DATASHEET
ET 8E8A
1
Remote Input-/Output Unit ET 8E8A This module enables the management of remote inputs and outputs in complex systems far from the central. Data is transmitted fully digital via 2-wire lines to the central. Managing of 8 inputs with 5 steps and 8 outputs, thereof 4 make- and 4 change-over contacts. Status-LEDs
for all inputs and outputs show the function at a glance, additionally the line from the ET 8E8A to the central is continuously monitored. Mounting is possible in a 19“ rack on a DIN rail or with the supplied mounting rail for wall mounting.
1. ET 8E8A Remote input- / output unit with 8 inputs (5 steps) and 8 outputs (4 make and 4 change over contacts).
Commend, Inc. · 63 Ramapo Valley Road, Suite 201 · Mahwah, New Jersey 07430 · Tel. (201) 529-2425 · Fax (201) 529-0008 · office@commendusa.com · www.commendusa.com Datasheet Version 1.1/1207 | Errors and omissions excepted | Products may change in the interest of technical improvements without notice.
www.commend.com
P1|3
DATASHEET
ET 8E8A
Technical Data – Benefits TECHNICAL DATA Inputs:
BENEFITS 8 inputs for floating contacts
Outputs:
8 relay outputs 30 V/3 A
Status indication:
Status-LEDs for all inputs and outputs
Operating temperature range:
–20° C bis +60° C (-4° F to 140° F)
Storage temperature range:
–20° C to +60° C (-4° F to 140° F)
Relative humidity:
• Star feed cabling via 2-wires to central • Fully digital transmission of data to the central • Can be connected to every 2-wire subscriber • 8 inputs with 5 steps • 8 outputs with 4 make contacts and 4 change-over contacts
up to 95 %
Plug:
plugable screw terminals
Cabling:
star feed, 2-wire, twisted
Power supply: from central option: external, floating supply for greater line length (8–24 VAC or 10–35 VDC, 500 mA) Measurements:
• Ideal for remote inputs and outputs
105 x 105 x 62 mm (4.14 x 4.14 x 2.44 inch) (incl. mounting rail)
Weight incl. package:
• Status–LEDs for all outputs • Status–LEDs for all inputs • Rack mounting on DIN rail • Wall mounting with included mounting rail • Line fault monitoring from ET 8E8A to central
350 g (0.8 lbs)
EXTENT OF SUPPLY 1 Input-/Output unit including: • Mounting rail, screws and dowels for wall mounting • Short reference
SYSTEM REQUIREMENTS • GE 200 with G2-GED-4 or GE 700 with G7-GED-4 • Central software min. Pro 05.0
• Screw terminals for use with cables up to 1.5 mm² (16 AWG)
LINE LENGTH ET8E8A – SUBSCRIBER CARD Cable type: AWG:
ø 0.5 mm 24
ø 0.6 mm 22
ø 0.8 mm 20
F-YAY (Installation cable PVC, 100 nF/km, 30.5 nF/1,000 ft)
750 m (2,460 ft)
1,000 m (3,281 ft))
2,000 m (6,562 ft)
F-YAY with external Supply
2,000 m (6,562 ft)
2,000 m (6,562 ft)
2,000 m (6,562 ft)
J-02YS(St)Y (Cat. 5 cable, foamed polyethylene, 45 nF/km, 13.7 nF/1,000 ft)
750 m (2,460ft) (1,000 m / 3,281 ft with max. 4 relays),
1,000 m (3,281 ft)
2,000 m (6,562 ft)
J-02YS(St)Y with external Supply
3,000 m (9,843 ft)
3,000 m (9,843 ft)
3,000 m (9,843 ft)
Commend, Inc. · 63 Ramapo Valley Road, Suite 201 · Mahwah, New Jersey 07430 · Tel. (201) 529-2425 · Fax (201) 529-0008 · office@commendusa.com · www.commendusa.com Datasheet Version 1.1/1207 | Errors and omissions excepted | Products may change in the interest of technical improvements without notice.
www.commend.com
P2|3
DATASHEET
ET 8E8A
Installation CONNECTION DIAGRAM
PRECAUTIONS • ESD precautions must be observed.
A B
Optional: external, floating supply for greater line length Plug in transformer 8-24 V AC or 10-35 V DC (500 mA)
• The station may only be installed by authorised service engineers.
Subscriber central
IN1 GND IN2 GND IN3 GND IN4 GND IN5 GND IN6 GND IN7 GND IN8 GND PWR1 PWR2
MOUNTING INSTRUCTIONS • Do not expose the station to extreme temperature (under –20° C/-4° F or above +60° C/140° F).
A B
Inputs 1 to 8
• Each card G2-GED-4 or G7-GED-4 can handle one ET 8E8A, that corresponds to 8 x ET 8E8A in a GE 200 or 12 x ET 8E8A in a GE 700.
MEASUREMENTS
e.g.: door opener
S8
S7
S6
S5
S4
S3
S1
105 (4.14)
S2
Bottom view with mounting rail for wall mounting. Measuring units: mm (inch), not scale!
Outputs 1 to 8
98 (3.86)
18 (0.71)
(0.28) 7
18 (0.71)
(0.28) 7
18 (0.71)
(0.28) 7
18 (0.71)
35 (1.38)
86 (3.39)
105 (4.14)
power supply
Commend, Inc. · 63 Ramapo Valley Road, Suite 201 · Mahwah, New Jersey 07430 · Tel. (201) 529-2425 · Fax (201) 529-0008 · office@commendusa.com · www.commendusa.com Datasheet Version 1.1/1207 | Errors and omissions excepted | Products may change in the interest of technical improvements without notice.
www.commend.com
P3|3