North American Power Fuses The most popular North American power fuses — to meet the most popular protection priorities.
Your problem: Today, you need a time-delay power fuse that can handle normal surges. Tomorrow, it’s a power fuse with a
• Class RK5 / Tri-onic® TR & TRS • DC-rated / Tri-onic® TRS-RDC
high interrupting rating and the added security of rejection dimen-
• Class J / Amp-trap® HSJ
sions. The day after that, one of those economical one-time power
• Class J / Amp-trap® A4J
fuses will do the trick. But where can you turn for all three?
• Class L / Amp-trap® A4BY
Our solution: Ferraz Shawmut’s comprehensive power fuse
• Class L / Amp-trap® A4BT
offering covers a complete range of applications and a complete
• Class T / Amp-trap® A3T & A6T
range of circuit-protection needs. Whether it’s the characteristics of our Tri-onic® time-delay fuses. The high current-limiting capacity of our original Amp-trap® power fuses. The cost-efficient protection of our One-Time fuses. Or some other application-specific power fuse solution.
• Class RK1 / Amp-trap® A2K & A6K • Class RK1/Amp-trap® HSRK • Class G / Amp-trap® AG • Class CC / Amp-trap® ATMR
Want more information fast? For more technical or applicationspecific information, please call our Power Fuse experts, at 978-462-6662; 416-252-9371 in Canada; or visit our website at us.ferrazshawmut.com.
• Class K-5 / OT, OTN & OTS One-time • Class H / RF/RFS & RL/RLS Renewable
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TRI-ONIC®
TR & TRS
Time Delay/Class RK5 The industry’s Most popular fuse for Motor circuit protection. Tri-onic® SmartSpot® fuses now provide a visual open fuse indicator. With advanced material technology added to the existing product the TR and TRS current limiting time delay fuses are engineered for overcurrent protection of motors and transformers, service entrance equipment, feeder and branch circuits. Tri-onic proven time delay characteristic safely handles harmless starting currents and inrush currents associated with today’s motors and transformers. Features/Benefits ➤ Solid State SmartSpot Indicator ➤ Time delay for motor start-ups and transformer inrush currents without nuisance opening ➤ Current limiting for low peak let-thru current ➤ Rejection-style design prevents replacement errors (when used with recommended fuse blocks) ➤ Easy-to-read label for quick recognition and replacement ➤ Metal-embossed date and catalog number for traceability and lasting identification ➤ Fiberglass body provides dimensional stability in harsh industrial settings ➤ High-grade silica filler ensures fast arc quenching and high current limitation
HIGHLIGHTS:
Applications:
➤ Time Delay ➤ Current Limiting ➤ AC & DC Rated
➤ Motor Circuits ➤ Mains ➤ Feeders ➤ Branch Circuits ➤ Transformers ➤ Service Entrance Equipment ➤ General-purpose Protection
Ratings
Approvals
➤ TR AC: 1/10 to 600A 250VAC, 200kA I.R.
➤ UL Listed to Standard 248-12 File E2137
➤ DC: 1/10 to 2 8/10A & 35 to 400A, 250VDC, 20kA I.R.; 3 to 30A & 450 to 600A, 160VDC, 20kA I.R.
➤ CSA Certified to Standard C22.2 No. 248.12 ➤ DC Listed to UL Standard 248 TRS only
➤ TRS AC: 1/10 to 600A 600VAC, 200kA I.R. ➤ DC: 1/10 to 12A, 600VDC, 20kA I.R.; 15 to 60A, 300VDC, 20kA I.R. 70 to 600A, 600VDC, 100kA I.R. Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
TRI-ONIC速
Time Delay/Class RK5 Fuses
TR & TRS
Standard Fuse Ampere Ratings, Catalog Numbers Ampere Catalog Number Rating 250V 600V
Ampere Catalog Number Rating 250V 600V
Ampere Catalog Number Rating 250V 600V
1/10 15/100 2/10 3/10 4/10 1/2 6/10 8/10 1 1-1/8 1-1/4 1-4/10 1-6/10 1-8/10
TR1/10R TR15/100R TR2/10R TR3/10R TR4/10R TR1/2R TR6/10R TR8/10R TR1R TR1-1/8R TR1-1/4R TR1-4/10R TR1-6/10R TR1-8/10R
TRS1/10R TRS15/100R TRS2/10R TRS3/10R TRS4/10R TRS1/2R TRS6/10R TRS8/10R TRS1R TRS1-1/8R TRS1-1/4R TRS1-4/10R TRS1-6/10R TRS1-8/10R
3-1/2 4 4-1/2 5 5-6/10 6 6-1/4 7 8 9 10 12 15 17-1/2
TR3-1/2R TR4R TR4-1/2R TR5R TR5-6/10R TR6R TR6-1/4R TR7R TR8R TR9R TR10R TR12R TR15R TR17-1/2R
TRS3-1/2R TRS4R TRS4-1/2R TRS5R TRS5-6/10R TRS6R TRS6-1/4R TRS7R TRS8R TRS9R TRS10R TRS12R TRS15R TRS17-1/2R
50 60 70 75 80 90 100 110 125 150 175 200 225 250
TR50R TR60R TR70R TR75R TR80R TR90R TR100R TR110R TR125R TR150R TR175R TR200R TR225R TR250R
TRS50R TRS60R TRS70R TRS75R TRS80R TRS90R TRS100R TRS110R TRS125R TRS150R TRS175R TRS200R TRS225R TRS250R
2 2-1/4 2-1/2 2-8/10 3 3-2/10
TR2R TR2-1/4R TR2-1/2R TR2-8/10R TR3R TR3-2/10R
TRS2R TRS2-1/4R TRS2-1/2R TRS2-8/10R TRS3R TRS3-2/10R
20 25 30 35 40 45
TR20R TR25R TR30R TR35R TR40R TR45R
TRS20R TRS25R TRS30R TRS35R TRS40R TRS45R
300 350 400 450 500 600
TR300R TR350R TR400R TR450R TR500R TR600R
TRS300R TRS350R TRS400R TRS450R TRS500R TRS600R
B
Note: Indicator not available (1/10 - 7) amps.
0-60A 61-600A
Dimensions AMPERE A RATING In. 250V-TR FUSES 0-30 2 31-60 3 61-100 5-7/8 101-200 7-1/8 201-400 8-5/8 401-600 10-3/8 600V-TRS FUSES 0-30 5 31-60 5-1/2 61-100 7-7/8 101-200 9-5/8 201-400 11-5/8 401-600 13-3/8
mm
B In. mm
C In. mm
D In. mm
E In. mm
51 76 149 181 219 264
9/16 13/16 1-1/16 1-9/16 2-1/16 2-9/16
14 21 27 40 53 66
- - 1/8 3/16 1/4 1/4
- - 3 5 6 6
- - 3/4 1-1/8 1-5/8 2
- - 19 28 41 51
- - 1 1-3/8 1-7/8 2-1/4
25 35 48 57
127 139 200 244 295 340
13/16 1-1/16 1-5/16 1-13/16 2-9/16 3-1/8
21 27 34 46 66 80
- - 1/8 3/16 1/4 1/4
- - 3 5 6 6
- - 3/4 1-1/8 1-5/8 2
- - 19 28 41 51
- - 1 1-3/8 1-7/8 2-1/4
25 35 48 57
Recommended Fuse Blocks With Box Connectors For Tri-onic速 Class RK5 Fuses Fuse Catalog Number Ampere 250V 600V Rating 1 Pole 3 pole 1 pole 3 pole 0-30 31-60 61-100 101-200 201-400 401-600
20306R 20606R 21036R 22001R 24001R 2631R
20308R 20608R 21038R 22003R 24003R 2633R
60306R 60308R 60606R 60608R 61036R 61038R 62001R 62003R 64001R 64003R 6631R 6633R
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
TRI-ONIC®
Time Delay/Class RK5 Fuses
TR & TRS
Current in Amperes
Melting Time – Current Data, 250V Fuses
TR15 to 600
Time in Seconds
Current in Amperes
Melting Time – Current Data, 250V Fuses
TR1/10 to 12
Time in Seconds Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
TRI-ONIC®
Time Delay/Class RK5 Fuses
TR & TRS
Current in Amperes
Melting Time – Current Data , 600V Fuses
TRS15 to 600
B
Time in Seconds
Current in Amperes
Melting Time – Current Data. 600V Fuses
TRS1/10 to 12
Time in Seconds Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
TRI-ONIC®
Time Delay/Class RK5 Fuses
TR & TRS
Maximum Instantaneous Peak Let-Thru Amperes
Peak Let-Thru Current Data – TR30 to 600, 250 Volts AC
Available Current in RMS Symmetrical Amperes
Maximum Instantaneous Peak Let-Thru Amperes
Peak Let-Thru Current Data – TRS15 to 600, 600 Volts AC
Note: See Application Information page L9 for All Motor and Transformer Tables.
Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
tri-onic®
TRS-RDC
time delay/dc rated DC RATED FOR TOUGH DC APPLICATIONS The Tri-onic® DC fuse series is designed for DC circuit protection in surface and underground mines. The TRS-RDC is MSHA approved and meets the industry’s most severe third party requirements for 600VDC rated fuses.
B
The TRS-RDC is a time-delay fuse with essentially the same time-current characteristic as the standard Tri-onic®.
Features/Benefits ➤ DC rated for mine duty and other long time-constant applications ➤ Time delay for motor start-ups and high inrush loads without nuisance opening ➤ Rugged glass melamine body for superior ➤ Reliability in harsh environments
HIGHLIGHTS:
Applications:
➤ Time Delay ➤ DC Rated
➤ Mine Circuits ➤ Trailing Cables ➤ Pump Motors ➤ Rail Heaters
Ratings
Approvals
➤ DC: 1 to 30A 300VDC, 20kA I.R. (Consult Factory for Availability)
➤ MSHA Approval No. 28-26-0
➤ DC: 35 to 400A 600VDC, 20kA I.R.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
TRI-ONIC®
Time Delay/600VDC Fuses
TRS-RDC
Standard Fuse Ampere Ratings, Catalog Numbers AMPERE RATING
CATALOG NUMBER
1/10 15/100 2/10 3/10 4/10 1/2 6/10 8/10 1 1-1/8
TRS1/10RDC TRS15/100RDC TRS2/10RDC TRS3/10RDC TRS4/10RDC TRS1/2RDC TRS6/10RDC TRS8/10RDC TRS1RDC TRS1-1/8RDC
AMPERE RATING
1-1/4 1-4/10 1-6/10 1-8/10 2 2-1/4 2-1/2 2-8/10 3 3-2/10
CATALOG NUMBER
AMPERE RATING
CATALOG NUMBER
AMPERE RATING
CATALOG NUMBER
AMPERE RATING
TRS1-1/4RDC TRS1-4/10RDC TRS1-6/10RDC TRS1-8/10RDC TRS2RDC TRS2-1/4RDC TRS2-1/2RDC TRS2-8/10RDC TRS3RDC TRS3-2/10RDC
3-1/2 4 4-1/2 5 5-6/10 6 6-1/4 8 9 10
TRS3-1/2RDC TRS4RDC TRS4-1/2RDC TRS5RDC TRS5-6/10RDC TRS6RDC TRS6-1/4RDC TRS8RDC TRS9RDC TRS10RDC
12 15 17-1/2 20 30 35 40 45 50 60
TRS12RDC TRS15RDC TRS17-1/2RDC TRS20RDC TRS30RDC TRS35RDC TRS40RDC TRS45RDC TRS50RDC TRS60RDC
70 80 90 100 125 150 175 200 250 300 400
CATALOG NUMBER TRS70RDC TRS80RDC TRS90RDC TRS100RDC TRS125RDC TRS150RDC TRS175RDC TRS200RDC TRS250RDC TRS300RDC TRS400RDC
0-60 Amperes 61-400 Amperes
Dimensions
AMPERE RATING 0-30 31-60 61-100 101-200 201-400
A In. mm 5 5-1/2 7-7/8 9-5/8 11-5/8
127 139 200 244 295
B In. mm 13/16 1-1/16 1-5/16 1-13/16 2-9/16
21 27 34 46 66
C In. mm - - 1/8 3/16 1/4
- - 3 5 6
D In. mm - - 3/4 1-1/8 1-5/8
- - 19 28 41
E In. mm - - 1 1-3/8 1-7/8
25 35 48
Current in Amperes
Melting Time – Current Data, 600V Fuses
TRS-RDC60 to 400
Time in Seconds Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
AMP-TRAP®
HSJ
HIGH SPEED/CLASS J Protect your wiring and power semiconductors with a single fuse. The new High Speed J (HSJ) combines the low I2t of a semiconductor fuse and the branch circuit performance of a Class J UL listed fuse. This fuse was designed for the starting characteristics of solid state motor controllers. The HSJ can provide branch circuit protection per NEC requirements, as well as very low I2t for protection of power semiconductors such as Diodes, SCR’s, GTO’s and SSR’s.
B
Features/Benefits ➤ Optimized over-load capability for withstanding elevated levels of current during electronic motor controller starts ➤ Low I2t (low thermal energy) ➤ Excellent Cycling Ability for frequent starts/stops without nuisance opening
HIGHLIGHTS:
Applications:
➤ Current-Limiting ➤ AC & DC Ratings ➤ Low l2t ➤ Compact Size
➤ Branch Circuits ➤ Control Panels ➤ Electronic Motor Controllers ➤ Phase Controllers ➤ Drives ➤ Soft-Starters ➤ Solid State Relays
Ratings
Approvals
➤ AC: 1-600A 600VAC, 200kA I.R. 300kA I.R. Self Certified
HSJ (15 to 600A) ➤ UL Listed to Standard 248-8 File E2137
➤ DC: 15-600A 500VDC, 100kA I.R. L/R 10mS
➤ DC Listed to UL248 ➤ CSA Certified to Standard C22.2 No. 248.8
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
AMP-TRAP速
HIGH SPEED/CLASS J
HSJ Recommended Fuse Blocks With Box Connectors for Amp-trap速 Class J Fuses
Standard Fuse Ampere Ratings, Catalog Numbers AMPERE RATING
CATALOG NUMBER
OUTLINE FIGURE
1
HSJ1
1
3
HSJ3
1
6
HSJ6
1
10
HSJ10
AMPERE RATING
CATALOG NUMBER
OUTLINE FIGURE
90
HSJ90
2
100
HSJ100
2
110
HSJ110
2
1
125
HSJ125
2
15
HSJ15
1
150
HSJ150
2
17-1/2
HSJ17-1/2
1
175
HSJ175
2
20
HSJ20
1
200
HSJ200
2
25
HSJ25
1
225
HSJ225
2
30
HSJ30
1
250
HSJ250
2
35
HSJ35
1
300
HSJ300
2
40
HSJ40
1
350
HSJ350
2
45
HSJ45
1
400
HSJ400
2
50
HSJ50
1
450
HSJ450
2
60
HSJ60
1
500
HSJ500
2
70
HSJ70
2
600
HSJ600
2
80
HSJ80
2
Fuse Catalog Number Ampere 600V OR LESS Rating 1 Pole 3 pole US3J1I US3J3I 0-30 31-60 US6J1I US6J3I 61-100 61036J 61038J 101-200 62001J 62003J 201-400 64031J 64033J 401-600 6631J 6633J A variety of pole configurations and termination provisions is available.
