Part 1 General Information .................................................................................................. 1 Part 2 Indoor Units ............................................................................................................... 8 Part 3 Outdoor Units ........................................................................................................ 100 Part 4 Installation.............................................................................................................. 132 Part 5 Control.................................................................................................................... 143
※The specifications, designs, and information in this book are subject to change without notice for product improvement. Contents
i
MLCAC-UTSM-2010-10
General Information
Part 1 General Information 1. Model Names of Indoor/Outdoor Units ...........................2 2. External Appearance ........................................................3 2.1 Indoor Units ................................................................................. 3 2.2 Outdoor Units .............................................................................. 4
3. Nomenclature ....................................................................5 4. Features .............................................................................7
General Information
1
Model Names of Indoor/Outdoor Units
MLCAC-UTSM-2010-10
1. Model Names of Indoor/Outdoor Units 1.1 Indoor Units R410A (capacity multiplied by 1000Btu/h) Type Four-way cassette ( t) Four-way cassette
Function
18
Cooling and heating
√
Cooling and heating
Ceiling & floor
Cooling and heating
Duct
Cooling and heating
√
24
36
48
60
√
√
√
√
√
√
√
√
√
√
√
1.2 Outdoor Units Model of outdoor unit and corresponding indoor unit Universal Outdoor unit Model Heat Pump
2
Compressor type
Compressor Brand
38HN0181120A
Rotary
GMCC
38HN0241120A
Rotary
GMCC
38HN0361120A
SCROLL
SANYO
38HN0481190A
SCROLL
SANYO
38HN0601190A
SCROLL
SANYO
Matched indoor units 42TLH0181001201 42FLH0181001201 42TNH0241001201 42FLH0241001201 42SMH0241011201 42TNH0361001201 42FLH0361001201 42SMH0361011201 42TNH0481001901 42FLH0481001901 42SMH0481011901 42FLH0601001901 42SMH0601011901
General Information
External Appearance
MLCAC-UTSM-2010-10
2.2 Outdoor Units 38HN0181120A
38HN0361120A
4
38HN0241120A
38HN0481190A~38HN0601190A
General Information
MLCAC-UTSM-2010-10
Nomenclature
3. Nomenclature 3.1 Indoor Unit DIGIT NO. CODE 1,2 Product Series Number 42: Central Station air handling unit-Packaged 3,4,5 Product Series Number SH/SM/SLH : Ducted for heat pump TN/TL/TSH : Cassette for heat pump FLH : Ceiling floor for cooling only and heat pump 6,7,8 Capacity The units(KW, BTUH,KCAL) should be defined in the business unit's model numbering policy, and depend on the product type and size 9 1: R410a Refrigerant 10 Option 0: Standard unit 11 Control 0: Wireless remote controller 1: Wired room controller 12 Market 1: For 50Hz market 13 Electrical characteristics 2: 220/240V-1PH-50HZ 9: 380V-3PH-50Hz 14 Model revision code 0: Original without revision 15 Environmental temperature 1:Temperate,T1
General Information
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
4 2 F L C 0 2 4 1 0 0 1 2 0 1
5
Nomenclature
MLCAC-UTSM-2010-10
3.2 Outdoor Unit DIGIT NO. CODE 1,2 Product Series Number 38: Condensing Unit (CDU)
1
2
3
4
5
6
7
8
9
10
11
12
3
8
H
N
0
2
4
1
1
2
0
A
3,4 Product Series Number HN: H: heat pump; N: universal CDU, for heat pump 5,6,7 Capacity The units(KW, BTUH,KCAL) should be defined in the business unit's model numbering policy, and depend on the product type and size 8 1: R410a Refrigerant 9 Market 1: For 50Hz market 10 Electrical characteristics 2: 220/240V-1PH-50HZ 9: 380V-3PH-50Hz 11 Model revision code 0: Original without revision 12 Product Discharge Number A:Side discharge,T1
6
General Information
MLCAC-UTSM-2010-10
Features
4. Features 4.1 High quality coils: The coil is constructed of advanced inner grooved copper tube and aluminum fins.
4.2 Anti-rust, 500 hours salt spray test. 4.3 Low operation sound level: Well-known stable and quiet running fan motor. 4.4 Well-known compressor. 4.5 Compact design: Smaller dimension and larger stuffing capacity. 4.6 Universal outdoor unit design. 4.7 Optional air outlet grille: plastic type and wire type.
Wire type
Plastic type
Plastic type
4.8 Optional low temperature cooling module. 4.9 R410A environment friendly refrigerant.
General Information
7
Indoor Units
MLCAC-UTSM-2010-10
Part 2 Indoor Units Four-way Cassette Type (Compact) ....................................9 Four-way Cassette Type .....................................................19 Ceiling & Floor Type ...........................................................35 Duct Type .............................................................................56
8
Indoor Units
MLCAC-UTSM-2010-10
New Four-way Cassette Type
Four-way Cassette Type (Compact) 1. Features ...........................................................................10 2. Specifications.................................................................. 11 3. Dimensions......................................................................12 4. Service Space ..................................................................13 5. Wiring Diagrams .............................................................14 6. Air Velocity and Temperature Distributions .................15 7. Electric Characteristics ..................................................16 8. Sound Levels...................................................................16 9. Accessories .....................................................................17 10. The Specification of Power ..........................................17 11. Field Wiring....................................................................18
New Four-way Cassette
9
Features
MLCAC-UTSM-2010-10
1. Features (1) Low operation noise ---Streamline plate ensures quietness ---Creates natural and comfortable environment (2) Efficient cooling ---Equal, fast and wide—range cooling (3) The adoption of the most advanced 3- Dimensional Screw fan ---Reduces the air resistance passing through ---Smoothes the air flow ---Makes air speed distribution to the heat exchange uniform
(4) Improvement for easy installation and maintenance ---Little space is required for installation into a shallow ceiling ---Because of the compactness and weight reduction of the main unit and panel, all models can be installed without a hoist
(5) 3600 Air Flow Panel 3600 air outlet makes equal,fast ad wide range cooling
(6) Inside E-box design The E-box is simply and safely build inside tge indoor unit, of witch ceiling side is 600mm*600mm. It is convenient to install and maintain. Checking the control part is easy, you only need to open the air return grille.
10
Four-way Cassette Type(Compact)
MLCAC-UTSM-2010-10
Specifications
2. Specifications Model
42TLH0181001201
Power supply Cooling
Heating
V-ph-Hz Capacity
kW
5.5
Input
kW
1.96
EER
W/W
2.81
Capacity
kW
5.9
Input
kW
1.83
COP
W/W
3.22
Model
YDK37-4P
Qty Indoor fan motor
1
Input
W
80/65/46
Capacitor
uF
2UF/400-450V
Speed(Hi/Mi/Lo)
r/min
1000/875/710
Number of rows
Indoor coil
220~240-1-50
2
Tube pitch(a)×row pitch(b)
mm
21×13.37
Fin spacing
mm
1.3
Fin type (code)
Hydrophilic aluminum
Tube outside dia. and type
mm
φ7Inner grooved copper tube
Coil length × height × width
mm
1370×210×26.74
Number of circuits
4 3
Indoor air flow (Hi/Mi/Lo)
m /h
860/760/500
Indoor noise level (sound pressure)
dB(A)
44/41/38
Indoor unit
Dimension (W×H×D)(body)
mm
570×260×570
Packing (W×H×D)(body)
mm
655×290×655
Dimension (W×H×D)(panel)
mm
647×50×647
Packing (W×H×D)(panel)
mm
705×113×705
Net/Gross weight(body)
kg
19/21
Net/Gross weight(panel)
kg
3/5
Refrigerant type
R410A
Design pressure Refrigerant piping
Liquid side/ Gas side
Drainage water pipe diameter Controller
MPa
4.2/1.5
mm
φ6.4/φ12.7
mm
ODφ25 R05/BGE (standard)
Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
Four-way Cassette Type(Compact)
11
Dimensions
MLCAC-UTSM-2010-10
3. Dimensions 42TLH0181001201
12
Four-way Cassette Type(Compact)
MLCAC-UTSM-2010-10
Service Space
4. Service Space
Four-way Cassette Type(Compact)
13
Wiring Diagrams
MLCAC-UTSM-2010-10
5. Wiring Diagrams 42TLH0181001201
14
Four-way Cassette Type(Compact)
MLCAC-UTSM-2010-10
Air Velocity and Temperature Distributions
6. Air Velocity and Temperature Distributions Airflow velocity
Temperature
Four-way Cassette Type(Compact)
15
Electric Characteristics
MLCAC-UTSM-2010-10
7. Electric Characteristics Hz
Voltage
Min.
Max.
Power Supply MFA
50
220-240V
198V
254V
25
Indoor Units
Model 42TLH0181001201 Remark: MFA: Max. Fuse Amps. (A)
8. Sound Levels FOUR-WAY CASSETTE TYPE
1.0m
Microphone
Model 42TLH0181001201
16
Noise level dB(A) H
M
L
44
41
38
Four-way Cassette Type(Compact)
MLCAC-UTSM-2010-10
Accessories
9. Accessories Name Installation fittings
Drainpipe Fittings
Remote controller & Its holder
Shape
Quantity
1. Expansible hook
4
2. Installation hook
4
3. Installation paper board
1
4. Out-let pipe sheath
1
5. Out-let pipe clasp
1
6. Tightening band
20
7. Drain joint
1
8. Remote controller
1
9. Remote controller holder
1
10. Mounting screw(ST2.9×10-C-H)
2
11. Alkaline dry batteries (AM4)
2
12. Owner's manual
1
13. Installation manual
1
Others
10. The Specification of Power Type
42TLH0181001201 Phase
Power
1-phase
Frequency and Voltage Circuit Breaker/ Fuse (A)
40/25 2
Indoor Unit Power Wiring (mm )
3×2.5 2
Ground wire(mm ) Indoor/Outdoor Connecting Wiring
2.5
Outdoor Unit Power Wiring Strong Electric Signal Weak Electric Signal (mm2)
Four-way Cassette Type(Compact)
220-240V, 50Hz
3×2.5 and 2×1.0 2-core shield wire 2×0.75
17
Field Wiring
MLCAC-UTSM-2010-10
11. Field Wiring
42TLH0181001201
18
Four-way Cassette Type(Compact)
MLCAC-UTSM-2010-10
Four-way Cassette Type
Four-way Cassette Type 1. Features ...........................................................................20 2. Specifications..................................................................20 3. Dimensions......................................................................26 4. Service Space ..................................................................27 5. Wiring Diagrams .............................................................28 6. Air Velocity and Temperature Distributions .................29 7. Electric Characteristics ..................................................30 8. Sound Levels...................................................................30 9. Accessories .....................................................................31 10. The Specification of Power ..........................................32 11. Field Wiring....................................................................33
Four-way Cassette Type
19
Features
MLCAC-UTSM-2010-10
1. Features (1) Low operation noise —Streamline plate ensures quietness —Creates natural and comfortable environment (2) Efficient cooling——Equal, fast and wide range cooling
(3) Excellent performance. The optimal evaporator & sufficient airflow volume guarantees the excellent capacity (4) The adoption of the most advanced 3- Dimensional Screw fan —Reduces the air resistance passing through —Smoothes the air flow —Makes air speed distribution to the heat exchange uniform
(5) Fresh air makes life healthier and more comfortable.
