Class I Overvoltage Protection with sparkover gaps with high-power varistors Overvoltage Protection, combination arrester
B.2 B.4 B.10 B.12
- B.3 - B.9 - B.11 - B.15
Class II Overvoltage Protection with varistors
B.16 - B.25
Class III Overvoltage Protection with varistors
B.26 - B.31
Plug-in Overvoltage Protection
B.32 - B.35
Mains filter
B.36 - B.39
Overvoltage Protection installation instructions Class I, II, III B.40 - B.43 Examples of applications for TN, TT and IT systems
B.44 - B.45
B.1
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies
B
Overvoltage Protection for low-voltage supplies
Overvoltage Protection class I with spark gap Power supply
Class I, sparkover gap
Electrical system I/O lines
B
Data interfaces Bus lines
Design surge voltage
Weidm端ller series PU 1 TSG and PU B (class I), PU x C (class II) plus PU D and PO D (class III) overvoltage protection devices lower the overvoltage protection level to below the limits prescribed by the insulation coordination to DIN VDE 0110. This means that the entire system is subjected to less interference. The coordination of the arresters is achieved by technical means. This means that decoupling between classes I, II and III is not necessary.
6.0 kV
4.0 kV
2.0 kV
1.5 kV B.2
Class I, high-power varistor
Class II, varistor
Overvoltage Protection for low-voltage supplies
Overvoltage Protection class I with spark gap Class III, varistor
B
for insulation coordination to IEC 664 and DIN VDE 0110 Lightning arresters Sparkover gaps, triggered and enclosed, 35/50 kA
PU 1 TSG
Page B.7
Sparkover gaps, triggered 50 kA
PU 1 TSG+
Page B.6
Triggered sparkover gaps, 100 kA
PU 1 TSG 100 kA Page B.8
High-power varistors, 20/25 kA
PU 3 B, PU 4 B
Page B.11
High-power varistors, 20/25 kA, with signalling contact
PU 3 BR, PU 4 BR Page B.11
Replacement arrester, high-power varistor
PU 0 B
Page B.11
Combined overvoltage protection
PU COMBI I + II
Page B.14/15
PU x C
Page B.17-24
with signalling contact
PU x CR
Page B.17-24
Replacement varistor to suit rated voltage
PU 0 C
Page B.17-24
with signalling contact
PU D, PU DS
Page B.27-29
Three-phase arresters with signalling contact
PU 3 D
Page B.30
Schuko plug-in overvoltage protector
PU D ZS
Page B.33-35
Overvoltage arresters Varistor arresters up to 100 kA for diverse voltages Varistor arresters up to 100 kA for diverse voltages,
Lightning arresters Single-phase arresters for diverse voltages,
B.3
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies Class I Overvoltage Protection with sparkover gaps Weidmüller Übergabeelemente gap is tripped, a safety clearance of min. 100 mm must be maintained between this and any current-conducting components. The maximum permissible operating voltage Uc is 330 or 440 Vac. Decoupling from downstream class II (C) arresters for 470 V is unnecessary because triggered sparkover gaps with a low sparkover voltage are used. Please follow the installation instructions.
B
Lightning conductors with spark gap for lighting protection equipotential bonding Overvoltage Protection class I (B charge eliminators) According to the requirements of class B (DIN VDE 0675 part 6 (draft 11.89)/A1: 3/96) and class I as per IEC 61643-1 (1/02), the lightning conductor at the transfer from interface 0 to 1 (as per IEC 1312-1) is used as the lightning protection equipotential bonding. In combination with several lightning protectors, the overvoltage protection is used in the mains forms TN, TT and IT. When lightning strikes, the triggered air gap protector provides the necessary equipotential bonding between the building lightning protection and the earthing system of the power supply. The use of a sparkover gap satisfies the inspection requirements for class B overvoltage protection systems according to the VDEW (Association of German Power Stations) directive (1st ed., 1998).
Checking operation, maintenance and approvals A visual check is necessary to ensure that PU 1 TSG and PU 1 TSG+ overvoltage protection components are operating correctly. Besides signalling a mains power failure, the lamp illuminates above 120 Vac to indicate the failure of the firing electronics. It is advisable to check frequently during stormy weather. The use of triggered sparkover gaps achieves a very low protection level of < 1.5 kV with high discharge currents. Depending on the cross-section of the line, the PU 1 TSG must be protected with a fuse of max. 125 A gL, the PU 1 TSG+ max. 250 A gL. The connection is designed for the following cross-sections: – solid wire:
10...35 mm2,
– multistrand wire:
10...25 mm2.
The operating temperature range is –40 °C ... +85 °C. Electrical connection for building installation The PU 1 TSG 35 kA class I lightning arrester is connected between the phase conductors (L1, L2, L3) and the N/PE. A Weidmüller PU 1 TS G 50 kA is used to provide the N-PE sparkover gap. The lines for this should be kept as short as possible.
The PU 1 TSG lightning arresters have UL and KEMA approval and are hence suitable for use worldwide.
The triggered and non-blowout PU 1 TSG devices can be clipped to TS 35 rails in electrical cabinets or distribution boards. The maximum permissible operating voltage Uc is 260 Vac. Decoupling from downstream class II (C) arresters is unnecessary because triggered sparkover gaps with a low sparkover voltage are used. Please follow the installation instructions. Electrical connection for industrial installations The PU 1 TSG+ 50 kA/330 V or 440 V class I lightning arrester is connected between the phase conductors (L1, L2, L3) and the N/PE. A Weidmüller PU 1 TSG 50 kA is used to provide the N-PE sparkover gap. The lines for this should be kept as short as possible. The triggered and blowout PU 1 TSG+ 50 kA devices can be clipped to TS 35 rails in electrical cabinets or distribution boards. Owing to the emissions given off when the sparkover
B.4
Dimensioned drawing PU 1 TSG+ Overall width 36 mm
Dimensioned drawing PU 1 TSG+ Overall width 18 mm
Accessories: QB 18-6
QB 18-4
BZ 18 L1, L2, L3, N, PE
BZ 18 PE, PE, PE, PE
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies Protection in the TN-S-system
B
Protecion in the TT-system
In contrast to conventional sparkover gaps, the Weidm端ller PU 1 TSG+ and PU 1 TSG sparkover gaps operate with electronic triggering. This fires the sparkover gap at such an early point that the downstream class II (Pu x C) arresters are relieved. Decoupling from downstream class II (C) arresters is unnecessary because triggered sparkover gaps with a low sparkover voltage are used. Choke or conductor
Lightning conductor class I
Overvoltage charge eliminator class II
The PU 1 TSG+ and PU 1 TSG differ in terms of the follow current extinction. The PU 1 TSG+ distributes the arc drop voltage over several chambers. As soon as the total arc drop voltage exceeds the mains voltage flowing, the follow current is extinguished. In the PU 1 TSG the follow current extinction takes place at the next current zero of the mains voltage. Integrated electronic trigger component
Lightning conductor class I
Overvoltage charge eliminator class II
B.5
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems Class I with triggered spark gap
PU 1TSG+ 50kA/0.9kV-330V
PU 1 TSG+ 50kA/1.5kV-440V
Class I lightning arrester
for use in industrial networks
for use in industrial networks
• encapsulated version • no decoupling necessary thanks to trigger electronics • suitable for networks with high short-circuit currents
B L/N
L/N
Trigger
Trigger
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 lightening test voltage imp (10/350µs) Specific energy, per path Short-circuit current extinction without back-up fuse Short-circuit strength at max. back-up fuse Response time Back-up fuse, max. Protection level Up (typ.) Optical function indicator Colour Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals le E198315 KEMA
Dimensions Clamping range (rating- / min. / max.) Length x width x height
mm2 mm
Technical specification 330V d voltage (AC) 330V ating voltage Uc (ac), max. Class I ment class acc. to IEC 61643-1 50 kA with 25 As charge imp (10/350µs) 625kJ/M rgy, per path 50 kA / 50 Hz current extinction without back-up fuse 25 kAeff gth at max. back-up fuse < 150 ns me 250 A gl fuse, max. 900V ion level Up (typ.) green LED unction indicator black r -40°C/85°C temp. min./Operating temp. max. -40°C/85°C mp. min./Storage temp., max. cURus, File E198315 KEMA
Technical specification 440V d voltage (AC) 440V ating voltage Uc (ac), max. Class I ment class acc. to IEC 61643-1 50 kA with 25 As charge imp (10/350µs) 625kJ/M rgy, per path 50 kA / 50 Hz current extinction without back-up fuse 25 kAeff gth at max. back-up fuse < 150 ns me 250 A gl fuse, max. 1500V on level Up (typ.) green LED unction indicator black r -40°C/85°C temp. min./Operating temp. max. -40°C/85°C mp. min./Storage temp., max. cURus, File E198315 KEMA
35.0 / 10.0 / 35.0 150.0 x 35 x 80.0
35.0 / 10.0 / 35.0 150.0 x 35 x 80.0
Information
Order data Version
Type PU1 TSG Plus 330 VAC 0,9kV
Information
Cross-connection QB 18-4 order No. 8619440000 Cross-connection QB 18-6 order No. 8619450000
Cross-connection QB 18-4 order No. 8619440000 Cross-connection QB 18-6 order No. 8619450000
Designation BZ18, PE PE PE PE PE order No. 8619470000
Designation BZ18, L1 L2 L3 N PE order No. 8619460000
Qty. 1
Order No. 8561220000
Type PU1 TSG Plus 440 VAC 1,5kV
Qty. 1
Order No. 8561250000
Accessories Information
B.6
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
Class I with triggered spark gap
PU 1 TSG 35kA/0.9kV-260V
PU 1 TSG 50kA/1.5kV-260V
Class I lightning arrester
for use in building networks
for use in building networks
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems
• encapsulated version • no decoupling necessary thanks to trigger electronics
B L/N
L/N
Trigger
Trigger
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 lightening test voltage imp (10/350µs) Specific energy, per path Short-circuit current extinction without back-up fuse Short-circuit strength at max. back-up fuse Response time Back-up fuse, max. Protection level Up (typ.) Optical function indicator Colour Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals le E198315
Dimensions Clamping range (rating- / min. / max.) Length x width x height
mm2 mm
Technical specification 230V d voltage (AC) 260V ating voltage Uc (ac), max. Class I ment class acc. to IEC 61643-1 35 kA with 17.5As charge imp (10/350µs) 305kJ/Ω per path 3 kA / 50 Hz t current extinction without back-up fuse 25 kAeff gth at max. back-up fuse < 1 µs time 125 A gl fuse, max. 900V ion level Up (typ.) green LED unction indicator grey ur -40°C/85°C temp. min./Operating temp. max. -40°C/85°C mp. min./Storage temp., max. cURus, File E198315
Technical specification 230V d voltage (AC) 260V ating voltage Uc (ac), max. Class I ment class acc. to IEC 61643-1 50 kA with 25 As charge imp (10/350µs) 625kJ/Ω per path 500 A / 50 Hz current extinction without back-up fuse 25 kAeff gth at max. back-up fuse < 1 µs time 125 A gl fuse, max. 1500V on level Up (typ.) No tical function indicator grey ur -40°C/85°C temp. min./Operating temp. max. -40°C/85°C mp. min./Storage temp., max. cURus, File E198315
35.0 / 10.0 / 35.0 91.0 x 18 x 63.0
35.0 / 10.0 / 35.0 91.0 x 18 x 63.0
Information
Order data Version
Type PU 1 TSG 35kA / 0,9kV
Information
Cross-connection QB 18-4 order No. 8619440000 Cross-connection QB 18-6 order No. 8619450000
Cross-connection QB 18-4 order No. 8619440000 Cross-connection QB 18-6 order No. 8619450000
Designation BZ18, L1 L2 L3 N PE order No. 8619460000
Designation BZ18, PE PE PE PE PE order No. 8619470000
Qty. 1
Order No. 8561260000
Type PU 1 TSG 50kA / 1,5kV
Qty. 1
Order No. 8561230000
Accessories Information
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
B.7
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems Class I with triggered spark gap
PU 1 TSG 100 kA
Class I lightning arrester
for use as N-PE arrester
• encapsulated version • no decoupling necessary thanks to trigger electronics • suitable as N-PE arrester
B L/N
Trigger
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 lightening test voltage imp (10/350µs) Specific energy, per path Short-circuit current extinction without back-up fuse Short-circuit strength at max. back-up fuse Response time Back-up fuse, max. Protection level Up (typ.) Optical function indicator Colour Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals le E198315 KEMA
Dimensions Clamping range (rating- / min. / max.) Length x width x height
Technical specification 230V d voltage (AC) 260V ating voltage Uc (ac), max. Class I ment class acc. to IEC 61643-1 100 kA with 50 As charge imp (10/350µs) 2500kJ/Ω per path 100 A 260 V/50 Hz rent extinction without back-up fuse Short-circuit strength at max. back-up fuse < 1 µs time 125 A gl fuse, max. 1500V on level Up (typ.) No tical function indicator grey ur -40°C/85°C temp. min./Operating temp. max. -40°C/85°C mp. min./Storage temp., max. cURus, File E198315 KEMA
mm2 mm
50.0 / 6.0 / 50.0 90.0 x 36 x 63.0
Information
Order data Version
Type PU 1 TSG 100kA/1,5 kV
Information
Cross-connection QB 18-4 order No. 8619440000 Cross-connection QB 18-6 order No. 8619450000
Qty. 1
Order No. 8762020000
Accessories Information
B.8
BZ18, L1 L2 L3 N PE order No. 8619460000 BZ18, PE PE PE PE PE order No. 8619470000
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
B
B.9 Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies Lightning arresters with varistors for lightning protection equipotential bonding Class I overvoltage protection (B arresters)
Weidmüller overvoltage protection type PU B is designed for lightning protection equipotential bonding to DIN VDE 0185 part 1 (Nov 1982). The PU B is a class I lightning arrester (B arrester) to DIN VDE 0675 part 6 (Nov 1989), IEC 61643-1 (Feb 1998), ENV 61024-1 (Jan 1995) and IEC 1312-1 (Feb 1995).
