AllconduitsandsubstructuresinstalledforTIDusemustbeinspectedpriorto backfilling.Failuretoobtainaninspectionwillrequiretheinstallertoexposetheburied facilitiesforinspection.
RefertotheappropriateTIDinformationbookletformaterialspecificationsand constructionstandards.Bookletsmaybeobtainedat333EastCanalDriveinTurlockor onlineat http://tid.com/power/engineering-construction
4
Underground Inspection check sheet
INSPECTIONS: www.tid.org/power/electrical-inspection-request/ Inspections: (209)883-8476 OR call (209) 606-0136 for questions
CUSTOMER NAME:
CONTACT NUMBER: JOB LOCATION:
JOB NUMBER:
INSPECTIONS:
TRENCH:
*Ref: 30571
PRIMARY CONDUIT:
*Ref: 30570,35201
SECONDARY CONDUIT:
*Ref: 30571,035201
WIRE:
*Ref: 30800, 34701
SECONDARY BOX:
*Ref: 34805, 35201
TRANSFORMER PAD:
*Ref: 35051,35054
GROUND GRID:
*Ref: 35051
REBAR:
*Ref: 35101
SECONDARY MANDRIL:
PRIMARY MANDRIL:
*Ref: 35201
PANEL:
Ref: 34815
PLACARDS:
BOLLARDS:
Ref: 35151, 35152, 35154
INSPECTION TAG:
KNOX BOX:
Ref: 50510
VAULT:
Ref: 35202
W.O. NUMBER:
INSPECTOR: DATE:
*Reference Constriction Standards customer information sticker
NOTES:
Section2
MeterRequirements
2.1MeterHeight
Therequirementsformeterheight,whichistheverticaldistancebetweenthecenterlineof themeterandthegroundorstandingsurface,shallbeasfollows:
48"minimum-75"maximumforsinglemeterresidential&meterpedestals
36"minimum–75”maximumallowedforcommercialmeterclustersinselfsupporting,rain-tightcabinets
2.2MeterWorkingSpace
Workingspaceinfrontofthemeterpermitsaccesstothemeteringinstallationand providesworkingsafetyforpersonnel.Aworkingspaceentirelyonthepropertyofthe customerisrequiredinfrontofallmetersexceptforbuildingsconstructedonzerolotlines.
Theworkingspaceistobekeptclearandunobstructedandshallnotbeusedforstorage.
Whenmetersormeteringequipmentareplacedincabinetenclosures,theclearworking spaceshallextendfromtheouterfaceofthecabinet.
Theheightoftheclearworkingspaceshallbe78inchesminimumfromthestanding surface.
Thewidthoftheclearworkingspaceshallbe36inchesminimumforaonemeter installationandshallextendtheadditionalwidthnecessaryforaccesstothetotalnumber ofmeteringpanels.Thecenterlineofanymetershallnotbelessthan18inchesfromany adjacentsidewallorotherprotrudingobstruction.
Thedepthoftheclearworkingspaceshallbe36inchesminimumforservicesrated150 voltsorlesstoground.Whentheserviceisratedinexcessof150voltstoground,the depthshallbeasrequiredbyapplicableelectricalcodesorasdictatedbythephysical designandarrangementofthemeteringcubicles.
2.3MeterLocations–GeneralConditions
Inorderthatthemostsatisfactorymeterlocationmaybedeterminedandadequatespace provided,TIDshouldbeconsultedwhilethebuildingorresidenceisinthepreliminary planningstage.Installationofadditionalfacilitiesatthecustomer'sexpenseorfuture relocationsathisexpensemaybepreventedbyearlyconsultationwithTID.
7
Thefollowingbasiclocationrequirementsshallapplyinallcases:
2.3.1AlllocationsformetersandmeteringequipmentaresubjecttoTIDapproval.
2.3.2Metersshallbeaccessible(withduallockingdevicesifnecessary)duringandafter landscapingorotherbuildingconstruction.Nometershallbeenclosedbyany fencingwithoutpermissionfromanauthorizedTIDrepresentative.
2.3.3Metersandmeteringequipmentinstalledonorrecessedintheexternalsurfaceof anybuildingshallhaveaclearworkingandstandingspaceentirelyontheproperty ofthecustomerserved.Anyexceptionfromthisrequirementmustbeapprovedby TID.
2.4UnacceptableLocationsforElectricMeters
2.4.1Inanylocationthatishazardoustoequipmentorpersonsorunsuitableforentry, suchas:
a.anyelevatorshaft.
b.anydoorwayorhatchway.
c. directlyoveranystairway,ramporsteps.
d.anyareaaccessibleonlythroughatrap-door,hatchway,orbymeans ofaladder.
e.anyareawherepersonnelmaycontactexposedhighvoltage conductorsorequipmentinmotion.
2.4.2Inanyplacewherevibration,moisture,excessivetemperature,fumes,ordustmay damagethemeterorinterferewithitsoperation.
2.4.3Withinorrequiringaccessthroughanybath,shower,powderortoiletroom.
2.4.4Onanyportionofabuildingwherelaterlandscaping,fencingorotherbuilding constructionwillmakethemeterinaccessible.
2.4.5Withinanyenclosedareathatcontainsorwillcontaingasmeters.
2.4.6Metersandmeteringequipmentshallnotbeinstalledwithinanylockedfacilityin whichTIDwouldbedeniedaccessatanytimeoftheday.
2.4.7Indoors.
2.4.8Outdoormetersshallnotbeinstalledwheretheywillinterferewithtraffic, sidewalks,driveways,orwheretheywillobstructtheopeningofdoorsorwindows, orinanylocationwhichmaybeconsideredhazardousorcausedamagetothe meteringequipment.
8
2.5RemoteMetering
Remotemeteringisacceptableininstanceswhereanexternalpanelorswitchboardisnot utilized.
Thefollowingspecialarrangementsarerequired:
2.5.1ApplicantshallprovideanapprovedCTmountingcabinetthatcomplieswiththe previousparagraph"MeterLocations-GeneralConditions."
2.5.211/4"steelconduitbetweentheCTcabinetandmetersocket.
2.5.3Meterwillbelocatedwithin50conductorfeetofCTcabinet.
2.5.4Junctionboxesarepermittedonlyiftheycanbesealed.
2.5.5Couplingsmusthavesealscrews.
2.5.6Forspecialmeterdistancerequirement,refertoconstructionstandard50510.
2.6PlanningandGroupingofAdditionalMeters
Occasionallythereisneedtolocateandinstalladditionalserviceandmeteringequipment aftertheoriginallyplannedelectricserviceforabuildingisinstalledandenergized.Where possible,additionalmetersshouldbegroupedwiththoseelectricmetersalreadyinservice.
2.7TwoorMoreHousesonOneLot
Ifmorethantwodwellingsorbuildingsarelocatedonthesamelot,consultTIDto determineacceptablemeterlocationsbeforeproceedingwiththewiringofthebuildings.
Forasingle-familydwellinglocatedbehindanotherdwellingorcommercialestablishment onaninside(non-corner)lotnotsubjecttofurthersubdivision,themetersshallbelocated adjacenttoeachotheratthebuildingclosesttothedistributionlinefromwhichservicewill besupplied.Allwiringbeyondthemeterswillbeatthecustomer'sexpense.
Formulti-dwellingbuildingsconstructedontherearofnon-commerciallots,ifpractical, andatthecustomer'srequest,TIDwillinstallseparateservicefacilitiestotherearbuilding. Themetersfortherearbuildingshallbegroupedtogetheratasuitablelocationattherear building.
2.8MeterOccupancyIdentification
Wheremetersaregroupedatacommonlocation,suchasfortwoormorehousesonalot orforamultipleoccupancybuilding,eitherresidentialornon-residential,eachmeter positionanditsdirectlyidentifiableservicedisconnectshallbeclearlyandpermanently markedbythebuildingownerorhisrepresentativetoindicatetheoccupancyserved(Per N.E.C.230-72a).Examplesofpermanentmarkingshallbeengravedplateattachedby screws,rivets,ortwo-partepoxy.Clearidentificationmeansalegibleapartmentorstreet number.Thestorenamemaybeincludedbutdoesnotconstituteacleardesignationin
9
itself.Apartmentorsuitenumbersmustbeonoradjacenttothedoorofeachunit.
