Uponor Smatrix Move PRO H E AT I N G / C O O L I N G A P P L I C AT I O N E N I N S TA L L AT I O N A N D O P E R AT I O N MANUAL
12 | 2016
UK
Table of contents
CZ DE
1 2
DK
Copyright and disclaimer......................................3
6
Preface...................................................................4
7 Operate the Uponor Smatrix Move PRO controller.............................................................51
2.1 2.2
EE
Safety instructions.....................................................4 Correct disposal of this product (Waste Electrical and Electronic Equipment)........................................4
Installation procedure..............................................12 Prepare for installation............................................12 Installation examples...............................................12
7.1 Principle of operation..............................................51 7.2 Controller layout......................................................51 7.3 Navigating the menu system...................................51 7.4 Start up...................................................................52 7.5 Information button..................................................52 7.6 Main menu..............................................................53 7.7 System Overview.....................................................53 7.8 Information..............................................................53 7.9 Alarms.....................................................................61 7.10 Settings...................................................................62 7.11 Pre Heating Info....................................................131 7.12 Pre Heating Settings.............................................133 7.13 Menu tree..............................................................140
5 Install Uponor Smatrix Move PRO controller.....23
8 Maintenance......................................................150
3
Uponor Smatrix Move PRO...................................5 3.1 System overview........................................................5 3.2 Example of a system..................................................6 3.3 Uponor Smatrix Move PRO components...................7 3.4 Accessories..............................................................10 3.5 Functions................................................................10
ES FI
4
Install Uponor Smatrix Move PRO system.........12 4.1 4.2 4.3
FR
5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8
HR HU IT
5.9 5.10
LT
5.11 5.12 5.13 5.14 5.15 5.16 5.17 5.18
LV NL
Finishing installation..........................................50
Placement of controller...........................................23 Select controller application....................................23 Attach stickers.........................................................23 Insert microSD card.................................................23 Attach controller to the wall....................................24 Terminal cover.........................................................24 Connect sensors to controller..................................24 Connect external signal for heating/cooling switch to the controller............................................36 Connect mixing valve actuators to the controller.....36 Connect diverting valve actuators to the controller.................................................................37 Connect circulation pumps to the controller............38 Connect a dehumidifier to the controller.................39 Connect Uponor Smatrix Base PRO controller.........40 Connect Modbus RTU interface...............................40 Connect the controller to AC power.........................41 Alternate power inputs............................................41 Startup wizard.........................................................41 Pre heating concrete slab (DIN 1264-4)..................48
8.1 8.2 8.3 8.4
Manual preventive maintenance............................150 Automatic preventive maintenance.......................150 Corrective maintenance.........................................150 Controller display...................................................150
9 Troubleshooting................................................151 9.1 9.2 9.3
Troubleshooting after installation..........................152 Contact the installer..............................................152 Installer instructions..............................................152
10 Technical data....................................................153 10.1 10.2 10.3 10.4
Technical data........................................................153 Technical specifications.........................................154 Controller layout....................................................154 Wiring diagram, Uponor Smatrix Move PRO controller...............................................................155 10.5 Dimensions............................................................156
11 Installation report.............................................157
NO PL PT RO RU SE SK 2
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK
1
Copyright and disclaimer
CZ DE
Uponor has prepared this installation and operation manual and all the content included solely for information purposes. The contents of the manual (including graphics, logos, icons, text, and images) are copyrighted and protected by worldwide copyright laws and treaty provisions. You agree to comply with all copyright laws worldwide in your use of the manual. Modification or use of any of the contents of the manual for any other purpose is a violation of Uponor’s copyright, trademark and other proprietary rights. The presumption for the manual is that the safety measures have been fully complied with and, further, that Uponor Smatrix Move PRO, including any components that are part of such system, covered by the manual: • is selected, planned and installed and put into operation by a licensed and competent planner and installer in compliance with current (at the time of installation) installation instructions provided by Uponor as well as in compliance with all applicable building and plumbing codes and other requirements and guidelines; • has not been (temporarily or continuously) exposed to temperatures, pressure and/or voltages that exceed the limits printed on the products or stated in any instructions supplied by Uponor; • remain in its originally installed location and is not repaired, replaced or interfered with, without prior written consent of Uponor;
While Uponor has made efforts to ensure that the manual is accurate, Uponor does not guarantee or warrant the accuracy of the information contained herein. Uponor reserves the right to modify the specifications and features described herein, or discontinue manufacture of Uponor Smatrix Move PRO described at any time without prior notice or obligation. The manual is provided “as is” without warranties of any kind, either expressed or implied. The information should be independently verified before using it in any manner.
DK EE ES FI
To the fullest extent permissible, Uponor disclaims all warranties, expressed or implied, including, but not limited to, the implied warranties of merchantability, fitness for particular purpose and non-infringement.
FR HR
This disclaimer applies to, but is not limited to, the accuracy, reliability or correctness of the manual. Under no circumstances shall Uponor be liable for any indirect, special, incidental or consequential damages or loss that result from the use of or the inability to use the materials or information in the manual, or any claim attributable to errors, omission or other inaccuracies in the manual, even if Uponor has been advised of the possibility of such damages.
HU IT LT
This disclaimer and any provisions in the manual do not limit any statutory rights of consumers.
LV
• is connected to potable water supplies or compatible plumbing, heating and/or cooling products approved or specified by Uponor;
NL
• is not connected to or used with non-Uponor products, parts or components except for those approved or specified by Uponor; and
NO PL
• does not show evidence of tampering, mishandling, insufficient maintenance, improper storage, neglect or accidental damage before installation and being put into operation.
PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
3
UK
2
CZ
Preface
DE This installation and operation manual describes how to install and operate the components of the system.
DK
2.1 Safety instructions EE
Warnings used in this manual
ES
The following symbols are used in the manual to indicate special precautions when installing and operating any Uponor equipment:
W arning !
FI
Risk of injury. Ignoring warnings can cause injury or damage components.
FR
C aution ! Ignoring cautions can cause malfunctions.
HR
Safety measures Conform to the following measures when installing and operating any Uponor equipment:
HU
• Read and follow the instructions in the installation and operation manual.
IT
• Installation must be performed by a competent person in accordance with local regulations.
LT
2.2 Correct disposal of this product (Waste Electrical and Electronic Equipment) N OT E ! Applicable in the European Union and other European countries with separate collection systems This marking shown on the product or its literature indicates that it should not be disposed with other household wasted at the end of its working life. To prevent possible harm to the environment or human health from uncontrolled waste disposal, please separate this from other types of wastes and recycle it responsibly to promote the sustainable reuse of material resources. Household users should contact either the retailer where they purchased this product, or their local government office, for details of where and how they can take this item for environmentally safe recycling. Business users should contact their supplier and check the terms and conditions of the purchase contract. This product should not be mixed with other commercial wastes of disposal.
• It is prohibited to make changes or modifications not specified in this manual. • All power supplies must be switched off before starting any wiring work.
LV
• Do not use water to clean Uponor components.
NL
• Do not expose the Uponor components to flammable vapours or gases. Uponor cannot accept any responsibility for damage or breakdown that can result from ignoring these instructions.
NO PL
Power
W arning !
PT
The Uponor system uses 50 Hz, 230 V AC power. In case of emergency, immediately disconnect the power.
RO
Technical constraints
RU
C aution ! To avoid interference, keep installation/data cables away from power cables of more than 50 V.
SE SK 4
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK
3
Uponor Smatrix Move PRO
CZ DE
Uponor Smatrix Move PRO is a supply temperature control system for use in different zones. The number of zones and setup vary depending on which application package (supplied with the controller) has been installed (inserting the microSD card into the controller). This manual only reflects the installation of the controller together with the heating/cooling application package. Heating application Using the heating application, enables up to four zones to be setup for heating with different radiant systems (such as underfloor loops, radiators etc.), domestic hot water, or snow melting (keeping large areas clear of snow). Heating/cooling application Using the heating/cooling application enables up to three zones to be setup for heating and/or cooling with different radiant systems (such as underfloor loops, ceiling panels etc.), domestic hot water, or snow melting (keeping large areas clear of snow)
3.1 System overview Uponor Smatrix Move PRO consists of a controller and a wide array of sensors. Together they control the supply temperature in each zone by managing the connected valve actuators and circulation pumps. The zones can be setup as follows. Zone
Setup alternatives
1
Stand Alone Control
Stand Alone Control If the zone is setup as Stand Alone Control, the controller operates without individual room control. The supply temperature setpoint is calculated using an outdoor sensor and a room temperature sensor (optional for heating only, mandatory together with humidity sensor S-157 for heating/cooling).
DK
The zone can switch between heating and cooling using one of the following functions (set in the startup wizard):
ES
EE
FI
• Indoor and Outdoor uses the indoor and outdoor temperatures to switch the zones between heating and cooling.
FR
• Supply Water Temp. uses the supply water temperature to switch the zones between heating and cooling.
HR
• Contact Input uses an external signal to switch the zones between heating and cooling.
HU
• Force Heating sets the zones in forced heating. • Force Cooling sets the zone in forced cooling.
IT
The optional room temperature sensor is placed in a reference area and enables an indoor temperature setpoint parameter. It is used to keep the indoor temperature as close as possible to the indoor temperature setpoint.
LT LV
A relative humidity sensor is used to avoid condensation problems while in cooling mode. An optional condesation sensor can be installed for added security.
NL
Smatrix Base PRO
2
NO
Stand Alone Control Smatrix Base PRO
PL
Domestic Hot Water
3
Stand Alone Control Smatrix Base PRO
PT
Meltaway
RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
5
UK CZ DE DK
Smatrix Base PRO
Meltaway
If the zone is setup as Smatrix Base PRO, individual room control in the zone is enabled via an integrated Uponor Smatrix Base PRO system. The supply temperature setpoint is calculated using sensor data and current mode from the Base PRO system.
If the zone is setup as Meltaway, snow melting (keeping large areas clear of snow) is enabled in the zone. The supply temperature setpoint is calculated using an outdoor sensor, a ground temperature sensor, and a ground moisture sensor.
Heating/cooling mode is set from the Smatrix Base PRO system.
When to start or stop snow melting (status: Stop, Idle or Meltaway) is determined by using an outdoor temperature sensor and two Uponor Smatrix Move PRO Sensor Snow S-158 sensors. One of S-158 sensors is used for measuring the ground temperature and the other one is used for measuring the ground moisture level.
The outdoor temperature sensor is connected to the Base PRO system via a thermostat, registered as a system device. The thermostat is preferably placed in a non-public area such as a technical room. The outdoor temperature sensor data will also be used by the other zones.
EE ES
This requires the Move PRO controller to be connected to a Smatrix Base PRO bus.
FI
A relative humidity sensor within the Smatrix Base PRO system is used to avoid condensation problems while in cooling mode.
FR
Domestic Hot Water
HR
If the zone is setup as Domestic Hot Water, hot water regulation is enabled in the zone. The supply temperature setpoint is set in the Move PRO controller display.
HU
The return temperature sensor is used to calculate the difference between the supply and return temperature and tripps an alarm if the difference is too high. The primary return sensor is used to protect the heat source from too low return temperatures.
3.2 Example of a system The illustration below shows a property divided into different zones. All zones are controlled by the Uponor Smatrix Move PRO. N OT E ! This is an example. The Move PRO controller can be setup in a wide array of combinations.
N OT E ! If the zone is setup as Domesitc Hot Water without a return sensor, the zone will work with reduced functionality. Functions such as BoostPower and hot water recirculation requires a return sensor to work properly.
IT LT
1 3
LV
2
NL NO PL PT RO
Zone
Description
1
The zone (underfloor heating in a warehouse) is setup as Stand Alone Control.
2
The zone (domestic hot water production) is setup as Domestic Hot Water.
3
The zone (keeping a parking lot and a large court yard clear of snow) is setup as Meltaway.
RU SE SK 6
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK
3.3 Uponor Smatrix Move PRO components C ontroller The controller operates the valve actuators and circulation pumps, which in turn affect the supply water temperature to the zone.
Components of the controller The illustration below shows the controller and its components with the heating/cooling application package.
CZ DE
The temperature in up to three zones can be regulated by the controller.
DK
Uponor Smatrix Move PRO Controller X-159 Main characteristics:
2 1 15VDC GND 12VDC IN GND 24VAC IN 1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18
- +
42 43
• Integrated display with menu system.
- +
- +
45 46
48 49
52 53 54 55 56
21 22 23 24 25 26
72 73
75 76
B
T
microSD
N L 125 mA 230 V ±10% 50/60 Hz
77 78
- A B
1 2
L N PRO PRO
L N
PRO PRO
3
L N
PRO PRO
06 | 2016
4
5
5
6
6
7
7
8
8
9
10 11 12 13 14 15 16 17 18 10 11 12 13 14 15 16 17 18
9
41
42
43
44
45
46
48
47
49
50
51
52
53
54
55
56
ES 56
1T
L
L
55
N
N
54 53
80
GND
52
GND
15VDC
230 V ± 10% 50/60 Hz
24VAC IN
12VDC IN
N L
3
IIN ≤ 6A
50
2
IIN ≤ 6A
!
77
N L
76
46
2
1
3
45
2
74
1
44
3
N L
1/2
73
3
43
2
30
Base PRO
26
3
29 28
25
3 1/2
27 26
3
25 24
1/2
8 8 7 7
T
4 3 3
1
2
microSD
2
27
28
71
72
73
74
75
76
77
78
79
80
125 mA
microSD
1
26
1
25
Base PRO
24
• Heating/cooling curve (Stand Alone Control and Smatrix Base PRO zones only).
Item A
Uponor Smatrix Move PRO Controller X-159
• Connection of maximum three actuators (one per zone).
B
Heating/cooling application package (microSD card, application diagram, connection stickers)
• Connection of maximum three circulation pumps (one per zone).
FI
23
3B A
22
Base PRO
-
L
21
N
9
N L
SMATRIX BASE PRO – BUS
≤ 1A
10 11 12 13 14 15 16 17 18 10 11 12 13 14 15 16 17 18
≤ 6A
N L
9
≤ 6A
N L
2
30
L
6
29
N
6
B 23
230 V ± 10% 50/60 Hz
5
A 22
2
5
21
26
3
4
microSD
25
2
!
Base PRO SMATRIX BASE PRO – BUS
1
!
3
!
41
71
42
72
1
1
75
47
48
3
49
78
IIN ≤ 1A
! !
1
51
Base PRO
79
15VDC
Base PRO
125 mA
2
3
4
GND
2
3
GND
1
2
24VAC IN
1
12VDC IN
• Control of supply temperature for up to three zones (up to three heating systems, one snow melting zone, and one domestic hot water zone).
EE
A
3
microSD
Description
FR HR
The box also contains a heating application package which is explained in another installation and operation manual.
HU
• Pump exercise. • Change supply temperature using customizable schedules (ECO mode).
IT
• Initial setup done via startup wizard. • BMS ready via Modbus and KNX interfaces.
LT
• Integration with Uponor Smatrix Base PRO via system bus.
LV
Options: • Cabinet or wall mounted using a DIN rail (not supplied).
NL NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
7
UK R oom
H umidity
sensor
N OT E ! The room sensor is affected by the temperature of the surrounding surfaces as well as the ambient air temperature.
CZ DE DK EE ES
Uponor Smatrix Move PRO Sensor Humidity S-157 The sensor is designed to measure the relative humidity within the zone.
Uponor Smatrix Move PRO Sensor Room S-155
The sensor is only used in zones setup as Stand Alone Control.
The sensor is designed to measure the indoor reference temperature within the zone.
Main characteristics:
The sensor is only used in zones setup as Stand Alone Control.
• Prepared for wall or connection box mounting.
• Sensor range is 0 – 100 %.
Main characteristics:
Components of the humidity sensor:
• Sensor range is 0 – 60 °C.
The illustration below shows the humidity sensor and its components.
• Prepared for wall or connection box mounting.
FI
sensor
Components of the room sensor: The illustration below shows the room sensor and its components.
FR
A HR
Item A
HU
Description Smatrix Move PRO Sensor Humidity S-157
A Item
IT
A
Description Smatrix Move PRO Sensor Room S-155
LT LV NL NO PL PT RO RU SE SK 8
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK C ondensation
S now
sensor
and ice sensor
Uponor Smatrix Condensation Set S-159
Uponor Smatrix Move PRO Sensor Snow S-158
CZ
The sensor set is designed to detect and prevent condensation while the zone is in cooling mode.
The sensor is designed to be embedded into outdoor surfaces to measure the ground temperature and moisture level.
DE
The sensor is only used in zones setup as Stand Alone Control or Smatrix Base PRO.
DK
• Sensor range: Condensation detected, Yes/No.
The sensor is only used in zones setup as Meltaway. To ensure the snow melting function, two Uponor Smatrix Move PRO Sensor Snow S-158 and three supply/return sensors must be installed.
• Converter for cooling allowed signal.
Main characteristics:
EE
Components of the condensation sensor:
• Detects moisture.
The illustration below shows the condensation sensor and its components.
• Detects temperature.
Main characteristics:
ES
• Horizontal installation to ensure collection of draining melt water.
FI
Options:
A Item
B
Description
A
Condensation sensor
B
Converter
• The sensor can be used as either ground temperature sensor or ground moisture sensor. It cannot be used for both at once.
FR HR
Components of the snow sensor: The illustration below shows the snow sensor and its components.
HU IT
A Item
B
LT
Description
A
Smatrix Move PRO Sensor Snow & Ice S-158
B
Mounting socket
LV NL NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
9
UK CZ
3.4 Accessories
3.5 Functions
Uponor offers a wide variety of accessories for use with the standard portfolio.
H eating / cooling
DE
A
DK
B
C
N OT E ! Some of these accessories may be included in the system.
EE ES
Item Component A
FI
Uponor Smatrix Sensor Outdoor S-1XX
Description Outdoor sensor for use with system without a zone setup as Smatrix Base PRO.
curve
The Move PRO controller use a heating/cooling curve to calculate the supply temperature setpoint. This requires the zone to be setup as Stand Alone Control or Smatrix Base PRO. The heating/cooling curve for the Uponor Smatrix Move PRO controller is shown in the diagram below. The diagram shows the calculated supply temperature, for each curve, at different outdoor temperatures. The controller uses the selected curve to operate the mixing valve, which in turn adjusts the supply temperature to the system. Supply temperature 5 4,5 4 3,5
80
3
2,5
2
70
(outdoor sensor S-1XX)
FR
B
HR
Uponor Smatrix Move Sensor Supply/Return S-152
C
Uponor Smatrix Bus cable A-145
1 0,8
50
0,7 0,6
40 0,4 30
0,2
20
(supply/return sensor S-152)
HU
1,2
60
Sensor that can be used as either a supply or return sensor.
1,5
10
Bus cable for use with integration of Uponor Smatrix Base PRO system
36 34 32 30 28 26 24 22 20 18 16 14 12 10 8
6
4
2
0 -2 -4 -6 -8 -10 -12 -14 -16 -18 -20
Outdoor temperature
IT
The choice of curve depends on a combination of different factors, such as how well insulated the house is, geographical location, type of heating/cooling system etc.
LT
Example: A poorly insulated house heated by a radiator system requires a higher curve value than an equivalent house with underfloor heating.
LV
The curves in the diagram are also limited by maximum and minimum parameters set in the system (marked in the diagram with extra thick lines).
NL NO PL PT RO RU SE SK 10
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK R eal
S ystem
time clock
To facilitate accurate scheduling, the controller contains a real time clock. If an Uponor Smatrix Base PRO system is connected it will act as a time master, pushing the current time setting to the Move PRO controller.
C omfort
and
ECO
modes
( scheduling )
With the integrated timer in the controller, it is possible to change the temperature setpoint modes between two different temperatures. To utilise the Comfort and ECO modes in a zone, the zone must be setup as Stand Alone Control and using an room sensor. Available modes are Comfortand ECO (economy). See example of Comfort and ECO mode below. Schedule 1
integration with
B ase PRO
systems
The system can be integrated with an Uponor Smatrix Base PRO system to enable individual room control in the zone.
CZ
The outdoor temperature sensor is connected to the Base PRO system, and an additional outdoor temperature sensor connected to the Move PRO controller is not needed. The outdoor temperature sensor data will also be used by the other zones.
DE DK
The integration is activated when a zone is setup as Smatrix Base PRO (requires that the wiring is done and that Supply Water Controller is activated in the Integration menu in the Base PRO interface) in the startup wizard on the Move PRO controller.
EE ES
See section 5.10 Connect Uponor Smatrix Base PRO controller for more information.
Comfort ECO night 0 h 00
morning 6 h 00
afternoon 12 h 00
night
18 h 00
24 h 00
Other zones can, depending on system setup, simultaneously switch between Comfort and ECO mode according to their own programmed schedules.
FI
See section 5.13 Startup wizard for more information. See Uponor Smatrix Base PRO documentation for more information.
FR HR
Schedule 2 Comfort ECO night 0 h 00
morning 6 h 00
afternoon 12 h 00
18 h 00
HU
night 24 h 00
IT
Even if programmed schedules exist in the system, some zones may still operate without any scheduling. These zones will operate in constant Comfort mode and is not affected by the programming of other zones.
LT LV NL NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
11
UK
4
CZ
Install Uponor Smatrix Move PRO system
DE
4.1 Installation procedure DK
To determine where to best place the Uponor Smatrix Move PRO components, follow these guidelines:
U ponor S matrix M ove PRO Uponor recommends following the process described below to guarantee the best possible installation results.
EE
Stage
ES FI FR
IT
Page
• Ensure that the controller can be mounted close to 230 V AC supply.
1
Prepare for installation
12
2
Install Uponor Smatrix Move PRO controller
23
3
Connect sensors to the controller
24
4
Connect mixing valve actuators to the controller
36
4.3 Installation examples
5
Connect diverting valve actuators to the controller
37
The following sections describe a selection of installation examples with the Move PRO controller:
6
Connect circulation pumps to the controller
38
• Heating/cooling 2-pipe system in three different zones
7
Connect Uponor Smatrix Base PRO controller
40
• Heating/cooling 2-pipe system together with domestic hot water and meltaway production
8
Connect the controller to AC power
41
9
Startup wizard
41
10
Finishing installation
50
HR HU
Procedure
• Ensure that the controller can be installed close to the valve actuators, if possible.
4.2 Prepare for installation LT
Before starting the installation:
LV
• Verify the contents of the package with the packing list. See also section 3.3 Uponor Smatrix Move PRO components for identification of components.
NL
• Study the wiring diagram in the end of this manual or on the controller.
NO
2 230
-24
0V
Hz 50 L N
N 79 77 74
PL
21
22
23
24
25
26
27
28
29
72
75
• Heating/cooling 4-pipe system in three different zones • Heating/cooling 4-pipe system together with domestic hot water production
W arning ! Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician. N OT E ! These are outline diagrams. Real systems must be installed according to applicable norms and regulations.
T
125
71
• Ensure that installed Uponor Smatrix Move PRO components are protected from running or dripping water, preferably in a cabinet.
mA
L
80
78
76
73
30
microSD
PT RO RU SE SK 12
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK H eating / cooling 2- pipe
The supply is routed to the zones from the heating and cooling sources using two diverting valves. This enables switching between heating and cooling in all zones simultaneously.
system in three
different zones
3
A
B
Base PRO
2
A
The zone temperatures are regulated using a wide range of sensors, by using either a three-way mixing valve (B) or a two-way valve together with a heat exchanger (A), set temperatures (setpoints), and other zone specific parameter settings.
DE
Example specific electrical connections
EE
DK
• The supply line diverting valve is connected to the terminals labelled 24 and 26.
B
Base PRO
1
CZ
ES
• The return line diverting valve is connected to the terminals labelled 25 and 26.
A
FI
• External signal for heating/cooling switch in all zones are connected to the terminals labelled 17 and 17 .
B
Base PRO
FR
See section 5 Install Uponor Smatrix Move PRO controller for more information.
HR
See also the wiring diagram in the end of the manual. Example specific system settings in startup wizard
HU
Operation Mode: Standard System Type: 2 Pipe
IT
Indoor Cooling Only: No Enable Zone # (# = 1, 2, and 3): Yes C
W arning ! Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
Zone setup: Stand Alone Control, or Smatrix Base PRO
LT
HC Switchover: Indoor and Outdoor, Supply Water Temp., Contact Input, Force Heating, or Force Cooling.
LV
See section 4.3 Installation examples > Zone setup for more zone specific startup wizard settings.
NL
See section 5.13 Startup wizard for more information.
NO
See section 7.10 Settings for more information.
N OT E ! These are outline diagrams. Real systems must be installed according to applicable norms and regulations.
PL PT
This connection example shows an Uponor Smatrix Move PRO Controller (with the heating/cooling application installed) regulating three different heating/ cooling zones in a 2-pipe system.
RO
• Zone 1 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling.
RU
• Zone 2 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling.
SE
• Zone 3 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling.
SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
13
UK H eating / cooling 2- pipe
system together with
domestic hot water and meltaway production
CZ
3
DE
A
B
2
This connection example shows an Uponor Smatrix Move PRO Controller (with the heating/cooling application installed) regulating three different zones in a 2-pipe system.
ES
1
FI
Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician. N OT E ! These are outline diagrams. Real systems must be installed according to applicable norms and regulations.
DK EE
W arning !
FR
A
• Zone 1 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling.
B
• Zone 2 is setup for Domestic Hot Water production. Base PRO
• Zone 3 is setup for melting snow with Meltaway. The supply is routed to zone 1 from the heating and cooling sources using two diverting valves, switching the zone between heating and cooling. Zones 2 and 3 are installed between the diverting valves and the heat source. This enables zones 2 and 3 to be operated independently from zone 1 (regardless if it is in heating or cooling mode).
HR HU IT
1
LT C
LV
The zone temperatures are regulated using a wide range of sensors, by using either a three-way mixing valve (B) or a two-way valve together with a heat exchanger (A), set temperatures (setpoints), and other zone specific parameter settings. N OT E ! When using a 3-way mixing valve (option B) in a meltaway zone, a heat exchanger may be needed. This creates a secondary loop where water mixed with antifreeze additives circulate.
NL NO PL PT RO RU SE SK 14
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Example specific electrical connections • The zone 1 supply and return line diverting valves are connected to the terminals labelled 24 and 26. Note! An external relay may be needed when connecting two diverting valves to the connection terminals.
CZ DE
• External signal for heating/cooling switch in zone 1 is connected to the terminals labelled 17 and 17 .
DK
See section 5 Install Uponor Smatrix Move PRO controller for more information.
EE
See also the wiring diagram in the end of the manual.
ES
Example specific system settings in startup wizard Operation Mode: Standard
FI
System Type: 2 Pipe Indoor Cooling Only: No Enable Zone # (# = 1, 2, and 3): Yes
FR
Zone setup (zone 1): Stand Alone Control, or Smatrix Base PRO
HR
Zone setup (zone 2): Domestic Hot Water Zone setup (zone 3): Meltaway
HU
HC Switchover: Indoor and Outdoor, Supply Water Temp., Contact Input, Force Heating, or Force Cooling.
IT
See section 4.3 Installation examples > Zone setup for more zone specific startup wizard settings.
LT
See section 5.13 Startup wizard for more information. See section 7.10 Settings for more information.
LV NL NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
15
UK H eating / cooling 4- pipe
system in three
W arning !
different zones
CZ
3
DE
Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
A
B
Base PRO
DK
2
EE
A
B
ES
Base PRO
1
FI FR
N OT E ! These are outline diagrams. Real systems must be installed according to applicable norms and regulations. This connection example shows an Uponor Smatrix Move PRO Controller (with the heating/cooling application installed) regulating three different heating/ cooling zones in a 4-pipe system.
A
• Zone 1 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling.
B
• Zone 2 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling. Base PRO
HR
• Zone 3 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling. The supply is routed to the zones from the heating and cooling sources using four diverting valves. This enables zone 3 to be switched between heating and cooling independently from in zones 1 and 2 (which switch simultaneously).
HU IT
3
The zone temperatures are regulated using a wide range of sensors, by using either a three-way mixing valve (B) or a two-way valve together with a heat exchanger (A), set temperatures (setpoints), and other zone specific parameter settings.
1&2
LT C
LV NL NO PL PT RO RU SE SK 16
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Example specific electrical connections • The zone 1&2 supply and return line diverting valves are connected to the terminals labelled 24 and 26. Note! An external relay may be needed when connecting two diverting valves to the connection terminals.
CZ
• The zone 3 supply and return line diverting valves are connected to the terminals labelled 25 and 26. Note! An external relay may be needed when connecting two diverting valves to the connection terminals.
DK
• External signal for heating/cooling switch in zone 1 and 2 are connected to the terminals labelled 17 and 17 .
ES
• External signal for heating/cooling switch in zone 3 is connected to the terminals labelled 18 and 18 .
FI
DE
EE
See section 5 Install Uponor Smatrix Move PRO controller for more information.
FR
See also the wiring diagram in the end of the manual.
HR Example specific system settings in startup wizard Operation Mode: Standard
HU
System Type: 4 Pipe Indoor Cooling Only: No
IT
Enable Zone # (# = 1, 2, and 3): Yes Zone setup: Stand Alone Control, or Smatrix Base PRO
LT
Z1&2 Operation Mode: Heating And Cooling Z3 Operation Mode: Heating And Cooling
LV
See section 4.3 Installation examples > Zone setup for more zone specific startup wizard settings.
NL
See section 5.13 Startup wizard for more information. See section 7.10 Settings for more information.
NO PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
17
UK H eating / cooling 4- pipe
system together with
domestic hot water production
CZ
3
DE
W arning ! Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
A
B
Base PRO
DK
2
EE
This connection example shows an Uponor Smatrix Move PRO Controller (with the heating/cooling application installed) regulating three different zones in a 4-pipe system.
ES
1
FI FR
A
• Zone 1 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling.
B
• Zone 2 is setup for Domestic Hot Water production. Base PRO
HR
3
1
LT C
LV
• Zone 3 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling. The supply is routed to zone 1 and 3 from the heating and cooling sources using four diverting valves, switching the zones between heating and cooling independently. Zone 2 is installed close to the heat source in permanent heating mode. This enables zones 2 to be operated independently from zones 1 and 3 (regardless if they are in heating or cooling mode).
HU IT
N OT E ! These are outline diagrams. Real systems must be installed according to applicable norms and regulations.
The zone temperatures are regulated using a wide range of sensors, by using either a three-way mixing valve (B) or a two-way valve together with a heat exchanger (A), set temperatures (setpoints), and other zone specific parameter settings.
NL NO PL PT RO RU SE SK 18
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Example specific electrical connections • The zone 1 supply and return line diverting valves are connected to the terminals labelled 24 and 26. Note! An external relay may be needed when connecting two diverting valves to the connection terminals.
CZ DE
• The zone 3 supply and return line diverting valves are connected to the terminals labelled 25 and 26. Note! An external relay may be needed when connecting two diverting valves to the connection terminals.
DK EE
• External signal for heating/cooling switch in zone 1 is connected to the terminals labelled 17 and 17 .
ES
• External signal for heating/cooling switch in zone 3 is connected to the terminals labelled 18 and 18 .
FI
See section 5 Install Uponor Smatrix Move PRO controller for more information.
FR
See also the wiring diagram in the end of the manual. Example specific system settings in startup wizard
HR
Operation Mode: Standard System Type: 4 Pipe
HU
Indoor Cooling Only: No Enable Zone # (# = 1, 2, and 3): Yes
IT
Zone setup (zone 1): Stand Alone Control, or Smatrix Base PRO Z1&2 Operation Mode: Heating And Cooling
LT
Zone setup (zone 2): Domestic Hot Water Zone setup (zone 3): Stand Alone Control, or Smatrix Base PRO
LV
Z3 Operation Mode: Heating And Cooling
NL
See section 4.3 Installation examples > Zone setup for more zone specific startup wizard settings.
NO
See section 5.13 Startup wizard for more information. See section 7.10 Settings for more information.
PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
19
UK Z one
setup
The zones can be setup as:
CZ
• Stand Alone Control • Smatrix Base PRO
DE
• Domestic Hot Water • Meltaway
DK
Stand Alone Control
The zone can switch between heating and cooling using one of the following functions (set in the startup wizard): • Indoor and Outdoor uses the indoor and outdoor temperatures to switch the zones between heating and cooling. • Supply Water Temp. uses the supply water temperature to switch the zones between heating and cooling. • Contact Input uses an external signal to switch the zones between heating and cooling.
EE
• Force Heating sets the zones in forced heating.
ES
• Force Cooling sets the zone in forced cooling. The outdoor temperature sensor is not needed if the Move PRO controller is integrated with an Uponor Smatrix Base PRO system (with outdoor temperature sensor).
FI FR
See section 5 Install Uponor Smatrix Move PRO controller for more information.
HR
If the zone (1 through 3) is setup as Stand Alone Control, basic control of the zone is enabled. The following components are required or optional for heating/cooling operation in the zone (regulate the zone temperature using a mixing valve).