(6) Drainage pump can take up the condenser water to750mm.
(7) Ultra thin machine body to easy installation and maintenance. 18K~24K:230mm, 36~48K:300mm.
20
Four-way Cassette Type
MLCAC-UTSM-2010-10
Features
(8) Different color panels for choose: White、Gray、Blue、Black
(9) Swing angle of louver 1) Add one more swing motor, one motor driving two louvers. Controlling the interspace of each part, minimizing the angle loss. 2) The swing angle of the first louver are 40~42 degrees and the second louver are 37~38 degrees. New evaporator and inner configuration designed can acquire high heat-exchanger effect.
(10) More strengthening rib design around the panel, preventing the distortion for the panel.
(11) New outlet frame design to make the phenomena of coagulation great improvement: prevent the condensing water from damaging the air guide strip. (12) Adding rib on the panel of fan outlet, which can avoid the air outlet direct flow to people.
(13) 4 speeds available, optional super high fan speed design suitable for the large building over 3m high.
(14) Adding digital tube displaying on the display board. LED can display the Error Code to make the malfunction checking easier.
Four-way Cassette Type
21
Features
MLCAC-UTSM-2010-10
(15) Reserve spaces for air side-outlet, it is available to connect duct pipe hence air supplying from the four sides to nearby small room..
(16) The connecting pipe and drop height is higher. Max. pipe length up to 50m(refer to ①), and Max. drop height up to 30m(refer to ②).
(17) Optimal design, smaller Control Box, Space saving and convenient for wiring, Using fire resistance galvanized steel for E-box material. Metal box make the control part more stable and prevent damaging. (18) 360°air flow panel : 360°air flow delivery ensures uniform airflow distribution. 60K is standard, the others are optional.
22
Four-way Cassette Type
MLCAC-UTSM-2010-10
Specifications
2. Specifications Model
42TNH0241001201
Power supply Cooling
Heating
V-ph-Hz
220~240-1-50
Capacity
kW
7.6
Input
kW
2.47
EER
W/W
3.08
Capacity
kW
8.2
Input
kW
2.33
COP
W/W
3.52
Model
YDK80-6E
Qty Indoor fan motor
1
Input
W
120/100/90
Capacitor
uF
3.5uF/450V
r/min
800/550/400
Speed(Hi/Mi/Lo) Number of rows
Indoor coil
2
Tube pitch(a)×row pitch(b)
mm
21×13.37
Fin spacing
mm
1.5
Fin type (code)
Hydrophilic aluminum
Tube outside dia. and type
mm
φ7 Inner grooved copper tube
Coil length × height × width
mm
1990×168×26.74
Number of circuits
8
Indoor air flow (Hi/Mi/Lo)
3
m /h
1327/1114/871
Indoor noise level (sound pressure)
dB(A)
42/40/39
Dimension (W×H×D)(body)
mm
840×230×840
Packing (W×H×D)(body)
mm
900×250×900
Dimension (W×H×D)(panel)
mm
950×55×950
Packing (W×H×D)(panel)
mm
1035×90×1035
Net/Gross weight(body)
kg
24/30
Net/Gross weight(panel)
kg
6/9
Indoor unit
Refrigerant type
R410A
Design pressure Refrigerant piping
Liquid side/Gas side
Drainage water pipe diameter Controller
MPa
4.2/1.5
mm
φ9.5/φ15.9
mm
ODφ32 R05/BGE(standard)
Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
Four-way Cassette Type
23
Specifications
MLCAC-UTSM-2010-10 Model
42TNH0361001201
Power supply Cooling
Heating
V-ph-Hz Capacity
kW
10
Input
kW
3.79
EER
W/W
2.64
Capacity
kW
11
Input
kW
3.57
COP
W/W
Model
1
Input
W
143/116/100
Capacitor
uF
3.5uF/450V
r/min
770/640/550
Speed(Hi/Mi/Lo) Number of rows
Indoor coil
3.08 YDK90-6E
Qty Indoor fan motor
220~240-1-50
2
Tube pitch(a)×row pitch(b)
mm
Fin spacing
mm
Fin type (code)
21×13.37 1.5 Hydrophilic aluminum
Tube outside dia. and type
mm
φ7 Inner grooved copper tube
Coil length × height × width
mm
1990×252×26.74
Number of circuits
12 3
Indoor air flow (Hi/Mi/Lo)
m /h
Indoor noise level (sound pressure)
dB(A)
1545/1354/1187 44/42/41
Dimension (W×H×D)(body)
mm
840×300×840
Packing (W×H×D)(body)
mm
900×320×900
Dimension (W×H×D)(panel)
mm
950×55×950
Packing (W×H×D)(panel)
mm
1035×90×1035
Net/Gross weight(body)
kg
30/36
Net/Gross weight(panel)
kg
6/9
Indoor unit
Refrigerant type
R410A
Design pressure Refrigerant piping
Liquid side/Gas side
Drainage water pipe diameter Controller
MPa
4.2/1.5
mm
φ12.7/φ19
mm
ODφ32 R05/BGE(standard)
Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
24
Four-way Cassette Type
MLCAC-UTSM-2010-10
Specifications
Model
42TNH0481001901
Power supply
Cooling
Heating
V-ph-Hz
380~415-3-50
Capacity
kW
13
Input
kW
4.93
EER
W/W
2.64
Capacity
kW
14.3
Input
kW
5.42
COP
W/W
2.64
Model
YDK90-6E
Qty Indoor fan motor
1
Input
W
143/116/100
Capacitor
uF
3.5uF/450V
r/min
770/640/550
Speed(Hi/Mi/Lo) Number of rows
Indoor coil
2
Tube pitch(a)×row pitch(b)
mm
21×13.37
Fin spacing
mm
1.5
Fin type (code)
Hydrophilic aluminum
Tube outside dia.and type
mm
φ7 Inner grooved copper tube
Coil length × height × width
mm
1990×252×26.74
Number of circuits
12 3
Indoor air flow (Hi/Mi/Lo)
m /h
Indoor noise level (sound pressure)
dB(A)
1545/1354/1187 44/42/41
Dimension (W×H×D)(body)
mm
840×300×840
Packing (W×H×D)(body)
mm
900×320×900
Dimension (W×H×D)(panel)
mm
950×55×950
Packing (W×H×D)(panel)
mm
1035×90×1035
Net/Gross weight(body)
kg
30/36
Net/Gross weight(panel)
kg
6/9
Indoor unit
Refrigerant type
R410A
Design pressure Refrigerant piping
Liquid side/Gas side
Drainage water pipe diameter Controller
MPa
4.2/1.5
mm
φ12.7/φ19
mm
ODφ32 R05/BGE(standard)
Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
Four-way Cassette Type
25
Dimensions
MLCAC-UTSM-2010-10
3. Dimensions 42TNH0241001201 4-install hanger Gas side Liquid side
E-parts box
Pump inspect hole
Drain hole
42TNH0361001201
42TNH0481001901
4-install hanger Gas side Liquid side
E-parts box
Pump inspect hole
Drain hole
26
Four-way Cassette Type
MLCAC-UTSM-2010-10
Service Space
4. Service Space The indoor unit should be installed in a location that meets the following requirements: ● There is enough room for installation and maintenance. ● The ceiling is horizontal, and its structure can endure the weight of the indoor unit. ● The outlet and the inlet are not impeded, and the influence of external air is the least. ● The air flow can reach throughout the room. ● The connecting pipe and drainpipe could be extracted out easily. ● There is no direct radiation from heaters.
Four-way Cassette Type
27
Wiring Diagrams
MLCAC-UTSM-2010-10
5. Wiring Diagrams 5.1 42TNH0241001201
42TNH0361001201
5.2 42TNH0481001901
28
Four-way Cassette Type
MLCAC-UTSM-2010-10
Air Velocity and Temperature Distributions
6. Air Velocity and Temperature Distributions Airflow velocity
Temperature
Four-way Cassette Type
29
Electric Characteristics
MLCAC-UTSM-2010-10
7. Electric Characteristics Indoor Units
Model
Power Supply
Hz
Voltage
Min.
Max.