2.9SealingofMetersandMeteringEquipment
Allmetersandenclosuresformeters,meteringequipmentandserviceentranceequipment onthelinesideofthemeterwillbesealedbyTID.TheTIDsealshallnotbebroken exceptbyanauthorizedrepresentativeofTID.Nopersonispermittedtotamper,remove, replace,orinanywayinterferewithameteroritsconnectionsasplacedbyTID.
2.10MeterSocketBypassDevices
Automaticbypassorcircuitclosingdevicesthatclosewhenthemeterisremovedfromthe socketshallnotbeused.
Manualcircuitclosingdevicesarerequiredonallserviceentranceequipmentexceeding30 ampsnameplateratingexceptdomestic,signboardsandtemporaryservice.Service entranceequipmentmustbecontinuouslyratedperU/L414.
2.11Self-containedMeteringDefined
Aself-containedmeteriscapableofcarryingthetotalcurrentatthevoltageoftheelectric servicesuppliedtothecustomer.Socketsforself-containedmetersaredirectlyconnected tothecustomer'sserviceentranceconductors,andthemeterisinsertedintothesocket. Metersocketsareavailablewithnominalratingsof100or200amperes.ContactTIDfor detailsonsingle-phase,400ampservice.
2.12Transformer-ratedMeteringDefined
Whentheelectricserviceneedsoftheapplicantexceedtheampacityorvoltagelimitations ofaself-containedmeter,meteringtransformers,whichconnectdirectlytothecustomer's serviceentranceconductors,mustbeused.Atransformer-ratedmeteristhenconnected tothemeteringtransformerstomeasuretheenergydeliveredtothecustomer.The meteringtransformersandthetransformer-ratedmeter(s)arefurnishedandinstalledby T.I.D.
2.13EUSERC
ElectricUtilityServiceEquipmentRequirementsCommittee(EUSERC)isanorganization whosepurposeistopromoteuniformelectricservicerequirementsamongtheutilities. TIDisamemberofandsupportsEUSERC.Assuch,whenanapplicantwishesservice withintheDistrictserviceareaandtheequipmentchosenmeetsEUSERC,itisunderstood, withsomespecificexceptions,thatTIDwillprovidepowertotheequipment.Checkwith theDistrictfordetails.
10
2.14Switchboards
Switchboardsareconsideredaspecialtyitemformeteringequipment.TIDrequirestwo setsofapprovaldrawingsofsuchequipment.IfTIDtakesexceptiontotheequipment,the applicantwillbenotifiedofthechangesrequired.Shouldtheapplicantrequestserviceand theequipmentisnotacceptable,servicewillnotbeconnected.Havetheequipment checkedandapprovedpriortorequestingservice.Itwillsavetimeandheadachesfor everyoneinvolved.
TheswitchboardmustataminimummeetEUSERCrequirements.Aswitchboardservice sectionhasahingedmeterpanellocatedinfrontoftheinstrumenttransformer compartment.HingedmeterpanelsmusthaveEUSERChandlesandopenaminimumof 90 withmetersandtestswitchesmounted.Hingedmeterpanelsmustbesealable.
Forspecialmeterdistancerequirement,refertoconstructionstandard50510.
11
12
ConstructionStandardsDrawings Page 30571–ServiceTrenchConfiguration 11 30800–GuideforPullingCables 12 34605–IndividualUnderground 15 34701–ServiceWireSizes 17 34805–ServiceBoxInstallation 19 34810–MinimumRequirements,ResidentialService 21 34815–UndergroundResidentialServicePanelLocation 22 34820–MinimumRequirements,SingleMobileHome 23 34830–MinimumRequirements,MultipleMobileHomes 24 34840–MinimumRequirements,MultipleMetering 25 35201–UndergroundConduitApplication 26 50500–Currenttransformercabinets400-800Amps. 28 50510–CriteriaforElectricalRooms 29 50600–Low&HighVoltageElectricServiceMeterSocketRequirements 30 51092–NetMeteringResidential&SmallIndustrialWiring&MeterInstallation 33 51093–NetMeteringLineSideConnectionWiring&MeterInstallation 35
Section3
36" +/3"
24" +/- 6" See Note
Service Conductor in Conduit
Notes:
1.1'-6" minimum loose backfill, water soaked when trench is filled; or 1'-0" compacted backfill, with compaction to be not less than 95% relative compaction.
2.Backfill material to be non-rock with no clumps larger than 1" diameter.
3.Conduit size as per Construction Standard 35201.
REVDESCRIPTIONINITCHKRV'DRV'DAPPDATE RV'D SHEET OF DWG. NO.PAGE
SERVICE TRENCH CONFIGURATION 30571G 11 GUPDATED TITLEBLOCK, ADDED HYPERLINKELJRWBLJCRAMSG09-2016 CDIMENSION CHANGESCPRWBLBGRAAKH09-1989
GENERAL & TID NOTESBBETERWBLBGRA01-1994 EREDRAWN IN AUTOCAD FREPLACE TITLE BLOCKJRSMSGJSAMLHSDPEDJ06-2013
CONSTRUCTION STANDARDS
DCLARIFY
1
CATV Telephone Gas
Electric
Finished Grade
Figure 1 Service Trench Configuration
Secondary Level See Note 1
See Note 1
Customer provided and installed equipment
Conduit PVC Sch 80
See Note 6
Finished Grade
3C See Note 5 (PVC Sch 40 Elbow)
Individual Underground
PVC conduit by customer to customer panel
Notes:
1.Service cable (provided by customer) is to be of sufficient length to exceed secondary level by three feet. Coil cable and tie in manner that will not damage cable.
2.After the elbow, (1) 10' straight length of conduit up the pole (no bell up) to be provided by customer.
3.TID to inform customer which quadrant of the pole the conduit is to rise.
4.TID to inspect conduit prior to backfilling.
5.All elbows to be 36" radius.
6.Attach conduit straps to pole using washerhead lag screws.
7.Refer to Construction Standard 35201 for conduit and conduit strap sizes.
ECHANGED ELBOW TO SCH 40BBJDBLL06-1998
FADD NOTE: WIRE COILED BY CUSTOMERBBSPLBLL09-1998
GCHANGED ELBOW RADIUS TO 36 INCHES
HREPLACE TITLE BLOCK, ADDED MATERIAL STDJRSMSGJSAMLHSDPEDJ06-2013
IUPDATED TITLEBLOCK AND TABLESELJMSG09-2016
CONSTRUCTION STANDARDS INDIVIDUAL UNDERGROUND
3 6 ' ' + /3 ' ' 3' 3' 10' 18''
RV'D SHEET OF DWG. NO.PAGE
REVDESCRIPTIONINITCHKRV'DRV'DAPPDATE
34605I 12
5 2 1 4
2C 1C 4C
3
Figure 1
Trench Depth Single Piece
2)
(See Note
3'
Table 1Bill of Materials Provided and Installed by TID
Table 4Resource (Multiple Conductor 600 A and Above)
SHEET OF DWG. NO.PAGE CONSTRUCTION STANDARDS
UNDERGROUND 34605I 22 Item Stock Number Qty Description Material STD 1O-7330-XXX3or4 Parallel Groove Clamp (size determined by wire) 2131 2 U-6370-XXX1 Cable Grip 2135 3U-6160-XXX20' Powermould (size determined by wire) 2170 4O-7189-00216 Washerhead Lag Screws 2322 5O-7192-0041J Hook
INDIVIDUAL
Resource Qty Hours Line Supervisor 1 1.5 Lineman 1 Line Truck 1 Personnel Lift1 Table 2Resource
to
Resource Qty Hours Line Supervisor 1 2.0 Lineman 1 Line Truck 1 Personnel Lift1 Table 3Resource (500 Triplex or Quad) Resource Qty Hours Line Supervisor 1 3.0 Lineman 2 Line Truck 1 Personnel Lift1
(1/0
4/0)
Item Stock Number Qty Description Material STD 1CU-6048-XXX3 Conduit Strap 2170 2CU-6050-XXX10'Conduit PVC Sch 80 3CU-6085-XXX 1 PVC Sch 40 90 Degree Elbow 4CO-7189-0024 Washerhead Lag Screws 2322
Resource Qty Hours Line Supervisor 1 0.5 Lineman 2 Line Truck 1 Table 6Resource
Table 5Bill of Materials Provided and Installed by Customer
Feed Conduit (from Transformer or Adjacent Box) to Occupy the Center Position
REVDESCRIPTIONINITCHKRV'DRV'DAPPDATE RV'D
IADDED TABLE 3SSGDNHDPMNMSG06-2021
HUPDATED TITLEBLOCK, TABLES, NOTESELJMSG09-2016
GREPLACE TITLE BLOCK, ADDED MATERIAL STDJRSMSGJSAMLHSDPEDJ06-2013
FRELABEL CONDUITSSDCBSKJODBMGKTBLL09-2007
ESPECIFY FEED CONDUIT IN CENTER POSITIONSDCGKTMSGDBMKJOBLL03-2007
Secondary Conduit(s)
Service Conduit(s)
SHEET OF DWG. NO.PAGE
INSTALLATION 34805I 12
CONSTRUCTION STANDARDS SERVICE BOX
Figure 1 Plan View
1 2 Service Conduit(s) Secondary Conduit(s) F B E C D
Figure 2 Profile View
Notes:
A.The soil under the service box shall be compacted to no less than 95% relative compaction.
