Kentec Extiguishant Control Panel

Page 1

Extinguishant System Control Equipment Pages 64-81


Sigma XT EN12094 Extinguishant Control Panels Page 64-65 Sigma XT+ Multi Area Extinguishant Control Panels Page 66-67 Sigma XT+ Extinguishant Coincidence Unit Page 68-69

Sigma Si Status Units and hold off switch for use with Sigma XT/XT+ Page 70-71 Sigma XT Ancillary PCB Extinguishant Ancillary PCB Page 72-73

Syncro XT+ Multi Area Addressable Extinguishant Control Panels Page 74-75

COMING SOON

Sigma A-XT NEW! UL Listed FM Approved Extinguishant Control Panels Page 76-77 Sigma A-Si NEW! Status Units and abort switch for use with Sigma A-XT Page 78-79 Sigma A-XT Ancillary PCB UL Listed FM Approved Extinguishant Ancillary PCB Page 80-81

NEW!


Sigma BS-EN12094-1 KM 96761

Extinguishant Control Panel

XT

Product Overview Designed and manufactured to the highest standards in a quality controlled environment and with European EN12094-1 approvals, the Sigma XT extinguishant releasing panel offers outstanding value and performance for all small to medium fixed firefighting installations.

Features Approved to EN12094-1, EN54-2 and EN54-4 Three detection zones as standard Any single zone or any combinations of zones can be configured to release Configurable first stage sounder delays Configurable detection delays Zero time delay upon manual release option Compatible with I.S. barriers Non-latching zone input option to receive signals from other systems such as aspirating equipment Configurable extinguishant delays up to 60 seconds in 5 second steps Configurable extinguishant duration up to 5 minutes in 5 second steps Countdown timer shows time remaining until release

With three detection zones as standard, extinguishant release can be configured to activate from any combination of detection zone inputs to allow (among other combinations) any two from three type activations such as would be required for detection in ceiling void, room and floor void applications. The extensive configuration options of the Sigma XT allow the functionality of the system to be extensively modified while still complying with the requirements of the controlling standard for the equipment (EN12094-1, EN54-2 and EN54-4). The panel contains a large LED display to enable easy configuration and control which also displays the time remaining until extinguishant release for added user safety. The countdown timer is duplicated on up to seven remote status units to provide local indication of the extinguishant system status. With all of the electronics mounted on a single, easily removable, steel plate Sigma XT panels are both robust and easy to install. Sigma XT is supplied in an enclosure that matches the design and colour of the Sigma CP range.

Supports up to seven, four wire status indicators Built in Extract Fan control

Programmable Functions Access Level 2

Test Zones 1 to 3 Disable Zones 1 to 3 Disable 1st Stage Alarms Disable Pre-activated 1st Stage Relay Disable Pre-activated 2nd Stage Relay Disable Extract Fan Output Disable Manual Release Input Disable Extinguishant Sub System Activate Extract Fan Output Activate Alarm Delays

Access Level 3

Page 64

Sounder Delay Coincidence Detection Disable Panel Features Zone Alarm Delays (Detectors) Zone Alarm Delay (Call Points) Configure Zone for I.S Barrier Use Zone Short Circuit Alarm Zone Non Latching Zone Inputs Delay Extinguishant Release Time Delay Extinguishant Release Duration Timer Extinguishant Reset Delay Timer

Model No. K11031M2


DS40.08.2012

Technical Construction IP Rating Finish Colour - lid & box Colour - controls plate & labels Mains supply Mains supply fuse Power supply rating Maximum ripple current Battery type (Yuasa NP) Battery charge voltage Battery charge current Battery fuse Maximum current draw from batteries Quiescent current of panel in mains fail R0V output Sounder outputs Fault relay contact rating Fire relay contact rating Local fire relay contact rating First stage contact rating Second stage contact rating Extract contact rating Zone quiescent current Terminal capacity Number of detectors per zone Number of sounders per circuit Detection circuit end of line Monitored input end of line Sounder circuit end of line Extinguishant output EOL No. of detection circuits No. of sounder circuits Extinguishant release output Extinguishant release delay Extinguishant release duration SIL, AL, FLT, RST inputs Zone normal threshold Detector alarm threshold Call point alarm threshold Short circuit threshold Head removal condition Cabling Monitored inputs normal threshold Monitored inputs alarm threshold Monitored inputs Short circuit threshold Status unit/Ancillary board connection Status unit power output

-

1.2mm mild sheet steel IP30 Epoxy powder coated BS 00 A 05 grey - fine texture RAL 7047 light grey - satin 230V AC +10%/-15% (100 Watts maximum) 1.6 Amp (F1.6A L250V) 3 Amps total including battery charge 28V +/- 2V 200 millivolts Two 12 Volt 7Ah sealed lead acid in series 27.6VDC nominal (temperature compensated) 0.7A maximum 20mm, 3.15A glass 3 Amps 0.095A Fused at 500mA with electronic fuse 24V Fused at 500mA with electronic fuse 30VDC 1A Amp maximum 30VDC 1A Amp maximum 30VDC 1A Amp maximum 30VDC 1A Amp maximum 30VDC 1A Amp maximum 30VDC 1A Amp maximum 2mA maximum 0.5mm² to 2.5mm² solid or stranded wire Dependent on type (maximum 32) Dependent on type (max. 0.5A per sounder circuit) 6K8 5% ½ Watt resistor 6K8 5% ½ Watt resistor 10K 5% ¼ Watt resistor 1N4004 Diode 3 2 x 1st Stage, 1 x 2nd Stage Fused at 1 Amp Adjustable 0 to 60 seconds (in 5 second steps) Adjustable 60 to 300 seconds (in 5 second steps) Switched -ve, max resistance 100 Ohms 8K ohms to 1K ohm 999 ohms to 400 ohms 399 ohms to 100 ohms 99 ohms to 0 ohms 15.5 to 17.5 volts FP200 or equivalent 8K ohms to 1K ohm 999 ohms to 100 ohms 99 ohms to 0 ohms Two wire RS485 connection Fused at 500mA with electronic fuse