Dimensions Fig 1
Fig 2
AMPERE A RATING In. mm 15-30
2-1/4
B In. mm
57
13/16
21
C In. mm -
-
D In. mm -
-
E In. mm -
-
F In. mm -
-
G In. mm -
-
H In. mm -
-
31-60
2-3/8
60
1-1/16
27
-
-
-
-
-
-
-
-
-
-
-
-
61-100
4-4/8
117
1-1/8
29
1/8
3.2
3/4
19
1
25
3-5/8
92
3/8
10
9/32
7
101-200
5-3/4
146
1-5/8
41
3/16
4.8
1-1/8
29
1-3/8
35
4-3/8
111
3/8
10
9/32
7
201-400
7-1/8
181
2-1/8
54
1/4
6.3
1-5/8
41
1-7/8
48
5-1/4
133
17/32
13
13/32
10
401-600
8
203
2-1/2
64
3/8
9.5
2
51
2-1/8
54
6
152
11/16
18
17/32
13
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 10
AMP-TRAP速
HIGH SPEED/CLASS J
HSJ
I2t Data - 600 Volts AC, 100kA Max Clearing I2t @ Ampere 600V AC 100kA Rating Pre-Arc 1 Fuse 2 in Series (A2s x 103) (A2s x 103) (A2s x 103) (A) 15 0.02 0.36 0.15 17.5 0.03 0.45 0.19 20 0.04 0.58 0.24 25 0.08 1.2 0.50 30 0.16 2 0.84 35 0.16 1.5 0.63 40 0.27 2.3 1.0 45 0.32 3.3 1.4 50 0.44 5.5 2.3 60 0.72 8.0 3.4 70 1.2 12 5.0 80 1.6 15 6.3 90 2.3 21 8.8 100 2.7 23 9.7 110 2.3 21 10 125 3.4 29 14 150 5.1 41 20 175 8.0 60 29 200 14 92 44 225 14 110 53 250 16 130 62 300 26 200 96 350 37 290 139 400 63 450 216 450 67 500 240 500 98 600 288 600 141 900 432
Max Clearing I 2t @ 480V AC 100kA 1 Fuse 2 in Series (A2s x 103) (A2s x 103) 0.23 0.12 0.29 0.15 0.37 0.19 0.77 0.40 1.3 0.66 0.96 0.50 1.5 0.76 2.1 1.1 3.5 1.8 5.1 2.6 7.7 4.0 9.6 5.0 13 6.9 15 7.6 13.9 8 19 11 27 16 40 23 61 35 73 42 86 49 132 76 191 110 297 171 330 190 396 228 594 342
Clearing I2t vs Operating Voltage 1.0
Correction Factor for Watts Loss
Correction Factor for I2t
B
Watts Loss vs. % Rated Current
1.0 .8 110-600 AMP .6 .4 .2 0
Watts Loss at Rated Current 2.6 3.5 3.7 4 4.1 5.3 5.5 6 6.8 8.4 10 11 13 14 18 19 22 24 26 30 36 38 40 42 58 59 68
15-100 AMP 0
100
200
300
400
.8
.6
.4
.2
500 600
50
60
70
80
90
100
Operating Voltage (AC RMS Volts) Percent Rated Current Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com B 11
AMP-TRAP速
HIGH SPEED/CLASS J
HSJ
Maximum Instantaneous Peak Let-Thru Amperes
Peak Let-Thru Data - HSJ15 to 600, 600Volts AC
Available Current in RMS Symmetrical Amperes Clearing I2t at 500 VDC 100kA, L/R = 10mS CLEARING I2t @ 500 VDC L/R = 10 ms (A2s X 103) 0.12 0.18 0.24 0.46 0.91 0.60 0.92 1.3 2.2 3.2 4.8 6.2 8.9 10 8.8 13 19 28 46 52 59 96 136 230 270 390 560
DC Voltage Capability
AMPERE RATING 15 17.5 20 25 30 35 40 45 50 60 70 80 90 100 110 125 150 175 200 225 250 300 350 400 450 500 600
DC Voltage vs. Time Constant
L/R Time Constant (mS)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 12
AMP-TRAP速
HIGH SPEED/CLASS J
HSJ
Melting Time - Current Data, HSJ15 to 600, 600Volts AC
Time in Seconds
B
Time in Seconds
Available Current in RMS Symmetrical Amperes
Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 13
AMP-TRAP®
A4J
FAST ACTING/Class J For excellent CURRENT LIMITING PROTECTION A4J Class J fuses deliver excellent current-limiting protection to a wide variety of applications. Their unique dimensions prevent the substitution of other fuses with lower voltage ratings, interrupting ratings, or current-limiting capability.
Features/Benefits ➤ High current limitation for low peak let-thru current ➤ Unique dimensions prevent replacement by other fuse classes ➤ Fiberglass body provides dimensional stability in harsh industrial environments ➤ Easy-to-read imprint label for quick recognition and replacement
HIGHLIGHTS:
Applications:
Ratings
Approvals
➤ Fast Acting ➤ Very Current-Limiting ➤ DC Ratings
➤ Capacitors ➤ Loadcenters ➤ Panelboards ➤ Switchboards ➤ Bus Duct ➤ Feeder Circuits ➤ Circuit Breakers ➤ Lighting, Heating, and General Loads
➤ AC: 1 to 600A 600VAC, 200kA I.R.
➤ UL Listed to Standard 248-8 File E2137
➤ DC: 1 to 600A 300VDC, 100kA I.R.
➤ CSA Certified to Standard C22.2 No. 248.8 ➤ DC Listed to UL 248 ➤ IEC 269-2-1
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 14
AMP-TRAP速
fast acting/Class J Fuses
A4J
Standard Fuse Ampere Ratings, Catalog Numbers AMPERE RATING
CATALOG AMPERE NUMBER RATING
CATALOG AMPERE CATALOG NUMBER RATING NUMBER
1
A4J1
50
A4J50
200
A4J200
3
A4J3
60
A4J60
225
A4J225
6
A4J6
70
A4J70
250
A4J250
10
A4J10
75
A4J75
300
A4J300
15
A4J15
80
A4J80
350
A4J350
20
A4J20
90
A4J90
400
A4J400
25
A4J25
100
A4J100
450
A4J450
30
A4J30
110
A4J110
500
A4J500
35
A4J35
125
A4J125
600
A4J600
40
A4J40
150
A4J150
45
A4J45
175
A4J175
B
Recommended Fuse Blocks With Box Connectors for Amp-trap Class J Fuses Fuse
1-60A
61-600A
Ampere Rating
Catalog Number 600V OR LESS 1 Pole 3 pole
0-30 31-60 61-100 101-200 201-400 401-600
US3J1I US6J1I 61036J 62001J 64031J 6631J
US3J3I US6J3I 61038J 62003J 64033J 6633J
A variety of pole configurations and termination provisions are available. Refer to the fuse block section of this catalog for details.
Dimensions AMPERE A B C D E F G H RATING In. mm In. mm In. mm In. mm In. mm In. mm In. mm In. mm 1-30 2-1/4 57 13/16 21 - - - - - - - - - - - - 31-60 2-3/8 60 1-1/16 27 - - - - - - - - - - - - 61-100 4-5/8 117 1-1/8 29 1/8 3.2 3/4 19 1 25 3-5/8 92 3/8 10 9/32 7 101-200 5-3/4 146 1-5/8 41 3/16 4.8 1-1/8 29 1-3/8 35 4-3/8 111 3/8 10 9/32 7 201-400 7-1/8 181 2-1/8 54 1/4 6.3 1-5/8 41 1-7/8 48 5-1/4 133 17/32 13 13/32 10 401-600 8 203 2-1/2 64 3/8 9.5 2 51 2-1/8 54 6 152 11/16 18 17/32 13
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 15
AMP-TRAP®
fast acting/Class J Fuses
A4J
Current in Amperes
Melting Time – Current Data, 600V Fuses
A4J30 to 600
Time in Seconds
Maximum Instantaneous Peak Let-Thru Amperes
Peak Let-Thru Current Data – 30 to 600, 600 Volts AC
Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 16
AMP-TRAP®
A4BY
CLASS l count on the high interrupting rating of our most widely-used class L fuse When it comes to protecting service entrance equipment, feeder circuits, and circuit breakers, A4BY fuses have been the industry’s favorite. The A4BY is a 100% rated device and may be applied at continuous currents up to its ampere rating. A 4-second minimum time delay at 500% rating allows the A4BY to pass normal current surges and to coordinate with ground fault relays.
