About TTAF® TTAF Elektronik Ltd was founded in Turkey to prove cable assemblies, wiring harnesses, custom design interconnect solutions for military and civilian electronics as well as total system solutions for telecommunication applications including: wiring harnesses, cable assemblies, optical fibre, multi-branched, power, RF, moulded, electromechanical assemblies, racks, panels , control boxes and lighting systems. Servicing diverse customers worldwide from the state of the art 6,000 m2 manufacturing facilities in Istanbul , TTAF is now a global wire harness and cable assembly leader with in-house tool and die-making facility for injection and moulding capabilities. After more than 30 years in the connector marketplace, TTAF capitalised to create our wire harness and cable assembly services offering wiring harness assemblies using optimum grade wire and materials with the aid of cutting-edge machines to meet electronic industry norms. TTAF facilities are certified to meet the most demanding quality standards including ISO9001:2008, UL, CE, IPC / WHMA-A-620B, AS9100C and ISO 16949:2009. TTAF is a 3P & ETL certified telecom system provider and a USB and HDMI certified cable assembly manufacturer.
İstanbul | TÜRKİYE
Shenzhen | CHINA
Headquarters & Manufacturing
R&D Office
JoinExpanding The
World
of
TTAF
Today!
TTAF® Hakkında TTAF kablo gruplama ve bağlantı elemanları konusunda müşteriye özel ürün dizaynları ve farklı ihtiyaçlara yönelik çözümleriyle; hem Türkiye’de, hem dünya çapında güven ve beğeni kazanmış uzman bir kuruluştur. Konnektör alanında uzun yılların deneyimiyle 2003 yılında Beylikdüzü’nde 6,000 m2 kapalı alanda kablo grubu üretimine başlayan TTAF, ilk olarak kahverengi eşya sektörüne yan sanayi olarak hizmet vermiş, zaman içinde teknolojiye yapılan yatırımlarla, kazanılan bilgi, birikim ve vizyonla birlikte savunma sanayi , otomotiv, endüstriyel ve telekom sektörlerinin de ihtiyaçlarını karşılar hale gelmiştir. TTAF fiber optikten güç ve RF bağlantılarına, plastik enjeksiyonlu kablolardan elektromekanik çözümlere, panellere, kontrol kutularına ve led aydınlatma çözümlerine uzanan geniş bir yelpazede komple sistem çözümleri sağlamakta ve an itibariyle 65 ülkeye ihracat yapmaktadır. ISO 9001:2008, IPC/WHMA-A-620B, UL, CE, AS9100C ve ISO 16949:2009 kalite belgelerine sahip olan TTAF; aynı zamanda 3P ve ETL sertifikalı bir Telekom sistem sağlayıcısı ve USB & HDMI organizasyonları tarafından onaylı bir üreticidir.
EXPROOF LIGHTING SYSTEMS
Waterproof FIELD ASSEMBLY CONNECTOR SERIES IP68
Waterproof Field Assembly Junction ‘T’ Connector TECHNICAL SPECIFICATIONS
ART NO
WPT-0303M15-NN/00
Voltage Rating
250 Volts AC
Current Rating
15 Amps maximum
Min Wire Size OD
6 mm
Max Wire Size OD
10 mm
Contact Resistance
10 mΩ
Insulation Structure
500 MΩ at 500 Volts DC
Temperature Rating
-40 °C + 105 °C
IP Rating
IP 68
Mould Material
PA 66
Contact / Terminal Material
Nickel plated brass
Seal Material
EPDM 70Sh A
Number of Poles
3
Current Rating
15 Amps maximum
Voltage Rating
500 Volts AC
Durability Voltage
1500 Volts AC
ttaf.com.tr
IP68
Waterproof Field Assembly In-line ‘I’ Connector TECHNICAL SPECIFICATIONS
ART NO
WPI-0302M15-NN/00
Voltage Rating
250 Volts AC
Current Rating
15 Amps maximum
Min Wire Size (OD)
6 mm
Max Wire Size (OD)
10 mm
Contact Resistance
10 mΩ
Insulation Structure
500 MΩ at 500 Volts DC
Temperature Rating
-40 °C + 105 °C
IP Rating
IP 68
Mould Material
PA 66
Contact / Terminal Material
Nickel plated brass
Seal Material
EPDM 70 Sh A
Number of Poles
3
Current Rating
15 Amps maximum
Voltage Rating
500 Volts AC
Durability Voltage
1500 Volts AC
EXPROOF LIGHTING SYSTEMS
EXL-01 SERIES HIGH POWER EXPLOSION PROOF LED FLOODLIGHT
APPLICATIONS
»» »» »» »» »»
Designed and manufactured for the oilfield, chemical, steel, power, port and petroleum industries. Ideal for harsh environments with high levels of humidity and moisture. Suitable for gas explosive environments to group IIA, IIB and IIC requirements. Compliant with Zone 1, Zone2, Zone 21 and Zone 22 category areas. Temperature class areas from T1 to T6. PRODUCT FEATURES
»» Dual cable inlet system allowing for luminaries to be mounted in parallel or series configurations. »» Employs the highest specification industry recognised components, such as Cree LED light engines combined with a Mean-Well power supply. (PSU / driver) »» Isolated LED chip-and-lens design improves thermal conductivity and ensures a market-leading product lifespan. »» Dual purpose. This unit can function as either a high bay or floodlight dependent on installation and lens specification. »» In-built heat sink balances unit efficiency with extreme structural integrity.
