Virginia Beach Home Inspection Report

Page 1

Safe House Property Inspections Confidential Property Inspection Report Cover Page

1234 Anywhere Lane, Virginia Beach VA, 23456 Inspection prepared for: Mr. Sample & Mrs. Sample Inspection Date: 6/1/2009 Inspector: Troy Pappas NACHI ID# 09032603 Virginia Beach, VA, 23454 Phone: 757-418-0944 Email: troy@safehousepropertyinspections.com www.safehousepropertyinspections.com


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

Inspection and Site Details 1. Inspection Time Start: 09:00 AM

2. Attending Inspection Client present Buyer Agent present

3. Residence Type/Style Single Family Home

4. Garage/Carport Attached 1-Car Garage

5. Estimated Age of Home or Year Built BUILT IN • 1990

6. Square Footage Approx. 1775 sq ft Source:Zillow.com

7. Front of Home Faces East

8. Bedrooms and Bathrooms Number of Bedrooms: 3 Number of Bathrooms: 2 Full baths

9. Occupancy Occupied - Furnished

10. Temperature 75 degrees

11. Weather Conditions Clear, sunny sky

12. Ground/Soil Surface Condition Dry

13. Rain in the Last Three Days No

Page 1 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

Conventions and Terms Used in this Report USE OF PHOTOS: Your report includes many photographs. Some help clarify where I went, what I looked at, and the condition of the system or component at the time of the inspection. Some of the pictures may be of deficiencies or problem areas, these are to help you better understand what is documented in this report and may allow you see areas or items that you normally would not see. Not all problem areas or conditions will be supported with photos. TEXT COLOR SIGNIFICANCE: BLACK text: Denotes general/descriptive comments on the systems and components installed at the property. Limitations, if any, that restricted the inspection, associated with each area, are listed here as well. BLUE text: Denotes observations and information regarding the condition of the systems and components of the home. These include comments of deficiencies which are less than significant; or comments which further expand on a significant deficiency; or comments of recommendations, routine maintenance, tips, and other relevant resource information. RED text: Denotes a brief comment of significant deficient components or conditions which need attention, repair, or replacement. These comments are also duplicated in the Report Summary page(s). COMMENT KEY or DEFINITIONS: "NOT INSPECTED": I did not inspect this item, system, or component and make no representation of whether or not it was functioning as intended and I will state a reason for not inspecting. "NOT PRESENT": This item, system, or component is not in this home or building. "SAFETY CONCERN": A condition, system or component that is considered harmful or dangerous due its presence or absence. "DEFERRED COST": Denotes a system or component that is near or has reached its normal service life expectancy or shows indications that it may require repair or replacement anytime within the next five (5) years. "MAINTENANCE": Recommendations for the proper operation and routine maintenance of the home. "IMPROVE": Denotes improvements which are recommended but not required. These may be items identified to be upgraded to meet modern construction and/or safety standards. "FYI": For Your Information: Denotes additional general information and/or explanation of conditions; Safety information; Cosmetic issues; and useful tips or suggestions for home ownership.

Page 2 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

Exterior The inspector shall inspect: The siding, flashing and trim. All exterior doors, decks, stoops, steps, stairs, porches, railings, eaves, soffits and fascias. And report as in need of repair any spacing between intermediate balusters, spindles, or rails for steps, stairways, balconies, and railings that permit the passage of an object greater than four inches in diameter. A representative number of windows. The vegetation, surface drainage and retaining walls when these are likely to adversely affect the structure. And describe the exterior wall covering. The inspector is not required to: Inspect or operate screens, storm windows, shutters, awnings, fences, outbuildings, or exterior accent lighting, Inspect items, including window and door flashings, which are not visible or readily accessible from the ground, Inspect geological, geotechnical, hydrological and/or soil conditions, Inspect recreational facilities, Inspect seawalls, break-walls and docks, Inspect erosion control and earth stabilization measures, Inspect for safety type glass, Inspect underground utilities, Inspect underground items, Inspect wells or springs, Inspect solar systems, Inspect swimming pools or spas, Inspect septic systems or cesspools, Inspect playground equipment, Inspect sprinkler systems, Inspect drain fields or drywells, Determine the integrity of the thermal window seals or damaged glass.

1. Exterior Cladding Description: Vinyl Siding Observations:

• The hole in the exterior wall-covering cut to allow penetration of air-conditioning lines should be sealed with an appropriate sealant to prevent moisture and insect entry. • The vinyl siding covering has multiple areas of damage which should be repaired to prevent moisture intrusion of the wall assembly.

Page 3 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

2. Exterior Doors Description: Wood Observations:

• The frame for for the exterior garage entrance door is pulling away from the wall. The was no structural movement observed. The frame was most likely not secured properly during installation, and is pulling away due to use. Recommend repair by a qualified contractor.

3. Deck, Balcony Description: Wood Observations:

• The deck is in satisfactory and functional condition for its age.

4. Steps, Stoop, Porch Materials: Concrete • Brick • Front Porch: Observations: No deficiencies observed.

5. Eaves, Soffits, Fascias Description: Wood Observations: The fascia and soffits are in need of repair and maintenance in many areas. Have a qualified contractor repair or

replace these areas as needed. • The rear of the home is missing a large portion of the soffit which is allowing birds to nest. This can lead to health hazards. Have the nesting material removed and the soffit repaired by a qualified contractor.

Page 4 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

6. Windows Description: Vinyl Covered Observations:

• There are multiple damaged and poor fitting window screens.