Specification

R0V SIL AL FLT RST AUX REMOTE DATA POWER 24V CONTROL STATUS UNITS

S1

S2

S

S

S

S

6K8

S

Extract Fan Power

Releasing Solenoid

Extinguishant Low Pressure Switch 470R

Remote Hold Switch

Extinguishant Released Pressure Switch 470R

Remote Manual Release Switch

470R

DIODE

S O L

6K8

S

6K8

S

6K8

To Status Units

6K8

Releasing Detectors

Peripheral Detectors

10K

6K8

Remote Control Inputs

E

2nd Stage Sounders

10K

6K8

1st Stage Sounders 10K

Remote Auto/Manual Select Switch

385 x 310 x 90 415 x 315 x 86

470R

Surface mounting panel Flush mounting panel

6K8

Size (mm)

Shutdown Power

K11031M2 K11031F2

Description

Stop Air Conditioning

Product Code

470R

Panels

Auxiliary Signalling Relays

S

NC C NO NC C NO NO C NC C NO NC C NO NC C NO ZONE 1 ZONE 2 ZONE 3 2ND 1ST 2ND MODE MAN. HOLD REL EXTING. LOW EXTRACT FAULT LOCAL FIRE SOUNDER STAGE STAGE SELECT RELEASE PRESS. PRES. RELAY FIRE RELAY SWITCH SWITCH

Sigma XT PCB

The manufacturer reserves the right to amend specifications without prior notice

Page 65


Sigma BS-EN12094-1 KM 96761

Multi- Area Extinguishant Control Panels

Features Approved to EN12094-1, EN54-2 and EN54-4 2, 4 or 8 detection zones 1 to 4 extinguishant areas Dual extinguishant outputs for each area (configurable as Main/Reserve) First and second stage sounder outputs for each area

XT+

Product Overview Sigma XT+ control panels are multi-area extinguishant control panels complying with EN12094-1, EN54-2 and EN54-4. Up to 8 zones of conventional detection with up to 4 extinguishant areas are available. Stand alone extinguishant control units are also available with 2 monitored inputs to receive initiating signals from remote fire detection control panels or addressable modules. Each extinguishant area has a comprehensive set of inputs and outputs and is configurable via a simple programming interface. All extinguishant areas may have up to 7, serially connected Sigma Si status indication and control units or ancillary relay boards connected via a simple 4 core cable. The versatility of the control panel can be enhanced further by the fitting of up to 7 Sigma CP Ancillary boards (K580) or Sigma CP Sounder boards (K461) to the RS485 serial bus. See data sheet DS39 (page 52-53) and DS48 (page 53-54). For compatible status units see Sigma Si data sheet DS41 (page 70-71).

First and second stage volt free changeover contacts for each area Released volt free contact per area Fault volt free contact per area Programmable extinguishant delays Programmable output duration Extract fan control Countdown indicator shows time until release in seconds Mode select and manual release controls per area Monitored remote manual release input Monitored remote Hold input Monitored remote Mode select (door interlock) input Monitored remote Released pressure switch input Monitored remote Low Pressure switch input Monitored Abort input Serial connection for Sigma Si status units and ancillary boards. (K588) Model No. K21082M3

Page 66

Sigma XT Ancillary Board - K588

Sigma CP Ancillary Board - K580

Sigma CP Sounder Board - K461


DS50.05.2012

Panels

Specification

Product Code Zones Areas Size (mm) K21021M3 K21041M3 K21042M3 K21081M3 K21082M3 K21083M4 K21084M4

2 4 4 8 8 8 8

1 1 2 1 2 3 4

385 x 520 x 110 385 x 520 x 110 385 x 520 x 110 385 x 520 x 110 385 x 520 x 110 385 x 700 x 145 385 x 700 x 145

Technical Construction IP Rating Finish Colour - lid & box Colour - controls plate & labels Mains supply Mains supply fuse Power supply rating (1 & 2 area units) Power supply rating (3 & 4 area units) Maximum ripple current Battery charge voltage Battery charge current Battery fuse Current draw in mains fail condition Max. current draw from batteries

-

Sigma XT+ module Aux 24V output Sigma CP Aux 24V output 1st and 2nd stage Sounder outputs Fault relay contact rating Fire relay contact rating Local fire relay contact rating First stage contact rating Second stage contact rating Extract contact rating Zone quiescent current Terminal capacity Number of detectors per zone Number of sounders per circuit Detection circuit end of line Monitored input end of line Sounder circuit end of line Extinguishant output end of line No. of detection circuits No. of sounder circuits Extinguishant release output Extinguishant release delay Extinguishant release duration SIL, AL, FLT, RST inputs Zone normal threshold (Allowable EOL) Detector alarm threshold Call point alarm threshold Short circuit threshold Head removal condition Cabling Monitored inputs normal threshold (Allowable EOL) Monitored inputs alarm threshold Monitored inputs Short circuit threshold Status unit/Ancillary board connection Status unit power output

