MULTI-STAGE SURGE PROTECTION
SurGe
Installation and Operating Instruction ACDC Surge Protectors Type - PI (780; 7100; 7125; 7200) 3/3 - M - GS EIGHT (8) STAGES SERIES PROTECTOR 1/1 & 3/3 Single Phase & Three Phase CLASS I+II+III Hard Wire Installation - Modular System Cascade bi-directional EMI-RFI filtering of phase (L) and neutral (N) wire Indication for bed grounding, remote alarm CLASS
LPZ
I+II+III
0 1 2 3
IP
20
home
telecom
IT center
industry
SurGe Protection
Type - PI (780; 7100; 7125; 7200) 3/3 - M - GS
Empowered by Innovation
www.acdc-dcac.eu
Mounting of Protectors
SurGe
MULTI-STAGE SURGE PROTECTION
Mounting of ACDC Surge Protectors ACDC Surge Protectors Type-PI 3/3 - M - Green Series have to be installed at ENTRY POINT before the Main Power Distribution Boards (MDB) or internal Sub Distribution Boards (SDB) or right in front of the input power to the device that should be protected . The ACDC Surge Protector could be install in series or parallel configuration depending of total load per phase (>100A<). - If the load per phase is <100A the ACDC Surge Protector have to be install ed in SERIES configuration. - If the load per phase is >100A the ACDC Surge Protector must be installed in PARALLEL configuration. ! If the the load per phase is <100A, our RECOMMENDATION is to install the surge protector in SERIES configuration because only in this state your electrical devices will be fully protected. ! If the total load per phase is >100A and ACDC Surge Protector is installed in PARALLEL configuration our RECOMMENDATION is to install another ACDC Surge Protector in SERIES configuration ( before Sub Distribution Board), downstream power grid where the load per phase drops bellow 100A, ! CAUTION Only in SERIES configuration all eight (8) protection stages are in function.
Condition for Installations: - provides adequate electrical and safety protection - Prevents the ingress of moisture and water - Allows operating diagnostic status to be inspected . Mounting: ACDC Surge Protectors are designed to fixed to the wall with screws.
.
Terminal and Wire size: Each terminal is designed to accept wire sizes from 4mm2 to 25mm2 solid or stranded conductor. The wire insulation should be stripped back 8mm ! DANGER THIS UNIT SHOULD BE INSTALLED AND SERVICED ONLY BY QUALIFIED PERSONNEL.
Before installing the ACDC Surge Protector, AC power must be OFF. : During the installation please check: 1. The voltage of the ACDC Surge Protector matches actual system voltage. 2. All conductors are in accordance with the appropriate installation drawings. ! CAUTION CORRECT INSTALLATION - THE LIGHTS GREEN AND YELLOW ARE LIT ! CAUTION TROUBLESHOOTING - IF THE RED LED IS BLINKING THE GROUND WIRE IS NOT CONNECTED OR THE GROUND OF THE
POWER GRID SYSTEM IN NOT WELL PERFORMED
acdc-dcac@acdc-dcac.eu
New materials, New design, New approach to Surge Protection Industry
MULTI-STAGE SURGE PROTECTION
SurGe
Installation Instruction
Installation Instruction for Type - PI (780; 7100; 7125; 7200) 3/3 - M - GS The model could be installed in series configuration with or without neutral (N) filtering or in parallel configuration
- SERIES - Three Phase Installation with phase (L) and neutral (N) filtering
Installation Instruction
Ground Rail
L1IN L1OUT
L2IN L2OUT
Ground Rail
L3IN L3OUT
L1
Fuse
L2
Fuse
L3
Fuse
N PE
L
LIN
PARALLEL
L LOUT LIN
L
PARALLEL
PARALLEL
L LOUT LIN MULTI-STAGE
PROTECTION
SURGE
Type - PI Blue Series Load Rating: 230VAC @ 100A
PARALLEL
L LOUT
Type - PI Blue Series Load Rating: 230VAC @ 100A
GND II IV,VI
L LOUT LIN
PARALLEL
L
PARALLEL
L LOUT LIN
PARALLEL
L
PARALLEL
L LOUT
PARALLEL
SURGE
Green
MULTI-STAGE
PROTECTION
GND II IV,VI
GND II IV,VI
Series
CORRECT
CORRECT
FAULT
CLASS I+II+III
CORRECT
CORRECT
FAULT
EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
CLASS I+II+III
EIGHT PROTECTION STAGES
mark
Green
GND II IV,VI
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
CORRECT
N
Type - PI Green Series Load Rating: 230VAC @ 100A
EIGHT PROTECTION STAGES
mark
NIN NOUT NOUT GND NIN NOUT NOUT GND NIN NOUT NOUT GND
SURGE
