INTERNSHIP PORTFOLIO JUNE 2020 - PRESENT
VINCENT TIBURCIO
INDEX
SHEETS A2.1.1 - A2.2.4C - Set up sheets for the overall and area plans. - Revised dimensions for space adjustments A7.1.1 - A7.1.2 - Adjusted dimensions, walls, and provided design strategies for development of restrooms A7.1.3 - A7.1.5 - Provided detail drawings for tiered classroom - Designed alcove below staircase (in development) A8.1.1 - A8.2.1 - Provided curtain wall framing interior elevations. A9.9.1 - A9.9.2 - Modeled interior & exterior spaces using sketchup - Provided renderings for design development phases
GENERAL SHEET NOTES
H H.3
H.5
J
J.1
J.3
K
A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
FOR BASIC LIFE SAFETY AND CODE INFORMATION APPLYING TO THIS PROJECT, REFER TO THE G2.X SERIES SHEETS LOCATED PER THE PROJECT SHEET INDEX.
C.
REFER TO THE A3.X SERIES SHEETS FOR THE REFLECTED CEILING PLANS.
D.
REFER TO THE A9.2.X SERIES SHEETS FOR PARTITION SYSTEMS TYPES AND DETAILS. UNLESS OTHERWISE INDICATED, ALL WALLS SHALL BE P0A3. ALL WALLS OF OFFICES, CLASSROOMS, TEACHING SPACES, LABS, EXAM ROOMS, AND CONFERENCE/DEBRIEF ROOMS TO BE INSULATED AND ACOUSTICALLY SEALED. ALL J-BOXES AND OTHER SERVICE BOXES SHALL BE OFFSET NO LESS THAN 0' - 6".
CC 21 10' - 3" 1' - 5"
19' - 3 1/8"
2' - 4 1/2"
6' - 5 1/2"
21
7' - 9 1/8" 10' - 6 1/8"
1S4
1.9
1 18' - 10"
3' - 11 1/4"
1
1.9
130 131C
131B
2
3' - 0"
131A
0° .00 82
2
131F
131E
41' - 0"
131H
131D
3 128
8
118
32' - 8 3/8"
2' - 11 1/2"
1' - 6"
5.5
1C1
117
108K
A4.1.4
1E1
105A
108B
40
31
105
108
119 108D
108H
108G
108F
102
108E
104
165' - 4"
FEC
243' - 6 1/2"
240' - 2 5/8"
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
10
10.000°
01/29/2021
0° .50 7 7
52' - 4 1 /4"
1 / A2.2.1A 1 / A2.2.1B 3' - 11 3/8"
32
4' - 0"
KEYPLAN
NORTH
0° .00 7 7
12' - 3 1/2"
303' - 5 1/8"
41
° 00 0.0 10
1' - 11 3/8"
JAMES C. MENEFEE 20610
101
FEC
25' - 10 1/4"
30' - 11"
104A
108J
19 MAR 2021 29 JAN 2021 20 NOV 2020 23 OCT 2020 31 JULY 2020
SEALS AND SIGNATURES
9
42' - 1 1 /8"
0° .00 80
9
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS EARLY RELEASE PACKAGE NO. 1 100 PCT DESIGN DEVELOPMENT SCHEMATIC DESIGN
8
13' - 1"
48' - 4"
12.500°
41
108L
0° 33.00
1S1
108C
71' - 0 1/2"
22' - 10 1/4"
FEC
108M
DATE
7 19' - 0"
113
REV
6
10.000°
108A
108L
ISSUED FOR
12' - 0"
1C1B
112
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
5
FEC
115
AV-IT-SECURITY
26' - 8" 259' - 1 1/8"
121
34' - 9 3/4"
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
4.8
2' - 11 1/8"
2' - 7 3/4"
29.50 3°
A4.1.4
106
FEC
FEC
1 / A2.2.1C 1 / A2.2.1B
123
FEC
1C2
116
123C
FEC
1 / A2.2.1A 1 / A2.2.1B
4 3/8"
1E2
125
122
1C1A 9' - 8 1/8"
60' - 3"
1S2
85' - 6 1/8"
7
1E3
72
1C1AA
1C1C
123D
1C3A
21.500°
FEC
20' - 8"
109AA
6
1 / A2.2.1C 1 / A2.2.1B
12.000°
106A
107
5.7
123A
170' - 5 1/2"
109
114
120
133A
123B
2' - 0 1/2" 4"
5
126
REFER TO A5.1.X FOR BASEMENT WATERPROOFING INFORMATION.
SMITHGROUP
DATACOM DESIGN GROUP
4
133C
1S3
138' - 4 3/4"
REFER TO AND COORDINATE WITH CIVIL, STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL, AND COMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DRAWING.
3.8
9' - 7"
G
I.
15' - 2"
F
REFER TO THE 'AI' SERIES SHEETS FOR INTERIOR FURNISHING INFORMATION.
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
14' - 1"
E
3' - 11 3/8"
D
133
FEC
C
132B
7' - 11 1/2"
B
BB
H.
JQ ENGINEERING
10' - 8"
127
A.2
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
132
1C3
3.9 A A.1
G.
PACHEKO KOCH
24' - 4"
150' - 1"
3
4
REFER TO THE A9.3.X SERIES SHEETS FOR THE INTERIOR OPENING SCHEDULE(S), TYPES, AND DETAILS.
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
129
2
F.
501 W. MITCHELL ARLINGTON, TX 76010
TURNER
FEC
3.8
ALL COLUMNS TO BE EXPOSED UNLESS OTHERWISE NOTED. REF SPECS FOR EXPOSED CONCRETE FINISH INFORMATION.
J.
131
131G
A4.1.1
E.
15' - 10"
ACADEMIC BUILDING FOR SSW & CoNHI
33
1 A4.1.1
11.500° 7' - 5"
32' - 8"
23' - 4"
33' - 0"
34' - 0"
34' - 0"
34' - 0"
24' - 11"
7' - 1"
15' - 9 1/2"
11' - 4"
4' - 1 1/2"
5' - 8"
26' - 6"
2' - 1"
4' - 2"
51
Author
4' - 7"
10' - 4"
4/7/2021 10:47:38 AM
SHEET TITLE
BB
A
A.1
A.2
B
C
D
E
F
G
CC
G.4
G.5
G.6
H
H.3
H.4
H.6
J
J.9
K
FLOOR PLAN - LEVEL 1 OVERALL
Plot Date:
12287.000
1
LEVEL 01
SCALE: 1/16" = 1'-0"
PROJECT NUMBER
CD
SHEET NUMBER
A2.2.1
GENERAL SHEET NOTES
A
A.1 A.2
B
BB
C
D
E
F
G
A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
FOR BASIC LIFE SAFETY AND CODE INFORMATION APPLYING TO THIS PROJECT, REFER TO THE G2.X SERIES SHEETS LOCATED PER THE PROJECT SHEET INDEX.
C.
REFER TO THE A3.X SERIES SHEETS FOR THE REFLECTED CEILING PLANS.
D.
REFER TO THE A9.2.X SERIES SHEETS FOR PARTITION SYSTEMS TYPES AND DETAILS. UNLESS OTHERWISE INDICATED, ALL WALLS SHALL BE P0A3. ALL WALLS OF OFFICES, CLASSROOMS, TEACHING SPACES, LABS, EXAM ROOMS, AND CONFERENCE/DEBRIEF ROOMS TO BE INSULATED AND ACOUSTICALLY SEALED. ALL J-BOXES AND OTHER SERVICE BOXES SHALL BE OFFSET NO LESS THAN 0' - 6".
E.
ALL COLUMNS TO BE EXPOSED UNLESS OTHERWISE NOTED. REF SPECS FOR EXPOSED CONCRETE FINISH INFORMATION.
F.
REFER TO THE A9.3.X SERIES SHEETS FOR THE INTERIOR OPENING SCHEDULE(S), TYPES, AND DETAILS.
G.
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
H.
REFER TO THE 'AI' SERIES SHEETS FOR INTERIOR FURNISHING INFORMATION.
I.
REFER TO AND COORDINATE WITH CIVIL, STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL, AND COMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DRAWING.
REMOTE ANNUNCIATOR
13' - 2 3/4"
4' - 8"
8' - 8"
6' - 8"
4' - 0"
8' - 0"
4 A4.3.4 8' - 0"
14' - 0"
2' - 8"
21 A5.2.2
59
24 A9.6.2
120
HOISTWAY
DN
114
66 68
22
A7.2.4
CAFE SUPPORT
44
106A
HEALTH INFORMATICS LAB
A8.1.1
46
A7.2.4
13' - 1 1/8"
10' - 10 3/4"
6' - 2"
20' - 3 5/8"
107 28' - 1 3/8"
11' - 10 3/4"
5' - 5 3/4"
24 A7.1.1
HEALTH INFORMATICS CLASSROOM
109
7' - 7 3/4"
CUSTODIAL
8' - 11 7/8"
P0F2 P0F3
FEC
112B
113 113A
WOMEN 112
7
105A
ELEV 1
P0A3A
108B
105
108B 66
OFFICE P0A3A
108C
51 A7.2.3
A7.2.1
P0A3
108D 108AA
22 A9.6.4
OFFICE
RESEARCH & CENTERS SUITE 108
10' - 10 1/4"
108J
62
P0A3A
108H
108G
31' - 10"
OFFICE
P0A3A
104A
P0P2
7' - 4"
4' - 0"
JAMES C. MENEFEE 20610
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
60-SEAT CLASSROOM 21 A7.2.3
108E
01/29/2021 6' - 8"
6' - 8"
8' - 0"
104B 4' - 0"
7' - 4"
4' - 0"
KEYPLAN
FEC
4' - 0"
A8.1.1
104
GA WORKROOM
108F
14 APR 2021 19 MAR 2021 29 JAN 2021 23 OCT 2020 31 JULY 2020
SEALS AND SIGNATURES
STORAGE
3 A4.3.2
72
P0A3
10' - 8"
OFFICE
OFFICE
72 A5.2.2
9
A4.1.5
108D
108H
108J
10' - 0 1 /2"
P0A3A 10' - 6"
OFFICE
A8.1.1
2
ISSUE FOR CONSTRUCTION 95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT SCHEMATIC DESIGN
8' - 0"
NORTH
11' - 4" 16' - 8"
2
104A 7' - 4"
A4.1.6 2
2' - 8"
A4.3.2
FEC
70
DATE
8
5' - 11 5/8"
108C
A4.4.1
A8.1.2
REV
ISSUED FOR
60-SEAT CLASSROOM
108K
104
A4.1.5
1
4' - 10" 3' - 11 1/4" 4' - 10"
5' - 7"
119
2
119B
5' - 3 1/2"
108E
VESTIBULE
5' - 3 1/2"
1E1
108F
119A
11' - 10 1/8"
STRUCTURAL STOOP
4' - 10"
70
108L
27 A7.1.1
108L
5' - 11 3/8"
105C
A7.2.2
108A
P0A3A
RESEARCH ACTIVITIES
P0A6A
4' - 10"
FEC
70
A8.1.1
70 A9.6.2
25' - 7 3/8"
FEC
18 A4.4.1
6
FEC
OFFICE
112D
108G
A4.3.3
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
1C1A
10' - 7 1/8"
67
108A
112C
113B
AV-IT-SECURITY
RECESSED AED CABINET (OFCI)
HUDDLE
BREAKROOM
117
P0F3
VENDING
1C1A
107B 35
54
MDF
116
108L
A7.2.2
112A
MEN
ELEC.
11' - 2 5/8"
CONFERENCE ROOM
6' - 6"
116
72
6' - 5 1/2"
112
115
1C1AA
A8.1.1
A8.1.1
17' - 10 7/8"
5' - 11 3/8"
1
9
113
117 A7.2.2
8
1E2
27' - 2 3/4"
106
P0FH
69
1C1
115
1C2
ELEV 2
1C1B
DATACOM DESIGN GROUP
CAFE
FEC
6' - 1 5/8"
15' - 7 1/2"
105B
1C1C 9' - 7 1/4"
CORRIDOR
108BB
9' - 1 1/2"
10' - 8 1/8"
118
70 A7.2.9
108K
10' - 2 1/2"
32 A6.3.1
CORRIDOR RESEARCH COMMONS
109B
TRASH / RECYCLING
7 11.500°
14 A9.9.1
109A
2 A4.3.3
109AA
7' - 7 1/2"
6
P0L3
1S2A
1' - 7 3/8"
1S2
105AA
STAIR 2
107A
32 A6.1.2
GENDER NEUTRAL RESTROOM
PACHEKO KOCH
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
ELEVATOR MACHINE ROOM
109AA
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
JQ ENGINEERING
8' - 3"
12.000°
10' - 0 1/8"
SERVER / STORAGE
5.7
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
P0A3A
P0A3A
120B
24 A9.3.3
SIM
5
106
14' - 0 1/4"
A5.1.3
SMITHGROUP
1' - 4 1/4"
VESTIBULE
REFER TO A5.1.X FOR BASEMENT WATERPROOFING INFORMATION.
501 W. MITCHELL ARLINGTON, TX 76010
TURNER
4' - 0"
FEC
5
8' - 1"
3 A4.3.4
114
120A
45 A5.2.2
69 A5.2.2
1S2B
A4.3.4
2 A4.3.4
1C1AA
1
KNOXBOX
1 / A2.2.1B
J.
ACADEMIC BUILDING FOR SSW & CoNHI
12' - 0" 9' - 4"
4' - 8"
48 A5.2.2 12' - 0"
4' - 0"
67 A5.2.1
41
9' - 4"
A
1
Author
1 / A2.2.1B
A4.3.2
SHEET TITLE
FLOOR PLAN - LEVEL 1 AREA A
3
4/7/2021 10:47:45 AM
A4.3.1
Plot Date:
BB 1
LEVEL 1 - FLOOR PLAN AREA A SCALE: 1/8" = 1'-0"
A
A.1
A.2
B
C
D
E
F
G
12287.000 PROJECT NUMBER
CD
SHEET NUMBER
A2.2.1A
GENERAL SHEET NOTES G
G.4
G.5 G.6
H.3
CC
J
K
1
A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
FOR BASIC LIFE SAFETY AND CODE INFORMATION APPLYING TO THIS PROJECT, REFER TO THE G2.X SERIES SHEETS LOCATED PER THE PROJECT SHEET INDEX.
C.
REFER TO THE A3.X SERIES SHEETS FOR THE REFLECTED CEILING PLANS.
D.
REFER TO THE A9.2.X SERIES SHEETS FOR PARTITION SYSTEMS TYPES AND DETAILS. UNLESS OTHERWISE INDICATED, ALL WALLS SHALL BE P0A3.
A4.1.5 1 A4.1.6
ALL WALLS OF OFFICES, CLASSROOMS, TEACHING SPACES, LABS, EXAM ROOMS, AND CONFERENCE/DEBRIEF ROOMS TO BE INSULATED AND ACOUSTICALLY SEALED. ALL J-BOXES AND OTHER SERVICE BOXES SHALL BE OFFSET NO LESS THAN 0' - 6".
BEDROOM
MDF
123C
125
125
11' - 9 3/8"
P0A3A
11' - 10 1/2"
12' - 6 3/8"
123AA
P0B3
123C 14' - 0 1/4"
E.
ALL COLUMNS TO BE EXPOSED UNLESS OTHERWISE NOTED. REF SPECS FOR EXPOSED CONCRETE FINISH INFORMATION.
F.
REFER TO THE A9.3.X SERIES SHEETS FOR THE INTERIOR OPENING SCHEDULE(S), TYPES, AND DETAILS.
G.
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
H.
REFER TO THE 'AI' SERIES SHEETS FOR INTERIOR FURNISHING INFORMATION.
I.
REFER TO AND COORDINATE WITH CIVIL, STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL, AND COMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DRAWING.
1 / A2.2.1C
4.8
42
11' - 4 5/8"
FEC
1E3
1' - 1 1/2"
1 / A2.2.1C
1 / A2.2.1A
4.8
ELEV 3
1C3A
123A
TRASH / RECYCLING
A8.1.2
COMMUNITY COMMONS 122
5
5
1 A9.6.3
J.
5.5
4
121B
72
A4.3.7
18 A4.4.1
121A
SMITHGROUP
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
5.5
121
31
501 W. MITCHELL ARLINGTON, TX 76010
TURNER
VESTIBULE
A4.1.4
REFER TO A5.1.X FOR BASEMENT WATERPROOFING INFORMATION.
ACADEMIC BUILDING FOR SSW & CoNHI
PACHEKO KOCH
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
STRUCTURAL STOOP
6
6
JQ ENGINEERING
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
DATACOM DESIGN GROUP AV-IT-SECURITY
7
7
72
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
A6.1.1
ELEV 1 1E1
A4.1.4
FEC
40
31
21' - 8"
32
19 A9.6.2
24 A6.1.1
STAIR 1
SHEET KEYNOTES
1S1
2
2
A4.1.5
A4.1.5
COMMUNITY COMMONS
9
STRUCTURAL STOOP
101B
VESTIBULE 101
101A
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT SCHEMATIC DESIGN
33
19 MAR 2021 29 JAN 2021 23 OCT 2020 31 JULY 2020
SEALS AND SIGNATURES
1
"
102
DATE
KNOXBOX (EXTERIOR) REMOTE ANNUNCIATOR (INTERIOR)
18 A4.4.1
11' - 10 1/8
9
REV
ISSUED FOR
32
A4.3.8
JAMES C. MENEFEE 20610
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION 24' - 8"
41
01/29/2021
1
0° .50 7 7
67 A5.2.1
A4.1.6
KEYPLAN
NORTH
1 / A2.2.1A
43 A5.2.1
41 2
33
Author
A4.3.1
1
2
A4.3.1
4/7/2021 10:47:51 AM
B
A4.3.8
1
SHEET TITLE
FLOOR PLAN - LEVEL 1 AREA B
1 A4.1.5
A4.1.1
12287.000 Plot Date:
G 1
CC
LEVEL 1 - FLOOR PLAN AREA B SCALE: 1/8" = 1'-0"
G.4
G.5
G.6
H
H.3
H.4
H.6
J.9
K
PROJECT NUMBER
CD
SHEET NUMBER
A2.2.1B
GENERAL SHEET NOTES A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
FOR BASIC LIFE SAFETY AND CODE INFORMATION APPLYING TO THIS PROJECT, REFER TO THE G2.X SERIES SHEETS LOCATED PER THE PROJECT SHEET INDEX.