-

230V AC, 50Hz +10% - 15% (100 Watts maximum) 1.6 Amp ( F1.6A L250V) 3 Amps total including battery charge 28V +/- 2V 5.25 Amps including battery charge 28V +/- 2V 200 millivolts 27.6VDC nominal (temperature compensated) 0.7A maximum 20mm, 3.15A glass 54 milliamps per module 3A (K21021, K21041, K21042, K21081, K21082) 4A (K21083, K21084) Fused at 500mA with electronic fuse - 1 per extinguishant area Fused at 2.5A - not available to user 21 to 28V DC Fused at 1A with electronic fuse 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 0mA minimum, 2mA maximum 0.5mm2 to 2.5mm2 solid or stranded wire Dependent on type - typically 20 Dependent on type and current consumption - typically 20+ 6K8 +/- 5% ½ Watt resistor 6K8 +/- 5% ½ Watt resistor 10K +/- 5% ¼ Watt resistor 1N4004 Diode Two to eight. 21 to 28V DC Dependent on model 21 to 28V DC 21 to 28V DC. Fused at 1 Amp Adjustable 0 to 60 seconds (+/- 10%) Adjustable 60 to 300 seconds Switched -ve, min resistance 0 ohms, max resistance 100 Ohms 10K ohm to 2K ohm 1K ohms to 390 ohms 370 ohms to 150 ohms 130 ohms to 0 ohms 15.5 to 17.5 volts FP200 or equivalent (max capacitance 1uF max inductance 1 mH 10K ohm to 2K ohm

-

2K ohms to 150 ohms +/- 5% 140 ohms to 0 ohms +/- 5% Two wire RS485 connection (EIA-485 specification) 21 to 28V DC. Fused at 500mA with electronic fuse

1.2mm mild sheet steel IP30 Epoxy powder coated BS 00 A 05 grey - fine texture RAL 7047 light grey - satin

The manufacturer reserves the right to amend specifications without prior notice

Page 67


Sigma BS-EN12094-1 KM 96761

Extinguishant Coincidence Unit

XT+

Product Overview The Sigma XT+ ECU coincidence unit has two fully monitored inputs for connection to fire detection control equipment or addressable control modules to provide an EN12094-1 , EN54-2 and EN54-4 compliant extinguishant control system. Its many programmable features and extensive range of inputs and outputs make the Sigma XT+ ECU coincidence unit suitable for all extinguishing applications where a fully featured control device is required.

Features Approved to EN12094-1, EN54-2 and EN54-4 Dual extinguishant outputs First and second stage sounder outputs

Among the many features of the Sigma XT+ ECU are serially connected status units for reduced wiring and reduced installation cost, dual extinguishant outputs that may be configured for main/reserve applications and a countdown timer which displays the time until discharge of the extinguishant in seconds. All units are independently configurable via a simple, code based programming interface to suit the desired application.

First and second stage relay contacts Main reserve facility Serial connection to status units Discharge countdown time indicator

Model No. K21001M2

Page 68


DS55.07.2012

Example Schematic 1 Sigma CP Ancillary Board (S580)

Sigma CP Sounder Board (S461)

24V Power Supply KENTEC ELECTRONICS LTD FUSE-T2A 250V HRC

Sigma CP-R Repeater Panel (Up to 7)

L E N LOAD 28V DC

1. MAINS FAILED 2. BATT. DISCONN. 3. BATTERY LOW 4. EARTH FAULT 5. CHARGER FAIL 6. COMMON FAULT L1 - MAINS FAIL L2 - BATT DISCON. L3 - BATTERY LOW L4 - EARTH FAULT L5 - CHGR. FAULT

REPLACE FUSE ONLY WITH 20mm TIME DELAY TYPE T2A250V

L2

L1

Specification

MODEL - ENS400 INPUT VOLTAGE - 230V AC INPUT CURRENT - 2A FREQUENCY - 50 - 60Hz OUTPUT VOLTAGE - 28V DC POWER RATING - 112W

24V BATT.

1. 2. 3. 4. 5. 6.

L1 L2

L5 L4 L3 L3

L4

L5

EN54-4 : 1998

Up to 4 Sigma XT+ coincidence units may be fitted Sigma XT+ Coincidence Unit

RS485

Sigma XT+ Coincidence Unit 230V

RS485

Sigma CP Control Panel

RS485

Up to 7 Ancillary Boards

K588 Ancillary Board

Up to 7 Ancillary Boards

K588 Ancillary Board

Up to 7 Status Units

System Status & Control

Up to 7 Status Units

System Status & Control

Example Schematic 2

1 Loop Module

Syncro Control Panel

Loop Module Sigma XT+ Coincidence Unit

Sigma XT+ Coincidence Unit 230V

RS485

RS485

Up to 7 Ancillary Boards

K588 Ancillary Board

Up to 7 Ancillary Boards

K588 Ancillary Board

Up to 7 Status Units

System Status & Control

Up to 7 Status Units

System Status & Control

Technical Product Code Size Construction IP Rating Finish Colour - lid & box Colour - controls plate & labels Areas Mains supply Mains supply fuse Power supply rating

-

- 1 - 230V AC, 50Hz +10% - 15% (100 Watts max.) - 1.6 Amp ( F1.6A L250V) - 5.25 Amps total including battery charge 28V +/- 2V - 200 millivolts - 12 Volt sealed lead acid in series - Yuasa 7Ah

Maximum ripple current Battery type (Yuasa NP) Maximum Battery Capacity within Enclosure Battery charge voltage Battery charge current Battery fuse Current draw in mains fail condition Maximum current draw from batteries Aux 24V output 1st and 2nd stage Sounder outputs Fault relay contact rating Fire relay contact rating

K21001H2 Local fire relay 385mm(W) x 310mm(H) x 110mm(D) contact rating 1.2mm mild sheet steel First stage contact rating IP30 Epoxy powder coated Second stage contact rating BS 00 A 05 grey - fine texture RAL 7047 light grey - satin Extract contact rating