7. Vegetation Affecting Structure Observations:

• There is vegetation growing against the exterior walls which may introduce pests and/or accelerate deterioration of the exterior wall covering by retaining moisture. I suggest removal or pruning back the vegetation from exterior walls.

8. Grading, Surface Drainage Description: The ground is sufficiently graded away from the house

9. Walkways Materials: Concrete

10. Driveway Materials: Concrete Observations:

• There are minor predictable and common cracks in the asphalt. Monitor these areas for further movement or expansion and repair/seal as needed.

Page 5 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

11. Patio Description: Brick pavers set in sand

12. Exterior Caulking Observations:

• The exterior window caulking is failing in a number of locations and should be repaired to maintain proper seal. • The caulking at the front stoop need to be repaired to prevent moisture intrusion.

13. Limitations of Exterior Inspection I am not an exterior expert. Feel free to hire an exterior contractor prior to closing. The exterior of the home was inspected and reported on with the above information. I make every effort to find all areas of concern, some areas can go unnoticed. Please be aware that I have your best interest in mind. Any repair items mentioned in this report should be considered before purchase. I recommend that qualified contractors be used in any further inspections or repairs as they relate to the comments in this inspection report.

Page 6 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

Roofing The inspector shall inspect from ground level or eaves: The roof covering; the gutters; the downspouts; the vents, flashings, skylights, chimney and other roof penetrations; and the general structure of the roof from the readily accessible panels, doors or stairs. The inspector is not required to: Walk on any pitched roof surface,predict the service life expectancy, inspect underground downspout diverter drainage pipes, remove snow, ice, debris or other conditions that prohibit the observation of the roof surfaces, move insulation, inspect antennae, lightning arresters, de-icing equipment, or similar attachments, walk on any roof areas that appear, in the opinion of the inspector, to be unsafe, walk on any roof areas if it might, in the opinion of the inspector, cause damage, perform a water test, warrant or certify the roof, confirm proper fastening.

1. Method of Roof Inspection I inspected the roof and its components by walking the roof.

2. Roof Style Gabled

3. Roof Drainage Description: Galvanized/Aluminum Observations:

• MAINTENANCE: Routinely monitor to keep gutters and gutter screens from clogging. A good time to check for proper gutter system operation is during a rainfall -- walk the perimeter of the house. Clean and seal gutters as needed. • There are a number of downspouts openings that have been crushed which will limit the ability of the system to drain properly. Have openings repaired in order for proper drainage.

4. Roof Covering Materials: Fiberglass-based asphalt shingles Age: Appears to be original roof covering • 20+ years Observations:

• There is no visible felt paper underlayment beneath the shingles. This is an improper installation. • There are areas of missing shingles and exposed roof sheathing. • There are exposed roofing nails in multiple locations. Water can penetrate into the framing and interior surfaces. I recommend the nails properly sealed to prevent water penetration • Due to the age and multiple issues with this roof I recommend that you have a qualified roofing contractor evaluate an appropriate course of action for repair or replacement.

Page 7 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

5. Flashings Materials: Metal • Rubber Observations:

• The roof is missing drip edge flashings leaving underlying framing exposed to the weather. Have drip edge installed by a qualified roofing contractor. • Vent flashings have exposed nail heads which need to be sealed to prevent moisture intrusion.

Page 8 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

6. Roof Penetrations Description: PVC Piping for plumbing vent stack(s) Observations:

• The rubber seals at a few vent pipes are deteriorated and have allowed moisture intrusion of the roof assembly. Have these vent pipes resealed by a qualified contractor.

7. Skylight(s) Description: raised-curb-type Observations:

• The roof includes an older skylight. Skylights are very prone to leaking. The sealant used to protect the skylight shows evidence of drying, shrinking and cracking,which may provide an avenue for moisture intrusion. Have the sealant should re-applied where necessary.

8. Chimney(s) Description: Metal flue--for gas fireplace • Framed Observations:

• The chimney cap is rusting. Have the rust removed and reseal and paint the chimney cap.

9. Limitations of Roofing Inspection I am not roofing expert. Feel free to hire a roofing contractor prior to closing. The roof of the home was inspected and reported on with the above information. I make every effort to find all areas of concern, some areas can go unnoticed. Roof coverings and skylights can appear to be leak proof during inspections and weather conditions. I make an attempt to find leaks during the inspection, but sometimes I cannot. Please be aware that I have your best interest in mind. Any repair items mentioned in this report should be considered before purchase. I recommend that qualified contractors be used in any further inspections or repairs as they relate to the comments in this inspection report.

Page 9 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

Foundation/Crawlspace The inspector shall inspect: The basement. The foundation. The crawlspace. The visible structural components. Any present conditions or clear indications of active water penetration observed by the inspector. And report any general indications of foundation movement that are observed by the inspector, such as but not limited to sheetrock cracks, brick cracks, out-of-square door frames or floor slopes. The inspector is not required to: Enter any crawlspaces that are not readily accessible or where entry could cause damage or pose a hazard to the inspector, Move stored items or debris, Operate sump pumps with inaccessible floats, Identify size, spacing, span, location or determine adequacy of foundation bolting, bracing, joists, joist spans or support systems, Provide any engineering or architectural service, Report on the adequacy of any structural system or component.

