AMBULATORY 2.0 2020
ENERGY PERFORMANCE STANDARD
Page / 1
Page / 2
Ambulatory 2.0 Energy Performance Standard
ENERGY PERFORMANCE STANDARD
Page / 3
Navigating the Standard 1 SUMMARY OF SCOPE
AND PROJECT GOALS Identifies the overarching considerations, measures and strategies that a healthcare institution can implement to reduce carbon emissions and achieve net zero. 8 / Intent and Application 10 / Net-Zero Definition 11 / Energy Use Overview 13 / Carbon Intensity
2 ENERGY PERFORMANCE
TARGETS Articulates a structure and approach for establishing ambitious EUI goals that can be measured and recalibrated throughout a facility’s design and lifecycle cost analysis. 18 / Framework 22 / Calculation Methodology
Page / 4
Ambulatory 2.0 Energy Performance Standard
3 ENERGY DESIGN GUIDELINES
Summarizes the specific ways that EUI goals can be prioritized and monitored during each phase of planning, design and construction. 26 / Conceptual Design 28 / Schematic Design 30 / Design Development 31 / Construction Documents
4 RECOMMENDED STRATEGIES
FOR COMPLIANCE Explores the optimum design process for achieving ambitious energy goals, with a focus on the interplay between architectural strategies and MEP analysis. 34 / Passive Design Strategies 38 / Building System Strategies 42 / Plug and Process Loads
5 PLANNING FOR
7 COMISSIONING OPR STANDARDS
46 / Feasibility Analysis
62 / Measurement and Verification
48 / On-Site Systems
63 / Envelope Commissioning
49 / Off-Site & Offsets
65 / Continuous Commissioning
RENEWAL ENERGY Provides a framework for assessing the viability and opportunity of on-site renewable strategies.
6 ENERGY MODEL STANDARD
Overview of the methodology behind energy modeling practice and prescribes best practices in application and reporting.
Offers strategies in developing project specific OPR for facility energy performance in the context of optimizing EUI and minimizing carbon intensity.
8 APPENDIX 68 / Case Studies 72 / Resources 73 / Consultant Criteria
52 / Purpose and Assumptions 53 / Software 55 / Reporting 59 / Life Cycle Cost Analysis
Page / 5
Page / 6
Ambulatory 2.0 Energy Performance Standard
SUMMARY OF SCOPE AND PROJECT GOALS
Page / 7
SUMMARY OF SCOPE AND PROJECT GOALS
Intent and Application Partners HealthCare recognizes the
This Standard is written from the position
human and environmental health impacts
that for Partners, achieving the lowest
of utilizing energy from their operational
energy use intensity (EUI) possible while
footprint and has “made sustainability a
meeting all functional and programmatic
top organizational priority.” As a leading
requirements is paramount. The
healthcare organization in reducing carbon
intended audience for this standard are
emissions they have set a net zero goal for
the Ambulatory 2.0 integrated project
all future infrastructure projects including the
teams including Partners Healthcare,
Ambulatory 2.0 buildings.
architects, MEP engineers, consultants and contractors.
To achieve these goals, Partners HealthCare commissioned this Energy
Within the Standard there are
Performance Standard that will provide a
prescriptive measures that ensure the
roadmap for project teams to achieve net
minimum performance requirements
zero performance while maintaining design
are met. In addition, there are optional
fidelity and project budget. It provides
recommendations on a range of specific
direction through recommendations
strategies that may be used to achieve
and strategies that are integrated within
the minimum performance requirement.
the planning, design and construction
They are not intended to supersede any
framework, and represents a replicable
applicable codes or regulations in the
methodology.
municipalities that the Ambulatory 2.0
Page / 8
Ambulatory 2.0 Energy Performance Standard
projects will be constructed. Further •
When feasible, on-site renewable energy systems may also be incorporated.
•
The Standards have been developed specifically for the medical office buildings, ambulatory surgery centers, and smaller feeder fit-out sites.