HU IT
Required: • Supply sensor S-152 • Room sensor S-155 (optional for heating only)
LT
• Humidity sensor S-157 (optional for heating only) Optional:
LV
• Condensation sensor S-159 • Heating/Cooling Switch
NL
• Dehumidifier The optional dehumidifier can be connected to the controller instead of the circulation pump. If that option is chosen, then the circulation pump cannot be controlled by the Move PRO controller.
NO PL
SYSTEM SETTINGS IN STARTUP WIZARD Enable Zone # (# = 1, 2, or 3): Yes Zone setup: Stand Alone Control Z1&2 (or Z3) Operation Mode (4-pipe system only): Only Heating, Only Cooling, or Heating And Cooling Heating Mode: Outdoor (outdoor temperature sensor only) Outdoor + Indoor comp. (outdoor temperature sensor with optional room temperature sensor) Z1&2 (or Z3) HC Switchover (4-pipe system only): Indoor and Outdoor, Supply Water Temp., Contact Input, Force Heating, or Force Cooling Dehumidifier Control: Disable/Enable Condensation Sensor: No/Yes Other zone settings can be found in the menu system Settings > Zone # Setting (where # is the zone where Stand Alone Control is activated). See section 5.13 Startup wizard for more information.
PT
See section 7.10 Settings for more information.
RO RU SE SK 20
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Smatrix Base PRO
The optional dehumidifier can be connected to the controller instead of the circulation pump. If that option is chosen, then the circulation pump cannot be controlled by the Move PRO controller.
CZ DE
C aution ! PRO PRO
D
The integration is activated when a zone is setup as Smatrix Base PRO (requires that the wiring is done and that Supply Water Controller is activated in the Integration menu in the Base PRO interface) in the startup wizard on the Move PRO controller.
DK EE
See section 5 Install Uponor Smatrix Move PRO controller for more information.
ES
SYSTEM SETTINGS IN STARTUP WIZARD If the zone (1 through 3) is setup as Smatrix Base PRO, individual room control in the zone is enabled.
Enable Zone # (# = 1, 2, or 3): Yes
The controller is connected to an Uponor Smatrix Base PRO system, via the Smatrix Base PRO bus, utilising its components to regulate the zone temperature.
Z1&2 (or Z3) Operation Mode (4-pipe system only): Only Heating, Only Cooling, or Heating And Cooling
The following components are required or optional for heating/cooling operation in the zone (regulate the zone temperature using a mixing valve).
Heating Mode: Outdoor (outdoor temperature sensor only) Outdoor + Indoor comp. (outdoor temperature sensor with optional room temperature sensor)
Required: • Supply sensor S-152 • Smatrix Base PRO system Optional: • Condensation sensor S-159 • Heating/Cooling Switch • Dehumidifier The outdoor temperature sensor is connected to the Base PRO system via a thermostat, registered as a system device. The thermostat is preferably placed in a non-public area such as a technical room. Heating/cooling mode is set from the Smatrix Base PRO system.
FI
Zone setup: Smatrix Base PRO
FR HR HU
Smatrix Indoor Temperature: Worst Case (the measured worst case temperature in the zone), or Average (the calculated average temperature in the zone).
IT
Z1&2 (or Z3) HC Switchover (4-pipe system only): Indoor and Outdoor, Supply Water Temp., Contact Input, Force Heating, or Force Cooling
LT LV
Dehumidifier Control: Disable/Enable Condensation Sensor: No/Yes
NL
Assign Controller to zone: Assign connected Smatrix Base PRO controllers to zones.
NO
Other zone settings can be found in the menu system Settings > Zone # Setting (where # is the zone where Smatrix Base PRO is activated).
PL
See section 5.13 Startup wizard for more information. See section 7.10 Settings for more information.
PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
21
UK Domestic Hot Water
Meltaway
CZ DE DK EE ES
If the zone is setup as Domestic Hot Water, hot water production is enabled in the zone.
FI
C aution !
FR
The Domestic Hot Water function requires a constant delivery of heating supply water, such as district heating.
HR
The following components are required for regulating the hot water temperature in the zone (regulate the supply temperature using a mixing valve). Required:
HU
• Supply sensor S-152 • Return sensor S-152
IT
N OT E ! If the zone is setup as Domesitc Hot Water without a return sensor, the zone will work with reduced functionality. Functions such as BoostPower and hot water recirculation requires a return sensor to work properly.
LT LV
See section 5 Install Uponor Smatrix Move PRO controller for more information.
NL
SYSTEM SETTINGS IN STARTUP WIZARD Enable Zone 2: Yes
NO
Zone setup: Domestic Hot Water Other zone settings can be found in the menu system Settings > Zone # Setting (where # is the zone where Domestic Hot Water is activated).
PL
See section 5.13 Startup wizard for more information.
PT
See section 7.10 Settings for more information.
RO
If the zone is setup as Meltaway, hot water production for snow melting (keeping large areas clear of snow) is enabled in the zone. The following components are required for snow melting hot water production in the zone (regulate the supply temperature using a mixing valve). Required: • Supply sensor S-152 • Return sensor S-152 • Primary return sensor S-152 (not shown in illustration) • Snow sensor S-158 used as ground temperature sensor • Snow sensor S-158 used as ground moisture sensor The outdoor temperature sensor is not needed if the Move PRO controller is integrated with an Uponor Smatrix Base PRO system (with outdoor temperature sensor). See section 5 Install Uponor Smatrix Move PRO controller for more information. SYSTEM SETTINGS IN STARTUP WIZARD Enable Zone 3: Yes Zone setup: Meltaway Other zone settings can be found in the menu system Settings > Zone # Setting (where # is the zone where Melt away is activated). N OT E ! When using a 3-way mixing valve (option B) a heat exchanger may be needed, creating a secondary loop where water mixed with antifreeze additives circulate. See section 5.13 Startup wizard for more information.
RU
See section 7.10 Settings for more information.
SE SK 22
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK
5 Install Uponor Smatrix Move PRO controller
CZ DE
5.1 Placement of controller
5.3 Attach stickers
Refer to the installation preparation guidelines (see section 4.2 Prepare for installation), and use the following guidelines when positioning the controller:
Attach the stickers from the application package to the controller.
DK EE
• Position the controller close to at least one of the actuators, preferably inside a cabinet. Check the position of the 230 V AC supply.
ES 4
4 5
5 6
6 7
7 8
8 9
9 10
10 11
11 12
12 13
13 14
14 15
15 16
16
18 17 18 17
FI
41
42
43
44
45
46
47
48
49
15VDC
3
50
51
52
GND
3
53
54
GND
2
12VDC IN
2
55
24VAC IN
1
• Check that connectors and switches are easily accessible.
1
1
• Check that the terminal cover can be easily removed from the controller.
56
FR
1
5.2 Select controller application
1
The controller is delivered with two packages containing applications for different use of the controller. The package contains a microSD card, electrical connection stickers, and an application diagram depicting installation examples.
HR
2 2
2
N
L
T 125
N 79
Select the package containing the heating and cooling application and discard the other one.
75
74 71
21
22
23
24
25
26
76
73
72
30
29
28
27
HU
mA
L
80
78
77
IT
oSD micr
1T L
L
Hz
56 55 49
77
3 48
N L
2
47 46
75
2 45
74
44
1
73
43
1 72 71
41 Base PRO
30 29
27 26
3
25 24
1/2
12 13
23
3B
BASE – BUS
A
22
Base
PRO
-
10 11 11 12
LV
21
PRO SMATRIX
5.4 Insert microSD card
7 8
2
6 7 3 4
1
2 3 1 2
microSD
Base PRO
Base PRO
1
1
1
microSD
microSD
2
3 4
4 5
4 5
5 6
5 6
6 7
3
7 8
8 9
8 9
9
9
10
28
1/2
3
25
13 14 14 15 15 16 16 17 17 18 18
3
26
44
72
42
71
41
30
Base PRO
29 28 27 26
3/4
4
25
13 14 14 15 15 16 16 17 17 18 18
3
24
12 13
23
4B A
22 21
BASE – BUS
42
1
1
43
73
IIN ≤ 6A
Base
76
76
2
46
75
2 45
74 N L
!
PRO
N L
49
3
77
3 48
N L
IIN ≤ 6A
47
!
-
N
N
V± 50/60 10%
54 53
230
80
52
79
51
3
50
78
IIN ≤ 1A
78
!
PRO SMATRIX
IIN ≤ 6A
10 10 11 11 12
!
2 3
IIN ≤ 6A
1 2
!
microSD
mA 125
mA
L
4
79
51
4 N L
N L
Hz
55
L
N
N
V± 50/60 10%
54
230
53
N L
80
IIN ≤ 1A
52
!
50
GND 12VDC IN GND
15VDC
IIN ≤ 1A
GND 12VDC IN GND
15VDC
24VAC IN
!
56
125
1T
2
2
LT 24VAC IN
Insert the microSD card from the application package in to the controller.
NL 2
N
L
T 125
N 79 77 74 71
21
micro
22
23
24
25
26
27
28
29
72
75
mA
NO
L
80
78
76
73
30
PL
SD
PT
microSD
RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
23
UK
5.5 Attach controller to the wall
5.6 Terminal cover
CZ
DIN
DE
Attach the controller to a DIN rail in a cabinet (recommended), or to a DIN rail attached to a wall using screws and wall plugs.
The illustration below shows how to remove and reattach the terminal cover.
DK
The figure below shows how to attach the controller using a DIN rail.
rail
2
N
T 125
N 79 77 74 71
21
EE
L
22
23
24
25
26
27
28
29
72
75
mA
L
80
78
76
73
30
SD
micro
ES
A 5.7 Connect sensors to controller
B
FI
The following sensors can be connected to the system: • Uponor Smatrix Outdoor S-1XX
FR
A
2
HR
• Uponor Smatrix Move Sensor Supply/Return S-152
B
• Uponor Smatrix Move PRO Sensor Room S-155 • Uponor Smatrix Move PRO Sensor Humidity S-157
1
HU
3
3
2 1
C aution !
LT
Make sure the controller cannot slide off the DIN rail if mounting it in any other position than horizontal.
LV NL
• Uponor Smatrix Condensation Set S-159
W arning !
CLICK
IT
• Uponor Smatrix Move PRO Sensor Snow S-158
Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
C aution ! Make sure shielded cables are used when connecting sensors to the controller to prevent interference from power sources and cables.
NO PL PT RO RU SE SK 24
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK O utdoor
Connect outdoor sensor to controller
sensor
The outdoor sensor is mandatory and must always be installed. Either directly to the Move PRO controller or via an integrated Uponor Smatrix Base PRO controller. If a Base PRO controller is integrated to the system, it is a requirement to connect the outdoor temperature sensor to the Base PRO controller via a thermostat, registered as a system device. The thermostat is preferably placed in a non-public area such as a technical room.
The illustration below shows the outdoor sensor connected to the controller.
CZ DE
S-1XX DK #
Placement of outdoor sensor
16
Refer to the installation preparation guidelines (see section 4.2 Prepare for installation), and use the following guidelines when positioning the outdoor sensor: 1. Attach the outdoor sensor to the north side of the building where it is unlikely to be exposed to direct sunlight. 2. Ensure that the outdoor sensor is placed away from doors, windows, or air outlets.
X-159
ES
To connect an outdoor sensor to the controller:
FI
1. Ensure that the power is disconnected from the controller.
FR
2. Remove the terminal cover. See section 5.6 Terminal cover for more information. 3. Study the wiring diagram to locate the connection terminal positions.
N W
EE
E S
HR
4. Connect the wires from the outdoor sensor to terminals 16 and 16 on the controller.
HU
5. Tighten the screws fixing the wires to the connector.
IT LT LV NL NO PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
25
UK S upply
R eturn
sensor
The supply sensor needs to be installed in all zones.
CZ
sensor
The return sensor only needs to be installed in zones setup as Meltaway or DHW (domestic hot water).
Connect supply sensor to controller The illustration below shows supply sensors connected to the controller.
DE
1
DK
2
3
S-152
Connect return sensor to controller The illustration below shows return sensors connected to the controller.
2
3
6
10
S-152
EE #
ES
1
FI
5
9
#
X-159 X-159
FR
To connect a supply sensor to the controller: 1. Study the wiring diagram to locate the connection terminal positions.
HR
2. Ensure that the power is disconnected from the controller.
HU
3. Remove the terminal cover. See section 5.6 Terminal cover for more information.
IT
4. Connect the wires from the supply sensor to the controller.
LT LV
• ZONE 1: Terminals 1 and 1 .
• ZONE 2: Terminals 5 and 5 .
• ZONE 3: Terminals 9 and 9 .
5. Tighten the screws fixing the wires to the connector.
To connect a return sensor to the controller: 1. Study the wiring diagram to locate the connection terminal positions. 2. Ensure that the power is disconnected from the controller. 3. Remove the terminal cover. See section 5.6 Terminal cover for more information. 4. Connect the wires from the return sensor to the controller.
• ZONE 2: Terminals 6 and 6 .
• ZONE 3: Terminals 10 and 10 .
5. Tighten the screws fixing the wires to the connector.
NL NO PL PT RO RU SE SK 26
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK R oom
Label room sensor
sensor
The room sensor only needs to be installed in zones setup as Stand Alone, with Heating Mode setup as Outdoor + Indoor comp.. N OT E ! The sensor is required in zones where heating/cooling (or cooling only) is enabled. Otherwise (heating only) it is only optional. Placement of room sensor
Label the room sensors, where suitable, with the zone numbers they are to control, for example, #02, #03.
CZ
Attach room sensor to the wall
DE
The illustration below shows room sensor mounting hole positions and how to attach it to the wall using screws and wall plugs. 60
DK
mm
EE
Refer to the installation preparation guidelines (see section 4.2 Prepare for installation), and use the following guidelines when positioning the room sensors:
ES
1. Select an indoor wall and a position 1.3 m to 1.5 m above the floor.
FI
2. Ensure that the room sensor is away from direct solar radiation. 3. Ensure that the room sensor will not be heated through the wall by sunshine.
FR
4. Ensure that the room sensor is away from any source of heat, for example television set, electronic equipment, fireplace, spotlights, and so on.
HR
5. Ensure that the room sensor is away from any source of humidity and water splashes (IP20).
HU IT LT
1.3–1.5 m LV NL NO PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
27
UK CZ
Connect room sensor to controller
To connect a room sensor to the controller:
The illustration below shows room sensors connected to the controller.
1. Study the wiring diagram to locate the connection terminal positions.
1
DE
2
S-155
3
2. Ensure that the power is disconnected from the controller. 3. Remove the terminal cover. See section 5.6 Terminal cover for more information.
DK
4. Route the wires through points A or B. #
EE
2
ES
6
5. Connect the wires from the room sensor to the controller.
10
X-159
FI
1
FR HR
A
• ZONE 1: Terminals 2 and 2 .
• ZONE 2: Terminals 6 and 6 .
• ZONE 3: Terminals 10 and 10 .
6. Tighten the screws fixing the wires to the connector.
S-155
B
HU C aution !
IT
Do not change the jumper setting, otherwise the function of the sensor will be compromised.
LT
Default setting:
LV NL NO PL PT RO RU SE SK 28
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK H umidity
sensor
The humidity sensor only needs to be installed in zones setup as Stand Alone. N OT E ! The sensor is required in zones where heating/cooling (or cooling only) is enabled. Placement of humidity sensor Refer to the installation preparation guidelines (see section 4.2 Prepare for installation), and use the following guidelines when positioning the humidity sensors:
Label humidity sensor Label the humidity sensors, where suitable, with the zone numbers they are to control, for example, #02, #03.
The illustration below shows humidity sensor mounting hole positions and how to attach it to the wall using screws and wall plugs. 60
3
2. Ensure that the humidity sensor is away from direct solar radiation.
DK EE
mm
A
ES
10 V 0V +24 V
3. Ensure that the humidity sensor will not be heated through the wall by sunshine.
5. Ensure that the humidity sensor is away from any source of humidity and water splashes (IP30).
DE
Attach humidity sensor to the wall
1. Select an indoor wall and a position 1.3 m to 1.5 m above the floor.
4. Ensure that the humidity sensor is away from any source of heat, for example television set, electronic equipment, fireplace, spotlights, and so on.
CZ
1
FI
2
FR
60 mm
HR 50 mm
HU IT LT
1.3–1.5 m
LV NL NO PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
29
UK CZ
Connect humidity sensor to controller
To connect a humidity sensor to the controller:
The illustrations below shows humidity sensors connected to the controller.
1. Study the wiring diagram to locate the connection terminal positions.
1
DE
2
S-157
3 10 V 0V +24 V
10 V 0V +24 V
10 V 0V +24 V
3. Remove the terminal cover. See section 5.6 Terminal cover for more information.
DK
4. Route the wires through one of the points A. See Attach humidity sensor to the wall for more information.
#
EE
4
8
2. Ensure that the power is disconnected from the controller.
12
5. Connect the wires from the humidity sensor to the controller.
ES
X-159
FI 1
2
S-157
3
10 V 0V +24 V 10 V 0V +24 V 10 V 0V +24 V
FR HR
41
44
47
HU
ZONE 1:
• Control signal wires to terminals 4 and 4 .
• 24 V AC wire to terminal 41
ZONE 2:
• Control signal wires to terminals 8 and 8 .
• 24 V AC wire to terminal 44
ZONE 3:
• Control signal wires to terminals 12 and 12 .
• 24 V AC wire to terminal 47
6. Tighten the screws fixing the wires to the connector.
IT 10 V 0V
LT
+24 V
S-157
24 VAC
#
LV NL NO PL PT RO RU SE SK 30
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK S now
sensor
The snow sensor only needs to be installed in zones setup as Meltaway.
CZ
C aution !
DE
Two snow sensors are needed to guarantee the Meltaway function. One of them is used as a ground temperature sensor and the other one as a ground moisture sensor. When installing the snow and ice sensors in a zone a primary return sensor, and secondary supply and return temperature sensors are needed. See section 5.7 Connect sensors to controller for more information.
≥ 0,2 m
DK
≥ 0,1 m
EE m 3m
≤2
≤2
00m
ES FI
Placement of the snow sensor sensors The following requirements must be met when installing the snow sensor.
FR
• The snow sensor must be installed within the area to be heated. • The snow sensor must be installed levelled horizontally and embedded in a hard surface (such as concrete or asphalt). • The snow sensor must not protude from the surface. It can be recessed a few millimeters into the surface to allow draining melt water to collect on the sensor surface. Not too deep though. • The snow sensor must be installed in an open unsheltered position away from walls and exposed to the elements (eg. not close to walls, fan outlets, or other sources which can affect the sensors).
HR
A
HU IT
B LT LV
• If the snow sensor is to be used as a ground temperature sensor it must not be installed closer than 20 cm to the heating loop.
NL
• If the snow sensor is to be used as a ground moisture sensor it must not be installed closer than 10 cm to the heating loop.
NO
• If the ground is not horizontal, then the ground moisture sensor must be installer lower than the ground temperature sensor.
PL
• Use a cable conduit with a diameter of up to 23 mm when routing the sensor cables.
PT
• The sensor cable (supplied with 25 m) can be extended to up to 200 m using standard installation cable (6x1.5 mm2). The total resistance of the cable must be less than 10 ohm.
RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
31
UK Install snow sensor into the ground surface The following illustrations show how to install the snow sensor into the ground surface. 1. Create a notch for the cable conduit (maximum diameter of 23 mm). It is recommended to use a cable conduit equipped with a cord, in order to make it easier to pull the cable through when installed.
CZ DE DK
5. Remove the wood plug when the concrete/asphalt has cured.
EE 6. Ensure that the sunsor tube is clean.
ES m
3m
FI
≤2
FR
2. Insert the sensor tube in the hole where the sensor is to be installed. Make sure it is securely embedded in relation to the expected surface load.
HR
7. Insert the sensor cable and route it into the cable conduit. Ensure that the cable is not damaged on any sharp edges.
HU IT LT 3. Insert the supplied wood plug into the sensor tube before applying the concrete/asphalt.
LV NL
8. Place the snow sensor into the tube. Make sure that the cable easily fits in the hole in the bottom.
NO
Secure the sensor (in the middle of the sensor) with the supplied screw.
PL PT 4. Apply the concrete/asphalt.
RO RU SE SK 32
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Connect snow sensor, used as ground temperature sensor, to controller
Connect snow sensor, used as ground moisture sensor, to controller.
The illustration below shows the snow sensor, used as ground temperature sensor, connected to the controller.
The illustration below shows the snow sensor, used as ground moisture sensor, connected to the controller.
S-158
S-158
3
CZ DE
3
DK EE #
#
14
13
ES
X-159
X-159
FI
To connect a snow sensor to the controller:
FR
25 26
1. Study the wiring diagram to locate the connection terminal positions.
S-158 HR
2. Ensure that the power is disconnected from the controller. 3. Remove the terminal cover. See section 5.6 Terminal cover for more information. 4. Connect the wires from the snow sensor to the controller.
ZONE 3:
• Pink wire to terminal 13
• Grey wire to terminal 13
5. Tighten the screws fixing the wires to the connectors.
3
HU
To connect a snow sensor to the controller: 1. Study the wiring diagram to locate the connection terminal positions.
IT
2. Ensure that the power is disconnected from the controller.
LT
3. Remove the terminal cover. See section 5.6 Terminal cover for more information.
LV
4. Connect the wires from the snow sensor to the controller.
ZONE 3:
• White wire to terminal 14
• Yellow wire to terminal 14
• Brown wire to terminal 25
• Green wire to terminal 26
NL NO PL
5. Tighten the screws fixing the wires to the connectors.
PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
33
UK P rimary
C ondensation
return sensor
The primary return sensor may only need to be installed in zones setup as Meltaway.
CZ
3
The condensation kit consist of a relative humidity sensor connected to a converter, which in turn is connected to the Move PRO controller. The sensor measures the relative humidity of the air flowing through its capilary tubes and translates it to electrical resistance. If the electrical resistance drops to about 8 MΩ (about 80-85 % relative humidity) the converter opens the signal to the Move PRO controller, which shuts of cooling. When the electrical resistance reaches approximately 16 MΩ the signal to the controller is closed and cooling is allowed again.
15
Cut capilary tubes on the condensation sensor
Connect primary return sensor to controller
DE
The illustration below shows a primary return sensor connected to the controller.
DK
S-152
EE ES
sensor kit
The condensation sensor kit is optional for zones setup as Stand Alone or Smatrix Base PRO.
#
FI X-159 FR
The illustration below shows the capilary tubes beeing cut to allow air flow through the sensor (to measure relative humidity).
To connect a primary return sensor to the controller: 1. Study the wiring diagram to locate the connection terminal positions.
HR
2. Ensure that the power is disconnected from the controller.
HU
3. Remove the terminal cover. See section 5.6 Terminal cover for more information.
IT
4. Connect the wires from the primary return sensor to the controller.
LT
• ZONE 3: Terminals 15 and 15 .
Attach condensation sensor to the supply pipe The illustration below shows the condensation sensor attached to the supply pipe using cable straps.
5. Tighten the screws fixing the wires to the connector.
LV
S econdary
supply and return sensors
The secondary supply or return sensor is connected as a standard supply or return sensor.
NL
See section 5.7 Connect sensors to controller > Supply sensor for more information.
NO
See section 5.7 Connect sensors to controller > Return sensor for more information.
PL PT RO RU SE SK 34
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Attach converter to DIN rail
C aution !
The illustration below shows the attached to a DIN-rail.
Maximum lenght of the sensor cable is 10 meters.
CZ
To connect a condensation sensor kit to the controller:
DE
1. Study the wiring diagram to locate the connection terminal positions.
B 2
A 1
2. Ensure that the power is disconnected from the controller.
A B
3. Remove the terminal cover. See section 5.6 Terminal cover for more information.
EE
3
4. Connect the condensation sensor to terminals 1 and 2 on the the converter.
ES
3
2
CLICK
1 The illustration below shows a condensation sensor kit connected to the controller.
2 24 V AC
3
24 V AC
Note! Use one condensation sensor kit (converter and sensor) per zone where it is to be used.
FI
5. Connect the the converter to the controller.
Connect condensation sensor kit to controller
1
DK
S-159
ZONE 1:
• Converter terminal 3 to controller terminal 3.
• Converter terminal 4 to controller terminal 3
ZONE 2:
• Converter terminal 3 to controller terminal 7.
• Converter terminal 4 to controller terminal 7
FR HR HU
24 V AC
7 6 24V~
7 6 24V~
7 6 24V~
ZONE 3:
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
• Converter terminal 3 to controller terminal 11.
• Converter terminal 4 to controller terminal 11
IT LT
6. Connect the converter to 24 V AC. # 3
7
11
X-159
• L to converter terminal 6.
• N to converter terminal 7.
LV
Note! Use one condensation sensor kit (converter and sensor) per zone where it is to be used.
NL
7. Tighten the screws fixing the wires to the connectors.
NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
35
UK
5.8 Connect external signal for heating/cooling switch to the controller
5.9 Connect mixing valve actuators to the controller
DE
The external signal for heating/cooling switch is optional for zones setup as Stand Alone.
The illustration below shows actuators connected to the controller.
DK
A total of two external signals for heating/cooling switch can be connected to the controller. One external signal controls zone 1 and/or zone 2, depending on zone setup. The other one controls zone 3.
CZ
EE
The controller can control up to 3 different zones.
1 -
2 +
-
3 +
-
+
The illustration below shows external signals for heating/cooling switch connected to the controller.
ES
1&2
42 43
3
45 46
48 49
X-159
FI
W arning !
FR
#
Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
17 18
HR X-159
N OT E ! Only the control signals from the vavle acutators are connected to the Move PRO controller. Power must be obtained from an external source.
HU To connect an external signal for heating/cooling switch to the controller:
IT
1. Ensure that the power is disconnected from the controller. 2. Remove the terminal cover. See section 5.6 Terminal cover for more information.
LT LV
3. Study the wiring diagram to locate the connection terminal positions.
NL
4. Connect the wires for heating/cooling switch to the controller.
NO
• ZONE 1&2: Terminals 17 and 17 .
• ZONE 3: Terminals 18 and 18 .
5. Tighten the screws fixing the wires to the connector.
To connect valve actuators to the controller: 1. Ensure that the power is disconnected from both the controller and the actuator. 2. Remove the terminal cover. See section 5.6 Terminal cover for more information. 3. Study the wiring diagram to locate the connection terminal positions. 4. Connect the wires from the actuator to the controller.
ZONE 1: • 0...10 V wire to terminal 43.
• Ground wire ( ) to terminal 42.
ZONE 2: • 0...10 V wire to terminal 46.
• Ground wire ( ) to terminal 45.
RO
ZONE 3: • 0...10 V wire to terminal 49.
RU
• Ground wire ( ) to terminal 48.
PL PT
5. Tighten the screws fixing the wires to the connector.
SE SK 36
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK
5.10 Connect diverting valve actuators to the controller
W arning ! Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
The controller can control up to 3 different zones. The illustration below shows actuators in a 2 pipe setup connected to the controller.
CZ DE
N OT E ! Only the control signals from the vavle acutators are connected to the Move PRO controller. Power must be obtained from an external source.
X-159
24 25 26
DK EE
To connect valve actuators or external relays to the controller:
ES
1. Ensure that the power is disconnected from both the controller and the actuator.
3 1&2
FI
2. Remove the terminal cover. See section 5.6 Terminal cover for more information.
C aution !
3. Study the wiring diagram to locate the connection terminal positions.
An external relay may be needed when connecting two diverting valves to the connection terminals (24 V AC output). The illustration below shows diverting valves in a 4 pipe setup connected to the controller using external relays.
X-159
24 25 26
3
FR
4. Connect the wires from the actuator (or relay) to the controller.
ZONE 1&2 (4 pipe)/Supply line (2 pipe):
• 24 V AC wire to terminal 24.
• Ground wire ( ) to terminal 26.
ZONE 3 (4 pipe)/Return line (2 pipe):
• 24 V AC wire to terminal 25.
• Ground wire ( ) to terminal 26.
HR HU IT LT
5. Tighten the screws fixing the wires to the connector.
LV NL 1&2
NO PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
37
UK
5.11 Connect circulation pumps to the controller
CZ
W arning ! Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
The controller can control either a circulation pump or a dehumidifier in up to 3 different zones.
DE
The illustration below shows circulation pumps connected to the controller.
DK
1. Ensure that the power is disconnected from the controller.
X-159
2. Remove the terminal cover. See section 5.6 Terminal cover for more information.
EE 75 76
72 73
To connect circulation pumps or external relays to the controller:
77 78
3. Study the wiring diagram to locate the connection terminal positions.
ES L N
L N
24 V AC / 230V AC
L N
FI 1
FR
2
3
C aution ! The terminals are limited to 1A. An external relay might be needed.
HR
The illustration below shows a circulation pump connected to the controller using external relays.
HU
X-159
IT LT
L
LV
N N L
NL
24 V AC / 230V AC
4. Connect power (max 230VAC) to the circulation pumps/external relays via connection terminals on the controller. Caution! The terminals are limited to 1A. An external relay might be needed.
ZONE 1:
• Power (L) from the circulation pump to terminal 72.
• External 24 or 230 V A C (L) to terminal 73.
ZONE 2:
• Power (L) from the circulation pump to terminal 75.
• External 24 or 230 VAC (L) to terminal 76.
ZONE 3:
• Power (L) from the circulation pump to terminal 77.
• External 24 or 230 VAC (L) to terminal 78.
5. Connect the common wire (N) from the circulation pumps to external connection. 6. Tighten the screws fixing the wires to the connector.
NO PL PT RO RU SE SK 38
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK
5.12 Connect a dehumidifier to the controller
W arning ! Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
The controller can control either a dehumidifier or a circulation pump in up to 3 different zones. The illustration below shows dehumidifiers connected to the controller.
CZ DE
To connect dehumidifiers or external relays to the controller:
DK
1. Ensure that the power is disconnected from the controller.
X-159
75 76
72 73
L N
2. Remove the terminal cover. See section 5.6 Terminal cover for more information.
77 78
L N
24 V AC / 230V AC
L N
3. Study the wiring diagram to locate the connection terminal positions.
2
3
C aution ! The terminals are limited to 1A. An external relay might be needed. The illustration below shows dehumidifiers connected to the controller via dry contact.
ES
4. Connect the dehumidifier to the controller.
1
EE
FI
4.1 Connect power (max 230VAC) to the dehumidifiers/external relays via connection terminals on the controller. Caution! The terminals are limited to 1A. An external relay might be needed.
FR
ZONE 1: • Power (L) from the dehumidifier to terminal 72.
HR
HU
• External 24 or 230 VAC (L) to terminal 73.
ZONE 2: • Power (L) from the dehumidifier to terminal 75.
X-159
72 73
75 76
77 78
IT
• External 24 or 230 VAC (L) to terminal 76.
LT
ZONE 3: • Power (L) from the dehumidifier to terminal 77.
1
2
3
The illustration below shows a dehumidifier connected to the controller using external relays.
X-159
LV
• External 24 or 230 VAC (L) to terminal 78.
4.2 Connect the dry contact in the dehumidifiers to the connection terminals on the controller.
NL
ZONE 1: • Dry contact to terminals 72-73.
NO
ZONE 2: • Dry contact to terminals 75-76.
PL
ZONE 3: • Dry contact to terminals 77-78. L N
24 V AC / 230V AC
N L
PT
5. Connect the common wire (N) from the dehumidifiers to external connection. 6. Tighten the screws fixing the wires to the connector.
RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
39
UK CZ DE DK
5.13 Connect Uponor Smatrix Base PRO controller
4. Study the wiring diagrams of both controllers to locate the connection terminal positions.
The controller can be connected to an Uponor Smatrix Base PRO system bus for integration with Base PRO controllers and thermostats.
5. Connect the wires from the Base PRO controller to the Move PRO controller.
Uponor Smatrix Base PRO:
The illustration below shows the Uponor Smatrix Base Pro system bus connected to the controller.
• Communication wire to system bus terminal A, B and -.
Uponor Smatrix Move PRO:
• Communication wire to system bus terminal 21 (-), 22 (A) and 23 (B).
X-159 EE - A B 21 22 23
ES
- A B 21 22 23
FI
6. Tighten the screws fixing the wires to the connector. Enable the Move PRO controller in the Smatrix Base PRO interface I-147: 7. Go to the Integration menu (Main menu > Integration).
FR
A B - A B -
A B - A B -
X-147
HR
8. Press Supply Water Controller: Disable. 9. Press Enable to activate communication between the interface and the Move PRO controller. 10. Assign controllers at the end of the Startup Wizard in the Move PRO controller. Connected Smatrix Base PRO controllers will be shown in a list automatically. See section 5.14 Startup wizard for more information.
HU IT
W arning ! Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
LT LV
To connect an Uponor Smatrix Base PRO system bus to the controller:
NL
1. Ensure that the power is disconnected from all controllers.
NO
2. Remove the terminal cover on the Move PRO controller. See section 5.6 Terminal cover for more information.
5.14 Connect Modbus RTU interface The controller can be connected and integrated to a building management system (BMS) through a Modbus-RTU interface over RS-232. See separate documentation for more information about BMS integration.