1. Foundation Type Slab on Grade

2. Foundation Floor Description: Concrete slab

3. Under Floor Crawlspace(s) Method of Inspection: NOT PRESENT: There is no crawlspace under this home.

Page 10 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

Heating The inspector shall inspect: The heating system and describe the energy source and heating method using normal operating controls. And report as in need of repair electric furnaces which do not operate. And report if inspector deemed the furnace inaccessible. The central cooling equipment using normal operating controls. The inspector is not required to: Inspect or evaluate interiors of flues or chimneys, fire chambers, heat exchangers, humidifiers, dehumidifiers, electronic air filters, solar heating systems, solar heating systems or fuel tanks. Inspect underground fuel tanks. Determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the heating system. Light or ignite pilot flames. Activate heating, heat pump systems, or other heating systems when ambient temperatures or when other circumstances are not conducive to safe operation or may damage the equipment. Override electronic thermostats. Evaluate fuel quality. Verify thermostat calibration, heat anticipation or automatic setbacks, timers, programs or clocks. Determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the cooling system. Inspect window units, through-wall units, or electronic air filters. Operate equipment or systems if exterior temperature is below 60 degrees Fahrenheit or when other circumstances are not conducive to safe operation or may damage the equipment. Inspect or determine thermostat calibration, heat anticipation or automatic setbacks or clocks. Examine electrical current, coolant fluids or gasses, or coolant leakage.

1. Thermostat(s) Description: Analog, non-programmable type.

2. Heating System Description: A forced air natural gas furnace was located in the attic. Age and Heating Capacity: 20+ Observations:

• The furnace was in operating condition at the time of the inspection. The furnace is at the end of its life expectancy. There is no evidence of any recent service. It would be wise to have a service call done by a qualified HVAC technician to more accurately determine the furnace’s condition and ensure that it is in the best possible working condition.

3. Energy Source For Heating: Natural Gas -- Gas meter located at • Garage For Cooling: Electric - 220/240 volt A/C

4. Safety Switch Observations:

• There are safety switches located in the garage below the attic access stairs, and near the equipment in the attic.

5. Distribution Systems Description: Flex ducting in attic - ceiling registers Observations:

• Air supply ducts routed through unheated space had damaged insulation. The ducts need to be repaired to prevent loss of heating and cooling capabilities. • There are improperly installed flex vents delivering air to the registers into the great room off of the kitchen. Have vents properly installed by a qualified HVAC technician.

Page 11 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

6. Combustion Air Observations:

• No deficiencies were observed.

7. Venting, Flue(s), Chimney(s) Materials: Metal double wall chimney vent pipe Observations:

• The exhaust flue has extensive rusting and is starting to fail. Have repaired by a qualified HVAC contractor.

8. Filter(s) Description: 20 x 20 x 1 • Located in ceiling of bedroom hallway Observations:

• MAINTENANCE: Inspect the filters each month to determine if they need to be replaced.

Page 12 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

Cooling 1. Cooling System Description: Air Cooled Central Air Conditioner Compressor Age and Cooling Capacity: APPROXIMATELY • 10 years • Approx 2 Tons - 24,000 BTU • Approx 2 Tons for the A/C unit - Zone#1

Observations:

• The exterior compressor/condensor is dirty and needs to be cleaned.

2. Condensate Drain Observations:

• The primary condensate drain is dripping on the insulation of the exterior low pressure refrigerant line causing it to deteriorate. Remove the damaged section of insulation, and replace so all of the line is covered. Have the drain extended to prevent future deterioration. • The emergency drain pipe from attic air handler drain-pan is draining into a gutter which is not appropriate. Have the drain line extended to a conspicuous location by a qualified HVAC contractor. • The condensate drain pan is full of water. There has been a failure in the primary condensate drainage system. There is potential for extensive ceiling damage if this pan overflows. Have a qualified HVAC contractor repair or replace the condensate drainage system.

3. Cooling Performance Supply Temperature: 65 Return Temperature: 80 Temperature Difference:

• This indicates the unit is cooling as intended.

Page 13 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

4. Fuse/Circuit Breaker Protection Compressor Placard Max: 20 Amps Observations:

• The circuit breaker protecting the central air conditioning unit--at the main electrical panel--is too large. The manufacturer specifies a maximum 20 Amp size breaker at the data plate, located on the exterior unit. In case of an electrical problem -- this oversized breaker might not trip in time to protect the A/C unit from damage or fire.

5. Limitations of Heating and Air Conditioning Inspection I am not an HVAC professional. Feel free to hire one prior to closing. The heating and cooling system of this home was inspected and reported on with the above information. While I made every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection consists of using only the normal operating controls for the system does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that I have your best interest in mind. Any repair items mentioned in this report should be considered before purchase. I recommend that qualified contractors be used in any further inspections or repairs as they relate to the comments in this inspection report.

