SPECIFICATIONS
2(50)3(76)11(52.7)12(52.7)114.25(362)12.62(321)7.50(178)7(178)5.50(140)16(7)
3(80)4(102)12(57.0)11(48.3)18(457)15.12(384)9(229)8.12(206)6(152)34(16)
4(100)6(152)16(70.3)11(48.3)19.25(489)18.25(464)11(279)9.50(241)6.50(165)49(22)
6(150)8(203)16(70.3)16(70.3)26.50(673)23.75(603)13.5(343)12.75(324)8.50(216)93(42)
8(200)10(254)16(70.3)16(70.3)32.50(826)28.50(724)16(406)15.25(387)10.75(273)137(62)
10(250)12(305)16(70.3)16(70.3)37.75(959)34.50(876)19(483)18(457)12.50(318)186(85) 12(300)14(356)16(70.3)16(70.3)42.75(1086)39.12(994)21(533)20.62(524)15(381)260(118)
12(300)0.5051.1153.130
Inlet Flg◊ In(mm) Outlet Flg◊ In(mm) Max.Set Pressure Weight Loaded oz/in2(gm/cm
Max.Set Vacuum. Weight Loaded oz/in2(gm/cm
) Max. Setting Spring Loaded Min. Setting Weight Loaded A Length In(mm) B Height In(mm) C Width In(mm) D In(mm) E In(mm) Approx. ShipWt. forAI Lbs(kg)
2)
2
PAGE3
C A 15 psig Spring Loaded Pressure (1.05 kg/cm2) 12 psig Spring Loaded Vacuum (0.84 kg/cm2) *0.5 oz/in2 Weight Loaded (2.20 gm/cm2) B D E Minimum Vacuum Settings versus Maximum Tank Working Pressure SpunPalletStampedPalletMachinedPallet Size In(mm) Minimum* Vacuum Setting [oz/in2] Maximum Tank Pressure [psig] Minimum Vacuum Setting [oz/in2] Maximum Tank Pressure [psig] Minimum Vacuum Setting [oz/in2] Maximum Tank Pressure [psig]◊ 2(50)0.50151.2251.930
3(80)0.50151.2251.830 4(100)0.50121.0201.530 6(150)0.50121.3202.430 8(200)0.5051.3152.230 10(250)0.5051.2153.230
0.870.506.8713.325.252.782.6135175 1.000.587.3914.327.156.688.8145188
Flow Capacity Calculation
Flowcapacityvalueslistedabovearebasedonfullopen valvesat100%overpressure.Readtheflowcapacityat 100%overpressuredirectlyfromthetableabove.Use linearsted.Iftheallowableoverpressureislessthan 100%,modifytheflowcapacityusingtheappropriate“C” factorfromthetable.Ifallowableoverpressureismore than100%,consultyourGrothRepresentative.
Calculatethepercentageoverpressurebythefollowing formula.Notethatallpressuresaregaugepressure expressedinthesameunitsofmeasure.
Pf=Flowingpressure
Ps=Setpressure %OP=[(Pf-Ps)/Ps]x100
Calculateflowcapacityatlessthan100%overpressure accordingtothefollowingexample.