B In the event of a lightning strike, the integral plug-in high-power varistors create the necessary equipotential bonding between the building’s lightning protection system and the earthing system of the power supply. Electrical connection The PU B class I lightning arresters are connected between the phase conductors (L1, L2, L3), or the neutral conductor, the earth of the consumer installation and – in addition – the earthing bar of the distribution board. The lines for this should be kept as short as possible. The PU B is clipped to a TS 35 rail in the switching cabinet or distribution board. The maximum permissible operating voltage Uc is 275 Vac. No inductances are required for decoupling from downstream class II (C) arresters. Please follow the installation instructions.
The connection is to be designed to IEC 947-7-1 for the following cross-sections: – solid wire:
6...10 mm2,
– multistrand wire: 16...25 mm2, – fine strand wire
10...25 mm2.
Checking operation, maintenance and approvals A visual check is necessary – more frequently during storms – to ensure that the PU B overvoltage protection components are operating correctly. This visual check is easy because the varistor is fitted with a thermal disconnector. If this has been tripped and protection is no longer provided, the flag in the status window changes from green to red. A tripped arrester is easily replaced by a qualified technician without having to disconnect any wiring.
The operating temperature range is –40 °C ... +60 °C. The PU B is an arrester that can be used both as a class I and also a class II arrester. Weidmüller PU B lightning arresters have UL approval and are hence suitable for use worldwide.
The top section of the varistor is coded according to voltage and – to distinguish it from class II overvoltage arresters (C arresters) – integrated in a black plastic housing (PA 6.6). Therefore, it is not possible to plug in a different, i.e. wrong, replacement varistor. These plug-in high-power varistors achieve a very low protection level of < 2 kV with high discharge currents. The arrester is to be fused (max. 160 A gL) to suit the cross-section of the line. The use of varistors means that overvoltages do not give rise to any emissions within the installation.
B.10
PU-B dimensions Width PU3B 54 mm PU3BR 72 mm PU4B 72 mm PU4BR 90 mm
Class I with high-power varistors
PU 3 B/BR
PU 4 B/BR
Class I lightning arrester with high-power varistors, also suitable as class II arrester
PU 3 B/BR 230/400Vac
PU 4 B/BR 230/400Vac
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems
• plug-in version with visual function indicator • complete unit • coded voltage level, diverse voltages • high energy absorption, 7 kA 10/350 µs per disc • low residual voltage • short time to sparkover • no follow current • thermal overcurrent protection for varistors • no decoupling inductance required between PU B and PU C
B 1112 14
L1
L3
L2
11 12 14
OK CHANGE
OK CHANGE
U
U
L1
OK CHANGE
U
U
L2
N
L3
OK CHANGE
OK CHANGE
OK CHANGE
U
U
U
OK CHANGE
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 lightening test voltage imp (10/350µs) Specific energy, per path Leakage current, max. (8/20 µs) Response time Back-up fuse, max. Protection level Up (typ.) Optical function indicator faulty, replace Monitoring contact Design lation housing Colour Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals
Dimensions Clamping range (rating- / min. / max.) Length x width x height
mm2 mm
Technical specification 230V d voltage (AC) 275V ating voltage Uc (ac), max. Class I ment class acc. to IEC 61643-1 20 kA ening test voltage imp (10/350µs) 100kJ/M rgy, per path 100.0kA current, max. (8/20 µs) < 25 ns ime 160 A gl fuse, max. 2000V on level Up (typ.) green = OK; red = arrester faulty, replace 250V 1A 1CO contact installation housing black r -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. UL provals
Technical specification 230V d voltage (AC) 275V ating voltage Uc (ac), max. Class I ment class acc. to IEC 61643-1 25 kA ening test voltage imp (10/350µs) 100kJ/Ω per path 100.0kA current, max. (8/20 µs) < 25 ns ime 160 A gl fuse, max. 2000V on level Up (typ.) green = OK; red = arrester faulty, replace 250V 1A 1CO contact installation housing black r -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. UL provals
without telecomm. contact with telecomm. contact 10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0 90.0 x 54 x 61.0 90.0 x 72 x 61.0
without telecomm. contact with telecomm. contact 10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0 90.0 x 72 x 61.0 90.0 x 90 x 61.0
Type PU 3 B 275 VAC PU 3 BR 275 VAC
Type PU 4 B 275 VAC PU 4 BR 275 VAC
Information
Order data Version without telecomm. contact with telecomm. contact
Qty. 1 1
Order No. 8381890000 8381900000
Qty. 1 1
Order No. 8147020000 8291640000
Information
Accessories Information
Plug-in spare arrester, 275 V PU 0 B 8381880000
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
Plug-in spare arrester, 275 V PU 0 B 8381880000
B.11
Overvoltage Protection for low-voltage supplies
B
Overvoltage Protection for low-voltage supplies Combination arrester Combined lightning and overvoltage protection for low-voltage consumer installations and electronics
The PU I+II COMBI combined overvoltage protection incorporates triggered PU 1 TSG class I sparkover gaps, class II varistor arresters PU x C and cross-connections. This setup protects low-voltage consumer installations and electronic devices against overvoltages, both those caused by atmospheric discharges (lightning) and those caused by switching operations (transients). The PU COMBI complies with the requirements of IEC 616431 (Feb 1998). The PU R COMBI also has a remote signalling function achieved via a floating contact. Electrical connection The PU COMBI overvoltage protection device is connected with lines as short as possible between the phase conductors (L1, L2, L3), or the neutral conductor (N), and the earth of the consumer installation. Unprotected lines (e.g. to meters) and protected lines must not be routed together. The PU COMBI can be supplied for a 4-conductor system with three phases plus PEN conductor, and also for a 5-conductor system with three phases plus N-PE arrester. Checking operation, maintenance and approvals A visual check is necessary to ensure that the PU COMBI overvoltage protection components are operating correctly. This visual check is easy because the arrester is fitted with a thermal disconnector. If this has been tripped and protection is no longer provided, the flag in the status window changes from green to red. A tripped arrester is easily replaced by a qualified technician without having to disconnect any wiring. The top section of the varistor is coded according to voltage. Therefore, it is not possible to plug in a different, i.e. wrong, replacement varistor.
The cross-section of the earth line must be at least 10 mm2 or half the cross-sectional area of the phase conductor. The fuse protection (max. 125 A gL) for the PU modules is chosen depending on the line cross-section and the type of wiring. The connection is designed to IEC 947-7-1 for the following cross-sections: solid wire:
10...35 mm2
multistrand wire: 10...25 mm2 fine strand wire: 10...25 mm2 The operating temperature range is â&#x20AC;&#x201C;40 °C ... +60 °C.
B.12
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies
B
h
length x width x height PU Combi I+II 4-conductor system PU R Combi I+II 4-conductor system PU Combi I+II 5-conductor system PU R Combi I+II 5-conductor system
90 x 65 x 110 mm 90 x 65 x 126 mm 90 x 65 x 148 mm 90 x 65 x 162 mm
B.13
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems applicable for 4-wire systems
PU COMBI I+II 4 Wire
PU R COMBI I+II 4 Wire
The overvoltage protection combination consists of the class I triggered sparkover gap PU1TSG for protecting the phase to N of an N-PE sparkover gap and the class II PU3C. The arresters are interconnected via 16 mm2 jumpers.
for use in building networks
for use in building networks
Technical specification 230V d voltage (AC) 260V ating voltage Uc (ac), max. I+II (combination arrester) EC 61643-1 35 kA with 17.5 As charge mp (10/350µs) 305kJ/Ω per path 3 kA / 50 Hz t current extinction without back-up fuse 25 kAeff gth at max. back-up fuse sym/ asym: <100 ns 125 A gl fuse, max. 900V ion level Up (typ.) green = OK; red = arrester faulty, replace grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. Approvals
Technical specification 230V d voltage (AC) 260V ating voltage Uc (ac), max. I+II (combination arrester) EC 61643-1 35 kA with 17.5 As charge mp (10/350µs) 305kJ/Ω per path 3 kA / 50 Hz t current extinction without back-up fuse 25 kAeff gth at max. back-up fuse sym/ asym: <100 ns 125 A gl fuse, max. 900V ion level Up (typ.) green = OK; red = arrester faulty, replace grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. Approvals
35.0 / 10.0 / 35.0 91.0 x 110 x 65.0
35.0 / 10.0 / 35.0 90.0 x 126 x 65.0
The connection to the power line is made at the PU1TSG.
