum according to the following example.

VALVES & TANK EQUIPMENT // PAGE 11 www.grothcorp.com
AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000StandardCubicFeetperHourat60°F SetVacuum(Ps)Size psig2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 1.0013.830.552.9120197302422 1.1014.531.955.4126206316442 1.2015.133.257.7131215330460 1.3015.734.559.9136223342478 1.4016.235.762.0141231355495 1.5016.836.964.0145239366511 1.7518.039.668.7156256393548 2.0019.142.073.0166272417582 2.2520.144.376.9174286439613 2.5021.046.380.4183300460641 2.7521.948.283.7190312478667 3.0022.749.986.6197323495691 3.2523.451.489.3203333511713 3.5024.052.891.8208342525732 >3.50CONSULTFACTORYFORVACUUMSETTINGSGREATERTHAN3.5PSIG
CAPACITY
Example—FlowCapacityCalculation 1. Read flow capacity at set vacuum from table Flow = 166,000 SCFH 6" Model 1202B 2. Calculate over-vacuum % OV = [(3.50 - 2.0)/2.0] x 100 = 75% 2 psig Set Vacuum [Ps] 3. Read “C” factor from table “C” = 0.83 3.5 psig Flowing Vacuum [P ] 4. Calculate flow capacity Flow = 0.83 x 166,000 = 137,780 SCFH Example—To find “C” factor from table: Read “C” factor for 75% over-vacuum at intersection of row 70 and column 5 “C” factor at 75% OV = 0.83
“C”FactorTable %OV0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00

MODEL 1202B/1203A // VACUUM RELIEF CAPACITY

Flow capacity values listed above are based on full open valves at 100% over-vacuum.

Read the flow capacity at 100% over-vacuum directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable over-vacuum is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, consult your Groth Representative.

Calculate the percentage over-vacuum by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure % OV = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% over-vacuum according to the following example.

VALVES & TANK EQUIPMENT // PAGE 12 www.grothcorp.com
AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000NormalCubicMetersperHourat0°C SetVacuum(P
barg2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 0.070.410.901.553.525.778.8712.4 0.100.481.061.834.166.8310.514.6 0.110.511.111.924.357.1411.015.3 0.120.531.151.994.537.4311.415.9 0.130.551.202.074.697.7011.816.5 0.140.561.242.144.857.9612.217.1 0.150.581.272.205.008.2112.617.6 0.160.601.312.275.148.4413.018.1 0.170.611.352.335.288.6613.318.6 0.180.631.382.385.418.8813.619.0 0.190.641.412.445.539.0813.919.4 0.200.661.442.495.659.2714.219.8 0.220.681.492.585.869.6214.820.6 0.240.701.542.676.059.9315.221.3 >0.24CONSULTFACTORYFORVACUUMSETTINGSGREATERTHAN0.24BARG
s)Size
Example—FlowCapacityCalculation 1. Read flow capacity at set vacuum from table Flow = 4,530 NCMH 6" Model 1202B 2. Calculate over-vacuum % OV = [(0.17 - 0.12)/0.12] x 100 = 42% 0.12 barg Set Vacuum [Ps] 3. Read “C” factor from table “C” = 0.55 0.17 barg Flowing Vacuum [Pf] 4. Calculate flow capacity Flow = 0.55 x 4,530 = 2,492 NCMH Example—To find “C” factor from table: Read “C” factor for 72% over-vacuum at intersection of row 40 and column 2 “C” factor at 42% OV = 0.55 “C”FactorTable %OV0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00
MODEL 1220A FLOW CAPACITY CALCULATION

SERIES 1800

• Sizes // 2" (DN 50) through 12" (DN 300) flange sizes

• Available in aluminum, carbon steel, stainless steel

• Stable full lift at 10% overpressure

• Modulating action

• Near zero blowdown (reseats near set pressure)

• Ability to achieve set pressure/vacuum very close to tank maximum allowable working pressure/vacuum

FULL LIFT PRESSURE/VACUUM RELIEF VALVE

The most notable advantage of the Groth Full Lift Type Valve Compared to Standard Pressure/ Vacuum Relief Valves is its’ ability to open at 10% overpressure while standard Pressure/Vacuum Relief Valves achieve full open capacity at 100% overpressure. The use of a Full Lift Type Valve allows the user to select the valve set pressure (vacuum) within 10% of the tank Maximum Allowable Working Pressure (vacuum). This is important because operation near the tank design pressure greatly reduces the breathing losses of the product in the tank.

WHAT IS A FULL LIFT TYPE VALVE?

A Full Lift Type Valve is a relief valve which attains full stable lift at only 10% overpressure. Like all Groth Pressure/Vacuum Relief Valves, the Full Lift Type Valve is a modulating valve which offers near zero blowdown, meaning it reseats near set pressure. These performance capabilities are possible due to the harmonization of the nozzle, seating, and pallet areas such that the valve will achieve stable lift at only 10% above the set pressure/vacuum.

BENEFITS

• Ability to operate process closer to Tank MAWP, increasing operating range of process

• Minimal seat leakage to prevent fugitive emission and conserve tank product

• Narrow valve operating range (from seal to full open) maximizes tank operating range and reduces total vapor emissions

• Stable lift ensures that the venting requirements of the process are reliably met

• Reduced seat leakage, low overpressure, and near zero blowdown characteristics to allow for process maintenance, minimal product loss and better tank corrosion maintenance

VALVES & TANK EQUIPMENT // PAGE 13 www.grothcorp.com

MODEL 1800

2″ 13.625” 13″ 9.5”

50 mm346 mm330 mm241 mm

3″ 18″ 13.625”11.5″

30 mm457 mm346 mm292 mm

4″ 19.75″ 15.875” 13″

100 mm503 mm403 mm130 mm

6″ 27.75″ 22.25″ 19″

150 mm704 mm565 mm482 mm

8″ 33.875”26.375”23.625”

200 mm860 mm669 mm600 mm

10″ 48.875”28.875”30.75”

250 mm1038 mm733 mm781 mm

12″ 46″ 32.875” 36″

300 mm1165 mm835 mm914 mm

2”14.25”12.625”7.5” 50 mm361 mm320 mm 191 mm

3”18”15.125”9” 30 mm457 mm384 mm 229 mm

4”19.25”18.25” 11” 100 mm 489 mm463 mm 279 mm

6”26.25”23.75”13.5” 150 mm 673 mm603 mm 343 mm

8”32.5”28.5”16” 200 mm 826 mm723 mm 406 mm

10”37.75”34.25”19” 250 mm 959 mm876 mm 483 mm

12”42.75”39.125”21” 300 mm 1086 mm 993 mm 533 mm

2”7”5.5” 50 mm178 mm140 mm 3”8.125”6” 30 mm206 mm152 mm

4”9.5”6.5” 100 mm241 mm165 mm

6”12.75”8.5” 150 mm324 mm216 mm

8”15.25”10.75” 200 mm387 mm273 mm

10”18”12.5” 250 mm457 mm318 mm

12”20.625”15”

300 mm524 mm381 mm

2”9.5”6.625” 50 mm241 mm168 mm

3”11.5”8.625” 30 mm292 mm219 mm

4”13”10.5625” 100 mm330 mm268 mm

6”19”15” 150 mm482 mm381 mm

8”23.625”16.625”

200 mm600 mm422 mm

10”30.75”17” 250 mm781 mm431 mm

12”36”18”

300 mm914 mm457 mm

VALVES & TANK EQUIPMENT // PAGE 14 www.grothcorp.com
Inlet Flg A Length B Height C Width
Inlet Flg A Length B Height C Width
Inlet Flg DE
Inlet Flg A Diameter B Height
1820MODEL 1830 C A D B A B A C B A
MODEL

MODEL 1860 MODEL 1810MODEL 1870

2”8.625”9.375”7.5”

50 mm219 mm238 mm191 mm

3”10”11.125”9”

30 mm254 mm282 mm229 mm

4” 11” 13.875” 11”

100 mm 279 mm352 mm279 mm

6”14.5”17.375”13.5”

150 mm 368 mm441 mm343 mm

8”18”21.25”16”

200 mm 457 mm539 mm406 mm

10”20.75”23.625”19”

250 mm 527 mm600 mm483 mm

12”24.75”26.625”21”

300 mm 629 mm676 mm533 mm

2”4.125”5.5”

50 mm105 mm140 mm

3”5”6” 30 mm127 mm152 mm

4”6.5”6.5”

100 mm165 mm165 mm

6”8.5”8.5”

150 mm216 mm216 mm

8”9.75”10.75”

200 mm248 mm273 mm

10”10.25”12.5”

250 mm260 mm318 mm

12” 11” 15”

300 mm279 mm381 mm

2”11.625”6.875”6” 50 mm295 mm174 mm152 mm

3”15.75”7.75”7.75” 30 mm400 mm196 mm197 mm

4”17.25”9.625”9” 100 mm438 mm244 mm229 mm

6”23.5”11.875”12” 150 mm597 mm301 mm305 mm

8”28.5”15.5”14.5” 200 mm724 mm393 mm368 mm

10”33.25”18.625”16.5” 250 mm845 mm473 mm419 mm

12”37.25”21.625”19” 300 mm946 mm549 mm483 mm

3”8.625”9.25”

4”10”11.5”

8”14.5”17.75” 200 mm368 mm451 mm

10”18”21.25” 250 mm457 mm539 mm

12”20.75”25.75” 300 mm527 mm654 mm

14”24.75”29.25” 350 mm629 mm742 mm

mm229 mm152 mm

6” 11” 6.5” 150 mm279 mm165 mm

8”13.5”8.5” 200 mm343 mm216 mm

10”16”10.75”

250 mm406 mm273 mm

12”19”12.5”

300 mm483 mm318 mm

14”21”15” 350 mm533 mm381 mm

VALVES & TANK EQUIPMENT // PAGE 15 www.grothcorp.com Inlet Flg A Length B Height C Width
Inlet Flg DE
Inlet Flg A Length B Height C Width
Size Flange A Length B Height
80
mm219 mm235 mm
100
mm
150
mm254 mm292
6” 11” 14.25”
mm279 mm362 mm
Size Flange C Width D
80
mm
100
3”7.5”5.5”
mm191 mm140
4”9”6”
A A A C C C B B B D D E

MODEL

FlowCapacityat10%Overpressureand60°F[1000SCFH]

FlowCapacityat10%Overpressureand0°C[1000NCMH]

252.450.1020.2250.3880.881.522.403.44 504.900.1450.3180.5481.242.153.404.87 757.350.1770.3900.6711.522.644.165.96 1009.800.2040.4500.7751.763.054.806.89 12512.30.2280.5030.8671.973.415.377.70 15014.70.2500.5510.9492.153.735.888.43 20019.60.2890.6361.102.494.316.799.74 25024.50.3230.7111.222.784.817.5910.9 30029.40.3540.7791.343.045.278.3111.9 35034.30.3820.8411.453.295.698.9712.9

VALVES & TANK EQUIPMENT // PAGE 16 www.grothcorp.com
SetPressureSize InWCOSI 2” (DN50) 3” (DN75) 4” (DN100) 6” (DN150) 8” (DN200) 10” (DN250) 12” (DN300) 0.90.53.297.2512.528.349.177.3111 1.00.63.547.7913.430.552.783.1119 2.01.25.0011.019.043.174.6118169 3.01.76.1313.523.252.791.3144206 4.02.37.0715.626.860.9105166238 6.03.58.6619.132.974.6129204292 8.04.610.022.037.986.1149235337 10.05.811.224.642.496.2167263377 12.06.912.227.046.4105182288413 13.98.013.129.049.9113196309443
SetPressureSize mmWCmbar 2” (DN50) 3” (DN75) 4” (DN100) 6” (DN150) 8” (DN200) 10” (DN250) 12” (DN300)
1800A
PRESSURE RELIEF CAPACITY
//

FlowCapacityat10%Over-Vacuumand60°F[1000SCFH] SetVacuumSize

252.450.0490.1100.1960.440.7801.221.76 504.900.0690.1550.2760.6201.101.732.48 757.350.0840.1900.3380.7601.352.113.04 1009.800.0970.2190.3890.8801.562.433.50 12512.30.1090.2450.4350.9801.742.723.91 15014.70.1190.2670.4751.071.902.974.28 20019.60.1370.3080.5471.232.193.424.93 25024.50.1530.3430.6101.372.443.815.49 30029.40.1670.3750.6701.502.674.176.00 35034.30.1790.4040.7201.622.874.496.46

VALVES & TANK EQUIPMENT // PAGE 17 www.grothcorp.com
InWCOSI 2” (DN50) 3” (DN75) 4” (DN100) 6” (DN150) 8” (DN200) 10” (DN250) 12” (DN300)
1.00.61.693.816.8015.227.142.361.0
FlowCapacityat10%Over-Vacuumand0°C[1000NCMH] SetVacuumSize mmWcmbar 2” (DN50) 3” (DN75) 4” (DN100) 6” (DN150) 8” (DN200) 10” (DN250) 12” (DN300)
1800A // VACUUM RELIEF CAPACITY
0.90.51.573.546.3014.225.239.456.7
2.01.22.395.379.6021.538.260.086.0 3.01.72.926.611.726.346.773.0105 4.02.33.377.6013.530.353.984.0121 6.03.54.119.3016.537.066.0103148 8.04.64.7410.718.942.676.0118170 10.05.85.2811.921.147.584.0132190 12.06.95.8013.023.151.992.0144208 13.98.06.2013.924.755.699.0154222
MODEL

MODEL 1820 // PRESSURE

FlowCapacityat10%Overpressureand60°F[1000SCFH]

757.350.1350.2980.5131.172.023.184.56 1009.800.1560.3440.5931.352.333.675.27 12512.30.1750.3850.6631.502.604.115.89 15014.70.1910.4220.7261.652.854.506.45 20019.60.2210.4870.8381.903.295.197.45 25024.50.2470.5440.9372.133.685.808.32 30029.40.2700.5961.032.334.036.369.12 35034.30.2920.6431.112.514.356.869.84

VALVES & TANK EQUIPMENT // PAGE 18 www.grothcorp.com
RELIEF
CAPACITY
SetPressureSize InWCOSI 2” (DN50) 3” (DN75) 4” (DN100) 6” (DN150) 8” (DN200) 10” (DN250) 12” (DN300)
FlowCapacityat10%Overpressureand0°C[1000NCMH] SetPressureSize mmWCmbar 2” (DN50) 3” (DN75) 4” (DN100) 6” (DN150) 8” (DN200) 10” (DN250) 12” (DN300) 252.450.0780.1720.2970.6731.171.842.63
0.90.52.525.559.5021.737.559.185.0 1.00.62.715.9610.323.340.363.691.0 2.01.23.838.4014.532.957.090.0129 3.01.74.6810.317.840.369.8110158 4.02.35.4111.920.546.681.0127182 6.03.56.6214.625.157.099.0156223 8.04.67.6016.829.065.8114180258 10.05.88.5018.832.473.6127201288 12.06.99.4020.635.581.0140220316 13.98.010.122.238.187.0150236339
504.900.1110.2440.4190.9521.652.603.73

MODEL 1820 // VACUUM

FlowCapacityat10%Over-Vacuumand60°F[1000SCFH]

252.450.0490.1100.1960.4400.781.221.76 504.900.0690.1550.2760.6201.101.732.48 757.350.0840.1900.3380.7601.352.113.04 1009.800.0970.2190.3890.8801.562.433.50 12512.30.1090.2450.4350.9801.742.723.91 15014.70.1190.2670.4751.071.902.974.28 20019.60.1370.3080.5471.232.193.424.93 25024.50.1530.3430.6101.372.443.815.49 30029.40.1670.3750.6701.502.674.176.00 35034.30.1790.4040.7201.622.874.496.46

VALVES & TANK EQUIPMENT // PAGE 19 www.grothcorp.com
RELIEF CAPACITY
SetVacuumSize InWCOSI 2” (DN50) 3” (DN75) 4” (DN100) 6” (DN150) 8” (DN200) 10” (DN250) 12” (DN300) 0.90.51.573.546.3014.225.239.456.7 1.00.61.693.816.8015.227.142.361.0 2.01.22.395.379.6021.538.260.086.0 3.01.72.926.6011.726.346.773.0105
6.03.54.119.3016.537.066.0103148 8.04.64.7410.718.942.676.0118170 10.05.85.2811.921.147.584.0132190 12.06.95.8013.023.151.992.0144208
FlowCapacityat10%Over-Vacuumand0°C[1000NCMH] SetVacuumSize mmWCmbar 2” (DN50) 3” (DN75) 4” (DN100) 6” (DN150) 8” (DN200) 10” (DN250) 12” (DN300)
4.02.33.377.6013.530.353.984.0121
13.98.06.2013.924.755.699.0154222

MODEL 1830 // PRESSURE

FlowCapacityat10%Overpressureand0°C[1000NCMH]

757.350.1770.3900.6711.522.644.165.96 1009.800.2040.4500.7751.763.054.806.89 12512.30.2280.5030.8671.973.415.377.70 15014.70.2500.5510.9492.153.735.888.43 20019.60.2890.6361.102.494.316.799.74 25024.50.3230.7111.222.784.817.5910.9 30029.40.3540.7791.343.045.278.3111.9 35034.30.3820.8411.453.295.698.9712.9

VALVES & TANK EQUIPMENT // PAGE 20 www.grothcorp.com
SetPressureSize InWCOSI 2” (DN50) 3” (DN75) 4” (DN100) 6” (DN150) 8” (DN200) 10” (DN250) 12” (DN300) 0.90.53.297.2512.528.349.177.3111 1.00.63.547.7913.430.552.783.1119 2.01.25.0011.019.043.174.6118169 3.01.76.1313.523.252.791.3144206 4.02.37.0715.626.860.9105166238 6.03.58.6619.132.974.6129204292 8.04.610.022.037.986.1149235337 10.05.811.224.642.496.2167263377 12.06.912.227.046.4105182288413 13.98.013.129.049.9113196309443
RELIEF CAPACITY FlowCapacityat10%Overpressureand60°F[1000SCFH]
SetPressureSize mmWCmbar 2” (DN50) 3” (DN75) 4” (DN100) 6” (DN150) 8” (DN200) 10” (DN250) 12” (DN300) 252.450.1020.2250.3880.8801.522.403.44
504.900.1450.3180.5481.242.153.404.87

