161 w75th street 12d

Page 1

GENERAL NOTES 1. 2.

location of work Apt. 12D & 12E

4" 4'20 12

0'-

2008 Smoke/ Carbon Monoxide Detector Notes

Drawing List

0"

A-100.00

Cover Sheet, Plot Plan, Key Plan, Notes

DM-101.00

Demolition Plan

A-102.00

Construction Plan

A-103.00

Reflected Ceiling Plan

1. 2. 3. 4.

A-104.00

Exterior Elevation @ Kitchen Window

E-100.00

Electrical Plan

5.

M-100.00

Mechanical Floor Plan

6.

P-100.00

Demolition Floor Plan

P-101.00

Plumbing Floor Plan

7. 8. 9.

P-200.00

Plumbing Details, Notes and Riser Diagrams

10.

P-201.00

Plumbing Specifications

11. 12. 13. 14.

Smoke/ Carbon Monoxide detectors or devices shall be installed in ordinance with the Housing Maintenance Code. Multiple Dwelling Law, the New York Building Code, the New York City Electrical Code and NFPA 72. Smoke Detectors and Carbon Monoxide Detectors may be combined providing the devices comply with the provisions of title 28 of the administrative code of the city of New York and any applicable rules promulgated thereunder. Each Smoke/ Carbon Monoxide Detector shall be installed in accordance with Reference Standard UL 2034 and UL 2075 of the New York City Building Code. Each Smoke/ Carbon Monoxide Detector shall be installed outside of each sleeping room in the immediate vicinity of within 15'-0" of the entrance to a sleeping room; inside each sleeping room; and on each story within a dwelling unit, including below grade stories and penthouses per 908.7.1.1.1. Each Smoke/ Carbon Monoxide Detector shall be of a type that allows for readily testing of such a device. Duplex units shall have a device located on each level if only one means of egress is provided from each level. Ceiling mounted devices shall be a minimum distance of 4" from any wall. Wall mounted devices shall be a minimum of 4" to a maximum of 12" from the ceiling. Each dwelling unit shall be equipped with an approved type smoke/ carbon monoxide detector device receiving primary power from the building wiring with no switches in the circuit other than the over current device protecting the branch circuit as per New York City Building Code Sec. 907.2.10.2 through 907.2.10.4. Existing buildings that are not equipped with hardwired connections shall be supplied with battery operated devices. Such Smoke/ Carbon Monoxide Detector must be either the ionization chamber type or the photoelectric detector type as per New York City Building Code Sec. 907 and 908. A "Certificate of Satisfactory installation for Smoke/ Carbon Monoxide Detector" must be filed with the division of code enforcement H.P.D., 10 days after installation. Written information of testing and maintenance of the devices shall be provided to the dwelling unit owner. In multiple dwellings (R-2), smoke alarms shall be able to support visible alarm per ANSI A117.1.

Tenant Protection Plan 28-104.8.4 Tenant protection plan. Construction documents for alterations of buildings in which any dwelling unit will be occupied during construction shall include a tenant protection plan. Such plan shall contain a statement that the building contains dwelling units that will be occupied during construction and shall indicate in sufficient detail the specific units that are or may be occupied during construction, the means and methods to be employed to safeguard the safety and health of the occupants, including, where applicable, details such as temporary fire-rated assemblies, opening protective, or dust containment procedures. The elements of the tenant protection plan may vary depending on the nature and scope of the work but at a minimum shall make detailed and specific provisions for: 1.

2. 3.

4.

5. 6.

Egress. At all times in the course of construction provision shall be made for adequate egress as required by this code and the tenant protection plan shall identify the egress that will be provided. Required egress shall not be obstructed at any time except where approved by the commissioner. Fire Safety. All necessary laws and controls, including those with respect to occupied dwellings, as well as additional safety measures necessitated by the construction shall be strictly observed. Health requirements. Specification of methods to be used for control of dust, disposal of construction debris, pest control and maintenance of sanitary facilities, and limitation of noise to acceptable levels shall be included. 3.1 There shall be included a statement of compliance with applicable provisions of law relating to lead and asbestos. Compliance with housing standards. The requirements of the New York City housing maintenance code, and, where applicable, of the New York City housing maintenance code, and where applicable, the New York State multiple dwelling law shall be strictly observed. Structural safety. No structural work shall be done that may endanger the occupants. Noise restrictions. Where hours of the day or the days of the week in which construction work may be undertaken are limited to the New York City noise control code, such limitactions shall be stated.

Scope of Work: All work shall fully conform to the requirements of New York City Building Code, Fire Department Rules and Regulations, utility company requirements, and the best trade practices. 3. Before commencing work, the contractor shall file all required insurance certificates with the Department of Buildings, obtain all required permits, and pay all fees required by the governing New York City agencies. 4. Minor details not usually shown or specified, but required for proper construction of any part of the work shall be included as if they were indicated in the drawings. 5. The contractor shall coordinate all work procedures with the stipulations of local authorities, building management or board of directors. 6. The contractor shall be responsible for the protection of all conditions and materials within the proposed construction area. The contractor shall design and install adequate shoring and bracing for all structural or removal tasks. The contractor shall have sole responsibility for any damage or injuries caused by or during the execution of the work. 7. The contractor shall lay out his own work, and shall provide all dimensions required for other trades: plumbing, electrical, etc. 8. Plumbing work shall be performed by persons licensed in their trades, who shall arrange for and obtain through the Department of Buildings all required permits, inspections and required sign-offs. 9. Electrical work shall be performed by persons licensed in their trades, who shall arrange for and obtain through the Bureau of Electrical Control all required permits, inspections and required sign-offs. 10. The contractor shall do all cutting, patching, repairing as required to perform all of the work indicated on the drawings, and all other work that maybe required to complete the job. 11. All piping and wiring shall be removed to a point of concealment and shall be properly capped or plugged.

Tenant Safety Notes: Residential Renovation No change of use, occupancy, or zoning this application N

1

block: 1147 lot: 7501 Zone: C2-7A, R8B Map: 8C

ENERGY STATEMENT: To the best of my knowledge, belief, and professional judgement, this application is exempt from compliance with the 2011 NYCECC, USN# 06101.009566

plot plan n.t.s.

204'-4"

1.

General: All work to be completed in accordance with the New York City Building Code, Article 33, and regulation of all other agencies having jurisdiction.

2.

Means of Egress: All existing means of egress for tenants of the building to be maintained clear and free of all o obstructions, such as building materials, tools, etc.

3. a.

Fire Safety: All building materials which are stored at the site or any area of the building are to be stored in a locked area. Access to the area to be controlled by the owner, or the General Contractor. All materials to be stored in an orderly fashion. All flammable materials to be kept tightly sealed in their respective manufacturers’ containers. Such materials are to be kept away from heat. All flammable materials to be used and stored in an adequately ventilated space. All electrical power to be shut off where there are exposed conduits. All electrical power in the construction area to be shut off after working hours. Contractor, at all times, to ensure there is no natural gas leakage in the buildings, or any flammable gas to be used during construction.

b. c. d. e. f. g.

Amsterdam Avenue

4. a. b.

open to (2nd Flr.) below

open to (cellar) below

adjacent building

open to (1st Flr.) below

5. a. b.

Noise after Hours: Construction operations will be confined to normal working hours: 8am to 6pm, Monday to Friday, except legal holidays. Contractor must obtain written permission from all affected parties to work other than regular hours.

6.

Construction Operations will not involve interruption of heating, water, or electrical services to other tenants.

7.

Construction work will be confined to the apartment interior, and will not create dust, dirt, or other such i inconveniences to the other apartments units within the building.

8.

There will be no one occupying the premises to be renovated during the course of the construction work.

List of Inspections Special Inspections:

open to (cellar) below

area of work Apt. 12E. & 12D

W 76th Street

open to (2nd Flr.) below

120'-0"

open to (1st Flr.) below

1. Mechanical Systems 2. Firestop, Draftstop, and Fireblock Systems

E.S.

Progress Inspections:

open to (7th Flr.) below

59'-0"

W 75th Street

c.

Dust Control: Debris, dirt, and dust to be kept to a minimum and confined to the immediate construction area. Contractor to isolate construction area from occupied building area by means of temporary partitions or heavy w eight drop cloths. Debris, dirt, and dust to be cleaned up and cleared from the building site periodically to avoid excessive accumulation

E.E. E.S.

open to (1st Flr.) below

1. Preliminary 2. Fire-Resistance Rated Construction 3. Final Inspection

Endres Lyons Residence 161 West 75 St. , 12th Floor Apt. 12 D & E New York NY 10023

Page Goolrick Architect P.C. open to (cellar) below

open to (1st Flr.) below

20 W 22nd Street NY NY 10010 phone 212.219.3666

email pg@goolrick.com

www.goolrick.com

indicates apartment, area of work indicates demised space

2

key plan n.t.s.

E.S.

- existing egress stairs

E.E.

- existing elevator

title:

Cover Sheet, Plot Plan, Key Plan, Notes BOARD REVIEW SET

scale: varies date:

31 January 2014

A -100.00 Page 1 of 6


DEMOLITION NOTES 1.

up

2. shade area indicates new AC thru wall sleeve at LPC approved location DOCKET # 061595 ATP 06-1583

up

existing radiator and cabinet to be removed

3.

dn

existing riser pipe to remain existing risers to be relocated existing riser to remain existing vent stack to be relocated

shade area indicates new AC thru wall sleeve at LPC approved location DOCKET # 061595 ATP 06-1583

existing electrical panel to be relocated existing radiator and cabinet to be removed

shaded area (22 SF) indicates public hall SF incorporated into joined apartments 12D & E, (same as hall at floors 10 & 11 below) existing entry door to be relocated

4. shade area indicates new AC thru wall sleeve at LPC approved location DOCKET # 061595 ATP 06-1583

existing electrical splice box to remain existing radiator and cabinet to be removed

5.

existing radiator and cabinet to be removed

location of new apartment entrance door -existing corridor flooring to be removed

6. 7. 8.

7

1a existing doors to be removed and relocated; see door schedule

9.

10.

11. 12.

13.

existing PTAC to remain; cabinet to be removed

existing PTAC to remain; cabinet to be removed

existing radiator and cabinet to be removed

shade area indicates new AC thru wall sleeve at LPC approved location DOCKET # 061595 ATP 06-1583

1

existing radiator and cabinet to be removed

shade area indicates new AC thru wall sleeve at LPC approved location DOCKET # 061595 ATP 06-1583

existing radiator and cabinet to be removed

shade area indicates new AC thru wall sleeve at LPC approved location DOCKET # 061595 ATP 06-1583

14.

15.