B.Leave approximately 3 feet of pull rope extended past conduit.
C.Leave approximately 4 feet of service conductor extended past conduit.
D.Insert conduit 2 inches inside service box.
E.All conduits are to be located against the same end of the service box.
F.The box lid must be labeled "ELECTRIC".
G.See Construction Standard 35201 for size and quantity of conduits required.
SHEET OF DWG. NO.PAGE CONSTRUCTION STANDARDS SERVICE BOX INSTALLATION 34805I 22 Item Stock Number QtyDescription Material STD 1O-13XX-XXX1 Service Box (size as required) 2022 2 U-8200-004 As Req'd 3 4" Pull Rope 2401 Table 1Bill of Materials Resource Qty Hours Line Supervisor 1 1.0 Lineman 1 Line Truck1 Table 2Resources
TID Equipment Front SidesBack Service Box333 Table 3Clearances (Min. in Ft)
Alternate Location. Use 30 Degree (max) Sweeping Ells or Form Conduit to Fit, but Keep Angles 30 Degrees or Less (See Note 2)
Service Entrance Elbow to be Pointed Towards TID Electric Box
Service Entrance Elbow to be Pointed Towards TID Electric Box
Notes:
1.Service entrance equipment will conform to applicable sections of the Electric Utility Service Equipment Requirements Committee (EUSERC) Standards.
2.All PVC conduits must be adequately glued and set prior to installation of conductors. Only sweeping types of bends are acceptable. Conduit that is deformed due to heating or over stressing during installation will not be acceptable.
3.Meters will be furnished and set by TID after the installation has been approved by the governing inspection agency.
4.The service entrance panel shall be mounted so that the center of the meter will be at a height between a minimum of 48 inches and a maximum of 75 inches above finished grade.
5.Grounding shall be in accordance with the National Electric Code (NEC) and local codes. TID may require that the grounding conductor be installed in EMT or cable armor to protect the conductor from mechanical damage. Use approved cast ground clamp.
6.Conduit size and schedule per TID Construction Standard 35201.
CONSTRUCTION STANDARDS
SHEET OF DWG. NO.PAGE REVDESCRIPTIONINITCHKRV'DRV'DAPPDATE RV'D
RESIDENTIAL
UNDERGROUND CONSTRUCTION 34810J 11 JUPDATED TITLEBLOCKELJMSG09-2016 FCORRECTED METER HEIGHTBBRWCRWBLBGRA03-1994 GREDRAWN IN AUTOCADSDCPJOKJOLBGBLL04-2003 HCLARIFY GROUNDING REQUIREMENTSSDCKJODMGKTBLL02-2006 IREPLACE TITLE BLOCKJRSMSGJSAMLHSDPEDJ06-2013
MINIMUM REQUIREMENTS FOR
SERVICES USING
Figure
1 Typical Surface Mount
Flush
Conduit
Figure
2 Typical
Mount Service Entrance Panel Service Entrance Panel
Preferred Location
Conduit
36" 36" Finished Grade Finished Grade
See Note 2
Notes:
CONSTRUCTION STANDARDS
SHEET OF DWG. NO.PAGE REVDESCRIPTIONINITCHKRV'DRV'DAPPDATE RV'D
RESIDENTIAL SERVICE PANEL LOCATION 34815B 11 --INITIAL ISSUESDCKJOBLL04-2003
UNDERGROUND
1.The electrical panel shall be installed within the first five feet of the corner of the structure.
2.The electrical panel shall be installed near the corner of the structure closest to the utility trench.
3.The electrical panel shall be adjacent to other utilities.
4.The electrical panel shall be on the street side of any fences.
Surface mount
TITLE BLOCKJRSMSGJSAMLHSDPEDJ06-2013
Flush mount
AREPLACE
Figure 1
BUPDATE TITLE BLOCKELJMSG09-2016
Underground Residential Service Panel Location
Finished Grade
Conduit Size per TID Standards
Customer Conduit
Approved Grounding Clamp Must Be Accessible. Extend Metallic Tubing or Cable Armor to Ground Rod to Protect Ground Wire From Mechanical Damage.
Ground Conductor per Code
Treated or Redwood Timber per California Administrative Code, Title 25.
Meter & Breaker Assembly
Conduit Size per TID Standards
Customer Conduit
Approved Grounding Clamp Must Be Accessible. Extend Metallic Tubing or Cable Armor to Ground Rod to Protect Ground Wire From Mechanical Damage.
Ground Conductor per Code
Notes:
1.Service entrance equipment will conform to applicable sections of the Electric Utility Service Equipment Requirements Committee (EUSERC) Standards.
2.Customer shall supply panel with bus bar lugs where one set of lugs feeds all meters. Lug size and quantity will be specified by the District.
3.Meters will be furnished and set by TID after the installation has been approved by the governing inspection agency.
4.No service will be run under existing or future concrete areas.
5.All PVC conduits must be adequately glued and set prior to installation of conductors. Only sweeping type bends are acceptable.
6.See Construction Standard 30571 for trench configurations.
CONSTRUCTION STANDARDS
REVDESCRIPTIONINITCHKRV'DRV'DAPPDATE SHEET OF DWG. NO.PAGE RV'D
REQUIREMENTS FOR SINGLE MOBILE HOME METERING USING UNDERGROUND CONSTRUCTION 34820F 11 FUPDATE TITLEBLOCKELJMSG09-2016 BCHANGED NOTESSPRWBRCMRAAKH10-1989
WITH CUSTOMER BOOKBBETERWBLBGRA06-1993 DREDRAWN IN AUTOCADSDCPJOKJOBLL04-2003 EREPLACE TITLE BLOCKJRSMSGJSAMLHSDPEDJ06-2013
MINIMUM
CCOMBINED
Pre-Fabricated Metering Pedestal
Figure 1
36" +/3" 75" max. 48" min.
Figure 2
Treated or Redwood Timber Metering Pedestal
Pre-Fabricated Metering Pedestal Meter & Breaker Assembly
Redwood Hangers
Configuration May Vary
Meter and Breaker Assembly for Underground Feed
Redwood Posts per California Administrative Code, Title 25 Conduits from Panel
Service Entrance Conduit and Conductors to Service Pedestal, Size per TID Standards
Ground Conductor per Code
Approved Grounding Clamp, Must be Accessible. Extend Metallic Tubing or Cable Armor to Ground Rod to Protect Wire from Mechanical Damage.
Finished Grade
Ground Rod
Figure 1
Multiple Mobile Home Metering Using Underground Construction
Notes:
1.Service entrance equipment will conform to applicable sections of the Electric Utility Service Equipment Requirements Committee (EUSERC) Standards.
