Technical Bulletin Issue 06

Page 1

HI Technical Bulletin Issue 6 February 2009

For registered members of the SAVA Certification Scheme This month: The Party Wall etc. Act 1996 and the Home Inspector Do you agree with the Home Inspector? Some thoughts on pitched roofs Notes/record of inspection— important reminder Last month‟s case study comments

Welcome to Issue 6 of SAVA‟s Home Inspector Technical Bulletin The bulletin focuses on Home Condition Reports and associated non-energy issues. We trust that you will find the bulletin useful for your day-to-day work and we welcome any feedback you have about what you would like to see covered in future editions.

The Party Wall etc. Act 1996 and the Home Inspector It is a frequent misconception that the Party Wall etc. Act (PWA) 1996 only affects new construction and major conversion works such as extensions and radical internal re-configuration, for

example

loft

conversions

and

basement extensions. As this article will explain, the Home Inspector and surveyor must be aware of the PWA and

how

it

might

affect

smaller

building works. The purpose of the article is assist in identifying issues which may give rise to the proceedings and matters of which the Home Inspector should be aware

when

considering

the

costs

involved in the repairs, which he is identifying as being necessary.

The

most likely occasions that the HI will encounter the need for procedures involving

the

PWA

are

when

he

identifies a defect requiring repair, which is likely to affect the next door neighbour. This can be anything from a major repair such as underpinning a section of the building to simply repointing part of a shared chimney or

under the PWA, creating a record of the state of the neighbour's property (a

Schedule

of

Condition)

and

creating a legal document called an Award. (NB The protection provided operates in both directions. the

Schedule

of

Without

Condition,

the

instigator of the work can deny that reported damage occurred as result of his operation and a long legal battle ensures. It has also not been unknown for a neighbour to make a fraudulent

claim

that

pre-existing

damage has only just occurred and is clearly the result of the works.)

replacing the flashings.

What causes the PWA to

Before focussing on details, we need

be brought into action?

to look at what generally gives rise to

Essentially, there are three situations

circumstances, which will involve the

where Notices under the PWA are

PWA and why. The PWA came into

needed.

being in 1996 as a measure to prevent

construction is to occur right on the

unnecessary

boundary, the line of junction.

and

costly

litigation

One

is

where

new A

between neighbours when one of them

second is where the work is going to

did

interfere with the party wall or a wall

building

work

and

the

other

suffered damage. The

full

which might become a party wall.

procedure—this

shortened—involves

issuing

can

be

Notices

The third is where a trench is going to be

excavated

for

foundations

or


Issue 6 Page 2

HI Technical Bulletin © National Energy Services Ltd 2009

drains to such a depth that the bottom of the

occasions, be sufficient to "blow" the plaster

trench will be below the foundations of a

off the opposite side of the wall, particularly if

structure, which is within 3 metres, or in

it is weakly adhered in the first place.

some cases 6 metres, on neighbouring land.

Without a record that the plaster is poorly

It is considered to be highly unlikely that the first circumstance would result from a repair this can be ignored for the purpose of this article.

likely circumstances that the HI may identify could be that underpinning is likely to be necessary to the building or that there is some severe defect regarding the drains, which will entail the excavation of a deep trench.

Going up to the top of the building, there is the other common feature of the need to introduce

an

adequate

support

for

the

remnant of a chimney breast. Here we have one of the perennial problems of whether this is a defect or a deficiency, but we are not Suffice

Rating

both

consideration, there is adequate evidence of

Protocol—

a defect in the support of the chimney above

that

will

be

applied. the

SAVA

In

identified as CR3 on several grounds: the seriousness of the defect, the likely cost

costs sufficiently

Remember that if the party wall is only

½-brick thick the likelihood of damage is

here to discuss this particular conundrum.

the condition rating will have already been

raise overall

wall.

The HI needs to think about the Condition circumstances—using

procedure might

paying for re-plastering both sides of the

even greater.

Taking the last situation first, two of the most

“The PWA

attached to the wall, the client may finish up

related to the reinstatement cost, and the need to call for further investigation (the home inspection being non-invasive).