CONTRACTOR SHALL PERFORM ALL OPERATIONS AS DEMOLITION AND REMOVAL INDICATED ON THE DRAWINGS AND AS MAY BE REQUIRED BY THE WORK, ALL WORK SHALL BE DONE CAREFULLY AND NEATLY, IN A SYSTEMATIC MANNER. THE CONTRACTOR SHALL FILE ALL NECESSARY CERTIFICATES OF INSURANCE WITH THE DEPARTMENT OF BUILDINGS AND PROVIDE ANY AND ALL BONDS REQUIRED BY ANY CITY AGENCY IN ORDER TO DO THE WORK HEREIN DESCRIBED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND CARTING AWAY FROM THE BUILDING SITE OF ALL MATERIALS THAT MUST BE REMOVED TO COMPLETE THE PROJECT IN THE PROCESS OF CONSTRUCTION, DEMOLITION, AND CARTING OF MATERIALS, DEBRIS, AND EQUIPMENT IN AND OUT OF THE CONSTRUCTION SITE, CARE SHALL BE TAKEN TO PROTECT ALL EXISTING AREAS BEAMS, PIPES, DUCTS, AND FINISHES THAT ARE NOT TO BE AFFECTED BY CONSTRUCTION OR DEMOLITION. SHOULD ANY OF THESE AREA, BEAMS, PIPES, ETC. OF THE BUILDING OR THE APARTMENT BE DAMAGED, THEY SHALL BE REPAIRED OR PREPLACED BY THE CONTRACTOR AT NO EXPENSE TO THE OWNER. CONTRACTOR SHALL TAKE ADEQUATE PRECAUTIONS DURING THE COURSE OF THE DEMOLITION AND CONSTRUCTION TO MAINTAIN AND PROTECT INTERIOR EXISTING PARTITIONS, WALLS, CEILINGS, FLOORS, FIXTURES, ETC., TO REMAIN, THESE PRECAUTIONS SHALL INCLUDE BUT MANY NOT BE LIMITED TO ERECTION AND MAINTENANCE OF PROTECTIVE COVERINGS AND SHORING AND BRACING AS REQUIRED. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY INCIDENTAL DAMAGE TO EXISTING WORK. ALL ADJOINING PROPERTY AFFECTED BY ANY OPERATIONS OF DEMOLITION SHALL BE PROTECTED. NO STRUCTURAL ELEMENTS SHALL BE REMOVED. CONTRACTOR SHALL REMOVE AND STORE ALL EXISTING FIXTURES, FITTINGS AND MATERIALS TO BE SALVAGED IN A DESIGNATED "CLEAN ROOM" WHICH SHALL BE LOCKED AT ALL TIMES AND KEPT CLEAN, DRY AND DUST FREE. EXISTING FIXTURES, FITTINGS, MATERIALS, ETC...., TO BE SALVAGED SHALL BE DETERMINED BY CLIENT AND ARCHITECT IN FIELD. REMOVE DEMOLISHED MATERIALS FROM THE SITE IN A TIMELY MANNER. LEAVE SITE CLEAN AND FREE OF DANGEROUS CONDITIONS, NO DEBRIS SHALL BE ALLOWED TO ACCUMULATE ON THE SITE. DEBRIS SHALL BE REMOVED BY THE CONTRACTOR AS THE JOB PROCEEDS. THE SITE SHALL BE LEFT BROOM CLEAN AT THE COMPLETION OF DEMOLITION. REMOVE AND RELOCATE ALL WIRING, PLUMBING, AND MECHANICAL EQUIPMENT AFFECTED BY REMOVAL OF PARTITIONS. REMOVED PIPES AND/OR LINES SHALL BE CUT TO A POINT OF CONCEALMENT, BEHIND OR BELOW FINISH SURFACES, AND SHALL BE PROPERLY CAPPED AND PLUGGED. CAP UTILITIES AS REQUIRED. THE CONTRACTOR SHALL PROVIDE, ERECT AND MAINTAIN ALL TEMPORARY BARRIERS AND GUARDS, AND ALL TEMPORARY SHORING AND BRACING AS REQUIRED BY DEPARTMENT OF BUILDINGS RULES AND REGULATIONS. INFORM THE BUILDING ENGINEER AND ARCHITECT IF CONSTRUCTION WILL CAUSE ANY INTERRUPTIONS IN ANY UTILITIES OR SERVICES (I.E., ELECTRICAL, TELEPHONE, HOT WATER) AND COORDINATE WITH BUILDING. THE DRAWINGS SHOULD NOT BE CONSTRUED TO INDICATE FULL EXTENT OF PRECISE NATURE OF REQUIRED DEMOLITION. ANY DISCREPANCIES BETWEEN FIELD CONDITIONS AND AS DRAWN CONDITIONS SHALL BE REPORTED TO THE ARCHITECT PRIOR TO DEMOLITION. ALL EXISTING MEANS OF EGRESS FOR TENANTS OF BUILDING TO BE MAINTAINED CLEAR AND FREE OF ALL OBSTRUCTIONS, SUCH AS BUILDING MATERIALS, TOOLS, ETC.

demolition floor plan

Endres Lyons Residence 161 West 75 St. , 12th Floor Apt. 12 D & E New York NY 10023

Page Goolrick Architect P.C. 20 W 22nd Street NY NY 10010 phone 212.219.3666

email pg@goolrick.com

www.goolrick.com

title:

Demolition Plan BOARD REVIEW SET

N

scale: 1/4" = 1'-0" date:

31 January 2014

DM -101.00 Page 2 of 6


drawing key SD CD

9

up

smoke and carbon monoxide detector door number existing partition to be removed

demising wall tenant separation

existing partition to remain

existing egress stair not in scope of work

elev. 4

21

3'-7 1/2" wc 104

dn

w

4

d

1

Light and Air Calc. area: 91sq.ft. laundry light: 16 sq.ft. air: 8 sq. ft. 103

9'-9 1/2" study 105

acoustical insulation

window: 5'-5 1/2"h. x 4'-2"w. light: 23 sq.ft. air : 16.5 sq. ft.

18

1'-6"

20

9'-0 1/2"

replace lav. at existing location

1

16'-0 1/2"

mudroom 102 9'-11 1/2"

CD SD

7a

2

foyer 101

Light and Air Calc. area: 150 sq.ft. light: 23 sq.ft. air: 16.5 sq. ft. bedroom 1 106

1 family photo wall

1

1a

closet

7

work counter

17

walk-in closet 109

1 family photo wall

CD SD

1

14

2'-5"

bedroom foyer 111

13

15a

1

closet

4'-11 1/2" bath 1 110

window: 5'-5 1/2"h. x 2'-7"w. light: 14 sq.ft. air : 7 sq. ft. existing bathroom all plumbing fixtures to remain

15'-6 1/2" Light and Air Calc. area: 181 sq.ft. light: 36 sq.ft. air: 18 sq. ft.

bedroom 3 112

28'-3 1/2"

Light and Air Calc. area: 605 sq.ft. light: 83 sq.ft. air: 41.5 sq. ft.

CD

SD

11'-10"

4'-10"

bath 3 113

Light and Air Calc. area: 156 sq.ft. light: 23 sq.ft. air: 16.5 sq. ft.

12

SD

window: 5'-5 1/2"h. x 3'-4"w. light: 18 sq.ft. air : 9 sq. ft.

window: 5'-5 1/2"h. x 3'-4"w. light: 18 sq.ft. air : 9 sq. ft.

window: 5'-5 1/2"h. x 3'-4"w. light: 18 sq.ft. air : 9 sq. ft.

window: 5'-5 1/2"h. x 3'-4"w. light: 18 sq.ft. air : 9 sq. ft.

window: 5'-5 1/2"h. x 2'-3"w. light: 12 sq.ft. air : 6 sq. ft.

window: 5'-5 1/2"h. x 4'-2"w. light: 23 sq.ft. air : 16.5 sq. ft.

window: 5'-5 1/2"h. x 2'-3"w. light: 12 sq.ft. air : 6 sq. ft.

bedroom 2 108

CD

7'-9 1/2"

14'-10 1/2"

12'-3"

CD

1

9

10

11a

living room 114

1

SD

2'-11 1/2"

bedroom 4 115

9a

fire rated ceiling

CD 3'-7"

15

21'-6"

11

2 layers 5/8" gwb 3 5/8" c-h mtl stud @ 16" o.c. 2-HR fire rated partition

4 1

partition types - UL Des. U438 line of slab underside

4'-6 1/2"

5'-1"

hall 116

7'-0 1/2"

5'-11 1/2"

16'-10 1/2"

3

new full height medicine cabinet existing door to remain new trim

1

9'-10 1/2" closet

8

8a

metal runner secured to structure top and bottom

replace lav., new faucet and new vanity countertop at existing vanity cabinet -35" aff.

1

shelves for printer + supplies

closet

existing shower and toilet to remain

bath 2 107

closet

1

2 layers 5/8" gwb and 1" shaftliner over 3 5/8" c-h mtl stud @ 16" o.c. 2-HR fire rated partition

4'-10 1/2"

shallow artwork shelves, cork on wall

15b 1

shaft

acoustical insulation

18'-1"

linen

19

3

acoustical sealant top + bottom

fire rated ceiling at corridor ventilation riser ducting, see RCP A103.00

1

existing shaft wall enclosure to remain; new partition wall attached 7'-5 1/2"

line of slab underside

9"

16

closet

partition types - UL Des. U419

1

9'-4 1/2"

5'-5"

pantry closet

11'-6 1/2"

15'-2"

2

bar/pantry 119

70 bottle wine chiller

metal runner secured to structure top and bottom

2a

9'-7"

12'-10"

bath 4 117

dining room 118

9'-2"

new tub, toilet, at existing locations

2 layers 5/8" gwb ea. side over 3 5/8" mtl stud @ 16" o.c. 2-HR fire rated partition

2

equipment wall

8'-9"

Light and Air Calc. area: 195 sq.ft. light: 31 sq.ft. air: 15.5 sq. ft.

frig./frz. drawers

partition types

acoustical sealant top + bottom

fridge

1'-5"

1

1

existing sink relocated

1'-1"

new shower body relocated

metal runner secured to structure top and bottom

elev. 3 3'-1 1/2"

1

1 layer 5/8" gwb ea. side over 3 5/8" mtl stud @ 16" o.c.

line of slab underside

6

electrical splice box to remain, w/removable panel for access

acoustical insulation

window: 5'-5 1/2"h. x 2'-10"w. light: 16 sq.ft. air : 8 sq. ft.

6'-9 1/2"

(2) window: 5'-7"h. x 2'-9 1/2"w. light: 31 sq.ft. air : 15.5 sq. ft.

3 2

acoustical sealant top + bottom

5

6'-1"

kitchen new window;new lintel to receive 2-HR intumescent 120 coating; see detail 2/A104 Light and Air Calc. area: 248 sq.ft. 16'-8" light: 41 sq.ft. gas range air: 20.5 sq. ft.

line of slab underside

14'-10"

3'-8"

patch and repair existing rated wall enclosure at relocated electrical panel

dw

pull-out garbage

30" sink

note: refer to UL fire rating for all conditions requiring rated partition by code

new toilet at existing location

4'-4"

(2) window: 4'-2"h. x 3'-0 1/2"w. light: 26 sq.ft. air : 13 sq. ft.

partition types

demising wall tenant separation

10'-5 1/2"

18'-8 1/2"

new vent stack location existing sanity riser to remain, new column cover

3'-4 1/2"

existing riser pipe to remain

6'-9 1/2"

existing risers new location

new partition 3-5/8" metal stud with 5/8" GWB both sides

3'-11"

8'-2 1/2"

up

5'-6"

window: 5'-2 1/2"h. x 2'-11"w. light: 15 sq.ft. air : 7.5 sq. ft.

existing egress stair not in scope of work

window: 5'-5 1/2"h. x 2'-7"w. light: 14 sq.ft. air : 7 sq. ft.

11'-11"

Light and Air Calc. area: 213 sq.ft. light: 65 sq.ft. air: 32.5 sq. ft.

window: 5'-5 1/2"h. x 2'-7"w. light: 14 sq.ft. air : 7 sq. ft.