3. Remove the cover on (one of) the Base PRO controllers. See Uponor Smatrix Base PRO documentation for more information.
PL PT RO RU SE SK 40
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK
5.15 Connect the controller to AC power
5.17 Startup wizard
The illustration below shows the the controller connected to AC power.
The controller initiates a startup wizard the first time it is started, or after a factory reset. This wizard is designed to configure the controller zones. Further settings can be done in the Settings menu.
X-159
N L
CZ DE
It can also be started manually through the menu system, Settings > Installer Settings > Restart wizard.
DK
N OT E ! The display on the controller can start flashing when powered on. This is completely normal and the regular operation will continue shortly after.
N L 230 V 50 Hz
EE ES
C aution !
W arning !
FI
At least one zone must be enabled when setting up the controller. Otherwise a configuration error will appear and the startup wizard is restarted.
Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician. To connect the controller to AC power:
N avigating
1. Check that all wiring is complete and correct:
Select/change
• Sensors • Valve actuators • Circulation pump
Turn the control wheel to select an option, or to change a parameter setting.
FR
the startup wizard
HR HU
2. Connect the 230 V AC power cable to connection terminals N (blue) and L (brown).
IT
3. Ensure that all terminal covers are attached correctly.
LT
4. Connect the power cable to a 230 V AC wall socket, or if required by local regulations, to a junction box.
LV
5.16 Alternate power inputs The controller has connection terminals for alternate power inputs (connection terminals 52 – 56).
C aution ! Do not use these input terminals, unless instructed to by Uponor technical support.
NL Confirm
NO
Press the control wheel to confirm a selection or parameter setting.
PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
41
UK CZ
1. Set language
4. Select Operation Mode
Select operation mode of the controller.
• Select Standard to continue setting up the controller for heating/cooling operation.
• Select Pre Heating to enable pre heating operation mode in the controller.
DE
Select the language which is to be used in the controllers menu system. Language English Deutsch Espanol Swedish
DK
See section 5.17 Pre heating concrete slab (DIN 1264-4) for more information.
2. Set the time
EE
Set the time of the system, starting with the hours.
Time
Standard Pre Heating
Enter the hours
12:34
ES
hh:mm
FI
Time Enter the minutes
12:34 hh:mm
FR
5. System Type
Select system type, 2 Pipe or 4 Pipe hydraulic delivery system.
• 2 Pipe means that all zones setup as Stand Alone Control or Smatrix Base PRO switches between heating and cooling at the same time.
• 4 Pipe means that zones 1 and 2, and zone 3, switches between heating and cooling independently from each other.
Individual zones can still be setup as Domestic Hot Water or Meltaway if needed. Those zones will not be affected by this setting, as long as their supply pipes are placed before the heating/cooling diverting valves..
3. Set the date HR
Set the date of the system, starting with the day. Date Enter the day
Tue 01.06.2016
HU IT
Date Enter the month
Tue 01.06.2016
LT
LV
System Type 2 Pipe 4 Pipe
Date Enter the year
Tue 01.06.2016
6. Indoor Cooling Only
NL
Operation Mode
This setting is only shown if 2 Pipe is selected in the System Type menu.
Select Yes to enable cooling only (No enables heating/cooling) in the system.
NO
PL PT
Individual zones can still be setup as Domestic Hot Water or Meltaway if needed. Those zones will not be affected by this setting, as long as their supply pipes are placed before the heating/cooling diverting valves.. Indoor Cooling Only No Yes
RO RU SE SK 42
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK 7. Enable Zone 1 7.1 Select Yes to enable zone 1 in the controller.
Enable Zone 1 No Yes
7.2 Select the setup of the zone. Stand Alone Control only uses the sensors and components connected to the controller. Smatrix Base PRO uses a connected Uponor Smatrix Base PRO system.
Zone Setup Stand Alone Control Smatrix Base PRO
7.3 Select operation mode of the zone. The setting affects both zone 1 and 2, if the system is installed and setup accordingly.
This setting is only shown if 4 pipe is selected in the System Type menu. Z1&2 Operation Mode Only Heating Only Cooling Heating And Cooling
7.4 Select heating mode. Outdoor only uses an outdoor sensor, and Outdoor + Indoor comp. also uses a room sensor to calculate the supply temperature. The sensor/sensors are connected to either the Move PRO controller (Stand Alone Control) or to a connected Base PRO controller (Smatrix Base PRO).
See section 5.7 Connect sensors to controller > Outdoor sensor for more information Heating Mode
7.5 Select which indoor temperature data in the Smatrix Base PRO system to use when calculating the supply temperature.
CZ
• Worst Case uses the room temperature from the room (only rooms with a heating demand) with the highest setpoint value (heating mode), or with the highest measured relative humidity value (cooling), in the zone.
DE DK
• Average calculates,only in heating mode, the average from all connected room thermostats in the zone (selected in the Smatrix Base PRO interface I-147).
EE
ES
This setting is only shown if Smatrix Base PRO is selected in the Zone Setup menu, and if Outdoor + Indoor comp. is selected in Heating Mode.
FI
Smatrix Indoor Temperature Worst Case Average
FR 7.6 Select how to switch zone 1 and 2 between heating and cooling.
HR
• Indoor and Outdoor uses the indoor and outdoor temperatures to switch the zone between heating and cooling.
HU
• Supply Water Temp. uses the supply water temperature to switch the zone between heating and cooling.
IT
• Contact Input uses an external signal to switch the zone between heating and cooling.
LT
• Force Heating sets the zone in forced heating.
• Force Cooling sets the zone in forced cooling.
LV
This setting is only shown if 4 pipe is selected in the System Type menu, and if Z1&2 Operation Mode is set to Heating And Cooling.
NL
Outdoor Outdoor + Indoor comp.
Z1&2 HC Switchover Indoor and Outdoor Supply Water Temp. Contact Input Force Heating
NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
43
UK 7.7 Set minimum and maximum allowed supply temperature when in heating and/or cooling mode.
CZ
DE
DK
The heating minimum and maximum supply temperatures can only be set if heating is allowed in the zone. The cooling minimum and maximum supply temperatures can only be set if cooling is allowed in the zone. Heating Min. Supply Temp.
EE
15˚C min: 5
ES
max: 70
Heating Max. Supply Temp.
8. Enable Zone 2 8.1 Select Yes to enable zone 2 in the controller.
No Yes
8.2 Select the setup of the zone. Stand Alone Control only uses the sensors and components connected to the controller. Smatrix Base PRO uses a connected Uponor Smatrix Base PRO system. Domestic Hot Water (DHW) regulates the supply temperature for DHW in the zone.
min: 15
max: 70
Cooling Min. Supply Temp.
FR
8.0˚C min: 5.0
HR
max: 25.0
8.3 Select operation mode of the zone. The setting affects both zone 1 and 2, if the system is installed and setup accordingly.
Cooling Max. Supply Temp.
25.0˚C
HU
min: 8.0
max: 40.0
7.8 Select Enable to enable dehumidifier control in the zone.
IT
LT
LV
Note! Enabling dehumidifier disables circulation pump control in the zone (except for zones setup as Smatrix Base PRO where the circulation pump is controlled by the Base PRO controller). Dehumidifier Control Disable Enable
NL 7.9 Select Yes if a condensation sensor is installed in the zone and connected to the controller.
NO
Condensation Sensor No Yes
PL
Zone Setup Stand Alone Control Smatrix Base PRO Domestic Hot Water
70˚C
FI
Enable Zone 2
This setting is only shown if 4 pipe is selected in the System Type menu, zone 1 is not enabled, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO. Z1&2 Operation Mode Only Heating Only Cooling Heating And Cooling
8.4 Select heating mode. Outdoor only uses an outdoor sensor, and Outdoor + Indoor comp. also uses an room sensor to calculate the supply temperature. The sensor/sensors are connected to either the Move PRO controller (Stand Alone Control) or to a connected Base PRO controller (Smatrix Base PRO).
See section 5.7 Connect sensors to controller > Outdoor sensor for more information
This setting is not shown if Domestic Hot Water is selected in the Zone Setup menu.
Heating Mode Outdoor Outdoor + Indoor comp.
PT RO RU SE SK 44
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK 8.5 Select which indoor temperature data in the Smatrix Base PRO system to use when calculating the supply temperature. • Worst Case uses the room temperature from the room (only rooms with a heating demand) with the highest setpoint value (heating mode), or with the highest measured relative humidity value (cooling), in the zone. • Average calculates,only in heating mode, the average from all connected room thermostats in the zone (selected in the Smatrix Base PRO interface I-147).
This setting is only shown if Smatrix Base PRO is selected in the Zone Setup menu, and if Outdoor + Indoor comp. is selected in Heating Mode.
8.6 Select how to switch zone 1 and 2 between heating and cooling.
• Supply Water Temp. uses the supply water temperature to switch the zone between heating and cooling.
• Force Cooling sets the zone in forced cooling.
This setting is only shown if 4 pipe is selected in the System Type menu, zone 1 is not enabled, Zone Setup is set to Stand Alone Control or Smatrix Base PRO, and Z1&2 Operation Mode is set to Heating And Cooling. Z1&2 HC Switchover Indoor and Outdoor Supply Water Temp. Contact Input Force Heating
DE
The cooling minimum and maximum supply temperatures can only be set if cooling is allowed in the zone.
DK
Heating Min. Supply Temp.
EE
15˚C min: 5
max: 70
ES
Heating Max. Supply Temp.
70˚C min: 15
FI
max: 70
Cooling Min. Supply Temp.
FR
8.0˚C min: 5.0
max: 25.0
HR
Cooling Max. Supply Temp.
25.0˚C min: 8.0
HU
max: 40.0
8.7 Select Enable to enable dehumidifier control in the zone.
• Contact Input uses an external signal to switch the zone between heating and cooling. • Force Heating sets the zone in forced heating.
CZ
The heating minimum and maximum supply temperatures can only be set if heating is allowed in the zone.
• Indoor and Outdoor uses the indoor and outdoor temperatures to switch the zone between heating and cooling.
Smatrix Indoor Temperature Worst Case Average
8.7 Set minimum and maximum allowed supply temperature when in heating and/or cooling mode.
IT
Note! Enabling dehumidifier disables circulation pump control in the zone (except for zones setup as Smatrix Base PRO where the circulation pump is controlled by the Base PRO controller).
LT
Dehumidifier Control
LV
Disable Enable
NL 8.8 Select Yes if a condensation sensor is installed in the zone and connected to the controller.
NO
Condensation Sensor No Yes
PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
45
UK 9. Enable Zone 3 9.1 Select Yes to enable zone 3 in the controller.
CZ
Enable Zone 3 No Yes
DE
9.2 Select the setup of the zone. Stand Alone Control only uses the sensors and components connected to the controller. Smatrix Base PRO uses a connected Uponor Smatrix Base PRO system. Meltaway uses snow sensors to keep large areas clear of snow.
DK EE
ES
Zone Setup Stand Alone Control Smatrix Base PRO Meltaway
FI
9.3 Select operation mode of the zone. The setting affects zone 3, if the system is installed and setup accordingly.
FR
HR
This setting is only shown if 4 pipe is selected in the System Type menu and if Zone Setup is set to Stand Alone Control or Smatrix Base PRO. Z3 Operation Mode Only Heating Only Cooling Heating And Cooling
HU IT
9.4 Select heating mode. Outdoor only uses an outdoor sensor, and Outdoor + Indoor comp. also uses an room sensor to calculate the supply temperature. The sensor/sensors are connected to either the Move PRO controller (Stand Alone Control) or to a connected Base PRO controller (Smatrix Base PRO).
LT LV
See section 5.7 Connect sensors to controller > Outdoor sensor for more information
This setting is not shown if Meltaway is selected in the Zone Setup menu.
NL NO
Heating Mode Outdoor Outdoor + Indoor comp.
9.5 Select which indoor temperature data in the Smatrix Base PRO system to use when calculating the supply temperature. • Worst Case uses the room temperature from the room (only rooms with a heating demand) with the highest setpoint value (heating mode), or with the highest measured relative humidity value (cooling), in the zone. • Average calculates,only in heating mode, the average from all connected room thermostats in the zone (selected in the Smatrix Base PRO interface I-147).
This setting is only shown if Smatrix Base PRO is selected in the Zone Setup menu, and if Outdoor + Indoor comp. is selected in Heating Mode. Smatrix Indoor Temperature Worst Case Average
9.6 Select how to switch zone 3 between heating and cooling.
• Indoor and Outdoor uses the indoor and outdoor temperatures to switch the zone between heating and cooling.
• Supply Water Temp. uses the supply water temperature to switch the zone between heating and cooling.
• Contact Input uses an external signal to switch the zone between heating and cooling.
• Force Heating sets the zone in forced heating.
• Force Cooling sets the zone in forced cooling.
This setting is only shown if Z3 Operation Mode is set to Heating And Cooling, and if the zone is setup as Stand Alone Controller or Smatrix Base PRO.
HC Switchover Indoor and Outdoor Supply Water Temp. Contact Input Force Heating
PL PT RO RU SE SK 46
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK 9.7 Set minimum and maximum allowed supply temperature when in heating and/or cooling mode.
The cooling minimum and maximum supply temperatures can only be set if cooling is allowed in the zone. Heating Min. Supply Temp.
min: 5
max: 70
70˚C Cooling Min. Supply Temp.
min: 5.0
max: 25.0
Cooling Max. Supply Temp.
• Indoor and Outdoor uses the indoor and outdoor temperatures to switch the zones between heating and cooling.
EE
FI
• Force Heating sets the zones in forced heating.
FR
• Force Cooling sets the zone in forced cooling. HC Switchover
HR
Indoor and Outdoor Supply Water Temp. Contact Input Force Heating
HU
11. Assign Controller to zone
If the Move PRO controller is connected to a Smatrix Base PRO system, the connected controllers can be assigned to the different zones. This requires the zone setup to be set to Smatrix Base PRO.
IT LT
N OT E ! The controllers in the Base PRO system must be registered to the Smatrix Base PRO interface I-147. Otherwise they will not appear in this menu.
Dehumidifier Control Disable Enable
9.9 Select Yes if a condensation sensor is installed in the zone and connected to the controller.
This setting is only shown if Smatrix Base PRO is selected in the Zone Setup menu.
Select a connected Smatrix Base PRO controller and assign it to a zone.
No Yes
DK
• Contact Input uses an external signal to switch the zones between heating and cooling.
Note! Enabling dehumidifier disables circulation pump control in the zone (except for zones setup as Smatrix Base PRO where the circulation pump is controlled by the Base PRO controller).
Condensation Sensor
DE
max: 40.0
9.8 Select Enable to enable dehumidifier control in the zone.
CZ
ES
25.0˚C min: 8.0
Select how to switch the zones in a 2 pipe system between heating and cooling (requires Indoor Cooling Only to be set to No). This only affects zones set to Stand Alone Control. If one of the zones is set to Smatrix Base PRO this setting will not be shown, as the heating/cooling swtiching will be performed by the Base PRO system.
• Supply Water Temp. uses the supply water temperature to switch the zones between heating and cooling.
max: 70
8.0˚C
Heating Max. Supply Temp.
min: 15
The heating minimum and maximum supply temperatures can only be set if heating is allowed in the zone.
15˚C
10 HC Switchover
LV NL NO
Assign Controller to zone Controller 1 Controller 2
PL
Zone 1 > Zone 2 >
PT
Controller 1 Not Assigned Zone 1 Zone 2 Zone 3
RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
47
UK CZ DE
5.18 Pre heating concrete slab (DIN 1264-4)
3. Set the date
The controller can be setup to pre heat a concrete slab before a property is finished.
Set the date of the system, starting with the day. Date Enter the day
Tue 01.06.2016
Pre heating is run in three different phases.
DK
Pase 1: The supply temperature setpoint is set to 25 ˚C for 3 days (can be set in the Settings menu).
Pase 2: The supply temperature setpoint is set to maximum allowed calculated setpoint for 4 days (can be set in the Settings menu).
Pase 3: The controller enters Standby mode until the startup wizard is restarted (Settings > Installer Settings > Restart wizard). Frost protection is active during this final phase.
EE ES FI FR
Enter the month
Tue 01.06.2016
In order to setup the controller zones, after pre heating, the startup wizard must be restarted.
Select Pre Heating to enable pre heating operation mode in the controller.
Select the language which is to be used in the controllers menu system. Language
LV
5. Enable Pre Heating Zone 1 5.1 Select Enable to enable pre heating zone 1 in the controller.
Pre-Heating Zone 1 Disable Enable
Set the time of the system, starting with the hours. 5.2 Set a maximum allowed calculated supply setpoint.
Time Enter the hours
12:34
NL
hh:mm
Operation Mode Standard Pre Heating
2. Set the time
LT
Enter the year
4. Select Operation Mode
English Deutsch Espanol Swedish
IT
Date
Tue 01.06.2016
1. Set language
HU
Date
C aution !
To setup the controller for pre heating:
HR
Z1 Max. Calc. Supply Setpoint
45.0˚C min: 5.0
Time
max: 70.0
Enter the minutes
NO
12:34 hh:mm
PL PT RO RU SE SK 48
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK 6. Enable Pre Heating Zone 2 6.1 Select Enable to enable pre heating zone 2 in the controller.
CZ
Pre-Heating Zone 2
DE
Disable Enable
DK
6.2 Set a maximum allowed calculated supply setpoint.
Z2 Max. Calc. Supply Setpoint
EE
45.0˚C min: 5.0
max: 70.0
ES
7. Enable Pre Heating Zone 3 7.1 Select Enable to enable pre heating zone 3 in the controller.
FI
Pre-Heating Zone 3 Disable Enable
FR HR
7.2 Set a maximum allowed calculated supply setpoint.
Z3 Max. Calc. Supply Setpoint
45.0˚C min: 5.0
HU
max: 70.0
IT LT LV NL NO PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
49
UK
6
CZ
Finishing installation
DE Make a complete check up of the installation:
5 DK
1. Make sure all wiring is done correctly and that the wires are thoroughly fastened.
3 1
EE
2
N
L
74 71
ES
S BMdbus
Mo
21
22
23
24
25
26
27
28
29
72
75
3. Check the mixing valves.
T
125 N 79 77
2. Re-attach the terminal covers to the controller.
mA
L
80
78
76
73
30
Increase the setpoints in each zone to make sure the mixing valves are opening correctly.
D microS
5 RJ4
4. Check the diverting valves.
FI
Base PRO
2 FR
6
4
Go to Settings > Zone # Settings (# = 1 – 3) > Manual Operation > Mixing valve and make sure the diverting valves are operating correctly.
5. Set system parameters in the controller to the defined operating settings. 6. Print and fill in the “Installation report” located at the end of the manual.
HR
7. Give the manual and all information about the system to the user.
HU IT
7
LT LV NL NO PL PT RO RU SE SK 50
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK
7 Operate the Uponor Smatrix Move PRO controller
CZ DE
7.1 Principle of operation
7.2 Controller layout
The controller calculates the supply temperature for up to 3 different zones using a wide array of sensors. The calculated supply temperature is compared to the measured supply temperature. If the measured temperature differs from the calculated, the controller adjusts the mixing valve to raise or lower the supply temperature in the zone.
The illustration below shows parts of the controller.
A
C
DK
B EE ES
H eating / cooling The zones (if set to Stand Alone Control and heating/ cooling enabled) can switch between heating and cooling using one of the following functions (set in the startup wizard): • Indoor and Outdoor uses the indoor and outdoor temperatures to switch the zones between heating and cooling. • Supply Water Temp. uses the supply water temperature to switch the zones between heating and cooling.
FI
D FR Item
Description
A
Display
B
Navigation wheel/ OK button Used for navigating the menu system, selecting options and confirming selections.
C
• Force Cooling sets the zone in forced cooling. If one of the zones is set to Smatrix Base PRO the Base PRO system will perform the heating/ cooling swtiching. The optional room temperature sensor is placed in a reference area and enables an indoor temperature setpoint parameter. It is used to keep fluctuations in the indoor temperature close to a minimum and as close as possible to the indoor temperature setpoint. In cooling mode it is also used for dew point calculation.
HU
Information button Used for showing current zone information such as supply temperature, pump status etc.
• Contact Input uses an external signal to switch the zones between heating and cooling. • Force Heating sets the zones in forced heating.
HR
IT
Push the button repeatedly to switch zones. D
Back button
LT
7.3 Navigating the menu system S elect / change
LV
Turn the control wheel to select an option, or to change a parameter setting.
NL NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
51
UK CZ
C onfirm
S tand A lone C ontrol
Press the control wheel to confirm a selection or parameter setting.
The following information is shown if the zone is setup as Stand Alone Control. • Supply Temperature (current supply temperature)
DE
• Indoor Temperature (current indoor temperature in the reference room requires a room temperature sensor).
DK
If System Type is set to 4 Pipe, and Operation Mode for the zone is set to Only Heating, then Heating Mode for the zone must be set to Outdoor + Indoor comp. to show this information.
EE
• Outdoor Temperature (current outdoor temperature)
ES
7.4 Start up
FI
When starting up, the controller shows the Uponor logo before entering the main menu.
FR
N OT E ! The display on the controller may start flashing when powered on. This only occurs after a firmware update and regular operation will continue shortly after.
HR HU
7.5 Information button
IT
• Pump (status). This information is not shown if a dehumidifier is enabled in the zone. • Mixing valve (status)
S matrix B ase PRO The following information is shown if the zone is setup as Smatrix Base PRO. • Supply Temperature (current supply temperature) • Indoor Temperature (current indoor temperature, worst case or average temperature from integrated Smatrix Base PRO system is used). This information is only shown when there is a heating/cooling demand in the Smatrix Base PRO system. If System Type is set to 4 Pipe, and Operation Mode for the zone is set to Only Heating, then Heating Mode for the zone must be set to Outdoor + Indoor comp. to show this information.
LT
• Outdoor Temperature (current outdoor temperature)
LV
• Mixing valve (status)
D omestic H ot W ater
NL The information button can be pressed anytime to get instant access to a summary of current information in the zones. Press the button several times to toggle between the different zones. Press the back button to return to the menu system.
NO PL
The following information is shown if the zone is setup as Domestic Hot Water. • Supply Temperature (current supply temperature) • Return Temperature (current return temperature) • Pump (status) • Mixing valve (status)
PT RO RU SE SK 52
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK
7.7 System Overview
M eltaway The following information is shown if the zone is setup as Meltaway.
This menu shows the current outdoor temperature, and supply temperatures for enabled zones.
CZ
Z# - S upply T emperature
DE
• Supply Temperature (current supply temperature) • Outdoor Temperature (current outdoor temperature) • Status (current meltaway statu:, Stop, Idle, Melting, Protection) • Pump (status)
The current supply temperature is shown. The temperature is measured by the supply temperature sensor wired to the controller.
DK
O utdoor T emperature
• Mixing valve (status)
7.6 Main menu The main menu is the base of the menu system, giving access to 4 different menu alternatives. Use the navigation wheel to navigate the menus and parameter settings. System Overview Z1 - Supply Temperature
35.5 °C
Z2 - Supply Temperature
30.1 °C
Z3 - Supply Temperature
18.9 °C
Outdoor Temperature
27.4 °C
The current outdoor temperature is shown. The temperature is measured by an outdoor temperature sensor wired to either the controller or to a connected Smatrix Base PRO system.
EE ES
7.8 Information FI
This menu shows information about the system, enabled zones and the controller (when the operating mode is set to Standard in the startup wizard).
FR
Menu tree*
HR
Information System information
Icon
Zone 1 Information
Description
Zone 3 Information
- Current outdoor temperature, and supply temperatures for enabled zones are shown.
Controller Information
Information
*
- System, zone (enabled zones only) and controller information are shown in this menu.
S ystem
Alarms
The system information menu shows the current time and date.
- Active alarms and alarm history are shown in this menu. Acknowledge alarms and/or reset alarm history. Settings - System, zone (enabled zones only) and controller parameters can be set in this menu.
HU
Zone 2 Information
System Overview
IT
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
LT
information
LV
If Operating Mode is set to Standard the measured outdoor temperature (from either the controller of from a connected Smatrix Base PRO system, see section 5.7 Connect sensors to controller > Outdoor sensor for more information) is also shown.
NL NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
53
UK Z one 1 I nformation
Operating Mode
This menu shows information about zone 1.
CZ
Menu tree*
DE
Supply temperature
Zone 1 Information Zone Setup Heating Mode
DK
Operating Mode Supply temperature Indoor temperature
EE
Mixing Valve Pump
ES
Heating Cooling
FI
*
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
Zone Setup
FR
The selected zone setup is shown: • Stand Alone Control
HR
• Smatrix Base PRO (integrated with a Smatrix Base PRO system)
HU
The current operating mode (heating or cooling) for the zone is shown:
Heating Mode The selected heating mode for the zone is shown:
IT
• Outdoor (only the outdoor temperature sensor is used)
LT
• Outdoor + Indoor comp. (the outdoor temperature sensor is used together with room temperature data)
LV
This information is only shown if one of the following conditions is met:
NL
• System Type is set to 4 Pipe, and Z1&2 Operation Mode is set to Only Heating or Heating and Cooling.
NO
• System Type is set to 2 Pipe, and Indoor Cooling Only is set to No.
The current supply temperature is shown. The temperature is measured by the supply temperature sensor wired to the controller. Indoor temperature The current indoor temperature for the zone is shown. If the zone is setup as Stand Alone Control the temperature is measured by a room temperature sensor wired to the Move PRO controller. This information is always shown, except if System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating, and Heating Mode is set to Outdoor. If the zone is setup as Smatrix Base PRO the Base PRO controller sends either Average or Worst Case (setup in the startup wizard) temperatures from the Base PRO system. This information is shown when there is a heating/cooling demand in the zone, except if System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating, and Heating Mode is set to Outdoor. Mixing Valve The status of the mixing valve is shown. 0 % (supply from heat source closed) – 100 % (supply from heat or cooling source fully opened). Pump The status of the circulation pump is shown (on/off). This information is only shown if Zone Setup is set to Stand Alone Control, and if Dehumidifier Control is Disabled.
PL PT RO RU SE SK 54
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Heating
MENU TREE*
This menu shows current heating mode information in the zone.
CZ
Cooling Cooling Curve
This information is only shown if one of the following conditions is met:
Calculated Supply Setpoint
• System Type is set to 4 Pipe, and Z1&2 Operation Mode is set to Only Heating or Heating and Cooling.
Relative Humidity
• System Type is set to 2 Pipe, and Indoor Cooling Only is set to No.
Dew Point Temperature
DK
Dehumidifier *
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
EE
COOLING CURVE
MENU TREE*
This menu shows the cooling curve, and max/min supply temperature limits, for the zone.
Heating Heating Curve Calculated Supply Setpoint ECO-Comf Status *
DE
Condensation
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
ES
CALCULATED SUPPLY SETPOINT
FI
The calculated supply temperature for cooling is shown. CONDENSATION
FR
HEATING CURVE
The current condensation status (Yes/No) in the zone is shown.
This menu shows the heating curve, and max/min supply temperature limits, for the zone.
This menu is only shown if Condensation Sensor is enabled in the startup wizard for the zone.
HR
CALCULATED SUPPLY SETPOINT
RELATIVE HUMIDITY
HU
The calculated supply temperature is shown. The setpoint is calculated using the sensor setup selected in Heating Mode.
The relative humidity level in the zone is shown.
ECO-COMF STATUS The current ECO/Comfort status for the zone is shown. This information is only shown if Zone Setup is set to Stand Alone Control and Heating Mode is set to Outdoor + Indoor comp..
If the zone is setup as Stand Alone Control the relative humidity is measured by a relative humidity sensor wired to the Move PRO controller.
IT
If the zone is setup as Smatrix Base PRO the Base PRO controller sends the highest relative humidity level from the Base PRO system (measured at thermostats with RH sensors and an active cooling demand).
LT LV
DEW POINT TEMPERATURE Cooling This menu shows current cooling mode information in the zone. This information is only shown if one of the following conditions is met: • System Type is set to 4 Pipe, and Z1&2 Operation Mode is set to Only Cooling or Heating and Cooling.
NL
The current dew point temperature in the zone is shown. DEHUMIDIFIER
NO
The status of the dehumidifier in the zone is shown (on/off).
PL
This information is only shown if Dehumidifier Control is Enabled.
PT
• System Type is set to 2 Pipe.
RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
55
UK Z one 2 I nformation
Operating Mode
This menu shows information about zone 2.
CZ
Menu tree*
DE
Supply temperature
Zone 2 Information Zone Setup Heating Mode
DK
Operating Mode Supply temperature Indoor temperature
EE
DHW Circ. Return Temp Mixing Valve
ES
Pump Heating Cooling
FI *
FR
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
Zone Setup The selected zone setup is shown:
HR
• Stand Alone Control • Smatrix Base PRO (integrated with a Smatrix Base PRO system)
HU
• Domestic Hot Water (DHW)
IT
Heating Mode The selected heating mode for the zone is shown: • Outdoor (only the outdoor temperature sensor is used)
LT
• Outdoor + Indoor comp. (the outdoor temperature sensor is used together with room temperature data)
LV
This information is only shown if one of the following conditions is met:
NL
• System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating or Heating and Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO.
NO PL
• System Type is set to 2 Pipe, Indoor Cooling Only is set to No, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO.
PT
The current operating mode (heating or cooling) for the zone is shown:
The current supply temperature is shown. The temperature is measured by the supply temperature sensor wired to the controller. Indoor temperature The current indoor temperature for the zone is shown. If the zone is setup as Stand Alone Control the temperature is measured by a room temperature sensor wired to the Move PRO controller. This information is always shown, except if System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating, and Heating Mode is set to Outdoor. If the zone is setup as Smatrix Base PRO the Base PRO controller sends either Average or Worst Case (setup in the startup wizard) temperatures from the Base PRO system. This information is shown when there is a heating/cooling demand in the zone, except if System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating, and Heating Mode is set to Outdoor. DHW Circ. Return Temp The current return temperature is shown. This information is only shown if Zone Setup is set to Domestic Hot Water. Mixing Valve The status of the mixing valve is shown. 0 % (supply from heat source closed) – 100 % (supply from heat or cooling source fully opened). Pump The status of the circulation pump is shown (on/off). This information is only shown if Zone Setup is set to Stand Alone Control or Domestic Hot Water, and if Dehumidifier Control is Disabled.
RO RU SE SK 56
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Heating
MENU TREE*
This menu shows current heating mode information in the zone.
CZ
Cooling Cooling Curve
This information is only shown if one of the following conditions is met:
Calculated Supply Setpoint
• System Type is set to 4 Pipe, and Z1&2 Operation Mode is set to Only Heating or Heating and Cooling.
Relative Humidity
• System Type is set to 2 Pipe, and Indoor Cooling Only is set to No.
Dew Point Temperature
DK
Dehumidifier *
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
EE
COOLING CURVE
MENU TREE*
This menu shows the cooling curve, and max/min supply temperature limits, for the zone.
Heating Heating Curve Calculated Supply Setpoint ECO-Comf Status *
DE
Condensation
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
ES
CALCULATED SUPPLY SETPOINT
FI
The calculated supply temperature for cooling is shown. CONDENSATION
FR
HEATING CURVE
The current condensation status (Yes/No) in the zone is shown.
This menu shows the heating curve, and max/min supply temperature limits, for the zone.
This menu is only shown if Condensation Sensor is enabled in the startup wizard for the zone.
HR
CALCULATED SUPPLY SETPOINT
RELATIVE HUMIDITY
HU
The calculated supply temperature is shown. The setpoint is calculated using the sensor setup selected in Heating Mode.
The relative humidity level in the zone is shown.
ECO-COMF STATUS The current ECO/Comfort status for the zone is shown. This information is only shown if Zone Setup is set to Stand Alone Control and Heating Mode is set to Outdoor + Indoor comp..
If the zone is setup as Stand Alone Control the relative humidity is measured by a relative humidity sensor wired to the Move PRO controller.
IT
If the zone is setup as Smatrix Base PRO the Base PRO controller sends the highest relative humidity level from the Base PRO system (measured at thermostats with RH sensors and an active cooling demand).
LT LV
DEW POINT TEMPERATURE Cooling This menu shows current cooling mode information in the zone. This information is only shown if one of the following conditions is met: • System Type is set to 4 Pipe, and Z1&2 Operation Mode is set to Only Cooling or Heating and Cooling.
NL
The current dew point temperature in the zone is shown. DEHUMIDIFIER
NO
The status of the dehumidifier in the zone is shown (on/off).
PL
This information is only shown if Dehumidifier Control is Enabled.
PT
• System Type is set to 2 Pipe.
RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
57
UK Z one 3 I nformation
Operating Mode
This menu shows information about zone 3.