ttaf.com.tr
TECHNICAL SPECIFICATIONS
ART NO
EXL-01050U
EXL-01075U
EXL-01100U
EXL-01120U
LED Device
Cree
Cree
Cree
Cree
Lumen Output
4,925 lm (+/-5%)
6,015 lm (+/-5%)
9,195 lm (+/-5%)
11,440 lm (+/-5%)
Nominal Power Rating
50 Watts
75 Watts
96,5 Watts
120 Watts
Efficiency
98,5 lm / W
80,2 lm / W
95,3 lm / W
95,3 lm / W
Beam Angle (W/H)
90°(Standard), 60°, 120/140°
90°(Standard), 60°, 120/140°
90°(Standard), 60°, 120/140°
90°(Standard), 60°, 120/140°
Colour Temperature
5,000° Kelvin
5,000° Kelvin
5,000° Kelvin
5,000° Kelvin
Colour Rendering Index (CRI)
> 80 Ra
> 80 Ra
> 80 Ra
> 80 Ra
Lumen Maintenance
L70 > 50,000 Hours
L70 > 50,000 Hours
L70 > 50,000 Hours
L70 > 50,000 Hours
Input Voltage
90-305 Volts AC
90-305 Volts AC
90-305 Volts AC
90-305 Volts AC
Power Factor
> 0.95
> 0.95
> 0.95
> 0.95
Input Frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
Anti Corrosion Grade
WF2
WF2
WF2
WF2
Insulation Grade
I
I
I
I
Cable Diameter
8-14 mm
8-14 mm
8-14 mm
8-14 mm
Screw Thread
G3/4”
G3/4”
G3/4”
G3/4”
IP Rating
IP66
IP66
IP66
IP66
Operational Temperature
-40° to 50 °C
-40° to 50 °C
-40° to 50 °C
-40° to 50 °C
Operational Humidity
0% to 90% RH
0% to 90% RH
0% to 90% RH
0% to 90% RH
Dimensions (φ x H)
300 x 332 x 202 mm
300 x 332 x 202 mm
300 x 332 x 202 mm
300 x 332 x 202 mm
Weight
6.3 kg
6.3 kg
6.3 kg
6.3 kg
5 Years comprehensive
5 Years comprehensive
5 Years comprehensive
5 Years comprehensive
ENVIRONMENTAL
PHYSICAL
WARRANTY Details EX II 2 GD* Zone 1 Gas class: IIC Temperature Class: T6
LED
IP66
+50°C
-40°C
EXPROOF LIGHTING SYSTEMS
EXL-02 SERIES EXPLOSION PROOF LED FLOODLIGHT
APPLICATIONS
»» »» »» »» »»
Designed and manufactured for the oilfield, chemical, steel, power, port and petroleum industries. Ideal for harsh environments with high levels of humidity and moisture. Suitable for gas explosive environments to group IIA and IIB requirements. Compliant with Zone 1, Zone2, Zone 21 and Zone 22 category areas. Temperature class areas from T1 to T6. PRODUCT FEATURES
»» Dual cable inlet system allows that the fixtures can be installed in parallel or series configurations. »» Employs the highest specification industry recognised components, including Cree LED light engines combined with a Mean-Well power supply unit. (PSU / driver) »» Isolated LED chip-and-lens design improves thermal conductivity and ensures a market-leading fixture lifespan and durability. »» Multi-purpose, fit-and-forget technology for ultimate application flexibility and longevity. »» In-built heat sink balances luminaire efficiency with extreme structural integrity.