SD

window: 5'-5 1/2"h. x 4'-2"w. light: 23 sq.ft. air : 16.5 sq. ft.

window: 5'-5 1/2"h. x 4'-2"w. light: 23 sq.ft. 16.5 sq. ft. air :

construction floor plan

ADA diagrams & notes

Endres Lyons Residence

36" min

161 West 75 St. , 12th Floor

(a) before removal of cabinets and base

54" min 42" min

12" min

17"-19"

30" min

28"-36"

36"

stop or latch approach- sliding doors suggested flexible supply lines

4. Bathroom door buck shall be provided to allow remounting of door on same frame to achieve alternative swing.

6. Accessible routs to be provided between new facilities, providing a minimum of 36 inches of width along accessible route as per rs 4-6, 4.13.5.

12" min.

Apt. 12 D & E New York NY 10023

Page Goolrick Architect P.C.

3. Fixtures to be provided with required clear floor space as per the requirement of 4.32.4.2, 4.3, 4.4, and 4.5. New fixtures to be subject to requirements of 4.32.4 concerning dimensions and adaptability, as shown in attached details.

5. Control and operating mechanisms shall be operable with one hand and shall not require tight grasping, pinching or twisting of the wrist, as per rs 4-6, 4.25.4.

24" min.

18" min.

48" min.

36"

2. New bathroom walls to be provided with blocking, installed within the walls, making them adaptable to grab bars, handrail and shower seat attachments, meeting the requirements of rs 4-6, 4.23.3.

60" min.

12" min 42" min.

12" min

(b) cabinet and base removed and height alternatives Fig. 51 Kitchen Sink (bath sink similar)

suggested slip joint in tail piece

20 W 22nd Street NY NY 10010 front approach, pull side

phone 212.219.3666

email pg@goolrick.com

www.goolrick.com

48" min.

1. All new work to comply with the applicable requirements of Local Law No. 58/87 for handicap.

32" min.

32" min.

pull side, door with closer and latch

title:

New Construction Plan BOARD REVIEW SET

N

scale: 1/4" = 1'-0" date:

front approach- sliding doors 32" min. hinged doors

31 January 2014

A -102.00 Page 3 of 6

sliding doors


drawing key SD CD

9

smoke and carbon monoxide detector door number existing partition to be removed existing partition to remain

existing egress stair not in scope of work

new partition 3-5/8" metal stud with 5/8" GWB both sides existing egress stair not in scope of work

partition types note: refer to UL fire rating for all conditions requiring rated partition by code

wc 104

line of slab underside acoustical sealant top + bottom acoustical insulation

elev. 4

w E

30" sink

E

E

laundry 103

beam

dw

pull-out garbage

1 layer 5/8" gwb ea. side over 3 5/8" mtl stud @ 16" o.c.

d

+7'-11"

E

metal runner secured to structure top and bottom

ceiling

partition types

1

+8'-2 1/2"

line of slab underside

kitchen 120

acoustical sealant top + bottom

elev. 3

acoustical insulation

ceiling +8'-3" gas range

fridge

study 105

+8'-11"

+8'-6 1/2"

+8'-5" frig./frz. drawers

bath 4 117

4

bar/pantry 119 ceiling

ceiling

clg

line of slab underside

+9'-1/2"

acoustical sealant top + bottom acoustical insulation 2 layers 5/8" gwb and 1" shaftliner over 3 5/8" c-h mtl stud @ 16" o.c. 2-HR fire rated partition s

mudroom 102

+9'-1/2"

+9'-1/2"

partition types - UL Des. U419

2

shaded area indicates fire rated ceiling at corridor ventilation riser ducting

pantry closet

70 bottle wine chiller

metal runner secured to structure top and bottom

ceiling

beam

dining room 118

2 layers 5/8" gwb ea. side over 3 5/8" mtl stud @ 16" o.c. 2-HR fire rated partition

ceiling

metal runner secured to structure top and bottom bedroom 1 106

ceiling

foyer 101

+8'-0"

ceiling

+8'-0" soffit

+8'-6"

partition types - UL Des. U438

3 bath 2 107

line of slab underside

ceiling +8'-1 1/2"

s

beam +8'-1"

beam

ceiling

+8'-1"

+8'-7"

walk-in closet 109

2 layers 5/8" gwb 3 5/8" c-h mtl stud @ 16" o.c. 2-HR fire rated partition

+8'-2" beam clg

soffit +8'-6"

+8'-3"

hall 116 ceiling

fire rated ceiling

4

bedroom foyer 111 ceiling

+9'-1/2"

+8'-0"

ceiling fixture key

beam +8'-6"

recessed movie screen

bath 1 110

s

E indicates existing fixture

soffit +8'-6"

surface mounted fixture or pendant

beam +8'-1" +8'-1" beam

bedroom 4 115 beam

ceiling

+8'-2"

+9'-1/2"

soffit +8'-6"

ceiling +8'-11 1/2"

living room 114

beam

beam

+8'-0"

+8'-6"

bedroom 3 112

bedroom 2 108

ceiling

ceiling

+8'-11 1/2"

+8'-11 1/2"

bath 3 113

sconce s

sconce with switch recessed can

s

recessed or surface mount wall washer

soffit +8'-6"

ceiling fan ceiling fan with light undercabinet puck lights

1

reflected ceiling plan

Endres Lyons Residence 161 West 75 St. , 12th Floor Apt. 12 D & E New York NY 10023

Page Goolrick Architect P.C. 20 W 22nd Street NY NY 10010 phone 212.219.3666

email pg@goolrick.com

www.goolrick.com

title:

Reflected Ceiling Plan BOARD REVIEW SET

N

scale: 1/4" = 1'-0" date:

31 January 2014

A -103.00 Page 4 of 6


2

existing vent

EXISTING MASONRY WALL

DRYPACK PACK SOLID WITH MASONRY AND/ OR GROUT

(E) WALL CONSTRUCTION TO REMAIN , NO PROPOSED CHANGES (TYP .)

NEW ANGLE LINTELS, ONE FOR EACH 4" OF WALL WIDTH. SEE PLAN OR SCHEDULE FOR SIZE. BEAR LINTELS, 6" AT EACH END new window;new lintel to receive 2-HR intumescent coating

(E) ALUMINUM PANNING TO REMAIN , NO PROPOSED CHANGES (TYP .)

13th floor

new kitchen hood vent

2

1 (E) ALUMINUM WINDOW FRAME TO REMAIN (TYP.)

typical detail angle lintel in existing wall 3" = 1'-0"

new windows at 12E apartment kitchen

structural steel intumescent coating

(E) ALUMINUM PANNING TO REMAIN , NO PROPOSED CHANGES (TYP .)

1.

dashed lines indicate location of existing windows

Any exposed structural steel will be fire-rated with intumescent coating providing a 2-HR rating to meet the UL Des. D948.

new louvered sleeve and AC Unit 12th floor

existing vent

2

WINDOW DETAIL Scale: 1 1/2" = 1'-0"

EXISTING DOUBLE HUNG TYPE "A" Scale:

3/4" = 1'-0"

(E) WALL CONSTRUCTION TO REMAIN , NO PROPOSED CHANGES (TYP .)

11th floor (E) ALUMINUM WINDOW FRAME TO REMAIN (TYP .)

existing vent (E) ALUMINUM PANNING TO REMAIN , NO PROPOSED CHANGES (TYP.)

WINDOW DETAIL Scale: 1 1/2" = 1'-0"

PROJECT NAME & ADDRESS:

THE WELLSTON

WINDOW REPAIR 161 WEST 75TH STREET NEW YORK , NY

10th floor No .

1

DATE

REVISIONS

BY

CHK

note: no muntins at courtyard windows typical

3

typical window details courtesy of Cowley Engineering - reference only

exterior elevation - courtyard at 12 floor kitchen 1/4" = 1'-0" W 76th Street

existing courtyard windows at 12 E

11th floor windows

revised window at 10E

existing vent

existing vent

existing courtyard windows at 11 E

existing courtyard windows at 10 & 11 E

existing vent

Endres Lyons Residence 161 West 75 St. , 12th Floor

open to (7th Flr.) below

Apt. 12 D & E area of work Apt. 12E. & 12D

existing courtyard windows at 12 & 13 E

5

W 75th Street key plan 1/32" = 1'-0"

New York NY 10023

Page Goolrick Architect P.C. 120'-0"

site photos - courtyard at exterior of kitchen 12 E n.t.s.

dashed line indicates building 161 W 75th Street

13th floor windows

N

4

open to (1st Flr.) below

open to (1st Flr.) below open to (cellar) below open to (1st Flr.) below

open to (2nd Flr.) below

open to (cellar) below

elevation at exterior courtyard kitchen Apt. 12 E - not visible from any public street, 12th floor of 15 story building (this sheet, #3)

open to (2nd Flr.) below

heavy dashed line indicates location of new windows (2 windows in one opening)

204'-4"

Amsterdam Avenue

adjacent building

59'-0"

open to (cellar) below

OWNER:

open to (1st Flr.) below

1

existing revised window at 10E, hatched area indicates brick infill

20 W 22nd Street NY NY 10010 phone 212.219.3666

email pg@goolrick.com

www.goolrick.com

title:

Window Replacement BOARD REVIEW SET

scale: varies date:

31 January 2014

A -104.00 Page 5 of 6


GENERAL NOTES 1.

ALL WORK SHALL FULLY CONFORM WITH THE REQUIREMENTS OF THE BUILDING AN ELECTRICAL CODES OF THE CITY OF NEW YORK, THE NEW YORK STATE ENERGY CODE, O.S.H.A., ALL OTHER AUTHORITIES AND CODES HAVING JURISDICTION OVER THE WORK, AND THE BEST TRADE PRACTICES.

2.

THE SCOPE OF THE ELECTRICAL AND LIGHTING WORK WILL NOT INCREASE THE ELECTRICAL LOAD.

3.

NEW AND REVISED ELECTRICAL SCOPE SHOWN ONLY.

up

existing egress stair not in scope of work

A

T

existing egress stair not in scope of work

dn

wc 104

D

outlet and tv cable 4'-6" aff

up

GFI elev. 4

A

w

existing elec. panel

E

kitchen 120

at side face of counter

gas range

elev. 3

A

D

D

D

I

A

D

D

A

pantry closet

bar/pantry 119

D D

switch all existing electrical to remain, outlets shown are only those being altered

s

relocated ele. panel

foyer 101

D

D

bedroom 1 106

D

bath 2 107

D

D

D

T

T J

3 D

3

dimmer switch

3

3 way switch

3D

3 way dimmer jamb switch

J

s

outlets, tele., and data at counter height

D

D

D

D D

appliance outlet

A

mudroom 102

D

floor outlet

F

D

GFI

1/2 outlet switched

D

70 bottle wine chiller

outlet in cabinetry base

B

D

frig./frz. drawers

B

dining room 118

study 105

A

outlets and data at counter height

A

GFI

bath 4 117

grounded outlet

1/2

GFI

second set of puck lighting is in upper cabinets with glazed doors

electrical splice box to remain, upper cabinet w/removable panel for access

T

GFI

D

quad outlet GFI

fridge

3

A

GFI

A

A

outlet

laundry 103

D D I GFI

GFI

E

3

A

A

E

GFI

dw

D

electrical key

D

E

A pull-out garbage

30" sink

d

GFI

under counter

GFI

A

counter height

cable (TV + internet)

