Installation Instruction Type-PI 3/3-M-GS; ACDC Surge Protectors (http://shop.acdc-dcac.eu/)

Page 1

MULTI-STAGE SURGE PROTECTION

SurGe

Installation and Operating Instruction ACDC Surge Protectors Type - PI (780; 7100; 7125; 7200) 3/3 - M - GS EIGHT (8) STAGES SERIES PROTECTOR 1/1 & 3/3 Single Phase & Three Phase CLASS I+II+III Hard Wire Installation - Modular System Cascade bi-directional EMI-RFI filtering of phase (L) and neutral (N) wire Indication for bed grounding, remote alarm CLASS

LPZ

I+II+III

0 1 2 3

IP

20

home

telecom

IT center

industry

SurGe Protection

Type - PI (780; 7100; 7125; 7200) 3/3 - M - GS

Empowered by Innovation

www.acdc-dcac.eu


Mounting of Protectors

SurGe

MULTI-STAGE SURGE PROTECTION

Mounting of ACDC Surge Protectors ACDC Surge Protectors Type-PI 3/3 - M - Green Series have to be installed at ENTRY POINT before the Main Power Distribution Boards (MDB) or internal Sub Distribution Boards (SDB) or right in front of the input power to the device that should be protected . The ACDC Surge Protector could be install in series or parallel configuration depending of total load per phase (>100A<). - If the load per phase is <100A the ACDC Surge Protector have to be install ed in SERIES configuration. - If the load per phase is >100A the ACDC Surge Protector must be installed in PARALLEL configuration. ! If the the load per phase is <100A, our RECOMMENDATION is to install the surge protector in SERIES configuration because only in this state your electrical devices will be fully protected. ! If the total load per phase is >100A and ACDC Surge Protector is installed in PARALLEL configuration our RECOMMENDATION is to install another ACDC Surge Protector in SERIES configuration ( before Sub Distribution Board), downstream power grid where the load per phase drops bellow 100A, ! CAUTION Only in SERIES configuration all eight (8) protection stages are in function.

Condition for Installations: - provides adequate electrical and safety protection - Prevents the ingress of moisture and water - Allows operating diagnostic status to be inspected . Mounting: ACDC Surge Protectors are designed to fixed to the wall with screws.

.

Terminal and Wire size: Each terminal is designed to accept wire sizes from 4mm2 to 25mm2 solid or stranded conductor. The wire insulation should be stripped back 8mm ! DANGER THIS UNIT SHOULD BE INSTALLED AND SERVICED ONLY BY QUALIFIED PERSONNEL.

Before installing the ACDC Surge Protector, AC power must be OFF. : During the installation please check: 1. The voltage of the ACDC Surge Protector matches actual system voltage. 2. All conductors are in accordance with the appropriate installation drawings. ! CAUTION CORRECT INSTALLATION - THE LIGHTS GREEN AND YELLOW ARE LIT ! CAUTION TROUBLESHOOTING - IF THE RED LED IS BLINKING THE GROUND WIRE IS NOT CONNECTED OR THE GROUND OF THE

POWER GRID SYSTEM IN NOT WELL PERFORMED

acdc-dcac@acdc-dcac.eu

New materials, New design, New approach to Surge Protection Industry


MULTI-STAGE SURGE PROTECTION

SurGe

Installation Instruction

Installation Instruction for Type - PI (780; 7100; 7125; 7200) 3/3 - M - GS The model could be installed in series configuration with or without neutral (N) filtering or in parallel configuration

- SERIES - Three Phase Installation with phase (L) and neutral (N) filtering

Installation Instruction

Ground Rail

L1IN L1OUT

L2IN L2OUT

Ground Rail

L3IN L3OUT

L1

Fuse

L2

Fuse

L3

Fuse

N PE

L

LIN

PARALLEL

L LOUT LIN

L

PARALLEL

PARALLEL

L LOUT LIN MULTI-STAGE

PROTECTION

SURGE

Type - PI Blue Series Load Rating: 230VAC @ 100A

PARALLEL

L LOUT

Type - PI Blue Series Load Rating: 230VAC @ 100A

GND II IV,VI

L LOUT LIN

PARALLEL

L

PARALLEL

L LOUT LIN

PARALLEL

L

PARALLEL

L LOUT

PARALLEL

SURGE

Green

MULTI-STAGE

PROTECTION

GND II IV,VI

GND II IV,VI

Series

CORRECT

CORRECT

FAULT

CLASS I+II+III

CORRECT

CORRECT

FAULT

EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

CLASS I+II+III

EIGHT PROTECTION STAGES

mark

Green

GND II IV,VI

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

CORRECT

N

Type - PI Green Series Load Rating: 230VAC @ 100A

EIGHT PROTECTION STAGES

mark

NIN NOUT NOUT GND NIN NOUT NOUT GND NIN NOUT NOUT GND

SURGE

ACDC SURGE PROTECTOR

Green

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

CORRECT

mark

GND II IV,VI

FAULT

CLASS I+II+III

CORRECT

CORRECT

mark

FAULT

CLASS I+II+III

CORRECT

CORRECT

FAULT

CLASS I+II+III

CORRECT

EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)

