SW ITCHG EAR
ENERGY SAFELY SWITCHED
SWITCHGEAR PR OD U CT C ATA LOGU E 2013
Distributed By:
20 Neilpark Drive East Tamaki Auckland P: + 64 9 274 3340 E: sales@transnet.co.nz W: www.transnet.co.nz
SWITCHGEAR
ENERGY
safely switched
About Grupa Apator Who we are? Grupa Apator is a dynamic Polish capital group, it currently includes 14 companies – 8 Polish and 6 foreign. Grupa Apator is a pioneer in the implementation of innovative technical solutions and its sales income grows every year. Thanks to the application of modern technologies our products have the highest quality and win the recognition of our Clients.
Offer Grupa Apator focuses its activity in two segments of the electromechanical industry: metering and switchgear. Offer of the companies of Grupa includes metering equipment for all utilities (prepayment and post-payment electrical energy meters, heat meters, gas meters, water meters, temperature sensors). The above offer is a base for the development of systems enabling energy usage metering, remote reading, teletransmission and visualisation of data. Grupa Apator has a strong position and years of experience concerning safe making and breaking of electrical circuits.
ENERGY SAFELY SWITCHED
3
Apator ESTABLISHED SINCE: 1949.
04
Vertical fuse switch disconnectors ARS
The business activity covers: design,
RWS 1250 pro
production, sales of metering
Vertical switch disconnectors
16
equipment and systems and switchgear equipment. Standard product of company are as follows: LEWsystem APATOR, AMRsystem APATOR, prepaymet electricity meters, surge arresters, ARS, PBS, RBK type apparatuses and 4G series rotary cam switchers. CERTIFICATES: The Integrated Management System including the Quality Management System, Environmental Management System and Occupational Health and Safety Management System has been assessed and found to be in accordance with the requirements of: ISO 9001: 2008,
ARS Vertical fuse switch disconnectors ARS PBS
RBK pro
RBK 00 pro-S
RBK
lightning bolt is 1 km long, but some can reach more than 10 km.
84
Fuse switch disconnectors
Fuse bases
mostly in tropical areas. The average
68
Fuse switch disconnectors
PN-N-18001: 2004.
Earth six thousand times per minute,
62
Fuse switch disconnectors
PBD
Lightning strikes somewhere on the
44
Vertical fuse rails
ISO 14001:2004,
DID YOU KNOW THAT:
24
WTNH
112
122
Fuse links ZK
136
Cable service box
The longest recorded lightning bolt was 150 km!
RA/RAB
144
Switch disconnectors series R 4G Rotary cam switches
164
CONTENTS
BUSINESS ACTIVITY:
ARS pro
SWITCHGEAR
ARS pro
vertical fuse switch disconnectors - fibre glass extra strenghtened, self extinguishing thermoplastics of V0 flammability class - double clearance between open contacts - arc chutes with deionization plates over every contact - reversibility - top/bottom cable terminal connection - wide range of accesories
ENERGY SAFELY SWITCHED
SWITCHGEAR
GENERAL NFORMATION
GENERAL NFORMATION
6
ARS vertical fuse switch disconnectors are designed for distribution of electricity and protection against short circuits and overloads in three phase alternative current circuits. They are intended for direct installation on horizontal or vertical busbar systems. ARS pro fuse switch disconnectors meet technical requirements of polish and other european electricity boards and are conforming to EN 60947-1, EN 60947-3, IEC 60947-1, IEC 60947-3 standards. ARS pro fuse switch disconnectors are dedicated for applications which require reliability and safety like low voltage distribution boards installed in transformer substations, industrial low voltage distribution boards and cable cabinets. Removal of the fuse links provides clearly noticeable, large isolating distances in the circuit. ARS fuse switch disconnectors are designed to perform the following functions:
protection, energy distribution, earthing, switching, touch protection.
CONSTRUCTION ARS pro fuse switch disconnectors are manufactured in two versions: one pole switching (separately each pole) three pole switching (three poles at the same time)
They have manually operated handle therefore making and breaking operations should be done with determined movement. ARS pro fuse switch disconnectors are available in following sizes (according to rated current): 00 (160 A); 2 (400 A); 3 (630 A), also 910 A and 1250 A. ARS pro fuse switch disconnectors are designed for installation on to 185 mm busbar system. ARS pro of size 00 are manufactured in two versions depending on busbar system: ARS 00 pro fuse switch disconnector (160 A) for installation on to 185 mm busbar system ARS 00/100mm pro fuse switch disconnector (160 A) for installation on to 100 mm busbar system Installation on to 185 mm busbar system is possible by using adapter.
Main base of fuse switch disconnector ARS pro is made of halogen free, fibre glass strengthened, self extinguishing, thermoset polyester of V0 flammability class. Other plastic parts of fuse switch disconnectors ARS pro are made of fibre glass strengthened, thermoplastic polyamides with halogen free flame retardant added. Thanks to such addition the highest flammability class – V0 was achieved. Fuse switch disconnectors made from such termoplastics self-extinguish in specified time after ignition source is removed. Also dripping of flaming parts of plastic does not occur. Silver plated contacts provide low power loss. Depending on clamp type, ARS pro fuse switch disconnectors enable user to connect circular or sector-shaped conductors with bare ends or conductors with lug terminals. Arc chute with deionization plates is installed over each contact. Such design provides efficiency of arc extinction and controlled exhaust of arc plasma. ARS pro fuse switch disconnectors are adapted for using current transformers and ammeters. Protection degree of IP30 from the front is provided. Additionally offered accesories enable to install ARS fuse switch disconnectors of different sizes on common busbar systems. All sizes of ARS pro fuse switch disconnectors are provided complete with clamps (i. e. screws, V-terminals, 2V-terminals) and shrouds for cable terminals.
ENERGY SAFELY SWITCHED
Table 1. TECHNICAL DATA ARS pro
7
Parameters
ARS 630 kVA pro
RWS 1250 pro
ARS 1250 pro
400
630
910
-
1250
Rated thermal current Ith with solid links
A
-
-
600
750
-
1250
400
Rated short-circuit withstand current
V
690
690
690
690
400
400
690 V
AC-22B
AC-22B
AC-22B
AC-21B
-
-
500 V
-
-
-
AC-22B
-
-
-
400 V
AC-23B
AC-23B
AC-23B
AC-23B
AC-22B
AC-22B
AC-21B
A
160
160
400
630
910
1250
1250
80
-
kA
25
690 V 500 V
80 -
400 V
100
690 V
80
500 V
kA
100
400 V
-
100
100 80
100
100
100
-
-
-
50
100
-
-
-
-
50
100
Rated insulation voltage Ui
V
1000
1000
1000
1000
1000
1000
1000
Rated impulse withstand voltage Uimp.
kV
8
12
12
12
12
12
12
Rated short time withstand current Icw
kA
-
-
122)/153)
142)/163)
-
15/204)
-
Hz
50-60
50-60
50-60
50-60
50-60
50-60
50-60
1600
1600
1000
1000
600
600
600
200
200
200
200
100
100
100
IP
30
20
30
30
30
30
30
-
00
00
1, 2
3
gTr 630 kVA1)
solid-links TM 3 -1250 A
3
Rated frequency Mechanical durability Electrical durability
Number of cycles
IP degree of protection Fuse links size
fuse link gTr 630 kVA, DIN 43620, VDE 0636/2011 voltage for disconnectors 1-phase disconnected for disconnectors 3-phase disconnected with mechanical lock
OPERATING CONDITIONS
to be installed in the room free of any dust, aggressive or explosive gases, altitude up to 2000 meters above sea level, outdoor – in cabinets with protection degree > IP 34, ambient temperature from -25 °C to +55 °C, relative humidity of the air should not be higher than 50% at temperature of +40°.
FUNCTIONALITY making and breaking operations should be done with determined movement, parallelly moving, double contact system, designed for installation on to 100 mm or 185 mm busbar system, two versions: single pole switching (separately each pole) or triple pole switching (three poles at the same time), fuse switch disconnectors width: 50 mm, 100 mm, 200 mm, suitable for top cable terminal connection, possible connection of circular or sector-shaped conductors with bare ends (V-terminals, 2V-terminals or conductors with lug terminals (screw terminals), Voltage test is performed through test holes leading to blade contacts, possible installation of various types of earthing devices.
TECHNICAL DATA
160
Rated short-circuit making current
4)
ARS 3 pro
160
Rated switching current Ie
3)
ARS 2 pro
A
Utilization category
2)
ARS 00 pro
Rated thermal current Ith=In with fuse links
Rated voltage Un
1)
ARS 00/100 mm pro
SWITCHGEAR
FUSE SWITCH DISCONNECTOR ARS 00/100mm pro (160 A, 690 V)
8
ARS 00/100 mm pro
For installation on to 100 mm busbar system Fuse switch disconnector’s width 50 mm Three pole switching - all phases simultaneously
Padlocking in parked and closed position
Test holes
Fuse link cover label (one label for each phase) Hole for sealing of terminal shroud Terminal shroud label
ARS 00/100 mm pro
ENERGY SAFELY SWITCHED
ARS 00/100 mm pro (160 A, 690 V)
9
Table 2. TECHNICAL DATA ARS 00/100 mm pro
Parameters Rated thermal current Ith=In
A
Rated voltage Un
V
Utilization category
-
AC-22B
Rated switching voltage Ue
V
690
Rated switching current Ie
A
160
Rated short circuit making current
kA
25
Rated short circuit withstand current
kA
100
Rated insulation voltage Ui
V
1000
Rated impulse withstand voltage Uimp.
kV
8
Rated frequency
Hz
50-60
Number of cycles
1600
IP
30
-
00
Electrical durability IP degree of protection Fuse links size
690
ARS 00/100 mm pro
Mechanical durability
160 AC-23B 400
200
Accesories on page 42
Table 3. VERSIONS Version of ARS 00/100 mm pro
Weight
Article No.
three pole switching - all phases simultaneously (for installation on to 100 mm busbar system) ARS 00/100 mm pro
cable terminals: bridge terminals with bridge clamps (S) 4-70 mm2, screw terminals with M8 screws
1,3 kg
63-811628-041
ARS 00/100 mm-V pro
cable terminals: V-terminals with V-clamps 25-120SW
1,5 kg
63-811628-061
ARS 00/100 mm-V pro
cable terminals: V-terminals, without V-clamps
1,3 kg
63-811628-071
Table 4. ARS 00/100 mm pro TERMINAL CLAMPS Description Clamp
ARS 00/100 mm pro S-bridge clamp 2 x M5 x 25
M8 screw*
V-clamp 25-120 SW
HM 10-120 ***
Picture of clamp
Drawing of clamp
Cross –section of conductors Tightening torque
4 - 70 mm2
Conductor with lug terminal max 185 mm2
re 16 mm2 - 95 mm2 se 25 mm2 - 120 mm2 rm 16 mm2 - 95 mm2 sm 25 mm2 - 120 mm2
re 10 mm2 - 70 mm2 se 20 mm2 - 120 mm2 rm 10 mm2 - 70 mm2 sm 25 mm2 - 95 mm2
3 Nm**
12 Nm**
20 Nm**
15 Nm**
For stranded conductors using cable ferrules is recommended *) Bars of maximum width of 20 mm and maximum thickness of 5 mm can be fixed to M type screw terminals. **) using tension wrench is recommended ***) fuse switch disconnectors with V-terminals are equipped with steel V-clamp HM 10-120 on request Apator takes responsibility for technical quality of V-terminals manufactured only by the company. Minimum tightening torque (M8 screw) for screws fixing fuse switch disconnector to busbar system –12 Nm, recommended tightening torque for screws and nuts with property class 8.8 – 21 Nm
SWITCHGEAR
10
FUSE SWITCH DISCONNECTOR ARS 00 pro (160 A, 690 V) For installation on to 185 mm busbar system Fuse switch disconnector’s width 50 mm Three pole switching - all phases simultaneously - two-hand operation or one pole switching - each phase independently
ARS 00 pro
Table 5. DANE TECHNICZNE ARS 00 pro
Parameters Rated thermal current Ith=In
A
Rated voltage Un
V
Utilization category
-
AC-22B
Rated switching voltage Ue
V
690
Rated switching current Ie
A
Rated short circuit making current
690 V
Rated short circuit withstand current
690 V
400 V 400 V
kA kA
160 690 AC-23B 400 160 80 100 80 100
Rated insulation voltage Ui
V
1000
Rated impulse withstand voltage Uimp.
kV
12
Rated frequency
Hz
50-60
Number of cycles
1600
IP
20
-
00
Mechanical durability Electrical durability IP degree of protection Fuse links size
200
Accesories on page 42
ARS 00-1 pro
ARS 00-3 pro
Table 6. VERSIONS Version
Weight
Article No.
for installation on to 185 mm busbar system, one pole switching - each phase independently ARS 00-1 pro
cable terminals: bridge terminals with bridge clamps (S) 4-70 mm2, screw terminals with M8 screws
2,6 kg
63-811410-061
ARS 00-1-V pro
cable terminals: V-terminals with V-clamps 25-120SW
2,7 kg
63-811410-071
ARS 00-1-V pro
cable terminals: V-terminals, without V-clamps
2,6 kg
63-811410-101
for installation on to 185 mm busbar system, three pole switching - all phases simultaneously ARS 00-3 pro
cable terminals: bridge terminals with bridge clamps (S) 4-70 mm2, screw terminals with M8 screws
2,7 kg
63-811806-061
ARS 00-3-V pro
cable terminals: V-terminals with V-clamps 25-120SW
2,8 kg
63-811806-071
ARS 00-3-V pro
cable terminals: V-terminals, without V-clamps
2,7 kg
63-811806-101
2,7 kg
63-811839-061
ARS 00 pro with heightened rails adjusted to front line and terminal cover of ARS pro 2, 3 for installation on to 185 mm busbar system, one pole switching - each phase independently ARS 00-1 pro
cable terminals: bridge terminals with bridge clamps (S) 4-70 mm2, screw terminals with M8 screws
ARS 00-1-V pro
cable terminals: V-terminals with V-clamps 25-120SW
2,8 kg
63-811839-071
ARS 00-1-V pro
cable terminals: V-terminals, without V-clamps
2,7 kg
63-811839-101
2,8 kg
63-811840-061
for installation on to 185 mm busbar system, three pole switching - all phases simultaneously ARS 00-3 pro
cable terminals: bridge terminals with bridge clamps (S) 4-70 mm2, screw terminals with M8 screws
ARS 00-3-V pro
cable terminals: V-terminals with V-clamps 25-120SW
2,9 kg
63-811840-071
ARS 00-3-V pro
cable terminals: V-terminals, without V-clamps
2,8 kg
63-811840-101
ENERGY SAFELY SWITCHED
Table 7. ARS 00 pro TERMINAL CLAMPS
11
Description Clamp
ARS 00 pro (160A) S-bridge clamp 2 x M5 x 25
M8 screw*
V-clamp 25-120 SW
HM 10-120 ***
Picture of clamp
Cross–section of conductors
4 - 70 mm2
Conductor with lug terminal max 185 mm2
Tightening torque
3 Nm**
12 Nm**
re 16 mm2 - 95 mm2 se 25 mm2 - 120 mm2 rm 16 mm2 - 95 mm2 sm 25 mm2 - 120 mm2
re 10 mm2 - 70 mm2 se 25 mm2 - 120 mm2 rm 10 mm2 - 70 mm2 sm 25 mm2 - 95 mm2
20 Nm**
15 Nm**
For stranded conductors using cable ferrules is recommended *) bars of maximum width of 20 mm and maximum thickness of 5 mm can be fixed to M type screw terminals **) using tension wrench is recommended ***) fuse switch disconnectors with V-terminals are equipped with steel V-clamp HM 10-120 on request Apator takes responsibility for technical quality of V-terminals manufactured only by the company. Minimum tightening torque (M8 screw) for screws fixing fuse switch disconnector to busbar system – 12 Nm, recommended tightening torque for screws and nuts with property class 8.8 – 21 Nm
Fuse switch disconnector with cable terminals at the top
Parking position
ARS 00 pro version with heightened rails, adjusted to front line and terminal cover of ARS 1, 2, 3 without using adapter
Installation on to busbar system with use of hooked clamps
Or screws
ARS 00-1 pro
ARS 00-3 pro
ARS 00-3 pro
ARS 00-1 pro
ARS 00 pro
Drawing of clamp
SWITCHGEAR
12
FUSE SWITCH DISCONNECTOR ARS 2 pro (400 A, 690 V) ARS 3 pro (630 A, 690 V)
ARS 2 | ARS 3 pro
For installation on to 185 mm busbar system Fuse switch disconnector’s width 100 mm Three pole switching - all phases simultaneously or one pole switching - each phase independently 1
15
Sealing of each phase separately
Padlocking and sealing in closed and parked position
2
3
Possible connection of fused tee off adapter for temporary power supply
Possibility to use ammeter
8
5
Test holes
4
Fuse link cover labelling area
7 6
DESCRIPTON 1. Main base 2. Hooked clamp – for installation on to busbar system 1115281037T 3. Terminal shroud for fuse switch disconnector with double V-clamps (2 x 240 mm2) 4. Terminal shroud (long) 51-930271-021 5. Terminal shroud (short) 6. Bottom adjusting shroud 51-930313-011 7. Cable terminal protective cover 51-930272-011 8. Protective barrier
Hole for sealing of terminal shroud
Terminal shroud label
ARS 3-6-V pro
ENERGY SAFELY SWITCHED
ARS 2 pro (400 A, 690 V)
13
Designed for operation with NH1 and NH2 fuse links Table 8. TECHNICAL DATA ARS 2 pro
Parameters
IP degree of protection Fuse links size Accesories on page 43 2) 3)
IP -
400 600 690 AC-22B AC-23B 690 400 400 100 100 1000 12 122)/153) 50-60 1000 200 30 1, 2
ARS 2 pro
Rated thermal current Ith=In with fuse links A Rated thermal current Ithwith solid links A Rated voltage Un V Utilization category Rated switching voltage Ue V Rated switching current Ie A Rated short circuit making current kA Rated short circuit withstand current kA Rated insulation voltage Ui V Rated impulse withstand voltage Uimp. kV Rated short time withstand current Icw kA Rated frequency Hz Mechanical durability Number of cycles Electrical durability
for disconnectors 1-phase disconnected for disconnectors 3-phase disconnected
ARS 2-1-2V pro
Table 9. VERSIONS Version
ARS 2-6-V pro Weight
Article No.