T

walk-in closet 109

D

phone jack

locate cable, phone, modem at shelves this closet

hall 116

bedroom foyer 111

D

E indicates existing fixture

D outlet and tv cable 4'-6" aff

D D D

3

D

surface mounted fixture or pendant

T

1/2 switched

sconce

extg. 1/2 switched

bath 1 110

s

outlet and tv cable 4'-6" aff

T

bedroom 4 115

recessed can

F

F

outlet and tv cable 4'-6" aff

living room 114

T

bedroom 3 112

recessed or surface mount wall washer

bedroom 2 108

all existing electrical to remain, outlets shown are only those being altered

bath 3 113

sconce with switch

s

existing elec. to remain

ceiling fan s

ceiling fan with light B

B A

1

electrical floor plan

A

B

B A

A

existing elec. to remain

undercabinet puck lights

B A SD

smoke detector

CD

carbon monoxide detector

S1

stereo

S

speaker

W

woofer

EP

electrical panel

I

intercom

Endres Lyons Residence 161 West 75 St. , 12th Floor Apt. 12 D & E New York NY 10023

Page Goolrick Architect P.C. 20 W 22nd Street NY NY 10010 phone 212.219.3666

email pg@goolrick.com

www.goolrick.com

title:

Electrical Plan

N

BOARD REVIEW SET scale: 1/4" = 1'-0" date:

31 January 2014

E-100.00 Page 6 of 6


DUCTWORK

BUILDING DEPARTMENT NOTES

TO DRYER

HOOD WITH FAN (BY G.C.)

dw pull-out garbage

A. STANDARDS OF HEATING B. HEATING CAPACITY C. NOISE CONTROL.

CHAPTER 3, MC312 CHAPTER 3, MC312 CHAPTER 9, SUB-SECTION MC-926

D. NOISE CRITERIA LEVELS AND TEST PROCEDURES FOR SPL.

CHAPTER 9, SUB-SECTION MC-926

E. DUCT CONSTRUCTION, SUPPORTS, AIR INTAKES, EXHAUSTS AND RELIEFS.

CHAPTER 5, 6 & 7

F. AIR FILTERS, FANS, AIR COOLING AND HEATING EQUIPMENT.

CHAPTER 6

G. ELECTRIC WIRING

NYC ELECTRIC CODE

WALL CAP 4. MINIMUM TEMPERATURE BE MAINTAINED IN OCCUPIED SPACES DURING

AC-7

5. THE VENTILATION INDEX FOR ALL AREAS COMPLIES WITH THE MINIMUM CODE REQUIREMENTS PER CHAPTER 4 AND ALL SUBSECTIONS. 6. ALL TOILET ROOMS TO BE VENTILATED IN ACCORDANCE WITH SECTION 4, SUB-SECTION MC-403. 7. UPON COMPLETION OF THIS VENTILATION SYSTEM A TEST SHALL BE CONDUCTED IN THE PRESENCE OF AND UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT QUALIFIED TO CONDUCT SUCH TESTS. FOR SYSTEMS OF OR LESS THAN 5000 CFM THE INSPECTION MAY BE BY A PERSON HAVING NOT LESS THAN FIVE YEARS EXPERIENCE SUPERVISING INSTALLATION OF VENTILATING SYSTEMS. THE CONTRACTOR WILL BE REQUIRED TO RETAIN THE SERVICE OF THE PROPER PERSON TO CONDUCT THE TEST. THE TESTS SHALL SHOW COMPLIANCE WITH THE CODE REQUIREMENTS FOR VENTILATION AND THE PROPER FUNCTIONING OF ALL SMOKE DETECTION, FIRE PROTECTION AND OPERATING DEVICES BEFORE THE SYSTEM IS APPROVED. THE LICENSED PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT WHO CONDUCTS THE TESTS SHALL FILE A CERTIFICATE AS TO WHETHER THE SYSTEM COMPLIES WITH THE APPLICABLE LAWS. HE SHALL ALSO FILE WITH THIS CERTIFICATION A REPORT OF THE TEST. THE TEST AND REPORT SHALL BE MADE IN A MANNER SATISFACTORY TO THE SUPERINTENDENT. 8. NOT USED

36x4 LOUVER

AC-6

AC-2 frig./frz. drawers

CONNECT 8x8 WITH FD & AD TO EXISTING SHAFT

8x8 pantry closet

FIRE ENCLOSE

9. ALL VENTILATING AND AIR CONDITIONING DUCTWORK, BOTH LOW AND HIGH VELOCITY, TO BE CONSTRUCTED IN ACCORDANCE WITH THE DUCT MANUALS OF SMACNA, FIRST EDITION, 1985. 10. DUCT SUPPORT SHALL BE IN ACCORDANCE WITH CHAPTER 6, SECTION MC-603. IRON, STEEL, ALUMINUM, COPPER, CONCRETE, MASONRY OR CLAY TILE. 11. FIRE DAMPERS SHALL BE PROVIDED AT ALL FRESH AIR INTAKES AS PER CHAPTER 4, SECTION 401.5.1 AND IN ALL DUCTS PENETRATING FIRE RATED PARTITIONS AS PER CHAPTER 6. 12. ALL FIRE DAMPERS SHALL BE APPROVED BY THE NEW CITY BOARD OF STANDARDS AND APPEALS AND SHALL BE MANUFACTURED AND INSTALLED IN ACCORDANCE WITH UL 555, STANDARD FOR FIRE DAMPERS AND CEILING DAMPERS, 3rd. EDITION. 13. SMOKE DETECTORS AND SMOKE DAMPERS SHALL BE INSTALLED AS REQUIRED IN CHAPTER 4, SECTION 401.5.1, AND CHAPTER 6. DAMPER OPERATION SHALL CONFORM WITH CHAPTER 5 AND 6. 14. SMOKE DAMPERS SHALL BE APPROVED BY THE NEW CITY BOARD OF STANDARDS AND APPEALS AND SHALL BE MANUFACTURED AND INSTALLED IN ACCORDANCE WITH UL 555S-1983 STANDARD FOR LEAKAGE RATED DAMPERS FOR USE IN SMOKE CONTROL SYSTEMS, FIRST EDITION. 15. REFER TO ARCHITECTURAL DRAWING FOR FIRE RATED WALL LOCATIONS AND RATED CONSTRUCTION. 16. TESTS OF SOUND POWER LEVEL OF MECHANICAL EQUIPMENT SHALL BE CONDUCTED AND RESULTS SUBMITTED AS REQUIRED AS PER CHAPTER 9, SECTION MC-926. NOISE CRITERIA LEVEL AND TEST PROCEDURES FOR SOUND POWER LEVEL SHALL COMPLY WITH CHAPTER 9, SECTION MC-926.

CONNECT TO HOOD

EXISTING CORRIDOR VENTILATION RISER

EXISTING EXHAUST FAN

TR-1 SPECIAL INSPECTIONS TO BE FILED FOR THE FOLLOWING: MECHANICAL SYSTEMS

PTAC-1

PTAC-2

AC-5

AC-4

TWO LINE SYMBOLS SD

ABBREV.

N

2. MATERIALS AND EQUIPMENT SUBJECT TO SPECIAL INSPECTION: A. MECHANICAL VENTILATION, AIR CONDITIONING AND REFRIGERATION: 1) INSPECTION AND TESTS OF THE REQUIRED VENTILATION SYSTEMS CHAPTER 4. 2) INSPECTION AND TESTS OF THE REFRIGERATION SYSTEMS AS PER CHAPTER 11, SECTION MC-1109. B. HIGH PRESSURE STEAM PIPING PER RULES AND REGULATIONS FOR HIGH PRESSURE STEAM PIPING SYSTEMS. 3. THE FOLLOWING WORK ITEMS, COMPONENTS, MATERIALS, CAPACITIES, ETC. SHALL COMPLY WITH FOLLOWING CODE CHAPTER AND SUB-SECTION:

AC-8

30" sink

SINGLE LINE SYMBOLS SD

1. ALL WORK SHALL COMPLY WITH THE APPLICABLE SECTIONS OF THE BUILDING CODE, CITY OF NEW YORK, EFFECTIVE JULY 1, 2008 AND ALL AMENDMENTS AND RULES AND REGULATIONS OF THE DEPARTMENT OF BUILDINGS TO DATE.

EXISTING VENT TERMINAL

LEGEND

BC 1704.15

VD

VD

MD

MD

FC R

VD MD

FC D

VD MD

FC R

FC D

TR

TR

TG

TG

DESCRIPTION

SD

SPLITTER DAMPER (SPLIT. DPR.)

N

NECK SIZE

VD

VOLUME DAMPER (VOL. DPR.)

MD

MOTORIZED DAMPER (MOT. DPR.)

FC

FLEXIBLE CONNECTION (FLEX. CONN.)

-

RISE OR DROP IN THE DIRECTION OF AIRFLOW

CD

CEILING SUPPLY AIR DEVICE

RG

CEILING RETURN OR EXHAUST AIR DEVICE

TR TG

SIDE CONNECTED SUPPLY, RETURN OR EXHAUST AIR DEVICE

-

ACOUSTIC LINED DUCTWORK

-

FIRE ENCLOSE DUCTWORK OR OFFSET

FD

FD

FD

FIRE DAMPER

FD/ AD

FD/ AD

FD/ AD

FIRE DAMPER W/ AD

FSD

FSD

FSD

FIRE SMOKE DAMPER W/ AD

FSD-R

FSD-R

FSD-R

FIRE SMOKE DAMPER WITH RESET

BS TS EQ. SPT.

BOTTOM SPLIT SIZE, TOP SPLIT SIZE, EQUAL SPLIT

TV

TURNING VANES

O.A.I. S.A.

OUTSIDE AIR INTAKE SUPPLY AIR

EXH. R/ A

EXHAUST OR SPILL AIR RETURN AIR

X (XXX)

T

THERMOSTAT POINT OF NEW CONNECTION REMOVE AND CAP AIR TIGHT

A.C.

AIR CONDITIONING UNIT

AD

ACCESS DOOR

AHU

AIR HANDLING UNIT

A.L.

ACOUSTIC LINED

CD

CEILING DIFFUSER

COD

CABLE OPERATED DAMPER

CU

CONDENSING UNIT

EG

EXHAUST GRILLE

ER

EXHAUST REGISTER

ERV

ENERGY RECOVERY VENTILATOR

EF

EXHAUST FAN

GEF

GENERAL EXHAUST FAN

KEF

KITCHEN EXHAUST FAN

LEF

LAUNDRY EXHAUST FAN

LD.

LINEAR DIFFUSER

O.E.D.

OPEN END DUCT

TR

TOP REGISTER

TREF

TRASH ROOM EXHAUST FAN

VAV

VARIABLE AIR VOLUME BOX

WB

WAY BLOW

WMS

WIRE MESH SCREEN

BOARD REVIEW SET

MECHANICAL ENGINEER Abraham Joselow PC 45 W 34 Street Suite 1101 New York NY 10001 Tel (212) 736 2584 Fax (212) 736.0241

AC-3

EXISTING PTAC UNIT

AIR CONDITIONING UNIT SCHEDULE THRU THE WALL A.C. UNIT (TYP.) SEE SCHEDULE. SAW CUT OPENING (TYP.)

CONSTRUCTION FLOOR PLAN SCALE: 1/4" = 1' - 0"

1-1/2"x1-1/2"x1/4" ANGLE FOR NOT MORE THAN (4) 2" PIPES 2"x2"x5/16" ANGLE FOR ALL OTHERS

MANUFACTURER

MODEL NO. EER

ELECTRICAL DATA

COOLING CAPACITY

HEATING CAPACITY

DIMENSIONS

WEIGHT

NOTES

AC-1

NOT USED

AC-2

FRIEDRICH

WS08C10

9.9

7,800 BTU

-

27"x23"x17"H.

93 LBS.

1

AC-3

FRIEDRICH

WS12C10C

9.4

11,500 BTU

-

27"x23"x17"H.