B
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 lightening test voltage imp (10/350µs) Specific energy, per path Short-circuit current extinction without back-up fuse Short-circuit strength at max. back-up fuse Response time t;100 ns Back-up fuse, max. Protection level Up (typ.) Optical function indicator faulty, replace Colour Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals
Dimensions Clamping range (rating- / min. / max.) Length x width x height
mm2 mm
Information
Order data Version
Type PU COMBI I+II 4 Wire
Information
Set: PU3C(R), PU1TSG, jumpers
Qty. 1
Order No. 8729960000
Type PU R COMBI I+II 4 Wire
Qty. 1
Order No. 8729970000
Set: PU3C(R), PU1TSG, jumpers
Accessories Information
B.14
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
applicable for 5-wire systems
PU COMBI I+II 5 Wire
PU R COMBI I+II 5 Wire
The overvoltage protection combination consists of the class I triggered sparkover gap PU1TSG for protecting the phase to N of an N-PE sparkover gap and the class II PU3C. The arresters are interconnected via 16 mm2 jumpers.
for use in building networks
for use in building networks
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems
The connection to the power line is made at the PU1TSG.
B
h
h
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 lightening test voltage imp (10/350µs) 50 kA with 25 As charge Specific energy, per path Short-circuit current extinction without back-up fuse Short-circuit strength at max. back-up fuse Response time t;100 ns Back-up fuse, max. Protection level Up (typ.) Optical function indicator faulty, replace Colour Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals
Dimensions Clamping range (rating- / min. / max.) Length x width x height
mm2 mm
Technical specification 230V d voltage (AC) 260V ating voltage Uc (ac), max. I+II (combination arrester) EC 61643-1 35 kA with 17.5 As charge mp (10/350µs) 50 kA with 25 As charge 305kJ/Ω per path 3 kA t-circuit current extinction without back-up fuse 25 kAeff gth at max. back-up fuse sym/ asym: <100 ns 125 A gl fuse, max. 1500V on level Up (typ.) green = OK; red = arrester faulty, replace grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. Approvals
Technical specification 230V d voltage (AC) 260V ating voltage Uc (ac), max. I+II (combination arrester) EC 61643-1 35 kA with 17.5 As charge mp (10/350µs) 50 kA with 25 As charge 305kJ/Ω per path 3 kA t-circuit current extinction without back-up fuse 25 kAeff gth at max. back-up fuse sym/ asym: <100 ns 125 A gl fuse, max. 1500V on level Up (typ.) green = OK; red = arrester faulty, replace grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. Approvals
35.0 / 10.0 / 35.0 90.0 x 148 x 65.0
35.0 / 10.0 / 35.0 91.0 x 165 x 65.0
Information
Order data Version
Type PU COMBI I+II 5 Wire
Information
Set: PU3C(R), PU1TSG, jumpers
Qty. 1
Order No. 8729950000
Type PU R COMBI I+II 5 Wire
Qty. 1
Order No. 8729930000
Set: PU3C(R), PU1TSG, jumpers
Accessories Information
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
B.15
Overvoltage Protection for low-voltage supplies
B
Overvoltage Protection for low-voltage supplies Overvoltage Protection for low-voltage consumers and electronic components Low-voltage protection class II (C charge eliminators)
Weidmüller overvoltage protection type PU C protects lowvoltage consumer installations and electronic devices against overvoltages, both those caused by atmospheric discharges (lightning) and those caused by switching operations (transients). The PU C complies with the requirements of DIN VDE 0675 part 6, class C (Nov 1989), (draft) DIN VDE 0675 part 6, A2 (Oct 1996), ÖVE SN 60 parts 1 and 4, and IEC 61643-1 (Feb 1998). Electrical connection The PU COMBI overvoltage protection device is connected with lines as short as possible between the phase conductors (L1, L2, L3), or the neutral conductor (N), and the earth of the consumer installation. Unprotected lines (e.g. to meters) and protected lines must not be routed together. PU C arresters for the "3+1” circuit are also available. PU C overvoltage protection is available as a compact module, 3- or 4-pole, with up to 100 kA (8/20 µs), with the PE connections of the discs already interconnected. Versions can be supplied for the following rated voltages:
Weidmüller PU C arresters have ÖVE SN 60 and UL approval and are hence suitable for use worldwide. The connection is designed to IEC 947-7-1 for the following cross-sections: 6...10 mm2,
• 60 Vac,
– solid wire:
• 115/230 Vac,
– multistrand wire:
16...25 mm2,
• 230/400 Vac,
– fine strand wire:
10...25 mm2.
• 470/600 Vac, • for ”3+1” circuits
The operating temperature range is –40 °C ... +60 °C.
• special types for IT systems Checking operation, maintenance and approvals
Dimensioned drawing PU-C Overall width PU1C 18 mm PU2C 36 mm PU3C 54 mm PU3CR, PU4C 72 mm PU4CR 90 mm
A visual check is necessary to ensure that the PU COMBI overvoltage protection components are operating correctly. This visual check is easy because the arrester is fitted with a thermal disconnector. If this has been tripped and protection is no longer provided, the flag in the status window changes from green to red. A tripped arrester is easily replaced by a qualified technician without having to disconnect any wiring. The top section of the varistor is coded according to voltage and – to distinguish it from class I overvoltage arresters (B arresters) – integrated in a light grey plastic housing (PA 6.6). Therefore, it is not possible to plug in a different, i.e. wrong, replacement varistor. The cross-section of the earth line must be at least 10 mm2 or half the cross-sectional area of the phase conductor. The fuse protection (max. 125 A gL) for the PU modules is chosen depending on the line cross-section and the type of wiring. Monitoring unit
B.16
Class II with varistors
PU 3 C+CR 230 V
PU 4 C+CR 230 V
Class II overvoltage protection
PU 3 C / PU 3 CR 230/400Vac
PU 4 C / PU 4 CR 230/400Vac
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems
with Uc: 280 V • plug-in varistor top section • coded voltage level, diverse voltages • high energy absorption • short time to sparkover • no follow current • installed in Insta distributor • thermal and dynamic overcurrent protection • coordination between class I with Up:< 900 V
B L1
11 12 14
L3
L2
11 12 14
U
OK CHANGE
OK CHANGE
U
U
L1
OK CHANGE
U
L2
N
L3
OK CHANGE
OK CHANGE
OK CHANGE
U
U
U
OK CHANGE
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 Rated leakage current (8/20 µs) Limiting leakage current (8/20 µs) Leakage current, max. (8/20 µs) Response time Back-up fuse, max. Protection level Up (typ.) Optical function indicator faulty, replace Monitoring contact Design lation housing Colour Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals N 60, SABS
Dimensions Clamping range (rating- / min. / max.) Length x width x height
mm2 mm
Technical specification 230V d voltage (AC) 280V ating voltage Uc (ac), max. Class II ent class acc. to IEC 61643-1 20 kA leakage current (8/20 µs) 40kA ting leakage current (8/20 µs) 100.0kA current, max. (8/20 µs) < 25 ns ime 125 A gl fuse, max. 1300V on level Up (typ.) green = OK; red = arrester faulty, replace 250V 1A 1CO contact installation housing grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. UL, ÖVE SN 60, SABS
Technical specification 230V d voltage (AC) 280V ating voltage Uc (ac), max. Class II ent class acc. to IEC 61643-1 20 kA leakage current (8/20 µs) 40kA ting leakage current (8/20 µs) 100.0kA current, max. (8/20 µs) < 25 ns ime 125 A gl fuse, max. 1300V on level Up (typ.) green = OK; red = arrester faulty, replace 250V 1A 1CO contact installation housing grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. UL, ÖVE SN 60, SABS
without telecomm. contact with telecomm. contact 10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0 90.0 x 54 x 61.0 90.0 x 72 x 61.0
without telecomm. contact with telecomm. contact 10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0 90.0 x 72 x 61.0 90.0 x 91 x 61.0
Type PU 3 C 275 VAC PU 3 CR 275 VAC
Type PU 4 C 275 VAC PU 4 CR 275 VAC
Information
Order data Version without telecomm. contact with telecomm. contact
Qty. 1 1
Order No. 8021490000 8021510000
Qty. 1 1
Order No. 8021500000 8021520000
Information
Accessories Information
Plug-in spare arrester, 275 V PU 0 B 8339510000
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
Plug-in spare arrester, 275 V PU 0 B 8339510000
B.17
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems Class II with varistors
PU 1 C 230 V
PU 2 C 230 V
Class II overvoltage protection
PU 1 C
PU 2 C
with Uc: 280 V • plug-in varistor top section • coded voltage level, diverse voltages • high energy absorption • short time to sparkover • no follow current • installed in Insta distributor • thermal and dynamic overcurrent protection • coordination between class I with Up:< 900 V
B L1
L1
L2 OK CHANGE
OK CHANGE
U
U
OK CHANGE
U
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 Rated leakage current (8/20 µs) Limiting leakage current (8/20 µs) Leakage current, max. (8/20 µs) Response time Back-up fuse, max. Protection level Up (typ.) Optical function indicator faulty, replace Monitoring contact Design lation housing Colour Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals N 60, SABS
Dimensions Clamping range (rating- / min. / max.) Length x width x height
mm2 mm
Technical specification 230V d voltage (AC) 280V ating voltage Uc (ac), max. Class II ent class acc. to IEC 61643-1 20 kA leakage current (8/20 µs) 40kA ting leakage current (8/20 µs) 40.0kA e current, max. (8/20 µs) < 25 ns ime 125 A gl fuse, max. 1300V on level Up (typ.) green = OK; red = arrester faulty, replace 250V 1A 1CO contact installation housing grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. UL, ÖVE SN 60, SABS
Technical specification 230V d voltage (AC) 280V ating voltage Uc (ac), max. Class II ent class acc. to IEC 61643-1 20 kA leakage current (8/20 µs) 40kA ting leakage current (8/20 µs) 75.0kA e current, max. (8/20 µs) < 25 ns ime 125 A gl fuse, max. 1300V on level Up (typ.) green = OK; red = arrester faulty, replace 250V 1A 1CO contact installation housing grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. UL, ÖVE SN 60, SABS
without telecomm. contact 10.0 / 6.0 / 50.0 90.0 x 18 x 61.0
without telecomm. contact with telecomm. contact 10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0 90.0 x 36 x 61.0 90.0 x 54 x 61.0
Information
Order data Version without telecomm. contact with telecomm. contact
Type PU 1 C 275 VAC
Qty. 1
Order No. 8102610000
Type PU 2 C 275 VAC PU 2 CR 275 VAC
Qty. 1 1
Order No. 8098170000 8425240000
Information
Accessories Information
B.18
Plug-in spare arrester, 275 V PU 0 B 8339510000
Plug-in spare arrester, 275 V PU 0 B 8339510000
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
Class II with varistors
PU 3+1 C 230 V
PU 3+1 C 385 V
Class II overvoltage protection
PU 3+1 C/CR 230/400Vac
PU 3+1 C 385Vac
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems
with Uc: 280 V • plug-in varistor top section • coded voltage level, diverse voltages • high energy absorption • short time to sparkover • no follow current • installed in Insta distributor • thermal and dynamic overcurrent protection • coordination between class I with Up:< 900 V • complete 3- or 4-pole modules for TN and TT systems with 100 kA 8/20 µs discharge current
B L1
L2 OK CHANGE
OK CHANGE
U
U
U
PE
L3
L1
OK CHANGE
L3
L2 OK CHANGE
OK CHANGE
U
N
U
PE OK CHANGE
U
N
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 Rated leakage current (8/20 µs) Limiting leakage current (8/20 µs) Leakage current, max. (8/20 µs) Response time Back-up fuse, max. Protection level Up (typ.) Optical function indicator faulty, replace Monitoring contact Design lation housing Colour range Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals
Dimensions Clamping range (rating- / min. / max.) Length x width x height
mm2 mm
Technical specification 230V d voltage (AC) 280V ating voltage Uc (ac), max. Class II ent class acc. to IEC 61643-1 20 kA leakage current (8/20 µs) 40kA ting leakage current (8/20 µs) 100.0kA current, max. (8/20 µs) < 1 µs time 125 A gl fuse, max. 1900V on level Up (typ.) green = OK; red = arrester faulty, replace 250V 1A 1CO contact installation housing grey/orange -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. Approvals
Technical specification 230V d voltage (AC) 385V ating voltage Uc (ac), max. Class II ent class acc. to IEC 61643-1 20 kA leakage current (8/20 µs) 40kA ting leakage current (8/20 µs) 100.0kA current, max. (8/20 µs) < 1 µs time 125 A gl fuse, max. 1900V on level Up (typ.) green = OK; red = arrester faulty, replace Monitoring contact installation housing grey/orange -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. Approvals
without telecomm. contact with telecomm. contact 16.0 / 6.0 / 50.0 16.0 / 6.0 / 50.0 91.0 x 72 x 61.0 91.0 x 72 x 61.0
without telecomm. contact 10.0 / 6.0 / 50.0 91.0 x 72 x 61.0
Type PU 3+1 C 275 VAC PU 3+1 CR 275 VAC
Type PU 3+1 C 385 VAC
Information
Order data Version without telecomm. contact with telecomm. contact
Qty. 1 1
Order No. 8416370000 8576190000
Qty. 1
Order No. 8616990000
Information
Accessories Information
Plug-in spare arrester, 280 V PU 0 C 8339510000 Plug-in spare arrester N-PE distance PU 0 C N-PE 8796160000
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
Plug-in spare arrester, 385V PU 0 C 8328670000 Plug-in spare arrester N-PE distance PU 0 C N-PE 8796160000
B.19
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems Class II with varistors
PU 3 C 115 V
PU 4 C 115 V
Class II overvoltage protection
PU 3 C / PU 3 CR 115/230Vac
PU 4 C / PU 4 CR 115/230Vac
with Uc: 130 V • plug-in varistor top section • coded voltage level, diverse voltages • high energy absorption • short time to sparkover • no follow current • thermal and dynamic overcurrent protection • complete 3- or 4-pole modules for TN and TT systems with 100 kA 8/20 µs discharge current
B L1
11 12 14
L3
L2
11 12 14
OK CHANGE
U
OK CHANGE
U
L1
L2
N
L3
OK CHANGE
U
U
OK CHANGE
OK CHANGE
OK CHANGE
U
U
U
OK CHANGE
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 Rated leakage current (8/20 µs) Limiting leakage current (8/20 µs) Leakage current, max. (8/20 µs) Response time Back-up fuse, max. Protection level Up (typ.) Optical function indicator faulty, replace Monitoring contact Design lation housing Colour Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals
Dimensions Clamping range (rating- / min. / max.) Length x width x height
mm2 mm
Technical specification 115V d voltage (AC) 130V ating voltage Uc (ac), max. Class II ent class acc. to IEC 61643-1 20 kA leakage current (8/20 µs) 40kA ting leakage current (8/20 µs) 100.0kA current, max. (8/20 µs) < 25 ns ime 125 A gl fuse, max. 800V ion level Up (typ.) green = OK; red = arrester faulty, replace 250V 1A 1CO contact installation housing grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. UL provals
Technical specification 115V d voltage (AC) 130V ating voltage Uc (ac), max. Class II ent class acc. to IEC 61643-1 20 kA leakage current (8/20 µs) 40kA ting leakage current (8/20 µs) 100.0kA current, max. (8/20 µs) < 25 ns ime 125 A gl fuse, max. 800V ion level Up (typ.) green = OK; red = arrester faulty, replace 250V 1A 1CO contact installation housing grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. UL provals
without telecomm. contact with telecomm. contact 10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0 90.0 x 54 x 61.0 90.0 x 72 x 61.0
without telecomm. contact with telecomm. contact 10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0 90.0 x 72 x 61.0 90.0 x 90 x 61.0
Type PU 3 C 130 VAC PU 3 CR 130 VAC
Type PU 4 C 130 VAC PU 4 CR 130 VAC
Information
Order data Version without telecomm. contact with telecomm. contact
Qty. 1 1
Order No. 8291660000 8291680000
Qty. 1 1
Order No. 8291670000 8291690000
Information
Accessories Information
B.20
Plug-in spare arrester, 130 V PU 0 C 8432430000
Plug-in spare arrester, 130 V PU 0 C 8432430000
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
Class II with varistors
PU 1 C 115 V
PU 2 C 115 V
Class II overvoltage protection
PU 1 C
PU 2 C
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems
with Uc: 130 V • plug-in varistor top section • coded voltage level, diverse voltages • high energy absorption • short time to sparkover • no follow current • thermal and dynamic overcurrent protection
B L1
L1
L2 OK CHANGE
OK CHANGE
U
U
OK CHANGE
U
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 Rated leakage current (8/20 µs) Limiting leakage current (8/20 µs) Leakage current, max. (8/20 µs) Response time Back-up fuse, max. Protection level Up (typ.) Optical function indicator faulty, replace Monitoring contact Design lation housing Colour Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals
Dimensions Clamping range (rating- / min. / max.) Length x width x height
mm2 mm
Technical specification 115V d voltage (AC) 130V ating voltage Uc (ac), max. Class II ent class acc. to IEC 61643-1 20 kA leakage current (8/20 µs) 40kA ting leakage current (8/20 µs) 40.0kA e current, max. (8/20 µs) < 25 ns ime 125 A gl fuse, max. 800V ion level Up (typ.) green = OK; red = arrester faulty, replace Monitoring contact installation housing grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. UL provals
Technical specification 115V d voltage (AC) 130V ating voltage Uc (ac), max. Class II ent class acc. to IEC 61643-1 20 kA leakage current (8/20 µs) 40kA ting leakage current (8/20 µs) 75.0kA e current, max. (8/20 µs) < 25 ns ime 125 A gl fuse, max. 800V ion level Up (typ.) green = OK; red = arrester faulty, replace Monitoring contact installation housing grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. UL provals
without telecomm. contact 10.0 / 6.0 / 50.0 90.0 x 18 x 61.0
without telecomm. contact 10.0 / 6.0 / 50.0 90.0 x 36 x 61.0
Information
Order data Version without telecomm. contact
Type PU 1 C 130 VAC
Qty. 1
Order No. 8215820000
Type PU 2 C 130 VAC
Qty. 1
Order No. 8291650000
Information
Accessories Information
Plug-in spare arrester, 130 V PU 0 C 8432430000
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
Plug-in spare arrester, 130 V PU 0 C 8432430000
B.21
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems Class II with varistors
PU 3 C+CR 385 V
PU 4 C+CR 385 V
Class II overvoltage protection
PU 3 C / PU 3 CR (to Austrian standard 8001 section 18)
PU 4 C / PU 4 CR (to Austrian standard 8001 section 18)
with Uc: 385 V • suitable for IT networks • plug-in varistor top section • coded voltage level, diverse voltages • high energy absorption • short time to sparkover • no follow current • installed in Insta distributor • thermal and dynamic overcurrent protection
B
• complete 3- or 4-pole modules with 100 kA 8/20 µs discharge current
L1
11 12 14
L3
L2
1112 14 OK CHANGE
OK CHANGE
L1
U
N
OK CHANGE OK CHANGE
OK CHANGE
U
L3
L2
U
U
U
OK CHANGE
U
OK CHANGE
U
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 Rated leakage current (8/20 µs) Limiting leakage current (8/20 µs) Leakage current, max. (8/20 µs) Response time Back-up fuse, max. Protection level Up (typ.) Optical function indicator faulty, replace Monitoring contact Design lation housing Colour Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals
Dimensions Clamping range (rating- / min. / max.) Length x width x height
mm2 mm
Technical specification 230V d voltage (AC) 385V ating voltage Uc (ac), max. Class II ent class acc. to IEC 61643-1 20 kA leakage current (8/20 µs) 40kA ting leakage current (8/20 µs) 100.0kA current, max. (8/20 µs) < 25 ns ime 125 A gl fuse, max. 1500V on level Up (typ.) green = OK; red = arrester faulty, replace 250V 1A 1CO contact installation housing grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. UL provals
Technical specification 230V d voltage (AC) 385V ating voltage Uc (ac), max. Class II ent class acc. to IEC 61643-1 20 kA leakage current (8/20 µs) 40kA ting leakage current (8/20 µs) 100.0kA current, max. (8/20 µs) < 25 ns ime 125 A gl fuse, max. 1500V on level Up (typ.) green = OK; red = arrester faulty, replace 250V 1A 1CO contact installation housing grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. Approvals
without telecomm. contact with telecomm. contact 10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0 90.0 x 54 x 61.0 90.0 x 72 x 61.0
without telecomm. contact with telecomm. contact 10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0 90.0 x 72 x 61.0 90.0 x 91 x 61.0
Type PU 3 C 385 VAC PU 3 CR 385 VAC
Type PU 4 C 385 VAC PU 4 CR 385 VAC
Information
Order data Version without telecomm. contact with telecomm. contact
Qty. 1 1
Order No. 8197930000 8380730000
Qty. 1 1
Order No. 8601280000 8494040000
Information
Accessories Information
B.22
Plug-in spare arrester, 385V PU 0 C 8328670000
Plug-in spare arrester, 385V PU 0 C 8328670000
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
Class II with varistors
PU 3 C+CR 470 V
PU 4 C+CR 470 V
Class II overvoltage protection
PU 3 C / PU 3 CR 470/690Vac
PU 4 C / PU 4 CR 470/690Vac
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems
with Uc: 550 V • plug-in varistor top section • coded voltage level, diverse voltages • high energy absorption • short time to sparkover • no follow current • installed in Insta distributor • thermal and dynamic overcurrent protection • coordination between class I with Up:< 1.5 kV
B L1
11 12 14
U
L3
L2
1112 14
OK CHANGE
OK CHANGE
U
U
L1
OK CHANGE
OK CHANGE
OK CHANGE
U
L3
L2
U
N OK CHANGE
U
OK CHANGE
U
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 Rated leakage current (8/20 µs) Limiting leakage current (8/20 µs) Leakage current, max. (8/20 µs) Response time Back-up fuse, max. Protection level Up (typ.) Optical function indicator faulty, replace Monitoring contact Design lation housing Colour Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals
Dimensions Clamping range (rating- / min. / max.) Length x width x height
mm2 mm
