DRAWIN ARCHITECTURAL G ID A0.00 COVER SHEET
A0.06C A0.06D A0.08
C-5 GREEN BUILDING NOTES EGRESS DIAGRAM & WATER FLOW INFORMATION T24 RESIDENTIAL REPORT
A0.09
T24 RESIDENTIAL REPORT
A0.10 A0.11 A0.12
T24 RESIDENTIAL REPORT T24 COMMERCIAL REPORT T24 COMMERCIAL REPORT
A0.13 A0.14
ACCESSIBILITY DETAILS AB-005
A0.15 A0.16 A0.17
IS MEP-03a IS MEP-03b IS MEP-04a
A0.18 A1.00
IS MEP-04b SITE PLAN
A2.00 A2.01 A2.02
EXISTING BASEMENT-2ND PLANS BASEMENT-2ND PLANS 3RD-ROOF PLANS
A4.00
BASEMENT-2ND RCP
A4.01
3RD-ROOF RCP
A5.00 A5.01 A6.00
WINDOW SCHEDULE DOOR SCHEDULE ELEVATIONS
A6.01
ELEVATIONS
A7.00
BUILDING SECTIONS
A7.01 A9.00 A9.01
ENLARGED WALL SECTIONS WALL TYPES EXT. WALL TYPES INTERIOR
A9.02
FLOOR & ROOF TYPES
A0.07
1364 PACIFIC FILED UNDER SEPERATE PERMIT
SUBJECT PROPERTY
SUBJECT PROPERTY
1364 PACIFIC FILED UNDER SEPERATE PERMIT
STRUCTURAL S1.0 S1.1 S1.2
LYNCH STREET RENDERING
S2.0 S2.1 S2.2 S2.3 S3.1 S3.2 S4.1 S4.2 S5.1
02
GENERAL STRUCTURAL NOTES BASEMENT & FOUNDATION PLAN FIRST FLOOR FRAMING PLAN SECOND FLOOR FRAMING PLAN THIRD FLOOR FRAMING PLAN FOURTH FLOOR FRAMING PLAN ROOF FRAMING PLAN TYPICAL WOOD FRAMING DETAILS TYPICAL WOOD FRAMING DETAILS TYPICAL WOOD FRAMING DETAILS WOOD FRAMING DETAILS TYPICAL CONCRETE DETAILS TYPICAL CONCRETE DETAILS TYPICAL STEEL DETAILS TYPICAL STEEL DETAILS TYPICAL METAL DECK DETAILS
R1
E D A RCH NS D GHAN IT E A N Y
C-29116
A
GREEN BLDG REQUIREMENTS C-4
E
R1
NI
SITE CONTEXT
A0.06A A0.06B
LI RIC
A0.05
T E CM A
NSR & AFFIDAVIT OF SERVICE SITE SURVEY
T
A0.03 A0.04
A
PROJECT DATA VARIANCE DECISION
ST
A0.01 A0.02
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
6-30-2019 RENEWAL DATE
OF
CA LI
R
1370 PACIFIC AVE single family residential and commercial unit
rg-architecture
DRAWING INDEX
FO
R1
REVISIONS NO. DATE
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
ADDENDA SCHEDULE ADDENDUM #1: STRUCTURAL ADDENDUM #2: ARCHITECTURAL ADDENDUM #3: MEP
ISSUE 04/11/19 PLAN REVIEW COMMENTS
OWNER Mr. Harold Tang & Family
1370 Pacific Ave San Francisco, CA 94109 0155/021
1364 PACIFIC FILED UNDER SEPERATE PERMIT
SCALE AS NOTED DRAWN BY RG CHECKED BY
SUBJECT PROPERTY
RG PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 1 of 42
COVER SHEET DRAWING NO.
LYNCH STREET RENDERING
03
PACIFIC AVENUE RENDERING
01
A0.00
SOILS ENGINEER
Mr. Harold Tang & Family 555 4th Street, Unit 605 San Francisco, CA 94107 415.992.2990 etang18@gmail.com
Earth Mechanics 360 Grand Avenue, Suite 262 Oakland, CA 94610 510.839.0765
ARCHITECT rg-architecture 428 South Van Ness Ave San Francisco, CA 94103 415.699.3640
PLANNING CODE SUMMARY BLOCK & LOT: 0155/021 LOT SIZE: 17'-0" x 60'-0" = 1050sqft ZONING: PACIFIC AVENUE NEIGHBORHOOD COMMERCIAL DISTRICT (NCD)
Allen Gruen, GE earthmech1@aol.com PROJECT LOCATION
STRUCTURAL ONE Design 2849 California Street San Francisco CA 94115 415 828-4412
HEIGHT LIMIT: 40-X
Cp/M Company p. 510 813-8001
OFF STREET PARKING: COMMERCIAL: NONE REQUIRED IF OCCUPIED FLOOR AREA IS LESS THAN 200SQFT. THEREFORE NONE RESIDENTIAL: 1 SPACE FOR EACH DWELLING UNIT.
Curtis Poon rano1@att.net
DWELLING UNIT DENSITY: PER SFPC SECTIONS, 207.4, 1 UNIT PER 1000 SQFT OF LOT AREA. AFFORDABILITY REQUIREMENTS: PER SFPC SEC. 419.3, AFFORDABILITY REQUIREMENTS NOT APPLICABLE TO BUILDINGS WITH LESS THAN 5 DWELLING UNITS. BUILDING HAS 1 RESIDENTIAL DWELLING UNITS, THEREFORE NO AFFORDABILITY REQUIREMENT.
ABBREVIATIONS
VARIANCE REQ: REAR YARD AND GARAGE DOOR FILED 7.3.2013. CASE NUMBER: 2013.0884V REFERENCE SYMBOLS
ELECTRICAL/MECHANICAL SYMBOLS SINGLE ELECTRICAL OUTLET, DIRECT WIRED
DEMO WALL
DUPLEX OUTLET EXISTING WALL
FOURPLEX OUTLET ELECTRICAL OUTLET, HALF-SWITCHED
NEW WALL
ELECTRICAL OUTLET, FULLY SWITCHED
HIDDEN EDGE, ABOVE OR BEYOND
P
HIDDEN EDGE, BELOW OR BEHIND
ELECTRICAL OUTLET FOR PICTURE LIGHT 240V ELECTRICAL OUTLET
EMERGENCY ESCAPE & RESCUE WINDOWS
E
FLUSH FLOOR MOUNTED OUTLET GFI
123
DOOR SYMBOL
12
WINDOW SYMBOL
12
SKYLIGHT SYMBOL
GROUND FAULT INTERRUPT JUNCTION BOX
J SD
MULTI-FUNCTION SMOKE & CO DETECTOR
HD
HEAT DETTECTOR AUTOMATIC SPRINKLER HEAD
12
WALL TYPE
A
GRID OR REFERENCE LINE
3
BUILDING OR WALL SECTION NO. OVER SHEET NO.
A1.2 3
DETAIL NO. OVER SHEET NO.
A1.2 3
3 A1.2
+100.O'
DC
DOOR CHIME
GD
GARAGE DOOR OPENER SWITCH
I
INTERCOM STATION
KP
ALARM KEYPAD
MD
MOTION DETECTOR
SP
SPEAKER OUTLET
SC
SCENE CONTROL MASTER UNIT
W
SCENE CONTROL REMOTE WALL STATION
SU
STEAM UNIT CONTROL PANEL
CONTROL JOINT CLEAR CONTINUOUS CENTER
D. DBL. DET. D.F. DIA. DIM. DISP. DN. DR. D.S. D.W. DWG. DWR
DRYER DOUBLE DETAIL DOUGLAS FIR DIAMETER DIMENSION DISPOSER DOWN DOOR DOWN SPOUT DISHWASHER DRAWING DRAWER
E (E) EA. EL. ELEC. EQ. EXT.
EAST EXISTING EACH ELEVATION ELECTRICAL EQUAL EXTERIOR FLOOR DRAIN FOUNDATION FINISH FLOOR FACE OF FACE OF FINISH FACE OF STUD
(1) 24/4 PAIR CAT-6
F.S.M.F
FLEXIBLE SHEET MEMBRANE FLASHING
SPOT ELEVATION (N)
MM1
(1) CAT-6 & (1) RG6 QUAD
MM2
(2) CAT-6 & (2) RG6 QUAD
FT. FTG.
FEET FOOTING
HDMI
HDMI
GA. GALV. GYP. BD.
GAUGE GALVANIZED GYPSUM BOARD
H. H.B. HDR. HDWR. HORIZ. HT.
HIGH HOSE BIB HEADER HARDWARE HORIZONTAL HEIGHT
NEW OR FINISHED CONTOURS
(1) 24/4 PAIR CAT-3 C
COLD WATER CONNECTION
H
HOT WATER CONNECTION CENTRAL VACUUM
SURFACE CEILING LIGHT FIXTURE
G
GAS OUTLET
RECESSED DIRECTIONAL LIGHT FIXTURE
HB
HOSE BIB
RECESSED CEILING LIGHT FIXTURE
FD
FLOOR DRAIN
WALL MOUNTED LIGHT FIXTURE
DS
DOWNSPOUT
MOTION DETECTOR & PHOTOCONTROL LIGHT FIXTURE
T
THERMOSTAT
RECESSED WALL LIGHT FIXTURE
SUPPLY AIR REGISTER AT WALL OR TOE SPACE
EXPOSED STRIP LIGHT FIXTURE
SUPPLY AIR REGISTER AT FLOOR
CONCEALED STRIP LIGHT FIXTURE
SUPPLY AIR REGISTER AT CEILING
TRACK AND STRIP LIGHT FIXTURES
RETURN AIR GRILL AT WALL
ELECTRICAL SWITCH
RETURN AIR GRILL AT FLOOR
3
3-WAY SWITCH
RETURN AIR GRILL AT CEILING
4
4-WAY SWITCH
EXHAUST FAN
DIMMER SWITCH
EXHAUST FAN/ LIGHT UNIT
OS
C.J. CLR. CONT. CTR.
CAT-6
V
PS
BUILDING BLOCKING BUILT-UP ROOFING
LEVEL LINE OR DATUM
ELECTRICAL/ MECHANICAL SYMBOLS
FLUOR
BLDG. BLKG. B.U.R
(1) RG6 QUAD
45
MD
ABOVE AREA DRAIN ADJUSTABLE ABOVE FINISH FLOOR APPROXIMATE ARCHITECTURAL ASPHALT
TV
EXISTING CONTOURS
R
ABV A.D. ADJ. A.F.F. APPROX. ARCH. ASPH.
ROOM NO. OVER SHEET NO.
PLUG MOLD
PROPERTY LINE 45
DOOR BELL BUTTON
AT CENTERLINE DIAMETER
F.D. FDN. FIN. FL. F.O. F.O.F F.O.S.
ELEVATION NO. OVER SHEET NO.
A1.2
DB
@ CL O
PULL SWITCH MANUAL-ON OCCUPANCY SENSOR SWITCH
I.D. I.G. INSUL. INT.
INSIDE DIAMETER INSULATED GLASS INSULATION INTERIOR
JT.
JOINT
LAV. LT.
LAVATORY LIGHT
M. MAX. MECH. MFR. MIN. MISC.
MASTER MAXIMUM MECHANICAL MANUFACTURER MINIMUM MISCELLANEOUS
(N) N.I.C. NO. NOM. N.T.S O.C.
NEW NOT IN CONTRACT NUMBER NOMINAL NOT TO SCALE ON CENTER
O.H. OPNG. OPP. O/
OVERHANG OPENING OPPOSITE OVER
PL PL. P.LAM. PLYWD. P.T. PTD. P.V.
PROPERTY LINE PLATE PLASTIC LAMINATE PLYWOOD PRESSURE TREATED PAINTED PHOTOVOLTAIC
(R) R. R.A. REF. REG. REINF. REQ. RM. R.O. RDWD.
RELOCATED RISE, RISER RETURN AIR REFRIGERATOR REGISTER REINFORCED REQUIRED ROOM ROUGH OPENING REDWOOD
S. S.C. S.D. SECT. SHT. SHEATH'G SIM. SPEC. SQ. S.S.D. STD. STL. STOR. STRUCT. SUSP. SYM.
SOUTH SOLID CORE SMOKE DETECTOR SECTION SHEET SHEATHING SIMILAR SPECIFICATION SQUARE SEE STRUCT. DWGS. STANDARD STEEL STORAGE STRUCTURAL SUSPENDED SYMBOL
T. T.B. T&G T.I. T.O. T.O.C. T.O.P. T.O.W. T.P.H. TRSM. T.V. TYP.
TREAD TOWEL BAR TONGUE AND GROOVE TENANT IMPROVEMENT TOP OF TOP OF CURB TOP OF PLATE TOP OF WALL TOILET PAPER HOLDER TRANSOM TELEVISION TYPICAL
U.O.N
UNLESS OTHERWISE NOTED
V. VERT. V.I.F. V.G.
VENT VERTICAL VERIFY IN FIELD VERTICAL GRAIN
W. W. W/ W.C. WD. WH. W/O W.P. W.R. W.R.C.
WEST WASHING MACHINE WITH WATER CLOSET(TOILET) WOOD WATER HEATER WITHOUT WATERPROOF, WORK POINT WATER RESISTANT WESTERN RED CEDAR
YD.
YARD
FIRE DEPARTMENT
EXTERIOR AREA CALCS:
Exterior Gross Area
Exterior Gross Area Floor (Story) Basement Story 1 Story 2 Story 3 Story 4
Zone Name
Zone Category Gross Exterior Gross Exterior Gross Exterior Gross Exterior Gross Exterior
BASEMENT GROSS EXTERIOR FIRST FLOOR GROSS EXTERIOR 2ND FLOOR GROSS EXTERIOR 3RD FLOOR GROSS EXTERIOR 4TH FLOOR GROSS EXTERIOR
E D A RCH NS D GHAN IT E A N Y
C-29116
3. PLANS & SPECIFICATIONS: THE PLANS AND SPECIFICATIONS SUPPLEMENT EACH OTHER. CONTRACTOR TO IMMEDIATELY REPORT ANY ERRORS, OMISSIONS, AMBIGUITIES OR CONFLICTS IN THE PLANS AND SPECIFICATIONS TO THE ARCHITECT, AND UNTIL THEY ARE RESOLVED, SHALL NOT PROCEED WITH THE AFFECTED WORK.
E
6-30-2019 RENEWAL DATE
OF
CA LI
FO
4. DETAILS: DETAILS SHOWN ARE TYPICAL. SIMILAR DETAILS SHALL APPLY IN SIMILAR CONDITIONS.
USABLE OPEN SPACE (RESIDENTIAL): PER SFPC SEC. 135, 136; 100 SQ.FT. PER UNIT IF PRIVATE. 857 sqft PROVIDED
SYMBOLS
2. EXISTING CONDITIONS AND DIMENSIONS: CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AND DIMENSIONS ON SITE. CALLED-OFF DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED-OFF DIMENSIONS. DIMENSIONS ARE TO FACE OF STUD ORCONCRETE WALLS, UNLESS OTHERWISE NOTED. DIMENSIONS IN SECTIONS AND ELEVATIONS ARE TO TOP OF PLATE OR TOP OF SUBPLATE UNLESS OTHERWISE NOTED.
T
Dane Incels, CFS, 1099 surveyor@sanfranciscosurveyingcompany.com
GENERAL CONTRACTOR
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
A
San Francisco Surveying Company, Inc. 201 Harrison Street Ste 828 San Francisco, CA 94106-2058 p. 415-321-9300 f. 415-543-1915
rg-architecture
ST
REAR YARD: SEC 134: BASIC REQUIREMENT: 25% REQUIRED. SECTION 134 SUBSECTION (E): MODIFICATION OF REQUIREMENTS IN NC AND SOUTH OF MARKET MIXED USE DISTRICTS. THE REAR YARD REQUIREMENTS IN NC AND SOUTH OF MARKET MIXED USE DISTRICTS MAY BE MODIFIED OR WAIVED IN SPECIFIC SITUATIONS AS DESCRIBED IN THIS SUBSECTION (E). (1) GENERAL. THE REAR YARD REQUIREMENT IN NC DISTRICTS MAY BE MODIFIED OR WAIVED BY THE ZONING ADMINISTRATOR PURSUANT TO THE PROCEDURES WHICH ARE APPLICABLE TO VARIANCES, AS SET FORTH IN SECTIONS 306.1 THROUGH 306.5 AND 308.2, IN THE CASE OF NC DISTRICTS, AND IN ACCORDANCE WITH SECTION 307(G), IN THE CASE OF SOUTH OF MARKET MIXED USE DISTRICTS IF ALL OF THE FOLLOWING CRITERIA ARE MET FOR BOTH NC AND SOUTH OF MARKET MIXED USE DISTRICTS: (A) RESIDENTIAL USES ARE INCLUDED IN THE NEW OR EXPANDING DEVELOPMENT AND A COMPARABLE AMOUNT OF USABLE OPEN SPACE IS PROVIDED ELSEWHERE ON THE LOT OR WITHIN THE DEVELOPMENT WHERE IT IS MORE ACCESSIBLE TO THE RESIDENTS OF THE DEVELOPMENT; AND (B) THE PROPOSED NEW OR EXPANDING STRUCTURE WILL NOT SIGNIFICANTLY IMPEDE THE ACCESS OF LIGHT AND AIR TO AND VIEWS FROM ADJACENT PROPERTIES; AND (C) THE PROPOSED NEW OR EXPANDING STRUCTURE WILL NOT ADVERSELY AFFECT THE INTERIOR BLOCK OPEN SPACE FORMED BY THE REAR YARDS OF ADJACENT PROPERTIES.
Erevan O’Neill P.E. erevan@onedesignsf.com www.onedesignsf.com
SURVEYOR
1. CODES: ALL WORK SHALL MEET OR EXCEED THE REQUIREMENTS OF CURRENT APPLICABLE SAN FRANCISCO AND CALIFORNIA CODES, AND ALL OTHER APPLICABLE CODES, ORDINANCES AND REGULATIONS. SEE CODE EDITIONS ON THIS SHEET.
T E CM A
Riyad Ghannam, AIA, Principal: riyad@rg-architecture.com
NEW MIXED-USE OCCUPANCY 4 STORY BUILDING. THREE LEVELS OF SINGLE FAMILY RESIDENTIAL R3 OCCUPANCY OVER COMMERCIAL B OCCUPANCY OVER BASEMENT/PRIVATE GARAGE.
A
CLIENT
GENERAL NOTES
NI
NORTH
SCOPE OF WORK
5. CONTRACTOR RESPONSIBILITY: THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE MEANS, METHODS, TECHNIQUES AND SEQUENCES OF CONSTRUCTION. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL SAFETY PROGRAMS AND PROCEDURES DURING CONSTRUCTION, AND SHALL MAINTAIN THE SHORING AND BRACING UNTIL THE NEW PERMANENT STRUCTURE CAN PROVIDE ADEQUATE VERTICAL AND LATERAL SUPPORT. 6. INSTALLATION: ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTRUCTIONS OR RECOMMENDATIONS, UNLESS AGREED TO OTHERWISE BY THE ARCHITECTS.
Calculated Area 965 925 859 718 540 4,007 sq ft
BUILDING CODE SUMMARY OCCUPANCY: R3/ B AREA CALCS:
Commercial Interior Gross Area - B Occupancy Floor (Story) Story 1
Zone Category
Zone Name
Gross Interior Commercial FIRST FL. GROSS INT. (COMM.)
Calculated Area
REVISIONS NO. DATE
324 324 sq ft
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2
Residential Interior Gross Area - R3 Occupancy Floor (Story)
Zone Name
Zone Category Gross Interior Residential Gross Interior Residential Gross Interior Residential Gross Interior Residential Gross Interior Residential
BSMT. GROSS INT. (RES.) FIRST FL. GROSS INT. (RES.) 2ND FLOOR GROSS INTERIOR 3RD FLOOR GROSS INTERIOR 4TH FLOOR GROSS INTERIOR
840 424 775 624 490 3,153 sq ft
Story 4
Gross Interior Residential
4TH FLOOR GROSS INTERIOR
490 3,477 sq ft
Residential Open Space - R3 Occupancy Floor (Story) Story 3 Story 4 T.O. Roof
Zone Category Open Space Open Space Open Space
OCCUPANT LOAD: R3 = 3153 SQFT/200GROSS SQFT/OCCUPANT = 16 OCCUPANTS B = 326 SQFT/100 = 4 OCCUPANTS
Zone Name DECK DECK ROOF DECK
R1 04/11/19 PLAN REVIEW COMMENTS
Calculated Area
Basement Story 1 Story 2 Story 3 Story 4
TOTAL:
ISSUE
Calculated Area
R1
ISSUE 04/11/19 PLAN REVIEW COMMENTS
OWNER Mr. Harold Tang & Family
104 98 269 471 sq ft
1370 Pacific Ave R1
San Francisco, CA 94109 0155/021
NOTE: EACH OCCUPANCY HAS ITS OWN SEPARATE EXIT CONSTRUCTION TYPE: VA HEIGHT: - ALLOWABLE: 50'-0" PER CBC 2013 TABLE 503 + 20'-0" PER CBC 504.2 (AUTOMATIC SPRINKLER SYSTEM INCREASE) - PROPOSED: 40'-0" STORIES: - ALLOWABLE: 3 PER TABLE 503 + 1 PER SEC. 504.2 = 4 STORIES - PROPOSED: 4 STORIES
SCALE AS NOTED DRAWN BY RG CHECKED BY
NOTE: BUILDING IS EQUIPPED WITH THROUGHOUT WITH AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1
RG
MAXIMUM TRAVEL DISTANCE: - ALLOWABLE: 125'-0" PER TABLE 1021.2(1) FOR STORIES W/ 1 EXIT. 250'-0" FOR STORIES W/ TWO OR MORE EXITS (SEE EGRESS DIAGRAMS A0.07) - PROPOSED: 120'-4'' MAX. FOR STORIES WITH ONE EXIT. 220'-1'' MAX. TOTAL FROM FURTHEST POINT ON ROOF DECK TO EXIT AT PACIFIC AVE. (SEE EGRESS DIAGRAMS A0.07)
201209 DATE
EXITS: ONE EXIT REQUIRED PER CBC SEC. 1021.2 EXCEPTION 3
DRAWING NO. 2 of 42
ACCESSIBILITY: ACCESSIBLE ROUTE AND ONE ACCESSIBLE RESTROOM PROVIDED PER CBC CHAPTER 11B WTIHIN B OCCUPANCY. NO ACCESSIBILITY REQUIRED FOR LESS THAN 4 RESIDENTIAL UNITS PER CBC CHAPTER 11A.
PROJECT DATA
PROJECT NO.
4/29/19
1. FIRE FLOW CALCULATIONS ARE LOCATED ON SHEET A0.08 CEILING FAN
APPLICABLE CODES DEFERRED SUBMITTALS SUBMITTAL OF THE FOLLOWING WORK IS DEFERRED TO A LATER DATE: 1. AUTOMATIC SPRINKLER SYSTEM TO BE FILED UNDER SEPARATE PERMIT 2.SHORING PERMIT FILED SEPARATELY
R
VICINITY MAP
LI RIC
DIRECTORY
2013 CALIFORNIA BUILDING CODE 2013 CALIFORNIA ELECTRICAL CODE 2013 CALIFORNIA MECHANICAL CODE 2013 CALIFORNIA PLUMBING CODE 2013 SAN FRANCISCO BUILDING, ELECTRICAL, MECHANICAL, AND PLUMBING CODE AMENDMENTS
DRAWING NO.