5,8 kg 5,7 kg 6,4 kg 5,5 kg 6,9 kg
63-811801-011 63-811801-031 63-811801-051 63-811801-071 63-811801-091
5,8 kg 5,7 kg 6,4 kg 5,5 kg 5,9 kg
63-811802-011 63-811802-031 63-811802-051 63-811802-071 63-811802-091
for installation on to 185 mm busbar system, one pole switching - each phase independently ARS 2-1-V pro ARS 2-1-M pro ARS 2-1-2V pro ARS 2-1-V pro ARS 2-1-2V pro
cable terminals: V-terminals with V-clamps 240 mm2 cable terminals: screw terminals with pressed nuts M10 cable terminals: 2V-terminals with double V-clamps 240 mm2 cable terminals: V-terminals without V-clamps cable terminals: 2V-terminals without double V-clamps
for installation on to 185 mm busbar system, three pole switching - all phases simultaneously ARS 2-6-V pro ARS 2-6-M pro ARS 2-6-2V pro ARS 2-6-V pro ARS 2-6-2V pro
cable terminals: V-terminals with V-clamps 240 mm2 cable terminals: screw terminals with pressed nuts M10 cable terminals: 2V-terminals with double V-clamps 240 mm2 cable terminals: V-terminals without V-clamps cable terminals: 2V-terminals without double V-clamps
Tabela 10. ARS 2 pro TERMINAL CLAMPS ARS 2-x-M pro (400 A)
Clamp
V-clamp 35-300SW-B
V-clamp HS 2/35-240-C
M10 screw (pressed nut)
Cross-section of conductors
Drawing of clamp
V-clamp for direct fixing of conductor with bare end with crosssection of:
Tightening torque
35 - 185 mm2
35 - 240 mm2
35 - 185 mm2
35 - 240 mm2
35 - 240 mm2
35 - 300 mm2
35 - 240 mm2
35 - 300 mm2
30 Nm
40 Nm
Lug terminal
ARS 2-x-2V pro (400 A)
Crosssection of conductors
ARS 2-x-V pro (400 A)
Cross-section of conductors
Description
32 Nm
For stranded conductors using cable ferrules is recommended *) Bars of maximum width of 40 mm and maximum thickness of 8 mm can be fixed to M type screw terminals when protective barrier between phases is installed. Apator takes responsibility for technical quality of V-terminals manufactured only by the company. Minimum tightening torque (M12 screw) for screws fixing fuse switch disconnector to busbar system – 32 Nm, recommended tightening torque for screws and nuts with property class 8.8 – 56 Nm
SWITCHGEAR
14
ARS 3 pro (630 A, 690 V)
ARS 3 pro
Table 11. TECHNICAL DATA Parameters
ARS 3
Rated thermal current Ith=In with fuse links A Rated thermal current Ithwith solid links A Rated voltage Un V Utilization category Rated switching voltage Ue V Rated switching current Ie A 690 V Rated short circuit making current kA 500 V Rated short circuit withstand current kA Rated insulation voltage Ui V Rated impulse withstand voltage Uimp. kV Rated short time withstand current Icw kA Rated frequency Hz Mechanical durability Number of cycles Electrical durability
630 750 690 AC-23B 400 630 80 100 100 1000 12 122)/153) 50-60 1000 200 30 3
IP degree of protection Fuse links size Accesories on page 43 2) 3)
AC-22B 500
IP -
AC-21B 690
for disconnectors 1-phase disconnected for disconnectors 3-phase disconnected
ARS 3-1-2V pro
ARS 3-6-V pro
Table 12. VERSIONS Version
Weight
Article No.
6,6 kg 6,5 kg 7,2 kg 6,3 kg 6,7 kg
63-811801-021 63-811801-041 63-811801-061 63-811801-081 63-811801-101
6,6 kg 6,5 kg 7,2 kg 6,3 kg 6,7 kg
63-811802-021 63-811802-041 63-811802-061 63-811802-081 63-811802-101
for installation on to 185 mm busbar system, one pole switching - each phase independently ARS 3-1-V pro ARS 3-1-M pro ARS 3-1-2V pro ARS 3-1-V pro ARS 3-1-2V pro
cable terminals: V-terminals with V-clamps 240 mm2 cable terminals: screw terminals with pressed nuts M12 cable terminals: 2V-terminals with double V-clamps 240 mm2 cable terminals: V-terminals without V-clamps cable terminals: 2V-terminals without double V-clamps
for installation on to 185 mm busbar system, three pole switching - all phases simultaneously ARS 3-6-V pro ARS 3-6-M pro ARS 3-6-2V pro ARS 3-6-V pro ARS 3-6-2V pro
cable terminals: V-terminals with V-clamps 240 mm2 cable terminals: screw terminals with pressed nuts M12 cable terminals: 2V-terminals with double V-clamps 240 mm2 cable terminals: V-terminals without V-clamps cable terminals: 2V-terminals without double V-clamps
Table 13. ARS 3 pro TERMINAL CLAMPS ARS 3-x-M pro (630 A)
Clamp
V-clamp 35-300SW-B
V-clamp HS 2/35-240-C
M12 screw (pressed nut)
Cross-section of conductors
Drawing of clamp
V-clamp for direct fixing of conductor with bare end with crosssection of: 35 - 185 mm2
35 - 240 mm2
35 - 185 mm2
35 - 240 mm2
35 - 240 mm
35 - 300 mm
35 - 240 mm
35 - 300 mm2
2
Tightening torque
2
30 Nm
2
40 Nm
Lug terminal
ARS 3-x-2V pro (630 A)
Crosssection of conductors
ARS 3-x-V pro (630 A)
Cross-section of conductors
Description
56 Nm
For stranded conductors using cable ferrules is recommended *)Bars of maximum width of 40 mm and maximum thickness of 8 mm can be fixed to M type screw terminals when protective barrier between phases is installed. Apator takes responsibility for technical quality of V-terminals manufactured only by the company Minimum tightening torque (M12 screw) for screws fixing fuse switch disconnector to busbar system – 32 Nm, recommended tightening torque for screws and nuts with property class 8.8 – 56 Nm
ENERGY SAFELY SWITCHED
FUSE SWITCH DISCONNECTOR ARS 630 kVA pro
15
Fuse switch disconnector ARS 630 kVA pro is dedicated for protection of transformers up to 630 kVA. Fuse switch disconnector is designed for operation with NH fuse links of size 3, with gTr characteristic. For installation onto 185 mm busbar system. ARS 630 kVA pro
Table 14. TECHNICAL DATA Parameters
ARS 630 kVA pro
Rated thermal current Ith=In
A
910
Rated voltage Un
V
400
Utilization category
-
AC-22B
Rated switching voltage Ue
V
400
Rated switching current Ie
A
910
Rated short circuit making current
kA
50
Rated short circuit withstand current
kA
50
Rated insulation voltage Ui
V
1000
Rated impulse withstand voltage Uimp.
kV
12
Rated frequency
Hz
50-60
Number of cycles
600
IP degree of protection
IP
30
Weight
kg
9,8
-
gTr 630 kVA1)
Mechanical durability Electrical durability
Fuse links size
100
Accesories on page 43 1)
Cable terminal: three pressed nuts M12
Fuse link gTr 630 kVA, DIN 43620, VDE 0636/2011, the volume of NH3
ARS 630 kVA pro
Cable terminal: two pressed nuts M12
Table 15. VERSIONS Versions of 630 kVA pro
Article No.
one pole switching - each phase independently ARS 630 kVA-1-2M pro
cable terminals: screw terminals with two pressed nuts M12/pole , width 100 mm
63-811860-001
ARS 630 kVA-1-3M pro
cable terminals: screw terminals with three pressed nuts M12/pole , width 200 mm
63-811860-002
three pole switching - all phases simultaneously ARS 630 kVA-6-2M pro
cable terminals: screw terminals with two pressed nuts M12/pole , width 100 mm
63-811722-011
ARS 630 kVA-6-3M pro
cable terminals: screw terminals with three pressed nuts M12/pole , width 200 mm
63-811722-021
Recommended tightening torque (M12 screw) for screws fixing fuse switch disconnector to busbar system – 56Nm, screws and nuts property class 8.8.
Table 16. ARS 630 kVA pro TERMINAL CLAMPS Description
ARS 630 kVA pro
Clamp
pressed nuts M12
Drawing of clamp
Cross-section of conductors Tightening torque
Cable lugs, max 300 mm2 56 Nm
SWITCHGEAR
16
SWITCH DISCONNECTOR RWS 1250 pro Main switch-disconnector 1250 A, equipped with NH3 solid-links 1250 A Switch-disconnector’s width 100 mm For installation onto 185 mm busbar system
RWS 1250 pro
Table 17. TECHNICAL DATA Parameters
RWS 1250 pro
Rated thermal current Ith=In
A
1250
Rated voltage Un
V
400
Utilization category
-
AC-22B
Rated switching voltage Ue
V
400
Rated switching current Ie
A
1000
Rated insulation voltage Ui
V
1000
Rated impulse withstand voltage Uimp.
kV
12
Rated short time withstand current Icw
kA
15
Rated frequency
Hz
50-60
Number of cycles
600
IP degree of protection
IP
30
Weight
kg
11
-
TM3-1250 A
Mechanical durability Electrical durability
Fuse links size
100
Accesories on page 43
RWS 1250 pro
Cable terminal: two pressed nuts M12
Table 18. VERSIONS Version RWS 1250 pro
Article No.
Switch-disconnector 1250 A, equipped with NH3 solid-links 1250 A. For installation onto 185 mm busbar system. Switch-disconnector’s width 100 mm three pole switching - all phases simultaneously RWS 1250-6-2M pro
cable terminals: screw terminals with two pressed nuts M12/pole , width 100 mm
63-811828-011
RWS 1250-6-3M pro
cable terminals: screw terminals with three pressed nuts M12/pole , width 200 mm
63-811828-021
RWS 1250-6-T pro
power supply connection at the back of the switch disconnector, feeding rail’s length = 120 mm, feeding rails designed for fixing with M12 screws
63-811861-001
RWS 1250-6-T pro
power supply connection at the back of the switch disconnector, feeding rail’s length = 170 mm, feeding rails designed for fixing with M12 screws
63-811861-002
Recommended tightening torque (M12 screw) for screws fixing fuse switch disconnector to busbar system – 56Nm, screws and nuts property class 8.8
Table 19. RWS 1250 pro TERMINAL CLAMPS Description Clamp
RWS 1250 pro pressed nuts M12
Drawing of clamp
Cross-section of conductors Tightening torque
Cable lugs, max 300 mm2 56 Nm
Cable terminal: three pressed nuts M12
RWS 1250-6-3M pro
Version of RWS 1250 A pro with cable terminals at the back of the switch
RWS 1250-6-T pro
ENERGY SAFELY SWITCHED
FUSE SWITCH DISCONNECTOR ARS 1250 pro
17
Fuse switch disconnector’s width 200 mm Table 20. TECHNICAL DATA ARS 1250 pro
Parameters Rated thermal current Ith=In
A
Rated voltage Un
V
400
Utilization category
-
AC-21B
1250
V
400
Rated switching current Ie
A
1250
Rated short circuit making current
kA
100
Rated short circuit withstand current
kA
100
Rated insulation voltage Ui
V
1000
Rated impulse withstand voltage Uimp.
kV
12
Rated frequency
Hz
50-60
Number of cycles
600
IP
30
-
3
Mechanical durability Electrical durability IP degree of protection Fuse links size
ARS 1250 pro
Rated switching voltage Ue
100
Accesories on page 43
ARS 1250-1-M pro
ARS 1250-6-M pro
Table 21. VERSIONS Version ARS 1250 pro
Weight
Article No.
for installation on to 185 mm busbar system, fuse disconnector’s width – 200 mm one pole switching - each phase independently ARS 1250-1-3M pro
mechanically and electrically coupled two ARS 3 pro fuse switch disconnectors, cable terminals: screw terminals with three pressed screw M12/pole
16,3 kg
63-811757-011
ARS 1250-1-4M pro
mechanically and electrically coupled two ARS 3 pro fuse switch disconnectors, cable terminals: screw terminals with four pressed screw M12/pole
17 kg
63-811757-021
three pole switching - all phases simultaneously ARS 1250-6-3M pro
mechanically and electrically coupled two ARS 3 pro fuse switch disconnectors, cable terminals: screw terminals with three pressed screw M12/pole
16,3 kg
63-811756-011
ARS 1250-6-4M pro
mechanically and electrically coupled two ARS 3 pro fuse switch disconnectors, cable terminals: screw terminals with four pressed screw M12/pole
17 kg
63-811756-021
Recommended tightening torque (M12 screw) for screws fixing fuse switch disconnector to busbar system – 56Nm, screws and nuts property class 8.8
Table 22. ARS 1250-x-M pro TERMINAL CLAMPS Description Clamp
ARS 1250-x-M pro three pressed nuts M12
Drawing of clamp
Cross-section of conductors Tightening torque
Cable lugs, max 300 mm2 56 Nm
M3 type cable terminals: screw terminals with three pressed screw M12/pole
M3 type cable terminals: screw terminals with four pressed screw M12/pole
SWITCHGEAR
electronic fuse monitoring module
18
ELECTRONIC FUSE MONITORING MODULE Fuse switch disconnector can be equipped with electronic fuse monitoring module. Fuse link status (operational, operated, loss of voltage) is indicated by light-emittng diodes and status of relay contacts.
PRINCIPLE OF OPERATION
RBK 00-X
L1, L2, L3 diodes are flashing - all three phases are supplied, all fuse links are operational. Relay contacts: [21..22] - closed; [13..14] - opened L1, L2, L3 diodes are blinking - all three phases are supplied, fuse links operated Relay contacts: [21..22] opened; [13..14] - closed L1, L2, L3 diodes are off - two or more phases are not supplied or fuse links are removed. Relay contacts: [21..22] - opened; [13..14] – closed
NOMINAL PARAMETERS operating voltage AC - 400÷690 V, 40÷60 Hz; relay parameters 5A , 250 V~
Diody 5 A 250 V AC
ENERGY SAFELY SWITCHED
Table 23. VERSIONS WITH ELECTRONIC FUSE MONITORING MODULE
19
Version
Weight
Article No.
cable terminals: V-terminals with V-clamps 240 mm2
5,9 kg
63-811830-001
Fuse switch disconnectors ARS 2 pro - 400 A
ARS 2-1-M-X pro
cable terminals: screw terminals with pressed nuts M10
5,8 kg
63-811830-003
ARS 2-1-2V-X pro
cable terminals: 2V-terminals with double V-clamps 240 mm2
6,5 kg
63-811830-005
ARS 2-1-V-X pro
cable terminals: V-terminals without V-clamps
5,6 kg
63-811830-007
ARS 2-1-2V-X pro
cable terminals: 2V-terminals without double V-clamps
6,0 kg
63-811830-009
for installation on to 185 mm busbar system, three pole switching - all phases simultaneously
RBK 00-X
ARS 2-6-V-X pro
cable terminals: V-terminals with V-clamps 240 mm2
5,9 kg
63-811829-001
ARS 2-6-M-X pro
cable terminals: screw terminals with pressed nuts M10
5,8 kg
63-811829-003
ARS 2-6-2V-X pro
cable terminals: 2V-terminals with double V-clamps 240 mm2
6,5 kg
63-811829-005
ARS 2-6-V-X pro
cable terminals: V-terminals without V-clamps
5,6 kg
63-811829-007
ARS 2-6-2V-X pro
cable terminals: 2V-terminals without double V-clamps
6,0 kg
63-811829-009
6,7 kg
63-811830-002
6,6 kg
63-811830-004
Fuse switch disconnectors ARS 3 pro – 630 A for installation on to 185 mm busbar system, one pole switching - each phase independently ARS 3-1-V-X pro
cable terminals: V-terminals with V-clamps 240 mm2
ARS 3-1-M-X pro
cable terminals: screw terminals with pressed nuts M12
ARS 3-1-2V-X pro
cable terminals: 2V-terminals with double V-clamps 240 mm
7,3 kg
63-811830-006
ARS 3-1-V-X pro
cable terminals: V-terminals without V-clamps
6,4 kg
63-811830-008
ARS 3-1-2V-X pro
cable terminals: 2V-terminals without double V-clamps
6,8 kg
63-811830-010
2
for installation on to 185 mm busbar system, three pole switching - all phases simultaneously ARS 3-6-V-X pro
cable terminals: V-terminals with V-clamps 240 mm2
6,7 kg
63-811829-002
ARS 3-6-M-X pro
cable terminals: screw terminals with pressed nuts M12
6,6 kg
63-811829-004
ARS 3-6-2V-X pro
cable terminals: 2V-terminals with double V-clamps 240 mm2
7,3 kg
63-811829-006
ARS 3-6-V-X pro
cable terminals: V-terminals without V-clamps
6,4 kg
63-811829-008
ARS 3-6-2V-X pro
cable terminals: 2V-terminals without double V-clamps
6,8 kg
63-811829-010
electronic fuse monitoring module
for installation on to 185 mm busbar system, one pole switching - each phase independently ARS 2-1-V-X pro
SWITCHGEAR
20
FUSE SWITCH DISCONNECTOR WITH LATERAL BUSBAR TERMINAL
ARS pro with lateral busbar terminals
(separation, coupling of busbar systems) Table 24. TECHNICAL DATA Parameters
ARS 2 pro ARS 3 pro
Rated thermal current Ith=In
A
400
630
Rated voltage Un
V
690
690
Utilization category
-
AC-22B
AC-22B
Rated switching voltage Ue
V
690
500
Rated switching current Ie
A
400
630
Rated short circuit making current
kA
100
100
Rated short circuit withstand current
kA
100
100
Rated insulation voltage Ui
V
1000
1000
Rated impulse withstand voltage Uimp.
kV
12
12
Rated frequency
Hz
50-60
50-60
Number of cycles
1000
1000
200
200
IP
30
30
-
2
3
Mechanical durability Electrical durability IP degree of protection Fuse links size Accesories on page 43
Lateral busbar terminals
Table 25. VERSIONS WITH LATERAL BUSBAR TERMINAL Version
Weight
Article No.