MODEL 1860 // PRESSURE

FlowCapacityat10%Overpressureand60°F[1000SCFH]

504.900.1110.2440.4190.9521.652.603.73 757.350.1350.2980.5131.172.023.184.56 1009.800.1560.3440.5931.352.333.675.27 12512.30.1750.3850.6631.502.604.115.89 15014.70.1910.4220.7261.652.854.506.45 20019.60.2210.4870.8381.903.295.197.45 25024.50.2470.5440.9372.133.685.808.32 30029.40.2700.5961.032.334.036.369.12 35034.30.2920.6431.112.514.356.869.84

VALVES & TANK EQUIPMENT // PAGE 21 www.grothcorp.com
RELIEF CAPACITY
InWCOSI 2” (DN50) 3” (DN75) 4” (DN100) 6” (DN150) 8” (DN200) 10” (DN250) 12” (DN300)
SetPressureSize
FlowCapacityat10%Overpressureand0°C[1000NCMH] SetPressureSize mmWCmbar 2” (DN50) 3” (DN75) 4” (DN100) 6” (DN150) 8” (DN200) 10” (DN250) 12” (DN300)
0.90.52.525.559.521.737.559.185.0 1.00.62.715.9610.323.340.363.691.0 2.01.23.838.4014.532.957.090.0129 3.01.74.6810.317.840.369.8110158 4.02.35.4111.920.546.681.0127182 6.03.56.6214.625.157.099.0156223 8.04.67.6016.829.065.8114180258 10.05.88.5018.832.473.6127201288 12.06.99.4020.635.581.0140220316 13.98.010.122.238.187.0150236339
252.450.0780.1720.2970.6731.171.842.63

MODEL 1810 // VACUUM

FlowCapacityat10%Over-Vacuumand60°F[1000SCFH]

13.98.06.2013.924.755.699.0154222

252.450.0490.1100.1960.4400.781.221.76 504.900.0690.1550.2760.6201.101.732.48 757.350.0840.1900.3380.7601.352.113.04 1009.800.0970.2190.3890.8801.562.433.50 12512.30.1090.2450.4350.9801.742.723.91 15014.70.1190.2670.4751.071.902.974.28 20019.60.1370.3080.5471.232.193.424.93 25024.50.1530.3430.6101.372.443.815.49 30029.40.1670.3750.6701.502.674.176.00 35034.30.1790.4040.7201.622.874.496.46

VALVES & TANK EQUIPMENT // PAGE 22 www.grothcorp.com
RELIEF CAPACITY
SetVacuumSize InWCOSI 2” (DN50) 3” (DN75) 4” (DN100) 6” (DN150) 8” (DN200) 10” (DN250) 12” (DN300) 0.90.51.573.546.3014.225.239.456.7 1.00.61.693.816.8015.227.142.361.0 2.01.22.395.379.6021.538.260.086.0 3.01.72.926.6011.726.346.773.0105 4.02.33.377.6013.530.353.984.0121 6.03.54.119.3016.537.066.0103148 8.04.64.7410.718.942.676.0118170 10.05.85.2811.921.147.584.0132190 12.06.95.8013.023.151.992.0144208
FlowCapacityat10%Over-Vacuumand0°C[1000NCMH] SetVacuumSize mmWCmbar 2” (DN50) 3” (DN75) 4” (DN100) 6” (DN150) 8” (DN200) 10” (DN250) 12” (DN300)

MODEL 1870 // VACUUM

FlowCapacityat10%Over-Vacuumand60°F[1000SCFH] SetVacuumSize

504.900.1210.2710.4821.081.933.014.34 757.350.1470.3320.5901.332.363.685.31 1009.800.1700.3820.6801.532.724.256.12 12512.30.1900.4270.7591.713.044.746.83 15014.70.2080.4670.8301.873.325.197.47 20019.60.2390.5380.9562.153.825.978.60 25024.50.2660.5991.072.404.266.669.59 30029.40.2910.6551.162.624.667.2710.5 35034.30.3130.7051.252.825.017.8311.3

VALVES & TANK EQUIPMENT // PAGE 23 www.grothcorp.com
RELIEF
CAPACITY
InWCOSI 3” (DN75) 4” (DN100) 6” (DN150) 8” (DN200) 10” (DN250) 12” (DN300) 14” (DN350)
FlowCapacityat10%Over-Vacuumand0°C[1000NCMH] SetVacuumSize mmWCmbar 3” (DN75) 4” (DN100) 6” (DN150) 8” (DN200) 10” (DN250) 12” (DN300) 14” (DN350)
0.90.52.756.1811.024.744.068.798.9 1.00.62.956.6511.826.647.373.8106 2.01.24.179.3816.737.566.7104150 3.01.75.1011.520.445.981.6128184 4.02.35.8813.223.552.994.1147212 6.03.57.1816.228.764.6115180259 8.04.68.2718.633.174.4132207298 10.05.89.2220.736.983.0147230332 12.06.910.122.640.390.6161252362 13.98.010.824.343.197.1173270388
252.450.0850.1920.3410.7701.372.133.07

SERIES 1800

HOW TO ORDER

For easy ordering, select proper model numbers

VALVES & TANK EQUIPMENT // PAGE 24 www.grothcorp.com
MODEL#SIZEMATERIALOPTIONS 1800A 1820A 1830A 1860A 1810A 1870A 1 = Aluminum 3 = Carbon Steel 5 = Stainless Steel
= No Options Z = Special Options
= No Jacket J = Steam Jacket
= Spacer
= Steam Jacket & Spacer
Material
B = Buna-N T = Fluoropolymer V = FKM
= Special Pallet Material Seat Material Body Material 02" Thru 14" EXAMPLE Indicates a 2" Model 1800A with Aluminum Body and Seat, Stainless Steel Pallet, Fluoropolymer Seat Diaphragm, and no other options. 1800A021T1O5O
O
O
S
H
Diaphragm
(Seat):
Z

MODEL 1220A

• Sizes // 2" through 12"

• Pressure settings // 0.5 oz/in2 to 15 psig

• Vacuum settings // 0.5 oz/in2 to 12 psig

• Available in aluminum, carbon steel, stainless steel, fiberglass and other materials

• Modular construction

PRESSURE / VACUUM RELIEF

VALVE WITH PIPE-AWAY FEATURE

Model 1220A is used for pressure and vacuum relief where vapors must be piped away. Escaping vapors are piped away through a flanged outlet connection. This helps to provide increased fire protection and safety.

SPECIAL FEATURES

Model 1220A offers Groth’s special “cushioned air” seating. Superior performing fluoropolymer seating diaphragms are standard to minimize sticking caused by resinous vapors and atmospheric moisture. The Model 1220A has a self draining housing body and drip rings to protect seating surfaces from condensate and freezing. This design also avoids pressure or vacuum buildup due to binding or clogging of the valve. Buna-N, FKM, and other seating diaphragms can be provided when required. Model 1221B may be spring loaded when required for use on blanketed tanks or other type installation requiring higher settings. To insure the proper alignment of seating surfaces there is peripheral guiding and a center stabilizing stem.

VALVES & TANK EQUIPMENT // PAGE 25 www.grothcorp.com
MODEL 1220A MODEL 1221B

SPECIFICATIONS

C A D E

Specifications

†W.P. = Working Pressure. ‡On spring loaded valves, change model number. ◊150# R.F. drilling compatibility F.F. on aluminum and R.F. on carbon steel and stainless steel alloys. Fiberglass dimensions on request. 16 oz/in2 set with spacer. SS set weights-consult factory. *Some sizes require non-ferrous components to achieve 0.5 oz/in2 setting. See TPD for Vacuum Settings

• Include model number and setting when ordering.

• For special options, consult factory

• When ordering steam jacket, include steam pressure/temperature. * Stainless steel guides, stems are

O = No Options Z = Special Options O = No Jacket J = Steam Jacket S = Spacer H = Steam Jacket & Spacer

Diaphragm Material (Seat): B = Buna-N T = Fluoropolymer V = FKM

Z = Special

=

VALVES & TANK EQUIPMENT // PAGE 26 www.grothcorp.com Inlet Flg◊ (Metric) Outlet Flg◊ (Metric) Max.Set Pressure Weight Loaded Max.Set Vacuum. Weight Loaded Max. Setting Spring Loaded Min. Setting Weight Loaded Max. W.P.† forMin. Vacuum Setting Min.Vac. Setting for Max. W.P.† A Length (Metric) B Height (Metric) C Width (Metric) D (Metric) E (Metric) Approx. Ship Wt.Lbs. (Aluminum) 2"3"11oz/in212oz/in214.25"12.62"7.50"7"5.50"26 (50 mm)(76 mm)(48.2 gm/cm2)(52.7 gm/cm2) (362 mm)(321 mm)(191 mm)(178 mm)(140 mm)(12 kg)
211oz/in218"15.12"9"8.12"6"34 (80 mm)(102 mm)(57.0 gm/cm2)(48.3 gm/cm2) (457 mm)(384 mm)(229 mm)(206 mm)(152 mm)(16 kg) 4"6"16oz/in211oz/in219.25"18.25"11"9.50"6.50"49 (100 mm)(152 mm)(70.3 gm/cm2)(48.3 gm/cm2) (489 mm)(464 mm)(279 mm)(241 mm)(165 mm)(22 kg) 6"8"16oz/in216oz/in226.50"23.75"13.50"12.75"8.50"93
(673 mm)(603 mm)(343 mm)(324 mm)(216 mm)(42 kg) 8"10"16oz/in216oz/in232.50"28.50"16"15.25"10.75"137 (200 mm)(254 mm)(70.3 gm/cm2)(70.3 gm/cm2) (826 mm)(724 mm)(406 mm)(387 mm)(273 mm)(62 kg) 10"12"16oz/in216oz/in237.75"34.50"19"18"12.50"186 (250 mm)(305 mm)(70.3 gm/cm2)(70.3 gm/cm2) (959 mm)(876 mm)(483 mm)(457 mm)(318 mm)(85 kg) 12"14"16oz/in216oz/in242.75"39.12"21"20.62"15"260 (300 mm)(356 mm)(70.3 gm/cm2)(70.3 gm/cm2) (1086 mm)(994 mm)(533 mm)(524 mm)(381 mm)(118 kg)
3"4"13oz/in
(150 mm)(203 mm)(70.3 gm/cm2)(70.3 gm/cm2)
B
subject to change without notice. Certified dimensions available upon request. 15 psig SPRING LOADED PRESSURE (1.05 kg/cm 2 ) 12 psig SPRING LOADED VACUUM (0.84 kg/cm 2 ) *0.5 oz/in 2 WEIGHT LOADED (2.20 gm/cm 2 )
MAWP
MODEL#SIZEMATERIALOPTIONS 1220A Weight Loaded 1221B Pressure Spring 1222B Vacuum Spring 1223B Pressure
Vacuum
1 = Aluminum 3 = Carbon Steel 5 = Stainless Steel 6
Vinyl Ester Resin 7
Furan Z
and
For easy ordering, select proper model numbers
&
Springs
=
=
Special
Pallet Material Seat Material Body Material 02" Thru 12"
carbon steel
Stainless steel seats standard
carbon steel bodies. NOTES EXAMPLE Indicates a 2" Model 1220A with Aluminum Body and Seat, Stainless Steel Pallet, Fluoropolymer Seat Diaphragm, and no other options. 1220A021T1O5O
standard with aluminum and
bodies.
with
HOW TO ORDER

MODEL 1220A/1222B // PRESSURE RELIEF CAPACITY

0.870.506.8713.325.252.782.6135175 1.000.587.3914.327.156.688.8145188 1.731.009.7118.835.674.3117190247 2.001.1610.420.238.279.8125205265

2.601.5011.923.043.590.8143233302

3.001.7312.824.746.897.5153250324 3.462.0013.726.650.2105164268348

4.002.3114.728.653.9112177288374

6.003.4718.035.065.9137215351456 8.004.6220.740.475.8157248404525 10.05.7823.145.184.6175276450584 12.06.9325.249.492.4191301491638 15.08.6628.155.2103211335546709 20.011.632.263.7118241383625811 25.014.435.871.2131267424692898 30.017.339.077.9143289460751975

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear sted.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 27 www.grothcorp.com
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 112,000 SCFH 6" Model 1220A 2. Calculate overpressure % OP = [(7 - 4)/4] x 100 = 75% 4 InWC set pressure [Ps] 3. Read “C” factor from table “C” = 0.87 7 InWC flowing pressure [Pf] 4. Calculate flow capacity Flow = 0.87 x 112,000 = 97,440 SCFH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.87 “C”FactorTable %OP0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00 MODEL 1220A FLOW CAPACITY CALCULATION AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000StandardCubicFeetperHourat60°F SetPressure(Ps)Size InWCoz/in22" (50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)

222.160.190.370.711.482.333.804.93 504.900.290.561.072.233.505.727.42

12512.30.460.891.683.505.518.9911.7 15014.70.500.981.843.826.029.8012.7 17517.20.541.061.994.126.4910.613.7 20019.60.581.132.124.396.9211.314.7 22522.10.611.202.254.657.3312.015.5 25024.50.651.262.364.897.7112.616.3 27527.00.681.322.485.118.0713.217.1 30029.40.701.382.585.338.4213.717.8 37536.80.781.542.885.919.4015.319.8 50049.00.901.783.306.7510.717.522.7 62561.31.001.993.677.4611.919.425.1 75073.51.092.183.998.0712.921.027.3

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 28 www.grothcorp.com
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 3,140 NCMH 6" Model 1220A 2. Calculate overpressure % OP = [(175 - 100)/100] x 100 = 75% 100 mmWC Set Pressure [Ps] 3. Read “C” factor from table “C” = 0.87 175 mmWC Flowing Pressure [Pf] 4. Calculate flow capacity Flow = 0.87 x 3,140 = 2,732 NCMH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.87 “C”FactorTable %OP0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00 MODEL 1220A FLOW CAPACITY CALCULATION AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000NormalCubicMetersperHourat0°C SetPressure(Ps)Size mmWCmb2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)
MODEL 1220A/1222B // PRESSURE RELIEF CAPACITY
757.350.360.691.312.724.286.999.10 1009.800.410.801.513.144.938.0510.4

0.870.504.7010.316.034.760.591.1129

1.000.585.0511.017.237.365.097.9138

1.731.006.6314.522.649.085.3129182

2.001.167.1215.624.252.691.6138195

2.601.508.1017.727.659.8104157222

3.001.738.7019.029.664.2112169238

3.462.009.3320.431.868.9120181256

4.002.3110.021.934.174.0129194274

6.003.4712.226.741.590.1157237334

8.004.6214.030.647.7103180272384 10.05.7815.634.053.0115200302427 12.06.9317.037.157.8125218329465 15.08.6618.841.164.0139242365516 20.011.621.446.872.9158276415587 25.014.423.651.580.3174304457646 30.017.325.455.686.6188327493697

Flow capacity values listed above are based on full open valves at 100% over-vacuum.

Read the flow capacity at 100% over-vacuum directly from the table above. Use linear interpolation if the set vacuum is not listed.

If the allowable over-vacuum is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, consult your Groth Representative.

Calculate the percentage over-vacuum by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OV = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% over-vacuum according to the following example.

VALVES & TANK EQUIPMENT // PAGE 29 www.grothcorp.com
Example—FlowCapacityCalculation 1. Read flow capacity at set vacuum from table Flow = 74,000 SCFH 6" Model 1220A 2. Calculate over-vacuum % OV = [(7 - 4)/4] x 100 = 75% 4 InWC Set Vacuum [Ps] 3. Read “C” factor from table “C” = 0.87 7 InWC Flowing Vacuum [P ] 4. Calculate flow capacity Flow = 0.87 x 74,000 = 64,380 SCFH Example—To find “C” factor from table: Read “C” factor for 75% over-vacuum at intersection of row 70 and column 5 “C” factor at 75% OV = 0.87 “C”FactorTable %OV0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00 MODEL 1220A FLOW CAPACITY CALCULATION MODEL 1220A/1221B // VACUUM RELIEF CAPACITY AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000StandardCubicFeetperHourat60°F SetVacuum(Ps)Size InWCoz/in22" (50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" 250mm) 12" (300mm)

25024.50.440.961.493.235.648.4912.0 27527.00.461.001.563.385.908.8812.6 30029.40.481.041.623.526.149.2513.1 37536.80.531.161.803.916.8110.314.5 50049.00.601.322.054.457.7511.716.5 62561.30.661.452.264.908.5412.918.2 75073.50.721.572.445.299.2213.919.6

Flow capacity values listed above are based on full open valves at 100% over-vacuum.

Read the flow capacity at 100% over-vacuum directly from the table above. Use linear interpolation if the set vacuum is not listed.

If the allowable over-vacuum is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, consult your Groth Representative.

Calculate the percentage over-vacuum by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OV = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% over-vacuum according to the following example.