A0.01
rg-architecture 428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
~~P~o couNrfoN
Fes' 415.558.6409
C-29116
3. On August 13, 2015 (continued from previously scheduled hearings on April 23, 2015, May 7, 2015, and July 2, 2015) the Planning Commission held a duly noticed public hearing at a regularly scheduled meeting and took Discretionary Review and approved the project with the following modifications for both buildings in the Project(DRA=0429):
6. As required by the Planning Commission's decision on the Discretionary Review case, the project shall provide a 3-foot setback at the basement/garage and first floor levels facing Lynch Street, add landscaped planting strips adjacent to the driveways that are accessed via Lynch Street, reduce the size of the commercial windows facing Lynch Street and conversion of the ground-floor commercial spaces to residential uses are not allowed.
DESCRIPTION OF VARIANCE AND REAR YARD MODIFICATION SOUGHT: The project is to demolish two existing one-story commercial buildings and construct two new fourstory buildings, each reaching a height of 40 feet, containing one dwelling unit and ground-floor retail space. T'he subject properties are through-lots between Pacific Avenue and Lynch Street. 'The proposal includes two separate buildings on separate lots, filed under separate building permit applications. However, the requests for a Variance and a Rear Yard modification apply to both individual buildings, and are referred collectively herein as the "Project". Section 134 of the Planning Code. requires a rear yard area in the Pacific Avenue Neighborhood Commercial District (NCD) measuring 25% of the lot depth (equivalent to 15 feet on the subject properties), at the lowest level containing a dwelling unit, and at each succeeding story. It should be noted that there is a discrepancy in the Planning Code on this topic, because Section 732.1 specifies a 45% rear yard requirement at all levels of the building. The Project, as modified by the Planning Commission through its Discretionary Review (DR), would provide a minimum three-foot setback from Lynch Street at the basement and first level, a 9' — 9" setback at the second level, a 19' — 4" setback at the third level, and a 28' — 8" setback at the fourth level. Section 145.1 of the Planning Code limits the width of parking entries to no more than 20 feet, or onethird of the building frontage, whichever is less. Given the narrowness of each lot, this Section would allow a vehicular entry of approximately 6.5 feet (for 1364 Pacific Avenue) and six feet (for 1370 Pacific Avenue). The project is requesting a Variance to provide a 10-foot wide vehicular entry for the building at 1364 Pacific Avenue, and an 8-foot wide vehicular entry for the building at 1370 Pacific Avenue.
E
T
a. Provide a 3-foot setback at the basement/garage and first floor levels facing Lynch Street. b. Add landscaped planting strips adjacent to the driveways that are accessed via Lynch Street. c. Reduce the size of the commercial windows facing Lynch Street. d. Record a Notice of Special Restrictions precluding the future conversion of the groundfloor commercial spaces to residential uses.
A
Planning Information: 415.558.6377
T E CM A
Reception: 415.558.6378
E D A RCH NS D GHAN IT E A N Y
ST
Date: September 23, 2015 Case Nos.: 2013.0883DV and 2013.0884DV Project Addresses: 1364-1370 PACIFIC AVENUE Permit Applications:2014.0812.3674 and 2014.0812.3679 Zoning: Pacific Avenue Neighborhood Commercial District 40-X Height and Bulk District Block/Lot: 0155/020, 021 Project Sponsor: Riyad Ghannam r-g architecture 560 3rd Street San Francisco, CA 94107 Staff Contact: Kevin Guy(415)558-6163 kevin.gu~@sfgov.org
5. This Variance Decision and the recorded Notice of Special Restrictions shall be reproduced on the Index Sheet of the construction plans submitted with the Site or Building Permit Application for the Project. This Index Sheet of the construction plans shall reference the Variance Case Number.
2. On April 23, 2014, the Zoning Administrator held a duly noticed public hearing at a regularly scheduled meeting and considered the requested Variance and Rear Yard Modification, but did not take final action on these requests.
A
Variance/Rear Yard Modification Decision
The Project is exempt from the California Environmental Quality Act ("CEQA") as a Class categorical exemption.
NI
1650 Mission St. Suite 400 San Francisco, CA 94103-2479
CASE NOS.2013.0883DV 2013.0884DV 1364-1370 Pacific Avenue
4. The owner of the subject property shall record on the land records of the City and County of San Francisco the conditions attached to this Variance decision as a Notice of Special Restrictions in a form approved by the Zoning Administrator.
PROCEDURAL BACKGROUND:
~ ~ O~bdSn. 0~5~
Variance/Rear Yard Modification Decision September 23, 2015
6-30-2019 RENEWAL DATE
OF
CA LI
R
'a x b a
CASE NOS.2013.0883DV 2013.0884DV 1364-1370 Pacific Avenue
LI RIC
u ~ W
Variance/Rear Yard Modification Decision September 23, 2015
SAN FRANCISCO PLANNING DEPARTMENT
FO
REAR YARD MODIFICATION CRITERIA: Section 134(e) of the Planning Code states that, in order to grant a modification of rear yard requirements within an NCD, the Zoning Administrator must determine that the facts of the case are sufficient to meet the following three criteria: CRITERION 1. Residential uses are included in the new or expanding development and a comparable amount of usable open space is provided elsewhere on the lot or within the development where it is more accessible to the residents of the development.
4. At the same hearing on August 13, 2015, the Zoning Administrator held a public hearing on Variance/Rear Yard Modification Application Nos. 2013.0883V and 2013.0884V.
DECISION: Requirement Met.
GRANTED,in general conformity with the plans on file with this application, shown as EXHIBIT A, to construct two new four-story buildings, each reaching a height of 40 feet, containing one dwelling unit and ground-floor retail space, constructed with a minimum setback of three feet at the basement and first levels of each building, with increased setbacks at the second, third, and fourth floors of each building, a 10-foot wide vehicular entry for the building at 1364 Pacific Avenue, and an 8-foot wide vehicular entry for the building at 1370 Pacific Avenue, subject to the following conditions:
A. The Project contains two residential dwelling units in two separate buildings. As noted above, there is an existing discrepancy in the Planning Code regarding the depth of a required rear yard in the Pacific Avenue NCD (either 25% or 45% of the lot depth). For the property at 1364 Pacific Avenue, acode-complying rear yard would yield an open space of either 263 square feet or 473 square feet. The building at 1364 Pacific Avenue includes approximately 566 square feet of usable open area in the form of decks at the third level, fourth level, and roof. For the property at 1370 Pacific Avenue, acode-complying rear yard would yield an open space of either 300 square feet or 540 square feet. The building at 1370 Pacific Avenue includes approximately 473 square feet of usable open area in the form of decks at the third level, fourth level, and roof. It should be noted that additional decks were proposed at lower levels in prior iterations of the Project, but were deleted by the Project Sponsor to address noise and privacy concerns raised by the neighbors of the site and by the DR Requestors.
Any future physical expansion, even in the buildable area, shall be reviewed by the Zoning Administrator to determine if the expansion is compatible with existing neighborhood character and scale. If the Zoning Administrator determines that there would be a significant or extraordinary impact, the Zoning Administrator shall require either notice to adjacent and/or affected property owners or a new Variance application be sought and justified. 2. T'he proposed project must meet these conditions and all applicable City Codes. In case of conflict, the more restrictive controls apply.
CRITERION 2. The proposed new or expanding structure will not significantly impede the access of light and air to and views from adjacent properties.
3. Minor modifications as determined by the Zoning Administrator may be permitted.
Requirement Met.
SAN FRANCISCO PLANNING DEPARTMENT
www.sfplanning.org
2
SAN FRANCISCO PL4NNING DEPARTMENT
3
REVISIONS NO. DATE
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 Variance/Rear Yard Modification Decision September 23, 2015
CASE NOS.2013.0883DV 2013.0884DV 1364-1370 Pacific Avenue
A. The purpose of the rear yard requirement is to provide a sense of openness between structures and promote a pattern of mid-block open space, and the sunlight access plane reflected in the Project reinforces the sense of openness and preservation of light on the alley. Planning Code Section 261.1 requires that the buildings observe a 45-degree sunlight access plane, measured beginning at the property line on the north (opposite) side of Lynch Street. This results in a terraced configuration of the Project above the second story, so that the upper stories would be minimally visible from Lynch Street, and sunlight will be allowed to reach Lynch Street itself, as well as the other existing buildings which abut Lynch Street. Although the measured overall height of the buildings would be taller than several other buildings on the subject block, the rear of the buildings along the Lynch Street frontage would be expressed as a two-story element. This two-story expression is consistent with the majority of buildings fronting on Lynch Street, and would be lower than several other buildings expressing three- and four-story elevations on the street. T'he proposed configuration of the project is consistent with a traditional urban pattern of buildings built to the edge of the sidewalk, and is consistent with the scale of other existing buildings on Lynch Street.
CASE NOS.2013.OS83DV 2013.0884DV 1364-1370 Pacific Avenue
the Planning Code limits the width of parking entries to a maximum of one-third of the building frontages of the Project, application of this ratio would allow a vehicular entry of approximately 6.5 feet (for 1364 Pacific Avenue) and six feet (for 1370 Pacific Avenue). The subject lots are narrower than many other lots in the vicinity, and for properties containing residential development in general.
Requirement Met. The purpose of the rear yard requirement is to provide a sense of openness between structures and promote a pattern of mid-block open space, and the sunlight access plane reflected in the buildings reinforces the sense of openness and preservation of light on the alley. There is currently no pattern of mid-block open space for lots located between Pacific Avenue and Lynch Street. Separation is provided instead by the presence of Lynch Street itself. The Project would be built close to the rear properly line, consistent with the pattern of the remainder of the block. Given the narrowness of Lynch Street, this development pattern creates the intimate, granular scale of an 'outdoor room'.
Section 305(c) of the Planning Code states that in order to grant a variance, the Zoning Administrator must determine that the facts of the case are sufficient to establish the following five findings: FINDING 1. That there are exceptional or extraordinary circumstances applying to the property involved or to the intended use of the property that do not apply generally to other properties or uses in the same class of district.
B. Multiple properties in the vicinity consist of residential buildings or mixed-use buildings that do not include off-street parking. These conditions are particularly found on those properties that were developed prior to the enactment of zoning regulations. The Planning Code regulations for the Pacific Avenue NCD require a minimum of one off-street parking space for each residential unit.
ISSUE
FINDING 2. That owing to such exceptional and extraordinary circumstances the literal enforcement of specified provisions of this Code would result in a practical difficulty or unnecessary hardship not created by or attributed to the applicant or the owner of the property.
A. The subject properties are each narrow, with the property at 1364 Pacific Avenue measuring 17.5 feet in width, and the property at 1370 Pacific Avenue measuring 20 feet in width. Because
4
FINDING 5. The granting of such variance will be in harmony with the general purpose and intent of this Code and will not adversely affect the General Plan.
04/11/19 PLAN REVIEW COMMENTS
Requirement Met.
OWNER
A. This development is consistent with the generally stated intent and purpose of the Planning Code to promote orderly and beneficial development. Planning Code Section 101.1 establishes eight priority-planning policies and requires review of variance applications for consistency with said policies. The project meets all relevant policies, including conserving neighborhood character, and maintaining housing stock.
A. Due to the narrowness of the lots, strict application of the maximum vehicular entry widths would create driveways and garages in the Project which are too narrow to provide physical access for passenger vehicles. As such, the Project would not be able to meet the off-street parking requirements of the Planning Code, creating both a practical difficulty and an unnecessary hardship. The narrowness of the lots is apre-existing condition, and is not a condition created by the applicant or property owner.
1. Some existing neighborhood retail uses which are currently operated by the property owner will be removed by the project, however, each building in the Project will include small-scale ground-floor retail uses in keeping with the mixed residential/commercial character of Pacific Avenue.
FINDING 3. That such variance is necessary for preservation and enjoyment of a substantial property right of the subject property, possessed by other property in the same class of district.
3. T'he proposed project will have no negative effect on the City's supply of affordable housing, and will increase the supply of housing by adding two dwelling units.
Requirement Met. 4. T'he proposed project does not adversely affect neighborhood parking or public transit.'The granting of the variances will enable the project to comply with the off-street parking requirements of the Planning Code. Access to these spaces will be from Lynch Street, and will not conflict with the operation of buses on Pacific Avenue.
1370 Pacific Ave San Francisco, CA 94109 0155/021
SCALE AS NOTED DRAWN BY RG CHECKED BY RG PROJECT NO.
FINDING 4. That the granting of such variance will not be materially detrimental to the public welfare or materially injurious to the property or improvements in the vicinity.
5. The project will have no effect on the City's industrial and service sectors.
201209 DATE
6. The proposed project will have no effect on the City's preparedness to protect against injury and loss of life in an earthquake.
4/29/19
Requirement Met.
SAN FRANCISCO PL4NNING DEPARTMENT
Mr. Harold Tang & Family
2. T'he proposed project will be in keeping with the existing housing and neighborhood character.
A. Granting the variance will allow the Project to provide access to off-street parking. Given the existing density of the area, access to on-street parking in generally limited in this neighborhood. Because Pacific Avenue is narrower than other major public streets in the area, and is served by two existing bus lines, on-street parking is prohibited on the north side of
Requirement Met.
CASE NOS.2013.0883DV 2013.0884DV 1364-1370 Pacific Avenue
B. The Planning Department is not aware of any opposition to the requested variance regarding maximum vehicular entry widths.
A. Granting the variance will allow the Project to provide access to off-street parking, which is a requirement of the Planning Code and is a property right enjoyed by other properties in the vicinity.
VARIANCE FINDINGS:
R1 04/11/19 PLAN REVIEW COMMENTS Variance/Rear Yard Modification Decision September 23, 2015
Pacific Avenue east of Larkin Street. These circumstances compound the scarcity of on-street parking availability in the neighborhood. By providing suitable access to off-street parking for the Project, the granting of the variance with be beneficial to the public welfare by avoiding further impacts to on-street parking availability.
Requirement Met.
CRITERION 3. The proposed new or expanding structure will not adversely affect the interior block open space formed by the rear yards of adjacent properties.
SAN FRANCISCO PL4NNING DEPApTMENT
Variance/Rear Yard Modification Decision September 23, 2015
C J
7. The project will have no effect on the City's landmarks or historic buildings.
DRAWING NO. 3 of 42
8. The project would not affect any existing or planned public parks or open spaces.
VARIANCE DECISION
SAN FRANCISCO PLANNING DEPARTMENT
6
DRAWING NO.
A0.02
rg-architecture 428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
LI RIC
T E CM A
E D A RCH NS D GHAN IT E A N Y
T
REVISIONS NO. DATE
NI
A
E
6-30-2019 RENEWAL DATE
OF
CA LI
R
ST
A
C-29116
FO
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
ISSUE 04/11/19 PLAN REVIEW COMMENTS
OWNER Mr. Harold Tang & Family
1370 Pacific Ave San Francisco, CA 94109 0155/021
SCALE AS NOTED DRAWN BY RG CHECKED BY RG PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 4 of 42
NSR & AFFIDAVIT OF SERVICE DRAWING NO.
NOTICE OF SPECIAL RESTRICTIONS
B.O.A. AFFIDAVIT OF SERVICE
A0.03
rg-architecture
SUBJECT PROPERTY
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
SUBJECT PROPERTY
LI RIC
T E CM A
E D A RCH NS D GHAN IT E A N Y
T
VIEW LOOKING WEST ON PACIFIC AVE
A
F
VIEW LOOKING AT FACADE OF SUBJECT PROPERTY
VIEW LOOKING EAST ON PACIFIC AVE
B
NI
A
E
6-30-2019 RENEWAL DATE
OF
CA LI
R
ST
A
C-29116
FO
C
G
E SUBJECT PROPERTY 1370 PACIFIC AVE
REVISIONS NO. DATE
ISSUE
08/12/14 ORIGINAL SITE PERMIT
A
B
C
D
11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
N
ISSUE 04/11/19 PLAN REVIEW COMMENTS
BUILDINGS ON THE FACING SIDE OF THE STREET
D
OWNER Mr. Harold Tang & Family
SUBJECT PROPERTY
1370 Pacific Ave REAR OF SUBJECT PROPERTY
San Francisco, CA 94109 0155/021
REAR OF SUBJECT PROPERTY
SCALE AS NOTED DRAWN BY RG CHECKED BY RG PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 6 of 42
SITE CONTEXT
DRAWING NO.
VIEW LOOKING EAST ON LYNCH ALLEY
D
VIEW OF SUBJECT PROPERTY ON LYNCH ALLEY
E
VIEW LOOKING WEST ON LYNCH ALLEY
F
A0.05
(b) Indicate in one of the columns below which type of project is proposed. If applicable, fill in the blank lines below to identify the number of points the project must meet or exceed. A LEED or GreenPoint checklist is not required to be submitted with the site permit application, but using such tools as early as possible is strongly recommended. Solid circles in the column indicate mandatory measures required by state and local codes. For projects applying LEED or GreenPoint Rated, prerequisites of those systems are mandatory. See relevant codes for details.
LEED PROJECTS
Water Efficient Irrigation - Projects that include ≥
1,000 square feet of new or modified landscape must comply with the SFPUC Water Efficient Irrigation Ordinance.
Construction Waste Management – Comply with
the San Francisco Construction & Demolition Debris Ordinance
Recycling by Occupants: Provide adequate space
and equal access for storage, collection and loading of compostable, recyclable and landfill materials. See Administrative Bulletin 088 for details.
● ● ● ●
Base number of required points:
Base number of required Greenpoints:
75
Adjustment for retention / demolition of historic features / building:
20
Final number of required points (base number +/adjustment)
95
GreenPoint Rated (i.e. meets all prerequisites)
Construction Waste Management – 75% Diversion
AND comply with San Francisco Construction & Demolition Debris Ordinance - LEED MR 2, 2 points
Energy Efficiency: Demonstrate a 10% energy use reduction compared to Title 24, Part 6 (2013). Meet all California Green Building Standards Code requirements (CalGreen measures for residential projects have been integrated into the GreenPoint Rated system.)
● ●
Notes 1) New residential projects of 4 or more occupied floors must use the “New Residential High-Rise” column. New residential with 3 or fewer occupied floors must use the “New Residential Low Rise” column. 2) LEED for Homes Mid-Rise projects must meet the “Silver” standard, including all prerequisites. The number of points required to achieve Silver depends on unit size. See LEED for Homes Mid-Rise Rating System to confirm the base number of points required.
60
2
SILVER
GOLD
GOLD
GOLD
50
60
60
60
n/a
Effective 1/1/2012: Generate renewable energy on-site ≥1% of total annual energy cost (LEED EAc2), OR Demonstrate at least 10% energy use reduction (compared to Title 24 Part 6 2013), OR Purchase Green-E certified renewable energy credits for 35% of total electricity use (LEED EAc6).
Enhanced Commissioning of Building Energy Systems LEED EA 3
Water Use - 30% Reduction LEED WE 3, 2 points Enhanced Refrigerant Management LEED EA 4 Indoor Air Quality Management Plan LEED IEQ 3.1
Bicycle parking: Provide short-term and long-term bicycle
●
●
●
●
LEED prerequisite
●
●
occupied spaces of mechanically ventilated buildings (or LEED credit IEQ 5).
Air Filtration: Provide MERV-13 filters in residential buildings in
●
Water Meters: Provide submeters for spaces projected to consume >1,000 gal/day,
● ●
Meet C&D ordinance only
●
LEED prerequisite only
for showerheads, lavatories, kitchen faucets, wash fountains, water closets, and urinals.
Commissioning: For new buildings greater than 10,000 square feet, commissioning
shall be included in the design and construction of the project to verify that the building systems and components meet the owner’s project requirements. OR for buildings less than 10,000 square feet, testing and adjusting of systems is required.
n/r
n/r
n/r
n/r
n/r
●
Addition only
● ●
(Testing & Balancing)
● ●
● ●
●
●
●
●
●
●
resilient flooring complying with the VOC-emission limits defined in the 2009 Collaborative for High Performance Schools (CHPS) criteria or certified under the Resilient Floor Covering Institute (RFCI) FloorScore program.
●
●
Environmental Tobacco Smoke: Prohibit smoking within 25 feet of building
● ●
● ● ●
VOC limits and California Code of Regulations Title 17 for aerosol adhesives.
Paints and coatings: Comply with VOC limits in the Air Resources Board Architectural Coatings Suggested Control Measure and California Code of Regulations Title 17 for aerosol paints. Carpet: All carpet must meet one of the following:
● ● ● ● ●
● ●
air-quality hot-spots (or LEED credit IEQ 5). (SF Health Code Article 38 and SF Building Code 1203.5)
n/r
Acoustical Control: Wall and roof-ceilings STC 50, exterior
●
windows STC 30, party walls and floor-ceilings STC 40.
●
Adhesives, sealants, and caulks: Comply with VOC limits in SCAQMD Rule 1168
●
Air Filtration: Provide at least MERV-8 filters in regularly
●
motorized parking capacity each, or meet San Francisco Planning Code Sec 155, whichever is greater (or LEED credit SSc4.2).
Protect duct openings and mechanical equipment during construction
Designated parking: Mark 8% of total parking stalls for
consume more than 1,000 gal/day, or more than 100 gal/day if in building over 50,000 sq. ft.
Fuel efficient vehicle and carpool parking: Provide stall marking for
Bicycle parking: Provide short-term and long-term bicycle parking for 5% of total
or >100 gal/day if in buildings over 50,000 sq. ft.
●
●
Water Meters: Provide submeters for spaces projected to
● ●
Indoor Water Efficiency: Reduce overall use of potable water within the building by 20%
parking for 5% of total motorized parking capacity each, or meet San Francisco Planning Code Sec 155, whichever is greater, or meet LEED credit SSc4.2.
low-emitting, fuel efficient, and carpool/van pool vehicles.
● ●
Energy Efficiency: Comply with California Energy Code, Title 24, Part 6 (2013).
low-emitting, fuel efficient, and carpool/van pool vehicles; approximately 8% of total spaces.
50
Renewable Energy or Enhanced Energy Efficiency
Low-Emitting Materials LEED IEQ 4.1, 4.2, 4.3, and 4.4
●
SILVER
Specific Requirements: (n/r indicates a measure is not required)
Comply with California Title-24 Part 6 (2013) and meet LEED minimum energy performance (LEED EA p2)
Proposing a GreenPoint Rated Project (Indicate at right by checking the box.)
GOLD
Adjustment for retention / demolition of historic features / building: Final number of required points (base number +/- adjustment)
Energy Use
GREENPOINT RATED PROJECTS
Type of Project Proposed (Check box if applicable)
Overall Requirements: LEED certification level (includes prerequisites):
Addition Other New ≥1,000 sq ft NonOR Residential Alteration ≥$200,0003
Meet LEED prerequisites Meet LEED prerequisite
●
n/r
n/r
●
●
n/r
CalGreen 4.504.1
CalGreen 4.504.1
CalGreen 5.504.3
CalGreen 5.504.3
CalGreen 4.504.1
●
●
●
●
●
See San Francisco Planning Code 155
Meet LEED prerequisite
●
n/r
●
n/r
n/r
●
See CBC 1207
Composite wood: Meet CARB Air Toxics Control Measure for Composite Wood Resilient flooring systems: For 80% of floor area receiving resilient flooring, install
entries, outdoor air intakes, and operable windows.
● n/r
See San Francisco Planning Code 155
1. Carpet and Rug Institute Green Label Plus Program, 2. California Department of Public Health Standard Practice for the testing of VOCs (Specification 01350), 3. NSF/ANSI 140 at the Gold level, 4. Scientific Certifications Systems Sustainable Choice, OR 5. California Collaborative for High Performance Schools EQ 2.2 and listed in the CHPS High Performance Product Database AND carpet cushion must meet Carpet and Rug Institute Green Label, AND indoor carpet adhesive & carpet pad adhesive must not exceed 50 g/L VOC content.