Fuse switch disconnectors ARS 2 pro - 400A for installation on to 185 mm busbar system, one pole switching - each phase independently ARS 2-1 NL pro
cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - left side
5,1 kg
63-811837-011
ARS 2-1 NR pro
cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - right side
5,1 kg
63-811837-031
for installation on to 185 mm busbar system, three pole switching - all phases simultaneously ARS 2-6 NL pro
cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - left side
5,1 kg
63-811838-011
ARS 2-6 NR pro
cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - right side
5,1 kg
63-811838-031
Fuse switch disconnectors ARS 3 pro – 630 A for installation on to 185 mm busbar system, one pole switching - each phase independently ARS 3-1 NL pro
cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - left side
5,9 kg
63-811837-021
ARS 3-1 NR pro
cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - right side
5,9 kg
63-811837-041
for installation on to 185 mm busbar system, three pole switching - all phases simultaneously ARS 3-6 NL pro
cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - left side
5,9 kg
63-811838-021
ARS 3-6 NR pro
cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - right side
5,9 kg
63-811838-041
three pole switching - all phases simultaneously RWS 1250 NL pro
Switch-disconnector 1250 A pro, equipped with solid-links 1250 A cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - left side
7 kg
63-811862-005
RWS 1250 NR pro
Switch-disconnector 1250 A pro, equipped with solid-links 1250 A cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - right side
7 kg
63-811862-001
Table 26. ARS 2, 3 pro WITH LATERAL BUSBAR TERMINALS TERMINAL CLAMPS Description Clamp
ARS 2-x-NL (400 A)
ARS 2-x-NR (400 A)
ARS 3-x-NL (630 A)
ARS 3-x-NR (630 A)
M12 screw
M12 screw
M12 screw
M12 screw
Left side
Right side
Left side
Right side
56 Nm
56 Nm
56 Nm
56 Nm
Drawing of clamp Lateral busbar terminal Tightening torque
ENERGY SAFELY SWITCHED
21
Unscrewing the enclosure
Fuse link replacement
Installation in reversed position
Ammeter
Fused tee off adapter/ piggy back adapter
a
Earthing of fuse switch disconnector
a
Voltage test
SWITCHGEAR
THREE PHASE CURRENT MEASUREMENT WITH FUSE SWITCH DISCONNECTOR ARS
THREE PHASE CURRENT MEASUREMENT
22
ONE PHASE CURRENT MEASUREMENT WITH FUSE SWITCH DISCONNECTOR ARS
Fuse switch disconnectors ARS 400 A, ARS 2 pro, ARS 3 pro
Fuse switch disconnectors ARS 00/160 mm, ARS 00/160 mm pro, ARS 00, ARS 00 pro
CURRENT TRANSFORMER ASR22.3
CURRENT TRANSFORMER ASR21.3
ratios: 50 A/5 A 100 A/5 A 150 A/5 A 200 A/5 A 250 A/5 A 300 A/5 A 400 A/5 A 500 A/5 A 600 A/5 A dimensions: a = 61 mm, b = 35 mm, c = 78,5 mm
ratios: 100 A/5 A 150 A/5 A dimensions: a = 48,5 mm, b = 35 mm, c= 65 mm
DISTANCE SLEEVE
DISTANCE SLEEVE
Length 36 mm Ø Inner diameter = 12,5 mm, Ø outer diameter = 22,5 mm Accuracy class = 1
Length 36 mm Ø Inner diameter = 12,5 mm Ø outer diameter = 22,5 mm Accuracy class = 1
Distance sleeve
Current transformer
ENERGY SAFELY SWITCHED
NOTES
23
NOTES
SWITCHGEAR
24
ARS
vertical fuse switch disconnectors - fibre glass extra strenghtened, self extinguishing thermoplastics of V0 flammability class - double clearance between open contacts - arc chutes with deionization plates over every contact - reversibility - top/bottom cable terminal connection - wide range of accesories
ENERGY SAFELY SWITCHED
25
SWITCHGEAR
26
CONSTRUCTION ARS fuse switch disconnectors are manufactured in two versions:
GENERAL INFORMATION
one pole switching (separately each pole) three pole switching (three poles at the same time)
They have manually operated handle therefore making and breaking operations should be done with determined movement. ARS fuse switch disconnectors are available in following sizes (according to rated current): 00 (ARS 00 and ARS 00/100 mm -160 A) and 2 (ARS 400 A). ARS fuse switch disconnectors are designed for installation on to 185 mm busbar system. ARS of size 00 are manufactured in two versions depending on busbar system: ARS 00 fuse switch disconnector (160 A) for installation on to 185 mm busbar system ARS 00/100 mm fuse switch disconnector (160 A) for installation on to 100 mm busbar system Installation on to 185 mm busbar system is possible by using adapter.
Fuse switch disconnectors ARS are made of fibre glass strengthened, thermoplastic polyamides with halogen free flame retardant added. Added flame retardant provides V2 flammability class. Silver plated contacts provide low power loss. Depending on clamp type, ARS fuse switch disconnectors enable user to connect circular or sectorshaped conductors with bare ends or conductors with lug terminals. Arc chute with deionization plates is installed over each contact. Such design provides efficiency of arc extinction and controlled exhaust of arc plasma. ARS fuse switch disconnectors are adapted for using current transformers and ammeters. Protection degree of IP30 from the front is provided. Additionally offered accesories enable to install ARS fuse switch disconnectors of different sizes on common busbar systems. All sizes of ARS pro fuse switch disconnectors are provided complete with clamps (i. e. screws, V-terminals, 2V-terminals) and shrouds for cable terminals.
FUNCTIONALITY
making and breaking operations should be done with determined movement, parallelly moving, double contact system, designed for installation on to 100 mm or 185 mm busbar system, two versions: single pole switching (separately each pole) or triple pole switching (three poles at the same time), fuse switch disconnectors width: 50 mm, 100 mm, 200 mm, suitable for top cable terminal connection, possible connection of circular or sector-shaped conductors with bare ends (V-terminals, 2V-terminals or conductors with lug terminals (screw terminals).
ENERGY SAFELY SWITCHED
Table 27. ARS TECHNICAL DATA
27
Parameters Rated thermal current Ith=In Rated voltage Un
ARS 00
ARS 400 A
160
160
400
V
690
690
690
690 V
AC-22B
AC-22B
AC-22B
Rated switching voltage Ue
V
690
690
690
Rated switching current Ie
A
160
160
400
Rated short-circuit making current
kA
25
22
100
Rated short-circuit withstand current
kA
100
100
100
Rated insulation voltage Ui
V
1000
1000
1000
Rated impulse withstand voltage Uimp.
kV
8
12
12
Rated frequency
Hz
50-60
50-60
50-60
Number of cycles
1600
1600
1000
200
200
200
IP
30
20
30
-
00
00
1, 2
Mechanical durability Electrical durability IP degree of protection Fuse links size
OPERATING CONDITIONS
to be installed in the room free of any dust, aggressive or explosive gases, altitude up to 2000 meters above sea level, outdoor – in cabinets with protection degree > IP 34, ambient temperature from -25 °C to +55 °C, relative humidity of the air should not be higher than 50% at temperature of +40°.
TECHNICAL DATA
Utilization category
A
ARS 00/100 mm
SWITCHGEAR
28
FUSE SWITCH DISCONNECTOR ARS 00/100 mm (160 A, 690 V) For installation on to 100 mm busbar system Fuse switch disconnector’s width 50 mm Three pole switching - all phases simultaneously
ARS 00/100 mm
Table 28. TECHNICAL DATA ARS 00/100 mm
Parameters Rated thermal current Ith=In
A
Rated voltage Un
V
690
Utilization category
-
AC-22B
Rated switching voltage Ue
V
690
Rated switching current Ie
A
160
Rated short circuit making current
kA
25
Rated short circuit withstand current
kA
100
Rated insulation voltage Ui
V
1000
Rated impulse withstand voltage Uimp.
kV
8
Rated frequency
Hz
50-60
Number of cycles
1600
IP
30
-
00
Mechanical durability Electrical durability IP degree of protection Fuse links size
160
200
Accesories on page 42
Table 29. VERSIONS Version
Weight
Article No.
1,3 kg
63-811628-011
for installation on to 100 mm busbar system ,three pole switching - all phases simultaneously ARS 00/100mm
cable terminals: bridge terminals with bridge clamps (S) 4-70 mm2, screw terminals with M8 screws
ARS 00/100mm-V
cable terminals: V-terminals with V-clamps 25-120SW
1,5 kg
63-811628-021
ARS 00/100mm-V
cable terminals: V-terminals, without V-clamps
1,3 kg
63-811628-081
Table 30. ARS 00/100mm TERMINAL CLAMPS Description Clamp
ARS 00/100 mm S-bridge clamp 2 x M5 x 25
M8 screw*
V- clamp 25-120 SW
HM 10-120 ***
Picture of clamp
Drawing of clamp
Cross –section of conductors Tightening torque
4 - 70 mm2
Conductor with lug terminal max 185 mm2
re 16 mm2 - 95 mm2 se 25 mm2 - 120 mm2 rm 16 mm2 - 95 mm2 sm 25 mm2 - 120 mm2
re 10 mm2 - 70 mm2 se 25 mm2 - 120 mm2 rm 10 mm2 - 70 mm2 sm 25 mm2 - 95 mm2
3 Nm**
12 Nm**
20 Nm**
15 Nm**
For stranded conductors using cable ferrules is recommended *) Bars of maximum width of 20 mm and maximum thickness of 5 mm can be fixed to M type screw terminals. **) using tension wrench is recommended ***) fuse switch disconnectors with V-terminals are equipped with steel V-clamp HM 10-120 on request Apator takes responsibility for technical quality of V-terminals manufactured only by the company. Minimum tightening torque (M8 screw) for screws fixing fuse switch disconnector to busbar system – 12 Nm, recommended tightening torque for screws and nuts with property class 8.8 – 21 Nm
ENERGY SAFELY SWITCHED
FUSE SWITCH DISCONNECTOR ARS 00 (160 A, 690 V)
29
For installation on to 185 mm busbar system Three pole switching - all phases simultaneously - two-hand operation or one pole switching - each phase independently Fuse switch disconnector’s width 50 mm Table 31. TECHNICAL DATA ARS 00
Parameters A
Rated voltage Un
V
690
Utilization category
-
AC-22B
160
Rated switching voltage Ue
V
690
Rated switching current Ie
A
160
Rated short circuit making current
kA
22
Rated short circuit withstand current
kA
100
Rated insulation voltage Ui
V
1000
Rated impulse withstand voltage Uimp.
kV
12
Rated frequency
Hz
50-60
Number of cycles
1600
IP
20
-
00
Mechanical durability Electrical durability IP degree of protection Fuse links size
ARS 00
Rated thermal current Ith=In
200
Accesories on page 42
ARS 00-1
ARS 00-3
Table 32. VERSIONS Version
Weight
Article No.
for installation on to 185 mm busbar system, one pole switching - each phase independently ARS 00-1
cable terminals: bridge terminals with bridge clamps (S) 4-70 mm2, screw terminals with M8 screws
2,6 kg
63-811410-011
ARS 00-1-V
cable terminals: V-terminals with V-clamps 25-120SW
2,7 kg
63-811410-021
ARS 00-1-V
cable terminals: V-terminals, without V-clamps
2,6 kg
63-811410-051
for installation on to 185 mm busbar system, three pole switching - all phases simultaneously ARS 00-3
cable terminals: bridge terminals with bridge clamps (S) 4-70 mm2, screw terminals with M8 screws
2,7 kg
63-811806-011
ARS 00-3-V
cable terminals: V-terminals with V-clamps 25-120SW
2,8 kg
63-811806-021
ARS 00-3-V
cable terminals: V-terminals, without V-clamps
2,7 kg
63-811806-051
SWITCHGEAR
30
Table 33. ARS 00 TERMINAL CLAMPS Description Clamp
ARS 00 S-bridge clamp 2 x M5 x 25
M8 screw*
V- clamp 25-120 SW
HM 10-120 ***
ARS 00
Picture of clamp
Drawing of clamp
Cross –section of conductors Tightening torque
4 - 70 mm2
Conductor with lug terminal max 185 mm2
re 16 mm2 - 95 mm2 se 25 mm2 - 120 mm2 rm 16 mm2 - 95 mm2 sm 25 mm2 - 120 mm2
re 10 mm2 - 70 mm2 se 25 mm2 - 120 mm2 rm 10 mm2 - 70 mm2 sm 25 mm2 - 95 mm2
3 Nm**
12 Nm**
20 Nm**
15 Nm**
For stranded conductors using cable ferrules is recommended *) Bars of maximum width of 20 mm and maximum thickness of 5 mm can be fixed to M type screw terminals. **) using tension wrench is recommended ***) fuse switch disconnectors with V-terminals are equipped with steel V-clamp HM 10-120 on request Apator takes responsibility for technical quality of V-terminals manufactured only by the company. Minimum tightening torque (M8 screw) for screws fixing fuse switch disconnector to busbar system – 12 Nm, recommended tightening torque for screws and nuts with property class 8.8 – 21 Nm
ENERGY SAFELY SWITCHED
FUSE SWITCH DISCONNECTOR ARS 400 A (400 A, 690 V)
31
For installation on to 185 mm busbar system Three pole switching - all phases simultaneously or one pole switching - each phase independently Fuse switch disconnector’s width 100 mm Designed for operation with NH1 and NH2 fuse links Table 34. TECHNICAL DATA
ARS 400 A
ARS 400 A
Parameters Rated thermal current Ith=In
A
400
Rated voltage Un
V
690
Utilization category
-
AC-22B
Rated switching voltage Ue
V
690
Rated switching current Ie
A
400
Rated short circuit making current
kA
100
Rated short circuit withstand current
kA
100
Rated insulation voltage Ui
V
1000
Rated impulse withstand voltage Uimp.
kV
12
Hz
50-60
Number of cycles
1000
Rated frequency Mechanical durability Electrical durability IP degree of protection Fuse links size
200
IP
30
-
1, 2
Accesories on page 43
ARS 2-1-V
Table 35. VERSIONS
ARS 2-6-V
Version
Weight
Article No.