B
Features/Benefits ➤ Unique dimensions prevent replacement by other fuse classes ➤ Blade stamped catalog numbers for permanent identification ➤ Glass melamine body and plated terminals provide superior reliability in harsh environments
HIGHLIGHTS:
Applications:
➤ Current-Limiting ➤ 4-Second Time Delay ➤ DC Ratings ➤ Uniform Characteristics in all Ampere Ratings
➤ Mains, Feeders ➤ Circuit Breakers ➤ Loadcenters ➤ Panelboards ➤ Switchboards ➤ Metering Centers
Ratings ➤ AC: 200 to 6,000A 600VAC,200kA I.R. ➤ DC: 200 to 2500A 300VDC, 100kA I.R.
Approvals ➤ UL Listed to Standard 248-10 (601-6000A) File E2137 ➤ CSA Certified to Standard C22.2 No. 248.10 (601-6000A) ➤ Ferraz Shawmut Certified for DC per UL248 (601-6000A)
Indicators Optional built-in fuse indicators (-TI) are available. Consult factory.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 17
AMP-TRAP速
Class L Fuses
A4BY
Standard Fuse Ampere Ratings, Catalog Numbers AMPERE RATING
CATALOG NUMBER
AMPERE RATING
CATALOG NUMBER
AMPERE RATING
CATALOG NUMBER
A4BY200 A4BY250 A4BY300 A4BY350 A4BY400 A4BY450 A4BY500 A4BY600 A4BY601 A4BY650 A4BY700 A4BY750 A4BY800
801 900 1000 1100 1200 1201 1350 1400 1500 1600 1601 1800
A4BY801 A4BY900 A4BY1000 A4BY1100 A4BY1200 A4BY1201 A4BY1350 A4BY1400 A4BY1500 A4BY1600 A4BY1601 A4BY1800
2000 2001 2200 2500 3000 3001 3500 4000 4001 4500 5000 6000
A4BY2000 A4BY2001 A4BY2200 A4BY2500 A4BY3000 A4BY3001 A4BY3500 A4BY4000 A4BY4001 A4BY4500 A4BY5000 A4BY6000
200 250 300 350 400 450 500 600 601 650 700 750 800
2001-3000A
3001-4000A
4001-6000A
200-800A
801-2000A
Dimensions AMPERE RATING
In.
200-600 601-800 801-1200 1201-1600 1601-2000 2001-2500 2501-3000 3001-4000 4001-5000 5001-6000
8-5/8 8-5/8 10-3/4 10-3/4 10-3/4 10-3/4 10-3/4 10-3/4 10-3/4 10-3/4
A mm 219 219 273 273 273 273 273 273 273 273
B In. mm 2 2-1/2 2-1/2 3 3-1/2 4-1/2 5 5-3/4 6-1/4 7-1/8
51 63 63 76 89 114 127 146 159 181
C In. 5/16 3/8 3/8 7/16 1/2 3/4 3/4 3/4 1 1
mm 8 9 9 11 13 19 19 19 25 25
D In. 1-5/8 2 2 2-3/8 2-3/4 3-1/2 4 4-3/4 5-1/4 5-3/4
mm 41 51 51 60 70 89 102 121 133 146
In. 2-13/32 2-13/32 3-15/32 3-15/32 3-15/32 3-15/32 3-15/32 3-15/32 3-15/32 3-15/32
E mm 61 61 88 88 88 88 88 88 88 88
Safety Note: Class L fuses are dimensioned for one-way interchangeability. A Class L fuse of any lower ampere rating can be substituted for a given Class L fuse.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 18
AMP-TRAP®
Class L Fuses
A4BY
Melting Time – Current Data, 600V Fuses
A4BY200 to 6000
Current in Amperes
B
Time in Seconds
Maximum Instantaneous Peak Let-Thru Amperes
Peak Let-Thru Current Data – A4BY300 to 6000, 600 Volts AC
Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 19
AMP-TRAP®
A4BT
TIME DELAY/CLASS L when your heavier loads need protection a4BT fuses won’t let you down The high interrupting rating of A4BT current limiting fuses is ideally suited for protecting mains, feeders, and general circuits. The 10-second time delay at 500% of fuse rating is ideal for large motors and other loads with a high inrush. A4BT fuses are suitable for DC applications up to 500VDC. An A4BT fuse can be applied to normal loads up to its full ampere rating to allow 100% rating of equipment. Features/Benefits ➤ Unique dimensions prevent replacement by other fuse classes. ➤ Blade-stamped catalog numbers for permanent identification ➤ Glass melamine body and plated terminals provide superior reliability in harsh environments
HIGHLIGHTS:
Applications:
➤ Current-Limiting ➤ Full 10-Second Delay ➤ DC Ratings ➤ Uniform Characteristics in all Ampere Ratings
➤ Motors ➤ Motor Controllers ➤ Transformers ➤ Mains ➤ Feeders
Ratings ➤ AC: 200 to 2,000A 600VAC, 200kA I.R. ➤ DC: 200 to 2,000A 500VDC, 100kA I.R.
Approvals ➤ UL Listed to Standard 248-10 (601-2000A) File E2137 ➤ CSA Certified to Standard C22.2 No. 248.10 (601-2000A) ➤ Ferraz Shawmut Certified for DC per UL248 (601-2000A)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 20
AMP-TRAP速
Time Delay/Class L Fuses
A4BT
Standard Fuse Ampere Ratings, Catalog Numbers AMPERE RATING
CATALOG NUMBER
AMPERE RATING
CATALOG NUMBER
AMPERE RATING
CATALOG NUMBER
A4BT200 A4BT250 A4BT300 A4BT350 A4BT400 A4BT450 A4BT500 A4BT600
601 650 700 750 800 900 1000
A4BT601 A4BT650 A4BT700 A4BT750 A4BT800 A4BT900 A4BT1000
1100 1200 1400 1500 1600 1800 2000
A4BT1100 A4BT1200 A4BT1400 A4BT1500 A4BT1600 A4BT1800 A4BT2000
200 250 300 350 400 450 500 600
200-800A
B
801-2000A
Dimensions AMPERE A RATING In. 200-600* 8-5/8 601-800 8-5/8 801-1200 10-3/4 1201-1600 10-3/4 1601-2000 10-3/4
B C mm In. mm In. mm 219 219 273 273 273
2 2-1/2 2-1/2 3 3-1/2
51 63 63 76 89
5/16 3/8 3/8 7/16 1/2
8 9 9 11 13
D In. mm 1-5/8 2 2 2-3/8 2-3/4
41 51 51 60 70
E In. mm 2-13/32 2-13/32 3-15/32 3-15/32 3-15/32
61 61 88 88 88
Safety Note: Class L fuses are dimensioned for one-way interchangeability. A Class L fuse of any lower ampere rating can be substituted for a given Class L fuse.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 21
AMP-TRAP®
Time delay/Class l Fuses
A4BT
Current in Amperes
Melting Time – Current Data, 600V AC/500V DC Fuses
A4BT200 to 2000
Time in Seconds
Maximum Instantaneous Peak Let-Thru Amperes
Peak Let-Thru Current Data – A4BT300 to 2000, 600 Volts AC
Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 22
AMP-TRAP®
A3T & A6T
fasT acting/CLASS T tHEse small dimension fuses are the right fit... for a tight fit Fast acting A3T and A6T Class T fuses combine two highly desirable features -- high current limitation and a small physical size. Their unique dimensions prevent the substitution of other fuses with lower voltage ratings or current limiting capability. These fuses have glass melamine bodies for superior dimensional stability and catalog numbers stamped into the blades for permanent identification.