● ● n/r
●
n/r
●
(addition only)
● n/r
●
(envelope alteration & addition only)
n/r
n/r
n/r
● n/r
Air Filtration: Provide at least MERV-8 filters in regularly occupied spaces of
mechanically ventilated buildings.
Acoustical Control: Wall and roof-ceilings STC 50, exterior windows STC 30, party
●
CFCs and Halons: Do not install equipment that contains CFCs or Halons.
●
walls and floor-ceilings STC 40.
(envelope alteration & addition only)
●
Additional Requirements for New A, B, I, OR M Occupancy Projects 5,000 - 25,000 Square Feet Construction Waste Management – Divert 75% of construction and demolition
debris AND comply with San Francisco Construction & Demolition Debris Ordinance.
●
Meet C&D ordinance only
●
n/r
Renewable Energy or Enhanced Energy Efficiency
Effective January 1, 2012: Generate renewable energy on-site equal to ≥1% of total annual energy cost (LEED EAc2), OR demonstrate a 10% energy use reduction compared to Title 24 Part 6 (2013), OR purchase Green-E certified renewable energy credits for 35% of total electricity use (LEED EAc6).
AI N
T E CM A
R
I C R IL
L AC
square feet must implement a Stormwater Control Plan meeting SFPUC Stormwater Design Guidelines
Type of Project Proposed (Indicate at right)
Requirements below only apply when the measure is applicable to the project. Code references below are applicable to New Non-Residential buildings. Corresponding requirements for additions and alterations can be found in Title 24 Part 11, Division 5.7. Requirements for additions or alterations apply to applications received July 1, 2012 or after.3
FI
Stormwater Control Plan: Projects disturbing ≥5,000
●
Large First Time Commercial Residential Commerical Major Alteration Major Alteration Interior
Y DA NE DES
construction site Stormwater Pollution Prevention Plan and implement SFPUC Best Management Practices.
New High Rise Residential
O
Construction activity stormwater pollution prevention and site runoff controls - Provide a
New Large Commercial
New Low Rise Residential
OTHER APPLICABLE NON-RESIDENTIAL PROJECTS
ST
A
T
DRAWING NO. 7 of 42
ALL PROJECTS, AS APPLICABLE
OF
Design Professional/Applicant: Sign & Date
RENEWAL DATE
4
6-30-2019
R3
E
Number of occupied floors
04/11/19 ADDENDUM 2
Primary Occupancy
ISSUE
1370 Pacific Avenue, San Francisco, CA 94109
San Francisco, CA 94109 0155/021
4,007 Sq Ft
0155/021
C-29116
Gross Project Area
AND
Address
1370 PACIFIC AVENUE Insert Project Name / Titleblock here
1370 Pacific Avenue
Block/Lot
428 SOUTH VAN NESS AVENUE SAN FRANCISCO, CA 94103 415.699.3640 mail@rg-architecture.com
Project Name
(a) Provide basic information about the project in the box at left. This info determines which green building requirements apply.
A RC GHANHIT N
BASIC INFORMATION: These facts, plus the primary occupancy, determine which requirements apply. For details, see AB 093 Attachment A Table 1.
Version: July 1, 2014
As part of application for site permit, this form acknowledges the specific green building requirements that apply to a project under San Francisco Green Building Code, California Title 24 Part 11, and related codes. Attachment C3, C4, C5, C6, C7, or C8 will be due with the applicable addendum. To use the form:
rg-architecture
Green Building: Site Permit Submittal
Attachment C-2: Green Building: Site Permit Submittal
Instructions:
R1
R1
rg-architecture 428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
LI RIC
T E CM A
E D A RCH NS D GHAN IT E A N Y
T
REVISIONS NO. DATE
6-30-2019 RENEWAL DATE
OF
CA LI
NI
A
E
R
ST
A
C-29116
FO
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
ISSUE 04/11/19 PLAN REVIEW COMMENTS
OWNER Mr. Harold Tang & Family
1370 Pacific Ave San Francisco, CA 94109 0155/021
SCALE AS NOTED DRAWN BY RG CHECKED BY RG PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 10 of 42
GREEN BUILDING NOTES DRAWING NO.
A0.06D
R1
2
1
(N) CURB CUT
LYNCH STREET PUBLIC WAY LEVEL OF DISCHARGE
rg-architecture
2
E
C AN T S DI " L E 4'-8 AV 1
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
TR B
B
HP
EXIT
B
B
B
B
CE
16'-6" 8'-4" 12 R. @ 7 3/4" 11 T. @ 10"
UP
EXIT ACCESS 26'-2"
UP
14 R. @ 7 9/16" 13 T. @ 10" 12 R. @ 7 3/4" 11 T. @ 10"
EXIT ACCESS 60'-5"
14 R. @ 7 9/16" 13 T. @ 10"
R3 OCC
F
EXIT ACCESS 19'-1"
TR
TR
R3 OCC
UP
R1
6-30-2019 RENEWAL DATE
OF
CA LI
FO
E
TR
14 R. @ 7 5/16" 13 T. @ 10"
EXIT ACCESS 22'-0"
E
EXIT ACCESS 43'-11"
DN 14 R. @ 7 5/16" 13 T. @ 10"
TR AV EL D 9'- IST 6" AN C
C AN T S DI " L '-4 E AV 11
0
UP
6'-8"
17 R. @ 7 1/2" 16 T. @ 10"
EXIT ACCESS 23'-5"
15 R. @ 7 3/4"17 R. @ 7 1/2" 14 T. @ 10" 16 T. @ 10"
UP
EXIT PATH OF TRAVEL FROM ROOF TO 2ND FLOOR = 124'-1"
E
LD 13 IST '-3 A NC " E
E
B OCC
DN
TR AV E
C AN T S DI " L '-9 E AV 17
HW
2'-3"
C-29116
T
DN
T E CM A
E
C AN T IS L D '-9" E 3 AV 1
A
DN
E D A RCH NS D GHAN IT E A N Y
ST
R3 OCC
AN ST I D " EL 2'-8 V 1 A TR
LI RIC
HP
EXIT
A
1
NI
2
R
1
4'
8'
SECTION SCALE: 1/8" = 1'-0"
16'
8
EXIT
LONGEST EXIT PATH OF TRAVEL CALCULATIONS - R3 OCCUPANCY
STORIES W/ 1 EXIT
1
2
STORY 2 SCALE: 1/8" = 1'-0" 4'
8'
4'
8'
2
B
A
1
2
BASEMENT SCALE: 1/8" = 1'-0"
2
16'
0
1
B
A
2
STORY 1 SCALE: 1/8" = 1'-0"
3 0
1
A
PACIFIC AVENUE PUBLIC WAY LEVEL OF DISCHARGE
1
16'
4'
8'
2
B
B
2
B
PLAN 23'-5" 28'-0" 27'-10" 42'-6" 26'-2" 8'-4"
+ + + + + +
STAIR 14'-8" 12'-8" 13'-9" 13'-3" 9'-6"
= = = = = = =
- ALLOWABLE: 250'-0" PER CBC 2013 TABLE 1016.2 (AUTOMATIC SPRINKLER SYSTEM INCREASE) - PROPOSED: 220'-1" COMPLIES
1
16'
1
STORY ROOF 4TH 3RD 2ND 1ST BASEMENT TOTAL -
TOTAL 38'-1" 78'-9" 120'-4" 176'-1" 211'-9" 220'-1" 220'-1"
TOTAL 1 EXIT STY R-3
120'-4"
BASEMENT
93'-9"
- ALLOWABLE: 125'-0" PER CBC 2013 TABLE 1014.3 (AUTOMATIC SPRINKLER SYSTEM INCREASE) - PROPOSED: 120'-4" MAX. - COMPLIES EXIT PATH OF TRAVEL CALCULATIONS - B OCCUPANCY STORY PLAN STAIR 1ST 43'-11" = 43'-11"
REVISIONS NO. DATE
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
B
ISSUE 04/11/19 PLAN REVIEW COMMENTS
PLANTER
OWNER
PLANTER
R3 OCC
San Francisco, CA 94109 0155/021
DN
R3
1370 Pacific Ave
EXIT ACCESS 45'-5"
R3 OCC
EXIT ACCESS 32'-9"
Mr. Harold Tang & Family
SCALE
1 HR LVL ROOF ASSEMBLY SCALE: 1' = 1'-0"
EXIT ACCESS 27'-10"
13 R. @ 7 3/4" 12 T. @ 10"
DRAWN BY
W/D
15 R. @ 7 3/4" 14 T. @ 10"
AS NOTED F05
RG CHECKED BY RG PROJECT NO. 201209
UP
FD
EXIT ACCESS 28'-0"
UP
15 R. @ 7 3/4" 14 T. @ 10"
13 R. @ 7 3/4" 12 T. @ 10"
DN
EXIT ACCESS 23'-5"
DN 15 R. @ 7 3/4" 14 T. @ 10"
0
A
1 STAIR
A
2 STAIRS
A
2 R. @ 5 1/4" UP 1 T. @ 1'-3"
EXIT
DATE 4/29/19
A
A
A
A
A
A
DRAWING NO. 11 of 42
1
2
1
2
1
EGRESS DIAGRAM & WATER FLOW INFORMATION
2
DRAWING NO.
SCALE: 1/8" = 0
4'
8'
16'
ROOF 1'-0"
STORY 4 SCALE: 1/8" = 1'-0"
6 0
4'
8'
16'
STORY 3 SCALE: 1/8" = 1'-0"
5 0
4'
8'
16'
4
A0.07
rg-architecture 428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
Page 1 of 9
C-29116
Calculation Description Title 24 Analysis
03
Project Location 1370 Pacific Ave
04
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis. NO SPECIAL FEATURES REQUIRED
City San Francisco
06
05
Zip Code 94109 Climate Zone CZ3
09
10
Building Type Single Family
11
12
Project Scope Newly Constructed
13
Number of Dwelling Units 1
15
Number of Zones 4
17
Number of Stories 4
19
Natural Gas Available Yes
Total Cond. Floor Area
(ft2)
2428
Slab Area (ft2) 0
16
Addition Cond. Floor Area N/A
20
Addition Slab Area
(ft2)
N/A
Software Version EnergyPro 6.8
Glazing Percentage (%) 26.4%
This is the sum of the annual TDV energy consumption for energy use components included in the performance compliance approach for the Standard Design Building (Energy Budget) and the annual TDV energy consumption for lighting and components not regulated by Title 24, Part 6 (such as domestic appliances and consumer electronics) and accounting for the annual TDV energy offset by an on-site renewable energy system.
01
Building Complies with Computer Performance
02
This building incorporates features that require field testing and/or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider.
Reference Energy Use
Energy Design Rating
Margin
Percent Improvement
75.08
69.16
5.92
7.9%
Total Energy (kTDV/f2-yr)* This compliance analysis is valid only for permit applications through December 31, 2016
* includes calculated Appliances and Miscellaneous Energy Use (AMEU) BUILDING - FEATURES INFORMATION
ENERGY USE SUMMARY
01
02
03
04
05
06
07
Percent Improvement
Project Name
Conditioned Floor Area (ft2)
Number of Dwelling Units
Number of Bedrooms
Number of Zones
Number of Ventilation Cooling Systems
Number of Water Heating Systems
-0.81
-7.2%
1370 Pacific Ave
2428
1
3
4
0
1
0.72
3.33
82.2%
1.04
1.04
0.00
0.0%
12.63
9.23
3.40
26.9%
04
05
06
07
08
Energy Use (kTDV/ft2-yr)
Standard Design
Proposed Design
Compliance Margin
Space Heating
11.30
12.11
Space Cooling
4.05
IAQ Ventilation Water Heating Photovoltaic Offset
----
0.00
0.00
----
Compliance Energy Total
29.02
23.10
5.92
20.4%
CA Building Energy Efficiency Standards - 2013 Residential Compliance
FO
ENERGY DESIGN RATING
COMPLIANCE RESULTS
218-N0289504A-000000000-0000
CA LI
Building-level Verifications: • IAQ mechanical ventilation Cooling System Verifications: • -- None -HVAC Distribution System Verifications: • -- None -Domestic Hot Water System Verifications: • -- None --
Front Orientation (deg/Cardinal) 180
21
RENEWAL DATE
OF
The following is a summary of the features that must be field-verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is provided in the building components tables below.
Compliance Manager Version BEMCmpMgr 2013-4b (433)
08
6-30-2019
HERS FEATURE SUMMARY
Standards Version Compliance 2015
07
E
T
02
Registration Number:
Page 2 of 9
A
Project Name 1370 Pacific Ave
18
Input File Name: 1370 Pacific Av Res v6.ribdx
REQUIRED SPECIAL FEATURES
01
14
Calculation Date/Time: 09:18, Fri, Oct 26, 2018
Calculation Description: Title 24 Analysis
ST
GENERAL INFORMATION
Project Name: 1370 Pacific Ave
A
Input File Name: 1370 Pacific Av Res v6.ribdx
NI
Calculation Date/Time: 09:18, Fri, Oct 26, 2018
Calculation Description: Title 24 Analysis
CF1R-PRF-01
R
Project Name: 1370 Pacific Ave
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
LI RIC
CF1R-PRF-01
T E CM A
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
E D A RCH NS D GHAN IT E A N Y
Registration Date/Time:
HERS Provider:
2018-10-26 09:28:55
Report Version - CF1R-01212016-433
CalCERTS inc.
Report Generated at: 2018-10-26 09:18:54
Registration Number:
Registration Date/Time:
218-N0289504A-000000000-0000
CA Building Energy Efficiency Standards - 2013 Residential Compliance
HERS Provider:
2018-10-26 09:28:55
Report Version - CF1R-01212016-433
CalCERTS inc.
Report Generated at: 2018-10-26 09:18:54
REVISIONS NO. DATE
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
CF1R-PRF-01
Project Name: 1370 Pacific Ave
Calculation Date/Time: 09:18, Fri, Oct 26, 2018
Calculation Description: Title 24 Analysis
Input File Name: 1370 Pacific Av Res v6.ribdx
Page 3 of 9
ZONE INFORMATION 01
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
CF1R-PRF-01
Project Name: 1370 Pacific Ave
Calculation Date/Time: 09:18, Fri, Oct 26, 2018
Calculation Description: Title 24 Analysis
Input File Name: 1370 Pacific Av Res v6.ribdx
Page 4 of 9
R1 04/11/19 PLAN REVIEW COMMENTS
OPAQUE SURFACES 02
03
04
05
06
Zone Name
Zone Type
HVAC System Name
Zone Floor Area (ft2)
Avg. Ceiling Height
Water Heating System 1
Story 1 Area
Conditioned
Mini-Split Heat Pump1
429
10
DHW Sys 1
Story 2 Zone
Conditioned
Mini-Split Heat Pump1
799
9
DHW Sys 1
Story 3 Zone
Conditioned
Mini-Split Heat Pump1
644
9
DHW Sys 1
Story 4 Zone
Conditioned
Mini-Split Heat Pump1
556
9
DHW Sys 1
07
01
Water Heating System 2
02
03
04 Azimuth
05 Orientation
06
07
Gross Area
(ft2)
Window & Door Area
08 (ft2)
Name
Zone
Construction
North Wall
Story 1 Area
R-19 Wall
0
Back
173.3
East Wall
Story 1 Area
R-19 Wall
90
Right
200
90
West Wall
Story 1 Area
R-19 Wall
270
Left
214.5
90
West Wall 2
Story 1 Area
R-19 Wall
270
Left
250
South Wall
Story 1 Area
R-19 Wall
180
Front
73
Interior Surface 2
Story 1 Area>>__Garage__
R-19 Floor No Crawlspace
Interior Surface 3
Story 1 Area>>__Garage__
R-19 Floor No Crawlspace
North Wall 2
Story 2 Zone
R-19 Wall
0
Back
East Wall 2
Story 2 Zone
R-19 Wall
90
Right
South Wall 2
Story 2 Zone
R-19 Wall
180
West Wall 3
Story 2 Zone
R-19 Wall
270
63
Tilt (deg) 90
90
ISSUE
56
90
04/11/19 PLAN REVIEW COMMENTS
173.3
81
90
465.75
12
90
OWNER
Front
173.3
80.6
90
Mr. Harold Tang & Family
Left
465.75
333 250
90
North Wall 3
Story 3 Zone
R-19 Wall
0
Back
156
98
90
East Wall 3
Story 3 Zone
R-19 Wall
90
Right
378
8.25
90
South Wall 3
Story 3 Zone
R-19 Wall
180
Front
156
67.4
90
West Wall 4
Story 3 Zone
R-19 Wall
270
Left
378
North Wall 4
Story 4 Zone
R-19 Wall
0
Back
156
98
90 90
East Wall 4
Story 4 Zone
R-19 Wall
90
Right
288
8.25
90
South Wall 4
Story 4 Zone
R-19 Wall
180
Front
156
67.4
90
West Wall 5
Story 4 Zone
R-19 Wall
270
Left
288
North Wall 5
__Garage__
6 Concrete Wall
270
Left
152
90 70
90
East Wall 5
__Garage__
6 Concrete Wall
90
Right
448
90
South Wall 5
__Garage__
6 Concrete Wall
180
Front
152
90
West Wall 6
__Garage__
6 Concrete Wall
270
Left
448
90
1370 Pacific Ave San Francisco, CA 94109 0155/021
SCALE AS NOTED DRAWN BY RG CHECKED BY RG Registration Number:
218-N0289504A-000000000-0000
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
2018-10-26 09:28:55
Report Version - CF1R-01212016-433
HERS Provider:
CalCERTS inc.
Report Generated at: 2018-10-26 09:18:54
Registration Number:
218-N0289504A-000000000-0000
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
2018-10-26 09:28:55
Report Version - CF1R-01212016-433
HERS Provider:
CalCERTS inc.
Report Generated at: 2018-10-26 09:18:54
PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 12 of 42
T24 RESIDENTIAL REPORT DRAWING NO.
A0.08
rg-architecture 428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
Calculation Date/Time: 09:18, Fri, Oct 26, 2018
Calculation Description: Title 24 Analysis
Input File Name: 1370 Pacific Av Res v6.ribdx
Page 5 of 9
Project Name: 1370 Pacific Ave
Calculation Date/Time: 09:18, Fri, Oct 26, 2018
Calculation Description: Title 24 Analysis
Input File Name: 1370 Pacific Av Res v6.ribdx
Page 6 of 9
DOORS 04
05
07
08
09
10
11
01
02
03
04
Name
Zone
Type
Roof Rise (x in 12)
Roof Pitch
Roof Tilt (deg)
Roof Reflectance
Roof Emittance
Framing Factor
Name
Side of Building
Area (ft2)
U-factor
Roof
Story 1 Area
R-38 Roof No Attic
Back
123.5
Door
North Wall 5
70.0
1.00
0
0
0
0
0.1
0.85
0.1
Roof 2
Story 2 Zone
R-38 Roof No Attic
Back
155
0
0
0
0
0.1
0.85
0.1
Roof 3
Story 3 Zone
R-38 Roof No Attic
Back
154
0
0
0
0
0.1
0.85
0.1
Roof 4
Story 4 Zone
R-38 Roof No Attic
Back
556
0
0
0
0
0.1
0.85
0.1
Orientatio Skylight Area n Area (ft2) (ft2)
WINDOWS
01
02
03
04
05
06
07
Framing
Total Cavity R-value
Winter Design U-value
Construction Name
Surface Type
Construction Type
6 Concrete Wall
Exterior Walls
Concrete / ICF / Brick
Assembly Layers
0.741
• Mass Layer: 6 in. Concrete
0.069
• Inside Finish: Gypsum Board • Cavity / Frame: R-19 / 2x6 • Exterior Finish: Wood Siding/sheathing/decking
0.048
• • • •
Floor Surface: Carpeted Floor Deck: Wood Siding/sheathing/decking Cavity / Frame: R-19 / 2x6 Ceiling Below Finish: Gypsum Board
0.030
• • • •
Inside Finish: Gypsum Board Cavity / Frame: R-38 / 2x12 Roof Deck: Wood Siding/sheathing/decking Roofing: Light Roof (Asphalt Shingle)
0.196
• • • •
Floor Surface: Carpeted Floor Deck: Wood Siding/sheathing/decking Cavity / Frame: no insul. / 2x12 Ceiling Below Finish: Gypsum Board
02
03
04
05
06
07
08
09
10
Name
Type
Surface (Orientation-Azimuth)
Width (ft)
Height (ft)
Multipli er
Area (ft2)
U-factor
SHGC
Exterior Shading
W9
Window
North Wall (Back-0)
----
----
1
31.5
0.32
0.40
Insect Screen (default)
W9 2
Window
North Wall (Back-0)
----
----
1
31.5
0.32
0.40
Insect Screen (default)
Door/Window
Window
South Wall (Front-180)
----
----
1
56.0
0.32
0.40
Insect Screen (default)
W10
Window
North Wall 2 (Back-0)
----
----
1
81.0
0.32
0.40
Insect Screen (default)
W6
Window
East Wall 2 (Right-90)
----
----
1
12.0
0.32
0.40
Insect Screen (default)
W3
Window
South Wall 2 (Front-180)
----
----
1
20.6
0.32
0.40
Insect Screen (default)
W4
Window
South Wall 2 (Front-180)
----
----
1
18.0
0.32
0.40
Insect Screen (default)
W5
Window
South Wall 2 (Front-180)
----
----
1
42.0
0.32
0.40
Insect Screen (default)
W11
Window
North Wall 3 (Back-0)
----
----
1
98.0
0.32
0.40
Insect Screen (default)
W8
Window
East Wall 3 (Right-90)
----
----
1
8.3
0.32
0.40
Insect Screen (default)
W3 2
Window
South Wall 3 (Front-180)
----
----
1
20.6
0.32
0.40
Insect Screen (default)
W4 2
Window
South Wall 3 (Front-180)
----
----
1
18.0
0.32
0.40
Insect Screen (default)
01
02
03
04
W7
Window
South Wall 3 (Front-180)
----
----
1
28.8
0.32
0.40
Insect Screen (default)
Quality Insulation Installation (QII)
Quality Installation of Spray Foam Insulation
Building Envelope Air Leakage
CFM50
W12
Window
North Wall 4 (Back-0)
----
----
1
98.0
0.32
0.40
Insect Screen (default)
Not Required
Not Required
Not Required
---
W8 2
Window
East Wall 4 (Right-90)
----
----
1
8.3
0.32
0.40
Insect Screen (default)
W3 3
Window
South Wall 4 (Front-180)
----
----
1
20.6
0.32
0.40
Insect Screen (default)
W4 3
Window
South Wall 4 (Front-180)
----
----
1
18.0
0.32
0.40
Insect Screen (default)
01
02
03
04
05
06
W7 2
Window
South Wall 4 (Front-180)
----
----
1
28.8
0.32
0.40
Insect Screen (default)
Name
System Type
Distribution Type
Water Heater
Number of Heaters
Solar Fraction (%)
DHW Sys 1 - 1/1
DHW
Standard
DHW Heater 1
1
.0%
Registration Number:
Registration Date/Time:
218-N0289504A-000000000-0000
HERS Provider:
2018-10-26 09:28:55
Report Version - CF1R-01212016-433
CalCERTS inc.
Report Generated at: 2018-10-26 09:18:54
C-29116
OPAQUE SURFACE CONSTRUCTIONS
01
CA Building Energy Efficiency Standards - 2013 Residential Compliance
E D A RCH NS D GHAN IT E A N Y
T E CM A
06
R-19 Wall
Exterior Walls
R-19 Floor No Crawlspace
R-38 Roof No Attic
Wood Framed Wall
Interior Floors
Wood Framed Floor
Cathedral Ceilings
Interior Floor
2x6 @ 16 in. O.C.
2x6 @ 16 in. O.C.
Wood Framed Ceiling
Interior Floors
R 19
R 19
2x12 @ 16 in. O.C.