5,0 kg 4,8 kg 5,7 kg 4,7 kg 5,2 kg
63-811825-011 63-811825-031 63-811825-051 63-811825-091 63-811825-121
5,0 kg 4,8 kg 5,7 kg 4,7 kg 5,2 kg
63-811826-011 63-811826-031 63-811826-051 63-811826-091 63-811826-121
for installation on to 185 mm busbar system, one pole switching - each phase independently ARS 2-1-V cable terminals: V-terminals with V-clamps 240 mm2 ARS 2-1-M cable terminals: screw terminals with pressed nuts M10 ARS 2-1-2V cable terminals: 2V-terminals with double V-clamps 240 mm2 ARS 2-1-V cable terminals: V-terminals without V-clamps ARS 2-1-2V cable terminals: 2V-terminals without double V-clamps for installation on to 185 mm busbar system, three pole switching - all phases simultaneously ARS 2-6-V cable terminals: V-terminals with V-clamps 240 mm2 ARS 2-6-M cable terminals: screw terminals with pressed nuts M10 ARS 2-6-2V cable terminals: 2-Vterminals with double V-clamps 240 mm2 ARS 2-6-V cable terminals: V-terminals without V-clamps ARS 2-6-2V cable terminals: 2-Vterminals without double V-clamps
Table 36. ARS 400 A TERMINAL CLAMPS
V-clamp 35-300SW-B
V-clamp HS 2/35-240-C
M10 screw (pressed nut)
V-clamp for direct fixing of conductor with bare end with crosssection of: 35 - 185 mm2
35 - 240 mm2
35 - 185 mm2
35 - 240 mm2
35 - 240 mm
35 - 300 mm
35 - 240 mm
35 - 300 mm2
2
Tightening torque
2
30 Nm
2
40 Nm
Lug terminal
ARS 2-x-M (400 A)
Crosssection of conductors
Drawing of clamp
ARS 2-x-2V (400 A)
Cross -section of conductors
Clamp
ARS 2-x-V (400 A)
Cross -section of conductors
Description
32 Nm
For stranded conductors using cable ferrules is recommended *) Bars of maximum width of 40 mm and maximum thickness of 8 mm can be fixed to M type screw terminals when protective barrier between phases is installed. Apator takes responsibility for technical quality of V-terminals manufactured only by the company. Minimum tightening torque (M12 screw) for screws fixing fuse switch disconnector to busbar system – 32 Nm, recommended tightening torque for screws and nuts with property class 8.8 – 56 Nm
SWITCHGEAR
THREE PHASE CURRENT MEASUREMENT WITH FUSE SWITCH DISCONNECTOR ARS
THREE PHASE CURRENT MEASUREMENT
32
ONE PHASE CURRENT MEASUREMENT WITH FUSE SWITCH DISCONNECTOR ARS
Fuse switch disconnectors ARS 400 A, ARS 2 pro, ARS 3 pro
Fuse switch disconnectors ARS 00/160 mm, ARS 00/160 mm pro, ARS 00, ARS 00 pro
CURRENT TRANSFORMER ASR22.3
CURRENT TRANSFORMER ASR21.3
ratios: 50 A/5 A 100 A/5 A 150 A/5 A 200 A/5 A 250 A/5 A 300 A/5 A 400 A/5 A 500 A/5 A 600 A/5 A dimensions: a = 61 mm, b = 35 mm, c = 78,5 mm
ratios: 100 A/5 A 150 A/5 A dimensions: a = 48,5 mm, b = 35 mm, c= 65 mm
DISTANCE SLEEVE
DISTANCE SLEEVE
Length 36 mm Ø Inner diameter = 12,5 mm, Ø outer diameter = 22,5 mm Accuracy class = 1
Length 36 mm Ø Inner diameter = 12,5 mm Ø outer diameter = 22,5 mm Accuracy class = 1
Distance sleeve
Current transformer
ENERGY SAFELY SWITCHED
ARS 00/100 mm , ARS 00-1, ARS 00-3, ARS 00/100 mm pro, ARS 00-1 pro, ARS 00-3 pro
33
127
8,5x16
423
ø 8,5
50 100 100
172,5 113,5
84,5 38 39,5
39,6
39 40,6
24
OPENED 240
PARKED 163
ARS OVERALL DIMENSIONS
CLOSED 49,8
SWITCHGEAR
34
ARS 00/100 mm , ARS 00-1, ARS 00-3, ARS 00/100 mm pro, ARS 00-1 pro, ARS 00-3 pro CLOSED 134
279,5
49,5
185
279,5
185 297,5
297,5 185
705
705
279,5
49,5
1-phase 133,7 106
185
ARS OVERALL DIMENSIONS
3-phase 133,7 106
3
40
40 40
39,5
15,5
44 45
44 45
141,5
OPENED 3-phase 186
PARKED 1-phase 185
3-phase 196
ARS WITH HEIGHTENED RAILS 1-phase
3-phase
204
1-phase
165 31
165 31
172,5
172,5
ENERGY SAFELY SWITCHED
ARS 400 A, ARS 2 pro, ARS 3 pro
35 175 135
40
305
185
185
665
ø 14
185
92
92
ARS OVERALL DIMENSIONS
220 230
18,5
52
220 225
175
170 135
92 185 185
665
185
40
305
665
185
ø 14
185
185
92
92
135
52 99
18,5
53,5 150
53,5 150
99
18,5
53,5 150
SWITCHGEAR
TERMINALS 2x240 mm2
TERMINALS 3x120 mm2
185 709
ø 14
185
38 30
30 38
32,5 30 38
349
752
185
185
744 349
50
11 48,5 49,5
42 12
175
92 185 780
ø 14
185 185
185
ø 14 780
175 135
92
92 185
92 185 185
150
ARS 630 kVA-6-3M pro RWS 1250-6-3M pro
135
50
185
ARS 630 kVA-6-2M pro RWS 1250-6-2M pro
49
36 36
36 36
401
401
ARS OVERALL DIMENSIONS
92
36
46 99
6,5
54,5 51,5 151,5
46
46 199
6,5
54,5 51,5 151,5
ENERGY SAFELY SWITCHED 175
175
135
135
ARS 630 kVA-1-3M pro
37
92 185
185
185
780
36 36
36 36
401
401
185
185
185
780
ø 14
ø 14
185
ARS OVERALL DIMENSIONS
185
92
92
92
ARS 630 kVA-1-2M pro
6,5
46
54,5 51,5
46 46
151,5
99
6,5
54,5 51,5
199
151,5 175
ARS 400 A, ARS 2 pro, ARS 3 pro with terminals 2V (2 x 240 mm2)
135
185
702
305
373,5
185
753,5
185
ø 14
185
185
185
92
92
92
ARS 1250-1-3M pro
76
46
79
7
45 195
59,5
28 55 151,5
52 99
5
67 150 178
183,5
ARS 2-X pro ARS 3-X pro 59,5
185
195
183,5
183,5
183,5
45
185
185
185
756
185
185
756
185
46
79
373,5 185
753,5 185
92
38
185
ARS OVERALL DIMENSIONS
SWITCHGEAR
ARS 1250-1-4M pro
7
28
151,5 55
157,5 157,5
ENERGY SAFELY SWITCHED
ARS 2 pro, ARS 3 pro with lateral busbar terminal
39
99
92
548
548 600
600
185
185
185
185
185
185
14
ø 14
ø 14
185
185
92
14
92
175 135
66
66
RWS 1250 NT pro 175
120 lub 170
665
185
68
99
ø14
185
50
ARS, RWS OVERALL DIMENSIONS
175 135
92
99
SWITCHGEAR
40
RWS 1250 NR pro 175
99
64
20
120 lub 170
50
185
99
185
665
2 x ø13,5
RWS 1250 NL pro 175
64
99
20
20
185
99
185
665
50
RWS OVERALL DIMENSIONS
20
2 x ø13,5
ENERGY SAFELY SWITCHED
Adjusting ARS 00/100 mm, ARS 00/100 mm pro to ARS 400 A, ARS 2 pro, ARS 3 pro, ARS 630 kVA pro, RWS 1250 A pro, ARS 1250 pro
41
4 2
2
1
1
2
2 3
3 Adjusting dimensions of ARS 00/100 mm to length and depth of ARS 1, 2, 3 with terminal shroud. Installation of extended shroud on the top of ARS 00/100 mm and label holder on the top of ARS 1, 2, 3 enables easy installation under distribution board’s panel
Adjusting dimensions of ARS 00/100 mm to length and depth of ARS 1, 2, 3 with terminal shroud.
5 4 2 1
2 1
2 2
4 5
6 Adjusting dimensions of ARS 00/100 mm to length and depth of ARS 1,2,3 without terminal shroud.
DESCRIPTION 1. 63-930547-011 Single Adapter 100/185 or 63-930549-011 Double adapter 100/185 2. 53-945924-011 terminal shroud 3. 51-823244-011 Extended terminal shroud 4. 51-945857-011 Extended terminal shroud 5. 53-945826-011 Label holder 6. 51-930272-011 Cable terminal protective cover Accessories on page 42-43
6 Adjusting dimensions of ARS 00/100 mm to length and depth of ARS 1,2,3 without terminal shroud. Installation of extended shroud on the top and bottom of ARS 00/100 mm and label holder on the top and bottom of ARS 1,2,3 enables easy installation under distribution board’s panel and Prisma enclosures.
Adjusting ARS 00/100 mm to ARS 1, 2, 3
5
SWITCHGEAR
1119510077T 53-945361-011
16 - 95 mm2
25 - 120 mm2
25 - 120 mm2
V- clamp HM-10-120. For connection of conductor with cross-section: 10 - 70 mm2
10 - 70 mm2
25 - 120 mm
2
25 - 95 mm2
Hooked clamps for installation of ARS on to busbar system without drilled holes. (set - 3 pcs.)
1115296049
ARS 00/100 mm Micro switch for fuse link cover position monitoring (0-1) of ARS 00/100mm
support angle for installation of Busbar shroud
53-945333-011
16 - 95 mm2
53-945924-011
V- clamp 25-120 SW. For connection of conductor with cross-section:
51-823244-011
1115281041T
Universal earthing device for ARS 00, 1, 2, 3
51-945857-011
00 – SV 1115281034
V-shape clamp – S-bridge clamp + V-shape saddle - for connection of sector-shaped conductors with cross-section 1,5 up to 70 mm2 (stranded) or 95 mm2 (solid) (set - 3 pcs.)
Extended terminal shroud/adjusting shroud. When fixed to shroud 53-945924-011it adjusts the length and height of ARS 00/100 mm to that of ARS 1, 2, 3 with label holder 53-945826-011. It allows installation of ARS 00/100 mm in Prisma enclosures
1115281021T
00 – S
S-Bridge clamp – fixed with 2 x M5 screw - for connection of conductors with cross-section 4 mm2 up to 70 mm2 (set – 3 pcs.)
Single adapter 100/185 enabling to install ARS 00/100 mm on busbar system 185 mm
Double adapter 100/185 enabling to install two ARS 00/100 mm units on busbar system 185 mm
ARS 00 51-945160-011 (Nr dot. 1 szt.)
1115718010T
Distance sleeve for current transformer ASR 21.3 (Length 36 mm, outer diameter = 22,5 mm, inner diameter =12,5 mm)
Extended terminal shroud/adjusting shroud. Together with two shrouds 53-945924-011 it adjusts the length and height of ARS 00/100 mm to that of ARS 1, 2, 3 with terminal shroud
Single distance adapter 185/185. It adjusts front line of ARS 00 to that of ARS 1,2,3 (set – 3 pcs.)
52-945158-011 (Nr dot. 1 szt.)
1115718002T
Current transformer ASR21.3; Accuracy class 1; Ratios: 50/5 A to 150/5 A
Terminal shroud/adjusting shroud. When fixed on top and bottom of ARS 00/100 mm it adjusts it’s length and height to length and height of ARS 1, 2, 3 enclosure
Double distance adapter 185/185. Designed for two ARS 00 units. It adjusts front line of ARS 00 to that of ARS 1,2,3 (set – 3 pcs.)
51-823342-011
1361400001T
Isolating pin for fixing the 50 mm busbar shroud, M8 (set – 2 pcs.)
Labelling area
Terminal shroud
53-945361-041
00 – M 1361400006T
Busbar shroud (polycarbonate) for busbar system 185 mm, Width 50 mm, length 562 mm, thickness 3 mm
25-120 SW 1119510008T
M8 terminal screw, for connection of conductors with lug terminal (set - 3 pcs.)
1115281022T
ARS 00/100 mm
ARS 00, ARS 00 /100 mm
1115281081T
ARS ACCESSORIES
42
Hooked clamps for installation of ARS pro with heightened rails on to busbar system without drilled holes. (set - 3 pcs.)
ENERGY SAFELY SWITCHED
35 - 300 mm2
Double V-clamp. For connection of two conductors with cross-section: 35 - 185 mm2
35 - 240 mm2
35 - 240 mm2
35 - 300 mm2
V-clamp HS (steel) for connection of two conductors with cross-section
35 - 300 mm2
53-931200-001
35 - 240 mm2
Cable terminal 2x240 mm2 Cable terminal for connection of two cables with lug terminals and cross-section of 240 mm2 to each phase Set contains two M12 screws per terminal and cable terminal shroud. For use with ARS 2 pro, ARS 3 pro, ARS 400 with M terminals
53-931201-001
35 - 240 mm2
Cable terminal 3x120 mm2 Cable terminal for connection of three cables with lug terminals and cross-section of 120 mm2 to each phase Set contains three M12 screws per terminal and cable terminal shroud. For use with ARS 2 pro, ARS 3 pro, ARS 400 with M terminals
63-931296-001
35 - 185 mm2
Przyłącze kablowe umożliwiające podłączenie bezpośrednio dwóch odizolowanych żył kabli o przekroju do 240 mm2. Zestaw 3 szt obejm+osłona zacisku. Do ARS w wersji zacisków typu V
Hooked clamps for installation of ARS 1, 2, 3 on to busbar system without drilled holes (set - 3 pcs.)
1361400007T
35 - 240 mm
1361400002T
35 - 240 mm2
2
51-930313-011
35 - 185 mm2
Extended terminal shroud. For use with terminal shroud 51-930271-021
51-930272-011
V- clamp. For connection of conductor with cross-section:
Terminal protective cover
51-930271-021
35 - 300 mm
Isolating pin for fixing the 50 mm busbar shroud, M12 (set – 2 pcs.)
Terminal shroud
1115718006T
35 - 240 mm
2
Current transformer ASR22.3 Accuracy class 1 Ratios: 50/5 A to 600/5 A
115718010T
35 - 150 mm2
2
Distance sleeve for current transformer ASR 22.3 Length 36 mm, outer diameter =22,5 mm, inner diameter =12,5 mm
1115281041T
35 - 120 mm2
Busbar shroud (polycarbonate) for busbar system 185 mm, Width 100 mm, length 562 mm, thickness 3 mm
Universal earthing device for ARS 00, 1, 2, 3
53-945826-01
HS 35-300-C 1119510084T 2/35-300SW-B 1119510082T
V- clamp. For connection of conductor with cross-section:
1115281037T
HS 2/35-240-C 1119510085T
M10 terminal screw: for ARS 1 and ARS 2 M12 terminal screw: for ARS 3; for connection of conductors with lug terminal (set- 3pcs)
ARS 400 A, ARS 2 pro, ARS 3 pro, ARS 630 kVA pro, ARS 1250 pro
Label holder
43
AKCESORIA ARS
35-300 SW-B 1119510081T
M
ARS 400 A, ARS 2 pro, ARS 3 pro, ARS 630 kVA pro, ARS 1250 pro
SWITCHGEAR
PBS
vertical fuse rails
- self extinguishing thermoplastics with flame retardant - touch protection IP 20 with fuse link shrouds
ENERGY SAFELY SWITCHED
SWITCHGEAR
46
GENERAL INFORMATION PBS fuse rails thanks to it’s high technical standards are among top such products. They are approved and recognized by polish and foreign electricity boards and distribution boards manufacturers.
GENERAL INFORMATION
APPLICATIONS PBS fuse bases are designed for the distribution of electricity and protection against short circuits and overloads in three phase alternative current circuits with maximum operating voltage of 690 V. They are intended for direct installation on horizontal or vertical bus bar system. Due to their modern and compact design installing is easy and gives much saving of space in substations and distribution boards. All technical parameters required by standards and requirements of the market were taken into account during design (conformity with EN 60269-1, HD 60269-2). Several advices and remarks from business partners were also taken into account.
CONSTRUCTION: plastic parts of PBS fuse rails are made of fibre glass strengthened, thermoplastic polyamides, silver plated contacts provide low power loss, all energized metal parts are fully protected against accidental touch.
FUNCTIONALITY: PBS FUSE RAILS are available in following sizes : 00 -160 A; 2 -400 A; 3-630 A, designed for installation on to 185 mm busbar system, size 00, 1, 2, 3, PBS 00/100 mm fuse rails are designed for installation on to 100 mm busbar system installation on to 185 mm busbar system is possible by using adapter, fuse rails width: size 2, 3 - 100 mm, size 00 – 50 mm, removal of the fuse link provides clearly noticeable, large isolating gap in the circuit, possible installation of various earthing devices, possible connection of circular or sector-shaped conductors with bare ends (V-terminals, 2V-terminals or conductors with lug terminals (screw terminals), touch protection IP 20 with fuse link shrouds for fuse rails of size 2, 3.
ENERGY SAFELY SWITCHED
Table 37. PBS FUSE RAILS TECHNICAL DATA Parameters Size
47 PBS 00/100 mm
PBS 00-SM
PBS 2
PBS 3
00
00
2
3
Rated thermal current Ith=In
A
160
160
400
630
Rated voltage Un
V
690
690
690
690
Rated insulation voltage Ui
V
1000
1000
1000
1000
Rated frequency
Hz
50-60
50-60
50-60
50-60
W
12
12
45
60
Rated short-circuit withstand current
kA
100
100
100
100
Number of cycles
100
100
100
100
Weight
kg
0,75
2,00
4,50
5,00
IP degree of protection
IP
00
00
20*
20*
00
00
2
3
Mechanical durability
Size of fuse links * with fuse link shrouds
OPERATING CONDITIONS to be installed in the room free of any dust, aggressive or explosive gases, altitude up to 2000 meters above sea level, outdoor – in cabinets with protection degree > IP 34, ambient temperature from -25 °C to +55 °C – but in case of use of disconnectors in temperature from +41 °C to +45 °C current value Ith should be reduced by 5 % and within temperature range of +46 °C to +55 °C current value Ith should be reduced by 10 %, relative humidity of the air should not be higher than 50 % at temperature of +40 °C.
TECHNICAL DATA
Rated power dissipation
SWITCHGEAR
48
FUSE RAIL PBS 00/100 mm (160 A, 690 V) For 100 mm busbar system
1
PBS 00/100 mm
8
4
2
3
Place of installing insulating barrier Place of installing clip with description label
5
6
7
DESCRIPTION 1. 2. 3. 4. 5. 6. 7. 8.
Main base Protective contact cover Terminal shroud Busbar terminals acces covers S-bridge clamp M8 screw V-shape clamp for sector-shaped conductor Hooked clamp
Terminal shroud label
PBS 00/100 mm PBS 00/100 mm-V
ENERGY SAFELY SWITCHED
PBS 00/100 mm (160 A, 690 V)
49
Table 38. TECHNICAL DATA PBS 00/100 mm
Parameters Size
00
Rated thermal current Ith=In
A
160
Rated voltage Un
V
690
V
1000
Hz
50-60
Rated power dissipation
W
12
Rated short-circuit withstand current
kA
100
Mechanical durability
Number of cycles
100
IP degree of protection
IP
00
Size of fuse links
PBS 00/100 mm
Rated insulation voltage Ui Rated frequency
00
Accesories on page 60
PBS 00/100 mm PBS 00/100 mm-V Table 39. VERSIONS Version
Weight
Article No.
PBS 00/100 mm
cable terminals: bridge terminals with bridgeclamps (S) 4-70 mm , screw terminals with M8 screws
1,0 kg
63-811627-011
PBS 00/100 mm-V
cable terminals: V-terminals with V-clamps 25-120SW
1,1 kg
63-811627-021
PBS 00/100 mm-V
cable terminals: V-terminals, without V-clamps
1,0 kg
63-811627-041
2
Table 40. PBS 00/100 mm TERMINAL CLAMPS Description Clamp
PBS 00/100 mm S-bridge clamp 2 x M5 x 25
M8 screw*
V- clamp 25-120 SW
HM 10-120 ***
Picture of clamp
Drawing of clamp
Cross–section of conductors Tightening torque
4 - 70 mm2
Conductor with lug terminal max 185 mm2
re 16 mm2 - 95 mm2 se 25 mm2 - 120 mm2 rm 16 mm2 - 95 mm2 sm 25 mm2 - 120 mm2
re 10 mm2 - 70 mm2 se 25 mm2 - 120 mm2 rm 10 mm2 - 70 mm2 sm 25 mm2 - 95 mm2
3 Nm**
12 Nm**
20 Nm**
15 Nm**
For stranded conductors using cable ferrules is recommended *) Bars of maximum width of 20 mm and maximum thickness of 5 mm can be fixed to M type screw terminals. **) using tension wrench is recommended ***) fuse switch disconnectors with V-terminals are equipped with steel V-clamp HM 10-120 on request Apator takes responsibility for technical quality of V-terminals manufactured only by the company. Minimum tightening torque (M8 screw) for screws fixing fuse switch disconnector to busbar system –12 Nm, recommended tightening torque for screws and nuts with property class 8.8 – 21 Nm
SWITCHGEAR
50
FUSE RAIL PBS 00-SM (160 A, 690 V) For 185 mm busbar system Table 41. TECHNICAL DATA PBS 00-SM
Parameters
PBS 00-SM
Size
00
Rated thermal current Ith=In
A
160
Rated voltage Un
V
690
Rated insulation voltage Ui
V
1000
Rated frequency
Hz
50-60
Rated power dissipation
W
12
Rated short-circuit withstand current
kA
100
Mechanical durability
Number of cycles
100
IP degree of protection
IP
00
Size of fuse links
00
Accesories on page 60
PBS 00-SM PBS 00-V Table 42. VERSIONS Version
Weight
Article No.