2.Customer shall supply panel and bus bar lugs where one set of lugs feeds all meters. Lug size and quantity will be specified by the District.
3.Meters will be furnished and set by TID after the installation has been approved by the governing inspection agency.
4.No service will be run under existing or future concrete areas.
5.All PVC conduits must be adequately glued and set prior to installation of conductors. Only sweeping type bends are acceptable.
6.See Construction Standard 30571 for trench configurations.
CONSTRUCTION STANDARDS
REVDESCRIPTIONINITCHKRV'DRV'DAPPDATE SHEET OF DWG. NO.PAGE RV'D
MULTIPLE MOBILE HOME METERING USING UNDERGROUND CONSTRUCTION 34830F 11 FUPDATE TITLEBLOCKELJMSG09-2016 BCHANGED NOTESSPRWBRCMRAAKH10-1989 CCOMBINED WITH CUSTOMER BOOKBBETERWBLBGRA06-1993 DREDRAWN IN AUTOCADSDCPJOKJOBLL04-2003 EREPLACE TITLE BLOCKJRSMSGJSAMLHSDPEDJ06-2013 36" +/3" 48" min. 75" max.
MINIMUM REQUIREMENTS FOR
Ground Conductor per Code
Finished Grade
Approved Grounding Clamp Must be Accessible. Extend Metallic Tubing or Cable Armor to Ground Rod to Protect Ground Wire from Mechanical Damage.
Customer Service Conduit if Required
Configurations May Vary Main
Conduit Size per TID Requirements
36" +/3"
Notes:
1.Service entrance equipment will conform to applicable sections of the Electric Utility Service Equipment Requirements Committee (EUSERC) Standards.
2.Customer shall supply panel with bus bar lugs where one set of lugs feeds all meters. Lug size and quantity will be specified by the District.
3.Meters will be furnished and set by TID after the installation has been approved by the governing inspection agency.
4.No service will be run under existing or future concrete areas.
5.All PVC conduits must be adequately glued and set prior to installation of conductors. Only sweeping type bends are acceptable.
6.Minimum meter height may be reduced to 36" when utilizing enclosed switchboards.
7.See Construction Standard 30571 for trench configurations.
CONSTRUCTION STANDARDS
REVDESCRIPTIONINITCHKRV'DRV'DAPPDATE SHEET OF DWG. NO.PAGE RV'D
34840F 11 FUPDATE TITLEBLOCKELJMSG09/28/2016 BDIMENSION CHANGESPRWBRCMRAAKH10-1989 CCOMBINED WITH CUSTOMER BOOKBBETERWBLBGRA06-1993 DREDRAWN IN AUTOCAD EREPLACE TITLE BLOCKJRSMSGJSAMLHSDPEDJ06-2013 Figure 1 Multiple Metering Using Underground Construction 48" min. 75" max. See Note 6
MINIMUM REQUIREMENTS FOR MULTIPLE METERING USING UNDERGROUND CONSTRUCTION
Disconnect
39
MaterialStandardsDrawings Page 2022–Specification,ServiceBox 40 2170–Specification,PlasticConduit&Accessories 44 2202–ContractorDeveloperConductorInformation 52
Section4
Figure1
Table1PVCConduit,Schedules40&80
StockNumberDescription
U-6050-0011"Schedule80
U-6050-0022"Schedule80
U-6050-0033"Schedule80
U-6050-0044"Schedule80
U-6050-0055"Schedule80
U-6050-0066"Schedule80
U-6060-0001 2"Schedule40
U-6060-0011"Schedule40
U-6060-0022"Schedule40
U-6060-0033"Schedule40
U-6060-0044"Schedule40
U-6060-0055"Schedule40
Notes:
1.MeetsNEMATC-2
2.MeetsUL-651
3.10'lengthwithbelledendorcoupling attached
TURLOCKIRRIGATIONDISTRICT
VREMOVEDDISCONTINUEDPARTSADL SSG11-2022
Table2PVCCoupling
StockNumberDescription
U-6090-0001 2"Coupling
U-6090-0011"Coupling
U-6090-0022"Coupling
U-6090-0033"Coupling
U-6090-0044"Coupling
U-6090-0055"Coupling
U-6090-0066"Coupling
U-6092-0022"Coupling-longline
U-6092-0033"Coupling-longline
U-6092-0044"Coupling-longline
Notes:
Figure2 TADDEDCONDUITCARRIERSTOCKNUMBERSSG EDJEDJ04-2018
PVCCoupling UADDED60"RADIUSELBOW SSGABDHEDJEDJ12-2018
1.Forusewithschedules40or80
SHEET OFDWG.NO. PAGE
REVDESCRIPTION INITCHKRV'DRV'DAPPDATE RV'D MATERIALSTANDARDS SPECIFICATION PLASTICCONDUIT&ACCESSORIES 2170V 18
PVCConduit
2.Meetsallspecificationsforschedules 40and80conduit SUPDATEDTITLEBLOCK,STANDARDELJ MSG09-2016 RREPLACEDTITLEBLOCK/UPDATEDSTANDARDJRSJSASDPMLHMSGEDJ06-2013
StockNumberDescription
U-6075-0022"45°elbow,18"radius,schedule40
U-6075-0033"45°elbow,36"radius,schedule40
U-6075-0044"45°elbow,36"radius,schedule40
U-6075-0055"45°elbow,36"radius,schedule40
U-6085-0011"90°elbow,53 4"radius,schedule40
U-6085-0022"90°elbow,36"radius,schedule40
U-6085-0033"90°elbow,36"radius,schedule40
U-6085-0044"90°elbow,36"radius,schedule40
U-6085-0055"90°elbow,36"radius,schedule40
U-6085-0066"90°elbow,60"radius,schedule40
U-6085-0084"90°elbow,60"radius,schedule40
U-6085-0095"90°elbow,60"radius,schedule40
U-6085-0106"90°elbow,60"radius,schedule40
Notes:
1.Forusewithschedules40or80conduit.
StockNumberDescription
U-6063-0033"30°elbow,36"radius,schedule80
U-6063-0044"30°elbow,36"radius,schedule80
U-6063-0055"30°elbow,36"radius,schedule80
U-6070-0022"45°elbow,18"radius,schedule80
U-6070-0033"45°elbow,36"radius,schedule80
U-6070-0044"45°elbow,36"radius,schedule80
U-6070-0055"45°elbow,36"radius,schedule80
U-6080-0011"90°elbow,53 4"radius,schedule80
U-6080-0022"90°elbow,18"radius,schedule80
U-6080-0033"90°elbow,36"radius,schedule80
U-6080-0044"90°elbow,36"radius,schedule80
U-6080-0055"90°elbow,36"radius,schedule80
2.Meetsallspecificationsforschedules40and80conduit.
SHEET OFDWG.NO. PAGE MATERIALSTANDARDS
PLASTICCONDUIT&ACCESSORIES 2170V 28
SPECIFICATION
Table3PVCElbow,Schedule40
Figure3 PVCElbow
Table4PVCElbow,Schedule80
Table6PVCConduit,Flexible
StockNumberDiameter(in.)
U-6150-0001 2*
U-6150-0011*
U-6150-0022
U-6150-0033
U-6150-0044
Notes:
*Maintainsshape afterbending.
1.PVCConduit,flexible,corrugated.
Table9PVCPowermould
StockNumberDiameter(in.)
U-6160-0022
U-6160-0033
U-6160-0044
U-6160-0055
Notes:
1.Schedule40.
2.10'lengthwithbelledend.
3.PerNEMAPH41,TC-19.
Table10PVCConduittoPowermouldAdapter
StockNumberAdapterSize(in.)
U-6170-0024"conduitto2"Powermould
U-6170-0046"conduitto4"Powermould
Notes:
1.PerNEMAPH41,TC-19.
SHEET OFDWG.NO. PAGE MATERIALSTANDARDSSPECIFICATION PLASTICCONDUIT&ACCESSORIES 2170V 38
Figure4 PVCConduit,Flexible
Figure5 PVCPowermould,Schedule40
Figure6 PVCConduittoPowermouldAdapter
Table7PVCRepairDuct
StockNumberDiameter(in.)