27.6VDC nominal (temperature compensated) 0.7A maximum 20mm, 3.15A glass 54 milliamps 4 Amps

Fused at 500mA with electronic fuse 21 to 28V DC Fused at 1A with electronic fuse 5 to 30VDC 1A Amp maximum for each - 5 to 30VDC 1A Amp maximum for each

- 5 to 30VDC 1A Amp maximum for each - 5 to 30VDC 1A Amp maximum for each - 5 to 30VDC 1A Amp maximum for each - 5 to 30VDC 1A Amp maximum for each Zone quiescent current - 0mA minimum, 2mA maximum Terminal capacity - 0.5mm2 to 2.5mm2 solid or stranded wire Number of sounders - Dependent on type and per circuit current consumption Monitored input end of line - 6K8 +/- 5% ½ Watt resistor Sounder circuit end of line 10K +/- 5% ¼ Watt resistor Extinguishant output - 1N4004 Diode end of line Extinguishant release output - 21 to 28V DC. Fused at 1 Amp Extinguishant release delay Adjustable 0 to 60 seconds - (+/- 10%) Extinguishant release - Adjustable 60 to 300 seconds duration Monitored inputs normal - (Allowable EOL) threshold 10K ohm to 2K ohm Monitored inputs alarm - 2K ohms to 150 ohms +/- 5% threshold Monitored inputs Short - 140 ohms to 0 ohms +/- 5% circuit threshold Status unit/Ancillary - Two wire RS485 connection board connection (EIA-485 specification) Status unit power output - 21 to 28V DC, Fused at 500mA with electronic fuse

The manufacturer reserves the right to amend specifications without prior notice

Page 69


Sigma Si

& Hold Switch Extinguishant Status Indicators

Sigma Si

Product Overview The Sigma Si range of status indicators provide detailed status information for Sigma XT/XT+ extinguishant release control equipment. All models provide high brightness, LED indication of Manual Only, Automatic and Manual, Hold operated, Disabled, Imminent and Released conditions. Models are also available with zonal fire indicators and a common fault indicator. For systems where local control of the Automatic/Manual mode and or a Manual extinguishant release control are required, units are available with these controls fitted.

Sigma Si

Features

All models have monitored inputs for the remote connection of Automatic/ Manual mode and Hold switches.

Certified compliant with BS EN12094-1 when used with Sigma XT control equipment

All units contain a large, LED display which shows a countdown of the time remaining until the extinguishant is released in seconds.

High brightness LEDs Detailed indication of the status of the control panel Monitored data connection

Hold off

Countdown timer shows time remaining until release

Product Overview

Manual only and Automatic & Manual mode select keyswitch option

Available with red or green actuators (BS 7273-1 recommends white with red button)

Four wire connection (data and power)

Shrouded push button to prevent accidental operation

Protected dual action manual release switch option

Fitted with normally open and normally closed contacts to allow operation with monitored and unmonitored systems

Option for zonal fire and common fault indication with buzzer

Robust all steel enclosure

Robust, high quality enclosure Easy access to terminals Remote Auto/Manual door interlock input (monitored) Remote Hold input (monitored) Internal fault diagnosis indicators Weatherproof IP65 versions available Internal buzzer

Model No. K91000M10

Model No. K911000M8

Page 70

Model No. K911111M8

Model No. K911113M8

Model No. K911100M8

Model No. K911110M8


DS41.05.2012

Manual Only Auto/Manual

Specification

Hold Activated Disabled

256mm

Imminent Released

available on 10 lamp units only

Fire Zone 2 Fire Zone 3

170mm

Fire Zone 1

Fault Weatherproof Version Model No. W911113W8*

Equipment Product Code Description

Size (mm)

K911000M8 K911000F8 K911100M8 K911100F8 K911010M8 K911010F8 K911110M8 K911110F8 K911113M8* K911113F8*

6 lamp status unit surface 6 lamp status unit flush 6 lamp status unit with mode select keyswitch surface 6 lamp status unit with mode select keyswitch flush 6 lamp status unit with manual release surface 6 lamp status unit with manual release flush 6 lamp status unit with mode select keyswitch and manual release surface 6 lamp status unit with mode select keyswitch and manual release flush 10 lamp status unit with mode select keyswitch and manual release surface 10 lamp status unit with mode select keyswitch and manual release flush

186 x 132 x 50 186 x 132 x 55 186 x 132 x 50 186 x 132 x 55 186 x 132 x 50 186 x 132 x 55 186 x 132 x 50 186 x 132 x 55 186 x 132 x 50 186 x 132 x 55

W911000W8 W911100W8 W911110W8 W911113W8*

IP65 - 6 lamp status unit surface IP65 - 6 lamp status unit with mode select keyswitch surface IP65 - 6 lamp status unit with mode select keyswitch and manual release surface IP65 - 10 lamp status unit with mode select keyswitch and manual release surface

256 x 170 x 60 256 x 170 x 60 256 x 170 x 60 256 x 170 x 60

K91000M10 KB91000M10

Extinguishant hold off switch unit - green button Extinguishant hold off switch unit - red button

97 x 97 x 45 97 x 97 x 45

* Not suitable for Sigma XT+ / Syncro XT+ or Sigma XT+ ECU products

Sigma Si

Hold off

Technical Construction IP Rating (Standard unit) IP Rating (Weatherproof unit) Colour - lid & box Power supply Maximum current draw Max. number of status units Quiescent current Cable capacity Monitored inputs end of line resistor Monitored inputs normal threshold Monitored inputs trigger threshold Monitored inputs Short circuit threshold Data connection

