Ferraz shawmut

Page 1

North American Power Fuses The most popular North American power fuses — to meet the most popular protection priorities.

Your problem: Today, you need a time-delay power fuse that can handle normal surges. Tomorrow, it’s a power fuse with a

• Class RK5 / Tri-onic® TR & TRS • DC-rated / Tri-onic® TRS-RDC

high interrupting rating and the added security of rejection dimen-

• Class J / Amp-trap® HSJ

sions. The day after that, one of those economical one-time power

• Class J / Amp-trap® A4J

fuses will do the trick. But where can you turn for all three?

• Class L / Amp-trap® A4BY

Our solution: Ferraz Shawmut’s comprehensive power fuse

• Class L / Amp-trap® A4BT

offering covers a complete range of applications and a complete

• Class T / Amp-trap® A3T & A6T

range of circuit-protection needs. Whether it’s the characteristics of our Tri-onic® time-delay fuses. The high current-limiting capacity of our original Amp-trap® power fuses. The cost-efficient protection of our One-Time fuses. Or some other application-specific power fuse solution.

• Class RK1 / Amp-trap® A2K & A6K • Class RK1/Amp-trap® HSRK • Class G / Amp-trap® AG • Class CC / Amp-trap® ATMR

Want more information fast? For more technical or applicationspecific information, please call our Power Fuse experts, at 978-462-6662; 416-252-9371 in Canada; or visit our website at us.ferrazshawmut.com.

• Class K-5 / OT, OTN & OTS One-time • Class H / RF/RFS & RL/RLS Renewable

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com


TRI-ONIC®

TR & TRS

Time Delay/Class RK5 The industry’s Most popular fuse for Motor circuit protection. Tri-onic® SmartSpot® fuses now provide a visual open fuse indicator. With advanced material technology added to the existing product the TR and TRS current limiting time delay fuses are engineered for overcurrent protection of motors and transformers, service entrance equipment, feeder and branch circuits. Tri-onic proven time delay characteristic safely handles harmless starting currents and inrush currents associated with today’s motors and transformers. Features/Benefits ➤ Solid State SmartSpot Indicator ➤ Time delay for motor start-ups and transformer inrush currents without nuisance opening ➤ Current limiting for low peak let-thru current ➤ Rejection-style design prevents replacement errors (when used with recommended fuse blocks) ➤ Easy-to-read label for quick recognition and replacement ➤ Metal-embossed date and catalog number for traceability and lasting identification ➤ Fiberglass body provides dimensional stability in harsh industrial settings ➤ High-grade silica filler ensures fast arc quenching and high current limitation

HIGHLIGHTS:

Applications:

➤ Time Delay ➤ Current Limiting ➤ AC & DC Rated

➤ Motor Circuits ➤ Mains ➤ Feeders ➤ Branch Circuits ➤ Transformers ➤ Service Entrance Equipment ➤ General-purpose Protection

Ratings

Approvals

➤ TR AC: 1/10 to 600A 250VAC, 200kA I.R.

➤ UL Listed to Standard 248-12 File E2137

➤ DC: 1/10 to 2 8/10A & 35 to 400A, 250VDC, 20kA I.R.; 3 to 30A & 450 to 600A, 160VDC, 20kA I.R.

➤ CSA Certified to Standard C22.2 No. 248.12 ➤ DC Listed to UL Standard 248 TRS only

➤ TRS AC: 1/10 to 600A 600VAC, 200kA I.R. ➤ DC: 1/10 to 12A, 600VDC, 20kA I.R.; 15 to 60A, 300VDC, 20kA I.R. 70 to 600A, 600VDC, 100kA I.R. Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B


TRI-ONIC速

Time Delay/Class RK5 Fuses

TR & TRS

Standard Fuse Ampere Ratings, Catalog Numbers Ampere Catalog Number Rating 250V 600V

Ampere Catalog Number Rating 250V 600V

Ampere Catalog Number Rating 250V 600V

1/10 15/100 2/10 3/10 4/10 1/2 6/10 8/10 1 1-1/8 1-1/4 1-4/10 1-6/10 1-8/10

TR1/10R TR15/100R TR2/10R TR3/10R TR4/10R TR1/2R TR6/10R TR8/10R TR1R TR1-1/8R TR1-1/4R TR1-4/10R TR1-6/10R TR1-8/10R

TRS1/10R TRS15/100R TRS2/10R TRS3/10R TRS4/10R TRS1/2R TRS6/10R TRS8/10R TRS1R TRS1-1/8R TRS1-1/4R TRS1-4/10R TRS1-6/10R TRS1-8/10R

3-1/2 4 4-1/2 5 5-6/10 6 6-1/4 7 8 9 10 12 15 17-1/2

TR3-1/2R TR4R TR4-1/2R TR5R TR5-6/10R TR6R TR6-1/4R TR7R TR8R TR9R TR10R TR12R TR15R TR17-1/2R

TRS3-1/2R TRS4R TRS4-1/2R TRS5R TRS5-6/10R TRS6R TRS6-1/4R TRS7R TRS8R TRS9R TRS10R TRS12R TRS15R TRS17-1/2R

50 60 70 75 80 90 100 110 125 150 175 200 225 250

TR50R TR60R TR70R TR75R TR80R TR90R TR100R TR110R TR125R TR150R TR175R TR200R TR225R TR250R

TRS50R TRS60R TRS70R TRS75R TRS80R TRS90R TRS100R TRS110R TRS125R TRS150R TRS175R TRS200R TRS225R TRS250R

2 2-1/4 2-1/2 2-8/10 3 3-2/10

TR2R TR2-1/4R TR2-1/2R TR2-8/10R TR3R TR3-2/10R

TRS2R TRS2-1/4R TRS2-1/2R TRS2-8/10R TRS3R TRS3-2/10R

20 25 30 35 40 45

TR20R TR25R TR30R TR35R TR40R TR45R

TRS20R TRS25R TRS30R TRS35R TRS40R TRS45R

300 350 400 450 500 600

TR300R TR350R TR400R TR450R TR500R TR600R

TRS300R TRS350R TRS400R TRS450R TRS500R TRS600R

B

Note: Indicator not available (1/10 - 7) amps.

0-60A 61-600A

Dimensions AMPERE A RATING In. 250V-TR FUSES 0-30 2 31-60 3 61-100 5-7/8 101-200 7-1/8 201-400 8-5/8 401-600 10-3/8 600V-TRS FUSES 0-30 5 31-60 5-1/2 61-100 7-7/8 101-200 9-5/8 201-400 11-5/8 401-600 13-3/8

mm

B In. mm

C In. mm

D In. mm

E In. mm

51 76 149 181 219 264

9/16 13/16 1-1/16 1-9/16 2-1/16 2-9/16

14 21 27 40 53 66

- - 1/8 3/16 1/4 1/4

- - 3 5 6 6

- - 3/4 1-1/8 1-5/8 2

- - 19 28 41 51

- - 1 1-3/8 1-7/8 2-1/4

25 35 48 57

127 139 200 244 295 340

13/16 1-1/16 1-5/16 1-13/16 2-9/16 3-1/8

21 27 34 46 66 80

- - 1/8 3/16 1/4 1/4

- - 3 5 6 6

- - 3/4 1-1/8 1-5/8 2

- - 19 28 41 51

- - 1 1-3/8 1-7/8 2-1/4

25 35 48 57

Recommended Fuse Blocks With Box Connectors For Tri-onic速 Class RK5 Fuses Fuse Catalog Number Ampere 250V 600V Rating 1 Pole 3 pole 1 pole 3 pole 0-30 31-60 61-100 101-200 201-400 401-600

20306R 20606R 21036R 22001R 24001R 2631R

20308R 20608R 21038R 22003R 24003R 2633R

60306R 60308R 60606R 60608R 61036R 61038R 62001R 62003R 64001R 64003R 6631R 6633R

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B


TRI-ONIC®

Time Delay/Class RK5 Fuses

TR & TRS

Current in Amperes

Melting Time – Current Data, 250V Fuses

TR15 to 600

Time in Seconds

Current in Amperes

Melting Time – Current Data, 250V Fuses

TR1/10 to 12

Time in Seconds Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B


TRI-ONIC®

Time Delay/Class RK5 Fuses

TR & TRS

Current in Amperes

Melting Time – Current Data , 600V Fuses

TRS15 to 600

B

Time in Seconds

Current in Amperes

Melting Time – Current Data. 600V Fuses

TRS1/10 to 12

Time in Seconds Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B


TRI-ONIC®

Time Delay/Class RK5 Fuses

TR & TRS

Maximum Instantaneous Peak Let-Thru Amperes

Peak Let-Thru Current Data ­– TR30 to 600, 250 Volts AC

Available Current in RMS Symmetrical Amperes

Maximum Instantaneous Peak Let-Thru Amperes

Peak Let-Thru Current Data ­– TRS15 to 600, 600 Volts AC

Note: See Application Information page L9 for All Motor and Transformer Tables.

Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B


tri-onic®

TRS-RDC

time delay/dc rated DC RATED FOR TOUGH DC APPLICATIONS The Tri-onic® DC fuse series is designed for DC circuit protection in surface and underground mines. The TRS-RDC is MSHA approved and meets the industry’s most severe third party requirements for 600VDC rated fuses.

B

The TRS-RDC is a time-delay fuse with essentially the same time-current characteristic as the standard Tri-onic®.

Features/Benefits ➤ DC rated for mine duty and other long time-constant applications ➤ Time delay for motor start-ups and high inrush loads without nuisance opening ➤ Rugged glass melamine body for superior ➤ Reliability in harsh environments

HIGHLIGHTS:

Applications:

➤ Time Delay ➤ DC Rated

➤ Mine Circuits ➤ Trailing Cables ➤ Pump Motors ➤ Rail Heaters

Ratings

Approvals

➤ DC: 1 to 30A 300VDC, 20kA I.R. (Consult Factory for Availability)

➤ MSHA Approval No. 28-26-0

➤ DC: 35 to 400A 600VDC, 20kA I.R.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B


TRI-ONIC®

Time Delay/600VDC Fuses

TRS-RDC

Standard Fuse Ampere Ratings, Catalog Numbers AMPERE RATING

CATALOG NUMBER

1/10 15/100 2/10 3/10 4/10 1/2 6/10 8/10 1 1-1/8

TRS1/10RDC TRS15/100RDC TRS2/10RDC TRS3/10RDC TRS4/10RDC TRS1/2RDC TRS6/10RDC TRS8/10RDC TRS1RDC TRS1-1/8RDC

AMPERE RATING

1-1/4 1-4/10 1-6/10 1-8/10 2 2-1/4 2-1/2 2-8/10 3 3-2/10

CATALOG NUMBER

AMPERE RATING

CATALOG NUMBER

AMPERE RATING

CATALOG NUMBER

AMPERE RATING

TRS1-1/4RDC TRS1-4/10RDC TRS1-6/10RDC TRS1-8/10RDC TRS2RDC TRS2-1/4RDC TRS2-1/2RDC TRS2-8/10RDC TRS3RDC TRS3-2/10RDC

3-1/2 4 4-1/2 5 5-6/10 6 6-1/4 8 9 10

TRS3-1/2RDC TRS4RDC TRS4-1/2RDC TRS5RDC TRS5-6/10RDC TRS6RDC TRS6-1/4RDC TRS8RDC TRS9RDC TRS10RDC

12 15 17-1/2 20 30 35 40 45 50 60

TRS12RDC TRS15RDC TRS17-1/2RDC TRS20RDC TRS30RDC TRS35RDC TRS40RDC TRS45RDC TRS50RDC TRS60RDC

70 80 90 100 125 150 175 200 250 300 400

CATALOG NUMBER TRS70RDC TRS80RDC TRS90RDC TRS100RDC TRS125RDC TRS150RDC TRS175RDC TRS200RDC TRS250RDC TRS300RDC TRS400RDC

0-60 Amperes 61-400 Amperes

Dimensions

AMPERE RATING 0-30 31-60 61-100 101-200 201-400

A In. mm 5 5-1/2 7-7/8 9-5/8 11-5/8

127 139 200 244 295

B In. mm 13/16 1-1/16 1-5/16 1-13/16 2-9/16

21 27 34 46 66

C In. mm - - 1/8 3/16 1/4

- - 3 5 6

D In. mm - - 3/4 1-1/8 1-5/8

- - 19 28 41

E In. mm - - 1 1-3/8 1-7/8

25 35 48

Current in Amperes

Melting Time – Current Data, 600V Fuses

TRS-RDC60 to 400

Time in Seconds Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B


AMP-TRAP®

HSJ

HIGH SPEED/CLASS J Protect your wiring and power semiconductors with a single fuse. The new High Speed J (HSJ) combines the low I2t of a semiconductor fuse and the branch circuit performance of a Class J UL listed fuse. This fuse was designed for the starting characteristics of solid state motor controllers. The HSJ can provide branch circuit protection per NEC requirements, as well as very low I2t for protection of power semiconductors such as Diodes, SCR’s, GTO’s and SSR’s.

B

Features/Benefits ➤ Optimized over-load capability for withstanding elevated levels of current during electronic motor controller starts ➤ Low I2t (low thermal energy) ➤ Excellent Cycling Ability for frequent starts/stops without nuisance opening

HIGHLIGHTS:

Applications:

➤ Current-Limiting ➤ AC & DC Ratings ➤ Low l2t ➤ Compact Size

➤ Branch Circuits ➤ Control Panels ➤ Electronic Motor Controllers ➤ Phase Controllers ➤ Drives ➤ Soft-Starters ➤ Solid State Relays

Ratings

Approvals

➤ AC: 1-600A 600VAC, 200kA I.R. 300kA I.R. Self Certified

HSJ (15 to 600A) ➤ UL Listed to Standard 248-8 File E2137

➤ DC: 15-600A 500VDC, 100kA I.R. L/R 10mS

➤ DC Listed to UL248 ➤ CSA Certified to Standard C22.2 No. 248.8

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B


AMP-TRAP速

HIGH SPEED/CLASS J

HSJ Recommended Fuse Blocks With Box Connectors for Amp-trap速 Class J Fuses

Standard Fuse Ampere Ratings, Catalog Numbers AMPERE RATING

CATALOG NUMBER

OUTLINE FIGURE

1

HSJ1

1

3

HSJ3

1

6

HSJ6

1

10

HSJ10

AMPERE RATING

CATALOG NUMBER

OUTLINE FIGURE

90

HSJ90

2

100

HSJ100

2

110

HSJ110

2

1

125

HSJ125

2

15

HSJ15

1

150

HSJ150

2

17-1/2

HSJ17-1/2

1

175

HSJ175

2

20

HSJ20

1

200

HSJ200

2

25

HSJ25

1

225

HSJ225

2

30

HSJ30

1

250

HSJ250

2

35

HSJ35

1

300

HSJ300

2

40

HSJ40

1

350

HSJ350

2

45

HSJ45

1

400

HSJ400

2

50

HSJ50

1

450

HSJ450

2

60

HSJ60

1

500

HSJ500

2

70

HSJ70

2

600

HSJ600

2

80

HSJ80

2

Fuse Catalog Number Ampere 600V OR LESS Rating 1 Pole 3 pole US3J1I US3J3I 0-30 31-60 US6J1I US6J3I 61-100 61036J 61038J 101-200 62001J 62003J 201-400 64031J 64033J 401-600 6631J 6633J A variety of pole configurations and termination provisions is available.