112 LBS.

1

AC-4

FRIEDRICH

WS10C10

9.4

9,700 BTU

-

27"x23"x17"H.

103 LBS.

1

Endres Residence

AC-5

FRIEDRICH

WS16C30

8.5

15,000 BTU

-

27"x23"x17"H.

119 LBS.

1

AC-6

FRIEDRICH

WS12C10C

9.4

11,500 BTU

-

27"x23"x17"H.

112 LBS.

1

161 West 75 St. Apt. 12 D & E New York NY 10023

AC-7

FRIEDRICH

WS08C10

9.9

7,800 BTU

-

27"x23"x17"H.

93 LBS.

1

AC-8

FRIEDRICH

WS08C10

9.9

7,800 BTU

-

27"x23"x17"H.

93 LBS.

1

Page Goolrick Architect P.C. STEEL ROD

STEEL ROD SEE SPEC FOR SIZE PIPE CLAMP

TAG

1-31-2014

NOTES & ACCESSORIES:

20 W 22nd Street NY NY 10010

1. ARCHITECTURAL GRILLE - FINISH AS PER BUILDING STANDARDS.

phone 212.219.3666 email pg@goolrick.com www.goolrick.com

CARRIER PIPE

CARRIER PIPE

INSULATION - SEE SPEC. CLEVIS HANGAR

INSULATION SEE SPEC

PACKAGED TERMINAL AIR CONDITIONER (PTAC) SCHEDULE

SHIELD ANGLE STEEL

INSULATION SADDLE

MULTIPLE PIPES UP TO 4"

SINGLE PIPES UP TO 4"

RISER CLAMP

TAG

MANUFACTURER

MODEL NUMBER

COOLING CAP. (BTU)

HEATING CAPACITY (BTU)

GPM

ELECTRICAL DATA

SLEEVE DIM.

WEIGHT

NOTES

TYPICAL PIPE HANGER AND SUPPORT DETAILS NO SCALE

PTAC-1

McQUAY

PGAN012

12,000

-

-

42"x16"

140 LBS.

1,2

PTAC-2

McQUAY

PGAN015

15,000

-

-

42"x16"

160 LBS.

1,2

NOTES: 1. ARCHITECTURAL GRILLE - FINISH AS PER BUILDING STANDARDS. 2. UNIT MOUNTED DIGITAL CONTROL PANEL.

title:

MECHANICAL FLOOR PLAN

scale:

1/4" = 1'-0"

date:

05 December 2013

M-100.00


24 KEY NOTES:

10 2 13

5

20

25

16 2

27

19

17

EXISTING RADIATOR TO REMAIN

2

EXISTING RADIATOR & PIPING TO BE REMOVED.

3

EXISTING RADIATOR & PIPING TO BE RELOCATED. SEE NEW CONSTRUCTION PLAN FOR NEW LOCATION.

4

EXISTING PACKAGED TERMINAL AIR CONDITIONING UNIT (PTAC) TO BE REMOVED. SEE P-101 FOR ADDITIONAL WORK.

5

EXISTING THRU THE WINDOW AIR CONDITIONING UNIT TO BE REMOVED

6

EXISTING THRU THE WINDOW AIR CONDITIONING UNIT TO REMAIN.

7

EXISTING CORRIDOR EXHAUST RISER TO REMAIN.

8

EXISTING CORRIDOR EXHAUST GRILLE TO BE REMOVED. PATCH RISER AIR TIGHT.

9

EXISTING EXHAUST FAN TO REMAIN

23

28

26

18

1

10

EXISTING STACKING WASHING MACHINE & DRYER TO BE REMOVED. REMOVE EXHAUST DUCT. CUT BACK & CAP WASTE & WATER PIPING AT RISER.

11

EXISTING PLUMBING FIXTURES TO REMAIN

12

EXISTING LAVATORY & ASSOCIATED PIPING TO BE REMOVED. SALVAGE FAUCET FOR USE IN BATH # 4.

13

EXISTING GAS RANGE TO BE REMOVED.

14

EXISTING SINK TO BE REMOVED AND REUSED IN LAUNDRY # 103. CUT BACK & CAP PIPING AT RISERS.

15

EXISTING DISHWASHER & ASSOCIATED PIPING TO BE REMOVED. CAP PIPING AT RISERS.

16

EXISTING REFRIGERATOR WITH ICE MAKER TO BE REMOVED

17

EXISTING SINK & ASSOCIATED PIPING TO BE REMOVED.

18

EXISTING WATER CLOSET & ASSOCIATED PIPING TO BE REMOVED.

19

EXISTING LAVATORY & ASSOCIATED PIPING TO BE REMOVED.

20

EXISTING SHOWER & ASSOCIATED PIPING TO BE REMOVED.

21

EXISTING LAVATORY TO BE REPLACED ON EXISTING ROUGHING.

22

EXISTING BATHTUB TO BE REPLACED.

23

EXISTING WATER CLOSET TO BE REPLACED ON EXISTING ROUGHING.

24

ASSUMED LOCATION OF EXISTING SOIL & VENT STACK TO REMAIN.

25

EXISTING WATER RISERS TO REMAIN.

26

EXISTING 4" SANITARY RISER TO REMAIN.

27

EXISTING 4" VENT STACK TO BE RELOCATED. SEE NEW CONSTRUCTION PLAN.

28

EXISTING WATER RISERS TO BE RELOCATED. SEE NEW CONSTRUCTION PLAN.

15 14

15

16

5

13 24

23

22

3

8 7 3

2

11

21

12 25

11

9

11

BOARD REVIEW SET

11

4

4

2

3

3

5

5

5

1-31-2014

MECHANICAL ENGINEER Abraham Joselow PC 45 W 34 Street Suite 1101 New York NY 10001 Tel (212) 736 2584 Fax (212) 736.0241

Endres Residence 161 West 75 St. Apt. 12 D & E New York NY 10023

DEMOLITION FLOOR PLAN SCALE: 1/4" = 1' - 0"

Page Goolrick Architect P.C. 20 W 22nd Street NY NY 10010 phone 212.219.3666 email pg@goolrick.com www.goolrick.com

title:

DEMOLITION FLOOR PLAN

scale:

1/4" = 1'-0"

date:

05 December 2013

P-100.00


CONNECT 11 4" CW. & 1" HW. TO EXISTING WATER RISERS

ASSUMED LOCATION OF EXISTING SOIL & VENT STACK

BRANCH SHUT-OFF VALVES WITH ACCESS DOOR WASHING MACHINE 2" W., 2" V., 1 2" H. & CW. SEE NOTE # 2 BELOW

CONNECT 2" W. & 2" V. TO EXISTING STACK DRYER (GAS) CONNECT 3 4" G. TO EXISTING

INSTALL 4 TUBE, 19" HIGH, 22 SECTION RADIATOR. CONNECT TO STEAM SUPPLY & RETURN SEE PLUMBING RISER DIAGRAM 'A'

FOR WATER PIPING IN THIS AREA SEE WATER RISER DIAGRAM

BRANCH SHUT-OFF VALVES WITH ACCESS DOOR

WATER CLOSET CONNECT TO EXISTING ROUGHING

EXISTING 4" SANITARY RISER RELOCATED 4" VENT STACK

DISHWASHER 2" W., 2" V., 1 2" HW.

1" 11 4"

SINK (TYP.) 2" W., 2" V., 1 2" H. & CW.

2"

SEE PLUMBING RISER DIAGRAM 'D' dw

30" sink

1

pull-out garbage

2" 1

RELOCATED EXISTING RADIATOR. REPIPE TO EXISTING STEAM SUPPLY & RETURN PIPING.

CONNECT 3 4" H. & CW. WITH SHUT-OFF VALVES TO EXISTING RISERS. PROVIDE ACCESS DOOR.

2"

EXISTING WATER RISERS

1 1

ASSUMED LOCATION OF EXISTING SOIL & VENT STACK

2"

REFRIGERATOR WITH ICE MAKER 1 2" CW. SEE NOTE # 1 BELOW

2"

INSTALL 4 TUBE, 19" HIGH, 10 SECTION RADIATOR. CONNECT TO STEAM SUPPLY & RETURN. VERIFY LOCATION OF STEAM RISERS IN FIELD.

frig./frz. drawers

WATER CLOSET CONNECT TO EXISTING ROUGHING BATHTUB 11 2" W., 11 2" V., 3 4" H. & CW. CONNECT TO EXISTING SEE PLUMBING RISER DIAGRAM 'C' LAVATORY CONNECT TO EXISTING ROUGHING

pantry closet

SEE PLUMBING RISER DIAGRAM 'B'

RANGE (GAS) CONNECT 3 4" G. TO EXISTING

EXISTING SHOWER TO REMAIN

SINK 2" W., 2" V., 1 2" H. & CW.

EXISTING WATER CLOSET TO REMAIN

EXISTING WATER RISERS RELOCATED EXISTING RADIATOR. REPIPE TO EXISTING STEAM SUPPLY & RETURN PIPING.

LAVATORY CONNECT TO EXISTING ROUGHING

BOARD REVIEW SET

1-31-2014

MECHANICAL ENGINEER Abraham Joselow PC 45 W 34 Street Suite 1101 New York NY 10001 Tel (212) 736 2584 Fax (212) 736.0241

INSTALL 4 TUBE, 19" HIGH, 22 SECTION RADIATOR. CONNECT TO STEAM SUPPLY & RETURN

INSTALL 4 TUBE, 19" HIGH, 28 SECTION RADIATOR. CONNECT TO STEAM SUPPLY & RETURN

RELOCATED EXISTING RADIATOR. REPIPE TO EXISTING STEAM SUPPLY & RETURN PIPING.

EXISTING PTAC UNIT TO REPLACED (BY MECH. CONTRACTOR). DISCONNECT STEAM COIL AND CUT BACK STEAM PIPING.

RELOCATED EXISTING RADIATOR. REPIPE TO EXISTING STEAM SUPPLY & RETURN PIPING.