CZ
Menu tree*
DE
Supply temperature
Zone 3 Information Zone Setup Heating Mode
DK
Operating Mode Supply temperature Indoor temperature
EE
Calculated Supply Setpoint Indoor temperature
ES
Meltaway Curve Return temperature
FI
Heating Cooling Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
Zone Setup
IT
The selected zone setup is shown: • Stand Alone Control
LT
• Smatrix Base PRO (integrated with a Smatrix Base PRO system)
LV NL
If the zone is setup as Stand Alone Control the temperature is measured by a room temperature sensor wired to the Move PRO controller. This information is always shown, except if System Type is set to 4 Pipe, Z3 Operation Mode is set to Only Heating, and Heating Mode is set to Outdoor. If the zone is setup as Smatrix Base PRO the Base PRO controller sends either Average or Worst Case (setup in the startup wizard) temperatures from the Base PRO system. This information is shown when there is a heating/cooling demand in the zone, except if System Type is set to 4 Pipe, Z3 Operation Mode is set to Only Heating, and Heating Mode is set to Outdoor.
• Meltaway
Meltaway Curve
Heating Mode
This menu shows the meltaway curve, and max/min supply temperature limits, for the zone.
The selected heating mode for the zone is shown:
NO
• Outdoor (only the outdoor temperature sensor is used)
PL
• Outdoor + Indoor comp. (the outdoor temperature sensor is used together with room temperature data)
PT
This information is only shown if one of the following conditions is met:
RO
• System Type is set to 4 Pipe, Z3 Operation Mode is set to Only Heating or Heating and Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO.
RU
This information is only shown if Zone Setup is set to Meltaway.
The current indoor temperature for the zone is shown.
Pump
*
The calculated supply temperature for meltaway is shown.
Indoor temperature
Mixing Valve
HU
Calculated Supply Setpoint
Ground Moisture Status
HR
The current supply temperature is shown. The temperature is measured by the supply temperature sensor wired to the controller.
Ground Temperature Primary Return Temperature
FR
The current operating mode (heating or cooling) for the zone is shown:
This information is only shown if Zone Setup is set to Meltaway. Return temperature The current return temperature is shown. This information is only shown if Zone Setup is set to Meltaway.
• System Type is set to 2 Pipe, Indoor Cooling Only is set to No, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO.
SE SK 58
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Ground Temperature
Pump
The current temperature in the ground around the snow sensor is shown.
The status of the circulation pump is shown (on/off).
CZ
This information is only shown if Zone Setup is set to Meltaway.
This information is only shown if Zone Setup is set to Stand Alone Control or Meltaway, and if Dehumidifier Control is Disabled.
DE
Ground Moisture
Heating
This parameter shows if there is moisture around the snow sensor.
This menu shows current heating mode information in the zone.
This information is only shown if Zone Setup is set to Meltaway.
This information is only shown if one of the following conditions is met:
DK EE
The current primary return temperature is shown.
• System Type is set to 4 Pipe, and Z3 Operation Mode is set to Only Heating or Heating and Cooling.
This information is only shown if Zone Setup is set to Meltaway.
• System Type is set to 2 Pipe, and Indoor Cooling Only is set to No.
FI
Status
MENU TREE*
FR
Primary Return temperature
This parameter shows the current meltaway status.
Heating
Stop: Meltaway is inactive.
Heating Curve
Idle: Meltaway is idle and the supply temperature is kept low to keep the zone from getting too cold.
Calculated Supply Setpoint
Melting: M eltaway is active. Protection: Protecting the heat source from low return temperatures. The status may change, in case of sensor fault. An alarm will also be shown in the display if that is the case. This information is only shown if Zone Setup is set to Meltaway. Mixing Valve The status of the mixing valve is shown. 0 % (supply from heat source closed) – 100 % (supply from heat or cooling source fully opened).
ES
HR
ECO-Comf Status *
HU
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
HEATING CURVE
IT
This menu shows the heating curve, and max/min supply temperature limits, for the zone.
LT
CALCULATED SUPPLY SETPOINT The calculated supply temperature is shown. The setpoint is calculated using the sensor setup selected in Heating Mode.
LV
ECO-COMF STATUS
NL
The current ECO/Comfort status for the zone is shown. This information is only shown if Zone Setup is set to Stand Alone Control and Heating Mode is set to Outdoor + Indoor comp..
NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
59
UK Cooling
DEW POINT TEMPERATURE
CZ
This menu shows current cooling mode information in the zone.
The current dew point temperature in the zone is shown.
DE
This information is only shown if one of the following conditions is met:
DEHUMIDIFIER
DK
• System Type is set to 4 Pipe, and Z3 Operation Mode is set to Only Cooling or Heating and Cooling.
The status of the dehumidifier in the zone is shown (on/off). This information is only shown if Dehumidifier Control is Enabled.
• System Type is set to 2 Pipe.
EE
C ontroller I nformation MENU TREE*
This menu shows information about the controller.
Cooling
ES
Menu tree Cooling Curve Calculated Supply Setpoint
FI
Controller Information Language
Condensation
About...
Relative Humidity Dew Point Temperature
FR
Dehumidifier *
HR HU
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
Language This menu show the set display language for the controller.
COOLING CURVE
About...
This menu shows the cooling curve, and max/min supply temperature limits, for the zone.
This menu shows the serial number, software versions, and hardware versions of the controller.
CALCULATED SUPPLY SETPOINT
IT
The calculated supply temperature for cooling is shown. CONDENSATION
LT
The current condensation status (Yes/No) in the zone is shown.
LV
This menu is only shown if Condensation Sensor is enabled in the startup wizard for the zone. RELATIVE HUMIDITY
NL
The relative humidity level in the zone is shown. If the zone is setup as Stand Alone Control the relative humidity is measured by a relative humidity sensor wired to the Move PRO controller.
NO
If the zone is setup as Smatrix Base PRO the Base PRO controller sends the highest relative humidity level from the Base PRO system (measured at thermostats with RH sensors and an active cooling demand).
PL PT RO RU SE SK 60
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK
7.9 Alarms
A larm
This menu shows the current active alarms and the alarm history. A possibility of acknowleding all alarms and reseting the alarm histroy is also available. Active alarms are always indicated with a ! and an number (of alarms) in the upper right corner of the display. Acknowledge the active alarms to remove the alarm indicator. Menu tree Alarms Active alarms Alarm history Acknowledge all alarms Reset alarm history
A ctive
alarms
This menu shows a list of all active alarms in the controller. Each active alarm is presented with a short description about when it was logged, why it occured, and if it has been acknowledged (indicated with a !). Detailed information is available via button press. The detailed information shows alarm type, time and date when it was logged, the source of the alarm with severity (PR1 to PR5, where PR5 is the worst), and which alarm group it belongs to (1 to 10). The alarm can alse be acknowledged in the detailed information. To access detailed alarm information: 1. Select an alarm. 2. Press the navigation wheel to confirm selection.
history
This menu shows a list of the 10 latest alarms in the controller. Each active alarm is presented with a short description about when it was logged and why it occured. Detailed information is available via button press.
CZ DE
The detailed information shows alarm type, time and date when it was logged, the source of the alarm with severity (PR1 to PR5, where PR5 is the worst), and which alarm group it belongs to (1 to 10).
DK
To access detailed alarm information:
EE
1. Select an alarm.
ES
2. Press the navigation wheel to confirm selection.
A cknowledge
all alarms
FI
This menu enables to acknowledge all active alarms. To acknowledge all active alarms:
FR
1. Select Acknowledge all alarms. 2. Press the navigation wheel to confirm selection.
HR
3. Select Yes.
Setting range: No (default)/Yes
4. Press the navigation wheel to confirm selection.
R eset
HU
alarm history
This menu enables to reset the alarm history.
IT
To reset the alarms history: 1. Select Reset alarm history.
LT
2. Press the navigation wheel to confirm selection. 3. Select Yes.
LV
Setting range: No (default)/Yes
4. Press the navigation wheel to confirm selection.
NL NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
61
UK CZ DE
7.10 Settings
T Outdoor Fallback
In this menu installer settings, enabled zone settings, and controller settings can be changed (when the operating mode is set to Standard in the startup wizard).
In this menu the fallback temperature for the outdoor temperature sensor is set. This value will be used if the connection to the outdoor temperature sensor is lost.
Menu tree*
To set the fallback temperature for the outdoor temperature sensor: 1. Select T Outdoor Fallback.
DK
Settings Installer Settings
EE ES
Zone 1 Settings
3. Set the value.
Zone 2 Settings
Default: 0 ˚C
Zone 3 Settings
Setting range: -50 – 50 ˚C, 1 ˚C increments
HC Switchover
4. Confirm the new setting by pressing the navigation wheel again.
Controller Settings *
FI
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
I nstaller S ettings In this menu lock codes (to gain access to locked parameter settings) can be set or changed, factory settings can be restored, backup of controller parameter settings can be managed, or the setup wizard can be restarted.
FR HR
Menu tree
HU
LT
A lock code can be used to block a user from changing parameter settings. The menu system is fully accessible, but the lock code is required to enter and change parameter settings. The default lock code is 0000. It is recommended to change this code if using this function.
T Outdoor Fallback
To enable lock code in the controller:
Lock code
1. Select Lock code.
Change lock code
2. Press the navigation wheel to confirm selection.
Display settings Restore factory settings Restore backup
LV
Lock code
The controller locks itself when it has been left untouched for about 10 minutes.
Installer Settings
IT
2. Press the navigation wheel to confirm selection.
3. Select Enable. 4. Press the navigation wheel to confirm selection.
New backup Restart wizard
NL NO PL PT RO RU SE SK 62
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK ENTERING A MENU WHEN LOCK CODE IS ENABLED
Display settings
To enter a lock code:
This menu enables display settings, such as contrast, and it also shows the version number of the display software.
CZ
To set the display contrast:
DE
1. Select the parameter. 2. Press the navigation wheel to confirm selection. 3. Enter the lock code in the boxes using the navigation wheel.
Turn the navigation wheel to either select a box, or to increase/decrease a value in edit mode.
Press the navigation wheel to enter edit mode or to confirm the new setting.
Default: 0000
1. Select Display settings.
3. Select Display contrast.
5. Set the display contrast.
Setting range: -50 – 100 %, 1 % increments
6. Press the navigation wheel to confirm selection.
5. Change the parameter setting and exit.
Restore factory settings
Change lock code
This menu enables all parameter settings in the controller to be reset to the factory default settings.
This menu is only shown when Lock code has been enabled in the Lock code menu. N OT E ! If the controller display is already locked, it has to be unlocked before entering the new lock code. To change the lock code:
EE
4. Press the navigation wheel to confirm selection.
4. Confirm the lock code by pressing and holding the navigation wheel for a number of seconds.
The standard lock code which is used to block a user from changing parameter settings, can be changed in this menu.
DK
2. Press the navigation wheel to confirm selection.
ES FI FR
To restore the factory settings: 1. Select Restore factory settings.
HR
2. Press the navigation wheel to confirm selection. 3. Select Yes.
HU
Setting range: No (default)/Yes
4. Press the navigation wheel to confirm selection.
IT
5. All parameters in the controller are being restored to factory settings.
LT
1. Select Change lock code. 2. Press the navigation wheel to confirm selection.
LV
3. Enter the new lock code in the boxes using the navigation wheel.
Turn the navigation wheel to either select a box, or to increase/decrease a value in edit mode.
NL
Press the navigation wheel to enter edit mode or to confirm the new setting.
NO
Default: 0000
PL
4. Confirm the new lock code by pressing and holding the navigation wheel for about 8 seconds.
PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
63
UK Restore backup
CZ
This menu enables the controller to restore all parameter settings from a previously created backup located on the microSD-card.
DE
To restore from a backup: 1. Make sure the microSD-card with the backup is inserted into the controller.
DK EE
Z one 1 S ettings In this menu parameter settings for zone 1 can be set or changed. Menu tree* Zone 1 Settings Supply Temp. Settings
2. Select Restore backup.
Heating Indoor Temp. Settings
3. Press the navigation wheel to confirm selection.
Comf. - ECO Heating Curve
4. Select Yes.
ES
Cooling Curve
Setting range: No (default)/Yes
Manual Operation
5. Press the navigation wheel to confirm selection.
Pump
6. All parameters in the controller are being restored from backup.
FI
Mixing Valve Dehumidifier Control Seasonal Shut Off
New backup
FR
This menu enables the controller to save a backup of all parameter settings to the microSD-card.
HR
H/C Switchover Condensation Delay *
To save from a backup: 1. Make sure a microSD-card, where the backup is to be saved, into the controller.
HU IT
Supply Temp. Settings
2. Select New backup.
This menu enables access to settings related to the supply temperature in the zone.
3. Press the navigation wheel to confirm selection.
MENU TREE*
4. Select Yes.
LT
Supply Temp. Settings Heating
Setting range: No (default)/Yes
Cooling
5. Press the navigation wheel to confirm selection. 6. All parameters in the controller are being saved to the microSD card.
LV
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
*
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
Restart wizard
NL
This menu enables the controller to restart the setup wizard.
NO
To restart the setup wizard: 1. Select Restart wizard.
PL
2. Press the navigation wheel to confirm selection. 3. Select Yes.
PT
Setting range: No (default)/Yes
4. Press the navigation wheel to confirm selection. 5. The setup wizard is now being restarted.
RO RU SE SK 64
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK HEATING
H E AT I N G M A X . S U P P LY T E M P.
This menu enables access to settings related to the heating supply temperature in the zone.
In this menu the maximum allowed supply temperature for the zone can be set. The supply temperature is not allowed to rise above this value.
CZ
This menu is only shown if one of the following requirements are met:
To set the maximum allowed supply temperature:
DE
• System Type is set to 2 Pipe and Indoor Cooling Only is set to No. • System Type is set to 4 Pipe and Z1&2 Operation Mode is set to Only Heating or Heating And Cooling.
1. Select Heating Max. supply temp. 2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 70.0 ˚C
Setting range: 5.0 (or min. supply temp) – 70.0 ˚C, 0.1 ˚C increments
MENU TREE
Heating Calculated Supply Setpoint
D E V I AT I O N A L A R M L I M I T
Heating Max. Supply Temp.
In this menu the deviation alarm limit for the supply temperature in the zone is set. If the difference between the measured and the calculated supply temperatures are higher than the set limit during the time set in Deviation alarm delay, the alarm is triggered.
Deviation alarm delay C A L C U L AT E D S U P P LY S E T P O I N T
In this menu the calculated supply setpoint for the zone can be overidden. This temperature is used as setpoint for the supply temperature.
To set the deviation alarm limit:
To override the calculated supply setpoint:
2. Press the navigation wheel to confirm selection.
1. Select Calculated supply setpoint.
3. Set the value.
2. Press the navigation wheel to confirm selection. 3. Select Manual. 4. Set the override value.
Setting range: -5.0 – 70.0 ˚C, 0.1 ˚C increments
5. Confirm the new setting by pressing the navigation wheel again. H E AT I N G M I N . S U P P LY T E M P.
In this menu the minimum allowed supply temperature for the zone can be set. The supply temperature is not allowed to fall below this value.
EE ES
4. Confirm the new setting by pressing the navigation wheel again.
Heating Min. Supply Temp. Deviation alarm limit
DK
FI FR HR
1. Select Deviation alarm limit.
Default: 10.0 ˚C
Setting range: 0.0 – 50.0 ˚C, 0.1 ˚C increments
HU IT
4. Confirm the new setting by pressing the navigation wheel again.
LT
D E V I AT I O N A L A R M D E L AY
In this menu the deviation alarm delay for the deviation alarm limit in the zone is set. If the difference between the measured and the calculated supply temperatures are higher than Deviation alarm limit during the set delay, the alarm is triggered.
LV
To set the deviation alarm delay:
NO
To set the minimum allowed supply temperature:
1. Select Deviation alarm delay.
1. Select Heating Min. supply temp.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Set the value.
Default: 5 min
Default: 15.0 ˚C
Setting range: 0 – 30 min, 1 min increments
Setting range: 5.0 – 35.0 ˚C (or max. supply temp), 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
NL
PL PT RO
4. Confirm the new setting by pressing the navigation wheel again.
RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
65
UK COOLING
C O O L I N G M I N . S U P P LY T E M P.
CZ
This menu enables access to settings related to the cooling supply temperature in the zone.
In this menu the minimum allowed supply temperature for the zone can be set. The supply temperature is not allowed to fall below this value.
DE
This menu is only shown if one of the following requirements are met:
To set the minimum allowed supply temperature:
• System Type is set to 2 Pipe.
DK
• System Type is set to 4 Pipe and Z1&2 Operation Mode is set to Only Cooling or Heating And Cooling.
EE
MENU TREE
1. Select Cooling Min. supply temp. 2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 8.0 ˚C
Setting range: 5.0 – 40.0 ˚C (or max. supply temp), 0.1 ˚C increments
Cooling
ES
Calculated Supply Setpoint Cooling Min. Supply Temp.
FI
Cooling Max. Supply Temp.
C O O L I N G M A X . S U P P LY T E M P.
Dew Point Margin
In this menu the maximum allowed supply temperature for the zone can be set. The supply temperature is not allowed to rise above this value.
Dew Point Offset
FR
C A L C U L AT E D S U P P LY S E T P O I N T
In this menu the calculated supply setpoint for the zone can be overidden. This temperature is used as setpoint for the supply temperature.
HR HU IT
To set the maximum allowed supply temperature: 1. Select Cooling Max. supply temp. 2. Press the navigation wheel to confirm selection.
To override the calculated supply setpoint:
3. Set the value.
1. Select Calculated supply setpoint.
Default: 25.0 ˚C
2. Press the navigation wheel to confirm selection.
Setting range: 5.0 (or min. supply temp) – 40.0 ˚C, 0.1 ˚C increments
3. Select Manual. 4. Set the override value.
LT
4. Confirm the new setting by pressing the navigation wheel again.
4. Confirm the new setting by pressing the navigation wheel again.
Setting range: -5.0 – 70.0 ˚C, 0.1 ˚C increments
5. Confirm the new setting by pressing the navigation wheel again.
LV NL NO PL PT RO RU SE SK 66
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK DEW POINT MARGIN
Heating Indoor Temp. Settings
In this menu the dew point margin for the zone can be set. The dew point temperature is calculated using the current room temperature and relative humidity.
This menu enables access to settings related to the room temperature sensor in the zone.
CZ
This menu and its submenus are only shown if Heating Mode is set to Outdoor + Indoor comp. for the zone.
DE
When the calculated supply temperature is lower than the dew point temperature + Dew Point Offset this value is added to the calculated supply temperature.
MENU TREE*
To set the dew point margin:
DK
Heating Indoor Temp. Settings
1. Select Dew Point Margin.
Indoor Setpoint
2. Press the navigation wheel to confirm selection.
Calculated Indoor Setpoint
3. Set the value.
ECO-Comf. Status
Default: 4.0 ˚C
Setting range: -1.0 – 10.0 ˚C
Indoor Setpoint Influence (Lower)
4. Confirm the new setting by pressing the navigation wheel again.
*
DEW POINT OFFSET
The offset is used together with the dew point temperature to decide when to increase the calculated supply temperature with the value set in Dew Point Margin.
This information is only shown if Zone Setup is set to Stand Alone Control for the zone.
To set the dew point offset:
1. Select Indoor Setpoint.
1. Select Dew Point Offset.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 1.0 ˚C
Setting range: 0.0 – 4.0 ˚C
4. Confirm the new setting by pressing the navigation wheel again.
FI
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
INDOOR SETPOINT
ES
Indoor Setpoint Influence (Upper)
In this menu the dew point offset for the zone can be set. The dew point temperature is calculated using the current room temperature and relative humidity.
3. Set the value.
EE
FR
In this menu the indoor temperature setpoint for the zone is set.
HR HU
To set the indoor temperature setpoint:
Default: 21.0 ˚C
Setting range: 5.0 – 35.0 ˚C, 0.1 ˚C increments
IT LT
4. Confirm the new setting by pressing the navigation wheel again.
LV
CALCULATED INDOOR SETPOINT
NL
This menu shows the calculated indoor setpoint for the zone.
NO
This information is only shown if Zone Setup is set to Stand Alone Control and if ECO-Comf mode is set to ECO for the zone.
PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
67
UK CZ
ECO-COMF STATUS
INDOOR SETPOINT INFLUENCE (UPPER)
This menu shows if the zone is set in ECO mode.
In this menu the indoor setpoint influence (upper) is set. If the measured indoor temperature is lower than the indoor temperature setpoint, the supply temperature sepoint will be increased using this value.
This information is only shown if ECO-Comf mode is set to ECO for the zone.
DE
INDOOR SETPOINT INFLUENCE (LOWER) In this menu the indoor setpoint influence (lower) is set. If the measured indoor temperature is higher than the indoor temperature setpoint, the supply temperature sepoint will be lowered using this value.
DK EE
This menu is used to to keep the measured room temperature as close as possible to the indoor temperature setpoint.
ES
N OT E ! If the value is set too high it can lead to the system being unstable and the room temperature will start fluctuating.
FI FR HR
N OT E ! If the value is set too high it can lead to the system being unstable and the room temperature will start fluctuating. To set the indoor setpoint influence (upper): 1. Select Indoor Setpoint Influence (Upper). 2. Press the navigation wheel to confirm selection. 3. Set the value.
To set the indoor setpoint influence (lower):
Default: 4.0 ˚C
1. Select Indoor Setpoint Influence (Lower).
Setting range: 0.0 – 10.0 ˚C, 0.1 ˚C increments
2. Press the navigation wheel to confirm selection.
4. Confirm the new setting by pressing the navigation wheel again.
3. Set the value.
HU
This menu is used to to keep the measured room temperature as close as possible to the indoor temperature setpoint.
Default: 4.0 ˚C
Setting range: 0.0 – 10.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
IT LT LV NL NO PL PT RO RU SE SK 68
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Comf. - ECO
To edit/create the ECO-Comf Schedule:
This menu enables access to settings related to the controller Comfort/ECO modes.
1. Select ECO-Comf Schedule.
This menu and its submenus are only shown if Zone Setup is set to Stand Alone Control and if Heating Mode is set to Outdoor + Indoor comp. for the zone.
CZ
2. Press the navigation wheel to confirm selection.
The current schedule is showing.
DE
3. Select a day. 4. Press the navigation wheel to confirm selection.
MENU TREE
Comf. - ECO ECO Setback ECO-Comf Status ECO-Comf Schedule
ECO SETBACK In this menu the ECO setback temperature is set. The parameter reduces the current setpoint with the set value. If the setback is set to 0 the zone will resume its normal operation, even if it is set in ECO mode. To set the ECO setback value: 1. Select ECO Setback. 2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 4.0 ˚C
Setting range: 0.0 – 10.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again. ECO-COMF STATUS This menu shows if the zone is set in ECO or Comf (comfort) mode. ECO-COMF SCHEDULE In this menu a schedule for switching between Comfort and ECO mode can be created. The default schedule is set to Comfort mode 24h a day, 7 days a week.
W arning ! Ensure that different schedules cannot enable ECO and Comf and the same time. This may cause an error where the controller must be reset to factory default values.
DK
All current schedule settings are shown, each line representing a switch between Comfort and ECO mode. If entering the menu for the first time only one line is present, showing Comf starting at 00:00 every day of the week.
EE ES
5. Select an existing line to edit or 00:00 Add new to add a new setting.
FI
6. Select wether to edit the hours, minutes, mode or day of the week. HOURS: Set at which hour the mode will start and press the navigation wheel to confirm selection.
FR
MINUTES: Set at which minte of the hour the mode will start and press the navigation wheel to confirm selection.
HR HU
MODE: Select a mode which should start at the set time and press the navigation wheel to confirm selection. Select between Comf, ECO and Delete switch time. Delete switch time erases the current line when selecting OK and pressing the navigation wheel.
IT LT
DAY OF THE WEEK:
Select which days of the week, at the set time the selected mode should start.
LV
7. Select OK at the end of the line, when done, and press the navigation wheel to confirm selection.
NL
A new line has been added to the schedule.
NO
8. Redo steps 5 and 6 until the schedule is complete. 9. Press the back button on the controller to exit the schedule setup.
PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
69
UK Heating Curve
Cooling Curve
CZ
This menu enables access to heating curve settings for the zone. Settings such as the slope (Setting) and offset of the heating curve.
This menu enables access to cooling curve settings for the zone. Settings such as the slope (Setting) and offset of the heating curve.
DE
This menu is only shown if one of the following requirements are met:
This menu is only shown if one of the following requirements are met:
DK
• System Type is set to 2 Pipe, and Indoor Cooling Only is set to No.
• System Type is set to 2 Pipe.
EE
• System Type is set to 4 Pipe, and Z1&2 Operation Mode is set to Only Heating or Heating And Cooling.
• System Type is set to 4 Pipe, and Z1&2 Operation Mode is set to Only Cooling or Heating And Cooling. MENU TREE
MENU TREE
ES
Cooling Curve
Heating Curve
FI
Setting Setting
Offset
Offset
Cooling Curve
Heating Curve
SETTING
FR
SETTING In this menu the slope of the heating curve is selected.
HR
To select a heating curve: 1. Select Setting.
HU
2. Press the navigation wheel to confirm selection.
IT LT
Default: 0.2
Setting range: 0.1 – 1.6, 0.1 increments
Setting range: 0.1 – 1.6, 0.1 increments
1. Select Offset. 2. Press the navigation wheel to confirm selection.
PT
3. Set the value.
To offset the heating curve:
PL
2. Press the navigation wheel to confirm selection.
Default: 0.9
In this menu the the heating curve can be offset. The offset can be used for temporary changes to the heating curve.
NO
1. Select Setting.
OFFSET
NL
To select a heating curve:
3. Set the value.
4. Confirm the new setting by pressing the navigation wheel again.
LV
In this menu the slope of the heating curve is selected.
4. Confirm the new setting by pressing the navigation wheel again. OFFSET In this menu the the heating curve can be offset. The offset can be used for temporary changes to the heating curve. To offset the heating curve: 1. Select Offset. 2. Press the navigation wheel to confirm selection. 3. Set the value.
3. Set the value.
Default: 0
Default: 0
Setting range: -8 – 8, 1 increments
Setting range: -8 – 8, 1 increments
4. Confirm the new setting by pressing the navigation wheel again.
RO
HEATING CURVE
RU
This menu shows the heating curve, and max/min supply temperature limits, for the zone.
4. Confirm the new setting by pressing the navigation wheel again. COOLING CURVE This menu shows the cooling curve, and max/min supply temperature limits, for the zone.
SE SK 70
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Manual Operation
MIXING VALVE
This menu enables access to manual operation mode in the zone.
In this menu the mixing valve can be overriden opened or closed manually.
When manual operation mode is activated, access to manual control (override) of the circulation pump and mixing valve is enabled.
This menu is only shown if Manual Mode is set to On.
DE
To override the mixing valve setting: 1. Select Mixing valve.
MENU TREE*
DK
2. Press the navigation wheel to confirm selection.
Manual Operation Manual Mode
*
CZ
3. Select Manual.
Pump
4. Set the override value.
Mixing valve
Default: 0 %
Setting range: 0 – 100 %, 1 % increments.
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
To activate manual operation mode:
EE ES
5. Confirm the new setting by pressing the navigation wheel again.
FI
1. Select Manual Mode. 2. Press the navigation wheel to confirm selection.
FR
3. Select On. 4. Confirm the new setting by pressing the navigation wheel again.
HR
PUMP
HU
In this menu the pump can be overidden and turned on or off manually. This menu is only shown if Zone Setup is set to Stand Alone Control, Dehumidifier is set to Disable, and Manual Mode is set to On.
IT LT
To override the circulation pump operation: 1. Select Pump. 2. Press the navigation wheel to confirm selection.
LV
3. Select Manual. 4. Select On.
Default: Off
Setting range: Off/On
NL NO
5. Confirm the new setting by pressing the navigation wheel again.
PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
71
UK Pump
Pump Exercise.
CZ
This menu enables access to pump settings in the zone.
To select a day of the week for pump exercise: 1. Select Exercise Day of the Week.
DE
This menu is only shown if Zone Setup is set to Stand Alone Control, and if Dehumidifier is disabled for the zone.
3. Select a day.
MENU TREE*
DK
Pump Pump Exercise Exercise Day of the Week
EE
Exercise Hour Exercise Min
ES
*
FI FR HR HU
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
EXERCISE HOUR In this menu the hour of the day for pump exercise is set.
In this menu pump exercise can be activated.
To select an hour of the day for pump exercise:
To activate pump exercise:
1. Select Exercise Hour.
1. Select Pump Exercise.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Select Pump Exercise.
Default: 8 h
Setting range: 0 – 23 h, 1 h increments
Default: No Exercise
Setting range: No Exercise/Pump Exercise
In this menu the day of the week for pump exercise is set. This menu is only shown if Pump Exercise is set to
LV
4. Confirm the setting by pressing the navigation wheel again.
PUMP EXERCISE
EXERCISE DAY OF THE WEEK
LT
Setting range: Monday – Sunday
This menu is only shown if Pump Exercise is set to Pump Exercise.
4. Confirm the new setting by pressing the navigation wheel again.
IT
2. Press the navigation wheel to confirm selection.
4. Confirm the setting by pressing the navigation wheel again. EXERCISE MIN In this menu the minute of the hour for pump exercise is set. This menu is only shown if Pump Exercise is set to Pump Exercise. To select a minute of the hour for pump exercise: 1. Select Exercise Min. 2. Press the navigation wheel to confirm selection.
NL
3. Set the value.
NO
Default: 0 min
Setting range: 0 – 59 min, 1 min increments
4. Confirm the setting by pressing the navigation wheel again.
PL PT RO RU SE SK 72
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK I-TIME
Mixing Valve This menu enables access to mixing valve settings in the zone.
CZ
To set the I-time:
MENU TREE*
DE
1. Select I-time.
Mixing Valve
*
In this menu the I-time for the mixing valve regulation is set.
Heating
2. Press the navigation wheel to confirm selection.
Cooling
3. Set the value.
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
HEATING This menu enables access to mixing valve settings in the zone while in heating mode.
Default: 35 seconds
Setting range: 5 – 300 seconds, 1 second increments
• System Type is set to 2 Pipe and Indoor Cooling Only is set to No.
To set the actuator running time:
Heating P-area I-time
ES
A C T U AT O R R U N N I N G T I M E
In this menu the actuator running time for the mixing valve regulation is set.
MENU TREE
EE
4. Confirm the setting by pressing the navigation wheel again.
This menu is only shown if one of the following requirements are met:
• System Type is set to 4 Pipe and Z1&2 Operation Mode is set to Only Heating or Heating And Cooling.
DK
FI
1. Select Actuator running time.
FR
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 120 seconds
Setting range: 0 – 500 seconds, 1 second increments
HR HU
4. Confirm the setting by pressing the navigation wheel again.
Actuator running time
IT
P-AREA
In this menu the P-area for the mixing valve regulation is set.
LT
To set the P-area:
LV
1. Select P-area. 2. Press the navigation wheel to confirm selection.
NL
3. Set the value.
Default: 140.0 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
NO
4. Confirm the setting by pressing the navigation wheel again.
PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
73
UK I-TIME
COOLING
CZ
This menu enables access to mixing valve settings in the zone while in cooling mode.
DE
This menu is only shown if one of the following requirements are met: • System Type is set to 2 Pipe and Indoor Cooling Only is set to Yes or No.
DK
• System Type is set to 4 Pipe and Z1&2 Operation Mode is set to Only Cooling or Heating And Cooling.
EE
Cooling P-area I-time
FI
Actuator running time P-AREA
FR
In this menu the P-area for the mixing valve regulation is set.
HR
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 50 seconds
Setting range: 5 – 300 seconds, 1 second increments
A C T U AT O R R U N N I N G T I M E
In this menu the actuator running time for the mixing valve regulation is set. To set the actuator running time: 1. Select Actuator running time. 2. Press the navigation wheel to confirm selection. 3. Set the value.
1. Select P-area.
Default: 60 seconds
Setting range: 0 – 500 seconds, 1 second increments
3. Set the value.
IT
1. Select I-time.
To set the P-area:
2. Press the navigation wheel to confirm selection.
HU
To set the I-time:
4. Confirm the setting by pressing the navigation wheel again.
MENU TREE
ES
In this menu the I-time for the mixing valve regulation is set.
Default: 200.0 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
4. Confirm the setting by pressing the navigation wheel again.
LT LV NL NO PL PT RO RU SE SK 74
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Dehumidifier Control
Seasonal Shut Off
This menu enables access to dehumidifier settings in the zone.
This menu enables access to seasonal shut off settings in the zone.
This menu is only shown if Dehumidifier Control is enabled in the startup wizard for the zone.
MENU TREE*
CZ DE
Seasonal Shut Off
MENU TREE
Heating
DK
Cooling
Dehumidifier Control Dew Point Margin
*
Dead Zone
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
EE
HEATING DEW POINT MARGIN In this menu the dew point margin, for controlling the dehumidifier, in the zone can be set. The dehumidifier is started when the supply temperature is equal or lower than the dew point temperature + dew point margin. The dehumidifier is shut off when the supply temperature is equal or higher than the dew point temperature + dew point margin + deadzone temperature.