B
Features/Benefits ➤ Extremely current limiting for low peak let-thru current ➤ Unique dimensions prevent replacement by other fuse classes ➤ Blade-stamped catalog numbers for permanent identification ➤ Small physical size for greater design flexibility
HIGHLIGHTS:
Applications:
➤ Fast Acting ➤ Extremely Current Limiting ➤ Small Physical Size ➤ DC Ratings
➤ Loadcenters ➤ Panelboards ➤ Switchboards ➤ Circuit Breakers ➤ Metering Centers
Recommended Fuse Blocks With Box Connectors for Amp-trap Class T Fuses
Ratings ➤ A3T AC:1 to 1200A 300VAC, 200kA I.R. DC: 1 to 1200A 160VDC, 50kA I.R. ➤ A6T AC: 1 to 800A 600VAC, 200kA I.R. DC: 1 to 800A 300VDC, 100kA I.R.
Approvals ➤ UL Listed to Standard 248-15 File E2137 ➤ CSA Certified to Standard C22.2 No. 248.15 ➤ DC Listed to UL Standard 248
Catalog Number Ampere Rating 30 60 100 200 400 600
1-pole 30306T 30606T 31031T 32031T 34031T 36031T
300V
600V 3-pole
1-pole
3-pole
30308T 30608T 31033T 32033T 34033T
60306T 60606T 61031T 62031T 64031T 66031T
60308T 60608T 61033T 62033T – –
–
A variety of pole configurations and termination provisions are available. Refer to the fuse block section of this catalog for details. Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 23
AMP-TRAP速
fast acting/Class t Fuses
A3T & A6T
Standard Fuse Ampere Ratings, Catalog Numbers Ampere Catalog Number Rating 300V 600V 1 A3T1 A6T1 3 A3T3 A6T3 6 A3T6 A6T6 10 A3T10 A6T10 15 A3T15 A6T15 20 A3T20 A6T20 25 A3T25 A6T25 30 A3T30 A6T30 35 A3T35 A6T35 40 A3T40 A6T40 45 A3T45 A6T45 50 A3T50 A6T50
Ampere Catalog Number Rating 300V 600V
Ampere Catalog Number Rating 300V 600V
60 70 80 90
A3T60 A3T70 A3T80 A3T90
A6T60 A6T70 A6T80 A6T90
300 350 400 450
A3T300 A3T350 A3T400 A3T450
A6T300 A6T350 A6T400 A6T450
100 110 125 150
A3T100 A3T110 A3T125 A3T150
A6T100 A6T110 A6T125 A6T150
500 600 700 800
A3T500 A3T600 A3T700 A3T800
A6T500 A6T600 A6T700 A6T800
175 200 225 250
A3T175 A3T200 A3T225 A3T250
A6T175 A6T200 A6T225 A6T250
1000 1200
A3T1000 A3T1200
A3T
A6T
A3T 1-60 A6T 1-30
A6T 31-60
A3T 61-1200
Dimensions
A6T 61-800
AMPERE RATING A3T 1-30 31-60 61-100 101-200
In.
mm
In.
mm
In.
mm
In.
mm
In.
mm
.88 .88 2.16 2.44
22.4 22.4 54.9 62.0
.41 .56 .81 1.06
10.3 14.1 20.6 26.9
- - .12 .19
- - 3.2 4.8
- - .75 .88
- - 19.0 22.4
- - 1.56 1.70
- - 39.6 43.2
201-400 401-600 601-800 801-1200
2.75 3.06 3.38 4.00
69.8 77.7 85.8 102
1.33 1.62 2.08 2.52
33.8 41.1 52.8 64.0
.25 .31 .38 .44
6.4 7.8 9.7 11.2
1.00 1.25 1.75 2.00
25.4 31.8 44.4 50.8
1.84 2.03 2.22 2.53
A6T 1-30 31-60 61-100 101-200
1.50 1.57 2.95 3.26
38.1 39.9 75.0 82.8
.57 .81 .82 1.07
14.5 20.6 20.8 27.2
- 1.51 .12 .19
- 38.4 3.2 4.8
- 1.00 .75 .88
- 25.4 19.0 22.4
201-400 401-600 601-800
3.62 3.98 4.33
92.1 101.2 110.0
1.62 2.06 2.50
41.3 52.4 63.5
.25 .31 .37
6.4 7.9 9.5
1.00 1.25 1.75
25.4 31.8 44.4
A
B
C
D
F
G In.
J mm
In.
mm
- - .28 .34
- - 7.1 8.6
- - .82 .83
- 20.8 21.1
46.7 51.6 56.4 64.3
.41 .48 .55 .61
10.4 12.2 14.0 15.5
.84 .84 .88 1.03
21.3 21.3 22.4 26.2
- - 2.35 2.51
- - 59.7 63.7
- - .28 .34
- - 7.1 8.6
- - 1.58 1.61
40.1 41.0
2.72 2.95 3.17
69.1 75.0 80.5
.41 .48 .56
10.4 12.2 14.1
1.70 1.70 1.70
43.2 43.2 43.2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 24
AMP-TRAP®
fast acting/Class t Fuses
A3T & A6T
Melting Time – Current Data, 300V Fuses
A3T30 to 1200
Current in Amperes
B
Time in Seconds
Maximum Instantaneous Peak Let-Thru Amperes
Peak Let-Thru Current Data – A3T30 to 1200, 300 Volts AC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 25
AMP-TRAP®
fast acting/Class t Fuses
A3T & A6T
Current in Amperes
Melting Time – Current Data, 600V Fuses
A6T1 to 800
Time in Seconds
Maximum Instantaneous Peak Let-Thru Amperes
Peak Let-Thru Current Data – A6T30 to 800, 600 Volts AC
Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 26
AMP-TRAP®
A2K & A6K
class RK1
tHESE FAST-ACTING FUSES DELIVER A HIGH DEGREE OF CURRENT LIMITATION WHERE YOU NEED IT MOST Current-limiting A2K and A6K fuses provide excellent protection where high available short circuit currents exist. These fast-acting fuses are particularly good for branch/feeder circuits and back-up protection.
B
Features/Benefits ➤ Rejection style design prevents replacement by other fuse classes ➤ Fiberglass body provides dimensional stability in harsh industrial environments ➤ Easy-to-read imprint label for quick recognition and replacement ➤ High degree of current limitation for low peak let-thru current
HIGHLIGHTS:
Applications:
➤ Highly Current-Limiting ➤ Fast Acting ➤ Rejection Style
➤ Loadcenters ➤ Panelboards ➤ Switchboards ➤ Bus Duct ➤ Feeder Circuits ➤ Non-inductive Loads ➤ Lighting Circuits
Ratings
Approvals
➤ A2K AC: 1 to 600A 250VAC, 200kAI.R. DC: 1 to 600A 250VDC, 200kA I.R.
➤ UL Listed to Standard 248-12 File E2137
➤ A6K AC: 1 to 600A 600VAC, 200kA I.R. DC: 1 to 600A 300VDC, 20kA I.R.