C.
REFER TO THE A3.X SERIES SHEETS FOR THE REFLECTED CEILING PLANS.
D.
REFER TO THE A9.2.X SERIES SHEETS FOR PARTITION SYSTEMS TYPES AND DETAILS. UNLESS OTHERWISE INDICATED, ALL WALLS SHALL BE P0A3. ALL WALLS OF OFFICES, CLASSROOMS, TEACHING SPACES, LABS, EXAM ROOMS, AND CONFERENCE/DEBRIEF ROOMS TO BE INSULATED AND ACOUSTICALLY SEALED. ALL J-BOXES AND OTHER SERVICE BOXES SHALL BE OFFSET NO LESS THAN 0' - 6".
E.
ALL COLUMNS TO BE EXPOSED UNLESS OTHERWISE NOTED. REF SPECS FOR EXPOSED CONCRETE FINISH INFORMATION.
F.
REFER TO THE A9.3.X SERIES SHEETS FOR THE INTERIOR OPENING SCHEDULE(S), TYPES, AND DETAILS.
G.
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
H.
REFER TO THE 'AI' SERIES SHEETS FOR INTERIOR FURNISHING INFORMATION.
I.
REFER TO AND COORDINATE WITH CIVIL, STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL, AND COMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DRAWING.
J.
H
CC
H.3
H.5
J
J.1
J.3
2
3
A4.3.6
A4.3.6
21
1
32 A6.1.4
JQ ENGINEERING
1S4A
130A
9' - 7 3/8"
8' - 10 1/2"
COUNSELING
COUNSELING
COUNSELING
131F
131E
131D
P0F3A
P0A3A
22
A8.1.2
4' - 8"
COLLABORATION
9' - 8 3/4"
8' - 8"
129
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT
2' - 1 1/4"
15' - 5 1/4"
A8.1.2
9' - 8 5/8"
P0A3A
132A
A7.2.4
3
4' - 8 5/8"
2' - 8"
A7.2.4 45
SIMULATION THEATER
6' - 0"
JAMES C. MENEFEE 20610
A4.3.7
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
CORRIDOR
A434
2' - 8"
P0A3A
6' - 0"
128E
128D
128B
128A
5' - 4"
128C
WOMEN 24 A7.1.2
1C3 "
3
Author
123A
2' - 0 3/4" 1' - 4 1/2"
ELEV 3 1E3
BEDROOM
MDF
123C
125
1 / A2.2.1B
123AA
P0A3A
123C
16 A6.1.3
5' - 1 1/4" 1' - 1 1/4"
5' - 4"
KEYPLAN
4 P0A3A
P0A3A
C
72
22
P0B3
A7.2.4 5' - 10"
HOME HEALTH 123
DEBRIEF 123D
SHEET TITLE 1 / A2.2.1B
4.8
FLOOR PLAN - LEVEL 1 AREA C
1 A4.1.5
CC
G.6
H
H.3
J
K
12287.000 PROJECT NUMBER
Plot Date:
NORTH
A7.2.4
9' - 4"
123A
4/7/2021 10:48:00 AM
KITCHEN
3' - 0"
1S3
1C3A
4.8
123B
UP
TRASH / RECYCLING
123D
BATHROOM
1S3
CONTROL 133C
70
STAIR 3
70 A7.2.9
133B
P0A6A
132B
123B
126
CORRIDOR
133A
126
133C
133E
ELEC
6' - 7 5/8"
ELEV MACHINE ROOM
P0A6A
CONTROL
6' - 10 3/4"
133A
3.8
EJ
1' - 1 1/2"
4
A7.2.4
01/29/2021
4' - 8"
FEC
133
56
SIM
8 5/8"
STORAGE
133B
127
8' - 10"
MEN 32 A5.2.2
32 A5.2.2
P0A3A
132C
127C
127B
3.9
133D
127A
132B
A4.3.7
C
11' - 1 17/3 2
3.8
19 MAR 2021 29 JAN 2021 23 OCT 2020
SEALS AND SIGNATURES
2
132
128
DATE
6' - 0"
5' - 4"
FEC
3' - 4 3/8"
4
REV
P0A3A
7' - 4"
20
ISSUED FOR
11' - 4 1/4"
131G
2 3/8"
2
2' - 8"
2' - 8"
COUNSELING
131
131H 131E
9' - 4"
SSW COUNSELING
19 A5.2.1
CORRIDOR
131F
18 A9.6.4
A8.1.2
122200.A00 CURTAINS AND DRAPES
131D
40
P0A3A
5' - 7 3/4"
20
32
131H
131
131C
5' - 4"
131B
GROUP ROOM
1.9
131C
131A
131B
COUNSELING 131A
COUNSELING
8' - 10 3/4"
P0A3A
8' - 0" 2' - 8" 4' - 0"
A4.3.7
1S4B
P0A3A
3
1
4' - 8" 6' - 5 1/2"
67 A5.2.2
130B
4' - 4 3/8"
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
131G
14' - 5 7/8 "
AV-IT-SECURITY
1S4
A8.1.2
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
DATACOM DESIGN GROUP
STAIR 4
REMOTE ANNUNCIATOR
2
19 A5.2.2
35 A5.2.2
51 A5.2.2
1.9
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
1
KNOX BOX
130
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
PACHEKO KOCH
A4.3.6
VESTIBULE
SMITHGROUP
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
1
21
501 W. MITCHELL ARLINGTON, TX 76010
TURNER
K
A4.1.5
1
REFER TO A5.1.X FOR BASEMENT WATERPROOFING INFORMATION.
ACADEMIC BUILDING FOR SSW & CoNHI
1
LEVEL 1 - FLOOR PLAN AREA C SCALE: 1/8" = 1'-0"
CD
SHEET NUMBER
A2.2.1C
GENERAL SHEET NOTES A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
FOR BASIC LIFE SAFETY AND CODE INFORMATION APPLYING TO THIS PROJECT, REFER TO THE G2.X SERIES SHEETS LOCATED PER THE PROJECT SHEET INDEX.
C.
REFER TO THE A3.X SERIES SHEETS FOR THE REFLECTED CEILING PLANS.
D.
REFER TO THE A9.2.X SERIES SHEETS FOR PARTITION SYSTEMS TYPES AND DETAILS. UNLESS OTHERWISE INDICATED, ALL WALLS SHALL BE P0A3. ALL WALLS OF OFFICES, CLASSROOMS, TEACHING SPACES, LABS, EXAM ROOMS, AND CONFERENCE/DEBRIEF ROOMS TO BE INSULATED AND ACOUSTICALLY SEALED. ALL J-BOXES AND OTHER SERVICE BOXES SHALL BE OFFSET NO LESS THAN 0' - 6".
CC
H.3
H.5
J
J.1
J.3
73' - 8" 22' - 7" 19' - 7 3/4"
K
18' - 7"
10' - 8"
19' - 3 1/8"
21
5' - 10 5/8"
E.
ALL COLUMNS TO BE EXPOSED UNLESS OTHERWISE NOTED. REF SPECS FOR EXPOSED CONCRETE FINISH INFORMATION.
F.
REFER TO THE A9.3.X SERIES SHEETS FOR THE INTERIOR OPENING SCHEDULE(S), TYPES, AND DETAILS.
G.
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
H.
REFER TO THE 'AI' SERIES SHEETS FOR INTERIOR FURNISHING INFORMATION.
I.
REFER TO AND COORDINATE WITH CIVIL, STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL, AND COMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DRAWING.
3' - 0"
3' - 11 1/4"
1
A7.2.4
14' - 5"
2S4
6' - 8 3/4"
10' - 4" 1' - 5"
1
232
1.9 2
231
J.
REFER TO A5.1.X FOR BASEMENT WATERPROOFING INFORMATION.
ACADEMIC BUILDING FOR SSW & CoNHI 501 W. MITCHELL ARLINGTON, TX 76010
SMITHGROUP
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
TURNER
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
PACHEKO KOCH
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
228
229
2C2C
230
10' - 1 3/8"
JQ ENGINEERING
65' - 4"
FEC
3 223 227
4' - 9"
212
22
1' - 11 1/2"
- 9" 47'
11' - 0"
11' - 0"
71 11' - 0 1/8"
214 203JJ
203K
203G
203L
203N
203O
203Q
203S
203R
2E1
FEC
211
87.000 °
210
22' - 10 1/4"
204
204H
204J
204K
204L
203J
203M
203P
203U
LOWEST POINT OF EXTERIOR SOFFIT EXTERIOR WALL SLOPES DOWNWARD SOFFIT AT THIS POSITION
" 1/4
2S1 203H
A4.1.4
40
215
216
203D
203C
204D
204C
204B
FEC
203X
204A
17' - 6 1 /4"
204E
2C2
19 MAR 2021 29 JAN 2021 23 OCT 2020 31 JULY 2020
SEALS AND SIGNATURES
JAMES C. MENEFEE 20610
9 32
01/29/2021
10
KEYPLAN
NORTH
1 / A2.2.2A 1 / A2.2.2B
2"
24' - 6 1 /8"
2C2A
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT SCHEMATIC DESIGN
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
203A
203B
203 204F
31 8
203V
FEC
204G
7
203F 203E
DATE
6
A4.1.4
'-7 48
4 3/8"
11' - 0"
REV
2C2B
205
FEC
FEC
85' - 6 1/8"
5' - 3 1/4"
2E2
11' - 0"
ISSUED FOR
5.5
1/2"
10' - 11 3/4" 10' - 11 3/4"
2C1A
2C3
4.8 5
A4.1.4
FEC
217
221
5 23' -
208AA
2C4
41' - 11 1/4"
207AA
1 / A2.2.2C 1 / A2.2.2B
10 7/8"
5.7
38
224
219 0° 3. 10
2E3
25' - 2 3/4"
207
208
FEC
2' - 6"
209
42' - 8 1/8"
1 / A2.2.2A 1 / A2.2.2B
41' - 10"
20' - 8"
213
2S3
° 25.000
206
2S2
7' - 9 7/8"
69
1 / A2.2.2C 1 / A2.2.2B
10' - 2"
2' - 0 1/2"
5
48' - 9"
A4.1.4
4
220
A4.1.4
97' - 11 3/4"
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
9' - 4 7/8"
17' - 4 7/8 " 34
27' - 8 1/2"
3.8
222
3.9
12' - 8 3/8"
225
2C4A
2
DATACOM DESIGN GROUP AV-IT-SECURITY
168' - 6 3/8"
A4.1.1
5' - 11 3/8"
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
226
33 Author
41
4/7/2021 10:48:18 AM
51 7' - 5" 4' - 7"
BB
A
A.1
32' - 8"
A.2
23' - 4"
B
33' - 0"
C
34' - 0"
D
34' - 0"
E
34' - 0"
F
32' - 0"
G
CC
G.4
19' - 11"
G.5
G.6
11' - 4"
H
4' - 2"
H.3
16' - 0"
H.4
26' - 6"
H.6
J
2' - 1"
J.9
SHEET TITLE
FLOOR PLAN - LEVEL 2 OVERALL
K 12287.000
Plot Date:
PROJECT NUMBER
1
LEVEL 2
SCALE: 1/16" = 1'-0"
CD
SHEET NUMBER
A2.2.2
GENERAL SHEET NOTES A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
FOR BASIC LIFE SAFETY AND CODE INFORMATION APPLYING TO THIS PROJECT, REFER TO THE G2.X SERIES SHEETS LOCATED PER THE PROJECT SHEET INDEX.
C.
REFER TO THE A3.X SERIES SHEETS FOR THE REFLECTED CEILING PLANS.
D.
REFER TO THE A9.2.X SERIES SHEETS FOR PARTITION SYSTEMS TYPES AND DETAILS. UNLESS OTHERWISE INDICATED, ALL WALLS SHALL BE P0A3. ALL WALLS OF OFFICES, CLASSROOMS, TEACHING SPACES, LABS, EXAM ROOMS, AND CONFERENCE/DEBRIEF ROOMS TO BE INSULATED AND ACOUSTICALLY SEALED. ALL J-BOXES AND OTHER SERVICE BOXES SHALL BE OFFSET NO LESS THAN 0' - 6".
2
3
68 A7.2.6
A4.3.4
1 A4.3.4
21' - 3 3/4"
4' - 8"
8' - 8"
2' - 8"
6' - 8"
4' - 0"
8' - 0"
8' - 0" 2 EQ PANELS
14' - 0"
1 / A2.2.2B
A4.1.6
4 A4.3.4
E.
ALL COLUMNS TO BE EXPOSED UNLESS OTHERWISE NOTED. REF SPECS FOR EXPOSED CONCRETE FINISH INFORMATION.
F.
REFER TO THE A9.3.X SERIES SHEETS FOR THE INTERIOR OPENING SCHEDULE(S), TYPES, AND DETAILS.
G.
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
H.
REFER TO THE 'AI' SERIES SHEETS FOR INTERIOR FURNISHING INFORMATION.
I.
REFER TO AND COORDINATE WITH CIVIL, STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL, AND COMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DRAWING.
J.
REFER TO A5.1.X FOR BASEMENT WATERPROOFING INFORMATION.
4' - 0"
ACADEMIC BUILDING FOR SSW & CoNHI 501 W. MITCHELL ARLINGTON, TX 76010
SMITHGROUP
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
TURNER
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
5 CONFERENCE
72 A5.2.3
206
VIRTUAL REALITY 8' - 7 7/8"
49' - 5 3/4"
16' - 7"
VIRTUAL REALITY 209
NURSING AV PRODUCTION
SSW AV PRODUCTION
208
207
212
STUDY
207AA
10' - 11 3/4"
203F
10' - 9"
A7.2.6
204D
3' - 4"
7' - 4"
4' - 0"
6' - 8"
2
6' - 8"
207
9 1/4"
204B 11' - 1"
203H
203J
203M
203P
P0A3A
P0A3A
11' - 9"
10 1/2"
OFFICE
P0A3A
203U P0A3A
OFFICE
OFFICE
OFFICE
A4.1.6
203V
203E
203D
203C
203B
STAIR 1 2S1
62
40 A9.3.3
FEC
P0F3
8
A8.2.1
SIM
9
203
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT SCHEMATIC DESIGN
CORRIDOR
JAMES C. MENEFEE 20610
2C2 203
204A 11' - 6"
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
1' - 6 1/4"
ADVISING / ADMISSIONS & COMM OPEN OFICE 203X SIM
40 A9.3.3
EQ
FEC
1 A9.6.7
8' - 0"
01/29/2021
COLLABORATION EQ
11' - 4 3 EQ PA " NELS
19 MAR 2021 29 JAN 2021 23 OCT 2020 31 JULY 2020
SEALS AND SIGNATURES
P0A3A
OFFICE
DATE
SIM
48 A9.3.3
OFFICE
REV
FEC
9' - 6 3/4"
10.000°
4' - 0"
ISSUED FOR
P0A3A
CONFERENCE
OFFICE
P0A3A
7' - 4"
2E1
A6.1.1
ADVISING / ADMISSIONS & COMM SUITE
8"
4' - 0"
P0A3A
203A
P0A3A
8' - 0"
ELEV 1
203S
204O
203Q
11' - 0 1/8"
5' - 7"
OFFICE
11' - 1"
P0A3A
4' - 0"
OFFICE 204C
11' - 1"
204N
OFFICE
204A
P0A3A
OFFICE
11' - 0"
204B
204E 11' - 6"
48
204C
OFFICE
204D
204F 11' - 6"
204E
OFFICE
1' - 0 3/4"
A8.2.1
OFFICE 204G
OFFICE
203E
P0A3A
70 204G
A8.1.2
204F
A4.1.5
10' - 10 1/2"
OFFICE
P0A3A
53
10' - 10 1/2"
OFFICE
5' - 3 3/4"
2
10' - 10 1/2"
203D
SIM
WORK/STORAGE
204L
10' - 9"
204K
204
204K
10' - 9"
204J
204H 10' - 3 1/2"
204H
40 A9.3.3
204J
COLLAB.
OFFICE
204L
OFFICE
A4.3.3
OFFICE
11' - 0"
P0A3A
210E
OFFICE
11' - 0"
P0F3
10' - 10 3/4"
1
11' - 0"
203S
8' - 7"
10' - 11 3/4"
P0A3A
P0A3A
P0A3A
OFFICE
7
22' - 10"
211C
P0A3A
72
203U
210
215
216
203O
203R
21' - 1 1/8"
IDF
ELEC.
