Carrier poluprom fmcc sm 2010

Page 1

Content

Part 1 General Information .................................................................................................. 1 Part 2 Indoor Units ............................................................................................................... 8 Part 3 Outdoor Units ........................................................................................................ 100 Part 4 Installation.............................................................................................................. 132 Part 5 Control.................................................................................................................... 143

※The specifications, designs, and information in this book are subject to change without notice for product improvement. Contents

i



MLCAC-UTSM-2010-10

General Information

Part 1 General Information 1. Model Names of Indoor/Outdoor Units ...........................2 2. External Appearance ........................................................3 2.1 Indoor Units ................................................................................. 3 2.2 Outdoor Units .............................................................................. 4

3. Nomenclature ....................................................................5 4. Features .............................................................................7

General Information

1


Model Names of Indoor/Outdoor Units

MLCAC-UTSM-2010-10

1. Model Names of Indoor/Outdoor Units 1.1 Indoor Units R410A (capacity multiplied by 1000Btu/h) Type Four-way cassette ( t) Four-way cassette

Function

18

Cooling and heating

Cooling and heating

Ceiling & floor

Cooling and heating

Duct

Cooling and heating

24

36

48

60

1.2 Outdoor Units Model of outdoor unit and corresponding indoor unit Universal Outdoor unit Model Heat Pump

2

Compressor type

Compressor Brand

38HN0181120A

Rotary

GMCC

38HN0241120A

Rotary

GMCC

38HN0361120A

SCROLL

SANYO

38HN0481190A

SCROLL

SANYO

38HN0601190A

SCROLL

SANYO

Matched indoor units 42TLH0181001201 42FLH0181001201 42TNH0241001201 42FLH0241001201 42SMH0241011201 42TNH0361001201 42FLH0361001201 42SMH0361011201 42TNH0481001901 42FLH0481001901 42SMH0481011901 42FLH0601001901 42SMH0601011901

General Information



External Appearance

MLCAC-UTSM-2010-10

2.2 Outdoor Units 38HN0181120A

38HN0361120A

4

38HN0241120A

38HN0481190A~38HN0601190A

General Information


MLCAC-UTSM-2010-10

Nomenclature

3. Nomenclature 3.1 Indoor Unit DIGIT NO. CODE 1,2 Product Series Number 42: Central Station air handling unit-Packaged 3,4,5 Product Series Number SH/SM/SLH : Ducted for heat pump TN/TL/TSH : Cassette for heat pump FLH : Ceiling floor for cooling only and heat pump 6,7,8 Capacity The units(KW, BTUH,KCAL) should be defined in the business unit's model numbering policy, and depend on the product type and size 9 1: R410a Refrigerant 10 Option 0: Standard unit 11 Control 0: Wireless remote controller 1: Wired room controller 12 Market 1: For 50Hz market 13 Electrical characteristics 2: 220/240V-1PH-50HZ 9: 380V-3PH-50Hz 14 Model revision code 0: Original without revision 15 Environmental temperature 1:Temperate,T1

General Information

1

2

3

4

5

6

7

8

9 10 11 12 13 14 15

4 2 F L C 0 2 4 1 0 0 1 2 0 1

5


Nomenclature

MLCAC-UTSM-2010-10

3.2 Outdoor Unit DIGIT NO. CODE 1,2 Product Series Number 38: Condensing Unit (CDU)

1

2

3

4

5

6

7

8

9

10

11

12

3

8

H

N

0

2

4

1

1

2

0

A

3,4 Product Series Number HN: H: heat pump; N: universal CDU, for heat pump 5,6,7 Capacity The units(KW, BTUH,KCAL) should be defined in the business unit's model numbering policy, and depend on the product type and size 8 1: R410a Refrigerant 9 Market 1: For 50Hz market 10 Electrical characteristics 2: 220/240V-1PH-50HZ 9: 380V-3PH-50Hz 11 Model revision code 0: Original without revision 12 Product Discharge Number A:Side discharge,T1

6

General Information


MLCAC-UTSM-2010-10

Features

4. Features 4.1 High quality coils: The coil is constructed of advanced inner grooved copper tube and aluminum fins.

4.2 Anti-rust, 500 hours salt spray test. 4.3 Low operation sound level: Well-known stable and quiet running fan motor. 4.4 Well-known compressor. 4.5 Compact design: Smaller dimension and larger stuffing capacity. 4.6 Universal outdoor unit design. 4.7 Optional air outlet grille: plastic type and wire type.

Wire type

Plastic type

Plastic type

4.8 Optional low temperature cooling module. 4.9 R410A environment friendly refrigerant.

General Information

7


Indoor Units

MLCAC-UTSM-2010-10

Part 2 Indoor Units Four-way Cassette Type (Compact) ....................................9 Four-way Cassette Type .....................................................19 Ceiling & Floor Type ...........................................................35 Duct Type .............................................................................56

8

Indoor Units


MLCAC-UTSM-2010-10

New Four-way Cassette Type

Four-way Cassette Type (Compact) 1. Features ...........................................................................10 2. Specifications.................................................................. 11 3. Dimensions......................................................................12 4. Service Space ..................................................................13 5. Wiring Diagrams .............................................................14 6. Air Velocity and Temperature Distributions .................15 7. Electric Characteristics ..................................................16 8. Sound Levels...................................................................16 9. Accessories .....................................................................17 10. The Specification of Power ..........................................17 11. Field Wiring....................................................................18

New Four-way Cassette

9


Features

MLCAC-UTSM-2010-10

1. Features (1) Low operation noise ---Streamline plate ensures quietness ---Creates natural and comfortable environment (2) Efficient cooling ---Equal, fast and wide—range cooling (3) The adoption of the most advanced 3- Dimensional Screw fan ---Reduces the air resistance passing through ---Smoothes the air flow ---Makes air speed distribution to the heat exchange uniform

(4) Improvement for easy installation and maintenance ---Little space is required for installation into a shallow ceiling ---Because of the compactness and weight reduction of the main unit and panel, all models can be installed without a hoist

(5) 3600 Air Flow Panel 3600 air outlet makes equal,fast ad wide range cooling

(6) Inside E-box design The E-box is simply and safely build inside tge indoor unit, of witch ceiling side is 600mm*600mm. It is convenient to install and maintain. Checking the control part is easy, you only need to open the air return grille.

10

Four-way Cassette Type(Compact)


MLCAC-UTSM-2010-10

Specifications

2. Specifications Model

42TLH0181001201

Power supply Cooling

Heating

V-ph-Hz Capacity

kW

5.5

Input

kW

1.96

EER

W/W

2.81

Capacity

kW

5.9

Input

kW

1.83

COP

W/W

3.22

Model

YDK37-4P

Qty Indoor fan motor

1

Input

W

80/65/46

Capacitor

uF

2UF/400-450V

Speed(Hi/Mi/Lo)

r/min

1000/875/710

Number of rows

Indoor coil

220~240-1-50

2

Tube pitch(a)×row pitch(b)

mm

21×13.37

Fin spacing

mm

1.3

Fin type (code)

Hydrophilic aluminum

Tube outside dia. and type

mm

φ7Inner grooved copper tube

Coil length × height × width

mm

1370×210×26.74

Number of circuits

4 3

Indoor air flow (Hi/Mi/Lo)

m /h

860/760/500

Indoor noise level (sound pressure)

dB(A)

44/41/38

Indoor unit

Dimension (W×H×D)(body)

mm

570×260×570

Packing (W×H×D)(body)

mm

655×290×655

Dimension (W×H×D)(panel)

mm

647×50×647

Packing (W×H×D)(panel)

mm

705×113×705

Net/Gross weight(body)

kg

19/21

Net/Gross weight(panel)

kg

3/5

Refrigerant type

R410A

Design pressure Refrigerant piping

Liquid side/ Gas side

Drainage water pipe diameter Controller

MPa

4.2/1.5

mm

φ6.4/φ12.7

mm

ODφ25 R05/BGE (standard)

Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Four-way Cassette Type(Compact)

11


Dimensions

MLCAC-UTSM-2010-10

3. Dimensions 42TLH0181001201

12

Four-way Cassette Type(Compact)


MLCAC-UTSM-2010-10

Service Space

4. Service Space

Four-way Cassette Type(Compact)

13


Wiring Diagrams

MLCAC-UTSM-2010-10

5. Wiring Diagrams 42TLH0181001201

14

Four-way Cassette Type(Compact)


MLCAC-UTSM-2010-10

Air Velocity and Temperature Distributions

6. Air Velocity and Temperature Distributions Airflow velocity

Temperature

Four-way Cassette Type(Compact)

15


Electric Characteristics

MLCAC-UTSM-2010-10

7. Electric Characteristics Hz

Voltage

Min.

Max.

Power Supply MFA

50

220-240V

198V

254V

25

Indoor Units

Model 42TLH0181001201 Remark: MFA: Max. Fuse Amps. (A)

8. Sound Levels FOUR-WAY CASSETTE TYPE

1.0m

Microphone

Model 42TLH0181001201

16

Noise level dB(A) H

M

L

44

41

38

Four-way Cassette Type(Compact)


MLCAC-UTSM-2010-10

Accessories

9. Accessories Name Installation fittings

Drainpipe Fittings

Remote controller & Its holder

Shape

Quantity

1. Expansible hook

4

2. Installation hook

4

3. Installation paper board

1

4. Out-let pipe sheath

1

5. Out-let pipe clasp

1

6. Tightening band

20

7. Drain joint

1

8. Remote controller

1

9. Remote controller holder

1

10. Mounting screw(ST2.9×10-C-H)

2

11. Alkaline dry batteries (AM4)

2

12. Owner's manual

1

13. Installation manual

1

Others

10. The Specification of Power Type

42TLH0181001201 Phase

Power

1-phase

Frequency and Voltage Circuit Breaker/ Fuse (A)

40/25 2

Indoor Unit Power Wiring (mm )

3×2.5 2

Ground wire(mm ) Indoor/Outdoor Connecting Wiring

2.5

Outdoor Unit Power Wiring Strong Electric Signal Weak Electric Signal (mm2)

Four-way Cassette Type(Compact)

220-240V, 50Hz

3×2.5 and 2×1.0 2-core shield wire 2×0.75

17


Field Wiring

MLCAC-UTSM-2010-10

11. Field Wiring

42TLH0181001201

18

Four-way Cassette Type(Compact)


MLCAC-UTSM-2010-10

Four-way Cassette Type

Four-way Cassette Type 1. Features ...........................................................................20 2. Specifications..................................................................20 3. Dimensions......................................................................26 4. Service Space ..................................................................27 5. Wiring Diagrams .............................................................28 6. Air Velocity and Temperature Distributions .................29 7. Electric Characteristics ..................................................30 8. Sound Levels...................................................................30 9. Accessories .....................................................................31 10. The Specification of Power ..........................................32 11. Field Wiring....................................................................33

Four-way Cassette Type

19


Features

MLCAC-UTSM-2010-10

1. Features (1) Low operation noise —Streamline plate ensures quietness —Creates natural and comfortable environment (2) Efficient cooling——Equal, fast and wide range cooling

(3) Excellent performance. The optimal evaporator & sufficient airflow volume guarantees the excellent capacity (4) The adoption of the most advanced 3- Dimensional Screw fan —Reduces the air resistance passing through —Smoothes the air flow —Makes air speed distribution to the heat exchange uniform

(5) Fresh air makes life healthier and more comfortable.

