SCF830-D-N SVE panel de control para bombas contra incendios con motor diésel NFPA20

Page 1

SCF830-D-N DIESEL ENGINE DRIVEN CONFIGURABLEPROGRAMMABLE FIRE PUMP CONTROL PANEL SCF830-D-U control panels are complete, automatic and configurable instruments, useful for managing operations of any tipe diesel engine driven firefighting pumpsets of any power in any environment.Designed to comply with NFPA 20 They govern the start and stop of the diesel engine driven fire pumps and protect them by means of the action of the connected and controller-generated alarms, visualize the most relevant values and informations, also manage the communication with the operator and both the contour elements and the remote manned centre.

SCF830-D-N MODELS SCF830

U SCF830-D SERIES

EN12845

U

12030

ES

Standards

Battery chargers

Language

UNE-EN 12845: 2015

SBB 12070 (12V / 7A)

EN: English

UNE 23500:2018

SBB 12100 (12V / 10A)

ES: Español

UNI 10779:2014

SBB 24050 (24V / 5 A)

FR: Français

SBB 24100 (24V / 10 A)

IT: Italiano

SBB 12070 (12V / 7A)

PT: Portugues

AS AS 2941:2013 B

LPCB

N

NFPA-20

V

VdS

F

FM

A

APSAD SCF830-D-N-01-EN-Rev.0_br1.docx


SCF830-D-N DIESEL ENGINE DRIVEN CONFIGURABLE-PROGRAMMABLE FIRE PUMP CONTROL PANEL

MAIN FEATURES Standards and technical regulations Compliance with standards and technical regulations

NFPA-20 NFPA-70 UNE-EN 61439-1 Low-voltage switchgear

Electrical features and batteries Incoming line voltage and frequency

From 85V to 265 VAC 50-60Hz depending on model

Nominal battery voltage

12 VDC or 24 VDC depending on model Models

Battery chargers

SBB12070

Nominal charging current Supported battery capacity (C10) DIN power

SBB12100

7A

10 A

5A

10 A

285 Ah

142 Ah

285 Ah

96,6 W

138,0 W

138,0 W

276,0 W

85% nominal power

Float voltage drift

< 1% from 0% to 90% of nominal current load

Charge current drift

SBB24100

200 Ah

Performance

Supported batteries (except SBA12030)

SBB24050

Lead-Acid open fluid

Lead-Acid VRLA (AGM or GEL)

NiCd-(9-18 cells)

NiCd-(10-20 cells)

< 5% from 50% to 99% of the float voltage

Design features IP65 Protected from total dust ingress (NEMA 4) Enclosure

Impact rating: IK10 (except for display) Fireproof grade: Fire extinguishes <30s

Display

Transflective: Visible under direct sunlight Halogen free

Wiring

Fire resistance: RZ1 according to EN50200 (830º during 90min)

Pressure sensor

1 pressure measuring device using pressure transducers 0-100bar / 4-20mA It can be used to monitor the system pressure of the pump The demand pressure to start and stop the pump are configurable

Working temperatures

Recommended: -5ºC to 40ºC (tested up to 60ºC)

Electromagnetic environment

CEM-1

Pump and system protection Total system alarms

38

Pump start methods Pressure switch line: Low system pressure Automatic Mode

Manometer: system pressure Water level contact: Low priming tank level Remote start contact

Manual Mode

“Battery A” and “Battery B” press buttons in front panel

Test Mode

Manual start press button to evaluate the status of the emergency start button

EN12845

2


SCF830-D-N DIESEL ENGINE DRIVEN CONFIGURABLE-PROGRAMMABLE FIRE PUMP CONTROL PANEL Measuring instruments Batteries

2 voltmeters, battery voltage 2 battery charge current ammeters Engine cooling temperature (water) Engine cooling oil temperature

Engine

Oil pressure Fuel tank level Engine speed in rpm 1 Voltmeter: Supply voltage AC. Accuracy >1%