VALVES & TANK EQUIPMENT // PAGE 30 www.grothcorp.com
Example—FlowCapacityCalculation 1. Read flow capacity at set vacuum from table Flow = 2,080 NCMH 6" Model 1220A 2. Calculate over-vacuum % OV = [(175 - 100)/100] x 100 = 75% 100 mmWC Set Vacuum [Ps] 3. Read “C” factor from table “C” = 0.87 175 mmWC Flowing Vacuum [P ] 4. Calculate flow capacity Flow = 0.87 x 2,080 = 1,810 NCMH Example—To find “C” factor from table: Read “C” factor for 75% over-vacuum at intersection of row 70 and column 5 “C” factor at 75% OV = 0.87 “C”FactorTable %OV0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00 MODEL 1220A FLOW CAPACITY CALCULATION MODEL 1220A/1221B // VACUUM RELIEF CAPACITY AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000NormalCubicMetersperHourat0°C SetVacuum(Ps)Size mmWCmb2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)
757.350.240.530.831.813.154.746.70 1009.800.280.620.962.083.625.467.72 12512.30.310.691.072.324.046.098.60 15014.70.340.751.172.534.416.659.40 17517.20.370.811.262.734.757.1610.1 20019.60.390.861.342.915.077.6410.8
222.160.130.290.450.981.712.583.65 504.900.200.440.681.482.583.885.48
22522.10.420.911.423.085.368.0811.4

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 31 www.grothcorp.com
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 448,000 SCFH 6" Model 1221B 2. Calculate overpressure % OP = [(7 - 4)/4] x 100 = 75% 4 psig Set Pressure [Ps] 3. Read “C” factor from table “C” = 0.83 7 psig Flowing Pressure [Pf] 4. Calculate flow capacity Flow = 0.83 x 448,000= 371,840 SCFH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.83 “C”FactorTable %OP0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00 MODEL 1220A FLOW CAPACITY CALCULATION MODEL 1221B/1223B // PRESSURE RELIEF CAPACITY AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000StandardCubicFeetperHourat60°F SetPressure(Ps)Size psig2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)
2.0040.377.41343045007671070
7.0080.4158274622102215682188 8.0086.7171297674110716992371 9.0092.8184319724118918252546
1.0028.053.492.5210345529739
3.0050.296.91683816259601340 4.0058.811419844873611301577 5.0066.513022551083812861794 6.0073.714425056893214311997
10.098.6196340772126719452714 11.0104208360818134320622877 12.0110219380863141721763036 13.0115231400907148922863189 14.0120241418949155923933339 15.0125252437991162724983486

MODEL 1221B/1223B // PRESSURE RELIEF CAPACITY

0.070.821.572.726.1610.115.521.7 0.100.991.893.287.4512.218.826.2 0.151.232.364.099.2815.223.432.6 0.201.432.764.8010.917.927.438.3 0.251.623.145.4412.320.331.143.4 0.301.793.486.0413.722.534.548.2 0.351.953.816.6115.024.637.852.7 0.402.104.127.1416.226.640.957.0 0.452.254.417.6617.428.543.861.1 0.502.394.708.1618.530.446.665.1 0.552.524.988.6419.632.249.468.9 0.602.655.259.1020.633.952.172.6 0.702.895.7610.022.737.257.279.7 0.803.136.2510.824.640.462.186.5 0.903.356.7211.726.543.566.793.1 1.003.567.1812.528.346.471.299.4

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 32 www.grothcorp.com
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 16,200 NCMH 6" Model 1221B 2. Calculate overpressure % OP = [(0.7 - 0.4)/0.4] x 100 = 75% 0.4 barg Set Pressure [Ps] 3. Read “C” factor from table “C” = 0.83 0.7 barg Flowing Pressure [Pf] 4. Calculate flow capacity Flow = 0.83 x 16,200 = 13,446 NCMH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.83 “C”FactorTable %OP0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00 MODEL 1220A FLOW CAPACITY CALCULATION AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000NormalCubicMetersperHourat0°C SetPressure(Ps)Size barg2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)

MODEL 1222B/1223B // VACUUM RELIEF CAPACITY

Flow capacity values listed above are based on full open valves at 100% over-vacuum.

Read the flow capacity at 100% over-vacuum directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable over-vacuum is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, consult your Groth Representative.

Calculate the percentage over-vacuum by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OV = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% over-vacuum according to the following example.

VALVES & TANK EQUIPMENT // PAGE 33 www.grothcorp.com
Example—FlowCapacityCalculation 1. Read flow capacity at set vacuum from table Flow = 166,000 SCFH 6" Model 1222B 2. Calculate over-vacuum % OV = [(3.50 - 2.0)/2.0] x 100 = 75% 2 psig Set Vacuum [Ps] 3. Read “C” factor from table “C” = 0.83 3.5 psig Flowing Vacuum [P ] 4. Calculate flow capacity Flow = 0.83 x 166,000 = 137,780 SCFH Example—To find “C” factor from table: Read “C” factor for 75% over-vacuum at intersection of row 70 and column 5 “C” factor at 75% OV = 0.83
“C”FactorTable %OV0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00 AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000StandardCubicFeetperHourat60°F SetVacuum(Ps)Size psig2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 1.0013.830.552.9120197302422 1.1014.531.955.4126206316442 1.2015.133.257.7131215330460 1.3015.734.559.9136223342478 1.4016.235.762.0141231355495 1.5016.836.964.0145239366511 1.7518.039.668.7156256393548 2.0019.142.073.0166272417582 2.2520.144.376.9174286439613 2.5021.046.380.4183300460641 2.7521.948.283.7190312478667 3.0022.749.986.6197323495691 3.2523.451.489.3203333511713 3.5024.052.891.8208342525732 >3.50CONSULTFACTORYFORVACUUMSETTINGSGREATERTHAN3.5PSIG
MODEL 1220A FLOW CAPACITY CALCULATION

MODEL 1222B/1223B // VACUUM RELIEF CAPACITY

0.070.410.901.553.525.778.8712.4 0.100.481.061.834.166.8310.514.6

0.170.611.352.335.288.6613.318.6 0.180.631.382.385.418.8813.619.0 0.190.641.412.445.539.0813.919.4 0.200.661.442.495.659.2714.219.8 0.220.681.492.585.869.6214.820.6 0.240.701.542.676.059.9315.221.3 >0.24CONSULTFACTORYFORVACUUMSETTINGSGREATERTHAN0.24BARG

Flow capacity values listed above are based on full open valves at 100% over-vacuum.

Read the flow capacity at 100% over-vacuum directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable over-vacuum is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, consult your Groth Representative.

Calculate the percentage over-vacuum by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OV = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% over-vacuum according to the following example.

VALVES & TANK EQUIPMENT // PAGE 34 www.grothcorp.com
Example—FlowCapacityCalculation 1. Read flow capacity at set vacuum from table Flow = 4,530 NCMH 6" Model 1222B 2. Calculate over-vacuum % OV = [(0.17 - 0.12)/0.12] x 100 = 42% 0.12 barg Set Vacuum [Ps] 3. Read “C” factor from table “C” = 0.55 0.17 barg Flowing Vacuum [Pf] 4. Calculate flow capacity Flow = 0.55 x 4,530 = 2,492 NCMH Example—To find “C” factor from table: Read “C” factor for 72% over-vacuum at intersection of row 40 and column 2 “C” factor at 42% OV = 0.55 “C”FactorTable %OP0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00 MODEL 1220A FLOW CAPACITY
AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000NormalCubicMetersperHourat0°C SetVacuum(Ps)Size barg2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)
CALCULATION
0.110.511.111.924.357.1411.015.3 0.120.531.151.994.537.4311.415.9 0.130.551.202.074.697.7011.816.5 0.140.561.242.144.857.9612.217.1 0.150.581.272.205.008.2112.617.6
0.160.601.312.275.148.4413.018.1

MODEL 1720A/1760A

• Same size inlet and outlet connections

• “Cushioned air” seating

• Non-sticking design

• Center and peripheral pallet guiding

• Self-draining body

• Factory tested for compliance with API 2000

• ISO-Certified manufacturing facility

• Higher set pressures (in weight loaded configuration) than standard pipe-away valves

VACUUM RELIEF VALVE WITH PIPE-AWAY FEATURE

Groth Series 1700 relief valves are designed with inlet and outlet flanges of the same size to reduce installation costs by having smaller downstream piping. Model 1720A valves are designed for systems requiring pressure and vacuum relief. Model 1760A valves are designed for systems requiring only pressure relief.

SPECIAL FEATURES

Model 1700 offers Groth’s special “cushioned air” seating. Superior performing fluoropolymer seating diaphragms minimize sticking caused by resinous vapors and atmospheric moisture. The Model 1700 has a self draining housing body and drip rings to protect seating surfaces from condensate and freezing. This design also avoids pressure or vacuum buildup due to binding or clogging of the valve. Buna-N, FKM, and other seating diaphragms can be provided when required. Available in 2”, 3” and 4” sizes and in carbon steel, stainless steel or fiberglass. Trim materials (seat and pallet components) are 316SS. Other materials available on request. Options include stainless steel weights.

SETTING RANGES

VALVES & TANK EQUIPMENT // PAGE 35 www.grothcorp.com
ModelSize(inches) StandardWeightsStainlessSteelWeights PressureVacuumPressureVacuum MinMaxMinMaxMinMaxMinMax 1720A 2X20.5330.517.40.5240.516.5 2.21422.1742.21032.271 3X30.5330.515.50.5240.515.2 2.21422.1662.21032.265 4X40.5330.516.50.5240.515.0 2.21422.1712.21032.264 1760A 2X20.533––0.524––2.2142––2.2103––3X30.533––0.524––2.2142––2.2103––4X40.533––0.524––
The1700Seriesreliefvalvesarealsoavailableinspringloadeddesignsforpressuresettingsupto15psig. OtheroptionsincludeFRP(FuranorDerakane)construction,positiveliftindicatorsandspecialcoatings.
Whitebarsinoz/in
2.Bluebarsinmbar.
2.2142––2.2103––
Consultthefactoryfordetails.

MODEL 1720/1760 // PRESSURE RELIEF CAPACITY

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 36 www.grothcorp.com
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 23,100 SCFH 3" Model 1760A 2. Calculate overpressure % OP = [(7 - 4)/4] x 100 = 75% 4 InWC Set Pressure [Ps] 3. Read “C” factor from table “C” = 0.87 7 InWC Flowing Pressure [Pf] 4. Calculate flow capacity Flow = 0.87 x 23,100 = 20,097 SCFH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.87 “C”FactorTable %OP0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00 MODEL 1220A FLOW CAPACITY CALCULATION AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000StandardCubicFeetperHourat60°F AirFlowCapacityat100%Overpressure(DoubleSetPressure) NormalCubicMetersperHourat0°C SetPressure[Ps]SizeSetPressure[Ps]Size InWCoz/in22"x2"3"x3"4"x4"mmWCmbar2"x2"3"x3"4"x4" 0.90.54.7910.718.1
3.01.78.9420.033.8757.35258577976 4.02.310.323.139.01009.802996671128 6.03.512.728.347.915014.73678181383 8.04.614.732.855.420019.64249461599 10.05.816.536.762.025024.547610601790 30029.452211641963 35034.356512592123 15.08.720.345.276.1 40039.260613492285 20.011.623.652.478.550049.068015142467 60058.874917572627 25.014.426.558.984.7 30.017.329.260.390.2 80078.487218772756
100098.098420522959 41.624.034.870.5102 1200118108622813243 51.930.039.378.3111 57.133.041.482.0116 1500147122923883374
1.00.65.1511.519.5252.45149332563 2.01.27.2916.327.6504.90211470797
34.620.031.564.594.6

MODEL 1720 // VACUUM RELIEF CAPACITY

MODEL 1220A FLOW CAPACITY CALCULATION

Flow capacity values listed above are based on full open valves at 100% over-vacuum.

Read the flow capacity at 100% over-vacuum directly from the table above. Use linear interpolation if the set vacuum is not listed.

If the allowable over-vacuum is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, consult your Groth Representative.

Calculate the percentage over-vacuum by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OV = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% over-vacuum according to the following example.

VALVES & TANK EQUIPMENT // PAGE 37 www.grothcorp.com
AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000StandardCubicFeetperHourat60°F AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) NormalCubicMetersperHourat0°C SetVacuum[Ps]SizeSetVacuum[Ps]Size InWCoz/in22"x2"3"x3"4"x4"mmWCmbar2"x2"3"x3"4"x4" 0.870.504.7010.316.0222.16130290450
757.35240530830
12512.33106901070
17517.23708101260
22522.14209101420 10.05.7815.634.053.025024.54409601490 27527.046010001560 12.06.9317.037.157.830029.448010401620 15.08.6618.841.164.037536.853011601800 20.011.621.446.872.950049.060013202050 25.014.423.651.580.362561.366014502260 27.716.024.653.883.880078.487218772756 75073.572015702440
1.00.585.0511.017.2252.45149332563 2.01.167.1215.624.2504.90200440680
4.02.3110.021.934.11009.80280620960
6.03.4712.226.741.515014.73407501170
8.04.6214.030.647.720019.63908601340
Example—FlowCapacityCalculation 1. Read flow capacity at set vacuum from table Flow = 21,900 SCFH 6" Model 1720A 2. Calculate over-vacuum % OV = [(7 - 4)/4] x 100 = 75% 4 InWC Set Vacuum [Ps] 3. Read “C” factor from table “C” = 0.87 7 InWC Flowing Vacuum [P ] 4. Calculate flow capacity Flow = 0.87 x 21,900 = 19,053 SCFH Example—To find “C” factor from table: Read “C” factor for 75% over-vacuum at intersection of row 70 and column 5 “C” factor at 75% OV = 0.87 “C”FactorTable %OV0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00
VALVES & TANK EQUIPMENT // PAGE 38 www.grothcorp.com
MODEL1720AMODEL1720AtopviewMODEL1760A White bars in inches or pounds. Blue bars in millimeters or kilograms. Model1720A Size (inches)ABCDEWeight 2X2 13.5014.636.506.754.7580 34337216517112136 3X3 18.0017.388.008.006.00105 45744120320315248 4X4 19.2519.509.009.136.50150 48949522923216568 Model1760A AABBCDDEWeight 7.7511.886.503.884.7550 1973021659912123 10.0014.138.004.756.0070 25435920312115232 10.7516.509.006.066.5092 27341922915416542 1720A 1760A 3 = Carbon Steel 5 = Stainless 6 = Vinyl Ester 7 = Furan Z = Special 5 = 316SS 6 = Vinyl Ester 7 = Furan Z = Special (See note regarding seat material) 5 = 316SS 6 = Vinyl Ester 7 = Furan Z = Special O = No Options Z = Special Options O = No Jacket N = Steam Jacket S = Vacuum Port Spacer H = Vacuum Port Spacer and Steam Jacket 02 03 04 • Include model number and setting when ordering. • For steam jacket, include steam pressure/temperature. • For special options, consult factory • Stainless steel seats are standard with stainless steel and carbon steel bodies. For easy ordering, select proper model numbers NOTES EXAMPLE Indicates a 3” x 3” Model 1720 A with CS body, 316SS seat, 316SS pallet, Buna-N diaphragm, no steam jacket and no special options. 1720A033B5O5O
B = Buna N K = FFKM T = Fluoropolymer V = FKM Z = Special MODEL#SIZE BODY MATERIAL SEAT MATERIAL PALLET MATERIAL DIAPHRAGM MATERIALJACKET SPECIAL OPTIONS D E A B BB E C DD AA
SPECIFICATIONS
HOW TO ORDER

MODEL 12-TH

•Size: 8” (200 mm)

•Bolting: API 12

•Available Pressure Settings:

4, 6, 8, 12, 16, 24 & 32 osig

•Available Vacuum Settings:

0.4, 0.9 & 3.5 osig

•Leak Rate:

1 SCFH air @ 90% of set pressure

•Materials of Construction:

Casting: Aluminum (Non-Sparking)

Envelope Gasket: HNBR, FKM, or Fluorosilicone

Vacuum Diaphragm: HNBR, FKM, Fluorosilicone, or Fluoropolymer

•Optional: Polyester/PTFE Coating

•Accessories: Flange (base) Gasket, Mounting Kit

PRESSURE/VACUUM RELIEF VALVE

The Model 12-TH Thief Hatch was designed to out perform the competition, with industry leading high flow rates and precision tolerances to provide a superior sealing performance. The leakage is less than 1 SCFH of air @ 90% of the set pressure, keeping your tanks in compliance with industry standards.

The Model 12-TH Thief Hatch incorporates a spring loaded pressure/vacuum relief valve within the device. Thief Hatches are used on steel or fiberglass (FRP) low pressure oil tanks. Providing access for level gauging, sampling, and overpressure/vacuum protection for the tanks, all in one compact design.