ACDC SURGE PROTECTOR
Green
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
CORRECT
mark
GND II IV,VI
FAULT
CLASS I+II+III
CORRECT
CORRECT
mark
FAULT
CLASS I+II+III
CORRECT
CORRECT
FAULT
CLASS I+II+III
CORRECT
EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
CORRECT
EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
FAULT
CLASS I+II+III
EIGHT PROTECTION STAGES
Type - PI Green Series Load Rating: 230VAC @ 100A
PROTECTION
Series
ACDC SURGE PROTECTOR
Green
Type - PI Green Series Load Rating: 230VAC @ 100A
MULTI-STAGE
SURGE
Series
ACDC SURGE PROTECTOR
Type - PI Blue Series Load Rating: 230VAC @ 100A
GND II IV,VI
MULTI-STAGE
PROTECTION
SURGE
Series
ACDC SURGE PROTECTOR
Green
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
mark
L
PARALLEL
MULTI-STAGE
PROTECTION
Series
ACDC SURGE PROTECTOR
Green
LIN
PARALLEL
SURGE
Series
ACDC SURGE PROTECTOR
L
PARALLEL
MULTI-STAGE
PROTECTION
mark
NIN NOUT NOUT GND NIN NOUT NOUT GND NIN NOUT NOUT GND
N
- SERIES - Three Phase Installation with phase (L) and without neutral (N) filtering
Installation Instruction
Ground Rail
L1IN L1OUT
L2IN L2OUT
Ground Rail
L3IN L3OUT
L1
Fuse
L2
Fuse
L3
Fuse
N PE
LIN
L
PARALLEL
L LOUT LIN
PARALLEL
L
PARALLEL
L LOUT LIN
PARALLEL
MULTI-STAGE
MULTI-STAGE
PROTECTION
PROTECTION
Series
Series
SURGE
ACDC SURGE PROTECTOR
Type - PI Blue Series Load Rating: 230VAC @ 100A
L
PARALLEL
L LOUT
ACDC SURGE PROTECTOR
Green
Type - PI Blue Series Load Rating: 230VAC @ 100A
GND II IV,VI
L
PARALLEL
L LOUT LIN
PARALLEL
L
PARALLEL
L LOUT LIN
PARALLEL
L
PARALLEL
L LOUT
PARALLEL
MULTI-STAGE
SURGE
ACDC SURGE PROTECTOR
Green
PROTECTION
MULTI-STAGE
MULTI-STAGE
Series
PROTECTION
PROTECTION
Series
Series
SURGE
Green
ACDC SURGE PROTECTOR
Type - PI Blue Series Load Rating: 230VAC @ 100A
GND II IV,VI
GND II IV,VI
Type - PI Green Series Load Rating: 230VAC @ 100A
ACDC SURGE PROTECTOR
Green
Type - PI Green Series Load Rating: 230VAC @ 100A
Series
CORRECT
CORRECT
FAULT
CLASS I+II+III
CORRECT
CORRECT
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
FAULT
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
CLASS I+II+III
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
mark
Green
GND II IV,VI
EIGHT PROTECTION STAGES
CORRECT
N
Type - PI Green Series Load Rating: 230VAC @ 100A
EIGHT PROTECTION STAGES
mark
NIN NOUT NOUT GND NIN NOUT NOUT GND NIN NOUT NOUT GND
SURGE
PROTECTION
ACDC SURGE PROTECTOR
Green
GND II IV,VI
EIGHT PROTECTION STAGES CORRECT
mark
MULTI-STAGE
SURGE
GND II IV,VI
FAULT
CLASS I+II+III
CORRECT
CORRECT
mark
FAULT
CLASS I+II+III
CORRECT
CORRECT
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
FAULT
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
CLASS I+II+III
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
CORRECT
EIGHT PROTECTION STAGES
CORRECT
EIGHT PROTECTION STAGES FAULT
CLASS I+II+III
EIGHT PROTECTION STAGES
mark
LIN
PARALLEL
SURGE
mark
NIN NOUT NOUT GND NIN NOUT NOUT GND NIN NOUT NOUT GND
N
- PARALLEL - Three Phase Installation (for current > 100A per phase) Ground Rail
Installation Instruction L1
L2
Ground Rail
L3
L1
C1
Fuse
L2
C2
Fuse
L3
C3
Fuse
N PE
LIN
L
PARALLEL
L LOUT LIN
PARALLEL
L
PARALLEL
L LOUT LIN
PARALLEL
MULTI-STAGE
L LOUT SURGE
PROTECTION
Series
ACDC SURGE PROTECTOR
Type - PI Blue Series Load Rating: 230VAC @ 100A
Type - PI Blue Series Load Rating: 230VAC @ 100A
PARALLEL
L LOUT LIN
C3'
PARALLEL
L
PARALLEL
L LOUT LIN
PARALLEL
MULTI-STAGE
MULTI-STAGE
PROTECTION
PROTECTION
SURGE
L LOUT
PARALLEL
Type - PI Green Series Load Rating: 230VAC @ 100A
MULTI-STAGE
GND II IV,VI
SURGE
PROTECTION
Series
ACDC SURGE PROTECTOR
Green
Type - PI Green Series Load Rating: 230VAC @ 100A
GND II IV,VI
CORRECT
CORRECT
FAULT
CORRECT
CORRECT
CLASS I+II+III
FAULT
CORRECT
CORRECT
EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
CLASS I+II+III
EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
mark
Green
GND II IV,VI
EIGHT PROTECTION STAGES
mark
Series
ACDC SURGE PROTECTOR
Green
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
FAULT
CLASS I+II+III
CORRECT
CORRECT
mark
NIN NOUT NOUT GND NIN NOUT NOUT GND NIN NOUT NOUT GND