MFA
42TNH0241001201
50
220-240V
198V
254V
25
42TNH0361001201
50
220-240V
198V
254V
25
50
380-415V
342V
418V
15
42TNH0481001901 Remark: MFA: Max. Fuse Amps. (A)
8. Sound Levels FOUR-WAY CASSETTE TYPE
1.0m
Microphone
Model
30
Noise level dB(A) H
M
L
42TNH0241001201
42
40
39
42TNH0361001201
44
42
41
42TNH0481001901
44
42
41
Four-way Cassette Type
MLCAC-UTSM-2010-10
Accessories
9. Accessories Name
Installation Fittings
Tubing & Fittings
Drainpipe Fittings
Protect Pipe Fittings
Remote controller & Its Frame
Shape
Quantity
1. Expansible hook
4
2. Installation hook
4
3. Installation paper board
1
4. Bolt M5
4
5. Connecting pipe group
1
6. Binding tape
6
7.Soundproof/insulation sheath
2
8. Out-let pipe sheath
1
9. Out-let pipe clasp
1
10. Tightening band
20
11. Drain joint
1
12. Seal ring
1
13. Wall conduit
1
14. Wall conduit cover
1
15. Remote controller
1
16. Frame
1
17. Mounting screw(ST2.9Ă—10-C-H)
2
18. Alkaline dry batteries (AM4)
2
19. Owner's manual
1
20. Installation manual
1
Others
Four-way Cassette Type
31
The Specification of Power
MLCAC-UTSM-2010-10
10. The Specification of Power Type Power
Phase Frequency and Voltage
Circuit Breaker/ Fuse (A) Indoor Unit Power Wiring (mm2) Ground Wiring Outdoor Unit Indoor/Outdoor Power Wiring Connecting Wiring Strong 2 (mm ) Electric Signal Weak Electric Signal
32
42TNH0241001201 1-phase
42TNH0361001201 1-phase
42TNH0481001901 3-phase
220-240V, 50Hz
220-240V, 50Hz
380-415V, 50Hz
40/25 3×4.0
40/25 3×4.0
25/15 5×2.5
4.0
4.0
2.5
3×4.0
3×4.0
5×2.5
3×2.5
3×2.5
3×1.0
1-core shield wire 1×0.5
1-core shield wire 1×0.5
Four-way Cassette Type
MLCAC-UTSM-2010-10
Field Wiring
11. Field Wiring Wiring chart
42TNH0241001201
Four-way Cassette Type
42TNH0361001201
33
Field Wiring
MLCAC-UTSM-2010-10
42TNH0481001901
34
Four-way Cassette Type
MLCAC-UTSM-2010-10
Ceiling & Floor Type
Ceiling & Floor Type 1. Features ...........................................................................36 2. Specifications..................................................................37 3. Dimensions......................................................................42 4. Service Space ..................................................................43 5. Wiring Diagrams .............................................................44 6. Air Velocity and Temperature Distributions .................47 7. Electric Characteristics ..................................................49 8. Sound Levels...................................................................50 9. Accessories .....................................................................51 10. The Specification of Power ..........................................52 11. Field Wiring....................................................................53
Ceiling & Floor Type
35
MLCAC-UTSM-2010-10
Specifications
2. Specifications Model
42FLH0181001201
Power supply Cooling
Heating
V-ph-Hz
220~240-1-50
Capacity
kW
5.29
Input
kW
1.94
EER
W/W
2.73
Capacity
kW
5.82
Input
kW
1.61
COP
W/W
3.61
Model
YSK55-4L
Qty Indoor fan motor
1
Input
W
125/105/85
Capacitor
uF
2.5uF/450V
r/min
1310/1190/1040
Speed(Hi/Mi/Lo) Number of rows
Indoor coil
3
Tube pitch(a)×row pitch(b)
mm
21×13.37
Fin spacing
mm
1.3
Fin type (code)
Hydrophilic aluminum
Tube outside dia. and type
mm
Φ7 Inner grooved copper tube
Coil length× height× width
mm
804×252×40.11
Number of circuits
4
Indoor air flow(Hi/Mi/Lo)
3
m /h
800/600/500
Indoor noise level (sound pressure)
dB(A)
43/41/38
Dimension (W×H×D)
mm
990×203×660
Packing (W×H×D)
mm
1090×297×745
kg
26/32
Indoor unit
Net/Gross weight Refrigerant type
R410A
Design pressure Refrigerant piping
Liquid side/Gas side
Drainage water pipe diameter Controller
MPa
4.2/1.5
mm
φ6.4/φ12.7
mm
ODφ25 R05/BGE(standard)
Operation temperature 17-30 ℃ Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
Ceiling & Floor Type
37
Specifications
MLCAC-UTSM-2010-10
Model
42FLH0241001201
Power supply
V-ph-Hz
220~240-1-50
kW
6.90
kW W/W
2.46 2.81
kW
7.60
Input
kW
2.36
COP
W/W
3.22
Capacity Cooling
Input EER Capacity
Heating
Model
YSK55-4L
Qty Indoor fan motor
1
Input
W
125/105/85
Capacitor
uF
2.5uF/450V
r/min
1310/1190/1040
Speed(Hi/Mi/Lo) Number of rows
Indoor coil
3
Tube pitch(a)×row pitch(b)
mm
21×13.37
Fin spacing
mm
1.3
Fin type (code)
Hydrophilic aluminum
Tube outside dia. and type
mm
Coil length× height×width
mm
Number of circuits
Φ7 Inner grooved copper tube 804×252×40.11 4
Indoor air flow(Hi/Mi/Lo)
3
m /h
1200/900/700
Indoor noise level (sound pressure)
dB(A)
45/43/40
Dimension (W×H×D)
mm
990×203×660
Packing (W×H×D)
mm
1090×297×745
kg
27/33
Indoor unit
Net/Gross weight Refrigerant type
R410A
Design pressure Refrigerant piping
Liquid side/Gas side
Drainage water pipe diameter Controller
MPa
4.2/1.5
mm
φ9.5/φ15.9
mm
ODφ25 R05/BGE(standard)
Operation temperature 17-30 ℃ Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
38
Ceiling & Floor Type
MLCAC-UTSM-2010-10
Specifications
Model
42FLH0361001201
Power supply Cooling
Heating
V-ph-Hz
220~240-1-50
Capacity
kW
9.46
Input
kW
3.80
EER
W/W
2.49
Capacity
kW
10.60
Input
kW
3.93
COP
W/W
2.70
Model
YSK80-4A
Qty Indoor fan motor
1
Input
W
143/122/110
Capacitor
uF
3.5uF/450V
r/min
1310/1210/1115
Speed(Hi/Mi/Lo) Number of rows
Indoor coil
3
Tube pitch(a)×row pitch(b)
mm
25.4×22
Fin spacing
mm
1.7
Fin type (code)
Hydrophilic aluminum
Tube outside dia.and type
mm
φ9.53 Inner grooved copper tube
Coil length×height×width
mm
1094×254×66
Number of circuits
5
Indoor air flow(Hi/Mi/Lo)
3
m /h
1400/1200/1000
Indoor noise level (sound pressure)
dB(A)
45/43/40
Dimension (W×H×D)
mm
1280×203×660
Packing (W×H×D)
mm
1380×745×297
kg
35/42
Indoor unit
Net/Gross weight Refrigerant type
R410A
Design pressure Refrigerant piping
Liquid side/Gas side
Drainage water pipe diameter Controller
MPa
4.2/1.5
mm
φ12.7/φ19
mm
ODφ25 R05/BGE(standard)
Operation temperature 17-30 ℃ Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
Ceiling & Floor Type
39
Specifications
MLCAC-UTSM-2010-10
Model
42FLH0481001901
Power supply Cooling
Heating
V-ph-Hz
380~415-3-50
Capacity
kW
13.63
Input
kW
4.96
EER
W/W
2.75
Capacity
kW
15.00
Input
kW
4.55
COP
W/W
3.30
Model
YSK59-4D
Qty Indoor fan motor
2
Input
W
102/98/96
Capacitor
uF
2.5uF/450V
r/min
1230/1130/1070
Speed(Hi/Mi/Lo) Number of rows
Indoor coil
3
Tube pitch(a)×row pitch(b)
mm
25.4×22
Fin spacing
mm
1.7
Fin type (code)
Hydrophilic aluminium
Tube outside dia.and type
mm
φ9.53 Inner grooved copper tube
Coil length×height×width
mm
1360×254×66
Number of circuits
5
Indoor air flow(Hi/Mi/Lo)
3
m /h
2000/1800/1600
Indoor noise level (sound pressure)
dB(A)
50/47/45
Dimension (W×H×D)
mm
1670×240×680
Packing (W×H×D)
mm
1764×329×760
kg
50/58
Indoor unit
Net/Gross weight Refrigerant type
R410A
Design pressure Refrigerant piping
Liquid side/Gas side
Drainage water pipe diameter Controller
MPa
4.2/1.5
mm
φ12.7/φ19
mm
ODφ25 R05/BGE(standard)
Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
40
Ceiling & Floor Type
MLCAC-UTSM-2010-10
Specifications
Model
42FLH0601001901
Power supply Cooling
Heating
V-ph-Hz
380~415-3-50
Capacity
kW
14.90
Input
kW
5.59
EER
W/W
2.67
Capacity
kW
16.50
Input
kW
5.63
COP
W/W
2.93
Model
YSK59-4D
Qty Indoor fan motor
2
Input
W
89.5/81.5/77.5
Capacitor
uF
2.5uF/450V
r/min
1170/1070/995
Speed(Hi/Mi/Lo) Number of rows
Indoor coil
3
Tube pitch(a)×row pitch(b)
mm
25.4×22
Fin spacing
mm
1.7
Fin type (code)
Hydrophilic aluminium
Tube outside dia.and type
mm
φ9.53 Inner grooved copper tube
Coil length×height×width
mm
1360×254×66
Number of circuits
5
Indoor air flow(Hi/Mi/Lo)
3
m /h
2000/1800/1600
Indoor noise level (sound pressure)
dB(A)
50/49/47
Dimension (W×H×D)
mm
1670×240×680
Packing (W×H×D)
mm
1764×329×760
kg
52/59
Indoor unit
Net/Gross weight Refrigerant type
R410A
Design pressure Refrigerant piping
Liquid side/Gas side
Drainage water pipe diameter Controller
MPa
4.2/1.5
mm
φ12.7/φ19
mm
ODφ25 R05/BGE(standard)
Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
Ceiling & Floor Type
41
Dimensions
MLCAC-UTSM-2010-10
3. Dimensions a. Wall mounting installation
b. Ceiling installation
Model A B C 42FLH0181001201 990 660 203 42FLH0241001201 42FLH0361001201 1280 660 203 42FLH0481001901 1670 680 240 42FLH0601001901 Note: The dimension of 18000Btu/h and 24000Btu/h are the same. The dimension of 48000Btu/h and 60000Btu/h are the same. 42
D
E
F
G
505
506
907
200
795
506
1195
200
1070
450
1542
200
Ceiling & Floor Type
MLCAC-UTSM-2010-10
Service Space
4. Service Space
Ceiling & Floor Type
43
Wiring Diagrams
MLCAC-UTSM-2010-10
5. Wiring Diagrams 42FLH0181001201
44
Ceiling & Floor Type
MLCAC-UTSM-2010-10
42FLH0241001201
Ceiling & Floor Type
Wiring Diagrams
42FLH0361001201
45
Wiring Diagrams
42FLH0481001901
46
MLCAC-UTSM-2010-10
42FLH0601001901
Ceiling & Floor Type
MLCAC-UTSM-2010-10
Air Velocity and Temperature Distributions
6. Air Velocity and Temperature Distributions Discharge angle 60째 (CEILING)
Airflow velocity
Temperature
Ceiling & Floor Type
47
Air Velocity and Temperature Distributions
MLCAC-UTSM-2010-10
Discharge angle 60째(FLOOR)
Temperature
Airflow velocity
48
Ceiling & Floor Type
MLCAC-UTSM-2010-10
Electric Characteristics
7. Electric Characteristics Model
Indoor Units
Power Supply
Hz
Voltage
Min.
Max.