SPECIAL FEATURES

•Ultra-tight sealing reduces product leakage and fugitive emissions

•Higher flow capacity to protect from excessive pressure build up

•Designed for easy maintenance, thus reducing downtime and lower operational cost

•Corrosion resistance can be enhanced with FKM soft goods and coating

•Direct replacement for any standard round API 12 thief hatch

•Incorporates a mechanical lock system to be used with a pad lock or lock out bar

VALVES & TANK EQUIPMENT // PAGE 39 www.grothcorp.com

SPECIFICATIONS

VALVES & TANK EQUIPMENT // PAGE 40 www.grothcorp.com
A B A A E C D SIZE WIDTH HEIGHT ANGLE ASSEMBLY WEIGHT Closed Open Closed Open Open A D B C E in mm in mm in mm in mm in mm deg lbs kg 8 200 14.95 379 20.25 514 7.45 189 15.25 387 109.5 13.8 6.26

HOW TO ORDER

Body Material:

1 = Aluminum

Envelope Gasket:

H = HNBR

V = FKM

F = Fluorosilicone

Vacuum Diaphragm:

H = HNBR

V = FKM

T = Fluoropolymer

F = Fluorosilicone

Pressure Setting:

1 = 4 osig

2 = 6 osig

3 = 8 osig

4 = 12 osig

5 = 16 osig

6 = 24 osig

7 = 32 osig

Vacuum Setting:

1 = 0.4 osig

2 = 0.9 osig

3 = 3.5 osig

Coating:

O = No Coating

E = Polyester/PTFE Coating

Maintenance Repair Kit: (use the above chart for selecting material and options) KIT # SIZE MATERIAL* OPTIONS*

K S 1 2 T H M K 0 8

Envelope Gasket

Vacuum Diaphragm

Pressure Setting

Vacuum Setting

OPTIONAL ACCESSORIES:

Base Gasket:

GKT12TH08K302 = Non-Asbestos

GKT12TH087602 = FKM

GKT12TH087102 = PTFE

GKT12TH084402 = Black Neoprene

Mounting Kit:

KS12THBS08P01 = Zinc Plated Steel (½-13 UNC Hex Nut & Bolt)

VALVES & TANK EQUIPMENT // PAGE 41 www.grothcorp.com
SIZE MATERIAL OPTIONS
MODEL #
1 2 - T H 0 8 1
Product #:

MODEL 12-TH // PRESSURE/VACUUM RELIEF CAPACITY

FlowRate(1000SCFH)

Flowvaluesbasedonairat60

VACUUM RELIEF CAPACITY

FlowRate(1000SCFH)

Flowvaluesbasedonairat60

VALVES & TANK EQUIPMENT // PAGE 42 www.grothcorp.com 0 1 2 3 4 5 6 7 051015202530354045 Vacuum Flowing Pressure (osig)
0 8 16 24 32 40 48 56 64 020406080100120140160180200220 Flowing Pressure (osig)
°Fandatmosphericpressureof14.6959psia
RELIEF CAPACITY
°Fandatmosphericpressureof14.6959psia PRESSURE
32osig 24osig 16osig 12osig8osig6osig4osig 3.5osig 0.9osig 0.4osig Flow curve represents each pressure setting Flow curve represents each vacuum setting

MODEL 1260A

• Sizes // 2" through 12"

• Pressure settings // 0.5 oz/in2 to 15 psig

• Available in aluminum, carbon steel, stainless steel, fiberglass and other materials

• Modular construction

PRESSURE RELIEF VALVE

Pressure Relief Valve Model 1260A is for use where pressure relief is required and all relieving vapors must be piped away. Tank relief, to avoid tank damage, is controlled by a spring or weight loaded pallet in the valve housing. Pressure relief valves help provide increased fire protection and safety. The Model 1260A can also be used for in-line vacuum relief where flanged inlet connection is required. Back pressure in the system must be considered when using flow curves.

SPECIAL FEATURES

Model 1260A offers Groth’s special “cushioned air” seating. Superior performing fluoropolymer seating diaphragms are standard to minimize sticking caused by resinous vapors and atmospheric moisture. The Model 1260A has a self-draining housing body and drip rings to protect seating surfaces from condensate and freezing. This design also avoids pressure or vacuum buildup due to binding or clogging of the valve. Buna-N, FKM and other seating diaphragms can be provided when required.

VALVES & TANK EQUIPMENT // PAGE 43 www.grothcorp.com
MODELMODEL1260A 1261A

SPECIFICATIONS

Specifications subject to change without notice. Certified dimensions available upon request.

2"3"11oz/in28.62"9.37"7.50"4.12"5.50"16.62"16 (50mm)(80mm)(48.3gm/cm2)(219mm)(238mm)(191mm)(105mm)(140mm)(422mm)(7kg) 3"4"13oz/in

(80mm)(100mm)(57.1gm/cm2)(254mm)(282mm)(229mm)(127mm)(152mm)(514mm)(10kg) 4"6"16oz/in211"13.87"11"6.50"6.50"25.62"29 (100mm)(150mm)(70.3gm/cm2)(279mm)(352mm)(279mm)(165mm)(165mm)(651mm)(13kg) 6"8"16oz/in214.50"17.37"13.50"8.50"8.50"34.50"55 (150mm)(200mm)(70.3gm/cm2)(368mm)(441mm)(343mm)(216mm)(216mm)(876mm)(25kg) 8"10"16oz/in218"21.25"16"9.75"10.75"39.75"92 (200mm)(250mm)(70.3gm/cm2)(457mm)(540mm)(406mm)(248mm)(273mm)(1010mm)(42kg) 10"12"16oz/in220.75"23.62"19"10.25"12.50"46.37"105 (250mm)(300mm)(70.3gm/cm2)(527mm)(600mm)(483mm)(260mm)(318mm)(1178mm)(48kg) 12"14"16oz/in224.75"26.62"21"11"15"49.25"149 (300mm)(350mm)(70.3gm/cm2)(629mm)(676mm)(533mm)(279mm)(381mm)(1251mm)(68kg)

VALVES & TANK EQUIPMENT // PAGE 44 www.grothcorp.com
Inlet Flg◊ (Metric) Outlet Flg◊ (Metric) Max.Set Pressure Weight Loaded Max.Set Pressure Spring Loaded Min. Setting Weight Loaded A Length (Metric) B Height (Metric) C Width (Metric) D (Metric) E (Metric) BB (Metric) Approximate Shipping WeightLbs. (Aluminum)
15 psig SPRING LOADED PRESSURE (1.05 kg/cm 2 ) *0.5 oz/in 2 WEIGHT LOADED (2.20 gm/cm 2 ) ‡ On spring loaded valves, change model number. ◊ 150# R.F. drilling compatibility F.F. on aluminum and R.F. on carbon steel and stainless steel alloys. Fiberglass dimensions on request. 16 oz/in2 set with spacer. SS set weights-consult factory. *Some sizes require non-ferrous components to achieve 0.5 oz/in2 setting. BB D E B D E A C For easy ordering, select proper model numbers MODEL#SIZEMATERIALOPTIONS 1260A Weight Loaded 1261B Pressure Spring 1 = Aluminum 3 = Carbon Steel 5 = Stainless Steel 6 = Vinyl Ester Resin 7 = Furan Z = Special O = No Options Z = Special Options O = No Jacket J = Steam Jacket S = Spacer H = Steam Jacket & Spacer Diaphragm Material (Seat): B = Buna-N T = Fluoropolymer V = FKM Z = Special Pallet Material Seat Material Body Material 02" Thru 12" • Include model number and setting when ordering. • For special options, consult factory • When ordering steam jacket, include steam pressure/temperature. * Stainless steel guides, stems are standard with aluminum and carbon steel bodies. Stainless steel seats standard with carbon steel bodies. NOTES EXAMPLE Indicates a 2" Model 1260A with Aluminum Body and Seat, Stainless Steel Pallet, Fluoropolymer Seat Diaphragm, and no other options. 1260A021T1O5O
ORDER
210"11.12"9"5"6"20.25"22
HOW TO

MODEL 1260A // PRESSURE RELIEF CAPACITY

0.870.506.8713.325.252.782.6135175 1.000.587.3914.327.156.688.8145188 1.731.009.7118.835.674.3117190247

2.001.1610.420.238.279.8125205265

2.601.5011.923.043.590.8143233302

3.001.7312.824.746.897.5153250324

3.462.0013.726.650.2105164268348

4.002.3114.728.653.9112177288374

6.003.4718.035.065.9137215351456 8.004.6220.740.475.8157248404525 10.05.7823.145.184.6175276450584 12.06.9325.249.492.4191301491638 15.08.6628.155.2103211335546709 20.011.632.263.7118241383625811 25.014.435.871.2131267424692898 30.017.339.077.9143289460751975

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear sted.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 45 www.grothcorp.com
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 112,000 SCFH 6" Model 1260A 2. Calculate overpressure % OP = [(7 - 4)/4] x 100 = 75% 4 InWC set pressure [Ps] 3. Read “C” factor from table “C” = 0.87 7 InWC flowing pressure [Pf] 4. Calculate flow capacity Flow = 0.87 x 112,000 = 97,440 SCFH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.87 “C”FactorTable %OP0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00 MODEL 1220A FLOW CAPACITY CALCULATION AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000StandardCubicFeetperHourat60°F SetPressure(Ps)Size InWCoz/in22" (50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)

MODEL 1260A // PRESSURE RELIEF CAPACITY

12512.30.460.891.683.505.518.9911.7 15014.70.500.981.843.826.029.8012.7 17517.20.541.061.994.126.4910.613.7 20019.60.581.132.124.396.9211.314.7 22522.10.611.202.254.657.3312.015.5 25024.50.651.262.364.897.7112.616.3 27527.00.681.322.485.118.0713.217.1 30029.40.701.382.585.338.4213.717.8 37536.80.781.542.885.919.4015.319.8 50049.00.901.783.306.7510.717.522.7 62561.31.001.993.677.4611.919.425.1 75073.51.092.183.998.0712.921.027.3

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 46 www.grothcorp.com
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 3,140 NCMH 6" Model 1260A 2. Calculate overpressure % OP = [(175 - 100)/100] x 100 = 75% 100 mmWC Set Pressure [Ps] 3. Read “C” factor from table “C” = 0.87 175 mmWC Flowing Pressure [P ] 4. Calculate flow capacity Flow = 0.87 x 3,140 = 2,732 NCMH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.87 “C”FactorTable %OP0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00 MODEL 1220A FLOW CAPACITY CALCULATION AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000NormalCubicMetersperHourat0°C SetPressure(Ps)Size mmWCmb2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)
504.900.290.561.072.233.505.727.42 757.350.360.691.312.724.286.999.10 1009.800.410.801.513.144.938.0510.4
222.160.190.370.711.482.333.804.93

MODEL 1261A // PRESSURE RELIEF CAPACITY

MODEL 1220A FLOW CAPACITY CALCULATION

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 47 www.grothcorp.com
AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000StandardCubicFeetperHourat60°F SetPressure(Ps)Size psig2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 1.0028.053.492.5210345529739 2.0040.377.41343045007671070 3.0050.296.91683816259601340 4.0058.811419844873611301577 5.0066.513022551083812861794 6.0073.714425056893214311997 7.0080.4158274622102215682188 8.0086.7171297674110716992371 9.0092.8184319724118918252546 10.098.6196340772126719452714 11.0104208360818134320622877 12.0110219380863141721763036 13.0115231400907148922863189 14.0120241418949155923933339 15.0125252437991162724983486
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 448,000 SCFH 6" Model 1261A 2. Calculate overpressure % OP = [(7 - 4)/4] x 100 = 75% 4 psig Set Pressure [Ps] 3. Read “C” factor from table “C” = 0.83 7 psig Flowing Pressure [Pf] 4. Calculate flow capacity Flow = 0.83 x 448,000 = 371,840 SCFH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.83 “C”FactorTable %OP0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00

MODEL 1261A // PRESSURE RELIEF CAPACITY

0.070.821.572.726.1610.115.521.7

MODEL 1220A FLOW CAPACITY CALCULATION

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 48 www.grothcorp.com
AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000NormalCubicMetersperHourat0°C SetPressure(P
barg2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)
s)Size
0.502.394.708.1618.530.446.665.1 0.552.524.988.6419.632.249.468.9 0.602.655.259.1020.633.952.172.6 0.702.895.7610.022.737.257.279.7 0.803.136.2510.824.640.462.186.5 0.903.356.7211.726.543.566.793.1 1.003.567.1812.528.346.471.299.4
0.100.991.893.287.4512.218.826.2 0.151.232.364.099.2815.223.432.6 0.201.432.764.8010.917.927.438.3 0.251.623.145.4412.320.331.143.4 0.301.793.486.0413.722.534.548.2 0.351.953.816.6115.024.637.852.7 0.402.104.127.1416.226.640.957.0 0.452.254.417.6617.428.543.861.1
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 16,200 NCMH 6" Model 1261A 2. Calculate overpressure % OP = [(0.7 - 0.4)/0.4] x 100 = 75% 0.4 barg Set Pressure [Ps] 3. Read “C” factor from table “C” = 0.83 0.7 barg Flowing Pressure [Pf] 4. Calculate flow capacity Flow = 0.83 x 16,200 = 13,446 NCMH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.83 “C”FactorTable %OP0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00

MODEL 2300A

• Sizes // 2" through 12"

• Pressure settings // 0.5 oz/in2 to 15 psig

• Available in aluminum, carbon steel, stainless steel, and other materials

EMERGENCY RELIEF VALVE

Model 2300A is designed for emergency relief capacity above that supplied by a standard operating valve used on tanks, piping, and low pressure vessels. Emergency relief valves provide relief from excessive internal pressures which may cause tank damage.

SPECIAL FEATURES

Model 2300A is built of corrosion resistant material throughout. Groth’s self-closing special fluoropolymer “cushioned air” pallet with center stabilizing stem and peripheral guiding provides uniform seating and alignment. Superior performing fluoropolymer seating diaphragms are standard to minimize sticking caused by resinous vapors and atmospheric moisture. The guides support a spun weatherhood which covers and protects the entire valve structure. As added protection against the entry of foreign matter, a mesh screen encircles the valve under the weatherhood. Buna-N, FKM and other seating diaphragms can be provided when required.

VALVES & TANK EQUIPMENT // PAGE 49 www.grothcorp.com
MODEL2300AMODEL2301A

SPECIFICATIONS

Specifications subject to change without notice. Certified dimensions available upon request.

2"9.50"9.50"9.75"16.50"12 (50mm)(241mm)(241mm)(248mm)(419mm)(5kg)

3"11.50"13"8.62"22.00"15 (80mm)(292mm)(330mm)(219mm)(550mm)(7kg)

4"13"13"10.56"22.50"20 (100mm)(330mm)(330mm)(268mm)(572mm)(9kg)

6"19"19.50"15"30.50"30 (150mm)(480mm)(495mm)(381mm)(784mm)(14kg)

8"23.62"23.50"16.62"35.37"45 (200mm)(600mm)(597mm)(422mm)(899mm)(20kg)

10"30.75"25.50"17"41.37"65 (250mm)(781mm)(648mm)(431mm)(1051mm)(30kg) 12"36"25.50"18"42.37"100 (300mm)(914mm)(648mm)(457mm)(1076mm)(45kg)

‡ On spring loaded valves, change to model 2301A. † Larger

VALVES & TANK EQUIPMENT // PAGE 50 www.grothcorp.com
factory. * 150# ANSI. drilling compatibility, F.F. on aluminum and R.F. on
steel
stainless steel
dimensions on request. **Some sizes require non-ferrous components to achieve 0.5 oz/in2 setting. BB AA B A Size* Flange (Metric) Max.Set Pressure Minimum Set Pressure A Diameter (Metric) AA Diameter (Metric) B Height (Metric) BB Height (Metric) Approx.Ship Wt.Lbs. (Aluminum)
sizes available - consult
carbon
and
alloys. Fiberglass
16 oz/in 2 WEIGHT LOADED (70.3 gm/cm 2 ) 15 psig SPRING LOADED (1.05 kg/cm 2 ) **0.5 oz/in 2 (2.2 gm/cm 2 ) WEIGHT LOADED For easy ordering, select proper model numbers MODEL#SIZEMATERIALOPTIONS 2300A Weight Loaded 2301A Spring Loaded 1 = Aluminum 3 = Carbon Steel 5 = Stainless Steel 6 = Vinyl Ester Resin 7 = Furan Z = Special O = No Options Z = Special Options O = No Jacket J = Steam Jacket S = Spacer H = Steam Jacket & Spacer Diaphragm Material (Seat): B = Buna-N T = Fluoropolymer V = FKM Z = Special Pallet Material Seat Material Body Material 02" Thru 12" • Include model number and setting when ordering. • For special options, consult factory • When ordering steam jacket, include steam pressure/temperature. * Stainless steel guides, stems are standard with aluminum and carbon steel bodies. Stainless steel seats standard with carbon steel bodies. # Aluminum body not available on 2301A. NOTES EXAMPLE Indicates a 2" Model 2300A with Aluminum Body and Seat, Stainless Steel Pallet, Fluoropolymer Seat Diaphragm, and no other options. 2300A021T1O5O
TO ORDER
HOW

0.870.506.9815.426.158.588.4143211 1.000.587.5016.528.062.895.0154227 1.731.009.8521.736.882.5125203298 2.001.1610.623.339.688.6134218320 2.601.5012.126.645.1101153248365 3.001.7312.928.648.4108164266392 3.462.0013.930.752.0116176285420 4.002.3114.933.055.8125189307451

6.003.4718.240.468.2152230374550 8.004.6221.046.678.5175265430633 10.05.7823.452.187.6194295479705 12.06.9325.657.195.7212322523769 15.08.6628.563.8107235358581855 20.011.632.773.6122268409665979 25.014.436.382.21362964547361084 30.017.339.589.91483214927991177

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear sted.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 51 www.grothcorp.com Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 125,000 SCFH 6" Model 2300A 2. Calculate overpressure % OP = [(7 - 4)/4] x 100 = 75% 4 InWC set pressure [Ps] 3. Read “C” factor from table “C” = 0.87 7 InWC flowing pressure [Pf] 4. Calculate flow capacity Flow = 0.87 x 125,000 = 108,750 SCFH
Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.87 “C”FactorTable %OP0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00 MODEL 1220A FLOW CAPACITY CALCULATION AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000StandardCubicFeetperHourat60°F SetPressure(Ps)Size InWCoz/in22" (50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)
2300A // PRESSURE RELIEF CAPACITY
MODEL

15014.70.511.131.914.256.4410.515.4 17517.20.551.222.064.586.9411.316.6 20019.60.591.302.194.887.4012.017.7 22522.10.621.382.325.167.8412..718.7 25024.50.651.462.455.438.2513.419.7 27527.00.691.532.565.688.6314.020.6 30029.40.721.592.675.929.0014.621.5 37536.80.801.782.986.5710.016.223.9 50049.00.912.063.427.4911.418.627.4 62561.31.022.303.808.2812.720.630.3 75073.51.112.514.138.9713.822.432.9

