Q-BE INSERT - INSTALLATION OF THE INSERT
When you choose where to set up your RAIS/attika wood burning stove, you should consider the heat distribution to the other rooms. This will enable you to get the best use out of your stove.
See the manufacturer’s plate on the wood burning stove.
Upon receiving the stove must be inspected for defects.
Installation materials: • 12,5 mm Fermacell panels • calcium silicate panels (eg. 50 mm Super Isol or Skamotec 225) • bricks
Hole measurements (height x width x depth) min. 918 x 399 x 399 mm (int. size).
When the stove is placed against a combustible wall, the back and side walls should be installed with Fermacell 12.5mm or 50mm calcium silicate panels. The stove with the panels should have convection holes above and below.
A fireplace insert shall never be installed too tightly, since steel works in heat.
Convection area must be at least 200 cm2 both above and below the stove (can be distributed).