(6) Drainage pump can take up the condenser water to750mm.

(7) Ultra thin machine body to easy installation and maintenance. 18K~24K:230mm, 36~48K:300mm.

20

Four-way Cassette Type


MLCAC-UTSM-2010-10

Features

(8) Different color panels for choose: White、Gray、Blue、Black

(9) Swing angle of louver 1) Add one more swing motor, one motor driving two louvers. Controlling the interspace of each part, minimizing the angle loss. 2) The swing angle of the first louver are 40~42 degrees and the second louver are 37~38 degrees. New evaporator and inner configuration designed can acquire high heat-exchanger effect.

(10) More strengthening rib design around the panel, preventing the distortion for the panel.

(11) New outlet frame design to make the phenomena of coagulation great improvement: prevent the condensing water from damaging the air guide strip. (12) Adding rib on the panel of fan outlet, which can avoid the air outlet direct flow to people.

(13) 4 speeds available, optional super high fan speed design suitable for the large building over 3m high.

(14) Adding digital tube displaying on the display board. LED can display the Error Code to make the malfunction checking easier.

Four-way Cassette Type

21


Features

MLCAC-UTSM-2010-10

(15) Reserve spaces for air side-outlet, it is available to connect duct pipe hence air supplying from the four sides to nearby small room..

(16) The connecting pipe and drop height is higher. Max. pipe length up to 50m(refer to ①), and Max. drop height up to 30m(refer to ②).

(17) Optimal design, smaller Control Box, Space saving and convenient for wiring, Using fire resistance galvanized steel for E-box material. Metal box make the control part more stable and prevent damaging. (18) 360°air flow panel : 360°air flow delivery ensures uniform airflow distribution. 60K is standard, the others are optional.

22

Four-way Cassette Type


MLCAC-UTSM-2010-10

Specifications

2. Specifications Model

42TNH0241001201

Power supply Cooling

Heating

V-ph-Hz

220~240-1-50

Capacity

kW

7.6

Input

kW

2.47

EER

W/W

3.08

Capacity

kW

8.2

Input

kW

2.33

COP

W/W

3.52

Model

YDK80-6E

Qty Indoor fan motor

1

Input

W

120/100/90

Capacitor

uF

3.5uF/450V

r/min

800/550/400

Speed(Hi/Mi/Lo) Number of rows

Indoor coil

2

Tube pitch(a)×row pitch(b)

mm

21×13.37

Fin spacing

mm

1.5

Fin type (code)

Hydrophilic aluminum

Tube outside dia. and type

mm

φ7 Inner grooved copper tube

Coil length × height × width

mm

1990×168×26.74

Number of circuits

8

Indoor air flow (Hi/Mi/Lo)

3

m /h

1327/1114/871

Indoor noise level (sound pressure)

dB(A)

42/40/39

Dimension (W×H×D)(body)

mm

840×230×840

Packing (W×H×D)(body)

mm

900×250×900

Dimension (W×H×D)(panel)

mm

950×55×950

Packing (W×H×D)(panel)

mm

1035×90×1035

Net/Gross weight(body)

kg

24/30

Net/Gross weight(panel)

kg

6/9

Indoor unit

Refrigerant type

R410A

Design pressure Refrigerant piping

Liquid side/Gas side

Drainage water pipe diameter Controller

MPa

4.2/1.5

mm

φ9.5/φ15.9

mm

ODφ32 R05/BGE(standard)

Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Four-way Cassette Type

23


Specifications

MLCAC-UTSM-2010-10 Model

42TNH0361001201

Power supply Cooling

Heating

V-ph-Hz Capacity

kW

10

Input

kW

3.79

EER

W/W

2.64

Capacity

kW

11

Input

kW

3.57

COP

W/W

Model

1

Input

W

143/116/100

Capacitor

uF

3.5uF/450V

r/min

770/640/550

Speed(Hi/Mi/Lo) Number of rows

Indoor coil

3.08 YDK90-6E

Qty Indoor fan motor

220~240-1-50

2

Tube pitch(a)×row pitch(b)

mm

Fin spacing

mm

Fin type (code)

21×13.37 1.5 Hydrophilic aluminum

Tube outside dia. and type

mm

φ7 Inner grooved copper tube

Coil length × height × width

mm

1990×252×26.74

Number of circuits

12 3

Indoor air flow (Hi/Mi/Lo)

m /h

Indoor noise level (sound pressure)

dB(A)

1545/1354/1187 44/42/41

Dimension (W×H×D)(body)

mm

840×300×840

Packing (W×H×D)(body)

mm

900×320×900

Dimension (W×H×D)(panel)

mm

950×55×950

Packing (W×H×D)(panel)

mm

1035×90×1035

Net/Gross weight(body)

kg

30/36

Net/Gross weight(panel)

kg

6/9

Indoor unit

Refrigerant type

R410A

Design pressure Refrigerant piping

Liquid side/Gas side

Drainage water pipe diameter Controller

MPa

4.2/1.5

mm

φ12.7/φ19

mm

ODφ32 R05/BGE(standard)

Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

24

Four-way Cassette Type


MLCAC-UTSM-2010-10

Specifications

Model

42TNH0481001901

Power supply

Cooling

Heating

V-ph-Hz

380~415-3-50

Capacity

kW

13

Input

kW

4.93

EER

W/W

2.64

Capacity

kW

14.3

Input

kW

5.42

COP

W/W

2.64

Model

YDK90-6E

Qty Indoor fan motor

1

Input

W

143/116/100

Capacitor

uF

3.5uF/450V

r/min

770/640/550

Speed(Hi/Mi/Lo) Number of rows

Indoor coil

2

Tube pitch(a)×row pitch(b)

mm

21×13.37

Fin spacing

mm

1.5

Fin type (code)

Hydrophilic aluminum

Tube outside dia.and type

mm

φ7 Inner grooved copper tube

Coil length × height × width

mm

1990×252×26.74

Number of circuits

12 3

Indoor air flow (Hi/Mi/Lo)

m /h

Indoor noise level (sound pressure)

dB(A)

1545/1354/1187 44/42/41

Dimension (W×H×D)(body)

mm

840×300×840

Packing (W×H×D)(body)

mm

900×320×900

Dimension (W×H×D)(panel)

mm

950×55×950

Packing (W×H×D)(panel)

mm

1035×90×1035

Net/Gross weight(body)

kg

30/36

Net/Gross weight(panel)

kg

6/9

Indoor unit

Refrigerant type

R410A

Design pressure Refrigerant piping

Liquid side/Gas side

Drainage water pipe diameter Controller

MPa

4.2/1.5

mm

φ12.7/φ19

mm

ODφ32 R05/BGE(standard)

Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Four-way Cassette Type

25


Dimensions

MLCAC-UTSM-2010-10

3. Dimensions 42TNH0241001201 4-install hanger Gas side Liquid side

E-parts box

Pump inspect hole

Drain hole

42TNH0361001201

42TNH0481001901

4-install hanger Gas side Liquid side

E-parts box

Pump inspect hole

Drain hole

26

Four-way Cassette Type


MLCAC-UTSM-2010-10

Service Space

4. Service Space The indoor unit should be installed in a location that meets the following requirements: ● There is enough room for installation and maintenance. ● The ceiling is horizontal, and its structure can endure the weight of the indoor unit. ● The outlet and the inlet are not impeded, and the influence of external air is the least. ● The air flow can reach throughout the room. ● The connecting pipe and drainpipe could be extracted out easily. ● There is no direct radiation from heaters.

Four-way Cassette Type

27


Wiring Diagrams

MLCAC-UTSM-2010-10

5. Wiring Diagrams 5.1 42TNH0241001201

42TNH0361001201

5.2 42TNH0481001901

28

Four-way Cassette Type


MLCAC-UTSM-2010-10

Air Velocity and Temperature Distributions

6. Air Velocity and Temperature Distributions Airflow velocity

Temperature

Four-way Cassette Type

29


Electric Characteristics

MLCAC-UTSM-2010-10

7. Electric Characteristics Indoor Units

Model

Power Supply

Hz

Voltage

Min.

Max.

MFA

42TNH0241001201

50

220-240V

198V

254V

25

42TNH0361001201

50

220-240V

198V

254V

25

50

380-415V

342V

418V

15

42TNH0481001901 Remark: MFA: Max. Fuse Amps. (A)

8. Sound Levels FOUR-WAY CASSETTE TYPE

1.0m

Microphone

Model

30

Noise level dB(A) H

M

L

42TNH0241001201

42

40

39

42TNH0361001201

44

42

41

42TNH0481001901

44

42

41

Four-way Cassette Type


MLCAC-UTSM-2010-10

Accessories

9. Accessories Name

Installation Fittings

Tubing & Fittings

Drainpipe Fittings

Protect Pipe Fittings

Remote controller & Its Frame

Shape

Quantity

1. Expansible hook

4

2. Installation hook

4

3. Installation paper board

1

4. Bolt M5

4

5. Connecting pipe group

1

6. Binding tape

6

7.Soundproof/insulation sheath

2

8. Out-let pipe sheath

1

9. Out-let pipe clasp

1

10. Tightening band

20

11. Drain joint

1

12. Seal ring

1

13. Wall conduit

1

14. Wall conduit cover

1

15. Remote controller

1

16. Frame

1

17. Mounting screw(ST2.9Ă—10-C-H)

2

18. Alkaline dry batteries (AM4)

2

19. Owner's manual

1

20. Installation manual

1

Others

Four-way Cassette Type

31


The Specification of Power

MLCAC-UTSM-2010-10

10. The Specification of Power Type Power

Phase Frequency and Voltage

Circuit Breaker/ Fuse (A) Indoor Unit Power Wiring (mm2) Ground Wiring Outdoor Unit Indoor/Outdoor Power Wiring Connecting Wiring Strong 2 (mm ) Electric Signal Weak Electric Signal

