Whole Building Simulation Design - Hyderabad

Page 1

Whole Building Simulation Design Hyderabad

Office Building Shubham Solanki

Whole Building Design Simulation

M.Tech Building Energy Performance | CEPT University

1


Project Detail Building type – Office building Location – Hyderabad Area – 1600 sq m

The aim of the study was to integrate the Climate study with Passive strategies, HVAC and lighting. The tools used were Design builder, Rhino-Grasshopper plugin- Ladybird + Honeybee, Light stanza. The project was documented in MS word and MS Powerepoint. MS Excel was used for visualization of the result.

2


Introduction The aim of the exercise is to design an energy efficient building. The process of the design is to reduce the load, reuse the energy (cool) and produce the renewable energy. It is an integrated design process. The design decision are taken considering energy, comfort and cost.

Summary The study was conducted to create a link between outdoor environment and occupant without compromising the occupant comfort. The aim to create the net zero energy building, using passive strategies and promoting comfort. The means of passive design studies such as climatic analysis, solar exposure, shading analysis,

daylight studies and thermal comfort studies for natural ventilation. The thumb rules were applied for daylighting and CIBSE tool was used to for natural ventilation for single side window. The fenestration were designed from thumb rule calculation. The shading were designed using shading mask and radiation analyses.

The second stage of design consist of optimization of modelling business as usual case, the elimination parametric simulation followed by sensitivity analysis

and HVAC optimization. There was reduction of 40% after the envelope optimization and further 22% reduction after HVAC optimization. The design case is compared with BAU and ECBC Case.

The Third Stage consist of energy generation. The total energy generated was 75,000 kWh. For the net zero energy building to be designed the EUI should be less than 55 kWh/ sqm. The design case building EUI is 44.78 kWh/sqm.

The forth and final stage of exercise is return on investment, which was calculated and thus resulted in ROI of 3.1 year.

Thus, the building is net positive in energy with ROI of 28% and payback 3.1

Shubham Solanki

Whole Building Design Simulation

M.Tech Building Energy Performance | CEPT University

3


Climate analysis Dry Bulb Temperature, Relative humidity, Solar radiation, UTCI It can be observes that highest temperature 43⁰c is in the month of April – June, the Relative temperature is as low as 7% during these months. The solar radiation is also maximum in these months. The lowest temperature is in the month of December – January, the

relative humidity is low even in these months. During the month of July-October higher humidity level up to 90% are observed. The

highest universal thermal climate index temperature lies in the month on April – May around 42.25⁰c.

Shubham Solanki

Whole Building Design Simulation

M.Tech Building Energy Performance | CEPT University

4


Climate analysis Wind Analysis and Diurnal variation Months March – June (Summer) July – October (Monsoon) November – February (Winter)

Predominant Direction West – Northwest West East - Southeast

Average Speed 2.8 m/s 2.0 m/s 1.18 m/s

The wind direction and speed is used to design fenestration design.

Figure 2 Wind Rose diagram- summer, monsoon, winter

It can be used to bring the immediate uncomfortable hour in the comfort zone.

The average variation thought out the year is 7-8⁰c.

In winter the temperature is 30 ⁰ c during day time but 15 ⁰ c during night time.

In summers the highest is 42 ⁰ c and at nigh the temperature lie in the range of 30-33 c. The diurnal variation are higher than 10 ⁰ c.

The difference is only 5 ⁰ c in monsoon months.

Shubham Solanki

Whole Building Design Simulation

M.Tech Building Energy Performance | CEPT University

5


Thermal Comfort Dry Bulb Temperature- Mix mode adaptive band

UTCI – Mix mode adaptive band

Legend

Legend

For Mix-Mode building = (0.28*outdoor temperature + 17.87) Âą3.46.

UTCI=f (Ta; Tmrt; Va; RH) , For outdoor Tmrt = Ta

Total number of comfortable hours are 4562

Total number of comfortable hours are 5092

Total number of comfortable hours for operational hours are 1100

Total number of comfortable hours for operational hours are 1488

Shubham Solanki

Whole Building Design Simulation

M.Tech Building Energy Performance | CEPT University

6


Thermal Comfort Dry Bulb Temperature + Relative humidity - Mix mode adaptive band Comfortable hours in percentage operational hours. 45⁰

40⁰ 35⁰ 30⁰ 25⁰ 20⁰ 15⁰ 10⁰ Total number of comfortable hours are 4068

5⁰

0

Total number of comfortable hours for operational hours are 1044

Shubham Solanki

Whole Building Design Simulation

Legend

M.Tech Building Energy Performance | CEPT University

7


Thermal Comfort Conclusion

Shubham Solanki

Whole Building Design Simulation

M.Tech Building Energy Performance | CEPT University

8


Window to wall ratio Daylight

Second Floor Ground Floor

Natural Ventilation – CIBSE Tool for 15 ACH at 0.25 discharge coefficient.