Technical -

1.2mm mild sheet steel IP30 IP65 BS 00 A 05 grey - fine texture

21 to 30 V DC 0.07A 7 0.033A 2.5mm² per terminal 6K8 0.5W Resistor

Construction IP Rating Colour - lid & box Contacts Trigger resistor

-

1.2mm mild sheet steel IP30 White 1 N.O and 1 N.C 470R 1 Watt

8K ohm to 1K ohm 700 ohms to 100 ohms 99 ohms to 0 ohms Two wire RS485 connection (max 1200 metres)

The manufacturer reserves the right to amend specifications without prior notice

Page 71


Sigma Si

Ancillary PCB Extinguishant Ancillary PCB Ancillary PCB

Product Overview The Sigma XT Ancillary Board is compatible with all Sigma XT control panels which have operating software version SIGXT_11A.HEX or above. The board provides volt free normally open contacts allowing control of sub-systems and plant remotely from the main panel over a two wire data bus. Mains powered, boxed Ancillary boards require only a two core data cable from the main control panel. 24V DC versions require an additional two cores for power either from the main panel or from another 24V DC source.

Ancillary PCB

Features

Up to 7 Ancillary boards can be connected to a control panel and each is allocated an address from 1 to 7 using a binary coded DIL switch. The total length of the data cable from the main panel to the last repeater must not exceed 1200 metres.

Two wire serial connection Up to 7 per system

A mixture of status units and Ancillary boards, up to a maximum of 7 of each type, can be connected to the serial data bus.

230V AC or 24V DC powered versions Volt free relay outputs for fire and extinguishing system status Relay operated LED indicators

HOLD MODE OUT IN RS485 24V DC

Status PCB

Equipment

6K8 6K8

470R

Product Code Description

Size (mm)

K588 K03000M2 K03750M2

155 x 136 385 x 310 x 90 385 x 310 x 90

Stand alone ancillary PCB Boxed ancillary PCB Boxed ancillary PCB with 0.75A PSU

470R

To next Status Unit if fitted From previous status unit or control panel To next Status Unit if fitted From previous status unit or control panel

Ancillary PCB

Technical Construction (Boxed) IP Rating (Boxed) Colour - lid & box

- 1.2mm mild sheet steel - IP30 - BS 00 A 05 grey - fine texture Supply voltage (K03750M2) - 230V AC (+10%/-15%) Supply voltage (K03000M2) - 20-30V DC

Mains supply fuse Power supply DC rating Maximum battery size Contact ratings Cable capacity Operating temperature Operating humidity

Model No. K1822

Page 72

-

1.6A 250V 24V 0.75 Amp 2Ah 24V (2 per panel) 30V DC 1 Amp 2.5mm² per terminal -5°C to +50°C <95% (non condensing)


DS75.02.2012

Specification + - + 24V DC

24V DC

Z1

Z2

PF

Z1 FIRE

Z3

Z2 FIRE

Z3 MAN DISAB FIRE MODE

MAN DISAB

REL

ACT

REL

MAN REL

ACT

EXTR

HOLD EXTR

HOLD

+ - +-

MAN RS485 RS485 REL OUT IN

FUSE OK FAIL

PROCESSOR RESET

ADDRESS

Door Interlock

Hold 1st Stage Sounders

Low Pressure Switch Released Pressure Switch Activate Extinguisher

2nd Stage Sounders

Detection Zone 3

Manual Release

Example System Schematic

Detection Zone 2 Detection Zone 1

System Status and Control 4 Core

Ancillary Board EN12094-1 Approved Control Unit

System Status and Control

Addressable House Fire Alarm

System Status and Control

BMS Interface

4 Core

Ancillary Board

The manufacturer reserves the right to amend specifications without prior notice

Page 73


XT+

Multi-Area, Addressable Extinguishant Control Panels

CO SO MI O NG N

Syncro

Product Overview Syncro XT+ control panels are multi-area extinguishant control panels complying with EN12094-1. p to 16 zones of addressable detection over 1 or 2 loops ensure U every detector is able to contribute to extinguishant release. Up to 4 extinguishant areas are available. Stand alone extinguishant control units are also available with 2 monitored inputs to receive initiating signals from remote fire detection control panels or addressable modules.

Features Complies with EN12094-1 16 detection zones

Each extinguishant area has a comprehensive set of inputs and outputs and is configurable via a simple programming interface. All extinguishant areas may have up to 7, serially connected Sigma Si status indication and control units or ancillary relay boards connected via a simple 4 core cable. For compatible status units see Sigma Si data sheet DS41 (page 70-71).

Up to 4 extinguishant areas Dual extinguishant outputs for each area (configurable as Main/Reserve) First and second stage sounder outputs for each area First and second stage volt free changeover contacts for each area Released volt free contact per area Fault volt free contact per area Programmable extinguishant delays Programmable output duration Countdown indicator shows time until release in seconds Mode select and manual release controls per area Monitored remote manual release input Monitored remote hold input Monitored remote mode select (door interlock) input Monitored remote released pressure switch input Monitored Abort input Serial connections for Sigma Si status units and ancillary boards. (K588)

Model No. #32162M3

Page 74


DS58.03.2012

Specification Panels Product Code Loop Areas Size (mm) #31161M3 #32161M3 #31162M3 #32162M3 #31163M4 #32163M4 #31164M4 #32164M4

1 2 1 2 1 2 1 2

1 1 2 2 3 3 4 4

385 x 520 x 110 385 x 520 x 110 385 x 520 x 110 385 x 520 x 110 385 x 700 x 145 385 x 700 x 145 385 x 700 x 145 385 x 700 x 145

‘#’ - replace with: ‘A’ for Apollo protocol, ‘H’ for Hochiki protocol ‘V’ for Argus Vega protocol