•
The primary focus is new construction however it also addresses considerations for anticipated fit-out projects (medical office).
The intent of the Energy Performance Standard is to provide project teams contracted for the Ambulatory 2.0 project the recommendations, strategies and supporting resources needed for achieving optimal energy performance with the potential of net-zero emissions depending on the implementation of renewable energy systems, clean energy purchase contracts, and environmental offsets.
Page / 9
SUMMARY OF SCOPE AND PROJECT GOALS
Energy Use Overview Outpatient healthcare buildings typically
Even for outpatient buildings in the same
have lower annual energy consumption than
region the “average” energy use intensity
other healthcare buildings like hospitals
tends to vary considerably due to a number
number of FTEs, outpatients and
in part due to reduced operating hours.
of factors including:
visitors.
However when compared to most other building types, outpatient facilities and in
•
•
•
The specific healthcare services
Unique electrical related demands and other equipment.
equipment needs and usage. •
Total occupants including the
such as the number of computers
provided and corresponding medical
particular ambulatory surgery centers are relatively energy intensive.
procedures provided.
•
Business activity including the
Unique natural gas related demands such as heating and steam systems,
hours and days of operation and
sterilization and more.
business activity like the number of ENERGY END-USE 100%
Natural Gas 49%
80%
Plug Loads Water-heating
60%
Ventilation Cooling/Heat rejection
40%
Electricity 51%
ST AN D AR D M OB
Figure 2a. Standard Medical Office Building
Heating 20% 0%
Lighting
GAS + ELEC.
ALL ELECTRIC
Figure 2b. Standard Medical Office Building
Page / 11
The content provided in this Standard is intended to serve as guidelines and parameters to be followed by project teams to align with Partners’ energy policies, objectives, and goals. Project teams are expected to comply with the requirements and/or demonstrate the process used to evaluate the design parameters with respect to the requirements. In circumstances where the requirements are not achievable, a thorough analysis should be provided to demonstrate the process used and rationalize the parameters which may exist that impede compliance.
Page / 15
Page / 16
Ambulatory 2.0 Energy Performance Standard
ENERGY PERFORMANCE TARGETS
Page / 17
ENERGY PERFORMANCE TARGETS
Framework Energy performance targets have been
Benchmarks
preliminary prototype clinical program. The
developed to help guide design teams
A comprehensive review of industry energy
reference developed guideline baselines
and better align project expectations with
performance benchmarks has been
ranges have been established to align with
Partners’ sustainability goals. The targets
performed to establish a reference baseline
IECC 2018/ASHRAE Standard 90.1-2016
are based on a comprehensive analysis of
to be used for the project. The review
(with MA amendments):
industry benchmarks and baseline metrics
included the following:
for comparable facilities in the region.
•
They are primarily intended to serve as
Outpatient Healthcare database
a framework, acknowledging that as the
•
facility program and configuration evolves
ASHE (American Society of Healthcare Engineers) Energy to
throughout the project, variances in
Care database
projected energy use are expected.
•
As the design team progresses through the
IFMA (International Facility Management Association) Health
evaluation of building system options, the
Care Facility Management Report
targets should be referenced to assess the
•
relative predicted performance of the project
LeapStep Healthcare Facility Energy Performance Database
and energy conservation measures being evaluated.
ENERGY STAR / CBECS 2012 –
Baseline In addition, conceptual energy models have been developed for each of the primary outpatient project types based on a
Page / 18
Ambulatory 2.0 Energy Performance Standard
Ambulatory Surgery Centers •
Site EUI: 90-125 kBTU/SF/yr
Medical Office Buildings •
Site EUI: 65-85 kBTU/SF/yr
Fit-out Facilities •
Site EUI: 70-90 kBTU/SF/yr
These baseline ranges are intended to be guidelines only. Project specific baselines should be developed by the project team according to the energy modeling guidelines outlined in this Standard.