Dimensions Fig 1

Fig 2

AMPERE A RATING In. mm 15-30

2-1/4

B In. mm

57

13/16

21

C In. mm -

-

D In. mm -

-

E In. mm -

-

F In. mm -

-

G In. mm -

-

H In. mm -

-

31-60

2-3/8

60

1-1/16

27

-

-

-

-

-

-

-

-

-

-

-

-

61-100

4-4/8

117

1-1/8

29

1/8

3.2

3/4

19

1

25

3-5/8

92

3/8

10

9/32

7

101-200

5-3/4

146

1-5/8

41

3/16

4.8

1-1/8

29

1-3/8

35

4-3/8

111

3/8

10

9/32

7

201-400

7-1/8

181

2-1/8

54

1/4

6.3

1-5/8

41

1-7/8

48

5-1/4

133

17/32

13

13/32

10

401-600

8

203

2-1/2

64

3/8

9.5

2

51

2-1/8

54

6

152

11/16

18

17/32

13

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 10


AMP-TRAP速

HIGH SPEED/CLASS J

HSJ

I2t Data - 600 Volts AC, 100kA Max Clearing I2t @ Ampere 600V AC 100kA Rating Pre-Arc 1 Fuse 2 in Series (A2s x 103) (A2s x 103) (A2s x 103) (A) 15 0.02 0.36 0.15 17.5 0.03 0.45 0.19 20 0.04 0.58 0.24 25 0.08 1.2 0.50 30 0.16 2 0.84 35 0.16 1.5 0.63 40 0.27 2.3 1.0 45 0.32 3.3 1.4 50 0.44 5.5 2.3 60 0.72 8.0 3.4 70 1.2 12 5.0 80 1.6 15 6.3 90 2.3 21 8.8 100 2.7 23 9.7 110 2.3 21 10 125 3.4 29 14 150 5.1 41 20 175 8.0 60 29 200 14 92 44 225 14 110 53 250 16 130 62 300 26 200 96 350 37 290 139 400 63 450 216 450 67 500 240 500 98 600 288 600 141 900 432

Max Clearing I 2t @ 480V AC 100kA 1 Fuse 2 in Series (A2s x 103) (A2s x 103) 0.23 0.12 0.29 0.15 0.37 0.19 0.77 0.40 1.3 0.66 0.96 0.50 1.5 0.76 2.1 1.1 3.5 1.8 5.1 2.6 7.7 4.0 9.6 5.0 13 6.9 15 7.6 13.9 8 19 11 27 16 40 23 61 35 73 42 86 49 132 76 191 110 297 171 330 190 396 228 594 342

Clearing I2t vs Operating Voltage 1.0

Correction Factor for Watts Loss

Correction Factor for I2t

B

Watts Loss vs. % Rated Current

1.0 .8 110-600 AMP .6 .4 .2 0

Watts Loss at Rated Current 2.6 3.5 3.7 4 4.1 5.3 5.5 6 6.8 8.4 10 11 13 14 18 19 22 24 26 30 36 38 40 42 58 59 68

15-100 AMP 0

100

200

300

400

.8

.6

.4

.2

500 600

50

60

70

80

90

100

Operating Voltage (AC RMS Volts) Percent Rated Current Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com B 11


AMP-TRAP速

HIGH SPEED/CLASS J

HSJ

Maximum Instantaneous Peak Let-Thru Amperes

Peak Let-Thru Data - HSJ15 to 600, 600Volts AC

Available Current in RMS Symmetrical Amperes Clearing I2t at 500 VDC 100kA, L/R = 10mS CLEARING I2t @ 500 VDC L/R = 10 ms (A2s X 103) 0.12 0.18 0.24 0.46 0.91 0.60 0.92 1.3 2.2 3.2 4.8 6.2 8.9 10 8.8 13 19 28 46 52 59 96 136 230 270 390 560

DC Voltage Capability

AMPERE RATING 15 17.5 20 25 30 35 40 45 50 60 70 80 90 100 110 125 150 175 200 225 250 300 350 400 450 500 600

DC Voltage vs. Time Constant

L/R Time Constant (mS)

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 12


AMP-TRAP速

HIGH SPEED/CLASS J

HSJ

Melting Time - Current Data, HSJ15 to 600, 600Volts AC

Time in Seconds

B

Time in Seconds

Available Current in RMS Symmetrical Amperes

Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 13


AMP-TRAP®

A4J

FAST ACTING/Class J For excellent CURRENT LIMITING PROTECTION A4J Class J fuses deliver excellent current-limiting protection to a wide variety of applications. Their unique dimensions prevent the substitution of other fuses with lower voltage ratings, interrupting ratings, or current-limiting capability.

Features/Benefits ➤ High current limitation for low peak let-thru current ➤ Unique dimensions prevent replacement by other fuse classes ➤ Fiberglass body provides dimensional stability in harsh industrial environments ➤ Easy-to-read imprint label for quick recognition and replacement

HIGHLIGHTS:

Applications:

Ratings

Approvals

➤ Fast Acting ➤ Very Current-Limiting ➤ DC Ratings

➤ Capacitors ➤ Loadcenters ➤ Panelboards ➤ Switchboards ➤ Bus Duct ➤ Feeder Circuits ➤ Circuit Breakers ➤ Lighting, Heating, and General Loads

➤ AC: 1 to 600A 600VAC, 200kA I.R.

➤ UL Listed to Standard 248-8 File E2137

➤ DC: 1 to 600A 300VDC, 100kA I.R.

➤ CSA Certified to Standard C22.2 No. 248.8 ➤ DC Listed to UL 248 ➤ IEC 269-2-1

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 14


AMP-TRAP速

fast acting/Class J Fuses

A4J

Standard Fuse Ampere Ratings, Catalog Numbers AMPERE RATING

CATALOG AMPERE NUMBER RATING

CATALOG AMPERE CATALOG NUMBER RATING NUMBER

1

A4J1

50

A4J50

200

A4J200

3

A4J3

60

A4J60

225

A4J225

6

A4J6

70

A4J70

250

A4J250

10

A4J10

75

A4J75

300

A4J300

15

A4J15

80

A4J80

350

A4J350

20

A4J20

90

A4J90

400

A4J400

25

A4J25

100

A4J100

450

A4J450

30

A4J30

110

A4J110

500

A4J500

35

A4J35

125

A4J125

600

A4J600

40

A4J40

150

A4J150

45

A4J45

175

A4J175

B

Recommended Fuse Blocks With Box Connectors for Amp-trap Class J Fuses Fuse

1-60A

61-600A

Ampere Rating

Catalog Number 600V OR LESS 1 Pole 3 pole

0-30 31-60 61-100 101-200 201-400 401-600

US3J1I US6J1I 61036J 62001J 64031J 6631J

US3J3I US6J3I 61038J 62003J 64033J 6633J

A variety of pole configurations and termination provisions are available. Refer to the fuse block section of this catalog for details.

Dimensions AMPERE A B C D E F G H RATING In. mm In. mm In. mm In. mm In. mm In. mm In. mm In. mm 1-30 2-1/4 57 13/16 21 - - - - - - - - - - - - 31-60 2-3/8 60 1-1/16 27 - - - - - - - - - - - - 61-100 4-5/8 117 1-1/8 29 1/8 3.2 3/4 19 1 25 3-5/8 92 3/8 10 9/32 7 101-200 5-3/4 146 1-5/8 41 3/16 4.8 1-1/8 29 1-3/8 35 4-3/8 111 3/8 10 9/32 7 201-400 7-1/8 181 2-1/8 54 1/4 6.3 1-5/8 41 1-7/8 48 5-1/4 133 17/32 13 13/32 10 401-600 8 203 2-1/2 64 3/8 9.5 2 51 2-1/8 54 6 152 11/16 18 17/32 13

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 15


AMP-TRAP®

fast acting/Class J Fuses

A4J

Current in Amperes

Melting Time –  Current Data, 600V Fuses

A4J30 to 600

Time in Seconds

Maximum Instantaneous Peak Let-Thru Amperes

Peak Let-Thru Current Data ­– 30 to 600, 600 Volts AC

Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 16


AMP-TRAP®

A4BY

CLASS l count on the high interrupting rating of our most widely-used class L fuse When it comes to protecting service entrance equipment, feeder circuits, and circuit breakers, A4BY fuses have been the industry’s favorite. The A4BY is a 100% rated device and may be applied at continuous currents up to its ampere rating. A 4-second minimum time delay at 500% rating allows the A4BY to pass normal current surges and to coordinate with ground fault relays.