This menu enables access to seasonal shut off settings in the zone, while in heating mode. This menu is only shown if one of the following requirements are met:
To set the dew point margin: 1. Select Dew Point Margin.
MENU TREE*
Setting range: -1.0 – 10.0 ˚C
Shut Off Outdoor Temp.
DEAD ZONE
T. Indoor Delay
1. Select Dead Zone. 2. Press the navigation wheel to confirm selection. 3. Set the value.
LT
Shut Off Indoor Temp.
*
LV
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
PUMP STOP
In this menu a function to stop the circulation pump, when requirements are met, is enabled.
NL
This menu is only shown if Zone Setup is set to Stand Alone Control, and Dehumidifier is set to Disable.
Default: 2.0 ˚C
To enable the function:
Setting range: 1.0 – 5.0 ˚C
1. Select Pump Stop.
4. Confirm the new setting by pressing the navigation wheel again.
IT
T. Outdoor Setpoint T. Outdoor Delay
To set the dead zone:
HU
Valve Close
4. Confirm the new setting by pressing the navigation wheel again.
In this menu the dead zone (hysteresis) for when to shut off the dehumidifier in the zone can be set.
HR
Pump Stop
3. Set the value.
FR
Heating
2. Press the navigation wheel to confirm selection.
Default: 4.0 ˚C
FI
• System Type is set to 2 Pipe, and Indoor Cooling Only is set to No. • System Type is set to 4 Pipe, and Z1&2 Operation Mode is set to Only Heating or Heating And Cooling.
ES
NO PL
2. Press the navigation wheel to confirm selection.
PT
3. Select Enable.
Default: Disable
Setting range: Disable/Enable
RO
4. Confirm the setting by pressing the navigation wheel again.
RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
75
UK CZ
VA LV E C LO S E
T. O U T D O O R S E T P O I N T
In this menu a function to close the mixing valve, when requirements are met, is enabled.
In this menu the outdoor temperature setpoint for stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
To enable the function:
DE
1. Select Valve Close. 2. Press the navigation wheel to confirm selection.
DK
3. Select Enable.
EE
Default: Disable
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation wheel again.
ES
S H U T O F F O U T D O O R T E M P.
This menu is only shown if Shut Off Outdoor Temp. is enabled. To set an outdoor temperature setpoint: 1. Select T Outdoor Setpoint. 2. Press the navigation wheel to confirm selection. 3. Select Enable.
Default: 17.0 ˚C
Setting range: 0.0 – 40.0 ˚C, 0.1 ˚C increments
FI
In this menu the function to stop the circulation pump and/or when to close the mixing valve, at an outdoor temperature setpoint is enabled/disabled for the zone.
4. Confirm the setting by pressing the navigation wheel again.
FR
This menu is only shown if Pump Stop and/or Valve Close is enabled.
In this menu the time delay for how long the outdoor temperature must be equal or higher than T Outdoor Setpoint before stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
To set an shut off outdoor temperature:
HR
1. Select Shut Off Outdoor Temp..
HU IT
2. Press the navigation wheel to confirm selection.
This menu is only shown if Shut Off Outdoor Temp. is enabled.
3. Select Enable.
To set the delay:
Default: Disable
1. Select T. Outdoor Delay.
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation wheel again.
LT
T. O U T D O O R D E L AY
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 24 h
Setting range: 0 – 24 h, 1 h increments
4. Confirm the setting by pressing the navigation wheel again.
LV NL NO PL PT RO RU SE SK 76
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK S H U T O F F I N D O O R T E M P.
COOLING
In this menu the function to stop the circulation pump, and/or when to close the mixing valve, at an indoor temperature setpoint is enabled/disabled for the zone.
This menu enables access to seasonal shut off settings in the zone, while in cooling mode.
CZ
This menu is only shown if one of the following requirements are met:
DE
This menu is only shown if Pump Stop and/or Valve Close is enabled, and if Heating Mode is set to Outdoor + Indoor comp. for the zone. To set an shut off outdoor temperature: 1. Select Shut Off Outdoor Temp.. 2. Press the navigation wheel to confirm selection.
• System Type is set to 2 Pipe.
EE
MENU TREE*
3. Select Enable.
Cooling
Default: Disable
Pump Stop
Setting range: Disable/Enable
Valve Close
In this menu the time delay for how long the indoor temperature must be equal or higher than the indoor setpoint before stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
ES
T. Outdoor Setpoint
4. Confirm the setting by pressing the navigation wheel again. T . I N D O O R D E L AY
DK
• System Type is set to 4 Pipe, and Z1&2 Operation Mode is set to Only Cooling or Heating And Cooling.
FI
T. Outdoor Delay *
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
FR
PUMP STOP
In this menu a function to stop the circulation pump, when requirements are met, is enabled.
This menu is only shown if Shut Off Indoor Temp. is enabled.
To enable the function:
To set the delay:
2. Press the navigation wheel to confirm selection.
1. Select T. Indoor Delay.
3. Select Enable.
2. Press the navigation wheel to confirm selection.
Default: Disable
3. Set the value.
Setting range: Disable/Enable
Default: 0 h
Setting range: 0 – 5 h, 1 h increments
4. Confirm the setting by pressing the navigation wheel again.
HR
1. Select Pump Stop.
HU IT LT LV
4. Confirm the setting by pressing the navigation wheel again.
NL NO PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
77
UK VA LV E C LO S E
In this menu a function to close the mixing valve, when requirements are met, is enabled.
CZ
To enable the function:
DE
1. Select Valve Close. 2. Press the navigation wheel to confirm selection.
DK
3. Select Enable.
EE
Default: Disable
Setting range: Disable/Enable
H/C Switchover This menu enables access to settings related to switching between heating and cooling in the zone. This menu is only shown if System Type is set to 4 Pipe and Z1&2 Operation Mode is set to Heating And Cooling. MENU TREE* H/C Switchover H/C Switchover Outdoor Trigger Temp.
4. Confirm the setting by pressing the navigation wheel again.
ES
Outdoor Trigger Delay Indoor Trigger Temp.
T. O U T D O O R S E T P O I N T
Indoor Trigger Delay.
In this menu the outdoor temperature setpoint for stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
FI
To set an outdoor temperature setpoint:
FR
1. Select T Outdoor Setpoint. 2. Press the navigation wheel to confirm selection.
HR
3. Select Enable.
HU
Default: 17.0 ˚C
Setting range: 0.0 – 40.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
IT
T . O U T D O O R D E L AY
In this menu the time delay for how long the outdoor temperature must be equal or higher than T Outdoor Setpoint before stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
LT LV
Supply Setpoint for HC Switch Hysteresis *
H/C SWITCHOVER In this menu settings for switching the zone between heating and cooling is set. To select heating/cooling swithover function for the zone: 1. Select H/C Switchover. 2. Press the navigation wheel to confirm selection. 3. Select heating/cooling switchover function for the zone.
• Indoor and Outdoor uses the indoor and outdoor temperatures and time delays to switch the zone between heating and cooling.
• Supply Water Temp. uses the supply water temperature and a hysteresis to switch the zone between heating and cooling.
• Contact Input uses an external signal to switch the zone between heating and cooling.
• Force Heating sets the zone in forced heating.
• Force Cooling sets the zone in forced cooling.
To set the delay: 1. Select T. Outdoor Delay.
NL
2. Press the navigation wheel to confirm selection. 3. Set the value.
NO PL
Default: 24 h
Setting range: 0 – 24 h, 1 h increments
4. Confirm the setting by pressing the navigation wheel again.
PT
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
4. Confirm the new setting by pressing the navigation wheel again.
RO RU SE SK 78
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK OUTDOOR TRIGGER TEMP.
INDOOR TRIGGER TEMP.
In this menu one of the triggers (outdoor temperature) for switching the zone between heating and cooling is set.
In this menu one of the triggers (indoor temperature) for switching the zone between heating and cooling is set.
N OT E ! All triggers and time delays must be met for the zone to switch heating/cooling mode.
N OT E ! All triggers and time delays must be met for the zone to switch heating/cooling mode.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
To set the outdoor trigger temperature:
To set the indoor trigger temperature:
1. Select Outdoor Trigger Temp.
1. Select Indoor Trigger Temp.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Set the value.
Default: 20.0 ˚C
Default: 22.0 ˚C
Setting range: 5.0 – 30.0 ˚C, 0.1 ˚C increments
Setting range: 5.0 – 30.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
4. Confirm the new setting by pressing the navigation wheel again.
OUTDOOR TRIGGER DELAY
INDOOR TRIGGER DELAY
In this menu one of the triggers (delay for outdoor temperature) for switching the zone between heating and cooling is set.
In this menu one of the triggers (delay for indoor temperature) for switching the zone between heating and cooling is set.
N OT E ! All triggers and time delays must be met for the zone to switch heating/cooling mode.
N OT E ! All triggers and time delays must be met for the zone to switch heating/cooling mode.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
To set the outdoor trigger delay:
To set the indoor trigger delay:
1. Select Outdoor Trigger Delay.
1. Select Indoor Trigger Delay.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Set the value.
Default: 24 h
Default: 24 h
Setting range: 1 – 48 h, 1 h increments
Setting range: 1 – 48 h, 1 h increments
4. Confirm the new setting by pressing the navigation wheel again.
CZ DE DK EE ES FI FR HR HU IT LT LV NL NO
4. Confirm the new setting by pressing the navigation wheel again.
PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
79
UK CZ
SUPPLY SETPOINT FOR HC SWITCH
HYSTERESIS
In this menu the supply temperature setpoint for switching between heating and cooling is set.
In this menu the hysteresis which is used to switch between heating and cooling using Supply Setpoint for HC Switch is set.
The zone switches to heating when the supply temperature is higher than Supply Setpoint for HC Switch. The zone switches back when the supply temperature is lower than Supply Setpoint for HC Switch - Hysteresis.
DE DK
The zone switches to cooling when the supply temperature is lower than Supply Setpoint for HC Switch. The zone switches back when the supply temperature is lower than Supply Setpoint for HC Switch + Hysteresis.
EE ES
N OT E ! When using this switch mode, the heating/ cooling switch is done in the heat pump/ chiller. The Move PRO controller switches the operation mode when it detects the change in supply temperture.
FI FR
No diverting valves are controlled in this mode.
HR
This menu is only shown if H/C Switchover is set to Supply Water Temp..
HU
To set the supply temperature setpoint for HC switch: 1. Select Supply Setpoint for HC Switch.
IT
2. Press the navigation wheel to confirm selection. 3. Set the value.
LT LV
Default: 18 ˚C
Setting range: 5 – 30 ˚C, 1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
To set the hysteresis: 1. Select Hysteresis. 2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 2 ˚C
Setting range: 0 – 4 ˚C, 1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again. Condensation Delay In this menu the condensation delay in the zone is set. If condensation is not detected (by the condensation sensor in the zone) during the time set in the delay, the condensation status (in the zone information menu) switches to No. This menu is only shown if Condensation Sensor is enabled in the startup wizard for the zone. To set the condensation delay: 1. Select Condensation Delay. 2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 10 min
Setting range: 0 – 120 min, 1 min increments
4. Confirm the new setting by pressing the navigation wheel again.
NL NO PL PT RO RU SE SK 80
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Z one 2 S ettings
HEATING
In this menu parameter settings for zone 2 can be set or changed. Menu tree* Zone 2 Settings Supply Temp. Settings Heating Indoor Temp. Settings DHW Circ Return Settings Comf. - ECO Heating Curve Cooling Curve Manual Operation
This menu enables access to settings related to the heating supply temperature in the zone.
CZ
This menu is only shown if one of the following requirements are met:
DE
• System Type is set to 2 Pipe, Indoor Cooling Only is set to No, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
DK
• System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
Heating
Mixing Valve
Calculated Supply Setpoint
Dehumidifier Control
Heating Min. Supply Temp.
Seasonal Shut Off
Heating Max. Supply Temp.
H/C Switchover
Deviation alarm limit
Condensation Delay
Deviation alarm delay
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
Supply Temp. Settings This menu enables access to settings related to the supply temperature in the zone. MENU TREE*
ES
MENU TREE
Pump
*
EE
FI FR HR
C A L C U L AT E D S U P P LY S E T P O I N T
In this menu the calculated supply setpoint for the zone can be overidden. This temperature is used as setpoint for the supply temperature.
HU
To override the calculated supply setpoint:
IT
1. Select Calculated supply setpoint. 2. Press the navigation wheel to confirm selection.
Supply Temp. Settings Heating Cooling DHW Supply Setpoint Overheating alarm limit Overheating alarm delay Deviation alarm limit
LT
3. Select Manual. 4. Set the override value.
LV
Setting range: -5.0 – 70.0 ˚C, 0.1 ˚C increments
5. Confirm the new setting by pressing the navigation wheel again.
NL
Deviation alarm delay *
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
81
UK H E AT I N G M I N . S U P P LY T E M P.
D E V I AT I O N A L A R M L I M I T
CZ
In this menu the minimum allowed supply temperature for the zone can be set. The supply temperature is not allowed to fall below this value.
DE
To set the minimum allowed supply temperature:
In this menu the deviation alarm limit for the supply temperature in the zone is set. If the difference between the measured and the calculated supply temperatures are higher than the set limit during the time set in Deviation alarm delay, the alarm is triggered.
1. Select Heating Min. supply temp. 2. Press the navigation wheel to confirm selection.
DK
3. Set the value.
EE ES
Default: 15.0 ˚C
Setting range: 5.0 – 35.0 ˚C (or max. supply temp), 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again. H E AT I N G M A X . S U P P LY T E M P.
FI
In this menu the maximum allowed supply temperature for the zone can be set. The supply temperature is not allowed to rise above this value.
FR
HU IT
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 10.0 ˚C
Setting range: 0.0 – 50.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again. D E V I AT I O N A L A R M D E L AY
1. Select Heating Max. supply temp. 2. Press the navigation wheel to confirm selection.
To set the deviation alarm delay:
3. Set the value.
1. Select Deviation alarm delay.
Default: 70.0 ˚C
Setting range: 5.0 (or min. supply temp) – 70.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
LT
1. Select Deviation alarm limit.
In this menu the deviation alarm delay for the deviation alarm limit in the zone is set. If the difference between the measured and the calculated supply temperatures are higher than Deviation alarm limit during the set delay, the alarm is triggered.
To set the maximum allowed supply temperature:
HR
To set the deviation alarm limit:
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 5 min
Setting range: 0 – 30 min, 1 min increments
4. Confirm the new setting by pressing the navigation wheel again.
LV NL NO PL PT RO RU SE SK 82
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK COOLING
C O O L I N G M I N . S U P P LY T E M P.
This menu enables access to settings related to the cooling supply temperature in the zone.
In this menu the minimum allowed supply temperature for the zone can be set. The supply temperature is not allowed to fall below this value.
CZ
This menu is only shown if one of the following requirements are met:
To set the minimum allowed supply temperature:
DE
• System Type is set to 2 Pipe, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone. • System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Cooling or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
1. Select Cooling Min. supply temp. 2. Press the navigation wheel to confirm selection.
DK
3. Set the value.
Default: 8.0 ˚C
Setting range: 5.0 – 40.0 ˚C (or max. supply temp), 0.1 ˚C increments
EE ES
4. Confirm the new setting by pressing the navigation wheel again.
MENU TREE
Cooling
C O O L I N G M A X . S U P P LY T E M P.
Calculated Supply Setpoint Cooling Min. Supply Temp. Cooling Max. Supply Temp. Dew Point Margin Dew Point Offset C A L C U L AT E D S U P P LY S E T P O I N T
In this menu the calculated supply setpoint for the zone can be overidden. This temperature is used as setpoint for the supply temperature. To override the calculated supply setpoint: 1. Select Calculated supply setpoint. 2. Press the navigation wheel to confirm selection.
FI
In this menu the maximum allowed supply temperature for the zone can be set. The supply temperature is not allowed to rise above this value.
FR
To set the maximum allowed supply temperature: 1. Select Cooling Max. supply temp.
HR
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 25.0 ˚C
Setting range: 5.0 (or min. supply temp) – 40.0 ˚C, 0.1 ˚C increments
HU IT
4. Confirm the new setting by pressing the navigation wheel again.
LT
3. Select Manual. 4. Set the override value.
LV
Setting range: -5.0 – 70.0 ˚C, 0.1 ˚C increments
5. Confirm the new setting by pressing the navigation wheel again.
NL NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
83
UK CZ
DEW POINT MARGIN
DHW SUPPLY SETPOINT
In this menu the dew point margin for the zone can be set. The dew point temperature is calculated using the current room temperature and relative humidity.
In this menu the supply temperature setpoint for domestic hot water production is set.
When the calculated supply temperature is lower than the dew point temperature + Dew Point Offset this value is added to the calculated supply temperature.
DE DK EE ES
1. Select Supply Setpoint.
1. Select Dew Point Margin.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Set the value.
Default: 60.0 ˚C
Setting range: 5.0 – 95.0 ˚C, 0.1 ˚C increments
Default: 4.0 ˚C
Setting range: -1.0 – 10.0 ˚C
DEW POINT OFFSET
FR
In this menu the dew point offset for the zone can be set. The dew point temperature is calculated using the current room temperature and relative humidity.
HR
The offset is used together with the dew point temperature to decide when to increase the calculated supply temperature with the value set in Dew Point Margin.
HU
To set the dew point offset:
IT
1. Select Dew Point Offset. 2. Press the navigation wheel to confirm selection.
LT
3. Set the value.
LV
To set the supply temperature setpoint:
To set the dew point margin:
4. Confirm the new setting by pressing the navigation wheel again.
FI
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone.
Default: 1.0 ˚C
Setting range: 0.0 – 4.0 ˚C
4. Confirm the new setting by pressing the navigation wheel again. OVERHEATING ALARM LIMIT In this menu the overheating alarm limit for domestic hot water production is set. If the supply temperature is higher than the set limit during the time set in Overheating alarm delay, the alarm is triggered. This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone. To set the overheating alarm limit: 1. Select Overheating alarm limit. 2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 68.0 ˚C
Setting range: 65.0 – 120.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
4. Confirm the new setting by pressing the navigation wheel again.
NL NO PL PT RO RU SE SK 84
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK OVERHEATING ALARM DELAY
DEVIATION ALARM DELAY
In this menu the overheating alarm delay for the overheating alarm limit of the zone is set. If the supply temperature is higher than Overheating alarm limit, during the set delay, the alarm is triggered.
In this menu the deviation alarm delay for the deviation alarm limit in the zone is set. If the difference between the measured and the calculated supply temperatures are higher than Deviation alarm limit during the set delay, the alarm is triggered.
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone To set the overheating alarm delay: 1. Select Overheating alarm delay. 2. Press the navigation wheel to confirm selection. 3. Set the value.
DK
To set the deviation alarm delay:
EE
1. Select Deviation alarm delay. 2. Press the navigation wheel to confirm selection.
Default: 10 min
3. Set the value.
Setting range: 0 – 15 min, 1 min increments
Default: 60 seconds
Setting range: 0 – 600 seconds, 1 second increments
DEVIATION ALARM LIMIT
DE
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone.
4. Confirm the new setting by pressing the navigation wheel again.
CZ
ES FI
4. Confirm the new setting by pressing the navigation wheel again.
FR
In this menu the deviation alarm limit for the supply temperature in the zone is set. If the difference between the measured and the calculated supply temperatures are higher than the set limit during the time set in Deviation alarm delay, the alarm is triggered.
HR HU
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone. To set the deviation alarm limit:
IT
1. Select Deviation alarm limit. 2. Press the navigation wheel to confirm selection.
LT
3. Set the value.
Default: 10 ˚C
Setting range: 0.0 – 30.0 ˚C, 0.1 ˚C increments
LV
4. Confirm the new setting by pressing the navigation wheel again.
NL NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
85
UK Heating Indoor Temp. Settings
INDOOR SETPOINT INFLUENCE (LOWER)
CZ
This menu enables access to settings related to the room temperature sensor in the zone.
DE
This menu and its submenus are only shown if Heating Mode is set to Outdoor + Indoor comp. for the zone.
In this menu the indoor setpoint influence (lower) is set. If the measured indoor temperature is higher than the indoor temperature setpoint, the supply temperature sepoint will be lowered using this value. This menu is used to to keep the measured room temperature as close as possible to the indoor temperature setpoint.
MENU TREE*
DK
Heating Indoor Temp. Settings
N OT E ! If the value is set too high it can lead to the system being unstable and the room temperature will start fluctuating.
Indoor Setpoint
EE
Calculated Indoor Setpoint ECO-Comf. Status
ES
Indoor Setpoint Influence (Lower) Indoor Setpoint Influence (Upper)
FI *
FR HR
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
Default: 4.0 ˚C
In this menu the indoor temperature setpoint for the zone is set.
Setting range: 0.0 – 10.0 ˚C, 0.1 ˚C increments
2. Press the navigation wheel to confirm selection. 3. Set the value.
LV
3. Set the value.
1. Select Indoor Setpoint.
LT
2. Press the navigation wheel to confirm selection.
To set the indoor temperature setpoint:
IT
1. Select Indoor Setpoint Influence (Lower).
INDOOR SETPOINT
This information is only shown if Zone Setup is set to Stand Alone Control for the zone.
HU
To set the indoor setpoint influence (lower):
Default: 21.0 ˚C
Setting range: 5.0 – 35.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again. INDOOR SETPOINT INFLUENCE (UPPER) In this menu the indoor setpoint influence (upper) is set. If the measured indoor temperature is lower than the indoor temperature setpoint, the supply temperature sepoint will be increased using this value. This menu is used to to keep the measured room temperature as close as possible to the indoor temperature setpoint.
4. Confirm the new setting by pressing the navigation wheel again.
N OT E ! If the value is set too high it can lead to the system being unstable and the room temperature will start fluctuating.
CALCULATED INDOOR SETPOINT
NL
This menu shows the calculated indoor setpoint for the zone.
NO
This information is only shown if Zone Setup is set to Stand Alone Control and if ECO-Comf mode is set to ECO for the zone.
PL PT
To set the indoor setpoint influence (upper): 1. Select Indoor Setpoint Influence (Upper). 2. Press the navigation wheel to confirm selection. 3. Set the value.
ECO-COMF STATUS
Default: 4.0 ˚C
This menu shows if the zone is set in ECO mode.
Setting range: 0.0 – 10.0 ˚C, 0.1 ˚C increments
This information is only shown if ECO-Comf mode is set to ECO for the zone.
4. Confirm the new setting by pressing the navigation wheel again.
RO RU SE SK 86
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK DHW Circ Return Settings
Comf. - ECO
This menu enables access to settings related to the return temperature sensor.
This menu enables access to settings related to the controller Comfort/ECO modes.
CZ
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone.
This menu and its submenus are only shown if Zone Setup is set to Stand Alone Control and if Heating Mode is set to Outdoor + Indoor comp. for the zone.
DE
MENU TREE
DK
MENU TREE DHW Circ Return Settings
Comf. - ECO
DHW Circ Return Setpoint
ECO Setback
BoostPower
EE
ECO-Comf Status
DHW CIRC RETURN SETPOINT In this menu the return temperature setpoint for the zone is set.
ECO-Comf Schedule
ES
ECO SETBACK In this menu the ECO setback temperature is set. The parameter reduces the current setpoint with the set value.
FI
If the setback is set to 0 the zone will resume its normal operation, even if it is set in ECO mode.
FR
3. Set the value.
Default: 50.0 ˚C
To set the ECO setback value:
Setting range: 50.0 – 250.0 ˚C, 0.1 ˚C increments
1. Select ECO Setback.
To set the return temperature setpoint: 1. Select DHW Circ Return Setpoint. 2. Press the navigation wheel to confirm selection.
4. Confirm the new setting by pressing the navigation wheel again. BOOSTPOWER
2. Press the navigation wheel to confirm selection.
HU
3. Set the value.
Default: 4.0 ˚C
In this menu the boost power for domestic hot water production is set. The parameter is used to adjust the calculated supply temperature, if the difference between the supply and return temperatures is to large.
Setting range: 0.0 – 10.0 ˚C, 0.1 ˚C increments
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone.
ECO-COMF STATUS
To set the boost power:
HR
IT
4. Confirm the new setting by pressing the navigation wheel again.
LT
This menu shows if the zone is set in ECO or Comf (comfort) mode.
LV
1. Select BoostPower.
NL
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 60 %
Setting range: 0 – 100 %, 1 % increments
NO PL
4. Confirm the new setting by pressing the navigation wheel again.
PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
87
UK ECO-COMF SCHEDULE
CZ
In this menu a schedule for switching between Comfort and ECO mode can be created.
DE
The default schedule is set to Comfort mode 24h a day, 7 days a week.
W arning !
DK
7. Select OK at the end of the line, when done, and press the navigation wheel to confirm selection.
A new line has been added to the schedule.
8. Redo steps 5 and 6 until the schedule is complete. 9. Press the back button on the controller to exit the schedule setup.
Ensure that different schedules cannot enable ECO and Comf and the same time. This may cause an error where the controller must be reset to factory default values.
EE
To edit/create the ECO-Comf Schedule: 1. Select ECO-Comf Schedule.
ES
2. Press the navigation wheel to confirm selection.
FI
The current schedule is showing.
3. Select a day. 4. Press the navigation wheel to confirm selection.
FR
HR HU
All current schedule settings are shown, each line representing a switch between Comfort and ECO mode. If entering the menu for the first time only one line is present, showing Comf starting at 00:00 every day of the week.
5. Select an existing line to edit or 00:00 Add new to add a new setting.
IT
6. Select wether to edit the hours, minutes, mode or day of the week.
LT
HOURS: Set at which hour the mode will start and press the navigation wheel to confirm selection.
LV
MINUTES: Set at which minte of the hour the mode will start and press the navigation wheel to confirm selection.
NL
MODE: Select a mode which should start at the set time and press the navigation wheel to confirm selection. Select between Comf, ECO and Delete switch time. Delete switch time erases the current line when selecting OK and pressing the navigation wheel.
NO PL PT
DAY OF THE WEEK:
Select which days of the week, at the set time the selected mode should start.
RO RU SE SK 88
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Heating Curve
OFFSET
This menu enables access to heating curve settings for the zone. Settings such as the slope (Setting) and offset of the heating curve.
In this menu the the heating curve can be offset. The offset can be used for temporary changes to the heating curve.
CZ
This menu is only shown if one of the following requirements are met:
To offset the heating curve:
DE
• System Type is set to 2 Pipe, Indoor Cooling Only is set to No, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone. • System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone. MENU TREE
1. Select Offset.
DK
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 0
Setting range: -8 – 8, 1 increments
EE
4. Confirm the new setting by pressing the navigation wheel again.
ES
HEATING CURVE
Heating Curve Setting
FI
This menu shows the heating curve, and max/min supply temperature limits, for the zone.
Offset
FR
Heating Curve
SETTING
HR
In this menu the slope of the heating curve is selected. To select a heating curve:
HU
1. Select Setting. 2. Press the navigation wheel to confirm selection.
IT
3. Set the value.
Default: 0.9
Setting range: 0.1 – 1.6, 0.1 increments
LT
4. Confirm the new setting by pressing the navigation wheel again.
LV NL NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
89
UK Cooling Curve
OFFSET
CZ
This menu enables access to cooling curve settings for the zone. Settings such as the slope (Setting) and offset of the heating curve.
In this menu the the heating curve can be offset. The offset can be used for temporary changes to the heating curve.
DE
This menu is only shown if one of the following requirements are met:
To offset the heating curve:
DK
• System Type is set to 2 Pipe and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
EE
• System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Cooling or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
ES
MENU TREE
FI
1. Select Offset. 2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 0
Setting range: -8 – 8, 1 increments
4. Confirm the new setting by pressing the navigation wheel again. COOLING CURVE
Cooling Curve Setting
This menu shows the cooling curve, and max/min supply temperature limits, for the zone.
Offset
FR
Cooling Curve
SETTING
HR
In this menu the slope of the heating curve is selected. To select a heating curve:
HU
1. Select Setting. 2. Press the navigation wheel to confirm selection.
IT
3. Set the value.
LT
Default: 0.2
Setting range: 0.1 – 1.6, 0.1 increments
4. Confirm the new setting by pressing the navigation wheel again.
LV NL NO PL PT RO RU SE SK 90
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Manual Operation
MIXING VALVE
This menu enables access to manual operation mode in the zone.
In this menu the mixing valve can be overriden opened or closed manually.
When manual operation mode is activated, access to manual control (override) of the circulation pump and mixing valve is enabled.
This menu is only shown if Manual Mode is set to On.
DE
To override the mixing valve setting: 1. Select Mixing valve.
MENU TREE*
DK
2. Press the navigation wheel to confirm selection.
Manual Operation Manual Mode
*
CZ
3. Select Manual.
Pump
4. Set the override value.
Mixing valve
Default: 0 %
Setting range: 0 – 100 %, 1 % increments.
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
To activate manual operation mode:
EE ES
5. Confirm the new setting by pressing the navigation wheel again.
FI
1. Select Manual Mode. 2. Press the navigation wheel to confirm selection.
FR
3. Select On. 4. Confirm the new setting by pressing the navigation wheel again.
HR
PUMP
HU
In this menu the pump can be overidden and turned on or off manually. This menu is only shown if Zone Setup is set to Stand Alone Control or Domestic Hot Water, Dehumidifier is set to Disable, and Manual Mode is set to On.
IT LT
To override the circulation pump operation: 1. Select Pump.
LV
2. Press the navigation wheel to confirm selection. 3. Select Manual.
NL
4. Select On.
Default: Off
Setting range: Off/On
NO
5. Confirm the new setting by pressing the navigation wheel again.
PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
91
UK Pump
EXERCISE HOUR
CZ
This menu enables access to pump settings in the zone.
DE
This menu is only shown if Zone Setup is set to Stand Alone Control or Domestic Hot Water, and if Dehumidifier is disabled for the zone.
In this menu the hour of the day for pump exercise is set.
MENU TREE*
DK
To select an hour of the day for pump exercise: 1. Select Exercise Hour.
Pump
EE
Pump Exercise
2. Press the navigation wheel to confirm selection.
Exercise Day of the Week
3. Set the value.
Exercise Hour Exercise Min
ES
*
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
PUMP EXERCISE
FI
In this menu pump exercise can be activated. To activate pump exercise:
FR
1. Select Pump Exercise.
HR HU
Default: 8 h
Setting range: 0 – 23 h, 1 h increments
4. Confirm the setting by pressing the navigation wheel again. EXERCISE MIN In this menu the minute of the hour for pump exercise is set.
2. Press the navigation wheel to confirm selection.
This menu is only shown if Pump Exercise is set to Pump Exercise.
3. Select Pump Exercise.
To select a minute of the hour for pump exercise:
Default: No Exercise
1. Select Exercise Min.
Setting range: No Exercise/Pump Exercise
4. Confirm the new setting by pressing the navigation wheel again.
IT
This menu is only shown if Pump Exercise is set to Pump Exercise.
EXERCISE DAY OF THE WEEK
LT
In this menu the day of the week for pump exercise is set.
LV
This menu is only shown if Pump Exercise is set to Pump Exercise.
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 0 min
Setting range: 0 – 59 min, 1 min increments
4. Confirm the setting by pressing the navigation wheel again.
To select a day of the week for pump exercise:
NL
1. Select Exercise Day of the Week. 2. Press the navigation wheel to confirm selection.
NO
3. Select a day.
Setting range: Monday – Sunday
4. Confirm the setting by pressing the navigation wheel again.
PL PT RO RU SE SK 92
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK I-TIME
Mixing Valve This menu enables access to mixing valve settings in the zone.
CZ
To set the I-time:
MENU TREE*
DE
1. Select I-time.
Mixing Valve Heating
2. Press the navigation wheel to confirm selection.
Cooling
3. Set the value.
P-area
Default: 35 seconds
I-time
Setting range: 5 – 300 seconds, 1 second increments
Actuator running time *
In this menu the I-time for the mixing valve regulation is set.
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
DK EE
4. Confirm the setting by pressing the navigation wheel again.
ES
A C T U AT O R R U N N I N G T I M E
HEATING This menu enables access to mixing valve settings in the zone while in heating mode. This menu is only shown if one of the following requirements are met:
In this menu the actuator running time for the mixing valve regulation is set.
FI
To set the actuator running time: 1. Select Actuator running time.
• System Type is set to 2 Pipe, Indoor Cooling Only is set to No, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
2. Press the navigation wheel to confirm selection.
Default: 120 seconds
• System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
Setting range: 0 – 500 seconds, 1 second increments
FR
3. Set the value.
HR HU
4. Confirm the setting by pressing the navigation wheel again.
IT
MENU TREE
Heating
LT
P-area I-time Actuator running time
LV
P-AREA
In this menu the P-area for the mixing valve regulation is set.
NL
To set the P-area:
NO
1. Select P-area. 2. Press the navigation wheel to confirm selection.
PL
3. Set the value.
Default: 140.0 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
PT
4. Confirm the setting by pressing the navigation wheel again.
RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
93
UK I-TIME
COOLING
CZ
This menu enables access to mixing valve settings in the zone while in cooling mode.