The

probable need to involve PWA procedure simply

exacerbates

the

cost

and

the

to

say

that,

in the

case

under

the roof line. The HI's decision is that support is required and because of the design of the house, the only acceptable route is the introduction of a pair of gallows brackets with an intervening beam.

This will need PWA notices because

the action will interfere with the party wall and may place a strain on it. It is not

to cause the

likelihood of CR3 rating is confirmed.

repair to be

CR2 and the PWA

thick

brought from a

What we must consider in greater detail are

damage.

CR2 into a CR3.”

the ramifications of repairs which involve a

There is also the common discovery of a lack

uncommon for the wall to be only ½-brick

part of the building which could be deemed under the PWA as being a party structure or may be sufficiently close to a party structure that the PWA may apply. These repairs may appear minor and, when the SAVA Protocol is applied, only attract a CR2 but the Home Inspector must bear in mind that the costs of the PWA procedure might be such that the

creating

an

even

greater

risk

of

of a firebreak in the loft between the two properties.

Again, as the party wall will be

"interfered

with"

the

PWA

procedure

is

required. There are several places externally where repair of defects must give rise to the anticipation of the necessity of providing PWA notices.

overall costs are raised sufficiently to cause the repair to be brought into a CR3. Let us take, as an example, the very common occurrence of a defective damp proof course, which is likely to result in a chemical barrier being introduced.

If this affects the party

wall, both properties will need the treatment, but there may be circumstances where the neighbour will either be unwilling to partake in a joint operation or consider that any dampness is not causing any discomfort or unsightliness on their side.

They may even

consider that they have had satisfactory treatment

previously

and

are

not

now

affected by rising dampness. It should be noted that, by the mere act of injection,

the

pressure

injected

can,

on

Chimney support

Keeping with the theme of chimneys, another example is that of a badly pointed chimney stack where repair to one half may result in


Issue 6 Page 3

Issue 6 February 2009

the dislodgement of the brickwork of the

If there is a parapet wall between the two

other half.

Clearly, if this occurs, the client

properties and a flashing is dressed into it,

will have to meet the costs for the repair of

this amounts to disturbance of the party wall

the neighbours' side and it is essential that

and the process is preferable to avoid the risk

adequate records are provided.

of later litigation. Therefore, we can see that what might on the face of it be quite minor, though advisable repairs, can considerably increase the cost can by virtue of reference to the PWA.

What are these costs? First of all there is the cost of the initial notices;

sometimes

if

the

neighbour

is

prepared to "play ball" the matter may go no further. If however, there is some resistance from the neighbour the full procedure of the PWA will come into play.

Fire break missing

Similarly, where flashings around a chimney are defective, if the replacement runs the possibility of disturbing the flashings of the other half of the chimney care should be taken.

In both of these cases, the HI may

have determined that the defect warrants a CR2; but may rise to a CR3 if the possible involvement

of

the

This involves the

neighbour appointing a surveyor—it might be

PWA

gives

rise

to

significant additional costs.

the same one that the client appoints but can be another, a Schedule of Condition has be drawn up after an inspection of relevant parts of the neighbour's property, and a document called an ‗Award‘ has to be agreed on and ‗published‘ to each of the parties. Imagine if there is a terraced house and a new roof is required, the procedures of the PWA are likely to apply to both neighbours, increasing costs commensurately.

“Costs can increase considerably by virtue of

Cost can vary considerably, but if there is the necessity to follow the full procedures under the PWA, there can be a charge of around £750 from the surveyor appointed by your client for each neighbour he has to deal with and

this

is

frequently

doubled

by

the

surveyor appointed by the neighbour, even if it is the same surveyor. Chimney stack

On the exterior of roofs, where the HI has identified a defect to a roof which might involve considerable repair, it is highly likely

For example the cost for the replacement of a flat roof covering, which might be estimated at about £1500, could easily double if these procedures are necessary, or even triple if the work goes across boundary to boundary

that the repair will involve working on the

and notices are required to two parties.

party wall.

Finally, how does the HI deal with informing the client?

This can be done by adding a

short sentence to each related section of the report

(e.g.