ttaf.com.tr
TECHNICAL SPECIFICATIONS
ART NO
EXL-02030U
EXL-02040U
EXL-02060U
EXL-02075U
LED Devices
Cree
Cree
Cree
Cree
Lumen Output
2,660 lm (+/-5%)
3,820 lm (+/-5%)
5,260 lm (+/-5%)
6,010 lm (+/-5%)
Nominal Power Rating
30 Watts
40 Watts
60 Watts
75 Watts
Efficiency
88,7 lm / W
95,5 lm / W
87,7 lm / W
80,1 lm / W
Beam Angle (W/H)
140 / 100°
140 / 100°
140 / 100°
140 / 100°
Colour Temperature
5,000° Kelvin
5,000° Kelvin
5,000° Kelvin
5,000° Kelvin
Colour Rendering Index (CRI)
> 80 Ra
> 80 Ra
> 80 Ra
> 80 Ra
Lumen Maintenance
L70 > 100,000 Hours
L70 > 100,000 Hours
L70 > 100,000 Hours
L70 > 100,000 Hours
Input Voltage
90-305 Volts AC
90-305 Volts AC
90-305 Volts AC
90-305 Volts AC
Power Factor
> 0.98
> 0.98
> 0.98
> 0.98
Input Frequency
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
Anti Corrosion Grade
WF2
WF2
WF2
WF2
Insulation Grade
I
I
I
I
Cable Diameter (OD)
8-14 mm
8-14 mm
8-14 mm
8-14 mm
Screw Thread
G3/4”
G3/4”
G3/4”
G3/4”
IP Rating
IP66
IP66
IP66
IP66
Operational Temperature
-40° to 50 °C
-40° to 50 °C
-40° to 50 °C
-40° to 50 °C
Operational Humidity
0% to 90% RH
0% to 90% RH
0% to 90% RH
0% to 90% RH
Dimensions (φ x H)
370 x 326 x 88 mm
370 x 326 x 88 mm
370 x 326 x 88 mm
370 x 326 x 88 mm
Weight
6.5 kg
6.5 kg
6.5 kg
6.5 kg
5 Years comprehensive
5 Years comprehensive
5 Years comprehensive
5 Years comprehensive
ENVIRONMENTAL
PHYSICAL
WARRANTY Details EX II 2 GD* Zone 1 Gas class: IIC Temperature Class: T6
LED
IP66
+50°C
-40°C
EXPROOF LIGHTING SYSTEMS
EXL-03 SERIES EXPLOSION PROOF PENDANT LUMINAIRE
APPLICATIONS
»» Designed and approved for safe use in explosive environments such as underground in coal mining where dangerous levels of methane and explosive dust exist. »» The idea lighting fixture solution for the underground working in tunnels or tunnel construction. PRODUCT FEATURES
»» Dual cable inlet system allows that the fixtures can be installed in parallel or series configurations. »» Employs the highest specification industry recognised components, including Cree LED light engines combined with a Mean-Well power supply unit. (PSU / driver) »» Isolated LED chip-and-lens design improves thermal conductivity and ensures a market-leading fixture lifespan and durability. »» Multi-purpose, fit-and-forget technology for ultimate application flexibility and longevity. »» In-built heat sink balances luminaire efficiency with extreme structural integrity.
ttaf.com.tr
TECHNICAL SPECIFICATIONS
ART NO
EXL-03060U
LED Devices
Cree
Lumen Output
5,230 lm (+/-5%)
Nominal Power Rating
60 Watts
Efficiency
87.2 lm / W
Beam Angle (W/H)
220°
Colour Temperature
5,000° Kelvin
Colour Rendering Index (CRI)
> 80 Ra
Lumen Maintenance
L70 > 100,000 Hours
Input Voltage
90-264 Volts AC
Power Factor
> 0.95
Input Frequency
50 / 60Hz
Anti Corrosion Grade
WF2
Insulation Grade
I
Cable Diameter (OD)
8-14 mm
Screw Thread
G3/4”
ENVIRONMENTAL IP Rating
IP66
Operational Temperature
-40° to 50 °C
Operational Humidity
0% to 90% RH
PHYSICAL Dimensions (φ x H)
240 x 234 mm
Weight
5.0 kg
WARRANTY Details EX II 2 GD* Zone 1 Gas class: IIC Temperature Class: T6
5 Years comprehensive
LED
IP66
+50°C
-40°C
EXPROOF LIGHTING SYSTEMS
EXL-O4 SERIES EXPLOSION PROOF MINING SPOTLIGHT
APPLICATIONS
»» Provides operators with a powerful and energy efficient spotlight for use in flammable environments such as coal mines, indoor and outdoor work and/or monitoring tasks. PRODUCT FEATURES
»» Dual cable inlet system allows that the fixtures can be installed in parallel or series configurations. »» Employs the highest specification industry recognised components, including Cree LED light engines combined with a Mean-Well power supply unit. (PSU/driver) »» Isolated LED chip-and-lens design improves thermal conductivity and ensures a market-leading fixture lifespan and durability. »» Multi-purpose, fit-and-forget technology for ultimate application flexibility and longevity. »» In-built heat sink balances luminaire efficiency with extreme structural integrity.