DE
This menu is only shown if one of the following requirements are met:
DK
• System Type is set to 2 Pipe and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone. • System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Cooling or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
EE ES
MENU TREE
FR HR
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 50 seconds
Setting range: 5 – 300 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
P-area I-time
To set the actuator running time:
Actuator running time
1. Select Actuator running time.
P-AREA
2. Press the navigation wheel to confirm selection.
In this menu the P-area for the mixing valve regulation is set.
3. Set the value.
1. Select P-area. 2. Press the navigation wheel to confirm selection.
IT
1. Select I-time.
In this menu the actuator running time for the mixing valve regulation is set.
To set the P-area:
HU
To set the I-time:
A C T U AT O R R U N N I N G T I M E
Cooling
FI
In this menu the I-time for the mixing valve regulation is set.
Default: 60 seconds
Setting range: 0 – 500 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
3. Set the value.
LT
Default: 200.0 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
LV NL NO PL PT RO RU SE SK 94
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK P-AREA
ACTUATOR RUNNING TIME
In this menu the P-area for the mixing valve regulation is set.
In this menu the actuator running time for the mixing valve regulation is set.
CZ
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone.
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone.
DE
To set the P-area:
To set the actuator running time:
1. Select P-area.
1. Select Actuator running time.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Set the value.
Default: 70 ˚C
Default: 60 seconds
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
Setting range: 0 – 300 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
DK EE ES
4. Confirm the setting by pressing the navigation wheel again.
FI
I-TIME In this menu the I-time for the mixing valve regulation is set.
FR
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone.
HR
To set the I-time: 1. Select I-time.
HU
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 18 seconds
Setting range: 5 – 300 seconds, 1 second increments
IT LT
4. Confirm the setting by pressing the navigation wheel again.
LV NL NO PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
95
UK Dehumidifier Control
Seasonal Shut Off
CZ
This menu enables access to dehumidifier settings in the zone.
This menu enables access to seasonal shut off settings in the zone.
DE
This menu is only shown if Dehumidifier Control is enabled in the startup wizard for the zone.
This menu is only shown if Zone Setup is set to Stand Alone Control or Smatrix Base PRO.
MENU TREE
MENU TREE*
DK
Dehumidifier Control
EE
Seasonal Shut Off Dew Point Margin
Heating
Dead Zone
Cooling
DEW POINT MARGIN
ES
In this menu the dew point margin, for controlling the dehumidifier, in the zone can be set. The dehumidifier is started when the supply temperature is equal or lower than the dew point temperature + dew point margin. The dehumidifier is shut off when the supply temperature is equal or higher than the dew point temperature + dew point margin + deadzone temperature.
FI FR
To set the dew point margin:
HR
LT LV
HEATING This menu enables access to seasonal shut off settings in the zone, while in heating mode. This menu is only shown if one of the following requirements are met: • System Type is set to 2 Pipe, Indoor Cooling Only is set to No, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
3. Set the value.
Default: 4.0 ˚C
MENU TREE*
Setting range: -1.0 – 10.0 ˚C
2. Press the navigation wheel to confirm selection.
IT
Heating
4. Confirm the new setting by pressing the navigation wheel again.
Pump Stop
DEAD ZONE
Shut Off Outdoor Temp.
In this menu the dead zone (hysteresis) for when to shut off the dehumidifier in the zone can be set.
T. Outdoor Setpoint
Valve Close
T. Outdoor Delay Shut Off Indoor Temp.
To set the dead zone:
NL
1. Select Dead Zone. 2. Press the navigation wheel to confirm selection.
NO
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
• System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
1. Select Dew Point Margin.
HU
*
T. Indoor Delay *
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
3. Set the value.
Default: 2.0 ˚C
PL
Setting range: 1.0 – 5.0 ˚C
PT
4. Confirm the new setting by pressing the navigation wheel again.
RO RU SE SK 96
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK PUMP STOP
T. O U T D O O R S E T P O I N T
In this menu a function to stop the circulation pump, when requirements are met, is enabled.
In this menu the outdoor temperature setpoint for stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
CZ
This menu is only shown if Shut Off Outdoor Temp. is enabled.
DE
This menu is only shown if Zone Setup is set to Stand Alone Control, and Dehumidifier is set to Disable. To enable the function: 1. Select Pump Stop. 2. Press the navigation wheel to confirm selection. 3. Select Enable.
To set an outdoor temperature setpoint:
2. Press the navigation wheel to confirm selection.
Default: Disable
3. Select Enable.
Setting range: Disable/Enable
Default: 17.0 ˚C
Setting range: 0.0 – 40.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again. VA LV E C LO S E
In this menu a function to close the mixing valve, when requirements are met, is enabled. To enable the function: 1. Select Valve Close. 2. Press the navigation wheel to confirm selection. 3. Select Enable.
ES FI
T. O U T D O O R D E L AY
In this menu the time delay for how long the outdoor temperature must be equal or higher than T Outdoor Setpoint before stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
FR HR
This menu is only shown if Shut Off Outdoor Temp. is enabled.
Default: Disable
To set the delay:
Setting range: Disable/Enable
1. Select T. Outdoor Delay.
4. Confirm the setting by pressing the navigation wheel again.
2. Press the navigation wheel to confirm selection.
S H U T O F F O U T D O O R T E M P.
Default: 24 h
Setting range: 0 – 24 h, 1 h increments
This menu is only shown if Pump Stop and/or Valve Close is enabled.
EE
4. Confirm the setting by pressing the navigation wheel again.
In this menu the function to stop the circulation pump and/or when to close the mixing valve, at an outdoor temperature setpoint is enabled/disabled for the zone.
DK
1. Select T Outdoor Setpoint.
HU IT
3. Set the value.
LT
4. Confirm the setting by pressing the navigation wheel again.
LV NL
To set an shut off outdoor temperature: 1. Select Shut Off Outdoor Temp..
NO
2. Press the navigation wheel to confirm selection. 3. Select Enable.
Default: Disable
Setting range: Disable/Enable
PL PT
4. Confirm the setting by pressing the navigation wheel again.
RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
97
UK CZ
S H U T O F F I N D O O R T E M P.
COOLING
In this menu the function to stop the circulation pump, and/or when to close the mixing valve, at an indoor temperature setpoint is enabled/disabled for the zone.
This menu enables access to seasonal shut off settings in the zone, while in cooling mode.
This menu is only shown if Pump Stop and/or Valve Close is enabled, and if Heating Mode is set to Outdoor + Indoor comp. for the zone.
DE DK
To set an shut off outdoor temperature: 1. Select Shut Off Outdoor Temp..
EE
2. Press the navigation wheel to confirm selection. 3. Select Enable.
ES
Default: Disable
Setting range: Disable/Enable
This menu is only shown if one of the following requirements are met: • System Type is set to 2 Pipe, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.. • System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Cooling or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.. MENU TREE*
Cooling
4. Confirm the setting by pressing the navigation wheel again.
FI
Pump Stop Valve Close
T . I N D O O R D E L AY
FR
T. Outdoor Setpoint
*
HR
In this menu the time delay for how long the indoor temperature must be equal or higher than the indoor setpoint before stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
HU
This menu is only shown if Shut Off Indoor Temp. is enabled.
In this menu a function to stop the circulation pump, when requirements are met, is enabled.
To set the delay:
To enable the function:
1. Select T. Indoor Delay.
1. Select Pump Stop.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Select Enable.
Default: 0 h
Default: Disable
Setting range: 0 – 5 h, 1 h increments
Setting range: Disable/Enable
IT LT LV
4. Confirm the setting by pressing the navigation wheel again.
T. Outdoor Delay Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
PUMP STOP
4. Confirm the setting by pressing the navigation wheel again.
NL NO PL PT RO RU SE SK 98
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK VA LV E C LO S E
In this menu a function to close the mixing valve, when requirements are met, is enabled. To enable the function: 1. Select Valve Close. 2. Press the navigation wheel to confirm selection. 3. Select Enable.
Default: Disable
Setting range: Disable/Enable
H/C Switchover This menu enables access to settings related to switching between heating and cooling in the zone. This menu is only shown if System Type is set to 4 Pipe, Z1&2 Operation Mode (for Zone 1) is set to Only Heating or Only Cooling and Z1&2 Operation Mode (for Zone 2) is set to Heating And Cooling.
Outdoor Trigger Temp. Indoor Trigger Temp. Indoor Trigger Delay.
Hysteresis
1. Select T Outdoor Setpoint. 2. Press the navigation wheel to confirm selection.
H/C SWITCHOVER
3. Select Enable.
In this menu settings for switching the zone between heating and cooling is set.
T . O U T D O O R D E L AY
In this menu the time delay for how long the outdoor temperature must be equal or higher than T Outdoor Setpoint before stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
1. Select H/C Switchover.
IT
2. Press the navigation wheel to confirm selection. 3. Select heating/cooling switchover function for the zone.
Setting range: 0 – 24 h, 1 h increments
4. Confirm the setting by pressing the navigation wheel again.
LT
• Indoor and Outdoor uses the indoor and outdoor temperatures and time delays to switch the zone between heating and cooling.
• Supply Water Temp. uses the supply water temperature and a hysteresis to switch the zone between heating and cooling.
NL
• Contact Input uses an external signal to switch the zone between heating and cooling.
NO
• Force Heating sets the zone in forced heating.
• Force Cooling sets the zone in forced cooling.
3. Set the value. Default: 24 h
HR HU
2. Press the navigation wheel to confirm selection.
FR
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
To select heating/cooling swithover function for the zone:
To set the delay: 1. Select T. Outdoor Delay.
FI
Supply Setpoint for HC Switch
*
4. Confirm the setting by pressing the navigation wheel again.
ES
Outdoor Trigger Delay
To set an outdoor temperature setpoint:
Setting range: 0.0 – 40.0 ˚C, 0.1 ˚C increments
EE
H/C Switchover
In this menu the outdoor temperature setpoint for stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
DK
H/C Switchover
T. O U T D O O R S E T P O I N T
Default: 17.0 ˚C
DE
MENU TREE*
4. Confirm the setting by pressing the navigation wheel again.
CZ
LV
PL
4. Confirm the new setting by pressing the navigation wheel again.
PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
99
UK CZ
OUTDOOR TRIGGER TEMP.
INDOOR TRIGGER TEMP.
In this menu one of the triggers (outdoor temperature) for switching the zone between heating and cooling is set.
In this menu one of the triggers (indoor temperature) for switching the zone between heating and cooling is set.
DE
N OT E ! All triggers and time delays must be met for the zone to switch heating/cooling mode.
N OT E ! All triggers and time delays must be met for the zone to switch heating/cooling mode.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
To set the outdoor trigger temperature:
To set the indoor trigger temperature:
1. Select Outdoor Trigger Temp.
1. Select Indoor Trigger Temp.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Set the value.
Default: 20.0 ˚C
Default: 22.0 ˚C
Setting range: 5.0 – 30.0 ˚C, 0.1 ˚C increments
Setting range: 5.0 – 30.0 ˚C, 0.1 ˚C increments
DK EE ES FI FR HR HU
4. Confirm the new setting by pressing the navigation wheel again.
4. Confirm the new setting by pressing the navigation wheel again.
OUTDOOR TRIGGER DELAY
INDOOR TRIGGER DELAY
In this menu one of the triggers (delay for outdoor temperature) for switching the zone between heating and cooling is set.
In this menu one of the triggers (delay for indoor temperature) for switching the zone between heating and cooling is set.
N OT E ! All triggers and time delays must be met for the zone to switch heating/cooling mode.
N OT E ! All triggers and time delays must be met for the zone to switch heating/cooling mode.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
To set the outdoor trigger delay:
To set the indoor trigger delay:
1. Select Outdoor Trigger Delay.
1. Select Indoor Trigger Delay.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Set the value.
Default: 24 h
Default: 24 h
Setting range: 1 – 48 h, 1 h increments
Setting range: 1 – 48 h, 1 h increments
IT LT LV NL NO
4. Confirm the new setting by pressing the navigation wheel again.
4. Confirm the new setting by pressing the navigation wheel again.
PL PT RO RU SE SK 100
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK SUPPLY SETPOINT FOR HC SWITCH
HYSTERESIS
In this menu the supply temperature setpoint for switching between heating and cooling is set.
In this menu the hysteresis which is used to switch between heating and cooling using Supply Setpoint for HC Switch is set.
CZ
To set the hysteresis:
DE
The zone switches to heating when the supply temperature is higher than Supply Setpoint for HC Switch. The zone switches back when the supply temperature is lower than Supply Setpoint for HC Switch - Hysteresis. The zone switches to cooling when the supply temperature is lower than Supply Setpoint for HC Switch. The zone switches back when the supply temperature is lower than Supply Setpoint for HC Switch + Hysteresis.
1. Select Hysteresis.
DK
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 2 ˚C
Setting range: 0 – 4 ˚C, 1 ˚C increments
EE
4. Confirm the new setting by pressing the navigation wheel again.
ES
N OT E ! When using this switch mode, the heating/ cooling switch is done in the heat pump/ chiller. The Move PRO controller switches the operation mode when it detects the change in supply temperture.
FI FR
No diverting valves are controlled in this mode.
HR
This menu is only shown if H/C Switchover is set to Supply Water Temp..
HU
To set the supply temperature setpoint for HC switch: 1. Select Supply Setpoint for HC Switch.
IT
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 18 ˚C
Setting range: 5 – 30 ˚C, 1 ˚C increments
LT LV
4. Confirm the new setting by pressing the navigation wheel again.
NL NO PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
101
UK Condensation Delay In this menu the condensation delay in the zone is set. If condensation is not detected (by the condensation sensor in the zone) during the time set in the delay, the condensation status (in the zone information menu) switches to No.
CZ DE
Z one 3 S ettings In this menu parameter settings for zone 3 can be set or changed. Menu tree* Zone 3 Settings Supply Temp. Settings
This menu is only shown if Condensation Sensor is enabled in the startup wizard for the zone.
DK
Heating Indoor Temp. Settings
To set the condensation delay:
EE
Comf. - ECO
1. Select Condensation Delay.
ES FI
Heating Curve
2. Press the navigation wheel to confirm selection.
Cooling Curve
3. Set the value.
Meltaway Curve (IDLE Status)
Default: 10 min
Setting range: 0 – 120 min, 1 min increments
Return Temperature Enter Stop State Conditions
4. Confirm the new setting by pressing the navigation wheel again.
Enter Idle State Conditions Enter Melting State Conditions
FR
Manual Operation Pump
HR
Mixing Valve Dehumidifier Control
HU
Seasonal Shut Off H/C Switchover Automatic Freeze Protection
IT
Condensation Delay *
LT
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
LV NL NO PL PT RO RU SE SK 102
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Supply Temp. Settings
C A L C U L AT E D S U P P LY S E T P O I N T
This menu enables access to settings related to the supply temperature in the zone.
In this menu the calculated supply setpoint for the zone can be overidden. This temperature is used as setpoint for the supply temperature.
CZ
To override the calculated supply setpoint:
DE
MENU TREE* Supply Temp. Settings Heating Cooling
2. Press the navigation wheel to confirm selection.
Calculated Supply Setpoint
3. Select Manual.
Melting Supply Setpoint
4. Set the override value.
Heating Curve Meltaway
IDLE Supply Setpoint Min. Supply Temp. (IDLE Status) Max. Supply Temp. (IDLE Status) *
1. Select Calculated supply setpoint.
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
5. Confirm the new setting by pressing the navigation wheel again. H E AT I N G M I N . S U P P LY T E M P.
This menu enables access to settings related to the heating supply temperature in the zone.
1. Select Heating Min. supply temp.
• System Type is set to 4 Pipe, Z3 Operation Mode is set to Only Heating or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone. MENU TREE
Heating Calculated Supply Setpoint
FI FR HR
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 15.0 ˚C
Setting range: 5.0 – 35.0 ˚C (or max. supply temp), 0.1 ˚C increments
HU IT
4. Confirm the new setting by pressing the navigation wheel again. H E AT I N G M A X . S U P P LY T E M P.
LT
In this menu the maximum allowed supply temperature for the zone can be set. The supply temperature is not allowed to rise above this value.
LV
To set the maximum allowed supply temperature:
Heating Min. Supply Temp.
1. Select Heating Max. supply temp.
Heating Max. Supply Temp.
2. Press the navigation wheel to confirm selection.
Deviation alarm limit
3. Set the value.
Deviation alarm delay
ES
In this menu the minimum allowed supply temperature for the zone can be set. The supply temperature is not allowed to fall below this value. To set the minimum allowed supply temperature:
• System Type is set to 2 Pipe, Indoor Cooling Only is set to No, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
EE
Setting range: -5.0 – 70.0 ˚C, 0.1 ˚C increments
HEATING
This menu is only shown if one of the following requirements are met:
DK
Default: 70.0 ˚C
Setting range: 5.0 (or min. supply temp) – 70.0 ˚C, 0.1 ˚C increments
NL NO PL
4. Confirm the new setting by pressing the navigation wheel again.
PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
103
UK D E V I AT I O N A L A R M L I M I T
In this menu the deviation alarm limit for the supply temperature in the zone is set. If the difference between the measured and the calculated supply temperatures are higher than the set limit during the time set in Deviation alarm delay, the alarm is triggered.
CZ DE
To set the deviation alarm limit:
DK
1. Select Deviation alarm limit. 2. Press the navigation wheel to confirm selection.
EE
3. Set the value.
ES
Default: 10.0 ˚C
Setting range: 0.0 – 50.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
FI
COOLING This menu enables access to settings related to the cooling supply temperature in the zone. This menu is only shown if one of the following requirements are met: • System Type is set to 2 Pipe, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone. • System Type is set to 4 Pipe, Z3 Operation Mode is set to Only Cooling or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone. MENU TREE
Cooling Calculated Supply Setpoint
D E V I AT I O N A L A R M D E L AY
Cooling Min. Supply Temp.
In this menu the deviation alarm delay for the deviation alarm limit in the zone is set. If the difference between the measured and the calculated supply temperatures are higher than Deviation alarm limit during the set delay, the alarm is triggered.
FR HR
To set the deviation alarm delay: 1. Select Deviation alarm delay.
HU
2. Press the navigation wheel to confirm selection. 3. Set the value.
IT LT
Dew Point Margin Dew Point Offset C A L C U L AT E D S U P P LY S E T P O I N T
In this menu the calculated supply setpoint for the zone can be overidden. This temperature is used as setpoint for the supply temperature. To override the calculated supply setpoint:
Default: 5 min
1. Select Calculated supply setpoint.
Setting range: 0 – 30 min, 1 min increments
2. Press the navigation wheel to confirm selection.
4. Confirm the new setting by pressing the navigation wheel again.
LV
Cooling Max. Supply Temp.
3. Select Manual. 4. Set the override value.
Setting range: -5.0 – 70.0 ˚C, 0.1 ˚C increments
5. Confirm the new setting by pressing the navigation wheel again.
NL NO PL PT RO RU SE SK 104
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK C O O L I N G M I N . S U P P LY T E M P.
DEW POINT MARGIN
In this menu the minimum allowed supply temperature for the zone can be set. The supply temperature is not allowed to fall below this value.
In this menu the dew point margin for the zone can be set. The dew point temperature is calculated using the current room temperature and relative humidity.
To set the minimum allowed supply temperature:
When the calculated supply temperature is lower than the dew point temperature + Dew Point Offset this value is added to the calculated supply temperature.
DE
To set the dew point margin:
DK
1. Select Cooling Min. supply temp. 2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 8.0 ˚C
Setting range: 5.0 – 40.0 ˚C (or max. supply temp), 0.1 ˚C increments
1. Select Dew Point Margin.
3. Set the value.
Default: 4.0 ˚C
Setting range: -1.0 – 10.0 ˚C
C O O L I N G M A X . S U P P LY T E M P.
4. Confirm the new setting by pressing the navigation wheel again.
To set the maximum allowed supply temperature: 1. Select Cooling Max. supply temp. 2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 25.0 ˚C
Setting range: 5.0 (or min. supply temp) – 40.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
EE
2. Press the navigation wheel to confirm selection.
4. Confirm the new setting by pressing the navigation wheel again. In this menu the maximum allowed supply temperature for the zone can be set. The supply temperature is not allowed to rise above this value.
CZ
ES FI
DEW POINT OFFSET
FR
In this menu the dew point offset for the zone can be set. The dew point temperature is calculated using the current room temperature and relative humidity.
HR
The offset is used together with the dew point temperature to decide when to increase the calculated supply temperature with the value set in Dew Point Margin.
HU
To set the dew point offset:
IT
1. Select Dew Point Offset. 2. Press the navigation wheel to confirm selection.
LT
3. Set the value.
Default: 1.0 ˚C
Setting range: 0.0 – 4.0 ˚C
LV
4. Confirm the new setting by pressing the navigation wheel again.
NL NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
105
UK CALCULATED SUPPLY SETPOINT
HEATING CURVE MELTAWAY
CZ
In this menu the calculated supply setpoint for the zone can be overidden. This temperature is used as setpoint for the supply temperature.
In this menu a heating curve for the zone, while meltaway status is IDLE, can be enabled.
DE
This menu is only shown if Zone Setup is set to Meltaway for the zone.
DK
To override the calculated supply setpoint: 1. Select Calculated supply setpoint. 2. Press the navigation wheel to confirm selection.
EE
3. Select Manual.
ES
This menu is only shown if Zone Setup is set to Meltaway for the zone. To enable the heating curve: 1. Select Heating Curve. 2. Press the navigation wheel to confirm selection. 3. Select Enable.
4. Set the override value.
4. Confirm the new setting by pressing the navigation wheel again.
IDLE SUPPLY SETPOINT
Setting range: -5.0 – 70.0 ˚C, 0.1 ˚C increments
5. Confirm the new setting by pressing the navigation wheel again. MELTING SUPPLY SETPOINT
In this menu a setpoint for the zone, while meltaway status is IDLE, can be set. This temperature is used as setpoint for the supply temperature.
FR
In this menu the supply temperature setpoint for meltaway in the zone is set.
This menu is only shown if Zone Setup is set to Meltaway for the zone.
HR
This menu is only shown if Zone Setup is set to Meltaway for the zone.
To set the IDLE supply setpoint:
To set the melting supply temperature setpoint:
2. Press the navigation wheel to confirm selection.
1. Select Supply Setpoint.
3. Set the override value.
2. Press the navigation wheel to confirm selection.
Default: 8.0 ˚C
3. Set the value.
Setting range: 1.0 – 15.0 ˚C, 0.1 ˚C increments
Default: 35 ˚C
Setting range: 5.0 – 35.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
FI
HU IT LT
1. Select IDLE supply setpoint.
4. Confirm the new setting by pressing the navigation wheel again.
LV NL NO PL PT RO RU SE SK 106
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK MIN. SUPPLY TEMP. (IDLE STATUS)
Heating Indoor Temp. Settings
In this menu the minimum available supply temperature for the zone, while meltaway status is IDLE, can be set. The supply temperature is not allowed to fall below this value.
This menu enables access to settings related to the room temperature sensor in the zone.
CZ
This menu and its submenus are only shown if Heating Mode is set to Outdoor + Indoor comp..
DE
This menu is only shown if Zone Setup is set to Meltaway for the zone.
MENU TREE*
DK
Heating Indoor Temp. Settings
To set the minimum allowed supply temperature: 1. Select Min. supply temp.
Indoor Setpoint
2. Press the navigation wheel to confirm selection.
Calculated Indoor Setpoint
3. Set the value.
ECO-Comf. Status
Default: 5.0 ˚C
Indoor Setpoint Influence (Lower)
Setting range: 0.0 – 25.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again. MAX. SUPPLY TEMP. (IDLE STATUS) In this menu the maximum available supply temperature for the zone, while meltaway status is IDLE, can be set. The supply temperature is not allowed to rise above this value. This menu is only shown if Zone Setup is set to Meltaway for the zone.
ES
Indoor Setpoint Influence (Upper) *
FI
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
FR
INDOOR SETPOINT In this menu the indoor temperature setpoint for the zone is set.
HR
This information is only shown if Zone Setup is set to Stand Alone Control for the zone.
HU
To set the indoor temperature setpoint:
To set the minimum allowed supply temperature:
1. Select Indoor Setpoint.
1. Select Max. supply temp.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Set the value.
Default: 21.0 ˚C
Default: 15.0 ˚C
Setting range: 5.0 – 35.0 ˚C, 0.1 ˚C increments
Setting range: 0.0 – 70.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
4. Confirm the new setting by pressing the navigation wheel again.
EE
IT LT LV
CALCULATED INDOOR SETPOINT
NL
This menu shows the calculated indoor setpoint for the zone.
NO
This information is only shown if Zone Setup is set to Stand Alone Control and if ECO-Comf mode is set to ECO for the zone.
PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
107
UK CZ
ECO-COMF STATUS
INDOOR SETPOINT INFLUENCE (UPPER)
This menu shows if the zone is set in ECO mode.
In this menu the indoor setpoint influence (upper) is set. If the measured indoor temperature is lower than the indoor temperature setpoint, the supply temperature sepoint will be increased using this value.
This information is only shown if ECO-Comf mode is set to ECO for the zone.
DE
INDOOR SETPOINT INFLUENCE (LOWER) In this menu the indoor setpoint influence (lower) is set. If the measured indoor temperature is higher than the indoor temperature setpoint, the supply temperature sepoint will be lowered using this value.
DK EE
This menu is used to to keep the measured room temperature as close as possible to the indoor temperature setpoint.
ES
N OT E ! If the value is set too high it can lead to the system being unstable and the room temperature will start fluctuating.
FI FR HR
N OT E ! If the value is set too high it can lead to the system being unstable and the room temperature will start fluctuating. To set the indoor setpoint influence (upper): 1. Select Indoor Setpoint Influence (Upper). 2. Press the navigation wheel to confirm selection. 3. Set the value.
To set the indoor setpoint influence (lower):
Default: 4.0 ˚C
1. Select Indoor Setpoint Influence (Lower).
Setting range: 0.0 – 10.0 ˚C, 0.1 ˚C increments
2. Press the navigation wheel to confirm selection.
4. Confirm the new setting by pressing the navigation wheel again.
3. Set the value.
HU
This menu is used to to keep the measured room temperature as close as possible to the indoor temperature setpoint.
Default: 4.0 ˚C
Setting range: 0.0 – 10.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
IT LT LV NL NO PL PT RO RU SE SK 108
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Comf. - ECO
To edit/create the ECO-Comf Schedule:
This menu enables access to settings related to the controller Comfort/ECO modes.
1. Select ECO-Comf Schedule.
This menu and its submenus are only shown if Zone Setup is set to Stand Alone Control and if Heating Mode is set to Outdoor + Indoor comp. for the zone.
CZ
2. Press the navigation wheel to confirm selection.
The current schedule is showing.
DE
3. Select a day. 4. Press the navigation wheel to confirm selection.
MENU TREE
Comf. - ECO ECO Setback ECO-Comf Status ECO-Comf Schedule
ECO SETBACK In this menu the ECO setback temperature is set. The parameter reduces the current setpoint with the set value. If the setback is set to 0 the zone will resume its normal operation, even if it is set in ECO mode. To set the ECO setback value: 1. Select ECO Setback. 2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 4.0 ˚C
Setting range: 0.0 – 10.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again. ECO-COMF STATUS This menu shows if the zone is set in ECO or Comf (comfort) mode. ECO-COMF SCHEDULE In this menu a schedule for switching between Comfort and ECO mode can be created. The default schedule is set to Comfort mode 24h a day, 7 days a week.
W arning ! Ensure that different schedules cannot enable ECO and Comf and the same time. This may cause an error where the controller must be reset to factory default values.
DK
All current schedule settings are shown, each line representing a switch between Comfort and ECO mode. If entering the menu for the first time only one line is present, showing Comf starting at 00:00 every day of the week.
EE ES
5. Select an existing line to edit or 00:00 Add new to add a new setting.
FI
6. Select wether to edit the hours, minutes, mode or day of the week. HOURS: Set at which hour the mode will start and press the navigation wheel to confirm selection.
FR
MINUTES: Set at which minte of the hour the mode will start and press the navigation wheel to confirm selection.
HR HU
MODE: Select a mode which should start at the set time and press the navigation wheel to confirm selection. Select between Comf, ECO and Delete switch time. Delete switch time erases the current line when selecting OK and pressing the navigation wheel.
IT LT
DAY OF THE WEEK:
Select which days of the week, at the set time the selected mode should start.
LV
7. Select OK at the end of the line, when done, and press the navigation wheel to confirm selection.
NL
A new line has been added to the schedule.
NO
8. Redo steps 5 and 6 until the schedule is complete. 9. Press the back button on the controller to exit the schedule setup.
PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
109
UK Heating Curve
OFFSET
CZ
This menu enables access to heating curve settings for the zone. Settings such as the slope (Setting) and offset of the heating curve.
In this menu the the heating curve can be offset. The offset can be used for temporary changes to the heating curve.
DE
This menu is only shown if one of the following requirements are met:
To offset the heating curve:
DK
• System Type is set to 2 Pipe, Indoor Cooling Only is set to No, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
EE
• System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
ES
MENU TREE
FI
1. Select Offset. 2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 0
Setting range: -8 – 8, 1 increments
4. Confirm the new setting by pressing the navigation wheel again. HEATING CURVE
Heating Curve Setting
This menu shows the heating curve, and max/min supply temperature limits, for the zone.
Offset
FR
Heating Curve
SETTING
HR
In this menu the slope of the heating curve is selected. To select a heating curve:
HU
1. Select Setting. 2. Press the navigation wheel to confirm selection.
IT
3. Set the value.
LT
Default: 0.9
Setting range: 0.1 – 1.6, 0.1 increments
4. Confirm the new setting by pressing the navigation wheel again.
LV NL NO PL PT RO RU SE SK 110
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Cooling Curve
OFFSET
This menu enables access to cooling curve settings for the zone. Settings such as the slope (Setting) and offset of the heating curve.
In this menu the the heating curve can be offset. The offset can be used for temporary changes to the heating curve.
CZ
This menu is only shown if one of the following requirements are met:
To offset the heating curve:
DE
• System Type is set to 2 Pipe and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone. • System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Cooling or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone. MENU TREE
1. Select Offset.
DK
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 0
Setting range: -8 – 8, 1 increments
EE
4. Confirm the new setting by pressing the navigation wheel again.
ES
COOLING CURVE
Cooling Curve Setting
FI
This menu shows the cooling curve, and max/min supply temperature limits, for the zone.
Offset
FR
Cooling Curve
SETTING
HR
In this menu the slope of the heating curve is selected. To select a heating curve:
HU
1. Select Setting. 2. Press the navigation wheel to confirm selection.
IT
3. Set the value.
Default: 0.2
Setting range: 0.1 – 1.6, 0.1 increments
LT
4. Confirm the new setting by pressing the navigation wheel again.
LV NL NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
111
UK Meltaway Curve (IDLE Status)
OFFSET In this menu the the meltaway heating curve can be offset. The offset can be used for temporary changes to the heating curve.
DE
This menu enables access to meltaway heating curve settings for the zone while in IDLE status. Settings such as the slope (Setting) and offset of the meltaway heating curve.
DK
This menu is only shown if Zone Setup is set to Meltaway and if Heating Curve Meltaway is enabled for the zone.
CZ
Meltaway Curve (IDLE Status) Setting
ES
Offset Heating Curve
FI
SETTING In this menu the slope of the meltaway heating curve is selected.
FR
1. Select Offset. 2. Press the navigation wheel to confirm selection. 3. Set the value.
MENU TREE
EE
To offset the meltaway heating curve:
Default: 0
Setting range: -8 – 8, 1 increments
4. Confirm the new setting by pressing the navigation wheel again. HEATING CURVE This menu shows the meltaway heating curve, and max/ min supply temperature limits, for the zone.
To select a meltaway heating curve:
HR
1. Select Setting. 2. Press the navigation wheel to confirm selection.
HU
3. Set the value.
IT
Default: 0.9
Setting range: 0.1 – 1.6, 0.1 increments
4. Confirm the new setting by pressing the navigation wheel again.
LT LV NL NO PL PT RO RU SE SK 112
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Return Temperature
Enter Stop State Conditions
This menu enables access to settings related to the return temperature sensor.
This menu enables access to parameters deciding when to switch the meltaway state in the zone between IDLE and STOP.
CZ
The zone switches from IDLE to STOP state when the measured outdoor temperature is higher than the value set in Outdoor Temperature, for the number of days set in Delay (days).
DE
This menu is only shown if Zone Setup is set to Meltaway for the zone. MENU TREE Return Temperature Max. Supply-Return Diff.
MAX. SUPPLY-RETURN DIFF. In this menu the maximum difference allowed between the supply and return temperature is set.
This menu is only shown if Zone Setup is set to Meltaway for the zone.