"This

repair

may

involve

procedures under the Party Wall etc. Act 1996.") or by adding a similar general note to the report or your covering letter in the case of the HCS (e.g. "Some of the repairs identified in this report may give rise to procedures under the Party Wall etc. Act 1996.").

The danger of using the former is

that you might miss a specific example where Cutting flashing into parapet wall

the party act will apply and get a complaint – or worse.

reference to the PWA.”


Issue 6 Page 4

HI Technical Bulletin © National Energy Services Ltd 2009

Do you agree with the Inspector? There were a number of small localised damp

or lifting of the wall paper and no smell of

patches found at the property:

damp in the room. As mentioned above, the cause could be due to the lack of the drying

Bedrooms 2 and 3 Bedroom 3 had a small (300mm² or so) patch to the external gable wall at skirting

effect (these patches also faced north-west), or it could be due to condensation.

level. This had caused a small section of wall paper to lift.

High readings on stained area

Bathroom

This month’s case

There was a small patch of damp in the

Bedroom 3 small patch of damp and

study focuses on

bathroom.

slight lifting of wall paper

the interpretation of moisture meter readings and the consequent

This wall was rendered externally, but the render was in very good condition with no cracks visible.

There was also a projecting

string course which would retain water; but

derivation of

as this is lower down the wall, and there are

condition ratings.

no signs of damp to the corresponding area

It was submitted by Steve Pierpoit, DipHI.

This was located at high level

adjacent to the boiler cupboard and there

of the internal wall (bedroom 2), it seemed unlikely to be the cause. The damp patch in bedroom 2 was similar in that it was about the same size and located at skirting level. There was no staining to the paintwork and no smell of damp in the room.

was visible staining of the paint surface. The moisture meter readings peaked at the edge of the staining, so the HI concluded that there were salts being deposited.

This

section of wall was located roughly beneath the valley gutter to the cross gable. This was inspected from the outside and in the roof space and no evidence of water penetration was found. This dampness may be the result of a past leak to the valley gutter.

The

hygroscopic salts are extracting moisture from the air and will continue to do, so spoiling any redecoration.

These sections of wall faced north-west and would get little sun in winter, so perhaps it was the lack of drying effect that was the cause. Alternatively it could be condensation, as the owners do not fully heat the house if they are going out for the day and the damp patches were located in areas of limited airflow, i.e. low down and surrounded by furniture and stored items.

Bedroom 1: Two small patches of damp were found: the first is at high level inside the fitted cupboard—this is an external wall.

The

second patch is at waist height in the north-west corner. The HI ruled out the poor quality brickwork to the bricked up window as the cause, because if this was the cause the damp would be likely to be more

wide

spread;

it

also

did

not

correspond to the location of the patch. There was no staining to the paintwork High readings on stained area

Splash-back from RWP

Kitchen This small section below the window, which was an exterior

wall, had visible damp

staining and high readings to the edges where salts were being deposited.

There

were a number of possible causes that the HI checked externally.


Issue 6 Page 5

Issue 6 February 2009

The brickwork repairs beneath the sill – these

bathroom and kitchen walls which will need

were sound with no open joints or cracks to

to have small sections of plaster removed (to

the mortar beds.

remove the salts) and patch repairs to these

The nearby soil pipe was

not damaged or leaking.

This only left the

guttering arrangement for the lean-to, which may not have coped with the rainfall as this was South-West facing.

areas.

My

condition

rating

for

the

internal walls follows this path: For bathroom and kitchen walls

Living room and dining room The damp patches to these rooms were very localised: in one corner of the living room and two small patches to the dining room. ‗

A – No hazard is present, i.e. the plaster work is not loose or dangerous J – A repair is required L – The repairs are not cosmetic/minor, i.e.

Conclusions

the damp areas will need patch repairs to

In the absence of any definite/cast iron

remove the salts before redecoration can

causes for the areas of damp outlined above,

take place

The HI will need to recommend further

N – The defect is not serious, would not be at

investigations by an independent suitably

considerable cost and are not detrimental

qualified person. This is necessary to exclude

to the structure – FI is needed for damp

the possibility that the damp is caused by condensation and to prevent money being wasted on unnecessary remedial treatments or repairs.