WOMEN
203N
OFFICE
203Q
2' - 1 3/4"
33' - 9 1/8" 210D
211B
203L
203A
6' - 6 1/8"
203K
OFFICE
203P
8' - 8 1/8"
203G
203B
5' - 10 1/2"
216
9' - 4 3/4"
OFFICE
203H
OPEN TO BELOW
1
210C
215
OFFICE
203M
211
OFFICE
203C
2C3
A8.2.1
210B
OFFICE
203L
MEN
OFFICE
204G
214
CORRIDOR
17' - 10 3/4"
2E2
1' - 0 3/4"
ELEV 2
42
32
CUSTODIAL
ALIGN
A6.2.2
210A
2C1
P0A3A
204K
211A
214
CORRIDOR
10' - 9 7 /8"
FEC
217
SIM
20 A7.1.2
203J
22 A6.3.1
70 A7.2.9
AV-IT-SECURITY
6
FEC
203F
2C1A
FEC
TRASH / RECYCLING
OPEN COLLABORATION
DATACOM DESIGN GROUP 300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
205
A8.2.1
2
5.7
A7.2.2
208AA
208
207A
207B
212
213
2S2
60
50
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
SHEET KEYNOTES
206
SOUND ISOLATION BOOTH
SOUND ISOLATION BOOTH
A4.3.3
A8.2.1
205
STAIR 2
A4.1.2
JQ ENGINEERING 30
STORAGE - SSW
UP
2S2
16' - 6 1/2"
203V
213
19' - 1 7/8"
11' - 1 3/4"
13' - 1 1/8"
1' - 10 1/2" 8' - 7"
48 A6.1.2 A8.1.1
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
A7.2.2
203R
22
66
209
STORAGE - CoNHI
PACHEKO KOCH
2C2A
EQ
KEYPLAN 16' - 8"
2' - 8"
7' - 4"
2 A4.3.2 3
12' - 0 3 EQ PA " NELS SIM
9' - 4"
12' - 0"
4' - 0"
41 9' - 4"
A
Author
1 / A2.2.2B
A4.3.4
4' - 8"
NORTH
SHEET TITLE
4/7/2021 10:48:27 AM
FLOOR PLAN - LEVEL 2 AREA A
BB
A
A.1 A.2
B
C
D
E
F
G
12287.000
Plot Date:
PROJECT NUMBER
1
LEVEL 2 - FLOOR PLAN AREA A SCALE: 1/8" = 1'-0"
CD
SHEET NUMBER
A2.2.2A
GENERAL SHEET NOTES G
G.6
H
H.3
1 / A2.2.2C
1 / A2.2.2A
J
J.9
K
224A
MDF CORRIDOR
A4.1.6
221
5' - 0"
5
38
B.
FOR BASIC LIFE SAFETY AND CODE INFORMATION APPLYING TO THIS PROJECT, REFER TO THE G2.X SERIES SHEETS LOCATED PER THE PROJECT SHEET INDEX.
C.
REFER TO THE A3.X SERIES SHEETS FOR THE REFLECTED CEILING PLANS.
D.
REFER TO THE A9.2.X SERIES SHEETS FOR PARTITION SYSTEMS TYPES AND DETAILS. UNLESS OTHERWISE INDICATED, ALL WALLS SHALL BE P0A3. ALL WALLS OF OFFICES, CLASSROOMS, TEACHING SPACES, LABS, EXAM ROOMS, AND CONFERENCE/DEBRIEF ROOMS TO BE INSULATED AND ACOUSTICALLY SEALED. ALL J-BOXES AND OTHER SERVICE BOXES SHALL BE OFFSET NO LESS THAN 0' - 6".
A7.1.4
60-SEAT CLASSROOM
1' - 2 7/8"
A4.1.4
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
4.8
35
2C4
72 A5.2.3
A.
1 / A2.2.2C
219 1 219
4.8
G.5
G.4
5
221
22
32 A5.2.3
2
A4.1.2
E.
ALL COLUMNS TO BE EXPOSED UNLESS OTHERWISE NOTED. REF SPECS FOR EXPOSED CONCRETE FINISH INFORMATION.
F.
REFER TO THE A9.3.X SERIES SHEETS FOR THE INTERIOR OPENING SCHEDULE(S), TYPES, AND DETAILS.
G.
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
H.
REFER TO THE 'AI' SERIES SHEETS FOR INTERIOR FURNISHING INFORMATION.
I.
REFER TO AND COORDINATE WITH CIVIL, STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL, AND COMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DRAWING.
217AA
4 A4.3.7 2C2B
PLYWOOD? CHANGE TYPE
COLLABORATIVE OVERLOOK
5.5 J.
2C2B
60. 000 °
REFER TO A5.1.X FOR BASEMENT WATERPROOFING INFORMATION.
ACADEMIC BUILDING FOR SSW & CoNHI 501 W. MITCHELL ARLINGTON, TX 76010
SMITHGROUP
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
TURNER
6
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
6
PACHEKO KOCH
71
67 A9.6.3
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
A4.1.4
7
7
70 67
OPEN TO BELOW
JQ ENGINEERING
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
SHEET KEYNOTES
A7.1.3
ELEV 1 2E1
A7.1.3
A4.1.4 40
DATACOM DESIGN GROUP
FEC
AV-IT-SECURITY
31
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
STAIR 1 2S1
8
8
48 A6.1.1
9
9
2 A4.1.5
ISSUED FOR
REV
DATE
CORRIDOR 2C2 203 OPEN TO BELOW
1 A4.3.8
33
32
COLLABORATION 2C2A
41
9' - 11 3/4"
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT SCHEMATIC DESIGN
19 MAR 2021 29 JAN 2021 23 OCT 2020 31 JULY 2020
SEALS AND SIGNATURES
JAMES C. MENEFEE 20610 1
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
A4.1.6
1 / A2.2.2A
51
01/29/2021
41
KEYPLAN
NORTH
33 2 A4.3.1
1
2
A4.3.1
A4.3.8
4
B
Author
A4.3.2
1
4/7/2021 10:48:37 AM
A4.1.5
G
CC
G.4
G.5
G.6
H
H.3
H.4
51 H.6
J
J.9 K
SHEET TITLE
FLOOR PLAN - LEVEL 2 AREA B
12287.000 Plot Date:
PROJECT NUMBER
1
LEVEL 2 - FLOOR PLAN AREA B SCALE: 1/8" = 1'-0"
CD
SHEET NUMBER
A2.2.2B
GENERAL SHEET NOTES
CC
H
H.3
H.5
J
J.1
J.3
K
A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
FOR BASIC LIFE SAFETY AND CODE INFORMATION APPLYING TO THIS PROJECT, REFER TO THE G2.X SERIES SHEETS LOCATED PER THE PROJECT SHEET INDEX.
C.
REFER TO THE A3.X SERIES SHEETS FOR THE REFLECTED CEILING PLANS.
D.
REFER TO THE A9.2.X SERIES SHEETS FOR PARTITION SYSTEMS TYPES AND DETAILS. UNLESS OTHERWISE INDICATED, ALL WALLS SHALL BE P0A3. ALL WALLS OF OFFICES, CLASSROOMS, TEACHING SPACES, LABS, EXAM ROOMS, AND CONFERENCE/DEBRIEF ROOMS TO BE INSULATED AND ACOUSTICALLY SEALED. ALL J-BOXES AND OTHER SERVICE BOXES SHALL BE OFFSET NO LESS THAN 0' - 6".
1 A4.1.5 6.5°
21
E.
ALL COLUMNS TO BE EXPOSED UNLESS OTHERWISE NOTED. REF SPECS FOR EXPOSED CONCRETE FINISH INFORMATION.
F.
REFER TO THE A9.3.X SERIES SHEETS FOR THE INTERIOR OPENING SCHEDULE(S), TYPES, AND DETAILS.
G.
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
H.
REFER TO THE 'AI' SERIES SHEETS FOR INTERIOR FURNISHING INFORMATION.
I.
REFER TO AND COORDINATE WITH CIVIL, STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL, AND COMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DRAWING.
1 A4.3.6
38 A5.2.3
1
1
48 A6.1.4
J.
REFER TO A5.1.X FOR BASEMENT WATERPROOFING INFORMATION.
ACADEMIC BUILDING FOR SSW & CoNHI 501 W. MITCHELL ARLINGTON, TX 76010
SMITHGROUP
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
TURNER STAIR 4
2
21
2S4
A4.3.6
1
3
A7.2.4
1
A4.3.6
232
1.9 2
2S4
1.9 231
4' - 0"
2' - 8"
9' - 7 5/8"
71
2' - 8"
230
28
22 A7.1.1
MOTHERS ROOM
SIM
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
SIM
DATACOM DESIGN GROUP
37
36
AV-IT-SECURITY
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
A7.2.1
2C2C 67
228
229
68
JQ ENGINEERING
TRASH / RECYCLING
229 7' - 4"
A8.2.1
GENDER NEUTRALGENDER NEUTRAL RESTROOM RESTROOM
A7.2.2
72 A9.3.3
225B
8' - 0"
A4.3.6 232
A7.2.6
230
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
4
231
2
PACHEKO KOCH
A4.3.7
CONFERENCE
UP
STUDENT ORGS
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
A7.2.1
228
22 A7.1.1
1
7' - 9"
SIM
7' - 8 3/8"
1' - 10 1/4" A7.2.2
12
OPEN COLLABORATION
8' - 8"
226
60-SEAT CLASSROOM
A8.2.1
226
EJ
222E
P0F3
223A
A4.3.7
EJ, INPRO 502-A01-100
WOMEN 222
225A
2' - 6"
224B
6' - 0"
2' - 6"
4
3.9
3' - 0"
220
33' - 0 1/2"
SEALS AND SIGNATURES
P0F3A
30-SEAT CLASSROOM
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
224
STAIR 3
01/29/2021
3' - 0"
2S3 38
7' - 0"
A6.1.3
FEC
KEYPLAN
219
CORRIDOR
1 / A2.2.2B
221
2C4
4.8
29' - 8 1/2"
C
13 A6.1.3
Author
NORTH
224A
MDF 1 / A2.2.2B
19 MAR 2021 29 JAN 2021 23 OCT 2020
JAMES C. MENEFEE 20610
220
UP
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT
A7.2.1
ELEC
7' - 0"
3.8
4
2S3
4.8
EJ AT CURTAINWALL 32 A5.2.7
EJ ON WALL, INPRO 114-A07-075
2' - 6"
A4.1.4
69
A4.3.7
P0F3A
1
34
A4.1.4
3
2 A9.4.2
34
3.8
3 2
222A
222B
222C
222D
40 A7.1.2 A7.2.2
DATE
37
A7.2.1
68 A5.2.3
REV
Sim
5' - 4"
227
ISSUED FOR
223 223B
6' - 0"
CONFERENCE
225
MEN
223C
2' - 8"
227
3
FEC
57' - 2 5/8"
5' - 4"
70 A7.2.9
1
4/7/2021 10:48:46 AM
A4.1.5
CC
G.6
H
H.3
SHEET TITLE
J
K
FLOOR PLAN - LEVEL 2 AREA C
Plot Date:
12287.000
1
LEVEL 2 - FLOOR PLAN AREA C SCALE: 1/8" = 1'-0"
PROJECT NUMBER
CD
SHEET NUMBER
A2.2.2C
GENERAL SHEET NOTES A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
FOR BASIC LIFE SAFETY AND CODE INFORMATION APPLYING TO THIS PROJECT, REFER TO THE G2.X SERIES SHEETS LOCATED PER THE PROJECT SHEET INDEX.
C.
REFER TO THE A3.X SERIES SHEETS FOR THE REFLECTED CEILING PLANS.
D.
REFER TO THE A9.2.X SERIES SHEETS FOR PARTITION SYSTEMS TYPES AND DETAILS. UNLESS OTHERWISE INDICATED, ALL WALLS SHALL BE P0A3. ALL WALLS OF OFFICES, CLASSROOMS, TEACHING SPACES, LABS, EXAM ROOMS, AND CONFERENCE/DEBRIEF ROOMS TO BE INSULATED AND ACOUSTICALLY SEALED. ALL J-BOXES AND OTHER SERVICE BOXES SHALL BE OFFSET NO LESS THAN 0' - 6".
CC
H.3
H.5
J
J.1
J.3
K
21
22' - 1 7/8"
10' - 8"
7' - 8 3/8"
3S4
14' - 4 3/8 "
1.9
3C3C
331
79' - 8 3/8 " 63' - 4"
333B
41' - 0"
333D 328
68
3S2 312
315
5.7
310
308
3S3 3C3B
1 / A2.2.3C 1 / A2.2.3B 29' - 10"
3E3
333
324
9' - 10 5/8"
A4.1.4
3C3A 22
OPEN TO BELOW
318
FEC
8
3E2
3C2
322B
3C3
3C1
FEC
3E1
314
311
309
305N
317
318
?
301D
304
307
FEC
9
319
305A
305M
301C
7' - 0"
AV-IT-SECURITY
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
ISSUED FOR
6
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT SCHEMATIC DESIGN
7
SEALS AND SIGNATURES
305D
31 8
A4.1.3
305E 305F
305H
301K
301G
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION 01/29/2021
32 KEYPLAN
305G 301P
301
301L
19 MAR 2021 29 JAN 2021 23 OCT 2020 31 JULY 2020
9
301J 30' - 11"
305K
DATE
JAMES C. MENEFEE 20610
12
305J
REV
5
FEC
305C
305L
41
305B
319A
322D
4.8
301E 13' - 1"
322C
44
DATACOM DESIGN GROUP
5.5
301A
305
301B A4.1.3
24' - 4"
1 / A2.2.3C 1 / A2.2.3B
333H 38
306
313
316
322A
322
36
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
26' - 8"
69
9' - 7"
A4.1.4
12' - 0"
A9.6.5
3C1B
TURNER
3.9
19' - 0"
75' - 3 1/2"
80' - 4"
7
3C1C
10' - 8"
2' - 0"
333G
3C1A
6
4
333J
320
321
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
15' - 2"
A4.1.3
3.8
14' - 1"
320AA
326
286' - 7 7/8"
48' - 9"
333K
FEC
2' - 0"
REFER TO A5.1.X FOR BASEMENT WATERPROOFING INFORMATION.
SMITHGROUP
333F
325
34' - 4 1/2"
1 / A2.2.3A 1 / A2.2.3B
126' - 9"
10' - 2"1' - 10 1/2"
5
21' - 1 3/4"
1' - 11 1/2"
2' - 0 6' 1/2" - 5 1/4"
70
REFER TO AND COORDINATE WITH CIVIL, STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL, AND COMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DRAWING.
333L
5' - 10 5/8"
G
A4.4.11 A4.1.3 56
I.
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
333N
333E
327
1' - 7 1/8"
3.9 F
REFER TO THE 'AI' SERIES SHEETS FOR INTERIOR FURNISHING INFORMATION.
JQ ENGINEERING
3
333P
FEC
FEC
3C3
E
H.
333Q
11' - 4 1/8 "
D
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
333C
333M
C
G.
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
332
333R
A4.1.1
B
REFER TO THE A9.3.X SERIES SHEETS FOR THE INTERIOR OPENING SCHEDULE(S), TYPES, AND DETAILS.
501 W. MITCHELL ARLINGTON, TX 76010
PACHEKO KOCH
3
BB
1.9 2
333A
A.2
1
330
2
A.1
F.
J.
3' - 0"
21' - 10"
30' - 3 3/4" ' 15 - 10"
2' - 8 3/4" 3' - 2" 10"
18' - 2 1/2" 3' - 11 1/4"
A
ALL COLUMNS TO BE EXPOSED UNLESS OTHERWISE NOTED. REF SPECS FOR EXPOSED CONCRETE FINISH INFORMATION.
21
1
2
E.
ACADEMIC BUILDING FOR SSW & CoNHI
10
301Q
301N
NORTH
301R
301M 301T
301U
33
301O 301V
10 1/4"
Author
301S
1
3' - 8 3/8"
73' - 7" 75' - 7 3/4"
A4.1.1
Plot Date:
4/7/2021 10:49:05 AM
7' - 5" 4' - 7"
BB
1
LEVEL 3
A
SCALE: 1/16" = 1'-0"
A.1
32' - 8"
A.2
23' - 4"
B
33' - 0"
C
34' - 0"
D
34' - 0"
E
34' - 0"
F
32' - 0"
G
CC
G.4 G.5
41
13.000°
1 / A2.2.3A 1 / A2.2.3B
FEC
19' - 11"
G.6
11' - 4"
H
4' - 2"
H.3
SHEET TITLE
16' - 0"
H.4 H.6
26' - 6"
J
J.9
2' - 1"
51
FLOOR PLAN - LEVEL 3 OVERALL
K 12287.000 PROJECT NUMBER
CD
SHEET NUMBER
A2.2.3
GENERAL SHEET NOTES A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
FOR BASIC LIFE SAFETY AND CODE INFORMATION APPLYING TO THIS PROJECT, REFER TO THE G2.X SERIES SHEETS LOCATED PER THE PROJECT SHEET INDEX.
C.
REFER TO THE A3.X SERIES SHEETS FOR THE REFLECTED CEILING PLANS.
D.
REFER TO THE A9.2.X SERIES SHEETS FOR PARTITION SYSTEMS TYPES AND DETAILS. UNLESS OTHERWISE INDICATED, ALL WALLS SHALL BE P0A3. ALL WALLS OF OFFICES, CLASSROOMS, TEACHING SPACES, LABS, EXAM ROOMS, AND CONFERENCE/DEBRIEF ROOMS TO BE INSULATED AND ACOUSTICALLY SEALED. ALL J-BOXES AND OTHER SERVICE BOXES SHALL BE OFFSET NO LESS THAN 0' - 6".
2 A4.1.3
56
70
A4.1.6
68 A5.2.4
70 A5.2.5 6' - 0"
12' - 0"
17' - 0" 6' - 0"
2' - 4"
4' - 8" 6' - 8"
8' - 8"
2' - 0"
11' - 4"
2
3
A4.3.4
A4.3.4
12' - 8"
4' - 8"
4' - 8"
7' - 4"
7' - 3"
4' - 8"
10' - 8"
5' - 4"
8' - 0"
6' - 5"
1 / A2.2.3B
A4.4.11
72 A5.2.6
2' - 0"
3' - 4"
E.
ALL COLUMNS TO BE EXPOSED UNLESS OTHERWISE NOTED. REF SPECS FOR EXPOSED CONCRETE FINISH INFORMATION.