Technical Construction IP Rating Finish Colour - lid & box Colour - controls plate & labels Mains supply Mains supply fuse Power supply rating (1 & 2 area units) Power supply rating (3 & 4 area units) Maximum ripple current Battery charge voltage Battery charge current Battery fuse Current draw in mains fail condition Max. current draw from batteries

-

Sigma XT+ module Aux 24V output Syncro AS Aux 24V output 1st and 2nd stage Sounder outputs Fault relay contact rating Fire relay contact rating Local fire relay contact rating First stage contact rating Second stage contact rating Extract contact rating Terminal capacity Number of sounders per circuit Monitored input end of line Sounder circuit end of line Extinguishant output end of line Number of detection loops Number of zones No. of sounder circuits Extinguishant release output Extinguishant release delay Extinguishant release duration SIL, AL, FLT, RST inputs Cabling Monitored inputs normal threshold Monitored inputs alarm threshold Monitored inputs Short circuit threshold Status unit/Ancillary board connection Status unit power output

-

1.2mm mild sheet steel IP30 Epoxy powder coated BS 00 A 05 grey - fine texture RAL 7047 light grey - satin

230V AC, 50Hz +10% - 15% (100 Watts maximum) 1.6 Amp ( F1.6A L250V) 3 Amps total including battery charge 28V +/- 2V 4 Amps including battery charge 28V +/- 2V 200 millivolts 27.6VDC nominal (temperature compensated) 0.7A maximum 20mm, 3.15A glass 54 milliamps per extinguishing module 3A (#31161M3, #32161M3, #31162M3, #32162M3) 5.25A (#31163M4, #32163M4, #31164M4, #32164M4) Fused at 500mA with electronic fuse - 1 per extinguishant area Fused at 2.5A - not available to user 21 to 28V DC Fused at 1A with electronic fuse 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 0.5mm2 to 2.5mm2 solid or stranded wire Dependent on type and current consumption - typically 20+ 6K8 +/- 5% ½ Watt resistor 10K +/- 5% ¼ Watt resistor 1N4004 Diode 1 or 2 16 Dependent on model 21 to 28V DC 21 to 28V DC. Fused at 1 Amp Adjustable 0 to 60 seconds (+/- 10%) Adjustable 60 to 300 seconds Switched -ve, min resistance 0 ohms, max resistance 100 Ohms FP200 or equivalent (max capacitance 1uF max inductance 1 mH 10K ohm to 2K ohm 2K ohms to 150 ohms +/- 5% 140 ohms to 0 ohms +/- 5% Two wire RS485 connection (EIA-485 specification) 21 to 28V DC. Fused at 500mA with electronic fuse The manufacturer reserves the right to amend specifications without prior notice

Page 75


A-XT

Extinguishant Control Panel

! N EW

Sigma

Product Overview Designed and manufactured to the highest standards in a quality controlled environment and with UL and FM approvals, the Sigma A-XT releasing panel offers outstanding value and performance for all small to medium fixed firefighting installations.

Features UL864 and FM listed Three initiation circuits as standard Any single zone or any combinations of zones can be configured to release Configurable first stage NAC delays Configurable detection delays Zero time delay upon manual release option Compatible with I.S. barriers Non-latching zone input option to receive signals from other systems such as aspirating equipment Configurable releasing delays up to 60 seconds in 5 second steps Configurable releasing duration up to 5 minutes in 5 second steps

With three initiation circuits as standard, release can be configured to activate from any combination of detection zone inputs to allow (among other combinations) any two from three type activations such as would be required for detection in ceiling void, room and floor void applications. The extensive configuration options of the Sigma A-XT allow the functionality of the system to be extensively modified. The panel contains a large LED display to enable easy configuration and control which also displays the time remaining until release for added user safety. The countdown timer is duplicated on up to seven remote status units to provide local indication of the system status. With all of the electronics mounted on a single, easily removable, steel plate Sigma A-XT panels are both robust and easy to install. Sigma A-XT is supplied in an enclosure that matches the design and color of the Elite RS range and is available in standard red or optional gray.

Countdown timer shows time remaining until release Supports up to seven, four wire status indicators Built in Extract Fan control

Programmable Functions Access Level 2

Test Zones 1 to 3 Disable Zones 1 to 3 Disable 1st Stage Alarms Disable Pre-activated 1st Stage Relay Disable Pre-activated 2nd Stage Relay Disable Extract Fan Output Disable Manual Release Input Disable Releasing Sub System Activate Extract Fan Output Activate Alarm Delays

Access Level 3

Page 76

Sounder Delay Coincidence Detection Disable Panel Features Zone Alarm Delays (Detectors) Zone Alarm Delay (Call stations) Configure Zone for I.S Barrier Use Zone Short Circuit Alarm Zone Non Latching Zone Inputs Delay Extinguishant Release Time Delay Extinguishant Release Duration Timer Extinguishant Reset Delay Timer

Model No. K1810-10


DS72.03.2012

Technical Construction IP Rating Finish Colour - lid & box Mains supply Mains supply fuse Power supply rating Maximum ripple current Battery type (Yuasa NP) Battery charge voltage Battery charge current Battery fuse Maximum current draw from batteries Quiescent current of panel in mains fail R0V output Sounder outputs Fault relay contact rating Fire relay contact rating Local fire relay contact rating First stage contact rating Second stage contact rating Extract contact rating Zone quiescent current Terminal capacity Number of detectors per zone NAC rating Detection circuit end of line Monitored input end of line Sounder circuit end of line Extinguishant output EOL No. of initiating circuits No. of NAC circuits Extinguishant release output Extinguishant release delay Extinguishant release duration SIL, AL, FLT, RST inputs Zone normal threshold Detector alarm threshold Call point alarm threshold Short circuit threshold Monitored inputs normal threshold Monitored inputs alarm threshold Monitored inputs Short circuit threshold Status unit/Ancillary board connection Status unit power output