Carbide meter testing or deep

wall probes and salts analysis of the affected areas will be required and this is not possible under the terms of engagement for a Home Condition Report. The damp will be included in section E9 (dampness). Condition

Rating

of

Therefore a CR3 —Further

not for the condition of the walls O – The defect is not likely to develop rapidly or to cause structural failure R – This path delivers a CR 2 rating For all other walls A – No hazard is present, i.e. the plaster work is not loose or dangerous

Do you agree with the Home

J – A repair is required

Inspector?

L – The repairs are cosmetic/minor, i.e. the

Contact the

Investigations will be entered in Section

damp areas should dry out OK when the

Editor with your

E9 —Dampness.

source of moisture is eliminated and then

views and

redecoration can take place as part of For the condition ratings of the internal walls the HI will need to be balanced and not let the relatively small areas of damp found

ongoing maintenance. They are not so severe that re-plastering is required M – The defect is not impairing the

unduly affect the condition rating of these

performance of the building i.e. it is the

elements in a disproportionate way.

source of damp that is doing this not the

The

patches are small, and once the source of moisture is eliminated, these should redecorate OK, with the exception of the

condition of the internal walls. This path delivers a CR 1 rating

Inside partitions—room in the roof: The internal partitions of the bedroom located in the roof room are of timber constructions and are finished with laminated boarding.

E 3. Inside walls, Partitions &

2

plasterwork

The internal partitions to the bedroom located in the roof room are distorted. Some repairs or replacements are required but these are not considered serious or urgent. Inside walls & plasterwork—bathroom and kitchen: The internal walls to the bathroom and kitchen are of solid construction finished with plaster. The internal walls to the bathroom and kitchen are damp. Some repairs or replacements are required but these are not considered serous or urgent.

Rating

Description. Justification for Rating & Comments There is evidence of dampness in the property.

E 9. Dampness

3

Dampness is affecting small sections of the internal walls in the bedrooms, bathroom, living room, dining room and kitchen. The cause of the dampness cold not be definitively identified within the terms of engagement of this report. This is considered serious and in need of further investigations [see repairs and further investigations, Section B8].

opinions.


Issue 6 Page 6

HI Technical Bulletin Š National Energy Services Ltd 2009

Some thoughts on pitched roofs Home Inspectors should be familiar with

correct erection and fixing procedures on site

different types of pitched roof construction.

under competent supervision.

The roof structure of pre-1960s houses will generally

comprise

rafters

supported

on

purlins; the purlins either being strutted down onto load-bearing walls or, for larger roofs, supported on trusses (see Figure 1). The rafters are commonly 50mm x 100mm at about 450mm – 600mm centres, with purlins varying in size according to span and roof

Trussed

rafters

normally

span

between

external load-bearing walls without the need for

intermediate

supporting

walls,

but

adequate bracing of the whole roof and satisfactory connections to the supporting structure are essential to ensure overall stability.

type, but usually in the range of 75mm x

Permanent bracing ensures that wind forces

150mm up to 100mm x 250mm. Older roofs

do not impair the stability of the roof. This is

were often covered in thin slates, often

particularly important on gable ended roofs

Welsh, which have a low self-weight, and the

(as opposed to a hip ended roof).

roof structure was designed to accept this

must the roof structure be stable under wind

load.

loads, but the gable ends must be prevented

When an older roof is recovered, it can be subjected to substantially higher loads from new tiles than from the original ones. This is particularly relevant when a slate roof is replaced with plain clay tiles or concrete interlocking

tiles,

which

can result in a doubling of the dead load. s tr uc tur e

that

performed before

has

satisfactorily

recovering

from being blow in under a positive wind pressure

or

being

sucked

negative wind pressure.

out

under

a

Up to 1973 the

significance of wind bracing was not always fully appreciated, so any property with a trussed rafter roof built before 1975 could be suspect. with

Fortunately, remedial work to deal

inadequate

bracing

is

not normally

expensive. Whilst trussed rafter roofs are economical

may

and cost effective, they do have limitations.

or

In a competitive market, they are designed to

sagging of the ridge after

the limit and thus do not allow for any

recovering.