F.
REFER TO THE A9.3.X SERIES SHEETS FOR THE INTERIOR OPENING SCHEDULE(S), TYPES, AND DETAILS.
G.
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
H.
REFER TO THE 'AI' SERIES SHEETS FOR INTERIOR FURNISHING INFORMATION.
I.
REFER TO AND COORDINATE WITH CIVIL, STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL, AND COMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DRAWING.
J.
43 A9.6.6
REFER TO A5.1.X FOR BASEMENT WATERPROOFING INFORMATION.
ACADEMIC BUILDING FOR SSW & CoNHI 501 W. MITCHELL ARLINGTON, TX 76010
SMITHGROUP
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
TURNER
5
320AA
45
SERVER 24 A4.1.3 A5.2.5 68
STORAGE
12 A6.1.2
69
66
A7.2.9
MULTI-USE SKILLS
MULTI-USE SKILLS
312
310
BIOMAKER LAB
A7.2.9
68
68
315
47
A7.2.9
A7.2.9
A7.2.1
MULTI-USE SKILLS
72
JQ ENGINEERING
308
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
68
STUDENT LOCKERS
Sim
320
321
SIM
A7.2.9
Sim
320 42
5.7
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
A4.3.4
36
321
48 A9.3.3
PACHEKO KOCH
312C
Sim
FACULTY / STAFF BREAK
A7.2.2
310C
A7.2.9
3S2
1 52
A7.2.9
STAIR 2
320AA
5
44
68
306
A7.2.9
4
DATACOM DESIGN GROUP
A4.3.4
AV-IT-SECURITY
1' - 6 3/4"
322
3C2
316 314
318
ELEC. 318
322B
322C
322C
322D
HEALTH ASSESSMENT ROOM
24' - 4 3 /8"
A4.1.3
313
313D
314C
308B 5' - 11 1/8"
7' - 2"
A9.6.5
7
ISSUED FOR
33' - 1 3/8"
319A
A7.2.7
A7.2.7
311
LAUNDRY/ FOLDING
31
P0A3A
SKILLS LAB
SKILLS LAB
309
307
P0A3A
P0A3A
9
A7.2.10 72
P0A3A
P0A3
JAMES C. MENEFEE 20610
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
6' - 0"
48' - 0"
4' - 0"
5' - 4" 14' - 0"
2
A7.2.10 19 4' - 8"
A7.2.10 72
309B 6' - 0"
11' - 4"
A4.1.6
6' - 0"
72 A5.2.4
5' - 3 7/8 "
3' - 4"
01/29/2021
307C KEYPLAN
10' - 8" 36' - 0"
2
41
12' - 0" 10' - 8"
1 A4.3.2
6' - 0"
4' - 8"
Author
3
4/7/2021 10:49:23 AM
A.2
B
C
D
E
F
A
1 / A2.2.3B
71 A7.2.10
SHEET TITLE
A4.3.1
A.1
FLOOR PLAN - LEVEL 3 AREA A
G
12287.000
Plot Date:
PROJECT NUMBER
1
LEVEL 3 - FLOOR PLAN AREA A SCALE: 1/8" = 1'-0"
NORTH
307B
4' - 8"
12' - 0"
A4.3.2
A
19 MAR 2021 29 JAN 2021 23 OCT 2020
SEALS AND SIGNATURES
P0A3A
311B
BB
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT
P0A3A
319A
3
DATE
8
12' - 11 7/8"
A4.3.2
REV
1' - 1 1/2"
313E
SKILLS LAB
SUPPLY / SUPPORT
A7.2.8
4' - 0"
6' - 10"
A8.3.2
3E1
WOMEN
4
2' - 4" 3 ' - 4"
6' - 10" SIM 34
34
34' - 0"
319
6' - 0"
6' - 4 5/8"
3C1
317
322D
12
7' - 6 7/8"
FEC
IDF
27' - 0 3/8"
32
6' - 4 5/8"
3C1
ELEV 1
313C
314B
11' - 6 1/4"
HEALTH ASSESSMENT ROOM
6' - 10"
CORRIDOR
A7.2.10
313B
MEN 317
36
6
Sim
A4.1.5
6' - 2"
3' - 0"
2
322A
6' - 10"
47Sim
CUSTODIAL
CORRIDOR
5' - 3 5/8"
5' - 10 3/4"
Sim
44
3E2
HEALTH ASSESSMENT ROOM
2' - 7"
A4.1.3
71
HEALTH ASSESSMENT
6' - 2"
1
A7.2.7
ELEV 2
7' - 6 7/8"
3' - 0 1/2"
2' - 7"
6' - 2"
322B
30 A6.3.1
14' - 3 5/8"
314A
316
319B
322A
A4.3.3
25' - 5"
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
20' - 2 1/4"
HEALTH ASSESSMENT ROOM
72
6' - 6 1/8"
311A
8' - 6"
310B
312A
32' - 10 1/8"
A9.6.5
17' - 4 1/8"
3C1B
322
SIM
A8.3.1
20 A7.1.2
TRASH / RECYCLING
17' - 10 1/8"
7' - 0"
309A
70 A7.2.9
7' - 0"
66
FEC
3C1C
14' - 0 3/4"
308A
10' - 3 1/2"
OPEN COLLAB
A4.3.3
72 A9.3.3
10' - 2 3/4"
42' - 9 3/4" 122200.A00 CURTAINS AND DRAPES
307A
2
7' - 10 1/8"
315A
3S2B
8' - 3 1/4"
37' - 3 3/8"
310A
16' - 6 1/8"
312B
13' - 1 1/8"
3S2A
17' - 8"
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
CD
SHEET NUMBER
A2.2.3A
GENERAL SHEET NOTES G
G.5
G.4
G.6
H
H.3
J
K
A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
FOR BASIC LIFE SAFETY AND CODE INFORMATION APPLYING TO THIS PROJECT, REFER TO THE G2.X SERIES SHEETS LOCATED PER THE PROJECT SHEET INDEX.
C.
REFER TO THE A3.X SERIES SHEETS FOR THE REFLECTED CEILING PLANS.
D.
REFER TO THE A9.2.X SERIES SHEETS FOR PARTITION SYSTEMS TYPES AND DETAILS. UNLESS OTHERWISE INDICATED, ALL WALLS SHALL BE P0A3.
1 A4.1.5
TRASH / RECYCLING 3C3B
MDF
3E3 A7.2.9
324
5
COLLABORATION
A4.1.4
32 A9.9.1
SIM
64 A9.3.3
5 SIM
72 A9.3.3
4 303
5.5
1' - 5 1/8"
OPEN COLLABORATION
32 A7.1.3
21 A9.6.3
3C1A
6
6
3C3
3C1
47 A9.6.6
318
69
11' - 1 3/8"
305L
37
305J
OFFICE
OFFICE
305K
305E
P0A3A
300A 15' - 6 5/8"
10
305H
301G
1 2
1 A4.3.8
OFFICE
P0A3A
305G
P0A3A
2' - 6"
6' - 10" ALIGN 10' - 0"
305BB
STORAGE
PATIENT
PATIENT
301P
301Q
6' - 5 3/8"
301L
10' - 0 1/2"
A7.2.7
301L
301N
P0A3A
A7.2.8 301N
301R
9
A7.2.7
P0A3A
50
DEBRIEF
A7.2.8
A7.2.8
CONTROL
01/29/2021
A8.3.2
P0A3A
301T
301O
301M
P0A3A
CONTROL
KEYPLAN
301U
301T
20' - 10 5/8"
8' - 9"
41
10' - 6 1/8"
10' - 6"
PATIENT
A4.3.1
P0A3A
301S
72 A5.2.1 72 A9.3.3
NORTH
P0A3A
301O
A4.3.1
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
A4.1.6
52
1
SEALS AND SIGNATURES
JAMES C. MENEFEE 20610
1
CONTROL
19 MAR 2021 29 JAN 2021 23 OCT 2020
FEC
A8.3.2
A8.3.2
2
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT
35 A7.2.8
10' - 0 1/4"
8' - 4 7/8"
58
301S
1 / A2.2.3A
DEBRIEF
9' - 2 1/2"
301M
301P
4' - 8"
301KB
1 Sim
32 10
CONTROL
MEDICINE ROOM
24' - 0"
DATE
10' - 1 1/4"
A7.2.8
307B
REV
A8.3.2
A7.2.7
301K
P0A3A
ISSUED FOR
P0A3A
LARGE PATIENT
ALIGN
41
A4.1.5
24
18' - 5 3/4"
P0A3A
305F
10' - 10 1/2"
305H
11' - 6"
OFFICE
301J
9
P0A3A
OFFICE
305G
P0A3A
CONTROL
8
305F P0A3A
A7.2.7
305D 1' - 7 1/2"
P0A3A
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
301Q
OFFICE
11' - 0"
305J
7 P0A3A
OFFICE
305E
305K
P0A3A
P0A3A
A7.2.6
2
301R
P0A3A
305C
FEC
P0A3
301V
305L
WORKROOM
P0A3A
301U
OFFICE
301 A8.3.2
P0A3
10' - 8"
A4.1.5
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
56
301C
305D
PACHEKO KOCH
CLINICAL SIMULATION
47
2
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
301B
301C
STORAGE
REFER TO A5.1.X FOR BASEMENT WATERPROOFING INFORMATION.
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
8
301E 301F
301AB
P0A3A
21
31
CONTROL
DEBRIEF
301J
305B
A8.3.1
J.
SMITHGROUP
10' - 0 1/2"
9' - 6 1/4"
305B
305M
REFER TO AND COORDINATE WITH CIVIL, STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL, AND COMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DRAWING.
13' - 11 7/8"
OFFICE
4' - 11 1/2" 1' - 9"
10' - 4 1/2"
9
P0A3A
305A
2' - 11"
301AA
48 A7.2.8
14' - 11 7/8"
P0A3A
OFFICE
LARGE PATIENT
A8.3.1
6' - 0 1/4"
P0A3A
I.
DATACOM DESIGN GROUP
10' - 0 1/2"
305M
9' - 2 1/4"
REFER TO THE 'AI' SERIES SHEETS FOR INTERIOR FURNISHING INFORMATION.
AV-IT-SECURITY
301KA
OFFICE
10' - 8 1/4"
20
301A
1' - 5 1/2"
6' - 5 7/8"
P0A3A
A7.1.3
301D
DEBRIEF
7' - 3 7/8"
1' - 2 7/8"
305N
305
FEC
10' - 10 3/4"
5' - 2 5/8"
305N
A9.6.4
RECEPTION
A7.1.3
67
301B
STORAGE
8
6.500°
SIM CENTER OFFICE
H.
7
70
300
304 1' - 1 1/2"
7' - 1 1/2"
4' - 0"
ELEC
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
301D
305AA
3E1
318
301G
30 4
ELEV 1
G.
JQ ENGINEERING
9' - 0"
6.541°
A8.3.1
20 A6.1.1
REFER TO THE A9.3.X SERIES SHEETS FOR THE INTERIOR OPENING SCHEDULE(S), TYPES, AND DETAILS.
501 W. MITCHELL ARLINGTON, TX 76010
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
60-SEAT CLASSROOM 1' - 7 1/4"
A8.3.2
7
F.
ACADEMIC BUILDING FOR SSW & CoNHI
TURNER
CORRIDOR
34
ALL COLUMNS TO BE EXPOSED UNLESS OTHERWISE NOTED. REF SPECS FOR EXPOSED CONCRETE FINISH INFORMATION.
A4.3.7
STUDENT LOCKERS 306
E.
333H
36
333A A8.3.1
3C3A
22
DEBRIEF
A7.1.4
30 A9.9.1
ALL WALLS OF OFFICES, CLASSROOMS, TEACHING SPACES, LABS, EXAM ROOMS, AND CONFERENCE/DEBRIEF ROOMS TO BE INSULATED AND ACOUSTICALLY SEALED. ALL J-BOXES AND OTHER SERVICE BOXES SHALL BE OFFSET NO LESS THAN 0' - 6".
1 / A2.2.3C
4.8
5.5°
38
SIM
10.0°
A4.1.6
48 A9.3.3
68
FEC
1
A8.3.1
324
SIM
15 A9.3.3
333H
1 / A2.2.3A
1 / A2.2.3C
ELEV 3 70
SIM
15 A9.3.3
7' - 5 1/4"
A7.2.8
33
PATIENT 301V
B
2
SIM
A4.3.8
4
Author
A4.3.2
72 A9.3.3
SIM SHEET TITLE
4/7/2021 10:49:34 AM
40 A5.2.1
G
G.4
G.5
G.6
H
H.3
H.4
1
H.6
51
FLOOR PLAN - LEVEL 3 AREA B
J.9
A4.1.5
12287.000 Plot Date:
PROJECT NUMBER
1
LEVEL 3 - FLOOR PLAN AREA B SCALE: 1/8" = 1'-0"
CD
SHEET NUMBER
A2.2.3B
GENERAL SHEET NOTES A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
FOR BASIC LIFE SAFETY AND CODE INFORMATION APPLYING TO THIS PROJECT, REFER TO THE G2.X SERIES SHEETS LOCATED PER THE PROJECT SHEET INDEX.
C.
REFER TO THE A3.X SERIES SHEETS FOR THE REFLECTED CEILING PLANS.
D.
REFER TO THE A9.2.X SERIES SHEETS FOR PARTITION SYSTEMS TYPES AND DETAILS. UNLESS OTHERWISE INDICATED, ALL WALLS SHALL BE P0A3. ALL WALLS OF OFFICES, CLASSROOMS, TEACHING SPACES, LABS, EXAM ROOMS, AND CONFERENCE/DEBRIEF ROOMS TO BE INSULATED AND ACOUSTICALLY SEALED. ALL J-BOXES AND OTHER SERVICE BOXES SHALL BE OFFSET NO LESS THAN 0' - 6".
H
H.3
H.5
J
J.1
J.3
K
E.
ALL COLUMNS TO BE EXPOSED UNLESS OTHERWISE NOTED. REF SPECS FOR EXPOSED CONCRETE FINISH INFORMATION.
F.
REFER TO THE A9.3.X SERIES SHEETS FOR THE INTERIOR OPENING SCHEDULE(S), TYPES, AND DETAILS.
G.
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
H.
REFER TO THE 'AI' SERIES SHEETS FOR INTERIOR FURNISHING INFORMATION.
I.
REFER TO AND COORDINATE WITH CIVIL, STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL, AND COMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DRAWING.
J.
REFER TO A5.1.X FOR BASEMENT WATERPROOFING INFORMATION.
ACADEMIC BUILDING FOR SSW & CoNHI 501 W. MITCHELL ARLINGTON, TX 76010
SMITHGROUP
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
TURNER
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com 1
PACHEKO KOCH
A4.1.5
21
29 A6.1.4
1 A4.3.6
4 A4.3.6
1
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
JQ ENGINEERING
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
1
DATACOM DESIGN GROUP AV-IT-SECURITY
UP
21
STAIR 4
2
3S4
A4.3.6
SP WAITING
3
1
330
A4.3.6
A4.3.7
DN
COLLAB
1.9
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
3C3C
1.9
3S4
332
14' - 5 7/8"
DEBRIEF 333A
333AB
333BA
333BB 30
28
13' - 1 1/8"
333R
EXAM
A8.3.2
333Q
CONTROL 333D
333D
333P
8' - 8"
333N
EJ, INPRO 502-A01-100
333F
327
6' - 6 1/2"
EJ, INPRO 502-A01-100 8' - 6 1/4"
333L
8' - 6 1/4"
EXAM
325
325
ELEC 326
STORAGE
333K
3S3
SHEET TITLE
A8.3.1
324
1 / A2.2.3B
68
DEBRIEF 333H
40 A6.1.3
CC
G.5
G.6
5' - 6" 16' - 5 5/8"
MDF
333 13' - 1 1/8"
12' - 6"
324
70 A7.2.9
3E3 FEC
1 / A2.2.3B
C
333J
16' - 0 1/4"
Author
4/7/2021 10:49:45 AM
5' - 5 1/4"
ELEV 3
3C3B
H
H.3
J
67
70
A7.1.3
A7.1.3
48 A9.3.3
4.8
FLOOR PLAN - LEVEL 3 AREA C
SIM
K
12287.000
Plot Date:
PROJECT NUMBER
1
LEVEL 3 - FLOOR PLAN AREA C SCALE: 1/8" = 1'-0"
NORTH
CLINICAL SIMULATION
3S3
TRASH / RECYCLING
4.8
333J
333GB
DN
333H
3' - 0"
11' - 11 1/8"
69
KEYPLAN
333G
326
12' - 0"
A4.1.4
STAIR 3
3.8
4
333K
EXAM 4' - 0" 2' - 6"
01/29/2021
8' - 6 1/4"
9' - 2"
GENDER NEUTRAL RESTROOM
48 A5.2.7 EJ AT CURTAINWALL
1' - 7" 20' - 4 1/2"
2' - 6"
A4.3.7
333L
333GA
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
EJ ON WALL, INPRO 114-A07-075, IN OFFWHITE 3
333M
EXAM
21 A7.1.1
12' - 0"
333M
333F
47 A5.2.6
JAMES C. MENEFEE 20610
333N
EXAM
19 MAR 2021 29 JAN 2021 23 OCT 2020
SEALS AND SIGNATURES
A4.3.7
8' - 6 1/4"
FACULTY
12' - 4 5/8"
462
MEN
463
327
EJ, INPRO 502-A01-100
69 A5.2.6
4
EXAM
333E
56 A7.2.8
3
333P
8' - 6 1/4"
328
EXAM
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT
2
11' - 11 1/2"
328D
328C
328B
328A
42' - 7 1/8"
6' - 0"
8' - 8"
FEC
EXAM
WOMEN
32 A5.2.6
3.8
333Q
8' - 6 1/4"
P0A3A
10' - 5 5/8"
5' - 4"
EXAM
333E
3.9
333R
333C
333B
328
DATE
6' - 6"
EXAM
DEBRIEF
64 A7.1.2
REV
8' - 6 1/4"
333AA
12' - 1 1/8"
5' - 4"
A8.3.2
ISSUED FOR
8' - 6 1/4"
333C
FEC
3
6' - 9"
CHANGING
331
5' - 4 7/8"
CHANGING
333DD
332
A8.3.2 331
18
333CC
5' - 4"
9' - 11 3/8"
330
4' - 4"
4' - 8"
6' - 0"
6' - 0"
8' - 0"
2
6' - 6 1/8"
2
1 A4.1.5
CD
SHEET NUMBER
A2.2.3C
GENERAL SHEET NOTES
H.3
H.5
J
J.1
J.3
K
A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
FOR BASIC LIFE SAFETY AND CODE INFORMATION APPLYING TO THIS PROJECT, REFER TO THE G2.X SERIES SHEETS LOCATED PER THE PROJECT SHEET INDEX.