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 52 www.grothcorp.com
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 3,490 NCMH 6" Model 2300A 2. Calculate overpressure % OP = [(175 - 100)/100] x 100 = 75% 100 mmWC Set Pressure [Ps] 3. Read “C” factor from table “C” = 0.87 175 mmWC Flowing Pressure [Pf] 4. Calculate flow capacity Flow = 0.87 x 3,490 = 3,036 NCMH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.87 “C”FactorTable %OP0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00 MODEL 1220A FLOW CAPACITY CALCULATION MODEL 2300A // PRESSURE RELIEF CAPACITY AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000NormalCubicMetersperHourat0°C SetPressure(Ps)Size mmWCmb2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 222.160.200.430.731.652.494.045.95 504.900.300.651.112.483.756.088.95 757.350.360.801.353.034.587.4310.9 1009.800.420.921.563.495.288.5712.6
12512.30.471.031.743.895.899.5614.1

MODEL 2301A // PRESSURE RELIEF CAPACITY

MODEL 1220A FLOW CAPACITY CALCULATION

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 53 www.grothcorp.com
AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000StandardCubicFeetperHourat60°F SetPressure(Ps)Size psig2" (50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 1.0027.159.9104198345529739 2.0039.787.71522965007671070 3.0050.11111923796259601340 4.0059.513122845673611301577 5.0068.315126153083812861794 6.0076.516929360193214311997 7.0084.3186323670102215682188
9.0099.3219380804118918252546 10.0107235407869126719452714 11.0113250434934134320622877 12.0120265460998141721753036 13.01272804851061148922863189 14.01342955101124155923933339 15.01403095351186162724983486
8.0091.9203352737110716992371
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 456,000 SCFH 6" Model 2301A 2. Calculate overpressure % OP = [(7 - 4)/4] x 100 = 75% 4 psig Set Pressure [Ps] 3. Read “C” factor from table “C” = 0.83 7 psig Flowing Pressure [Pf] 4. Calculate flow capacity Flow = 0.83 x 456,000 = 378,480 SCFH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.83 “C”FactorTable %OP0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00

MODEL 2301A // PRESSURE RELIEF CAPACITY

0.070.801.763.055.8310.115.521.7 0.100.972.133.707.1312.218.826.2 0.151.212.674.649.0515.223.432.7 0.201.433.165.4810.817.927.438.3 0.251.633.606.2512.520.331.143.4 0.301.824.026.9814.022.534.548.2 0.352.004.427.6815.624.637.852.7 0.402.184.818.3417.126.640.857.0 0.452.355.188.9918.628.543.861.1

MODEL 1220A FLOW CAPACITY CALCULATION

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 54 www.grothcorp.com
AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000NormalCubicMetersperHourat0°C SetPressure(P
barg2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)
s)Size
0.502.515.549.6220.030.446.665.1 0.552.675.8910.221.432.249.468.9 0.602.836.2410.822.833.952.072.7 0.703.136.9012.025.637.357.179.8 0.803.427.5513.128.340.462.086.6 0.903.708.1714.231.043.566.793.2 1.003.988.7815.233.646.471.299.4
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 17,100 NCMH 6" Model 2301A 2. Calculate overpressure % OP = [(0.7 - 0.4)/0.4] x 100 = 75% 0.4 barg Set Pressure [Ps] 3. Read “C” factor from table “C” = 0.83 0.7 barg Flowing Pressure [Pf] 4. Calculate flow capacity Flow = 0.83 x 17,100 = 14,193 NCMH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.83 “C”FactorTable %OP0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00

• Sizes // 2" through 12"

• Vacuum settings // 0.5 oz/in2 to 12 psig

• Available in aluminum, carbon steel, stainless steel, and other materials

• Modular construction

VACUUM RELIEF VALVE

Model 1300A is used when vacuum relief is the only requirement. Intake relief necessary under working conditions is achieved by a spring or weight loaded pallet. This feature of the Model 1300A reduces the possibility of tank damage. The Model 1300A helps to provide increased fire protection and safety. Valve size must be selected to perform required vacuum relief under operating and thermal conditions. Flow curves for vacuum relief are provided.

SPECIAL FEATURES

Model 1300A offers Groth’s special “cushioned air” seating. Superior performing fluoropolymer seating diaphragms are standard to minimize sticking caused by resinous vapors and atmospheric moisture. The Model 1300A has a self draining housing body and drip rings to protect seating surfaces from condensate and freezing. This design also avoids vacuum buildup due to binding or clogging of the vent. Metal-to-metal, Buna-N, FKM and other seating diaphragms can be provided when required.

VALVES & TANK EQUIPMENT // PAGE 55 www.grothcorp.com
MODEL1300AMODEL1301A
MODEL 1300

SPECIFICATIONS

Specifications subject to change without notice. Certified dimensions available upon request.

2"12oz/in211.62"6.87"14"6"15 (50mm)(52.7gm/cm2)(295mm)(174mm)(356mm)(152mm)(7kg) 3"11oz/in215.75"7.75"16.25"7.75"21 (80mm)(48.3gm/cm2)(400mm)(196mm)(413mm)(197mm)(10kg) 4"11oz/in217.25"9.62"19.87"9"32 (100mm)(48.3gm/cm2)(438mm)(244mm)(505mm)(229mm)(14kg) 6"16oz/in223.50"11.87"27"12"61 (150mm)(70.3gm/cm2)(597mm)(301mm)(686mm)(305mm)(28kg) 8"16oz/in228.50"15.50"31.87"14.50"81 (200mm)(70.3gm/cm2)(724mm)(394mm)(810mm)(368mm)(37kg) 10"16oz/in233.25"18.62"37.87"16.50"121 (250mm)(70.3gm/cm2)(845mm)(473mm)(962mm)(419mm)(55kg) 12"16oz/in237.25"21.62"42"19"165 (300mm)(70.3gm/cm2)(946mm)(549mm)(1067mm)(483mm)(75kg)

VALVES & TANK EQUIPMENT // PAGE 56 www.grothcorp.com
Size◊ (Metric) Max.Set Vacuum Weight Loaded Max.Set Vacuum Spring Loaded Min.Set Vacuum Weight Loaded Max.W.P.† forMin. Vacuum Setting Min.Vac. Setting for Max.W.P.† A Length (Metric) B Height (Metric) BB Height (Metric) C Width (Metric) Approx. Ship Wt.Lbs. (Aluminum)
12 psig SPRING LOADED PRESSURE (0.84 kg/cm 2 ) *0.5 oz/in 2 WEIGHT LOADED (2.20 gm/cm 2 ) †
◊ 150# ANSI. drilling compatibility, F.F. on aluminum and R.F. on carbon steel
stainless steel alloys.
request. 16 oz/in2 set
spacer. SS set weights-consult factory. *Some sizes require non-ferrous components to achieve 0.5 oz./in2 setting. B A CBB For easy ordering, select proper model numbers MODEL#SIZEMATERIALOPTIONS 1300A Weight Loaded 1301A Spring Loaded 1 = Aluminum 3 = Carbon Steel 5 = Stainless Steel 6 = Vinyl Ester Resin 7 = Furan Z = Special O = No Options Z = Special Options O = No Jacket J = Steam Jacket S = Spacer H = Steam Jacket & Spacer Diaphragm Material (Seat): B = Buna-N T = Fluoropolymer V = FKM M = Metal-to-Metal Z = Special Pallet Material Seat Material Body Material* 02" Thru 12" • Include model number and setting when ordering. • For special options, consult factory • When ordering steam jacket, include steam pressure / temperature. * Stainless steel guides, stems are standard with aluminum and carbon steel bodies. Stainless steel seats standard with carbon steel bodies. NOTES EXAMPLE Indicates a 2" Model 1300A with Aluminum Body and Seat, Stainless Steel Pallet, Fluoropolymer Seat Diaphragm, and no other options. 1300A021T1O5O HOW TO ORDER SeeTPD forVacuum Settingsand MAWP
W.P. = Working Pressure. ‡ On spring loaded valves, change model number.
and
Fiberglass dimensions on
with

MODEL 1300A // VACUUM RELIEF CAPACITY

Flow capacity values listed above are based on full open valves at 100% over-vacuum.

Read the flow capacity at 100% over-vacuum directly from the table above. Use linear interpolation if the set vacuum is not listed.

If the allowable over-vacuum is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, consult your Groth Representative.

Calculate the percentage over-vacuum by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OV = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% over-vacuum according to the following example.

VALVES & TANK EQUIPMENT // PAGE 57 www.grothcorp.com
AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000StandardCubicFeetperHourat60°F SetVacuum(Ps)Size InWCoz/in22" (50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 0.870.504.7010.316.034.760.591.1129 1.000.585.0511.017.237.365.097.9138 1.731.006.6314.522.649.085.3129182 2.001.167.1215.624.252.691.6138195 2.601.508.1017.727.659.8104157222
3.462.009.3320.431.868.9120181256 4.002.3110.021.934.174.0129194274 6.003.4712.226.741.590.1157237334 8.004.6214.030.647.7103180272384 10.05.7815.634.053.0115200302427 12.06.9317.037.157.8125218329465 15.08.6618.841.164.0139242365516 20.011.621.446.872.9158276415587 25.014.423.651.580.3174304457646 30.017.325.455.686.6188327493697
3.001.738.7019.029.664.2112169238
Example—FlowCapacityCalculation 1. Read flow capacity at set vacuum from table Flow = 74,000 SCFH 6" Model 1300A 2. Calculate over-vacuum % OV = [(7 - 4)/4] x 100 = 75% 4 InWC Set Vacuum [Ps] 3. Read “C” factor from table “C” = 0.87 7 InWC Flowing Vacuum [P ] 4. Calculate flow capacity Flow = 0.87 x 74,000 = 64,380 SCFH Example—To find “C” factor from table: Read “C” factor for 75% Over-vacuum at intersection of row 70 and column 5 “C” factor at 75% OV = 0.87 “C”FactorTable %OV0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00
MODEL 1220A FLOW CAPACITY CALCULATION

MODEL 1300A // VACUUM RELIEF CAPACITY

Flow capacity values listed above are based on full open valves at 100% over-vacuum.

Read the flow capacity at 100% over-vacuum directly from the table above. Use linear interpolation if the set vacuum is not listed.

If the allowable over-vacuum is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, consult your Groth Representative.

Calculate the percentage over-vacuum by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OV = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% over-vacuum according to the following example.

VALVES & TANK EQUIPMENT // PAGE 58 www.grothcorp.com
AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000NormalCubicMetersperHourat0°C SetVacuum(Ps)Size mmWCmb2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 222.160.130.290.450.981.712.583.65 504.900.200.440.681.482.583.885.48 757.350.240.530.831.813.154.746.70 1009.800.280.620.962.083.625.467.72 12512.30.310.691.072.324.046.098.60 15014.70.340.751.172.534.416.659.40 17517.20.370.811.262.734.757.1610.1 20019.60.390.861.342.915.077.6410.8 22522.10.420.911.423.085.368.0811.4 25024.50.440.961.493.235.648.4912.0 27527.00.461.001.563.385.908.8812.6 30029.40.481.041.623.526.149.2513.1 37536.80.531.161.803.916.8110.314.5 50049.00.601.322.054.457.7511.716.5 62561.30.661.452.264.908.5412.918.2 75073.50.721.572.445.299.2213.919.6
Example—FlowCapacityCalculation 1. Read flow capacity at set vacuum from table Flow = 2,080 NCMH 6" Model 1300A 2. Calculate over-vacuum % OV = [(175 - 100)/100] x 100 = 75% 100 mmWC Set Vacuum [Ps] 3. Read “C” factor from table “C” = 0.87 175 mmWC Flowing Vacuum [P ] 4. Calculate flow capacity Flow = 0.87 x 2,080 = 1,810 NCMH Example—To find “C” factor from table: Read “C” factor for 75% over-vacuum at intersection of row 70 and column 5 “C” factor at 75% OV = 0.87 “C”FactorTable %OV0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00
MODEL 1220A FLOW CAPACITY CALCULATION

MODEL 1301A // VACUUM RELIEF CAPACITY

Flow capacity values listed above are based on full open valves at 100% over-vacuum.

Read the flow capacity at 100% over-vacuum directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable over-vacuum is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, consult your Groth Representative.

Calculate the percentage over-vacuum by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OV = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% over-vacuum according to the following example.

VALVES & TANK EQUIPMENT // PAGE 59 www.grothcorp.com
AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000StandardCubicFeetperHourat60°F SetVacuum(Ps)Size psig2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 1.0013.830.552.9120197302422 1.1014.531.955.4126206316442 1.2015.133.257.7131215330460 1.3015.734.559.9136223342478 1.4016.235.762.0141231355495 1.5016.836.964.0145239366511 1.7518.039.668.7156256393548 2.0019.142.073.0166272417582 2.2520.144.376.9174286439613 2.5021.046.380.4183300460641 2.7521.948.283.7190312478667 3.0022.749.986.6197323495691 3.2523.451.489.3203333511713 3.5024.052.891.8208342525732 >3.50 CONSULT FACTORY FOR VACUUM SETTINGS GREATER THAN 3.5 PSIG
Example—FlowCapacityCalculation 1. Read flow capacity at set vacuum from table Flow = 166,000 SCFH 6" Model 1301A 2. Calculate over-vacuum % OV = [(3.50 - 2.0)/2.0] x 100 = 75% 2 psig Set Vacuum [Ps] 3. Read “C” factor from table “C” = 0.83 3.5 psig Flowing Vacuum [P ] 4. Calculate flow capacity Flow = 0.83 x 166,000 = 137,780 SCFH Example—To find “C” factor from table: Read “C” factor for 75% over-vacuum at intersection of row 70 and column 5 “C” factor at 75% OV = 0.83
“C”FactorTable %OV0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00
MODEL 1220A FLOW CAPACITY CALCULATION

MODEL 1301A // VACUUM RELIEF CAPACITY

Flow capacity values listed above are based on full open valves at 100% over-vacuum.

Read the flow capacity at 100% over-vacuum directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable over-vacuum is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, consult your Groth Representative.

Calculate the percentage over-vacuum by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OV = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% over-vacuum according to the following example.

VALVES & TANK EQUIPMENT // PAGE 60 www.grothcorp.com
barg2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)
AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000NormalCubicMetersperHourat0°F SetVacuum(Ps)Size
0.240.701.542.676.059.9315.221.3
0.070.410.901.553.525.778.8712.4 0.100.481.061.834.166.8310.514.6 0.110.511.111.924.357.1411.015.3 0.120.531.151.994.537.4311.415.9 0.130.551.202.074.697.7011.816.5 0.140.561.242.144.857.9612.217.1 0.150.581.272.205.008.2112.617.6 0.160.601.312.275.148.4413.018.1 0.170.611.352.335.288.6613.318.6 0.180.631.382.385.418.8813.619.0 0.190.641.412.445.539.0813.919.4 0.200.661.442.495.659.2714.219.8 0.220.681.492.585.869.6214.820.6
>0.24CONSULTFACTORYFORVACUUMSETTINGSGREATERTHAN0.24BARG
Example—FlowCapacityCalculation 1. Read flow capacity at set vacuum from table Flow = 4,530 NCMH 6" Model 1301A 2. Calculate over-vacuum % OV = [(0.17 - 0.12)/0.12] x 100 = 42% 0.12 barg Set Vacuum [Ps] 3. Read “C” factor from table “C” = 0.55 0.17 barg Flowing Vacuum [Pf] 4. Calculate flow capacity Flow = 0.55 x 4,530 = 2,492 NCMH Example—To find “C” factor from table: Read “C” factor for 72% over-vacuum at intersection of row 40 and column 2 “C” factor at 42% OV = 0.55 “C”FactorTable %OV0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00
MODEL 1220A FLOW CAPACITY CALCULATION

MODEL 1360A

• Sizes // 3" through 14"

• Vacuum settings // 0.5 oz/in2 to 12 psig

• Available in aluminum, carbon steel, stainless steel, fiberglass and other materials

VACUUM RELIEF VALVE

Model 1360A is used when vacuum relief is the only requirement. The Model 1360A may be side mounted on the tank body or piped in. Intake relief necessary under working conditions is achieved by a spring or weight loaded pallet in the valve housing. The Model 1360A reduces the possibility of tank damage.

Valve size must be selected to meet required vacuum relief under operating and thermal conditions. Flow curves for vacuum relief are provided.

SPECIAL FEATURES

Model 1300A offers Groth’s special “cushioned Model 1360A offers Groth’s special “cushioned air” seating. Superior performing fluoropolymer seating diaphragms are standard to minimize sticking caused by resinous vapors and atmospheric moisture. The Model 1360A has a self draining housing body and drip rings to protect seating surfaces from condensate and freezing. This design also avoids vacuum buildup due to binding or clogging of the vent. Metal-to-metal, Buna-N, FKM and other seating diaphragms can be provided when required.