ENERGY PERFORMANCE TARGETS Framework
Target Setting
systems that are included in the design
Guideline energy performance targets have
scope. Total energy savings should still
developed for the facility types based on
be calculated; however, the project’s
evaluation of benchmark data for comparable
performance will be measured based on the
high-performance projects and precedents.
systems affected by the project scope.
Additional energy modeling was performed to
project: •
Energy Use Savings over IECC 2018/ASHRAE 90.1-2016: 30%
Reporting
use intensity target ranges for the ambulatory
‘
targets are predicted to result in roughly
should be reported according to the
project types are as follows:
a 30% total annual savings in energy use
following guidelines:
validate the guidelines.The guideline energy
The guideline energy performance
» Estimated energy use for the project
relative to IECC 2018/ASHRAE Standard •
Site EUI: 65-85 kBTU/SF/yr
Medical Office Buildings •
40% savings relative to ASHRAE Standard 90.1-2010 (with MA amendments).
Site EUI: 45-65 kBTU/SF/yr
Fit-out Facilities •
90.1-2016 (with MA amendments) and a
Site EUI: 50-70 kBTU/SF/yr
‘
Ambulatory Surgery Centers
These target ranges are intended to be guidelines only. Project specific targets
•
Total Energy Use ○ Annual energy use intensity (EUI) – kBTU/SF/yr
•
Energy End Use ○ Annual energy end-use (EUI) – kBTU/SF/yr
should be developed by the project team a Tenant improvement projects in facilities
ccording to the Energy Modeling Guidelines
with existing central building systems
outlined in this Standard. Accordingly, the
should measure the energy savings toward
project teams should ultimately use the
with respect to the Standards goals for the
following guideline target for each specific
Page / 19
3
Energy Performance Design Guidelines Page / 24
Ambulatory 2.0 Energy Performance Standard
Page / 24
3
ENERGY DESIGN GUIDELINES
Page / 25
ENERGY DESIGN GUIDELINES
Conceptual Design
•
Sustainability Charette
•
LEED v4
» Convene a meeting with the design
•
State energy code
○ Current
team, Partners leadership, operations staff,
•
Local municipality energy code/
○ Projected (calculate escalation)
standard
○ Energy procurement contracts
and other stakeholders (industry partners,
Utility rates
utility providers, prospective vendors and service providers.
Energy Modeling
Financial Parameters
» Review energy performance and carbon
» Establish project-specific energy
» Financial parameters for life-cycle cost
emission mitigation goals.
modeling assumptions:
analysis (LCCA):
» Establish Energy & Emissions guiding principles for the project
•
○ Operating rooms
performance goals/targets for energy use
○ Conference rooms
» Define energy use and carbon emission
•
required:
Page / 26
Ambulatory 2.0 Energy Performance Standard
•
Additional operating costs - identify any additional projected operational cost variances for proposed building system options
Building Operating Schedule ○ By program areas
System life - anticipated duration of service for major equipment
occupancy profiles
» IECC 2018/ASHRAE Standard 90.1» Consideration for multiple baselines, if
•
○ Other spaces with variable
baselines for the project.
Interest rate / minimum acceptable rate of return (MARR)
○ Exam rooms
and carbon emissions.
2016 with MA amendments
•
program areas
» Develop/refine project specific
Reference Standards
Occupancy projections for key
•
Energy rebates/incentives
○ Support spaces •
Temperature set-points
Preliminary Measures
•
Anticipated plug/process loads
» Develop preliminary energy
•
Process medical equipment
conservation measures for analysis:
ENERGY DESIGN GUIDELINES Conceptual Design
•
Passive Strategies
•
Prioritize evaluation of passive design strategies to mitigate building loads.
•
Active strategies - evaluate active building system strategies that are compatible with the passive design strategies.
•
Identify synergies between active and passive design strategies to optimize building loads and energy use.