Wood Framed Floor
R 38
2x12 @ 16 in. O.C.
none
E
T
03
A
02
ST
01
LI RIC
OPAQUE SURFACES – Cathedral Ceilings
CF1R-PRF-01
A
Project Name: 1370 Pacific Ave
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
NI
CF1R-PRF-01
6-30-2019 RENEWAL DATE
OF
CA LI
R
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
FO
BUILDING ENVELOPE - HERS VERIFICATION
WATER HEATING SYSTEMS
Registration Number:
Registration Date/Time:
218-N0289504A-000000000-0000
CA Building Energy Efficiency Standards - 2013 Residential Compliance
HERS Provider:
2018-10-26 09:28:55
Report Version - CF1R-01212016-433
CalCERTS inc.
Report Generated at: 2018-10-26 09:18:54
REVISIONS NO. DATE
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
CF1R-PRF-01
Project Name: 1370 Pacific Ave
Calculation Date/Time: 09:18, Fri, Oct 26, 2018
Calculation Description: Title 24 Analysis
Input File Name: 1370 Pacific Av Res v6.ribdx
Page 7 of 9
WATER HEATERS
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
CF1R-PRF-01
Project Name: 1370 Pacific Ave
Calculation Date/Time: 09:18, Fri, Oct 26, 2018
Calculation Description: Title 24 Analysis
Input File Name: 1370 Pacific Av Res v6.ribdx
Page 8 of 9
IAQ (Indoor Air Quality) FANS
01
02
03
04
05
Name
Heater Element Type
Tank Type
Tank Volume (gal)
DHW Heater 1
Natural Gas
Small Instantaneous
0
06
07
08 Standby Loss (Fraction) 0
Energy Factor or Efficiency
Input Rating
Tank Exterior Insulation R-value
0.82
199000-Btu/hr
0
01
02
03
04
05
06 HERS Verification Required
Dwelling Unit
IAQ CFM
IAQ Watts/CFM
IAQ Fan Type
IAQ Recovery Effectiveness(%)
SFam IAQVentRpt
54.28
0.25
Default
0
ISSUE 04/11/19 PLAN REVIEW COMMENTS
OWNER
WATER HEATING - HERS VERIFICATION 01
02
03
04
05
06
07
Name
Pipe Insulation
Parallel Piping
Compact Distribution
Point-of Use
Recirculation Control
Central DHW Distribution
DHW Sys 1 - 1/1
---
---
---
---
---
---
Mr. Harold Tang & Family
SPACE CONDITIONING SYSTEMS 01
02
03
04
05
06
SC Sys Name
System Type
Heating Unit Name
Cooling Unit Name
Fan Name
Distribution Name
:Heat Pump System 1:::2:3
Heat Pump Heating and Cooling System
Heat Pump System 1
Heat Pump System 1
None
None
1370 Pacific Ave San Francisco, CA 94109 0155/021
HVAC - HEAT PUMPS 01
02
03
04
05
06
Heating Name
Type
Heat Pump System 1
DuctlessHeatPump
HSPF/COP 8.2
Cap 47 60000
07
Cooling Cap 17
SEER
50000
EER
14
11.7
08
09
10
Zonally
Multispeed
HERS
Controlled
Compressor
Verification
No
Heat Pump System 1-hers-cool
No
SCALE AS NOTED DRAWN BY RG CHECKED BY
HVAC COOLING - HERS VERIFICATION 01
02
03
04
05
06
Name
Verified Airflow
Airflow Target
Verified EER
Verified SEER
Verified Refrigerant Charge
Heat Pump System 1-hers-cool
Not Required
----
Not Required
Not Required
Not Required
RG PROJECT NO. 201209 DATE 4/29/19
Registration Number:
218-N0289504A-000000000-0000
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
2018-10-26 09:28:55
Report Version - CF1R-01212016-433
HERS Provider:
CalCERTS inc.
Report Generated at: 2018-10-26 09:18:54
Registration Number:
218-N0289504A-000000000-0000
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
2018-10-26 09:28:55
Report Version - CF1R-01212016-433
HERS Provider:
CalCERTS inc.
Report Generated at: 2018-10-26 09:18:54
DRAWING NO. 13 of 42
T24 RESIDENTIAL REPORT DRAWING NO.
A0.09
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
rg-architecture
CF1R-PRF-01
Project Name: 1370 Pacific Ave
Calculation Date/Time: 09:18, Fri, Oct 26, 2018
Calculation Description: Title 24 Analysis
Input File Name: 1370 Pacific Av Res v6.ribdx
Page 9 of 9
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. I certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name:
Documentation Author Signature:
Hayley Monahan
Hayley Monahan Signature Date:
2018-10-26 09:22:51
City/State/Zip:
LI RIC
1025 5th Street, Suite A Phone:
Novato, CA 94945
C-29116
415-897-6400 ST
RESPONSIBLE PERSON'S DECLARATION STATEMENT
A
I certify the following under penalty of perjury, under the laws of the State of California: 1. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance. 2. I certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 3. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
E
T
Responsible Designer Name:
T E CM A
E D A RCH NS D GHAN IT E A N Y
CEA/HERS Certification Identification (If applicable):
A
Address:
NI
Energysoft LLC
6-30-2019 RENEWAL DATE
OF
CA LI
R
Company:
FO
Responsible Designer Signature:
Riyad Ghannam Company:
Date Signed:
RG-Architecture
2018-10-26 09:28:55
Address:
License:
428 South Van Ness City/State/Zip:
na Phone:
San Francisco, CA 94103
415-646-6202
Digitally signed by CalCERTS. This digital signature is provided in order to secure the content of this registered document, and in no way implies Registration Provider responsibility for the accuracy of the information. Easy to Verify at CalCERTS.com
Registration Number:
218-N0289504A-000000000-0000
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
2018-10-26 09:28:55
Report Version - CF1R-01212016-433
HERS Provider:
CalCERTS inc.
Report Generated at: 2018-10-26 09:18:54
REVISIONS NO. DATE
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
ISSUE 04/11/19 PLAN REVIEW COMMENTS
OWNER Mr. Harold Tang & Family
1370 Pacific Ave San Francisco, CA 94109 0155/021
SCALE AS NOTED DRAWN BY RG CHECKED BY RG PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 14 of 42
T24 RESIDENTIAL REPORT DRAWING NO.
A0.10
rg-architecture 428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
STATE OF CALIFORNIA
ENVELOPE COMPONENT APPROACH CEC-NRCC-ENV-01-E (Revised 08/15)
10/26/2018
2
CA City and Zip Code:
San Francisco, 94109
✔ Component Unconditioned (file Affidavit)
7
Building Front Orientation (deg or cardinal):
180 deg
3
Climate Zone:
3
4
Total Conditioned Floor Area:
5
Building Type
C-29116
✔ New Construction Addition Alteration ✔ Nonresidential 376 9 Building Occupancy High-Rise Residential Hotel/Motel Guest Room ✔ Conditioned Spaces Unconditioned Spaces Schools (Public School) Relocatable Public School Bldg. 2 Skylight Area for Large Enclosed Space > 5000 ft (If checked include the NRCC-ENV-04-E with submittal)
8
Phase of Construction
A
Compliance Method:
E
6-30-2019 RENEWAL DATE
OF
CA LI
NI
6
LI RIC
1370 Pacific Ave
T
rg-architecture 428 South Van Ness Ave San Francisco, CA 94103 415-649-6202
Project Location:
A
Project Designer:
1
T E CM A
E D A RCH NS D GHAN IT E A N Y
ST
Commercial Unit 1370 Pacific Ave San Francisco, CA 94109
Date Prepared:
A. GENERAL INFORMATION
1 2 3 7 10
Cover Page Table of Contents Form ENV-01-E Envelope Component Approach Form ENV-02-E Fenestration Worksheet Form ENV-MM Envelope Mandatory Measures
NRCC-ENV-01-E (Page 1 of 4)
Commercial Unit 1370
Project Name:
PROJECT:
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE Envelope Component Approach
R
TABLE OF CONTENTS
BUILDING ENERGY ANALYSIS REPORT
FO
B. ENVELOPE DETAILS – FRAMED 1
Tag/ID
1
2
3
4
5
6
7
8
9
10
Assembly Type
Frame Material
Frame Depth
Frame Spacing
Appendix JA4 Reference
Cavity R-value
Continuous Insulation R-value
Proposed U-Factor
Required U-Factor from Tables, B, C, D
Wall
2x6 @ 16 in. O.C.
Wood
4.3.1-A5
19
0.0
0.074
0.110
11
Field Inspection Comments
R-19 Wall
Report Prepared by: C. ENVELOPE DETAILS – NON-FRAMED
Hayley Monahan EnergySoft, LLC 1025 5th Street, Suite A Novato, CA 94945 (415) 301-0163
1
2
Tag/ID
Job Number:
Assembly Type
3
4
Assembly Materials
Thickness (inches)
CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance
18189
5 Interior or Core Insulation R-value
6
7
8
9
10
Continuous Insulation R-value
Appendix JA4 Reference
Proposed U-Factor
Required U-Factor from Tables, B, C, D
Field Inspection Comments
August 2015
Date: 10/26/2018 REVISIONS NO. DATE
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC – www.energysoft.com. EnergyPro 6. by EnergySoft
User Number: 0000
ID: 18189
EnergyPro 6. by EnergySoft
Job Number: ID: 18189
ISSUE
08/12/14 ORIGINAL SITE PERMIT
User Number: 0000
11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
STATE OF CALIFORNIA
STATE OF CALIFORNIA
ENVELOPE COMPONENT APPROACH CEC-NRCC-ENV-01-E (Revised 08/15)
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE Envelope Component Approach Project Name:
NRCC-ENV-01-E (Page 2 of 4) Date Prepared:
Commerical Unit 1370
ENVELOPE COMPONENT APPROACH CEC-NRCC-ENV-01-E (Revised 08/15)
CERTIFICATE OF COMPLIANCE Envelope Component Approach Project Name:
10-26-2018
CALIFORNIA ENERGY COMMISSION
NRCC-ENV-01-E (Page 3 of 4) Date Prepared:
Commercial Unit 1370
ISSUE 04/11/19 PLAN REVIEW COMMENTS
10/26/2018
OWNER
D. ENVEL0PE DETAILS – MASS 1
2
3
Tag/ID
Mass Type
Density 3) (lb/ft
4 Mass Thickness (inches)
5 Furring Strip Thickness (inches)
6 Interior Insulation R-value
7 Exterior Insulation R-value
8 Appendix JA4 Reference
9 Proposed Insulation U-factor
F. AIR BARRIER
10
11
Required U-Factor from Tables, B, C, D
Field Inspection Comments
Mr. Harold Tang & Family
1
2
3
4
5
Name
Air Barrier Material Type
Air Barrier Assembly Type
Whole Building Air Leakage Testing
Comments
ENV-MM
E. ROOFING PRODUCTS (COOL ROOF) 1 Mass Roof 25 lb ft2 or greater
2
3
Roof Pitch
CRRC Product ID Number
4
5
Product Type
Aged Solar Reflectance
1
1
1
6 Proposed Thermal Emittance
7
8
2
SRI (Optional)
9 10 Minimum Required Aged Solar Thermal SRI Reflectance Emittance (optional)
1370 Pacific Ave
G. FENESTRATION PROPOSED AREAS AND EFFICIENCIES
11
1
2
3
Fenestration Type
Surface Area
Comments Tag/ID
1 2
Door Fixed Window
28 34
3
Fixed Window
28
4 Orientation N, S, W, E or Roof
S S W
2 2 2
5
6
# of Panes
Max U-Factor
7
8
9
10
11
12
Overhang
Max (R) SHGC
Min VT
Label
Conditions Status
Comments
0.45
No
0.23
0.50
NFRC
New
0.36 0.36
No No
0.25 0.25
0.50 0.50
NFRC NFRC
New New
SCALE
An aged solar reflectance less than 0.63 is allowed provided the maximum roof / ceiling U-factor in TABLE 140.3 is not exceeded
AS NOTED
High-rise residential buildings and Hotels and Motels with low-sloped roofs in Climate Zones 1 through 8, 12 and 16 are exempted from aged Solar Reflectance and emittance requirements. High-rise residential buildings and Hotels and Motels with steep-sloped roofs in Climate Zones 1 and 16 are exempt from aged Solar Reflectance and emittance requirements. The roof area covered by building integrated photovoltaic panels and building integrated solar thermal panels are exempt from aged Solar Reflectance and emittance requirements To apply Liquid Field Applied Coatings, the coating must be applied across the entire roof surface and meet the dry mil thickness or coverage recommended by the coatings manufacturer and meet minimum performance requirements listed in §110.8(i)4. Select the applicable coating: Aluminum-Pigmented Asphalt Roof Coating
Cement-Based Roof Coating
DRAWN BY RG CHECKED BY RG PROJECT NO.
Other ______________________
NOTES: 1. Check the box if the aged Solar reflectance was not available in the Cool Roof Rating Council’s Rated Product Directory, Then use the equation in Section 110.8(i)2 where the Initial Reflectance value from the same directory and use the equation (0.2+B(ρinitial – 0.2) to obtain a calculated aged value. Where ρ is the Initial Solar Reflectance and B is either set to 0.65 for Field-Applied Coatings or it is set to 0.70 for all other roofing products other than Field-Applied Coating. 2. Calculate the SRI Value by using the SRI-Worksheet at (TBD) and enter the resulting value in the SRI Column above and attach a copy for the SRI-Worksheet NRCC-ENV-03-E to the to this form.
August 2015
201209
H. ENVELOPE MANDATORY MEASURES
DATE
Indicate location on building plans of Mandatory Envelope Measures Note Block: __________________________
4/29/19
INSTRUCTIONS TO APPLICANT ENVELOPE COMPLIANCE & WORKSHEETS (check box if worksheet are included)
DRAWING NO. 15 of 42
For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, please refer to the Nonresidential Compliance Manual.
✔
CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance
San Francisco, CA 94109 0155/021
NRCC-ENV-01-E NRCC-ENV-04-E
T24 COMMERCIAL REPORT
Certificate of Compliance. Required on plans for all submittals. Use when minimum skylight requirements for large enclosed spaces are required in climate zones 2 through 15. Optional on plans.
CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance
August 2015
DRAWING NO.
A0.11
STATE OF CALIFORNIA
FENESTRATION WORKSHEET
CERTIFICATE OF COMPLIANCE Envelope Component Approach Date Prepared:
Commercial Unit 1370
10/26/2018
1025 5th Street, Suite A
CEA/ HERS Certification Identification (if applicable):
Novato, CA 94945
Phone:
10/26/2018
1
3
4
5
U-Factor
(415) 301-0163 Window Type (e.g., Window-1)
Tag/ID
1 2 3
Surface Area
Window Window Window
6 7 Fenestration SHGC
8
0.450
0.450 0.230 0.230 0.500 0.170
34
0.360
0.360 0.250 0.250 0.500 0.420
28
0.360
0.360 0.250 0.250 0.500 0.420
12
13 Overhang
H
V
H/V
14
2
West Display Perimeter Area
2
Maximum Standard West Area
2
Proposed West Window Area
rg-architecture
Date Signed:
B. West Display Linear Perimeter
0
FT × 6 ft =
0
ft
428 South Van Ness Ave
License:
C. Enter Larger of A or B
50
ft
D. Enter Proposed West Window Area
28
ft
ft
ft × 0.10 = 2
ft
0
= Proposed Skylight Area Divided by Actual Gross Roof Area
0.0
C-29116
%
1. If the SKYLIGHT SSR % is less than or equal to 5% then choose the appropriate column in Table 140.3-B and C and row in Table 140.3-D. 2. If the SKYLIGHT SSR % is greater than 5% then the Envelope Component Approach may not be used.
For Specific Climate Zone, use Table 140.3-B - Prescriptive Envelope Criteria.
2
Riyad Ghannam
ft
1, 2
E D A RCH NS D GHAN IT E A N Y
2
2
E
6-30-2019 RENEWAL DATE
OF
CA LI
FO
Option 1
40% of Gross West Facing Exterior Wall Area; or
50
2
E. RELOCATABLE PUBLIC SCHOOL BUILDINGS - See Section140.3(a)8 in the Energy Standards
2
ft × 0.40 =
D. Skylight SSR %
STANDARD ALLOWED SKYLIGHT AREA 2 ft 0
ft × 0.05 =
0
C. Proposed Skylight Area (from plans)
Max (R)SHGC Allowed
(R)SHGC Proposed
A IF Atrium/Skylight Height is ≤ 55 ft; or B. IF Atrium/Skylight Height is > 55 ft
Calculated
B. WEST WINDOW AREA CALCULATION - See §140.3(a)5A in the Energy Standards
124
San Francisco, CA 94103
11
Dimensions
28
A. Gross West Exterior Wall Area
415-649-6202
10
VT
Responsible Designer Signature:
Phone:
9
ACTUAL GROSS ROOF AREA
T
City/State/Zip:
2
Allowed
Signature Date:
10/26/2018
A
Address:
Date Prepared:
Commercial Unit 1370
D. SKYLIGHT AREA CALCULATION See §143(a)6A in the Energy Standards
Proposed
EnergySoft, LLC
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
NRCC-ENV-02-E (Page 2 of 3)
ST
Company :
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE Fenestration Worksheet
NOTE: Newly installed fenestration shall have a certified NFRC Label Certificate or use the CEC default tables found in Table 116-A and Table 116B. 2 Site-built fenestration less than 1,000 ft , or more than or equal to1,000 ft² see Reference Nonresidential Appendix NA6.
RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer). 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Designer Name:
CEC-NRCC-ENV-02-E (Revised 07/16)
T E CM A
City/State/Zip:
Hayley Monahan
FENESTRATION WORKSHEET
Project Name:
10/26/2018
A. WINDOWS DETAILS Worksheet §140.3(a)5B and C Documentation Author Signature:
Allowed
Address:
Date Prepared:
Commercial Unit 1370
Proposed
Company:
NRCC-ENV-02-E (Page 1 of 3)
Allowed
Documentation Author Name:
CERTIFICATE OF COMPLIANCE Fenestration Worksheet Project Name:
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. I certify that this Certificate of Compliance documentation is accurate and complete.
CALIFORNIA ENERGY COMMISSION
Proposed
Project Name:
NRCC-ENV-01-E (Page 4 of 4)
CEC-NRCC-ENV-02-E (Revised 07/16)
A
CALIFORNIA ENERGY COMMISSION
NI
CEC-NRCC-ENV-01-E (Revised 08/15)
R
ENVELOPE COMPONENT APPROACH
rg-architecture
STATE OF CALIFORNIA
LI RIC
STATE OF CALIFORNIA
Specific Climate Zone Metal Identification Label – Place two labels on each relocatable school building and indicate on the building plans. Indicate location from the building plans:
Option 2 For Any (All) Climate Zone, use Table 140.3-D - Prescriptive Envelope Criteria.
Any (All) Climate Zone Metal Identification Label - Place two labels on each relocatable school building and indicate on the building plans. Indicate location from the building plans:
Note: If the PROPOSED WEST WINDOW AREA is greater than the MAXIMUM STANDARD WEST AREA then the envelope component approach may not be used.
C. WINDOW AREA CALCULATION - See §140.3(a)5A in the Energy Standards 2
E. Gross Exterior Wall Area
641
ft × 0.40 =
256
ft
F. Linear Display Perimeter
0
FT × 6 ft =
0
ft
2
40% of Gross Exterior Wall Area or
2
Display Perimeter Area
2
Maximum Standard Area
2
Proposed Window Area
G. Enter The Larger of E or F
256
ft
H. Enter Proposed Window Area
90
ft
Note: If the PROPOSED WINDOW AREA is greater than the MAXIMUM STANDARD AREA then the envelope component approach may not be used.
CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance
August 2015
CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance
July 2016
CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance
July 2016
REVISIONS NO. DATE
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
STATE OF CALIFORNIA
FENESTRATION WORKSHEET CEC-NRCC-ENV-02-E (Revised 07/16)
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE Fenestration Worksheet Project Name:
NRCC-ENV-02-E (Page 3 of 3) Date Prepared:
Commercial Unit 1370
10/26/2018
ENVELOPE MANDATORY MEASURES: NONRESIDENTIAL Project Name
ENV-MM Date
Commercial Unit
10/26/2018
DESCRIPTION Building Envelope Measures:
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. I certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name:
Hayley Monahan
Documentation Author Signature:
Company:
EnergySoft, LLC
Signature Date:
Address: City/State/Zip:
1025 5th Street, Suite A Novato, CA 94945
10/26/2018
CEA/ HERS Certification Identification (if applicable): Phone:
I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer). 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy. Company : Address: City/State/Zip:
Installed insulating material shall have been certified by the manufacturer to comply with the California Quality Standards for insulating material, Title 20 Chapter 4, Article 3.
§110.8(c):
All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2.
§110.8(f):
The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an installed R-value of no less than R-13 between framing members.
§110.7(a):
(415) 301-0163
RESPONSIBLE PERSON'S DECLARATION STATEMENT
Responsible Designer Name:
§110.8(a):
§110.6(a):
All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed, weatherstripped or otherwise sealed. Manufactured fenestration products and exterior doors shall have air infiltration rates not exceeding 0.3 cfm/ft.² of window area, 0.3 cfm/ft.² of door area for residential doors, 0.3 cfm/ft.² of door area for nonresidential single doors (swinging and sliding), and 1.0 cfm/ft.² for nonresidential double doors (swinging).
§110.6(a):
Fenestration U-factor shall be rated in accordance with NFRC 100, or the applicable default U-factor.
§110.6(a) :
Fenestration SHGC shall be rated in accordance with NFRC 200, or NFRC 100 for site-built fenestration, or the applicable default SHGC.
§110.6(b):
Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be weatherstripped (except for unframed glass doors and fire doors).
428 South Van Ness Ave San Francisco, CA 94103
04/11/19 PLAN REVIEW COMMENTS
OWNER Mr. Harold Tang & Family
1370 Pacific Ave San Francisco, CA 94109 0155/021
Responsible Designer Signature:
rg-architecture
ISSUE
Date Signed: License: Phone:
415-649-6202
SCALE AS NOTED DRAWN BY RG CHECKED BY RG PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 16 of 42
T24 COMMERCIAL REPORT EnergyPro 6. by EnergySoft
CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance
July 2016
User Number: 0000
ID: 18189
Page 10 of 10
DRAWING NO.
A0.12
NOTE 2
18"
60
ENLARGED ACCESSIBLE COMMERCIAL BATHROOM SCALE: 1/2" = 1'-0"
20
SINGLE ACCOMIDATION TOILET SCALE: 1/4" = 1'-0"
8" CLEAR KNEE
CLR. MANEUVERING SPACE PLAN VIEW
FRONT ELEVATION
ACCESSIBLE CLEARANCES AT LAVATORY SCALE: 1/2" = 1'-0"
12
40" MIN.
17" - 18"
MAX.
MIN. MAX. 3'-0" TO 4'-0" SEE PLAN
6" MAX.
A
2 1 ISSUE
1/2" MAX.
04/11/19 PLAN REVIEW COMMENTS
1/4" MAX.
33" A.F.F.
GRAB BAR TO CL OF GRAB BAR
12" MIN.
TO CL OF GRAB BAR
33" A.F.F.
19" MIN.
SIDE ELEVATION
OWNER Mr. Harold Tang & Family
FRONT ELEVATION
12" MAX.
TYP. ACCESSIBLE DETAILS SCALE: 1/2" = 1'-0"
EXIT IDENTIFICATION, DIRECTIONAL & DISABLED ACCESS ENTRY SIGNAGE
2
1370 Pacific Ave 855 Folsom Street #330 San Francisco, CA 94107
1. ROOM NAME TO BE RAISED 1/32" SANS SERIF, COLOR WHITE. BRAILLE TO BE GRADE 2 BRAILLE, COLOR WHITE. 2. SIGNAGE TO BE 1/4" THICK BLUE ACRYLIC PLASTIC TO MATCH FED. STND. 595B, COLOR #15090. SYMBOL TO BE SILK-SCREEN EPOXY OR VINYL, COLOR WHITE.