PBS 00-SM
cable terminals: bridge terminals with bridge clamps (S) 4-70 mm , screw terminals with M8 screws
2,0 kg
63-811411-011
PBS 00-V
cable terminals: V-terminals with V-clamps 25-120SW
2,1 kg
63-811411-031
PBS 00-V
cable terminals: V-terminals, without V-clamps
2,0 kg
63-811411-051
2
Table 43. PBS 00 TERMINAL CLAMPS Description Clamp
PBS 00 S-bridge clamp 2 x M5 x 25
M8 screw*
V- clamp 25-120 SW
HM 10-120 ***
Picture of clamp
Drawing of clamp
Cross – section of conductors Tightening torque
4 - 70 mm2
Conductor with lug terminal max 185 mm2
re 16 mm2 - 95 mm2 se 25 mm2 - 120 mm2 rm 16 mm2 - 95 mm2 sm 25 mm2 - 120 mm2
re 10 mm2 - 70 mm2 se 25 mm2 - 120 mm2 rm 10 mm2 - 70 mm2 sm 25 mm2 - 95 mm2
3 Nm**
12 Nm**
20 Nm**
15 Nm**
For stranded conductors using cable ferrules is recommended *) Bars of maximum width of 20 mm and maximum thickness of 5 mm can be fixed to M type screw terminals. **) using tension wrench is recommended ***) fuse switch disconnectors with V-terminals are equipped with steel V-clamp HM 10-120 on request Apator takes responsibility for technical quality of V-terminals manufactured only by the company. Minimum tightening torque (M8 screw) for screws fixing fuse switch disconnector to busbar system –12 Nm, recommended tightening torque for screws and nuts with property class 8.8 – 21 Nm
ENERGY SAFELY SWITCHED
FUSE BASE PBS 2 (400 A, 690 V) PBS 3 (630 A, 690 V)
51
1 Option of fuse link state indication by neon indicator tube
PBS 2 | PBS 3
3
Labels on bus bar terminals acces covers
4 2
9
Clip with label
6 5
8
7
DESCRIPTON 1. Main base 2. Hooked clamp – for installation on to busbar system 1115281037T 3. Terminal shroud for fuse switch disconnector with double V-clamps (2 x 240 mm2) 4. Terminal shroud (long) 51-930271-021 5. Terminal shroud (short) 6. Bottom adjusting shroud 51-930313-011 7. Cable terminal protective cover 51-930272-011 8. Protective barrier
Terminal shroud label
PBS 2 PBS 3
SWITCHGEAR
52
PBS 2 (400 A, 690 V) Fuse rail designed for operation with NH1 and NH2 fuse links Table 44. TECHNICAL DATA PBS 2
Parameters
2
Rated thermal current Ith=In
A
400
Rated voltage Un
V
690
Rated insulation voltage Ui
V
1000
Rated frequency
Hz
50-60
Rated power dissipation
W
45
Rated short-circuit withstand current
kA
100
Mechanical durability
Number of cycles
100
IP degree of protection
IP
20*
Size of fuse links
1,2
Accesories on page 61 *with fuse link shrouds
PBS 2-2V
PBS 2-V with fuse link shrouds
Table 45. VERSIONS Wykonanie
Weight
Article No.
PBS 2-V
cable terminals: V-terminals with V-clamps (35-240 mm2)
3,2 kg
63-811639-011
PBS 2-M
cable terminals: screw terminals with pressed nuts M10 (M10 screw)
3,1 kg
63-811639-031
PBS 2-2V
cable terminals: 2V-terminals with double Vclamps (2 x 50- 240 mm2)
3,8 kg
63-811639-051
Table 46. PBS 2 TERMINAL CLAMPS PBS 2-2V (400 A)
PBS 2-M (400 A)
V-clamp HS 2/35-240-C
M10 screw (pressed nut)*
V-clamp for direct fixing of conductor with bare end with crosssection of: 35 - 185 mm2
35 - 240 mm2
35 - 185 mm2
35 - 240 mm2
35 - 240 mm
35 - 300 mm
35 - 240 mm
35 - 300 mm2
2
Tightening torque
2
30 Nm
2
40 Nm
Lug terminal
Drawing of clamp
PBS 2-V (400 A) V-clamp 35-300SW-B
Cross-setion of condutors
Clamp
Cross-setion of condutors
Description
Cross-setion of condutors
PBS 2
Size
32 Nm
*For stranded conductors using cable ferrules is recommended Bars of maximum width of 40 mm and maximum thickness of 8 mm can be fixed to M type screw terminals when protective barrier between phases is installed. Apator takes responsibility for technical quality of V-terminals manufactured only by the company. Minimum tightening torque (M12 screw) for screws fixing fuse switch disconnector to busbar system – 32 Nm, recommended tightening torque for screws and nuts with property class 8.8 – 56 Nm
ENERGY SAFELY SWITCHED
PBS 3 (630 A, 690 V)
53
Table 47. TECHNICAL DATA PBS 3
Parameters Size
3
Rated thermal current Ith=In
A
630
Rated voltage Un
V
690
Rated insulation voltage Ui
V
1000
Rated frequency
Hz
50-60
Rated power dissipation
W
60
Rated short-circuit withstand current
100
Mechanical durability
100
IP degree of protection
IP
20*
Size of fuse links
PBS 3
kA Number of cycles
3
Accesories on page 61 *with fuse link shrouds
PBS 3-2V
PBS 3-M with fuse link shrouds
Table 48. VERSIONS Wykonanie
Weight
Article No.
PBS 3-V
cable terminals: V-terminals with V-clamps (70-300 SW)
4,0 kg
63-811639-021
PBS 3-M
cable terminals: screw terminals with pressed nuts M12 (M12 screw)
4,1 kg
63-811639-041
PBS 3-2V
cable terminals: 2V-terminals with double V-clamps (2 x 50- 240 mm )
4,8 kg
63-811639-061
2
Table 49. PBS 3 TERMINAL CLAMPS
V-clamp 35-300SW-B
V-clamp HS 2/35-240-C
M10 screw (pressed nut)*
V-clamp for direct fixing of conductor with bare end with cross-section of: 35 - 185 mm2
35 - 240 mm2
35 - 185 mm2
35 - 240 mm2
35 - 240 mm
35 - 300 mm
35 - 240 mm
35 - 300 mm2
2
Tightening torque
2
30 Nm
2
40 Nm
Lug terminal
PBS 3-M (630 A)
Cross-setion of condutors
Drawing of clamp
PBS 3-2V (630 A)
Cross-setion of condutors
Clamp
PBS 3-V (630 A)
Cross-setion of condutors
Description
56 Nm
*For stranded conductors using cable ferrules is recommended Bars of maximum width of 40 mm and maximum thickness of 8 mm can be fixed to M type screw terminals when protective barrier between phases is installed. Apator takes responsibility for technical quality of V-terminals manufactured only by the company. Minimum tightening torque (M12 screw) for screws fixing fuse switch disconnector to busbar system – 32 Nm, recommended tightening torque for screws and nuts with property class 8.8 – 56 Nm
SWITCHGEAR
54
PBS FUSE RAIL WITH LATERAL BUSBAR TERMINAL (separation, coupling of busbar systems)
PBS fuse rail with lateral busbar terminal
Table 50. TECHNICAL DATA PBS 2
Parameters Size
PBS 3
2
3
Rated thermal current Ith=In
A
400
630
Rated voltage Un
V
690
690
Rated insulation voltage Ui
V
1000
1000
Rated frequency
Hz
50-60
50-60
Rated power dissipation
W
45
60
Rated short-circuit withstand current
kA
100
100
Mechanical durability
Number of cycles
100
100
IP degree of protection
IP
20*
20*
2
3
Size of fuse links Accesories on page 61 *with fuse link covers
PBS 2-NR
PBS 3-NL
Table 51. VERSIONS Version
Weight
Article No.
PBS 2-NL
lateral busbar terminal - left side
2,2 kg
63-811673-011
PBS 2-NR
lateral busbar terminal - right side
2,2 kg
63-811673-031
PBS 3-NL
lateral busbar terminal - left side
3,0 kg
63-811673-021
PBS 3-NR
lateral busbar terminal - right side
3,0 kg
63-811673-041
Table 52. PBS (WITH LATERAL BUSBAR TEMINAL) TERMINAL CLAMPS Description Clamp Cable terminal Tightening torque
Drawing of clamp
PBS 2-NL (400 A)
PBS 2-NR (400 A)
PBS 3-NL (630 A)
PBS 3-NR (630 A)
M12 screw
M12 screw
M12 screw
M12 screw
Left side
Right side
Left side
Right side
56 Nm
56 Nm
56 Nm
56 Nm
ENERGY SAFELY SWITCHED
THREE PHASE CURRENT MEASUREMENT WITH FUSE RAIL PBS
ONE PHASE CURRENT MEASUREMENT WITH FUSE FUSE RAIL PBS
55
ratios: 100 A/5 A 150 A/5 A dimensions: a = 48,5 mm, b = 35 mm, c= 65 mm DISTANCE SLEEVE C
Length 36 mm Inner diameter = 12,5 mm, outer diameter = 22,5 mm Accuracy class = 1
B A
Distance sleeve
Current transformer
PBS 00/100 mm
8,5x16
172,5
113,5
423
50 100 100
8,5x16 ø 8,5
50 100
ø 8,5
39,5
39,5
38
39,5
84.5
100
112,5
49,8
49,8
24
40,6
THREE PHASE CURRENT MEASUREMENT
PBS 00/160 A fuse rails ASR21.3 CURRENT TRANSFORMER
40
39,5
97
185 705 185
8,5x1
94,5
40 39,5
97 185
705
8,5
185
49
94,5
56,5
8,5x1
56
8,5
PBS DIMENSIONS
SWITCHGEAR
PBS 00-SM
15,5
44
49
44 45
141,5
15,5
3
45
141,5
ENERGY SAFELY SWITCHED
PBS 2 | PBS 3
57
113
99 83
L3
112
40
305
185
664
ø 8,5
185
92
111
L2
L1 52 99
18,5
53,5
150
PBS DIMENSIONS
150
SWITCHGEAR
PBS 2 | PBS 3 with terminals 2V (2 x 240 mm2)
PBS DIMENSIONS
150 113
82
111
185 76,5
L3
150
305
702
185
92
99
ø 14
58
L2
L1 52 99
5
67
150 178
ENERGY SAFELY SWITCHED
PBS 2 | PBS 3 with lateral busbar terminal
59
113 111
L1
L1
L2
L2
L3
L3
185
600
14
ø 14
185
92
99 82
50 66
PBS DIMENSIONS
150
SWITCHGEAR
1115718002T
Current transformer ASR21.3; Accuracy class 1; Ratios: 50/5 A to 150/5 A
1115718010T
Distance sleeve for current transformer ASR 21.3 (Length 36 mm, outer diameter =22,5 mm, inner diameter =12,5 mm)
00 – S
S-Bridge clamp – fixed with 2 x M5 screw - for connection of conductors with cross-section 4 mm2 up to 70 mm2 (set – 3 pcs.)
V-shape clamp – S-bridge clamp + V-shape saddle - for connection of sector-shaped conductors with cross-section 1,5 up to 70 mm2 (stranded) or 95 mm2 (solid) (set - 3 pcs.)
53-945924-011
1361400001T
Isolating pin for fixing the 50 mm busbar shroud, M8 (set – 2 pcs.)
1115281021
53-945361-011
Hooked clamps for installation of ARS on to busbar system without drilled holes. (set - 3 pcs.)
Terminal shroud/adjusting shroud
Single adapter 100/185 enabling to install PBS 00/100 mm on busbar system 185 mm
1115281022T
1361400006T
Busbar shroud (polycarbonate) for busbar system 185 mm, Width 50 mm, length 562 mm, thickness 3 mm
PBS 00/100 mm
Double adapter 100/185 enabling to install two PBS 00/100mm units on busbar system 185 mm
51-930474-011
00 – M
M8 terminal screw, for connection of conductors with lug terminal (set - 3 pcs.)
1115281034T
PBS 00 | PBS 00/100 mm
Insulating barrier for PBS 00/100 mm
V- clamp HM-10-120. For connection of conductor with cross-section: 10 - 70 mm2
10 - 70 mm2
25 - 120 mm
2
25 - 95 mm2
51-945160-011 (Nr dot. 1 szt.) 52-945158-011 (Nr dot. 1 szt.)
Universal earthing device for PBS 00, 1, 2, 3
Double distance adapter 185/185. Designed for two PBS 00 units. It adjusts front line of PBS 00 to that of PBS 1, 2, 3 (set – 3 pcs.)
Single distance adapter 185/185. It adjusts front line of ARS 00 to that of ARS 1, 2, 3 (set – 3 pcs.)
51-823342-011
1115281041T
PBS 00
1119510077T
PBS ACCESSORIES
60
Terminal shroud
ENERGY SAFELY SWITCHED
35 - 240mm2
35 - 240 mm2
35 - 300 mm2
Double V-clamp. For connection of two conductors with cross-section:
35 - 185 mm2
35 - 240 mm2
35 - 240 mm
35 - 300 mm2
1115281037T
HS 2/35-240-C 1119510085T
VL240/ 1119510002T
2
V-terminal lug for V-clamp for connection of conductors with cross-section 35 mm2 up to 240 mm2
V-clamp HS (steel) for connection of two conductors with cross-section
35 - 135 mm2
35 - 240 mm2
35 - 240 mm2
35 - 300 mm2
Hooked clamps for installation of PBS 1, 2, 3 on to busbar system without drilled holes (set - 3 pcs.)
1361400007T
35 - 185 mm2
1361400002T
V-clamp. For connection of conductor with cross-section:
51-930313-01
35 - 300 mm2
Extended terminal shroud. For use with terminal shroud 51-930271-021
51-930272-011
35 - 240 mm2
Terminal protective cover
1115718006T
35 - 150 mm2
Current transformer ASR22.3 Accuracy class 1 Ratios: 50/5 A to 600/5 A
115718010T
35 - 120 mm2
Isolating pin for fixing the 100mm busbar shroud, M12 (set – 2 pcs.)
Distance sleeve for current transformer ASR 22.3 Length 36 mm, outer diameter =22,5 mm, inner diameter =12,5 mm
51-930271-021
V-clamp. For connection of conductor with cross-section:
Busbar shroud (polycarbonate) for busbar system 185 mm, Width 100 mm, length 707 mm, thickness 2 mm
Terminal shroud
51-836288-011
M10 terminal screw: for PBS 1 and PBS 2 M12 terminal screw: for PBS 3; for connection of conductors with lug terminal (set- 3pcs)
Fuse link shroud
1115281041T
HS 35-300-C 1119510084T 2/35-300SW-B 1119510082T
PBS 2 | PBS 3
Universal earthing device for ARS 00, 1, 2, 3
61
PBS ACCESSORIES
35-300 SW-B 1119510081T
M
PBS 2 | PBS 3
SWITCHGEAR
62
RBK pro
Fuse switch disconnectors
designed for distribution of electricity and protection of electrical equipment against short-circuits and overloads with industrial fuse links.
ENERGY SAFELY SWITCHED
63
64
SWITCHGEAR
64
APPLICATIONS RBK fuse switch disconnectors are designed for distribution of electricity and protection of electrical equipment against short-circuits and overloads with industrial fuse links. They are conforming to EN 60947-1, EN 60947-3, IEC 60947-1, IEC 60947-3 standards. They are intended for installation in low voltage distribution boards, cable and metering cabinets.
GENERAL INFORMATION
CONSTRUCTION thermoplastic parts of RBK fuse switch disconnectors are made of fibre glass strengthened polyamide with halogen free flame retardant added and have highest possible flammability class – V0, RBK fuse switch disconnectors consist of following parts: – three pole main base with spring-loaded contacts designed for connection of circular or sector-shaped conductors, conductors with lug terminals or bars, – removable cover with fuse links, arc chutes with steel deionization plates over top contacts, silver plated contacts providing low power loss.
MOUNTING on mounting plate – RBK 00 pro, RBK 1 pro, RBK 2 pro, RBK 3, on double DIN rail – RBK 00 pro, on to busbar systems: – 60 mm busbar system, – RBK 00 pro-S, RBK 1pro-S, RBK 2pro-S – installation on to bysbar system with hooked clamps, – 100 mm busbar system, – RBK 2-S, RBK 1 pro-S – installation on to bus bar system with hooked clamps.
FUNCTIONALITY: making and breaking operations should be done with determined movement, possible connection of circular or sector-shaped conductors with bare ends (V-terminals, 2V-terminals) or conductors with lug terminals (screw terminals), voltage test performed through test holes in fuse link cover, fuse links state monitoring.
ENERGY SAFELY SWITCHED
CONFORMITY WITH STANDARDS
65
EN 60947-1 EN 60947-3 HD 60269-2 Table 53. RBK FUSE SWITCH DISCONNECTORS TECHNICAL DATA Parameters
RBK 00 pro RBK 00 pro-S
RBK 00 pro-V 120
RBK 1 pro
RBK 1 pro-S
RBK 2 pro RBK 2 pro-S
RBK 3 RBK 3-S
A
160
160
250
250
400
630
Rated voltage Un
V
690
690
690
690
690
690
Utilization category
-
AC -23B
DC -21B
DC -22B
AC -23B
AC -22B
DC -22B
AC -23B
DC -22B
AC -23B
AC -22B
DC -22B2)
AC -23B
DC -21B
DC -22B
AC -22B
DC -21B
Rated switching current Ie
A
160
160
160
160
160
160
250
250
250
250
250
400
400
400
630
630
Rated switching voltage Ue
V
690
440
250
400
690
250
690
250
400
690
250
690
440
220
690
250
15
20
Rated short circuit making current
690 V
80
80
kA 400 V
20
100
100
690 V Rated short kA circuit withstand current 400 V
80
20 100
80 100
80
25 100
100
100
80
20
100
25 100
80 20
80
25
25
25
100
100
Rated insulation voltage Ui
V
1000
1000
1000
1000
1000
1000
Rated power dissipation
W
12
12
32
32
45
60
Rated impulse kV withstand voltage Uimp.
