High Sensitivity Air Sampling Smoke Detector
FIRElink-25 Features Ultra small, low cost aspirating smoke detector for easy and discreet installation High sensitivity provided by laser based forward light scatter for reliable early warning Single sampling pipe up to 50 m in length (still air) False alarms reduced by unique laser sensing technology - able to discriminate against dust RS485 communications built in as standard for networking and remote communications
Description Model FIRElink-25 is designed to provide very high sensitivity smoke detection in a small package. A unique sensing technology ensures that the detector operates at optimum sensitivity for the protected environment, without the need for complex setup. This means the product will configure itself to provide high sensitivity in a computer room or reduced sensitivity in a smoky area. The detector is designed to fit into a Docking Station which accepts all sampling pipes and cables leaving the detector to be fitted during the final commissioning phase. This ensures that the detector is less likely to be damaged during installation. Volt-free Fire 1 and Fault relay outputs are provided for remote monitoring by local fire detection or BMS systems.
Specification Order Code Supply Voltage Current Consumption Relay Contact Rating Operating Temperature Range Operating Humidity Range Measurement range (obs/m) Detection Principle Particle Sensitivity Range Dust Discrimination Principle Maximum Sampling Pipe Length Sampling Pipe Diameter Alarm Levels IP Rating Sampling Pipe Inlets Exhaust Air Pipe Outlets Weight(kg) / Size(mm)
FIRElink-25 21.6 - 26.4 V dc 250 mA @ 24 V dc 500 mA @ 30 V 0 to +38 °C (UL268), -10 to + 60 °C (CEA4022) 0 - 90% non-condensing 0.03% to 25% Full Scale Deflection (FSD) 0.0015% to 25% Sensitivity Resolution Laser light scattering mass detection and particle evaluation 0.003 µ to 10 µ 3D3 Laser Dust Discrimination (LDD) 25 m moving air (>1 ms) / 50 m still air (max) ¾” nominal bore (27 mm O/D) 2 - “FIRE” and “FAULT” (2 additional levels available with optional Relay Card or APIC fitted) IP50 1 1 (on optional Piped Exhaust docking station) 1.7 (with docking station) / H205 x W138 x D84
Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although every effort has been made to ensure the accuracy of the information contained in this document it is not warranted or represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description.
High Sensitivity Air Sampling Smoke Detector FIRElink-100 Features Ultra small, low cost aspirating smoke detector for easy and discreet installation High sensitivity provided by laser based forward light scatter for reliable early warning Two sampling pipes up to 100 m (aggregate) in length (still air) False alarms reduced by unique laser sensing technology - able to discriminate against dust RS485 communications built in as standard for networking and remote communications
Description Model FIRElink-100 is designed to provide very high sensitivity smoke detection in a small package. A unique sensing technology ensures that the detector operates at optimum sensitivity for the protected environment, without the need for complex setup. This means the product will configure itself to provide high sensitivity in a computer room or reduced sensitivity in a smoky area. The detector is designed to fit into a Docking Station which accepts all sampling pipes and cables leaving the detector to be fitted during the final commissioning phase. This ensures that the detector is less likely to be damaged during installation. Volt-free Fire 1 and Fault relay outputs are provided for remote monitoring by local fire detection or BMS systems.
Specification Order Code Supply Voltage Current Consumption Relay Contact Rating Operating Temperature Range Operating Humidity Range Measurement Range (obs/m) Detection Principle Particle Sensitivity Range Dust Discrimination Principle Maximum Sampling Pipe Length Sampling Pipe Diameter Alarm Levels IP Rating Sampling Pipe Inlets Exhaust Air Pipe Outlets Weight(kg) / Size(mm)
FIRElink-100 21.6 - 26.4 VDC 400 mA @ 24 VDC 500 mA @ 30 V 0 to +38 °C (UL268), -10 to + 60 °C (CEA4022) 0 - 90% non-condensing 0.03% to 25% Full Scale Deflection (FSD) 0.0015% to 25% Sensitivity Resolution Laser light scattering mass detection and particle evaluation 0.003 µ to 10 µ 3D3 Laser Dust Discrimination (LDD) 50m ( 2 x 25 m or 1 x 35 m) moving air (>1 ms) OR 100 m (2 x 50 m OR 1 x 65 m) still air (max) ¾” nominal bore (27 mm O/D) (EN54-20 performances) 2 - “FIRE” and “FAULT” (2 additional levels available with optional Relay Card or APIC fitted) IP50 2 1 (on optional Piped Exhaust docking station) 3.8 (with docking station) / H220 x W300 x D85
Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although every effort has been made to ensure the accuracy of the information contained in this document it is not warranted or represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description.