Enter Stop State Conditions
ES Outdoor Temperature Delay (days)
1. Select Max. Supply-Return Diff.. 2. Press the navigation wheel to confirm selection.
OUTDOOR TEMPERATURE
3. Set the value.
In this menu the outdoor temperature, used to switch meltaway state between IDLE and STOP, is set.
Default: 20 ˚C
Setting range: 0.0 – 80.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
EE
MENU TREE
To set the return temperature setpoint:
DK
FI FR
To set the outdoor temperature:
HR
1. Select Outdoor Temperature. 2. Press the navigation wheel to confirm selection.
HU
3. Set the value.
Default: 10.0 ˚C
Setting range: 0.0 – 15.0 ˚C, 0.1 ˚C increments
IT
4. Confirm the new setting by pressing the navigation wheel again.
LT
DELAY (DAYS) In this menu the number of delay days, used to switch meltaway state between IDLE and STOP, is set.
LV
To set the delay:
NL
1. Select Delay (days). 2. Press the navigation wheel to confirm selection.
NO
3. Set the value.
Default: 2 days
Setting range: 0 – 5 days, 1 day increments
PL
4. Confirm the new setting by pressing the navigation wheel again.
PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
113
UK CZ DE DK EE ES
Enter Idle State Conditions
DELAY (HOURS)
This menu enables access to parameters used when to switch the meltaway state in the zone to and from IDLE.
In this menu the number of delay hours, used to switch meltaway state from STOP to IDLE, is set.
The zone switches from STOP to IDLE state when the measured outdoor temperature is lower than the value set in Outdoor Temperature, for the number of hours set in Delay (hours).
To set the delay:
The zone switches from MELTING to IDLE state when no moisture has been detected (for the number of days set in Delay Surface Dry), when the outdoor temperature is higher than the value set in Outdoor Temperature, and when the ground temperature is higher than Enter Melting State Conditions > Ground Temperature Limit.
3. Set the value.
This menu is only shown if Zone Setup is set to Meltaway for the zone.
FI
MENU TREE
FR
Delay (hours) Delay Surface Dry
IT
Default: 1 hour
Setting range: 0 – 24 hours, 1 hour increments
4. Confirm the new setting by pressing the navigation wheel again. DELAY SURFACE DRY In this menu the number of delay days, used to switch meltaway state from MELTING to IDLE, is set.
1. Select Delay Surface Dry. Outdoor Temperature
HU
2. Press the navigation wheel to confirm selection.
To set the dry surface delay:
Enter Idle State Conditions
HR
1. Select Delay (hours).
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 0 days
OUTDOOR TEMPERATURE
Setting range: 0 – 2 days, 1 day increments
In this menu the outdoor temperature, used to switch meltaway state from STOP or MELTING to IDLE, is set.
4. Confirm the new setting by pressing the navigation wheel again.
To set the outdoor temperature: 1. Select Outdoor Temperature.
LT
2. Press the navigation wheel to confirm selection. 3. Set the value.
LV NL
Default: 5.0 ˚C
Setting range: 0.0 – 15.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
NO PL PT RO RU SE SK 114
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Enter Melting State Conditions
GROUND TEMPERATURE LIMIT
This menu enables access to parameters used when to switch the meltaway state in the zone to and from MELTING. When entering MELTING state the zone stays in that condition until the min limit set in Min. Time in Melting is met.
In this menu the ground temperature limit, used to switch meltaway state between IDLE to MELTING , is set.
CZ
To set the ground temperature limit:
DE
The zone switches from IDLE to MELTING state when one of the following scenarios are met: 1. No ground moisture is detected and the measured ground temperature is lower than than the set limit in Ground Temperature Limit. 2. No ground moisture is detected and the measured outdoor temperature is lower than than the set limit in Outdoor Temperature Low Limit. The zone switches from PROTECTION to MELTING when the primary return sensor measures a supply temperature that is higher than PRIMARY RETURN TEMP. HIGH, set in Automatic Freeze Protection . This menu is only shown if Zone Setup is set to Meltaway for the zone.
1. Select Ground Temperature Limit.
DK
2. Press the navigation wheel to confirm selection. 3. Select Low Limit.
EE
4. Press the navigation wheel to confirm selection. 5. Set the value.
Default: 2 ˚C
Setting range: 0 – 10 ˚C, 1 ˚C increments
ES
6. Confirm the new setting by pressing the navigation wheel again.
FI
OUTDOOR TEMP. OFFSET
FR
In this menu the outdoor temperature offset, used to switch meltaway state from IDLE to MELTING, is set. To set the outdoor temperature offset:
MENU TREE
HR
1. Select Outdoor Temp. Offset.
Enter Melting State Conditions
2. Press the navigation wheel to confirm selection. Ground Temperature Limit
3. Set the value.
Outdoor Temp. Offset
Default: 1 ˚C
Outdoor Temperature Low Limit
Setting range: -5 – 5 ˚C, 1 ˚C increments
Min. Time in Melting
4. Confirm the new setting by pressing the navigation wheel again.
HU IT LT LV NL NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
115
UK CZ DE
OUTDOOR TEMPERATURE LOW LIMIT
Manual Operation
In this menu the lower outdoor temperature limit, used to switch meltaway state from IDLE to MELTING, is set.
This menu enables access to manual operation mode in the zone.
To set the lower outdoor temperature limit:
When manual operation mode is activated, access to manual control (override) of the circulation pump and mixing valve is enabled.
1. Select Outdoor Temperature Low Limit. 2. Press the navigation wheel to confirm selection.
DK
3. Set the value.
EE
Default: 1 ˚C
Setting range: -5 – 5 ˚C, 1 ˚C increments
Menu tree* Manual Operation Manual Mode Pump
4. Confirm the new setting by pressing the navigation wheel again.
ES
MIN. TIME IN MELTING In this menu the minimum number of hours the zone can be in meltaway state MELTING, is set.
FI
To set the minimum time:
FR
1. Select Min. Time in Melting. 2. Press the navigation wheel to confirm selection.
HR
3. Set the value.
HU
Default: 2 hour
Setting range: 0 – 10 hours, 1 hour increments
4. Confirm the new setting by pressing the navigation wheel again.
IT LT
Mixing valve *
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
To activate manual operation mode: 1. Select Manual Mode. 2. Press the navigation wheel to confirm selection. 3. Select On. 4. Confirm the new setting by pressing the navigation wheel again. PUMP In this menu the pump can be overidden and turned on or off manually. This menu is only shown if Zone Setup is set to Stand Alone Control or Meltaway, Dehumidifier is set to Disable, and Manual Mode is set to On. To override the circulation pump operation: 1. Select Pump.
LV
2. Press the navigation wheel to confirm selection. 3. Select Manual.
NL
4. Select On.
NO
Default: Off
Setting range: Off/On
5. Confirm the new setting by pressing the navigation wheel again.
PL PT RO RU SE SK 116
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK MIXING VALVE
Pump
In this menu the mixing valve can be overriden opened or closed manually.
This menu enables access to pump settings in the zone.
CZ
This menu is only shown if Zone Setup is set to Stand Alone Control or Meltaway, and if Dehumidifier is disabled for the zone.
DE
This menu is only shown if Manual Mode is set to On. To override the mixing valve setting: 1. Select Mixing valve.
MENU TREE*
Pump Exercise
3. Select Manual.
Exercise Day of the Week
4. Set the override value.
Default: 0 %
Setting range: 0 – 100 %, 1 % increments.
5. Confirm the new setting by pressing the navigation wheel again.
DK
Pump
2. Press the navigation wheel to confirm selection.
EE
Exercise Hour Exercise Min *
ES
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
PUMP EXERCISE
FI
In this menu pump exercise can be activated. To activate pump exercise:
FR
1. Select Pump Exercise. 2. Press the navigation wheel to confirm selection.
HR
3. Select Pump Exercise.
Default: No Exercise
Setting range: No Exercise/Pump Exercise
HU
4. Confirm the new setting by pressing the navigation wheel again.
IT
EXERCISE DAY OF THE WEEK In this menu the day of the week for pump exercise is set.
LT
This menu is only shown if Pump Exercise is set to Pump Exercise.
LV
To select a day of the week for pump exercise:
NL
1. Select Exercise Day of the Week. 2. Press the navigation wheel to confirm selection.
NO
3. Select a day.
Setting range: Monday – Sunday
4. Confirm the setting by pressing the navigation wheel again.
PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
117
UK EXERCISE HOUR
Mixing Valve
CZ
In this menu the hour of the day for pump exercise is set.
This menu enables access to mixing valve settings in the zone.
DE
This menu is only shown if Pump Exercise is set to Pump Exercise.
MENU TREE* Mixing Valve
To select an hour of the day for pump exercise:
DK EE
Heating
1. Select Exercise Hour.
Cooling
2. Press the navigation wheel to confirm selection.
P-area I-time
3. Set the value.
ES
Default: 8 h
Setting range: 0 – 23 h, 1 h increments
4. Confirm the setting by pressing the navigation wheel again.
FI FR HR
In this menu the minute of the hour for pump exercise is set.
This menu is only shown if one of the following requirements are met:
This menu is only shown if Pump Exercise is set to Pump Exercise.
• System Type is set to 2 Pipe, Indoor Cooling Only is set to No, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
2. Press the navigation wheel to confirm selection. 3. Set the value.
LT
HEATING This menu enables access to mixing valve settings in the zone while in heating mode.
1. Select Exercise Min.
IT
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
EXERCISE MIN
To select a minute of the hour for pump exercise:
HU
Actuator running time *
Default: 0 min
Setting range: 0 – 59 min, 1 min increments
4. Confirm the setting by pressing the navigation wheel again.
• System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone. MENU TREE
Heating P-area I-time Actuator running time
LV NL NO PL PT RO RU SE SK 118
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK P-AREA
In this menu the P-area for the mixing valve regulation is set. To set the P-area: 1. Select P-area. 2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 140.0 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
COOLING This menu enables access to mixing valve settings in the zone while in cooling mode.
CZ
This menu is only shown if one of the following requirements are met:
DE
• System Type is set to 2 Pipe and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
DK
4. Confirm the setting by pressing the navigation wheel again.
• System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Cooling or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
I-TIME
MENU TREE
In this menu the I-time for the mixing valve regulation is set.
1. Select I-time.
Actuator running time
2. Press the navigation wheel to confirm selection.
P-AREA
3. Set the value.
In this menu the P-area for the mixing valve regulation is set.
Setting range: 5 – 300 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
Default: 200.0 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
1. Select Actuator running time.
4. Confirm the setting by pressing the navigation wheel again.
2. Press the navigation wheel to confirm selection.
I-TIME
3. Set the value.
In this menu the I-time for the mixing valve regulation is set.
Setting range: 0 – 500 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
HU
2. Press the navigation wheel to confirm selection.
In this menu the actuator running time for the mixing valve regulation is set.
Default: 120 seconds
HR
1. Select P-area.
3. Set the value.
FR
To set the P-area:
A C T U AT O R R U N N I N G T I M E
To set the actuator running time:
FI
P-area I-time
Default: 35 seconds
ES
Cooling
To set the I-time:
EE
IT LT LV NL
To set the I-time: 1. Select I-time.
NO
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 50 seconds
Setting range: 5 – 300 seconds, 1 second increments
PL PT
4. Confirm the setting by pressing the navigation wheel again.
RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
119
UK A C T U AT O R R U N N I N G T I M E
In this menu the actuator running time for the mixing valve regulation is set.
CZ
To set the actuator running time:
DE DK EE
This menu is only shown if Zone Setup is set to Meltaway for the zone.
2. Press the navigation wheel to confirm selection.
To set the I-time:
3. Set the value.
1. Select I-time.
Default: 60 seconds
2. Press the navigation wheel to confirm selection.
Setting range: 0 – 500 seconds, 1 second increments
3. Set the value.
P-AREA In this menu the P-area for the mixing valve regulation is set.
FI
This menu is only shown if Zone Setup is set to Meltaway for the zone.
FR
To set the P-area:
HR HU IT
Default: 50 seconds
Setting range: 5 – 300 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again. ACTUATOR RUNNING TIME In this menu the actuator running time for the mixing valve regulation is set.
1. Select P-area.
This menu is only shown if Zone Setup is set to Meltaway for the zone.
2. Press the navigation wheel to confirm selection.
To set the actuator running time:
3. Set the value.
1. Select Actuator running time.
Default: 200.0 ˚C
2. Press the navigation wheel to confirm selection.
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
3. Set the value.
4. Confirm the setting by pressing the navigation wheel again.
LT
In this menu the I-time for the mixing valve regulation is set.
1. Select Actuator running time.
4. Confirm the setting by pressing the navigation wheel again.
ES
I-TIME
Default: 60 seconds
Setting range: 0 – 500 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
LV NL NO PL PT RO RU SE SK 120
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Dehumidifier Control
Seasonal Shut Off
This menu enables access to dehumidifier settings in the zone.
This menu enables access to seasonal shut off settings in the zone.
CZ
This menu is only shown if Dehumidifier Control is enabled in the startup wizard for the zone.
This menu is only shown if Zone Setup is set to Stand Alone Control or Smatrix Base PRO.
DE
MENU TREE
MENU TREE*
Dehumidifier Control
DK
Seasonal Shut Off Dew Point Margin
Heating
Dead Zone
Cooling
DEW POINT MARGIN In this menu the dew point margin, for controlling the dehumidifier, in the zone can be set. The dehumidifier is started when the supply temperature is equal or lower than the dew point temperature + dew point margin. The dehumidifier is shut off when the supply temperature is equal or higher than the dew point temperature + dew point margin + deadzone temperature. To set the dew point margin:
*
ES
HEATING This menu enables access to seasonal shut off settings in the zone, while in heating mode.
Default: 4.0 ˚C
MENU TREE*
Setting range: -1.0 – 10.0 ˚C
HU IT
Pump Stop
DEAD ZONE
Shut Off Outdoor Temp.
In this menu the dead zone (hysteresis) for when to shut off the dehumidifier in the zone can be set.
T. Outdoor Setpoint
LT
Valve Close
LV
T. Outdoor Delay Shut Off Indoor Temp.
To set the dead zone:
2. Press the navigation wheel to confirm selection.
HR
Heating
4. Confirm the new setting by pressing the navigation wheel again.
1. Select Dead Zone.
FR
• System Type is set to 2 Pipe, Indoor Cooling Only is set to No, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
3. Set the value.
2. Press the navigation wheel to confirm selection.
FI
This menu is only shown if one of the following requirements are met:
• System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
1. Select Dew Point Margin.
EE
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
NL
T. Indoor Delay *
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
NO
3. Set the value.
Default: 2.0 ˚C
Setting range: 1.0 – 5.0 ˚C
PL
4. Confirm the new setting by pressing the navigation wheel again.
PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
121
UK PUMP STOP
T. O U T D O O R S E T P O I N T
CZ
In this menu a function to stop the circulation pump, when requirements are met, is enabled.
DE
This menu is only shown if Zone Setup is set to Stand Alone Control, and Dehumidifier is set to Disable.
In this menu the outdoor temperature setpoint for stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
To enable the function: 1. Select Pump Stop.
DK
2. Press the navigation wheel to confirm selection. 3. Select Enable.
EE ES
Setting range: Disable/Enable
Default: 17.0 ˚C
Setting range: 0.0 – 40.0 ˚C, 0.1 ˚C increments
To enable the function: 1. Select Valve Close. 2. Press the navigation wheel to confirm selection. 3. Select Enable.
HU
2. Press the navigation wheel to confirm selection. 3. Select Enable.
VA LV E C LO S E
HR
1. Select T Outdoor Setpoint.
Default: Disable
In this menu a function to close the mixing valve, when requirements are met, is enabled.
FR
To set an outdoor temperature setpoint:
4. Confirm the setting by pressing the navigation wheel again.
FI
This menu is only shown if Shut Off Outdoor Temp. is enabled.
4. Confirm the setting by pressing the navigation wheel again. T. O U T D O O R D E L AY
In this menu the time delay for how long the outdoor temperature must be equal or higher than T Outdoor Setpoint before stopping the circulation pump, and/or closing the mixing valve, in the zone is set. This menu is only shown if Shut Off Outdoor Temp. is enabled.
Default: Disable
To set the delay:
Setting range: Disable/Enable
1. Select T. Outdoor Delay.
IT
4. Confirm the setting by pressing the navigation wheel again.
2. Press the navigation wheel to confirm selection.
LT
S H U T O F F O U T D O O R T E M P.
Default: 24 h
Setting range: 0 – 24 h, 1 h increments
In this menu the function to stop the circulation pump and/or when to close the mixing valve, at an outdoor temperature setpoint is enabled/disabled for the zone.
LV
This menu is only shown if Pump Stop and/or Valve Close is enabled.
NL
3. Set the value.
4. Confirm the setting by pressing the navigation wheel again.
To set an shut off outdoor temperature: 1. Select Shut Off Outdoor Temp..
NO
2. Press the navigation wheel to confirm selection. 3. Select Enable.
PL PT
Default: Disable
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation wheel again.
RO RU SE SK 122
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK S H U T O F F I N D O O R T E M P.
COOLING
In this menu the function to stop the circulation pump, and/or when to close the mixing valve, at an indoor temperature setpoint is enabled/disabled for the zone.
This menu enables access to seasonal shut off settings in the zone, while in cooling mode.
CZ
This menu is only shown if one of the following requirements are met:
DE
• System Type is set to 2 Pipe, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone..
DK
This menu is only shown if Pump Stop and/or Valve Close is enabled, and if Heating Mode is set to Outdoor + Indoor comp. for the zone. To set an shut off outdoor temperature: 1. Select Shut Off Outdoor Temp.. 2. Press the navigation wheel to confirm selection. 3. Select Enable.
Default: Disable
Setting range: Disable/Enable
• System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Cooling or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone..
ES
MENU TREE*
Cooling
4. Confirm the setting by pressing the navigation wheel again.
FI
Pump Stop Valve Close
T . I N D O O R D E L AY
T. Outdoor Setpoint
In this menu the time delay for how long the indoor temperature must be equal or higher than the indoor setpoint before stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
*
This menu is only shown if Shut Off Indoor Temp. is enabled.
In this menu a function to stop the circulation pump, when requirements are met, is enabled.
To set the delay:
To enable the function:
1. Select T. Indoor Delay.
1. Select Pump Stop.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Select Enable.
Default: 0 h
Default: Disable
Setting range: 0 – 5 h, 1 h increments
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation wheel again.
EE
FR
T. Outdoor Delay Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
HR
PUMP STOP
HU IT LT LV
4. Confirm the setting by pressing the navigation wheel again.
NL NO PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
123
UK VA LV E C LO S E
In this menu a function to close the mixing valve, when requirements are met, is enabled.
CZ
To enable the function:
DE
1. Select Valve Close. 2. Press the navigation wheel to confirm selection.
DK
3. Select Enable.
EE
Default: Disable
Setting range: Disable/Enable
H/C Switchover This menu enables access to settings related to switching between heating and cooling in the zone. This menu is only shown if System Type is set to 4 Pipe and Z3 Operation Mode is set to Heating And Cooling. MENU TREE* H/C Switchover H/C Switchover Outdoor Trigger Temp.
4. Confirm the setting by pressing the navigation wheel again.
ES
Outdoor Trigger Delay Indoor Trigger Temp.
T. O U T D O O R S E T P O I N T
Indoor Trigger Delay.
In this menu the outdoor temperature setpoint for stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
FI
To set an outdoor temperature setpoint:
FR
1. Select T Outdoor Setpoint. 2. Press the navigation wheel to confirm selection.
HR
3. Select Enable.
HU
Default: 17.0 ˚C
Setting range: 0.0 – 40.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
IT
T . O U T D O O R D E L AY
In this menu the time delay for how long the outdoor temperature must be equal or higher than T Outdoor Setpoint before stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
LT LV
Supply Setpoint for HC Switch Hysteresis *
H/C SWITCHOVER In this menu settings for switching the zone between heating and cooling is set. To select heating/cooling swithover function for the zone: 1. Select H/C Switchover. 2. Press the navigation wheel to confirm selection. 3. Select heating/cooling switchover function for the zone.
• Indoor and Outdoor uses the indoor and outdoor temperatures and time delays to switch the zone between heating and cooling.
• Supply Water Temp. uses the supply water temperature and a hysteresis to switch the zone between heating and cooling.
• Contact Input uses an external signal to switch the zone between heating and cooling.
• Force Heating sets the zone in forced heating.
• Force Cooling sets the zone in forced cooling.
To set the delay: 1. Select T. Outdoor Delay.
NL
2. Press the navigation wheel to confirm selection. 3. Set the value.
NO PL
Default: 24 h
Setting range: 0 – 24 h, 1 h increments
4. Confirm the setting by pressing the navigation wheel again.
PT
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
4. Confirm the new setting by pressing the navigation wheel again.
RO RU SE SK 124
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK OUTDOOR TRIGGER TEMP.
INDOOR TRIGGER TEMP.
In this menu one of the triggers (outdoor temperature) for switching the zone between heating and cooling is set.
In this menu one of the triggers (indoor temperature) for switching the zone between heating and cooling is set.
N OT E ! All triggers and time delays must be met for the zone to switch heating/cooling mode.
N OT E ! All triggers and time delays must be met for the zone to switch heating/cooling mode.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
To set the outdoor trigger temperature:
To set the indoor trigger temperature:
1. Select Outdoor Trigger Temp.
1. Select Indoor Trigger Temp.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Set the value.
Default: 20.0 ˚C
Default: 22.0 ˚C
Setting range: 5.0 – 30.0 ˚C, 0.1 ˚C increments
Setting range: 5.0 – 30.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
4. Confirm the new setting by pressing the navigation wheel again.
OUTDOOR TRIGGER DELAY
INDOOR TRIGGER DELAY
In this menu one of the triggers (delay for outdoor temperature) for switching the zone between heating and cooling is set.
In this menu one of the triggers (delay for indoor temperature) for switching the zone between heating and cooling is set.
N OT E ! All triggers and time delays must be met for the zone to switch heating/cooling mode.
N OT E ! All triggers and time delays must be met for the zone to switch heating/cooling mode.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
To set the outdoor trigger delay:
To set the indoor trigger delay:
1. Select Outdoor Trigger Delay.
1. Select Indoor Trigger Delay.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Set the value.
Default: 24 h
Default: 24 h
Setting range: 1 – 48 h, 1 h increments
Setting range: 1 – 48 h, 1 h increments
4. Confirm the new setting by pressing the navigation wheel again.
CZ DE DK EE ES FI FR HR HU IT LT LV NL NO
4. Confirm the new setting by pressing the navigation wheel again.
PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
125
UK CZ
SUPPLY SETPOINT FOR HC SWITCH
HYSTERESIS
In this menu the supply temperature setpoint for switching between heating and cooling is set.
In this menu the hysteresis which is used to switch between heating and cooling using Supply Setpoint for HC Switch is set.
The zone switches to heating when the supply temperature is higher than Supply Setpoint for HC Switch. The zone switches back when the supply temperature is lower than Supply Setpoint for HC Switch - Hysteresis.
DE DK
The zone switches to cooling when the supply temperature is lower than Supply Setpoint for HC Switch. The zone switches back when the supply temperature is lower than Supply Setpoint for HC Switch + Hysteresis.
EE ES
N OT E ! When using this switch mode, the heating/ cooling switch is done in the heat pump/ chiller. The Move PRO controller switches the operation mode when it detects the change in supply temperture.
FI FR
No diverting valves are controlled in this mode.
HR
This menu is only shown if H/C Switchover is set to Supply Water Temp..
HU
To set the hysteresis: 1. Select Hysteresis. 2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 2 ˚C
Setting range: 0 – 4 ˚C, 1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again. Automatic Freeze Protection This menu decides when to activate automatic freeze protection during meltaway in the zone. The controller will kepp the return temperature between the low and high thersholds. This menu is only shown if Zone Setup is set to Meltaway for the zone. MENU TREE Automatic Freeze Protection
To set the supply temperature setpoint for HC switch:
Primary return Temp. Low
1. Select Supply Setpoint for HC Switch.
IT
Primary return Temp. High
2. Press the navigation wheel to confirm selection.
LT LV
3. Set the value.
PRIMARY RETURN TEMP. LOW
Default: 18 ˚C
In this menu the lower threshold is set.
Setting range: 5 – 30 ˚C, 1 ˚C increments
To set the low threshold:
4. Confirm the new setting by pressing the navigation wheel again.
NL
1. Select Primary return Temp. Low. 2. Press the navigation wheel to confirm selection. 3. Set a value.
NO
Default: 0.0 ˚C
Setting range: -5.0 – 5.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
PL PT RO RU SE SK 126
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK PRIMARY RETURN TEMP. HIGH
H/C S witchover
In this menu the higher threshold is set.
This menu enables access to settings related to switching between heating and cooling in the zone.
CZ DE
2. Press the navigation wheel to confirm selection.
This menu is only shown if System Type is set to 2 Pipe and one of the zones is not set to Smatrix Base PRO.
3. Set a value.
Menu tree*
DK
To set the high threshold: 1. Select Primary return Temp. High.
Default: 15.0 ˚C
Setting range: 15.0 – 45.0 ˚C, 0.1 ˚C increments
H/C Switchover H/C Switchover
4. Confirm the setting by pressing the navigation wheel again.
Outdoor Trigger Temp.
Condensation Delay
Indoor Trigger Temp.
In this menu the condensation delay in the zone is set. If condensation is not detected (by the condensation sensor in the zone) during the time set in the delay, the condensation status (in the zone information menu) switches to No.
Outdoor Trigger Delay
Supply Setpoint for HC Switch
FI
Hysteresis *
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
H/C Switchover
To set the condensation delay:
In this menu settings for switching the zone between heating and cooling is set.
2. Press the navigation wheel to confirm selection.
To select heating/cooling swithover function for the zone:
3. Set the value.
1. Select H/C Switchover.
Default: 10 min
2. Press the navigation wheel to confirm selection.
Setting range: 0 – 120 min, 1 min increments
3. Select heating/cooling switchover function for the zone.
4. Confirm the new setting by pressing the navigation wheel again.
ES
Indoor Trigger Delay.
This menu is only shown if Condensation Sensor is enabled in the startup wizard for the zone.
1. Select Condensation Delay.
EE
FR HR HU IT LT
• Indoor and Outdoor uses the indoor and outdoor temperatures and time delays to switch the zone between heating and cooling.
LV
• Supply Water Temp. uses the supply water temperature and a hysteresis to switch the zone between heating and cooling.
NL
• Contact Input uses an external signal to switch the zone between heating and cooling.
NO
• Force Heating sets the zone in forced heating.
• Force Cooling sets the zone in forced cooling.
PL
4. Confirm the new setting by pressing the navigation wheel again.
PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
127
UK CZ
Outdoor Trigger Temp.
Indoor Trigger Temp.
In this menu one of the triggers (outdoor temperature) for switching the zone between heating and cooling is set.
In this menu one of the triggers (indoor temperature) for switching the zone between heating and cooling is set.
DE
N OT E ! All triggers and time delays must be met for the zone to switch heating/cooling mode.
N OT E ! All triggers and time delays must be met for the zone to switch heating/cooling mode.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
To set the outdoor trigger temperature:
To set the indoor trigger temperature:
1. Select Outdoor Trigger Temp.
1. Select Indoor Trigger Temp.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Set the value.
Default: 20.0 ˚C
Default: 22.0 ˚C
Setting range: 5.0 – 30.0 ˚C, 0.1 ˚C increments
Setting range: 5.0 – 30.0 ˚C, 0.1 ˚C increments
DK EE ES FI FR
4. Confirm the new setting by pressing the navigation wheel again.
4. Confirm the new setting by pressing the navigation wheel again.
HR
Outdoor Trigger Delay
Indoor Trigger Delay
HU
In this menu one of the triggers (delay for outdoor temperature) for switching the zone between heating and cooling is set.
In this menu one of the triggers (delay for indoor temperature) for switching the zone between heating and cooling is set.
IT
N OT E ! All triggers and time delays must be met for the zone to switch heating/cooling mode.
N OT E ! All triggers and time delays must be met for the zone to switch heating/cooling mode.
LT
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
To set the outdoor trigger delay:
To set the indoor trigger delay:
1. Select Outdoor Trigger Delay.
1. Select Indoor Trigger Delay.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Set the value.
Default: 24 h
Default: 24 h
Setting range: 1 – 48 h, 1 h increments
Setting range: 1 – 48 h, 1 h increments
LV NL NO
4. Confirm the new setting by pressing the navigation wheel again.
PL
4. Confirm the new setting by pressing the navigation wheel again.
PT RO RU SE SK 128
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Supply Setpoint for HC Switch
Hysteresis
In this menu the supply temperature setpoint for switching between heating and cooling is set.
In this menu the hysteresis which is used to switch between heating and cooling using Supply Setpoint for HC Switch is set.
CZ
To set the hysteresis:
DE
The zone switches to heating when the supply temperature is higher than Supply Setpoint for HC Switch. The zone switches back when the supply temperature is lower than Supply Setpoint for HC Switch - Hysteresis. The zone switches to cooling when the supply temperature is lower than Supply Setpoint for HC Switch. The zone switches back when the supply temperature is lower than Supply Setpoint for HC Switch + Hysteresis.
1. Select Hysteresis.
DK
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 2 ˚C
Setting range: 0 – 4 ˚C, 1 ˚C increments
EE
4. Confirm the new setting by pressing the navigation wheel again.
ES
N OT E ! When using this switch mode, the heating/ cooling switch is done in the heat pump/ chiller. The Move PRO controller switches the operation mode when it detects the change in supply temperture.
FI FR
No diverting valves are controlled in this mode.
HR
This menu is only shown if H/C Switchover is set to Supply Water Temp..
HU
To set the supply temperature setpoint for HC switch: 1. Select Supply Setpoint for HC Switch.
IT
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 18 ˚C
Setting range: 5 – 30 ˚C, 1 ˚C increments
LT LV
4. Confirm the new setting by pressing the navigation wheel again.
NL NO PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
129
UK CZ
C ontroller S ettings
Language
In this menu parameter settings for the controller can be set or changed.
In this menu the language of the system is set. To set the language:
Menu tree
DE
1. Select Language.
Controller Settings
2. Press the navigation wheel to confirm selection. Time
DK
Date Language
EE
3. Select a language. 4. Confirm the setting by pressing the navigation wheel again.
Time In this menu the time of the system is set.
ES
To set the time: 1. Select Time.
FI
2. Press the navigation wheel to confirm selection. 3. Set the hours.
FR
4. Press the navigation wheel to confirm selection. 5. Set the minutes.
HR
6. Confirm the setting by pressing the navigation wheel again.
HU
Date In this menu the date of the system is set.
IT
To set the date: 1. Select Date.
LT
2. Press the navigation wheel to confirm selection. 3. Set the day. 4. Press the navigation wheel to confirm selection.
LV
5. Set the month. 6. Press the navigation wheel to confirm selection.
NL
7. Set the year. 8. Confirm the setting by pressing the navigation wheel again.
NO PL PT RO RU SE SK 130
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK
7.11 Pre Heating Info This menu shows information about the system, enabled zones and the controller (when the operating mode is set to Pre Heating in the startup wizard).
Z one 1 I nformation This menu shows information about zone 1.
CZ
Menu tree
DE
Zone 1 Information
Menu tree*
Supply temperature State
Pre Heating Info Zone 1 Information Zone 2 Information Zone 3 Information Controller Information *
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
S ystem
information
The system information menu shows the current time and date.
DK
Time Left
System information
Supply temperature
EE
The current supply temperature is shown. The temperature is measured by the supply temperature sensor wired to the controller.
ES
State The current pre-heating state (phase) in the zone is shown.
FI
Pre heating is run in three different phases.
FR
Pase 1: The supply temperature setpoint is set to 25 ˚C for 3 days (can be set in the Settings menu).
Pase 2: The supply temperature setpoint is set to maximum allowed calculated setpoint for 4 days (can be set in the Settings menu).
HR HU
Pase 3: The controller enters Standby mode until the startup wizard is restarted (Settings > Installer Settings > Restart wizard). Frost protection is active during this final phase.
IT LT
Time Left The time left of the current pre-heating phase in the zone is shown.
LV NL NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
131
UK CZ
Z one 2 I nformation
Z one 3 I nformation
This menu shows information about zone 2.
This menu shows information about zone 3.
Menu tree
Menu tree
DE
Zone 2 Information
DK EE ES FI FR HR
LT LV
Supply temperature
Supply temperature
State
State
Time Left
Time Left
Supply temperature
Supply temperature
The current supply temperature is shown. The temperature is measured by the supply temperature sensor wired to the controller.
The current supply temperature is shown. The temperature is measured by the supply temperature sensor wired to the controller.
State
State
The current pre-heating state (phase) in the zone is shown.
The current pre-heating state (phase) in the zone is shown.
Pre heating is run in three different phases.
Pre heating is run in three different phases.
Pase 1: The supply temperature setpoint is set to 25 ˚C for 3 days (can be set in the Settings menu).
Pase 1: The supply temperature setpoint is set to 25 ˚C for 3 days (can be set in the Settings menu).