U-6061-0022
U-6061-0033
U-6061-0044
U-6061-0055
Notes:
1.Schedule40.
2.10'section.
3.Interlockdesign.
4.Ultravioletresistant.
5.Forrepairofschedule40,schedule80,and DB120conduit.
Table8PVCRepairCoupling
StockNumberDiameter(in.)
U-6095-0022
U-6095-0033
U-6095-0044
U-6095-0055
U-6095-0066
Notes:
1.Forusewithrepairduct.
2.Interlockdesign.
SHEET OFDWG.NO. PAGE MATERIALSTANDARDSSPECIFICATION PLASTICCONDUIT&ACCESSORIES 2170V 48
Figure7 PVCRepairDuct
Figure8 PVCRepairCoupling
PVCPowermould,Schedule40
Table9PVCPowermould
StockNumberDiameter(in.)
U-6160-0022
U-6160-0033
U-6160-0044
U-6160-0055
Notes:
1.Schedule40.
2.10'lengthwithbelledend.
3.PerNEMAPH41,TC-19.
Table10PVCConduittoPowermouldAdapter
StockNumberAdapterSize(in.)
U-6170-0024"conduitto2"Powermould
U-6170-0046"conduitto4"Powermould
Notes:
1.PerNEMAPH41,TC-19.
58
SHEET OFDWG.NO. PAGE MATERIALSTANDARDS
PLASTICCONDUIT&ACCESSORIES
SPECIFICATION
2170V
Figure9
Figure10
PVCConduittoPowermouldAdapter
Table11ConduitStrap
StockNumberDiameter(in.)
U-6048-0011
U-6048-0022
U-6048-0033
U-6048-0044
U-6048-0055
U-6048-0066
Notes:
1.Hotdipgalvanized.
2.2holemounting.
3.Mountingtabsbend90°on1",2",and3"straps.
4.Mountingtabsbend30°on4"and5"straps.
Table13TerminalAdapter
StockNumberDiameter(in.)
U-6180-0011
U-6180-0022
U-6180-0033
U-6180-0044
Notes:
1.Forusewithschedules40or80conduit.
2.Meetsallspecificationsofschedules40and 80conduit.
SHEET OFDWG.NO. PAGE MATERIALSTANDARDSSPECIFICATION PLASTICCONDUIT&ACCESSORIES 2170V 68
Figure10 ConduitStrap
Figure11 TerminalAdapter
FemaleAdapter
Table14FemaleAdapter
StockNumberDiameter(in.)
U-6185-0011
U-6185-0022
U-6185-0033
U-6185-0044
Notes:
1.Forusewithschedules40or80conduit.
2.Meetsallspecificationsofschedules40and 80conduit.
Table15AccessFitting,TypeT
StockNumberDiameter(in.)
U-6190-0011
Notes:
1.Forusewithschedules40or80conduit.
2.Meetsallspecificationsofschedules40and 80conduit.
Table16ServiceEntranceCap
StockNumberDiameter(in.)
U-6200-0011
Notes:
1.Forusewithschedules40or80conduit.
2.Meetsallspecificationsofschedules40and 80conduit.
SHEET OFDWG.NO. PAGE MATERIALSTANDARDSSPECIFICATION PLASTICCONDUIT&ACCESSORIES 2170V 78
Figure12
Figure13
AccessFitting,TypeT
Figure14
ServiceEntranceCap
Table17PVCSolventCement
StockNumberSize(Qt.)
U-6140-0021
Notes:
1.Forusewithschedules40or80PVCconduit.
Table18BackingPlate
StockNumberSize(in.)
U-6165-0033
U-6165-0055
Notes: 1.10'length.
Table19ConduitCarrier
StockNumberSize(in.)
U-7325-0013/4"-1-1/4"
U-7325-0033"-4"
U-7325-0044"-6"
U-7325-0081-1/2"-2-1/2"
Notes:
1.Heavy-gaugeWaterproofwovennylon.
2.Eachinflatablelinecarrieradjuststofit conduit.
SHEET OFDWG.NO. PAGE MATERIALSTANDARDSSPECIFICATION PLASTICCONDUIT&ACCESSORIES 2170V 88
Figure15 PVCSolventCement
Figure16 BackingPlate
Figure17 ConduitCarrier
Conductor installed in the District must meet certain requirements. Included in the requirements are the conductor size, type, stranding and insulation. Material not in compliance will be rejected by the District inspectors. Initially, a few select conductors were accepted by the District. In an effort to have underground cable more readily available for contractor through local suppliers, changes have been made to enlarge the list of acceptable cable. Turlock Irrigation District still requires XLP insulation, 1350 aluminum alloy with standard stranding and insulation thickness. The best way to insure compliance is to specify the code name.
An additional change is the acceptance of paralleling the conductor by the contractor. Paralleling is installing three single conductors simultaneously without benefit of the conductors being intertwined; however, the neutral wire must be permanently marked. Color tape (preferably white) or wire ties with labeling is acceptable provided it is determined to be permanent for the neutral.
The following list of conductors with size, stranding, insulation and code names are acceptable for installation at the District
Notes:
1.Compacted cable and building wire known as S8000 is NOT acceptable.
SHEET OF DWG. NO.PAGE REVDESCRIPTIONINITCHKRV'DRV'DAPPDATE RV'D MATERIAL STANDARDS CONTRACTOR DEVELOPER CONDUCTOR INFORMATION 2202D 12 --INITIAL ISSUEETEBBBLLLBGRA08-94
350 MCMBBTHCJCBLL10-98
DRAWING NUMBERSDCBLL05-02 CUPDATED STANDARDJRSJSASDPMLHMSGEDJ06-13
AADDED
BCHANGED
Figure 1
Single Conductor
Size Stranding SIW Min Standing InsulationCode Name 1/0 197 80 mils Harvard 2/0 1911 80 mils Yale 4/0 191780 milsBeloit 35037 2495 mils Rutgers 500373095 mils Emory 7506153 110 mils Sewanee 10006153110 milsFordham
Table 1Single Conductor XLP EC Grade per NEMA WC-7 1350 Aluminum
DADDED SIWMSGEDJ02-14
Table 2Triplex/Tri Parallel Conductor XLP EC Grade 1350 Aluminum
SHEET OF DWG. NO.PAGE MATERIAL STANDARDS CONTRACTOR DEVELOPER CONDUCTOR INFORMATION 2202D 22 Cable Size Stranding SIW Min. Stranding Insulation (mils) Acceptable Code Names PhaseNeutral 1/0 #2 19, 19, 7 7, 7, 7 80, 80, 60 Queens Rosary Marion Brenau 1/0 19, 19, 19 7, 7, 7 80, 80, 80 Paterson LutherMontchlair Bergen 2/0 1/0 19, 19, 1911, 11, 780, 80, 80 Shaw 2/0 19, 19, 19 11, 11, 11 80, 80, 80 CaldwellLehmanBloomfield Hunter 4/0 1/0 19, 19, 1918, 18, 780, 80, 80 Molloy Manhattanville 2/0 19, 19, 1918, 18, 1180, 80, 80 Trinity Belmont Regis Sweetbriar 4/0 19, 19, 1918, 18, 1880, 80, 80 Bronx GlassboroManhattanMonmouth 350 4/0 37, 37, 1936, 36, 1895, 95, 80 Wesleyan 500 350 37, 37, 3736, 36, 3395, 95, 95 Kings Trenton Brooklyn Rider 500 37, 37, 3736, 36, 3695, 95, 95 Stevens Jersey City St. JohnsWestchester