Page / 27
Page / 32
Ambulatory 2.0 Energy Performance Standard
RECOMMENDED STRATEGIES FOR COMPLIANCE
Page / 33
RECOMMENDED STRATEGIES FOR COMPLIANCE
Passive Design Strategies The following is a summary of some of the
» A rule of thumb to use in conceptual
to help inform the overall massing and
available recommended architecture and
design is that daylight is able to penetrate
programming.
load reduction strategies and approaches
up to 15 feet within a building, or twice
for compliance with the Standards
the window head height. Consider how
Envelope
requirements.
to increase the percentage of floor area
» The building envelope and facade
within 15 feet of the perimeter and how that
should be climate responsive and aim
Massing and Orientation
threshold can inform the building program
to concurrently enhance both energy
» Depending on the specific project
and adjacencies.
performance and occupant comfort.
and location there may be opportunity to
» If building stacking allows for toplighting
» At a minimum, factors for envelope
optimally configure the building shape and
with skylights further consider how that
components like insulation values for
siting to enhance energy performance.
approach should inform the overall massing
the roof, wall and floors, and thermal
» Consider massing and orientation options
and orientation relative to solar exposure.
performance for glazing are established by code.
that reduce unwanted direct solar exposure and gain while maximizing access to views
Programming and Adjacencies
» Enhancements to code minimum
and natural light with side and top-lighting.
» The configuration of program in
values should be studied in an iterative
» In the standard MOB and ASC building
internally heat load dominated healthcare
energy modeling process as outlined in this
models, lighting may account for nearly 20%
buildings can impact energy usage.
document.
of annual energy use. The typical business
» The arrangement and adjacency of
» To inform the size and location of
hour occupancy of these building types
regularly and non-regularly occupied
glazing concurrently study the impact on
increases the net impact of daylighting on
spaces in the building should be studied
daylighting, solar heat gain and glare.
energy demands.
during conceptual stage energy modeling
» As a general rule a reduction in the
Page / 34
Ambulatory 2.0 Energy Performance Standard
RECOMMENDED STRATEGIES FOR COMPLIANCE Passive Design Strategies
Project Examples » The ambulatory care buildings on this page demonstrate varying massing, orientation and envelope design solutions to reduce unwanted solar gain and support beneficial daylighting.
Figure 5. Advocate Outpatient Center
Figure 6. Geisinger Gray’s Woods
Figure 7. Kaiser Permanente Next Generation Medical Office
Figure 8. Shirley Ryan Ability Lab
Page / 35
RECOMMENDED STRATEGIES FOR COMPLIANCE
Building System Strategies The following is a summary of some of
to reduce energy consumption in hospitals
Dedicated Outdoor Air Systems (DOAS)
the available recommended MEP building
(decoupling heating/cooling from ventilation)
» Provides ventilation of indoor spaces
systems design strategies and approaches
to reduce reheat energy.
with outdoor air independent of heating/ cooling processes.
for compliance with the Standards Heat Pumps
» Directly addresses minimum code
» Similar to heat recovery chillers, heat
requirements for ventilation
HVAC
pumps can help reclaim energy normally
» Complements a strategy for decoupling
Heat Recovery Chillers
rejected during heating and cooling
of heating/cooling from ventilation (as
» Heat recovery chillers can help reclaim
processes from air or water applications.
identified by Targeting 100!) in the pursuit of
energy normally rejected during heating
» Identified by the Targeting 100! study
optimizing energy performance.
and cooling processes from air or water
as a viable strategy to address one of the
» Has the potential to improve indoor
applications.
most impactful building system strategies
air quality (IAQ) while saving energy
» Heat recovery chillers can be
to reduce energy consumption in hospitals
consumption
an effective energy saving strategy
(decoupling heating/cooling from ventilation)
for healthcare facilities, by reducing
to reduce reheat energy.