Technical specification 470V d voltage (AC) 550V ating voltage Uc (ac), max. Class II ent class acc. to IEC 61643-1 20 kA leakage current (8/20 µs) 40kA ting leakage current (8/20 µs) 100.0kA current, max. (8/20 µs) < 25 ns ime 125 A gl fuse, max. 2200V on level Up (typ.) green = OK; red = arrester faulty, replace 250V 1A 1CO contact installation housing grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. UL provals
Technical specification 470V d voltage (AC) 550V ating voltage Uc (ac), max. Class II ent class acc. to IEC 61643-1 20 kA leakage current (8/20 µs) 40kA ting leakage current (8/20 µs) 100.0kA current, max. (8/20 µs) < 25 ns ime 125 A gl fuse, max. 2200V on level Up (typ.) green = OK; red = arrester faulty, replace 250V 1A 1CO contact installation housing grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. UL provals
without telecomm. contact with telecomm. contact 10.0 / 6.0 / 10.0 10.0 / 6.0 / 10.0 90.0 x 54 x 61.0 90.0 x 72 x 61.0
without telecomm. contact with telecomm. contact 10.0 / 6.0 / 50.0 10.0 / 6.0 / 50.0 90.0 x 72 x 60.0 90.0 x 90 x 60.0
Type PU 3 C 550 VAC PU 3 CR 550 VAC
Type PU 4 C 550 VAC PU 4 CR 550 VAC
Information
Order data Version without telecomm. contact with telecomm. contact
Qty. 1 1
Order No. 8451050000 8451060000
Qty. 1 1
Order No. 8291720000 8451070000
Information
Accessories Information
Plug-in spare arrester, 550 V PU 0 C 8451080000
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
Plug-in spare arrester, 550 V PU 0 C 8451080000
B.23
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems Class II with varistors
PU 1 C 470 V
PU 2 C 470 V
Class II overvoltage protection
PU 1 C
PU 2 C
with Uc: 550 V • plug-in varistor top section • coded voltage level, diverse voltages • high energy absorption • short time to sparkover • no follow current • installed in Insta distributor • thermal and dynamic overcurrent protection • coordination between class I with Up:< 1.5 kV
B L1
L1 OK CHANGE
L2 OK CHANGE
U
U
OK CHANGE
U
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 Rated leakage current (8/20 µs) Limiting leakage current (8/20 µs) Leakage current, max. (8/20 µs) Response time Back-up fuse, max. Protection level Up (typ.) Optical function indicator faulty, replace Monitoring contact Design lation housing Colour Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals
Dimensions Clamping range (rating- / min. / max.) Length x width x height
mm2 mm
Technical specification 470V d voltage (AC) 550V ating voltage Uc (ac), max. Class II ent class acc. to IEC 61643-1 20 kA leakage current (8/20 µs) 40kA ting leakage current (8/20 µs) 40.0kA e current, max. (8/20 µs) < 25 ns ime 125 A gl fuse, max. 2200V on level Up (typ.) green = OK; red = arrester faulty, replace Monitoring contact installation housing grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. UL provals
Technical specification 470V d voltage (AC) 550V ating voltage Uc (ac), max. Class II ent class acc. to IEC 61643-1 20 kA leakage current (8/20 µs) 40kA ting leakage current (8/20 µs) 75.0kA e current, max. (8/20 µs) < 25 ns ime 125 A gl fuse, max. 2200V on level Up (typ.) green = OK; red = arrester faulty, replace Monitoring contact installation housing grey ur -40°C/60°C temp. min./Operating temp. max. -40°C/80°C mp. min./Storage temp., max. UL provals
without telecomm. contact 10.0 / 6.0 / 50.0 90.0 x 18 x 61.0
without telecomm. contact 10.0 / 6.0 / 50.0 90.0 x 36 x 61.0
Information
Order data Version without telecomm. contact
Type PU 1 C 550 VAC
Qty. 1
Order No. 8291700000
Type PU 2 C 550 VAC
Qty. 1
Order No. 8291710000
Information
Accessories Information
B.24
Plug-in spare arrester, 550 V PU 0 C 8451080000
Plug-in spare arrester, 550 V PU 0 C 8451080000
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
B
B.25 Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies Low-voltage consumers, small distribution boards and electronic components Overvoltage protection class III (D charge eliminators)
Our overvoltage protection PU D protects low-voltage consumers and electronic devices from overvoltage caused by atmospheric discharges (thunderstorm) or switching procedures (transients). The PU D can be mounted in small or storey distribution boards.
B
PU D corresponds to the requirements of DIN VDE 0675, part 6, class C, 11/89, part 6, A2 10/96 and IEC 61643-1 02/98. Electrical connection PU D overvoltage protection is installed after the PU C before the device/consumer being protected. It can protect circuits up to 16 A. For example, an installation for a circuit in small distribution boards can be used to protect a monitor. Functional checks and maintenance Ageing of the varistors can cause high temperatures at the varistors. In low voltage systems, this can cause a fire. The integrated temperature monitoring automatically disconnects the varistor from the power supply. This is indicated by the glow lamp going off. Types PO DS also equipped with a switching contact to report this. The back-up fuse depends on the conductor cross-section and type of routing. For PU D charge eliminators, the maximum power rating is up to 16 A. The connection is rated to IEC 947-7-1 for the following cross-sections: solid conductor: 0,5...2,5 mm2 flexible conductor: 0,5...2,5 mm2 The operating temperature range is from –25 °C ... +55 °C, and the storage temperature range is from –40 °C ... +60 °C betragen.
B.26
Dimensioned drawing PU DS Overall width 18 mm
Class III with varistors
PU DS 230Vac 16A
PU DS 115Vac/dc 16A
Class III overvoltage arrester
PU DS 230Vac 16A
PU DS 115Vac/dc 16A
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems
B
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 Combined pulse Uoc Rated discharge current per path (8/20 µs) Leakage current, max. (8/20 µs) Response time Back-up fuse, max. Protection level Up (typ.) Optical function indicator Monitoring contact Design lation housing Colour Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals
Dimensions Clamping range (rating- / min. / max.) Length x width x height
mm2 mm
Technical specification 230V d voltage (AC) 275V ating voltage Uc (ac), max. Class III nt class acc. to IEC 61643-1 4kV ed pulse Uoc Rated discharge current per path (8/20 µs) 5.0kA ge current, max. (8/20 µs) < 150 ns me 16 A -up fuse, max. 1500V on level Up (typ.) green LED = OK on indicator 250V 1A 1CO contact installation housing grey ur -30°C/70°C temp. min./Operating temp. max. -40°C/70°C mp. min./Storage temp., max. Approvals
Technical specification 115V d voltage (AC) 130V ating voltage Uc (ac), max. Class III nt class acc. to IEC 61643-1 4kV ed pulse Uoc Rated discharge current per path (8/20 µs) 5.0kA ge current, max. (8/20 µs) < 150 ns me 16 A -up fuse, max. 850V ion level Up (typ.) green LED = OK on indicator 250V 1A 1CO contact installation housing grey ur -30°C/70°C temp. min./Operating temp. max. -40°C/70°C mp. min./Storage temp., max. Approvals
screw connection 2.5 / 0.5 / 2.5 91.0 x 18 x 61.0
screw connection 2.5 / 0.5 / 2.5 91.0 x 18 x 61.0
Information
Order data Type PU DS 230VAC 16A
Qty. 1
Order No. 8523740000
Type PU DS 115VAC 16A
Qty. 1
Order No. 8568650000
Information
Accessories Information
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
B.27
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems Class III with varistors
PU DS 48Vac/dc 16A
PU DS 24Vac/dc 16A
Class III overvoltage arrester
PU DS 48Vac/dc 16A
PU DS 24Vac/dc 16A
Technical specification 48V ed voltage (AC) 60V rating voltage Uc (ac), max. Class III nt class acc. to IEC 61643-1 4kV ed pulse Uoc 2.50kA discharge current per path (8/20 µs) 5.0kA ge current, max. (8/20 µs) < 150 ns me 16 A -up fuse, max. 1100V on level Up (typ.) green LED = OK on indicator 250V 1A 1CO contact installation housing grey ur -30°C/70°C temp. min./Operating temp. max. -40°C/70 temp. min./Storage temp., max. Approvals
Technical specification 24V ed voltage (AC) 30V rating voltage Uc (ac), max. Class III nt class acc. to IEC 61643-1 4kV ed pulse Uoc 1kA discharge current per path (8/20 µs) 2.0kA ge current, max. (8/20 µs) < 150 ns me 16 A -up fuse, max. 1100V on level Up (typ.) green LED = OK on indicator 250V 1A 1CO contact installation housing grey ur -30°C/70°C temp. min./Operating temp. max. -40°C/70°C mp. min./Storage temp., max. Approvals
screw connection 2.5 / 0.5 / 2.5 91.0 x 18 x 61.0
screw connection 2.5 / 0.5 / 2.5 91.0 x 18 x 61.0
B
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 Combined pulse Uoc Rated discharge current per path (8/20 µs) Leakage current, max. (8/20 µs) Response time Back-up fuse, max. Protection level Up (typ.) Optical function indicator Monitoring contact Design lation housing Colour Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals
Dimensions Clamping range (rating- / min. / max.) Length x width x height
mm2 mm
Information
Order data Type PU DS 48V 16A
Qty. 1
Order No. 8670740000
Type PU DS 24Vuc 16A
Qty. 1
Order No. 8682100000
Information
Accessories Information
B.28
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
Class III with varistors
PU D 230Vac 16A
PU D 115Vac 16A
Class III overvoltage arrester
PU D 230Vac 16A
PU D 115Vac 16A
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems
B L
L
U
OK
FAULT
U
N PE
L
L
11
U
12
U
N PE
OK
FAULT
11 12
N PE
N PE
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 Combined pulse Uoc Rated discharge current per path (8/20 µs) Leakage current, max. (8/20 µs) Response time Back-up fuse, max. Protection level Up (typ.) Optical function indicator fault Monitoring contact Design lation housing Colour Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals
Dimensions Clamping range (rating- / min. / max.) Length x width x height
mm2 mm
Technical specification 230V d voltage (AC) 275V ating voltage Uc (ac), max. Class III nt class acc. to IEC 61643-1 4kV ed pulse Uoc 2.50kA discharge current per path (8/20 µs) 7.0kA ge current, max. (8/20 µs) < 150 ns me 16 A -up fuse, max. 850V ion level Up (typ.) green LED = OK; red LED = fault 250V 1A 1CO contact installation housing grey ur -25°C/55°C temp. min./Operating temp. max. -40°C/55°C mp. min./Storage temp., max. Approvals
Technical specification 115V d voltage (AC) 130V ating voltage Uc (ac), max. Class III nt class acc. to IEC 61643-1 4kV ed pulse Uoc 2.50kA discharge current per path (8/20 µs) 7.0kA ge current, max. (8/20 µs) < 150 ns me 16 A -up fuse, max. 480V ion level Up (typ.) green LED = OK; red LED = fault 250V 1A 1CO contact installation housing grey ur -25°C/55°C temp. min./Operating temp. max. -40°C/55°C mp. min./Storage temp., max. Approvals
screw connection 2.5 / 0.5 / 2.5 91.0 x 54 x 61.0
screw connection 2.5 / 0.5 / 2.5 91.0 x 54 x 61.0
Information
Order data Type PU D 230V 16A
Qty. 1
Order No. 8411930000
Type PU D 115Vac 16A
Qty. 1
Order No. 8472100000
Information
Accessories Information
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
B.29
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems Class III with varistors
PU 3 D 230V/400Vac 16A
PO DS 230V 16A/ PO DAS 230V/16A