MFA
42FLH0181001201
50
220-240V
198V
254V
16
42FLH0241001201
50
220-240V
198V
254V
25
42FLH0361001201
50
220-240V
198V
254V
25
42FLH0481001901
50
380-415V
342V
418V
20
42FLH0601001901 Remark: MFA: Max. Fuse Amps. (A)
50
380-415V
342V
418V
20
Ceiling & Floor Type
49
Sound Levels
MLCAC-UTSM-2010-10
8. Sound Levels
Ceiling Model
50
Floor Noise level dB(A) H
M
L
42FLH0181001201
43
41
38
42FLH0241001201
45
43
40
42FLH0361001201
45
43
40
42FLH0481001901
50
47
45
42FLH0601001901
50
49
47
Ceiling & Floor Type
MLCAC-UTSM-2010-10
Accessories
9. Accessories Name
Installation fittings
Remote controller & Its holder
Others
Ceiling & Floor Type
Shape
Quantity
1.Hook
2
2.Hanging arm
2
3. Remote controller
1
4. Remote controller holder
1
5. Mounting screw (ST2.9Ă—10-C-H)
2
6. Alkaline dry batteries (AM4)
2
7. Owner's manual
1
8. Installation manual
1
9. Remote controller manual
1
51
The Specification of Power
MLCAC-UTSM-2010-10
10. The Specification of Power Cooling & Heating Phase
1-phase
42FLH0241001201 42FLH0361001201 1-phase
Frequency and Voltage
220-240V, 50Hz
220-240V, 50Hz
380-415V, 50Hz
Type Power
42FLH0181001201
Circuit Breaker/ Fuse (A)
20/16
40/25
40/20
2
3×2.5
3×2.5
5×2.5
Ground Wiring
2.5
2.5
2.5
3×2.5
5×2.5
3×2.5 1-core shield wire 1×0.5 mm2
3×2.5
Indoor Unit Power Wiring (mm )
Indoor/Outdoor 2 Connecting Wiring (mm )
Outdoor Unit Power Wiring Strong Electric Signal Weak Electric Signal
52
42FLH0481001901 42FLH0601001901 3-phase
5×2.5 1-core shield wire 2 1×0.5 mm
Ceiling & Floor Type
MLCAC-UTSM-2010-10
Field Wiring
11. Field Wiring
Ceiling & Floor Type
53
Field Wiring
MLCAC-UTSM-2010-10
42FLH0181001201
42FLH0241001201
54
Ceiling & Floor Type
MLCAC-UTSM-2010-10
Field Wiring
42FLH0361001201
42FLH0481001901
42FLH0601001901
、 Ceiling & Floor Type
55
Duct Type
MLCAC-UTSM-2010-06
Duct Type 1. Features ...........................................................................57 2. Specifications..................................................................58 3. Dimensions......................................................................62 4. Service Space ..................................................................63 5. Wiring Diagrams .............................................................64 6. Static Pressure ................................................................66 7. Electric Characteristics ..................................................68 8. Sound Levels...................................................................69 9. Accessories .....................................................................70 10. The Specification of Power ..........................................71 11. Field Wiring....................................................................72
56
Duct Type
MLCAC-UTSM-2010-10
Features
1. Features 1. Economic and convenient installation ---Several diffusers branch off from an indoor unit, adjusting the room temperature, which makes many rooms to be air-conditioned with only one indoor unit. ---All models feature thin design making them applicable to ceiling pocket that tends to be shallow 2. Optional accessories ---Including front clapboard, panel, canvas air passage, filter, etc..
Front boar
Panel
Canvas air passage
Filter
3. A long-life and high-efficiency filter 4. Way of air intake and inserting air filter ---Air intake can be positioned either at the back or below the unit. Similarly, the air filter also can be inserted either from the back or from the bottom of the unit.
Duct Type
57
Specifications
MLCAC-UTSM-2010-10
2. Specifications 42SMH0241011201
Model V-ph-Hz kW
220~240-1-50
Input
kW
2.60
EER
Power supply Capacity Cooling
Heating
W/W
2.73
Capacity
kW
7.60
Input
kW
2.37
COP
W/W
3.21 YSK74-4P
Model Qty Indoor fan motor
Input
1 W
Speed(Hi/Mi/Lo)
163/93/75 3.5UF/450V
Capacitor
Indoor coil
7.10
r/min
1000/750/680 4
Number of rows Tube pitch(a)×row pitch(b)
mm
Fin spacing
mm
1.5
mm
Hydrophilic aluminum φ7, Inner grooved copper tube
Fin type (code) Tube outside dia. and type Coil length × height × width
mm
21×13.37
735×252×53.48 6
Number of circuits 3
m /h
1400/1100/1000
Indoor external static pressure (Hi)
Pa
70
Indoor noise level (sound pressure) Dimension (W×H×D) Indoor unit Packing (W×H×D)
dB(A)
45/43/41
Indoor air flow(Hi/Mi/Lo)
mm
920x270x635
mm
1135x350x655
kg
28/34
Refrigerant type
R410A
Design pressure Refrigerant Liquid side/ Gas piping side
MPa
4.2/1.5
Drainage water pipe diameter
mm
Net/Gross weight
mm
φ9.5/φ15.9 ODφ25 Wireless Remote Controller
Controller Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
58
Duct Type
MLCAC-UTSM-2010-10
Specifications
42SMH0361011201
Model V-ph-Hz kW
220~240-1-50
Input
kW
4.09
EER
W/W
2.49
Capacity
kW
11.10
Input
kW
3.61
COP
W/W
3.08
Power supply Capacity Cooling
Heating
YSK140-4P
Model Qty Indoor fan motor
Input
1 W r/min
1070/790/710 4
Number of rows
Indoor coil
291/168/138 10uF/450V
Capacitor Speed(Hi/Mi/Lo)
10.20
Tube pitch(a)×row pitch(b)
mm
21×13.37
Fin spacing
mm
1.5 Hydrophilic aluminum
Fin type (code) Tube outside dia. and type
mm
φ7,inner grooved copper tube
Coil length × height × width
mm
955×336×53.48 8
Number of circuits m3/h
2270/1890/1650
Indoor external static pressure (Hi)
Pa
80
Indoor noise level (sound pressure)
dB(A)
46/44/42
Dimension (W×H×D)
mm
1140x270x775
Packing (W×H×D)
mm
1355x350x795
Net/Gross weight
kg
41/46
Refrigerant type
R410A
Design pressure
MPa
4.2/1.5
mm
φ12.7/φ19
mm
ODφ25
Indoor air flow(Hi/Mi/Lo)
Indoor unit
Refrigerant piping
Liquid side/ Gas side
Drainage water pipe diameter
Wireless Remote Controller Controller Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
Duct Type
59
Specifications
MLCAC-UTSM-2010-10
42SMH0481011901
Model V-ph-Hz kW
380~415-3-50
Input
kW
4.97
EER
W/W
2.75
Capacity
kW
14.40
Input
kW
4.27
COP
W/W
3.37
Power supply Capacity Cooling
Heating
YSK170-4P
Model Qty Indoor fan motor
Input
1 W r/min
1070/750/650 4
Number of rows
Indoor coil
356/201/152 10uF/450V
Capacitor Speed(Hi/Mi/Lo)
13.70
Tube pitch(a)×row pitch(b)
mm
21×13.37
Fin spacing
mm
1.5 Hydrophilic aluminum
Fin type (code) Tube outside dia. and type
mm
φ7,inner grooved copper tube
Coil length × height × width
mm
1030×378×53.48 8
Number of circuits m3/h
3010/2410/1940
Indoor external static pressure (Hi)
Pa
100
Indoor noise level (sound pressure)
dB(A)
47/45/43
Dimension (W×H×D)
mm
1200×300×865
Packing (W×H×D)
mm
1385×373×920
Net/Gross weight
kg
47/55
Refrigerant type
R410A
Design pressure
MPa
4.2/1.5
mm
φ12.7/φ19
mm
ODφ25
Indoor air flow(Hi/Mi/Lo)
Indoor unit
Refrigerant piping
Liquid side/ Gas side
Drainage water pipe diameter
Wireless Remote Controller Controller Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal); 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
60
Duct Type
MLCAC-UTSM-2010-10
Specifications
42SMH0601011901
Model V-ph-Hz kW
380~415-3-50
Input
kW
5.74
EER
W/W
2.58
Capacity
kW
16.00
Input
kW
4.98
COP
W/W
3.21
Power supply Capacity Cooling
Heating
YSK180-4P
Model Qty Indoor fan motor
Input
1 W r/min
1080/830/710 4
Number of rows
Indoor coil
355/223/173 10uF/450V
Capacitor Speed(Hi/Mi/Lo)
14.80
Tube pitch(a)×row pitch(b)
mm
21×13.37
Fin spacing
mm
1.5 Hydrophilic aluminum
Fin type (code) Tube outside dia. and type
mm
φ7 Inner grooved copper tube
Coil length × height × width
mm
1030×378×53.48 8
Number of circuits m3/h
3150/2510/1990
Indoor external static pressure (Hi)
Pa
100
Indoor noise level (sound pressure)
dB(A)
47/45/43
Dimension (W×H×D)
mm
1200×300×865
Packing (W×H×D)
mm
1385×373×920
Net/Gross weight
kg
47/55
Refrigerant type
R410A
Design pressure
MPa
4.2/1.5
mm
φ12.7/φ19
mm
ODφ25
Indoor air flow(Hi/Mi/Lo)
Indoor unit
Refrigerant piping
Liquid side/ Gas side
Drainage water pipe diameter
Wireless Remote Controller Controller Operation temperature ℃ 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal); 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
Duct Type
61
Dimensions
MLCAC-UTSM-2010-10
3. Dimensions
E
Air outlet o pening size F G H
42SMH0241011201
920
270
635
570
65
713
35
179
815
260
20
960
350
42SMH0361011201 42SMH0481011901 42SMH0601011901
1140
270
775
710
65
933
35
179
1035
260
20
1180
490
1200
300
865
800
80
968
40
204
1094
288
45
1240
500
Model
62
Outline dimension(mm) A B C D
Air return opening size I J K
Size of outline dimension mounted plug L M
Duct Type
MLCAC-UTSM-2010-10
ervice Space
4. Service Space Ensure enough space required for installation and maintenance.
There is enough space for installation and maintenance. The ceiling is horizontal, and its structure can endure the weight of the indoor unit. The outlet and the inlet are not impeded, and the influence of external air is the least. The air flow can reach throughout the room. The connecting pipe and drainpipe could be extracted out easily. There is no direct radiation from heater.