8
8
8
12
12
Rated frequency Mechanical durability Electrical durability
Hz 50-60
Size of fuse links
50-60
-
8
50-60
-
50-60
-
50-60
-
50-60
-
1600
1600
1600
1600
1000
1000
200
200
200
200
200
200
20
20
30
30
20
20
kg
~0,7 ~0,90
~0,9
~2
~2,5
~3 ~4,50
~5,00 ~5,90
-
00
00
1
1
2
3
Number of cycles
IP degree of protection IP Weight
-
8
Ith - thermal current of fuse switch disconnector without external enclosure, installed outdoors (In case of the installation of fuse switch disconnectors in enclosures then load factor should be considered) 2) for 60 mm busbar system 1)
RBK 2 switch disconnector with solid links 400 A rated short-time withstand current 1s Icw = 13 kA rated short-circuit making capacity Icm = 8 kA RBK 1000 - (RBK 3 switch disconnector with solid links 1000 A) rated short-time withstand current 1s Icw = 12,6 kA rated short-circuit making capacity Icm = 25,2 kA rated thermal current Ith = 1000 A when connected on to busbars 50 x 10 m utilization category AC21
TECHNICAL DATA
Rated thermal current Ith1)
SWITCHGEAR
66
RBK 00 pro (160 A, 690 V) Table 54. TECHNICAL DATA RBK 00 pro
Parameters A V V A
Rated thermal current Ith Rated voltage Un Utilization category Rated switching voltage Ue Rated switching current Ie Rated short circuit making current
RBK 00 pro
Rated short circuit withstand current
690 V 400 V 690 V 400 V
Rated insulation voltage Ui Rated impulse withstand voltage Uimp Rated power dissipation Rated frequency Mechanical durability Electrical durability IP degree of protection Size of fuse links
kA kA V kV W Hz
AC-23B 690 160 80 100 80 100
160 690 DC-22B 250 160
DC-21B 440 160 20 20
1000 8 12 50-60
Number of cycles
1600 200 IP 20 00
RBK 00 pro
Accesories on page 100
Table 55. VERSIONS RBK 00 pro/160 A
Cable terminal
Article No.
For installation on mounting plate RBK 00 pro
for connection of round conductors
S-bridge clamps
63-823256-011
RBK 00 pro-M
for connection of conductors with lug terminals
M8 screws
63-823256-021
RBK 00 pro-V
for connection of sector-shaped conductors
V-shape clamps
63-823256-031
RBK 00 pro-W
for connection of round conductors, lenghtened terminal shrouds
S-bridge clamps
63-823256-041
RBK 00 pro-M-W
for connection of conductors with lug terminals, lenghtened terminal shrouds
M8 screws
63-823256-051
RBK 00 pro-V-W
for connection of sector-shaped conductors, lenghtened terminal shrouds
V-shape clamps
63-823256-061
for mounting on double DIN rail RBK 00 pro-E-125mm
double DIN rail with spacing of 125 mm
S-bridge clamps/ M8 screws/ V-shape clamps
On request*
RBK 00 pro-E-150mm
double DIN rail with spacing of 150 mm
S-bridge clamps/ M8 screws/ V-shape clamps
On request*
ENERGY SAFELY SWITCHED
Table 56. RBK 00 pro TERMINAL CLAMPS Clamp
Drawing of clamp
Cross-section of conductors
S-bridge clamp 2 x M5 x 16
RBK 00 pro
Cu/Al conductor 4รท50 mm2
M8 x 16 screw
conductor with lug terminal up to 70 mm2
2) V-shape clamp 2 x M5 x 20
Tightening torque
Cu bar
4 mm2 - 70 mm2 4 mm2 - 95 mm2
Dimensions and spacing of holes for installation of RBK 00 on mounting plate
3 Nm* 70
5 maximum bar width 20 mm
R 7
Descrition
67
R
10 Nm*
66
3
3 Nm*
1) 1,5 mm2 - 2,5 mm2
RBK 00 pro
For stranded conductors using cable ferrules is recommended *using of tension wrench is recommended
RBK 00 pro-W
Fuse switch disconnector RBK 00 pro with additional terminal shrouds
Fuse switch disconnector RBK 00 pro for mounting on double DIN rail
SWITCHGEAR
68
FUSE SWITCH DISCONNECTORS FOR INSTALLATION ONTO 60 mm BUSBAR SYSTEM RBK 00 pro-S - system of protective covers provides touch protection - possible installation of distribution board’s protective panel at depth of 32 mm or 70 mm - built-in hooked clamps provide fast installation onto busbar system - top/bottom cable terminal Table 57. TECHNICAL DATA RBK 00 pro-S
RBK 00 pro-S
Parameter Rated thermal current Ith
A
160
Rated voltage Un
V
690
Utilization category
-
AC-23B
AC-22B
DC-22B
Rated switching voltage Ue
V
400
690
250
Rated switching current Ie
A
160
160
160
Rated short circuit making current
kA
100
Rated short circuit withstand current
kA
100
Rated insulation voltage Ui
V
1000
Rated impulse withstand voltage Uimp
kV
8
Rated power dissipation
W
Rated frequency
Hz
Mechanical durability
20
12 50-60
1600
Number of cycles
Electrical durability
20
200
IP degree of protection
IP 20
Size of fuse links
RBK 00 pro-S
00
Table 58. VERSIONS RBK 00 pro-S
Cable terminal
Article No.
For installation on to 60 mm busbar system RBK 00 pro-SG-M
cable terminal – bottom, for connection of conductors with lug terminals
M8 screws
63-823259-121
RBK 00 pro-SD-M
cable terminal – top, for connection of conductors with lug terminals
RBK 00 pro-SG-R
cable terminal-top, for connection of conductors with bare ends
M8 screws
63-823259-141
frame clamps
63-823259-151
RBK 00 pro-SD-R
cable terminal-bottom, for connection of conductors with bare ends
frame clamps
63-823259-161
Table 59. RBK 00 pro-S TERMINAL CLAMPS Descrition
Clamp
Drawing of clamp
Cross-section of conductors
Cu bar
Tightening torque
10 Nm*
RBK 00 pro-SGM RBK 00 pro-SDM
M8 x 16 screw
conductor with lug terminal up to 70 mm2
maximum bar width 20 mm
RBK 00 pro-SGR RBK 00 pro-SDR
frame clamps
4 ÷ 95 mm2
-
For stranded conductors using cable ferrules is recommended *using of tension wrench is recommended
6 Nm* 3 Nm*
ENERGY SAFELY SWITCHED
Fuse switch disconnectors RBK 00pro-S are designed for installation of distribution board’s protective panels at two depths: covering system at 70 mm depth covering system at 32 mm depth
69
distribution board’s protective panel installation depth
distribution board’s protective panel installation depth
70 mm 32 mm
with cables connected to the top cable terminal RBK 00 pro -SG
with cables connected to the bottom cable terminal RBK 00 pro- SD
Fuse switch disconnector RBK 00 pro-S has special cavity in it’s main base encasing busbar system’s support.
Cavity for busbar system’s support
RBK 00 pro-S
Fuse switch disconnectors RBK 00 pro-S are manufactured in two versions depending on type of cable terminal RBK 00 pro-SD-with bottom cable terminal RBK 00 pro-SG-with top cable terminal
SWITCHGEAR
RBK 00 pro-S
70
Cable terminals: M8 screw terminal (RBK 00 pro-SDM, RBK 00 pro-SGM)
Frame clamp (RBK 00 pro-SDR, RBK 00 pro-SGR)
It is possible to install microswitch indicating position in fuse switch disconnectors RBK 00 pro-S
hole for leading of wires connected to microswitch
ENERGY SAFELY SWITCHED
RBK 00 pro-V120 (160 A, 690 V)
71
Table 60. TECHNICAL DATA RBK 00 pro-V120
Parameters Rated thermal current Ith
A
160
Rated voltage Un
V
690
Utilization category
-
AC-23B
AC-22B
DC-22B
Rated switching voltage Ue
V
400
690
250
160
160
160
Rated switching current Ie
A
Rated short circuit making current
kA
100 100
Rated short circuit withstand current
kA
Rated insulation voltage Ui
V
20 20 1000
kV
8
W
12
Rated frequency
Hz
Mechanical durability
Number of cycles
Electrical durability IP degree of protection
50-60
1600 200
IP 20
Size of fuse links
00
RBK 00 pro-V120
Accesories on page 100
Table 61. VERSIONS RBK 00 pro-V120
Article No.
For installation on mounting plate RBK 00 pro-V120
for connection of conductors with bare ends (top terminals- S-bridge clamps, bottom terminals – V-clamps)
63-823341-011
RBK 00 pro-V120 - M
for connection of conductors with bare ends (top terminals- M8 screws, bottom terminals – V-clamps)
63-823341-021
RBK 00 pro-P
for connection of conductors with bare ends (top terminals- S-bridge clamps, bottom terminals – Prism clamps)
63-823341-031
RBK 00 pro-P-M
for connection of conductors with bare ends (top terminals- M8 screws, bottom terminals – Prism clamps)
63-823341-041
RBK 00 pro 2 x V120
for connection of conductors with bare ends (top terminals- S-bridge clamps, bottom terminals – double V-clamps)
63-823341-051
RBK 00 pro 2 x V120-M
for connection of conductors with bare ends (top terminals- M8 screws, bottom terminals – double V-clamps)
63-823341-061
RBK 00 pro-V120
Rated impulse withstand voltage Uimp Rated power dissipation
SWITCHGEAR
72
Table 62. RBK 00 pro TERMINAL CLAMPS Clamp
Picture of a clamp
Cross-section of conductors
Drawing of clamp
Cu/Al conductor 4÷50 mm2
Top terminals
S-bridge clamp 2 x M5 x 16
Tightening torque
3 Nm* maximum bar width 20 mm
M8 x 16 screw
V-clamp
conductor with lug terminal up to 70 mm2
**
10 Nm*
25 ÷ 120 mm2 20 Nm* 16 ÷ 95 mm
2
**
10 - 70 mm2 HM 10-120 Bottom terminals
RBK 00 pro-V120
Cu bar
15 Nm* 25 - 120 mm2 25 - 95 mm2 -
Double V-clamp
**
**
2 x ( 25 ÷ 120 mm2 ) 20 Nm* 2 x ( 16 ÷ 95 mm2 )
2 x ( 10 ÷ 70 mm2 ) Prism clamp
5,5 Nm* 2 x ( 10 ÷ 50 mm2 )
For stranded conductors using cable ferrules is recommended *using of tension wrench is recommended
ENERGY SAFELY SWITCHED
NEW FEATURES OF CABLE TERMINALS
73
connection of one or two sector-shaped conductors with cross-section up to 120 mm connection of two round conductors with bare ends and cross-section up to 70 mm2
2
SPACE SAVING possible reduction of external width of cable distribution cabinet to width of a fuse switch disconnector EFFICIENT CURRENT CIRCUIT no screw or riveted connection between contact and cable terminal (uniform design of current circuit ensures lower power loss and operating temperature) SAFETY fuse cover and cable terminal cover sealing extension of covering of conductors connected to cable terminals by installation of additional covers
Possible sealing of a fuse switch disconnector
Extension of covering of conductors connected to cable terminals by installation of additional covers
Possible connection of two sector-shaped conductors with cross-section up to 120 mm2 each with double V-clamp
Possible sealing of terminal cover
Description label
Possible connection of two round conductors with cross-section up to 70 mm2 with Prism clamp
RBK 00 pro-V120
Description label
SWITCHGEAR
74
EXTENDED COVERING OF CONDUCTORS CONNECTED TO CABLE TERMINAL For extension of covering of conductors connected to cable terminals, for example: to fully cover cables in cable distribution cabinet, any required number of additional covers could be installed (article number of additional extending cover: 51-930849-011) . Cover length - 50 mm.
RBK 00 pro-V120
Additional covers
RBK 00 pro-V120 with V-clamp for connection of sector-shaped conductors with cross-section up to 120 mm2
RBK 00 pro-V120 with double V-clamp for connection of two sector-shaped conductors with cross-section up to 120 mm2 each
ENERGY SAFELY SWITCHED
RBK 1 pro (250 A, 690 V)
75
Table 63. TECHNICAL DATA Parameters
RBK 1 pro
RBK 1 pro -S
Rated thermal current Ith=In
A
250
250
Rated voltage Un
V
690
690
Utilization category
-
AC-23B
DC-22B
AC-23B
AC-22B
DC-22B*
Rated switching voltage Ue
V
690
250
400
690
250*
A
250
250
Rated switching current Ie Rated short circuit making current
690 V
Rated short circuit withstand current
690 V
400 V 400 V
kA kA
80
25
100 80
25
100
250 80
25*
100 80
25*
100
Rated insulation voltage Ui
V
1000
1000
Rated impulse withstand voltage Uimp
kV
8
8
W
Rated frequency
Hz
Mechanical durability Electrical durability
32 50-60
Number of cycles
32 -
50-60
-
1600
1600
200
200
IP degree of protection
-
30
30
Size of fuse links
-
1
1
kg
~2
~2,5
Weight
RBK 1 pro for installation on mounting plate
Accesories on page 102 * for 60 mm busbar system
Table 64. VERSIONS RBK 1 pro/250 A For installation on mounting plate
Cable terminals
For connection of round conductors
Version
Article No..
S-bridge clamps
RBK 1 pro
63-811748-011
For connection of conductors with lug terminals
Screws
RBK 1 pro-M
63-811748-021
For connection of sector-shaped conductors
V-clamps
RBK 1 pro-V
63-811748-031
For connection of round conductors, top terminals V-terminals, bottom terminals - S-bridge terminals
V- clamps / S-bridge clamps
RBK 1 pro VG
63-811784-011
For connection of round conductors, top terminals V-terminals, bottom terminals - screw terminals
V- clamps /screws
RBK 1 pro VG-M
63-811784-021
For connection of round conductors, top terminals S-bridge terminals, bottom terminals - V-terminals
S-bridge clamps / V- clamps
RBK 1 pro VD
63-811784-031
For connection of round conductors, top terminals screw terminals, bottom terminals - V-terminals
screw terminals / V- clamps
RBK 1 pro VD-M
Cable terminals
Version
Article No..
63-811784-041
RBK 1 pro-S For installation on to busbar system 60 mm busbar system Top cable terminals, for connection of round conductors
S-bridge clamps
RBK 1 pro-SG 60
63-811750-011
Bottom cable terminals, for connection of round conductors
S-bridge clamps
RBK 1 pro-SD 60
63-811750-021
V- clamps
RBK 1 pro-SD-V 100
63-811750-121
Bottom cable terminals, for connection of conductors withlug terminals
Screws
RBK 1 pro-SD-M 60
63-811750-061
Top cable terminals, for connection of sector-shaped conductors
V- clamps
RBK 1 pro-SG-V 60
63-811750-091
Bottom cable terminals, for connection of sector-shaped conductors
V- clamps
RBK 1 pro-SD-V 60
63-811750-101
Bottom cable terminals, for connection of sector-shaped conductors
RBK 1 pro
Rated power dissipation
SWITCHGEAR
76
Table 64. VERSIONS RBK 1 pro-S For installation on to busbar system
Cable terminals
Version
Article No.
Top cable terminals, for connection of round conductors
S-bridge clamps
RBK 1 pro-SG 100
63-811750-031
Bottom cable terminals, for connection of round conductors
S-bridge clamps
RBK 1 pro-SD 100
63-811750-041
Screws
RBK 1 pro-SG-M 100
63-811750-071
100 mm busbar system
Top cable terminals, for connection of conductors with lug terminals Bottom cable terminals, for connection of conductorswith lug terminals
Screws
RBK 1 pro-SD-M 100
63-811750-081
Top cable terminals, for connection of sector-shaped conductors
V-clamps
RBK 1 pro-SG-V 100
63-811750-111
Bottom cable terminals, for connection of sector-shaped conductors
V-clamps
RBK 1 pro-SD-V 100
63-811750-121
Table 65. RBK 1 pro TERMINAL CLAMPS Description
RBK 1 pro
RBK 1 pro-M
RBK 1 pro-V
S-bridge clamp 2xM8x30
M10x25 screw
V-clamp HS 35-300-C
Picture of a clamp
Drawing of a clamp
Cross-section of conductors
conductor with lug terminal up to 120 mm2
Cu/Al conductor 35รท120 mm2
V-clamp for direct fixing of conductor with bare end with cross-section of: 35 - 185 mm2 35 - 240mm
2
maximum bar width 35 mm
Tightening torque
10 Nm*
20 Nm* 94
6 Dimensions and spacing of holes for installation of RBK 1 pro on mounting plate
For stranded conductors using cable ferrules is recommended *using of tension wrench is recommended
R 8
100
**
35 - 240 mm2 35 - 300 mm2
40 Nm*
50
Cu bar
11
RBK 1 pro
Clamp
ENERGY SAFELY SWITCHED
77
RBK 1 pro for installation on mounting plate, with additional terminal shrouds
RBK 1 pro-SG RBK 1 pro-SD for installation on to busbar system
RBK 1 pro VD-M for installation on mounting plate, picture of fuse switch disconnector without fuse links cover and terminal shrouds, top cable terminal - M screws, bottom cable terminal - V-clamps, (RBK 1 pro VG-M - bottom cable terminal - M screws, top cable terminal - V-clamps)
RBK 1 pro
RBK 1 pro for installation on mounting plate
SWITCHGEAR
78
RBK 2 pro (400 A, 690 V) Table 66. TECHNICAL DATA
RBK 2 pro
Parameters
RBK 2 pro
Rated thermal current Ith
A
400
Napięcie znamionowe Un
V
690
Utilization category
-
AC-23B
DC-21B
DC-22B
Rated switching voltage Ue
V
690
440
220
Rated switching current Ie
A
400
400
400
15
20
15
20
Rated short circuit making current
690 V
Rated short circuit withstand current
690 V
400 V 400 V
kA kA
80 100 80 100
Rated insulation voltage Ui
V
1000
Rated impulse withstand voltage Uimp
kV
12
Rated power dissipation
W
Rated frequency
Hz
Mechanical durability
45 50-60
Number of cycles
Electrical durability IP degree of protection
100 200
RBK 2-V pro for installation on mounting plate
IP20
Size of fuse links
2
Accessories on page 102
Table 67. VERSIONS RBK 2 pro/400 A
Cable terminal
Article No.