Page 14 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

Plumbing The inspector shall: Verify the presence of and identify the location of the main water shutoff valve. Inspect the water heating equipment, including combustion air, venting, connections, energy sources, seismic bracing, and verify the presence or absence of temperature-pressure relief valves and/or Watts 210 valves. Flush toilets. Run water in sinks, tubs, and showers. Inspect the interior water supply including all fixtures and faucets. Inspect the drain, waste and vent systems, including all fixtures. Describe any visible fuel storage systems. Inspect the drainage sump pumps testing sumps with accessible floats. Inspect and describe the water supply, drain, waste and main fuel shut-off valves, as well as the location of the water main and main fuel shut-off valves. Inspect and determine if the water supply is public or private. Inspect and report as in need of repair deficiencies in the water supply by viewing the functional flow in two fixtures operated simultaneously. Inspect and report as in need of repair deficiencies in installation and identification of hot and cold faucets. Inspect and report as in need of repair mechanical drain-stops that are missing or do not operate if installed in sinks, lavatories and tubs. Inspect and report as in need of repair commodes that have cracks in the ceramic material, are improperly mounted on the floor, leak, or have tank components which do not operate. The inspector is not required to: Light or ignite pilot flames. Determine the size, temperature, age, life expectancy or adequacy of the water heater. Inspect interiors of flues or chimneys, water softening or filtering systems, well pumps or tanks, safety or shut-of valves, floor drains, lawn sprinkler systems or fire sprinkler systems. Determine the exact flow rate, volume, pressure, temperature, or adequacy of the water supply. Determine the water quality or potability or the reliability of the water supply or source. Open sealed plumbing access panels. Inspect clothes washing machines or their connections. Operate any main, branch or fixture valve. Test shower pans, tub and shower surrounds or enclosures for leakage. Evaluate the compliance with local or state conservation or energy standards, or the proper design or sizing of any water, waste or venting components, fixtures or piping. Determine the effectiveness of anti-siphon, back-flow prevention or drain-stop devices. Determine whether there are sufficient clean-outs for effective cleaning of drains. Evaluate gas, liquid propane or oil storage tanks. Inspect any private sewage waste disposal system or component of. Inspect water treatment systems or water filters. Inspect water storage tanks, pressure pumps or bladder tanks. Evaluate time to obtain hot water at fixtures, or perform testing of any kind to water heater elements. Evaluate or determine the adequacy of combustion air. Test, operate, open or close safety controls, manual stop valves and/or temperature or pressure relief valves. Examine ancillary systems or components, such as, but not limited to, those relating to solar water heating, hot water circulation.

1. Water Supply Source: Public municipal water supply

2. Main Water Shut Off Location: Below ground at end of driveway

3. Water Heater(s) Description: Manufacturer • Rheem Capacity: 40 Gallons

4. Water Heater Vent System Materials: Metal double wall chimney vent pipe

5. Water Heater(s) Condition Age: 18+ years Observations:

• The water heater is functioning as intended, but is past the end of its typical service life. I suggest that you start budgeting for replacement in the near future.

6. Main Service Piping Materials: Copper

7. Exterior Hose Bibs/Spigots Description: Standard hose bib in front, and rear of home.

8. Water Supply, Distribution Systems Description: Copper

Page 15 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

9. Faucets Observations:

• No deficiencies observed.

10. Sinks Observations:

• No deficiencies observed.

11. Waste, Drain, Vent Piping Waste System Type: Public sewage disposal system Description: Visible waste piping in house: • PVC (Polyvinyl Chloride) - normally white in color Observations: • Visible piping was operating as intended at time of inspection.

12. Fuel Storage, Distribution Description: Black iron pipe used for gas branch/distribution service Shut Off: Main gas shut off located at outside meter

13. Traps and Drains Observations:

• There is a double trap under the double kitchen sink which can cause clogging of the plumbing system. Have a qualified plumber install a single trap for both sinks.

14. Flow and Pressure Observations:

• The water flow was adequate. This was determined by running water in the bath sink and shower while toilet is flushed.

15. Limitations of Plumbing Inspection The plumbing in the home was inspected and reported on with the above information. While I make every effort to find all areas of concern, some areas can go unnoticed. Washing machine drain line for example cannot be checked for leaks or the ability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed and barely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant home waiting for closing) rust or deposits within the pipes can further clog the piping system. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. I recommend that qualified contractors be used in any further inspections or repairs as they relate to the comments in this inspection report.

Page 16 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

Electrical The inspector shall inspect: The service line. The meter box. The main disconnect. And determine the rating of the service amperage. Panels, breakers and fuses. The service grounding and bonding. A representative sampling of switches, receptacles, light fixtures, AFCI receptacles and test all GFCI receptacles and GFCI circuit breakers observed and deemed to be GFCI's during the inspection. And report the presence of solid conductor aluminum branch circuit wiring if readily visible. And report on any GFCI-tested receptacles in which power is not present, polarity is incorrect, the receptacle is not grounded, is not secured to the wall, the cover is not in place, the ground fault circuit interrupter devices are not properly installed or do not operate properly, or evidence of arcing or excessive heat is present. The service entrance conductors and the condition of their sheathing. The ground fault circuit interrupters observed and deemed to be GFCI's during the inspection with a GFCI tester. And describe the amperage rating of the service. And report the absence of smoke detectors. Service entrance cables and report as in need of repair deficiencies in the integrity of the insulation, drip loop, or separation of conductors at weatherheads and clearances. The inspector is not required to: Insert any tool, probe or device into the main panel, sub-panels, downstream panel, or electrical fixtures. Operate electrical systems that are shut down. Remove panel covers or dead front covers if not readily accessible. Operate over current protection devices. Operate non-accessible smoke detectors. Measure or determine the amperage or voltage of the main service if not visibly labeled. Inspect the alarm system and components. Inspect the ancillary wiring or remote control devices. Activate any electrical systems or branch circuits which are not energized. Operate overload devices. Inspect low voltage systems, electrical de-icing tapes, swimming pool wiring or any time-controlled devices. Verify the continuity of the connected service ground. Inspect private or emergency electrical supply sources, including but not limited to generators, windmills, photovoltaic solar collectors, or battery or electrical storage facility. Inspect spark or lightning arrestors. Conduct voltage drop calculations. Determine the accuracy of breaker labeling.

1. Service Drop Description: Underground service lateral • METER LOCATION • Outside garage entrance door

2. Main Disconnect Description: One 150 Amp Breaker on Main Service Panel

3. Service Entrance Conductors Description:

2/0 Aluminum

4. Service Rating 150 amps

5. Main Service Panel(s) Description: MANUFACTURER • General Electric Observations:

• There is some rust inside the service panel which indicates that there has been moisture intrusion. Have the panel seal by a qualified electrical contractor.