B

Features/Benefits ➤ Unique dimensions prevent replacement by other fuse classes ➤ Blade stamped catalog numbers for permanent identification ➤ Glass melamine body and plated terminals provide superior reliability in harsh environments

HIGHLIGHTS:

Applications:

➤ Current-Limiting ➤ 4-Second Time Delay ➤ DC Ratings ➤ Uniform Characteristics in all Ampere Ratings

➤ Mains, Feeders ➤ Circuit Breakers ➤ Loadcenters ➤ Panelboards ➤ Switchboards ➤ Metering Centers

Ratings ➤ AC: 200 to 6,000A 600VAC,200kA I.R. ➤ DC: 200 to 2500A 300VDC, 100kA I.R.

Approvals ➤ UL Listed to Standard 248-10 (601-6000A) File E2137 ➤ CSA Certified to Standard C22.2 No. 248.10 (601-6000A) ➤ Ferraz Shawmut Certified for DC per UL248 (601-6000A)

Indicators Optional built-in fuse indicators (-TI) are available. Consult factory.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 17


AMP-TRAP速

Class L Fuses

A4BY

Standard Fuse Ampere Ratings, Catalog Numbers AMPERE RATING

CATALOG NUMBER

AMPERE RATING

CATALOG NUMBER

AMPERE RATING

CATALOG NUMBER

A4BY200 A4BY250 A4BY300 A4BY350 A4BY400 A4BY450 A4BY500 A4BY600 A4BY601 A4BY650 A4BY700 A4BY750 A4BY800

801 900 1000 1100 1200 1201 1350 1400 1500 1600 1601 1800

A4BY801 A4BY900 A4BY1000 A4BY1100 A4BY1200 A4BY1201 A4BY1350 A4BY1400 A4BY1500 A4BY1600 A4BY1601 A4BY1800

2000 2001 2200 2500 3000 3001 3500 4000 4001 4500 5000 6000

A4BY2000 A4BY2001 A4BY2200 A4BY2500 A4BY3000 A4BY3001 A4BY3500 A4BY4000 A4BY4001 A4BY4500 A4BY5000 A4BY6000

200 250 300 350 400 450 500 600 601 650 700 750 800

2001-3000A

3001-4000A

4001-6000A

200-800A

801-2000A

Dimensions AMPERE RATING

In.

200-600 601-800 801-1200 1201-1600 1601-2000 2001-2500 2501-3000 3001-4000 4001-5000 5001-6000

8-5/8 8-5/8 10-3/4 10-3/4 10-3/4 10-3/4 10-3/4 10-3/4 10-3/4 10-3/4

A mm 219 219 273 273 273 273 273 273 273 273

B In. mm 2 2-1/2 2-1/2 3 3-1/2 4-1/2 5 5-3/4 6-1/4 7-1/8

51 63 63 76 89 114 127 146 159 181

C In. 5/16 3/8 3/8 7/16 1/2 3/4 3/4 3/4 1 1

mm 8 9 9 11 13 19 19 19 25 25

D In. 1-5/8 2 2 2-3/8 2-3/4 3-1/2 4 4-3/4 5-1/4 5-3/4

mm 41 51 51 60 70 89 102 121 133 146

In. 2-13/32 2-13/32 3-15/32 3-15/32 3-15/32 3-15/32 3-15/32 3-15/32 3-15/32 3-15/32

E mm 61 61 88 88 88 88 88 88 88 88

Safety Note: Class L fuses are dimensioned for one-way interchangeability. A Class L fuse of any lower ampere rating can be substituted for a given Class L fuse.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 18


AMP-TRAP®

Class L Fuses

A4BY

Melting Time – Current Data, 600V Fuses

A4BY200 to 6000

Current in Amperes

B

Time in Seconds

Maximum Instantaneous Peak Let-Thru Amperes

Peak Let-Thru Current Data ­– A4BY300 to 6000, 600 Volts AC

Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 19


AMP-TRAP®

A4BT

TIME DELAY/CLASS L when your heavier loads need protection a4BT fuses won’t let you down The high interrupting rating of A4BT current limiting fuses is ideally suited for protecting mains, feeders, and general circuits. The 10-second time delay at 500% of fuse rating is ideal for large motors and other loads with a high inrush. A4BT fuses are suitable for DC applications up to 500VDC. An A4BT fuse can be applied to normal loads up to its full ampere rating to allow 100% rating of equipment. Features/Benefits ➤ Unique dimensions prevent replacement by other fuse classes. ➤ Blade-stamped catalog numbers for permanent identification ➤ Glass melamine body and plated terminals provide superior reliability in harsh environments

HIGHLIGHTS:

Applications:

➤ Current-Limiting ➤ Full 10-Second Delay ➤ DC Ratings ➤ Uniform Characteristics in all Ampere Ratings

➤ Motors ➤ Motor Controllers ➤ Transformers ➤ Mains ➤ Feeders

Ratings ➤ AC: 200 to 2,000A 600VAC, 200kA I.R. ➤ DC: 200 to 2,000A 500VDC, 100kA I.R.

Approvals ➤ UL Listed to Standard 248-10 (601-2000A) File E2137 ➤ CSA Certified to Standard C22.2 No. 248.10 (601-2000A) ➤ Ferraz Shawmut Certified for DC per UL248 (601-2000A)

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 20


AMP-TRAP速

Time Delay/Class L Fuses

A4BT

Standard Fuse Ampere Ratings, Catalog Numbers AMPERE RATING

CATALOG NUMBER

AMPERE RATING

CATALOG NUMBER

AMPERE RATING

CATALOG NUMBER

A4BT200 A4BT250 A4BT300 A4BT350 A4BT400 A4BT450 A4BT500 A4BT600

601 650 700 750 800 900 1000

A4BT601 A4BT650 A4BT700 A4BT750 A4BT800 A4BT900 A4BT1000

1100 1200 1400 1500 1600 1800 2000

A4BT1100 A4BT1200 A4BT1400 A4BT1500 A4BT1600 A4BT1800 A4BT2000

200 250 300 350 400 450 500 600

200-800A

B

801-2000A

Dimensions AMPERE A RATING In. 200-600* 8-5/8 601-800 8-5/8 801-1200 10-3/4 1201-1600 10-3/4 1601-2000 10-3/4

B C mm In. mm In. mm 219 219 273 273 273

2 2-1/2 2-1/2 3 3-1/2

51 63 63 76 89

5/16 3/8 3/8 7/16 1/2

8 9 9 11 13

D In. mm 1-5/8 2 2 2-3/8 2-3/4

41 51 51 60 70

E In. mm 2-13/32 2-13/32 3-15/32 3-15/32 3-15/32

61 61 88 88 88

Safety Note: Class L fuses are dimensioned for one-way interchangeability. A Class L fuse of any lower ampere rating can be substituted for a given Class L fuse.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 21


AMP-TRAP®

Time delay/Class l Fuses

A4BT

Current in Amperes

Melting Time – Current Data, 600V AC/500V DC Fuses

A4BT200 to 2000

Time in Seconds

Maximum Instantaneous Peak Let-Thru Amperes

Peak Let-Thru Current Data ­– A4BT300 to 2000, 600 Volts AC

Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 22


AMP-TRAP®

A3T & A6T

fasT acting/CLASS T tHEse small dimension fuses are the right fit... for a tight fit Fast acting A3T and A6T Class T fuses combine two highly desirable features -- high current limitation and a small physical size. Their unique dimensions prevent the substitution of other fuses with lower voltage ratings or current limiting capability. These fuses have glass melamine bodies for superior dimensional stability and catalog numbers stamped into the blades for permanent identification.