Duct Type
63
Wiring Diagrams
MLCAC-UTSM-2010-10
5. Wiring Diagrams 42SMH0241011201
64
42SMH0361011201
Duct Type
MLCAC-UTSM-2010-10
42SMH0481011901
Duct Type
Wiring Diagrams
42SMH0601011901
65
Static Pressure
MLCAC-UTSM-2010-10
6. Static Pressure 42SMH0241011201
42SMH0361011201 Pa
90
90
80
80
70 Super high speed
60 50
High speed
40
Mid speed
30
Low speed
70 60
40 30 20
10
10 800
900 1000 1100 1200 1300 1400 1500 Air volume(m3/h)
Super high speed High speed
50
20
700
66
External static pressure (Pa)
External static pressure (Pa)
Pa
Mid speed Low speed
1100 1200 1400 1600 1800 2000 2200 2400 Air volume(m3/h)
Duct Type
MLCAC-UTSM-2010-10
Static Pressure
42SMH0481011901
42SMH0601011901 Pa 120
Pa 120
110 110
100 100
90 90
External static pressure (Pa)
70 60 50
Super high speed High speed Mid speed Low speed
40 30
Super high speed
70 60 50 40
High speed
Mid speed Low speed
30 20
20
10
10
1000 1300 1600 1900 2200 2500 2800 3100 Air volume(m 3 /h)
Duct Type
External static pressure (Pa)
80 80
1000 1300 1600 1900 2200 2500 2800 3100 3400 Air volume(m3/h)
67
Electric Characteristics
MLCAC-UTSM-2010-10
7. Electric Characteristics Model
Indoor Units Hz
Voltage
Min.
Max.
MFA
42SMH0241011201
50
220-240V
198V
254V
25
42SMH0361011201
50
220-240V
198V
254V
30
42SMH0481011901
50
380-415V
342V
418V
30
380-415V
342V
418V
30
42SMH0601011901 50 Remark: MFA: Max. Fuse Amps. (A)
68
Power Supply
Duct Type
MLCAC-UTSM-2010-10
Sound Levels
8. Sound Levels Concealed Duct Type Discharge
Suction
Duct
Duct
1.4m
Microphone
Model
Duct Type
Noise level dB(A) H
M
L
42SMH0241011201
45
43
41
42SMH0361011201
46
44
42
42SMH0481011901
47
45
43
42SMH0601011901
47
45
43
69
Accessories
MLCAC-UTSM-2010-10
9. Accessories Name
Tubing & Fittings
Shape
Quantity
Soundproof/insulation sheath
2
Binding tape
1
Seal sponge
1
Drain joint
1
Seal ring
1
Wire controller
1
Owner's manual
1
Installation manual
1
Drainpipe Fittings
Wire controller
others
70
Duct Type
MLCAC-UTSM-2010-10
The Specification of Power
10. The Specification of Power Model
42SMH0481011901
42SMH0241011201
42SMH0361011201
1-Phase
1-Phase
3-Phase
220-240V,50Hz
220-240V,50Hz
380-415V, 50Hz
Circuit Breaker/Fuse(A)
30/25
35/30
40/30
Indoor unit power wiring(mm²)
3×2.5
3×4.0
5×4.0
2.5
4.0
4.0
Outdoor unit power wiring
3×2.5
3×4.0
5×4.0
Strong electric signal
3×1.5
3×1.5
3×1.5
Weak electric signal
2×0.75
2×0.75
Phase
42SMH0601011901
Power Frequency and Volt
Indoor/outdoor
Groud wiring
connecting wiring(mm² )
Duct Type
71
Field Wiring
MLCAC-UTSM-2010-10
11. Field Wiring
72
Duct Type
MLCAC-UTSM-2010-10
Field Wiring
42SMH0241011201
42SMH0361011201
Duct Type
73
Field Wiring
42SMH0481011901
74
MLCAC-UTSM-2010-10
42SMH0601011901
Duct Type
Outdoor Units
MLCAC-UTSM-2010-10
Part 3 Outdoor Units 1. Specifications ................................................................101 2. Dimensions....................................................................106 3. Service Space ................................................................107 4. Wiring Diagrams ...........................................................108 5. Electric Characteristics ................................................ 110 6. Operation Limits ........................................................... 111 7. Sound Levels................................................................. 112 8. Troubleshooting ............................................................ 113
100
Outdoor Units
MLCAC-UTSM-2010-10
Specifications
1. Specifications Model
38HN0181120A
Power supply
V-ph-Hz
Max. input consumption
W
Max. input current
A
PA225X2CS-4KU1
Type
Rotary
Brand
GMCC
Capacity
Btu/h
Input
W
Rated current(RLA)
A
1855/1940 8.7/8.7
Locked rotor Amp(LRA)
A
36.8
Thermal protector Capacitor
μF
50μF/440V-450V
Refrigerant oil
ml
ESTER OIL VG74 750 YDK48-6H(A)
Qty
1
Input
W
110
Capacitor
μF
3μF/450V
Speed
r/min
890
Tube pitch(a)× row pitch(b)
mm
21x13.37
Fin spacing
mm
1.4
Tube outside dia.and type
mm
Coil length × height × width
mm
Hydrophilic aluminum φ7, Inner grooved copper tube 658x546x26.74
Number of rows
Outdoor coil
18493/18698
Internal
Model Outdoor fan motor
2950 15
Model
Compressor
220~240-1-50
2
Fin type
Number of circuits Outdoor air flow
m /h
4 2439
Outdoor noise level (sound pressure)
dB(A)
54
Outdoor unit
Refrigerant
3
Dimension(W×H×D)
mm
760x590x285
Packing (W×H×D)
mm
887×645×355
Net/Gross weight
kg
Type Charged volume
g
Throttle type
Ambient temp.
1400 Capillary
Design pressure Refrigerant piping
39/42 R410a
MPa
4.2/1.5
Liquid side/ Gas side
mm
φ6.4/φ12.7
Max. pipe length
m
Max. difference in level
m
15
℃
cooling:18~43; heating:-7~24
25
Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
Outdoor Units
101
Specifications
MLCAC-UTSM-2010-10
Model
38HN0241120A
Power supply
V-ph-Hz
Max. input consumption
W
Max. input current
A
18 PA290X3CS-4MU1
Type
Rotary GMCC
Capacity
Btu/h
24498
Input
W
2430
Rated current(RLA)
A
11.4
Locked rotor Amp(LRA)
A
61
Capacitor
μF
Internal 50μF/440V-450V
Refrigerant oil
ml
ESTER OIL VG74/950
Thermal protector
Model
YDK100-6D
Qty Outdoor fan motor
1
Input
W
168.7
Capacitor
μF
5μF/450V
Speed
r/min
900
Tube pitch(a)× row pitch(b)
mm
21x13.37
Fin spacing
mm
1.4
Tube outside dia.and type
mm
Coil length × height × width
mm
Hydrophilic aluminum φ7, Inner grooved copper tube 785x651x26.74
Number of rows
Outdoor coil
3450
Model Brand
Compressor
220~240-1-50
2
Fin type
Number of circuits Outdoor air flow
m /h
4 3200
Outdoor noise level (sound pressure)
dB(A)
55
Outdoor unit
Refrigerant
3
Dimension(W×H×D)
mm
845×695×324
Packing (W×H×D)
mm
965×755×395
Net/Gross weight
kg
Type Charged volume
R410a g
Throttle type
Ambient temp.
1900 Capillary
Design pressure Refrigerant piping
53/57
MPa
4.2/1.5
Liquid side/ Gas side
mm
φ9.5/φ15.9
Max. pipe length
m
25
Max. difference in level
m
15
℃
cooling: 18~43; heating:-7~24
Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
102
Outdoor Units
MLCAC-UTSM-2010-10
Specifications
Model
38HN0361120A
Power supply
V-ph-Hz
Max. input consumption
W
4950
Max. input current
A
30
Model
C-SBN301H5D
Type
SCROLL
Brand
Compressor
SANYO
Capacity Input Rated current(RLA)
Btu/h W A
Locked rotor Amp(LRA)
A
Thermal protector μF
60μF/450V+90μF/400V
Refrigerant oil
ml
FV68S/1700 YDK190-6D
Qty Input Capacitor
W μF
Speed
r/min
Fin type Tube outside dia.and type Coil length × height × width Number of circuits
Outdoor air flow Outdoor noise level (sound pressure) Dimension(W×H×D) Outdoor unit
Packing
(W×H×D)
Net/Gross weight Refrigerant
mm mm
840 21x13.37 1.4 Hydrophilic aluminium
mm mm
φ7, Inner grooved copper tube 890x903x26.74
m3/h
7 5000
dB(A)
57
mm
990×966×354
mm
1120×1100×435
kg
94/98 R410a
g
2900
Type Charged volume
1 290 10μF/450V 1.5
Throttle type
Capillary
Design pressure Refrigerant piping
112
Capacitor
Number of rows Tube pitch(a)× row pitch(b) Fin spacing Outdoor coil
31902 3750 18.1 Internal
Model Outdoor fan motor
220~240-1-50
MPa
4.2/1.5 φ12.7/φ19
Liquid side/ Gas side
mm
Max. pipe length
m
30
Max. difference in level
m
20 cooling: 18~43; heating:-7~24
Ambient temp. ℃ Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
Outdoor Units
103
Specifications
MLCAC-UTSM-2010-10 Model
38HN0481190A
Power supply
V-ph-Hz
Max. input consumption
W
6300
Max. input current
A
10.5
Model
C-SBN373H8D
Type
Scroll
Brand
Compressor
Sanyo
Capacity
Btu/h
48109
Input
W
4750
Rated current(RLA)
A
8.22
Locked rotor Amp(LRA)
A
66
Thermal protector Capacitor
μF
Internal --
Refrigerant oil
ml
FV68S,1700
Model Outdoor fan motor
YDK65-6-1+YDK65-6F-1
Qty
2
Input
W
171×2
Capacitor
μF
(4μF/450V)×2
Speed
r/min
Number of rows Tube pitch(a)× row pitch(b) Fin spacing
mm
21×13.37
mm
1.4
825 2
Fin type Outdoor coil
380~415-3-50
Hydrophilic aluminums
Tube outside dia. and type
mm
φ7 Inner grooved copper tube
Coil length × height × width
mm
840×1113×26.74
Outdoor air flow
m3/h
4 6800
Outdoor noise level (sound pressure)
dB(A)
59
Number of circuits
Outdoor unit
Refrigerant
Dimension(W×H×D)
mm
900×1167×340
Packing (W×H×D)
mm
1032×1307×443
Net/Gross weight
kg
110/115
Type Charged volume
R410a g
Throttle type MPa
capillary 4.2/1.5
Liquid side/ Gas side
mm
φ12.7/φ19
Max. pipe length
m
50
Max. difference in level
m
25 cooling: 18~43; heating:-7~24
Design pressure Refrigerant piping
3250
Ambient temp. ℃ Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
104
Outdoor Units
MLCAC-UTSM-2010-10
Specifications
Model
38HN0601190A
Power supply
V-ph-Hz
Max. input consumption
W
7500
Max. input current
A
12.6
Model
C-SBN453H8D
Type
Scroll
Brand
Compressor
Sanyo
Capacity
Btu/h
Input
W
5750
Rated current(RLA)
A
9.77
Locked rotor Amp(LRA)
A
67
Thermal protector Capacitor
μF
Internal ---
Refrigerant oil
ml
FV68S, 1700
Model Outdoor fan motor
55956.8
YDK65-6+YDK65-6F
Qty
2
Input
W
148+140
Capacitor
μF
(3.5μF/450V)×2
Speed
r/min
800
Number of rows Tube pitch(a)× row pitch(b) Fin spacing
mm
22×19.05
2 mm
Fin type Outdoor coil
380~415-3-50
1.6 Hydrophilic aluminums
Tube outside dia. and type
mm
φ7.94 Inner grooved copper tube
Coil length × height × width
mm
837×1100×38.1
Number of circuits
8 3
Outdoor air flow
m /h
6850
Outdoor noise level (sound pressure)
dB(A)
59
Outdoor unit
Refrigerant
Dimension(W×H×D)
mm
900×1167×340
Packing (W×H×D)
mm
1032×1307×443
Net/Gross weight
kg
106/111
Type Charged volume
R410A g
Throttle type MPa
capillary 4.2/1.5
Liquid side/ Gas side
mm
φ12.7/φ19
Max. pipe length
m
Design pressure Refrigerant piping
3200
50
Max. difference in level m 25 Ambient temp. ℃ cooling: 18~43; heating:-7~24 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
Outdoor Units
105
Dimensions
MLCAC-UTSM-2010-10
2. Dimensions Model 38HN0181120A 38HN0241120A 38HN0361120A
A 760 842 990
B 530 560 624
Model 38HN0481190A 38HN0601190A
A 900 900
B 590 590
C 290 335 366
C 378 378
D 315 360 396
D 400 400
E 270 312 340
E 330 330
F 285 324 354
F 340 340
mm H 590 695 966
mm H 1167 1167
H
106
Outdoor Units
MLCAC-UTSM-2010-10
3.