C.
REFER TO THE A3.X SERIES SHEETS FOR THE REFLECTED CEILING PLANS.
D.
REFER TO THE A9.2.X SERIES SHEETS FOR PARTITION SYSTEMS TYPES AND DETAILS. UNLESS OTHERWISE INDICATED, ALL WALLS SHALL BE P0A3. ALL WALLS OF OFFICES, CLASSROOMS, TEACHING SPACES, LABS, EXAM ROOMS, AND CONFERENCE/DEBRIEF ROOMS TO BE INSULATED AND ACOUSTICALLY SEALED. ALL J-BOXES AND OTHER SERVICE BOXES SHALL BE OFFSET NO LESS THAN 0' - 6".
CC
2
431
21
2' - 10 3/4" 3' - 0"
1 21' - 10"
19' - 3 1/8"
4S4
14' - 4 3/8 "
1.9
10' - 8"
15' - 10"
3' - 11 1/4"
10' - 4 5/8"1' - 5"
21
19' - 7 3/4"
2' - 8 3/4" 3' - 2" 10"
18' - 2 1/2"
63' - 4"
3
420
48' - 10"
5
1 / A2.2.4C 1 / A2.2.4B 39' - 7 5/8"
38
46
407
411
4S2
423 4C1B
405
406
A4.1.3 48
6
5.5
414
44
416G
416F
4E1
403
416J
416K
416L
405A
404J
404T
416P
416M
404B
403W
403M
401B
405E
405B
404S
404H
403V
404C
416D
405D
405C
404R
416R
403N
404D
403U
403P
404N 404Q
404F
403T
404E
402A
401U
401D
403C
402N
402B
401T
401E
403D
402M
402C
401S
401F
403E
402L
402D
401R
401G
403F
402K
402E
401Q
401H
403Q
404P
FEC
402P
8
403R
95 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT SCHEMATIC DESIGN
9 32
403G 403S
REV
DATE
19 MAR 2021 23 OCT 2020 31 JULY 2020
SEALS AND SIGNATURES
403H
A4.1.3
416S
403B
31
403I 404G
ISSUED FOR
401C
403K
404L
404M
12
401A
403A
3
416B 416C
403L
401
416Q
7' - 0 1/8"
404A
FEC
413
416H
404U
A7.2.2
405F A4.1.3
404W
19' - 0"
4C2
416A
404X
13' - 1"
40
404Y
30' - 11"
8
409
404Z
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
7
FEC
34' - 0 1/2"
416
24 416N
408
412
4E2
4C1C
402
FEC
FEC
7
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
12' - 0"
4C1
4C1A
JQ ENGINEERING
6
A4.1.3 14
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
5
A4.1.4
8' - 7"
41' - 4"
A4.1.3
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
26' - 8"
4C4A
6
A7.2.7
415
REFER TO A5.1.X FOR BASEMENT WATERPROOFING INFORMATION.
SMITHGROUP
4.8
1 / A2.2.4C 1 / A2.2.4B
22
68
417
5.7
4C3
422 ° 0.0 10
286' - 7 7/8"
A4.1.3
4E3
4
9' - 7"
2' - 0"
REFER TO AND COORDINATE WITH CIVIL, STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL, AND COMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DRAWING.
15' - 2"
126' - 6 1/2"
4S3
FEC
20' - 4 1/2"
424
69
46' - 4"
1 / A2.2.4A 1 / A2.2.4B
A4.4.11 A4.1.3
11 3/4"
I.
AV-IT-SECURITY
3.9
425
4C4
70
REFER TO THE 'AI' SERIES SHEETS FOR INTERIOR FURNISHING INFORMATION.
DATACOM DESIGN GROUP
10' - 8"
2' - 0"
G
A4.1.4
56
3.8
5' - 6"
F
428
11' - 4 1/8 "
5' - 10 5/8"
E
H.
426
3.8 D
24' - 4"
4C3A
421
C
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
PACHEKO KOCH 427
B
G.
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
3
BB
REFER TO THE A9.3.X SERIES SHEETS FOR THE INTERIOR OPENING SCHEDULE(S), TYPES, AND DETAILS.
501 W. MITCHELL ARLINGTON, TX 76010
TURNER
41' - 0"
430
429
A.2
F.
J.
2
A.1
ALL COLUMNS TO BE EXPOSED UNLESS OTHERWISE NOTED. REF SPECS FOR EXPOSED CONCRETE FINISH INFORMATION.
1.9
432 FEC
A
E.
ACADEMIC BUILDING FOR SSW & CoNHI
10
JAMES C. MENEFEE 20610
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
FEC
1 / A2.2.4A 1 / A2.2.4B
01/29/2021 402J
402F
401P
401J
402H
402G
401N
401K
401M
401L
KEYPLAN
33
75' - 7 3/4"
3' - 8 3/8"11' - 3 1/4" 7' - 5" 4' - 7"
32' - 8"
23' - 4"
33' - 0"
34' - 0"
34' - 0"
34' - 0"
32' - 0"
19' - 11"
41
62' - 3 5/8" 11' - 4"
4' - 2"
NORTH
16' - 0"
26' - 6"
2' - 1"
Author
51
4/7/2021 10:50:00 AM
BB
1
A
A.1
A.2
B
C
D
E
F
G
CC
SHEET TITLE
G.4
G.5 G.6
H
H.3
H.4
H.6
J
J.9
K
FLOOR PLAN - LEVEL 4 OVERALL
LEVEL 4
12287.000
SCALE: 1/16" = 1'-0"
Plot Date:
PROJECT NUMBER
CD
SHEET NUMBER
A2.2.4
GENERAL SHEET NOTES
A
A.1
A.2
B
C
D
E
F
G
A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
FOR BASIC LIFE SAFETY AND CODE INFORMATION APPLYING TO THIS PROJECT, REFER TO THE G2.X SERIES SHEETS LOCATED PER THE PROJECT SHEET INDEX.
C.
REFER TO THE A3.X SERIES SHEETS FOR THE REFLECTED CEILING PLANS.
D.
REFER TO THE A9.2.X SERIES SHEETS FOR PARTITION SYSTEMS TYPES AND DETAILS. UNLESS OTHERWISE INDICATED, ALL WALLS SHALL BE P0A3. ALL WALLS OF OFFICES, CLASSROOMS, TEACHING SPACES, LABS, EXAM ROOMS, AND CONFERENCE/DEBRIEF ROOMS TO BE INSULATED AND ACOUSTICALLY SEALED. ALL J-BOXES AND OTHER SERVICE BOXES SHALL BE OFFSET NO LESS THAN 0' - 6".
2 A4.1.6
A4.4.11
A4.1.3 70
20 A4.4.11
A4.3.4
12' - 0" 12' - 8"
17' - 0"
6' - 0"
6' - 0"
4' - 8"
2' - 4"
5' - 3"
8' - 8"
2' - 0"
4' - 8"
11' - 4"
12' - 8"
4' - 0"
7' - 3"
4' - 8" 5' - 5"
7' - 4" 2' - 0"
4' - 8"
10' - 8"
5' - 4"
7' - 4"
8' - 0"
6' - 5"
4
2' - 0"
3' - 4"
30 A5.2.7
28 A6.1.2
37
OFFICE
416J
416K
OFFICE 416L
P0A3A
416C
PHONE 416C
6' - 0"
A4.1.3
2' - 4" 3 ' - 4" 24' - 4 3 /8"
4' - 0"
3' - 11 3/4"
2' - 6"
404L
Sim
OFFICE
OFFICE
405E
405B
404S 405B
405D
405C
10' - 8"
416R
P0A3A
OFFICE
OFFICE
405D
405C
P0A3A
14' - 0"
404Q
4' - 8" 0" 6' - 0"
11' - 4"
6' - 0"
5' - 3 7/8 "
3' - 4"2' 0
10' - 8"
404A 404H
10' - 8"
10' - 4 7/8"
OFFICE
OFFICE
404B
403W
P0A3A
ISSUED FOR
OFFICE
404H
404C
404B
403W
404C
403V
403V 2
9
A4.1.5
P0A3A
404N P0A3A
.0° 80
OFFICE
OFFICE
404D
403U
404G
404D
404F
404E
404N
OFFICE 404P
OFFICE
P0A3A
A8.4.2
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
OFFICE
OFFICE
403T
404E
P0A3A
P0A3A
403T
01/29/2021 OFFICE 403S KEYPLAN
P0A3A
4' - 8"
7' - 4" 12' - 0" 6' - 0"
4' - 8"
A
Author
SHEET TITLE
2
FLOOR PLAN - LEVEL 4 AREA A
4/7/2021 10:50:11 AM
A4.1.6
A
A.1
A.2
B
C
D
E
F
G
12287.000
Plot Date:
PROJECT NUMBER
1
PLAN DETAIL SCALE: 1/8" = 1'-0"
NORTH
41
1 / A2.2.4B
10' - 8"
BB
19 MAR 2021 23 OCT 2020
JAMES C. MENEFEE 20610
72
P0A3A
12' - 0"
A4.3.2
95 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT SEALS AND SIGNATURES
403S
2
DATE
8
403U
404F
1/8"
36' - 0"
REV
OFFICE
OFFICE
404G
OFFICE
404P
P0A3A
356 5' - 4"
18 A6.1.1
P0A3A
404J
OFFICE
404Q
FEC
4' - 0"
404M
OFFICE P0F3A
416S
OFFICE
P0A3A
404R
P0A3A
9"
4E1
404M
6' - 0"
48' - 0"
404L
OFFICE 404R
OFFICE
P0A3A
P0A3A
405E
OFFICE
401AB
OFFICE
404T
OFFICE
416R
416D P0A3A
12
416Q
404J
P0A3A
404S
416Q
ELEV 1
P0F3A
P0A3A
OFFICE
404T
10' - 5 1/4"
405A
404A
A8.4.1
38 A7.2.11
OFFICE
405F
416AC
OFFICE
FEC
P0A3A
27 A7.2.11
SM CONF
405A
10' - 5 1/2"
OFFICE
68
OFFICE
405F
P0A3A
P0A6A
P0A3A
OFFICE
416M
10' - 8"
416B
416D
A4.1.5
P0A3A
WORKROOM
A8.4.1
DEAN'S OFFICE
5' - 3 1/4"
STORAGE
416B
2
404U
5' - 10"
OFFICE
404W
4' - 10"
416H
10' - 3"
416P
404X
70
10' - 8"
OFFICE
416G
P0A3A
404Y
7
P0A3A
10' - 8"
OFFICE
17' - 7 5/8"
OFFICE
10' - 8"
P0A3A
6
2' - 6"
416F
10' - 8"
OFFICE
10' - 0 7/8"
OFFICE
416AB
10' - 8"
OFFICE
10' - 0 1/2"
P0A3A
10' - 8"
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
22' - 3 1/2"
P0A3A
4' - 4"
A9.6.5 P0A3A
P0A3A
5
10' - 10"
8' - 4 3/4"
OFFICE
70 A7.2.11
3
8' - 0 1/2"
A7.2.7
0"
408E
416L
SIM
32
10' - 9"
409C
416J
44
10' - 9"
408D
40 A7.2.2 2' - 1"
413
P0A3A
416K
P0A3A A9.6.8
404Z
24
IDF
414
30
414
416H
A9.6.5
A8.4.1
416G
42
409B
ELEC.
5
1
9
WOMEN 408
416F
7' - 2 1/4"
416A
8
40 A9.3.3
408C
416
CONFERENCE
A4.1.3
413
10' - 8"
10' - 0"
ADMIN SUITE
409
10' - 8"
P0A3A
OFFICE
416N
408B
MEN
19' - 2 1/2"
CORRIDOR
4E2
11' - 3"
P0A3A
WORKROOM
412
AV-IT-SECURITY
P0A3A
416N
4C2
A4.3.3
408A
CUSTODIAL
ELEV 2
P0A3A
11' - 0"
FEC
409A
412
416AA
26 A9.6.5
8' - 1 3/8" P0A3
4C1B
4C1A
FEC
A8.4.1 58
4C1
404U
33' - 3 7/8"
9' - 4 3/4"
6' - 6 1/8"
DATACOM DESIGN GROUP
A8.4.1
10' - 0 1/2"
9' - 5 5/8"
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
54 A5.2.7
CORRIDOR
13' - 8 1/2"
P0A3
404Y
5' - 1"
SIM
P0A3A
10' - 0"
20 A7.1.2
4C1A
9' - 4 3/4"
70 A5.2.7 405
72
9 1/4"
3' - 0"
P0A3A
7' - 3"
TRASH / RECYCLING
20 A6.3.1
1 A9.6.8
P0H3
406
4S2
411 A8.4.1
P0A3A
P0A3A
415
SIM 41 7
5.7
4C1D
P0H3
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
48
404W
P0H3
REFER TO A5.1.X FOR BASEMENT WATERPROOFING INFORMATION.
SMITHGROUP
405
406
404X
70 A7.2.9
66
7
REFER TO AND COORDINATE WITH CIVIL, STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL, AND COMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DRAWING.
STUDENT LOUNGE A4.1.3
4S2
40 A9.3.3
I.
JQ ENGINEERING
6
4
STAIR 2
A4.3.3
A7.2.7
30-SEAT CLASSROOM
407
407
5.7
37
3' - 7"
30-SEAT CLASSROOM
411 A7.2.7
A7.2.1
5' - 9 1/4"
CONFERENCE ROOM
415
2
REFER TO THE 'AI' SERIES SHEETS FOR INTERIOR FURNISHING INFORMATION.
6' - 3 3/4 "
FACULTY/STAFF BREAK
SIM
H.
5' - 6"
6' - 10 1/8"
24 A9.3.3
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
A7.2.2
11' - 4"
37
A7.2.1
Sim
37
A7.2.2
11.5°
TERRACE
6
G.
PACHEKO KOCH
52
404Z
A4.3.4
Sim
Sim
68
Sim
56
1
417
REFER TO THE A9.3.X SERIES SHEETS FOR THE INTERIOR OPENING SCHEDULE(S), TYPES, AND DETAILS.
501 W. MITCHELL ARLINGTON, TX 76010
TURNER
5
68 A5.2.7 A4.1.3
F.
J.
A4.3.4
1' - 5"
5
ALL COLUMNS TO BE EXPOSED UNLESS OTHERWISE NOTED. REF SPECS FOR EXPOSED CONCRETE FINISH INFORMATION.
3 1 / A2.2.4B
56
E.
ACADEMIC BUILDING FOR SSW & CoNHI
CD
SHEET NUMBER
A2.2.4A
GENERAL SHEET NOTES G
G.5
G.4
G.6
H
H.3
J
K
A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
FOR BASIC LIFE SAFETY AND CODE INFORMATION APPLYING TO THIS PROJECT, REFER TO THE G2.X SERIES SHEETS LOCATED PER THE PROJECT SHEET INDEX.
C.
REFER TO THE A3.X SERIES SHEETS FOR THE REFLECTED CEILING PLANS.
D.
REFER TO THE A9.2.X SERIES SHEETS FOR PARTITION SYSTEMS TYPES AND DETAILS. UNLESS OTHERWISE INDICATED, ALL WALLS SHALL BE P0A3.
1 A4.1.5
ALL WALLS OF OFFICES, CLASSROOMS, TEACHING SPACES, LABS, EXAM ROOMS, AND CONFERENCE/DEBRIEF ROOMS TO BE INSULATED AND ACOUSTICALLY SEALED. ALL J-BOXES AND OTHER SERVICE BOXES SHALL BE OFFSET NO LESS THAN 0' - 6".