32

42TNH0241001201 1-phase

42TNH0361001201 1-phase

42TNH0481001901 3-phase

220-240V, 50Hz

220-240V, 50Hz

380-415V, 50Hz

40/25 3×4.0

40/25 3×4.0

25/15 5×2.5

4.0

4.0

2.5

3×4.0

3×4.0

5×2.5

3×2.5

3×2.5

3×1.0

1-core shield wire 1×0.5

1-core shield wire 1×0.5

Four-way Cassette Type


MLCAC-UTSM-2010-10

Field Wiring

11. Field Wiring Wiring chart

42TNH0241001201

Four-way Cassette Type

42TNH0361001201

33


Field Wiring

MLCAC-UTSM-2010-10

42TNH0481001901

34

Four-way Cassette Type


MLCAC-UTSM-2010-10

Ceiling & Floor Type

Ceiling & Floor Type 1. Features ...........................................................................36 2. Specifications..................................................................37 3. Dimensions......................................................................42 4. Service Space ..................................................................43 5. Wiring Diagrams .............................................................44 6. Air Velocity and Temperature Distributions .................47 7. Electric Characteristics ..................................................49 8. Sound Levels...................................................................50 9. Accessories .....................................................................51 10. The Specification of Power ..........................................52 11. Field Wiring....................................................................53

Ceiling & Floor Type

35



MLCAC-UTSM-2010-10

Specifications

2. Specifications Model

42FLH0181001201

Power supply Cooling

Heating

V-ph-Hz

220~240-1-50

Capacity

kW

5.29

Input

kW

1.94

EER

W/W

2.73

Capacity

kW

5.82

Input

kW

1.61

COP

W/W

3.61

Model

YSK55-4L

Qty Indoor fan motor

1

Input

W

125/105/85

Capacitor

uF

2.5uF/450V

r/min

1310/1190/1040

Speed(Hi/Mi/Lo) Number of rows

Indoor coil

3

Tube pitch(a)×row pitch(b)

mm

21×13.37

Fin spacing

mm

1.3

Fin type (code)

Hydrophilic aluminum

Tube outside dia. and type

mm

Φ7 Inner grooved copper tube

Coil length× height× width

mm

804×252×40.11

Number of circuits

4

Indoor air flow(Hi/Mi/Lo)

3

m /h

800/600/500

Indoor noise level (sound pressure)

dB(A)

43/41/38

Dimension (W×H×D)

mm

990×203×660

Packing (W×H×D)

mm

1090×297×745

kg

26/32

Indoor unit

Net/Gross weight Refrigerant type

R410A

Design pressure Refrigerant piping

Liquid side/Gas side

Drainage water pipe diameter Controller

MPa

4.2/1.5

mm

φ6.4/φ12.7

mm

ODφ25 R05/BGE(standard)

Operation temperature 17-30 ℃ Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Ceiling & Floor Type

37


Specifications

MLCAC-UTSM-2010-10

Model

42FLH0241001201

Power supply

V-ph-Hz

220~240-1-50

kW

6.90

kW W/W

2.46 2.81

kW

7.60

Input

kW

2.36

COP

W/W

3.22

Capacity Cooling

Input EER Capacity

Heating

Model

YSK55-4L

Qty Indoor fan motor

1

Input

W

125/105/85

Capacitor

uF

2.5uF/450V

r/min

1310/1190/1040

Speed(Hi/Mi/Lo) Number of rows

Indoor coil

3

Tube pitch(a)×row pitch(b)

mm

21×13.37

Fin spacing

mm

1.3

Fin type (code)

Hydrophilic aluminum

Tube outside dia. and type

mm

Coil length× height×width

mm

Number of circuits

Φ7 Inner grooved copper tube 804×252×40.11 4

Indoor air flow(Hi/Mi/Lo)

3

m /h

1200/900/700

Indoor noise level (sound pressure)

dB(A)

45/43/40

Dimension (W×H×D)

mm

990×203×660

Packing (W×H×D)

mm

1090×297×745

kg

27/33

Indoor unit

Net/Gross weight Refrigerant type

R410A

Design pressure Refrigerant piping

Liquid side/Gas side

Drainage water pipe diameter Controller

MPa

4.2/1.5

mm

φ9.5/φ15.9

mm

ODφ25 R05/BGE(standard)

Operation temperature 17-30 ℃ Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

38

Ceiling & Floor Type


MLCAC-UTSM-2010-10

Specifications

Model

42FLH0361001201

Power supply Cooling

Heating

V-ph-Hz

220~240-1-50

Capacity

kW

9.46

Input

kW

3.80

EER

W/W

2.49

Capacity

kW

10.60

Input

kW

3.93

COP

W/W

2.70

Model

YSK80-4A

Qty Indoor fan motor

1

Input

W

143/122/110

Capacitor

uF

3.5uF/450V

r/min

1310/1210/1115

Speed(Hi/Mi/Lo) Number of rows

Indoor coil

3

Tube pitch(a)×row pitch(b)

mm

25.4×22

Fin spacing

mm

1.7

Fin type (code)

Hydrophilic aluminum

Tube outside dia.and type

mm

φ9.53 Inner grooved copper tube

Coil length×height×width

mm

1094×254×66

Number of circuits

5

Indoor air flow(Hi/Mi/Lo)

3

m /h

1400/1200/1000

Indoor noise level (sound pressure)

dB(A)

45/43/40

Dimension (W×H×D)

mm

1280×203×660

Packing (W×H×D)

mm

1380×745×297

kg

35/42

Indoor unit

Net/Gross weight Refrigerant type

R410A

Design pressure Refrigerant piping

Liquid side/Gas side

Drainage water pipe diameter Controller

MPa

4.2/1.5

mm

φ12.7/φ19

mm

ODφ25 R05/BGE(standard)

Operation temperature 17-30 ℃ Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Ceiling & Floor Type

39


Specifications

MLCAC-UTSM-2010-10

Model

42FLH0481001901

Power supply Cooling

Heating

V-ph-Hz

380~415-3-50

Capacity

kW

13.63

Input

kW

4.96

EER

W/W

2.75

Capacity

kW

15.00

Input

kW

4.55

COP

W/W

3.30

Model

YSK59-4D

Qty Indoor fan motor

2

Input

W

102/98/96

Capacitor

uF

2.5uF/450V

r/min

1230/1130/1070

Speed(Hi/Mi/Lo) Number of rows

Indoor coil

3

Tube pitch(a)×row pitch(b)

mm

25.4×22

Fin spacing

mm

1.7

Fin type (code)

Hydrophilic aluminium

Tube outside dia.and type

mm

φ9.53 Inner grooved copper tube

Coil length×height×width

mm

1360×254×66

Number of circuits

5

Indoor air flow(Hi/Mi/Lo)

3

m /h

2000/1800/1600

Indoor noise level (sound pressure)

dB(A)

50/47/45

Dimension (W×H×D)

mm

1670×240×680

Packing (W×H×D)

mm

1764×329×760

kg

50/58

Indoor unit

Net/Gross weight Refrigerant type

R410A

Design pressure Refrigerant piping

Liquid side/Gas side

Drainage water pipe diameter Controller

MPa

4.2/1.5

mm

φ12.7/φ19

mm

ODφ25 R05/BGE(standard)

Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

40

Ceiling & Floor Type


MLCAC-UTSM-2010-10

Specifications

Model

42FLH0601001901

Power supply Cooling

Heating

V-ph-Hz

380~415-3-50

Capacity

kW

14.90

Input

kW

5.59

EER

W/W

2.67

Capacity

kW

16.50

Input

kW

5.63

COP

W/W

2.93

Model

YSK59-4D

Qty Indoor fan motor

2

Input

W

89.5/81.5/77.5

Capacitor

uF

2.5uF/450V

r/min

1170/1070/995

Speed(Hi/Mi/Lo) Number of rows

Indoor coil

3

Tube pitch(a)×row pitch(b)

mm

25.4×22

Fin spacing

mm

1.7

Fin type (code)

Hydrophilic aluminium

Tube outside dia.and type

mm

φ9.53 Inner grooved copper tube

Coil length×height×width

mm

1360×254×66

Number of circuits

5

Indoor air flow(Hi/Mi/Lo)

3

m /h

2000/1800/1600

Indoor noise level (sound pressure)

dB(A)

50/49/47

Dimension (W×H×D)

mm

1670×240×680

Packing (W×H×D)

mm

1764×329×760

kg

52/59

Indoor unit

Net/Gross weight Refrigerant type

R410A

Design pressure Refrigerant piping

Liquid side/Gas side

Drainage water pipe diameter Controller

MPa

4.2/1.5

mm

φ12.7/φ19

mm

ODφ25 R05/BGE(standard)

Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Ceiling & Floor Type

41


Dimensions

MLCAC-UTSM-2010-10

3. Dimensions a. Wall mounting installation

b. Ceiling installation

Model A B C 42FLH0181001201 990 660 203 42FLH0241001201 42FLH0361001201 1280 660 203 42FLH0481001901 1670 680 240 42FLH0601001901 Note: The dimension of 18000Btu/h and 24000Btu/h are the same. The dimension of 48000Btu/h and 60000Btu/h are the same. 42

D

E

F

G

505

506

907

200

795

506

1195

200

1070

450

1542

200

Ceiling & Floor Type


MLCAC-UTSM-2010-10

Service Space

4. Service Space

Ceiling & Floor Type

43


Wiring Diagrams

MLCAC-UTSM-2010-10

5. Wiring Diagrams 42FLH0181001201

44

Ceiling & Floor Type


MLCAC-UTSM-2010-10

42FLH0241001201

Ceiling & Floor Type

Wiring Diagrams

42FLH0361001201

45


Wiring Diagrams

42FLH0481001901

46

MLCAC-UTSM-2010-10

42FLH0601001901

Ceiling & Floor Type


MLCAC-UTSM-2010-10

Air Velocity and Temperature Distributions

6. Air Velocity and Temperature Distributions Discharge angle 60째 (CEILING)

Airflow velocity

Temperature

Ceiling & Floor Type

47


Air Velocity and Temperature Distributions

MLCAC-UTSM-2010-10

Discharge angle 60째(FLOOR)

Temperature

Airflow velocity

48

Ceiling & Floor Type


MLCAC-UTSM-2010-10

Electric Characteristics

7. Electric Characteristics Model

Indoor Units

Power Supply

Hz

Voltage

Min.

Max.