32" MIN. CLR.
9"
AS NOTED RG CHECKED BY
BLUE ACRYLIC PLASTIC W/ POLISHED EDGES
RG PROJECT NO. 201209
WHITE SILKSCREEN GRAPHIC SYMBOL
DATE 4/29/19
3/4"
5'-1/16"
61/8" MN. SQUARE
24" MIN.
SCALE DRAWN BY
3. ATTACH SIGNAGE TO WALL W/ TWO-SIDED TAPE & SILICONE.
41/2"
60" MIN. PUSH SIDE
FINISH FLOOR
ELEVATION
DOOR CLEARANCES SCALE: 1/4" = 1'-0"
17
TYP. ACCESSIBLE SIGN MOUNTING HEIGHT SCALE: 3/4" = 1'-0"
3"
1"
NOTE: PLACE DISABLED ACCESS ENTRY SIGNAGE 9" FROM FRAME EDGE LATCH SIDE OF ENTRY DOOR.
TYP. TYP.
DRAWING NO. 17 of 42
1"
PULL SIDE
DOOR THRESHOLD SCALE: 3" = 1'-0"
10 NOTE:
44" MIN.
LEVER OPERATED OR PUSH-TYPE MECHANISM OR U-SHAPE HANDLE OPENING HARDWARE DOOR THRESHOLD, 1/2" MAX. (IF PROVIDED)
24" MIN.
24" MIN.
48" IF DOOR HAS BOTH A CLOSER AND A LATCH
DOOR FRAME
42" MIN.
17"-18"
24" MIN.
LATCH APPROACH
LATCH SIDE
HINGE SIDE
DOOR 30" TO 44" DOOR OPENING HARDWARE
80" MIN. EXT. DOOR HEIGHT
PLAN
12" MAX.
17" TO 19"
54" MIN.
*EXIT DOORS SHALL BE OPERABLE FROM THE INSIDE WITHOUT THE USE OF A KEY OF ANY SPECIAL KNOWLEDGE OR EFFORT DOOR OPENING FORCE 1.FIRE DOOR: AS REQ'D BY APPLICABLE ADMIN. AUTHORITY 2. INTERIOR DOORS 5LB. MAX. DOOR THRESHOLD, 1/2" MAX. (IF PROVIDED) DOOR CLOSER (OPR. SIDE OF WALL) (IF PROVIDED)
54" MIN.
GRAB BAR
PUSH SIDE
90 DEG. MIN. OPEN SWING
36" MIN. CL
TO T.O. TOILET SEAT
PULL SIDE
32" MIN. CLR.
48" MIN. IF DOOR HAS A CLOSER
CL
TOILET PAPER ROLL HOLDER
44" MIN.
48" MIN.
PROVIDE THIS ADDITIONAL SPACE IF DOOR IS EQUIPPED WITH BOTH A LATCH AND A CLOSER
DOOR CLOSER REQMTS. 3"
ISSUE
11/01/18 ADDENDUM 2
60" MIN.
PUSH PLATE TYP.
HINGE APPROACH
7 1/2"
12"
32" MIN. CLR
3
REVISIONS NO. DATE
08/12/14 ORIGINAL SITE PERMIT
3'
60" MIN.
R 2 1/4"
PUSH SIDE
TYP. GRAB BAR SECTION SCALE: 3" = 1'-0"
R1 04/11/19 PLAN REVIEW COMMENTS
R 2 1/4"
32" MIN. CLR.
19
COVER PLATE MANUFACTURER SUPPLIED WALL MOUNTING BRACKETS FOR METAL WALL FRAMING CERAMIC TILE WHERE OCCURS
36" MIN.
CLEAR AREA AT INTERIOR DOORS
PULL SIDE
2'-9" TO FINISH FLR
1'
32" MAX. AFF
19"
MIN.
C L
MED. CABINET
40"
44" MAX.
C L
1 1/4" - 1 1/2" Ø NOMINAL FUTURE GRAB BAR, N.I.C.
38" MIN. AFF
12" MAX.
TYP. ACCESSIBLE / ADAPTABLE FIXTURE MOUNTING HEIGHT REQUIREMENTS SCALE: 1/4" = 1'-0"
18" MIN.
8
1 1/2" MIN.
17" MIN. 19" MAX.
26" MIN.
38" MIN. 32" MAX.
40"
5' MAX.
FROM T.O. FIN. FLR. TO T.O. F.E.C.
CONTROLS AND MAX. HEIGHT OPERATING MECHANISMS
40"
TO BOTTOM OF REFLECTIVE SURFACE
42" MIN.
GRAB-BAR BLOCKING T.P.H.
CLEAR AREA AT EXTERIOR DOORS
FO
WALL FRAMING, PER PLANS 6" NOMINAL MIN. SOLID BLOCKING FOR WOOD WALL FRAMING
3'-0" TO 4'-0" SEE PLAN
24" MIN.
CA LI
TYP. GRAB BAR SECTION
C L
MIRROR
RENEWAL DATE
OF
CLR. TOE
SIDE ELEVATION
3 A0.13
TOWEL BAR; SEE UNIT PLANS FOR LENGTH
6-30-2019
6"
GRAB BAR BLOCKING; SEE DETAIL
FRONT APPROACH
48 48
30"
THIS DIAGRAM ILLUSTRATES THE SPECIFIC REQUIREMENT OF THE ACCESSIBILITY REGULATIONS AND IS INTENDED ONLY AS AN AID FOR BUILDING DESIGN AND CONSTRUCTION.
NI
D-5 12"
48
18" 32" MIN. MIN. CLR.
30
E
T
30" X 48" CLEAR FLOOR AREA
C-29116
A
60
E D A RCH NS D GHAN IT E A N Y
R
48
56
60 DIA " MIN .C . LR .
ST
6'-4 1/8"
R 2'-6"
18" MIN.
T E CM A
42"
C L
17" MIN.
LI RIC
C L
2. PROVIDE INSULATION PADS ON ALL WATER SUPPLY & DRAIN PIPES FOR ACCESSIBLE LAVS.
NOTE 1
FLUSH ACTIVATOR ON WIDE SIDE
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
9" CLR TOE
54" MIN.
7'-3"
12" 24" MIN. MIN.
34" MAX. 29" MIN. CLR. 27" CLR KNEE
18"
1. PROVIDE LEVER TYPE FAUCET CONTROLS FOR ACCESSIBLE LAVS.
18" CLR.
48" MIN. CLR.
24"
42" MIN.
12"
12"
6"
12" MAX.
BLOCKING FOR GRAB BAR
17"-18"
rg-architecture
NOTES:
CENTERLINE OF FIXTURE
60" MIN.
24" MIN.
SEE 2013 CBC 1127A.2.2.3
DN
ACCESSIBLE ENTRY
ACCESSIBILITY DETAILS
RAISED CHARACTER ROOM NAME, 1" HIGH ALL CAPS LOCATION FOR BRAILLE CHARACTER
DRAWING NO.
5
TYP. ACCESSIBLE SIGNAGE SCALE: 3" = 1'-0"
1
A0.13
R1
rg-architecture
04/02/2019
Permit Application # Property Address:
2014/0812/3679-S2 1370 PACIFIC AVENUE
Block and Lot: 0155 / 021 Occupancy Group: R3/B
Type of Construction:
V-A
No. of Stories: 4+Base
_______________
__________________
_____________
Division Manager:
_______________
__________________
_____________
E D A RCH NS D GHAN IT E A N Y
C-29116
for Director of Bldg. Inspection
_______________
__________________
_____________
for Fire Marshal:
_______________
__________________
_____________
E
T
If a permit application has been filed, no additional fees are required for this review.
Plan Reviewer:
A
Case-by-Case Basis of Request - Describe the practical difficulties presented in meeting the specific conditions of the code and how the proposed modification or alternate meets the intent of the code. A separate form should be filled for each requested modification or alternate. Attach copies of any Administrative Bulletin, Code Ruling, reference, test reports, expert opinions, etc., which support this request. The Department may require that an approved consultant be hired by the applicant to perform tests or analysis and to submit an evaluation report to the Department for consideration.
Disapprove
ST
If no permit application has been filed, a Preapplication Review Fee is required for review of a request for local equivalency or modification, per SFBC Table 1A-B, Item 5. Additional fees may be required by Fire Department and other City review agencies.
Approve with conditions
T E CM A
[Note: This form shall be recorded as part of the permanent construction records of the property]
Approve
A
DATE SUBMITTED
RECOMMENDATIONS: [signed off/dated by:]
CONDITIONS OF APPROVAL or OTHER COMMENTS
NI
REQUEST FOR APPROVAL OF LOCAL EQUIVALENCY FOR MODIFICATION OR ALTERNATE MATERIALS, DESIGN OR METHODS OF CONSTRUCTION
Proposed Modification or Alternate PER INFORMATION SHEETS FS-01 AND G-21, ROOF DECK PLATFORMS SHALL BE CONSTRUCTED OF NON - COMBUSTABLE MATERIALS. PEDESTAL SYSTEM USED SHALL COMPLY WITH INFO SHEET G-21. SHALL COMPLY WITH SFBC SEC 1509.10 FOR NONCOMBUSTIBILITY.
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
LI RIC
DEPARTMENT OF BUILDING INSPECTION City & County of San Francisco 1660 Mission Street, San Francisco, California 94103-2414
PLAN REVIEWER COMMENTS:
6-30-2019 RENEWAL DATE
OF
CA LI
R
ATTACHMENT A
FO
PEDESTAL SYSTEM SHALL COMPLY WITH INFORMATION SHEET G-21 12/12/18 SF DBI TECHNICAL SERVICES
Describe Use of Building MIXED-USE OCCUPANCY 4 STORY BUILDING. THREE LEVELS OF SINGLE FAMILY RESIDENTIAL R3 OCCUPANCY OVER COMMERCIAL B OCCUPANCY OVER BASEMENT Under the authority of the 2016 San Francisco Building Code, Sections 104A.2.7 and 104A.2.8; the 2016 San Francisco Mechanical Code, Section 302.2; the 2016 San Francisco Electrical Code, Section 89.117; and the 2016 San Francisco Plumbing Code, Section 301.3; the undersigned requests modifications of the provisions of these codes and/or approval of alternate materials, designs or methods of construction. Two copies of supporting documents, including plans showing the proposed modifications or alternate materials, design or methods of construction, are attached. ARCHITECT/ENGINEER E D A RCH NS D GHAN IT E A N Y [PROFESSIONAL
RIYAD GHANNAM
STAMP HERE] C-29116
A
T
E
Page 1 of 3
Page 2 of 3
6-30-2019 RENEWAL DATE
OF
CA LI
NI
415.649.6202
ST
Telephone:
A
Signature:
R
Print Name:
PROJECT SPONSOR
LI RIC
Requested by:
T E CM A
Regular Code Requirement (specify Code and Sections) SFBC SEC 1509.10 - Roof Decks < 500 square feet shall be constructed of Fire Retardant treated lumber rated for exterior exposure of all heart redwood or equivalent. ≥ 500 Square Feet shall be constructed of non-combustible materials.
FO
Page 3 of 3
REVISIONS NO. DATE
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
ISSUE 04/11/19 PLAN REVIEW COMMENTS
OWNER Mr. Harold Tang & Family
1370 Pacific Ave San Francisco, CA 94109 0155/021
SCALE AS NOTED DRAWN BY RG CHECKED BY RG PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 18 of 42
AB-005
DRAWING NO.
A0.14
R1
rg-architecture 428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
LI RIC
T E CM A
E D A RCH NS D GHAN IT E A N Y
T
REVISIONS NO. DATE
NI
A
E
6-30-2019 RENEWAL DATE
OF
CA LI
R
ST
A
C-29116
FO
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
ISSUE 04/11/19 PLAN REVIEW COMMENTS
OWNER Mr. Harold Tang & Family
1370 Pacific Ave San Francisco, CA 94109 0155/021
SCALE AS NOTED DRAWN BY RG CHECKED BY RG PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 19 of 42
IS MEP-03a
DRAWING NO.
A0.15
R1
rg-architecture 428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
LI RIC
T E CM A
E D A RCH NS D GHAN IT E A N Y
T
REVISIONS NO. DATE
NI
A
E
6-30-2019 RENEWAL DATE
OF
CA LI
R
ST
A
C-29116
FO
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
ISSUE 04/11/19 PLAN REVIEW COMMENTS
OWNER Mr. Harold Tang & Family
1370 Pacific Ave San Francisco, CA 94109 0155/021
SCALE AS NOTED DRAWN BY RG CHECKED BY RG PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 20 of 42
IS MEP-03b
DRAWING NO.
A0.16
R1
rg-architecture 428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
LI RIC
T E CM A
E D A RCH NS D GHAN IT E A N Y
T
REVISIONS NO. DATE
NI
A
E
6-30-2019 RENEWAL DATE
OF
CA LI
R
ST
A
C-29116
FO
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
ISSUE 04/11/19 PLAN REVIEW COMMENTS
OWNER Mr. Harold Tang & Family
1370 Pacific Ave San Francisco, CA 94109 0155/021
SCALE AS NOTED DRAWN BY RG CHECKED BY RG PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 21 of 42
IS MEP-04a
DRAWING NO.
A0.17
R1
rg-architecture 428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
LI RIC
T E CM A
E D A RCH NS D GHAN IT E A N Y
T
REVISIONS NO. DATE
NI
A
E
6-30-2019 RENEWAL DATE
OF
CA LI
R
ST
A
C-29116
FO
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
ISSUE 04/11/19 PLAN REVIEW COMMENTS
OWNER Mr. Harold Tang & Family
1370 Pacific Ave San Francisco, CA 94109 0155/021
SCALE AS NOTED DRAWN BY RG CHECKED BY RG PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 22 of 42
IS MEP-04b
DRAWING NO.
A0.18
R1
rg-architecture
GENERAL NOTES 68 LYNCH STREET
62 LYNCH STREET
68 LYNCH STREET
62 LYNCH STREET
3 STORY RESIDENTIAL APPROX. 30'-8" HT. ALONG LYNCH STREET
2 STORY RESIDENTIAL APPROX. 24'-0" HT. ALONG LYNCH STREET
3 STORY RESIDENTIAL APPROX. 30'-8" HT. ALONG LYNCH STREET
2 STORY RESIDENTIAL APPROX. 24'-0" HT. ALONG LYNCH STREET
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
LI RIC
T E CM A
E D A RCH NS D GHAN IT E A N Y
C-29116
LYNCH STREET (17.50' WIDE)
(N) CURB CUT
218.39
221.32 219.49
T
(N) CURB CUT
218.39
221.32
E
219.49 221.32
NI
A
CURB CUT (TO BE REPLACED)
6-30-2019 RENEWAL DATE
OF
CA LI
R
ST
A
LYNCH STREET (17.50' WIDE) FO
221.32
3'-0" RESIDENTIAL REAR YARD SETBACK PER PLANNING COMMISION REQUEST 08/13/15
PROPOSED BUILDING 1364 PACIFIC AVE UNDER SEPERATE PERMIT
STAIR PENTHOUSE
STAIR PENTHOUSE
SHEET NOTES GRADE PLANE CALCULATIONS
ADJACENT BLDG: 1372-74 PACIFIC AVE 2 STORY MIXED USE, APPROX. 27'-0" HT. ALONG PACIFIC AVE. +/-
ADJACENT BLDG: 1372-74 PACIFIC AVE
ADJACENT BLDG: 1354-58 PACIFIC AVE
ROOF DECK
2 STORY MIXED USE, APPROX. 27'-0" HT. ALONG PACIFIC AVE.
2 STORY MIXED USE, APPROX. 27'-0" HT. ALONG PACIFIC AVE. +/-
22'-6"
+/-
28'-0"
22'-6"
224.01' + 225.92' + 219.49' + 218.39' =887.17' ÷ 4 =221.79' AVERAGE GRADE PLANE = 221.79'
60'
60'
60'
60'
1370 PACIFIC AVENUE:
EXISTING 1 STORY BUILDING TO BE DEMOLISHED (UNDER SEPERATE PERMIT)
EXISTING 1 STORY BUILDING TO BE DEMOLISHED (UNDER SEPERATE PERMIT)
OCCUPANCY B +/- 510 SQFT
OCCUPANCY B +/- 1080SQFT
ADJACENT BLDG: 1354-58 PACIFIC AVE 2 STORY MIXED USE, APPROX. 27'-0" HT. ALONG PACIFIC AVE. +/-
REVISIONS NO. DATE
28'-0"
ISSUE
08/12/14 ORIGINAL SITE PERMIT SUBJECT PROPERTY 224.01 17'-6"
11/01/18 ADDENDUM 2 226.92 225.28
224.01
226.92 20'
225.28 226.92 17'-6"
R1 04/11/19 PLAN REVIEW COMMENTS
226.92 20'
N
N
ISSUE 04/11/19 PLAN REVIEW COMMENTS
OWNER Mr. Harold Tang & Family PACIFIC AVE (50.60' WIDE)
PACIFIC AVE (50.60' WIDE)
1370 Pacific Ave KEY
San Francisco, CA 94109 0155/021
SCALE AS NOTED DRAWN BY 1363, 65 & 67 PACIFIC AVE
1355 PACIFIC AVE
1363, 65 & 67 PACIFIC AVE
1355 PACIFIC AVE
3 STORY RESIDENTIAL, APPROX. 36'-0" HT. ALONG PACIFIC AVE.
5 STORY RESIDENTIAL, APPROX. 53'-0" HT. ALONG PACIFIC AVE. SCOPE OF WORK
3 STORY RESIDENTIAL, APPROX. 36'-0" HT. ALONG PACIFIC AVE.
5 STORY RESIDENTIAL, APPROX. 53'-0" HT. ALONG PACIFIC AVE. SCOPE OF WORK
RG CHECKED BY RG PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 23 of 42
0
4'
8'
16'
SITE PLAN SCALE: 1/8" = 1'-0"
02
0
4'
8'
16'
SITE PLAN (E) SCALE: 1/8" = 1'-0"
01
SITE PLAN DRAWING NO.
A1.00
rg-architecture
GENERAL NOTES
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
LYNCH STREET (BELOW)
LYNCH STREET
CURB CUT (TO BE REPLACED)
LI RIC
T E CM A
SIDEWALK (BELOW)
A
T
E
NI
ST
3'-6" SIDEWALK
A
C-29116
6-30-2019 RENEWAL DATE
OF
CA LI
R
SIDEWALK (BELOW)
E D A RCH NS D GHAN IT E A N Y
FO
SHEET NOTES
REVISIONS NO. DATE
STORAGE 4
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
C.H. 6'-3" STORAGE
ISSUE 04/11/19 PLAN REVIEW COMMENTS RETAIL
C.H. 6'-3" OWNER Mr. Harold Tang & Family STORAGE 1
STORAGE 2
1370 Pacific Ave KEY
San Francisco, CA 94109 0155/021
SCALE AS NOTED DRAWN BY RG CHECKED BY RG PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 24 of 42
11'-6" +/- SIDEWALK
N
0
2'
4'
8'
STORY 1 SCALE: 1/4" = 1'-0"
02
0
2'
4'
8'
BASEMENT SCALE: 1/4" = 1'-0"
01
EXISTING BASEMENT-2ND PLANS DRAWING NO.
A2.00
rg-architecture
GENERAL NOTES
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
2
02 A6.01
1
2
02 A6.01
(N) CURB CUT
SIDEWALK (BELOW) 1'-3"
3'-7"
8'
C-29116
4' ST
3'-6" SIDEWALK
A
B
B
B
3'-1 1/2"
3'-1 1/2"
03 A7.00
WI05 A9.01 WI07 A9.01
DN
W04 A9.00
8'-8 3/8"
W04
3'
02 A7.00
W05
5'-8 3/8" 02 A6.00
PL
W06
1'-4 5/8"
3'
A
2 R. @ 5 1/4" UP 1 T. @ 1'-3"
W02 A9.00
A
W02 A9.00
D-11 D-11
55'-4"
WI02 A9.01 OWNER
34"-38" TALL GUARDRAIL
3'-1 1/2"
W01 A9.00
Mr. Harold Tang & Family
W04 A9.00
1370 Pacific Ave
20 MIN W/ SELF CLOSER
W02 D-1
1 HOUR RATING
D-6 STO A: 8 sq ft
W03 A9.00
A
W04 A9.00
2 HOUR RATING
A
W01
SCALE AS NOTED DRAWN BY
A
3 HOUR RATING
17'-4"
ACCESSIBLE ROUTE
RG CHECKED BY RG PROJECT NO.
1'
PROJECTION SEC 136
San Francisco, CA 94109 0155/021
KEY
MUD ROOM A: 14 sq ft
R1
W03 A9.00
R1 04/11/19 PLAN REVIEW COMMENTS
PL
W02 A9.00
A
6'-5"
4'-2 1/2"
W03 A9.00 3'-8 1/8"
W03
W03 A9.00
W03 A9.00
11/01/18 ADDENDUM 2
04/11/19 PLAN REVIEW COMMENTS
3'-3 1/2" D-2
E.C.R. A: 13 sq ft
D-13
UP
UP
3'-1 1/2" W01 A9.00
08/12/14 ORIGINAL SITE PERMIT
PARKING PER TABLE 151
ELV A: 17 sq ft
201209
2
1
02 A7.00
02 A6.00
2
1
11'-6" +/- SIDEWALK
02 A7.00
02 A6.00
DATE 4/29/19
2
DRAWING NO. 25 of 42
N
SIDEWALK (BELOW)
BASEMENT-2ND PLANS DRAWING NO.