Cable Size Stranding SIW Min. Stranding Insulation (mils) Acceptable Code Names PhaseNeutral 1/0 #2 19, 19, 19, 77, 7, 7, 7 80, 80, 80, 60 Kent Cerritos Piedmont Notre Dame 1/0 19, 19, 19, 19 7, 7, 7, 7 80, 80, 80, 80 CarthageKellogg SouthernPurdue 2/0 1/019, 19, 19, 1911, 11, 11 ,780, 80, 80, 80 2/0 19, 19, 19, 19 11, 11, 11, 11 80, 80, 80, 80 Lycoming Itasca Brandeis Lafayette 500 350 37, 37, 37, 3736, 36, 36, 3395, 95, 95, 95 Salesian Berry Valparaiso Wofford 500 37, 37, 37, 3736, 36, 36, 3695, 95, 95, 95 Covenant CitadelMarshallLackawanna
Table 3Quadplex/Quad Parallel Conductor XLP EC Grade 1350 Aluminum
O-3325-008
GroundRod,8’x5/8"
KORTICK K5428
JOSLYN J8338
COOPER DN3C8
ABCHANCE C615880
ERITECH 615880 NEHRING NCC588
O-5505-001
Wire,BareCopper1/0AWG
SERVICE SOUTHWIRE
GENERALCABLE NEHRING
O-5505-002
Wire,BareCopper,2/0AWG
SERVICE SOUTHWIRE
GENERALCABLE NEHRING
O-5965-001
Wire,CoveredAAC,1000MCMXLP CodeName:FORDHAM
ALCAN
PRYSMIAN
NEXANS
SOUTHWIRE
GENERALCABLE KINGWIRE
54
DeveloperProvidedMaterialsUsed InUndergroundConstruction
TIDStock Number Description Manufacturer PartNumber
TIDStock Number Description
Manufacturer
PartNumber
O-5985-005 Wire,CoveredAAC,750MCMXLP
CodeName:SEWANEE
ALCAN PRYSMIAN
GENERALCABLE SOUTHWIRE NEXANS KINGWIRE
O-7189-002
Screws,Lag,WasherHead1/4”x2”or21/2”
JOSLYN J26486.2 EMC 105
O-7370-001
GroundRodClampfor5/8”Rod
PENNUNION CAB-2
BLACKBURN JAB58H
JOSLYN J8492H
KORTICK K4672
CMC WB58
ERITECH HDC58R
BURNDY GRC58
U-1346-008
ServiceBox(Small)13”x24”
NEWBASIS FCA132418C4036
QUAZITE/STRONGWELL PD1324Z501-17
CDR PA12-1324-18
U-1366-002
ServiceBox(Large)17”x30”
QUAZITE/STRONGWELL PD1730Z501-17
NEWBASIS FMA173018C4036
CDR PA12-1730-18
55
U-1366-002
Manufacturer
PartNumber
ServiceBox(ExtraLarge)24”x36”
QUAZITE/STRONGWELL PD2436Z501-17
NEWBASIS FDC243618C4938
CDR PA12-2436-18
U-2054-001
TransformerPad-SinglePhase
QUAZITE/STRONGWELL PH5448BA
NEWBASIS UGS-504
ARMORCAST 6001986
JENSENPRECAST
U-2056-001
TransformerPad–ThreePhase(75–500kVA)
UTILITYVAULT ByDescription&Spec NEWBASIS TEICHERTBROOKS
QUAZITE/STRONGWELL ARMORCAST JENSENPRECAST
U-2056-005
TransformerPad–ThreePhase(750kVA&larger)
UTILITYVAULT ByDescription&Spec NEWBASIS TEICHERTBROOKS
QUAZITE/STRONGWELL ARMORCAST
JENSENPRECAST
U-2095-001
PadmountedSwitchSubstructure
TIDStock Number Description
56
TEICHERTBROOKS 0510ASYB60PSSTID UTILITYVAULT 0260014-3300080 JENSENPRECAST 4686SWITCHVAULT
TIDStock
U-2146-003
PullBox-Large(12,000lbloading)(48”x78”x60”)
TEICHERTBROOKS 0500ASYB60TID
UTILITYVAULT
0290405-2024120
JENSENPRECAST PB466_4878_TID
U-2146-005
PullBox–X-Large(12,000lbloading)(54”x102”x72”)
UTILITYVAULT
0260012-2024120
TEICHERTBROOKS 0510ASYB60TID
JENSENPRECAST PB4686_54102_TID
U-2178-001
ConcreteTransformerVault(48”x48”x78”)
U-2178-002
ConcreteTransformerVaultCompleteLidAssembly
U-2178-003
ConcreteTransformerVault6”ExtensionRing
U-2179-001
HorizontalTransformerVault(36”x60”x54”)
TEICHERTBROOKS 0400ASYTE54LTPG
JENSENPRECAST 35TRANSFORMERVAULT UTILITYVAULT 3546–TID
U-6045-001
ConduitBrace
SHERMANRILEY KC-1
CONTINENTAL CRB396
Number Description
57
Manufacturer PartNumber
UTILITYVAULT ByDescription&Spec.
UTILITYVAULT ByDescription&Spec.
UTILITYVAULT ByDescription&Spec.
Number Description Manufacturer PartNumber 58 U-6048-001 ConduitStrap–1” INWESCO 50A10 L.H.DOTTIE 403 U-6048-002 ConduitStrap–2” INWESCO 50A14 L.H.DOTTIE 406 U-6048-003 ConduitStrap–3” INWESCO 50A18 L.H.DOTTIE 408 U-6048-004 ConduitStrap–4” INWESCO 50A22 L.H.DOTTIE 410 U-6048-005 ConduitStrap–5” INWESCO 50A26 U-6048-006 ConduitStrap–6” INWESCO 50A30 U-6050-001 Conduit–1”Schedule80 CARLON 49408 JMEAGLE 4701000102 CANTEX A53BA12 U-6050-002 Conduit–2”Schedule80
TIDStock
U-6050-003
Conduit–3”Schedule80
U-6050-004 Conduit–4”Schedule80
CANTEX A53EA12
U-6050-005
Conduit–5”Schedule80
U-6050-006
Conduit–6”Schedule80
CARLON
U-6060-002
Conduit–2”Schedule40
U-6060-003
Conduit–3”Schedule40
Manufacturer PartNumber 59
TIDStock Number Description
CARLON 49411 JMEAGLE 4702000102 CANTEX A53CA12
CARLON 49413 JMEAGLE 4703000102 CANTEX A53DA12
CARLON 49415 JMEAGLE 4704000102
CARLON 49416 JMEAGLE 4705000102 CANTEX A53FA12
49417-010 JMEAGLE 4706000103 CANTEX A53GA12
CARLON 49011 JMEAGLE 4602000103 CANTEX A52CA12
Manufacturer PartNumber 60 CARLON 49013 JMEAGLE 4603000103 CANTEX A52DA12 U-6060-004 Conduit–4”Schedule40 CARLON 49015 JMEAGLE 4604000103 CANTEX A52EA12 U-6060-005 Conduit–5”Schedule40 CARLON 49016 JMEAGLE 4605000103 CANTEX A52FA12 U-6063-003 Conduit-Elbow3”30°36”RadiusSchedule80 CARLON UB6FL CANTEX 5123759 JMEAGLE 3303680 U-6063-004 Conduit-Elbow4”30°36”RadiusSchedule80 CARLON UB6FN CANTEX 5123760 JMEAGLE 4303680 U-6063-005 Conduit-Elbow5”30°36”RadiusSchedule80 CARLON UB6FP CANTEX 5123761 JMEAGLE 5303680 U-6070-002 Conduit-Elbow2”45°18”RadiusSchedule80 CARLON UB7CJ
TIDStock Number Description