P0H3
TRASH/RECYCLING
4E3
422
1 / A2.2.4C
FEC
1
MDF
A4.1.6
8' - 5 1/4"
38
30-SEAT CLASSROOM
A4.1.4
423
22 A8.4.2
5
32' - 7 5/8"
5
4.8
423 422
1 / A2.2.4A
4.8
4C4A
1 / A2.2.4C
ELEV 3
2
11' - 4"
3' - 0"
7' - 3"
3' - 0"
7' - 3"
3' - 0"
7' - 2"
A4.3.7
5.5
2' - 6"
4C1B
P0A3A
45 A9.6.3
2' - 6"
OPEN COLLABORATION 4C1C A8.4.2
10' - 4 1/8"
2' - 5 7/8"
OFFICE
OFFICE
403W
403M
403W
403M 403N
403V
OFFICE P0A3A
OFFICE 403T
403Q
403T
403S
403R
403S
OFFICE
6' - 3 3/4 "
P0A3A
403H
10' - 5 3/8"
10' - 5 3/8"
OFFICE
402A
401U
401D
OFFICE
OFFICE
402N
402B
401U
402A
OFFICE
OFFICE
401T
401E
402B
401T
401E
402M
402C
401S
401F
OFFICE
P0A3A
P0A3A
P0A3A
OFFICE
OFFICE
OFFICE
TURNER
402C
401S
401F
OFFICE
OFFICE
OFFICE
OFFICE
402L
402D
401R
401G
402D
401R
401G
403F
402K
402E
401Q
401H
403F
402K
P0A3A
OFFICE
OFFICE
P0A6A
402E
401Q
P0A3A
OFFICE 401H
FEC
P0A3A
P0A3A
OFFICE 402J
OFFICE 402F
P0A3A
31 8
402F
402H
402G
OFFICE
OFFICE
402H
402G
A4.1.5
95 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT
A4.3.8
32
SEALS AND SIGNATURES
JAMES C. MENEFEE 20610
10
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
OFFICE
401P
401J
01/29/2021
401J KEYPLAN
OFFICE
OFFICE
401N
401K
401N
401K
401M
401L
OFFICE
OFFICE
401M
401L P0A3A
2
33
B
3 1
2
A7.2.7
A4.3.1
NORTH
41
A4.3.1
Author
19 MAR 2021 23 OCT 2020
A4.1.6
401P
P0A3A
A4.3.8
4 A4.3.2
SHEET TITLE
4/7/2021 10:50:20 AM
FLOOR PLAN - LEVEL 4 AREA B
51 G
CC
G.4
G.5
G.6
H
H.3
H.4
H.6
J
J.9
K
12287.000 PROJECT NUMBER
Plot Date:
DATE
10' - 8"
402J
REV
9
1
P0A3A
1 / A2.2.4A
2
P0A3A
OFFICE
4' - 8" 24' - 0"
AV-IT-SECURITY
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
1
402L
OFFICE
DATACOM DESIGN GROUP
401
403E
OFFICE
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
FACULTY OFFICES
P0A3A
A8.4.2
403E
403G
REFER TO A5.1.X FOR BASEMENT WATERPROOFING INFORMATION.
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
ISSUED FOR
402N
OFFICE
OFFICE
J.
SMITHGROUP
401D
OFFICE
74
11' - 5"
5' - 6 1/2"
OFFICE
403C
P0A3A
P0A3A
P0A3A
P0A3A
OFFICE
OFFICE
402M
10' - 6 1/2"
.0° 80
P0A3A
P0A3A
2' - 1 1/4"
41
401C
10' - 6 1/2"
402P
403D
403G
403R
OFFICE
403B
403I
403Q
OFFICE
402P
10' - 7 1/4"
OFFICE
403H
OFFICE
P0A3A
403B
403D
72
OFFICE
401B
P0A3A
P0A3A
P0A3A
OFFICE
401A
P0A3
403C
403P
403U
OFFICE
P0A3A
403I
OFFICE
OFFICE
OFFICE
7
P0A3A
OFFICE 403K
11' - 3"
403P
403U
A8.4.2
P0A3A
403N
P0A3A
10' - 6 1/2"
P0A3A
P0A3A
403K
OFFICE
403V
9
OFFICE
11' - 5"
8
11' - 3 3/8"
P0A3A
6' - 4 1/4"
FEC
P0A6A
10' - 9 5/8"
P0A3A
5' - 10 3/4"
7' - 8 1/2"
REFER TO AND COORDINATE WITH CIVIL, STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL, AND COMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DRAWING.
SIM
40 A9.3.3
5' - 2 7/8"
10' - 8"
403L
403A
10' - 8"
10' - 8"
10' - 5 1/2"
I.
21' - 4"
5' - 6"
P0A3
10' - 5 1/2"
P0A3A
OFFICE
402
P0F3A
P0A3A
P0A3A
403L
10' - 8"
10' - 8"
COPY/ OFFICE SUPPORT
REFER TO THE 'AI' SERIES SHEETS FOR INTERIOR FURNISHING INFORMATION.
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
5' - 5 1/4"
403
H.
10' - 8"
4E1
10' - 8"
10' - 8"
ELEC.
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
401C
MAILROOM ELEV 1
19
22' - 7 1/2"
401B
10' - 8"
401A
7
14' - 5 7/8"
401AA
6' - 0 1/8"
403
8' - 10 1/2"
G.
JQ ENGINEERING
31' - 11"
72 A7.2.11
403A
4C1D
6
18 A6.1.1
REFER TO THE A9.3.X SERIES SHEETS FOR THE INTERIOR OPENING SCHEDULE(S), TYPES, AND DETAILS.
PACHEKO KOCH
72 A5.2.7
54 A5.2.7
F.
501 W. MITCHELL ARLINGTON, TX 76010
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
OPEN COLLABORATION
48
6
A4.1.2
4
P0A3A 7' - 3"
ALL COLUMNS TO BE EXPOSED UNLESS OTHERWISE NOTED. REF SPECS FOR EXPOSED CONCRETE FINISH INFORMATION.
17
24 A9.6.3
A4.1.3
E.
ACADEMIC BUILDING FOR SSW & CoNHI
1
LEVEL 4 - FLOOR PLAN AREA B SCALE: 1/8" = 1'-0"
1 A4.1.5
CD
SHEET NUMBER
A2.2.4B
GENERAL SHEET NOTES
1 A4.1.5
H
H.3
H.5
J
J.1
J.3
K
45 A6.1.4
1 A4.3.6
21
4 A4.3.6
DN
FOR BASIC LIFE SAFETY AND CODE INFORMATION APPLYING TO THIS PROJECT, REFER TO THE G2.X SERIES SHEETS LOCATED PER THE PROJECT SHEET INDEX.
C.
REFER TO THE A3.X SERIES SHEETS FOR THE REFLECTED CEILING PLANS.
D.
REFER TO THE A9.2.X SERIES SHEETS FOR PARTITION SYSTEMS TYPES AND DETAILS. UNLESS OTHERWISE INDICATED, ALL WALLS SHALL BE P0A3.
STAIR 4 DISTANCE ED TRAINING ROOM
3 A4.3.6
1 A4.3.7
432
2
FEC
P0H3
8' - 0"
P0A3A
9' - 1 7/8"
P0F3
F.
REFER TO THE A9.3.X SERIES SHEETS FOR THE INTERIOR OPENING SCHEDULE(S), TYPES, AND DETAILS.
G.
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
H.
REFER TO THE 'AI' SERIES SHEETS FOR INTERIOR FURNISHING INFORMATION.
I.
REFER TO AND COORDINATE WITH CIVIL, STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL, AND COMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DRAWING. REFER TO A5.1.X FOR BASEMENT WATERPROOFING INFORMATION.
501 W. MITCHELL ARLINGTON, TX 76010
SMITHGROUP
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
PACHEKO KOCH
431
5' - 4"
1.9
4S4
COLLABORATION
ALL COLUMNS TO BE EXPOSED UNLESS OTHERWISE NOTED. REF SPECS FOR EXPOSED CONCRETE FINISH INFORMATION.
ACADEMIC BUILDING FOR SSW & CoNHI
TURNER
2 A4.3.6
E.
J.
4S4
4 A9.6.8
2
B.
1
6' - 8 3/4"
1
1.9
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
ALL WALLS OF OFFICES, CLASSROOMS, TEACHING SPACES, LABS, EXAM ROOMS, AND CONFERENCE/DEBRIEF ROOMS TO BE INSULATED AND ACOUSTICALLY SEALED. ALL J-BOXES AND OTHER SERVICE BOXES SHALL BE OFFSET NO LESS THAN 0' - 6".
CC
21
A.
P0H3
432
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
JQ ENGINEERING
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
2' - 8"
429 P0F3
6' - 0"
DATACOM DESIGN GROUP AV-IT-SECURITY
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
6' - 0" 4' - 4" 1' -
8"
P0A3A
30-SEAT CLASSROOM 30-SEAT CLASSROOM
69
4' - 8"
429
430
66
A8.4.2
427B
CORRIDOR 4C3
30-SEAT CLASSROOM
40 A7.1.2
426A
426B
426C
426D
426E
EJ, INPRO 502-A01-100
428
3 A4.3.7
WOMEN
EJ, INPRO 502-A01-100
426
3.8
421
EJ AT CURTAIN WALL
GENDER NEUTRAL RESTROOM
4
ELEC 425
420
A8.4.2
30-SEAT CLASSROOM
A4.1.4
4S3
14
64 A6.1.3
70 A7.2.9
4S3
TRASH/RECYCLING 4C4A
MDF
4E3
422
P0A3A 424
01/29/2021
P0H3
1 / A2.2.4B 423 422
4.8
ELEV 3
FEC
1 / A2.2.4B
424
STAIR 3
8' - 5 1/4"
JAMES C. MENEFEE 20610
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
67
CORRIDOR 4C4
19 MAR 2021 23 OCT 2020
SEALS AND SIGNATURES
425
420
95 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT
EJ ON WALL, INPRO 114-A07-075, IN OFF-WHITE
21 A7.1.1
A9.6.5
DATE
4C3A
3.9
69
REV
A4.3.7
421
4
ISSUED FOR
2
427A
427C
427
CONFERENCE
3.8
3
MEN
RR VESTIBULE
69 A5.2.6
428 P0A3A
8' - 8"
3
1' - 6"
8' - 8" 6' - 0" 2' - 8"
4' - 11 3/4"
5' - 4"
5' - 4"
430
KEYPLAN
NORTH
4.8
2' - 1 3/4"
Author
C
4/7/2021 10:50:28 AM
CC
H.3
J
1
K
SHEET TITLE
FLOOR PLAN - LEVEL 4 AREA C
A4.1.5
1 Plot Date:
H
LEVEL 4 - FLOOR PLAN AREA C SCALE: 1/8" = 1'-0"
12287.000 PROJECT NUMBER
CD
SHEET NUMBER
A2.2.4C
8' - 11 5/8" 4' - 0" MIN CLR
8' - 5 1/4" 8' - 5 1/4"
2' - 7 1/16"EQ
GENERAL SHEET NOTES
8' - 11 5/8" 4' - 0" MIN CLR
EQ2' - 7 1/16"
BPG W/ GRAPHIC
A7.1.1 2' - 10"
TA-2
TA-2
EQ
EQ
EQ
113
COAT HOOKS ON INSIDE OF DOOR, REF. SPECS
TA-2 ALIGN
61
3' - 5 5/8"
112
3' - 5 5/8" 4' - 3 1/4"
2' - 10"
1' - 10"
EQ
COUNTER OPENING TO HAVE METAL TRIM RING: BOBRICK B-532
P0A3
P0A3
P0C2A
66
SCALE: 3/8" = 1'-0"
42
REF: 27 / A7.1.1
ELEVATION AT WOMENS RESTROOM WEST SCALE: 3/8" = 1'-0"
21X
TA-9
C L
EQ. TO OPP SIDE
3' - 6 5/8"
EQ
REFER TO THE A0.X SERIES SHEETS FOR TYPICAL TOILET ROOM MOUNTING HEIGHTS AND STALL CONFIGURATION DIAGRAMS.
E.
PROVIDE TYPE 'A' BACKING PLATES FOR ALL SURFACE MOUNTED TOILET ACCESSORIES. REFER TO BACKING PLATE SCHEDULE IN THE A9.X.X SERIES SHEETS FOR INSTALLATION REQUIREMENTS.
1' - 0 5/8"
ACADEMIC BUILDING FOR SSW & CoNHI
TA-2
P0F2 TA-9
SMITHGROUP
8
TOILET ACCESSORIES LEGEND Type Mark
2' - 1 7/8"
13' - 2 1/4"
TA-1 TA-2 TA-3 TA-4
P0F3A
TA-5 TA-6 TA-8 TA-9 TA-10
REF: 1 / A2.2.1A
Description Sidewall and Rear Wall Grab Bars Glass Mirror with Stainless Steel Angle Frame Sidewall and Rear Wall Grab Bars Bobrick B-221 Classic Series Surface Mounted Seat Cover Dispenser BABY CHANGING STATION Sensor Activated Electronic Soap Dispenser BOBRICK B2892 TOILET TISSUE DISPENSER ADA Compliant Recess Kit BOBRICK B-279, WASTE RECEPTACLE
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
TURNER
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
PACHEKO KOCH
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
CT-1 2' - 0"
D.
TA-2
MEN'S AND WOMEN'S RESTROOM TYPICAL SCALE: 1/4" = 1'-0"
REFER TO THE LIFE SAFETY PLANS IN THE G2.X SERIES SHEETS FOR FIRE RESISTIVE CONSTRUCTION REQUIREMENTS.
501 W. MITCHELL ARLINGTON, TX 76010
26' - 4 1/2"
27
C.
TA-2 9' - 0"
112C
4' - 8 3/4"
5'-2" CLR MIN
P0C2A
2' - 10"
66
112D
5' - 2'' CLR MIN
REF: 27 / A7.1.1
A7.1.1
P0F2A
2' - 11 3/8"
ELEVATION AT MENS RESTROOM WEST
113B
REFER TO AND COORDINATE WITH STRUCTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS SHEET.
EQ
29
A7.1.1 21X
112B
4' - 0" CLR MIN FROM FINISH FACE
TA-1 TA-8 29Sim
112
A7.1.1
3' - 4 1/2"
P0A2
Sim
STOOL (OFOI)
42 TA-8
TA-8
P0A2 4' - 0" MIN CLR FROM FINISH FACE
B.
2' - 10"
P0F3
113A
TA-2
112B
P0A2
A7.2.2
Sim
EQ
TA-8
P0F2
WOMEN
5' - 6'' MIN CLR FROM FINISH FACE
PTB-2
69
A7.1.1
112A
2 EQ IN 6' - 7 1/4''
EQ
P0A2
P0F3
TA-9
TA-2
66
EQ. TO OPP SIDE
2' - 10" MAX AFF
2' - 10" MAX AFF
TA-2 EQ. TO OPP SIDE
5 1/2"
A9.6.1
TA-6
P0A3
113
SIM
23
TA-9
MEN
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
TA-9 ALIGN
TA-9
7
A.
8' - 10 1/8"
BACK PAINTED GLASS WITH CUSTOM GRAPHIC
2' - 0"
JQ ENGINEERING
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
DATACOM DESIGN GROUP AV-IT-SECURITY
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
TA-4
TA-8
40Sim
TA-1
TA-10
Sim
TA-1
56
A7.1.1 64
TERRAZZO BASE (TZB) ISSUED FOR
PAINTED GYPSUM BOARD
69
ELEVATION AT MENS RESTROOM EAST SCALE: 3/8" = 1'-0"
61
REF: 27 / A7.1.1
ELEVATION AT DRINKING FOUNTAINS SCALE: 3/8" = 1'-0"
29
REF: 27 / A7.1.1
RESTROOM ELEVATION SCALE: 3/8" = 1'-0"
RESTROOM ELEVATION
21X
REF: 27 / A7.1.1
SCALE: 3/8" = 1'-0"
21
REF: 27 / A7.1.1
REV
DATE
LEVEL 3 - GENDER NEUTRAL RESTROOM NORTH SCALE: 1/4" = 1'-0"
REF: 1 / A2.2.3C
1' - 9"
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT
ALIGN
GENDER NEUTRAL RESTROOM
229
TA-2
SEALS AND SIGNATURES
229 4' - 0"
TA-4
30
A7.1.1
JAMES C. MENEFEE 20610
54
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
38 TA-9
TA-5
2' - 5"
3' - 4 1/4"
TA-1
TA-10
70
ELEVATION AT STAIR ENTRY & TRASH/RECYCLING TYPICAL
54
SCALE: 3/8" = 1'-0"
ELEVATION AT GENDER NEUTRAL EAST SCALE: 3/8" = 1'-0"
38
REF: 22 / A7.1.1
01/29/2021
TA-8
PTB-2
ELEVATION AT GENDER NEUTRAL SOUTH SCALE: 3/8" = 1'-0"
REF: 22 / A7.1.1
30
ELEVATION AT GENDER NEUTRAL WEST SCALE: 3/8" = 1'-0"
22
REF: 22 / A7.1.1
ALIGN
GENDER NEUTRAL RESTROOM TYPICAL SCALE: 1/4" = 1'-0"
NORTH
REF: 50 / A1.2.1
CAFE SUPPORT
START Sheet
106A
GENDER NEUTRAL RESTROOM
TA-2 TA-10
ENLARGED PLAN & ELEVATIONS - RESTROOM
A7.1.1
56
1C1A
2' - 10"
4/7/2021 10:50:47 AM
32
TA-9
SHEET TITLE
40
1C1B
TA-9
TA-5 TA-8
PTB-2
12287.000
TA-5
Plot Date:
19 MAR 2021 29 JAN 2021 23 OCT 2020
64
ELEVATION SOUTH SCALE: 3/8" = 1'-0"
REF: 21 / A7.1.1
56
ELEVATION EAST SCALE: 3/8" = 1'-0"
REF: 21 / A7.1.1
40
ELEVATION NORTH SCALE: 3/8" = 1'-0"
REF: 21 / A7.1.1
32
ELEVATION WEST SCALE: 3/8" = 1'-0"
REF: 24 / A7.1.1
24
LEVEL 1 - GENDER NEUTRAL RESTROOM WEST SCALE: 1/4" = 1'-0"
REF: 1 / A2.2.1A
PROJECT NUMBER
CD
SHEET NUMBER
A7.1.1
GENERAL SHEET NOTES
3.8
A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
REFER TO AND COORDINATE WITH STRUCTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS SHEET.
C.
REFER TO THE LIFE SAFETY PLANS IN THE G2.X SERIES SHEETS FOR FIRE RESISTIVE CONSTRUCTION REQUIREMENTS.
D.
REFER TO THE A0.X SERIES SHEETS FOR TYPICAL TOILET ROOM MOUNTING HEIGHTS AND STALL CONFIGURATION DIAGRAMS.