0
2'
4'
8'
STORY 2 SCALE: 1/4" = 1'-0"
ISSUE
ISSUE
33'-8 3/8"
ACCESSIBLE ROUTE
ENTRY A: 94 sq ft
17 R. @ 7 1/2" 16 T. @ 10"
18'-11 1/8"
34"-38" TALL GUARDRAIL
W02 A9.00
REVISIONS NO. DATE
03 A6.01
11'-7 1/4"
DN 4 A9.05
DINING A: 288 sq ft
7'-8 3/8"
03 A7.00
FIRST FL. GROSS INT. (COMM.) A: 324 sq ft
FIRST FL. GROSS INT. (RES.) A: 102 sq ft
6"
15 R. @ 7 3/4"17 R. @ 7 1/2" 14 T. @ 10" 16 T. @ 10"
34"-38" TALL GUARDRAIL
STAIR 6" A: 52 sq ft
03 A6.00 WI08 A9.01
14 R. @ 7 5/16" 13 T. @ 10"
28'-8"
WI05 A9.01 WI07 A9.01
D-3
D-3
03 A7.00
03 A6.01
20 A0.13
D-4
ELV A: 17 sq ft
BASEMENT GROSS EXTERIOR A: 965 sq ft
HW
R1
KITCHEN A: 164 sq ft
ELV A: 17 sq ft
MECH A: 18 sq ft
WI01 A9.01
BSMT. GROSS INT. (RES.) A: 840 sq ft
D-16
03 A6.00
GARAGE A: 785 sq ft
D-12
03 A6.01
W02 A9.00
BATH 1 A: 39 sq ft
RESTRM. A: 42 sq ft
60' 13'-10 7/8"
F
03 A6.00
PL
UP
DN
D-5
THERE SHALL BE NO PENETRATION IN ELEVATOR SHEAR WALLS
D-8
POWDER A: 20 sq ft
STO A: 19 sq ft
1 A9.05
PROVIDE I HR RATED CLG. UNDER STAIR
14 R. @ 7 5/16" 13 T. @ 10"
W01 A9.00
D-18
R1
48'-10 3/4"
SHEET NOTES
UP
LIVING A: 171 sq ft
D-19
45'-4 13/16"
6"
12 R. @ 7 3/4" 11 T. @ 10"
14 R. @ 7 9/16" 13 T. @ 10"
12'-6 3/8"
NICHE
6"
R1
1
3'-1 1/2"
FIRST FLOOR GROSS EXTERIOR A: 925 sq ft
DN
THERE SHALL BE NO PENETRATION IN ELEVATOR SHEAR WALLS
FO
16%
19'-3 3/8"
A: 859 sq ft 2ND FLOOR GROSS INTERIOR A: 775 sq ft
14 R. @ 7 9/16" 13 T. @ 10"
W10
12 R. @ 7 3/4" 11 T. @ 10"
W03 A9.00 2ND FLOOR GROSS EXTERIOR 16'-6 1/4"
CA LI
MIN. 200 SQ INCHES NET AREA OF NATURAL VENTILATION PROVIDED IN GARAGE DOOR PANEL
15'-9 7/8"
UP
SEE 2-A7.00 FOR SUN ACCESS SETBACK
RENEWAL DATE
OF
W04 A9.00
20%
FIRST FL. GROSS INT. (RES.) A: 322 sq ft
D-6
6-30-2019
B
D-15
D-14
W03 A9.00
W06 A9.00
HP
20%
W09
9'-11 3/16"
W06 A9.00
W09
3'-10"
3'-8 1/8"
B
10'-5 1/8"
B
E
T
3'-0" RESIDENTIAL REAR YARD SETBACK PER PLANNING COMMISION REQUEST 08/13/15
T E CM A
E D A RCH NS D GHAN IT E A N Y
LI RIC
(N) CURB CUT
A
1
NI
2
02 A6.01
LYNCH STREET
R
1
LYNCH STREET (BELOW)
03
0
2'
4'
8'
STORY 1 SCALE: 1/4" = 1'-0"
02
0
2'
4'
8'
BASEMENT SCALE: 1/4" = 1'-0"
01
A2.01
rg-architecture
GENERAL NOTES
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
1
2
02 A6.01
1
2
02 A6.01
1
2
02 A6.01
LI RIC
T E CM A
E D A RCH NS D GHAN IT E A N Y
T
B
B
B
B
B
NI
A
E
6-30-2019 RENEWAL DATE
OF
CA LI
R
ST
A
C-29116
FO
B
ROOF BELOW
PLANTER
9'-7 1/8"
42" GUARDRAIL, PTD. STEEL NON COMBUSTIBLE
DECK BELOW
W06 A9.00
42" PARAPET, TYP
SHEET NOTES
W06 A9.00
DECK A: 104 sq ft
W11
W03
PLANTER
DECK A: 98 sq ft
THERE SHALL BE NO PENETRATION IN ELEVATOR SHEAR WALLS
42" PARAPET, TYP
W12
03 A6.00
03 A6.00
03 A6.01
4TH FLOOR GROSS EXTERIOR A: 540 sq ft
03 A6.01
W03 A9.00
W02 A9.00
03 A6.00
WI05 A9.01
DN
BATH 2 A: 45 sq ft
D-6
HALL A: 127 sq ft
ISSUE
42" GUARDRAIL
13 R. @ 7 3/4" 12 T. @ 10"
D-8
WI03 A9.01
OWNER Mr. Harold Tang & Family
D-10
W02 A9.00
1370 Pacific Ave
WI01 A9.01
UP
FD
W03 A9.00
A
A
W02 A9.00
A
3'
8"
W02 W03 A9.00 6'-1"
17'-4"
BEDROOM 1 A: 133 sq ft
3'-1 1/2"
D-6
W04
7'-4"
W03 A9.00 W02 A9.00 W07
1 HOUR RATING W03 A9.00
W03 A9.00
W03
A
W02 A9.00
A W02 A9.00
W08
2'-1"
San Francisco, CA 94109 0155/021
KEY
3'
M. BATH A: 99 sq ft
W/D
LAUNDRY A: 8 sq ft
D-6
26'-11 3/8"
D-8
W02 A9.00
D-6
13 R. @ 7 3/4" 12 T. @ 10"
7 3/4"
DN
3'-2 5/8"
D-17
WALK-IN A: 39 sq ft
15 R. @ 7 3/4" UP 14 T. @ 10"
34"-38" TALL GUARDRAIL
R1 04/11/19 PLAN REVIEW COMMENTS
BATH 1 A: 40 sq ft
04/11/19 PLAN REVIEW COMMENTS
3'
29'-11 3/4"
29'-11 3/4"
15 R. @ 7 3/4" 14 T. @ 10"
34"-38" TALL GUARDRAIL
30'-8"
3'-1 1/2"
NFPA CLASS A FLAME SPREAD RATED DECKING, IPE OR SIMILAR HARDWOOD
11/01/18 ADDENDUM 2
3'-3/8"
7 3/4"
42" PARAPET, TYP
DN
3'-1 1/2"
W02 A9.00
W06 A9.00
15 R. @ 7 3/4" 14 T. @ 10"
ROOF DECK A: 269 sq ft
08/12/14 ORIGINAL SITE PERMIT
D-8
WI06 A9.01
34"-38" TALL GUARDRAIL
W06 A9.00
ISSUE
03 A7.00
M. BEDROOM A: 210 sq ft
3'-2 1/4"
03 A7.00
42" GUARDRAIL, PTD. STEEL NON COMBUSTIBLE, TYP
39'-3 3/4"
03 A7.00
REVISIONS NO. DATE
03 A6.01
D-6
D-3
4TH FLOOR GROSS INTERIOR A: 490 sq ft
D-9
W06 A9.00
D-9
W06 A9.00
3RD FLOOR GROSS INTERIOR A: 624 sq ft BEDROOM 2 A: 174 sq ft
R1
12'-4 3/8"
42" GUARDRAIL, PTD. STEEL NON COMBUSTIBLE
10'-1/8"
DECK BELOW
3RD FLOOR GROSS EXTERIOR A9.00 A: 718 sq ft
6'-1"
W04
7'-4"
W02 A9.00 W07
2 HOUR RATING
SCALE AS NOTED DRAWN BY
A
3 HOUR RATING
W08
ACCESSIBLE ROUTE
2'-1"
RG CHECKED BY RG PROJECT NO. 201209
1
02 A7.00
02 A6.00
2
1
02 A7.00
02 A6.00
2
1
02 A7.00
02 A6.00
DATE 4/29/19
2
DRAWING NO. 26 of 42
N
3RD-ROOF PLANS DRAWING NO.
0
2'
4'
8'
SCALE: 1/4" =
ROOF 1'-0"
03
0
2'
4'
8'
STORY 4 SCALE: 1/4" = 1'-0"
02
0
2'
4'
8'
STORY 3 SCALE: 1/4" = 1'-0"
01
A2.02
rg-architecture
GENERAL NOTES
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
1
2
1
2
LI RIC
R1
C-29116 ST
A
COMMERCIAL HEATPUMP A
E
T
INTAKE RESIDENTIAL
B
B
B
B
B
T E CM A
E D A RCH NS D GHAN IT E A N Y
NI
2
6-30-2019 RENEWAL DATE
OF
CA LI
R
1
FO
B
A 3D
FIRST FL. GROSS INT. (RES.) A: 322 sq ft
D
D EQ.
LIVING A: 171 sq ft
D
ENVIRONMENTAL EXHAUST DUCT UP TO ROOF
R1
EQ.
D
GFCI
KITCHEN A: 164 sq ft D
DISP
3D 3D
D
3D
GFCI
ELV A: 17 sq ft
KITCHEN GAS EXHAUST UP TO ROOF
FCU
14 R. @ 7 5/16" 13 T. @ 10"
D
14 R. @ 7 5/16" 13 T. @ 10"
17 R. @ 7 1/2" 16 T. @ 10"
D
04/11/19 PLAN REVIEW COMMENTS
J
17. MAINTAIN RATED SEPARATION BETWEEN R-OCCUPANCY AND B-OCCUPANCY.
3
18. ANY VENTILATION REQUIREMENTS FOR THE ELEVATOR HOISTWAY OR ELEVATOR CONTROLLER SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
KEY
MUD ROOM A: 14 sq ft
Mr. Harold Tang & Family
1370 Pacific Ave San Francisco, CA 94109 0155/021
#LayID
D F
A
A
SURFACE MOUNT FIXTURE LED STRIP LIGHT
B
STO A: 8 sq ft
A
OWNER
16. LIGHTING SHALL COMPLY WITH THE REQUIREMENTS OF CEC 150.0(K)
A
A
ISSUE
15. CLOTHES DRYER EXHAUST SHALL BE A MINIMUM 4 INCHES, TERMINATE TO THE OUTSIDE OF THE BUILDING, SHALL BE EQUIPPED WITH A BACK-DRAFT DAMPER, AND MEET THE REQUIREMENTS OF CMC 504.3. PROVIDE 100 SQ. INCH MINIMUM MAKE-UP AIR OPENING FOR DOMESTIC DRYERS.
F
LOCATION FOR RESIDENTIAL INTAKE
A
R1 04/11/19 PLAN REVIEW COMMENTS
14. ALL INTERIOR SPACES INTENDED FOR HUMAN OCCUPANCY SHALL BE PROVIDED WITH SPACE HEATING PER CBC 1204.1.
2 R. @ 5 1/4" UP 1 T. @ 1'-3"
2'-8 15/16"
A
OS
13. DOMESTIC RANGE HOOD VENTS SHALL MEET THE REQUIREMENTS OF CMC 504.2 AND COMPLY WITH CMC TABLE 403.7.
UP
EQ.
UP
S/CD
11/01/18 ADDENDUM 2
12. ENVIRONMENTAL AIR DUCTS SHALL TERMINATE 3 FEET FROM THE PROPERTY LINE AND 3 FEET FROM OPENINGS INTO THE BUILDINGS PER CMC 504.5 AND PROVIDE WITH BACK-DRAFT DAMPERS PER CMC 504.1
E.C.R. A: 13 sq ft
D D
08/12/14 ORIGINAL SITE PERMIT
11. COMBUSTION AIR SHALL MEET THE REQUIREMENT OF CMC CHAPTER 7.
D
R1
ISSUE
10. GAS VENT TERMINATIONS SHALL MEET THE REQUIREMENTS OF CMC 802.6 & SFMC 802.6.2.
FIRST FL. GROSS INT. (COMM.) A: 324 sq ft
DN
3D
2'-8 15/16"
D
DINING A: 288 sq ft
D
9. PROVIDE AT LEAST ONE 20-AMP CIRCUIT FOR BATHROOM OUTLETS, WITH NO OTHER OUTLETS ON THE CIRCUIT PER NEC §210.11(C)(3).
FIRST FL. GROSS INT. (RES.) A: 102 sq ft
D
REVISIONS NO. DATE
8. IN ALL AREAS SPECIFIED IN CEC §210.52, ALL 125 VOLT, 15AND 20- AMP RECEPTACLES SHALL BE LISTED AS TAMPER RESISTANT. CEC §406.11.
ELV A: 17 sq ft
FCU ENTRY A: 94 sq ft
J
7. RECEPTACLE OUTLETS SHALL BE SPACED SO THAT NO POINT ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 FT FROM AN OUTLET. THIS APPLIES TO ANY WALL SPACE 2 FT OR MORE WIDE, INCLUDING FIXED ROOM DIVIDERS SUCH AS BARS OR RAILINGS. CEC §210.52
F
EQ.
15 R. @ 7 3/4"17 R. @ 7 1/2" 14 T. @ 10" 16 T. @ 10"
D
D
3D
J
BASEMENT GROSS EXTERIOR A: 965 sq ft
GAS EXHAUST DUCT UP TO ROOF
INTAKE COMMERCIAL & RESIDENTIAL D
BSMT. GROSS INT. (RES.) A: 840 sq ft
HW
D
DN
STAIR A: 52 sq ft
KITCHEN GAS EXHAUST UP TO ROOF
MECH A: 18 sq ft
GAS INSTANTANEOUS HOT WATER HEATER
DW
D
EXHAUST COMMERCIAL
C L
GFCI
R1
RESTRM. A: 42 sq ft
3
ELV A: 17 sq ft
INTAKE COMMERCIAL & RESIDENTIAL
EQ.
J
GAS EXHAUST DUCT UP TO ROOF
6. ALL 120V, SINGLE PHASE, 150 AND 20-AMP BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED IN DWELLING UNTI SHALL BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER, COMBINATION TYPE, INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. CEC §210.12 (B)
R1
OS
F D
C
GAS EXHAUST DUCT UP TO ROOF
4. CARBON MONOXIDE DETECTORS SHALL BE INSTALLED PER BUILDING CODE. POWER SUPPLY SHALL BE RECEIVED FROM BUILDING WIRING. CEC §240.24 (C THROUGH E).
GARAGE A: 785 sq ft
J
H
3. WHEN MORE THAN ONE SMOKE DETECTOR IS REQUIRED, INDICATE THAT THEY ARE INTERCONNECTED SO THAT ACTIVATION OF ONE WILL ACTIVATE THEM ALL.
STO A: 19 sq ft
FCU J BATH 1 A: 39 sq ft
MINI TANKLESS HOT WATER SYSTEM
EQ.
INTAKE COMMERCIAL
GFCI
OS
H
A: 20 sq ft
F OS
DN
EXHAUST COMMERCIAL
2. SMOKE DETECTORS SHALL BE POWERED BY BUILDING WIRING CURRENT WITH BATTER BACKUP.
UP
D
ENVIRONMENTAL EXHAUST DUCT UP TO ROOF POWDERJ
UP
A
EQ.
DN
MM2
R1
D
SHEET NOTES 1. SMOKE DETECTORS SHALL COMPLY WITH UL 217 AND INSTALLED IN ACCORDANCE WITH THE BUILDING CODE AND NFPA 72.
H
3D
J
C L
FIRST FLOOR GROSS EXTERIOR A: 925 sq ft
12 R. @ 7 3/4" 11 T. @ 10"
EQ.
R1
12 R. @ 7 3/4" 11 T. @ 10"
EQ.
S/CD
EQ.
EQ.
A
D
14 R. @ 7 9/16" 13 T. @ 10"
D
14 R. @ 7 9/16" 13 T. @ 10"
UP
D
2ND FLOOR GROSS EXTERIOR A: 859 sq ft 2ND FLOOR GROSS INTERIOR A: 775 sq ft
SCALE
RECESSED FIXTURE, INTERIOR
AS NOTED
EXPOSED STRIP LIGHT FIXTURE
DRAWN BY
VANITY LIGHT
H J
FAN/LIGHT COMBO
RG CHECKED BY
MULTI-FUNCTION SMOKE & CO DETECTOR
S/CD
J
RG
JUNCTION BOX
PROJECT NO.
EXHAUST
FCU
INTAKE
201209
FAN COIL UNIT
DATE 4/29/19
1
2
1
2
1
2
DRAWING NO. 27 of 42
N
R1
BASEMENT-2ND RCP DRAWING NO.
0
2'
4'
8'
SCALE: 1/4" =
Story 2 1'-0"
03
0
2'
4'
8'
SCALE: 1/4" =
Story 1 1'-0"
02
0
2'
4'
8'
Basement SCALE: 1/4" = 1'-0"
01
A4.00
rg-architecture
GENERAL NOTES
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
1
2
1
2
1
2
LI RIC
T E CM A
E D A RCH NS D GHAN IT E A N Y
T
B
B
B
B
B
NI
A
E
6-30-2019 RENEWAL DATE
OF
CA LI
R
ST
A
C-29116
FO
B
SHEET NOTES DECK A: 104 sq ft
3RD FLOOR GROSS EXTERIOR A: 718 sq ft
EXHAUST COMMERCIAL R1
GAS EXHAUST DUCT
RESIDENTAIL HEATPUMP
3'
INTAKE COMMERCIAL & RESIDENTIAL
ENVIRONMENTAL EXHAUST DUCT UP TO ROOF GAS EXHAUST DUCT UP TO ROOF
R1
R1
DECK A: 98 sq ft
R1
ENVIRONMENTAL EXHAUST DUCT
3'
3RD FLOOR GROSS INTERIOR A: 624 sq ft BEDROOM 2 A: 174 sq ft A
R1
EXHAUST COMMERCIAL
ENVIRONMENTAL EXHAUST DUCT UP TO ROOF GAS EXHAUST DUCT UP TO ROOF
4TH FLOOR GROSS EXTERIOR A: 540 sq ft
REVISIONS NO. DATE INTAKE COMMERCIAL & RESIDENTIAL
A
4TH FLOOR GROSS INTERIOR A: 490 sq ft
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
OS
BATH 1 A: 40 sq ft
D
J
ENVIRONMENTAL EXHAUST DUCT UP TO ROOF KITCHEN GAS EXHAUST UP TO ROOF
DN
D
H W/D
DN
3
Mr. Harold Tang & Family
J FCU
HM. BATH
A: 99 sq ft
UP
H
IAQ FAN
1370 Pacific Ave
3
13 R. @ 7 3/4" 12 T. @ 10"
15 R. @ 7 3/4" 14 T. @ 10" UP
OWNER
LAUNDRY A: 8 sq ft
D
FD
KITCHEN GAS EXHAUST
04/11/19 PLAN REVIEW COMMENTS
220V
OS GFCI
ENVIRONMENTAL EXHAUST
ISSUE
ENVIRONMENTAL EXHAUST DUCT UP TO ROOF
GFCI
D
13 R. @ 7 3/4" 12 T. @ 10"
D
R1
BATH 2 FCU A: 45 sq ft
OS
WALK-IN A: 39 sq ft
A
HALL A: 127 sq ft
KITCHEN GAS EXHAUST UP TO ROOF
J
15 R. @ 7 3/4" 14 T. @ 10"
D
GFCI
3
R1
H
A
M. BEDROOM A: 210 sq ft
KEY
BEDROOM 1 A: 133 sq ft
J
1 HOUR RATING
D
GFCI
2 HOUR RATING
3'
A
San Francisco, CA 94109 0155/021
A
D
A
ISSUE
A
A
A
SCALE AS NOTED DRAWN BY
A
3 HOUR RATING
RG CHECKED BY
ACCESSIBLE ROUTE RG
PROJECT NO. 201209 DATE 4/29/19
1
2
1
2
1
2
DRAWING NO. 28 of 42
N
3RD-ROOF RCP DRAWING NO.
0
2'
4'
8'
Penthouse SCALE: 1/4" = 1'-0"
03
0
2'
4'
8'
SCALE: 1/4" =
Story 4 1'-0"
02
0
2'
4'
8'
SCALE: 1/4" =
Story 3 1'-0"
01
A4.01
rg-architecture
W03 3 5'-6 3/4" 3'-9 3/8"×5'-6 3/4"
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
5'-6 3/4"
W02 1 7'-9" 3'-6 3/4"×7'-9"
3'-9 3/8"
C-29116
A
Window List Element ID Quantity Height Unit Dimensions
W06 1 8' 1'-1/2"×8'
W07 2 5'-6 3/4" 5'-3 1/2"×5'-6 3/4"
5'-6 3/4"
8'
View from Opening Side
8'
8'
E
5'-3 1/2" 5'-3 1/2"
Window List Element ID Quantity Height Unit Dimensions
W09 2 7' 4'-6"×7'
W10 1 7'-10 1/2" 14'-9 1/2"×8'
W12 1 7'-10 1/2" 12'-3"×8'
E 8'
8'
7'
14'-9 1/2"
FO
1'-1/2"
W11 1 7'-10 1/2" 12'-3"×8'
E
4'-6"
CA LI
1'-1/2"
E View from Opening Side
RENEWAL DATE
OF
12'-3"
8'
2'-3"
W08 2 5'-6 3/4" 1'-1/2"×5'-6 3/4"
6-30-2019
5'-6 3/4"
W05 1 8' 5'-3 1/2"×8'
T
W04 3 8' 2'-3"×8'
E
NI
ST
A
3'-6 3/4"
R
3'-8"
T E CM A
E D A RCH NS D GHAN IT E A N Y
LI RIC
7'-9"
1'
W01 1 7'-9" 3'-8"×7'-9"
6"
10"
10"
View from Opening Side
NA 2 6" 1'×6"
2 10" 10"×10"
7'-9"
Window List Element ID Quantity Height Unit Dimensions
12'-3" REVISIONS NO. DATE
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
ISSUE 04/11/19 PLAN REVIEW COMMENTS
OWNER Mr. Harold Tang & Family
1370 Pacific Ave San Francisco, CA 94109 0155/021
SCALE AS NOTED DRAWN BY RG CHECKED BY RG PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 29 of 42
WINDOW SCHEDULE
DRAWING NO.
A5.00
Door List Element ID W x H Size Quantity Orientation Fire Rating
D-1 3'×7'-8" 1 R
D-2 3'×7'-8" 1 L
D-3 2'-8"×7'-6" 3 L 90 MIN
D-4 2'-8"×7'-6" 1 L
D-5 3'×7'-6" 1 L
D-6 2'-8"×7'-6" 7 R
D-8 2'-6"×7'-6" 4 R
D-9 3'-6"×7'-6" 2
rg-architecture
D-10 4'-6 1/2"×7'-6" 1
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
7'-6 3/4"
LI RIC
7'-6 3/4"
7'-6 3/4"
7'-6 3/4"
7'-6 3/4"
7'-6 3/4"
E D A RCH NS D GHAN IT E A N Y
T E CM A
7'-6 3/4"
3D Back View
9'-2 3/4"
9'-2 3/4"
R1
D-14 3'×6'-8" 1 R
D-15 8'×7'-5" 1
D-16 2'-8"×6'-8" 1 L 90 MIN
2'-11 1/2"
E
3'-2"
8'
D-18 2'-8"×7' 1 R
NI
6-30-2019 RENEWAL DATE
OF
CA LI
FO
D-19 2'-8"×7' 1 L
6'-8 3/4" 2'-9 1/2"
2'-9 1/2"
7'-3/4"
R1
7'-5"
6'-9"
6'-8 3/4"
6'-8 3/4"
6'-8 3/4"
3'-7 1/2"
D-17 2'-8"×7'-6" 1 R
7'-3/4"
D-13 2'-10"×6'-8" 1 L
7'-6 3/4"
D-12 3'-6"×6'-8" 1 L
MIN. 200 SQ INCHES NET AREA OF NATURAL VENTILATION PROVIDED IN GARAGE DOOR PANEL
5'-7 1/2"
4'-8"
T
D-11 5'-6"×6'-8" 2
3D Back View
3'-7 1/2"
R
2'-7 1/2"
A
Door List Element ID W x H Size Quantity Orientation Fire Rating
5'-11"
2'-9 1/2"
3'-1 1/2"
ST
3'-2"
2'-9 1/2"
2'-9 1/2"
A
C-29116
2'-9 1/2"
2'-9 1/2"
R1
REVISIONS NO. DATE
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
ISSUE 04/11/19 PLAN REVIEW COMMENTS
OWNER Mr. Harold Tang & Family
1370 Pacific Ave San Francisco, CA 94109 0155/021
SCALE AS NOTED DRAWN BY RG CHECKED BY RG PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 30 of 42
DOOR SCHEDULE
DRAWING NO.
A5.01
rg-architecture 428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
LI RIC
T E CM A
E D A RCH NS D GHAN IT E A N Y
T
B
+264'-7" T.O. Roof
1
A
NI
A
E
6-30-2019 RENEWAL DATE
OF
CA LI
R
ST
A
C-29116
FO
2
HEIGHT LIMIT
40'-0" HEIGHT LIMIT (FROM PACIFIC AVE) SEC. 102.12 (a), (b) & (d)
CORNICE
CEMENT BOARD SIDING, PAINTED
STUCCO +254'-11" Story 4
WOOD SIDING, STAINED ALUMINUM CLAD WINDOWS, TYP.