VALVES & TANK EQUIPMENT // PAGE 61 www.grothcorp.com
MODEL1360AMODEL1361A

SPECIFICATIONS

3"11oz/in28.62"9.25"7.50"5.50"16.25"12 (80mm)(48.2gm/cm2)(219mm)(235mm)(191mm)(140mm)(413mm)(6kg) 4"13oz/in210"11.50"9"6"19.75"17 (100mm)(57.0gm/cm2)(254mm)(292mm)(229mm)(152mm)(502mm)(8kg) 6"16oz/in211"14.25"11"6.50"24.62"23 (150mm)(70.3gm/cm2)(279mm)(362mm)(279mm)(165mm)(625mm)(10kg) 8"16oz/in214.50"17.75"13.50"8.50"32.75"42 (200mm)(70.3gm/cm2)(368mm)(451mm)(343mm)(216mm)(832mm)(19kg) 10"16oz/in218"21.25"16"10.75"38"71 (250mm)(70.3gm/cm2)(457mm)(540mm)(406mm)(273mm)(965mm)(32kg) 12"16oz/in220.75"25.75"19"12.50"45.37"83 (300mm)(70.3gm/cm2)(527mm)(654mm)(483mm)(318mm)(1152mm)(38kg) 14"16oz/in224.75"29.25"21"15"48.75"118 (350mm)(70.3gm/cm2)(629mm)(743mm)(533mm)(381mm)(1238mm)(54kg)

VALVES & TANK EQUIPMENT // PAGE 62 www.grothcorp.com
MODEL#SIZEMATERIALOPTIONS 1360A Weight Loaded 1361A Spring Loaded 1 = Aluminum 3 = Carbon Steel 5 = Stainless Steel 6 = Vinyl Ester Resin 7 = Furan Z = Special O = No Options Z = Special Options O = No Jacket J = Steam Jacket S = Spacer H = Steam Jacket & Spacer Diaphragm Material
B = Buna-N T = Fluoropolymer V = FKM Z = Special Pallet Material Seat Material Body Material 03" Thru 14"
Include model number and setting when ordering.
For special options, consult factory
When ordering steam jacket, include steam pressure / temperature. • Stainless steel guides, stems are standard with aluminum and carbon steel bodies. NOTES EXAMPLE Indicates a 3" Model 1360A with Aluminum Body and Seat, Stainless Steel Pallet, Fluoropolymer Seat Diaphragm, and no other options. 1360A031T1O5O HOW TO ORDER BBB E A C Size◊ Flange (Metric) Max.Set Vacuum Weight Loaded Max.Set Vacuum Spring Loaded Min.Set Vacuum Weight Loaded Max. W.P.† forMin. Vacuum Setting Min.Vac. Setting vs. Max. W.P.† A Length (Metric) B Height (Metric) C Width (Metric) E (Metric) BB Height (Metric) Approx. Ship Wt.Lbs. (Aluminum)
For easy ordering, select proper model numbers
(Seat):
12 psig SPRING LOADED VACUUM (0.84 kg/cm 2 ) *0.5 oz/in 2 WEIGHT LOADED (2.20 gm/cm 2 ) † W.P. = Working Pressure. ‡ On spring loaded valves, change model number. ◊ 150# R.F. drilling compatibility F.F. on aluminum and R.F. on carbon steel and stainless steel alloys. Fiberglass dimensions on request. 16 oz/in2 set with spacer. SS set weights-consult factory. *Some sizes require non-ferrous components to achieve 0.5 oz./in2 setting. SeeTPD
MAWP
forVacuum Settingsand

MODEL 1360A // VACUUM RELIEF CAPACITY

MODEL 1220A FLOW CAPACITY CALCULATION

Flow capacity values listed above are based on full open valves at 100% over-vacuum.

Read the flow capacity at 100% over-vacuum directly from the table above. Use linear interpolation if the set vacuum is not listed.

If the allowable over-vacuum is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, consult your Groth Representative.

Calculate the percentage over-vacuum by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OV = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% over-vacuum according to the following example.

VALVES & TANK EQUIPMENT // PAGE 63 www.grothcorp.com
AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000StandardCubicFeetperHourat60°F SetVacuum(Ps)Size InWCoz/in23" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 14" (350mm) 0.870.508.0114.827.857.499.4136182 1.000.588.6115.929.961.6107146195 1.731.0011.320.839.380.9140192257 2.001.1612.122.442.286.9151207276 2.601.5013.825.548.098.9171235314
3.462.0015.929.355.3114197271361 4.002.3117.131.559.3122212291388 6.003.4720.838.472.3149258354472 8.004.6223.944.083.0171297407542 10.05.7826.649.092.3190330452603 12.06.9328.953.4101207359492657 15.08.6632.159.1111230398546728 20.011.636.567.3127261453621829 25.014.440.274.1140288499684913 30.017.343.480.0151311538738985
3.001.7314.827.351.5106184252337
Example—FlowCapacityCalculation 1. Read flow capacity at set vacuum from table Flow = 59,300 SCFH 6" Model 1360A 2. Calculate over-vacuum % OV = [(7 - 4)/4] x 100 = 75% 4 InWC Set Vacuum [Ps] 3. Read “C” factor from table “C” = 0.87 7 InWC Flowing Vacuum [P ] 4. Calculate flow capacity Flow = 0.87 x 59,300 = 51,591 SCFH Example—To find “C” factor from table: Read “C” factor for 75% Over-vacuum at intersection of row 70 and column 5 “C” factor at 75% OV = 0.87 “C”FactorTable %OV0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00

MODEL 1360A // VACUUM RELIEF CAPACITY

Flow capacity values listed above are based on full open valves at 100% over-vacuum.

Read the flow capacity at 100% over-vacuum directly from the table above. Use linear interpolation if the set vacuum is not listed.

If the allowable over-vacuum is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, consult your Groth Representative.

Calculate the percentage over-vacuum by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OV = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% over-vacuum according to the following example.

VALVES & TANK EQUIPMENT // PAGE 64 www.grothcorp.com
Example—FlowCapacityCalculation 1. Read flow capacity at set vacuum from table Flow = 1,660 NCMH 6" Model 1360A 2. Calculate over-vacuum % OV = [(175 - 100)/100] x 100 = 75% 100 mmWC Set Vacuum [Ps] 3. Read “C” factor from table “C” = 0.87 175 mmWC Flowing Vacuum [Pf] 4. Calculate flow capacity Flow = 0.87 x 1,660 = 1,444 NCMH Example—To find “C” factor from table: Read “C” factor for 75% over-vacuum at intersection of row 70 and column 5 “C” factor at 75% OV = 0.87 “C”FactorTable %OV0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00 MODEL 1220A FLOW CAPACITY CALCULATION AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000NormalCubicMetersperHourat0°C SetVacuum(Ps)Size mmWCmb3"(80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 14" (350mm) 222.160.230.420.781.622.803.845.12 504.900.340.631.182.434.215.777.70 757.350.410.761.442.975.147.059.41 1009.800.480.881.663.425.928.1210.8 12512.30.530.981.853.816.619.0612.1 15014.70.581.072.024.167.229.8913.2 17517.20.631.162.184.497.7810.714.2 20019.60.671.232.324.788.2911.415.2 22522.10.711.302.455.068.7712.016.0 25024.50.741.372.585.329.2212.616.9 27527.00.781.432.705.569.6413.217.6 30029.40.811.492.815.7910.013.818.4 37536.80.901.653.126.4211.115.320.4 50049.01.021.883.557.3112.717.423.2
62561.31.132.083.918.0614.019.125.5 75073.51.212.244.228.7015.120.727.6

MODEL 1361A // VACUUM RELIEF CAPACITY

MODEL 1220A FLOW CAPACITY CALCULATION

Flow capacity values listed above are based on full open valves at 100% over-vacuum.

Read the flow capacity at 100% over-vacuum directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable over-vacuum is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, consult your Groth Representative.

Calculate the percentage over-vacuum by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OV = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% over-vacuum according to the following example.

VALVES & TANK EQUIPMENT // PAGE 65 www.grothcorp.com
Example—FlowCapacityCalculation 1. Read flow capacity at set vacuum from table Flow = 116,000 SCFH 6" Model 1361A 2. Calculate over-vacuum % OV = [(3.50 - 2.0)/2.0] x 100 = 75% 2 psig Set Vacuum [Ps] 3. Read “C” factor from table “C” = 0.83 3.5 psig Flowing Vacuum [P ] 4. Calculate flow capacity Flow = 0.83 x 116,000 = 96,280 SCFH Example—To find “C” factor from table: Read “C” factor for 75% over-vacuum at intersection of row 70 and column 5 “C” factor at 75% OV = 0.83
“C”FactorTable %OV0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00 AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000StandardCubicFeetperHourat60°F SetVacuum(Ps)Size psig3"(80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 14" (350mm)
1.1023.652.090.2204336516720 1.2024.554.093.8213349536748 1.3025.456.097.2220362556775 1.4026.257.8100227374574801 1.5027.059.6103234385591825
2.0030.467.0116264433665928
>3.50CONSULTFACTORYFORVACUUMSETTINGSGREATERTHAN3.5PSIG
1.0022.649.886.4196322494689
1.7528.863.5110250411631880
2.2531.870.1122276453696971 2.5033.172.81262874717231009 2.7534.175.21312964867471042 3.0035.177.31343045007671070 3.2535.979.01373115117851095 3.5036.580.51403175207991115

MODEL 1361A // VACUUM RELIEF CAPACITY

0.070.661.462.535.749.3914.420.2 0.100.771.712.966.7211.016.923.7

0.110.811.783.097.0011.517.624.7 0.120.841.853.207.2611.918.325.6

0.130.861.913.317.5012.318.926.4 0.140.891.963.417.7212.619.427.2 0.150.912.023.507.9313.019.927.9 0.160.942.073.588.1213.320.428.6

0.170.962.113.668.3013.620.929.3 0.180.982.153.738.4713.921.329.8 0.190.992.193.808.6214.121.730.4 0.201.012.233.868.7614.322.030.9 0.221.042.293.979.0114.722.731.7 0.241.062.344.069.2115.123.232.4 >0.24CONSULTFACTORYFORVACUUMSETTINGSGREATERTHAN0.24BARG

Flow capacity values listed above are based on full open valves at 100% over-vacuum.

Read the flow capacity at 100% over-vacuum directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable over-vacuum is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, consult your Groth Representative.

Calculate the percentage over-vacuum by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OV = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% over-vacuum according to the following example.

VALVES & TANK EQUIPMENT // PAGE 66 www.grothcorp.com
Example—FlowCapacityCalculation 1. Read flow capacity at set vacuum from table Flow = 3,200 NCMH 6" Model 1361A 2. Calculate over-vacuum % OV = [(0.17 - 0.12)/0.12] x 100 = 42% 0.12 barg Set Vacuum [Ps] 3. Read “C” factor from table “C” = 0.55 0.17 barg Flowing Vacuum [Pf] 4. Calculate flow capacity Flow = 0.55 x 3,200 = 1,760 NCMH Example—To find “C” factor from table: Read “C” factor for 72% over-vacuum at intersection of row 40 and column 2 “C” factor at 42% OV = 0.55 “C”FactorTable %OV0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00 MODEL 1220A FLOW CAPACITY CALCULATION AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000NormalCubicMetersperHourat0°C SetVacuum(Ps)Size barg3"(80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 14" (350mm)

MODEL 5000

• Sizes // 2" through 12"

• Available in carbon steel, stainless steel, and other materials

• High flow capacity

FREE VENTS

Model 5100 Series are designed to be used on tanks containing non-volatile liqids and on vent pipe extremities. Groth Free Vents offer efficient flow capacity for the protection of the tank.

SPECIAL FEATURES

Model 5100 Series are built of corrosion resistant materials throughout. A wire mesh screen prevents foreign matter from entering the tank or pipe opening. Weather hoods are easily removable for inspection of vent and wire mesh screen.

VALVES & TANK EQUIPMENT // PAGE 67 www.grothcorp.com
MODEL5000MODEL5100
MODEL5100

SPECIFICATIONS

Specifications subject to change without notice. Certified dimensions available upon request.

MODEL5000

2"10.25"6.87"8 (50mm)(260mm)(174mm)(4kg)

3"14.50"9.25"20 (80mm)(368mm)(235mm)(9kg)

4"18.75"11.37"35 (100mm)(476mm)(289mm)(16kg)

6"26.87"15.68"70 (150mm)(682mm)(398mm)(32kg)

8"35.12"20.12"135 (200mm)(892mm)(511mm)(61kg)

10"43.37"24"235 (250mm)(1102mm)(610mm)(107kg)

12"51.87"28.43"350 (300mm)(1317mm)(722mm)(159kg)

Larger sizes available on special application.

HOW TO ORDER

MODEL5100

2"9.50"5.37"11 (50mm)(241mm)(136mm)(5kg)

3"11.50"5.81"14 (80mm)(292mm)(148mm)(6kg)

4"13"6.31"18 (100mm)(330mm)(160mm)(8kg)

6"17"7.37"28 (150mm)(432mm)(187mm)(13kg)

8"19.50"9.25"42 (200mm)(495mm)(235mm)(19kg)

10"23.50"10.62"60 (250mm)(597mm)(270mm)(27kg)

12"25.50"13.50"95 (300mm)(648mm)(343mm)(43kg)

VALVES & TANK EQUIPMENT // PAGE 68 www.grothcorp.com
B BB AA A
Size◊ Flange
A Width (Metric) B Height (Metric) Approx. Ship Wt.Lbs.
(Metric)
Size◊ Flange (Metric) AA Width (Metric) BB Height (Metric) Approx. Ship Wt.Lbs.
*
For
numbers MODEL#SIZEMATERIALOPTIONS 5000 5100 3 = Carbon Steel 5 = Stainless Steel Z = Special O = No Options Z = Special Options Body Material 02" Thru 12" • Include model number and setting when ordering. • For special options, consult factory NOTES EXAMPLE Indicates a 2" Model 5000 with Carbon Steel Body and no other options. 5000023O
easy ordering, select proper model

MODEL 5000 // FLOW CAPACITY

VALVES & TANK EQUIPMENT // PAGE 69 www.grothcorp.com
AirFlow-1000StandardCubicFeetperHourat60°F TankPressureSize InWCoz/in22" (50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 10.583.347.3412.728.649.678.2112 21.164.7210.417.940.570.2111159 31.735.7812.721.949.585.9135194 42.316.6714.725.357.299.2156224 63.478.1718.031.070.0121192275 84.629.4420.835.880.9140221317 105.7810.523.240.090.4157247354 158.6612.928.448.9111192303434 2011.614.932.856.5128221349501 2514.416.736.663.1143248390560 3017.318.240.169.1156271427613 3520.219.743.374.6169293461662 4023.121.046.379.7180313493707 4526.022.349.184.5191332523750 5028.923.551.789.1201349551790 5531.824.654.293.4211366577828 6034.725.756.697.5220382603864 Air Flow1000 SCFH at 60°F Tank Pressure - InWC 12" 10" 8" 6" 4" 3" 2" 1,000 100 10 1 0 10 20 30 40 50 60

MODEL 5000 // FLOW CAPACITY

13751350.691.522.625.9410.316.223.3 15001470.721.592.746.2010.716.924.3

VALVES & TANK EQUIPMENT // PAGE 70 www.grothcorp.com
TankPressureSize mmWCmb2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)
Air Flow1000 NCMH at 0°C Tank Pressure - mmWC 12" 10" 8" 6" 4" 3" 2" 100 10 1 0.1 0.01 0 250 500 750 1,000 1,250 1500
AirFlow-1000NormalCubicMetersperHourat0°C
252.450.090.210.360.801.392.203.15 504.900.130.290.501.141.973.114.46 757.350.160.360.621.392.413.815.46 1009.800.190.410.711.612.794.406.30 15014.70.230.510.871.973.415.387.72 20019.60.270.581.012.273.946.218.91 25024.50.300.651.122.544.416.959.96 37536.80.360.801.383.115.398.5012.2 50049.00.420.921.593.596.239.8114.1 62561.30.471.031.774.016.9611.015.7 75073.50.511.131.944.397.6212.017.2 87585.80.551.222.104.748.2213.018.6 100098.00.591.302.245.078.7913.919.9 11251100.631.382.385.379.3214.721.1 12501230.661.452.505.669.8215.522.2

MODEL 5000 // FLOW CAPACITY

VALVES & TANK EQUIPMENT // PAGE 71 www.grothcorp.com Air Flow1000 SCFH at 60°F Tank Vacuum - InWC 12" 10" 8" 6" 4" 3" 2" 1,000 100 10 1 0 10 20 30 40 50 60
AirFlow-1000StandardCubicFeetperHourat60°F TankVacuumSize InWCoz/in22" (50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 10.582.786.1110.523.841.365.193.4 21.163.928.6314.933.658.391.9132 31.734.8010.618.241.171.3112161 42.315.5312.221.047.482.3130186 63.476.7614.925.657.9100158227 84.627.7917.129.566.7116182262 105.788.6819.132.974.4129203292 158.6610.623.240.090.5157247355 2011.612.126.645.9104180284407 2514.413.429.651.0115200315452 3017.314.632.255.4125217343491 3520.215.734.559.4134233367527
4526.017.538.566.4150260411589 5028.918.340.369.5157272430616
4023.116.636.663.1143247390559
5531.819.142.072.3164284447641 6034.719.843.575.0169294463665

MODEL 5000 // FLOW CAPACITY

VALVES & TANK EQUIPMENT // PAGE 72 www.grothcorp.com
AirFlow-1000NormalCubicMetersperHourat0°C TankVacuumSize mmWCmb2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)
504.90.110.240.420.951.62.63.7
Air Flow1000 NCMH at 0°C Tank Vacuum - mmWC 12" 10" 8" 6" 4" 3" 2" 100 10 1 0.1 0.01 0 250 500 750 1,000 1,250 1500
252.50.080.170.300.671.21.82.6
757.40.130.300.511.162.03.24.5 1009.80.160.340.591.332.33.65.2 15014.70.190.420.721.632.84.56.4 20019.60.220.480.831.883.35.17.4 25024.50.240.540.922.093.65.78.2 37536.80.300.651.132.544.47.010.0 50049.00.340.751.292.925.18.011.4 62561.30.380.831.433.245.68.912.7 75073.50.410.901.563.526.19.613.8 87585.80.440.971.673.786.610.314.8 100098.00.471.031.774.017.011.015.7 11251100.491.081.874.237.311.616.6 12501230.521.131.964.427.712.117.3 13751350.541.182.044.608.012.618.0 15001470.561.222.114.778.313.018.7