Example Flow Capacity Calculation
Example to find “C” factor from table: Read“C”factorfor75%overpressureatintersectionof row70andcolumn5
“C”factorat75%OP=0.87
6”Model1220A1.ReadflowcapacityatsetpressurefromtableFlow=112,000SCFH
4InWCsetpressure[Ps]2.Calculateoverpressure%OP=[(7-4)/4]x100=75%
7InWCflowingpressure[Pf]3.Read“C”factorfromtable“C”=0.87
4.CalculateflowcapacityFlow=0.87x112,000=97,440SCFH “C”FactorTable %OP0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00 AirFlowCapacityat100%Overpressure(DoubleSetPressure)
PAGE4 MODEL1220A/1222BPRESSURERELIEFCAPACITY
1000StandardCubicFeetperHourat60°F SetPressure(P
)SizeIn(mm)
s
InWCoz/in22(50)3(80)4(100)6(150)8(200)10(250)12(300)
1.731.009.7118.835.674.3117190247 2.001.1610.420.238.279.8125205265 2.601.5011.923.043.590.8143233302 3.001.7312.824.746.897.5153250324 3.462.0013.726.650.2105164268348 4.002.3114.728.653.9112177288374
8.004.6220.740.475.8157248404525 10.05.7823.145.184.6175276450584 12.06.9325.249.492.4191301491638 15.08.6628.155.2103211335546709 20.011.632.263.7118241383625811 25.014.435.871.2131267424692898
6.003.4718.035.065.9137215351456
30.017.339.077.9143289460751975
222.160.190.370.711.482.333.804.93 504.900.290.561.072.233.505.727.42 757.350.360.691.312.724.286.999.10
Flow Capacity Calculation
Flowcapacityvalueslistedabovearebasedonfullopen valvesat100%overpressure.Readtheflowcapacityat 100%overpressuredirectlyfromthetableabove.Use linearinterpolationifthesetpressureisnotlisted.If theallowableoverpressureislessthan100%,modify theflowcapacityusingtheappropriate“C”factorfrom thetable.Ifallowableoverpressureismorethan100%, consultyourGrothRepresentative.
Calculatethepercentageoverpressurebythefollowing formula.Notethatallpressuresaregaugepressure expressedinthesameunitsofmeasure.
Pf=Flowingpressure
Ps=Setpressure
%OP=[(Pf-Ps)/Ps]x100
Calculateflowcapacityatlessthan100%overpressure accordingtothefollowingexample.
Example Flow Capacity Calculation
Example to find “C” factor from table:
Read“C”factorfor75%overpressureatintersectionof row70andcolumn5
“C”factorat75%OP=0.87
6”Model1220A1.ReadflowcapacityatsetpressurefromtableFlow=3,140NCMH
100mmWCSetPressure[Ps]2.Calculateoverpressure%OP=[(175-100)/100]x100=75% 175mmWCFlowingPressure[Pf]3.Read“C”factorfromtable“C”=0.87
4.CalculateflowcapacityFlow=0.87x3,140=2,732NCMH
PAGE5 MODEL1220A/1222BPRESSURERELIEFCAPACITY
%OP0123456789
1000NormalCubicMetersperHourat0°C SetPressure(P
)SizeIn(mm) mmWCmb2(50)3(80)4(100)6(150)8(200)10(250)12(300)
“C”FactorTable
100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00 AirFlowCapacityat100%Overpressure(DoubleSetPressure)
s
1009.800.410.801.513.144.938.0510.4 12512.30.460.891.683.505.518.9911.7 15014.70.500.981.843.826.029.8012.7 17517.20.541.061.994.126.4910.613.7 20019.60.581.132.124.396.9211.314.7 22522.10.611.202.254.657.3312.015.5 25024.50.651.262.364.897.7112.616.3 27527.00.681.322.485.118.0713.217.1 30029.40.701.382.585.338.4213.717.8 37536.80.781.542.885.919.4015.319.8 50049.00.901.783.306.7510.717.522.7 62561.31.001.993.677.4611.919.425.1 75073.51.092.183.998.0712.921.027.3
Flow Capacity Calculation
Flowcapacityvalueslistedabovearebasedonfullopen valvesat100%over-vacuum.Readtheflowcapacityat 100%over-vacuumdirectlyfromthetableabove.Use linearinterpolationifthesetvacuumisnotlisted.If theallowableover-vacuumislessthan100%,modify theflowcapacityusingtheappropriate“C”factorfrom thetable.Ifallowableover-vacuumismorethan100%, consultyourGrothRepresentative.
Calculatethepercentageover-vacuumbythefollowing formula.Notethatallpressuresaregaugepressure expressedinthesameunitsofmeasure.
Pf=Flowingpressure
Ps=Setpressure
%OV=[(Pf-Ps)/Ps]x100
Calculateflowcapacityatlessthan100%over-vacuum accordingtothefollowingexample.