B

Features/Benefits ➤ Extremely current limiting for low peak let-thru current ➤ Unique dimensions prevent replacement by other fuse classes ➤ Blade-stamped catalog numbers for permanent identification ➤ Small physical size for greater design flexibility

HIGHLIGHTS:

Applications:

➤ Fast Acting ➤ Extremely Current Limiting ➤ Small Physical Size ➤ DC Ratings

➤ Loadcenters ➤ Panelboards ➤ Switchboards ➤ Circuit Breakers ➤ Metering Centers

Recommended Fuse Blocks With Box Connectors for Amp-trap Class T Fuses

Ratings ➤ A3T AC:1 to 1200A 300VAC, 200kA I.R. DC: 1 to 1200A 160VDC, 50kA I.R. ➤ A6T AC: 1 to 800A 600VAC, 200kA I.R. DC: 1 to 800A 300VDC, 100kA I.R.

Approvals ➤ UL Listed to Standard 248-15 File E2137 ➤ CSA Certified to Standard C22.2 No. 248.15 ➤ DC Listed to UL Standard 248

Catalog Number Ampere Rating 30 60 100 200 400 600

1-pole 30306T 30606T 31031T 32031T 34031T 36031T

300V

600V 3-pole

1-pole

3-pole

30308T 30608T 31033T 32033T 34033T

60306T 60606T 61031T 62031T 64031T 66031T

60308T 60608T 61033T 62033T – –

A variety of pole configurations and termination provisions are available. Refer to the fuse block section of this catalog for details. Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 23


AMP-TRAP速

fast acting/Class t Fuses

A3T & A6T

Standard Fuse Ampere Ratings, Catalog Numbers Ampere Catalog Number Rating 300V 600V 1 A3T1 A6T1 3 A3T3 A6T3 6 A3T6 A6T6 10 A3T10 A6T10 15 A3T15 A6T15 20 A3T20 A6T20 25 A3T25 A6T25 30 A3T30 A6T30 35 A3T35 A6T35 40 A3T40 A6T40 45 A3T45 A6T45 50 A3T50 A6T50

Ampere Catalog Number Rating 300V 600V

Ampere Catalog Number Rating 300V 600V

60 70 80 90

A3T60 A3T70 A3T80 A3T90

A6T60 A6T70 A6T80 A6T90

300 350 400 450

A3T300 A3T350 A3T400 A3T450

A6T300 A6T350 A6T400 A6T450

100 110 125 150

A3T100 A3T110 A3T125 A3T150

A6T100 A6T110 A6T125 A6T150

500 600 700 800

A3T500 A3T600 A3T700 A3T800

A6T500 A6T600 A6T700 A6T800

175 200 225 250

A3T175 A3T200 A3T225 A3T250

A6T175 A6T200 A6T225 A6T250

1000 1200

A3T1000 A3T1200

A3T

A6T

A3T 1-60 A6T 1-30

A6T 31-60

A3T 61-1200

Dimensions

A6T 61-800

AMPERE RATING A3T 1-30 31-60 61-100 101-200

In.

mm

In.

mm

In.

mm

In.

mm

In.

mm

.88 .88 2.16 2.44

22.4 22.4 54.9 62.0

.41 .56 .81 1.06

10.3 14.1 20.6 26.9

- - .12 .19

- - 3.2 4.8

- - .75 .88

- - 19.0 22.4

- - 1.56 1.70

- - 39.6 43.2

201-400 401-600 601-800 801-1200

2.75 3.06 3.38 4.00

69.8 77.7 85.8 102

1.33 1.62 2.08 2.52

33.8 41.1 52.8 64.0

.25 .31 .38 .44

6.4 7.8 9.7 11.2

1.00 1.25 1.75 2.00

25.4 31.8 44.4 50.8

1.84 2.03 2.22 2.53

A6T 1-30 31-60 61-100 101-200

1.50 1.57 2.95 3.26

38.1 39.9 75.0 82.8

.57 .81 .82 1.07

14.5 20.6 20.8 27.2

- 1.51 .12 .19

- 38.4 3.2 4.8

- 1.00 .75 .88

- 25.4 19.0 22.4

201-400 401-600 601-800

3.62 3.98 4.33

92.1 101.2 110.0

1.62 2.06 2.50

41.3 52.4 63.5

.25 .31 .37

6.4 7.9 9.5

1.00 1.25 1.75

25.4 31.8 44.4

A

B

C

D

F

G In.

J mm

In.

mm

- - .28 .34

- - 7.1 8.6

- - .82 .83

- 20.8 21.1

46.7 51.6 56.4 64.3

.41 .48 .55 .61

10.4 12.2 14.0 15.5

.84 .84 .88 1.03

21.3 21.3 22.4 26.2

- - 2.35 2.51

- - 59.7 63.7

- - .28 .34

- - 7.1 8.6

- - 1.58 1.61

40.1 41.0

2.72 2.95 3.17

69.1 75.0 80.5

.41 .48 .56

10.4 12.2 14.1

1.70 1.70 1.70

43.2 43.2 43.2

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 24


AMP-TRAP®

fast acting/Class t Fuses

A3T & A6T

Melting Time – Current Data, 300V Fuses

A3T30 to 1200

Current in Amperes

B

Time in Seconds

Maximum Instantaneous Peak Let-Thru Amperes

Peak Let-Thru Current Data ­– A3T30 to 1200, 300 Volts AC

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 25


AMP-TRAP®

fast acting/Class t Fuses

A3T & A6T

Current in Amperes

Melting Time – Current Data, 600V Fuses

A6T1 to 800

Time in Seconds

Maximum Instantaneous Peak Let-Thru Amperes

Peak Let-Thru Current Data ­– A6T30 to 800, 600 Volts AC

Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 26


AMP-TRAP®

A2K & A6K

class RK1

tHESE FAST-ACTING FUSES DELIVER A HIGH DEGREE OF CURRENT LIMITATION WHERE YOU NEED IT MOST Current-limiting A2K and A6K fuses provide excellent protection where high available short circuit currents exist. These fast-acting fuses are particularly good for branch/feeder circuits and back-up protection.

B

Features/Benefits ➤ Rejection style design prevents replacement by other fuse classes ➤ Fiberglass body provides dimensional stability in harsh industrial environments ➤ Easy-to-read imprint label for quick recognition and replacement ➤ High degree of current limitation for low peak let-thru current

HIGHLIGHTS:

Applications:

➤ Highly Current-Limiting ➤ Fast Acting ➤ Rejection Style

➤ Loadcenters ➤ Panelboards ➤ Switchboards ➤ Bus Duct ➤ Feeder Circuits ➤ Non-inductive Loads ➤ Lighting Circuits

Ratings

Approvals

➤ A2K AC: 1 to 600A 250VAC, 200kAI.R. DC: 1 to 600A 250VDC, 200kA I.R.

➤ UL Listed to Standard 248-12 File E2137

➤ A6K AC: 1 to 600A 600VAC, 200kA I.R. DC: 1 to 600A 300VDC, 20kA I.R.