MODEL 5100 // FLOW CAPACITY

VALVES & TANK EQUIPMENT // PAGE 73 www.grothcorp.com
AirFlow-1000StandardCubicFeetperHourat60°F TankPressureSize InWCoz/in22" (50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 10.583.788.3214.332.456.288.6127 21.165.3511.820.345.879.5125180 31.736.5514.424.856.197.4154220 42.317.5616.628.764.8112177254 63.479.2620.435.179.4138217311 84.6210.723.540.591.7159251359 105.7812.026.345.3102178280402 158.6614.632.255.5125217343492 2011.616.937.264.0145251396568 2514.418.941.571.5162281442634 3017.320.745.578.3177307484695 3520.222.349.184.6191332523750 4023.123.852.490.4204354559801 4526.025.355.695.8217376592850 5028.926.658.6101228396624895 5531.827.961.4106239415654938 6034.729.264.1110250433683980 Air Flow1000 SCFH at 60°F Tank Pressure - InWC 12" 10" 8" 6" 4" 3" 2" 1,000 100 10 1 0 10 20 30 40 50 60

MODEL 5100 // FLOW CAPACITY

757.350.180.410.701.582.744.316.19 1009.800.210.470.811.823.164.987.14 15014.70.260.570.992.233.876.108.75 20019.60.300.661.142.584.477.0410.1 25024.50.340.741.272.884.997.8711.3 37536.80.410.901.563.536.119.6413.8 50049.00.471.041.804.077.0611.116.0 62561.30.531.172.014.557.8812.417.8 75073.50.581.282.204.988.6313.619.5 87585.80.631.382.385.389.3214.721.1 100098.00.671.472.545.7410.015.722.5 11251100.711.562.696.0910.616.623.9 12501230.751.652.846.4211.117.525.2 13751350.781.732.976.7311.718.426.4 15001470.821.803.117.0212.219.227.5

VALVES & TANK EQUIPMENT // PAGE 74 www.grothcorp.com
TankPressureSize mmWCmb2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm)
504.900.150.330.571.292.233.525.05
Air Flow1000 NCMH at 0°C Tank Pressure - mmWC 0 250 500 750 1,000 1,250 1500 100 10 1 0.1 12" 10" 8" 6" 4" 3" 2"
AirFlow-1000NormalCubicMetersperHourat0°C
252.450.110.230.400.911.582.493.57

MODEL 5100 // FLOW CAPACITY

VALVES & TANK EQUIPMENT // PAGE 75 www.grothcorp.com
InWCoz/in22" (50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 10.583.066.7211.626.245.471.6103 21.164.329.4916.437.064.1101145 31.735.2811.620.045.278.5124177 42.316.0913.423.152.290.5143205 63.477.4416.428.263.7111174250 84.628.5618.832.573.4127201288
158.6611.625.544.099.6173272390 2011.613.329.350.5114198312448
Air Flow1000 SCFH at 60°F Tank Vacuum - InWC 12" 10" 8" 6" 4" 3" 2" 1,000 100 10 1 0 10 20 30 40 50 60
AirFlow-1000StandardCubicFeetperHourat60°F TankVacuumSize
105.789.5521.036.281.8142224321
2514.414.832.556.1127220347497 3017.316.135.461.0138239377541 3520.217.337.965.4148256404580 4023.118.340.369.4157272429615 4526.019.342.473.1165286452648 5028.920.244.476.4173300473678 5531.821.046.279.6180312492705 6034.721.847.882.5186323510731

MODEL 5100 // FLOW CAPACITY

15014.70.210.460.791.793.114.907.02 20019.60.240.530.912.063.585.648.09 25024.50.270.591.022.303.996.299.02 37536.80.330.721.242.804.857.6511.0 50049.00.370.821.423.215.578.7812.6 62561.30.420.911.583.566.189.7414.0 75073.50.451.001.713.886.7210.615.2 87585.80.491.071.844.167.2111.416.3 100098.00.521.131.954.417.6512.117.3 11251100.541.192.064.658.0612.718.2 12501230.571.252.154.868.4313.319.1 13751350.591.302.245.068.7813.819.9 15001470.611.352.325.259.1014.320.6

VALVES & TANK EQUIPMENT // PAGE 76 www.grothcorp.com
TankVacuumSize mmWCmb2"(50mm) 3" (80mm) 4" (100mm) 6" (150mm) 8" (200mm) 10" (250mm) 12" (300mm) 252.450.090.190.330.741.282.012.89 504.900.120.270.461.041.802.844.08 757.350.150.330.561.272.213.484.99
Air Flow1000 NCMH at 0°C Tank Vacuum - mmWC 12" 10" 8" 6" 4" 3" 2" 100 10 1 0.1 0.01 0 250 500 750 1,000 1,250 1500
AirFlow-1000NormalCubicMetersperHourat0°C
1009.800.170.380.651.472.544.015.75

MODEL 6000

• Sizes // 4" through 10"

• Available in aluminum, carbon steel, stainless steel, and other materials

• Available in free lift or lockdown cover

• Designed to assure uniform seating

GAUGE HATCH

Model 6000 Series provide access for gauging or obtaining product samples from storage tanks. The Model 6000 also provides pressure relief as emergency venting. The Model 6100 incorporates a positive cover hold down which assures a premium tight seal on tanks with internal pressures up to 3 psig. Gasketed covers are recommended on tanks with high pressure settings. Model 6100 offers lockdown capability.

SPECIAL FEATURES

Model 6000 Series is designed with a serrated foot lever surface to avoid foot slippage when opening. This model permits the use of both hands during gauging or sampling. Gravity will close the cover upon removal of pressure on the foot treadle. Groth’s special “cushioned-air” seating or metal-to-metal seatings available.

VALVES & TANK EQUIPMENT // PAGE 77 www.grothcorp.com
MODEL6000MODEL6100

SPECIFICATIONS

Specifications subject to change without notice. Certified dimensions available upon request.

4"10"6"7 (100mm)(250mm)(152mm)(3kg)

6"12.50"8"10 (150mm)(318mm)(203mm)(5kg)

8"15"8"13 (200mm)(381mm)(203mm)(6kg) 10"17.75"9"17 (250mm)(451mm)(229mm)(8kg)

VALVES & TANK EQUIPMENT // PAGE 78 www.grothcorp.com
BB AA
Size (Metric) A Width (Metric) B Height (Metric) Approx.Ship Wt.Lbs. Aluminum
‡ When gauge hatch includes the lockdown feature, change model number to 6100. † 150 # ANSI. drilling compatibility, F.F. on aluminum, carbon steel, and stainless steel alloys. For easy ordering, select proper model numbers MODEL#SIZEMATERIALOPTIONS 6000 6100 1 = Aluminum 3 = Carbon Steel 5 = Stainless Steel Z = Special O = No Options Z = Special Options D = Drilled 150# ANSI U = Undrilled Diaphragm Material (Seat): B = Buna-N T = Fluoropolymer V = FKM M = Metal-to-Metal Z = Special Body Material 04" Thru 10" • Include model number and setting when ordering. • For special options, consult factory NOTES EXAMPLE Indicates a 4" Model 6000 with Aluminum Body, Fluoropolymer Seat Diaphragm, Drilled Flange and no other options. 6000041TDO HOW TO ORDER

MODEL 2000A

• Sizes // 16", 20" and 24”

• Pressure settings // 1.5 - 16 oz/in2

• Vacuum settings // 0.5 - 4 oz/in2

• Available in carbon steel, stainless steel, fiberglass and other materials

• Easy access manway combined with emergency relief

EMERGENCY PRESSURE RELIEF VALVE

Model 2000A is designed to provide emergency relief capacity beyond that furnished by the normal operating pressure relief valve on the tank. The valve protects the tank against rupture or explosion that could result from excessive internal pressures caused by fire, etc. As excessive pressure builds up, the Groth Model 2000A relieves excess pressure, then reseats when pressure has been dissipated. Removable stops can be provided which restrict the lift of the cover.

SPECIAL FEATURES

Model 2000A is built of corrosion resistant materials throughout. A grounding cable connects the head and flange. Groth’s special fluoropolymer “cushioned air” pallet and peripheral guiding insures proper alignment and integrity of seating. Model 2050A incorporates a vacuum breaker for added vacuum relief capability.

VALVES & TANK EQUIPMENT // PAGE 79 www.grothcorp.com MODEL2000AMODEL2050A

SPECIFICATIONS

B ABB

Specifications subject to change without notice. Certified dimensions available upon request.

MODEL2000A

16"1.50oz/in216oz/in223.50"11"62 (406mm)(6.5mbar)(69mbar)(597mm)(279mm)(28kg)

20"1.50oz/in216oz/in227.50"11"88 (508mm)(6.5mbar)(69mbar)(699mm)(279mm)(40kg)

24"1.50oz/in216oz/in232"11"114 (610mm)(6.5mbar)(69mbar)(813mm)(279mm)(52kg)

MODEL2050A

16"2.6oz/in20.5oz/in

(406mm)(11.2mbar)(2.2mbar)(34.5mbar)(597mm)(451mm)(31kg)

20"2.1oz/in20.5oz/in28oz/in227.50"17.75"95 (508mm)(9.1mbar)(2.2mbar)(34.5mbar)(699mm)(451mm)(43kg)

24"1.9oz/in20.5oz/in28oz/in232"17.75"120 (610mm)(8.2mbar)(2.2mbar)(34.5mbar)(813mm)(451mm)(55kg)

s Maximum

HOW TO ORDER

◊ Max. vacuum setting is 4 oz./in2 Fiberglass dimensions on request. For easy ordering, select proper model numbers

on

=

• Include model number and setting when ordering.

• For special options, consult factory

• When ordering steam jacket, include steam pressure / temperature. * Stainless steel guides, stems are standard with carbon steel bodies.

Material (Seat):

VALVES & TANK EQUIPMENT // PAGE 80 www.grothcorp.com
Size* (Metric) Minimum PressureSetting WeightLoaded Maximum PressureSetting WeightLoaded A Width (Metric) B Height† (Metric) Approx. ShipWt.Lbs. atmin.setting
Size* (Metric) MinimumSettingMaximumSettingsAWidth (Metric) BBHeight Closed (Metric) Approx. ShipWt.Lbs. Pressureatmin.settingWeightLoaded Vacuum SpringLoaded Pressures ◊ WeightLoaded
28oz/in223.50"17.75"69
*
650
MODEL#SIZEMATERIALOPTIONS 2000A Pressure Only 2050A Pressure/Vacuum 3 = Carbon Steel 5 = Stainless Steel 6 = Vinyl Ester Resin 7 = Furan Z = Special O
No Options Z
Special Options O = No Jacket J = Steam Jacket 1 = ANSI 150# drilled
A.P.I.
drilled
V
Body Material* 16" 20” 24"
150# ANSI. or API 650 drilling compatibility. “Caution” See IOM when mounting to API
flange.
pressure setting
16" size
4 oz/in2
=
=
2 =
650
Diaphragm
B = Buna-N T = Fluoropolymer
= FKM Z = Special
NOTES EXAMPLE Indicates a 20" Model 2000A with Stainless Steel Body, Fluoropolymer Seat Diaphragm, ANSI 150# drilled, Steam Jacket and no other options. 2000A2051JTO

* Standard vacuum settings, consult factory for other settings.

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 81 www.grothcorp.com
AirFlowCapacityat100%Overpressure(DoubleSetPressure/Vacuum) 1000StandardCubicFeetperHourat60°F SetPressure/Vacuum(Ps)Size InWCoz/in216"Pressure20"Pressure24"PressureAllVacuum*2050Only 0.870.50*65 1.731.00*91 2.601.50422668970 3.001.734547181043 3.462.00*4877711120129 4.002.315248291204 4.332.505458621252 5.002.895859261345 5.193.00*5979441371157 6.934.00*68910901583180 10.46.0084313341937 13.98.0097315392236 17.310.00108717202498 20.812.00119018832735 24.214.00128420332952 27.716.00137221723154 For Vacuum Flow, Usethe "C1" FactorTable Locatedwith Model2100
2000A/2050A // PRESSURE/ VACUUM RELIEF CAPACITY
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 829,000 SCFH 20" Model 2000A 2. Calculate overpressure % OP = [(7 - 4)/4] x 100 = 75% 4 InWC set pressure [Ps] 3. Read “C” factor from table “C” = 0.95 7 InWC flowing pressure [Pf] 4. Calculate flow capacity Flow = 0.95 x 829,000 = 787,550 SCFH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.95
CALCULATION “C4” Factor Table - Pressure Only %OP0123456789 100.700.710.710.720.720.730.730.740.740.75 200.750.760.760.770.770.780.780.790.790.80 300.800.810.810.820.820.830.830.840.840.85 400.850.860.860.870.870.880.880.890.890.90 500.900.900.900.910.910.910.910.910.920.92 600.920.920.920.930.930.930.930.930.940.94 700.940.940.940.950.950.950.950.950.960.96 800.960.960.960.970.970.970.970.970.980.98 900.980.980.980.990.990.990.990.991.001.00
MODEL 1220A FLOW CAPACITY

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 82 www.grothcorp.com AirFlowCapacityat100%Overpressure(DoubleSetPressure/Vacuum) 1000NormalCubicMetersperHourat0°C SetPressure/Vacuum(Ps)Size mmWCmb16"Pressure20"Pressure24"PressureAllVacuum*2050Only 222.16*1.83 444.31*2.58 888.63*13.821.931.73.63 1009.8014.723.333.8 13212.9*16.926.838.94.42 17617.3*19.530.944.95.08 20019.620.832.947.8 25024.523.236.853.4 30029.425.540.358.5 35034.327.543.563.2 40039.229.446.567.5 50049.032.851.975.4 60058.835.956.982.6 70068.638.861.489.1 For Vacuum Flow, Usethe "C1" FactorTable Locatedwith Model2100 * Standard vacuum settings, consult factory for other settings. “C4” Factor Table - Pressure Only %OP0123456789 100.700.710.710.720.720.730.730.740.740.75 200.750.760.760.770.770.780.780.790.790.80 300.800.810.810.820.820.830.830.840.840.85 400.850.860.860.870.870.880.880.890.890.90 500.900.900.900.910.910.910.910.910.920.92 600.920.920.920.930.930.930.930.930.940.94 700.940.940.940.950.950.950.950.950.960.96 800.960.960.960.970.970.970.970.970.980.98 900.980.980.980.990.990.990.990.991.001.00
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 23,300 NCMH 20" Model 2000A 2. Calculate overpressure % OP = [(175 - 100)/100] x 100 = 75% 100 mmWC Set Pressure [Ps] 3. Read “C” factor from table “C” = 0.95 175 mmWC Flowing Pressure [Pf] 4. Calculate flow capacity Flow = 0.95 x 23,300 = 22,135 NCMH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.95
PRESSURE/ VACUUM RELIEF CAPACITY
MODEL 1220A FLOW CAPACITY CALCULATION 2000A/2050A //

MODEL 2100

• Sizes // 16", 20" and 24”

• Pressure settings // 1 - 15 psig

• Available in carbon steel, stainless steel and other materials

• Unique design // spring loaded cover

EMERGENCY PRESSURE RELIEF VALVE

Model 2100 is designed to provide emergency relief capacity beyond that furnished by the normal operating pressure relief valve on the tank. The valve protects the tank against rupture or explosion that could result from excessive internal pressures caused by fire, etc. As excessive pressure builds up, Model 2100 relieves, then reseats when the overpressure has been dissipated.

SPECIAL FEATURES

Model 2100 is built of corrosion resistant materials throughout. It is designed with independently adjustable springs which load the cover and keep the valve tightly sealed until set pressure is reached. The Model 2100 features a FKM seating to ensure a tight seal.

VALVES & TANK EQUIPMENT // PAGE 83 www.grothcorp.com
MODEL2100

SPECIFICATIONS

Specifications subject to change without notice. Certified dimensions available upon request.

(406mm)(69mbar)(1.03bar)(933mm)(584mm)(141kg)(223kg)

(508mm)(69mbar)(1.03bar)(933mm)(584mm)(152kg)(227kg)

(610mm)(69mbar)(1.03bar)(1035mm)(686mm)(190kg)(304kg)

VALVES & TANK EQUIPMENT // PAGE 84 www.grothcorp.com
Size* Flange (Metric) Minimum Setting Pressure SpringLoaded Maximum Setting Pressure SpringLoaded A Width (Metric) B Height† (Metric) Approx. ShipWt.Lbs. (Atmin.set.)(Atmax.set.) 16” 1psig15psig 36.75”23” 310490
20” 1psig15psig 36.75”23” 335500
24” 1psig15psig 40.75”27” 420670
B A
For easy ordering, select proper model numbers MODEL#SIZEMATERIALOPTIONS 2100 3 = Carbon Steel 5 = Stainless Steel Z = Special O = No Options Z = Special Options O = No Jacket J = Steam Jacket 1 = ANSI 150# drilled 2 = A.P.I. 650 drilled O-Ring Material (Seat)** B = Buna-N V = FKM Z = Special Body Material* 16" 20” 24" • Include model number and setting when ordering. • For special options, consult factory • When ordering steam jacket, include steam pressure / temperature. * Seat material on carbon steel base is Stainless Steel weld overlay ** Fluoropolymer O-Ring not available NOTES EXAMPLE Indicates a 20" Model 2000A with Stainless Steel Body, FKM Seat O-Ring, ANSI 150# drilled, Steam Jacket and no other options. 21002051JVO
*150# ANSI. drilling compatibility, or API 650 drilled flange option
HOW TO ORDER

MODEL 2100 // PRESSURE RELIEF CAPACITY

MODEL 1220A FLOW CAPACITY CALCULATION

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 85 www.grothcorp.com
AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000StandardCubicFeetperHourat60°F SetPressure(Ps)Size psig16"(406mm)20"(508mm)24"(610mm) 1.006099521371 2.0085713401930 3.00104516332352 4.00120118772704 5.00133720893009 6.00145822783282 7.00156824503529 8.00166926083757 9.00176327553969 10.0185128934167 11.0193430224353 12.0201231454530 13.0208732614697 14.0215833724857 15.0222634785010
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 1,877,000 SCFH 20" Model 2100 2. Calculate overpressure % OP = [(7 - 4)/4] x 100 = 75% 4 psig Set Pressure [Ps] 3. Read “C” factor from table “C” = 0.83 7 psig Flowing Pressure [Pf] 4. Calculate flow capacity Flow = 0.83 x 1,877,000 = 1,557,910 SCFH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.83 “C”FactorTable %OP0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00

MODEL 2100 // PRESSURE RELIEF CAPACITY

MODEL 1220A FLOW CAPACITY CALCULATION

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 86 www.grothcorp.com
AirFlowCapacityat100%Overpressure(DoubleSetPressure) 1000NormalCubicMetersperHourat0°C SetPressure(Ps)Size barg16"(406mm)20"(508mm)24"(610mm) 0.0717.827.839.9 0.1021.233.147.6 0.1525.840.458.1 0.2029.746.566.8 0.2533.151.874.5 0.3036.256.681.3 0.3538.960.987.5 0.4041.564.993.3 0.4543.968.698.6 0.5046.172.1104 0.5548.275.4108 0.6050.278.5113
0.8057.389.6129 0.9060.594.6136 1.0063.499.2143
0.7053.984.3121
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 64,900 NCMH 20" Model 2100 2. Calculate overpressure % OP = [(0.7 - 0.4)/0.4] x 100 = 75% 0.4 barg Set Pressure [Ps] 3. Read “C” factor from table “C” = 0.83 0.7 barg Flowing Pressure [Pf] 4. Calculate flow capacity Flow = 0.83 x 64,900 = 53,867 NCMH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.83 “C”FactorTable %OP0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00

MODEL 2400A//2450A

• Sizes // 16", 20" and 24”

• Pressure settings // 1.5 - 8 oz/in2

• Vacuum settings // 0.5 - 4 oz/in2

• Hinged with lift stop for positive reseating

• Available in carbon steel, stainless steel, and other materials

• Easy access manway combined with emergency relief

EMERGENCY PRESSURE RELIEF VALVE

Series 2400A is designed to provide emergency relief capacity beyond that furnished by the normal operating pressure/vacuum relief valve on the tank. The valve protects the tank against rupture or internal pressures caused by fire exposure. Series 2400A is designed to be selfclosing. As excessive pressure builds up, Series 2400A relieves, then reseats when overpressure has been dissipated. Counter weights are available for lower settings.