-

1.2mm mild sheet steel IP30 Epoxy powder coated Red RAL 3002 (optional grey BS 00 A 05 semi-matt) 230V AC or 115V AC 1.6 Amp (F1.6A L250V) 3 Amps total including battery charge 28V +/- 2V 200 millivolts Two 12 Volt 7Ah sealed lead acid in series 27.6VDC nominal (temperature compensated) 0.7A maximum 20mm, 3.15A glass 3 Amps 0.095A Fused at 500mA with electronic fuse 24V Fused at 500mA with electronic fuse 30VDC 1A Amp maximum 30VDC 1A Amp maximum 30VDC 1A Amp maximum 30VDC 1A Amp maximum 30VDC 1A Amp maximum 30VDC 1A Amp maximum 2mA maximum

Specification

12 AWG

Dependent on type (maximum 32) 0.5A per circuit 6K8 5% ½ Watt resistor 6K8 5% ½ Watt resistor 10K 5% ¼ Watt resistor 1N4004 Diode 3 2 x 1st Stage, 1 x 2nd Stage Fused at 1 Amp Adjustable 0 to 60 seconds (in 5 second steps) Adjustable 60 to 300 seconds (in 5 second steps) Switched -ve, max resistance 100 Ohms 8K ohms to 1K ohm 999 ohms to 400 ohms 399 ohms to 100 ohms 99 ohms to 0 ohms 8K ohms to 1K ohm 999 ohms to 100 ohms 99 ohms to 0 ohms Two wire RS485 connection Fused at 500mA with electronic fuse

S

S

S

S

S

Extract Fan Power

Releasing Solenoid

Extinguishant Low Pressure Switch 470R

Remote Abort Switch

Extinguishant Released Pressure Switch 470R

Remote Manual Release Switch

470R

DIODE

S O L

6K8

S

6K8

6K8

S

6K8

To Status Units

6K8

Peripheral Detectors

10K

6K8

Remote Control Inputs

E

10K

Releasing Detectors

10K

2nd Stage Notification Appliances

6K8

1st Stage Notification Appliances

Remote Auto/Manual Select Switch

368 x 310 x 90 368 x 310 x 90 368 x 310 x 90 368 x 310 x 90

470R

Surface mounting panel - Red 115V Surface mounting panel - Red 230V Surface mounting panel - Grey 115V Surface mounting panel - Grey 230V

6K8

Size (mm)

Shutdown Power

K1810-12 K1810-13 K1810-44 K1810-43

Description

Stop Air Conditioning

Product Code

470R

Panels

Auxiliary Signalling Relays

S

R0V SIL AL FLT RST NC C NO NC C NO NO C NC C NO NC C NO NC C NO AUX REMOTE DATA POWER NAC 1 NAC 2 ZONE 1 ZONE 2 ZONE 3 2ND 1ST 2ND MODE MAN. ABORT REL EXTING. LOW EXTRACT TROUBLE LOCAL FIRE 24V CONTROL SOUNDER STAGE STAGE SELECT RELEASE PRESS. PRES. RELAY FIRE RELAY STATUS UNITS SWITCH SWITCH

Sigma A-XT PCB

The manufacturer reserves the right to amend specifications without prior notice

Page 77


A-Si

! N EW

Sigma

& Abort Switch Extinguishant Status Indicators

Sigma A-Si

Product Overview The Sigma A-Si range of status indicators provide detailed status information for Sigma A-XT releasing control equipment. All models provide high brightness, LED indication of Manual Only, Automatic and Manual, Abort operated, Disabled, Imminent and Released conditions. Models are also available with zonal fire indicators and a common trouble indicator. For systems where local control of the Automatic/Manual mode and or a Manual extinguishant release control are required, units are available with these controls fitted.

Sigma A-Si

Features

All models have supervised inputs for the remote connection of Automatic/ Manual mode and abort switches.

UL864 and FM listed

All units contain a large, LED display which shows a countdown of the time remaining until release in seconds.

High brightness LEDs Detailed indication of the status of the control panel Supervised data connection

Abort Switch

Countdown timer shows time remaining until release

Product Overview

Manual only and Automatic & Manual mode select keyswitch option

The Sigma A-XT Abort switch connects to the Abort terminals of the Sigma A-XT releasing panel. Any number of Sigma A-XT Abort switches may be connected to the circuit.

Four wire connection (data and power) Protected dual action manual release switch option

The last switch must have the end of line device from the Abort circuit terminals of the Sigma A-XT releasing panel fitted across its connections to provide open and short circuit supervision.

Option for zonal fire and trouble indication with buzzer

The unit is supplied mounted to a rugged steel enclosure but may also be flush mounted to a single gang electrical box.