For installation on mounting plate RBK 2 pro
for connection of round condutors
S-bridge clamps
63-811685-051
RBK 2 pro-V
for connection of sector-shaped condutors
V-clamps
63-811685-071
RBK 2 pro-2V
for connection of sector-shaped conductors
double V- clamps
63-811685-081
RBK 2 pro-M
or connection of conductors with lug terminals
M10 screws
63-811685-061 63-811686-061
For installation on to 60 mm busbar system RBK 2 pro-M-SD 60
Bottom cable terminals, for connection of conductors with lug terminals
M10 screws
RBK 2 pro-M-SG 60
Top cable terminals, for connection of conductors with lug terminals
M10 screws
63-811686-051
RBK 2 pro-V-SD 60
Bottom cable terminals, for connection of sector-shaped conductors
V-clamps
63-811686-101
RBK 2 pro-V-SG 60
Top cable terminals, for connection of sector-shaped conductors
V-clamps
63-811686-091
RBK 2 pro-2V-SD 60
Bottom cable terminals, for connection of sector-shaped conductors
double V- clamps
63-811686-141
RBK 2 pro-2V-SG 60
Top cable terminals, for connection of sector-shaped conductors
double V- clamps
63-811686-131
For installation on to 100 mm busbar system RBK 2 pro-M-SD 100
Bottom cable terminals, for connection of conductors withlug terminals
M10 screws
63-811686-081
RBK 2 pro-M-SG 100
Top cable terminals, for connection of conductors with lug terminals
M10 screws
63-811686-071
RBK 2 pro-V-SD 100
Bottom cable terminals, for connection of sector-shaped conductors
V-clamps
63-811686-121
RBK 2 pro-V-SG 100
Top cable terminals, for connection of sector-shaped conductors
V-clamps
63-811686-111
RBK 2 pro-2V-SD 100
Bottom cable terminals, for connection of sector-shaped conductors
double V-clamps
63-811686-161
RBK 2 pro-2V-SG 100
Top cable terminals, for connection of sector-shaped conductors
double V-clamps
63-811686-151
ENERGY SAFELY SWITCHED
Table 68. RBK 2 pro TERMINAL CLAMPS
RBK 2 pro
Drawing of clamp
Cross-section of conductors
Cu bar
Dimensions and spacing of Tightening holes for installation of RBK 2 torque on mounting plate
S-bridge clamp 2 x M8 x 30
Cu/Al conductor 50á185 mm2
10 Nm*
M10 x 30 screw
conductor with lug terminal up to 240 mm2
20 Nm*
V- clamp 35-300SW-B
35 - 185 mm2
35 - 240 mm2
35 - 240 mm2
35- 300 mm2
V-clamp for direct fixing of conductor with bare end with crosssection: 35 - 185 mm2
35 - 240 mm2
35 - 240 mm2
35 - 300 mm2
maximum bar width 35 mm
R 30 Nm*
14 130
40 Nm*
For stranded conductors using cable ferrules is recommended *using of tension wrench is recommended
RBK 2 pro-V for installation on mounting plate, cable terminals: V-clamps
RBK 2 pro-2V RBK 2 pro-SG* for installation (top cable terminal: M10 screws) on mounting plate, RBK 2 pro-SD* cable terminals: double V-clamps (bottom cable terminal: M10 screws) for installation on to busbar systems
RBK 2 pro-2V-SG (top cable terminal: double V-clamp RBK 2 pro-2V-SD (bottom cable terminal: doubleV-clamp) for installation on to busbar systems
RBK 2 pro-V-SG (top cable terminal: V-clamp) RBK 2 pro-V-SD (bottom cable terminal: V-clamp) for installation on to busbar systems
RBK 2 pro
double V- clamp HS2/ 35-240-C
V-clamp for direct fixing of conductor with bare end with cross-section:
ø13 50
Clamp
9,5
Description
79
SWITCHGEAR
80
RBK 3 (630 A, 690 V) Table 69. TECHNICAL DATA RBK 3
Parametr Rated thermal current Ith=ln
A
630
Rated voltage Un
V
690
Utilization category
-
AC-22B
DC-21B
Rated switching voltage Ue
V
690
250
Rated switching current Ie
A
630
Rated short circuit making current
kA
Rated short circuit withstand current
kA
100
Rated insulation voltage Ui
V
1000
Rated impulse withstand voltage Uimp
kV
12
Rated power dissipation
W
60
Rated frequency
Hz
50-60
Number of cycles
1000
Mechanical durability Electrical durability IP degree of protection
RBK 3 for installation on mounting plate
200 IP 20
Size of fuse links
3
Accesories on page 102
Table 70. VERSIONS RBK 3/630 A
Cable terminal
Article No..
S-bridge clamps
63-811501-021
for connection of conductors with lug terminals
M12 screws
63-811501-041
for installation on to 60 mm busbar system, top/bottom cable terminal
M12 screws
63-811502-021
RBK 3
for connection of round conductors
RBK 3-M RBK 3-S
Table 71. RBK 3 TERMINAL CLAMPS Version
Clamp
Drawing of clamp
Cross-section of conductors
Cu bar
Tightening torque
Dimensions and spacing of holes for installation of RBK 3 on mounting plate 8,5
Cu/Al conductor 50รท185 mm2
RBK 3 M12 x 30 screw
conductor with lug terminal up to 240 mm2
For stranded conductors using cable ferrules is recommended *using of tension wrench is recommended
10 Nm* maximum bar width 35 mm
50
S-bridge clamp 2 x M8 x 35
9,5
RBK 3
630 25
R 20 Nm* 150
ENERGY SAFELY SWITCHED
RBK 4a (1250 A, 500 V; 1600 A, 400 V)
81
Table 72. TECHNICAL DATA RBK 4a
Parametr Rated thermal current Ith=ln
A
1250
1600
Utilization category
-
AC-22B
AC-21B
Rated switching voltage Ue
V
500
400
Rated switching current Ie
A
1250
Rated short circuit withstand current
kA
50 800
1600
Rated insulation voltage Ui
V
Rated impulse withstand voltage Uimp
kV
8
Rated frequency
Hz
50-60
Mechanical durability
c.p
600
Electrical durability
c.ł.
100
IP degree of protection
IP 20
Size of fuse links
4a
Table 73. VERSIONS RBK 4a
Weight
Cable terminal
Article No..
RBK 4a/1250/1
ONE POLE SWITCHING - each phase independently, for connection of conductors with lug terminals
4,2 kg
M12 screws
63-946868-001
RBK 4a/1250/3
THREE POLE SWITCHING - all phases simultaneously, for connection of conductors with lug terminals
13,0 kg
M12 screws
63-946868-002
RBK 4a/1600/1
ONE POLE SWITCHING - each phase independently, for connection of conductors with lug terminals
5,0 kg
M12 screws
63-946869-001
RBK 4a/1600/3
THREE POLE SWITCHING - all phases simultaneously, for connection of conductors with lug terminals
14,0 kg
M12 screws
63-946869-002
Tabela 74. RBK 4a TERMINAL CLAMPS Drawing of clamp
Cross-section of conductors
M12x40 screw
conductor with lug terminal up to 800 mm2
2xM16x50 screw
conductor with lug terminal up to 800 mm2
Cu bar
2 x 80 x 10
RBK 4a
*using of tension wrench is recommended
Tightening Dimensions and spacing of holes torque for installation of RBK 4a on mounting plate
ø14
Clamp
56 Nm*
30
Version
45 108
RBK 4a
RBK 4a for installation on mounting plate
SWITCHGEAR
82
ELECTRONIC FUSE MONITORING MODULE DESCRIPTION
electronic fuse monitoring module
L1, L2, L3 diodes are flashing - all three phases are supplied, all fuse links are operational. Relay contacts: [21..22] - closed; [13..14] - opened L1, L2, L3 diodes are blinking - all three phases are supplied, fuse links operated Relay contacts: [21..22] - opened; [13..14] - closed L1, L2, L3 diodes are off - two or more phases are not supplied or fuse links are removed. Relay contacts: [21..22] - opened; [13..14] - closed
PARAMETERS operating voltage AC - 400÷ 690 V, 40÷ 60 Hz; relay parameters 5A , 250 V~
CAUTION! For use only with fuse-links with non-isolated gripping lugs!
RBK 00-X with electronic fuse monitoring module
ELECTRONIC FUSE MONITORING MODULE VERSIONS ACCORDING TO POWER SUPPLY CONNECTION RBK 00-XT - for RBK 00 installed on mounting plate, with power supply connected to top cable terminals RBK 00-X - for RBK 00 installed on mounting plate, with power supply connected to bottom cable terminals RBK 00S-X - for RBK 00 installed on to 60 mm busbar system
The leds
5A
Fuse switch disconnector
250 V
AC
Electronic fuse monitoring module
disconnector contact position during normal operation Table 75. VERSIONS Versions with electronic fuse monitoring module, cable terminals - S-bridge clamps RBK 00 pro-XT
For installation on mounting plate, power supply connected to top cable terminals
63-823304-011
RBK 00 pro-X
For installation on mounting plate, power supply connected to top bottom terminals
63-823304-021
RBK 00 pro-SG -X
For installation on to 60 mm busbar system, top cable terminals
63-823345-011
RBK 00 pro-SD-X
For installation on to 60 mm busbar system, bottom cable terminals
63-823345-021
RBK 1 pro-XT
For installation on mounting plate, power supply connected to top cable terminals
63-811785-011
RBK 1 pro-X
For installation on mounting plate, power supply connected to top bottom terminals
63-811785-021
RBK 1 pro-SG 60-X
For installation on to 60 mm busbar system, top cable terminals
63-811787-011
RBK 1 pro-SD 60-X
For installation on to 60 mm busbar system, bottom cable terminals
63-811787-021
RBK 1 pro-SG 100-X
For installation on to 100 mm busbar system, top cable terminals
63-811787-031
RBK 1 pro-SD 100-X
For installation on to 100 mm busbar system, bottom cable terminals
63-811787-041
RBK 2 pro-XT
For installation on mounting plate, power supply connected to top cable terminals
63-811786-011
RBK 2 pro-X
For installation on mounting plate, power supply connected to top bottom terminals
63-811786-021
RBK 2 pro-SG 60-X
For installation on to 60 mm busbar system, top cable terminals
63-811788-011
RBK 2 pro-SD 60-X
For installation on to 60 mm busbar system, bottom cable terminals
63-811788-021
RBK 2 pro-SG 100-X
For installation on to 100 mm busbar system, top cable terminals
63-811788-031
RBK 2 pro-SD 100-X
For installation on to 100 mm busbar system, bottom cable terminals
63-811788-041
ENERGY SAFELY SWITCHED
NOTES
83
NOTES
SWITCHGEAR
RBK
Fuse switch disconnectors
intended for distribution of electricity and protection of electrical equipment against short-circuits and overloads, with industrial fuse links
ENERGY SAFELY SWITCHED
86
SWITCHGEAR
86
APPLICATIONS RBK fuse switch disconnectors are designed for distribution of electricity and protection of electrical equipment against short-circuits and overloads with industrial fuse links. They are conforming to PN-EN 60947-1, PN-EN 60947-3, IEC 60947-1, IEC 60947-3 standards. They are intended for installation in low voltage distribution boards , cable and metering cabinets.
GENERAL INFORMATION
CONSTRUCTION thermoplastic parts of RBK fuse switch disconnectors are made of fibre glass strengthened polyamide with halogen free flame retardant added and flammability class V2 RBK fuse switch disconnectors consist of following parts: – three pole main base with spring-loaded contacts designed for connection of circular or sector-shaped conductors, conductors with lug terminals or bars – removable cover with fuse links arc chutes with steel deionization plates over top contacts silver plated contacts providing low power loss
MOUNTING on mounting plate – RBK 000, RBK 00, RBK 1 on to busbar systems – 60 mm busbar system – RBK 000-S – installation on to busbar system with hooked clamps
FUNCTIONALITY: making and breaking operations should be done with determined movement possible connection of circular or sector-shaped conductors with bare ends (V-terminals, 2V-terminals) or conductors with lug terminals (screw terminals) voltage test is performed through test holes in fuse link cover
ENERGY SAFELY SWITCHED
CONFORMITY WITH STANDARDS
87
EN 60947-1 EN 60947-3 HD 60269-2 Table 76. RBK FUSE SWITCH DISCONNECTORS TECHNICAL DATA
Parameters
RBK 000 RBK 000-S
RBK 00
RBK 1
A
160
160
250
Rated voltage Un
V
690
690
690
Utilization category
-
AC-23B
AC-22B
AC-22B
AC-21B
DC-21B
AC-22B
AC-22B
Rated switching current Ie
A
100
100
160
160
160
160
250
Rated switching voltage Ue
V
400
690
400
690
250
690
690
80
80
100
100
Rated short circuit making current
690 V
Rated short circuit withstand current
690 V
400 V 400 V
kA kA
100
15
25
15
80
80
100
100
Rated insulation voltage Ui
V
1000
1000
1000
Rated power dissipation
W
12
12
32
Rated impulse withstand voltage Uimp.
kV
8
8
8
Rated frequency
Hz
50-60
50-60
Mechanical durability
50-60
-
Number of cycles
2000
1600
1600
300
200
200
IP degree of protection
IP
20
20
303)
Weight
kg
~0,6 ~0,9
~0,65
~2
-
000
00
1
Electrical durability
size of fuse links PN/IEC 1)
Ith - thermal current of fuse switch disconnector without external enclosure, installed outdoors (In case of the installation of fuse switch disconnectors in enclosures then load factor should be considered)
TECHNICAL DATA
Rated thermal current Ith1)
SWITCHGEAR
88
RBK 000 (160 A, 690 V) Table 77. TECHNICAL DATA RBK 000
RBK 000
Parameters Rated thermal current Ith=ln
A
Rated voltage Un
V
Utilization category
-
160 690 AC-23B
AC-22B
AC-22B
AC-21B
DC-21B
Rated switching voltage Ue
V
400
690
400
690
250
Rated switching current Ie
A
100
100
160
160
160
Rated short circuit making current
kA
25
Rated short circuit withstand current
kA
100
Rated insulation voltage Ui
V
1000
Rated impulse withstand voltage Uimp
kV
8
Rated power dissipation
W
12
Rated frequency
Hz
Mechanical durability
50-60
Number of cycles
Electrical durability
2000
RBK 000 for installation on mounting plate
300
IP degree of protection
IP 20
Size of fuse links
000
Accesories on page 102
Table 78. VERSIONS RBK 000/160 A
Cable terminal
Article No.
For installation on mounting plate RBK 000
for connection of round conductors
S-bridge clamps
63-823191-011
RBK 000-E
for connection of round conductors, possible installation on DIN rail
S-bridge clamps
63-823191-051
RBK 000-M
for connection of round conductors with lug terminals
M8 screws
63-823191-021
RBK 000-M-E
for connection of round conductors with lug terminals, possible installation on DIN rail
M8 screws
63-823191-061
RBK 000-W
for connection of round conductors,lenghtened terminal shrouds
S-bridge clamps
63-823191-071
RBK 000-W-M
for connection of round conductors with lug terminals, lenghtened terminal shrouds
M8 screws
63-823191-081
Cable terminal – bottom, for connection of round conductors
S-bridge clamps
63-823234-031
For installation on to 60 mm busbar system RBK 000-SD RBK 000-SG
Cable terminal – top, for connection of round conductors
S-bridge clamps
63-823234-011
RBK 000-SD-M
Cable terminal – bottom, for connection of conductors with lug terminals
M8 screws
63-823234-041
RBK 000-SG-M
Cable terminal – top, for connection of conductors with lug terminals
M8 screws
63-823234-021
ENERGY SAFELY SWITCHED
Table 79. RBK 000 TERMINAL CLAMPS Drawing of clamp
Cross-section of conductors
S-bridge clamp 2 x M5 x 16
Cu/Al conductor 1,5 รท 35 mm2
M8 x 16 screw
conductor with lug terminal up to 70 mm2
RBK 000
Tightening torque
Cu bar
3 Nm* maximum bar width 15 mm 10 Nm*
Dimensions and spacing of holes for installation of RBK 000 on mounting plate
5
Clamp
ร 6 ,
Description
89
50
For stranded conductors using cable ferrules is recommended *using of tension wrench is recommended
RBK 000
RBK 000-E for mounting on DIN rail
RBK 000-O for installation on mounting plate with additional terminal shrouds
RBK 000-W for installation on mounting plate with extended terminal shrouds
RBK 000-SG (top cable terminals) RBK 000-SD (bottom cable terminals) for installation on to 60 mm busbar system
SWITCHGEAR
90
RBK 00 (160 A, 690 V) Table 80. TECHNICAL DATA RBK 00
Parameters Rated thermal current Ith=ln
A
160
Rated voltage Un
V
690
Utilization category
-
AC-22B
Rated switching voltage Ue
V
690
A
160
Rated short circuit making current
690 V
Rated short circuit withstand current
690 V
80
kA
400 V
100 80
kA
400 V
100
Rated insulation voltage Ui
V
Rated impulse withstand voltage Uimp
kV
8
Rated power dissipation
W
12
Rated frequency
Hz
50-60
Mechanical durability
1000
Number of cycles
Electrical durability IP degree of protection
1600
RBK 00 for installation on mounting plate
200 IP 20
Size of fuse links
00
Accesories on page 103
Table 81. VERSIONS RBK 00/160 A RBK 00
for connection of round conductors
Cable terminal
Article No.
S-bridge clamps
63-823333-011
RBK 00-M
for connection of conductors with lug terminals
M8 screws
63-823333-021
RBK 00-V
for connection of sectorshaped conductors
V-shape clamps
63-823333-031
S-bridge clamps
63-823333-041
M8 screws
63-823333-051
V-shape clamps
63-823333-061
RBK 00-W
for connection of round conductors ,lenghtened terminal shrouds
RBK 00-M-W
for connection of conductors with lug terminals, lenghtened terminal shrouds
RBK 00-V-W
for connection of sectorshaped conductors, lenghtened terminal shrouds
Table 82. RBK 00 TERMINAL CLAMPS Description
RBK 00
Clamp
Drawing of clamp
Cross-section of conductors
S-bridge clamp 2 x M5 x 16
Cu/Al conductor 4 รท 50 mm2
M8 x 16 screw
conductor with lug terminal up to 70 mm2
V-shape clamp 2 x M5 x 20
2)
4 mm2 - 70 mm2 4 mm2 - 95 mm2
1) 1,5 mm2 - 2,5 mm2
For stranded conductors using cable ferrules is recommended *using of tension wrench is recommended
Cu bar
Tightening torque
Dimensions and spacing of holes for installation of RBK 00 on mounting plate
3 Nm*
maximum bar width 20 mm
70
5
R 7
RBK 00
Rated switching current Ie
R
10 Nm*
66 3 Nm*
3
ENERGY SAFELY SWITCHED
RBK 1 (250 A, 690 V)
91
Table 83. TECHNICAL DATA Parameters
RBK 1
Rated thermal current Ith=ln
A
Rated voltage Un
V
690
Utilization category
-
AC-22B
Rated switching voltage Ue
V
690
A
250
Rated switching current Ie Rated short circuit making current
690 V
Rated short circuit withstand current
690 V
kA
400 V
kA
400 V
250
80 100 80 100
Rated insulation voltage Ui
V
Rated impulse withstand voltage Uimp
kV
8
Rated power dissipation
W
32
Rated frequency
Hz
50-60
Electrical durability
1600
Number of cycles
200
IP degree of protection
-
Size of fuse links
-
1
kg
~2
Weight
30
RBK 1 for installation on mounting plate
Accesories on page 104
Table 84. VERSIONS RBK 1/250 A For installation on mounting plate
Cable terminals
Version
Article No.