Page 17 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

6. Service Grounding Description: Copper • Water Pipe Connection • Ground Rod Connection

7. Overcurrent Protection Type: Breakers

8. Wiring Methods Description: Copper Observations:

• There is a missing junction box in the upper attic next to the attic access. Have a qualified electrical contractor install a junction box to house this wiring.

9. Lighting, Fixtures Description: Grounded Observations:

• The lighting fixture above the guest bathroom is not properly secured. Have the fixture secured to the wall to prevent the wiring from being exposed.

Page 18 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

10. Receptacles Observations:

• There is an extension cord being used a power source at the counter to the left of the stove top. There is no electrical outlet installed at the counter. There should be an outlet installed above the counter. Have a qualified electrical contractor install an outlet. • There are missing outlet cover plates in various rooms in the home. This condition leaves energized electrical components exposed to touch, a shock/electrocution hazard. Have these cover plates installed.

11. Switches Observations:

• Some switches in the home appeared to be inoperable at the time of the inspection. These switches may connect to exterior lights which are controlled by photo sensors and so will operate only at night. They may be improperly wired and represent a potential fire hazard or they may connect to outlets which were not tested. You should take action to confirm that these switches are safe, either by asking the seller or having them traced by a qualified electrician.

Page 19 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

12. GFCI Definition: Ground Fault Circuit Interrupter - GFCI - is an electrical safety device that cuts power to an individual outlet and/or entire

circuit when as little as .005 amps is detected leaking--this is faster than a person's nervous system can react! Kitchens, bathrooms. whirlpools/hot-tubs, unfinished basements, garages, and exterior circuits are normally GFCI protected. This protection is from electrical shock. Locations & Resets: PRESENT AT • Bathrooms • Kitchen • Exterior

Observations:

• The exterior GFCI outlet above the deck is damaged. Have a qualified electrical contractor replace.

13. AFCI Definition: AFCIs are newly developed electrical devices designed to protect against fires caused by arcing faults in the home’s wiring. Arc faults can be created by damaged, deteriorated, or worn electrical plugs, cords, and/or branch circuit conductors. AFCIs are required in new construction under current building standards which have been adopted in most jurisdictions across the country. AFCIs are currently only required for bedroom circuits but may be required for whole home protection in future updates of building standards and regulations. Older homes with aging and deteriorating wiring systems can especially benefit from the added protection of AFCIs. You may wish to consult with a qualified electrical contractor concerning options and costs for updating bedroom branch circuits to AFCI protection for safety reasons. Locations & Resets: None Found

14. Smoke/Heat Detector(s) Description: PRESENT AT • Hallway leading to bedrooms • Rear Great room Observations:

• IMPROVE: Recommend installing one in each bedroom to bring up to modern safety standards. A qualified contractor should be used to install smoke detectors that are hard wired to the house electrical system.

Page 20 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

15. Carbon Monoxide (CO) Detector(s) Description: There are no CO detectors in this home Observations:

• I recommend installation of Carbon Monoxide detectors in appropriate locations. Proper placement of a carbon monoxide detector is important. If you are installing only one carbon monoxide detector, the Consumer Product Safety Commission (CPSC) recommends it be located near the sleeping area where it can wake you if you are asleep. Additional detectors on every level and in every bedroom of a home provides extra protection. Homeowners should remember not to install carbon monoxide detectors directly above or beside fuelburning appliances, as appliances may emit a small amount of carbon monoxide upon start-up. A detector should not be placed within fifteen feet of heating or cooking appliances or in or near very humid areas such as bathrooms.

16. Limitations of Electrical Inspection I am not an electrician. Feel free to hire an electrician prior to closing. The electrical system of the home was inspected and reported on with the above information. While I make every effort to find all areas of concern, some areas can go unnoticed. Outlets were not removed and the inspection was only visual. Any outlet not accessible (behind the refrigerator for example) was not inspected or accessible. Please be aware that I have your best interest in mind. Any repair items mentioned in this report should be considered before purchase. I recommend that qualified contractors be used in any further inspections or repairs as they relate to the comments in this inspection report.

Page 21 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

Fireplace The inspector shall inspect: The fireplace, and open and close the damper door if readily accessible and operable. Hearth extensions and other permanently installed components. And report as in need of repair deficiencies in the lintel, hearth and material surrounding the fireplace, including clearance from combustible materials. The inspector is not required to: Inspect the flue or vent system. Inspect the interior of chimneys or flues, fire doors or screens, seals or gaskets, or mantels. Determine the need for a chimney sweep. Operate gas fireplace inserts. Light pilot flames. Determine the appropriateness of such installation. Inspect automatic fuel feed devices. Inspect combustion and/or make-up air devices. Inspect heat distribution assists whether gravity controlled or fan assisted. Ignite or extinguish fires. Determine draft characteristics. Move fireplace inserts, stoves, or firebox contents. Determine adequacy of draft, perform a smoke test or dismantle or remove any component. Perform an NFPA inspection.

1. Gas Fireplace(s) Description: LOCATION • Dual fireplace for living and dining rooms Observations: • Operated normally when tested

2. Limitations of Fireplace Inspection The Fireplace system of this home was inspected and reported on with the above information but it is incomplete. The liner or the safety aspect of the liner was not inspected. The inspection is not meant to be technically exhaustive and does not substitute an inspection by a certified chimney sweep. The inspection does not determine the safety of the fireplace in terms of the condition of liner or the absence of a liner. Any comments I have reported do not remove the need for an inspection by a certified chimney sweep. Chimneys should be inspected at least annually. Please be aware that the I have your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that a certified chimney sweep inspect the liner for safe operation.