➤ Ferraz Shawmut Certified for DC per UL248

➤ CSA Certified to Standard C22.2 No. 248.12

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 27


AMP-TRAP速

fast acting/Class rk1 Fuses

A2k & A6k

Standard Fuse Ampere Ratings, Catalog Numbers Ampere Catalog Number Rating 250V 600V 1 A2K1R A6K1R 3 A2K3R A6K3R 4 - A6K4R 5 A2K5R A6K5R 6 A2K6R A6K6R 8 - A6K8R 10 A2K10R A6K10R 12 A2K12R - 15 A2K15R A6K15R 20 A2K20R A6K20R 25 A2K25R A6K25R 30 A2K30R A6K30R

Ampere Catalog Number Rating 250V 600V

Ampere Catalog Number Rating 250V 600V

35 40 45 50

A2K35R A2K40R A2K45R A2K50R

A6K35R A6K40R A6K45R A6K50R

175 200 225 250

A2K175R A2K200R A2K225R A2K250R

A6K175R A6K200R A6K225R A6K250R

60 70 80 90

A2K60R A2K70R A2K80R A2K90R

A6K60R A6K70R A6K80R A6K90R

300 350 400 450

A2K300R A2K350R A2K400R A2K450R

A6K300R A6K350R A6K400R A6K450R

100 110 125 150

A2K100R A2K110R A2K125R A2K150R

A6K100R A6K110R A6K125R A6K150R

500 600

A2K500R A2K600R

A6K500R A6K600R

Recommended Fuse Blocks With Box Connectors For Amp-trap Class RK1 Fuses Fuse

Catalog Number Ampere 250V 600V Rating 1 Pole 3 pole 1 pole 3 pole

0-60A

0-30 31-60 61-100 101-200 201-400 401-600

20306R 20606R 21036R 22001R 24001R 2631R

20308R 20608R 21038R 22003R 24003R 2633R

60306R 60606R 61036R 62001R 64001R 6631R

60308R 60608R 61038R 62003R 64003R 6633R

A variety of pole configurations and termination provisions are available. Refer to the fuse block section of this catalog for details.

61-600A

Dimensions A AMPERE RATING In. mm 250V-A2K FUSES 0-30 2 51 31-60 3 76 61-100 5-7/8 149 101-200 7-1/8 181 201-400 8-5/8 219 401-600 10-3/8 264 600V-A6K FUSES 0-30 5 127 31-60 5-1/2 139 61-100 7-7/8 200 101-200 9-5/8 244 201-400 11-5/8 295 401-600 13-3/8 340

In.

B mm

In.

C mm

In.

D mm

In.

E mm

9/16 13/16 1-1/16 1-9/16 2-1/16 2-9/16

14 21 27 40 53 66

- - 1/8 3/16 1/4 1/4

- - 3 5 6 6

- - 3/4 1-1/8 1-5/8 2

- - 19 28 41 51

- - 1 1-3/8 1-7/8 2-1/4

25 35 48 57

13/16 1-1/16 1-5/16 1-13/16 2-9/16 3-1/8

21 27 34 46 66 80

- - 1/8 3/16 1/4 1/4

- - 3 5 6 6

- - 3/4 1-1/8 1-5/8 2

- - 19 28 41 51

- - 1 1-3/8 1-7/8 2-1/4

25 35 48 57

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 28


AMP-TRAP®

FAST ACTING/CLASS RK1 FUSES

A2K & A6K

Melting Time – Current Data, 250V Fuses

A2K30 to 600

Current in Amperes

B

Time in Seconds

Maximum Instantaneous Peak Let-Thru Amperes

Peak Let-Thru Current Data ­– A2K30 to 600, 250 Volts AC

Available Current in RMS Symmetrical Amperes

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 29


AMP-TRAP®

FAST ACTING/CLASS RK1 FUSES

A2K & A6K

Current in Amperes

Melting Time – Current Data, 600V Fuses

A6K30 to 600

Time in Seconds

Maximum Instantaneous Peak Let-Thru Amperes

Peak Let-Thru Current Data ­– A6K30 to 600, 600 Volts AC

Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 30


AMP-TRAP®

HSRK

high speed/class rk1 High speed rk1 (HSRK) Protect your electrical power wiring and power semiconductors with a single fuse. The new HIGH SPEED RK1 (HSRK) combines semiconductor fuse performance with NEC branch circuit compliance. The fuse was designed with two specific applications in mind: 1. To provide semiconductor fuse performance to solid state drive applications but in the larger RK body sizes that have been typically installed in older systems. 2. To provide industrial power applications with the most current limiting fuse available, which in turn provides the best arc flash mitigation available to power systems using the larger RK size fuses.

B

Features/Benefits

Highlights:

Applications:

➤ Current Limiting ➤ Low I2t ➤ Drive protection in larger RK body sizes for older installations ➤ Fast acting

➤ Branch circuits ➤ AC drives ➤ Solid state controllers ➤ Feeder circuits ➤ Arc flash mitigation

➤ Most current limiting RK1 available ➤ Provides the best Arc flash mitigation for feeder and branch circuits (non motor load circuits) ➤ Excellent cycling ability for frequent drive starts and stops without nuisance opening ➤ Extremely Low I2t

Ratings ➤ AC: (70 to 600A) 600VAC, 200KA I.R. ➤ 300KA I.R. Self certified

Approvals HSRK (70 to 600A) ➤ UL listed to 248-12 File E2137 ➤ CSA certified to C22.2 - No. 248.12

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 31


Amp-trap速

HIGH SPEED/CLASS RK1 Standard Fuse Ampere Ratings, Catalog Numbers Ampere Rating

Catalog # 600V

Ampere Rating

Catalog # 600V

200 225 250 300 350 400 450 500 600

HSRK200R HSRK225R HSRK250R HSRK300R HSRK350R HSRK400R HSRK450R HSRK500R HSRK600R

70 HSRK70R 80 HSRK80R 90 HSRK90R 100 HSRK100R 110 HSRK110R 125 HSRK125R 150 HSRK150R 175 HSRK175R

HSRK

Recommended Fuse Blocks With Box Connectors For Amp-trap速 Class RK1 Fuses Fuse Catalog Number Ampere 600V Rating 1 pole 3 pole 61-100 61036R 61038R 101-200 62001R 62003R 201-400 64001R 64003R 401-600 6631R 6633R A variety of pole configurations and termination provisions are available. Refer to the fuse block section of this catalog for details.

70-600A

Dimensions AMPERE RATING In. 600V-HSRK FUSES 61-100 101-200 201-400 401-600

7-7/8 9-5/8 11-5/8 13-3/8

A

mm 200 244 295 340

B In. mm 1-5/16 1-13/16 2-9/16 3-1/8

34 46 66 80

C In. mm 1/8 3/16 1/4 1/4

3 5 6 6

D In.

mm

E In.

3/4 1-1/8 1-5/8 2

19 28 41 51

1 1-3/8 1-7/8 2-1/4

mm 25 35 48 57

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 32


Amp-trap速

HIGH SPEED/CLASS RK1

HSRK

I2t Data HSRK (Amp Rating)R Max Clearing I2t @ 600V AC

Ampere Rating (A)

Pre-arc (A2s X 103)

70

1.2

14

80

1.6

17

B

(A2s X 103)

90

2.3

24

100

2.7

26

110

2.3

23

125

3.4

32

150

5.1

45

175

8.0

65

200

14

100

225

14

110

250

16

130

300

26

200

350

37

290

400

63

450

450

67

500

500

98

600

600

141

900

Watts Loss vs % Rated Current

Correction Factor for l2t

Correction Factor for Watts Loss

I2t vs Working Voltage

Working Voltage (AC RMS Volts)

% Rated Current

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 33


Amp-trap®

HIGH SPEED/CLASS RK1 Ampere Rating (A)

Watts Loss at Rated Current

70

10

80

11

90

13

100

14

110

18

125

19

150

25

175

26

200

27

225

35

250

43

300

45

350

47

400

53

450

62

500

63

600

83

Peak Let-Thru Data HSRK70 — 600R, 600V AC

Maximum Peak Let-Thru Current (A)

Watts Loss Data HSRK70 — 600R, 600V AC

HSRK

60Hz RMS Symmetrcal Prosective Current (A)

Prearcing Time(s)

Prearcing Time(s)

Melting Time — Current Data HSRK70 — 600R, 600V AC

Prearc Current (A RMS)±8%

Prearc Current (A RMS)±8%

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 34


AMP-TRAP®

AG

class G

amp-trap ag fuses fit right in to a wide variety of industrial applications The Ferraz Shawmut Amp-trap AG fuse series is a complete line of Class G fuses. AG fuses safely fit a wide variety of applications. Class G fuses are made in four physical sizes and provide good branch-circuit protection for lighting, heating, and appliance circuits.