Service Space
Service Space
Obstacle
Air inlet
>30cm
Air inlet
>30cm
>60cm
(Wall or obstacle)
Fix with bolt
Maintain channel >200cm
>60cm
Air outlet
Deep foundation Necessary width
600mm is necessary between 2 outdoor units
Outdoor Units
107
Wiring Diagrams
MLCAC-UTSM-2010-10
4. Wiring Diagrams 38HN0181120A
38HN0241120A
108
Outdoor Units
MLCAC-UTSM-2010-10
Wiring Diagrams
38HN0361120A
38HN0481190A
Outdoor Units
38HN0601190A
109
Electric Characteristics
MLCAC-UTSM-2010-10
5. Electric Characteristics Model
110
Outdoor Unit Hz
Voltage
Min.
Max.
38HN0181120A
50
220~240V
198V
254V
38HN0241120A
50
220~240V
198V
254V
38HN0361120A
50
220~240V
198V
254V
38HN0481190A
50
380~415V
342V
418V
38HN0601190A
50
380~415V
342V
418V
Outdoor Units
MLCAC-UTSM-2010-10
Operation Limits
6. Operation Limits Operation mode
Outdoor temperature(℃)
Room temperature(℃)
Cooling operation
18~43
17~30
Heating operation
-7~24
17~30
Cooling & Heating
Heating
Cooling 25 20
40 Outdoor temperature(℃ WB)
Outdoor temperature(℃ DB)
45
35 STD
30 25 20 15 10
15
20
25
30
Indoor temperature(℃ WB)
Outdoor Units
35
15 STD
10 5 0 -5 -10 10
15
20
25
30
35
Indoor temperature(℃ DB)
111
Sound Levels
MLCAC-UTSM-2010-10
7. Sound Levels 38HN0181120A 38HN0241120A 38HN0361120A 38HN0481190A
38HN0601190A
Outdoor Unit
Microphone
H
1.0m
Note: H= 0.5 Ă— height of outdoor unit
112
Note: The point A is in the middle of the whole outdoor panel.
Model
Noise level dB(A)
38HN0181120A
54
38HN0241120A
55
38HN0361120A
57
38HN0481190A
59
38HN0601190A
59
Outdoor Units
MLCAC-UTSM-2010-10
Troubleshooting
8. Troubleshooting 8.1. Self-diagnosis Indoor unit’s LED indication (1) For Big Four-way cassette
(2) For A5 Duct
Outdoor Units
113
Troubleshooting
MLCAC-UTSM-2010-10
(3) For AHU indoor unit The LED on indoor PCB Type
Contents
LED1
LED2
LED3
ERROR
Pipe Temp sensor error
Quick flash
Off
Off
ERROR
Wire controller input error
Quick flash
Off
Quick flash
(4)For CONSOLE
(5)For the other types indoor unit No.
Type
Contents
1
Normal
Standing-by
2
Normal
System Off
3
Normal
System startup
4
Normal
Forced cooling
5
Protection
Over current protection of the compressor occurs 4 times in 1h
114
LED Flashing Operation lamp flashes at 0.5Hz All lamps are off Operation lamp on Operation lamp flashes at 5Hz, Timer lamp on Lamps of operation, timer, defrosting (only fan) flashing simultaneously at 5Hz.
Remark
Nothing wrong with the unit when LED indicate these contents.
Whole unit is shut down. It cannot recover unless power is cut off Outdoor Units
MLCAC-UTSM-2010-10 6
Protection
7
Error
8
Error
9
Error
10
Error
11
Error
Troubleshooting Outdoor protection (lack of phase, phase sequence and temperature protection) Room temperature sensor checking channel is abnormal Evaporator sensor checking channel is abnormal Condenser sensor checking channel is abnormal Communication of EEPROM malfunction Water level alarm/pump sensor malfunction
All lamps flashing at 5Hz Timer lamp flashing at 5Hz Operation lamp flashing at 5Hz Defrosting lamp flashing at 5Hz Operation lamp and timer lamp flashing at 5Hz
Recover automatically after errors are eliminated (For T3 malfunction of 5HP, can’t recover automatically)
Alarm lamp flashes at 5Hz
LEDs’ for the indication of outdoor trouble Type
Contents
LED1
LED2
LED3
Trouble
Phase sequence
Flash
Off
Off
Trouble
Lack of phase(A,B)
Flash
Off
Off
Trouble
Lack of phase(C)
Off
Off
Off
Trouble
Protection of Low pressure
Flash
Flash
Off
Trouble
Overload of current
Off
Off
Flash
Trouble
Communication malfunction
Flash
Off
Flash
Trouble
Open-circuit and short-circuit trouble of T3
Off
Flash
Flash
Trouble
Open-circuit and short-circuit trouble of T4
Off
Flash
Off
Trouble
High temperature protection of condenser
Flash
Flash
Flash
Note: 1. If the LED1-LED3 are flashing slowly,means the system is stand-by. 2. T3: Outdoor condenser temperature sensor 3. T4: Outdoor ambient temperature sensor
Outdoor Units
115
Troubleshooting
MLCAC-UTSM-2010-10
8.2. Solving steps for typical malfunction (1) For indoor unit a. Indoor room temperature sensor is abnormal Indoor room temperature sensor is abnormal
No Whether the resistance of the room temp. sensor is 10K
Replace room temp. sensor
Yes Replace indoor PCB
b.
Evaporator temperature sensor is abnormal Evaporator temperature sensor is abnormal
No Whether the resistance of the evaporator temp. sensor is 10K
Replace evaporator temp. sensor
Yes Replace indoor PCB
c. Condenser temperature sensor is abnormal Condenser temperature sensor is abnormal
No Whether the resistance of the condenser temp. sensor is 10K
Replace condenser temp. sensor
Yes Replace indoor PCB
116
Outdoor Units
MLCAC-UTSM-2010-10
Troubleshooting
d. Outdoor unit malfunction Outdoor unit malfunction
No Whether the outdoor unit is power on
Check when the power is on
Yes No Measure whether the voltage of the communication line’s red and black end between the indoor and outdoor unit is +5V
Replace the outdoor unit board
Yes
Check the indoor unit main board CN5 or replace the main control board Yes Replace indoor PCB
e. EEPROM malfunction EEPROM malfunction
Yes EEPROM chip is broken
Replace EEPROM
No Yes Check whether the main control chip 9177 is broken
Replace 9177 chip
No
Check PCB board or replace the main control board
Outdoor Units
117
Troubleshooting
MLCAC-UTSM-2010-10
f. Full-water malfunction Full-water malfunction
No Check whether the water-level switch is inserted well
Insert the water-level switch well
Yes Yes Check whether the water-level switch is broken
Replace the water-level switch
No No Check whether the water pump is normal
Replace the water pump
Yes
Check PCB board or replace the main control board
g. Temperature sensor error of water pump E5
No Whether the resistance of the temp. sensor is 10K
Replace temp. sensor
Yes
Replace indoor PCB
118
Outdoor Units
MLCAC-UTSM-2010-10
Troubleshooting
(2) For the outdoor unit a. Phase sequence error: Phase sequence error
Change the order of two of the wires to power supply.
Switch on the unit again.
If the problem can not be solved, the outdoor PCB is defective b. Overload of current Overload of current
Check the current, normally Is the current in rated range?
No
Yes The outdoor PCB is defective
Possible reason 1. Outdoor fan is defective 2. The compressor is defective 3. Refrigerant is over charged 4. Air enter the refrigerant system 5. Heat exchanger is too dirty
c. Lack of phase Lack of phase
Check the power supply, is it 3 phase, 380-415V? Yes Check the connection between power supply and terminal, is the voltage in outdoor terminal is 3 phase, 380-415V? Yes Outdoor PCB is defective
Outdoor Units
119
Troubleshooting
MLCAC-UTSM-2010-10
d. Protection of pressure or temp. Protection of pressure or temp.
Yes Is it k1 or K2 open ?
Is temp. protective switch K1 open
Is pressure protective switch K2 open
Yes
Possible reason 1. The wires is loose to K1 2. Air or other gas in the refrigerant. 3. Heat exchanger is dirty 4. Outdoor fan or fan blade is defective 5. Outdoor unit is bad ventilation 6. Refrigerant is leakage 7. K1 switch is defective
Yes
Possible reason 1. The wires is loose to K2 2. Air or other gas in the refrigerant. 3. Heat exchanger is dirty 4. Outdoor fan or fan blade is defective 5. Outdoor unit is bad ventilation 6. Refrigerant is two much 7. K2 switch is defective
e. Open-circuit and short-circuit trouble of T3 Is connection to connector of temp. sensor good? No Yes
Repair connector
Check the resistance of the temp. sensor according to Annex 1
Is it the resistance is normal? Yes Indoor PCB is defective.