First Floor Whole Building Design Simulation Shubham Solanki

M.Tech Building Energy Performance | CEPT University

9


Window to wall ratio

The window size is reduced for each wall. The reduction for is up to 100%. The daylight penetration for both the case is same using the thumb rule. The reduction in WWR will help in reduction of solar heat gain which will reduce the cooling load of the building.

35% 30% 25% 20% 15% 10% 5%

Legend

Shubham Solanki

Whole Building Design Simulation

M.Tech Building Energy Performance | CEPT University

10


Solar radiation

Temperature > 30â °c Solar radiation > 300 Wh/ sqm Annual Solar radiation The Annual Solar radiation and Dry bulb temperature. The total solar radiation is up to 64 kWh/ sq. m in the south direction. The Direct solar radiation will be used to calculate the solar potential for generating the energy. The solar radiation in summer months is upto 51 kWh/ sqm. The temperature is around 31-34â °c in late evenings. The shading device is designed using the solar radiation and dry bulb temperature. The shading mask is designed for temperature above 30â °c and Radiation above 300 Wh/ sqm.

Shading mask

East

South

North

West

11


Daylight Floor

Target

UDI Occupancy: 9:00 AM - 5:00 PM Sky Type: Climate-based Lower Bound: 100 lux Upper Bound: 2000 lux Time Threshold: 90% 65% of floor area meeting the UDI requirement

Daylighting ASE

DA

Occupancy: 9:00 AM - 5:00 PM Sky Type: Climate-based Time Threshold: 250% and 100%

Occupancy: 9:00 AM - 5:00 PM Sky Type: Climate-based Illuminance target - 200 Lux

<1% floor area for 250 hour and <2% for 100 hour

>75% DA 200

Ground floor

UDI - 82.11%

ASE 250 hour - 0.22 ASE 100 hour - 0.62%

DA - 72% 200 Lux

UDI - 75%

ASE 250 hour - 1 ASE 100 hour - 1.7%

DA - 58% 200 Lux

UDI - 78.8%

ASE 250 hour - 0.95% ASE 100 hour - 1.6%

DA - 70% 200 Lux

First floor

Second floor

12


Passive Strategies Passive Cooling Strategies Thermal Mass

Natural ventilation

Nocturnal Cooling

Ground Cooling

Envelope

Air Tightness

Shading

Goal Parameter

Diurinal Temperature, Heat gains Summer-High Diurnal variation

Dry Bulb Temperature, Wind Speed, Relative Humidity

Diurnal Temperature, Relative humidity

Ground Temperature at 1m 2m and 4m depth Outdoor Dry bulb temperature Diurnal variation with 10⁰c The ground is with in adaptive band. If DBT difference will be temperature throught is higher than hours with high out the year are 4-6⁰ wind speed will be used c less than the ambient temperature. Throughtout the year Summer, Monsoon Not possible because Higher wind speed with The night temprature for the Ground immediation DBT above Monsoon and March and temperature and comfort band air will also be June summers night ambient temrpeture used to naturally ventilate the temperature lies in is less than 10⁰c . space. comfort band.

Solar radiation and Heat gains and surface temperature Reduces the heat gains, Block heat transfer

Infiltration, ACH

Higher the Diurnal Temperature, More the thermal mass helps

Higher Wind speed can be used to increase the comfortable hours in monsoon and summer. The IAQ plays an important role.

The insects and dust is a problem for indian climate.

It depends on the capital cost and Savings after the simulation results.

Increase the air It is not possible to tighness of the obstruct 100% west envelope, Difficult to sun. implement due to in-situ construction.

Increase of Wall thickness with Lower conductivity

Scheduling of the windows and use of Natural ventilation the DBT and RH is in comfortable zone

The use of night ventilation with scheduling and sensors for operation of the windows.