Class III overvoltage arrester
PU 3 D 230V/400Vac 16A
PO DAS 230V/16A
B L1 L2 L3
L1 L2 L3
L1
L2
L
11
L3
12
U
FAULT FAULT FAULT
N
N
N
PE
PE
FAULT
PE
Technical data Technical specification Rated voltage (AC) Operating voltage Uc (ac), max. Requirement class acc. to IEC 61643-1 Combined pulse Uoc Rated discharge current per path (8/20 µs) Leakage current, max. (8/20 µs) Response time t;100 ns Back-up fuse, max. Protection level Up (typ.) Optical function indicator fault Monitoring contact Design lation housing Colour Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. Approvals
Dimensions Clamping range (rating- / min. / max.) Length x width x height
mm2 mm
Technical specification 230V d voltage (AC) 275V ating voltage Uc (ac), max. Class III nt class acc. to IEC 61643-1 4kV ed pulse Uoc 6.50kA discharge current per path (8/20 µs) 18.0kA e current, max. (8/20 µs) < 150 ns <100 ns 16 A -up fuse, max. 850V ion level Up (typ.) green LED = OK; red LED = fault 250V 1A 1CO contact installation housing grey ur -25°C/55°C temp. min./Operating temp. max. -40°C/55°C mp. min./Storage temp., max. Approvals
Technical specification 230V d voltage (AC) 275V ating voltage Uc (ac), max. Class III nt class acc. to IEC 61643-1 4kV ed pulse Uoc 2.50kA discharge current per path (8/20 µs) 5.0kA ge current, max. (8/20 µs) sym/ asym: <100 ns 16 A -up fuse, max. 1500V on level Up (typ.) green LED = OK; red LED = fault Monitoring contact miscellaneous housing black r -25°C/55°C temp. min./Operating temp. max. -40°C/60°C mp. min./Storage temp., max. Approvals
screw connection 2.5 / 0.5 / 2.5 91.0 x 54 x 61.0
screw connection
screw connection
41.0 x 20 x 41.0
41.0 x 12 x 41.0
Information
Order data Type PU 3D 230V/400Vac 16A
Information
Qty. 1
Order No. 8509130000
Type PO D AS PO D S
Qty. 1 1
Order No. 8581830000 8581840000
PO D AS with audible signal
Accessories Information
B.30
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
B
B.31 Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies
B
Overvoltage Protection for low-voltage supplies PU D ZS plug-in Overvoltage Protection Class III overvoltage protection
The PU D ZS plug-in overvoltage protection device provides protection against transient overvoltages for equipment plugged into earthed power sockets. The plug-in overvoltage protection with its earthed power socket is designed for 230 V/16 A, fulfils the requirements of class III to IEC 61643-1 and is used in conjunction with class II, the PU C protection. The PU D ZS is fitted with components to monitor varistor temperature. In the event of an excessive temperature rise due to pulses from the mains supply, these disconnect the unit. The integral red warning lamp indicates that protection is no longer provided. The PU D ZS must then be replaced. The PU D ZS analog plug-in overvoltage protection device provides protection against transient overvoltages for equipment and analogue devices plugged into earthed power sockets. Besides the use of standard telephones, an analogue installation can also transmit data services like fault signalling systems and Internet. The fact that besides telephones other devices like fax machines and modems are also connected to the analogue line means that the hazards due to transient interference phenomena like overvoltages are on the increase. In order to achieve protection against these overvoltages, combined overvoltage protection for analogue lines and mains voltages is incorporated. The basic version of this power socket adapter is protected by two-stage overvoltage protection achieved with gas discharge tube and fast-acting suppression diodes. The gas discharge tube achieves a high energy discharge; the suppression diodes ensure a low residual voltage. The PU D ZS digital plug-in overvoltage protection provides protection against transient overvoltages for equipment and digital devices plugged into earthed power sockets. This power socket adapter is available for Uko and So interfaces. In order to achieve protection against these overvoltages, combined overvoltage protection for digital lines and mains voltages is incorporated. The basic version of this power socket adapter is protected by two-stage overvoltage protection achieved with gas discharge tube and fast-acting suppression diodes. The gas discharge tube achieves a high energy discharge; the suppression diodes ensure a low residual voltage. In the PU D ZS with the RJ45 sockets a connecting line with RJ45 plugs at both ends is included with the product.
B.32
Dimensioned drawing PU D ZS
Class III adapter plug
PU D ZS So
PU D ZS
Class III overvoltage arrester
PU D ZS So 230V 16A
PU D ZS analog 230V 16A
L
POWER
FAULT
L
POWER
L
B
230V~
N PE 1a
L
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems
FAULT
N PE PHONE
230V~
N PE
1a'
1b 2a
1b' 2a'
Lb(+)
2b
2b'
LA(-)
N PE PHONE
Lb' La'
Technical data Rated voltage (AC) Operating voltage Uc (ac), max. Operating current, Imax According to DIN VDE 0675-6 Requirement class acc. to IEC 61643-1 Combined pulse Uoc
230V d voltage (AC) 275V ating voltage Uc (ac), max. 16A ing current, Imax requirement class D E 0675-6 Class III nt class acc. to IEC 61643-1 4kV ed pulse Uoc
230V d voltage (AC) 275V ating voltage Uc (ac), max. 16A ing current, Imax requirement class D E 0675-6 Class III nt class acc. to IEC 61643-1 4kV ed pulse Uoc
Leakage current, max. (8/20 µs) Back-up fuse, max. Response time On output side sym., input 8/20 µs, typical Output side unsym., input 8/20 µs, typical Leakage current at Un Optical function indicator fault Pollution severity
5.0kA ge current, max. (8/20 µs) 16 A -up fuse, max. < 150 ns me 600V utput side sym., input 8/20 µs, typical 1500V t side unsym., input 8/20 µs, typical 1µA e current at Un green LED = OK; red LED = fault 2 ollution severity
5.0kA ge current, max. (8/20 µs) 16 A -up fuse, max. < 150 ns me 600V utput side sym., input 8/20 µs, typical 1500V t side unsym., input 8/20 µs, typical 1µA e current at Un green LED = OK; red LED = fault 2 ollution severity
Overvoltage category Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. General data Input voltage max. nominal current In, max. Norm Signal lephone signal RJ45/RJ11/12 Rated leakage current (8/20 µs) Total current Response time, type Resistance per path Cut-off frequency fg, 600 M-System Transistor output, positive-switching Residual voltage at output at input pulse of 1 kV/µs Residual voltage at output at 8/20µs and input pulse of 5kA
Dimensions Clamping range (rating- / min. / max.) Length x width x height Information
mm2 mm
III rvoltage category 0°C/60°C g temp. min./Operating temp. max. -25°C/85°C mp. min./Storage temp., max. General data 190V t voltage max. 0.45A al current In, max. ISDN telephone signal RJ45/RJ11/12 1/12 4 kA d leakage current (8/20 µs) 10A al current < 5 ns se time, type 1.1 Ω per path 80 MHz f frequency fg, 600 M-System Transistor output, positive-switching a/b <= 270V a-b/PE <= 270V at input pulse of 1 kV/µs a/b<= 100V a-b/PE<= 100V ut at 8/20µs and input pulse of 5kA
III rvoltage category 0°C/60°C g temp. min./Operating temp. max. -25°C/85°C mp. min./Storage temp., max. General data 190V DC oltage max. 0.45A al current In, max. Analogue telephone signal RJ45/RJ11/12 4 kA d leakage current (8/20 µs) 10A al current < 5 ns se time, type 1.1 Ω per path 2 MHz ff frequency fg, 600 M-System a/b <= 270V a-b/PE <= 270V e-switching Residual voltage at output at input pulse of 1 kV/µs a/b<= 100V a-b/PE<= 100V ut at 8/20µs and input pulse of 5kA
Earthed contact
Earthed contact
110.0 x 62 x 48.0
110.0 x 62 x 48.0
incl. conductor, RJ 11/12 both ends
incl. conductor, RJ 11/12 both ends
Order data Version
Type PU D ZS 230V~ 16A / ISDN So
Qty. 1
Order No. 8697560000
Type PU D ZS 230V~ 16A / analog a/b
Qty. 1
Order No. 8697600000
Information
Accessories Information
Conductor, RJ 45 at both ends, order no. 8697590000
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
Conductor, RJ45 on both sides, order no. 8697590000
B.33
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems Class III adapter plug
PU D ZS Uko
PU D ZS 230V 16A
Class III overvoltage arrester
PU D ZS Uko 230V 16A
PU D ZS 230V 16A
L
B
POWER
FAULT
L
POWER
L
230V~
N PE Lb(+)
L
N PE PHONE
La(-)
FAULT
230V~
N PE
Lb'
N PE
La'
Technical data Rated voltage (AC) Operating voltage Uc (ac), max. Operating current, Imax According to DIN VDE 0675-6 Requirement class acc. to IEC 61643-1 Combined pulse Uoc
230V d voltage (AC) 275V ating voltage Uc (ac), max. 16A ing current, Imax requirement class D E 0675-6 Class III nt class acc. to IEC 61643-1 4kV ed pulse Uoc
230V d voltage (AC) 275V ating voltage Uc (ac), max. 16A ing current, Imax requirement class D E 0675-6 Class III nt class acc. to IEC 61643-1 4kV ed pulse Uoc
Leakage current, max. (8/20 µs) Back-up fuse, max. Response time On output side sym., input 8/20 µs, typical Output side unsym., input 8/20 µs, typical Leakage current at Un Optical function indicator fault Pollution severity
5.0kA ge current, max. (8/20 µs) 16 A -up fuse, max. < 150 ns me 600V utput side sym., input 8/20 µs, typical 1500V t side unsym., input 8/20 µs, typical 1µA e current at Un green LED = OK; red LED = fault 2 ollution severity
5.0kA ge current, max. (8/20 µs) 16 A -up fuse, max. < 150 ns me 600V utput side sym., input 8/20 µs, typical 1500V t side unsym., input 8/20 µs, typical 1µA e current at Un green LED = OK; red LED = fault 2 ollution severity
Overvoltage category Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. General data Input voltage max. nominal current In, max. Norm Signal one signal RJ45/RJ11/12 Rated leakage current (8/20 µs) Total current Response time, type Resistance per path Cut-off frequency fg, 600 M-System Transistor output, positive-switching Residual voltage at output at input pulse of 1 kV/µs Residual voltage at output at 8/20µs and input pulse of 5kA
Dimensions Clamping range (rating- / min. / max.) Length x width x height Information
mm2 mm
III rvoltage category 0°C/60°C g temp. min./Operating temp. max. -25°C/85°C mp. min./Storage temp., max. General data 190V DC oltage max. 0.45A al current In, max. ISDN telephone signal RJ45/RJ11/12 4 kA d leakage current (8/20 µs) 10A al current < 5 ns se time, type 1.1 Ω per path 80 MHz f frequency fg, 600 M-System Transistor output, positive-switching a/b <= 270V a-b/PE <= 270V at input pulse of 1 kV/µs a/b<= 100V a-b/PE<= 100V ut at 8/20µs and input pulse of 5kA
III rvoltage category 0°C/60°C g temp. min./Operating temp. max. -25°C/85°C mp. min./Storage temp., max. General data Input voltage max. nominal current In, max. ISDN telephone signal RJ45/RJ11/12 Rated leakage current (8/20 µs) Total current Response time, type Resistance per path Cut-off frequency fg, 600 M-System Transistor output, positive-switching Residual voltage at output at input pulse of 1 kV/µs Residual voltage at output at 8/20µs and input pulse of 5kA
Earthed contact
Earthed contact
110.0 x 62 x 48.0
110.0 x 62 x 48.0
incl. conductor, RJ 11/12 both ends
Order data Version