Example Flow Capacity Calculation
“C”FactorTable %OV0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58 300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78 600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00
Example to find
6”Model1220A1.ReadflowcapacityatsetvacuumfromtableFlow=74,000SCFH
4InWCSetVacuum[Ps]2.Calculateover-vacuum%OV=[(7-4)/4]x100=75%
7InWCFlowingVacuum[Pf]3.Read“C”factorfromtable“C”=0.87
4.CalculateflowcapacityFlow=0.87x74,000=64,380SCFH
PAGE6 MODEL1220A/1221BVACUUMRELIEFCAPACITY
SetVacuum(P
2.001.167.1215.624.252.691.6138195 2.601.508.1017.727.659.8104157222 3.001.738.7019.029.664.2112169238 3.462.009.3320.431.868.9120181256 4.002.3110.021.934.174.0129194274 6.003.4712.226.741.590.1157237334 8.004.6214.030.647.7103180272384 10.05.7815.634.053.0115200302427 12.06.9317.037.157.8125218329465 15.08.6618.841.164.0139242365516 20.011.621.446.872.9158276415587 25.014.423.651.580.3174304457646 30.017.325.455.686.6188327493697
AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000StandardCubicFeetperHourat60°F
s)SizeIn(mm) InWCoz/in22(50)3(80)4(100)6(150)8(200)10(250)12(300) 0.870.504.7010.316.034.760.591.1129 1.000.585.0511.017.237.365.097.9138 1.731.006.6314.522.649.085.3129182
“C”factorat75%OV=0.87
“C” factor from table: Read“C”factorfor75%over-vacuumatintersectionof row70andcolumn5
222.160.130.290.450.981.712.583.65 504.900.200.440.681.482.583.885.48 757.350.240.530.831.813.154.746.70
Flow Capacity Calculation
Flowcapacityvalueslistedabovearebasedonfullopen valvesat100%over-vacuum.Readtheflowcapacityat 100%over-vacuumdirectlyfromthetableabove.Use linearinterpolationifthesetvacuumisnotlisted.If theallowableover-vacuumislessthan100%,modify theflowcapacityusingtheappropriate“C”factorfrom thetable.Ifallowableover-vacuumismorethan100%, consultyourGrothRepresentative.
Calculatethepercentageover-vacuumbythefollowing formula.Notethatallpressuresaregaugepressure expressedinthesameunitsofmeasure.
Pf=Flowingpressure
Ps=Setpressure %OV=[(Pf-Ps)/Ps]x100
Calculateflowcapacityatlessthan100%over-vacuum accordingtothefollowingexample.
Example Flow Capacity Calculation
Example to find “C” factor from table: Read“C”factorfor75%over-vacuumatintersectionof row70andcolumn5 “C”factorat75%OV=0.87
6”Model1220A1.ReadflowcapacityatsetvacuumfromtableFlow=2,080NCMH 100mmWCSetVacuum[Ps]2.Calculateover-vacuum%OV=[(175-100)/100]x100=75% 175mmWCFlowingVacuum[Pf]3.Read“C”factorfromtable“C”=0.87
4.CalculateflowcapacityFlow=0.87x2,080=1,810NCMH
PAGE7 MODEL1220A/1221BVACUUMRELIEFCAPACITY “C”FactorTable
300.590.590.600.610.610.620.630.640.640.65 400.660.660.670.680.680.690.700.700.710.72 500.720.730.730.740.750.750.760.770.770.78
1000NormalCubicMetersperHourat0°C SetVacuum(P
mmWCmb2(50)3(80)4(100)6(150)8(200)10(250)12(300)
1009.800.280.620.962.083.625.467.72 12512.30.310.691.072.324.046.098.60 15014.70.340.751.172.534.416.659.40 17517.20.370.811.262.734.757.1610.1 20019.60.390.861.342.915.077.6410.8 22522.10.420.911.423.085.368.0811.4 25024.50.440.961.493.235.648.4912.0 27527.00.461.001.563.385.908.8812.6 30029.40.481.041.623.526.149.2513.1 37536.80.531.161.803.916.8110.314.5 50049.00.601.322.054.457.7511.716.5 62561.30.661.452.264.908.5412.918.2 75073.50.721.572.445.299.2213.919.6
%OV0123456789 100.420.430.440.450.460.460.470.480.490.50 200.510.520.520.530.540.550.560.560.570.58
600.780.790.800.800.810.810.820.820.830.84 700.840.850.850.860.860.870.880.880.890.89 800.900.900.910.910.920.920.930.930.940.94 900.950.950.960.960.970.970.980.990.991.00 AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum)
s)SizeIn(mm)
Flow Capacity Calculation
Flowcapacityvalueslistedabovearebasedonfullopen valvesat100%overpressure.Readtheflowcapacityat 100%overpressuredirectlyfromthetableabove.Use linearinterpolationifthesetpressureisnotlisted.If theallowableoverpressureislessthan100%,modify theflowcapacityusingtheappropriate“C”factorfrom thetable.Ifallowableoverpressureismorethan100%, consultyourGrothRepresentative.