MFA

42FLH0181001201

50

220-240V

198V

254V

16

42FLH0241001201

50

220-240V

198V

254V

25

42FLH0361001201

50

220-240V

198V

254V

25

42FLH0481001901

50

380-415V

342V

418V

20

42FLH0601001901 Remark: MFA: Max. Fuse Amps. (A)

50

380-415V

342V

418V

20

Ceiling & Floor Type

49


Sound Levels

MLCAC-UTSM-2010-10

8. Sound Levels

Ceiling Model

50

Floor Noise level dB(A) H

M

L

42FLH0181001201

43

41

38

42FLH0241001201

45

43

40

42FLH0361001201

45

43

40

42FLH0481001901

50

47

45

42FLH0601001901

50

49

47

Ceiling & Floor Type


MLCAC-UTSM-2010-10

Accessories

9. Accessories Name

Installation fittings

Remote controller & Its holder

Others

Ceiling & Floor Type

Shape

Quantity

1.Hook

2

2.Hanging arm

2

3. Remote controller

1

4. Remote controller holder

1

5. Mounting screw (ST2.9Ă—10-C-H)

2

6. Alkaline dry batteries (AM4)

2

7. Owner's manual

1

8. Installation manual

1

9. Remote controller manual

1

51


The Specification of Power

MLCAC-UTSM-2010-10

10. The Specification of Power Cooling & Heating Phase

1-phase

42FLH0241001201 42FLH0361001201 1-phase

Frequency and Voltage

220-240V, 50Hz

220-240V, 50Hz

380-415V, 50Hz

Type Power

42FLH0181001201

Circuit Breaker/ Fuse (A)

20/16

40/25

40/20

2

3×2.5

3×2.5

5×2.5

Ground Wiring

2.5

2.5

2.5

3×2.5

5×2.5

3×2.5 1-core shield wire 1×0.5 mm2

3×2.5

Indoor Unit Power Wiring (mm )

Indoor/Outdoor 2 Connecting Wiring (mm )

Outdoor Unit Power Wiring Strong Electric Signal Weak Electric Signal

52

42FLH0481001901 42FLH0601001901 3-phase

5×2.5 1-core shield wire 2 1×0.5 mm

Ceiling & Floor Type


MLCAC-UTSM-2010-10

Field Wiring

11. Field Wiring

Ceiling & Floor Type

53


Field Wiring

MLCAC-UTSM-2010-10

42FLH0181001201

42FLH0241001201

54

Ceiling & Floor Type


MLCAC-UTSM-2010-10

Field Wiring

42FLH0361001201

42FLH0481001901

42FLH0601001901

、 Ceiling & Floor Type

55


Duct Type

MLCAC-UTSM-2010-06

Duct Type 1. Features ...........................................................................57 2. Specifications..................................................................58 3. Dimensions......................................................................62 4. Service Space ..................................................................63 5. Wiring Diagrams .............................................................64 6. Static Pressure ................................................................66 7. Electric Characteristics ..................................................68 8. Sound Levels...................................................................69 9. Accessories .....................................................................70 10. The Specification of Power ..........................................71 11. Field Wiring....................................................................72

56

Duct Type


MLCAC-UTSM-2010-10

Features

1. Features 1. Economic and convenient installation ---Several diffusers branch off from an indoor unit, adjusting the room temperature, which makes many rooms to be air-conditioned with only one indoor unit. ---All models feature thin design making them applicable to ceiling pocket that tends to be shallow 2. Optional accessories ---Including front clapboard, panel, canvas air passage, filter, etc..

Front boar

Panel

Canvas air passage

Filter

3. A long-life and high-efficiency filter 4. Way of air intake and inserting air filter ---Air intake can be positioned either at the back or below the unit. Similarly, the air filter also can be inserted either from the back or from the bottom of the unit.

Duct Type

57


Specifications

MLCAC-UTSM-2010-10

2. Specifications 42SMH0241011201

Model V-ph-Hz kW

220~240-1-50

Input

kW

2.60

EER

Power supply Capacity Cooling

Heating

W/W

2.73

Capacity

kW

7.60

Input

kW

2.37

COP

W/W

3.21 YSK74-4P

Model Qty Indoor fan motor

Input

1 W

Speed(Hi/Mi/Lo)

163/93/75 3.5UF/450V

Capacitor

Indoor coil

7.10

r/min

1000/750/680 4

Number of rows Tube pitch(a)×row pitch(b)

mm

Fin spacing

mm

1.5

mm

Hydrophilic aluminum φ7, Inner grooved copper tube

Fin type (code) Tube outside dia. and type Coil length × height × width

mm

21×13.37

735×252×53.48 6

Number of circuits 3

m /h

1400/1100/1000

Indoor external static pressure (Hi)

Pa

70

Indoor noise level (sound pressure) Dimension (W×H×D) Indoor unit Packing (W×H×D)

dB(A)

45/43/41

Indoor air flow(Hi/Mi/Lo)

mm

920x270x635

mm

1135x350x655

kg

28/34

Refrigerant type

R410A

Design pressure Refrigerant Liquid side/ Gas piping side

MPa

4.2/1.5

Drainage water pipe diameter

mm

Net/Gross weight

mm

φ9.5/φ15.9 ODφ25 Wireless Remote Controller

Controller Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

58

Duct Type


MLCAC-UTSM-2010-10

Specifications

42SMH0361011201

Model V-ph-Hz kW

220~240-1-50

Input

kW

4.09

EER

W/W

2.49

Capacity

kW

11.10

Input

kW

3.61

COP

W/W

3.08

Power supply Capacity Cooling

Heating

YSK140-4P

Model Qty Indoor fan motor

Input

1 W r/min

1070/790/710 4

Number of rows

Indoor coil

291/168/138 10uF/450V

Capacitor Speed(Hi/Mi/Lo)

10.20

Tube pitch(a)×row pitch(b)

mm

21×13.37

Fin spacing

mm

1.5 Hydrophilic aluminum

Fin type (code) Tube outside dia. and type

mm

φ7,inner grooved copper tube

Coil length × height × width

mm

955×336×53.48 8

Number of circuits m3/h

2270/1890/1650

Indoor external static pressure (Hi)

Pa

80

Indoor noise level (sound pressure)

dB(A)

46/44/42

Dimension (W×H×D)

mm

1140x270x775

Packing (W×H×D)

mm

1355x350x795

Net/Gross weight

kg

41/46

Refrigerant type

R410A

Design pressure

MPa

4.2/1.5

mm

φ12.7/φ19

mm

ODφ25

Indoor air flow(Hi/Mi/Lo)

Indoor unit

Refrigerant piping

Liquid side/ Gas side

Drainage water pipe diameter

Wireless Remote Controller Controller Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Duct Type

59


Specifications

MLCAC-UTSM-2010-10

42SMH0481011901

Model V-ph-Hz kW

380~415-3-50

Input

kW

4.97

EER

W/W

2.75

Capacity

kW

14.40

Input

kW

4.27

COP

W/W

3.37

Power supply Capacity Cooling

Heating

YSK170-4P

Model Qty Indoor fan motor

Input

1 W r/min

1070/750/650 4

Number of rows

Indoor coil

356/201/152 10uF/450V

Capacitor Speed(Hi/Mi/Lo)

13.70

Tube pitch(a)×row pitch(b)

mm

21×13.37

Fin spacing

mm

1.5 Hydrophilic aluminum

Fin type (code) Tube outside dia. and type

mm

φ7,inner grooved copper tube

Coil length × height × width

mm

1030×378×53.48 8

Number of circuits m3/h

3010/2410/1940

Indoor external static pressure (Hi)

Pa

100

Indoor noise level (sound pressure)

dB(A)

47/45/43

Dimension (W×H×D)

mm

1200×300×865

Packing (W×H×D)

mm

1385×373×920

Net/Gross weight

kg

47/55

Refrigerant type

R410A

Design pressure

MPa

4.2/1.5

mm

φ12.7/φ19

mm

ODφ25

Indoor air flow(Hi/Mi/Lo)

Indoor unit

Refrigerant piping

Liquid side/ Gas side

Drainage water pipe diameter

Wireless Remote Controller Controller Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal); 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

60

Duct Type


MLCAC-UTSM-2010-10

Specifications

42SMH0601011901

Model V-ph-Hz kW

380~415-3-50

Input

kW

5.74

EER

W/W

2.58

Capacity

kW

16.00

Input

kW

4.98

COP

W/W

3.21

Power supply Capacity Cooling

Heating

YSK180-4P

Model Qty Indoor fan motor

Input

1 W r/min

1080/830/710 4

Number of rows

Indoor coil

355/223/173 10uF/450V

Capacitor Speed(Hi/Mi/Lo)

14.80

Tube pitch(a)×row pitch(b)

mm

21×13.37

Fin spacing

mm

1.5 Hydrophilic aluminum

Fin type (code) Tube outside dia. and type

mm

φ7 Inner grooved copper tube

Coil length × height × width

mm

1030×378×53.48 8

Number of circuits m3/h

3150/2510/1990

Indoor external static pressure (Hi)

Pa

100

Indoor noise level (sound pressure)

dB(A)

47/45/43

Dimension (W×H×D)

mm

1200×300×865

Packing (W×H×D)

mm

1385×373×920

Net/Gross weight

kg

47/55

Refrigerant type

R410A

Design pressure

MPa

4.2/1.5

mm

φ12.7/φ19

mm

ODφ25

Indoor air flow(Hi/Mi/Lo)

Indoor unit

Refrigerant piping

Liquid side/ Gas side

Drainage water pipe diameter

Wireless Remote Controller Controller Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal); 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Duct Type

61


Dimensions

MLCAC-UTSM-2010-10

3. Dimensions

E

Air outlet o pening size F G H

42SMH0241011201

920

270

635

570

65

713

35

179

815

260

20

960

350

42SMH0361011201 42SMH0481011901 42SMH0601011901

1140

270

775

710

65

933

35

179

1035

260

20

1180

490

1200

300

865

800

80

968

40

204

1094

288

45

1240

500

Model

62

Outline dimension(mm) A B C D

Air return opening size I J K

Size of outline dimension mounted plug L M

Duct Type


MLCAC-UTSM-2010-10

ervice Space

4. Service Space Ensure enough space required for installation and maintenance.

There is enough space for installation and maintenance. The ceiling is horizontal, and its structure can endure the weight of the indoor unit. The outlet and the inlet are not impeded, and the influence of external air is the least. The air flow can reach throughout the room. The connecting pipe and drainpipe could be extracted out easily. There is no direct radiation from heater.