Type - PI Green Series Load Rating: 230VAC @ 100A
SURGE
Series
ACDC SURGE PROTECTOR FAULT
CORRECT
CORRECT
CLASS I+II+III
FAULT
CORRECT
CORRECT
CLASS I+II+III
EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
FAULT
CLASS I+II+III
EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
L
PARALLEL
Green
GND II IV,VI
EIGHT PROTECTION STAGES
mark
C2'
L
Series
ACDC SURGE PROTECTOR
Green
GND II IV,VI
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
mark
LIN
MULTI-STAGE
PROTECTION
Series
Green
GND II IV,VI
C1'
PARALLEL
SURGE
PROTECTION
ACDC SURGE PROTECTOR
Type - PI Blue Series Load Rating: 230VAC @ 100A
L
PARALLEL
MULTI-STAGE
SURGE
mark
NIN NOUT NOUT GND NIN NOUT NOUT GND NIN NOUT NOUT GND
N
Integrated Multi-Stage Protection
N
www.acdc-dcac.eu
Installation Instruction
SurGe
MULTI-STAGE SURGE PROTECTION
Installation Instruction for Type - PI (780; 7100; 7125; 7200) 3/3 - M - GS The Surge Protectors are installed in Metal Distribution board with degree of protection IP54
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
CAUTION This equipment must only be installed and serviced by qualified electrical . personnel. Tu r n o f f a l l p o w e r supplying this equipment before working on or inside equipment. . During installation into an electrical system, it must not be energized until completely inspection. Failure to follow these instructions will result in serious injury.
acdc-dcac@acdc-dcac.eu
New materials, New design, New approach to Surge Protection Industry
MULTI-STAGE SURGE PROTECTION
Operation
SurGe
Diagnostic System
Operation Diagnostic System Normal:
Red
Yellow
Green Led Indication for correct stage no. 2,4 and 6. The stages no. 1,3 and 7 (high garde bi-directional filtering) are always in function along with ultimate (5-th) protection stage.
Continuous yellow and green
Fault: Led Indication for correct stage no. 4,6 and un correct no 2. The stages no. 1,3 and 7 (bi-directional filtering) are always in function along with ultimate (5-th) protection stage.
Continuous green
Fault: Led Indication for bed grounding (Low impedance equipotential ground is not provided)
Blinking red
Fault: Continuous red
Only stages 1,3 and 7 are still in function along with ultimate (5-th) protection stage.
Connections for common contact alarm
LIN
L LOUT LIN
L
PARALLEL
PARALLEL
L
PARALLEL
L LOUT LIN
PARALLEL
L LOUT
PARALLEL
MULTI-STAGE
MULTI-STAGE
MULTI-STAGE
PROTECTION
PROTECTION
PROTECTION
Series
Series
SURGE
ACDC SURGE PROTECTOR
Type - PI Green Series Load Rating: 230VAC @ 100A
L
PARALLEL
SURGE
ACDC SURGE PROTECTOR
Green
Type - PI Green Series Load Rating: 230VAC @ 100A
GND II IV,VI
SURGE
Series
ACDC SURGE PROTECTOR
Green
Type - PI Green Series Load Rating: 230VAC @ 100A
GND II IV,VI
GND II IV,VI
CORRECT
CORRECT
FAULT
CORRECT
CLASS I+II+III
CORRECT
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) mark 125kA (8x20μs); 20kA (10/350μs)
FAULT
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) mark 125kA (8x20μs); 20kA (10/350μs)
CLASS I+II+III
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) mark 125kA (8x20μs); 20kA (10/350μs)
CORRECT
EIGHT PROTECTION STAGES
CORRECT
EIGHT PROTECTION STAGES FAULT
CLASS I+II+III
EIGHT PROTECTION STAGES
Green
NIN NOUT NOUT GND NIN NOUT NOUT GND NIN NOUT NOUT GND
-
+ 13
Free Contact Alarm Every ACDC Surge Protector Type -PI (740; 780; 7125; 7200) Green Series have free contact alarm as basic option. The alarm is activate in two cases: 1. When some of the protection stages (2, 4 or 6) are damaged or burned and Red Led is ON. Alarm contacts 1-3 are permanently closed. 2. When the ground of the power grid system is not well performed (pour grounding). Alarm contacts1-3 are closing with frequency of 2Hz (0,5s) Red led is blinking. . Free contacts are on the cover of the protector with contact no. 1 and 3. (see picture) . The contact is a optocoupler with maximum value of voltage 70VDC and current of 10mA. In normal condition it is open.
ACDC DCAC Dane Krapcev no.2/1, 1000-Skopje, Macedonia
Phone: 389 2 3216 988; Fax: 389 2 3216 993
-
+ 1
N.C
3
www.acdc-dcac.eu