Displacement Ventilation
simultaneous heating/cooling by capturing
» Ground source (geothermal)
» Room air distribution strategy where
waste heat from cooling processes and
applications may provide additional
conditioned outdoor air is supplied at a low
utilizing them for heating demands.
opportunities for energy savings dependent
velocity from air supply diffusers located
» Identified by the Targeting 100! study
on space and site soil conditions.
near floor level and extracted above the
requirements.
as a viable strategy to address one of the
occupied zone, usually at ceiling height.
most impactful building system strategies
» Can improve IAQ while reducing energy
Page / 38
Ambulatory 2.0 Energy Performance Standard
Page / 44
Ambulatory 2.0 Energy Performance Standard
5
5
PLANNING FOR RENEWABLE ENERGY
Page / 45
PLANNING FOR RENEWABLE ENERGY
Feasibility Analysis Perform an analysis of the potential
Cost Implications
opportunities for incorporating renewable
» Identify and analyze the cost
costs for the proposed
energy systems and approaches to mitigate
considerations of the potential options
renewable systems options
□ Identify ongoing operational
•
carbon emissions related to building
Rebates/incentives
energy use. Maximize the potential site
Analysis
and building options for renewable energy.
Calculation Methodology
and rebates for renewable
Outline pertinent constraints and limitations.
» Utilize the following factors for
systems
Consider industry best-practices and
evaluating the cost effectiveness of the
emerging technologies/approaches.
renewable systems options for the project: •
Approach Site Considerations » Evaluate the project site to identify locations for renewable energy systems. Integrated Design and Coordination » Consider the relation and synergies of other proposed building systems that may complement or impact the analysis
○ Incorporate available incentives
First costs ○ Capital Costs of the System
•
Operational Costs
Ambulatory 2.0 Energy Performance Standard
Financial Analysis ○ LCCA methodology reference
Reporting •
○ Utility rates/escalation
Format ○ Assumptions
□ Current rates
□ State all assumptions for the
□ Projected escalation ○ Offsets □ Comparison of renewable system costs with offsets prices ○ Maintenance costs
Page / 46
•
feasibility analysis •
Inputs ○ Capital costs ○ Operational costs □ Energy cost savings □ Maintenance costs
PLANNING FOR RENEWABLE ENERGY Feasibility Analysis
□ Service contract costs
Renewables Readiness
□ Additional operating cost
» Identify building system strategies
savings
and approaches that enable and support
□ Escalation
integration of renewables systems for the
□ Rebates/incentives
future
○ Financial analysis parameters □ Service life / analysis period □ Interest rate □ Tax rate •
Outputs ○ Net present value (NPV) ○ Discounted payback ○ Internal rate of return
Recommendations Project Strategies » Identify recommended strategies and approaches for renewable energy systems and offsets for the project than can support the energy/carbon goals outlined in this Standard.
Page / 47
Page / 50
Ambulatory 2.0 Energy Performance Standard
6
6
ENERGY MODEL STANDARD
Page / 51
Purpose & Assumptions ENERGY MODEL STANDARD
○ Support spaces
The purpose of the energy modeling standard is to establish a clear framework
•
Temperature set-points
for the energy optimization process. The
•
Anticipated plug/process loads
standard outlines Partners’ expectations
•
Process medical equipment
on all coordination activities including:
•
Utility rates
energy modeling procedures, performance
○ Current
reporting format, and stakeholder
○ Projected (calculate escalation)
engagement.
○ Energy procurement contracts
» Establish project-specific energy modeling assumptions: •
Occupancy projections for key program areas ○ Operating rooms ○ Exam rooms ○ Conference rooms ○ Other spaces with variable occupancy profiles
•
Building Operating Schedule ○ By program areas
Page / 52
Ambulatory 2.0 Energy Performance Standard
Reporting
ENERGY MODELING STANDARD
» Partners has adopted the following
» Present the following for each ECM
Qualitative Parameters
requirements for reporting on energy
evaluated:
1. Architectural / Building Integration - impacts of the proposed systems
performance modeling results: •
Assumptions - outline the assumptions used for simulation parameters.
•
Methodology/ Approach - summarize the overall process and approach used for the energy optimization process implemented by the design team.
•
Baseline Reference - define the reference baseline used for energy simulation and emissions calculations.
•
Climate/ Load Analysis - summarize the results and resulting
Quantitative Parameters
on space requirements and other
1. Energy savings potential - EUI (kBTU/
architectural aspects.