Calculatethepercentageoverpressurebythefollowing formula.Notethatallpressuresaregaugepressure expressedinthesameunitsofmeasure.
Pf=Flowingpressure
Ps=Setpressure %OP=[(Pf-Ps)/Ps]x100
Calculateflowcapacityatlessthan100%overpressure accordingtothefollowingexample.
Example Flow Capacity Calculation
Example to find “C” factor from table: Read“C”factorfor75%overpressureatintersectionof row70andcolumn5 “C”factorat75%OP=0.83
6”Model1221B1.ReadflowcapacityatsetpressurefromtableFlow=448,000SCFH 4psigSetPressure[Ps]2.Calculateoverpressure%OP=[(7-4)/4]x100=75% 7psigFlowingPressure[Pf]3.Read“C”factorfromtable“C”=0.83
4.CalculateflowcapacityFlow=0.83x448,000=371,840SCFH
PAGE8 MODEL1221B/1223BPRESSURERELIEFCAPACITY “C”FactorTable
200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00
1000StandardCubicFeetperHourat60°F SetPressure
SizeIn(mm)
%OP0123456789 10•••ConsultFactory•••
AirFlowCapacityat100%Overpressure(DoubleSetPressure)
(Ps)
6.0073.714425056893214311997 7.0080.4158274622102215682188 8.0086.7171297674110716992371 9.0092.8184319724118918252546 10.098.6196340772126719452714 11.0104208360818134320622877 12.0110219380863141721763036 13.0115231400907148922863189 14.0120241418949155923933339 15.0125252437991162724983486
psig2(50)3(80)4(100)6(150)8(200)10(250)12(300) 1.0028.053.492.5210345529739 2.0040.377.41343045007671070 3.0050.296.91683816259601340 4.0058.811419844873611301577 5.0066.513022551083812861794
AirFlowCapacityat100%Overpressure(DoubleSetPressure)
barg2(50)3(80)4(100)6(150)8(200)10(250)12(300) 0.070.821.572.726.1610.115.521.7 0.100.991.893.287.4512.218.826.2 0.151.232.364.099.2815.223.432.6 0.201.432.764.8010.917.927.438.3 0.251.623.145.4412.320.331.143.4 0.301.793.486.0413.722.534.548.2 0.351.953.816.6115.024.637.852.7 0.402.104.127.1416.226.640.957.0 0.452.254.417.6617.428.543.861.1 0.502.394.708.1618.530.446.665.1 0.552.524.988.6419.632.249.468.9 0.602.655.259.1020.633.952.172.6 0.702.895.7610.022.737.257.279.7
Flow Capacity Calculation
Flowcapacityvalueslistedabovearebasedonfullopen valvesat100%overpressure.Readtheflowcapacityat 100%overpressuredirectlyfromthetableabove.Use linearinterpolationifthesetpressureisnotlisted.If theallowableoverpressureislessthan100%,modify theflowcapacityusingtheappropriate“C”factorfrom thetable.Ifallowableoverpressureismorethan100%, consultyourGrothRepresentative.