Pase 2: The supply temperature setpoint is set to maximum allowed calculated setpoint for 4 days (can be set in the Settings menu).
Pase 2: The supply temperature setpoint is set to maximum allowed calculated setpoint for 4 days (can be set in the Settings menu).
Pase 3: The controller enters Standby mode until the startup wizard is restarted (Settings > Installer Settings > Restart wizard). Frost protection is active during this final phase.
Pase 3: The controller enters Standby mode until the startup wizard is restarted (Settings > Installer Settings > Restart wizard). Frost protection is active during this final phase.
HU IT
Zone 3 Information
Time Left
Time Left
The time left of the current pre-heating phase in the zone is shown.
The time left of the current pre-heating phase in the zone is shown.
NL NO PL PT RO RU SE SK 132
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK C ontroller I nformation This menu shows information about the controller. Menu tree Controller Information Language About...
Language This menu show the set display language for the controller.
7.12 Pre Heating Settings In this menu installer settings, enabled zone settings, and controller settings can be changed (when the operating mode is set to Pre Heating in the startup wizard).
CZ DE
See section 5.14 Pre heating concrete slab (DIN 1264-4) for more information.
DK
Menu tree*
EE
Pre Heating Settings Installer Settings Zone 1 Settings
About...
ES
Zone 2 Settings
This menu shows the serial number, software versions, and hardware versions of the controller.
Zone 3 Settings Controller Settings *
FI
Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
I nstaller S ettings
FR
In this menu lock codes (to gain access to locked parameter settings) can be set or changed, factory settings can be restored, backup of controller parameter settings can be managed, or the setup wizard can be restarted.
HR HU
Menu tree Installer Settings
IT Lock code Change lock code
LT
Display settings Restore factory settings Restore backup
LV
New backup Restart wizard
NL NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
133
UK Change lock code
A lock code can be used to block a user from changing parameter settings. The menu system is fully accessible, but the lock code is required to enter and change parameter settings.
The standard lock code which is used to block a user from changing parameter settings, can be changed in this menu.
CZ
Lock code
DE
This menu is only shown when Lock code has been enabled in the Lock code menu.
The default lock code is 0000. It is recommended to change this code if using this function.
DK
N OT E ! If the controller display is already locked, it has to be unlocked before entering the new lock code.
The controller will stay unlocked until it has been left untouched fro about 10 minutes. Then it will lock itself again.
EE
To change the lock code:
1. Select Lock code.
1. Select Change lock code.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Select Enable. 4. Press the navigation wheel to confirm selection.
3. Enter the new lock code in the boxes using the navigation wheel.
ENTERING A MENU WHEN LOCK CODE IS ENABLED
Turn the navigation wheel to either select a box, or to increase/decrease a value in edit mode.
Press the navigation wheel to enter edit mode or to confirm the new setting.
2. Press the navigation wheel to confirm selection.
Default: 0000
3. Enter the lock code in the boxes using the navigation wheel.
4. Confirm the new lock code by pressing and holding the navigation wheel for about 8 seconds.
ES
To enable lock code in the controller:
FI FR
To enter a lock code: 1. Select the parameter.
HR HU
Turn the navigation wheel to either select a box, or to increase/decrease a value in edit mode.
Display settings
Press the navigation wheel to enter edit mode or to confirm the new setting.
Default: 0000
This menu enables display settings, such as contrast, and it also shows the version number of the display software.
IT LT
4. Confirm the lock code by pressing and holding the navigation wheel for a number of seconds.
LV
5. Change the parameter setting and exit.
To set the display contrast: 1. Select Display settings. 2. Press the navigation wheel to confirm selection. 3. Select Display contrast.
NL
4. Press the navigation wheel to confirm selection. 5. Set the display contrast.
NO
Setting range: -50 – 100 %, 1 % increments
6. Press the navigation wheel to confirm selection.
PL PT RO RU SE SK 134
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Restore factory settings
New backup
This menu enables all parameter settings in the controller to be reset to the factory default settings.
This menu enables the controller to save a backup of all parameter settings to the microSD-card.
To restore the factory settings:
To save from a backup:
1. Select Restore factory settings.
1. Make sure a microSD-card, where the backup is to be saved, into the controller.
2. Press the navigation wheel to confirm selection. 3. Select Yes.
Setting range: No (default)/Yes
4. Press the navigation wheel to confirm selection. 5. All parameters in the controller are being restored to factory settings. Restore backup This menu enables the controller to restore all parameter settings from a previously created backup located on the microSD-card. To restore from a backup: 1. Make sure the microSD-card with the backup is inserted into the controller. 2. Select Restore backup. 3. Press the navigation wheel to confirm selection. 4. Select Yes.
Setting range: No (default)/Yes
5. Press the navigation wheel to confirm selection.
CZ DE DK
2. Select New backup. 3. Press the navigation wheel to confirm selection.
EE
4. Select Yes.
Setting range: No (default)/Yes
5. Press the navigation wheel to confirm selection.
ES
6. All parameters in the controller are being saved to the microSD card.
FI
Restart wizard This menu enables the controller to restart the setup wizard.
FR
To restart the setup wizard:
HR
1. Select Restart wizard. 2. Press the navigation wheel to confirm selection.
HU
3. Select Yes.
Setting range: No (default)/Yes
IT
4. Press the navigation wheel to confirm selection. 5. The setup wizard is now being restarted.
6. All parameters in the controller are being restored from backup.
LT LV NL NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
135
UK Z one 1 S ettings
P-area
In this menu parameter settings for zone 1 can be set or changed.
CZ
To set the P-area:
Menu tree
DE
1. Select P-area.
Zone 1 Settings Z1 Max. Calc. Supply Setpoint
DK
Frost Protection Setpoint P-area
EE
I-time Actuator running time
ES
In this menu the P-area for the mixing valve regulation is set.
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 140.0 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
Z1 Max. Calc. Supply Setpoint In this menu the maximum allowed calculated supply setpoint for the zone can be set.
FI
To set the maximum allowed calculated supply setpoint:
FR
1. Select Z1 Max. Calc. Supply Setpoint. 2. Press the navigation wheel to confirm selection.
HR
3. Set the value.
HU
Default: 45.0 ˚C
Setting range: -5.0 – 70.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
IT
I-time In this menu the I-time for the mixing valve regulation is set. To set the I-time: 1. Select I-time. 2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 35 seconds
Setting range: 5 – 300 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
Frost Protection Setpoint In this menu the frost protection setpoint (minimum available supply temperature) for the zone can be set. The supply temperature is not allowed to fall below this value.
LT LV NL NO PL
Actuator running time In this menu the actuator running time for the mixing valve regulation is set. To set the actuator running time:
To set the frost protection setpoint:
1. Select Actuator running time.
1. Select Frost Protection Setpoint.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Set the value.
Default: 120 seconds
Default: 5.0 ˚C
Setting range: 0 – 500 seconds, 1 second increments
Setting range: 5.0 – 20.0 ˚C (or max. supply temp), 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
4. Confirm the new setting by pressing the navigation wheel again.
PT RO RU SE SK 136
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Z one 2 S ettings
P-area
In this menu parameter settings for zone 2 can be set or changed.
In this menu the P-area for the mixing valve regulation is set.
CZ
To set the P-area:
Menu tree
DE
1. Select P-area.
Zone 2 Settings Z2 Max. Calc. Supply Setpoint Frost Protection Setpoint P-area I-time Actuator running time
2. Press the navigation wheel to confirm selection.
DK
3. Set the value.
Default: 200.0 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
EE
4. Confirm the setting by pressing the navigation wheel again.
ES
Z2 Max. Calc. Supply Setpoint In this menu the maximum allowed calculated supply setpoint for the zone can be set. To set the maximum allowed calculated supply setpoint: 1. Select Z2 Max. Calc. Supply Setpoint. 2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 45.0 ˚C
Setting range: -5.0 – 70.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
I-time
FI
In this menu the I-time for the mixing valve regulation is set. To set the I-time:
FR
1. Select I-time. 2. Press the navigation wheel to confirm selection.
HR
3. Set the value.
Default: 50 seconds
Setting range: 5 – 300 seconds, 1 second increments
HU
4. Confirm the setting by pressing the navigation wheel again.
IT
Frost Protection Setpoint In this menu the frost protection setpoint (minimum available supply temperature) for the zone can be set. The supply temperature is not allowed to fall below this value.
Actuator running time In this menu the actuator running time for the mixing valve regulation is set.
LT
To set the actuator running time:
LV
To set the frost protection setpoint:
1. Select Actuator running time.
1. Select Frost Protection Setpoint.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Set the value.
Default: 60 seconds
Default: 5.0 ˚C
Setting range: 0 – 500 seconds, 1 second increments
Setting range: 5.0 – 20.0 ˚C (or max. supply temp), 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
NL NO PL
4. Confirm the new setting by pressing the navigation wheel again.
PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
137
UK Z one 3 S ettings
P-area
In this menu parameter settings for zone 3 can be set or changed.
CZ
To set the P-area:
Menu tree
DE
1. Select P-area.
Zone 3 Settings Z3 Max. Calc. Supply Setpoint
DK
Frost Protection Setpoint P-area
EE
I-time Actuator running time
ES
In this menu the P-area for the mixing valve regulation is set.
2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 200.0 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
Z3 Max. Calc. Supply Setpoint In this menu the maximum allowed calculated supply setpoint for the zone can be set.
FI
To set the maximum allowed calculated supply setpoint:
FR
1. Select Z1 Max. Calc. Supply Setpoint. 2. Press the navigation wheel to confirm selection.
HR
3. Set the value.
HU
Default: 45.0 ˚C
Setting range: -5.0 – 70.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
IT
I-time In this menu the I-time for the mixing valve regulation is set. To set the I-time: 1. Select I-time. 2. Press the navigation wheel to confirm selection. 3. Set the value.
Default: 50 seconds
Setting range: 5 – 300 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
Frost Protection Setpoint In this menu the frost protection setpoint (minimum available supply temperature) for the zone can be set. The supply temperature is not allowed to fall below this value.
LT LV NL NO PL
Actuator running time In this menu the actuator running time for the mixing valve regulation is set. To set the actuator running time:
To set the frost protection setpoint:
1. Select Actuator running time.
1. Select Frost Protection Setpoint.
2. Press the navigation wheel to confirm selection.
2. Press the navigation wheel to confirm selection.
3. Set the value.
3. Set the value.
Default: 60 seconds
Default: 5.0 ˚C
Setting range: 0 – 500 seconds, 1 second increments
Setting range: 5.0 – 20.0 ˚C (or max. supply temp), 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
4. Confirm the new setting by pressing the navigation wheel again.
PT RO RU SE SK 138
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK C ontroller S ettings
Language
In this menu parameter settings for the controller can be set or changed.
In this menu the language of the system is set.
CZ
To set the language: Menu tree
1. Select Language.
Controller Settings
DE
2. Press the navigation wheel to confirm selection. Time Date Language Operation mode
Time In this menu the time of the system is set.
3. Select a language.
EE Operation mode In this menu the operation mode of the system is set.
To set the time:
This setting is used to change from pre heating to standard mode, when done pre heating.
1. Select Time.
To set operation mode:
2. Press the navigation wheel to confirm selection. 3. Set the hours. 4. Press the navigation wheel to confirm selection. 5. Set the minutes.
In this menu the date of the system is set. To set the date:
ES FI
1. Select Operation mode.
FR
2. Press the navigation wheel to confirm selection. 3. Select an operation mode.
Standard: This selection will make the controller to restart the startup wizard, after a small delay.
Pre Heating: This selection will make the controller stay in Pre Heating mode.
6. Confirm the setting by pressing the navigation wheel again. Date
DK
4. Confirm the setting by pressing the navigation wheel again.
HR HU IT
4. Confirm the setting by pressing the navigation wheel again.
1. Select Date.
LT
2. Press the navigation wheel to confirm selection. 3. Set the day.
LV
4. Press the navigation wheel to confirm selection. 5. Set the month.
NL
6. Press the navigation wheel to confirm selection. 7. Set the year.
NO
8. Confirm the setting by pressing the navigation wheel again.
PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
139
UK
7.13 Menu tree CZ
N OT E ! Parts of the menu tree may only be visible in the Move PRO controller depending on its current configuration.
DE
S tandard O perating M ode DK
System Overview Information
System information
EE
Time Date Outdoor Temperature
ES
Zone 1 Information
Zone Setup Heating Mode
FI
Operating Mode Supply temperature Mixing Valve
FR
Pump Heating
HR
Heating Curve Calculated Supply Setpoint Indoor temperature
HU
ECO-Comf Status Cooling
IT
Cooling Curve Calculated Supply Setpoint Condensation
LT
Relative Humidity Dew Point Temperature Dehumidifier
LV Zone 2 Information
Zone Setup Heating Mode
NL
Operating Mode Supply temperature
NO
Calculated Supply Setpoint DHW Circ. Return Temperature
PL
Mixing Valve Pump
PT
Heating
Heating Curve Calculated Supply Setpoint
RO
Indoor temperature ECO-Comf Status
RU SE SK 140
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Cooling
Cooling Curve Calculated Supply Setpoint
CZ
Condensation Relative Humidity
DE
Dew Point Temperature Dehumidifier Zone 3 Information
DK
Zone Setup Heating Mode
EE
Operating Mode Supply temperature Calculated Supply Setpoint
ES
Indoor temperature Meltaway Curve
FI
Return temperature Ground Temperature
FR
Ground Moisture Primary Return Temperature Status
HR
Mixing Valve Pump
HU
Status Heating
Heating Curve
IT
Calculated Supply Setpoint Indoor temperature ECO-Comf Status Cooling
LT
Cooling Curve
LV
Calculated Supply Setpoint Condensation Relative Humidity
NL
Dew Point Temperature Dehumidifier
NO Controller Information
Language About...
PL Alarms
Active alarms Alarm history
PT
Acknowledge all alarms Reset alarm history
RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
141
UK Settings
Installer Settings
T Outdoor Fallback Lock code
CZ
Change lock code Display settings
DE
Restore factory settings Restore backup
DK
New backup Restart wizard
EE
Zone 1 Settings
Supply Temp. Settings
Heating
Calculated Supply Setpoint Heating Min. Supply Temp. Heating Max. Supply Temp.
ES
Deviation alarm limit Deviation alarm delay
FI
Cooling
Calculated Supply Setpoint Cooling Min. Supply Temp.
FR
Cooling Max. Supply Temp. Dew Point Margin Dew Point Offset
HR Heating Indoor Temp. Settings
HU
Indoor Setpoint Calculated Indoor Setpoint ECO-Comf. Status Indoor Setpoint Influence (Lower)
IT
Indoor Setpoint Influence (Upper)
LT Comf. - ECO
ECO Setback ECO-Comf Status
LV
ECO-Comf Schedule Heating Curve
NL
Setting Offset Heating Curve
NO Cooling Curve
Setting Offset
PL
Cooling Curve Manual Operation
PT
Manual Mode Pump Mixing valve
RO Pump
Pump Exercise Exercise Day of the Week
RU
Exercise Hour Exercise Min
SE SK 142
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Mixing Valve
Heating
P-area I-time
CZ
Actuator running time Cooling
P-area
DE
I-time Actuator running time
DK Dehumidifier Control
Dew Point Margin Dead Zone
EE Seasonal Shut Off
Heating
Pump Stop Valve Close
ES
Shut Off Outdoor Temp. T. Outdoor Setpoint T. Outdoor Delay
FI
Shut Off Indoor Temp. T. Indoor Delay
FR Cooling
Pump Stop Valve Close
HR
T. Outdoor Setpoint T. Outdoor Delay HC Switchover
HU
H/C Switchover Outdoor Trigger Temp. Outdoor Trigger Delay
IT
Indoor Trigger Temp. Indoor Trigger Delay.
LT
Supply Setpoint for HC Switch Hysteresis
LV
Condensation Delay Zone 2 Settings
Supply Temp. Settings
Heating
Calculated Supply Setpoint
NL
Heating Min. Supply Temp. Heating Max. Supply Temp.
NO
Deviation alarm limit Deviation alarm delay Cooling
PL
Calculated Supply Setpoint Cooling Min. Supply Temp.
PT
Cooling Max. Supply Temp. Dew Point Margin Dew Point Offset
RO
DHW Supply Setpoint Overheating alarm limit
RU
Overheating alarm delay Deviation alarm limit
SE
Deviation alarm delay
SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
143
UK Heating Indoor Temp. Settings
CZ
Indoor Setpoint Calculated Indoor Setpoint ECO-Comf. Status
DE
Indoor Setpoint Influence (Lower) Indoor Setpoint Influence (Upper)
DK DHW Circ Return Settings
EE
DHW Circ Return Setpoint BoostPower
Comf. - ECO
ES
ECO Setback ECO-Comf Status ECO-Comf Schedule
FI
Heating Curve
Setting Offset Heating Curve
FR Cooling Curve
Setting Offset
HR
Cooling Curve
HU
Manual Operation
Manual Mode Pump Mixing valve
IT Pump
Pump Exercise Exercise Day of the Week
LT
Exercise Hour Exercise Min
LV Mixing Valve
Heating
P-area I-time
NL
Actuator running time Cooling
NO
P-area I-time Actuator running time
PL
P-area I-time
PT
Actuator running time Dehumidifier Control
RO
Dew Point Margin Dead Zone
RU SE SK 144
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Seasonal Shut Off
Heating
Pump Stop Valve Close
CZ
Shut Off Outdoor Temp. T. Outdoor Setpoint
DE
T. Outdoor Delay Shut Off Indoor Temp.
DK
T. Indoor Delay Cooling
Pump Stop
EE
Valve Close T. Outdoor Setpoint T. Outdoor Delay HC Switchover
ES
H/C Switchover Outdoor Trigger Temp.
FI
Outdoor Trigger Delay Indoor Trigger Temp.
FR
Indoor Trigger Delay. Supply Setpoint for HC Switch
HR
Hysteresis Condensation Delay Zone 3 Settings
Supply Temp. Settings
HU Heating
Calculated Supply Setpoint Heating Min. Supply Temp.
IT
Heating Max. Supply Temp. Deviation alarm limit
LT
Deviation alarm delay Cooling
Calculated Supply Setpoint
LV
Cooling Min. Supply Temp. Cooling Max. Supply Temp. Dew Point Margin
NL
Dew Point Offset Calculated Supply Setpoint
NO
Melting Supply Setpoint Heating Curve Meltaway
PL
IDLE Supply Setpoint Min. Supply Temp. (IDLE Status)
PT
Max. Supply Temp. (IDLE Status) Heating Indoor Temp. Settings
RO
Indoor Setpoint Calculated Indoor Setpoint
RU
ECO-Comf. Status Indoor Setpoint Influence (Lower)
SE
Indoor Setpoint Influence (Upper)
SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
145
UK Comf. - ECO
ECO Setback ECO-Comf Status
CZ
ECO-Comf Schedule
DE
Heating Curve
Setting Offset Heating Curve
DK Cooling Curve
Setting Offset
EE
Cooling Curve Meltaway Curve (IDLE Status)
ES
Setting Offset
FI
Heating Curve
FR
Return Temperature
Max. Supply-Return Diff.
Enter Stop State Conditions
Outdoor Temperature Delay (days)
HR
Enter Idle State Conditions
Outdoor Temperature Delay (hours)
HU
Delay Surface Dry Enter Melting State Conditions
IT
Ground Temperature Limit Outdoor Temp. Offset Outdoor Temperature Low Limit
LT
Min. Time in Melting
LV
Manual Operation
Manual Mode Pump Mixing valve
NL Pump
Pump Exercise
NO
Exercise Day of the Week Exercise Hour Exercise Min
PL Mixing Valve
Heating
P-area I-time
PT
Actuator running time Cooling
RO
P-area I-time Actuator running time
RU P-area I-time
SE
Actuator running time
SK 146
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Dehumidifier Control
Dew Point Margin Dead Zone
Seasonal Shut Off
Heating
CZ Pump Stop
DE
Valve Close Shut Off Outdoor Temp. T. Outdoor Setpoint
DK
T. Outdoor Delay Shut Off Indoor Temp.
EE
T. Indoor Delay Cooling
Pump Stop
ES
Valve Close T. Outdoor Setpoint T. Outdoor Delay HC Switchover
FI
H/C Switchover Outdoor Trigger Temp.
FR
Outdoor Trigger Delay Indoor Trigger Temp.
HR
Indoor Trigger Delay. Supply Setpoint for HC Switch
HU
Hysteresis Automatic Freeze Protection
Primary return Temp. Low
IT
Primary return Temp. High Condensation Delay HC Switchover
LT
H/C Switchover Outdoor Trigger Temp.
LV
Outdoor Trigger Delay Indoor Trigger Temp.
NL
Indoor Trigger Delay. Supply Setpoint for HC Switch
NO
Hysteresis Controller Settings
Time
PL
Date Language
PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
147
UK P re H eating O perating M ode System Overview
CZ
Pre Heating Info
System information
DE
Time Date
Zone 1 Information
DK
Z1 - Supply Temperature State Time Left
EE
Zone 2 Information
Z2 - Supply Temperature State
ES
Time Left Zone 3 Information
FI
Z3 - Supply Temperature State Time Left
FR
Controller Information
Language About...
HR
Alarms
Active alarms Alarm history Acknowledge all alarms
HU
Reset alarm history
IT LT LV NL NO PL PT RO RU SE SK 148
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK Pre Heating Settings
Installer Settings
Lock code Change lock code
CZ
Display settings Restore factory settings
DE
Restore backup New backup
Zone 1 Settings
Restart wizard
DK
Z1 Max. Calc. Supply Setpoint
EE
Frost Protection Setpoint P-area
ES
I-time Actuator running time Zone 2 Settings
FI
Z2 Max. Calc. Supply Setpoint Frost Protection Setpoint
FR
P-area I-time
Zone 3 Settings
Actuator running time
HR
Z3 Max. Calc. Supply Setpoint
HU
Frost Protection Setpoint P-area
IT
I-time Actuator running time
LT Controller Settings
Time Date
LV
Language Operation mode
NL NO PL PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
149
UK
8 Maintenance
CZ DE
The maintenance of Uponor Smatrix Move PRO includes the following:
DK
• Manual preventive maintenance • Automatic preventive maintenance
EE
• Corrective maintenance • Controller display
ES
8.1 Manual preventive maintenance Uponor Smatrix Move PRO requires no preventive maintenance except cleaning:
FI
1. Use a dry soft cloth to clean the components.
FR W arning ! Do not use any detergents to clean the Uponor Smatrix Move PRO components.
HR
8.2 Automatic preventive maintenance HU IT
Uponor Smatrix Move PRO is equipped with an automatic exercise function. This function consists of a test run designed to prevent the pump from seizing up due to inactivity.
LT
This exercise is run a fixed intervals, set in the menu system:
8.3 Corrective maintenance F allback
mode
If a sensor is malfunctioning or not detected, the controller triggers an alarm and executes the fallback mode to maintain the temperature in the zone until the problem is resolved.
R esetting
the controller
If the controller does not work as expected, for example due to a hang-up, it can be reset (requires a service level code) to solve the problem: See section 7.10 Settings > Installer Settings > Restore factory settings for more information.
8.4 Controller display It is recommended to occasionally check the display on the controller for alarms. The display flashes continuously for general alarms, until acknowledged. Determine what is causing the alarm by reading the alarm description. See section 7.8 Alarms for more information.
See section 7.10 Settings > Zone # Settings > Pump > Pump Exercise for more information.
LV
• The pump exercise operates only in the zone if enabled in the Move PRO controller display. The pump is activated for 1 minutes during the exercise.
NL NO PL PT RO RU SE SK 150
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK
9 Troubleshooting
CZ DE
The table below shows problems and alarms that can occur with Uponor Smatrix Move PRO and describes solutions. A common cause of a problem though may be due to wrongly installed loops or mixed up thermostats. Problem Fluctuating floor temperature
Indication Floor temperature is changing abnormally between hot and cold Room temperature does not match setpoint on the controller, and mixing valves open/close on a fixed interval Room temperature does not match setpoint on the controller
Probable cause Supply water temperature is too high
Solutions Check boiler or mixing valve
Heating fall back function is activated due to lost communication with an room sensor The room sensor is placed in direct sunlight or close to other heat sources
Check the connection of the room sensor
DK EE
The room sensor is placed in the wrong room. The indoor setpoint is too low
Reconnect if the connection is lost
ES
Check placement of the room sensor according to installation instructions and change location if needed Check the placement of the room sensor and change room if needed. Change the temperature setpoint
FI
The room is too Check the indoor setpoint in the menu cold (or too warm in system cooling mode) The temperature displayed in the controller The room sensor may be influenced by Change location of the room sensor menu system changes after the room an external heat source sensor is moved The indicator on the mixing valve actuator The mixing valve does not open 1. Check that the mixing valve is does not change/move correctly installed
FR HR
2. Contact the installer The room is too Corresponding loop is warm (or cold, in warm (or too cold in cooling mode) even after a long period heating mode) without heat call (or cooling call)
A mixing valve does not close
The floor is cold
No heat demand from the underfloor heating system
HU
3. Replace the mixing valve 1. Check that the mixing valve is correctly installed
IT
2. Contact the installer 3. Replace the mixing valve
All rooms are cold (or too warm in cooling mode)
Disturbing noise from the pump at the same time and day of the week No communication
The room temperature OK but the floor is cold
The room is heated by another heat source Check the indoor setpoint in the menu The indoor setpoint is too low (or too system high, in cooling mode) ECO mode for the zone programmed in the ECO mode controller
Alarm shown in controller display
LT LV
Change the temperature setpoint
NL
Change ECO profile or assign another profile to the room/system
Pump exercise is active
Reduce the ECO setback value for the zone Change time for pump exercise
Communication error
Contact the installer
NO PL
Software versions incompatible
PT RO RU SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
151
UK
9.1 Troubleshooting after installation CZ DE
Problem
Indication
Probable cause
Solutions
The system does not start
The controller display is off
There is no AC power to the controller
1. Check that the controller is connected to AC power 2. Check the wiring 3. Check that there is 230 V AC power in the wall socket
DK EE
The sensors are faulty
ES
There is 230 V AC power in the wall socket
Blown controller fuse or faulty power cable
1. Replace the fuse and/or power cable and plug
The controller display continue flashing and an alarm is displayed
The cable is not connected or a wire is damaged
Check the wiring
9.2 Contact the installer For installer contact information, see the installation report in the end of this document. Prepare the following information before contacting an installer:
FI
• Installation report
FR
• Drawings of the underfloor heating system (if available)
HR
• List of all alarms, including time and date
9.3 Installer instructions
HU
To determine if a problem is caused by the supply system or the control system, loosen the actuators from the manifold for the room concerned, wait a few minutes and check if the flow pipe of the underfloor heating loop becomes warm.
IT LT LV
If the pipe does not become warm, the problem is in the heating system. If the loop becomes warm, the cause could be the room control system.
NL
A supply system defect can be indicated by no warm water in the manifold. Check the boiler and circulation pump.
NO PL PT RO RU SE SK 152
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK
10 Technical data
CZ DE
10.1 Technical data
DK
General IP ErP (with room sensors) Operating temperature Storage temperature Mounting standard microSD
EE IP20 (IP: degree of inaccessibility to active parts of the product and degree of water) III (VII) 0 °C to +50 °C -20 °C to +70 °C EN 50022, DIN 46277-3 micro SDHC, UHS/Standard
ES FI
4...32 GB, FAT 32 Class 4...10 +
FR
230 V AC ±10%, 50/60 Hz (maximum 125 mA) 12 V DC / 125 mA 24 V AC / 0.7A (maximum 6 A) 125 mA
HR
Power Supply Operating voltage Battery input (UPS) Transformer input Internal fuse
HU
Sensor inputs Supply temperature sensor Return temperature sensor Room temperature sensor Outdoor temperature sensor Ground temperature sensor (Snow and ice sensor) Moisture sensor (Snow and ice sensor)
NTC 10
IT
-50 °C...+100 °C, ±0.1 °C
LT ROFF = ∞ Ω
Relative humidity sensor
RON < 2MΩ UIN = 0...10V
Condensation sensor
0...100% RH UO < 5 V
LV NL
IO < 0.5 A ROFF > 11 kΩ
NO
RON < 1.6 kΩ Outputs Mixing valves
UO = 0...10V
Diverting valves
IO < 10 mA UO = 24 V AC
Snow sensor
PO < 10 VA UO = 24 V AC
Circulation pumps/Dehumidifiers
PO < 10 VA UIN = 230 V AC
PL PT RO
IIN ≤ 1 A
RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
153
UK Communication
CZ
BMS interface
MODBUS-RTU (RS-232)
Uponor Smatrix Base PRO bus
RJ45 Galvanically isolated
DE
Terminals: –, A, B
10.2 Technical specifications
DK
Cables Cable from controller to valve actuator (shielded connected to ground) Cable to sensor input on controller (shielded connected to ground) Cable from output on controller to external devices
EE ES
Standard cable length
Maximum cable length
0.75 m
20 m
0.2 mm² to 1.5 mm²
5m
100 m
0.6 mm²
5m
20 m
Up to 4.0 mm² solid, or 2.5 mm² flexible with ferrules
-
5m
0.5 mm² to 2.5 mm²
2m
20 m
Up to 4.0 mm² solid, or 2.5 mm² flexible with ferrules
Communication cable
FI
Power cable
Wire gauge
10.3 Controller layout
FR
B
C
D
HR HU IT
L M N
A
LT LV
E
F
G
H
I
J
K
NL Item
NO
Description
A
Display
B
Sensor input connection terminals
C
Mixing valve output connection terminals
D
Battery and transformer input connection terminals
E
microSD
F
BMS, MODBUS-RTU (RS-232), connection
G
Uponor Smatrix Base PRO bus connection terminals
H
Diverting valves/Snow and ice sensor output connection terminals
I
Circulation pump/Dehumidifier output connection terminals
J
Power connection connection terminal
RU
K
Fuse (125 mA)
L
Information button
SE
M
Navigation wheel/ OK button
N
Back button
PL PT RO
SK 154
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK
10.4 Wiring diagram, Uponor Smatrix Move PRO controller
3
CZ 24VAC
DE
2 1
DK
24VAC
EE 24VAC
ES FI 15VDC GND
FR
12VDC IN GND 24VAC IN 1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18
- +
- +
HR
- +
41 42 43 44 45 46 47 48 49
52 53 54 55 56
HU IT LT LV NL T
microSD
72 73
21 22 23 24 25 26
75 76
77 78
N L 125 mA 230 V ±10% 50/60 Hz
NO
- A B
≤ 1A PRO PRO
!
PL
I > 1A
!
L N ≤ 1A
PRO PRO
PT
L N
!
1 2
L N
RO
≤ 1A
PRO PRO
L N
RU
!
3
L N
SE SK U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
155
UK
10.5 Dimensions CZ
C ontroller X-159 90 mm
DE
45 mm
DK
50 mm
93 mm
214 mm
EE R oom
temperature sensor 80 mm
S-155
ES
60 mm
30 mm
85 mm
FI FR HR
R elative
humidity sensor 85 mm
S-157
60 mm
HU
85 mm
IT
26 mm
LT 50 mm
20 mm
LV S now
sensor
S-158
NL
63.5 mm
78 mm
NO PL 60 mm
32 mm
PT RO RU SE SK 156
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK
11 Installation report
CZ DE DK EE ES FI Zone 1
Zone 2
Zone 3
FR Setup
Sensors
HR Supply temperature sensor
HU
Indoor temperature sensor Condensation sensor
IT
Relative Humidity sensor
LT
Stand Alone Control
Outdoor temperature sensor
LV Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
No
No
No
Mixing Valve
NL NO
Diverting Valve
PL
Circulation pump
PT
Dehumidifier
RO
Heating/Cooling switch/external signal
RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
157
UK CZ DE Setup
DK
Zone 1
Zone 2
Zone 3
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
No
No
No
Sensors Supply temperature sensor
EE Condensation sensor
ES Mixing valve
Smartix Base PRO
FI FR HR
Diverting Valve
Circulation pump
HU
Dehumidifier
IT Heating/Cooling switch/external signal
LT PRO PRO
LV
Smatrix Base PRO controller Supply temperature sensor
NL
Return temperature sensor Outdoor temperature sensor
NO
Ground temperature sensor
Meltaway
PL PT
Moisture sensor 1
Primary return sensor
RO
Yes Mixing valve No
RU
Yes Circulation pump No
SE Snow and ice sensor
SK 158
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
UK CZ Zone 1
Setup
Zone 2
Zone 3
DE
Sensors
DK
Domestic Hot Water
Supply temperature sensor
EE Return temperature sensor
ES
Yes Mixing valve No
FI
Yes Circulation pump No
FR HR HU IT LT LV NL NO PL PT RO RU SE SK
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
159
Production: Uponor AB, MRY, Virsbo; Sweden 1088471 12_2016_EN
Uponor Corporation www.uponor.com
Uponor reserves the right to make changes, without prior notification, to the specification of incorporated components in line with its policy of continuous improvement and development.