OUTLINE OF ADJACENT BUILDING (1372-74 PACIFIC AVE.)
REVISIONS NO. DATE
E
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
40'-0"
+245'-3" Story 3
ISSUE 04/11/19 PLAN REVIEW COMMENTS
BLIND WALL +235'-7" Story 2
OWNER
10'
9'-6"
Mr. Harold Tang & Family
1370 Pacific Ave San Francisco, CA 94109 0155/021
+225' Story 1 SIDEWALK
SCALE
PACIFIC AVE.
AS NOTED DRAWN BY RG CHECKED BY
LYNCH ST.
+216'-6" Basement
RG
SIDEWALK
PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 31 of 42
ELEVATIONS 0
2'
4'
8'
WEST ELEVATION (1370) SCALE: 1/4" = 1'-0"
03
0
2'
4'
8'
SOUTH ELEVATION (PACIFIC) SCALE: 1/4" = 1'-0"
02 DRAWING NO.
A6.00
rg-architecture 428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
LI RIC
T E CM A
E D A RCH NS D GHAN IT E A N Y
T
A
+264'-7" T.O. Roof
6-30-2019 RENEWAL DATE
OF
CA LI
FO
1
2
B
NI
A
E
R
ST
A
C-29116
40'-0" HEIGHT LIMIT (FROM PACIFIC AVE) SEC. 102.12 (a), (b) & (d)
40'-0" HEIGHT LIMIT (FROM PACIFIC AVE) SEC. 102.12 (a), (b) & (d)
ALUMINUM CLAD WINDOWS, TYP.
+254'-11" Story 4
STUCCO 2'-11" REVISIONS NO. DATE 8'
E
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
BLIND WALL
+245'-3" Story 3
ISSUE 04/11/19 PLAN REVIEW COMMENTS +235'-7" Story 2
OWNER
2'-1"
4'-4"
Mr. Harold Tang & Family E
1370 Pacific Ave San Francisco, CA 94109 0155/021
+225' Story 1
BOARD FORMED CONCRETE
SIDEWALK PACIFIC AVE.
SCALE AS NOTED DRAWN BY SIDEWALK
RG CHECKED BY
LYNCH ST.
RG
PLANTER +216'-6" Basement
PROJECT NO.
MIN. 200 SQ INCHES NET AREA OF NATURAL VENTILATION PROVIDED IN GARAGE DOOR PANEL
R1
201209 DATE 4/29/19 DRAWING NO. 32 of 42
ELEVATIONS 0
2'
4'
8'
EAST ELEVATION (1370) SCALE: 1/4" = 1'-0"
03
0
2'
4'
8'
NORTH ELEVATION (LYNCH) SCALE: 1/4" = 1'-0"
02 DRAWING NO.
A6.01
rg-architecture 428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
LI RIC
T E CM A
E D A RCH NS D GHAN IT E A N Y
T
9'-9"
F04 A9.02
5 A9.04 +254'-11" Story 4
F05 A9.02
F03 A9.02
2
+264'-7" T.O. Roof
F04 A9.02
6-30-2019 RENEWAL DATE
OF
CA LI
FO
OUTLINE OF PROPOSED ADJACENT BUILDING (1364 PACIFIC AVE.)
40'-0" HEIGHT LIMIT (FROM PACIFIC AVE) SEC. 102.12 (a), (b) & (d)
R1
F06 A9.02
17 A9.05
+254'-11" Story 4
OUTLINE OF ADJACENT BUILDING (1372-74 PACIFIC AVE.)
F03 A9.02
REVISIONS NO. DATE
8'-4 7/8"
9'-7"
ADJACENT PROPERTY LINE
9'-4"
REAR PROPERTY LINE
15'-0" 25% SETBACK
27'-0" 45% SETBACK
40'-0" HEIGHT LIMIT (FROM PACIFIC AVE) SEC. 102.12 (a), (b) & (d)
3'-0" RESIDENTIAL REAR YARD SETBACK PER PLANNING COMMISION REQUEST 08/13/15
+264'-7" T.O. Roof
1
B
PROPERTY LINE
A
NI
A
E
R
ST
A
C-29116
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
+245'-3" Story 3 45'-9 1/4"
+245'-3" Story 3
F05 A9.02
F03 A9.02
8'-4"
F03 A9.02
ISSUE 04/11/19 PLAN REVIEW COMMENTS
ES C
7'-6 7/8"
F03 A9.02
AC S E AN PL
1370 Pacific Ave
EC
(S
9'-3 7/8"
Mr. Harold Tang & Family
N
F05 A9.02
OWNER
SU
F03 A9.02
37'-1 7/8"
+235'-7" Story 2 1'-3 1/8"
+235'-7" Story 2
1. 26 1)
San Francisco, CA 94109 0155/021
7'-3 1/2"
F02 A9.02
GRADE PLANE
+225' Story 1
F02 A9.02
3'-2 1/2"
+225' Story 1
NATURAL PL
ANE
SCALE
F02 A9.02
45°
AS NOTED DRAWN BY RG CHECKED BY
EL. 219'-1" @ CENTER OF LOT
BASEMENT
RG PROJECT NO. 201209
1'
+216'-6" Basement
+216'-6" Basement F01 A9.02
DATE
F01 A9.02
4/29/19 DRAWING NO. 33 of 42
BUILDING SECTIONS
0
2'
4'
8'
LONGITUDINAL SECTION SCALE: 1/4" = 1'-0"
02
0
2'
4'
8'
TRANSVERSE SECTION SCALE: 1/4" = 1'-0"
03
DRAWING NO.
A7.00
-9'-3/4" Basement
-6 3/4" Story 1
+10'-1/4" Story 2
+19'-8 1/4" Story 3
+29'-4 1/4" Story 4
+39'-1/4" T.O. Roof
T.O. PLYWD
6 A9.03
B.O FRAMING
T.O. PLYWD
VARIES
B.O FRAMING
T.O. PLYWD
3 A9.03
B.O FRAMING
TYPICAL WALL ON PACIFIC AVE. SCALE: 1/2" = 1'-0"
SIDEWALK T.O SLAB
3 A9.03
6 A9.03
7 A9.03
1 1/4" 8"
1 1/4" 8"
2
13 A9.06
13 A9.06
13 A9.06
VARIES
REVISIONS NO. DATE
A7.01
DRAWING NO.
E
OF
RENEWAL DATE
CA LI
NI
6-30-2019 FO
R
A
LI RIC
BAY WINDOW WALL ON PACIFIC AVE. SCALE: 1/2" = 1'-0"
SIDEWALK T.O SLAB
F02 A9.02
B.O FRAMING
T.O. PLYWD
2 A9.03
B.O FRAMING
T.O. PLYWD
3 A9.03
2 A9.03
B.O FRAMING
T.O. PLYWD
3 A9.03
2 A9.03
4 A9.03
1 1/4" 1'-5/8" 1 1/4" 1'-5/8" 1 1/4"
1
9'-8" 9'-8" 9'-8" 10'-7" 8'-6"
SIM.
T
SIM.
A
PL
E D A RCH NS D GHAN IT E A N Y
T E CM A
ST
PL
-9'-3/4" Basement
-6 3/4" Story 1
+10'-1/4" Story 2
+19'-8 1/4" Story 3
+29'-4 1/4" Story 4
+39'-1/4" T.O. Roof
rg-architecture
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
C-29116
ISSUE
08/12/14 ORIGINAL SITE PERMIT
11/01/18 ADDENDUM 2
R1 04/11/19 PLAN REVIEW COMMENTS
ISSUE
04/11/19 PLAN REVIEW COMMENTS
OWNER Mr. Harold Tang & Family
1370 Pacific Ave
San Francisco, CA 94109 0155/021
SCALE
AS NOTED DRAWN BY
RG CHECKED BY
RG
PROJECT NO.
201209
DATE 4/29/19
DRAWING NO. 34 of 42
ENLARGED WALL SECTIONS
8'-4 5/8"
CBC 721.1(2) ITEM 4-1.1
rg-architecture
3 HOUR EXTERIOR WALL
STC -
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
LI RIC
T E CM A
E D A RCH NS D GHAN IT E A N Y
T
DRAINAGE BOARD O/ LIQUID APPLIED FOUNDATION WATERPROOFING WHERE BELOW GRADE CONDITION OCCURS
SHOTCRETE
1 HOUR
LOAD-BEARING
WOOD STUDS
RENEWAL DATE
OF
CA LI
FO
EXT.
PROPERTY LINE WHERE OCCURS
U344
6-30-2019
R
A
E
NI
A
C-29116 ST
4"
1 HR ASSEMBLY 8"-10" SSD
INT.
W04 DS# EXTERIOR WALL
N/A STC -
2' MAX. S.S.D
1/2" PLYWOOD, S.S.D. FOR SHEATHING REQ.
8 1/8"
1 HR ASSEMBLY
1 HR ASSEMBLY 1 HR ASSEMBLY 7 1/4"
7/8" 3-PART STUCCO O/ EXPANDED METAL LATH O/ LIQUID APPLIED WATERPROOF MEMBRANE 5/8" TYPE X EXT. GYP. SHEATHING
5/8" TYPE X GYP. BD. 2 x 6 WOOD STUDS @ 24" O.C. MAX.
U344
1 HOUR
LOAD-BEARING
WOOD STUDS
DS# PARAPET PARTITION
N/A STC -
U344
1 HOUR
LOAD-BEARING
WOOD STUDS
2' MAX. S.S.D
W03 DS# EXTERIOR WALL
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
2' MAX. S.S.D
3/4" MAX. FIBER CEMENT LAP SIDING O/ LIQUID APPLIED WATERPROOF MEMBRANE 5/8" TYPE X EXT. GYP. SHEATHING
1/2" PLYWOOD, S.S.D. FOR SHEATHING REQ.
1/2" PLYWOOD, S.S.D. FOR SHEATHING REQ.
04/11/19 PLAN REVIEW COMMENTS
8"
8 3/4"
ISSUE
1 HR ASSEMBLY 7 1/4"
3/4" MAX. FIBER CEMENT LAP SIDING O/ LIQUID APPLIED WATERPROOF MEMBRANE WHERE OCCURS 5/8" TYPE X EXT. GYP. SHEATHING
5/8" TYPE X GYP. BD.
5/8" TYPE X EXT. GYP. SHEATHING 3/4" MAX. FIBER CEMENT LAP SIDING O/ LIQUID APPLIED WATERPROOF MEMBRANE
NOTE: USED AT VISIBLE SIDE LOT LINE WALL LOCATIONS
W06 U344 LOAD-BEARING
1 HOUR
DS# EXTERIOR WALL
WOOD STUDS
OWNER Mr. Harold Tang & Family
1370 Pacific Ave
2 x 6 WOOD STUDS @ 24" O.C. MAX.
W02 N/A STC -
San Francisco, CA 94109 0155/021
SCALE AS NOTED DRAWN BY
2' MAX. S.S.D
RG CHECKED BY
1/2" P.T. PLYWOOD O/ LIQUID APPLIED WATERPROOF MEMBRANE
RG
5/8" TYPE X EXT. GYP. SHEATHING
PROJECT NO.
1 HR ASSEMBLY 7 1/4"
1/2" PLYWOOD, S.S.D. FOR SHEATHING REQ.
201209 DATE 4/29/19
7 3/4"
1 HR ASSEMBLY 8 3/4"
N/A STC -
REVISIONS NO. DATE
WALL TYPES EXT.
DRAWING NO.
5/8" TYPE X GYP. BD. 2 x 6 WOOD STUDS @ 24" O.C. MAX.
NOTE: USED AT BLIND WALL LOCATIONS
DRAWING NO. 35 of 42
W01
A9.00
U423
2 HOUR
LOAD-BEARING
STEEL STUDS
TEST NO.
920479 N/A INTERIOR PARTITION STC -
rg-architecture
FIRE RATING INTERIOR FURRING
24" MAX. S.S.D
STC -
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
16" MAX. S.S.D
2 x 5/8" TYPE X GYP. BD.
5/8" TYPE X GYP. BD.
LI RIC
T E CM A
E D A RCH NS D GHAN IT E A N Y
A
T
6" STEEL STUDS @ 24" O.C. MAX.
U301
2 HOUR
LOAD-BEARING
WOOD STUDS
6-30-2019 RENEWAL DATE
OF
CA LI
FO
2X4 @ 16" OC, WHERE TYPE 5A CONSTRUCTION ALLOWED. TURNED WHERE REQ'D.
2 x 5/8" TYPE X GYP. BD.
NOTE: USED WHERE NON-COMBUSTIBLE ASSEMBLIES ARE REQUIRED
NI
A
E
R
ST
8 1/2"
C-29116
NOTE: FURRING WALL, NON-RATED
WI08
DS# N/A INTERIOR PARTITION STC -
U305
1 HOUR
LOAD-BEARING
WOOD STUDS
WI04 920553 RAL-TL11-172 INTERIOR PARTITION STC = 33
16" MAX. S.S.D 16" MAX. S.S.D
1/2" PLYWOOD, S.S.D. FOR SHEATHING REQ. 2 x 5/8" TYPE X GYP. BD.
2 x 5/8" TYPE X GYP. BD.
6 3/4"
9"
1 HR ASSEMBLY 6 3/4"
5/8" TYPE X GYP. BD.
5/8" TYPE X GYP. BD.
1/2" PLYWOOD, S.S.D. FOR SHEATHING REQ.
2 x 6 WOOD STUDS @ 16" O.C. MAX.
2 x 6 WOOD STUDS @ 24" O.C. MAX.
NOTE: USED AT SHAFT LOCATIONS, DOUBLE SHEAR
U301
2 HOUR
LOAD-BEARING
WOOD STUDS
WI07
DS# N/A INTERIOR PARTITION STC -
U423
1 HOUR
LOAD-BEARING
STEEL STUDS
16" MAX. S.S.D
WI03 920622 USG-810519 INTERIOR PARTITION STC = 40
REVISIONS NO. DATE
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
24" MAX. S.S.D
2 x 5/8" TYPE X GYP. BD. 5/8" TYPE X GYP. BD. ISSUE
8 1/2"
4 3/4 in
04/11/19 PLAN REVIEW COMMENTS
OWNER Mr. Harold Tang & Family
5/8" TYPE X GYP. BD. 3 1/2" STEEL STUDS @ 24" O.C. MAX.
2 x 5/8" TYPE X GYP. BD. 1/2" PLYWOOD, S.S.D. FOR SHEATHING REQ.
NOTE: USED WHERE NON-COMBUSTIBLE ASSEMBLIES ARE REQUIRED
2 x 6 WOOD STUDS @ 24" O.C. MAX.
NOTE: USED AT SHAFT LOCATIONS, SINGLE SHEAR
U301
2 HOUR
LOAD-BEARING
WOOD STUDS
WI06
PPM 90024 USG-810218 INTERIOR PARTITION STC = 52
U305
1 HOUR
LOAD-BEARING
WOOD STUDS
1370 Pacific Ave
WI02 920553 RAL-TL11-172 INTERIOR PARTITION STC = 33
San Francisco, CA 94109 0155/021
SCALE AS NOTED DRAWN BY
24" MAX. S.S.D
RG CHECKED BY
16" MAX. S.S.D
2 x 5/8" TYPE X GYP. BD.
RG
5/8" TYPE X GYP. BD.
PROJECT NO. 201209
8"
4 3/4 in
DATE 4/29/19 DRAWING NO. 36 of 42
WALL TYPES INTERIOR
5/8" TYPE X GYP. BD. 2 x 4 WOOD STUDS @ 16" O.C. MAX.
2 x 5/8" TYPE X GYP. BD. 2 x 6 WOOD STUDS @ 24" O.C. MAX.
NOTE: USED AT SHAFT LOCATIONS
DRAWING NO.
WI05
WI01
A9.01
FRAMING DROPPED SOFFIT WHERE OCCURS ROOF
TEST NO./ FIRE RATING/ STC 1 HR TJI ROOF ASSEMBLY W/ PAVERS 2013 CBC TABLE 722.6.2 | 1HR | 59 SCALE: 3" = 1'-0"
RATED WALL ASSEMBLY PER PLANS
1/2" MIN.
MECH.DUCTING WHERE OCCURS FRAMING DROPPED SOFFIT WHERE OCCURS ROOF
NI
A RENEWAL DATE
OF
CA LI
R
6-30-2019
FO
RESILIENT CHANNEL @ 16" O.C. 2 LAYERS 1/2" SHEETROCK MIN. BRAND FIRECODE C CORE GYPSUM PANELS STANDARD CEILING 2ND - 4TH STORY
NOTE: SEE ALSO ACOUSTIC DETAILS 13 & 14/A7.02
TEST NO./ FIRE RATING/ STC UL L570 | 1HR | STC62
MECH.DUCTING WHERE OCCURS FRAMING DROPPED SOFFIT WHERE OCCURS 2ND - 4TH STORY 1/2" TYPE 'C' GYPSUM WALL BOARD
1 HR WOOD FLOOR ASSEMBLY SCALE: 3" = 1'-0"
F03
R1
3/4"
3/4" HARDWOOD O/ UNDERLAYMENT
ISSUE
TYPICAL SPRAYAPPLIED FIRE RESISTIVE MATERIAL THICKNESS @ RESTRAINED BEAM
R1 04/11/19 PLAN REVIEW COMMENTS
ROD COUPLER UL N706 3 HR ASSEMBLY
1 1/4"
11/01/18 ADDENDUM 2
3/4" PLY COMPOSITE PAN DECK W/ APPLIED FIRE PROOFING
3/4" 2 1/2" 1 1/2"
1 1/2"
W8 x 24 MIN., SSD
UL N706 3 HR ASSEMBLY
1/2"
1/2" 1'-6"
TYPICAL SPRAYAPPLIED FIRE RESISTIVE MATERIAL THICKNESS @ DECK
2 1/2"
T.O.C. STORY 1
2 1/2"
1 1/2"
F05
R1
F.F. STORY 1
4"
2"MIN.
E
08/12/14 ORIGINAL SITE PERMIT 1 1/2"
4"
LOT LINE
1 HR LVL ROOF ASSEMBLY SCALE: 3" = 1'-0"
3/4" PLYWOOD SHEATHING; S.S.D.
REVISIONS NO. DATE
L LEDGER,SSD. PROVIDE 1 1/4" THICKNESS SPRAY APPLIED FIRE RESISTIVE MATERIAL
16 GA GSM Z FLASHING
TEST NO./ FIRE RATING/ STC 2013 CBC TABLE 722.6.2 | 1HR | 59
F04
R1
PT MUD SILL SET IN BED OF CONTINUOUS SEALANT
1/2" MIN.
1/2" TYPE 'C' GYPSUM WALL BOARD
1 1/2"
LIQUID APPLIED WATERPROOF MEMBRANE, LAP O/ FLASHING
1 HR ASSEMBLY
1 HR ASSEMBLY
RESILIENT CHANNEL @ 16" O.C. 2 LAYERS 1/2" SHEETROCK MIN. BRAND FIRECODE C CORE GYPSUM PANELS STANDARD CEILING 2ND - 4TH STORY
1/2" TYPE 'C' GYPSUM WALL BOARD
C-29116
3 1/2" NON-COMBUSTIBLE GLASS FIBER INSULATION 0.90 PCF IN JOIST SPACE; STAPLE TO PLY (OPTIONAL)
1/2" MIN.
MECH.DUCTING WHERE OCCURS
1/2" MIN.
NON-RATED ASSEMBLY
SEE RCP FOR SOFFITING LOCATIONS
R1
RESILIENT CHANNEL @ 16" O.C. 2 LAYERS 1/2" SHEETROCK MIN. BRAND FIRECODE C CORE GYPSUM PANELS STANDARD CEILING ROOF
FINISHED FLOOR 2ND - 4TH STORY
11 7/8" TJI FRAMING S.S.D.
2X OR LVL OR PSL S.S.D R38 NON-COMBUSTIBLE GLASS FIBER INSULATION 0.90 PCF IN JOIST SPACE; STAPLE TO PLY
1/2" MIN.
1/2" MIN.
F06
R38 NON-COMBUSTIBLE GLASS FIBER INSULATION 0.90 PCF IN JOIST SPACE; STAPLE TO PLY
NON-RATED ASSEMBLY
1 HR ASSEMBLY
2 HR ELEVATOR CEILING SCALE: 3" = 1'-0"
11 7/8" TJI FRAMING S.S.D.
E D A RCH NS D GHAN IT E A N Y
T
1 LAYERS 1/2" SHEETROCK BRAND FIRECODE C CORE GYPSUM PANELS 25 MIN PER TABLE 722.6.2(1)
1/2" PROTECTIVE BD. 3/4" PLYWOOD SHEATHING; S.S.D.
3/4" GYPSUM CONCRETE UNDERLAYMENT
A
3/4" PLYWOOD SHEATHING; S.S.D.
1/8"
TYP.
ST
2 LAYERS 5/8" SHEETROCK MIN. BRAND FIRECODE C CORE GYPSUM PANELS 40MIN EACH (80MIN) PER TABLE 7.22.6.2(1)
R10 MIN. POLYISO. TAPERED INSULATION T.O. PLYWD. ROOF
NON-RATED ASSEMBLY
3 1/2" NON-COMBUSTIBLE GLASS FIBER INSULATION 15MIN PER TABLE 722.6.2(5)
1/2" PROTECTIVE BD.
1'-3 1/8"
NOTE: SEE ALSO AB-005 REGARDING ROOF DECK CONSTRUCTION
NOTE: SEE ALSO AB-005 REGARDING ROOF DECK CONSTRUCTION
3/8" LATEX PORTLAND CEMENT MORTAR BOND COAT ON WATERPROOF MEMBRANE
T E CM A
2 HR ASSEMBLY
9"
3/4" PLYWOOD SHEATHING; S.S.D. 2X WOOD JOIST S.S.D. 10MIN PER TABLE 722.6.2(2)
FINISH FLOOR PER SCHEDULE MEMBRANE ROOF WATERPROOF CLASS B MIN. ROOF MEMBRANE COVERING PER SFBC (IN WET LOCATIONS 1509.10 AND CBC 1505.1 UNDER WOOD) FINISHED FLOOR 2ND - 4TH STORY R10 MIN. POLYISO. TAPERED INSULATION PROVIDE RADIANT BARRIER PER CENC 110.8 (J)
LI RIC
PEDESTAL SYSTEM MEMBRANE ROOF CLASS B MIN. ROOF COVERING PER SFBC 1509.10 AND CBC 1505.1 PROVIDE RADIANT BARRIER PER CENC 110.8 (J)
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
1/4" CERAMIC TILE (ALIGN W/ ADJACENT WOOD FIN. FLOOR)
1/4" PRE-ENGINEERED WOOD FLOORING PER FINISH SCHEDULE
SEE RCP FOR SOFFITING LOCATIONS
3/4" GYPSUM CONCRETE UNDERLAYMENT FINISHED FLOOR 4TH STORY
TEST NO./ FIRE RATING/ STC 2013 CBC TABLE 722.6.2 | 2HR
rg-architecture
CLASS B MIN. ROOF COVERING PER CBC SEC. 1505.1
SEE RCP FOR SOFFITING LOCATIONS
1/4" PRE-ENGINEERED WOOD FLOORING PER FINISH SCHEDULE
1/4" ROD HANGERS
ISSUE
R-19 BATT INSULATION, WHEN ABOVE UN-CONDITIONED SPACE
04/11/19 PLAN REVIEW COMMENTS
OWNER
1 1/2" C.R. CHANNELS
Mr. Harold Tang & Family
SUSPENDED GYP. BD CLNG, TYP. HAT CHANNEL DRAINAGE BOARD O/ LIQUID APPLIED FOUNDATION WATERPROOFING WHERE BELOW GRADE CONDITION OCCURS PT LAGGING PER SHORING PLANS
OPTIONAL FINISH CEILING
R1
UL N779 | 2 HR | R 20.08
5/8" TYPE X GYP. BD. PAN DECK COMPOSITE FLOOR | 3HR SCALE: 3" = 1'-0"
1370 Pacific Ave F02
855 Folsom Street #330 San Francisco, CA 94107
SCALE AS NOTED
T.O.S. BASEMENT
DRAWN BY RG CHECKED BY RG PROJECT NO. 201209 DATE 4/29/19 DRAWING NO. 37 of 42
FLOOR & ROOF TYPES DRAWING NO.