SF/yr), Carbon Intensity (MT CO2/SF/yr) 2. Energy savings over the reference baseline (%) 3. Carbon emission savings over the reference baseline (%) 4. First cost considerations/impacts 5. Operations impacts (utility costs, FTE requirements, service requirements,
2. Code / Standards - limitations or opportunities related to code/standards compliance requirements. 3. Flexibility - considerations related to potential future building or operations changes. 4. Resiliency - considerations that impact/ support resilience
ongoing maintenance costs) 6. Rebates/ incentives - opportunities to leverage available energy rebates/ incentives
recommendations of the climate analysis.
Page / 55
ENERGY MODELING STANDARD
Life Cycle Cost Analysis The purpose of the LCCA analysis standard is to ensure consistency in reporting of financial results for comparison of building systems options for decision making. Inputs
Reporting Format •
Procedure
•
Assumptions
•
Baseline
•
Proposed Design ○ ECMs □ Summary of ECMs for
•
Capital costs
•
Annual energy cost savings
•
Annual operating costs
□ Savings projections
•
Rebates/Incentives
□ Bundles (compilation of
•
System life
multiple interdependent or
•
Utility costs
complementary ECMs)
•
Utility rate escalation projections
•
Analysis
○ Provide sensitivity analysis
•
Results
•
comparison
Interest rate
Outputs •
Net Present Value (%)
•
Discounted payback (years)
•
Internal Rate of Return (%)
Page / 59
Page / 60
Ambulatory 2.0 Energy Performance Standard
COMMISSIONING OPR STANDARD
Page / 61
Continuous Commissioning COMMISSIONING OPR STANDARD
» Develop a plan and strategy for
•
continuously monitoring building energy end-use for the purpose of identifying energy savings opportunities, system faults, and corrective measures.
•
Establish a system quality assurance
reporting. The following is a summary of the
plan
requirements for building commissioning
Reporting
reporting:
○ Energy performance dashboard □ Monthly energy use
•
-- Commissioning Process for
□ Modeled vs. actual Requirements •
Develop a process for continuous energy performance monitoring and optimization.
•
Identify personnel responsible for managing/implementing the CCx plan and define roles/responsibilities. ○ Partners staff ○ Third-party contractors
•
Develop a data management plan
•
Develop a process for identifying performance anomalies and corrective measures
□ Rolling annual EUI □ Energy costs □ Monthly
ASHRAE Standard 202-2018 Buildings and Systems
•
ASHRAE Guideline 0-2005: The Commissioning Process
□ Rolling annual ○ Alerts/alarms □ Performance deviation □ System faults ○ Monitoring intervals □ Minimum - hourly □ Recommended - 15-minute Reporting Requirements » Follow the procedures and comply with the requirements of the following standards/ guidelines for building commissioning
Page / 65
Page / 66
Ambulatory 2.0 Energy Performance Standard
8
8
APPENDIX
Page / 67
APPENDIX
Case Studies
Figure 16. Energy, HVAC, and Others for Various Projects
Page / 68
Ambulatory 2.0 Energy Performance Standard
APPENDIX
Resources Publication: Advanced Energy Design
Publication: Healthcare Energy Metering
Guide for Small Hospitals and Healthcare
Guidance, NREL
Facilities Achieving 30% Energy Savings
Author: National Renewable Energy Labo-
Toward a Net Zero Energy Building
ratory
Author: ASHRAE
Link: https://www.nrel.gov/docs/fy11os-
Link: https://www.nrel.gov/docs/fy10os-
ti/50942.pdf
ti/47013.pdf Publication: Advanced Energy Design Guide for Large Hospitals: Achieving 50% Energy Savings Author: ASHRAE Link: https://buildingdata.energy.gov/cbrd/ resource/1103 Publication: Target 100, Re-Envisioning Today’s Hospital Author: University of Washington Link: http://t100.be.uw.edu/
Page / 72
Ambulatory 2.0 Energy Performance Standard
Consultant Criteria APPENDIX
Team Selection Criteria
publicly accessible? If so please provide
decarbonization / electrification of buildings
Fidelity to sustainability has become a
web link.
with respect to the future of net-zero energy
ubiquitous claim across the A/E practice
» Describe briefly your firm’s
and zero-carbon buildings?
landscape. In order to get to the truth of
philosophy with respect to the design
a firm’s commitment and experience with
and implementation of high performance
Experience & Expertise
navigating these goals, we have devised the
healthcare projects.