Page 22 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

Interior The home inspector shall observe: Walls, ceiling, and floors; Steps, stairways, balconies, and railings; Counters and a representative number of installed cabinets; and A representative number of doors and windows. The home inspector shall: Operate a representative number of windows and interior doors; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; Carpeting; or Draperies, blinds, or other window treatments. The inspector shall: Open and close a representative number of doors and windows. Inspect the walls, ceilings, steps, stairways, and railings. Inspect garage doors and garage door openers by operating first by remote (if available) and then by the installed automatic door control. And report as in need of repair any installed electronic sensors that are not operable or not installed at proper heights above the garage door. And report as in need of repair any door locks or side ropes that have not been removed or disabled when garage door opener is in use. And report as in need of repair any windows that are obviously fogged or display other evidence of broken seals. The inspector is not required to: Inspect paint, wallpaper, window treatments or finish treatments. Inspect central vacuum systems. Inspect safety glazing. Inspect security systems or components. Evaluate the fastening of countertops, cabinets, sink tops and fixtures, or firewall compromises. Move furniture, stored items, or any coverings like carpets or rugs in order to inspect the concealed floor structure. Move drop ceiling tiles. Inspect or move any household appliances. Inspect or operate equipment housed in the garage except as otherwise noted. Verify or certify safe operation of any auto reverse or related safety function of a garage door. Operate or evaluate security bar release and opening mechanisms, whether interior or exterior, including compliance with local, state, or federal standards. Operate any system, appliance or component that requires the use of special keys, codes, combinations, or devices. Operate or evaluate self-cleaning oven cycles, tilt guards/latches or signal lights. Inspect microwave ovens or test leakage from microwave ovens. Operate or examine any sauna, steam-jenny, kiln, toaster, ice-maker, coffee-maker, can-opener, bread-warmer, blender, instant hot water dispenser, or other small, ancillary devices. Inspect elevators. Inspect remote controls. Inspect appliances. Inspect items not permanently installed. Examine or operate any above-ground, movable, freestanding, or otherwise non-permanently installed pool/spa, recreational equipment or self-contained equipment. Come into contact with any pool or spa water in order to determine the system structure or components. Determine the adequacy of spa jet water force or bubble effect. Determine the structural integrity or leakage of a pool or spa.

1. Wall and Ceiling Finishes Materials: Drywall Observations:

• There are multiple large stains on the ceiling of the back great room. There was no evidence of current moisture intrusion observed at the ceiling or in the attic space above. There is evidence of a prior repair in the roof directly above this area of the ceiling. I suggest you monitor this area to determine if future action will be necessary to correct the problem. • The drywall in the dining room had some buckling due to moisture intrusion caused by the secondary condensate drain prior to it being extended. There was no moisture detected at the time of the inspection. Due to the prior moisture damage there is a high probability of damage behind the wall. I recommend having the wall repaired by a qualified contractor.

Page 23 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

2. Floor Finishes Materials: Laminate • Ceramic tile Observations:

• Carpet

• There were mutilple areas missing baseboard trim and mouldings. • Carpeting exhibited moderate wear with areas of severe wear. Consider getting estimates from a qualified flooring contractor to gain an idea of options and costs for replacement.

3. Windows Description: Vinyl Observations:

• The double pane window in the living room has failed. Have a qualified contractor repair or replace.

Page 24 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

4. Interior Doors Description: Hollow core wood doors

5. Closets Observations:

• Missing one of the bi-fold doors in bedroom across from guest bathroom.

6. Countertops Materials: Laminate Observations:

• The underside of the laminate counter top above the dishwasher has some water damage. Have this area sealed to prevent any further damage.

7. Cabinets, Vanities Materials: Wood laminate Observations:

• Although the kitchen cabinets were old and appeared to be original, they were in generally serviceable condition at the time of the inspection. Except where noted. • The shelf under the kitchen sink is damaged. Have a qualified contractor replace or repair.

8. Limitations of Interior Inspection The interior of the home was inspected and reported on with the above information. While I make every effort to find all areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view. Please be aware that I have your best interest in mind. Any repair items mentioned in this report should be considered before purchase. I recommend that qualified contractors be used in any further inspections or repairs as they relate to the comments in this inspection report.

Page 25 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

Built-in Appliances The home inspector shall: Observe and operate the basic functions of the following kitchen appliances: Permanently installed dishwasher, through its normal cycle; Range, cook top, and permanently installed oven; Trash compactor; Garbage disposal; Ventilation equipment or range hood; and Permanently installed microwave oven. The home inspector is not required to observe: Clocks, timers, self-cleaning oven function, or thermostats for calibration or automatic operation; Non built-in appliances; or Refrigeration units. The home inspector is not required to operate: Appliances in use; or Any appliance that is shut down or otherwise inoperable.

1. Dishwasher Description: Maytag Observations:

• I ran the dish washer through one cycle and appeared to be in working order at time of inspection.

2. Garbage Disposal Description: InSinkErator Observations:

• The disposal was functional at the time of inspection.

3. Ranges, Ovens, Cooktops Observations:

• The gas burners all functioned as intended when I turned them on, and the oven heated up when turned on.

4. Microwave Description: GE

5. Refrigerator Description: Whirlpool Observations:

• NOT INSPECTED: Refrigerator was present

6. Washer Description: Maytag Observations:

• I ran the washer through one full cycle. The washer filled with water, agitated, spun, and drained. This does not in anyway confirm how well the machine washes clothes.