SLAB ON GRADE SCALE: 3" = 1'-0"
F01
A9.02
rg-architecture
E D A RCH NS D GHAN IT E A N Y
A
T
BATT INSULATION FIBER CEMENT LAP SIDING PER ELEVATION
1/2" PLYWOOD
1/4":12" MIN.
6-30-2019 RENEWAL DATE
OF
CA LI
FO
5/8" TYPE 'X' EXT. GYP. SHEATHING
5/8" TYPE 'X' EXT. GYP. SHEATHING
HIGH END OF PARAPET SCALE: 3" = 1'-0"
E
NI
WATER RESISTANT UNDERLAYMENT, PER SPECIFICATIONS
A
C-29116 ST
WATER RESISTANT UNDERLAYMENT, PER SPECIFICATIONS
R-10 SLOPED RIGID INSULATION
R
ALIGHN W/ LOW END OF PARAPET
R-10 SLOPED RIGID INSULATION
SINGLE PLY ROOFING LAP TO ADJ SURFACES PROTECTIVE BOARD GSM FLASHING WITH CLEAT
LI RIC
1/4":12" MIN.
SINGLE PLY ROOFING LAP TO ADJ SURFACES PROTECTIVE BOARD GSM FLASHING WITH CLEAT
T E CM A
ALIGHN W/ LOW END OF PARAPET
1/4":12" MIN.
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
1/2" PLYWOOD
7
1/4":12" MIN.
WALL TYPE PER PLAN
HIGH END OF PARAPET SCALE: 3" = 1'-0"
4
WALL TYPE PER PLAN
3/4" TRIM, PAINTED, SEE FINISH SCHEDULE 4"
4"
3/4" TRIM, PAINTED, SEE FINISH SCHEDULE FLOORING, SEE FINISH SCHEDULE 5/8" TYPE 'X' EXT. GYP. SHEATHING
FLOORING, SEE FINISH SCHEDULE 5/8" TYPE 'X' EXT. GYP. SHEATHING
LIQUID APPLIED WATERPROOFING MEMBRANE FIBER CEMENT LAP SIDING PER ELEVATION
REVISIONS NO. DATE
WATER RESISTANT UNDERLAYMENT, PER SPECIFICATIONS
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
Wx BEAM, S.S.D.
Wx BEAM, S.S.D.
3 PART CEMENT PLASTER
1/2" RC-1 RESILIENT CHANNEL
AIR SEALANT
2 LAYERS 5/8" TYPE 'X' GYP. BD.
1/2" RC-1 RESILIENT CHANNEL
CONTINUOUS LIQUID APPLIED WATERPROOF MEMBRANE
PAINTABLE CAULK
SEALANT
EXTENDED ALUMINUM FRAME NAIL-ON WINDOW
04/11/19 PLAN REVIEW COMMENTS
4" MIN. LIQUID APPLIED FLASHING
AIR SEALANT
2 LAYERS 5/8" TYPE 'X' GYP. BD.
CONTINUOUS LIQUID APPLIED WATERPROOF MEMBRANE
PAINTABLE CAULK
OWNER Mr. Harold Tang & Family
EXTENDED ALUMINUM FRAME NAIL-ON WINDOW
1370 Pacific Ave WINDOW HEAD @ BAY SCALE: 3" = 1'-0"
WINDOW HEAD, TYP. SCALE: 3" = 1'-0"
6
3
855 Folsom Street #330 San Francisco, CA 94107
SCALE AS NOTED
SHIM AS REQ'D
MDO SILL W/ SAWCUT REVEAL, PTD.
RG CHECKED BY
SHIM AS REQ'D
MDO SILL W/ SAWCUT REVEAL, PTD.
EXTENDED ALUMINUM FRAME NAIL-ON WINDOW
RG
EXTENDED ALUMINUM FRAME NAIL-ON WINDOW
1/4"
PROJECT NO. 201209 DATE
1/2" 1/4"
1/4"
DRAWN BY
PL
PL
FIBER CEMENT LAP SIDING PER ELEVATION
AIR SEALANT
DRAWING NO. 38 of 42
WINDOW DETAILS
CONTINUOUS LIQUID APPLIED WATERPROOF MEMBRANE
LIQUID APPLIED WATERPROOFING MEMBRANE WINDOW SILL @ BAY, TYP. SCALE: 3" = 1'-0"
4/29/19 4"
AIR SEALANT
4"
1/2" 1/4"
SEALANT
4" MIN. LIQUID APPLIED FLASHING
ISSUE
5
WINDOW SILL, TYP. SCALE: 3" = 1'-0"
2
DRAWING NO.
A9.03
rg-architecture 428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
LI RIC
T E CM A
E D A RCH NS D GHAN IT E A N Y
NI
A
T
E
6-30-2019 RENEWAL DATE
OF
CA LI
R
ST
A
C-29116
FO
GSM PARAPET CAP ATTACH WITH CLEAT
42" ABOVE DECK
1/2" PLATE STEEL WELDED TO STANCHION
1/2" TEMPERED GLASS CR LAWRENCE WALL MOUNT 2"x2" SQUARE CLAMPS FIBER CEMENT PANEL OR SIDING
8" FIBER CEMENT SIDING
1/2x3" PLATE STEEL STANCHION WELDED TO BASE PLATE
WATER RESISTANT UNDERLAYMENT, PER SPECIFICATIONS
3'-6"
1 LAYER 5/8" TYPE X EXT. GYP. SHEATHING 1/2" PLYWOOD
NOTE: GUARDRAIL DESIGNED TO RESIST LIVE LOAD FORCES PER CBC 1607.8.1
REVISIONS NO. DATE
PARAPET BRACING, S.S.D
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
2X6 STUDS @ 16" O.C., S.S.D. COUNTERFLASHING ISSUE
BASE FLASHING SHOULD EXTEND 8" TO 12" ABOVE HIGHEST ANTICIPATED WATERLINE
CRICKET TO ROOF DRAIN
04/11/19 PLAN REVIEW COMMENTS
SINGLE PLY ROOF MEMBRANE; EXTEND UNDER COPING OWNER
ROOF DECK PAVERS ON PEDESTAL SYSTEM
Mr. Harold Tang & Family DOOR FINISHING PER SECHEDULE SILL PAN FLASHING MEMBRANE ROOF CLASS B MIN. ROOF COVERING PER SFBC 1509.10 AND CBC 1505.1
1/2" PLATE STEEL GSM METAL COPING WITH CLEATS
CMSTC16 STRAP @ EACH DOUBLE STUD
ANCHOR BOLT W/ NEOPRENE WASHER, S.S.D WOOD FRAMING, S.S.D BUILDING TAPE AT JOINTS PROTECTIVE BOARD OVER R10 TAPER INSULTION
R-30 INSULATION
FIBER CEMENT SIDING R-21 BATT INSULATION WATER RESISTANT UNDERLAYMENT, PER SPECIFICATIONS 1 LAYER 5/8" TYPE 'X' EXT. GYP. SHEATHING
PSL, S.S.D
1/2" PLYWOOD BUILDING TAPE AT JOINTS BACKER ROD AND SEALANT UNDER DRIP METAL
1X6 WOOD DECKING 1/4" :12 MIN
FLOOR PER SCHEDULE
2X PARAPET FRAMING, S.S.D.
2X6 WOOD SLEEPERS
855 Folsom Street #330 San Francisco, CA 94107
1/2" PLYWOOD R38 NON-COMBUSTIBLE GLASS FIBER INSULATION 0.90 PCF IN JOIST SPACE; STAPLE TO PLY
SCALE AS NOTED DRAWN BY RG CHECKED BY
RIPPED 11 7/8" LVLS MIN. DEPTH 7 1/2" @ 16" C.C.
RG
WOOD FRAMING, S.S.D
PROJECT NO. 201209
RESILIENT CHANNEL @ 16" O.C.
DATE 4/29/19
DRIP FLASHING
SEALANT
SEALANT
R-19 INSULATION
DRAWING NO. 39 of 42
2 LAYERS 1/2" SHEETROCK BRAND FIRECODE C CORE GYPSUM PANELS
WINDOW
1370 Pacific Ave
DECK DETAILS DRAWING NO.
PARAPET @ DECK SCALE: 3" = 1'-0"
3
DECK DETAILS SCALE: 3" = 1'-0"
18
BALCONY TRANSITION S.S.D. SCALE: 3" = 1'-0"
5
A9.04
rg-architecture
1 1/2" CLR.
CONCRETE WALL; S.S.D.
6" MIN. TREAD DEPTH
1 HR ASSEMBLY
3'
3/8" DIAM X 2" HEX HEAD LAG SCREWS
C-29116
GYPSUM WALL BOARD; PTD. A
R38 NON-COMBUSTIBLE GLASS FIBER INSULATION 0.90 PCF IN JOIST SPACE; STAPLE TO PLY
E
T
3' CLEAR MIN.
RESILIENT CHANNEL @ 16" O.C. 2 LAYERS 1/2" SHEETROCK MIN. BRAND FIRECODE C CORE GYPSUM PANELS STANDARD CEILING ROOF
EXHAUST DUCT
EXHAUST DUCT THROUGH JOIST BAY RATED FLOOR ASSEMBLY SCALE: 3" = 1'-0"
HANDRAIL ANCHORAGE AT CONCRETE WALL SCALE: 3" = 1'-0"
16
WINDING STAIR DETAIL SCALE: 3" = 1'-0"
8
T E CM A
11 7/8" TJI FRAMING S.S.D.
E D A RCH NS D GHAN IT E A N Y
ST
6" MIN. TREAD DEPTH
STEEL HANDRAIL BRACKET @ 4'-0"O.C. MAX.; PAINTED.
A
T.O. PLYWD. ROOF
NI
14 GA X 2" STEEL CLOSURE STRIP
3/4" PLYWOOD SHEATHING; S.S.D.
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
1-1/2" O.D. STEEL HANDRAIL; PAINTED. WELD TO HANDRAIL BRACKET; S.S.D.
6-30-2019 RENEWAL DATE
OF
CA LI
R
WALL TYPE PER PLAN
LI RIC
NOTE: SEE ALSO AB-005 REGARDING ROOF DECK CONSTRUCTION
FO
4
1-1/2" O.D. STEEL HANDRAIL; PAINTED. WELD TO HANDRAIL BRACKET; S.S.D. STAIR CROSS SECTION SCALE: 1 1/2"= 1'-0"
19 1 1/2" CLR.
2 HR WALL ASSEMBLY; SEE PLANS FOR WALL TYPES GYPSUM WALL BOARD; PTD. STEEL HANDRAIL BRACKET @ 4'-0"O.C. MAX.; PAINTED. 3/8" DIAM X 3" HEX HEAD LAG SCREWS
2x8 BLOCKING
HANDRAIL ANCHORAGE AT TYPICAL STUD WALL SCALE: 3" = 1'-0"
3
REVISIONS NO. DATE
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
1/4" CERAMIC TILE (ALIGN W/ ADJACENT WOOD FIN. FLOOR)
1/4" PRE-ENGINEERED WOOD FLOORING PER FINISH SCHEDULE
3/8" LATEX PORTLAND CEMENT MORTAR BOND COAT ON WATERPROOF MEMBRANE
FINISH FLOOR PER SCHEDULE
3/4" GYPSUM CONCRETE UNDERLAYMENT
FINAL MORTAR BED WATERPROOFING MEMBRANE
1/8"TYP.
2 HR ASSEMBLY
9"
PRIMARY MORTAR BED
ISSUE 04/11/19 PLAN REVIEW COMMENTS
FINISHED FLOOR 2ND - 4TH STORY
OWNER Mr. Harold Tang & Family
3/4" PLYWOOD SHEATHING; S.S.D.
3 1/2" OR LVL OR PSL S.S.D
1370 Pacific Ave 855 Folsom Street #330 San Francisco, CA 94107
2 LAYERS 5/8" SHEETROCK MIN. BRAND FIRECODE C CORE GYPSUM PANELS 40MIN EACH (80MIN) PER TABLE 7.22.6.2(1)
1 1/4" TIMBERSTRAND RIM JOIST 2X OR TJI JOISTS @ 16" C.C., S.S.D
1 LAYERS 1/2" SHEETROCK BRAND FIRECODE C CORE GYPSUM PANELS 25 MIN PER TABLE 722.6.2(1) ELEVATOR SHAFT R-19 ACOUSTICAL INSULATION
SCALE AS NOTED DRAWN BY
2 HR ASSEMBLY
2 LAYERS 1/2" SHEETROCK BRAND FIRECODE C CORE GYPSUM PANELS 4x 5/8" TYPE X GYP. BD.
RG CHECKED BY W8x15, S.S.D.
RG
2 LAYERS 1/2" SHEETROCK BRAND FIRECODE C CORE GYPSUM PANELS
PROJECT NO. 201209 DATE
RESILIENT CHANNEL @ 16" O.C.
4/29/19 DRAWING NO. 40 of 42
R38 NON-COMBUSTIBLE FIBERGLASS INSULATION 0.90 PCF IN JOIST SPACE; STAPLE TO PLY
INTERIOR DETAILS DRAWING NO.
2 HR RATED WALL /FLOOR INTERSECTION SCALE: 3" = 1'-0"
17
SHOWER W/ CENTER DRAIN SCALE: 3" = 1'-0"
1
A9.05
rg-architecture WALL PER PLANS
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
1 1/2" x 1/2" PAINT GRADE CASING, TYP.
DWELLING UNIT SIDE
1/4"
LI RIC
NI
A RENEWAL DATE
OF
CA LI
R
6-30-2019
FO
4
WALL PER PLANS HEADER S.S.D.
DOOR FRAME ANCHOR
SHIM AT ANCHOR AS REQ'D.
HOLLOW CORE METAL FRAME HOLLOW CORE METAL DOOR
EXPANSION ANCHOR
1 1/2" x 1/2" PAINT GRADE CASING, TYP.
WOOD DOOR FRAME
1/4"
CORRIDOR SIDE ALIGN
FIRE-RESISTANT CAULKING
NON-RATED WOOD DOOR JAMB SCALE: 3" = 1'-0" 9''
6''
E
T
CONCRETE HEADER PER PLANS, S.S.D.
3''
A
DOOR PANEL PER SCHEDULE
0
T E CM A
C-29116 ST
WOOD DOOR FRAME HINGE
E D A RCH NS D GHAN IT E A N Y
DOOR PANEL PER SCHEDULE
THRESHOLD; SEE ADA DETAIL #DrgID #LayID
0
3''
RATED DOOR HEAD IN TYPE 1 CONST. - CONC. SCALE: 3" = 1'-0" 6'' 9''
7
0
3''
6''
NON-RATED WOOD DOOR HEAD SCALE: 3" = 1'-0" 9''
3
REVISIONS NO. DATE
ISSUE
08/12/14 ORIGINAL SITE PERMIT 11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
WALL PER PLANS WALL PER PLANS HEADER S.S.D. HEADER S.S.D. ISSUE
1 1/2" x 1/2" PAINT GRADE CASING, TYP.
DOOR FRAME ANCHOR
1/4"
WOOD DOOR FRAME
PROPRIETARY FRAMING INCLUDED WITH POCKET DOOR HARDWARE
3''
OWNER Mr. Harold Tang & Family
HOLLOW CORE METAL DOOR
DOOR PANELS PER SCHEDULE
0
04/11/19 PLAN REVIEW COMMENTS
HOLLOW CORE METAL FRAME
6''
9''
SLIDING DOOR HEAD SCALE: 3" = 1'-0"
6
0
3''
6''
RATED STEEL FRAME DOOR JAMB SCALE: 3" = 1'-0" 9''
2
855 Folsom Street #330 San Francisco, CA 94107
SEE DOOR SCHEDULE
SCALE
3 1/2"
WALL PER PLANS WALL PER PLANS
AS NOTED
HEADER S.S.D.
DRAWN BY
HOLLOW CORE METAL FRAME
RG
RG CHECKED BY
3 7/16" VIEW A-A
PROJECT NO.
1 1/2" x 1/2" PAINT GRADE CASING, TYP.
DOOR FRAME ANCHOR
201209 DATE
HOLLOW CORE METAL DOOR
DRAWING NO. 41 of 42
DOOR DETAILS
THRESHOLD
DOOR PANEL PER SCHEDULE
6"
4/29/19
1/4"
WOOD DOOR FRAME
2X4 STUD CUT TO 6"
1370 Pacific Ave
DRAWING NO.
ADA COMPLIANT POCKET DOOR HEADER BEAM AT STOREFRONT DOOR SCALE: 3" = 1'-0"
13
NOT TO SCALE
9
0
3''
6''
9''
SLIDING DOOR JAMB SCALE: 3" = 1'-0"
5
0
3''
RATED STEEL FRAME DOOR HEAD/THRESHOLD SCALE: 3" = 1'-0" 6'' 9''
1
A9.06
rg-architecture WALL ASSEMBLY. USG SHEETROCK® BRAND FIRECODE® X PANELS. USG SHEETROCK® BRAND FIRECODE® COMPOUND, 1" [25] MIN. THICKNESS.
PENETRANT
A
T
=
1'-0"
19
E
CH-STUD
6-30-2019 RENEWAL DATE
OF
CA LI
FO
PLAN
SECTION F-RATING 2-HR/T-RATING 0-HR SYSTEM NO. W-L-1063
SYSTEM NO. W-L-3034 SCALE: 3"
LI RIC ST
PLAN
F-RATING 1-HR/T-RATING 0-HR & 1-HR PIPE PENETRATION THROUGH HORIZONTAL SHAFT WALL
C-29116
SEC A-A
SEC 2
SECTION
SECTION
PIPE COVERING AND THROUGH PENETRATION
MINERAL WOOL BATT INSULATION.
CUT LINER PANEL TO FIT AROUND PENETRANT WITH 1/2" NOM. ANNULAR SPACE
E D A RCH NS D GHAN IT E A N Y
T E CM A
PIPE COVERING AND THROUGH PENETRATION.
J-RUNNER
SEC 1
A
USG SHEETROCK® BRAND FIRECODE® COMPOUND, 1/2" [12] MIN. THICKNESS.
FIRECODE COMPOUND
SEC A-A
NI
USG SHEETROCK® BRAND FIRECODE® X PANELS.
428 SOUTH VAN NESS AVE. SAN FRANCISCO, CA 94103 415.649.6202 mail@rg-architecture.com
R
WALL ASSEMBLY.
THERMA FIBER INSULATION IN CAVITY
ELECTRICAL PIPE PENETRATION THROUGH 1-HR WALL SCALE: 3"
=
15
1'-0"
METALLIC PIPE PENETRATION THROUGH 2-HR WALL SCALE: 3"
=
11
1'-0"
J-RUNNER
ELEVATION WALL ASSEMBLY.
WALL ASSEMBLY.
SHAFT WALL - DUCT PENETRATION
WALL ASSEMBLY.
SCALE: 3"
USG SHEETROCK® BRAND FIRECODE® X PANELS.
USG SHEETROCK® BRAND FIRECODE® X PANELS.
USG SHEETROCK® BRAND FIRECODE® X PANELS.
USG SHEETROCK® BRAND FIRECODE® COMPOUND, 1" [25] MIN. THICKNESS.
USG SHEETROCK® BRAND FIRECODE® COMPOUND, 1" [25] MIN. THICKNESS.
USG SHEETROCK® BRAND FIRECODE® COMPOUND, 1/2" [12] MIN. THICKNESS.
PIPE COVERING AND THROUGH PENETRATION
AIR DUCT ENCLOSURE. MINERAL WOOL.
PIPE COVERING AND THROUGH PENETRATION
MINERAL WOOL
PLAN SECTION
SECTION
PLAN
AIR DUCTS PENETRATION THROUGH 2-HR WALL SCALE: 3"
=
1'-0"
18
BATT INSULATION
ELECTRICAL PIPE PENETRATION THROUGH 1 & 2-HR WALL SCALE: 3"
=
1'-0"
14
SLEEVE
SECTION 1
1/4" TO 1/2"
FULL HEIGHT E-STUD INFILL E-STUD
SECTION A-A
SCALE: 3"
J-RUNNER
PLAN
METALLIC PIPE PENETRATION THROUGH 1-HR WALL =
1'-0"
10
7
1/4" TO 1/2"
SHEETROCK ACOUSTICAL SEALANT AS NECESSARY FOR SMOKE SEAL
F-RATING 1-HR/T-RATING 0-HR & 1-HR. SYSTEM NO. W-L-1039
F-RATING 1 & 2-HR/ T-RATING 0 & 1 HR SYSTEM NO. W-L-3023
F-RATING 2-HR SYSTEM NO. W-L-7002
SECTION
SLEEVE
1'-0"
FULL HEIGHT E-STUD
SHEETROCK ACOUSTICAL SEALANT AS NECESSARY FOR SMOKE SEAL SLEEVE 1 1/2" X 1 1/2" X 16 GA ANGLE
=
REVISIONS NO. DATE
SECTION 2
FRAMED COLUMN SECTION SCALE: 3"
=
1'-0"
ISSUE
08/12/14 ORIGINAL SITE PERMIT
7
11/01/18 ADDENDUM 2 R1 04/11/19 PLAN REVIEW COMMENTS
WALL ASSEMBLY.
WALL ASSEMBLY.
USG SHEETROCK® BRAND FIRECODE® X PANELS.
USG SHEETROCK® BRAND FIRECODE® X PANELS. USG SHEETROCK® BRAND FIRECODE® COMPOUND, 1/2" [12] MIN. THICKNESS.
USG SHEETROCK® BRAND FIRECODE® COMPOUND, 1" [25] MIN. THICKNESS.
ISSUE 04/11/19 PLAN REVIEW COMMENTS
PIPE COVERING AND THROUGH PENETRATION AIR DUCT ENCLOSURE MINERAL WOOL BATT INSULATION.
SECTION
OWNER
MINERAL WOOL
Mr. Harold Tang & Family
PLAN SECTION
PLAN
1370 Pacific Ave
F-RATING 2-HR/T-RATING 2-HR. SYSTEM NO. W-L-1065
F-RATING 1-HR/T-RATING 0-HR SYSTEM NO. W-L-7001 AIR DUCTS PENETRATION THROUGH 1-HR WALL SCALE: 3"
=
1'-0"
17
GROUPED CONDUITS PENETRATION THROUGH 2-HR WALL SCALE: 3"
=
1'-0"
13
855 Folsom Street #330 San Francisco, CA 94107
SCALE AS NOTED DRAWN BY RG CHECKED BY
USG SHEETROCK® BRAND FIRECODE® COMPOUND.
RG PROJECT NO. 201209
PIPE COVERING AND THROUGH PENETRATION
DATE 4/29/19 DRAWING NO. 42 of 42
ASSEMBLY PENETRATION PROTECTIVES DRAWING NO.
PLAN
SECTION F-RATING 2-HR/ T-RATING 3/4-HR SYSTEM NO. W-L-5044
INSULATED PIPE PENETRATION THROUGH 2-HR WALL SCALE: 3"
=
1'-0"
27
A9.07