Endres Residence 161 West 75 St. Apt. 12 D & E New York NY 10023

Page Goolrick Architect P.C. 20 W 22nd Street NY NY 10010

NOTES: 1. 1 2" CW. VALVED OUTLET WALL BOX JAMECO # 200-IK. 2. WASHING MACHINE - 2" STANDPIPE, 2" V., 3/4" H. & CW. AIR CHAMBER WATTS # SERIES 05 WITH WATTS INTELLIFLOW MODEL A2C-WB-M1 AUTOMATIC SHUT-OFF VALVE WITH LEAK SENSOR, WALL BOX, STAINLESS STEEL BRAIDED HOSES WATTS # CWM-S-HL.

phone 212.219.3666 email pg@goolrick.com www.goolrick.com

title:

PLUMBING FLOOR PLAN

scale:

1/4" = 1'-0"

date:

05 December 2013

CONSTRUCTION FLOOR PLAN SCALE: 1/4" = 1' - 0"

P-101.00


EX. WATER CLOSET TO BE REPLACED ON EXISTING ROUGHING

EX. BATHTUB TO BE REPLACED. REPIPE 11 2" W. & 11 2" V. TO EXISTING

EX. FIXTURE TO BE REPLACED ON EXISTING ROUGHING

EXISTING FIXTURES & ASSOCIATED PIPING TO BE REMOVED

EXISTING PLUMBING STACK TO REMAIN

13 th FLOOR

EXISTING PLUMBING STACK TO REMAIN

EX. FIXTURES TO REMAIN

EXISTING FIXTURES & ASSOCIATED PIPING TO BE REMOVED

EX. LAV TO BE REPLACED ON EXISTING ROUGHING

13 th FLOOR

EX. SK

12 th FLOOR

EX. DW

CONNECT 2" V. TO EXISTING

EX. WM

EX. LAV

SK

WM

CONNECT 2" W. TO EXISTING

EX. LAV

EX. WC

12 th FLOOR

EX. SH

2"

DEAFENING

EXISTING PLUMBING STACK TO REMAIN

13 th FLOOR

2"

2"

EX. WATER CLOSET TO BE REPLACED ON EXISTING ROUGHING

12 th FLOOR

DEAFENING

DEAFENING

CONNECT 2" W. TO EXISTING

PLUMBING RISER DIAGRAM 'A' NO SCALE

PLUMBING RISER DIAGRAM 'B' NO SCALE

EXISTING FIXTURES & ASSOCIATED PIPING TO BE REMOVED

AIR CHAMBER (TYP.) SIOUX CHIEF MINI-RESTER

EXISTING SOIL STACK TO REMAIN

CONNECT 4" V. TO EXISTING

2" DISHWASHER STANDPIPE

13 th FLOOR

PLUMBING RISER DIAGRAM 'C' NO SCALE

EXISTING HOT & COLD WATER RISERS

CONNECT 11 4" CW. & 1" HW. TO EXISTING

13 th FLOOR

4"

EX. WC 12 th FLOOR

EX. SK

EX. SH

11 4" 1"

2"

EX. LAV

EX. DW

2"

SK

SK

DW 4"

DEAFENING

SK

12 th FLOOR

2" 2"

1

1

2"

1

2"

2"

REF.

SK 2"

DEAFENING

2"

CONNECT 2" W. TO EXISTING

CONNECT 4" V. TO EXISTING

DW

1

EXISTING H. & CW. RISERS TO BE REMOVED

BRANCH SHUT-OFF VALVES WITH ACCESS DOOR

PLUMBING RISER DIAGRAM 'D' NO SCALE

CONNECT 11 4" CW. & 1" HW. TO EXISTING

WATER RISER DIAGRAM NO SCALE

EXISTING GAS RISER EXISTING GAS RISER

EXISTING SHUT-OFF VALVES TO REMAIN

EXISTING SHUT-OFF VALVES TO REMAIN

13th FLOOR DRYER

RANGE

FOR BUILDING DEPARTMENT USE ONLY

12th FLOOR

FIXTURES EXISTING RANGE TO BE REMOVED

EXISTING RANGE TO BE REMOVED

11th FLOOR

WC

L

BT

SH

SK

WM DW DRYER RANGE

NEW

0

0

0

0

1

0

0

1

0

REMOVE REPLACE

1

2

0

1

0

0

1

0

1

2

2

1

0

2

1

1

0

1

BUILDING DEPARTMENT PLUMBING NOTES : 1. ALL PLUMBING SYSTEMS (SANITARY, WASTE, VENT, WATER DISTRIBUTION AND GAS PIPING SYSTEMS) AND ASSOCIATED EQUIPMENT SHALL BE INSTALLED, OPERATED AND MAINTAINED IN ACCORDANCE WITH THE REQUIREMENTS OF 2008 THE NEW YORK CITY PLUMBING CODE (NYCPC). 2. INSTALLATION OF UNDERGROUND PIPING SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION PC 702.2. 3. PROTECTION OF PIPING PASSING UNDER OR THROUGH FOUNDATION WALLS AS PER SECTION PC 305. 4. TRENCHING, EXCAVATION AND BACKFILL AS PER SECTION PC 306. 5. RAT PROOFING AS PER PC 304. 6. MATERIALS USED IN PLUMBING SYSTEMS SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION PC 303, PC 605, PC 702, PC 902, PC 1102. 7. EQUIPMENT CONNECTIONS AND JOINING OF PIPING SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF CHAPTERS 4, 5, 6, 7 AND 9. 8. DEEP SEAL TRAPS FOR FLOOR DRAINS SHALL BE PROVIDED AS PER PC 1002, AND CLEAN-OUTS SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION PC 708. 9. BUILDING HOUSE TRAPS SHALL BE PROVIDED AS PER SECTION PC 1002. 10. DRAINAGE PIPE CLEANOUTS AS PER SECTION PC 708. 11. VERTICAL AND HORIZONTAL PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION PC 308. 12. WATER SUPPLY SYSTEMS SHALL BE INSTALLED AND MAINTAINED IN ACCORDANCE WITH THE REQUIREMENTS OF CHAPTER 6 SECTION PC 601-603, 604, 606, 607, 608, 610. 13. THE SANITARY DRAINAGE SYSTEM SHALL BE SIZED AND INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF CHAPTER 7 SECTION PC 701, 704, 705, 706, 707, 708, 711. 14 VENT PIPING FOR SANITARY DRAINAGE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF CHAPTER 9 SECTION PC 901 THROUGH 912 THROUGH 917. 15. THE STORM DRAINAGE PIPING SHALL BE SIZED AND INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF CHAPTER 11 SECTION PC 1101 THROUGH 1113. 16. INSPECTION AND TESTING OF PLUMBING AND GAS PIPING SYSTEMS SHALL BE IN ACCORDANCE WITH SECTIONS PC 107, 312.

1st FLOOR

CELLAR EXISTING GAS METERS TO REMAIN

GAS RISER DIAGRAM NO SCALE

1-31-2014

MECHANICAL ENGINEER Abraham Joselow PC 45 W 34 Street Suite 1101 New York NY 10001 Tel (212) 736 2584 Fax (212) 736.0241

RADIATOR

AIR VENT

UNION (TYP.) RADIATOR VALVE

RADIATOR TRAP 1-1/2"x1-1/2"x1/4" ANGLE FOR NOT MORE THAN (4) 2" PIPES 2"x2"x5/16" ANGLE FOR ALL OTHERS

BOARD REVIEW SET

Endres Residence 161 West 75 St. Apt. 12 D & E New York NY 10023

STEEL ROD

STEEL ROD SEE SPEC FOR SIZE PIPE CLAMP

FLOOR

CARRIER PIPE

CARRIER PIPE

Page Goolrick Architect P.C.

INSULATION - SEE SPEC. CLEVIS HANGAR

INSULATION SEE SPEC

20 W 22nd Street NY NY 10010

SHIELD ANGLE STEEL

INSULATION SADDLE

MULTIPLE PIPES UP TO 4"

SINGLE PIPES UP TO 4"

TYPICAL PIPE HANGER AND SUPPORT DETAILS NO SCALE

RISER CLAMP

EXISTING CONDENSATE RETURN

CONNECT 3 4" CONDENSATE RETURN TO EXISTING

phone 212.219.3666 email pg@goolrick.com www.goolrick.com

CONNECT 11 4" STEAM SUPPLY TO EXISTING EXISTING STEAM SUPPLY

title:

PLUMBING: DETAILS, NOTES AND RISER DIAGRAMS

TYPICAL RADIATION SCHEMATIC

scale:

AS NOTED

NO SCALE

date:

05 December 2013

P-200.00


PLUMBING WORK 3. 1.