Duct Type

63


Wiring Diagrams

MLCAC-UTSM-2010-10

5. Wiring Diagrams 42SMH0241011201

64

42SMH0361011201

Duct Type


MLCAC-UTSM-2010-10

42SMH0481011901

Duct Type

Wiring Diagrams

42SMH0601011901

65


Static Pressure

MLCAC-UTSM-2010-10

6. Static Pressure 42SMH0241011201

42SMH0361011201 Pa

90

90

80

80

70 Super high speed

60 50

High speed

40

Mid speed

30

Low speed

70 60

40 30 20

10

10 800

900 1000 1100 1200 1300 1400 1500 Air volume(m3/h)

Super high speed High speed

50

20

700

66

External static pressure (Pa)

External static pressure (Pa)

Pa

Mid speed Low speed

1100 1200 1400 1600 1800 2000 2200 2400 Air volume(m3/h)

Duct Type


MLCAC-UTSM-2010-10

Static Pressure

42SMH0481011901

42SMH0601011901 Pa 120

Pa 120

110 110

100 100

90 90

External static pressure (Pa)

70 60 50

Super high speed High speed Mid speed Low speed

40 30

Super high speed

70 60 50 40

High speed

Mid speed Low speed

30 20

20

10

10

1000 1300 1600 1900 2200 2500 2800 3100 Air volume(m 3 /h)

Duct Type

External static pressure (Pa)

80 80

1000 1300 1600 1900 2200 2500 2800 3100 3400 Air volume(m3/h)

67


Electric Characteristics

MLCAC-UTSM-2010-10

7. Electric Characteristics Model

Indoor Units Hz

Voltage

Min.

Max.

MFA

42SMH0241011201

50

220-240V

198V

254V

25

42SMH0361011201

50

220-240V

198V

254V

30

42SMH0481011901

50

380-415V

342V

418V

30

380-415V

342V

418V

30

42SMH0601011901 50 Remark: MFA: Max. Fuse Amps. (A)

68

Power Supply

Duct Type


MLCAC-UTSM-2010-10

Sound Levels

8. Sound Levels Concealed Duct Type Discharge

Suction

Duct

Duct

1.4m

Microphone

Model

Duct Type

Noise level dB(A) H

M

L

42SMH0241011201

45

43

41

42SMH0361011201

46

44

42

42SMH0481011901

47

45

43

42SMH0601011901

47

45

43

69


Accessories

MLCAC-UTSM-2010-10

9. Accessories Name

Tubing & Fittings

Shape

Quantity

Soundproof/insulation sheath

2

Binding tape

1

Seal sponge

1

Drain joint

1

Seal ring

1

Wire controller

1

Owner's manual

1

Installation manual

1

Drainpipe Fittings

Wire controller

others

70

Duct Type


MLCAC-UTSM-2010-10

The Specification of Power

10. The Specification of Power Model

42SMH0481011901

42SMH0241011201

42SMH0361011201

1-Phase

1-Phase

3-Phase

220-240V,50Hz

220-240V,50Hz

380-415V, 50Hz

Circuit Breaker/Fuse(A)

30/25

35/30

40/30

Indoor unit power wiring(mm²)

3×2.5

3×4.0

5×4.0

2.5

4.0

4.0

Outdoor unit power wiring

3×2.5

3×4.0

5×4.0

Strong electric signal

3×1.5

3×1.5

3×1.5

Weak electric signal

2×0.75

2×0.75

Phase

42SMH0601011901

Power Frequency and Volt

Indoor/outdoor

Groud wiring

connecting wiring(mm² )

Duct Type

71


Field Wiring

MLCAC-UTSM-2010-10

11. Field Wiring

72

Duct Type


MLCAC-UTSM-2010-10

Field Wiring

42SMH0241011201

42SMH0361011201

Duct Type

73


Field Wiring

42SMH0481011901

74

MLCAC-UTSM-2010-10

42SMH0601011901

Duct Type



Outdoor Units

MLCAC-UTSM-2010-10

Part 3 Outdoor Units 1. Specifications ................................................................101 2. Dimensions....................................................................106 3. Service Space ................................................................107 4. Wiring Diagrams ...........................................................108 5. Electric Characteristics ................................................ 110 6. Operation Limits ........................................................... 111 7. Sound Levels................................................................. 112 8. Troubleshooting ............................................................ 113

100

Outdoor Units


MLCAC-UTSM-2010-10

Specifications

1. Specifications Model

38HN0181120A

Power supply

V-ph-Hz

Max. input consumption

W

Max. input current

A

PA225X2CS-4KU1

Type

Rotary

Brand

GMCC

Capacity

Btu/h

Input

W

Rated current(RLA)

A

1855/1940 8.7/8.7

Locked rotor Amp(LRA)

A

36.8

Thermal protector Capacitor

μF

50μF/440V-450V

Refrigerant oil

ml

ESTER OIL VG74 750 YDK48-6H(A)

Qty

1

Input

W

110

Capacitor

μF

3μF/450V

Speed

r/min

890

Tube pitch(a)× row pitch(b)

mm

21x13.37

Fin spacing

mm

1.4

Tube outside dia.and type

mm

Coil length × height × width

mm

Hydrophilic aluminum φ7, Inner grooved copper tube 658x546x26.74

Number of rows

Outdoor coil

18493/18698

Internal

Model Outdoor fan motor

2950 15

Model

Compressor

220~240-1-50

2

Fin type

Number of circuits Outdoor air flow

m /h

4 2439

Outdoor noise level (sound pressure)

dB(A)

54

Outdoor unit

Refrigerant

3

Dimension(W×H×D)

mm

760x590x285

Packing (W×H×D)

mm

887×645×355

Net/Gross weight

kg

Type Charged volume

g

Throttle type

Ambient temp.

1400 Capillary

Design pressure Refrigerant piping

39/42 R410a

MPa

4.2/1.5

Liquid side/ Gas side

mm

φ6.4/φ12.7

Max. pipe length

m

Max. difference in level

m

15

cooling:18~43; heating:-7~24

25

Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Outdoor Units

101


Specifications

MLCAC-UTSM-2010-10

Model

38HN0241120A

Power supply

V-ph-Hz

Max. input consumption

W

Max. input current

A

18 PA290X3CS-4MU1

Type

Rotary GMCC

Capacity

Btu/h

24498

Input

W

2430

Rated current(RLA)

A

11.4

Locked rotor Amp(LRA)

A

61

Capacitor

μF

Internal 50μF/440V-450V

Refrigerant oil

ml

ESTER OIL VG74/950

Thermal protector

Model

YDK100-6D

Qty Outdoor fan motor

1

Input

W

168.7

Capacitor

μF

5μF/450V

Speed

r/min

900

Tube pitch(a)× row pitch(b)

mm

21x13.37

Fin spacing

mm

1.4

Tube outside dia.and type

mm

Coil length × height × width

mm

Hydrophilic aluminum φ7, Inner grooved copper tube 785x651x26.74

Number of rows

Outdoor coil

3450

Model Brand

Compressor

220~240-1-50

2

Fin type

Number of circuits Outdoor air flow

m /h

4 3200

Outdoor noise level (sound pressure)

dB(A)

55

Outdoor unit

Refrigerant

3

Dimension(W×H×D)

mm

845×695×324

Packing (W×H×D)

mm

965×755×395

Net/Gross weight

kg

Type Charged volume

R410a g

Throttle type

Ambient temp.

1900 Capillary

Design pressure Refrigerant piping

53/57

MPa

4.2/1.5

Liquid side/ Gas side

mm

φ9.5/φ15.9

Max. pipe length

m

25

Max. difference in level

m

15

cooling: 18~43; heating:-7~24

Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

102

Outdoor Units


MLCAC-UTSM-2010-10

Specifications

Model

38HN0361120A

Power supply

V-ph-Hz

Max. input consumption

W

4950

Max. input current

A

30

Model

C-SBN301H5D

Type

SCROLL

Brand

Compressor

SANYO

Capacity Input Rated current(RLA)

Btu/h W A

Locked rotor Amp(LRA)

A

Thermal protector μF

60μF/450V+90μF/400V

Refrigerant oil

ml

FV68S/1700 YDK190-6D

Qty Input Capacitor

W μF

Speed

r/min

Fin type Tube outside dia.and type Coil length × height × width Number of circuits

Outdoor air flow Outdoor noise level (sound pressure) Dimension(W×H×D) Outdoor unit

Packing

(W×H×D)

Net/Gross weight Refrigerant

mm mm

840 21x13.37 1.4 Hydrophilic aluminium

mm mm

φ7, Inner grooved copper tube 890x903x26.74

m3/h

7 5000

dB(A)

57

mm

990×966×354

mm

1120×1100×435

kg

94/98 R410a

g

2900

Type Charged volume

1 290 10μF/450V 1.5

Throttle type

Capillary

Design pressure Refrigerant piping

112

Capacitor

Number of rows Tube pitch(a)× row pitch(b) Fin spacing Outdoor coil

31902 3750 18.1 Internal

Model Outdoor fan motor

220~240-1-50

MPa

4.2/1.5 φ12.7/φ19

Liquid side/ Gas side

mm

Max. pipe length

m

30

Max. difference in level

m

20 cooling: 18~43; heating:-7~24

Ambient temp. ℃ Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Outdoor Units

103


Specifications

MLCAC-UTSM-2010-10 Model

38HN0481190A

Power supply

V-ph-Hz

Max. input consumption

W

6300

Max. input current

A

10.5

Model

C-SBN373H8D

Type

Scroll

Brand

Compressor

Sanyo

Capacity

Btu/h

48109

Input

W

4750

Rated current(RLA)

A

8.22

Locked rotor Amp(LRA)

A

66

Thermal protector Capacitor

μF

Internal --

Refrigerant oil

ml

FV68S,1700

Model Outdoor fan motor

YDK65-6-1+YDK65-6F-1

Qty

2

Input

W

171×2

Capacitor

μF

(4μF/450V)×2

Speed

r/min

Number of rows Tube pitch(a)× row pitch(b) Fin spacing

mm

21×13.37

mm

1.4

825 2

Fin type Outdoor coil

380~415-3-50

Hydrophilic aluminums

Tube outside dia. and type

mm

φ7 Inner grooved copper tube

Coil length × height × width

mm

840×1113×26.74

Outdoor air flow

m3/h

4 6800

Outdoor noise level (sound pressure)

dB(A)

59

Number of circuits

Outdoor unit

Refrigerant

Dimension(W×H×D)

mm

900×1167×340

Packing (W×H×D)

mm

1032×1307×443

Net/Gross weight

kg

110/115

Type Charged volume

R410a g

Throttle type MPa

capillary 4.2/1.5

Liquid side/ Gas side

mm

φ12.7/φ19

Max. pipe length

m

50

Max. difference in level

m

25 cooling: 18~43; heating:-7~24

Design pressure Refrigerant piping

3250

Ambient temp. ℃ Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

104

Outdoor Units


MLCAC-UTSM-2010-10

Specifications

Model

38HN0601190A

Power supply

V-ph-Hz

Max. input consumption

W

7500

Max. input current

A

12.6

Model

C-SBN453H8D

Type

Scroll

Brand

Compressor

Sanyo

Capacity

Btu/h

Input

W

5750

Rated current(RLA)