120
No
Replace the sensor
Outdoor Units
MLCAC-UTSM-2010-10
Troubleshooting
f. Open-circuit and short-circuit trouble of T4 Is connection to connector of temp. sensor good? No
Yes Check the resistance of the temp. sensor according to Annex 1
Repair connector
Is it the resistance is normal? No
Yes Indoor PCB is defective.
Replace the sensor
g. High temperature protection of condenser High temperature protection of condenser
Check the resistance of the temp. sensor according to Annex 1, is it normal?
Yes
Possible reason 1. Air or other gas in the refrigerant. 2. Heat exchanger is dirty 3. Outdoor fan or fan blade is defective 4. Outdoor unit is bad ventilation 5. Refrigerant is leakage 6. Outdoor PCB is defective
Outdoor Units
No
Replace the sensor
121
Troubleshooting
MLCAC-UTSM-2010-10
Appendix Indoor Temp. and Pipe Temp. Sensor Resistance Value Table
122
(℃--K)
℃
K Ohm
℃
K Ohm
℃
K Ohm
℃
K Ohm
-20
115.266
20
12.6431
60
2.35774
100
0.62973
-19
108.146
21
12.0561
61
2.27249
101
0.61148
-18
101.517
22
11.5000
62
2.19073
102
0.59386
-17
96.3423
23
10.9731
63
2.11241
103
0.57683
-16
89.5865
24
10.4736
64
2.03732
104
0.56038
-15
84.2190
25
10.000
65
1.96532
105
0.54448
-14
79.3110
26
9.55074
66
1.89627
106
0.52912
-13
74.5360
27
9.12445
67
1.83003
107
0.51426
-12
70.1698
28
8.71983
68
1.76647
108
0.49989
-11
66.0898
29
8.33566
69
1.70547
109
0.48600
-10
62.2756
30
7.97078
70
1.64691
110
0.47256
-9
58.7079
31
7.62411
71
1.59068
111
0.45957
-8
56.3694
32
7.29464
72
1.53668
112
0.44699
-7
52.2438
33
6.98142
73
1.48481
113
0.43482
-6
49.3161
34
6.68355
74
1.43498
114
0.42304
-5
46.5725
35
6.40021
75
1.38703
115
0.41164
-4
44.0000
36
6.13059
76
1.34105
116
0.40060
-3
41.5878
37
5.87359
77
1.29078
117
0.38991
-2
39.8239
38
5.62961
78
1.25423
118
0.37956
-1
37.1988
39
5.39689
79
1.21330
119
0.36954
0
35.2024
40
5.17519
80
1.17393
120
0.35982
1
33.3269
41
4.96392
81
1.13604
121
0.35042
2
31.5635
42
4.76253
82
1.09958
122
0.3413
3
29.9058
43
4.57050
83
1.06448
123
0.33246
4
28.3459
44
4.38736
84
1.03069
124
0.32390
5
26.8778
45
4.21263
85
0.99815
125
0.31559
6
25.4954
46
4.04589
86
0.96681
126
0.30754
7
24.1932
47
3.88673
87
0.93662
127
0.29974
8
22.5662
48
3.73476
88
0.90753
128
0.29216
9
21.8094
49
3.58962
89
0.87950
129
0.28482
10
20.7184
50
3.45097
90
0.85248
130
0.27770
11
19.6891
51
3.31847
91
0.82643
131
0.27078
12
18.7177
52
3.19183
92
0.80132
132
0.26408
13
17.8005
53
3.07075
93
0.77709
133
0.25757
14
16.9341
54
2.95896
94
0.75373
134
0.25125
15
16.1156
55
2.84421
95
0.73119
135
0.24512
16
15.3418
56
2.73823
96
0.70944
136
0.23916
17
14.6181
57
2.63682
97
0.68844
137
0.23338
18
13.9180
58
2.53973
98
0.66818
138
0.22776
19
13.2631
59
2.44677
99
0.64862
139
0.22231
Outdoor Units
Installation
MLCAC-UTSM-2010-10
Part 4 Installation 1.Precaution on Installation ................................................133 2.Vacuum Dry and Leakage Checking ...............................134 3.Additional Refrigerant Charge .........................................136 4.Water Drainage ................................................................137 5.Insulation Work ................................................................140 6.Wiring ...............................................................................141 7.Test Operation..................................................................142
132
Installation
MLCAC-UTSM-2010-10
Precaution on Installation
1. Precaution on Installation 1). Measure the necessary length of the connecting pipe, and make it by the following way. a.
Connect the indoor unit at first, then the outdoor unit. Bend the tubing in proper way. Do not harm them.
Specially Notice the pipe length/height/dimension of each capacity. Maximum pipe length Model 38HN0181120A ~38HN0241120A 38HN0361120A 38HN0481190A~38HN0601190A Piping sizes Model 38HN0181120A 38HN0241120A 38HN0361120A~38HN0601190A(Cooling & Heating)
Max. Length 25m
Max. Elevation 15m
30m 50m
20m 25m
Liquid(mm) 6.4
Gas(mm) 12.7
9.5
15.9
12.7
19
CAUTIONS
z Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds z With hands before fasten the flare nuts. z Be sure to use two wrenches simultaneously when you connect or disconnect the pipes. Flare dimension A Pipe gauge Tightening torque Flare shape Min (mm) Max 15~16N.m Φ6.4 8.3 8.7 (153~163 kgf.cm) 25~26N.m 12.0 12.4 Φ9.5 (255~265kgf.cm) 35~36N.m Φ12.7 15.4 15.8 (357~367kgf.cm) 45~47N.m Φ15.9 18.6 19.1 (459~480 kgf.cm) 65~67N.m Φ19.1 22.9 23.3 (663~684kgf.cm) b. The stop value of the outdoor unit should be closed absolutely (as original state). Every time you connect it, first loosen the nuts at the part of stop value, then connect the flare pipe immediately (in 5 minutes). If the nuts have been loosened for a long time, dusts and other impurities may enter the pipe system and may cause malfunction later. So please expel the air out of the pipe with refrigerant before connection. c.
Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten the nuts at the repair-points.
2)
Locate The Pipe
a.
Drill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the wall conduit and its cover.
b.
Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will cause water leakage by condensation.
c.
Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation to do no damage to the tubing.
3)
Connect the pipes.
4)
Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting the indoor unit with the outdoor unit in fluent flow.
5)
Be sure of no leakage by checking it with leak detector or soap water.
6)
Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and bind it well with the tapes to prevent leakage.
Installation
133
Vacuum Dry and Leakage Checking
MLCAC-UTSM-2010-10
2. Vacuum Dry and Leakage Checking 2.1 Vacuum Dry: use vacuum pump to change the moisture (liquid) into steam (gas) in the pipe and discharge it out of the pipe to make the pipe dry. Under one atmospheric pressure, the boiling point of water(steam temperature) is 100℃. Use vacuum pump to make the pressure in the pipe near vacuum state, the boiling point of water falls relatively. When it falls under outdoor temperature, the moisture in the pipe will be vaporized.
2.2 Vacuum dry procedure There are two methods of vacuum dry due to different construction environment: common vacuum dry, special vacuum dry. ①. Common vacuum dry procedure z Vacuum dry (for the first time)---connect the all-purpose detector to the inlet of liquid pipe and gas pipe, and run the vacuum pump more than two hours (the vacuum pump should be below -755mmHg) z If the pump can’t achieve below -755mmHg after pumping 2 hours, moisture or leakage point will still exist in the pipe. At this time, it should be pumped 1 hour more. z If the pump can’t achieve -755mmHg after pumping 3 hours, please check if there are some leakage points. z Vacuum placement test: place 1 hour when it achieves -755mmHg, pass if the vacuum watch shows no rising. If it rises, it shows there’s moisture or leakage point. z Vacuuming from liquid pipe and gas pipe at the same time. z Sketch map of common vacuum dry procedure.
134
Installation
MLCAC-UTSM-2010-10
Vacuum Dry and Leakage Checking
②. Special vacuum dry procedure z This vacuum dry method is used in the following conditions: z There’s moisture when flushing the refrigerant pipe. z Rainwater may enter into the pipe. z Vacuum dry for the first time ······ 2h pumping ③. Vacuum destroy for the second time ······ Fill nitrogen to 0.5Kgf/cm2 Because nitrogen is for drying gas, it has vacuum drying effect during vacuum destroy. But if the moisture is too much, this method can’t dry thoroughly. So, please pay more attention to prevent water entering and forming condensation water. ④. Vacuum
dry for the second time······1h pumping
Determinant: Pass if achieving below -755mmHg. If -755mmHg can’t be achieved in 2h, repeat procedure ③ and ④. ⑤.
Vacuum placing test ······ 1h
⑥. Sketch map of special vacuum dry procedure
Installation
135
Additional Refrigerant Charge
MLCAC-UTSM-2010-10
3. Additional Refrigerant Charge Caution ● Refrigerant cannot be charged until field wiring has been completed. ● Refrigerant may only be charged after performing the leak test and the vacuum pumping. ● When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in view of the danger of liquid hammer. ● Charging with an unsuitable substance may cause explosions and accidents, so always ensure that the appropriate refrigerant is charged. ● Refrigerant containers shall be opened slowly. ● Always use protective gloves and protect your eyes when charging refrigerant. The outdoor unit is factory charged with refrigerant. Calculate the added refrigerant according to the diameter and the length of the liquid side pipe of the outdoor unit/indoor unit R(g)
D(mm)
L(m) Less than 5m (One-way) Added Refrigerant When Over 5m(One-way)
φ6.4
Φ9.5
Φ12.7
—
—
—
11g/m×(L-5)
30g/m×(L-5)
60g/m×(L-5)
Remark: R (g): Additional refrigerant to be charged L (m): The length of the refrigerant pipe (one-way) D (mm): Liquid side piping diameter
136
Installation
MLCAC-UTSM-2010-10
Water Drainage
4. Water Drainage 4.1 Gradient and Supporting 4.1.1 Keep the drainpipe sloping downwards at a gradient of at least 1/100. Keep the drainpipe as short as possible and eliminate the air bubble. 4.1.2 The horizontal drainpipe should be short. When the pipe is too long, a prop stand must be installed to keep the gradient of 1/100 and prevent bending. Refer to the following table for the specification of the prop stand. Hard PVC pipe
Diameter
Distance between the prop stands
25~40mm
1.5~2m
4.1.3. Precautions ① The diameter of drainpipe should meet the drainage requirement at least. ② The drainpipe should be heat-insulated to prevent atomization. ③ Drainpipe should be installed before installing indoor unit. After powering on, there is some water in water-receiver plate. Please check if the drain pump can operate correctly. ④ All connection should be firm. ⑤ Wipe color on PVC pipe to note connection. ⑥ Climbing, horizontal and bending conditions are prohibited. ⑦ The dimension of drainpipe can’t less than the connecting dimension of indoor drainpipe. ⑧ Heat-insulation should be done well to prevent condensation. ⑨ Indoor units with different drainage type can’t share one convergent drainpipe.