➤ Ferraz Shawmut Certified for DC per UL248
➤ CSA Certified to Standard C22.2 No. 248.12
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 27
AMP-TRAP速
fast acting/Class rk1 Fuses
A2k & A6k
Standard Fuse Ampere Ratings, Catalog Numbers Ampere Catalog Number Rating 250V 600V 1 A2K1R A6K1R 3 A2K3R A6K3R 4 - A6K4R 5 A2K5R A6K5R 6 A2K6R A6K6R 8 - A6K8R 10 A2K10R A6K10R 12 A2K12R - 15 A2K15R A6K15R 20 A2K20R A6K20R 25 A2K25R A6K25R 30 A2K30R A6K30R
Ampere Catalog Number Rating 250V 600V
Ampere Catalog Number Rating 250V 600V
35 40 45 50
A2K35R A2K40R A2K45R A2K50R
A6K35R A6K40R A6K45R A6K50R
175 200 225 250
A2K175R A2K200R A2K225R A2K250R
A6K175R A6K200R A6K225R A6K250R
60 70 80 90
A2K60R A2K70R A2K80R A2K90R
A6K60R A6K70R A6K80R A6K90R
300 350 400 450
A2K300R A2K350R A2K400R A2K450R
A6K300R A6K350R A6K400R A6K450R
100 110 125 150
A2K100R A2K110R A2K125R A2K150R
A6K100R A6K110R A6K125R A6K150R
500 600
A2K500R A2K600R
A6K500R A6K600R
Recommended Fuse Blocks With Box Connectors For Amp-trap Class RK1 Fuses Fuse
Catalog Number Ampere 250V 600V Rating 1 Pole 3 pole 1 pole 3 pole
0-60A
0-30 31-60 61-100 101-200 201-400 401-600
20306R 20606R 21036R 22001R 24001R 2631R
20308R 20608R 21038R 22003R 24003R 2633R
60306R 60606R 61036R 62001R 64001R 6631R
60308R 60608R 61038R 62003R 64003R 6633R
A variety of pole configurations and termination provisions are available. Refer to the fuse block section of this catalog for details.
61-600A
Dimensions A AMPERE RATING In. mm 250V-A2K FUSES 0-30 2 51 31-60 3 76 61-100 5-7/8 149 101-200 7-1/8 181 201-400 8-5/8 219 401-600 10-3/8 264 600V-A6K FUSES 0-30 5 127 31-60 5-1/2 139 61-100 7-7/8 200 101-200 9-5/8 244 201-400 11-5/8 295 401-600 13-3/8 340
In.
B mm
In.
C mm
In.
D mm
In.
E mm
9/16 13/16 1-1/16 1-9/16 2-1/16 2-9/16
14 21 27 40 53 66
- - 1/8 3/16 1/4 1/4
- - 3 5 6 6
- - 3/4 1-1/8 1-5/8 2
- - 19 28 41 51
- - 1 1-3/8 1-7/8 2-1/4
25 35 48 57
13/16 1-1/16 1-5/16 1-13/16 2-9/16 3-1/8
21 27 34 46 66 80
- - 1/8 3/16 1/4 1/4
- - 3 5 6 6
- - 3/4 1-1/8 1-5/8 2
- - 19 28 41 51
- - 1 1-3/8 1-7/8 2-1/4
25 35 48 57
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 28
AMP-TRAP®
FAST ACTING/CLASS RK1 FUSES
A2K & A6K
Melting Time – Current Data, 250V Fuses
A2K30 to 600
Current in Amperes
B
Time in Seconds
Maximum Instantaneous Peak Let-Thru Amperes
Peak Let-Thru Current Data – A2K30 to 600, 250 Volts AC
Available Current in RMS Symmetrical Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 29
AMP-TRAP®
FAST ACTING/CLASS RK1 FUSES
A2K & A6K
Current in Amperes
Melting Time – Current Data, 600V Fuses
A6K30 to 600
Time in Seconds
Maximum Instantaneous Peak Let-Thru Amperes
Peak Let-Thru Current Data – A6K30 to 600, 600 Volts AC
Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 30
AMP-TRAP®
HSRK
high speed/class rk1 High speed rk1 (HSRK) Protect your electrical power wiring and power semiconductors with a single fuse. The new HIGH SPEED RK1 (HSRK) combines semiconductor fuse performance with NEC branch circuit compliance. The fuse was designed with two specific applications in mind: 1. To provide semiconductor fuse performance to solid state drive applications but in the larger RK body sizes that have been typically installed in older systems. 2. To provide industrial power applications with the most current limiting fuse available, which in turn provides the best arc flash mitigation available to power systems using the larger RK size fuses.
B
Features/Benefits
Highlights:
Applications:
➤ Current Limiting ➤ Low I2t ➤ Drive protection in larger RK body sizes for older installations ➤ Fast acting
➤ Branch circuits ➤ AC drives ➤ Solid state controllers ➤ Feeder circuits ➤ Arc flash mitigation
➤ Most current limiting RK1 available ➤ Provides the best Arc flash mitigation for feeder and branch circuits (non motor load circuits) ➤ Excellent cycling ability for frequent drive starts and stops without nuisance opening ➤ Extremely Low I2t
Ratings ➤ AC: (70 to 600A) 600VAC, 200KA I.R. ➤ 300KA I.R. Self certified
Approvals HSRK (70 to 600A) ➤ UL listed to 248-12 File E2137 ➤ CSA certified to C22.2 - No. 248.12
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 31
Amp-trap速
HIGH SPEED/CLASS RK1 Standard Fuse Ampere Ratings, Catalog Numbers Ampere Rating
Catalog # 600V
Ampere Rating
Catalog # 600V
200 225 250 300 350 400 450 500 600
HSRK200R HSRK225R HSRK250R HSRK300R HSRK350R HSRK400R HSRK450R HSRK500R HSRK600R
70 HSRK70R 80 HSRK80R 90 HSRK90R 100 HSRK100R 110 HSRK110R 125 HSRK125R 150 HSRK150R 175 HSRK175R
HSRK
Recommended Fuse Blocks With Box Connectors For Amp-trap速 Class RK1 Fuses Fuse Catalog Number Ampere 600V Rating 1 pole 3 pole 61-100 61036R 61038R 101-200 62001R 62003R 201-400 64001R 64003R 401-600 6631R 6633R A variety of pole configurations and termination provisions are available. Refer to the fuse block section of this catalog for details.
70-600A
Dimensions AMPERE RATING In. 600V-HSRK FUSES 61-100 101-200 201-400 401-600
7-7/8 9-5/8 11-5/8 13-3/8
A
mm 200 244 295 340
B In. mm 1-5/16 1-13/16 2-9/16 3-1/8
34 46 66 80
C In. mm 1/8 3/16 1/4 1/4
3 5 6 6
D In.
mm
E In.
3/4 1-1/8 1-5/8 2
19 28 41 51
1 1-3/8 1-7/8 2-1/4
mm 25 35 48 57
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 32
Amp-trap速
HIGH SPEED/CLASS RK1
HSRK
I2t Data HSRK (Amp Rating)R Max Clearing I2t @ 600V AC
Ampere Rating (A)
Pre-arc (A2s X 103)
70
1.2
14
80
1.6
17
B
(A2s X 103)
90
2.3
24
100
2.7
26
110
2.3
23
125
3.4
32
150
5.1
45
175
8.0
65
200
14
100
225
14
110
250
16
130
300
26
200
350
37
290
400
63
450
450
67
500
500
98
600
600
141
900
Watts Loss vs % Rated Current
Correction Factor for l2t
Correction Factor for Watts Loss
I2t vs Working Voltage
Working Voltage (AC RMS Volts)
% Rated Current
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 33
Amp-trap®
HIGH SPEED/CLASS RK1 Ampere Rating (A)
Watts Loss at Rated Current
70
10
80
11
90
13
100
14
110
18
125
19
150
25
175
26
200
27
225
35
250
43
300
45
350
47
400
53
450
62
500
63
600
83
Peak Let-Thru Data HSRK70 — 600R, 600V AC
Maximum Peak Let-Thru Current (A)
Watts Loss Data HSRK70 — 600R, 600V AC
HSRK
60Hz RMS Symmetrcal Prosective Current (A)
Prearcing Time(s)
Prearcing Time(s)
Melting Time — Current Data HSRK70 — 600R, 600V AC
Prearc Current (A RMS)±8%
Prearc Current (A RMS)±8%
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 34
AMP-TRAP®
AG
class G
amp-trap ag fuses fit right in to a wide variety of industrial applications The Ferraz Shawmut Amp-trap AG fuse series is a complete line of Class G fuses. AG fuses safely fit a wide variety of applications. Class G fuses are made in four physical sizes and provide good branch-circuit protection for lighting, heating, and appliance circuits.