Reduction in Uvalue using the sensivity study and cost analysis

Design and Air tight building also analysisng the cost and energy reduction

Throughtout the year Duration

SWOT

Result

Shubham Solanki

Whole Building Design Simulation

N/A

Direct solar radiation and Temperature Higher temperature The solar radiation of outside air will higher than 300Wh/ increase the load in sqm and the building temperature higher than 30⁰c will be cut. Throughout the year Summer, Winter will Throught the year The change in U value increase the sensible 9am morning sun will help in reduction load, and winter late in energy Monsoon -Sensible + evening sun is consumption Latent Load difficult to cut.

Designing Shading mask and shading device accoring to the results.

M.Tech Building Energy Performance | CEPT University

13


Base Case Business as usual Parameter

Envelope

Building details

HVAC Specs

Input Parameter

Value

Wall U (external) Roof U Glass U Glass SHGC Glass VLT WWR Shading Occupant Density Lighting power density

2.5 W/m2K 3.2 W/m2K 5.8 W/m2K 0.88 50 As/ Arch dwg. As/ Arch dwg. Space wise calculation (Refer Appendix) Space wise calculation as/ ECBC (Refer Appendix) Space wise calculation with 1 Star rated appliance (Refer Appendix) As per ECBC & Building use (Refer Appendix) .0025m3/ person + .0003 m2/m2 Packaged terminal Air-Conditioner (PTAC) 3.2

Electric power density Building Schedules Fresh air System type COP

Monthly Load Distribution

Legend

Shubham Solanki

Whole Building Design Simulation

M.Tech Building Energy Performance | CEPT University

14


Elimination Parameter Roof

Window

BAU Case

Wall

BAU U val - 2.3

Wall Uval-0.01

Roof Uval-0.01

Roof SRI95%

Window Uval-0.01

Cooling Load 67266.04 Cooling EUI 65.6 % reduction N/A Energy end use (kWh) 144907 EUI (kWh/ sq m) 111.5 % reduction N/A Sensible Load 105 Latent Load 30 Peak cooling load (kW) 149 Percentage reduction N/A

66201 64.6 1.6 141771.0 109.1 2.2 120.6 26 169 -13.4

60601 59.1 9.9 136098.2 104.7 6.1 94.0 22 134 10.1

48642 47.5 27.7 122567.4 94.3 15.4 85.0 22 121 18.8

55813 54.5 17.0 133310.7 102.5 8.0 90.0 23 130.8 12.2

Window SHGC 0.01 42908 41.9 36.2 120019.2 92.3 17.2 88.0 21 126 15.4

Window Section

Shading

Fresh Air

Active Cooling

Electric lighting

64674 63.1 3.9 139600.5 107.4 3.7 90.0 22 131 12.1

54208 52.9 19.4 128301.6 98.7 11.5 60.0 16 83 44.3

47151 46.0 29.9 121057.9 93.1 16.5 45.0 30 92 38.3

0 0.0 100.0 72547.1 55.8 49.9 73.0 19 105 29.5

56593 55.2 15.9 95574.4 73.5 34.0 54.0 15 80 46.3

120.0

170

100.0

EUI (kWh/ sqm)

The strategies with highest reduction were roof U-value, roof solar reflectance index, windows solar heat gain coefficient, shading, air tightness, daylighting and natural ventilation.

150

80.0

130

60.0

110

40.0

90

20.0

70

0.0

Peak Cooling Load (kW)

Parameters

50 BAU U val - 2.3

Wall Uval-0.01

Roof Uval-0.01

Roof SRI95%

Window Uval-0.01

EUI (kWh/ sq m)

Window SHGC 0.01

Window Section

Shading

Fresh Air

Active Cooling

Electric lighting

Peak cooling load (kW)

Note - The peak cooling load is simulated keeping Operative temperature as set point where as energy simulation is based on air temperature

Shubham Solanki

Whole Building Design Simulation

M.Tech Building Energy Performance | CEPT University

15


Sensitivity analysis

0.2

95

3Star

Legend

Source – imimg.comt

The roof of U value – 0.2 was used for further analysis. The reduction of 6% was noted in cooling EUI and reduction of 2.7% in peak cooling load.

Shubham Solanki

The material of SRI - 95% was used on the roof. The reduction of 19.8% was in cooling EUI and reduction of 14% in peak cooling load.