SPECIAL FEATURES

Model 2000A is built of corrosion resistant materials throughout. Groth’s special fluoropolymer “cushioned air” pallet and peripheral guiding insures proper alignment and integrity of seating. Model 2450A incorporates a vacuum breaker for added vacuum relief capability.

VALVES & TANK EQUIPMENT // PAGE 87 www.grothcorp.com
MODEL2400AMODEL2450A

SPECIFICATIONS

Specifications subject to change without notice. Certified dimensions available upon request.

MODEL2400A

16"1.5oz/in28oz/in223.50" 11” 20.50"72 (406mm)(6.5mbar)(34.5mbar)(597mm)(279mm)(521mm)(33kg)

20"1.5oz/in28oz/in228.75"11"22.50"98 (508mm)(6.5mbar)(34.5mbar)(730mm)(279mm)(572mm)(45kg)

24"1.5oz/in28oz/in233.25" 11” 24.50"124 (610mm)(6.5mbar)(34.5mbar)(845mm)(279mm)(622mm)(56kg)

MODEL2450A

(406mm)(11.6mbar)(2.2mbar)(34.5mbar)(597mm)(470mm)(622mm)(36kg)

20"2.3oz/in20.5oz/in28oz/in228.75"18.50" 26” 105 (508mm)(9.9mbar)(2.2mbar)(34.5mbar)(730mm)(470mm)(660mm)(48kg)

24"2.0oz/in20.5oz/in28oz/in233.25"

27.50"130 (610mm)(8.6mbar)(2.2mbar)(34.5mbar)(845mm)(470mm)(699mm)(59kg)

* 150# ANSI. or API 650 drilling compatibility. † Minimum pressure setting 1.0 oz/in2 on special application.

s Maximum pressure setting on 16” size = 4 oz/in2. Fiberglass dimensions on request. “Caution” See IOM when mounting to API 650 flange. ◊ Max. vacuum setting is 4 oz./in2. **Minimum pressure setting 1.5 oz/in2 on special application.

HOW TO ORDER

For easy ordering, select proper model numbers

• Include model number and setting when ordering.

• For special options, consult factory

• When ordering steam jacket, include steam pressure / temperature.

* Seat material on carbon steel base is Stainless Steel weld overlay

Material*

= No Options

= Special Options

= No Jacket

= Steam Jacket

= ANSI 150# drilled

= A.P.I. 650 drilled

Diaphragm Material (Seat): B = Buna-N T = Fluoropolymer V = FKM

Z = Special

VALVES & TANK EQUIPMENT // PAGE 88 www.grothcorp.com
Size* (Metric) Standard SettingPressure WeightLoaded Maximum SettingPressure WeightLoaded A Width (Metric) BHeight (Atmax.setting)Approx.ShipWt.Lbs. Closedatmin.setting (Metric)Open(Metric)
Size* (Metric) StandardSettingMaximumSettingA Width (Metric) BHeightApprox. ShipWt.Lbs. atmin.setting Pressure† Weight Loaded Vacuum Spring Loaded Pressure s◊ Weight Loaded Closed (Metric) Open (Metric)
28oz/in223.50" 18.50”
16"2.7oz/in20.5oz/in
24.50"79
18.50”
B BB A
MODEL#SIZEMATERIALOPTIONS 2400A Pressure Only 2450A Pressure/Vacuum 3 = Carbon Steel 5 = Stainless Steel Z = Special O
Z
O
J
1
2
Body
16" 20” 24"
NOTES EXAMPLE Indicates a 20" Model 2400A with Stainless Steel Body, Fluoropolymer Seat Diaphragm, ANSI 150# drilled, Steam Jacket and no other options. 2400A2051JTO

* Standard vacuum settings, consult factory for other settings.

MODEL 1220A FLOW CAPACITY CALCULATION

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 89 www.grothcorp.com
AirFlowCapacityat100%Overpressure(DoubleSetPressure/Vacuum) 1000StandardCubicFeetperHourat60°F SetPressure/Vacuum(Ps)Size InWCoz/in216"Pressure20"Pressure24"PressureAllVacuum*2050Only 0.870.50*65 1.731.00*91 2.601.50422668970 3.001.734547181043 3.462.00*4877711120129 4.002.315248291204 4.332.505458621252 5.002.895859261345 5.193.00*5979441371157 6.934.00*68910901583180 10.46.0084313341937 13.98.0097315392236 For Vacuum Flow, Usethe "C1" FactorTable Locatedwith Model2100
2400A/2450A // PRESSURE/ VACUUM RELIEF CAPACITY
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 829,000 SCFH 20" Model 2400A 2. Calculate overpressure % OP = [(7 - 4)/4] x 100 = 75% 4 InWC set pressure [Ps] 3. Read “C” factor from table “C” = 0.95 7 InWC flowing pressure [Pf] 4. Calculate flow capacity Flow = 0.95 x 829,000 = 787,550 SCFH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.95
“C4” Factor Table - Pressure Only %OP0123456789 100.700.710.710.720.720.730.730.740.740.75 200.750.760.760.770.770.780.780.790.790.80 300.800.810.810.820.820.830.830.840.840.85 400.850.860.860.870.870.880.880.890.890.90 500.900.900.900.910.910.910.910.910.920.92 600.920.920.920.930.930.930.930.930.940.94 700.940.940.940.950.950.950.950.950.960.96 800.960.960.960.970.970.970.970.970.980.98 900.980.980.980.990.990.990.990.991.001.00

MODEL 1220A FLOW CAPACITY CALCULATION

Flow capacity values listed above are based on full open valves at 100% overpressure.

Read the flow capacity at 100% overpressure directly from the table above. Use linear interpolation if the set pressure is not listed.

If the allowable overpressure is less than 100%, modify the flow capacity using the appropriate “C” factor from the table. If allowable overpressure is more than 100%, consult your Groth Representative.

Calculate the percentage overpressure by the following formula. Note that all pressures are gauge pressure expressed in the same units of measure.

Pf = Flowing pressure

P s = Set pressure

% OP = [(Pf - Ps)/Ps] x 100

Calculate flow capacity at less than 100% overpressure according to the following example.

VALVES & TANK EQUIPMENT // PAGE 90 www.grothcorp.com AirFlowCapacityat100%Overpressure(DoubleSetPressure/Vacuum) 1000NormalCubicMetersperHourat0°C SetPressure/Vacuum(Ps)Size mmWCmb16"Pressure20"Pressure24"PressureAllVacuum*2050Only 222.16*1.83 444.31*2.58 888.63*13.821.931.73.63 1009.8014.723.333.8 13212.9*16.926.838.94.42 17617.3*19.530.944.95.08 20019.620.832.947.8 25024.523.236.853.4 30029.425.540.358.5 35034.327.543.563.2 For Vacuum Flow, Usethe "C1" FactorTable Locatedwith Model2100 * Standard vacuum settings, consult factory for other settings. “C4” Factor Table - Pressure Only %OP0123456789 100.700.710.710.720.720.730.730.740.740.75 200.750.760.760.770.770.780.780.790.790.80 300.800.810.810.820.820.830.830.840.840.85 400.850.860.860.870.870.880.880.890.890.90 500.900.900.900.910.910.910.910.910.920.92 600.920.920.920.930.930.930.930.930.940.94 700.940.940.940.950.950.950.950.950.960.96 800.960.960.960.970.970.970.970.970.980.98 900.980.980.980.990.990.990.990.991.001.00
Example—FlowCapacityCalculation 1. Read flow capacity at set pressure from table Flow = 23,300 NCMH 20" Model 2400A 2. Calculate overpressure % OP = [(175 - 100)/100] x 100 = 75% 100 mmWC Set Pressure [Ps] 3. Read “C” factor from table “C” = 0.95 175 mmWC Flowing Pressure [Pf] 4. Calculate flow capacity Flow = 0.95 x 23,300 = 22,135 NCMH Example—To find “C” factor from table: Read “C” factor for 75% overpressure at intersection of row 70 and column 5 “C” factor at 75% OP = 0.95
2400A/2450A // PRESSURE/ VACUUM RELIEF CAPACITY

FIBERGLASS RELIEF VALVES

• Groth provides fiberglass products for corrosive service

• Available Available in Series 1200A, 1300A, 2000A and others

FIBERGLASS SERIES 1200A, 1300A, 2000A AND OTHERS

Fiberglass valves are used the same as their counterparts manufactured in metal, primarily on aboveground storage tank installations. Fiberglass construction can be used where highly corrosive and toxic liquids are being stored. The fiberglass series design will protect the tank from damage created by overpressuring or excessive vacuum. Costly product evaporation losses due to normal tank “breathing” are greatly reduced. Retention of product vapors reduces the possibility of atmospheric contamination.

SPECIAL FEATURES

Fiberglass valves offer Groth’s special “cushioned air” seating. Superior performing fluoropolymer seating diaphragms are standard to minimize sticking caused by resinous vapors and atmospheric moisture. These valves have a self draining housing body and drip rings to protect seating surfaces from condensate and freezing. This design also avoids pressure or vacuum buildup due to binding or clogging of the valves. These fiberglass valves may be spring loaded when required for use on blanketed tank or other type installations requiring higher settings. To insure the proper alignment of seating surfaces there is peripheral guiding and a center stabilizing stem.

VALVES & TANK EQUIPMENT // PAGE 91 www.grothcorp.com

FIBERGLASS RELIEF VALVES

FIBERGLASSWITH VINYLESTERRESIN#411

FIBERGLASS WITHFURANRESIN

RESISTANTRESISTANT

ACIDS:BASES:ACIDS:

Acetic Potassium HydroxideAcetic Nitric (5%)

Acrylic Sodium Hydroxide *Acrylic Phosphoric

Boric Ammonium Hydroxide *Chlorophenol Sulfonic

Chromic (20%)Ammonium CarbonateHydrochloric Sulfuric (25%, 50%)

Formic Potassium Carbonate *

Hydrochloric Sodium Carbonate *

BASES:

Hydrofluoric * Aniline Sodium Carbonate

Nitric (<40%)

WATER: Diethylamine Sodium Hydroxide

Perchloric Demineralized Potassium Carbonate(5%, 50%)

Phosphoric Distilled

Sulfuric (75%)

SALTS:

OTHERS: Alum Ferric Chloride

SALTS: Alcohols Ammonium BromideMagnesium Sulfate

Alum Alum ChlorohydroxideCalcium ChlorideSodium Chromate

Ammonium ChlorideGlycerin

Calcium ChlorideSulfonated Detergents

WATER: Ferric ChlorideUrea-Ammonium NitrateDemineralizedDistilled

Magnesium SulfateFertilizers

Sodium Chloride

Sodium Chromate

BLEACHINGAGENTS:

Calcium Chlorate

Calcium Hypochlorite

Chlorine Dioxide

Chlorine Water

Hydrogen Peroxide

Potassium

Permanganate

Sodium Chlorate

Sodium Hypochlorite

Solvents

SOLVENTS:

Acetone Methanol

Benzene Methyl Ethyl Ketone

Carbon DisulfideMethyl Isobutyl Ketone

Carbon TetrachloridePerchloroethylene

ChlorobenzeneToluene

Ethanol Trichloroethylene

Ethyl Acetate Xylene

Ethylene Dichloride

OTHERS:

Acrylonitrile Pulp Mill Liquors

Benzyl ChlorideStyrene

CyclohexanoneToluene Diisocyanate

Formalin

NONRESISTANTNONRESISTANT

Phenol

Bleaching AgentsPeroxides

Oleum Bromine Free Halogens

Furfural

*Synthetic Veil should be used in inner layer.

• Dimensional drawings on request.

• Chemical resistance information provided by Dow Chemical (Vinyl Ester Resin) and Qua Corr (Furan).

• End user to make final determination on suitability of chemical resistance

• Consult a chemical resistance guide or handbook for additional material compatibility information.

• For Flow Data see corresponding model literature.

VALVES & TANK EQUIPMENT // PAGE 92 www.grothcorp.com

STEAM JACKETED VALVES

• Prevents freezing and product buildup

• Designed for easy maintenance

• Available in Series 1200A, 1300A, 2000A and others

STEAM JACKETED VALVES

Steam jacketed valves are designed for use on tanks containing liquids whose vapors may crystallize at normal temperature. They afford protection against valve clogging. Uniform heating of the housing and valves assures the valve will remain in operating condition. Available on model numbers 1200A, 1220A, 1260A, 1300A, 1360A, 2000A, 2300A and 2400A.

SPECIAL FEATURES

Valve covers can be easily removed for convenient inspection and maintenance. Steam heated valves are suitable for steam circulation up to 100 psig saturated.

VALVES & TANK EQUIPMENT // PAGE 93 www.grothcorp.com

TECHNICAL SECTION // TPD

1200ASeriesValves

Due to the modular construction of Groth pressure/vacuum relief valves, internal components can be utilized which permit settings as low as 0.5 oz/in2 and as high as 15 psig. Similarly, vacuum relief valves may withstand tank working pressures as high as 100 psig (special construction required).

However, the light weight formed pallets required for low vacuum settings may not withstand the high working pressures, and the heavier machined plate pallets required for high working pressures may not permit low vacuum settings.

The following table defines the minimum vacuum setting as a function of the maximum tank working pressures for Models 1201B, 1221B, 1300A and 1360A valves based on the dead weight of each pallet assembly.

VALVES & TANK EQUIPMENT // PAGE 94 www.grothcorp.com
STANDARDSETTINGSANDMAXIMUMTANKWORKINGPRESSURE
MinimumVacuumSettingsversusMaximumTankWorkingPressure SpunPalletStampedPalletMachinedPallet Size (inches) Minimum* Vacuum Setting [oz/in2] Maximum Tank Pressure [psig] Minimum Vacuum Setting [oz/in2] Maximum Tank Pressure [psig] Minimum Vacuum Setting [oz/in2] Maximum Tank Pressure [psig]◊ 2"0.50151.2251.930 3"0.50151.2251.830 4"0.50121.0201.530 6"0.50121.3202.430 8"0.5051.3152.230 10"0.5051.2153.230 12"0.5051.1153.130 *Some sizes require non-ferrous components to achieve 0.5 oz/in2 setting. ◊Consult factory for MAWP >30 psig.
VALVES & TANK EQUIPMENT // PAGE 95 www.grothcorp.com
NOTES

NEW CASTLE

2680 New Butler Rd. New Castle, PA 16101

Tel: 724-368-8725

Email: sales@portersvillerd.com

RICHMOND

700 Southlake Blvd. North Chesterfield VA 23236

Tel: 804-593-2384

Email: sales@portersvillerd.com

www.portersvilleprd.com

TALLMADGE

143 S.Thomas Rd. Tallmadge, OH 44278

Tel: 330-253-4800

Email: sales@portersvilleprd.com

KINGSPORT

1551 Shipley Ferry Road Blountville, TN 37617

Tel: 423.482.0496

Email: sales@portersvillerd.com

SIGNAL HILL

1500 E. Burnett St. Signal Hill, CA 90755

Tel: 562-424-8108

Email: Sales@BV-BM.com

www.bv-bm.com

SOUTH POINT

403 Technology Dr South Point, OH 45680

Tel: 740-377-0012

Email: sales@portersvilleprd.com

BAKERSFIELD

3800 Fruitvale Avenue Bakersfield, CA 93308

Tel: 661-589-6801

Email: Sales@BV-BM.com

BENICIA

3195 Park Road, Benicia, CA 94510

Tel: 707-590-6688

Email: Sales@BV-BM.com

Groth Corporation, LLC reserves the right to alter the information in this publication without notice. // © 2021 Groth Corporation, LLC Reproduction without written permission is prohibited. LIT1307 // 0321 GROTHCORP.COM