B

Features/Benefits ➤ Four unique sizes from ½-60 amperes do not allow inter-changeability with other fuse classes ➤ Fiberglass bodies provide dimensional stability in harsh industrial settings

HIGHLIGHTS:

Applications:

➤ Current-Limiting ➤ Time Delay (above 5A)

➤ Lighting ➤ Heating* ➤ Appliances ➤ Branch Circuits * Except in Canada, where fuses must be “P” or “D” type. ­

Standard Fuse Ampere Ratings, Catalog Numbers AMPERE RATING 1/2 1 1-1/2 2 3 4 5 6 8 10

CATALOG NUMBER

AMPERE RATING

CATALOG NUMBER

AG1/2 AG1 AG1-1/2 AG2 AG3

15 20 25 30 35

AG15 AG20 AG25 AG30 AG35

AG4 40 AG5 45 AG6 50 AG8 60 AG10

AG40 AG45 AG50 AG60

Ratings

Approvals

➤ AC: 1/2 to 20A 600VAC, 100K A I.R. 25 to 60A, 480VAC, 100k A I.R.

➤ UL Listed to Standard 248-5 File E2137 ➤ CSA Certified to Standard C22.2 No. 248.5

Dimensions

AMPERE A B C RATING In. mm In. mm In. mm

1/2-15A

1.31

33.3

.406

10.3

.28

7.1

20A

1.41

35.8

.406

10.3

.28

7.1

25, 30A

1.62

41.2

.406

10.3

.28

7.1

35-60A

2.25

57.2

.406

10.3

.50

12.7

Cross Reference: AG will replace the following fuses: Bussmann SC, Littelfuse SLC

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 35


AMP-TRAP®

Time Delay/Class g Fuses

ag

Current in Amperes

Melting Time – Current Data, 480V Fuses

AG1 to 10

Time in Seconds

Current in Amperes

Melting Time – Current Data, 480V Fuses

AG15 to 60

Maximum Instantaneous Peak Let-Thru Amperes

Time in Seconds Peak Let-Thru Current Data ­– AG1 to 60, 480 Volts AC

Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 36


AMP-TRAP®

ATMR

class CC SMALL FUSE - BIG PROTECTION FOR GENERAL CIRCUITS Amp-trap® ATMR fuses, in the Class CC family, are the smallest dimension 600VAC/DC fuses suitable for branch circuit protection. The ATMR is a popular choice for economical protection of control circuits and control circuit transformers where available short circuit currents exceed 10,000 amperes. ATMR’s rejection dimensions prevent substitution by lesser rated fuses. These fast acting fuses give current limiting protection to general circuits.

B

Features/Benefits ➤ Rejection style design prevents replacement errors when used with recommended fuse blocks ➤ Versatile design for individual component and branch circuit protection

HIGHLIGHTS:

Applications:

➤ Fast Acting ➤ Very Current-Limiting

➤ Control Circuits ➤ Lighting ➤ General Loads ➤ Branch Circuit Protection

Ratings ➤ AC: 1/10 to 30A 600VAC, 200kA I.R. ➤ DC: 1/10 to 30A 600VDC, 100kA I.R.

Approvals ➤ UL Listed to Standard 248-4 File E2137 ➤ CSA Certified to Standard C22.2 No. 248.4 ➤ DC Listed to ULStandard 248

Standard Fuse Ampere Ratings, Catalog Numbers AMPERE RATING

CATALOG NUMBER

AMPERE RATING

CATALOG NUMBER

1/10 1/8 2/10

ATMR1/10 ATMR1/8 ATMR2/10

3-1/2 4 5

ATMR3-1/2 ATMR4 ATMR5

1/4 3/10 1/2

ATMR1/4 ATMR3/10 ATMR1/2

6 7 8

ATMR6 ATMR7 ATMR8

3/4 1

ATMR3/4 ATMR1

9 10

ATMR9 ATMR10

1-1/4 1-1/2 2

ATMR1-1/4 ATMR-1-1/2 ATMR2

12 15 20

ATMR12 ATMR15 ATMR20

2-1/2 3

ATMR2-1/2 ATMR3

25 30

ATMR25 ATMR30

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 37


AMP-TRAP®

FAST ACTING/Class CC Fuses

aTMR

Recommended Fuse Blocks For Amp-Trap® Class CC Fuses

Dimensions

CATALOG NUMBER ULTRASAFE™ Screw Connector Pressure Plate Number of Indicating with Double Connector Poles Fuse Holders Quick Connects with Double Quick Connects ADDER 30310R 30320R 1 USCC1I 30311R 30321R 2 USCC2I 30312R 30322R 3 USCC3I 30313R 30323R 3 USFMCCI

Copper Box Connector

30350R 30351R 30352R 30353R

Refer to the Class CC Fuse Block section of this catalog for other details.

Current in Amperes

Melting Time – Current Data, 600V Fuses

ATMR1/10 to 30

Maximum Instantaneous Peak Let-Thru Amperes

Time in Seconds Peak Let-Thru Current Data ­– ATMR3/4 to 30, 600 Volts AC

Current in Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 38


ONE-TIME

OT/OTN/OTS

class K-5 for versatility and economy, these general purpose fuses are hard to beat OT, OTN and OTS general purpose fuses provide low cost protection for feeder and branch circuits serving lighting, heating, and other non-motor loads. OT, OTN and OTS fuses will safely interrupt available short circuit currents up to 50,000 amperes in all ratings.

B

OT, OTN and OTS fuses are not rejection fuses – care should be taken to ensure that replacement fuses do not have lower interrupting ratings than original fuses. OTN 15 through 60 satisfy the Canadian electrical code requirement for Type “P,” low melting-point, non-time delay fuses. Features/Benefits ➤ Easy to read imprint label for quick recognition and replacement ➤ Low cost for high protection value

HIGHLIGHTS:

Applications:

➤ Versatile ➤ Lowest cost protection for circuits serving non-inductive loads

➤ Feeders ➤ Branch Circuits ➤ Resistive Heating ➤ Residential and Small Commercial Installations

Ratings ➤ OT AC: 1 to 600A 250VAC, 50kA I.R. DC: 1 to 600A 250VDC, 20kA I.R. ➤ OTN (Canada) AC: 15 to 60A 250VAC, 50kA I.R. ➤ OTS AC: 1 to 600A 600VAC, 50kA I.R. DC: 1 to 600A 300VDC, 20kA I.R.