Manufacturer PartNumber 61 JMEAGLE 2451880 U-6070-003 Conduit-Elbow3”45°36”RadiusSchedule80 CARLON UB7FL CANTEX 5121077 JMEAGLE 3453680 U-6070-004 Conduit-Elbow4”45°36”RadiusSchedule80 CARLON UB7FN CANTEX 5119821 JMEAGLE 4453680 U-6070-005 Conduit-Elbow5”45°36”RadiusSchedule80 CARLON UB7FP CANTEX 5119820 JMEAGLE 5453680 U-6075-002 Conduit-Elbow2”45°18”RadiusSchedule40 CARLON UA7CJ CANTEX 5133797 JMEAGLE 2451840 U-6075-003 Conduit-Elbow3”45°36”RadiusSchedule40 CARLON UA7FL CANTEX 5133779 JMEAGLE 3453640 U-6075-004 Conduit-Elbow4”45°36”RadiusSchedule40 CARLON UA7FN CANTEX 5133777 JMEAGLE 4453640
TIDStock Number Description
Manufacturer PartNumber 62 U-6075-005 Conduit-Elbow5”45°36”RadiusSchedule40 CARLON UA7FP CANTEX 5133780 JMEAGLE 5453640 U-6080-002 Conduit-Elbow2”90°24”RadiusSchedule80 CARLON UB9CJ CANTEX 5121099 JMEAGLE 2901880 U-6080-003 Conduit-Elbow3”90°36”RadiusSchedule80 CARLON UB9FL CANTEX 5121081 JMEAGLE 3903680 U-6080-004 Conduit-Elbow4”90°36”RadiusSchedule80 CARLON UB9FN CANTEX 5121023 JMEAGLE 4903680 U-6080-005 Conduit-Elbow5”90°36”RadiusSchedule80 CARLON UB9FP CANTEX 5121083 JMEAGLE 5903680 U-6085-002 Conduit-Elbow2”90°24”RadiusSchedule40 CARLON UA9CJ CANTEX 5133844 JMEAGLE 2901840
TIDStock Number Description
Manufacturer PartNumber 63 U-6085-003 Conduit-Elbow3”90°36”RadiusSchedule40
UA9FL PWPIPE ByDescription CANTEX 5133820 JMEAGLE 3903640 U-6085-004 Conduit-Elbow4”90°36”RadiusSchedule40 CARLON UA9FN CANTEX 5133821 JMEAGLE 4903640 U-6085-005 Conduit-Elbow5”90°36”RadiusSchedule40 CARLON UA9FP CANTEX 5133841 JMEAGLE 5903640 U-6085-006 Conduit-Elbow6”90°60”RadiusSchedule40 CARLON UA9IR CANTEX 5133886 JMEAGLE ByDescription U-6090-002 Conduit–2”Schedule40/80Coupling CARLON E940J JMEAGLE 60010200 KRALOY E13120 CANTEX 6141628 U-6090-003 Conduit–3”Schedule40/80Coupling CARLON E940L JMEAGLE 60010300 KRALOY E13130
TIDStock Number Description
CARLON
Manufacturer PartNumber 64 CANTEX 6141630 U-6090-004 Conduit–4”Schedule40/80Coupling CARLON E940N JMEAGLE 60010400 KRALOY E13140 CANTEX 6141632
Conduit–5”Schedule40/80Coupling CARLON E940P JMEAGLE 60010500 KRALOY E13150 CANTEX 6141633 U-6090-006 Conduit–6”Schedule40/80Coupling CARLON E940R JMEAGLE 60010600 CANTEX 6141634 U-6092-002 Conduit–2”Schedule40LongLineCoupling CARLON E941J CANTEX 6121623 JMEAGLE 240FABCPL U-6092-003 Conduit–3”Schedule40LongLineCoupling CARLON E941L CANTEX 6202005 JMEAGLE 340FABCPL
Conduit–4”Schedule40LongLineCoupling CARLON E941N
TIDStock Number Description
U-6090-005
U-6092-004
TIDStock Number Description
Manufacturer
PartNumber
CANTEX 6202010
JMEAGLE 440FABCPL
U-6135-002
Conduit–2”Plug(Cap)
CARLON P258J
PWPIPE 61800200
KRALOY E35020A
CANTEX 5315248
U-6135-003
Conduit–3”Plug(Cap)
CARLON P258LT
PWPIPE 61800300
KRALOY E35030A
CANTEX 5315260
U-6135-004
Conduit–4”Plug(Cap)
CARLON P258N
PWPIPE 61800400
KRALOY E35040A
CANTEX 5315252
U-6135-005
Conduit–5”Plug(Cap)
CARLON P258P
PWPIPE 61800500
KRALOY E35050A
CANTEX 5315253
U-6140-002
SolventCementforConduit-1qtPVCAllWeather
CARLON VC9982 WELDON DUIT427
U-6220-000
CompressionTerminalLugfor#2Wire
65
TIDStock Number Description
Manufacturer
ANDERSON
PartNumber
AHL-2-BN-TP
BLACKBURN AL4P
HOMAC SA2NTN
DOSSERT DPL6-2N-D2-EC-SN
U-6220-001
CompressionTerminalLugfor1/0Wire
PENNUNION
ANDERSON
BLUA-1/0D3
AHL-1/0-BN-TP
BLACKBURN AL6P HOMAC AL1/0-NTN
U-6220-002
CompressionTerminalLugfor2/0Wire
PENNUNION
ANDERSON
BLUA-2/0D
AHL-2/0-BN-TP
BLACKBURN AL8P
HOMAC AL2/0-NTN
U-6220-003
CompressionTerminalLugfor4/0Wire
PENNUNION
ANDERSON
BLUA-4/0D
AHL-4/0-BN-TP
BLACKBURN AL12P
HOMAC AL4/0-NTN
U-6220-004
CompressionTerminalLugfor350MCMWire
PENNUNION
ANDERSON
BLUA-035D
AHL-350-BN-TP
BLACKBURN AL18P
HOMAC AL350-NTN
U-6220-005
CompressionTerminalLugfor500MCMWire
PENNUNION
ANDERSON
BLUA-050D2
VACL-500-12BN
BLACKBURN ALS4P
66
TIDStock Number Description
Manufacturer
PartNumber
HOMAC 2081-500
MAC MUH500
U-6220-006
CompressionTerminalLugfor750MCMWire
ANDERSON AHL-750-BN-TP
BLACKBURN AL44P
HOMAC AL750-NTN
PENNUNION KWL-079D1-P1C
U-6220-007
CompressionTerminalLugfor1000MCMWire
BURNDY YCAK44A-2G2
PENNUNION KWL-100D1-TN
BLACKBURN AL60P
U-6225-004
Wire,CoveredAAC,4/0AWGXLP
CodeName:BELOIT
ALCAN PRYSMIAN NEXANS
SOUTHWIRE CENTELSA
U-6225-007
Wire,CoveredAAC,500MCMXLPE
CodeName:EMORY
ALCAN PRYSMIAN NEXANS
SOUTHWIRE CENTELSA
U-6229-001
Cable,CoveredAAC,Triplex1/0XLPE
CodeName:BRENAU,MARIAN,QUEENS,ROSARY,PATERSON, LUTHER,MONTCHLAIR,BERGEN
67
Manufacturer
ALCAN PRYSMIAN NEXANS SOUTHWIRE CENTELSA
PartNumber
U-6229-002
Cable,CoveredAAC,Triplex2/0XLPE
CodeName:SHAW,CALDWELL,LEHMAN,BLOOMFIELD,HUNTER
ALCAN PRYSMIAN NEXANS SOUTHWIRE CENTELSA
U-6229-004
Cable,CoveredAAC,Triplex4/0XLPE
CodeName:MOLLOY,MANHATTANVILLE,TRINITY,BELMONT, REGIS,SWEETBRIAR
ALCAN PRYSMIAN NEXANS SOUTHWIRE CENTELSA
U-6229-006
Cable,CoveredAAC,Triplex350XLPE
CodeName:WESLEYAN
ALCAN PRYSMIAN NEXANS SOUTHWIRE CENTELSA
U-6229-007
Cable,CoveredAAC,Triplex500XLPE
CodeName:RIDER,BROOKLYN,KINGS,TRENTON,STEVENS, JERSEYCITY,ST.JOHNS,WESTCHESTER
ALCAN
TIDStock Number Description
68
Manufacturer
PRYSMIAN
NEXANS
SOUTHWIRE
CENTELSA
PartNumber
U-6232-001
Cable,CoveredAAC,Quadplex1/0XLPE
CodeName:NOTREDAME,PIEDMONT,CERRITOS,KENT, CARTHAGE,KELLOGG,SOUTHERNPURDUE
ALCAN
PRYSMIAN
NEXANS
SOUTHWIRE
U-6232-002
Cable,CoveredAAC,Quadplex2/0XLPE
CodeName:LYCOMING,ITASCA,BRANDEIS,LAFAYETTE
ALCAN
PRYSMIAN
NEXANS
SOUTHWIRE
U-6232-007
Cable,CoveredAAC,Quadplex500XLPE
CodeName:WOFFORD,VALPARAISO,BERRY,SALESIAN, MARSHALL,CITADEL,LACKAWANNA,COVENANT