High Sensitivity Air Sampling Smoke Detector with Command Module
FIRElink-400CM Features High sensitivity provided by laser based forward light scatter for reliable early warning Four sampling pipes up to 200 m (aggregate) in length (still air) False alarms reduced by unique dust discrimination RS485 communications for networking and remote communications Command Module allows control over other FIRElink units on network
Description Model FIRElink-400CM is designed to provide very high sensitivity smoke detection using an aspirating technique. A unique sensing technology ensures that the detector operates at optimum sensitivity for the protected environment, without the need for complex setup. With the integrated Command Module this unit also provides a single location display, control and interfacing option for systems of up to 127 detectors and allow global programming of all detector functions simultaneously.
Specification Order Code Supply Voltage Current Consumption Relay Contact Rating Operating Temperature Range Operating Humidity Range Measurement Range (obs/m) Detection Principle Particle Sensitivity Range Dust Discrimination Principle Maximum Single Sampling Pipe Length / Diameter Total Sampling Pipe Maximum Alarm Levels IP Rating Sampling Pipe Inlets Exhaust Air Pipe Outlets Weight(kg) / Size(mm)
FIRElink-400CM (Standard Detector with Command Module) 21.6 - 26.4 V dc 920 mA @ 24 V dc at fan speed 8 500 mA @ 30 V 0 to +38 °C (UL268), -10 °C to + 60 °C (CEA4022) 0 - 90% non-condensing 0.0015% to 25% Full Scale Deflection (FSD) 0.0015% to 25% Sensitivity Resolution Laser light scattering mass detection and particle evaluation 0.003 μ to 10 μ 3D3 Laser Dust Discrimination (LDD) 100 / ¾” nominal bore (27mm O/D) 200 m @ 100 sampling holes 4 (Aux, Pre-alarm, Fire 1 and Fire 2) IP50 4 on top, 4 at rear 1 on top, 1 at rear 5.3 / H372 x W427 x D95
Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although every effort has been made to ensure the accuracy of the information contained in this document it is not warranted or represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description.
Single Pipe Air Sampling Detector
FIRElink-NANO Features Ultra small, low cost aspirating smoke detector for easy and discreet installation High sensitivity provided by laser based forward light scatter for reliable early warning Single sampling pipe up to 50 m in length (still air) False alarms reduced by unique laser sensing technology - able to discriminate against dust Easy commissioning without the need for a PC
Description FIRElink-NANO is designed to provide reliable sensitivity smoke detection in a small, easy to install package. The unit’s perceptive artificial intelligence ensures that it operates at optimum sensitivity for the protected environment, without the need for complex setup. This means the product will configure itself to provide high sensitivity in a small comms room or reduced sensitivity in a smoky area. Interfacing to Fire panels or BMS systems is via integral Pre-Alarm, Fire and Fault relays. An Hochiki ESP compatible interface card (APIC) is available for addressable systems.
Specification Ordering code Suppply voltage Current consumption
Particle Sensitivity Range Dust Discrimination Principle Recommended Sampling Pipe Length Colour / Case material Sampling Pipe Diameter
FIRElink-NANO 21.6 - 26.4 VDC 350 mA @ 24 VDC -10 °C to +38 °C (UL268), -10 °C to + 60 °C (CEA4022) 0 - 90% non-condensing 0.4% to 25% Laser light scattering mass detection and particle evaluation 0.003 µ to 10 µ 3D3 Laser Dust Discrimination (LDD) 25 m moving air / 50 m still air (max) Ivory / ACS 3/4” nominal bore (27 mm O/D)
Recommended Number of Sampling Holes(EN54-20 performances)
Class A 2 holes
Alarm Levels IP Rating Sampling Pipe Inlets Exhaust Air Pipe Outlets Weight (kg) / Length / Width / Depth (mm)
“PRE-ALARM”, “FIRE” and “FAULT” IP50 1 1
Operating temperature range Operating humidity range Measurement Range (%Obs/m) Detection Principle
Class B 6 holes
Class C 10 holes
1.2 / 225 / 185 / 105
Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although every effort has been made to ensure the accuracy of the information contained in this document it is not warranted or represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description.