ttaf.com.tr
TECHNICAL SPECIFICATIONS
ART NO
EXL-04060U
LED Devices
Cree
Lumen Output
5,500 lm / W (+/-5%)
Nominal Power Rating
60 Watts
Efficiency
91.7 lm / W
Beam Angle (W/H)
25° (45°-60°)
Colour Temperature
5,000° Kelvin
Colour Rendering Index (CRI)
> 80 Ra
Lumen Maintenance
L70 > 100,000 hours
Input Voltage
90-264 Volts AC
Power Factor
> 0.95
Input Frequency
50 / 60Hz
Anti Corrosion Grade
WF2
Insulation Grade
I
Cable Diameter
8-14 mm
Screw Thread
G3/4”
ENVIRONMENTAL IP Rating
IP66
Operational Temperature
-40° to 50 °C
Operational Humidity
0% to 90% RH
PHYSICAL Dimensions (φ x H)
180 x 243 mm
Weight
3.8 kg
WARRANTY Details
5 Years comprehensive
EX II 2 GD* Zone 1 Gas class: IIC Temperature Class: T6
LED
IP66
+50°C
-40°C
EXPROOF LIGHTING SYSTEMS
EXL-05 SERIES EXPLOSION PROOF LINEAR LED LUMINAIRE
APPLICATIONS
»» Designed and manufactured for widespread uses within the petroleum, chemical, transport, aerospace, aviation, military, processing and other industries. »» Ideal for harsh environments with high levels of humidity and moisture. »» Suitable for gas explosive environments to group IIA, IIB and IIC requirements. »» Compliant with Zone 1, Zone2, Zone 21 and Zone 22 category areas. »» Temperature class areas from T1 to T6. PRODUCT FEATURES
»» Dual cable inlet system allows that the fixtures can be installed in parallel or series configurations. »» Employs the highest specification industry recognised components, including Cree LED light engines combined with a Mean-Well power supply unit. (PSU / driver) »» Isolated LED chip-and-lens design improves thermal conductivity and ensures a market-leading fixture lifespan and durability. »» Multi-purpose, fit-and-forget technology for ultimate application flexibility and longevity. »» In-built heat sink balances luminaire efficiency with extreme structural integrity.
ttaf.com.tr
TECHNICAL SPECIFICATIONS
ART NO
EXL-05040U
LED Devices
Cree
Lumen Output
2,590 lm (+/-5%)
Nominal Power Rating
40 Watts
Efficiency
65 lm / W
Beam Angle (W/H)
25° (45° - 60°)
Colour Temperature
5, 500° Kelvin
Colour Rendering Index (CRI)
> 70 Ra
Lumen Maintenance
L70 > 50,000 Hours
Input Voltage
90-264 Volts AC
Power Factor
> 0.95
Input Frequency
50 / 60 Hz
Anti Corrosion Grade
WF2
Insulation Grade
I
Cable Diameter
8-14 mm
Screw Thread
G3/4”
ENVIRONMENTAL IP Rating
IP66
Operational Temperature
-40° to 45 °C
Operational Humidity
0% to 90% RH
PHYSICAL Dimensions (φ x H)
1370 x 215 x 110 mm
Weight
12 kg
WARRANTY Details
5 Years comprehensive
EX II 2 GD* Zone 1 Gas class: IIC Temperature Class: T6
LED
IP66
+45°C
-40°C
ISO 9001 2008
www.ttaf.com.tr | export@ttaf.com.tr
ttafelectronic
HEADQUARTERS & MANUFACTURING FACILITY Kavaklı Mah İstanbul Cad. No:21 Beylikdüzü İstanbul / TÜRKİYE - Tel +90 212 855 82 20 | Fax +90 212 855 82 21 CHINA RESEARCH & DEVELOPMENT OFFICE Room No.4305, ShunHingSquare, Diwang Commercial Center, 5002# Shennan East Road, Luohu District, Shenzhen City, China - Tel +86 755 25882560 | Fax +86 755 25882623