E.
PROVIDE TYPE 'A' BACKING PLATES FOR ALL SURFACE MOUNTED TOILET ACCESSORIES. REFER TO BACKING PLATE SCHEDULE IN THE A9.X.X SERIES SHEETS FOR INSTALLATION REQUIREMENTS.
CT-1 2' - 0"
3' - 0 1/2"
5' - 6 3/8"
BACK PAINTED GLASS WITH CUSTOM GRAPHIC
2' - 0"
ACADEMIC BUILDING FOR SSW & CoNHI 501 W. MITCHELL ARLINGTON, TX 76010
TERRAZZO BASE (TZB)
PAINTED GYPSUM BOARD
18
WALL EJ COVER
SMITHGROUP
LEVEL 01 - NORTH RESTROOM FOUNTAIN ELEVATION SCALE: 3/8" = 1'-0"
REF: 24 / A7.1.2
TOILET ACCESSORIES LEGEND Type Mark 8' - 5 1/4" 6' - 3 1/2"
8' - 10 3/4" 3' - 9"
EQ
EQ
2' - 3 1/2"
TA-1 TA-2 TA-3 TA-4
8' - 5 1/4" 4' - 0" MIN CLR
A7.1.1 61Sim
5' - 4 3/4"
7
5' - 2" MIN CLR
PACHEKO KOCH
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
JQ ENGINEERING
3' - 4 3/4"
DATACOM DESIGN GROUP AV-IT-SECURITY
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
2' - 6" 2' - 6"
66
48'' MIN CLR EQ
8
ISSUED FOR
REV
D
REF: 1 / A2.2.2A
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS
5' - 4 3/4"
4/7/2021 10:50:58 AM
EQ
2' - 8 1/2"
2' - 8 1/2"
EQ
2' - 10 1/8"
2' - 8"
2' - 8"
2' - 1"
ALIGN
4' - 1 1/8"
EQ 10 1/8"
ALIGN
A7.1.1
3.8
5' - 0'' MIN CLR FROM FINISH FACE
2' - 1 3/8"
WALL EJ COVER
SHEET TITLE WALL EJ COVER
6' - 1 5/8"
2' - 10"
EQ
2' - 8 1/2"
2' - 8 1/2"
EQ
3' - 3"
P0C2 4' - 1 3/4"
01/29/2021
5' - 2'' MIN CLR
2' - 4 1/4"
127A
1' - 10"
8' - 9 1/2"
EQ TO OPP SIDE
EQ
9' - 2 3/4"
5' - 10 1/4"
4
ENLARGED PLANS RESTROOMS
133A
H
H.3 H
Plot Date:
42Sim
66Sim
66Sim
WALL EJ COVER EQ
5'' - 6'' MIN CLR FROM FINISH FACE
69Sim
3.8 WALL EJ COVER
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
NORTH
FEC
WALL EJ COVER
JAMES C. MENEFEE 20610
EQ
Sim 4' - 0"
222
3' - 0"
18
EJ
222A
2' - 2 7/8"
WOMEN
A7.1.1
A7.1.1
4' - 4 1/16"
A7.1.1
ALIGN
5' - 2" CLR MIN
2 EQ IN 5' - 7 3/8"
3.8 WALL EJ COVER
A7.1.2
42Sim
4' - 0'' MIN CLR
Author
4' - 1 3/8"
9' - 0 1/2"
EQ TO OPP SIDE
3' - 9 3/4"
13' - 1"
6' - 0" MIN CLR
5' - 2" MIN CLR
2' - 4 7/8"
61
2 EQ IN 6' - 0 5/8"
4' - 6 3/4"
2' - 4 7/16"
37
5' - 6" CLR MIN
SEALS AND SIGNATURES
3' - 3"
10 1/8" 5' - 0'' MIN CLR
EQ TO OPP SIDE
9" 9"
61
EQ
66Sim
2' - 4 9/16"
3 5/16"
Sim
A7.2.1
2' - 8 1/2"
P0C2
4' - 0 3/4"
223
3
5' - 2" CLR MIN
5' - 2'' MIMN CLR
6' - 0" MIN CLR
MEN
A7.1.1 66Sim
2' - 8 1/2"
8' - 6 7/8"
13' - 1 5/8"
227
EQ
19 MAR 2021 29 JAN 2021
5' - 10"
11' - 10 1/8"
48'' MIN CLR
CONFERENCE
42Sim
3' - 6 1/8"
EQ
8' - 2 7/16"
C
3
Sim
8' - 0 1/8"
A7.1.1
4' - 0" MIN CLR
4' - 2 1/8"
3' - 4 1/2"
2' - 4 7/8"
9' - 1 3/8"
2 EQ IN 5' - 11 7/8"
4' - 2"
2' - 8"
128A
1' - 11 1/8"
2' - 8"
1' - 3 1/2"
2' - 8 1/2"
13' - 1 5/8"
2' - 8 1/2"
1' - 3 1/2"
2' - 1 1/8"
9' - 2 3/4"
EQ
8' - 11"
2' - 10 1/8"
8' - 11 3/16"
3' - 3"
2' - 4 1/2"
9' - 10 1/2"
ALIGN
2' - 9 7/8"
4' - 0 5/8"
3' - 7 1/2"
FEC
3 1/2"
2' - 6 1/8"
DATE
5' - 2" MIN CLR
LEVEL 3 - RESTROOMS WEST SCALE: 1/4" = 1'-0"
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
3' - 0 3/4"
A7.1.1
A7.1.1
Sim OH
Sim Sim
Sim OH
21X
A7.1.1 21X
Sidewall and Rear Wall Grab Bars Glass Mirror with Stainless Steel Angle Frame Sidewall and Rear Wall Grab Bars Bobrick B-221 Classic Series Surface Mounted Seat Cover Dispenser BABY CHANGING STATION Sensor Activated Electronic Soap Dispenser BOBRICK B2892 TOILET TISSUE DISPENSER ADA Compliant Recess Kit BOBRICK B-279, WASTE RECEPTACLE
TURNER
EQ
2 EQ IN 6' - 6 1/2''
29Sim
29Sim OH
5' - 6'' MIN CLR
EQ
48'' MIN CLR
20
42
3' - 4 1/2"
69
5' - 6" MIN CLR
Sim
Sim
EQ 2' - 8"
A7.1.1
2' - 8"
9' - 0"
66
TA-5 TA-6 TA-8 TA-9 TA-10
Description
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
64
LEVEL 3 - M/W RESTROOM NORTH SCALE: 1/4" = 1'-0"
REF: 1 / A2.2.3C
40
H.3
LEVEL 2 - M/W RESTROOMS NORTH SCALE: 1/4" = 1'-0"
H
REF: 50 / A1.2.1
H.3
12287.000 PROJECT NUMBER
24
LEVEL 1 - M/W RESTROOM NORTH SCALE: 1/4" = 1'-0"
REF: 22 / A1.2.1
CD
SHEET NUMBER
A7.1.2
A8.3.1 68
4.8 35 GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
EQ
EQ
EQ
EQ
EQ
EQ
EQ
EQ
GL-1
A7.1.4
ACADEMIC BUILDING FOR SSW & CoNHI
11 EQ
A7.1.5
5
501 W. MITCHELL ARLINGTON, TX 76010
GL-1
GL-1
GL-1
GL-1
EQ
EQ
2' - 7 3/4"
EQ
EQ
EQ
PORTION OF GLAZED WALL AT LANDING TO BE MOVING GLASS WALL SYSTEM
SMITHGROUP
A7.1.3
36 27
A7.1.5
63. 6°
26.4°
A9.6.2
5.5
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
JQ ENGINEERING
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098 AV-IT-SECURITY
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
9' - 0" 3 EQ TREADS @ 36''
15' - 6"
DATACOM DESIGN GROUP
10' - 0" 10 EQ TREADS @ 12''
2' - 8 3/4"
LEVEL 2 EL +118' - 0"
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
PACHEKO KOCH
IS THERE A TYPICAL FOR THE FIXED SEATING?
PORTION OF GLAZED WALL AT LANDING TO BE MOVING GLASS WALL SYSTEM
ELEVATION
6
SCALE: 3/8" = 1'-0"
A7.1.4 37
27' - 11 5/8" OVERALL CLR LENGTH
ISSUED FOR
REV
DATE
7
300A
7
7' - 4 1/2"
5' - 8 3/8" CLR TREAD WIDTH
8' - 5"
36
7' - 0" LANDING DEPTH
109 .4°
SIM
5' - 0" LANDING DEPTH
GYP FINISH 72
TURNER
35' - 0" OVRALL CLR LENGTH
1" 1' -
27 A7.1.5
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
31' - 0" OVERALL CLR LENGTH
GL-1
15' - 0" 5 EQ TREADS @ 36''
GL-1
20' - 0" 20 TREADS @ 12''
LEVEL 3 EL +134' - 0"
67
67
70
72
A7.1.5
A7.1.3
A7.1.3
A7.1.5
J.9 32
TIERED CLASSROOM ENLARGED PLAN - LEVEL 3
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS
SCALE: 1/4" = 1'-0"
19 MAR 2021 29 JAN 2021
SEALS AND SIGNATURES
6 7
6
5.5
5
5.5
5
4.8
JAMES C. MENEFEE 20610
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
4.8
01/23/21 GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1 NORTH
COMPOUND CEILING GYP
P0A3A GL-1
LEVEL 3 EL +134' - 0"
+ 13' - 0" GL-1
GL-1
GL-1
6' - 0" 6 EQ RISERS
5' - 6" 10 EQ RISERS
LEVEL 3 EL +134' - 0"
GL-1
DO WE NEED THIS?
8' - 9" 5 EQ RISERS
10' - 0" 21 EQ RISERS
Author
GL-1
27
Plot Date:
4/7/2021 10:54:28 AM
A7.1.5
7' - 0"
SHEET TITLE
11 A7.1.5 LEVEL 2 EL +118' - 0"
67
SECTION - TEIRED CLASSROOM STAIRS SCALE: 1/4" = 1'-0"
LEVEL 2 EL +118' - 0"
70
TIERED CLASSROOM ENLARGED PLAN & SECTIONS
SECTION - TIERED CLASSROOM SEATING SCALE: 1/4" = 1'-0"
12287.000 PROJECT NUMBER
CD
SHEET NUMBER
A7.1.3
GENERAL SHEET NOTES 6
5.7
5.5
A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
FOR BASIC LIFE SAFETY AND CODE INFORMATION APPLYING TO THIS PROJECT, REFER TO THE G2.X SERIES SHEETS LOCATED PER THE PROJECT SHEET INDEX.
C.
REFER TO AND COORDINATE WITH STRUCTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS SHEET.
D.
REFER TO THE LIFE SAFETY PLANS IN THE G2.X SERIES SHEETS FOR FIRE RESISTIVE CONSTRUCTION REQUIREMENTS.
E.
REFER TO A9.6.1 FOR MILLWORK TAG LEGEND
F.
ADD FRY REGLET TRIM, WCTBT125-217 IN POWDER COATED WHITE, TO ALL EXPOSED EDGES OF PL-3
5 PROJECTOR SCREEN - REF AVI
67
A7.1.5
P0H3
P0P2
LEVEL 3 EL +134' - 0"
7' - 0"
ACADEMIC BUILDING FOR SSW & CoNHI 501 W. MITCHELL ARLINGTON, TX 76010
7' - 6 3/4"
SMITHGROUP
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com LEVEL 2 EL +118' - 0"
BPG-1 BACK PAINTED GLASS
TURNER
BPG-1 BACKPAINTED GLASS
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
PACHEKO KOCH
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
60
ENLARGED ELEVATION - TIERED CLASSROOM EXTERIOR GLAZING SCALE: 1/4" = 1'-0"
REF: 2 / A4.1.2
35
JQ ENGINEERING
ELEVATION - TIERED CLASSROOM NORTH SCALE: 3/8" = 1'-0"
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
REF: 1 / A2.2.2B
DATACOM DESIGN GROUP AV-IT-SECURITY
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443 OPERBLE PARTITION DOOR
15' - 10 7/8"
FPD, REF AVI ISSUED FOR
DATE
4' - 0"
REV
37
ELEVATION - TIERED CLASSROOM TOP LANDING SCALE: 3/8" = 1'-0"
REF: 32 / A7.1.3
67
A7.1.5
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS
19 MAR 2021 29 JAN 2021
SEALS AND SIGNATURES
JAMES C. MENEFEE 20610
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION 02/04/21
Author
NORTH
SHEET TITLE
4/7/2021 10:57:26 AM
TIERED CLASSROOM ELEVATIONS
Plot Date:
1
{3D - vincent.tiburcio-ochoa} Copy 1 SCALE:
12287.000 PROJECT NUMBER
CD
SHEET NUMBER
A7.1.4
6
5.5
5
4.8 3/4'' SOLID HARDWOOD CAP - SPECIES TO MATCH VERTICAL VENEER
CARPET TILE
1/4'' X 1/4'' ROUTED REVEAL
J
3/8'' THICK TERRAZZO TREAD
24 A7.1.5
PAINTED TUBE STEEL STAIR STRINGER, #6 SATIN FINISH. REF. TO STRUCTURAL FOR ADDITIONAL INFORMATION 2'' X 5.375'' RECTANGULAR MULLION
LEVEL 3 EL +134' - 0"
CONT. STEEL ANGLE FULL LENGTH OF WALL
SHOULD I MATCH FRANK'S MATERIAL THICKNESS?
ACADEMIC BUILDING FOR SSW & CoNHI
3/4'' PLYWOOD W/ HARDWOOD VENEER ON ALL EXPOSED EDGES
501 W. MITCHELL ARLINGTON, TX 76010
3/4'' SOLID HARDWOOD BASE - SPECIES TO MATCH VERTICAL VENEER
12" O.C. HORIZONTAL FRAMING
5' - 8"
METAL STUD BOX BEAM HEADER AT OPENING
SMITHGROUP
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
39 A7.1.5
11 27 67
TURNER
FINISHED FLOOR LINE
PACHEKO KOCH
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
4"
LEVEL 2 EL +118' - 0"
3/4'' SOLID HARDWOOD BASE - SPECIES TO MATCH VERTICAL VENEER
Section 97
HALF HEIGHT WALL SCALE: 1" = 1'-0"
JQ ENGINEERING
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
REF: 32 / A7.1.3
REF: 32 / A7.1.3
SCALE: 1" = 1'-0"
DATACOM DESIGN GROUP AV-IT-SECURITY
STAIRS CONNECTION DETAIL SCALE: 1/4" = 1'-0"
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
REF: 32 / A7.1.3
REV
ISSUED FOR
5.5
4 A4.3.7
LEVEL 3 EL +134' - 0"
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS
J
67 A7.1.5
STRUCTURAL CONCRETE BEAM
P0A3 GYPSUM WALL
3 5/8'' COLD FORMED STEEL STUD
JAMES C. MENEFEE 20610
J FRY REGLET REVEAL
ALIGN
these diagonal studs would have to go all the way down, what is the max angled span?
19 MAR 2021 29 JAN 2021
SEALS AND SIGNATURES
HOLLOW STEEL SECTION PROVIDED BY STRUCTURAL 5/8'' GYPSUM WALLBOARD
DATE
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
8'' BOX BEAM
02/07/21
3/4'' PLYWOOD VENEER W/HARDWOOD ON ALL EXPOSED EDGES
5/8'' GYPSUM WALLBOARD 67
PROVIDE KICKERS AT EACH VERTICAL STUD
NORTH
A7.1.5
1' - 1"
STRUCTURAL TIERS BEYOND
4.8
4.8
Author
9 3/8"
SHEET TITLE
LEVEL 2 EL +118' - 0"
4/7/2021 10:57:42 AM
J 1
Plot Date:
72
SECTION - TIERED CLASSROOM SIDE RAILING SCALE: 1/2" = 1'-0"
REF: 40 / A5.3.22
LEVEL 2 AREA B - Callout 1 SCALE: 1/2" = 1'-0"
TIERED CLASSROOM PARTITION
67 A7.1.3
24
Section 97 - Callout 1 SCALE: 3" = 1'-0"
REF: 27 / A7.1.5
12287.000 PROJECT NUMBER
CD
SHEET NUMBER
A7.1.5
GENERAL SHEET NOTES
BUTT GLAZED WITH SEALANT JOINT, TYP.
A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
REFER TO AND COORDINATE WITH MECHANICAL, PLUMBING, AND ELECTRICAL FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS SHEET.
C.
THE PURPOSE OF THE DRAWINGS ON THIS SHEET IS TO ILLUSTRATE THE OVERALL CONFIGURATION OF ALL ITEMS OF ALL TRADES OCCURRING ON THE INTERIOR ELEVATIONS. LOCATIONS OF ELEMENTS SHOWN ON ELECTRICAL, MECHANICAL, AND PLUMBING DRAWINGS ARE SCHEMATIC AND THE DIMENSIONS SHOWN HERE TAKE PRECEDENCE.
D.
REFER TO THE A0.X SERIES SHEETS FOR TYPICAL MOUNTING HEIGHTS FOR DIMENSIONS NOT SHOWN ON THIS SHEET.
E.
