Uponor plaster system for ceiling and wall cooling/heating

MOUNTING INSTRUCTIONS

Only for installation by authorised specialists!

Pipe system installation

≈ 500

500 ø 6 mm

a T

Uponor PEX 9,9

Optimal loop length: L = 50 m

T 80 100 140

a 60 70 90


Supply pipe installation

INSTALLATIONSSYSTEME TECHNISCHE INFORMATIONEN

PE-Xa Installationssystem mit Quick & Easy Verbindungstechnik

Follow the additional instruction: Uponor Q&E Installation

ø 6 mm

Q&E 9,9

Q&E 20

Fill pipes/Pressure test

2h

max. 6 bar

MONTAGEANLEITUNG MOUNTING INSTRUCTIONS

D

F

GB

I

NL

CZ

DIN 1264-4

After 2 h leak test

Mounting/operating instructions for the Uponor manifolds

2

1048014 03/2010


Plaster work

≈10 14

e.g. Knauf MP75 G/F-Light

e.g. Knauf NP75 Diamant ≈ 10 14

While plastering, all circuits have to be held under operating pressure. The system has to be kept frostfree.

Operational check

The system function has to be tested with the heating function process. For documentation use the Uponor heating function form. The waiting period after palstering should be Cement-bonded plaster: > 21 days Gypsum-bonded plaster: > 7 days Observe also the plaster manufacturer's instructions.

1048014 03/2010

3


Operation

ϑSupply ϑSurface

16 – 40° C < 35° C

16 – 50° C < 40° C

1048014 – 03/2010 ME – Subject to modifications

The building management must be informed of the location of the system pipes.