7. Dryer Description: Maytag Observations:

• FYI: Three prong 220 Volt electrical outlet installed. You will have to convert a new dryer's four prong cord to fit this three prong outlet.

Page 26 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

8. Dryer Vent Observations:

• The dryer vent is crushed where it exits the rear of the dryer. Replace the vent and protect it from being crushed in the future. • There is an abandoned exterior dryer vent that has not been properly terminated which can allow intrusion by moisture or animals. Have a qualified contractor remove or seal this vent.

9. Limitations of Appliances Inspection The built-in appliances of the home were inspected reported on with the above information. Even though I make every effort to find all areas of concern, some areas can go unnoticed. Please be aware that I have your best interest in mind. I recommend that qualified contractors be used in any further inspections or repairs as they relate to the comments in this inspection report.

Page 27 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

Attic, Ventilation, and Insulation The inspector shall inspect: The insulation in unfinished spaces, the ventilation of attic spaces, mechanical ventilation systems, and report on the general absence or lack of insulation in unfinished spaces. The inspector is not required to: Enter the attic or any unfinished spaces that are not readily accessible, or where entry could cause damage or pose a safety hazard to the inspector, in his or her opinion, to move, touch, or disturb insulation, to move, touch or disturb vapor retarders, break or otherwise damage the surface finish or weather seal on or around access panels and covers, identify the composition or exact R-value of insulation material, activate thermostatically operated fans, determine the types of materials used in insulation or wrapping of pipes, ducts, jackets, boilers and wiring, determine the adequacy of ventilation.

1. Attic Access Attic Inspection Method: I inspected attic by crawling the ceiling truss framing Type of Access: Pull Down Ladder located in: Garage Observations: The pull down stairs do not meet the firewall requirements for the garage. Have repaired by a qualified contractor.

2. Insulation in Unfinished Spaces Description: Attic Insulation: • Cellulose, loose fill Depth/R-Value: Approximately: • 9-12 inches Observations:

• The insulation level was not adequate near the damaged soffit. Have the soffit repaired and insulation levels corrected by a qualified contractor.

3. Attic Ventilation Description: Under eave soffit inlet vents

• Static roof vents

4. Vent Piping Through Attic Description: PVC plumbing vents

5. Ceiling, Roof Structure Description: Engineered wood roof truss framing • Rafters Observations: • There were no deficiencies were observed in visible areas.

6. Limitations of Attic and Insulation Inspection The insulation and ventilation of the home was inspected and reported on with the above information. While I make every effort to find all areas of concern, some areas can go unnoticed. Venting of exhaust fans or clothes dryer cannot be fully inspected and bends or obstructions can occur without being accessible or visible (behind wall and ceiling coverings). Only insulation that is visible was inspected. Please be aware that I have your best interest in mind. Any repair items mentioned in this report should be considered before purchase I recommend that qualified contractors be used in any further inspections or repairs as they relate to the comments in this inspection report.

Page 28 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

Garage 1. Garage Door(s) Description: Fiberglass Observations:

• I recommend placing weather stripping on both sides of garage door.

2. Garage Door Opener(s) Description: Craftsman • 1/2 Horsepower Observations:

• The garage door was functional using normal controls. • The outdoor keypad opener was not tested due to not having code. I recommend getting the code from the homeowner to determine if the keypad is operational.

3. Garage Door Safety Features Safety Reverse: Present Safety Sensor: Present Observations:

• Safety sensors operated normally, reversing the door when tested.. • The automatic garage door opener(s) reversed direction when met with resistance.

4. Garage Floor, Sill Plates Description: Concrete

5. Garage Firedoor Material: Present

Page 29 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

Bathrooms 1. Faucets Observations:

• No deficiencies were observed.

2. Sinks Observations:

• There are stoppers missing or inoperable in both bathrooms. • The cold water shut off handle at the left sink in the master bathroom has a slow leak. The two gallon bucket below the handle is not an appropriate long term solution. Have a qualified plumbing contractor repair or replace. • The pedastal sink in the guest bathroom is not secured to the wall. Have a qualified contractor repair as needed.

3. Tub(s) Description: Plastic/Fiberglass Observations:

• There were no deficiencies observed at time of inspection.

4. Shower(s) Description: Plastic/Fiberglass Observations:

• There were no deficiencies observed at time of inspection.

5. Toilet(s) Observations:

• All toilets flushed properly and no deficiencies were observed.

6. Bathroom Exhaust Fan(s) Observations:

• Operated when tested.

7. Limitations of Bathroom Inspection All bathroom fixtures, including toilets, tubs, showers, and sinks are inspected. Readily visible water-supply and drain pipes are inspected. Plumbing access panels are opened, if readily accessible and available to open. Normal foot pressure is applied around the base of each toilet, tub, and shower to check for deteriorated flooring. Normal hand pressure is applied carefully to the walls of each shower to check for deterioration. Re-grouting and sealant around the tub shower, and fixtures should be considered routine maintenance. I do not perform water leak tests on drain lines or shower pans. I simply look for active leaks, which is quite limited by my short time in the property. Any repair items mentioned in this report should be considered before purchase. I recommend that qualified contractors be used in any further inspections or repairs as they relate to the comments in this inspection report.

