SCF8M-JJ SVE Control panel for 2 Jockey pumps in alternate operation EN12845 / NFPA 20 / APSAD R5

Page 1

SCF8M-EE

CONTROL PANEL FOR 2 ELECTRIC MOTOR DRIVEN Programable-configurable FIRE PUMP in ALTERNATE OPERATION

The SCF8M-EE control panels control the starting and stopping of 2 main electric pumps or 2 Jockey pumps working in alternate operation. In the event of successive start-up requests, the pumps will be activated in such a way that only one of them will come into operation at a time; the pump that is activated will be the one that has remained at rest in the previous sequence. If an anomaly is detected in any of the pumps or if its disconnection has been selected, it will be the pump that remains in operation that will assume the totality of the activations in the event of start-up demands. The SCF8M-EE control panels also display the most relevant values and information and manage the communication with both the control elements and the remote monitors.

MODELS ie: SCF8M

JD

0750

JD

075

U

EN

PUMP TYPE

POWER

PUMP TYPE

POWER

NORMA

LANGUAGE

JD: Jockey (DOL) 0075: 7,5 kW

JD: Jockey (DOL) 0075: 7,5 kW

ED: Electric (DOL)

ED: Electric (DOL)

SCF8M-EE Series

0185: 18,5 kW

0185: 18,5 kW

UNE-EN 12845:2016 EN: English UNE 23500:2018 UNE 23500:2012

FR: Français

UNI 10779:2014

ES: Español

B

LPC TB210 / FOC

PT: Portugues

AS

AS 2941 Ed. 2013

IT: Italiano

N

NFPA-20

DE: Deutsch

U

NE: Nederlandse

EN12845

SCF8M-EE-U-03-EN-Rev.0_br2.docx


SCF8M-E-U 2 ELECTRIC MOTOR DRIVEN PROGRAMABLE-CONFIGURABLE FIRE PUMPS IN ALTERNATE OPERATION CONTROL PANEL

MAIN FEATURES Standards and technical regulations EN 12845 Ed.2016 UNE 23500 Ed. 2018- Ed.2012 APSAD R5 REGLE D’INSTALLATION. Robinets d’incendie armés Standard, Technical regulations

LPC-TB210 / FOC CEPREVEN R.T.2-ABA Ed. 2006 / CEPREVEN R.T.1-ROC Ed. 2007 CEA-4001 Sprinkler Systems UNE-EN 61439-1 Low-voltage switchgear

Electric and pump motor Incoming line voltage

400 Vac

Electrics frequency

50Hz / 60Hz. (depending on model)

Electric pumps motor size

Up to 18,5kW

Design features Enclosure Display Wiring Pump room temperature Isolation rating between phases Isolation rating between phases and ground Isolation impedance between phases and ground Earthing system Electromagnetic environment

IP65 Protected from total dust ingress (NEMA 4) Impact rating: IK10 (except for display) Fireproof grade: Fire extinguishes <30s Transflective: Visible under direct sunlight Halogen free In compliance with UNE-EN 50525-3-31 Wires up to 1,5mm2: H05Z1-K flame retardant. Power supply: H07Z1-K Fire resistant:(830º C during 90min) 20ᵅF to 104ᵅF (-5ºC to 40ºC) ,Tested up to 140ᵅF (60ºC) 500 Vac 2.500 Vac 2M Ohm between one phase and ground Does not required neutral connection ECM-1

Pump protections Total system alarms Mains

Electric pumps protections

21 Under / Over Voltage Under / Over Frequency Phases rotation sense Fuses/Magnetic relays (depending on model) Overcurrent alarm Low Cos φ Alarm Undercurrent alarm Low water level alarm Pump start failure alarm Pump-1 pressure switch: Short circuit / Open circuit Pump-2 pressure switch: Short circuit / Open circuit Pressure sensor alarm Anti-freeze liquid low level alarm

Start up and sotp methods

Automatic Mode

Pressure switch: Low system pressure pump-1 / pump-2 (Short and open circuit detection) Manometer: System pressure 4-20mA (0-100bar) Flow switch Pump-1, Pump-2 “Start” press buttons

EN12845

2


SCF8M-E-U 2 ELECTRIC MOTOR DRIVEN PROGRAMABLE-CONFIGURABLE FIRE PUMPS IN ALTERNATE OPERATION CONTROL PANEL Measuring instruments General