CORRECT

EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)

FAULT

CLASS I+II+III

EIGHT PROTECTION STAGES

Type - PI Green Series Load Rating: 230VAC @ 100A

PROTECTION

Series

ACDC SURGE PROTECTOR

Green

Type - PI Green Series Load Rating: 230VAC @ 100A

MULTI-STAGE

SURGE

Series

ACDC SURGE PROTECTOR

Type - PI Blue Series Load Rating: 230VAC @ 100A

GND II IV,VI

MULTI-STAGE

PROTECTION

SURGE

Series

ACDC SURGE PROTECTOR

Green

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)

mark

L

PARALLEL

MULTI-STAGE

PROTECTION

Series

ACDC SURGE PROTECTOR

Green

LIN

PARALLEL

SURGE

Series

ACDC SURGE PROTECTOR

L

PARALLEL

MULTI-STAGE

PROTECTION

mark

NIN NOUT NOUT GND NIN NOUT NOUT GND NIN NOUT NOUT GND

N

- SERIES - Three Phase Installation with phase (L) and without neutral (N) filtering

Installation Instruction

Ground Rail

L1IN L1OUT

L2IN L2OUT

Ground Rail

L3IN L3OUT

L1

Fuse

L2

Fuse

L3

Fuse

N PE

LIN

L

PARALLEL

L LOUT LIN

PARALLEL

L

PARALLEL

L LOUT LIN

PARALLEL

MULTI-STAGE

MULTI-STAGE

PROTECTION

PROTECTION

Series

Series

SURGE

ACDC SURGE PROTECTOR

Type - PI Blue Series Load Rating: 230VAC @ 100A

L

PARALLEL

L LOUT

ACDC SURGE PROTECTOR

Green

Type - PI Blue Series Load Rating: 230VAC @ 100A

GND II IV,VI

L

PARALLEL

L LOUT LIN

PARALLEL

L

PARALLEL

L LOUT LIN

PARALLEL

L

PARALLEL

L LOUT

PARALLEL

MULTI-STAGE

SURGE

ACDC SURGE PROTECTOR

Green

PROTECTION

MULTI-STAGE

MULTI-STAGE

Series

PROTECTION

PROTECTION

Series

Series

SURGE

Green

ACDC SURGE PROTECTOR

Type - PI Blue Series Load Rating: 230VAC @ 100A

GND II IV,VI

GND II IV,VI

Type - PI Green Series Load Rating: 230VAC @ 100A

ACDC SURGE PROTECTOR

Green

Type - PI Green Series Load Rating: 230VAC @ 100A

Series

CORRECT

CORRECT

FAULT

CLASS I+II+III

CORRECT

CORRECT

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

FAULT

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

CLASS I+II+III

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

mark

Green

GND II IV,VI

EIGHT PROTECTION STAGES

CORRECT

N

Type - PI Green Series Load Rating: 230VAC @ 100A

EIGHT PROTECTION STAGES

mark

NIN NOUT NOUT GND NIN NOUT NOUT GND NIN NOUT NOUT GND

SURGE

PROTECTION

ACDC SURGE PROTECTOR

Green

GND II IV,VI

EIGHT PROTECTION STAGES CORRECT

mark

MULTI-STAGE

SURGE

GND II IV,VI

FAULT

CLASS I+II+III

CORRECT

CORRECT

mark

FAULT

CLASS I+II+III

CORRECT

CORRECT

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)

FAULT

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)

CLASS I+II+III

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)

CORRECT

EIGHT PROTECTION STAGES

CORRECT

EIGHT PROTECTION STAGES FAULT

CLASS I+II+III

EIGHT PROTECTION STAGES

mark

LIN

PARALLEL

SURGE

mark

NIN NOUT NOUT GND NIN NOUT NOUT GND NIN NOUT NOUT GND

N

- PARALLEL - Three Phase Installation (for current > 100A per phase) Ground Rail

Installation Instruction L1

L2

Ground Rail

L3

L1

C1

Fuse

L2

C2

Fuse

L3

C3

Fuse

N PE

LIN

L

PARALLEL

L LOUT LIN

PARALLEL

L

PARALLEL

L LOUT LIN

PARALLEL

MULTI-STAGE

L LOUT SURGE

PROTECTION

Series

ACDC SURGE PROTECTOR

Type - PI Blue Series Load Rating: 230VAC @ 100A

Type - PI Blue Series Load Rating: 230VAC @ 100A

PARALLEL

L LOUT LIN

C3'