B
Features/Benefits ➤ Four unique sizes from ½-60 amperes do not allow inter-changeability with other fuse classes ➤ Fiberglass bodies provide dimensional stability in harsh industrial settings
HIGHLIGHTS:
Applications:
➤ Current-Limiting ➤ Time Delay (above 5A)
➤ Lighting ➤ Heating* ➤ Appliances ➤ Branch Circuits * Except in Canada, where fuses must be “P” or “D” type.
Standard Fuse Ampere Ratings, Catalog Numbers AMPERE RATING 1/2 1 1-1/2 2 3 4 5 6 8 10
CATALOG NUMBER
AMPERE RATING
CATALOG NUMBER
AG1/2 AG1 AG1-1/2 AG2 AG3
15 20 25 30 35
AG15 AG20 AG25 AG30 AG35
AG4 40 AG5 45 AG6 50 AG8 60 AG10
AG40 AG45 AG50 AG60
Ratings
Approvals
➤ AC: 1/2 to 20A 600VAC, 100K A I.R. 25 to 60A, 480VAC, 100k A I.R.
➤ UL Listed to Standard 248-5 File E2137 ➤ CSA Certified to Standard C22.2 No. 248.5
Dimensions
AMPERE A B C RATING In. mm In. mm In. mm
1/2-15A
1.31
33.3
.406
10.3
.28
7.1
20A
1.41
35.8
.406
10.3
.28
7.1
25, 30A
1.62
41.2
.406
10.3
.28
7.1
35-60A
2.25
57.2
.406
10.3
.50
12.7
Cross Reference: AG will replace the following fuses: Bussmann SC, Littelfuse SLC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 35
AMP-TRAP®
Time Delay/Class g Fuses
ag
Current in Amperes
Melting Time – Current Data, 480V Fuses
AG1 to 10
Time in Seconds
Current in Amperes
Melting Time – Current Data, 480V Fuses
AG15 to 60
Maximum Instantaneous Peak Let-Thru Amperes
Time in Seconds Peak Let-Thru Current Data – AG1 to 60, 480 Volts AC
Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 36
AMP-TRAP®
ATMR
class CC SMALL FUSE - BIG PROTECTION FOR GENERAL CIRCUITS Amp-trap® ATMR fuses, in the Class CC family, are the smallest dimension 600VAC/DC fuses suitable for branch circuit protection. The ATMR is a popular choice for economical protection of control circuits and control circuit transformers where available short circuit currents exceed 10,000 amperes. ATMR’s rejection dimensions prevent substitution by lesser rated fuses. These fast acting fuses give current limiting protection to general circuits.
B
Features/Benefits ➤ Rejection style design prevents replacement errors when used with recommended fuse blocks ➤ Versatile design for individual component and branch circuit protection
HIGHLIGHTS:
Applications:
➤ Fast Acting ➤ Very Current-Limiting
➤ Control Circuits ➤ Lighting ➤ General Loads ➤ Branch Circuit Protection
Ratings ➤ AC: 1/10 to 30A 600VAC, 200kA I.R. ➤ DC: 1/10 to 30A 600VDC, 100kA I.R.
Approvals ➤ UL Listed to Standard 248-4 File E2137 ➤ CSA Certified to Standard C22.2 No. 248.4 ➤ DC Listed to ULStandard 248
Standard Fuse Ampere Ratings, Catalog Numbers AMPERE RATING
CATALOG NUMBER
AMPERE RATING
CATALOG NUMBER
1/10 1/8 2/10
ATMR1/10 ATMR1/8 ATMR2/10
3-1/2 4 5
ATMR3-1/2 ATMR4 ATMR5
1/4 3/10 1/2
ATMR1/4 ATMR3/10 ATMR1/2
6 7 8
ATMR6 ATMR7 ATMR8
3/4 1
ATMR3/4 ATMR1
9 10
ATMR9 ATMR10
1-1/4 1-1/2 2
ATMR1-1/4 ATMR-1-1/2 ATMR2
12 15 20
ATMR12 ATMR15 ATMR20
2-1/2 3
ATMR2-1/2 ATMR3
25 30
ATMR25 ATMR30
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 37
AMP-TRAP®
FAST ACTING/Class CC Fuses
aTMR
Recommended Fuse Blocks For Amp-Trap® Class CC Fuses
Dimensions
CATALOG NUMBER ULTRASAFE™ Screw Connector Pressure Plate Number of Indicating with Double Connector Poles Fuse Holders Quick Connects with Double Quick Connects ADDER 30310R 30320R 1 USCC1I 30311R 30321R 2 USCC2I 30312R 30322R 3 USCC3I 30313R 30323R 3 USFMCCI
Copper Box Connector
30350R 30351R 30352R 30353R
Refer to the Class CC Fuse Block section of this catalog for other details.
Current in Amperes
Melting Time – Current Data, 600V Fuses
ATMR1/10 to 30
Maximum Instantaneous Peak Let-Thru Amperes
Time in Seconds Peak Let-Thru Current Data – ATMR3/4 to 30, 600 Volts AC
Current in Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 38
ONE-TIME
OT/OTN/OTS
class K-5 for versatility and economy, these general purpose fuses are hard to beat OT, OTN and OTS general purpose fuses provide low cost protection for feeder and branch circuits serving lighting, heating, and other non-motor loads. OT, OTN and OTS fuses will safely interrupt available short circuit currents up to 50,000 amperes in all ratings.
B
OT, OTN and OTS fuses are not rejection fuses – care should be taken to ensure that replacement fuses do not have lower interrupting ratings than original fuses. OTN 15 through 60 satisfy the Canadian electrical code requirement for Type “P,” low melting-point, non-time delay fuses. Features/Benefits ➤ Easy to read imprint label for quick recognition and replacement ➤ Low cost for high protection value
HIGHLIGHTS:
Applications:
➤ Versatile ➤ Lowest cost protection for circuits serving non-inductive loads
➤ Feeders ➤ Branch Circuits ➤ Resistive Heating ➤ Residential and Small Commercial Installations
Ratings ➤ OT AC: 1 to 600A 250VAC, 50kA I.R. DC: 1 to 600A 250VDC, 20kA I.R. ➤ OTN (Canada) AC: 15 to 60A 250VAC, 50kA I.R. ➤ OTS AC: 1 to 600A 600VAC, 50kA I.R. DC: 1 to 600A 300VDC, 20kA I.R.