For connection of round conductors
S-bridge clamps
RBK 1
63-811779-011
For connection of conductors with lug terminals
Screws
RBK 1-M
63-811779-021
V-clamps
RBK 1-V
63-811779-031
For connection of round conductors, top terminals -V-terminals, bottom terminals - S-bridge terminals
V-clamps / S-bridge clamps
RBK 1 VG
63-811784-051
For connection of round conductors, top terminals -V-terminals, bottom terminals - screw terminals
V- clamps / screws
RBK 1 VG-M
63-811784-061
For connection of round conductors, top terminals -S-bridge terminals, bottom terminals - V-terminals
S-bridge clamps / V-clamps
RBK 1 VD
63-811784-071
For connection of round conductors, top terminals-screw terminals, bottom terminals - V-terminals
screw terminals / V-clamps
RBK 1 VD-M
63-811784-081
For connection of sector-shaped conductors
RBK 1
Mechanical durability
1000
SWITCHGEAR
92
Table 85. RBK 1 TERMINAL CLAMPS Description Clamp
RBK 1
RBK 1-M
RBK 1-V
S-bridge clamp 2 x M8 x 30
M10x25 screw
V-clamp HS 35-300-C
Cu/Al conductor 35 รท 120 mm2
conductor with lug terminal up to 120 mm2
V-clamp for direct fixing of conductor with bare end with cross-section of:
Picture of a clamp
Drawing of a clamp
35 - 185 mm2
maximum bar width 35 mm
Cu bar 10 Nm*
20 Nm*
Dimensions and spacing of holes for installation of RBK 1 pro on mounting plate
30 Nm*
94
6 11
RBK 1
Tightening torque
35 - 240 mm2 ** 35 - 240 mm2 35 - 300 mm2
R 8
100
50
Cross-section of conductors
For stranded conductors using cable ferrules is recommended *using of tension wrench is recommended
RBK 1 for installation on mounting plate
RBK 1 for installation on mounting plate, with additional terminal shrouds
RBK 1 VD-M for installation on mounting plate, picture of fuse switch disconnector without fuse links cover and terminal shrouds, top cable terminal - M screws, bottom cable terminal - V-clamps, ( RBK 1 VG-M - bottom cable terminal M screws, top cable terminal - V-clamps)
ENERGY SAFELY SWITCHED
RBK 000 RBK 000-E
93 91,5 23,3 70
째
181
sealing point
205,5 159 111,5
DIN rail
25
50
25
217
5
RBK 000-O
25
207
91,5
RBK 000-W
3
194 190
91,5
47
RBK DIMENSIONS
89
SWITCHGEAR
94
RBK 000-SG - top cable terminal RBK 000-SD - bottom cable terminal
112 70 70
60 58
215
191
min. 12 mm max. 30 mm
60
째
89
242
RBK 00 / RBK 00 pro 81 18,3 2
sealing point
7,5
2
207 157 106,5*
182
*122.5 mm for M screw terminal (for busbar and lug terminal)
33
33 106
42 45
212
RBK 00-W / RBK 00 pro-W, 81 18,3
sealing point
207 106,5*
*122.5 mm for M screw terminal (for busbar and lug terminal) 7,5 198 184
RBK DIMENSIONS
busbar thickness 3-10 mm
25
25
33
106
33
42 45
212
ENERGY SAFELY SWITCHED
33,5
109,5 32 26
8
95
70 M8
5
RBK 00 pro-S
sealing point 70
194
206
214
60
°
5-10
12-30
60
7,5
3 33
19,5
33
241
RBK 1, RBK 1 pro 111 27
4
70
°
292 243 240 176*
269
Ø7,5
57
41 65
57 180
3
309 *197 mm for M type clamp
RBK 1 pro-V 111 4
70
°
292 243 240
269
Ø7,5
57
180
57
41 65
3 309
RBK DIMENSIONS
106
SWITCHGEAR
96
RBK 1 pro-SD, RBK 1 pro-SG
165 140 94 4
70
°
B
A
C
292 243
A
Ø7,5
57 180
A
B
C
60 mm
66 mm
max 30 mm
100 mm 27-66 mm M,S,V types of clamps
70 339 Thickness of the bus bar from 3 to 10 mm
max 60 mm
RBK 1 pro-O
111
70
°
Ø7,5
314 310
RBK DIMENSIONS
57
57
180
57
41 65
3
309
ENERGY SAFELY SWITCHED
RBK 00 pro-V 120
97
93 30,3
2
54 sealing point
o
225 33
16,5 54
224,5 *197 mm for M screw terminal (for busbar and lug terminal)
70 66
5
R
3
12,5 25
7
120,5
R
4,5
R 2
106
6,5
33
3,5
sealing point
33
spacing of holes for installation of RBK 00 pro-V120 on mounting plate
RBK DIMENSIONS
184*
252
,5 Ă˜7
70
SWITCHGEAR
98
RBK 2 pro
130 80 31 sealing point
70
°
65
260 216
266
319
298
Ø7,5
65 341
RBK 2 pro-V 130 sealing point
321
325
Ø7,5
208
RBK 2 pro-2V
170 120 70
sealing point
°
208
300
319
Ø7,5 315
RBK DIMENSIONS
208
381
ENERGY SAFELY SWITCHED
RBK 2 pro-SG / RBK 2 pro-SD
154
99
* cable terminal: screw terminal M, S-bridge clamp
70
°
sealing point
65
260
319 266
298
Ø7,5
208
RBK DIMENSIONS
busbar thickness 5-10 mm 109 366
65
154
RBK 2 pro-V-SG / RBK 2 pro-V-SD top cable terminal
70
°
sealing point
319 321 266 260
298
Ø7,5
65
bottom cable terminal
65
busbar thickness 5-10 mm
208
RBK 2 pro-2V-SG / RBK 2 pro-2V-SD
109 366 194
top cable terminal 70
sealing point
°
busbar thickness 5-10 mm
65
65
300
319
315
Ø7,5
208 A
B
C
60 mm
75 mm
maks. 30 mm
100 mm
35-67 mm
maks. 60 mm
bottom cable terminal 149 406
SWITCHGEAR
100
RBK 3
140 31-33
70
80
212
86,5
80
371
250
RBK 3-S
60 mm busbar system adapter - fixed to the fuse switch disconnector main base with M6x10 screws
60 60
308
155 102 17
fixing point
M6x10
94
154
RBK DIMENSIONS
48
154
337
308
째
80
80
80
80
250
RBK 00-X
RBK 1-X
RBK 2-X
113
138
156
ENERGY SAFELY SWITCHED
Terminal adapters:
101
RBK 00
RBK 1
140 32 37
15 7
8
140 37
32
84
15 7 R3
85
102
85
102
R3
25
48
58
20
ø9
33
18,3
ø11
RBK 2
27
57
57 196 214
212 197
RBK 4a
15
84
8
20
85
102
R3
213
7
350
140 37
10
168
50
69
196 214
69
17,5
153 156
RBK 4a 1250
RBK 4a 1600 26
60
30
30
ø14
ø14
26
ø13,5
17
60
45
108
108 324
45
108
108 324
RBK DIMENSIONS
33 196 214
32
84
8
SWITCHGEAR
RBK 000 -ACCESSORIES
102
Table 86. RBK 000 - ACCESSORIES Description
Size
Article No.
Feeding bridge 2 x RBK 000, 35 mm2
000
1119510055T
Feeding bridge 3 x RBK 000, 35 mm2
000
1119510056T
Feeding bridge 4 x RBK 000, 35 mm2
000
1119510057T
Feeding bridge 5 x RBK 000, 35 mm2
000
1119510058T
Feeding bridge 2 x RBK 000, 50 mm2
000
1119510059T
Feeding bridge 3 x RBK 000, 50 mm2
000
1119510060T
Feeding bridge 4 x RBK 000, 50 mm2
000
1119510061T
Feeding bridge 5 x RBK 000, 50 mm2
000
1119510062T
000
1119510071T
Auxiliary contacts (microswitch) AC-15 Ue 230 V~ Ie 2,5 A DC-13 Ue 230 V~ Ie 0,3 A
000
1115296311T
Additional terminal shroud „O” extends shroud length of 25 mm
000
51-930160-011
Feeding bridge RBK 000 25-95 mm2 (1 set - 3 pcs.) for connection of conductor of cross-section 25 - 70 mm2
25 - 95 mm2
Picture
ENERGY SAFELY SWITCHED
Table 87. RBK 00 - ACCESSORIES Description
103 Article No.
Feeding bridge 2 x RBK 00, 35 mm2
00
1119510063T
Feeding bridge 3 x RBK 00, 35 mm2
00
1119510064T
Feeding bridge 4 x RBK 00, 35 mm2
00
1119510065T
Feeding bridge 5 x RBK 00, 35 mm2
00
1119510066T
Feeding bridge 2 x RBK 00, 50 mm2
00
1119510067T
Feeding bridge 3 x RBK 00, 50 mm2
00
1119510068T
Feeding bridge 4 x RBK 00, 50 mm2
00
1119510069T
Feeding bridge 5 x RBK 00, 50 mm2
00
1119510070T
00
1119510072T
Clamp for RBK 00 2x25 mm2 1x16 mm2
00
1119510073T
Clamp for RBK 00 4x10 mm2
00
1119510074T
Feeding bridge clampRBK 00 25-95 mm2 (1 set - 3 pcs.) for connection of conductor of cross-section 25 - 70 mm2
25 - 95 mm2
Picture
RBK 00 - ACCESSORIES
Size
SWITCHGEAR
ACCESSORIES RBK
104
Description
Size/Version
Article No.
Auxiliary contacts (microswitch) AC-15 Ue 230 V~ Ie 2,5 A DC-13 Ue 230 V~ Ie 0,3 A
00
1115296311T
Additional terminal shroud „O” extends shroud length of 25 mm
00
51-930499-011
Full cover (matt)
00
1361399021T
RBK 00
1119510048T
RBK 00 W
1119510043T
Picture
Terminal adapter + 3 x V-clamp + terminal shroud
Table 88. RBK 1, RBK 2, RBK 3 - ACCESSORIES Description
Version
Article No.
RBK 1 RBK 1 pro RBK 2
1115296316
RBK 3
1115296037
Additional terminal shroud „O” extends shroud length of 35 mm
RBK 1 pro-O
51-823278-011
Additional terminal shroud „O” extends shroud length of 60 mm
RBK 2-O
51-822405-011
Terminal adapter RBK 1 + 3 x V-clamp + terminal shroud
RBK 1
1119510046T
Terminal adapter RBK 2 + 3 x V-clamp + terminal shroud
RBK 2
1119510047T
Auxiliary contacts (microswitch) AC-15 Ue 230 V~ Ie = 2,5 A DC-13 Ue 230 V~ Ie = 0,3 A Auxiliary contacts (microswitch) AC-15 Ue 110/230/400 V~ Ie = 1 A DC-13 Ue 48/110/220 V~ Ie = 0,5 A
screw terminals conductors cross-section: – solid – 1 x 0,5 = 1,0 mm2 – stranded – 1 x 0,5 = 0,75 mm2
Picture
ENERGY SAFELY SWITCHED
Table 89. RBK 00, RBK 000 FEEDING BRIDGES TECHNICAL DATA
105 Cu busbar Insulating parts, pressed PC/ABS RAL7035
Materials
Cover, injection molded PC/ABS RAL7035 Shroud, injection molded PC/ABS RAL7035 >80 째C UL94V0
Temperature range
pressed PC/ABS 960 째C / 3.2 mm
Glow wire flammability index
850 째C / 1 mm injection molded PC/ABS 960 째C / 1 mm Overvoltage category III/Pollution degree rating II
Insulation properties
pressed PC/ABS 600 V
TECHNICAL DATA
CTI
injection molded PC/ABS 250 V 25 kA/0.1 s
Short-circuit strength
>32 kV / mm
Dielectric strength
>6.5 kV / >8.5 kV
Rated impulse withstand voltage 35 mm / 50 mm 2
2
>6 mm / >8 mm
Minimal insulating distance in air 35 mm / 50 mm 2
2
>8.5 mm / >9 mm
Minimal creepage distance 35 mm2/ 50 mm2
690 V
Rated switching voltage
Feeding bridge length Cross-section
Max. 1000 mm
Max. 300 mm
Max. 1000 mm
Max. 300 mm
35 mm2
35 mm2
50 mm2
50 mm2
160 A
250 A
Power supply connection point at the end or at the beginning of feeding bridge Maximum Is current / phase Feeding conductors crosssection
125 A 35 mm
200 A 2
70 mm
50 mm
95 mm2
250 A
160 A
250 A
2
2
Other points of connection of power supply to the feeding bridge Maximum feeding current Ie Feeding conductors crosssection
160 A 70 mm
95 mm
2
Sn
Is
70 mm
2
S3
95 mm2
2
S2
S1
S1
S2
Is
Is
Ie =Is Other points of connection of power supply to the feeding bridge Power supply connection point at the end or at the beginning of bridge
In case of connection of power supply in the middle of feeding bridge sum of output currents S1,..., Sn cannot be greater than corresponding maximum current Is .
S3
Ie=sum of Is
Sn
SWITCHGEAR
APPLICATION EXAMPLES
Fuse switch disconnectors RBK 00 connected with feeding bridge , power supply cables connected to feeding bridge clamps
APPLICATION EXAMPLES
106
Article No. 1119510070T
Article No. 1119510072T
Article No. 1119510065T
Article No. 1119510072T
Article No. 1119510064T Article No. 1119510072T
Article No. 1119510063T
Article No. 1119510072T
ENERGY SAFELY SWITCHED
107
Article No. 1119510048T Article No. 1119510073T
35 - 95 mm2
35 - 120 mm2
50 - 185 mm
50 - 240 mm2
2
Article No. 51-930499-011
Article No. 1119510073T conductor up to 16 mm2
Article No. 51-930499-011
conductor up to 25 mm2
RBK 00-W with terminal clamp 1x16 mm2, 2x25 mm2 (view of fuse swith disconnector without fuse-link cover)
RBK 00-O for installation on mounting plate, version with additional terminal shrouds „O”
Article No. 51-930160-011
Article No. 51-823278-011
Article No. 51-930160-011
Article No. 51-823278-011
RBK 000-O for installation on mounting plate, version with additional terminal shrouds „O”
RBK 1-O for installation on mounting plate, version with additional terminal shrouds „O”
APPLICATION EXAMPLES
RBK 00-W with terminal adapter for connection of sector- RBK 00-W with terminal clamp 1x16 mm2, 2x25 mm2 shaped conductors with cross-section up to 240 mm2 (view of fuse swith disconnector without fuse-link cover and terminal shrouds)
SWITCHGEAR
108
FULL COVER FOR RBK 00
135 117 109
sealing point
Ø7
ADDITIONAL ACCESSORIES
190 240 258
full cover
sealing point
Ø12
TERMINAL ADAPTER FOR RBK 00 / RBK 1
35-240SE 30Nm
35-240SE 30Nm
100
75
35-240SE 30Nm
CONFORMING TO STANDARDS:
220
1. PN-EN 60947-7-1: 2010 2. EN 60947-7-1: 2009
ENERGY SAFELY SWITCHED
109
COVERING OF RBK FUSE SWITCH DISCONNECTORS (REAR INSTALLATION)
front cover
TABLE 90. FRONT COVER DIMENSIONS Typ
D B
hole in front cover for RBK fuse switch disconnector
B
C
D
104
166
94
156
RBK 000-S, RBK 000-W
104
205
94
195
RBK 00, RBK 00 pro, RBK 00 pro-S
120
207
110
197
RBK 00-W
120
207
110
182
RBK 1, RBK 1-S
198
262
186
250
RBK 2, RBK 2-S
230
285
209
255
RBK 2-V, RBK 2-2V
230
340
209
255
RBK 3, RBK 3-S
272
328
258
316
ELECTRICAL DIAGRAMS (RBK 1-S, RBK 3-S - POSSIBLE BOTTOM CABLE TERMINAL CONNECTION)
RBK 000 RBK 00 RBK 00 pro RBK 1 RBK 2 RBK 3
RBK 000-SG RBK 00 proSG RBK 1 pro-SG RBK 2-SG
RBK 3-S
RBK 000-SD RBK 00 pro-SD RBK 1 pro-SD RBK 2-SD RBK 3-S
ADDITIONAL ACCESSORIES
C A
A
RBK 000
SWITCHGEAR
110
UNIVERSAL EARTHING DEVICE FOR RBK 000, 00, 1, 2, 3
ACCESSORIES RBK
Catalogue Nr 1119510032T
DESCRIPTION 1. 2. 3. 4. 5. 6. 7.
short-circuiting links working pole earth terminal short-circuiting cable earthing cable cable connection point case
EXAMPLE OF THE ORDER OF RBK 2 - V - SD - 100
160 A Fuse switch disconnector
Terminal clamps
For installation on to busbar system Cable terminal Busbar system
RBK 000, RBK 00, RBK 00 pro
250 A
RBK 1
400 A
RBK 2
630 A
RBK 3
V
Typ V
2V
Typ 2V
M
screw terminal
S
S-bridge clamps
S
RBK 2 V
S
D
bottom
G
top
60 mm
60
100 mm
100
D
100