Overloading

significant increase over the design loads.

may also manifest itself in

The loft space, for instance, can only be used

sagging

and

for light storage which should be placed on

sometimes

boarding supported on the ceiling ties and

roof spread. Conversely,

not on the plasterboard ceiling. Supports for

suffer

from

rafters,

Figure 1: Strutted purlin roof

A roof

Not only

dishing

purlins and

if a heavier roof is re-covered in a lighter

water

material such as artificial slates, there may

structure. High levels of insulation above the

not be sufficient self-weight to prevent uplift

ceiling joists create a 'cold' roof in winter

under wind suction, leading to holding-down

which

straps being required.

vapour barrier is incorporated at ceiling level

Roof

construction

normally

in

comprises

post-1960s lightweight

houses trussed

rafters at 600mm centres (see Figure 2). The rafters

are

fabricated

from

38mm

thick

timber members fastened together in one plane

with

metal

tanks

can

the

introduction

Regulations).

tiling battens and the ceilings of

providing separate ceiling joists, purlins or ridgeboard. be

emphasised

rafters

are

components satisfactory

that

It should trussed

engineered and

performance

thus can

only be ensured by adopting

unless

the

a

of

Figure 2: Trussed rafter roof

the

1985

Building

Cold water pipes can freeze

unless well insulated.

connectors,

necessity

condensation

into

is particularly relevant for houses built before

rafters provide support for the the

cause

engineered

and ventilation is provided at the eaves (this

normally nailplates. The trussed

without

are


Issue 6 Page 7

Issue 6 February 2009

It is important that HIs are aware of these

The hazards created by this process are

issues

clearly severe, leading to the possibility of

when

Overloading

inspecting of

older

roof

roof

structures.

structures

by

heavier replacement roof coverings is not an uncommon problem, and if HIs come across this situation, they should check whether the

the collapse of the roof. Compiled from Fact Sheets written by Rodney Higgins.

roof structure has been strengthened. If the

References: BS 5268-3:1998 Structural Use

roof structure is showing signs of distress,

of Timber Part 3: Code of practice for trussed

then clearly it must be reported. Overloading

rafter roofs.

of the ceiling structure by excessive storage, especially with trussed rafter roofs, does also happen and again should be reported.

The Trussed Rafter Association: www.tra.org.uk/.

It is also not unknown for the internal bracing of trussed rafters to be partially or completely removed to create loft space without the roof structure being appropriately strengthened.

Notes/record of inspection—important reminder In times of depreciating property values,

surveyors have forgotten this, or, if they

there is a much greater risk of a home owner

trained with another provider, the mantra

casting around to see if any blame for the

was not drummed into them in the first place.

“The Home

downturn in the value of their home can be

However, the subject is so important, that we

laid anywhere else. Therefore, if ever Home

make no apology for returning to the subject

Inspector

Inspectors

were

here

obligation

to

in

any

doubt

of

their

in

the

technical

bulletin.

Home

needs to make

notes,

Inspectors need to be aware of their liabilities

complete and

including the clear recording of all moisture

in carrying out residential inspections and

meter readings, now is the time to re-assess

must understand how much detail they need

comprehensive

inspection practices.

to record

make

reasonable

This obligation is unequivocally covered in the National Occupational Standards for Home Inspectors.

Element 4.2 states clearly and

about the property and what

activities they have undertaken on site to

record his

verify the condition of the property at the

findings

date of inspection.

accurately”.

plainly that the Home Inspectors are to

Historically, within the surveying profession,

―Make

claims

complete

and

comprehensive

site

for

negligence

against

surveyors

notes‖ and need to ―Record [their] findings

relating to damp and timber defects are

accurately‖.

among the most common. Therefore, we are

The

point

Inspection

is

further

and

amplified

Reporting

in

the

Requirements,

which state that:

are the Home Inspectors’ proof that the inspection,

reflections

conclusions accordance

focussing

this

reminder

on

the

use

of

moisture meters. Fryer v Bunney (1982) is a court case that

“Site notes must be complete, as they

were with

and

technical

conducted the

in

Performance

Requirements.

demonstrates this very clearly and sets the precedent for how surveyors should behave when inspecting a property for the presence of damp. The case centred on the failure of the surveyor to identify the presence of damp in the property he had inspected.