Approvals ➤ UL Listed to Standard 248-9 File E2137 ➤ CSA Certified to Standard C22.2 No. 248.9* ➤ Ferraz Shawmut Certified for DC per UL248
*The Canadian Electrical Code requires these fuses in ratings 15 through 60A to be of the low melting point design use OTN 15-60.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 39
ONE-TIME
general purpose/CLASS K-5 Fuses
ot/OTN/ots
Standard Fuse Ampere Ratings, Catalog Numbers Ampere Catalog Number Rating 250V 600V 1 OT1 OTS1 2 OT2 OTS2 3 OT3 OTS3 4 OT4 OTS4 5 OT5 OTS5 6 OT6 OTS6 7 OT7 – 8 OT8 OTS8 10 OT10 OTS10 12 OT12 OTS12 15 OT15, OTN15* OTS15 20 OT20, OTN20* OTS20 25 OT25, OTN 25* OTS25
Ampere Catalog Number Rating 250V 600V
Ampere Catalog Number Rating 250V 600V
30 35 40 45
OT30, OTN30* OT35, OTN35* OT40, OTN40* OT45, OTN45*
OTS30 OTS35 OTS40 OTS45
125 150 175 200
OT125 OT150 OT175 OT200
OTS125 OTS150 OTS175 OTS200
50 60 65 70
OT50, OTN 50* OT60, OTN60* OT65 OT70
OTS50 OTS60 – OTS70
225 250 300 350
OT225 OT250 OT300 OT350
OTS225 OTS250 OTS300 OTS350
75 80 90 100 110
OT75 OT80 OT90 OT100 OT110
OTS75 OTS80 OTS90 OTS100 OTS110
400 450 500 600
OT400 OT450 OT500 OT600
OTS400 OTS450 OTS500 0TS600
* In Canada
Recommended Fuse Blocks With Box Connectors For One-Time Class K-5 Fuses Fuse
Catalog Number Ampere 250V 600V Rating 1 Pole 3 pole 1 pole 3 pole
0-60A
Dimensions A AMPERE RATING In. 250V-OT, OTN FUSES 0-30 2 31-60 3 61-100 5-7/8 101-200 7-1/8 201-400 8-5/8 401-600 10-3/8 600V-OTS FUSES 0-30 5 31-60 5-1/2 61-100 7-7/8 101-200 9-5/8 201-400 11-5/8 401-600 13-3/8
0-30 31-60 61-100 101-200 201-400 401-600
20308 20608 21038 22003 24003 2633
60306 60606 61036 62001 64001 6631
60308 60608 61038 62003 64003 6633
A variety of pole configurations and termination provisions are available. Refer to the fuse block section of this catalog for details.
61-600A mm
20306 20606 21036 22001 24001 2631
B In. mm
C In.
mm
D In. mm
E In. mm
51 76 149 181 219 264
9/16 13/16 1-1/16 1-9/16 2-1/16 2-9/16
14 21 27 40 53 66
- - 1/8 3/16 1/4 1/4
- - 3 5 6 6
- - 3/4 1-1/8 1-5/8 2
- - 19 28 41 51
- - 1 1-3/8 1-7/8 2-1/4
25 35 48 57
127 139 200 244 295 340
13/16 1-1/16 1-5/16 1-13/16 2-9/16 3-1/8
21 27 34 46 66 80
- - 1/8 3/16 1/4 1/4
- - 3 5 6 6
- - 3/4 1-1/8 1-5/8 2
- - 19 28 41 51
- - 1 1-3/8 1-7/8 2-1/4
25 35 48 57
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 40
ONE-TIME
general purpose/CLASS K-5 Fuses
ot/OTN/ots
Current in Amperes
Melting Time – Current Data, 250V Fuses
OT30 to 600; OTN 30, 60
B
Time in Seconds
Current in Amperes
Melting Time – Current Data, 600V Fuses
OTS30 to 600
Time in Seconds
Maximum Instantaneous Peak Let-Thru Amperes
Peak Let-Thru Current Data – OT, OTN & OTS30 to 600, 250 and 600 Volts AC
Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 41
RENEWABLE
RF/RFS & RL/RLS
class H traditional protection for circuits with less than 10,000a SHORT CIRCUIT CURRENT RF and RFS general purpose fuses are suitable for application where available short circuit currents do not exceed 10,000 amperes. RF and RFS renewable fuses use matched RL and RLS die-cut zinc links from 1 to 600 amperes in 32 ratings.
Features/Benefits ➤ Knurled bushings for ease of disassembly ➤ Rugged construction for maximum service life ➤ Precision die-cut renewal links renew quickly and give repeatable performance
HIGHLIGHTS:
Applications:
➤ Renewable ➤ 32 Renewal Link Ratings
➤ General purpose loads where short circuits are 10,000 amperes or less
Ratings ➤ RF AC: 1 to 600A 250VAC, 10kA I.R. ➤ RFS AC: 1 to 600A 600VAC, 10kA I.R.
Approvals ➤ UL Listed to Standard 248-7 File E2137 ➤ CSA Certified to Standard C22.2 No. 248.7
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 42
RENEWABLE Class h Fuses/links
RF/rfS & rl/rls
Standard Fuse Ampere Ratings, Catalog Numbers Ampere Catalog Number Rating 250V 600V 1 RF1/RL1 RFS1/RLS1 2 RF2/RL2 RFS2/RLS2 3 RF3/RL3 RFS3/RLS3 5 RF5/RL5 RFS5/RLS5 6 RF6/RL6 RFS6/RLS6 10 RF10/RL10 RFS10/RLS10 15 RF15/RL15 RFS15RLS15 20 RF20/RL20 RFS20/RLS20 25 RF25/RL25 RFS25/RLS25 30 RF30/RL30 RFS30/RLS30 35 RF35/RL35 RFS35/RLS35 40 RF40/RL40 RFS40/RLS40
Ampere Catalog Number Rating 250V 600V 45 50 60 70 80 90
RF45/RL45 RF50/RL50 RF60/RL60 RF70/RL70 RF80/RL80 RF90/RL90
RFS45/RLS45 RFS50/RLS50 RFS60/RLS60 RFS70/RLS70 RFS80/RLS80 RFS90/RLS90
100 110 125 150 175 200
RF100/RL100 RF110/RL110 RF125/RL125 RF150/RL150 RF175/RL175 RF200/RL200
Ampere Catalog Number Rating 250V 600V 225 250 300 350 400 450
RF225/RL225 RF250/RL250 RF300/RL300 RF350/RL350 RF400/RL400 RF450/RL450
RFS225/RLS225 RFS250/RLS250 RFS300/RLS300 RFS350/RLS350 RFS400/RLS400 RFS450/RLS450
RFS100/RLS100 500 RFS110/RLS110 600 RFS125/RLS125 RFS150/RLS150 RFS175/RLS175 RFS200/RLS200
RF500/RL500 RF600/RL600
RFS500/RLS500 RFS600/RLS600
B
Recommended Fuse Blocks With Box Connectors For Renewable Class H Fuses Fuse
Catalog Number Ampere 250V 600V Rating 1 Pole 3 pole 1 pole 3 pole 0-30 31-60 61-100 101-200 201-400 401-600
20306 20606 21036 22001 24001 2631
20308 20608 21038 22003 24003 2633
60306 60606 61036 62001 64001 6631
60308 60608 61038 62003 64003 6633
0-60A
A variety of pole configurations and termination provisions is available. Refer to the fuseholder section of this catalog for details.
61-600A
Dimensions AMPERE RATING In. 250V-RF FUSES
0-30 2 31-60 3 61-100 5-7/8 101-200 7-1/8 201-400 8-5/8 401-600 10-3/8 600V-RFS FUSES 0-30 5 31-60 5-1/2 61-100 7-7/8 101-200 9-5/8 201-400 11-5/8 401-600 13-3/8
A mm
In.
B
mm
C In.
mm
D In. mm
E In. mm
51 76 149 181 219 264
9/16 13/16 1-1/16 1-9/16 2-1/16 2-9/16
14 21 27 40 54 66
- - 1/8 3/16 1/4 1/4
- - 3 5 6 6
- - 3/4 1-1/8 1-5/8 2
- - 18 28 41 51
- - 1 1-3/8 1-7/8 2-1/4
25 35 48 57
127 139 200 244 295 340
13/16 1-1/16 1-5/16 1-13/16 2-9/16 3-1/8
21 27 34 46 67 80
- - 1/8 3/16 1/4 1/4
- - 3 5 6 6
- - 3/4 1-1/8 1-5/8 2
- - 18 28 41 51
- - 1 1-3/8 1-7/8 2-1/4
25 35 48 57
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 43