Page 30 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

Report Summary Report Summary

REPORT CONCLUSION &WALK-THROUGH CONCLUSION: I am proud of the service I provide, and trust that you will be happy with the quality of my report. I have made every effort to provide you with an accurate assessment of the condition of the property and its components and to alert you to any significant defects or adverse conditions. However, I may not have tested every outlet, and opened every window and door, or identified every problem. Also because my inspection is essentially visual, latent defects could exist. I cannot see behind walls. Therefore, you should not regard my inspection as a guarantee or warranty. It is simply a report on the general condition of a property at a given point in time. As a homeowner, you should expect problems to occur. Roofs will leak, basements may have water problems, and systems may fail without warning. I cannot predict future events. For these reasons, you should keep a comprehensive insurance policy current. This report was written exclusively for my client. It is not transferable to other people. The report is only supplemental to a seller's disclosure. Thank you for taking the time to read this report, and call me if you have any questions. I am always attempting to improve the quality of my service and my report. PRE-CLOSING WALK THROUGH: The walk-through prior to closing is the time for Client to inspect the property. Conditions may change between the time of a home inspection and the time of closing. Restrictions that existed during the inspection may have been removed for the walk-through. Defects or problems that were not found during the home inspection may be discovered during the walk-through. Client should be thorough during the walk-through. Any defect or problem discovered during the walk-through should be negotiated with the owner/seller of the property prior to closing. Purchasing the property with a known defect or problem releases Safe House Property Inspections of all responsibility. Client assumes responsibility for all known defects after settlement. Sincerely, Troy Pappas, Owner Safe House Property Inspections

Page 31 of 33


Safe House Property Inspections

1234 Anywhere Lane, Virginia Beach, VA

IMPORTANT: This following items are a brief summary of the significant deficiencies or critical concerns which are important to highlight as they relate to function or safety. Some of these items may warrant further investigation by a specialist. This is only a summary and is provided as a courtesy— it should not be considered to be the complete report. The complete list of issues, concerns, deficiencies and important details pertaining to this property is found throughout the body of the inspection report. Your entire report must be carefully read to fully assess all of the findings and benefit from the recommendations, maintenance advice, tips and other important resource information.

Exterior Page 3 Item: 1

Exterior Cladding

Page 5 Item: 5

Eaves, Soffits, Fascias

• The vinyl siding covering has multiple areas of damage which should be repaired to prevent moisture intrusion of the wall assembly. • The rear of the home is missing a large portion of the soffit which is allowing birds to nest. This can lead to health hazards. Have the nesting material removed and the soffit repaired by a qualified contractor.

Roofing Page 8 Item: 4

Roof Covering

Page 9 Item: 5

Flashings

Page 9 Item: 6

Roof Penetrations

• There is no visible felt paper underlayment beneath the shingles. This is an improper installation. • There are areas of missing shingles and exposed roof sheathing. • There are exposed roofing nails in multiple locations. Water can penetrate into the framing and interior surfaces. I recommend the nails properly sealed to prevent water penetration • Due to the age and multiple issues with this roof I recommend that you have a qualified roofing contractor evaluate an appropriate course of action for repair or replacement. • The roof is missing drip edge flashings leaving underlying framing exposed to the weather. Have drip edge installed by a qualified roofing contractor. • Vent flashings have exposed nail heads which need to be sealed to prevent moisture intrusion. • The rubber seals at a few vent pipes are deteriorated and have allowed moisture intrusion of the roof assembly. Have these vent pipes resealed by a qualified contractor.

Heating Distribution Systems Venting, Flue(s), Chimney(s)

• There are improperly installed flex vents delivering air to the registers into the great room off of the kitchen. Have vents properly installed by a qualified HVAC technician.

Page 13 Item: 2

Condensate Drain

Page 14 Item: 4

Fuse/Circuit Breaker Protection

• The condensate drain pan is full of water. There has been a failure in the primary condensate drainage system. There is potential for extensive ceiling damage if this pan overflows. Have a qualified HVAC contractor repair or replace the condensate drainage system. • The circuit breaker protecting the central air conditioning unit--at the main electrical panel--is too large. The manufacturer specifies a maximum 20 Amp size breaker at the data plate, located on the exterior unit. In case of an electrical problem -- this oversized breaker might not trip in time to protect the A/C unit from damage or fire.

Page 12 Item: 5 Page 12 Item: 7

• The exhaust flue has extensive rusting and is starting to fail. Have repaired by a qualified HVAC contractor.

Cooling

Electrical Page 18 Item: 8

Wiring Methods

Page 19 Item: 10 Receptacles Page 20 Item: 12 GFCI

• There is a missing junction box in the upper attic next to the attic access. Have a qualified electrical contractor install a junction box to house this wiring. • There are missing outlet cover plates in various rooms in the home. This condition leaves energized electrical components exposed to touch, a shock/electrocution hazard. Have these cover plates installed. • The exterior GFCI outlet above the deck is damaged. Have a qualified electrical contractor replace.

Interior Page 24 Item: 1

Wall and Ceiling Finishes

• The drywall in the dining room had some buckling due to moisture intrusion caused by the secondary condensate drain prior to it being extended. There was no moisture detected at the time of the inspection. Due to the prior moisture damage there is a high probability of damage behind the wall. I recommend having the wall repaired by a qualified contractor.

Attic, Ventilation, and Insulation Page 28 Item: 1

Attic Access

• The pull down stairs do not meet the firewall requirements for the garage. Have repaired by a qualified contractor.

Bathrooms Page 32 of 33


Safe House Property Inspections Page 30 Item: 2

Sinks

1234 Anywhere Lane, Virginia Beach, VA

• The pedastal sink in the guest bathroom is not secured to the wall. Have a qualified contractor repair as needed.

Page 33 of 33