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
F. FOR ALL CONTROL ROOM GLAZING REFER TO A7.X.X SHEETS
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
45
GL-1
GL-1
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
9' - 2"
GL-1
TURNER
SIM
A9.3.3
3 EQ IN 10' - 7 1/2''
ELEVATION
67
SCALE: 3/8" = 1'-0"
3' - 6" REF SCHED
6 EQ IN 17' - 0 1/2''
REF SCHED
2 EQ IN 5' - 8"
REF: 1 / A2.2.1A
ELEVATION
SCALE: 3/8" = 1'-0"
REF: 1 / A2.2.1A
2"
2' - 6"
4' - 10 1/2"
1' - 9"
27
2' - 6"
2"
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
PACHEKO KOCH
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
5' - 0"
8' - 10" FV
35
501 W. MITCHELL ARLINGTON, TX 76010
SMITHGROUP
SIM
A9.3.3
9' - 2"
9' - 2" TYP
45
ACADEMIC BUILDING FOR SSW & CoNHI
CLASSROOM ENTRY, TYP. SCALE: 3/8" = 1'-0"
JQ ENGINEERING
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
10' - 0"
DATACOM DESIGN GROUP
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
9' - 2"
GL-1
AV-IT-SECURITY
LEVEL 1 EL +100' - 0"
ELEVATION
69
SCALE: 3/8" = 1'-0"
8 EQ IN 24' - 11 3/4''
ISSUED FOR
9' - 5 1/2"
6 EQ IN 16' - 7''
REV
DATE
FROSTED GLASS BAND
GL-1
45
GL-1
GL-1
GL-1
SIM
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT 8' - 4 1/2"
GL-1
4' - 0"
9' - 2"
9' - 2" 4' - 0"
2"
REF: 1 / A2.2.1A
SEALS AND SIGNATURES
JAMES C. MENEFEE 20610
SIM
2' - 10"
2' - 10"
A9.3.3 45
A9.3.3
3' - 5"
48
REF SCHED
REF SCHED
6' - 7 1/16"
ELEVATION
SCALE: 3/8" = 1'-0"
REF: 1 / A2.2.1A
62
ELEVATION
SCALE: 3/8" = 1'-0"
13' - 8 7/16"
4 EQ IN 15' 4 7/8'' 18' - 2 1/2"
REF: 1 / A2.2.1A
FROSTED GLASS BAND
22
ELEVATION
SCALE: 3/8" = 1'-0"
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
REF: 1 / A2.2.1A
01/29/2021
4/7/2021 10:57:44 AM
11' - 4"
START Sheet
70
A7.2.3
19 MAR 2021 29 JAN 2021 23 OCT 2020
SHEET TITLE
FRAME ELEVATIONS LEVEL 1
12287.000 Plot Date:
PROJECT NUMBER
72
ELEVATION
SCALE: 3/8" = 1'-0"
REF: 1 / A2.2.1A
PORTION OF GLAZED WALL AT LANDING TO BE MOVING GLASS WALL SYSTEM
CD
SHEET NUMBER
A8.1.1
GENERAL SHEET NOTES
SIM GL-1
A9.3.3 GL-1
GL-1
GL-1
GL-1
9' - 2"
9' - 2"
45
GL-1
GL-1
GL-1
GL-1
GL-1
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
REFER TO AND COORDINATE WITH MECHANICAL, PLUMBING, AND ELECTRICAL FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS SHEET.
C.
THE PURPOSE OF THE DRAWINGS ON THIS SHEET IS TO ILLUSTRATE THE OVERALL CONFIGURATION OF ALL ITEMS OF ALL TRADES OCCURRING ON THE INTERIOR ELEVATIONS. LOCATIONS OF ELEMENTS SHOWN ON ELECTRICAL, MECHANICAL, AND PLUMBING DRAWINGS ARE SCHEMATIC AND THE DIMENSIONS SHOWN HERE TAKE PRECEDENCE.
D.
REFER TO THE A0.X SERIES SHEETS FOR TYPICAL MOUNTING HEIGHTS FOR DIMENSIONS NOT SHOWN ON THIS SHEET.
E.
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
F. FOR ALL CONTROL ROOM GLAZING REFER TO A7.X.X SHEETS
ACADEMIC BUILDING FOR SSW & CoNHI 501 W. MITCHELL ARLINGTON, TX 76010
4' - 0"
GL-1
FROSTED GLAZING FILM W/ CUSTOM GRAPHIC
A.
SIGNAGE UTA
SIGNAGE UTA
GL-1
SMITHGROUP 2' - 6"
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
BUTT-GLAZED CORNER 3 EQ IN 8' - 5"
REF SCHED
3 EQ IN 8' - 9"
REF SCHED
3 EQ IN 11' - 0"
4 EQ IN 12' 10 1/8''
TURNER
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
12' - 0"
42
ELEVATION
SCALE: 3/8" = 1'-0"
20
REF: 1 / A2.2.1B
ELEVATION
SCALE: 3/8" = 1'-0"
REF: 1 / A2.2.1C
PACHEKO KOCH
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
JQ ENGINEERING
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
DATACOM DESIGN GROUP AV-IT-SECURITY
GL-1
GL-1
GL-1
GL-1
GL-1
10' - 0"
GL-1
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
GL-1
LEVEL 2 EL +118' - 0"
G4
G4
G4
G4
G4
ISSUED FOR
7' - 0"
G4
G4
REV
DATE
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
7' - 8"
BACK PAINTED GLASS
11' - 0"
GL-1
REF DOOR SCHED
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT SEALS AND SIGNATURES
JAMES C. MENEFEE 20610
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
LEVEL 1 EL +100' - 0"
3 EQ IN 9' - 9 29/32"
16' - 5 5/8"
REF DOOR SCHED
2 EQ IN 8' - 7 19/32"
24' - 1" FV
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
4' - 0"
GL-1
9' - 2"
GL-1
Author
GL-1
01/29/2021
REF: 1 / A2.2.1A
9' - 2"
SCALE: 3/8" = 1'-0"
4' - 0"
ELEVATION
9' - 2"
70
19 MAR 2021 29 JAN 2021 23 OCT 2020
GL-1
Plot Date:
EQ
REF SCHED
EQ
2' - 6"
4/7/2021 10:57:52 AM
2' - 10"
SHEET TITLE
LEVEL 1 EL +100' - 0"
LEVEL 1 EL +100' - 0" 1' - 3 11/16"
REF SCHED
5' - 7 1/2"
4 EQ IN 13' - 7 7/8'' 17' - 11 9/16" FV
3' - 2"
REF SCHED
4 EQ IN 13' - 8 7/8"
FRAME ELEVATIONS LEVEL 1
3' - 9 7/16"
20' - 1 7/8" FV
FROSTED GLASS BAND
40
ELEVATION
SCALE: 3/8" = 1'-0"
REF: 1 / A2.2.1C
32
ELEVATION
SCALE: 3/8" = 1'-0"
22 REF: 1 / A2.2.1C
ELEVATION
SCALE: 3/8" = 1'-0"
REF: 1 / A2.2.1C
4
ELEVATION
SCALE: 3/8" = 1'-0"
12287.000 REF: 1 / A2.2.1C
PROJECT NUMBER
CD
SHEET NUMBER
A8.1.2
GENERAL SHEET NOTES A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
REFER TO AND COORDINATE WITH MECHANICAL, PLUMBING, AND ELECTRICAL FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS SHEET.
C.
THE PURPOSE OF THE DRAWINGS ON THIS SHEET IS TO ILLUSTRATE THE OVERALL CONFIGURATION OF ALL ITEMS OF ALL TRADES OCCURRING ON THE INTERIOR ELEVATIONS. LOCATIONS OF ELEMENTS SHOWN ON ELECTRICAL, MECHANICAL, AND PLUMBING DRAWINGS ARE SCHEMATIC AND THE DIMENSIONS SHOWN HERE TAKE PRECEDENCE.
D.
REFER TO THE A0.X SERIES SHEETS FOR TYPICAL MOUNTING HEIGHTS FOR DIMENSIONS NOT SHOWN ON THIS SHEET.
E.
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
F. FOR ALL CONTROL ROOM GLAZING REFER TO A7.X.X SHEETS
ACADEMIC BUILDING FOR SSW & CoNHI 501 W. MITCHELL ARLINGTON, TX 76010
SMITHGROUP
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
TURNER
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
PACHEKO KOCH
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
JQ ENGINEERING
GL-1
GL-1
GL-1
GL-1
45
SIM
GL-1
GL-1
GL-1
GL-1
9' - 2"
GL-1
9' - 2"
A9.3.3
9' - 2"
9' - 2"
45
SIM
45
SIM GL-1
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
A9.3.3
DATACOM DESIGN GROUP
GL-1
AV-IT-SECURITY
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
A9.3.3 45
SIM
A9.3.3
REF SCHED
60
5 EQ IN 17' - 0 1/8" 23' - 4 1/8" FV
ELEVATION
SCALE: 3/8" = 1'-0"
REF SCHED
9' - 0 165/256"
2 EQ IN 7' 4''
REF SCHED
REF SCHED
6' - 1"
12' - 3 165/256"
36
REF: 1 / A2.2.2A
ELEVATION
SCALE: 3/8" = 1'-0"
ELEVATION
28
REF: 1 / A2.2.2C
SCALE: 3/8" = 1'-0"
2' - 11"
12
REF: 1 / A2.2.2C
ELEVATION
SCALE: 3/8" = 1'-0"
REF: 1 / A2.2.2C ISSUED FOR
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
9' - 2"
GL-1
1' - 6"
GL-1
4' - 0"
9' - 2"
45 GL-1
GL-1
GL-1
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT
SIM GL-1
SIGNAGE UTA
45
GL-1
GL-1
GL-1
SIM
JAMES C. MENEFEE 20610
2' - 10"
3' - 0"
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
8 EQ IN 25' - 9 1/8"
3 EQ IN 9' - 2 3/8"
REF SCHED
REF SCHED
5 EQ IN 15' - 5 1/4''
12' - 4 3/8"
45
SIM
GL-1
GL-1
ELEVATION
SCALE: 3/8" = 1'-0"
GL-1
18' - 5 1/4"
01/29/2021
REF: 1 / A2.2.2A
GL-1
9' - 2" 4' - 0"
30
REF: 1 / A2.2.2A
9' - 2"
SCALE: 3/8" = 1'-0"
4' - 0"
ELEVATION
9' - 2"
Author
62
19 MAR 2021 29 JAN 2021 23 OCT 2020
GL-1
LEVEL 2 EL +118' - 0" REF SCHED
DATE
SEALS AND SIGNATURES
A9.3.3
A9.3.3
2 EQ IN 6' - 8 7/8"
REV
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
A9.3.3
FRAME ELEVATIONS LEVEL 2
2' - 10"
2' - 10"
4/7/2021 10:58:01 AM
SHEET TITLE
REF SCHED
1' - 5"
2 EQ 7' - 11 1/8'' 9' - 1 1/8"
REF SCHED
1' - 5" 2 EQ IN 4' - 11 3/8"
6' - 0"
4 EQ IN 13' - 11 1/2"
FROSTED GLASS BAND
12287.000
FROSTED GLASS BAND
Plot Date:
PROJECT NUMBER
48
OFFICES TYPICAL SCALE: 3/8" = 1'-0"
REF: 1 / A2.2.2A
32
ELEVATION
SCALE: 3/8" = 1'-0"
REF: 1 / A2.2.2A
24
ELEVATION
SCALE: 3/8" = 1'-0"
REF: 1 / A9.6.7
CD
SHEET NUMBER
A8.2.1
GENERAL SHEET NOTES A.
REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B.
REFER TO AND COORDINATE WITH MECHANICAL, PLUMBING, AND ELECTRICAL FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS SHEET.
C.
THE PURPOSE OF THE DRAWINGS ON THIS SHEET IS TO ILLUSTRATE THE OVERALL CONFIGURATION OF ALL ITEMS OF ALL TRADES OCCURRING ON THE INTERIOR ELEVATIONS. LOCATIONS OF ELEMENTS SHOWN ON ELECTRICAL, MECHANICAL, AND PLUMBING DRAWINGS ARE SCHEMATIC AND THE DIMENSIONS SHOWN HERE TAKE PRECEDENCE.
D.
REFER TO THE A0.X SERIES SHEETS FOR TYPICAL MOUNTING HEIGHTS FOR DIMENSIONS NOT SHOWN ON THIS SHEET.
E.
REFER TO THE 'AF' SERIES SHEETS FOR INTERIOR FINISH INFORMATION.
F. FOR ALL CONTROL ROOM GLAZING REFER TO A7.X.X SHEETS
ACADEMIC BUILDING FOR SSW & CoNHI 501 W. MITCHELL ARLINGTON, TX 76010
SMITHGROUP
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
TURNER
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
PACHEKO KOCH
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
JQ ENGINEERING
GL-1
GL-1
GL-1
GL-1
45
SIM
GL-1
GL-1
GL-1
GL-1
9' - 2"
GL-1
9' - 2"
A9.3.3
9' - 2"
9' - 2"
45
SIM
45
SIM GL-1
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
A9.3.3
DATACOM DESIGN GROUP
GL-1
AV-IT-SECURITY
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
A9.3.3 45
SIM
A9.3.3
REF SCHED
60
5 EQ IN 17' - 0 1/8" 23' - 4 1/8" FV
ELEVATION
SCALE: 3/8" = 1'-0"
REF SCHED
9' - 0 165/256"
2 EQ IN 7' 4''
REF SCHED
REF SCHED
6' - 1"
12' - 3 165/256"
36
REF: 1 / A2.2.2A
ELEVATION
SCALE: 3/8" = 1'-0"
ELEVATION
28
REF: 1 / A2.2.2C
SCALE: 3/8" = 1'-0"
2' - 11"
12
REF: 1 / A2.2.2C
ELEVATION
SCALE: 3/8" = 1'-0"
REF: 1 / A2.2.2C ISSUED FOR
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
9' - 2"
GL-1
1' - 6"
GL-1
4' - 0"
9' - 2"
45 GL-1
GL-1
GL-1
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS 100 PCT DESIGN DEVELOPMENT
SIM GL-1
SIGNAGE UTA
45
GL-1
GL-1
GL-1
SIM
JAMES C. MENEFEE 20610
2' - 10"
3' - 0"
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
8 EQ IN 25' - 9 1/8"
3 EQ IN 9' - 2 3/8"
REF SCHED
REF SCHED
5 EQ IN 15' - 5 1/4''
12' - 4 3/8"
45
SIM
GL-1
GL-1
ELEVATION
SCALE: 3/8" = 1'-0"
GL-1
18' - 5 1/4"
01/29/2021
REF: 1 / A2.2.2A
GL-1
9' - 2" 4' - 0"
30
REF: 1 / A2.2.2A
9' - 2"
SCALE: 3/8" = 1'-0"
4' - 0"
ELEVATION
9' - 2"
Author
62
19 MAR 2021 29 JAN 2021 23 OCT 2020
GL-1
LEVEL 2 EL +118' - 0" REF SCHED
DATE
SEALS AND SIGNATURES
A9.3.3
A9.3.3
2 EQ IN 6' - 8 7/8"
REV
GL-1
GL-1
GL-1
GL-1
GL-1
GL-1
A9.3.3
FRAME ELEVATIONS LEVEL 2
2' - 10"
2' - 10"
4/7/2021 10:58:01 AM
SHEET TITLE
REF SCHED
1' - 5"
2 EQ 7' - 11 1/8'' 9' - 1 1/8"
REF SCHED
1' - 5" 2 EQ IN 4' - 11 3/8"
6' - 0"
4 EQ IN 13' - 11 1/2"
FROSTED GLASS BAND
12287.000
FROSTED GLASS BAND
Plot Date:
PROJECT NUMBER
48
OFFICES TYPICAL SCALE: 3/8" = 1'-0"
REF: 1 / A2.2.2A
32
ELEVATION
SCALE: 3/8" = 1'-0"
REF: 1 / A2.2.2A
24
ELEVATION
SCALE: 3/8" = 1'-0"
REF: 1 / A9.6.7
CD
SHEET NUMBER
A8.2.1
ACADEMIC BUILDING FOR SSW & CoNHI 501 W. MITCHELL ARLINGTON, TX 76010
SMITHGROUP
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
TURNER
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
PACHEKO KOCH
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
JQ ENGINEERING
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
DATACOM DESIGN GROUP AV-IT-SECURITY
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
ISSUED FOR
REV
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS SCHEMATIC DESIGN
DATE
19 MAR 2021 29 JAN 2021 31 JULY 2020
SEALS AND SIGNATURES
JAMES C. MENEFEE 20610
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
Author
01/29/2021
SHEET TITLE
4/7/2021 12:55:16 PM
INTERIOR RENDERINGS
12287.000 Plot Date:
PROJECT NUMBER
CD
SHEET NUMBER
1 A9.9.2
ACADEMIC BUILDING FOR SSW & CoNHI 501 W. MITCHELL ARLINGTON, TX 76010
SMITHGROUP
LANDSCAPE ARCHITECTURE, ARCHITECTURE, INTERIOR DESIGN, MEP ENGINEERING 5910 N. CENTRAL EXPY SUITE #1765 DALLAS, TX, 75206 214.559.4851 www.smithgroup.com
TURNER
CONSTRUCTION 10100 N CENTRAL EXPY #600 DALLAS, TEXAS 75231 214.721.8400 www.turnerconstruction.com
PACHEKO KOCH
CIVIL ENGINEERING 7557 RAMBLER ROAD, SUITE 1400 DALLAS, TEXAS 75231 972.235.3031
JQ ENGINEERING
STRUCTURAL ENGINEERS 100 GLASS STREET DALLAS, TEXAS 75207 214.752.9098
DATACOM DESIGN GROUP AV-IT-SECURITY
300 N COIT RD. RICHARDSON, TEXAS 75080 214.221.5443
ISSUED FOR
REV
95 PCT CONSTRUCTION DOCUMENTS 50 PCT CONSTRUCTION DOCUMENTS SCHEMATIC DESIGN
DATE
19 MAR 2021 29 JAN 2021 31 JULY 2020
SEALS AND SIGNATURES
JAMES C. MENEFEE 20610
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION
Author
01/29/2021
SHEET TITLE
4/7/2021 12:55:16 PM
INTERIOR RENDERINGS
12287.000 Plot Date:
PROJECT NUMBER
CD
SHEET NUMBER
A9.9.2