Calculatethepercentageoverpressurebythefollowing formula.Notethatallpressuresaregaugepressure expressedinthesameunitsofmeasure.
Pf=Flowingpressure
Ps=Setpressure %OP=[(Pf-Ps)/Ps]x100
Calculateflowcapacityatlessthan100%overpressure accordingtothefollowingexample.
Example Flow Capacity Calculation
“C”FactorTable %OP0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00
Example to find “C” factor from table: Read“C”factorfor75%overpressureatintersectionof row70andcolumn5
“C”factorat75%OP=0.83
6”Model1221B1.ReadflowcapacityatsetpressurefromtableFlow=16,200NCMH 0.4bargSetPressure[Ps]2.Calculateoverpressure%OP=[(0.7-0.4)/0.4]x100=75% 0.7bargFlowingPressure[Pf]3.Read“C”factorfromtable“C”=0.83
4.CalculateflowcapacityFlow=0.83x16,200=13,446NCMH
PAGE9 MODEL1221B/1223BPRESSURERELIEFCAPACITY
1000NormalCubicMetersperHourat0°C SetPressure (Ps) SizeIn(mm)
0.803.136.2510.824.640.462.186.5 0.903.356.7211.726.543.566.793.1 1.003.567.1812.528.346.471.299.4
psig2(50)3(80)4(100)6(150)8(200)10(250)12(300) 1.0013.830.552.9120197302422 1.1014.531.955.4126206316442 1.2015.133.257.7131215330460 1.3015.734.559.9136223342478
Flow Capacity Calculation
Flowcapacityvalueslistedabovearebasedonfullopen valvesat100%over-vacuum.Readtheflowcapacityat 100%over-vacuumdirectlyfromthetableabove.Use linearinterpolationifthesetpressureisnotlisted.If theallowableover-vacuumislessthan100%,modify theflowcapacityusingtheappropriate“C”factorfrom thetable.Ifallowableover-vacuumismorethan100%, consultyourGrothRepresentative.
Calculatethepercentageover-vacuumbythefollowing formula.Notethatallpressuresaregaugepressure expressedinthesameunitsofmeasure.
Pf=Flowingpressure
Ps=Setpressure
%OV=[(Pf-Ps)/Ps]x100
Calculateflowcapacityatlessthan100%over-vacuum accordingtothefollowingexample.
Example Flow Capacity Calculation
factor from table: Read“C”factorfor75%over-vacuumatintersectionof row70andcolumn5
6”Model1222B1.ReadflowcapacityatsetvacuumfromtableFlow=166,000SCFH 2psigSetVacuum[Ps]2.Calculateover-vacuum%OV=[(3.50-2.0)/2.0]x100=75% 3.5psigFlowingVacuum[Pf]3.Read“C”factorfromtable“C”=0.83
4.CalculateflowcapacityFlow=0.83x166,000=137,780SCFH
PAGE10 MODEL1222B/1223BVACUUMRELIEFCAPACITY “C”FactorTable %OV0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00
SetVacuum (Ps
SizeIn(mm)
AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000StandardCubicFeetperHourat60°F
)
1.4016.235.762.0141231355495 1.5016.836.964.0145239366511 1.7518.039.668.7156256393548 2.0019.142.073.0166272417582 2.2520.144.376.9174286439613 2.5021.046.380.4183300460641 2.7521.948.283.7190312478667 3.0022.749.986.6197323495691 3.2523.451.489.3203333511713 3.5024.052.891.8208342525732 >3.50CONSULTFACTORYFORVACUUMSETTINGSGREATERTHAN3.5PSIG
“C”
“C”factorat75%OV=0.83
Example to find
AirFlowCapacityat100%Over-Vacuum(DoubleSetVacuum) 1000NormalCubicMetersperHourat0°C
barg2(50)3(80)4(100)6(150)8(200)10(250)12(300) 0.070.410.901.553.525.778.8712.4 0.100.481.061.834.166.8310.514.6 0.110.511.111.924.357.1411.015.3 0.120.531.151.994.537.4311.415.9 0.130.551.202.074.697.7011.816.5 0.140.561.242.144.857.9612.217.1 0.150.581.272.205.008.2112.617.6
0.240.701.542.676.059.9315.221.3
Flow Capacity Calculation
Flowcapacityvalueslistedabovearebasedonfullopen valvesat100%over-vacuum.Readtheflowcapacityat 100%over-vacuumdirectlyfromthetableabove.Use linearinterpolationifthesetpressureisnotlisted.If theallowableover-vacuumislessthan100%,modify theflowcapacityusingtheappropriate“C”factorfrom thetable.Ifallowableover-vacuumismorethan100%, consultyourGrothRepresentative.