High Sensitivity Air Sampling Smoke Detector Command Module
FIRElink-CM Features Network control of 127 detectors RS485 communications Built in short circuit isolators for optimum reliability Integral Serial Interface programmable for TAP text messages/paging or BACnet BMS communications RS232 serial interface for SenseNET PC Graphical Management System Multiple Programming Options
Description Model FIRElink-CM is a standalone Command Module designed to provide a single location display, control and interfacing option for systems of up to 127 other FIRElink detectors. Also allows global programming of all detector functions simultaneously. Each detector on the network can be up to 1.2 Km apart and each is wired in the same manner as an Hochiki ESP loop. Use of the Command Module will provide a full tolerant connection between all detectors. The FIRElink-CM is fully compatible with the SenseNET monitoring and management system.
Specification Order Codes Supply Voltage Current Consumption Relay Contact Rating Operating Temperature Range Operating Humidity Range Alarm Levels Cable Entries Network data bus / Maximum data bus length IP Rating Weight(kg) / Size(mm)
FIRElink-CM (Standalone Command Module) 21.6 - 26.4 V dc 450 mA @ 24 V dc 500 mA @ 30 V 0 to +38 °C (UL268), -10 °C to + 60°C (CEA4022) 0 - 90% non-condensing 4 (Aux, Pre-alarm, Fire 1 and Fire 2) 6 top and 6 rear RS485 / 1.2 km between detectors IP50 6.2 / H372 x W427 x D95
Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although every effort has been made to ensure the accuracy of the information contained in this document it is not warranted or represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description.
Voice Alarm System
FIREvac Features A high quality digital message store containing programmable evacuate alert and test messages A prioritised mixer Two 60 Watt 'Class D' amplifiers An EN54 compliant switch mode PSU/battery charger Three balanced line level inputs (for the optional connection of a firefighter's microphone, paging/public address equipment and a background music source)
Description Hochiki’s FIREvac is a low-cost, high quality modular voice alarm system purposely designed to simplify the provision of a fully BS5839-8 compliant voice alarm system. From one compact wall-mounted enclosure, FIREvac can easily be added to an Hochiki ESP loop by way of a module such as the CHQ-DRC (Dual Relay Controller), making integration with an existing fire detection system simple. Up to 10 Slave FIREvac panels can be connected to give more voice alarm coverage if required. Both Master and Slave FIREvac panels are also available with a hot swap amplifier.
Specification Ordering Codes Operating Voltage Maximum Output Current Quiescent Current Battery Size & Type Speaker Circuits Speaker Line Cabling BGM Input Level Page Mic Input Level Inputs Balanced Line Level Outputs Slave Line Output Colour and Case Material Weight (kg) / Dimensions (mm)
FIREvac Master / FIREvac Slave 230 V ac ±10% 50/60 Hz 5 A (continuous), 7 A (peak) @230 V ac 85 mA (mains fail, no devices) 2 x 12 V 7 AHr VRLA connected in series 2 x 60 Watts (continuous average power) 2 core fire resistant screened, min 1.5 mm2 (500 m max) 230 mV RMS (no link), 2.3 V RMS (link fitted) 230 mV RMS (no link), 2.3 V RMS (link fitted) 4 – Evacuate, Alert, Test, Reset 3 – Fireman's Mic, Background Music, Public Address Up to 10 Slaves per Master Panel RAL 7042 – "Traffic Grey A") / Steel Master 11.1, Slave 10.6 / H450 x W450 x D115
Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although every effort has been made to ensure the accuracy of the information contained in this document it is not warranted or represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description.