GENERAL A. THE "GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION" AIA DOCUMENTA201, LATEST EDITION, AND THESE SPECIFICATIONS AS APPLICABLE ARE PART OF THIS CONTRACT. B. ALL APPLICABLE CODES, LAWS AND REGULATIONS GOVERNING OR RELATING TO ANY PORTION OF THIS WORK ARE HEREBY INCORPORATED INTO AND MADE A PART OF THESE SPECIFICATIONS, AND THEIR PROVISIONS SHALL BE CARRIED OUT BY THE CONTRACTOR WHO SHALL INFORM THE OWNER, PRIOR TO SUBMITTING A PROPOSAL, OF ANY WORK OR MATERIALS WHICH VIOLATE ANY OF THE ABOVE LAWS AND REGULATIONS. ANY WORK DONE BY THE CONTRACTOR CAUSING SUCH VIOLATION, SHALL BE CORRECTED BY THE CONTRACTOR. C. INVESTIGATE EACH SPACE THROUGH WHICH EQUIPMENT MUST BE MOVED. WHERE NECESSARY, EQUIPMENT SHALL BE SHIPPED FROM THE MANUFACTURER IN SECTIONS OF SIZE SUITABLE FOR MOVING THROUGH AVAILABLE RESTRICTIVE SPACES. ASCERTAIN FROM BUILDING OWNER AT WHAT TIMES OF DAY EQUIPMENT MAY BE MOVED THROUGH ALL AREAS. D. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK. PIPE ROUTING IS SHOWN DIAGRAMMATICALLY AND DOES NOT SHOW ALL OFFSETS, DROPS AND RISES OF RUNS. THE CONTRACTOR SHALL ALLOW IN HIS PRICE FOR ROUTING OF PIPING TO AVOID OBSTRUCTIONS. EXACT LOCATIONS ARE SUBJECT TO APPROVAL OF ARCHITECT. COORDINATION WITH EXISTING SERVICES, INCLUDING THOSE OF OTHER TRADES IS REQUIRED. MAINTAIN HEADROOM AND SPACE CONDITIONS. E. INSTALL WORK SO AS TO BE READILY ACCESSIBLE FOR OPERATION, MAINTENANCE AND REPAIR. MINOR DEVIATIONS FROM DRAWINGS MAY BE MADE TO ACCOMPLISH THIS, BUT CHANGES WHICH INVOLVE EXTRA COST SHALL NOT BE MADE WITHOUT APPROVAL. F. REMOVAL AND RELOCATION OF CERTAIN EXISTING WORK WILL BE NECESSARY FOR THE PERFORMANCE OF THE GENERAL WORK. ALL EXISTING CONDITIONS CANNOT BE COMPLETELY DETAILED ON THE DRAWINGS. THE CONTRACTOR SHALL SURVEY THE SITE AND INCLUDE ALL CHANGES IN MAKING UP THE WORK PROPOSAL. G. CONNECTIONS TO EXISTING WORK: INSTALL NEW WORK AND CONNECT TO EXISTING WORK WITH MINIMUM INTERFERENCE TO EXISTING FACILITIES. TEMPORARY SHUTDOWNS OF EXISTING SERVICES SHALL BE PERFORMED AT NO ADDITIONAL CHARGES, AT TIMES NOT TO INTERFERE WITH NORMAL OPERATION OF EXISTING FACILITIES AND ONLY WITH WRITTEN CONSENT OF OWNER. MAINTAIN CONTINUOUS OPERATION OF EXISTING FACILITIES AS REQUIRED WITH NECESSARY TEMPORARY CONNECTIONS BETWEEN NEW AND EXISTING WORK. CONNECT NEW WORK TO EXISTING WORK IN NEAT AND ACCEPTABLE MANNER. RESTORE EXISTING DISTURBED WORK TO ORIGINAL CONDITION. H. DISCONNECT, REMOVE AND/ OR RELOCATE EXISTING MATERIAL, EQUIPMENT AND OTHER WORK AS NOTED OR REQUIRED FOR PROPER INSTALLATION OF NEW WORK. I. THE CONTRACTOR SHALL KEEP ALL EQUIPMENT AND MATERIALS, AND ALL PARTS OF THE BUILDING, EXTERIOR SPACES AND ADJACENT STREETS, SIDEWALKS AND PAVEMENTS, FREE FROM MATERIAL AND DEBRIS RESULTING FROM THE EXECUTION OF THIS WORK. EXCESS MATERIALS WILL NOT BE PERMITTED TO ACCUMULATE EITHER ON THE INTERIOR OR THE EXTERIOR. J. THE LOCATION OF THE EXISTING SERVICES ARE BELIEVED TO BE AS INDICATED ON THE DRAWINGS. THE CONTRACTOR SHALL VERIFY THE ACTUAL LOCATION AND SIZES OF THESE SERVICES AND NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO COMMENCING ANY WORK. K. SEAL OPENINGS THROUGH PARTITIONS, WALL AND FLOORS WITH NON SHRINK FIRE PROOF CAULKING. L. PROVIDE ALL NECESSARY FLASHING AND COUNTER-FLASHING TO MAINTAIN THE WATER PROOFING INTEGRITY OF THIS BUILDING AS REQUIRED BY THE INSTALLATION OR REMOVAL OF PIPING AND EQUIPMENT. PROVIDE EQUIPMENT CURBS AS REQUIRED. M. ALL PRESENT MATERIAL, EQUIPMENT AND CONSTRUCTION DEBRIS TO BE REMOVED UNDER THIS CONTRACT SHALL BECOME THE PROPERTY OF THE CONTRACTOR WITH THE EXCEPTION OF SPECIFIC EQUIPMENT AND APPARATUS REQUESTED BY THE BUILDING REPRESENTATIVE, ARCHITECT OR AS NOTED TO BE RELOCATED ON THE DRAWINGS. REMOVED EQUIPMENT SHALL BE PROPERLY DISPOSED OF BY THIS CONTRACTOR. N. MATERIALS AND WORKMANSHIP, UNLESS OTHERWISE NOTED, SHALL BE IN ACCORDANCE WITH BUILDING STANDARDS. O. THE WORK IN THE BUILDING SHALL BE DONE WHEN AND AS DIRECTED, AND IN A MANNER SATISFACTORY TO THE OWNER. THE WORK SHALL BE PERFORMED SO AS TO CAUSE THE LEAST POSSIBLE INCONVENIENCE AND DISTURBANCE TO THE PRESENT OCCUPANTS. P. THE CONTRACTOR'S PROPOSAL FOR ALL WORK SHALL BE PREDICATED ON THE PERFORMANCE OF THE WORK DURING REGULAR WORKING HOURS. WHEN SO DIRECTED, HOWEVER, THE CONTRACTOR SHALL INSTALL WORK IN OVERTIME AND THE ADDITIONAL COST TO BE CHARGED THEREFORE SHALL BE ONLY THE "PREMIUM" PORTION OF THE WAGES PAID. Q. UNLESS OTHERWISE SPECIFICALLY SPECIFIED, INCLUDE ALL CUTTING AND PATCHING OF EXISTING FLOORS, WALLS, PARTITIONS AND OTHER MATERIALS IN THE EXISTING BUILDING. THE CONTRACTOR SHALL RESTORE THESE AREAS TO ORIGINAL CONDITION, R. ALL MATERIAL AND EQUIPMENT TO BE NEW UNLESS OTHERWISE NOTED AND SHALL BE IN ACCORDANCE WITH BUILDING STANDARDS. S. SUBMISSION OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT A CAREFUL EXAMINATION OF THE PORTIONS OF THE EXISTING BUILDING, EQUIPMENT, ETC., WHICH AFFECT THIS WORK, AND THE ACCESS TO SUCH SPACES, HAS BEEN MADE AND THAT THE CONTRACTOR IS FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT THE EXECUTION OF THE WORK. THE CONTRACTOR IS RESPONSIBLE TO INDICATE ANY DISCREPANCIES BETWEEN THE CONTRACT DRAWINGS AND ACTUAL FIELD CONDITIONS PRIOR TO SUBMITTAL OF BID. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS SHALL NOT BE MADE FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN DURING SUCH AN EXAMINATION. THE ON-SITE INSPECTION SHALL VERIFY EXISTING PIPE SIZES, CLEARANCES, ETC., AND CONDITIONS. T. INSURANCE: IN ACCORDANCE WITH OWNER REQUIREMENTS AND SHALL INCLUDE A HOLD HARMLESS CLAUSE FOR OWNER AND ENGINEER. U. THE FINAL ACCEPTANCE WILL BE MADE AFTER THE CONTRACTOR HAS ADJUSTED HIS EQUIPMENT, TESTED THE VARIOUS SYSTEMS, DEMONSTRATED THAT IT FULFILLS THE REQUIREMENTS OF THE DRAWINGS AND SPECIFICATIONS AND HAS FINISHED ALL THE REQUIRED CERTIFICATES OF INSPECTION AND APPROVAL.

2.

SHOP DRAWINGS

7.

A. PRIOR TO THE INSTALLATION OF ANY WORK AND PROCUREMENT OF EQUIPMENT PROVIDE COMPLETE SET OF COORDINATED SHOP DRAWINGS OF ALL NEW AND EXISTING EQUIPMENT, INDICATING CAPACITY, DIMENSIONS AND SEQUENCE OF OPERATION FOR WRITTEN APPROVAL BY THE ARCHITECT AND ENGINEER.

A.

GATE VALVES: BRONZE RISING STEM, 200 PSI WOG; SIMILAR TO STOCKHAM #B-105, B-109.

B.

BALL VALVES: TWO PIECE, BRONZE, END ENTRY, 600 PSI WWP; SIMILAR TO STOCKHAM #S-216 BR-R-T, #S-126 BR-R-S.

C.

CHECK VALVES: BRONZE, THREADED CAP, TEFLON DISC; SIMILAR TO STOCKHAM #B-310T, B-320T.

B. INDICATE ON EACH SHOP DRAWINGS SUBMITTED: 1)

PROJECT NAME AND LOCATION.

2)

NAME OF ARCHITECT AND ENGINEER.

3)

ITEM IDENTIFICATION.

4)

APPROVAL STAMP OF PRIME CONTRACTOR.

8.

INSULATION: A. ALL INSULATION, JACKET, FACING AND ADHESIVES SHALL HAVE A COMPOSITE FIRE AND SMOKE HAZARD RATING AS TESTED BY PROCEDURES LISTED IN ASTM E-84, NFPA 255 AND UL 273; NOT EXCEEDING A FLAME SPREAD OF 25 AND A SMOKE DEVELOPED OF 50. INSULATION THICKNESS SHALL BE AS PER NYCECC. B. ON VALVES AND FITTINGS PROVIDE PREMOLDED FIBERGLASS FITTINGS WITH VAPER SEAL.

C. SUBMISSIONS: C. COLD WATER PIPING: PROVIDE 1/2 IN. THICK FIBERGLASS PIPE COVERING WITH VAPOR BARRIER. 1) SUBMISSIONS 11 IN. X 17 IN. OR SMALLER: IF THE SUBMISSION IS A CATALOG CUT, THEN THE CONTRACTOR SHALL SUBMIT ONE ORIGINAL AND FOUR COPIES. OTHERWISE, HE SHALL SUBMIT FIVE COPIES. THE ARCHITECT WILL FORWARD THE ORIGINAL AND THREE COPIES (FOUR COPIES WHEN NO ORIGINAL IS RECEIVED) TO THE ENGINEER. ALL CATALOG CUTS SHALL BE COMPLETE. 2) SUBMISSIONS LARGER THAN 11IN. X 17IN.: SUBMIT FIVE PRINTS TO THE ARCHITECT. THE ARCHITECT WILL FORWARD FOUR PRINTS TO THE ENGINEER.

D. HOT WATER PIPING: PROVIDE 1 IN. THICK FIBERGLASS SECTIONAL PIPE COVERING. E. HEATING PIPING: PROVIDE 1 IN. THICK FIBERGLASS SECTIONAL PIPE COVERING. 9.

1) PIPE AND FITTINGS 2) PLUMBING FIXTURES AND TRIM 3) VALVES, RADIATION 4) PIPING LAYOUTS 5) SUPPORTS, HANGERS AND GUIDES 6) INSULATION 7) BOILER, PUMPS AND HYDRONIC ACCESSORIES. 8) CONTROLS AND CONTROL WIRING. 4.

PLUMBING FIXTURES: A. PROVIDE ALL FIXTURES WITH STOP VALVES, SUPPLIES, TRAPS AND AIR CHAMBERS AS REQUIRED. ALL EXPOSED PIPING FINISH SHALL MATCH FIXTURE TRIM.

D. SUBMIT SHOP DRAWINGS FOR THE FOLLOWING:

B. ALL FIXTURES AND TRIM AS SPECIFIED BY OTHERS. 10.

PIPING SUPPORTS: A. SUPPORT AL PIPING FROM BUILDING CONSTRUCTION BY PROVIDING INSERTS, BEAM CLAMPS, STEEL FISHPLATES (IN CONCRETE FILL ONLY), AND ACCEPTABLE BRACKETS. B. PROVIDE TRAPEZE HANGERS OF BOLTED ANGLES OR CHANNELS FOR GROUPED LINES AND SERVICES. C. PROVIDE ADDITIONAL FRAMING WHERE BUILDING CONSTRUCTION IS INADEQUATE. SUBMIT FOR REVIEW.

AS-BUILT DRAWINGS AND EQUIPMENT OPERATIONAL INSTRUCTIONS

D. SUSPENDED HORIZONTAL PIPING:

A. UPON COMPLETION AND ACCEPTANCE OF WORK, CONTRACTOR SHALL FURNISH WRITTEN INSTRUCTIONS AND EQUIPMENT MANUALS AND DEMONSTRATE TO THE OWNER THE PROPER OPERATION AND MAINTENANCE OF ALL EQUIPMENT AND APPARATUS FURNISHED UNDER THIS CONTRACT.

1) SUPPORT ALL PIPING INDEPENDENTLY FROM STRUCTURE USING HEAVY IRON HINGED TYPE HANGERS, SIMILAR TO GRINNEL CLEVIS NO. 260.

B. THESE INSTRUCTIONS SHALL BE TYPED ON 8-1/2 IN. X 11 IN. PAPER AND BOUND IN THREE D-RING BINDERS WITH CLEAR ACETATE COVERS. CONTRACTOR SHALL GIVE THREE COPIES OF THE INSTRUCTIONS TO THE OWNER AND ONE COPY TO THE ENGINEER.

2) PROVIDE ELECTROPLATED SOLID BAND HANGERS SIMILAR TO AUTO-GRIP, FOR TWO INCH AND SMALLER PIPE. 3) PROVIDE WALL BRACKETS FOR WALL SUPPORTED PIPING AND PROVIDE SADDLES FOR FLOOR MOUNTED PIPING.

C. THE INSTRUCTION BOOKLET SHALL BEAR THE NAME, ADDRESS AND TELEPHONE NUMBER OF THE PROJECT, ARCHITECT AND ENGINEER.

4) SUSPEND PIPING FROM INSERTS, USING BEAM CLAMPS WITH RETAINING CLAMP OR LOCKNUT, STEEL FISHPLATES, CANTILEVER BRACKETS OR OTHER ACCEPTED MEANS. BEAM CLAMPS SHALL BE SIMILAR TO GRINNEL FIGURES 61,87 131 0R 225.

D. REPRODUCIBLE "AS-BUILT" DRAWINGS SHALL BE PROVIDED INDICATING THE AS INSTALLED CONDITIONS OF THE WORK. "AS-BUILT" DRAWINGS SHALL BE PROVIDED TO THE ARCHITECT AFTER COMPLETION OF THE INSTALLATION. 5.

5) PROVIDE SUPPORTS WITH COPPER LINING FOR UNINSULATED COPPER PIPING. 6) SUSPEND PIPING BY RODS WITH DOUBLE NUTS.

