Industrial UV/IR Flame Detector 2

16591 Features  Unaffected by convection currents, draughts or wind and solar-blind  Tolerant of fumes, vapours, dust and mist  Selectable response speed  Class 1 performance as defined in BS EN54-10:2002 (on the high sensitivity setting)  Solar Blind  Built in auto and manual test

 SIL2 Rated

Description Model 16591 is an UV/IR2 flame detector designed for use where open flaming fires may be expected and responds to the light emitted from flames during combustion. The UV/IR2 flame detector is designed to protect areas where open fires may be expected and detects most flames from hydrocarbon fires with 4.3μm emissions through to invisible fires such as hydrogen. The UV/IR2 Flame Detector is sensitive to flickering, low frequency (1-15Hz) infrared radiation along with ultra-violet emitted by flames during combustion. This detector has a UV sensor and two IR sensors which respond to different wavelengths of both the ultra-violet and the infra-red spectrum. The signals from these sensors are processed by the detector and checked for characteristics of a flame. The simultaneous detection of both the UV and the IR light by the sensors will signal an alarm. False alarms from flickering sunlight, arc welding and lighting are eliminated by a combination of UV and dual IR signal processing techniques. The UV/IR2 flame detector has selectable output options or relay contacts or 4 to 20mA signal as standard.

Specification Ordering codes Operating voltage Alarm Current (selected via by DIL switches) Test Signal Voltage Current Relay Contact Ratings Voltage Power Power Up Time Field of View Range – Class 1* Class 3 Spectral Response Operating temperature range Storage temperature range Maximum humidity Ingress Protection Rating Colour / Case Material Weight (Kg) / Height / Width / Depth (mm)

16591 IFD-MB (Stainless Steel Mounting Bracket) 14 – 30 V dc 9 ~ 28 mA 14 to 30 V dc 1.0 A (max) 50 V dc (max) 30 W (max) (resistive loads only) 2 seconds (max) 90° min. Cone 0.1 m2 n-heptane at 25 m 0.1 m2 n-heptane at 12 m (see EN54: 10 for sensitivity settings) UV (185 – 260 nm) IR (1.0 ~ 2.7 μm) -10 °C to + 55 °C -20 °C to + 65 °C 95% RH - Non condensing (at 40 C) IP65 Blue / Die-Cast Zinc Alloy (ZA12) 2 / 142 / 108 / 82

This product is not suitable for use in Intrinsically Safe areas

Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although every effort has been made to ensure the accuracy of the information contained in this document it is not warranted or represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description.