Whole Building Design Simulation

The Super ECBC LPD shows the reduction of 5% in cooling EUI and 8% in peak cooling load.

M.Tech Building Energy Performance | CEPT University

16


Sensitivity analysis

0.75

Legend

0.35

0.15

Source- saint gobain faรงade glass

Source- Slide share/ Shengxi's Portfolio

Highest Reduction in terms of cooling EUI and peak cooling was noted in shading windows and shading roof and both the strategies were used in further analysis. The roof was shaded with solar structure.

Shubham Solanki

0.55

There was 11% Reduction in cooling EUI and 6.5% reduction peak cooling, but the glass specification is also dependant on VLT.

Whole Building Design Simulation

The 5star appliances showed the reduction of 23% in cooling EUI and 5 % in peak cooling load.

M.Tech Building Energy Performance | CEPT University

17


Energy Conservation Measures Glass Optimization Saint Gobain Glass - Performance of Glasses

1.Window Shading – From the shading mask Sno Shading

Colour (70%) Shade

2.Roof photovoltaic cells to shade Neutral

1 Royale Blue 3.Roof SRI 2– Cool Roof Misty Blue reflectance 395% Turquoise 4 Blue Ray

Light Factors

– Brand Using

Code Sno

DGU/SGU Antelio Plus SGU with solar DGU Nano Cool-lite SGU Cool-lite DGU

ST1750 KT2755 ST3436 ST4767

Light SolarFactors Radiation

Colour Transmission Reflection Brand Shade Neutral Royale33 Blue Misty Blue 33 Turquoise 30 Blue Ray 39

External Antelio 10 Plus Nano 10 Cool-lite16 Cool-lite12

Saint Gobain Glass - Performance of Glasses

Code UV DGU/SGU Internal SGU 16 DGU 9 SGU 18 DGU 22

ST11 750 KT 8755 ST 436 8 ST12 767

Solar Radiation

Shading Solar Relative Solar Transmission Reflectance Reflection Absorbtion UV Transmission coReflectance U value Absorbtion Rate Factor Heat Gain Factor efficient 33 25 33 18 30 17 39 28

External 10 8 10 10 16 10 12 9

Internal 1667 9 72 1873 2263

SF 110.42 8 0.25 8 0.35 120.37

SC 25 0.49 18 0.29 17 0.41 28 0.43

W/ sqm K W/ Sqm 5.6 8 365 67 1.810 212 72 5.5210 319 73 2.8 9 306 63

4.Roof U-value – Ceramic Tile + Plaster + XPS(110mm) + Concrete Slab (125mm) + Cement Plaster 5.Window SHGC (Solar Gains) + VLT (Daylight) – 0.35 SHGC, 0.3 VLT Coollite Saint Gobain 6.Electric Lighting – Super ECBC Lighting power density 7.Equipment – 5 star

8.Variable Set Point- According to NBC Mix mode Band

Variable Set point

9.Nocturnal Cooling – 9pm to 7am 10.Natural Ventilation

Shubham Solanki

Whole Building Design Simulation

M.Tech Building Energy Performance | CEPT University

18

Rs/sqm S F 2288.54 0.42 3567.43 0.25 2288.54 0.35 2288.54 0.37


BAU Case

Shading Device

Shading Roof

Roof SRI

Roof Insulation

Glazing

Appliance

Electric lighting

Variable Set Point

Nocturnal Cooling

140.00

100.00

System Efficiency – 32%

Building Envelope -19%

90.00

120.00 80.00

70.00 60.00

80.00

50.00 60.00

40.00

30.00

40.00

20.00 20.00 10.00 0.00

0.00

EUI – 117 kWh/ sqm

Shading Mask

EUI (kWh/ sq m)

Solar PV 70% covered

Cool Roof 95% Reflectance

U- 0.2 XPS- 110mm

Cooling EUI % reduction

SHGC –0.35 VLT- 30%

Super ECBC

BEE - 5 Star

Peak cooling load % reduction

NBC MM Adaptive Band

Throughout year

Incremental cost Increase

19

Percentage

EUI (kWh/sqm)

100.00


Monthly Load Reduction

Legend

Overall 40% of load reduction

Shubham Solanki

Monthly Load Distribution

Whole Building Design Simulation

M.Tech Building Energy Performance | CEPT University

20


Com

HVAC Optimization – Natural Ventilation

Uncomfortable

9 11 1 3 5 7 January

February

March

April

May

June

July

August

September

October

November

December

November

December

The total number of comfortable hours during operational hours using Natural ventilation are 420. 9

Time

11 1 3 5 7 January

February

March

April

May

June

July

August

September

October

The total number of comfortable hours during operational hours using ceiling fan assisted ventilation are 1070. the increase is by 1.5 times 9 11 1 3

5 7 January

February

March

April

May

June

July

August

September

October

The total number of comfortable hours during operational hours using Evaporative cooler are 1222.