ALCAN
PRYSMIAN
NEXANS
SOUTHWIRE
U-6290-000
CablePullingCompound1Gallon
ARNCO HLB1005P
POLYWATER A-640
DCD 35000-410
U-6300-001
SealingCompound
TIDStock Number Description
69
A.C.HORN.INC DEHYDRATING6MASTIC
U-6360-001 CableProtector
T&B
UTILCO HSC-2
3M ICEC031A
RAYCHEM ESC-3/A
U-6390-002 HeatShrinkCap(1.25”-2.50”)
T&B HSC250 SIGMAFORM SSC-250 MAC ISC250
UTILCO HSC-3
3M ICEC061A
RAYCHEM ESC-5/A
U-6390-003 HeatShrinkCap(1.75”-3.60”)
T&B HSC360
SIGMAFORM SSC-360
MAC ISC360
3M ICEC161A
RAYCHEM ESC-6/A
U-6440-001 PowerMarker-Flat
70
TIDStock Number Description Manufacturer PartNumber
CONDUX
VIRGINIAPLASTICS LG-345 ELECRICALMATERIALSCO. 27-1
08042300 EMCO 27-1G
U-6390-001 HeatShrinkCap(0.75”-1.50”)
HSC300-600 SIGMAFORM SSC-150 MAC ISC150
TIDStock Number Description
Manufacturer
PartNumber
3M #1251
U-6470-001
StreetLightFuseHolder
BUSS TRONHEB-JJ
U-6471-001
StreetLightFuseHolderBoots
BUSS 1A0512
U-7145-010
StreetLightFuse10Amp
BUSS BAF10
U-7145-015
StreetLightFuse15Amp
BUSS BAF15
U-7145-025
StreetLightFuse25Amp
BUSS BAF25
U-7145-030
StreetLightFuse30Amp
BUSS BAF30
U-8200-004 PullRope–3/4"
NEPTCO WP2500P
ARNCO BLWP25
HERCULINE P2500W
WELLINGTON N303M
71
Section5
LocatingMaterials
Thefollowingisalistofsupplierswhohaveindicatedthattheystockmaterialsrequiredby TID.Pleasenotethat notallmaterialsareavailablefromallsuppliers.Ifyouhave anyquestionsorproblemssourcingmaterialsrequiredbyTID,pleasecontacttheTID PurchasingDivisionat(209)883-8401.
AcmeElectric
1025S.KilroyRd.
Turlock,CA95380
(209)667-2851
Contact:BusterLucas
All-PhaseElectric 2250CooperAve
Merced,CA95340
(209)384-0777
ChampionWireandCable
822W.22ndSt
Tempe,AZ85282
(800)329-1900
(602)736-1525
Contact:JeremyScott
ConsolidatedElectricDistributors(CED)
1343N.EmeraldAvenue
Modesto,CA95351
(209)524-5591
Contact:SteveMiller
CentralWholesaleElectric
1466N.CarpenterRd
Modesto,CA95351
(209)550-2500
Contact:RandyDeCicco
GraybarElectric
1211FeeDr
Sacramento,CA95815
(800)388-8061ext.1947
Contact:RodRuggles
72
HerningUndergroundSupply
567ExchangeCt
Livermore,CA94550
(925)373-8660
Contact:PatRuth:(559)994-8312
IndependentElectricSupply,Inc.
1565VentureLane
Turlock,CA95380
(209)668-4702
Contact:DavidCrew
Kingwire
3030N.LambBlvdSte113
LasVegas,NV89115
(702)368-7597
(702)368-7598(fax)
Contact:Bob
PlattElectric
1431FreitasPkwy
Turlock,CA95380
(209)656-1063
Contact:DeeannHarmon
RexelNorcalValley
919EmeraldAvenue
Modesto,CA95351
(209)577-6611
Contact:AlexCeja
WillieElectricSupply
101S.7thStreet
Modesto,CA95333
(209)527-6800
Contact:GaryBird/ToddWilson
73
Thefollowinglistofcompanieshavematerialonhand,haveaccesstomaterial,orwill provideyouwithadditionalsourcestolocatematerialsrequiredbytheDistrict.Order materialsinadvanceassomemayhavealeadtime.
COMPANY
NewBasis
11501DublinBlvdSte.200
Dublin,CA94568
(925)551-5019
TeichertBrooks
2441CharterWay Stockton,CA95206
(209)464-7696
ElectriGroup
4600PellDr.
Sacramento,CA95838
(916)922-5550
GEXPRO
GeneralElectricSupplyCompany
4608RosevilleRd
NorthHighlands,CA95660
(916)339-4521
Intraline
379BeachRd.
Burlingame,CA94010
(650)340-9133
KortickManufacturingCo.
2230DavisSt. Hayward,CA94545
(510)856-3600
BRANDNAME
NewBasis
TeichertBrooks
Carlon
Carlon
Cantex
Polywater
Cantex
J-MEagle
Kortick
72
COMPANY
Neptco
P.O.Box2323
Pawtucket,RI02861-0323
(800)354-5445
Maydwell&Hartzell
2236DavisCt.
Hayward,CA94545
(510)780-1700
PacificUtilities
2475EstandWay
PleasantHill,CA94523
(925)674-1600
HDSupply-Benicia
6350GoodyearRd
Benicia,CA94510
(800)670-7746
HDSupply-Portland
9151S.E.McBrod
Portland,OR97222
(800)547-9490
WestchemEquipmentCo.
28301IndustrialBlvd.
Hayward,CA94545
(510)782-3675
BRANDNAME
Neptco
Strongwell/Quazite
VirginiaPlastics
Utilco Fargo
Homac
Inwesco
Burndy
Alcan
Cantex
Carlon
Polywater
Inwesco
73
Section6 Inspections
Facilitiesconstructedbyeithertheownerorhisorherbuildermustbeconstructed accordingtoTIDstandardsandapplicablelocalbuildingcodes.
IftheTIDinspectordeterminesthatanyofthecustomer/builder-installedfacilitiesdonot meetTIDstandards,theowner/builderwillberesponsibleformakingthenecessary changesathisorhercost.
TIDcannotcompletetheserviceworkuntil ALL customerworkhaspassedTIDand applicablegoverningagencies’inspections.
ThefollowingisalistofgoverningagencieswithintheTIDserviceterritory:
StanislausCountyBuildingInspectionOffice
ATTN:DeputyBuildingInspector
101010thSt.,Suite3500,Modesto95354
(Serving:Ceres,Denair,Hickman,Keyes,LaGrange&StanislausCo.)
Phone:(209)525-6557
MercedCountyInspectionOffice
ATTN:ChiefBuildingOfficial 2222MSt.,Merced95340
(Serving:Ballico,Delhi,Hilmar&MercedCo.)
Phone:209)385-7477
CityofHughsonBuildingDepartment
ATTN:ChiefBuildingOfficial 7001WhitmoreAve.#8
Hughson,CA.95326
(Serving:CityofHughson)
Phone:(209)883-0811
CityofModestoBuildingInspectionDepartment 101010thSt.,Suite3100,Modesto95354
(Serving:CityofModesto)
Phone:(209)577-5232
74
CityofPattersonCommunityDevelopmentDepartment
BuildingDivision
1Plaza,Patterson95363
(Serving:CityofPatterson)
(209)895-8030
CityofTurlockBuildingInspectionDepartment
156S.Broadway,Ste130,Turlock95380
(Serving:CityofTurlock)
Phone:(209)668-5560
NOTE:Undersomeconditions,stateorotherauthoritieswillberesponsibleforinspecting theelectricfacilities.Theagencieslistedabovewillassistyouindeterminingtheproper authority.
75