» On a typical project, how are
following sets of questions to be integrated
» Describe your firm’s approach for
sustainability and high performance design
into the team selection process for architect,
tracking the modeled performance of a
supported from a work plan and team
MEP engineer and construction manager.
project during the design process.
member standpoint?
These questions aim to assess the veracity
» Describe your firm’s approach for
» List the top 3-5 factors your firm believes
of a firm’s commitment to sustainability, to
tracking and evaluating the operational
are critical to achieving a high performance /
identify the individual team members, firm
performance of completed projects.
net-zero healthcare building.
practices, completed projects, ongoing
» Does your firm have positions /
» List the top 3-5 challenges your firm
metrics and evaluation strategies, and best
individuals whose sole responsibility is
has encountered in achieving a high
practices that exemplify a firm’s respective
sustainability? If so, are they located in the
performance / net-zero healthcare building.
approach.
primary office that will deliver this project?
» How does your firm consider carbon
» Do you consider your firm a leader in
emission impacts when evaluating the
Team Selection - Architect
designing high performance healthcare
performance of design projects?
Approach
projects that are capable of achieving net-
» Describe your firm’s experience
» Does your firm have a written
zero? If yes, why?
with alternative mechanical systems on
commitment to sustainable design that is
» How does your firm view
healthcare projects including (but not
Page / 73
APPENDIX Consultant Criteria
•
limited to) natural ventilation, displacement ventilation, chilled beams, heat recovery
Carbon Intensity: _________lbs CO2/MWh
•
systems (heat pumps / VRF / heat recovery
•
Carbon Reduction:________% reduction
Energy Reduction _______%
chillers), geothermal (ground source)
reduction vs applicable reference
Process
systems, advanced building controls.
code, (e.g. ASHRAE 90.1) ____ yr
» What lessons has your firm learned from
Carbon Reduction________%
the projects identified above? How has your
reduction
firm adapted its approach in response?
Lead Design Professional
» Has your firm attempted to achieve
____________
net-zero on a healthcare project before?
Lead Sustainability Professional
If so, what was the primary challenge that
____________
prevented it from being achieved? For those
•
» If experience is cited, provide the number of in-progress and completed
•
healthcare projects that include each of the alternative mechanical systems identified in
•
the prior response. » If available, provide Energy Use Intensity (EUI), Energy Percent Reduction,
•
MEP Engineer____________
projects, how was net-zero defined; net-
and Carbon Intensity data on the top 3
•
Owner Contact ____________
zero energy (site), net-zero energy (source),
performing non-inpatient healthcare projects
» Operational Performance
your firm has designed. If this information is unavailable please write N/A. •
EUI: ___________kBtu/sf/yr
•
Carbon Intensity: _________lbs CO2/MWh
Project Name and Location ____________
» Modeled Performance •
•
EUI: ___________kBtu/sf/yr
Page / 74
Ambulatory 2.0 Energy Performance Standard
•
Energy Reduction: _______% reduction vs applicable reference code, (e.g. ASHRAE 90.1)
net-zero energy (cost), or net-zero carbon emissions? If your firm has attempted this only on a non-healthcare project please include instead and note the project type. » Excluding the cost of on-site renewable energy systems, how does your firm consider the financial implications of pursuing high-performance / net-zero design?
Location Authors
Contact
LeapStep Design, LLC brooklyn & san francisco Breeze Glazer, Principal Arash Guity, Principal John Rudikoff, Principal www.leapstep.design info@leapstep.design
Page / 81