Page 1

Application Instruction

(foto)

Sealing of cable duct

(foto)


02-07-2013

APPLICATION INSTRUCTION

Outside

Duct to be sealed with a barrier, 2100 Aquastop and Stopaq Mortar FR or WR.

Basement side

Sealing of cable duct

2


1. 2. 3.

02-07-2013

Barrier Stopaq 2100 Aquastop, 100mm Mortar, 50mm FR = Flame retardant WR = Water resistant

APPLICATION INSTRUCTION

Outside

The complete system:

Basement side

Sealing of cable duct

3

2

50mm

100mm

1

3


Outside

Clean the duct with a brush, cleaning pad or similar equipment. Total length approx. 175mm. Rinse with clean water is allowed as 2100 Aquastop can be applied on a wet surface. Adhesion can be improved when pipe and duct are pre-applied with 2100 Aquastop.

Basement side

Sealing of cable duct

Âą175mm

02-07-2013

APPLICATION INSTRUCTION

4


Outside

Insert barrier at a depth of 150mm into the duct. Use a foam tape or, cloth to separate the cables from each other.

Basement side

Sealing of cable duct

150mm

02-07-2013

APPLICATION INSTRUCTION

5


Sealing of cable duct

Cables separated by foam tape

Cables separated by pre impregnated cloth 02-07-2013

APPLICATION INSTRUCTION

6


Sealing of cable duct Preheat the 2100 Aquastop up to a temperature 30째C. A bucket of water and a water heating coil can be used. STOPAQ

STOPAQ

STOPAQ

STOPAQ STOPAQ

STOPAQ

30째C

02-07-2013

APPLICATION INSTRUCTION

7


Outside

Apply 100mm of 2100 Aquastop without air enclosures. Work from inside out to prevent air-enclosures. Lift the cables and apply the 2100 Aquastop with an appropriate application gun around the cables. Clean the remaining 50mm of the duct prior to the installation of Mortar FR or WR.

Basement side

Sealing of cable duct

STOPAQ

STOPAQ

STOPAQ

STOPAQ

STOPAQ

STOPAQ

100mm

30째C

02-07-2013

APPLICATION INSTRUCTION

8


Sealing of cable duct Prepare Mortar WR to a mouldable mass. Mortar WR shall be used as a waterproofing barrier in wall inlets that frequently exposed to huge amounts of water. Mixing ratio by volume, mixing time 1 minute: 4 parts Mortar WR 1 part of Water. 1 min

Mortar WR

02-07-2013

Mortar WR

Mortar WR

Mortar WR

APPLICATION INSTRUCTION

H20

9


Sealing of cable duct Prepare Mortar FR to a mouldable mass. Mortar FR shall be used in fire rated walls and floors. Mixing ratio by weight, mixing time 3-5 minutes: 1 kg Mortar FR 0,6 – 0,8 litres of water Mixing ratio by volume, mixing time 3-5 minutes: 2 – 4 parts Mortar WR 1 part of Water. 0,6 – 0,8 litres H20

Mortar FR

02-07-2013

Mortar FR

Mortar FR

Mortar FR

H20

APPLICATION INSTRUCTION

3–5 min

1 kg Mortar FR

KG 10


Outside

Check the malleability of the Mortar by moulding the Mortar to a ball shape without it falling apart. Apply Mortar in the remaining 50mm of the duct. Start at the bottom between the cables. Smoothen the surface of the mortar by using a putty knife and some water.

Basement side

Sealing of cable duct

50mm

02-07-2013

APPLICATION INSTRUCTION

11


02-07-2013

APPLICATION INSTRUCTION

Outside

If an extra cable has to be put through the duct, first drill a hole with a larger diameter as the cable on the position where the cable has to go through.

Basement side

Sealing of cable duct

12


Outside

Insert the cable and inject 2100 Aquastop and apply Mortar WR or Mortar FR. Smoothen the surface with a putty knife. A cable can be removed with the same procedure; remove cable new 2100 Aquastop New mortar.

Basement side

Sealing of cable duct

STOPAQ

STOPAQ

STOPAQ

STOPAQ

STOPAQ

STOPAQ

30째C

02-07-2013

APPLICATION INSTRUCTION

13


Outside

Basement side

Sealing of cable duct

Note: Simplified representation of the application, Please check PDS, SDS, Scope of work for detailed product- and application descriptions. 02-07-2013

APPLICATION INSTRUCTION