Type PU D ZS Uko 230V 16A
Qty. 1
Order No. 8697570000
Type PU D ZS 230V~ 16A
Qty. 1
Order No. 8697580000
Information
Accessories Information
B.34
Conductor, RJ 45 at both ends, order no. 8697590000
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
Class III adapter plug
PU D ZS TV/R
Class III overvoltage protection
PU D ZS TV/R 230V 16A
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for energy distribution systems
for signals up to 1 GHz (radio/TV )
L
POWER
FAULT
L
N PE TV
B
230V~
N PE TV/R +
TV +
+
R
R
Technical data Rated voltage (AC) Operating voltage Uc (ac), max. Operating current, Imax According to DIN VDE 0675-6 Requirement class acc. to IEC 61643-1 Combined pulse Uoc
230V d voltage (AC) 275V ating voltage Uc (ac), max. 16A ing current, Imax requirement class D E 0675-6 Class III nt class acc. to IEC 61643-1 4kV ed pulse Uoc
Leakage current, max. (8/20 µs) Back-up fuse, max. Response time On output side sym., input 8/20 µs, typical Output side unsym., input 8/20 µs, typical Leakage current at Un Optical function indicator fault Pollution severity
5.0kA ge current, max. (8/20 µs) 16 A -up fuse, max. < 150 ns me 600V utput side sym., input 8/20 µs, typical 1500V t side unsym., input 8/20 µs, typical 1µA e current at Un green LED = OK; red LED = fault 2 ollution severity
Overvoltage category Operating temp. min./Operating temp. max. Storage temp. min./Storage temp., max. General data Input voltage max. nominal current In, max. Norm Signal trial and cable Rated leakage current (8/20 µs) Total current Response time, type Resistance per path Cut-off frequency fg, 600 M-System Transistor output, positive-switching Residual voltage at output at input pulse of 1 kV/µs Residual voltage at output at 8/20µs and input pulse of 5kA
III rvoltage category 0°C/60°C g temp. min./Operating temp. max. -25°C/85°C mp. min./Storage temp., max. General data 70 put voltage max. 1.50 nal current In, max. TV/R terrestrial and cable 5 kA d leakage current (8/20 µs) Total current < 100 ns time, type 1.1 Ω per path 1 GHz / 75 M ncy fg, 600 M-System Transistor output, positive-switching 600 V ual voltage at output at input pulse of 1 kV/µs 800 V ual voltage at output at 8/20µs and input pulse of 5kA
Dimensions Clamping range (rating- / min. / max.) Length x width x height
Earthed contact mm2 mm
110.0 x 62 x 48.0
Information
Order data Version
Type PU D ZS TV/R
Information
Coaxial cable approx. 35 cm long in each case
Qty. 1
Order No. 8779230000
Accessories Information
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
B.35
Overvoltage Protection for low-voltage supplies
B
Overvoltage Protection for low-voltage supplies Overvoltage Protection mains filter WAVEFILTER
WAVEFILTERS for simple radio interferences suppression in the switching cabinet
Insertion loss
The WAVEFILTER series eliminates the time-consuming need to screw in mains filters. These filters are simply clipped on to the TS35 and connected to the device needing suppression. The two-stage WAVEFILTER with overall width 22.5 mm in designs 1 A, 3 A, 6 A and 10 A offers high attenuation.
1 A WAVEFILTER
The WAVEFILTER with current-compensating choke is ideal for applications in drive technology and control/automation technology, e.g. for suppressing continuous interference types such as “noise” or “ripple” from interfering radiation from other systems or interference from frequency converters and switched-mode power supplies. A short, low-ohm mass connection is required for the WAVEFILTER to function perfectly. We recommend earthing all devices directly with the largest possible cross-section to a central earthing point in the switching cabinet.
3 A WAVEFILTER
Interference signals We distinguish between two types of induced transient and continuous interference signals: Symmetrical (differential mode) and asymmetrical (common mode). The symmetrical interference signals generate voltage between the signal leads of the system. The asymmetrical interference voltages occur between the signal leads and earth. The WAVEFILTER is suitable of attenuating both kinds of interference signal. In addition, WAVEFILTER 10 A also has an earthing conductor choke. This earthing conductor choke supports both attenuation on the earthing conductor for the filter and additional attenuation of asymmetrical interference voltages.
B.36
6 A WAVEFILTER
10 A WAVEFILTER
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies
,
,
,
,
,
,
B
B.37
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies Overvoltage Protection Mains filter
WAVEFILTER 1 A
WAVEFILTER 6 A
Wavefilter 1 A 250 V
Wavefilter 6 A 250 V
B LOAD
LINE L
L'
L
Cx
L'
Cx
N
N'
Cy
LOAD
LINE
N
Cy
N'
Cy
Cy
Technical data Technical specification Rated voltage (AC/DC) Rated current Capacitance Inductance L and L1 Leakage current at Un Test voltage P/N-PE Test voltage P-N Operating temp., min./Operating temp., max.
Dimensions Clamping range (nom./min./max) length x width x height Note
mm2 mm
250V 1A 33nF 10mH 190µA 2000Vac 1700Vdc -20°C/40°C
250V 6A 33nF Cx 22nF Cy 0.80mH 190µA 2000Vac 1700Vdc -20°C/40°C
2.50 / 0.50 / 2.50 90 x 22.5 x 73.40
2.50 / 0.50 / 2.50 90 x 22.5 x 73.40
See attenuation diagram
See attenuation diagram
Ordering data Version
Type WAVEFILTER 1A
VPE 1
Order No. 8614790000
Type WAVEFILTER 6A
VPE 1
Order No. 8614800000
Note
Accessories Note
B.38
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
Overvoltage Protection Mains filter
WAVEFILTER 3 A
WAVEFILTER 10 A
Wavefilter 3 A 250 V
Wavefilter 10 A 250 V
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies
B LOAD
LINE L
L'
L
Cx
L'
Cx
N
N'
Cy
LOAD
LINE
N
Cy
N'
Cy
Cy
Technical data Technical specification Rated voltage (AC/DC) Rated current Capacitance Inductance L and L1 Leakage current at Un Test voltage P/N-PE Test voltage P-N Operating temp., min./Operating temp., max.
Dimensions Clamping range (nom./min./max) length x width x height Note
mm2 mm
250V 3A 33nF 2mH 190µA 2000Vac 1700Vdc -20°C/40°C
250V 10A 470nF Cx 4.7nF Cy 0.80mH 190µA 2000Vac 1700Vdc -20°C/40°C
2.50 / 0.50 / 2.50 90 x 22.5 x 73.40
2.50 / 0.50 / 2.50 90 x 22.5 x 73.40
See attenuation diagram
See attenuation diagram
Ordering data Version
Type WAVEFILTER 3A
VPE 1
Order No. 8614780000
Type WAVEFILTER 10A
VPE 1
Order No. 8614770000
Note
Accessories Note
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany. Delivery times see page X.8
B.39
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies Installation specification for our PU Overvoltage Protection in power supply networks
The overvoltage protection may only be installed by suitably qualified personnel.During the installation, please observe the connection conditions specific to the country of application.
part 534 (Apr 1999) “Selection and installation of equipment”. This draft standard should be used in conjunction with the following standards: 1. IEC 60364-4-43 “Protection from overvoltage due to atmospheric influences and switching operations”
B
2. IEC 61024-1 “Protection of buildings against lightning” 3. IEC 61312-1 “Protection against electromagnetic lightning pulses” 2.2 Electrical connection
1. Application The PU C overvoltage protection to class C (class II) protects low-voltage consumer installations and electronic devices against overvoltages that can occur as a result of atmospheric discharges (thunderstorms) or switching operations. The PU C complies with VDE 0675 part 6, class C (draft, Nov 1989), DIN VDE 0675 part 6, A2 (Oct 1996), IEC 61643-1 (Feb 1998) and ÖVE SN 60 parts 1 and 4. High-power metal oxide varistors are employed as the voltage-limiting component. The PU B is a class B (class I) lightning arrester complying with DIN VDE 0675 part 6 (Nov 1989), IEC 61643-1 (Feb 1998), ENV 61024-1 (Jan 1995) and IEC 1312-1 (Feb 1995). The integral varistors create the necessary equipotential bonding (lightning protection equipotential bonding according to DIN VDE 0185 part 1, Nov 1982) between the building’s lightning protection and the earthing system of the power supply during lightning strikes. The PU D overvoltage protection to class D (class III) protects low-voltage consumer installations and electronic devices against overvoltages and switching operations. The PU D is integrated in addition after the PU C in small/storey distribution boards. The PU D complies with DIN VDE 0675 part 6, classD (draft, Nov 1989), DIN VDE 0675 part 6, A2 (Oct 1996) and IEC 61643-1 (Feb 1998). 2. Installation specifications 2.1 Place of installation The PU C must be incorporated in a meter cupboard or distribution board in such a way that the connection terminal compartment is not accessible to unauthorised persons. The PU B is incorporated near the incoming power lines in order to create the necessary lightning protection equipotential bonding between the lightning protection system and the power distribution network. All arresters must be installed by a qualified electrician. The installation of systems with overvoltage protection devices is described in VDE 0100
B.40
The lines connecting the PU C overvoltage protection and the PU B lightning arrester between the phase conductor (L1, L2, L3) or neutral conductor (N) and earth (PE) of the consumer installation should be kept as short as possible. The routing of protected and unprotected lines together must be avoided. (See diagrams on pp. 70-71 for examples of connections.) 2.2.1 Connection to phase conductor and neutral conductor As a rule, the conductor cross-section for the connection lines to the PU C or PU B arrester is selected as for the phase conductor (L1, L2, L3) and neutral conductor (N). If a reduced cross-section is desired, a protective device (e.g. main terminal fuse) must guarantee short-circuit protection for the connecting lines. The connection terminals on the arresters may not be used as branch terminals. The backup fuse for the PU C should not exceed 125 A gL. Upstream residual-current circuit-breakers (RCD) type S (3 kA, 8/20 µs) must be able to withstand surge currents.The backup fuse for the PU B should not exceed 160 A gL. Note: Three-pole PU C devices are employed in a TN-CS system (fig. 2). If the PE and N conductors of the PEN conductor are routed separately, a four-pole PU should be used. In a TT system, a four-pole PU C protector can be installed together with an arrester disconnector according to DIN VDE 0100534/A1 (Oct 1996). To avoid accidental energisation between PE and N and to be able to omit arrester disconnectors, the PU 4 C TT module (Part No. 8416370000) provides the best solution (3+1 circuit). A 385 V PU 3 C is installed in an IT system with 400 V phase-to-phase voltage. 2.2.2 Installation of D arrester The PU D arrester is installed in conjunction with a PU C, in the downstream direction. The PU D is incorporated in the line to be protected and can protect circuits up to 16 A. The installation can be carried out in small distribution boards for single circuits protecting, for example, monitors. The PO DS is suitable for incorporating in situ, directly in devices or cable ducts.