4.2 Drainpipe Trap 4.2.1. If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe trap. 4.2.2. Every indoor unit needs one drainpipe trap. 4.2.3. A plug should be designed to do cleaning.
50cm 50cm
Plug
4.3 Upwards drainage (drain pump) For Four-way cassette(compact)
Installation
137
Water Drainage
MLCAC-UTSM-2010-10
For Four-way cassette
4.4 Convergent drainage 4.4.1. The number of indoor units should be as small as possible to prevent the traverse main pipe overlong. 4.4.2. Indoor unit with drain pump and indoor unit without drain pump should be in different drainage system.
4.4.3. Selecting the diameter Number of connecting indoor units→Calculate drainage volume→Select the diameter Calculate allowed volume =Total cooling capacity of indoor units(HP)×2 (l/ hr) Allowed volume(lean 1/50) (l/ hr) I.D. (mm) 集中排水管 Hard PVC ∽≤14 ¢25 Hard PVC 14<∽≤88 ¢30 Hard PVC 88<∽≤334 ¢40 Hard PVC 175<∽≤334 ¢50 Hard PVC 334<∽ ¢80
Thick 3.0 3.5 4.0 4.5 6.0
4.5 Drainage test 4.5.1Drainage without drain pump After finishing drainpipe installation, pour some water into the water receiver plate to check if the water flows smoothly. 4.5.2 Drainage with drain pump ① Poke the Water Level Switch, remove the cover, use water pipe to pour 2000ml water into the water receipt plate through the water inlet.
② Turn on the power to Cooling operation. Check the pump’s operation and switch on the Water Level Switch. Check the pump’s sound and look into the transparent hard pipe in the outlet at the same time to check if the water can discharge normally.
138
Installation
MLCAC-UTSM-2010-10
Water Drainage
③ Stop the air conditioner running, turn off the power, and put back the cover. Stop the air conditioner. After 3 minutes, check if it has abnormity. If the collocation of drainpipes is illogical, the water will flow back overfull, which will cause the alarm lamp flashes, even overflow from the water receipt plate. z Keep on pouring water until it gives an alarm signal for high water level, check if the pump drains water at once. If the water level can’t fall below the alarmed water level after 3 minutes, the air conditioner will stop. Turn off the power and drain the remained water, and then turn on the air conditioner. Note: the drain stuff in the main water receipt plate is for maintenance. Stuff up the drain stuff to prevent water leakage. z
Installation
139
Insulation Work
MLCAC-UTSM-2010-10
5. Insulation Work 5.1 Insulation material and thickness 5.1.1. Insulation material Insulation material should adopt the material which is able to endure the pipe’s temperature: no less than 70℃ in the high-pressure side, no less than 120℃ in the low-pressure side(For the cooling type machine, no requirements at the low-pressure side.)
Example: Heat pump type----Heat-resistant Polyethylene foam (withstand above 120℃) Cooling only type----Polyethylene foam (withstand above 100℃)
5.1.2. Thickness choice for insulation material Insulation material thickness is as follows:
Refrigerant pipe Drainage pipe
Pipe diameter (mm) Φ6.4—Φ25.4 Φ28.6—Φ38.1 Inner diameterΦ20—Φ32
Adiabatic material thickness 10mm 15mm 6mm
5.2 Refrigerant pipe insulation 5.2.1. Work Procedure ① Before laying the pipes, the non-jointing parts and non-connection parts should be heat insulated. ② When the gas proof test is eligible, the jointing area, expanding area and the flange area should be heat insulated 5.2.2. Insulation for non-jointing parts and non-connection parts wrong Gas pipe and liquid pipe should not be put together to insulate
140
right Insulate the gas pipe (cooling only)
Insulate the gas pipe and liquid pipe
Installation
MLCAC-UTSM-2010-10
Insulation Work
For construction convenience, before laying pipes, use insulation material to insulate the pipes to be deal with, at the same time, at two ends of the pipe, remain some length not to be insulated, in order to be welded and check the leakage after laying the pipes. 5.2.3. Insulate for the jointing area, expanding area and the flange area ① Insulate for the jointing area, expanding area and the flange area should be done after checking leakage of the pipes ② Make sure there’s no clearance in the joining part of the accessorial insulation material and local preparative insulation material.
5.3 Drainage pipe insulation The connection part should be insulated, or else water will be condensing at the non-insulation part.
5.4 Note 5.4.1 The jointing area, expanding area and the flange area should be heat insulated after passing the pressure test 5.4.2 The gas and liquid pipe should be heat insulated individually, the connecting part should be heat insulated individually. 5.4.3 Use the attached heat-insulation material to insulate the pipe connections (pipes’ tie-in ,expand nut ) of the indoor unit
6. Wiring Please refer to the Wiring Diagram.
Installation
141
Test Operation
MLCAC-UTSM-2010-10
7. Test Operation (1) The test operation must be carried out after the entire installation has been completed. (2) Please confirm the following points before the test operation. z The indoor unit and outdoor unit are installed properly. z Tubing and wiring are correctly completed. z The refrigerant pipe system is leakage-checked. z The drainage is unimpeded. z The ground wiring is connected correctly. z The length of the tubing and the added stow capacity of the refrigerant have been recorded. z The power voltage fits the rated voltage of the air conditioner. z There is no obstacle at the outlet and inlet of the outdoor and indoor units. z The gas-side and liquid-side stop values are both opened. z The air conditioner is pre-heated by turning on the power. (3) According to the user's requirement, install the remote controller when the remote controller's signal can reach the indoor unit smoothly. (4) Test operation Set the air conditioner under the mode of "COOLING" with the remote controller, and check the following points. Indoor unit z Whether the switch on the remote controller works well. z Whether the buttons on the remote controller works well. z Whether the air flow louver moves normally. z Whether the room temperature is adjusted well. z Whether the indicator lights normally. z Whether the temporary buttons works well. z Whether the drainage is normal. z Whether there is vibration or abnormal noise during operation. Outdoor unit z Whether there is vibration or abnormal noise during operation. z Whether the generated wind, noise, or condensed of by the air conditioner have influenced your neighborhood. z Whether any of the refrigerant is leaked.
142
Installation
MLCAC-UTSM-2010-10
Control
Part 5 Control 1. Wireless Remote Controller .........................................144
Control
143
MLCAC-UTSM-2010-10
Wireless Remote Controller
1. Wireless Remote Controller 1.1 R05/BGE The R05/BGE wireless remote controller is for Four-way cassette type and the Ceiling& floor type.
AUTO TE MP
C O OL
Mo de s etting
1
SET
DRY
2 Fan s peed se ttin g
SET
H E AT F AN
Ad jus t
4
3
Adj us t
FAN S P EED
MOD E
M
ON/OFF
5
Horiz swin g
7
Vert. swing
8
Reset
12
Loc k
13
Co ol/heat
15
SWIN G
AIR DIRE CTI ON
C LOC K
SW IN G
OK
TIME ON
EC O
TI ME OF F
6
Ai r dire cti on setting
9
Tim e settin g
10
Time ON
11
Ti me OFF
14
Confirm b utton
16
Economic operation
1.2 General Function for wireless remote controller: Model and Specification
144
Model
R05/BGE
Rated voltage
3.0V(2pieces of LR03 7# batteries)
Min voltage for sending signal of CPU
2.4V
Effective receiving distance
8m~11m
Operation condition
-5~60℃
Control
MLCAC-UTSM-2010-10
Wireless Remote Controller
Buttons and functions 1. MODE: Once pressing, running mode will be selected in the following sequence: AUTO COOL
DRY
HEAT FAN
NOTE: No heating mode for cool only type unit. 2. FAN SPEED: Fan speed will be selected in following sequence once pressing this button: AUTO LOW
MED
HIGH
3. Adjust
: Decrease the set temp. Keeping pressing will decrease the temp with 1℃ per 0.5s.
4. Adjust
: Increase the set temp. Keeping pressing will increase the temp with 1℃ per 0.5s.
5. ON/OFF: For turning on or turning off the air conditioner. 6. AIR DIRECTION: Activate swing function of air deflector. Once pressing, air deflector will turn 6°. For normal operation and better cooling and heating effect, deflector will not turn to the degree which is the state of deflector when the unit is turned off.( Only available when remote controller is used with corresponding unit.) 7. HORIZ SWING: Activate or turn off horizontal swing function. (Only available when remote controller is used with corresponding unit, i.e. Ceiling & floor type) 8. VERT SWING: Activate or turn off vertical swing function. (Only available when remote controller is used with corresponding unit.) 9. CLOCK: Display the current time. (12:00 is displayed when resetting or electrifying for the first time.) Press CLOCK for 5s, icon indicating hour will flash with 0.5s. Press it again; icon indicating minute will flash with 0.5s. and are used to adjust the figure. Setting or modification is effective only by pressing OK button to make confirmation. 10. TIME ON: For time ON setting. Once pressing this button, the time will increase by 0.5 hour. When the set time exceeds 10 hours, pressing the button will increase the time by 1 hour. Adjusting the figure to 0.00 will cancel time ON setting. 11. TIME OFF: For time OFF setting. Once pressing this button, the time will increase by 0.5 hour. When the set time exceeds 10 hours, pressing the button will increase the time by 1 hour. Adjust the figure to 0.00 will cancel time ON setting. 12. RESET (inner located): Press this button with a needle of 1mm to cancel the current setting and reset remote controller. 13. LOCK (inner located): Press this button with a needle of 1mm to lock or unlock the current setting. 14. OK: Used to confirm the time setting and modification. 15. COOL/HEAT (inner located): Press this button with a needle of 1mm to shift mode between COOL only and COOL&HEAT. During setting, background light will be lightened. Factory default mode is COOL &HEAT. 16. ECO: Activate or turn off economic operation mode. It is suggested to turn on this function when sleeping. (Only available when remote controller is used with corresponding unit.)
Control
145