PARALLEL

L

PARALLEL

L LOUT LIN

PARALLEL

MULTI-STAGE

MULTI-STAGE

PROTECTION

PROTECTION

SURGE

L LOUT

PARALLEL

Type - PI Green Series Load Rating: 230VAC @ 100A

MULTI-STAGE

GND II IV,VI

SURGE

PROTECTION

Series

ACDC SURGE PROTECTOR

Green

Type - PI Green Series Load Rating: 230VAC @ 100A

GND II IV,VI

CORRECT

CORRECT

FAULT

CORRECT

CORRECT

CLASS I+II+III

FAULT

CORRECT

CORRECT

EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

CLASS I+II+III

EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

mark

Green

GND II IV,VI

EIGHT PROTECTION STAGES

mark

Series

ACDC SURGE PROTECTOR

Green

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

FAULT

CLASS I+II+III

CORRECT

CORRECT

mark

NIN NOUT NOUT GND NIN NOUT NOUT GND NIN NOUT NOUT GND

Type - PI Green Series Load Rating: 230VAC @ 100A

SURGE

Series

ACDC SURGE PROTECTOR FAULT

CORRECT

CORRECT

CLASS I+II+III

FAULT

CORRECT

CORRECT

CLASS I+II+III

EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)

FAULT

CLASS I+II+III

EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)

L

PARALLEL

Green

GND II IV,VI

EIGHT PROTECTION STAGES

mark

C2'

L

Series

ACDC SURGE PROTECTOR

Green

GND II IV,VI

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)

mark

LIN

MULTI-STAGE

PROTECTION

Series

Green

GND II IV,VI

C1'

PARALLEL

SURGE

PROTECTION

ACDC SURGE PROTECTOR

Type - PI Blue Series Load Rating: 230VAC @ 100A

L

PARALLEL

MULTI-STAGE

SURGE

mark

NIN NOUT NOUT GND NIN NOUT NOUT GND NIN NOUT NOUT GND

N

Integrated Multi-Stage Protection

N

www.acdc-dcac.eu


Installation Instruction

SurGe

MULTI-STAGE SURGE PROTECTION

Installation Instruction for Type - PI (780; 7100; 7125; 7200) 3/3 - M - GS The Surge Protectors are installed in Metal Distribution board with degree of protection IP54

DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

CAUTION This equipment must only be installed and serviced by qualified electrical . personnel. Tu r n o f f a l l p o w e r supplying this equipment before working on or inside equipment. . During installation into an electrical system, it must not be energized until completely inspection. Failure to follow these instructions will result in serious injury.

acdc-dcac@acdc-dcac.eu

New materials, New design, New approach to Surge Protection Industry


MULTI-STAGE SURGE PROTECTION

Operation

SurGe

Diagnostic System

Operation Diagnostic System Normal:

Red

Yellow

Green Led Indication for correct stage no. 2,4 and 6. The stages no. 1,3 and 7 (high garde bi-directional filtering) are always in function along with ultimate (5-th) protection stage.

Continuous yellow and green

Fault: Led Indication for correct stage no. 4,6 and un correct no 2. The stages no. 1,3 and 7 (bi-directional filtering) are always in function along with ultimate (5-th) protection stage.

Continuous green

Fault: Led Indication for bed grounding (Low impedance equipotential ground is not provided)

Blinking red

Fault: Continuous red

Only stages 1,3 and 7 are still in function along with ultimate (5-th) protection stage.

Connections for common contact alarm

LIN

L LOUT LIN

L

PARALLEL

PARALLEL

L

PARALLEL

L LOUT LIN

PARALLEL

L LOUT

PARALLEL

MULTI-STAGE

MULTI-STAGE

MULTI-STAGE

PROTECTION

PROTECTION

PROTECTION

Series

Series

SURGE

ACDC SURGE PROTECTOR

Type - PI Green Series Load Rating: 230VAC @ 100A

L

PARALLEL

SURGE

ACDC SURGE PROTECTOR

Green

Type - PI Green Series Load Rating: 230VAC @ 100A

GND II IV,VI

SURGE

Series

ACDC SURGE PROTECTOR

Green

Type - PI Green Series Load Rating: 230VAC @ 100A

GND II IV,VI

GND II IV,VI

CORRECT

CORRECT

FAULT

CORRECT

CLASS I+II+III

CORRECT

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) mark 125kA (8x20μs); 20kA (10/350μs)

FAULT

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) mark 125kA (8x20μs); 20kA (10/350μs)

CLASS I+II+III

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) mark 125kA (8x20μs); 20kA (10/350μs)

CORRECT

EIGHT PROTECTION STAGES

CORRECT

EIGHT PROTECTION STAGES FAULT

CLASS I+II+III

EIGHT PROTECTION STAGES

Green

NIN NOUT NOUT GND NIN NOUT NOUT GND NIN NOUT NOUT GND

-

+ 13

Free Contact Alarm Every ACDC Surge Protector Type -PI (740; 780; 7125; 7200) Green Series have free contact alarm as basic option. The alarm is activate in two cases: 1. When some of the protection stages (2, 4 or 6) are damaged or burned and Red Led is ON. Alarm contacts 1-3 are permanently closed. 2. When the ground of the power grid system is not well performed (pour grounding). Alarm contacts1-3 are closing with frequency of 2Hz (0,5s) Red led is blinking. . Free contacts are on the cover of the protector with contact no. 1 and 3. (see picture) . The contact is a optocoupler with maximum value of voltage 70VDC and current of 10mA. In normal condition it is open.

ACDC DCAC Dane Krapcev no.2/1, 1000-Skopje, Macedonia

Phone: 389 2 3216 988; Fax: 389 2 3216 993

-

+ 1

N.C

3

www.acdc-dcac.eu