A

9.77

Locked rotor Amp(LRA)

A

67

Thermal protector Capacitor

μF

Internal ---

Refrigerant oil

ml

FV68S, 1700

Model Outdoor fan motor

55956.8

YDK65-6+YDK65-6F

Qty

2

Input

W

148+140

Capacitor

μF

(3.5μF/450V)×2

Speed

r/min

800

Number of rows Tube pitch(a)× row pitch(b) Fin spacing

mm

22×19.05

2 mm

Fin type Outdoor coil

380~415-3-50

1.6 Hydrophilic aluminums

Tube outside dia. and type

mm

φ7.94 Inner grooved copper tube

Coil length × height × width

mm

837×1100×38.1

Number of circuits

8 3

Outdoor air flow

m /h

6850

Outdoor noise level (sound pressure)

dB(A)

59

Outdoor unit

Refrigerant

Dimension(W×H×D)

mm

900×1167×340

Packing (W×H×D)

mm

1032×1307×443

Net/Gross weight

kg

106/111

Type Charged volume

R410A g

Throttle type MPa

capillary 4.2/1.5

Liquid side/ Gas side

mm

φ12.7/φ19

Max. pipe length

m

Design pressure Refrigerant piping

3200

50

Max. difference in level m 25 Ambient temp. ℃ cooling: 18~43; heating:-7~24 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Outdoor Units

105


Dimensions

MLCAC-UTSM-2010-10

2. Dimensions Model 38HN0181120A 38HN0241120A 38HN0361120A

A 760 842 990

B 530 560 624

Model 38HN0481190A 38HN0601190A

A 900 900

B 590 590

C 290 335 366

C 378 378

D 315 360 396

D 400 400

E 270 312 340

E 330 330

F 285 324 354

F 340 340

mm H 590 695 966

mm H 1167 1167

H

106

Outdoor Units


MLCAC-UTSM-2010-10

3.

Service Space

Service Space

Obstacle

Air inlet

>30cm

Air inlet

>30cm

>60cm

(Wall or obstacle)

Fix with bolt

Maintain channel >200cm

>60cm

Air outlet

Deep foundation Necessary width

600mm is necessary between 2 outdoor units

Outdoor Units

107


Wiring Diagrams

MLCAC-UTSM-2010-10

4. Wiring Diagrams 38HN0181120A

38HN0241120A

108

Outdoor Units


MLCAC-UTSM-2010-10

Wiring Diagrams

38HN0361120A

38HN0481190A

Outdoor Units

38HN0601190A

109


Electric Characteristics

MLCAC-UTSM-2010-10

5. Electric Characteristics Model

110

Outdoor Unit Hz

Voltage

Min.

Max.

38HN0181120A

50

220~240V

198V

254V

38HN0241120A

50

220~240V

198V

254V

38HN0361120A

50

220~240V

198V

254V

38HN0481190A

50

380~415V

342V

418V

38HN0601190A

50

380~415V

342V

418V

Outdoor Units


MLCAC-UTSM-2010-10

Operation Limits

6. Operation Limits Operation mode

Outdoor temperature(℃)

Room temperature(℃)

Cooling operation

18~43

17~30

Heating operation

-7~24

17~30

Cooling & Heating

Heating

Cooling 25 20

40 Outdoor temperature(℃ WB)

Outdoor temperature(℃ DB)

45

35 STD

30 25 20 15 10

15

20

25

30

Indoor temperature(℃ WB)

Outdoor Units

35

15 STD

10 5 0 -5 -10 10

15

20

25

30

35

Indoor temperature(℃ DB)

111


Sound Levels

MLCAC-UTSM-2010-10

7. Sound Levels 38HN0181120A 38HN0241120A 38HN0361120A 38HN0481190A

38HN0601190A

Outdoor Unit

Microphone

H

1.0m

Note: H= 0.5 Ă— height of outdoor unit

112

Note: The point A is in the middle of the whole outdoor panel.

Model

Noise level dB(A)

38HN0181120A

54

38HN0241120A

55

38HN0361120A

57

38HN0481190A

59

38HN0601190A

59

Outdoor Units


MLCAC-UTSM-2010-10

Troubleshooting

8. Troubleshooting 8.1. Self-diagnosis Indoor unit’s LED indication (1) For Big Four-way cassette

(2) For A5 Duct

Outdoor Units

113


Troubleshooting

MLCAC-UTSM-2010-10

(3) For AHU indoor unit The LED on indoor PCB Type

Contents

LED1

LED2

LED3

ERROR

Pipe Temp sensor error

Quick flash

Off

Off

ERROR

Wire controller input error

Quick flash

Off

Quick flash

(4)For CONSOLE

(5)For the other types indoor unit No.

Type

Contents

1

Normal

Standing-by

2

Normal

System Off

3

Normal

System startup

4

Normal

Forced cooling

5

Protection

Over current protection of the compressor occurs 4 times in 1h

114

LED Flashing Operation lamp flashes at 0.5Hz All lamps are off Operation lamp on Operation lamp flashes at 5Hz, Timer lamp on Lamps of operation, timer, defrosting (only fan) flashing simultaneously at 5Hz.

Remark

Nothing wrong with the unit when LED indicate these contents.

Whole unit is shut down. It cannot recover unless power is cut off Outdoor Units


MLCAC-UTSM-2010-10 6

Protection

7

Error

8

Error

9

Error

10

Error

11

Error

Troubleshooting Outdoor protection (lack of phase, phase sequence and temperature protection) Room temperature sensor checking channel is abnormal Evaporator sensor checking channel is abnormal Condenser sensor checking channel is abnormal Communication of EEPROM malfunction Water level alarm/pump sensor malfunction

All lamps flashing at 5Hz Timer lamp flashing at 5Hz Operation lamp flashing at 5Hz Defrosting lamp flashing at 5Hz Operation lamp and timer lamp flashing at 5Hz

Recover automatically after errors are eliminated (For T3 malfunction of 5HP, can’t recover automatically)

Alarm lamp flashes at 5Hz

LEDs’ for the indication of outdoor trouble Type

Contents

LED1

LED2

LED3

Trouble

Phase sequence

Flash

Off

Off

Trouble

Lack of phase(A,B)

Flash

Off

Off

Trouble

Lack of phase(C)

Off

Off

Off

Trouble

Protection of Low pressure

Flash

Flash

Off

Trouble

Overload of current

Off

Off

Flash

Trouble

Communication malfunction

Flash

Off

Flash

Trouble

Open-circuit and short-circuit trouble of T3

Off

Flash

Flash

Trouble

Open-circuit and short-circuit trouble of T4

Off

Flash

Off

Trouble

High temperature protection of condenser

Flash

Flash

Flash

Note: 1. If the LED1-LED3 are flashing slowly,means the system is stand-by. 2. T3: Outdoor condenser temperature sensor 3. T4: Outdoor ambient temperature sensor

Outdoor Units

115


Troubleshooting

MLCAC-UTSM-2010-10

8.2. Solving steps for typical malfunction (1) For indoor unit a. Indoor room temperature sensor is abnormal Indoor room temperature sensor is abnormal

No Whether the resistance of the room temp. sensor is 10K

Replace room temp. sensor

Yes Replace indoor PCB

b.

Evaporator temperature sensor is abnormal Evaporator temperature sensor is abnormal

No Whether the resistance of the evaporator temp. sensor is 10K

Replace evaporator temp. sensor

Yes Replace indoor PCB

c. Condenser temperature sensor is abnormal Condenser temperature sensor is abnormal

No Whether the resistance of the condenser temp. sensor is 10K

Replace condenser temp. sensor

Yes Replace indoor PCB

116

Outdoor Units


MLCAC-UTSM-2010-10

Troubleshooting

d. Outdoor unit malfunction Outdoor unit malfunction

No Whether the outdoor unit is power on

Check when the power is on

Yes No Measure whether the voltage of the communication line’s red and black end between the indoor and outdoor unit is +5V

Replace the outdoor unit board

Yes

Check the indoor unit main board CN5 or replace the main control board Yes Replace indoor PCB

e. EEPROM malfunction EEPROM malfunction

Yes EEPROM chip is broken

Replace EEPROM

No Yes Check whether the main control chip 9177 is broken

Replace 9177 chip

No

Check PCB board or replace the main control board

Outdoor Units

117


Troubleshooting

MLCAC-UTSM-2010-10

f. Full-water malfunction Full-water malfunction

No Check whether the water-level switch is inserted well

Insert the water-level switch well

Yes Yes Check whether the water-level switch is broken

Replace the water-level switch

No No Check whether the water pump is normal

Replace the water pump

Yes

Check PCB board or replace the main control board

g. Temperature sensor error of water pump E5

No Whether the resistance of the temp. sensor is 10K

Replace temp. sensor

Yes

Replace indoor PCB

118

Outdoor Units


MLCAC-UTSM-2010-10

Troubleshooting

(2) For the outdoor unit a. Phase sequence error: Phase sequence error

Change the order of two of the wires to power supply.

Switch on the unit again.

If the problem can not be solved, the outdoor PCB is defective b. Overload of current Overload of current

Check the current, normally Is the current in rated range?

No

Yes The outdoor PCB is defective

Possible reason 1. Outdoor fan is defective 2. The compressor is defective 3. Refrigerant is over charged 4. Air enter the refrigerant system 5. Heat exchanger is too dirty

c. Lack of phase Lack of phase

Check the power supply, is it 3 phase, 380-415V? Yes Check the connection between power supply and terminal, is the voltage in outdoor terminal is 3 phase, 380-415V? Yes Outdoor PCB is defective

Outdoor Units

119


Troubleshooting

MLCAC-UTSM-2010-10

d. Protection of pressure or temp. Protection of pressure or temp.

Yes Is it k1 or K2 open ?

Is temp. protective switch K1 open

Is pressure protective switch K2 open

Yes

Possible reason 1. The wires is loose to K1 2. Air or other gas in the refrigerant. 3. Heat exchanger is dirty 4. Outdoor fan or fan blade is defective 5. Outdoor unit is bad ventilation 6. Refrigerant is leakage 7. K1 switch is defective

Yes

Possible reason 1. The wires is loose to K2 2. Air or other gas in the refrigerant. 3. Heat exchanger is dirty 4. Outdoor fan or fan blade is defective 5. Outdoor unit is bad ventilation 6. Refrigerant is two much 7. K2 switch is defective

e. Open-circuit and short-circuit trouble of T3 Is connection to connector of temp. sensor good? No Yes

Repair connector

Check the resistance of the temp. sensor according to Annex 1

Is it the resistance is normal? Yes Indoor PCB is defective.