GENERAL PROVISIONS FOR PLUMBING WORK:

7) PROVIDE ADDITIONAL STEEL FRAMING AS REQUIRED AND ACCEPTED WHERE OVERHEAD CONSTRUCTION DOES NOT PERMIT FASTENING HANGER RODS IN REQUIRED LOCATIONS.

A. SPECIFICATIONS ARE OF SIMPLIFIED FORM AND INCLUDE INCOMPLETE SENTENCES. WORDS OR PHRASES SUCH AS "THE CONTRACTOR SHALL", "SHALL BE", "FURNISH", AND "PROVIDE" HAVE BEEN OMITTED FOR BREVITY.

8) SUPPORT BRANCH FIXTURE WATER PIPING IN CHASES WITH COPPER PLATED METAL BRACKETS, SECURED TO STUDS, SIMILAR TO HOLDRITE NOS. 102-18, 107-18, 102-26 OR 101-26.

B. DEFINITIONS: 1) "PROVIDE": TO SUPPLY, INSTALL AND CONNECT UP COMPLETE AND READY FOR SAFE AND REGULAR OPERATION THE PARTICULAR WORK REFERRED TO UNLESS SPECIFICALLY OTHERWISE NOTED.

E. PROVIDE 180 DEGREE ARC GALVANIZED METAL COVERING SHIELDS ON HANGERS FOR INSULATED PIPING WITHOUT INCOMPRESSIBLE INSULATING BLOCK IN INSULATION AT HANGERS.

2) "INSTALL": TO ERECT, MOUNT AND CONNECT COMPLETE WITH RELATED ACCESSORIES.

F.

MAXIMUM HANGER SPACING AS FOLLOWS: 1) PIPE 1 INCH AND SMALLER SHALL BE EVERY 8 FEET.

3) "FURNISH" OR "SUPPLY": TO PURCHASE, PROCURE, ACQUIRE AND DELIVER COMPLETE WITH RELATED ACCESSORIES.

2) PIPE 1-1/4 INCH AND LARGER SHALL BE EVERY 10 FEET. C. QUALITY ASSURANCE 3) COPPER TUBING 1-1/4 INCH AND SMALLER SHALL BE EVERY 6 FEET. 1) QUALITY AND GAUGE OF MATERIALS: NEW, BEST OF THEIR RESPECTIVE KINDS, FREE FROM DEFECTS AND LISTED BY UNDERWRITERS LABORATORIES, INC. OR BEARING THEIR LABEL. MATERIALS AND EQUIPMENT OF SIMILAR APPLICATION SHALL BE OF SAME MANUFACTURER, EXCEPT AS NOTED.

4) COPPER TUBING 1-1/2 INCH AND LARGER SHALL BE EVERY 10 FEET. 5) CAST IRON EVERY 5 FEET AND AT EVERY FITTING OR JOINT.

2) GUARANTEE: ALL MATERIALS AND WORKMANSHIP SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM DATE OF ACCEPTANCE OF WORK. D.

G.

2) CAST IRON PIPING SHALL BE SUPPORTED AT EVERY FLOOR LEVEL AT A MAXIMUM 10 FEET ON CENTER.

1) MOVING OF EQUIPMENT: WHERE NECESSARY, SHIP IN CARTED SECTIONS OF SIZE TO PERMIT PASSING THROUGH AVAILABLE SPACES. H. 2) ACCESSIBILITY: FOR OPERATION, MAINTENANCE AND REPAIR. MINOR DEVIATIONS SHALL BE PERMITTED. CHANGES OF MAGNITUDE OR INVOLVING EXTRA COST ARE NOT PERMISSIBLE WITHOUT REVIEW. GROUP CONCEALED VALVES AND EQUIPMENT REQUIRING ACCESS WITH EQUIPMENT FREELY ACCESSIBLE THROUGH ACCESS DOORS. E.

FINAL LOCATIONS AND MOUNTING ORIENTATIONS OF ALL PLUMBING FIXTURES, SHALL BE VERIFIED BY ARCHITECT.

F.

ALL ACCESS DOOR LOCATIONS, SHALL BE REVIEWED BY THE ARCHITECT PRIOR TO INSTALLATION.

VERTICAL PIPING: 1) GAS AND WATER PIPING SHALL BE SUPPORTED AT EVERY OTHER FLOOR LEVEL AT A MAXIMUM OF 25 FEET ON CENTER.

PRODUCT DELIVERY, STORAGE AND HANDLING

EXPANSION ANCHORS: 1) PROVIDE SMOOTH WALL, NON SELF DRILLING INTERNAL PLUG EXPANSION TYPE ANCHORS CONSTRUCTED OF AISC 12L14 STEEL AND ZINC PLATED. 2) DO NOT EXCEED 1/4 OF AVERAGE VALUES FOR SPECIFIC ANCHOR SIZE USING 2000 PSIG CONCRETE ONLY, FOR MAXIMUM WORKING LOADS.

SCOPE OF WORK: A. SCOPE OF WORK SHALL CONSIST OF PROVIDING LABOR, MATERIALS, EQUIPMENT, SERVICES AND FEES NECESSARY FOR COMPLETE AND SAFE INSTALLATION IN CONFORMITY WITH THE NEW YORK CITY PLUMBING CODE AND ALL OTHER APPLICABLE INDUSTRY, NATIONAL AND LOCAL CODES AND AUTHORITIES HAVING JURISDICTION, AS INDICATED ON DRAWINGS AND HEREIN SPECIFIED. B. THE BASE BUILDING DRAWINGS, PLANS , DETAILS, BUILDING WORK LETTERS, SPECIFICATIONS AND ADDENDA ARE MADE PART OF THIS CONTRACT AND SHALL APPLY TO ALL WORK UNDER THE CONTRACT UNLESS OTHERWISE AMENDED, MODIFIED, SUPPLEMENTED OR SPECIFIED HEREIN. C. THE CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE TO REPLACE OR REPAIR PROMPTLY AND ASSUME RESPONSIBILITY FOR ALL EXPENSES INCURRED FOR ANY WORKMANSHIP AND EQUIPMENT IN WHICH DEFECTS DEVELOP WITHIN ONE YEAR FROM THE DATE OF FINAL CERTIFICATE FOR PAYMENT AND/OR FROM DATE OF ACTUAL USE OF EQUIPMENT OR OCCUPANCY OF SPACES BY OWNER INCLUDED UNDER THE VARIOUS PARTS OF THE WORK, WHICH DATE IS EARLIER. THIS WORK SHALL BE DONE AS DIRECTED BY THE OWNER. THIS GUARANTEE SHALL ALSO PROVIDE THAT WHERE DEFECTS OCCUR, THE CONTRACTOR WILL ASSUME RESPONSIBILITY FOR ALL EXPENSES INCURRED IN REPAIRING AND REPLACING WORK OF OTHER TRADES AFFECTED BY DEFECTS, REPAIRS OR REPLACEMENTS IN EQUIPMENT SUPPLIED BY THE CONTRACTOR. D. THE CONTRACTOR SHALL GIVE NECESSARY NOTICE, FILE DRAWINGS AND SPECIFICATIONS WITH THE DEPARTMENT HAVING JURISDICTION, OBTAIN PERMITS OR LICENSES NECESSARY TO CARRY OUT THIS WORK AND PAY ALL FEES THEREFORE. THE CONTRACTOR SHALL ARRANGE FOR INSPECTION AND TESTS OF ANY OR ALL PARTS OF THE WORK IF SO REQUIRED BY AUTHORITIES AND PAY ALL CHARGES FOR SAME. THE CONTRACTOR SHALL PAY ALL COSTS FOR, AND FURNISH TO THE OWNER BEFORE FINAL BILLING, ALL CERTIFICATES NECESSARY AS EVIDENCE THAT THE WORK INSTALLED CONFORMS WITH ALL REGULATIONS WHERE THEY APPLY TO THIS WORK.

VALVES:

3) PROVIDE SPACING AND INSTALL ANCHORS IN ACCORDANCE WITH THE MANUFACTURE'S RECOMMENDATIONS. 4) EXPANSION ANCHORS SHALL BE U.L. LISTED AND MEA APPROVED SIMILAR TO HILTI HDI. 6.

PIPE AND FITTINGS: A.

11.

2) DURATION OF TEST SHALL BE 2 HOURS WITHOUT A LOSS IN PRESSURE. B. DRAINAGE AND VENT PIPING:

1) COPPER PIPE TYPE "L" WITH WROUGHT COPPER FITTINGS. MAKE UP JOINTS WITH LEAD FREE SOLDER. C.

MECHANICAL ENGINEER Abraham Joselow PC 45 W 34 Street Suite 1101 New York NY 10001 Tel (212) 736 2584 Fax (212) 736.0241

1) TEST PIPING HYDROSTATICALLY AT A PRESSURE OF 125 PSI.

DOMESTIC WATER

1-31-2014

TESTS: A. DOMESTIC WATER PIPING:

SANITARY, STORM DRAINAGE AND VENT 1) SERVICE WEIGHT NO HUB CAST IRON PIPE AND FITTINGS WITH HEAVY DUTY GASKETED HUBLESS COUPLINGS.

B.

BOARD REVIEW SET

1) CAP ALL OUTLETS AND FILL PIPING SYSTEM TO OVERFLOW FROM A POINT AT LEAST 10 FEET ABOVE FLOOR.

GAS

2) THE WATER SHALL REMAIN CONSTANT THROUGHOUT THE TEST DURATION OF 2 HOURS.

1) STANDARD WEIGHT BLACK STEEL, SCHEDULE 40, WELDED OR SEAMLESS, WITH MANUFACTURERS NAME ROLLED INTO EACH LENGTH.

C. GAS PIPING AS PER CON-ED. AND N.Y.C. CODE REQUIREMENTS. 2) FITTINGS SHALL BE THREADED STANDARD MALLEABLE IRON COUPLINGS WITH FLAT BAND. 12. D.

ALL EXPOSED PIPE AND FITTING SHALL HAVE THE SAME FINISH AS THE FIXTURE TRIM IN THE ROOM IN WHICH THEY ARE PROVIDED.

E.

ALL EXPOSED PIPING PASSING THROUGH WALLS, FLOORS, CEILINGS AND PARTITIONS SHALL BE PROVIDED WITH CAST BRASS ESCUTCHEONS HELD IN PLACE WITH SET SCREWS. ESCUTCHEON FINISH SHALL HAVE THE SAME FINISH AS THE FIXTURE TRIM IN THE ROOM IN WHICH THEY ARE PROVIDED.

F.

HEATING 1) PIPING SHALL BE COPPER TYPE "L" 2) FITTINGS SHALL BE WROUGHT COPPER WITH SWEAT JOINTS.

DISINFECTION: A. THE POTABLE WATER SYSTEM SHALL BE DISINFECTED PRIOR TO USE BY A METHOD OF DISINFECTION IN ACCORDANCE WITH THE NEW YORK CITY BUILDING CODE RS 16, P107.27. THE POTABLE WATER PURITY TEST RESULT FROM A NEW YORK CITY CERTIFIED TESTER SHALL BE SUBMITTED FOR ENGINEER'S REVIEW AND APPROVAL.

Endres Residence 161 West 75 St. Apt. 12 D & E New York NY 10023

Page Goolrick Architect P.C. 20 W 22nd Street NY NY 10010 phone 212.219.3666 email pg@goolrick.com www.goolrick.com

title:

PLUMBING: SPECIFICATIONS

scale:

AS NOTED

date:

05 December 2013

P-201.00