Approvals ➤ UL Listed to Standard 248-9 File E2137 ➤ CSA Certified to Standard C22.2 No. 248.9* ➤ Ferraz Shawmut Certified for DC per UL248

*The Canadian Electrical Code requires these fuses in ratings 15 through 60A to be of the low melting point design ­use OTN 15-60.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 39


ONE-TIME

general purpose/CLASS K-5 Fuses

ot/OTN/ots

Standard Fuse Ampere Ratings, Catalog Numbers Ampere Catalog Number Rating 250V 600V 1 OT1 OTS1 2 OT2 OTS2 3 OT3 OTS3 4 OT4 OTS4 5 OT5 OTS5 6 OT6 OTS6 7 OT7 – 8 OT8 OTS8 10 OT10 OTS10 12 OT12 OTS12 15 OT15, OTN15* OTS15 20 OT20, OTN20* OTS20 25 OT25, OTN 25* OTS25

Ampere Catalog Number Rating 250V 600V

Ampere Catalog Number Rating 250V 600V

30 35 40 45

OT30, OTN30* OT35, OTN35* OT40, OTN40* OT45, OTN45*

OTS30 OTS35 OTS40 OTS45

125 150 175 200

OT125 OT150 OT175 OT200

OTS125 OTS150 OTS175 OTS200

50 60 65 70

OT50, OTN 50* OT60, OTN60* OT65 OT70

OTS50 OTS60 – OTS70

225 250 300 350

OT225 OT250 OT300 OT350

OTS225 OTS250 OTS300 OTS350

75 80 90 100 110

OT75 OT80 OT90 OT100 OT110

OTS75 OTS80 OTS90 OTS100 OTS110

400 450 500 600

OT400 OT450 OT500 OT600

OTS400 OTS450 OTS500 0TS600

* In Canada

Recommended Fuse Blocks With Box Connectors For One-Time Class K-5 Fuses Fuse

Catalog Number Ampere 250V 600V Rating 1 Pole 3 pole 1 pole 3 pole

0-60A

Dimensions A AMPERE RATING In. 250V-OT, OTN FUSES 0-30 2 31-60 3 61-100 5-7/8 101-200 7-1/8 201-400 8-5/8 401-600 10-3/8 600V-OTS FUSES 0-30 5 31-60 5-1/2 61-100 7-7/8 101-200 9-5/8 201-400 11-5/8 401-600 13-3/8

0-30 31-60 61-100 101-200 201-400 401-600

20308 20608 21038 22003 24003 2633

60306 60606 61036 62001 64001 6631

60308 60608 61038 62003 64003 6633

A variety of pole configurations and termination provisions are available. Refer to the fuse block section of this catalog for details.

61-600A mm

20306 20606 21036 22001 24001 2631

B In. mm

C In.

mm

D In. mm

E In. mm

51 76 149 181 219 264

9/16 13/16 1-1/16 1-9/16 2-1/16 2-9/16

14 21 27 40 53 66

- - 1/8 3/16 1/4 1/4

- - 3 5 6 6

- - 3/4 1-1/8 1-5/8 2

- - 19 28 41 51

- - 1 1-3/8 1-7/8 2-1/4

25 35 48 57

127 139 200 244 295 340

13/16 1-1/16 1-5/16 1-13/16 2-9/16 3-1/8

21 27 34 46 66 80

- - 1/8 3/16 1/4 1/4

- - 3 5 6 6

- - 3/4 1-1/8 1-5/8 2

- - 19 28 41 51

- - 1 1-3/8 1-7/8 2-1/4

25 35 48 57

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 40


ONE-TIME

general purpose/CLASS K-5 Fuses

ot/OTN/ots

Current in Amperes

Melting Time – Current Data, 250V Fuses

OT30 to 600; OTN 30, 60

B

Time in Seconds

Current in Amperes

Melting Time – Current Data, 600V Fuses

OTS30 to 600

Time in Seconds

Maximum Instantaneous Peak Let-Thru Amperes

Peak Let-Thru Current Data ­– OT, OTN & OTS30 to 600, 250 and 600 Volts AC

Available Current in RMS Symmetrical Amperes Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 41


RENEWABLE

RF/RFS & RL/RLS

class H traditional protection for circuits with less than 10,000a SHORT CIRCUIT CURRENT RF and RFS general purpose fuses are suitable for application where available short circuit currents do not exceed 10,000 amperes. RF and RFS renewable fuses use matched RL and RLS die-cut zinc links from 1 to 600 amperes in 32 ratings.

Features/Benefits ➤ Knurled bushings for ease of disassembly ➤ Rugged construction for maximum service life ➤ Precision die-cut renewal links renew quickly and give repeatable performance

HIGHLIGHTS:

Applications:

➤ Renewable ➤ 32 Renewal Link Ratings

➤ General purpose loads where short circuits are 10,000 amperes or less

Ratings ➤ RF AC: 1 to 600A 250VAC, 10kA I.R. ➤ RFS AC: 1 to 600A 600VAC, 10kA I.R.

Approvals ➤ UL Listed to Standard 248-7 File E2137 ➤ CSA Certified to Standard C22.2 No. 248.7

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 42


RENEWABLE Class h Fuses/links

RF/rfS & rl/rls

Standard Fuse Ampere Ratings, Catalog Numbers Ampere Catalog Number Rating 250V 600V 1 RF1/RL1 RFS1/RLS1 2 RF2/RL2 RFS2/RLS2 3 RF3/RL3 RFS3/RLS3 5 RF5/RL5 RFS5/RLS5 6 RF6/RL6 RFS6/RLS6 10 RF10/RL10 RFS10/RLS10 15 RF15/RL15 RFS15RLS15 20 RF20/RL20 RFS20/RLS20 25 RF25/RL25 RFS25/RLS25 30 RF30/RL30 RFS30/RLS30 35 RF35/RL35 RFS35/RLS35 40 RF40/RL40 RFS40/RLS40

Ampere Catalog Number Rating 250V 600V 45 50 60 70 80 90

RF45/RL45 RF50/RL50 RF60/RL60 RF70/RL70 RF80/RL80 RF90/RL90

RFS45/RLS45 RFS50/RLS50 RFS60/RLS60 RFS70/RLS70 RFS80/RLS80 RFS90/RLS90

100 110 125 150 175 200

RF100/RL100 RF110/RL110 RF125/RL125 RF150/RL150 RF175/RL175 RF200/RL200

Ampere Catalog Number Rating 250V 600V 225 250 300 350 400 450

RF225/RL225 RF250/RL250 RF300/RL300 RF350/RL350 RF400/RL400 RF450/RL450

RFS225/RLS225 RFS250/RLS250 RFS300/RLS300 RFS350/RLS350 RFS400/RLS400 RFS450/RLS450

RFS100/RLS100 500 RFS110/RLS110 600 RFS125/RLS125 RFS150/RLS150 RFS175/RLS175 RFS200/RLS200

RF500/RL500 RF600/RL600

RFS500/RLS500 RFS600/RLS600

B

Recommended Fuse Blocks With Box Connectors For Renewable Class H Fuses Fuse

Catalog Number Ampere 250V 600V Rating 1 Pole 3 pole 1 pole 3 pole 0-30 31-60 61-100 101-200 201-400 401-600

20306 20606 21036 22001 24001 2631

20308 20608 21038 22003 24003 2633

60306 60606 61036 62001 64001 6631

60308 60608 61038 62003 64003 6633

0-60A

A variety of pole configurations and termination provisions is available. Refer to the fuseholder section of this catalog for details.

61-600A

Dimensions AMPERE RATING In. 250V-RF FUSES

0-30 2 31-60 3 61-100 5-7/8 101-200 7-1/8 201-400 8-5/8 401-600 10-3/8 600V-RFS FUSES 0-30 5 31-60 5-1/2 61-100 7-7/8 101-200 9-5/8 201-400 11-5/8 401-600 13-3/8

A mm

In.

B

mm

C In.

mm

D In. mm

E In. mm

51 76 149 181 219 264

9/16 13/16 1-1/16 1-9/16 2-1/16 2-9/16

14 21 27 40 54 66

- - 1/8 3/16 1/4 1/4

- - 3 5 6 6

- - 3/4 1-1/8 1-5/8 2

- - 18 28 41 51

- - 1 1-3/8 1-7/8 2-1/4

25 35 48 57

127 139 200 244 295 340

13/16 1-1/16 1-5/16 1-13/16 2-9/16 3-1/8

21 27 34 46 67 80

- - 1/8 3/16 1/4 1/4

- - 3 5 6 6

- - 3/4 1-1/8 1-5/8 2

- - 18 28 41 51

- - 1 1-3/8 1-7/8 2-1/4

25 35 48 57

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

B 43