120

No

Replace the sensor

Outdoor Units


MLCAC-UTSM-2010-10

Troubleshooting

f. Open-circuit and short-circuit trouble of T4 Is connection to connector of temp. sensor good? No

Yes Check the resistance of the temp. sensor according to Annex 1

Repair connector

Is it the resistance is normal? No

Yes Indoor PCB is defective.

Replace the sensor

g. High temperature protection of condenser High temperature protection of condenser

Check the resistance of the temp. sensor according to Annex 1, is it normal?

Yes

Possible reason 1. Air or other gas in the refrigerant. 2. Heat exchanger is dirty 3. Outdoor fan or fan blade is defective 4. Outdoor unit is bad ventilation 5. Refrigerant is leakage 6. Outdoor PCB is defective

Outdoor Units

No

Replace the sensor

121


Troubleshooting

MLCAC-UTSM-2010-10

Appendix Indoor Temp. and Pipe Temp. Sensor Resistance Value Table

122

(℃--K)

K Ohm

K Ohm

K Ohm

K Ohm

-20

115.266

20

12.6431

60

2.35774

100

0.62973

-19

108.146

21

12.0561

61

2.27249

101

0.61148

-18

101.517

22

11.5000

62

2.19073

102

0.59386

-17

96.3423

23

10.9731

63

2.11241

103

0.57683

-16

89.5865

24

10.4736

64

2.03732

104

0.56038

-15

84.2190

25

10.000

65

1.96532

105

0.54448

-14

79.3110

26

9.55074

66

1.89627

106

0.52912

-13

74.5360

27

9.12445

67

1.83003

107

0.51426

-12

70.1698

28

8.71983

68

1.76647

108

0.49989

-11

66.0898

29

8.33566

69

1.70547

109

0.48600

-10

62.2756

30

7.97078

70

1.64691

110

0.47256

-9

58.7079

31

7.62411

71

1.59068

111

0.45957

-8

56.3694

32

7.29464

72

1.53668

112

0.44699

-7

52.2438

33

6.98142

73

1.48481

113

0.43482

-6

49.3161

34

6.68355

74

1.43498

114

0.42304

-5

46.5725

35

6.40021

75

1.38703

115

0.41164

-4

44.0000

36

6.13059

76

1.34105

116

0.40060

-3

41.5878

37

5.87359

77

1.29078

117

0.38991

-2

39.8239

38

5.62961

78

1.25423

118

0.37956

-1

37.1988

39

5.39689

79

1.21330

119

0.36954

0

35.2024

40

5.17519

80

1.17393

120

0.35982

1

33.3269

41

4.96392

81

1.13604

121

0.35042

2

31.5635

42

4.76253

82

1.09958

122

0.3413

3

29.9058

43

4.57050

83

1.06448

123

0.33246

4

28.3459

44

4.38736

84

1.03069

124

0.32390

5

26.8778

45

4.21263

85

0.99815

125

0.31559

6

25.4954

46

4.04589

86

0.96681

126

0.30754

7

24.1932

47

3.88673

87

0.93662

127

0.29974

8

22.5662

48

3.73476

88

0.90753

128

0.29216

9

21.8094

49

3.58962

89

0.87950

129

0.28482

10

20.7184

50

3.45097

90

0.85248

130

0.27770

11

19.6891

51

3.31847

91

0.82643

131

0.27078

12

18.7177

52

3.19183

92

0.80132

132

0.26408

13

17.8005

53

3.07075

93

0.77709

133

0.25757

14

16.9341

54

2.95896

94

0.75373

134

0.25125

15

16.1156

55

2.84421

95

0.73119

135

0.24512

16

15.3418

56

2.73823

96

0.70944

136

0.23916

17

14.6181

57

2.63682

97

0.68844

137

0.23338

18

13.9180

58

2.53973

98

0.66818

138

0.22776

19

13.2631

59

2.44677

99

0.64862

139

0.22231

Outdoor Units



Installation

MLCAC-UTSM-2010-10

Part 4 Installation 1.Precaution on Installation ................................................133 2.Vacuum Dry and Leakage Checking ...............................134 3.Additional Refrigerant Charge .........................................136 4.Water Drainage ................................................................137 5.Insulation Work ................................................................140 6.Wiring ...............................................................................141 7.Test Operation..................................................................142

132

Installation


MLCAC-UTSM-2010-10

Precaution on Installation

1. Precaution on Installation 1). Measure the necessary length of the connecting pipe, and make it by the following way. a.

Connect the indoor unit at first, then the outdoor unit. Bend the tubing in proper way. Do not harm them.

Specially Notice the pipe length/height/dimension of each capacity. Maximum pipe length Model 38HN0181120A ~38HN0241120A 38HN0361120A 38HN0481190A~38HN0601190A Piping sizes Model 38HN0181120A 38HN0241120A 38HN0361120A~38HN0601190A(Cooling & Heating)

Max. Length 25m

Max. Elevation 15m

30m 50m

20m 25m

Liquid(mm) 6.4

Gas(mm) 12.7

9.5

15.9

12.7

19

CAUTIONS

z Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds z With hands before fasten the flare nuts. z Be sure to use two wrenches simultaneously when you connect or disconnect the pipes. Flare dimension A Pipe gauge Tightening torque Flare shape Min (mm) Max 15~16N.m Φ6.4 8.3 8.7 (153~163 kgf.cm) 25~26N.m 12.0 12.4 Φ9.5 (255~265kgf.cm) 35~36N.m Φ12.7 15.4 15.8 (357~367kgf.cm) 45~47N.m Φ15.9 18.6 19.1 (459~480 kgf.cm) 65~67N.m Φ19.1 22.9 23.3 (663~684kgf.cm) b. The stop value of the outdoor unit should be closed absolutely (as original state). Every time you connect it, first loosen the nuts at the part of stop value, then connect the flare pipe immediately (in 5 minutes). If the nuts have been loosened for a long time, dusts and other impurities may enter the pipe system and may cause malfunction later. So please expel the air out of the pipe with refrigerant before connection. c.

Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten the nuts at the repair-points.

2)

Locate The Pipe

a.

Drill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the wall conduit and its cover.

b.

Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will cause water leakage by condensation.

c.

Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation to do no damage to the tubing.

3)

Connect the pipes.

4)

Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting the indoor unit with the outdoor unit in fluent flow.

5)

Be sure of no leakage by checking it with leak detector or soap water.

6)

Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and bind it well with the tapes to prevent leakage.

Installation

133


Vacuum Dry and Leakage Checking

MLCAC-UTSM-2010-10

2. Vacuum Dry and Leakage Checking 2.1 Vacuum Dry: use vacuum pump to change the moisture (liquid) into steam (gas) in the pipe and discharge it out of the pipe to make the pipe dry. Under one atmospheric pressure, the boiling point of water(steam temperature) is 100℃. Use vacuum pump to make the pressure in the pipe near vacuum state, the boiling point of water falls relatively. When it falls under outdoor temperature, the moisture in the pipe will be vaporized.

2.2 Vacuum dry procedure There are two methods of vacuum dry due to different construction environment: common vacuum dry, special vacuum dry. ①. Common vacuum dry procedure z Vacuum dry (for the first time)---connect the all-purpose detector to the inlet of liquid pipe and gas pipe, and run the vacuum pump more than two hours (the vacuum pump should be below -755mmHg) z If the pump can’t achieve below -755mmHg after pumping 2 hours, moisture or leakage point will still exist in the pipe. At this time, it should be pumped 1 hour more. z If the pump can’t achieve -755mmHg after pumping 3 hours, please check if there are some leakage points. z Vacuum placement test: place 1 hour when it achieves -755mmHg, pass if the vacuum watch shows no rising. If it rises, it shows there’s moisture or leakage point. z Vacuuming from liquid pipe and gas pipe at the same time. z Sketch map of common vacuum dry procedure.

134

Installation


MLCAC-UTSM-2010-10

Vacuum Dry and Leakage Checking

②. Special vacuum dry procedure z This vacuum dry method is used in the following conditions: z There’s moisture when flushing the refrigerant pipe. z Rainwater may enter into the pipe. z Vacuum dry for the first time ······ 2h pumping ③. Vacuum destroy for the second time ······ Fill nitrogen to 0.5Kgf/cm2 Because nitrogen is for drying gas, it has vacuum drying effect during vacuum destroy. But if the moisture is too much, this method can’t dry thoroughly. So, please pay more attention to prevent water entering and forming condensation water. ④. Vacuum

dry for the second time······1h pumping

Determinant: Pass if achieving below -755mmHg. If -755mmHg can’t be achieved in 2h, repeat procedure ③ and ④. ⑤.

Vacuum placing test ······ 1h

⑥. Sketch map of special vacuum dry procedure

Installation

135


Additional Refrigerant Charge

MLCAC-UTSM-2010-10

3. Additional Refrigerant Charge Caution ● Refrigerant cannot be charged until field wiring has been completed. ● Refrigerant may only be charged after performing the leak test and the vacuum pumping. ● When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in view of the danger of liquid hammer. ● Charging with an unsuitable substance may cause explosions and accidents, so always ensure that the appropriate refrigerant is charged. ● Refrigerant containers shall be opened slowly. ● Always use protective gloves and protect your eyes when charging refrigerant. The outdoor unit is factory charged with refrigerant. Calculate the added refrigerant according to the diameter and the length of the liquid side pipe of the outdoor unit/indoor unit R(g)

D(mm)

L(m) Less than 5m (One-way) Added Refrigerant When Over 5m(One-way)

φ6.4

Φ9.5

Φ12.7

11g/m×(L-5)

30g/m×(L-5)

60g/m×(L-5)

Remark: R (g): Additional refrigerant to be charged L (m): The length of the refrigerant pipe (one-way) D (mm): Liquid side piping diameter

136

Installation


MLCAC-UTSM-2010-10

Water Drainage

4. Water Drainage 4.1 Gradient and Supporting 4.1.1 Keep the drainpipe sloping downwards at a gradient of at least 1/100. Keep the drainpipe as short as possible and eliminate the air bubble. 4.1.2 The horizontal drainpipe should be short. When the pipe is too long, a prop stand must be installed to keep the gradient of 1/100 and prevent bending. Refer to the following table for the specification of the prop stand. Hard PVC pipe

Diameter

Distance between the prop stands

25~40mm

1.5~2m

4.1.3. Precautions ① The diameter of drainpipe should meet the drainage requirement at least. ② The drainpipe should be heat-insulated to prevent atomization. ③ Drainpipe should be installed before installing indoor unit. After powering on, there is some water in water-receiver plate. Please check if the drain pump can operate correctly. ④ All connection should be firm. ⑤ Wipe color on PVC pipe to note connection. ⑥ Climbing, horizontal and bending conditions are prohibited. ⑦ The dimension of drainpipe can’t less than the connecting dimension of indoor drainpipe. ⑧ Heat-insulation should be done well to prevent condensation. ⑨ Indoor units with different drainage type can’t share one convergent drainpipe.