General System

1 Manometer: System pressure (4-20mA pressure sensor required) 1 Manometer: Pump suction pressure (4-20mA pressure sensor required 1 Flow Meter (manual flow input / pulse output / 4/ 20 mA sensor)

Other information in display Current Date and Time (RTC with independent battery)

Accumulated engine working hours

150 latest events (pump starts, alarms‌). 500 recorded

Pump start demand type

150 latest records of system pressure variation. 16.000 recorded

Active Alarms

50 Pump test records stored (pump curve)

Commissioning and maintenance performed register

Automatic start of weekly test programming

Digital and analog input and output test:

Other features Pressure switch lines’ monitoring with short-and open circuit alarm

Engine heating management through constant engine temperature monitoring

Engine crank levers connection monitoring with open circuit alarm

Engine cooling system operation management

Monitoring signals in front panel Off Operating Modes

Auto Manual

Not in auto

Not in Auto Pump on demand

Pump status

Pump start with A battery/ Pump start with B battery Pump running

Batteries

Battery A / Battery B correct Chargers correct Alarms on display

Alarms

Common alarm relay

Buzzer

100 dB

EN12845

3


SCF830-D-N DIESEL ENGINE DRIVEN CONFIGURABLE-PROGRAMMABLE FIRE PUMP CONTROL PANEL Communications USB connector B Device type

SAF830-D PC Communication

USB connector A Host type

SAF830-D-> PENDRIVE Communication LAN (local area network) port included in all models

Ethernet Modbus Protocol/ TCP-IP

WAN (Ethernet) port included in all models Point-to-point port included in all models

RS485 Modbus Protocol / RTU

Optional module SCOM901 not included

USB connector B Device type

SAF830-D PC Communication

Languages ENGLISH / ESPAÑOL / FRANÇAIS /ITALIANO / PORTUGUES

DIMENSIONS, FIXING AND MAIN ELEMENTS

Dimensions (mm) and weight Model SCF830-D-N 12070 /12100 / 24050 / 24100

A

B

C

D

E

F

Weight

570

550

230

210

462

470

26 kg

Control panel main elements Element

Nomenclature

Amount

SCF830-D-N control panel enclosure

ENV1

1

SAF830-D-N PLC: Operator interface

MC1

1

SAF830-D-N PLC: SCF-D-NFPA-00 Base Plate Card

TE1

1

CA1, CA2

2

S1

1

Q1, Q2, Q3

3

H1

1

Drain solenoid valve

Y1

1

Pressure sensor

B1

1

Battery charger SBB series Load break switch (230V) Magneto thermic circuit breakers Buzzer (12V DC)

EN12845

4


SCF830-D-N DIESEL ENGINE DRIVEN CONFIGURABLE-PROGRAMMABLE FIRE PUMP CONTROL PANEL

INTERNAL AND EXTERNAL WIRING DIAGRAM

EN12845

5


SCF830-D-N DIESEL ENGINE DRIVEN CONFIGURABLE-PROGRAMMABLE FIRE PUMP CONTROL PANEL

DISPLAYS SYSTEM PRESSURES System pressures

9.5 8.5

8.75 PRES. SWITCH LOW

Pump parameters

bar

LAST ALARMS Last alarms

Batteries

NO ACTIVE ALARMS AL01-NORMAL POWER LOSS AL10-LOW PRIMING TANK LEVEL RESET

EVENTS Event history

OFF MODE M. PUMP AL01-NORMAL POWER LOSS PRIMING TANK L.L. ON PRIMING TANK L.L. OFF AL10-L. PRIMING TANK LEVEL OFF MODE M. PUMP

09:10 15/05/04 08:32 15/05/04 06:50 15/05/04 06:28 15/05/04 06:28 15/05/04 06:10 15/05/04

Systempressure log

Sensors

About…

MAINTENANCE Maintenance menu

Maintenance menu ACCES

Digital input status

Digital output status

PC / SMARTPHINE SOFTWARE

EN12845

6