2.2.3 Connection to earth The earth line of the arrester is connected to the earth of the consumer installation via the shortest route (= 0.5 m). Longer connecting lines reduce the effectiveness of the overvoltage protection. Routing the line parallel with other electrical cables should be avoided. In electrical consumer installations with equipotential bonding, an earthed equipotential bonding rail is available as a connection point (see p. 56 ”Principles for low-voltage supplies”). A connection between the arrester earth and the consumer installation earth must always be guaranteed. In TN systems the PEN conductor and the arrester earth line should be connected together. The PEN conductor of the power supply company may not be used as an earth. If the PE or PEN rail of a distribution board is used as an earth connection point, it is then necessary for this rail to be connected to the consumer installation earth via a separate earth line. Two earth connection terminals are available on the PU B. Both terminals must be connected. One connection goes to the equipotential bonding connection of the building, the other to the PE conductor of the installation. The cross-section for the earth line of the arrester is determined, as for lines, according to table 1 for the main equipotential bonding. It must be min. 0.5 times the cross-section of the main protective conductor, where 25 mm2 copper is taken to be the upper limit and 10 mm2 copper the lower limit.
Earth line Main protective conductor – coming from current source or protective conductor leaving – incoming service box or – main distribution board Phase conductor Earth line of arrester
Cross-section mm2) ≤ 16
25
≤ 35
PUxBR and PU D by a switch contact as well. The backup fuse should be selected depending on the cross-section of the line and type of installation. Backup fuses of 16 A should be used for the PU D.
B
3.1 Replacement If as described under point 3 above an arrester shows a red flag or red LED, it should be replaced by a qualified electrician. The individual class I and II and arresters are plug-in units and coded according to voltage. When performance in- sulation resistance tests to DIN VDE 0100 part 610, the varistor arresters must be removed, e.g. by lifting off the top section. The arrester must be replaced by one suitable for the rated voltage of the system. 4. Connecting the remote signalling 4.1 Remote signalling with monitoring module type PUxCR, PUxBR or PU D
≤ 35
50
≥ 70
10
26
25
Table 1 3. Checking the function A visual inspection of PU overvoltage protection devices and lightning arresters is especially important during storms. If the flag in the status window or the LED is red, the overvoltage protection device concerned must be replaced. Ageing of the varistors can lead to high temperatures in the varistors. This situation can cause fires in low-voltage systems. Therefore, in a hazardous situation the integral temperature monitoring automatically disconnects the varistor from the power supply. This disconnection is indicated by the warning lamp being extinguished, and in the PO DS or the PUxCR,
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies
The signalling contact of a PUxCR or PUxBR is a changeover contact and is connected to terminals 11 and 14. In normal operation (green flag) terminals 11/12 are closed. In this situation terminals 11/14 are open. In the case of a fault (red flag), terminals 11/14 are closed and 11/12 open. In the PU D the triggering of the disconnection device is signalled by the opening of an irreversible thermal release. The signalling circuit is connected with twisted lines (e.g. NYM); parallel routing with the connecting and earth lines must be avoided here. A protection circuit formed by an overvoltage fine protection corresponding to the voltage level reduces interference at and in the evaluator. 4.2 Remote signalling with photoelectric barrier type PU-O/S-E Every PU C and PU B arrester is suitable for use with remote monitoring and this can be retrofitted at any time. The transmitter must be clipped on to the top-hat rail to the left and the receiver to the right of the PU blocks and the devices connected to a 230 V supply.
B.41
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies
Afterwards, the remote signalling is connected to terminals 11/14 and/or 11/12, as already described under point 4.1 above. This system allows up to 40 overvoltage arresters to be monitored simultaneously. 4.3 Approvals
B
PUxC(R) for 230/400 V power supply networks to ÖVE SN 60 parts 1 and 4. PU units are provided with CE and UL symbols.
Accessories A system marker is available from LogiMark with the text “Warning! System protected by overvoltage arresters”. Lift off plug-in top section for insulation measurements. This yellow card (Part No. 175184 1687) can be affixed with self-adhesive tape. Installation specification for PU1 TSG “Overvoltage protection in power supply networks”. 1. Application The arrester serves as lightning protection equipotential bonding at the interface transition 0 to 1 (according to IEC 1312-1) in accordance with the requirements of class B to DIN VDE 0675 part 6 (draft, Nov 1989), A1 (Mar 1996) and the requirements of class I to IEC 61643-1 (Feb 1998). Combinations of several overvoltage arresters are frequently used as an N-PE arrester in TN, TT and IT systems. The PU 1 TSG 50 kA / 1.5 kV-260 V can be used in a combination circuit as a 50 kA sparkover gap between L and N in systems designed for a short-circuit current of 500 A. The use of a sealed sparkover gap satisfies the inspection requirements for class B overvoltage protection systems according to the VDEW directive (1st ed., 1998). 2. Installation instructions 2.1 Special installation conditions for metal distribution boards The following points should be taken into consideration when installing a PU x C: 1. The use of a plastic partition to separate it from adjacent metal parts. It is recommended to incorporate a WTW partition (Part No. 1058800000) or a WEW/2 end bracket (Part No. 1061200000). 2. The switching voltage of the PU x CR must be reduced to £ 48 V. 3. PU x C modules for Uc 550 V must always be closed with plastic covers. 2.2 Backup fuse The overvoltage protection devices of the PU series exhibit passive behaviour in normal operation; no current is consumed. The necessary protection against short-circuits and overloads is thus provided by a fuse designed for the type of installation and the cross-section of the connecting lines. In addition, the products of the PU series are tested with a maximum backup fuse (refer to technical data for details). If the fuse used in the installation is less than or equal to this value, then this can be used as the line protection in the incoming supply. However, if the fuse is larger than that given in the technical specification, additional fuses to suit the connecting line must be incorporated in the line to the PU module.
B.42
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies
2.3 Application PU 1 TSG (+) modules provide the necessary lightning protection equipotential bonding for existing lightning protection systems and incoming supplies. Enclosed PU 1 TSG modules are preferably installed in the distribution boards of the buildingâ&#x20AC;&#x2122;s electrical installation.
B
Unenclosed PU 1 TSG+ modules with voltages of 330 or 440 V are frequently installed in industrial applications. 3. Maintenance According to their applications, PU 1 TSG(+) modules are designed for high electrical mechanical loads. Faulty arresters must be replaced immediately. The arresters may not be opened. Installation specification for PU 1 TSG(+) overvoltage protection in power supply networks. May only be installed by qualified personnel. During the installation, please observe the connection conditions specific to the country of application.
B.43
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies Examples of applications in 230/400 V systems TN-C system applications
B Ordering data Class I (B arrester) Sparkover gap High-power varistor Class II (C arrester) Varistor Class III (D arrester Hybrid circuit Hybrid circuit
TN-C 230/400 V Type 3 x PU 1 TSG 35 kA/0.9 kA-260 V 1 x PU 3 B 20 kA in Summe Type PU 3 C Type PU DS PU D
Order No. 8561260000 8381890000 Order No. 8021490000 Order No. 8523740000 8411930000
Remarks No decoupling necessary Remarks Remarks Install behind RCD Install behind RCD
TN-C-S system applications
Ordering data Class I (B arrester) Sparkover gap or High-power varistor Class II (C arrester) Varistor Varistor Class III (D arrester) Hybrid circuit Hybrid circuit
TN-S system applications
B.44
TN-C-S 230/400 V with 3+1 circuit Type 3 x PU 1 TSG 35 kA/0.9 kA-260 V + 1 x PU 1 TSG 50 kA/0.9kA-260 V 1 x PU 4 B 25 kA Type PU 4 C TT 3+1 circuit PU 4 C Type PU DS PU D
Order No. 8561260000 8561230000 8381890000 Order No. 8416370000 8021500000 Order No. 8523740000 8411930000
Remarks No decoupling necessary as N-PE sparkover gap Install behind RCD Remarks Install behind RCD Remarks Install behind RCD Install behind RCD
Overvoltage Protection for low-voltage supplies
Overvoltage Protection for low-voltage supplies Examples of applications in 230/400 V systems TT system applications
B Ordering data Class I (B arrester) Sparkover gap High-power varistor Class II (C arrester) Varistor Varistor Class III (D arrester) Hybrid circuit Hybrid circuit
TT 230/400 V with 3+1 circuit Type 3 x PU 1 TSG 35 kA/0.9 kA-260 V + 1 x PU 1 TSG 50 kA/0.9kA-260 V 1 x PU 3 B 20 kA + 1 x PU 1 TSG Type PU 4 C TT 3+1 circuit PU 4 C Type PU DS PU D
Order No. 8561260000 8561230000 8381890000 Order No. 8416370000 8021500000 Order No. 8523740000 8411930000
Remarks No decoupling necessary as N-PE sparkover gap Install behind RCD Remarks Install behind RCD Remarks Install behind RCD Install behind RCD
IT system applications
Ordering data Class I (B arrester) Sparkover gap High-power varistor Class II (C arrester) Varistor Varistor Class III (D arrester) Hybrid circuit Hybrid circuit
IT 230/400 V with 3+1 circuit Type 3 x PU 1 TSG 35 kA/0.9 kA-260 V + 1 x PU 1 TSG 50 kA/0.9 kA-260 V 1 x PU 3 B 20 kA Type PU 4 C TT 3+1 circuit PU 4 C Type PU DS PU D
Order No. 8561260000 8561230000 8381890000 Order No. 8416370000 8021500000 Order No. 8523740000 8411930000
Remarks No decoupling necessary as N-PE sparkover gap Install behind RCD Remarks Install behind RCD Remarks Install behind RCD Install behind RCD
B.45
B
B.46
Overvoltage Protection for low-voltage supplies