Calculatethepercentageover-vacuumbythefollowing formula.Notethatallpressuresaregaugepressure expressedinthesameunitsofmeasure.
Pf=Flowingpressure
Ps=Setpressure
%OV=[(Pf-Ps)/Ps]x100
Calculateflowcapacityatlessthan100%over-vacuum accordingtothefollowingexample.
Example Flow Capacity Calculation
Example to find “C” factor from table:
Read“C”factorfor72%over-vacuumatintersectionof row40andcolumn2
“C”factorat42%OV=0.55
6”Model1222B1.Readflowcapacityatsetvacuumfrom table Flow=4,530NCMH
0.12bargSetVacuum[Ps]2.Calculateover-vacuum%OV=[(0.17-0.12)/0.12]x100= 42%
0.17bargFlowingVacuum [Pf]
3.Read“C”factorfromtable“C”=0.55
4.CalculateflowcapacityFlow=0.55x4,530=2,491NCMH
PAGE11 MODEL1222B/1223BVACUUMRELIEFCAPACITY
“C”FactorTable %OP0123456789 10•••ConsultFactory••• 200.270.290.300.320.330.350.360.380.390.40 300.420.430.440.450.470.480.490.500.510.52 400.530.540.550.560.570.580.590.600.610.62 500.630.640.650.660.670.670.680.690.700.71 600.720.720.730.740.750.760.760.770.780.79 700.800.800.810.820.820.830.840.850.850.86 800.870.870.880.890.900.900.910.920.920.93 900.940.940.950.960.960.970.970.980.991.00
SetVacuum (Ps
) SizeIn(mm)
>0.24CONSULTFACTORYFORVACUUMSETTINGSGREATERTHAN0.24BARG
0.160.601.312.275.148.4413.018.1 0.170.611.352.335.288.6613.318.6 0.180.631.382.385.418.8813.619.0 0.190.641.412.445.539.0813.919.4 0.200.661.442.495.659.2714.219.8 0.220.681.492.585.869.6214.820.6
NEW CASTLE
2680 New Butler Rd. New Castle, PA 16101
Tel: 724-368-8725
Email: sales@portersvillerd.com
RICHMOND
700 Southlake Blvd. North Chesterfield VA 23236
Tel: 804-593-2384
Email: sales@portersvillerd.com
www.portersvilleprd.com
TALLMADGE
143 S.Thomas Rd. Tallmadge, OH 44278
Tel: 330-253-4800
Email: sales@portersvilleprd.com
KINGSPORT
1551 Shipley Ferry Road Blountville, TN 37617
Tel: 423.482.0496
Email: sales@portersvillerd.com
SIGNAL HILL
1500 E. Burnett St. Signal Hill, CA 90755
Tel: 562-424-8108
Email: Sales@BV-BM.com
www.bv-bm.com
SOUTH POINT
403 Technology Dr South Point, OH 45680
Tel: 740-377-0012
Email: sales@portersvilleprd.com
BAKERSFIELD
3800 Fruitvale Avenue Bakersfield, CA 93308
Tel: 661-589-6801
Email: Sales@BV-BM.com
BENICIA
3195 Park Road, Benicia, CA 94510
Tel: 707-590-6688
Email: Sales@BV-BM.com
GrothCorporation,LLCreservestherighttoaltertheinformationinthispublicationwithoutnotice.//©2021GrothCorporation,LLC Reproductionwithoutwrittenpermissionisprohibited.LIT1307//0321 GROTHCORP.COM