Robust, high quality enclosure Easy access to terminals Remote Auto/Manual door interlock input (supervised) Remote Abort input (supervised) Internal trouble diagnosis indicators

Model No. K1821-19 Model No. K1823-10

Model No. K1821-11

Page 78

Model No. K1821-15

Model No. K1821-13

Model No. K1821-17


DS73.02.2012

Manual Only Auto/Manual

Specification

Abort Activated Disabled Imminent Released Fire Zone 1 Fire Zone 2 Fire Zone 3 Trouble

Equipment Product Code Description

Size (mm)

K1821-11 K1821-41 K1821-12 K1821-42 K1821-13 K1821-43 K1821-14 K1821-44 K1821-15* K1821-45* K1821-16* K1821-46* K1821-17* K1821-47* K1821-18* K1821-48* K1821-19* K1821-49* K1821-20* K1821-50* K1823-10 K1823-40

186 x 132 x 50 186 x 132 x 50 186 x 132 x 55 186 x 132 x 55 186 x 132 x 50 186 x 132 x 50 186 x 132 x 55 186 x 132 x 55 186 x 132 x 50 186 x 132 x 50 186 x 132 x 55 186 x 132 x 55 186 x 132 x 50 186 x 132 x 50 186 x 132 x 55 186 x 132 x 55 186 x 132 x 50 186 x 132 x 50 186 x 132 x 55 186 x 132 x 55 98 x 98 x 59 98 x 98 x 59

6 lamp status unit surface mount - red 6 lamp status unit surface mount - gray 6 lamp status unit flush mount - red 6 lamp status unit flush mount - gray 6 lamp status unit with mode select keyswitch surface mount - red 6 lamp status unit with mode select keyswitch surface mount - gray 6 lamp status unit with mode select keyswitch flush mount - red 6 lamp status unit with mode select keyswitch flush mount - gray 6 lamp status unit with manual release surface mount - red 6 lamp status unit with manual release surface mount - gray 6 lamp status unit with manual release flush mount - red 6 lamp status unit with manual release flush mount - gray 6 lamp status unit with mode select keyswitch & manual release surface mount - red 6 lamp status unit with mode select keyswitch & manual release surface mount - gray 6 lamp status unit with mode select keyswitch & manual release flush mount - red 6 lamp status unit with mode select keyswitch & manual release flush mount - gray 10 lamp status unit with mode select keyswitch & manual release surface mount - red 10 lamp status unit with mode select keyswitch & manual release surface mount - gray 10 lamp status unit with mode select keyswitch & manual release flush mount - red 10 lamp status unit with mode select keyswitch & manual release flush mount - gray Elite Extinguishing Abort switch surface mount - red Elite Extinguishing Abort switch surface mount - gray

* Not UL/FM Listed

Sigma A-Si

Abort Switch

Technical Construction IP Rating Colour - lid & box Power supply Maximum current draw Max. number of status units Quiescent current Cable capacity Monitored inputs end of line resistor Monitored inputs normal threshold Monitored inputs trigger threshold Monitored inputs Short circuit threshold Data connection

Technical -

1.2mm mild sheet steel IP30 Red (optional grey)

21 to 30 V DC 0.07A 7 0.033A 2.5mm² per terminal 6K8 0.5W Resistor

Construction IP Rating Colour Switch rating Trigger resist End of line resistor

-

1.2mm mild sheet steel IP30 Red (optional grey)

1A at 30V DC 470R 1W 6K8 1/2 W

- 8K ohm to 1K ohm - 700 ohms to 100 ohms - 99 ohms to 0 ohms - Two wire RS485 connection

(max 1200 metres)

The manufacturer reserves the right to amend specifications without prior notice

Page 79


A-XT

Ancillary PCB

N EW

!

Sigma Extinguishant Ancillary PCB Ancillary PCB

Product Overview The Sigma A-XT Ancillary Board is compatible with all Sigma A-XT control panels. The board provides volt free normally open contacts allowing control of sub-systems and plant remotely from the main panel over a two wire data bus. Ancillary boards require only a two core data cable from the main control panel and a two core power cable from the main panel.

Ancillary PCB

Up to 7 Ancillary boards can be connected to a control panel and each is allocated an address from 1 to 7 using a binary coded DIL switch. The total length of the data cable from the main panel to the last repeater must not exceed 4000 feet.

UL864 and FM listed

A mixture of status units and Ancillary boards, up to a maximum of 7 of each type, can be connected to the serial data bus.

Features

Two wire serial connection Up to 7 per system Volt free relay outputs for fire and releasing system status

Equipment

Relay operated LED indicators

ABORT MODE OUT IN RS485 24V DC

Status PCB

6K8 6K8

470R

Product Code Description

Size (mm)

K1822-00 K1822-10

155 x 136 385 x 310 x 90 385 x 310 x 90

K1822-40

Sigma A-XT Ancillary Board Sigma A-XT Ancillary Board with cabinet - red Sigma A-XT Ancillary Board with cabinet - gray

470R

To next Status Unit if fitted From previous status unit or control panel To next Status Unit if fitted From previous status unit or control panel

Ancillary PCB

Technical Construction (Boxed) IP Rating (Boxed) Colour - lid & box Supply voltage Contact ratings Cable capacity Operating temperature Operating humidity

Model No. K1822

Page 80

-

1.2mm mild sheet steel IP30 Red (optional grey)

20-30V DC 30V DC 1 Amp 2.5mm² per terminal -5°C to +50°C <95% (non condensing)


DS74.02.2012

Specification + - + 24V DC

24V DC

Z1

Z2

PF

Z1 FIRE

Z3

Z2 FIRE

Z3 MAN DISAB FIRE MODE

MAN DISAB

REL

ACT

REL

MAN REL

ACT

EXTR

HOLD EXTR

HOLD

+ - +-

MAN RS485 RS485 REL OUT IN

FUSE OK FAIL

PROCESSOR RESET

ADDRESS

Door Interlock

Hold 1st Stage Sounders

Low Pressure Switch Released Pressure Switch Activate Extinguisher

2nd Stage Sounders

Detection Zone 3

Manual Release

Example System Schematic

Detection Zone 2 Detection Zone 1

System Status and Control 4 Core

Ancillary Board Sigma A-XT Control Panel

System Status and Control

Addressable House Fire Alarm

System Status and Control

BMS Interface

4 Core

Ancillary Board

The manufacturer reserves the right to amend specifications without prior notice

Page 81


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.