Electric Pumps Control module Internal battery

3 True RMS Voltmeter: voltage for every phase L1-L2-L3 1 pump rotation/phase rotation sense 1 Electric frequency meter 1 Manometer pump discharge pressure ( pressure sensor required with 4-20mA signal) 1 True RMS Ammeter: pump current 1 True RMS Active power in KW 1 Power factor (Phi Cos) 1 Voltmeter: Incoming line voltage 1 Voltmeter: battery voltage 1 Ammeter: battery charging electrical current

Other information in display Pumps working hours and minutes

16,000 pressure registers: 150 on display

Pumps start count & working hours and minutes

50 pump test registers

Current date and time (RTC with independent battery)

Active demands: pressure switches and sensor

500 last events (pump starts, alarms, etc.): 150 on display

Active alarms

Input & Output. Digital / Analog test on display

Calibration of measuring instruments

Battery and battery charger: charging process and status

Commissioning register / maintenance performed records

Front panel lights and acoustic alarms Operating modes Electric Pump Pumps status Alarm Incoming line voltage and phase connections Buzzer

Off Auto Demand Start order Red led indicator lamp and 80dB buzzer One led light for each phase / phase rotation 80dB 1 hour autonomy

Communications Micro USB connector AB type Micro USB connector AB type Ethernet Modbus Protocol/ TCP-IP RS485 Modbus Protocol/ RTU Voltage free contacts

SAF8M-EE PC Communication SAF8M-EE PENDRIVE Communication LAN (local area network) / WAN (Ethernet) Point-to-point Optional Optional module SCOM901 not included 6 Voltage-free switched contacts: 30Vdc – 0.3A

Language ENGLISH / ESPAÑOL / FRANÇAIS / ITALIANO / PORTUGUES / DEUTSCH / NEDERLANDSE

DIMENSIONS

Dimensions and attachments (mm) Up to 18,5 kW

A

B

C

D

E

F

340

430

182

214

290

335

EN12845

3


SCF8M-E-U 2 ELECTRIC MOTOR DRIVEN PROGRAMABLE-CONFIGURABLE FIRE PUMPS IN ALTERNATE OPERATION CONTROL PANEL

INTERNAL WIRING CONNECTION DIAGRAM: 2

ELECTRIC PUMPS IN ALTERNATE OPERATION

EN12845

4


SCF8M-E-U 2 ELECTRIC MOTOR DRIVEN PROGRAMABLE-CONFIGURABLE FIRE PUMPS IN ALTERNATE OPERATION CONTROL PANEL

INTERNAL WIRING CONNECTION DIAGRAM: 2 JOCKEY PUMPS IN ALTERNATE OPERATION

EN12845

5


SCF8M-E-U 2 ELECTRIC MOTOR DRIVEN PROGRAMABLE-CONFIGURABLE FIRE PUMPS IN ALTERNATE OPERATION CONTROL PANEL

DISPLAYS

Incoming electric line voltage and frequency

System pressures

PUMP Pump parameters

12

1 T:00001h 2 T:00001h

4.3bar 1 OFF

2 MAN

00114 00112

PUMP

Demand:

Pumps parameters

Pressure Switch

I: 48.2A P: 31.3KW PF: 0.95

12

1 T:00001h 2 T:00001h

Batery and current control

Last alarms

Events log

System pressures log

Maintenance menu

Maintenance menu

4.3bar 1 OFF

2 MAN

00114 00112

COMMUNICATIONS SCF8M-EE === PC USB

SCF8M-EE === Pendrive Pendrive === PC

Monitoring / Configuration via SSW1005 software Bootloader: SCF8-EE firmware update Information download from SCF8-E(X)-U to PENDRIVE Information transfer from PENDRIVE to PC

Ethernet MODBUS TCP/IP

SCF8M-EE === PC

Monitoring / Configuration via SSW1004 software Data can be monitored using customer’s SCADA system

RS485 MODBUS / RTU

SCF8M-EE === PC

Monitoring / Configuration via SSW1004 software Data can be monitored using customer’s SCADA system

EN12845

6

Demand:

Pressure Switch

I: 48.2A P: 31.3KW PF: 0.95


SVE, S. L. Albert Einstein 36-B Parque Tecnológico de Álava 01510 Vitoria-Gasteiz SPAIN www.svecorp.com