Fryer

bought the property and in doing so relied on

Queries can be raised several months,

Bunney‘s report which did not mention the

even years, after the inspection, and

presence of damp. Subsequently, damp was

Home Inspectors should appreciate that

found in the property.

a good set of legible site notes, which can be interpreted by another Home Inspector, will be the best.”

Counsel for Fryer argued that the surveyor had been negligent in not taking moisture meter readings. Bunney‘s defence responded

Any surveyor who trained with SAVA, should

by arguing that not only had the surveyor

be familiar with the mantra of „record it in

taken moisture meter readings, but had

your site notes/record of inspection‟.

taken them at one metre centres to those

Unfortunately, during some recent audits, we

walls that were accessible, as is commonly

found

and accepted practice.

that

some

Home

Inspectors

and

site notes and


Issue 6 Page 8

HI Technical Bulletin © National Energy Services Ltd 2009

The defence was

indicate when the meter readings do not

unable to prove this except by the verbal

indicate the presence of damp and when

evidence of the surveyor, as the surveyor had

readings

suggest

made no corroborative notes at the time of

present.

In addition, because it is accepted

the inspection to support his defence.

practice that the moisture meter should be

But here is the point:

The case went against the surveyor because he could not prove, after the event, that he had taken moisture meter readings.

The

property may well have not been damp at the time of the inspection but he could not prove that. This tells us that it can be an expensive mistake not to record properly where all moisture meter readings have been taken. The best way to do this is by use of a simple sketch plan to indicate where the moisture

that

moisture

may

be

used at 1m intervals, the same sketch plan should also identify the position of any furniture or other obstructions that might prevent readings being taken to some parts of the walls (cupboards, sofas, radiators etc.). This is best supported by photographs. These are simple tasks, and while they might mean a little while longer on site, they are the kind of best practice that can save you a fortune in claims for negligence at a later date.

meter was used, and a simple code to

Last month‟s case study at

caused by the guttering leaking, and causing

defects of dampness and cracking in

splash-back onto the wall. I agree with the

walls and the use of cross-referencing in

rating, though D3 might have been a rating

the HCR to clarify the effects of these

of three.

Last

month‟s

case

study

looked

defects.

I would state such dampness as penetrating

The following comments were sent in by Neil Hewitt.

different type of defect, and requires a different remedial approach (if any).

D2: Flat roof—this is quite an interesting example, though it is clear cut, and it is hard to see how any rating could be less than three. It would be good some time to see an example that is more borderline e.g. clay tiles with lamination, or a slate roof that has slippage, but is not leaking. Plus of course, the classic concrete interlocking tiles on an older roof.

damp, not rising damp, which is a totally

There is also the health and

safety issue of the loose bricks on the flat roof.

D4 main walls—without full reference to the inspector‘s site notes, it is difficult to fully ascertain the type of movement. However, it does not look like a form of differential subsidence, but it may be due to thermal movement, perhaps the roof/structure of the extension. The danger is that under section B reference has been made to trees on clay subsoil. This may suggest to the lay person reading the HCR, that there is subsidence due to soil conditions.

E9 Dampness—the issue here is that the inspector has stated that rising damp is We welcome your feedback and comments. Please email: bulletins@nesltd.co.uk Registration Services : 01908 442 277 registration@nesltd.co.uk Compliance: 01908 442288 compliance@nesltd.co.uk Technical Support Helpdesk: 01908 442105 support@nesltd.co.uk Training enquiries: 01908 442254 training@nesltd.co.uk NES one Credit Top up line: 01908 442299 To download electronic copies of the bulletins, login to NES one and go to ‗Useful Documents‘ All original content © 2009 National Energy Services Ltd SAVA, The National Energy Centre Davy Avenue, Milton Keynes, MK5 8NA Web: www.sava.org.uk


Turn static files into dynamic content formats.