4.2 Drainpipe Trap 4.2.1. If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe trap. 4.2.2. Every indoor unit needs one drainpipe trap. 4.2.3. A plug should be designed to do cleaning.

50cm 50cm

Plug

4.3 Upwards drainage (drain pump) For Four-way cassette(compact)

Installation

137


Water Drainage

MLCAC-UTSM-2010-10

For Four-way cassette

4.4 Convergent drainage 4.4.1. The number of indoor units should be as small as possible to prevent the traverse main pipe overlong. 4.4.2. Indoor unit with drain pump and indoor unit without drain pump should be in different drainage system.

4.4.3. Selecting the diameter Number of connecting indoor units→Calculate drainage volume→Select the diameter Calculate allowed volume =Total cooling capacity of indoor units(HP)×2 (l/ hr) Allowed volume(lean 1/50) (l/ hr) I.D. (mm) 集中排水管 Hard PVC ∽≤14 ¢25 Hard PVC 14<∽≤88 ¢30 Hard PVC 88<∽≤334 ¢40 Hard PVC 175<∽≤334 ¢50 Hard PVC 334<∽ ¢80

Thick 3.0 3.5 4.0 4.5 6.0

4.5 Drainage test 4.5.1Drainage without drain pump After finishing drainpipe installation, pour some water into the water receiver plate to check if the water flows smoothly. 4.5.2 Drainage with drain pump ① Poke the Water Level Switch, remove the cover, use water pipe to pour 2000ml water into the water receipt plate through the water inlet.

② Turn on the power to Cooling operation. Check the pump’s operation and switch on the Water Level Switch. Check the pump’s sound and look into the transparent hard pipe in the outlet at the same time to check if the water can discharge normally.

138

Installation


MLCAC-UTSM-2010-10

Water Drainage

③ Stop the air conditioner running, turn off the power, and put back the cover. Stop the air conditioner. After 3 minutes, check if it has abnormity. If the collocation of drainpipes is illogical, the water will flow back overfull, which will cause the alarm lamp flashes, even overflow from the water receipt plate. z Keep on pouring water until it gives an alarm signal for high water level, check if the pump drains water at once. If the water level can’t fall below the alarmed water level after 3 minutes, the air conditioner will stop. Turn off the power and drain the remained water, and then turn on the air conditioner. Note: the drain stuff in the main water receipt plate is for maintenance. Stuff up the drain stuff to prevent water leakage. z

Installation

139


Insulation Work

MLCAC-UTSM-2010-10

5. Insulation Work 5.1 Insulation material and thickness 5.1.1. Insulation material Insulation material should adopt the material which is able to endure the pipe’s temperature: no less than 70℃ in the high-pressure side, no less than 120℃ in the low-pressure side(For the cooling type machine, no requirements at the low-pressure side.)

Example: Heat pump type----Heat-resistant Polyethylene foam (withstand above 120℃) Cooling only type----Polyethylene foam (withstand above 100℃)

5.1.2. Thickness choice for insulation material Insulation material thickness is as follows:

Refrigerant pipe Drainage pipe

Pipe diameter (mm) Φ6.4—Φ25.4 Φ28.6—Φ38.1 Inner diameterΦ20—Φ32

Adiabatic material thickness 10mm 15mm 6mm

5.2 Refrigerant pipe insulation 5.2.1. Work Procedure ① Before laying the pipes, the non-jointing parts and non-connection parts should be heat insulated. ② When the gas proof test is eligible, the jointing area, expanding area and the flange area should be heat insulated 5.2.2. Insulation for non-jointing parts and non-connection parts wrong Gas pipe and liquid pipe should not be put together to insulate

140

right Insulate the gas pipe (cooling only)

Insulate the gas pipe and liquid pipe

Installation


MLCAC-UTSM-2010-10

Insulation Work

For construction convenience, before laying pipes, use insulation material to insulate the pipes to be deal with, at the same time, at two ends of the pipe, remain some length not to be insulated, in order to be welded and check the leakage after laying the pipes. 5.2.3. Insulate for the jointing area, expanding area and the flange area ① Insulate for the jointing area, expanding area and the flange area should be done after checking leakage of the pipes ② Make sure there’s no clearance in the joining part of the accessorial insulation material and local preparative insulation material.

5.3 Drainage pipe insulation The connection part should be insulated, or else water will be condensing at the non-insulation part.

5.4 Note 5.4.1 The jointing area, expanding area and the flange area should be heat insulated after passing the pressure test 5.4.2 The gas and liquid pipe should be heat insulated individually, the connecting part should be heat insulated individually. 5.4.3 Use the attached heat-insulation material to insulate the pipe connections (pipes’ tie-in ,expand nut ) of the indoor unit

6. Wiring Please refer to the Wiring Diagram.

Installation

141


Test Operation

MLCAC-UTSM-2010-10

7. Test Operation (1) The test operation must be carried out after the entire installation has been completed. (2) Please confirm the following points before the test operation. z The indoor unit and outdoor unit are installed properly. z Tubing and wiring are correctly completed. z The refrigerant pipe system is leakage-checked. z The drainage is unimpeded. z The ground wiring is connected correctly. z The length of the tubing and the added stow capacity of the refrigerant have been recorded. z The power voltage fits the rated voltage of the air conditioner. z There is no obstacle at the outlet and inlet of the outdoor and indoor units. z The gas-side and liquid-side stop values are both opened. z The air conditioner is pre-heated by turning on the power. (3) According to the user's requirement, install the remote controller when the remote controller's signal can reach the indoor unit smoothly. (4) Test operation Set the air conditioner under the mode of "COOLING" with the remote controller, and check the following points. Indoor unit z Whether the switch on the remote controller works well. z Whether the buttons on the remote controller works well. z Whether the air flow louver moves normally. z Whether the room temperature is adjusted well. z Whether the indicator lights normally. z Whether the temporary buttons works well. z Whether the drainage is normal. z Whether there is vibration or abnormal noise during operation. Outdoor unit z Whether there is vibration or abnormal noise during operation. z Whether the generated wind, noise, or condensed of by the air conditioner have influenced your neighborhood. z Whether any of the refrigerant is leaked.

142

Installation


MLCAC-UTSM-2010-10

Control

Part 5 Control 1. Wireless Remote Controller .........................................144

Control

143


MLCAC-UTSM-2010-10

Wireless Remote Controller

1. Wireless Remote Controller 1.1 R05/BGE The R05/BGE wireless remote controller is for Four-way cassette type and the Ceiling& floor type.

AUTO TE MP

C O OL

Mo de s etting

1

SET

DRY

2 Fan s peed se ttin g

SET

H E AT F AN

Ad jus t

4

3

Adj us t

FAN S P EED

MOD E

M

ON/OFF

5

Horiz swin g

7

Vert. swing

8

Reset

12

Loc k

13

Co ol/heat

15

SWIN G

AIR DIRE CTI ON

C LOC K

SW IN G

OK

TIME ON

EC O

TI ME OF F

6

Ai r dire cti on setting

9

Tim e settin g

10

Time ON

11

Ti me OFF

14

Confirm b utton

16

Economic operation

1.2 General Function for wireless remote controller: Model and Specification

144

Model

R05/BGE

Rated voltage

3.0V(2pieces of LR03 7# batteries)

Min voltage for sending signal of CPU

2.4V

Effective receiving distance

8m~11m

Operation condition

-5~60℃

Control


MLCAC-UTSM-2010-10

Wireless Remote Controller

Buttons and functions 1. MODE: Once pressing, running mode will be selected in the following sequence: AUTO COOL

DRY

HEAT FAN

NOTE: No heating mode for cool only type unit. 2. FAN SPEED: Fan speed will be selected in following sequence once pressing this button: AUTO LOW

MED

HIGH

3. Adjust

: Decrease the set temp. Keeping pressing will decrease the temp with 1℃ per 0.5s.

4. Adjust

: Increase the set temp. Keeping pressing will increase the temp with 1℃ per 0.5s.

5. ON/OFF: For turning on or turning off the air conditioner. 6. AIR DIRECTION: Activate swing function of air deflector. Once pressing, air deflector will turn 6°. For normal operation and better cooling and heating effect, deflector will not turn to the degree which is the state of deflector when the unit is turned off.( Only available when remote controller is used with corresponding unit.) 7. HORIZ SWING: Activate or turn off horizontal swing function. (Only available when remote controller is used with corresponding unit, i.e. Ceiling & floor type) 8. VERT SWING: Activate or turn off vertical swing function. (Only available when remote controller is used with corresponding unit.) 9. CLOCK: Display the current time. (12:00 is displayed when resetting or electrifying for the first time.) Press CLOCK for 5s, icon indicating hour will flash with 0.5s. Press it again; icon indicating minute will flash with 0.5s. and are used to adjust the figure. Setting or modification is effective only by pressing OK button to make confirmation. 10. TIME ON: For time ON setting. Once pressing this button, the time will increase by 0.5 hour. When the set time exceeds 10 hours, pressing the button will increase the time by 1 hour. Adjusting the figure to 0.00 will cancel time ON setting. 11. TIME OFF: For time OFF setting. Once pressing this button, the time will increase by 0.5 hour. When the set time exceeds 10 hours, pressing the button will increase the time by 1 hour. Adjust the figure to 0.00 will cancel time ON setting. 12. RESET (inner located): Press this button with a needle of 1mm to cancel the current setting and reset remote controller. 13. LOCK (inner located): Press this button with a needle of 1mm to lock or unlock the current setting. 14. OK: Used to confirm the time setting and modification. 15. COOL/HEAT (inner located): Press this button with a needle of 1mm to shift mode between COOL only and COOL&HEAT. During setting, background light will be lightened. Factory default mode is COOL &HEAT. 16. ECO: Activate or turn off economic operation mode. It is suggested to turn on this function when sleeping. (Only available when remote controller is used with corresponding unit.)

Control

145