November

DEC 21


HVAC Optimization – VRF

Scheduling according the assisted ceiling fan ventilation. The VRF will function in the months of 2nd half of February till 1st week of November. The morning hours from 9- 11th in the month of March, July and August the operative hours are in comfortable band, the VRF wont be Functioning in those hours.

55%

60%

62%

The reduction is final proposed case is 62% with reference to BAU case, set point as NBC adaptive Band. VRF specification

80%

83%

86%

COP – 3.3 Company – Trane – 20 ton 4TV Compressor – SSC Scroll Indoor Units connection – 41 Refrigerant – 410A

Shubham Solanki

Whole Building Design Simulation

M.Tech Building Energy Performance | CEPT University

22


BAU Case Shading Device

Shading Roof

Roof SRI

Roof Insulation

Glazing

Electric lighting

Appliance Variable Nocturnal Set Point Cooling

VRF

VRF + NV Variable Set Point

140.00

100.00

Building Envelope -19%

Scheduling and System Efficiency – 32 + 11%% 90.00

120.00 80.00

70.00 60.00

80.00

50.00 60.00

40.00

30.00

40.00

20.00 20.00

10.00 0.00

0.00 EUI – 117 kWh/ sqm

Shading Mask

Solar PV 70% covered

EUI (kWh/ sq m)

Shubham Solanki

Cool Roof 95% Reflectance

U- 0.2 XPS- 110mm

SHGC –0.35 VLT- 30%

Super ECBC

Cooling EUI % reduction

Whole Building Design Simulation

BEE - 5 Star

NBC MM Adaptive Band

Throughout year

Peak cooling load % reduction

Trane 20 ton

Winter Cooling Off

Incremental cost % Increase

M.Tech Building Energy Performance | CEPT University

23

Percentage

EUI (kWh/sqm)

100.00


Comparison

45%

62%

80%

85%

ROI BAU Proposed ECBC Case Total Cost of Construction ₹ 1,65,54,240.00 ₹ 1,94,96,690.00 ₹ 1,96,18,125.00 Incremental Cost NA ₹ 29,42,450.00 ₹ 30,63,885.00 %Increase in Cost 0 17.77% 18.51% Total Energy Cost/year 153025.58 58219 85800 Annual Saving NA 948065.8 672255.8 ROI NA 32.22% 21.94% Payback NA 3.1 4.6

Shubham Solanki

Whole Building Design Simulation

M.Tech Building Energy Performance | CEPT University

24


Solar Generation

Sno 1 2 3 4 5

Solar Renewable Calculation Name Total Built-up area Maximum area available for installing solar PVs (roof+surface parking) Installed capacity of solar PVs as per available area Potential energy generated annually as per installed capacity (@ 1500kWh energy generated annually per 1kWp of installed capacity) Target Energy Performance Index for Project to be Net-Zero

Quantity Units 1,300 sq.m 439 sq.m 44 kWp 62,390 kWh 48 kWh/m2/yr

Thus, the Building is Net positive with ROI of 3.1

Shubham Solanki

Whole Building Design Simulation

M.Tech Building Energy Performance | CEPT University

25


Limitation There is scope of the energy reduction. The sensors are not used in the project. If 100 utilization of naturally ventilated hours is possible with use of sensors and BMS, but BMS capital cost is high. The natural ventilation hasn't been utilised to fullest.

The scope of optimization of VRF with different curve is possible. The different cooling system like radiant-chill ceiling, which is possible to have high efficiency in this climate hasnet been studied.

LCCA of the project is not complete to give a better result for the costing.

Shubham Solanki

Whole Building Design Simulation

M.Tech Building Energy Performance | CEPT University

26


Thank You shubham.pg180982@gmail.com

27


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.